HSC 120: Room humidistat How energy efficiency is improved Enables humidity control devices to be switched on according to needs Features Monitoring and regulation of relative air humidity in rooms by controlling fans, drying units and air humidifiers Variable relative humidity as setpoint based on printed scale in % rh Measurement taken via a measuring element of stabilised synthetic textile tape. Controller with fixed switching difference of X sd Technical data Power supply Max. load 5(3) A, 250 V~ Min. load 100 mA, 24 V=/~ Parameters Setting range 30...90% rh Setting accuracy 1) ±5% rh Humidity calibration at 55% rh, 23 °C Switching difference Typ. 6% rh Long-term stability Approx. -1.5% rh/a Time constant in moving air (0.2 m/s) Approx. 5 minutes Temperature effect 0.5% rh/K Ambient conditions Operation Admissible ambient humidity 30...90% rh non-condensing Temperature 0...50 °C Storage and transport Admissible ambient humidity 10...95% rh non-condensing Temperature -25...70 °C without condensation Construction Dimensions W x H x D 76 × 76 × 34 mm Weight 0.09 kg Housing Pure white (RAL 9010) Housing material Fire-retardant thermoplastic, UL94V-0 Screw terminals For electrical wires of up to 1.5 mm² Standards and directives Type of protection 2) IP 30 (EN 60730-1), operating status Protection class II (IEC 60730) Environment class 3K3 (IEC 60721-3-3) CE conformity according to EMC Directive 2014/30/EU EN 60730 Low-Voltage Directive 2014/35/EU EN 60730-1, EN 60730-2-13 Overview of types Type Features HSC120F001 Setting via external setpoint adjuster HSC120F010 Internal setpoint adjuster Accessories Type Description 0362225001 Intermediate plate, pure white, for wall mounting on recessed junction box 1) The setting accuracy of the humidistat is valid for the calibration point ±5% rh at 55% rh and 23 °C following initial calibration at the factory. See diagram “Setting accuracy”. In general, humidity sensors (humidistats) are subject to increased ageing if they are used and/or stored in very contaminated air or aggressive gases. The humidistat may start to drift and its linearity may change under these conditions. If the humidistats are used in very contaminated air, the warranty does not cover a premature re-calibration or the replacement of the com- plete humidistat 2) Operating status: device mounted and closed Product data sheet 10.1 24.012 Right of amendment reserved © 2020 Fr. Sauter AG 1/3 HSC120F001 HSC120F010 2 3 1 X Sd X s H% B01572 relative humidity at 23 °C
Transcript
Page 1: HSC 120: Room humidistat · HSC 120: Room humidistat How energy efficiency is improved Enables humidity control devices to be switched on according to needs Features • Monitoring

HSC 120: Room humidistat

How energy efficiency is improvedEnables humidity control devices to be switched on according to needs

Features• Monitoring and regulation of relative air humidity in rooms by controlling fans, drying units and air

humidifiers• Variable relative humidity as setpoint based on printed scale in % rh• Measurement taken via a measuring element of stabilised synthetic textile tape.• Controller with fixed switching difference of Xsd

Technical data

Power supplyMax. load 5(3) A, 250 V~Min. load 100 mA, 24 V=/~

ParametersSetting range 30...90% rhSetting accuracy1) ±5% rhHumidity calibration at 55% rh, 23 °CSwitching difference Typ. 6% rhLong-term stability Approx. -1.5% rh/aTime constant in moving air (0.2 m/s) Approx. 5 minutesTemperature effect 0.5% rh/K

Ambient conditionsOperation Admissible ambient humidity 30...90% rh non-condensing

Temperature 0...50 °CStorage and transport Admissible ambient humidity 10...95% rh non-condensing

Temperature -25...70 °C without condensation

ConstructionDimensions W x H x D 76 × 76 × 34 mmWeight 0.09 kgHousing Pure white (RAL 9010)Housing material Fire-retardant thermoplastic, UL94V-0Screw terminals For electrical wires of up to 1.5 mm²

Standards and directivesType of protection2) IP 30 (EN 60730-1), operating statusProtection class II (IEC 60730)Environment class 3K3 (IEC 60721-3-3)

CE conformity according to EMC Directive 2014/30/EU EN 60730Low-Voltage Directive 2014/35/EU EN 60730-1, EN 60730-2-13

Overview of typesType Features

HSC120F001 Setting via external setpoint adjuster

HSC120F010 Internal setpoint adjuster

AccessoriesType Description

0362225001 Intermediate plate, pure white, for wall mounting on recessed junction box

1) The setting accuracy of the humidistat is valid for the calibration point ±5% rh at 55% rh and 23 °C followinginitial calibration at the factory. See diagram “Setting accuracy”. In general, humidity sensors (humidistats) aresubject to increased ageing if they are used and/or stored in very contaminated air or aggressive gases. Thehumidistat may start to drift and its linearity may change under these conditions. If the humidistats are used invery contaminated air, the warranty does not cover a premature re-calibration or the replacement of the com-plete humidistat

2) Operating status: device mounted and closed

Product data sheet 10.1 24.012

Right of amendment reserved © 2020 Fr. Sauter AG 1/3

HSC120F001

HSC120F010

23

1

XS

d

Xs

H%

B01572

relative humidityat 23 °C

Page 2: HSC 120: Room humidistat · HSC 120: Room humidistat How energy efficiency is improved Enables humidity control devices to be switched on according to needs Features • Monitoring

Additional information

Fitting instructionsHSC120F001 P100013519HSC120F010 P100013250

Description of operationWhen the relative air humidity is increasing, contacts 1-2 are opened and 1-3 closed after the upperchange-over point has been reached. Setpoint XS corresponds to the upper change-over point. Thecontacts are reset when the humidity value falls again below the upper change-over point by theamount of the fixed switching difference Xsd.The normal ageing process of the measuring element causes the change-over point to gradually andpermanently shift. Recalibration may, therefore, be necessary.At temperatures other than the compensation temperature, the change-over point is shifted systemat-ically (effect of temperature). Similarly, if the humidity changes quickly, the change-over point is shif-ted temporarily.

Intended useThis product is only suitable for the purpose intended by the manufacturer, as described in the “De-scription of operation” section.All related product regulations must also be adhered to. Changing or converting the product is not ad-missible.

Improper useHSC 120 is not suitable for safety applications.The product must not be used outdoors or in rooms where there is a risk of condensation. Condensa-tion can have a negative effect on the measuring accuracy.

Engineering and fitting notes

)NoteOnly qualified electricians are permitted to fit, connect, and dismantle the product.> Disconnect from mains before opening.> Once open, prevent access of non-professionals.> Take damaged devices out of operation immediately.

The housing base allows cables to be inserted from behind so that the unit can be fitted on recessedjunction boxes. With surface-mounting, openings can be made above or below as required.

DisposalWhen disposing of the product, observe the currently applicable local laws.More information on materials can be found in the Declaration on materials and the environment forthis product.

Connection diagram

A03377

H%

1 2 3

Product data sheet 10.1 24.012

2/3 Right of amendment reserved © 2020 Fr. Sauter AG

Page 3: HSC 120: Room humidistat · HSC 120: Room humidistat How energy efficiency is improved Enables humidity control devices to be switched on according to needs Features • Monitoring

Dimension drawing

HSC120F001 HSC120F010

34

76

75 60

4

4,2

60

75

ø4

ø4,

2

76 34

Accessories0362225001

60

60

M05364

85

77

10

5

Product data sheet 10.1 24.012

Right of amendment reserved © 2020 Fr. Sauter AG 3/3