GRX-IRPS-WH Infrared Transmitter/Receiver Pair (Class 2 Device) Specifications • Operating voltage: Low-voltage Class 2 (PELV) 12 V~ from GRX-12VDC plug-in power supply (ordered separately). One GRX-12VDC can supply power to five sensor transmitter/receiver pairs. • Transmitter and receiver have reverse polarity and short-circuit protection. • Receiver includes an LED indicator that assists in sensor alignment during installation and sensor operating status. • Each GRX-AV or OMX-AV interface (ordered sep- arately) can accommodate up to five transmitter/receiver pairs for five different move- able walls. • 32 -104°F (0 - 40°C). Relative humidity less than 90% non-condensing. • Surface mount indoors only. Installation Instructions Please Read Description Infrared transmitter/receiver pair automatically coor- dinates lighting preset functions in areas with parti- tions (example: partitioned meeting rooms and ball- rooms). Sensors may be used with any GRAFIK Eye 3000 or 4000 systems as well as GRAFIK Eye Centralized Lighting Control Systems. • Automatically combines lighting preset functions when partition is open creating one large space. • Lighting preset functions become independent as partition is closed creating several smaller spaces. Sensors require additional Lutron interface (GRX-AV or OMX-AV) and power supply (GRX-12VDC) for proper operation. Important Notes 1. Read all instructions carefully before starting installation. 2. This device must be installed by a qualified electrician. 3. Install in accordance with the National Electric Code ® and all applicable local regulations. 4. Turn power OFF at the control panel before installing the device. Do not connect high-volt- age power to low voltage terminals. Improper wiring can result in personal injury or damage to the device or to other equipment. GRX-IRPS-WH ®
Transcript

GRX-IRPS-WH InfraredTransmitter/Receiver Pair(Class 2 Device)

Specifications• Operating voltage: Low-voltage Class 2 (PELV) 12

V~ from GRX-12VDC plug-in power supply(ordered separately). One GRX-12VDC can supplypower to five sensor transmitter/receiver pairs.

• Transmitter and receiver have reverse polarity andshort-circuit protection.

• Receiver includes an LED indicator that assists insensor alignment during installation and sensoroperating status.

• Each GRX-AV or OMX-AV interface (ordered sep-arately) can accommodate up to fivetransmitter/receiver pairs for five different move-able walls.

• 32-104°F (0 - 40°C). Relative humidity less than90% non-condensing.

• Surface mount indoors only.

Installation InstructionsPlease Read

DescriptionInfrared transmitter/receiver pair automatically coor-dinates lighting preset functions in areas with parti-tions (example: partitioned meeting rooms and ball-rooms). Sensors may be used with any GRAFIKEye 3000 or 4000 systems as well as GRAFIK EyeCentralized Lighting Control Systems.• Automatically combines lighting preset functions

when partition is open creating one large space.• Lighting preset functions become independent as

partition is closed creating several smallerspaces.

Sensors require additional Lutron interface (GRX-AVor OMX-AV) and power supply (GRX-12VDC) forproper operation.

Important Notes1. Read all instructions carefully before starting

installation.2. This device must be installed by a qualified

electrician.3. Install in accordance with the National Electric

Code® and all applicable local regulations.4. Turn power OFF at the control panel before

installing the device. Do not connect high-volt-age power to low voltage terminals. Improperwiring can result in personal injury or damage tothe device or to other equipment.

GRX-IRPS-WH

®

Side View

Standard single-gang U.S. wallbox mountedfacedown and flush with ceiling surface (typicalof two).

8 ft. (243 mm) maximum)

1.5 in. (38.1 mm)

GRX-IRPS-WHReceiver

GRX-IRPS-WHTransmitter

Partition

Ceiling

Dimensions and MountingReceiver and transmitter surface mount in 1-gang U.S. wallboxes 3.5 in. (89 mm) deep mounted face-down from the ceiling. Indoors only.• The sensors must be mounted in a position where the partition separates the transmitter and receiver

when the partition is closed.• Transmitter and receiver may be located no more than 8 ft. (2430 mm) apart.• Adjustable mounting brackets allow easy alignment during installation.• Wires feed through the back of the transmitter/receiver.

LUTRON LUTRON

1 2 3 4 5 6 7 8

MUX LINK INPUTS OUTPUTS

CO

M +V

MU

X

PR

OG

RA

MS

WIT

CH

CO

M

CO

M

C 1 2 3 4 5 1 2 3 4 5 C1 2 3 4

MU

X

MUX LINK INPUTS OUTPUTSC 1 2 3 4 5 1 2 3 4 5 C1 2 3 4

0 = ON; 1 = OFF

1 2 3 4

0 0 0 00 0 0 10 0 1 00 0 1 1

1 2 3 4

1 1 0 01 1 0 11 1 1 01 1 1 1

1 2 3 4

1 0 0 01 0 0 11 0 1 01 0 1 1

1 2 3 4

0 1 0 00 1 0 10 1 1 00 1 1 1

ADDRESS

1234

ADDRESS

13141516

ADDRESS

9101112

ADDRESS

5678

DIP SWITCH SETTINGS (1-4)

DIP SWITCH SETTINGS (5-8)

TYPE DIP SETTINGCONFIGURATION

ADDRESS

CONFIG.

TYPE

1 2 3 4 5 6 7 8

ON

OFF

GRX-AVINTERFACE CONTROL

SELV(CLASS 2:USA)COOPERSBURG, PA 18036

4S CONTROL SCENES 1-4, MAINTAIN OUTPUTS 5 ON 6 ONSCENES 5-8, MAINTAIN OUTPUTS 5 OFF 6 ON

7 ON 8 ON SCENES 9-12, MAINTAIN OUTPUTS 5 ON 6 OFFSCENES 13-16, MAINTAIN OUTPUTS 5 OFF 6 OFF

4S CONTROL SCENES 1-4, MOMENTARY OUTPUTS 5 ON 6 ONSCENES 5-8, MOMENTARY OUTPUTS 5 OFF 6 ON

7 ON 8 OFF SCENES 9-12, MOMENTARY OUTPUTS 5 ON 6 OFFSCENES 13-16, MOMENTARY OUTPUTS 5 OFF 6 OFF

4Q CONTROL SEQUENCE 1-4, MAINTAIN INPUTS 5 OFF 6 ONSEQUENCE 1-4, MOMENTARY INPUTS 5 ON 6 ON

7 OFF 8 OFF SEQUENCE 5-16, MAINTAIN INPUTS 6 OFF 6 OFFSEQUENCE 5-16, MOMENTARY INPUTS 6 ON 6 OFF

4PS CONTROL PARTITION STATUS, MOMENTARY INPUTS 5 ON 6 ON7 OFF 8 ON PARTITION STATUS, MAINTAINED INPUTS 5 OFF 6 ON

SPECIAL OCCUPANCY SENSOR - SCENE 1 & OFF 5 ON 6 OFFCONTROL OCCUPANCY SENSOR - OFF ONLY 5 OFF 6 OFF7 OFF 8 ON

SELV (CLASS 2:USA)

R

R

System Diagram

GRX-IRPS ReceiverGRX-IRPS Transmitter

Room A Room B

Partition

GRX-12VDC

Wallstations Wallstations

GRX/OMX-AV

Class 2/PELV Control Link

Ceiling

2 GRX-IRPS-WH Infrared Transmitter/Receiver Pair

Top View

Single gang wallbox(typical of two)

Wallbox mountingline of center

WiringWARNING: Always turn off the power to the control panel before doing any work. Failure to do so

can result in serious personal injury and damage to equipment.

1. Turn power OFF.2. Strip insulation from wires so 3/8" (10 mm) bare wire is exposed.3. Gently squeeze the sides of the GRX-IRPS cover and remove to expose the sensor mounting bracket.

Unsnap the plastic faceplate.4. Connect wiring as shown in the Wiring Diagram (next page). Confirm all connections.5. Attach the device to the ceiling-mounted wallbox - Do not fully tighten the screws6. Plug in the GRX-12VDC to apply power to the transmitter and receiver. Note: Do not restore power to

the control panel until after the installation of the system is complete.7. Verify that the Transmitter and Receiver are properly aligned (the movable partition must be OPEN to

allow the beam to travel from the Transmitter to the Receiver). A Green LED should be lit on theTransmitter to indicate that it is properly powered and transmitting. Adjust the horizontal and verticalalignment of the units until they are aligned.Receiver LED(s) lit:— Amber. Indicates that a strong signal is being received.— Amber and Red. Receiver is partially misaligned, improper functionality may occur.— Red. Receiver is misaligned, improper functionality will occur.— No LED. Receiver is completely misaligned and no signal is being received.

8. Close and re-open the movable partition to verify that the LEDs on the receiver turn OFF when thepartition is closed and ON when the partition is re-opened.

9. Tighten all screws and verify that the Amber LED on the receiver is still on.10. Snap the faceplate onto the unit.11. Snap the cover over the sensor.12. Restore power to the control panel.

GRX-IRPS-WH Infrared Transmitter/Receiver Pair 3

Internet: www.lutron.comE-mail: [email protected]

WORLD HEADQUARTERSLutron Electronics Co. Inc.,TOLL FREE: 1.800.523.9466(U.S.A., Canada, portions ofCaribbean)Tel: 1.610.282.3800Fax: 1.610.282.3090

GREAT BRITAINLutron EA Ltd.,Tel: +44.207.702.0657Fax: +44.207.480.6899

GERMANYLutron Electronics GmbHTel: +49.309.710.4590Fax: +49.309.710.4591

JAPAN SALES OFFICELutron Asuka CorporationTel: +813.5405.7333Fax: +813.5405.7496

HONG KONG SALES OFFICELutron GL (Hong Kong)Tel: +852.2104.7733Fax: +852.2104.7633

SINGAPORELutron GL (Singapore)Tel: +65.220.4666Fax: +65.220.4333

LIMITED WARRANTYLutron will, at its option, repair or replace any unit that is defective in mate-rials or manufacture within one year after purchase. For warranty service,return unit to place of purchase or mail to Lutron at 7200 Suter Rd.,Coopersburg, PA 18036-1299, postage pre-paid.This warranty is in lieu of all other express warranties, and the implied war-ranty of merchantability is limited to one year from purchase. This warrantydoes not cover the cost of installation, removal, or reinstallation, or damageresulting from misuse, abuse, or improper or incorrect repair, or damagefrom improper wiring or installation. This warranty does not cover incidentalor consequential damages. Lutron’s liability on any claim for damages aris-ing out of or in connection with the manufacture, sale, installation, delivery,or use of the unit shall never exceed the purchase price of the unit.This warranty gives you specific legal rights, and you may also have otherrights which vary from state to state. Some states do not allow limitations onhow long an implied warranty lasts, so the above limitation may not apply toyou. Some states do not allow the exclusion or limitation of incidental orconsequential damages, so the above limitation or exclusion may not applyto you.This product may be covered under one or more of the following U.S.patents: 4,803,380; 4,835,343; 4,924,349 and corresponding foreignpatents.Lutron and Nova T and design are registered trademarks of Lutron Electron-ics Co., Inc.National Electric Code is a registered trademark of the National FireProtection Association, Inc., Quincy, Massachusetts.© 2005 Lutron Electronics Co., Inc.

Lutron Electronics Co., Inc.Made and printed in U.S.A.P/N 040-XXX 4/05

3OUTPUTS

C 5421 3INPUTS

21 4 5 C

GRX-AV* or OMX-AV(ordered separately)

Twist-onConnector

Black Wire withWhite Trace (+)

Solid Black Wire (-)

6 ft. (1829 mm)Cable

GRX-12VDC12V Power Supply(ordered separately)

RECEIVER

SINGLE-GANGBACKBOX

BLU

E

BR

OW

N

BLA

CK

BLU

E

BR

OW

N

TRANSMITTER

* GRX-AV is programmed for partition mode. Set input closuresfor maintained inputs (refer to GRX-AV installation instructions).

Note: Drawing represents a single partition. GRX-AV/OMX-AV will accomodate up to five sets of sensors (five parti-tions). A single GRX-12VDC will power up to five GRX-IRPS sensors.

SINGLE-GANGBACKBOX

Wiring Diagram


Recommended