(Hazardous Materials and Risk Assessment)
Initial Survey : Noel Arnold & Associates : 16 - Dec - 2009
Parsons Brinckerhoff : 28 - Feb - 2017
School : Finley High School (8360)
Asbestos Register
Region : Riverina
State Electorate : Murray
Local Government Area : Berrigan
Reviewed By :
Register Issue Date : Friday, 24 Mar 2017 Page 1 of 338360 - Finley High School
ProductMaterial
Description ExtentLocation
ReferenceMaterial
ConditionRisk
Status
Sample No
ControlPriority
8360 Finley High School 2017
Test Result
B00A - Various - 1958 - Brick/Block (Brick/Block)
Exterior
Ceiling Voids - Raked Ceiling
No Asbestos Found
Eaves Linings Flat AC Sheeting
8360/B00A/R1002/Ceiling Structures/Linings/S14
48m2 All surfaces Good Condition (1) Low (1)
Chrysotile (white asbestos) , Amosite (brown
asbestos)
Low Priority (2-3)
Underfloor Voids - Slab on Ground
No Asbestos Found
Interior
B00A - R0001 - Plant
Ceiling Structures/Linings Flat AC Sheeting
Assumed Asbestos - Height Restriction Not able to be
7m2 All surfaces Good Condition (1) Low (1) Low Priority (2-3)
B00A - R0002 - Distribution Board Cupboard Note: No inspection of live electrical installation.
Electrical Mounting Board Resinous Board
Assumed Asbestos - Not able to sampled due to live
1Unit South facing Good Condition (1) Low (1) Low Priority (2-3)
B00A - R0003 - Movement
No Asbestos
B00A - R0005 - Leading Teacher
Ceiling Structures/Linings Vermiculite
8360/B00A/R0024/Ceiling Structures/Linings/S13
20m2 All surfaces Friable Asbestos (5) Low (1)
Chrysotile (white asbestos)
Low Priority (2-3)
B00A - R0006 - General Storeroom
Ceiling Structures/Linings Vermiculite
8360/B00A/R0024/Ceiling Structures/Linings/S13
10m2 All surfaces Friable Asbestos (5) Low (1)
Chrysotile (white asbestos)
Low Priority (2-3)
B00A - R0007 - Staff - Toilet
Ceiling Structures/Linings Vermiculite
8360/B00A/R0024/Ceiling Structures/Linings/S13
2m2 All surfaces Friable Asbestos (5) Low (1)
Chrysotile (white asbestos)
Low Priority (2-3)
B00A - R0008 - General Storeroom
Ceiling Structures/Linings Vermiculite
8360/B00A/R0024/Ceiling Structures/Linings/S13
5m2 All surfaces Friable Asbestos (5) Low (1)
Chrysotile (white asbestos)
Low Priority (2-3)
B00A - R0009 - Cleaning Store - Distributed
Ceiling Structures/Linings Vermiculite
8360/B00A/R0024/Ceiling Structures/Linings/S13
3m2 All surfaces Friable Asbestos (5) Low (1)
Chrysotile (white asbestos)
Low Priority (2-3)
B00A - R0010 - Distribution Board Cupboard Note: No inspection of live electrical installation.
No Asbestos
B00A - R0011 - Principal Office
Ceiling Structures/Linings Vermiculite
8360/B00A/R0024/Ceiling Structures/Linings/S13
20m2 All surfaces Friable Asbestos (5) Low (1)
Chrysotile (white asbestos)
Low Priority (2-3)
B00A - R0012 - Interview/Office - Type 1
Ceiling Structures/Linings Vermiculite
8360/B00A/R0024/Ceiling Structures/Linings/S13
20m2 All surfaces Friable Asbestos (5) Low (1)
Chrysotile (white asbestos)
Low Priority (2-3)
B00A - R0013 - Deputy Principal Office
Ceiling Structures/Linings Vermiculite
8360/B00A/R0024/Ceiling Structures/Linings/S13
16m2 All surfaces Friable Asbestos (5) Low (1)
Chrysotile (white asbestos)
Low Priority (2-3)
B00A - R0014 - Administration - Clerical
Register Issue Date : Friday, 24 Mar 2017 Page 2 of 338360 - Finley High School
ProductMaterial
Description ExtentLocation
ReferenceMaterial
ConditionRisk
Status
Sample No
ControlPriority
8360 Finley High School 2017
Test Result
Ceiling Structures/Linings Vermiculite
8360/B00A/R0024/Ceiling Structures/Linings/S13
16m2 All surfaces Friable Asbestos (5) Low (1)
Chrysotile (white asbestos)
Low Priority (2-3)
B00A - R0017 - Cleaning Store - Distributed
Ceiling Structures/Linings Vermiculite
8360/B00A/R0024/Ceiling Structures/Linings/S13
3m2 All surfaces Friable Asbestos (5) Low (1)
Chrysotile (white asbestos)
Low Priority (2-3)
B00A - R0019 - Commonroom
Ceiling Structures/Linings Vermiculite
8360/B00A/R0024/Ceiling Structures/Linings/S13
65m2 All surfaces Friable Asbestos (5) Low (1)
Chrysotile (white asbestos)
Low Priority (2-3)
B00A - R0020 - Ancillary Staff
Ceiling Structures/Linings Vermiculite
8360/B00A/R0024/Ceiling Structures/Linings/S13
15m2 All surfaces Friable Asbestos (5) Low (1)
Chrysotile (white asbestos)
Low Priority (2-3)
B00A - R0021 - Administration - Clerical
Ceiling Structures/Linings Vermiculite
8360/B00A/R0024/Ceiling Structures/Linings/S13
20m2 All surfaces Friable Asbestos (5) Low (1)
Chrysotile (white asbestos)
Low Priority (2-3)
B00A - R0024 - Movement
Ceiling Structures/Linings Vermiculite
8360/B00A/R0024/Ceiling Structures/Linings/S13
9m2 All surfaces Friable Asbestos (5) Low (1)
Chrysotile (white asbestos)
Low Priority (2-3)
B00A - R0025 - Distribution Board Cupboard Note: No inspection of live electrical installation.
No Asbestos
B00A - R0026 - Cleaning Store - Distributed
Ceiling Structures/Linings Vermiculite
8360/B00A/R0024/Ceiling Structures/Linings/S13
4m2 All surfaces Friable Asbestos (5) Low (1)
Chrysotile (white asbestos)
Low Priority (2-3)
B00A - R0027 - Laboratory L.S.
Ceiling Structures/Linings Vermiculite
8360/B00A/R0024/Ceiling Structures/Linings/S13
93m2 All surfaces Friable Asbestos (5) Low (1)
Chrysotile (white asbestos)
Low Priority (2-3)
B00A - R0028 - Apparatus Store
Ceiling Structures/Linings Vermiculite
8360/B00A/R0024/Ceiling Structures/Linings/S13
10m2 All surfaces Friable Asbestos (5) Low (1)
Chrysotile (white asbestos)
Low Priority (2-3)
B00A - R0029 - Preparation
Ceiling Structures/Linings Vermiculite
8360/B00A/R0024/Ceiling Structures/Linings/S13
29m2 All surfaces Friable Asbestos (5) Low (1)
Chrysotile (white asbestos)
Low Priority (2-3)
B00A - R0030 - General Storeroom
Ceiling Structures/Linings Vermiculite
8360/B00A/R0024/Ceiling Structures/Linings/S13
7m2 All surfaces Friable Asbestos (5) Low (1)
Chrysotile (white asbestos)
Low Priority (2-3)
B00A - R0031 - Cleaning Store - Distributed
Ceiling Structures/Linings Vermiculite
8360/B00A/R0024/Ceiling Structures/Linings/S13
7m2 All surfaces Friable Asbestos (5) Low (1)
Chrysotile (white asbestos)
Low Priority (2-3)
B00A - R0032 - General Storeroom
Ceiling Structures/Linings Vermiculite
8360/B00A/R0024/Ceiling Structures/Linings/S13
13m2 All surfaces Friable Asbestos (5) Low (1)
Chrysotile (white asbestos)
Low Priority (2-3)
B00A - R0033 - Staff Study
Ceiling Structures/Linings Vermiculite
8360/B00A/R0024/Ceiling Structures/Linings/S13
39m2 All surfaces Friable Asbestos (5) Low (1)
Chrysotile (white asbestos)
Low Priority (2-3)
Register Issue Date : Friday, 24 Mar 2017 Page 3 of 338360 - Finley High School
ProductMaterial
Description ExtentLocation
ReferenceMaterial
ConditionRisk
Status
Sample No
ControlPriority
8360 Finley High School 2017
Test Result
Wall Linings Internal Flat AC Sheeting
8360/B00A/R0033/Wall Linings Internal/S15 No Asbestos Detected
B00A - R0034 - Duplicating Workroom
Ceiling Structures/Linings Vermiculite
8360/B00A/R0024/Ceiling Structures/Linings/S13
48m2 All surfaces Friable Asbestos (5) Low (1)
Chrysotile (white asbestos)
Low Priority (2-3)
Wall Linings Internal No Asbestos Found
B00A - R0035 - Administration - Clerical
Ceiling Structures/Linings Vermiculite
8360/B00A/R0024/Ceiling Structures/Linings/S13
20m2 All surfaces Friable Asbestos (5) Low (1)
Chrysotile (white asbestos)
Low Priority (2-3)
B00A - R0036 - Clinic - Boys
Ceiling Structures/Linings Vermiculite
8360/B00A/R0024/Ceiling Structures/Linings/S13
13m2 All surfaces Friable Asbestos (5) Low (1)
Chrysotile (white asbestos)
Low Priority (2-3)
B00A - R0037 - Stairs
Ceiling Structures/Linings Vermiculite
8360/B00A/R0024/Ceiling Structures/Linings/S13
2m2 All surfaces Friable Asbestos (5) Low (1)
Chrysotile (white asbestos)
Low Priority (2-3)
B00A - R0038 - Stairs
Ceiling Structures/Linings Vermiculite
8360/B00A/R0024/Ceiling Structures/Linings/S13
9m2 All surfaces Friable Asbestos (5) Low (1)
Chrysotile (white asbestos)
Low Priority (2-3)
B00A - R0039 - External Movement
No Asbestos
B00A - R0040 - Movement
No Asbestos
B00A - R0041 - Toilet - Lobby
No Asbestos
B00A - R0042 - Toilet - Lobby
No Asbestos
B00A - R0043 - Staff - Toilet
No Asbestos
B00A - R0044 - Staff - Toilet
No Asbestos
B00A - R0045 - Movement
No Asbestos
B00A - R0046 - Movement
No Asbestos
B00A - R0047 - External Movement
No Asbestos
B00A - R1001 - Computer Learning Space
Ceiling Structures/Linings Vermiculite
8360/B00A/R0024/Ceiling Structures/Linings/S13
53m2 All surfaces Friable Asbestos (5) Low (1)
Chrysotile (white asbestos)
Low Priority (2-3)
B00A - R1003 - General Storeroom
Ceiling Structures/Linings Vermiculite
8360/B00A/R0024/Ceiling Structures/Linings/S13
9m2 All surfaces Friable Asbestos (5) Low (1)
Chrysotile (white asbestos)
Low Priority (2-3)
B00A - R1004 - Distribution Board Cupboard Note: No inspection of live electrical installation.
No Asbestos
B00A - R1005 - General Storeroom
Ceiling Structures/Linings Vermiculite
8360/B00A/R0024/Ceiling Structures/Linings/S13
4m2 All surfaces Friable Asbestos (5) Low (1)
Chrysotile (white asbestos)
Low Priority (2-3)
Register Issue Date : Friday, 24 Mar 2017 Page 4 of 338360 - Finley High School
ProductMaterial
Description ExtentLocation
ReferenceMaterial
ConditionRisk
Status
Sample No
ControlPriority
8360 Finley High School 2017
Test Result
B00A - R1006 - Resources Store
Ceiling Structures/Linings Vermiculite
8360/B00A/R0024/Ceiling Structures/Linings/S13
7m2 All surfaces Friable Asbestos (5) Low (1)
Chrysotile (white asbestos)
Low Priority (2-3)
B00A - R1007 - Darkroom Space
Ceiling Structures/Linings Vermiculite
8360/B00A/R0024/Ceiling Structures/Linings/S13
7m2 All surfaces Friable Asbestos (5) Low (1)
Chrysotile (white asbestos)
Low Priority (2-3)
B00A - R1008 - Art Learning Space
Ceiling Structures/Linings Vermiculite
8360/B00A/R0024/Ceiling Structures/Linings/S13
80m2 All surfaces Friable Asbestos (5) Low (1)
Chrysotile (white asbestos)
Low Priority (2-3)
B00A - R1009 - Kiln Space
Ceiling Structures/Linings Vermiculite
8360/B00A/R0024/Ceiling Structures/Linings/S13
7m2 All surfaces Friable Asbestos (5) Low (1)
Chrysotile (white asbestos)
Low Priority (2-3)
B00A - R1010 - Resources Store
Ceiling Structures/Linings Vermiculite
8360/B00A/R0024/Ceiling Structures/Linings/S13
7m2 All surfaces Friable Asbestos (5) Low (1)
Chrysotile (white asbestos)
Low Priority (2-3)
B00A - R1011 - General Learning Space
Wall Linings Internal Flat AC Sheeting
8360/B00A/R0024/Ceiling Structures/Linings/S13
10m2 West facing Good Condition (1) Low (1)
Chrysotile (white asbestos)
Low Priority (2-3)
Ceiling Structures/Linings Vermiculite
8360/B00A/R0024/Ceiling Structures/Linings/S13
53m2 All surfaces Friable Asbestos (5) Low (1)
Chrysotile (white asbestos)
Low Priority (2-3)
B00A - R1012 - General Storeroom
Ceiling Structures/Linings Vermiculite
8360/B00A/R0024/Ceiling Structures/Linings/S13
5m2 All surfaces Friable Asbestos (5) Low (1)
Chrysotile (white asbestos)
Low Priority (2-3)
B00A - R1013 - Computer Store
Ceiling Structures/Linings Vermiculite
8360/B00A/R0024/Ceiling Structures/Linings/S13
5m2 All surfaces Friable Asbestos (5) Low (1)
Chrysotile (white asbestos)
Low Priority (2-3)
B00A - R1014 - Cleaning Store - Distributed
Ceiling Structures/Linings Vermiculite
8360/B00A/R0024/Ceiling Structures/Linings/S13
3m2 All surfaces Friable Asbestos (5) Low (1)
Chrysotile (white asbestos)
Low Priority (2-3)
B00A - R1015 - Computer Learning Space
Ceiling Structures/Linings Vermiculite
8360/B00A/R0024/Ceiling Structures/Linings/S13
53m2 All surfaces Friable Asbestos (5) Low (1)
Chrysotile (white asbestos)
Low Priority (2-3)
B00A - R1016 - Stairs
Ceiling Structures/Linings Vermiculite
8360/B00A/R0024/Ceiling Structures/Linings/S13
24m2 All surfaces Friable Asbestos (5) Low (1)
Chrysotile (white asbestos)
Low Priority (2-3)
B00A - R1017 - Stairs
Ceiling Structures/Linings Vermiculite
8360/B00A/R0024/Ceiling Structures/Linings/S13
13m2 All surfaces Friable Asbestos (5) Low (1)
Chrysotile (white asbestos)
Low Priority (2-3)
B00A - R1018 - External Movement
No Asbestos
B00A - R1019 - Movement
No Asbestos
Register Issue Date : Friday, 24 Mar 2017 Page 5 of 338360 - Finley High School
ProductMaterial
Description ExtentLocation
ReferenceMaterial
ConditionRisk
Status
Sample No
ControlPriority
8360 Finley High School 2017
Test Result
B00B - Technological & Applied Studies - 1958 - Brick/Block (Brick/Block)
Exterior
Underfloor Voids - Packing to Floor Joists
No Asbestos Found
Ceiling Voids - Flat Roof No Asbestos Found
Eaves Linings Flat AC Sheeting
8360/B00D/R0004/Ceiling Structures/Linings/S3
40m2 Variable positions
Minimal Damage (2) Low (1)
Chrysotile (white asbestos) , Amosite (brown
asbestos)
Low Priority (2-3)
Interior
B00B - R0002 - Toilets-Girls
Ceiling Structures/Linings Vermiculite
8360/B00B/R0001/Ceiling Structures/Linings/S9 No Asbestos Detected
Partition Walls (Cubicles) Compressed AC Sheet
8360/B00H/R0010/Partition Walls (Cubicles)/S5 No Asbestos Detected
Incinerator Encapsulated Insulation material within unit
Assumed Asbestos - Area inaccessible Not sampled due to
1Unit(s) North facing Friable Asbestos (5) Low (1) Low Priority (2-3)
B00B - R0003 - Cleaning Store - Distributed
Ceiling Structures/Linings Vermiculite
8360/B00B/R0001/Ceiling Structures/Linings/S9 No Asbestos Detected
B00B - R0004 - Distribution Board Cupboard Note: No inspection of live electrical installation.
Electrical Mounting Board Resinous Board
Assumed Asbestos - Not able to sampled due to live
2Unit Variable positions
Good Condition (1) Low (1) Low Priority (2-3)
Door Lining Flat AC Sheeting
8360/B00B/R0004/Door Lining/S16
4m2 All surfaces Good Condition (1) Low (1)
Chrysotile (white asbestos) , Amosite (brown
asbestos)
Low Priority (2-3)
B00B - R0005 - Toilets-Boys
Ceiling Structures/Linings Vermiculite
8360/B00B/R0001/Ceiling Structures/Linings/S9 No Asbestos Detected
Partition Walls (Cubicles) Compressed AC Sheet
8360/B00H/R0010/Partition Walls (Cubicles)/S5 No Asbestos Detected
B00B - R0006 - General Storeroom
Wall Linings Internal Flat AC Sheeting
Assumed Asbestos - Wall lining unable to be sampled due
to proximity of staff and students, sampling should be
4m2 East facing, West facing
Some Damage / Unsealed (3)
Low (1) Low Priority (2-3)
B00B - R0007 - Staff Study
Ceiling Structures/Linings Vermiculite
8360/B00B/R0001/Ceiling Structures/Linings/S9 No Asbestos Detected
Floor Coverings Res/Textile
Vinyl Tiles
8360/B00B/R0007/Floor Coverings Res/Textile/S10 No Asbestos Detected
B00B - R0008 - Staff Study
Ceiling Structures/Linings Vermiculite
8360/B00B/R0001/Ceiling Structures/Linings/S9 No Asbestos Detected
Floor Coverings Res/Textile
Vinyl Tiles
8360/B00B/R0007/Floor Coverings Res/Textile/S10 No Asbestos Detected
B00B - R0009 - Staff Study
Ceiling Structures/Linings Vermiculite
8360/B00B/R0001/Ceiling Structures/Linings/S9 No Asbestos Detected
Register Issue Date : Friday, 24 Mar 2017 Page 6 of 338360 - Finley High School
ProductMaterial
Description ExtentLocation
ReferenceMaterial
ConditionRisk
Status
Sample No
ControlPriority
8360 Finley High School 2017
Test Result
Floor Coverings Res/Textile
Vinyl Tiles
8360/B00B/R0007/Floor Coverings Res/Textile/S10 No Asbestos Detected
B00B - R0010 - Staff Study
Ceiling Structures/Linings Vermiculite
8360/B00B/R0001/Ceiling Structures/Linings/S9 No Asbestos Detected
B00B - R0011 - Staff Study
Ceiling Structures/Linings Vermiculite
8360/B00B/R0001/Ceiling Structures/Linings/S9 No Asbestos Detected
Floor Coverings Res/Textile
Vinyl Tiles
8360/B00B/R0007/Floor Coverings Res/Textile/S10 No Asbestos Detected
B00B - R0012 - Distribution Board Cupboard Note: No inspection of live electrical installation.
Electrical Mounting Board Resinous Board
Assumed Asbestos - Not able to sampled due to live
1Unit East facing Good Condition (1) Low (1) Low Priority (2-3)
B00B - R0013 - Food Technology L.S.
Ceiling Structures/Linings Vermiculite
8360/B00B/R0001/Ceiling Structures/Linings/S9 No Asbestos Detected
B00B - R0019 - General Storeroom
Ceiling Structures/Linings Vermiculite
8360/B00B/R0001/Ceiling Structures/Linings/S9 No Asbestos Detected
Floor Coverings Res/Textile
Vinyl Tiles
8360/B00B/R0007/Floor Coverings Res/Textile/S10 No Asbestos Detected
B00B - R0020 - Cleaning Store - Distributed
Ceiling Structures/Linings Vermiculite
8360/B00B/R0001/Ceiling Structures/Linings/S9 No Asbestos Detected
Floor Coverings Res/Textile
Vinyl Tiles
8360/B00B/R0007/Floor Coverings Res/Textile/S10 No Asbestos Detected
B00B - R0021 - Stairs
Ceiling Structures/Linings Vermiculite
8360/B00B/R0001/Ceiling Structures/Linings/S9 No Asbestos Detected
B00B - R0022 - Stairs
Ceiling Structures/Linings Vermiculite
8360/B00B/R0001/Ceiling Structures/Linings/S9 No Asbestos Detected
B00B - R0023 - Lift
No Asbestos
B00B - R0024 - External Movement
No Asbestos
B00B - R0025 - Movement
No Asbestos
B00B - R0026 - Movement
No Asbestos
B00B - R0027 - Materials Store - Type 1
No Asbestos
B00B - R0028 - Laundry
No Asbestos
B00B - R0029 - Food Technology L.S.
No Asbestos
B00B - R0030 - Pantry
No Asbestos
B00B - R0031 - Preparation - Materials
Register Issue Date : Friday, 24 Mar 2017 Page 7 of 338360 - Finley High School
ProductMaterial
Description ExtentLocation
ReferenceMaterial
ConditionRisk
Status
Sample No
ControlPriority
8360 Finley High School 2017
Test Result
No Asbestos
B00B - R1002 - Staff Study
Ceiling Structures/Linings Vermiculite
8360/B00B/R0001/Ceiling Structures/Linings/S9 No Asbestos Detected
Floor Coverings Res/Textile
Vinyl Tiles
8360/B00B/R0007/Floor Coverings Res/Textile/S10 No Asbestos Detected
B00B - R1003 - Distribution Board Cupboard Note: No inspection of live electrical installation.
Electrical Mounting Board Resinous Board
Assumed Asbestos - Not able to sampled due to live
2Unit Variable positions
Good Condition (1) Low (1) Low Priority (2-3)
Ceiling Structures/Linings Flat AC Sheeting
8360/B00B/R1003/Ceiling Structures/Linings/S17
1m2 All surfaces Some Damage / Unsealed (3)
Low (1)
Chrysotile (white asbestos) , Amosite (brown
asbestos)
Low Priority (2-3)
Door lining No Asbestos Found
B00B - R1004 - Cleaning Store - Distributed
Ceiling Structures/Linings Vermiculite
8360/B00B/R0001/Ceiling Structures/Linings/S9 No Asbestos Detected
B00B - R1008 - Materials Technology L.S.
Ceiling Structures/Linings Vermiculite
8360/B00B/R0001/Ceiling Structures/Linings/S9 No Asbestos Detected
Floor Coverings Res/Textile
Vinyl Tiles
8360/B00B/R0007/Floor Coverings Res/Textile/S10 No Asbestos Detected
B00B - R1009 - Distribution Board Cupboard Note: No inspection of live electrical installation.
Door Lining Flat AC Sheeting
8360/B00B/R1009/Door Lining/S24
4m2 All surfaces Good Condition (1) Low (1)
Chrysotile (white asbestos)
Low Priority (2-3)
Electrical Mounting Board Resinous Board
Assumed Asbestos - Not able to sampled due to live
2Unit Variable positions
Good Condition (1) Low (1) Low Priority (2-3)
Ceiling Structures/Linings Flat AC Sheeting
Assumed Asbestos - Not able to be sampled due to height
1m2 All surfaces Some Damage / Unsealed (3)
Low (1) Low Priority (2-3)
B00B - R1010 - Resource/Project Store
Ceiling Structures/Linings Vermiculite
8360/B00B/R0001/Ceiling Structures/Linings/S9 No Asbestos Detected
Floor Coverings Res/Textile
Vinyl Tiles
8360/B00B/R0007/Floor Coverings Res/Textile/S10 No Asbestos Detected
B00B - R1011 - General Storeroom
Ceiling Structures/Linings Vermiculite
8360/B00B/R0001/Ceiling Structures/Linings/S9 No Asbestos Detected
Floor Coverings Res/Textile
Vinyl Tiles
8360/B00B/R0007/Floor Coverings Res/Textile/S10 No Asbestos Detected
B00B - R1012 - Art Learning Space
Ceiling Structures/Linings Vermiculite
8360/B00B/R0001/Ceiling Structures/Linings/S9 No Asbestos Detected
Floor Coverings Res/Textile
Vinyl Tiles
8360/B00B/R0007/Floor Coverings Res/Textile/S10 No Asbestos Detected
B00B - R1013 - Music Store
Register Issue Date : Friday, 24 Mar 2017 Page 8 of 338360 - Finley High School
ProductMaterial
Description ExtentLocation
ReferenceMaterial
ConditionRisk
Status
Sample No
ControlPriority
8360 Finley High School 2017
Test Result
Ceiling Structures/Linings Vermiculite
8360/B00B/R0001/Ceiling Structures/Linings/S9 No Asbestos Detected
Floor Coverings Res/Textile
Vinyl Tiles
8360/B00B/R0007/Floor Coverings Res/Textile/S10 No Asbestos Detected
B00B - R1014 - Music Learning Space
Ceiling Structures/Linings Vermiculite
8360/B00B/R0001/Ceiling Structures/Linings/S9 No Asbestos Detected
B00B - R1015 - Movement
Ceiling Structures/Linings Vermiculite
8360/B00B/R0001/Ceiling Structures/Linings/S9 No Asbestos Detected
B00B - R1016 - Movement
Ceiling Structures/Linings Vermiculite
8360/B00B/R0001/Ceiling Structures/Linings/S9 No Asbestos Detected
B00B - R1017 - Lift
No Asbestos
B00B - R1018 - Toilet - Lobby
No Asbestos
B00B - R1019 - Toilet - Lobby
No Asbestos
B00B - R1020 - Staff - Toilet
No Asbestos
B00B - R1021 - Staff - Toilet
No Asbestos
B00B - R1022 - Computer Store
No Asbestos
B00B - R1023 - Commonroom
No Asbestos
B00B - R1024 - Movement
No Asbestos
B00B - R1025 - Movement
No Asbestos
Register Issue Date : Friday, 24 Mar 2017 Page 9 of 338360 - Finley High School
ProductMaterial
Description ExtentLocation
ReferenceMaterial
ConditionRisk
Status
Sample No
ControlPriority
8360 Finley High School 2017
Test Result
B00C - Pupil Facilities - 1958 - Brick/Block (Brick/Block)
Exterior
Ceiling Voids - Flat Roof No Asbestos Found
Underfloor Voids - Packing to Floor Joists
No Asbestos Found
Interior
B00C - R0001 - Multi-Purpose Space
Ceiling Structures/Linings No Asbestos Found
B00C - R0002 - Toilets-Boys
Ceiling Structures/Linings Flat AC Sheeting
8360/B00C/R0002/Ceiling Structures/Linings/S18
60m2 All surfaces Good Condition (1) Low (1)
Chrysotile (white asbestos) , Amosite (brown
asbestos)
Low Priority (2-3)
Partition Walls (Cubicles) Compressed AC Sheet
8360/B00C/R0002/Partition Walls (Cubicles)/S1
20m2 All surfaces Minimal Damage (2) Low (1)
Chrysotile (white asbestos) , Amosite (brown
asbestos)
Low Priority (2-3)
B00C - R0004 - Movement
Ceiling Structures/Linings Flat AC Sheeting
8360/B00C/R0004/Ceiling Structures/Linings/S25
14m2 All surfaces Good Condition (1) Low (1)
Chrysotile (white asbestos)
Low Priority (2-3)
B00C - R0005 - Shower/Change
Ceiling Structures/Linings Flat AC Sheeting
Assumed Asbestos - Not able to be sampled due to height
29m2 All surfaces Good Condition (1) Low (1) Low Priority (2-3)
B00C - R0006 - Cleaning Store - Distributed
Ceiling Structures/Linings Flat AC Sheeting
8360/B00C/R0004/Ceiling Structures/Linings/S25
5m2 All surfaces Good Condition (1) Low (1)
Chrysotile (white asbestos)
Low Priority (2-3)
B00C - R0007 - General Storeroom
Ceiling Structures/Linings Flat AC Sheeting
8360/B00C/R0007/Ceiling Structures/Linings/S26
7m2 All surfaces Good Condition (1) Low (1)
Chrysotile (white asbestos)
Low Priority (2-3)
B00C - R0008 - General Storeroom
Ceiling Structures/Linings Flat AC Sheeting
8360/B00C/R0007/Ceiling Structures/Linings/S26
12m2 All surfaces Good Condition (1) Low (1)
Chrysotile (white asbestos)
Low Priority (2-3)
B00C - R0009 - Shower/Change
Ceiling Structures/Linings Flat AC Sheeting
8360/B00C/R0009/Ceiling Structures/Linings/S27
29m2 All surfaces Good Condition (1) Low (1)
Chrysotile (white asbestos)
Low Priority (2-3)
Partition Walls (Cubicles) Compressed AC Sheet
8360/B00C/R0002/Partition Walls (Cubicles)/S1
10m2 All surfaces Minimal Damage (2) Low (1)
Chrysotile (white asbestos) , Amosite (brown
asbestos)
Low Priority (2-3)
B00C - R0010 - Cleaning Store - Distributed
Ceiling Structures/Linings Flat AC Sheeting
8360/B00C/R0009/Ceiling Structures/Linings/S27
5m2 All surfaces Good Condition (1) Low (1)
Chrysotile (white asbestos)
Low Priority (2-3)
B00C - R0011 - Toilets-Girls
Ceiling Structures/Linings Flat AC Sheeting
8360/B00C/R0011/Ceiling Structures/Linings/S28
93m2 All surfaces Good Condition (1) Low (1)
Chrysotile (white asbestos)
Low Priority (2-3)
Partition Walls (Cubicles) Compressed AC Sheet
8360/B00C/R0002/Partition Walls (Cubicles)/S1
24m2 All surfaces Minimal Damage (2) Low (1)
Chrysotile (white asbestos) , Amosite (brown
asbestos)
Low Priority (2-3)
Register Issue Date : Friday, 24 Mar 2017 Page 10 of 338360 - Finley High School
ProductMaterial
Description ExtentLocation
ReferenceMaterial
ConditionRisk
Status
Sample No
ControlPriority
8360 Finley High School 2017
Test Result
B00C - R0012 - General Storeroom
Ceiling Structures/Linings Flat AC Sheeting
8360/B00C/R0011/Ceiling Structures/Linings/S28
13m2 All surfaces Good Condition (1) Low (1)
Chrysotile (white asbestos)
Low Priority (2-3)
B00C - R0013 - External Movement
No Asbestos
B00C - R0014 - External Movement
No Asbestos
Register Issue Date : Friday, 24 Mar 2017 Page 11 of 338360 - Finley High School
ProductMaterial
Description ExtentLocation
ReferenceMaterial
ConditionRisk
Status
Sample No
ControlPriority
8360 Finley High School 2017
Test Result
B00D - General Learning - 1958 - Timber (Timber)
Exterior
Ceiling Voids - Flat Roof No Asbestos Found
Eaves Linings Flat AC Sheeting
8360/B00D/R0004/Ceiling Structures/Linings/S3
70m2 All surfaces Minimal Damage (2) Low (1)
Chrysotile (white asbestos) , Amosite (brown
asbestos)
Low Priority (2-3)
Wall Cladding Flat AC Sheeting
8360/B00D/R0004/Ceiling Structures/Linings/S3
12m2 Variable positions
Good Condition (1) Low (1)
Chrysotile (white asbestos) , Amosite (brown
asbestos)
Low Priority (2-3)
Underfloor Voids No Asbestos Found
Interior
B00D - R0001 - Cleaning Store - Distributed
Ceiling Structures/Linings Flat AC Sheeting
8360/B00D/R0004/Ceiling Structures/Linings/S3
7m2 All surfaces Good Condition (1) Low (1)
Chrysotile (white asbestos) , Amosite (brown
asbestos)
Low Priority (2-3)
B00D - R0002 - Resource/Project Store
Electrical cupboard lining No Asbestos Found
Electrical Backing Board No Asbestos Found
B00D - R0003 - Staff Study
No Asbestos
B00D - R0004 - Movement
Floor Coverings Res/Textile
Compressed AC Sheet
8360/B00E/R0001/Floor Coverings Res/Textile/S2
163m2 All surfaces Good Condition (1) Low (1)
Chrysotile (white asbestos) , Amosite (brown
asbestos)
Low Priority (2-3)
Ceiling Structures/Linings Flat AC Sheeting
8360/B00D/R0004/Ceiling Structures/Linings/S3
163m2 All surfaces Good Condition (1) Low (1)
Chrysotile (white asbestos) , Amosite (brown
asbestos)
Low Priority (2-3)
Electrical cabinet lining No Asbestos Found
Electrical Backing Board No Asbestos Found
B00D - R0005 - General Learning Space
No Asbestos
B00D - R0006 - General Learning Space
No Asbestos
B00D - R0007 - General Learning Space
Panel next to heater No Asbestos Found
B00D - R0008 - General Learning Space
Wall Linings Internal No Asbestos Found
B00D - R0009 - Staff Study
No Asbestos
B00D - R0010 - General Learning Space
No Asbestos
B00D - R0011 - General Learning Space
Wall Linings Internal No Asbestos Found
B00D - R0012 - Darkroom Space
No Asbestos
B00D - R0013 - General Learning Space
No Asbestos
B00D - R0014 - General Learning Space
No Asbestos
Register Issue Date : Friday, 24 Mar 2017 Page 12 of 338360 - Finley High School
ProductMaterial
Description ExtentLocation
ReferenceMaterial
ConditionRisk
Status
Sample No
ControlPriority
8360 Finley High School 2017
Test Result
B00D - R0015 - General Storeroom
Wall Linings Internal Flat AC Sheeting
8360/B00D/R0004/Ceiling Structures/Linings/S3
12m2 South facing Some Damage / Unsealed (3)
Low (1)
Chrysotile (white asbestos) , Amosite (brown
asbestos)
Low Priority (2-3)
Register Issue Date : Friday, 24 Mar 2017 Page 13 of 338360 - Finley High School
ProductMaterial
Description ExtentLocation
ReferenceMaterial
ConditionRisk
Status
Sample No
ControlPriority
8360 Finley High School 2017
Test Result
B00E - Senior Learning - 1890 - Timber (Timber)
Exterior
Ceiling Voids - Flat Roof No Asbestos Found
Underfloor Voids - Packing to Floor Joists
No Asbestos Found
Interior
B00E - R0001 - Movement
Floor Coverings Res/Textile
Compressed AC Sheet
8360/B00E/R0001/Floor Coverings Res/Textile/S2
20m2 All surfaces Good Condition (1) Low (1)
Chrysotile (white asbestos) , Amosite (brown
asbestos)
Low Priority (2-3)
B00E - R0002 - General Learning Space
Wall Linings Internal Flat AC Sheeting
Assumed Asbestos - Wall lining unable to be sampled due
to proximity of staff and students, sampling should be
2m2 South facing, East facing
Good Condition (1) Low (1) Low Priority (2-3)
Wall Linings Internal No Asbestos Found
B00E - R0003 - Resource/Project Store
No Asbestos
Register Issue Date : Friday, 24 Mar 2017 Page 14 of 338360 - Finley High School
ProductMaterial
Description ExtentLocation
ReferenceMaterial
ConditionRisk
Status
Sample No
ControlPriority
8360 Finley High School 2017
Test Result
B00F - Pupil Facilities - 1958 - Timber (Timber)
Exterior
Ceiling Voids - Flat Roof No Asbestos Found
Eaves Linings Flat AC Sheeting
8360/B00D/R0004/Ceiling Structures/Linings/S3
25m2 All surfaces Minimal Damage (2) Low (1)
Chrysotile (white asbestos) , Amosite (brown
asbestos)
Low Priority (2-3)
Underfloor Voids - Slab on Ground
No Asbestos Found
Wall Cladding No Asbestos Found
Interior
B00F - R0001 - Movement
No Asbestos
B00F - R0002 - Student Canteen
Wall Linings Internal Flat AC Sheeting
8360/B00F/R0002/Wall Linings Internal/S12
30m2 Variable positions
Good Condition (1) Low (1)
Chrysotile (white asbestos)
Low Priority (2-3)
Ceiling Structures/Linings Flat AC Sheeting
8360/B00F/R0002/Wall Linings Internal/S12
10m2 Variable positions
Good Condition (1) Low (1)
Chrysotile (white asbestos)
Low Priority (2-3)
B00F - R0003 - Office/Store
No Asbestos
B00F - R0004 - General Storeroom
Ceiling Structures/Linings Flat AC Sheeting
8360/B00F/R0002/Wall Linings Internal/S12
6m2 Variable positions
Good Condition (1) Low (1)
Chrysotile (white asbestos)
Low Priority (2-3)
Wall Linings Internal Flat AC Sheeting
8360/B00F/R0002/Wall Linings Internal/S12
15m2 Variable positions
Good Condition (1) Low (1)
Chrysotile (white asbestos)
Low Priority (2-3)
B00F - R0006 - Staff - Toilet
No Asbestos
B00F - R0007 - Movement
No Asbestos
B00F - R0008 - Movement
No Asbestos
Register Issue Date : Friday, 24 Mar 2017 Page 15 of 338360 - Finley High School
ProductMaterial
Description ExtentLocation
ReferenceMaterial
ConditionRisk
Status
Sample No
ControlPriority
8360 Finley High School 2017
Test Result
B00G - General Learning - 1958 - Timber (Timber)
Exterior
Underfloor Voids - Packing to Floor Joists
No Asbestos Found
Ceiling Voids - Flat Roof No Asbestos Found
Interior
B00G - R0001 - Movement
Ceiling Structures/Linings Flat AC Sheeting
8360/B00D/R0004/Ceiling Structures/Linings/S3
65m2 All surfaces Good Condition (1) Low (1)
Chrysotile (white asbestos) , Amosite (brown
asbestos)
Low Priority (2-3)
Floor Coverings Res/Textile
Compressed AC Sheet
8360/B00E/R0001/Floor Coverings Res/Textile/S2
65m2 All surfaces Good Condition (1) Low (1)
Chrysotile (white asbestos) , Amosite (brown
asbestos)
Low Priority (2-3)
Wall Linings Internal Flat AC Sheeting
8360/B00D/R0004/Ceiling Structures/Linings/S3
6m2 North facing, South facing
Good Condition (1) Low (1)
Chrysotile (white asbestos) , Amosite (brown
asbestos)
Low Priority (2-3)
B00G - R0002 - General Learning Space
Wall Linings Internal No Asbestos Found
B00G - R0003 - General Learning Space
Wall Linings Internal No Asbestos Found
B00G - R0004 - General Learning Space
Wall Linings Internal Flat AC Sheeting
8360/B00D/R0004/Ceiling Structures/Linings/S3
2m2 North facing, West facing
Good Condition (1) Low (1)
Chrysotile (white asbestos) , Amosite (brown
asbestos)
Low Priority (2-3)
B00G - R0005 - General Learning Space
Wall Linings Internal Flat AC Sheeting
8360/B00D/R0004/Ceiling Structures/Linings/S3
3m2 Variable positions
Good Condition (1) Low (1)
Chrysotile (white asbestos) , Amosite (brown
asbestos)
Low Priority (2-3)
Register Issue Date : Friday, 24 Mar 2017 Page 16 of 338360 - Finley High School
ProductMaterial
Description ExtentLocation
ReferenceMaterial
ConditionRisk
Status
Sample No
ControlPriority
8360 Finley High School 2017
Test Result
B00H - Multi Purpose Facilities - 1985 - Brick/Veneer (Brick/Veneer)
Exterior
Underfloor Voids - Slab on Ground
No Asbestos Found
Ceiling Voids - Flat Roof No Asbestos Found
Interior
B00H - R0001 - Sport Equipment Store
No Asbestos
B00H - R0002 - Multi-Purpose Space
No Asbestos
B00H - R0003 - Chair Store
No Asbestos
B00H - R0004 - Toilets-Disabled
No Asbestos
B00H - R0005 - Distribution Board Cupboard Note: No inspection of live electrical installation.
No Asbestos
B00H - R0006 - Movement
No Asbestos
B00H - R0007 - Shower/Change
Floor Coverings Res/Textile
Vinyl Tiles
8360/B00H/R0014/Floor Coverings Res/Textile/S6 No Asbestos Detected
Partition Walls (Cubicles) Compressed AC Sheet
8360/B00H/R0010/Partition Walls (Cubicles)/S5 No Asbestos Detected
B00H - R0008 - Sport Equipment Store
No Asbestos
B00H - R0009 - Stage
No Asbestos
B00H - R0010 - Shower/Change
Floor Coverings Res/Textile
Vinyl Tiles
8360/B00H/R0014/Floor Coverings Res/Textile/S6 No Asbestos Detected
Partition Walls (Cubicles) Compressed AC Sheet
8360/B00H/R0010/Partition Walls (Cubicles)/S5 No Asbestos Detected
B00H - R0011 - Cleaning Store - Distributed
No Asbestos
B00H - R0012 - Movement
No Asbestos
B00H - R0013 - Staff Kitchen
Floor Coverings Res/Textile
Vinyl Tiles
8360/B00H/R0014/Floor Coverings Res/Textile/S6 No Asbestos Detected
B00H - R0014 - General Storeroom
Floor Coverings Res/Textile
Vinyl Tiles
8360/B00H/R0014/Floor Coverings Res/Textile/S6 No Asbestos Detected
B00H - R0015 - Staff Study
Floor Coverings Res/Textile
Vinyl Tiles
8360/B00H/R0014/Floor Coverings Res/Textile/S6 No Asbestos Detected
B00H - R0016 - Movement
No Asbestos
Register Issue Date : Friday, 24 Mar 2017 Page 17 of 338360 - Finley High School
ProductMaterial
Description ExtentLocation
ReferenceMaterial
ConditionRisk
Status
Sample No
ControlPriority
8360 Finley High School 2017
Test Result
B00I - Agricultural Science - 1958 - Timber (Timber)
Exterior
Underfloor Voids - Packing to Floor Joists
No Asbestos Found
Ceiling Voids - Flat Roof No Asbestos Found
Eaves Linings Flat AC Sheeting
8360/B00I/Eaves Linings/S4
10m2 All surfaces Good Condition (1) Low (1)
Chrysotile (white asbestos) , Amosite (brown
asbestos)
Low Priority (2-3)
Electrical backing board Resinous Board
Assumed Asbestos - Not able to sampled due to live
1Unit(s) East facing Minimal Damage (2) Low (1) Low Priority (2-3)
Flooring Compressed AC Sheet
8360/B00E/R0001/Floor Coverings Res/Textile/S2
1m2 Redundant Step Minimal Damage (2) Low (1)
Chrysotile (white asbestos) , Amosite (brown
asbestos)
Low Priority (2-3)
Interior
B00I - R0001 - General Assistants
Wall Linings Internal Flat AC Sheeting
8360/B00I/Eaves Linings/S4
35m2 All surfaces Good Condition (1) Low (1)
Chrysotile (white asbestos) , Amosite (brown
asbestos)
Low Priority (2-3)
Ceiling Structures/Linings Flat AC Sheeting
8360/B00I/Eaves Linings/S4
17m2 All surfaces Good Condition (1) Low (1)
Chrysotile (white asbestos) , Amosite (brown
asbestos)
Low Priority (2-3)
B00I - R0002 - General Storeroom
Wall Linings Internal Flat AC Sheeting
8360/B00I/Eaves Linings/S4
30m2 All surfaces Good Condition (1) Low (1)
Chrysotile (white asbestos) , Amosite (brown
asbestos)
Low Priority (2-3)
Ceiling Structures/Linings Flat AC Sheeting
8360/B00I/Eaves Linings/S4
11m2 All surfaces Good Condition (1) Low (1)
Chrysotile (white asbestos) , Amosite (brown
asbestos)
Low Priority (2-3)
B00I - R0003 - Machine Storage
Wall Linings Internal Flat AC Sheeting
8360/B00I/Eaves Linings/S4
30m2 All surfaces Good Condition (1) Low (1)
Chrysotile (white asbestos) , Amosite (brown
asbestos)
Low Priority (2-3)
Ceiling Structures/Linings Flat AC Sheeting
8360/B00I/Eaves Linings/S4
12m2 All surfaces Good Condition (1) Low (1)
Chrysotile (white asbestos) , Amosite (brown
asbestos)
Low Priority (2-3)
B00I - R0004 - Class Tools Storage
Wall Linings Internal Flat AC Sheeting
8360/B00I/Eaves Linings/S4
20m2 All surfaces Good Condition (1) Low (1)
Chrysotile (white asbestos) , Amosite (brown
asbestos)
Low Priority (2-3)
Ceiling Structures/Linings Flat AC Sheeting
8360/B00I/Eaves Linings/S4
7m2 All surfaces Good Condition (1) Low (1)
Chrysotile (white asbestos) , Amosite (brown
asbestos)
Low Priority (2-3)
Register Issue Date : Friday, 24 Mar 2017 Page 18 of 338360 - Finley High School
ProductMaterial
Description ExtentLocation
ReferenceMaterial
ConditionRisk
Status
Sample No
ControlPriority
8360 Finley High School 2017
Test Result
B00J - Multi Purpose Facilities - 1993 - Brick/Veneer (Brick/Veneer)
Exterior
Underfloor Voids - Slab on Ground
No Asbestos Found
Ceiling Voids No Asbestos Found
Interior
B00J - R0001 - Movement
No Asbestos
B00J - R0002 - Multi-Purpose Space
Vinyl Tiles (Under Floor Covering/Carpet)
No Asbestos Found
B00J - R0003 - Staff Kitchen
No Asbestos
B00J - R0004 - Toilets-Girls
No Asbestos
B00J - R0005 - Senior Study
Vinyl Tiles (Under Floor Covering/Carpet)
No Asbestos Found
Register Issue Date : Friday, 24 Mar 2017 Page 19 of 338360 - Finley High School
ProductMaterial
Description ExtentLocation
ReferenceMaterial
ConditionRisk
Status
Sample No
ControlPriority
8360 Finley High School 2017
Test Result
B00L - Library/Science Learning - 1973 - Brick/Block (Brick/Block)
Exterior
Underfloor Voids - Packing to Floor Joists
No Asbestos Found
Ceiling Voids - Raked Ceiling
No Asbestos Found
Interior
B00L - M1001 - No Access
No Asbestos
B00L - M1002 - Special Learning Space
Ceiling Structures/Linings Vermiculite
8360/B00L/M1002/Ceiling Structures/Linings/S11 No Asbestos Detected
B00L - M1003 - Main Area
No Asbestos
B00L - M1004 - No Access
No Asbestos
B00L - M1005 - Staff Study
Ceiling Structures/Linings Vermiculite
8360/B00L/M1002/Ceiling Structures/Linings/S11 No Asbestos Detected
B00L - M1006 - No Access
No Asbestos
B00L - M1007 - Stairs
No Asbestos
B00L - M1008 - Stairs
No Asbestos
B00L - R0001 - Laboratory L.S.
Floor Coverings Res/Textile
Vinyl Tiles
8360/B00B/R0007/Floor Coverings Res/Textile/S10 No Asbestos Detected
Ceiling Structures/Linings Vermiculite
8360/B00L/M1002/Ceiling Structures/Linings/S11 No Asbestos Detected
B00L - R0002 - Plant
Gasket Fibrous Membrane
8360/B00L/R0002/Gaskets to pipework/S7
16Unit(s) Variable positions
Minimal Damage (2) Low (1)
Chrysotile (white asbestos)
Low Priority (2-3)
Drainage pipework Fibre Cement Pipe
8360/B00L/R0002/Drainage pipework/S20
1Unit(s) South facing Minimal Damage (2) Low (1)
Chrysotile (white asbestos) , Amosite (brown
asbestos)
Low Priority (2-3)
Gasket Rope material
8360/B00L/R0002/Gasket/S21
3Unit(s) To Flue Friable Asbestos (5) Medium (2)
Chrysotile (white asbestos)
Low Priority (2-3)
B00L - R0003 - Chemical Store
Floor Coverings Res/Textile
Vinyl Tiles
8360/B00B/R0007/Floor Coverings Res/Textile/S10 No Asbestos Detected
B00L - R0004 - Distribution Board Cupboard Note: No inspection of live electrical installation.
No Asbestos
B00L - R0005 - Laboratory L.S.
Floor Coverings Res/Textile
Vinyl Tiles
8360/B00B/R0007/Floor Coverings Res/Textile/S10 No Asbestos Detected
Ceiling Structures/Linings Vermiculite
8360/B00L/M1002/Ceiling Structures/Linings/S11 No Asbestos Detected
B00L - R0008 - Laboratory L.S.
Register Issue Date : Friday, 24 Mar 2017 Page 20 of 338360 - Finley High School
ProductMaterial
Description ExtentLocation
ReferenceMaterial
ConditionRisk
Status
Sample No
ControlPriority
8360 Finley High School 2017
Test Result
Floor Coverings Res/Textile
Vinyl Tiles
8360/B00B/R0007/Floor Coverings Res/Textile/S10 No Asbestos Detected
Ceiling Structures/Linings Vermiculite
8360/B00L/M1002/Ceiling Structures/Linings/S11 No Asbestos Detected
B00L - R0009 - Cleaning Store - Distributed
No Asbestos
B00L - R0010 - Movement
No Asbestos
B00L - R0011 - Laboratory L.S.
Floor Coverings Res/Textile
Vinyl Tiles
8360/B00B/R0007/Floor Coverings Res/Textile/S10 No Asbestos Detected
Ceiling Structures/Linings Vermiculite
8360/B00L/M1002/Ceiling Structures/Linings/S11 No Asbestos Detected
B00L - R0012 - Preparation
Floor Coverings Res/Textile
Vinyl Tiles
8360/B00B/R0007/Floor Coverings Res/Textile/S10 No Asbestos Detected
Ceiling Structures/Linings Vermiculite
8360/B00L/M1002/Ceiling Structures/Linings/S11 No Asbestos Detected
B00L - R0013 - Chemical Store
Floor Coverings Res/Textile
Vinyl Tiles
8360/B00B/R0007/Floor Coverings Res/Textile/S10 No Asbestos Detected
Ceiling Structures/Linings Vermiculite
8360/B00L/M1002/Ceiling Structures/Linings/S11 No Asbestos Detected
B00L - R0014 - Movement
Floor Coverings Res/Textile
Vinyl Tiles
8360/B00B/R0007/Floor Coverings Res/Textile/S10 No Asbestos Detected
B00L - R0015 - Stairs
No Asbestos
B00L - R0016 - Movement
No Asbestos
B00L - R0018 - Preparation
No Asbestos
B00L - R1001 - Seminar
No Asbestos
B00L - R1002 - No Access
No Asbestos
B00L - R1003 - No Access
No Asbestos
B00L - R1004 - Cleaning Store - Distributed
No Asbestos
B00L - R1006 - Movement
No Asbestos
B00L - R1007 - Distribution Board Cupboard Note: No inspection of live electrical installation.
No Asbestos
B00L - R1008 - Seminar
No Asbestos
B00L - R1009 - Seminar
No Asbestos
B00L - R1010 - Main Area
Register Issue Date : Friday, 24 Mar 2017 Page 21 of 338360 - Finley High School
ProductMaterial
Description ExtentLocation
ReferenceMaterial
ConditionRisk
Status
Sample No
ControlPriority
8360 Finley High School 2017
Test Result
Ceiling Structures/Linings Vermiculite
8360/B00L/M1002/Ceiling Structures/Linings/S11 No Asbestos Detected
B00L - R1011 - Audio Visual Workroom
No Asbestos
B00L - R1012 - Librarian
No Asbestos
B00L - R1013 - Workroom
No Asbestos
B00L - R1014 - Workroom
No Asbestos
B00L - R1016 - Movement
No Asbestos
B00L - R1018 - Main Area
Ceiling Structures/Linings Vermiculite
8360/B00L/M1002/Ceiling Structures/Linings/S11 No Asbestos Detected
B00L - R1019 - Stairs
No Asbestos
B00L - R1020 - Movement
No Asbestos
B00L - R1021 - Stairs
No Asbestos
B00L - R1022 - Stairs
No Asbestos
B00L - R1023 - Toilet - Lobby
No Asbestos
B00L - R1024 - Staff - Toilet
No Asbestos
B00L - R1025 - Toilet - Lobby
No Asbestos
B00L - R1026 - Staff - Toilet
No Asbestos
Register Issue Date : Friday, 24 Mar 2017 Page 22 of 338360 - Finley High School
ProductMaterial
Description ExtentLocation
ReferenceMaterial
ConditionRisk
Status
Sample No
ControlPriority
8360 Finley High School 2017
Test Result
B00N - Support Unit/Technological & Applied Studies - 1958 - Timber (Timber)
Exterior
Ceiling Voids - Flat Roof No Asbestos Found
Pillar Packing Flat AC Sheeting
8360/B00N/Stump packing/S8 No Asbestos Detected
Eaves Linings Flat AC Sheeting
8360/B00D/R0004/Ceiling Structures/Linings/S3
40m2 All surfaces Minimal Damage (2) Low (1)
Chrysotile (white asbestos) , Amosite (brown
asbestos)
Low Priority (2-3)
Underfloor Voids - Packing to Floor Joists
AC Fragments/Debris
8360/B00N/Underfloor Voids - Packing to Floor Joists/S23
2m2 Throughout Minimal Damage (2) Low (1)
Chrysotile (white asbestos)
Low Priority (2-3)
Interior
B00N - R0002 - Cleaning Store - Distributed
Ceiling Structures/Linings Flat AC Sheeting
8360/B00D/R0004/Ceiling Structures/Linings/S3
7m2 All surfaces Good Condition (1) Low (1)
Chrysotile (white asbestos) , Amosite (brown
asbestos)
Low Priority (2-3)
B00N - R0003 - General Learning Space
Wall Linings Internal No Asbestos Found
B00N - R0004 - General Learning Space
No Asbestos
B00N - R0005 - General Learning Space
Wall Linings Internal No Asbestos Found
B00N - R0008 - Distribution Board Cupboard Note: No inspection of live electrical installation.
Ceiling Structures/Linings Flat AC Sheeting
8360/B00D/R0004/Ceiling Structures/Linings/S3
1m2 All surfaces Good Condition (1) Low (1)
Chrysotile (white asbestos) , Amosite (brown
asbestos)
Low Priority (2-3)
Wall Linings Internal Flat AC Sheeting
8360/B00D/R0004/Ceiling Structures/Linings/S3
3m2 All surfaces Good Condition (1) Low (1)
Chrysotile (white asbestos) , Amosite (brown
asbestos)
Low Priority (2-3)
B00N - R0010 - Home Base Store - S
No Asbestos
B00N - R0011 - Home Base Store - S
No Asbestos
B00N - R0012 - General Learning Space - S/P
No Asbestos
B00N - R0013 - Seminar - Type 3
No Asbestos
B00N - R0014 - General Learning Space - S/P
No Asbestos
B00N - R0015 - Practical Activity Area
No Asbestos
B00N - R0016 - Staff Kitchen
Wall Linings Internal Flat AC Sheeting
8360/B00N/R0016/Wall Linings Internal/S22 No Asbestos Detected
B00N - R0017 - Student Laundry - Type 3
Wall Linings Internal Flat AC Sheeting
8360/B00N/Stump packing/S8 No Asbestos Detected
B00N - R0018 - Toilets-Disabled
Wall Linings Internal No Asbestos Found
B00N - R0019 - Movement
Register Issue Date : Friday, 24 Mar 2017 Page 23 of 338360 - Finley High School
ProductMaterial
Description ExtentLocation
ReferenceMaterial
ConditionRisk
Status
Sample No
ControlPriority
8360 Finley High School 2017
Test Result
Floor Coverings Res/Textile
Compressed AC Sheet
8360/B00E/R0001/Floor Coverings Res/Textile/S2
75m2 All surfaces Good Condition (1) Low (1)
Chrysotile (white asbestos) , Amosite (brown
asbestos)
Low Priority (2-3)
Ceiling Structures/Linings Flat AC Sheeting
8360/B00D/R0004/Ceiling Structures/Linings/S3
75m2 All surfaces Some Damage / Unsealed (3)
Low (1)
Chrysotile (white asbestos) , Amosite (brown
asbestos)
Low Priority (2-3)
B00N - R0020 - Movement
Ceiling Structures/Linings Flat AC Sheeting
8360/B00D/R0004/Ceiling Structures/Linings/S3
10m2 All surfaces Some Damage / Unsealed (3)
Low (1)
Chrysotile (white asbestos) , Amosite (brown
asbestos)
Low Priority (2-3)
Floor Coverings Res/Textile
Compressed AC Sheet
8360/B00E/R0001/Floor Coverings Res/Textile/S2
10m2 All surfaces Good Condition (1) Low (1)
Chrysotile (white asbestos) , Amosite (brown
asbestos)
Low Priority (2-3)
Wall Linings Internal Flat AC Sheeting
8360/B00D/R0004/Ceiling Structures/Linings/S3
4m2 West facing Good Condition (1) Low (1)
Chrysotile (white asbestos) , Amosite (brown
asbestos)
Low Priority (2-3)
Register Issue Date : Friday, 24 Mar 2017 Page 24 of 338360 - Finley High School
ProductMaterial
Description ExtentLocation
ReferenceMaterial
ConditionRisk
Status
Sample No
ControlPriority
8360 Finley High School 2017
Test Result
B00P - Senior Learning - 1958 - Timber (Timber)
Exterior
Ceiling Voids - Flat Roof No Asbestos Found
Electrical backing board Resinous Board
Assumed Asbestos - Not able to sampled due to live
1Unit(s) South facing Minimal Damage (2) Low (1) Low Priority (2-3)
Underfloor Voids - Slab on Ground
No Asbestos Found
Interior
B00P - R0001 - General Storeroom
Wall Linings Internal Flat AC Sheeting
8360/B00D/R0004/Ceiling Structures/Linings/S3
3m2 South facing Good Condition (1) Low (1)
Chrysotile (white asbestos) , Amosite (brown
asbestos)
Low Priority (2-3)
B00P - R0002 - Movement
Floor Coverings Res/Textile
Compressed AC Sheet
8360/B00E/R0001/Floor Coverings Res/Textile/S2
16m2 All surfaces Good Condition (1) Low (1)
Chrysotile (white asbestos) , Amosite (brown
asbestos)
Low Priority (2-3)
Ceiling Structures/Linings Flat AC Sheeting
8360/B00D/R0004/Ceiling Structures/Linings/S3
16m2 All surfaces Good Condition (1) Low (1)
Chrysotile (white asbestos) , Amosite (brown
asbestos)
Low Priority (2-3)
Wall Linings Internal Flat AC Sheeting
8360/B00D/R0004/Ceiling Structures/Linings/S3
4m2 North facing, South facing
Some Damage / Unsealed (3)
Low (1)
Chrysotile (white asbestos) , Amosite (brown
asbestos)
Low Priority (2-3)
B00P - R0003 - General Learning Space
Wall Linings Internal No Asbestos Found
B00P - R0004 - General Storeroom
No Asbestos
Register Issue Date : Friday, 24 Mar 2017 Page 25 of 338360 - Finley High School
ProductMaterial
Description ExtentLocation
ReferenceMaterial
ConditionRisk
Status
Sample No
ControlPriority
8360 Finley High School 2017
Test Result
B00Q - Technological & Applied Studies - 2007 - Brick/Veneer (Brick/Veneer)
Exterior
Underfloor Voids - Slab on Ground
No Asbestos Found
Ceiling Voids No Asbestos Found
Interior
B00Q - M0001 - Plant
No Asbestos
B00Q - R0001 - External Movement
No Asbestos
B00Q - R0002 - General Learning Space
No Asbestos
B00Q - R0003 - Seminar/Technology Space
No Asbestos
B00Q - R0004 - Workshop Area
No Asbestos
B00Q - R0005 - Entry
No Asbestos
B00Q - R0006 - Workshop Area
No Asbestos
B00Q - R0007 - Welding Area
No Asbestos
B00Q - R0008 - Welding Store
No Asbestos
B00Q - R0009 - Welding Store
No Asbestos
B00Q - R0010 - Bulk Store
No Asbestos
B00Q - R0011 - Dust Extraction Space
No Asbestos
B00Q - R0012 - Workshop Area
No Asbestos
B00Q - R0013 - Welding Area
No Asbestos
B00Q - R0014 - Welding Area
No Asbestos
B00Q - R0015 - Welding Area
No Asbestos
B00Q - R0016 - Project Store - Type 1
No Asbestos
B00Q - R0017 - Materials Store
No Asbestos
B00Q - R0018 - Plant
No Asbestos
Register Issue Date : Friday, 24 Mar 2017 Page 26 of 338360 - Finley High School
ProductMaterial
Description ExtentLocation
ReferenceMaterial
ConditionRisk
Status
Sample No
ControlPriority
8360 Finley High School 2017
Test Result
B00R - Art - 2008 - Metal Shed (Metal Shed)
Exterior
Underfloor Voids - Slab on Ground
No Asbestos Found
Ceiling Voids No Asbestos Found
Interior
B00R - R0001 - Art Learning Space
No Asbestos
Register Issue Date : Friday, 24 Mar 2017 Page 27 of 338360 - Finley High School
ProductMaterial
Description ExtentLocation
ReferenceMaterial
ConditionRisk
Status
Sample No
ControlPriority
8360 Finley High School 2017
Test Result
B0AG - Agricultural Science - 2009 - Brick/Veneer (Brick/Veneer)
Exterior
Underfloor Voids - Slab on Ground
No Asbestos Found
Ceiling Voids No Asbestos Found
Interior
B0AG - R0001 - Plant Space
No Asbestos
B0AG - R0002 - Class Tools Storage
No Asbestos
B0AG - R0003 - Agriculture Covered Area
No Asbestos
Register Issue Date : Friday, 24 Mar 2017 Page 28 of 338360 - Finley High School
ProductMaterial
Description ExtentLocation
ReferenceMaterial
ConditionRisk
Status
Sample No
ControlPriority
8360 Finley High School 2017
Test Result
BAG1 - Agricultural Science - 2011 - Steel (Steel)
Exterior
Underfloor Voids - Slab on Ground
No Asbestos Found
Ceiling Voids No Asbestos Found
Interior
BAG1 - R0001 - Agriculture Covered Area
No Asbestos
Register Issue Date : Friday, 24 Mar 2017 Page 29 of 338360 - Finley High School
ProductMaterial
Description ExtentLocation
ReferenceMaterial
ConditionRisk
Status
Sample No
ControlPriority
8360 Finley High School 2017
Test Result
BAG2 - Agricultural Science - 2011 - Brick/Veneer (Brick/Veneer)
Exterior
Underfloor Voids - Slab on Ground
No Asbestos Found
Ceiling Voids No Asbestos Found
Interior
BAG2 - R0001 - Toilets-Unisex
No Asbestos
BAG2 - R0002 - Toilet - Lobby
No Asbestos
Register Issue Date : Friday, 24 Mar 2017 Page 30 of 338360 - Finley High School
ProductMaterial
Description ExtentLocation
ReferenceMaterial
ConditionRisk
Status
Sample No
ControlPriority
8360 Finley High School 2017
Test Result
BAG3 - Agricultural Science - 2011 - Brick/Veneer (Brick/Veneer)
Exterior
Underfloor Voids - Slab on Ground
No Asbestos Found
Ceiling Voids No Asbestos Found
Interior
BAG3 - R0001 - Movement
No Asbestos
BAG3 - R0002 - Chemical Store
No Asbestos
Register Issue Date : Friday, 24 Mar 2017 Page 31 of 338360 - Finley High School
ProductMaterial
Description ExtentLocation
ReferenceMaterial
ConditionRisk
Status
Sample No
ControlPriority
8360 Finley High School 2017
Test Result
Demountables
Demountable details as per the AMS records as of 15 Feb 2017.
OS 759 - D16153 - Darkroom : Placement Date - 23/08/2005
Exterior
Step Treads Compressed AC Sheet Assumed Asbestos 1.08 m2
Landing Compressed AC Sheet Assumed Asbestos 1.2 m2
Eave Lining Flat AC Sheet Assumed Asbestos 2.88 m2
Interior
R1 - Darkroom Space
End wall panel Flat AC Sheet Assumed Asbestos 36 m2
Ceiling Flat AC Sheet Assumed Asbestos 18 m2
Register Issue Date : Friday, 24 Mar 2017 Page 32 of 338360 - Finley High School
ProductMaterial
Description ExtentLocation
ReferenceMaterial
ConditionRisk
Status
Sample No
ControlPriority
8360 Finley High School 2017
Test Result
Listing of Electronic Attachments as of 22/03/2017
There are no asbestos related file attachment(s) for this school.
Register Issue Date : Friday, 24 Mar 2017 Page 33 of 338360 - Finley High School