3847uk/1/08/15/10 HYDRA® GS INSTALLATION MANUAL United Kingdom and Ireland Witzenmann UK Ltd Head Office 2 Earn Avenue Righead Industrial Estate Bellshill, Scotland, ML4 3LW Phone +44 1698 74 96 60 Fax +44 1698 74 07 74 [email protected] www.witzenmann.co.uk Unit 4 Whitfield Business Park Manse Lane Knaresborough North Yorkshire, HG5 8BS Phone + 44 1423 868586 Fax +44 1423 865783 [email protected] Office Suite 9 Cwm Cynon Business Centre Cwm Cynon Industrial Park Mountain Ash Mid Glamorgan, CF45 4ER Phone +44 1443 471000 Fax +44 1443 479638 [email protected]
Transcript
Page 1: HYDRA® GS INSTALLATION MANUAL - Witzenmann · certificate must have been issued under either the Approved Code of Practise (ACoP) or the National Accredited Certification Scheme

3847

uk/1

/08/

15/1

0

HYDRA® GSINSTALLATIONMANUALUnitedKingdomandIreland

Witzenmann UK Ltd

Head Office

2EarnAvenue

RigheadIndustrialEstate

Bellshill,Scotland,ML43LW

Phone+441698749660

Fax+441698740774

[email protected]

www.witzenmann.co.uk

Unit4

WhitfieldBusinessPark

ManseLane

Knaresborough

NorthYorkshire,HG58BS

Phone+441423868586

Fax+441423865783

[email protected]

OfficeSuite9

CwmCynonBusinessCentre

CwmCynonIndustrialPark

MountainAsh

MidGlamorgan,CF454ER

Phone+441443471000

Fax+441443479638

[email protected]

Page 2: HYDRA® GS INSTALLATION MANUAL - Witzenmann · certificate must have been issued under either the Approved Code of Practise (ACoP) or the National Accredited Certification Scheme

3847uk/1/08/15/10 3847uk/1/08/15/102 3

CONTENTS

1. Scope of application and general notes 41.1. Validity 41.2. Theproduct 41.3. Definition 41.3.1. Systemdefinition 41.3.2. FlexiblecorrugatedhosesPLT(pliabletube) 41.4. Specifications 51.5. Standardsandcodesofpractice 61.6. Systemconformity 71.7. Fieldsofapplication 71.8. Operatingconditions 7 2. HYDRA GS installation system and system components 8 HYDRAGSstainlesssteelcorrugatedpipesandpipedimensions 92.1. HYDRAGSPress 10 HYDRAGSPress-Threadednipple 10 HYDRAGSPress–Swivelconnection 10 HYDRAGSPress–Adaption 11 HYDRAGSPress–T-piece 11 HYDRAGSPress–Reducer 12 HYDRAGSPress–Conicalnipple 12 HYDRAGSPress–Presscase 13 HYDRAGSPress–Pipecutter 13 HYDRAGSPress–Expansionhead 142.2. HYDRAGSClick 15 HYDRAGSClick–ThreadedBSPfixedtapermale 15 HYDRAGSClick–ThreadedBSPparafixedfemale 15 HYDRAGSClick–T-piece 16 HYDRAGSClick–Soldersocket 17 HYDRAGSClick–ConnectionBS746female 17 HYDRAGSClick–Coppercompressionfitting 18 HYDRAGSClick–StraightCoupling 182.3. HYDRAGSPressundHYDRAGSClick 19 HYDRAGSBISMAT-Flashpipeclamp 19 HYDRAGSCaddyclip 19 HYDRAGSStripearthband 20 HYDRAGSCoroplastadhesivetape 20

3. Dimensioning the pipeline system 213.1. Basisfordimensions 213.2. Preliminarydimensioningusingtable 213.3. Pressurelossesinthecorrugatedpipeline 223.3.1. NaturalgasL 223.3.2. NaturalgasH 233.3.3. Propanegas 243.4. Examplecalculation 253.5. Pressurelosscalculationwithsoftwaretool 26 4. Assembly HYDRA GS Press 304.1. Assemblyprocedure 30 5. Assembly HYDRA GS Click 365.1. Assemblyprocedure 36 6. Assembly on parts outside the HYDRA GS gas installation system 386.1. ValidforHYDRAGSPressandClick Tighteningtorques 386.2. ValidforHYDRAGSPressandClick Minimumbendingradii 38 7. General notes on installation 397.1. Generalinstructions 397.2. HYDRAGSfirebehaviour 407.3. Potentialequalisation 407.4. Fasteningandfasteningdistances 41 8. Protection against corrosion or damage 43 9. Recommendations for storing gaskets 4310. Repair methods 4410.1. DamagetoHYDRAGSstainlesssteelcorrugatedpipes 44

Page 3: HYDRA® GS INSTALLATION MANUAL - Witzenmann · certificate must have been issued under either the Approved Code of Practise (ACoP) or the National Accredited Certification Scheme

3847uk/1/08/15/10 3847uk/1/08/15/104 5

1. SCOPE OF APPLICATION AND GENERAL NOTES

1.1.Validity

ThisinstallationinstructionisvalidforthegasinstallationsystemHYDRAGSmadebyWitzen-mannGmbH,Germany.Itisintendedtoguidethegaspipeinstallerinthedesign,installationandfinaltestingstages.Allspecificationsinthismanualmustbecompliedwithduringworkandinstallation.NodeviationsfromtheinstallationspecificationsinthismanualarepermittedwithoutpriorconsultationwithWitzenmannGmbH.

1.2.Theproduct

TheWitzenmanngasinstallationsystemHYDRAGScompliestoandistestedaccordingtotherequirementsofBSEN15266:2007(Stainlesssteelpliablecorrugatedtubingkitsinbuildingsforgaswithanoperatingpressureupto0.5bar).ThegasinstallationsystemHYDRAGShasbeengrantedKitemarkLicenceNumberKM594313byBritishStandardsInstitution,coveringsizesDN15,DN22,DN28andDN32andassociatedfittings.Thecertificationalsoincludesresistancetohightemperatures(HTB)accordingtoBSEN1775.HYDRAGScanbeinstalledindomestic,industrialandcommercialbuildings.HYDRAGSissuitablefornaturalgasandliquifiedpetrolgas(2ndand3rdfamilygas).

1.3.Definition

1.3.1. System definitionHYDRAGSisaflexiblegasinstallationsystemforcarryinggasinthebuildingtechnology.HY-DRAGSisofferedinthefournominaldiametersDN15,DN22,DN28andDN32.HYDRAGSconsistsofflexiblecorrugatedhosesandHYDRAGSPressfittingsorHYDRAGSClickfittings,specialfasteningelements,abattery-operatedaxialpressingtoolforexpandingtheHYDRAGSPressfittingsandconfigurationsoftwarefordeterminingthesizeofthepipelines.

1.3.2. Flexible corrugated hoses PLT (pliable tube)Corrugated,sheathedpipewhichcanbebentbyhandeasilyforalimitednumberoftimes.

1.4.Specifications

GasinstallersshallbeinpossessionofavalidcertificateofcompetenceforactivitiesnecessarytoinstallandtestthegasinstallationsystemHYDRAGS,seeBS6891section4.ThevalidcertificatemusthavebeenissuedundereithertheApprovedCodeofPractise(ACoP)ortheNationalAccreditedCertificationScheme(ACS)forindividualgasinstallersoranequivalentqualification.

AllbusinessesandindividualsundertakinggasworkoninstallationssuppliedwithnaturalgasorLPGmustberegisteredwithabodyapprovedbytheHealthandSafetyExecutive(HSE).(InGreatBritainitisTheGasSafeRegister.InNorthernIreland,theCannelIslandsandtheIsleofMan,consulttherelevantauthoritiesforup-to-dateguidance.)AllgasappliancesandothergasfittingsmustbeinstalledinaccordancewithTheGasSafety(InstallationandUse)Regulations1998,buildingregulationsandmanufacturers'installationinstructions.InstallationsshouldalsocomplywithBritishStandards.(OurDesignandInstallationGuiderevisionswillfollowanyamendmentstotheRegulationsorBritishStandardsatalaterdate,andthusintheeventofanyconflicttheRegulationsand/orBritishStandardswilltakeprecedenceoverthisDesignandInstallationGuide).

Fordetailedinformationaboutconnection/disconnectionofpipes,installationindifferentmaterials(e.g.woodenjoistfloors;walls;cavitieswalls;etc.)seeBS5482-1sections12.3ffandBS6891section8.6ff.Note:thesestandardsarecurrentlyunderrevisionwiththeaimtocondensethedesignandinstallationspecificationsforalldomesticfuelgaspipeworksystemsintoonestandard.InstallationforindustrialandcommercialpremisesshallfollowIGEM/UP/2LatestEdition(forsizesaboveDN32andworkingpressureabove21mbar)andIGE/UP/1Lat-estEdition(strengthandtightnesstestingandpurging).Additionallocalregulationsshallalsobefollowed.Pleasecontactlocalauthoritiesfornecessaryinformation.

Thisinstallationguidecannotcoverallpossiblevariationsinconstructionstyle,buildingconfig-uration,appliancerequirementsorlocalrestrictions.IftheinstallerisunsureabouttheproperapplicationofHYDRAGS,werecommendyoucontactusoralocalrepresentative.

Page 4: HYDRA® GS INSTALLATION MANUAL - Witzenmann · certificate must have been issued under either the Approved Code of Practise (ACoP) or the National Accredited Certification Scheme

3847uk/1/08/15/10 3847uk/1/08/15/106 7

1.5.Standardsandcodesofpractice

Aswellastheplanningandinstallationinstructionsgiveninthisinstallationmanual,itisalsonecessarytocomplywiththecurrenteditionsofthefollowingcodesofpracticewhenplanningandinstallingtheentiregassupplysysteminthebuilding:BSEN15266:2007 Stainlesssteelpliablecorrugatedtubingkitsinbuildingsforgas

withanoperatingpressureupto0.5barBSEN549 Rubbermaterialsforsealsanddiaphragmsforgasappliances

andgasequipmentBSEN10226-1:2004-09 Pipethreadswherepressuretightjointsaremadeonthethreads

–Part1:Taperexternalthreadsandparallelinternalthreads–Dimensions,tolerancesanddesignation

BSEN14291:2005-4 FoamproducingsolutionsforleakdetectionongasinstallationsBSEN837-1:1997-02 Pressuregauges–Part1:Bourdontubepressuregauges;

Dimensions,metrology,requirementsandtestingBSEN681-1:2003-8 Elastomericseals–Materialrequirementsforpipejointsealsused

inwateranddrainageapplications–Part1:VulcanizedrubberBS6891 Installationoflowpressuregaspipeworkofupto35mm(R11/4)

indomesticpremises(2ndfamilygas)-SpecificationBS5482-1 Codeofpracticefordomesticbutane-andpropane-gas-burning

installations. Part1:Installationsatpermanentdwellings,residentialparkhomes

andcommercialpremises,withinstallationpipeworksizesnotexceedingDN25forsteelandDN28forcorrugatedstainlesssteelorcopper

IGE/UP/1(Edition2) Strengthtesting,tightnesstestinganddirectpurgingofindustrialandcommercialgasinstallations.

IGEM/UP/2(Edition3) Installationpipeworkonindustrialandcommercialpremises.BSEN437 Testgases–Testpressures–Appliancecategories

Important Note:Crossreferencestoregulations,standardsandcodesofpracticerefertothecurrentstatusatthetimewhenthisinstallationmanualwaspublished.Intheeventofupdates,theuserisresponsibleforapplyingthecurrentregulations,standardsandcodesofpracticeapplicableatthegiventime.Thegenerallyacceptedengineeringstandardsmustalwaysbecompliedwith.

1.6.Systemconformity

OnlycomponentsfromtheHYDRAGSsystemmaybeusedforinstallation.The HYDRA GS installation system made from Witzenmann corrugated pipes is not compatible with the corrugated pipe kits for gas installations from other manufacturers. WitzenmannGmbHdoesnotacceptanyliabilityformalfunctionsthatarecausedbymixingwithsystemcomponentsfromothermanufacturers.Forinstallationofallgasappli-ancesandothergasfittings,itisnecessarytocomplywiththeinstallationinstructionsofthemanufacturer,theapplicablesafetyguidelinesaswellasthecorrespondingbuildingregula-tionsandstandards.

1.7.Areasofapplication

TheHYDRAGSmadefromflexiblestainlesssteelcorrugatedpipescanbeusedforpNewinstallationsofpipelinesystemspRenewingexistingpipelinesystemspExtendingexistingpipelinesystems

1.8.Operatingconditions

pMax.operatingpressure500mbarpTemperaturerange-40°Cto+60°CpNaturalgas/liquefiedgas

Page 5: HYDRA® GS INSTALLATION MANUAL - Witzenmann · certificate must have been issued under either the Approved Code of Practise (ACoP) or the National Accredited Certification Scheme

3847uk/1/08/15/10 3847uk/1/08/15/108 9

HYDRA®GScorrugatedpipesandpipedimensionsTheHYDRAGSsystemofferstheinstallereasyandsafeinstallationofgaspipelines.Theflexiblegaspipeiseasytotransportandlay;theconnectingtechnologyissimpleandunprob-lematic,bothindesignandinhandling.The system is available in 2 designs:As a Click System for easy assembly with no hydraulic tool.Forthissystem,thefittingsareconnectedusingasimpleplugconnection.Thefittingisself-lockingandonlyneedstobescrewedtightusingaspannerorwrenchafterwards.Informationonallcomponentscanbefoundinchapter2.1.Asanalternative,thereisthePressSystemwithahydraulictoolforquickandeffectiveassem-blyoverlongdistances.Forthissystem,thefittingsareconnectedusingaspecialhydraulictool.Itislight,easytouseandisergonomicallyshaped.Thismakesitpossibletoworklongerwithouttiring.Informationonallcomponentscanbefoundinchapter2.2.

Country-specificapprovalsensurethatHYDRAGSsystemsfulfilallrequirementsforalongandsafeservice.

2. HYDRA® GS INSTALLATION SYSTEM AND THE SYSTEM COMPONENTS

StainlesssteelcorrugatedpipeforgasinstallationpPipematerial:1.4404(stainlesssteel)pSheathingmaterial:PE(polyethylene)

DNPipedimensions Corrugated

pipelength

d1+PE d2 d3 ondrummm mm mm m

15 22.1 21.2 16.5 15/30/7522 27.3 26.4 20.5 15/30/7528 32.6 31.7 25.7 15/30/7532 41.5 40.6 35.5 15/30/75

HYDRA® GS

Themanual"QuickSystem" Thesystemusingahydraulictool

HYDRA® GS CLICK HYDRA® GS PRESS

HYDRA Corrugated Hose

Page 6: HYDRA® GS INSTALLATION MANUAL - Witzenmann · certificate must have been issued under either the Approved Code of Practise (ACoP) or the National Accredited Certification Scheme

3847uk/1/08/15/10 3847uk/1/08/15/1010 11

2.1.HYDRA®GSPress

Threadednipple–HYDRA®GSPress

Adapter–HYDRA®GSPress

Threadednippleswithmalethreadacc.toDINEN10226-1areusedforconnectingthepliableHYDRAGSstainlesssteelcorrugatedpipestothefemalethreadconnectionsofvalves,fittingsorgassockets.pMaterial:brasspSealring:HNBR

Theadaptershaveapipethreadacc.toDINEN10226-1anda24°conewithmalethread.Togetherwiththero-tatingconnection,theyformaconicallysealingthreadedconnectionwithaswivelconnectionforconnectingthepliableHYDRAGSstainlesssteelcorrugatedpipestothefemalethreadedconnectionsofvalves,fittingsorgassockets.pMaterial:brass

Swivelconnection–HYDRA®GSPress T-piece–HYDRA®GSPress

Therotatingconnectionhasa24°coneandisusedforconnectingthepliableHYDRAGSstainlesssteelcorrugatedpipestovalvesorfittingswithanmalethreadanda24°cone.pMaterial:brasspSealring:HNBRpO-ring:HNBR

TheT-pieceshavea24°conewithmalethreadateachend.Theyareusedasconnectionelementstootherlinesandthusmakeitpossibletoconnectadditionalconsumers.pMaterial:brass

Dimensions[Nominaldiameterxthread]

DN

Articlenumber Weight

kg15/22xM30x2 1198222 0.196

28xM36x2 1198224 0.25832xM48x2 1198226 0.552

Dimensions[Nominaldiameterxconexunionnutthread]

DN

Articlenumber Weight

kg

15x24°xM30x2 1198215 0.11222x24°xM30x2 1198216 0.13128x24°xM36x2 1198217 0.17832x24°xM48x2 1198221 0.333

Connectiontofitting[Nominaldiameterxthreadacc.to

EN10226-1]DN

Connectiontonipplewithunionnut

[Nominaldiameterxconexthread]

DN

Articlenumber Weight

kg

15xR½ 15x24°xM30x2 1198227 0.07722xR¾ 22x24°xM30x2 1198228 0.09528xR1 28x24°xM36x2 1198229 0.166

32xR1¼ 32x24°xM48x2 1198230 0.254

Dimensions[Nominaldiameterxthreadacc.toEN10226-1]

DN

Articlenumber Weight

kg

15xR½ 1198211 0.06422xR¾ 1198212 0.12028xR1 1198213 0.175

32xR1¼ 1198214 0.248

Page 7: HYDRA® GS INSTALLATION MANUAL - Witzenmann · certificate must have been issued under either the Approved Code of Practise (ACoP) or the National Accredited Certification Scheme

3847uk/1/08/15/10 3847uk/1/08/15/1012 13

Reducer–HYDRA®GSPress

Presscase–HYDRA®GSPress

Tool case Case content

1Charger 4Adhesivetape2Expansionhead 54Pressheads:DN15/DN22/DN28/DN323Axialpressingtool 6Pipecutter

Conicalnipple–HYDRA®GSPress Pipecutter–HYDRA®GSPress

Reducershavealarge24°conewitharotatableunionnutandasmaller24°conewithmalethread.Theyareusedforreducingthediameterofbranchestotheexistingconnection.Thismeansitispossibletomakeconnectionstoadditionallinesusingsmallernominaldiameters.ThereductionfromDN20toDN16ismadedirectlywiththerotatableconnections,sincethesearecompatibleindiam-eterandthread.pMaterial:brasspO-ring:HNBR

Theconenippleshavea24°conewithmalethreadandareconnectedusingaswivelconnectioninordertocon-necttwoHYDRAGSstainlesssteelcorrugatedpipesofthesamediametertogether.pMaterial:brasspSealring:HNBR

6 54

2

3

Thecorrugatedpipecutterisusedforcuttingthecorruga-tedtubetotherequiredlength.

Dimensions[Nominaldiameter]

DN

Articlenumber

15to32 1158149

Dimensions[Nominaldiameterxconexthread]

DN

Articlenumber Weight

kg15x24°xM30x2 1198233 0.08322x24°xM30x2 1198234 0.09628x24°xM36x2 1198235 0.13032x24°xM48x2 1198236 0.233

Connectiontohose[Nominaldiameterxthread]

DN

ConnectiontoT-piece[Nominaldiameterxconexunionnut

thread]DN

Articlenumber

Weight

kg22xM30x2 25x24°xM36x2 1198231 0.19028xM36x2 32x24°xM48x2 1198232 0.397

Page 8: HYDRA® GS INSTALLATION MANUAL - Witzenmann · certificate must have been issued under either the Approved Code of Practise (ACoP) or the National Accredited Certification Scheme

3847uk/1/08/15/10 3847uk/1/08/15/1014 15

Expansionhead–HYDRA®GSPress

Theexpansiontoolisusedforcorrectingthedeformationofthecutedgecreatedwhencuttingthecorrugatedpipeandforexpandingthecorrugatedpipetothediameterre-quiredforassemblywiththefitting.Theexpanderheadiscompatiblewithcommerciallyavailableexpansiontongsorelectrohydraulicgunswith18°cones.

Dimensions[Nominaldiameter]

DN

Articlenumber

Expansionhead 15to32 1060722Expansiontool 15to32 1078856

2.2.HYDRA®GSClick

ThreadedBSPfixedtapermale–HYDRA®GSClick

ThreadedBSPparafixedfemale–HYDRA®GSClick

Dimensions[Nominaldiameterxthreadacc.toEN10226-1]

DN

Articlenumber Weight

kg153/8 1197725 0.181151/2 1197726 0.191223/4 1197727 0.322281 1197728 0.331

321¼ 1197729 0.440

Dimensions[Nominaldiameterxthreadacc.toEN10226-1]

DN

Articlenumber Weight

kg151/2 1197731 0.20221/2 1197732 0.33281/2 1197733 0.316223/4 1197734 0.302283/4 1197735 0.286323/4 1197736 0.420

ThreadedBSPfixedtapermaleacc.toDINEN10226-1areusedforconnectingthepliableHYDRAGSstainlesssteelcorrugatedpipestothefemalethreadconnectionsofvalves,fittingsorgassockets.pMaterial:brasspSealring:HNBR

ThreadedBSPparafixedfemaleacc.toDINEN10226-1areusedforconnectingthepliableHYDRAGSstainlesssteelcorrugatedpipestothemalethreadconnectionsofvalves,fittingsorgassockets.pMaterial:brasspSealring:HNBR

Page 9: HYDRA® GS INSTALLATION MANUAL - Witzenmann · certificate must have been issued under either the Approved Code of Practise (ACoP) or the National Accredited Certification Scheme

3847uk/1/08/15/10 3847uk/1/08/15/1016 17

T-piece–HYDRA®GSClick

Dimensions[Nominaldiameterxthreadacc.toEN10226-1]

DN

Articlenumber Weight

kg15 1197740 0.51722 1197739 0.91828 1197742 0.84932 1197748 1.54

22x22x15 1197738 0.86322x15x15 1197741 0.78328x28x15 1197744 0.79828x22x22 1197746 0.86528x22x15 1197747 0.81332x28x22 1197749 1.44632x28x15 1197751 1.342

TheT-piecesareusedasconnectionelementstootherlinesandthusmakeitpossibletoconnectadditionalconsumers.pMaterial:brasspSealring:HNBR

Soldersocket–HYDRA®GSClick

ConnectionBS746female–HYDRA®GSClick

Dimensions[Nominaldiameterxthreadacc.toEN10226-1]

DN

Articlenumber Weight

kgDN15Ø15 1197771 0.267DN22Ø15 1197772 0.282DN22Ø22 1197766 0.287DN28Ø22 1197767 0.267DN28Ø28 1197768 0.268DN32Ø22 1197769 0.344DN32Ø28 1197770 0.349

Dimensions[Nominaldiameterxthreadacc.toEN10226-1]

DN

Articlenumber Weight

kg22 1197763 0.37428 1197764 0.37032 1197765 0.462

ConnectionpartwithsolderlugsforconnectingpliableHYDRAGSstainlesssteelcorrugatedpipeswithcopperlines.pMaterial:brasspSealring:HNBR

Connectionpartforconnectingtogasmeterwith1"threadacc.toBS746pMaterial:brasspSealring:HNBR

Page 10: HYDRA® GS INSTALLATION MANUAL - Witzenmann · certificate must have been issued under either the Approved Code of Practise (ACoP) or the National Accredited Certification Scheme

3847uk/1/08/15/10 3847uk/1/08/15/1018 19

StraightCoupling–HYDRA®GSClick

Coppercompressionfitting–HYDRA®GSClick

Dimensions[Nominaldiameterxthreadacc.toEN10226-1]

DN

Articlenumber Weight

kg15 1197752 0.30722 1197753 0.51728 1197754 0.44932 1197755 0.581

Dimensions[Nominaldiameterxthreadacc.toEN10226-1]

DN

Articlenumber Weight

kgDN15Ø15 1197756 0.203DN22Ø15 1197757 0.316DN22Ø22 1197758 0.342DN28Ø22 1197759 0.313DN28Ø28 1197761 0.335DN32Ø22 1197760 0.416DN32Ø35 1197762 0.462

ConnectionparttoconnecttwoHYDRAGSstainlesssteelcorrugatedpipeofsamediameter.pMaterial:brasspSealring:HNBR

CompressionfittingforconnectingpliableHYDRAGSstainlesssteelcorrugatedpipewithcopperlines.pMaterial:brasspSealring:HNBR

2.3.HYDRA®GSPressundHYDRA®GSClick

BISMAT®-Flashpipeclamp–HYDRA®GS

TheBISMAT®-Flashpipeclampisusedforfasteningthecorrugatedpipestobuildingstructuresorsupportingstructures.pMaterial:galvanisedsteelpSealring:EPDM(black)

DN D D G B H h bxs Articlenumber

mm Inch mm mm mm mm15 20-23 ½" M8 54 39 23 r20x1.25 105254922 25-28 ¾" M8 59 44 26 r20x1.25 105255628 32-35 1" M8 65 51 30 r20x1.25 105256032 40-43 1¼" M8 74 60 34 r20x1.25 1052562

Caddyclip–HYDRA®GS

TheholdingloopisanalternativetotheBISMAT-Flashpipeclampandisalsousedforfasteningthecorrugatedpipestothebuildingstructureorsupportingstructures.pMaterial:galvanisedsteel

DN d d B A Articlenumber

mm Inch mm mm22 26.9 ¾" 60.3 31.8 105252128 33.7 1" 68.3 36.5 105252732 42.2 1¼" 77.8 41.3 1052528

Page 11: HYDRA® GS INSTALLATION MANUAL - Witzenmann · certificate must have been issued under either the Approved Code of Practise (ACoP) or the National Accredited Certification Scheme

3847uk/1/08/15/10 3847uk/1/08/15/1020 21

3. DIMENSIONING THE PIPELINE SYSTEM

3.1.Basisfordimensions

Thedesignandinstallationoflow-pressuregaspipeworkindomesticpremisesisspecifiedinBS6891(2ndfamilygas)andBS5482-1(3rdfamilygases),whilstpipeworkwithlargerboresizesandhigheroperatingpressureiscoveredinIGEM/UP/2LatestEdition.Strengthtesting,tightnesstestinganddirectpurgingofinstallationpipeworkarecoveredintheIGE/UP/1standards.

NaturalgasL NaturalgasH Propane

Operatingtemperature t °C 15 15 25Operatingpressure,absolute p Pa 103300 103300 106300

Netcalorificvalue HI,B kWh/m³ 8.6 10.6 26.8

Dimensioning with the software tool allows a free choice of entries.

3.2.Preliminarydimensioningusingtable

Whenusingthetable,thepressurelossesofthecomponentsarereadinrelationtotheload.Thepressurelossoftheentirepipelinesystemiscalculatedbyaddingupthepressurelossesalongthecourseofthepipeline.Asarule,thetablesapplytoindividuallines.Whenthereareseveralconsumers,calculatebackwardsfromthem.Fromthebranchonwards,calculatebytakingthetotaloftheindividualloadings,wherebyitisalsopossibletotakeintoaccountasimultaneityfactorforreducingtheoverallload.Thepressurelossesofthestraightcorrugatedpipesarespecifiedbelowpermetre.Bendsandconnectionpartsinherentinthesystemaretakenintoaccountasadditionalpipelength.pR=R·(lR+lz) linm

Forallothercomponents(flowmonitor,gasmeter,applianceconnectionfitting,etc.),usetheinformationfromthemanufacturers.(pGS,pZG,pGA)Theheightdifferencebetweenthestartofthepipelineatthegaspressurecontrolinstallationandtheinstallationconnectionistakenintoaccountacc.tothefollowingformula.pH=(-4)·H Hinm

Thepressurelossinthepipelineis:p=pR+pGS+pZG+pGA+pH

Stripearthband-HYDRA®GS

Thestripearthingclipisusedforpotentialequalisationforthebuildinginstallation.pMaterial:stainlesssteel(V2A)

Type forcorrugatedpipediameterDN

Articlenumber

9271 15to32 1051809

Coroplastadhesivetape–HYDRA®GS

Type Lengthxwidth Articlenumber

PVC302 10mx25mm 1147254

Page 12: HYDRA® GS INSTALLATION MANUAL - Witzenmann · certificate must have been issued under either the Approved Code of Practise (ACoP) or the National Accredited Certification Scheme

3847uk/1/08/15/10 3847uk/1/08/15/1022 23

3.3.Pressurelossesinthecorrugatedpipelinedepending on the nominal load

3.3.1. Natural gas LPressurelossincorrugatedpipelinesfornaturalgasL(15°C,20mbar,8.6kW/m³)

RPa/m

DN[mm]15 22 28 32

0.4 2 4 8 200.6 5 10 250.8 3 6 11 291.0 7 13 331.2 4 14 361.4 8 16 391.6 9 17 421.8 5 18 452.0 10 19 482.5 6 12 21 543.0 7 13 24 603.5 14 26 654.0 8 15 28 705 9 17 31 796 10 19 34 877 11 20 37 958 12 22 40 1029 13 23 43 10810 14 24 45 11512 15 27 50 12714 16 29 54 13816 17 31 58 14820 20 35 66 167

Pressurelossesoftheconnectionparts,additionallengthslZtotheoverallpipelengthforsystemcomponents

DN Pressurelossesinmetres

90°bends Hoseconnection Tstraight Tbranch

16 0.15 0.2 0.4 0.520 0.2 0.3 0.6 0.925 0.25 0.2 0.4 0.832 0.3 0.2 0.4 1.3

3.3.2. Natural gas HPressurelossincorrugatedpipelinesfornaturalgasH(15°C,20mbar,10.6kW/m³)

RPa/m

DN[mm]15 22 28 32

0.4 3 5 10 240.6 6 12 300.8 4 8 14 361.0 9 16 401.2 5 18 441.4 10 19 481.6 6 11 21 521.8 12 22 552.0 7 13 23 592.5 8 14 26 663.0 9 16 29 733.5 17 32 804.0 10 18 34 865 12 21 38 976 13 23 42 1077 14 25 46 1168 15 27 49 1259 16 28 53 13310 17 30 56 14112 18 33 61 15614 20 36 67 16916 21 39 72 18220 24 43 81 205

QN

Bv

alue

sin

kW

QN

Bv

alue

sin

kW

0 5 10 15 20

20

40

60

80

100

120

140

160

180

200

Pa/m

DN15 DN28DN22 DN32

0 5 10 15 20

20

40

60

80

100

120

140

160

180

200

Pa/m

DN15 DN28DN22 DN32

Pressurelossesoftheconnectionparts,additionallengthslZtotheoverallpipelengthforsystemcomponents

DN Pressurelossesinmetres

90°bends Hoseconnection Tstraight Tbranch

16 0.15 0.2 0.4 0.520 0.2 0.3 0.6 0.925 0.25 0.2 0.4 0.832 0.3 0.2 0.4 1.3

QN

B/k

W

QN

B/k

W

Page 13: HYDRA® GS INSTALLATION MANUAL - Witzenmann · certificate must have been issued under either the Approved Code of Practise (ACoP) or the National Accredited Certification Scheme

3847uk/1/08/15/10 3847uk/1/08/15/1024 25

3.3.3. Propane gasPressurelossincorrugatedpipelinesforpropane(25°C,50mbar,26.8kW/m³)

RPa/m

DN[mm]15 22 28 32

0.4 5 9 17 430.6 6 12 21 540.8 7 13 25 631.0 8 15 28 711.2 9 17 31 791.4 10 18 34 851.6 11 20 36 921.8 21 39 982.0 12 22 41 1042.5 14 25 46 1173.0 15 27 51 1293.5 16 30 55 1414.0 18 32 60 1515 20 36 67 1716 22 40 74 1887 24 43 80 2058 25 46 86 2209 27 49 92 23510 29 52 97 24912 31 57 107 27414 34 62 116 29816 36 67 125 32120 41 75 141 362

3.4.Examplecalculation

pCombinationwaterheater,result:pressureloss<300PapNominalload:18kWpApplianceconnectionfitting,straightpattern:20PapHeightdifference:8.9m-35PapSelectedcrosssection:DN2266PapPiperesistance:6Pa/m(Table1naturalgasL)pPipelength:9.9mpStraightT-piece:(Tab.14lZ)0.6mpThreadedconnectionreduced:0.3mp90°bend:0.2m

QN

Bv

alue

sin

kW

0.6

2.4

0.4

3.0

0.6

0.6

1.2

0.3

0.4

3.2

2.8

7.1

Line12

Line21

Line20

Line10

GS 4 36 Pa

KWH 260 Pa18 kW15D 20Pa+8.9m -35PaDN22 66Pa6Pa/m9.9+0.6+0.3+0.2=11.0m

H 155 Pa9 kW15E 10Pa+5.4m -21PaDN15 38Pa5Pa/m6.4+0.5+0.2+0.45=7.55m

33 kW 128 PaDN28 9Pa6Pa/m1.0+0.25+0.2=1.45m

GDS 224 Pa6 kWGSD 15Pa+2.5m -10PaDN15 10Pa2.5Pa/m3.9+0,5+0,2+0,45=3.25

24 kW 209 PaDN22 81Pa10Pa/m7.0+0.9+0.2=8.1m

33 kW 54 PaDN28 18Pa6Pa/m2.1+0.5+0.4=3.0m

Line11

Line30

0 5 10 15 20

20

40

60

80

100

120

140

160

180

200

Pa/m

DN15 DN28DN22 DN32

QN

B/k

W

Page 14: HYDRA® GS INSTALLATION MANUAL - Witzenmann · certificate must have been issued under either the Approved Code of Practise (ACoP) or the National Accredited Certification Scheme

3847uk/1/08/15/10 3847uk/1/08/15/1026 27

3.5.PressurelosscalculationwithsoftwaretoolFirst,openthe"HydraGS.xlt"filewithadouble-click.Important:Macrosmustbeactivated.Tofillintheemptydialoguebox,clickoneofthetwobuttons"Createnewproject"or"Editproject".Adialogueboxappearswhichhasthesamestructure.Ifadialogueboxiscalledupwhichhasalreadybeenfilledin(*.xls)thenthe"Createnewproject"buttondeletesallpreviousentries.

Selectionofthegastypeusingthedrop-downmenuandtheoperatingconditionsintheheadofthetable.Theproposedvaluesforgastemperature,connectionpressure,permissiblepressurelossandnetcalorificvaluecanbeoverwritten.

pEntryofthepipelineroutingstartingfromthehouseconnectionincolumn2.Select"Continue"ifsubdividingintoseveralsections.Select"Branch"ifabranchfollows.Ifthelineendsattheconsumer,enter"End"andthenominalload(column5).Thelinesarenumberedautomatically(columns1,3,4).Entriesareonlypossibleinthewhitefields.

pIncolumn6,enterthedifferenceinheightbetweeneachconsumerandthehouseconnection.

7

2

8

3

9

4

5

6

Page 15: HYDRA® GS INSTALLATION MANUAL - Witzenmann · certificate must have been issued under either the Approved Code of Practise (ACoP) or the National Accredited Certification Scheme

3847uk/1/08/15/10 3847uk/1/08/15/1028 29

pEnterthenominaldiameterincolumn7.Thesubsequentlineshouldonlybeonenominaldiametersmallerthanthepreviousone.

pAftera"branch"isenteredincolumn2,twosubsequentlinesaredisplayed.Incolumn8forthefirstfollow-online,nowselectwhethertheflowthroughtheT-pieceisstraightorasaT-branch.Thesecondfollow-onlineisalwaysaT-branch.Adiameterreductionofthefollow-onlineisautomaticallytakenintoaccount.

pColumn9containstheextendedpipelengthoftheline.pThenumberof90°bendsisenteredincolumn10.However,itisalsopossibletoenterfrac-

tions(e.g.30°=0.33).p"Connections"incolumn11referstoallstartingorfinishingpiecesonthehose,irrespective

ofwhethertheyarethreadedorconeconnections.Inthecaseofreducers,theconnectormustalwaysbeenteredinthelinewiththesmallernominaldiameter.2connectionsmustbecountedforahoseextensionbyaconescrewconnection.

pThepressurelossesanddescriptionsofcomponentsfromothermanufacturerscanbeen-teredincolumns12and13.

pColumn14showsthepressurelossoftheindividuallineandcolumn15showsthetotalfortheparticularconsumer.Iftheresultincolumn15islargerthanthepermissiblepressurelossthentheresultisshowninred.Inthiscase,itisnecessarytoincreasethenominaldiameterincolumn7from16to20forline2-1.Alternatively,however,changingthetypeandnumberofinstalledpartscanproduceasuccessfulresult.

Oncethedialogueboxhasbeenclosed(cross),thedialogueboxallowingsavingandprintingwithnormalWindowsfunctionsisactivatedagain.Theentriescanbeeditedagainusingthe"Editproject"button.

Advantagesofthesoftwaretoolcomparedtousingthetable:pThepressurelossvaluesofthelinesareonlyroundedoffattheendofthecalculation.This

makestheresultmoreaccurate.pThepipelinecrosssectionscanbeoptimisedveryquickly.Theresultisdisplayedimmediately

aftereachentryiscompleted.pDialogueboxesthathavealreadybeencreatedcanbemodifiedforsimilarprojects.pItispossibletoenterthenetcalorificvalueasrequired,thusallowingoptimumadaptationto

theparticulargassupply.Thesameappliestotheoperatingconditionofthegas.

7

Page 16: HYDRA® GS INSTALLATION MANUAL - Witzenmann · certificate must have been issued under either the Approved Code of Practise (ACoP) or the National Accredited Certification Scheme

3847uk/1/08/15/10 3847uk/1/08/15/1030 31

4.1.Assemblyprocedure

4. ASSEMBLY HYDRA® GS PRESS

Step 1: Prepare the hose

Step 3: Expand the corrugated pipe

Theinitialpieceoftherolled-upHYDRAGScorrugatedpipemustalwaysbecutoffwithacleancutpriortouse.Measurethesuitablepipelength.

Nowtheendofthecut-to-lengthpipemustbeexpandedinordertoallowtheconnectionpartstobefitted.

Todothis,theexpansionheadfromthetoolcaseisscrewedontostandardexpandertongs

Step 2: Cut the corrugated pipe to length

Usethecorrugatedpipecuttertocutthesheathedpipetolength.Thecutmustbelo-catedinthegrooveofacorrugation.Turnthepipecutterinonedirectionandslowlytightenthepressurerolleraftereachturn.Important:Tighteningtoomuchleadstoirregularcutsanddeformations.Avoidkinkingandtearingthecorrugatedpipeafteranincompletecut.

Theclosedtoolispushedintotheendofthecorrugatedpipeuptothecollar.Theexpandertongisopenatthisstage.

Operate(close)thetongonceuptothestoppoint.Removetheexpansionhead.

Page 17: HYDRA® GS INSTALLATION MANUAL - Witzenmann · certificate must have been issued under either the Approved Code of Practise (ACoP) or the National Accredited Certification Scheme

3847uk/1/08/15/10 3847uk/1/08/15/1032 33

Step 5: Carry out visual inspection.

Theexpandedcorrugatedpipeispushedovertheconnectionpart.

Thenecessaryinsertiondepthhasbeenrea-chedwhentheyellowPEsheathingcanbeseenintheroundviewingholesofthecon-nectionpart.

Thecorrugatedpipethenmakesfirmmetal-on-metalcontactwiththeconnectionpart.

Right:Theviewingwindowiscompletelyfil-ledbythecorrugatedpipe.

Wrong:Inadequateinsertiondepth!

Thecutedgeofthecorrugatedpipemustneverbevisibleintheviewingwindow.

Step 4: Fit the connection part onto the press head; lock the pull rod with the bayonet socket

Selecttheappropriatepressheadfromthetoolcasetomatchthediameterofthefitting.Pushthepressheadfromthefrontintotheconnectionfittingwiththethreadedpartfore-most.

Pushthepressheadasfaraspossibleintothefitting.

Theninsertthepressheadasfaraspossibleintotheaxialpressingtool.Turn90°clock-wiseinthechuckoftheaxialpressingtooltolockthepresshead(bayonetsocket).

Brieflyoperatetheaxialpressingtooltosecuretheconnectionpartonthecentringpieceoftheaxialpressing

Page 18: HYDRA® GS INSTALLATION MANUAL - Witzenmann · certificate must have been issued under either the Approved Code of Practise (ACoP) or the National Accredited Certification Scheme

3847uk/1/08/15/10 3847uk/1/08/15/1034 35

Step 8: Remove the press head

Step 9: Seal the connection part

Removethepressheadbypressingtheunlockingmechanismontheendandbyturningit90°anticlockwise

Step 6: Install the connection part

Step 7: Trigger the return stroke

Thebattery-operatedaxialpressingtoolisstartedatthepushofabutton

Toremovethepresshead,releasetheslideontherearofthetool

Thepressheadthenmovesbacktoitsorigi-nalposition

Afteramaximumof8seconds,thepressheadwillhaveexpandedtheconnectionpart.Theaxialpressingtoolthenswitchesoffautomatically,anditcansimplybepulledoutofthecorrugatedpipe.

Wrapwithadhesivetape,beginningonthehoseandworkingtowardsthefitting.

Overlapthelayersbyapprox.0.5cm.Makesuretherearenocreases.

Wraptwolayersoftapearoundthehoseandthefittinguptothenut.

28 mm

5 mm

Page 19: HYDRA® GS INSTALLATION MANUAL - Witzenmann · certificate must have been issued under either the Approved Code of Practise (ACoP) or the National Accredited Certification Scheme

3847uk/1/08/15/10 3847uk/1/08/15/1036 37

5. ASSEMBLY HYDRA® GS CLICK

5.1.Assemblyprocedure

Step 1: Prepare the hose

Step 3: Assemble the connection part

Theinitialpieceoftherolled-upHYDRAGScorrugatedpipemustalwaysbecutoffwithacleancutpriortouse.Measurethesuitablepipelength.

Removesheathfromthefirst6corrugations,seesketch.

Step 2: Cut the corrugated pipe to lengthUsethecorrugatedpipecuttertocutthesheathedpipetolength.Thecutmustbelo-catedinthegrooveofacorrugation.Turnthepipecutterinonedirectionandslowlytightenthepressurerolleraftereachturn.Important:Tighteningtoomuchleadstoirregularcutsanddeformations.Avoidkinkingandtearingthecorrugatedpipeafteranincompletecut.

Loosenscrewfittinglightlybyhand.

Pushtheendofthehosefirmlyintothefitting.Therewillbeanpositiveclick.

Tightenthefittingusingawrench.Thedis-tancebetweenthebrasspartsofthefitting(aftertightening)shouldbe0.5mmmax.

Wrapwithadhesivetape,beginningonthehoseandworkingtowardsthefitting.

Overlapthelayersbyapprox.0.5cm.Makesuretherearenocreases.

Wraptwolayersoftapearoundthehoseandthefittinguptothenut.

28 mm

5 mm6 corrugations

Step 4: Seal the connection part

Page 20: HYDRA® GS INSTALLATION MANUAL - Witzenmann · certificate must have been issued under either the Approved Code of Practise (ACoP) or the National Accredited Certification Scheme

3847uk/1/08/15/10 3847uk/1/08/15/1038 39

6.1.ValidforHYDRA®GSPressandHYDRA®GSClick

Externalsystemsandfittingsmayonlybeconnectedtogetherusingscrewfittingswithstandardisedthreadora24°cone.

TighteningtorqueforHYDRA®GSPress

ScrewconnectionsforHYDRAGSPressshouldbetightenedwiththetoleratedtorquesasspecifiedinthefollowingtable.

NominaldiameterofcorrugatedpipeDN

Tighteningtorqueforunionscrewconnection

[Nm]

15 30±1022 30±1028 35±1032 50±10

6.2.ValidforHYDRA®GSPressandHYDRA®GSClick

Minimumbendingradii

Whenbendingcorrugatedpipes,makesurethebendingradiiarenotlessthantheminimumbendingradiispecifiedinthefollowingtable.

NominaldiameterofcorrugatedpipeDN

Minimumbendingradius

mm15 2522 3028 4532 60

7. GENERAL NOTES ON INSTALLATION

7.1.Generalinstructions

pStoreallHYDRAGSPresscomponentsintheiroriginalpackinginadryplace.pMakesurethatthecomponentsarestoredatroomtemperaturedirectlybeforebeinglaid.pIftheHYDRAGSstainlesssteelcorrugatedpipesweresubjectedtolowtemperatures,store

thematroomtemperatureuntiltheythemselveshaveroomtemperature.pBeforefitting,makesurethatsufficientHYDRAGSsystemcomponentsareavailableforthe

requiredlengthanddiameters.pInstallHYDRAGSstainlesssteelcorrugatedpipesinsuchawaythattheyareprotectedfrom

mechanicaldamage.pDuringfitting,avoidkinking,crimping,over-bending,over-stretchingortwistingtheHYDRAGS

stainlesssteelcorrugatedpipe.Alsoavoidcontactwithsharpobjects.Renewdamagedparts.pAvoidimpairingthefreeflowcross-sectionofHYDRAGSstainlesssteelcorrugatedpipes.pMakesurethatnoforeignbodiesenterthecorrugatedpipe.pHYDRAGSstainlesssteelcorrugatedpipesmaynot,underanycircumstances,beusedas

flexibleconnectionsforapparatus(forexample,insteadofgashoses).pPriortotakingacompletedinstallationintooperation,theentireinstallation

mustbecheckedinaccordancewiththetechnicalcodesofpractice.pFittingsandcomponentsmustbearrangedandsupportedsothattheycannottransmitany

impermissibleforcesanddeformationsontothepipesystem.pCorrugatedpipelinesdonotprovideasufficientlyrigidconnection.pThesealingsurfacesofconnectionpartsmustremainundamagedduringlayingpConnectionpartsmustbeinstalledwheretheyareeasilyaccessiblepThenumberofconnectionpartsmustbereducedtotheminimumnecessarypInnerpipesmustbelaidinaccordancewiththeapplicablecodesofpractice.pChargethebatterypriortoinitialusepPressheadsshouldnotbegreased

6. ASSEMBLY ON PARTS OUTSIDE THE HYDRA® GS GAS INSTALLATION SYSTEM

Page 21: HYDRA® GS INSTALLATION MANUAL - Witzenmann · certificate must have been issued under either the Approved Code of Practise (ACoP) or the National Accredited Certification Scheme

3847uk/1/08/15/10 3847uk/1/08/15/1040 41

7.2.HYDRA®GSFirebehaviour

HYDRAGSstainlesssteelcorrugatedpipeshavebeentestedfortheirfirebehaviourinaccor-dancewithEN13501-1andhavebeenclassifiedasB-S1-D2.ThePE-sheathingdoesnotconstituteaninsulatinglayerasdefinedbyBS4102.

7.3.Potentialequalisation

Gaspipelinesmaynotbeused(fullyorinpart)asprotectiveoroperationalearthsorasprotec-tiveearthconductorsinelectricalsystems.Gaspipelinesmaynotbeusedasalightningcon-ductorsorearthingsinlightningprotectionsystems.Themetalinnerpipingofeachbuildingmustbeconnectedtotherelevantequipotentialequalisationsystem.PleaseobservealsoBS6891,8.6andBS5482-1,12.3.3.

1Stripearthingcliponhexagonprofile2 HYDRAGScorrugatedpipe3 HYDRAGSthreadednipple

1Stripearthingcliponhexagonprofile2 HYDRAGScorrugatedpipe3 HYDRAGSunionnutnipplewithadapter

2

3 3

2

7.4.Fasteningandfasteningdistances

Gaspipelinesmaynotbeattachedtootherpipelines,normaytheybeusedassupportsforotherpipelinesandloads.Theymustbearrangedsothatdripsandcondensationfromotherpipelinescannothaveanyeffectonthem.

Dependingonthemechanicalstrength(tensilestrength)oftheirpipeconnections,theymustbeattachedtocomponentswithanadequatestructuralstrengthbymeansofpipebrackets.Thesupportingpartsofthepipebrackets(e.g.pipeclamps/clips,bolts)mustbemadefromnon-flammablematerials.Thefollowingtableprovidesguidancevaluesforfasteningdistancesoflaidpipelines.

Itisessentialtocomplywiththerecommendedfasteningdistances:

NominaldiameterDN

Recommendedfasteningdistance

horizontal vertical Bendm m m

15 1.00 2.50 0.2522 1.25 2.50 0.3028 1.50 2.50 0.4032 1.75 2.50 0.45

Plasticplugscanbeusedifthemechanicalstrengthofthepipelinewillnotbeimpairedincaseoffireattemperaturesupto650°C.Inpipelineswithpipeconnectionswhichnolongerguaranteetherequiredmechanicalstrength(tensilestrength)whenexposedtotemperaturesupto650°C,itisnecessaryfortheplugsusedtobeabletowithstandthesetemperatures(e.g.metalplugs).Furthermore,solidorcomparablestructuralcomponentsarerequiredinthebuildingforthefasteningpoints.

Page 22: HYDRA® GS INSTALLATION MANUAL - Witzenmann · certificate must have been issued under either the Approved Code of Practise (ACoP) or the National Accredited Certification Scheme

3847uk/1/08/15/10 3847uk/1/08/15/1042 43

8. PROTECTION AGAINST CORROSION OR DAMAGE

OnlyHYDRAGSBISMAT®-FlashpipeclampsandHYDRAGSCaddyholdingloopscertifiedinaccordancewithBSEN15266maybeusedtofastentheHYDRAGSstainlesssteelcorrugatedhosesystem.

Thepipeclampsandholdingloopsarepartoftheoverallapprovedsystem.HYDRAGSstain-lesssteelcorrugatedpipesmaynotbeinstalledusingotherpipeclamps.BISMATFlashisascrew-inpipeclampmadefromelectrolyticallygalvanisedsteelwithanacousticinsulationinsertmadefromblackEPDMrubberandaquickfastener.Themaximumpermittedloadiscertifiedacc.toRAL-GZ655/Aandis260N.

Inordertoguaranteeanoptimumdurationoffireresistance,useplugsandthreadedrodswhosefire-resistancepropertieshavebeentested(dimension≥M8orM10,strengthclass≥4.6).

Avoidanycontactbetweenthegaspipelinesandacids,alkalis,saltsorothercorrosivesub-stances.Inaddition,alsoavoidcontactbetweenthegaspipelinesandaggressivechemicalcompoundswhichcanleadtocorrosionofstainlesssteel.

Shouldcontactoccurnevertheless,removethechemicalresiduesthoroughlywithoutdelay.CheckthePEsheathingofthegaspipelinefordamage.IfthePEsheathingisundamaged,itwillprotectthestainlesssteelcorrugatedpipeagainstcorrosion.Ifthereisdamage,renewtheaffectedsection.

Avoidusingcompoundscontainingchloride,e.g.fordetectingleaks.Contactwithsuchcom-poundscancausetheHYDRAGSstainlesssteelcorrugatedpipestocorrode.

Atallintermediatestagesbetweenmanufactureanduse,storethegasketsinaccordancewiththerecommendationsofISO22301.

Comply with the following points:a)Thestoragetemperatureshouldbebelow25°C,preferablybelow15°C.b)Thegasketsshouldbeprotectedagainstlight,inparticularagainststrongsunlightandartifi-

ciallightwithahighultravioletproportion.c)Thegasketsshouldnotbestoredinaroomcontainingsystemsthatcan

generateozone,e.g.mercuryarclampsordeviceswithhigh-voltageelectricitywhichcancausesparkinganddarkelectricaldischarges.

d)Thegasketsshouldbestoredwithoutstress,i.e.withouttension,pressureorotherdeforma-tions;forexample,theyshouldnotbehungup.

e)Thegasketsshouldbekeptclean.

Insertthepipe. Pushtheclampclosedbyhand.

Done!

9. RECOMMENDATIONS FOR STORING THE GASKETS

Page 23: HYDRA® GS INSTALLATION MANUAL - Witzenmann · certificate must have been issued under either the Approved Code of Practise (ACoP) or the National Accredited Certification Scheme

3847uk/1/08/15/10 3847uk/1/08/15/1044 45

10. REPAIR METHODS

10.1.DamagetotheHYDRA®GSstainlesssteelcorrugatedpipes

The flexible corrugated pipes must be renewed without fail if:pthereisvisibledamagetothePEsheathing.pthecorrugatedpipehasbeenbenttootightly,leavingakink.pthecorrugatedpipehasbeendamagedbyasharporpointedobject.pthecorrugatedpipehasbeensignificantlycompressed.pthereisapressurelossinthehoseassembly

Renewaloftheentirecorrugatedpipelengthisrecommendedforsafetyreasons,inordertoavoidhavingscrewconnectionsincavities.Inaddition,inmostcasesthisprocedureismoreeconomicalthanrepairingonlypartofasection.Ifasectionistoberepaired,itispossible,dependingonthelengthofthepipelineremaining,toremovethedamagedpartandconnectthepartsleftusingHYDRAGSscrewconnections.Iftheremaininglengthsareshort,itispossibletouseapipelinesectionwithtwoHYDRAGSscrewconnectionsbetweenthetworemainingsections.Note:Aleaktestmustalwaysbecarriedoutaftereachrepair.


Recommended