GU601A Controller Operation Manual
1
The clarification of no tation used within th is manual:
WARNING:A WARNING indicates a potentially hazardous situationwhich, if not avoided, could result in death, seriouspersonal injury or property damage.
CAUTION:
A CAUTION indicates a potentially hazardous situationwhich, if not avoided, could result in damage toequipment or property.
NOTE:A NOTEprovides other helpful information that does notfall under the warning o r caution categories.
7/24/2019 GU601A-EN0507.pdf
2/30
GU601A Controller Operation Manual
2
WARNING:Read this entire manual pertaining to the work to beperformed before installing, operating, or servicing thiscontroller. Practice all plant and safety instructions andprecautions. Failure to follow instructions can causepersonal injury and/or property damage.
The engine or other type of prime mover should beequipped with an overspeed shutdown device to protect
against runaway or damage to the prime mover withpossible personal injury, loss of l ife, or property damage.
The overspeed shutdown device must be totallyindependent of the prime mover control system. Anovertemperature or overpressure shutdown device mayalso be needed for safety, as appropr iate.
CAUTIONBATTERY CHARGINGTo prevent damage to a contro ller that uses an alternator orbattery-charging device, make sure the charging device isturned off before disconnecting the battery from thesystem.
Controllers contain static-sensitive parts. Observe thefollowing precautions to prevent damage to these parts:
Do not disassemble the rear back of contro ller and touchthe components or conductors on a printed circuit board.
7/24/2019 GU601A-EN0507.pdf
3/30
GU601A Controller Operation Manual
3
Contents
1. Descr ip tion ...........................................................................................4
2. The Outline Dimensional Drawings and Wirings of Controller ......5
3. Operation Panel ............................ .............................. ................................8
4. Instal lat ion Guide ........................................................................................10
5. Cont rol and Operation Instruct ion ............................................................11
6. Measure and Display Data ......................................................................16
7. Warni ng and Shutdown Alar m ......................................................16
8. Paramet ers Sett ing ..........................................................................20
9. LCD Displ ay and Menu Syst em....................................................24
10. Preparation before Start the Controller..................................................27
11. Troubleshooting .......................................................................................28
12. Technical Parameters.................................................................................30
7/24/2019 GU601A-EN0507.pdf
4/30
GU601A Controller Operation Manual
4
1. Descript ion
GU601A is an auto control and protection module of generator. The control modes
of manual or auto are selectable by buttons on panel. Manual starts or stops
Genset under manual mode by buttons on panel. Auto starts or stops Genset
under auto mode by remote switch input signal. The module is adopted LCD, which
displays running status and operating parameters of generator. The main
characteristics as following:
The core adopts MPU.
Flexible configure running parameters via buttons and LCD on panel.
Measure and display parameters, such as frequency and voltage for generator;
battery voltage; oil pressure, coolant temp and running hours for engine.
The fuel mode (NC or NO) of engine can be set by procedure.
Has five relays control output, others can be defined by user except the
outputs of fuel and start control are fixed.
5 channels for switch input, others can be defined by user except the inputs of
oil pressure and coolant temperature are fixed.
Internal kinds of P-sensor and T-sensor for user choice.
Optional internal communication interface can be used to configureparameters via PC.
All connections are connected by pin-like and locked up terminal, easier and more
convenient to connect, move, maintain and replace the device.
This manual only suitable for GU601A generator automatic controller, user must
carefully see this manual first.
7/24/2019 GU601A-EN0507.pdf
5/30
GU601A Controller Operation Manual
5
2. The Outline Dimensional Drawings and Wirings of Controller
2.1 Following Details:
Operation Panel W88mmH75mm
Install Cutout W78mm H65mm
Thickness D48mmunconnected
7/24/2019 GU601A-EN0507.pdf
6/30
GU601A Controller Operation Manual
6
2.2 Connect ing Terminals:
Pin no. Function Description Signal Dim
1 phase voltage input 1mm
2 neutral0-300Vac
1mm
3 P-sensor or switch signal P-sensor (
7/24/2019 GU601A-EN0507.pdf
7/30
GU601A Controller Operation Manual
7
2.3 Typical Wiring Diagram
(12/24V)
LOAD
G
U601A
CONFIG.
OUTPUT
FUEL
C
RANK
DC
POWER
OILPRESSURE
COOLANTTEMP.
CONFIG.
INPUT
A fuse with the rating of 10A shall be provided external to the equipment.
7/24/2019 GU601A-EN0507.pdf
8/30
GU601A Controller Operation Manual
8
3. Operation Panel
The whole operation panel includes 3 sections: LCD displays measuringparameters, indicator light for common failure, and control buttons and selectbuttons for control modes.
LCD cycle displays different measuring parameters. When failure occurs LCDdisplays corresponding sign. LCD has background-light function so that operatorcan clearly read information whenever at day or night. After pressing any buttons
the background-light will auto turn off in a certain time.
LCD display and its control buttons provide a friendly operation interface foroperator, which makes operator conveniently read information and set runningparameter.
3.1 Contro l buttons and LED
Function Description Tag
Enter into submenu/modify/confirm modification/scroll menu
AUTO button/ LED
The button is used for setting auto-operation mode. When
controller is running in AUTO mode, LED above the button lights
up. According to the remote start signal is active or not, to control
generator start or stop.
MAN button /LED
The button is used for setting manual-operation mode. When
controller is running in MAN mode, LED above the button lights
up. The controller controls generator start and stop by pressing
START and STOP buttons.
START/ VALUE ASCEND + button for parameters setting
The button is used for MAN start Genset. When controller is
setting in MAN-operation mode, press this button can start
generator. When enter in parameters setting operation, this button
is used for value ascend.
7/24/2019 GU601A-EN0507.pdf
9/30
GU601A Controller Operation Manual
9
STOP/ RESET / VALUE DESCEND
The button is used for MAN stop Genset. When controller issetting in MAN-operation mode, continuously press this buttonmore than 2s can stop generator.
If occur failure output, light press this button, the shutdown lockoutcan be cleared by controller.
When enter in parameters setting operation, this button is used forvalue descend.
FAILURE LED
When controller occur warning, failure LED flash.When controller occur shutdown alarm, failure LED lights up.
7/24/2019 GU601A-EN0507.pdf
10/30
7/24/2019 GU601A-EN0507.pdf
11/30
GU601A Controller Operation Manual
11
5. Control and Operation Instruction
The controller has 2 kinds of control mode: AUTO mode and MAN mode.
5.1 Operation Mode Setting:
Operation Description
Press AUTO button (continue 2s), LED
above the button lights up; controller is
running in AUTO mode.
Press MAN button (continue 2s), LED
above the button lights up; controller is
running in MAN mode.
NOTE: Only can select 1 mode from above 2 modes.
5.2 AUTO Control Process:
The controller is running in AUTO mode.
First of all, define one of the configurable inputs as Remote Start Signal.
When detects that the remote signal is active, the controller implements following procedure:
Start-delay timer begins count, when delay time out, if preset preheat function,preheat relay making output, the timer for preheat time begins count, when timeexpired, fuel relay takes action, the fuel solenoid of engine opened, after 300ms delay,the start relay making output, the start motor of engine switches on power, begincrank, when the running speed of engine is reach to the crank disconnect speed,controller stop start-output, the safety-on delay time begin count, before time out, ifcontroller detects that parameters of Genset such as voltage, frequency, oil pressure,coolant temperature are normal, and no other failure, means Genset successfullystart and running normal, LCD displays corresponding measuring parameters.
NOTE: When remote signal is active, the timer for start-relay begins
count. During counting, if remote start signal is inactive, thestart-relay stop counting immediately, controller stop startprocedure and related output, recover to original standbystatus.
During the period of crank or idle, if remote start signal isinactive, controller stop start procedure and related output,recover to original standby status.
1 configurable input must be set as Remote Start Signal, orwill not process start procedure under AUTOmode.
7/24/2019 GU601A-EN0507.pdf
12/30
GU601A Controller Operation Manual
12
NOTE: During crank, engine ignition, when the output frequency of
alternator is reaches to preset frequency, start motordisconnect power. Or the start motor is disconnected powerby one of the following reasons: the output voltage ofalternator is reaches to 80% rating voltage; start time over.After the low oil pressure switch of engine opening, delaycounting time out.
Controller can not implement idle procedure, when it detectsthat the frequency of generator is reached the preset level, or
the oil pressure switch of engine is open.
CAUTION
Since the crank disconnect signal of engine is from the output voltagefrequency of generator, must make sure the output voltage is greaterthan controller measurable voltage during the period of generatorcrank attempt, to avoid the possible damage on start motor.
If preset idle function, simultaneously the start relay making output, the relay whichis defined for idle function making output, the timers for idle delay and safety-ontime delay begins count together, the shorter delay will be displayed first, thefollowing procedure as above.
During crank counting time, engine can not igniting, and controller will not output start
signal during crank intermission, and the Fail to Start Sign in LCD flashing at that time.Once crank intermission time out, controller will attempt to restart engine again.
Above start phenomena repeat again and again until engine successful ignition andor reach the preset crank times. If any stop failures occur during start process,controller stops control output immediately, until failure eliminated and reset, then itcan be operated again.
Fail to start: When above start phenomena repeat again and again and over thepreset crank times, controller will stop control output, failure LED lights up, and LCDstatus bar displays Fail to Start Sign.
CAUTION
If occur start failure, operator must check the whole Gensetsystem to make sure failure reason, only after eliminating thefailure can press STOP/RESET button to unlock fault-lockedstatus, and restart the Genset.
7/24/2019 GU601A-EN0507.pdf
13/30
GU601A Controller Operation Manual
13
The process of generator shutdown:
When remote signal is not active, the timer for cooling delay begins counting, when
time expired, the fuel relay of controller takes action, breaking fuel solenoid
immediately, generator stop and enter into standby status.
Fail to stop: When cooling-delay expired, the fuel relay of controller takes action,the timer for fail to stop delay begins counting, when time expired, if controller detectsthat the voltage and frequency of generator is greater than the internal setting value,or the oil pressure of engine is greater than the internal setting value, failure LED
for Fail to stop lights up, LCD displays Fail to stopicon.
NOTE:When occur fail to stop, except failures were removed and reset orcan not restart generator.
5.3 The produce of MAN cont rol:
The controller is running in MAN mode.
The process of generator start supply:
Press START button, fuel relay takes action, the fuel solenoid of engine opened,after 300ms delay, the start relay making output, the start motor of engine switcheson power, begin crank, when the running speed of engine is reach to the crank
disconnect speed, controller stop start-output, the safety-on delay time begin count,before time out, if controller detects that parameters of Genset such as voltage,frequency, oil pressure, coolant temperature are normal, and no other failure,means Genset successfully start and running normal, LCD displays correspondingmeasuring parameters.
5.4 The start and stop processes of engine, which fuel solenoid is N. O. type:
Start contro l process:
When start running, the fuel relay of controller will not close, fuel solenoid no power,means the electromagnet of solenoid no action.
Stop control process:
When controller starts at stop control process, the fuel relay of controller is close,
fuel solenoid on load, fuel solenoid take action, engine begins stop. After delay(same as fail to stop delay) fuel relay breaking, disconnect the power of fuelsolenoid.
Other control process same as engine fuel solenoid is N. C. type.
7/24/2019 GU601A-EN0507.pdf
14/30
GU601A Controller Operation Manual
14
5.5 Idle function:
When one of the configurable outputs is defined as Idle, controller has idle controlfunction immediately.
The idle control flow reference to the flow chart for start and stop.
5.6 Preheat func tion :
When one of the configurable outputs is defined as Preheat, controller obtainspreheat control function immediately. Controller has 3 optional preheat control modes:
Mode 1 during preheat time, preheat relay making output.Mode 2 during preheat time, preheat relay making output until successfully
ignition.Mode 3 during preheat time, preheat relay making output until safety-on
delay expired.
No matter setting at which mode, during crank attempt the preheat relay will notmaking output.
The idle control flow reference to the flow chart for start and stop.
7/24/2019 GU601A-EN0507.pdf
15/30
GU601A Controller Operation Manual
15
5.7 Flow chart for start and stop
T1start delay
T2crank time
T3preheat time
T4safety-on time
T5idle time
T6fail to stop delay
NOTE:
When T4>T5 and engine is under the period of idle, the protection
of low oil pressure will not operation; When T4
7/24/2019 GU601A-EN0507.pdf
16/30
GU601A Controller Operation Manual
16
6. Measure and Display DataThe AC phase voltage of generator VacGenerator frequency HzEngine speed RPM(signal from generator frequency)Battery voltage VdcEngine running hours hEngine coolant temperature /F(signal from engine T-sensor)Engine oil pressure BAR /PSI (signal from engine P-sensor)
7. Warning and Shutdown Alarm
7.1 Warning
(NOTE:Warns are non-critical failure conditions and do not affect the operation ofthe generator system, they serve to draw the operators attention to an undesirablecondition and remove it to make sure system continuous running. When warnsoccur, the status indicator light flash, but failure will not be locked and the unit willnot shutdown. Once failure removed warning indicator auto turn off.)
Warning/ Description LCD Display
Fail to Charge: if controller detects that voltagehas fallen below the low battery warning valuefrom the excitation contact of auxiliary AC chargerafter the safety-on timer has expired, failureindicator light flash, LCD displays Fail to Chargeicon.Battery Low Voltage: if controller detects thatbattery voltage has fallen below the low batterywarning value, failure indicator lights up. Forexample, low battery warning value preset as:23.6V, when battery voltage falls below this value,LCD flashing low value icon.Battery High Voltage: if controller detects thatbattery voltage has exceeded the high batterywarning value, failure indicator lights up. Forexample, high battery warning value preset as:28.2V, when battery voltage exceeds this value,LCD flashing high value icon.
Low Oil Pressure: if controller detects that theengine oil pressure has fallen below the low oilpressure warning value after the safety-on timerhas expired, failure indicator light flash. Forexample, low oil pressure warning value presetas: 2.20BAR, when engine oil pressure falls belowthis value, LCD flashing low value icon.
7/24/2019 GU601A-EN0507.pdf
17/30
GU601A Controller Operation Manual
17
High Temperature: if controller detects that
engine coolant temperature has exceeded the
high coolant temperature warning value, failure
indicator lights up. For example, high coolant
temperature warning value preset as: 95,
when engine coolant temperature exceeds this
value, LCD flashing high value icon.
Overspeed: if engine speed exceeds the
overspeed warning value, failure indicator lightsup. For example, overspeed warning value preset
as: 1600RPM, when engine speed exceeds this
value, LCD flashing high value icon.
Underspeed: if engine speed falls below the
underspeed warning value after the safety-on
timer has expired, failure indicator lights up. For
example, underspeed warning value preset as:
1440RPM, when engine speed falls below this
value, LCD flashing low value icon.
High Voltage: if controller detects that the voltage of
generator any phase output has exceeded the high
voltage warning value after the safety-on timer has
expired, failure indicator light flash.For example, rating
voltage preset as: 220A, high voltage warning value
preset as: 115%, when the generator output voltage
exceeds this value, LCD flashing high value icon for
corresponding phase.
Low Voltage: if controller detects that the voltage of
generator any phase output has fallen below the low
voltage warning value after the safety-on timer has
expired, failure indicator light flash. For example,
rating voltage preset as: 220A, low voltage warning
value preset as: 90%, when the generator output
voltage falls below this value, LCD flashing low value
icon for corresponding phase.
Auxi liary Warning: define a configurable switch as
warning input, when the input signal is active, failure
indicator light flash.LCD flashing Aux. warning icon.
7/24/2019 GU601A-EN0507.pdf
18/30
GU601A Controller Operation Manual
18
Note:
To make warnings of low oil pressure and high coolant temperature
active, must use P-sensor and T-sensor, when only use oil pressure
switch and temperature switch, both warnings inactive.
Caution:Under the period of safety-on delay, some warnings are inactive,the safety-on time must be carefully and properly set to makeGenset has full protection.
7.2 Shutdown Alarm
(NOTE: shutdown failures immediately lock system and stop generator, it only canoperate controller again after removing failures and press rest button to unlock)
Failures/ Description LCD Display
Fail to Start: if engine does not fire after the
preset number of crank attempts has been made,
means fail to start, failure LED lights up. LCD
displays fail to start icon.
Fail to Stop: if engine does not stop after the
stop delay expires, failure LED lights up. LCDdisplays fail to stop icon.
Emergency Stop: define a configurable switch as
emergency stop input, when the input signal is
active, controller immediately stop all relay control
output except alarm, failure LED lights up. LCD
displays emergency stop icon.
Low Oil Pressure: if controller detects that the oil
pressure level still falls below oil pressure alarm
value or oil pressure switch is closing after the
safety-on timer has expired, engine stop
immediately, failure LED lights up.LCD displays lowoil pressure icon.
High Temperature: if controller detects that engine
coolant temperature has exceeded the high coolant
temperature alarm value or temperature switch is
closing, engine stop immediately, and failure LED
lights up.LCD displays high temperature icon.
7/24/2019 GU601A-EN0507.pdf
19/30
GU601A Controller Operation Manual
19
Overspeed: if controller detects that engine speedexceeds the overspeed alarm value, engine stopimmediately, and failure LED lights up.LCD displaysoverspeed icon.
Auxi liary Failure: define a configurable switch as
failure input, when the input signal is active, failure
LED lights up.LCD displays Aux. warning icon.
Note:
Engine speed signal is from generator output voltage
frequency, is used for control and failure protection
parameters, to the convenience of user, some data
expressed by RPM, RPM=HZ*60/pair of poles.
The generator occur failure during its operating: stop
immediately no delay after occurred high temperature, low oil
pressure and overspeed; protection is active whatever has
idle function or not when low oil pressure occurs during
coolant delay.
Caution:Under the period of safety-on delay, the protection of low oil pressurefailure is inactive, to avoid non oil start engine, must make sure the oilis normal and the safety-on time shall be carefully and properly set forthe first commissioning.
7/24/2019 GU601A-EN0507.pdf
20/30
GU601A Controller Operation Manual
20
8. Parameters Setting
8.1 System Parameters:
NO. Items Preset Value Range
1.1 voltage ratio 1.0 1.0-100.0
1.2 rating voltage 220 45-9999Vac
1.3 begin control mode 0 0-1 / 0 (AUTO) /1 (MAN)
1.4 oil pressure units 0 0-2(0-BAR,1-PSI, 2-all displayed)
1.5 temperature units 00-2
(0-,1-,2- all displayed)
1.6communicationaddress
1 1-247
1.7 resume to default
1.8 on-line update
1.9 page scroll time 0S 0-10S /0 (not used)
NOTE:Begin Control Mode is used for the setting the begin controlmode of controller when controller switches on power. When the
parameter set at 1 and controller switches on power, controllerwill auto operating in AUTO control mode; When the parameter setat 0 and controller switches on power, controller will autooperating in MAN control mode.
NOTE:Generator running speed is set by pair of poles, RPM=HZ*60/ pairof poles, when rating frequency is 50 HZ, if pole pairs set at 2,the running speed is 1500 rpm, if pole pairs set at 1 , the runningspeed is 3000 rpm.
8.2 Generator Parameters:
NO. Items Preset Value Range
2.1 V low alarm 0 20-200% / 0 (not set)2.2 V low warning 90% 20-200% / 0 (not set)
2.3 V high warning 115% 20-200% / 9999 (not set)
2.4 V high alarm 9999 20-200% / 9999 (not set)
2.5 Failure delay 10S 0-600S
7/24/2019 GU601A-EN0507.pdf
21/30
GU601A Controller Operation Manual
21
8.3 Engine Parameters:
NO. Items Preset Value Range
3.1 pair of poles 2 1-4
3.2 fuel mode 0 0-1 / 0(NC) /1 (NO)
3.3 T-sensor mode 3 0-10 / 0 (not use)
3.4 P-sensor mode 3 0-11 / 0 (not use)
3.5 start delay 10S 0-300 S3.6 crank attempt 3 times 1-10 times
3.7 crank time 8S 0-30 S
3.8 crank rest 15s 0-300 s
3.9 crank disconnect 300RPM 1-9999 RPM
3.10 preheat delay 3S 0-300 S
3.11 preheat mode 1 1-3
3.12 idle delay 0 0-9999s
3.13 safety on delay 10S 0-600S
3.14 cooling delay 300S 0-600 S
3.15 fail to stop delay 20S 0-60S
3.16 underspeed alarm 0RPM 0-9999 RPM / 0 (not set)
3.17 Underspeed warning 1440RPM 0-9999 RPM / 0 (not set)
3.18 overspeed warning 1600 RPM 1-9999 RPM / 9999 (not set)
3.19 overspeed alarm 1710 RPM 1-9999 RPM/ 9999 (not set)
3.20 low oil-press alarm 1.4BAR 0-45.0 BAR
3.21 low oil-press warning 2.2BAR 0-45.0BAR
3.22 high temp warning 95 70-320 / 9999 (not set)
3.23 high temp alarm 105 70-320 / 9999 (not set)
3.24 low battery warning 8.0V 1-25.0V / 0 (not set)3.25 high battery warning 28.0V 1-35.0V / 99.9 (not set)
3.26 charge V warning 8.0V 1-25.0V / 0 (not set)
7/24/2019 GU601A-EN0507.pdf
22/30
GU601A Controller Operation Manual
22
8.4 Input and Output Setting
4.1 configurable input 1 8 0-12 (define code as follows)
4.2 configurable input 2 7 0-12 (define code as follows)
4.3 configurable input 3 12 0-12 (define code as follows)
4.4 input 1 delay 2S 0-60S
4.5 input 2 delay 2S 0-60S
4.6 input 3 delay 2S 0-60S
4.7 configurable relay 1 2 0-80 (define code as follows)
4.8 configurable relay 2 3 0-80 (define code as follows)
4.9 configurable relay 3 5 0-80 (define code as follows)
NOTE: configurable input delay is only for 1 to 4 codes in 8.7.
8.5 Calibration Menu
5.1 Gen voltage V1 0 10.0
5.2 oil pressure 0 10.0
5.3 coolant temp 0 10.0
5.4 battery voltage 0 10.0
8.6 The optional items for PT-sensor:
Code The brand model of P-sensor The brand model of T-sensor
0 not used not used
1 close for low oil pressure close for high temperature
2 open for low oil pressure open for high temperature
3 VDO 10 bar VDO 120 degrees C
4 KD 10 bar KD KD 120 dc KD
5 YG962 1J1M ZJ WGJ 900131 ZJ
6 KP 6 bar KP KP 130 dc KP
7 3846 N-010-B2 DX 21YB054 DX
8 3967251 KL 3967250 KL9 MHI 10 bar SL MHI 98 dc SL
10 Datcon 10 bar configurable (base on sensor data)
11 configurable (base on sensor data)
7/24/2019 GU601A-EN0507.pdf
23/30
GU601A Controller Operation Manual
23
Note:
When controller leave factory, the optional model and function of
P-sensor and T-sensor have been preset as above table, if the
used sensor not listed in table, user can select the item of
configurable, read-in sensor parameters to controller by software.
8.7 The optional items for configurable inpu t:
Code Optional Funct ion NOTE
0 not used1 warning (active immediately) low level is active
2 alarm (active immediately) low level is active
3warning(active after safety-on delay)
low level is active
4alarm(active after safety-on delay)
low level is active
5 low oil pressure low level is active
6 high temperature low level is active
7 emergency stop low level is active
8 remote start low level is active
9 reserved low level is active
10 reserved low level is active
11 low fuel level low level is active12 lamp test low level is active
8.8 The optional items for configurable output:
Code Failure Type Define Code Failure Type Define
0 Not used 1 Over current tripping
2 Alarm 3 Warning
4 Idle 0 (NC) 5 Preheat mode
6 Speed up 7 Reserved
8 Fuel pump control 9 Running
10 System in AUTO mode 11 Reserved
12 System in MAN mode 13 Reserved
14 Idle 1 (NO) 15 Reserved
16 Reserved 17 Fail to start
Note:Define one of the configurable outputs as Speed Up, aftercontroller detects that engine is successfully crank, speed up relaymaking output; if has idle function, then speed up relay makingoutput after idle delay expired.
7/24/2019 GU601A-EN0507.pdf
24/30
GU601A Controller Operation Manual
24
9. LCD Display and Menu System
Adopt TN type LCD displays data information, and LCD has background-light
function, after pressing any buttons the background-light will auto turn off in a
certain time. In normal operating status, auto scroll page to cycle display each
measuring data, also can press scroll to view each measuring data, when
failure occurs, LCD flashing the corresponding failure icon.
Continuously press button 2s in any page enter into setting status, you canuse or in the same grade menu to scroll page at that moment, press
again enter into submenu, select the desired item to be modified, press
or enter into modify, displays 0 0 0 0 when prompt key in password,
you can use or to modify value at that moment, press move to
modify lower value, the first value will be displayed as asterisk * after moved to
right, press again for exit after the password was set to 2213, and
parameters have been changed, otherwise prompted key in password again,
Continuously press button 2s after modification can exit the setting status.
9.1 Static LCD disp lays:
When controller standby:
Operation Description
Controller only displays detected batteryvoltage and running hour, LCD displays:
When controller normal running, cycle displays each measuring data:
(AC voltagefrequencyrunning houroil pressurecoolant temperaturebattery voltagespeed)
7/24/2019 GU601A-EN0507.pdf
25/30
GU601A Controller Operation Manual
25
9.2 Setting runn ing parameters
For example: (setting VT rate at 2.0)
Operation Description
Continuously press 2s, enter into parameters setting menu,then LCD display:
press , then LCD display:
press , then LCD display:
Press or key in modified password: (2213),press ,then LCD display:
Press or change parameter, change at 2.0, then LCDdisplay:
After changing press to confirmthen press and ,
then LCD display:
Press again for quit, or continuously press more that 2salso can quit:
For example: (setting controller crank attempt at 2)
Operation Description
Continuously press 2s, enter into parameters setting menu,then LCD display:
Press 19 times, then LCD display:
Press again, then LCD display:
Press then LCD display:
Press or key in modified password: (2213),press ,then LCD display:
Press or change parameter, change at 2, Press
confirm change, and then continuously press 2s can quit
parameters setting menu.
7/24/2019 GU601A-EN0507.pdf
26/30
GU601A Controller Operation Manual
26
For example: (resume all parameters of controller to factory default)
Operation Description
Continuously press 2s, enter into parameters setting menu,
then LCD display:
Press 6 times again, then LCD display:
press , prompt enter password, then LCD display:
Press or key in modified password: (2213),press ,
then LCD display:
Press recover default, continuous press 2s can quit
parameters setting menu.
For example: (set controller as online program mode)
Operation Description
Continuously press 2s, enter into parameters setting menu,
then LCD display:
Press 7 times, then LCD display:
Press 1 times again, then LCD display:
Press or key in modified password: (3132)ess , then
LCD display:
Press again enter into program mode, in this mode the
power supply must be make sure normal, after connecting to the
communication line, using special program software correctly
duplication, controller will auto repeat reset action, or will not quit
this status, until switch off plant supply.
7/24/2019 GU601A-EN0507.pdf
27/30
GU601A Controller Operation Manual
27
10. Preparation before Start the Control ler
10.1 Make sure controller is fixed well and its install ambient meet requirements.
10.2 Confirm all wiring connections of controller are meet electric specification andcorresponding to 2.3 typical wiring diagram. Especially need confirm DCsupply source has added fusing element to protect, and correct polarity.Otherwise, it maybe damage controller.
10.3 We recommend mounting E- stop button in external, connecting E-stopsignal input terminal to the N. O. contact of E- stop button, and anotherterminal of contact connected to the negative of battery source.
10.4 Switch on DC plant supply, make sure the preset parameter meet practicalcondition, such as P-sensor mode, T-sensor mode, etc.
7/24/2019 GU601A-EN0507.pdf
28/30
GU601A Controller Operation Manual
28
11. Troubleshoot ing
Failure Phenomenon Failure Eliminate
Genset no
crank
No crank attempteither in MANmode pressSTART buttonor in AUTO
mode the remotestart signal isactive.
1. Check failure LED, or check LCD display toconfirm has failure display or not.
2. Check DC voltage on controller no. 14terminal, if no voltage, check related circuitryfuse. Such as low voltage, use charger chargingbattery, restart after battery fully charging.
3. Check DC voltage on controller no. 9
terminal when crank, if no voltage, needchange controller.
4. Check starting motor normal operating or not,if not change it.
Diesel fail
o start
Controller LCDdisplay: fail tostart, dieselrotates but cannot start or dieselstop after startoperating.
1. Check fuel level.2. Check DC voltage on controller no. 8
terminal, if no voltage need change controller.3. Check the connection of fuel control magnet
and the voltage on magnet.4. Check fuse on the side of alternator.5. Both check fuel manifold and filter jam or not.6. If has white smoke release from exhaust
system, means fuel has gone into engine, butdiesel not start. Please refer to DieselManual for further check.
7. If low ambient temp and has heat startfunction, please preheat first.
8. Once failure removed, press RESET buttonto reset control system.
Diesel
high
temp
shutdown
Controller LCD
display high temp
failure icon,
common failure
LED lights up.
1. Check the mode of controller T-sensorcorrectly set or not, if error need reset.
2. Check radiator jam or not.3. Check fan belt loose or tighten.4. Check if ambient temperature meets
generator usage range.5. After diesel cooling, check coolant position, do
not add a great deal of coolant into diesel before itis not cooling, or will cause serious damage to it.
6. Refer to Diesel Manual7. Once failure removed, press RESET button
to reset control system.
Low oil
pressure
shutdown
Controller LCDdisplay low oilpressure failureicon, commonfailure LED lightsup.
1. Check the mode of controller P-sensorcorrectly set or not, if error need reset.
2. Check fuel level, if oil not enough, add oil.3. Refer to Diesel Manual4. Check oil pressure switch by test meter, if
any problems change it.5. Once failure removed, press RESET
button to reset control system.
7/24/2019 GU601A-EN0507.pdf
29/30
GU601A Controller Operation Manual
29
Diesel
overspeed
shutdown
Controller LCD
display overspeed
failure icon,
common failure
LED lights up.
1. Check governor speed shaft moved or not,if moved correct it.
2. If installed electronics governor, check iflevel shaft can freely move, correct it ifnecessary.
3. Refer to Diesel Manual.4. Once failure removed, press RESET
button to reset control system.
Under-
speed
shutdown
LCD display low
frequency failure
1. Check the frequency input value ofmagnetic pickup on controller correctly
set or not, if error need reset.2. Check supply fuels enough or not.3. Check governor speed shaft moved or
not, if moved correct it.4. If installed electronics governor, check if
level shaft can freely move, correct it ifnecessary.
5. Adjust diesel speed when it is running.6. Check the parameters setting for
underspeed failure right or not.
Low
voltage
shutdown
LCD display low
voltage failure
1. Switch off load on alternator, remove failureafter shutdown and restart unit.
2. Check the setting value of Gen low voltagefailure, make sure correct data.
3. If voltage still low, adjust generator output
voltage by setting potentiometer to recover tonormal value.
4. Refer to Alternator Manual
High
voltage
shutdown
LCD display high
voltage failure
1. Switch off load on alternator, remove failureafter shutdown and restart unit.
2. Check the setting value of Gen high voltagefailure, make sure correct data.
3. Check the measuring voltage of controller, ifvoltage normal, check load and make sure itis non capacitive (power factor compensationdevice will casual cause a capacitive load).
4. If voltage still low, adjust generator outputvoltage by setting potentiometer to recover tonormal value.
5. Refer to Alternator Manual
Engine
fail not
stop
Generator still
running after stop,
LCD display fail to
stop failure
1. Check fuel solenoid valve on diesel (or levelshaft), make sure oil channel is completelyclosed under close status.
2. Check fuel control solenoid valve, change it ifnecessary.
7/24/2019 GU601A-EN0507.pdf
30/30
GU601A Controller Operation Manual
30
12. Technical Parameters
DC supply: 8.0V to 35V continuous
Max. operating current: @12V 150mA, @24V 75mA
AC input voltage: phase voltage15~300 Vac RMS (AC frequency 40 Hz)
AC input frequency: 3~70Hz (voltage15V)
Control relay output: 3A/30Vdc
Operating ambient temperature: -20 to 70
Storage ambient temperature: -30 to 80
Version070A090507