How to install PowerChute Network Shutdown 3 0 1 on Network Shutdown 3.0.1 on VMware vMA 5.0
Transcript

How to install PowerChute Network Shutdown 3 0 1 onNetwork Shutdown 3.0.1 on

VMware vMA 5.0

Basic knowledge of Linux commands and Linux administration is needed before user should attempt the installation of the software.

PowerChute Network Shutdown (PCNS) 3.0.1 is required.

PowerChute Network Shutdown requires VMware Infrastructure Management Assistant (vMA) 5.0 install on the VMware ESXi host. if you need help installing vMA please contact VMware support or review KBase document FA159777

The vMA client requires AMD Opteron, Rev E or later CPU or Intel processors with EM64T and VT support

You will need VMware vSphere Client installed on your desktop / laptop to log into the ESXi host system. Review KBase document FA159775 for vSphere Client installation instructions or contact VMware support.

Communications ports TCP 3052, 6547, 80 and UDP port 3052 need to be open on the network.

Note: vMA 5.0 is delivered with the firewall inactive.

Schneider Electric 2- IT Business- SmartWare Tiger Team Leader

To install VMWare vCenter clientTo install VMWare vCenter client review KBase # FA159775 for

instructionsor use the utility PuTTY to log y g

onto the vMA.

To load PCNS from the vSphere client click on the shortcut and the login window will launch.g

Schneider Electric 4- IT Business- SmartWare Tiger Team Leader

View of Infrastructure Client

Schneider Electric 5- IT Business- SmartWare Tiger Team Leader

Next you need to log into the vMA.

To load VMware vMA please review VMware technical support video provide on youtube http://www.youtube.com/watch?v=J4KdUoToCxM or

review KBase # FA159777review KBase # FA159777

Click here to power the vMA on if it is not running

Once the vMA client has been added select it from the list of available

g

Schneider Electric 7- IT Business- SmartWare Tiger Team Leader

virtual systems to load PCNS.

Click on the console tab to log into the vMA then press the enterinto the vMA then press the enter

key to go to the log in screen.

Schneider Electric 8- IT Business- SmartWare Tiger Team Leader

Enter user name and password.

Schneider Electric 9- IT Business- SmartWare Tiger Team Leader

Install PowerChute Network Shutdown 3.0.1 on vMA 5.0

Note: if installing from CD review pages 56 6356 - 63

If the install files were downloaded from APC web site you will need to copy the files to atemporary directory to be uncompressed before the program can be installed See FA159776 fortemporary directory to be uncompressed before the program can be installed. See FA159776 for instruction on how to copy file to the vMA.

Assuming you copied the downloaded files to /opt/temp the commands arecd /opt/temp

d i 301ESXi t

Schneider Electric 11- IT Business- SmartWare Tiger Team Leader

sudo gunzip pcns301ESXi.tar.gzsudo tar –xf pcns301ESXi.tarThere will now be a new directory named ESXi created in /opt/temp

After uncompress the file change directory to /opt/temp/ESXi (caution Linux is case sensitive)Assuming you are still in the /opt/temp directory the commands arecd ESXils –la (to view the contents of the directory)

Schneider Electric 12- IT Business- SmartWare Tiger Team Leader

After running the command ls – la to view the contents of the directory you need change the permissions of the file install_en.sh to make it executable.The command issudo chmod 777 install en sh (en indicates the English version)

Schneider Electric 13- IT Business- SmartWare Tiger Team Leader

sudo chmod 777 install_en.sh (en indicates the English version)

Next run the installerThe command issudo ./install_en.sh

Schneider Electric 14- IT Business- SmartWare Tiger Team Leader

When running the install file view and accept the license and answer the installation questions as they appear on the console.

Schneider Electric 15- IT Business- SmartWare Tiger Team Leader

Select the default installation path or enter a new path.

Schneider Electric 16- IT Business- SmartWare Tiger Team Leader

Select yes to accept the path.

Schneider Electric 17- IT Business- SmartWare Tiger Team Leader

Select yes to use the bundled java (recommended) or enter the path to a preinstalled java version.

Schneider Electric 18- IT Business- SmartWare Tiger Team Leader

Be sure when asked to enter the host server ipaddress, user name, and password. This enables i ti b t th MA li t d th h t

Schneider Electric 19- IT Business- SmartWare Tiger Team Leader

communication between the vMA client and the host server.

Once the installation is complete open web browser to configure PCNS

Schneider Electric 20- IT Business- SmartWare Tiger Team Leader

PCNS Configuration WizardPCNS Configuration Wizard

Configuration WizardConfiguration Wizard

●The first time logging into PCNS the configuration wizard is displa ed a tomaticall This can occ r after a reg lar install or adisplayed automatically. This can occur after a regular install or a silent install which failed to register PCNS with a Network Management Card.

●Post install, the user will be redirected to the PCNS web user interface. If PCNS has not previously been configured, the user will be automatically logged in and directed to configure PCNS to ensure server protection. Once the first time wizard completes, the session ends and the user will be redirected to the login screen.

● If PCNS has been configured by this wizard or by a successful registration during a silent install, a visitor to the PCNS web user interface will be welcomed by the log in screen.

Schneider Electric 22- IT Business- SmartWare Tiger Team Leader

interface will be welcomed by the log in screen.

Click I understand the

risk.

Since we use SSL and the browser does not know site a connection warning will appear

Schneider Electric 23- IT Business- SmartWare Tiger Team Leader

Since we use SSL and the browser does not know site a connection warning will appear. You will need to accept the SSL certificate that is generated by PCNS.

Click Add Exception

Schneider Electric 24- IT Business- SmartWare Tiger Team Leader

Click Confirm Security

Exception

After accepting the security exception the customer will be directed to the PCNS

Schneider Electric 25- IT Business- SmartWare Tiger Team Leader

After accepting the security exception the customer will be directed to the PCNSConfiguration wizard .

This is the opening window for the configuration Wizard. The wizard can be accessed at anytime via the web interface and is the ysame for all supported OS!

Click next

Schneider Electric 26- IT Business- SmartWare Tiger Team Leader

Click next

Enter the User Name and Password along with the Authentication Phrase

Schneider Electric 27- IT Business- SmartWare Tiger Team Leader

gThe User Name and Authentication Phrase must match the one entered on the NMC

If the serverIf the server has multiple

NICs you must chose the IP Address that

will be registered with

the NMC

Schneider Electric 28- IT Business- SmartWare Tiger Team Leader

the NMC

After choosing the IP Address

that will be registered withregistered with the NMC click

next

Schneider Electric 29- IT Business- SmartWare Tiger Team Leader

Schneider Electric 30- IT Business- SmartWare Tiger Team Leader

Select if the configuration is Single, Redundant, or Parallel UPS then click next.

Single-UPS Configuration

In a Single UPS configuration h t f iIn a Single-UPS configuration, each computer server or group of servers is protected by a single UPS. That is, each server has one PCNS agent communicating with a single NMC installed on a UPS.

Supported UPS devices: The entire Smart-UPS range of UPS devices, including Smart-UPS VT and MGE Galaxy 3500 1- and 3-phase, Galaxy 7000, Galaxy 300; the Symmetra 1-Phase and 3-Phase, the Symmetra PX, and the Sil DP3500E d SilSilcon DP3500E and Silcon.

Schneider Electric 31- IT Business- SmartWare Tiger Team Leader

Single-UPS Configuration

Schneider Electric 32- IT Business- SmartWare Tiger Team Leader

Redundant Configuration

In a Redundant-UPS Configuration, PowerChute Network Shutdown recognizes a group of either two or three UPS’s as a single UPS. In this configuration, one PowerChute Network Shutdown Agent on a server communicates with two or three NMCs (depending on the number of UPS’s in the configuration). Typically, the servers have multiple (dual or triple) power cords. Each UPS has its own NMC, which has a unique IP address. In addition all the NMCs use the same HTTP port and the same administratoraddition, all the NMCs use the same HTTP port and the same administrator user name, password, and authentication phrase.

Each UPS has the capacity to supply power to the load on its own. The first UPS id ll h f h l d h ddi i l UPS( )UPS provides all the power for the load, the additional UPS(s) act as reserve. When the first UPS in unable to supply power, the server switches over to take power from the next UPS. As a result, if one of the UPS’s goes down, for whatever reason, the other UPS(s) can continue to supply power to the loadwhatever reason, the other UPS(s) can continue to supply power to the load and therefore provide redundancy between UPS’s. PowerChute Network Shutdown recognizes that the UPS’s are set-up in a Redundant-UPS configuration and listens to all the UPS NMCs for a shutdown command.

Schneider Electric 33- IT Business- SmartWare Tiger Team Leader

Redundant Configuration

Schneider Electric 34- IT Business- SmartWare Tiger Team Leader

See the updated Applications Note #98 for more information

Redundant Configuration

Schneider Electric 35- IT Business- SmartWare Tiger Team Leader

Parallel Configurations

In a Parallel-UPS Configuration, two or more UPS’s (up to nine dependingIn a Parallel UPS Configuration, two or more UPS s (up to nine depending on the model) support the load. Each UPS does not need to be capable of supporting the load on its own as the combined output of all UPS’s in the configuration share the load. However, depending on the size of the load there

b UPS( ) il bl R d d i id d if th i t l tmay be reserve UPS(s) available. Redundancy is provided if there is at least one more UPS than is required to support the load.

See the updated Applications Note #169 for more information

Schneider Electric 36- IT Business- SmartWare Tiger Team Leader

Parallel Configurations

Schneider Electric 37- IT Business- SmartWare Tiger Team Leader

Parallel Configurations

Schneider Electric 38- IT Business- SmartWare Tiger Team Leader

Enter protocol, NMC communication

port and NMC ipport, and NMC ip address then click

next

Schneider Electric 39- IT Business- SmartWare Tiger Team Leader

Select whether to check for updates,whether to shutdownshutdownthe UPS then click next

Schneider Electric 40- IT Business- SmartWare Tiger Team Leader

Click apply after verifying the information is correctcorrect.

Schneider Electric 41- IT Business- SmartWare Tiger Team Leader

PCNS will register with the NMC

Schneider Electric 42- IT Business- SmartWare Tiger Team Leader

If the UPS has the proper firmware

and supports ppoutlet groups you

can select the outlet group the

server is pluggedserver is plugged into.

Schneider Electric 43- IT Business- SmartWare Tiger Team Leader

For this example we selected outletselected outlet group 1 then clicked apply.

Schneider Electric 44- IT Business- SmartWare Tiger Team Leader

Once registered Click next

Schneider Electric 45- IT Business- SmartWare Tiger Team Leader

Click Finish

Schneider Electric 46- IT Business- SmartWare Tiger Team Leader

PowerChute Network Shutdown web interface

After the configuration is complete you will be logged into the PCNS clientThis is the opening page for PCNS client on all supported OS.

Schneider Electric 48- IT Business- SmartWare Tiger Team Leader

This is the configure events page for all PCNS clients

Schneider Electric 49- IT Business- SmartWare Tiger Team Leader

This is the configure events page for all PCNS clients

To see a full list of configurable and non-configurable event view PCNS help

If the UPS has the proper firmware

and supportsand supports outlet groups you

can select the outlet group g pshutdown behavior.

Schneider Electric 50- IT Business- SmartWare Tiger Team Leader

This is the configure shutdown page for all PCNS clients

If the UPS has the proper firmware

and supports outlet groups you

can select the outlet group theoutlet group the PCNS client is

attached to.

Schneider Electric 51- IT Business- SmartWare Tiger Team Leader

This is the Set Up Communications page for all PCNS clients

Schneider Electric 52- IT Business- SmartWare Tiger Team Leader

This is the check for Updates page for all PCNS clients

How to add host servers to theHow to add host servers to the server list

If you would like to add additional host server to the server list (this will allow for the shutdown of multiple host by a single vMA) first check to be sure the server is not already in the list by running the command vifp listserversIf the server is not in the list add the server to the list by running the commandsudo vifp addserver 10.218.45.20 Verif the ser er has been added

Schneider Electric 54- IT Business- SmartWare Tiger Team Leader

Verify the server has been addedvifp listservers

NOTE: The address of the host running the vMA should always be last in the list.

Next you need to add the server to the fasspass list the command is vifptarget –s <server name or ipaddress> NOTE: there is a known issue with this command on vMA 5.1.xTo verify there is communications between the client and the host run the command Vicfg-nics –l (lower

Schneider Electric 55- IT Business- SmartWare Tiger Team Leader

To verify there is communications between the client and the host run the command Vicfg nics l (lower case letter l) should display a list of the host NICs.

Install PCNS 3.0.1 onto vMA 5.0 from CD

If loading PCNS from CD verify that the CD drive is y

connected on the client and the CD is loaded into the host system CD drive. If installer

was downloaded from

Schneider Electric 57- IT Business- SmartWare Tiger Team Leader

was downloaded from APC.com go to page 11

Note to make any changes to the hardware profile the vMA pwill need to be powered down

Schneider Electric 58- IT Business- SmartWare Tiger Team Leader

Click on the console tab to log into the vMA then press the enterinto the vMA then press the enter

key to go to the log in screen.

Schneider Electric 59- IT Business- SmartWare Tiger Team Leader

Once logged in if one has not O ce ogged o e as otbeen created, create a mount

point for the CD. sudo mkdir /mnt/cdrom

Schneider Electric 60- IT Business- SmartWare Tiger Team Leader

Change the permissions on the new mount pointp

sudo chmod 666 /mnt/cdrom

Schneider Electric 61- IT Business- SmartWare Tiger Team Leader

Mount the APC CD and change directory to view the files in the ESXi directory.

Commands

Schneider Electric 62- IT Business- SmartWare Tiger Team Leader

sudo mount –t iso9660 /dev/cdrom /mnt/cdromcd /mnt/cdrom/ls to list the contents of the CD

For this example the CD contains a parent directory of PCNS 3 0 1For this example the CD contains a parent directory of PCNS 3.0.1and child directory of ESXiChange directory to ESXi and copy the contents to /opt/tempChange directory to /opt/temp

Schneider Electric 63- IT Business- SmartWare Tiger Team Leader

Continue with instruction on page 13

Thank YouThank You