1 IEA Annex 45 · Peter Dehoff Sep 5./6., 2006 2 IEA Annex 45 Subtask B Dipl. Ing. Peter Dehoff Strategic Lighting Application Zumtobel Lighting Dornbirn/ Austria IEA Annex 45 · Peter Dehoff Sep 5./6., 2006 2 IEA Annex 45 subtask B Task 53: Trends in lighting solutions Task 56: Collect and provide other integral metrics Comparison of installations Task 57: Provide suited Case Study to test the spider web and evtl. other suited metrics Task 58: Collect Information on Potential Case, Arnaud Studies employing innovative Technology, briefly describe - IBP: "Veru & Energ Efficient Lighting„ - "Zumtobel projects"
Transcript
Page 1: Hans Mustermann Strategic Lighting · PDF fileStrategic Lighting Application Zumtobel Lighting Dornbirn/ Austria 2 IEA Annex 45 · Peter Dehoff Sep 5./6., 2006 IEA Annex 45 subtask

1

IEA Annex 45 · Peter Dehoff Sep 5./6., 20062

Hans Mustermann

IEA Annex 45Subtask B

Dipl. Ing.

Peter Dehoff

Strategic Lighting Application

Zumtobel LightingDornbirn/ Austria

IEA Annex 45 · Peter Dehoff Sep 5./6., 20062

IEA Annex 45 subtask B

Task 53: Trends in lighting solutions

Task 56: Collect and provide other integral metricsComparison of installations

Task 57: Provide suited Case Study to test the spider web and evtl. other suited metrics

Task 58: Collect Information on Potential Case, ArnaudStudies employing innovative Technology,briefly describe- IBP: "Veru & Energ Efficient Lighting„- "Zumtobel projects"

Page 2: Hans Mustermann Strategic Lighting · PDF fileStrategic Lighting Application Zumtobel Lighting Dornbirn/ Austria 2 IEA Annex 45 · Peter Dehoff Sep 5./6., 2006 IEA Annex 45 subtask

2

IEA Annex 45 · Peter Dehoff Sep 5./6., 20063

IEA Annex 45 subtask BTask 53: Trends in lighting solutions

Use of efficient light sources, i.e. - fluorescent: T 5 with high output (instead of high efficiency) to

reduce number of luminaires- HID instead of tungsten halogen in spotlighting - Higher wattage in fluorescent (Compact > 120 W , T5 > 80 W)

LED global trend, growing efficacy, improoved colour rendering

Use of controls - daylight dependency- constant illuminance (to reduce initial illuminance to maintained)- Scene setting- Light changes accoring to a storyboard

IEA Annex 45 · Peter Dehoff Sep 5./6., 20064

IEA Annex 45 subtask B

Luminaires- Smaller- More emphasis on design- Better material to improove LOR- Better glare control using new techniques (mirco material)

Lighting interacts with other disciplines

Page 3: Hans Mustermann Strategic Lighting · PDF fileStrategic Lighting Application Zumtobel Lighting Dornbirn/ Austria 2 IEA Annex 45 · Peter Dehoff Sep 5./6., 2006 IEA Annex 45 subtask

3

Licht für Büros · W. Preisenhammer · 10. OKT. 200550

New impacts of luminaires

Licht für Büros · W. Preisenhammer · 10. OKT. 200551

New impacts of luminaires

Page 4: Hans Mustermann Strategic Lighting · PDF fileStrategic Lighting Application Zumtobel Lighting Dornbirn/ Austria 2 IEA Annex 45 · Peter Dehoff Sep 5./6., 2006 IEA Annex 45 subtask

4

Licht für Büros · W. Preisenhammer · 10. OKT. 200552

New impacts of luminaires

Licht für Büros · W. Preisenhammer · 10. OKT. 200553

New impacts of luminaires

Page 5: Hans Mustermann Strategic Lighting · PDF fileStrategic Lighting Application Zumtobel Lighting Dornbirn/ Austria 2 IEA Annex 45 · Peter Dehoff Sep 5./6., 2006 IEA Annex 45 subtask

5

Licht für Büros · W. Preisenhammer · 10. OKT. 200554

New impacts of luminaires

IEA Annex 45 · Peter Dehoff Sep 5./6., 2006

New impacts of luminaires

40

Three functions of light

Bild Messe komponenten, emotion,

Visual (performance, detection)

Emotional (environment, architecture)

Biological (biological clock, health)

Page 6: Hans Mustermann Strategic Lighting · PDF fileStrategic Lighting Application Zumtobel Lighting Dornbirn/ Austria 2 IEA Annex 45 · Peter Dehoff Sep 5./6., 2006 IEA Annex 45 subtask

6

IEA Annex 45 · Peter Dehoff Sep 5./6., 200611

New impacts of luminairesDifferent lighting situations support the wellbeing during a long working day

IEA Annex 45 · Peter Dehoff Sep 5./6., 200612

IEA Annex 45 subtask BEnergy is a global interest!

Kyoto protocol:

Reduction of CO2 emission (f.e. Germany 21% until 2012)

Directives

f.e. Energy Performance of Buildings

National legislation

Energy saving laws

19%

81%

International Energy Agency:19% of electricity worldwide used for lighting

Page 7: Hans Mustermann Strategic Lighting · PDF fileStrategic Lighting Application Zumtobel Lighting Dornbirn/ Austria 2 IEA Annex 45 · Peter Dehoff Sep 5./6., 2006 IEA Annex 45 subtask

7

IEA Annex 45 · Peter Dehoff Sep 5./6., 200613

IEA Annex 45 subtask BThere is a gossip:

LENIundELI

They have a relationship!

IEA Annex 45 · Peter Dehoff Sep 5./6., 200614

IEA Annex 45 subtask BWho is ...

LENI ?

Page 8: Hans Mustermann Strategic Lighting · PDF fileStrategic Lighting Application Zumtobel Lighting Dornbirn/ Austria 2 IEA Annex 45 · Peter Dehoff Sep 5./6., 2006 IEA Annex 45 subtask

8

IEA Annex 45 · Peter Dehoff Sep 5./6., 200615

IEA Annex 45 subtask BThe draft standard prEN 15193 defines the calculation method for annual lighting consumption

IEA Annex 45 · Peter Dehoff Sep 5./6., 200616

IEA Annex 45 subtask BLENI is defined in the European standard as the measure for energy consumption for lighting in a building.

“The Lighting Energy Numeric Indicator (LENI) has been established toshow the annual lighting energy required to fulfil the illumination functionand purpose in the building specifications”

Lighting Energy Numeric Indicator

Source: prEN 15193 (July 2006 final draft)

LENI = Energy consumption

m² yearkWh/ m² a

Page 9: Hans Mustermann Strategic Lighting · PDF fileStrategic Lighting Application Zumtobel Lighting Dornbirn/ Austria 2 IEA Annex 45 · Peter Dehoff Sep 5./6., 2006 IEA Annex 45 subtask

9

IEA Annex 45 · Peter Dehoff Sep 5./6., 200617

IEA Annex 45 subtask BEnergy calculation and measurement acc to EN 15193

IEA Annex 45 · Peter Dehoff Sep 5./6., 200618

IEA Annex 45 subtask BEnergy calculation acc to EN 15193

Page 10: Hans Mustermann Strategic Lighting · PDF fileStrategic Lighting Application Zumtobel Lighting Dornbirn/ Austria 2 IEA Annex 45 · Peter Dehoff Sep 5./6., 2006 IEA Annex 45 subtask

10

IEA Annex 45 · Peter Dehoff Sep 5./6., 200619

IEA Annex 45 subtask BEnergy calculation acc to EN 15193

IEA Annex 45 · Peter Dehoff Sep 5./6., 200620

IEA Annex 45 subtask BEuropean Performance of Buildings Directive requires an energy certificate for buildings.

Energy certificate

Page 11: Hans Mustermann Strategic Lighting · PDF fileStrategic Lighting Application Zumtobel Lighting Dornbirn/ Austria 2 IEA Annex 45 · Peter Dehoff Sep 5./6., 2006 IEA Annex 45 subtask

11

IEA Annex 45 · Peter Dehoff Sep 5./6., 200621

IEA Annex 45 subtask BVERU is an experimental installation for energy and indoor climate investigations

Versuchseinrichtung für energetische und raumklimatische Untersuchungen

IEA Annex 45 · Peter Dehoff Sep 5./6., 200622

IEA Annex 45 subtask BA comparison between different installations in a small office

Layout of VERU test building

Page 12: Hans Mustermann Strategic Lighting · PDF fileStrategic Lighting Application Zumtobel Lighting Dornbirn/ Austria 2 IEA Annex 45 · Peter Dehoff Sep 5./6., 2006 IEA Annex 45 subtask

12

IEA Annex 45 · Peter Dehoff Sep 5./6., 200623

IEA Annex 45 subtask BResearch project: veru (with Fraunhofer Institute in Holzkirchen near Munich) measuring energy consumption within one year

GF-O

Louvre

Mellowlight

3 components

GF-R

1.FL-R 1.FL-O

2.FL-R 2.FL-O

IEA Annex 45 · Peter Dehoff Sep 5./6., 200624

IEA Annex 45 subtask B3 component solution to fulfil comprehensive needs of the user

Wallwasher:T 16 Colour temp.: 860

Task area lighting:ID Light FiledsT 16 HO

Wallwasher Downlights:CFL 18 W

Page 13: Hans Mustermann Strategic Lighting · PDF fileStrategic Lighting Application Zumtobel Lighting Dornbirn/ Austria 2 IEA Annex 45 · Peter Dehoff Sep 5./6., 2006 IEA Annex 45 subtask

13

IEA Annex 45 · Peter Dehoff Sep 5./6., 200625

IEA Annex 45 subtask BResults of the energy calculation

446425192240212268Total installed load PN (W)

33.157.517.933.029.336.1LENI ( kWh/(m²*year) )

496862269495439542Energy for lighting (kWh/year) (incl. standby)

461844243477422533Energy for lighting (kWh/year)

11841126509636562711All energy (kWh/year)

9141061444600530670Quick method (kWh/year)

29.7628.3012.8016.0014.1317.87Installed load (W/m²)

2.FL-O2.FL-R1.FL-O1.FL-RGF-OGF-R

IEA Annex 45 · Peter Dehoff Sep 5./6., 200626

IEA Annex 45 subtask BWho is ...

ELI ?

Page 14: Hans Mustermann Strategic Lighting · PDF fileStrategic Lighting Application Zumtobel Lighting Dornbirn/ Austria 2 IEA Annex 45 · Peter Dehoff Sep 5./6., 2006 IEA Annex 45 subtask

14

IEA Annex 45 · Peter Dehoff Sep 5./6., 200627

IEA Annex 45 subtask BELI is defined to give an evaluation of the quality of a lighting installation

1 2 3 4 5

Performance o o o o o

Appearance o o o o o

Comfort o o o o o

Emotion o o o o o

Individuality o o o o o

ELI: Ergonomic Lighting Indicator

IEA Annex 45 · Peter Dehoff Sep 5./6., 200628

IEA Annex 45 subtask BErgonomic quality in 3 levels

Louvre

Mellow Light

Combined

Ergonomic Level 0:Horizontal task

Em: 500 lx, UGR≤19, L65° ≤1000cd/m²

Ergonomic Level 1:Horizontal taskCylindrical task

Ergonomic Level 2:Horizontal taskCylindrical taskVertical and moods

Page 15: Hans Mustermann Strategic Lighting · PDF fileStrategic Lighting Application Zumtobel Lighting Dornbirn/ Austria 2 IEA Annex 45 · Peter Dehoff Sep 5./6., 2006 IEA Annex 45 subtask

15

IEA Annex 45 · Peter Dehoff Sep 5./6., 200629

IEA Annex 45 subtask BELI criteria checklist: under developement with ETH Zurich

IEA Annex 45 · Peter Dehoff Sep 5./6., 200630

IEA Annex 45 subtask B

Page 16: Hans Mustermann Strategic Lighting · PDF fileStrategic Lighting Application Zumtobel Lighting Dornbirn/ Austria 2 IEA Annex 45 · Peter Dehoff Sep 5./6., 2006 IEA Annex 45 subtask

16

IEA Annex 45 · Peter Dehoff Sep 5./6., 200631

IEA Annex 45 subtask B

IEA Annex 45 · Peter Dehoff Sep 5./6., 200632

Page 17: Hans Mustermann Strategic Lighting · PDF fileStrategic Lighting Application Zumtobel Lighting Dornbirn/ Austria 2 IEA Annex 45 · Peter Dehoff Sep 5./6., 2006 IEA Annex 45 subtask

17

IEA Annex 45 · Peter Dehoff Sep 5./6., 200633

IEA Annex 45 subtask B

IEA Annex 45 · Peter Dehoff Sep 5./6., 200634

IEA Annex 45 subtask B

Page 18: Hans Mustermann Strategic Lighting · PDF fileStrategic Lighting Application Zumtobel Lighting Dornbirn/ Austria 2 IEA Annex 45 · Peter Dehoff Sep 5./6., 2006 IEA Annex 45 subtask

18

IEA Annex 45 · Peter Dehoff Sep 5./6., 200635

IEA Annex 45 subtask B

Fraunhofer München

IEA Annex 45 · Peter Dehoff Sep 5./6., 200636

IEA Annex 45 subtask B

Page 19: Hans Mustermann Strategic Lighting · PDF fileStrategic Lighting Application Zumtobel Lighting Dornbirn/ Austria 2 IEA Annex 45 · Peter Dehoff Sep 5./6., 2006 IEA Annex 45 subtask

19

IEA Annex 45 · Peter Dehoff Sep 5./6., 200637

IEA Annex 45 subtask B

IEA Annex 45 · Peter Dehoff Sep 5./6., 200638

IEA Annex 45 subtask BDifferent lighting situations by scene setting and individual control of the user as well as automatic control

\\dop110/seminararchiv/Kundenseminare/Junghans/ILCT_V180

Page 20: Hans Mustermann Strategic Lighting · PDF fileStrategic Lighting Application Zumtobel Lighting Dornbirn/ Austria 2 IEA Annex 45 · Peter Dehoff Sep 5./6., 2006 IEA Annex 45 subtask

20

IEA Annex 45 · Peter Dehoff Sep 5./6., 200639

IEA Annex 45 subtask BGF-RGround Floor - Reference

0

1

2

3

4

5Performance

Appearance

ComfortEmotion

Individuality

IEA Annex 45 · Peter Dehoff Sep 5./6., 200640

IEA Annex 45 subtask BGF-OGround Floor - Optimised

0

1

2

3

4

5Performance

Appearance

ComfortEmotion

Individuality

Ergonomic Level Indicator (ELI): 8

Page 21: Hans Mustermann Strategic Lighting · PDF fileStrategic Lighting Application Zumtobel Lighting Dornbirn/ Austria 2 IEA Annex 45 · Peter Dehoff Sep 5./6., 2006 IEA Annex 45 subtask

21

IEA Annex 45 · Peter Dehoff Sep 5./6., 200641

IEA Annex 45 subtask B1.FL-R1st Floor - Reference

0

1

2

3

4

5Performance

Appearance

ComfortEmotion

Individuality

Ergonomic Level Indicator (ELI): 12

IEA Annex 45 · Peter Dehoff Sep 5./6., 200642

IEA Annex 45 subtask B1.FL-O1st Floor - Optimised

0

1

2

3

4

5Performance

Appearance

ComfortEmotion

Individuality

Ergonomic Level Indicator (ELI): 16

Page 22: Hans Mustermann Strategic Lighting · PDF fileStrategic Lighting Application Zumtobel Lighting Dornbirn/ Austria 2 IEA Annex 45 · Peter Dehoff Sep 5./6., 2006 IEA Annex 45 subtask

22

IEA Annex 45 · Peter Dehoff Sep 5./6., 200643

IEA Annex 45 subtask B2.FL-R2nd Floor - Reference

0

1

2

3

4

5Performance

Appearance

ComfortEmotion

Individuality

Ergonomic Level Indicator (ELI): 17

IEA Annex 45 · Peter Dehoff Sep 5./6., 200644

IEA Annex 45 subtask B2.FL-O2nd Floor - Optimised

0

1

2

3

4

5Performance

Appearance

ComfortEmotion

Individuality

Ergonomic Level Indicator (ELI): 25

Page 23: Hans Mustermann Strategic Lighting · PDF fileStrategic Lighting Application Zumtobel Lighting Dornbirn/ Austria 2 IEA Annex 45 · Peter Dehoff Sep 5./6., 2006 IEA Annex 45 subtask

23

IEA Annex 45 · Peter Dehoff Sep 5./6., 200645

IEA Annex 45 subtask BThe energy-to-ergonomic ratio

The energy-to-ergonomic ratio of an installation might be described as the ratio of the LENI to the ELI

1.323.381.122.753.664.52LENI-to-ELI Ratio

2517161288ELI (Ergonomic Level Indicator)

33.157.517.933.029.336.1LENI (Lighting Energy Numeric Indicator)

2.FL-O2.FL-R1.FL-O1.FL-RGF-OGF-R

The ratio shows that the installation an the 2nd floor has a very good value. Even if the installed load is very high.

IEA Annex 45 · Peter Dehoff Sep 5./6., 200646

IEA Annex 45 subtask BHuman aspects (lighting quality for people) and energy efficiencymay be measured and quantified

Quality criteria of good lighting:Performance/ Sehleistung(EN 12464)

Appearance/ Erscheinungsbild

Comfort/ Sehkomfort

Emotion/ Emotionalität

Individuality/ Individualität

ELI:Ergonomic Lighting Indicator

LENI:Lighting Energy Numeric Indicator

Installed load and parasitic power (Stand by)

Reduced by Time of usage (Day/night)

Daylight controlPresence detectionAlgorithmic lighting

EN 15193/ EPBD

Page 24: Hans Mustermann Strategic Lighting · PDF fileStrategic Lighting Application Zumtobel Lighting Dornbirn/ Austria 2 IEA Annex 45 · Peter Dehoff Sep 5./6., 2006 IEA Annex 45 subtask

24

IEA Annex 45 · Peter Dehoff Sep 5./6., 200647

IEA Annex 45 subtask BErgonomic quality and energy efficiency can be measured!

ELI:Ergonomic Lighting Indicator

LENI:Lighting Energy Numeric Indicator

0

1

2

3

4

5Performance

Appearance

ComfortEmotion

Individuality

LENI = 1/A x (Wp + Wlight) kWh/m²/year

Annual Energy consumptiom per m²for lighting incl. Stand by

IEA Annex 45 · Peter Dehoff Sep 5./6., 200648

IEA Annex 45 subtask BErgonomic quality and energy efficiency can be measured!

ELI:Ergonomic Lighting Indicator

LENI:Lighting Energy Numeric Indicator

kWh/ m² a

Annual energy consumption per m² for lightingLighting quality

Page 25: Hans Mustermann Strategic Lighting · PDF fileStrategic Lighting Application Zumtobel Lighting Dornbirn/ Austria 2 IEA Annex 45 · Peter Dehoff Sep 5./6., 2006 IEA Annex 45 subtask

25

IEA Annex 45 · Peter Dehoff Sep 5./6., 200649

IEA Annex 45 subtask BHumanergy Balance in all applications

OFFICE AND EDUCATION

INDUSTRY AND ENGINEERING

PRESENTATION AND RETAIL

HEALTH & CARE

ART AND CULTURE

TRANSIT AREAS AND CAR PARKS

HOTELS AND WELLNESS

SPORT AND LEISURE

ORIENTATION AND SAFETY

IEA Annex 45 · Peter Dehoff Sep 5./6., 200668

IEA Annex 45 subtask BOffice: intellectually and emotionally satisfying lighting

Münchner RückversicherungMunich, Germany

One of the first buildings getting an energy certificate

Fully automatic control of lighting and blinds

High class work place lighting

Page 26: Hans Mustermann Strategic Lighting · PDF fileStrategic Lighting Application Zumtobel Lighting Dornbirn/ Austria 2 IEA Annex 45 · Peter Dehoff Sep 5./6., 2006 IEA Annex 45 subtask

26

IEA Annex 45 · Peter Dehoff Sep 5./6., 200669

IEA Annex 45 subtask B

Kreditanstalt für WiederaufbauFrankfurt, Germnay

Low impact on primary energy

Fully automatic control of lighting, blinds and cooling/ ventilation

Special solution with integrated LIGHT FIELDS

Office: intellectually and emotionally satisfying lighting

IEA Annex 45 · Peter Dehoff Sep 5./6., 200670

IEA Annex 45 subtask B

T-mobile Center Vienna/ Austria

Office: intellectually and emotionally satisfying lighting

Energy saving in efficieny lighting and controls

Combination of daylight and time control

Work place oriented direct/ indirect lighting with CLARIS

Page 27: Hans Mustermann Strategic Lighting · PDF fileStrategic Lighting Application Zumtobel Lighting Dornbirn/ Austria 2 IEA Annex 45 · Peter Dehoff Sep 5./6., 2006 IEA Annex 45 subtask

27

IEA Annex 45 · Peter Dehoff Sep 5./6., 200673

IEA Annex 45 subtask BEducation: light that strikes a balance between encouraging and challenging students

EURAC academyBozen/ Italy:

Energy saving in efficieny lighting and controls

Combination of daylight and time control

Work place oriented direct/ indirect lighting with CLARIS

IEA Annex 45 · Peter Dehoff Sep 5./6., 200654

IEA Annex 45 subtask BEducation: light that strikes a balance between encouraging and challenging students

Secondary schoolBünzmatt/Switzerland:

Meets Swiss minergie-requirements

Combination of presence and time control

Glare-free direct/ indirect lighting with LIGHT FIELDS

Page 28: Hans Mustermann Strategic Lighting · PDF fileStrategic Lighting Application Zumtobel Lighting Dornbirn/ Austria 2 IEA Annex 45 · Peter Dehoff Sep 5./6., 2006 IEA Annex 45 subtask

28

IEA Annex 45 · Peter Dehoff Sep 5./6., 2006

IEA Annex 45 subtask B

78

Retail: light that strikes the balance between supply and demand

Hugo Boss Richmond, Virginia/USA

Energy and heat reducing lighting

Combination of efficient fluorescent and CDM-T lamps

High quality display of clothing with CARDAN SPIRIT spotlights and wallwashing

IEA Annex 45 · Peter Dehoff Sep 5./6., 200656

IEA Annex 45 subtask B

GM showroom

Retail: light that strikes the balance between supply and demand

Page 29: Hans Mustermann Strategic Lighting · PDF fileStrategic Lighting Application Zumtobel Lighting Dornbirn/ Austria 2 IEA Annex 45 · Peter Dehoff Sep 5./6., 2006 IEA Annex 45 subtask

29

IEA Annex 45 · Peter Dehoff Sep 5./6., 200680

IEA Annex 45 subtask BRetail: light that strikes the balance between supply and demand

COOP-SupermarktetBrescia, Italy

Energy and heat reducing lighting

Variety of different color temperatures by efficient fluorescent and CDM lamps

Right light for each product for best display

IEA Annex 45 · Peter Dehoff Sep 5./6., 200683

IEA Annex 45 subtask BWellness: light that leaves guest and host alike with fond memories

Nova thermal resortKöflach, Austria

Energy conscious lighting

Use of daylight and day and night related lighting

Reduced lighting at night, use of colors in scene setting

Page 30: Hans Mustermann Strategic Lighting · PDF fileStrategic Lighting Application Zumtobel Lighting Dornbirn/ Austria 2 IEA Annex 45 · Peter Dehoff Sep 5./6., 2006 IEA Annex 45 subtask

30

IEA Annex 45 · Peter Dehoff Sep 5./6., 200684

IEA Annex 45 subtask B

Riders Palace Sports hotelLaax, Switzerland

Hotel: light that leaves guest and host alike with fond memories

Intelligent use of lighting in the suites

Different scene settings and general control

Personal lighting including ACTIVE LIGHT WALLS

IEA Annex 45 · Peter Dehoff Sep 5./6., 200660

IEA Annex 45 subtask BHuman Aspects and Energy Efficiency have a clear content

BACK UP SLIDES

HUMAN ASPECTS

Optimal lighting for:

Visual (performance, detection)

Emotional (environment, architecture)

Biological (biological clock, health)

ENERGY EFFIENCY

Energy awarenessIntelligent use of light Lightmanagement- daylight control- time control- presence detection

Energy efficient luminaires and components- lamps- ballasts- material- design

Page 31: Hans Mustermann Strategic Lighting · PDF fileStrategic Lighting Application Zumtobel Lighting Dornbirn/ Austria 2 IEA Annex 45 · Peter Dehoff Sep 5./6., 2006 IEA Annex 45 subtask

31

IEA Annex 45 · Peter Dehoff Sep 5./6., 200661

IEA Annex 45 subtask BHuman Aspects and Energy Efficiency have a clear content

ENERGY EFFIENCY

Energy awarenessIntelligent use of light Lightmanagement- daylight control- time control- presence detection

Energy efficient luminaires and components- lamps- ballasts- material- design

HUMAN ASPECTS

Optimal lighting for:

Visual (performance, detection)

Emotional (environment, architecture)

Biological (biological clock, health)

BACK UP SLIDES