Automation & Controlp.2 switch disconnectors
p.3 contactors
p.4 latching relays
p.5-6 electromechanical time switches
p.7 digital time switches
p.8 twilight switches
p.9 delay timmers
p.10 time lag switches
p.11 pushbuttons
p.12 pushbuttons and indicator lights
p.13 transformers, bells and buzzers
p.14 analogue voltmeters and ammeters
- digital voltmeters and ammeters
p.15 selector switches for voltmeters and ammeters
current transformers (C.T.)
p.16 kilowatt hour meter and hours counter
2
SB499S
switch disconnectors
descriptionfor use as a switch disconnectorin all types of circuit. Complieswith: BSEN 60 947-3
BS 5419 -1977
technical dataAC 22 duty specification: BS 5419-1977
In : 25, 32Ashrouded cable clamps, connection capacity:10 mm2 – rigid conductor.6 mm2 – flexible conductor.
In : 40, 63, 80Acable clamps, connection capacity:25mm2 – rigid conductor.16mm2 – flexible conductor.
In : 100Acable clamps, connection capacity:50 mm2 – rigid conductor.35 mm2 – flexible conductor.All switches have a green / redmechanical indication giving a positive contact indication:
- version with pilot light for 25-32A SP/DP switches.
optionhandle link pin
designation characteristics width in I pack cat.
17.5mm qty. ref.
single pole 1 x 25A 250V~ 1 12 SB116S
1 x 32A 250V~ 1 12 SB132S
1 x 63A 250V~ 1 12 SB163S
1 x 80A 250V~ 1 12 SB177S
1 x 100A 250V~ 1 12 SB197S
double pole 2 x 32A 400V~ 1 12 SB232S
2 x 40A 400V~ 2 6 SB240S
2 x 63A 400V~ 2 6 SB263S
2 x 80A 400V~ 2 1 SB280S
2 x 100A 400V~ 2 1 SB299S
triple pole 3 x 25A 400V~ 2 6 SB316S
3 x 32A 400V~ 2 6 SB332S
3 x 40A 400V~ 3 4 SB340S
3 x 63A 400V~ 3 4 SB363S
3 x 80A 400V~ 3 1 SB380S
3 x 100A 400V~ 3 1 SB399S
3 x 125A 400V~ * 1 JK125S
3 x 160A 400V~ * 1 JK160S
3 x 200A 400V~ * 1 JK200S
four pole 4 x 25A 400V~ 2 6 SB416S
with indicator 4 x 32A 400V~ 2 6 SB432S
4 x 40A 400V~ 4 3 SB440S
4 x 63A 400V~ 4 3 SB463S
4 x 80A 400V~ 4 1 SB480S
4 x 100A 400V~ 4 1 SB499S
* please consult us
SB116S
SB240S
SB399S
JK200S
3
contactors
descriptioncontactors for the remoteswitching and control of powercircuits (20A-63A AC1)
technical datathe choice of contactor dependsupon a number of parameters,e.g.– the nature of the supply.– the power it is switching.– the characteristics of the load.– the control voltage required.
All contactors ratings are forAC1 loads only – if the load dif-fers from AC1 the contactor mayneed de-rating. Derating information can be obtainedfrom Hager Engineers at thenearest Regional Centre.
The use of LZ060 (heat dissipation inserts) between allcontactors installed or betweencontactors and adjacent devicesis recommended.
optionscontact choice– normally open (NO)– normally closed (NC)
LZ060 heat dissipation inserts.
ES237 and ES238 low noise version available.
auxiliary20A contactors will accept auxiliary, EP071 contact.
• for technical information see page 19
designation type coil power width in I pack cat.circuit AC1 17.5mm qty. ref.
2 NO 230V 50 Hz 20A - 250V~ 1 12 ES220
40A - 400V~ 3 4 ES240
63A - 400V~ 3 4 ES263
3 NO 230V 50 Hz 20A - 400V~ 2 6 ES320
40A - 400V~ 3 4 ES340
63A - 400V~ 3 4 ES365auxiliary contact 1 NC (10A)
4 NO 230V 50 Hz 20A - 400V~ 2 6 ES420
40A - 400V~ 3 4 ES440
63A - 400V~ 3 4 ES463
auxiliary for 20A contactors 2A - 250V~ 1/2 1 EP071
heat dissipation insert 1/2 10 LZ060
ES463
ES320
ES230
4
latching relays
descriptionlatching relays - operate whenimpulsed by a signal voltage. The impulse can be provided via a pushbutton or switch. The firstpulse operates the relay andlatches it into its set (opposite)state, the next operation of thepushbutton returns the relay intoits reset (original) state.
auxiliary contacts (EP070, EP071) are available for remotesignalling applications and canbe easily combined with thelatching relays.connection: 10mm2 flexible
6mm2 rigid
• for technical information see page 20
designation type coil power width in I pack cat.circuit 17.5mm qty. ref.
latching relays 1 NO 230V 50 Hz 16A - 250V~ 1 12 EP510
24V 50 Hz 16A - 250V~ 1 12 EP513
2 NO 230V 50 Hz 16A - 250V~ 1 12 EP520
24V 50 Hz 16A - 250V~ 1 12 EP524
1 NC + 1 NO 230V 50 Hz 16A - 250V~ 1 12 EP515
24V 50 Hz 16A - 250V~ 1 12 EP518
12V 50 Hz 16A - 250V~ 1 12 EP519
2 NC + 2 NO 230V 50 Hz 16A - 250V~ 2 6 EP525
24V 50 Hz 16A - 250V~ 2 6 EP528
12V 50 Hz 16A - 250V~ 2 6 EP529
4 NO 230V 50 Hz 16A - 400V~ 2 6 EP540
24V 50 Hz 16A - 400V~ 2 6 EP541
designation voltage power width in I pack cat.circuit 17.5mm qty. ref.
auxiliary contact 2A - 250V~ 1/2 1 EP071
EP510
EP541
EP071
5
electromechanical time switches
description:electromechanical time switches1 channel for daily or weeklyprogramming.to control lighting, heating,household appliances, shop win-dows etc.- to improve comfort and saveenergy.Applications: domesticcommercial premises
Din rail mounting technical data:- programming by captivesegments.manual override:on 1 module devices:- automatic- permanent ONon 3 and 5 modules devices:- automatic- permanent ON
- permanent OFFminimum switching time:- 15 min for daily versions- 2 hours for weekly version- 15 min and 2 hours on thedaily + weekly version
connection capacity:1 to 4 mm2
complies with EN 60730
designation characteristics width in I pack cat.17.5mm qty ref.
1 channel voltage supply: 230V50/60Hz
daily dial output:without battery reserve 1M devices= 1N/O 1 1 EH010
16A - 250V AC1
3M devices = 1 3 1 EH110changeover16A - 250V AC1
1 channel voltage supply: 230V50/60Hz
daily dial output:with battery reserve 1M devices = 1NO 1 1 EH011
16A - 250V AC1
reserve: 3M devices = 1 3 1 EH111200 hours after being changeoverconnected for 120 hours 16A - 250V AC1
1 channel voltage supply: 230V50/60Hz
weekly dial output: with battery reserve 1 changeover 3 1 EH171
16A - 250V AC1reserve:200 hours after being connected for 120 hours
1 channel voltage supply: 230V50/60Hz
daily + weekly dial outputwith battery reserve 1 changeover 5 1 EH191
16A - 250V AC1reserve:200 hours after being connected for 120 hours
EH 111
EH 011
6
electromechanical time switches
description:for daily or weekly programming.1 channel for the control oflighting, heating, householdappliances, shop windows etc...to improve comfort and saveenergy.application: domestic commer-cial premises.
technical data:- suitable for surface, flush ordin rail mounting- programming by captive seg-ments- manual override with automaticreturn to programme- operating reserve: 200h afterbeing connected for 120h- output: voltage freechangeover contact 16A/250V
daily version:programming in steps of 10minutes.- minimum time between 2switching intervals: 20minutes
weekly version:programming in steps of onehour.- minimum time between 2switching intervals: 2 hours- switching accuracy: 10 mincomplies with EN60730
designation characteristics pack cat.qty ref.
1 channel daily cycle supply: 230V 50/60Hz
without battery reserve 1 EH710
with battery reserve 1 EH711
Economy version (1 NO contact) 1 EH712
1 channel weekly cycle supply: 230V 50/60Hz
without battery reserve 1 EH770
with battery reserve 1 EH771
1 channel daily cycle supply: 48V DC 110 to 230V 50/60Hz
without battery reserve 1 EH715
with battery reserve 1 EH716
11
56
EH 711
EH 771
7
digital time switches
description:for the control of lighting, schoolbells (EG171), pumps, heating,household appliances, shop win-dows etc...
- to improve comfort and saveenergy
applications: domestic, schools,colleges and commercialpremises
technical data:1, 2 or 4 channel :- programming in 1 minuteincrements- easy programming- display and control of theprogram- possibility to override the output (permanent or temporary)- operating reserve:lithium battery total of threeyears.
- output: changeover contacts16A -250V AC1- sealable front cover
connection capacity:1 to 4 mm2
complies with EN 60730
designation characteristics width in I pack cat.
17.5mm qty. ref
1 channel daily cycle 5 adjustable pre-recor- 1 1 EG010
-ded programs: 6 com-
-mutations per day
230V 50/60 Hz
1 channel daily cycle capacity: 20 program 3 1 EG110
steps. 230V 50/60Hz
2 channel daily cycle capacity: 20 program 3 1 EG210
steps to be divided
between the 2 channels
110/230V 50/60 Hz
1 channel weekly cycle capacity: 20 program 1 1 EG071
steps. 230V 50/60 Hz
1 channel weekly cycle capacity: 20 program 3 1 EG170
steps. 230V 50/60Hz
1 channel weekly cycle capacity: 20 program 3 1 EG172
steps. 12V AC/DC
1 channel weekly cycle capacity: 20 program 3 1 EG171
pulsed output steps. 230V 50/60Hz
pulsed output adjustable
from 1 sec. to 99 mins.
2 channel weekly cycle capacity: 20 program 3 1 EG270
steps to be divided be-
-tween the 2 channels
110/230V 50/60Hz
4 channel weekly cycle capacity: 84 program 5 1 EG470
steps to be divided
between the 4 channels
230V 50/60Hz
EG 210
EG 071
8
description:The light sensitive switch con-trols light systems according todaylight level:- the user sets the switchinglevel- the photo cell measures theexternal light level.
applications: domestic and com-mercial premises
technical data:supply: 230V +10%-15% 50Hz1 changeover contact 16A 250Vselection switch:5 to 100 lux50 to 2000 lux4 position override switch allow-ing:-auto: normal operation mode- on: permanently switched-on- off: permanently switched-off-test: setting mode for easy
adjustmenta light indicator when installingshows the status “on” of thecontact
complies with EN 60730
designation characteristics width in I cat.
17.5mm ref
twilight switch 3 EE100
with surface cell
twilight switch 3 EE101
with flush cell
programmable twilight daily cycle / electromech. switch 5 EE110
switch with flush cell
programmable twilight weekly cycle / electronical program 3 EE170
switch with flush cell
flush cell IP54 for EE100, 101,110 & 170 EE002
surface cell IP54 for EE100, 101,110 & 170 EE003
twilight switches
EE 170
EE 110
EE 002
9
delay timers
descriptionto provide all types of automaticcontrol i.e. lighting, ventilation,watering, machine pre-heating,automatic door and visual audible indication, cycle controletc.
applicationsfor timing and automation indomestic and commercial premises. The input signal canbe via various switching devices (pushbutton, latching switch, timeclock etc.) and the timedoutput used to control the appli-cation.
technical datavoltage range:12 & 24 to 48V DC12 & 24 to 230V ACadjustable:time delay from 0.1s to 10hrs.Led indicator complies with EN 60669-2-1terminal capacity:6mm2 max rigid1.5mm - 10mm2 flexible
• for technical information see page 25 - 26
designation characteristics width in I pack cat.17.5mm qty. ref.
delay on 1 c/o contact 1 1 EZ00110A / 230V~ ACtime delay T: 0.1s to 10hr
adjustable time on 1 c/o contact 1 1 EZ00310A / 230V~ ACtime delay T: 0.1s to 10hr
delay off 1 c/o contact 1 1 EZ00210A / 230V~ ACtime delay T: 0.1s to 10hr
symmetrical flasher 1 c/o contact 1 1 EZ00510A / 230V~ ACtime delay T: 0.1s to 10hr
timer 1 c/o contact 1 1 EZ00410A / 230V~ ACtime delay T: 0.1s to 10hr
multifunction 1 c/o contact 1 1 EZ0066 individual functions 10A - 230V~ AC including: time delay T. 0.1s. to 10hdelay ondelay offtimersee page 28 for moreinformation
EZ001
EZ002
10
time lag switches
descriptionto provide control of lighting circuits with automatic switch-offafter a pre-set time(e.g.: staircase, corridors).command signal via impulse
technical data– time delay setting by rotating
thumbwheel dial on frontof device.
EM002 switch off notice add-on blockincorporating pre-warning ofswitch-off improves the safetyfor users / pre-warning ofswitch-off at the end of thetime delay,light intensity reduction by 50%for a period of 24 sec. prior tofinal switch off.use only on incandescentlighting circuits.
EM001 time lag switchfor lighting circuits (medium orhigh daily use)characteristic: compact designequipped with a 2 position dialpermanent/timed lightingimplementation facility.
note: this range is only suitablefor use with pushbuttons,not switches.
• for technical characteristics,see page 27
designation characteristics width in I pack cat.17.5 mm qty. ref.
time lag switch voltage rating: 1 6 EM001230V; - 50/60 Hzrestart facility
24 sec. to 12 min. 2 function switch:– permanent– timed
output: 1 changeover contact16 A - 230V; AC 110A - 2300W - incandescent10A - 2300W - halogen 230V10A - 2300W - on compact fluorescent
Note: Heat dissipation insert (LZ060) recommended between switch off notice & timer
Add-on block voltage rating: 2 1 EM002pre-warning 230V; - 50/60 Hzswitch off notice restart facility
pre-warning of switch-offby decrease of outputvoltage (50% for 24 sec.)
switch off notice: 24 secsoutput power:1000W - incandescent1000W - halogenEM002
EM001
11
pushbuttons
description
pushbuttonsto actuate loads either directly orvia contactors etc.
technical datamodular pushbuttons– without light with grey button, red/greenoptional
– with lightwith red, green button (amber,blue, colourless, red, green lens-es on option).delivered with neon lamp 240V~, E 10 cap.
optionspushbuttons can be fitted with 12, 24, 48, 60V lamps (see below).
shrouded cable clamp type, connection capacity:10mm2 rigid conductor.6mm2 flexible conductor.
designation characteristics width in I pack cat.17.5mm qty. ref.
pushbuttons 16A – 250V~without indicator light
contacts: 1 NO 1 12 SV021
contacts: 2 NO 1 12 SV022
contacts: 3 NO 1 12 SV025
contacts: 1 NC 1 12 SV023
contacts: 2 NC 1 12 SV024
contacts: 1 NO + 1 NC 1 12 SV120
contacts: 1NO + 1 NC 1 12 SV031
contacts: 2 changeover 1 12 SV026
pushbuttons with indicator light
contacts: 1NO green 1 12 SV124
contacts: 2 NO red 1 12 SV062
contacts: 1 NC red 1 12 SV123
contacts: 2 NC green 1 12 SV064
SV025
SV031
SV062
12
pushbuttons
indicator lights
modular indicator lightsavailable with red, green, amber,blue, colourless lensdelivered with neon lamp230V~, E10 cap
optionsindicator lights can be fitted with12, 24, 48, 60V lamps (seebelow)
shrouded cable clamp type, connection capacity:10mm2 rigid conductor.6mm2 flexib le conductor.
designation characteristics width in I pack cat.17.5mm qty. ref.
indicator lights 230V~ with light green 1 12 SV121
red 1 12 SV122
orange 1 12 SV126
clear 1 12 SV127
blue 1 12 SV128
designation characteristics width in I pack cat.17.5mm qty. ref.
pushbuttons 16A – 250V~without indicator lightcontacts: 1 NO 1 12 SV041
contacts: 2 NO 1 12 SV042
contacts: 3 NO 1 12 SV047
contacts: 4 NO 1 12 SV048
contacts: 1 NO + 1 NC 1 12 SV045
contacts: 2 changeover 1 12 SV046
with indicator lightcontacts: 1 NO green 1 12 SV071
contacts: 2 NO green 1 12 SV072
SV072
SV121 SV127 SV126SV122 SV128
13
transformers, bells and buzzers
descriptionProvide extra safety low voltage8, 12, 24V~.
technical datasecondary voltages: 8V, 12V, 24V~bell transformers are short-circuit protected.bells/buzzers:max. continuous duty≤ 30 minutes.connection capacities: 6 mm2
cable clamp typeoutput:bells: 85 dBAbuzzers: 78 dBA
When a bell transformer isinstalled in an enclosure withmains voltage equipment, 230Vcable should be used on thesecondary side of the trans-former or extra low voltage cableshould be sheathed within theenclosure.
note: the transformers have ahigher no load voltage.The stated voltages correspond to the voltages on nominalload.
∆ for technical information see page 29
designation characteristics width in I pack cat.17.5mm qty. ref.
safety transformers 16VA 50/60 Hz 4 3 ST313
230V/12-24V~ 25VA 50/60 Hz 4 3 ST31250Hz
40VA 50/60 HZ 4 1 ST314
60VA 50/60 Hz 6 2 ST315
bell transformers 230V/8V~ 50/60 Hz 2 6 ST3014VA - 8-12V : 0.33A
230V/8-12V~ 50/60 Hz 2 6 ST3038VA - 8V : 1A
12V : 0.67A
230V/8-12V~ 50/60 Hz 3 4 ST30516VA - 8V : 2A
12V : 1.33A24V : 0.67A
bells 8/12V~ 1 12 SU2124VA - 0.35A
230V~ 1 12 SU2136.5VA - 0.03A
buzzers 8/12V~ 1 12 SU2144VA - 0.35A
230V~ 1 12 SU2156.5VA - 0.03A
ST313
ST301
SU212
SU214
14
digital voltmetersSM501for domestic and commercialinstallations
three phase: use of avoltmeter selector switch SK602
digital ammetersSM151, SM401, SM601SM151: direct readingSM401, SM601: reading via acurrent transformer (see below)
• for detailed characteristics,see page 31
designation characteristics width in I pack cat.17.5 mm qty. ref.
digital voltmeters voltage rating:220/230V ; 50/60 Hzaccuracy: ± 1%consumption: 4 VA
scale: 0 - 500V
4 1 SM501
digital ammeters voltage rating:220/230V ; 50/60 Hzaccuracy: ± 1%consumption: 4 VA
–reading via CT 150/5A scale: 0 - 150A 4 1 SM151(SR150)
–reading via CT 400/5A scale: 0 - 400A 4 1 SM401(SR400)
–reading via CT 600/5A scale: 0 - 600A 4 1 SM601(SR600)
SM501
SM401
analogue voltmeters, ammeters
designation characteristics width in I pack cat.17.5 mm qty. ref.
voltmeter
3 1 SM500
ammeter accuracy: 2% or via a current transformer (CT) (page 33)
0 - 50A 1 SM050
0 - 100A 1 SM100
0 - 150A 1 SM150
0 - 250A 1 SM250
0 - 400A 1 SM400
0 - 600A 1 SM600
accuracy: 2%consumption: 2.5 VA0 - 500V
SM500
SM050
analogue voltmetersfor domestic and commercialinstallations
single phase:direct connectionthree phase: use of avoltmeter selector switchSK602 see page 64
frequency: 50 Hzconnection capacity:rigid conductor 10mm2
flexible conductor 6mm2
analogue ammetersfor domestic and commercialinstallations
direct reading:SM005: 0 - 5ASM015: 0 - 15ASM030: 0 - 30A
indirect reading via currenttransformers: 50-100-150-50-400-600A
• for detailed characteristics, `see page 31
digital voltmeters, ammeters
15
selector switches for voltmeters and ammeters
descriptionFor use with voltmeters andammeters.
applicationscomplies with IEC 947-3BSEN 60947-3.
terminal capacity 2.5mm2
isolating voltage 500Vacnominal current 10-20A
connecting capacityrigid conductor 1.5 to 10mm2
flexible conductor 1 to 6mm2
designation characteristics width in I pack cat.17.5mm qty. ref.
voltmeter selector 20A 400Vac 3 1 SK6023P&N3 readings between phases3 readings between phase & neutralnull position (no reading)
ammeter selector 20A 400Vac 3 1 SK6034 positionsuse in 3P&Nreading by phasenull position (no reading)should be used with current transformer (CT)see page 111
lockable rotary switch 10A 400Vac 3 1 SK6064 positions
SK602
SK603
SK606
current transformers (C.T.)
current transformers are used tofeed analogue and digitalammeters
Their current on secondarycircuit (0 - 5A) is proportionalto the current on primary circuitclass: 1
can be mounted on copper baror on cable
can be mounted on DIN rail withadaptors
∆ for detailed characteristics,see page 31
current transformers
(CT) ratio:
50/5 1 SR050
100/5 1 SR100
150/5 1 SR150
200/5 1 SR200
250/5 1 SR250
300/5 1 SR300
400/5 1 SR400
600/5 1 SR600
SR300
16
kilowatt hour meters and hours counter
descriptionkilowatt hour meters measurethe active energy used in anelectrical installation. The rangeincludes metres with pulsed outputs for remote indication orlinking into an energy management system. KwH meters can be used forlocal metering of installations or monitoring individual machines.The single phase meter offers 3 options:– total counter (non resettable)– resettable counter (shows
energy used since last reset)– watt meter (displays power as
it is used)
technical data2 types– for single phase (direct
reading)– for three phase (via a CT)
displaysthree phase - 6 digit roller typesingle phase - LCD
pulsed LED - 1 pulse = 1 Wh
optionssingle phase – without pulsed output
three phase– without pulsed output
single phase– with pulsed output
three phase– with pulsed output
• for technical information see page 32
designation characteristics width in I pack cat.17.5mm qty. ref.
kilowatt hour meter without pulsed output 7 1 EC010single phasevoltage 230V - 50Hzdirect connection In = 75mA - 90A with pulsed output 7 1 EC011
1 pulse = 1 Wh
kilowatt hour meter without pulsed output 7 1 EC030three phasevoltage 3 x 230/400V 50-60 Hzconnection via a currenttransformer (In/5A) with pulsed output 7 1 EC031ratio of 50/5 - 100/5200/5 - 300/5 - 400/5500/5 - 600/5 - 800/5 1 pulse = 1 Whsee page 34 for CT
hours counter
descriptionto measure the total operatingtime of any circuit/loadnon resettable
application example– total time of plant running– connection in parallel withcontactor coil– recording of lighting hours forrelamping purposes
designation characteristics width in I pack cat.17.5mm qty. ref.
kilowhours counter voltage ratings: 2 1 EC100230V - 50 Hz
EC010
EC100
technical information
p.18 choice of contactors
p.19-20 contactors and relays
p.21 latching relays- technical
p.22 technical data - analogue time switches
p.23 technical data 72 X 72mm
p.24 technical data - digital time switches
p.25-26 delay timers
p.27 time lag switches
p.28 technical data - twilight switches
p.29 transformers
p.30 voltmeters, ammeters and hours counters
p.31 voltmeters, ammeters and current transformers
p.32 kWh meters
18
choice of contactors
requirements of useinfluence of working temperature:derating factor between 40°C and 50°C : 0.9example: heating with convectorthe maximum load of ES220 is 4.4kW for 50,000 operations and for
a temperature <40°C.between 40°C and 50°C, the load is 4.4 x 0.9 i.e. 3.96kWclose fitting:it is necessary to put a heat dissipation insert (reference LZ060)between each contactor.
heatingthe choice of the contactor depends on the mechanical resistance(number of operations) and on the electrical heating load i.e. resistive elements, infra-red element, convectors.
choice of contactorsthe choice of contactor is dependant upon many parameters i.e. operating voltage, size of contacts, number of operations, ambient temperature, type of load supplied etc.
type of loadloads are categorised into various AC ratings, (AC1, AC2, AC3 etc.)and the higher the AC rating the more inductive the load becomes.All Hager contactor ratings are given at AC1, therefore they must bede-rated if used on other types of AC load.
heat dissipation insertsthe ambient temperature around a contactor can affect its lifeexpectancy, therefore, we strongly recommend that heat dissipationinserts (LZ060) are fitted between all contactors and adjacentdevices.
please consult your Local Regional Office, if you require helpselecting a suitable contactor.
single phase three phase
motors (AC3)single phase 230V three phase 400V three phase 400V
single phase with three phase choice of contactor accordingcapacitor (AC3 cat.) to control diagram230V 400V 2 wires 3 wires
1.1 ES220
maximum 2.2 ES240
load 4 ES320 - ES420
in kW 7.5 ES340 - ES345 - ES440
15 ES365 - ES463
* on three phase configuration the maximum load per phase corresponds to the values states divided by 3.
example:function of a heating installation 200 days/annum, 100 operations per day (1 opening + 1 closing = 2 operations)mechanical life = 10 yearstotal number of operations: 200 x 100 x 10 = 200,000in that case select an ES240 to control a load of 4.4 kW(single phase 230V)
U R R
L1 U
V
M
L2
L1 U
W
M
L3
L2 V
R
R
R
U
U
U
number of operations 50,000 100,000 150,000 200,000 300,000 single phase 230V three phase*400V
4.4 4.4 3.9 3.5 2.9 ES220 - ES230
7.8 5.9 5 4.4 3.7 ES240
maximum 12 8.8 7.7 6.6 5.9 ES263
load* 12 10.5 8.5 6.5 5.8 ES320 - ES430
in kW 23.2 17.7 15 13.1 10.8 ES340
35 26.3 23 19.7 5.8 ES463
19
contactors and relays
technical characteristics
auxiliary contacts auxiliary contacts are available for the range of relays and 20A contactors.
20A relays and contactors with manual override1. permanently on2. automatic3. permanently off
I
Auto
0
1
2
3
control voltage start and maintainedconsumption
12V DC 0.5W
24V DC 1.5W
12V AC 1VA
24V ac 2VA
contactors
ES320 ES240 ES263
ES220 ES340 ES365ES420 ES463
ES440command voltage V 230 230 230 230
frequency % +10/ -15 for all
productsHz 50
starting consumption VA 15 20 50 50
maintained consumption VA 5 5 7 7
max perm.current AC1 A 20 20 40 63
insulation voltage V 250 400 400 400
mech. endurance 1,000,000
working temperature °C -10/ +50 for
all products
storage temperature °C -40/ +80
connectioncontrol flexible mm2 0.5 to 4 0.5 to 4 1 to 2.5 1 to 2.5
rigid mm2 1 to 6 1 to 6 1.5 to 4 1.5 to 4
power flexible mm2 1 to 6 1 to 6
rigid mm2 1.5to10 1.5to10 4to25 4to25
note: (a) power consumption of EN145 and EN146
20
contactors and relays
incandescent lamps
tungsten filament and halogen 230 V : 40 W60 W75 W100 W150 W200 W300 W500 W1000 W
45302418129531
503528211410642
100756545332516105
1201059065453523147
halogen 12 or 24V with transformer electronic: 20 W50 W75 W100 W150 W
702819149
8040262013
16080524026
240120786039
fluorescent tubes
single with starter non compensated : 15 W18 W30 W36 W58 W
2925252414
5042353020
11080706040
1501301109060
single with starter in parallel :15 W18 W30 W36 W58 W
C max.25 112 UF25 112 UF20 90 UF20 90 UF15 67 UF
C max.30 135 UF30 135 UF25 112 UF25 112 UF17 76 UF
C max.45 202 UF45 202 UF40 180 UF40 180 UF22 99 UF
C max.60 270 UF60 270 UF55 247 UF55 247 UF40 180 UF
double with starter compensated : 2 x 18 W 2,7 UF2 x 20 W 2,7 UF2 x 36 W 3,4 UF2 x 40 W 3,4 UF2 x 58 W 5,3 UF2 x 65 W 5,3 UF
404022221212
454526261313
909050502323
1401401001005050
single with electronic ballast : 18 W36 W58 W
302615
353017
603225
804530
double with electronic ballast : 2 x 18 W2 x 36 W2 x 58 W
15138
17159
301612
402215
compact fluorescent with electromagnetic bal-last, without compensation :
7 W10 W18 W26 W
50454025
55504227
100906550
1301159080
compact fluorescent with electronic supplyincorporated:
11 W15 W20 W23 W
80605040
85635242
1101007060
150130110100
discharge lamps
high pressure mercury without compensation : 50 W80 W125 W250 W400 W
119731
1210832
362719107
5038261410
high pressure mercury with parralled compensation :50 W80 W125 W250 W400 W
C max.9 63 UF7 49 UF5 50 UF3 54 UF1 25 UF
C max.10 70 UF8 56 UF6 60 UF3 54 UF2 50 UF
C max.25 175 UF21 147 UF14 140 UF7 126 UF4 100 UF
C max.30 210 UF25 175 UF17 170 UF9 162 UF6 150 UF
mixed : 100 W160 W250 W400 W
9631
10742
2219118
33271511
high pressure sodium vapour or metal halidewithout compensation:
70 W150 W250 W400 W
9531
10642
201064
3015106
high pressure sodium vapour or metal halide withcompensation: 70 W
150 W250 W400 W
C max.5 60 UF3 54 UF1 32 UF1 /
C max.6 72 UF3 54 UF2 64 UF1 50 UF
C max.15 180 UF9 162 UF5 160 UF3 150 UF
C max.20 240 UF16 198 UF7 224 UF5 250 UF
type 16 A 20 A 40 A 63 A
connector selectionthe table below indicates the number of lamps that can be connected to each pole of the contactor on 230V 50Hz circuits.
21
latching relays - technical
technical characteristics
latching relays auxiliaries
EP510 EP513 EP519 EP525 EP528 EP529 EP071EP515 EP518 EP540 EP541EP520 EP524
voltage 230V 24V 12V 230V 24V 12V
start consumption 16VA 30VA
contact rating 16A 250V~* 2A 250V~AC1
electrical endurance 100,000 operations –AC1 - 16A
mechanical endurance 500,000 operations –
current in open position 8 mA –
max duration of 1 h –voltage supply to coil
min duration of 0.1 s –current supply to coil
working temperature -10 to +50°C -1 to +50°C
stocking temperature -40 to +80°C -40 to +80°C
connectionscoilflexible 0.5 to 4mm2 0.5 to 4mm2
rigid 1 to 6mm2 1 to 6mm2
powerflexible 1 to 6mm2
rigid 1.5 to 10mm2
*400V~ for the EP540 and EP541.
auxiliary contacts (EP071)The range of latching relays have been designed for use with an auxiliarycontact. The devices simpl clip on the side of the relay.
EH010 EH011 EH110 EH111 EH171 EH191width in 17.5mm 1 1 3 3 3 5version daily weekly daily +weeklyelectricalcharacteristicsvoltage supply 230V +10/ -10%
50/60HZconsumption 0.5VAoutput 1NO 1NO 1 changeover 1 changeover 1 changeover 1 changeoverswitching capacityAC1 16A / 250Vinductive load 4A / 250V(cos phi = 0.6)incandescent 900Wlampscharacteristicstechnology Quartzdial 24 hours 7 days 24 hours and
7 daysmin. switching 15 min 2 hours 15 min and
2 hoursmax. number of 96 84 96 / 84switchingaccuracy +/- 1 sec per daysupply failure 200 hours 200 hours 200 hours 200 hoursreservereached in 120 hours 120 hours 120 hours 120 hoursmanual override auto / on / offEnvironmentprotection degree IP20working -100C to temperature +450Cstorage -100C to temperature + 500Cconnection 0.5 to 4 mm2
22
technical data - analogue time switches
PhN
3 4 5 621
M
EH110 Electrical connections
EH010EH011
21
43
Ph
N
EH010, EH011 electrical connections
Simple time setting and programming using dual direction dial
Programming by captive segments
23
technical data - 72 x 72 mm
M
PhN
3 4 521
53
EH710 electrical connection
3 4 5
Very easy programmingwith dual direction dial
3 4 5
manual override
EH710 EH711 EH770 EH771 EH712 EH715 EH716dimensions(mm) 72x72x48
electrical characteristicsvoltage supply 230V +10/-15% 110 to 240V AC 50/60 Hz
50/60Hz 48V DC +10% / -15%
consumption 0.5VAoutput: 1 changeover 1 N/O 1 changeover switching capacity:AC1 16A / 250Vinductive load cos phi= 0.6 3A / 250Vincandescent lighting 1000 W
characteristicstechnology Quartzdial 24h 24h 7 days 7 days 24h 24h 24hswitching dial 10min 10min 1 hour 1 hour 10 min 10min 10minminimum switching 20min 20min 2 hours 2 hours 20 min 20min 20minworking accuracy + / - 1 sec per daysupply failure reserve - 200h - 200h - - 200hreached in 120h 120h 120hmanual switch temporary ON or OFFenvironementworking temperature -10 to + 500Cstorage temperature -20 to +600Cconnection capacity 1 to 6 mm2
24
EG 170
3 4 5 621
LN
1 2 3 4 5 6 7
4
5
1
6 7 8 9
3
2
enter
reseton
off
progautomanu
OFF
LN
65
21
43
EG 010
1 2 3
OFF
P
- +
6
7
4
3
1
5
2
technical data - digital time switches
3 4 5 621
LN
EG 470
14 15
7 8 9
18 19
A
A,B
,C,D
C
11 12 13
B
10
D
16 17
OFF
20
Electrical connections:
EG 010
EG 170
EG 470
Display:
1. Time2. Output contact (ON or OFF)3. Program selected
Buttons:
4. To select the program to apply5. To scroll program steps6. Reset7. + and -: change time settings
Display:
1. Time2. Circuit status (ON or OFF)3. Day of the week (1 = Monday, 2 =Tuesday...)
Buttons:
4. Mode selector: to select one of thefollowing modes:- time setting- programming- running mode- manual override
5. “1” to “7”: selection of the days6 “on/off”: chooses whether the cir-cuit is on or off7. “+” and “-”: changes settings8 ”enter”: to confirm selection9.”reset”
EG010 EG110 EG210 EG071 EG170 EG171 EG172 EG270 EG470width in 17.5 mm 1 3 3 1 3 3 (pulsed) 3 3 5version daily weeklyelectrical characteristicsvoltage supply 230V +15 / -15% 110/230V 230V +15 / -15% 12V AC 110/230V 230V
50Hz 50/60Hz 50Hz 50Hz 50/60Hz+ 15 / -15%12V DC 50 Hz+ 15/-15%
consumption 1VA 20VAoutput changeover contactswitching capacityAC1 16A / 250Vinductive load 3A / 250Vcos phi = 0.6incandescent lamps 1000Wcharacteristicsaccuracy + / - 1 sec per daysupply failure reserve Lithium battery total of three yearsmanual override permanent permanent ON/OFF permanent permanent ON/OFF
ON/OFF temporary ON/OFF ON/OFF temporary ON/OFFenvironmentprotection degree IP20working temperature -100C to + 500Cstorage temperature -100C to + 500Cconnection 0.5 to 4 mm2
25
delay timers
Ph / +N / -
In
18
18
16
15
15
A1/B1
A2
A3/B1
16
Ph / +N / -
18
18
16
15
15 B1
A1
A2
In
A3
16
technical specifications
functional characteristicsEZ001, EZ003, EZ005, EZ006 functions D,E,F) EZ002, EZ004, EZ006 (functions A,B,C)
Cd: command.O: output.T: time delay.
indicator light (for versions with NO contact).ONOFF
product EZ001, EZ002, EZ003, EZ004, EZ005, EZ006.
electrical characteristics
supply voltage 24-28 Vdc (+10% - 15%) terminals A1 & A224-230 Vac (+10% - 15%) terminals A1 & A212 Vac & dc (+10% -10%) terminals A3 & A2
output 1 volt free C/O contact
life expectancymax load AC1 10A / 230V~ 50,000 cyclesincandescent 450W~ 100,000 cyclesfluorescent non comp. 600W~ 50,000 cyclesinductive load 0.6pf 5A / 230V~ 100,000 cycles
min powerAC 100mA at 230VDC 100mA at 12V
galvanic isolation 2kV
standard / norm EN60669-2-1
functional characteristics
timer range 0.1s - 10 hours
min. command periodAC 50msDC 30ms
operating temperatureworking -20oC to +50oCstorage -40oC to +50oC
connection capacityflexible 1 - 6 mm2
rigid 1.5 - 10 mm2
each time delay bracket is divided into 4 ranges
time delay brackets 1s to 1h 0.1min to 10h 0.1s to 10min 0.2min to 20h
ranges 1s to 10s 0.1min to 1min 0.1s to 1s 0.2min to 2min0.1min to 1min 1min to 10min 1s to 10s 2min to 20min1min to 10min 0.1h to 1h 0.1min to 1min 0.2h to 2h0.1h to 1h 1h to 10h 1min to 10min 2h to 20h
environmentworking temperature: -10°C to +60°C.storage temperature: -20°C to +70°C
26
delay timers
T
Command (B1)
output (15,18)
LED
T
Command (B1)
output (15,18)
LED
delay onEZ001 & EZ006 function D
delay offEZ002 & EZ006 function C
T
Command (B1)
output (15,18)
LED
T
Command (B1)
output (15,18)
LED
delay offEZ003 & EZ006 function E
impulse timerEZ004 & EZ006 function A
T TT T T
Command (B1)
output (15,18)
LED
T
Command (B1)
output (15-10)
LED
symmetrical timerEZ005 & EZ006 function F
multifunction timerEZ004 & EZ006 function A
multifunction timer - 8 individual functionsA = timer.B = delay off (output relay opens either at end of command or
after set time period - which ever is shorter).C = delay off.D = delay on.E = delay on (output relay closes either at end of command or
after set time period - which ever is shorter).F = Symmetrical timer.
on selection - contact permanently closedoff selection - contact permanently open
output relay open - with no command
output relay open - with command signal running
output relay closed - with command signal running
output relay closed - with command signal removed
output relay closed (EZ005)
27
time lag switches
technical specifications
electrical connections
1 3
42
EM001
NPh
24 stime period
EM 001 EM 002
pre warning
secondaryimpulse
inputimpulse
working diagram
I3
I2
I1
I = (I1 + I2 + I3)
1 3
42
EM001
1 3
42
EM001
NPh
1 3
42
7
8
EM001EM 002
NPh
7
8
EM 002
1 3
42
EM001
NPh
cat. ref. EM001 EM002
Electrical characteristics
supply voltage 230V +10 - 15% 230V +10 - 15%50/60 Hz 50/60 Hz
consumption 0.5 VA 0.5 W permanent8 W max.
Breaking capacity
AC1 16A 230V~ 4A 230V~incandescent 2300W 1000Whalogen 230V 2300W 1000Wfero magnetic transformer 1600W -parallel compensated cap 112µF -fluorescent series 3000W -electronic transformer 3600W -compact fluorescent 2300W -
Functional characteristics
time delay 24s to 12 min 24smax. current in rest position 50 mA -
environment
working temperature –15 to +55ºC –15 to +55ºCstorage temperature –25 to +70ºC –25 to +70ºC
connection
flexible (mm2) 0.75 to 4 1 to 6rigid (mm2) 1 to 6 1.5 to 10connection EM001/EM002 2 wires 1.5 2 wires 1.5
28
technical data - twilight switches
NL
13302133722330123801
EE 100EE 100
Wiring Diagram
note: * delivered with a 1 m cable (2 x 0.75mm2)** 8 predefined programs
cells EE002 EE003type flush mounting surface mountingdimension (mm) 89x48x32 25x25x20 hole O 25mmconnection cable 1 m 2x0.75mm2 0.75 to 4 mm2
protection class IP54 IP54working and storage temperature -300C to +600C -300C to +600C
EE100 EE101 EE110 EE170width in 17.5 mm 3 3 5 3electrical characteristicsvoltage supply 230V +10 / -15% frequency 50Hzconsumption 1.5 VA maximumoutput 1 voltage free changeover contactsmaximum switching capacityAC1 16A / 250Vincandescent lamps 2000W230V halogen lamps 1000Wfluorescent lamps, non compensated 1000Wfluorescent lamps, compensated 200Wfluorescent lamps compensated in series 1000Wduo fluorescent lamps 1000Wfunctional characteristicslighting level: 2 ranges 5 to 100 lux and 50 to 2000 luxON and OFF delay 15 to 60 secondsmounting of cell surface flush* surface surfaceprogrammable no no yes yestechnology electromechanical digitalcycle 24h 7 days**program setting 15 min. 1 min.accuracy +/- 6 min/year +/- 6 min./yearoperating reserve accu lithium battery
200h after beeing total of 3 year ofconnected for 120h supply failure
environmentworking temperature -300C to + 600C (cell) -100C to + 500C (modular device) storage temperature -200C to + 600Cconnectionmaximum length between cell and modular 50 meterscapacity mm2 (modular device) 0.5 to 4 0.5 to 4 0.5 to 4 0.5 to 4capacity mm2 (cell) 0.75 to 4 0.75 to 4 0.75 to 4
29
transformers
24 V230 V
U1
U2
U3
safety transformersThese transformers are designed to ensure personal safety, their primary winding are electrically separated from their secondary windings and they are intended to feed safety extra low voltage circuits U ≤ 50V. A thermal overload, in the primary windings,ensures that if a short circuit or an overload occurs in the output itwill not damage the device.
bell transformersBell transformers are similar to safety transformers but the secondary voltages do not exceed 24 volts, they are also similarlyprotected against short circuits and overloads, by thermal protectionin the primary winding.
compliance with the standardsThe bell and safety transformers conform with EN 60742 (BS 3535).
technical specification
reference ST301 ST303 ST305 ST312 ST313 ST314 ST315
nominal power 4VA 8VA 16VA 25VA 16VA 40VA 60VA
designation bell bell bell safety safety safety safety
primary voltage 230 volts 230 volts 230 volts 230 volts 230 volts 230 volts 230 volts
U2 12 volts 8 volts 8 volts 12 volts 12 volts 12 volts 12 voltsIn = 0.33A In = 1A In = 2A In = 2.08A In = 1.33A In = 3.33A In = 5.25A
secondary voltageU3 12 volts 12 volts 12 volts 24 volts 24 volts 24 volts 24 volts
In = 0.5A In = 0.67A In = 1.33A In = 1.04A In = 0.67A In = 1.67A In = 2.63A
no load U2 12 volts 15 volts 12.4 volts 14 volts 15.5 volts 13.7 volts 13.6 voltssecondary voltage
U3 18 volts 21.8 volts 18.5 volts 29 volts 29.7 volts 26.5 volts 27 volts
galvanic isolation 4kV 4kV 4kV 4kV 4kV 4kV 4kV
max functional temperature 35°C 35°C 35°C 35°C 35°C 35°C 35°C
overload and S/C protection thermal cut out in the primary winding
number of products that can be operated simultaneously by a transformer
transformer reference ST301 ST303 ST305 ST312 ST313 ST314 ST315
8V 12V 8V 12V 8V 12V 12V 24V 12V 24V 12V 24V 12V 24V
power 4 4 8 8 16 16 25 25 16 16 40 40 63 63
bell SU212 8/12V 1 1 3 2 5 3 - - - - - - - -
buzzer SU214 8/12V 1 1 3 2 5 3 - - - - - - - -
relays ER124 12V - - - - - - 4 - 2 - 7 - 8 -
ER139 12V - - - - - - 2 - 1 - 3 - 4 -
ER123 24V - - - - - - - 2 - 2 - 7 - 8
ER138 24V - - - - - - - 2 - 1 - 3 - 4
contactors ES224 24V - - - - - - - 5 - 3 - 11 - 12
ES424 24V - - - - - - - 3 - 2 - 7 - 8
latching relays EP519 12V - - - - - 2 3 - 2 - 4 - 4 -
EP529 12V - - - - - 1 2 - 1 - 3 - 3 -
EP513 24V - - - - - - - 2 - 2 - 3 - 3
EP518 24V - - - - - - - 2 - 2 - 3 - 3
EP525 24V - - - - - - - 2 - 2 - 3 - 3
EP528 24V - - - - - - - 2 - 1 - 3 - 3
EP541 24V - - - - - - - 2 - 1 - 3 - 3
30
voltmeters, ammeters and hours counters
R
S
T
N
0
SK 603
L1
L2
L3
11 9
4 10 2
3
2 4 1412SM 151/SM 401
RSTN
0L1L2
L2L3
L3L1
SK 602
L1
L2
L3
3 1
12 2 4 12 1410 6 2SM 501
2 4 12 14SM 020
230 V~0/20 A
2 4 12 14
230 V~/5 A
SM 151/SM 401/SM 6012 4 12 14
SM 501
230 V~0/500 V~
A1
A2
00005 20
EC 100
digital voltmeter and ammeter
technical specificationselectrical characteristics– working voltage: 220/230V~ 50/60Hz– consumption: 4VA
environment– working T°: -5 to +40°C– storage T°: -30°C to +75°C
connection
– connection capacity: flexible: 6mm2
rigid: 10mm2
overload withstand of ammeters- 2 x In continuous- 10 x In for 5 secondsthese values are to allow for starting currents
electrical connectionelectrical connection
hours countertechnical specifications
electrical characteristics– working voltage: 230V~
electrical connection– connection in parallel on the command of the receiver
(contactor coil)
electrical connection
application diagrams
range of voltmeters
cat. ref. scale input resolution accuracyresistance ±1 digit
SM625 0-999V 3.3 MOhm 1V 1%
range of ammeterscat. ref. scale volt resolution accuracy
drop ± digit
SM626 0-99.9A 120 mV 0.01A 1%
SM627 0-99.9/5A 120 mV 0.1A 1%
SM628 0-400/5A 120 mV 1A 1%
31
voltmeters, ammeters and current transformers
R
ST
N
0L1L2
L2L3
L3L1
SK 602
L1
L2
L3
3 1
12 10 6 2SM 500
1000200 400
500
V
300
0
SK 603
L1
L2
L3
R
S
T
N
11 9
4 10 2
3
SM 050
0 50
A
analogue voltmeter and ammeter
technical specificationselectrical characteristics– direct reading voltmeter: 300V and 500V for 50/60Hz– direct reading ammeter: 10A, 20A, 30A– ammeter with CT: CT/5A– consumption: voltmeter: 1.5VA/ammeter: 0.3VA– isolating voltage: 2kV
environment– working T°: 20°C ± 10°C class = 2– working T°: -10°C to +50°C class > 2– storage T°: -30°C to +75°C
connection capacity– flexible: 1 to 6mm2
– rigid: 1.5 to 10mm2
electrical connectionelectrical connection
voltmeters range
current transformers (CT)technical specificationselectrical characteristics– primary current: 50 to 400A (depend. on model) secondary current: 5A– frequency: 40/60Hz
56 28
84
46
56
84
42
60
46
107
77
64
range of CT’sSR671: 50/5A - SR673: 80/5ASR672: 60/5A - SR674: 100/5A
SR675: 150/5A - SR677: 250/5ASR676: 200/5A
SR678: 300/5ASR679: 400/5A
voltmeters range
cat. ref. scale reading
SM630 0-300V direct
SM650 0-500V direct
cat. ref. scale reading
SM615 0-10A direct
SM620 0-20A direct
SM640 0-30A direct
SM610 see below via CT/5A
measurement scale for SM610
SM659 0-5A
SM661 0-50A
SM662 0-60A
SM663 0-80A
SM664 0-100A
SM665 0-150A
SM666 0-200A
SM667 0-250A
SM668 0-300A
SM669 0-400A
32
kWh meters
technical specifications EC031electrical characteristics– working voltage: 3 x 230/400V -20% +15%– frequency: 50/60Hz– In: 5A– Imax: 6A– current transformer ratio:
50/5 - 100/5 - 200/5 - 300/5 - 400/5 - 500/5 - 600/5 - 800/5 – CT ratio selector, not accessible when front plate in place B.– to get direct reading in kWh the selector must be adjusted to the
corresponding value of chosen.functional characteristics– size: 7 modules (122.5mm)– direct reading on display: unit = 1 kWh– accuracy: class 2 (acc. to IEC 1036)– power level indicator: 16 impulses per kWh A.environment– working temperature: -10°C to +45°C– storage temperature: -25°C to +70°Cconnection capacity– max: 6mm2
electrical connection1. supply 2. loadIt is important to ensure correct termination and that the polarity of the conductors passingthrough the torroid is constant to achieve accurate recording of the cumulative current consumption in all three phases.warning:– never connect the secondaries of CTs to earth – never make a common connection on the meters (+)
incoming terminals.impulse transmitter (EC031 only)– output optocoupler– conformity DIN 43864– 1 pulse = 1kWh– pulse duration: 100ms ±10%– internal between 2 pulse ≥ 30ms– insulation: 2kV– external supply: 27V ... max.
– operating current:– – closed output: 10 to 27mA– open output: 0 to 2mA
connection capacity– max: 6mm2
technical specifications EC010-EC011direct connection– supply : 230V -20 +15%– frequency: 50Hz.– working current: 75 mA to 90A– wattmeter measure: 10 to 18,000 W– the counters comply with IEC 1036– accuracy: class 2 (±2% from 1.5A to 90A)– power level indicator: illum. in excess of 1W– direct reading on displays, unit:
energy 1 kWhinstant consumption 1W
– working temperature: -10°C to +60°C– storage temperature: -25°C to +70°Cconnection capacity– power clamps 25mm2 max– impulse transmitter: max 6mm2 for a connection with flexible cableelectrical connection1. supply 2. loadimpulse transmitter (EC011)– output an optocoupler complying with DIN 43– 1 pulse = 1 Wh– interval between 2 impulses ≥ 30ms– insulation: 2kV– external supply: Ue ≤ 27V dc
Re (kΩ) ≥ Ue (V) /27– operating current:– closed output: ≤ 27mA
1(mA) = Ue (V) / Re (kΩ)– open output: ≤ 2mA by 27V
L2
S1 S2
P2
L3
L1
S1 S2
P2
S1 S2
P2
ED
3+
4-
5+
6-
7+
8-
9L1
10L2
11L3 N
N
12
B
A
1 2
50
100
200
300400
500
600
800
000001 kWh
kWh
CL?
E
ED
C
B
A
1 2