Page 1 of 6 TECHNICAL DATA SCHEDULE TRANSFORMER 40/50/60 MVA, 132/34.5kV ITEM DESCRIPTION UNITS REQUIRED GUARANTEED 1.0 Manufacturer - - T & R (I) LTD 1.1 Type - Three-phase with 2 windings Three-phase with 2 windings 1.2 Class - Power X’mer 2.0 Rated data and characteristics 2.1 Rated power: - primary/secondary MVA 40/50/60 40/50/60 2.2 Cooling - ONAN/ONAF/ONAF ONAN/ONAF1/ ONAF2 2.3 Rated voltage - HV winding - LV winding kV kV 132 34.5 132 34.5 2.4 Tap changer: - manufacturer - model - type - on-load tap changer location - regulating range - rating - - % - MR M III 500 CFVV HV neutral 132 kV +4 x 1.25% -12 x 1.25% Rated power on all taps Huaming CM III 500 Y High speed, transition resistor HV neutral 132 kv +4x1.25% -12x1.25% Rated power on all taps 2.5 Frequency Hz 50 50 2.6 Connection of the three-phase windings (group of vectors IEC 76) - YNd11 YNd11 2.7 Rated current at ONAF rated power and rated voltage tap: - HV winding - LV winding A A 263 1004.1 262.43@60M 1004.1 2.8 No-load current through: - HV winding - LV winding A A - - 0.5% of Rated full load current (Approx) 2.9 Short circuit impedance Base: rated voltage and 60 MVA Base: rated voltage and 60 MVA TRANSFORMER, 40/50/60 MVA, 132/34.5KV
Transcript
Page 1: GTP-R1 TR 60MVA

Page 1 of 6

TECHNICAL DATA SCHEDULE

TRANSFORMER 40/50/60 MVA, 132/34.5kV

ITEM DESCRIPTION UNITS REQUIRED GUARANTEED

1.0 Manufacturer - - T & R (I) LTD

1.1 Type - Three-phase with 2 windings

Three-phase with 2 windings

1.2 Class - Power X’mer

2.0 Rated data and characteristics

2.1 Rated power:

- primary/secondary

MVA

40/50/60

40/50/60

2.2 Cooling - ONAN/ONAF/ONAF ONAN/ONAF1/ ONAF2

2.3 Rated voltage

- HV winding - LV winding

kV kV

132 34.5

132 34.5

2.4 Tap changer:

- manufacturer

- model - type - on-load tap changer location

- regulating range - rating

-

-

% -

MR

M III 500 CFVV

HV neutral 132 kV

+4 x 1.25% -12 x 1.25%

Rated power on all taps

Huaming

CM III 500 Y High speed, transition resistor

HV neutral 132 kv +4x1.25% -12x1.25% Rated power on all taps

2.5 Frequency Hz 50 50

2.6 Connection of the three-phase windings (group of vectors IEC 76)

- YNd11 YNd11

2.7 Rated current at ONAF rated power and rated voltage tap:

- HV winding - LV winding

A A

263 1004.1

262.43@60M 1004.1

2.8 No-load current through:

- HV winding - LV winding

A A

- -

0.5% of Rated full load current (Approx)

2.9 Short circuit impedance Base: rated voltage and 60

MVA

Base: rated voltage and 60 MVA

TRANSFORMER, 40/50/60 MVA, 132/34.5KV

harshj
Typewritten text
Date: 10.12.2014
harshj
Stamp
harshj
Typewritten text
Rev-R1
Page 2: GTP-R1 TR 60MVA

Page 2 of 6

TECHNICAL DATA SCHEDULE

TRANSFORMER 40/50/60 MVA, 132/34.5kV

ITEM DESCRIPTION UNITS REQUIRED GUARANTEED

2.9.1 Direct impedance at nominal voltage tap:

- HV/LV

%

10

10% (Sub. To Tolerance)@60 MVA

2.9.2 Direct impedance at minimum voltage tap:

- HV/LV

%

-

9.25%(Approx)

2.9.3 Direct impedance at maximum voltage tap:

- HV/LV

%

-

10.3%(Approx)

2.9.4 Zero sequence impedance at nominal voltage tap

- HV / LV % - 9.0%(Approx)

2.10 Tolerance to be applied to the short circuit impedance, in terms of % of the guaranteed value on:

- nominal voltage tap - other taps

% %

±7.5 ±10

±7.5 ±10

2.11 Transformer capacity to withstand external short circuits:

2.11.1 Short circuit duration s 2 2

2.11.2 Symmetrical short circuit current withstand during the indicated period and asymmetrical short circuit withstand:

- HV winding kA RMS kA (peak)

- -

2.9 (Approx) 7.4(Approx)

- LV winding kA RMS kA (peak)

6.06(Approx) 15.5(Approx)

- tertiary winding kA RMS kA (peak)

- NA

- pre-fault voltage p.u. 1.05 1.05

2.12 Guaranteed losses

2.12.1 No-load losses at rated voltage and frequency, with rated voltage tap

kW - 32.0 (Max)

2.12.2 No-load losses at 110% of the rated voltage, at rated frequency and rated voltage tap

kW - 45.0 (Approx)

2.12.3 No-load losses capitalized value US $/kW 3000 3000

2.12.4 Tolerance to be applied to no-load losses (in % of the guaranteed value)

% 10 0%, Max Loss Specified

harshj
Stamp
Page 3: GTP-R1 TR 60MVA

Page 3 of 6

TECHNICAL DATA SCHEDULE

TRANSFORMER 40/50/60 MVA, 132/34.5kV

ITEM DESCRIPTION UNITS REQUIRED GUARANTEED

2.12.5 On-load losses at rated voltage and frequency, with rated voltage tap and ONAN rating: - HV winding - LV winding – tertiary winding

kW kW kW

- - -

112 @ 40MVA 247.5@60 MVA NA

2.12.6 On-load losses capitalized value US $/kW 1080 1080

2.12.7 Tolerance to be applied to total losses (in %of the guaranteed value) for all the windings

% 10 0%, Max Loss Specified

2.12.8 Auxiliaries consumption at second stage of cooling (ONAF/ONAF)

kW - 4 KW

2.13 Highest voltage for equipment:

- HV winding - LV winding

kV kV

145 36

145 36

2.14

2.14.1

Rated insulation level:

Short time power frequency withstand:

- HV winding - line terminal - LV winding - line terminal - neutral - control wiring

kV RMS kV RMS kV RMS kV RMS

230 70 38 2.0

230 70 38 2.0

2.14.2 Basic impulse level:

- HV winding - line terminal - LV winding - line terminal - neutral point

kV (peak) kV (peak) kV (peak)

550 145 95

550 145 95

2.15 Temperature rise limits at maximum power output at ONAN and ONAF ratings and at lowest voltage tap and corresponding voltage:

- top oil at ambient temperature - average copper at ambient temperature

oC oC

60 65

60 65

2.16 Permissible overload in emergency cases:

- permanent permissible overload based on highest winding temperature which exceeds by 5oC the guaranteed limit

MVA

As per IEC-60076-7

- permanent permissible over voltage based on the maximum top oil temperature which exceeds by 5oC the guaranteed limit at rated power (in % of the rated voltage)

% As per IEC-60076-7

harshj
Stamp
Page 4: GTP-R1 TR 60MVA

Page 4 of 6

TECHNICAL DATA SCHEDULE

TRANSFORMER 40/50/60 MVA, 132/34.5kV

ITEM DESCRIPTION UNITS REQUIRED GUARANTEED

2.17 Oil:

- manufacturer

- type - data sheet attached

- - -

PCB prohibited

- - -

PCB provided Apar/Savita or equi.

As per IEC-296

2.18 Bushings

2.18.1 HV bushings:

- class - manufacturer - type designation - rated current

- short circuit withstand - basic insulation level - power frequency withstand for 1 minute - connectors for - leakage distance

kV - - A

kA RMS

kV(peak) kV RMS - mm

145 - - - -

650 275 TBA

As per pollution level of site

145 ABB/ALSTOM/ CGL or equi. 800 A 25 times the rated current for 2 sec 650 275 - 3625 mm

2.18.2 LV bushings:

- class - manufacturer - type designation - rated current - short circuit withstand

- basic insulation level

- power frequency withstand for 1 minute - connectors for - leakage distance

kV - - A

KA RMS

kV (peak)

kV RMS

- mm

36 - - - -

170

70 TBA

As per pollution level of site

36 GENESIS/CJI or equi. Porcelain type 2000 A 25 times the rated current for 2 sec. 170 70 - 900 mm

2.18.3 Neutral bushings:

- class - manufacturer

- type designation - rated current - short circuit withstand

- basic insulation level

- power frequency withstand for 1 minute - connectors for

kV -

- A

kA RMS

kV (peak)

kV RMS

24 -

- - -

125

50 –

52 GENESIS/CJI/ or equi. Porcelain type 1000 A 25 times the rated current foe 2 sec 125 50 -

harshj
Stamp
Page 5: GTP-R1 TR 60MVA

Page 5 of 6

TECHNICAL DATA SCHEDULE

TRANSFORMER 40/50/60 MVA, 132/34.5kV

ITEM DESCRIPTION UNITS REQUIRED GUARANTEED

- leakage distance mm As per pollution level at site

1300 mm

2.19

2.19.1

Design data:

Maximum flux density in the columns at:

- rated voltage - 105% of the rated voltage

tesla tesla

- -

1.6 T 1.68 T

2.19.2 Maximum flux density in the yokes at:

- rated voltage - 105% of the rated voltage

tesla tesla

- -

1.6 T 1.68 T

2.19.3 Maximum current density at ONAN rated power and rated voltage tap:

- HV winding

- LV winding

A/mm2

A/mm2

-

-

< 3.5 at ONAF2 A/mm2

< 3.5 at ONAF2 A/mm2

2.19.4 Winding resistance:

- HV winding - LV winding

ohms ohms

- -

0.61 ohm/ph. (Approx) 0.095 ohm/ph. (Approx)

2.19.5 Voltage regulation at ONAN rating and rated voltage tap (in % of the rated voltage):

- with unity power factor: . LV side . TV side

% %

- -

0.50@ 40 MVA NA

- with 0.9 power factor (lagging): . LV side . TV side

% %

- -

3.33 @ 40MVA NA

- with 0.8 power factor (lagging): . LV side . TV side

% %

- -

4.36 @ 40 MVA NA

2.19.6 Primary exciting current, LV side:

- at 0.01 second - at 0.1 second

kA kA

- -

0.5 % of rated current (Exciting current)

2.19.7 Core type (core or shell) - - Core

2.19.8 Winding conductor - Copper Copper

2.20 Audible noise level

- Voltage in percent of rated value - ONAN rating - ONAF maximum rating

% dB(A) dB(A)

105 75 max 78 max

105 75 max 78 max

2.21 Radio Interference Voltage at 0.5 MHz µV 2500 max 2500 max

harshj
Stamp
Page 6: GTP-R1 TR 60MVA

Page 6 of 6

TECHNICAL DATA SCHEDULE

TRANSFORMER 40/50/60 MVA, 132/34.5kV

ITEM DESCRIPTION UNITS REQUIRED GUARANTEED

as per IEC 694

3.0 Weights and dimensions

3.1 Total weight of transformer, equipped for service

kg - 77000(approx)

3.2 Weight:

- oil - core and coil assembling - tank and accessories - net copper

- net core steel

kg kg kg kg

kg

- - - - -

17000(approx) 40000(approx) 20000(approx) 8250(approx) WITH INSULATION 28000(approx)

3.3 Maximum shipping weight (heaviest item) kg - 70000(approx) Oil Filled

3.4 Height from foundation to:

- highest point of HV bushing - highest point of tank - highest point of conservator tank - highest point of lifting hook to remove core and coil assembly

mm mm mm

mm

- - - -

As per Attached GA Drawing

3.5 Outline dimensions:

- length - width

mm mm

- -

3.6 Layout drawing no - To be enclosed with bid

3.7 Maximum shipping dimensions of tank: - outside height - outside width - outside length

mm mm mm

- - -

harshj
Stamp