+ All Categories
Home > Documents > Hilti Firestop Specification Binder CP 651N trays and inside cable trunking PVC pipes up to 50mm...

Hilti Firestop Specification Binder CP 651N trays and inside cable trunking PVC pipes up to 50mm...

Date post: 20-Jun-2018
Category:
Upload: lamdan
View: 219 times
Download: 0 times
Share this document with a friend
13
Data Sheet Hilti (Gt. Britain) Limited, 1 Trafford Wharf Road, Trafford Park, Manchester M17 1BY Telephone: 0800 886 100 HILTI CP 651N Firestop Cushion The enclosed pages are taken from the Hilti Firestop Systems Manual Edition April 2011 Supported by additional standard details For Material Safety data sheets visit the technical library at www.hilti.co.uk/cfs Hilti (Gt Britain) Ltd TECHNICAL ADVISORY SERVICE TELEPHONE 0161 886 1144 Quality Management System Certification Standard: ISO 9001:2008 Issued by: The Swiss Association for Quality and Management Systems SQS. Registration No: 12455 (The current certificate can be downloaded from www.hilti.co.uk) Field of activity: Market Organisation. Note: The certificate of Hilti (Gt. Britain) Ltd. is a sub-certificate to the master certificate of Hilti Aktiengesellschaft,FL-9494 Schaan with the field of activity: Research, Development, Manufacturing, Sales and Service.
Transcript
Page 1: Hilti Firestop Specification Binder CP 651N trays and inside cable trunking PVC pipes up to 50mm Ordering Order description Package Contents Dimensions (LxWxH) Package Quantity Item

Data Sheet

Hilti (Gt. Britain) Limited,

1 Trafford Wharf Road, Trafford Park, Manchester M17 1BY

Telephone:

0800 886 100

HILTI CP 651N Firestop Cushion

The enclosed pages are taken from the Hilti Firestop Systems Manual

Edition April 2011 Supported by additional standard details

For Material Safety data sheets visit the technical library at www.hilti.co.uk/cfs

Hilti (Gt Britain) Ltd

TECHNICAL ADVISORY SERVICE TELEPHONE 0161 886 1144

Quality Management System Certification Standard: ISO 9001:2008 Issued by: The Swiss Association for Quality and Management Systems SQS. Registration No: 12455 (The current certificate can be downloaded from www.hilti.co.uk) Field of activity: Market Organisation. Note: The certificate of Hilti (Gt. Britain) Ltd. is a sub-certificate to the master certificate of Hilti Aktiengesellschaft,FL-9494 Schaan with the field of activity: Research, Development, Manufacturing, Sales and Service.

Page 2: Hilti Firestop Specification Binder CP 651N trays and inside cable trunking PVC pipes up to 50mm Ordering Order description Package Contents Dimensions (LxWxH) Package Quantity Item

Data Sheet

Hilti (Gt. Britain) Limited,

1 Trafford Wharf Road, Trafford Park, Manchester M17 1BY

Telephone:

0800 886 100

Don’t just use Hilti Firestop Products, use our Hilti Accredited Firestop Contractors

It is the combination of a quality conscious and third party accredited manufacturer working in close co-operation with a selected group of third party accredited installers that can offer you the best value.

Here are some of the benefits available to you by using this co-operation:-

Reduce your liability; liability that comes from poor or incorrect installation and performance of products.

Efficient Project Management based on the co-operation of a specialised manufacturer with a specialist contractor

Commercially designed, effective Fire Protection solutions

Products that adhere to 3rd

party product conformity schemes such as FM, UL

and Certifire.

These approvals are an assurance of product and manufacturer quality, they

can also have an influence on the building insurance premium reducing the

service costs of the building. Solutions that have been tested for long term performance. Solutions that offer business continuity and protections of premises. Certification of conformity of work completed. Installation work audited by FIRAS on site to ensure compliance with

manufacturers’ recommendations and Building regulations. Installer with site based manufacturer support. Installer having available site based manufacturers support when needed. Clear and comprehensive documentation of installation. Comprehensive support documentation for proposed solutions. Clarity and assistance understanding the role of Passive Fire measures in

modern building construction.

Product Accreditation Hilti Firestop Systems have been certified by a wide variety of international bodies, such as FM, UL, Certifire and iBMB As part of this process products are monitored on an on-going basis so you can have absolute confidence in the quality and standard of the product you are specifying.

Installation Accreditation Hilti-Accredited Firestop Contractors are also third party certified (e.g. FIRAS or LPCB). This means that they work to agreed industry standards, employ trained operatives and are subject to on-site audits and inspection of representative samples of the work carried out to ensure compliance with manufacturers’ recommendations and Building Regulations

Further details about Hilti accredited Firestop Contractors and the support that we can offer you can be obtained by telephoning Freephone 0800 083 8889 (GB only).

Association for Specialist Fire Protection Hilti is proud to support and be a member of The Association for Specialist Fire Protection (ASFP) ASFP Vision To offer the industry it serves with: Knowledge / guidance on all aspects of ‘built-in’ fire protection Technical support / impartial advice Direction through industry authority

AGE TESTED

Page 3: Hilti Firestop Specification Binder CP 651N trays and inside cable trunking PVC pipes up to 50mm Ordering Order description Package Contents Dimensions (LxWxH) Package Quantity Item

CP 651N

Hilti (Gt. Britain) Limited,

1 Trafford Wharf Road, Trafford Park, Manchester M17 1BY

Telephone:

0800 886 100

AGE TESTED

Contents Hilti Firestop Systems Manual Pages for Hilti CP 651N FS 011 - 02 Hilti CP 651N Metal Trunking – Solid wall – Drywall – (Pillows) FS 066 - 01 Hilti CP 651N Plastic Pipe – Cables - Solidwall 30 YEARS

Data summary Additional Properties of CP 651N seals Data summary CP 651N - Firestop Cushion – BREEAM Criteria summary Data summary CP 651N - Firestop Cushion - NBS specification clauses 30 YEARS

Material Safety Data Sheets and CAD files of the standard details FS ***-** can be downloaded from the technical library at www.hilti.co.uk/cfs Revision History May 2011 First release July 2011 Data summaries added, inappropriate standard details removed. May 2013 Update

Page 4: Hilti Firestop Specification Binder CP 651N trays and inside cable trunking PVC pipes up to 50mm Ordering Order description Package Contents Dimensions (LxWxH) Package Quantity Item

Hilti Firestop Systems Hilti Firestop Systems

Firestop cushion CP 651 N

Applications Applications for permanent of temporary seal in fl oors and walls Installations where frequent changes may be required Dust free applications in switch or computer rooms Cable trays and inside cable trunking PVC pipes up to 50mm

OrderingOrder description Package Contents Dimensions (LxWxH) Package Quantity Item numberFirestop cushion CP 651 N-L

6 x CP 651N fi restop pillow (large)

300 x 170 x 30 mm 6 pc 00382626

Firestop cushion CP 651 N-M

15 x CP 651N fi restop pillow (medium)

300 x 80 x 30 mm 15 pc 00382625

Firestop cushion CP 651 N-S

30 x CP 651N fi restop pillow (small)

300 x 40 x 30 mm 30 pc 00382624

Technical dataCP 651 N

Fire rating Up to 4 hoursBase materials Concrete, Masonry, DrywallDensity ~0.35 g/cm³Colour WhiteAcoustics performance Up to 58db

Ready-to-use fi restop intumescent cushion

Advantages Excellent for laying new cables Tear-resistant and dust-free pillows for dust-free rooms Easy installation without use of a special tool Re-usable, economical in use A fl exible system (temporary or permanent fi restop) Also for use in drywall Uneff ected by water or mild frost

EN1366-3

Technical Information

Installation instructions for CP 651 NNotice • Before handling, read Material Safety Data Sheet and

product label for safe usage and health information.

Opening1. Clean the opening. Cables and cable supporting structures must be installed and fastened in compliance with standards.2. Cushion arrangement without cables running through wall partition.3. Cushion arrangement with cables running through wall partition.

4. For floor openings fasten wire mesh in placewhen closing the opening.5. Cushion arrangement in floor. Seal gaps between cables and CP651 N with CP606 if required (please refer to approval).6. Wrap cable/ cable tray resp. pipes running through opening with CP651 N-L if required (please refer to approval).7. Fasten identification plate in pace (if required).

The following points when installing the cushions:• Insert the first layer of CP 651 N underneath the

cables if possible.• Overlap (> 20 mm)• Shift next layer 1/2 width of cushion (stretcher bond).• Seal off the opening with CP651 N tightly.• If cable penetration must carry permanent

identification mark in the form of an installation plate. Enter the appropriate details on the installation plate and mount it in a visible position beside the cable penetration.

Inspection• Check that the cushions have been installed

in compliance with regulations.

The following dimensions must be observed when installing fi restop cushions:

Size Wall FloorMax. opening size

Width x Height

1200x1500mm 700mm x unlimited

Min. building component thickness

100 mm 150 mm

Min. distance of cable run from opening

40 mm 40 mm

Min. distance between cable trays (horizontal)

0 mm 0 mm

Min. distance between cable trays (vertical)

80 mm 80 mm

Min. distance between openings

200 mm 200 mm

Max. cable loading (as % of opening size)

60 % 60 %

For more standard details and technical information register online at the Hilti Firestop Design Centre at www.hilti.co.uk/cfs

Page 5: Hilti Firestop Specification Binder CP 651N trays and inside cable trunking PVC pipes up to 50mm Ordering Order description Package Contents Dimensions (LxWxH) Package Quantity Item

Hilti Firestop Systems Hilti Firestop Systems

Firestop cushion CP 651 N

Applications Applications for permanent of temporary seal in fl oors and walls Installations where frequent changes may be required Dust free applications in switch or computer rooms Cable trays and inside cable trunking PVC pipes up to 50mm

OrderingOrder description Package Contents Dimensions (LxWxH) Package Quantity Item numberFirestop cushion CP 651 N-L

6 x CP 651N fi restop pillow (large)

300 x 170 x 30 mm 6 pc 00382626

Firestop cushion CP 651 N-M

15 x CP 651N fi restop pillow (medium)

300 x 80 x 30 mm 15 pc 00382625

Firestop cushion CP 651 N-S

30 x CP 651N fi restop pillow (small)

300 x 40 x 30 mm 30 pc 00382624

Technical dataCP 651 N

Fire rating Up to 4 hoursBase materials Concrete, Masonry, DrywallDensity ~0.35 g/cm³Colour WhiteAcoustics performance Up to 58db

Ready-to-use fi restop intumescent cushion

Advantages Excellent for laying new cables Tear-resistant and dust-free pillows for dust-free rooms Easy installation without use of a special tool Re-usable, economical in use A fl exible system (temporary or permanent fi restop) Also for use in drywall Uneff ected by water or mild frost

EN1366-3

Technical Information

Installation instructions for CP 651 NNotice • Before handling, read Material Safety Data Sheet and

product label for safe usage and health information.

Opening1. Clean the opening. Cables and cable supporting structures must be installed and fastened in compliance with standards.2. Cushion arrangement without cables running through wall partition.3. Cushion arrangement with cables running through wall partition.

4. For floor openings fasten wire mesh in placewhen closing the opening.5. Cushion arrangement in floor. Seal gaps between cables and CP651 N with CP606 if required (please refer to approval).6. Wrap cable/ cable tray resp. pipes running through opening with CP651 N-L if required (please refer to approval).7. Fasten identification plate in pace (if required).

The following points when installing the cushions:• Insert the first layer of CP 651 N underneath the

cables if possible.• Overlap (> 20 mm)• Shift next layer 1/2 width of cushion (stretcher bond).• Seal off the opening with CP651 N tightly.• If cable penetration must carry permanent

identification mark in the form of an installation plate. Enter the appropriate details on the installation plate and mount it in a visible position beside the cable penetration.

Inspection• Check that the cushions have been installed

in compliance with regulations.

The following dimensions must be observed when installing fi restop cushions:

Size Wall FloorMax. opening size

Width x Height

1200x1500mm 700mm x unlimited

Min. building component thickness

100 mm 150 mm

Min. distance of cable run from opening

40 mm 40 mm

Min. distance between cable trays (horizontal)

0 mm 0 mm

Min. distance between cable trays (vertical)

80 mm 80 mm

Min. distance between openings

200 mm 200 mm

Max. cable loading (as % of opening size)

60 % 60 %

For more standard details and technical information register online at the Hilti Firestop Design Centre at www.hilti.co.uk/cfs

Page 6: Hilti Firestop Specification Binder CP 651N trays and inside cable trunking PVC pipes up to 50mm Ordering Order description Package Contents Dimensions (LxWxH) Package Quantity Item

Hilti Firestop Systems Hilti Firestop Systems

Opening (m2 %01 daol elbaC%0 daol elbaC)0.01 0 1 4 – – –0.02 3 2 3 3 2 20.04 6 2 1 5 2 10.05 8 2 2 8 2 10.1 16 4 2 18 3 20.2 32 7 3 31 6 30.4 65 15 6 63 13 60.5 80 19 8 76 16 70.6 96 23 9 90 20 80.8 128 29 11 118 26 101.0 160 36 13 148 32 121.2 182 47 15 169 39 131.4 215 54 16 201 48 151.6 257 61 18 232 55 161.8 298 68 21 278 61 19Cushion CP 651N-L CP 651N-M CP 651N-S CP 651N-L CP 651N-M CP 651N-S

Consumption guide

Wall assembly

Cable penetrations through walls covering all cable diameters

Opening (m2 %06 daol elbaC%03 daol elbaC)0.01 – – – – – –0.02 – – – – – –0.04 5 2 1 – – –0.05 7 4 1 – – –0.1 15 3 2 12 4 20.2 23 6 3 20 5 30.4 51 14 5 36 9 40.5 64 13 5 40 11 40.6 74 16 7 52 12 60.8 92 20 8 66 13 61.0 119 25 10 78 18 81.2 136 31 11 86 24 91.4 164 38 12 109 31 101.6 189 43 12 120 36 101.8 218 48 15 136 41 12Cushion CP 651N-L CP 651N-M CP 651N-S CP 651N-L CP 651N-M CP 651N-S

Cable penetrations through walls with cable diameters ≤ 16 mmOpening (m2 %01 daol elbaC%0 daol elbaC)0.01 0 1 4 – – –0.02 3 2 3 3 2 20.04 6 2 1 5 2 10.05 8 2 2 8 2 10.1 16 4 2 17 3 20.2 32 7 3 29 6 30.4 65 15 6 59 13 60.5 80 19 8 72 16 70.6 96 23 9 86 20 80.8 128 29 11 105 26 101.0 160 36 13 144 32 121.2 182 47 15 164 39 131.4 215 54 16 180 48 151.6 257 61 18 206 55 161.8 298 68 21 269 61 18Cushion CP 651N-L CP 651N-M CP 651N-S CP 651N-L CP 651N-M CP 651N-S

The following numerical values can only be taken as a rough guideline. The actual number of cushions which will be required, will vary according to a number of conditions including opening size, wall or floor thickness, as well as the shape of the opening.

Opening (m2 %06 daol elbaC%03 daol elbaC)0.01 – – – – – –0.02 – – – – – –0.04 4 2 1 – – –0.05 6 3 1 – – –0.1 11 3 2 9 5 30.2 23 6 2 14 5 30.4 45 11 4 26 8 40.5 56 13 5 33 11 40.6 67 16 6 41 12 60.8 82 20 8 54 13 61.0 112 25 9 65 18 81.2 128 33 11 76 24 91.4 158 39 11 87 31 101.6 181 43 12 104 36 101.8 208 48 15 121 41 12Cushion CP 651N-L CP 651N-M CP 651N-S CP 651N-L CP 651N-M CP 651N-S

Floor assemblyOpening (m2 %01 daol elbaC%0 daol elbaC)0.01 0 1 1 – – –0.02 0 2 3 1 2 30.04 3 3 2 2 4 30.05 5 4 2 5 3 20.1 9 5 2 11 5 20.2 20 10 4 22 10 40.3 30 15 8 32 14 80.4 42 21 9 46 18 80.5 52 26 12 57 21 100.6 63 31 14 69 23 120.7 73 36 16 81 25 15Cushion CP 651N-L CP 651N-M CP 651N-S CP 651N-L CP 651N-M CP 651N-S

Opening (m2 %06 daol elbaC%03 daol elbaC)0.01 – – – – – –0.02 – – – – – –0.04 3 2 2 – – –0.05 6 2 2 – – –0.1 9 4 3 7 3 10.2 18 7 4 12 4 20.3 26 11 5 18 6 30.4 34 15 6 24 8 50.5 42 18 8 28 10 60.6 49 22 10 33 13 70.7 57 26 12 39 15 9Cushion CP 651N-L CP 651N-M CP 651N-S CP 651N-L CP 651N-M CP 651N-S

Cable penetrations through walls with cable diameters ≤ 16 mm

Page 7: Hilti Firestop Specification Binder CP 651N trays and inside cable trunking PVC pipes up to 50mm Ordering Order description Package Contents Dimensions (LxWxH) Package Quantity Item

Hilti Firestop Systems Hilti Firestop Systems

Opening (m2 %01 daol elbaC%0 daol elbaC)0.01 0 1 4 – – –0.02 3 2 3 3 2 20.04 6 2 1 5 2 10.05 8 2 2 8 2 10.1 16 4 2 18 3 20.2 32 7 3 31 6 30.4 65 15 6 63 13 60.5 80 19 8 76 16 70.6 96 23 9 90 20 80.8 128 29 11 118 26 101.0 160 36 13 148 32 121.2 182 47 15 169 39 131.4 215 54 16 201 48 151.6 257 61 18 232 55 161.8 298 68 21 278 61 19Cushion CP 651N-L CP 651N-M CP 651N-S CP 651N-L CP 651N-M CP 651N-S

Consumption guide

Wall assembly

Cable penetrations through walls covering all cable diameters

Opening (m2 %06 daol elbaC%03 daol elbaC)0.01 – – – – – –0.02 – – – – – –0.04 5 2 1 – – –0.05 7 4 1 – – –0.1 15 3 2 12 4 20.2 23 6 3 20 5 30.4 51 14 5 36 9 40.5 64 13 5 40 11 40.6 74 16 7 52 12 60.8 92 20 8 66 13 61.0 119 25 10 78 18 81.2 136 31 11 86 24 91.4 164 38 12 109 31 101.6 189 43 12 120 36 101.8 218 48 15 136 41 12Cushion CP 651N-L CP 651N-M CP 651N-S CP 651N-L CP 651N-M CP 651N-S

Cable penetrations through walls with cable diameters ≤ 16 mmOpening (m2 %01 daol elbaC%0 daol elbaC)0.01 0 1 4 – – –0.02 3 2 3 3 2 20.04 6 2 1 5 2 10.05 8 2 2 8 2 10.1 16 4 2 17 3 20.2 32 7 3 29 6 30.4 65 15 6 59 13 60.5 80 19 8 72 16 70.6 96 23 9 86 20 80.8 128 29 11 105 26 101.0 160 36 13 144 32 121.2 182 47 15 164 39 131.4 215 54 16 180 48 151.6 257 61 18 206 55 161.8 298 68 21 269 61 18Cushion CP 651N-L CP 651N-M CP 651N-S CP 651N-L CP 651N-M CP 651N-S

The following numerical values can only be taken as a rough guideline. The actual number of cushions which will be required, will vary according to a number of conditions including opening size, wall or floor thickness, as well as the shape of the opening.

Opening (m2 %06 daol elbaC%03 daol elbaC)0.01 – – – – – –0.02 – – – – – –0.04 4 2 1 – – –0.05 6 3 1 – – –0.1 11 3 2 9 5 30.2 23 6 2 14 5 30.4 45 11 4 26 8 40.5 56 13 5 33 11 40.6 67 16 6 41 12 60.8 82 20 8 54 13 61.0 112 25 9 65 18 81.2 128 33 11 76 24 91.4 158 39 11 87 31 101.6 181 43 12 104 36 101.8 208 48 15 121 41 12Cushion CP 651N-L CP 651N-M CP 651N-S CP 651N-L CP 651N-M CP 651N-S

Floor assemblyOpening (m2 %01 daol elbaC%0 daol elbaC)0.01 0 1 1 – – –0.02 0 2 3 1 2 30.04 3 3 2 2 4 30.05 5 4 2 5 3 20.1 9 5 2 11 5 20.2 20 10 4 22 10 40.3 30 15 8 32 14 80.4 42 21 9 46 18 80.5 52 26 12 57 21 100.6 63 31 14 69 23 120.7 73 36 16 81 25 15Cushion CP 651N-L CP 651N-M CP 651N-S CP 651N-L CP 651N-M CP 651N-S

Opening (m2 %06 daol elbaC%03 daol elbaC)0.01 – – – – – –0.02 – – – – – –0.04 3 2 2 – – –0.05 6 2 2 – – –0.1 9 4 3 7 3 10.2 18 7 4 12 4 20.3 26 11 5 18 6 30.4 34 15 6 24 8 50.5 42 18 8 28 10 60.6 49 22 10 33 13 70.7 57 26 12 39 15 9Cushion CP 651N-L CP 651N-M CP 651N-S CP 651N-L CP 651N-M CP 651N-S

Cable penetrations through walls with cable diameters ≤ 16 mm

Page 10: Hilti Firestop Specification Binder CP 651N trays and inside cable trunking PVC pipes up to 50mm Ordering Order description Package Contents Dimensions (LxWxH) Package Quantity Item

CP 651N

Hilti (Gt. Britain) Limited, 1 Trafford Wharf Road, Trafford Park, Manchester M17 1BY

Telephone: 0800 886 100

Additional Properties of CP 651N – Firestop Cushion Property Test regime Notes

Fire BS EN 1366-3

ETA

Acoustic EN ISO 20 140-10: 1992 Dnw

58 dB

BS EN ISO 140-3:1995 Rw

50 dB

EN ISO 20 140-10: 1992 Blank

Dn,e,wtest results obtained 58 dB

EN ISO 20 140-10: 1992 Cables

Dn,e,w, 57 dB

Ageing DIBT

DAfSTB

Fire test after ageing

VOC LEED 2009 LEED 3.0 6.6 g/l

Chemical Resistance Contact Hilti Technical Advisory Service with details of type, concentration, duration and ambient temperature of exposure conditions

N.R Not relevant Meets standard

Page 11: Hilti Firestop Specification Binder CP 651N trays and inside cable trunking PVC pipes up to 50mm Ordering Order description Package Contents Dimensions (LxWxH) Package Quantity Item

CP 651N

Hilti (Gt. Britain) Limited,

1 Trafford Wharf Road, Trafford Park, Manchester M17 1BY

Telephone:

0800 886 100

CP 651N –Firestop cushion - BREEAM criteria

BREEAM Section

Management construction site impact

No power tools required for installation (no energy source required)

Dust free installation

Saves water during application No water pollution

Health and wellbeing

Low VOC* (air quality)

No ozone depletion potential (ODP)

Low global warming potential (GWP)

Smoke and gas tightness

Noise reduction

Energy Air tightness NA

Avoidance of air infiltration NA

Materials

Product Carbon Footprint or LCA Data

Thermal insulation

Waste

Recycling of packaging

Reuse of materials

Re-penetration in existing opening (No waste)

Product contributes to Green Building under this clause

Not applicable for this product NA

Product makes No contribution to green Building under this clause

Page 12: Hilti Firestop Specification Binder CP 651N trays and inside cable trunking PVC pipes up to 50mm Ordering Order description Package Contents Dimensions (LxWxH) Package Quantity Item

CP 651N

Hilti (Gt. Britain) Limited, 1 Trafford Wharf Road, Trafford Park, Manchester M17 1BY

Telephone: 0800 886 100

CP 651N –Firestop cushion - NBS specification clauses This page is to be used in conjunction with the NBS Specification clauses in the introduction to the Hilti Firestop Specifiers Binder. Application: Imperfections of fit of building components and Service penetrations through fire rated walls and floors requiring treatment to reinstate the fire performance of said walls and floors P12 FIRE STOPPING SYSTEMS PRODUCTS 345 INTUMESCENT PILLOWS

• Composition: sealed polythene bags contained within a glass fibre outer containing graphite and vermiculite granules that intumesce to provide a fire rated barrier for service penetrations in solid walls and floors and partition walls when packed into opening in layers. CP 651N use to Firestop inside cable trunking.

• Tested to BS 476: Part 20: 1987 and BS EN 1366-3:2004. • Fire resistance: up to 4 hours • Age tested as defined in the DafStb guidelines, with subsequent fire testing. • Manufacturer: Hilti (Gt Britain) Ltd, 1Trafford Wharf Road, Manchester M17 1BY, Tel no 0800 886

100, Fax 0800 886 200. Website www.hilti.co.uk. - Product Reference: CP 651N Intumescent Cushions

Page 13: Hilti Firestop Specification Binder CP 651N trays and inside cable trunking PVC pipes up to 50mm Ordering Order description Package Contents Dimensions (LxWxH) Package Quantity Item

CP 651N

Hilti (Gt. Britain) Limited, 1 Trafford Wharf Road, Trafford Park, Manchester M17 1BY

Telephone: 0800 886 100

Visit our web site at www.Hilti.co.uk/cfs to access our Firestop Design Centre

Penetration product selector Other product features Joints product selector

Interactive product selector for firestopping openings through walls and floors

Find out more about the benefits of using Hilti firestop systems

Interactive product selector for wall to wall, top of wall, curtain wall , floor to floor and floor to wall applications.

Important note:

All sales are subject to Hilti (Gt Britain) Ltd. “Terms and Conditions of Sale”.

Copies of these “Terms and Conditions of sale” are available on request.

All descriptions and illustrations in this publication are intended for

guidance only and shall not constitute a “sale by description / picture”. All dimensions given are nominal and Hilti (Gt Britain) Limited may change the information, products and specifications from time to time for a variety of reasons, without prior notice. The information in this publication is provided “as is” at the date specified on the front cover. (Updates will not be issued automatically) This information is not intended to have any legal effect, whether by way of advice, representation or warranty (express or implied). Hilti (Gt Britain) Ltd accepts no liability whatsoever (to the extent permitted by law) if you place any reliance on this publication and you must do so at your own risk.

RETURNS AND CANCELLATIONS Subject to condition 6.3 of the Company’s Terms and Conditions, Goods supplied pursuant to the Contract cannot be returned without the Company’s prior written authorisation. Duly authorised returns:

• shall be sent to the Company’s premises at the Buyer’s expense;

• may be subject to a handling charge of £10 or 20% Hilti Gt. Britain Ltd) of the value of the Goods, whichever amount is the greater; and

• Must be in the same condition as originally supplied to the Buyer.

• The Buyer may not cancel an order of the Goods including but without limitation, any Goods that involve special requirements of the Buyer once the order has been inputted onto the Company’s ordering system, without the prior written consent of the Company.

Right of technical and programme changes reserved S.E&O;

no liability accepted for printing errors or other deficiencies, earlier catalogues are thus rendered non valid. Hilti = registered trademark of Hilti Corp. Schaan


Recommended