Date post: | 17-Feb-2016 |
Category: |
Documents |
Upload: | anonymous-dhlfezuhba |
View: | 92 times |
Download: | 11 times |
CENTRIFUGAL PUMPS
F a c t o r y A d d r e s s : C o r p o r a t e A d d r e s s :
A-5, Sector XXII, Meerut road, WPIL Limited
Ghaziabad – 201002, (U.P), India Trinity Plaza,3rd
floor
Phone:+91-120-3015784 84/1 a, Topsia road (south)
Kolkata 700046, India
1
WPE ES IOM Manual
2
1 . I N T R O D U C T I O N2 . P U M P E R E C T I O N3 . C O M M I S I O N I N G4 . M A I N T E N A N C E5 . S E C T I O N A L D R A W I N G6 . B I L L O F M A T E R I A L7 . C A U S E O F F A I L U R E8 . P O S S I B L E C A U S E9 . G U A R A N T E E C A R D
WPIL designs are being regularly
improved and are thus subject to
changes.The pumps designed as
per customer’s requirement will
not exactly match data provided in
this manual.
2
WPE ES IOM Manual
3
I N T R O D U C T I O N P r e f a c e
The booklet covers the instructions for the following models of W P E pumps.
Brg.Frame unit Pump models
15 11 32/130,40/130,50/130,65/130,32/200,40/200,50/200,65/200
12 32/160,40/160,50/160,65/160,80/160,32/260,40/260,50/260
18 80/200,100/200,65/260,80/260,100/260,125/260,40/320,50/320,65/320,80/320,100/320
22 150/260,125/320,150/320,100/400,125/400,150/400
� This manual contains important and useful information for the proper
functioning and maintenance of this pump. It also contains important
instructions to prevent possible accidents and serious damage and to
ensure the safe and smooth functioning of this pump.
� Read this manual carefully before commissioning the pump. Familiarize
your self with the operation of the pump and strictly obey the
instructions!
G u a r a n t e e W P I L shall not be bound to any Guarantee other than the guarantee
accepted by W P I L. In particular, W P I L
will not assume any liability for
explicit and/ or suitability of the articles supplied.
The guarantee shall forthwith and legally defunct in case:
� Service and/ or maintenance has not been carried out strictly in
accordance with the instructions.
� Installations and/ or commissioning has not been carried out in
accordance with the instructions.
� Necessary repairs have not been carried out by our personal or have
been carried out without our prior written consent.
� The articles supplied have been changed without our prior written
consent.
� The spare parts used are not original WPIL Pump parts.
� The articles supplied are used amateurishly, carelessly, improperly
and/or negligently.
� The articles supplied become defective due to out side circumstances
beyond our control.
Furthermore, all deliveries are subject our “G e n e r a l c o n d i t i o n s o f d e l i v e r ya n d p a y m e n t
“, which will be forwarded to you, free of charge and request.
I n s p e c t i o n o f d e l i v e r e d i t e m s
� Check the consignment immediately on arrival for damage and
conformity with the advice note.
� In case of damage and/or missing parts, have a report drawn up by the
carrier at once.
3
WPE ES IOM Manual
4
L i f t i n g If a pump or a complete pump unit has to be lifted, the slings should be fixed
as shown in figure 1. And figure 2.
F i g u r e 1
.
F i g u r e 2
N o t e : P r o p e r c a r e s h o u l d b e t a k e n t o p r o t e c t p u m p a n d / o r p r i m e m o v e r a n d / o rp a i n t a t c o n t a c t a r e a o f s l i n g o r r o p e a t t h e t i m e o f l i f t i n g.
4
WPE ES IOM Manual
5
S t o r a g e
In case the pump is not immediately being used, the pump shaft has to be
rotated manually twice a week.
D E S C R I P T I O N O F T H E P U M P
Every WPIL pump has a name plate giving following details:
While you correspond with us for your
requirements of spare parts or for any
technical information, please always quote
this details in your letter.
C o n s t r u c t i o n a l D e t a i l s :WPIL water pumps are single volute casing pumps with axial suction branch and top
centre line delivery branch. All pumps supported by integrally cast foot in the casing
and all water pumps are centerline mounted.
Bearings are cooled when liquids are handled at temperatures above 100˚c
D i r e c t i o n o f R o t a t i o n Clockwise, pump viewed from driven end.
S u i t a b l e s p e e d s All the WPE models are suitable for the speed of 1450 rpm. Besides that the following
speeds are recommended.
WPIL PUMPS
Ghaziabad
CENTRIFUGAL PUMP
SL.NO : TYPE :
SIZE : MM TOTAL M
HEAD
SPEED: RPM CAPACITY :
M³/HR
DRIVE : HP JOB NO :
Max speed Pump Models
Upto 3600
rpm 32/130,40/130,50/130,65/130,32/160,40/160,50/160,65/160,32/200,40/200
Upto 2900
rpm 50/200,80/160,80/200,100/200,32/260,40/260,50/260,65/260,80/260,100/260
Upto 1800
rpm
125/260,150/260,40/320,50/320,65/320,80/320,100/320,125/320,150/320,
80/400,100/400,125/400,150/400
5
WPE ES IOM Manual
6
P U M P E R E C T I O N 1 . 0
A s s e m b l i n g t h e s e t o n t h e B a s e p l a t e:
1.1 If the assembly of the pump with the driver on a common base plate is done in
our works, the whole set will be carefully mounted and aligned. It is necessary
to check once more the alignment of the coupling before putting the pump
into operation.
The eye bolts which may be fitted to the driver must never be used to lift the
complete set as they are meant to carry the weight of the driver only.
1.2. If you furnish the driver yourselves, the clearance between the motor and pump
coupling halves as shown on the arrangement drawing must be strictly observed.
Difference in level between the shaft centre lines of pump and driver must be
equalized by suitable pickings (plain parallel shims). When the pump and motor
holding – down bolts are finally secured, care must be taken to avoid distortion.
A l i g n m e n t o f c o u p l i n g
� Place a ruler (A) on the coupling. The ruler should touch both coupling halves
across the whole width( see figure ).
� Do the same check against both sides of the coupling near the axis.
� For all security the alignment is also checked with a pair of out side caliper (B) at
2 – diametrically opposite points of the side surfaces of the coupling halves.
A
B
6
WPE ES IOM Manual
7
C O M M I S S I O N I N G
C h e c k p u m p
� Construction with stuffing box: check whether the gland nuts have not been
over tightened. If necessary, loosen the gland nuts and retighten them by
hand.
� Check whether the shaft turns freely. Do this turning the shaft end at the
coupling a few times by hand.
P r e p a r a t i o n o f l u b r i c a t i o n
The bearings of pumps provided with grease-lubricated bearings are filled with
grease at the time of delivery.
Pump provided with oil lubricated bearings are supplied without oil. See the
enclosed chart for specifications of oil to be used.
� Fill the oil sump through the oil filling orifice up to the bottom of the
constant level oiller.
� After that fill the constant level oiller entirely.
P r e p a r i n g t h e u n i t o f c o m m i s s i o n i n g
Proceed as follows, both when the unit is put into operation for the first time
and after the pump has been overhauled.
� Fully open the stop value in the suction pipe. Closed the delivery stop
value.
� Fill the pump and the suction pipe with liquid to be pumped.
� Turn the pump shaft a few times by hand and more liquid, if
necessary.
C h e c k i n g t h e d i r e c t i o n o f r o t a t i o n
� The sense of rotation of the pump is indicated the arrow. Check
whether the sense of rotation of the motor corresponds with that of
the pump.
� Let the motor run for only a short time and check the sense of
rotation.
� If the sense of rotation is not correct, change connecting wire of
motor so as to match with rotation of the pump.
� Mount coupling guard. S t a r t i n g t h e p u m p
� Open the stop valve in the supply piping for flushing for flushing or
cooling liquid, if the pump is supplied with a flushing or cooling
system.
� Start the pump.
7
WPE ES IOM Manual
8
� As soon as the pump is under pressure, slowly open delivery stop
valve until the working pressure is attained. A d j u s t m e n t o f s h a f t s e a l i n g S t u f f i n g B o x P a c k i n g
After the pump is started, the stuffing box will show a certain amount
of leakage. Because of the expansion of the packing fibers, this
leakage will gradually decrease. Make sure that the packing never
runs dry. To prevent this, loosen that gland nut to the extent that the
stuffing box leaks drop wise. As soon as the pump has reached the
proper temperature (and leakage is still too much) the gland can be
adjusted permanently.
� Tighten both gland nuts, one after the other, a quarter turn.
� Wait 15 minutes after each adjustment before making the next
adjustment.
� Continue in this way until an acceptable drop wise leakage has
been attained (20-30 drops/ minutes).
M e c h a n i c a l s e a l� A mechanical seal may never show visible leakage.
C o n t r o l .
If a pump is in operation pay attention to the following:
� The pump should never run dry.
� Never use a stop valve in the suction pipe to control pump capacity.
The stop valve should always be fully opened during operation.
� Check whether the absolute inlet pressure is sufficient, so that no
vapour can be formed.
� Check whether the pressure difference between suction and delivery
pressure corresponds with the specifications for the duty point of the
pump.
D I S M A N T L I N GSince the pumps are offered of back pull out type of design. While
dismantling the pump, casing will remain in its place with the suction and
delivery piping. The rotating
Assembly can be pulled back easily. If spacer coupling is used, then the driver
also
Need not to be removed, enabling easy re-assembling of the pump without
affecting the alignment. We recommend to mach-mark the parts before
removing the spacer so as to ensure the original state of mounting when re-
assembling.
• Drain the liquid handled by the volute casing(C 1) and oil from bearing
bed(C 27).
8
WPE ES IOM Manual
9
• Remove spacer coupling or if there is no such coupling, loosen driver and
move it aside.
• Loosen sealing liquid and coolant pipes if it is there and undo the
fastening bolt on the support foot.
• Undo stud nuts on volute casing (C 1).
• Using the 2 forcing screws on the stuffing box(C 11) with draw the volute
casing..
• After undoing the impeller nut (C 6) withdraw the impeller with gasket.
• After that undo the stuffing box studs from lantern(C 34), withdraw the
stuffing box along with packing, Lantern ring( C 4),Pressure Ring(C 33) and
Gland ( C 13) .
• Remove the Shaft sleeve (C 14).
• Remove the lantern from bearing housing.
• Remove Deflector (C 31 ) and Inner Bearing Cap(C15) from bearing
housing.
• Remove the Outer Bearing Cap(C 20).Remove pump shaft(C 24) with
Bearings towards drive side.A S S E M B L I N G
For assembly proceed with reverse sequence. After mounting the shaft,
check the axial flow of the rotor from 0.01mm to 0.7mm.
If new bearings are mounted on the shaft, they must first to be heated up to
80˚c in an oil bath. The bearings if installed in our works, have normal
clearances, however, use of bearings with C3 play is permissible.
.
L u b r i c a t i o n s
The pump is furnished with two deep groove ball bearings (table 1.) G r e a s e L u b r i c a t i o n s.
The grease lubricated bearing have been lubricated before shipment. For this
bearings following bearing greases are recommended which are available in
the market.G r e a s e S p e c i f i c a t i o n sName of the firm Speed 1450 rpm Speed 2900 rpm/3600 rpm
Indian oil Servo gem 3 Servo gem 2
Caltex Starfak 3 Starfak 2
Hindustan petroleum Natra 3 Natra 2
9
WPE ES IOM Manual
10
Table – 1
The lubrication in Table 1 apply if the temperature is below 70˚C.
Each temperature rise of 15˚C will reduce the lubrication interval to a half.
O i l l u b r i c a t e d b e a r i n g s .� The bearing housing has been emptied of oil prior to shipment and must be
refilled before starting.
� Pour oil in the bearing housing half way up the sight glass.
� During operation the level may slightly fall. Refilling during operation.
� When the pump is put into operation after prolonged shut down, flush
bearings and bearing housing with petrol or benzyl in order to remove
impurities. During the flushing procedure rotate the shaft slowly.
For lubrication of our pumps we recommend the lubricants shown on this lubrication table
O i l C h a n g e
It is recommended that for a new pump the oil should be changed after 100
hours of operation for the first time and thereafter at intervals of 6-12 months add
oil when necessary.
Frame
unit Bearings
Amount
of oil in
liters
Qty of grease for re-
lubr of each bearing
(g)
15 6305 – 2 Nos 0.550 100
18 6307 - 2 Nos 0.700 150
22 6309 - 1 No
3309 – 1 No 0.850 200
Firm
L u b r i c a t i n g o i l f o r T e m p e r a t u r e u p t o 8 0 ˚ CSpeed up to 1500 rpm Speed above 1500 rpm
Indian Oil Servo System 150 Servo system 68, 46
Hindustan Petroleum Esstic 55, Terresso 56 Esstic 50, Terresso 52
Mobil
Mobil Vactra oil Heavy
Mobile D.T.E. oil Heavy
Vac HLP 49
Mobil Vactra oil Medium
Mobile D.T.E. oil Medium
Vac HLP 36
10
WPE ES IOM Manual
11
S T U F F I N G B O X
M a i n t e n a n c e a n d r e - p a c k i n g
When a new pump is being put into service or the stuffing box has just been
re-packed, watch the packing performance more closely than normal. Shut
off the cooling water to the gland (if applicable).
During the first hours, the stuffing box is allowed to leak quite a good deal,
about 100 drops a minute. If the leakage degreases, slack the packing gland.
If you want to reduce the leakage, tighten the packing stepwise at intervals of
about 10 minutes and continue until packing performance is satisfactory. A
small leakage of single drops should be allowed from the stuffing box for
ascertainment of lubrication and of the correct packing tightness. A suitable
leakage is 5 – 30 drops a minute. If the packing cannot be made to seal
without intense tightening, it is best to re-pack. When re-packing remove all
the old packing rings and cleans the stuffing box thoroughly. At the same
time check to see that the water channels are clear and the shaft is free of
warpage and score marks.
When selecting the packing type, observe the quality and temperature of the
liquid being pumped and the shaft sleeve material.
Carefully form the packing into the right shape over the shaft sleeve.
First insert the cut ends into the stuffing box and then push the whole ring to
the bottom of the stuffing box. Put the rings one by one in the stuffing box,
with the cut ends spaced 90 degrees apart. (See figure)
P A C K I N G O F S T U F F I N G B O X:
Frame unit Packing ring
a x d / L in mm
No of packing
ring Size in mm
Total length of
packing in mm
15 8 x 8 x 150 4 (1 x L x 3) 8 600
18 10 x 10 x 188.5 4 (1 x L x 3) 10 754
22 10 x 10 x 220 4 (1 x L x 3) 10 880
ad
11
WPE ES IOM Manual
12
O I L S E A L SS t a n d a r d – DIN 3760
Because of design and
manufacturing tolerances it
is recommended to use
metric Oil seals according
to the following tables.
D a i l y m a i n t e n a n c e
� Regularly check the outlet pressure.
� Bearing Temperature.
� Noise and Vibration.
� Voltage and Current.
� Check the pressure of the flushing liquid. This pressure must be 1.5
bar higher than the pressure at the impeller hub.
S h a f t s e a l i n g
G l a n d p a c k i n g
� Do not tighten the gland nuts any more after the running in period and
adjustment.
� If in time in gland packing starts to leak excessively, new packing rings have to
be mounted instead further tightening the gland nuts. M e c h a n i c a l s e a l
A mechanical seal generally requires no maintenances. However, it should
never be allowed to run dry. If there are no problems it is not advisable to dismantle
the seal as the facing surfaces are running one another. Dismantling always means
replacement of the mechanical seal.
When the mechanical seal is leaking it has to be replaced.
L u b r i c a t i o n o f t h e b e a r i n g
G r e a s e l u b r i c a t e d b e a r i n g s
.
Bearing housings with grease packed deep – groove ball bearings require no
maintenance.. The bearings are filled with grease during assembly. In case the pump
is overhauled, the bearing housing and the bearings have to be cleaned and provided
with new grease.
Frame
unit
Size of Oil seal used in Bearing cap
Drive end Non drive end
15 25 x 37 x 7 25 x 37 x 7
18 35 x 47 x 7 35 x 47 x 7
22 45 x 60 x 10 45 x 60 x 10
12
WPE ES IOM Manual
13
During operation the constant level oiler should never be empty, so take care to top
up timely. The oil should be changed once a year. If the oil temperature is higher
than 80 ˚C, the oil should be change more often.
S E C T I O N A L D R A W I N G
13
WPE ES IOM Manual
14
B I L L O F M A T E R I A L C O D E N O P A R T N A M EW 1 Volute Casing
W 2 * Impeller
W 3 * Stuffing Box
W 4 * Gasket – Shaft/ Sleeve
W 5 * Impeller Nut
W 6 * Impeller Key
W 7 * Lantern Ring
W 8 * Wear Ring
W 9 Casing Drain Plug
W 10 * Gasket - Stuffing Box/Casing
W 11 * Sleeve
W 12 Stud – Gland/Stuffing Box
W 13 * Oil Seal – Inner Bearing Cap
W 14 Plug – Oil Drain
W15 Bearing Bed
W 16 Oil Level Sight Glass
W 17 Support Foot
W 18 Hex Bolt – Support Foot
W 19 Outer Bearing Cap
W 20 * Oil Seal – Outer Bearing Cap
W 21 Key – Coupling
W 22 Shaft
W 23 Hex Bolt – Outer cover/Bed
W 24 * Gaskets – Outer Bearing Cap
W 25 * Bearing - Coupling End
W 26 Vent
W 27 * Bearing – Pump End
W 28 Bearing Cap Inner
W 29 * Deflector
W 30 Gland
W 31 Stud – Bed/Stuffing BOx
W 32 * Gland Packing
W 33 Stud – Stuffing Box / Casing.
*R e c o m m e n d e d s p a r e s f o r 2 y e a r s n o r m a l o p e r a t i o n .
14
WPE ES IOM Manual
15
C A U S E S O F F A I L U R E
In general failures in a pump unit are attributable to the following causes:
� Failures in the pump
� Failures or faults in the piping systems
� Faults due to a wrong installation or commissioning
� Faults due to a wrong pump selections
A number of the most frequently occurring failures as well as their possible causes
are set forth in the below table.
M o s t f r e q u e n t l y o c c u r r i n g f a i l u r e s P o s s i b l e c a u s e sPump doesn't deliver any liquid
1 2 3 4 5 6 7 8 9 10 11 13 14 17 19 20
21 29
Volume flow of the pump is
insufficient
1 2 3 4 5 6 7 8 9 10 11 13 14 17 19 20
21 28 29
The discharge head of the pump is
insufficient 2 4 5 13 14 17 19 28 29
Pump stalls after it has been put into
operation 1 2 3 4 5 6 7 8 9 10 11
The power consumption of the pump
is higher than normal
12 15 16 17 18 22 23 24 25 26 27 32 34
38 39
The power consumption of the pump
is lower than normal 13 14 15 16 17 18 20 21 28 29
The stuffing box is leaking excessively 6 7 23 25 26 30 31 32 33 43
Shaft packing or mechanical seal have
to be replaced to often 6 7 23 25 26 30 31 32 33 34 35 36 41
Pump vibrates or makes noise 1 9 10 11 15 18 19 20 22 23 24 25 26 27
29 37 38 39 40
Bearings wear too soon or gets hot 23 24 25 26 27 37 38 39 40 42
Pump runs with difficulty, gets hot or
stuck 23 24 25 26 27 34 37 38 39 40 42 P o s s i b l e c a u s e s :
1. Pump or suction pipe not sufficiently filled or de-aerated.
2. Gas or air coming from the liquid.
3. Air lock in the suction pipe.
4. Suction pipe leaks air.
5. The pump sucks in air through the stuffing box.
6. The sealing or flush water pipe to the stuffing box is not connected or blocked.
7. The lantern ring in the stuffing box has been mounted wrongly.
8. The manometric suction head is too high.
9. Suction pipe or suction strainer is blocked.
15
WPE ES IOM Manual
16
10. Insufficient immersion of foot valve or suction pipe during operation of the pump.
11. NPSH available too low.
12. Speed too high.
13. Speed too low.
14. Wrong sense of rotation.
15. Pump doesn't work at the right duty point.
16. Liquid density differs from the calculated liquid density.
17. Liquid viscosity differs from the calculated liquid viscosity.
18. Pumps works when the liquid flow is too low.
19. Wrong pump selection.
20. Obstruction in impeller or pump housing.
21. Obstruction in the piping.
22. Wong installation of the pump unit.
23. Pump and motor nor well alignment.
24. Rotating part running out of true.
25. Imbalance in rotating parts (for instance impeller, coupling).
26. Pump shaft is running out of true.
27. Bearing faulty or worn out.
28. Seals rings faulty or worn out.
29. Damaged impeller.
30. Pump shaft or shaft sleeve at shaft packing or running surfaces of the mechanical
seal are worn out or damaged.
31. Worn or dried up shaft packing.
32. Not well packed stuffing box or bad mounting of the mechanical seal.
33. Packing type of the mechanical seal not suitable for the operation liquid or
operation circumstances.
34. Gland of seal cover has been tightened too much or crookedly.
35. No water cooling of stuffing box at high temperatures.
36. The sealing or flushing liquid to the stuffing box or the mechanical seal is polluted.
37. Axial retaining of impeller or pump shaft is defective.
38. The bearings have been mounted wrongly.
39. Too much or too little bearing lubrication.
40. Wrong or polluted lubricant.
41. Impurities in the liquid get into the stuffing box.
42. Too high axial force because worn dorsal blades or excessive inlet pressure.
43. Excessive pressure in packing space due to much play in the smothering bush,
blocked by-pass pipe or worn dorsal blades.
16
WPE ES IOM Manual
17
For any correspondence / ordering spares , please quote the
following
CUSTOMER :
PROJECT :
WPIL REF. :
PUMP MODEL :
PUMP SERIAL NO. :
Contact WPIL
For any complaints and suggestion regarding Pumps
Email us: [email protected]
Phone: +91-120-3015784
Fax : +91-120-3015740
Factory Address :
WPIL LIMITED
A-5, Sector XXII, Meerut road,
Ghaziabad – 201002, (U.P), India
Corporate office address :
WPIL limited
Trinity Plaza, 3rd Floor,
84/1 a, Topsia Road (South)
Kolkata 700046, India
P: +91.33.3021.6800
F:+91.33.3021.6835
17
WPE ES IOM Manual
18
WPIL PUMP BASKET
18
INSTALLATION, OPERATION AND
MAINTENANCE MANUALCENTRIFUGAL PUMPS
TYPE U
Factory Address: Corporate Address:
A-5, Sector XXII, Meerut Road, WPIL Limited
Ghaziabad - 201002, (U.P.), India Trinity Plaza, 3rd Floor,
Phone:+91-120-3015784 84/1 A, Topsia Road (South)
Kolkata 700 046, India
WPIL LTD. [email protected] 201119
What do you want to do?
• Foreword & safety regulations
• Receiving & Checking
• Storage & Shifting
• Preparation for installation
• Installation Procedure
• Pump start-up and operation
• Maintenance of the pump
• Contact Us
Click on the option you need above,
for any further assistance, contact WPIL on
WPIL LTD. [email protected] 201120
Foreword & safety regulations
Foreword & safety regulations
1. Foreword
2. Safety regulations
3. Safety instructions
4. Manufacturer’s regulations
Go Back to Main Menu
WPIL LTD. [email protected] 201121
Receiving & Checking
Receiving & Checking
1. Unloading & inspection.
2. Shortages & damages.
Go Back to Main Menu
WPIL LTD. [email protected] 201122
Storage & Shifting
Storage & Shifting
1. Environmental briefing.
2. Recommended storage procedure.
3. Recommended shifting procedure .
Go Back to Main Menu
WPIL LTD. [email protected] 201123
Preparation for installation
Preparation for installation
1. Required tools, material & equipment.
2. Installation drawings.
3. Preparing the pump foundation.
4. Layout & inspection of pump parts for installation.
5. Hoisting instructions.
6. Layout of pipe work valves and accessories
Go Back to Main Menu
WPIL LTD. [email protected] 201124
Installation Procedure
Installation Procedure
5.1 Leveling & grout type
5.1.1 Leveling of base plate
5.2 Installing the pump assembly
5.3 Couplings
5.3.1 Flexible coupling
5.3.2 Coupling alignment
5.3.2.1 Radial Alignment
5.3.2.2 Angular Alignment
5.3.2.3 Alternative Method for Alignment
5.4 Installing the accessories
5.4.1 Priming connection
5.4.2 Air vent connection
5.4.3 Pressure gauge connections
5.4.4 Stuffing box packing
5.4.5 Mechanical seal
Go Back to Main Menu
WPIL LTD. [email protected] 201125
Pump start-up and operation
Pump start-up and operation
1. Pre-start checks.
2. Important operating instructions.
3. Trouble shooting chart.
Go Back to Main Menu
WPIL LTD. [email protected] 201126
Maintenance of the pump
Maintenance of the pump
7.1 Preventive maintenance table.
7.2 Recommended spare parts & ordering procedure .
7.2.1 Procedure for Odering Spare Part
7.2.2 Recommended list of spare parts subject to most wear
7.2.3 Recommended list of spare parts to be stocked if down time is critical
7.3 Major maintenance of pump.
7.3.1 Packing box assembly/Mechanical Seal
7.3.2 Bearings
7.3.3 Pump assembly (U) removal
7.3.3.1 Complete rotating assembly removal
7.3.3.2 Dismantling of rotor shaft
7.3.3.3 Method of removing dowel bushing
7.3.3.4 Re-Assembly of the rotor assembly
7.3.4 Re-Assembly of the pump unit
7.3.5 Dismantling of Re-Assembly of U pumps
7.3.6 Lubrication chart
WPIL LTD. [email protected] 201127
Maintenance of the pump
7.3.6.1 Recommended grease lubricants
7.3.6.2 Recommended oil lubricants
7.4 Reference drawings, material of construction & technical details.
Go Back to Main Menu
WPIL LTD. [email protected] 201128
FOREWORD
1.1 FOREWORD
This manual provides instructions for installing, operating and maintaining WPIL Horizontal
Centrifugal Pumps. These instructions are written only for those who have a working knowledge of
Horizontal pumps and a familiarity with both the terminology and proper field practices used in
pump industry. Cautions and warnings are included, but they are not substitutes for the careful
work of the experienced.
If installation & maintenance work is neglected, or carried out incorrectly, we will not be able to
fulfill our warranty obligations as agreed and documented in the purchase contract.
Although we used the most current information available at the time this manual was published, all
information contained herein is subject to change without notice. We have made every effort to
avoid errors, but we cannot guarantee that this manual is error-free.
We appreciate your interest in our product. If you have questions about the contents of this manual,
please contact our field service department.
Go Back to Menu
WPIL LTD. [email protected] 2011
By furnishing this manual, WPIL does not
accept liability for successful pump installation,
operation or maintenance; that liability belongs
to those who actuallyinstall, operate and
maintain the pump.
29
SAFETY REGULATIONS
1.2. SAFETY REGULATIONS
This section contains safety regulations which must be always followed when operating our pumps. The regulations are highlighted in the text using the following symbols:
The words WARNING and CAUTION are always in front of the text to which they refer. The word NOTE is after the associated text.
Go Back to Menu
WPIL LTD. [email protected] 2011
WARNING
We wish to point out that we accept no liability for damage and operatrional faults arising from non-adherence to the instructions in the operating and maintenance manual.
=Working safety symbol = “WARNING”
For working and operating procedures which is must.
= CAUTION
To prevent damage to the EQUIPMENT.
30
SAFETY REGULATIONS
It is essential to observe the regulations highlighted this way.
Particular attention must be paid to the safety equipment installed in the pump. If the safety equipment is not working or malfunctioning, the pump must not be operated.
The following instructions for guaranteeing protection at work and safety must be observed:
- Operators must have the necessary specialist knowledge.
- Maintenance work may only be carried out by authorized persons.
- The laws and regulations valid at the place of use must be observed when operating the
pump. In the interest of occupational safety, operators, supervisors and machine operators
are responsible for observing the regulations.
- Perform functional inspections before starting work.
- Tools and other objects may only be kept in their correct places; otherwise they can
jeopardize safe operation.
- Operating media (e.g. oils, lubricants and cleaning agents) for maintenance, servicing and
repair work and oil changes must be collected in suitable containers and disposed of
correctly, (in accordance with statutory guidelines applicable in the country).
- Wear protective gloves when carrying out cleaning work, particularly when using solvents or
petroleum ether. Avoid naked flamers and smoking during cleaning.
Go Back to Menu
WPIL LTD. [email protected] 201131
SAFETY INSTRUCTIONS
1.3. SAFETY INSTRUCTIONS
1. The pumps may only be operated and maintained by persons who are qualified and
competent to operate such machines.
Go Back to Menu
WPIL LTD. [email protected] 2011
WARNING
The electrical machines and units are equipment with an industrial heavy-current connection.
These items of equipment have dangerous conductive with rotating parts during operation.
Serious material or health damage may be caused by removal of safety facilities, incorrect use and wrong operation.
The persons responsible for the pump must therefore guarantee that:
1. Only qualified persons are assigned to work on the pump.
2. This manual is available to operating persons and that they follow it.
3. Non-qualified persons do not operate the pump and are not allowed in its proximity.
32
SAFETY INSTRUCTIONS
2. The operator must be instructed about his pump’s power supply and how to switch it off.
3. The operational reliability of the safety equipment must be checked daily.
4. The operator must report to his superior as quickly as possible for any fault or irregularity which
occurs. This applies to both the mechanical and electrical units.
5. It is absolutely essential that the operator shuts down the pump immediately if faults occur which
jeopardize safety.
These include:
1. Failure of the safety facilities
2. Damage to important pump components
3. Damage to electrical units and lines as well as insulation
Go Back to Menu
WPIL LTD. [email protected] 2011
WARNING
The electrical connection must be made by a qualified electrician in accordance with the local regulations.
The mains voltage must be the same as the voltage stated on the rating plate. The “electrical circuit diagrams” must be observed with regard to electrical
connection of the pump.
If the motor was switched off by the triggering of a safety element, it should not be switched back on again. The fault must be located and remedied. Switching back on without fault correction presents a risk of explosion.
33
SAFETY INSTRUCTIONS
6. The operator is forbidden to modify electrical connections. Only trained specialists may perform
this work.
7. Work on the pump may only be carried out if the current is switched off and when the moving
parts are no longer turning. Unauthorized switching-on must be prevented by suitable measures.
8. The pump may only be switched on when it is installed and flooded.
Go Back to Menu
WPIL LTD. [email protected] 2011
Dry running is not permissible.
Briefly switching on for maximum 10 seconds is possible without any danger.
Do not switch on if there’s a fault.
WARNING
Never put hands and objects into the pump while turning.
WARNING
Wear protective gloves when carrying out cleaning work, particularly when using solvents or petroleum ether.
Naked flames and smoking are forbidden.
Operating media (e.g. gear oils, transformer oils, lubricants and cleaning agents) for maintenance work and servicing and
oil changes must be collected in suitable containers and disposed off correctly.
34
MANUFACTURER’S REGULATIONS
1.4. MANUFACTURER’S REGULATIONS
1.4.1 General
These instructions must always be kept at hand where the pump is in use. It is essential that these instructions be read before work is started by all persons involved in working with or on the pump (make entry in the machine operator list).
Person(s) who will only occasionally work on the pump (e.g. for assembly and maintenance) must also read and understand the operating and maintenance manual.
It is essential to follow the instructions in the operating and maintenance manual of the pump. This applies strictly to the general and special safety instructions at the start of this manual and in the appropriate chapters.
If in doubt, consult the person responsible for safety and accident prevention in your division.
1.4.2 Correct behavior
Use the pump only for the intended liquids and data sheet parameters.
Any other use is regarded as a special application which must be clarified with the manufacturer.
The manufacturer is not liable for use of the pump for purposes other than those for which it was
designed.
The pump is operated from the control unit intended for this purpose.
Go Back to Menu
WPIL LTD. [email protected] 201135
MANUFACTURER’S REGULATIONS
Faults which can impair safety must be remedied immediately.
1.4.3 Behavior during operation
All accident prevention regulations must be observed.
A further precondition for safe operation is that the additional instructions in this operating and maintenance manual are observed.
1.4.4 Original parts and safety
Original parts and accessories are designed specially for the pump by WPIL Limited.
We expressly point out that original parts and accessories not supplied by WPIL Limited are not tested and released by the company. The installation and/or use of such products can impair the active and/or passive performance / safety of the pump.
1.4.5 Maintenance and inspection list
Keeping the maintenance and inspection list (Chapter 7 of the operating and maintenance manual) will help you to monitor the stipulated inspection and maintenance work.
1.4.6 Damage
Damage must be immediately remedied by specialists only.
Go Back to Menu
WPIL LTD. [email protected] 2011
Unauthorized modification / application of the pump
render the manufacturer’s liability VOID for any
resulting damage.
WPIL Limited shall not be liable for any damage arising from the use of non-original parts and accessories.
36
RECEIVING & CHECKING
2.1 UNLOADING & INSPECTION
All pump parts are precision machined parts. Unload with adequate care. Check the following:
Contents against packing list.
All components for damages.
Shafting for straightness and damage in case of broken crate or careless handling.
Go Back to Menu
WPIL LTD. [email protected] 201137
RECEIVING & CHECKING
2.2 SHORTAGES AND DAMAGES
Any shortages or damages should be immediately noted on the receipted documents of freight
agent/carrier to facilitate prompt and satisfactory resolution.
Go Back to Menu
WPIL LTD. [email protected] 2011
REPORT ALL TRANSIT DAMAGE / SHORTAGE
IMMEDIATELY ON FREIGHT AGENT / CARRIER
RECEIPT.
Late reports of shortage/transit damage will
cause controversy and delay prompt &
satisfactory resolution.
38
STORAGE & SHIFTING
3.1 ENVIRONMENTAL BRIEFING
All pump parts are precision machined. All parts supplied should be stored indoors in a dry (45%
RH) and non-corrosive environment.
The effective life of preservatives applied at the factory is 60 days including transportation period,
unless specifically agreed other-wise.
Go Back to Menu
WPIL LTD. [email protected] 2011
HIGH-HUMIDITY / COASTAL & CORROSIVE ENVIRONMENTS
A.) Inspect pump and parts periodically to ensure that
preservatives are intact.
B.) All machined surfaces and exposed shafting must be
coated with rust preventive agents suitable for the local
environment.
C.) Turn pump rotor manually each week a few turns.
39
STORAGE & SHIFTING
3.2 RECOMMENDED STORAGE PROCEDURE
• Storage area must be level and not at risk of flooding.
• All openings need to be sealed against ingress of dirt, particulate matter and water.
• All small parts need to be stored in covered boxes with preservative paper.
• Rubber parts like o-rings, gaskets and bearings need to be stored in closed containers.
• Keep heavy components off the ground by using supports.
• Shafting need to be removed from boxes, coated with preservative and then re-boxed with preservative paper.
Go Back to Menu
WPIL LTD. [email protected] 2011
DO NOT DISCARD ORIGINAL PACKING BOXES. RE-PACK AND STORE & MOVE IN ORIGINAL PACKING
BOXES.
INSPECT ALL PARTS PERIODICALLY TO ENSURE
PRESERVATIVES ARE INTACT AND NO SIGN OF
CORROSION IS VISIBLE.
40
STORAGE & SHIFTING
3.3 RECOMMENDED MOVEMENT / SHIFTING PROCEDURE
Pump assembly, thrust bearing assembly, all shaftings & small parts must be moved in boxed
condition only.
Go Back to Menu
WPIL LTD. [email protected] 2011
DO NOT MOVE LOOSE PARTS. STICK TO
ORIGINAL FACTORY PACKAGING METHODS
FOR MOVEMENT.
41
PREPARATION FOR INSTALLATION
4.1 REQUIRED TOOLS,MATERIALS AND EQUIPMENTS
The materials and equipment necessary for installation of the pump will vary with the size of the
pump and type of the installation. The list of lifting equipments and hand tools at Table below is
offered as a guide only.
S.No. TOOLS & MATERIALS QUANTITY REMARKS
1 Washing Oil, Kerosene For washing of parts
2 Emery Cloth Paper For cleaning of parts
3 Molycote (anti-galling grease) For assembly
4 Sealing tape/Thread compound for pipe For auxiliary piping
5 Line Marker 2 Sets For alignment of foundation
6 Chisel 3 Sets For foundation preparation
7 Lifting Nylon Slings of suitable capacity
and 3 m long
2 nos. For installation & rigging
8 1 / 5 / 10 lb Hammer 2 nos. For assembly
Go Back to Menu
WPIL LTD. [email protected] 2011
The installation rig should be rated to hold at least 1.5 times the weight of the complete pumping unit i.e. the assembled pump and
driver.
42
PREPARATION FOR INSTALLATION
9 File Set 2 sets For assembly
10 Screw Driver 2 each For assembly
11 Adjustable Wrench 1 no. For assembly
12 Pipe Wrench 2 nos. For auxiliary piping / Line Shaft.
13 Allen Key(2 mm to 10 mm size) 1 set For assembly
14 Wire Brush 2 nos. For assembly
15 Single ended / double ended wrench(10mm
to 36mm)
2 each For assembly
16 Plumb Bob with string 1 no. For installation
17 Nylon hand hammer 2 nos. For installation
18 Eye bolt of various sizes For rigging
19 D-shackle of various sizes (5 /7.5 M) 1 set For rigging
20 Socket wrench 1 set For assembly
21 Position marker punch 1 set For assembly
22 Gap gauge (feeler gauge) 2 sets For erection
23 Scraper 2 sets For assembly
24 Marking String - For assembly
25 Ring spanner 2 nos. each For assembly
Go Back to Menu
WPIL LTD. [email protected] 201143
PREPARATION FOR INSTALLATION
26 S.S. shims of various sizes (0.1 mm to 2 mm) - For assembly
27 Mobile hoist/ travelling crane 1 no. For assembly depending on size &
weight of the pump
28 Bearing pullers 1 no. For Bearing removal
Measuring tools required during installation:
Sno. Tools & Materials Quantity Remarks
1 Precision Class Spirit Level Gauge (Accuracy 0.02
mm/ M)
1 no For level checking
2 Steel Tape (5, 10M) 1 each For measurement of foundation
3 Dial Gauge with Magnet Holder & Clamps
(Minimum division 0.01mm)
1 set For alignment checking
4 Gap Gauge (feeler gauge) 2 sets For assembly
5 Edge 1.5 M long 1 No. For Leveling
6 Straight Steel Scale (1 M) 1 each For assembly
7 Straight Edge (I–beam type) 1.5 m long,
Accuracy-0.05mm/M
1 no. For level checking
Go Back to Menu
WPIL LTD. [email protected] 201144
PREPARATION FOR INSTALLATION
4.2 INSTALLATION DRAWINGS
Collect and arrange the following drawings:
• Foundation drawing (refer pump General Arrangement drawing),
• Installation dimensional drawing (refer pump General Arrangement drawing & pump cross-
sectional drawing),
• Functional unit layout, (as per design by you), and
• Piping diagram (as per design by you).
Finalize the method of installation based on these documents before starting work.
Go Back to Menu
WPIL LTD. [email protected] 201145
PREPARATION FOR INSTALLATION
4.3 PREPARING THE PUMP FOUNDATION
The foundation must be built to support the weight of the entire pump unit when the pump is full of
water. It should be rigid enough to withstand and prevent vibrations. The loading details of the
pump are given in General Arrangement Drawing.
WPIL recommends that a concrete foundation be used wherever possible.
Steel I-beams or timbers may also be used, but they should be strong enough to prevent spring
action and braced (tied together) to prevent lateral movement.
In case of concrete foundation, the top surface of the foundation should be left rough to allow
proper binding of final grout mixture. Also the top surface level should be lower in height by at least
20 to 35 mm to permit leveling of base plate.
Go Back to Menu
WPIL LTD. [email protected] 201146
PREPARATION FOR INSTALLATION
4.4 LAYOUT & INSPECTION OF PUMP PARTS FOR INSTALLATION
• All pump accessories should be checked for correctness and cleanliness.
• All small components and fasteners should be separated assembly-wise as per cross-
sectional drawing & checked for correctness and cleanliness.
Go Back to Menu
WPIL LTD. [email protected] 201147
PREPARATION FOR INSTALLATION
4.5 HOISTING INSTRUCTIONS
Nylon slings (of rated load capacity) for lifting the pump assembly should pass at positions on the
pump branches as shown in Fig. 4.5.a
Fig:- 4.5a
Go Back to Menu
WPIL LTD. [email protected] 2011
Horizontal/Vertical Pump Lifting Arrangements
48
PREPARATION FOR INSTALLATION
To lift the prime-mover (electric motor), pass sling as shown in Fig 4.5.b
Fig: 4.5b
Go Back to Menu
WPIL LTD. [email protected] 2011
Never lift the entire pump assembly by the eye-bolts or from the bearing housing or from the shaft extension.
49
PREPARATION FOR INSTALLATION
4.6 LAYOUT OF PIPE WORK, VALVES and ACCESSORIES
It is important to ensure that pipe work, valves etc. connected to the pump are adequately
supported. Ensure that the pump does not carry the weight of the pipe work when filled with water
or tend to be dragged in any direction.
4.6.1 SUCTION PIPING
To avoid the formation of air pocket, the installation of suction pipe work must be arranged under
the following conditions:
• Always as few bends as possible
• Suction pipe work must be perfectly air tight
• There must be a gradual rise in the suction pipe work towards the pump
Go Back to Menu
WPIL LTD. [email protected] 2011
No strain is put on the pump casing flanges by the pipe work else would disturb the pump alignment leading to vibrations.
Never connect a pump to the piping; always connect pipe to the pump
50
PREPARATION FOR INSTALLATION
• In case of an elbow is required at the pump suction flange, it should have a long radius. Location of the elbow from the pump flange should be more than 2D of straight pipe.
• In case of an expander is required at the pump suction flange, it should be eccentric type to avoid the air pockets.
• In case of strainer is provided, for clear water the total area of these holes should exceed three times the area of the bore of the pump suction branch.
Typical good and bad suction arrangements are shown in Fig 4.6.1.a & b and typical layouts are shown in Fig. 4.6.1.c & d
Good suction layouts, showing pipes rising all the way to the pump.
Bad suction layouts, which will cause air pockets and failure to pump.
Fig. 4.6.1.a
Go Back to Menu
WPIL LTD. [email protected] 201151
PREPARATION FOR INSTALLATION
Fig. 4.6.1.b
Typical Layout – Flooded Suction (Fig. 4.6.1.c)
Go Back to Menu
WPIL LTD. [email protected] 2011
Showing how an air pocket may be formed when the suction pipe is bigger than the pump branch.
avoided.
Showing how the fault in the illustration on the left may be avoided.
52
PREPARATION FOR INSTALLATION
Typical Layout – Suction Lift (Fig. 4.6.1.d)
4.6.2 DELIVERY PIPING
• Pipe work, valve, fitting etc. are located in the delivery pipe line should be adequately supported to avoid any strains on the pump flange.
• If an expansion joint is used it is recommended that this should be located at a distance not less than 2D from pump flange.
• The intermediate spool piece between pump and expansion joint needs to be anchored.
• Improper anchoring may subject to large reaction forces which could be detrimental to the installation.
• A check valve is recommended in the case of back flow/high pressure surge is anticipated.
Go Back to Menu
WPIL LTD. [email protected] 201153
INSTALLATION PROCEDURES
5.1 LEVELING & GROUT TYPE
The purpose of grouting is to prevent lateral shifting of the base plate, not to fix irregularities in the foundation. Base plates are normally fabricated M.S. channel width plates at top and bottom accurately machined to have parallel plane surfaces. The base plate looks similar to as shown in Fig. 5.1.a
Base Frame with Channel (Fig. 5.1.a)
5.1.1 LEVELING OF BASE PLATE
1. Mark the base plate/base frame and foundation bolts position as per GA Drawing.
2. Grout foundation bolts, as per GA drawing, using quick setting cements.
3.WPIL recommends that 20-30 mm of epoxy grout is maintained under the base frame.
4.In case epoxy grout is not available, level using leveling wedges. Fill the gap between sole plate and foundation with quick setting concrete. Refer fig. 5.1.1.a & b
5.Level base plate/base plate with the help of straight edge and spirit level in two directions at 90 degrees by either leveling wedges or leveling nuts on anchor bolts.
Go Back to Menu
WPIL LTD. [email protected] 201154
INSTALLATION PROCEDURES
6. Allow curing time for grout as per manufacturer’s recommendations. Setting time is usually 48 hrs and the grouting becomes hard in 72 hrs.
7. In case of vertical installation, the pump should be mounted following the practices outline for base plate mounted pumps similar to horizontal pumps.
8. If the pump is driven via a universal joint drive shaft, there may be a requirement to offset the pump shaft w.r.t. the driver. Optimal offset will typically be in the range 0 to 4º depending on shaft design. Consult the separate user instructions before installation.
9. Any support for the universal joint drive shaft, Plummer blocks must not exhibit resonant frequencies in the range of 0.8 to 1.2 of nominal pump speed.
10. In case of vertical pump, the alignment of the unit is achieved by adding or removing shims between the motor stool and the pump casing. The motor has a spigot fit in to the motor stool and it is therefore not possible to achieve any horizontal movement at this interface.
Go Back to Menu
WPIL LTD. [email protected] 2011
Before leveling, the sole plate should be high enough in grout thickness.
Preferred levelness is dead-level. Maximum acceptable tolerance is 0.15 mm/meter.
55
INSTALLATION PROCEDURES
Fig. 5.1.1.a
Fig. 5.1.1.b
Go Back to Menu
WPIL LTD. [email protected] 2011
FOUNDATION BOLT FIXING DETAILS WITH BASE PLATE
56
INSTALLATION PROCEDURES
5.2 INSTALLING THE PUMP ASSEMBLY
The horizontal & vertical pumps are supplied in assembled condition from the works (as shown in Fig. 5.2.a & 5.2.b). The accessories like couplings, coupling guard, motor stool & pump stool (in vertical pump) etc. are supplied separately, are to be assembled with the pump and motor shaft respectively at site and to be installed on the base frame/base plate. The following steps shall be followed in installing the pump assembly.
• Sling and hoist the pump with its half coupling and gently lower in position on the leveled base plate.
• Check that no gap exists between pump feet and the respective machined pads on the base plate.
• Locate the pump fixing bolts and tighten down.
• Similarly locate the prime mover with its coupling half in position on the leveled base plate.
• Rotate each shaft independently by ensuring that the bearings run freely and that shafts are true within 0.1mm. Coupling pins should not be fixed during this check.
Fig. 5.2.a
Go Back to Menu
WPIL LTD. [email protected] 201157
INSTALLATION PROCEDURES
Vertical Pump Assembly (Fig: 5.2b)
Go Back to Menu
WPIL LTD. [email protected] 201158
INSTALLATION PROCEDURES
5.3 COUPLINGS
5.3.1 FLEXIBLE COUPLING
For horizontal pumps, the couplings used are Flexible pin bush type similar to as shown in Fig. 5.3.1a & b. Both couplings are identical except 5.3.1b with the exception of bore and the pins can be inserted from either side.
Fig. 5.3.1.a
Go Back to Menu
WPIL LTD. [email protected] 2011
‘A’ Type Flexible Coupling
Ref. Description
2 Coupling Pin
3 Coupling Bush
5 Distance Sleeve
272 Locking Washer
276 Flexible Coupling (Pin Half)
277 Flexible Coupling (Bush Half)
59
INSTALLATION PROCEDURES
Fig. 5.3.1.b
5.3.2 COUPLING ALIGNMENT
The pump unit has been manufactured to allow field alignment. The unit must be properly aligned at the time of installation. The importance of correct alignment can not be over emphasized. Alignment should be checked and corrected as required after:
1. Mounting
2. Piping is connected
3. Pump or driver is moved for any reason.
Angular and parallel mis-alignment are corrected by shifting the motor and adding or removing shims from under the motor feet.
Go Back to Menu
WPIL LTD. [email protected] 2011
‘B’ Type Flexible Coupling
Ref. Description
2 Coupling Pin
3 Coupling Bush
54 Coupling Key
272 Retaining Washer
275 Locking Nut
276 Flexible Coupling (Pin Half)
277 Flexible Coupling (Bush Half)
60
INSTALLATION PROCEDURES
5.3.2.1 RADIAL ALIGNMENT
The radial alignment (intersection of axis) refer fig. 5.3.2.1a, for the rotating unit are carried out with the help of dial gauge.
• Clamp the dial indicator to one of couplings or to the shaft behind it, with the plunger resting on the rim of the other half coupling.
• Set the pointer to zero.
• Rotate the coupling and note the readings at each quarter revolution (90º).
• Any variation in readings indicates a deviation in alignment. The position of one of the units must be adjusted until the readings at each quarter revolution are within the specified tolerances given below.
Fig. 5.3.2.1.a
Go Back to Menu
WPIL LTD. [email protected] 2011
To check intersection of axes (Shaft in line at coupling end)
For detecting this type of error
61
INSTALLATION PROCEDURES
5.3.3.2 ANGULAR ALIGNMENT
The angular alignment (parallelism of axis) refer fig. 5.3.2.2a, for the rotating unit are carried out with the help of dial gauge.
1.Clamp two dial gauge indicators at diametrically opposite points on one half of the coupling, on to the shaft behind it, with plungers resting on the back of the coupling.
2.Inscribe a line across both of couplings for reference, readings are to be taken only when the two marks coincide.
3.Rotate the couplings until the gauges are in line vertically and set the gauges to zero.
4.Rotate the coupling through half revolution.
5.If the alignment of the pump and its driving unit is correct the reading of both gauges should be the same, though not necessarily zero.
6.Equally positive or negative readings are acceptable.
7.Adjust the position of any one of the units to correct the readings.
8.Rotate the couplings until the gauges are in line horizontally and reset the dial so that the pointers are at zero.
9.Repeat the operations from point 4 to 7.
Go Back to Menu
WPIL LTD. [email protected] 2011
Coupling up to Ø300mm 0.05mm (0.002”)
Coupling > Ø300mm 0.07mm (0.003”)
RADIAL & ANGULAR ALIGNMENT NOT TO EXCEED
0.5mm (0.004”) ON DIAL GAUGE
62
INSTALLATION PROCEDURES
Fig. 5.3.2.2a
5.3.2.3 ALTERNATIVE METHOD FOR ALIGNMENT
Angular and parallel misalignment can alternatively quickly be checked by using the straight edge and feeler gauge as described below.
Go Back to Menu
WPIL LTD. [email protected] 2011
To check the parallelism of axes (Angular alignment)
For detecting this type of error
63
INSTALLATION PROCEDURES
Fig. 5.3.2.3a
Check for angular alignment by inserting the taper or feeler gauges between the coupling faces at 90º intervals. The unit is in angular alignment when these four measurements are the same, or within recommended tolerances.
Check for parallel alignment by placing a straight edge across both coupling rings on all four sides. The unit is in parallel alignment when the straight edge rests evenly across both coupling rings in all four directions.
Go Back to Menu
WPIL LTD. [email protected] 201164
INSTALLATION PROCEDURES
5.4 INSTALLING THE ACCESSORIES
5.4.1 PRIMING CONNECTION
Priming connection has been provided in the upper half of the casing to fill the casing with water from some outside source until suction pipe and casing are completely filled with the water. Priming may also be accomplished by the use of vacuum pump. Sometimes put valves are also used for priming purpose depending upon the size of the pump.
5.4.2 AIR VENT CONNECTION
The air vent connection is provided at the top of the casing near the priming plug to provide the air release valve for the removal of air during priming. It is necessary to exhaust air from suction pipe and pump casing, as any air that remains in trapped will interfere with operation or hinder pump from lifting water and will loose the priming.
5.4.3 PRESSURE GAUGE CONNECTION
Connect a compound gauge to suction of pump and pressure gauge to discharge flange of the pump. It is advisable to furnish shut-off valves between flange gauged connections and gauges. The gauges are necessary for an adequate check on pump performance.
5.4.4 STUFFING BOX PACKING
Packing and repacking of stuffing box should be done with great skill and care. Normally the pump is dispatched from works along with packing. However, the time between the date the pump is dispatched from works and date it is commissioned is more than three months, replace the packing. For various pump models, refer the packing sizes as per the following Table 5.4.4. For installation purpose, refer the pump assembly drawing (Fig. 7.3.3). Mechanical seal is optional and factory assembled.
Go Back to Menu
WPIL LTD. [email protected] 2011
THE PACKING RING JOINTS SHOULD BE
STAGGERED AND EACH RING SHOULD
BE PUSHED IN TO POSITION
SEPARATELY.
65
INSTALLATION PROCEDURES
PUMP SIZE & TYPE SHAFT SLEEVE
DIA. AT PACKING
STUFFING BOX DATA
HORIZONTAL VERTICAL SIZE OF PACKING
SQ. (mm X mm)
No. OF RINGS PER
BOX
8 LN 18 8 LNV 18 101.6 15.88 5
8 LN 21 8 LNV 21 114.3 15.88 5
8 LN 29 8 LNV 29 114.3 15.88 5
10 LN 18 10 LNV 18 88.9 15.88 5
10 LN 22 10 LNV 22 114.3 15.88 5
10 LN 26 10 LNV 26 114 15.88 5
12 LN 14 12 LNV 14 88.9 15.88 5
12 LN 17 12 LNV 17 101.6 15.88 5
12 LN 21 12 LNV 21 114.3 15.88 5
12 LNH 21 12 LNHV 21 114.3 15.88 5
14 LN 19 14 LNV 19 95 19.05 5
16 LN 23 16 LNV 23 114 15.88 5
16 LN 35 16 LNV 35 165.1 19.05 5
20 LN 26 20 LNV 26 152.4 19.05 5
20 LN 28 20 LNV 28 152.4 19.05 5
Go Back to Menu
WPIL LTD. [email protected] 201166
INSTALLATION PROCEDURES
24 LN 34 24 LNV 34 140 19.05 5
24 LN 42 24 LNV 42 190.5 19.05 5
30 WLN 30 30 WLNV 30 130 20 5
30 LN 41 30 LNV 41 203.2 19.05 5
Table 5.4.4
5.4.5 MECHANICAL SEAL
The typical mechanical seal assembly is shown in fig. 5.4.5.a The correct functioning of the seal must be checked regularly. No adjustment is possible locally. When leakage reaches an unacceptable level, the seal will need replacement.
Fig. 5.4.5.a
Go Back to Menu
WPIL LTD. [email protected] 2011
PART DESCRIPTION
119 SEAL RING
220 MATING RING
301 O-RING
321 O-RING
412 SPRING
431 GRUB SCREW
449 SPRING HOLDER
554 DRIVE COLLAR
67
PUMP START-UP & OPERATION
6.1 PRE-START PROCEDURES
Before the pump is brought in to the service, suction and delivery pipe work should be flushed and the sump clear of all debris like foreign material, silt and other deposits. This is done to prevent damage to the pump internals.
Consult the applicable manufacturer’s instructions for detailed information for the prime mover (motor, engine or steam turbine) coupling, drive-shaft, electric driver, gear-head or mechanical seal applicable to the pump. Prior to start-up, check/do the following:
1. Open the vent connection on top of the pump upper casing to allow the trapped air to escape. Let liquid run out until casing is free from air bubbles.
2. In the case of vertical installation, open vent connection at the front of the upper half casing and disconnect the seal flush line at the mechanical seal/ stuffing box to allow the trapped air to escape. Let liquid run out until free from air bubbles.
Go Back to Menu
WPIL LTD. [email protected] 2011
IF PUMP IS STORED FOR MORE THAN
THREE MONTHS, THE BEARING SHOULD
BE DISMANTLED, CLEANED & RE-
GREASED.
ENSURE THAT THE PUMP IS GIVEN THE
SAME ROTATION AS THE PUMP
DIRECTION ARROW CAST ON THE
PUMP CASING/ NAME PLATE.
WHENEVER COUPLING GUARD IS
REMOVED OR DISTURBED, ENSURE
THAT THE PROTECTIVE GUARD IS
SECURELY REFITTED PRIOR TO
STARTUP.
ENSURE THE INLET PIPE AND PUMP
CASING ARE COMPLETELY FULL OF
LIQUID BEFORE STARTING
CONTINUOUS DUTY OPERATION.
68
PUMP START-UP & OPERATION
3. That the pump operates with suction lift and is fitted with foot valve. Fill suction pipe and casing with liquid at a pressure of 1 to 2 bar from external source.
4. In case pump operates with suction lift without foot valve, the pump casing vents on suction volute must be connected to an external vacuum pump priming system.
5. In case of mechanical seal pump, all piping to the seal should be connected and properly lubricated.
6. Check that all cooling, heating and flushing lines are operating and are regulated for required flow.
7. Check that allowable runout shaft with seal is 0.050 mm.
8. Check wiring of the driver.
9. Check rotation of driver with the coupling halves disconnected i.e. under no-load condition.
10. Check that all connections to driver and starting device are as per the wiring diagram.
11. Check that voltage, phase, and frequency of the supply line are as per the motor name plate.
12. Rotate the shaft manually to ensure that the impellers rotate freely.
13. Check driver bearings for proper lubrication and oil level in housing.
14. Check that auxiliary seal components are properly vented.
15. Check discharge piping and pressure gages for proper operation.
Go Back to Menu
WPIL LTD. [email protected] 201169
PUMP START-UP & OPERATION
6.2 IMPORTANT START-UP INSTRUCTIONS
Following these helpful guidelines will assure longer life for your pump.
1.Check the tightness of pump set holding down bolts. (Refer torque as per the table 7.3.3.1)
2.Pump/base plate should not be used as pipe anchor.
3.Suction and discharge piping should be anchored as close as possible to the pump flanges to reduce vibration and prevent strain on the pump casing.
4.Expansion joints, if used, they must be properly tied and located on the side of the pipe anchor away from the pump.
5.Ensure adequate liquid is available in the sump and that sump levels are within the recommended values to meet NPSHR (Net positive suction head).
6.If the pump loses its prime or breaks suction, immediately shut it down and investigate the cause.
7.Ensure that suction valve is fully open.
8.Ensure that delivery valve is closed. The pump may be started with a fully open delivery valve provided the system operating pressure is standing on the discharge side of the pump NRV (if fitted).
9.Issue permission to startup after obtaining clearance from the concerned official to whom the essential system condition is known.
10.Start the pump through panel or local station.
11.Allow pump to reach its full speed and check the pressure gauge reading.
12.At this point the pump should generate a pressure higher or equal to its rated pressure.
Go Back to Menu
WPIL LTD. [email protected] 2011
DO NOT RUN PUMP DRY!
The impellers and bearing have small clearances and may bind / seize and
cause serious trouble.
70
PUMP START-UP & OPERATION
13.If the generated pressure is lower the rated pressure stop the pump immediately and investigate.
14.Rectify the fault and re-prime the pump before restart.
15.If the pressure is within the satisfactory limits, slowly open the delivery valve to permit charging the line.
16.Care to be taken to avoid prolonged operation at near closed valve condition. It should not be more than five minutes.
17.Ascertain the pump total head from the pump test sheet or pump name plate.
18. If the pump capacity is much higher than the supplied pump, it is better to throttle the pump than to let it break suction. Only pumps may be throttled, however, the throttling should be limited to 50 percent of design flow.
NOTE: Throttling may affect the driver load.
19.When the pump is stopped, the flow of liquid backing down through the pump will cause the pump to rotate backward.
20.The bearing should be watched for signs of over heating. The bearing temperature may be allowed to rise 50ºC above ambient but not to exceed 80ºC for both oil & grease lubricated bearings.
Normally recommended intervals between oil/grease changes are 4000 hours or at least every six months. The quality of grease should be of lithium soap base.
Go Back to Menu
WPIL LTD. [email protected] 2011
NEVER START THE PUMP AGAIN WHILE THIS
BACKWARD ROTATION IS HAPPENING!
If you do, you will place a severe strain on the
shafting and it may break. Always allow the pump to
stop completely before restarting it.
71
PUMP START-UP & OPERATION
21. Do not operate the pump for long period at low capacity on account of overheating from churning.
22. If necessary, bypass arrangements may be adopted to save the pump operations at low capacity.
23. The gland should be checked to make sure that they are not cracked and rubbing on shaft sleeves causing overheating and overloading of motor.
24. When the pump is in operation, there should be some leakage at the stuffing box packing (Fig. 6.3.a). For cooling and lubrication, allow approximately 60 drops of liquid to escape each minute.
Fig. 6.3.a
25. In case of mechanical seal fitted with the pump, the seal leaks slightly at start-up, allow a reasonable amount of time for the seal to adjust itself. Liquids with good lubricating qualities normally take longer to wear in the seal than liquid with lesser qualities. When a seal starts out with a slight leak and gets progressively less with running, it indicates leakage across the seal faces and continued running will usually eliminate this. Where leakage occurs immediately and remains constant, unaffected by running, it usually indicates a secondary seal damage (shaft packing), or the seal faces are warped out of flat. See Section 6.3 (Troubleshooting), for possible causes and remedies.
Go Back to Menu
WPIL LTD. [email protected] 2011
NEVER MIX GREASES CONTAINING DIFFERENT
BASES, THICKENERS OR ADDITIVES.
72
PUMP START-UP & OPERATION
26. After the pump set has run out for an hour, all readings should be suitably logged in site records.
27. The pump set should be allowed to run for another hour or so to observe any undue change in parameters or until such time as the pump stabilizes.
Go Back to Menu
WPIL LTD. [email protected] 2011
NEVER RUN A MECHANICAL
SEAL DRY EVEN FOR A
SHORT TIME.
TOLERANCE : VIBRATION LEVELS
95 Microns peak to peak when run at 1450 rpm. Measurement shall
be on pump bearing housing. Refer Hydraulic Institute Standards
(ANSI/HI-1994) for different speeds.
EXTERNAL FLUSH OR QUENCH SHOULD BE
STARTED BEFORE THE PUMP IS RUN AND
ALLOWED TO FLOW FOR A PERIOD OF FIVE
MINUTES AFTER THE PUMP HAS STOPPED.
73
PUMP START-UP & OPERATION
Trouble shooting chart
6.3.1 NO LIQUID DELIVERED
6.3.2 INSUFFICIENT PRESSURE
6.3.3 INSUFFICIENT CAPACITY
6.3.4 PUMP LOSES PRIME AFTER STARTING
6.3.5 PUMP OVERHEATS AND SEIZES
6.3.6 SHORT BEARING LIFE
6.3.7 VIBRATION AND NOISE
6.3.8 STUFFING BOX LEAKS EXCESSIVELY
6.3.9 SHORT SEAL LIFE
6.3.10 MECHANICAL SEAL LEAKS
6.3.11 USING TOO MUCH POWER
Go Back to Menu
WPIL LTD. [email protected] 201174
PUMP START-UP & OPERATION (Trouble shooting chart)
6.3.1 NO LIQUID DELIVERED
TROUBLE INDICATOR
POSSIBLE CAUSES RECOMMENDED REMEDIES
NO LIQUID DELIVERED
• Lack of priming
• Loss of Prime or Air leaks
• Suction valve closed
• Impeller plugged
• Suction lift too high
• Foot valve/strainer clogged
• Speed too slow
• Wrong rotation
• Parallel operation of pumps unsuitable for operations
• Pump or suction pipe not completely filled with liquid. Fill pump and suction pipe completely with liquid.
• Check for leaks in suction pipe joints and fittings. Vent casing to remove accumulated air. Check and replace packing and shaft sleeve for wear if required.
• Open valve.
• Open pump and inspect for obstruction.
• Check the liquid level in the sump, static lift may be too high. Maintain the required level/suction pressure to meet the NPSHR of the pump. Measure with mercury column or vacuum gauge while pump is in operation. If static lift is too high, liquid to be pumped must be raised or pump lowered.
• Inspect and clean the foot valve and/or strainer. Area through foot valve should preferably 2 times, if strainer is used, area should be 3-4 times the area of suction pipe.
• Check motor voltage or frequency may be low. Check the pump’s speed is consistent with manufacturer’s recommendations.
• Rotation must be as indicated by arrow on pump nameplate. Check engagement of motor coupling.
• Check the system head curve with the pump curve and see the suitability of the pump.
Go Back to Menu
WPIL LTD. [email protected] 201175
PUMP START-UP & OPERATION (Trouble shooting chart)
6.3.2 INSUFFICIENT PRESSURE
TROUBLE INDICATOR
POSSIBLE CAUSES RECOMMENDED REMEDIES
INSUFFICIENT PRESSURE
• Speed too slow
• Air leaks in suction piping
• Mechanical defects
• Wrong rotation
• Check motor voltage or frequency may be low. Check the pump’s speed is consistent with manufacturer’s recommendations.
• Check the piping joints for air leakage. Check for gaskets in place and tighten the bolts to prevent air leakage.
• Defective impeller, wearing rings or packing. Inspect impeller, wearing rings and packing. Replace if vane sections eroded or damaged. Replace wearing rings, packing if worn out.
• Rotation must be as indicated by arrow on pump nameplate. Check engagement of motor coupling.
Go Back to Menu
WPIL LTD. [email protected] 201176
PUMP START-UP & OPERATION (Trouble shooting chart)
6.3.3 INSUFFICIENT CAPACITY
TROUBLE INDICATOR
POSSIBLE CAUSES RECOMMENDED REMEDIES
INSUFFICIENT CAPACITY
• Speed too slow
• Lack of priming
• Suction lift too high
• Air leaks in suction piping
• Air leaks in to pump through stuffing boxes
• Foot valve/strainer partially clogged
• Excessive amount of air/gas in liquid
• Suction valve throttle
• Impeller passage partially plugged
• Total head of system higher than designed head of pump
• Wrong rotation
• Parallel operation of pump unsuitable
• Check motor voltage or frequency may be low. Check the pump’s speed is consistent with manufacturer’s recommendations.
• Pump or suction pipe not completely filled with liquid. Fill pump and suction pipe completely with liquid.
• Check the liquid level in the sump, static lift may be too high. Maintain the required level/suction pressure to meet the NPSHR of the pump.
• Check the piping joints for air leakage. Check for gaskets in place and tighten the bolts to prevent air leakage.
• Inspect and replace the incorrect/worn out packing.
• Inspect and clean the foot valve and/or strainer. Area through foot valve should preferably 2 times, if strainer is used, area should be 3-4 times the area of suction pipe.
• Inlet of suction pipe insufficiently submerged. The inlet pipe to be sufficiently submerged at least 2-3 feet in liquid.
• Check and open valve.
• Dismantle the pump, inspect passage, clean if required.
• Take suitable measure to reduce the friction losses or static lift or replace the pump.
• Rotation must be as indicated by arrow on pump nameplate. Check engagement of motor coupling.
• Check the system head curve with the pump curve and see the suitability of the pump.
Go Back to Menu
WPIL LTD. [email protected] 201177
PUMP START-UP & OPERATION (Trouble shooting chart)
6.3.4 PUMP LOSES PRIME AFTER STARTING
TROUBLE INDICATOR
POSSIBLE CAUSES RECOMMENDED REMEDIES
PUMP LOSES PRIME AFTER STARTING
• Pump or suction pipe not completely filled with liquid
• Suction lift too high or water level too low
• Excessive amount of air or gas in liquid
• Air or vapor pocket in suction line
• Air leaks in to suction line
• Air leaks in to pump through mechanical seal, sleeve joints, casing joint or pipe lugs
• Inlet of suction pipe insufficiently submerged
• Check and fill liquid completely.
• Check NPSHA > NPSHR, proper submergence, loses at strainers and fittings.
• Check and purge from pipes.
• Check suction line design for pockets.
• Check air tight pipe then joints and gaskets.
• Check air tight assembly then joints and gaskets.
• Check cut out system design.
Go Back to Menu
WPIL LTD. [email protected] 201178
PUMP START-UP & OPERATION (Trouble shooting chart)
6.3.5 PUMP OVERHEATS AND SEIZES
TROUBLE INDICATOR
POSSIBLE CAUSES RECOMMENDED REMEDIES
PUMP OVERHEATS AND SEIZES
• Operation at very low capacity
• Parallel operation of pump unsuitable for operation
• Misalignment
• Rotor out of balance
• Bearing worn out
• Lack of prime- Fill pump and suction pipe completely with liquid. Suction lift too high- If static lift is too high than liquid to be pumped must be raised or pump to be lowered.
• Check the system head curve with the pump curve and see the suitability of the pump.
• Check for misalignment both angular and radial and correct to tolerance limit.
• Check and balance the rotor with in the specified grade.• Check the bearing lubrication and replace
the bearing.
Go Back to Menu
WPIL LTD. [email protected] 201179
PUMP START-UP & OPERATION (Trouble shooting chart)
6.3.6 SHORT BEARING LIFE
TROUBLE INDICATOR
POSSIBLE CAUSES RECOMMENDED REMEDIES
SHORT BEARING LIFE
• Operation at high capacity
• Misalignment due to pipe strain
• Shaft bent
• Rotating part rubbing on stationary part internally
• Bearings worn• Shaft running off
centre because of worn bearings or misalignment
• Impeller out of balance resulting in vibration
• Excessive trust caused by mechanical failure inside the pump
• Excessive grease in ball bearings
• Lack of lubrication for bearings
• Improper installation of bearings
• Damage bearings due to contaminations
• Wrong direction of rotation
• Measure value and check maximum permitted.
• Check the flange connections and eliminate strains using method permitted.
• Check shaft run-outs within acceptable values (0.05 mm).
• Check for signs of this and correct it.
• Replace bearings• Check misalignment and correct if necessary.
Check bearings for excessive wear.
• Check and balance the impeller to the required grade (ISO 6.3 Grade).
• Check wear condition of impeller, its clearances and liquid passages.
• Check method of re-greasing.
• Check hours run since last change of lubricant.
• Check method of assembly or state of cleanliness during assembly and type of bearing used.
• Check contamination source and replace damaged bearings.
• Reverse two phases on motor terminal box.
Go Back to Menu
WPIL LTD. [email protected] 201180
PUMP START-UP & OPERATION (Trouble shooting chart)
6.3.7 VIBRATION AND NOISE
TROUBLE INDICATOR
POSSIBLE CAUSES RECOMMENDED REMEDIES
VIBRATION AND NOISE
• Inadequate grouting
• Misalignment
• Motor imbalance Driver
• Foreign Material in unit
• Mechanical Defects
• Rotor out of balance
• Clogged impeller or foreign material in pump
• Foundation not rigid
• Vortex problems in sump
• Resonance
• Excessive grease or oil in antifriction bearing housing
• Motor noise• Cavitation due to low
submergence or operation beyond maximum capacity rating
• Foreign material in pump
• Entrained air
• Check base plate grouting, re grout if required. Also piping supports for anchoring.
• Check for misalignment both angular and radial. Correct to tolerance limits.
• Isolate driver from pump unit, if vibration continues. Inspect driver and determine the cause utilizing vibration frequency analyzer and/or pump assembly. Consult motor/pump manufacturer.
• Inspect volute, impeller and suction piping for foreign material and remove. Also repair any accompanying damage.
• Shaft running off center because of worn bearings or misalignment. Inspect impeller bearings and shaft for damage and repair or replace as required.
• Balance the impeller to the specified grade.
• Back flush. Pull, check for damage and replace.
• Check the proper tightness of the foundation bolts and check for no gap between the base plate and finished floor level. Re grouting is recommended.
• Increase pump submergence. Apply sump modification such as; relocate pump in sump, lower the inlet velocity in sump.
• System frequency at or near pump speed—Loosen anchor bolts. Change pipe loading.
• Fill the quantity of grease as recommended.
• Check for bearing failure. Install RTD’S in bearing housing. Monitor bearing oil level.
• Insufficient NPSH available. Evaluate system head conditions and reduce pump capacity, if possible. Change pump’s impeller to lower NPSH design to meet the system NPSH available.
• Back flush or pull and inspect.
• Air separation can also cause hydraulic noise. Bleed off entrained air.
Go Back to Menu
WPIL LTD. [email protected] 201181
PUMP START-UP & OPERATION (Trouble shooting chart)
6.3.8 STUFFING BOX LEAKS EXCESSIVELY
TROUBLE INDICATOR
POSSIBLE CAUSES RECOMMENDED REMEDIES
STUFFING BOX LEAKS EXCESSIVELY
• Packing is worn out or not properly lubricated
• Packing is improperly inserted
• Packing is not right kind for liquid handle
• Shaft scored
• Inspect packing, lubrication line and lantern ring location to ensure flow.
• Inspect packing for correct size and avoid overlaps.
• Packing selection should be checked against manufacturer recommendation.
• If shaft/sleeve scored excessively, repacking alone may not stop excessive leakage. Hence replace shaft/sleeve.
Go Back to Menu
WPIL LTD. [email protected] 201182
PUMP START-UP & OPERATION (Trouble shooting chart)
6.3.9 SHORT SEAL LIFE
TROUBLE INDICATOR
POSSIBLE CAUSES RECOMMENDED REMEDIES
SHORT SEAL LIFE • Abrasive particles in fluid
• Seal running too hot
• Equipment mechanical misaligned
• Prevent abrasives from accumulating at seal faces. Flush line maybe required. Use abrasive separator or filter.
• Increase cooling of seal faces (for example, by increasing flush line flow). Check for obstructed flow in cooling lines.
• Align properly. Check for rubbing of seal on shaft.
Go Back to Menu
WPIL LTD. [email protected] 201183
PUMP START-UP & OPERATION (Trouble shooting chart)
6.3.10 MECHANICAL SEAL LEAKS
TROUBLE INDICATOR
POSSIBLE CAUSES RECOMMENDED REMEDIES
MECHANICAL SEAL LEAKS STEADILY (OPTIONAL)
• Faces not flat• Blistered carbon graphite
seal faces
• Secondary seals nicked or scratched during installation
• Worn out or damaged O-rings
• Compression set of secondary seal (hard and brittle)
• Chemical attack (soft and sticky)
• Spring failures• Erosion damage of
hardware and/ or corrosion of drive mechanism
• Check for incorrect installation dimensions.• Check for gland plate distortion due to over-
torquing of gland bolts. Improve cooling flush line, if overheated. Check gland gasket for proper compression. Clean out any foreign particles between seal faces and re-lap faces. Check for cracks and chips at seal faces during installation. Replace primary and mating rings, if damaged.
• Replace secondary seals.
• Check for proper seal selection with seal manufacturer.
• Check for proper lead-in on chamfers, burrs, etc.
• Review with seal manufacturer for alternate materials selection.
• Replace parts.
• Review with seal manufacturer for alternate materials selection.
SEAL LEAKS INTERMITTENTLY
• Faces not flat• Blistered carbon graphite
seal faces
• Secondary seals nicked or scratched during installation
• Worn out or damaged O-rings
• Compression set of secondary seal (hard and brittle)
• Chemical attack (soft and sticky)
• Spring failures• Erosion/Corrosion
damage of hardware
• Check for incorrect installation dimensions.• Check for gland plate distortion due to over-
torquing of gland bolts. Improve cooling flush line, if overheated. Check gland gasket for proper compression. Clean out any foreign particles between seal faces and re-lap faces. Check for cracks and chips at seal faces during installation. Replace primary and mating rings, if damaged.
• Replace secondary seals.
• Check for proper seal selection with seal manufacturer.
• Check for proper lead-in on chamfers, burrs, etc.
• Review with seal manufacturer for alternate materials selection.
• Replace parts.• Review with seal manufacturer for alternate
materials selection.• Check for square-ness of stuffing box to shaft. • Align shaft, impeller and bearing to prevent
shaft vibration and/or distortion of gland plate and/or mating ring.
Go Back to Menu
WPIL LTD. [email protected] 201184
PUMP START-UP & OPERATION (Trouble shooting chart)
6.3.11 USING TOO MUCH POWER
TROUBLE INDICATOR
POSSIBLE CAUSES RECOMMENDED REMEDIES
USING TOO MUCH POWER
• Speed too high
• Improper impeller trim
• Total head of system lower or higher than pump design head
• Pump out of alignment or shaft bent
• Pumping sand, silt, or foreign material i.e. heavier liquid than allowed for
• Check voltage and frequency on motor.
• Pull pump and inspect. Modify existing impeller to provide actual system requirements.
• Take suitable measure to reduce the friction losses or static lift or replace the pump.
• Check alignment of pump and driver, also foundations.
• Test liquid for viscosity and specific gravity.
Go Back to Menu
WPIL LTD. [email protected] 201185
MAINTENANCE OF THE PUMP
7.1 PREVENTIVE MAINTENANCE TABLE
It is recommended that a maintenance plan and schedule is adopted, in line with the user instructions. It should include the followings :
S# Stage Preventive maintenance checks/actions
1 Pump start-up • Static lift/water level in the sump is adequate and that sump
water level are within the recommended value.
• If the pump sets have been stored for more than three
months, the bearing housing should be cleaned and old
grease should be washed out. Re-grease the bearing housing
DE and NDE side as per recommendation specified in manual.
Refer lubrication chart (7.3.6).
• Ensure that the pump is properly primed by opening the vent
on pump top casing and shut the vent after ensuring that the
entrained air is removed.
• Ensure that pump shaft is free in rotation.
• Startup the prime mover on no load condition to check the
direction of rotation.
• Ensure that suction valve is fully open.
• Ensure that delivery valve is closed. The pump may be started
with a fully opened delivery valve in case NRV is fitted.
• Start the pump through panel or local station.
• Allow pump to reach its full speed and check the pressure
gauge reading. At this point the pump should generate a
pressure higher than its rated pressure. If the pressure is
lower than rated pressure, stop the pump and investigate.
Rectify the fault and re-prime the pump before re-start.
• If pressure is within satisfactory limits than slowly open the
delivery valve, to permit charging the line.
• Gradual opening to maintain equilibrium is recommended.
WPIL LTD. [email protected] 201186
• Care to be taken to avoid prolonged operation at near close
valve condition.
• The pump set should be allowed to run for one hour or so to
observe any undue change in performance parameter.
• The delivery sluice valve should be closed prior to going in to
STOP mode.
• Do not go in to start mode when pump rotor is subjected to
reverse flow or reverse rotation.
2. Pump operation • Change grease in bearing housing every 1000 hours running.
• Grease motor bearings as per motor manufacturer’s instruction.
• Adjustment of gland packing / change of gland packing in case of leakage.
• Pack grease at every 500 hours of operation.
• Check temperature of motor bearings, motor winding and pump bearing. Bearings will normally run between temperatures of 30º to 60ºC.
• Any abrupt change in bearing temperature is much more indicative of trouble than a constant high temperature. If so than it is to be investigated and rectified.
• Check input current, voltage, frequency, sump water level, suction and discharge pressure gauge readings and enter all the observations in log book with date and time at-least once in a day.
• Tighten all loose bolts and check for excessive vibration.
• Check for some excessive leakage through stuffing box while the pump is in operation. If the leakage can not be reduced by gland adjustment than replace the packing as per 7.3.1
3. Temporary shut-
down
• The discharge valve should be closed before shutdown of the pump to prevent back flow.
• If NRV is installed in the delivery line then discharge valve can be closed after shutdown the pump.
Go Back to Menu
WPIL LTD. [email protected] 201187
MAINTENANCE OF THE PUMP
7.2 RECOMMENDED SPARE PARTS AND ORDERING PROCEDURE
7.2.1 PROCEDURE FOR ODERING SPARE PARTS:
• List the serial number and model of the pump (refer the name plate).
• List the part number (from the Bill of Material in cross sectional drawing).
• List the Quantity.
• List the complete Part Description (from the Bill of Material in cross sectional drawing).
7.2.2 RECOMMENDED LIST OF SPARE PARTS SUBJECT TO MOST WEAR.
• Impeller ring with grub screw/ casing ring.
• Line bearing in case of vertical pump assembly.
• Shaft sleeve with ‘O’ ring.
• Gland Packing.
• Complete Mechanical Seal (optional).
Go Back to Menu
WPIL LTD. [email protected] 2011
To ensure continued satisfactory operation, replacement parts to the original design specifications should be obtained from WPIL. Any change to the original design specifications
i.e. modifications or use of a non standard part will invalidate the pump safety certification.
88
MAINTENANCE OF THE PUMP
7.2.3 RECOMMENDED LIST OF SPARE PARTS TO BE STOCKED IF DOWN TIME IS
CRITICAL. (Refer Sectional Drawing Fig. 7.3.3 for part no’s.)
NAME OF PART PART No. QUANTITYCasing ring with anti rotation pin 03, 24 02Stuffing box packing rings (Sets) 15 02Shaft sleeve with ‘O’ ring 07, 18 02Seal cage/ Lantern ring (Sets) 16 02Water thrower/ Deflector 17 02Bearing lock nut with washer 13 01Bearing cover gasket - 02Casing split flange gasket - 01Bearing (DE & NDE) 09 02Mechanical seal (optional) - 02
Go Back to Menu
WPIL LTD. [email protected] 201189
MAINTENANCE OF THE PUMP
7.3 MAJOR MAINTANENCE OF PUMP
7.3.1 PACKING BOX ASSEMBLY / MECHANICAL SEAL
The major cause of the packing box troubles are due to excessively or unevenly tightened packing / correct fitment of mechanical seal especially during the first hour of operation.
WE WOULD CALL THE ATTENTON OF THE USER ON THE FOLLOWING RECOMMENDATIONS.
Over tightening would immediately damage the packing.
To replace a damaged / worn out packing, following steps should be taken:
• Remove split packing gland, old packing ring & finally lantern and end packing.
• If pump is fitted with mechanical seal, then remove gland plate and mechanical seal, (refer fig. 5.4.5a).
• Prepare bevel-cut packing ring, carefully made according to the dimension of recesses. This packing ring should be same grade as original packing.
• Insert the packing ring by staggering the bevel-cut and fit it in original position. Reinstall the split packing gland and tighten it gradually.
Go Back to Menu
WPIL LTD. [email protected] 2011
Put a warning board on starting device with words.
MACHINE UNDER REPAIR :
DO NOT START/CONNECT
90
MAINTENANCE OF THE PUMP
7.3.2 BEARINGS
GREASE LUBRICATED BEARINGS:
• Only Bearing grade grease should be used .Never use pink greases. Use Lithium based Grease suitable for use up to 100 degree Celsius.
• Pack grease moderately to avoid overheating of Bearings.(preferably every 500 hrs).
• All pumps with grease lubricated bearings are greased at the factory. As a secondary precaution, check and re-grease the bearing before starting the unit so as to ensure proper lubrication. This is recommended if the pump has been stored for three months or more.
• One third to half of the volume in the housing should be filled with grease for normal applications. This will give the most ideal operating conditions. Greasing has to be done by a grease gun through the grease plug provided in the bearing housing.
Go Back to Menu
WPIL LTD. [email protected] 2011
Complete Overhauls
This depends on hours of operations of the pump/ the severity of the condition of service.
Do not open the pump for inspection unless there is an indication of trouble inside the pump or in the bearings.
91
MAINTENANCE OF THE PUMP
7.3.3 PUMP ASSEMBLY (U) REMOVAL
Refer to the sectional drawing before dismantling of the pump (Fig. 7.3.3).
Fig. 7.3.3
Go Back to Menu
WPIL LTD. [email protected] 2011
Typical View of U Pump Assembly
92
MAINTENANCE OF THE PUMP
Cross Sectional Assembly
Fig: 7.3.3
Go Back to Menu
WPIL LTD. [email protected] 201193
MAINTENANCE OF THE PUMP
7.3.3.1 COMPLETE ROTATING ASSEMBLY REMOVAL
Care must be exercised in dismantling operation to prevent damage to parts of the pump.
Following points must be kept in mind during dismantling of the pump.
• Following Table 7.3.3.1 should be used for applying the fasteners torque.
Go Back to Menu
WPIL LTD. [email protected] 2011
The pump is separated from the drive after the pump has been electrically isolated & pump
casing is drained down.
For convenience at re-assembly, layout all parts in the order in which they are removed.
Protect all machined faces against metal to metal contact and corrosion.
94
MAINTENANCE OF THE PUMP
Screw/bolt sizeTorque Nm (lbf-ft)
Pump feet fasteners All other fastenersM8 (5/16 in.) - 10 (7)M10 (3/8 in.) - 20 (15)M12 (1/2 in.) 63 (46) 34 (25)M16 (5/8 in.) 170 (125) 84 (62)M20 (3/4 in.) 340 (250) 165 (120)M24 (7/8 in.) 590 (435) 285 (210)
Table 7.3.3.1
• Withdraw the coupling guard and remove the coupling nut, bolts, distance pieces, washers applicable to flexible pin bush type coupling. For any other type of coupling, refer the manufacturer brochure.
• Remove the sealing pipe (item 20) connected to the pump top half casing (item 02).
• Withdraw dowel pins fitted in bearing housing (item 10) and loosen studs and nuts.
• Remove bearing housing studs and nuts.
• Remove hexagonal screws for bearing end covers (item 11,12) and slide the end covers from location to reset on the shaft.
• Disconnect the glands (item 14) from casing by unscrewing nuts from gland’s studs.
• With a suitable punch, drive out the two straight roll pins which are used at the horizontal split to align the upper (item 02) and lower casing halves (item 01).
• Remove the bolts which hold the upper and lower half of the casing together.
• By use of jacking screws located on the casing ease off the top half through equal jacking up and sling the top half casing (item 02) through the eye bolts provided at the top of the casing. Lift and place on the wooden supports.
Go Back to Menu
WPIL LTD. [email protected] 201195
MAINTENANCE OF THE PUMP
• Remove split flange gasket carefully and store.
• Sling the rotor assembly and carefully lift out from the bottom half casing in a perfectly horizontal plane as the coupling weight will tend to move the rotor towards the prime-mover during hoisting operation.
7.3.3.2 DISMANTALING OF ROTOR SHAFT
The rotor assembly is removed as described in 7.3.3.1.Under mentioned procedure should be followed for dismantling:
• Lift out the rotor assembly. Use care in slinging, handling and supporting of the rotor for subsequent dismantling.
• Remove the impeller wearing ring (item 06) by removing the locking grub screw (item 22).
• Withdraw the pump half coupling from the shaft (item 04) by means of puller and withdraw the coupling key.
• Withdraw the DE bearing housing (item 10). Note that the bearing is in interference fit with the bearing housing (item 10) hence withdraw should be square with the bore/shaft.
• Withdraw the DE bearing (item 09) from bearing housing by suitable puller.
• Remove DE & NDE bearing housing end covers (item 11,12) and slide bearing housing off the bearings.
• Remove water thrower (item 18) from the shaft.
• Remove gland packing (item 15) and lantern ring/seal cage (item 16).
• Withdraw the sleeve nut (item 08).
• Remove both the sleeves (item 07) from the shaft.
Go Back to Menu
WPIL LTD. [email protected] 2011
Casing neck rings will be dislodged with the rotor. Hence care to be taken during hoisting
to prevent falling off.
96
MAINTENANCE OF THE PUMP
• Remove impeller (item 05) and impeller key (item 24).
• Withdraw the NDE bearing housing (item 10).
• Release the bearing lock washer at the NDE and remove bearing nut (item 13).
• Remove the NDE bearing (item 09) and distance piece.
• Remove water thrower (item 18), gland packing (item 15) & lantern ring/seal cage (item 16).
• The rotor is fully dismantled for inspection and repair.
7.3.3.3 METHOD OF REMOVING DOWEL BUSHING :
As shown in sectional drawing (fig. 7.3.3) accurate alignment between the casing and bearing brackets is obtained with the use of straight hollow dowel bushings. The dowel bushings have internal threads which are used for milling the dowels see fig. 7.3.3.3a which shows the dowel bushing puller installed in position as shown, tighten the hexagon head bolt to remove dowels.
Fig. 7.3.3.3a
Go Back to Menu
WPIL LTD. [email protected] 2011
All individual parts, all important joints and all wearing surfaces should be carefully examined and parts appreciably worn should be renewed.
97
MAINTENANCE OF THE PUMP
7.3.3.4 RE-ASSEMBLY OF THE ROTOR ASSEMBLY:
To assemble the pump reverse the dismantling procedure as described in 7.3.3.2 & 7.3.3.1 respectively, except the following instructions.
• All bearings, wearing rings, gland packing ,sleeves should be checked and changed unless found in good. The gland packing details should be referred as per 5.4.4.
• Impellers should be checked, before assembly, for dynamic balancing to grade 6.3 of ISO 1940.
• Shaft to be checked for its trueness on V roller support on an inspection table. Pump shaft run out should be checked within 0.05 mm.
• At bearing, impeller and coupling locations, the maximum permissible run out is 0.05 to 0.07 mm total indicated reading.
• The clearance between impeller and casing neck ring should be maintained to the recommended values. Renewal is recommended when the worn value is twice the clearance. The diameter clearance value normally lies between 0.4 to 0.6 depending on the model size and may be obtained from the pump manufacturers for the given pump model.
• When reassembling the impeller on the shaft, it is important to mount the impeller so that the vane tips point away from the apparent flow direction. The rotor always rotates towards increasing sections of the volute as shown in fig. 7.3.3.4
• Install the rotor in the casing and check to see that the rotor rotates freely by hand, wearing surfaces at the impeller should not touch. Align the pump carefully and install the packing and seal cage.
Go Back to Menu
WPIL LTD. [email protected] 201198
MAINTENANCE OF THE PUMP
FIG. 7.3.3.4
7.3.4 RE-ASSEMBLY OF THE PUMP UNIT:
The rotating element is now fully assembled as described in rotor assembly 7.3.3.4. The further steps for pump assembly shall be followed as under.
• Clean the casing and remove any protrusions on split flange of casing.
• Ensure threads, gaskets and ‘o’ ring (item 19) mating faces are cleaned. Apply thread sealant to non face sealing pipe thread fittings.
• Fit casing gasket to the bottom half horizontal flange using a small amount of contact adhesive to prevent movement when the top half is fitted. Do not apply adhesive to the top surface of the gasket.
• Hoist the rotor assembly (as described in 7.3.3.4) and gradually lower in to the bottom half casing (item 01). Care to be taken to see that neck rings and bearing housing get positively located at spigot area.
• Unlock the rotor assembly from the sling after locating in bottom half casing.
• Fit the NDE bearing housing. Note that bearing is interference with the bearing housing. Hence fitment should always be square to the bore/shaft.
• Fit the DE bearing housing. Note that bearing is interference with the bearing housing. Hence fitment should always be square to the bore/shaft.
Go Back to Menu
WPIL LTD. [email protected] 201199
MAINTENANCE OF THE PUMP
• Apply grease of the recommended type to the bearings.
• Locate dowel pins in bearing housing and insert studs through bearing housing and tighten nuts both on DE & NDE sides.
• Fix hexagonal screws to bearing housing end covers and tighten in position.
• Now rotate shaft and ensure free rotation.
• Apply a light layer of grease on split flange bottom half and locate gasket in position, ensuring that bolt holes are all clear from any obstruction.
• Fix dowel pins to casing top half.
• Hoist the top half casing (02) and slowly lower on to the bottom half. Ensure perfect match of the bolt holes. The dowel pins to be tapped in position.
• Torque up the fixing screws. Firmly secure casing with nuts and bolts as per sequence as shown in fig. 7.3.4
• Torque up the fixing screws.
• Rotate the shaft and ensure the free rotation.
• Connect water seal pipes and other accessories.
• Fit the coupling and align the pump and motor unit.
• If mechanical seals are fitted, a small amount of silicon rubber sealant along the horizontal joint line on the stuffing box face and fit the seal cover complete with gasket or ‘o’ ring.
• Care must be taken to ensure the seal seat bore is concentric to the shaft sleeve and it can be achieved using filler gages between the stationary seal seat bore and the shaft sleeve.
• Torque up the seal cover screws and check shaft/sleeve does not rub on seal cover or stationary seal seat bore.
Go Back to Menu
WPIL LTD. [email protected] 2011100
MAINTENANCE OF THE PUMP
7.3.5 DISMENTALING AND RE-ASSEMBLY OF U PUMPS
In U pump models, the horizontal pump unit is installed vertically along with pump and motor stools directly coupled with motor (fig. 7.3.5.a). In some cases intermediate shafts and bearings are used between the pump and motor. Since the horizontal pump unit is installed vertically hence the dismantling and re-assembly procedure will remain same except the following steps.
• Isolate the electrical connections of the motor.
• Remove the motor half coupling bolts and free the coupling.
• Hoist the motor from the motor stool after removing the motor stool bolts on motor side.
• Remove the motor stool from the pump after removing the motor stool bolts from pump side.
• Remove the upper half casing after disconnecting the sealing lines and other accessories.
• While lowering the casing upper half over the lower half, take care to ensure that the wearing rings are correctly located in the upper half bores.
• The remaining steps shall be followed as per 7.3.3.1, 7.3.3.2, 7.3.3.3, 7.3.3.4
Go Back to Menu
WPIL LTD. [email protected] 2011
RECOMMENDATION
For Grease/Oil Lubrication, Refer Table 7.3.6.1 & 7.3.6.2
101
MAINTENANCE OF THE PUMP
Fig. 7.3.5.a
Fig. 7.3.5.a
Go Back to Menu
WPIL LTD. [email protected] 2011
102
MAINTENANCE OF THE PUMP
7.3.6 LUBRICATION CHART
7.3.6.1 Recommended Grease Lubricants
Manufacturer Grease Ball & Roller BearingsESSCO Petroleum Co. Ltd. Beacon 2 or Beacon 3Mobile Companies Throughout the world Mobilux Grease No. 3 or Mobilplex 48Shell Companies throughout the world Shell Alvania Grease 3Caltex Caltex Multifak 2Castrol Castrol Spheerol AP 3Indian Oil Servogem 3
Table 7.3.6
7.3.6.2 Recommended Oil Lubricants
Table 7.3.6.1
Go Back to Menu
WPIL LTD. [email protected] 2011
It is unsafe to mix greases of two or more grades for use in ball bearings.
103
MAINTENANCE OF THE PUMP
7.4 REFRENCE DRAWING, MATERIAL OF CONSTRUCTION & TECHNICAL DETAILS
Reference drawing, material of construction & other technical details refer the following drawing for respective jobs
General arrangement drawing.
Cross-sectional drawing.
For any correspondence/ordering spares, please quote the following.
CUSTOMER :
PROJECT :
WPIL REF. :
PUMP MODEL :
PUMP SERIAL No. :
Go Back to Menu
WPIL LTD. [email protected] 2011104
Contact Details
Contact WPIL
For any complaints and suggestion regarding Pumps
Email us: [email protected]
Phone: +91-120-3015784
Fax: +91-120-3015740
Factory Address:
WPIL LIMITED
A-5, Sector XXII, Meerut Road,
Ghaziabad - 201002, (U.P.), India
Corporate Office Address:
WPIL Limited
Trinity Plaza, 3rd Floor,
84/1 A, Topsia Road (South)
Kolkata 700 046, India
P: +91.33.3021.6800
F: +91.33.3021.6835
Go Back to Main Menu
WPIL LTD. [email protected] 2011105