Prepared for: Theodore Babiak Prepared by: Bob Papadopoulos P.Eng., RHI* www.redbrickinspections.ca [email protected] 416-829-6655 Please Read: http://redbrickinspections.ca/docs/1_Introduction_Reference_Guide.pdf *please see credentials at end of report HOME INSPECTION REPORT Inspection Date: Aug 10 2020 124 Westminster Ave Toronto
Transcript
Page 1: HOME INSPECTION REPORTbabiakteam.com/theodorebabiak/custom_WebPage_Files... · 124 Westminster Ave page 1 SIGNIFICANT ITEMS This page should not be considered as the complete report.

Prepared for: Theodore Babiak

Prepared by: Bob Papadopoulos P.Eng., RHI*

www.redbrickinspections.ca

[email protected]

416-829-6655

Please Read: http://redbrickinspections.ca/docs/1_Introduction_Reference_Guide.pdf

*please see credentials at end of report

HOME INSPECTION REPORT

Inspection Date: Aug 10 2020

124 Westminster Ave

Toronto

Page 2: HOME INSPECTION REPORTbabiakteam.com/theodorebabiak/custom_WebPage_Files... · 124 Westminster Ave page 1 SIGNIFICANT ITEMS This page should not be considered as the complete report.

124 Westminster Ave page 1

SIGNIFICANT ITEMSThis page should not be considered as the complete report. For the purposes of this report,

Please read all other forms contained within the Home the front of the house is considered

Inspection Report to be facing:

ROOFING

EXTERIOR

STRUCTURE

ELECTRICAL

HEATING

COOLING/HEAT PUMPS

INSULATION/VENTILATION

PLUMBING

INTERIOR

* * * * P * * * *

Below Typical Typical Above Typical

Aug 10 2020

The following rating reflects both the original quality of construction and the overall current condition of the

home, based on a comparison to similar homes.

OVERALL RATING

Toronto SUMMARY

South

Approx. 10-yr-old high quality asphalt shingles with a typical life expectancy of 30-yrs.

The garage shingles are older- replace within 1-yr.

The 100 AMP service size is presently adequate. In addition to upgraded wiring there is

knob and tube wiring-please see details.

Restricted access to roof and wall spaces therefore insulation not determined.

Overall well maintained. See details for general repairs and maintenance.

Overall adequate water pressure. In addition to copper there is galvanized steel supply

piping which should be replaced. Further evaluation to basement and main waste drain.

The washrooms and kitchen are older though overall in good repair.

Overall well maintained. Many windows have been upgraded. There is evidence of

basement dampness - please see details.

14-yr-old gas-fired hot-water boiler with a typical life expectancy of 20-yrs.

none

Overall well built house.

Prior to reviewing the Home Inspection Report please read the Terms and Conditions of the Home Inspection

and the Standards of Practice of the Canadian Association of Home and Property Inspectors available online

at www.redbrickinspections.ca.

Page 3: HOME INSPECTION REPORTbabiakteam.com/theodorebabiak/custom_WebPage_Files... · 124 Westminster Ave page 1 SIGNIFICANT ITEMS This page should not be considered as the complete report.

124 Westminster Ave ROOFING/Chimneys page 2

Description

Roofing Material: Location: Leakage Probability:

Limitations

Roof Inspected By: Chimney Access Limited By:

Observations/Recommendations

majority of shingles in good repair

loose shingles on southwest side require repairs

rebuilt at top, central brick have surface spalling - monitor and repair as required

old shingles, replace within 1-yr

Note: Recommend Annual Maintenance Contract for Roof Surface, Flashing Details and Chimney(s)

http://redbrickinspections.ca/docs/2_Roofing_Reference_Guide.pdf

Chimney(s):

Binoculars

West Medium

Location:

Asphalt Shingles:

Asphalt Shingles: Garage:

Slope:

Aug 10 2020

Chimney(s) Type:

Brick:

Height

Access Limited By:

Height

Garage:

Sloped Surface:

High

Page 4: HOME INSPECTION REPORTbabiakteam.com/theodorebabiak/custom_WebPage_Files... · 124 Westminster Ave page 1 SIGNIFICANT ITEMS This page should not be considered as the complete report.

124 Westminster Ave page 3

Description

Gutters & Downspouts: Lot Topography:

Limitations

Observations/Recommendations

maintenance, extend 6-ft away from house

overall in good repair- budget to replace with metal siding

overall in good repair

overall in good repair, budget for painting

requires general repairs and maintenance

overall in good repair, paint wood components as required

rear porch: column rotted at base- repair

requires maintenance/repairs, recommend installing gutters/downspouts,

car door replacements

Note: Maintain Gutters & Downspouts annually. Extend Downspouts at least 6-feet away from the house

** Any or all these items may contribute to Basement Leakage. Please see Interior Form

http://redbrickinspections.ca/docs/3_Exterior_Reference_Guide.pdf

WALL SURFACES:

Insulbrick:

Brick:

Wood Shingles:

Soffit & Facia:

PORCH

DETACHED GARAGE:

Walls & Wall Structures:

FlatAluminum:

Galvanized Steel:

Downspout(s) Discharge:

Aug 10 2020

Exterior Inspection from Ground Level

Brick

Wood Shingles

Asphalt Shingles

DOORS/WINDOWS:

Below/Above Grade

EXTERIOR

**Gutters/Downspouts:

Page 5: HOME INSPECTION REPORTbabiakteam.com/theodorebabiak/custom_WebPage_Files... · 124 Westminster Ave page 1 SIGNIFICANT ITEMS This page should not be considered as the complete report.

124 Westminster Ave page 4

Description

Configuration: Foundations: Floor : Walls : Roof/Ceiling Framing:

Limitations

Foundation Wall Not Visible: 80 %

Observations/Recommendations

overall well built house

exterior rear under porch: typical mortar maintenance

exterior east: general repairs to parging

minor surface spalling on west side not critical

http://redbrickinspections.ca/docs/4_Structure_Reference_Guide.pdf

FOUNDATIONS:

Wood Frame (Siding)

Masonry:

WALLS:

Aug 10 2020STRUCTURE

Basement: Stone No Access

Wall Space

Masonry (Double-Brick)

Restricted Access to:

Wood Joists

Roof Space

Page 6: HOME INSPECTION REPORTbabiakteam.com/theodorebabiak/custom_WebPage_Files... · 124 Westminster Ave page 1 SIGNIFICANT ITEMS This page should not be considered as the complete report.

124 Westminster Ave page 5

Description

AMP (240volts) Service Entrance Cable: Distribution Wire:

Main Disconnect/Service Box Location:

Rating: 100 AMP Type of material:

Description:

Location:

Distribution Panel System Grounding:

Rating: 100 AMP Description:

Description: Location: Ground Fault Circuit Interrupter:

Location: Location:

Auxiliary Panel(s): Outlets

Rating: AMP Description:

Description: Number of Outlets: Arc Fault Circuit Interrupter:

Location: Location:

Limitations

Observations/Recommendations

crowded though overall in good repair

install larger 200 amp panel if renovating

based on random sampling observed in majority of house,

upgrade for insurance purposes and/or when renovating

for insurance option contact David Slack 1-800-971-1363 of David Slack

Insurance Brokers Ltd.

provide to exterior outlet

provide to washroom outlet

Note 1: All recommendations are safety issues - Treat them as high priority.

Note 2: Please ensure accurate labelling on panels.

http://redbrickinspections.ca/docs/5_Electrical_Reference_Guide.pdf

Breakers

GFCI:

SERVICE PANEL:

Basement

Grounded & Ungrounded

Knob-and-Tube-Copper

ELECTRICAL

Overhead

Not Visible

Copper

Water Pipe

Copper

Service Size:

BRANCH WIRING:

Breakers

Basement

Aug 10 2020

100

Grounded/Ungrounded

Minimal

Bathroom(s)

Main Disconnect Cover Not Removed

Page 7: HOME INSPECTION REPORTbabiakteam.com/theodorebabiak/custom_WebPage_Files... · 124 Westminster Ave page 1 SIGNIFICANT ITEMS This page should not be considered as the complete report.

124 Westminster Ave page 6

Description

Description: Efficiency: Approx. Age: Life Expectancy: Fuel: Shut Off at:

136 14 yrs. 20 yrs.

Limitations

Observations/Recommendations

service annually

typical corrosion of heat exchanger

annual CO test mandatory for this type of unit

automatic damper requires servicing

service annually

abandoned in basement- typically belonged to an oil tank

that has been removed

old - replace

http://redbrickinspections.ca/docs/6_Heating_Reference_Guide.pdf

HOT WATER BOILER:

Hot Water Boiler:

Electric Heater(s):

Mid

Heat Loss Calculations Not Done Summer Test Procedure

Exhaust Vent Arrangement: Metal Through Masonry Chimney

ELECTRIC HEATERS(s):

Radiator(s):

Oil Piping:

x1000BTU/hr Gas

Heat Exchanger- Limited Access

Meter-Exterior

Aug 10 2020

Boiler Performance

Pressure lbs/in2: 14

HEATING

Rated Input:

Page 8: HOME INSPECTION REPORTbabiakteam.com/theodorebabiak/custom_WebPage_Files... · 124 Westminster Ave page 1 SIGNIFICANT ITEMS This page should not be considered as the complete report.

124 Westminster Ave COOLING/Heat Pumps page 7

Description

Description: Cooling Capacity: Approx. Age: Typical Life Expectancy:

yrs.

Limitations Cooling Performance

Observations/Recommendations

http://redbrickinspections.ca/docs/7_AC_Heat_Pump_Reference_Guide.pdf

x1,000 BTU/hr yrs. old

Supply Temp F:

Return Temp F:

: none

Aug 10 2020

Page 9: HOME INSPECTION REPORTbabiakteam.com/theodorebabiak/custom_WebPage_Files... · 124 Westminster Ave page 1 SIGNIFICANT ITEMS This page should not be considered as the complete report.

124 Westminster Ave INSULATION/VENTILATION page 8

Description

Material: Location

Limitations

Observations/Recommendations

provide for 2nd level washroom

Note: adding insulation is considered an improvement rather than a repair

http://redbrickinspections.ca/docs/8_Insulation_Ventilation_Reference_Guide.pdf

Air/Vapour Barrier:

Access Not Gained To Wall Space

Roof

Access Not Gained To Roof Space

Venting:

Aug 10 2020

R-Value

Exhaust Fan Vents:

Page 10: HOME INSPECTION REPORTbabiakteam.com/theodorebabiak/custom_WebPage_Files... · 124 Westminster Ave page 1 SIGNIFICANT ITEMS This page should not be considered as the complete report.

124 Westminster Ave page 9

Description

Service Piping into House: Main Shut Off Valve at: Water Flow (Pressure):

Supply Piping & Pump(s): Waste Piping & Pump(s): Water Heater

Type:

Fuel Type:

Capacity:

Age Yrs.: 2

Life Expectancy: 15

Limitations

Observations/Recommendations

corroded connections, overall should be replaced and might be required for

insurance purposes

exterior walls: stacks should be replaced with larger size piping and

extended above roof line though relocating to interior when renovating

recommended

main floor drain not found- further evaluation - install with

backflow valve to main waste drain

note: floor drain in basement washroom does not have a trap and

appears to be an access to main drain

whirlpool not tested, service before use, install GFCI for safety

older though overall in good repair

older though overall in good repair

http://redbrickinspections.ca/docs/9_Plumbing_Reference_Guide.pdf

Galvanized Steel:

Venting:

Copper

Plastic

Cast Iron

Basement Washroom:

SUPPLY PIPING:

Basement Floor Drain:

Galvanized Steel

Isolating/Relief Valves & Main Shut Off Valves Not Tested

WASTE PIPING:

Kitchen(s)

2nd Level Washroom:

Adequate

PLUMBING

Kitchen and Laundry Appliances Were Not Inspected

Basement-Front

Aug 10 2020

Tub/Sink Overflows Not Tested

Concealed Plumbing not Inspected

Copper

Conventional

Gas

40 Gal

Page 11: HOME INSPECTION REPORTbabiakteam.com/theodorebabiak/custom_WebPage_Files... · 124 Westminster Ave page 1 SIGNIFICANT ITEMS This page should not be considered as the complete report.

124 Westminster Ave page 10

Description

Floor Finishes: Wall Finishes: Ceiling Finishes: Windows: Exterior Doors:

Limitations

Restricted/No Access To: Foundation Not Visible 80 %

CO Detectors, Security Systems, Central Vacuum, Chimney Flues Not Inspected Drainage Tile Not Visible

Observations/Recommendations

basement: minor damage to laminate floor form prior pipe leak

overall in good repair

overall in good repair

various upgraded units, upgrade older units as required

contact specialist for options

typical efflorescence, staining and dampness for older foundation

moisture meter indicates dampness along drywall

long term moisture may result in visible or concealed mould growth.

overall recommend damp-proofing when renovating

see steps below

CO/Smoke detectors: please ensure one per level each with annual maintenance, this is a life

safety concern and mandatory by law

** Steps recommended in order to minimize basement leakage

1. gutters, downspouts, grading, driveways: ongoing maintenance and repair/see Exterior

2. cracks/form ties on foundation: monitor/repair as required

3. excavation/damp-proofing: monitor basement, consider step 3 as a last resort

Environmental/Health Concerns: http://redbrickinspections.ca/docs/11_Environmental_Reference_Guide.pdf

http://redbrickinspections.ca/docs/10_Interior_Reference_Guide.pdf

Fireplace Fuel:Fireplaces:

Laminate

Wood

Fireplaces:

**Basement Leakage:

Floors:

Resilient

Window(s):

Non-Functional

Trim/Cabinets/Counters:

Floors/Walls/Ceilings:

Plaster/Drywall Plaster/Drywall Single/Double Hung Wood

Paneling Fixed

Double Glazing

Primary Plus Storm

Paneling

INTERIOR Aug 10 2020

Page 12: HOME INSPECTION REPORTbabiakteam.com/theodorebabiak/custom_WebPage_Files... · 124 Westminster Ave page 1 SIGNIFICANT ITEMS This page should not be considered as the complete report.

Bob Papadopoulos P.Eng, RHI

• Over 20 years of building inspecting experience in Toronto and the GTA

• Over 5,000 residential and commercial buildings inspected

Professional Designations

• P.Eng. (Professional Engineer of Ontario)

• RHI Registered Home Inspector

• Certified Energy Auditor

http://www.oahi.com/

http://www.peo.on.ca/

Bob has inspected over 5,000 residential and commercial buildings of various

descriptions and reporting on conditions of major systems including structure,

building envelope and mechanical systems, specific problem investigations and

pre-renovation inspections. In the past Bob has helped train Home Inspectors

and assisted in the creation of educational courses on home inspecting as well

as taught Home Inspection courses at Seneca College. Bob also has experience

in the construction industry inspecting many large scale projects through-out the

GTA. He also served in the Canadian Navy as a Marine Mechanic and Ships

Team Diver.


Recommended