    Marine and Offshore Cables5/ 2014

  • 8/9/2019 Helkama Bica Marine and Offshore Cables (1)

    2/84

    Helkama a true specialistin marine cables ......................2Approvals..................................30,6/1kV cablesLKM-HF.....................................4LKMM-HF .................................8LKSM-HF.................................10LKMSM-HF .............................14LKAM-HF.................................16LKEM-HF.................................18EMC cablesLKSM-EMC..............................20LKSM-EMC-FRHF....................24RFE-EMC.................................28RFE-EMC(i) .............................301,8/3kV cablesLKSM-VFD ..............................320,6/1kV FR cablesLKM-FRHF...............................34LKSM-FRHF ............................38LKAM-FRHF ............................42250V cablesLKM-HF ..................................44LKSM-HF.................................46LKAM-HF ................................48RFE-HF....................................50RFE-HF (i) ...............................52RFA-HF....................................54RFA-HF (i) ...............................56250V FR cablesLKM-FRHF ..............................58LKSM-FRHF ...........................60LKAM-FRHF ...........................62RFE-FRHF................................64RFE-FRHF (i) ...........................66RFA-FRHF................................68RFA-FRHF (i) ...........................70Optical fibre cablesFXMSU....................................72FXMMS ...................................74Cabled optical fibrescharacteristics.........................76Technical informationGeneral information.................78Bending radius ........................79Diameter tolerance ..................79Core identification ...................79Current rating..........................80Short circuit current ................81Short time duty .......................82Voltage drop............................83

    Subject to change without prior notice.See latest updates on our webpagewww.helkamabica.com

    ContentsHelkama is specializing in development and production of

    marine and offshore cables. Our experience in this field goes back fifty years. Our high technical quality has been achieved by continuous development work supported by our clients.In this catalogue we proudly present our most comprehensive

    range of marine cables.

    We have chosen to produce only halogen-free cables. They remarkably improve the fire safety of the ships by not emittingtoxic burning fumes or thick smoke. In addition no corrosive

    gases damaging the ship and its equipment are emitted incase of a fire. Using the latest technology we have been ableto reduce cable weight and size to a minimum and still

    maintain quality as well as enabling easy and fast installation.The halogen free range of cables includes both flame-retardant (IEC 60332-3) and fire resistant (IEC 60331-series) cables.Helkama marine cables are approved by all major classification

    societies.

    As a specialized and independent company, focusing on service, we have

    been able to grow steadily by quickly

    responding to our customers needs.Our short delivery times, backed up by extensive stocks, enable us to deliver

    punctually and keep our clients satisfied.This remains our goal for the future, too.

    HELKAMA a true specialist in marine cables

    Marine cable factory inKaarina, Finland.

  • 8/9/2019 Helkama Bica Marine and Offshore Cables (1)

    3/84

    www

    .h el k am

    a b i c a . c om

    3T Y P E AP P R

    OV AL

    S

    Marine cable factory inShanghai, China.

    Type Approval Certificates for factories in Finland and China

    Please check updated approval situation on www.helkamabica.com

  • 8/9/2019 Helkama Bica Marine and Offshore Cables (1)

    4/84

    4

    0 , 6 / 1 k V C A B L E S

    DESIGN: STANDARDS:IEC 60092-353, design

    1. Conductor- stranded copper conductor 1,0-10mm 2 IEC 60228, class 2- stranded copper conductor 16-300mm 2 IEC 60228, class 5 (Flex)- tinned stranded copper conductor on request

    2. Insulation- XLPE plastic IEC 60092-3513. Bedding

    - separator tape4. Sheath

    - polyolefine plastic, SHF1 IEC 60092-359- on request, thermosetting polyolefine, SHF2- standard colour black, other colours on request

    LKM-HFUnarmoured power andcontrol cable 0,6/1kV

    Application: For fixed installation in most areas and on open deck in ships.

    Main characteristics

    Rated voltage AC 0,6/1kV (1,2kV)DC 0,9/1,5kV (if voltage to earth does not exceed 0,9kV)

    Maximum conductortemperature + 90 CFlame-retardant IEC 60332-1-2 -test for single insulated wire and cable

    IEC 60332-3-22 -test for bunched wires and cables,category A

    Halogen-free IEC 60754 seriesSmoke emission IEC 61034 seriesOil resistance (only SHF2) IEC 60811-2-1 conditions according to 60092-359/SHF2

    Minimum recommended installation temperature -15 CLowest operation temperature -40 C

    Core identification: see technical information section

    Identification: Lot number, cable type, cable size, voltage, temperature,standards, production month, manufacturer's name and

    meter marking printed on the sheath

    5 / 2 0 1 4

    Tel. +358 2 410 8700, fax +358 2 237 2428, www.helkamabica.com

    Flame-retardantFire-resistantHalogen-freeLow smokeemissionOil resistant(only SHF2)

  • 8/9/2019 Helkama Bica Marine and Offshore Cables (1)

    5/84

    1x1,0 5,0 35 18 2025636 28396 1x1,5 5,5 40 23 2525638 27000 1x2,5 5,5 55 30 2525640 27002 1x4 6,5 70 40 3025642 27004 1x6 7,0 95 52 3025644 27006 1x10 8,0 140 72 3525647 27009 1x16 Flex 9,0 185 94 4025649 27011 1x25 Flex 11,5 290 123 5025651 27013 1x35 Flex 12,5 385 153 5025653 27015 1x50 Flex 14,5 540 196 6025655 27017 1x70 Flex 17,0 750 240 70

    25657 27019 1x95 Flex 19,5 975 284 8025659 27021 1x120 Flex 21,5 1225 331 9025661 27023 1x150 Flex 24,5 1545 381 10025663 27025 1x185 Flex 27,0 1880 429 16525665 27027 1x240 Flex 30,5 2495 507 18526047 27029 1x300 Flex 33,0 3055 582 20025581 2x1,0 7,5 65 15 3025670 2x1,5 8,5 80 20 3525686 2x2,5 9,5 115 26 4025702 2x4 10,5 155 34 4525701 2x6 12,0 240 44 5025717 2x10 14,0 360 61 6026054 2x16 Flex 16,5 490 80 7026055 2x25 Flex 20,5 755 105 8526056 2x35 Flex 23,0 1035 130 9526057 2x50 Flex 27,5 1455 167 17026058 2x70 Flex 31,5 1995 204 19025582 3x1,0 8,0 80 13 3525671 25672 3x1,5 9,0 100 16 4025688 25689 3x2,5 10,0 145 21 4525703 25704 3x4 11,5 200 28 5025705 25706 3x6 13,0 310 36 5525707 25708 3x10 15,0 465 50 6526071 26072 3x16 Flex 17,5 625 66 7526073 26074 3x25 Flex 22,0 970 86 90

    26075 26076 3x35 Flex 25,0 1325 107 10026077 26078 3x50 Flex 29,5 1880 137 18026079 26080 3x70 Flex 34,5 2615 168 21026081 26082 3x95 Flex 40,0 3455 199 24026083 26085 3x120 Flex 44,5 4365 232 27026084 26086 3x150 Flex 50,5 5485 267 30526087 26088 3x185 Flex 57,0 6800 300 34526089 26090 3x240 Flex 64,5 9045 355 390

    5 0 , 6 / 1 k V

    C A B L E S

    LKM-HF 0,6/1kVPart number

    Number ofconductors &cross-section

    n x mm2

    Nominalouter

    diameter

    mm

    Approximateweight kg/km

    CurrentRating Aat +45C

    Min. bendingradius fixedinstallation

    mmNormal G-type

    5 / 2 0 1 4

    Table continues on next page

    G-type is with yellow/green earth conductor and marking on sheath is, for example, 3G1,5

    Part number for oil resistant SHF2 cable:

    4 + code from above table 4xxxxx

  • 8/9/2019 Helkama Bica Marine and Offshore Cables (1)

    6/84

    25583 4x1,0 8,5 95 13 3525673 25674 4x1,5 10,0 135 16 4025690 25691 4x2,5 11,0 180 21 4525725 25726 4x4 12,5 260 28 5525727 25728 4x6 14,0 385 36 6025729 25730 4x10 16,5 585 50 7026101 26102 4x16 Flex 19,5 800 66 8026103 26104 4x25 Flex 24,5 1250 86 10026105 26106 4x35 Flex 27,5 1695 107 17026107 26108 4x50 Flex 33,0 2420 137 20026109 26110 4x70 Flex 38,0 3350 168 230

    26111 26112 4x95 Flex 44,5 4465 199 27026113 26114 4x120 Flex 49,5 5590 232 30025584 5x1,0 9,5 125 10 4025676 25677 5x1,5 11,0 160 13 4525692 25693 5x2,5 12,0 220 17 5025864 25865 5x4 13,5 320 23 5525866 25867 5x6 15,5 475 30 6525868 25869 5x10 18,5 720 42 7526131 26132 5x16 Flex 21,5 970 55 9026133 26134 5x25 Flex 27,5 1545 71 16526135 26136 5x35 Flex 30,5 2100 89 18526137 26138 5x50 Flex 37,0 2980 114 22526139 26140 5x70 Flex 42,5 4175 139 26025585 7x1,0 10,5 155 9 4525586 10x1,0 13,5 225 8 5525587 12x1,0 13,5 250 8 5525588 14x1,0 14,5 280 7 6025589 16x1,0 15,5 325 7 6525590 19x1,0 16,0 365 7 6525592 24x1,0 19,0 465 6 8025593 27x1,0 19,5 510 6 8025597 30x1,0 20,0 555 5 8525595 37x1,0 22,0 680 5 90

    6

    0 , 6 / 1 k V C A B L E S

    5 / 2 0 1 4

    Tel. +358 2 410 8700, fax +358 2 237 2428, www.helkamabica.com

    LKM-HF 0,6/1kVPart number

    Number ofconductors &cross-section

    n x mm2

    Nominalouter

    diameter

    mm

    Approximateweight kg/km

    CurrentRating Aat +45C

    Min. bendingradius fixedinstallation

    mmNormal G-type

    G-type is with yellow/green earth conductor and marking on sheath is, for example, 3G1,5

    Table continues on next pagePart number for oil resistant SHF2 cable:4 + code from above table 4xxxxx

  • 8/9/2019 Helkama Bica Marine and Offshore Cables (1)

    7/84

    25678 25679 7x1,5 11,5 200 12 5025667 25668 10x1,5 15,0 290 11 6025680 25681 12x1,5 15,5 335 10 6525991 25992 14x1,5 16,5 380 10 7025989 25990 16x1,5 17,0 430 9 7025682 25683 19x1,5 18,5 495 9 7525875 25876 24x1,5 22,0 635 8 9025684 25685 27x1,5 22,0 700 8 9025675 25687 37x1,5 25,0 920 7 10025694 25695 7x2,5 13,5 285 16 5525993 25994 10x2,5 17,0 410 14 7025696 25874 12x2,5 17,5 465 13 7025995 25996 14x2,5 18,5 535 13 7525997 25998 16x2,5 19,5 605 12 8025873 25872 19x2,5 20,5 690 11 8525877 25878 24x2,5 24,5 900 10 10026141 26142 27x2,5 25,0 990 10 155

    7 0 , 6 / 1 k V

    C A B L E S

    5 / 2 0 1 4

    LKM-HF 0,6/1kVPart number

    Number ofconductors &cross-section

    n x mm2

    Nominalouter

    diameter

    mm

    Approximateweight kg/km

    CurrentRating Aat +45C

    Min. bendingradius fixedinstallation

    mmNormal G-type

    G-type is with yellow/green earth conductor and marking on sheath is, for example, 3G1,5

    Part number for oil resistant SHF2 cable:4 + code from above table 4xxxxx

  • 8/9/2019 Helkama Bica Marine and Offshore Cables (1)

    8/84

    Tel. +358 2 410 8700, fax +358 2 237 2428, www.helkamabica.com

    8

    0 , 6 / 1 k V C A B L E S

    5 / 2 0 1 4

    DESIGN: STANDARDS:IEC 60092-353, design

    1. Conductor- stranded copper conductor 1,510mm 2 IEC 60228, class 2- stranded copper conductor 16150mm 2 IEC 60228, class 5- tinned stranded copper conductor on request

    2. Insulation- XLPE plastic IEC 60092-351

    3. Bedding- extruded filler

    4. Sheath- polyolefine plastic, SHF1 IEC 60092-359- on request, thermosetting polyolefine, SHF2- standard colour black, other colours on request

    LKMM-HFUnarmoured power cablewith extruded filler 0,6/1kV

    Application: For fixed installation in most areas and on open deck in ships.

    Main characteristics

    Rated voltage AC 0,6/1kV (1,2kV)DC 0,9/1,5kV (if voltage to earth does not exceed 0,9kV)

    Maximum conductortemperature + 90 CFlame-retardant IEC 60332-1-2 -test for single insulated wire and cable

    IEC 60332-3-22 -test for bunched wires and cables,category A

    Halogen-free IEC 60754 seriesSmoke emission IEC 61034 seriesOil resistance (only SHF2) IEC 60811-2-1 conditions according to 60092-359/SHF2

    Minimum recommended installation temperature -15 CLowest operation temperature -40 C

    Core identification: see technical information section

    Identification: Lot number, cable type, cable size, voltage, temperature,standards, production month, manufacturer's name and

    meter marking printed on the sheath

    Flame-retardantFire-resistantHalogen-freeLow smokeemissionOil resistant(only SHF2)

  • 8/9/2019 Helkama Bica Marine and Offshore Cables (1)

    9/84

    9 0 , 6 / 1 k V

    C A B L E S

    5 / 2 0 1 4

    G-type is with yellow/green earth conductor and marking on sheath is, for example, 3G1,5

    LKMM-HF 0,6/1kVPart number

    Number ofconductors &cross-section

    n x mm2

    Nominalouter

    diametermm

    Approximateweight kg/km

    CurrentRating Aat +45C

    Min. bendingradius fixedinstallation

    mmNormal G-type27532 2x1,5 9,0 110 20 3527534 2x2,5 10,0 155 26 4027536 2x4 11,0 205 34 4527538 2x6 12,5 285 44 5027540 2x10 14,5 420 61 6027543 2x16 18,5 630 80 7527545 2x25 23,0 970 105 9027547 2x35 25,5 1340 130 15527549 2x50 30,0 1855 167 18027551 2x70 34,0 2510 204 20527564 27566 3x1,5 9,5 130 16 3527568 27570 3x2,5 10,5 180 21 4527572 27574 3x4 12,0 245 28 4527576 27578 3x6 13,5 350 36 5527580 27582 3x10 15,5 515 50 6027585 27587 3x16 20,0 770 66 8027589 27591 3x25 24,5 1170 86 10027593 27595 3x35 27,0 1600 107 16027597 27599 3x50 32,0 2220 137 19027601 27603 3x70 37,0 3090 168 22027605 27607 3x95 42,5 4055 199 25527609 27611 3x120 47,0 5070 232 28527613 27615 3x150 53,5 6425 267 32027628 27630 4x1,5 10,5 165 16 4027632 27634 4x2,5 11,5 215 21 4527636 27638 4x4 13,0 305 28 5027640 27642 4x6 14,5 420 36 6027644 27646 4x10 17,5 635 50 7027649 27651 4x16 21,5 935 66 8527653 27655 4x25 27,0 1440 86 16027657 27659 4x35 30,0 1955 107 18027661 27663 4x50 35,5 2735 137 21027665 27667 4x70 40,5 3790 168 24527692 27694 5x1,5 11,5 195 13 4527696 27698 5x2,5 12,5 255 17 5027700 27702 5x4 14,5 360 23 5527704 27706 5x6 16,5 515 30 6027708 27710 5x10 19,0 770 42 7527713 27715 5x16 24,0 1145 55 9527717 27719 5x25 29,5 1750 71 175

    5 / 2 0 0 9

    Part number for oil resistant SHF2 cable:4 + code from above table 4xxxxx

  • 8/9/2019 Helkama Bica Marine and Offshore Cables (1)

    10/84

    Tel. +358 2 410 8700, fax +358 2 237 2428, www.helkamabica.com

    DESIGN: STANDARDS:IEC 60092-353,design

    1. Conductor- stranded copper conductor 1,0-10mm 2 IEC 60228, class 2- stranded copper conductor 16-300mm 2 IEC 60228, class 5 (Flex)- tinned stranded copper conductor on request

    2. Insulation- XLPE plastic IEC 60092-351

    3. Bedding- filler tape4. Armour

    - copper wire braid, coverage > 90% IEC 60092-350- tinned copper wire braid on request

    5. Sheath- polyolefine plastic, SHF1 IEC 60092-359- on request, thermosetting polyolefine, SHF2- standard colour black, other colours on request

    10

    0 , 6 / 1 k V C A B L E S

    5 / 2 0 1 4

    LKSM-HFArmoured power andcontrol cable 0,6/1kV

    Application: For fixed installation in most areas and on open deck in ships.

    Main characteristics

    Rated voltage AC 0,6/1kV (1,2kV)DC 0,9/1,5kV (if voltage to earth does not exceed 0,9kV)

    Maximum conductortemperature + 90 CFlame-retardant IEC 60332-1-2 -test for single insulated wire and cable

    IEC 60332-3-22 -test for bunched wires and cables,category A

    Halogen-free IEC 60754 seriesSmoke emission IEC 61034 seriesOil resistance (only SHF2) IEC 60811-2-1 conditions according to 60092-359/SHF2

    Minimum recommended installation temperature -15 CLowest operation temperature -40 C

    Core identification: see technical information section

    Identification: Lot number, cable type, cable size, voltage, temperature,standards, production month, manufacturer's name and

    meter marking printed on the sheath

    Flame-retardant

    Fire-resistantHalogen-freeLow smokeemissionOil resistant(only SHF2)

  • 8/9/2019 Helkama Bica Marine and Offshore Cables (1)

    11/84

    LKSM-HF 0,6/1kVPart number

    Number ofconductors &cross-section

    n x mm2

    Nominalouter

    diameter

    mm

    Approximateweight kg/km

    CurrentRating Aat +45C

    Min. bendingradius fixedinstallation

    mmNormal G-type

    Cross-section of

    armour

    mm2

    25955 1x1,0 3,0 6,0 70 18 4025736 1x1,5 3,0 6,5 75 23 4025738 1x2,5 3,1 7,0 90 30 4525740 27052 1x4 3,1 7,5 105 40 4525742 27054 1x6 3,1 8,0 130 52 5025744 27056 1x10 3,5 9,5 190 72 6026237 27059 1x16 Flex 4,1 10,5 240 94 6526238 27061 1x25 Flex 4,9 13,0 360 123 8026239 27063 1x35 Flex 5,5 14,0 460 153 9026240 27065 1x50 Flex 8,7 17,0 650 196 10526241 27067 1x70 Flex 11,4 19,0 885 240 115

    26242 27069 1x95 Flex 11,5 21,5 1115 284 13026243 27071 1x120 Flex 14,5 23,5 1405 331 14526244 27073 1x150 Flex 14,7 26,5 1720 381 16026245 27075 1x185 Flex 15,2 29,0 2065 429 18026246 27077 1x240 Flex 18,2 32,5 2715 507 20026247 27079 1x300 Flex 18,7 35,5 3300 582 21525956 2x1,0 3,6 9,0 110 15 5525770 2x1,5 3,8 9,5 130 20 6025785 2x2,5 4,3 10,5 160 26 6525801 2x4 4,9 12,0 210 34 7525803 2x6 5,4 13,0 315 44 8025805 2x10 8,7 15,5 480 61 9526254 2x16 Flex 10,0 18,0 625 80 11026255 2x25 Flex 14,5 23,0 985 105 14026256 2x35 Flex 14,7 25,5 1240 130 15526257 2x50 Flex 18,1 29,5 1700 167 18026258 2x70 Flex 18,7 34,0 2270 204 20526259 2x95 Flex 22,2 39,0 2965 241 23525957 3x1,0 3,7 9,5 130 13 6025772 25773 3x1,5 4,1 10,0 155 16 6525786 25787 3x2,5 4,6 11,0 195 21 7025802 25880 3x4 5,2 12,5 260 28 8025804 25882 3x6 5,8 14,0 370 36 8525806 25884 3x10 9,3 16,5 570 50 10026271 26272 3x16 Flex 10,7 19,0 750 66 11526273 26274 3x25 Flex 14,6 24,5 1165 86 15026275 26276 3x35 Flex 15,0 27,0 1505 107 16526277 26278 3x50 Flex 18,3 32,0 2100 137 19526279 26280 3x70 Flex 22,0 36,5 2850 168 22026281 26282 3x95 Flex 22,8 42,0 3685 199 25526283 26284 3x120 Flex 37,8 47,0 4745 232 28526285 26286 3x150 Flex 39,3 53,0 5885 267 32026287 26288 3x185 Flex 47,9 59,5 7265 300 360

    11 0 , 6 / 1 k V

    C A B L E S

    5 / 2 0 1 4

    G-type is with yellow/green earth conductor and marking on sheath is, for example, 3G1,5

    Table continues on next pagePart number for oil resistant SHF2 cable:4 + code from above table 4xxxxx

  • 8/9/2019 Helkama Bica Marine and Offshore Cables (1)

    12/84

    Tel. +358 2 410 8700, fax +358 2 237 2428, www.helkamabica.com

    25958 4x1,0 4,1 10,0 150 13 6525774 25775 4x1,5 4,5 11,0 180 16 7025788 25789 4x2,5 5,0 12,5 240 21 7525830 25831 4x4 5,8 13,5 320 28 8525832 25833 4x6 8,8 15,5 475 36 9525834 25835 4x10 10,3 18,0 695 50 11026301 26302 4x16 Flex 11,9 21,0 945 66 13026303 26304 4x25 Flex 14,8 27,0 1440 86 16526305 26306 4x35 Flex 18,1 29,5 1900 107 18026307 26308 4x50 Flex 19,5 35,5 2635 137 21526309 26310 4x70 Flex 22,6 40,0 3590 168 245

    26311 26312 4x95 Flex 37,8 47,0 4850 199 28526313 26314 4x120 Flex 39,3 52,0 6010 232 315 4x150 Flex 48,2 59,0 7565 267 35525959 5x1,0 4,5 10,5 175 10 6525776 25777 5x1,5 5,0 12,0 220 13 7525790 25791 5x2,5 5,6 13,5 285 17 8026011 26012 5x4 8,6 15,0 410 23 9526013 26014 5x6 9,7 17,0 565 30 10526015 26016 5x10 11,5 20,0 830 42 12026331 26332 5x16 Flex 13,2 23,0 1070 55 14026333 26334 5x25 Flex 18,1 29,5 1655 71 18025960 7x1,0 4,9 11,5 215 9 7525961 10x1,0 8,7 15,0 320 8 9025962 12x1,0 9,0 15,0 350 8 9525963 14x1,0 9,4 16,0 385 7 10025964 16x1,0 11,4 17,0 445 7 10525965 19x1,0 11,4 17,5 490 7 11025977 24x1,0 12,5 20,5 610 6 12525978 27x1,0 12,8 21,0 655 6 13025981 37x1,0 14,4 23,5 840 5 145

    12

    0 , 6 / 1 k V C A B L E S

    5 / 2 0 1 4

    LKSM-HF 0,6/1kV

    Part number

    Number ofconductors &cross-section

    n x mm2

    Nominalouter

    diameter

    mm

    Approximateweight kg/km

    CurrentRating Aat +45C

    Min. bendingradius fixedinstallation

    mmNormal G-type

    Cross-section of

    armour

    mm2

    G-type is with yellow/green earth conductor and marking on sheath is, for example, 3G16

    Table continues on next pagePart number for oil resistant SHF2 cable:4 + code from above table 4xxxxx

  • 8/9/2019 Helkama Bica Marine and Offshore Cables (1)

    13/84

    25778 25779 7x1,5 5,4 13,0 265 12 8026025 26026 10x1,5 9,6 16,5 390 11 10025780 25846 12x1,5 9,9 17,0 440 10 10526027 26028 14x1,5 10,5 18,0 490 10 11026030 26029 16x1,5 11,5 19,0 545 9 11525782 25781 19x1,5 11,7 19,5 610 9 12025828 25829 24x1,5 13,9 23,5 780 8 14025783 25847 27x1,5 14,1 24,0 845 8 14525784 25848 37x1,5 16,0 26,5 1085 7 16025792 25793 7x2,5 8,5 15,0 380 16 9026033 26034 10x2,5 11,5 18,5 535 14 115

    25794 25795 12x2,5 11,5 19,0 595 13 11526035 26036 14x2,5 11,8 20,5 680 13 12526037 26038 16x2,5 12,5 21,5 760 12 13025796 25797 19x2,5 13,2 22,5 855 11 13525798 25799 24x2,5 15,7 26,0 1080 10 16025768 25769 27x2,5 16,1 27,0 1175 10 165

    13 0 , 6 / 1 k V

    C A B L E S

    5 / 2 0 1 4

    LKSM-HF 0,6/1kV

    Part number

    Number ofconductors &cross-section

    n x mm2

    Nominalouter

    diameter

    mm

    Approximateweight kg/km

    CurrentRating Aat +45C

    Min. bendingradius fixedinstallation

    mmNormal G-type

    Cross-section of

    armour

    mm2

    G-type is with yellow/green earth conductor and marking on sheath is, for example, 3G16

    Part number for oil resistant SHF2 cable:4 + code from above table 4xxxxx

  • 8/9/2019 Helkama Bica Marine and Offshore Cables (1)

    14/84

    Tel. +358 2 410 8700, fax +358 2 237 2428, www.helkamabica.com

    DESIGN: STANDARDS:IEC 60092-353,design

    1. Conductor- stranded copper conductor 1,510mm 2 IEC 60228, class 2- stranded copper conductor 16150mm 2 IEC 60228, class 5- tinned stranded copper conductor on request

    2. Insulation- XLPE plastic IEC 60092-351

    3. Bedding- extruded filler

    4. Armour- copper wire braid, coverage > 90% IEC 60092-350- tinned copper wire braid and galvanized steel wire braid on request

    5. Sheath- polyolefine plastic, SHF1 IEC 60092-359- on request, thermosetting polyolefine, SHF2- standard colour black, other colours on request

    Application: For fixed installation in most areas and on open deck in ships.

    Main characteristics

    Rated voltage AC 0,6/1kV (1,2kV)DC 0,9/1,5kV (if voltage to earth does not exceed 0,9kV)

    Maximum conductortemperature + 90 CFlame-retardant IEC 60332-1-2 -test for single insulated wire and cable

    IEC 60332-3-22 -test for bunched wires and cables,category A

    Halogen-free IEC 60754 seriesSmoke emission IEC 61034 seriesOil resistance (only SHF2) IEC 60811-2-1 conditions according to 60092-359/SHF2

    Minimum recommended installation temperature -15 CLowest operation temperature -40 C

    Core identification: see technical information section

    Identification: Lot number, cable type, cable size, voltage, temperature,standards, production month, manufacturer's name and

    meter marking printed on the sheath

    14

    0 , 6 / 1 k V C A B L E S

    5 / 2 0 1 4

    LKMSM-HFArmoured power cablewith extruded filler 0,6/1kV

    Flame-retardant

    Fire-resistantHalogen-freeLow smokeemissionOil resistant(only SHF2)

  • 8/9/2019 Helkama Bica Marine and Offshore Cables (1)

    15/84

    27232 2x1,5 4,9 11,5 195 20 7027234 2x2,5 5,4 12,5 230 26 7527236 2x4 6,0 14,0 290 34 8527238 2x6 9,1 15,5 425 44 9027240 2x10 10,7 17,5 580 61 10527243 2x16 12,4 20,0 740 80 12027245 2x25 15,4 24,5 1085 105 14527247 2x35 17,1 27,0 1400 130 16027249 2x50 20,2 31,0 1895 167 19027264 27266 3x1,5 5,1 12,0 220 16 7527268 27270 3x2,5 5,7 13,5 275 21 8027272 27274 3x4 6,4 14,5 345 28 85

    27276 27278 3x6 9,7 16,0 495 36 9527280 27282 3x10 11,4 18,5 685 50 11027285 27287 3x16 13,2 21,0 885 66 12527289 27291 3x25 16,4 26,0 1320 86 15527293 27295 3x35 18,2 28,5 1710 107 17027297 27299 3x50 21,9 33,5 2345 137 20027301 27303 3x70 25,4 38,5 3200 168 23027305 27307 3x95 40,6 45,0 4270 199 27027309 27311 3x120 44,8 49,0 5235 232 29527313 27315 3x150 51,7 55,5 6610 267 33527328 27330 4x1,5 5,6 13,0 260 16 8027332 27334 4x2,5 6,3 14,0 320 21 8527336 27338 4x4 9,5 16,0 430 28 9527340 27342 4x6 10,6 17,5 590 36 10527344 27346 4x10 12,5 20,0 830 50 12027349 27351 4x16 14,5 23,0 1085 66 14027353 27355 4x25 18,2 28,5 1605 86 17027357 27359 4x35 20,2 31,5 2105 107 19027361 27363 4x50 24,1 37,0 2875 137 22027365 27367 4x70 45,7 43,0 4120 168 26027369 27371 4x95 45,0 49,0 5245 199 29527373 27375 4x120 51,2 55,0 6575 232 33027392 27394 5x1,5 6,1 14,0 300 13 8527396 27398 5x2,5 9,2 15,5 395 17 9527400 27402 5x4 10,4 17,0 510 23 10527404 27406 5x6 11,8 19,0 690 30 11527408 27410 5x10 13,8 22,0 985 42 130

    27413 27415 5x16 16,0 25,5 1300 55 15227417 27419 5x25 20,1 31,0 1925 71 185

    15 0 , 6 / 1 k V

    C A B L E S

    5 / 2 0 1 4

    LKMSM-HF 0,6/1kV

    Part number

    Number ofconductors &cross-section

    n x mm2

    Nominalouter

    diametermm

    Approximateweight kg/km

    CurrentRating Aat +45C

    Min. bendingradius fixedinstallation

    mmNormal G-type

    Cross-section of

    armourmm2

    G-type is with yellow/green earth conductor and marking on sheath is, for example, 3G1,5

    Part number for oil resistant SHF2 cable:4 + code from above table 4xxxxx

  • 8/9/2019 Helkama Bica Marine and Offshore Cables (1)

    16/84

    Tel. +358 2 410 8700, fax +358 2 237 2428, www.helkamabica.com

    16

    0 , 6 / 1 k V C A B L E S

    5 / 2 0 1 4

    LKAM-HFScreened power and control cable0,6/1kV

    DESIGN: STANDARDS:IEC 60092-353, design

    1. Conductor- stranded copper conductor IEC 60228, class 2- tinned stranded copper conductor on request

    2. Insulation- XLPE plastic IEC 60092-351

    3. Screen- drain wire of tinned copper 1,0mm 2 (in all sizes)- aluminium polyester tape, IEC 60092-350 coverage 100%

    4. Sheath- polyolefine plastic, SHF1 IEC 60092-359- on request, thermosetting polyolefine, SHF2- standard colour black, other colours on request

    Application: For fixed installation in most areas and on open deck in ships, especially when lightweight cables are needed.

    Main characteristics

    Rated voltage AC 0,6/1kV (1,2kV)DC 0,9/1,5kV (if voltage to earth does not exceed 0,9kV)

    Maximum conductortemperature + 90 CFlame-retardant IEC 60332-1-2 -test for single insulated wire and cable

    IEC 60332-3-22 -test for bunched wires and cables,category A

    Halogen-free IEC 60754 seriesSmoke emission IEC 61034 series

    Minimum recommended installation temperature -15 CLowest operation temperature -40 C

    Core identification: see technical information section

    Identification: Lot number, cable type, cable size, voltage, temperature,standards, production month, manufacturer's name andmeter marking printed on the sheath

    Flame-retardantFire-resistantHalogen-freeLow smokeemissionOil resistant(only SHF2)

  • 8/9/2019 Helkama Bica Marine and Offshore Cables (1)

    17/84

    17 0 , 6 / 1 k V

    C A B L E S

    5 / 2 0 1 4

    LKAM-HF 0,6/1kVPart number

    Number ofconductors &cross-section

    n x mm2

    Nominalouter

    diametermm

    Approximateweight kg/km

    CurrentRating Aat +45C

    Min. bendingradius fixedinstallation

    mm27102 2x1,5 9,0 100 20 5527106 27107 3x1,5 9,5 125 16 5527110 27111 4x1,5 10,0 150 16 6027114 27115 5x1,5 11,0 175 13 6527118 27119 7x1,5 12,0 220 12 7027140 27141 10x1,5 15,5 310 11 9027122 27123 12x1,5 16,0 350 10 9527144 27145 14x1,5 16,5 395 10 10027148 27149 16x1,5 17,5 450 9 10527126 27127 19x1,5 18,5 510 9 11027130 27131 24x1,5 22,0 650 8 13027134 27135 27x1,5 22,5 710 8 13527155 27156 32x1,5 23,5 825 7 14027136 27137 37x1,5 25,0 935 7 15027104 2x2,5 9,5 130 26 6027108 27109 3x2,5 10,5 160 21 6027112 27113 4x2,5 11,0 195 21 6527116 27117 5x2,5 12,5 240 17 7527120 27121 7x2,5 13,5 300 16 8027142 27143 10x2,5 17,5 430 14 10527124 27125 12x2,5 18,0 495 13 10527146 27147 14x2,5 18,5 565 13 11027150 27151 16x2,5 19,5 635 12 12027128 27129 19x2,5 21,0 740 11 12527132 27133 24x2,5 25,0 930 10 15027138 27139 27x2,5 25,5 1025 10 15027157 27158 32x2,5 26,5 1195 9 16027152 27153 37x2,5 28,5 1355 9 170

    Normal G-type

    G-type is with yellow/green earth conductor and marking on sheath is, for example, 3G1,5

    Part number for oil resistant SHF2 cable:4 + code from above table 4xxxxx

  • 8/9/2019 Helkama Bica Marine and Offshore Cables (1)

    18/84

    Tel. +358 2 410 8700, fax +358 2 237 2428, www.helkamabica.com

    18

    0 , 6 / 1 k V C A B L E S

    5 / 2 0 1 4

    DESIGN: STANDARDS:IEC 60092-353, design

    1. Conductor- stranded flexible IEC 60228,

    copper conductor class 5

    2. Insulation- HF90 plastic IEC 60092-351- standard colour black, other colours on request- on request, oil resistant thermosetting polyolefine, SHF2

    LKEM-HFSwitchboard wire0,6/1kV

    Application: For fixed wiring in switchboards, control panels and other enclosures.

    Main characteristics

    Rated voltage AC 0,6/1kV (1,2kV)DC 0,9/1,5kV (if voltage to earth does not exceed 0,9kV)

    Maximum conductortemperature + 90 CFlame-retardant IEC 60332-1-2 -test for single insulated wire and cableHalogen-free IEC 60754 series

    Smoke emission IEC 61034 series

    Minimum recommended installation temperature -15 CLowest operation temperature -40 C

    Identification: Cable type, cable size, voltage and manufacturer's name

    Flame-

    retardantFire-resistantHalogen-freeLow smokeemissionOil resistant(only SHF2)

  • 8/9/2019 Helkama Bica Marine and Offshore Cables (1)

    19/84

    19 0 , 6 / 1 k V

    C A B L E S

    5 / 2 0 1 4

    LKEM-HF 0,6/1kVPart number

    Number of

    conductors &cross-sectionn x mm2

    Nominal

    outerdiametermm

    Approximateweight kg/km

    Current

    Rating Aat +45C

    Min. bending

    radius fixedinstallationmm

    25117 * 1x0,5 2,3 10 11 1025120 1x0,75 2,7 14 14 1525121 1x1,0 2,8 17 17 1525122 1x1,5 3,1 21 22 1525124 1x2,5 3,6 32 30 1525125 1x4 4,1 45 39 2025126 1x6 4,7 63 50 2025128 1x10 5,7 103 71 2525130 1x16 6,7 154 94 3025132 1x25 8,6 244 123 35

    25134 1x35 9,7 334 153 4025136 1x50 11,9 476 196 5025138 1x70 13,7 671 240 5525165 1x95 16,2 887 284 6525166 1x120 18,2 1125 331 7525279 1x150 20,8 1424 381 8525281 1x185 23,3 1753 429 9525283 1x240 26,8 2357 507 11025285 1x300 28,9 2900 582 120

    * Rated voltage 300/500V Available in colours:

    blue, dark blue, black, brown, red, yellow, green, yellow/green, grey, orange, violet and whiteOther colours on request Delivery lengths:0,5 mm 2, 0,75 mm 2, 1 mm 2, 1,5 mm 2 and 2,5 mm 2 available in 200 m boxes or 500 m drums4 mm 2 available in 100 m boxes or 500 m drums6 mm 2 and 10 mm 2 available in 100 m coils or 500 m drums

    Part number for oil resistant SHF2 cable:4 + code from above table 4xxxxx

  • 8/9/2019 Helkama Bica Marine and Offshore Cables (1)

    20/84

    Tel. +358 2 410 8700, fax +358 2 237 2428, www.helkamabica.com

    DESIGN: STANDARDS:IEC 60092-353, design

    1. Conductor-stranded copper conductor 1,0-10mm 2 IEC 60228, class 2-stranded copper conductor 16-300mm 2 IEC 60228, class 5- tinned stranded copper conductor on request

    2. Insulation- XLPE plastic IEC 60092-351

    3. Bedding- filler tape

    4. Screen- copper tape, coverage 100%

    5. Armour- copper wire braid, coverage > 90% IEC 60092-350- tinned copper wire braid on request

    6. Sheath- polyolefine plastic, SHF1 IEC 60092-359- on request, thermosetting polyolefine, SHF2- standard colour black, other colours on request

    20

    E M C C A B L E S

    5 / 2 0 1 4

    LKSM-EMC

    Application: For fixed installation in most areas and on open deck in ships.Design to meet requirements for improved EMC screening properties.

    Main characteristics

    Rated voltage AC 0,6/1kV (1,2kV)DC 0,9/1,5kV (if voltage to earth does not exceed 0,9kV)

    Maximum conductortemperature + 90 CFlame-retardant IEC 60332-1-2 -test for single insulated wire and cable

    IEC 60332-3-22 -test for bunched wires and cables,category A

    Halogen-free IEC 60754 series

    Smoke emission IEC 61034 seriesOil resistance (only SHF2) IEC 60811-2-1 conditions according to 60092-359/SHF2

    Transfer impedance IEC 61196-1 (typical value 26dB over 1m/mat 100MHz [20m/m])

    For details see general information section

    Minimum recommended installation temperature -15 CLowest operation temperature -40 C

    Core identification: See technical information section.

    Identification: Lot number, cable type, cable size, voltage, temperature,standards, production month, manufacturer's name andmeter marking printed on the sheath

    Armoured power and control cablewith improved EMC screening 0,6/1kV

    Flame-retardant

    Fire-resistantHalogen-freeLow smokeemissionOil resistant(only SHF2)

  • 8/9/2019 Helkama Bica Marine and Offshore Cables (1)

    21/84

    26904 1x1,0 4,0 3,0 6,0 90 18 3727513 1x1,5 4,0 3,0 6,5 100 23 3927514 1x2,5 4,5 3,0 7,0 110 30 4127515 1x4 5,0 3,1 7,5 130 40 4527516 1x6 6,0 3,1 8,0 155 52 4827517 1x10 7,0 3,3 9,5 230 72 5727518 1x16 8,5 4,2 11,0 280 94 6627519 1x25 10,5 4,9 13,5 405 123 8027520 1x35 11,5 5,6 14,5 515 153 8627521 1x50 14,0 8,8 17,0 705 196 10227522 1x70 16,0 10,0 19,0 940 240 11427523 1x95 18,5 11,5 21,5 1185 284 12927524 1x120 20,0 12,4 24,0 1465 331 14327525 1x150 23,0 14,7 26,5 1815 381 16027526 1x185 25,5 15,3 29,5 2165 429 17627527 1x240 29,0 17,1 33,0 2795 507 19727528 1x300 31,0 18,8 35,5 3425 582 21326905 2x1,0 6,5 3,3 9,5 130 15 5627480 2x1,5 7,0 3,6 10,0 145 20 5927481 2x2,5 8,0 4,1 11,0 180 26 6527482 2x4 9,0 4,6 12,0 250 34 7227483 2x6 10,5 5,1 13,0 340 44 7927484 2x10 12,5 8,5 16,0 535 61 9527485 2x16 15,5 11,4 18,5 725 80 11227486 2x25 19,5 12,4 23,0 1045 105 13827487 2x35 21,5 14,7 25,5 1325 130 15327529 2x50 26,0 16,4 30,0 1785 167 17927530 2x70 29,5 18,8 34,0 2385 204 20427531 2x95 34,5 21,3 39,0 3100 241 235

    21E M

    C C A B L E S

    5 / 2 0 1 4

    LKSM-EMC 0,6/1kV Number ofconductors &cross-section

    n x mm2

    Nominalouter

    diameter

    mm

    Approx-imateweight

    kg/km

    CurrentRating Aat +45C

    Min. bendingradius fixedinstallation

    mm

    Cross-section of

    armour

    mm2

    Part number

    Normal G-type

    Table continues on next pagePart number for oil resistant SHF2 cable:4 + code from above table 4xxxxx

    Diameterof screen

    mm

  • 8/9/2019 Helkama Bica Marine and Offshore Cables (1)

    22/84

    Tel. +358 2 410 8700, fax +358 2 237 2428, www.helkamabica.com

    26906 26988 3x1,0 7,0 3,6 10,0 155 13 5926861 26862 3x1,5 7,5 3,9 10,5 175 16 6226863 26864 3x2,5 8,5 4,3 11,5 215 21 6826865 26866 3x4 10,0 5,0 12,5 285 28 7626867 26868 3x6 11,0 5,6 14,0 395 36 8426869 26870 3x10 13,5 8,9 16,5 630 50 10026872 26851 3x16 16,5 10,9 19,5 835 66 11826874 26852 3x25 21,0 14,6 24,5 1245 86 14726876 26853 3x35 23,0 15,2 27,0 1590 107 16226878 26854 3x50 27,5 18,3 32,0 2205 137 19326880 26855 3x70 32,0 22,0 36,5 2970 168 21926882 26856 3x95 37,0 22,9 42,0 3825 199 25226884 26857 3x120 41,5 37,9 47,0 4895 232 28326886 26858 3x150 47,5 39,4 53,0 6060 267 31926907 26989 4x1,0 8,0 3,9 10,5 175 13 6326942 26943 4x1,5 8,5 4,3 11,0 200 16 6726944 26945 4x2,5 9,5 4,9 12,5 260 21 7426946 26947 4x4 11,0 5,5 13,5 340 28 8226948 26949 4x6 12,5 8,5 15,5 505 36 9426950 26951 4x10 15,0 9,9 18,5 750 50 11026952 26953 4x16 18,0 12,0 22,0 1020 66 13126954 26955 4x25 23,0 14,8 27,0 1510 86 16126956 26957 4x35 25,5 18,2 30,0 1970 107 17926958 26959 4x50 31,0 19,6 35,5 2715 137 21326960 26961 4x70 35,5 22,6 40,0 3675 168 24126962 26963 4x95 42,0 37,9 47,5 4935 199 28426964 26965 4x120 46,5 39,4 52,5 6095 232 31426966 26967 4x150 52,5 43,7 59,0 7610 267 35526908 26990 5x1,0 8,5 4,2 11,0 200 10 6727488 27838 5x1,5 9,5 4,7 12,0 240 13 7327489 27839 5x2,5 10,5 5,3 13,5 305 17 8027490 27940 5x4 12,5 11,3 15,5 460 23 9227491 27941 5x6 14,0 11,4 17,0 615 30 10227492 27942 5x10 16,5 11,0 20,0 875 42 12027493 27943 5x16 20,0 13,3 23,5 1220 55 14227494 27944 5x25 25,5 16,4 29,5 1775 71 177

    22

    E M C C A B L E S

    5 / 2 0 1 4

    Table continues on next pagePart number for oil resistant SHF2 cable:4 + code from above table 4xxxxx

    LKSM-EMC 0,6/1kV Number ofconductors &cross-section

    n x mm2

    Nominalouter

    diameter

    mm

    Approx-imateweight

    kg/km

    CurrentRating Aat +45C

    Min. bendingradius fixedinstallation

    mm

    Cross-section of

    armour

    mm2

    Part number

    Normal G-type

    Diameterof screen

    mm

  • 8/9/2019 Helkama Bica Marine and Offshore Cables (1)

    23/84

    23E M

    C C A B L E S

    5 / 2 0 1 4

    26909 26991 7x1,0 9,5 4,7 12,5 240 9 7426910 26992 10x1,0 12,5 9,9 15,5 365 8 9326911 26993 12x1,0 13,0 9,9 16,0 395 8 9626912 26994 14x1,0 13,5 9,9 16,5 430 7 10026913 26995 16x1,0 14,5 10,0 17,5 465 7 10526914 26996 19x1,0 15,0 10,2 18,5 550 7 11126915 26997 24x1,0 18,0 12,2 21,5 695 6 13026916 26998 27x1,0 18,5 12,5 22,0 750 6 13226917 26999 37x1,0 20,5 14,1 24,5 935 5 14727495 27840 7x1,5 10,0 5,2 13,0 285 23 7827497 27842 10x1,5 13,5 9,2 16,5 420 20 9927499 27844 12x1,5 14,0 10,0 17,0 465 16 10227501 27846 14x1,5 15,0 10,2 18,0 520 16 10827503 27848 16x1,5 15,5 10,8 19,0 570 13 11327505 27850 19x1,5 16,5 11,4 20,0 675 23 11927507 27852 24x1,5 19,5 13,6 23,0 855 20 13927509 27854 27x1,5 20,0 13,9 24,0 930 16 14327511 27856 37x1,5 22,5 15,7 26,5 1175 23 16027496 27841 7x2,5 11,5 5,8 14,5 365 30 8727498 27843 10x2,5 15,5 11,4 18,5 555 26 11127500 27845 12x2,5 16,0 11,5 19,0 620 21 11527502 27847 14x2,5 17,0 11,5 20,0 690 21 12027504 27849 16x2,5 18,0 12,2 21,5 775 17 12827506 27851 19x2,5 19,0 12,9 22,5 910 30 13527508 27853 24x2,5 22,5 15,3 26,0 1145 26 15727510 27855 27x2,5 23,0 15,8 27,0 1250 21 161

    Part number for oil resistant SHF2 cable:4 + code from above table 4xxxxx

    LKSM-EMC 0,6/1kV Number ofconductors &cross-section

    n x mm2

    Nominalouter

    diameter

    mm

    Approx-imateweight

    kg/km

    CurrentRating Aat +45C

    Min. bendingradius fixedinstallation

    mm

    Cross-section of

    armour

    mm2

    Part number

    Normal G-type

    Diameterof screen

    mm

  • 8/9/2019 Helkama Bica Marine and Offshore Cables (1)

    24/84

    Tel. +358 2 410 8700, fax +358 2 237 2428, www.helkamabica.com

    DESIGN: STANDARDS:IEC 60092-353, design

    1. Conductor-stranded copper conductor 1,0-10mm 2 IEC 60228, class 2-stranded copper conductor 16-300mm 2 IEC 60228, class 5- tinned stranded copper conductor on request

    2. Insulation- Mica tape- XLPE plastic IEC 60092-351

    3. Bedding- filler tape

    4. Screen- copper tape, coverage 100%5. Armour

    - copper wire braid, coverage > 90% IEC 60092-350- tinned copper wire braid on request

    6. Sheath- polyolefine plastic, SHF1, standard colour orange IEC 60092-359- on request thermosetting polyolefine, SHF2, standard colour black - other colours on request

    24

    E M C C A B L E S

    5 / 2 0 1 4

    LKSM-EMC-FRHF

    Application: For fixed installation in all areas and on open deck in ships.

    If the cable is exposed to direct sun light protective covering or cable withblack outer shetah is recommended. Design to meet requirements for improvedEMC screening properties.

    Main characteristics

    Rated voltage AC 0,6/1kV (1,2kV)DC 0,9/1,5kV (if voltage to earth does not exceed 0,9kV)

    Maximum conductortemperature + 90 CFlame-retardant IEC 60332-1-2 -test for single insulated wire and cable

    IEC 60332-3-22 -test for bunched wires and cables,category A

    Fire -resistant IEC 60331-1 and IEC 60331-2Halogen-free IEC 60754 seriesSmoke emission IEC 61034 series

    Transfer impedance IEC 61196-1 (typical value 26dB over 1m/mat 100MHz [20m/m])

    For details see general information section

    Minimum recommended installation temperature -15 CLowest operation temperature -40 C

    Core identification: See technical information section.

    Identification: Lot number, cable type, cable size, voltage, temperature,standards, production month, manufacturer's name andmeter marking printed on the sheath

    Fire-resistant armoured powerand control cable with improvedEMC screening 0,6/1kV

    Flame-retardantFire-resistantHalogen-freeLow smoke

    emissionOil resistant(only SHF2)

  • 8/9/2019 Helkama Bica Marine and Offshore Cables (1)

    25/84

    25E M

    C C A B L E S

    5 / 2 0 1 4

    LKSM-EMC-FRHF0,6/1kV

    Number ofconductors &cross-section

    n x mm2

    Nominalouter

    diameter

    mm

    Approx-imateweight

    kg/km

    CurrentRating Aat +45C

    Min. bendingradius fixedinstallation

    mm

    Cross-section of

    armour

    mm2

    1x1,0 3,0 6,0 105 18 35 1x1,5 3,0 7,0 115 23 40 1x2,5 3,1 7,5 125 30 45 1x4 3,1 8,0 145 40 45 1x6 3,1 8,5 170 52 50 1x10 3,5 10,0 230 72 60 1x16 4,1 11,0 285 94 65 1x25 4,9 13,0 410 123 80 1x35 5,5 14,5 515 153 85 1x50 8,7 17,0 705 196 100 1x70 9,9 19,0 945 240 115 1x95 11,5 21,5 1195 284 130 1x120 12,3 23,5 1475 331 140 1x150 14,7 26,5 1820 381 160 1x185 15,2 29,0 2175 429 175 1x240 17,0 32,5 2800 507 195 1x300 18,7 35,5 3430 582 210

    2x1,0 3,3 9,5 135 15 5527872 2x1,5 4,1 10,5 165 20 6527873 2x2,5 4,6 11,5 190 26 7027874 2x4 5,1 13,0 270 34 8027875 2x6 5,6 14,0 390 44 8527876 2x10 9,0 16,5 570 61 10027877 2x16 11,4 19,0 745 80 11527878 2x25 12,7 23,5 1075 105 14027879 2x35 14,8 26,0 1355 130 15527880 2x50 16,7 30,0 1830 167 18027881 2x70 19,1 34,5 2435 204 205 2x95 21,5 40,0 3170 241 240

    3x1,0 3,6 10,0 155 13 6027882 3x1,5 4,4 11,5 210 16 7027883 3x2,5 4,9 12,5 260 21 7527884 3x4 5,5 13,5 325 28 8027885 3x6 11,3 15,5 505 36 9027886 3x10 9,7 17,5 665 50 10527887 3x16 11,6 20,5 900 66 12527888 3x25 14,7 25,5 1335 86 15527889 3x35 15,9 28,0 1695 107 17027890 3x50 18,5 33,0 2285 137 20027891 3x70 22,2 37,5 3060 168 22527892 3x95 43,2 44,0 4160 199 265

    27893 3x120 38,3 48,0 5010 232 29027894 3x150 40,2 54,5 6210 267 325

    4x1,0 3,9 10,5 190 13 6527897 4x1,5 4,9 12,5 250 16 7527898 4x2,5 5,5 13,5 305 21 8027899 4x4 11,3 15,5 445 28 9027900 4x6 9,3 16,5 570 36 10027905 4x10 10,8 19,5 805 50 11527906 4x16 12,9 23,0 1105 66 14027907 4x25 15,6 28,0 1620 86 17027908 4x35 18,3 31,0 2105 107 18527909 4x50 20,4 36,5 2840 137 22027910 4x70 23,4 41,5 3830 168 25027912 4x95 38,3 48,5 5060 199 290

    27913 4x120 40,4 53,5 6260 232 320 4x150 45,0 60,5 7790 267 365

    Part number

    Table continues on next pagePart number for oil resistant SHF2 cable:4 + code from above table 4xxxxx

  • 8/9/2019 Helkama Bica Marine and Offshore Cables (1)

    26/84

    Tel. +358 2 410 8700, fax +358 2 237 2428, www.helkamabica.com

    5x1,0 4,3 11,5 220 10 7027914 5x1,5 5,4 13,5 290 13 8027915 5x2,5 11,3 15,0 415 17 9027916 5x4 11,4 16,5 525 23 10027917 5x6 11,4 18,5 685 30 11027918 5x10 11,9 21,5 975 42 13027919 5x16 14,1 25,0 1320 55 15027920 5x25 17,3 30,5 1880 71 185

    7x1,0 5,2 12,5 250 9 75 10x1,0 8,5 15,5 360 8 95 12x1,0 9,9 16,0 405 8 95 14x1,0 9,9 17,0 440 7 100 16x1,0 10,0 17,5 480 7 105 19x1,0 11,4 18,5 550 7 110 24x1,0 12,4 21,5 690 6 130 27x1,0 12,7 22,0 735 6 135 30x1,0 13,2 23,0 795 6 135 37x1,0 14,4 24,5 930 5 150

    27921 7x1,5 14,1 15,0 400 12 9027923 10x1,5 10,6 18,5 485 11 11027925 12x1,5 11,0 19,0 535 10 11527927 14x1,5 11,7 20,0 590 10 12027929 16x1,5 12,4 21,5 675 9 13027931 19x1,5 13,1 22,5 750 9 13527933 24x1,5 15,6 26,0 945 8 15527935 27x1,5 15,9 27,0 1030 8 160 30x1,5 16,5 27,5 1110 7 16527937 37x1,5 18,0 30,0 1315 7 180

    27922 7x2,5 11,3 16,0 460 16 9527924 10x2,5 11,8 21,0 630 14 12527926 12x2,5 12,3 21,5 705 13 13027928 14x2,5 13,0 22,5 785 12 13527930 16x2,5 13,8 23,5 875 12 14027932 19x2,5 14,6 25,0 985 11 15027934 24x2,5 17,5 29,0 1245 10 17527936 27x2,5 17,9 30,0 1375 10 180 30x2,5 18,6 31,0 1490 10 18527938 37x2,5 20,2 33,5 1770 9 200

    26

    E M C C A B L E S

    5 / 2 0 1 4

    Number ofconductors &cross-section

    n x mm2

    Nominalouter

    diameter

    mm

    Approx-imateweight

    kg/km

    CurrentRating Aat +45C

    Min. bendingradius fixedinstallation

    mm

    Cross-section of

    armour

    mm2

    LKSM-EMC-FRHF0,6/1kV

    Part number

    Part number for oil resistant SHF2 cable:4 + code from above table 4xxxxx

  • 8/9/2019 Helkama Bica Marine and Offshore Cables (1)

    27/84

    27E M

    C C A B L E S

    5 / 2 0 1 4

  • 8/9/2019 Helkama Bica Marine and Offshore Cables (1)

    28/84

    Tel. +358 2 410 8700, fax +358 2 237 2428, www.helkamabica.com

    DESIGN: STANDARDS:IEC 60092-376, design

    1. Conductor- stranded copper conductor IEC 60228, class 2- tinned stranded copper conductor on request

    2. Insulation- XLPE plastic IEC 60092-351

    3. Twisted pair- two insulated cores twisted together to form a pair See next page for Quad

    4. Bedding- filler tape

    5. Screen - drain wire copper (in all sizes) - copper tape 100%6. Armour - copper wire braid, coverage >94% EC 60092-350 - tinned copper wire braid on request7. Sheath - polyolefine plastic, SHF1 EC 60092-359

    - on request, thermosetting polyolefine, SHF2- standard colour grey, other colours on request

    28

    E M C C A B L E S

    5 / 2 0 1 4

    RFE-EMCArmoured instrumentation andcommunication cable with improvedEMC screening 250V

    Application: For fixed installation in most areas and on open deck in ships.If the cable is exposed to direct sun light protective covering or

    cable with black outer sheath is recommended.Design to meet requirements for improved EMC screening properties.

    Main characteristicsRated voltage 150/250V (300V)Maximum conductortemperature + 90 CFlame-retardant IEC 60332-1-2 -test for single insulated wire and cable

    IEC 60332-3-22 -test for bunched wires and cables, category A

    Halogen-free IEC 60754 seriesSmoke emission IEC 61034 series

    Transfer impedance IEC 61196-1 (typical value 26dB over 1m/mat 100MHz [20m/m])

    Electrical data:Loop resistance of pair, max. / +20CPair capacitance, nom. / 800HzLoop inductance, nom.Insulation resistance / +20C

    Minimum recommended installation temperature -15 CLowest operation temperature -40 CCore identification: See technical information sectionIdentification: Lot number, cable type, cable size, voltage, temperature,standards, production month, manufacturer's name andmeter marking printed on the sheath

    0,5mm 2 0,75mm 2 1,5mm 2 Unit80 52 24,4 ohm/km55 50 60 nF/km0,6 0,6 0,7 mH/km

    1500 1500 1500 Mohm/km

    Flame-retardantFire-resistantHalogen-freeLow smokeemissionOil resistant(only SHF2)

  • 8/9/2019 Helkama Bica Marine and Offshore Cables (1)

    29/84

    29E M

    C C A B L E S

    5 / 2 0 1 4

    RFE-EMC 250V

    Part number

    Number ofconductors &cross-section

    n x mm2

    Nominalouter

    diameter

    mm

    Approximateweight kg/km

    Min. bendingradius fixedinstallation

    mm21968 1x2x0,5 7,0 95 4021969 1x3x0,5 7,0 105 4521970 2x2x0,5 Quad 7,5 115 4521971 2x2x0,5 9,5 150 6021972 3x2x0,5 10,0 165 6021973 4x2x0,5 11,0 185 6521974 7x2x0,5 13,0 270 7521975 8x2x0,5 13,5 290 8021976 10x2x0,5 15,5 365 9521977 12x2x0,5 16,0 395 9521978 14x2x0,5 17,5 445 10521979 16x2x0,5 18,0 480 110

    21980 19x2x0,5 19,5 540 11521981 24x2x0,5 21,5 655 13021982 27x2x0,5 22,5 710 13521983 30x2x0,5 23,5 775 14021984 32x2x0,5 24,5 810 14521985 37x2x0,5 26,0 900 15521987 1x2x0,75 8,0 110 4521988 1x3x0,75 8,0 130 5021989 2x2x0,75 Quad 9,0 150 5521990 2x2x0,75 11,0 175 6521991 3x2x0,75 11,5 200 7021992 4x2x0,75 13,0 255 7521993 7x2x0,75 15,5 365 9521994 8x2x0,75 16,5 400 10021995 10x2x0,75 18,5 475 11021996 12x2x0,75 19,0 520 11521997 14x2x0,75 20,5 600 12521998 16x2x0,75 22,0 655 13021999 19x2x0,75 23,5 755 14022000 24x2x0,75 26,0 900 15522001 27x2x0,75 27,0 980 16522002 30x2x0,75 28,5 1060 17022003 32x2x0,75 29,5 1140 17522004 37x2x0,75 31,0 1270 18522375 1x2x1,5 10,0 165 6022376 1x3x1,5 10,5 210 6522377 2x2x1,5 Quad 11,5 220 7022378 2x2x1,5 14,5 285 8522379 3x2x1,5 15,0 335 9022380 4x2x1,5 17,0 425 10022381 7x2x1,5 20,5 605 12022382 8x2x1,5 22,0 690 13022383 10x2x1,5 24,5 820 15022384 12x2x1,5 26,0 935 15522385 14x2x1,5 27,5 1045 16522386 16x2x1,5 29,5 1175 17522387 19x2x1,5 31,5 1335 19022388 24x2x1,5 35,5 1650 21022389 27x2x1,5 37,0 1810 22022390 30x2x1,5 39,0 1985 23522391 32x2x1,5 40,0 2090 24022392 37x2x1,5 43,5 2490 260

    Part number for oil resistant SHF2 cable:4 + code from above table 4xxxxx

  • 8/9/2019 Helkama Bica Marine and Offshore Cables (1)

    30/84

    Tel. +358 2 410 8700, fax +358 2 237 2428, www.helkamabica.com

    0,5mm 2 0,75mm 2 1,5mm 2 Unit80 52 24,4 ohm/km55 70 90 nF/km0,6 0,6 0,7 mH/km

    1500 1500 1500 Mohm/km

    DESIGN: STANDARDS:IEC 60092-376, design

    1. Conductor- stranded copper conductor IEC 60228, class 2- tinned stranded copper conductor on request

    2. Insulation- XLPE plastic IEC 60092-351

    3. Twisted pair & pair screen- two insulated cores twisted together to form a pair- plastic coated aluminium tape and a tinned copper drain wire

    4. Bedding- filler tape

    5. Screen - drain wire copper (in all sizes) - copper tape 100%6. Armour - copper wire braid, coverage >94% IEC 60092-350 - tinned copper wire braid on request7. Sheath - polyolefine plastic, SHF1 EC 60092-359

    - on request, thermosetting polyolefine, SHF2- standard colour grey, other colours on request

    30

    E M C C A B L E S

    5 / 2 0 1 4

    RFE-EMC(i)Armoured and pair screenedinstrumentation and communication cablewith improved EMC screening 250V

    Application: For fixed installation in most areas and on open deck in ships.If the cable is exposed to direct sun light protective covering or

    cable with black outer sheath is recommended.Design to meet requirements for improved EMC screening properties.

    Main characteristicsRated voltage 150/250V (300V)Maximum conductortemperature + 90 CFlame-retardant IEC 60332-1-2 -test for single insulated wire and cable

    IEC 60332-3-22 -test for bunched wires and cables, category A

    Halogen-free IEC 60754 seriesSmoke emission IEC 61034 series

    Transfer impedance IEC 61196-1 (typical value 26dB over 1m/mat 100MHz [20m/m])

    Electrical data:Loop resistance of pair, max. / +20CPair capacitance, nom. / 800HzLoop inductance, nom.Insulation resistance / +20C

    Minimum recommended installation temperature -15 CLowest operation temperature -40 CCore identification: See technical information sectionIdentification: Lot number, cable type, cable size, voltage, temperature,standards, production month, manufacturer's name andmeter marking printed on the sheath

    Flame-retardantFire-resistantHalogen-freeLow smokeemissionOil resistant(only SHF2)

  • 8/9/2019 Helkama Bica Marine and Offshore Cables (1)

    31/84

    31E M

    C C A B L E S

    5 / 2 0 1 4

    RFE-EMC(i) 250V

    Part number

    Number ofconductors &cross-section

    n x mm2

    Nominalouter

    diameter

    mm

    Approximateweight kg/km

    Min. bendingradius fixedinstallation

    mm21949 1x2x0,5 7,0 90 4021950 1x3x0,5 7,0 100 4521951 1x4x0,5 7,5 120 4521952 2x2x0,5 10,0 150 6021953 3x2x0,5 10,0 175 6021954 4x2x0,5 11,0 205 6521955 7x2x0,5 13,0 300 8021956 8x2x0,5 14,0 360 8521957 10x2x0,5 16,0 430 9521958 12x2x0,5 16,5 490 10021959 14x2x0,5 17,5 540 10521960 16x2x0,5 18,5 590 110

    21961 19x2x0,5 20,0 690 12021962 24x2x0,5 22,0 835 13521963 27x2x0,5 23,0 910 14021964 30x2x0,5 24,0 990 14521965 32x2x0,5 25,0 1050 15021966 37x2x0,5 26,5 1180 160

    21911 1x2x0,75 7,5 105 4521912 1x3x0,75 8,0 115 5021913 1x4x0,75 9,0 150 5521914 2x2x0,75 11,5 185 7021915 3x2x0,75 12,0 215 7021916 4x2x0,75 13,0 255 7521917 7x2x0,75 15,5 390 9521918 8x2x0,75 16,5 435 10021919 10x2x0,75 19,0 530 11521920 12x2x0,75 20,0 590 12021921 14x2x0,75 21,0 660 12521922 16x2x0,75 22,5 740 13521923 19x2x0,75 24,0 840 14521924 24x2x0,75 26,5 1040 16021925 27x2x0,75 28,0 1135 16521926 30x2x0,75 29,0 1230 17521927 32x2x0,75 30,0 1310 18021928 37x2x0,75 32,0 1465 190

    21930 1x2x1,5 10,0 160 60

    21931 1x3x1,5 10,5 190 6521932 1x4x1,5 11,5 220 7021933 2x2x1,5 14,5 280 8521934 3x2x1,5 16,0 370 9521935 4x2x1,5 17,0 440 10521936 7x2x1,5 20,5 645 12521937 8x2x1,5 22,0 730 13521938 10x2x1,5 25,0 890 15021939 12x2x1,5 26,0 1005 15521940 14x2x1,5 28,0 1150 17021941 16x2x1,5 29,5 1275 18021942 19x2x1,5 32,0 1490 19521943 24x2x1,5 36,0 1835 21521944 27x2x1,5 37,5 2015 22521945 30x2x1,5 40,0 2235 24021946 32x2x1,5 41,0 2450 24521947 37x2x1,5 44,0 2780 265

    Part number for oil resistant SHF2 cable:4 + code from above table 4xxxxx

  • 8/9/2019 Helkama Bica Marine and Offshore Cables (1)

    32/84

    Tel. +358 2 410 8700, fax +358 2 237 2428, www.helkamabica.com

    DESIGN: STANDARDS:IEC 60092-353, design

    1. Conductor- stranded copper conductor IEC 60228, class 5- tinned stranded copper conductor on request

    2. Insulation- XLPE plastic IEC 60092-351

    3. Bedding- filler tape

    4. Screen- copper tape, coverage 100%

    5. Armour- copper wire braid, coverage > 90% IEC 60092-350- tinned copper wire braid on request

    6. Sheath- polyolefine plastic, SHF1 IEC 60092-359- on request, thermosetting polyolefine, SHF2- standard colour black, other colours on request

    32

    1 , 8 / 3 k V C A B L E S

    5 / 2 0 1 4

    LKSM-VFD

    Application: For fixed installation in most areas and on open deck in ships.Design to meet requirements for V ariable Frequency Drivers (VFD).Suitable for voltage peaks up to 3kV.

    Main characteristics

    Rated voltage 1,8/3kV (3,6kV)Maximum conductortemperature + 90 CFlame-retardant IEC 60332-1-2 -test for single insulated wire and cable

    IEC 60332-3-22 -test for bunched wires and cables,category A

    Halogen-free IEC 60754 series

    Smoke emission IEC 61034 seriesOil resistance (only SHF2) IEC 60811-2-1 conditions according to 60092-359/SHF2

    Transfer impedance IEC 61196-1 (typical value 26dB over 1m/mat 100MHz [20m/m])

    For details see general information section

    Minimum recommended installation temperature -15 CLowest operation temperature -40 C

    Core identification: See technical information section.Cable with yellow/green protective earth (PE)conductor on request

    Identification: Lot number, cable type, cable size, voltage, temperature,standards, production month, manufacturer's name andmeter marking printed on the sheath

    Armoured power and control cablewith improved EMC screening 1,8/3kV

    Flame-retardantFire-

    resistantHalogen-freeLow smokeemissionOil resistant(only SHF2)

  • 8/9/2019 Helkama Bica Marine and Offshore Cables (1)

    33/84

    331

    , 8 / 3 k V

    C A B L E S

    5 / 2 0 1 4

    LKSM-VFD 1,8/3kV

    Part number

    Number ofconductors &cross-section

    n x mm2

    Nominalouter

    diametermm

    Approx-imateweightkg/km

    CurrentRating Aat +45C

    Min. bendingradius fixedinstallation

    mm26920 1x16 5,5 14,0 355 94 85 1)26922 1x25 8,5 16,0 495 123 95 1)26924 1x35 9,3 17,0 625 153 105 1)26926 1x50 10,3 19,0 795 196 115 1)26928 1x70 11,3 20,5 995 240 125 1)26930 1x95 12,5 23,5 1280 284 140 1)26932 1x120 13,6 25,5 1525 331 150 1)26934 1x150 14,7 27,5 1830 381 165 1)26936 1x185 15,8 29,5 2165 429 180 1)26938 1x240 17,6 33,0 2800 507 200 1)26940 1x300 18,9 35,0 3365 582 210 1)26871 3x16 16,4 26,5 1165 66 160

    26873 3x25 16,9 29,5 1525 86 18026875 3x35 18,7 32,5 1910 107 19526877 3x50 28,8 37,0 2580 137 22526879 3x70 35,0 41,0 3395 168 24526881 3x95 35,4 46,5 4295 199 280 1)26883 3x120 38,6 50,5 5200 232 305 1)26885 3x150 42,0 55,0 6255 267 330 1)26887 3x185 45,5 60,0 7475 300 360 1)26893 3x95+3x16 35,4 46,5 4655 199 280 2)26895 3x120+3x25 38,6 50,5 5755 232 305 2)26897 3x150+3x25 42,0 55,0 6825 267 330 2)

    Cross-section of

    armourmm2

    Note

    NOTE!1) = Protective earth (PE) rules are not fulfilled.

    (PE rules, for cables over 16mm 2 the PE-conductor have to be half of main conductorand min. 16mm 2. This according to IEC 60092-352, Electrical installationsin ships Choice and installation of electrical cables)

    2 = Three additional protective earth (PE) conductors.Protective earth (PE) rules are fulfilled.

    Part number for oil resistant SHF2 cable:

    4 + code from above table 4xxxxx

  • 8/9/2019 Helkama Bica Marine and Offshore Cables (1)

    34/84

    Tel. +358 2 410 8700, fax +358 2 237 2428, www.helkamabica.com

    34

    0 , 6 / 1 k V C A B L E S

    5 / 2 0 1 4

    DESIGN: STANDARDS:IEC 60092-353, design

    1. Conductor- stranded copper conductor IEC 60228, class 2 (class 5 on request)- tinned stranded copper conductor on request

    2. Insulation- Mica tape

    - XLPE plastic IEC 60092-3513. Bedding

    - separator tape

    4. Sheath- polyolefine plastic, SHF1, standard colour orange IEC 60092-359- on request thermosetting polyolefine, SHF2, standard colour black - other colours on request

    LKM-FRHF

    Application: For fixed installation in most areas and on open deck in ships.If the cable is exposed to direct sun light protective covering orcable with black outer sheath is recommended.

    Main characteristics

    Rated voltage AC 0,6/1kV (1,2kV)DC 0,9/1,5kV (if voltage to earth does not exceed 0,9kV)

    Maximum conductortemperature + 90 CFlame-retardant IEC 60332-1-2 -test for single insulated wire and cable

    IEC 60332-3-22 -test for bunched wires and cables,category A

    Fire-resistant IEC 60331-1 or IEC 60331-2Halogen-free IEC 60754 seriesSmoke emission IEC 61034 seriesOil resistance (only SHF2) IEC 60811-2-1 conditions according to 60092-359/SHF2

    Minimum recommended installation temperature -15 CLowest operation temperature -40 C

    Core identification: see technical information section

    Identification: Lot number, cable type, cable size, voltage, temperature,standards, production month, manufacturer's name andmeter marking printed on the sheath

    Fire-resistant unarmoured powerand control cable 0,6/1kV

    Flame-retardantFire-

    resistantHalogen-freeLow smokeemissionOil resistant(only SHF2)

  • 8/9/2019 Helkama Bica Marine and Offshore Cables (1)

    35/84

    35 0 , 6 / 1 k V

    C A B L E S

    5 / 2 0 1 4

    LKM-FRHF 0,6/1kVPart number

    Number ofconductors &cross-section

    n x mm2

    Nominalouter

    diameter

    mm

    Approximateweight kg/km

    CurrentRating Aat +45C

    Min. bendingradius fixedinstallation

    mmNormal G-type28275 1x1,0 5,5 40 18 3028100 1x1,5 5,5 45 23 3528102 1x2,5 6,0 60 30 3528104 1x4 6,5 80 40 4028106 1x6 7,5 100 52 4528108 1x10 8,5 150 72 5029326 1x16 Flex 9,5 200 94 4029327 1x25 Flex 12,0 310 123 5029328 1x35 Flex 13,0 405 153 5529329 1x50 Flex 15,0 560 196 6529330 1x70 Flex 17,5 775 240 7029331 1x95 Flex 20,0 1000 284 8029332 1x120 Flex 22,0 1255 331 9029333 1x150 Flex 25,0 1580 381 10029334 1x185 Flex 27,5 1920 429 17029335 1x240 Flex 31,0 2540 507 19029336 1x300 Flex 33,5 3105 582 20528276 2x1,0 8,5 75 15 5028132 2x1,5 9,0 90 20 5528134 2x2,5 10,5 125 26 6528136 2x4 11,5 165 34 7028138 2x6 13,0 260 44 7528140 2x10 15,0 385 61 9029343 - 2x16 Flex 17,5 530 80 7029344 2x25 Flex 21,5 805 105 9029345 2x35 Flex 24,0 1095 130 10029346 2x50 Flex 28,5 1525 167 17529347 2x70 Flex 32,5 2075 204 20029348 2x95 Flex 38,0 2775 241 23028278 28279 3x1,0 9,0 95 13 5528162 28163 3x1,5 9,5 115 16 6028164 28165 3x2,5 11,0 160 21 6528166 28167 3x4 12,5 220 28 7528168 28169 3x6 14,0 330 36 8528170 28171 3x10 16,0 485 50 9529366 29367 3x16 Flex 18,5 675 66 7529368 29369 3x25 Flex 23,0 1030 86 9529370 29371 3x35 Flex 26,0 1400 107 15529372 29373 3x50 Flex 30,5 1970 137 18529374 29375 3x70 Flex 35,0 2720 168 21529376 29377 3x95 Flex 41,0 3570 199 24529378 29379 3x120 Flex 45,5 4500 232 275

    G-type is with yellow/green earth conductor and marking on sheath is, for example, 3G1,5

    Table continues on next pagePart number for oil resistant SHF2 cable:4 + code from above table 4xxxxx

  • 8/9/2019 Helkama Bica Marine and Offshore Cables (1)

    36/84

    36

    0 , 6 / 1 k V C A B L E S

    5 / 2 0 1 4

    LKM-FRHF 0,6/1kVPart number

    Number ofconductors &cross-section

    n x mm2

    Nominalouter

    diameter

    mm

    Approximateweight kg/km

    CurrentRating Aat +45C

    Min. bendingradius fixedinstallation

    mmNormal G-type28280 28281 4x1,0 9,5 115 13 6028182 28183 4x1,5 11,0 150 16 6528184 28185 4x2,5 12,0 200 21 7528186 28187 4x4 13,5 280 28 8028188 28189 4x6 15,0 405 36 9028190 28191 4x10 18,0 610 50 10529400 29401 4x16 Flex 20,5 865 66 8529402 29403 4x25 Flex 26,0 1330 86 15529404 29405 4x35 Flex 28,5 1790 107 17529406 29407 4x50 Flex 34,5 2530 137 21029408 29409 4x70 Flex 39,0 3475 168 23529410 29411 4x95 Flex 46,0 4615 199 27528282 28283 5x1,0 11,0 150 10 6528212 28213 5x1,5 12,0 185 13 7028214 28215 5x2,5 13,0 240 17 8028501 28502 5x4 15,0 345 23 9028503 28504 5x6 16,5 505 30 10028505 28506 5x10 19,5 750 42 11529434 29435 5x16 Flex 22,5 1050 55 9529436 29437 5x25 Flex 28,5 1640 71 17529438 29439 5x35 Flex 31,5 2215 89 19529440 29441 5x50 Flex 38,0 3120 114 230

    G-type is with yellow/green earth conductor and marking on sheath is, for example, 3G1,5

    Table continues on next pagePart number for oil resistant SHF2 cable:4 + code from above table 4xxxxx

    Tel. +358 2 410 8700, fax +358 2 237 2428, www.helkamabica.com

  • 8/9/2019 Helkama Bica Marine and Offshore Cables (1)

    37/84

    37 0 , 6 / 1 k V

    C A B L E S

    5 / 2 0 1 4

    LKM-FRHF 0,6/1kVPart number

    Number ofconductors &cross-section

    n x mm2

    Nominalouter

    diameter

    mm

    Approximateweight kg/km

    CurrentRating Aat +45C

    Min. bendingradius fixedinstallation

    mmNormal G-type28284 28285 7x1,0 12,0 180 9 7028286 28287 10x1,0 15,0 260 8 9028288 28289 12x1,0 15,5 295 8 9528290 28291 14x1,0 16,5 330 7 10028292 28293 16x1,0 17,5 380 7 10528294 28295 19x1,0 18,5 435 7 11028296 28297 24x1,0 21,5 550 6 13028298 28299 27x1,0 22,0 600 6 13028300 28301 37x1,0 25,0 805 5 15028216 28217 7x1,5 13,0 230 12 8028240 28241 10x1,5 16,5 330 11 100

    28220 28221 12x1,5 17,5 380 10 10528244 28245 14x1,5 18,5 430 10 11028248 28249 16x1,5 19,5 485 9 11528224 28225 19x1,5 20,5 565 9 12528228 28229 24x1,5 24,5 725 8 14528232 28233 27x1,5 25,0 795 8 15028234 28235 37x1,5 28,0 1050 7 17028218 28219 7x2,5 14,5 315 16 9028242 28243 10x2,5 18,5 450 14 11028222 28223 12x2,5 19,5 510 13 11528246 28247 14x2,5 20,5 590 13 12528250 28251 16x2,5 21,5 670 12 13028226 28227 19x2,5 23,0 765 11 13528230 28231 24x2,5 27,5 995 10 16528236 28237 27x2,5 28,0 1095 10 17028238 28239 37x2,5 31,5 1450 9 190

    G-type is with yellow/green earth conductor and marking on sheath is, for example, 3G1,5

    Part number for oil resistant SHF2 cable:4 + code from above table 4xxxxx

  • 8/9/2019 Helkama Bica Marine and Offshore Cables (1)

    38/84

    Tel. +358 2 410 8700, fax +358 2 237 2428, www.helkamabica.com

    DESIGN: STANDARDS:IEC 60092-353, design

    1. Conductor- stranded copper conductor IEC 60228, class 2 (class 5 on request)- tinned stranded copper conductor on request

    2. Insulation- Mica tape- XLPE plastic EC 60092-351

    3. Bedding

    - separator tape4. Armour

    - copper wire braid, coverage > 90% IEC 60092-350- tinned copper wire braid on request

    5. Sheath- polyolefine plastic, SHF1, standard colour orange IEC 60092-359- on request thermosetting polyolefine, SHF2, standard colour black - other colours on request

    38

    0 , 6 / 1 k V C A B L E S

    5 / 2 0 1 4

    LKSM-FRHF

    Application: For fixed installation in most areas and on open deck in ships.If the cable is exposed to direct sun light protective covering orcable with black outer sheath is recommended.

    Main characteristics

    Rated voltage AC 0,6/1kV (1,2kV)DC 0,9/1,5kV (if voltage to earth does not exceed 0,9kV)

    Maximum conductortemperature + 90 CFlame-retardant IEC 60332-1-2 -test for single insulated wire and cable

    IEC 60332-3-22 -test for bunched wires and cables,category A

    Fire-resistant IEC 60331-1 or IEC 60331-2Halogen-free IEC 60754 seriesSmoke emission IEC 61034 seriesOil resistance (only SHF2) IEC 60811-2-1 conditions according to 60092-359/SHF2

    Minimum recommended installation temperature -15 CLowest operation temperature -40 C

    Core identification: see technical information section

    Identification: Lot number, cable type, cable size, voltage, temperature,standards, production month, manufacturer's name andmeter marking printed on the sheath

    Fire-resistant armoured powerand control cable 0,6/1kV

    Flame-retardantFire-resistantHalogen-freeLow smokeemissionOil resistant(only SHF2)

  • 8/9/2019 Helkama Bica Marine and Offshore Cables (1)

    39/84

    28541 1x1,0 3,0 6,5 75 18 4028568 1x1,5 3,0 7,0 80 23 4028570 1x2,5 3,1 7,0 95 30 4528572 1x4 3,1 8,0 115 40 4528574 1x6 3,1 8,5 140 52 5028576 1x10 3,5 10,0 195 72 6029060 1x16 Flex 4,1 11,0 255 94 7029061 1x25 Flex 5,2 13,5 380 123 8529062 1x35 Flex 5,5 14,5 475 153 9029063 1x50 Flex 8,7 17,5 665 196 10529064 1x70 Flex 11,4 19,5 905 240 12029065 1x95 Flex 11,5 22,0 1135 284 13529066 1x120 Flex 12,3 24,0 1410 331 15029067 1x150 Flex 14,7 27,0 1745 381 16529068 1x185 Flex 15,2 29,5 2090 429 18029069 1x240 Flex 18,2 33,0 2735 507 20029070 1x300 Flex 18,7 36,0 3325 582 21528542 2x1,0 3,5 10,0 120 15 6028602 2x1,5 3,8 10,5 140 20 6528604 2x2,5 4,3 11,5 170 26 7028606 2x4 4,9 13,0 225 34 7528608 2x6 5,4 14,0 340 44 8528610 2x10 8,7 16,5 505 61 10029071 2x16 Flex 10,0 19,0 665 80 11529072 2x25 Flex 14,5 24,0 1035 105 14529073 2x35 Flex 14,7 26,0 1300 130 16029074 2x50 Flex 18,1 30,5 1765 167 18529075 2x70 Flex 18,7 35,0 2345 204 21029076 2x95 Flex 22,2 40,0 3045 241 24528543 28544 3x1,0 4,1 10,5 145 13 6028622 28623 3x1,5 4,1 11,0 170 16 6528624 28625 3x2,5 4,6 12,0 210 21 7528626 28627 3x4 5,2 13,5 280 28 8028628 28629 3x6 5,8 15,0 400 36 9028630 28631 3x10 9,3 17,5 595 50 10529082 29083 3x16 Flex 10,7 20,0 800 66 12529084 29085 3x25 Flex 14,6 25,5 1225 86 155

    29086 29087 3x35 Flex 15,0 28,0 1570 107 17029088 29089 3x50 Flex 17,5 33,0 2170 137 20029090 29091 3x70 Flex 22,0 37,5 2935 168 22529092 29093 3x95 Flex 22,8 43,0 3775 199 26029094 29095 3x120 Flex 37,8 48,0 4840 232 290

    39 0 , 6 / 1 k V

    C A B L E S

    5 / 2 0 1 4

    LKSM-FRHF 0,6/1kV

    Part number

    Number ofconductors &cross-section

    n x mm2

    Nominalouter

    diameter

    mm

    Approximateweight kg/km

    CurrentRating Aat +45C

    Min. bendingradius fixedinstallation

    mmNormal G-type

    Cross-section of

    armour

    mm2

    G-type is with yellow/green earth conductor and marking on sheath is, for example, 3G1,5

    Table continues on next pagePart number for oil resistant SHF2 cable:4 + code from above table 4xxxxx

  • 8/9/2019 Helkama Bica Marine and Offshore Cables (1)

    40/84

    Tel. +358 2 410 8700, fax +358 2 237 2428, www.helkamabica.com

    40

    0 , 6 / 1 k V C A B L E S

    5 / 2 0 1 4

    28545 28546 4x1,0 4,1 11,0 170 13 6528642 28643 4x1,5 4,5 12,0 200 16 7028644 28645 4x2,5 5,0 13,5 255 21 8028646 28647 4x4 5,7 14,5 335 28 9028648 28649 4x6 8,8 16,5 505 36 10028650 28651 4x10 10,3 19,5 725 50 11529104 29105 4x16 Flex 11,9 22,5 1010 66 13529106 29107 4x25 Flex 14,8 28,0 1515 86 17029108 29109 4x35 Flex 18,1 30,5 1980 107 18529110 29111 4x50 Flex 19,5 36,5 2730 137 22029112 29113 4x70 Flex 22,6 41,0 3695 168 25029114 29115 4x95 Flex 35,0 48,5 4935 199 290

    28547 28548 5x1,0 4,5 12,0 195 10 7028662 28663 5x1,5 5,0 13,5 245 13 8028664 28665 5x2,5 5,6 14,5 305 17 8528705 28706 5x4 8,6 16,5 440 23 10028707 28708 5x6 9,7 18,0 600 30 11028709 28710 5x10 11,5 21,0 870 42 12529126 29127 5x16 Flex 13,2 24,5 1135 55 15029128 29129 5x25 Flex 18,1 30,5 1735 71 18529130 29131 5x35 Flex 18,6 34,0 2390 89 20529132 29133 5x50 Flex 22,4 40,0 3330 114 24528549 28550 7x1,0 4,9 13,0 240 9 8028551 28552 10x1,0 8,7 16,5 355 8 10028553 28554 12x1,0 9,0 17,0 395 8 10028555 28556 14x1,0 11,4 18,0 455 7 10528557 28558 16x1,0 11,4 19,0 505 7 11528559 28560 19x1,0 11,4 20,0 555 7 12028561 28562 24x1,0 12,5 23,5 695 6 14028563 28564 27x1,0 12,8 24,0 750 6 14528565 28566 37x1,0 14,4 26,5 960 5 16028666 28667 7x1,5 5,4 14,5 295 12 8528723 28724 10x1,5 9,6 18,0 430 11 11028670 28671 12x1,5 9,9 19,0 490 10 11528727 28728 14x1,5 11,4 20,0 555 10 12028731 28732 16x1,5 11,5 21,0 610 9 12528674 28675 19x1,5 11,7 22,0 680 9 130

    28678 28679 24x1,5 13,9 26,0 875 8 15528682 28683 27x1,5 14,1 26,5 945 8 16028684 28685 37x1,5 16,0 29,5 1220 7 18028668 28669 7x2,5 8,5 16,0 405 16 9528725 28726 10x2,5 11,5 20,0 570 14 12028672 28673 12x2,5 11,5 21,0 635 13 12528729 28730 14x2,5 11,8 22,5 730 13 13528733 28734 16x2,5 12,5 23,5 815 12 14028676 28677 19x2,5 13,2 24,5 920 11 14528680 28681 24x2,5 15,7 29,0 1165 10 17528686 28687 27x2,5 16,1 29,5 1265 10 17528688 28689 37x2,5 18,1 33,0 1660 9 200

    LKSM-FRHF 0,6/1kV

    Part number

    Number ofconductors &cross-section

    n x mm2

    Nominalouter

    diametermm

    Approximateweight kg/km

    CurrentRating Aat +45C

    Min. bendingradius fixedinstallation

    mmNormal G-type

    Cross-section of

    armour

    mm2

    G-type is with yellow/green earth conductor and marking on sheath is, for example, 3G1,5Part number for oil resistant SHF2 cable:4 + code from above table 4xxxxx

  • 8/9/2019 Helkama Bica Marine and Offshore Cables (1)

    41/84

    41 0 , 6 / 1 k V

    C A B L E S

    5 / 2 0 1 4

  • 8/9/2019 Helkama Bica Marine and Offshore Cables (1)

    42/84

    Tel. +358 2 410 8700, fax +358 2 237 2428, www.helkamabica.com

    42

    0 , 6 / 1 k V C A B L E S

    5 / 2 0 1 4

    LKAM-FRHFFire-resistant screened powerand control cable 0,6/1kV

    DESIGN: STANDARDS:IEC 60092-353, design

    1. Conductor- stranded copper conductor IEC 60228, class 2- tinned stranded copper conductor on request

    2. Insulation- Mica tape IEC 60092-351- XLPE plastic

    3. Screen- drain wire of tinned copper 1,0mm 2 (in all sizes)- aluminium polyester tape, IEC 60092-350 coverage 100%

    4. Sheath- polyolefine plastic, SHF1, standard colour orange IEC 60092-359- on request thermosetting polyolefine, SHF2, standard colour black - other colours on request

    Application: For fixed installation in most areas and on open deck in ships,especially when lightweight cables are needed.If the cable is exposed to direct sun light protective covering orcable with black outer sheath is recommended.

    Main characteristics

    Rated voltage AC 0,6/1kV (1,2kV)DC 0,9/1,5kV (if voltage to earth does not exceed 0,9kV)

    Maximum conductortemperature + 90 CFlame-retardant IEC 60332-1-2 -test for single insulated wire and cable

    IEC 60332-3-22 -test for bunched wires and cables,category A

    Fire-resistant IEC 60331-1 or IEC 60331-2Halogen-free IEC 60754 seriesSmoke emission IEC 61034 series

    Minimum recommended installation temperature -15 CLowest operation temperature -40 C

    Core identification: see technical information section

    Identification: Lot number, cable type, cable size, voltage, temperature,standards, production month, manufacturer's name and

    meter marking printed on the sheath

    Flame-retardantFire-resistantHalogen-freeLow smokeemissionOil resistant(only SHF2)

  • 8/9/2019 Helkama Bica Marine and Offshore Cables (1)

    43/84

    43 0 , 6 / 1 k V

    C A B L E S

    5 / 2 0 1 4

    LKAM-FRHF 0,6/1kVPart number

    Number ofconductors &cross-section

    n x mm2

    Nominalouter

    diametermm

    Approximateweight kg/km

    CurrentRating Aat +45C

    Min. bendingradius fixedinstallation

    mmNormal G-type28741 2x1,5 9,5 115 20 6028743 28744 3x1,5 10,5 140 16 6028747 28748 4x1,5 11,0 165 16 6528751 28752 5x1,5 12,0 200 13 7528755 7x1,5 13,5 250 12 8028763 12x1,5 17,5 400 10 10528767 14x1,5 18,5 450 10 11028771 16x1,5 19,5 515 9 12028775 19x1,5 20,5 580 9 12528779 24x1,5 24,5 740 8 14528783 27x1,5 25,0 810 8 15028742 2x2,5 10,5 140 26 6528745 28746 3x2,5 11,5 175 21 7028749 28750 4x2,5 12,5 215 21 7528753 28754 5x2,5 13,5 270 17 8028769 14x2,5 20,5 625 13 12528773 16x2,5 22,0 700 12 13028777 19x2,5 23,5 820 11 14028781 24x2,5 27,5 1035 10 16528785 27x2,5 28,0 1140 10 170

    G-type is with yellow/green earth conductor and marking on sheath is, for example, 3G1,5

    Part number for oil resistant SHF2 cable:4 + code from above table 4xxxxx

  • 8/9/2019 Helkama Bica Marine and Offshore Cables (1)

    44/84

    Tel. +358 2 410 8700, fax +358 2 237 2428, www.helkamabica.com

    44

    2 5 0 V C A B L E S

    5 / 2 0 1 4

    LKM-HFUnarmoured control andinstrumentation cable250V

    DESIGN: STANDARDS:IEC 60092-376,design

    1. Conductor- stranded copper conductor IEC 60228, class 2- tinned stranded copper conductor on request

    2. Insulation- XLPE plastic IEC 60092-351

    3. Bedding- separator tape

    4. Sheath- polyolefine plastic, SHF1 EC 60092-359- on request, thermosetting polyolefine, SHF2- standard colour grey, other colours on request

    Application: For fixed installation in most areas and on open deck in ships.If the cable is exposed to direct sun light protective covering orcable with black outer sheath is recommended..

    Main characteristics

    Rated voltage 150/250V (300V)Maximum conductortemperature + 90 CFlame-retardant IEC 60332-1-2 -test for single insulated wire and cable

    IEC 60332-3-22 -test for bunched wires and cables,category A

    Halogen-free IEC 60754 seriesSmoke emission IEC 61034 series

    Minimum recommended installation temperature -15 CLowest operation temperature -40 C

    Core identification: black numbers on white base

    Identification: Lot number, cable type, cable size, voltage, temperature,standards, production month, manufacturer's name andmeter marking printed on the sheath

    Flame-retardant

    Fire-resistantHalogen-freeLow smokeemissionOil resistant(only SHF2)

  • 8/9/2019 Helkama Bica Marine and Offshore Cables (1)

    45/84

    27821 2x0,5 6,0 40 8,7 2527822 3x0,5 6,5 50 7,6 2527823 4x0,5 7,0 60 6,9 3027824 5x0,5 7,5 70 6,4 3027825 7x0,5 8,0 85 5,8 3027826 10x0,5 10,5 125 5,1 4027827 12x0,5 10,5 140 4,8 4527828 14x0,5 11,0 160 4,6 4527829 16x0,5 12,0 175 4,4 4527830 19x0,5 12,5 200 4,1 50

    27831 20x0,5 13,5 220 4,1 5527832 24x0,5 14,5 250 3,8 6027833 27x0,5 15,0 275 3,7 6027834 32x0,5 15,5 310 3,5 6027835 37x0,5 16,5 350 3,3 6526365 2x0,75 6,5 50 11,3 2526366 3x0,75 7,0 60 9,8 3026367 4x0,75 7,5 75 8,9 3026368 5x0,75 8,0 85 8,3 3026369 7x0,75 8,5 110 7,4 3526370 10x0,75 11,0 160 6,6 4526371 12x0,75 11,5 180 6,2 4526372 14x0,75 12,0 200 5,9 5026373 16x0,75 13,0 235 5,6 5026374 19x0,75 13,5 265 5,3 5526375 20x0,75 14,5 285 5,2 6026376 24x0,75 16,0 335 4,9 6526377 27x0,75 16,5 365 4,7 6526378 32x0,75 17,0 415 4,5 6526379 37x0,75 18,0 470 4,3 70

    452

    5 0 V

    C A B L E S

    5 / 2 0 1 4

    LKM-HF 250V

    Part number

    Number ofconductors &cross-section

    n x mm2

    Nominalouter

    diametermm

    Approximateweight kg/km

    CurrentRating Aat +45C

    Min. bendingradius fixedinstallation

    mm

    Other sizes on request.

    Part number for oil resistant SHF2 cable:4 + code from above table 4xxxxx

  • 8/9/2019 Helkama Bica Marine and Offshore Cables (1)

    46/84

    Tel. +358 2 410 8700, fax +358 2 237 2428, www.helkamabica.com

    DESIGN: STANDARDS:IEC 60092-376,design

    1. Conductor- stranded copper conductor IEC 60228, class 2- tinned stranded copper conductor on request

    2. Insulation- XLPE plastic IEC 60092-351

    3. Bedding- separator tape

    4. Armour- drain wire copper (in all sizes)- copper wire braid, coverage > 90% IEC 60092-350- tinned copper wire braid on request

    5. Sheath- polyolefine plastic, SHF1 EC 60092-359- on request, thermosetting polyolefine, SHF2- standard colour grey, other colours on request

    46

    2 5 0 V C A B L E S

    5 / 2 0 1 4

    LKSM-HFArmoured control andinstrumentation cable250V

    Application: For fixed installation in most areas and on open deck in ships.If the cable is exposed to direct sun light protective covering orcable with black outer sheath is recommended.

    Main characteristics

    Rated voltage 150/250V (300V)Maximum conductortemperature + 90 CFlame-retardant IEC 60332-1-2 -test for single insulated wire and cable

    IEC 60332-3-22 -test for bunched wires and cables,category A

    Halogen-free IEC 60754 seriesSmoke emission IEC 61034 seriesOil resistance (only SHF2) IEC 60811-2-1 conditions according to 60092-359/SHF2

    Minimum recommended installation temperature -15 CLowest operation temperature -40 C

    Core identification: black numbers on white base

    Identification: Lot number, cable type, cable size, voltage, temperature,

    standards, production month, manufacturer's name andmeter marking printed on the sheath

    Flame-retardant

    Fire-resistantHalogen-freeLow smokeemissionOil resistant(only SHF2)

  • 8/9/2019 Helkama Bica Marine and Offshore Cables (1)

    47/84

    472

    5 0 V

    C A B L E S

    5 / 2 0 1 4

    LKSM-HF 250V

    Part number

    Number ofconductors &cross-section

    n x mm2

    Nominalouter

    diameter

    mm

    Approximateweight kg/km

    CurrentRating Aat +45C

    Min. bendingradius fixedinstallation

    mm27779 2x0,5 3,1 7,0 80 8,7 4027780 3x0,5 3,1 7,5 85 7,6 4527781 4x0,5 3,1 8,0 95 6,9 4527782 5x0,5 3,2 8,5 110 6,4 5027783 7x0,5 3,5 9,0 125 5,8 5527784 10x0,5 4,6 11,5 180 5,1 7027785 12x0,5 4,8 11,5 195 4,8 7027786 14x0,5 5,1 12,0 215 4,6 7027787 16x0,5 5,5 12,5 235 4,4 7527788 19x0,5 5,8 13,5 265 4,1 8027789 20x0,5 6,1 14,0 285 4,1 8527790 24x0,5 6,8 15,5 325 3,8 90

    27791 27x0,5 6,9 15,5 345 3,7 9527792 32x0,5 9,9 16,5 420 3,5 10027793 37x0,5 10,9 18,0 470 3,3 10526402 2x0,75 3,6 7,5 90 11,3 4526403 3x0,75 3,6 7,5 100 9,8 4526404 4x0,75 3,6 8,5 115 8,9 5026405 5x0,75 4,1 9,5 140 8,3 5526407 7x0,75 4,1 10,0 165 7,4 6026410 10x0,75 5,1 12,5 220 6,6 7526412 12x0,75 5,3 12,5 245 6,2 7526414 14x0,75 5,6 13,0 270 5,9 8026416 16x0,75 6,1 14,0 300 5,6 8526419 19x0,75 6,3 14,5 330 5,3 8526420 20x0,75 11,0 18,0 455 5,2 11026424 24x0,75 11,7 17,0 450 4,9 10026427 27x0,75 11,7 17,5 485 4,7 10526432 32x0,75 11,8 18,0 545 4,5 11026437 37x0,75 11,9 19,5 605 4,3 115

    Cross-section of

    armour

    mm2

    Other sizes on request.

    Part number for oil resistant SHF2 cable:4 + code from above table 4xxxxx

  • 8/9/2019 Helkama Bica Marine and Offshore Cables (1)

    48/84

    Tel. +358 2 410 8700, fax +358 2 237 2428, www.helkamabica.com

    48

    2 5 0 V C A B L E S

    5 / 2 0 1 4

    DESIGN: STANDARDS:IEC 60092-376, design

    1. Conductor- stranded copper conductor IEC 60228, class 2- tinned stranded copper conductor on request

    2. Insulation- XLPE plastic IEC 60092-351

    3. Screen- drain wire of tinned copper- aluminium polyester tape, coverage 100% IEC 60092-350

    4. Sheath- polyolefine plastic, SHF1 EC 60092-359- on request, thermosetting polyolefine, SHF2- standard colour grey, other colours on request

    Application: For fixed installation in most areas and on open deck in ships,

    especially when lightweight cables are needed.If the cable is exposed to direct sun light protective covering orcable with black outer sheath is recommended.

    Main characteristics

    Rated voltage 150/250V (300V)Maximum conductortemperature + 90 CFlame-retardant IEC 60332-1-2 -test for single insulated wire and cable

    IEC 60332-3-22 -test for bunched wires and cables,category A

    Halogen-free IEC 60754 seriesSmoke emission IEC 61034 series

    Minimum recommended installation temperature -15 CLowest operation temperature -40 C

    Core identification: black numbers on white base

    Identification: Lot number, cable type, cable size, voltage, temperature,

    standards, production month, manufacturer's name andmeter marking printed on the sheath

    LKAM-HFScreened control andinstrumentation cable250V

    Flame-retardantFire-resistantHalogen-freeLow smokeemissionOil resistant(only SHF2)

  • 8/9/2019 Helkama Bica Marine and Offshore Cables (1)

    49/84

    492

    5 0 V

    C A B L E S

    5 / 2 0 1 4

    26440 2x0,5 6,0 45 8,7 2526441 3x0,5 6,5 55 7,6 2526442 4x0,5 7,0 65 6,9 3026443 5x0,5 7,5 75 6,4 3026444 7x0,5 8,0 90 5,8 3026445 10x0,5 10,5 130 5,1 4026446 12x0,5 11,0 145 4,8 4526447 14x0,5 11,5 165 4,6 4526448 16x0,5 12,0 180 4,4 4526449 19x0,5 12,5 205 4,1 50

    26450 20x0,5 13,5 225 4,1 5526451 24x0,5 14,5 260 3,8 6026452 27x0,5 15,0 280 3,7 6026453 32x0,5 15,5 325 3,5 6026454 37x0,5 16,5 365 3,3 6526382 2x0,75 6,5 55 11,3 2526383 3x0,75 7,0 65 9,8 3026384 4x0,75 7,5 80 8,9 3026385 5x0,75 8,0 95 8,3 3026386 7x0,75 9,0 120 7,4 3526387 10x0,75 11,5 165 6,6 4526388 12x0,75 12,0 190 6,2 4526389 14x0,75 12,5 215 5,9 5026390 16x0,75 13,0 240 5,6 5026391 19x0,75 13,5 270 5,3 5526392 20x0,75 17,0 345 5,2 7026393 24x0,75 16,0 340 4,9 6526394 27x0,75 16,5 370 4,7 6526395 32x0,75 17,0 430 4,5 7026396 37x0,75 18,5 485 4,3 75

    LKAM-HF 250V

    Part number

    Number ofconductors &cross-section

    n x mm2

    Nominalouter

    diametermm

    Approximateweight kg/km

    CurrentRating Aat +45C

    Min. bendingradius fixedinstallation

    mm

    Other sizes on request.

    Part number for oil resistant SHF2 cable:4 + code from above table 4xxxxx

  • 8/9/2019 Helkama Bica Marine and Offshore Cables (1)

    50/84

    Tel. +358 2 410 8700, fax +358 2 237 2428, www.helkamabica.com

    50

    2 5 0 V C A B L E S

    5 / 2 0 1 4

    DESIGN: STANDARDS:IEC 60092-376, design

    1. Conductor- stranded copper conductor IEC 60228, class 2- tinned stranded copper conductor on request

    2. Insulation- XLPE plastic IEC 60092-351

    3. Twisted pair- two insulated cores twisted together to form a pair See next page for Quad

    4. Bedding- filler tape

    5. Armour- drain wire copper (in all sizes)- copper wire braid, coverage > 94% IEC 60092-350- tinned copper wire braid on request

    6. Sheath- polyolefine plastic, SHF1 EC 60092-359- on request, thermosetting polyolefine, SHF2- standard colour grey, other colours on request

    Armoured instrumentationand communication cable250V

    RFE-HF

    Application: For fixed installation in most areas and on open deck in ships.If the cable is exposed to direct sun light protective covering orcable with black outer sheath is recommended.

    Main characteristicsRated voltage 150/250V (300V)Maximum conductortemperature + 90 CFlame-retardant IEC 60332-1-2 -test for single insulated wire and cable

    IEC 60332-3-22 -test for bunched wires and cables, category A

    Halogen-free IEC 60754 seriesSmoke emission IEC 61034 series

    Oil resistance (only SHF2) IEC 60811-2-1 conditions according to 60092-359/SHF2

    Electrical data:Loop resistance of pair, max. / +20CPair capacitance, nom. / 800HzLoop inductance, nom.Insulation resistance / +20C

    Minimum recommended installation temperature -15 CLowest operation temperature -40 C

    Identification: Lot number, cable type, cable size, voltage, temperature,standards, production month, manufacturer's name andmeter marking printed on the sheath

    0,5mm 2 0,75mm 2 1,5mm 2 Unit80 52 24,4 ohm/km55 50 60 nF/km0,6 0,6 0,7 mH/km

    1500 1500 1500 Mohm/km

    Flame-retardantFire-resistant

    Halogen-freeLow smokeemissionOil resistant(only SHF2)

  • 8/9/2019 Helkama Bica Marine and Offshore Cables (1)

    51/84

    512

    5 0 V

    C A B L E S

    5 / 2 0 1 4

    RFE-HF 250V

    Part number

    Number ofconductors &cross-section

    n x mm2

    Nominalouter

    diametermm

    Approximateweight kg/km

    Min. bendingradius fixedinstallation

    mm20362 1x2x0,5 7,0 85 4520364 2x2x0,5 Quad 8,0 105 5020363 2x2x0,5 10,5 130 6020366 4x2x0,5 11,5 175 7020368 7x2x0,5 14,0 245 8520369 8x2x0,5 14,5 270 8520370 10x2x0,5 17,0 355 10020371 12x2x0,5 17,5 390 10520372 14x2x0,5 18,5 440 11020373 16x2x0,5 19,5 485 12020374 19x2x0,5 21,0 545 12520376 24x2x0,5 23,5 670 14020378 37x2x0,5 28,0 930 17020382 1x2x0,75 7,5 95 4520384 2x2x0,75 Quad 9,0 125 5520383 2x2x0,75 11,0 155 6520386 4x2x0,75 12,5 215 7520388 7x2x0,75 15,5 330 9020389 8x2x0,75 16,0 375 9520390 10x2x0,75 18,5 440 11020391 12x2x0,75 19,0 490 11520392 14x2x0,75 20,5 565 12520393 16x2x0,75 21,5 620 13020394 19x2x0,75 23,5 715 14020396 24x2x0,75 26,0 860 15520398 32x2x0,75 29,5 1100 17520490 1x2x1,5 9,5 135 6020491 2x2x1,5 Quad 11,0 190 6520492 2x2x1,5 14,0 235 8520493 4x2x1,5 17,0 375 10020494 7x2x1,5 20,0 545 12020495 8x2x1,5 21,5 625 13020496 10x2x1,5 24,5 760 14520497 12x2x1,5 25,5 855 15520498 14x2x1,5 27,0 960 16520499 19x2x1,5 31,0 1230 18520500 24x2x1,5 35,0 1530 21020501 32x2x1,5 39,5 1950 235

    Core identification

    Each pair white - blue. Cores numbered 1, 2, 3, 4, 5....(Quad)cable is built up as a star quadwith the following identification1 core white2 core blue3 core white4 core blue

    Part number for oil resistant SHF2 cable:4 + code from above table 4xxxxx

  • 8/9/2019 Helkama Bica Marine and Offshore Cables (1)

    52/84

    Tel. +358 2 410 8700, fax +358 2 237 2428, www.helkamabica.com

    52

    2 5 0 V C A B L E S

    5 / 2 0 1 4

    DESIGN: STANDARDS:IEC 60092-376, design

    1. Conductor- stranded copper conductor IEC 60228, class 2- tinned stranded copper conductor on request

    2. Insulation- XLPE plastic IEC 60092-351

    3. Twisted pair & pair screen- two insulated cores twisted together to form a pair- plastic coated aluminium tape and a tinned copper drain wire

    4. Bedding- filler tape

    5. Armour- drain wire copper (in all sizes)- copper wire braid, coverage > 94% IEC 60092-350- tinned copper wire braid on request

    6. Sheath- polyolefine plastic, SHF1 EC 60092-359- on request, thermosetting polyolefine, SHF2- standard colour grey, other colours on request

    Armoured and pair screenedinstrumentation and communicationcable 250V

    RFE-HF (i)

    Application: For fixed installation in most areas and on open deck in ships.If the cable is exposed to direct sun light protective covering orcable with black outer sheath is recommended.

    Main characteristicsRated voltage 150/250V (300V)Maximum conductortemperature + 90 CFlame-retardant IEC 60332-1-2 -test for single insulated wire and cable

    IEC 60332-3-22 -test for bunched wires and cables, category A

    Halogen-free IEC 60754 seriesSmoke emission IEC 61034 seriesOil resistance (only SHF2) IEC 60811-2-1 conditions according to 60092-359/SHF2

    Electrical data:Loop resistance of pair, max. / +20CPair capacitance, nom. / 800HzLoop inductance, nom.Insulation resistance / +20C

    Minimum recommended installation temperature -15 CLowest operation temperatur


Recommended