Attach inline pressure gauge at pump
panelA section of 2 1/2 will need to be used between the pressure gauge and
the hose being tested
Attach the gated valve between 2 1/2
section and hose to be tested
The gated valve should be open at this time
Use necessary adaptors to attach a nozzle at the
end of hose you are testing to allow you to bleed
the air out of the system
Use a marker to mark all hoses at
couplingsThis will give you a visual if a coupling is loose on the
hose