HOME AFFAIRS DEPARTMENT OFFICE OF THE LICENSING AUTHORITY
Standard Licensing Requirements
Part I : Health Requirements
Part II : Fire Safety Requirements
Part III : Building Safety Requirements
(For Karaoke Establishments)
LASC-VII (07-2017)
1
Part I : HEALTH REQUTREMENTS
1. Provision of Sanitary Fitments
1.1 Sanitary fitments shall be provided to a standard not less than that required by the
Building (Standards Of Sanitary Fitments, Plumbing, Drainage Works And Latrines)
Regulations (Cap. 123 sub. Leg.) applicable to restaurants.
1.2 The following number of watercloset fitments, urinals and lavatory basins shall be
provided.
Type of fitment For Male For Female
(a) Watercloset fitment
(b) Lavatory basins
(c) Urinals
2. Lighting and ventilation to toilets
2.1 Natural lighting and ventilation to toilets shall be provided by means of windows so
that :-
(a) the total area of glazing is not less than one-tenth of the floor area of the rooms;
and
(b) a window area of not less than one-tenth of the floor area of the room is
openable to open air with the top being at least 2 m above the floor.
2.2 Where natural means are inadequate / unavailable due to planning constraint, artificial
lighting and ventilation to toilets shall be provided so that :-
(a) artificial lighting of not less than 50 lux is provided; and
(b) mechanical ventilation of not less than 5 air changes per hour is provided.
2.3 Toilets shall not open directly into a kitchen or food preparation or storage room.
3. Lighting and ventilation to kitchens
3.1 Natural lighting and ventilation to the kitchen shall be provided by means of windows
so that :-
(a) the total area of glazing is not less than one-tenth of the floor area of the room;
and
(b) a window area of not less than one-sixteenth of the floor area of the room is
openable to external air with the top being at least 2 m above the floor.
2
3.2 Where natural means are inadequate / unavailable due to planning constraint,
artificial lighting and ventilation to the kitchen shall be provided so that :-
(a) artificial lighting of not less than 300 lux is provided; and
(b) mechanical ventilation of not less than 5 air changes per hour is provided.
4. Sanitizing facilities for microphones
Adequate sanitizing facilities for all microphones shall be provided and maintained in the
premises to which a permit or licence relates and the microphones shall be kept in a clean
and hygienic condition. Some suggestions on sanitizing measures are:
4.1 The surface of the microphone should be cleaned with damp cloth and then wiped
with alcohol daily or when it appears soiled; or
4.2 Every microphone should be properly covered by a disposal cover which will be
discarded and replaced after each sectional use by customers.
5. Toilet Utilities
5.1 Wash-hand basin must be provided with adequate supply of liquid soap in
dispensers and clean paper towel or cloth towel rolls in dispensers or electric hand
dryer.
5.2 If cloth towel rolls in dispensers are used,
(a) the dispensers should be designed in such a way that the users can only
retrieve the clean and unused portion of the cloth towel roll therein; and
(b) the towels or towel rolls provided through the dispensers must be dry, clean,
sanitized, unworn, stainless and of good quality.
5.3 If electrical hand dryers are provided, they must be in good working condition at all
times.
5.4 Each water closet must be provided with an adequate supply of toilet paper and
kept clean at all times.
3
Part II : Fire Safety Requirement
1. Combustible materials used as false ceiling, partitions or wall furnishing
All combustible materials used as false ceilings, partitions or wall furnishings shall conform
to British Standard 476: Part 7 Class 1 or 2 Rate of Surface Spread of Flame or to another
standard acceptable to the Director of Fire Services, or shall be brought up to any of those
standards by treating with a fire retardant paint or solution acceptable to the Director of Fire
Services.
2. Draperies and curtains
All draperies and curtains, if installed, shall be made of fire resistant material and conform to
British Standard 5867: Part 2 fabric type B when tested in accordance with British Standard
5438 or to another standard acceptable to the Director of Fire Services, or shall be brought up
to any of those standards by treating with a fire retardant solution acceptable to the Director
of Fire Services.
3. Carpet
3.1 All carpets within the protected means of escape shall
(a) be made of pure wool;
(b) conform to British Standard 5287 when tested in accordance with British Standard
4790; or
(c) be manufactured to a standard acceptable to the Director of Fire Services.
3.2 Carpets that do not meet any of the above requirements shall also be accepted as
complying with fire safety requirements if their pile height does not exceed 10mm and
they do not cover more than 5% of the protected means of escape calculated on a
floor-by floor basis.
4. Polyurethane foam (PU foam) filled mattresses
All polyurethane foam (PU foam) filled mattresses shall conform to British Standard 7177
(for use in medium hazard premises) or to another standard acceptable to the Director of Fire
Services. The mattress meeting the specified standards shall bear an appropriate label (See
Annex A of Part II). Invoices from manufacturers/suppliers and test certificates from a
testing laboratory both indicating that the PU foam filled mattresses comply with the
specified standards shall be produced for verification. The test certificates shall be issued by a
testing laboratory accredited to conduct tests according to the specified standards, and be
authenticated by the company’s stamp of manufacturers/suppliers.
5. Polyurethane foam filled upholstered furniture
All polyurethane foam filled upholstered furniture shall conform to British Standard 7176
(for use in medium hazard premises) or to another standard acceptable to the Director of Fire
Services. The furniture items meeting the specified standards shall bear an appropriate label
(See Annex A of Part II). Invoices from manufacturers/suppliers and test certificates from a
testing laboratory both indicating that the PU foam filled furniture items comply with the
specified standards shall be produced for verification. The test certificates shall be issued by a
testing laboratory accredited to conduct tests according to the specified standards, and be
authenticated by the company’s stamp of manufacturers/suppliers
4
6 Dedicated smoke extraction system
The window of the premises shall not in any way be obstructed by any decoration or sealed
up for more than 50% of the designed openable/breakable windows unless protected by a
dedicated smoke extraction system which shall conform to the standard set out in the Code of
Practice for Minimum Fire Services Installations and Equipment issued by the Director of
Fire Services.
7 Exit sign & Directional sign
All exits shall be indicated by illuminated signs, bearing the word and characters “EXIT出
口” (See Annex B of Part II). Adequate directional signs indicating the route to an exit shall
be provided at locations where exit signs are not readily visible. Exit Signs and directional
signs shall be installed in accordance with the requirements set out in the Code of Practice for
Minimum Fire Service Installations and Equipment as published from time to time by the
Director of Fire Services.
8 Low level directional sign
Low level directional signs capable of indicating the route to an exit in darkness shall be
provided at 200mm above floor level. The Low level Directional Signs shall be of self
luminous type and conform to British Standard 5499:Part 2, or conforms to the standard set
out in the Code of Practice for Minimum Fire Service Installations and Equipment as
published from time to time by the Director of Fire Services shall be provided.
9 Exit plan
An exit plan drawn to a ratio of not less than 1:200 showing the floor layout of the premises
and the directions of egress to escape staircases and means of escape shall be displayed in
each room intended to be used by customers. The size of the exit plan shall not be less than
250mm x 250mm and shall be affixed adjacent to the exit of each room at 1500mm above
floor level.
10 Emergency lighting
Emergency Lighting - Self-contained Luminaries shall be provided. (See Annex C of Part II)
11 Short film on fire safety
A short film on fire safety including what to do in case of fire inside the premises shall be
provided for showing to the customers before they start each session of karaoke activity.
12 Emergency alert system
An emergency alert system which can interrupt the music or other sound and visual images
produced by the karaoke equipment and at the same time produce visible and audible
warning signals in case of a fire alarm shall be provided.
5
13 Fire safety training
The grantee/licensee should make arrangement to ensure that at least one of their management staff in employment has completed a fire safety training course recognized by the Fire Services Department; and to ensure that all employees working in the karaoke establishment must have received the fire safety training given by this trained management staff at least once every 12 months.
14 Fire service installations and equipment
Ardor service installations of the following description shall be provided in accordance with the following provisions and with the Code of Practice for Minimum Fire Service Installations and Equipment as published from time to time by the Director of Fire Services:-
14.1 a fire hydrant and hose reel system; 14.2 a manual fire alarm system with operation switches provided at each of the
following locations - (a) near each exit leading away from the premises; (b) at the main entrance; (c) at the cashier’s counter; (d) at the reception area; and
(e) at the waiting area;
14.3 alarm bells of the fire alarm system in individual rooms intended to be used by customers (see also paragraph 12);
14.4 where the premises are located in a curtain-walled building or on a basement floor
and occupy an area exceeding 126 m2, an automatic sprinkler system that uses fast-
response-type sprinkler heads. 14.5 where the premises are located in a place other than those described in paragraph
14.4 and- (a) occupy an area exceeding 126 m
2 but not exceeding 230 m
2, either an
automatic fire detection system or an automatic sprinkler system; or (b) occupy an area exceeding 230m
2, an automatic sprinkler system that uses
fast-response-type sprinkler heads;
14.6 In respect of paragraphs 14.4 and 14.5, the sprinkler system shall be designed and installed in accordance with the Loss Prevention Council Rules for Automatic Sprinkler Installations For retro-fitting of such system, a compromised standard with water supplied directly from town mains may be accepted subject to approval of the Director of Water Supplies.
14.7 where the premises are located in a curtain-walled building or on a basement floor
with a cubic volume exceeding 7000m3, a smoke extraction system.
14.8 Where the karaoke room situated in a dead-end corridor, a 9-litres water type fire
extinguisher and a manual fire alarm system with operation switches shall be provided in such room.
15 Ventilating System 15.1 All ventilating systems shall be inspected by the Ventilation Division of Fire
Services Department and a copy of letter of compliance shall be submitted to the relevant authority as proof of compliance.
6
15.2 in the case where the karaoke establishment is located in a restaurant, comply with
the requirements set out in the Ventilation of Scheduled Premises Regulation (Cap.
132 sub. leg.); or
15.3 in any other case, comply with the requirements set out in the Building (Ventilating
Systems) Regulations (Cap. 123 sub. leg.)
15.4 Automatic cut-off devices shall be provided for mechanical ventilating systems to
enable the ventilation supply to be cut off in case of fire.
16 Electrical Installations
16.1 New fixed electrical installations, after completion, shall be inspected, tested and
certified by an electrical worker/contractor registered with the Director of Electrical
and Mechanical Services (DEMS). A copy of the Work Completion Certificate
(Form WR1) shall be submitted to the Authority as proof of Compliance.
16.2 For existing electrical installations, a Periodic Test Certificate (Form WR2)
endorsed by DEMS in lieu of the required Form shall be submitted instead.
17 Kitchen
17.1 The requirements for the use of fuel in kitchen are stipulated Annex D of Part II.
17.2 Portable Fire Fighting Equipment
(a) One 4.5 Kg CO2 or 2 Kg dry powder fire extinguisher shall be provided in the
kitchen.
(b) One x 1.44sq.m fire blanket for every 3 frying pans/woks using oils/fat for
deep frying;
Number of frying pans/woks = Fire blanket
3
18 Fuel for Seating Accommodation
18.1 The requirements for the use of fuel for seating accommodation are stipulated in
Annex E of Part II.
7
Part III : BUILDING SAFETY REQUIREMENTS
The Code of Practice for the Provision of Means of Escape in Case of Fire 1996, the Code of
Practice for Fire Resisting Construction 1996 and the Code of Practice for Means of Access
for Firefighting and Rescue 2004 issued by the Buildings Department have been replaced by
the Code of Practice for Fire Safety in Buildings 2011 and the following information should
make reference to the updated version therein where appropriate.
1. Structural suitability
1.1 Every karaoke establishment shall be structurally capable of withstanding an
imposed load of not less than 5 kPa and be in sound structural condition. If the
structural capacity for imposed load is less than 5kPa, structural justification
prepared by an Authorized Person / Registered Structural Engineer (AP/RSE) on the
structural adequacy of the premises shall be submitted for consideration by the
Licensing Authority.
1.2 Non-structural screeding on slabs to raise floors levels, solid partition walls, heavy
equipment or installations, structural justification prepared by an Authorized Person /
Registered Structural Engineer (AP/RSE) on the structural adequacy of the existing
building may be required for consideration by the Licensing Authority.
2 Compliance with the code of practice on fire resisting construction
The karaoke establishment shall be designed and constructed in accordance with the
requirements set out in the Code of Practice for the Provision of Fire Resisting Construction
(the “FRC code”) as published from time to time by the Director of Buildings.
3 Protection of adjoining buildings
3.1 Every karaoke establishment should be separated from any adjoining building by an
external wall having a fire resistance period (FRP) of not less than 2 hours.
3.2 No openings should be made in such external walls that are within a distance of
900mm of any part of any building on the same site or within 450mm of the
boundary with an adjoining site. Openings may however be made in external walls
within a distance between 900mm and 1.8m of any part of any building on the same
site or within 900mm of the boundary with an adjoining site provided that these
openings are protected by fixed light of FRP as specified in the Code of Practice for
the Provision of Fire Resisting Construction.
4 Separation between uses
4.1 Every karaoke establishment should be separated from areas adjacent to or within a
karaoke establishment that are for different uses as classified in Table 1 by walls and
floors having an FRP of 1 hour or such longer period as required for the uses.
8
Table 1 : Fire Resistance Period
Type Use Volume of compartment FRP
1 Domestic
Not exceeding 28 000m3 1 hour 2 Hotel bedroom
3 Office
4 Shop, restaurant, and hotel foyer If not exceeding 7 000m3
or
If exceeding 7 000m3 but
not exceeding 28 000m3
1 hour
2 hours
5 Place of public entertainment
6 Place of assembly
7 Carparking
8 Bulk storage and warehouse Not exceeding 7 000m3 2 hours
4.2 For any karaoke establishment situated in any basement, its elements of construction,
including walls and floors, should have an FRP of not less than 4 hours.
5 Separation between occupancies
Karaoke establishments shall be separated from adjoining occupancies by walls and floors
having a FRP of not less than 1 hour or not less than that required for the elements of
construction of the compartment in which it is situated, whichever is the greater.
6 Fire Resistance Period for internal corridors
6.1 Every internal corridor within a karaoke establishment shall be separated from other
areas by walls having an FRP of not less than one hour (“fire resisting walls”) and
the doors in the corridor shall be self-closing and have a fire resistance period of not
less than 1/2 hour.
6.2 For karaoke establishments that have been in operation immediately before the
commencement of the Ordinance (i.e. 8 January 2003), upgrading of fire resistance
of corridor walls may be carried out in phases. For karaoke establishment installed
with sprinklers, the upgrading works could be carried out within 36 months counting
from the date on which the Ordinance comes into operation (i.e. before 8 January
2006). For establishments without sprinklers, the upgrading works could be carried
out within 18 months counting from the date on which the Ordinance comes into
operation (i.e. before 8 July 2004) subject to the provision of emergency alert system
in every room and at suitable locations of the corridor.
7 Compartmentation
7.1 Every karaoke establishment should be divided into compartments by walls and
floors such that no compartment exceeds 28,000 m3.
7.2 Compartment walls, compartment floors, separations and lobbies should be
constructed with all joints completely filled with non-combustible material to
prevent the passage of smoke or flame.
9
8 Protection of openings in fire resisting walls and floors
8.1 Openings through compartment walls shall be protected to maintain the fire
resistance of the wall, by a protected lobby with doors of the required FRP or, except
for places of public entertainment or carparks, by a fire shutter with the same FRP
(with respect to integrity) as the wall.
8.2 Escalators or staircases, other than required staircases, which perforate floors
between compartments may be unenclosed in one compartment provided that such
escalators or staircases are enclosed in the adjoining compartment by walls having
an FRP of not less than the longer period required for the elements of construction of
the compartments so served. Every opening in such enclosing walls should be
provided with a door or fire shutter having an FRP of not less than half that of the
enclosing wall in which it is situated.
8.3 Every opening for the passage of building services through a fire resisting wall or
floor, and every hole in the wall or floor left after construction shall be protected
with fire dampers or other form of fire stop that is considered suitable by the
Licensing Authority to maintain the FRP of that wall.
8.4 If any building services passing through a fire resisting wall or floor consist of
combustible material, the material shall be contained within an enclosure having a
fire resistance period of not less than one hour. Every access opening provided to
the enclosure shall be provided with a door having a fire resistance period of not less
than 1/2 that of the enclosure.
9 Protection of liftwells and required staircases
9.1 All liftwells except for openings for doors and ventilation should be separated from
the remainder of the karaoke establishment by walls having an FRP of not less than
that required by the elements of construction of the compartment.
9.2 All required staircases and any lobbies separating those staircases from the general
accommodation should :-
(a) be separated from the remainder of the karaoke establishment by walls having
an FRP of not less than that required for the compartment to which they
connect.
(b) be imperforate, except for any doorway giving access to the karaoke
establishment which should be provided with a door having an FRP of not less
than half of the wall in which the doorway is situated, or 1 hour whichever is
less.
(c) not accommodate any services other than emergency services such as fire
Hydrants, sprinkler systems, emergency lights and exit signs.
10
10 Protection against spread of fire and smoke between floors
At any internal unprotected opening in floors within a compartment, such as at escalators,
circulation staircases, a barrier of not less than 450 mm measured vertically downwards
from the underside of the floor, should be provided to surround the opening. The barrier
should be constructed to have an FRP of not less than 1 hour. The barrier shall extend not
less than 450 mm below any false ceiling hung in the vicinity of the opening.
11 Special hazards
11.1 Areas for electrical or hazardous installations or for storing dangerous goods should
be enclosed by non-combustible construction having an FRP of not less than 2 hours
(4 hours adjoining required staircases), and any permitted openings thereto should be
provided with a door having an FRP of not less than one hour.
11.2 Kitchens:-
(a) should be enclosed by walls and floors having a FRP of not less than 1 hour,
and any door opening on such walls should be provided with self-closing
doors having FRP of not less than 1/2 hour;
(b) should be provided with protected lobbies between each door of the kitchen
and any escape route from the main building; and/or the dining area where the
kitchen has a usable floor area exceeding 45 m2 and the door opens onto an
exit route of the dining area;
(c) hatch (permitted for small food serving hatch only) should be provided with a
fire shutter having a FRP of 1 hour, and shall be activated by a fusible link.
11.3 Other areas of high fire risk directly associated with a normal occupancy in a
karaoke establishment should be adequately separated by fire resisting construction.
12 Doors
12.1 All doors required to have an FRP should be arranged to be self-closing. The
self-closing mechanism shall not be capable of allowing a check action to hold the
door open.
12.2 A notice should be provided on both sides of such doors in English and Chinese in
letters and characters not less than 10 mm high as follows :-
FIRE DOOR
TO BE KEPT CLOSED
防 火 門防 火 門防 火 門防 火 門
應 常 關應 常 關應 常 關應 常 關
11
12.3 All FRP doors shall be closely fitted around their edges to impede the passage of
smoke or flame.
12.4 FRP doors should be tested or assessed in accordance with BS 476: Parts 20 and 22:
1987 and certified as being capable of resisting the action of fire for the specified
period. Certification including test report and assessment report prepared by a
laboratory recognized by the Hong Kong Laboratory Accreditation Scheme or the
Building Authority shall be submitted to the Licensing Authority for proof of the
compliance with the standard.
13 Basements
13.1 All approved smoke outlets, vents and dynamic smoke extraction system shall be maintained in efficient working condition or reinstated; and in case rendered inadequate by any alteration of the premises, they shall be provided in accordance with the Code of Practice for the Provision of Fire Resisting Construction.
13.2 Where a basement has the same use as the ground storey and any upper storeys, it may be united thereto provided that every element of construction, compartment wall and compartment floor in such storeys and the construction separating the uppermost of such storeys from the storey above have the same FRP as that of the basement.
14. Fire Resisting Materials
For all building materials required to have specified fire resisting period under this Standard
Licensing Conditions (LASC-VII Part III) or the Special Conditions, supporting documents
including supplier’s certificate, test report, delivery note and construction photos shall be
submitted to the Licensing Authority as proof of compliance of the Conditions so stipulated.
15. Compliance with the code of practice on means of escape
The karaoke establishment shall be provided with adequate means of escape complying with
the requirements set out in the Code of Practice for the Provision of Means of Escape in
Case of Fire (the “MOE code”) as published from time to time by the Director of Buildings.
16 Population of a karaoke establishment for the provision of means of escape
Under the circumstances of the premises, the maximum number of persons ( including staff)
that can be accommodated within the karaoke establishment is restricted to .
17 General requirements on exit routes
17.1 At least two exit routes or such higher numbers as required under the “MOE code’’
shall be provided on each storey.
17.2 Any room/storey/premises with a capacity exceeding 30 persons shall be provided
with at least 2 exits.
17.3 A clear and unobstructed access route of not less than mm, as Required
under the “MOE code’’ , shall be provided throughour the seating Area to the exit
route.
12
17.4 Every part of an exit route shall be provided with artificial lighting providing a
horizontal luminance at floor level of not less than 30 lux and backed up by an
emergency lighting system providing a horizontal luminance at floor level of not less
than 2 lux. The design of the emergency lighting system should comply with the
Code of Practice for Minimum Fire Service Installations and Equipment.
17.5 The means of escape from any part of the karaoke establishment shall be so arranged
that it is not necessary to pass through one staircase enclosure in order to reach an
alternative staircase.
17.6 Where the building/storey(s) in which the karaoke establishment is located is
required to have two or more exit staircases and it is required that people using one
staircase is able to gain access to at least one of the other staircases at any time
without having to pass through private premises, such protected access shall be
maintained at all times, without being locked up.
17.7 Every part of an exit route should have a clear height of not less than 2 m.
18 Direct distance and travel distance
Every room intended to be used by customers, except toilets, shall have at least two exit
routes leading in different directions to a staircase or a point of discharge to a street. The
maximum distances that will be permitted from any part of the karaoke establishment shall
be in accordance with paragraph 14 of the “MOE” code. In this connection the maximum
distance in the karaoke establishment is exceeded. Modification of the layout is required.
19 Internal exit routes
19.1 The width of exit routes including internal corridors within a karaoke establishment
must be at least 1.2 m.
19.2 If a karaoke establishment is in operation immediately before the commencement of
the Ordinance (i.e. 8 January 2003), widening of the corridor to meet the new
requirement may be deferred until such time the karaoke establishment undertakes
major alteration works on the condition that all other building and fire safety
requirements are complied with and that the width of the corridor is not less than
1.05 m and the total capacity of the karaoke establishment is not more than 500
persons per floor. (For avoidance of doubt, upgrading of the corridor walls to meet
the required FRP is not regarded as major alteration works unless the layout of the
karaoke establishment is also substantially changed at the same time.)
20 Exit from entertainment rooms (room to be used by customers except toilets)
20.1 The exit from every entertainment room should have and must enable at least two
directional travels to a staircase or a point of discharge to a street. An
entertainment room opening off a dead-end corridor (i.e. the direction of travel from
the exit door of the room to a staircase or a point of discharge to a street is possible
in one direction only) is generally not permitted.
13
20.2 A dead-end situation is only permitted in circumstances due to unavoidable building
design subject to the provision of the following additional safety measures :
(a) the karaoke establishment being protected by an automatic sprinkler system;
and
(b) the provision of a portable water type fire extinguisher with 9-litre capacity
and an additional manual fire alarm in each entertainment room opening off
the dead-end corridor.
(An example of unavoidable dead-end due to building design is provided in
Annex A of Part III whereas an example of avoidable dead-ends is illustrated
In Annex B of Part III.)
20.3 For Karaoke establishments that have been in operation immediately before the
commencement of the Ordinance (i.e. 8 January 2003), modification of the layout is
required for dead-ends created not as a result of building design. The following
emergency escape route arrangements are acceptable in resolving the dead-end
problem :-
(a) Creation of a second emergency exit route ( Annexes C & F of Part III):
(i) Two adjoining dead-end corridors should be linked up and the two
entertainment rooms at the dead-ends should be transformed into an exit
corridor in the event of an emergency.
(ii) An additional double-swing exit door should be provided in the
common partition wall of these two entertainment rooms. It may be
fitted with a door lock provided that such lock would be released
automatically in response to fire alarm. An additional manual fire alarm
operation switch should be provided in a safe and convenient position so
that the lock should be released when this alarm is actuated. Upon
power failure, the lock should also be released automatically.
(iii) The emergency escape route within these entertainment rooms should
not be blocked. All furniture in these two rooms should be fixed (i.e.
without movable furniture) and should not obstruct the exit door
between these two rooms.
(iv) To provide additional protection to the secondary exit, doors with 1/2
hour FRP are provided across these two adjoining dead-ends. These
doors may be fitted with a hold-open device that can be released
manually or upon activation of a smoke detection system or the
operation of a fire alarm.
14
(v) The width of the exit doors required in items (ii) and (iv) should comply
with Table 2 of the Code of Practice for the Provision of Means of
Escape in Case of Fire.
(vi) The exit door should meet with the requirements in Annex F of Part III.
(vii) This option can be modified to apply to a single dead-end corridor.
(b) Utilizing access panel in other entertainment room (Annexes D,E&F
of Part III):
(i) Customers in an entertainment room without alternative escape route
should be able to use the access panel in another entertainment room
located within the same corridor to reach an alternative exit route, if
required, in case of an emergency.
(ii) A self-closing exit door with 1/2 hour FRP is installed across the dead-end
corridor to provide additional protection to customers within the
protected dead-end corridor. This door may be fitted with a hold-open
device that can be released manually or upon activation of a smoke
detection system or the operation of a fire alarm. The width of this door
should comply with Table 2 of the Code of Practice for the Provision of
Means of Escape in Case of Fire.
(iii) An access panel in one room to serve customers in one other
entertainment room is acceptable. For dead-end corridor exceeding
15m long additional portable water type fire extinguisher with 9-litre
capacity may be required should be provided in those entertainment
rooms without access panels.
(iv) The access panel should meet with the requirements in Annexes
E and F of Part III.
(c) Providing access panel in entertainment room (Annexes D,E&F of
Part III):
(i) Every entertainment room in the dead-end corridor is provided with an
access panel giving access to the adjacent entertainment room where its
exit discharges to another corridor.
(ii) The access panels should meet with the requirements in Annexes E and
F of Part III.
20.4 The fire safety video to be shown to the customers before music videos are started
should include the above special exit arrangements if adopted. Adequate
illuminated directional signs and notices should also be prominently displayed to
show the escape arrangement in accordance with Annex F of Part III. The swing of
the emergency exit doors and access panels should be indicated on the submitted
plans.
15
21 Vision Panel
A vision panel of not less than 0.04 m2 should be provided either on the wall facing the
internal corridors or on the access door of every entertainment room. The vision panel
should have the same FRP of the wall or the door on which it is installed, and shall provide
a clear view of things on the other side of the panel both from inside and outside the room at
normal eye level.
(For existing karaoke establishments that have been in operation immediately before the
commencement date of the Karaoke Establishments Ordinance, i.e. 8 January 2003, the
provision of vision panels may be deferred until such time the corridors are upgraded to
comply with the fire resisting walls requirements of the internal corridors. See also
paragraphs 6.2, 18.2 & 19.)
22 Doors gates and shutters in exit routes
22.1 Every door across an exit, or into an exit route from a room or storey the capacity of
which exceeds 30 should open in the direction of exit, and if it opens both ways,
have a transparent upper view panel.
22.2 Gates and shutters across exit routes are not permitted.
22.3 Locking devices shall be capable of being readily opened from the inside without the
use of a key. A locking device which is electrically operated is acceptable provided
that such lock is capable of automatic release upon actuation of a smoke detection
system or the operation of an alarm system or a central manual override, installed to
the satisfaction of the Director of Fire Services. Upon power failure, the electrical
locking device shall also be released automatically.
22.4 Every door giving access to a protected lobby from a staircase enclosure or corridor,
and every door across an exit route shall be provided with a transparent upper view
panel of the requisite fire resistance.
22.5 Every door opening on to an exit route shall be so arranged as not to obstruct the exit
route at any point of its swing; and every door opening on to a landing between
flights of stairs shall not at any point of its swings, reduce the effective width of the
landing to less than the width of the stair.
22.6 Exit door from a room or storey having a capacity in excess of 3 persons should not
be less than 750 mm in width. In the case of a double leaf door, no leaf of such
door should be less in width than 600 mm and, where the meeting stiles are rebated,
a checking device to control the closing order of the doors should be installed.
Such checking device should ensure that both leaves of door are closed in the correct
order and position. (For the minimum width requirements and other exit
requirements, the “MOE” code shall be observed.)
22.7 Exit doors of not less than mm wide shall be provided in the karaoke
establishment.
16
23 Compliance with the code of practice on means of access for firefighting and rescue
23.1 The requirements set out in the Code of Practice for Means of Access for
Firefighting and Rescue as published from time to time by the Director of Buildings
shall be complied with.
23.2 No alteration to approved fireman’s lift lobby shall be carried out unless the
minimum requirements of the above Code of Practice are maintained.
24 Concealed construction works
For all critical construction works to be concealed under finished works, including drainage
works, fire resisting construction works, waterproofing works and duct-works passing
through fire resisting walls, etc., construction photos clearly showing the critical steps,
components or details before covering up of which shall be submitted to the Licensing
Authority. Otherwise, the applicant may be required to open up the finished works for
verifying compliance with the relevant Standard Licensing Conditions (LASC-VII Part III) or
Special Conditions.
LASC-VIII (07-2017)
17
Annex A of Part II
Sample of Label (標籤樣本標籤樣本標籤樣本標籤樣本)
Sample I (樣本I)
*Delete wherever inapplicable/請刪去不適用者
Note: The minimum size of the label shall be 5×7.5cm and the minimum size of the
type shall be 3mm in height. All type shall be in capital letters.
註: 標籤面積最小須為 5×7.5厘米,字體高度最小須為3毫米。
(英文告示的所有字體必須為大楷)
NOTICE
THIS ARTICLE IS MANUFACTURED FOR USE IN PUBLIC
OCCUPANCIES AND MEETS THE FLAMMABILITY
REQUIREMENTS OF CALIFORNIA BUREAU OF HOME
FURNISHINGS TECHNICAL BULLETIN 133*/129*/121*.
CARE SHOULD BE EXERCISED NEAR OPEN FLAME OR
WITH BURINING CIGARETTES.
告示
此家具為供公眾使用而製造,符合加利福尼亞州家具局技術
報告(TB)第 133*/129*/121* 的可燃規定,請勿將此家具放近
明火或有香煙的地方。
5
抗火
RESISTANT
Complies with BS 7176:1995
Didirect test/predictive test*
for medium hazard *Delete whichever is
inappropriate 符合英國標準 7176:1995 適用於中度危險的 *
5
抗火
Complies with BS 7177:1996
for medium hazard 符合英國標準 7177:1996 適用於中度危險的
Sample II (樣本 II) Sample III (樣本 III)
RESISTANT
18
RESISTANT
Annex B of Part II
Exit Signs
All exits of the exit routes within the premises leading to the exit routes of the building shall be
indicated by internally illuminated/self luminous signs bearing the word and characters ‘EXIT出
口’ in block letters and characters of not less than 125mm high. The letter style shall be in
‘Modified Garamond’ or ‘Helvetica’ or ‘Marigold’ as indicated on the samples below while the
Chinese characters shall be with width of vertical strokes not less than 15mm and with width of
horizontal stokes not less than 10mm.
Modified Garamond Helvetica Marigold
Color contrast for translucent surrounds to lettering shall be as follows :-
Color Contrasting Color
Green White
White Green
The color combination selected shall preferably be consistent throughout the same licensing
premises.
Directional Signs
If an exit sign is not clearly visible from any location in the premises, suitable internally
illuminated/self luminous directional signs shall be erected to assist occupants to identify the exits
in the event of emergency. The graphics of directional signs shall be as shown in the figures
below, signs having substantial compliance with the figures shall also be acceptable.
19
Annex C of Part II
Requirements for self-contained luminaries emergency lighting system
1. The units shall be constructed from fire resistant materials.
2. Each unit shall be so designed as to provide a broad non glare illumination when in use
and not less than two units shall be provided for any installation.
3. An automatic trickle charger with a 220-volt input and suitable output and fitted with pilot
lights or other indicating device shall be provided for the batteries. The charger shall be
capable of recharging the battery in not more than 12 hours.
4. The minimum illumination provided by the emergency lighting system shall be:
Staircase/exit route not less than 2 lux measured along
the center line of the staircase/exit
route at floor/nosing level.
Night club, restaurant, dance hall, not less than 1 lux measured at floor
or premises where people have level
freedom of movement and there
are loose fixtures and fittings
All readings shall taken by a portable photoelectric photometer and a discretionary tolerance
of plus or minus 10% is permitted.
5. The self-contained luminaries emergency lighting system shall be capable of maintaining the
stipulated lighting levels for a period of not less than one hour.
6. Each unit shall be provided with a “TEST” switch, a charge monitor light and a low voltage
cut out to disconnect the batteries when fully discharged.
7. The emergency lighting system shall be wired in M.I.C.C. in accordance with B.S.6207/P.V.C.
in conduit in accordance with B.S.5266.
8. Once every month a discharge test shall be carried out and the results entered in a register.
20
Annex D of Part II
Requirement for various fuels used in kitchen
1. Scope
The document specifies the various fuels that may be used in kitchen and prescribes the
relevant fire safety requirements.
2. Restriction
2.1 Liquefied Petroleum Gas (LPG) is not permitted :
(a) In any quantity if the kitchen of the karaoke establishment is located on any
floor below ground level;
(b) In quantities exceeding 130 litres water capacity contained in portable
cylinders if the kitchen of the premises is located on or above ground floor
level;
(c) LPG cylinders should not be installed in commercial premises to supply
fixed gas appliances for catering purposes unless a central LPG, or Towngas,
supply is unavailable;
2.2 The following fuels may be used in kitchens of premises without any restriction:
(a) Electricity;
(b) Towngas or Towngas (Synthetic Natural Gas (SNG))
2.3 The following fuels may be used in kitchens of the premises subject to the
conditions stipulated for fire safety. There may be other requirements relating to
smoke emission control in which respect the approval of Director of Environmental
Protection should be obtained.
(a) Solid fuels such as wood and coal;
(b) Liquid fuels such as diesel and kerosene;
(c) LPG in aggregate quantity below 130 litres water capacity, the kitchen of
the premise should be located on or above ground floor level and the ‘Gas
Utilisation Guidance Note 6’ prepared by the Gas Authority to be complied
with.
3. Electricity
3.1 The electrical system shall be designed and installed by contractors, which are
certificated by the Director of Electrical and Mechanical Services.
21
3.2 The materials used and safety devices installed shall conform to the legal
requirements and as specified by the respective power companies. In particular:
(a) Each item of fixed electric catering equipment shall be provided with a
readily accessible electric isolator/switch to cut off all live conductors in the
event of emergency. These isolators/switches shall be clearly identified in
English and Chinese and by letters and characters as large as practicable
which items of equipment they control;
(b) All electrical wiring to fixed electric catering equipment shall be installed
within metal conduit and/or trunking systems to provide protection from
mechanical damage. As an alternative to protect short lengths, flexible
conduit to BS 731 Part I may be acceptable.
3.3 The installation shall be inspected and a stability certificate issued by the respective
power company or a registered electrical worker/ contractor certificated by the
Director of Electrical and Mechanical Services. This certificate shall be
forwarded to the Licensing Authority as proof of compliance.
4. Towngas/Towngas (Synthetic Natural Gas (SNG) / Liquefied Petroleum Gas (LPG))
4.1 The existing Towngas/LPG installation shall be overhauled by Towngas
Co./registered gas contractor*. A copy of the job card, completed by the contractor to
this effect, shall be submitted to the Licensing Authority. The overhaul must include a
soundness test of the gas installation at normal working pressure, the servicing of gas
appliances to ensure correctness of operation; and a check for adequate ventilation.
4.2 The Towngas/LPG installation shall be installed by Towngas Co./registered gas
contractor* and the attached certificates shall be completed by the contractor and
submitted to the Licensing Authority through the applicant in the following
manner :-
(a) Certificate of Compliance -- To be submitted before in stallation
Work is carried out.
(b) Certificate of Completion -- To be submitted after installation
work is completed and/or in
commission.
4.3 The alteration to the Towgas/LPG installation shall be carried out by Towngas
Co./registered gas contractor* and the attached certificates shall be completed by
the contractor and submitted to the Licensing Authority through the applicant in
the following manner.
(a) Certificate of Compliance -- To be submitted before alteration
work is carried out.
(b) Certificate of Completion -- To be submitted after alteration
work is completed and/or in
Commission
* who shall employ installers registered for relevant classes of work (i.e. Class 5, 6, 7)
22
5. Solid Fuels
5.1 A chimney shall be erected and provide with :
(a) An inspection door at the bottom; and
(b) A spark arrestor constructed of wire gauze having an aperture size not
greater than 1.25mm.
6. Diesel
6.1 The service tank shall not be more than 500 litres maximum capacity.
6.2 The service tank should preferably be located in open air. Where this is not
practicable, it shall be contained in a separate room constructed of walls of solid
brick of 100mm thick or 75mm reinforced concrete to give a fire resisting period
(FRP) of one hour, and provided with a sill, a bund wall or metal tray forming a
retaining space of sufficient capacity to hold the entire contents in the event of a
leakage or fire.
6.3 A robust gauge shall be provided for measuring the contents of the service tank.
Glass type gauges shall not be used.
6.4 The oil supply pipe to the burner(s) shall be fitted with a remote control valve at an
easily accessible location outside the kitchen, clearly indicated in English and
Chinese and in capital letters and characters as large as practicable.
6.5 A catchment of metal tray shall be provided under each burner.
6.6 A chimney shall be erected and provided with:
(a) An inspection door at the bottom; and
(b) Sufficient access to the ducting for regular removal of the accumulated
grease.
7. Kerosene
7.1 The capacity of this system shall not exceed 20 litres and a separate licensable store
shall be provided for any additional supply in excess of this quantity.
7.2 If the system incorporates a pressure vessel :
(a) The pressure vessel shall be provided with;
(i) a pressure gauge,
(ii) a pressure release valve, and
(iii) a safety valve
(b) The pressure vessel shall be separated from the burners;
23
(c) Only copper piping shall be used to connect the pressure vessel and the
burner(s). The piping shall be;
(i) fixed to the walls except the length of 600mm from the burner which
shall be arranged in a flexible coil to allow cleaning.
(ii) fitted with a stop valve at either end.
(d) The pressure vessel and all burners shall be installed in fixed positions to
prevent accidental overturning when is use;
7.3 If the system incorporates an electric pump:
(a) The kerosene container shall be;
(i) bounded or placed in metal tray so as to form a retaining space of
sufficient cubic capacity to hold the entire contents; and
(ii) provided with 3mm self-closing lid.
(b) The electric pump shall be ;
(i) separated from the burners; and
(ii) provided with an independent switch at an easily accessible location.
The “ON/OFF” positions shall be clearly identified in English and
Chinese and by capital letters and characters as large as practicable.
(c) Only copper piping shall be used to connect the electric pump and the
burner(s). The piping shall be:
(i) fixed to the walls except the length of 600mm from the burner which
shall be arranged in a flexible coil to allow cleaning; and
(ii) fitted with on/off tap on either end.
(d) A catchment or metal tray shall be provided under the burner(s).
8. Fuel for food warming and water boiling outside kitchen
8.1 On compliance with the requirements stipulated in paras. 3 and 4 above, electricity,
towngas and LPG in piped supply may be used for food warming and water boiling
outside kitchen. Cooking shall be carried out inside kitchen.
24
Annex E of Part II
Requirements for various fuels used in seating accommodation
1. Scope
This document specifies the various fuels that may be used in seating accommodation of the
premises serving barbecue food and/or hot pot and prescribes the relevant fire safety
requirements.
2. Restriction
2.1 The following fuels are not permitted for use in seating accommodation:
(a) Solids such as fire wood and coal;
(b) Liquids such as diesel and kerosene;
(c) LPG in any quantity if the premises are located on any floor below ground
floor level;
2.2 The following fuels are permitted for use in seating accommodation:
(a) Electricity;
(b) Towngas/Towngas (Synthetic Natural Gas (SNG));
(c) LPG in piped supply if the premises are located on or above ground level
where;
(i) the gas is supplied through a central system or (ii) suitable space is available for the construction of a dangerous goods
store for LPG cylinders to provide piped supply.
(d) LPG in cartridge type cylinders each does not contain more than 500 grams
of LPG if the premises are located on or above ground floor level.
3. Electricity
3.1 The electrical system shall be designed and installed by contractors:
(a) Registered either by the China Light and Power Company Limited or the
Hong Kong Electrical Company Limited; or
(b) Certificated by the Director of Electrical and Mechanical Services.
3.2 The materials used and safety devices installed shall conform to the legal
requirements and as specified by the respective power companies. In particular:
25
(a) Every electric circuit containing sockets for use with catering equipment
shall be protected by,
(i) A residual current device of sensitivity not exceeding 30mA, and (ii) fixed or flexible conduit against mechanical damage.
(b) The wiring between the plug ad the catering equipment shall be carried out
in heat resistant cable.
(c) an over-temperature cut out thermostat shall be fitted to every catering
equipment using oil/fat as cooking medium, to prevent these from reaching
flash point temperature.
(d) The catering equipment shall be securely fixed to the tables and suitably
isolated to avoid igniting the surrounding combustibles.
3.3 The installation shall be inspected and stability certificate issued by the respective
power company or a registered electrical worker/contractor certificated by the
Director of Electrical and Mechanical Services. This certificate shall be
forwarded to the Office of the Licensing Authority as proof of compliance.
4. Towngas/Towngas (Synthetic Natural Gas (SNG)/Liquefied Petroleum Gas (LPG))
4.1 The existing Towngas / LPG installation shall be overhauled by Towngas Co./
registered gas contractor*. A copy of the job card completed by the contractor to
this effect, shall be submitted to the Licensing Authority. The overhaul must
include a soundness test of the gas installation at normal working pressure, the
servicing of gas appliances to ensure correctness of operation; and a check for
adequate ventilation.
4.2 The Towngas / LPG installation shall be installed by Towngas Co./ registered gas
contractor* and the attached certificates shall be completed by the contractor and
submitted to the Licensing Authority through the applicant in the following
manner :-
(a) Certificate of Compliance - To be submitted before installation
work is carried out.
(b) Certificate of Completion - To be submitted after installation
work is completed and/or in
Commission
26
4.3 The alteration to the Towngas / LPG installation shall be carried out by Towngas
Co./ registered gas contractor* and the attached certificates shall be completed by
the contractor and submitted to the Licensing Authority through the applicant in the
following manner.
(a) Certificate of Compliance - To be submitted before alteration
work is carried out.
(b) Certificate of Completion - To be submitted after alteration work
is completed and/or in commission
* who shall employ installers registered for relevant classes for work (i.e. class 5, 6, 7)
27
28
29
30
31
Part III
Annex E
Requirements for Access Panel
1. Acceptable Designs
1.1 Option A
(a) The access panel should have minimum clear dimensions of 1.8m in height measuring
from the ground and 0.5m in width.
(b) The access panel should be constructed to open both ways.
(c) Only electrical locking device can be installed in the access panel. The locking device
should be capable of automatic release upon actuation of a smoke detection system or
the operation of an alarm System. An additional manual fire alarm operation switch
should be provided in a safe and convenient position so that the lock should be released
when this alarm is actuated. Upon power failure, The lock should also be released
automatically.
(d) A movable sofa can be located fronting an access panel subject to:
(i) the sofa not exceeding 1m in width with an overall height not exceeding 0.9m; and
(ii) Sufficient space being provided for maneuvering the movable sofa so as to avoid
obstructing the exit route through the access panel.
1.2 Option B
(a) An access opening between two entertainment rooms should be provided above
permanently fixed sofas. It should have a minimum clear height of 1.1m and
minimum clear width of 0.7m and should not be more than 0.65m above the seat level
of the sofas.
(b) The access panel should capable of 180O swing to avoid causing obstruction. A swing
of not less than 90O after fully open is acceptable if the hinges of the panel are adjacent
to the corner of the room.
32
(c) For safe evacuation, the access panel and the opening should be surrounded with soft
material and the panel should be of lightweight hollow construction.
(d) Only electrical locking device can be installed in the access panel. The locking device
should be capable of automatic release upon actuation of a smoke detection system or
the operation of an alarm system. An additional manual fire alarm operation switch
should be provided in a safe and convenient position so that the lock should be released
when this alarm is actuated. Upon power failure, the lock should also be released
automatically.
33
Part III
Annex F
Signs and Notices for Emergency Exit Door and
Access Panel Required under Paragraph 9
of the Guidelines on building Safety Requirements
1. Emergency Exit Door under Paragraph 9(a)(ii) of the Guidelines
(a) For emergency exit door serving entertainment rooms on both sides, it should be
provided with a notice on both sides stating in English and Chinese characters, not less
than 10mm high, as follows :
Double-swing Emergency Exit Door
Push SLOWLY or Pull to Open
Upon Operation of Fire Alarm
雙向方式開啟的緊急出口門
火警警報系統啟動後
拉開或輕輕推開
(b) For emergency exit door serving one entertainment rooms, it should be provided with a notice on both sides stating in English and Chinese characters, not less than 10mm high, as follow :
(i) on the side tacing the entertainment room in a dead-end corridor –
Emergency Exit Door
Push SLOWLY or Pull to Open
Upon Operation of Fire Alarm
緊急出口門
火警警報系統啟動後
拉開或輕輕推開
(ii) on the other side –
Double-swing Emergency Exit Door
For the Room Behind
雙向方式開啟的緊急出口門
供隔壁的房間使用
(c) An exit sign bearing the wording “Exit Door” and “出口門” not less than 25mm high should be provided within the entertainment room to indicate the emergency exit door serving as a second exit.
34
(d) An exit sign bearing the wording “To Exit Door” and “往出口門” not less than 25mm
high should be provided outside such entertainment rooms at the dead-end corridors to
indicate the availability of a second exit serving other entertainment rooms.
2. Access Panel under Option A of Annex E
(a) For access panel serving entertainment rooms on both sides, it should be provided with
a notice on both sides stating in English and Chinese characters, not less than 10mm
high, as follow :
Double-swing Emergency Access Panel
Push SLOWLY or Pull to Open
Upon Operation of Fire Alarm
雙向方式開啟的緊急的通道門
火警警報系統啟動後
拉開或輕輕推開
(b) For access panel serving only one entertainment room, it should be provided with
notices stating in English and Chinese characters, not less than 10mm high, as follow :
(i) On the side facing the entertainment room in a dead-end corridor –
Emergency Access Panel
Push SLOWLY or Pull to Open
Upon Operation of Fire Alarm
緊急通道門
火警警報系統啟動後
拉開或輕輕推開
(ii) on the other side –
Double-swing Emergency Access Panel
For the Room Behind
雙向方式開啟的緊急處道門
供隔壁的房間使用
(c) An exit sign bearing the wording “Access Panel” and “通道門” not less than 25mm high
should be provided within the entertainment room to indicate the access panel serving
as a second exit.
35
(d) An exit sign bearing the wording “To Access Panel” and “往通道門” not less than
25mm high should be provided outside every such entertainment rooms at the dead-end
corridor to indicate the availability of access panel serving other entertainment rooms
for the purposes of paragraph 9(b) of the Guidelines.
3. Access Panel under Option B of Annex E
(a) For access panel serving entertainment rooms on both sides, it should be provided
with notices stating in English and Chinese characters, not less than 10mm high, as
follow :
(i) single-swing access panel
� on the side open in the direction of exit –
Emergency Access Panel
Push SLOWLY or Open
Upon Operation of Fire Alarm
緊急通道門
火警警報系統啟動後
輕輕推開
� on the other side –
Emergency Access Panel
For this Room and the Room Behind
(Open towards this Room)
Pull to Open
Upon Operation of Fire Alarm
向此房間開啟的緊急通道門
供這間房間及隔壁房間使用
火警善報系統啟動後拉開
(ii) double-swing access panel
Double-swing Emergency Access Panel
Push SLOWLY or Pull to open
Upon Operation of Fire Alarm
雙向方式開啟的緊急的通道門
火警警報系統啟動後
拉開或輕輕推開
36
(b) For access panel serving only one entertainment room, it should be provided with
notices stating in English and Chinese characters, not less than 10mm high, as follows :
(i) single-swing access panel open in the direction of exit –
� on the side facing the entertainment room in a dead-end corridor –
Emergency Access Panel
Push SLOWLY or Open
Upon Operation of Fire Alarm
緊急通道門
火警警報系統啟動後
輕輕推開
� on the other side –
Emergency Access Panel
For the Room Behind
(Open towards this Room
Upon Operation of Fire Alarm)
火警警報系統啟動後
向此房間開啟的緊急通道門
(供隔壁的房間使用 )
(ii) single-swing access panel not open in the direction of exit-
� on the side facing the entertainment room in a dead-end corridor-
Emergency Access Panel
Pull to Open
Upon Operation of Fire Alarm
緊急通道門
火警警報系統啟動後
拉開
� on the other side-
Emergency Access Panel
For the Room Behind
緊急通道門
供隔壁的房間使用
37
(iii) double-swing access panel
� on the side facing the entertainment room in a dead-end corridor-
Emergency Access Panel
Push SLOWLY or Open
Upon Operation of Fire Alarm
緊急通道門
火警警報系統啟動後
拉開或輕輕推開
� on the side facing the other room-
Double-swing Emergency Access Panel
For the Room Behind
雙向方式開啟的緊急的通道門
供隔壁的房間使用
(c) An exit sign bearing the wording “Access Panel” and “通道門” not less than 25mm high
should be provided within the entertainment room to indicate the access panel serving as a second exit.
(d) An exit sign bearing the wording “To Access Panel” and “往通道門” not less than
25mm high should be provided outside every such entertainment rooms at the dead-end corridors to indicate the availability of access panel serving other entertainment rooms for the purposes of paragraph 9(b) of the Guidelines.
4. The exit signs required under paragraphs 1 (c) & (d), 2 (c) & (d) and 3(d) & (e) should be internally illuminated bearing the word in English and Chinese as depicted in the aforesaid paragraphs. The letter style shall be in “Helvetica” or ‘Marigold’ or ‘Modified Garamond’ while the Chinese character shall be with width of vertical strokes 3mm and with width of horizontal strokes not less than 2mm. Exit sign shall be connected to both mains and emergency power supply. If the establishment is not equipped with an emergency generator, the exit sign shall be provided with secondary battery in accordance with British Standard 5266: Part1. Color contrast for translucent surrounds to lettering shall be as follows :
Color Contrasting Color
Green White
White Green
The Color combination selected shall be consistent throughout the same establishment.