Date post: | 05-Jul-2018 |
Category: |
Documents |
Upload: | ahmed-azad |
View: | 215 times |
Download: | 0 times |
of 48
8/16/2019 Hospital Vent
1/48
COMPONENTS FOR MEDICAL PREMISES
AND SURGERIES IMPLEMENTATION
medical
HEALTH CARE
8/16/2019 Hospital Vent
2/48
8/16/2019 Hospital Vent
3/48
P r t t o n p n e l b a s i c
Cat.No. 102.01 B
PaRTiTiON PaNEL
The product has been cert if ied in EU countr ies.
basic
In the premises established by the partition panels overpressure
or urderpressure maintaining is guaranteed due to their tight
connection between the panels, floor, and ceiling, which fact
meets the basic criteria for cleanrooms for which these panels
have been specially designed and verified in practical operation.
COMPONENTS FOR MEDICAL PREMISES
AND SURGERIE S IMPLEMENTATIONmedical
The basic partition panels
represent one of the basic
elements for the construc-
tion of cleanrooms and
workplaces with maximum
safety, sterility, hygiene,
simple maintenance, and
sanitation.
Due to their design
they are mainly suitable
for hospitals, pharmaceu-
tical, electrical, enginee-
ring, foodstuff, and chemi-
cal industry premises.
8/16/2019 Hospital Vent
4/48
Colour shadeand materialof the coat
two-side zinc-coated steel sheet, surface treated, protected by PE foil,
standard colour: RAL 9010, 9002, 6027 or 1015
two-side zinc-coated steel sheet, surface treated, colour to order
AISI 304 FIN 8 stainless steel sheet, protected by PE foil
zinc-coated sheet (HVAC panels)
mutual combination of the above designs
Prole types
for xing the panels tothe oor
„Basic“- type prole
„U“- type prole, with Al cavetto„U“- type prole
Side-type ending Ending to be specied together with a seller
Lower-type ending Ending to be specied together with a seller
Bottom-type ending Ending to be specied together with a seller
Side reinforcement
left
right
no reinforcement
Bushings
from the left side number and distance from the partition edge to be determined
from the right side number and distance from the partition edge to be determined
no bushing
Openingrequired dimension, number, and placing to be specied
no opening
BLOCK a.s., U Kasáren 727, 757 01 Valašské Meziříčí, tel.: +420 571 670 111, fax: +420 571 670 244, e-mail: [email protected], www.block.cz
102.01 B PARTITION PANEL BASIC
ANCHORING AND INSTALLATION
DESCRIPTION
THE PANELS
• Sandwich type, consisting of external coat
and optional material fill
• Connected by mutual slipping over, self-supporting
• Full or glazed by indoor pharma-glazing
( t h e g l a z i n g , s e e C a t . N o . 1 0 3 )
• Above-the-door panel
• At-the-door panel
• Installation panel for the media distribution lead,
as a standard, from the floor or from above soffit.
Installation column, width 200÷400 mm
• May be completed with bushings for electric feeders
• May be provided with HVAC grids
ALL SHAPES AND DESIGNS OF THE BASIC PARTITION PANELSMEET PARAMETERS REQUIRED FOR EXPLOSIVE ENVIRONMENT
TECHNICAL DATA
OPTIONAL ELEMENTS
ACCESORY AND RELATED PRODUCTS
Cat.no. 103 Partition wall glazing
Cat.no. 102.02 Fire-resistant panels
FILLS OF THE PARTITION PANELS
ADVANTAGES OF THE PARTITION PANELS• quick installation and dismantling to enable flexible space layout change• simple maintenance• long-lasting appearance• anti-corrosion protection• thermal and sound insulation
Thickness[mm]
Preferredheight [mm]
Max. **panelheight [mm]
Standard width ***[mm]
Weight/surface ratio in relation to the ll [kg/m2]
PSE-SF Styrofoam IB Mineral wool
60 / 62*/
2550, 2750,3050
4200 1190, 640, 830
13.7 14.3 18.5
80 / 82*/ 14.0 14.8 20.5
100 / 102*/ 14.4 15.4 22.5
120 / 122*/ 14.8 16.0 24.5
*** Panels with a different width are to be made as atypic al, max. panel width 1190mm
FillThickness
[mm]Density[kg/m3]
Max. loadtemperature [°C]
Thermal conductivityfactor K [W/m.K]
Flammability
PSE-SF 58, 78, 98, 118 18 +70 0.0365 B
Styrofoam IB 60, 80, 100, 120 28 +75 0.035 C1
Mineral wool 58, 78, 98, 118 100, 150 +900 0.040 B
Coat
Fill
„BASIC“- type profile
B P
• 0 6
• 0 2
** For higher walls, the panels are assembled as for height to reach required dimension
* Panel thickness with the Styrofoam IB fill will be increased by 2 mm
FIXING THE PANEL TO THE FLOOR
• Fixing of the panel to the floor • slipping over profiles - either the “Basic” or the „U“-type profiles
• Panel fixed, above soffit, to the constructionceiling or auxiliary structure
• according to space layout requirementsand interacting with other componentsof an implemented building, by means
of the „U“- type profile
„BASIC“- type profile
„U“- type profile
„U“- type profile, with Al cavetto
Cement
PVC floor
Underlay profil
Cement
Al cavetto
Poured floor
MAINTENANCE AND CLEANING
To be cleaned by non-abrasive disinfecting cleaning
agents, or by slightly abrasive disifecting cleaning
agents (applicable only for the ground/matt surfaces,
only in the grinding direction) based on butyl alcohol(stains, fingerprints); based on acids where heavier
pollution occurs (mineral sediments, corrosion due
to HCl).
Concentration to be chosen in relation to the
pollution extent.
•
„U“- type profile
Cat.no. 102.05 Soundproofng panels
Coat„U“- type profile
medical
8/16/2019 Hospital Vent
5/48
F
i r e - r e s i s t a n t p a r t i t i o n w a l l p a n e l Cat. No. 102.02 B
FIRE-RESISTANT PARTITION WALL PANEL
The fire-resistant pa-
nels are sandwich
type; they consist
of a coat and insi-
de fil l. Mineral wool
has been used as the
panel fil l.
For electrical feeders,
electrical bushings
may be installed
in the panel fil l.
The fire-resistant par-
tition walls are desig-
ned in the EI15/EW30
fire resistance.
The guaranteed pa-
nels fire resistance,
complying with rele-
vant regulations, has
been tested in a natio-
nal test facility.
The product has been certified in EU countries.
EI15 / EW30 FIRE RESISTANCE
COMPONENTS FOR MEDICAL PREMISES
AND SURGERIES I MPLEMENTATIONmedical
8/16/2019 Hospital Vent
6/48
102.02B FIRE-RESISTANT PARTITION WALL PANEL
EI15/EW30 FIRE-RESISTANT PANEL
Basic partition wall panels with a specific connection system
Minimum panel thickness - 60 mm• Coat - face, rear• Fill - mineral wool of min. density
100 kg/m3
• Fire-resistant protection sheet• Metal bushings for el. feeders
BEING CONDUCTIVELY INTERCONNECTED, THE FIRE-RESIS-TANT PARTITION WALL PANELS MAY BE USED IN EXPLOSIVEENVIRONMENT, ZONE II
B P
• 0 6
• 0 8
DESCRIPTION
FIXING OF THE PANEL TO THE FLOOR
FIRE RESISTANCE
INSTALLATIONInstallation and possible dismantling shallbe carried out exclusively by a company autho-rised to do so.
EI15/EW30 PANEL
** Panels of different width must be produced as atypical (max. panel width is 1,190 mm)
EI15/EW30 FIRE-RESISTANT PANELS - TECHNICAL DATA
Thickness[mm]
Height*[mm]
Standard width[mm]**
EI-type fireresistance [min]
Area weight[kg/m2]
60 max. 4200 640, 1190 15 18.5
EI15/EW30 FIRE-RESISTANT PANELS - MINERAL WOOL FILL
FillThickness
[mm]Density[kg/m3]
Maximumloading tem-perature (ºC)
Thermal con-ductivity factor
K (W/m.K)Flammability
Nobasil 58 100, 150 +900 0.040 B
Conrock 58 100 +1000 0.040 A
OPTIONAL ELEMENTS
Colour shade
and material
of the
- face side
- rear side
two-side zinc-coated steel sheet, surface treated, protected
by PE foil, standard colour RAL 9010, 9002, 6027, and 1015
two-side zinc-coated steel sheet, surface treated, protected
by PE foil, colour to order
stainless steel sheet, AISI 304 FIN 8, protected by PE foil
zinc-coated sheet (HVAC panels)
mutual combination of the above specified items
Side ending ending to be specified together with a seller
Bottom ending ending to be specified together with a seller
Top ending ending to be specified together with a seller
Side strut
simple strut - right-side, left-side
strut with a fire resistant facing - right-side, left-side
no strut
Bushing from right side
number and distance from
the edge to be determined
no bushing
EI15/EW30
• 15 minutes for the panel thickness 60 mm
* Preferred height - 2,500; 2,750; 3,050 mm
MAINTENANCE AND CLEANING
To be washed by non-abrasive disinfecting cleaning
agents, or by slightly abrasive disinfecting cleaning
agents (for ground/matt surface only; always clean
in the grind direction) based on butyl alcohol
(stains, fingerprints); based on acids where heavier
pollution occurs (mineral sediments, corrosion due
to HCl).
Concentration to be selected in relation to the pollu-
tion extent.
ADVANTAGES OF THE PARTITION WALL PANELS
• Quick installation and dismantling to enable flexible space layout change.• Simple maintenance• Long-lasting appearance
• Anti-corrosion protection• Thermal and sound insulation
Electrical bushing
Fill
Fire-resistantprotectionsheet Coat
Slip-over direction
ACCESSORIES AND RELATED PRODUCTS
Cat. No. 104.05 Fire-resistant door
Panel
PVC oor
Cement
Underlay rubber proleProle
medical
BLOCK a.s., Stulíková 1392, 198 00 Praha 9, Czech Republic, tel.: +420 571 670 111, e-mail: [email protected], www.block.cz
8/16/2019 Hospital Vent
7/48
P l a s t e r b o a r d f a c i n g p a n e l
Cat. No. 102.03 B Cat. No. 102.01 B
PLASTERBOARD FACING PANEL
Together with the partition
panel system, the plaster-
board panel represents
one of the basic elements
for building cleanrooms and
facilities with maximum pos-
sible safety, sterility, hygie-
ne, simple maintenanceand sanitation.
It is used for facing of exi-
sting walls of a building. Its
advantage is the simplicity,
quick installation and dis-
mantling, price and small
thickness.
PARTITION WALL
FACING PANEL
The panel is of sandwich
type, consisting of a coat
and inside fill of various
variants, with the thi ckness
32 mm.
P a r t i t i o n w a l l f a c i n g p a n e l
The product has been cert if ied in EU countr ies.
Top anchoring Bottom anchoring
medical COMPONENTS FOR MEDICAL PREMISESAND SURGERIE S IMPLEMENTATION
8/16/2019 Hospital Vent
8/48
Panel thickness[mm]
Height[mm]
Standard width*[mm]
Weight[kg/m2]
C B A
19 2350, 2550, 3000 640 14
19 2350, 2550, 3000 1190 20
BLOCK a.s., U Kasáren 727, 757 01 Valašské Meziříčí, tel.: +420 571 670 111, fax: +420 571 670 244, e-mail: [email protected], www.block.cz
102.03 B PLASTERBOARD FACING PANEL
B P
• 0 6
• 0 6
BASIC DIMENSION LINE - PLASTERBOARD FACING PANEL CONNECTION OF THE PANELS - SLIPPING OVER
FIXING OF THE FACING PANEL
102.01 B PARTITION WALL FACING PANEL
FILL OF THE PARTITION WALL FACING PANEL
DESCRIPTION
OPTIONAL ELEMENTS OF THE PARTITION WALL FACING PANEL
* Panels of different widths must be produced as atypical (max. panel width is 1,190 mm).BASIC DIMENSION LINE - PLASTERBOARD FACING WALL PANEL
PLASTERBOARD FACING PANEL
PARTITION WALL FACING PANEL
PARTITION WALL FACING PANELPLASTERBOARD FACING PANEL
Panel thickness[mm]
Height[mm]
Standard width*[mm]
Weight[kg/m2]
C B A
32 max. 4200 1190, 640 according to the used ll
• One coat (fair-face)- optional colour and material
• Pasted-in plasterboard
(15 mm thick)
• Anchored into floor
- by means of a guide
profile
• Coat (fair-face) - optional colour and material
• Fill
- optional material
• Struts
• Coat (rear)
- zinc-coated sheet
• Anchoring into floor
- by means
of a guide profileFair-face coat
Fair-facecoat
Plasterboard
Fill Thickness[mm]
Density[kg/m3]
Max. loadingtemperature
[C°]
Thermal conductivityfactor K [W/m.K]
Flamma-bility
PSE-SF 30 18 +70 0.0365 B
Styrofoam IB 30 28 +75 0.035 C1
Nobasil 30 100, 150 +900 0.040 A
Conrock 30 100 +1000 0.040 B
Colourand material ofthe fair-face coat
two-side zinc-coated steel sheet, surface treated, protected by PE foil,
standard colours RAL 9010, 9002, 6027 a 1015two-side zinc-coated steel sheet, surface treated, colour to order
stainless steel sheet, AISI 304 FIN 8, protected by PE foil
mutual combination of the above specied items
Fill
PSE-SF - foam polystyrene, self-extinguishing, in compliance with DIN 18164
Styrofoam IB - extruded polystyrene foam with good mechanical strength
Conrock - felt with thermal, sound, and re insulation (mineral wool)
Nobasil - felt with thermal, sound, and re insulation (mineral wool)
MAINTENANCE AND CLEANING
To be washed by non-abrasive disinfecting cl eaning
agents, or by slightly abrasive disinfecting cleaning
agents based on butyl alcohol (stains, fingerprints);
based on acids where heavier pollution occurs
(mineral sediments, corrosion due to HCl).
Concentration to be selected in relation to the pollu-
tion extent.
PVC
FACINGPANELExisting
wall
Bottomguideprofile
Topguideprofile
Floor
OPTIONAL ELEMENTS OF THE PLASTERBOARD FACING PANEL
Colourand material ofthe fair-face coat
zinc-coated sheet, MYRIAD, colour RAL 9010
zinc-coated sheet, MYRIAD, colour RAL 9002, 6027, 1015
stainless steel, AISI 304, FIN8 grind
zinc-coated sheet
Komaxit of RAL colour
C
B
A
B
A
C
* Panels of different widths must be produced as atypical (max. panel width is 1,190 mm).
Coat, rear
Struts
Fill
medical
8/16/2019 Hospital Vent
9/48
W i n d o w n e l - p h a r m a - t y e g l z i n g
G l z i n g i n t o l s t e b o d t i t i o n w l l sCat.No. 103.01 B 103.06 B
WINDOW paNEL - pharma-TYpE GLaZING
Together with the partition
wall system, the fully gla-
zed window panel represent
one of the basic elementsfor the construction of clean-
rooms and facilities with
maximum safety, sterility,
hygiene, simple maintenance
and sanitation.
In question is the PHARMA
-type glazing, i.e. the two-sided
glazing, where the glassplates are flush with the pa-
nel surface. Due to its
layout it is suitable, first of
all, for hospitals, for phar-
maceutical, electrical, engi-
neering, and foodstuff in-
dustry facilities etc.
aLONG ThE WhOLE paNEL LENGTh
GLaZING INTO pLaSTErBOarD
parTITION WaLLS
The product has been certified in EU countries.
medical COMPONENTS FOR MEDICAL PREMISESAND SURGERIE S IMPLEMENTATION
8/16/2019 Hospital Vent
10/48BLOCK a.s., U Kasáren 727, 757 01 Valašské Meziříčí, tel.: +420 571 670 111, fax: +420 571 670 244, e-mail: [email protected], www.block.cz
103.01 B WINDOW PANEL - PHARMA-TYPE GLAZING
B P
• 0 6
• 0 6
TECHNICAL PARAMETERS OF THE PHARMA - TYPE GLAZING ADVANTAGES OF THE WINDOW PANELS
CONNECTION OF THE PLASTERBOARD WITH THE GLAZING
103.06 B GLAZING INTO PLASTERBOARD PARTITION WALLS
Partition panel(Cat. No. 102.01)
Glazing
Plasterboard
Glass
* operated from one side only
ACCESSORY AND RELATED PRODUCTS
Ct.No. 102.01 Prtton pnel - basiC
Ct.No. 102.03 Fcng pnel
Ct.No. 105 soft
Ct.No. 107 Lght ttng
TECHNICAL PARAMETERS OF THE GLAZING INTO PLASTERBOARD PANELS
WINDOW PANEL - PHARMA - TYPE GLAZING FOR THE WHOLE PANEL WIDTH
• Quick installation and dismantling, ena-
bling flexible change of the spatial layout.
• The system of the window panels con-
nection is identical with the installation
system of standa rd partitions, i.e. by means
of mutual slip-over.
• The window panel flush with the both
surface sides of other partition panels.
A
B
C
Glazing
Plasterboard
A
B
C
OPTIONAL ELEMENTS POSSIBLE OPTION STANDARD OPTION
Width [mm] min. 640 - max. 1190 1190
Height [mm] min. 800 - max. 1500 1200, 1500
Thickness [mm] min. 60 - max. 120 60
Glazing typeoat glass, thick. 4 mm
foat glass, thick. 4 mmsafety laminated glass, thick. 6 mm
Sun-blind
mechanical
without sun-blindsmagnetic*
without sun-blinds
Window frame material steel, class 11 steel, class 11
Surface treatmentof the window frame
RAL 9010, 9002, 6027, 1015 metal sheet,colour RAL 9010AISI 304, FIN8 grind
A
B
C
CONNECTION OF TWO GLAZINGS
CONNECTION OF THE GLAZINGWITH THE PANEL
Glass
Glass
Glass
Cementing
Electrical bushing
Partition panel
OPTIONAL ELEMENTS POSSIBLE OPTION STANDARD OPTION
Width [mm] A min 640 - max. 1500 1000, 1200
Height [mm] B min 800 - max. 1500 1200, 1500
Thickness [mm] C min. 75 - max. 150 100, 120
Glazing typeoat glass, thick. 4 mm
oat glass, thick. 4 mmsafety laminated glass, thick. 6 mm
Window frame material steel, class 11 steel, class 11
Surface treatmentof the window frame RAL 9010, 9002, 6027, 1015 metal sheet,colour RAL 9010AISI 304, FIN8 grind
GLAZING INTO PLASTERBOARD PANELS
MAINTENANCE AND CLEANING OF THE BOTH GLAZING TYPES
• Glass may not be cleaned by acids, thinners, and by other chemical agents thatmay affect the protection silicon layer between a glass plate and a glazing molding.
• Upon a larger-scale integrity damage of the protection silicon layer it is necessaryto consult the defect removal with the manufacturer.
• Upon a glass crack, glass is exchanged exclusively by a company authorised bythe manufacturer.
• Any check on the installed glazing is inadmissible.
• To secure the quality of the surface treatment, the installed glazing may not be
subject to air humidity, in an object, higher than 60 %.
Glass
Electrical bushing
Cementing
Plasterboard
Glass
medical
8/16/2019 Hospital Vent
11/48
M e t a l p a r t i t i o n w a l l
a d d i t i o n a l g l a z i n g
Cat. No. 103.02B Cat. No. 103.03 B
METAL PARTITION WALL ADDITIONAL GLAZING
This glazing type is inserted into the existing parti-
tion wall panels, thickness 60, 80, 100, and 120 mm.
The window consists of a stiffening profile, cover
frames, and a sheet glass, 4 or 6 mm thi ck.
ONE-SIDED, TWO-SIDED
The product has been certified in EU countries.
medical COMPONENTS FOR MEDICAL PREMISESAND SURGERIES IMPLEMENTATION
8/16/2019 Hospital Vent
12/48
Note:Maximum dimensions of the construction opening are 1,500 x 1,800 mm! – the glazingmust be installed through two panels. This is an atypical product; it is always advanta-geous to consult the producer directly.
BLOCK a.s., U Kasáren 727, 757 01 Valašské Meziříčí, tel.: +420 571 670 111, fax: +420 571 670 244, e-mail: [email protected], www.block.cz
103.02B 103.03B METAL PARTITION WALL ADDITIONAL GLAZING
METAL PARTITION WALL ADDITIONAL GLAZING
Type - one-sided (Cat. No. 103.03) - two-sided (Cat. No. 103.02)
• Glazing clear glass as a standard, milk glass an atypical
• Panel thickness [mm]60, 80, 100, 120
- the panel with Styrofoam IB fill is by 2 mm more thick
• Panel weight, thickness 60 mm, (80 mm)
One-sided glazing - 21.4 kg/m2, (22.4 kg/m2)
Two-sided glazing - 37.4 kg/m
2
, (38.4 kg/m
2
)
B P
• 0 6
• 0 8
ONE-SIDED ADDITIONAL GLAZING
DESCRIPTION
ACCESSORY AND RELATED PRODUCTS
Cat. No. 102.01 Basic partition wall panels
DESCRIPTION
Optional elements Possible design Standard design
Width* [mm] 600, 800, 1000 800, 1000
Height* [mm] min. 800 - max. 1500 1200, 1500
Panel thicknessH [mm] min. 60 - max. 120 60
Glazing typefloat glass, thick. 4 mm
float glass, thick. 4 mmsafety laminated glass, thick. 6 mm
Colour shadeand material
of the cover frame
RAL 9010, 9002, 6027, 1015RAL 9010
Stainless steel, AISI 304, FIN8 grind
TWO-SIDED ADDITIONAL GLAZING
Optional elements Possible design Standard design
Width* [mm] 600, 800, 1000 800, 1000
Height* [mm] min. 800 - max. 1500 1200, 1500
Panel thickness [mm] min. 60 - max. 120 60
Glazing typefloat glass, thick. 4 mm
safety laminated glass, thick. 6 mmfloat glass, thick. 4 mm
Sun-blinds
mechanical sun-blinds
without sun-blindsmagnetic sun-blinds **
without sun-blinds
Colour shadeand material
of the cover frame
RAL 9010, 9002, 6027, 1015
Stainless steel, AISI 304, FIN8 grindRAL 9010
** operated from one side only
DIMENSION LINE
Recommended dimen-sions of the construc-tion opening [mm]
Glazing size [mm]
O n e
- s i d e d g l a z i n g
600 x 1200 548 x 1148
600 x 1500 548 x 1448
800 x 1200 748 x 1148
800 x 1500 748 x 1448
1000 x 1200 948 x 1148
1000 x 1500 948 x 1448
T w o - s
i d e d g l a z i n g
600 x 1200 548 x 1148
600 x 1500 548 x 1448
800 x 1200 748 x 1148
800 x 1500 748 x 1448
1000 x 1200 948 x 1148
1000 x 1500 948 x 1448
INSTALLATION
Installation and possible dismantling shall becarried out exclusively by a company authori-sed to do so.
TWO-SIDED ADDITIONAL GLAZING
ONE-SIDED ADDITIONAL GLAZING
A
A
B
H
B
H
Metalpartitionwall panel
Prole
CoverframeGlass
Cementing
A
BH
A
B
H
Note:
Standard dimensions in bold letters.
* construction opening A x B
* construction opening A x B
Metalpartitionwall panel
Prole
Coverframe
Glass
Cementing
medical
8/16/2019 Hospital Vent
13/48
T u r n n g
d o o r b a s i c
Cat.No. 104.01 C
TURNiNG DOOR
Together with the door-
frame, the metal turning
door is one of the basic
elements for the building
of cleanrooms and work-
places with maximum
safety, sterility, hygiene,
simple maintenance, and
sanitation.
The door wing coat con-
sists of a formed panel
made by the precise
forming method. Along
the coat perimeter, braces
are cemented to increase
the door wing solidity,
hinge and lock fixing. The
coat, brace and fill are
mutually cemented under
pressure.
The product has been cert if ied in EU countr ies.
basic
The door wing is either full or glazed by the PHARMA
system, which is a both sided glazing where glass plate
is flush with the door wing surface. The space between
the glass plates may be provided with sun-blinds.
COMPONENTS FOR MEDICAL PREMISES
AND SURGERIE S IMPLEMENTATIONmedical
8/16/2019 Hospital Vent
14/48BLOCK a.s., U Kasáren 727, 757 01 Valašské Meziříčí, tel.: +420 571 670 111, fax: +420 571 670 244, e-mail: [email protected], www.block.cz
104.01 C
ACCESSORIES
BASIC TECHNICAL DATA
Clear width[mm]
single-wing min. 600 - max. 1200
double-wing min. 1200 - max. 2200, active wing min. 600 - max. 1100
Clear height[mm]
single-wing min. 1550 - max. 2400
double-wing min. 1550 - max. 2400
Door thickness [mm] (standard) 52 (standard), 60
Coat materialand colour shade
zinc-coated steel sheet, colour 9010 (standard), protected by PE foil
zinc-coated steel sheet, colour 9010, 6027, 1015, protected by PE foil
AISI 304 stainless steel, FIN8 grind, protected by PE foilzinc-coated sheet, protected by PE foil
Komaxit, RAL colour, protected by PE foil
Orientationand design
single-wing Left, right
double-wingLeft, right
Left, right, with above-standard control of the xed wing
Hinge typeHäfele AISI
Dr. Hahn, RAL 9006, matt, as a standard colour
TURNING DOOR BASIC
Glazing
full, with no glazing
standard glazing 320x1050 mm
glazing 1/3 ( S*- 276 mm) x 551 mm
glazing 1/2 ( S*- 276 mm) x 901 mm
glazing 2/3 ( S*- 276 mm) x 1251 mm
fully glazed ( S*- 276 mm ) x 1601 mm
Glazingmaterial
oat glass, thickness 4 mm
oat glass, thickness 4 mm - milk glass
safety glass, laminated, thickness 6mm
mirror glazing, 2/3 on the hinge sidemirror glazing, 2/3 opposite the hinge side
Sun-blinds andtheir control
mechanical sun-blinds
magnetic sun-blinds
controls on the hinge side
controls opposite the hinge side
controls on the both sides
no sun-blinds
Sun-blindcolour shade
standard sun-blind colour, RAL 9006
to order, in accordance with the basic RAL scale
ACCESSORY AND RELATED PRODUCTS
Cat.No. 109 HVAC grids
Cat.No. 102 Partition panels B P
• 0 6
• 0 1Cat.No. 111.02 Signalization into doorframes
Cat.No. 111.05 Door wing blocking
door wing
hinge
Yale lock
standardglazing
door control- door check
seal rail
SINGLE-WING DOOR WITH THE Dr. HAHN HINGE DOUBLE-WING DOOR WITH THE HÄFELE HINGE
Fittings
OGRO - stainless Zelinger - thermoplastic
- handle- xed ball- turning ball
- handle- xed ball
panic
other, optional
supplied without ttings
Yale lock
Yale lock standard
Yale lock - combined lock / one key for more Yale locks
Yale lock - general key / entry level may be pre-set
without the Yale lock, opening covered by a stainless blind
without the Yale lock
Telescopic seal rail telescopic seal rail, wiping rail, or no rail
Door control type manual, door check (to be specied), or automatic drive
Other accessories ofthe door wing
door wing blocking
signalization
HVAC grid
300x500 [mm]
300x400 [mm]
300x300 [mm]
without an HVAC grid
Grounding for the I and II zoneswith grounding
no grounding
Doorframematerialand colour shade
two-side zinc-coated steel sheet, surface treated,standard colour: RAL 9006
two-side zinc-coated steel sheet, surface treated,colour to order
AISI 304 stainless steel sheet
Fixing design
for partition panels
for wall partitions
for plasterboard partitions
Doorframe thickness 60, 80, 100, 120 mm
DOORFRAME
MAINTENANCE AND OPERATION
• Door wing coat and doorframe - to be cleaned and disinfected by common cleaning agents, in relat ion to surface treatment
• Glass door f i l l - to be cleaned by common cleaning agents for glass fills - acids, thinners, and other chemicals not to be used
• Steel door hinges - for the Häfele hinge, grease to be appl ied and
possible sett ing of the hinge to be perform ed (every two months) - the Dr. Hahn hinges are maintenance-free
• Door check - every two months, or upon need, closing speed, c los ing force to be set by the set t ing sc rews
• Door with seal ing rai l - the space in front of the door to be maintained
clean, without solid particles that could cause jamming or damage of the seal ing rai l
• To secure permanent quality of the surface treatment,
the steel door, with the RAL design, may not be subject
to the relative humidity higher than 60 %.
Mineral woolThickness [mm] Density [kg/m3]
Thermal conductivityfactor K [W/m.K]
Flammability
50 100 0.040 A
GLAZING AND SUN-BLINDS
* S = door wing width
FILL
STANDARD DIMENSIONS AND MASS PATTERN
doorframe
fittings
lock
H
S
H
S
ac tive wing passive wi ng
Orderdimensions
Doorframeclear open-ing, width xheight [mm]
Dimensionsof the build-
ing opening,width xheight[mm]
Pass-throughdimensions when
the door wingopen by 90°
[mm]
Door wing weightwith the standard
glazing[kg]
activewing*
active +passive
activwing
passivewing
s i n g l e - w i n g 700 x 2100 822 x 2162 644 - 41 -
900 x 2100 1022 x 2162 844 - 48 -
1100 x 2100 1222 x 2162 1044 - 54 -
d o u b l e - w i n g 1300 x 2100 1422 x 2162 644 1189 41 38
1500 x 2100 1622 x 2162 844 1389 48 38
1700 x 2100 1822 x 2162 1044 1589 54 38
* When using the Häfele hinges the straight-through is 10 mm bigger
medical
8/16/2019 Hospital Vent
15/48
F i r e - r e s i s t a n t t u r n i n g d
o o r
Cat.No. 104.05 B
FIRE-RESISTANT TURNING DOOR
The fire-resistant metal
turning door is, together
with the metal doorframe,
one of the basic elements
for the building of clean-
rooms and facilities with
required increased limita-
tion of fire spread, upon
maintained maximum steri-
lity, hygiene and simple
maintenance.
The single-wing door is
provided with a fire-resis-
tant lock and fire-resistant
handle. For double-wing
door, the fixed wing is pro-
vided with a top and bottom
door-latch.
The product has been cert if ied in EU countr ies.
A door wing may be ful l or glazed, using the PHARMA system,
which is a both-sided glazing, where the outer glass panel
is flushed with the door wing surface; the intermediate space
is fitted with safety fire-resistant glass.
medical COMPONENTS FOR MEDICAL PREMISESAND SURGERIE S IMPLEMENTATION
8/16/2019 Hospital Vent
16/48BLOCK a.s., U Kasáren 727, 757 01 Valašské Meziříčí, tel.: +420 571 670 111, fax: +420 571 670 244, e-mail: [email protected], www.block.cz
104.05 B
ACCESSORIES
BASIC TECHNICAL DATA
Clear width[mm]
single-wing min. 700 - max. 1100
double-wing min. 1400 - max. 2200
Clear height[mm]
single-wing min. 1550 - max. 2400
double-wing min. 1550 - max. 2400
Door thickness [mm] 52
Coat materialand colour shade
zinc-coated sheet, RAL colour, protected by PE foil
AISI 304 stainless steel, FIN8 grind, protected by PE foil
Komaxit, RAL colour, protected by PE foil
Door orientation and design left, rightHinge type Forclean - all-metal hinges for cleanrooms
Glazing
full, without glazing
standard glazing, 320x1050 mm
glazing to order - the glazing may not exceed 25 % of the door wing surface
Glazing material• inside - re-resistant glass
armoured glass, re-resistant
clear re-resistant
Material of theoutside glazing
Float glass - thick. 4 mm
safety laminated glass - thick. 6 mm
FIRE-RESISTANT TURNING DOOR
B P
• 0 6
• 0 2
door wing
hinges
Yale lock
glazing
door control
- door check
seal rail
Fittings
handle, xed ball, turning ball (OGRO - stainless)
panic
other, optional
supplied without ttings
Yale lock
Yale lock, standard
Yale lock - combined lock / one key for more Yale locks
Yale lock - general key / entry level may be pre-set
without the Yale lock, opening covered by a stainless blind
without the Yale lock
Mutual sealing of the door and doorframe re-resistant sealing tape
Sealing of the bottom door section telescopic seal rail
Door control type door check (to be specied)
Grounding for the I and II zoneswith grounding
no grounding
Material andcolour shade ofthe doorframe
two-side zinc-coated steel sheet, surfacetreated, standard colour: RAL 9006
two-side zinc-coated steel sheet,surface treated, colour to order
AISI 304 stainless steel sheet
Installationinto wall, min. thickness 100 mm
into porous concrete, min. thickness 150 mm
Doorframe thickness 100, 120, 150 mm
DOORFRAME
MAINTENANCE AND OPERATION
• Door-wing coat and doorframe - to be c l eaned and d i s infec ted by common cleaning agents, in relation to surface treatment
• Glass door fi l l - to be cleaned by common cleaning agents
for glass f i l l s - acids, thinners, and other chemicals not to b e used
• Steel door hinges - grease to be applied and possible setting
of the hinge to be performed (every two months)
• Door check - every two months, or upon need, closing speed,
closing force to be set by the setting screws
• Door with sealing rail - the space in front of the door to be maintained clean, without sol id part ic les that could cause jamming or damage of the sealing rail
• To secure permanent quality of the surface treatment, the steel door, with the RAL design, may not be subject to the relative humidity higher than 60%
Fill typeThickness
[mm]Density[kg/m3]
Max. ther-mal load
temperature[°C]
Thermalconductivi-ty factor K[W/m.K]
Flamma-bility*
Mineralwool
30 100 +900 0.040 A
Fire-resist-ant plates I.
10 800 +1100 0.18 A
Fire-resistant
plates II. 10 1150 +1000 0.32 A
Orderdimensions Doorframeopening,
width x height[mm]
Construction
openingdimensions,
width x height[mm]
Pass-through dimensions
when the door wingopen by 90°
[mm]
Door wingweight with
the standard glazingand ll of
the re-resistant plate II.[kg]
active wingactive +passive
active wing passive wing
s i n g l e - w i n g 700 x 2100 822 x 2162 644 - 82 -
900 x 2100 1022 x 2162 844 - 95 -
1100 x 2100 1222 x 2162 1044 - 110 -
d o u b l e - w i n g 1400 x 2100 1522 x 2162 644 1289 82 80
1600 x 2100 1722 x 2162 844 1489 95 80
1800 x 2100 1922 x 2162 1044 1689 110 80
INSIDE DOOR FILL
FIRE-RESISTANCE CLASSIFICATION
STANDARD DIMENSIONS AND WEIGHT EXAMPLES
doorframe
fittings
lock
Single-wing door, full type EI1 20-C2 / EI
2 30-C2 / EW 30-C2(1)
Double-wing door, full type EI1 15-C2 / EI
2 30-C2 / EW 30-C2
Single-wing door, partially glazed: Float, thick. 4mm -re-resistant armoured glass - Float, thick. 4 mm EW 30 C2
Double-wing door, partially glazed: Float, thick. 4mm - armoured glass, re-resistant - Float, thick. 4 mm EW 30 C2
Single-wing door, partially glazed: Float, thick. 4mm- clear re-resistant - Float, thick. 4 mm EI1 15-C2 / EI2 15-C2 / EW 30-C2
Double-wing door, partially glazed: Float, thick. 4mm - clear re-resistant - - Float, thick. 4 mm EI1 15-C2 / EI2 15-C2 / EW 30-C2
Single-wing door, full, hinges on the side ofa thermal load EI1 30-C2
(2)
/EI2 30-C2/EW 60-C2Double-wing door, full, hinges on the side ofa thermal load
EI1 30-C2(2)/EI
2 45-C2(2)/EW 30-C2(1)
(1) The EN 13501-2 standard enables to classify doo rs only as EW 20, EW 30, EW 60.The doors classified in this table meet the integrity criterion (E) as well as the radiation criterionat the same time (W), for the classification time 45 minutes.
(2) Does not apply for the fill – FIRER ESISTANT PLATE II. – MINERAL WOOL – FIRERES ISTANT PLATE II.
*Flammability determined in accordance with Czech standard norm 73 0862: 1983
H
S
ac tive wing passi ve wing
H
S
NOTEEvery installation must be carried out only in compliancewith a project documentation.The installation and possible dismantling of the doorand doorframe shall be carried out exclusively by a com-pany authorised by the manufacturer.
medical
8/16/2019 Hospital Vent
17/48
X - r a y s d o o r
s i n g l e - w i n g ,
d o u b l e - w i n g
Cat.No. 104.08 B
X-RAYS DOOR
COMPONENTS FOR MEDICAL PREMISES
AND SURGERIES IMPLEMENTATION
The product has been cert if ied in EU countr ies.
SINGLE-WING, DOUBLE-WING
Together with the doorframe,
the metal X-rays door is one of
the basic elements for the buil-
ding of cleanrooms and work-
places with protection against
X-rays radiation.
The door is sandwich type. The
door wing coat consists of
a formed panel made by the pre-
cise forming method. Along the
coat perimeter, braces of zinc-
coated sheet are cemented to
increase the door wing solidity,
hinge and lock fixing.
Mineral wool is used as standard
fill together with auxiliary plate
HPS and shielding lead insert,
which is delivered in thickness
within 0,4 mm ÷ 3 mm. A part of
door is also shielded doorframe
with protection against X-rays
radiation.
medical
8/16/2019 Hospital Vent
18/48
104.08 B X-RAYS DOOR
medical
BLOCK a.s., Stulíková 1392, 198 00 Praha 9, Czech Republic, tel.: +420 571 670 111, e-mail: [email protected], www.block.cz
ACCESSORIES
BASIC TECHNICAL DATA
ACCESSORY AND RELATED PRODUCTS
Cat.No. 102.08 X-rays partition panels B P
• 0 7
• 0 5
Fittingstype OGRO stainless
handle
fixed ball
turning ball
panic
stainless blind
supplied without fittings
Yale lock
Yale lock, standard
Yale lock - combined lock / one key for more Yale locks
Yale lock - general key / entry level may be pre-set
without the Yale lock, opening covered by a stainless blind
without the Yale lock
Telescopic seal railtelescopic seal rail
without rail
Door control type
manual
door check (to be specified)
automatic drive
Doorframematerialand shade
two-side zinc-coated steel sheet, surface treated,standard colour RAL 9006
two-side zinc-coated steel sheet, surface treated,colour RAL 9002, 6027, 1015
AISI 304 stainless steel sheet, FIN8 grind
Fixing design
for partition panels
for wall partitions
Doorframethickness
60, 80, 100, 120 mm
SHIELDING INSERT
MAINTENANCE AND OPERATION
Fill Thickness [mm] Density [kg/m3]Thermal conductivity
factor K [W/m.K]Flammability
Mineral wool 50 100 0.040 A
Shielding Pb insert 0,4 - 3 11340 - -
FILL
STANDARDISED DIMENSIONS AND MASS PATTERN
Order dimension
Doorframe clearopeningwidth x height
[mm]
Dimensions
of the building openingwidth x height[mm]
Pass through
dimensionswhen the doorwing open by 90°
[mm]
Weight of door
wing with leadinsert 2 mm[kg]
s i n g l e - w i n g 700 x 2100 820
x 2160 644 74
900 x 2100 1020 x 2160 844 91
d o u b l e - w i n g 1300 / 700 x 2100 1420 x 2160 1189 74 / 58
1500 / 900 x 2100 1620 x 2160 1389 91 / 58
At door wing open by 180º, the pass-through dimensions are the same as doorframe clear opening.
door wing
hinge
Yale lock
door control
– door check
seal rail
doorframe
ttings
lockpassive wing
H
S
active wing
DOORFRAME
• Door-wing coat and doorframe
- to be cleaned and disinfected by common cleaning
agents, in relation to surface treatment
• Door check
- every two months, or upon need, closing speed, closing
force to be set by the setting screws
• Door with sealing rail
- the space in front of the door to be maintained clean,
without solid particles that could cause jamming
or damage of the sealing rail
• To secure permanent quality of the surfacetreatment, the steel door, with the RAL design, maynot be subject to the relative humidity higher than
60%.
WARNING:
Installation and possible dismantling shall be
carried out exclusively by a company authorised
to do so.
*active wing min. 600 - max. 1000
Optional design Standard design
Clear widthsingle-wing min. 600 - max. 1000 [mm] 700, 900 [mm]
double-wing* min. 1200 - max. 2000 [mm] 1500 [mm]
Clear height Single as wellas double wing min. 1550 - max. 2100 [mm] 2100 [mm]
Door thickness 52 [mm] 52 [mm]
Coat material and colour shade
zinc-coated steel sheet, colourRAL 9010, 9002, 6027, 1015
protected by PE foilzinc-coated steel sheet,colour RAL 9010 protectedby PE foil
zinc-coated steel sheet accordingto RAL patternsAISI 304 stainless steel, FIN8grind protected by PE foilmutual combinations of abovementioned
Orientationand design
single-wingleft, right left, right
double-wing
S
H
Shielding lead insert thickness has to be stated by designer
every time on base of optimalization and radiation limit
according delegated legislature.
Cat.No. 103.08 X-rays partition panel glazing
-0 -0
-0 -0
-0 -0
-0 -0
+10
+10
+10
+10
+5
+5
+5
+5
8/16/2019 Hospital Vent
19/48
M e c h a n i c s l i d i n g d o o r
A u t o m a t i c s l i d i n g d o o r
Cat.No. 104.21 B Cat.No. 104.22 C
MECHANIC SLIDING DOOR
COMPONENTS FOR MEDICAL PREMISES
AND SURGERIES IMPLEMENTATION
The product has been cert if ied in EU countr ies.
SINGLE-WING, DOUBLE-WING
The sliding door provides
a wild spectrum of door
types described by basic
and additional parameters
that enable to produce the
door on the customer’s
requirements.
This is produced as one-
wing or double-wing door.
Automatic sliding doors
are a. c. motor powered.
Motor is operated by
frequency converter which
is controlled by micropro-
cessor and that control
automatic door faultless-
ly in each situation with
emphasis on safety. It is
possible to control the
sliding door by means of
control accessories, inclu-
ding remote control and
possibility of connectionto safety system.
The door wing is either full or glazed by the PHARMA system,
which is a both sided glazing where glass plate is flush with the door
wing surface. The space between the glass plates may beprovided with sun-blinds.
medical
AUTOMATIC SLIDING DOOR
8/16/2019 Hospital Vent
20/48
104.22 C AUTOMATIC SLIDING DOOR
DESCRIPTION
SECTIONS
B P
• 0 7
• 0 5
medical
BLOCK a.s., Stulíková 1392, 198 00 Praha 9, Czech Republic, tel.: +420 571 670 111, e-mail: [email protected], www.block.cz
FILL
BASIC TECHNICAL DATA
Glazing
full, with no glazing
glazing 1/3
glazing 1/2
glazing 2/3
Glazing material
cast glass, thickness 4 mm
cast glass, thickness 4 mm - satin painted glass
safety glass, laminated, thickness 6mm - clear
Sun-blindsand their control
mechanical sun-blinds
magnetic sun-blinds
controls on the hinge side
controls opposite the hinge side
controls on the both sides
no sun-blinds
Sun-blindcolour shade
standard sun-blind colour, RAL 9006
to order, in accordance with the basic RAL scale
GLAZING AND SUN-BLINDS
DOORFRAME AND FITTINGS
CONTROL ACCESSORY - 104.22 Automatic sliding door
WARNING:
Installation and possible dismantling of sliding door shall be carried out exclusively by a company
authorised to do so or by company whose specialist was trained in BLOCK a.s
Fill Thickness [mm] Density [kg/m3]Max. load
temperature (°C)Thermal conductivity
factor K [W/m.K]Flammability
Mineral wool 50 100 +1000 0.040 A
Optional design Standard design
Clear width[mm]
single-wing min. 800 - max. 1000 800, 900, 1000
single-wing - atype* 1200 1200
double-wing min. 1200 - max. 2000 1600, 2000
Clear height [mm] Single as well as doublewing min. 1550 - max. 2400 2100
Door thickness [mm] 52 52
Coat material and colour shade
zinc-coated steel sheet,colour RAL 9010, 9002, 6027, 1015protected by PE foil
zinc-coated steel sheet, colourRAL 9010 protected by PE foil
zinc-coated steel sheet accordingto RAL patternsAISI 304 stainless steel, FIN8grind protected by PE foilmutual combinationsof above mentioned
Orientationand design
single-wingleft, right left, right
double-wing
Doorframeand backstopcolumn materialand colour shade
zinc-coated steel sheet, colour RAL 9010
zinc-coated steel sheet, colour 9002, 6027, 1015
AISI 304 stainless steel sheet, FIN8 grind
zinc-coated steel sheet, according to RAL scale
Fixing design
for partition panels and wall partitions
without doorframe only with sheeting
without doorframe
Doorframe thickness 60, 80, 100, 120 [mm]
Fittings
stainless steel handles
clips FOR CLEAN AISI (only from traversing side)
clips FOR CLEAN AISI
without fittings
Elbow switch
Large-area wall switch. This is activated by elbow lean againstthe folding surface, hands stay free. This is delivered in some versions– grey plastic design, crash resistant or clear anodised aluminium
as a standard.
Proximity switchThis switch is used especially in hospitals where activates automaticdoor by only hand proximity at distance of 10-50 cm (hygienic reasons).This is placed in the height of usual light switch.
Contact switchSwitch is possible to place approx. 15-20 cm over the floor, and enablesthe automatic door activation after mild tread to rubber top.
Microwave radar
By means of detection field this is enable to scan defined area in frontof the door. Microwave sensors differ movement direction „to the sen-sor“ and „from the sensor“. So it is possible to notably reduce openingperiod.
Switch knob Wall switch is activated by touch.
Card scannerCard scanner and entry control system can be used also as activatedunit of automatic door system.
Door wing
• coat of optional material and surface treatment
• fill - mineral wool • optional glazing and glazing dimensions
• fittings, lock
Door control
104.22 Automatic sliding door
• elbow switch
• proximity switch
• contact switch
• microwave radar
• switch knob
• card scanner
Partition thickness for sliding door installation
• 60, 80, 100, 120 mm
• another thick.- it is possible to produce the door as atypical
* Single-wing door with clear width 1200 mm is designated for hospitals and medical premises, where the sufficient width has to be for trolleysand mobile beds – that is atypical design of door wing. The door can be full or glazed by pharma glazing. This is equipped by Acrovyn protectioncrash rail in the height of 720 mm above the floor as a standard.
104.21 Mechanic sliding door 104.22 Automatic sliding door
104.21 B MECHANIC SLIDING DOOR
2 S + 3 5 5 m m *
2 S + 5 0 0 m m *
* S = door clear width
Cover
Coat I.
Coat II.
8/16/2019 Hospital Vent
21/48
L i g h t m e t a l s o f f i t F O R C L E A N
Cat.No. 105.01 B
LIGHT METAL SOFFIT FORCLEAN
The light metal soffit is
a lowered ceiling struc-
ture with a hidden sus-
pension system, desig-
nated in particular to
close cleanrooms, facili-
tating certain pressu-
res.
The soffit is used in
pharmaceutical, ele-
ctrical, foodstuff, che-
mical, and engineering
industry premises, as
well as in civil engi-
neering. It is suita-
ble for hospitals and
laboratories.
The soffit structure may be fitted with light fittings, glazed
and service panels, filtration extenders, and various HVAC elements.
The product has been cert if ied in EU countr ies.
medical COMPONENTS FOR MEDICAL PREMISESAND SURGERIE S IMPLEMENTATION
8/16/2019 Hospital Vent
22/48
Installationheight[mm]
Suspension systemThreaded
rod[mm]
Components that may be used
Standardpanel
Servicepanel
Glazedpanel
Lighttting
PUROFIL
155 - 205 short truss - 125 mm** max. 1000 YES YES YES NO NO
205 - 550 long truss - 175 mm** max. 1000 YES YES YES YES NO
550 - 1135 long truss - 175 mm** max. 1000 YES YES YES YES YES
1135 - 2135* long truss - 175 mm** max. 2000 YES YES YES YES YES
Types of ceilingpanels
standard
offset (height to be specied, when ordered)
offset, edge-type (height to be specied, when ordered)
glazed
service
Colour shadeand materialof the standard panel
zinc-coated, painted steel sheet, colour: RAL 9010, 9002, 1015, 6027
zinc-coated, painted steel sheet, colour to order
steel stainless sheet, AISI 304, FIN 8 grind
Ending type of thesoft
with a cavetto and perimeter trim (length 3m)
2x with perimeter trim (length 3m)
Minimum installation height• see the table TECHNICAL DATA
Anchoring• into concrete ceiling
steel anchor, M6 with min. bearingcapacity 0.2 kN/pc
• into a steal steel structuremetal truss clamps, M6 The installation and commissioningshall be carried out exclusivelyby a company authorised to do so.
BLOCK a.s., U Kasáren 727, 757 01 Valašské Meziříčí, tel.: +420 571 670 111, fax: +420 571 670 244, e-mail: [email protected], www.block.cz
105.01 B LIGHT METAL SOFFIT FORCLEAN
ANCHORING AND INSTALLATION
MAINTENANCE
• Painted surfaces to be cleaned by non -abrasivedisinfecting cleaning agents based on alcohol
• Stainless surfaces to be cleaned by non-abrasive disinfecting cleaning agents basedon alcohol, or by slightly abrasive disinfectingcleaning agents (only for the ground/mattsurface, always in the gring direction) basedon butyl alcoh ol (stains, fingeprints), or based
on acids where heavier pollution occurs. Con-centration to be selected in relation to thepollution extent
• Glass surfaces to be wiped by a fine fabriccombined with cleaning agents based on alco-hol.
DESCRIPTION
• BEARING PROFILES (length 3m - extension by means of links)
are suspended on threaded rods, M6 (1000mm; 2000mm
- extension by means of links) anchored to a construction ceiling
or on an auxiliary structure • Threaded rods span - 1200 mm (max. 1500mm)
• Bearing profiles span - 1000 mm (max. 2000mm)
• SNAP-TYPE PROFILES (length 3m - extension by means of links)
they are suspended under the bearing profiles by means of
SNAP-TYPE PROFILE TRUSSES -
- short truss: 125mm from the soffit level
- long truss: 175mm from the soffit level
The snap-type profile trusses are secured against fall off due
to an excessive overpressure under the soffit.
• THE SNAP-TYPE PROFILES are fitted with individual
standard, glazed, service, or offset panels by their “snapping-in”.
The FORCLEAN - type light metal soffit is fully compatible
with HVAC EXTENDERS, PUROFIL FILTRATION EXTENDERS,FORCLEAN LIGHT SNAP-TYPE LIGHT FITTINGS.
TECHNICAL DATA
OPTIONAL ELEMENTS
PRESSURE CONDITIONS
Max. short-term admissible underpressure in the room vs. the tight space above the soft ca 300Pa
Max. short-term admissible overpressure in the room vs. the tight space above the soft ca 200Pa
Operation overpressure and underpressure in the room vs. the tight space above the soft 100 Pa
GLAZED PANEL SERVICE PANELThe GLAZED PANEL facilitates the room lighting by daylight or by a light fitting placed above the soffit. It
consists of a snap-type panel with an opening and of a bot tom panel with prismatic glass, type BARLO SAN.
Above the panel a light fitting may be used with the min. shielding IP20 and max. dimensions 600x600mm.
Apart from screws, the bottom panel is secured by two springs against fall-out. Standard dimensions
of the glazed panel are 625x625mm.
The SERVICE PANEL • enables quick access to the space above
the soffit, when servicing is needed.
It consists of a snap-type panel with an opening, and of a bot-
tom panel. Apart from screws, the bottom panel is secured by two
springs against fall-out. Standard dimensions of the service panel are
625x625mm.
* Bigger installation height may be solved by extension of the threaded rods** The suspension distance between the soffit level and the top edge of the bearing profile
STANDARD PANELThe STANDARD PANEL • standard basic module
• Standard dimensions 625x625mm
• Non-standard dimensions 600x600,1250x625, 1200x620mm
• Face side surface
- standard treatment by the RAL 9010 colour
- non-standard treatment according to the RAL
colour list, or with the AISI 304 design, FIN8 grind
• Panel structure
- metal panels are fixed by snapping into the snap type panel
ACCESSORY AND RELATED PRODUCTS
Cat.No. 107 Light fttings
Cat.No. 108 Filtration extenders, fltration outlet
Cat.No. 109 HVAC extenders and grilles
Cat.No. 102 Basic partition panels
Anchoring spot for
the M6 threaded rods
Bearingprofile
Snap-type profiletruss Panel
Soffit weight approx. 12 kg.m-2
B P
• 0 6
• 0 1
Snap-type profile
medical
8/16/2019 Hospital Vent
23/48
T r a n s f e r h a t c h
Cat. No.106.01 B Cat. No. 106.02 B
TRANSFER HATCH
The product has been cert if ied in EU countr ies.
For a transfer of smaller
objects and material
between rooms with di ffe-
rent cleanliness class
the transfer hatch
installed directly into
a partition wall may be
used.
Walls, ceiling and bottom
of the transfer hatch are
made of sandwich-type
panels.
If laminar flow inside the hatch is needed, HEPA filter
is fixed to the hatch ceiling provided with an opening.
To exhaust air from the hatch, the right door is provided
with a grille in the bottom section. Where a ventilation
control grille may be installed in the panel, the hatch bot-
tom consists of a perforated sheet, under which a catch
basin is placed.
- with mechanical blocking- with electromagnetic blocking
- with blocking controlled by electric lock
medical COMPONENTS FOR MEDICAL PREMISESAND SURGERI ES IMPLEMENTATION
8/16/2019 Hospital Vent
24/48
Walls, ceiling, and bottom of the hatch
• external coat
- optional material and colour shade • inside coat
- optional material and colour shade
- sandwich-type panels, thickness 52 mm,
mineral wool ll
Door frame • steel, class 11, polyamide
Bearing frame • steel, class 11
Glazed door • left, right
• optional glazing type
• ttings - handle,
type OGRO, stainless steel
Blocking • pls. see „Optional elements“
Signalization • pls. see „Optional elements“
BLOCK a.s., U Kasáren 727, 757 01 Valašské Meziříčí, tel.: +420 571 670 111, fax: +420 571 670 244, e-mail: [email protected], www.block.cz
106.01 B 106.02 B TRANSFER HATCH
B P
• 0 6
• 0 8
BASIC DIMENSION LINE
DESCRIPTION
TRANSFER HATCH WITH HEPA FILTER
AIR STREAMOPTIONAL ELEMENTS
Wallpanel
Clear transfer dimension Recommended design Standard design
Clear width S [mm] 600, 800, 1000
600 x 600 x 600800 x 800 x 800Clear height
H [mm] 600, 800, 1000
Clear depth U [mm] 600, 800
External coat colourshade and material
two-side zinc-coated steel sheet, surface-treated, protected by PE foil,standard colour: RAL 9010, 9002, 6027 and 1015
stainless steel design, of AISI 304, on customer´s request
Inside coat colourshade and material
stainless steel sheet, AISI 304 FIN 8, protected by PE foil
stainless steel design, of AISI 304, on customer´s request
Door frames and frames
powder nish, identical with the partition wall colour shade
RAL 9010-K3, 9002, 6027, 1015 as a standard
stainless steel sheet, AISI 304 FIN 8, protected by PE foil
any other colour shades according to order
Air stream
active
semi-active
passive
Blocking
mechanicalCat. No. 106.01
no blocking
electromagneticCat. No 106.02
controlled by electric lock
Signalizationalways combined with the electromagnetic blocking
always with the blocking controlled by the electric lock
Door wingmax. glazing, door wing the thickness 35 mm
all-glazed door wing
Glazingoat glass, thickness 4 mm
safety laminated glass, thickness 6 mm
Door openingrst the door from the cleanroomside is referred
right - left*, right – right
left - right*, left – left WARNINGInstallation and possible dismantling shall be carriedout exclusively by a company authorised to do so.*for the hatches with mechanical blocking only these variants may be used
Maximum clear dimension of the hatch[mm]
Minimum clear dimension of the hatch[mm]
width x height x depth width x height x depth
S x H x U S x H x U
1000 x 1000 x 1000 400 x 400 x 400
• ActiveOwn ltered air supply through HEPA lter; air exhaustto the room with a lower cleanliness class.
• Semi-activeThe hatch is washed by air from the room with highercleanliness class; air is exhausted to the room with a lowercleanliness class.
• PassiveThe hatch is not provided with HVAC.
MAINTENANCE AND CLEANING
• Painted surfaces to be washed by non-abrasive disinfecting cleaning agents basedon alcohol.
• Stainless surfaces to be washed by non-abra-sive disinfecting cleaning agents, orby slightly abrasive disinfecting cleaningagents (for ground surface only; alwaysclean in the grind direction) based on butylalcohol (stains, fingerprints); based onacids where heavier pollution occurs.
Concentration to be selected in relation tothe pollution extent.
• Glass surfaces to be wiped by fine fabriccombined with cleaning agents basedon alcohol.
Partition wall
H + 104 mm
S + 104 mm U + 86 mm
Doorframe
Signalization
Bearing frame
Glass
Partitionwall
H + 104 mm
S + 104 mm U + 86 mm
Doorframe
Mechanicalblocking
Bearing frameGrille
Glass
HEPAfilter
Electro-
magneticblocking
Partitionwall
medical
8/16/2019 Hospital Vent
25/48
F l u o r t u b e l i g h t t t i n g , F O R C L E A N l i g h t
t o l i g h t m e t a l s o f t – s n a p - o n t y p e
Cat. No. 107.04 A
FLUOR TUBE LIGHT FITTING, FORCLEAN LIGHT
The product has been cert if ied in EU countr ies.
TO LIGHT METAL SOFFIT - SNAp-ON TypE
The uor tube light t-
tings, FORCLEAN Light,
are designated for lighting
of interior rooms with cont-
rolled cleanliness classes.
They are installed into light
metal softs. They are airtight,
thus securing the pressure
tightness of the whole soft.
The surface treatment and
light ttings colour shadeare identical with those
of the soft.
medical COMPONENTS FOR MEDICAL PREMISESAND SURGERI ES IMPLEMENTATION
8/16/2019 Hospital Vent
26/48BLOCK a.s., U Kasáren 727, 757 01 Valašské Meziříčí, tel.: +420 571 670 111, fax: +420 571 670 244, e-mail: [email protected], www.block.cz
107.04 A
BASIC DESCRIPTION
TECHNICAL SPECIFICATION
OPTIONAL ELEMENTS
Bottom frame materialand colour shade
steel sheet, class 11, colour: RAL 9010-K3
steel sheet, class 11, colour: RAL 9002
steel sheet, class 11, colour: RAL 1015
steel sheet, class 11, colour: RAL 6027
stainless steel, AISI 304, FIN 8 grind
Optical part solutionprismatic (lenticular)
clear, with optical raster (grille)
Compact uortubes colour
PHILIPS PL-L 830/4P, light colour: warm tone (55 W)
PHILIPS PL-L 840/4P, light colour: white (55 W)
no compact uor tubes delivered
Emergenc power sourceemergenc lighting set, HELP2
no emergenc power source delivered
FLUOR TUBE LIGHT FITTING, FORCLEAN LIGHT TO LIGHT METAL SOFFIT - SNAP-ON TyPE
B P
• 0 6
• 0 8ACCESSORy AND RELATED PRODUCTS
Cat. No. 105 Light metal soft FORCLEAN Cat. No. 102 Partition wall panel
INSTALLATION
Tpe Bn/O/N Bn/P/N Bn/O Bn/P
Design Clear, with optical raster(grille) PrismaticClear, with optical raster
(grille) Prismatic
Shielding IP 54 IP 54 IP 54 IP 54
Light source [W] 2x55 2x55 2x55 2x55
Voltage [V] 230 230 230 230
Current [A] 1,0 1,0 1,0 1,0
Dimensions A x B[mm] 625 x 625 625 x 625 625 x 625 625 x 625
Weight [kg] 8,0 7,8 7,5 7,2
Illuminating power[lm] 10007,4 10007,4 10007,4 10007,4
Emergenc source* HELP 2 (18-58W) HELP 2 (18-58W) - -
MAINTENANCE AND OPERATION
Prior to any repair and cleaning, power supply
of the appliance must be disconnected and secu-
red against accidental switch-on!
• Under an suspicion in respect of a shielding failure,
a check of the device, or a shut-down and repair,
is necessar.
• Fluor tubes exchange and cleaning of the applian-
ce must be done onl b a person or service
organisation authorised to do so.
Surface cleaning of the light tting
• Common cleaning agents to be used that do not
contain abrasive agents.
Disinfection
• to be done b common disinfecting agents
• Connection of the appliance to electric system
Connection of the appliance to electric sstem,from the building’s side is resolvedb the designer.Terminal board , X1
• designed to connect one phase,voltage 23 0 V / 50 Hz
• scope of possibl applicable cross-sec-tions of connection conductors:
0.5 mm2 - 1.5 mm2 Distribution system: 1 + N + PE AC / 50 Hz
Network: TN-S 230 V / 50 Hz
Master protection system: max 10 A
Under no circumstances the light tting may be co-
vered by an insulation pad or by a similar material.
WARNING
The connection of the appliance to electri-
cal system, of a conductor to the termi-
nal board and to a terminal, and handling
with electric installations may be done
only by a person with a necessary quali-
fication in respect of works on electrical
equipment.
Used abbreviations:
Bn - dimension line, A x B /625 x 625 mm/ - snap-on tpe O - with clear glass and optical raster
P - with prismatic raster N - emergenc power source set, HELP
The radiating angle of a guaranteed luminance for the calculation of an illuminated area:• 45 deg. for the optical raster solution• 50 deg. for the prismatic raster solution
LUMINANCE RADIATING ANGLE
*Upon electric system outage, the emergency source will supply the light fitting for at least 1 hour.
• Light fitting frame- secures its shape stabilit
• Optical part - prismatic cover in a metal frame
- clear plexi-glass in a metal frame with a metal-coatedparabolic grille
A correct type of its optical part to be determined by a designer for a concrete space.Detail optical/technical specication upon request.
• Inside equipment
- compact fluor tubes, caps - electronic stabiliser - cabling and connection terminal board - optional emergenc power source - batter
- test button
The light tting‘s inside space is hermeticall separated from the space above
the soft b the coat. The suppl cable is lead through a tight bushing, PG11 / IP54.The light tting, type FORCLEAN Light, is fully compatible with the light metal soft (105.01).
Light ftting with an optical part- clear plexi-glass
with a parabolic grille
Light fttingwith an optical part- prismatic cover
medical
8/16/2019 Hospital Vent
27/48
F i l t r a t i o n e x t e n d e r s ,
t y p e P U R O F I L
- T Y P E F N A
Cat. No. 108.01 B
FILTRATION EXTENDERS, TYPE PUROFIL
with the filter, dimensions: 305 x 305 mm - TYPE FNA
The extenders are made with several coat dimensions, according
to filter size. For the supply air distribution, the bottom section
of the extenders is fitted with whirl outlets or perforated elements.
The PUROFIL filtration ex-
tenders are intended to be
the terminal element of
air supply for premises
with high demands on thecleanness of supplied air,
like surgeries, sterilisation
premises, intensive care
units, premises in the phar-
maceutical, electrical, engi-
neering, foodstuff industries,
etc.
The product has been certified in EU countries.
medical COMPONENTS FOR MEDICAL PREMISESAND SURGERIE S IMPLEMENTATION
8/16/2019 Hospital Vent
28/48
Raster[mm]
C x C
Filter
AIR SUPPLY TYPE
Side circularSide rectangular
+ one-side conversionTop circular
HEPA H12, Alframe[mm]
HEPA H13,MDF frame
[mm]
HEPA H14,Al frame
[mm]
Throatdimen-
sion[mm]
Totalheight
[mm]
Heightof
bottomstructure
[mm]
Heightof top
structure[mm]
Throatdimen-
sion[mm]
Totalheight
[mm]
Heightof
bottomstructure
[mm]
Heightof top
structure[mm]
Throatdimen-
sion[mm]
Totalheight
[mm]
Heightof
bottomstructure
[mm]
Heightof top
structure[mm]
A x A x B D H G I E x F H G I D H G I
600x600305x305x78
Ø160 390 180 210 265x80 290 180 110 Ø160 260 180 80
625x625* Ø200 430 180 250 265x120 330 180 150 Ø200 260 180 80
600x600305x305x149
Ø160 462 252 210 265x80 362 252 110 Ø160 332 252 80
625x625* Ø200 502 252 250 265x120 402 252 150 Ø200 332 252 80
600x600305x305x117
Ø160 427 217 210 265x80 327 217 110 Ø160 297 217 80
625x625* Ø200 467 217 250 265x120 367 217 150 Ø200 297 217 80
BLOCK a.s., U Kasáren 727, 757 01 Valašské Meziříčí, tel.: +420 571 670 111, fax: +420 571 670 244, e-mail: [email protected], www.block.cz
108.01 B FILTRATION EXTENDERS, TYPE PUROFIL - TYPE FNA
DESCRIPTION
STANDARD DIMENSION LINE
OPTIONAL ELEMENTS FURTHER AIR SUPPLY OPTIONS
B P
• 0 6
• 0 6
H
A
C
G
E
F
B
Installation into softLight metal soft, FORCLEANThermatexMetal panel-type soft
Type dimensionsof the raster [mm]
625 x 625 (preferred)600 x 600
Surface
of the PUROFIL elementsPowder-type stove enamel, Komaxit, with standard colours,RAL 9010, 9002, 6027, 1015, or stainless steel, AISI 304, FIN 8 grind
Surface
of the output elementPowder-type stove enamel, Komaxit, with standard colours,RAL 9010, 9002, 6027, 1015, or stainless steel, AISI 304, FIN 8 grind
Filter frame material
Aluminium (for the ltration class H12, H13, H14)
MDF (for the ltration class H12, H13)
Output elementWhirling elementWhirling element, densePerforated sheet
Accessories - one-sideconversions [mm]
265 x 80 / Ø160265 x 120 / Ø200
Accessories – probes1 probe as a standard2 probes
A
Bottom structure
Filter
Top structure
HVAC flange
Raster
Snap-type profile
* Preferred raster dimensions
PUROFIL, WITH SIDE RECTANGULAR AIR SUPPLY
TECHNICAL PARAMETERS
FILTER DISTRIBUTION ELEMENTMedia height [“] Weight [kg] Flow-rate [m3/hod] Initial pressure drop [Pa] Flow speed [m/s] Whirling, standard Whirling, dense Perforated
HEPA H12
Al frame
305x305x78 [mm]
1” 3 50 83 0,15 yes no yes
2” 3 100 91 0,3 yes no yes
3” 3 150 100 0,45 no yes yes
HEPA H13
MDF frame
305x305x149 [mm]
1” 4 90 86 0,15 yes no yes
2” 4 160 94 0,3 no yes yes
3” 4 220 103 0,45 no yes yes
4” 4 250 116 0,6 no yes yes
HEPA H14 Al frame
305x305x117 [mm]
1” 3 90 86 0,15 yes no yes
2” 3 160 94 0,3 no yes yes
3” 3 220 103 0,45 no yes yes
4” 3 250 116 0,6 no yes yes
TOP CIRCULAR
SIDE CIRCULAR
D
D
C
I
PUROFIL
• Bottom structure
- secures the shape stability- fitted with the HEPA filter - contains a distribution element
(whirl outlets or perforated sheet)• Top structure
- zinc-coated sheet - with air supply of the • side rectangular shape
• side circular shape• top circular shape
As a standard, the extenders are provided with one probefor the leakage aerosol tests.
THE EXTENDER IS FULLY COMPATIBLE WITH THE LIGHT METALSOFFIT (Cat. No. 105).
medical
8/16/2019 Hospital Vent
29/48
F i l t r a t i o n e x t e n d e r s ,
t y p e P U R O F I L
- T Y P E F N B
Cat. No. 108.01 B
FILTRATION EXTENDERS, TYPE PUROFIL
with the filter, dimensions: 457 x 457 mm - TYPE FNB
The product has been certified in EU countries.
The extenders are made with several coat dimensions, according
to filter size. For the supply air distribution, the bottom section
of the extenders is fitted with whirl outlets or perforated elements.
COMPONENTS FOR MEDICAL PREMISES
AND SURGERIE S IMPLEMENTATIONmedical
The PUROFIL filtration ex-
tenders are intended to be
the terminal element of
air supply for premises
with high demands on thecleanness of supplied air,
like surgeries, sterilisation
premises, intensive care
units, premises in the phar-
maceutical, electrical, engi-
neering, foodstuff industries,
etc.
8/16/2019 Hospital Vent
30/48
Raster[mm]
C x C
Filter
AIR SUPPLY TYPE
Side circularSide rectangular
+ one-side conversionTop circular
HEPA H12Al frame
[mm]
HEPA H13MDF frame
[mm]
HEPA H14Al frame
[mm]
Throatdimen-
sion[mm]
Totalheight
[mm]
Heightof
bottomstructure
[mm]
Heightof top
structure[mm]
Throatdimen-
sion[mm]
Totalheight
[mm]
Heightof
bottomstructure
[mm]
Heightof top
structure[mm]
Throatdimen-
sion[mm]
Totalheight
[mm]
Heightof
bottomstructure
[mm]
Heightof top
structure[mm]
A x A x B D H G I E x F H G I D H G I
600x600475x457x78
Ø200 430 180 250 417x80 290 180 110 Ø200 260 180 80
625x625* Ø250 480 180 300 417x120 330 180 150 Ø250 260 180 80
600x600475x457x149
Ø200 502 252 250 417x80 362 252 110 Ø200 332 252 80
625x625* Ø250 552 252 300 417x120 402 252 150 Ø250 332 252 80
600x600475x457x117
Ø200 467 217 250 417x80 327 217 110 Ø200 297 217 80
625x625* Ø250 517 217 300 417x120 367 217 150 Ø250 297 217 80
BLOCK a.s., U Kasáren 727, 757 01 Valašské Meziříčí, tel.: +420 571 670 111, fax: +420 571 670 244, e-mail: [email protected], www.block.cz
108.01 B FILTRATION EXTENDERS, TYPE PUROFIL - TYPE FNB
DESCRIPTION
STANDARD DIMENSION LINE
OPTIONAL ELEMENTS FURTHER AIR SUPPLY OPTIONS
B P
• 0 6
• 0 6
H
A
C
G
E
F
B
Installation into softLight metal soft, FORCLEANThermatexMetal panel-type soft
Type dimensionsof the raster [mm]
625 x 625 (preferred)600 x 600
Surfaceof the PUROFIL elements
Powder-type stove enamel, Komaxit, with standard colours,RAL 9010, 9002, 6027, 1015, or stainless steel, AISI 304, FIN 8 grind
Surfaceof the output element
Powder-type stove enamel, Komaxit, with standard colours,RAL 9010, 9002, 6027, 1015, or stainless steel, AISI 304, FIN 8 grind
Filter frame materialAluminium (for the ltration class H12, H13, H14)
MDF (for the ltration class H12, H13)
Output element
Whirling, innovatedWhirling elementWhirling element, densePerforated sheet
Accessories - one-sideconversions [mm]
417 x 80 / Ø200417 x 120 / Ø250
Accessories – probes1 probe as a standard2 probes
A
Bottom structure
Filter
Top structure
HVAC flange
Raster
Snap-type profile
* Preferred raster dimensions
PUROFIL, WITH SIDE RECTANGULAR AIR SUPPLY
TECHNICAL PARAMETERS
FILTER DISTRIBUTION ELEMENTMedia height [“] Weight [kg] Flow-rate [m3/hod] Initial pressure drop [Pa] Flow speed [m/s] Whirling, innovated Whirling, standard Whirling, dense Perforated
HEPA H12
Al frame
457x457x78 [mm]
1” 3,5 100 83 0,15 yes yes no yes
2” 3,5 220 91 0,3 yes yes no yes
3” 3,5 330 100 0,45 yes yes yes yes
HEPA H13
MDF frame
457x457x149 [mm]
1” 4,5 200 86 0,15 yes yes no yes
2” 4,5 360 94 0,3 yes yes yes yes
3” 4,5 490 103 0,45 yes no yes yes
4” 4,5 570 116 0,6 yes no yes yes
HEPA H14 Al frame
457x457x117 [mm]
1” 3,5 200 86 0,15 yes yes no yes
2” 3,5 360 94 0,3 yes yes yes yes
3” 3,5 490 103 0,45 yes no yes yes
4” 3,5 570 116 0,6 yes no yes yes
TOP CIRCULAR
SIDE CIRCULAR
D
D
C
I
PUROFIL
• Bottom structure
- secures the shape stability- fitted with the HEPA filter - contains a distribution element
(whirl outlets or perforated sheet)• Top structure
- zinc-coated sheet - with air supply of the • side rectangular shape
• side circular shape• top circular shape
As a standard, the extenders are provided with one probefor the leakage aerosol tests.
THE EXTENDER IS FULLY COMPATIBLE WITH THE LIGHT METALSOFFIT (Cat. No. 105).
medical
8/16/2019 Hospital Vent
31/48
F i l t r a t i o n e x t e n d e r s ,
t y p e P U R O F I L
- T Y P E F N C
Cat. no. 108.01 B
FILTRATION EXTENDERS, TYPE PUROFIL
with the filter, dimensions: 570 x 570 mm - TYPE FNC
The product has been certified in EU countries.
The extenders are made with several coat dimensions, according
to filter size. For the supply air distribution, the bottom section
of the extenders is fitted with whirl outlets, perforated elements,
or with anemostat.
COMPONENTS FOR MEDICAL PREMISES
AND SURGERIE S IMPLEMENTATIONmedical
The PUROFIL filtration ex-
tenders are intended to be
the terminal element of
air supply for premises
with high demands on thecleanness of supplied air,
like surgeries, sterilisation
premises, intensive care
units, premises in the phar-
maceutical, electrical, engi-
neering, foodstuff industries,
etc.
8/16/2019 Hospital Vent
32/48
Raster[mm]
C x C
Filter
AIR SUPPLY TYPE
Side circularSide rectangular
+ one-side conversionTop circular
HEPA H13MDF frame
[mm]
HEPA H14Al frame
[mm]
Throatdimen-
sion[mm]
Totalheight
[mm]
Heightof bottomstructure
[mm]
Heightof top
structure[mm]
Throatdimension
[mm]
Totalheight
[mm]
Heightof bottomstructure
[mm]
Heightof top
structure[mm]
Throatdimension
[mm]
Totalheight
[mm]
Heightof bottomstructure
[mm]
Heightof top
structure[mm]
A x A x B D H G I E x F H G I D H G I
625x625
570x570x149Ø250 555 255 300 530x95 380 255 125 Ø250 345 255 90
Ø315 625 255 370 530x145 430 255 175 Ø315 345 255 90
570x570x117Ø250 520 220 300 530x95 345 220 125 Ø250 310 220 90
Ø315 590 220 370 530x145 395 220 175 Ø315 310 220 90
BLOCK a.s., U Kasáren 727, 757 01 Valašské Meziříčí, tel.: +420 571 670 111, fax: +420 571 670 244, e-mail: [email protected], www.block.cz
108.01 B FILTRATION EXTENDERS, TYPE PUROFIL - TYPE FNC
DESCRIPTION
STANDARD DIMENSION LINE
OPTIONAL ELEMENTS FURTHER AIR SUPPLY OPTIONS
B P
• 0 6
• 0 6
PUROFIL
• Bottom structure
- secures the shape stability- fitted with the HEPA filter - contains a distribution element
(whirl outlets, perforated sheet or anemostat)• Top structure
- zinc-coated sheet - with air supply of the • side rectangular shape
• side circular shape• top circular shape
As a standard, the extenders are provided with one probefor the leakage aerosol tests.
THE EXTENDER IS FULLY COMPATIBLE WITH THE LIGHT METALSOFFIT (Cat. No. 105).
H
A
C
G
E
F
B
Installation into soft
Light metal soft, FORCLEAN
Thermatex
Metal panel-type soft
Type dimensions of the raster [mm] 625 x 625
Surfaceof the PUROFIL elements
Powder-type stove enamel, Komaxit, with standard colours,RAL 9010, 9002, 6027, 1015, or stainless steel, AISI 304, FIN 8 grind
Surfaceof the output element
Powder-type stove enamel, Komaxit, with standard colours,RAL 9010, 9002, 6027, 1015, or stainless steel, AISI 304, FIN 8 grind
Filter frame materialAluminium (for the ltration class H13, H14)
MDF (for the ltration class H13)
Output elementWhirling innovated, whirling element, whirling element dense, perforated sheet
or anemostat
Accessories - one-sideconversions [mm]
530x145 / Ø315
530x95 / Ø251
Accessories – probes1 probe as a standard
2 probes
A
Bottom structure
Filter
Top structure
HVAC flange
Raster
Snap-type profile
PUROFIL, WITH SIDE RECTANGULAR AIR SUPPLY
TECHNICAL PARAMETERS
FILTER DISTRIBUTION ELEMENT
Media height [“] Weight [kg] Flow-rate [m3/hod] Initial pressure drop [Pa] Flow speed [m/s] Whirl ing, innovated Whirl ing, standard Whirl ing, dense Perforated Anemostat
HEPA H13
MDF frame
570x570x149
[mm]
1” 5,5 300 86 0,15 yes yes no yes no
2” 5,5 560 94 0,3 yes no yes yes yes
3” 5,5 760 103 0,45 yes no yes yes yes
4” 5,5 880 116 0,6 yes no no yes yes
HEPA H14
Al frame570x570x117
[mm]
1” 4,5 300 86 0,15 yes yes no yes no
2” 4,5 560 94 0,3 yes no yes yes yes3” 4,5 760 103 0,45 yes no yes yes yes
4” 3,5 880 116 0,6 yes no no yes yes
TOP CIRCULAR
SIDE CIRCULAR
D
D
C
I
medical
8/16/2019 Hospital Vent
33/48
F i l t r a t i o n
o u t l e t
f o r
s u r g e r i e s
The filtration outlet is connected to HVAC ducts
supplying pre-filtered air (at least F7 class in complian-
ce with Czech standard norm EN 779) of a prescribed
temperature and relati ve humidity.
In the fil tration outlet air is treated to reach the required clean-liness (H13 ÷ H14 HEPA filters).
The filtration outlet
serves for establishing
of a uniform air stre-
am, of a defined clean-
liness class, in the o-
peration sector of sep-
tic, aseptic, and super-
aseptic surgeries.
The implementation
of the filtration outlet
prevents the operation
sector from the conta-
mination by bacteria,
viruses, and dust par-
ticles.
The highest hygienic
and technical require-
ments for the air filtra-
tion are hereby met.
The product has been cert if ied in EU countr ies.
FILTRATION OUTLET FOR SURGERIES
Cat. No. 108.03 A
medical COMPONENTS FOR MEDICAL PREMISESAND SUR GERIES IMPLEMENTATION
8/16/2019 Hospital Vent
34/48BLOCK a.s., U Kasáren 727, 757 01 Valašské Meziříčí, tel.: +420 571 670 111, fax: +420 571 670 244, e-mail: [email protected], www.block.cz
108.03 A FILTRATION OUTLET FOR SURGERIES
medical
Illuminationcontrol
dimming illuminationnon-dimming illumination
no light ttings
Lighting(tube types)
90219 49 W F49W/T5/HO/830, luminous ux 4,900 lm length 1,449 mm
90223 49 W F49W/T5/HO/840, luminous ux 4,900 lm length 1,449 mm
no uor tubes
HEPA ltersH13; H14 - lter frame of Al; lter height 117mm; 4“ medium
H13 - lter frame of MDF; lter height 130mm; 4“ medium
Screens
no screens
exible screens (length to be laid down - min. 100 mm)
xed screens (length to be laid down - min. 100 mm)
antistatic exible screens (length to be laid down - min. 100 mm)
antistatic xed screens (length to be laid down - min. 100 mm)
Fixing of the lami-nar ow device
quick-acting clamps
threaded connection and riveting nutsTube diameterof the operation lighttting
125 mm as a standard
atypical diameter
TECHNICAL DESCRIPTION
TECHNICAL PARAMETERS
Filtrationoutlet
dimensions[mm]
Maximum air ow parameters Recommended air ow parameters
Air owQ
max
[m3/hod]
InitialΔp
max[Pa] for
the H13/H14
HEPA lters
Outputvelocityv
max[m/s]
Acousticpressure
level[dB(A)]*
Air ow Q[m3/hod]
InitialΔp
[Pa] for
the H13/H14
HEPA lters
Outputvelocityv [m/s]
Acousticpressure
level[dB(A)]*
1875x1875 3797 170/207 0,3 40 2785 150/183 0,22 36
1875x2500 5062 190/232 0,3 40 3712 170/207 0,22 36
2500x2500 6750 190/232 0,3 40 4950 170/207 0,22 36
FILTRATION OUTLET – 1,875 x 1