Description Hoval UltraGas ® Cascades CL/R (140-450) Floor standing gas condensing boiler in series Subject to alterations, 1.8.2013 93 Hoval UltraGas ® (70,90) Cascades consisting of the following components 2,3,4 or 5 gas boiler UltraGas ® (70,90) Hydraulic pipe connection Flue gas over pressure set All components must be ordered separately. (see «page 2 and 3»). On-site Installation of hydraulic connection set Installation of flue gas over pressure set Pressure gauge, automatic air vent, safety valve Data bus connecting cable Hoval UltraGas ® (70,90) Gas boiler Heating boiler made of steel with conden- sing systems Combustion chamber made of stainless steel Maximal flue gas condensation through downstream heating surface made of aluFer ® stainless steel bounded pipe; flue gas side: aluminium water side: stainless steel Thermal insulation with mineral wool mat Water pressure sensor (built-in water shortage protection) Flue gas temperature sensor with flue gas limiter function Pre-mix burner - with blower and venturi - Automatic ignition - Ionisation guard Gas boiler fully cased with steel plate, red powder-coated Heating connections to left and right for: - Flow - Return - high temperature - Return - low temperature UltraGas ® (70,90): Combustion air connection, vertically upwards Control panel TopTronic ® T/U4.1 Gas firing sequence controller with monito- ring unit BIC960 Modulating burner control Connection for external gas solenoid valve and fault indication Regulation function integrated for: - 1 mixer circuit - 1 heating circuit without mixing operation - domestic hot water loading circuit Option to expand the functions - by different Key Module and/or - UltraGas(70,90) Installation of a supplementary heating regulator TopTronic ® T/N (see accessories) Main switch „I/O“ Safety temperature limiter 110 °C Fuse 6.3 A Trouble indication «Burner» Running time meter and count-up Boiler sensor Large LCD-Displays Rotary pushbutton Buttons for - daytime room temperature - night room temperature - hot water temperature - operating mode selection (holiday, absent, heating operation prolongation, automa- tic, summer, continuous - reduced - frost protection) - adjusting the heating curves - system information - emission measurement and manual operation Outdoor sensor AF 200 Flow sensor with plug Calorifier heater sensor with plug Connection available for room station Optional For propane Free standing calorifier «Calorifier» Flue gas systems Delivery Floor standing gas condensing boiler fully cased Hydraulic connection set Pipe system consisting of Feed line connection between boilers incl. biral pump M14, check valve and balancing valve Return line connection between boilers Two executions for heating flow connection: top right (cascade CR) or top left (cascade CL) Model range UltraGas ® Cascade UltraGas ® Output range at 40/30 °C Type Type kW 2 CL (140) (70) 13,6-140 2 CR (140) (70) 13,6-140 2 CL (180) (90) 16,1-183 2 CR (180) (90) 16,1-183 3 CL (210) (70) 13,6-210 3 CR (210) (70) 13,6-210 3 CL (270) (90) 16,1-275 3 CR (270) (90) 16,1-275 4 CL/R (280) (70) 13,6-280 4 CL/R (360) (90) 16,1-366 5 CL/R (350) (70) 13,6-350 5 CL/R (450) (90) 16,1-458 Delivery Hydraulic connection set packed and delivered separately. Flue gas over pressure set consisting of: Motorized air intake flaps and flue gas collector Delivery flue gas over pressure set supplied in separate packaging BMS-Modul 0-10 V (Bulding managment system) For boiler control as part of a building manage- ment system. External temperature control 0-10 V 0-1,0 V desired value 1,0-10,0 V ...... 11,5-115°C External temperature control with 1 0-10 V 0-0,4 V without temperature control (automatic) 0,5-0,9 V ...... Boiler off 0 % 1,0-10,0 V ...... 10-100 % Can be installed in the boiler control panel! 1 see engineering instructions Permissions boilers UltraGas ® (70,90) CE-Product-ID-No. CE-0085AQ0620
Transcript
Page 1: Hoval UltraGas® Cascades CL/R (140-450)

■ Description

Hoval UltraGas® Cascades CL/R (140-450)Floor standing gas condensing boiler in series

Subject to alterations, 1.8.2013 93

Hoval UltraGas® (70,90) Cascadesconsisting of the following components• 2,3,4 or 5 gas boiler UltraGas® (70,90)• Hydraulic pipe connection• Flue gas over pressure setAll components must be ordered separately. (see «page 2 and 3»).

On-site • Installation of hydraulic connection set• Installationoffluegasoverpressureset• Pressure gauge, automatic air vent,

safety valve• Data bus connecting cable

Hoval UltraGas® (70,90)Gas boiler• Heating boiler made of steel with conden-

sing systems• Combustion chamber made of stainless

steel• Maximalfluegascondensationthrough

downstream heating surface made of aluFer® stainless steel bounded pipe;fluegasside:aluminiumwaterside: stainless steel

• Thermal insulation with mineral wool mat• Water pressure sensor

(built-in water shortage protection)• Fluegastemperaturesensorwithfluegas

limiter function• Pre-mix burner

- with blower and venturi - Automatic ignition - Ionisation guard

• Gas boiler fully cased with steel plate, red powder-coated

• Heatingconnectionstoleftandrightfor: - Flow - Return - high temperature - Return - low temperature

• UltraGas® (70,90): Combustion air connection, vertically upwards

Control panel TopTronic®T/U4.1• Gasfiringsequencecontrollerwithmonito-

ring unit BIC960• Modulating burner control• Connection for external gas solenoid valve

and fault indication• Regulationfunctionintegratedfor:

- 1 mixer circuit - 1 heating circuit without mixing operation - domestic hot water loading circuit

• Option to expand the functions - by different Key Module and/or - UltraGas(70,90)

Installation of a supplementary heating regulator TopTronic®T/N (see accessories)

• Main switch „I/O“• Safety temperature limiter 110 °C• Fuse 6.3 A• Trouble indication «Burner»• Running time meter and count-up• Boiler sensor• Large LCD-Displays• Rotary pushbutton• Buttons for

- daytime room temperature - night room temperature - hot water temperature

- operating mode selection (holiday, absent, heating operation prolongation, automa-tic, summer, continuous - reduced - frost protection)

- adjusting the heating curves - system information - emission measurement

and manual operation• Outdoor sensor AF 200• Flow sensor with plug• Calorifierheatersensorwithplug

Connection available for room station

Optional• For propane• Freestandingcalorifier«Calorifier»• Flue gas systems

Delivery• Floor standing gas condensing boiler

fully cased

Hydraulic connection setPipe system consisting of• Feed line connection between boilers

incl. biral pump M14, check valve and balancing valve

• Return line connection between boilers • Twoexecutionsforheatingflowconnection:

top right (cascade CR) or top left (cascade CL)

Model rangeUltraGas® Cascade

UltraGas®

Output range at 40/30 °C

Type Type kW

2 CL (140) (70) 13,6-1402 CR (140) (70) 13,6-1402 CL (180) (90) 16,1-1832 CR (180) (90) 16,1-1833 CL (210) (70) 13,6-2103 CR (210) (70) 13,6-2103 CL (270) (90) 16,1-2753 CR (270) (90) 16,1-2754 CL/R (280) (70) 13,6-2804 CL/R (360) (90) 16,1-3665 CL/R (350) (70) 13,6-3505 CL/R (450) (90) 16,1-458

DeliveryHydraulic connection set packed and delivered separately.

Flue gas over pressure setconsisting of:• Motorizedairintakeflaps

and fluegascollector

Deliveryflue gas over pressure set supplied in separate packaging

BMS-Modul 0-10 V(Bulding managment system)For boiler control as part of a building manage-ment system.External temperature control 0-10 V0-1,0 V desired value1,0-10,0 V ...... 11,5-115°CExternal temperature control with 1 0-10 V0-0,4 V without temperature control (automatic)0,5-0,9 V ...... Boiler off 0 %1,0-10,0 V ...... 10-100 %Can be installed in the boiler control panel!

1 see engineering instructions

Permissions boilersUltraGas® (70,90)

CE-Product-ID-No. CE-0085AQ0620

Page 2: Hoval UltraGas® Cascades CL/R (140-450)

■ Part N°

Part N°

94 Subject to alterations, 1.8.2013

Hoval UltraGas® Cascades CL/R (140-450)

Hoval UltraGas® Cascades

Hoval UltraGas®

Standing gas condensing boilerFloor standing gas condensing boiler, com-bustion chamber made of stainless steel. Down stream heating surface made of aluFer® stainless steel bounded pipe. Pre-mix burner with blower fan. Modulating burner. With boiler control TopTronic®T/U4.1

DeliveryBoiler fully cased

Modification propaneOutput range see technical data

for UltraGas® (70) 619 568for UltraGas® (90) 6015 663

Cascade Type Connectionsnumberboiler

Set of 2 2 C-HS-R right 2 6025 423Set of 2 2 C-HS-L left 2 6025 424

Set of 3 3 C-HS-R right 3 6025 425Set of 3 3 C-HS-L left 3 6025 426

Set of 4 4 C-HS-RL right/ left 4 6025 427

Set of 5 5 C-HS-RL right/ left 5 6025 428

UltraGas® Output rangeType kW at 40/30 °C

(70) 13,6 - 69,9(90) 16,1 - 91,5

7007 664 7007 665

Hydraulic connection setEach set is matched to Hoval UltraGas® (70,90)

One set per cascade necessary!

Order the number of boilers necessary for the cascade!

Page 3: Hoval UltraGas® Cascades CL/R (140-450)

■ Part N°

Part N°

Hoval UltraGas® Cascades CL/R (140-450)

Subject to alterations, 1.8.2013 95

Cascade Type Connectionsnumberboiler

Set of 2 2C-AS right/ left 2 6025 443

Set of 3 3C-AS right/ left 3 6025 444

Set of 4 4C-AS right/ left 4 6025 445

Set of 5 5C-AS right/ left 5 6025 446

Flue gas over pressure setEach set is matched to Hoval UltraGas® (70,90)

Hoval UltraGas® Cascades

One set per cascade necessary!

2007 995 2007 996

Gas filterwith measurement nozzle before and behind thefilterinset(diameter:9mm)Porewidthofthefilterinset<50mmMax. pressure difference 10 mbarMax. inlet pressure 100 mbar

Type Connection

70612/6B Rp ¾"70602/6B Rp 1"

Hydraulic switch with deaerator MH (100)completely insulated and encased, inclusive Victaulic flanges, ½" fitting for the temperature sensor, exhaust automat with automatic shut-off valve, rinsing and emptying device on the soil and the cover.

6032 315

Page 4: Hoval UltraGas® Cascades CL/R (140-450)

Room station RS-Tfor TopTronic®Teffective on one mixing circuit

2034 939

Remote control RFF-Tfor TopTronic®Teffective on one mixing circuit

2022 239

Outdoor sensor AF 200(may be included in the heat generatorscope of delivery)for one mixing circuit or for the meanvalue (per regulator 2 outdoortemperature sensors possible)

2022 995

Cable sensor KVT 20/5/6S5 m cable and plug

6012 687

Contact sensor VF204Scan be used as flow or returnflow sensorwith 4 m cable and plug

6012 688

■ Part N°

Part N°

96 Subject to alterations, 1.8.2013

Hoval UltraGas® Cascades CL/R (140-450)

Accessories

Set BMS-Module 0-10 V (Building management system)Consistingof:BMS-ModuleandTrafoCan be installed in the boiler controlpanel!

6015 195

Communication modules/remote connection see Controls

Additional heating regulator set ZN1for extending functionality and implementing further heating circuitsConsistingof:Heating regulator TopTronic®T/N for- 1 mixer circuit- 1 heating circuit without mixer- hot water loadingOnly one key module per regulator is possible!Flow sensor VF202Kwith 2 m cable and plug.Cable set for connecting the auxiliary heatingregulator TopTronic®T/ N with the boiler con-trol ler.Mounting on-site

6020 574 274,51

Page 5: Hoval UltraGas® Cascades CL/R (140-450)

■ Part N°

Part N°

Hoval UltraGas® Cascades CL/R (140-450)

Subject to alterations, 1.8.2013 97

Key-Module 1for 2. mixing circuitFunction key 1, 1 flow sensor, 2 loose plugs

Key-Module 2for solid fuel/ storage tank/ bivalent installationFunction key 2, 3 immersion sensors, 4 looseplugs

Key-Modul 3for solar plantsFunction key 3, 1 collector sensor, 1 calorifiersensor, 4 loose plugs

Key-Module 4for 2. mixing circuit and solid fuel/ storage tank/bivalent installationFunction key 4, 1 flow sensor, 3 immersion sensors, 6 loose plugs

Key-Module 5for 2. mixing circuit and solar plantsFunction key 5, 1 flow sensor, 1 collector sensor,1 calorifier sensor, 6 loose plugs

Key-Module 6for solid fuel/ storage tank/ bivalent installationand solar plantsFunction key 6, 1 collector sensor, 4 immersionsensors, 6 loose plugs

Key-Module 7for 2. mixing circuit, solid fuel/ storage tank/bivalent installation and solar plantsFunction key 7, 1 flow sensor, 1 collector sensor,4 immersion sensors, 8 loose plugs

Sensor typeImmersion/calorifiersensor: Type KVT20/5/6 (L = 5 m) without immersion sleeveflowsensor: TypeVF204Swithplugcollectorsensor: TypePT1000(Silicone)

Accessoires for heating regulator system Hoval TopTronic®T

M

Key-Module for Hoval TopTronic®Tfor further functions additionally to standard functions.Key-Modul consists of: Function key for plugging into TopTronic®T

TopTronic®T incl. accessoriesOnly one Key-Module possible!

Standard functionsalready included in TopTronic®T.- 1 mixer circuit- 1 heating circuit without mixing operation- domestic hot water loading circuit

1

2

3

4

5

6

7

1-7

M

M

M

M

M

M

3

Functions of key modulesKey- 2. mixing solid fuel- SolarModule circuit storage tank- Bivalent

2

1

4

5

6

7

M

System approaches and applicationssee Hoval CD

6012 154

6012 155

6012 156

6012 157

6012 158

6012 159

6012 160

Page 6: Hoval UltraGas® Cascades CL/R (140-450)

Safety set SG20-1"Range of application to 100 kWcomplete with safety valve (3 bar)Pressure gauge and autom.aspirator with shut-off valve.Connection:DN201"internalthread

6014 390

Condensate pumpfor UltraGas® (70,90), UltraOil® (50)for transporting condensation waterinto a higher drainage ductIncluding connection linecompletely wiredcable and plug for connectionto the boiler controllerMax.transportheight:3.5mcombinable with neutralisation boxcan be mounted in boiler socket

6025 850

Neutralisation boxfor UltraOil® 50, UltraGas® (70,90)for transporting condensation water intoa lower lying drainage duct incl.neutralisation granulate 6 kg.Combinable with condensate pump;can be mounted in boiler socket

6012 553

Neutralisation granulatefor neutralisation boxRefill set volume 3 kgLifetimeofonefilling:approx. 2-4 years; depending on amountof condensate

2028 906

■ Part N°

Part N°

98 Subject to alterations, 1.8.2013

Hoval UltraGas® Cascades CL/R (140-450)

Flow temperature guard for under floor heating (1 guard per heating circuit) 15-95 °C, differential gap 6K, capillary tube max. 700 mm, setting (visible from the outside) inside the housing cover.

Clamp-on thermostat RAK-TW1000.SThermostat with strap, enclosed cable and plug

242 902

Set Clamp-on thermostat RAK-TW1000.SThermostat with strap, with cable (4 m) and plug

6015 000

Immersion thermostat RAK-TW1000.S SB 150Thermostat with immersion sleeve ½“ - depth of immersion150 mm, brass nickel-plated

6010 082

Drainage duct

Commissioning

Commissioning must be made by works ser-vice or Hoval trained authorized serviceman/company is condition for warranty.

For commissioning and other services pleasecontactyourHovalsalesoffice.

Service

Accessories

Page 7: Hoval UltraGas® Cascades CL/R (140-450)

■ Technical data

Hoval UltraGas® Cascades CL/R (140-450)

Subject to alterations, 1.8.2013 99

UltraGas® (70) (90) (70) (90) (70) (90) (70) (90)2er Kaskade 3er Kaskade 4er Kaskade 5er Kaskade

2 CR (140)

2 CR (180)

3 CR (210)

3 CR (270) 4 CR (280) 4 CR (360) 5 CR (350) 5 CR (450)

•Nenn-Wärmeleistung bei 80/ 60 °C bei Erdgas 1 kW 25-127 29-167 37-190 43-250 49-253 57-333 61-316 72-417

•Nenn-Wärmeleistung bei 40/ 30 °C bei Erdgas 1 kW 27-140 32-183 41-210 48-275 54-280 64-366 68-350 68-458

•Nenn-Wärmeleistung bei 80/ 60 °C bei Propangas 3 kW 31-126 35-167 46-190 52-250 62-253 70-333 77-316 87-417

•Nenn-Wärmeleistung bei 40/ 30 °C bei Propangas 3 kW 34-140 39-183 51-210 58-275 68-280 77-366 85-350 96-458

• Nenn-Wärmebelastung bei Erdgas 1 kW 23-131 29-172 37-197 44-258 50-262 59-344 62-328 73-430• Nenn-Wärmebelastung bei Propangas 3 kW 32-131 36-172 48-197 54-268 64-262 72-344 80-328 90-430

• Betriebsdruck Heizung max./min. bar 4,0 / 1,0 4,0 / 1,0 4,0 / 1,0 4,0 / 1,0 4,0 / 1,0 4,0 / 1,0 4,0 / 1,0 4,0 / 1,0

• Kesselwasserinhalt (gesamte Kaskade) l 314 298 471 447 628 596 785 745• Mindestumlaufwassermenge l/h 0 0 0 0 0 0 0 0

•Kesselgewicht (ohne Wasserinhalt, inkl. Verschalung) kg 498 536 747 804 996 1072 1245 1340

•Kesselwirkungsgrad bei Teillast bei 30% (nach EN 303)

• Normnutzungsgrad (nach DIN 4702 Teil 8) 40/ 30 °C % 109,6/98,7 109,6/98,7 109,6/98,7 109,6/98,7(bezogen auf unteren / oberen Heizwert) 75/ 60 °C % 107,1/96,5 107,1/96,5 107,1/96,5 107,1/96,5

• Bereitschaftswärmeverluste bei 70 °C (Kessel) Watt 580 580 870 870 1160 1160 1450 1450• Normemissionsfaktoren Stickoxide mg/kWh 32 39 32 39 32 39 32 39

Kohlenmonoxide mg/kWh 3 3 3 3 3 3 3 3• CO2 Gehalt im Abgas max./min. Leistung % 9,0 / 8,8 9,0 / 8,8 9,0 / 8,8 9,0 / 8,8 9,0 / 8,8 9,0 / 8,8 9,0 / 8,8 9,0 / 8,8

• Masse siehe Abmessungen

• Anschlüsse Vor- Rücklauf DN

Luft-/Abgas mm

• Gasfliessdruckmin./max.

Flüssiggas mbar 37-50 37-50 37-50 37-50 37-50 37-50 37-50 37-50• Gas-Anschlusswertebei0°C/1013mbar:

Erdgas E - (Wo = 15,0 kWh/m3) Hu = 9,97 kWh/m3 m3/h 13.2 17.2 19.8 25.8 26.4 34.4 33.0 43.0Erdgas LL- (Wo = 12,4 kWh/m3) Hu = 8,57 kWh/m3 m3/h 15.2 20.0 22.8 30.0 30.4 40.0 38.0 50.0Propangas (Hu = 25,9 kWh/m3) m3/h 5.0 6.6 7.5 9.9 10.0 13.2 12.5 16.5

Note:Technical Data Hoval UltraGas® (70,90) see Hoval UltraGas® (15-90)

Page 8: Hoval UltraGas® Cascades CL/R (140-450)

■ Technical data

100 Subject to alterations, 1.8.2013

Hoval UltraGas® Cascades CL/R (140-450)

UltraGas® (70) (90) (70) (90) (70) (90) (70) (90)2er Kaskade 3er Kaskade 4er Kaskade 5er Kaskade

Typ2 CL (140)

2 CL (180)

3 CL (210)

3 CL (270) 4 CL (280) 4 CL (360) 5 CL (350) 5 CL (450)

2 CR (140)

2 CR (180)

3 CR (210)

3 CR (270) 4 CR (280) 4 CR (360) 5 CR (350) 5 CR (450)

•Nenn-Wärmeleistung bei 80/ 60 °C bei Erdgas 1 kW 25-127 29-167 37-190 43-250 49-253 57-333 61-316 72-417

•Nenn-Wärmeleistung bei 40/ 30 °C bei Erdgas 1 kW 27-140 32-183 41-210 48-275 54-280 64-366 68-350 68-458

•Nenn-Wärmeleistung bei 80/ 60 °C bei Propangas 3 kW 31-126 35-167 46-190 52-250 62-253 70-333 77-316 87-417

•Nenn-Wärmeleistung bei 40/ 30 °C bei Propangas 3 kW 34-140 39-183 51-210 58-275 68-280 77-366 85-350 96-458

• Nenn-Wärmebelastung bei Erdgas 1 kW 23-131 29-172 37-197 44-258 50-262 59-344 62-328 73-430• Nenn-Wärmebelastung bei Propangas 3 kW 32-131 36-172 48-197 54-268 64-262 72-344 80-328 90-430

• Betriebsdruck Heizung max./min. bar 4,0 / 1,0 4,0 / 1,0 4,0 / 1,0 4,0 / 1,0 4,0 / 1,0 4,0 / 1,0 4,0 / 1,0 4,0 / 1,0

• Kesselwasserinhalt (gesamte Kaskade) l 314 298 471 447 628 596 785 745• Mindestumlaufwassermenge l/h 0 0 0 0 0 0 0 0

•Kesselgewicht (ohne Wasserinhalt, inkl. Verschalung) kg 498 536 747 804 996 1072 1245 1340

•Kesselwirkungsgrad bei Teillast bei 30% (nach EN 303)

• Normnutzungsgrad (nach DIN 4702 Teil 8) 40/ 30 °C % 109,6/98,7 109,6/98,7 109,6/98,7 109,6/98,7(bezogen auf unteren / oberen Heizwert) 75/ 60 °C % 107,1/96,5 107,1/96,5 107,1/96,5 107,1/96,5

•Bereitschaftswärmeverluste bei 70 °C (Kessel) Watt 580 580 870 870 1160 1160 1450 1450

• Normemissionsfaktoren Stickoxide mg/kWh 32 39 32 39 32 39 32 39Kohlenmonoxide mg/kWh 3 3 3 3 3 3 3 3

• CO2 Gehalt im Abgas max./min. Leistung % 9,0 / 8,8 9,0 / 8,8 9,0 / 8,8 9,0 / 8,8 9,0 / 8,8 9,0 / 8,8 9,0 / 8,8 9,0 / 8,8

Gas ZollLuft-/Abgas mm

Erdgas E/LL mbar 18-50 18-50 18-50 18-50 18-50 18-50 18-50 18-50Flüssiggas mbar 37-50 37-50 37-50 37-50 37-50 37-50 37-50 37-50

• Gas-Anschlusswertebei0°C/1013mbar:Erdgas E - (Wo = 15,0 kWh/m3) Hu = 9,97 kWh/m3 m3/h 13.2 17.2 19.8 25.8 26.4 34.4 33.0 43.0Erdgas LL- (Wo = 12,4 kWh/m3) Hu = 8,57 kWh/m3 m3/h 15.2 20.0 22.8 30.0 30.4 40.0 38.0 50.0

Note:Technical Data Hoval UltraGas® (70,90) see Hoval UltraGas® (15-90)

Page 9: Hoval UltraGas® Cascades CL/R (140-450)

■ Dimensions

Hoval UltraGas® Cascades CL/R (140-450)

Subject to alterations, 1.8.2013 101

Hoval UltraGas® (70,90)(Dimensions in mm)

Space requirements

Legend (70) (90)

1. Flowheating/safetyflow R1½" R1½"2. Low temperature-return R1½" R1½"2a. High temperature-return R1½" R1½"3. Duct for the gas pipe left or right R ¾" R ¾"4. LASfluegas/supplyairconnection C100/150 C100/1505. Control panel C100/150 E1006. Condensate drain (left or right)

incl. syphon (DN25) and 2 m PVC passage tube ø-inside19x4

7. Electrical connection left or right8. Drain (behind the front casing) ½" ½"

UltraGas® (70) (90) (70) (90) (70) (90) (70) (90)2er Kaskade 3er Kaskade 4er Kaskade 5er Kaskade

Typ2 CL (140)

2 CL (180)

3 CL (210)

3 CL (270) 4 CL (280) 4 CL (360) 5 CL (350) 5 CL (450)

2 CR (140)

2 CR (180)

3 CR (210)

3 CR (270) 4 CR (280) 4 CR (360) 5 CR (350) 5 CR (450)

•Nenn-Wärmeleistung bei 80/ 60 °C bei Erdgas 1 kW 25-127 29-167 37-190 43-250 49-253 57-333 61-316 72-417

•Nenn-Wärmeleistung bei 40/ 30 °C bei Erdgas 1 kW 27-140 32-183 41-210 48-275 54-280 64-366 68-350 68-458

•Nenn-Wärmeleistung bei 80/ 60 °C bei Propangas 3 kW 31-126 35-167 46-190 52-250 62-253 70-333 77-316 87-417

•Nenn-Wärmeleistung bei 40/ 30 °C bei Propangas 3 kW 34-140 39-183 51-210 58-275 68-280 77-366 85-350 96-458

• Nenn-Wärmebelastung bei Erdgas 1 kW 23-131 29-172 37-197 44-258 50-262 59-344 62-328 73-430• Nenn-Wärmebelastung bei Propangas 3 kW 32-131 36-172 48-197 54-268 64-262 72-344 80-328 90-430

• Betriebsdruck Heizung max./min. bar 4,0 / 1,0 4,0 / 1,0 4,0 / 1,0 4,0 / 1,0 4,0 / 1,0 4,0 / 1,0 4,0 / 1,0 4,0 / 1,0

• Kesselwasserinhalt (gesamte Kaskade) l 314 298 471 447 628 596 785 745• Mindestumlaufwassermenge l/h 0 0 0 0 0 0 0 0

•Kesselgewicht (ohne Wasserinhalt, inkl. Verschalung) kg 498 536 747 804 996 1072 1245 1340

•Kesselwirkungsgrad bei Teillast bei 30% (nach EN 303)

• Normnutzungsgrad (nach DIN 4702 Teil 8) 40/ 30 °C % 109,6/98,7 109,6/98,7 109,6/98,7 109,6/98,7(bezogen auf unteren / oberen Heizwert) 75/ 60 °C % 107,1/96,5 107,1/96,5 107,1/96,5 107,1/96,5

•Bereitschaftswärmeverluste bei 70 °C (Kessel) Watt 580 580 870 870 1160 1160 1450 1450

• Normemissionsfaktoren Stickoxide mg/kWh 32 39 32 39 32 39 32 39Kohlenmonoxide mg/kWh 3 3 3 3 3 3 3 3

• CO2 Gehalt im Abgas max./min. Leistung % 9,0 / 8,8 9,0 / 8,8 9,0 / 8,8 9,0 / 8,8 9,0 / 8,8 9,0 / 8,8 9,0 / 8,8 9,0 / 8,8

Gas ZollLuft-/Abgas mm

Erdgas E/LL mbar 18-50 18-50 18-50 18-50 18-50 18-50 18-50 18-50Flüssiggas mbar 37-50 37-50 37-50 37-50 37-50 37-50 37-50 37-50

• Gas-Anschlusswertebei0°C/1013mbar:Erdgas E - (Wo = 15,0 kWh/m3) Hu = 9,97 kWh/m3 m3/h 13.2 17.2 19.8 25.8 26.4 34.4 33.0 43.0Erdgas LL- (Wo = 12,4 kWh/m3) Hu = 8,57 kWh/m3 m3/h 15.2 20.0 22.8 30.0 30.4 40.0 38.0 50.0

Page 10: Hoval UltraGas® Cascades CL/R (140-450)

■ Dimensions

102 Subject to alterations, 1.8.2013

Hoval UltraGas® Cascades CL/R (140-450)

Hoval UltraGas® Cascade 2 CL (140,180)

1 Flow DN652 Return DN653 Combustion air connection ∅ 200

mountable on both sides4 Position solar tank sensor5 Splice for bleeder 1/2"6 cleaning opening

Hoval UltraGas® Cascade 2 CR (140,180)

1 Flow DN652 Return DN653 Combustion air connection ∅ 200

mountable on both sides4 Position solar tank sensor5 Splice for bleeder 1/2"6 cleaning opening

Page 11: Hoval UltraGas® Cascades CL/R (140-450)

■ Dimensions

Hoval UltraGas® Cascades CL/R (140-450)

Subject to alterations, 1.8.2013 103

Hoval UltraGas® Cascade 3CL (210,270)

Hoval UltraGas® Cascade 3CR (210,270)

1 Flow DN652 Return DN653 Combustion air connection ∅ 200

mountable on both sides4 Position solar tank sensor5 Splice for bleeder 1/2"6 cleaning opening

1 Flow DN652 Return DN653 Combustion air connection ∅ 200

mountable on both sides4 Position solar tank sensor5 Splice for bleeder 1/2"6 cleaning opening

Page 12: Hoval UltraGas® Cascades CL/R (140-450)

■ Dimensions

104 Subject to alterations, 1.8.2013

Hoval UltraGas® Cascades CL/R (140-450)

Hyd

raul

ic s

witc

h

Hyd

raul

ic s

witc

h

Hoval UltraGas® Cascade 4CL (280,360)

Hoval UltraGas® Cascade 4CR (280,360)

1 Flow DN652 Return DN653 Combustion air connection ∅ 200

mountable on both sides4 Position solar tank sensor5 Splice for bleeder 1/2"5 cleaning opening

1 Flow DN652 Return DN653 Combustion air connection ∅ 200

mountable on both sides4 Position solar tank sensor5 Splice for bleeder 1/2"5 cleaning opening

Page 13: Hoval UltraGas® Cascades CL/R (140-450)

■ Dimensions

Hoval UltraGas® Cascades CL/R (140-450)

Subject to alterations, 1.8.2013 105

Hyd

raul

ic s

witc

h

1 Flow DN1002 Return DN1003 Combustion air connection ∅ 200

mountable on both sides4 Splice for bleeder 1/2"5 cleaning opening

Hyd

raul

ic s

witc

h

1 Flow DN1002 Return DN1003 Combustion air connection ∅ 200

mountable on both sides4 Splice for bleeder 1/2"5 cleaning opening

Hoval UltraGas® Cascade 5CL (350,450)

Hoval UltraGas® Cascade 5CR (350,450)

Page 14: Hoval UltraGas® Cascades CL/R (140-450)

■ Engineering

106 Subject to alterations, 1.8.2013

Hoval UltraGas® Cascades CL/R (140-450)

Standards and guidelinesThe following standards and guidelines must becompliedwith:

• Hoval technical information and installation in structions.

• Hydraulic and technical control regulations of Hoval.

• Local building law

• Fire protection regulations

• DVGW regulations.

• DIN EN 12828 Safety-relevantrequirements.

• DIN EN 12831 Heaters Rulesforthecalculationoftheheatrequire-

ments of buildings.

• VDI 2035 Protection against damage by cor-rosion and boiler scale formation in heating and service water installations.

• VDE 0100

• Localfirebrigaderegulations

• According to local regulations.

Water qualityHeatingwater:• The European Standard EN 14868 and the

Directive VDI 2035 must be observed. In particular, attention must be paid to the fol-lowingstipulations:

• Hovalboilersandcalorifiersaredesignedforheatingplantswithoutsignificantoxygenintake (plant type I according to EN 14868).

• Plants with - continuous oxygen intake (e.g. under-

floor heating systems without diffusion proof plastic piping) or

- intermittent oxygen intake (e.g. where frequentrefillingisnecessary)

mustbeequippedwithseparate circuits.

• Treated heating water must be tested at least 1x yearly, according to the inhibitor manufacturer‘sinstructions,morefrequenttesting may be necessary.

• Arefillingisnotnecessaryifthequalityofthe heating water in existing installations (e.g. exchange of boiler) conforms to VDI 2035.TheDirectiveVDI2035appliesequal-ly to the replacement water.

• New and if applicable existing installations mustbeadequatelycleanedandflushedbefore being recharged! The boiler may only befilledaftertheheatingsystemhasbeenflushed.

• Partsoftheboiler/thecalorifierwhichhavecontact with water are made of ferrous ma-terials and stainless steel.

• On account of the danger of stress cracking corrosion in the parts made of stainless steel the chloride, nitrate and sulfate con-tents of the heating water must not exceed 50 mg/l in total.

• The pH value of the heating water should lie between 8,3 and 9,5 after 6 - 12 weeks of heating operation.

Filling and replacement water:• For a plant using Hoval boilers untreated

drink ing water is generally best suited as fillingandreplacementwater.However,thequalityoftheuntreateddrinkingwatermustatleastfulfilthestandardsetinVDI2035orbe desalinated and/or be treated with inhibi-tors. The stipulations of EN 14868 must be observed.

• In order to maintain a high level of boiler ef ficiency and to avoid overheating of the heat ing surfaces the values given in the ta ble should not be exceeded (dependent on boil er performance ratings - for multi-boiler plants rating of smallest boiler applies - and on the water content of the plant).

• The total amount of filling and replacement water which is used throughout the total ser-vice life of the boiler must not exceed three times the water capacity of the plant.

• If frost protection agent is being used, please contact the Hoval company to ask for the separate engineering sheet.

Heating installationInstallation room• Gas boilers cannot be positioned in rooms

in which halogen compounds can occur and into which combustion air can enter (e.g. laundrettes, hairdressers).

• Halogen compounds can be caused by clean ing and degreasing solutions, dissol-vents, glue and bleaching lyes. Pay atten-tiontotheProcalleaflet,corrosionthroughHalogen compounds.

Combustion airFor the version with a common exhaust pipe it isimperativethatthefreshairflapsuppliedisin fact installed!

The supply of combustion air must be guaran-teed. There must be no possibility to close the air supply opening.

If the heating rooms are extremely dirty or if there is a high dirt incidence in the combusti-on air (e.g. operation of the boiler during the construction phase), clean combustion air has to be fed directly from outdoors or from a suitable area.

The minimum free cross-section for the com-bustion air can be assumed simplifi ed as fol-lows:Consideringnominaloutput!

- Only room air-dependent operation: Minimum free cross-section of the opening intotheopen:150cm²ortwice75cm²andadditionally2cm²necessaryforeachKWofoutput over 50 KW for vent into the open.

Manual gas shut-off tap and gas filterImmediately in front of the boiler a manual gas shut-off device (tap) must be installed accord-ing to relevant regulations. Should the local re-gu lations or conditions demand this, an appro-ved gas filter must be installed in the gas sup-ply pipe between the gas tap (thermally releas-ing) and the boiler in order to prevent malfunc-tion due to foreign particles being carried along with the gas.

1 total of alkaline earths2 If the conductance in µS/cm exceeds the tabular value an analysis of the water is necessary.

Table 1: Maximum filling capacity based on VDI 2035

Total hardness of the filling water up to ...[mol/m3] 1 <0,1 0,5 1 1,5 2 2,5 3 >3,0f°H <1 5 10 15 20 25 30 >30d°H <0,56 2,8 5,6 8,4 11,2 14,0 16,8 >16,8e°H <0,71 3,6 7,1 10,7 14,2 17,8 21,3 >21,3~mg/l <10 50,0 100,0 150,0 200,0 250,0 300,0 >300Leitwert 2 <20 100,0 200,0 300,0 400,0 500,0 600,0 >600boiler size of the individual boiler maximum filling quantity without desalination

50 to 200 kW NO DEMAND 50 l/kW 20 l/kW 20 l/kW200 to 600 kW 50 l/kW 50 l/kW 20 l/kW always desalinateover 600 kW

Page 15: Hoval UltraGas® Cascades CL/R (140-450)

■ Engineering

Hoval UltraGas® Cascades CL/R (140-450)

Subject to alterations, 1.8.2013 107

Gas connection Commissioning• Start-up is to be carried out only by a spe-

cia list of Hoval and the gas supplier.

• Burner setting values according to the in-stal lation instructions.

Shut off valve• A shut-off valve must be built-in in front of

every gas boiler.

Type of gas• The boiler is only to be operated with the

type of gas stated on the rating plate.

• A gas pressure controller to reduce the boi-ler inlet pressure must be installed on-site for propane.

• Version for Propan Type UltraGas® Cascade CL/R (140-450).

Gas pressure natural gas Necessaryflowpressureattheboilerinlet:For UltraGas® Cascade CL/R (140-450)- min. 18 mbar, max. 50 mbar

Gas pressure propaneNecessaryflowpressureattheboilerinlet:For UltraGas® Cascade CL/R (140-450)- min. 37 mbar, max. 50 mbar

Space requirementsSee „Dimensions’’ for information

Heating boiler in the attic• If the gas boiler is positioned on the top floor,theinstallationofalowwaterprotec-tion, which automatically turns the gas bur-ner off in case of water shortage, is recom-mended.

Condensate drain • The condensate from the exhaust system

can be discharged through the boiler. A con-densate trap is not needed anymore with the exhaust system .

• The condensate drainage without neutralisa-tion is allowed, if you are using for the drain only plastic tubes or stoneware (possibly ob tain special exemption from the relevant authority).

• A siphon must be installed at the condensa-te outlet on the gas boiler (included in the boiler scope of delivery).

Expansion tank• Anadequatelydimensionedexpansiontank

must be provided.

• The expansion tank has to be installed in principle at the boiler return.

• Attheheatingflowasafetyvalvemustbeinstalled. An automatic exhauster is built in the boiler.

Noise level• The acoustic power level value is dependent

on the local and spacial circumstances. • The acoustic pressure level is dependent

on the installation conditions and can for in stance be 5 to 10 dB(A) lower than the acoustic power level at a distance of 1 m.

Recommendation:If the air inlet at the facade is near a noise sen-sitive place (window of bedroom, terrace etc.), we recommend to use a sound absorber at the direct cumbustion air inlet.

Chimney / flue gas system• Gasboilersmustbeconnectedtoafluegassystem(chimneyorfluegaslines).

• Flue gas lines must be gastight and leak-tight against condensate and over pressure andaretobefittedwithasafetytempera-ture li miting device.

• Gas boilers with condensation heat utilisa-tionaretobeconnectedtoafluegaslinemin. Temperature class T120.

• Afluegastemperaturelimiterisbuiltintheboiler.

External boiler control• In principle the Hoval TopTronic®T is intend-

ed to assume the cascade control function. This ensures an environmental and pro-duct- conserving mode of operation. If, in spite of this, the cascade strategy is planned externally and power control of the boiler takesplace,frequentsequencinghastobeavoided (a burner running time of at least 12 minutes).

Page 16: Hoval UltraGas® Cascades CL/R (140-450)

■ Engineering

108 Subject to alterations, 1.8.2013

Hoval UltraGas® Cascades CL/R (140-450)

Extension for cascades of a set of 4 UltraGas® to D250 and cascades of a set of 5 UltraGas® to D300 directly after the last exhaust pipe strin gently necessary.

- In the case of the Hoval cascades 4CL/R and 5CL/R, immediately after the supplied exhaust pipe a widening of the exhaust pipe’s diameter is necessary.

Chimney dimensions (Overpressure)to Hoval UltraGas® Cascade CL/R (140-450)

Principles- Height above sea level max. 1000 m- Introduction to a vertical section 90°

Chimney dimensions (negative pressure)to Hoval UltraGas® Cascade CL/R (140-450)The flue gas system is to be dimensioned in such a way that no back circulation is possible in the room. A safe operation of the fl ue gas system has to be proved by approved measuring principles.

Boiler Flue gas line (smooth walled) Number of bow 90° (flue gas + air supply)

Type Flue gas-Dim. Dimension Totalpipelengthinm(fluegas+airsupply)

UltraGas® Cascade

Hoval UltraGas®

internal DN 1 2 3 4 5 *

2 CL/R (140) (70) 200 200 50 50 50 502 CL/R (180) (90) 200 50 50 50 50

3 CL/R (210) (70) 200 200 50 50 45 403 CL/R (270) (90) 200 16 12 6 –

4 CL/R (280) (70) 200 250 50 50 50 504 CL/R (360) (90) 200 45 40 35 30

5 CL/R (350) (70) 200 250 40 40 40 –

5 CL/R (450) (90) 200 300 40 40 40 –

Notice: Thedatacontainedinthetable«chimneydimensions»representguidevalues. An exact calculation for the flue gas duct must be made on-site.

* With 5 bends or more the residual overpressure of the device is to be reduced by 30% for the calculation. With total pipe lengths exceeding 50 m, a separate calculation is necessary.

Page 17: Hoval UltraGas® Cascades CL/R (140-450)

■ Examples

Hoval UltraGas® Cascades CL/R (140-450)

Subject to alterations, 1.8.2013 109

AF Outdoor sensorVF1 Flow sensor 1VF2 Flow sensor 2VF3 Flow sensor 3SF Calorifier heater sensorB1 Flow temperature guard (ifrequired)SVLF Solar tank sensor

M5.1 Boiler circuit pump 1M5.2 Boiler circuit pump 2M5.3 Boiler circuit pump 3

MK1 Pump mixing circuit 1MK2 Pump mixing circuit 2MK3 Pump mixing circuit 3 Calorifier loading pump

YK1 Actuator mixer 1YK2 Actuator mixer 2YK3 Actuator mixer 3

KW Cold WaterWW Domestic Hot Water

Version

Hydr.1 »Verbindungshinweise /Notice / Nota / Remarque:

.

Datei: UG70-90_Kask.vsd

Datum Name16.07.10Achtung ! Für die Installation muss das anlagenbezogene Schema verwendet werden!UG70-

90_KASK.VSD Attention! This is just a schematic. For installation please use the detail-plan!Attenzione! Per la messa in funzione, utilizzare lo schema dettagliato!Attention! Pour la réalisation pratique de l'installation, il faut utiliser le schéma détaillé!

.

+ Leg._LB020

1 / 3

SVLF

Option / Opzione

SVLF

B1VF1

TT

M K 1

MYK1

B1VF2

TT

M K 2

MYK2

TT

M K 2

MYK2

B1VF2 B1VF3

TT

M K 3

MYK3

B1VF3

TT

M K 3

MYK3

Dies ist ein unerlaubter Weg!Gehen Sie einen Schritt zurück oder löschen Sie dieses Shape!Sie haben die Möglichkeit ein neues Shape zu nehmen!!! hovhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalh

WW

T

KW

S F

S L P

AF

TopTronic T TopTronic T TopTronic T

Dies ist ein unerlaubter Weg!Gehen Sie einen Schritt zurück oder löschen Sie dieses Shape!Sie haben die Möglichkeit ein neues Shape zu nehmen!!! hovhovalhhovalhovaalhovalho

P

UltraGas70, 90

1

M5.1

Dies ist ein unerlaubter Weg!Gehen Sie einen Schritt zurück oder löschen Sie dieses Shape!Sie haben die Möglichkeit ein neues Shape zu nehmen!!! hovhovalhhovalhovaalhovalho

P

UltraGas70, 90

2

M5.2

Dies ist ein unerlaubter Weg!Gehen Sie einen Schritt zurück oder löschen Sie dieses Shape!Sie haben die Möglichkeit ein neues Shape zu nehmen!!! hovhovalhhovalhovaalhovalho

P

UltraGas 70, 903 - 5

M5.3

Hoval UltraGas® Cascades CL/R (140-450)BoilersequentialcontrolbyTopTronic®T

Version

Hydr.2 »Verbindungshinweise /Notice / Nota / Remarque:

.

Datei: UG70-90_Kask.vsd

Datum Name16.07.10Achtung ! Für die Installation muss das anlagenbezogene Schema verwendet werden!UG70-

90_KASK.VSD Attention! This is just a schematic. For installation please use the detail-plan!Attenzione! Per la messa in funzione, utilizzare lo schema dettagliato!Attention! Pour la réalisation pratique de l'installation, il faut utiliser le schéma détaillé!

.

+ Leg._LB020

2 / 3

SVLF

Option / Opzione

SVLF

TopTronic T TopTronic T TopTronic T

Dies ist ein unerlaubter Weg!Gehen Sie einen Schritt zurück oder löschen Sie dieses Shape!Sie haben die Möglichkeit ein neues Shape zu nehmen!!! hovhovalhhovalhovaalhovalho

P

UltraGas70, 90

1

M5.1

Dies ist ein unerlaubter Weg!Gehen Sie einen Schritt zurück oder löschen Sie dieses Shape!Sie haben die Möglichkeit ein neues Shape zu nehmen!!! hovhovalhhovalhovaalhovalho

P

UltraGas70, 90

2

M5.2

Dies ist ein unerlaubter Weg!Gehen Sie einen Schritt zurück oder löschen Sie dieses Shape!Sie haben die Möglichkeit ein neues Shape zu nehmen!!! hovhovalhhovalhovaalhovalho

P

UltraGas 70, 903 - 5

M5.3

0-10VModul

Hoval UltraGas® Cascades CL/R (140-450)BoilersequentialcontrolbyTopTronic®T and 1 x GLT 0-10V -ModuleTemperature control

For further information concerning temperature control see Controls

Notice: - This hydraulic schematic is a principle

schematic. It does not contain all details for installation. The installation must be done according to local conditions, di men-sioning and regulations

- Forunderfloorheating,aflowtemperaturemonitor must be built-in.

- Shut-off devices to the safety valve (pres-surized expansion tank, safety valve, etc.) are to safe against unintended closing!

- Anti thermal siphon dip has to be installed.