+ All Categories
Home > Documents > HV DOUBLE POLE ISOLATOR TRACTION POWER TRANSFORMER … · The minimum clearances in air for live...

HV DOUBLE POLE ISOLATOR TRACTION POWER TRANSFORMER … · The minimum clearances in air for live...

Date post: 18-Mar-2020
Category:
Upload: others
View: 2 times
Download: 0 times
Share this document with a friend
8
HV DOUBLE POLE ISOLATOR TYPE: Manually operated single or Double break upright mounting with the movement of blade(s) in a horizontal plane with or without earthing switch and suitable for outdoor installation No. of pole Two/Three Nominal system voltage 132kV 220kV Highest system voltage 145kV 245kV Rated current 1250A 1250A Rated short time withstand current for one second 31.5kA (rms) 31.5kA (rms) Isolating distance in air 1800mm 2800mm HV CURRENT TRANSFORMER TYPE: Single phase, Oil filled, Self cooled, Outdoor Type Rated system voltage 132kV 220kV Frequency 50Hz. ±3% Rated primary current 400-200 200-100 Rated secondary current 5A 5A Rated burden 30VA 30VA Class of isolation A A HV CIRCUIT BREAKER (CB) Rated system voltage 132kV 220kV Rated normal current 1600A 2000A Rated short circuit breaking current 40kA 50kA Rated breaking capacity 5800MVA 12250 MVA Frequency 50Hz TRACTION POWER TRANSFORMER TYPE: ONAN cooled, single phase, step down Power transformer, Double limb wound, Core Type Outdoor installation Winding Uniformly insulated concentratric Frequency 50Hz Rated primary voltage 132kV OR 220kV Rated secondary voltage 27kV Rated power 21.6/30 MVA 30/42 MVA 25kV LIGHTING ARRESTER System Single phase ac traction Nominal system voltage 25kV (phase to earth) possible variation in the traction supply 22.5 to 27.5 kV sometimes touching 30kV Rated frequency 50Hz Type Non-linear metal oxide resistor type without gap Line discharge class CLASS 3 Continous operating voltage capability 35kV (rms) 25kV POTENTIAL TRANSFORMER (PT) Type I II PTR 27.5Kv/100V 27.5kV/110V Burden 30VA 100VA 1 2 25kV CURRENT TRANSFORMER (CT) TYPE OCT 47 AD/01 CTR 1500/750/5A Burden 60VA Insulation Level 35/250kV
Transcript
Page 1: HV DOUBLE POLE ISOLATOR TRACTION POWER TRANSFORMER … · The minimum clearances in air for live equipment shall be as under: Clearance in mm 25 kV 66 kV 110 kV 132 kV 220 kV 1 Between

HV DOUBLE POLE ISOLATOR

TYPE: Manually operated single or Double break

upright mounting with the movement of blade(s)

in a horizontal plane with or without earthing

switch and suitable for outdoor installation

No. of pole Two/Three

Nominal system voltage 132kV 220kV

Highest system voltage 145kV 245kV

Rated current 1250A 1250A

Rated short time withstand

current for one second

31.5kA

(rms)

31.5kA (rms)

Isolating distance in air 1800mm 2800mm

HV CURRENT TRANSFORMER

TYPE: Single phase, Oil filled, Self cooled,

Outdoor Type

Rated system voltage 132kV 220kV

Frequency 50Hz. ±3%

Rated primary current 400-200 200-100

Rated secondary current 5A 5A

Rated burden 30VA 30VA

Class of isolation A A

HV CIRCUIT BREAKER (CB)

Rated system voltage 132kV 220kV

Rated normal current 1600A 2000A

Rated short circuit

breaking current

40kA 50kA

Rated breaking capacity 5800MVA 12250

MVA

Frequency 50Hz

TRACTION POWER TRANSFORMER

TYPE: ONAN cooled, single phase, step down Power

transformer, Double limb wound, Core Type

Outdoor installation

Winding Uniformly insulated

concentratric

Frequency 50Hz

Rated primary voltage 132kV OR 220kV

Rated secondary voltage 27kV

Rated power 21.6/30 MVA

30/42 MVA

25kV LIGHTING ARRESTER

System Single phase ac traction

Nominal system

voltage

25kV (phase to earth) possible

variation in the traction supply 22.5 to

27.5 kV sometimes touching 30kV

Rated frequency 50Hz

Type Non-linear metal oxide resistor type

without gap

Line discharge class CLASS 3

Continous operating

voltage capability

35kV (rms)

25kV POTENTIAL TRANSFORMER (PT)

Type I II

PTR 27.5Kv/100V 27.5kV/110V

Burden 30VA 100VA

1 2

25kV CURRENT TRANSFORMER (CT)

TYPE OCT – 47 AD/01

CTR 1500/750/5A

Burden 60VA

Insulation Level 35/250kV

Page 2: HV DOUBLE POLE ISOLATOR TRACTION POWER TRANSFORMER … · The minimum clearances in air for live equipment shall be as under: Clearance in mm 25 kV 66 kV 110 kV 132 kV 220 kV 1 Between

DYNAMIC REACTIVE POWER COMPENSATION

EQUIPMENT ( DRPC)

System Single phase ac Traction System

Nominal system

voltages

25kV (phase to earth)

Rated frequency 50Hz

25KV AC SINGLE POLE ISOLATOR (SPI) AND DOUBLE

POLE ISOLATOR (DPI)

Type Manually operated, horizontally mounted on

pole, vertical break type and suitable for outdoor

Number of

phases

One

No’s of pole Single pole/double pole

Isolating

distance

500mm (min.) in air

Rated voltage 25kV (nominal) 30kV max.

Rated current Type –I 1250A (used at SSP & SP)

Type –II 1600A (used at FP & TSS)

AUXILARY TRANSFORMER (AT)

Type Double wound, single phase, ONAN

cooled, step down transformer for

outdoor installation.

Rated voltage of

primary winding

a) Nominal voltage 25kV

b) Minimum voltage 19kV

c) Maximum voltage 27.5kV

Rated voltage of

secondary winding

240V

Rated frequency 50Hz ±3%

Rated Power at rated

nominal voltage

5kVA, 10kVA, 25kVA and 100kVA

25kV INTERRUPTER

System Single phase ac traction system

Nominal system

voltage

25kV variation from 19kV to 27.5kV

– occasionally touching 30kV

Rated frequency 50Hz ±3%

No. of poles One

Class Outdoor

Rated voltage class 52kV

Rated normal current 800A

Rated short circuit

making current

20kA (peak)

25KV CIRCUIT BREAKER (CB)

System Single phase ac traction system

Rated system voltage 25kV

Rated normal current 1600A

Rated short circuit

breaking current

20kA

Rated breaking

capacity

550MVA

Rated Frequency 50 Hz

3 4

Voltage Regulation

The permissible variation of the bus bar voltage on the busbars at

the grid sub-station is +10% and -5% i.e., between 27,500 V. and 23,750

V. The tappings on the transformers are on the secondary winding and are

set to ensure that the voltage is maintained as high as possible but not

exceeding 27.5 kV at the feeding post at any time.

Page 3: HV DOUBLE POLE ISOLATOR TRACTION POWER TRANSFORMER … · The minimum clearances in air for live equipment shall be as under: Clearance in mm 25 kV 66 kV 110 kV 132 kV 220 kV 1 Between

Rating Of Equipments At Traction Sub-Staion

with 30/42MVA Power Transformer

Sr. Name of Equipment Rating

1. 132kV Double pole Isolator 1250A

2. 132kV Current Transformer 400-200/5A

3. 132kV Circuit Breaker 1600A

4. 132kV Potential Transformer 132kV/110V

5. 132kV Lightning Arrester 120kV

6. 132kV Bushing CT 600/5A

7. Traction Transformer 132kV/25kV,

30/42MVA

8. 25kV Bushing CT 3000/5A

9. 25kV Lightning Arrester 42kV

10 25kV Current Transformer 1500-750/5A

11. 25kV Circuit Breaker 2000A

12. 25kV Single pole Isolator 3150A

13. 25kV Potential Transformer type-II 27.5kV/110V

14. Series Reactor 875 kVAR

15. Shunt Capacitor 7700kVAR

16. NCT 4/2/1A

17. 25kV Potential Transformer type-I 27.5kV/100V

18. 25kV Bi polar Isolator 1600A

19. 25kV Interruptor 2000A

Feeding and Sectioning Arrangements

The generation and transmission systems are 3-phase systems. The single-

phase traction load causes unbalance in the supply system. This unbalance

has undesirable effects on the generators and equipment of other consumers,

if its value becomes excessive.

Voltage Unbalance (%)

Instantaneous 5

2 hours 3

Continuous 2

To keep the unbalance on the 3-phase grid system within the above limits,

power for ac single-phase traction is tapped off the grid system across the

different phases at adjacent sub-stations in cyclic order.

TSS Bus-bar layout

The bay widths are standardized for each primary voltage i.e. 66 kV, 110kV,

132 kV and 220 kV.

The most generally used system voltage is 132 kV and bay widths for 132 kV

are standardized as 14.0 m for HV bay and 6.0 m for 25 kV bay.

The stung bus on the HV side stung at a height of 9.35 m from ground level

comprises of 54/3.18 mm (28.62 mm dia) ACSR conductor (Zebra) with a

gross area of aluminium of 428 mm2.

On the 25 kV side 50 mm outside dia. aluminium tubular bus bar is provided

at a height of 3.8 m.

Tension of stung bus is specified as 450 kgf and the earth screen wires as 200

kgf at 4°C without wind.

The maximum span from the last tower to sub-station gantry is generally

limited to around 75 m.

If the distance of the incoming HV transmission line from the grid sub-station

is more than 4 km, lightning arrestors are provided on the incoming lines, at

the traction sub-station.

5 6

The deflections of bus-bars supported on post insulators should not exceed

half the diameter of the bus bars or span/1440 whichever is less.

The current density generally adopted for outdoor copper bus-bars is 2

A/mm2.

The insulators, bus bars and connections should not be stressed to more than

1/4 of the breaking load or 1/3 of their elastic limit whichever is lower. The permissible voltage unbalance at the point of common coupling on the grid

supply system should not exceed the following limits:—

Page 4: HV DOUBLE POLE ISOLATOR TRACTION POWER TRANSFORMER … · The minimum clearances in air for live equipment shall be as under: Clearance in mm 25 kV 66 kV 110 kV 132 kV 220 kV 1 Between

The minimum clearances in air for

live equipment shall be as under:

Clearance in mm

25 kV 66

kV

110

kV

132

kV

220

kV

1 Between phases NA

[ since

single

phase]

2000 3000 3000 4000

2 Between one phase and earth for

rigid connection

500 630 900 1300 2100

3 Between any point where man

may be required to stand to the

nearest

a) unsecured conductor in air

b) secured conductors in air

3000

2000

3500

3500

3500

3500

4000

4000

5000

5000

4 Minimum height of bus bar 3800 4600 4600 4600 5500

Characteristics Of Traction Transformers

To cater for the peaks in the demands, the transformers are capable of

withstanding non-recurring over-loads of 50% for 15 minutes and 100% for 5

minutes after the transformer has reached steady temperature on continuous

operation at full load.

Off load tap changing from + 10% to –15% in steps of 5% is provided on the

low voltage side. The maximum efficiency is specified at about 50% of full

load.

The temperature rise over an ambient of 50oC for 100% over load for 5

minutes or 50% over load for 15 minutes after continuous full load operation

is specified not to exceed 50oC for winding (resistance measurement) and

40oC for oil by thermometer.

The transformers of ratings of 21.6 MVA are specified as ONAN cooled and

so designed that with ONAF cooling at a later date the capacity is capable of

being increased by 40% more by provision of forced cooling (ONAF).

Winding And Oil Temperature Protection

The life of the transformer depends upon the state of its insulation, whose rate

of deterioration is accelerated at excessively high temperatures. Therefore, the

transformers have been provided with winding and oil temperature alarm and

tripping device which operate through mercury contacts. The settings adopted

for the above are :

Winding

temperature

alarm

Winding

temperature

tripping

Oil

temperature

alarm

Oil

Temperature

tripping

100°C 105°C 85°C 90°C

Earth Resistance

At each power supply installation, an earthing system shall be provided. The

combined resistance of the earthing system shall be not more than the

following values:-

S.N. Name of the station The limit of combined earth

resistance in Ohm

1. Traction substation 0.5

2. Switching station 2.0

3. Booster transformer station 10.0

4. Auxiliary transformer station 10.0

7 8

Earth Electrodes

The earth electrode shall normally be of mild steel galvanised perforated pipe

of not less than 40 mm nominal bore, of about 4 m length provided with a

spike at one end and welded lug suitable for taking directly MS flat of required

size at the other end.

The pipe shall be embedded as far as possible vertically into the ground, except

when hard rock is encountered, where it may be buried inclined to the vertical,

the inclination being limited to 30° from the vertical.

Earth electrodes shall be embedded as far apart as possible from each other.

Mutual separation between them shall usually be not less than 6.0 m (which is

twice the length of the electrode).

Page 5: HV DOUBLE POLE ISOLATOR TRACTION POWER TRANSFORMER … · The minimum clearances in air for live equipment shall be as under: Clearance in mm 25 kV 66 kV 110 kV 132 kV 220 kV 1 Between

If the value of earth resistance can not be achieved with a reasonable number

of electrodes connected in parallel, the earth surrounding the electrodes shall

be chemically treated. The earth electrode shall be surrounded in an earth-pit

by alternate layers of finely divided coke, crushed coal or charcoal and salt at

least 150 mm all round.

In high embankments, it may be difficult to achieve earth resistance even after

chemical treatment of electrodes. In those locations, use of electrodes longer

than 4 m so as to reach the parent soil is recommended.

Earthing Arrangement at Traction Substation

Earthing Grid.

An earthing grid is formed by means of bare mild steel rod of appropriate size

buried at a depth of about 600-mm below the ground level and connected to

earth electrodes. The connection between the earth electrode and the grid shall

be by means of two separate and distinct connections made with 75 mm x 8

mm MS flat.

The size of the earthing grid conductor shall be decided based on the incoming

system voltage and fault level. The fault level considered shall take into

account the anticipated increase in fault current during the life span of the

station. The size shall be as given below:

Sr. System

Voltage (kV)

Fault Level (MVA) Diameter of the grid

conductor (MS rod) in mm

1 66 Upto 4000

Above 4000 upto 5000

Above 5000 upto 6000

32

36

40

2 110 Upto 6000

Above 6000 upto 8000

Above 8000 upto 10000

32

36

40

3 132 Upto 7000

Above 7000 upto 10000

32

36

4 220 Upto 12000

Above 12000 upto 16000

Above 16000 upto 20000

32

36

40

System Earthing.

One terminal of the secondary winding (25 kV winding) of each traction

power transformer shall be earthed directly by connecting it to the earthing

grid by means of one 75 mm x 8 mm MS flat, and to the buried rail by means

of another 75 mm x 8 mm MS flat.

One designated terminal of the secondary of each potential, current and

auxiliary transformer shall be connected to the earthing grid by means of two

separate and distinct earth connections made with 50 mm x 6mm MS flat.

9 10

Equipment Earthing.

The metallic frame work of all outdoor equipments such as transformers,

circuit breakers, Interrupters and Isolators, as well as steel structures shall be

connected to the earthing grid by means of two separate and distinct

connections made with MS flat of size as indicated below; one connection

shall be made with the nearest longitudinal conductor, while the other shall be

made to the nearest transverse conductor of the grid:

Buried Rail

A steel rail of section 52 kg/m (the one used for the railway track) and

length about 13 m shall be buried near the track at the traction substation at

a depth of about one metre to form part of the earthing system.

Two separate and distinct connections shall be made by means of 75 mm x

8 mm MS flat between the earthing grid and the buried rail. The buried rail

shall also be connected by means of two separate and distinct connections

made of 75 mm x 8 mm MS flat to the rail(s) in a single-rail track circuited

section and to the neutral point(s) of the impedance bond(s) in a double-rail

track circulated section.

Page 6: HV DOUBLE POLE ISOLATOR TRACTION POWER TRANSFORMER … · The minimum clearances in air for live equipment shall be as under: Clearance in mm 25 kV 66 kV 110 kV 132 kV 220 kV 1 Between

Sr. Equipment System voltage

and fault level

Ground

conductor size

1. Equipments on the

primary side of traction

power transformer.

66 kV, upto 3000 MVA

110 kV, upto 5000 MVA

132 kV, upto 6000 MVA

220 kV, upto 10000 MVA

50 mm x 6 mm

66 kV, above 3000 upto 6000 MVA

110 kV, above 5000 upto 10000 MVA

132 kV, above 6000 upto 12000 MVA

220 kV, above10000 upto 20000 MVA.

75 mm x 8 mm

2. Equipments on the

secondary side of

traction power

transformer.

50 mm x 6 mm

3. Fencing uprights/ steel

structures

50 mm x 6 mm

4. Doors/ fencing panels 6 SWG G.l.

Wire

This earth electrode shall be connected to the ground terminal of the LA as well

as to the main earthing grid by means of two separate and distinct connections

made with 50 mm x 6 mm MS flat for the 25 kV side LA, and with 75 mm x 8

mm MS flat for the primary side LA. For LA provided for the traction power

transformers, there shall also be a connection as direct as possible from the

ground terminal of the LA to the frame of the transformer being protected; this

connection shall also be made by means of two separate and distinct connections

made with 50 mm x 6 mm MS flat for 25 kV side, and with 75 mm x 8mm MS

flat for primary side LA.

Earth Screen.

● The area covered by outdoor substation equipments shall be shielded against

direct strokes of lightning by an overhead earth screen comprising 19/2.5 mm

galvanised steel stranded wire strung across the pinnacles of the metallic

structures. The earth screen wires shall be strung at a height as indicated in the

approved traction substation layouts (not less than 2.5 m above the live

conductors) and shall be solidly connected to the traction substation earthing grid

at each termination by means of 50 mm x 6fmm MS flat.

Earthing Of Fencing Uprights And Panels.

● Each metallic fencing upright shall be connected to the traction substation main

earthing grid by means of two separate and distinct connections made with 50 mm

x 6 mm MS flat. In addition, all the metallic fencing panels shall be connected to

the uprights by means of two separate and distinct connections made with 6 SWG

G.I. wire. All the metallic door panels shall also be connected to the supporting

uprights by means of two separate and distinct connections made with 6 SWG GI

wire.

Earthing At The Point Of 240 V Ac 50 Hz Supply For Oil Filtration Plant.

● The 240 V ac 50 Hz distribution board for power supply to oil filtration plant

shall be connected to the main earthing grid by means of two separate and distinct

connections made with 50 mm x 6 mm MS flat.

Earthing Inside Control Room.

● An earthing ring shall be provided inside the control room by means of 50 mm x

6 mm MS flat which shall be run along the wall at a height of about 300 mm from

the floor level. The earthing ring shall be connected to the main earthing grid by

means of two separate and distinct connections made with 50 mm x 6 mm MS

flat. The earthing ring shall also be connected to an independent earth electrode

by means of two separate and distinct connections made with 50 mm x 6 mm MS

flat.The metallic framework of control and relay panels, LT A.C. and D.C.

distribution boards, battery chargers, remote control equipment cabinets and such

other equipments shall be connected to the earthing ring by means of two separate

and distinct connections made with 8 SWG galvanised steel wire.

The connections shall be taken along the wall and in recesses in the floor. All

recesses shall be covered with cement plaster after finishing the work.

Connections between the MS flats shall be made by welding.

Earthing of lightning arrester (LA).

● In addition to the earth electrodes provided for the main earthing grid, an

independent earth electrode shall be provided for each LA.

Earthing Arrangement at Switching Station

● A minimum number of three earth electrodes (excluding the one to be provided

separately for the remote control cubicle earthing) shall be provided at each

switching station, and they shall be interconnected by means of 50 mm x 6 mm

MS flat forming a closed loop main earthing ring.

11 12

Page 7: HV DOUBLE POLE ISOLATOR TRACTION POWER TRANSFORMER … · The minimum clearances in air for live equipment shall be as under: Clearance in mm 25 kV 66 kV 110 kV 132 kV 220 kV 1 Between

● This ring shall be connected by two separate and distinct connections made with

50 mm x 6 mm MS flat, to the traction rail in a single-rail track circuited section

and to the neutral point of the impedance bond in a double-rail track circuited

section of the nearest track, so as to limit the potential gradient developing in the

vicinity of the switching station in the event of a fault.

System Earthing.

● One designated terminal of the secondary of each potential, current and auxiliary

transformer shall be connected to the main earthing ring by means of two separate

and distinct connections made with 50 mm x 6mm MS flat.

Equipment Earthing.

● All masts, structures, fencing uprights, and all outdoor equipment pedestals

including auxiliary transformer tank shall be connected to the earthing ring by

means of two separate and distinct connections made with 50 mm x 6 mm MS

flat. All fencing panels shall be connected to the supporting uprights by means of

two separate and distinct connections made with 6 SWG GI wire. All the metallic

door panels shall be connected to the supporting uprights by means of two

separate and distinct connections made with 6 SWG GI wire.

● The metal casing of CT’s & PT’s shall be connected to the mast/structures by

means of two separate and distinct connections made with 50 mm x 6 mm MS

flat.

● The ground terminal of lightning arrester shall be connected directly to the earth

electrode by means of two separate and distinct connections made with 50 mm x

6 mm MS flat. The earth electrode shall be so placed that the earthing leads from

the lightning arrester may be brought to the earth electrode by as short and

straight path as possible.

The metal casing of LT A.C. and D.C. distribution board, battery chargers,

terminal board, remote control equipment cabinets and other such equipments

shall be connected to the earthing ring by means of two separate and distinct

connections made with 8 SWG G.I. wire. The connections shall be taken along

the wall and in recesses in the floor. All recesses shall be covered with cement

plaster after finishing the work. Connections of earth strips to each other shall be

made by welding.

Earthing of Neutral of Local Power Supply System

● At TSS and switching stations where power supply at 415 V/ 240 V, ac, 50 Hz, is

taken from the local supply authority and having neutral earth at some distant

point in the premises 'of the supply authority, the neutral of such supply shall also

be earthed by means of two separate and distinct connections made with 6 SWG

G.I. wire by connecting to an independent earth electrode.

Earthing Arrangement at Auxiliary Transformer Station

● The combined earth resistance at an auxiliary transformer station shall be not

more than 10 ohm.

● Normally one earth electrode is sufficient for an auxiliary transformer station. The

earth electrode shall be connected to the mast on which the auxiliary transformer

is mounted by means of two separate and distinct connections made with 50 mm

x 6 mm MS flat. In addition the mast shall be connected to the nearest traction rail

or to the neutral point of the nearest impedance bond in a double rail track

circuited section by means of a 50 mm x 6 mm MS flat.

● The earthing terminal on the transformer tank shall be connected to the mast on

which the transformer is mounted by means of two separate and distinct

connections made with 50 mm x 6 mm

● MS flat. One terminal of the secondary winding of the auxiliary transformer shall

be connected to the earthing terminal on the transformer tank and as well as to the

mast by means of 50 mm x 6 mm MS flat. Earthing Inside Remote Control Cubicle.

● An earthing ring shall be provided inside the remote control cubicle by means of

50 mm x 6 mm MS flat; the earthing ring shall be run along the wall on teak

wood blocks fixed to the wall at a height of 300 mm from the floor level. The

earthing ring shall be connected to the main earthing ring as well as to an

independent earth electrode by means of two separate and distinct connections

madel with 50 mm x 6 mm MS flat.

Crushed Rock Surface Layer

● At the TSS and switching stations, a surface layer of crushed rock shall be

provided to a thickness of about 100 mm. If considered necessary from the point

of view of containing the step and touch voltages within the acceptable limits,

higher thicknesses may be provided depending on calculation based on site

conditions. 13 14

Page 8: HV DOUBLE POLE ISOLATOR TRACTION POWER TRANSFORMER … · The minimum clearances in air for live equipment shall be as under: Clearance in mm 25 kV 66 kV 110 kV 132 kV 220 kV 1 Between

It is clarified that this pamphlet does not supersede any existing provisions laid down by RDSO, Railway Board or Zonal Railways. The pamphlet is for guidance only and it is not a statutory document.

If you have any suggestion or comment, please write to: Director (Electrical), CAMTECH, Maharajpur, Gwalior (M.P.) – 474 005

Ph.0751-2470740, Fax 0751-2470841 E-mail: [email protected]

Disclaimer:

(For Official Use Only)

Hkkjr ljdkj GOVERNMENT OF INDIA

jsy ea=ky; MINISTRY OF RAILWAYS

CAMTECH/E/2018-19/PSI Parameter/1.0

June, 2018

egkjktiqj, Xokfy;j & 474 005

Maharajpur, GWALIOR - 474 005

सत्यमेव जयते

End User : TrD – PSI Staff

OHM IMPEDANES

The following values of OHE impedances may be used for the purpose of calculating

relay settings:

i. Single track OHE without return conductor : 0.4 l ∠70° Ohm/km

ii. Double track OHE without RC : 0.24 ∠70° Ohm/km

iii. Single track OHE with RC : 0.70 ∠70° Ohm/km

iv. Double track OHE with RC : 0.43 ∠70° Ohm/km

Lead Acid Batteries

On electrified sections batteries and battery chargers are installed at the following

locations:-

1. Traction Sub-stations -

110V, 200Ah.lead acid cells for control, protection and indication circuits.

2. Switching Stations -

110V, 40Ah lead acid batteries for operation of circuit breakers and interruptors

and motor operated isolators.

Specific Gravity

The specific gravity of the electrolyte should be maintained at about 1.210 at 27° C

and when it drops to 1.150 the cell may be considered discharged. These values vary

with the type of battery, temperature, age and working conditions.

Cell Voltage

The voltage of new cells at the end of a full charge will be about 2.5 to 2.75 V when

it is receiving charge at the 10 hour rate. This gradually decreases as the age of the

battery increases until it comes down to 2.4 V with normal temperature and charging

rate. No cell should ever be discharged below the point where the cell voltage

reaches 1.85 V as measured when the cell is discharging at the normal 10 hour rate.


Recommended