+ All Categories
Home > Documents > HCA HEALTH ONE, LLC 4500 E 9TH AVE STE 160 DENVER, CO …

HCA HEALTH ONE, LLC 4500 E 9TH AVE STE 160 DENVER, CO …

Date post: 14-Mar-2022
Category:
Upload: others
View: 0 times
Download: 0 times
Share this document with a friend
31
1. CONTRACTOR SHALL NOTIFY ARCHITECT IMMEDIATELY OF MATERIAL DISCREPANCIES FOUND IN THE DRAWINGS OR ANY EXISTING CONDITIONS FOUND ON THE SITE WHICH CONFLICT WITH CONDITIONS AS SHOWN IN THE CONTRACT DOCUMENTS. 2. DRAWINGS ARE NOT TO BE SCALED. DIMENSIONS INDICATED ON DRAWINGS TAKE PRECEDENCE. LARGE SCALE DRAWINGS TAKE PRECEDENCE OVER SMALLER SCALE DRAWINGS. NOTIFY THE ARCHITECT FOR CLARIFICATIONS. 3. ABBREVIATIONS THROUGHOUT THE DRAWINGS ARE THOSE IN COMMON USE. NOTIFY THE ARCHITECT OF ANY ABBREVIATIONS IN QUESTION. 4. CONTRACTOR TO COORDINATE THE WORK OF ALL TRADES 5. PROVIDE SOLID WOOD BLOCKING IN STUD WALLS AS REQUIRED TO SUPPORT WALL MOUNTED CABINETRY, COUNTERS, AND ALL OTHER COMPONENTS. 6. ALL CONCEALED INSULATION SHALL HAVE A FLAME SPREAD RATING OF 25 OR LESS AND A SMOKE DEVELOPED RATING OF 450 OR LESS IN ACCORDANCE WITH ASTM E84. 7. EXIT HARDWARE SHALL ALLOW FOR EGRESS AT ALL TIMES WITHOUT THE USE OF SPECIAL KNOWLEDGE OR EFFORT. 8. THE CONTRACTOR SHALL BRACE ENTIRE STRUCTURE AS REQUIRED DURING CONSTRUCTION TO MAINTAIN STABILITY UNTIL THE STRUCTURE IS COMPLETE AND FUNCTIONING AS THE DESIGNED UNIT. 9. THE ARCHITECT SHALL NOT BE RESPONSIBLE FOR THE MEANS, METHODS, TECHNIQUES, SEQUENCES, OR PROCEDURES OF CONSTRUCTION SELECTED AND UTILIZED BY CONTRACTOR. 10. THE CONTRACTOR WILL BE SOLELY AND COMPLETELY RESPONSIBLE FOR CONDITIONS OF THE JOB SITE INCLUDING SAFETY OF ALL PERSONS AND PROPERTY DURING PERFORMANCE OF THE WORK. THIS REQUIREMENT WILL APPLY CONTINUOUSLY AND NOT BE LIMITED TO NORMAL WORKING HOURS. THE ARCHITECT / ENGINEER HAVE NO RESPONSIBILITY FOR THE SAFETY OF PERSONNEL OR SAFE CONDITIONS AT THE SITE. 11. CONTRACTOR TO VERIFY ALL DIMENSIONS AND INFORMATION IN THESE DRAWINGS. CONTRACTOR TO COMPLY WITH ALL EXISTING CONDITIONS, INCLUDING BUILDINGS, SITE CONDITIONS AND SOIL BEARINGS PRESSURE. ALL ERRORS, OMISSIONS AND INCONSISTENCIES ARE TO BE REPORTED TO THE ARCHITECT BEFORE PROCEEDING WITH THE WORK. FAILURE TO DO SO WILL RELEASE THE ARCHITECT AND ENGINEERS OF ANY RESPONSIBILITY. ANY CHANGE FROM THESE DOCUMENTS ARE THE RESPONSIBILITY OF THE CONTRACTOR. THESE DRAWINGS ARE NOT TO BE SCALED. IF INSUFFICIENT INFORMATION EXISTS, CONTACT THE ARCHITECT FOR CLARIFICATION BEFORE PROCEEDING WITH THE WORK. 12. CONTRACTOR IS TO COMPLY WITH ALL APPLICABLE CODES AND SAFETY REGULATIONS. 13. EXTERIOR AND INTERIOR PLAN DIMENSIONS ARE TO FACE OF STUD FRAMING. PARTITIONS ARE 3 5/8" UNLESS NOTED OTHERWISE. 14. NOTCHES IN WALL STUDS ARE NOT TO EXCEED 1/4" OF THE STUD WIDTH, AND NO HOLES ARE TO BE GREATER THAN 40% OF THE STUD WIDTH. NO HOLES OR NOTCHES ARE ALLOWED IN BEAMS OR COLUMNS UNLESS APPROVED BY ARCHITECT. 15. FIRE STOPPING OF TWO INCH NOMINAL LUMBER SHALL BE PROVIDED TO FORM AN EFFECTIVE FIRE BARRIER BETWEEN ALL CONCEALED DRAFT OPENINGS, BOTH VERTICAL AND HORIZONTAL. 16. STRUCTURAL LUMBER EXPOSED TO THE EXTERIOR OR CONTACT WITH THE FOUNDATION TO BE PRESSURE TREATED. 17. ALL FINISHES IN EXIT ACCESS CORRIDOR/EXIT WAYS TO BE CLASS B. ALL FINISHES IN ROOMS/ENCLOSED SPACES TO BE CLASS C. 18. ALL WOOD BLOCKING TO BE FIRE RETARDANT TREATED. 19. AIR MOISTURE BARRIER OVER CMU AND EXTERIOR SHEATHING, REFER TO SPECIFICATIONS AND MANUFACTURER AND PRODUCTION INFORMATION. BUILDING DEPARTMENT: CITY OF DENVER - PLANNING & DEVELOPMENT 201 W. COLFAX AVE., DEPT 205 DENVER, CO 80202 CONTACT: INGRID ANTOINE PHONE: 720-865-2837 EMAIL: INGRID [email protected] BUILDING OWNER: CONTACT: KRISTIN CRITES-EKSTROM PHONE: 720-308-9215 EMAIL: [email protected] TENANT: QUEST DIAGNOSTICS NATIONAL PATIENT SERVICES 500 PLAZA DRIVE SECAUCUS, NJ 07094 CONTACT: BILL WILLIAMS PHONE: 813-927-9235 EMAIL: [email protected] TENANT REPRESENTATIVE: C2 CONSULTANTS 9160 HIGHWAY 64, SUITE 12 #189 LAKELAND, TN 38002 CONTACT: JOEY MARKHAM PHONE: 901-651-0204 EMAIL: [email protected] ARCHITECT: MS CONSULTANTS, INC. 2221 SCHROCK ROAD COLUMBUS, OH 43229 ARCHITECT OF RECORD: CHARLES M. BUSCH CONTACT: CATHY RAMONDELLI PHONE: 614-898-7100 EMAIL: [email protected] MEP ENGINEER: MS CONSULTANTS, INC. 2221 SCHROCK ROAD COLUMBUS, OH 43229 ENGINEER OF RECORD: JASON E. CHRISTOFF CONTACT: CATHY RAMONDELLI PHONE: 614-898-7100 EMAIL: [email protected] GENERAL EXISTING BUILDING 7-STORY BUSINESS CONSTRUCTION TYPE TYPE II-B OCCUPANCY GROUP BUSINESS FIRE PROTECTION SPRINKLERED TENANT SPACE 1-STORY (1ST FLOOR/GRADE LEVEL) GROSS SQ FT (TENANT SPACE) 1,024 SF PARKING EXISTING FINISHES: INTERIOR WALLS AND CEILINGS CLASS 'A' FLOOR FINISH CLASS "II" CODE REQUIREMENTS 2018 INTERNATIONAL BUILDING CODE (IBC) 2018 INTERNATIONAL FIRE CODE (IFC) 2018 INTERNATIONAL MECHANICAL CODE (IMC) 2018 INTERNATIONAL PLUMBING CODE (IPC) 2018 INTERNATIONAL ENERGY CONSERVATION CODE (IECC) 2018 INTERNATIONAL FUEL GAS CODE (IFGC) 2020 EDITION OF THE NATIONAL ELECTRICAL CODE (NEC) 2009 ICC A117.1 ACCESSIBLE & USABLE BUILDINGS & FACILITIES CODE 2018 INTERNATIONAL EXISTING BUILDING CODE (IEBC) OCCUPANCY LOAD CALCULATIONS OCC USE AREA FACTOR LOAD BUSINESS 1,024 SF 150 7 TOTAL 1,024 SF 7 EGRESS WIDTH REQUIREMENTS 0.2" x 7 = 1.4" = 32" MINIMUM REQUIRED 72" PROVIDED EGRESS EXIT REQUIREMENTS (≤49 OCCUPANTS) EXITS REQUIRED = 1 EXITS PROVIDED = 1 TRAVEL DISTANCE MAX DEAD END (SPRINKLERED) = 50'-0" MAX EGRESS TRAVEL (BUSINESS) = 100'-0" FIRE EXTINGUISHERS 1. EXTINGUISHERS SHALL BE 10 LB. CAPACITY, UL LABELED, ENAMEL STEEL CONTAINER WITH PRESSURE INDICATING GAUGE FOR CLASS A, B, OR C FIRES. 2. MAXIMUM SPACING TO BE 75 FEET APART ACCORDING TO IBC TABLE 906.3. TO BE WALL MOUNTED. 3. GENERAL CONTRACTOR TO COORDINATE FINAL LOCATIONS OF FIRE EXTINGUISHERS WITH LOCAL FIRE MARSHAL & SUBMIT DRAWING FOR BUILDING DEPARTMENT APPROVAL. TRAVEL DISTANCE = 55' - 2" ADJACENT TENANT (BUSINESS) FIRE EXTINGUISHERS ARE REQUIRED FOR EVERY 75 FEET FOR PATH OF TRAVEL SHARED HALLWAY S H A RE D HA LL W A Y EXIT EXIT TRAVEL T O EX IT = 63' - 4" X X AXX AXX X X X X X X X X X ? X 01 ? X - 01 DETAIL NUMBER "SIM" MARKER SHEET WHERE DETAIL IS SHOWN SHEET WHERE DETAIL IS SHOWN ELEVATION NUMBER DOOR TAG MATERIAL TAG KEY NOTE NUMBER PARTITION TYPE WINDOW NUMBER FURNITURE / EQUIPMENT NUMBER ELEVATION OR DATUM X AXX DETAIL NUMBER SHEET WHERE DETAIL IS SHOWN TYPICAL DETAIL TYPICAL ELEVATION TYPICAL WALL SECTION SHEET SHEET TITLE ISSUE DATE DRAWN BY CHECKED BY APPROVED BY PROJECT NO. REVISION PROFESSIONAL OF RECORD: NOTICE: THIS ARCHITECTURAL AND ENGINEERING DRAWING IS GIVEN IN CONFIDENCE AND SHALL BE USED ONLY PURSUANT TO THE AGREEMENT WI TH THE ARCHITECT. NO OTHER USE, DISSEMINATION, OR DUPLICATION MAY BE MADE WITHOUT PRIOR WRITTEN CONSENT OF THE ARCHITECT. ALL COMMON LAW RIGHTS OF COPYRIGHT AND OTHERWISE ARE HEREBY SPECIFICALLY RESERVED. CLIENT 2221 Schrock Road Columbus, Ohio 43229 - 1547 p 614.898.7100 f 614.898.7570 www.msconsultants.com PROJECT 10/5/2021 10:45:23 AM COVER SHEET G001 JPJ CHARLES M. BUSCH - RA No. ARC.00403518 EXP. DATE: 10/31/2021 10/04/2021 CLR/CMB 10/04/2021 62 - 40487 - 06 HCA HEALTH ONE, LLC 4500 E 9TH AVE STE 160 DENVER, CO 80220 QUEST DIAGNOSTICS HCA HEALTH ONE, LLC 4500 E 9TH AVE STE 160 DENVER, CO 80220 SITE CODE:G62 INDEX OF DRAWINGS G001 COVER SHEET G002 ACCESSIBILITY STANDARDS G003 COMCHECK SP001 SITE PLAN D101 DEMOLITION PLAN A101 FLOOR PLAN A111 REFLECTED CEILING PLAN A131 FURNITURE AND FINISH PLAN A210 INTERIOR ELEVATIONS A601 SCHEDULES AND DETAILS Q001 SPECIFICATIONS Q002 SPECIFICATIONS Q003 SPECIFICATIONS FP101 FIRE PROTECTION PLAN P001 PLUMBING GENERAL NOTES P002 PLUMBING SPECIFICATIONS P101 PLUMBING SANITARY PLAN P102 PLUMBING SUPPLY PLAN P601 PLUMBING SCHEDULES AND DETAILS M001 MECHANICAL GENERAL NOTES M002 MECHANICAL SPECIFICATIONS M003 MECHANICAL SPECIFICATIONS M101 MECHANICAL PLAN M601 MECHANICAL SCHEDULES AND DETAILS E001 ELECTRICAL SYMBOLS AND GENERAL NOTES E002 ELECTRICAL SPECIFICATIONS E101 ELECTRICAL POWER PLAN E201 ELECTRICAL LIGHTING PLAN E601 ELECTRICAL SCHEDULES FA001 FIRE ALARM GENERAL NOTES FA101 FIRE ALARM PLAN GENERAL NOTES SITE KEY PLAN PROJECT DIRECTORY QUEST DIAGNOSTICS E 9TH ST NORTH TOTAL FIXTURES PROVIDED 2 UNISEX 3 0 1 TOTAL FIXTURES REQUIRED 1 1 <15 NR 1 7 OCC 7/25 7/40 7/100 1 B - BUSINESS 1:25 (FIRST 50); 1:50 AFTER 1:40 (FIRST 80); 1:80 AFTER 1:100 1 REQUIRED USE GROUP WATER CLOSETS LAVATORIES DRINKING FOUNTAINS SERVICE SINK PLUMBING FIXTURE REQUIREMENTS PROJECT CODE DATA LIFE SAFETY PLAN 3/32" = 1'-0" SYMBOL LEGEND SCOPE OF WORK TENANT FIT OUT IN EXISTING SPACE. NEW PATIENT SERVICE CENTER FOR QUEST DIAGNOSTICS WILL BE CONSTRUCTED IN EXISTING GROUND FLOOR SUITE. THE PATIENT SERVICE CENTER IS AN OFFICE WHERE PATIENTS MAY COME TO HAVE BLOOD DRAWN OR TO LEAVE URINE SAMPLES. THERE IS NO LABORATORY WORK PERFORMED ON THE PREMISES; ALL SAMPLES ARE SAFELY STORED AND SENT TO QUEST DIAGNOSTICS LABORATORIES FOR PROCESSING. THE QUEST DIAGNOSTICS PATIENT SERVICE CENTER IS NOT A HEALTHCARE FACILITY SUCH AS A HOSPITAL OR OUTPATIENT CLINIC. QUEST DIAGNOSTICS CONTINUES TO EXPAND CONSUMER ACCESS TO HEALTHCARE SERVICES WHERE PEOPLE ALSO SHOP, MAKING IT EASIER FOR THEM TO GET THE QUALITY DIAGNOSTIC INSIGHTS THEY NEED IN CONVENIENT LOCATIONS. WHETHER USED FOR AN OCCASIONAL PHYSICAL EXAM, OR FOR DIAGNOSTIC PURPOSES, OR FOR MONITORING OF A PATIENT'S CONDITION DURING A SERIOUS ILLNESS, THE OFFICE'S LOCATION NEAR PEOPLE'S HOMES AND OFFICES WILL PROVE A GREAT CONVENIENCE AND WILL IMPROVE THE ACCESS OF THE COMMUNITY TO QUALITY HEALTHCARE SERVICES. # DATE DESCRIPTION CHERRY ST CLERMONT ST
Transcript

1. CONTRACTOR SHALL NOTIFY ARCHITECT IMMEDIATELY OF MATERIALDISCREPANCIES FOUND IN THE DRAWINGS OR ANY EXISTING CONDITIONSFOUND ON THE SITE WHICH CONFLICT WITH CONDITIONS AS SHOWN IN THECONTRACT DOCUMENTS.

2. DRAWINGS ARE NOT TO BE SCALED. DIMENSIONS INDICATED ON DRAWINGSTAKE PRECEDENCE. LARGE SCALE DRAWINGS TAKE PRECEDENCE OVERSMALLER SCALE DRAWINGS. NOTIFY THE ARCHITECT FOR CLARIFICATIONS.

3. ABBREVIATIONS THROUGHOUT THE DRAWINGS ARE THOSE IN COMMON USE.NOTIFY THE ARCHITECT OF ANY ABBREVIATIONS IN QUESTION.

4. CONTRACTOR TO COORDINATE THE WORK OF ALL TRADES5. PROVIDE SOLID WOOD BLOCKING IN STUD WALLS AS REQUIRED TO SUPPORT

WALL MOUNTED CABINETRY, COUNTERS, AND ALL OTHER COMPONENTS.6. ALL CONCEALED INSULATION SHALL HAVE A FLAME SPREAD RATING OF 25 OR

LESS AND A SMOKE DEVELOPED RATING OF 450 OR LESS IN ACCORDANCEWITH ASTM E84.

7. EXIT HARDWARE SHALL ALLOW FOR EGRESS AT ALL TIMES WITHOUT THE USEOF SPECIAL KNOWLEDGE OR EFFORT.

8. THE CONTRACTOR SHALL BRACE ENTIRE STRUCTURE AS REQUIRED DURINGCONSTRUCTION TO MAINTAIN STABILITY UNTIL THE STRUCTURE IS COMPLETEAND FUNCTIONING AS THE DESIGNED UNIT.

9. THE ARCHITECT SHALL NOT BE RESPONSIBLE FOR THE MEANS, METHODS,TECHNIQUES, SEQUENCES, OR PROCEDURES OF CONSTRUCTION SELECTEDAND UTILIZED BY CONTRACTOR.

10. THE CONTRACTOR WILL BE SOLELY AND COMPLETELY RESPONSIBLE FORCONDITIONS OF THE JOB SITE INCLUDING SAFETY OF ALL PERSONS ANDPROPERTY DURING PERFORMANCE OF THE WORK. THIS REQUIREMENT WILLAPPLY CONTINUOUSLY AND NOT BE LIMITED TO NORMAL WORKING HOURS. THEARCHITECT / ENGINEER HAVE NO RESPONSIBILITY FOR THE SAFETY OFPERSONNEL OR SAFE CONDITIONS AT THE SITE.

11. CONTRACTOR TO VERIFY ALL DIMENSIONS AND INFORMATION IN THESEDRAWINGS. CONTRACTOR TO COMPLY WITH ALL EXISTING CONDITIONS,INCLUDING BUILDINGS, SITE CONDITIONS AND SOIL BEARINGS PRESSURE. ALLERRORS, OMISSIONS AND INCONSISTENCIES ARE TO BE REPORTED TO THEARCHITECT BEFORE PROCEEDING WITH THE WORK. FAILURE TO DO SO WILLRELEASE THE ARCHITECT AND ENGINEERS OF ANY RESPONSIBILITY. ANYCHANGE FROM THESE DOCUMENTS ARE THE RESPONSIBILITY OF THECONTRACTOR. THESE DRAWINGS ARE NOT TO BE SCALED. IF INSUFFICIENTINFORMATION EXISTS, CONTACT THE ARCHITECT FOR CLARIFICATION BEFOREPROCEEDING WITH THE WORK.

12. CONTRACTOR IS TO COMPLY WITH ALL APPLICABLE CODES AND SAFETYREGULATIONS.

13. EXTERIOR AND INTERIOR PLAN DIMENSIONS ARE TO FACE OF STUD FRAMING.PARTITIONS ARE 3 5/8" UNLESS NOTED OTHERWISE.

14. NOTCHES IN WALL STUDS ARE NOT TO EXCEED 1/4" OF THE STUD WIDTH, ANDNO HOLES ARE TO BE GREATER THAN 40% OF THE STUD WIDTH. NO HOLES ORNOTCHES ARE ALLOWED IN BEAMS OR COLUMNS UNLESS APPROVED BYARCHITECT.

15. FIRE STOPPING OF TWO INCH NOMINAL LUMBER SHALL BE PROVIDED TO FORMAN EFFECTIVE FIRE BARRIER BETWEEN ALL CONCEALED DRAFT OPENINGS,BOTH VERTICAL AND HORIZONTAL.

16. STRUCTURAL LUMBER EXPOSED TO THE EXTERIOR OR CONTACT WITH THEFOUNDATION TO BE PRESSURE TREATED.

17. ALL FINISHES IN EXIT ACCESS CORRIDOR/EXIT WAYS TO BE CLASS B. ALLFINISHES IN ROOMS/ENCLOSED SPACES TO BE CLASS C.

18. ALL WOOD BLOCKING TO BE FIRE RETARDANT TREATED.19. AIR MOISTURE BARRIER OVER CMU AND EXTERIOR SHEATHING, REFER TO

SPECIFICATIONS AND MANUFACTURER AND PRODUCTION INFORMATION.

BUILDING DEPARTMENT:CITY OF DENVER - PLANNING & DEVELOPMENT201 W. COLFAX AVE., DEPT 205DENVER, CO 80202CONTACT: INGRID ANTOINE PHONE: 720-865-2837EMAIL: INGRID [email protected]

BUILDING OWNER:CONTACT: KRISTIN CRITES-EKSTROMPHONE: 720-308-9215EMAIL: [email protected]

TENANT:QUEST DIAGNOSTICSNATIONAL PATIENT SERVICES 500 PLAZA DRIVE SECAUCUS, NJ 07094CONTACT: BILL WILLIAMS PHONE: 813-927-9235EMAIL: [email protected]

TENANT REPRESENTATIVE:C2 CONSULTANTS9160 HIGHWAY 64, SUITE 12 #189LAKELAND, TN 38002CONTACT: JOEY MARKHAMPHONE: 901-651-0204EMAIL: [email protected]

ARCHITECT:MS CONSULTANTS, INC.2221 SCHROCK ROADCOLUMBUS, OH 43229ARCHITECT OF RECORD: CHARLES M. BUSCHCONTACT: CATHY RAMONDELLI PHONE: 614-898-7100EMAIL: [email protected]

MEP ENGINEER:MS CONSULTANTS, INC.2221 SCHROCK ROADCOLUMBUS, OH 43229ENGINEER OF RECORD: JASON E. CHRISTOFFCONTACT: CATHY RAMONDELLI PHONE: 614-898-7100EMAIL: [email protected]

GENERALEXISTING BUILDING 7-STORY BUSINESSCONSTRUCTION TYPE TYPE II-BOCCUPANCY GROUP BUSINESSFIRE PROTECTION SPRINKLEREDTENANT SPACE 1-STORY (1ST FLOOR/GRADE LEVEL)GROSS SQ FT (TENANT SPACE) 1,024 SFPARKING EXISTING FINISHES: INTERIOR WALLS AND CEILINGS CLASS 'A'FLOOR FINISH CLASS "II"

CODE REQUIREMENTS2018 INTERNATIONAL BUILDING CODE (IBC)2018 INTERNATIONAL FIRE CODE (IFC)2018 INTERNATIONAL MECHANICAL CODE (IMC)2018 INTERNATIONAL PLUMBING CODE (IPC)2018 INTERNATIONAL ENERGY CONSERVATION CODE (IECC)2018 INTERNATIONAL FUEL GAS CODE (IFGC)2020 EDITION OF THE NATIONAL ELECTRICAL CODE (NEC)2009 ICC A117.1 ACCESSIBLE & USABLE BUILDINGS & FACILITIES CODE2018 INTERNATIONAL EXISTING BUILDING CODE (IEBC)

OCCUPANCY LOAD CALCULATIONSOCC USE AREA FACTOR LOADBUSINESS 1,024 SF 150 7TOTAL 1,024 SF 7

EGRESS WIDTH REQUIREMENTS0.2" x 7 = 1.4" = 32" MINIMUM REQUIRED

72" PROVIDED

EGRESS EXIT REQUIREMENTS (≤49 OCCUPANTS)EXITS REQUIRED = 1EXITS PROVIDED = 1

TRAVEL DISTANCEMAX DEAD END (SPRINKLERED) = 50'-0"MAX EGRESS TRAVEL (BUSINESS) = 100'-0"

FIRE EXTINGUISHERS1. EXTINGUISHERS SHALL BE 10 LB. CAPACITY, UL LABELED, ENAMEL STEEL

CONTAINER WITH PRESSURE INDICATING GAUGE FOR CLASS A, B, OR C FIRES.2. MAXIMUM SPACING TO BE 75 FEET APART ACCORDING TO IBC TABLE 906.3. TO

BE WALL MOUNTED.3. GENERAL CONTRACTOR TO COORDINATE FINAL LOCATIONS OF FIRE

EXTINGUISHERS WITH LOCAL FIRE MARSHAL & SUBMIT DRAWING FORBUILDING DEPARTMENT APPROVAL.

TRAVEL DISTANCE = 55' - 2"

ADJACENT TENANT (BUSINESS)

FIRE EXTINGUISHERS ARE REQUIRED FOR EVERY 75 FEET FOR PATH OF TRAVEL

SHAR

ED H

ALLW

AY

SHARED HALLWAY

EXIT

EXITTRAVEL TO EXIT = 63' - 4"

XX

AXX

AXX

X X

X

X

X X

X

X

X

?

X

01

?

X-01

DETAIL NUMBER"SIM" MARKER

SHEET WHERE DETAIL IS SHOWN

SHEET WHERE DETAIL IS SHOWN

ELEVATION NUMBER

DOOR TAG

MATERIAL TAG

KEY NOTE NUMBER

PARTITION TYPE

WINDOW NUMBER

FURNITURE / EQUIPMENT NUMBER

ELEVATION OR DATUM

XAXX

DETAIL NUMBER

SHEET WHERE DETAIL IS SHOWN

TYPICAL DETAIL

TYPICAL ELEVATION

TYPICAL WALL SECTION

SHEET

SHEET TITLE

ISSUE DATE

DRAWN BY

CHECKED BYAPPROVED BY

PROJECT NO.

REVISION

PROFESSIONAL OF RECORD:NOTIC

E: THIS

ARCHIT

ECTURAL A

ND E

NGIN

EERIN

G D

RAW

ING IS G

IVEN IN C

ONFID

ENCE A

ND S

HALL B

E U

SED O

NLY P

URSUANT T

O T

HE A

GREEMENT W

ITH T

HE A

RCHIT

ECT. NO O

THER U

SE, DIS

SEMIN

ATIO

N, OR D

UPLIC

ATIO

N M

AY B

E M

ADE W

ITHOUT P

RIO

R W

RIT

TEN

CONSENT O

F T

HE A

RCHIT

ECT. ALL C

OMMON L

AW

RIG

HTS O

F C

OPYRIG

HT A

ND O

THERW

ISE A

RE H

EREBY S

PECIF

ICALLY R

ESERVED.

CLIENT

2221 Schrock RoadColumbus, Ohio 43229-1547p 614.898.7100f 614.898.7570www.msconsultants.com

PROJECT

10/5

/202

1 10

:45:

23 A

M

COVER SHEET

G001

JPJ

CHARLES M. BUSCH - RA No. ARC.00403518EXP. DATE: 10/31/2021

10/04/2021

CLR/CMB

10/04/2021

62-40487-06

HCA HEALTH ONE, LLC4500 E 9TH AVESTE 160DENVER, CO 80220

QUESTDIAGNOSTICS

HCA HEALTH ONE, LLC4500 E 9TH AVE

STE 160DENVER, CO 80220

SITE CODE:G62

INDEX OF DRAWINGSG001 COVER SHEETG002 ACCESSIBILITY STANDARDSG003 COMCHECKSP001 SITE PLAN

D101 DEMOLITION PLAN

A101 FLOOR PLANA111 REFLECTED CEILING PLANA131 FURNITURE AND FINISH PLANA210 INTERIOR ELEVATIONSA601 SCHEDULES AND DETAILS

Q001 SPECIFICATIONSQ002 SPECIFICATIONSQ003 SPECIFICATIONS

FP101 FIRE PROTECTION PLAN

P001 PLUMBING GENERAL NOTESP002 PLUMBING SPECIFICATIONSP101 PLUMBING SANITARY PLANP102 PLUMBING SUPPLY PLANP601 PLUMBING SCHEDULES AND DETAILS

M001 MECHANICAL GENERAL NOTESM002 MECHANICAL SPECIFICATIONSM003 MECHANICAL SPECIFICATIONSM101 MECHANICAL PLANM601 MECHANICAL SCHEDULES AND DETAILS

E001 ELECTRICAL SYMBOLS AND GENERAL NOTESE002 ELECTRICAL SPECIFICATIONSE101 ELECTRICAL POWER PLANE201 ELECTRICAL LIGHTING PLANE601 ELECTRICAL SCHEDULES

FA001 FIRE ALARM GENERAL NOTESFA101 FIRE ALARM PLAN

GENERAL NOTES SITE KEY PLAN PROJECT DIRECTORYQUEST DIAGNOSTICS

E 9TH ST

NORTH

TOTAL FIXTURESPROVIDED 2 UNISEX 3 0 1

TOTAL FIXTURESREQUIRED 1 1 <15 NR 1

7 OCC 7/25 7/40 7/100 1

B - BUSINESS 1:25 (FIRST 50);1:50 AFTER

1:40 (FIRST 80);1:80 AFTER 1:100 1 REQUIRED

USE GROUP WATERCLOSETS LAVATORIES DRINKING

FOUNTAINS SERVICE SINK

PLUMBING FIXTURE REQUIREMENTS

PROJECT CODE DATA

LIFE SAFETY PLAN3/32" = 1'-0"

SYMBOL LEGEND

SCOPE OF WORK

TENANT FIT OUT IN EXISTING SPACE. NEW PATIENT SERVICE CENTER FOR QUEST DIAGNOSTICS WILL BE CONSTRUCTED IN EXISTING GROUND FLOOR SUITE.

THE PATIENT SERVICE CENTER IS AN OFFICE WHERE PATIENTS MAY COME TO HAVE BLOOD DRAWN OR TO LEAVE URINE SAMPLES. THERE IS NO LABORATORY WORK PERFORMED ON THE PREMISES; ALL SAMPLES ARE SAFELY STORED AND SENT TO QUEST DIAGNOSTICS LABORATORIES FOR PROCESSING. THE QUEST DIAGNOSTICS PATIENT SERVICE CENTER IS NOT A HEALTHCARE FACILITY SUCH AS A HOSPITAL OR OUTPATIENT CLINIC. QUEST DIAGNOSTICS CONTINUES TO EXPAND CONSUMER ACCESS TOHEALTHCARE SERVICES WHERE PEOPLE ALSO SHOP, MAKING IT EASIER FOR THEM TO GET THE QUALITY DIAGNOSTIC INSIGHTS THEY NEED IN CONVENIENT LOCATIONS. WHETHER USED FOR AN OCCASIONAL PHYSICAL EXAM, OR FOR DIAGNOSTIC PURPOSES, OR FOR MONITORING OF A PATIENT'S CONDITION DURING A SERIOUS ILLNESS, THE OFFICE'S LOCATION NEAR PEOPLE'S HOMES AND OFFICES WILL PROVE A GREAT CONVENIENCE AND WILL IMPROVE THE ACCESS OF THE COMMUNITY TO QUALITY HEALTHCARE SERVICES.

# DATE DESCRIPTION

CH

ERR

Y ST

CLE

RM

ON

T ST

CL

CL

CL

CL

SIDEAPPROACHESFRONT APPROACH

32"MIN.

14" IF DOOR HASBOTH A CLOSERAND A LATCH

50" M

IN.

PUSHSIDE

PULLSIDE

20"

62"

32"MIN.

PULLSIDE

X

Y

2'-8"MIN.

PUSHSIDE 44

" MIN

.50

" MIN

. IF

DO

OR

HAS

CLO

SER

AN

D L

ATC

H

56" MIN.

PULLSIDE

PUSHSIDE

26" MIN.

44" M

IN.

NO

TE: 5

0" M

IN.

IF D

OO

R H

AS

CLO

SER 2'-2" MIN.

50" M

IN.

54" M

IN. I

F D

OO

R H

AS

CLO

SER NOTE:

DOORS SHALL NOTSWING INTO THECLEAR FLOORSPACE REQUIREDFOR ANY FIXTURE.INTERIOR HINGEDDOORS SHALLHAVE 5 LBFOPENING FORCE.

X = 38" MIN. IF Y =62";X = 44" MIN. IF Y = 56"

17" M

IN.

19" M

AX.

50"

MIN

EQ EQ

32"MIN

MIRROR

INSULATED PIPEPROTECTOROR PROVIDEPROTECTIONAS ILLUSTRATEDPER ANSI §4.24.3

34" A

.F.F

. MAX

.

6"MAX.

8"MIN.

9" MIN

. 27" M

IN.

40" A

.F.F

. MAX

TO B

OTT

OM

OF

THE

REFL

ECTIV

E SU

RFAC

E

NOTE:1. CABINETS ARE NOT

PERMITTED UNDERTHE LAVATORYWITHIN THEREQUIRED CLEARFLOOR AREA.FAUCET CONTROLSSHALL COMPLYWITH ANSI § 606

2. REFER TO KNEE ANDTOE CLEARANCEREQUIREMENTS FORADDITIONALDIMENSIONALREQUIREMENTS

50"

32"

PARALLELAPPROACH

FORW

ARD

APPR

OAC

H

64"MINIMUM

38"

MIN

IMUM

64"

MIN

IMUM

13"MINIMUM

38"MINIMUM

13"MINIMUM

26"

MIN

IMUM

NOTE: AN UNOBSTRUCTED TURNING SPACE SHALL BE IN ALL ACCESSIBLE SPACES. THECLEAR FLOOR SPACE AT FIXTURES AND CONTROLS, THE ACCESSIBLE ROUTE AND TURNINGSPACE MAY OVERLAP

27" M

IN

34" M

AX

9" MIN

6"MAX

11"MIN

8"MIN

1'-5" MIN2'-1" MAX

NOTE: CLEAR FLOOR WIDTH AT KNEE AND TOE CLEARANCE SPACE SHALL BE 2'-6"MINIMUM. ADDITIONAL SPACE BEYOND KNEE AND TOE CLEARANCES SHALL BEPERMITTED BENEATH ELEMENTS.

62"MINIMUM

SIZE OF CLEARFLOOR SPACE

CIRCULARTURNING SPACE 'T'-SHAPED TURNING SPACEKNEE AND TOE CLEARANCES

OBSTRUCTEDHIGH FORWARD

REACH

UNOBSTRUCTEDFORWARD

REACHUNOBSTRUCTED SIDE REACH

OBSTRUCTEDHIGH SIDE REACH

18"

MIN

46" M

AX

>20" MAX*20" TO 25" MAX

46" M

AX*4

2" M

AX34

" MAX

2'-4

" MIN

NOTE: 2'-6" MIN WIDECLEAR FLOOR SPACEMUST BE PROVIDEDUNDEROBSTRUCTION.MAXIMUM REACHDEPTH IS 2'-1"

18"

MIN

46" M

AX

10"MAX

<20" MAX*20" TO 25"

44" M

AX*4

2" M

AX34

" MAX

33" M

IN36

" MAX

42"MIN

12"MAX

7" MIN9" MAX

1 1/

2"

15"

MIN

DISPENSER LOCATION. DISPENSERS SHALL NOT BE OF A TYPE THAT CONTROL DELIVERY OR PROHIBIT A CONTINUOUS PAPER FLOW

54" MIN

40" MIN

39" M

IN41

" MAX

18" H VERTICAL GRAB BAR NOTE:

1. GRAB BARS SHALLHAVE A DIAMETERBETWEEN 1 1/4" AND2" TO PROVIDEGRASPABILITY.

2. GRAB BARS SHALLBE 1 1/2" FROM THEWALL SURFACE.

SIDE WALL GRAB BARS

2'-9

" MIN

3'-0

" MAX

12"MIN

24"MIN

18"HOLD

HAND OPERATEDFLUSH CONTROLSSHALL BE LOCATEDON THE OPEN SIDEOF THE WATERCLOSET

REAR WALL GRAB BARSNO TOILET PARTITIONS

58" M

IN

62" MIN

18"HOLD

SIDE OPP.APPROACH

WALL FINISHNOTE:1. WATER CLOSET SHALL BE ON

AN ACCESSIBLE ROUTE. WALLMOUNTED WATER CLOSET TOBE MIN. OF 58" FROM FINISHWALL SURFACE, 61" FOR AFLOOR MOUNTED W.C. ASSHOWN. GRAB BARS ANDOTHER TOILET ROOMACCESSORIES SHALL BE THESAME AS STANDARDACCESSIBLE WATER CLOSET.

2. NOTHING SHALL BE PERMITTEDIN THE CLEAR FLOOR AREAEXCEPT FOR GRAB BARS ANDOTHER TOILET ROOMACCESSORIES, ACCESSIBLEROUTES, TURNING RADII, ANDOTHER FIXTURES' CLEAR FLOORAREAS.

18 MIN

46" M

AX U

NO

BSTR

UCTE

D R

EAC

H35

" MAX

OBS

TRUC

TED

REA

CH

DIMENSIONS ARE TOTHE TOP OF THEOPERABLE PART, NOTTHE ℄ OF THE DEVICE

DIMENSIONS IS TO THEBOTTOM OF THELOWER RECEPTACLE,NOT THE ℄ OF THEOUTLET

NOTE: OBSTRUCTED REACH LOCATIONSMUST COMPLY WITH THE DEPTHDIMENSIONS SHOWN ABOVE. REFER TOANSI § 308 AND 309 FOR ADDITIONALDETAILS AND REQUIREMENTS

3'-5

" MIN

FO

R VI

SUAL

CHA

RAC

TERS

4'-1

" MIN

FO

R TA

CTIL

E SI

GN

S

4'-1

1" M

AX F

OR

TAC

TILE

CHA

RAC

TERS

5/8"

MIN

4'-1

" MIN

4'11

" MAX

NOTE: VISUAL CHARACTERS MUST BEHIGH-CONTRAST. REFER TO CHAPTER 7IN ANSI A117.1-2009 FOR ADDITIONALDETAILS AND REQUIREMENTS

AREA OFREFUGE

CL

CENTERED ON TACTILECHARACTERS

18" MIN.

18" MIN

.

>27"

4"MAX

≥80"

NOTE: HANDRAILS MAYPROTRUDE 4-1/2" AND DOORCLOSERS AND DOOR STOPSSHALL BE PERMITTED TO BE 6'-6"A.F.F.

TURNING SPACE• ALL ROOMS SHALL BE SERVICED BY AN ACCESSIBLE ROUTE, AND SHALL

PROVIDE A TURNING RADIUS 60" MINIMUM DIAMETER CIRCULAR SPACE OR T-SHAPED SPACE WITH 60" MINIMUM SQUARE, WITH ARMS AND BASE 36"MINIMUM IN WIDTH.

ACCESSIBLE ROUTES• ACCESSIBLE ROUTES SHALL BE 3'-0" WIDE MINIMUM.

OPERABLE PARTS• THE ENTIRE OPERABLE PARTS SHALL FALL WITHIN THE REQUIRED REACH

RANGES• OPERABLE PARTS SHALL BE OPERABLE WITH ONE HAND AND SHALL NOT

REQUIRE TIGHT GRASPING, PINCHING, OR TWISTING OF THE WRISTS. THEFORCE REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5.0 POUNDSMAXIMUM.

SIGNAGE• REFER TO 2010 ADA AND ANSI §703 FOR COMPLETE SIGNAGE

REQUIREMENTS• VISUAL SIGNAGE MUST BE 3'-5" MIN A.F.F. AND LETTERING MUST BE 5/8" MIN

AND HIGH-CONTRAST• CHARACTERS IN TACTILE AND BRAILLE SIGNS MUST BE BETWEEN 4'-1" AND

4'-11" A.F.F.

DOORS AND DOORWAYS • PRIMARY ENTRANCES SHALL BE ACCESSIBLE AND LOCATED ON AN

ACCESSIBLE ROUTE.• A CLEAR OPENING OF 32" SHALL BE PROVIDED

TOILET FACILITIES• AT LEAST ONE LAVATORY, ONE WATER CLOSET SHALL MEET ALL ANSI AND

2010 ADA REQUIREMENTS.• DOORS SHALL NOT SWING INTO THE CLEAR FLOOR SPACE OR CLEARANCE

FOR ANY FIXTURE. EXCEPTION: WHERE A 30" X 48" CLEAR FLOOR SPACE ISPROVIDED WITHIN THE ROOM BEYOND THE SWING OF THE DOOR.

• CLEAR FLOOR SPACES, CLEARANCES AT FIXTURES AND TURNING SPACESARE PERMITTED TO OVERLAP.

• REINFORCEMENT SHALL BE PROVIDED FOR INSTALLATION OF GRAB BARSAT WATER CLOSETS AS REQUIRED.

LAVATORY• PROVIDE A 30" X 48" CLEAR FLOOR SPACE POSITIONED FOR FORWARD

APPROACH.• THE FRONT OF LAVATORIES AND SINKS SHALL BE 33-1/2" MAXIMUM A.F.F.

MEASURED TO THE HIGHER OF THE RIM OR COUNTER SURFACE.• THE DEPTH OF THE SINK BOWL SHALL BE 6 1/2" MAXIMUM. MULTIPLE-

COMPARTMENT SINKS SHALL HAVE AT LEAST ONE COMPARTMENTCOMPLYING WITH THIS REQUIREMENT.

• EXPOSED PIPES AND SURFACES UNDER LAVATORIES AND SINKS SHALL BEINSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST CONTACT.THERE SHALL BE NO SHARP OR ABRASIVE SURFACES UNDER LAVATORIESAND SINKS.

MIRRORS• MIRRORS ABOVE LAVATORIES SHALL HAVE THE BOTTOM EDGE OF THE

REFLECTING SURFACE 40" MAXIMUM A.F.F.

WATER CLOSET• THE REQUIRED CLEARANCE AROUND THE WATER CLOSET SHALL BE

PERMITTED TO OVERLAP THE WATER CLOSET, ASSOCIATED GRAB BARS,PAPER DISPENSERS, COAT HOOKS, SHELVES, ACCESSIBLE ROUTES, CLEARFLOOR SPACE REQUIRED AT OTHER FIXTURES AND THE WHEELCHAIRTURNING SPACE. NO OTHER FIXTURES OR OBSTRUCTIONS SHALL BELOCATED WITHIN THE REQUIRED WATER CLOSET CLEARANCE.

• THE TOP OF THE WATER CLOSET SEAT SHALL BE 15" MINIMUM AND 19"MAXIMUM A.F.F.

• A WALL CAPABLE OF SUPPORTING GRAB BARS IN WEIGHT AND DIMENSIONMUST BE PROVIDED AT THE SIDE OF THE WATER CLOSET, 18" FROM THE ℄OF THE WATER CLOSET TO FINISHED WALL SURFACE. SWING-DOWN GRABBARS ARE NOT PERMITTED.

SINK• PROVIDE A 30" X 48" CLEAR FLOOR AREA POSITIONED FOR FORWARD

APPROACH. THE CLEAR FLOOR SPACE SHALL BE CENTERED ON THE SINKBOWL.

• THE REQUIREMENT FOR KNEE AND TOE CLEARANCE SHALL NOT APPLY TOMORE THAN ONE BOWL OF A MULTI-BOWL SINK.

• THE FRONT OF LAVATORIES AND SINKS SHALL BE 33-1/2" MAXIMUM A.F.F.MEASURED TO THE HIGHER OF THE RIM OR COUNTER SURFACE.

• THE DEPTH OF THE SINK BOWL SHALL BE 6 1/2" MAXIMUM.• ALL EXPOSED PIPES AND SURFACES UNDER LAVATORIES AND SINKS SHALL

BE INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINSTCONTACT AND THERE SHALL BE NO SHARP OR ABRASIVE SURFACES UNDERLAVATORIES AND SINKS.

INFANT DRAW STATION• REFER TO 2010 ADA REQUIREMENT 902 WORK SURFACES. WHEN IN THE

OPEN POSITION, THE TABLE SURFACE SHOULD BE A MAX OF 30" A.F.F. SAMECLEAR FOR SPACE FOR FORWARD APPROACH COMPLYING WITH 305, WITHEXCEPTION OF KNEE CLEARANCE OF 24" MIN.

SPOUT HEIGHTS KNEE CLEARANCECLEAR FLOOR SPACE FOR FORWARD APPROACH, CENTERED ON ACCESSIBLE DRINKING FOUNTAIN

STAN

DIN

G42

" MAX

ACC

ESSI

BLE

36" M

AX

MAX27

" MAX4"

MAX30"

MAX48

"

SHEET

SHEET TITLE

ISSUE DATE

DRAWN BY

CHECKED BYAPPROVED BY

PROJECT NO.

REVISION

PROFESSIONAL OF RECORD:NOTIC

E: THIS

ARCHIT

ECTURAL A

ND E

NGIN

EERIN

G D

RAW

ING IS G

IVEN IN C

ONFID

ENCE A

ND S

HALL B

E U

SED O

NLY P

URSUANT T

O T

HE A

GREEMENT W

ITH T

HE A

RCHIT

ECT. NO O

THER U

SE, DIS

SEMIN

ATIO

N, OR D

UPLIC

ATIO

N M

AY B

E M

ADE W

ITHOUT P

RIO

R W

RIT

TEN

CONSENT O

F T

HE A

RCHIT

ECT. ALL C

OMMON L

AW

RIG

HTS O

F C

OPYRIG

HT A

ND O

THERW

ISE A

RE H

EREBY S

PECIF

ICALLY R

ESERVED.

CLIENT

2221 Schrock RoadColumbus, Ohio 43229-1547p 614.898.7100f 614.898.7570www.msconsultants.com

PROJECT

10/4

/202

1 4:

48:3

7 PM

ACCESSIBILITY STANDARDS

G002

JPJ

CHARLES M. BUSCH - RA No. ARC.00403518EXP. DATE: 10/31/2021

10/04/2021

CLR/CMB

10/04/2021

62-40487-06

HCA HEALTH ONE, LLC4500 E 9TH AVESTE 160DENVER, CO 80220

QUESTDIAGNOSTICS

ACCESSIBLE CLEARANCES

ACCESSIBILITY NOTES

ACCESSIBLE REACH RANGES

ACCESSIBLE DOOR MANEUVERING CLEARANCES ACCESSIBLE OUTLETS, SWITCHES,& OPERABLE CONTROL ACCESSIBLE SIGNAGE

ACCESSIBLE WATER CLOSET - PLAN ACCESSIBLE WATER CLOSET - ELEVATION PROTRUDING OBJECTS

ACCESSIBLE DRINKING FOUNTAIN ACCESSIBLE LAVATORY

SCALE: 3/8" = 1' SCALE: 3/8" = 1'

SCALE: 3/8" = 1' SCALE: 3/8" = 1'

SCALE: 3/8" = 1' SCALE: 3/8" = 1'

SCALE: 3/8" = 1'

SCALE: 3/8" = 1'

SCALE: 3/8" = 1' SCALE: 3/8" = 1'

# DATE DESCRIPTION

SHEET

SHEET TITLE

ISSUE DATE

DRAWN BY

CHECKED BYAPPROVED BY

PROJECT NO.

REVISION

PROFESSIONAL OF RECORD:NOTIC

E: THIS

ARCHIT

ECTURAL A

ND E

NGIN

EERIN

G D

RAW

ING IS G

IVEN IN C

ONFID

ENCE A

ND S

HALL B

E U

SED O

NLY P

URSUANT T

O T

HE A

GREEMENT W

ITH T

HE A

RCHIT

ECT. NO O

THER U

SE, DIS

SEMIN

ATIO

N, OR D

UPLIC

ATIO

N M

AY B

E M

ADE W

ITHOUT P

RIO

R W

RIT

TEN

CONSENT O

F T

HE A

RCHIT

ECT. ALL C

OMMON L

AW

RIG

HTS O

F C

OPYRIG

HT A

ND O

THERW

ISE A

RE H

EREBY S

PECIF

ICALLY R

ESERVED.

CLIENT

2221 Schrock RoadColumbus, Ohio 43229-1547p 614.898.7100f 614.898.7570www.msconsultants.com

PROJECT

10/5

/202

1 3:

51:0

2 PM

COMCHECK

G003

JMM

JASON E. CHRISTOFF - PE No.PE.0056074EXP DATE: 10/31/2021

10/04/2021

MRM

10/04/2021

62-40487-06

HCA HEALTH ONE, LLC4500 E 9TH AVESTE 160DENVER, CO 80220

QUESTDIAGNOSTICS

# DATE DESCRIPTION

SHEET

SHEET TITLE

ISSUE DATE

DRAWN BY

CHECKED BYAPPROVED BY

PROJECT NO.

REVISION

FOR REFERENCE

ONLY

NOTIC

E: THIS

ARCHIT

ECTURAL A

ND E

NGIN

EERIN

G D

RAW

ING IS G

IVEN IN C

ONFID

ENCE A

ND S

HALL B

E U

SED O

NLY P

URSUANT T

O T

HE A

GREEMENT W

ITH T

HE A

RCHIT

ECT. NO O

THER U

SE, DIS

SEMIN

ATIO

N, OR D

UPLIC

ATIO

N M

AY B

E M

ADE W

ITHOUT P

RIO

R W

RIT

TEN

CONSENT O

F T

HE A

RCHIT

ECT. ALL C

OMMON L

AW

RIG

HTS O

F C

OPYRIG

HT A

ND O

THERW

ISE A

RE H

EREBY S

PECIF

ICALLY R

ESERVED.

CLIENT

2221 Schrock RoadColumbus, Ohio 43229-1547p 614.898.7100f 614.898.7570www.msconsultants.com

PROJECT

10/6

/202

1 12

:00:

51 P

M

SITE PLAN

SP001

JPJ

CLR/CMB

10/04/2021

62-40487-06

HCA HEALTH ONE, LLC4500 E 9TH AVESTE 160DENVER, CO 80220

QUESTDIAGNOSTICS

# DATE DESCRIPTION

QUEST DIAGNOSTICS

CLE

RM

ON

T ST

E 9TH AVE

CH

ERR

Y ST

SITE PLANN.T.S.

PROPERTY LINE

NORTH

X

1. OBTAIN DEMOLITION PERMITS AND INCLUDE ALL COSTS OF SAME INCONTRACT PRICE, IF REQUIRED.

2. PROVIDE ALL LABOR AND MATERIALS/EQUIPMENT AS REQUIRED TO COMPLETEDEMOLITION AND REMOVAL OF ALL ITEMS AS INDICATED.

3. PROVIDE STRICT CONTROL OF JOB CLEANING AND PREVENT DUST ANDDEBRIS FROM REMAINING FROM DEMOLITION/ CONSTRUCTION AREA. KEEPAREA CLEAN.

4. IF ANY QUESTIONS ARISE AS TO THE REMOVAL OF ANY MATERIAL, CLARIFYTHE POINT IN QUESTION WITH THE ARCHITECT BEFORE PROCEEDING.

5. AT COMPLETION OF DEMOLITION WORK, THE CONSTRUCTION AREA(S) SHALLBE LEFT IN "BROOM CLEAN" CONDITION. ALL DEBRIS AND MISCELLANEOUSMATERIAL SHALL BE REMOVED. ALL DEBRIS REMOVAL SHALL BE PERFORMEDIN ACCORDANCE WITH BUILDING MANAGEMENT REQUIREMENTS ANDPROCEDURES.

6. THE ELECTRICAL CONTRACTOR SHALL FURNISH A SYSTEM OF TEMPORARYLIGHT & POWER IN THE SPACE DURING CONSTRUCTION.

7. ALL DEMOLISHED ELECTRICAL DEVICES, PLUMBING LINES, VENTS, DRAINS,APPLIANCES, TO BE REMOVED AND TERMINATED AT THEIR SOURCE U.N.O.

8. IN PARTITIONS TO BE REMOVED, REMOVE AND CAP ALL OUTLETS, SWITCHES,WIRES THERMOSTATS, ETC. TO THEIR SOURCE AS REQUIRED.

9. CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING AND/OR REPAIRINGANY DAMAGE CAUSED BY THE CONTRACTOR OR CONTRACTOR'SSUBCONTRACTORS TO EXISTING CONSTRUCTION. REFINISH TO MATCHEXISTING ADJACENT FINISH, OR AS NOTED HEREIN.

10. FIRE PROTECTION RENOVATIONS, BY OTHERS. PROTECT EXISTING DURINGDEMOLITION WORK.

11. ALL EXISTING FLOOR MOUNTED OUTLETS AND ASSOCIATED WIRING SHALL BEREMOVED AND CAPPED OFF AT THE NEAREST JUNCTION BOX. FILL AND LEVELFLOOR TO ACCEPT NEW SCHEDULED FLOOR COVERING.

12. RE-USE OR RELOCATE ALL ABOVE CEILING DUCTWORK AS CONTAINED HEREININCLUDING BUT NOT LIMITED TO, DIFFUSERS, GRILLES, OR OTHER EQUIPMENT,AS REQUIRED FOR PROPER DISTRIBUTION WITH NEW LAYOUT. CONFIRM WITHNEW WORK MECHANICAL DRAWINGS.

13. REMOVAL OF ANY EQUIPMENT, CABLING SWITCHES, AND CONDUITPERTAINING TO DATA/ COMMUNICATIONS AND TELEPHONE SHALL BE VERIFIEDWITH TELEPHONE COMPANIES SERVICE OWNER OR TENANTDATA/COMMUNICATIONS REPRESENTATIVE AS REQUIRED TO PREVENT NEWCONSTRUCTION DELAYS.

14. REMOVE ALL EXISTING IRREGULAR MATERIALS WHICH CAUSE RISES ORDEPRESSIONS IN FLOORING SURFACE, SUCH AS FASTENERS, OUTLET CORES,COVER PLATES, RESILIENT FLOOR COVERINGS, CARPET, CARPET PAD, FLASHPATCH, CONCRETE FILL, PLYWOOD, ETC.

15. DEMOLITION IS NOT NECESSARILY LIMITED TO WHAT IS SHOWN ON DRAWINGS.THE INTENT IS TO INDICATE THE GENERAL SCOPE OF DEMOLITION REQUIREDTO COMPLETE THE WORK IN ACCORDANCE WITH THE CONTRACT DRAWINGS.GENERAL CONTRACTOR SHALL VISIT SITE & FAMILIARIZE THEMSELVES WITHEXISTING CONDITIONS & NOTE ANY DISCREPANCIES IN WRITING TO PROJECTMANAGER & ARCHITECT.

16. EXIT PATHS MUST REMAIN ACCESSIBLE AT ALL TIMES DURING DEMOLITION.17. REMOVE EXISTING SIGNAGE/GRAPHICS AND STORE FOR RE-USE, WHERE

APPLICABLE.18. ALL CEILING AND LIGHTING TO BE REMOVED IN AREAS SHOWN IN CONTRACT.19. ALL FLOOR FINISHES AND WALL BASE TO BE REMOVED IN AREAS SHOWN IN

CONTRACT.20. COORDINATE AREAS OF SLAB TO BE REMOVED WITH PLUMBING PLANS.

4' -

10 1

/2"

3' -

11 3

/4"

3' -

3"

+/- 2

1/2

"

+/- 7

' - 0

"

+/- 4

' - 1

1 3/

4"2'

- 9

1/4"

+/- 2' - 10 1/2"

D1

ADJACENT TENANT (BUSINESS)

D2

D2

D2

D2 D2

D2

D3

D3

D3D3D3

D3

D3

D3

D4

D4 D4

D4

D4

D4

D4

D4

D4

D5

D5

D5

D5D5

D5D5

D5

D5

D5

D5

D5

D7

D7

D7

D7

D7

D7

D7D7

D7

D10

D10

D11

D11

D10

D11

D11 D11

D11

D11

D10

D11

D11

D12

D12

D12

D9 D6

D6

D6

D6

SHEET

SHEET TITLE

ISSUE DATE

DRAWN BY

CHECKED BYAPPROVED BY

PROJECT NO.

REVISION

PROFESSIONAL OF RECORD:NOTIC

E: THIS

ARCHIT

ECTURAL A

ND E

NGIN

EERIN

G D

RAW

ING IS G

IVEN IN C

ONFID

ENCE A

ND S

HALL B

E U

SED O

NLY P

URSUANT T

O T

HE A

GREEMENT W

ITH T

HE A

RCHIT

ECT. NO O

THER U

SE, DIS

SEMIN

ATIO

N, OR D

UPLIC

ATIO

N M

AY B

E M

ADE W

ITHOUT P

RIO

R W

RIT

TEN

CONSENT O

F T

HE A

RCHIT

ECT. ALL C

OMMON L

AW

RIG

HTS O

F C

OPYRIG

HT A

ND O

THERW

ISE A

RE H

EREBY S

PECIF

ICALLY R

ESERVED.

CLIENT

2221 Schrock RoadColumbus, Ohio 43229-1547p 614.898.7100f 614.898.7570www.msconsultants.com

PROJECT

10/4

/202

1 4:

48:3

3 PM

DEMOLITION PLAN

D101

JPJ

CHARLES M. BUSCH - RA No. ARC.00403518EXP. DATE: 10/31/2021

10/04/2021

CLR/CMB

10/04/2021

62-40487-06

HCA HEALTH ONE, LLC4500 E 9TH AVESTE 160DENVER, CO 80220

QUESTDIAGNOSTICS

1/4" = 1'-0"1 DEMOLITION PLAN

DEMOLITION KEYNOTESD1 EXISTING DOOR TO REMAIN. PROTECT FROM DAMAGE DURING CONSTRUCTION.

PREP TO RECEIVE NEW FINISHES AND HARDWARE AS REQUIREDD2 EXISTING TENANT DEMISING WALL - REVIEW DRYWALL AND REPAIR/REPLACE

AS REQUIRED TO RECEIVE NEW DRYWALL LEVEL 4 FINISH FOR NEW FINISHES.GC TO MAINTAIN ANY EXISTING DEMISING WALL RATINGS.

D3 REMOVE EXISTING DOOR, FRAME AND HARDWARE AND DISPOSE OF ASREQUIRED.

D4 REMOVE EXISTING FLOORING AND PREP SLAB AS REQUIRED TO RECEIVE NEWFINISHES UNLESS NOTED OTHERWISE.

D5 EXISTING STUD WALL AND GYP TO BE REMOVED, PATCH FLOOR AS REQUIREDAND PREP FOR NEW CONSTRUCTION. CAP ALL PLUMBING AND ELECTRICAL ASREQUIRED.

D6 SAW-CUT EXISTING SLAB AS REQUIRED IN ORDER TO CONNECT NEW PLUMBINGFIXTURES TO EXISTING SANITARY LINES. SEE PLUMBING PLAN FOR ADDITIONALINFORMATION. NOTIFY ARCHITECT IMMEDIATELY IF CONFLICTS WITH DESIGNINTENT ARE DISCOVERED

D7 REMOVE EXISTING EQUIPMENT, FIXTURES AND FURNITURE AS REQUIRED FORNEW CONSTRUCTION - CONFIRM WITH OWNER'S REP. ON DISPOSAL. CAP ALLPLUMBING AND ELECTRICAL AS REQUIRED.

D9 APPROXIMATE LOCATION OF EXISTING SANITARY LINE AT CROSSHATCHEDAREA - SEE PLUMBING DRAWINGS

D10 REMOVE EXISTING PERIMETER WALL FINISHES - PREPARE DRYWALL WITHLEVEL 4 FINISH FOR NEW FINISHES.

D11 REMOVE THE EXISTING CEILING, LIGHTING AND ANY CEILING DEVICESTHROUGHOUT THE ENTIRE SPACE AND DISPOSE OF AS REQUIRED. PREPAREFOR NEW ACOUSTIC TILE CEILING. SEE MECHANICAL/ELECTRICAL PLANS FORNEW LOCATIONS.

D12 REMOVE EXISTING BLINDS FROM WINDOWS AND SET ASIDE FOR POSSIBLEREUSE AS DETERMINED BY OWNER'S REP.

PLAN NORTH

GENERAL NOTES

# DATE DESCRIPTION

EXIS

T. F

.F. T

O N

EW S

TUD

+/- 8

' - 0

5/8

" FV

3 5/

8"8'

- 1

1/4"

3 5/

8"8'

- 1

1/4"

3 5/

8"

EXIS

T. F

.F. T

O N

EW S

TUD

+/- 7

' - 2

" FV

3 5/

8"

HO

L D

4' -

1 1/

4"3

5/8"

EXIS

T. F

.F. T

O N

EW S

TUD

+/- 6

' - 7

" FV

*12'

- 3

1/8"

EXIST. F.F. TO NEW STUD+/- 4' - 4 7/8" FV

3 5/8"4' - 1 1/4"

3 5/8"

EXIST. F.F. TO NEW STUD+/- 10' - 0 7/8" FV* 11' - 3 1/2"

EXIST. F.F. TO NEW STUD+/- 7' - 10 1/2" FV 3 5/8" 7' - 11 1/8" 3 5/8"

HOLD4' - 1 1/4" 3 5/8" 10' - 0 7/8" 3 5/8"

* 7' - 10 1/2"* 9' - 2 5/8"* 10' - 5 1/8"

3A101

TYP

@ B

ARN

DO

OR

3' -

5 1/

4"+/

- 8 3

/8"

TYP

@ P

ER3'

- 1

1/4"

* 4' - 0"

5' -

0"1'

- 1"

1' -

4"

7' -

0"

6' - 6"

EXIS

T. F

.F. T

O N

EW S

TUD

+/- 5

' - 2

5/8

" FV

3 5/

8"

100A

103

101

107 105

100B

102

106

HALL101

SPECIMENCONSOLIDATION

104

SPECIALSERVICES

01

PATIENTENCOUNTER

03

PATIENTENCOUNTER

02

EMPLOYEEBREAKROOM106

JANITOR/STORAGE

102

SUPPLY103

WAITINGROOM100

UNISEXTOILET

107UNISEXTOILET

105

01

01

02

02

02

0202

02

02

02

02

02

2' -

0" 2' - 6" 2' - 0"

2' -

0" 2' - 6" 2' - 0"

B

B

B

09

09

10

10

10

A2108

A210 7

A2106B

A210

6A

A210 3C

3B

3A

3D

A210 5A

5C

A210

2B

2A

2C

A210

1A

A210

1B

8A601

07

A210 4

5B

2' -

0"

2' - 6" 2' - 0"

3' - 10 1/8"TYP @ BARN DOOR

3' - 5 1/4"

5D

1. ALL MILLWORK AND CABINETRY TO BE FURNISHED BY OWNER2. REMOVE EXISTING FINISHES AND PATCH EXISTING WALL AS

REQUIRED. PREP TO RECEIVE NEW FINISHES AS SHOWN ONTHE FINISH SCHEDULE. PREPARE ALL SURFACES TO LEVEL 4FINISH TO AS REQUIRED TO RECEIVE NEW FINISHES.

3. ALL DIMENSIONS ARE TO FACE OF STUD AND OPENINGCENTERLINES U.N.O.

4. THE GC IS RESPONSIBLE FOR ALL COORDINATION BETWEENALL SUBCONTRACTORS BASED ON THE ENTIRE SET OFCONSTRUCTION DOCUMENTS. IN CASE OF INCONSISTENCIESOR DISCREPANCIES BETWEEN DRAWINGS, THE MOSTSTRINGENT NOTE OR CONDITION SHALL APPLY, AND THE GCSHALL NOTIFY THE ARCHITECT IN WRITING IMMEDIATELY

5. IT IS THE RESPONSIBILITY OF THE GC TO FIELD VERIFYEXISTING SITE CONDITIONS AND DIMENSIONS PRIOR TOCOMMENCING WORK, AND TO IMMEDIATELY NOTIFYARCHITECT IN WRITING IF DISCREPANCIES ARE DISCOVEREDTHAT WOULD IMPACT THE DESIGN INTENT

6. ALL CABINETRY TO BE FABRICATED OFF-SITE, AND SHALLCOMPLY WITH ALL APPLICABLE ACCESSIBILITYREQUIREMENTS. GC TO INSTALL. CABINET FABRICATOR TOSUBMIT SHOP DRAWINGS FOR REVIEW AND APPROVAL. GCTO PROVIDE ALL REQUIRED FIRE-RETARDANT-TREATEDBLOCKING AND ANY ADDITIONAL CONSTRUCTION ASREQUIRED FOR FULL AND COMPLETE INSTALLATION

7. WRITTEN DIMENSIONS TAKE PRECEDENCE OVER ANYSCALED DIMENSIONS

8. COORDINATE MILLWORK DRAWINGS WITH C2CREPRESENTITIVE. NOTIFY ARCHITECT IMMEDIATELY INWRITING OF DISCREPANCIES WITH DESIGN INTENT INREGARDS TO THESE DRAWINGS, THE MILLWORK DRAWINGSAND/OR EXISTING FIELD CONDITIONS

9. COORDINATE WITH SHEET A601 FOR FINISH PLAN ANDSCHEDULE

10. ALL WOOD OR PLYWOOD BLOCKING/SHEATHING TO BE FIRE-RETARDANT-TREATED

11. DOORS INDICATED ON THE PLAN SHALL BE LOCATED AMINIMUM OF 4" FROM ADJACENT WALLS UNLESS NOTED ORDIMENSIONED OTHERWISE OR AS REQUIRED FORHARDWARE INSTALLATION.

12. ALL PARTITIONS ARE TYP "A" U.N.O.13. F.F. STANDS FOR FINISH FACE

EXIST F.F TO NEW STUD+/- 7' - 10 1/2" FV 3 5/8" 7' - 11 1/8" 3 5/8" 4' - 1 1/4" 3 5/8"

3 5/

8"3'

- 10

5/8

" 3 5/

8"2'

- 7

1/4"

6"6'

- 8"

3 5/

8"4'

- 1

1/4"

3 5/

8"

TYP

@ P

ER

+/- 3

' - 1

1/4

" FV

09

3 5/8" 3' - 3 1/2"3 5/8"

10 3/8"3 5/8"

0505

48

48

54

60

30

48

60

56

54

60

30

48

60

56

HOLD* 18"

HOLD* 18"

HOLD* 18"

HOLD* 18"

06

09

3 5/

8"8'

- 1

1/4"

3 5/

8"

* 1' -

3"

*1' -

3"

48

48

C

C

C

C C

C

UNISEXTOILET

107

UNISEXTOILET

105

JANITOR/STORAGE

102

HALL101

PROVIDE GENDER NEUTRAL SIGNAGE. REFER TO G002 FOR ADDITIONAL INFORMATION

PROVIDE GENDER NEUTRAL SIGNAGE. REFER TO G002 FOR ADDITIONAL INFORMATION

C

HOLD* 15"

METAL STUD

CONTINUOUS C-CHANNEL

5/8" GYP BOARD4" WB

EXISTING TENANT DEMISING WALL

PLANSEE FLOOR

NO. 10 SCREW THROUGH EACH FLANGE

HILTI X-U UNIVERSAL KNURLED-SHANK PAF'S @ 24" OC MAX (EMBEDMENT = 1 1/4")

METAL STUD - SEE PLAN FOR WIDTH

CONTINUOUS C-CHANNEL

5/8" GYP BOARD

4" WB

PLANSEE FLOOR

NO. 10 SCREW THROUGH EACH FLANGE

HILTI X-U UNIVERSAL KNURLED-SHANK PAF'S @ 24" OC MAX (EMBEDMENT = 1 1/4")

METAL STUD

CONTINUOUS C-CHANNEL

5/8" CEMENT BOARD

TILE AND GROUT

CONTINUOUS BATT INSULATION

CAULKING

6'-4"

T.O. TILE

PLANSEE FLOOR

5/8" GYP BOARD

HILTI X-U UNIVERSAL KNURLED-SHANK PAF'S @ 24" OC MAX (EMBEDMENT = 1 1/4")

4" WB

NO. 10 SCREW THROUGH EACH FLANGE

+ 0' - 0" A.F.F.

FINISH FLOOR

+ 2' - 10" A.F.F.

T.O. SINK

9"

8"

2' -

9 1/

2"

27" M

IN.

1' -

6"

SINK APRON

SANITARY PANEL

HATCHED AREAMUST BE FREE OFOBSTRUCTIONS

BASE CABINET BEYOND

EXTEND STUD AND GYP BOARD TO BOTTOM OF STRUCTURE. DO NOT ATTACH TO DECK. (PER DETAIL 4/A111)

EXTEND STUD AND GYP BOARD TO 6" ABOVE CEILING. BRACE TO STRUCTURE ABOVE. (PER DETAIL 2/A111)

SHEET

SHEET TITLE

ISSUE DATE

DRAWN BY

CHECKED BYAPPROVED BY

PROJECT NO.

REVISION

PROFESSIONAL OF RECORD:NOTIC

E: THIS

ARCHIT

ECTURAL A

ND E

NGIN

EERIN

G D

RAW

ING IS G

IVEN IN C

ONFID

ENCE A

ND S

HALL B

E U

SED O

NLY P

URSUANT T

O T

HE A

GREEMENT W

ITH T

HE A

RCHIT

ECT. NO O

THER U

SE, DIS

SEMIN

ATIO

N, OR D

UPLIC

ATIO

N M

AY B

E M

ADE W

ITHOUT P

RIO

R W

RIT

TEN

CONSENT O

F T

HE A

RCHIT

ECT. ALL C

OMMON L

AW

RIG

HTS O

F C

OPYRIG

HT A

ND O

THERW

ISE A

RE H

EREBY S

PECIF

ICALLY R

ESERVED.

CLIENT

2221 Schrock RoadColumbus, Ohio 43229-1547p 614.898.7100f 614.898.7570www.msconsultants.com

PROJECT

10/4

/202

1 4:

48:1

8 PM

FLOOR PLAN

A101

JPJ

CHARLES M. BUSCH - RA No. ARC.00403518EXP. DATE: 10/31/2021

10/04/2021

CLR/CMB

10/04/2021

62-40487-06

HCA HEALTH ONE, LLC4500 E 9TH AVESTE 160DENVER, CO 80220

QUESTDIAGNOSTICS

1/4" = 1'-0"1 FLOOR PLAN

FLOOR PLAN KEYED NOTESKey Value Keynote Text

01 INSTALL CORNER GUARDS PER FINISH PLANS. SEE A131.02 EXISTING WALL TO REMAIN - INSTALL NEW 5/8" GYP. BOARD -

PREPARE ALL SURFACES AS REQUIRED TO RECEIVE NEW FINISHES05 DOOR SILL TRANSITION STRIP TO BE FLUSH AND LEVEL AT VINYL

TILE AND PORCELAIN TILE. PROVIDE MAX TRANSITION OF 1/2" WITHBEVEL TO COMPLY WITH ADA 303

06 RECESSED FIRE EXTINGUISHER CABINET.07 SCRIBE GYP BOARD FROM B.O. DOOR/WINDOW OPENING TO FINISH

FACE OF DOOR/WINDOW HEAD. PROVIDE FRT BLOCKING OR SHIMAS NECESSARY TO ASSURE GYP BOARD IS FLUSH WITH WINDOWPANE. CAULK AT ALL SEAMS.

09 INFILL STUD WALL AND GYP BD FINISHES TO ALIGN WITH THEADJACENT EXISTING GYP BD FOR A SMOOTH AND FLUSHTRANSITION.

10 INFILL EXISTING WINDOW WITH STUD, GYP BOARD ANDCONTINUOUS BATT INSULATION FROM B.O. WINDOW OPENING TO 6"ABOVE CEILING AS REQUIRED. ADD OPAQUE FILM TO INSIDE OFWINDOW.

GENERAL FLOOR PLAN NOTES

PLAN NORTH

3/8" = 1'-0"3

ENLARGED PLAN -TOILET ROOMS

1 1/2" = 1'-0"4 PARTITION TYPES

TYPE C TYPE B TYPE A

SEE A111 FOR ATTACHMENT DETAILS

NOTE: DIMENSIONS TO FINISH FACE MARKED WITH AN

NOTES:1. TYPICAL STUD FRAMING: 362PDS125-33 STUDS @ 16" OC TYP WHERE NOTED ON PLAN2. STUD BRIDGING REQUIRED @ 4'-0" OC IN STUD WALLS, EXCEPT WHERE EACH STUD FLANGE IS

CONTINUOUSLY FASTENED TO STRUCTURAL SHEATHING OR GYPSUM BOARD3. TYPICAL TRACK: 1 1/4" FLANGE, MATCH STUD GA AND DEPTH. ATTACH TRACK FLANGES TO EACH STUD

FLANGE W/ #10 SCREW

*

NOTE: DIMENSIONS TO FINISH FACE MARKED WITH AN *

3/4" = 1'-0"2 SINK SECTION

SYMBOL LEGEND

# DATE DESCRIPTION

7' - 11" AFF

HALL101

ACT

7' - 11" AFF

SPECIMENCONSOLIDATION

104

ACT

7' - 11" AFF

SPECIALSERVICES

01

ACT

7' - 11" AFF

PATIENTENCOUNTER

03

ACT

7' - 11" AFF

PATIENTENCOUNTER

02

ACT

7' - 11" AFF

EMPLOYEEBREAK ROOM

106

ACT

7' - 11" AFF

JANITOR/STORAGE

102

ACT

7' - 11" AFF

SUPPLY103

ACT

9' - 0" AFF

WAITING ROOM100

ACT

7' - 11" AFF

UNISEX TOILET107

GYP BD

7' - 11" AFF

UNISEX TOILET105

GYP BD

EQ EQ

EQEQ

EQEQ

EQ EQ

EQEQ

EQ EQ

EQEQ

EQ EQ

EQ 4' - 0" EQ EQ 4' - 0" EQ

EQEQEQ

EQ

START HERE

EQEQ

EQ EQ EQEQ

EQEQ

EQEQ

EQEQ

EQEQ

EQEQ

EQEQ

4A111

2A111

2' -

6" 4' - 0" 4' - 0"

2' -

6"

1' -

2"

1' -

2"

1' - 4"1' - 3"

6" DIA DOWNLIGHT

EXIT SIGN

2'X2' RECESSED LIGHTING

2'X4' RECESSED LIGHTING

EMERGENCY EVACUATION LIGHTING

GYP BOARD DROP CEILING

ACOUSTIC CEILING TILE AND GRID

SUPPLY DIFFUSER

RETURN GRILLE

EXHAUST GRILLE

EXTEND STUD AND GYP BOARD TO BOTTOM OF STRUCTURE. DO NOT ATTACH TO DECK. (PER DETAIL 4/A111)

LINEAR STRIP LIGHT

EXTEND STUD AND GYP BOARD TO 6" ABOVE CEILING. BRACE TO STRUCTURE ABOVE. (PER DETAIL 2/A111)

6"

GYP BOARD

METAL STUD - SEE FLOOR PLAN FOR DIM

24"X48" ACOUSTICAL CEILING TILES

ACOUSTICAL MAIN TEE

HANGER WIRE

WALL ANGLE TRACK FASTENED TO GYP BOARD

SEE RCPMETAL STUD @ 16" O.C.CEILING - SEE DETAIL 3/A111

SHEET METAL SCREW EACH SIDE

SHEET METAL SCREWS EACH END

ANGLE AT EACH BRACESHEET METAL SCREW3 5/8" METAL STUD BRACING @ 48" O.C.

11

ANGLE AT EACH END

CONTINUOUS METAL TRACK

6"

METAL STUD @ 16" O.C.

CEILING - SEE DETAIL 3/A111

SHEET METAL SCREW EACH SIDE

ANGLE AT EACH END

CONTINUOUS METAL TRACKSLIP TYPE HEAD JOINT - INSTALL PER MFR'S RECOMMENDATIONS

NOTE: DO NOT ATTACH GYP TO LONG LEG TRACK

SHEET

SHEET TITLE

ISSUE DATE

DRAWN BY

CHECKED BYAPPROVED BY

PROJECT NO.

REVISION

PROFESSIONAL OF RECORD:NOTIC

E: THIS

ARCHIT

ECTURAL A

ND E

NGIN

EERIN

G D

RAW

ING IS G

IVEN IN C

ONFID

ENCE A

ND S

HALL B

E U

SED O

NLY P

URSUANT T

O T

HE A

GREEMENT W

ITH T

HE A

RCHIT

ECT. NO O

THER U

SE, DIS

SEMIN

ATIO

N, OR D

UPLIC

ATIO

N M

AY B

E M

ADE W

ITHOUT P

RIO

R W

RIT

TEN

CONSENT O

F T

HE A

RCHIT

ECT. ALL C

OMMON L

AW

RIG

HTS O

F C

OPYRIG

HT A

ND O

THERW

ISE A

RE H

EREBY S

PECIF

ICALLY R

ESERVED.

CLIENT

2221 Schrock RoadColumbus, Ohio 43229-1547p 614.898.7100f 614.898.7570www.msconsultants.com

PROJECT

10/4

/202

1 4:

48:2

0 PM

REFLECTED CEILING PLAN

A111

JPJ

CHARLES M. BUSCH - RA No. ARC.00403518EXP. DATE: 10/31/2021

10/04/2021

CLR/CMB

10/04/2021

62-40487-06

HCA HEALTH ONE, LLC4500 E 9TH AVESTE 160DENVER, CO 80220

QUESTDIAGNOSTICS

1/4" = 1'-0"1 REFLECTED CEILING PLANPLAN NORTH

SYMBOL LEGEND

GENERAL NOTES: 1. CENTER GRID WITHIN ROOM U.N.O.2. CENTER EXIT SIGN OVER ADJACENT DOOR U.N.O.3. REFER TO BRACING DETAILS FOR ADDITIONAL

INFORMATION

1 1/2" = 1'-0"3 DROP CEILING DETAIL1 1/2" = 1'-0"2

STUD BRACINGDETAIL

1 1/2" = 1'-0"4

WALL CONNECTIONDETAIL

# DATE DESCRIPTION

1. NO PAINTING OR INTERIOR FINISHING SHALL BE DONE UNDER CONDITIONS WHICH WILLJEOPARDIZE THE QUALITY OR APPEARANCE OF SUCH WORK. ALL WORKMANSHIP WHICH ISJUDGED LESS THAN FIRST QUALITY BY THE ARCHITECT SHALL BE REJECTED.

2. FLAME SPREAD TO BE CLASS 1: 0-25. SMOKE DENSITY TO BE LESS THAN 450.3. ALL SURFACES SHALL BE PREPARED TO RECEIVE THE SPECIFIED FINISH. ALL GYPSUM

BOARD PARTITIONS SHALL BE TAPED, SPACKLED AND SANDED SMOOTH AND PREPARED TORECEIVE THE SPECIFIED FINISH. PAINT-GRADE WOODWORK SHALL BE HAND SANDEDBETWEEN COATS AND DUSTED CLEAN. ALL HOLES, PITCH POCKETS, OR SAPPY PORTIONSSHALL BE SCRAPED AND SHELLACKED, OR SEALED WITH KNOT SEALER. NAIL HOLES,CRACKS, OR OTHER DEFECTS SHALL BE PUTTIED AFTER FIRST COAT WITH PUTTY MATCHINGCOLOR OF STAIN OR PAINT FINISH. REMOVE OIL OR GREASE WITH MINERAL SPIRITS.

4. ALL CRACKS, HOLES, IMPERFECTIONS IN EXISTING WALLS, PARTITIONS, OR GYP BOARDSHALL BE FILLED AND SMOOTHED OFF TO MATCH ADJOINING SURFACES INVISIBLY.

5. INTERIOR GYP BOARD SURFACES SHALL BE WIPED WITH A DAMP CLOTH JUST PRIOR TOAPPLICATION OF THE FIRST COAT OF PAINT IN ORDER TO LAY FLAT ANY NAP WHICH MAYHAVE FORMED DURING THE SANDING PROCESS.

6. UPON COMPLETION, REMOVE ALL PAINT FROM WHERE IT WAS SPILLED, SPLASHED, ORSPATTERED ON EXPOSED SURFACES.

7. ALL VENEER STAINS SHALL HAVE A UNIFORM COLOR.8. EXAMINE ALL FINISH SURFACES AFTER COMPLETION OF WORK AND PROCEED WITH "TOUCH-

UP" AS REQUIRED AFTER APPROPRIATE CURING TIME HAS ELAPSED.9. PROVIDE CLIENT WITH A MINIMUM OF (3) 8" x 10" BRUSH-OUTS OF EACH COLOR AND FINISH

FOR APPROVAL AT LEAST 2 WEEKS PRIOR TO SITE APPLICATION. ON-SITE APPLICATION WILLBE REQUIRED ONE WEEK PRIOR TO FINAL APPROVAL. THE CLIENT RESERVES THE RIGHT TOADJUST ANY COLOR/FINISH ONCE THE WALL TEST HAS BEEN MADE.

10. CONTRACTOR SHALL BE RESPONSIBLE FOR ALLOWING FOR DELIVERY LEAD TIMES FOR ALLFABRICS AND OTHER CUSTOM FINISHES WITHIN THE CONSTRUCTION SCHEDULE. ALLDELIVERY TIMES MUST BE CONFIRMED AND ANY EXCESSIVE LEAD TIME MUST BE BROUGHTTO THE ARCHITECT'S ATTENTION IMMEDIATELY TO ALLOW FOR RE-SPECIFICATION ASNECESSARY.

11. ALL VERTICAL SURFACES SHALL RECEIVE A WALL BASE UNLESS NOTED OTHERWISE.12. SEE FINISH PLAN, ELEVATIONS, AND DETAILS FOR CLARIFICATION OF EXTENT OF FINISH

MATERIALS.13. PAINT IS DEFINED AS ONE (1) PRIMER COAT AND TWO (2) FINISH COATS. ALL WALLS TO BE

ROLLER APPLIED.14. PAINT CEILING ACCESS PANELS WHERE THEY OCCUR TO MATCH ADJACENT CEILING FINISH.15. STAINED AND PAINTED SURFACES SHALL BE FINISHED SUCH THAT THE JOINTS ARE NOT

VISIBLE WHEN VIEWED FROM ANY ANGLE AS DETERMINED BY THE ARCHITECT.16. APPLY WALLCOVERING SO WALL IS DIVIDED WITH A MINIMUM NUMBER OF SEAMS, AND WITH

EQUAL-WIDTH PANELS, UNO.17. ALL INTERSECTIONS OF FLOOR FINISH MATERIALS SHALL BE LOCATED DIRECTLY UNDER

CENTER OF DOOR, WHEREVER OCCURS, UNO.18. ALL OPEN CABINETRY SHALL BE PLASTIC LAMINATE ON ALL EXPOSED SURFACES, UNO.

APPLY WHITE MELAMINE TO INTERIOR OF CABINETRY WITH DOORS AND DRAWERS, UNO.19. NO FINISHING IN EXISTING BUILDING CORE AREAS AND CORRIDORS, UNO.20. PAINT ALL EXPOSED SURFACES, INCLUDING GRILLES, FIRE HOSE OR EXTINGUISHER

CABINETS, EXPOSED PIPING, ETC., UNO.21. ALL COVER PLATES, SWITCHES, OUTLETS, RECEPTACLES, AND DEVICES TO BE WHITE, UNO.

NO EMPTY COVER PLATES TO REMAIN IN SPACE UPON COMPLETION. PATCH AND PAINT ASREQUIRED.

22. FIRE RATINGS OF ALL FLOOR WALL AND CEILING FINISH MATERIALS TO COMPLY WITH ICC2015 IBC SECTION 803 & 804

3"

4"

MOUNT FORMONITORLEDGER

UNDER COUNTERSUPPORT

GROMMET

UNDER COUNTER SUPPORTCABINET

EQEQ

EQEQ

4" WALL BASE (WB-1) INSTALL AFTER/OVER INPRO WALL PROTECTION INSTALLED

0'-0" A.F.F.

FINISH FLOOR

4'-0" A.F.F.

CUT CG AT THIS LOCATION ON ALL OUTSIDE CORNERS

CORNER GUARD (CG-1) INSTALL LAST -AFTER INPRO WALL PROTECTION AND WALL BASE - CUT AT BOTTOM OF CORNER GUARD TO PROVIDE 48" TO TOP OF CG AND INPRO

INPRO WALL (WP-2) PROTECTION - INSTALL ON WALLS FIRST

TR-3

HALL101

SPECIMENCONSOLIDATION

104

SPECIALSERVICES

01

PATIENTENCOUNTER

03

PATIENTENCOUNTER

02

EMPLOYEEBREAKROOM106

JANITOR/STORAGE

102

SUPPLY103

WAITINGROOM100

UNISEXTOILET

107

UNISEXTOILET

105

A15

Q301Q230

A3

A1

Q276

Q245Q230Q274

A13

A14

A12

Q150

A1

Q260 Q263

Q263

Q231 Q231

A13Q252

Q362 A14

Q123

Q140Q340

Q129

Q330Q231

Q133Q153

Q150Q102

Q140

Q340

Q129

Q231Q330

Q102Q150

Q153

Q123

Q140

A13

Q340Q129

Q252

Q362 A14

Q231Q133

Q150

Q153Q128

Q102

Q160

LVT-1

LVT-1

LVT-1

LVT-1

LVT-1

LVT-1LVT-1

LVT-1

CT-2 CT-2

TILE FLOOR GRID TO ALIGN TO TILE WALL GRID IN UNISEX TOILET ROOMS, TYP. SEE A210

S1S1

S2S3S2

TR-3

TR-1

BW-1

BW-1

BW-1

PT-3

PT-3

WP-2

WP-2

WP-2

WP-2

WP-2

WP-2

WP-2

SHEET

SHEET TITLE

ISSUE DATE

DRAWN BY

CHECKED BYAPPROVED BY

PROJECT NO.

REVISION

PROFESSIONAL OF RECORD:NOTIC

E: THIS

ARCHIT

ECTURAL A

ND E

NGIN

EERIN

G D

RAW

ING IS G

IVEN IN C

ONFID

ENCE A

ND S

HALL B

E U

SED O

NLY P

URSUANT T

O T

HE A

GREEMENT W

ITH T

HE A

RCHIT

ECT. NO O

THER U

SE, DIS

SEMIN

ATIO

N, OR D

UPLIC

ATIO

N M

AY B

E M

ADE W

ITHOUT P

RIO

R W

RIT

TEN

CONSENT O

F T

HE A

RCHIT

ECT. ALL C

OMMON L

AW

RIG

HTS O

F C

OPYRIG

HT A

ND O

THERW

ISE A

RE H

EREBY S

PECIF

ICALLY R

ESERVED.

CLIENT

2221 Schrock RoadColumbus, Ohio 43229-1547p 614.898.7100f 614.898.7570www.msconsultants.com

PROJECT

10/4

/202

1 4:

48:2

5 PM

FURNITURE AND FINISH PLAN

A131

JPJ

CHARLES M. BUSCH - RA No. ARC.00403518EXP. DATE: 10/31/2021

10/04/2021

CLR/CMB

10/04/2021

62-40487-06

HCA HEALTH ONE, LLC4500 E 9TH AVESTE 160DENVER, CO 80220

QUESTDIAGNOSTICS

NOTE: ALL EXISTING DOORS SHALL HAVE EXISTING THRESHOLDS TO REMAIN. REPLACE AS REQUIRED IF DAMAGED WITH ADA COMPLIANT

GENERAL FINISH NOTES

1/2" = 1'-0"2

ENLARGED PERCOUNTER

FURNITURE & FIXTURE SCHEDULEID # DESCRIPTION COMMENTS

Q092 E-CHECK INQ094 50" TV KIOSK (60" WIDE)Q102 DURISAN DISPENSER INCLUDES Q103 DURISAN REFILLQ110 EYE AND FACE WASH STATION - (2) 32 oz. MOUNTED 42" A.F.F. TO BOTTOM - CENTERED OVER SINKQ123 CENTRIFUGE, HORIZON BY DECKER INCLUDES Q124 CENTRIFUGE MATQ128 TAPE MEASURE, HEIGHT (MOUNTED)Q129 WEIGHT SCALE, DIGITAL FLOOR MODELQ133 BP MACHINE/CUFFQ140 LABWALL UNIT 12" ANODIZED MOUNTED 6" ABOVE BACKSPLASH. INCLUDES Q141 LABWALL UNIT

6" EXPANSION KIT, Q143 LARGE ULTRA CLEAR LABWALL BINS, Q144SMALL ULTRA CLEAR LABWALL BINS, AND Q145 MEDIUM ULTRACLEAR LABWALL BINS

Q150 GLOVE HOLDER, TRIPLE SIDE LOADING MOUNT 40" TO BOTTOM OF UNIT, 19" FROM CORNERQ153 WALL MOUNTED TUBE RACK (9 BIN) MOUNT 40" TO BOTTOM OF UNIT IN SPECIAL SERVICESQ160 INFANT EXAM STATION MOUNT WHEN IN THE OPEN POSITION AS A WORK SURFACE 30"

AFF. SEE NOTES ON G002Q202 INSIGNIA TV MONITOR (50") (1) Q220 TV MONITOR MOUNT PER TVQ230 OVAL TRASH CAN, 16 GALLONQ231 OVAL TRASH CAN, 13 GALLONQ245 SPECIMEN REFRIGERATOR/FREEZER 18cuQ252 CABLE MANAGEMENTQ260 SHELVING : 5 TIER - 24"Q263 SHELVING : 5 TIER - 60"Q274 15-SHEET CROSS-CUT SHREDDERQ276 MEAD BULLETIN BOARD, ALUMINUM FRAME, 3' x 2'Q292 LATERAL FILES 36"Q301 PLAYER CHAIRQ320 KRUG KARMA CHAIR WITH ARMSQ321 KRUG KARMA CHAIR WITHOUT ARMSQ330 STANDARD PHLEBOTOMY/DRAW CHAIRQ331 WALL AWAY RECLINER (PREFERRED)Q340 HON TASK STOOLQ362 ARTICULATING MONITOR ARMS

MILLWORK SCHEDULEID # DESCRIPTIONM2 PHLEBOTOMY CARTM3 UNDER COUNTER PER CABINETM4 UNDER COUNTER IT CABINETM5 2-HOOK COAT HOOK - MOUNT 54" AFF TO BOTTOM - SPECIAL SERVICES AND RESTROOMS AT

48" AFFM7 CUBBY SHELFM8 4-HOOK COAT HOOK - MOUNT 45" AFF TO BOTTOMM9 RESTROOM CABINET

M10 LOCKERSM13 EMPLOYEE BREAK ROOM TABLE

GENERAL NOTES:

1. ALL (U.N.O.) SHALL BE MOUNTED 48" A.F.F. TO BOTTOM OF OPERABLE PART. REFER TO G002 FOR ALL MOUNTING HEIGHTS ANDDIMENSIONS FOR FIXTURES AND RESTROOM ACCESSORIES.

2. ALL LISTED ITEMS ARE OWNER PROVIDED / GC INSTALLED

ALL ITEMS ARE OWNER PROVIDED/GC INSTALLED

ACCESSORY LISTID # DESCRIPTION MANUF/MODEL NO.A1 PAPER TOWEL DISPENSER BOBRICK B-2620A2 HAND DRYER Q973A; VERDEDRI / ITEM#: T97B489340A3 MICROWAVE SHARP-ZSMC1441CBA4 STAINLESS STEEL SHELF-4"x18" BOBRICK - T97B489340A5 MOP HOOK UNGER-964770A6 18" GRAB BAR BOBRICK B-6806x18A7 36" GRAB BAR BOBRICK B-6806x36A8 42" GRAB BAR BOBRICK B-6806x42A9 WIRE SHELVING 12" x 72"A10 TOILET PAPER DISPENSER BOBRICK B2840A11 MIRROR T97B489400 BY GLOBAL INDUSTRIESA12 COPIER/FAX TENANT PROVIDED / TENANT INSTALLEDA13 PRINTER TENANT PROVIDED / TENANT INSTALLEDA14 COMPUTER, KEYBOARD,

MOUSE, MONITORTENANT PROVIDED / TENANT INSTALLED

A15 REFRIGERATOR/FREEZER PRN12160MS (DOOR TO SWING INTO WALL AND OPENTOWARDS OPENING OF SPACE)

3/4" = 1'-0"3

ENLARGED CORNERGUARD DETAIL

1/4" = 1'-0"4 FURNITURE AND FINISH PLAN

*ALL ITEMS LISTED ARE GC PROVIDED / GC INSTALLED (U.N.O.)**ALL ITEMS SHALL BE MOUNTED AT 48" A.F.F. (U.N.O) TO BOTTOM OF OPERABLE PART. REFER TO G002 FOR ALL MOUNTING HEIGHTS AND DIMENSIONS FOR FIXTURES AND RESTROOM ACCESSORIES.

SIGNAGE REQUIREMENTSID # DESCRIPTIONS1 SINGLE-OCCUPANCY PUBLIC FACILITIES SHALL BE DESIGNATED WITH GENDER-NEUTRAL

SIGNAGE. SIGNS SHALL BE READILY VISIBLE AND LOCATED NEAR THE ENTRANCE TO EACHTOILET FACILITY

S2 DIRECTIONAL SIGNAGE INDICATING EXIT AT EGRESS DOOR AT EXIT SHALL INCLUDE RAISEDCHARACTER BRAILLE ON SIGNAGE

S3 OCCUPANT LOAD SIGN. ALL SIGNS SHALL MEET IBC 1004.3

GENERAL:THESE DIRECTIONAL SIGNS SHALL INCLUDE THE INTERNATIONAL SYMBOL OF ACCESSIBILITY AND SIGN CHARACTERS SHALL MEET THE VISUAL CHARACTER REQUIREMENTS IN ACCORDANCE WITH ICC A117.1. ALL SIGNS SHALL BE MOUNTED 40" A.F.F. TO BASELINE OF SIGN CHARACTER. SEE SHEET G002 FOR ADDITIONAL INFORMATION. ALL SIGNS SHALL MEET IBC 1004.3

FINISH LEGENDTAG DESCRIPTION MANUFACTURER STYLE COLOR SIZE COMMENTS

ACT-1 ACOUSTIC CEILINGTILE

ARMSTRONG CORTEGA - SECOND LOOK ANGLEDTEGULAR

WHITE 24"x48" PRELUDE EXPOSED TEE, XL 15/16" GRID, WHITE

CG-1 CORNER GUARD INPRO TAPE ON CORNER GUARD (WITHOUTTAPE)

TAUPE 0113 2"x48" INSTALL AT ALL OUTSIDE CORNERS THROUGHOUT SPACE. SEEDETAIL 4/A131 FOR INSTALLATION DIRECTIONS

CG-2 CORNER GUARD INPRO TAPE ON CORNER GUARD (WITHOUTTAPE)

TAUPE 0113 2"xOPENINGH

INSTALL AT ALL OPENINGS INTO PERS AND GRAPHIC WALLS

BW-1 BRANDING WALLPAPER

SEE PLAN

CPT-1 CARPET TARKETT TANDUSCENTIVA

SINE EFFECT 11340 SNAKEBARK 39101 MOD/ROLL NOT USED

CPT-2 WALKOFF MAT MATS, INC CALYPSO TILE ANTHRACITE 20"x20" IN VESTIBULE ONLY

CT-1 PORCELAIN TILE CROSSVILLE BASALT SILICA #AV291 12"x24" 4"X24" BULLNOSE CAP AT TOP OF CT-1 WAINSCOT, START FULLTILE AT FLOOR WITH TR-3 COVE - 3/16" GROUT JOINT

CT-2 PORCELAIN TILE CROSSVILLE BASALT MAGMA #AV295 12"x24" FLOOR ONLY

LVT-1 LUXURY VINYL TILE ARMSTRONG NATURAL CREATIONS ARBOR ART COASTAL CRAFTED MARITIME #NA120 9"x48"

PT-1 PAINT SHERWIN WILLIAMS SATIN SW 7003 TOQUE WHITE GENERAL WALLS FIELD PAINTPT-2 PAINT SHERWIN WILLIAMS SATIN SW 6525 RARIFIED AIR ACCENT PAINTPT-3 PAINT SHERWIN WILLIAMS SATIN SW 6241 ALEUTIAN ACCENT PAINTPT-4 PAINT SHERWIN WILLIAMS SATIN SW 9166 DRIFT OF MIST ACCENT PAINTPT-5 PAINT SHERWIN WILLIAMS FLAT SW 7007 CEILING BRIGHT WHITE GYP BOARD CEILINGSPT-6 PAINT SHERWIN WILLIAMS SEMI-GLOSS SW 6005 FOLKSTONE HOLLOW METAL DOOR FRAMES

T-1 GROUT TEC INCOLOR ADVANCED PERFORMANCE 909 STERLING 3/16" GROUT JOINT/WALLS ONLYT-2 GROUT TEC INCOLOR ADVANCED PERFORMANCE 929 CHARCOAL GRAY 3/16" GROUT JOINT/FLOORS ONLY

TR-1 TRANSITION STRIP SCHLUTER RENO-U EB-BRUSHED STAINLESS STEEL HEIGHT TO BE COORDINATED WITH THE PORCELAIN TILETHICKNESS

TR-2 TRANSITION STRIP SCHLUTER RENO-RAMP-K AE-SATIN ANODIZED ALUMINUM HEIGHT TO BE COORDINATED WITH THE WALKOFF MAT CARPETTILE THICKNESS

TR-3 TRANSITION STRIP SCHLUTER DILEX-HKU STAINLESS STEEL INSTALL AT TOILET ROOM FLOOR/WALL TRANSITION

WB-1 WALL BASE JOHNSONITE 197 SHADED WG 4" WHERE LVT-1 IS USEDWB-2 WALL BASE ROPPE TOELESS 123 CHARCOAL 4" WHERE CPT-1 AND CPT-2 ARE USED

PL-1 PLASTIC LAMINATE --- --- LAMINATE "SLATE GRAY" PLASTIC LAMINATE DOOR

WD-1 WOOD STAIN SHERWINWILLIAMS-MINWAX

--- MW 405 TOASTED BARREL GC TO PROVIDE SAMPLE FOR APPROVAL PRIOR TO STAINING ALLDOORS

WP-2 WALL PROTECTION INPRO RICOCHET HARMONY GLADIATOR RD-HAR-R308 INSTALL IN ALL HALLWAYS WITH 0113 TAUPE TOP CAP TRIM. SEEDETAIL 3/A131 FOR INSTALLATION INFORMATION

ROOM FINISH SCHEDULEROOM NAME

FLOORFINISH

BASEFINISH

CEILINGFINISH WALL COMMENTS

EMPLOYEE BREAK ROOM LVT-1 WB-1 ACT-1 PT-2/PT-3 SEE PLAN FOR PT-3 ACCENT WALLEMPLOYEE CONSULTATIONROOM

LVT-1 WB-1 ACT-1 PT-2/PT-3 SEE PLAN FOR PT-3 ACCENT WALL

HALL LVT-1 WB-1 ACT-1 PT-1/WP-2 PT-4 AT ALL ALCOVE WALLS INCLUDING SINK AND DRINKING FOUNTAIN; MOUNT TWO (4) COAT HOOKS OUTSIDE OFBREAKROOM AT 4'-0" A.F.F.

JANITOR/STORAGE LVT-1 WP-2 EXPOSED WP-2/PT-1 WP-2 UP TO 48" A.F.F. ON ALL WALLSPATIENT ENCOUNTER ROOMS LVT-1 WB-1/WP-2 ACT-1 PT-1 WP-2 UP TO 48" A.F.F. ON WALL BEHIND PHLEBOTOMY CHAIR. SEE PLAN FOR ADDITIONAL REQ. LOCATIONSPATIENT HOLD ROOM LVT-1 WB-1 ACT-1 PT-2/PT-3 SEE PLAN FOR PT-3 ACCENT WALLSPECIAL SERVICES ROOM LVT-1 WB-1/WP-2 ACT-1 PT-1 WP-2 UP TO 48" A.F.F. ON WALL BEHIND PHLEBOTOMY CHAIR. SEE PLAN FOR ADDITIONAL REQ. LOCATIONSSPECIMEN CONSOLIDATIONROOM

LVT-1 WB-1 ACT-1 PT-2/PT-3 SEE PLAN FOR PT-3 ACCENT WALL

SUPPLY ROOM LVT-1 WB-1 ACT-1 PT-1TOILET ROOMS CT-2 CT-1/TR-3 GYP-1 CT-1/PT-4 REFER TO DETAIL 4 ON A601 FOR SILL INFORMATION.VESTIBULE CPT-2 WB-2 ACT-1 -- STOREFRONT WINDOWS AT ALL NEW VESTIBULE SIDES - PAINT BELOW EXISTING WINDOW SILL PT-1WAITING ROOM LVT-1 WB-1 ACT-1 PT-1

# DATE DESCRIPTION

FINISH FLOOR

+ 0' - 0" A.F.F.

ACT CEILING

9' - 0" A.F.F.

PT-1

WB-1

60"

Q202

4"

18"

12"

CENTER OF TV

ADA DOOR CLEARANCE5' - 0" MIN

7' - 6"

20"

FINISH FLOOR

+ 0' - 0" A.F.F.

ACT CEILING

+9' - 0" A.F.F.

PT-1

WB-1

Q102

5' - 0"CLR15"

T.O. BULL NOSE

+ 6' - 4" A.F.F.

GYP BD CEILING+ 7' - 11" A.F.F.

FINISH FLOOR

+ 0' - 0" A.F.F.

PT-4

CT-1

START TILE IN CENTER

A8

A2

B.O

.F.

4' -

0" M

AX

A6

A10

PROTECTED (TYP.)FIXTURES TO BEALL PLUMBING

GYP BD CEILING

+ 7' - 11" A.F.F.

T.O. BULL NOSE

+ 6' - 4" A.F.F.

FINISH FLOOR

+ 0' - 0" A.F.F.

CT-1

PT-43' - 9"

A11 A2

A7 A8

A10

START TILE IN CENTER

FINISH FLOOR

+ 0' - 0" A.F.F.

GYP BD CEILING

+ 7' - 11" A.F.F.

T.O. BULL NOSE

+ 6' - 4" A.F.F.

CT-1

PT-4

M5

FINISH FLOOR

+ 0' - 0" A.F.F.

T.O. WALL+ 7' - 11" A.F.F.

PT-1

WB-1

EQ EQ

T.O

. CO

UN

TER

2' -

10" M

AX.

6"

Q160Q140

6"

BEYONDOPEN TO

T.O. FRAMED OPENING+ 7' - 0" A.F.F.

FINISH FLOOR

+ 0' - 0" A.F.F.

PT-1

WB-1

1' - 7"

ACT CEILING+ 7' - 11" A.F.F.

Q102 Q150 Q153

3' - 7"

WP-2

FINISH FLOOR

+ 0' - 0" A.F.F.

PT-1

WP-2

T.O

. CO

UN

TER

3' -

2"

1' - 0"

8' - 0"

20"

ACT CEILING+ 7 - 11" A.F.F.

Q150

Q102

Q133

Q153

4' -

0"

FINISH FLOOR

+ 0' - 0" A.F.F.

PT-1

WB-1

EQ EQ

ACT CEILING+ 7' - 11" A.F.F.

6"

Q140

6"

FINISH FLOOR

+ 0' - 0" A.F.F.

WB-1

PT-1

ACT CEILING+7' - 11" A.F.F.

M5

1' - 0"

ACT CEILING

+ 7' - 11" A.F.F.

FINISH FLOOR

+ 0' - 0" A.F.F.

WB-1

PT-2

EQ. EQ

T.O

. CO

UN

TER

3' -

2"

Q150

M7

T.O

. SIN

K

2' -

10"

TO B

OTT

OM

54"

PT-3

FINISH FLOOR

+ 0' - 0" A.F.F.

ACT CEILING

+ 7' - 11" A.F.F.

1' - 6"

2' - 6"

WB-12

A101

A1 Q150

FINISH FLOOR

+ 0' - 0" A.F.F.

WB-1

PT-1

2' -

1" B

.O.F

.

5' - 0"

1' - 0"

ACT CEILING+ 7' - 11" A.F.F.

Q160 M5

3' - 3"

FINISH FLOOR

+ 0' - 0" A.F.F.

PT-1

WP-2

8' - 0"

20"

1' - 0"

T.O

. CO

UN

TER

2' -

10"

ACT CEILING+ 7' - 11" A.F.F.

Q153

FINISH FLOOR

+ 0' - 0" A.F.F.

ACT CEILING

+ 7' - 11" A.F.F.8"

4' -

6"

T.O

. SIN

K2'

- 10

"

2A101

PT-2

WB-1

A1

A3

ACCESSIBLE LOCKER TO BE WITHIN 15" A.F.F. TO 48" A.F.F.

PROTECTEDPIPES TO BEALL PLUMBING

+ 0' - 0" A.F.F.

FINISH FLOOR

WP-2

WB-1

T.O

.F.

3' -

4"T.

O. S

INK

2' -

10"

PT-4

+ 7' - 11" A.F.F.

A1Q110

A4

FINISH FLOOR

+ 0' - 0" A.F.F.

PT-1

WB-1

EQEQ

T.O

. CO

UN

TER

3' -

2"

6"

ACT CEILING+ 7' - 11" A.F.F.

6"

Q140

20"

2' - 9"

PT-1

1' - 7"

3' - 7"

Q150Q102

WB-1

OPENING FOR BARN

DOOR

T.O. FRAMED OPENING+ 6' - 10" A.F.F.

FINISH FLOOR

+ 0' - 0" A.F.F.

ACT CEILING+ 7' - 11" A.F.F.

SHEET

SHEET TITLE

ISSUE DATE

DRAWN BY

CHECKED BYAPPROVED BY

PROJECT NO.

REVISION

PROFESSIONAL OF RECORD:NOTIC

E: THIS

ARCHIT

ECTURAL A

ND E

NGIN

EERIN

G D

RAW

ING IS G

IVEN IN C

ONFID

ENCE A

ND S

HALL B

E U

SED O

NLY P

URSUANT T

O T

HE A

GREEMENT W

ITH T

HE A

RCHIT

ECT. NO O

THER U

SE, DIS

SEMIN

ATIO

N, OR D

UPLIC

ATIO

N M

AY B

E M

ADE W

ITHOUT P

RIO

R W

RIT

TEN

CONSENT O

F T

HE A

RCHIT

ECT. ALL C

OMMON L

AW

RIG

HTS O

F C

OPYRIG

HT A

ND O

THERW

ISE A

RE H

EREBY S

PECIF

ICALLY R

ESERVED.

CLIENT

2221 Schrock RoadColumbus, Ohio 43229-1547p 614.898.7100f 614.898.7570www.msconsultants.com

PROJECT

10/4

/202

1 4:

48:2

8 PM

INTERIOR ELEVATIONS

A210

JPJ

CHARLES M. BUSCH - RA No. ARC.00403518EXP. DATE: 10/31/2021

10/04/2021

CLR/CMB

10/04/2021

62-40487-06

HCA HEALTH ONE, LLC4500 E 9TH AVESTE 160DENVER, CO 80220

QUESTDIAGNOSTICS

NOTE: REFER TO G002 FOR ALL MOUNTING HEIGHTS AND DIMENSIONS FOR FIXTURES AND RESTROOM ACCESSORIES

ACCESSORY LISTID # DESCRIPTION MANUF/MODEL NO.A1 PAPER TOWEL DISPENSER BOBRICK B-2620A2 HAND DRYER Q973A; VERDEDRI / ITEM#: T97B489340A3 MICROWAVE SHARP-ZSMC1441CBA4 STAINLESS STEEL SHELF-4"x18" BOBRICK - T97B489340A5 MOP HOOK UNGER-964770A6 18" GRAB BAR BOBRICK B-6806x18A7 36" GRAB BAR BOBRICK B-6806x36A8 42" GRAB BAR BOBRICK B-6806x42A9 WIRE SHELVING 12" x 72"A10 TOILET PAPER DISPENSER BOBRICK B2840A11 MIRROR T97B489400 BY GLOBAL INDUSTRIESA12 COPIER/FAX TENANT PROVIDED / TENANT INSTALLEDA13 PRINTER TENANT PROVIDED / TENANT INSTALLEDA14 COMPUTER, KEYBOARD,

MOUSE, MONITORTENANT PROVIDED / TENANT INSTALLED

A15 REFRIGERATOR/FREEZER PRN12160MS (DOOR TO SWING INTO WALL AND OPENTOWARDS OPENING OF SPACE)

3/8" = 1'-0"1A WAITING ROOM ELEVATION3/8" = 1'-0"1B WAITING ROOM ELEVATION

3/8" = 1'-0"2A TOILET ROOM3/8" = 1'-0"2B TOILET ROOM

3/8" = 1'-0"2C TOILET ROOM

3/8" = 1'-0"5A SPECIAL SERVICES

3/8" = 1'-0"3A

PATIENT ENCOUNTERROOM

3/8" = 1'-0"3B

PATIENT ENCOUNTERROOM

3/8" = 1'-0"3C

PATIENT ENCOUNTERROOM 3/8" = 1'-0"3D

PATIENT ENCOUNTERROOM

3/8" = 1'-0"6A

SPECIMENCONSOLIDATION

3/8" = 1'-0"6B

SPECIMENCONSOLIDATION

3/8" = 1'-0"5B SPECIAL SERVICES3/8" = 1'-0"5C SPECIAL SERVICES

3/8" = 1'-0"7

EMPLOYEEBREAKROOM

3/8" = 1'-0"8 HALL ALCOVE

*ALL ITEMS LISTED ARE GC PROVIDED / GC INSTALLED (U.N.O.)**ALL ITEMS SHALL BE MOUNTED AT 48" A.F.F. (U.N.O) TO BOTTOM OF OPERABLE PART. REFER TO G002 FOR ALL MOUNTING HEIGHTS AND DIMENSIONS FOR FIXTURES AND RESTROOM ACCESSORIES.

3/8" = 1'-0"4

PATIENT ENCOUNTERROOM IT CABINET

3/8" = 1'-0"5D SPECIAL SERVICES

# DATE DESCRIPTION

1/2" 1/2"

H.M. FRAME AS SCHEDULED

WOOD NAILER

DOOR AS SCHEDULED

+ 7' - 0" A.F.F.

H.M. FRAME AS SCHEDULED

DOOR AS SCHEDULED

WOOD NAILER AND BLOCKING

SEALANT (BOTH SIDES)

OPENING3' - 4"

A B C D

6' -

10"

34"

8"

FROSTED

7' -

0"2"

2" 3' - 0" 2"

10"

7' -

2"

2"

3' - 4"

2" 2" 2"

1' - 3 3/4"

6"6'

- 6"

7' -

2"2"

2"

3' - 4"

2"

TT

1' - 1 3/4"

T

6" 23 3/4" 6"

12"

63 3

/4"

8"

ALUM FRAMED DOOR AS SCHEDULED

4"X4" INTERIOR ALUMINUM FRAMING

VESTIBULE STOREFRONT SYSTEM

2"

4"X4" INTERIOR ALUMINUM FRAMING

VESTIBULE STOREFRONT SYSTEM

DOOR AS SCHEDULED

PROVIDE F.R.T. BLOCKING PER DOOR INSTALLATION REQUIREMENTS

5/8" GYP BD ON METAL STUD

PARTITION BEYOND

+ 6' - 10" A.F.F.

NO. 2 HALL1 1/2 PAIR HINGES 5BB1 4 1/2" X 4 1/2" (5KNUCKLE BALL BEARING) IVE1 ELEC LOCK CO-SCH-FE575-PLY-ELA-626 (BATTERY OPERATED) SCHLAGE1 DOOR CLOSER 1450 EDA (SURFACE- CORRIDOR SIDE) (AUX STOP MAX OF 135 DEG) LCN

NOTE: HALL SIDE TO HAVE A EGRESS LEVER AND FUNCTION WITHOUT KEY CONTROL

NO. 31 1/2 PAIR HINGES IVE1 LEVER PASSAGE SET AL10S, SATURN SERIES - ASA STRIKE OR EQUAL US26D SCHLAGE1 WALL STOP 409 ROCKWOOD

NO. 4 TOILET ROOMS1 1/2 PAIR HINGES 5BB1 4 1/2" X 4 1/2" (5KNUCKLE BALL BEARING) IVE1 LEVER PRIVACY SET L9040 06A L583-363-L283-722L9040 06A L583-363-L283-722

L SERIES S/EZ TURN AND OCCUPANCY INDICATOR W/ TRIM, EMERGENCY KEYSCHLAGE

1 DOOR CLOSER 1450 EDA (SURFACE- INTERIOR SIDE NOT HALL SIDE) LCN1 WALL STOP ROCKWOOD

NO. 51 PULL (EA. SIDE) 1 WALL SEAL

FLEXIBLE TRACK SYSTEM

NOTE: INSTALL PER MANUFACTURER'S REQUIREMENTS.

BARN DOOR RE:A2/A601

FINISH 651

FINISH 651FINISH 625

FINISH 651

409

FINISH 689

GENERAL NOTES:1. VERIFY HARDWARE REQUIREMENTS, TYPES & FINISHES W/ OWNER REP PRIOR TO PURCHASE. PROVIDE CUT

SHEETS FOR REVIEW.2. ALL SELECTED HARDWARE, CLOSER PRESSURES, THRESHOLDS, AND CLEARANCES TO COMPLY WITH APPLICABLE

NATIONAL, STATE, AND LOCAL ACCESSIBILITY CODES AND REQUIREMENTS. VERIFY ACCESSIBILITY COMPLIANCE WITHMANUFACTURER.

3. PROVIDE HC SIGNAGE PER CODE4. ALL SEALS PROVIDED BY "THE SLIDING DOOR COMPANY".5. WHERE APPLICABLE, VERIFY EXISTING HARDWARE TO REMAIN AND SUPPLEMENT WITH NEW HC HARDWARE AS REQUIRED.

HARDWARE SET DESCRIPTION MANUFACTURERHARDWARE SCHEDULENO. 1 STORE FRONT ENTRY

REPLACE INTERCHANGEABLE CORE FOR ENTRY DOOR. COORDINATE KEYING WITH OWNER - REPLACE ANY DAMAGED HARDWARE WITH COMPARABLE QUALITY

H.M. FRAME AS SCHEDULED

DOOR AS SCHEDULED

2"x4 1/2" HOLLOW METAL FRAME AS SCHEDULED

HEIGHT OF STUD GAUGE SPACING (IN U.N.O)

INTERIOR MTL. STUD SCHEDULE (U.N.O)

< 15'-0"

15'-0" - 20'-0"

> 20'-0"

20

18

16

16

16

16

STUD DEPTH INDICATED ON DRAWINGSNOTES

THIS TABLE IS FOR GENERAL REFERENCE ONLY, STUD MANUFACTURER'S SPAN TABLES SHOULD SUPERSEDE THIS TABLE BASED ON STUD DESIGNATION SELECTED AND SPAN REQUIREMENTS

HOLLOW METAL FRAME BEYOND

DOOR AND FINISH AS SCHEDULED

(1/4

" CH

AMFE

R)

1/2"

MAX

.

LVT FLOORING AS SPECIFIED

ANODIZED ALUMINUM TRANSITION STRIP BY SCHLUTER - RENO-U OR EQUAL

PORCELAIN TILE AS SPECIFIED

EXISTING FLOOR SLAB

4"

4"

PROVIDE SOLID BLOCKING PAINTED BLACK WITH BREAK METAL TO MATCH NEW STOREFRONT

NEW VESTIBULE STOREFRONT SYSTEM

EXISTING INSULATED STOREFRONT WINDOW SYSTEM TO REMAIN AS IS

SHEET

SHEET TITLE

ISSUE DATE

DRAWN BY

CHECKED BYAPPROVED BY

PROJECT NO.

REVISION

PROFESSIONAL OF RECORD:NOTIC

E: THIS

ARCHIT

ECTURAL A

ND E

NGIN

EERIN

G D

RAW

ING IS G

IVEN IN C

ONFID

ENCE A

ND S

HALL B

E U

SED O

NLY P

URSUANT T

O T

HE A

GREEMENT W

ITH T

HE A

RCHIT

ECT. NO O

THER U

SE, DIS

SEMIN

ATIO

N, OR D

UPLIC

ATIO

N M

AY B

E M

ADE W

ITHOUT P

RIO

R W

RIT

TEN

CONSENT O

F T

HE A

RCHIT

ECT. ALL C

OMMON L

AW

RIG

HTS O

F C

OPYRIG

HT A

ND O

THERW

ISE A

RE H

EREBY S

PECIF

ICALLY R

ESERVED.

CLIENT

2221 Schrock RoadColumbus, Ohio 43229-1547p 614.898.7100f 614.898.7570www.msconsultants.com

PROJECT

10/4

/202

1 4:

48:3

1 PM

SCHEDULES AND DETAILS

A601

JPJ

CHARLES M. BUSCH - RA No. ARC.00403518EXP. DATE: 10/31/2021

10/04/2021

CLR/CMB

10/04/2021

62-40487-06

HCA HEALTH ONE, LLC4500 E 9TH AVESTE 160DENVER, CO 80220

QUESTDIAGNOSTICS

1 1/2" = 1'-0"5 HEAD DETAIL

1 1/2" = 1'-0"3 JAMB DETAIL

3/8" = 1'-0"

DOOR / FRAME ELEVATIONS

1 1/2" = 1'-0"7

VESTIBULE DOORJAMB DETAIL

1 1/2" = 1'-0"1

VESTIBULE CORNERJAMB DETAIL

1 1/2" = 1'-0"6

BARN DOOR HEADDETAIL

NOTE: "T" INDICATES GLAZING UNITS TO BE FULLY TEMPERED GLASS

1 1/2" = 1'-0"2 SIDELIGHT JAMB DETAIL

9

1 1/2" = 1'-0"4 SILL DETAIL

DOOR SCHEDULENO. ROOM NAME WIDTH HEIGHT

DOORMATERIAL

DOOR/ FRAMETYPE

FRAMEMATERIAL

HEADDETAIL

JAMBDETAIL

HARDWARESET REMARKS

100A WAITING ROOM 3' - 0" 7' - 0" ETR ETR ETR -- -- 1 EXISTING DOOR TO REMAIN - GC TO VERIFY EXISTINGDOOR COMPLIES WITH DETAIL 4/A601. PROTECTDURING CONSTRUCTION. RE-KEY AS REQUIRED.REPLACE ANY DEFICIENT HARDWARE.

100B WAITING ROOM 3' - 0" 7' - 0" WOOD/GLASS C H.M. 5/A601 2/A601 2 FLUSH WOOD WITH FULL PANEL TEMPERED GLASS101 SPECIAL SERVICES 3' - 4" 6' - 10" ALUM/GLASS A ALUM 6/A601 -- 5 ADJUST DOOR STOPS AT HEAD TRACK AS NECESSARY

TO MAINTAIN 1 1/2" MIN BETWEEN DOOR HANDLE ANDJAMB, AND FOR DOOR TO NOT STRIKE FAR JAMBSURFACE WHEN FULLY CLOSED.

102 JANITOR/ STORAGE 3' - 0" 7' - 0" WOOD B H.M. 5/A601 3/A601 3103 SUPPLY 3' - 0" 7' - 0" WOOD B H.M. 5/A601 3/A601 3105 UNISEX TOILET 3' - 0" 7' - 0" WOOD B H.M. 5/A601 3/A601 4 COAT/PURSE HOOK MOUNTED TO TOILET SIDE OF

DOOR106 EMPLOYEE BREAK

ROOM3' - 4" 6' - 10" ALUM/GLASS A ALUM 6/A601 -- 5 ADJUST DOOR STOPS AT HEAD TRACK AS NECCESARY

TO MAINTAIN 1 1/2" MIN BETWEEN DOOR HANDLE ANDJAMB, AND FOR DOOR TO NOT STRIKE FAR JAMBSURFACCE WHEN FULLY CLOSED.

107 UNISEX TOILET 3' - 0" 7' - 0" WOOD B H.M. 5/A601 3/A601 4 COAT/PURSE HOOK MOUNTED TO TOILET SIDE OFDOOR

NOTE: *PAINT ALL HOLLOW METAL DOOR FRAMES PT-6 OR STAINED WD-1**GC TO VERIFY LAMINATE WOOD DOOR LEAD TIME PRIOR TO ORDERING. IF REQUIRED PROVIDE WOOD DOOR W/ STAIN PER FINISH LEGEND

1 1/2" = 1'-0"8 CONNECTION DETAIL

NOT USED

NOT USED

NOT USED

# DATE DESCRIPTION

00 70 00 - CONDITIONS OF THE CONTRACT1. THE GENERAL CONDITIONS OF THE CONTRACT FOR CONSTRUCTION AND SUPPLEMENTAL CONDITIONS ARE PROVIDED UNDER

SEPARATE COVER, AND ARE INCORPORATED INTO THESE SPECIFICATIONS BY REFERENCE. WHERE ANY PART OF THE CONTRACTDOCUMENTS IS INCONSISTENT WITH THESE CONDITIONS OF THE CONTRACT, THE CONDITIONS OF THE CONTRACT SHALL GOVERN.

2. DEFINITIONS:A. "DAY": A DAY IS A CALENDAR DAY BEGINNING AND ENDING AT 12:00 MIDNIGHT.B. "ALIGN": MEANS TO INSTALL FINISHED FACES OF NEW MATERIAL FLUSH, PLUMB AND TRUE TO LINE WITH ADJACENT EXISTING

CONSTRUCTION.C. "FURNISH": MEANS TO SUPPLY AND DELIVER TO PROJECT SITE, READY FOR UNLOADING, UNPACKING, ASSEMBLY,

INSTALLATION, AND SIMILAR OPERATIONS.D. "INSTALL": MEANS TO UNLOAD, PROVIDE TEMPORARY STORAGE AT THE SITE, UNPACK, ASSEMBLE, ERECT, PLACE, ANCHOR,

APPLY, WORK TO DIMENSION, FINISH, CURE, PROTECT, CLEAN, AND SIMILAR OPERATIONS TO PROVIDE THE WORK REQUIRED BY THE CONTRACT DOCUMENTS.

E. "PROVIDE": MEANS TO FURNISH AND INSTALL, COMPLETE, AND READY FOR THE INTENDED USE.F. "SIMILAR": MEANS SYSTEM OR CONSTRUCTION COMPARABLE TO CONDITION NOTED. IN CASE OF CONTROVERSY, REQUEST

INSTRUCTION FROM ARCHITECT PRIOR TO PROCEEDING.G. "TYPICAL": MEANS IDENTICAL SYSTEM OR CONSTRUCTION AT SIMILAR LOCATIONS NOTED.

3. ALL COMMUNICATIONS FROM OWNER RELATIVE TO CHANGES IN THE WORK WILL BE THROUGH PROJECT MANAGER TO CONTRACTOR.IF CONTRACTOR CLAIMS THAT A REVISION TO CONTRACT DOCUMENTS INVOLVES EXTRA COST, CONTRACTOR SHALL SUBMIT WRITTENNOTICE TO THE PROJECT MANAGER WITHIN 30 DAYS AFTER RECEIPT OF SUCH INSTRUCTIONS. NO CHANGE IN THE WORK SHALL BEPERFORMED WITHOUT A VALID CHANGE ORDER COVERING THE SCOPE OF THE CHANGE AND SIGNED BY THE OWNER.

4. BY ENTERING INTO THIS AGREEMENT WITH THE OWNER, THE CONTRACTOR REPRESENTS THAT HE HAS VISITED THE JOB SITE,FAMILIARIZED HIMSELF WITH EXISTING CONDITIONS, AND NOTED DISCREPANCIES BETWEEN EXISTING CONDITIONS AND THOSE OF THECONTRACT DOCUMENTS.

5. SUBMIT A COMPLETE WRITTEN DESCRIPTION OF THE SCOPE OF EACH CHANGE IN THE WORK INCLUDING ROOM NUMBERS AFFECTED.PREPARE QUOTATIONS FOR PROPOSED CHANGES IN THE WORK IN A "BREAK-DOWN" FORM, GIVING THE NUMBER OF UNITS, UNIT COSTOF MATERIALS, HOURS OF LABOR, HOURLY COST OF LABOR, TOOLS, SUPPLIES, EQUIPMENT, TRANSPORTATION, SUPERINTENDENTS,CONSTRUCTION FACILITIES AND TEMPORARY CONTROLS OF EVERY NATURE, INSURANCE, TAXES, BONDS, ALL OTHER OVERHEADCOSTS AND PROFIT, AND SHALL REFLECT CREDITS AS WELL AS EXTRAS.

6. CONTRACTOR SHALL MAINTAIN A CURRENT AND COMPLETE SET OF CONTRACT DOCUMENTS ON SITE DURING CONSTRUCTION FORUSE OF ALL TRADES. ENSURE THAT ALL SUBCONTRACTORS RECEIVE COMPLETE SETS OF CONSTRUCTION DRAWINGS. CONTRACTORSHALL ASSUME RESPONSIBILITY FOR COORDINATION OF ALL WORK.

7. THE OWNER, WITHOUT INVALIDATING THE CONTRACT, MAY ORDER EXTRA WORK OR MAKE CHANGES BY ALTERING, ADDING T0, ORDEDUCTING FROM THE WORK. CONTRACT SUM AND CLAIMS FOR EXTENSION OF TIME WILL BE ADJUSTED IN ACCORDANCE WITHCONTRACT CONDITIONS RELATIVE TO CHANGES IN THE WORK. CHANGES IN THE WORK SHALL BE PROVIDED IN ACCORDANCE WITHTHE CONTRACT DOCUMENTS.

8. SECTIONS OF DIVISION 1 - GENERAL REQUIREMENTS, GOVERN THE EXECUTION OF THE WORK OF ALL SECTIONS OF THESPECIFICATIONS.

9. GC WILL ASSIGN PM TO ATTEND WEEKLY PROJECT CALLS LASTING APPROXIMATELY ONE HOUR AND OTHER CALLS AS NEEDED.

01 10 00 - SUMMARY OF WORK1. SCOPE OF WORK, LOCATION, AND OTHER DATA IS INDICATED BY DRAWING CONTENT.2. PROVIDE WORK IN ACCORDANCE WITH REQUIREMENTS OF THE "AMERICANS WITH DISABILITIES ACT" (ADA), INCLUDING LATEST

AMENDMENTS. WHERE WORK SHOWN DOES NOT COMPLY WITH THE ADA, HALT THE EFFECTED WORK AND REQUEST WRITTENINSTRUCTIONS FROM THE ARCHITECT PRIOR TO PROCEEDING.

3. IDENTIFY TOILET FACILITIES WITH SIGNAGE COMPLYING WITH THE INTERNATIONAL SYMBOL OF ACCESSIBILITY (UBC CHAPTER 11).4. THE PATH OF TRAVEL FROM THE DESIGNATED HANDICAP PARKING SPACES AND THE PUBLIC SIDEWALK PROVIDES A FREE AND

UNOBSTRUCTED PASSAGE FOR ACCESS TO AND EGRESS FROM THE AREA OF WORK.5. MOUNT LIGHT AND CONTROL SWITCHES NOT MORE THAN 4-FEET-0-INCHES ABOVE FINISHED FLOOR OR WORKING LEVEL.6. PROVIDE DOORS NOT LESS THAN 3-FEET-0-INCH WIDE BY 6-FEET -8-INCHES IN HIGH.7. PROVIDE FLOORS AND LANDINGS LOCATED AT A DOORWAYS NOT MORE THAN 1/2-INCH LOWER THAN THE TOP OF THE THRESHOLD.

PROVIDE THRESHOLDS WITH 1/4-INCH MAXIMUM VERTICAL EDGE AND WITH A CHANGE IN LEVEL NOT GREATER THAN 1:2.8. PROVIDE A CLEAR AND LEVEL AREA ON EACH SIDE OF EXIT DOORS WITH A LENGTH OF AT LEAST 60-INCHES IN THE DIRECTION OF THE

DOOR SWING AND AT LEAST 48-INCHES IN THE OPPOSITE DIRECTION, MEASURED AT RIGHT ANGLE TO DOOR IN ITS CLOSED POSITION.9. PROVIDE LEVER TYPE HARDWARE COMPLYING WITH ADA REQUIREMENTS.10. PROVIDE BOTTOM 10-INCHES OF DOORS, EXCEPT AUTOMATIC AND SLIDING DOORS, WITH A SMOOTH, UNINTERRUPTED SURFACE.11. PROVIDE EXIT DOORS TO SWING IN THE DIRECTION OF TRAVEL WHEN SERVING AN OCCUPANT LOAD OF MORE THAN 50 (UBC CHAPTER

10).12. ARRANGE EXIT DOORS TO OPERATE FROM THE INSIDE WITHOUT USE OF A KEY OR ANY SPECIAL KNOWLEDGE OR EFFORT. USE ONLY

SPECIAL LOCKING DEVICES OF AN APPROVED TYPE. PROVIDE EXIT DOOR CLOSERS ADJUSTED SO THAT THE DOOR TAKES AT LEAST 3SECONDS TO CLOSE FROM AN OPEN POSITION OF 70 DEGREES TO WITHIN 3-INCHES OF THE LATCH.

01 31 00 - PROJECT MANAGEMENT AND COORDINATION1. FORWARD COPIES OF EXECUTED PERMITS TO PROJECT MANAGER.2. SYMBOLS AND ABBREVIATIONS USED ON THE DRAWINGS ARE CONSTRUCTION STANDARD. REFER QUESTIONS REGARDING THEIR

DEFINITION TO ARCHITECT FOR CLARIFICATION.3. ALL DIMENSIONS ARE FROM FACE OF FINISH TO FACE OF FINISH, U.N.O.4. ARRANGE FOR EACH TRADE TO CHECK AND VERIFY ALL DIMENSIONS AND CONDITIONS AT JOB SITE RELATING TO THEIR WORK. NO

ALLOWANCE SHALL BE MADE FOR ANY EXTRA EXPENSE OR EXTENSION OF TIME DUE TO CONTRACTOR'S FAILURE OR NEGLIGENCE INCOMPLETELY EXAMINING THE JOB SITE AND CONDITIONS EFFECTING EXECUTION OF THE WORK.

5. CONTACT OWNER'S REPRESENTATIVE FOR RULES FOR USE OF EXISTING FACILITIES, DELIVERIES, REMOVALS, STORAGE, TEMPORARYFACILITIES AND CONTROLS, TEMPORARY UTILITIES AND SERVICES, CONSTRUCTION OPERATIONS, WORK PERFORMED OUTSIDEREGULAR BUSINESS HOURS, AND OTHER REQUIREMENTS AFFECTING USE OF THE SITE AND PROSECUTION OF THE WORK. IFOVERTIME WORK IS REQUIRED BY ANY TRADE, APPROVAL (INCLUDING COST APPROVAL) MUST BE OBTAINED FROM OWNER PRIOR TOEXECUTION OF THE OVERTIME WORK. THE GENERAL INTENT IS THAT ALL WORK EXCEPT FOR NOISE-GENERATING CONSTRUCTIONSHALL BE PERFORMED ON REGULAR TIME.

6. COORDINATE AND VERIFY SIZE, LOCATION AND CHARACTERISTICS OF OWNER SUPPLIED MATERIAL AND EQUIPMENT WITH WORK OFTHIS CONTRACT TO PROVIDE A NEAT WORKMANLIKE INSTALLATION OF ALL WORK THAT FITS AVAILABLE SPACE, PROVIDES THEFUNCTION OR USE INTENDED, AND PROVIDES ADEQUATE SERVICE ACCESS.

7. VERIFY AND COORDINATE LOCATION OF ALL ACCESS PANELS (IN PARTITIONS, FLOORS, OR CEILINGS). CONFIRM LOCATIONS WITHOWNER PRIOR TO INSTALLATION.

8. PROVIDE BLOCKING, BACKING, FRAMING HANGERS, OR OTHER SUPPORT FOR ALL FIXTURES, EQUIPMENT, CABINETRY, FURNISHINGS,AND OTHER HEAVY CONSTRUCTION.

01 32 00 - CONSTRUCTION PROGRESS DOCUMENTATION1. SUBMIT A DETAILED CONSTRUCTION SCHEDULE TO THE OWNER INDICATING SEQUENCE AND PHASING OF WORK FROM START TO

FINISH OF THE PROJECT.2. SUBMITTALS SCHEDULE: TABULATE THE FOLLOWING: SCHEDULED DATE FOR FIRST SUBMITTAL; SPECIFICATION SECTION NUMBER AND

TITLE; SUBMITTAL CATEGORY (ACTION OR INFORMATIONAL); NAME OF SUBCONTRACTOR; DESCRIPTION OF THE WORK COVERED;SCHEDULED DATE FOR OWNER'S FINAL RELEASE OR APPROVAL.

3. REPORTS: PROVIDE AS REQUIRED TO DOCUMENT EVENTS DAILY CONSTRUCTION REPORTS; MATERIAL LOCATION REPORTS; FIELDCONDITION REPORTS; SPECIAL REPORTS, AND WEEKLY PROGRESS PHOTOS.

4. GC TO PROVIDE A WEEKLY PROGRESS REPORT TO INCLUDE A TIMELINE SHOWING PERCENT COMPLETE.

01 40 00 - QUALITY REQUIREMENTS1. TESTING AND INSPECTING SERVICES ARE REQUIRED TO VERIFY COMPLIANCE WITH REQUIREMENTS SPECIFIED OR INDICATED. PROVIDE

SPECIAL INSPECTIONS BY INDEPENDENT TESTING AGENCY WHEN REQUIRED BY CODE AUTHORITIES. THESE SERVICES DO NOT RELIEVECONTRACTOR OF RESPONSIBILITY FOR COMPLIANCE WITH THE CONTRACT DOCUMENT REQUIREMENTS.

01 42 00 - REFERENCES1. ABBREVIATIONS AND ACRONYMS: WHERE ABBREVIATIONS AND ACRONYMS ARE USED IN CONTRACT DOCUMENTS, THEY SHALL MEAN

THE RECOGNIZED NAME OF THE ENTITIES INDICATED IN GALE RESEARCH'S "ENCYCLOPEDIA OF ASSOCIATIONS" OR IN COLUMBIABOOKS' "NATIONAL TRADE & PROFESSIONAL ASSOCIATIONS OF THE U.S," AND THE ABBREVIATION LIST INCLUDED WITH THE PROJECTDOCUMENTS.

01 50 00 - TEMPORARY FACILITIES AND CONTROLS1. REMOVE ALL RUBBISH AND WASTE MATERIALS FROM THE PREMISES ON AT LEAST A WEEKLY BASIS, AND PROVIDE LEGAL DISPOSAL.2. EXERCISE STRICT DUST CONTAINMENT CONTROL TO PREVENT DIRT OR DUST FROM LEAVING LIMITS OF CONSTRUCTION.3. UNLESS OTHERWISE REQUIRED BY THE CONTRACT DOCUMENTS, WATER, GAS, LIGHTING, POWER AND TELEPHONE CONDUITS AND

WIRES, SEWER LINES, STREETS, CURBS, DRIVEWAY APPROACHES, TREES, LANDSCAPING, BUILDINGS AND OTHER SURFACE ANDSUBSURFACE STRUCTURES AND LINES, OPENINGS, FINISHES, FURNISHINGS, EQUIPMENT, AND SIMILAR IMPROVEMENT ITEMS SHALL BEPROTECTED BY CONTRACTOR AND SHALL NOT BE DISTURBED, DISCONNECTED OR DAMAGED BY HIM DURING PROGRESS OF WORK.SHOULD CONTRACTOR IN PERFORMANCE OF WORK DISTURB, DISCONNECT OR DAMAGE ANY OF THE ABOVE ITEMS, REMOVE, REPAIR,OR REPLACE SUCH DISCONNECTED OR DAMAGED ITEMS WITH MATERIALS, CONSTRUCTION, AND IMPROVEMENTS MATCHING EXISTINGUNDAMAGED WORK AND RESTORE TO A CONDITION AS GOOD AS OR BETTER THAN EXISTED PRIOR TO SUCH DISTURBANCE,DISCONNECTION OR DAMAGE AT NO ADDITIONAL EXPENSE TO OWNER. PROVIDED TEMPORARY PROTECTION OF THE WORK UNTILREMOVAL OF TEMPORARY PROTECTION IS APPROVED BY ARCHITECT.

4. CONTRACTOR IS RESPONSIBLE FOR THE WORK AND PROPERTY OF OTHERS THAT IS IN CONTRACTOR'S CARE, CUSTODY, ANDCONTROL AT ALL TIMES DURING PROGRESS OF THE WORK AND UNTIL FINAL ACCEPTANCE. SECURE AND LOCK THE PREMISES WHENWORKMEN ARE NOT PRESENT.

5. CONTRACTOR IS RESPONSIBLE FOR LIFE SAFETY EQUIPMENT REQUIRED BY AUTHORITIES HAVING JURISDICTION.6. DURING THE ENTIRE PERIOD OF DEMOLITION AND CONSTRUCTION, EXISTING EXIT SIGNS, EXIT LIGHTING, FIRE PROTECTION DEVICES

AND ALARMS SHALL BE CONTINUOUSLY MAINTAINED.7. MAINTAIN REQUIRED EXITS AND EXIT EGRESS FREE FROM ALL OBSTRUCTIONS AND IMPEDIMENTS.8. MAINTAIN EXISTING UTILITIES AND SERVICES TO EXISTING FACILITIES INDICATED TO REMAIN, KEEP IN SERVICE, AND PROTECT AGAINST

DAMAGE DURING DEMOLITION OPERATIONS. GIVE MINIMUM 72 HOUR ADVANCE NOTICE TO OWNER'S REPRESENTATIVE IF SERVICESHUT-DOWN-DOWN IS NECESSARY.

9. EXISTING WATER, PERMANENT FIRE PROTECTION, ELECTRICAL POWER SERVICE AND LIGHTING, HEATING, AIR CONDITIONING, ANDTOILETS WITHIN THE VARIOUS AREAS OF WORK WILL BE MADE AVAILABLE TO CONTRACTOR WITHOUT ADDITIONAL METERING ANDWITHOUT PAYMENT OF USE CHARGES FOR SERVICES. PROVIDE AND PAY FOR ALL OTHER TEMPORARY UTILITIES AND UTILITYSERVICES, TEMPORARY SUPPORT FACILITIES AND SERVICES, TEMPORARY SECURITY AND PROTECTION FACILITIES NECESSARY FORTHE PROPER AND EXPEDITIOUS EXECUTION OF THE WORK.

10. KEEP ALL EXISTING FACILITIES AND SERVICES CLEAN AND IN GOOD WORKING CONDITION. CLEAN OR REPLACE CHANGEABLE FILTERMEDIA AND TURN OVER WITH NEW FILTER MEDIA AT COMPLETION OF WORK. CONTRACT DOCUMENTS.

11. COSTS FOR DELAYS BECAUSE OF NON-AVAILABILITY OF SPECIFIED ITEMS, WHEN SUCH DELAYS COULD HAVE BEEN AVOIDED BYCONTRACTOR, WILL BE BORNE BY THE CONTRACTOR.

01 60 00 - PRODUCT REQUIREMENTS1. MANUFACTURER'S NAME, TRADEMARK, LOGOS, ETC., SHALL NOT BE VISIBLE TO THE PUBLIC.2. NO SUBSTITUTIONS OF LISTED MATERIALS OR PRODUCTS SHALL BE PERMITTED WITHOUT FIRST SUBMITTING SPECIFICATIONS,

SAMPLES, AND COST IMPACT FOR OWNER'S APPROVAL.A. USE SUBSTITUTION REQUEST FORMS AVAILABLE FROM OWNER.B. AT THE TIME OF BID SUBMITTAL, THE CONTRACTOR SHALL ADVISE OWNER, IN WRITING OF ANY SPECIFIED MATERIAL OR

EQUIPMENT THAT IS EITHER UNAVAILABLE OR WILL CAUSE A DELAY IN THE COMPLETION OF CONSTRUCTION.C. PROPOSED REVISIONS SHALL BE SUBMITTED IN THE FORM OF A WRITTEN CHANGE ORDER TO BE APPROVED AND AUTHORIZED

BY OWNER PRIOR TO START OF PROPOSED WORK.D. NO SUBSTITUTIONS ALLOWED FOR PAINT, RESILIENT BASE, PLASTIC LAMINATES, SOLID SURFACES, CARPET, VINYL

COMPOSITION TILE, ACOUSTICAL CEILING TILE, AND UPHOLSTERY.3. EXISTING MANUFACTURED ITEMS NOT BEING REMOVED SHALL BE REFURBISHED AS REQUIRED, ANY LOOSE ITEMS TIGHTENED

(INCLUDING, BUT LIMITED TO, EXIT SIGNS, DOWN LIGHTS, SPEAKERS, MOLDINGS, ETC.), AND ANY MISSING PARTS REPLACED BY THECONTRACTOR TO ACHIEVE A COMPLETE FUNCTIONING INSTALLATION WITH A NEW APPEARANCE.

4. COMPATIBILITY OF OPTIONS: IF CONTRACTOR IS GIVEN OPTION OF SELECTING BETWEEN TWO OR MORE PRODUCTS FOR USE ONPROJECT, PRODUCT SELECTED SHALL BE COMPATIBLE WITH PRODUCTS PREVIOUSLY SELECTED, EVEN IF PREVIOUSLY SELECTEDPRODUCTS WERE ALSO OPTIONS.

5. RELIABILITY OF CALCULATIONS BY DATE SENSITIVE EQUIPMENT, SYSTEMS AND COMPONENTSA. DEFINITION: DATE SENSITIVE EQUIPMENT INCLUDES EQUIPMENT, SYSTEMS AND COMPONENTS THEREOF WHICH RELY ON OR

UTILIZE COMPUTERS, SUBSYSTEMS, HARDWARE, SOFTWARE, FIRMWARE, INCLUDING EMBEDDED CHIP SYSTEMS OR COMPONENTS, WHICH PROCESS, SEQUENCE, CALCULATE, UTILIZE, OR IN ANY FASHION ARE AFFECTED IN FUNCTION OR OPERATION BY DATE AND DATE RELATED OR TIME AND TIME RELATED DATA, INCLUDING THE PASSAGE OF TIME.

B. DATE SENSITIVE EQUIPMENT, SYSTEMS AND COMPONENTS THEREOF MUST INDIVIDUALLY AND IN COMBINATION PROPERLY FUNCTION AND CONTINUE TO CORRECTLY PROCESS, SEQUENCE AND UTILIZE DATE AND TIME RELATED DATA FOR ALL DATES AND TIMES, WHICH OCCUR DURING A REASONABLE LIFE EXPECTANCY FOR SAID EQUIPMENT, SYSTEMS AND COMPONENTS THEREOF.

C. CORRECTLY PROCESS, SEQUENCE, AND CALCULATE ALL DATE AND DATE RELATED DATA FOR ALL DATES PRIOR TO, THROUGH AND AFTER JANUARY 1, 2000, INCLUDING LEAP YEAR CALCULATIONS.

D. SOFTWARE PRODUCTS THAT PROCESS DATE OR DATE RELATED DATA SHALL RECOGNIZE, STORE AND TRANSMIT DATE DATA IN A FORMAT WHICH EXPLICITLY AND UNAMBIGUOUSLY SPECIFIES THE CORRECT CENTURY.

E. CONTRACTOR SHALL INCLUDE THIS REQUIREMENT IN ALL SUB-CONTRACTS AND EQUIPMENT ORDERS FOR THIS PROJECT.F. SUBMITTALS: PROVIDE CERTIFICATION FROM SUPPLIERS AND SUB-CONTRACTORS PROVIDING DATE SENSITIVE EQUIPMENT,

SYSTEMS, AND SOFTWARE THAT THE PROPOSED EQUIPMENT, COMPONENTS AND SYSTEMS COMPLY WITH THESE REQUIREMENTS.

6. COMPLETE ASSEMBLIES: PROVIDE PRODUCTS COMPLETE WITH ACCESSORIES, TRIM FINISH, FASTENERS, AND OTHER ITEMS NEEDEDFOR A COMPLETE INSTALLATION FOR THE INDICATED USE AND EFFECT.

7. PROVIDE STANDARD PRODUCTS IF AVAILABLE, AND UNLESS CUSTOM PRODUCTS OR NON-STANDARD OPTIONS ARE SPECIFIED,PROVIDE STANDARD PRODUCTS OF THE TYPES THAT HAVE BEEN PRODUCED AND USED SUCCESSFULLY IN SIMILAR SITUATIONS ONOTHER PROJECTS.

8. THE OWNER RESERVES THE RIGHT TO LIMIT SELECTION TO PRODUCTS WITH WARRANTIES NOT IN CONFLICT WITH REQUIREMENTS OFTHE CONTRACT DOCUMENTS.

9. WHERE PRODUCTS ARE ACCOMPANIED BY THE TERM "AS SELECTED", OWNER WILL MAKE SELECTION.10. WHERE PRODUCTS ARE ACCOMPANIED BY THE TERM "MATCH SAMPLE", SAMPLE IS OWNER'S.11. DESCRIPTIVE, PERFORMANCE, AND REFERENCE STANDARD REQUIREMENTS IN THE SPECIFICATIONS ESTABLISH "SALIENT

CHARACTERISTICS" OF PRODUCTS.12. VERIFY PRIOR TO BIDDING THAT ALL SPECIFIED ITEMS WILL BE AVAILABLE IN TIME FOR INSTALLATION TO ASSURE COMPLETION OF THE

PROJECT WITHIN THE TIME REQUIRED BY THE CONTRACT DOCUMENTS.13. COSTS FOR DELAYS BECAUSE OF NON-AVAILABILITY OF SPECIFIED ITEMS, WHEN SUCH DELAYS COULD HAVE BEEN AVOIDED BY

CONTRACTOR, WILL BE BORNE BY THE CONTRACTOR.

01 73 00 - EXECUTION1. CONSTRUCTION LAYOUT

A. DO NOT SCALE DRAWINGS, DIMENSIONS GOVERN. LARGE SCALE DETAILS GOVERN OVER SMALLER SCALE DETAILS.B. INFORM CLIENT WHEN CHALK LINE LAYOUT OF PARTITIONS IS COMPLETED SO THAT IT CAN BE VERIFIED. MAKE REQUIRED

CHANGES PRIOR TO START OF CONSTRUCTION.C. SUPPLY ALL NECESSARY INFORMATION ON REQUIRED CUTOUTS FOR PLUMBING FIXTURES TO MILLWORK CONTRACTOR.D. DOOR OPENINGS IN GYPSUM BOARD PARTITIONS NOT DIMENSIONED ARE TO BE LOCATED IN CENTER OF ROOM OR 4" FROM

ADJOINING PARTITION AS SHOWN.2. COMPLY WITH MANUFACTURER'S WRITTEN INSTRUCTIONS AND RECOMMENDATIONS FOR INSTALLING PRODUCTS IN APPLICATIONS

INDICATED.3. ENSURE THAT INSTALLATION CONFORMS TO BUILDING CODE REQUIREMENTS. THE MATERIALS SPECIFIED ARE INTENDED TO MEET

CODE REQUIREMENTS. IMMEDIATELY NOTIFY ARCHITECT OF ALL DISCREPANCIES BETWEEN THE CONSTRUCTION DOCUMENTS ANDCODE REQUIREMENTS. DO NOT PROCEED WITH INSTALLATION UNTIL INSTRUCTIONS RESOLVING DISCREPANCIES HAVE BEENRECEIVED.

01 73 30 - CORRECTION OF DEFECTIVE WORK1. PATCH, REPAIR, REPLACE, AND/OR REFINISH EXISTING CONSTRUCTION AS NECESSARY TO REFURBISH DAMAGED AND

NONCONFORMING AREA OF WORK.

01 74 00 - CLEANING AND WASTE MANAGEMENT1. CLEAN PREMISES WITHIN CONSTRUCTION LIMITS AND ALONG ACCESS ROUTES DAILY, INCLUDING COMMON AREAS. COORDINATE

PROGRESS CLEANING FOR JOINT-USE AREAS WHERE MORE THAN ONE INSTALLER HAS WORKED. ENFORCE REQUIREMENTS STRICTLY.DISPOSE OF MATERIALS LAWFULLY.

2. KEEP INSTALLED WORK CLEAN.3. CONCEALED SPACES: REMOVE DEBRIS FROM CONCEALED SPACES BEFORE ENCLOSING THE SPACE.

01 75 00 - STARTING AND ADJUSTING1. START EQUIPMENT AND OPERATING COMPONENTS TO CONFIRM PROPER OPERATION. REMOVE MALFUNCTIONING UNITS, REPLACE

WITH NEW UNITS, & RETEST.2. ADJUST OPERATING COMPONENTS FOR PROPER OPERATION WITHOUT BINDING, VIBRATING, OR PRODUCING EXCESSIVE NOISE.

ADJUST EQUIPMENT FOR PROPER OPERATION.3. PROTECT INSTALLED CONSTRUCTION.

01 77 00 - CLOSEOUT PROCEDURES1. CONTRACT CLOSE-OUT SHALL OCCUR ONLY AFTER CLIENT HAS PREPARED THE CERTIFICATE OF SUBSTANTIAL COMPLETION, OR

CONFIRMED PROCEDURES WITH LOCAL AUTHORITATIVE JURISDICTION, AND PUNCH LIST, AND PUNCH LIST ITEMS HAVE BEENCORRECTED. THE CONTRACTOR SHALL SUBMIT MAINTENANCE AND WARRANTY MANUALS, RELEASE OF LIENS, AND RECORDDRAWINGS TO CLIENT WITH HIS FINAL APPLICATION FOR PAYMENT. CLIENT SHALL PREPARE ANY NECESSARY CHANGE ORDERSREQUIRED TO FINALIZE THE COST OF THE PROJECT BASED ON THE CONTRACTORS FINAL SUBMITTALS.

2. "EXISTING TO REMAIN", "EXISTING TO BE RELOCATED", AND/OR NEW ITEMS INSTALLED BY THE CONTRACTOR, IN ADDITION TO BEINGAMPLY PROTECTED THROUGHOUT THE PERIOD OF CONSTRUCTION, SHALL BE THOROUGHLY CLEANED TO THE SATISFACTION OFOWNER PRIOR TO BEING TURNED OVER TO THE OWNER.

3. BEFORE ACCEPTANCE BY THE OWNER, THE COMPLETED CONSTRUCTION SHALL BE CLEANED, LABELS REMOVED, AND ALL OTHERTOUCH UP COMPLETED.

4. GC TO PROVIDE AS-BUILT CAD DRAWINGS UPON COMPLETION OF WORK.

02 41 19 - SELECTIVE DEMOLITION1. DEMOLISH AND REMOVE EXISTING CONSTRUCTION ONLY TO THE EXTENT REQUIRED BY NEW CONSTRUCTION AND AS INDICATED. USE

METHODS REQUIRED TO COMPLETE THE WORK WITHIN THE LIMITATIONS OF GOVERNING REGULATIONS AND IN COMPLIANCE WITH THELANDLORD'S RULES AND REGULATIONS.

2. COORDINATE WITH THE OWNER TO ESTABLISH A LIST OF ITEMS THAT WILL REMAIN THE OWNER'S PROPERTY, ALL OTHER DEMOLISHEDMATERIALS SHALL BECOME THE CONTRACTOR'S PROPERTY AND SHALL BE REMOVED FROM THE SITE WITH FURTHER DISPOSITION ATTHE CONTRACTOR'S OPTION. ITEMS TO REMAIN THE OWNER'S PROPERTY SHALL BE CAREFULLY REMOVED AND PROTECTED, ANDSTORED AT A LOCATION AS DIRECTED BY THE OWNER.

3. EXCEPT FOR ITEMS OR MATERIALS INDICATED TO BE RECYCLED, REUSED, SALVAGED, REINSTALLED, OR OTHERWISE INDICATED TOREMAIN OWNER'S PROPERTY, REMOVE DEMOLISHED MATERIALS FROM PROJECT SITE AND LEGALLY DISPOSE OF THEM IN AN EPA-APPROVED LANDFILL.

4. REVIEW AND FINALIZE SELECTIVE DEMOLITION SCOPE AND SCHEDULE WITH ARCHITECT.5. REMOVE TO SOURCE, PIPES, VENTS, DRAINS, ELECTRICAL WIRING AND CONDUIT, FLOOR BOXES, AND OTHER UTILITIES NOT

SCHEDULED TO BE REUSED. REFER TO MEP DRAWINGS FOR SCOPE OF WORK.6. REMOVE, CLEAN AND PROTECT ITEMS SCHEDULED TO BE RE-INSTALLED.7. PROTECTIONS: PROVIDE TEMPORARY BARRICADES AND OTHER FORMS OF PROTECTION TO PROTECT OWNER'S PERSONNEL AND

GENERAL PUBLIC FROM INJURY DUE TO SELECTIVE DEMOLITION WORK.A. PROVIDE PROTECTIVE MEASURES AS REQUIRED TO PROVIDE FREE AND SAFE PASSAGE OF OWNER'S PERSONNEL AND

GENERAL PUBLIC TO OCCUPIED PORTIONS OF THE BUILDING.B. ERECT TEMPORARY COVERED PASSAGEWAYS WHERE OVERHEAD WORK IS REQUIRED.C. PROVIDE SHORING, BRACING, OR SUPPORT TO PREVENT MOVEMENT, SETTLEMENT, OR COLLAPSE OF STRUCTURE OR

ELEMENT TO BE DEMOLISHED AND ADJACENT FACILITIES OR WORK TO REMAIN.D. PROTECT FROM DAMAGE EXISTING FINISH WORK THAT IS TO REMAIN IN PLACE BECOMES EXPOSED DURING DEMOLITION

OPERATIONS.E. PROTECT FLOORS WITH SUITABLE COVERINGS WHEN NECESSARY.

8. PRIOR TO COMMENCEMENT OF DEMOLITION WORK, INSPECT AREAS IN WHICH WORK WILL BE PERFORMED. PHOTOGRAPH EXISTINGCONDITIONS WHICH COULD BE MISCONSTRUED AS DAMAGE RESULTING FROM DEMOLITION WORK; FILE WITH ARCHITECT PRIOR TOSTARTING WORK.

03 54 16 - HYDRAULIC CEMENT UNDERLAYMENT1. USE SELF-LEVELING UNDERLAYMENT FOR INTERIOR FINISH FLOORING AT LOCATIONS INDICATED, AND TO ACHIEVE FLATNESS WHERE

STRUCTURAL SLAB DOES NOT COMPLY WITH SPECIFIED FLATNESS REQUIREMENTS.2. UNDERLAYMENT: CEMENT-BASED, POLYMER-MODIFIED, SELF-LEVELING PRODUCT THAT CAN BE APPLIED IN UNIFORM THICKNESSES

FROM 1/8 INCH (3 MM) AND THAT CAN BE FEATHERED AT EDGES TO MATCH ADJACENT FLOOR ELEVATIONS.A. CEMENT BINDER: ASTM C 150, PORTLAND CEMENT, OR HYDRAULIC OR BLENDED HYDRAULIC CEMENT AS DEFINED BY ASTM C

219.B. COMPRESSIVE STRENGTH: NOT LESS THAN 4100 PSI (28 MPA) AT 28 DAYS WHEN TESTED ACCORDING TO ASTM C 109/C 109M.C. PRODUCTS:

a. K-15 SELF-LEVELING UNDERLAYMENT CONCRETE; ARDEX, INC.b. SELF-LEVELING UNDERLAYMENT; W. R. BONSAL COMPANY.c. 300 PREMIUM UNDERLAYMENT; BURKE GROUP, LLC (THE).d. LEVELEX UNDERLAYMENT; L&M CONSTRUCTION CHEMICALS, INC.e. LEVEL-RIGHT; MAXXON CORPORATION.

3. AGGREGATE: WELL-GRADED, WASHED GRAVEL, 1/8 TO 1/4 INCH (3 TO 6 MM), OR COARSE SAND AS RECOMMENDED BY UNDERLAYMENTMANUFACTURER.A. PROVIDE AGGREGATE WHEN RECOMMENDED IN WRITING BY UNDERLAYMENT MANUFACTURER FOR UNDERLAYMENT

THICKNESS REQUIRED.4. WATER: POTABLE AND AT A TEMPERATURE OF NOT MORE THAN 70 DEG F (21 DEG C).5. REINFORCEMENT: FOR UNDERLAYMENT APPLIED TO WOOD SUBSTRATES, PROVIDE GALVANIZED METAL LATH OR OTHER CORROSION-

RESISTANT REINFORCEMENT RECOMMENDED IN WRITING BY UNDERLAYMENT MANUFACTURER.6. PRIMER: PRODUCT OF UNDERLAYMENT MANUFACTURER RECOMMENDED IN WRITING FOR SUBSTRATE, CONDITIONS, AND APPLICATION

INDICATED.

05 00 00 - METALS - COMMON WORK RESULTS1. DESIGN, ENGINEER, FABRICATE, AND INSTALL METAL FABRICATIONS TO WITHSTAND THE FOLLOWING STRUCTURAL LOADS WITHOUT

EXCEEDING THE ALLOWABLE DESIGN WORKING STRESS OF THE MATERIALS INVOLVED, INCLUDING ANCHORS AND CONNECTIONS.APPLY EACH LOAD TO PRODUCE .THE MAXIMUM STRESS IN EACH RESPECTIVE COMPONENT OF EACH METAL FABRICATION.

05 50 00 - METAL FABRICATIONS1. METAL SURFACES, GENERAL: PROVIDE MATERIALS WITH SMOOTH, FLAT SURFACES WITHOUT BLEMISHES.2. STEEL PLATES, SHAPES, AND BARS: ASTM A 36/A 36M.3. STAINLESS-STEEL BARS AND SHAPES: ASTM A 276, TYPE 304.4. STEEL TUBING: COLD-FORMED STEEL TUBING COMPLYING WITH ASTM A 500.5. STEEL PIPE: ASTM A 53, STANDARD WEIGHT (SCHEDULE 40), UNLESS ANOTHER WEIGHT IS INDICATED OR REQUIRED BY STRUCTURAL

LOADS.6. ALUMINUM: EXTRUSIONS: ASTM B 221 (ASTM B 221M), ALLOY 6063-T6.7. SHEAR AND PUNCH METALS CLEANLY AND ACCURATELY. REMOVE BURRS.8. WELD CORNERS AND SEAMS CONTINUOUSLY. USE MATERIALS AND METHODS THAT MINIMIZE DISTORTION AND DEVELOP STRENGTH

AND CORROSION RESISTANCE OF BASE METALS. OBTAIN FUSION WITHOUT UNDERCUT OR OVERLAP. REMOVE WELDING FLUXIMMEDIATELY. FINISH EXPOSED WELDS SMOOTH AND BLENDED.

9. MISCELLANEOUS FRAMING AND SUPPORTS: FABRICATE STEEL FRAMING AND SUPPORTS THAT ARE NOT A PART OF STRUCTURAL-STEEL FRAMEWORK AS NECESSARY TO COMPLETE THE WORK. CUT, DRILL, AND TAP UNITS TO RECEIVE HARDWARE, HANGERS, ANDSIMILAR ITEMS.

10. FINISH METAL FABRICATIONS AFTER ASSEMBLY. COMPLY WITH NAAMM "METAL FINISHES MANUAL FOR ARCHITECTURAL AND METALPRODUCTS" FOR RECOMMENDATIONS FOR APPLYING AND DESIGNATING FINISHES. SHOP PRIME FERROUS-METAL ITEMS NOTINDICATED TO BE GALVANIZED.

06 00 00 - WOOD, PLASTICS AND COMPOSITES - COMMON WORK RESULTS1. ADHERE WOOD VENEER AND PLASTIC LAMINATE TO SUBSTRATE USING ADHESIVES THAT COMPLY WITH LOW-VOC (VOLATILE ORGANIC

COMPOUND) REQUIREMENTS.2. USE COMPOSITE WOOD PRODUCTS THAT CONTAIN NO UREA FORMALDEHYDE3. PROVIDE THE FOLLOWING SUBMITTALS:

A. GRADE: CUSTOM.B. FINISH: AWI SYSTEM TR-4, CONVERSION VARNISH; WI SYSTEM #2, CONVERSION VARNISH.C. STAINING, EFFECT, SHEEN: TO MATCH APPROVED SAMPLES.

4. INSTALL WOODWORK PLUMB, LEVEL, TRUE AND STRAIGHT WITH NO DISTORTIONS. SHIM AS REQUIRED USING CONCEALED SHIMS.INSTALL TO A TOLERANCE OF 1/8-INCH IN 8-FEET-0-INCHES FOR PLUMB AND LEVEL (INCLUDING TOPS); AND WITH NO VARIATIONS INFLUSHNESS OF ADJOINING SURFACES. COMPLY WITH INSTALLATION REQUIREMENTS ESTABLISHED BY REFERENCED STANDARDS.

5. FINISH HARDWARE ITEMSA. DRAWER GLIDES: NO. 8400 BOX/FILE DRAWER SLIDE – FULL EXTENSION BY KNAPE & VOGT MFG. CO OR APPROVED EQUALB. SHELF STANDARDS AND SUPPORTS (RECESSED SHELVES IN ENCLOSED CABINETS): NO 255 STANDARD AND NO. 256 SUPPORTS

BY KNAPE & VOGT MFG. CO., NATURAL ALUMINUM FINISH OR APPROVED EQUALC. DOORS: 1 PAIR HEAVY-DUTY INSTITUTIONAL HINGES, STANLEY HT1592, US 28, SATIN ALUMINUM FINISH

a. 1 CATCH, STANLEY 41 SERIESb. 1 PULL, HAFELE 116.09.288 MATTE ALUMINUM FINISH

D. DRAWER PULLS: HAFELE 116.09.288 MATTE ALUMINUM FINISHE. DRAWER LOCKS: SCHLAGE CL 2000 CABINET DRAWER LOCK, US26D COMPLETE WITH STRIKE PLATE

6. DOOR LOCKS: SCHLAGE CL1000 CABINET DOOR LOCK, US26D, COMPLETE WITH STRIKE PLATE. PROVIDE ONE ELBOW CATCH PER PAIRDOORS. MASTER KEY ALL LOCKS AND PROVIDE KEY SCHEDULE TO TENANTA. SILENCERS: NEOPRENE TYPE WITH SELF-ADHESIVE AT ALL CABINET DOORS

03 30 00 - CAST IN PLACE CONCRETE1. CONCRETE MATERIALS:

A. CEMENT: ASTM C150, TYPE I - NORMAL.B. FINE AND COURSE AGGREGATES: ASTM C33.C. WATER: CLEAN AND NOT DETRIMENTAL TO CONCRETE.D. FLY ASH: ASTM C618, TYPE F.

2. ADMIXTURESA. AIR ENTRAINMENT: ASTM C260; CERTIFIED BY MANUFACTURER TO BE COMPATIBLE WITH OTHER ADMIXTURES.

1. AVAILABLE PRODUCTS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PRODUCTS THAT MAY BEINCORPORATED IN THE WORK INCLUDE, BUT ARE NOT LIMITED TO, THE FOLLOWING:a. HOLNAM, INC., 1-313-663-1532 – RECOVERABLE MATERIALS AVAILABLE.b. AIR-TITE, CORMIX CONSTRUCTION CHEMICALS.c. AIR-MIX OR PERMA-AIR, EUCLID CHEMICAL CO.d. DAREX AEA OR DARAVAIR, W. R. GRACE & COMPANY.e. MB-VR OR MICRO-AIR, MASTER BUILDERS, INC.f. SEALTIGHT AEA, W. R. MEADOWS, INC.g. SIKA AER, SIKA CORP.

A. WATER-REDUCING ADMIXTURE: ASTM C494, TYPE A.1. AVAILABLE PRODUCTS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PRODUCTS THAT MAY BE

INCORPORATED IN THE WORK INCLUDE, BUT ARE NOT LIMITED TO, THE FOLLOWING:a. HOLNAM, INC., 1-313-663-1532 – RECOVERABLE MATERIALS AVAILABLE.b. CHEMTARD, CHEMMASTERS CORP.c. PSI N, CORMIX CONSTRUCTION CHEMICALSd. EUCON WR-75, EUCLID CHEMICAL CO.e. WRDA, W. R. GRACE & COMPANYf. POZZOLITH NORMAL OR POLYHEED, MASTER BUILDERS, INC.g. METCO, W. R. METALCRETE INDUSTRIESh. PROKRETE-N, PROKETE INDUSTRIESi. PLASTOCRETE 161, SIKA CORP.

3. CURE & SEALA. CURE AND SEAL COMPOUND CONFORMING TO ASTM C-309, MANUFACTURERS AND PRODUCTS MEETING THE ABOVE

REQUIREMENT AS FOLLOWS:1. SONNEBORN – ‘KURE-N-SEAL”.2. SYMONS – “RESI-CHEM” CLEAR CURE.

4. ACCESSORIESA. BONDING AGENT: LATEX EMULSION; MANUFACTURED BY SONNEBORNE BUILDING PRODUCTS OR APPROVED EQUAL.B. NON-SHRINK GROUT: PREMIXED COMPOUND CONSISTING OF NON-METALLIC AGGREGATE, CEMENT, WATER REDUCING

AND PLASTICIZING AGENTS; CAPABLE OF DEVELOPING MINIMUM COMPRESSIVE STRENGTH OF 2,400 PSI IN 48 HOURS AND 7,000 PSI IN 28 DAYS; EMBECO 885 MANUFACTURED BY MASTER BUILDERS OR APPROVED EQUAL.

5. JOINT DEVICES AND FILLER MATERIALSA. CONSTRUCTION JOINT DEVICES FOR 4”AND 6” THICK SLABS: INTEGRAL GALVANIZED STEEL, FORMED TO TONGUE AND

GROOVE PROFILE, KNOCKOUT HOLES SPACED AT 6 INCHES, RIBBED STEEL SPIKES WITH TONGUE TO FIT TOP SCREED EDGE; MANUFACTURED BY HECKMAN BUILDING PRODUCTS OR APPROVED EQUAL.

B. CONSTRUCTION JOINT DEVICES FOR 8”-10” THICK SLABS: DIAMOND PLATE DOWELS WITH SLEEVES THAT PROVIDE VERTICAL LOAD TRANSFER WHILE ALLOWING BOTH PARALLEL AND PERPENDICULAR MOVEMENT AT THE JOINT. SEE DRAWINGS FOR SIZE AND SPACING.

6. CONCRETE MIXA. MIX AND DELIVER CONCRETE IN ACCORDANCE WITH ASTM C94, ALTERNATIVE NO. 3.B. SELECT PROPORTIONS FOR NORMAL WEIGHT CONCRETE IN ACCORDANCE WITH ACI 301, METHOD C. PROVIDE CONCRETE TO THE FOLLOWING CRITERIA:

D. USE ACCELERATING ADMIXTURES IN COLD WEATHER ONLY WHEN APPROVED BY ENGINEER. USE OF ADMIXTURES WILL NOT RELAX COLD WEATHER PLACEMENT REQUIREMENTS.

E. USE CALCIUM CHLORIDE ONLY WHEN APPROVED BY ENGINEER.F. USE SET RETARDING ADMIXTURES DURING HOT WEATHER ONLY WHEN APPROVED BY ENGINEER.G. ADD AIR ENTRAINING AGENT TO NORMAL WEIGHT CONCRETE MIX FOR WORK EXPOSED TO EXTERIOR.H. LIMIT USE OF FLYASH TO NOT EXCEED 25 PERCENT OF CEMENT CONTENT BY WEIGHT.

ITEM OR STRUCTURE

28 DAY (COMPRESSIVE

STRENGTH)

MAX. SLUMP

(INCHES)

AIR CONTENT

(%)

WAT/CEM RATIO

(BY WT.)

MAX. SIZEAGGREGATE

INCHES

Exterior slabs

Piers, Footings and all concrete below grade unless noted otherwise.

Interior slabExterior walls 4,000

3,000

4,000

4,000 2-4

3-5

2-4

2-4

5-7

0-1

5-7

5-7

0.45

0.50

0.45

0.45

1

1

1

1

SHEET

SHEET TITLE

ISSUE DATE

DRAWN BY

CHECKED BYAPPROVED BY

PROJECT NO.

REVISION

PROFESSIONAL OF RECORD:NOTIC

E: THIS

ARCHIT

ECTURAL A

ND E

NGIN

EERIN

G D

RAW

ING IS G

IVEN IN C

ONFID

ENCE A

ND S

HALL B

E U

SED O

NLY P

URSUANT T

O T

HE A

GREEMENT W

ITH T

HE A

RCHIT

ECT. NO O

THER U

SE, DIS

SEMIN

ATIO

N, OR D

UPLIC

ATIO

N M

AY B

E M

ADE W

ITHOUT P

RIO

R W

RIT

TEN

CONSENT O

F T

HE A

RCHIT

ECT. ALL C

OMMON L

AW

RIG

HTS O

F C

OPYRIG

HT A

ND O

THERW

ISE A

RE H

EREBY S

PECIF

ICALLY R

ESERVED.

CLIENT

2221 Schrock RoadColumbus, Ohio 43229-1547p 614.898.7100f 614.898.7570www.msconsultants.com

PROJECT

10/4

/202

1 4:

48:3

9 PM

SPECIFICATIONS

Q001

JPJ

CHARLES M. BUSCH - RA No. ARC.00403518EXP. DATE: 10/31/2021

10/04/2021

CLR/CMB

10/04/2021

62-40487-06

HCA HEALTH ONE, LLC4500 E 9TH AVESTE 160DENVER, CO 80220

QUESTDIAGNOSTICS

# DATE DESCRIPTION

06 10 00 - ROUGH CARPENTRY1. PROVIDE WOOD FOR SUPPORT OR ATTACHMENT OF OTHER WORK. PROVIDE LUMBER SIZES INDICATED, WORKED INTO SHAPES

SHOWN.2. MOISTURE CONTENT: 19 PERCENT MAXIMUM FOR LUMBER ITEMS, INCLUDING ITEMS TO RECEIVE WOOD PRESERVATIVE TREATMENT

OR FIRE RETARDANT TREATMENT.3. GRADE: STANDARD GRADE LIGHT FRAMING SIZE LUMBER OF ANY SPECIES OR BOARD SIZE LUMBER AS REQUIRED. NO. 3 COMMON OR

STANDARD GRADE BOARDS PER SPIB, WCLIB OR WWPA RULES APPLICABLE TO AGENCY UNDER WHICH LUMBER IS GRADED.4. PLYWOOD BACKING PANELS: FOR MOUNTING ELECTRICAL OR TELEPHONE EQUIPMENT, PROVIDE FIRE-RETARDANT TREATED

PLYWOOD PANELS WITH GRADE DESIGNATION, APA-B-C PLUGGED INTERIOR WITH EXTERIOR GLUE, IN THICKNESS NOT LESS THAN 3/4"(19MM)

5. FIRE-RETARDANT TREATED LUMBER AND PLYWOOD BY PRESSURE PROCESS: PRODUCTS WITH A FLAME SPREAD INDEX OF 25 OR LESSWHEN TESTED ACCORDING TO ASTM E 84. PROVIDE FOR ALL NAILERS, BLOCKING, PLYWOOD AND SIMILAR MEMBERS WHICH AREPERMANENTLY INSTALLED WITHIN THE INTERIOR PORTION OF THE BUILDING.

06 40 00 - ARCHITECTURAL WOODWORK1. PROVIDE OWNER WITH ELECTRONIC COPY OF ALL ARCHITECTURAL WOODWORK SHOP DRAWINGS PRIOR TO FABRICATION.2. QUALITY STANDARDS: COMPLY WITH ONE OF THE FOLLOWING:

A. AWI'S "ARCHITECTURAL WOODWORK QUALITY STANDARDS" FOR GRADES OF INTERIOR ARCHITECTURAL WOODWORK, CONSTRUCTION, FINISHES, AND OTHER REQUIREMENTS. PROVIDE AWI CERTIFICATION LABELS OR COMPLIANCE CERTIFICATE INDICATING THAT WOODWORK COMPLIES WITH REQUIREMENTS OF GRADES SPECIFIED.

B. WI (FORMERLY WIC) "MANUAL OF MILLWORK" FOR GRADES OF INTERIOR ARCHITECTURAL WOODWORK, CONSTRUCTION, FINISHES, AND OTHER REQUIREMENTS. PROVIDE WIC-CERTIFIED COMPLIANCE CERTIFICATE INDICATING THAT WOODWORK COMPLIES WITH REQUIREMENTS OF GRADES SPECIFIED. PROVIDE WIC-CERTIFIED COMPLIANCE CERTIFICATE FOR INSTALLATION.

3. PROVIDE MATERIALS THAT COMPLY WITH REQUIREMENTS OF THE REFERENCED PRODUCT STANDARDS FOR GRADE INDICATED.4. HARDBOARD: ANSI/AHA A135.4.5. MEDIUM DENSITY FIBERBOARD (MDF) or PLYWOOD: ANSI A208.2; FORMALDEHYDE FREE.6. PARTICLEBOARD: NOT ALLOWED.7. SOFTWOOD PLYWOOD: PS 1.8. FORMALDEHYDE EMISSION LEVELS: PROVIDE FORMALDEHYDE FREE MATERIALS. REFERENCE SECTION 018113 FOR LEED

REQUIREMENTS.9. FABRICATION: COMPLY WITH DETAILS AND CONSTRUCTION TYPES INDICATED.10. CABINET HARDWARE AND ACCESSORY MATERIALS: AS INDICATED ON DRAWINGS AND SCHEDULES.11. EDGING: HPL UNLESS OTHERWISE INDICATED PER AWI12. FACTORY FINISHING OF INTERIOR ARCHITECTURAL WOODWORK

A. AWI SECTION 1500, UNLESS OTHERWISE INDICATED.B. WI SECTION 1, "GENERAL INFORMATION - TECHNICAL BULLETIN", REQUIREMENTS FOR "FACTORY FINISHING OF MILLWORK"C. GRADE: PREMIUM.D. FINISH: AWI SYSTEM TR-4, CONVERSION VARNISH; WI SYSTEM #2, CONVERSION VARNISH.E. STAINING, EFFECT, SHEEN: TO MATCH APPROVED SAMPLES.

13. INSTALL WOODWORK PLUMB, LEVEL, TRUE AND STRAIGHT WITH NO DISTORTIONS. SHIM AS REQUIRED USING CONCEALED SHIMS.INSTALL TO A TOLERANCE OF 1/8-INCH IN 8-FEET-0-INCHES FOR PLUMB AND LEVEL (INCLUDING TOPS); AND WITH NO VARIATIONS INFLUSHNESS OF ADJOINING SURFACES. COMPLY WITH INSTALLATION REQUIREMENTS ESTABLISHED BY REFERENCED STANDARDS.

14. FINISH HARDWARE ITEMS DRAWER GLIDES: NO. 8400 BOX/FILE DRAWER SLIDE – FULL EXTENSION BY KNAPE & VOGT MFG. CO ORAPPROVED EQUALA. SHELF STANDARDS AND SUPPORTS (RECESSED SHELVES IN ENCLOSED CABINETS): NO 255 STANDARD AND NO. 256 SUPPORTS

BY KNAPE & VOGT MFG. CO., NATURAL ALUMINUM FINISH OR APPROVED EQUALB. DOORS:

a. CONCEALED HINGES: CONCEALED, SELF-CLOSING TYPE HINGES OF TYPE REQUIRED BY DOOR CONSTRUCTION ANDSTILE APPLICATIONS. THE SIZE AND NUMBER OF HINGES REQUIRED PER LEAF SHALL BE DETERMINED BY DOOR SIZEAND WEIGHT. HINGES SHALL COMPLY WITH THE ANSI/BHMA GRADE 1 REQUIREMENTS. FINISH: NICKEL CHROME ORSTAINLESS STEEL. MANUFACTURERS: HAFELE, GRASS OR BLUM.

b. 1 CATCH, STANLEY 41 SERIESc. 1 PULL, HAFELE 116.09.288 POLISHED CHROME FINISH

C. DRAWER PULLS: HAFELE 116.09.288 POLISHED CHROME FINISHD. DRAWER LOCKS: SCHLAGE CL 2000 CABINET DRAWER LOCK, US26D COMPLETE WITH STRIKE PLATEE. DOOR LOCKS: SCHLAGE CL1000 CABINET DOOR LOCK, US26D, COMPLETE WITH STRIKE PLATE. PROVIDE ONE ELBOW CATCH

PER PAIR DOORS.

07 21 19 - THERMAL INSULATION1. INSULATING MATERIALS:

A. BASIS OF DESIGN: PROVIDE THE FOLLOWING MATERIAL AND MANUFACTURER:1. "HEATLOK SOY 200" BY DEMILEC (USA) LLC, ARLINGTON, TX

B. SPRAYED FOAM INSULATION: POLYURETHANE CLOSED-CELL INSULATION; CONFORMING TO THE FOLLOWING:1. DENSITY, CORE; LBS/FT3: ASTM D-1622 @ 74 DEG F 1.70-1.90 TO 2.22. COMPRESSIVE STRENGTH: ASTM D-1621 @ 74 DEG F PARALLEL TO RISE, MINIMUM, PSI 12-193. MOISTURE VAPOR TRANSMISSION: MAXIMUM 0.79 PERMS AT 1.5 INCH THICKNESS, TESTED TO ASTM E964. AGED THERMAL RESISTANCE, 180D DAYS @ 23 DEG C (R-VALUE) ASTM C-177, R-7.4 @ 1 INCH5. FLAME SPREAD AND SMOKE DEVELOPED RATING: ASTM E84; CLASS 1, <20/<400

2. AUXILIARY INSULATING MATERIALSA. INTUMESCENT THERMAL BARRIER:

1. "BLAZE LOK TB" BY DEMILEC (USA) LLC, ARLINGTON, TX3. INSTALLATION:

A. COMPLY WITH MANUFACTURER'S INSTRUCTIONS FOR PARTICULAR CONDITIONS OF INSTALLATION IN EACH CASE. IF PRINTED INSTRUCTIONS ARE NOT AVAILABLE OR DO NOT APPLY TO PROJECT CONDITIONS, CONSULT THE MANUFACTURER'S TECHNICAL REPRESENTATIVE FOR SPECIFIC RECOMMENDATIONS BEFORE PROCEEDING WITH THE WORK.

B. APPLY FOAM INSULATION AT NOT MORE THAN TWO INCHES IN A SINGLE PASS AND ALLOW ADEQUATE TIME FOR THE HEAT WITHIN THE FOAM TO ESCAPE. IN APPLICATIONS REQUIRING MULTIPLE PASSES THE TIME REQUIRED BETWEEN THE PASSES SHALL BE EXTENDED TO ALLOW THE HEAT TO ESCAPE.1. APPLY INSULATION IN THICKNESS AS REQUIRED TO PRODUCE AN "R" VALUE OF (13).

C. APPLY THERMAL BARRIER IN ACCORDANCE WITH MANUFACTURER'S AND UL REQUIREMENTS.

07 81 05 - PATCHING DAMAGED FIREPROOFING1. PROVIDE MATERIALS AND CONSTRUCTION THAT ARE IDENTICAL TO THOSE TESTED BY UNDERWRITER'S LABORATORY, INC., FOR FIRE

RATED ASSEMBLY DESIGN NUMBERS INDICATED.2. DO NOT REMOVE ANY SPRAYED-ON FIRE RESISTIVE MATERIAL WITHOUT PRIOR APPROVAL. RE-COAT FIRE RESISTIVE MATERIALS

DAMAGED BY OTHER TRADES AND SURFACES WHERE FIRE RESISTIVE MATERIAL HAS BEEN REMOVED FOR INSTALLATION OF RELATEDWORK; COST OF REPAIRS TO BE BORNE BY RESPECTIVE TRADES.

3. SPRAYED FIRE RESISTIVE MATERIAL: CEMENTITIOUS SPRAYED FIRE RESISTIVE MATERIAL CONSISTING OF FACTORY MIXED, DRYFORMULATION OF GYPSUM OR PORTLAND CEMENT BINDERS AND LIGHTWEIGHT MINERAL OR SYNTHETIC AGGREGATES MIXED WITHWATER AT PROJECT SITE TO FORM A SLURRY OR MORTAR FOR CONVEYANCE AND APPLICATION AND AS REQUIRED FOR THE ULDESIGNS INDICATED.A. CONCEALED APPLICATION: MATERIALS APPLIED TO SURFACES THAT ARE CONCEALED FROM VIEW BEHIND OTHER

CONSTRUCTION WHEN THE WORK IS COMPLETED, INTENDED TO BE CONCEALED BY TENANT IMPROVEMENTS, AND WHICH HAVE NOT BEEN DEFINED AS EXPOSED.

4. BASIS OF DESIGN PRODUCTS: W. R. GRACE - "MONOKOTE TYPE MK-6" FULLY CONCEALED; "RETRO-GUARD" REPAIRS.5. EXPOSED INTERIOR APPLICATION: MATERIALS ARE THOSE APPLIED TO SURFACES THAT ARE EXPOSED TO VIEW WHEN THE WORK IS

COMPLETED, THAT ARE IN ELEVATOR SHAFTS AND MACHINE ROOMS, THAT ARE IN MECHANICAL ROOMS, AND THAT ARE IDENTIFIED ASEXPOSED ON DRAWINGS.

6. BASIS OF DESIGN PRODUCTS: “MONOKOTE TYPE Z106 & Z106/HY” EXPOSED INTERIOR; “MONOKOTE TYPE Z146” SUBJECT TO IMPACT.

07 84 13 - PENETRATION FIRESTOPPING1. PROVIDE PENETRATION FIRESTOPPING THAT IS PRODUCED AND INSTALLED TO RESIST SPREAD OF FILE ACCORDING TO

REQUIREMENTS INDICATED, RESIST PASSAGE OF SMOKE AND OTHER GASES, AND MAINTAIN ORIGINAL FIRE-RESISTANCE RATING OFCONSTRUCTION PENETRATED. PENETRATION FIRESTOPPING SYSTEMS SHALL BE COMPATIBLE WITH ONE ANOTHER, WITH THESUBSTRATES FORMING OPENINGS, AND WITH PENETRATING ITEMS IF ANY.

2. SUBMIT SCHEDULE OF PENETRATION FIRESTOPPING INDICATING LOCATION AND SPECIFIC ASSEMBLY DESIGNATION OF QUALIFIEDTESTING AND INSPECTING AGENCY.

3. PENETRATIONS IN FIRE-RESISTANCE-RATED WALLS: RATING DETERMINED BY ASTM E 814 OR UL 1479, BASED ON TESTING AT APOSITIVE PRESSURE DIFFERENTIAL OF 0.01-INCH (2.49 PA). PROVIDE F-RATING NOT LESS THAN THE FIRE-RESISTANCE RATING OFCONSTRUCTIONS PENETRATED.

4. PENETRATIONS IN HORIZONTAL ASSEMBLIES: RATINGS DETERMINED BY ASTM E 814 OR UL 1479, BASED ON TESTING AT A POSITIVEPRESSURE DIFFERENTIAL OF 0.01-INCH WG (2.49 PA). PROVIDE F-RATING OF AT LEAST 1 HOUR, BUT NOT LESS THAN THE FIRERESISTANCE RATING OF CONSTRUCTIONS PENETRATED. PROVIDE T-RATING OF AT LEAST 1 HOUR, BUT NOT LESS THAN THE FIRE-RESISTANCE RATING OF CONSTRUCTIONS PENETRATED EXCEPT FOR FLOOR PENETRATIONS WITHIN THE CAVITY OF A WALL.

5. PENETRATIONS IN SMOKE BARRIERS: PROVIDE PENETRATION FIRESTOPPING WITH RATINGS DETERMINED PER UL 1479. PPROVIDE L-RATING NOT EXCEEDING 5.0 CFM/SQ.FT. (0.025 CU. M/S PER SQ.M) OF PENETRATION OPENING AT 0.30-INCH WG (74.7 PA) AT BOTHAMBIENT AND ELEVATED TEMPERATURES.

07 84 46 - FIRE-RESISTIVE JOINT SYSTEMS1. PROVIDE RATED SYSTEMS PER ASTM E 814 or UL 1479 AT PENETRATIONS OF RATED CONSTRUCTION.2. PERFORMANCE REQUIREMENTS:

A. F-RATINGS: PROVIDE FIRESTOP SYSTEMS WITH F-RATINGS EQUALING OR EXCEEDING FIRE-RESISTANCE RATING OF CONSTRUCTIONS PENETRATED AS DETERMINED PER ASTM E 814.

B. T-RATINGS: PROVIDE FIRESTOP SYSTEMS WITH T-RATINGS REQUIRED, AS WELL AS F-RATINGS, DETERMINED PER ASTM E 814, WHERE SYSTEMS PROTECT PENETRATING ITEMS WITH POTENTIAL TO CONTACT ADJACENT MATERIALS IN OCCUPIABLE FLOOR AREAS INCLUDING, BUT NOT LIMITED, TO THE FOLLOWING:1. PENETRATIONS LOCATED OUTSIDE WALL CAVITIES.2. PENETRATIONS LOCATED OUTSIDE FIRE-RESISTIVE SHAFT ENCLOSURES.3. PENETRATIONS LOCATED IN CONSTRUCTION CONTAINING FIRE-PROTECTION-RATED OPENINGS.4. PENETRATING ITEMS LARGER THAN 4-INCH- (100-MM-) DIAMETER NOMINAL PIPE OR 16 SQ. IN. (100 SQ. CM) IN OVERALL

CROSS-SECTIONAL AREA.3. FOR FIRESTOP SYSTEMS EXPOSED TO VIEW, TRAFFIC, MOISTURE, AND PHYSICAL DAMAGE, PROVIDE PRODUCTS THAT AFTER CURING

DO NOT DETERIORATE WHEN EXPOSED TO THESE CONDITIONS BOTH DURING AND AFTER CONSTRUCTION.4. FOR THROUGH-PENETRATION FIRESTOP SYSTEMS EXPOSED TO VIEW, PROVIDE PRODUCTS WITH FLAME-SPREAD INDICES OF LESS

THAN 25 AND SMOKE DEVELOPED INDICES OF LESS THAN 450, WHEN TESTED PER ASTM E 84.5. FIRE-TEST-RESPONSE CHARACTERISTICS: PROVIDE RATED SYSTEMS IDENTICAL TO THOSE TESTED PER ASTM E 814 AND WITH

PRODUCTS BEARING THE CLASSIFICATION MARKING OF A QUALIFIED TESTING AND INSPECTING AGENCY ACCEPTABLE TOAUTHORITIES HAVING JURISDICTION.

6. FIRESTOP SYSTEMS: COMPATIBLE WITH THE SUBSTRATES FORMING OPENINGS, AND WITH THE ITEMS, IF ANY, PENETRATING FIRESTOPSYSTEMS, UNDER CONDITIONS OF SERVICE AND APPLICATION, AS DEMONSTRATED BY MANUFACTURER BASED ON TESTING AND FIELDEXPERIENCE.

7. ACCESSORIES: PROVIDE ACCESSORIES REQUIRED TO INSTALL FILL MATERIALS THAT COMPLY WITH REQUIREMENTS OF TESTEDASSEMBLIES, ARE APPROVED BY QUALIFIED TESTING AND INSPECTING AGENCY THAT PERFORMED TESTING, AND ARE SPECIFIED BYMANUFACTURER OF TESTED ASSEMBLIES.

8. INSTALL THROUGH-PENETRATION FIRESTOP SYSTEMS TO MEET RATINGS REQUIRED AND TO COMPLY WITH FIRESTOP SYSTEMMANUFACTURER'S WRITTEN INSTALLATION INSTRUCTIONS AND PUBLISHED DRAWINGS FOR PRODUCTS AND APPLICATIONSINDICATED.

07 92 00 - JOINT SEALANTS - INTERIOR WORK1. VOC CONTENT OF INTERIOR SEALANTS: PROVIDE INTERIOR SEALANTS AND SEALANT PRIMERS THAT COMPLY WITH THE FOLLOWING

LIMITS FOR VOC CONTENT WHEN CALCULATED ACCORDING TO 40 CFR 59, SUBPART D (EPA METHOD 24); 250 G/L FOR SEALANTS ANDSEALANT PRIMERS FOR NONPOROUS SUBSTRATES; 775 G/L. FOR SEALANT PRIMERS FOR POROUS SUBSTRATES.

2. GENERAL SEALANT (ACRYLIC-EMULSION): MANUFACTURER'S STANDARD, ONE-PART, NON-SAG, MILDEW-RESISTANT, ACRYLIC-EMULSION SEALANT COMPLYING WITH ASTM C 834, FORMULATED TO BE PAINTABLE AND RECOMMENDED FOR EXPOSED APPLICATIONSON INTERIOR AND PROTECTED EXTERIOR EXPOSURES INVOLVING JOINT MOVEMENT OF NOT MORE THAN 7.5%.

3. SANITARY SEALANT: ONE-PART MILDEW-RESISTANT SILICONE SEALANT: TYPE S; GRADE NS; CLASS 25; USES NT, G, A, AND, ASAPPLICABLE TO NONPOROUS JOINT SUBSTRATES INDICATED, O; FORMULATED WITH FUNGICIDE; INTENDED FOR SEALING INTERIORJOINTS WITH NONPOROUS SUBSTRATES AND SUBJECT TO IN-SERVICE EXPOSURE TO CONDITIONS OF HIGH HUMIDITY ANDTEMPERATURE EXTREMES. PRODUCT - DOW CORNING 786 OR GE SILICONES; SANITARY 1700.

08 12 16 - INTERIOR ALUMINUM FRAMES1. BASIS OF DESIGN PRODUCT: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE "SOLUTION II" INTERIOR ALUMUNUM FRAMES

BY RACO INTERIOR PRODUCTS, INC. OR COMPARABLE PRODUCT.2. FIRE-RATED FRAMES: FRAMES FOR FIRE-RATED DOOR ASSEMBLIES COMPLYING WITH NFPA 80 THAT ARE LISTED AND LABELED BY A

QUALIFIED TESTING AGENCY, FOR FIRE-PROTECTION RATINGS INDICATED, BASED ON TESTING AT POSITIVE PRESSURE ACCORDING TONFPA 252 OR ][L 10C.

3. ALUMINUM FRAMING: ASTM 221 (ASTM B221M), ALLOY 6063-T5 OR ALLOW AND TEMPER REQUIRED TO SUIT STRUCTURAL AND FINISHREQUIREMENTS, NOT LESS THAN 0.062 INCH (1.6MM) THICK.

4. DOOR FRAMES: EXTRUDED ALUMINUM, REINFORCED FOR HINGES, STRIKES, AND CLOSERS.5. GLAZING FRAMES: EXTRUDED ALUMINUM, FOR GLAZING THICKNESS INDICATED. FRAMELESS SHALL BE CAPABLE OF RECEIVING 1/2"

THICK GLASS WITHOUT MODIFICATIONS TO FRAMES.6. TRIM: EXTRUDED ALUMINUM, NOT LESS THAN 0.062 INCH (1.6MM) THICK, WITH REMOVABLE SNAP-IN TRIM GLAZING STOPS AND DOOR

STOPS WITHOUT EXPOSED FASTENERS.7. CLEAR ANODIZED FINISH: AAMA 611, AA-M12C22A31, CLASS II, 0.010MM OR THICKER8. DOOR INSTALLATION: INSTALL INTERIOR ALUMINUM FRAMES PLUMB, RIGID, PROPERLY ALIGNED, AND SECURELY FASTENED IN PLACE;

COMPLY WITH MANUFACTRER'S WRITTEN INSTRUCTIONS.

08 14 10 - FLUSH WOOD DOORS1. QUALITY STANDARD: COMPLY WITH NWWDA I.S.1-A, "ARCHITECTURAL WOOD FLUSH DOORS."2. FIRE-RATED WOOD DOORS: DOORS THAT ARE LISTED AND LABELED BY A TESTING AND INSPECTING AGENCY ACCEPTABLE TO

AUTHORITIES HAVING JURISDICTION, FOR FIRE RATINGS INDICATED.A. TEST PRESSURE: BASED ON TESTING AT POSITIVE PRESSURE ACCORDING TO APPLICABLE CODE.

3. DOORS FOR TRANSPARENT FINISH: PREMIUM GRADE , WITH GRADE AA FACES, SPECIES TO BE BIRCH.4. DOORS FOR OPAQUE FINISH: CUSTOM GRADE, WITH FACES OF CLOSED-GRAIN HARDWOOD.5. INTERIOR DOOR CONSTRUCTION: SOLID WOOD CORE, FIVE PLIES WITH STILES AND RAILS BONDED TO CORE, THEN ENTIRE UNIT

ABRASIVE PLANED BEFORE VENEERING. PROVIDE EITHER GLUED-BLOCK OR STRUCTURAL COMPOSITE LUMBER CORES INSTEAD OFPARTICLEBOARD CORES AT LOCATIONS WHERE EXIT DEVICES ARE INDICATED. REFERENCE SECTION 018113 FOR LEEDREQUIREMENTS.

6. FIRE-RATED DOORS: CONSTRUCTION AND CORE SPECIFIED ABOVE FOR TYPE OF FACE INDICATED OR MANUFACTURER'S STANDARDMINERAL CORE CONSTRUCTION AS NEEDED TO PROVIDE FIRE RATING INDICATED.A. EDGE CONSTRUCTION: INTUMESCENT SEALS CONCEALED BY OUTER STILE MATCHING FACE VENEER, AND LAMINATED

BACKING FOR IMPROVED SCREW-HOLDING CAPABILITY AND SPLIT RESISTANCE.B. PAIRS: FURNISH FORMED-STEEL EDGES AND ASTRAGALS WITH INTUMESCENT SEALS FOR PAIRS OF FIRE-RATED DOORS,

UNLESS OTHERWISE INDICATED.C. THE DOOR AND FRAME SHALL BEAR AN APPROVED LABEL OR OTHER IDENTIFICATION SHOWING THE RATING THEREOF,

FOLLOWED BY THE LETTER "S", THE NAME OF THE MANUFACTURER AND THE IDENTIFICATION OF THE SERVICE CONDUCTING THE INSPECTION OF MATERIALS AND WORKMANSHIP AT THE FACTORY DURING FABRICATION AND ASSEMBLY.

7. BLOCKING: FOR MINERAL-CORE DOORS USE COMPOSITE BLOCKING WITH IMPROVED SCREW-HOLDING CAPABILITY TO PROVIDE AMINIMUM 500 LB. SCREW WITHDRAWAL RESISTANCE PER ASTM D 143/NWWDA TM-10 (NOW PUBLISHED BY WDMA) AND MINIMUM 200,000SLAM CYCLES PER ANSI A151.1/NWWDA TM-7 (NOW PUBLISHED BY WDMA) WITHOUT FAILURE.

8. INSTALL DOORS TO COMPLY WITH MANUFACTURER'S WRITTEN INSTRUCTIONS, REFERENCED QUALITY STANDARD, AND AS INDICATED.INSTALL FIRE-RATED DOORS IN CORRESPONDING FIRE-RATED FRAMES ACCORDING TO NFPA 80.

08 31 00 - ACCESS DOORS AND PANELS1. PROVIDE ACCESS DOORS AND PANELS AS SHOWN ON THE DRAWINGS AND AS REQUIRED FOR ACCESS TO UTILITIES AND EQUIPMENT.

FURNISH EACH ACCESS DOOR ASSEMBLY MANUFACTURED AS AN INTEGRAL UNIT, COMPLETE WITH ALL PARTS, AND READY FORINSTALLATION.A. FIRE-RATED ACCESS DOORS AND FRAMES: UNITS COMPLYING WITH NFPA 80 THAT ARE IDENTICAL TO ACCESS DOOR AND

FRAME ASSEMBLIES TESTED FOR FIRE-TEST-RESPONSE CHARACTERISTICS PER THE FOLLOWING TEST METHOD AND THAT ARE LISTED AND LABELED BY UL.

B. VERTICAL ACCESS DOORS AND FRAMES TESTED PER NFPA 252 OR UL 10B.C. HORIZONTAL ACCESS DOORS AND FRAMES TESTED PER ASTM E 119 OR UL 263.

2. FLUSH METAL ACCESS DOORS AND TRIMLESS FRAMES:A. WALL MATERIAL:

1. TILE SURFACES (TOILET ROOMS): STAINLESS STEEL, ASTM A 666, TYPE 304. REMOVE TOOL AND DIE MARKS ANDSTRETCH LINES OR BLEND INTO DIRECTIONAL SATIN NO. 4 FINISH.

B. DOOR: MINIMUM 0.060-INCH (1.5-MM) THICK SHEET METAL, SET FLUSH WITH SURROUNDING FINISH SURFACES.C. FRAME: MINIMUM 0.060-INCH (1.5-MM) THICK SHEET METAL WITH BEAD FOR TYPE OF SURFACE INDICATED.D. HARDWARE:

1. HINGES: CONCEALED PIN TYPE.2. LATCH: SCREWDRIVER-OPERATED CAM LATCH.

E. MANUFACTURERS: KARP ASSOCIATES, INC., MILCOR, INC., OR APPROVED EQUAL.3. CONCEALED FRAME TYPE W/ RECESSED GYP BOARD PANEL FOR EXPOSED GYPSUM BOARD CEILINGS:

A. PRODUCTS/MANUFACTURERS: MODEL L-DWR BY LARSEN'S MANUFACTURING COMPANY OR APPROVED EQUAL

08 71 00 - DOOR HARDWARE1. PROVIDE COMMERCIAL DOOR HARDWARE FOR OPENINGS SHOWN.2. COORDINATION: COORDINATE DOOR HARDWARE WITH OTHER WORK. FURNISH SHOP DRAWINGS OF OTHER WORK WHERE REQUIRED

OR REQUESTED TO COORDINATE INSTALLATION.3. PREPARE DOOR HARDWARE SCHEDULE UNDER THE SUPERVISION OF SUPPLIER, DETAILING FABRICATION AND ASSEMBLY OF DOOR

HARDWARE, AS WELL AS PROCEDURES AND DIAGRAMS. COORDINATE THE FINAL DOOR HARDWARE SCHEDULE WITH DOORS, FRAMES,AND RELATED WORK TO ENSURE PROPER SIZE, THICKNESS, HAND, FUNCTION, AND FINISH OF DOOR HARDWARE.A. FORMAT: COMPLY WITH SCHEDULING SEQUENCE AND VERTICAL FORMAT IN DOOR HARDWARE INSTITUTE'S "SEQUENCE AND

FORMAT FOR THE HARDWARE SCHEDULE."B. ORGANIZATION: ORGANIZE THE DOOR HARDWARE SCHEDULE INTO DOOR HARDWARE SETS INDICATING COMPLETE

DESIGNATIONS OF EVERY ITEM REQUIRED FOR EACH DOOR OR OPENING.C. PROVIDE COMPLETE HARDWARE SETS FOR ALL OPENINGS SHOWN, IN COMPLIANCE WITH LOCAL CODES AND INDUSTRY

STANDARDS.D. WHERE REQUIRED TO MATCH EXISTING BUILDING ITEMS, PROVIDE MANUFACTURERS AND PRODUCTS THAT MATCH BUILDING

STANDARD.E. COORDINATE DOOR FUNCTION AND KEYING WITH TENANT / OWNER.

4. FIRE-RATED DOOR ASSEMBLIES: PROVIDE DOOR HARDWARE FOR ASSEMBLIES COMPLYING WITH NFPA 80 THAT ARE LISTED ANDLABELED BY A TESTING AND INSPECTING AGENCY ACCEPTABLE TO AUTHORITIES HAVING JURISDICTION, FOR FIRE RATINGS INDICATED,BASED ON TESTING ACCORDING TO NFPA 252.

5. SUPPLIER QUALIFICATIONS: DOOR HARDWARE SUPPLIER WITH WAREHOUSING FACILITIES IN PROJECT'S VICINITY AND WHO IS OREMPLOYS A QUALIFIED ARCHITECTURAL HARDWARE CONSULTANT, AVAILABLE DURING THE COURSE OF THE WORK TO CONSULT WITHCONTRACTOR AND OWNER ABOUT DOOR HARDWARE AND KEYING.

6. INSTALL EACH DOOR HARDWARE ITEM TO COMPLY WITH MANUFACTURER'S WRITTEN INSTRUCTIONS. PROVIDE DOOR REINFORCINGAND BLOCKING FOR INSTALLATION OF DOOR HARDWARE WITHOUT THRU-BOLTS. DO NOT INSTALL SURFACE-MOUNTED ITEMS UNTILFINISHES HAVE BEEN COMPLETED ON SUBSTRATES INVOLVED. SET UNITS LEVEL, PLUMB, AND TRUE TO LINE AND LOCATION. ADJUSTAND REINFORCE ATTACHMENT SUBSTRATES AS NECESSARY FOR PROPER INSTALLATION AND OPERATION.

08 80 00 - GLAZING1. MATERIALS: AS SCHEDULED ON THE DRAWINGS.2. GLAZING FOR FIRE-RATED ASSEMBLIES: GLAZING FOR ASSEMBLIES THAT COMPLY WITH NFPA 80 AND THAT ARE LISTED AND LABELED

BY A TESTING AND INSPECTING AGENCY ACCEPTABLE TO AUTHORITIES HAVING JURISDICTION, FOR FIRE RATINGS INDICATED, BASEDON TESTING ACCORDING TO NFPA 257.

3. SAFETY GLAZING PRODUCTS: COMPLY WITH TESTING REQUIREMENTS IN 16 CFR 1201 AND, FOR WIRED GLASS, ANSI Z97.1.4. GLAZING PUBLICATIONS: COMPLY WITH PUBLISHED RECOMMENDATIONS OF GLASS PRODUCT MANUFACTURERS AND ORGANIZATIONS

BELOW, UNLESS MORE STRINGENT REQUIREMENTS ARE INDICATED. REFER TO THESE PUBLICATIONS FOR GLAZING TERMS NOTOTHERWISE DEFINED IN THIS SECTION OR IN REFERENCED STANDARDS.A. GLASS ASSOCIATION OF NORTH AMERICA (GANA) PUBLICATIONS: GANA LAMINATED DIVISION'S "LAMINATED GLASS DESIGN

GUIDE" AND GANA'S "GLAZING MANUAL."

09 00 00 - FINISHES - COMMON WORK RESULTS1. ADHESIVES: USE WATER-RESISTANT, LOW ODOR, LOW VOLATILE, NON-TOXIC AND EMIT LESS THAN EPA MAXIMUM EMISSION RATE

GUIDELINE OF 0.6 MG/M2 HR. FOR VOLATILES; VOC CONTENT OF 65 G/L OR LESS WHEN CALCULATED ACCORDING TO 40 CFR 59,SUBPART D (EPA METHOD 24); AND MEETING GOVERNMENT REQUIREMENTS, AND AS RECOMMENDED BY MANUFACTURER TO SUITPRODUCTS AND SUBSTRATE CONDITIONS INDICATED.

2. BASIS OF DESIGN FINISH PRODUCTS ARE SCHEDULED ON THE DRAWINGS.3. INSTALLER QUALIFICATIONS: MINIMUM 3 YEARS EXPERIENCE IN WORK OF APPLICABLE SECTIONS.4. SAMPLES: PROVIDE SAMPLES OF SUITABLE SIZE FOR REVIEW.

A. SAMPLES FOR INITIAL SELECTION: SUBMIT FOR COMPONENTS WITH FACTORY-APPLIED COLOR FINISHES NOT PRE-SELECTED.B. SAMPLES FOR VERIFICATION (PRE-SELECTED COLORS AND PRODUCT CHARACTERISTICS): SUBMIT FOR EACH COMPONENT

INDICATED AND FOR EACH EXPOSED FINISH REQUIRED5. WARRANTIES: WARRANT FINISH PRODUCTS AGAINST

A. CARPET INSTALLATION: 2 YEAR WARRANTY - DEFECTIVE MATERIALS AND WORKMANSHIP, ISSUED JOINTLY BY FINISH MATERIAL MANUFACTURER, CONTRACTOR, AND INSTALLER.

B. CARPET MATERIAL: MANUFACTURER'S LIMITED 10-YEAR COMMERCIAL WEAROUT / DELAMINATING / TUFT-BIND WARRANTY.6. EXTRA STOCK: PROVIDE 10% PERCENT OF SPECIFIED CARPET, VCT, AND FLOORING MATERIALS TO THE OWNER.7. INSTALL FINISH MATERIALS IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS TO MEET PROJECT REQUIREMENTS INDICATED.8. MOISTURE VAPOR EMISSION TESTS - FLOORING: TEST EACH 1,000-SQ. FT. (92.9-SQ M) OF FLOORING SUBSTRATE, OR PORTION

THEREOF, WITH AN ANHYDROUS CALCIUM CHLORIDE TEST KIT EQUIVALENT TO THE VAPRECISION TEST KIT PRODUCED BYVAPRECISION PROFESSIONAL VAPOR EMISSION TESTING SYSTEMS, NEWPORT BEACH, CA (TEL) 800-449-6194.A. CONDUCT TESTS FOR A MINIMUM OF 72-HOURS IN ACCORDANCE WITH THE TEST KIT MANUFACTURER'S PRINTED

INSTRUCTIONS.B. AN EMISSION RATE OF LESS THAN 3.0-LB/1,000 SQ FT (14.6-KG/SQ M) IN 24-HOURS INDICATES THAT SUBSTRATE IS ACCEPTABLE

FOR FLOORING INSTALLATION.C. IF EMISSION RATES ARE 3.0-LB/1,000 SQ FT (14.6-KG/SQ M) IN 24- HOURS OR GREATER ANYWHERE IN THE AREA TESTED, SUBMIT

A WRITTEN TEST REPORT TO ARCHITECT AND OWNER WITHIN 24-HOURS, INDICATING THE TYPE OF TEST KIT USED AND THE TEST RESULTS AT EACH LOCATION TESTED.

D. IN ADDITION, SUBMIT A PROPOSAL TO FURNISH AND INSTALL A VAPOR EMISSION CONTROL PENETRATE SYSTEM, OR A VAPOR EMISSION CONTROL COATING SYSTEM, OR A VAPOR EMISSION CONTROL DISPERSAL MEMBRANE SYSTEM AS DICTATED BY TEST RESULTS AND PRODUCED BY FLOOR SEAL TECHNOLOGY, INC., SAN JOSE, CA (TEL) 800-572-2344, OR ONE OF THE APPROPRIATE "VAPRSTOP" FAST-CURE EPOXY CONCRETE WATER SEALER SYSTEM PRODUCED BY DUPONT FLOORING SYSTEMS, KENNESAW, GA (TEL) 800-438-7668, WWW.DUPONTCOMMERCIAL.COM

09 22 16 - NON-STRUCTURAL METAL FRAMING1. QUALITY ASSURANCE:

A. FIRE-TEST-RESPONSE CHARACTERISTICS: FOR FIRE-RESISTANCE-RATED ASSEMBLIES THAT INCORPORATE NON-LOAD-BEARING STEEL FRAMING, PROVIDE MATERIALS AND CONSTRUCTION IDENTICAL TO THOSE TESTED IN ASSEMBLY INDICATED ACCORDING TO ASTM E 119 BY AN INDEPENDENT TESTING AGENCY.

B. STC-RATED ASSEMBLIES: FOR STC-RATED ASSEMBLIES, PROVIDE MATERIALS AND CONSTRUCTION IDENTICAL TO THOSE TESTED IN ASSEMBLY INDICATED ACCORDING TO ASTM E 90 AND CLASSIFIED ACCORDING TO ASTM E 413 BY AN INDEPENDENT TESTING AGENCY.

2. STEEL FRAMING: COMPLY WITH ASTM C 754 FOR CONDITIONS INDICATED. METAL COMPLYING WITH ASTM C 645 REQUIREMENTS, ASTMA 653/A 653M, G60 (Z180), HOT-DIP GALVANIZED ZINC COATING.A. FIRESTOP TRACKS: TOP RUNNER MANUFACTURED TO ALLOW PARTITION HEADS TO EXPAND AND CONTRACT WITH MOVEMENT

OF THE STRUCTURE WHILE MAINTAINING CONTINUITY OF FIRE-RESISTANCE-RATED ASSEMBLY INDICATED; IN THICKNESS NOT LESS THAN INDICATED FOR STUDS AND IN WIDTH TO ACCOMMODATE DEPTH OF STUDS

3. GRID SUSPENSION SYSTEM FOR INTERIOR CEILINGS: ASTM C 645, DIRECT-HUNG SYSTEM COMPOSED OF MAIN BEAMS AND CROSS-FURRING MEMBERS THAT INTERLOCK.

4. FURRING CHANNELS (FURRING MEMBERS):A. COLD-ROLLED CHANNELS: 0.0538-INCH (1.37-MM) BARE-STEEL THICKNESS, WITH MINIMUM 1/2-INCH- (12.7-MM-) WIDE FLANGES,

3/4 INCH (19.1 MM) DEEP.

09 29 00 - GYPSUM BOARD1. FIRE-TEST-RESPONSE CHARACTERISTICS: PROVIDE MATERIALS AND CONSTRUCTION IDENTICAL TO THOSE TESTED IN ASSEMBLY

INDICATED ACCORDING TO ASTM E 119 BY AN INDEPENDENT TESTING AND INSPECTING AGENCY.2. SOUND TRANSMISSION CHARACTERISTICS: PROVIDE MATERIALS AND CONSTRUCTION IDENTICAL TO THOSE TESTED IN ASSEMBLY

INDICATED ACCORDING TO ASTM E 90 AND CLASSIFIED ACCORDING TO ASTM E 413 BY A QUALIFIED INDEPENDENT TESTING AGENCY.3. GYPSUM WALLBOARD: ASTM C 36, TYPE AND THICKNESS INDICATED.4. WATER-RESISTANT GYPSUM BACKING BOARD: ASTM C 630/C 630M, WITH CORE TYPE AND IN THICKNESS INDICATED.5. INTERIOR GALVANIZED METAL TRIM: ASTM C 1047.6. EXTRUDED ALUMINUM TRIM: PROFILES AND DIMENSIONS INDICATED. FRY REGLET CORP.,GORDON, INC., PITTCON INDUSTRIES, OR

APPROVED EQUAL.7. JOINT TREATMENT MATERIALS:

A. GENERAL: PROVIDE MATERIALS COMPLYING WITH ASTM C 475, ASTM C 840, AND RECOMMENDATIONS OF MANUFACTURER OF BOTH GYPSUM BOARD AND JOINT TREATMENT MATERIALS FOR THE APPLICATION INDICATED.

B. JOINT TAPE: PAPER REINFORCING TAPE.C. SETTING-TYPE JOINT COMPOUNDS: CHEMICAL-HARDENING POWDER.D. DRYING-TYPE JOINT COMPOUNDS: VINYL-BASED PRODUCTS.

8. NON-LOAD-BEARING STEEL FRAMING INSTALLATION: ASTM C 754, AND ASTM C 840 REQUIREMENTS THAT APPLY TO FRAMINGINSTALLATION.

9. DEFLECTION COMPENSATION: PROVIDE DEFLECTION COMPENSATION AT THE TOP OF PARTITIONS EXTENDING TO STRUCTURE.METHOD SHALL COMPLY WITH UBC 1997 SECTION 706, "FIRE-RESISTIVE JOINT SYSTEMS" AND SECTION 711, "SHAFT ENCLOSURES," ANDUBC STANDARD 7.1, "FIRE TEST PROCEDURES."

10. GYPSUM BOARD INSTALLATION: COMPLY WITH ASTM C 840 AND GA-216.11. WATER-RESISTANT GYPSUM BACKING BOARD: INSTALL WITH 1/4-INCH (6.4-MM) GAP WHERE PANELS ABUT OTHER CONSTRUCTION OR

PENETRATIONS.12. LEVELS OF GYPSUM BOARD FINISH: PROVIDE THE FOLLOWING LEVELS OF GYPSUM BOARD FINISH PER GA-214.

A. LEVEL 1 FOR CEILING PLENUM AREAS, CONCEALED AREAS, AND WHERE INDICATED, UNLESS A HIGHER LEVEL OF FINISH IS REQUIRED FOR FIRE-RESISTIVE-RATED ASSEMBLIES AND SOUND-RATED ASSEMBLIES.

B. LEVEL 2 WHERE WATER-RESISTANT GYPSUM BACKING BOARD PANELS FORM SUBSTRATES FOR TILE, AND WHERE INDICATED.C. LEVEL 4 FOR GYPSUM BOARD SURFACES UNLESS OTHERWISE INDICATED.D. LEVEL 5 FOR GYPSUM BOARD SURFACES WHERE INDICATED TO RECEIVE SMOOTH FINISH AND/OR WALL WASH LIGHT

FIXTURES.

08 11 13 - HOLLOW METAL FRAMES1. MINIMUM THICKNESS: MINIMUM THICKNESS OF BASE METAL WITHOUT COATINGS ACCORDING TO NAAMM- HMMA 803 OR SDI A250.8.2. COORDINATE ANCHORAGE INSTALLATION FOR HOLLOW-METAL FRAMES. FURNISH SETTING DRAWINGS, TEMPLATES, AND DIRECTIONS

FOR INSTALLING ANCHORAGES, INCLUDING SLEEVES, CONCRETE INSERTS, ANCHOR BOLTS, AND ITEMS WITH INTEGRAL ANCHORS.DELIVER SUCH ITEMS TO PROJECT SITE IN TIME FOR INSTALLATION.

3. BASIS OF DESIGN PRODUCT: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE STEELCRAFT FRAMES.A. CONSTRUCT INTERIOR FRAMES TO COMPLY WITH THE STANDARDS INDICATED FOR MATERIALS, FABRICATION, HARDWARE

LOCATIONS, HARDWARE REINFORCEMENT, TOLERANCES, AND CLEARANCES, AND AS SPECIFIED.B. HEAVY-DUTY FRAMES: SDI A250.8, LEVEL 2 AND ANSI A250.8-2017.C. MATERIALS: UNCOATED STEEL SHEET, MINIMUM THICKNESS OF 0.053 INCH.D. CONSTRUCTION: FULL PROFILE WELDED.E. PRIME FINISH: CLEAN, PRETREAT, AND APPLY MANUFACTURER'S STANDARD PRIMER.F. JAMB ANCHORS:

1. MASONRY TYPE: ADJUSTABLE STRAP-AND-STIRRUP OR T-SHAPED ANCHORS TO SUIT FRAME SIZE, NOT LESS THAN 0.042INCH THICK, WITH CORRUGATED OR PERFORATED STRAPS NOT LESS THAN 2 INCHES WIDE BY 10 INCHES LONG; ORWIRE ANCHORS NOT LESS THAN 0.177 INCH THICK.

2. STUD-WALL TYPE: DESIGNED TO ENGAGE STUD, WELDED TO BACK OF FRAMES; NOT LESS THAN 0.042 INCH THICK.G. FLOOR ANCHORS: FORMED FROM SAME MATERIAL AS FRAMES, MINIMUM THICKNESS OF 0.042 INCH, AND

WELD ANCHORS TO BOTTOMS OF JAMBS WITH AT LEAST FOUR SPOT WELDS PER ANCHOR; HOWEVER, FOR SLIP-ON DRYWALL FRAMES, PROVIDE ANCHOR CLIPS OR COUNTERSUNK HOLES AT BOTTOMS OF JAMBS.

E. MATERIAL: COLD-ROLLED STEEL SHEET: ASTM A 1008/A 1008M, COMMERCIAL STEEL (CS), TYPE B; SUITABLE FOR EXPOSED APPLICATIONS. WHERE FRAMES ARE FABRICATED IN SECTIONS DUE TO SHIPPING OR HANDLING LIMITATIONS, PROVIDE ALIGNMENT PLATES OR ANGLES AT EACH JOINT, FABRICATED OF SAME THICKNESS METAL AS FRAMES.

F. FRAME ANCHORS: ASTM A 879/A 879M, COMMERCIAL STEEL (CS), 04Z COATING DESIGNATION; MILL PHOSPHATIZED.DOOR SILENCERS: EXCEPT ON WEATHER-STRIPPED FRAMES, DRILL STOPS TO RECEIVE DOOR SILENCERS AS FOLLOWS. KEEP HOLES CLEAR DURING CONSTRUCTION. DRILL STOP IN STRIKE JAMB TO RECEIVE THREE DOOR SILENCERS.

SHEET

SHEET TITLE

ISSUE DATE

DRAWN BY

CHECKED BYAPPROVED BY

PROJECT NO.

REVISION

PROFESSIONAL OF RECORD:NOTIC

E: THIS

ARCHIT

ECTURAL A

ND E

NGIN

EERIN

G D

RAW

ING IS G

IVEN IN C

ONFID

ENCE A

ND S

HALL B

E U

SED O

NLY P

URSUANT T

O T

HE A

GREEMENT W

ITH T

HE A

RCHIT

ECT. NO O

THER U

SE, DIS

SEMIN

ATIO

N, OR D

UPLIC

ATIO

N M

AY B

E M

ADE W

ITHOUT P

RIO

R W

RIT

TEN

CONSENT O

F T

HE A

RCHIT

ECT. ALL C

OMMON L

AW

RIG

HTS O

F C

OPYRIG

HT A

ND O

THERW

ISE A

RE H

EREBY S

PECIF

ICALLY R

ESERVED.

CLIENT

2221 Schrock RoadColumbus, Ohio 43229-1547p 614.898.7100f 614.898.7570www.msconsultants.com

PROJECT

10/4

/202

1 4:

48:4

1 PM

SPECIFICATIONS

Q002

JPJ

CHARLES M. BUSCH - RA No. ARC.00403518EXP. DATE: 10/31/2021

10/04/2021

CLR/CMB

10/04/2021

62-40487-06

HCA HEALTH ONE, LLC4500 E 9TH AVESTE 160DENVER, CO 80220

QUESTDIAGNOSTICS

# DATE DESCRIPTION

09 30 00 - TILING1. TILE PRODUCTS: AS INDICATED ON DRAWINGS AND SCHEDULES.2. WATERPROOFING AND CRACK-SUPPRESSION MEMBRANE: MANUFACTURER'S STANDARD PRODUCT THAT COMPLIES WITH ANSI

A118.10; NOBLE COMPANY (THE); NOBLESEAL TS, CHLORINATED-POLYETHYLENE-SHEET.3. PORTLAND CEMENT MORTAR (THICKSET) INSTALLATION MATERIALS: ANSI A108.1A.4. DRY-SET PORTLAND CEMENT MORTAR (THIN SET): ANSI A118.1.5. LATEX-PORTLAND CEMENT MORTAR (THIN SET): ANSI A118.4.6. TILE GROUT PER DRAWINGS7. ONE-PART, MILDEW-RESISTANT SILICONE: ASTM C 920; TYPE S; GRADE NS; CLASS 25; FORMULATED WITH FUNGICIDE, INTENDED FOR

IN-SERVICE EXPOSURES OF HIGH HUMIDITY AND EXTREME TEMPERATURES.8. MEDIUM-BED, LATEX-PORTLAND CEMENT MORTAR: COMPLY WITH REQUIREMENTS IN ANSI A118.4. PROVIDE PRODUCT THAT IS

APPROVED BY MANUFACTURER FOR APPLICATION THICKNESS OF 3/4 INCH.9. ANSI TILE INSTALLATION STANDARDS: COMPLY WITH PARTS OF ANSI A108 SERIES "SPECIFICATIONS FOR INSTALLATION OF CERAMIC

TILE" THAT APPLY TO TYPES OF SETTING AND GROUTING MATERIALS AND TO METHODS INDICATED IN CERAMIC TILE INSTALLATIONSCHEDULES.

10. TCA INSTALLATION GUIDELINES: TCA'S "HANDBOOK FOR CERAMIC TILE INSTALLATION." COMPLY WITH TCA INSTALLATION METHODSINDICATED IN CERAMIC TILE INSTALLATION SCHEDULES.

11. TRIMS, EDGES, AND TRANSITIONS TO BE SCHLUTER - SCHIENEA. "L" SHAPED PROFILEB. STRAIGHT ANCHORING LEGC. RADIUS ANCHORING LEG FOR RADIUS APPLICATIONSD. EB - BRUSHED STAINLESS STEEL TYPE 304=V2AE. HEIGHT AS REQUIRED

09 51 10 - ACOUSTICAL PANEL CEILINGS1. ACCEPTABLE MANUFACTURERS FOR SUSPENSION SYSTEMS:

A. ARMSTRONG WORLD INDUSTRIES, INC.B. CHICAGO METALLIC CORPORATIONC. USG INTERIORS INC.; DONN CEILING SUSPENSION SYSTEMS.D. NATIONAL ROLLING MILLS, INC.

2. ACCEPTABLE MANUFACTURERS FOR CEILING PANELS:A. ARMSTRONG WORLD INDUSTRIESB. CERTAINTEED.C. USG

3. ACOUSTICAL CEILING PANEL: REFER TO THE "FINISH AND MATERIALS LEGEND" ON DRAWING "A131" FOR TYPE, SIZE, PATTERN ANDMANUFACTURER.

4. SUSPENSION SYSTEM: RUNNERS AND CROSS RUNNERS SHALL BE DOUBLE THICKNESS WEB, BULB, SECTION DESIGN OR ELECTRO-GALVANIZED STEEL CONFORMING TO ASTM A 366, WEB HEIGHT 1-1/2" WITH 9/16 EXPOSED FACE UNLESS OTHERWISE INDICATED.A. CLASSIFICATION: ASTM C 635, HEAVY DUTYB. COLOR: WHITE, LOW LUSTRE, FACTORY FINISHED.

5. ATTACHMENT DEVICES: SIZED FOR 5 TIMES DESIGN LOAD INDICATED IN ASTM C 635, TABLE 1, DIRECT HUNG, UNLESS OTHERWISEINDICATED.

6. HANGER WIRE: FOR SUPPORT OF SUSPENDED AND FURRED CEILINGS.A. GALVANIZED STEEL WIRE COMPLYING WITH ASTM A641, SOFT TEMPER, PRESTRETCHED, WITH A YIELD STRESS LOAD OF NOT

LESS THAN 3 TIMES DESIGN LOAD.B. THICKNESS: NOT LESS THAN 12 GAUGE, 0.106 INCH DIAMETER.

7. SEISMIC STABILIZER BARS: MANUFACTURER'S STANDARD PERIMETER STABILIZERS DESIGNED TO ACCOMMODATE SEISMIC FORCES.8. SEISMIC STRUTS: MANUFACTURER'S STANDARD COMPRESSION STRUTS DESIGNED TO ACCOMMODATE SEISMIC FORCES.9. SEISMIC CLIPS: MANUFACTURER'S STANDARD SEISMIC CLIPS DESIGNED AND SPACED TO SECURE ACOUSTICAL PANELS IN PLACE.10. WALL MOLDINGS:

A. ELECTRO-GALVANIZED STEEL WITH HEMMED EDGES; PAINTED FINISH; SUPPLIED BY THE MANUFACTURER OF THE SUSPENSION SYSTEM.

B. PROVIDE INSIDE AND OUTSIDE CORNER CAPS TO MATCH THE WALL ANGLE; OUTSIDE CAP TO HAVE APPROPRIATE RADIUS FOR WALL CORNER CONDITION

C. COLOR: MATCH ADJACENT SUSPENSION SYSTEM.11. MOLDINGS AND TRIM: PROVIDE "COMPASSO" BY USG OR "AXIOM" BY ARMSTRONG, OR APPROVED EQUAL, FINISH COLOR AS SELECTED

BY THE ARCHITECT.12. INSTALLATION: COMPLY WITH ASTM C 636, ASTM E 580 AND SUSPENSION SYSTEM MANUFACTURER'S RECOMMENDATIONS. INSTALL

SUSPENSION SYSTEM LEVEL, TRUE TO PLANE, AT INDICATED ELEVATIONS AND PATTERN WITH FINISHED SURFACED UNDAMAGED.

09 65 13 - RESILIENT BASE AND ACCESSORIES1. RESILIENT BASE STANDARD: ASTM F 1861.

A. MATERIAL REQUIREMENT: TYPE TVB. MANUFACTURING METHOD: GROUP 1C. STYLE: STANDARD TOP-SET COVE

2. MINIMUM THICKNESS: 1/8”3. HEIGHT: 4”4. FINISH: MATTE5. INSTALLATION MATERIALS

A. TROWELABLE LEVELING AND PATCHING COMPOUNDS: LATEX-MODIFIED, PORTLAND CEMENT BASED OR BLENDED HYDRAULIC-CEMENT-BASED FORMULATION PROVIDED OR APPROVED BY MANUFACTURER FOR APPLICATIONS INDICATED.

B. ADHESIVES: WATER-RESISTANT TYPE RECOMMENDED BY MANUFACTURER TO SUIT RESILIENT PRODUCTS AND SUBSTRATE CONDITIONS INDICATED.

6. RESILIENT BASE INSTALLATIONA. COMPLY WITH MANUFACTURER'S WRITTEN INSTRUCTIONS FOR INSTALLING RESILIENT BASE.B. APPLY RESILIENT BASE TO WALLS, COLUMNS, PILASTERS, CASEWORK AND CABINETS IN TOE SPACES, AND OTHER PERMANENT

FIXTURES IN ROOMS AND AREAS WHERE BASE IS REQUIRED.C. INSTALL RESILIENT BASE IN LENGTHS AS LONG AS PRACTICABLE WITHOUT GAPS AT SEAMS AND WITH TOPS OF ADJACENT

PIECES ALIGNED.D. TIGHTLY ADHERE RESILIENT BASE TO SUBSTRATE THROUGHOUT LENGTH OF EACH PIECE, WITH BASE IN CONTINUOUS

CONTACT WITH HORIZONTAL AND VERTICAL SUBSTRATES.E. DO NOT STRETCH RESILIENT BASE DURING INSTALLATION.

09 65 19 - RESILIENT TILE FLOORING1. PRODUCTS

A. GENERAL:1. RESILIENT TILE FLOORING COMPLIES WITH FLOORSCORE STANDARD.2. LOW-VOC ADHESIVE AND SEALANT.

B. VINYL COMPOSITION FLOOR TILE:1. SIZE: 12 BY 12 INCHES (305 BY 305 MM).

C. SOLID VINYL FLOOR TILE:1. ASTM F 1700, CLASS III, TYPE B EMBOSSED SURFACE. THICKNESS: 0.125

D. INSTALLATION MATERIALS:1. TROWELABLE LEVELING AND PATCHING COMPOUNDS.2. ADHESIVES.3. SEAMLESS-INSTALLATION ACCESSORIES.4. FLOOR POLISH.

2. FLOOR TILE INSTALLATIONA. LAY TILES SQUARE WITH ROOM AXISB. FOR STATIC DISSIPATIVE TILE, REFERENCE MANUFACTURER'S INSTALLATION REQUIREMENTS

09 68 00 - CARPETING1. SUBMIT SHOP DRAWINGS INDICATING CARPET LOCATIONS, DYE LOT LIMITATIONS, SEAMING PLAN, METHOD OF JOINING SEAMS,

DIRECTION OF CARPET IN EACH ROOM OR AREA, AND TYPE AND LOCATION OF TRANSITION STRIPS. SUBMIT SAMPLES: 12X12 INCHSAMPLES IN EACH COLOR AND PATTERN. SUBMIT SAMPLE OF TRANSITION STRIPS, 4 INCHES LONG IN EACH COLOR.

2. SEAMING MATERIALS: AS RECOMMENDED BY CARPET MANUFACTURER. ADHESIVE WATERPROOF LATEX BASED CEMENT FORMULATEDSPECIFICALLY FOR INSTALLING CARPET; RECOMMENDED BY CARPET MANUFACTURER. LEVELING COMPOUND: WHITE, PREMIXED,LATEX BASED.

3. INSTALL CARPET IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. PROVIDE "LOK DOTS" FOR ALL CARPET TILE.

09 72 00 - WALL COVERINGS1. SURFACE-BURNING CHARACTERISTICS: COMPLY WITH ASTM E 84; TESTING BY A QUALIFIED TESTING AGENCY. IDENTIFY PRODUCTS

WITH APPROPRIATE MARKINGS OF APPLICABLE TESTING AGENCY.A. FLAME-SPREAD INDEX: 25 OR LESSB. SMOKE-DEVELOPED INDEX 450 OR LESS

2. VINYL WALL COVERING: REFER TO THE "FINISH LEGEND" FOR TYPE, COLOR, PATTERN, AND MANUFACTURER.3. FABRIC WALL COVERING: TYPES, COLORS, PATTERNS, AND MANUFACTURERS OF WALL COVERING MATERIAL SHALL BE AS INDICATED

IN "FINISH LEGEND". PROVIDE MANUFACTURER'S STANDARD BACKING ON FABRICS WHICH ARE ADHESIVE APPLIED. ALL FABRICS SHALLBE FLAME RETARDANT TREATED BY FABRIC MANUFACTURER.

4. PRIMER/SEALER: MILDEW RESISTANT, RECOMMENDED IN WRITING BY WALLCOVERING MANUFACTURER FOR INTENDED SUBSTRATE.5. INSTALL SEAMS VERTICAL AND PLUMB AT LEAST 6 INCHES FROM OUTSIDE CORONERS AND 3 INCHES FROM INSIDE CORNERS UNLESS A

CHANGE OF PATTERN OR COLOR EXISTS AT CORNER. NO HORIZONTAL SEAMS ARE PERMITTED.

09 90 00 - PAINTING AND COATING1. SUBMIT PRODUCT DATA FROM MANUFACTURER FOR PROPOSED USE. INCLUDE PRODUCT DESIGNATION AND GRADE OF EACH PAINT

AND COATING TYPE, SURFACE PREPARATION MATERIALS AND PROCEDURES, AND PRODUCT ANALYSIS AND PERFORMANCECHARACTERISTICS FOR EACH PAINT AND COATING TYPE.

2. SUBMIT SAMPLES OF 8.5"X11" INCH FOR EACH TYPE PAINT SHOWING COLOR AND LUSTER, ON REPRESENTATIVE SUBSTRATE. SUBMIT12X12 INCH TEXTURE SAMPLES ON GYPSUM BOARD BACKING.

3. PROVIDE 1 GALLON CONTAINERS EXTRA STOCK OF EACH COLOR FINISH COAT TO THE OWNER.4. NO SUBSTITUTIONS UNLESS APPROVED BY ARCHITECT. FOR GYPSUM BOARD SURFACES USE

A. PROMAR 200 ZERO VOC INTERIOR LATEXB. PROMAR 400 ZERO VOC INTERIOR LATEX

5. DO NOT THIN PAINT IN EXCESS OF MANUFACTURER'S RECOMMENDATIONS.6. APPLY PAINTS AND COATINGS WITHIN MINIMUM DRY FILM THICKNESS RANGE RECOMMENDED BY MANUFACTURER. MATCH FINAL COAT

OF PAINT TO APPROVED COLOR.7. THE NUMBER OF COATS AND FILM THICKNESS REQUIRED IS THE SAME REGARDLESS OF THE APPLICATION METHOD. DO NOT APPLY

SUCCEEDING COATS UNTIL THE PREVIOUS COAT HAS CURED AS RECOMMENDED BY THE COATING MANUFACTURER. SAND BETWEENAPPLICATIONS WHERE SANDING IS REQUIRED TO PRODUCE AN EVEN SMOOTH SURFACE IN ACCORDANCE WITH THEMANUFACTURER'S DIRECTIONS. SAND LIGHTLY BETWEEN EACH SUCCEEDING ENAMEL OR VARNISH COAT.

8. APPLY ADDITIONAL COATS AND BARRIER COATS WHEN UNDERCOATS, STAINS, OR OTHER CONDITIONS SHOW THROUGH FINAL COATOF PAINT UNTIL PAINT FILM IS OF UNIFORM SHEEN, FINISH, COLOR, AND APPEARANCE. GIVE SPECIAL ATTENTION TO ENSURE THATSURFACES, INCLUDING EDGES, CORNERS, CREVICES, WELDS, AND EXPOSED FASTENERS, RECEIVE A DRY FILM THICKNESSEQUIVALENT TO THAT OF FLAT SURFACES.

9. BEFORE APPLICATION OF FINISH COATS, APPLY A PRIME COAT OF MATERIAL AS RECOMMENDED BY THE MANUFACTURER TOMATERIAL THAT IS REQUIRED TO BE PAINTED OR FINISHED AND HAS NOT BEEN PRIME COATED BY OTHERS. CLEAN AND TOUCH-UPPRIME PAINT WELDS AND OTHER DAMAGED AREAS OF SHOP PRIMED ITEMS.

10. COMPLETELY COVER TO PROVIDE AN OPAQUE, SMOOTH SURFACE OF UNIFORM FINISH, COLOR, APPEARANCE, AND COVERAGE.CLOUDINESS, SPOTTING, HOLIDAYS, LAPS, BRUSH MARKS, RUNS, SAGS, ROPINESS, OR OTHER SURFACE IMPERFECTIONS WILL NOT BEACCEPTABLE.

11. PAINT INTERIOR SURFACES OF DUCTS, WHERE VISIBLE THROUGH REGISTERS OR GRILLES, WITH A FLAT, NONSPECULAR BLACK PAINT.12. PAINT BACK SIDES OF ACCESS PANELS AND REMOVABLE OR HINGED COVERS TO MATCH EXPOSED SURFACES.13. DRYWALL STIPPLE ENAMEL FINISH: ROLL AND REDISTRIBUTE PAINT TO AN EVEN AND FINE "ORANGE-PEEL" FINE NAP TEXTURE. LEAVE

NO EVIDENCE OF ROLLING SUCH AS LAPS, IRREGULARITY IN TEXTURE, SKID MARKS, OR OTHER SURFACE IMPERFECTIONS.14. FINISH EXTERIOR DOORS ON TOPS, BOTTOMS, AND SIDE EDGES SAME AS EXTERIOR FACES.

10 26 00 CORNER GUARDS1. HEAVY-DUTY CORNER TRIM: FABRICATE FROM EXTRUDED POLYESTER WITH CONTINUOUS INTEGRAL 7/8" WIDE TAPERED FIN WITH

STAGGERED HOLE TO RECEIVE STANDARD FASTENERS, AND CONTINUOUS GROOVES INTO FACE OF FINS TO IMPROVE BONDING OFGYPSUM BOARD JOINT COMPOUND. HEAVY-DUTY CORNER TRIM SHALL PRIME PAINTED AFTER FABRICATION.A. PRODUCT/MANUFACTURERS: INPRO - SEE FINISH SCHEDULE FOR COLOR/PATTERNB. EXPOSED CORNER WIDTH: 1.25"

10 44 00 FIRE EXTINGUISHERS1. PROVIDE FIRE-RATED CABINETS THAT ARE LISTED AND LABELED TO COMPLY WITH REQUIREMENTS IN ASTM E 814 FOR FIRE-

RESISTANCE RATING OF WALLS WHERE THEY ARE INSTALLED.2. CABINET CONSTRUCTION: RECESSED CABINET WITH STEEL SHEET BODY AND FULLY GLAZED ALUMINUM SHEET DOOR.3. IDENTIFICATION: LETTERING COMPLYING WITH AUTHORITIES HAVING JURISDICTION FOR LETTER STYLE, SIZE, SPACING, AND LOCATION.

LOCATE ON DOOR ADJACENT TO HANDLE.4. FIRE EXTINGUISHERS: PROVIDE ONE OR BOTH OF THE FOLLOWING FIRE EXTINGUISHERS BASED ON THE RULES AND REGULATIONS OF

THE AUTHORITY HAVING JURISDICTION:A. MULTIPURPOSE DRY-CHEMICAL TYPE: UL-RATED 4-A:60-B:C, 10-LB (4.5-KG) NOMINAL CAPACITY

5. MOUNTING BRACKETS: MANUFACTURER'S STANDARD GALVANIZED STEEL, DESIGNED TO SECURE FIRE EXTINGUISHER TO WALL ORSTRUCTURE, OF SIZES REQUIRED FOR TYPES AND CAPACITIES OF FIRE EXTINGUISHERS INDICATED, WITH PLATED OR BLACK BAKED-ENAMEL FINISH.

SHEET

SHEET TITLE

ISSUE DATE

DRAWN BY

CHECKED BYAPPROVED BY

PROJECT NO.

REVISION

PROFESSIONAL OF RECORD:NOTIC

E: THIS

ARCHIT

ECTURAL A

ND E

NGIN

EERIN

G D

RAW

ING IS G

IVEN IN C

ONFID

ENCE A

ND S

HALL B

E U

SED O

NLY P

URSUANT T

O T

HE A

GREEMENT W

ITH T

HE A

RCHIT

ECT. NO O

THER U

SE, DIS

SEMIN

ATIO

N, OR D

UPLIC

ATIO

N M

AY B

E M

ADE W

ITHOUT P

RIO

R W

RIT

TEN

CONSENT O

F T

HE A

RCHIT

ECT. ALL C

OMMON L

AW

RIG

HTS O

F C

OPYRIG

HT A

ND O

THERW

ISE A

RE H

EREBY S

PECIF

ICALLY R

ESERVED.

CLIENT

2221 Schrock RoadColumbus, Ohio 43229-1547p 614.898.7100f 614.898.7570www.msconsultants.com

PROJECT

10/4

/202

1 4:

48:4

2 PM

SPECIFICATIONS

Q003

JPJ

CHARLES M. BUSCH - RA No. ARC.00403518EXP. DATE: 10/31/2021

10/04/2021

CLR/CMB

10/04/2021

62-40487-06

HCA HEALTH ONE, LLC4500 E 9TH AVESTE 160DENVER, CO 80220

QUESTDIAGNOSTICS

# DATE DESCRIPTION

NOTICE TO CONTRACTOR1. THESE DOCUMENTS ARE INTENDED TO ILLUSTRATE CLIENT PREFERENCES AND MINIMUM ACCEPTABLE CRITERIA FOR THIS

PROJECT. IN ADDITION, THESE DOCUMENTS ARE INTENDED TO FACILITATE A DEGREE OF PRELIMINARY COORDINATIONAMONG THE TRADES. HOWEVER, NOTHING CONTAINED IN THESE DOCUMENTS SHALL DIMINISH OR NEGATE THECONTRACTOR'S RESPONSIBILITIES OR OBLIGATIONS FOR COMPLETE, FUNCTIONAL, AND PROPERLY COORDINATED SYSTEMS.

2. ALTHOUGH THE LOCATIONS AND TYPES OF SPRINKLER HEADS MAY BE SHOWN ON THE DRAWINGS, THE CONTRACTOR SHALLBE RESPONSIBLE TO ENSURE THAT THE NUMBER, TYPE, AND LOCATIONS OF SPRINKLER HEADS COMPLIES WITH NFPASTANDARDS, ALL GOVERNING CODES, AND APPROVALS FROM AUTHORITIES HAVING JURISDICTION. WHEREVER POSSIBLE,FINAL SPRINKLER HEAD LOCATIONS SHALL FOLLOW THE PATTERNS, POSITIONS, AND CRITERIA AS SHOWN ON THEDRAWINGS, SUCH AS CENTERING ON LAY-IN CEILING TILES, SYMMETRY WITH RESPECT TO CORRIDORS AND OTHER BUILDINGGEOMETRY, POSITIONING WITH RESPECT TO LIGHTING FIXTURES, AND OTHER PERTINENT AND RELATIVE CONDITIONS. ITSHALL BE THE CONTRACTOR'S RESPONSIBILITY TO MAKE ALL ROUGH-IN AND FINAL COORDINATION OF ALL SPRINKLER HEADSWITH ALL OTHER TRADES AND BUILDING FEATURES.

3. PIPE SIZES WHEN SHOWN ON THE DRAWINGS SHALL BE CONSIDERED THE MINIMUM ACCEPTABLE FOR THIS PROJECT.THE CONTRACTOR SHALL BE RESPONSIBLE TO ENSURE THAT THE CORRECT PIPE SIZES ARE INSTALLED FOR EACHAPPLICATION.

4. DETAILS SHOWN ON THE DRAWINGS ARE INTENDED TO ILLUSTRATE THE TYPES AND ARRANGEMENTS OF SPRINKLER SYSTEMSPECIALTIES, GENERAL LOCATIONS OF RISERS, AND THE MINIMUM ACCEPTABLE PROVISIONS. THE CONTRACTOR SHALL BERESPONSIBLE TO DETERMINE THE NUMBER AND LOCATIONS OF SPRINKLER RISER, WATER SUPPLY ARRANGEMENTS,BACKFLOW PREVENTION REQUIREMENTS, ALL COORDINATION, AND ALL COMPONENTS ANCILLARY TO AND REQUIRED FORPROPER AND COMPLETE SPRINKLER SYSTEM OPERATION, TESTING, AND MAINTENANCE.

5. UNLESS OTHERWISE NOTED OR REQUIRED, ROUTING OF SPRINKLER SYSTEM PIPING SHOWN ON THE DRAWINGS ISDIAGRAMMATIC ONLY AND INTENDED TO ILLUSTRATE GENERAL SPACE PLANNING. THE CONTRACTOR SHALL BERESPONSIBLE TO COORDINATE FINAL ROUGH-IN AND PIPE ROUTING AS REQUIRED FOR PROPER SPRINKLER SYSTEMINSTALLATION AND COORDINATION WITH OTHER BUILDING SYSTEMS AND FEATURES.

6. SPRINKLER CONTRACTOR SHALL OBTAIN THE MOST RECENT FLOW TEST FOR THE DESIGN AND HYDRAULIC CALCULATIONSON THE PROJECT. FLOW TEST SHALL BE NO OLDER THAN 6 MONTHS FROM THE DATE OF SUBMITTAL FOR ENGINEERINGREVIEW.

105LH

101LH

104LH

103LH

106LH

03LH

02LH

01LH

100LH

107LH

102LH

SHEET

SHEET TITLE

ISSUE DATE

DRAWN BY

CHECKED BYAPPROVED BY

PROJECT NO.

REVISION

FOR REFERENCE

ONLY

NOTIC

E: THIS

ARCHIT

ECTURAL A

ND E

NGIN

EERIN

G D

RAW

ING IS G

IVEN IN C

ONFID

ENCE A

ND S

HALL B

E U

SED O

NLY P

URSUANT T

O T

HE A

GREEMENT W

ITH T

HE A

RCHIT

ECT. NO O

THER U

SE, DIS

SEMIN

ATIO

N, OR D

UPLIC

ATIO

N M

AY B

E M

ADE W

ITHOUT P

RIO

R W

RIT

TEN

CONSENT O

F T

HE A

RCHIT

ECT. ALL C

OMMON L

AW

RIG

HTS O

F C

OPYRIG

HT A

ND O

THERW

ISE A

RE H

EREBY S

PECIF

ICALLY R

ESERVED.

CLIENT

2221 Schrock RoadColumbus, Ohio 43229-1547p 614.898.7100f 614.898.7570www.msconsultants.com

PROJECT

10/5

/202

1 3:

51:0

1 PM

FIRE PROTECTION PLAN

FP101

GSG

MRM

10/04/2021

62-40487-06

HCA HEALTH ONE, LLC4500 E 9TH AVESTE 160DENVER, CO 80220

QUESTDIAGNOSTICS

HAZARD CLASSIFICATION...NO. NAME

HAZARDCLASSIFICATION DESCRIPTION

01 SPECIAL SERVICES LH LIGHT HAZARD02 PATIENT ENCOUNTER LH LIGHT HAZARD03 PATIENT ENCOUNTER LH LIGHT HAZARD

100 WAITING ROOM LH LIGHT HAZARD101 HALL LH LIGHT HAZARD102 JANITOR/ STORAGE LH LIGHT HAZARD103 SUPPLY LH LIGHT HAZARD104 SPECIMEN

CONSOLIDATIONLH LIGHT HAZARD

105 UNISEX TOILET LH LIGHT HAZARD106 EMPLOYEE BREAK ROOM LH LIGHT HAZARD107 UNISEX TOILET LH LIGHT HAZARD

PLAN NORTH

GENERAL NOTESA PROVIDE ALL WORK IN COMPLIANCE WITH ALL LOCAL, STATE AND FEDERAL CODES.

COORDINATE ALL WORK WITH LOCAL FIRE MARSHAL.B SPRINKLER CONTRACTOR SHALL OBTAIN AND PAY FOR ALL STATE AND LOCAL

PERMITS REQUIRED FOR THIS WORK, AND SCHEDULE ANY INSPECTIONS REQUIREDBY GOVERNING RULES AND REGULATIONS.

C PROVIDE FULL SPRINKLER COVERAGE FOR ALL SPACES IN COMPLIANCE WITHLOCAL, STATE AND FEDERAL CODES, NFPA-13 AND OWNER'S INSURANCECARRIER/UNDERWRITER.

D COORDINATE FIRE PROTECTION SYSTEMS WITH ALL OTHER TRADES, BUILDINGCONDITIONS, ETC.

E ALL PIPING SHALL BE ROUTED AND PITCHED BELOW BUILDING STEEL WITHSPRINKLER HEADS AS HIGH AS POSSIBLE IN SPACES WITH NO CEILINGS (EXPOSEDROOF STRUCTURE).

F FOR ALL AREAS WITH CEILING GRIDS, PROVIDE SPRINKLERS IN THE CENTER TILESAND SHALL BE WHITE FINISH. REFER TO ARCHITECTURAL PLAN FOR CEILING GRIDLAYOUT.

G THE SPRINKLER/FIRE PROTECTION CONTRACTOR SHALL BE RESPONSIBLE FORMODIFYING AND HYDRAULICALLY CALCULATING EXISTING SPRINKLER SYSTEM.

H FIRE PROTECTION CONTRACTOR SHALL TEST AND FLUSH PIPING.I NOTE THAT THIS PLAN IS FOR REFERENCE ONLY. THE FIRE PROTECTION

CONTRACTOR SHALL DESIGN THE ENTIRE FIRE PROTECTION SYSTEM PER NFPA-13,INCLUDING ALL HEAD LOCATIONS, BRANCH PIPING, MAIN RUNS AND ASSOCIATEDPIPING SIZES.

1/4" = 1'-0"1 FIRE PROTECTION PLAN

# DATE DESCRIPTION

AV

D

M

D

MAX

S

R

HB

PIPING ANCHOR INTERMEDIATE

AUTOMATIC AIR VENT

BALL VALVE

BLOW OFF STRAINER

BUTTERFLY VALVE

DIELECTRIC UNION

FLANGED GLOBE VALVE (PLAN)

FLANGED OUTLET DOWN TEE

FLANGED OUTLET UP TEE

FLANGED SIDE OUTLET TEE

FLANGED SIDE OUTLET UP TEE

FLANGED TURNED DOWN ELBOW

FLANGED TURNED UP ELBOW

FLANGED UNION

DOMESTIC COLD WATER

DOMESTIC HOT WATER

DOMESTIC HOT WATER RETURN

SANITARY VENT

STORM PIPING

SEWER

WALL CLEANOUT

FLOOR CLEANOUT

FLOOR DRAIN

ROOF DRAIN

WATER METER

SANITARY DRAIN

GATE VALVE (OR OTHER TYPE VALVE WHERE SPECIFIED)

GLOBE VALVE

CHECK VALVE

3-WAY VALVE (MANUAL)

3-WAY CONTROL VALVE

3-WAY PNEUMATIC CONTROL VALVE WITH POSITIONER

RELIEF VALVE

PRESSURE REDUCING VALVE

CONTROL VALVE-ELECTRONIC

CONTROL VALVE-SOLENOID

STRAINER

THERMOMETER & SEPARABLE SOCKET

PRESSURE GAUGE W/GAUGE COCK

DIAPHRAM VALVE

ANGLE VALVE-VERTICAL

BALANCING VALVE

CIRCUIT SETTER

PLUG VALVE

NEEDLE VALVE

UNION

PIPE RUN UP

PIPE RUN DOWN

PIPE DROP

FLOW DIRECTION

PITCH DIRECTION (D-DOWN, R-RISE)

PIPING GUIDE

EXPANSION JOINT

EXPANSION LOOP

FLEXIBLE CONNECTION

REDUCER, CONCENTRIC

REDUCER, ECCENTRIC

MANUAL AIR VENT

PRESSURE & TEMPERATURE TAP

STEAM TRAP

HOSE BIBB

PLUMBING PIPING

VALVES AND FITTINGS

12

12

1

12

2

GENERAL NOTES - PLUMBING

AFF ABOVE FINISHED FLOORAP ACCESS PANELARCH ARCHITECT (-URAL, -URE)ATM ATMOSPHEREAUX AUXILIARY

BFP BACKFLOW PREVENTERBHP BRAKE HORSEPOWER, BOILER HORSEPOWERBOP BOTTOM OF PIPEBTU BRITISH THERMAL UNITBTUH BRITISH THERMAL UNITS PER HOUR

CA COMPRESSED AIRCB CATCH BASINCI CAST IRONCO CLEANOUT, CARBON MONOXIDECOL COLUMNCOMP COMPRESSORCOND CONDENSATECONT CONTINU (-E, -ATION, -OUS)CP CONDENSATE PUMPCR CONDENSATE RETURNCS CIRCUIT SETTERCV CONTROL VALVECv COEFFICIENT, VALVE FLOWCWR COLD WATER RETURNCWS COLD WATER SUPPLY

DB DRY-BULBDCW DOMESTIC COLD WATERDHW DOMESTIC HOT WATERDHWR DOMESTIC HOT WATER RETURNDIA DIAMETERDN DOWNDS DOWNSPOUTDWG DRAWING

EQUIP EQUIPMENTET EXPANSION TANKEW EYE WASH

EXP EXPANSION

F FAUCET

FD FLOOR DRAINFDC FIRE DEPARTMENT CONNECTIONFH FIRE HOSEFHC FIRE HOSE CABINETFHR FIRE HOSE RACKFHYR FIRE HYDRANTFIXT FIXTUREFOR FUEL OIL RETURNFOS FUEL OIL SUPPLYFPM FEET PER MINUTEFPS FEET PER SECONDFS FLOW SWITCHFT FEET

GC GENERAL CONTRACTORGPH GALLONS PER HOURGPM GALLONS PER MINUTE

HB HOSE BIBHD HEADHP HORSEPOWERHT HEIGHT

IN INCHES

LAV LAVATORYLBS POUNDSLF LINEAR FEETLPS LOW PRESSURE STEAM

M METERMAX MAXIMUMMBH BRITISH THERMAL UNITS (THOUSANDS)MIN MINUTES, MINIMUMMP MEDIUM PRESSUREMPC MEDIUM PRESSURE CONDENSATEMPS MEDIUM PRESSURE STEAMMWP MAXIMUM WORKING PRESSURE

N/A NOT APPLICABLENC NORMALLY CLOSEDNG NATURAL GASNIC NOT IN CONTRACTNO NORMALLY OPENNPW NON POTABLE WATER

OD OUTSIDE DIAMETEROS&Y OUTSIDE SCREW & YOKE (VALVE)

PCF POUNDS PER CUBIC FOOTPC PUMPED CONDENSATEPD PRESSURE DROPPPM PARTS PER MILLIONPRESSPRV PRESSURE REDUCING VALVEPSI POUNDS PER SQUARE INCHPSIG PRESSURE PER SQUARE INCH GAUGEPSV PILOT SOLENOID VALVE

QTY QUANTITY

RD ROOF DRAINRECIRC RECIRCULATEREFRIG REFRIGERANTRL REFRIGERANT LIQUIDRPBP REDUCED PRESSURE BACKFLOW PREVENTERRPM REVOLUTIONS PER MINUTERPS REVOLUTIONS PER SECONDRR REFRIGERANT RELIEFRS REFRIGERANT SUCTION

SCFM CFM, STANDARD CONDITIONSSF SQUARE FEETSHT SHEETSP STATIC PRESSURESPGR SPECIFIC GRAVITYSPKLR SPRINKLERSS SERVICE SINKSTD STANDARD

TAB TESTING, ADJUSTING AND BALANCINGTCC TEMPERATURE CONTROL CONTRACTORTD TEMPERATURE DIFFERENCETI TEMPERATURE INDICATORTSP TOTAL STATIC PRESSURETT TEMPERATURE TRANSMITTERTYP TYPICAL

UNO UNLESS NOTED OTHERWISEUR URINAL

UT UTILITY REEL

PLUMBING ABBREVIATIONS GENERAL SYMBOLS PLUMBING PIPING SYMBOLSKEYNOTE TAG1. DEMOLITION KEYNOTE2. NEW WORK KEYNOTE

MECHANICAL EQUIPMENT TAG1. MECHANICAL EQUIPMENT TYPE2. EQUIPMENT NUMBER

DETAIL TAG1. DETAIL NUMBER2. SHEET NUMBER

SECTION TAG1. SECTION NUMBER2. SHEET NUMBER

LINETYPE INDICATES NEW PIPING

LINETYPE INDICATES EXISTING PIPINGTO BE REMOVED

NEW WORK CONNECTION

DEMOLITION WORK CONNECTION

DCW

DHW

DHWR

V

ST

SAN

S

V

EWC ELECTRIC WATER COOLER

AD AREA DRAIN

US UTILITY SINK

KS KITCHEN SINK

PRESSURE

V VENTVAC VACUUMVEL VELOCITYVTR VENT THRU ROOF

W WASTEW/ WITHWC WATER CLOSETW/O WITHOUTWC WATER COLUMNWH WATER HEATER

FCO FLOOR CLEANOUT

A. PRIOR TO BID, PLUMBING CONTRACTOR AND GENERAL CONTRACTOR SHALL VERIFY SANITARY SEWER SYSTEM LOCATION, ROUTING, PITCHES, INVERTS, SIZES AND TIE-IN POINT. ALL SEWER SYSTEM INFORMATION SHALL BE COORDINATED WITH GC AND OWNER REPRESENTATIVE AT TIME OF BID WALK-THROUGH. INFORM PLUMBING ENGINEER OF ANY AND ALL DISCREPANCIES FROM WORK SHOWN ON PLUMBING DRAWINGS PRIOR TO BID DATE.

B. ALL PIPING AND EQUIPMENT SHOWN IN LIGHT LINEWORK IS EXISTING AND TO REMAIN OR AS INDICATED BY KEYNOTES.

C. ALL PIPING AND EQUIPMENT SHOWN IN DARK LINEWORK IS NEW OR AS INDICATED BY KEYNOTES.

D. ALL PIPING, DUCTWORK OR MECHANICAL EQUIPMENT SHOWN ON DEMOLITION DRAWINGS IN DASHED LINE WORK IS TO BE REMOVED OR AS INDICATED ON KEYNOTES.

E. THE DRAWINGS INDICATE THE GENERAL ARRANGEMENT OF NEW AND EXISTING PIPING AND EQUIPMENT. THE CONTRACTOR SHALL FOLLOW THIS ARRANGEMENT WHEREVER FEASIBLE. HOWEVER, IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTORS TO VERIFY EXISTING FIELD CONDITIONS AND TO MAKE MINOR MODIFICATIONS TO LOCATIONS, ELEVATIONS ETC., AS MAY BE REQUIRED. IF A DIFFERENT ARRANGEMENT THAN THAT SHOWN OR A MINOR OFFSET, RISE OR DROP IS REQUIRED TO CLEAR AN OBSTRUCTION, IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO PROVIDE AND INSTALL SUCH WORK AS MAY BE REQUIRED WITHOUT ADDITIONAL COST TO THE OWNER.

F. INSTALL ALL EQUIPMENT AND COMPONENTS IN ACCORDANCE WITH MANUFACTURER'S PUBLISHED INSTALLATION INSTRUCTIONS WITH RECOMMENDED LOCATIONS TO ENSURE THAT THE SPECIFIED PRODUCTS SERVE THE INTENDED FUNCTION. MAINTAIN PROPER CLEARANCES FOR SERVICE, INSPECTION AND MAINTENANCE OF EQUIPMENT.

G. ALL CONTRACTORS SHALL COORDINATE AND SCHEDULE THEIR WORK WITH OWNER AND ALL OTHER TRADES TO MINIMIZE THE INTERFERENCE WITH THE OPERATION OF THE BUILDING. ALL CONTRACTORS SHALL TAKE THE NECESSARY PRECAUTIONS TO PROTECT THE OWNER BUILDING AND EQUIPMENT AT ALL TIMES DURING CONSTRUCTION.

H. THE WORD "PROVIDE" MEANS TO FURNISH AND INSTALL.

I. THE WORD "FURNISH" MEANS TO SUPPLY TO JOB SITE ONLY.

J. WHEN INSTALLING PIPING OR EQUIPMENT UNDER THIS CONTRACT, THE CONTRACTOR SHALL CONFER WITH OTHER CONTRACTORS TO AVOID ANY CONFLICTS BETWEEN THE THE CONTRACTOR SHALL BE RESPONSIBLE, AT THEIR OWN EXPENSE, FOR THE REMOVAL AND RE-INSTALLATION OF ANY PART OF THEIR WORK IF IT WAS INSTALLED WITHOUT CONSULTING THE OTHER TRADES.

K. SEAL ALL EDGES OF INSULATION ON PIPING. REPAIR AND PATCH ALL INSULATION TO MATCH EXISTING AT AREAS WHERE NEW CONNECTIONS HAVE BEEN MADE TO EXISTING PIPING OR EQUIPMENT.

L. SEE CIVIL, ELECTRICAL AND ARCHITECTURAL DRAWINGS FOR ADDITIONAL WORK TO BE COORDINATED WITH THESE DRAWINGS. COORDINATE PIPING INSTALLATION WITH NEW CABLE TRAY SUSPENSION SYSTEM INCLUDING THREADED RODS, CABLE TRAYS, ETC.

M. UNDER NO CONDITION, SHOULD ELECTRICAL CONDUITS, FEEDERS AND/OR ANY ON-LINE SERVICE BE DISTURBED, MOVED OR INTERRUPTED UNLESS SPECIFICALLY REQUIRED TO INSTALL NEW PIPING AND EQUIPMENT. IT SHALL BE THE RESPONSIBILITY OF THE PLUMBING CONTRACTOR TO COORDINATE THE RELOCATION OF EXISTING CONDUITS WHERE REQUIRED, WITH THE ELECTRICAL CONTRACTOR, TEMPERATURE CONTROLS CONTRACTOR AND THE OWNER'S REPRESENTATIVE. IF RELOCATION IS REQUIRED, IT SHALL BE DONE AT NO ADDITIONAL COST TO THE OWNER.

N. SHOP DRAWINGS TO BE PROVIDED FOR ALL EQUIPMENT AND PIPING LAYOUTS.

O. THE CONTRACTOR SHALL CLEAN-UP ALL DEBRIS CAUSED BY THEIR WORK AS IT ACCUMULATES. CONTRACTOR SHALL CLEAN AND DAMP MOP ALL WORK AREAS AND WORK TRAFFIC AREAS AT THE END OF EACH WORK DAY. CONTRACTORS ARE TO CONFINE CONSTRUCTION TRAFFIC TO THE CONSTRUCTION AREA AS MUCH AS POSSIBLE TO MINIMIZE DUST.

P. ASBESTOS CONTAINING MATERIALS (ACM) IS STRICTLY PROHIBITED FROM BEING INSTALLED. SHOULD ACM BE INADVERTENTLY INSTALLED ON PROJECTS, PROPER REMOVAL, DISPOSAL AND REPLACEMENT WITH APPROVED PRODUCT SHALL BE THE SOLE RESPONSIBILITY OF THE INSTALLING CONTRACTOR AT NO COST TO THE OWNER.

Q. ALL WORK SHALL BE PROVIDED IN ACCORDANCE WITH CURRENT VERSIONS OF APPLICABLE LOCAL, STATE, AND NATIONAL CODES AS DETERMINED BY THE AUTHORITY HAVING JURISDICTION (AHJ).

R. PENETRATIONS THROUGH FIRE/SMOKE RATED CONSTRUCTION SHALL BE PROTECTED WITH A PRODUCT LISTED AND LABELED TO MAINTAIN THE FIRE/SMOKE RATING.

S. MINIMUM PARALLEL DISTANCE FROM EXTERIOR OR LOAD BEARING WALLS TO THE CENTERLINE OF AN UNDERGROUND PIPE SHALL BE THREE FEET FOR REPAIR ACCESS. PIPING SHALL NOT BE INSTALLED DIRECTLY UNDER EXTERIOR OR LOAD BEARING WALLS.

T. INCLUDE ALLOWANCES IN BID FOR MODIFICATIONS OF ALL FIXTURES AND EQUIPMENT CONNECTIONS TO MATCH REQUIREMENTS OF ACTUAL INSTALLATION WITHOUT ADDITIONAL COSTS TO OWNER.

U. FOR HOT AND COLD DOMESTIC SUPPLY PIPING CONNECTIONS(S) AT NEW FIXTURE(S), PROVIDE ANGLE STOP VALVE WITH ESCUTCHEON WASHER AND REMOVABLE KEY.

V. ALL GAS PIPING SHALL BE INSPECTED AND TESTED IN ACCORDANCE WITH THE REQUIREMENTS OF INTERNATIONAL FUEL GAS CODE SECTION 406.1.

W. CAULK ALL CLEANOUT GRATINGS FLUSH TO AVOID TRAPPING OF DIRT.

X. ALL PLUMBING PIPING SHALL BE ROUTED AROUND ELECTRICAL AREAS WHERE POSSIBLE. IF ROOF DRAINS ARE OVER THE AREA, DRIP PAN SHALL BE INSTALLED UNDER THE ENTIRE LENGTH OF EACH PIPE OVER THE SENSITIVE AREA OVER THE ROOM, CHANNELING WATER AWAY SO AS TO PREVENT ANY LEAKS IN THE AREA. AT THE LOWER SEGMENT OF DRIP PAN, ROUTE DRAIN TO NEAREST APPROVED RECEPTACLE WITH AN APPROVED AIR GAP PER CODE. CONTRACTOR SHALL REVIEW ALL DRAWING PRIOR TO CONSTRUCTION, AND REPORT IF THIS CONDITION EXIST.

SHEET

SHEET TITLE

ISSUE DATE

DRAWN BY

CHECKED BYAPPROVED BY

PROJECT NO.

REVISION

PROFESSIONAL OF RECORD:NOTIC

E: THIS

ARCHIT

ECTURAL A

ND E

NGIN

EERIN

G D

RAW

ING IS G

IVEN IN C

ONFID

ENCE A

ND S

HALL B

E U

SED O

NLY P

URSUANT T

O T

HE A

GREEMENT W

ITH T

HE A

RCHIT

ECT. NO O

THER U

SE, DIS

SEMIN

ATIO

N, OR D

UPLIC

ATIO

N M

AY B

E M

ADE W

ITHOUT P

RIO

R W

RIT

TEN

CONSENT O

F T

HE A

RCHIT

ECT. ALL C

OMMON L

AW

RIG

HTS O

F C

OPYRIG

HT A

ND O

THERW

ISE A

RE H

EREBY S

PECIF

ICALLY R

ESERVED.

CLIENT

2221 Schrock RoadColumbus, Ohio 43229-1547p 614.898.7100f 614.898.7570www.msconsultants.com

PROJECT

10/5

/202

1 3:

51:1

6 PM

PLUMBING GENERAL NOTES

P001

GSG

JASON E. CHRISTOFF - PE No.PE.0056074EXP DATE: 10/31/2021

10/04/2021

MRM

10/04/2021

62-40487-06

HCA HEALTH ONE, LLC4500 E 9TH AVESTE 160DENVER, CO 80220

QUESTDIAGNOSTICS

# DATE DESCRIPTION

DIVISION 22 - PLUMBINGSECTION 22 00 00 - PLUMBING

PART 1 - GENERAL1.1 SCOPE

A. Furnish all materials, labor, tools, transportation, incidentals and appurtenances to complete in every detail and leave in working order all items of work called for herein or shown on the accompanying drawings.

B. Include any minor items of work necessary to provide a complete and fully operative plumbing system.C. All questions relating to this Section of Plans and Specifications should be addressed to the Construction Manager.D.

1.2 WORK DESCRIBED ELSEWHEREA. The Contractor for this work is referred to Bidding Requirements. General Conditions, Special Conditions, Temporary Services and other

pertinent Sections of Division I. These Sections describe work which is a part of this Contract. The following General Provisions amplify and supplement these Sections of Division I. In cases of conflicting requirements, the stipulations set forth in Divisions I supersede and must be satisfied by the Contractor.

B. Related work described elsewhere:1. High voltage wiring and disconnects by electrician.2. Roof openings framed by General Contractor. General Contractor to furnish and install roof flashing.3. Motor starter and interlock wiring by Electrical Contractor.

1.3 GENERAL REQUIREMENTSA. Contractor must read the entire Specifications covering other branches or work. He is responsible for coordination of his work with work

performed by other trades.B. Consult all contract drawings and shop drawings which may affect the location of any equipment or apparatus furnished under this work and

make minor adjustments in location as necessary to secure coordination.C. The layout shown on the Drawings is based on a particular make of equipment. If another make of equipment is used which requires modification

or changes of any description from the drawings or specifications, Contractor shall be responsible as a part of this work, for making all such modifications and changes, including those involving other trades with the cost thereof included in his bid. In such case, Contractor shall submit drawings and specifications prior to starting work showing all such modifications and changes. His proposal shall be subject to the approval of the Construction Manager.

D. System layout is schematic and exact locations shall be determined by structural and other conditions. This shall not be construed to mean that the design of the system may be arbitrarily changed. The equipment layout is to fit into the building as constructed and to coordinate with equipment included under other Divisions of work.

E. Contact the Construction Manager immediately if noticing discrepancies or omissions in either the drawings, or the specifications, or if there are any questions regarding their meaning or intent.

F. Submit all changes, other than minor adjustments, to the Construction Manager for approval before proceeding with the work.G. Architect or Construction Manager reserves the right to make minor changes in location of piping and equipment, up to the time of roughing-in,

without additional cost.H. The Contractor is required to visit the site and fully inform himself concerning all conditions affecting the scope of work. Failure to visit the site

shall not relieve the Contractor from any responsibility in the performance of his work.I. All workmanship to be of the highest quality in accordance with the best practices of the trade by craftsmen skilled in this particular work. All work

shall be done in a timely manner as to not disrupt coordination with other trades.J. Contractor to have a competent superintendent in charge of the work installed under this Contract. Superintendent to be experienced in this type

of work.

1.4 PERMITS, INSPECTIONS AND CODESA. File all Drawings, pay all fees, and obtain permits and certificates of inspection relative to this work.B. Completed installation shall conform with all applicable Federal, State and Local Laws, Codes and Ordinances, including, but not limited to the

latest editions of the following:1. State Building Code.2. Specific Construction Safety Requirements, State Industrial Commission.3. State Pressure Piping Systems Rules.4. A.S.M.E. Pressure Piping Code.5. Standards for Welding Requirements, State Industrial Commission.6. Occupational Safety and Health Act (OSHA) of 1971 and all amendments and revisions thereto.

C. Nothing contained in the drawings and specifications shall be construed to conflict with these laws, codes and ordinances and they are hereby included in these Specifications.

1.5 DRAWINGSA. Drawings are schematic and show approximate locations of piping and equipment. Exact locations shall be coordinated by Contractor.B. Significant deviations from drawings must be approved by the Construction Manager.

1.6 ELECTRICAL MOTORSA. All motors shall comply with Energy Policy Act of 1992 (EPACT). Motors shall be provided by contractor unless they are factory installed on the

unit. All wiring, safety switches and motor starters shall be provided by the Electrical Contractor.B. This Contractor shall furnish the Electrical Contractor with all wiring diagrams necessary to connect and control plumbing equipment.

1.7 OPERATING AND MAINTENANCE INSTRUCTIONSA. Instruct the Construction Manager in all matters pertaining to the proper operation and maintenance of equipment furnished under this contract.B. Submit three (3) sets of instructions to the Owner in the hard-bound three-ring notebooks, including installation, maintenance and operating

instructions, pamphlets or brochures and warranties obtained from each manufacturer of principal items of equipment.C. Copies of warranties on all equipment shall be included with this data.D. A copy of final inspection certificate shall also be turned over to the Owner before final payment will be made.

1.8 INSPECTIONA. Contractor to arrange for and include in his bid, inspection of this work by one of the following:

1. Local Code Authority2. State Code Authority3. Certified Private Inspection Agency

1.9 GUARANTEEA. Contractor is responsible for defects, repairs and replacements in materials and workmanship for a period of one (1) year after final payment is

approved by the Construction Manager.

1.10 MATERIALSA. Furnish new and un-deteriorated materials and of a quality not less than what is specified.

1. Contractor to furnish and install only those brands of equipment mentioned specifically or accepted as substitutes.

1.11 EQUIPMENT SELECTION AND APPROVALA. The selection of materials and equipment to be furnished shall be governed by the following:

1. Where trade names, brands, or manufacturer of equipment or materials are listed in the Schedules, the exact equipment listed shall beused in the bid. Where more than one name is listed, Contractor may select any one of the several brands specified.

2. Any additional approved optional manufacturer will be listed by Addendum only. In order to be considered, Contractor must requestapproval of optional manufacturer in writing no later than one (1) week prior to the bid date.

B. Within ten (10) days after the Award of Contract, Contractor must submit a list to the Construction Manager showing the names of manufacturers and sub-contractors he intends to use.

1.12 SUBSTITUTIONSA. Contractor must base his bid on furnishing the brands of material and equipment listed in the Specifications.B. He is entitled to bid on any other equal or similar brands of material and equipment he may desire to substitute. The substitute must be listed on

the substitution sheet, with the difference in cost from base bid clearly stated.C. Substitutions which are accepted shall be written into the Contract and no changes of brands shall be made after the Contract is signed unless

approved in writing.

1.13 PROTECTION AND CLEANINGA. Protect all fixtures against damage from leaks or abuse and pay the cost of repair or replacement of fixtures, piping or equipment made

necessary by failure to provide suitable safeguards or protection.B. After all piping and equipment has been inspected and approved, thoroughly clean all equipment, bare piping and insulation provided under this

work.C. After all fixtures have been set, thoroughly clean all fixtures, removing stickers and other foreign matter and leave every part in acceptable

condition, clean and ready for use.D. Repair all dents and scratches in factory prime or finish coats on all equipment. If damage is excessive, replacement shall be required.

1.14 CUTTING AND PATCHINGA. Plan work ahead and place sleeves in walls, floors and ceiling and anticipate during initial stages of construction such openings as will be

required to accommodate equipment and ducts. Coordinate work closely with the Construction Manager so as to conceal plumbing work in the finished portions of the building.

B. Cut as necessary to install new fixtures and equipment piping. Avoid cutting of concrete, masonry and other work by inserts and sleeves.C. Give the Construction Manager locations and sizes of all openings required for the installation of equipment before construction and walls are

started. If it becomes necessary to cut into new work because of the failure of Contractor to notify the Construction Manager, then the Construction Manager shall do any necessary cutting and patching at this Contractor’s expense.

D. Patching must match existing surfaces in kind and finish, and shall be done by the Construction Manager at this Contractor’s expense.

1.15 EXCAVATION AND BACKFILLA. Provide any trenching required to install underground plumbing items and piping. Remove forms and debris before backfilling. Tamp and

compact backfill in 6 inch layers to bring level with existing grade. Replace and patch surface to match existing sod, gravel, blacktop or concrete.

1.16 FOUNDATIONS & SUPPORTSA. Contractor is fully responsible for the proper installation of all concrete pads and related work. Coordinate the installation of foundations, curbs

and bases for plumbing equipment with the Construction Manager. Concrete work to be performed by the Construction Manager.B. Install welded steel frames for equipment and auxiliary steel supports for piping. Use black steel supports for piping. Use black steel or channel

iron all coated with primer and finish coat; weatherproof with coating of bitumastic where supports are exposed to elements.

1.17 SLEEVES AND COLLARSA. Pipe sleeves shall be installed in all ceilings where pipes are to pass through. Sleeves shall be galvanized sheet metal of such size as to allow

pipe and insulation to pass through with a minimum clearance of ¼” on all sides. Install chrome-plated collars where piping is exposed in “finished” areas.

B. Sleeves through fire rated construction shall be packed with 3M Brand Firestop caulk or tape, Fyre Putty Brand caulk.

1.18 SHOP DRAWINGSA. Shop drawings, wiring diagrams, pump curves or other data shall be submitted for review.B. Shop drawing will not be reviewed unless they are clearly stamped by the Construction Manager.C. Review of shop drawings or schedules shall not relieve the Contractor from responsibility for errors, omissions or other deficiencies or

deviations from the contract drawings or specifications.D. Furnish detailed drawings of the following:

1. Plumbing Fixtures and All Trim2. Drains and Cleanouts3. Carriers4. Hose Bibs5. Water Heater6. House Water Pumps (if required)7. Grease Trap (if required)8. Backflow Preventers (if required)

PART 2 - PRODUCTS

2.1 SOIL, WASTE, & VENT PIPINGA. Provide fully functional sanitary piping system including sewer and sewer connection to city sewer if shown on plans.B. Piping and fittings: Any type allowed by Building and Health Codes and as approved by Owner. Use no plastic less than Schedule 40,

minimum. ABS plastic not allowed.C. Contractor must comply with Local Building and Health Codes with respect to usage of these materials.D. Joints:

1. Cast Iron:a. Compression type plastic seal.b. Neoprene gaskets with approved neoprene-based lubricant sealer.

2. No-Hub: Neoprene sealing sleeve and stainless steel shield and clamp.3. Other Materials: As recommended by manufacturer in accordance with governing Building and Health Codes.

2.2 DRAINS – SEE PLANS

2.3 CLEANOUTSA. In walls of finished areas, use cleanout tee and provide cleanout and access cover similar to Zurn Series No. ZANB-1468 with round stainless

steel cover and threaded plug. Size to suit cleanout.B. In floors of finished areas, provide Jonespec Co. #2450-PV4 cast iron, round screwdown access cover box with polished scoriated Bronze top

and anchor lugs. Use 4” (max.).C. All other cleanouts shall be similar to Zurn ZARB-1470 and be flush with floor or wall and have countersunk brass heads. Use 4” (max.).D. Zurn, Wade, J.R. Smith, or Josam.

2.4 TRAPSA. Trap each fixture drain and piece of equipment that connects to soil and waste system. Bell and spigot pipe shall be trapped with service

weight cast iron. Traps on threaded pipe shall be recess drainage pattern. Trap primers to be provided where required by code.B. Furnish trap constructed and sized as indicated on the drawings.

2.5 DOMESTIC HOT & COLD WATER PIPINGA. Furnish and install the following:

1. Complete hot, cold, and make-up water piping system for fixtures and equipment.B. Piping:

1. Above Grade: Water piping shall be one of the following:a. Type “L” hard tempered copper tubing (ASTM B-88) with wrought copper, bronze or brass fittings, polished joints and

soldered with 95/5 solder to work at 150 lbs. S.W.P.b. CPVC only, no PVCc. PEX.d. Aquatherm fittings as an alternative to copper.

2. Below Grade, Interior and Exterior: Water Piping shall be NSF 61 rated SDR-9 Polyethylene pipe ASTM D-2239 or as required bylocal code.

3. Galvanized steel piping may be used for line sizes 2 ½” and larger.C. Valves:

1. 125 lbs. S.W.P. gate, ball, globe and check valves:a. Gate (2 ½” and larger) – Iron body, bronze mounted O.S. and Y, flanged, taper solid wedge disc.b. Ball (2” and smaller) – all bronze, screwed or sweat, two piece, full port design.c. Check (3” and larger) – Iron body, bronze mounted, flanged horizontal swing with bronze disc.d. Check (2 ½” and smaller) – All bronze, screwed or sweat, horizontal swing check with bronze disc.e. Fixture shutoff cocks on hot or cold water to be straight or angle stop type, ½” size, chrome plated brass, rigid supply and

stop.2. Crane, Fairbanks, Powell, Walworth, Hammond, Lunkenheimer or Stockham.

D. Hose Bibbs:1. Interior hose bibbs to include gate valves and vacuum breaker. Crane, Flat, or Kohler.2. All exterior hose bibbs are to be freezeless. Woodford 65C.

E. Unions:1. For copper pipe, use 150 lbs., all bronze, solder end type. Chase, Crane, Flagg, Mueller or Northern Indiana Brass Company.2. For steel pipe, use 300 lbs. galvanized malleable iron, ground seat, bronze to stub, non-shock Fairbanks type PIC or equal by

Rockwell, Grinnel, or Crane.3. Dielectric unions between ferrous and copper shall be insulated to prevent metal-to-metal contact and be manufactured by Capital

Manufacturing Company of Columbus, Ohio, Patrol or PECO Sales Company.F. Thermostatic and Point-of-Use Tempering Vavles:

1. Point-of-use tempering valve shall be installed on the hot water supply to each lavatory and hand sink.2. It shall have a lead free cast copper silicon alloy body. Lead free thermostatic valves shall comply with state codes and standards,

where applicable, requiring reduced lead content. The valve shall include integral filter washers and check valves and an adjustmentcap with locking feature. The valve shall be provided with solder, threaded, CPVC, Quick Connect, PEX or w/press union connections.The valve shall be a Watts WLFUSGBM2C, or equal.

3. Approvals: ASSE 1017, ASSE 1069, ASSE 1070 and IAPMO cUPC listed.

2.6 GAS PIPINGA. Furnish and install complete system of low pressure gas piping to all items of equipment, including shutoff valve, union and dirt leg at each final

connection as required by drawings and plans.B. Verify special installation and metering requirements with Utility Company.C. If propane is required, all gas piping should be sized for natural gas and necessary hook up to propane tank must be coordinated with propane

supplier.D. Piping:

1. Schedule 40 black steel pipe (ASTM A53). Welded joints. Screwed malleable iron fittings may be used on piping 2 ½” and smaller.2. Underground gas pipe shall be standard weight black steel and shall be welded and wrapped with factory coated Minnesota Mining &

Manufacturing Company’s “Scot-Cote 202”. Prime fittings and welds with Royston A-36 gray primer and wrap with Scot-Wrap No. 40protective tape, Overlap the spiral turn a minimum of ¼”. “X-Tru-Coat” factory coating and plastic shrink sleeves may be used at theContractor’s option. Provide anode protection on gas lines.

E. Valves:1. 1” and smaller; 125 lbs. iron body with bronze plug washer. Crane #320 or Homestead #601.2. 1 ¼” and larger; Lubricated plug cock. Nordstrum #142 or Homestead #6023. Equal valves by Nibco, Lunkenheimer, Stockham or Powell are acceptable.

2.7 HANGERSA. Hangers for copper lines. 2” and smaller, shall be similar to Grinnell Fig. CT-99, adjustable carbon steel pipe ring, copper plated, with 3/8”

hanger rods. Galvanized hangers and strap hangers will not be permitted for supporting copper lines.B. Hangers for copper lines 2 ½” and larger shall be similar to Grinnell Fig. CT-65, adjustable carbon steel clevis, copper plated, with proper size

rods. Unplated clevis may be used if lead sleeves 2” wider than the clevis are secured to the pipe at each hanger.C. Hangers for steel and plastic lines 2 ½” and smaller, similar to Grinnell Fig. 97, adjustable pipe ring, galvanized steel band.D. Hangers for steel and plastic lines 3” and larger shall be similar to Grinnell Fig. 260, adjustable carbon steel clevis, heavy duty, with proper size

rods.E. Horizontal soil pipe to be supported at hub of each 5’-0” joint, base of each riser, at each floor and elsewhere as required, using Grinnell Fig.

260, adjustable carbon steel clevis with proper size rods.F. Plastic pipe shall be supported in accordance with prevailing Codes and manufacturer’s recommendations.G. Grinnell, Elcen, Penn, Fee-Mason, Modern, Michigan Hanger Co.H. Corrosion resistant factory finish. Support, Unistrut No. P-1000 or Kindorf.

2.8 FIXTURESA. Refer to Drawing Fixture Schedules for specific catalog numbers.B. Carriers where applicable, to be three-point supported by Wade, Zurn, or Josam.

2.9 PIPING INSULATIONA. Furnish and install insulation as follows:

1. All insulations, jackets, cements, adhesives, and vapor barriers shall have a U.L. listing not to exceed a flame spread rating of 25 andsmoke developed rating of 50 (NFPA 90A).

2. Insulation shall be Armstrong “AP Armaflex SS” or equal, self-sealing, flexible, closed-cell elastomeric insulation, 1” thickness. R-valuemust be 3.7 or larger as tested per ASTM C177 or C518. Piping insulation shall be Armaflex, Rubetex or equal.

3. Branch runs shall be insulated with ½” thick Armstrong “AP Armaflex SS”. Piping insulation shall be by Armaflex, Rubetex or equal.4. Exposed lavatory piping, drain and trap under lavatories and sinks shall be insulated with Handi Lav-Guard Insulation kit as

manufactured by Truebro Inc. Model #101, color white.

2.10 PLUMBING PIPING SPECIALTIESA. Install piping specialties as indicated on the Drawings and as described therein.B. Design capacities and ratings shown on Drawings.C. Thermometers (4 ½”): (Package)

1. Weiss 45VA3 piping thermometers, direct mounting, or remote reading as required, with adjustable 4 ½” diameter face, black steelcase, and brass separable sockets.

D. Pressure Gauges: (Package)1. Weiss PG-1 Series cast aluminum, black case, 4 ½” diameter with phosphor bronze Bourdon tube and brass socket ¼” N.P.T.

E. Strainers:1. V.D. Anderson style AMF (flanged) or BGC (threaded), 125 lbs. S.W.P. Y-pattern, cast iron body with perforated brass screen for water.

Threaded for 2 ½” and smaller, flanged for 3” and larger. Trane or Sarco.F. Shock Absorbers:

1. Wade, Josam, or Zurn shockstops sized as recommended by Plumbing and Drainage Institute and Manufacturer.G. Vacuum Breakers:

1. Watts No. 288A with bronze body and trim, disc float, full size orifice, 125 lbs. S.W.P.H. Backflow Preventer Valves: (Package)

1. Watts Series 009, Install in accordance with local codes.I. Meters – Furnished by Owner and installed by P.C.

1. Master Meter multi-jet water meter with pulse outlet communication.2. RCM flow transmitter for natural gas with pulse outlet communication.

J. Access Doors:1. Milcor Style M with gauge steel frame, 14 gauge steel panel, (factory prime coat), spring-type concealed hinges and screwdriver-

operated, metal cam lock, wall access panels only.

PART 3 - EXECUTION

3.1 PLUMBING TESTINGA. Piping systems to be tested as follows and be proven tight:

1. General requirements: All defects disclosed as the result of the tests shall be remedied at this Contractor’s expense. All materials andequipment used for tests shall be provided by the contractor.

2. Water piping: Shall be subjected to hydrostatic test of 200 pounds per square inch. All potable water piping shall be disinfected by amixture containing not less than 0.6 pound of high-test calcium hypochlorite, or an equivalent amount of chlorinated lime (about 2 pounds) to each 100 gallons of water, which provides not less than 50 ppm of available chlorine. The mixture shall be injected into the system and retained for not less than 12 hours. The system shall then be drained thoroughly, flushed until all traces of chlorine and foreign materials are removed.

3. Sanitary piping: 1st test: Underground piping shall be pressure tested before backfilling. 2nd test: Before the installation of any fixtures,the ends of the system shall be capped and all lines filled with water to the highest vent and allowed to stand for at least 24 hours without leakage. This test shall be made with piping exposed. 3rd test: This shall be an in-service test performed after all equipment is installed. The entire vent and sewer system shall be tested. Final test shall be either smoke or peppermint test, using an approved apparatus. Before proceeding with either test, all traps shall be filled with water. Smoke test shall be accomplished by filling entire sewer system with a pungent thick smoke produced by one or more smoke machines. When smoke appears at stack openings on the roof, they shall be closed and a pressure equivalent to a 1 inch water column shall be exerted and maintained for 15 minutes beforeinspection starts. An alternate peppermint test shall be accomplished by introducing a minimum of 2 ounces of oil of peppermint into each stack. All stacks and line openings shall be closed during test for a minimum period of ½ hour.

B. Changes in ambient temperature will be taken into account when testing piping, however, the various systems shall be thoroughly inspected for leaks before hydrostatic pressure tests are concluded.

C. Furnish all pumps for air and water pressure, gauges, and all required test equipment.D. Remove all air from lines before beginning of tests.E. Flush scale and dirt from piping until clean.

3.2 GAS PIPING TESTINGA. Gas piping shall be black steel, schedule 40, conforming to ANSI Z21-30 and AGA industrial and commercial gas requirements. Fitting shall be

welded as according to ANSI-16.9 or screwed as specified.B. This Contractor shall run all supplies as shown by the drawings. Final connections to mechanical equipment shall be by this contractor. All

equipment furnished under this contract not having “off-on” gas cocks furnished shall have gas cocks furnished and installed by this contractor.C. Test interior gas piping at a pressure of 100 psig for a period of 24 hours without a drop in pressure. Any leaks shall be repaired by this

contractor and the lines retested. All tests shall be in accordance with the local utility and shall be witnessed by that utility and Owner’s Representative. Replace Ansul Valve with a filler piece during testing and replace after testing.

D. Electrically isolate service piping from the building gas piping with insulator at building entrance.E. Provide building shut-off valve immediately after entering building.

3.3 SOIL, WASTE, VENT AND CONDENSATE PIPING INSTALLATIONA. Coordinate locations of cleanouts with General Contractor and with equipment location.B. Pitch all soil, waste, and condensate piping a minimum of 1/8” per foot except as noted on Plans or as required by Local Codes.C. All vent and branch vent piping shall be self-draining.D. Trap all floor drains.E. Exposed fixture traps shall be chrome-plated brass.F. Tops of drains and cleanouts shall be installed flush with the finished floor.

3.4 WATER PIPING INSTALLATIONA. Install piping to provide complete drainage of the system toward the source wherever possible. Provide drain valves at all drainage points on

pipes. Pipe shall be cut accurately to measurements established at the building by the Contractor and worked into place without springing or forcing. After cutting and reaming and before assembling, all lengths of pipe shall be set vertically and tapped with a hammer to remove scale and dust and inspected to insure that no foreign matter is lodged therein. Pipe shall follow building lines clearing all windows, doors, and other openings and no diagonal piping will be allowed. Keep pipe a sufficient distance apart to allow installation of pipe insulation covering. Allowance and provisions to be made for expansion and contraction of pipe.

B. Pipe to be run concealed wherever possible. Location of pipe in interior partitions shall be carefully coordinated with the Construction Manager who will construct the partitions after the piping is in place. Where exposed risers occur they shall be kept as close to walls as possible.

C. Piping to be run as close to underside of roof structure as physically possible.D. All copper pipe joints to be made with 95/5 solder unless threaded.E. Install shut-off valves on hot and cold water branch lines serving more than one fixture.F. Install shock absorbers where shown on Plans and where recommended by the Plumbing and Drainage Institute. Provide access panels if

installed in walls or above gypsum board ceilings.G. Install 1” thick Armaflex insulation on all copper piping passing through concrete or masonry.H. All underslab copper piping shall have a minimum of 2” thick gravel cover.

3.5 GAS PIPING INSTALLATIONA. Use backing rings on welded piping.B. Provide lubricated plug cock immediately inside building and at each unit.C. Line to have minimum of 24 inches cover to finish grade.D. Test piping in accordance with Utility Company’s requirement. After testing, purge system completely.

3.6 PIPE HANGERS INSTALLATIONA. Hangers for steel or copper pipe shall be as follows:

PIPE SIZE MAX. SPAN½” – 1” 6 ft.1 ¼” – 2 ½” 10 ft.3”-4” 12 ft.5”-8” 16 ft.

B. Hanger spacing for plastic pipe shall be in accordance with prevailing Codes and manufacturer’s recommendations.C. Isolate copper piping from steel pipe and conduits with lead sheet or electrical tape.D. Install pipe anchors and guides to control expansion of piping.

3.7 PLUMBING FIXTURES INSTALLATIONA. Fixtures to be installed in accordance with Manufacturer’s recommendations at mounting heights indicated in the Fixture Schedule or per

Handicap Code. Install stop valves on all fixture supply lines.B. Carriers to be securely anchored to structure. Bolt feet to the floor. Install chrome plated brass escutcheons on exposed lines entering walls.C. Provide rough-in waste, vent, hot and cold water piping to equipment. Coordinate exact location and rough-in requirements with Equipment

Contractor, or installer. Install cast brass P-traps, chrome plated, only where exposed.D. Make final connections to each piece of equipment whether or not furnished under this Contract.

3.8 PIPING INSULATION INSTALLATIONA. Insulate domestic cold water lines, hot water lines (1/2” size and over), and horizontal runs of interior condensate lines.B. Insulation shall not be applied unless, or until:

1. Surfaces are clean and dry.2. System has been thoroughly tested.3. Hanger rods are perpendicular to building lines.

C. Taper pipe insulation ends with insulating cement. All insulation to be finished smooth, ready for painting.D. Install all insulation in strict accordance with the manufacturer’s recommendations.E. Insulate exposed drains and traps for public lavatories. Install according to manufacturer’s recommendations.

3.9 PIPING SPECIALTIES INSTALLATIONA. Install all items per Manufacturer’s recommendation and/or where shown on Plans.

SHEET

SHEET TITLE

ISSUE DATE

DRAWN BY

CHECKED BYAPPROVED BY

PROJECT NO.

REVISION

PROFESSIONAL OF RECORD:NOTIC

E: THIS

ARCHIT

ECTURAL A

ND E

NGIN

EERIN

G D

RAW

ING IS G

IVEN IN C

ONFID

ENCE A

ND S

HALL B

E U

SED O

NLY P

URSUANT T

O T

HE A

GREEMENT W

ITH T

HE A

RCHIT

ECT. NO O

THER U

SE, DIS

SEMIN

ATIO

N, OR D

UPLIC

ATIO

N M

AY B

E M

ADE W

ITHOUT P

RIO

R W

RIT

TEN

CONSENT O

F T

HE A

RCHIT

ECT. ALL C

OMMON L

AW

RIG

HTS O

F C

OPYRIG

HT A

ND O

THERW

ISE A

RE H

EREBY S

PECIF

ICALLY R

ESERVED.

CLIENT

2221 Schrock RoadColumbus, Ohio 43229-1547p 614.898.7100f 614.898.7570www.msconsultants.com

PROJECT

10/5

/202

1 3:

51:1

8 PM

PLUMBING SPECIFICATIONS

P002

GSG

JASON E. CHRISTOFF - PE No.PE.0056074EXP DATE: 10/31/2021

10/04/2021

MRM

10/04/2021

62-40487-06

HCA HEALTH ONE, LLC4500 E 9TH AVESTE 160DENVER, CO 80220

QUESTDIAGNOSTICS

# DATE DESCRIPTION

FCO

WAITINGROOM100

SPECIALSERVICES

01

PATIENTENCOUNTER

02

PATIENTENCOUNTER

03

SUPPLY103

SPECIMENCONSOLIDATION

104

EMPLOYEEBREAKROOM106

HALL101

UNISEXTOILET

107

UNISEXTOILET

105

JANITOR/STORAGE

102

LAV-1LAV-1FD-1WC-1 FD-1 WC-1

LAV-2

SK-2SK-1

V

V

SAN

V

SAN SAN

FD-1

V V VVVVV

1

3

33

2 V

SHEET

SHEET TITLE

ISSUE DATE

DRAWN BY

CHECKED BYAPPROVED BY

PROJECT NO.

REVISION

PROFESSIONAL OF RECORD:NOTIC

E: THIS

ARCHIT

ECTURAL A

ND E

NGIN

EERIN

G D

RAW

ING IS G

IVEN IN C

ONFID

ENCE A

ND S

HALL B

E U

SED O

NLY P

URSUANT T

O T

HE A

GREEMENT W

ITH T

HE A

RCHIT

ECT. NO O

THER U

SE, DIS

SEMIN

ATIO

N, OR D

UPLIC

ATIO

N M

AY B

E M

ADE W

ITHOUT P

RIO

R W

RIT

TEN

CONSENT O

F T

HE A

RCHIT

ECT. ALL C

OMMON L

AW

RIG

HTS O

F C

OPYRIG

HT A

ND O

THERW

ISE A

RE H

EREBY S

PECIF

ICALLY R

ESERVED.

CLIENT

2221 Schrock RoadColumbus, Ohio 43229-1547p 614.898.7100f 614.898.7570www.msconsultants.com

PROJECT

10/5

/202

1 3:

51:2

2 PM

PLUMBING SANITARY PLAN

P101

GSG

JASON E. CHRISTOFF - PE No.PE.0056074EXP DATE: 10/31/2021

10/04/2021

MRM

10/04/2021

62-40487-06

HCA HEALTH ONE, LLC4500 E 9TH AVESTE 160DENVER, CO 80220

QUESTDIAGNOSTICS

PLUMBING KEYNOTES1 APPROXIMATE LOCATION OF EXISTING SANITARY MAIN SHOWN FOR REFERENCE

ONLY. CONTRACTOR TO COORDINATE AND FIELD VERIFY EXACT LOCATION,ROUTING, DEPTH AND DIRECTION OF FLOW WITH LANDLORD REPRESENTATIVEPRIOR TO PIPING ROUGH IN. CONTRACTOR TO COORDINATE AND FIELD VERIFYEXACT CONNECTION POINT OF NEW PIPING WITH LANDLORD REPRESENTATIVE.

3 CONTRACTOR TO PROVIDE TRAP PRIMER TO FLOOR DRAIN.4 CONNECT TO EXISTING SANITARY VENT SYSTEM. COORDINATE AND FIELD VERIFY

EXACT ROUTING AND CONNECTION POINT WITH GC AND LANDLORDREPRESENTATIVE.

GENERAL NOTESA ROUTE SANITARY PIPING BELOW FLOOR. ALL EXISTING SANITARY PIPING BELOW

FLOOR IS TO REMAIN FOR FUTURE USE UNLESS NOTED OTHERWISE. ANY PIPINGTHAT EXTENDS UP ABOVE FLOOR SHALL BE CUT AND CAPPED. SAW CUT EXISTINGSLAB AS REQUIRED TO INSTALL NEW UNDERFLOOR SANITARY PIPING BELOWFLOOR. IF EXISTING SANITARY PIPING BELOW FLOOR PRESENTS ANYOBSTRUCTIONS, THAT PIPING SHALL BE REMOVED TO THE EXTENT NEEDED TOCOMPLETE NEW WORK.

B ROUTE VENT PIPING ABOVE CEILING. CONTRACTOR TO FIELD COORDINATE EXACTROUTING WITH DUCTWORK, SUPPLY PIPING AND EQUIPMENT FOR COMPLETESYSTEM. CONTRACTOR TO NOTIFY ENGINEER OF ALL CONFLICTS PRIOR TOINSTALLATION.

C REFER TO ISOMETRIC DIAGRAM ON SHEET P-601 FOR PIPE SIZES.

PLAN NORTH

# DATE DESCRIPTION

1/4" = 1'-0"1 SANITARY PLAN

WAITINGROOM100

SPECIALSERVICES

01

PATIENTENCOUNTER

02

PATIENTENCOUNTER

03

SUPPLY103

SPECIMENCONSOLIDATION

104EMPLOYEEBREAKROOM106

JANITOR/STORAGE

102

HALL101

UNISEXTOILET

107

UNISEXTOILET

105

LAV-2

F-2

WC-1

LAV-1F-1

LAV-1F-1

WC-1

SK-1F-2

SK-2F-2

1"ø DCW1/2"ø DHW

1/2"ø DHWR1/2"ø DCW 3/4"ø DHW

3/4"ø DHWR1"ø DCW

3/4"ø DHW3/4"ø DHWR1"ø DCW

1/2"ø DHW1/2"ø DHWR

1/2"ø DCW1/2"ø DCW1/2"ø DHWR1/2"ø DHW

2 2

4 4

1

3

1"ø DHWR1"ø DHW

3/4"ø DHW3/4"ø DHWR

1"ø DCW

US-1

SHEET

SHEET TITLE

ISSUE DATE

DRAWN BY

CHECKED BYAPPROVED BY

PROJECT NO.

REVISION

PROFESSIONAL OF RECORD:NOTIC

E: THIS

ARCHIT

ECTURAL A

ND E

NGIN

EERIN

G D

RAW

ING IS G

IVEN IN C

ONFID

ENCE A

ND S

HALL B

E U

SED O

NLY P

URSUANT T

O T

HE A

GREEMENT W

ITH T

HE A

RCHIT

ECT. NO O

THER U

SE, DIS

SEMIN

ATIO

N, OR D

UPLIC

ATIO

N M

AY B

E M

ADE W

ITHOUT P

RIO

R W

RIT

TEN

CONSENT O

F T

HE A

RCHIT

ECT. ALL C

OMMON L

AW

RIG

HTS O

F C

OPYRIG

HT A

ND O

THERW

ISE A

RE H

EREBY S

PECIF

ICALLY R

ESERVED.

CLIENT

2221 Schrock RoadColumbus, Ohio 43229-1547p 614.898.7100f 614.898.7570www.msconsultants.com

PROJECT

10/5

/202

1 3:

51:2

7 PM

PLUMBING SUPPLY PLAN

P102

GSG

JASON E. CHRISTOFF - PE No.PE.0056074EXP DATE: 10/31/2021

10/04/2021

MRM

10/04/2021

62-40487-06

HCA HEALTH ONE, LLC4500 E 9TH AVESTE 160DENVER, CO 80220

QUESTDIAGNOSTICS

GENERAL NOTESA ROUTE DOMESTIC SUPPLY PIPING ABOVE CEILING. CONTRACTOR TO FIELD

COORDINATE EXACT ROUTING WITH OTHER DISCIPLINES. CONTRACTOR TO NOTIFYENGINEER OF ALL CONFLICTS PRIOR TO INSTALLATION.

PLUMBING KEYNOTES1 CONNECT TO EXISTING LANDLORD DOMESTIC COLD WATER SUPPLY, HOT WATER

SUPPLY AND HOT WATER RETURN LINES. COORDINATE EXACT ROUTING ANDCONNECTION POINT IN FIELD WITH GC AND LANDLORD REPRESENTATIVE. PROVIDESHUTOFF ABOVE CEILING IN ACCESSIBLE LOCATION.

2 TESTING RESTROOM - PROVIDE 3/4" DCW LINE WITH SHUTOFF AND SOLENOIDVALVE, 1/2" DHW LINE WITH SHUTOFF AND SOLENOID VALVE, AND 1/2" DHWR LINEWITH CIRCUIT SETTER AND CHECK VALVE TO SERVE TESTING RESTROOM. ROUTE1/2" DCW, 1/2" DHW, AND 1/2" DHWR DOWN IN WALL TO THERMOSTATIC MIXINGVALVE (ASSE 1070) AND LAVATORY FAUCET. ROUTE 1/2" DCW DOWN IN WALL TOWATER CLOSET. SHUTOFF VALVES, CIRCUIT SETTERS, CHECK VALVES, ANDSOLENOIDS TO BE LOCATED ABOVE CEILING OUTSIDE OF RESTROOM INACCESSIBLE LOCATIONS. LOCATE VALVES AS TO LIMIT LENGTH OF SUPPLY PIPINGBETWEEN VALVE AND FIXTURES. SOLENOIDS ARE TO BE CONTROLLED VIAELECTRICAL CONTRACTOR PROVIDED WALL SWITCH. SEE ELECTRICAL DRAWINGSFOR MORE INFORMATION.

3 UTILITY SINK - PROVIDE 1/2" DCW LINE WITH SHUTOFF VALVE AND 1/2" DHW LINEWITH SHUTOFF VALVE TO PLUMBING FIXTURE. ROUTE 1/2" DCW AND 1/2" DHWDOWN IN WALL TO THERMOSTATIC MIXING VALVE AND FAUCET. SHUTOFF VALVESTO BE LOCATED IN ACCESSIBLE LOCATIONS.

4 SINK/LAVATORY - PROVIDE 1/2" DCW LINE WITH SHUTOFF VALVE, 1/2" DHW LINEWITH SHUTOFF VALVE, AND 1/2" DHWR LINE WITH CIRCUIT SETTER TO PLUMBINGFIXTURE. ROUTE 1/2" DCW, 1/2" DHW, AND 1/2" DHWR DOWN IN WALL TOTHERMOSTATIC MIXING VALVE AND FAUCET. SHUTOFF VALVES AND CIRCUITSETTERS TO BE LOCATED ABOVE CEILING IN ACCESSIBLE LOCATIONS.

PLAN NORTH

# DATE DESCRIPTION

1/4" = 1'-0"1 SUPPLY PLAN

FLOW

FINISHED FLOOR

CLEANOUT COVER

CLEANOUT PLUG

CAULKING FERRULE

COUNTERSUNK SCREW

CONCRETE ANCHORSFINISH FLOOR

1/2" COPPER TUBING TYPE LTO TRAP PRIMER

1/2" C.W.

TEE.

AG-500 AIRGAP FITTING

1/2" C.W. 1/2" SOV

C.W. LINEABOVE CEILING

P-TRAP

WASTE LINE

FINISH FLOOR

FLOOR DRAIN

15 1

/2"

1/2" 'K' COPPER TUBING TRAP SUPPLIES. ROUTE BELOW FLOOR DRAIN TRAPS. SEE PLAN AND RISERS.

DISTRIBUTION UNIT #DU-3

SECURE DISTRIBUTION UNIT TOSTRUCTURAL WHERE STUDSDO-NOT GO UP PAST CEILING.

TRAP PRIMER VALVE WITHINTEGRAL BACKFLOWPREVENTER AND VACUUMBREAKER PORT.PRECISION PLUMBINGPRODUCTS #PR-500

SECURE DISTRIBUTIONUNIT TO BACKING SHEETBETWEEN STUDS.

TAPPED P-TRAP ADAPTER, PPP INC. OR EQUAL

COORDINATE CONNECTION TO EXISTINGSANITARY MAIN IN FIELD.

FCO

LAV-2

FD-1

FD-1

FD-1

WC-1

LAV-1

LAV-1

WC-1

SK-1

SK-2

2"ø V

1 1/2"ø V

1 1/2"ø V

1 1/2"ø V

2"ø V

1 1/2"ø V

2"ø V

1 1/

2"ø

V

1 1/2"ø V

2"ø V

1 1/2"ø V

4"ø SAN

4"ø SAN 3"ø SAN

2"ø SAN

2"ø SAN

3"ø SAN

1 1/2"ø SAN

1 1/2"ø SAN

COORDINATE CONNECTIONTO EXISTING SANITARY VENT SYSTEM.

2"ø V

SHEET

SHEET TITLE

ISSUE DATE

DRAWN BY

CHECKED BYAPPROVED BY

PROJECT NO.

REVISION

PROFESSIONAL OF RECORD:NOTIC

E: THIS

ARCHIT

ECTURAL A

ND E

NGIN

EERIN

G D

RAW

ING IS G

IVEN IN C

ONFID

ENCE A

ND S

HALL B

E U

SED O

NLY P

URSUANT T

O T

HE A

GREEMENT W

ITH T

HE A

RCHIT

ECT. NO O

THER U

SE, DIS

SEMIN

ATIO

N, OR D

UPLIC

ATIO

N M

AY B

E M

ADE W

ITHOUT P

RIO

R W

RIT

TEN

CONSENT O

F T

HE A

RCHIT

ECT. ALL C

OMMON L

AW

RIG

HTS O

F C

OPYRIG

HT A

ND O

THERW

ISE A

RE H

EREBY S

PECIF

ICALLY R

ESERVED.

CLIENT

2221 Schrock RoadColumbus, Ohio 43229-1547p 614.898.7100f 614.898.7570www.msconsultants.com

PROJECT

10/5

/202

1 3:

51:3

8 PM

PLUMBING SCHEDULES ANDDETAILS

P601

GSG

JASON E. CHRISTOFF - PE No.PE.0056074EXP DATE: 10/31/2021

10/04/2021

MRM

10/04/2021

62-40487-06

HCA HEALTH ONE, LLC4500 E 9TH AVESTE 160DENVER, CO 80220

QUESTDIAGNOSTICS

PLUMBING FIXTURE SCHEDULE

MARK DESCRIPTION

MINIMUM PIPING CONNECTIONS FLOW RATE MFR. CATALOG NUMBER

PLUMBING REMARKSWASTE TRAP VENT HW CW WATERFLUSHRATE MANUFACTURER MODEL

FD-1FD-1 MEDIUM-DUTY ADJUSTABLE FLOOR DRAIN 3" 3" 1 1/2" ZURN FD-2340 PROVIDE WITH TRAP PRIMER CONNECTION

LAV-1F-1 SINGLE CONTROL CENTERSET FAUCET 1/2" 1/2" 0.50 GPM AMERICAN STANDARD 6114.111.002

LAV-1 WALL-HUNG LAVATORY 1 1/4" 1 1/4" 1 1/4" AMERICAN STANDARD LUCERNE 0355.012LAV-2

F-2 TWO-HANDLE WIDESPREAD LAVATORY FAUCET 1/2" 1/2" 1.50 GPM AMERICAN STANDARD 6540.278.002LAV-2 WALL-HUNG LAVATORY 1 1/4" 1 1/4" 1 1/4" AMERICAN STANDARD DECORUM 9024.008EC

SK-1F-2 TWO-HANDLE WIDESPREAD LAVATORY FAUCET 1/2" 1/2" 1.50 GPM AMERICAN STANDARD 6540.278.002 FURNISHED BY OWNER. INSTALLED BY PLUMBING

CONTRACTOR.SK-1 STAINLESS STEEL SINGLE BOWL SINK 1 1/2" 1 1/2" 1 1/2" PROFLO PFSR2521553C FURNISHED BY OWNER. INSTALLED BY PLUMBING

CONTRACTOR.SK-2

F-2 TWO-HANDLE WIDESPREAD LAVATORY FAUCET 1/2" 1/2" 1.50 GPM AMERICAN STANDARD 6540.278.002 FURNISHED BY OWNER. INSTALLED BY PLUMBINGCONTRACTOR.

SK-2 STAINLESS STEEL SINGLE BOWL SINK 1 1/2" 1 1/2" 1 1/2" PROFLO PFSR17196 FURNISHED BY OWNER. INSTALLED BY PLUMBINGCONTRACTOR.

US-1US-1 LAUNDRY/UTILITY TUB 1 1/2" 1 1/2" 1 1/2" 1/2" 1/2" 3.00 GPM MUSTEE 12C FAUCET, AERATOR AND HOSE END CONNECTION PROVIDED

WITH UTILITY SINK 12C.WC-1

WC-1 PRESSURE-ASSISTED TOILET W/ LOCKABLE TANK (ADA) 4" 2" 1/2" 1.6 AMERICAN STANDARD 2467.016 PROVIDE WITH SEAT (AMERICAN STANDARD #5324.019)

N.T.S.6 FLOOR CLEANOUT DETAIL

N.T.S.4 FLOOR DRAIN DETAIL

N.T.S.5 TRAP PRIMER DETAIL

N.T.S.2 SANITARY ISOMETRIC

# DATE DESCRIPTION

AV

D

D

MAX

S

R

HB

M

M

P

PS

M

S

T

REFRIGERANT DISCHARGE LINE

REFRIGERANT LIQUID LINE

REFRIGERANT SUCTION LINE

REFRIGERANT PIPING

PIPING, ANCHOR INTERMEDIATE

PIPING, AUTOMATIC AIR VENT

PIPING, BALL VALVE

PIPING, BLOW OFF STRAINER

PIPING, BUTTERFLY VALVE

PIPING, DIELECTRIC UNION

PIPING, FLANGED GLOBE VALVE (PLAN)

PIPING, FLANGED OUTLET DOWN TEE

PIPING, FLANGED OUTLET UP TEE

PIPING, FLANGED SIDE OUTLET TEE

PIPING, FLANGED SIDE OUTLET UP TEE

PIPING, FLANGED TURNED DOWN ELBOW

PIPING, FLANGED TURNED UP ELBOW

PIPING, FLANGED UNION

PIPING, GATE VALVE (OR OTHER TYPE VALVE WHERE SPECIFIED)

PIPING, GLOBE VALVE

PIPING, CHECK VALVE

PIPING, 3-WAY VALVE (MANUAL)

PIPING, 3-WAY CONTROL VALVE

PIPING, 3-WAY PNEUMATIC CONTROL VALVE WITH POSITIONER

PIPING, RELIEF VALVE

PIPING, PRESSURE REDUCING VALVE

PIPING, CONTROL VALVE-ELECTRONIC

PIPING, CONTROL VALVE-SOLENOID

PIPING, STRAINER

PIPING, THERMOMETER & SEPARABLE SOCKET

PIPING, PRESSURE GAUGE W/GAUGE COCK

PIPING, DIAPHRAM VALVE

PIPING, ANGLE VALVE-VERTICAL

PIPING, BALANCING VALVE

PIPING, CIRCUIT SETTER

PIPING, PLUG VALVE

PIPING, NEEDLE VALVE

GLYCOL SUPPLY

GLYCOL RETURN

PIPING, UNION

PIPE RUN UP

PIPE RUN DOWN

PIPE DROP

FLOW DIRECTION

PITCH DIRECTION (D-DOWN, R-RISE)

PIPING, GUIDE

PIPING, EXPANSION JOINT

PIPING, EXPANSION LOOP

PIPING, FLEXIBLE CONNECTION

PIPING, REDUCER, CONCENTRIC

PIPING, REDUCER, ECCENTRIC

PIPING, MANUAL AIR VENT

PIPING, PRESSURE & TEMPERATURE TAP

PIPING, STEAM TRAP

PIPING, HOSE BIBB

AIR DISTRIBUTION, DAMPER CONTROL, ELECTRIC OPERATED

HVAC CONTROL, FLANGED MOTOR OPERATED GLOBE VALVE

HVAC CONTROL, PRESSURE STAT

HVAC CONTROL, PRESSURE SWITCH, TYPE 1

HVAC CONTROL, SCREWED MOTOR OPERATED GLOBE VALVE

HVAC CONTROL, SOLENOID VALVE

HVAC CONTROL, THERMOSTAT, ELECTRIC

12

12

1

12

2

AC AIR CONDITION (-ED, -ER, -ING)ACC AIR COOLED CONDENSERACCU AIR COOLED CONDENSING UNIT

AFF ABOVE FINISHED FLOORAFMS AIR FLOW MEASURING STATIONAHU AIR HANDLING UNITAI ANALOG INPUTAO ANALOG OUTPUTAP ACCESS PANELARCH ARCHITECT (-URAL, -URE)ATM ATMOSPHEREAUX AUXILIARY

BC BOOSTER COILBDD BACK DRAFT DAMPERBFP BACKFLOW PREVENTERBHP BRAKE HORSEPOWER, BOILER HORSEPOWERBOD BOTTOM OF DUCTBOP BOTTOM OF PIPEBTU BRITISH THERMAL UNITBTUH BRITISH THERMAL UNITS PER HOUR

CA COMPRESSED AIRCAP CAPACITYCB CATCH BASINCC CABLE CHASECFM CUBIC FEET PER MINUTECH CABINET HEATERCHWR CHILLED WATER RETURNCHWS CHILLED WATER SUPPLYCI CAST IRONCL CLASSCO CLEANOUT, CARBON MONOXIDECOL COLUMNCOMP COMPRESSORCOND CONDENS (-ER, -ING, -ATION, -ATE)CONN CONNECT (-ION)CONT CONTINU (-E, -ATION, -OUS)CP CONTROL PANEL, CONDENSATE PUMPCR CONDENSATE RETURN

CS CIRCUIT SETTERCT COOLING TOWERCV CONSTANT VOLUME, CONTROL VALVECv COEFFICIENT, VALVE FLOWCW COLD WATERCWP COLD WATER PUMPCWR COLD WATER RETURN

CU CONDENSING UNIT

DB DRY-BULBDD DUCT DETECTORDDC DIRECT DIGITAL CONTROLDI DIGITAL INPUTDIA DIAMETERDIV DIVISIONDN DOWNDO DIGITAL OUTPUT

DP DEW POINTDS DOWNSPOUT, DUCT SILENCERDWG DRAWINGDX DIRECT EXPANSION

EA EXHAUST AIR

EAT ENTERING AIR TEMPERATUREEF EXHAUST FANEQUIP EQUIPMENTERU ENERGY RECOVERY UNIT

ET EXPANSION TANKEWC ELECTRIC WATER COOLEREWT ENTERING WATER TEMPERATUREEXH EXHAUSTEXP EXPANSION

FA FIRE ALARMFAP FIRE ALARM PANELFAG FIRE ALARM GONGFCO FLOOR CLEANOUTFCU FAN COIL UNITFD FIRE DAMPER, FLOOR DRAINFDC FIRE DEPARTMENT CONNECTIONFE FIRE EXTINGUISHERFEC FIRE EXTINGUISHER CABINETFH FIRE HOSEFHC FIRE HOSE CABINETFHR FIRE HOSE RACKFHYR FIRE HYDRANTFIXT FIXTUREFLA FULL LOAD AMPSFOR FUEL OIL RETURNFOS FUEL OIL SUPPLYFPM FEET PER MINUTEFPS FEET PER SECONDFS FLOW SWITCHFST FREEZE STATFT FEETFTR FIN TUBE RADIATION

GC GENERAL CONTRACTORGPH GALLONS PER HOURGPM GALLONS PER MINUTE

HB HOSE BIBHC HEATING COILHD HEADHEV HAND EXPANSION VALVEHG HEAT GAIN, HOT GAS, MECURYHP HORSEPOWER, HIGH POINTHT HEIGHTHVAC HEATING/VENTILATION/AIR CONDITIONINGHW HOT WATERHWP HOT WATER PUMPHWR HOT/HYDRONIC WATER RETURNHWS HOT/HYDRONIC WATER SUPPLYHYD HYDRAULICHZ HERTZ

IN INCHES

KW KILOWATTS

L LENGTHLAT LEAVING AIR TEMPERATURELAV LAVATORYLBS POUNDSLF LINEAR FEETLH LATENT HEATLHG LATENT HEAT GAINLPS LOW PRESSURE STEAMLTD LEAST TEMPERATURE DIFFERENCELVG LEAVINGLWT LEAVING WATER TEMPERATURE

M METER, MOTORMA MIXED AIRMAT MIXED AIR TEMPERATURE

MAX MAXIMUMMBH BRITISH THERMAL UNITS (THOUSANDS)MCC MOTOR CONTROL CENTERMD MOTORIZED DAMPERMIN MINUTES, MINIMUMMP MEDIUM PRESSUREMPC MEDIUM PRESSURE CONDENSATEMPS MEDIUM PRESSURE STEAMMTD MEAN TEMPERATURE DIFFERENCEMU MAKE-UPMVD MOTOR-OPERATED VOLUME DAMPERMWP MAXIMUM WORKING PRESSURE

N/A NOT APPLICABLENC NORMALLY CLOSED, NOISE CRITERIANG NATURAL GASNIC NOT IN CONTRACTNK NECKNO NORMALLY OPEN, NUMBER

OA OUTSIDE AIROBD OPPOSED BLADE DAMPEROD OUTSIDE DIAMETEROS&Y OUTSIDE SCREW & YOKE (VALVE)OV OUTLET VELOCITYOW OPEN WASTE

P'WIRED PRE-WIREDPBD PARALLEL BLADE DAMPERPCF POUNDS PER CUBIC FOOTPC PUMPED CONDENSATEPD PRESSURE DROPP-E PNEUMATIC TO ELECTRICPH PHASEPHC PREHEAT COILPI PRESSURE INDICATORPKG PACKAGEPNEU PNEUMATICPNL PANELPPM PARTS PER MILLIONPRESS PRESSUREPRV PRESSURE REDUCING VALVEPSI POUNDS PER SQUARE INCHPSIG PRESSURE PER SQUARE INCH GAUGEPSV PILOT SOLENOID VALVE

QT QUARTQTY QUANTITY

RA RETURN AIRRAD RADIAT(-E, -ION, -OR)

RD RETURN DUCTRECIRC RECIRCULATEREFRIG REFRIGERANTREG REGISTERRET RETURNRH RELATIVE HUMIDITYRHC REHEAT COILRL REFRIGERANT LIQUIDRPBP REDUCED PRESSURE BACKFLOW PREVENTERRPM REVOLUTIONS PER MINUTERPS REVOLUTIONS PER SECONDRR REFRIGERANT RELIEFRS REFRIGERANT SUCTION

RV ROOF VENTILATOR

S/M SHEET METALSA SUPPLY AIRSAT SATURAT(-E, -ED, -ION), SUPPLY AIR TEMPERATURESC SUPPLY CEILING

SD SUPPLY DUCTSF SQUARE FEETSH SENSIBLE HEATSHG SENSIBLE HEAT GAINSHT SHEETSP STATIC PRESSURESPGR SPECIFIC GRAVITYSPKLR SPRINKLERSPT STATIC PRESSURE TRANSMITTERSPVOL SPECIFIC VOLUMESS STAINLESS STEEL, SERVICE SINKSTD STANDARDSYS SYSTEM

T THERMOSTAT, TANKTAB TESTING, ADJUSTING AND BALANCINGTAU TOP ANGULAR UPTCC TEMPERATURE CONTROL CONTRACTORTCP TEMPERATURE CONTROL PANELTD TEMPERATURE DIFFERENCETI TEMPERATURE INDICATORTR TRANSFERTSP TOTAL STATIC PRESSURETT TEMPERATURE TRANSMITTERTYP TYPICAL

U HEAT TRANSFER COEFFICIENTUB UP BLASTUH UNIT HEATERUNO UNLESS NOTED OTHERWISEUR URINAL

V VENT, VOLTSVAC VACUUMVAV VARIABLE AIR VOLUMEVD MANUAL VOLUME DAMPER

VEL VELOCITYVLV VALVEVPT VELOCITY PRESSURE TRANSMITTERVTR VENT THRU ROOF

W WASTE, WIDTH, WATTSW/ WITHWC WATER CLOSETW/O WITHOUTWB WET-BULBWC WATER COLUMN

WH WATER HEATER, WALL HUNGWTR WATER

MECHANICAL ABBREVIATIONS

GENERAL SYMBOLS

HVAC PIPING SYMBOLS HVAC DUCTWORK SYMBOLS

KEYNOTE TAG1. DEMOLITION KEYNOTE2. NEW WORK KEYNOTE

MECHANICAL EQUIPMENT TAG1. MECHANICAL EQUIPMENT TYPE2. EQUIPMENT NUMBER

DETAIL TAG1. DETAIL NUMBER2. SHEET NUMBER

SECTION TAG1. SECTION NUMBER2. SHEET NUMBER

LINETYPE INDICATES NEW DUCTWORK AND PIPING

LINETYPE INDICATES EXISTINGDUCTWORK AND PIPING TO BE REMOVED

INSTRUMENTATION AND CONTROL SYMBOLS

RD

RL

RS

GS

GR

GS

GR

AD AIR DRYER

DOAS DEDICATED OUTDOOR AIR-HANDLING SYSTEM

MAU MAKE-UP AIR UNIT

RTD RESISTANCE TEMPERATURE DETECTOR

CWS COLD WATER SUPPLY

ESP EXTERNAL STATIC PRESSUREEUH ELECTRIC UNIT HEATER

E-P ELECTRIC TO PNEUMATIC

IRH INFARED HEATER

RTU ROOF TOP UNIT

VEF VEHICLE EXHAUST FAN

WEF WELDING EXHAUST FAN

AI ANALOG INPUTAO ANALOG OUTPUTCONO CARBON MONOXIDE / NITROGEN OXIDECT CURRENT TRANSDUCER

DO DIGITAL OUTPUTEF DPR EXHAUST FAN DAMPER

DI DIGITAL INPUT

EF EN EXHAUST FAN ENABLE RELAY

EUH ELECTRIC UNIT HEATER ENABLE RELAYF EN FAN ENABLE RELAYOA DPR OUTSIDE AIR DAMPER

TEMPERATURE CONTROL ABBREVIATIONS

RC RETURN CEILING

SD SMOKE DETECTORSCFM CFM, STANDARD CONDITIONS

CRAC COMPUTER ROOM AIR CONDITIONER

M

M

S

HVAC CONTROL, THREE-WAY ELECTRIC MOTOR CONTROLLED VALVE

HVAC CONTROL, VALVE ACTUATOR ELECTRIC MOTOR

HVAC CONTROL, VALVE ACTUATOR ELECTRIC SOLENOID

C LOCAL MAKE-UP AIR, ENERGY RECOVERY UNIT CONTROLLER

S CARBON MONOXIDE / NITROGEN OXIDE SENSOR

M MOTOR STARTER

FSD

VAVTU

POINT OF CHANGE IN DUCT CONSTRUCTION(BY STATIC PRESSURECLASS)DUCT (1ST FIGURE, SIDESHOWN; SECOND FIGURE, SIDE NOT SHOWN)

20"x12"

ACOUSTICAL LININGDUCT DIMENSIONS FORNET FREE AREA

DIRECTION OF FLOW

DUCT SECTION (SUPPLY) S 30"x12"

DUCT SECTION (RETURN) R30"x12"

INCLINED RISE (R) ORDROP (D) ARROW INDIRECTION OF AIR FLOW

R

TRANSITIONS: F.O.T.FLAT ON TOP OR F.O.B.FLAT ON BOTTOM

STANDARD BRANCH FORSUPPLY AND RETURN(NO SPLITTER) 45º INLET

RS

WYE JUNCTION

VOLUME DAMPERMANUAL OPERATION

AUTOMATIC DAMPERSMOTOR OPERATED SEC MOD

ACCESS DOOR (AD)ACCESS PANEL (AP)

APAD

FIRE DAMPER:SHOW VERTICALPOS.SHOW HORIZ. POS. AD

FD

SMOKE DAMPERAD S

HEAT STOP -

CEILING DAMPER - C

RADIATION DAMPER - R

TURNING VANES(TYPE AS SPECIFIED)

FLEXIBLE DUCT

FLEXIBLE CONNECTION

GOOSENECK HOOD (COWL)

BACK DRAFT DAMPERBDD

SQUARE TO ROUNDTAKEOFF

ROUND DUCT BREAKLINE

ROUND DROP TODIFFUSER

DIE STAMPED 90º ELBOW

DIE STAMPED 45º ELBOW

FIVE PIECE 90º ELBOW

THREE PIECE 45º ELBOW

WYE 45º DIVERGING TEE

DIVERGING TEE

DIVERGING CONICAL CROSS

DIVERGING CROSS

MECH. EQUIPMENT TAG

MOTORIZED DAMPER

THERMOSTAT CONTROL

DUCT SECTION(EXHAUST)

E30"x12"

VOLUME DAMPERMANUAL OPERATION

VARIABLE AIR VOLUME BOX W/REHEAT

COMBINATION FIRE SMOKE DAMPER

HUMIDITY SENSOR

DUCT SHOE WITH DAMPER

SUPPLY DUCT UP

SUPPLY DUCT DOWN

RETURN OR EXHAUST DUCT UP

RETURN OR EXHAUST DUCT DOWN

SUPPLY AIR TERMINAL

RETURN AIR TERMINAL

ROUND SUPPLY AIR TERMINAL

SQUARE TO ROUND TRANSITION

VARIABLE AIR VOLUME BOX

VARIABLE AIR VOLUME BOX W/REHEAT

BOOSTER COIL, DUCT MOUNTED

TRANSFER DUCT W/REGISTERS

DOOR TRANSFER GRILLE

M

AHU-#

1 2 - 3 4

TAHU-#

H

HVAC TERMINAL TAG1. TERMINAL FUNCTION

(S-SUPPLY, R-RETURN, E-EXHAUST, T-TRANSFER)2. TERMINAL TYPE

(C-CEILING, D-DUCT, W-WALL)3. NUMBER4. AIRFLOW CFM

1. PROVIDE ALL NEW DUCTWORK, DAMPERS, DIFFUSERS, GRILLES,DUCTWORK INSULATION AND DUCTWORK APPURTENANCES ASREQUIRED FOR A COMPLETE SYSTEM.

2. INSTALL ALL EQUIPMENT AND COMPONENTS IN ACCORDANCEWITH MANUFACTURER'S PUBLISHED INSTALLATION INSTRUCTIONSWITH RECOMMENDED LOCATIONS TO ENSURE THAT THESPECIFIED PRODUCTS SERVE THE INTENDED FUNCTION. MAINTAINPROPER CLEARANCES FOR SERVICE, INSPECTION ANDMAINTENANCE OF EQUIPMENT.

3. PERFORM ALL DEMOLITION WORK IN A NEAT, SKILLFUL ANDCAREFUL MANNER TERMINATING DEMOLITION AT EXISTINGCONSTRUCTION TO REMAIN IN A MANNER THAT SHALL LEAVESTRAIGHT AND CLEAN BREAK LINES. USE PRECAUTIONS ANDMETHODS NOT TO DAMAGE OR DEFACE EXISTING CONSTRUCTION.

4. ALL CONTRACTORS SHALL COORDINATE AND SCHEDULE THEIRWORK WITH OWNER AND ALL OTHER TRADES TO MINIMIZE THEINTERFERENCE WITH THE OPERATION OF THE BUILDING. ALLCONTRACTORS SHALL TAKE THE NECESSARY PRECAUTIONS TOPROTECT THE OWNER BUILDING AND EQUIPMENT AT ALL TIMESDURING CONSTRUCTION.

5. UNDER NO CIRCUMSTANCES SHALL ANY OF THE EXISTING FANSYSTEMS, HEATING OR CHILLED WATER SYSTEMS BE SHUT DOWNWITHOUT PRIOR COORDINATION AND APPROVAL OF THE OWNER.

6. ALL PIPING, DUCTWORK AND MECHANICAL EQUIPMENTSCHEDULED FOR DEMOLITION SHALL BECOME THE PROPERTY OFTHE CONTRACTOR (UNLESS SPECIFICALLY NOTED) AND SHALL BEREMOVED FROM THE PREMISES AS SOON AS POSSIBLE.

7. THE WORD "PROVIDE" MEANS TO FURNISH AND INSTALL.

8. THE WORD "FURNISH" MEANS TO SUPPLY TO JOB SITE ONLY.

9. WHEN INSTALLING PIPING OR MECHANICAL EQUIPMENT UNDERTHIS CONTRACT, THE CONTRACTOR SHALL CONFER WITH OTHERCONTRACTORS TO AVOID ANY CONFLICTS BETWEEN THE TRADES.THE CONTRACTOR SHALL BE RESPONSIBLE, AT HIS OWN EXPENSE,FOR THE REMOVAL AND RE-INSTALLATION OF ANY PART OF HISWORK IF SAME WAS INSTALLED WITHOUT CONSULTING THE OTHERTRADES.

10. SEAL ALL EDGES OF INSULATION ON DUCTWORK, PIPING ORDUCTWORK OR PLENUMS. REPAIR AND PATCH ALL INSULATION TOMATCH EXISTING AT AREAS WHERE NEW CONNECTIONS HAVEBEEN MADE TO EXISTING PIPING, DUCTWORK OR EQUIPMENT.

11. SEE ELECTRICAL AND ARCHITECTURAL DRAWINGS FORADDITIONAL WORK TO BE COORDINATED WITH THESE DRAWINGS.COORDINATE DUCTWORK AND DIFFUSER/GRILLE INSTALLATIONWITH SUSPENSION SYSTEM INCLUDING THREADED RODS, ETC.MUST NOT BLOCK OR INHIBIT THE DIFFUSER DISCHARGE AIRFLOWPATTERNS.

12. UNDER NO CONDITION, SHOULD ELECTRICAL CONDUITS, FEEDERSAND/OR ANY ON-LINE SERVICE BE DISTURBED, MOVED ORINTERRUPTED UNLESS SPECIFICALLY REQUIRED TO INSTALL NEWDUCTWORK/EQUIPMENT. IT SHALL BE THE RESPONSIBILITY OF THEMECHANICAL CONTRACTOR TO COORDINATE THE RELOCATION OFEXISTING CONDUITS WHERE REQUIRED, WITH THE ELECTRICALCONTRACTOR, TEMPERATURE CONTROLS CONTRACTOR AND THEOWNER'S REPRESENTATIVE. IF RELOCATION IS REQUIRED, ITSHALL BE DONE AT NO ADDITIONAL COST TO THE OWNER.

13. AIR BALANCING AS INDICATED SHALL BE PERFORMED BY ANINDEPENDENT TEST AND BALANCING CONTRACTOR.

14. PROVIDE MANUAL VOLUME DAMPERS AT ALL BRANCH TAKE-OFFSTO DIFFUSER AND RETURN AIR/EXHAUST GRILLES.

15. THE CONTRACTOR SHALL CLEAN-UP ALL DEBRIS CAUSED BY THEIRWORK AS IT ACCUMULATES. CONTRACTOR SHALL CLEAN ANDDAMP MOP ALL WORK AREAS AND WORK TRAFFIC AREAS AT THEEND OF EACH WORK DAY. CONTRACTORS ARE TO CONFINECONSTRUCTION TRAFFIC TO THE CONSTRUCTION AREA AS MUCHAS POSSIBLE TO MINIMIZE DUST.

17. PROVIDE ACCESS PANELS TO ALL DAMPERS AS REQUIRED.

18. ASBESTOS CONTAINING MATERIALS (ACM) IS STRICTLYPROHIBITED FROM BEING INSTALLED. SHOULD ACM BEINADVERTENTLY INSTALLED ON PROJECTS, PROPER REMOVAL,DISPOSAL AND REPLACEMENT WITH APPROVED PRODUCT SHALLBE THE SOLE RESPONSIBILITY OF THE INSTALLING CONTRACTORAT NO COST TO THE OWNER.

GENERAL NOTES

19. PROVIDE FLEXIBLE CONNECTOR FOR ALL MECHANICAL DUCTEDDEVICES.

20. BALANCE AIRFLOWS TO VALUES INDICATED. PERFORM TESTINGAND BALANCING. PROVIDE MANUAL DUCT MOUNTED BALANCINGDAMPER WHERE POSSIBLE AND ACCESS IS NOT RESTRICTED.

SHEET

SHEET TITLE

ISSUE DATE

DRAWN BY

CHECKED BYAPPROVED BY

PROJECT NO.

REVISION

PROFESSIONAL OF RECORD:NOTIC

E: THIS

ARCHIT

ECTURAL A

ND E

NGIN

EERIN

G D

RAW

ING IS G

IVEN IN C

ONFID

ENCE A

ND S

HALL B

E U

SED O

NLY P

URSUANT T

O T

HE A

GREEMENT W

ITH T

HE A

RCHIT

ECT. NO O

THER U

SE, DIS

SEMIN

ATIO

N, OR D

UPLIC

ATIO

N M

AY B

E M

ADE W

ITHOUT P

RIO

R W

RIT

TEN

CONSENT O

F T

HE A

RCHIT

ECT. ALL C

OMMON L

AW

RIG

HTS O

F C

OPYRIG

HT A

ND O

THERW

ISE A

RE H

EREBY S

PECIF

ICALLY R

ESERVED.

CLIENT

2221 Schrock RoadColumbus, Ohio 43229-1547p 614.898.7100f 614.898.7570www.msconsultants.com

PROJECT

10/5

/202

1 3:

51:0

5 PM

MECHANICAL GENERAL NOTES

M001

JPF

JASON E. CHRISTOFF - PE No.PE.0056074EXP DATE: 10/31/2021

10/04/2021

MRM

10/04/2021

62-40487-06

HCA HEALTH ONE, LLC4500 E 9TH AVESTE 160DENVER, CO 80220

QUESTDIAGNOSTICS

# DATE DESCRIPTION

PART 1 - GENERAL

1.1 SCOPEA. Furnish all materials, labor, tools, transportation, incidentals and appurtenances to complete in every detail and leave in working order all items of

work called for herein or shown on the accompanying drawings.B. Include any minor items of work necessary to provide a complete and fully operative HVAC system.C. All questions relating to this Section of Plans and Specifications should be addressed to the Construction Manager.

1.2 WORK DESCRIBED ELSEWHEREA. The Contractor for this work is referred to Bidding Requirements, General Conditions, Special Conditions, Temporary Services and other pertinent

Sections of Division I. These Sections describe work which is a part of this Contract. The following General Provisions amplify and supplement these Sections of Division I. In cases of conflicting requirements, the stipulations set forth in Divisions I supersede and must be satisfied by the Contractor.

B. Related work described elsewhere:1. High voltage wiring and disconnects by electrician.2. Gas piping by the plumber.3. Roof openings framed by General Contractor. General Contractor to furnish and install roof flashing.4. Motor starter and interlock wiring by Electrical Contractor.

1.3 GENERAL REQUIREMENTSA. Contractor must read the entire Specifications covering other branches or work. He is responsible for coordination of his work with work performed by

other trades.B. Consult all Contract Drawings and shop drawings which may affect the location of any equipment or apparatus furnished under this work and make

minor adjustments in location as necessary to secure coordination.C. The layout shown on the Drawings is based on a particular make of equipment. If another make of equipment is used which required modification or

changes of any description from the Drawings or Specifications, Contractor shall be responsible as a part of this work, for making all such modifications and changes, including those involving other trades with the cost thereof included in his bid. In such case, Contractor shall submit Drawings and Specifications prior to starting work showing all such modifications and changes. His proposal shall be subject to the approval of the Construction Manager.

D. System layout is schematic and exact locations shall be determined by structural and other conditions. This shall not be construed to mean that the design of the system may be arbitrarily changed. The equipment layout is to fit into the building as constructed and to coordinate with equipment included under other Divisions of work.

E. Contact the Construction Manager immediately if noticing discrepancies or omissions in either the Drawings, or the Specifications, or if there are any questions regarding the meaning or intent.

F. Submit all changes, other than minor adjustments, to the Construction Manager for approval before proceeding with the work.G. Architect or Construction Manager reserves the right to make minor changes in location of piping and equipment, up to the time of roughing-in,

without additional cost.H. The Contractor is required to visit the site and fully inform himself concerning all conditions affecting the scope of work. Failure to visit the site shall

not relieve the Contractor from any responsibility in the performance of his work.I. All workmanship to be of the highest quality in accordance with the best practices of the trade by craftsmen skilled in this particular work. All work

shall be done in a timely manner as to not disrupt coordination with other trades.J. Contractor to have a competent superintendent in charge of the work installed under this Contract. Superintendent to be experienced in this type of

work.

1.4 PERMITS, INSPECTIONS AND CODESA. File all Drawings, pay all fees, and obtain permits and certificates of inspection relative to this work.B. Completed installation shall conform with all applicable Federal, State and Local Laws, Codes and Ordinances, including, but not limited to, the latest

editions of the following:1. State Building Code.2. Specific Construction Safety Requirements, State Industrial Commission.3. State Pressure Piping Systems Rules.4. A.S.M.E. Pressure Piping Code.5. Standards for Welding Requirements, State Industrial Commission.6. Occupational Safety and Health Act (OSHA) of 1971 and all amendments and revisions thereto.7. S.M.A.C.N.A.8. NFPA-96 (where required by Local Codes).

C. Nothing contained in the Drawings and Specifications shall be construed to conflict with these laws, codes and ordinances and they are hereby included in these Specifications.

1.5 ELECTRICAL MOTORSA. All motors shall comply with Energy Policy Act of 1992 (EPACT). Motors shall be provided by contractor, unless they are factory-installed on the unit.

All wiring, safety switches and motor starters shall be provided by the Electrical Contractor.B. This Contractor shall furnish the Electrical Contractor with all wiring diagrams necessary to connect and control HVAC equipment.

1.6 OPERATING AND MAINTENANCE INSTRUCTIONSA. Instruct the Construction Manager in all matters pertaining to the proper operation and maintenance of equipment furnished under this contract.B. Submit three (3) sets of instructions to the Owner in the hard-bound three-ring notebooks, including installation, maintenance and operating

instructions , pamphlets or brochures and warranties obtained from each manufacturer of principal items of equipment.C. Copies of warranties on all equipment shall be included with this data.D. A copy of final inspection certificate shall also be turned over to the Owner before final payment will be made.

1.7 INSPECTIONA. Contractor shall arrange for and include in his bid, inspection of this work by one of the following:

1. Local Code Authority2. State Code Authority3. Certified Private Inspection Agency

1.8 GUARANTEEA. Contractor is responsible for defects, repairs and replacements in materials and workmanship for a period of one (1) year after final payment is

approved by the Construction Manager. Equipment and controls warranty provided by equipment manufacturer.

1.9 MATERIALSA. Furnish new and un-deteriorated materials and of a quality not less than what is specified.

1. Contractor to furnish and install only those brands of equipment mentioned specifically or accepted as substitutes.

1.10 EQUIPMENT SELECTION AND APPROVALA. The selection of materials and equipment to be furnished shall be governed by the following:

1. Where trade names, brands, or manufacturer of equipment or materials are listed in the Specification, the exact equipment listed shall beused in the bid. Where more than one name is listed, Contractor may select any one of the several brands specified.

2. Any additional approved optional manufacturer will be listed by Addendum only. In order to be considered, Contractor must request approvalof optional manufacturer in writing no later than one (1) week prior to the bid date.

B. Within ten (10) days after the Award of Contract, Contractor must submit a list to the Construction Manager showing the names of manufacturers and subcontractors Contractor intends to use.

1.11 SUBSTITUTIONSA. Contractor must base his bid on furnishing the brand of material and equipment listed in the Specifications.B. Contractor is entitled to bid on any other equal or similar brands of material and equipment he may desire to substitute. The substitute must be listed

on the Specification sheet, with the difference in cost from base bid clearly stated.C. Substitutions which are accepted shall be written into the Contract and no changes of brands shall be made after the Contract is signed unless

approved in writing.

1.12 PROTECTION AND CLEANINGA. Protect all equipment against damage from leaks or abuse and pay the cost of repair or replacement of piping or equipment made necessary by

failure to provide suitable safeguards or protection.B. After all piping and equipment have been inspected and approved, thoroughly clean all equipment, bare piping and insulation provided under this

work.C. After all equipment has been set, thoroughly clean, remove stickers and other foreign matter and leave every part in acceptable condition, clean and

ready for use.D. Repair all dents and scratches in factory prime or finish coats on all equipment. If damage is excessive, replacement shall be required.

1.13 CUTTING AND PATCHINGA. Plan work ahead and place sleeves in walls, floors and ceiling and anticipate during initial stages of construction such opening as will be required to

accommodate equipment and ducts. Coordinate work closely with the Construction Manager so as to conceal HVAC work in the finished portions of the building.

B. Cut as necessary to install new equipment and ducts. Avoid cutting of concrete, masonry and other work by inserts and sleeves.C. Give the Construction Manager locations and sizes of all openings required for the installation of equipment before construction and walls are started.

If it becomes necessary to cut into new work because of failure of Contractor to notify the Construction Manager, then the Construction Manager shall do all necessary cutting and patching at this Contractor’s expense.

D. Patching must match existing surfaces in kind and finish, and shall be done by the Construction Manager at this Contractor’s expense.

1.14 SLEEVES AND COLLARSA. Duct sleeves shall be installed in all walls and ceilings where pipes or ducts are to pass through. Sleeves shall be galvanized sheet metal of greater

gauge than duct passing through and of such size as to allow duct and insulation to pass through with a minimum clearance of ¼” on all sides.B. Sleeves through fire rated construction shall be packed with 3M Brand Firestop caulk or tape, Fyre Putty Brand caulk, or equal.

1.15 EQUIPMENT CLEANOUT PROCEDURESA. Ductwork and air handling equipment is to be cleaned out and blown out before painting is started by the Construction Manager. B. If heating units are operated for temporary heat during construction, replace the filters before the building is turned over to the Owner. Filters must be

in units at all times fans are operated.

1.16 SHOP DRAWINGSA. Submit shop drawings, wiring diagrams, and other data by equipment manufacturer to Architect/Engineer for review.B. Engineer’s review of Shop Drawings or Schedules shall not relieve the Contractor from responsibility for errors, omissions or other deficiencies or

deviations in the Shop Drawings from the Contract Drawings or Specifications.C. Mechanical contractor shall furnish detailed Drawings of the following:

1. HVAC Units2. Boilers and Pumps, Air Separators, Expansion Tanks, Hydronic Accessories3. Chillers, Air Conditioners, Pumps, Hydronic Accessories4. Registers, Grilles, Diffusers and Dampers5. Temperature Controls6. Duct Smoke Detectors.

PART 2 - PRODUCTS

2.1 LOW PRESSURE DUCTWORKA. Furnish and install low pressure ductwork as indicated on the Drawings.B. Install turning vanes, take-offs, and splitter dampers as indicated on plans and as required.C. Coordinate duct locations with all Contractors to eliminate conflicts with new work by under other trades.D. Construction standards and recommendations of the Sheet Metal and Air Conditioning Contractors National Assoc. (SMACNA) shall be followed with

respect to construction and supporting of all ductwork.E. Dimensions on Drawing indicate inside dimensions of air flow area.F. Galvanized Steel:

1. 24 Ga. ductwork – 30” maximum dimension – one side2. 22 Ga. ductwork – 54” maximum dimension – one side3. 20 Ga. ductwork – 84” maximum dimension – one side

G. Provide neoprene-coated glass fabric flex connections where supply and return ducts connect to motor-driven unit, except at grease duct exhaust fans.

2.2 AIR DISTRIBUTION DEVICES & DAMPERSA. All diffusers, grilles and registers to be Titus, E.H. Price or as shown on Drawings.B. Balancing Dampers:

1. Opposed blade, 16 gauge galvanized steel blades and locking quadrants, or equal.2. Dampers for round duct and rectangular ducts less than 12” to be single blade, 20 gauge galvanized steel with locking quadrants.

C. Fire Dampers: Provided by HVAC Contractor if required by local code.1. Dampers to be Type A fusible link. U.L. listed and comply with requirements of NFPA-90A.2. Furnish access door in duct at each fire damper.3. Ruskin, Greenheck, or equal.

D. High Efficiency Take-offs:1. Required on all round pipe branch supply ducts. Fittings to be equipped with balancing damper quads.

2.3 DUCT INSULATIONA. Blanket duct wrap shall be 1-1/2” thick fiberglass with foil vapor barrier manufactured by John Manville, or equal by KNAUF or CSG.B. Sleeve insulation for round hard pipe shall be 1-1/2” fiberglass with foil vapor barrier and shall be Owens Corning, Manville, or equal. Vinyl vapor barrier is

not acceptable.

2.4 DUCT SMOKE DETECTORSA. As indicated on plans provided by equipment manufacturer.

2.5 REFRIGERANT PIPINGA. Copper Tubing: ASTM B280, Type ACR hard drawn.

1. Fittings: ASME B16.22 wrought copper.2. Joints: Braze, AWS A5.8 BCuP silver/phosphorus/copper alloy with melting range 1190 to 1480 degrees F.

B. Copper Tubing to 7/8 inch OD: ASTM B88, Type K, annealed.1. Fittings: ASME B16.26 cast copper, compression type.2. Joints: Flared.

2.6 CHILLED WATER PIPINGA. Steel Pipe: ASTM A53, Schedule 40, black.

1. Fittings: ASME B16.3, malleable iron or ASTM A234, forged steel welding type.2. Joints: Threads for pipe 2 inch and smaller, welded for pipe 2-1/2 inches and larger.

B. Steel Pipe: ASTM A53, Schedule 40, black, grooved ends.1. Fittings: ASTM A395 and ASTM A536 ductile iron, or ASTM A234 carbon steel, grooved ends.2. Joints: Grooved mechanical couplings meeting ASTM F1476

a. Housing clamps: ASTM A395 and ASTM A536 ductile iron, compatible with steel piping sizes.b. Gasket: Elastomer composition for operating temperature range from 30 degrees F to 180 degrees F.c. Accessories: Steel bolts, nuts, and washers.

2.7 INDOOR SPLIT SYSTEM AIR HANDLING UNITS:A. General:

1. Unit shall be a factory-assembled, single-piece central station air handler consisting of a fan and coil section with factory-installed chilled water ordirect expansion coil, preheat or reheat coil, heating coil section, filter section, mixing box or combination filter/mixing box, or access section as indicated on the equipment schedules. Unit base rail shall be 14 gage galvanized steel.

B. Unit Cabinet:1. Unit panels shall be constructed of 20 gage galvanized steel. Casing panels shall be removable for easy access to the unit. All panels shall be

gasketed to ensure a tight seal.2. Optional double wall construction shall be available with inner panels constructed of 20 gage steel.3. Hinged access doors shall be double wall with 1.5 lb dual-density fiberglass between galvanized steel panels.4. Insulation for casing panels on unit shall be 1-in. minimum thickness dual-density fiberglass insulation with a nominal density of not less

than 1.5 lb per cubic foot.5. Insulation shall be secured to casing with water- proof adhesive.6. Condensate drain pans shall be sloped to prevent standing water and constructed of stainless steel; they shall have double wall construction with

threaded drain connection.C. Fan Section:

1. Fan sections shall be constructed of galvanized steel and shall have a formed channel base for integral mounting of fan, motor, and casingpanels. Fan scroll, wheel, shaft, and bearings are to be rigidly secured to the base unit.

2. Each unit shall have a single fan wheel and scroll. Fans shall be double width, double inlet type, with forward-curved blades. Wheels shall bebonderized steel with baked enamel, or galvanized steel.

3. Fan wheels shall be keyed to the shaft and shall be designed for continuous operation at the maximum rated fan speed and motor horsepower.Fan wheels and shafts shall be selected to operate at least 25% below the first critical speed, and shall be statically and dynamically balanced as an assembly.

4. Fan shafts shall be solid steel, turned, ground and polished.5. Fan bearings shall be self-aligning, pillow-block regreasable ball type selected for an average life of 200,000 hours at design operation

conditions, per ANSI Code B3.15.6. Fan motor shall be mounted within the fan section casing on slide rails having 2 adjusting screws. Motor shall be NEMA (National Manufacturing

Association) Design B with sizes and electrical characteristics as shown on the equipment schedule.7. Fan drive shall be designed for a 1.5 service factor and shall be factory mounted and aligned. Belt drive shall be variable or fixed-pitch type.

D. Coil Sections:1. All coils shall have mill galvanized casings. Coils shall be factory leak tested at 450 psig air pressure.2. Chilled water coils shall have aluminum plate fins with belled collars bonded to 1/2-in. mini- mum OD copper tubes by mechanical expansion.

Coils shall have galvanized steel casings and copper headers with threaded steel pipe connections. Working pressure shall be 300 psig at 200 F.Coils shall be drainable and have non-trapping circuits. No turbulence- promoting devices will be permitted inside the tubes. Headers shall havedrain and vent connections.

3. Direct-expansion coils shall have aluminum plate fins with belled collars bonded to 1/2-in. OD copper tubes by mechanical expansion. Coils shallbe provided with pressure-type brass distributors with solder-type connections and shall have a minimum of 2 distributors. Coils for full faceactive or face-split operation shall have intertwined circuits for equal loading on each circuit. Suction and discharge connections shall be on thesame end. Coils shall be designed and tested in accordance with ANSI/ASHRAE 15.

4. Hot water coils shall have aluminum plate fins with belled collars bonded to copper tubes by mechanical expansion. Coils shall have galvanizedsteel casings and copper headers with threaded steel pipe connections. Working pressure shall be 175 psig at 400 F. Headers shall have drainand vent connections.

5. Steam distributing coils (non-freeze type) shall have aluminum plate fins with an outer copper tube diameter of 1-in. with a 5/8-in. diameter innerdistributing tube, galvanized steel casings, and steel headers. Working pressure shall be 175 psig at 400 F.

6. Electric heat coils for use in large air-handling units shall be open wire type, 80% nickel, 20% chromium resistance coils, insulated by floatingsteatite bushings and supported in a galvanized steel frame. Bushings shall be recessed into embossed openings and stacked into supportingbrackets spaced on not more than 4-in. centers. Thermal cutouts for primary and secondary over-temperature protection shall be provided tomeet UL (Underwriters Laboratories) and NEC (National Electrical Code) requirements. Maximum element heating density shall be 55 watts/sqinch.

7. An integral control box shall be furnished by the manufacturer. It shall contain thermal cutouts, primary and secondary control, sub-circuit fusing,airflow switch, and fused control transformer.

E. Filter Sections:1. Each filter section shall be designed and constructed to house the specific type of filter specified on the equipment schedule.2. Flat filter sections shall accept filters of standard sizes. Sections shall include side access slide rails and hinged door access. Flat filter section

shall be arranged with minimum depth in direction of airflow.3. Angle filter section shall accept 2-in. filters arranged in horizontal V formation. Double- walled hinged doors shall be provided.

F. Damper Sections:1. Mixing boxes and filter mixing boxes shall have parallel blade, interconnecting outside-air and return-air dampers. Damper blades shall have

parallel bends for stiffness and shall be welded to 1/2-in. diameter steel rods rotating in nylon bushings and mounted in rigid galvanized steel frames. Dampers shall be sectionalized to limit blade width to no more than 50-in. to minimize blade warpage and to ensure tight closure. All mixing boxes and filter mixing boxes shall have double-walled hinged access doors.

2. All dampers for mixing boxes and filter mixing boxes shall be rated as low-leakage dampers, having a leakage rate not to exceed 2% of airquantity calculated at 2000 fpm velocity through damper and 4.0-in. wg pressure difference. Damper blades shall be gasketed and perimeter sealing strips shall be provided.

G. Access Sections:1. Access sections shall be installed where indicated on the drawings and shall be as specified on the equipment schedule.2. Access sections shall have double-walled hinged doors.

H. Special Features: The following unit options shall be available.1. Chilled water coil with copper plate fins or e- coated fins and stainless steel casing.2. Direct-expansion coil with copper plate fins or e-coated fins and stainless steel casing.3. Hot water (U-bend) coil with copper plate fins or e-coated fins and stainless steel casing.4. Steam distributing coil with copper fins or e- coated fins.

I. Electrical Accessories:1. Starter without disconnect:

a. Adjustable motor overload with trip indication.b. Manual overload reset button (accessible without opening enclosure).c. 115-v fused secondary control trans- former (fuse included — fused primary and secondary over 50 amps).d. Hand/Off/Auto selector switch (accessible without opening enclosure).e. Separate 4-position terminal strip for remote H-O-A wiring.f. C series contactors.g. Horsepower rated for motor applications.h. NEMA 4X type non-metallic enclosures.i. Lug connections for field wiring.j. Factory mounted, wired, and run tested with factory-supplied motor.k. UL listed.

DIVISION 23 - MECHANICALSECTION 23 00 00 - HEATING, VENTILATING, AND AIR CONDITIONING

a. Combination Starter/Disconnect:a. Non-fused UL 508 disconnect switch with lockable handle (locks not provided).b. Cover interlock.c. Adjustable motor overload with trip indication.d. Manual overload reset button (accessible without opening enclosure).e. 115-v fused secondary control transformer (fuse included — fused primary and secondary over 50 amps).f. Hand/Off/Auto selector switch (accessible without opening enclosure).g. Separate 4-position terminal strip for remote H-O-A wiring.h. C series contactors.i. Horsepower rated for motor applications.j. NEMA 4X type non-metallic enclosures.k. Lug connections for field power wiring.l. Factory mounted, wired, and run tested with factory-supplied motor.m. UL listed.

2.8 AIR COOLED REFRIGERANT CONDENSERSA. General:

1. Packaged, factory assembled, pre-wired unit, suitable for outdoor use consisting of casing, condensing coil and fans, integral sub-cooling coil,and controls.

B. Housing:1. House components in welded steel frame with galvanized steel panels with weather resistant, baked enamel finish.2. Mount starters, disconnects, and controls in weatherproof panel with full opening access doors. Furnish mechanical interlock to disconnect power

when door is opened.3. Furnish removable access doors or panels with quick fasteners.

C. Condenser Coils:1. Coils: Aluminum fins mechanically bonded to seamless copper tubing. Furnish sub-cooling circuits as applicable. Air test under water to 425 psig,

and vacuum dehydrate. Seal with holding charge of nitrogen.2. Coil Guard: Expanded metal.3. Configuration: Single refrigeration circuit.

D. Fans and Motors:1. Vertical discharge direct driven propeller type condenser fans with fan guard on discharge, equipped with roller or ball bearings with grease

fittings extended to outside of casing.2. Weatherproof motors suitable for outdoor use, single phase permanent split capacitor or 3 phase, with permanent lubricated ball bearings and

built-in thermal overload protection.E. Controls:

1. Factory wired and mounted control panel, NEMA 250 Type 4 enclosure, containing fan motor starters, fan cycling thermostats, compressorinterlock and control transformer.

2. Furnish controls to permit operation down to 32 degrees F ambient temperature.3. Furnish thermostat to cycle fan motors in response to outdoor temperature.

2.9 PACKAGED ROOFTOP AIR CONDITIONER:A. General:

1. Factory-assembled, single-piece heating and cooling unit. Contained within the unit enclosure shall be all factory wiring, piping, refrigerant charge(R-410A), operating oil charge, dual refrigerant circuits, microprocessor-based control system and associated hardware, and all special features required prior to field start-up.

B. Unit Cabinet:1. Constructed of galvanized steel, bonderized and precoated with a baked enamel finish.

a. Top cover shall be 18-gage sheet metal with 0.75-in. thick, 1.5-lb density, fiberglass insulation.b. Access panels and doors shall be 20-gage sheet metal with 0.5-in. thick, 1.5-lb density, fiberglass insulation.c. Corner and center posts shall be 16-gage galvanized steel.d. Basepans in the heating and return air sections shall be 16-gage galvanized steel.e. Basepans in the condenser section shall be 16-gage galvanized steel.f. Compressor rail shall be 12-gage galvanized steel.g. Condensate pan shall be 16-gage aluminized steel.h. Air baffles shall be 18-gage galvanized steel with 0.5-in. thick, 1.5-lb density, fiberglass insulation.i. Base rail shall be 14-gage galvanized steel.j. Fan deck (indoor and outdoor section) shall be 16-gage galvanized steel.

2. Unit casing shall be capable of withstanding 500-hour salt spray exposure per ASTM (American Society for Testing and Materials) B117 (scribedspecimen).

3. Sides shall have person-sized insulated hinged access doors for easy access to the control box and other areas requiring servicing. Each doorshall seal against a rubber gasket to help prevent air and water leakage and be equipped to permit ease and safety during servicing.

4. Interior cabinet surfaces shall be sheet metal lined or insulated with flexible fire-retardant material, coated on the air side.5. Unit shall have a factory-installed sloped condensate drain connection made from an aluminized steel or optional stainless steel.6. Equipped with lifting lugs to facilitate overhead rigging.7. Filters shall be accessible through a hinged access panel without requiring any special tools.

C. Fans:1. Indoor Evaporator Fans:

a. Double-width/double-inlet, centrifugal, belt driven, forward-curved type with single outlet discharge.b. Fan shaft bearings shall be of the pillow-block type with positive locking collar and lubrication provisions.c. Statically and dynamically balanced.d. Evaporator fan shaft bearings shall have a life of 200,000 hours at design operating conditions in accordance with ANSI B3.15.e. Solid fan shaft construction for size 020-050 units and two-piece solid fan shaft construction on the size 060 unit.

2. Condenser Fans:a. Fans shall be direct-driven propeller type only, with corrosion-resistant blades riveted to corrosion-resistant steel supports for all size

020-050 units and the size 060 unit with optional condenser coil. Size 060 units with the microchannel condenser coil shall have a directdriven, 9-blade airfoil cross section, reinforced polymer construction, and shrouded-axial type fans with inherent corrosion resistance.

b. Fans discharge air vertically upward and are protected by PVC coated steel wire safety guards.c. Statically and dynamically balanced.

D. Supply Fan Drive:1. Unit shall be equipped with variable frequency drive (VFD) inverter. The VFD shall be installed inside the unit cabinet and shall be factory

mounted, wired, and tested. The VFD shall control motor speed to maintain set point static pressure at the sensor tube location of the supply duct pressure transducer (transducer is factory provided and installed; sensor tube must be field routed). The control system may be field-adjusted to maintain supply duct static pressure set points from 0 in. wg to 3.5 in. wg.

2. The variable frequency drive shall include the following features:a. Full digital control with direct control from the unit ComfortLink controls.b. Insulated Gate Bi-Polar Transistors (IGBT) used to produce the output pulse width modulated (PWM) waveform, allowing for quiet motor

operation.c. Inverters capable of operation at a frequency of 8 kHz, so no acoustic noise shall be produced by the motor.d. Self diagnostics.e. Personal lockout code for additional security.f. Critical frequency avoidance.g. RS485 capability standard.h. Electronic thermal overload protection.i. 5% swinging chokes for harmonic reduction and improved power factor.j. All printed circuit boards shall be conformal coated.k. Shall, through ABB, qualify for a 24-month warranty from date of commissioning or 30 months from date of sale, whichever comes first.

E. Compressors:1. Fully hermetic, scroll type compressors with overload protection and short cycle protection with minimum on and off timers.2. Factory rubber-in-shear mounted for vibration isolation.3. Reverse rotation protection capability.4. Crankcase heaters shall only be activated during compressor off mode.

F. Coils:1. Standard evaporator coil shall have aluminum plate fins mechanically bonded to seamless internally grooved copper tubes with all joints brazed.2. Standard condenser coil shall be microchannel design. The coil shall have a series of flat tubes containing a series of multiple, parallel flow

microchannels layered between the refrigerant manifolds. Microchannel coils shall consist of a two-pass arrangement. Coil construction shallconsist of aluminum alloys for the fins, tubes, and manifolds.

3. Coils shall be leak tested at 150 psig and pressure tested at 650 psig.4. Optional condenser coil shall have aluminum plate fins mechanically bonded to seamless internally grooved copper tubes with all joints brazed.5. Optional pre-coated aluminum-fin coils shall have a durable epoxy-phenolic coating to provide protection in mildly corrosive coastal

environments. Coating shall be applied to the aluminum fin stock prior to the fin stamping process to create an inert barrier between thealuminum fin and copper tube. Epoxy-phenolic barrier shall minimize galvanic action between dissimilar metals.

6. Copper-fin coils shall be constructed of copper fins mechanically bonded to copper tubes and copper tube sheets. Galvanized steel tube sheetsshall not be acceptable. A polymer strip shall prevent coil assembly from contacting the sheet metal coil pan to minimize potential for galvaniccorrosion between coil and pan. All copper construction shall provide protection in moderate coastal environments.

7. E-coated coils shall have a flexible epoxy polymer coating uniformly applied to all coil surface areas without material bridging between fins.Coating process shall ensure complete coil encapsulation. Color shall be high gloss black with gloss—60 deg of 65 to 90% per ASTM D523-89.Uniform dry film thickness from 0.8 to 1.2 mil on all surface areas including fin edges. Superior hardness characteristics of 2H per ASTMD3363-92A and cross-hatch adhesion of 4B-5B per ASTM D3359-93. Impact resistance shall be up to 160 in./lb (ASTM D2794-93). Humidity andwater immersion resistance shall be up to minimum 1000 and 250 hours respectively (ASTM D2247-92 and ASTM D870-92). Corrosion durabilityshall be confirmed through testing to be no less than 6000 hours salt spray per ASTM B117-90. Coil construction shall be aluminum finsmechanically bonded to copper tubes.

G. Refrigerant Components:1. Unit shall be equipped with dual refrigerant circuits each containing:

a. Solid core filter drier.b. Thermostatic expansion valve.c. Fusible plug.

H. Filter Section:1. Standard filter section shall be supplied with 2-in. thick disposable fiberglass filters.

I. Controls and Safeties:1. Unit Controls:

a. Scrolling marquee display.b. CCN (Carrier Comfort Network®) capable.c. Unit control with standard suction pressure and condensing pressure transducers.d. Shall provide a 5° F temperature difference between cooling and heating set points to meet ASHRAE 90.1, energy standard.e. Shall provide and display a current alarm list and an alarm history list.f. Automatic compressor redundancy.g. Service run test capability.h. Shall accept input from a CO2 sensor (both indoor and outdoor).i. Configurable alarm light shall be provided which activates when certain types of alarms occur.j. Compressor minimum run time (3 minutes) and minimum off time (3 minutes) are provided.k. Service diagnostic mode.l. Optional integrated economizer control or two-position self-closing adjustable outside-air damper.m. Minimum of 3 capacity stages of mechanical capacity control (excluding hot gas bypass) controlled with logic to maintain supply air

temperature set point.n. Optional minimum load valve for additional capacity stage.o. Unit shall be complete with self-contained low voltage control circuit.

SHEET

SHEET TITLE

ISSUE DATE

DRAWN BY

CHECKED BYAPPROVED BY

PROJECT NO.

REVISION

PROFESSIONAL OF RECORD:NOTIC

E: THIS

ARCHIT

ECTURAL A

ND E

NGIN

EERIN

G D

RAW

ING IS G

IVEN IN C

ONFID

ENCE A

ND S

HALL B

E U

SED O

NLY P

URSUANT T

O T

HE A

GREEMENT W

ITH T

HE A

RCHIT

ECT. NO O

THER U

SE, DIS

SEMIN

ATIO

N, OR D

UPLIC

ATIO

N M

AY B

E M

ADE W

ITHOUT P

RIO

R W

RIT

TEN

CONSENT O

F T

HE A

RCHIT

ECT. ALL C

OMMON L

AW

RIG

HTS O

F C

OPYRIG

HT A

ND O

THERW

ISE A

RE H

EREBY S

PECIF

ICALLY R

ESERVED.

CLIENT

2221 Schrock RoadColumbus, Ohio 43229-1547p 614.898.7100f 614.898.7570www.msconsultants.com

PROJECT

10/5

/202

1 3:

51:0

7 PM

MECHANICAL SPECIFICATIONS

M002

JPF

JASON E. CHRISTOFF - PE No.PE.0056074EXP DATE: 10/31/2021

10/04/2021

MRM

10/04/2021

62-40487-06

HCA HEALTH ONE, LLC4500 E 9TH AVESTE 160DENVER, CO 80220

QUESTDIAGNOSTICS

# DATE DESCRIPTION

J. Safeties:1. Unit shall incorporate a solid-state compressor lockout which provides optional reset capability at the space thermostat should any of the

following safety devices trip and shut off compressor:a. Compressor lockout protection provided for either internal or external overload.b. Low-pressure protection.c. Freeze protection (evaporator coil).d. High-pressure protection (high pressure switch or internal).e. Compressor reverse rotation protection.f. Loss of charge protection.g. Welded contactor protection.

2. Supply-air sensor shall be located in the unit and should be used for economizer control and compressor stage control.3. Induced draft heating section (48 Series) shall be provided with the following minimum protections:

a. High-temperature limit switch.b. Induced-draft motor speed sensor.c. Flame rollout switch.d. Flame proving controls.e. Redundant gas valve.

K. Operating Characteristics:1. Unit shall be capable of starting and running at 115 F ambient outdoor temperature per maximum load criteria of AHRI Standard 340/360.2. Unit with standard controls will operate in cooling down to an outdoor ambient temperature of 32 F.3. Unit shall be provided with fan time delay to prevent cold air delivery.

L. Electrical Requirements:1. All unit power wiring shall enter unit cabinet at a single location.

M. Motors:1. Compressor motors shall be cooled by refrigerant gas passing through motor windings and shall have either internal line break thermal and

current overload protection or external current overload modules with compressor temperature sensors.2. All condenser-fan motors shall be totally enclosed 3-phase type with permanently lubricated ball bearings, class F insulation and internal,

automatic-reset thermal overload protection or manual reset calibrated circuit breakers.3. All indoor fan and power exhaust motors 5 hp and larger shall meet the minimum efficiency requirements as established by the Energy

Independence and Security Act (EISA) of 2007.N. Special Features:

1. Ultra Low Leak Economizer:a. Differential enthalpy controlled integrated type consisting of dampers, actuator, and linkages in conjunction with control system to

provide primary cooling using outdoor air, conditions permitting, supplemented with mechanical cooling when necessary.b. Dampers shall be a gear-driven ultra low leakage type with blade and edge seals. Dampers shall exhibit a maximum leakage rate of 3

cfm per square foot of area at 1 in. wg pressure differential when tested in accordance with AMCA (Air Movement and ControlAssociation) Standard 500.

2. Power Exhaust:a. Package shall include a centrifugal style exhaust fan, 1 Hp 208-230, 460 v direct-drive motor, and damper for vertical flow units with

economizer to control over-pressurization of building. Control shall be through ComfortLink controls based on optional building pressuresensor. 4 stages of control shall be available.

3. Convenience Outlet:a. Shall be factory installed and internally mounted with an externally accessible 115-v, 15 amp GFI (ground fault interrupter), female

receptacle with hinged cover. A step-down transformer and overload protection shall be included so no additional wiring is necessaryunless the field-wired outlet has been requested. When applied with a unit-mounted disconnect, the outlet shall be wired to the loadside of the disconnect so the outlet will shut off with the disconnect.

4. Non-Fused Disconnect Switch:a. Shall be factory installed, internally mounted, and UL approved. Non-fused switch shall provide unit power shutoff. Shall be accessible

from outside the unit and shall provide power off lockout capability.O. Electric Heater:

1. Electric resistance heaters shall be factory-installed, nichrome element type, open wire coils with 0.29 in. inside diameter, insulated with ceramicbushings, and include operating and safety controls. Coil ends are staked and welded to terminal screw slots.

P. Hail Guard, Condenser Coil Grille:1. Shall protect the condenser coil from hail, flying debris, and damage by large objects without increasing unit clearances.

Q. CO2 Sensor:1. The CO2 sensor shall have the ability to monitor CO2 levels and relay information to the controller. The controller will use CO2 level information

to modulate the economizer and provide demand controlled ventilation. The sensor shall be provided as a factory-installed return air sensor.R. Return Air Smoke Detector:

1. The smoke detector shall send input to the controller to shut down the unit in case smoke is detected. The smoke detector shall be factoryinstalled in the return air section or shall be provided as a field-installed accessory.

S. Filter Status:1. The filter status switch shall be a pressure differential switch and will indicate a dirty filter. The switch shall be available as factory installed.

T. Humidity Sensor:1. A humidity sensor shall allow for outside air enthalpy changeover control using the standard outside air dry bulb sensor and the accessory

humidity sensor. When both an outside and return air humidity sensor are used, differential enthalpy changeover can be supported.U. 4-Inch Filters:

1. Optional filter section shall be supplied with 4-in. thick MERV (Minimum Efficiency Reporting Value) 7 pleated fiberglass filters.V. BACnet* Communication Option:

1. Shall provide factory-installed communication capability with a BACnet MS/TP network. Allows integration with i-Vu® Open Control System or aBACnet Building Automation System.

W. Full Perimeter Roof Curbs:1. Shall be formed of 14-gage galvanized steel with wood nailer strip and shall be capable of supporting entire unit weight.

X. Double Wall Option:1. Unit cabinet shall have double wall construction featuring flexible fire retardant fiberglass insulation sandwiched between pre-painted exterior

panels and galvanized steel inner panels.Y. Low Ambient Control:

1. Control shall regulate outdoor fan motor speed in response to the saturated condensing temperature of the unit. The control shall be capable ofoperating the rooftop unit with outdoor temperatures at –20 F.

2. Motormaster® low ambient control shall be provided as a factory-installed option.

PART 3 - EXECUTION

3.1 DUCTWORKA. Cross-break ducts over 12” maximum dimension. Install double wall turning vanes in 90° elbows and extractors at rectangular takeoffs. Install access

doors for automatic and fire dampers. Door width should approximate duct dimension to permit easy access.B. Hang ductwork in accordance with SMACNA recommendations. Support directly from structure.C. All rectangular, round, and flexible duct shall be sized as shown on these Drawings.

3.2 AIR DEVICES INSTALLATIONA. Install fire dampers, sleeves and duct access doors as indicated on Drawings, or as required by code.B. Install balancing dampers and takeoff fittings as indicated and as required for proper balancing of the system.C. Leave all balancing dampers in fully open position prior to air balance.

3.3 DUCT INSULATION INSTALLATIONA. Insulation shall not be applied until the general construction has progressed sufficiently to insure against physical or moisture damage to the insulation.

Replace any insulation which has become wet.B. Ductwork hanger rods must be installed and perpendicular before insulation is installed.C. All joints between insulation blankets, sleeves, etc., shall be sealed and taped with 3” wide pressure sensitive tape with adhesive applied to overlapping

vapor barriers before tape is applied. Tape to be foil faced, reinforced type, as recommended by insulation manufacturer to maintain all ratings of insulation. Cloth backed, generic “duct tape” is not acceptable.

D. Insulate all diffusers and tape insulation to edges of diffusers.E. All supply, return, make-up air, and restroom exhaust ducts, both rectangular and round, are to be fully insulated.F. Hood exhaust ducts are not to be insulated, except as required by local code for fire protection.G. Insulation to be secured externally to all ductwork as well as permanently joined to other portions of insulation on the same duct per manufacturer’s

recommendations.H. All insulation, blanket or sleeve type, as well as insulated flexible duct shall have a foil vapor barrier. Vinyl vapor barriers are not acceptable.I. Interior duct liner shall not be acceptable.J. All duct insulation to be U.L. listed.K. Insulate all diffusers down to ceiling.

3.4 CONTROLSA. All control systems to be installed and adjusted by this Contractor.B. Line voltage wiring is the responsibility of the Electrical Contractor.C. Start-up contractor is responsible for proper operation of the control system.D. Mechanical Contractor is responsible to run control wiring within conduit, and coordinate the installation of such as required.

3.5 AIR SYSTEM BALANCINGA. Balancing of all air and hydronic systems to be performed by this Contractor.B. Perform adjustments as necessary to establish the design quantities indicated on the Drawing, within +/- 5%.C. Demonstrate the system balance to the Construction Manager.

3.6 PROTECTION OF FINISH WORKA. Protect all equipment against damage from leaks or abuse and pay the cost of repair or replacement of piping or equipment made necessary by failure to

provide suitable safeguards or protection.

3.7 HYDRONIC PIPE CLEANINGA. Concentration:

1. As recommended by manufacturer.B. Hot Water Heating Systems:

1. Apply heat while circulating, slowly raising temperature to 160 degrees F and maintain for 12 hours minimum.2. Remove heat and circulate to 100 degrees F or less; drain systems as quickly as possible and refill with clean water.3. Circulate for 6 hours at design temperatures, then drain.4. Refill with clean water and repeat until system cleaner is removed.

C. Use neutralizer agents on recommendation of system cleaner supplier and acceptance of Engineer.D. Flush open systems and glycol filled closed systems with clean water for one hour minimum. Drain completely and refill.E. Remove, clean, and replace strainer screens.F. Inspect, remove sludge, and flush low points with clean water after cleaning process is completed. Include disassembly of components as required.

3.8 CHILLED WATER CLOSED SYSTEM TREATMENTA. Provide one bypass feeder on each system. Install isolating and drain valves and interconnecting piping. Install around balancing valve downstream of

circulating pumps.B. Introduce closed system treatment through bypass feeder when required or indicated by test.

DIVISION 23 - MECHANICALSECTION 23 00 00 - HEATING, VENTILATING, AND AIR CONDITIONING (CONTINUED)

3.9 DEMONSTRATIONFurnish two hour training course for operating personnel, instruction to include installation, care, maintenance, testing, and operation of water treatment systems. Arrange course at startup of systems.

SHEET

SHEET TITLE

ISSUE DATE

DRAWN BY

CHECKED BYAPPROVED BY

PROJECT NO.

REVISION

PROFESSIONAL OF RECORD:NOTIC

E: THIS

ARCHIT

ECTURAL A

ND E

NGIN

EERIN

G D

RAW

ING IS G

IVEN IN C

ONFID

ENCE A

ND S

HALL B

E U

SED O

NLY P

URSUANT T

O T

HE A

GREEMENT W

ITH T

HE A

RCHIT

ECT. NO O

THER U

SE, DIS

SEMIN

ATIO

N, OR D

UPLIC

ATIO

N M

AY B

E M

ADE W

ITHOUT P

RIO

R W

RIT

TEN

CONSENT O

F T

HE A

RCHIT

ECT. ALL C

OMMON L

AW

RIG

HTS O

F C

OPYRIG

HT A

ND O

THERW

ISE A

RE H

EREBY S

PECIF

ICALLY R

ESERVED.

CLIENT

2221 Schrock RoadColumbus, Ohio 43229-1547p 614.898.7100f 614.898.7570www.msconsultants.com

PROJECT

10/5

/202

1 3:

51:0

8 PM

MECHANICAL SPECIFICATIONS

M003

JPF

JASON E. CHRISTOFF - PE No.PE.0056074EXP DATE: 10/31/2021

10/04/2021

MRM

10/04/2021

62-40487-06

HCA HEALTH ONE, LLC4500 E 9TH AVESTE 160DENVER, CO 80220

QUESTDIAGNOSTICS

# DATE DESCRIPTION

T

HALL101

SPECIMENCONSOLIDATION

104

SPECIALSERVICES

01

PATIENTENCOUNTER

03

PATIENTENCOUNTER

02

EMPLOYEEBREAKROOM106

JANITOR/STORAGE

102

SUPPLY103

WAITINGROOM100

UNISEXTOILET

107

UNISEXTOILET

105

SC4300 CFM

SC4250 CFM

SC2100 CFM

SC3100 CFM

SC3100 CFM

SC3100 CFM

SC2100 CFM

SC3225 CFM

EC175 CFM

EC175 CFM

EC170 CFM

RC1260 CFM

RC190 CFM

RC190 CFM

RC190 CFM

RC190 CFM

RC1215 CFM

RC190 CFM

RC1200 CFM

SC150 CFM

SC150 CFM

SC150 CFM

1 1

1

2

SHEET

SHEET TITLE

ISSUE DATE

DRAWN BY

CHECKED BYAPPROVED BY

PROJECT NO.

REVISION

PROFESSIONAL OF RECORD:NOTIC

E: THIS

ARCHIT

ECTURAL A

ND E

NGIN

EERIN

G D

RAW

ING IS G

IVEN IN C

ONFID

ENCE A

ND S

HALL B

E U

SED O

NLY P

URSUANT T

O T

HE A

GREEMENT W

ITH T

HE A

RCHIT

ECT. NO O

THER U

SE, DIS

SEMIN

ATIO

N, OR D

UPLIC

ATIO

N M

AY B

E M

ADE W

ITHOUT P

RIO

R W

RIT

TEN

CONSENT O

F T

HE A

RCHIT

ECT. ALL C

OMMON L

AW

RIG

HTS O

F C

OPYRIG

HT A

ND O

THERW

ISE A

RE H

EREBY S

PECIF

ICALLY R

ESERVED.

CLIENT

2221 Schrock RoadColumbus, Ohio 43229-1547p 614.898.7100f 614.898.7570www.msconsultants.com

PROJECT

10/5

/202

1 3:

51:1

1 PM

MECHANICAL PLAN

M101

JPF

JASON E. CHRISTOFF - PE No.PE.0056074EXP DATE: 10/31/2021

10/04/2021

MRM

10/04/2021

62-40487-06

HCA HEALTH ONE, LLC4500 E 9TH AVESTE 160DENVER, CO 80220

QUESTDIAGNOSTICS

PLAN NORTH

MECHANICAL KEYNOTES1 CONNECT NEW EXHAUST GRILLE TO EXISTING EXHAUST SYSTEM. FIELD VERIFY

EXACT SIZE, LOCATION, AND WORKING CONDITION OF NEAREST EXISTINGEXHAUST SYSTEM PRIOR TO CONSTRUCTION.

2 NEW LOCATION OF EXISTING TEMPERATURE SENSOR. FIELD VERIFY EXACTLOCATION OF EXISTING TEMPERATURE SENSOR PRIOR TO CONSTRUCTION. FIELDVERIFY EXACT LOCATION OF NEW LOCATION WITH ARCHITECTURAL DRWAINGS.

# DATE DESCRIPTION

1/4" = 1'-0"1 MECHANICAL PLAN

MECHANICAL GENERAL NOTESA PROVIDE DUCTWORK AS REQUIRED FOR A COMPLETE SYSTEM PER

SPECIFICATIONS AND SMACNA STANDARDS. BRANCH DUCTWORK SHOWN FORREFERENCE ONLY. THE DRAWINGS INDICATE A GENERAL SCHEMATIC LAYOUT OFDUCTWORK AND MECHANICAL EQUIPMENT. THE CONTRACTOR SHALL FOLLOW THISARRANGEMENT WHEREVER FEASIBLE. HOWEVER, IT SHALL BE THERESPONSIBILITY OF THE CONTRACTOR TO VERIFY EXISTING FIELD CONDITIONSAND MAKE MODIFICATIONS TO LOCATIONS, ROUTING, ETC. AS MAY BE REQUIRED.IF A DIFFERENT ARRANGEMENT THAN SHOWN IS REQUIRED THEN IT SHALL BE THECONTRACTOR'S RESPONSIBILITY TO PROVIDE AND INSTALL SUCH WORK AS IT MAYBE REQUIRED.

B THE MECHANICAL CONTRACTOR SHALL FIELD VERIFY EXACT LOCATIONS, SIZES,AND WORKING CONDITIONS OF ALL MECHANICAL SYSTEMS PRIOR TOCONSTRUCTION. THE MECHANICAL CONTRACTOR SHALL REPORT ISSUES ORDISCREPANCIES FOUND IN THE FIELD THAT DO NOT COORDINATE WITH THESEDRAWINGS TO THE ENGINEER.

C SUPPLY BRANCH DUCTWORK DOWNSTREAM OF EXISTING VAV BOXES SHALL HAVETHE SAME DIAMETER OF THE DIFFUSER CONNECTION SIZE UNLESS OTHERWISENOTED. REFER TO MECHANICAL SCHEDULES SHEET FOR ADDITIONALINFORMATION.

D NEW DIFFUSERS SHALL REUSE EXISTING BRANCH DUCTWORK IN AREAS WHEREPOSSIBLE. CONTRACTOR SHALL FIELD VERIFY EXACT SIZE AND LOCATION OFEXISTING BRANCH DUCTWORK PRIOR TO CONSTRUCTION. EXTEND AND CONNECTEXISTING BRANCH DUCTOWORK TO NEW DIFFUSERS AS NECESSARY.CONTRACTOR SHALL SUPPLY NEW BRANCH DUCTWORK TO EXISTING DUCTWORKMAIN FOR DIFFUSERS WITHOUT REUSABLE BRANCH DUCTWORK. CONTRACTORSHALL FIELD VERIFY EXACT SIZE AND LOCATION OF EXISING DUCTWORK MAINSPRIOR TO CONTRUCTION. REPORT ANY ISSUES FOUND IN FIELD TO ENGINEERPRIOR TO CONTINUATION OF CONSTRUCTION.

ROUND DUCTRECTANGULAR DUCT

SQUARE TO ROUND1 TO 4 TRANSITION

45°

AIR FLOW AIR FLOWAI

R F

LOW

AIR

FLO

W

MAINDUCT

MAINDUCT

45°

AIR FLOW

AIR

FLO

WSD

R=1.5D

CONICAL SPIN-IN FITTING

MANUALDAMPER

W/LOCKING

QUADRANTBRANCH DUCT

MAIN DUCT

MANUALDAMPER

W/LOCKING

QUADRANTBRANCH DUCT

DO NOT OBSTRUCT

AIR FLOW IN MAINDUCTROUND &

RECTANGULARRADIUSED ELBOW

RECTANGULAR 90° ELBOWWITH DOUBLE DOUBLETHICKNESS TURNING

VANES

RECTANGULAR 90° SPLITTER

DAMPER WITH DOUBLETHICKNESS TURNING

VANES

ROUND LOWPRESSURE

SUPPLY DUCTS

ROUND ANDRECTANGULARRETURN AND

EXHAUST DUCTS

ROUND ANDRECTANGULAR

LOW PRESSURE

SUPPLY DUCTS

MANUAL VOLUMEDAMPER

SPIRAL CONNECTIONSUPPLY AIR DUCTWORK

INSULATED ROUNDSPIRAL SUPPLY AIR DUCTWORK

STRAP CLAMP

FLEXIBLE CONNECTION(MAXIMUM 5 FEET)

FLOW STRAIGHTENER

SUPPLY AIR DIFFUSER(REFER TO DIFFUSER SCHEDULE)

DRYWALL CEILING OR LAY-IN FRAME

SHEET

SHEET TITLE

ISSUE DATE

DRAWN BY

CHECKED BYAPPROVED BY

PROJECT NO.

REVISION

PROFESSIONAL OF RECORD:NOTIC

E: THIS

ARCHIT

ECTURAL A

ND E

NGIN

EERIN

G D

RAW

ING IS G

IVEN IN C

ONFID

ENCE A

ND S

HALL B

E U

SED O

NLY P

URSUANT T

O T

HE A

GREEMENT W

ITH T

HE A

RCHIT

ECT. NO O

THER U

SE, DIS

SEMIN

ATIO

N, OR D

UPLIC

ATIO

N M

AY B

E M

ADE W

ITHOUT P

RIO

R W

RIT

TEN

CONSENT O

F T

HE A

RCHIT

ECT. ALL C

OMMON L

AW

RIG

HTS O

F C

OPYRIG

HT A

ND O

THERW

ISE A

RE H

EREBY S

PECIF

ICALLY R

ESERVED.

CLIENT

2221 Schrock RoadColumbus, Ohio 43229-1547p 614.898.7100f 614.898.7570www.msconsultants.com

PROJECT

10/5

/202

1 3:

51:1

4 PM

MECHANICAL SCHEDULES ANDDETAILS

M601

JPF

JASON E. CHRISTOFF - PE No.PE.0056074EXP DATE: 10/31/2021

10/04/2021

MRM

10/04/2021

62-40487-06

HCA HEALTH ONE, LLC4500 E 9TH AVESTE 160DENVER, CO 80220

QUESTDIAGNOSTICS

N.T.S.1 SQUARE TO ROUND TRANSITION DETAILN.T.S.2 TYPICAL LOW PRESSURE FITTING DETAIL

NOTES:1. PROVIDE MOUNTING FRAME TO MATCH CEILING TYPE.2. MAXIMUM N.C. OF 25 FOR ALL GRILLES, REGISTERS AND DIFFUSERS.3. NECK SIZE SHALL BE THE SAME AS BRANCH DUCT SIZE.

DIFFUSER, REGISTER, AND GRILLE SCHEDULENOTES: - NECK SIZE SHALL MATCH DUCT SIZE ON PLANS UNLESS NOTED OTHERWISE. TRANSITION FROM DUCT TO NECK SIZE IF DIFFERENT.

EQUIPMENT SYSTEM DAMPER DIMENSIONS MATERIAL

NOTESTYPE NO.BASIS OF DESIGN

VOLUME TYPEFACE SIZE NECK SIZE

TYPE COLORMANUFACTURER MODEL L W DIA. L WEC 1 TITUS 50F Yes VOLUME 12" 12" 6" STEEL WHITE 1, 2, 3RC 1 TITUS 50F Yes VOLUME 24" 12" 8" 8" STEEL WHITE 1,2,3SC 1 TITUS OMNI-06 Yes VOLUME 12" 12" 6" STEEL WHITE 1, 2, 3SC 2 TITUS OMNI-06 Yes VOLUME 24" 24" 6" STEEL WHITE 1, 2, 3SC 3 TITUS OMNI-08 Yes VOLUME 24" 24" 8" STEEL WHITE 1, 2, 3SC 4 TITUS OMNI-10 Yes VOLUME 24" 24" 10" STEEL WHITE 1, 2, 3

# DATE DESCRIPTION

N.T.S.3 DIFFUSER TAKEOFF DETAIL

OUTSIDE AIR CALCULATIONS

RoomNumber

Building / SpaceArea Use Classification

Actual Code* Code* Code* Code* ASHRAE Code* Exhaust Code** Total Vent. ExhaustFloor Area Occupancy Occupancy Vent. Rate Vent. Rate 62.1 Ez Total Vent. Rate Exhaust Provided Provided

SF PPL/1000 SF People CFM/Person CFM/SF Value CFM^ (CFM/sqft) (CFM) (CFM) (CFM)Az Pz Rp Ra Ez EzVdz

101 Corridors 164.0 0 0 0.0 0.06 0.8 12 0 20 0102 Occupiable storage rooms for liquids or gels 26.0 2 0 5.0 0.12 0.8 4 1 26 10 50106 Breakrooms 61.0 50 3 5.0 0.12 0.8 28 0 60 0103 Occupiable storage rooms for dry materials 65.0 2 0 5.0 0.06 0.8 6 0 20 0

1, 2, 104, 3 Office Space 309.0 5 2 5.0 0.06 0.8 33 0 110 0100 Reception Areas 163.0 30 5 5.0 0.06 0.8 43 0 45 0

105, 107 Toilets** 102.0 0 0 0.0 0 0.8 0 140 20 150890 10 Total 126 166 285 200

^ Room CFMs justified through ASHRAE 62.1-2016 Appendix A Calculations* Based on ASHRAE 62-2016**Toilet rooms are based on 70 CFM per Fixture (water closet or urinal)NOTE: Outside Air provided by existing system in existing space.

T

3

T

OS

G

J

M

RC

DC

ASI

AUD

COMM

CTRL

IP

DGA

AES

FO

I

HDMI

SDI

MIC

RF

RGBHV

SYNC

VID

SPKR

T

NC

4" TELECOM CONDUIT

GENERAL ELECTRICAL

ELECTRICAL MOTOR, SINGLE PHASE

ELECTRICAL MOTOR, THREE PHASE

TRANSFORMERONE-LINE

TRANSFORMERPLAN

ELECTRICAL AND COMMUNICATIONS SYMBOLS AND LINETYPES LEGEND

BASE BLOCK COMMUNICATIONS SYMBOLM: MOUNT T: TECHNOLOGY

X: LEGEND REF T2: SECONDARY TECHNOLOGY

COMMON WORK RESULTS FOR COMMUNICATIONS

BASE CIRCLE COMMUNICATIONS SYMBOLM: MOUNT T: TECHNOLOGY

X: LEGEND REF T2: SECONDARY TECHNOLOGY

DATA/TELEPHONE OUTLET BOX

BASE PORT SYMBOLM: MOUNT T: TECHNOLOGY

X: LEGEND REF T2: SECONDARY TECHNOLOGY

BASE SYMBOL ANNOTATIONSM: MOUNT C = CEILING D = DESK/TABLE F = FLUSH FL = FLOOR G = GROUND H = HIDDEN M = MULLION O = OUTDOOR P = PEDESTAL RK = RACK R = ROOF REC = RECESSED S = SURFACE W = WALL

T: TECHNOLOGY UPS = UNINTERRUPTIBLE POWER SUPPLY CCT = CHARGE CONTROLLER AV = AUDIO VIDEO CT = CURRENT TRANSFORMER D = DATA G = GENERATOR J = JUNCTION BOX S = SPEAKER (OLD FORMAT) WP = WEATHER PROOF

T2: SECONDARY TECHNOLOGY

X: LEGEND REF

MT

T2 X

MT

T2 X

MT

T2 X

EXIT SIGNMOUNT: WALL

EMERGENCY LIGHTING

EMERGENCY LIGHT FIXTURE

EMERGENCY BATTERY LIGHTSINGLE HEAD

DUAL HEAD

TRIPLE HEAD

EXIT SIGNMOUNT: CEILING

REMOTE EGRESS HEADSINGLE HEAD

DUAL HEAD

ABBREVIATION TERM

1PH SINGLE-PHASE1P SINGLE POLE

1WAY ONE-WAY2/C TWO-CONDUCTOR

2WAY TWO-WAY3/C THREE-CONDUCTOR3PH THREE-PHASE

3WAY THREE-WAY4/C FOUR-CONDUCTOR

4PDT FOUR-POLE DOUBLE THROW4PST FOUR-POLE SINGLE THROW4W FOUR-WIRE

4WAY FOUR-WAYAIC AMPERE INTERRUPTING CAPACITYASC AMPS SHORT CIRCUITATS AUTOMATIC TRANSFER SWITCHAWG AMERICAN WIRE GAUGEBIL BASIC INSULATION LEVELCB CIRCUIT BREAKERCLF CURRENT LIMITING FUSECT CURRENT TRANSFORMERdB DECIBEL

DPDT DOUBLE POLE, DOUBLE THROWDPST DOUBLE POLE, SINGLE THROW

DS DISCONNECT SWITCHEPO EMERGENCY POWER OFFFC FOOTCANDLEFLA FULL LOAD AMPS

F FRAME/FUSEFVNR FULL VOLTAGE NON-REVERSINGFVR FULL VOLTAGE REVERSING

GFI/GFCI GROUND FAULT INTERRUPTERHOA HAND-OFF-AUTOMATICHP HORSEPOWERIC INTERRUPTING CAPACITY

J-BOX JUNCTION BOXLTG LIGHTINGMCB MAIN CIRCUIT BREAKERMCC MOTOR CONTROL CENTERMTS MANUAL TRANSFER SWITCHNC NORMALLY CLOSEDNF NONFUSEDNL NIGHT LIGHTNO NORMALLY OPEN

OCB OIL CIRCUIT BREAKEROCR OIL CIRCUIT RECLOSEROGA OIL GAGEOL OVERLOAD

OLVL OIL LEVELPB PUSHBUTTONPE PHOTOELECTRIC

RCPT RECEPTACLESCC SHORT CIRCUIT CAPACITYSPDT SINGLE POLE, DOUBLE THROWSPST SINGLE POLE, SINGLE THROW

ST SINGLE THROWSW SWITCH

SWBD SWITCHBOARDSWGR SWITCHGEAR

T TRIP RATINGTL TWIST LOCKTP TWISTED PAIR

TPS TWISTED PAIR SHIELDEDUPS UNINTERRUPTIBLE POWER SUPPLYUTP UNTWISTED PAIRVFD VARIABLE FREQUENCY DRIVE

XFMR TRANSFORMER

A. GENERAL REQUIREMENTS

1. BEFORE SUBMITTING THE BID PROPOSAL THE ELECTRICAL CONTRACTOR SHALL MAKESITE VISITS AS NECESSARY TO FULLY ACQUAINT HIMSELF WITH THE JOB CONDITIONS.

2. VERIFY EXACT DIMENSIONS AND LOCATIONS OF EXISTING CONSTRUCTION, BUILDINGSTRUCTURES, AND WORK OF OTHER TRADES AND COORDINATE WITH NEW WORK.WIRING AND CONDUIT SHALL BE INSTALLED ONLY AFTER COORDINATION WITH OTHERTRADES.

3. LAYOUTS ARE SCHEMATIC AND SHOWN FOR GENERAL REFERENCE, MAKE MINORCHANGES AS NECESSARY FOR EASE OF CONSTRUCTION FOR EXACT LOCATIONLIGHTING, POWER, AND DATA EQUIPMENT REFER TO ARCHITECTURAL DRAWINGS ANDCOORDINATE WITH FURNISHINGS AND EQUIPMENT IN FIELD.

4. CONDUIT, ELBOWS, OFFSETS, ACCESSORIES, AND OTHER MISCELLANEOUSHARDWARE AND APPURTENANCES ARE NOT SHOWN BUT SHALL BE INCLUDED AT NOADDITIONAL COST WHERE REQUIRED TO COMPLETE THE SYSTEM.

5. MAKE MINOR CHANGES AS NECESSARY FOR EASE OF CONSTRUCTION. MAJORDEVIATIONS OR CHANGES FROM THE DESIGN SHALL BE APPROVED BY THEARCHITECT/ENGINEER BEFORE ORDERING SUPPLIES OR STARTING WORK.

6. DASHED AREAS SHOWN IN FRONT OF AND AROUND EQUIPMENT ARE AREASREQUIRED FOR SERVICE AND INSPECTION. THESE AREAS SHALL BE MAINTAINEDCLEAR OF OBSTRUCTIONS TO 7'-0" AFF OR TO THE HEIGHT OF THE EQUIPMENT,WHICHEVER IS HIGHER.

7. ALL INTERIOR CIRCUITS SHALL BE CONCEALED IN WALLS OR CEILING SPACES.CIRCUITS IN CEILING SPACES SHALL BE RUN TIGHT TO STRUCTURE AND HORIZONTALTO OR PERPENDICULAR WITH STRUCTURAL MEMBERS.

B. INSPECTION

1. ALL WORK SHALL BE INSPECTED BY THE AUTHORITY HAVING JURISDICTION.

2. UPON COMPLETION OF THE WORK, THIS CONTRACTOR SHALL FURNISH TO THEARCHITECT A CERTIFICATE OF INSPECTION AND APPROVAL FROM SAID AUTHORITYBEFORE FINAL PAYMENT ON THE CONTRACT WILL BE ALLOWED.

3. FEE FOR THE INSPECTION SHALL BE A PART OF THE CONTRACT, THE COST OF WHICHSHALL BE INCLUDED IN THIS CONTRACTOR'S BID.

C. CODES

1. PERFORM ALL WORK IN ACCORDANCE WITH THE LATEST EDITION OF THE NATIONALELECTRICAL CODE, NATIONAL ELECTRICAL SAFETY CODE, AND ANY STATE AND LOCALCODES OR ORDINANCES.

2. CONTRACTOR SHALL INSTALL AT EACH SERVICE ENTRANCE A PERMANENTDIRECTORY ACCORDING TO ARTICLE 230.2(E), OF THE NATIONAL ELECTRICAL CODE.

3. ELECTRICAL CONTRACTOR SHALL PROVIDE ARC FLASH WARNING LABELS FOR ALLDISCONNECTS PER NFPA AND OSHA STANDARDS.

D. SHOP DRAWINGS

1. THE CONTRACTOR SHALL SUBMIT COMPLETE DETAILED SHOP DRAWINGS COVERINGALL ITEMS OF EQUIPMENT. NO EQUIPMENT SHALL BE PUT INTO MANUFACTURE ORORDERED UNTIL THESE SHOP DRAWINGS OR BROCHURES HAVE BEEN APPROVED BYTHE ARCHITECT/ENGINEER.

E. MATERIALS & EQUIPMENT1. ALL MATERIALS AND EQUIPMENT SHALL BE NEW AND OF THE TYPE LISTED BY

UNDERWRITERS LABORATORIES, INC. AND SHALL BE IN STRICT CONFORMITY WITHTHE LATEST STANDARDS OF THE FOLLOWING WHERE SUCH STANDARDS NORMALLYAPPLY:

a. UNDERWRITERS LABORATORIES, INC.

b. NATIONAL FIRE PROTECTION ASSOCIATION

2. WHERE MATERIALS, EQUIPMENT, APPARATUS OR OTHER PRODUCTS ARE SPECIFIEDBY BRAND NAME, TYPE OR CATALOG NUMBER, SUCH DESIGNATION IS TO ESTABLISHSTANDARDS OF DESIRED QUALITY AND STYLE AND SHALL BE THE BASIS OF THE BID.MATERIALS SO SPECIFIED SHALL BE FURNISHED UNDER THE CONTRACT. WHERE TWOOR MORE DESIGNATIONS ARE LISTED, CHOICE SHALL BE OPTIONAL TO THECONTRACTOR.

3. PROVIDE MEANS TO FURNISH AND INSTALL ALL EQUIPMENT INDICATED. FURNISHMEANS TO PURCHASE, ARRANGE FOR DELIVERY TO SITE, AND TO TAKE DELIVERY ATTHE SITE. INSTALL MEANS TO PLACE IN POSITION FOR USE.

F. CUTTING AND REPAIRING

1. THE ELECTRICAL CONTRACTOR SHALL DO ALL CUTTING AND PATCHING TO MATCHEXISTING ADJACENT CONSTRUCTION REQUIRED TO PERFORM THEIR WORK, ANDWARRANTY ALL REPAIRS FOR A MINIMUM OF ONE YEAR.CONTRACTOR SHALL BERESPONSIBLE FOR ALL OPENINGS REQUIRED IN WALLS.

2. ALL OPENINGS SHALL BE REPAIRED TO MATCH EXISTING BY A QUALIFIEDCONTRACTOR AT THE EXPENSE OF THIS CONTRACTOR.

3. ALL CONDUIT PENETRATIONS THROUGH BUILDING WALLS SHALL BE GROUTED ORSEALED CLOSED. WHERE CONDUIT PENETRATES WALLS AND FLOORS SEAL WITH AU.L. LISTED SEALANT. SEAL PENETRATIONS WITH INTUMESCENT CAULK, PUTTY, ORSHEET INSTALLED PER MANUFACTURER'S RECOMMENDATIONS.

4. ALL MATERIALS USED TO SEAL PENETRATIONS OF FIRE WALLS AND FLOORS SHALL BETESTED AND CERTIFIED AS A SYSTEM PER ASTM E814 STANDARDS FOR FIRE TESTSOR THROUGH-PENETRATION FIRESTOPS AS MANUFACTURED BY 3M, THOMAS &BETTS, OR DUPONT.

G. GUARANTEE

1. THIS CONTRACTOR SHALL GUARANTEE THEIR WORKMANSHIP AND MATERIAL(FLUORESCENT LAMPS EXCEPTED) FOR A PERIOD OF ONE YEAR FROM THE DATE OFFINAL ACCEPTANCE AND LEAVE THEIR WORK IN PERFECT ORDER AT COMPLETION.SHOULD DEFECTS DEVELOP WITHIN THE GUARANTEE PERIOD, THIS CONTRACTORSHALL, UPON NOTICE OF DEFECTS, REMEDY THE DEFECTS AND HAVE ALL DAMAGESTO OTHER WORK OR FURNISHINGS CAUSED BY THE DEFECTS OR THE WORK OFCORRECTING SAME, REPAIRED AND/OR REPLACED AT THEIR EXPENSE, TO THECONDITION BEFORE SUCH DAMAGE.

ELECTRICAL GENERAL NOTES

HANDHOLE/PULL BOXH

TELEPHONE OUTLET BOX

PROVIDE 3/4" CONDUIT TURNED OUT ABOVE CEILING OR IN JOIST SPACE WITH BUSHING AND PULLWIRE.

PROVIDE 3/4" CONDUIT TURNED OUT ABOVE CEILING OR IN JOIST SPACE WITH BUSHING AND PULLWIRE.

ELECTRICAL RECEPTACLEDUPLEXMOUNT VERTICALLY, 18"AFF UNLESS OTHERWISE NOTED(TYPICAL)

LOW-VOLTAGE DISTRIBUTION EQUIPMENT

ELECTRICAL RECEPTACLEDUPLEX WITH GROUND FAULT INTERRUPTER

ELECTRICAL RECEPTACLEQUADRAPLEX

ELECTRICAL RECEPTACLESINGLE

ELECTRICAL RECEPTACLESPECIAL PURPOSE

SWITCHTHREE-WAY

SWITCHWITH PILOT LIGHT

SWITCHTIMER OPERATED

SWITCHOCCUPANCY SENSOR

ELECTRICAL RECEPTACLEDUPLEX WITH ISOLATED GROUND

ELECTRICAL RECEPTACLEDUPLEX ON GENERATOR POWER

LIGHT FIXTURE (TYPICAL)MOUNT: RECESSED

INTERIOR LIGHTING

LIGHT FIXTURE (TYPICAL)MOUNT: SURFACE

LIGHT FIXTURE (TYPICAL)MOUNT: WALL

LIGHT FIXTURE (TYPICAL)MOUNT: SUSPENDED

LIGHT FIXTUREMOUNT: CEILING

LIGHTINGSWITCHBOARDS AND PANELBOARDS

PANELBOARD CABINETMOUNTING: RECESSED

PANELBOARD CABINETMOUNTING: SURFACE

ELECTRICAL LINETYPES

DIRECT CURRENT UNDERGROUND

DIRECT CURRENT ABOVEGROUND

RIGID CONDUIT

COMMUNICATIONS LINETYPES

COMMUNICATIONS

ANALOG AUDIO

DIGITAL VIDEO

DIGITAL AUDIO

DATA INTERNET PROTOCOL (IP)

CONTROL

INTERCOM

FIBEROPTICS

DIGITAL AES AUDIO

MICROPHONE AUDIO

DIGITAL VIDEO STANDARD DEFINITION SDI

DIGITAL VIDEO HIGH DEFINITION HDMI

SYNC VIDEO

COMPONENT RGBHV VIDEO

RADIO FREQUENCY (RF), CCTV, MATV, IF

VIDEO, COMPOSITE ANALOG

NURSE CALL

TELEPHONE

SPEAKER AUDIO

WALL MOUNTING

CEILING MOUNTING

FLOOR MOUNTING

TYPICAL MOUNTING SYMBOLS

WALL MOUNTING

CEILING MOUNTING

FLOOR MOUNTING

TYPICAL MOUNTING SYMBOLSCIRCUIT BREAKER

DUPLEX

LOW-VOLTAGE CIRCUIT PROTECTIVE DEVICES

DISCONNECT SWITCHFUSED

DISCONNECT SWITCHUNFUSED

STARTERCOMBINATION WITH DISCONNECT SWITCH

LOW-VOLTAGE CONTROLLERS

STARTER OR MOTOR CONTROLLER

TIME CLOCK

GENERATOR

PACKAGED GENERATOR ASSEMBLIES

BATTERY

BATTERY EQUIPMENT

CAPACITOR

POWER FILTERS AND CONDITIONERS

UNINTERRUPTABLE POWER SUPPLYM: MOUNT C = CEILING D = DESK/TABLE F = FLUSH FL = FLOOR G = GROUND H = HIDDEN M = MULLION O = OUTDOOR P = PEDESTAL RK = RACK

T: TECHNOLOGY OL = OFF-LINE ONL = ON-LINE LNI = LINE INTERACTIVE UPS = UNINTERRUPTIBLE POWER SUPPLY

T2: SECONDARY TECHNOLOGY

X: LEGEND REF

XT2UPS

M

EARTH GROUND

JUNCTION BOXMOUNTING: WALL

COMMON WORK RESULTS FOR ELECTRICAL

HOME RUNARROWHEADS INDICATE THE NUMBER OF CIRCUITS

ELECTRICAL METER

INSTRUMENTATION AND CONTROL FOR ELECTRICAL SYSTEMS

FUSE WITH RATING

LOW-VOLTAGE ELECTRICAL TRANSMISSION

NORMALLY CLOSED RELAY CONTACT

NORMALLY OPEN RELAY CONTACT

ELECTRICAL PUSH BUTTON

EXTERIOR LIGHTING

LIGHT POSTONE ARM, ONE POST

LIGHT POSTTWO ARMS, TWO HEADS

EXTERIOR WALL PACK

DC

SWITCHSINGLE POLE

ELECTRICAL RECEPTACLEDUPLEX WITH USB CHARGING OUTLETUSB

GFI

IG

TC

P

SHEET

SHEET TITLE

ISSUE DATE

DRAWN BY

CHECKED BYAPPROVED BY

PROJECT NO.

REVISION

PROFESSIONAL OF RECORD:NOTIC

E: THIS

ARCHIT

ECTURAL A

ND E

NGIN

EERIN

G D

RAW

ING IS G

IVEN IN C

ONFID

ENCE A

ND S

HALL B

E U

SED O

NLY P

URSUANT T

O T

HE A

GREEMENT W

ITH T

HE A

RCHIT

ECT. NO O

THER U

SE, DIS

SEMIN

ATIO

N, OR D

UPLIC

ATIO

N M

AY B

E M

ADE W

ITHOUT P

RIO

R W

RIT

TEN

CONSENT O

F T

HE A

RCHIT

ECT. ALL C

OMMON L

AW

RIG

HTS O

F C

OPYRIG

HT A

ND O

THERW

ISE A

RE H

EREBY S

PECIF

ICALLY R

ESERVED.

CLIENT

2221 Schrock RoadColumbus, Ohio 43229-1547p 614.898.7100f 614.898.7570www.msconsultants.com

PROJECT

10/5

/202

1 3:

50:4

4 PM

ELECTRICAL SYMBOLS ANDGENERAL NOTES

E001

GSG

JASON E. CHRISTOFF - PE No.PE.0056074EXP DATE: 10/31/2021

10/04/2021

MRM

10/04/2021

62-40487-06

HCA HEALTH ONE, LLC4500 E 9TH AVESTE 160DENVER, CO 80220

QUESTDIAGNOSTICS

# DATE DESCRIPTION

DIVISION 26 – ELECTRICALSECTION 26 00 00 – ELECTRICAL

PART 1 - GENERAL

1.1 SCOPE OF WORKA. Furnish and install all materials and equipment and provide all labor, tools, transportation, superintendence and services required and necessary

to complete the work shown on the drawings and/or specified herein. Also are included all other work and miscellaneous items, not specifically mentioned, but reasonably inferred for a complete installation including all accessories and appurtenances required for testing the system. It is the intent of the drawings and specifications that all systems be complete, and ready for operation.

1.2 REGULATORY REQUIREMENTSA. Code compliance is mandatory. Nothing in these Drawings and Specifications permits work not conforming to these codes. Where work is

shown to exceed minimum code requirements, comply with the drawings and specifications. All work and materials shall comply with the latest rules, codes and regulations, including, but not limited to the following:1. Occupational Safety and Health Act Standards (OSHA).2. STATE Electric Code.3. NFPA #101: Life Safety Code.4. State Fire Marshal.5. Local Utilities Companies.

1.3 LICENSE, FEES AND PERMITSA. Electrical contractor shall pay for all licenses, permits and inspections fees required by the authority having jurisdiction and shall arrange for all

required inspections.

1.4 SAFETY AND INDEMNITYA. The contractor shall be solely responsible for conditions of the job site, including safety of all persons and property during performance of work.

This requirement will apply continuously and not be limited to normal working hours.B. No act, service, drawing review or construction review by the Owner, the Engineers or the Consultants, is intended to include review of the

adequacy of the Contractor’s safety measures in, on, or near the construction site.

1.5 DRAWINGS AND SPECIFICATIONSA. All drawings and all Divisions of the specifications shall be considered as a whole and work of this Division shown anywhere therein shall be

furnished under this Division.B. Drawings are diagrammatic and indicate the general arrangement of equipment and wiring. Most direct routing of conduits and wiring is not

assured. Exact requirements shall be governed by conditions of the job. Consult all other drawings in preparation of the bid. Extra lengths of wiring or addition of pull or junction boxes, etc. necessitated by such conditions shall be included in the bid.

1.6 CONDITIONS AT SITEA. The electrical contractor shall have examined the site and familiarized themselves with all discernable existing conditions. No extra payment will

be allowed for work required because of these conditions, whether specifically mentioned or not.

1.7 WORKMANSHIP AND CONTRACTOR’S QUALIFICATIONSA. Only quality workmanship will be accepted. Haphazard or poor installation will be cause for rejection of work.

1.8 SHOP DRAWINGS AND MATERIALS LISTSA. Submit to Owner in a single package six (6) copies of complete shop drawings and materials list, as noted below, for review within fifteen (15)

days after award of contract. Submittals required as follows:1. Wiring devices: switches, receptacles, device plates.2. Enclosures for utility company metering.3. Main fused disconnect switch.4. Panelboards.5. Disconnect switches.6. Lighting fixtures, lamps and lighting control equipment.

1.9 SUBSTITUTIONSA. One or more makes of materials or methods may have been specified to establish the standard of quality, workmanship, finish and design

required, but other materials or methods equal in quality, workmanship, finish, design, and guaranteed performance, will be accepted. However, all changes and substitutions shall be requested in letter form and shall be accompanied with a statement of the amount of money to be returned to the contract if the substitution is permitted.

B. No work involving materials submitted for substitution shall proceed until written acceptance is received from the Owner. The Owner is the sole judge of acceptability of preferred substitutions. If a substitution item is permitted, and any re-design effort is thereby necessitated, the required re-design shall be at the Contractor’s expense.

1.10 COORDINATIONA. Coordinate work with other trades to avoid conflict and to provide correct rough-in and connection for equipment furnished under other trades

that require electrical connections. Inform Contractors of other trades of the required access to and clearances around electrical equipment to maintain serviceability and code requirements.

B. Verify equipment dimensions and requirements with provisions specified under this Section. Check actual job conditions before fabricating work. Report necessary changes in time to prevent needless work. Changes or additions, subject to additional compensation, which are made without written authorization and an agreed price, shall be at the Contractor’s risk and expense.

1.11 CUTTING AND PATCHINGA. All cutting and patching required for work of this Division is included herein. Coordination with General Contractor and other trades is imperative.

Contractor shall bear the responsibility for and the added expense of adjusting for improper holes, supports, etc.

1.12 ACCEPTANCE DEMONSTRATIONA. Upon completion of work, at a time to be designated by the Owner, the Contractor shall demonstrate for the Owner the operation of the electrical

installation, including any and all special items installed by him or installed under his supervision. Properly set automatic time switches to perform switching operations in accordance with schedules provided by the Owner’s representative, and demonstrate (using the manufacturer’s operating instructions) how to override and/or test time switches programming.

1.13 RECORD DRAWINGS, EQUIPMENT DATAA. Maintain one set of clean working drawings at the job site and enter daily such “as-built” information as feeder and services routes, pull box

locations and changes in layout or arrangement which occur during construction. Deliver completed drawings to the Owner.B. Deliver to the Owner’s representative three (3) copies of data sheets or other current manufacturer’s publications for each item of electrical

equipment furnished for the project including at least these data:1. Technical description and replaceable parts list.2. Physical description and installation instructions.3. User’s manual and operating instructions.4. Manufacturer’s Warranty.

1.14 CLEAN-UPA. Rid the premises of scrap materials, trash and debris both during construction and at the completion of the project. Leave the building and

surrounding area in a clean and orderly condition.

1.15 GUARANTEEA. Guarantee the installation free from defects of workmanship and material for a period of one year after Date of Certification of final payment and

promptly remedy any defects developing during this period, without charge.

1.16 TEMPORARY SERVICESA. Provide adequate and safe temporary electrical power and lighting throughout the construction and finishing of the premises. In addition to

special or unusual requirements, provide at least these items:

PART 2 - PRODUCTS

2.1 MATERIAL APPROVALA. All materials must be new and bear Underwriter’s Laboratories label. Materials that are not covered by UL testing standards shall be tested and

approved by an independent testing laboratory or a governmental agency. Material not in accordance with these specifications may be rejected either before or after installation.

2.2 CONDUITS AND OTHER RACEWAYSA. Rigid Steel: Hot-dipped galvanized.B. Intermediate Metal Conduit (IMC): Hot-dipped galvanized.C. Electrical Metallic Tubing (EMT): Electro-galvanized.D. Wireway: Code gauge steel, with knockouts and hinged cover, corrosion resistant gray baked enamel finish.E. Provide fittings and accessories approved for the purpose equal in all respects to the conduit or raceway. EMT connectors and couplings shall be

steel setscrew type indoors and steel compression type in wet locations and outdoors.

2.3 WIRES AND CABLESA. For power and lighting system 600V or less:

1. Conductor: minimum size #12 AWG.a. #12 and #10 AWG solid copper.b. #8 AWG and larger shall be stranded copper.

2. Insulation type:a. #12 to #1 AWG: THWN for wet or underground and THHN for dry locations.b. #1/0 through #4/0 AWG: XHHW (55 mils).c. #250 MCM and larger: XHHW (65 mils).d. Grounding wire: TW.

B. For signal and communications circuit:1. Special cables shall be as specified on drawings.2. Conductors for general use shall be stranded copper conductor, #16 AWG minimum, with THWN insulation for underground or wet

locations and THHN insulation for dry locations.C. Acceptable Products: General Electric, Anaconda, Okonite, Paranite or Triangle products conforming or exceeding applicable IPCEA standards.

2.4 OUTLET BOXES, JUNCTION AND PULL BOXESA. Outlet boxes: 4” square x 1-1/2” deep (or larger) galvanized sheet steel KO-type with plaster ring and cover for general interior use and cast metal

type FS or FD with matching screw covers for exterior and exposed interior locations (gasketed in damp or wet locations).B. Junctions boxes shall be same as outlet boxes up to 42 cu. In. and code-gauge steel in larger sizes with surface or flush-type screw-mounted trim

covers, both boxes and covers inhibitor-primed and painted inside out.C. Pull boxes shall be same as junction boxes unless indicated otherwise on the drawings, with covers.D. Telephone outlet boxes shall be the type and size required by the serving telephone company but not smaller than 4-11/16” square x 2-1/8” deep

with single gang-ring and Sierra #S-754N split plate bushing.

2.5 WIRING DEVICES AND PLATESA. Wiring devices and plates shall be by Pass and Seymour or approved equal.

1. Standard design:a. Switch and receptacles devices shall be plastic bodies, color shall be white unless noted otherwiseb. Wall plates shall be white plastic type, color shall be white unless noted otherwise.

2.6 CONDUIT HANGERSA. For individual conduit runs not directly fastened to the structure, use rod hangers manufactured by Caddy, Unistrut, or Powerstrut.B. For multiple conduit runs, use Unistrut or Powerstrut trapeze type conduit support designed for maximum deflection not greater than 1/8”.

2.7 WIRE CONNECTORSA. For wire sizes #8 AWG and smaller: Insulated pressure type (with live spring) rated 105°C, 600V, for building wiring and 1000V in signs or fixtures.

Scotchlok or Ideal. B. For wire size #6 AWG and larger: T&B or equivalent compression type with 3M #33+ or Plymouth “Slipknot Grey” tape insulation.

2.8 PANELBOARDSA. Construction: Cabinets shall be of code gauge, galvanized steel, surface or flush mounted as indicated. Doors shall be cold-rolled steel with

concealed hinges and flush catch and lock. All panels shall be keyed alike. Panels located adjacent to each other shall have identically sized enclosures and trims. Minimum panel width shall be 20”. Finish exposed part with one coat of primer and one coat of light grey enamel suitable for overpainting in field if desired.

B. Bus Bars: Provide ground block with full complement of terminals in addition to insulated neutral bus. Future breaker spaces shall have complete provision including busses and connecting hardware.

C. Manufacturers: Panelboards shall be General Electric Type “AQ” or type “AE” or equivalent products of Westinghouse, Square-D or Siemens-ITE.D. Circuit Breakers: Shall be quick-make, quick-break, molded case type:

1. 120/240 Volt Panels: Shall be General Electric Type “Q’ line, bolt-on type, with minimum symmetrical interrupting capacity as shown.2. Provide multi-pole units with common trip element.3. Circuit breakers used on “ON-OFF” control of fluorescent lighting (panelboard switching) shall be Underwriters’ Laboratories listed and

marked “SWD” to indicate their suitability.E. Identification: Provide screwed-on (no adhesives) Bakelite or photo-etched metallic nameplate identification on outside of each panel designation,

voltage and phase in minimum 1/8” high letters. Each panel shall contain a metal-framed circuit directory inside cover, with plastic protector.F. Complete shop drawings are required. See article 1.8.

2.9 INDIVIDUALLY MOUNTED MOTOR CONTROLLERSA. For Polyphase Motors: Combination motor circuit protector and magnetic starter, with 3-leg overload protection. Provide two interlock contacts of

the interchangeable open-close type. Provide hand-off-automatic selector switch, motor running pilot light and reset button in cover. Circuits 300V and over shall be provided with 120V control transformers.

B. Starters for fractional horsepower 120V motors shall be manual type unless shown otherwise, equipped with built-in overload protection.C. Acceptable manufacturers: General Electric, Siemens, Square D, Westinghouse, and Allen Bradley.

2.10 LIGHTINGA. Furnish and install all fixtures complete, including lamps and ballast ready for service.B. Supports: Proper supports and mounting accessories, such as hangers, stems, yokes, plaster frames, etc. shall be provided as required by the type

of ceiling installed. Where swivel canopies or ball aligners are specified, they shall cause fixture to hang plumb regardless of ceiling slope.C. Fixture Designation: Fixture types are designated on drawings. Where only one fixture designation is shown, it applies to all fixtures in that room or

area. For exact fixture count and location refer to reflected ceiling plan.D. Wire 1-lamp and 3-lamp fluorescent fixtures in tandem where required by code.E. Ballasts: Advance, GE, or Approved high frequency electronic, full light output, energy saving, Class “P”, high power factor, ETL certified, sound

rating “A” or as indicated on drawings.

2.11 MISCELLANEOUS MATERIALSA. Safety Switches: Heavy duty type, 600V, horsepower rated for motors, fused or non-fused as required. Mount in enclosure with NEMA rating as

required for the specific application General Electric, Square D or Westinghouse.

PART 3 - EXECUTION

3.1 GENERALA. Electric system layouts indicated on the drawings are generally diagrammatic and shall be followed as closely as actual construction and work

of other trades will permit. Govern exact routing of cable and wiring and the locations of outlets by the structure and equipment served. Take all dimensions from architectural drawings.

B. Consult all other drawings, verify scales and report and dimensional discrepancies or other conflicts with Owner before submitting bid.C. All home runs to panelboards are indicated as starting from the outlet nearest the panel and continuing in the general direction of that panel.

Continue such circuits to the panel as though the routes were completely indicated. Terminate homeruns of signal, alarm, and communication systems in a similar manner.

D. Avoid cutting and boring holes through structure or structural members wherever possible. Obtain prior approval of Owner and conform to all structural requirements when cutting or boring the structure is necessary and permitted.

E. Furnish and install all necessary hardware, hangers, blocking, brackets, bracing, runners, etc. required for equipment specified under this Section.

F. Provide necessary backing required to insure rigid mounting of outlet boxes.

3.2 WIRING METHODSA. The use of non-metallic (NM) cabling is not acceptable in any application.B. The use of metal-clad (MC) cabling is not acceptable for branch circuit home runs to panel boards and dedicated branch circuits.C. Minimum Raceway Size: 1/2-inch trade size.D. Outdoor - Apply raceway products as specified below, unless otherwise noted or indicated.

a. Exposed Conduit: Rigid steel conduit.b. Concealed Conduit, Aboveground: RNC, Type EPC-40-PVC.c. Underground Conduit: RNC, Type EPC-40-PVC, direct buried.d. Connection to Vibrating Equipment (Including Transformers and Pneumatic, Electric Solenoid, or Motor-Driven Equipment): LFMC.

E. Indoor - Apply raceway products as specified below, unless otherwise noted or indicated.a. Exposed, Not Subject to Physical Damage: Surface Metal Raceway in finished spaces and EMT in unfinished spaces.b. Exposed and Subject to Severe Physical Damage: IMC.c. Concealed in Ceilings and Interior Walls and Partitions: EMTor Metal-clad cable, Type MC.d. Connection to Vibrating Equipment (Including Transformers and Hydraulic, Pneumatic, Electric Solenoid, or Motor-Driven Equipment):

FMC, except use LFMC in damp or wet locations.e. Damp or Wet Locations: IMC.f. Raceways for Communications Cable in Spaces Used for Environmental Air: Plenum-type, communications cable raceway.g. Raceways for Communications Cable Risers in Vertical Shafts: Riser-type, communications cable raceway.h. Boxes and Enclosures: NEMA 250, Type 1, except use NEMA 250, Type 4, nonmetallic in damp or wet locations.

F. Apply conductor product as specified below, unless otherwise noted or indicated.a. Service Entrance: Type XHHW, single conductors in raceway.b. Exterior Feeders: Type XHHW, single conductors in raceway.c. Exposed, Interior, Feeders: Type THHN-THWN, single conductors in raceway.d. Feeders Concealed in Ceilings, Walls, Partitions, and Crawlspaces: Type THHN-THWN, single conductors in raceway or Metal-clad

cable, Type MC.e. Feeders Concealed in Concrete, below Slabs-on-Grade, and Underground: Type THHN-THWN, single conductors in raceway.f. Exposed, Interior, Branch Circuits, Including in Crawlspaces: Type THHN-THWN, single conductors in raceway.g. Branch Circuits Concealed in Ceilings, Walls, and Partitions: Type THHN-THWN, single conductors in raceway or Metal-clad cable,

Type MC.h. Branch Circuits Concealed in Concrete, below Slabs-on-Grade, and Underground: Type THHN-THWN, single conductors in raceway.i. Exterior Branch Circuits: Type XHHW, single conductors in raceway.j. Class 1 Control Circuits: Type THHN-THWN, in raceway.k. Class 2 Control Circuits: Power-limited cable, concealed in building finishes.

3.3 INSTALLATION OF CONDUITSA. General

1. Run all conduit unless otherwise noted or shown.2. Run all conduit parallel to or at right angles to center lines of columns and beams,3. Conduits above ceilings shall not obstruct removal of ceiling tiles.4. Conduits shall not cross and duct shaft or area designated as future duct shaft horizontally. Conduit risers when allowed in duct shaft

must be coordinated with Mechanical work to avoid any conflict.5. Conduits in exposed ceiling shall be kept tight to metal deck.

B. Conduit Supports1. Support conduits with Underwriter’s Laboratories listed steel conduit metal strips are not acceptable for conduit support. Use conduit

hangers for supports at intervals required by the NEC or applicable local code. Wires or sheet all conduits not fastened to structureand for all multiple conduit runs. Do not attach any conduit to mechanical ducts or pipes.

2. Individual conduits 1/2” and 3/4” size for lighting may be supported from ceiling support wires with Caddy clips only if acceptable tolocal code. Only one conduit is permitted to be attached to any ceiling support wire. Hang such conduit so as not to affect level ofceiling.

3. Avoid attaching conduit to fan plenums. When it is necessary to support conduit from fan plenum, provide a length of flexible conduitbetween portion attached to the fan plenum and portion attached to the building to minimize transmission of vibration to the buildingstructure.

C. Conduit Penetration1. Penetrating fire rated floor or wall: Install conduit in conduit sleeve or framed opening. Seal penetration with fire retardant sealant

specified herein.2. Penetrating roof or exterior wall: Avoid penetrating roof or exterior wall where possible. Where penetrations are necessary, building

weatherproof integrity must be preserved.3. Penetrating sound insulated or air plenum wall: Install conduit in conduit sleeve and seal penetration as detailed on the drawings.4. Penetrating non-fire rated dry wall: Conduit sleeves are not required. Penetrations must be sealed with plaster prior to painting.

Penetrations made after wall finish is applied must be as small as possible and provided with escutcheons, one on each side of wall.5. Penetrating suspended ceiling: Cut hole as small as possible to permit conduit penetration. Provide escutcheon for each conduit below

ceiling.

3.4 CONNECTIONS TO EQUIPMENTA. General

1. Furnish and install required power supply conduit and wiring to all equipment. See below for other wiring required.2. Furnish and install a disconnect switch immediately ahead of and adjacent to each magnetic motor starter or appliance unless the

motor appliance is located adjacent and within sight of the serving panelboard, circuit breaker or switch. Verify all equipmentnameplate current ratings prior to installation.

3. Install all rough-in work for equipment from approved shop drawings to suit the specific requirements of the equipment.4. Furnish and install manual thermal protection for all motors not integrally equipped with thermal protection.5. Furnish 120 Volt power to each control panel and time switch requiring a source of power to operate.

3.5 INSTALLATION OF WIRESA. Pull no wire into any portion of the conduit system until all construction work which might damage the wire has been completed.B. Install all wire continuous from outlet to outlet or terminal to terminal. Splices in cables when required shall be made in handholes, pull boxes or

junction boxes. Make branch circuit splices in outlet boxes with 8” of correctly color-coded tails left in the box.C. Splices in wires and cables shall be made utilizing materials and methods described herein before.D. Make all ground, neutral, and line connections to receptacle and wiring device terminals as recommended by manufacturer. Provide ground

jumper from outlet box to ground terminal of devices when the device is not approved for grounding through the mounting screws.E. Provide Brady wire markers where number of conductors in a box exceeds four (4).F. Megger and record insulation resistance of all 600 Volt insulated conductors size #4/0 and larger using 500 Volt megger for one minute. Make

tests with circuits isolated from source and load.

3.6 WIRE COLOR CODEA. Color coding shall be continuous for wire #12 through #10 AWG. Phase conductors #8 and larger and conductors of any size in cable

assemblies may have colored phasing tape at terminations. Color code wires as follows:Voltage Phase A Phase B Phase C Neutral Ground120/208V Black Red Blue White Green

3.7 IDENTIFICATIONA. Provide nameplates for switchgears, panelboards, and all similar devices. Nameplates shall be screwed (no adhesives) engraved Bakelite or

photo-etched metallic nameplate identification showing panel designation, voltage and phase in minimum 1/4” high letters.B. Provide dymo labels on all lighting switches and convenience and special purpose receptacles to show panel and circuit number to which the

device is connected.C. Each panelboard shall contain a metal-framed circuit directory inside cover, with plastic protector.D. Panelboard Schedule: After completion of work, provide typewritten updated panelboard schedules for all panelboards.

3.8 REMODELLING WORKA. Existing electrical wiring which will not be made obsolete and which will be disturbed due to construction changes required by this contract shall

be restored to operating condition. Where construction changes require, outlets and conduit runs shall be relocated. Extend conduits and pull in new wiring or install junction boxes and splice in new wiring.

B. Outlets from which fixtures, switches, receptacles, and/or other electrical devices are moved and which are not replaced or reused shall be removed, where outlet boxes, etc. are completely removed, the contractor shall cut off conduits and remove wiring.

C. Where conduits extending through floors are to be abandoned, the contractor shall cut and cap or plug conduit, and the conduit shall not protrude above floor.

D. Where existing conduit is to be abandoned, the conduit shall be removed if it is exposed, in a crawl space or in accessible ceiling. Where it is impossible to remove the conduit, it shall be cut off and capped or plugged.

E. Remove all existing wiring not reused or required to maintain continuity to circuits to remain.F. The contractor shall be held fully responsible for the proper restoration of all existing surfaces requiring patching, plastering, painting and/or

other repairs due to the installation of electrical work under the terms of this specification. Close all openings, repair all surfaces, etc. as required.

G. Maintain circuit continuity to areas outside of this work, provide new conduit and conductors as required to maintain continuity and maintain area as existing.

3.9 GROUNDINGA. Electrical service and separately derived alternating current system shall be grounded in accordance with NEC or applicable local code,

inclusive.B. Ground non-current carrying metal parts of electrical equipment enclosures, frames, conductor raceways or cable trays to provide a low

impedance path for line-to-ground fault current and to band all non-current carrying metal parts together. Provide ground conductor in each raceway system in addition to conductors shown. Equipment ground conductor shall be electrically and mechanically continuous from the electrical circuit source to the equipment to be grounded. Size conductors per NEC or applicable local code unless larger conductors are shown on drawings.

C. Grounding conductors shall be identified with green insulation. Where green insulation is not available on larger sizes, black insulation shall be used and suitable identified with green tape at each junction box or device enclosure.

SHEET

SHEET TITLE

ISSUE DATE

DRAWN BY

CHECKED BYAPPROVED BY

PROJECT NO.

REVISION

PROFESSIONAL OF RECORD:NOTIC

E: THIS

ARCHIT

ECTURAL A

ND E

NGIN

EERIN

G D

RAW

ING IS G

IVEN IN C

ONFID

ENCE A

ND S

HALL B

E U

SED O

NLY P

URSUANT T

O T

HE A

GREEMENT W

ITH T

HE A

RCHIT

ECT. NO O

THER U

SE, DIS

SEMIN

ATIO

N, OR D

UPLIC

ATIO

N M

AY B

E M

ADE W

ITHOUT P

RIO

R W

RIT

TEN

CONSENT O

F T

HE A

RCHIT

ECT. ALL C

OMMON L

AW

RIG

HTS O

F C

OPYRIG

HT A

ND O

THERW

ISE A

RE H

EREBY S

PECIF

ICALLY R

ESERVED.

CLIENT

2221 Schrock RoadColumbus, Ohio 43229-1547p 614.898.7100f 614.898.7570www.msconsultants.com

PROJECT

10/5

/202

1 3:

50:4

5 PM

ELECTRICAL SPECIFICATIONS

E002

GSG

JASON E. CHRISTOFF - PE No.PE.0056074EXP DATE: 10/31/2021

10/04/2021

MRM

10/04/2021

62-40487-06

HCA HEALTH ONE, LLC4500 E 9TH AVESTE 160DENVER, CO 80220

QUESTDIAGNOSTICS

# DATE DESCRIPTION

JJ

GFI

GFI

GFI

J

OUTLET MOUNTING SCHEDULEMOUNTING HEIGHTS ARE FROM FINISHED FLOOR TO CENTER OF FIXTURE. MOUNT OUTLETS AT 18"AFF UNLESS OTHERWISE NOTED BELOW OR ON PLAN. REFER TO ARCHITECTURAL ELEVATION FOR ADDITIONAL DETAILS. NOTE: NOT ALL ROOMS MAY BE PRESENT ON SPECIFIC PROJECT.

WAITING ROOM• USB OUTLETS @ CHAIRS - 38"AFF• USB OUTLETS @ TABLE - 24"AFF

PATIENT ENCOUNTER ROOM• COMPUTER OUTLETS/COUNTER RETURN - MOUNT BELOW COUNTER, 28"AFF• COUNTER CENTRIFUGE - MOUNT ABOVE COUNTER, 46"AFF, MOUNT 6" OFF WALL

SPECIAL SERVICES• COMPUTER OUTLETS/COUNTER RETURN - MOUNT BELOW COUNTER, 20"AFF• COUNTER CENTRIFUGE - MOUNT ABOVE COUNTER, 42"AFF, MOUNT 6" OFF WALL

SPECIMEN CONSOLIDATION• HIGH COUNTER - MOUNT BELOW COUNTER, 28" AFF• LOW COUNTER - MOUNT ABOVE COUNTER, 42"AFF

EMPLOYEE CONSULT• COMPUTER OUTLETS/COUNTER - MOUNT ABOVE COUNTER, 42"AFF, MOUNT 12"

OFF WALL.BREAKROOM

• COUNTER - MOUNT ABOVE COUNTER, 42"AFFPATIENT HOLD ROOM

• USB OUTLET - 38"AFF• TV AREA - 63"AFF

UNISEXTOILET

107

UNISEXTOILET

105

WAITINGROOM100

JANITOR/STORAGE

102

SPECIALSERVICES

01

PATIENTENCOUNTER

02

PATIENTENCOUNTER

03

SUPPLY103

SPECIMENCONSOLIDATION

104

EMPLOYEEBREAKROOM106

HALL101

USB

USBUSB

L1A:17L1A:19

L1A:21

L1A:23

L1A:27

L1A:29

22

1 1

3

2

L1A:25

L1A:31

PANEL L1A

APPROXIMATE+/- 65'

5

SHEET

SHEET TITLE

ISSUE DATE

DRAWN BY

CHECKED BYAPPROVED BY

PROJECT NO.

REVISION

PROFESSIONAL OF RECORD:NOTIC

E: THIS

ARCHIT

ECTURAL A

ND E

NGIN

EERIN

G D

RAW

ING IS G

IVEN IN C

ONFID

ENCE A

ND S

HALL B

E U

SED O

NLY P

URSUANT T

O T

HE A

GREEMENT W

ITH T

HE A

RCHIT

ECT. NO O

THER U

SE, DIS

SEMIN

ATIO

N, OR D

UPLIC

ATIO

N M

AY B

E M

ADE W

ITHOUT P

RIO

R W

RIT

TEN

CONSENT O

F T

HE A

RCHIT

ECT. ALL C

OMMON L

AW

RIG

HTS O

F C

OPYRIG

HT A

ND O

THERW

ISE A

RE H

EREBY S

PECIF

ICALLY R

ESERVED.

CLIENT

2221 Schrock RoadColumbus, Ohio 43229-1547p 614.898.7100f 614.898.7570www.msconsultants.com

PROJECT

10/5

/202

1 3:

50:4

9 PM

ELECTRICAL POWER PLAN

E101

GSG

JASON E. CHRISTOFF - PE No.PE.0056074EXP DATE: 10/31/2021

10/04/2021

MRM

10/04/2021

62-40487-06

HCA HEALTH ONE, LLC4500 E 9TH AVESTE 160DENVER, CO 80220

QUESTDIAGNOSTICS

GENERAL NOTESA LINE VOLTAGE WIRING SHALL BE RUN IN CONDUIT. INTERIOR CIRCUITS SHALL BE

CONCEALED IN WALLS OR CEILING SPACES. CIRCUITS IN CEILING SPACES SHALLBE RUN TIGHT TO STRUCTURE AND HORIZONTAL TO OR PERPENDICULAR WITHSTRUCTURAL MEMBERS.

B B.LOW VOLTAGE WIRING SHALL BE CONCEALED IN WALLS OR CEILING SPACES ANDSHALL BE RUN PERPENDICULAR WITH AND HORIZONTAL TO STRUCTURALMEMBERS. CIRCUITS WITHIN PLENUM CEILINGS SHALL BE PLENUM RATED OR RUNIN METALLIC CONDUIT (COORDINATE IN FIELD). LOW VOLTAGE WIRING SHALL BERUN IN CONDUIT WHERE NON-ACCESSIBLE AND WHERE SUBJECT TO PHYSICALDAMAGE.

C VERIFY VOLTAGE DROPS DO NOT EXCEED 3 PERCENT FOR BRANCH CIRCUITS, AND5 PERCENT TOTAL. OTHERWISE, INCREASE 120 VOLT BRANCH CONDUCTORS BYONE WIRE SIZE FOR EACH 75’ OF CONDUCTOR LENGTH.

D PROVIDE DISCONNECT SWITCHES AT ALL ELECTRICALLY POWERED EQUIPMENTAND FIXTURES (EVEN IF NOT SHOWN ON PLAN) UNLESS EQUIPMENT IS FURNISHEDBY MANUFACTURER WITH INTEGRAL SWITCH, OR UNLESS CIRCUIT BREAKER ISLOCKABLE IN THE OFF POSITION AND APPROVED BY THE AHJ. PROVIDE FINALCONNECTION FOR ALL ELECTRICALLY POWERED EQUIPMENT.

E VERIFY VOLTAGE AND AMPACITY OF EXISTING ELECTRICAL EQUIPMENT TO REMAIN.VERIFY ADDITONAL LOADS DO NOT OVERLOAD EXISTING PANELS, DISTRIBUTIONSYSTEMS OR SERVICE. NOTIFY ENGINEER OF ALL CONFLICTS WITH THE PLANS.

F COORDINATE FINAL LOCATION OF ALL OWNER PROVIDED EQUIPMENT IN FIELDPRIOR TO FINAL ELECTRICAL ROUGH IN. COORDINATE EXACT ELECTRICAL ANDLOW VOLTAGE REQUIREMENTS.

ELECTRICAL KEYNOTES1 PROVIDE TWO GANGED SWITCHES ON WALL OUTSIDE OF TESTING RESTROOM FOR

CONTROL OF HAND DRYER AND PLUMBING SOLENOID VALVES. SWITCHES TO BERED WITH RED FACEPLATE. SOLENOIDS TO BE NORMALLY OPEN TYPE PROVIDEDBY PLUMBING CONTRACTOR, FINAL ELECTRICAL CONNECTION BY ELECTRICALCONTRACTOR. SOLENOID SWITCH TO NORMALLY BE 'OFF' IN THE 'DOWN' POSITION.MOVING THE SWITCH INTO THE 'UP' POSITION SHALL TURN 'ON' AND CLOSE THESOLENOID. HAND DRYER SWITCH TO NORMALLY BE 'ON' IN THE 'DOWN' POSITION.MOVING THE SWITCH TO THE 'UP' POSITION SHALL TURN 'OFF' THE HAND DRYER.REFER TO WIRING DIAGRAM ON E601 FOR ADDITIONAL INFORMATION.

23 PROVIDE QUADPLEX RECEPTACLE AND TWO JUNCTION BOXES AT CABINET FOR

OWNER PROVIDED IT EQUIPMENT. PROVIDE 1” EMT STUBBED UP ABOVE CEILINGFROM JUNCTION BOXES FOR LOW VOLTAGE CABLING. PROVIDE WITH BUSHING ANDPULLCORD. COORDINATE EXACT LOCATION AND REQUIREMENTS IN FIELD WITHOWNER REPRESENTATIVE PRIOR TO ELECTRICAL ROUGH IN.

5 APPROXIMATE LOCATION OF EXISTING PANEL IN LANDLORD ELECTRICAL ROOM TOREMAIN. COORDINATE REUSE OF EXISTING CIRCUITS AND EXISTING SPAREAVAILABILITY PRIOR TO ELECTRICAL ROUGH IN. REFER TO PANEL SCHEDULE ANDONE LINE DIAGRAM FOR ADDITIONAL INFORMATION.

PLAN NORTH

# DATE DESCRIPTION

1/4" = 1'-0"1 POWER PLAN

WAITINGROOM100

UNISEXTOILET

107

UNISEXTOILET

105

HALL101

SPECIMENCONSOLIDATION

104

SUPPLY103

PATIENTENCOUNTER

03

PATIENTENCOUNTER

02

SPECIALSERVICES

01

JANITOR/STORAGE

102

R2EM R2 R2

R2R2

R2

R2EM

R2

R2

R2R2R2EM

R3EM R3

R3EM R3

R3 R3

R3EMR3

R3 R3EM

R3EMR3

R1E R1 R1 R1E

OS OS

EMPLOYEEBREAKROOM106

OS

OS

OS

OS

OSOS

OS

XW1

XW1

XW1

1

OS

OS

OS

SHEET

SHEET TITLE

ISSUE DATE

DRAWN BY

CHECKED BYAPPROVED BY

PROJECT NO.

REVISION

PROFESSIONAL OF RECORD:NOTIC

E: THIS

ARCHIT

ECTURAL A

ND E

NGIN

EERIN

G D

RAW

ING IS G

IVEN IN C

ONFID

ENCE A

ND S

HALL B

E U

SED O

NLY P

URSUANT T

O T

HE A

GREEMENT W

ITH T

HE A

RCHIT

ECT. NO O

THER U

SE, DIS

SEMIN

ATIO

N, OR D

UPLIC

ATIO

N M

AY B

E M

ADE W

ITHOUT P

RIO

R W

RIT

TEN

CONSENT O

F T

HE A

RCHIT

ECT. ALL C

OMMON L

AW

RIG

HTS O

F C

OPYRIG

HT A

ND O

THERW

ISE A

RE H

EREBY S

PECIF

ICALLY R

ESERVED.

CLIENT

2221 Schrock RoadColumbus, Ohio 43229-1547p 614.898.7100f 614.898.7570www.msconsultants.com

PROJECT

10/5

/202

1 3:

50:5

3 PM

ELECTRICAL LIGHTING PLAN

E201

GSG

JASON E. CHRISTOFF - PE No.PE.0056074EXP DATE: 10/31/2021

10/04/2021

MRM

10/04/2021

62-40487-06

HCA HEALTH ONE, LLC4500 E 9TH AVESTE 160DENVER, CO 80220

QUESTDIAGNOSTICS

LIGHTING CONTROL NARRATIVE – 2015 IECC

OCCUPANT SENSOR CONTROL – OCCUPANCY SENSOR SHALL TURN LIGHTS ON TO 50%. MANUAL SWITCH SHALL TURN LIGHTS ON TO 100%. 30 MINUTES OF NO ACTIVITY TURNS LIGHTS OFF. REACTIVATION OF MANUAL SWITCH TURNS LIGHTS OFF.

OCCUPANT SENSOR CONTROL (TOILET ROOMS) – OCCUPANCY SENSOR SHALL TURN LIGHTS ON TO 100%. MANUAL SWITCH SHALL TURN LIGHTS ON TO 100%. 30 MINUTES OF NO ACTIVITY TURNS LIGHTS OFF. REACTIVATION OF MANUAL SWITCH TURNS LIGHTS OFF.

ALL OTHER SPACES SHALL BE CONTROLLED VIA TIME CLOCK.

GENERAL NOTESA EMERGENCY FIXTURES SHALL BE SERVED WITH ADDITIONAL HOT CONDUCTOR TO

EMERGENCY BATTERY SUCH THAT EMERGENCY BATTERY REMAINS ENERGIZEDWHEN LIGHTS ARE SWITCHED OFF. FIXTURE SHALL BE NORMALLY CONTROLLEDVIA LOCAL CONTROL. FOR CODE REQUIRED EMERGENCY OPERATION THEFIXTURES SHALL BE WIRED SUCH THAT THE LOSS OF POWER INITIATESEMERGENCY OPERATION.

B LINE VOLTAGE WIRING SHALL BE RUN IN CONDUIT. USE OF NONMETALLIC “NM”CABLE IS STRICTLY PROHIBITED. INTERIOR CIRCUITS SHALL BE CONCEALED INWALLS OR CEILING SPACES. CIRCUITS IN CEILING SPACES SHALL BE RUN TIGHT TOSTRUCTURE AND HORIZONTAL TO OR PERPENDICULAR WITH STRUCTURALMEMBERS.

C WIRE ALL EXIT, EGRESS, REMOTE EMERGENCY AND NIGHT LIGHTS TO LOCALLIGHTING CIRCUIT AHEAD OF ANY SWITCHING AND TIME CLOCK.

D REFER TO SHEET E601 FOR LIGHTING FIXTURE SCHEDULE

LIGHTING KEYNOTES1 CONNECT NEW LIGHTING FIXTURES TO EXISTING LIGHTING CIRCUIT. REUSE WIRING

AND CONDUIT TO FULLEST EXTENT POSSIBLE. PROVIDE ADDITIONAL WIRE ASNECESSARY TO MAKE FINAL CONNECTIONS. FIELD VERIFY EXACT REQUIREMENTS.

PLAN NORTH

# DATE DESCRIPTION

1/4" = 1'-0"1 LIGHTING PLAN

EXISTING FEEDER TO REMAIN.

PANEL L1A

208Y/120V3Ø/4W

EXISTING PANEL TO REMAIN. COORDINATE AND FIELD VERIFY EXACT LOCATION AND REQUIREMENTS WITH LANDLORD REPRESENTATIVE.

SWITCHES ON WALL OUTSIDE OF TESTING RESTROOM FOR CONTROL OF HAND DRYER AND PLUMBING SOLENOID VALVES. SOLENOID SWITCH TO TURN 'ON' AND CLOSE THE SOLENOID IN THE 'UP' POSITION. SWITCH TO CONTROL HAND DRYER TO TURN 'OFF' THE HAND DRYER IN THE 'UP' POSITION. REFER TO WIRING DIAGRAM ON E601 FOR ADDITIONAL INFORMATION.

DOUBLE GANG SWITCH

HAND DRYER CIRCUT

GENERAL CIRCUIT

HAND DRYER

CW SOLENOID120V, NORMALLY OPEN

HW SOLENOID120V, NORMALLY OPEN

SHEET

SHEET TITLE

ISSUE DATE

DRAWN BY

CHECKED BYAPPROVED BY

PROJECT NO.

REVISION

PROFESSIONAL OF RECORD:NOTIC

E: THIS

ARCHIT

ECTURAL A

ND E

NGIN

EERIN

G D

RAW

ING IS G

IVEN IN C

ONFID

ENCE A

ND S

HALL B

E U

SED O

NLY P

URSUANT T

O T

HE A

GREEMENT W

ITH T

HE A

RCHIT

ECT. NO O

THER U

SE, DIS

SEMIN

ATIO

N, OR D

UPLIC

ATIO

N M

AY B

E M

ADE W

ITHOUT P

RIO

R W

RIT

TEN

CONSENT O

F T

HE A

RCHIT

ECT. ALL C

OMMON L

AW

RIG

HTS O

F C

OPYRIG

HT A

ND O

THERW

ISE A

RE H

EREBY S

PECIF

ICALLY R

ESERVED.

CLIENT

2221 Schrock RoadColumbus, Ohio 43229-1547p 614.898.7100f 614.898.7570www.msconsultants.com

PROJECT

10/5

/202

1 3:

50:5

5 PM

ELECTRICAL SCHEDULES

E601

GSG

JASON E. CHRISTOFF - PE No.PE.0056074EXP DATE: 10/31/2021

10/04/2021

MRM

10/04/2021

62-40487-06

HCA HEALTH ONE, LLC4500 E 9TH AVESTE 160DENVER, CO 80220

QUESTDIAGNOSTICS

LIGHTING FIXTURE SCHEDULECONTRACTOR TO VERIFY CORRECT MODEL NUMBER PRIOR TO ORDERING

MOUNTING LEGEND:C - CEILING R - RECESSED G - GRID S - SUSPENDED W - WALL MOUNTED WR - WALL RECESSED CV - COVE UC - UNDER COUNTER RF - ROOF MOUNTED

TYPE MARKDESCRIPTION

BASE OF DESIGN FIXTUREREMARKSMNT # MANUFACTURER MODEL TYPE WATTAGE VOLTAGE

R 1 6" LED DOWNLIGHT LITHONIA LDN6 35 15 L06 WR LSS MVOLT GZ10 LED 17.5 120R 1E 6" LED DOWNLIGHT LITHONIA LDN6 35 15 L06 WR LSS MVOLT GZ10 ELSD LED 17.5 120 ALTERNATE: IN LIEU OF EMERGENCY BACKUP OPTION

PROVIDE R1 FIXTURE WITH WALL MOUNTED EMERGENCYLIGHT (LITHONIA #EU2L) LOCATED ON ADJACENT WALL.

R 2 2'x2' RECESSED LED TROFFER LITHONIA 2BLT2 33L ADSM EZ1 LP835 LED 26 120 ALTERNATE: PROVIDE FLAT PANEL LED FIXTURE (LITHONIA #EPANL 2X2 3400LM 80CRI 35K)

R 2EM 2'x2' RECESSED LED TROFFER W/ EMERGENCY BACKUP LITHONIA 2BLT2 33L ADSM EZ1 LP835 E10WLCP LED 26 120 ALTERNATE: PROVIDE FLAT PANEL LED FIXTURE (LITHONIA #EPANL 2X2 3400LM 80CRI 35K) WITH WALL MOUNTEDEMERGENCY LIGHT (LITHONIA # EU2L) LOCATED ONADJACENT WALL

R 3 2'x4' RECESSED LED TROFFER LITHONIA 2BLT4 40L ADSM EZ1 LP835 LED 31 120 ALTERNATE: PROVIDE FLAT PANEL LED FIXTURE. (LITHONIA# EPANL 2X4 4000LM 80CRI 35K).

R 3EM 2'x4' RECESSED LED TROFFER W/ EMERGENCY BACKUP LITHONIA 2BLT4 40L ADSM EZ1 LP835 EL14L LED 31 120 ALTERNATE: PROVIDE FLAT PANEL LED FIXTURE (LITHONIA #EPANL 2X4 4000LM 80CRI 35K) WITH WITH WALL MOUNTEDEMERGENCY LIGHT (LITHONIA # EU2L) LOCATED ONADJACENT WALL.

XW 1 WALL MOUNTED EXIT SIGN COMBO LITHONIA LQM S 3 R 120/277 EL N LED 3 120

N.T.S.2 ONE LINE DIAGRAMN.T.S.1 TESTING SWITCHES

# DATE DESCRIPTION

ALL BREAKERS ARE EXISTING TO REMAIN UNLESS OTHERWISE NOTED. EXISTING CIRCUIT INFORMATION FROM BEST SOURCE AVAILABLE, CONTRACTOR TO COORDINATE AND FIELDVERIFY EXISTING CIRCUITS TO REMAIN AND CIRCUIT AVAILABILITY PRIOR TO ELECTRICAL ROUGH-IN. REUSE EXISTING CIRCUITS/SPARES TO EXTENT POSSIBLE. PROVIDE ADDITIONALBREAKERS IN PANEL AS REQUIRED. REVISE PANEL SCHEDULES TO AS-BUILT CONDITIONS AT COMPLETION OF WORK.

E = EXISTING BRANCH CIRCUIT AND ASSOCIATED DEVICES/EQUIPMENT TO REMAIN.G = GROUND FAULT CIRCUIT INTERRUPTING TYPE BREAKER.L = LOCK ON DEVICE.N = PROVIDE NEW CIRCUIT BREAKER AS INDICATED IN EXISTING SPACE.R = EXISTING EQUIPMENT TO BE RELOCATED OR REPLACED. ASSOCIATED CIRCUIT TO REMAIN. REUSE EXISTING CONDUIT AND WIRE TO EXTENT POSSIBLE. PROVIDE ADDITIONALCONDUIT AND WIRE AS REQUIRED TO EXTEND CIRCUIT TO NEW EQUIPMENT LOCATION.T = CIRCUIT CONTROLLED BY TIMECLOCK.

Notes:

Total Est. Demand: 24.93 ATotal Conn.: 24.93 A

Total Est. Demand: 8.980 kVAReceptacle 7080 VA 100.00% 7080 VA Total Conn. Load: 8.980 kVAEquipment 1900 VA 100.00% 1900 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Load: 2.310 kVA 2.520 kVA 4.150 kVA41 STE 150 RECEPT -- 20 A 1 E 0.000 0.000 E 1 20 A -- SPARE 4239 STE 150 RECEPT -- 20 A 1 E 0.000 0.000 ... 1 20 A -- STE 150 RECEPT 4037 STE 150 RECEPT -- 20 A 1 E 0.000 0.000 E 1 20 A -- LIGHT CONTROL RELAYS 3835 STE 150 RECEPT -- 20 A 1 E 0.000 0.000 E 1 20 A -- SUITE 170 DED REC 3633 STE 150 PARENT RECEPT -- 20 A 1 E 0.000 0.000 E 1 20 A -- STE 140 DED REC 3431 RCPT - BREAK ROOM... 1-#12, 1-#12, 1-#12 20 A 1 1.000 0.000 E 1 20 A -- RECEPT 3229 RCPT - SPEC CON 1-#12, 1-#12, 1-#12 20 A 1 1.580 0.000 E 1 20 A -- RECEPT 3027 RCPT - PATIENT ENCOUNTER 03 1-#12, 1-#12, 1-#12 20 A 1 1.440 0.000 E 1 20 A -- RECEPT 2825 RCPT - BREAK ROOM 106 1-#12, 1-#12, 1-#12 20 A 1 0.360 0.000 E 1 20 A -- RECEPT 2623 RCPT - SPECIAL SERVICES 01 1-#12, 1-#12, 1-#12 20 A 1 1.620 0.000 ... 1 20 A -- RECEPT SUITE 2421 RCPT - WAITING ROOM 100 1-#12, 1-#12, 1-#12 20 A 1 1.080 0.000 E 1 20 A -- RECEPT LTG 2219 HAND DRYER 107 1-#12, 1-#12, 1-#12 20 A 1 0.950 0.000 E 1 20 A -- RECEPT 2017 HAND DRYER 105 1-#12, 1-#12, 1-#12 20 A 1 0.950 0.000 E 1 20 A -- RECEPT 1815 LOBBY WALL SCONCES -- 20 A 1 E 0.000 0.000 E 1 20 A -- COPIER 1613 UH-13 -- 20 A 1 E 0.000 0.000 E 1 20 A -- RECEPT SUITE 140 1411 UH-11,12 -- 20 A 1 E 0.000 0.000 E 1 20 A -- WEST DOOR OPERATOR 129 SPARE -- 20 A 1 E 0.000 0.000 E 1 20 A -- 1ST FL RECEPT 107 SITE LTG -- 20 A 1 E 0.000 0.000 E 1 20 A -- TEL RECEPT 85 SITE LTG -- 20 A 1 E 0.000 0.000 E 1 20 A -- 1ST FL RECEPT EWC 63 DOOR OP & CUH1 -- 20 A 1 E 0.000 0.000 E 1 20 A -- 1ST FL RECEPT AMP 41 1ST FL LOBBY LTG -- 20 A 1 E 0.000 0.000 E 1 20 A -- 1ST FL RECEPT 2

CK Circuit Description Wire Size CB P NA B C

N P CB Wire Size Circuit Description CK

Enclosure: TYPE 1 MCB Rating: 225 AMounting: SURFACE Wires: 4 Main Type: MLO

Supply From: EXISTING Phases: 3 Frame Rating: 225 ALocation: Volts: 208Y/120V A.I.C. Rating: EXISTING

Panel: L1AEXISTING

1. THESE DOCUMENTS ARE INTENDED TO ILLUSTRATE CLIENTPREFERENCES AND MINIMUM ACCEPTABLE CRITERIA FOR THISPROJECT. IN ADDITION THESE DOCUMENTS ARE INTENDED TOFACILITATE A DEGREE OF PRELIMINARY COORDINATION AMONGTHE TRADES. HOWEVER NOTHING CONTAINED IN THESEDOCUMENTS SHALL DIMINISH OR NEGATE THE CONTRACTORSRESPONSIBILITIES AND OBLIGATIONS FOR COMPLETE,FUNCTIONAL AND PROPERLY COORDINATED SYSTEM.

2. ALTHOUGH THE LOCATIONS AND TYPES OF FIRE ALARM SYSTEMDEVICES AND EQUIPMENT MAY BE SHOWN ON THE DRAWINGS.THE CONTRACTOR SHALL BE RESPONSIBLE TO INSURE THAT THENUMBER, TYPE, AND LOCATIONS OF DEVICES COMPLIES WITH"NFPA" STANDARDS. ALL GOVERNING CODES AND APPROVALSFROM AUTHORITIES HAVE JURISDICTION. WHEREVER SHOWN ONTHE DRAWINGS SUCH AS SYMMETRY WITH RESPECT TOCORRIDORS AND OTHER BUILDING GEOMETRY, POSITIONING WITHRESPECT TO LIGHTING FIXTURES, AND OTHER PERTINENT ANDRELATIVE CONDITIONS. IT SHALL BE THE CONTRACTORSRESPONSIBILITY TO MAKE ALL ROUGH-IN AND FINALCOORDINATION OF ALL FIRE ALARM SYSTEM COMPONENTS WITHALL OTHER TRADES AND BUILDING FEATURES.

ANNU

NCIA

TES

ALAR

M S

IGNA

L AT

CO

NTRO

L

PANE

L AN

D RE

MOT

E AN

NUNC

IATO

R

ANNU

NCIA

TES

SUPE

RVIS

ORY

SIG

NAL

AT

CONT

ROL

PANE

L AN

D RE

MOT

E AN

NUNC

IATO

R

ANNU

NCIA

TES

TROU

BLE

SIGN

AL A

T CO

NTRO

L

PANE

L AN

D RE

MOT

E AN

NUNC

IATO

R

TRAN

SMIT

S AL

ARM

SIG

NAL

TO U

L LI

STED

CENT

RAL

STAT

ION

TRAN

SMIT

S SU

PERV

ISOR

Y SI

GNAL

TO

UL

LIST

ED C

ENTR

AL S

TATI

ON

TRAN

SMIT

S TR

OUBL

E SI

GNAL

TO

UL

LIST

ED

CENT

RAL

STAT

ION

SHUT

S DO

WN

ALL

RTU'

S

SHUT

S DO

WN

RTU

ACTI

VATE

S IN

TERI

OR H

ORN/

STRO

BES

ACTI

VATE

S EX

TERI

OR H

ORN/

STRO

BES

SPRINKLER SYSTEM-WATERFLOW SWITCH

-VALVE TAMPER SWITCH

SMOKE DETECTORS

-RTU'S-FACP

MANUAL PULL STATIONS

ABNORMAL CIRCUIT OR DEVICE

-RESTROOMS (N/A)

ELECTRONIC SAFETY AND SECURITY LINETYPES

FIRE ALARM

FAC

FACP

TS

TPR

FAA

FS

R/THD

ELECTRONIC DETECTION AND ALARM

ALARM, CHECK VALVE

ALARM, FIRE, COMMUNICATOR

ALARM, FIRE, CONTROL PANEL

ALARM, GONG

ALARM, HORN/LIGHT, ONE ASSEMBLY

ALARM, LAMP LIGHT, SIGNAL LIGHT, STROBE

ALARM, TAMPER SWITCH

ALARM, TRANSPONDER OR TRANSMITTER

DETECTION SWITCH, VALVE TAMPER

DETECTOR, FLAME FLICKER

DETECTOR, FLOW SWITCH

DETECTOR, SMOKE

FIRE ALARM ANNUNCIATOR PANEL

FIRE ALARM STATION, MANUAL PULL

DETECTOR, HEAT, COMBINATION

#

72" (

6'-0

") U

.N.O

.

TOP

OF

CAB

INET

48" (

4'-0

") U

.N.O

.

TOP

OF

DEV

ICE

NOTES:1. HEIGHTS SHOWN ARE TYPICAL TO CENTERLINE OF BOX UNLESS NOTED OTHERWISE.

2. WHEREVER DEVICES ARE INDICATED TO BE ABOVE DOORS, DEVICE SHALL BE CENTERED BETWEEN TOP OF DOOR TRIM AND CEILING LINE.

3. MOUNTING HEIGHTS SHOWN ON ARCHITECTURAL ELEVATIONS SHALL GOVERN OVER THOSE SHOWN ABOVE.

4. FOR CEILINGS BELOW 7'-4", FIRE ALARM STROBE OR HORN/STROBES SHALL BE WALL MOUNTED 6" BELOW FINISHED CEILING.

FINISHED FLOOR

80" (

PER

AD

A) U

.N.O

.

BOTT

OM

OF

DEV

ICE FACPFAA

FS

N.T.S.

PROVISION AND INSTALLATION OF A COMPLETE FIRE ALARM SYSTEM WILL BEA JOINT EFFORT BETWEEN THE FIRE ALARM VENDOR AND THE ELECTRICALCONTRACTOR.

BUILDING/ELECTRICAL CONTRACTOR(S) ARE RESPONSIBLE FOR "FA"INSTALLATION, INCLUSIVE OF ALL COSTS FOR DESIGN OF SYSTEM,MATERIALS, LABOR TO INSTALL, AND ALL PERMIT FEES.

THE FIRE ALARM VENDOR SHALL BE RESPONSIBLE FOR FURNISHING ALL FIREALARM SYSTEM EQUIPMENT, ANY SPECIAL BACK BOXES REQUIRED,PREPARING ALL FIRE ALARM SYSTEM DRAWINGS, CALCULATIONS, EQUIPMENTSUBMITTALS, AND PERMIT SUBMISSION TO THE LOCAL AUTHORITIES HAVINGJURISDICTION. IN ADDITION FIRE ALARM VENDOR SHALL TEST AND CERTIFYTHE FIRE ALARM SYSTEM AND SHALL DEMONSTRATE THE SYSTEMOPERATION TO LOCAL GOVERNING BODIES.THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALLREQUIRED EMPTY CONDUITS, OUTLET BOXES, 120VOLT OUTLETS REQUIREDAND SHALL INSTALL ALL EQUIPMENT. SPECIAL BACK BOXES. ASSOCIATEDLOW VOLTAGE WIRING AND ALL TERMINATION FOR FIRE ALARM SYSTEMEQUIPMENT.

THE FIRE ALARM SYSTEM DEVICE LOCATION SHOWN ON THE CONTRACTDOCUMENTS IS FOR ESTIMATING PURPOSES ONLY. THE ELECTRICALCONTRACTOR MUST USE THE FIRE ALARM VENDOR PROVIDED DRAWINGSFOR INSTALLATION.

1. FIRE ALARM SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITHTHE REQUIREMENTS OF THE INTERNATIONAL BUILDING CODE, THENATIONAL ELECTRIC CODE AND MEET ALL LOCALLY ENFORCED CODESAND ADA REQUIREMENTS. FIRE ALARM SYSTEM SHALL BE SUBMITTEDTO LOCAL FIREMARSHAL FOR APPROVAL PRIOR TO INSTALLATION.

2. ALL DEVICE LOCATIONS AND RATINGS ARE APPROXIMATE AND SHALL BEADJUSTED AND MODIFIED BY THE MANUFACTURER AS NECESSARY FORA FULLY COMPLIANT SYSTEM.

3. ALL CABLE SHALL BE PER FIRE ALARM VENDOR RECOMMENDATIONS.

4. ALL JUNCTION BOXES AND CONDUIT ASSOCIATED WITH THE FIRE ALARMSYSTEM SHALL BE PAINTED RED.

5. DEVICE MOUNTING HEIGHT TO BE COORDINATED AND APPROVEDBY AUTHORITIES HAVING JURISDICTION.

6.

7.

TO AVOID CONTAMINATION AND DUST ACCUMULATION IN THESMOKE DETECTORS, IT IS RECOMMENDED THAT THE SMOKEDETECTORS NOT BE INSTALLED UNTIL AFTER CONSTRUCTION ISCOMPLETED AND THE SUBJECT AREA HAS BEEN CLEANED.THESUPPLIER IS NOT RESPONSIBLE FOR DUST ACCUMULATION INSMOKE DETECTORS AND WILL NOT WARRANTEE DEVICES THATHAVE NOT BEEN PROPERLY MAINTAINED. WHEN DETECTORS AREINSTALLED. PROTECTIVE COVERS SHALL BE INSTALLED OVEREACH DETECTOR AND REMOVED BY AUTHORIZED SERVICE PERSONNEL.

ALL FIRE ALARM SYSTEM WIRING SHALL BE CLEAR FROMSHORTS, OPENS AND GROUNDS.

8. CONDUIT AND JUNCTION BOX LOCATIONS ARE DIAGRAMMATICONLY, EXACT LOCATIONS MAY VARY DUE TO FIELD CONDITIONS.ACTUAL INSTALLATION LOCATIONS SHALL BE DETERMINED BY THEINSTALLING CONTRACTOR.

9. DO NOT LOCATE SMOKE DETECTORS WITHIN 3 FEET OF SUPPLY AIRVENTS.

10. SIGNALING CIRCUIT WIRE RUNS ARE CRITICAL. ANY INCREASE INLENGTH OF WIRE MAY AFFECT CIRCUIT CONFIGURATION.

11.

12.

DRAWING IS DIAGRAMMATIC, COORDINATE IN FIELD EXACT ROUTINGAND INSTALLATION METHODS.

13.

PROVIDE AS-BUILT DRAWING TO SAFETY MANAGER UPONCOMPLETION OF ALL WORK.

14.

PROVIDE DUCT SMOKE DETECTORS AS REQUIRED BY LOCALAUTHORITY HAVING JURISDICTION.

15.

ALL DUCT MOUNTED DETECTORS ARE MOUNTED BY THE MECHANICALCONTRACTOR AND WIRED BY THE FIRE ALARM CONTRACTOR.

16.

FINAL LOCATION OF ANNUNCIATION PANEL SHALL BE COORDINATEDWITH ALL OTHER TRADES AND PRIOR TO INSTALLATION.

17.

PROVIDE REMOTE TEST STATION, FOR DUCT SMOKE DETECTORS, IFREQUIRED BY LOCAL CODES.

PROVIDED SMOKE DETECTOR AT FIRE ALARM CONTROL PANEL.

NOTICE TO CONTRACTOR

FIRE ALARMMATRIX WITHOCCUPANTNOTIFICATION

1EQUIPMENT/DEVICE MOUNTING HEIGHTS

FIRE ALARM SYMBOLS AND LINETYPES LEGEND

FIRE ALARM DESCRIPTION

FIRE ALARM SYSTEM NOTES

AABORT STATION, MANUAL PULL

1PH SINGLE-PHASE1P SINGLE POLE

1WAY ONE-WAY2/C TWO-CONDUCTOR

2WAY TWO-WAY3/C THREE-CONDUCTOR3PH THREE-PHASE

3WAY THREE-WAY4/C FOUR-CONDUCTOR

4PDT FOUR-POLE DOUBLE THROW4PST FOUR-POLE SINGLE THROW4W FOUR-WIRE

4WAY FOUR-WAYAIC AMPERE INTERRUPTING CAPACITYASC AMPS SHORT CIRCUIT ABOVE SUSPENDED

CEILING;ASPHALT SURFACE COURSE

ATS AUTOMATIC TRANSFER SWITCHAWG AMERICAN WIRE GAUGEBIL BASIC INSULATION LEVELCB CIRCUIT BREAKERCLF CURRENT LIMITING FUSECT CURRENT TRANSFORMER CERAMIC TILE; COUNTdB DECIBEL

DPDT DOUBLE POLE, DOUBLE THROWDPST DOUBLE POLE, SINGLE THROW

DS DISCONNECT SWITCH DOUBLE STRENGTH (GLASS); DOWNSPOUTEPO EMERGENCY POWER OFFFC FOOTCANDLE FILE CABINETFLA FULL LOAD AMPS

F FRAME/FUSEFVNR FULL VOLTAGE NON-REVERSINGFVR FULL VOLTAGE REVERSINGGFCI GROUND FAULT

CIRCUITHOA HAND-OFF-AUTOMATICHP HORSEPOWER HEAT PUMP; HIGH PRESSUREIC INTERRUPTING CAPACITY IRONING CABINET

J-BOX JUNCTION BOXLTG LIGHTINGMCB MAIN CIRCUIT BREAKER METAL CORNER BEADMCC MOTOR CONTROL CENTERMTS MANUAL TRANSFER SWITCHNC NORMALLY CLOSED NOISE CRITERIA; NURSE CALLNF NONFUSEDNL NIGHT LIGHTNO NORMALLY OPEN NUMBER

OCB OIL CIRCUIT BREAKEROCR OIL CIRCUIT RECLOSEROGA OIL GAGEOL OVERLOAD

OLVL OIL LEVELPB PUSHBUTTON PAINTED BASE;

PANELBOARD;PANIC BAR;PE PHOTOELECTRICPNEUMATIC ELECTRICRCPT RECEPTACLE

SCC SHORT CIRCUIT CAPACITYSPDT SINGLE POLE, DOUBLE THROWSPST SINGLE POLE, SINGLE THROW

ST SINGLE THROW STAIRS; STREETSW SWITCH SIDEWALK

SWBD SWITCHBOARDSWGR SWITCHGEAR

T TRIP RATINGTL TWIST LOCKTP TWISTED PAIR TELEPHONE POLE; TOTAL PRESSURE

TPS TWISTED PAIR SHIELDEDUPS UNINTERRUPTIBLE POWER SUPPLYUTP UNTWISTED PAIRVFD VARIABLE FREQUENCY DRIVE

XFMR TRANSFORMER

ABBREVIATION TERM SHARED ABBREVIATION

SHEET

SHEET TITLE

ISSUE DATE

DRAWN BY

CHECKED BYAPPROVED BY

PROJECT NO.

REVISION

FOR REFERENCE

ONLY

NOTIC

E: THIS

ARCHIT

ECTURAL A

ND E

NGIN

EERIN

G D

RAW

ING IS G

IVEN IN C

ONFID

ENCE A

ND S

HALL B

E U

SED O

NLY P

URSUANT T

O T

HE A

GREEMENT W

ITH T

HE A

RCHIT

ECT. NO O

THER U

SE, DIS

SEMIN

ATIO

N, OR D

UPLIC

ATIO

N M

AY B

E M

ADE W

ITHOUT P

RIO

R W

RIT

TEN

CONSENT O

F T

HE A

RCHIT

ECT. ALL C

OMMON L

AW

RIG

HTS O

F C

OPYRIG

HT A

ND O

THERW

ISE A

RE H

EREBY S

PECIF

ICALLY R

ESERVED.

CLIENT

2221 Schrock RoadColumbus, Ohio 43229-1547p 614.898.7100f 614.898.7570www.msconsultants.com

PROJECT

10/5

/202

1 3:

50:5

8 PM

FIRE ALARM GENERAL NOTES

FA001

JMM

MRM

10/04/2021

62-40487-06

HCA HEALTH ONE, LLC4500 E 9TH AVESTE 160DENVER, CO 80220

QUESTDIAGNOSTICS

# DATE DESCRIPTION

EMPLOYEEBREAKROOM

106

SPECIMENCONSOLIDATION

104SUPPLY

103

PATIENTENCOUNTER

03

PATIENTENCOUNTER

02

SPECIALSERVICES

01

WAITINGROOM

100

UNISEXTOILET

107

UNISEXTOILET

105

HALL101

JANITOR/STORAGE

102

SHEET

SHEET TITLE

ISSUE DATE

DRAWN BY

CHECKED BYAPPROVED BY

PROJECT NO.

REVISION

FOR REFERENCE

ONLY

NOTIC

E: THIS

ARCHIT

ECTURAL A

ND E

NGIN

EERIN

G D

RAW

ING IS G

IVEN IN C

ONFID

ENCE A

ND S

HALL B

E U

SED O

NLY P

URSUANT T

O T

HE A

GREEMENT W

ITH T

HE A

RCHIT

ECT. NO O

THER U

SE, DIS

SEMIN

ATIO

N, OR D

UPLIC

ATIO

N M

AY B

E M

ADE W

ITHOUT P

RIO

R W

RIT

TEN

CONSENT O

F T

HE A

RCHIT

ECT. ALL C

OMMON L

AW

RIG

HTS O

F C

OPYRIG

HT A

ND O

THERW

ISE A

RE H

EREBY S

PECIF

ICALLY R

ESERVED.

CLIENT

2221 Schrock RoadColumbus, Ohio 43229-1547p 614.898.7100f 614.898.7570www.msconsultants.com

PROJECT

10/5

/202

1 3:

50:5

8 PM

FIRE ALARM PLAN

FA101

JMM

MRM

10/04/2021

62-40487-06

HCA HEALTH ONE, LLC4500 E 9TH AVESTE 160DENVER, CO 80220

QUESTDIAGNOSTICS

GENERAL NOTESA ALL DEVICES ARE SHOWN DIAGRAMMATRICALLY AND SHALL BE COORDINATED

WITH EQUIPMENT PROVIDED BY SUCCESSFUL BIDDING CONTRACTOR.

PLAN NORTH

# DATE DESCRIPTION

1/4" = 1'-0"1 FIRE ALARM PLAN


Recommended