HyQuest Solutions New Zealand User Group August 2017
HS Bubbler Technology
Origins of Gas Purge Technology
1940s - Developed By Dutch Engineer Late 1940s
1954 - Adopted by State of Illinois Water Group
1950s - Adopted by United States Geological Survey (USGS)
1960s - Developed by Des Sherlock (Hydrological Services)
Gas Purge Operating Principle
Basic Operating Principle
dry nitrogen (or air) bubbled into the stream via a small diameter tube
bubbles escape from the end of the tube (orifice)
pressure transducer monitors changes in pressure within the tubing
available as single or dual orifice/riverline options
System pressure is proportional to water level
Typical installation of a Gas Purge system
-Nitrogen Gas Bottle
-HS23SL
-Standard BU07 Orifice
Evolution of Technology
5
Circa 1950s Developed as an alternate technology to traditional float operated systems
Gas Electric Manometer (Queensland Government)
Manometer Servo(Leopold & Stevens USA)
Hydrological Services (HS) Pressure Sensing Unit (DP30)
Des Sherlock (1965-68)
Typical Set-Up
6
How does a dry bubble unit work?
Gas feed should always be at a pressure twice the maximum river level likely to be recorded
Nupro Valve used to regulate the number of bubbles at the orifice
Balance line used to control the pressure coming to the valve to keep the system balanced
Instrument line where a dry pressure transducer is used
River Line extends all the way to the orifice.
Supply Line (Feed)
Nupro ValveBalance Line
River Line
Instrument Line
Pressure through this valve is always 27Kpa (4 PSI) greater than the pressure at the river
orifice (+ve pressure)
How does a dry bubble unit work?Pressure will increase to open the valve more when water level increases and decrease to reducing the valve opening when water decrease
Constant regulator to maintain a constant bubble rate with changes of water level
Nupro metering valve for accurately setting
bubble rate
Pressure at this point is always 27 kPa (4 PSI)
The Compressor Age
Alternative to gas cylinders (Safety Issues)
Effective air drying system essential - moisture ingress- aquatic growth
Some limitations riverline length- maximum head
Low powered types available (12V: 38aH with solar)
Original HS Compressors (circa late 1990s)
Model HS45(Required HS23 Bubble Unit)
Model HS55(In-Built HS23 Bubble Unit)
Typical installation HS55 Compressor?
Why use the GCO?
Minimises impact of sediment on water level sensing
Minimises time of lag for fast rising water levels
Allows for lower bubble rates (as low as 10 bpm) reducing gas and power consumption
Removeable copper screen to eliminate algal growth
Adjustable coupling for easy retrofit to existing sites
Why use the GCO?
HS40 Air Force Compressor Models
HS40 Air ForceSeries II
(Available with WL3100 or WL3100A or Stand-Alone)
HS40 Air ForceCompact
(Available with WL2100 or WL3100 or WL3100A or Stand-Alone)
HS40 Air ForceSeries I
(Available with WL3100 or WL3100A or Stand-Alone:
V type also developed)
HS40 Air Force Models General FeaturesFeature HS40 Air Force
Series IHS40 Air Force
Series IIHS40 Air Force
Compact
Operation Constant Bubble Constant Bubble Constant Bubble
Enclosure Zinc plated powder-coated metal Zinc plated powder-coated metal Zinc plated powder-coated metal
Dimensions 330mm (W) x 430mm (H) x 200mm (D) 405mm (W) x 620mm (H) x 220mm (D) 330mm (W) x 490mm (H) x 210mm (D)
Mass 16kg 24kg 22kg
Maximum Head 40 metres (200 metre river-line) 50 metres (200 metres river-line) 50 metres (200 metres river-line)
Orifice Suits either BU07 or GCO1P/SS Suits either BU07 or GCO1P/SS Suits either BU07 or GCO1P/SS
Power Supply 12VDC 12VDC 12VDC
Models HS40 / HS403100 / HS403100 / HS40/3100 (with DO Option)
HS40/II / HS40/3100II / HS40/3100A/II / HS40/3100/DO/II
HS40AFC / HS40AFC/2100 / HS40AFC/3100 / HS40AFC/3100A
Tank size 2.0L 2.0L 0.75L
Compressor Pump Thomas Pump Industrial strength ABB pump Industrial strength ABB pump
Air Dryer Auto DRAIN with nylon bulbs(V option also introduced in 2013)
Auto PURGE air dryer with micro-mist separator and membrane dryer
Auto DRAIN with micro-mist separator and membrane dryer
(Auto PURGE air dryer available in V model of the AFC)
Bubble Rate 26 BPM at orifice (Factory Set) 26 BPM at orifice (Factory Set) 26 BPM at orifice (Factory Set)
HS40 Air Force Models Continuous ImprovementCirca 2009 : HS45/HS55 to HS40 Series I - Industry demand for a smaller and less expensive product- Inclusion of on-board accurate pressure sensor (WL3100 & WL3100A)
Circa 2015 : HS40 Series I to HS40 Series II
- Alternate method of air drying
- More robust pump
- Short-comings of electronics (re-introduction of the Condor mechanical pressure switch used in HS55)
- Redundancy (unit will continue to function in the event of a controller failure)
- SDI-12 Diagnostics for Fault Finding:Compressor status / Duration of & Time since last pump cycle / Number of pump cycles in the last 24hrs / Minimum battery voltage & Maximum current draw
Circa 2017 : HS40 Series II to HS40 COMPACT - Industry demand for a smaller/lighter and less expensive product
- Options for inclusion of on-board accurate pressure sensor (WL2100, WL3100 & WL3100A)
- Air Dryer options (auto-drain) OR (auto-purge)
HS40 Air Force Compressors - How do They Work?
Tank
Controller
Pump
Membrane Dryer
Pressure Transducer
Condor Switch
Air Intake
Bubble Rate Adjust
Tank Pressure Gauge When tank pressure drops to 400kPa, Controller activates pump
Differential Regulator When tank pressure reaches 750kPa, Controller de-activates pump
Differential Regulator ensure a constant flow of dried air to orifice
Ambient air enters pump and put through Micromist Separator and Membrane Dryer prior to entering tank
Changes in stream water level reflected in changed pressure reading in river line
Pressure transducer converts pressure reading to a reading in metres 12VDC Supply
Micromist Separator
Solenoid Valve
Trapped Moisture Purged via Solenoid Valve
Purge Valve
Transducer Isolation Valve
ADVANTAGES:Desiccant Free means minimal maintenance
Constant Bubble ensures stability in water level reading
Moisture DRIED Air is ESSENTIAL!!!!
19
HS40 Fault Finding Pressure (ALL MODELS)
Pressure Transducer Connected?
?
Internal Connections
OK?
Bubble Rate OK
(26BPM)?
Valve Seats OK?
NO
NO
NO
NO
YES
YES
YES
Connect Transducer
Dismantle and Clean Valve
Use HS23QC tester / tighten or replace Check and/or
Replace Ferrules
Adjust to 26BPM
SYSTEM LEAK ISSUE
(Visual Inspection/Check Data) Trace
Compressor Working
OK
SYSTEM BLOCKAGE ISSUE
(Visual Inspection/Check Data)
Are both Valves Set at OPEN?
posit?
Is Orifice Clear and Bubbling?
Is River-Line Damaged?
Set both to OPEN position
Clean in and around orifice area. Manual
Purge then Check and reset bubble rate to (26BPM)
if required
Repair/replace tubing as required
YES
YES
NO
NO
YES
NO
YES
SYSTEM BLOCKAGE ISSUE
(Visual Inspection/Check Data)
SYSTEM LEAK ISSUE
(Visual Inspection/Check Data) Trace
Use HS23QC tester / tighten or replace Check and/or Replace Ferrules
NO
Dismantle and Clean Valve
NO
YES
YES
Adjust to 26BPM
NO
Bubble Rate OK (26BPM)?
YES
Internal Connections OK?
YES
Valve Seats OK?
NO
Pressure Transducer Connected??
Is River-Line Damaged?
Clean in and around orifice area. Manual Purge then Check and reset bubble rate to (26BPM) if required (26BPM)
NO
YES
Repair/replace tubing as required
Is Orifice Clear and Bubbling?
YES
Are both Valves Set at OPEN? posit?
Connect Transducer
Set both to OPEN position
NO
NO
YES
Compressor Working
OK
20
HS40 Fault Finding Electronic (Series I Model)
NO
NO
YES
NO
Duty Cycle Exceeded
(wait 30 mins. Until LED is GREEN then retry)
COMPRESSOR FAILS TO POWER UP
LED Flashing GREEN
Compressor Working
OK
COMPRESSOR FAILS TO START
(when BLUE button is pressed OR tank pressure
21
HS40 Fault Finding Electronic (Series II Model)
NO
NO
YES
NO
i) Check Condor Switch setting is at 1
ii)Ensure control valve is NOT set to PURGE
iii)Check ALL pressure fittings and power to solenoid valve
COMPRESSOR FAILS TO POWER UP
LED Flashing GREEN Compressor Working
(Use SDI-12 Diagnostics Feature if Required)
OK
COMPRESSOR FAILS TO START
(when tank pressure 12.5VDC
If Fast Flash then battery voltage is too high, >16VDC
YES YES
NO
Ensure Battery Voltage is =/>12VDC
Condor Switch must be set to 1
Check POWER/GROUND
Connections
Is LED Flashing
RED?
Is LED Flashing
BLUE (fast)?
Is LED Flashing WHITE?
Compressor duty cycle exceeded. Wait 10 mins until the LED flashes
GREEN
(it will automatically try to pump)
If LED GREEN Controller may be faulty
(remove from battery then re-connect to re-boot)
Compressor stops at 12.5VDC
If Fast Flash then battery voltage is too high, >16VDC
Is LED Flashing RED?
YES
Ensure Battery Voltage is =/>12VDC
Condor Switch must be set to 1
Check POWER/GROUND Connections
If LED GREEN Controller may be faulty
(remove from battery then re-connect to re-boot)
If LED RED or BLUE or WHITE follow steps above
NO
YES
NO
Compressor stops at
22
Fault Finding Real Examples
Problem: Water Level logged reading randomly dropping out to zero metres
Likely Cause: Communication problem (SDI-12) between logger and pressure sensor causes a Nan (Not A Number) value to be logged
Fix: Edited out via Time Series software
23
Fault Finding Real Examples
Problem: Water Level logged gradually increases then decreases on a random basis
Likely Cause: Possible Leakage in system
Fix: Check all fittings and valves for leakage
24
Fault Finding Real Examples
The Problem
Sensed Water Level reading randomly jumping to an un-realistic value (11002 in the case)
Likely Cause a voltage drop causes the WL3100 to output an Out of Range value (e.g. 999.999)
Fix: Usually rectified by checking and re-setting SDI-12 addresses
25
Fault Finding Real Examples
The Problem
Logged Data from WL3100 sensor is spikey?
Likely Cause WL3100 set at Continuous
Fix: Adjust from Continuous to Averaging (i.e. when set to Contin+Avg20 every 12 seconds, previous 20 level samples are averaged)Use Averaging Feature with caution where stream is flashy!!!!!!!
26
Fault Finding Real ExamplesThe Problem (s)i) Hunting over approx. 5mm range at start and end of traceii) Sudden drops up to approx. 40mm then rises cycling with large upwards spike present
Likely Cause (s): i) & ii) Sediment effect on orifice
Fix: More regular clearing of orifice, or re-location? Consider GCO1P/SS??
27
Fault Finding Real ExamplesThe Problem (s)Hunting over approx. 50mm range following a major flood the previous week
Likely Cause: Blockage in river line or sediment effect on orifice
Fix: Converted from dual to single line, upgraded to GCO1P/SS
28
Fault Finding Real ExamplesThe Problem (s)I) Although orifice (GCO) clear of sediment, steady rise even after purgingII) Drop-outs of water level
Likely Cause: i) Blockage in river line or sediment effect on orificeii) SDI-12 timingFix:i) Investigate blockage (try temporary orifice from HS40?)
ii) Edit spike using time series software
HS Bubbler TechnologyOrigins of Gas Purge TechnologyGas Purge Operating PrincipleTypical installation of a Gas Purge systemEvolution of TechnologyTypical Set-UpHow does a dry bubble unit work?How does a dry bubble unit work?The Compressor AgeOriginal HS Compressors (circa late 1990s)Typical installation HS55 Compressor?Why use the GCO?Why use the GCO?HS40 Air Force Compressor ModelsHS40 Air Force Models General FeaturesHS40 Air Force Models Continuous ImprovementHS40 Air Force Compressors - How do They Work?Slide Number 18Slide Number 19Slide Number 20Slide Number 21Slide Number 22Slide Number 23Slide Number 24Slide Number 25Slide Number 26Slide Number 27Slide Number 28Slide Number 29