Walls
(North) 0 0 0 0
(East) 0 0 0 0
(West) 19.55 0.81 18 285.77
(South) 9.39 0.81 18 137.19 422.96
Ceiling 0 0 0 0
Floor 0 0 0 0 T
Windows 18
(North) 0 0 0 0 18
(East)0 0 0 0
(West) 6.19 6.7 18 746.27
(South) 3.09 6.7 18 373.14 1119.41
Doors 0 0 0 0 0
Infiltration859.75 859.75
2402.12
(Safety factor Qspace )= 2642.33
Area (m2) Uoverall(W/m2.oC)
T (oC) Qloss (W)
Qspace
=
8/9/2019 Heating Load Third Floor
2/95
v L C Qv
0.78 11.74 23.71 278.36
0.78 24.52 23.71 581.39
859.75
Q total (watt) Q wall (w) Q win (w)
95330.38 86663.99 13386.8 41125.4
% 100 100 15.45 47.45
Q total (watt)
with S.F
8/9/2019 Heating Load Third Floor
3/95
Q inf (w) Q door (w)
29619.47 2532.31
34.18 2.92
8/9/2019 Heating Load Third Floor
4/95
Walls
(North) 0 0 0 0
(East) 0 0 0 0(West) 9 0.81 18 131.49
(South) 0 0 0 0
Ceiling 0 0 0 0
Floor 0 0 0 0
Windows
(North) 0 0 0 0
(East) 0 0 0 0
(West) 3.09 6.7 18 373.14
(South) 0 0 0 0
Doors 0 0 0 0
Infiltration 278.36
782.99
861.28
Area (m2) Uoverall(W/m2.oC)
T (oC) Qloss (W)
Qspace
=
(Safety factor * Qspace )=
8/9/2019 Heating Load Third Floor
5/95
131.49
T v L C Qv
18 0.78 11.74 23.71 278.36
373.14
0
278.36
8/9/2019 Heating Load Third Floor
6/95
Walls
(North) 0 0 0 0
(East) 0 0 0 0(West) 22.89 0.81 18 334.6
(South) 0 0 0 0
Ceiling 0 0 0 0
Floor 0 0 0 0
Windows
(North) 0 0 0 0
(East) 0 0 0 0
(West)9.28 6.7 18 1119.41
(South) 0 0 0 0
Doors 0 0 0 0
Infiltration 859.75
2313.76
2545.14
Area (m2) Uoverall(W/m2.oC)
T (oC) Qloss (W)
Qspace
=
(Safety factor * Qspace )=
8/9/2019 Heating Load Third Floor
7/95
334.6
T v L C Qv
18 0.78 11.74 23.71 278.36
18 0.78 24.52 23.71 581.39
859.75
1119.41
0
859.75
8/9/2019 Heating Load Third Floor
8/95
Walls
(North) 0 0 0 0
(East) 0 0 0 0(West) 5.76 0.81 18 84.17
(South) 0 0 0 0
Ceiling 0 0 0 0
Floor 0 0 0 0
Windows
(North) 0 0 0 0
(East) 0 0 0 0
(West) 1.46 6.7 18 175.59(South) 0 0 0 0
Doors 0 0 0 0
Infiltration 137.52
397.29
437.02
Area (m2) Uoverall(W/m2.oC)
T (oC) Qloss (W)
Qspace
=
(Safety factor * Qspace )=
8/9/2019 Heating Load Third Floor
9/95
84.17
T v L C Qv
18 0.78 5.8 23.71 137.52
175.59
0
137.52
8/9/2019 Heating Load Third Floor
10/95
Walls
(North) 0 0 0 0
(East) 0 0 0 0
(West) 9.78 0.81 18 142.89
(South) 0 0 0 0
Ceiling 0 0 0 0
Floor 0 0 0 0
Windows
(North) 0 0 0 0
(East) 0 0 0 0
(West) 0 0 0 0(South) 0 0 0 0
Doors 9.72 6.7 18 1172.71
Infiltration 624.54
1940.14
2134.15
Area (m2) Uoverall(W/m2.oC)
T (oC) Qloss (W)
Qspace
=
(Safety factor * Qspace )=
8/9/2019 Heating Load Third Floor
11/95
142.89
T v L C Qv
18 0.78 26.34 23.71 624.54
0
1172.71
624.54
8/9/2019 Heating Load Third Floor
12/95
Walls
(North) 0 0 0 0
(East) 0 0 0 0(West) 11.34 0.81 18 165.69
(South) 19.89 0.81 18 290.71
Ceiling 0 0 0 0
Floor 0 0 0 0
Windows
(North) 0 0 0 0
(East) 0 0 0 0
(West)8.55 6.7 18 1031.61
(South) 0 0 0 0
Doors 0 0 0 0
Infiltration 768.51
2256.52
2482.17
Area (m2) Uoverall(W/m2.oC)
T (oC) Qloss (W)
Qspace
=
(Safety factor * Qspace )=
8/9/2019 Heating Load Third Floor
13/95
456.4
T v L C Qv
18 0.78 32.41 23.71 768.51
1031.61
0
768.51
8/9/2019 Heating Load Third Floor
14/95
Walls
(North) 0 0 0 0
(East) 0 0 0 0(West) 15.18 0.81 18 221.88
(South) 0 0 0 0
Ceiling 0 0 0 0
Floor 0 0 0 0
Windows
(North) 0 0 0 0
(East) 0 0 0 0
(West)11.22 6.7 18 1353.39
(South) 0 0 0 0
Doors 0 0 0 0
Infiltration 1024.68
2599.95
2859.95
Area (m2) Uoverall(W/m2.oC)
T (oC) Qloss (W)
Qspace
=
(Safety factor * Qspace )=
8/9/2019 Heating Load Third Floor
15/95
221.88
T v L C Qv
18 0.78 32.41 23.71 768.51
18 0.78 10.8 23.71 256.17
1024.68
1353.39
0
1024.68
8/9/2019 Heating Load Third Floor
16/95
Walls
(North) 0 0 0 0
(East) 0 0 0 0(West) 18.67 0.81 18 272.95
(South) 0 0 0 0
Ceiling 0 0 0 0
Floor 0 0 0 0
Windows
(North) 0 0 0 0
(East) 0 0 0 0
(West) 13.89 6.7 18 1675.16
(South) 0 0 0 0
Doors 0 0 0 0
Infiltration 1280.85
3228.96
3551.86
Area (m2) Uoverall(W/m2.oC)
T (oC) Qloss (W)
Qspace
=
(Safety factor * Qspace )=
8/9/2019 Heating Load Third Floor
17/95
272.95
T v L C Qv
18 0.78 32.41 23.71 768.51
18 0.78 21.61 23.71 512.34
1280.85
1675.16
0
1280.85
8/9/2019 Heating Load Third Floor
18/95
Walls
(North) 35.88 0.81 18 524.42
(East) 0 0 0 0(West) 21.19 0.81 18 309.71
(South) 0 0 0 0
Ceiling 0 0 0 0
Floor 0 0 0 0
Windows
(North) 0 0 0 0
(East) 0 0 0 0
(West) 17.11 6.7 18 2063.22
(South) 0 0 0 0
Doors 0 0 0 0
Infiltration 1537.02
4434.38
4877.82
Area (m2) Uoverall(W/m2.oC)
T (oC) Qloss (W)
Qspace
=
(Safety factor * Qspace )=
8/9/2019 Heating Load Third Floor
19/95
834.14
T v L C Qv
18 0.78 32.41 23.71 768.51
18 0.78 32.41 23.71 768.51
1537.02
2063.22
0
1537.02
8/9/2019 Heating Load Third Floor
20/95
Walls
(North) 29.63 0.81 18 433.03
(East) 0 0 0 0
(West) 0 0 0 0
(South) 0 0 0 0
Ceiling 0 0 0 0
Floor 0 0 0 0
Windows
(North) 12.38 6.7 18 1492.55
(East)0 0 0 0
(West) 0 0 0 0
(South) 0 0 0 0
Doors 0 0 0 0
Infiltration 1162.77
3088.34
3397.18
Area (m2) Uoverall(W/m2.oC)
T (oC) Qloss (W)
Qspace
=
(Safety factor * Qspace )=
8/9/2019 Heating Load Third Floor
21/95
433.03
T v L C Qv
18 0.78 24.52 23.71 581.39
18 0.78 24.52 23.71 581.39
1162.77
1492.55
0
1162.77
8/9/2019 Heating Load Third Floor
22/95
Walls
(North) 12.92 0.81 18 188.87
(East) 22.23 2.54 9 508.18
(West) 0 0 0 0
(South) 0 0 0 0
Ceiling 0 0 0 0
Floor 0 0 0 0
Windows
(North) 6.19 6.7 18 746.27
(East) 0 0 0 0
(West) 0 0 0 0
(South) 0 0 0 0
Doors 0 0 0 0
Infiltration 581.39
2024.7
2227.18
Area (m2) Uoverall(W/m2.oC)
T (oC) Qloss (W)
Qspace
=
(Safety factor * Qspace )=
8/9/2019 Heating Load Third Floor
23/95
697.05
T v L C Qv
18 0.78 24.52 23.71 581.39
746.27
0
581.39
8/9/2019 Heating Load Third Floor
24/95
Walls
(North) 0 0 0 0
(East) 0 0 0 0(West) 0 0 0 0
(South) 0 0 0 0 0
Ceiling 0 0 0 0
Floor 0 0 0 0 T
Windows
(North) 0 0 0 0
(East) 0 0 0 0
(West) 0 0 0 0
(South) 0 0 0 0 0
Doors 0 0 0 0 0
Infiltration 0 0 0 0 0
0
0
Area (m2) Uoverall(W/m2.oC)
T (oC) Qloss (W)
Qspace
=
(Safety factor * Qspace )=
8/9/2019 Heating Load Third Floor
25/95
v L C Qv
8/9/2019 Heating Load Third Floor
26/95
Walls
(North) 15.29 0.81 18 223.45
(East) 21.7 0.81 18 317.12
(West) 22.23 2.54 9 508.18
(South) 0 0 0 0
Ceiling 0 0 0 0
Floor 0 0 0 0
Windows
(North) 0 0 0 0
(East) 17.11 6.7 18 2063.22
(West) 0 0 0 0(South) 0 0 0 0
Doors 0 0 0 0
Infiltration1537.02
4649
5113.9
Area (m2) Uoverall(W/m2.oC)
T (oC) Qloss (W)
Qspace
=
(Safety factor * Qspace )=
8/9/2019 Heating Load Third Floor
27/95
1048.75
T v L C Qv
18 0.78 32.41 23.71 768.51
18 0.78 32.41 23.71 768.51
1537.02
2063.22
0
1537.02
8/9/2019 Heating Load Third Floor
28/95
Walls
(North) 0 0 0 0
(East) 7.14 0.81 18 104.31
(West) 0 0 0 0
(South) 0 0 0 0
Ceiling 0 0 0 0
Floor 0 0 0 0
Windows
(North) 0 0 0 0
(East) 5.73 6.7 18 691.4
(West)0 0 0 0
(South) 0 0 0 0
Doors 0 0 0 0
Infiltration 512.34
1308.05
1438.86
Area (m2) Uoverall(W/m2.oC)
T (oC) Qloss (W)
Qspace
=
(Safety factor * Qspace )=
8/9/2019 Heating Load Third Floor
29/95
104.31
T v L C Qv
18 0.78 21.61 23.71 512.34
691.4
0
512.34
8/9/2019 Heating Load Third Floor
30/95
Walls
(North) 0 0 0 0
(East) 7.53 0.81 18 110.11
(West) 0 0 0 0
(South) 0 0 0 0
Ceiling 0 0 0 0
Floor 0 0 0 0
Windows
(North) 0 0 0 0
(East) 5.34 6.7 18 643.55
(West) 0 0 0 0
(South) 0 0 0 0
Doors 0 0 0 0
Infiltration 512.34
1266
1392.6
Area (m2) Uoverall(W/m2.oC) T (oC) Qloss (W)
Qspace
=
(Safety factor * Qspace )=
8/9/2019 Heating Load Third Floor
31/95
110.11
T v L C Qv
18 0.78 21.61 23.71 512.34
643.55
0
512.34
8/9/2019 Heating Load Third Floor
32/95
Walls
(North) 0 0 0 0
(East) 7.53 0.81 18 110.11(West) 0 0 0 0
(South) 0 0 0 0
Ceiling 0 0 0 0
Floor 0 0 0 0
Windows
(North) 0 0 0 0
(East) 5.34 6.7 18 643.55
(West) 0 0 0 0(South) 0 0 0 0
Doors 0 0 0 0
Infiltration 512.34
1266
1392.6
Area (m2) Uoverall(W/m2.oC)
T (oC) Qloss (W)
Qspace
=
(Safety factor * Qspace )=
8/9/2019 Heating Load Third Floor
33/95
110.11
T v L C Qv
18 0.78 21.61 23.71 512.34
643.55
0
512.34
8/9/2019 Heating Load Third Floor
34/95
Walls
(North) 0 0 0 0
(East) 11.92 0.81 18 174.24(West) 0 0 0 0
(South) 0 0 0 0
Ceiling 0 0 0 0
Floor 0 0 0 0
Windows
(North) 0 0 0 0
(East) 8.55 6.7 18 1031.61
(West) 0 0 0 0
(South) 0 0 0 0
Doors 0 0 0 0
Infiltration 768.51
1974.36
2171.8
Area (m2) Uoverall(W/m2.oC)
T (oC) Qloss (W)
Qspace
=
(Safety factor * Qspace )=
8/9/2019 Heating Load Third Floor
35/95
174.24
T v L C Qv
18 0.78 32.41 23.71 768.51
1031.61
0
768.51
8/9/2019 Heating Load Third Floor
36/95
Walls
(North) 0 0 0 0
(East) 11.35 0.81 18 165.88
(West) 0 0 0 0
(South) 0 0 0 0
Ceiling 0 0 0 0
Floor 0 0 0 0
Windows
(North) 0 0 0 0
(East) 6.01 6.7 18 724.32
(West)0 0 0 0
(South) 0 0 0 0
Doors 0 0 0 0
Infiltration 512.34
1402.54
1542.79
Area (m2) Uoverall(W/m2.oC)
T (oC) Qloss (W)
Qspace
=
(Safety factor * Qspace )=
8/9/2019 Heating Load Third Floor
37/95
165.88
T v L C Qv
18 0.78 21.61 23.71 512.34
724.32
0
512.34
8/9/2019 Heating Load Third Floor
38/95
Walls
(North) 0 0 0 0
(East) 14.35 0.81 18 209.77
(West) 0 0 0 0
(South) 0 0 0 0
Ceiling 0 0 0 0
Floor 0 0 0 0
Windows
(North) 0 0 0 0
(East) 11.19 6.7 18 1349.88
(West)0 0 0 0
(South) 0 0 0 0
Doors 0 0 0 0
Infiltration 1024.68
2584.32
2842.76
Area (m2) Uoverall(W/m2.oC) T (oC) Qloss (W)
Qspace
=
(Safety factor * Qspace )=
8/9/2019 Heating Load Third Floor
39/95
209.77
T v L C Qv
18 0.78 10.8 23.71 256.17
18 0.78 32.41 23.71 768.51
1024.68
1349.88
0
1024.68
8/9/2019 Heating Load Third Floor
40/95
Walls
(North) 0 0 0 0
(East) 7.72 0.81 18 112.86
(West) 0 0 0 0
(South) 0 0 0 0
Ceiling 0 0 0 0
Floor 0 0 0 0
Windows
(North) 0 0 0 0
(East) 5.73 6.7 18 691.4
(West) 0 0 0 0(South) 0 0 0 0
Doors 0 0 0 0
Infiltration 512.34
1316.6
1448.27
Area (m2) Uoverall(W/m2.oC)
T (oC) Qloss (W)
Qspace
=
(Safety factor * Qspace )=
8/9/2019 Heating Load Third Floor
41/95
112.86
T v L C Qv
18 0.78 21.61 23.71 512.34
691.4
0
512.34
8/9/2019 Heating Load Third Floor
42/95
Walls
(North) 0 0 0 0
(East) 3.6 0.81 18 52.63
(West) 0 0 0 0
(South) 0 0 0 0
Ceiling 0 0 0 0
Floor 0 0 0 0
Windows
(North) 0 0 0 0
(East) 2.64 6.7 18 318.26
(West)0 0 0 0
(South) 0 0 0 0
Doors 0 0 0 0
Infiltration 256.17
627.07
689.77
Area (m2) Uoverall(W/m2.oC)
T (oC) Qloss (W)
Qspace
=
(Safety factor * Qspace )=
8/9/2019 Heating Load Third Floor
43/95
52.63
T v L C Qv
18 0.78 10.8 23.71 256.17
318.26
0
256.17
8/9/2019 Heating Load Third Floor
44/95
Walls
(North) 0 0 0 0
(East) 10.95 0.81 18 159.99
(West) 0 0 0 0
(South) 0 0 0 0
Ceiling 0 0 0 0
Floor 0 0 0 0
Windows
(North) 0 0 0 0
(East) 8.55 6.7 18 1031.61
(West) 0 0 0 0
(South) 0 0 0 0
Doors 0 0 0 0
Infiltration 768.51
1960.11
2156.12
Area (m2) Uoverall(W/m2.oC)
T (oC) Qloss (W)
Qspace
=
(Safety factor * Qspace )=
8/9/2019 Heating Load Third Floor
45/95
159.99
T v L C Qv
18 0.78 32.41 23.71 768.51
1031.61
0
768.51
8/9/2019 Heating Load Third Floor
46/95
Walls
(North) 0 0 0 0
(East) 10.95 0.81 18 159.99
(West) 0 0 0 0
(South) 0 0 0 0
Ceiling 0 0 0 0
Floor 0 0 0 0
Windows
(North) 0 0 0 0
(East) 8.55 6.7 18 1031.61
(West) 0 0 0 0
(South) 0 0 0 0
Doors 0 0 0 0
Infiltration 768.51
1960.11
2156.12
Area (m2) Uoverall(W/m2.oC)
T (oC) Qloss (W)
Qspace
=
(Safety factor * Qspace )=
8/9/2019 Heating Load Third Floor
47/95
159.99
T v L C Qv
18 0.78 32.41 23.71 768.51
1031.61
0
768.51
8/9/2019 Heating Load Third Floor
48/95
Walls
(North) 0 0 0 0
(East) 10.36 0.81 18 151.44(West) 22.23 2.54 9 508.18
(South) 15.29 0.81 18 223.45
Ceiling 0 0 0 0
Floor 0 0 0 0
Windows
(North) 0 0 0 0
(East) 8.55 6.7 18 1031.61
(West)0 0 0 0
(South) 0 0 0 0
Doors 0 0 0 0
Infiltration 768.51
2683.19
2951.5
Area (m2) Uoverall(W/m2.oC)
T (oC) Qloss (W)
Qspace
=
(Safety factor * Qspace )=
8/9/2019 Heating Load Third Floor
49/95
883.06
T v L C Qv
18 0.78 32.41 23.71 768.51
1031.61
0
768.51
8/9/2019 Heating Load Third Floor
50/95
Walls
(North) 0 0 0 0
(East) 0 0 0 0
(West) 0 0 0 0
(South) 0 0 0 0
Ceiling 0 0 0 0
Floor 0 0 0 0
Windows
(North) 0 0 0 0
(East) 0 0 0 0
(West) 0 0 0 0
(South) 0 0 0 0
Doors 0 0 0 0
Infiltration 0 0 0 0
0
0
Area (m2) Uoverall(W/m2.oC)
T (oC) Qloss (W)
Qspace
=
(Safety factor * Qspace )=
8/9/2019 Heating Load Third Floor
51/95
0
T v L C Qv
0
0
0
8/9/2019 Heating Load Third Floor
52/95
Walls
(North) 0 0 0 0
(East) 18.72 2.54 9 427.94
(West) 0 0 0 0
(South) 5.77 0.81 18 84.36
Ceiling 0 0 0 0
Floor 0 0 0 0
Windows
(North) 0 0 0 0
(East) 0 0 0 0
(West) 0 0 0 0(South) 1.25 6.7 18 150.51
Doors 0 0 0 0
Infiltration 130.88
793.69
873.06
Area (m2) Uoverall(W/m2.oC) T (oC) Qloss (W)
Qspace
=
(Safety factor * Qspace )=
8/9/2019 Heating Load Third Floor
53/95
512.3
T v L C Qv
18 0.78 5.52 23.71 130.88
150.51
0
130.88
8/9/2019 Heating Load Third Floor
54/95
Walls
(North) 0 0 0 0
(East) 0 0 0 0
(West) 0 0 0 0
(South) 4.84 0.81 18 70.68
Ceiling 0 0 0 0
Floor 0 0 0 0
Windows
(North) 0 0 0 0
(East) 0 0 0 0
(West) 0 0 0 0
(South) 0.47 6.7 18 56.44
Doors 0 0 0 0
Infiltration 93.89
221.02
243.12
Area (m2) Uoverall(W/m2.oC)
T (oC) Qloss (W)
Qspace
=
(Safety factor * Qspace )=
8/9/2019 Heating Load Third Floor
55/95
70.68
T v L C Qv
18 0.78 3.96 23.71 93.89
56.44
0
93.89
8/9/2019 Heating Load Third Floor
56/95
Walls
(North) 0 0 0 0
(East) 0 0 0 0(West) 0 0 0 0
(South) 4.84 0.81 18 70.68
Ceiling 0 0 0 0
Floor 0 0 0 0
Windows
(North) 0 0 0 0
(East) 0 0 0 0
(West) 0 0 0 0
(South) 0.47 6.7 18 56.44
Doors 0 0 0 0
Infiltration 93.89
221.02
243.12
Area (m2) Uoverall(W/m2.oC)
T (oC) Qloss (W)
Qspace
=
(Safety factor * Qspace )=
8/9/2019 Heating Load Third Floor
57/95
70.68
T v L C Qv
18 0.78 3.96 23.71 93.89
56.44
0
93.89
8/9/2019 Heating Load Third Floor
58/95
Walls
(North) 0 0 0 0
(East) 0 0 0 0
(West) 0 0 0 0
(South) 5.98 0.81 18 87.4 87.4
Ceiling 0 0 0 0
Floor 0 0 0 0 T
Windows 18
(North) 0 0 0 0
(East) 0 0 0 0
(West)0 0 0 0
(South) 1.04 6.7 18 125.42 125.42
Doors 0 0 0 0 0
Infiltration 121.4 121.4
334.23
367.65
Area (m2) Uoverall(W/m2.oC)
T (oC) Qloss (W)
Qspace
=
(Safety factor * Qspace )=
8/9/2019 Heating Load Third Floor
59/95
v L C Qv
0.78 5.12 23.71 121.4
8/9/2019 Heating Load Third Floor
60/95
Walls
(North) 0 0 0 0
(East) 0 0 0 0(West) 0 0 0 0
(South) 9.78 0.81 18 142.89
Ceiling 0 0 0 0
Floor 0 0 0 0
Windows
(North) 0 0 0 0
(East) 0 0 0 0
(West) 0 0 0 0
(South) 3.09 6.7 18 373.14
Doors 0 0 0 0
Infiltration 278.36
794.39
873.82
Area (m2) Uoverall(W/m2.oC)
T (oC) Qloss (W)
Qspace
=
(Safety factor * Qspace )=
8/9/2019 Heating Load Third Floor
61/95
142.89
T v L C Qv
18 0.78 11.74 23.71 278.36
373.14
0
278.36
8/9/2019 Heating Load Third Floor
62/95
Walls
(North) 0 0 0 0
(East) 0 0 0 0
(West) 0 0 0 0
(South) 9.78 0.81 18 142.89
Ceiling 0 0 0 0
Floor 0 0 0 0
Windows
(North) 0 0 0 0
(East) 0 0 0 0
(West) 0 0 0 0
(South) 3.09 6.7 18 373.14
Doors 0 0 0 0
Infiltration 278.36
794.39
873.82
Area (m2) Uoverall(W/m2.oC)
T (oC) Qloss (W)
Qspace
=
(Safety factor * Qspace )=
8/9/2019 Heating Load Third Floor
63/95
142.89
T v L C Qv
18 0.78 11.74 23.71 278.36
373.14
0
278.36
8/9/2019 Heating Load Third Floor
64/95
Walls
(North) 0 0 0 0
(East) 0 0 0 0
(West) 0 0 0 0
(South) 9.58 0.81 18 140.04
Ceiling 0 0 0 0
Floor 0 0 0 0
Windows
(North) 0 0 0 0
(East)0 0 0 0
(West) 0 0 0 0
(South) 3.09 6.7 18 373.14
Doors 0 0 0 0
Infiltration 278.36
791.54
870.69
Area (m2) Uoverall(W/m2.oC)
T (oC) Qloss (W)
Qspace
=
(Safety factor * Qspace )=
8/9/2019 Heating Load Third Floor
65/95
140.04
T v L C Qv
18 0.78 11.74 23.71 278.36
373.14
0
278.36
8/9/2019 Heating Load Third Floor
66/95
Walls
(North) 9.85 0.81 18 144.03
(East) 0 0 0 0
(West) 0 0 0 0
(South) 0 0 0 0
Ceiling 0 0 0 0
Floor 0 0 0 0
Windows
(North) 2.82 6.7 18 340.21
(East) 0 0 0 0
(West) 0 0 0 0(South) 0 0 0 0
Doors 0 0 0 0
Infiltration 268.88
753.12
828.43
Area (m2) Uoverall(W/m2.oC)
T (oC) Qloss (W)
Qspace
=
(Safety factor * Qspace )=
8/9/2019 Heating Load Third Floor
67/95
144.03
T v L C Qv
18 0.78 11.34 23.71 268.88
340.21
0
268.88
8/9/2019 Heating Load Third Floor
68/95
Walls
(North) 8.26 0.81 18 120.69
(East) 0 0 0 0
(West) 0 0 0 0
(South) 0 0 0 0
Ceiling 0 0 0 0
Floor 0 0 0 0
Windows
(North) 4.5 6.7 18 542.15
(East) 0 0 0 0
(West) 0 0 0 0(South) 0 0 0 0
Doors 0 0 0 0
Infiltration 380.32
1043.16
1147.47
Area (m2) Uoverall(W/m2.oC)
T (oC) Qloss (W)
Qspace
=
(Safety factor * Qspace )=
8/9/2019 Heating Load Third Floor
69/95
120.69
T v L C Qv
18 0.78 16.04 23.71 380.32
542.15
0
380.32
8/9/2019 Heating Load Third Floor
70/95
Walls
(North) 8.26 0.81 18 120.69
(East) 0 0 0 0
(West) 0 0 0 0
(South) 0 0 0 0
Ceiling 0 0 0 0
Floor 0 0 0 0
Windows
(North) 4.5 6.7 18 542.15
(East) 0 0 0 0
(West) 0 0 0 0
(South) 0 0 0 0
Doors 0 0 0 0
Infiltration 380.32
1043.16
1147.47
Area (m2) Uoverall(W/m2.oC)
T (oC) Qloss (W)
Qspace
=
(Safety factor * Qspace )=
8/9/2019 Heating Load Third Floor
71/95
120.69
T v L C Qv
18 0.78 16.04 23.71 380.32
542.15
0
380.32
8/9/2019 Heating Load Third Floor
72/95
Walls
(North) 0 0 0 0
(East) 0 0 0 0
(West) 0 0 0 0
(South) 0 0 0 0 0
Ceiling 0 0 0 0
Floor 0 0 0 0 T
Windows
(North) 0 0 0 0
(East) 0 0 0 0
(West)0 0 0 0
(South) 0 0 0 0 0
Doors 0 0 0 0 0
Infiltration 0 0 0 0 0
0
0
Area (m2) Uoverall(W/m2.oC)
T (oC) Qloss (W)
Qspace
=
(Safety factor * Qspace )=
8/9/2019 Heating Load Third Floor
73/95
v L C Qv
8/9/2019 Heating Load Third Floor
74/95
Walls
(North) 6.97 0.81 18 101.84
(East) 0 0 0 0
(West) 0 0 0 0
(South) 7.8 2.54 9 178.31
Ceiling 0 0 0 0
Floor 0 0 0 0
Windows
(North) 0.83 6.7 18 100.34
(East) 0 0 0 0
(West) 0 0 0 0
(South) 0 0 0 0
Doors 0 0 0 0
Infiltration 137.52
518.01
569.81
Area (m2) Uoverall(W/m2.oC)
T (oC) Qloss (W)
Qspace
=
(Safety factor * Qspace )=
8/9/2019 Heating Load Third Floor
75/95
280.15
T v L C Qv
18 0.78 5.8 23.71 137.52
100.34
0
137.52
8/9/2019 Heating Load Third Floor
76/95
Walls
(North) 12.94 0.81 18 189.06
(East) 8.97 2.54 9 205.05
(West) 0 0 0 0
(South) 0 0 0 0
Ceiling 0 0 0 0
Floor 0 0 0 0
Windows
(North) 2.08 6.7 18 250.85
(East) 0 0 0 0
(West)0 0 0 0
(South) 0 0 0 0
Doors 0 0 0 0
Infiltration 193.48
838.44
922.28
Area (m2) Uoverall(W/m2.oC)
T (oC) Qloss (W)
Qspace
=
(Safety factor * Qspace )=
8/9/2019 Heating Load Third Floor
77/95
394.11
T v L C Qv
18 0.78 8.16 23.71 193.48
250.85
0
193.48
8/9/2019 Heating Load Third Floor
78/95
Walls
(North) 6.97 0.81 18 101.84
(East) 0 0 0 0
(West) 0 0 0 0
(South) 0 0 0 0
Ceiling 0 0 0 0
Floor 0 0 0 0
Windows
(North) 0.83 6.7 18 100.34
(East) 0 0 0 0
(West)0 0 0 0
(South) 0 0 0 0
Doors 0 0 0 0
Infiltration 137.52
339.71
373.68
Area (m2) Uoverall(W/m2.oC)
T (oC) Qloss (W)
Qspace
=
(Safety factor * Qspace )=
8/9/2019 Heating Load Third Floor
79/95
101.84
T v L C Qv
18 0.78 5.8 23.71 137.52
100.34
0
137.52
8/9/2019 Heating Load Third Floor
80/95
Walls
(North) 6.97 0.81 18 101.84
(East) 0 0 0 0
(West) 0 0 0 0
(South) 0 0 0 0
Ceiling 0 0 0 0
Floor 0 0 0 0
Windows
(North) 0.83 6.7 18 100.34
(East) 0 0 0 0
(West)0 0 0 0
(South) 0 0 0 0
Doors 0 0 0 0
Infiltration 137.52
339.71
373.68
Area (m2) Uoverall(W/m2.oC)
T (oC) Qloss (W)
Qspace
=
(Safety factor * Qspace )=
8/9/2019 Heating Load Third Floor
81/95
101.84
T v L C Qv
18 0.78 5.8 23.71 137.52
100.34
0
137.52
8/9/2019 Heating Load Third Floor
82/95
Walls
(North) 23.27 0.81 18 340.11
(East) 0 0 0 0
(West) 11.31 2.54 9 258.55
(South) 9.36 2.54 9 213.97
Ceiling 0 0 0 0
Floor 0 0 0 0
Windows
(North) 2.08 6.7 18 250.85
(East) 0 0 0 0
(West) 0 0 0 0
(South) 0 0 0 0
Doors 0 0 0 0
Infiltration 193.48
1256.96
1382.65
Area (m2) Uoverall(W/m2.oC)
T (oC) Qloss (W)
Qspace
=
(Safety factor * Qspace )=
8/9/2019 Heating Load Third Floor
83/95
812.63
T v L C Qv
18 0.78 8.16 23.71 193.48
250.85
0
193.48
8/9/2019 Heating Load Third Floor
84/95
Walls
(North) 0 0 0 0
(East) 0 0 0 0
(West) 0 0 0 0
(South) 0 0 0 0 0
Ceiling 0 0 0 0
Floor 0 0 0 0 T
Windows
(North) 0 0 0 0
(East) 0 0 0 0
(West)0 0 0 0
(South) 0 0 0 0 0
Doors 0 0 0 0 0
Infiltration 0 0 0 0 0
0
0
Area (m2) Uoverall(W/m2.oC)
T (oC) Qloss (W)
Qspace
=
(Safety factor * Qspace )=
8/9/2019 Heating Load Third Floor
85/95
v L C Qv
8/9/2019 Heating Load Third Floor
86/95
Walls
(North) 0 0 0 0
(East) 0 0 0 0
(West) 0 0 0 0
(South) 8.81 0.81 18 128.83
Ceiling 0 0 0 0
Floor 0 0 0 0
Windows
(North) 0 0 0 0
(East) 0 0 0 0
(West)0 0 0 0
(South) 4.64 6.7 18 559.7
Doors 0 0 0 0
Infiltration 414.46
1102.99
1213.29
Area (m2) Uoverall(W/m2.oC)
T (oC) Qloss (W)
Qspace
=
(Safety factor * Qspace )=
8/9/2019 Heating Load Third Floor
87/95
128.83
T v L C Qv
18 0.78 17.48 23.71 414.46
559.7
0
414.46
8/9/2019 Heating Load Third Floor
88/95
Walls
(North) 0 0 0 0
(East) 0 0 0 0(West) 0 0 0 0
(South) 13.31 0.81 18 194.57
Ceiling 0 0 0 0
Floor 0 0 0 0
Windows
(North) 0 0 0 0
(East) 0 0 0 0
(West)0 0 0 0
(South) 6.19 6.7 18 746.27
Doors 0 0 0 0
Infiltration 581.39
1522.23
1674.45
Area (m2) Uoverall(W/m2.oC)
T (oC) Qloss (W)
Qspace
=
(Safety factor * Qspace )=
8/9/2019 Heating Load Third Floor
89/95
194.57
T v L C Qv
18 0.78 24.52 23.71 581.39
746.27
0
581.39
8/9/2019 Heating Load Third Floor
90/95
Walls
(North) 0 0 0 0
(East) 0 0 0 0
(West) 0 0 0 0
(South) 13.31 0.81 18 194.57
Ceiling 0 0 0 0
Floor 0 0 0 0
Windows
(North) 0 0 0 0
(East) 0 0 0 0
(West) 0 0 0 0(South) 6.19 6.7 18 746.27
Doors 0 0 0 0
Infiltration 581.39
1522.23
1674.45
Area (m2) Uoverall(W/m2.oC)
T (oC) Qloss (W)
Qspace
=
(Safety factor * Qspace )=
8/9/2019 Heating Load Third Floor
91/95
194.57
T v L C Qv
18 0.78 24.52 23.71 581.39
746.27
0
581.39
8/9/2019 Heating Load Third Floor
92/95
Walls
(North) 0 0 0 0
(East) 0 0 0 0(West) 0 0 0 0
(South) 9.63 0.81 18 140.8
Ceiling 0 0 0 0
Floor 0 0 0 0
Windows
(North) 0 0 0 0
(East) 0 0 0 0
(West) 0 0 0 0(South) 3.82 6.7 18 460.93
Doors 0 0 0 0
Infiltration 316.3
918.03
1009.83
Area (m2) Uoverall(W/m2.oC)
T (oC) Qloss (W)
Qspace
=
(Safety factor * Qspace )=
8/9/2019 Heating Load Third Floor
93/95
140.8
T v L C Qv
18 0.78 13.34 23.71 316.3
460.93
0
316.3
8/9/2019 Heating Load Third Floor
94/95
Walls
(North) 20.02 0.81 18 292.61
(East) 58.27 0.81 18 851.62
(West) 54.81 0.81 18 801.07
(South) 14.82 0.81 18 216.61
Ceiling 0 0 0 0
Floor 0 0 0 0
Windows
(North) 5.92 6.7 18 713.35
(East) 21.29 6.7 18 2568.06
(West) 24.75 6.7 18 2985.09
(South) 51.48 6.7 18 6208.49
(North) 7.48 6.7 12 601.39
(South) 7.48 6.7 12 601.39
Doors 4.84 2.7 12 156.82
Infiltration 7052.98
23049.47
25354.42
Area (m2) Uoverall(W/m2.oC)
T (oC) Qloss (W)
Qspace
=
(Safety factor * Qspace )=
8/9/2019 Heating Load Third Floor
95/95
2161.91
T v L C Qv
18 0.78 23.08 23.71 North 547.24
18 0.78 84.5 23.71 East 2003.55
18 0.78 98.08 23.71 West 2325.54
18 0.78 91.8 23.71 South 2176.64
12474.98 7052.98
1359.6
7052.98