High Frequency Grid Impedance Analysis by Current Injection
A. Knop, F.W. Fuchs, Senior Member
Institute of Power Electronics and Electrical Drives,
Christian-Albrechts-University of Kiel, D-24143 Kiel, Germany,
[email protected], [email protected]
Abstract—The impedance of the electrical grid is frequencyand time depending. Therefore it is very useful to know itsvalue in the frequency range between grid fundamental frequencyand frequencies in the kHz-range. The proposed grid impedanceanalysis contributes to optimize energy feed especially fromdecentralized converter equipped renewable sources. This paperpresents an advanced impedance measurement system with ahigh frequency range for the energized electrical low voltagegrid. A sinusoidal current of predetermined frequency is injectedinto the grid. The grid impedance at that frequency is calculatedfrom the measured magnitude and phase of the injected currentand resulting voltage. The measurements are executed at nearbyfrequencies to produce nearly continuous impedance versusfrequency characteristic. The basic concept and a prototype oftest equipment are presented.
I. INTRODUCTION
Within the European Union the amount of regenerative
energy should be increased up to 20% of the total generated
energy by 2020 [1], [2]. Energy from big conventional power
plants which is nearly free of pollution of the electrical grid
will be substituted by more or less perturbated energy of
decentralized producers.
The application of non-linear and asymmetrical loads
or sources increases more and more because of converter
equipped and decentralized difficult controllable renewable
energy sources. The result is the reduction of the power quality
of the grid.
For a grid friendly connection of regenerative energy sys-
tems it is necessary to determine the fed in system perturba-
tions. These system perturbations can be calculated by the
grid impedance of the electric distribution network which
depends on time and frequency and the fed in current including
harmonics. By changing the grid loads this grid impedance
shows high variations over the day or season. Additionally
the load density is locally different. In the city areas the
grid is designed for a higher load density than in rural
areas. Hence the impedance of an electric distribution network
is time dependent and varies locally. Therefore, the same
regenerative systems or regenerative plants at different places
cause different system perturbations.
A simple grid constellation is shown in Fig. 1. This consists
of different low-voltage loads like for example domestic and
industrial loads and decentralized energy producers as for
example wind turbine generators. These are connected with
distributed low-voltage transformers at medium voltage level.
At the point of common coupling (PCC) on the medium
voltage level side the line voltage is influenced by other loads
low voltage medium voltage
Wind turbinef =2kHzR
lin. load
VARf =R 0,5...5kHz
Wind turbinef =1.7kHzR
nonlin. loadf =4kHzR
FACTSf =0,5...5kHzR
high voltage
lin. load
PCC
Fig. 1. Exemplary grid with domestic and industrial user and decentralizedenergy producers
in dependence of grid impedance. A estimation of the power
system impedance could be made by using the short circuit
power associated with the point of connection [3]. If wiring
diagrams are available, a more accurate evaluation may be
carried out. However, knowledge of the loads connected at
remote points will be unavailable and affects the accuracy.
Online measurement is the only practical solution as it requires
no a priori knowledge because of the grid and no connected
loads.
The proposed concept offers the accurate calculation of
system perturbation at the switching frequency.
By repeated measurement over time significant changes
in impedance may also be traced [4]. This yields to better
performance and improved power quality. The system becomes
more grid-friendly by taking into account of the system
perturbations in the control such as changing the switching
frequency. Hence maybe more decentralized energy production
units (wind turbine generators as well as the sun and biomass
plants) can be connected to the grid, i.e. a higher number of
decentralized energy production units can be connected to the
grid.
Furthermore changes in the grid impedance can lead to
performance degradation or even trigger system stability prob-
lems in LCL-based grid converter systems or when harmonics
compensators are employed [5], [6]. Information about the
actual grid impedance could be used for making the controller
adaptive in order to avoid these problems.
This paper describes an impedance measurement system
with a converter injecting a high frequency sinusoidal current
(with an amplitude up to 20 A) into the grid for measuring
the frequency dependent grid impedance in a frequency range
TABLE IOVERVIEW OF GRID IMPEDANCE MEASUREMENT METHODS
Methods passive resonance transient periodical distortions multi frequent
(switch a load) (LCL-Filter) (inrush C and L) (impulse / rectangle) current
Measuring time medium low low low high
Reproducibility always always none always always
Frequency selectivity none none none middle yes
Frequency resolution only harmonics only res. frequ. middle middle high
Online measuring none none none yes yes
Measurable impedance |Z| |Z| |Z(f)|,6 Z(f) |Z(f)|,6 Z(f) |Z(f)|,6 Z(f)
from 75 Hz to 10 kHz and the instrumentation for measuring
line impedance.
The measurement takes place without disrupting normal
system operation. Measurement results are visualized with a
diagram of impedance magnitude and phase depending on
frequency for frequencies between 75 Hz and 10 kHz. The
operation of the instrumentation is verified and illustrated by
exemplary measurements.
This paper is structured as follows: Chapter II comprises the
method of grid impedance measurement; Chapter III describes
the instrumentation of the measurement system and finally
Chapter IV presents measurement results.
II. METHODS OF GRID IMPEDANCE MEASUREMENT -
STATE OF THE ART
Measurement of non-fundamental frequency impedance of
energized power systems has a long history [7], [8]. Primarily,
all kinds of measurement methods differ in the origin of the
non-fundamental frequency signals used for measurement, i.e.
they differ in the measurement frequency band and associated
frequency resolution.
Passive measurement methods use non fundamental fre-
quency signals which are already presented in the literature.
A method derives the impedance at the fundamental and
harmonic frequencies by measuring the line-voltage magnitude
and phase before and after applying a known load in steady-
state [9], [10].
Another possibility is using the excitation of the LCL-filter
resonance in steady state to estimate the grid impedance [11].
This method is for employing the frequency characteristic of
the current-controlled converter in order to have an indication
of the grid impedance value. In fact, the frequency peak
due to the resonance is particularly sensitive to the grid
impedance change. This method can only be measured at the
grid impedance at the resonance frequency. Furthermore, the
system model has to be known exactly.
In [12] one method using transients to estimate line
impedance by spectral estimation is introduced. These tran-
sients can be generated by capacitor switching, transformer
inrush and line energization and de-energization. One draw-
back of this method is that these transients may not sufficiently
excite the line impedance at all necessary frequencies.
Another steady state method injects well known and typi-
cally periodically distortion currents into the grid and allows
an analysis in steady state. This technique is presented in
[13]–[16]. The basic idea is injecting a rectangular waveform
current into the grid and recording the voltage change re-
sponse. Results are processed by means of a Fourier analyses
at the particular injected harmonic. This technique can be
used to obtain the frequency characteristic of the grid if
the measurement is repeated at different nearby frequencies.
The grid-connected converter of the given system can be
used for injecting the disturbance [17]: a harmonic voltage
is injected by the converter and the following current is
analyzed. Hence, the impedance can be calculated as the ratio
between the voltage disturbance and the measured current. The
measured grid impedance is correctly at the frequency with
enough current and following voltage. These methods can fail
when many grid-connected converters are injecting disturbing
signals at the same time.
Another possibility to determine grid impedance can be
reached by injecting a signal at non characteristic frequencies
[7], [8], [18]. Therefore a multi frequent current source (syn-
chronous generator, converter or equivalent) injects a current
into the grid. With the resultant voltage in the same frequency
range it is possible to determine the magnitude and phase
of the frequency dependent impedance. The advantage of
this method is the measurement and calculation of the grid
impedance separately at each frequency. Furthermore, it is
possible to perform measurements with the same current or
the same voltage. When a high no fundamental voltage in the
grid is present, it is possible by two different measurement
currents to compensate this voltage. By variable selection of
the measuring current, it is possible to adapt to any grid
condition. For example high grid impedance required a low
current.
Finally, the measured response of an injected white noise
signal can be used with spectral estimation to obtain the line
impedance magnitude without phase [7], [19].
The advantages and disadvantages of the methods are sum-
marized in Tab. I.
III. DEVELOPED MEASUREMENT SYSTEM
The measurement method selected in this paper uses a three-
phase grid connected voltage source converter to generate
measurement currents with a variable measurement frequency
range from 75 Hz to 10 kHz. Thus, this is the underlying
Dead-time
3-phasehysterese-control
AD-Converter
+
+φgrid
PI
-
PLL
|I |supply
*
AD-Converter
VD,ref
+
3
3
3cos( )φ
φφ
cos( -120°)cos( -240°)
VD
1/s
φmeas
|I |*
meas FPGA-Controller
3
ΔIωmeas
3
6
LFilter LGrid v (t)Grida
b
c
N
cos( )φφφ
cos( -120°)cos( -240°)
Hardware
GridFilter/Transformer iact
LTransformer
iact,dig
Converter
Fig. 2. Power and control configuration of the high frequency measurement current generator; control implemented in a FPGA
principle for measuring the impedance versus frequency char-
acteristic of the grid. The selected method injects a signal at
non characteristic frequencies, multifrequent current according
to Tab. I. Compared, to earlier publications, the approach
introduced in this paper uses a grid connected converter creates
the measurement current. The measurement system is designed
for measuring the impedance of a 400 V grid and consists of
a fast switching converter, a control unit and a measurement
equipment.
A. Grid Connected Converter for Current Injection
Fig. 2 illustrates the proposed structure of the controlled
converter for measurement current injection - a three-phase
two-level voltage source converter (VSC) which is connected
via inductors and one transformer to the grid. The control of
the converter provides two basic functions. First, it controls
the DC-link voltage VD to be constant at 800 V. The second
function of the control is to regulate accurately the currents
to be injected in the inductors tracking their reference values.
In this way, the converter operates effectively as a controlled
current source and can inject currents into the grid. The current
control method used for the converter is for each phase a
sampled single phase hysteresis control. The control structure
is described in [20]. The control structure leads to a very
accurate control of the injected high frequency current. The
Phase-locked loop (PLL) for calculation the grid angle is very
robust against the injected measurement current. The control
calculations are performed by a field programmable gate array
(FPGA). Tab. II describes the specifications of the converter.
For the high frequency current (up to 10 kHz) a special
three-phase transformer and three-phase inductor are designed
and produced. These consist of several split tape-wound cores
to reduce the iron losses and flex wire to reduce the skin-effect.
These specific designs allow the operating at a frequency from
TABLE IICONVERTER SPECIFICATIONS
DC-Link voltage 800 V
Filter inductance LFilter = 1 mH
Grid voltage VGrid = 230 V
Transoformer ratio 1:1.7
Grid inductance LGrid = 0.4 mH
Rated power P = 10 kVA
Output frequency 50 Hz − 10 kHz
Switching frequency 30 kHz − 60 kHz
50 Hz to 10 kHz with acceptable iron losses. The transformer
and filter inductors designed for a power rating of 15 kVA.
For this application the converter IGBTs have been selected
with fast switching characteristics. To reduce the recovery cur-
rent from the diodes, SiC-Diodes are used in the freewheeling
path. The power semiconductors have a breakdown voltage
of 1200 V. By this configuration the converter can be used
with fast switching frequency, here up to 50 kHz, and reduced
switching losses [21].
In Fig. 3 the prototype of the high frequency measurement
current generator is shown.
B. Grid Impedance Measurement Method
The measured current iact and voltage vact waveforms are
transferred to AD converters which sample the waveforms. A
micro-controller performs a single frequency discrete Fourier
transform (DFT) with a Blackman window to find the real and
imaginary components of current iact and voltage vact at mea-
surement frequency fmeas [22]. With this components the line
impedance Z(fmeas) and associated magnitude |Z(fmeas)|and phase 6 Z(fmeas) at the measurement frequency fmeas
Converter with FPGA
transformer
inductor
Fig. 3. Prototype of the high frequency measurement current generator -converter, filter inductance and transformer
V
AD AD
DFT|i|i
DFT|v|
v
|Z(f )|meas
Z(f )meas
fmeas Imeas
controlunit
meas. current gen.L1
L2
L3
N
i ( )tact v ( )tact
grid withnon-linear
loads
Fig. 4. Setup for the grid impedance measurement
are calculated as
|Z(fmeas)| =|v(fmeas)||i(fmeas)|
(1)
6 Z(fmeas) = 6 v(fmeas) − 6 i(fmeas). (2)
The measurement is repeated at all frequencies in range of
interest to a complete characterization of the line impedance
as a function of frequency.
When the measurement frequency fmeas is close to the
harmonics from the 50 Hz fundamental the large grid voltage
superposes the component vmeas of the results from injecting
current imeas. To avoid this problem the harmonic frequency
values are calculated by linear interpolation by the nearby
valid measurements at ±5 Hz. The setup of the grid impedance
measurement is shown in Fig. 4.
C. Measurement setup
The measurement setup is summarized in Fig. 4. The
measurement connection is directly on the power connector.
The line voltages are measured by using voltage transform-
ers with a quoted bandwidth of 40 MHz, the accuracy is 1 %.
The line current is measured using hall effect devices with a
quoted bandwidth of 200 kHz, the accuracy is 1 %.
100 200 300 400 500 600 700 800 900 1000
1
2
3
4
|Z| (Ω
)
100 200 300 400 500 600 700 800 900 10000
50
100
∠ Z
( °
)
100 200 300 400 500 600 700 800 900 10000
0.5
1
L (
mH
)
100 200 300 400 500 600 700 800 900 10000
0.5
1
R (
Ω)
f (Hz)
0.0 mH 0.5 mH 0.2 mH
Fig. 5. Grid impedance with different inductors in series to the grid
The AD conversion is done with a maximum sample rate
of 500 kHz and an accuracy of 16 bit. The sample time is 10
periods of the measurement frequency fmeas.
IV. MEASUREMENT RESULTS
The grid impedance measurement setup, as shown in Fig. 4,
and the high frequency measurement current generator of Fig.
3 are used to a exemplary characterization of the impedance
of a 400 V three-phase electric power system located in
the institute of the authors. The institute has two medium
voltage transformer each with a power rating of 500 kVA.
Unfortunately, the transformer was inaccessible and no other
nameplate data were obtained.
To test the measurement, additionally the impedance char-
acteristics for various circuit components were determined by
the grid impedance analyzer.
A. Method Verification
The measurement method verified in experiments, whereas
many ”test supply impedance” configurations were used. Cir-
cuits which illustrate typical results are presented in this paper.
Further several experiments were performed to verify the
quality of the impedance measurement. These are explained
in the following.
In the first experiment, serial inductors with given values
were added to the line output. The measured impedance and
the calculated resistance and inductance for different inductors
are given in Fig. 5. In this case the grid with the inductors is
simplified as a series circuit of inductance and resistance. The
resistance and inductance are simplified calculated as
R = |Z| · cos6 Z (3)
L =1
2π · fmeas
|Z| · sin6 Z. (4)
According to expectations, the measured inductance varied
with the connected inductance. The resistance increasing with
frequency illustrates the iron losses of the serial inductors.
TABLE IIITEST WITH TWO SERIAL HARMONIC FILTERS
calculated measured
shunt 1 (0.50 mH, 16 µF) 1.454 kHz 1.4 kHz
shunt 2 (5.58 mH, 240 nF) 4.35 kHz 4.3 kHz
Next, two harmonic shunt filters (series-resonant circuit)
have been connected in series to the grid, close to the grid
impedance analyzer. These resonant frequencies are calculated
by
fR =1
2π
1√L · C
. (5)
The first harmonic filter (L = 0.5 mH, C = 16µF) has a
resonance frequency at fR1 = 1454 Hz and the second filter
(L = 5.58 mH, C = 240 nF) has a resonance frequency
at fR2 = 4350 Hz. The filter resonant peaks appear in the
grid impedance at the calculated frequency (Fig. 6). With the
measurement there exists a relatively good correspondence
between the calculated and measured data (Tab. III).
1 2 3 4 5 6 7 8 9 10
0.4
0.6
0.8
1
1.2
1.4
1.6
|Z| (Ω
)
1 2 3 4 5 6 7 8 9 100
10
20
30
40
50
60
∠ Z
( °
)
f (kHz)
with Filter without Filter
fR2
=4.3 kHz
fR1
=1.4 kHz
Fig. 6. Grid impedance with and without two serial harmonic filters (fR1 =1454 Hz, fR2 = 4350 Hz)
1 2 3 4 5 6 7 8 9 100
2
4
V (
V)
1 2 3 4 5 6 7 8 9 100
5
10
I (A
)
1 2 3 4 5 6 7 8 9 100
1
2
|Z| (Ω
)
1 2 3 4 5 6 7 8 9 100
20
40
∠ Z
( °
)
f (kHz)
Fig. 7. Grid impedance with different injected currents
In Fig. 7 measurements at the same connection point nearly
at the same time with different injected currents is presented.
It is shown that the results are almost independent from the
injected current.
B. Measured Grid Impedance
Fig. 8 shows the measured grid impedance of the institute,
the magnitude and the phase angle for a frequency range from
75 Hz to 10 kHz. The measurements are taken at different
days and times. At a frequency of nearly 3 kHz a resonance
is detected. As expected, the characteristics have no linear
dependency on the frequency. In these measurements it’s
clearly shown that, in many cases, the R-L model of the grid
is inadequate because the effective values of R and L depend
on frequency because of other components (C-compensators)
are part of the grid.
Finally in Fig. 9 the measurement results are presented of
the various grid impedance magnitudes over a 10-hour period.
This figure shows the fluctuations of the grid impedance over
a time.
1 2 3 4 5 6 7 8 9 10
0.5
1
1.5
|Z| (Ω
)
1 2 3 4 5 6 7 8 9 100
20
40
60
∠ Z
( °
)
1 2 3 4 5 6 7 8 9 100
0.05
0.1
L (
mH
)
1 2 3 4 5 6 7 8 9 100
0.5
1
R (
Ω)
f (kHz)
Fig. 8. Measured grid impedance with magnitude and phase at different days
09:00
12:00
18:00 1005.000
10.000
0,5
1
1,5
2
f (Hz)time
Z (
Ω)
Fig. 9. Measured grid impedance at different times within 10 hours
V. CONCLUSION
A practical and non-disruptive technique and prototype sys-
tem for measuring grid impedance as a function of frequency
for an energized low voltage grid in normal operation is
presented and evaluated.
Function and accuracy of the applied method are evaluated.
A sinusoidal current of predetermined frequency is injected
into the grid, and the grid impedance at that frequency is
calculated from the measured magnitude and phase of the
injected current and resulting voltage. The measurements are
executed at ascending nearby frequencies to produce nearly
continuous impedance versus frequency characteristic.
This complete characterization of power system impedance
for a wide frequency range provides valuable data for power
quality calculations.
The measured grid impedance provides accurate data as a
starting point for many power system calculations. This offers
the possibility to optimize the power of decentralized energy
production units that can be fed to the grid.
ACKNOWLEDGMENT
This work has been funded by the Innovation Fond of
the state Schleswig-Holstein (Germany). This work has been
carried out in the frame of CEwind (competence center for
wind energy of universities of Schleswig-Holstein) together
with Prof. Hinrichs, University of Applied Science, Kiel.
REFERENCES
[1] S. Gabriel, “Roadmap Energiepolitik 2020,” Bundesministerium fuerUmwelt Naturschutz und Reaktorsicherheit, 2009.
[2] European Union, “EU-spring summit,” 2007.
[3] Z. P. Fang, “Application issues of active power filters,” IEEE Industry
Applications Magazine, vol. 4, no. 5, pp. 21–30, 1998.
[4] Z. Staroszczyk, “Accuracy problems in on-line one-phase distribu-tion/load system identification task,” in Proceedings of the IEEE In-
ternational Symposium on Industrial Electronics, 1996.
[5] M. Liserre, R. Teodorescu, and F. Blaabjerg, “Stability of photovoltaicand wind turbine grid-connected inverters for a large set of gridimpedance values,” IEEE Transactions on Power Electronics, vol. 21,no. 1, pp. 263–272, 2006.
[6] J. Dannehl, F. W. Fuchs, and S. Hansen, “PWM rectifier with LCL-filterusing different current control structures,” in European Conference on
Power Electronics and Applications, 2007.
[7] M. B. Hughes, R. W. Leonard, and T. G. Martinich, “Measurement ofpower system subsynchronous driving point impedance and comparisonwith computer simulations,” IEEE Transactions on Power Apparatus and
Systems, vol. PAS-103, no. 3, pp. 619–630, 1984.
[8] B. L. Agrawal, J. A. Demcko, R. G. Farmer, and D. A. Selin, “Apparentimpedance measuring systems (aims),” IEEE Transactions on Power
Electronics, vol. 4, no. 2, pp. 575–585, 1989.
[9] R. M. Vines, H. J. Trussell, K. C. Shuey, and J. B. O’Neal, “Impedanceof the residential power-distribution circuit,” IEEE Transactions on
Electromagnetic Compatibility, vol. EMC-27, no. 1, pp. 6–12, 1985.
[10] L. S. Czarnecki and Z. Staroszczyk, “On-line measurement of equivalentparameters for harmonic frequencies of a power distribution system andload,” IEEE Transactions on Instrumentation and Measurement, vol. 45,no. 2, pp. 467–472, 1996.
[11] M. Liserre, F. Blaabjerg, and R. Teodorescu, “Grid impedance estimationvia excitation of LCL-filter resonance,” IEEE Transactions on Industry
Applications, vol. 43, no. 5, pp. 1401–1407, 2007.
[12] M. M. Forti and L. M. Millanta, “Power-line impedance and theorigin of the low-frequency oscillatory transients,” IEEE Transactions
on Electromagnetic Compatibility, vol. 32, no. 2, pp. 87–97, 1990.
[13] L. Asiminoaei, R. Teodorescu, F. Blaabjerg, and U. Borup, “A digitalcontrolled PV-inverter with grid impedance estimation for ENS detec-tion,” IEEE Transactions on Power Electronics, vol. 20, no. 6, pp. 1480–1490, 2005.
[14] M. Sumner, B. Palethorpe, and D. W. P. Thomas, “Impedance measure-ment for improved power quality-part 1: the measurement technique,”IEEE Transactions on Power Delivery, vol. 19, no. 3, pp. 1442–1448,2004.
[15] ——, “Impedance measurement for improved power quality-part 2:a new technique for stand-alone active shunt filter control,” IEEE
Transactions on Power Delivery, vol. 19, no. 3, pp. 1457–1463, 2004.[16] Z. Staroszczyk, “A method for real-time, wide-band identification of the
source impedance in power systems,” IEEE Transactions on Instrumen-
tation and Measurement, vol. 54, no. 1, pp. 377–385, 2005.[17] A. V. Timbus, R. Teodorescu, F. Blaabjerg, and U. Borup, “Online
grid measurement and ENS detection for PV inverter running on highlyinductive grid,” IEEE Power Electronics Letters, vol. 2, no. 3, pp. 77–82,2004.
[18] J. P. Rhode, A. W. Kelley, and M. E. Baran, “Complete characterizationof utilization-voltage power system impedance using wideband measure-ment,” IEEE Transactions on Industry Applications, vol. 33, no. 6, pp.1472–1479, 1997.
[19] E. Handschin, W. Horenkamp, T. Wiesner, and E. Stachorra, “Thespectral grid impedance of distribution networks as a key term analysis,”in PCIM, 2001.
[20] A. Knop and F. W. Fuchs, “High frequency grid impedance analysiswith three-phase converter and FPGA based tolerance band controller,”in CPE, 2009.
[21] A. Knop, W. T. Franke, and F. W. Fuchs, “Switching and conductingperformance of SiC-JFET and ESBT against MOSFET and IGBT,” in13th Power Electronics and Motion Control Conference, 2008.
[22] F. J. Harris, “On the use of windows for harmonic analysis with thediscrete fourier transform,” Proceedings of the IEEE, vol. 66, no. 1, pp.51–83, 1978.