Export limitation configuration on Smartlogger1000/2000 Public 2018-10-22 [email protected] Page1, Total13 Export limitation configuration on Smartlogger1000/2000 Huawei Technologies Co. Ltd. Version Created by Date Remarks 01 E84081311 17.10.2018 Smartlogger1000/2000 The information in this document may contain predictive statements including, without limitation, statements regarding the future financial and operating results, future product portfolio, new technology, etc. There are a number of factors that could cause actual results and developments to differ materially from those expressed or implied in the predictive statements. Therefore, such information is provided for reference purpose only and constitutes neither an offer nor an acceptance. Huawei may change the information at any time without notice.
Transcript
Page 1: Huawei Technologies Co. Ltd. Export limitation configuration...Export limitation configuration on Smartlogger1000/2000 Public 2018-10-22 eu_inverter_support@huawei.com Page12, Total13

Export limitation configuration on Smartlogger1000/2000 Public

2018-10-22 [email protected]

Page1, Total13

Export limitation configuration on

Smartlogger1000/2000

Huawei Technologies Co. Ltd.

Version Created by Date Remarks 01 E84081311 17.10.2018 Smartlogger1000/2000

The information in this document may contain predictive statements including, without limitation, statements regarding the future financial and operating results, future product portfolio, new technology, etc. There are a number of factors that could cause actual results and developments to differ materially from those expressed or implied in the predictive statements. Therefore, such information is provided for reference purpose only and constitutes neither an offer nor an acceptance. Huawei may change the information at any time without notice.

Page 2: Huawei Technologies Co. Ltd. Export limitation configuration...Export limitation configuration on Smartlogger1000/2000 Public 2018-10-22 eu_inverter_support@huawei.com Page12, Total13

Export limitation configuration on Smartlogger1000/2000 Public

2018-10-22 [email protected]

Page2, Total13

This manual describes the operation and maintenance instructions of the export limitation function. The function is available for the next firmware version of Smartlogger1000/2000: -Smartlogger1000: V100R001C00SPC115 or later version -Smartlogger2000: V200R002C20SPC115 or later version We recommend to use for this function the next type of power meters: UMG604, PD510, PZ96L, UPM209, or COUNTIS E43 1. System Network Diagram Without the DO control circuit breaker:

With the DO control circuit breaker:

2. Procedure 2.1 Connect the devices 2.1.1 Connect the inverters Write in a browser the link https://192.168.0.10 (default password “Changeme”) and login as Advanced UserMaintenanceConnect DeviceAuto assign addressSet start address to 1Auto assign address

Page 3: Huawei Technologies Co. Ltd. Export limitation configuration...Export limitation configuration on Smartlogger1000/2000 Public 2018-10-22 eu_inverter_support@huawei.com Page12, Total13

Export limitation configuration on Smartlogger1000/2000 Public

2018-10-22 [email protected]

Page3, Total13

After select auto assign address follow the below steps: confirm start allocate addressconfirm address need adjustmentaddress adjustmentconfirm

Page 4: Huawei Technologies Co. Ltd. Export limitation configuration...Export limitation configuration on Smartlogger1000/2000 Public 2018-10-22 eu_inverter_support@huawei.com Page12, Total13

Export limitation configuration on Smartlogger1000/2000 Public

2018-10-22 [email protected]

Page4, Total13

Search result:

2.1.2 Connect the power meter Connect the power meter in one of the RS485 port of the Smartlogger1000/2000. The power meter does not support automatic search and needs to be added manually like below: As Advanced User from Maintenance menu chose Connect DeviceAdd deviceChoose Device Type Power MeterComm. Protocol Modbus-RTUset the Port number accordingly and the RS485 communication address of the Power Meter

Page 5: Huawei Technologies Co. Ltd. Export limitation configuration...Export limitation configuration on Smartlogger1000/2000 Public 2018-10-22 eu_inverter_support@huawei.com Page12, Total13

Export limitation configuration on Smartlogger1000/2000 Public

2018-10-22 [email protected]

Page5, Total13

Set the RS485 communication parameters in Smartlogger1000/2000: As Advanced User choose Settings menuset the communication parameters for the port that you connect the Power Meter: protocol, baud rate, parity and stop bit

RS485-1 to RS485-3 correspond to the communications ports COM1 to COM3, and the default baud rate is 9600 bps. For the power meter connected to the corresponding RS485 port, the values of Protocol, Baud rate, Parity, and Stop bit must be the same as those on the web page. Setting Power Meter Parameters Login as Advanced User. Choose SettingsPower Meterselect the Power Meter modelSubmit

If the connected power meter model is UMG604, PD510, PZ96L, UPM209, or COUNTIS E43, select the corresponding model in the Intelligent Power Meter Type drop-down list box. When the UPM209 or COUNTIS E43 power meter is connected to the SmartLogger1000/2000, a 120-ohm resistor needs to be connected to the RS485 bus of the meter. For details, see the user manual of the power meter.

Page 6: Huawei Technologies Co. Ltd. Export limitation configuration...Export limitation configuration on Smartlogger1000/2000 Public 2018-10-22 eu_inverter_support@huawei.com Page12, Total13

Export limitation configuration on Smartlogger1000/2000 Public

2018-10-22 [email protected]

Page6, Total13

If your Power Meter type is not in the list choose in the tab Intelligent Power Meter Type “Other” And set the signal address, number of registers and gain manually, see the user manual of the power meter.

Check the Power Meter status: As advanced user from Monitoring menu select the Meter and check the status:

If the power meter show the status disconnected you need to check the physical connection and the communication parameters. The status of the power meter should be green and connected.

Page 7: Huawei Technologies Co. Ltd. Export limitation configuration...Export limitation configuration on Smartlogger1000/2000 Public 2018-10-22 eu_inverter_support@huawei.com Page12, Total13

Export limitation configuration on Smartlogger1000/2000 Public

2018-10-22 [email protected]

Page7, Total13

2.2 Configuring Automatic Shutdown in Case of Inverter Communication Interruption Login as Advanced User. Choose Monitoringselect the inverterRunning Param.-->Feature Parameters Set Communication interrupt shutdown and Communication resumed startup to Enableselect Batch configuration if you have connected more than one inverter

Set the communication interruption duration as required. Batch configuration can be used for multiple inverters. 2.3 Configuring the Active Power Change Gradient Login as Special User. Choose Monitoring select one inverterRunning Param. Power Adjustmentset the active power change gradientSubmit or Batch configuration if you have installed more than one inverter. If the maximum value of Active power change gradient is 50, set the parameter to the maximum value. If the maximum value of Active power change gradient is 1000, set the parameter to 125

Page 8: Huawei Technologies Co. Ltd. Export limitation configuration...Export limitation configuration on Smartlogger1000/2000 Public 2018-10-22 eu_inverter_support@huawei.com Page12, Total13

Export limitation configuration on Smartlogger1000/2000 Public

2018-10-22 [email protected]

Page8, Total13

Page 9: Huawei Technologies Co. Ltd. Export limitation configuration...Export limitation configuration on Smartlogger1000/2000 Public 2018-10-22 eu_inverter_support@huawei.com Page12, Total13

Export limitation configuration on Smartlogger1000/2000 Public

2018-10-22 [email protected]

Page9, Total13

2.4 Disable active power control Log in as Special User. Choose SettingsActive Power Control and set Active power control to DisableSubmit

2.5 Configuring Export Limitation Parameters Log in as Special User. Choose Settings > Export LimitationEnable the function Export Limitationselect at Power Meter tab Smart meterset the requested settingsSubmit If DO switch-on/off operations are not involved, ignore the switch-on/off configurations.

Page 10: Huawei Technologies Co. Ltd. Export limitation configuration...Export limitation configuration on Smartlogger1000/2000 Public 2018-10-22 eu_inverter_support@huawei.com Page12, Total13

Export limitation configuration on Smartlogger1000/2000 Public

2018-10-22 [email protected]

Page10, Total13

Parameter configuration: -Export Limitation: Enables or disables the Export Limitation prevention feature. -Control policy: Currently, only Strategy 1 is supported. - Electric meter power direction: Set this parameter to Positive if the active power reading of the power meter is positive when the inverter has no power output. Otherwise, set this parameter to Reverse. - Maximum grid feed-in power: Maximum output power of the inverter to the power grid. Suggestion: Set this parameter according to the threshold allowed by the local power company. - Power lowering adjustment period: Inverter output power lowering period. Refer to Empirical Parameters. (If it is consistent with Maximum protection time, the power can be lowered for 100% in a single step.) -Maximum protection time: The maximum duration of the inverter output power to the power grid exceeding the preset threshold detected by the SmartLogger1000/2000. If Switch-off with 0% power limit is enabled, DO switch-off is triggered. This parameter is used with Power lowering adjustment period. Refer to Empirical Parameters. Suggestion: Set this parameter according to the maximum duration allowed by the local power company. - Power raising threshold: Inverter output power raising threshold. - Power limit for abnormal electric meter: Inverter output power percentage controlled by the SmartLogger1000/2000 when communication between the SmartLogger1000/2000 and the power meter is abnormal.

Page 11: Huawei Technologies Co. Ltd. Export limitation configuration...Export limitation configuration on Smartlogger1000/2000 Public 2018-10-22 eu_inverter_support@huawei.com Page12, Total13

Export limitation configuration on Smartlogger1000/2000 Public

2018-10-22 [email protected]

Page11, Total13

- Switch-off with 0% power limit: Enables or disables DO switch-off. The default value is Disable. - Switch-off control port: Switch-off DO port. - Switch-on control port: Switch-on DO port. - Switch-off state feedback port: Switch-off state feedback DI port. - Switch-on state feedback port: Switch-on state feedback DI port. Empirical Parameters

Meter Model Power Raising Gradient

Power Raising Adjustment Period

Power Lowering Adjustment Period

Maximum Protection Time

UMG 10%/s 1s 0.5s 3s COUNTIS E43

5%/s 2s 0.5s 3s

UMP209 5%/s 2s 0.5s 3s 3. Circuit Breaker Control The following figure shows the circuit breaker drive wiring diagram for the SmartLogger2000. DO1 is used as an example.

Page 12: Huawei Technologies Co. Ltd. Export limitation configuration...Export limitation configuration on Smartlogger1000/2000 Public 2018-10-22 eu_inverter_support@huawei.com Page12, Total13

Export limitation configuration on Smartlogger1000/2000 Public

2018-10-22 [email protected]

Page12, Total13

The following figure shows the circuit breaker drive wiring diagram for the SmartLogger1000. DO1 is used as an example.

-DO1 on the SmartLogger1000/2000 is used to control the switch-off output. The NO port of DO1 is connected to relay +, and the COM port is connected to 12 V power supply +. The NO contact of the intermediate relay is connected to the circuit breaker switch-off coil. -DI1 on the SmartLogger1000/2000 is used to detect the switch-off status and is connected to the circuit breaker switch-off status output. DI2 is used to check the switch-on status and is connected to the circuit breaker switch-on status output. GND is connected to the common end of the circuit breaker. -DO2 on the SmartLogger1000/2000 is used to control the switch-on output. It is wired in the same way as DO1. The difference is that the NO contact of the intermediate relay is connected to the circuit breaker switch-on coil. - The intermediate relay uses a 12 V drive coil, the contact supports 250 V AC @ 10 A or higher, and the relay is installed with a base and guide rail. -The intermediate relay and external power adapter are configured by the customer and are not provided by Huawei. Switch-off control test:

Page 13: Huawei Technologies Co. Ltd. Export limitation configuration...Export limitation configuration on Smartlogger1000/2000 Public 2018-10-22 eu_inverter_support@huawei.com Page12, Total13

Export limitation configuration on Smartlogger1000/2000 Public

2018-10-22 [email protected]

Page13, Total13

After switch-off is complete, check whether the circuit breaker is OFF. Switch-on control test:

After switch-on is complete, check whether the circuit breaker is ON.