+ All Categories
Home > Documents > HydroBall Operational Manual

HydroBall Operational Manual

Date post: 07-Dec-2015
Category:
Upload: postboxsg
View: 231 times
Download: 3 times
Share this document with a friend
Description:
Condenser Auto Tube Cleaning
Popular Tags:
12
Telephone +65 6338 8033 24-hr Line +65 9191 9555 Website www.hbt.com.sg Email [email protected] Address Joo Chiat Complex Blk 1 Joo Chiat Road #04-1019 OPERATIONAL MANUAL FOR HYDROBALL SYSTEM
Transcript
Page 1: HydroBall Operational Manual

Telephone +65 6338 8033

24-hr Line +65 9191 9555

Website www.hbt.com.sg

Email [email protected]

Address Joo Chiat Complex Blk 1 Joo Chiat Road #04-1019

OPERATIONAL MANUAL FOR

HYDROBALL SYSTEM

Page 2: HydroBall Operational Manual

Company Reg No. 200300791R

© All Rights Reserved

Private and Confidential 1

Singapore 420001

1 Description of the HydroBall System and its Components

1.1 Components of HydroBall System

Hydroball System uses sponge balls to prevent scaling & fouling inside the heat exchanger

tubes of the water-cooled condenser or chiller.

It consists of 3-way motorised valve, four hand valves, two swing check valves, Ball Catch,

Ball Station, flow switch and Programmable Logic Controller (PLC).

There are four linkage pipes: Water Supply Pipe (WSP), Ball Supply Pipe (BSP), Water

Return Pipe (WRP) & Ball Return Pipe (BRP).

1.1.1 Valves

HydroBall System consists of a 3-way motorised valve, four hand valves and 2 swing

check valve.

There are 4 hand valves along each of the 4 pipes Water Supply Pipe (WSP), Ball Supply

Pipe (BSP), Water Return Pipe (WRP) & Ball Return Pipe (BRP).

WSP

BSP

BRP

WRP

Page 3: HydroBall Operational Manual

Company Reg No. 200300791R

© All Rights Reserved

Private and Confidential 2

Hand valves are used for isolating the HydroBall System during maintenance such as

replacement of sponge balls or servicing of valves.

1.1.2 Water Flow Control Switch

The Water Flow Control Switch is mounted along the horizontal section of

condenser water supply pipe (CWS). It is activated whenever there is water flowing in

the condenser supply pipe and the Programme Logic Control will activate whenever

water flow control switch is activated.

1.1.3 Programmable Logic Controller

The Programmable Logic Controller (PLC) serves to operate, control and

monitor the system. It signals the 3-way motorised valve to allow the sponge balls to

complete the cleaning cycle from the Ball Station to the condenser tubes and back to the

Ball Station.

The operation modes “automatic” or “manual” can be selected via a selector switch. It is

set default at the “automatic” mode. The cleaning system is continuously controlled by

the control system. All sequences to be started are controlled by the PLC.

3-way motorised valve Hand valve Check valve

Page 4: HydroBall Operational Manual

Company Reg No. 200300791R

© All Rights Reserved

Private and Confidential 3

1.1.4 Cleaning Balls

The sponge balls which are made rubber foam, are soft, elastic and non-abrasive. They

should have approximately the same density as water.

It is important to use the correct type and size for effective cleaning. The diameter of the

cleaning balls should be slightly bigger than the internal diameter of the condenser tubes

for effective removal of the microfilm from the inner surface of the heat-exchanger tubes

and to prevent scaling deposits from accumulating.

1.2 Working Principle of HydroBall System

When the PLC signals the 3-way motorised valve to open at position 1 (POS1), please refer

to page cooling water rushes into the Ball Station via WSP forcing the cleaning balls to

enter the BSP, into the condenser supply pipe before passing through the condenser tubes to

scour off any fouling deposits along these tubes.

After leaving the condenser tubes, the sponge balls get collected at the Ball Catch along the

Condenser Return Pipe. PLC then signals 3-way motorised valves to open at position 2

(POS2). The cycle is completed when the balls get sucked back into the Ball Station. PLC

then signals 3-way motorised valves to open at position 3 (POS3) and it is ready for the

next cleaning cycle at the interval of 30 mins.

Page 5: HydroBall Operational Manual

Company Reg No. 200300791R

© All Rights Reserved

Private and Confidential 4

2 Operation of the HydroBall System

2.1 Recommended Practice

For best results in preventing the formation of scales and fouling deposits, HydroBall Technics

recommends the following:

Operate the HydroBall system in tandem with the chiller.

Change the sponge ball every 6,000 cycles.

The number of sponge balls should be put into the Ball Station is based on 15% to 30%

of number of condenser tubes,

2.1.1 Basic positioning of component

All components have been installed as per layout.

Control panel Main Switch “On”

Selector Switch in “Automatic” Position

Ball Station Sponge balls of the correct type and size are in Ball

Station

Hand Valves All the 4 manual ball valves are in open position.

Electrical Wiring All wires have been properly connected and tested

by the contractor. Ensure there is no loose electrical

wire or cable.

2.2 Operational Sequence

Run the central air-conditioning system.

Make sure the Pressure Release Valve is shut.

Page 6: HydroBall Operational Manual

Company Reg No. 200300791R

© All Rights Reserved

Private and Confidential 5

Open the manual ball valves (hand valves) one by one slowly and carefully.

Switch on the power supply to the PLC, turn to “Auto” mode for the HBT system to

begin operation.

3-way motorised valve is activated by the PLC Controller to allow cooling water to flow

from the condenser water supply pipe into the Ball Station. The water pressure from the

condenser supply pipe pushes the cleaning balls from the Ball Station into the condenser.

As the cleaning balls leave the condenser, they get trapped within the aperture funnel of

the Ball Catch. When the 3-way motorised valve change to position 2, the cleaning balls

leave the Ball Catch to return to the Ball Station via the Ball Return Pipe.

The cleaning balls remain in the Ball Station until the next cleaning cycle.

The routine cleaning operation should be repeated after 30 mins by presetting the

cleaning cycle interval at the Programme Logic Controller.

Page 7: HydroBall Operational Manual

Company Reg No. 200300791R

© All Rights Reserved

Private and Confidential 6

2.3 Replacements of Sponge Balls

Control panel Switch off the main power supply

Valves Shut all the 4 manual ball valves

(hand valves)

Pressure Release

Hose at Ball Station

Open the pressure release valve slowly.

(Position pressure release pipe carefully to avoid wetting the

floor. If a pail is available, use it to collect the water released

from the ball station)

Ball Station cover Loosen the bolts to remove the cover of the Ball station.

Sponge Balls Remove all the used balls, and replace them with new ones.

After removing the sponge balls, check diameter of sponge balls and see if there is any wear and tear. Soak

the new cleaning balls sufficiently to remove the tiny air pockets within them.

Ball Station cover After replacing the sponge balls, put back the transparent

cover of the Ball Station and tighten the bolts. The bolts

should be tightened evenly.

Page 8: HydroBall Operational Manual

Company Reg No. 200300791R

© All Rights Reserved

Private and Confidential 7

Pressure Release

Mechanism at Ball

Station

Check to make sure the pressure release valve is in close

position.

Valves Open all the 4 manual ball valves (hand valves)

Pressure Release or

venting Mechanism

at Ball Station

Open the pressure release valve slowly and carefully to allow

the trapped air pockets to escape. Then close the valve

gently.

Control panel Switch on the main power supply and select the “automatic”

operation mode.

The cleaning system will then start automatically.

Page 9: HydroBall Operational Manual

Company Reg No. 200300791R

© All Rights Reserved

Private and Confidential 8

3 Operating Modes of Programmable Logic Controller

The system can either be set to Auto or Manual Mode depending on your operating requirements. Auto

Mode gives you a hassle free operation while Manual Mode gives you certain flexibility in controlling the

system.

Power Indicator

• Power Indicator turns ON when the system power is ON

• Power Indicator turns OFF when the system power is OFF

Position Indicator (SEND, RETURN and REST)

• 3 Lighted Pushbutton Switch turn ON when the system power is ON

• 3 Lighted Pushbutton Switch turn OFF when the system power is OFF

• Lighted Pushbutton Switch blinks while the respective valve is turning to its position

• Lighted Pushbutton Switch stays ON when the respective valve reach its position

• 3 Lighted Pushbutton Switch blink at the same time when the valve did not reach its position

Auto/Manual Selector

• Select to Auto to run in Auto Mode

• Select to Manual to stop the Auto Process:

• press SEND pushbutton to turn the valve to position 1

• press RETURN pushbutton to turn the valve to position 2

• press REST pushbutton to turn the valve to position 3

Counter Indicator

• Display the total cleaning cycle count

Reset Button

• To reset the cycle count to zero

Page 10: HydroBall Operational Manual

Company Reg No. 200300791R

© All Rights Reserved

Private and Confidential 9

3.1 Auto Mode

The system starts and stops continuously in the preset sequence. The cleaning procedure is started

as the following:

Switch on to operational “Automatic” Position by turning the control knob on the panel

to “AUTO”

The manual control buttons to control position of the 3-way motorised valve will be

disabled under the Auto Mode

The automatic mode is the default-operating mode under normal condition. The system will begin

operating automatically when the chiller starts running.

3.2 Manual Mode

The Position 1, Position 2 and Position 3 of the 3-way motorised valve can be selected using the

relevant push buttons. Signal lights indicate the on/off status of the position.

The “manual” mode is selected when:

Testing and Commissioning

Replacement of sponge balls

Re-starting after lengthier non-operational periods

The “manual” mode is not a default operating mode and shall only be used to switch the cleaning

system into the basic condition for maintenance and testing purposes.

The system is set to Manual Mode by turning the control knob to “MANUAL”.

Page 11: HydroBall Operational Manual

Company Reg No. 200300791R

© All Rights Reserved

Private and Confidential 10

4 Operational Troubleshooting

Possible Problems Solution

Programme Logic

Controller

No supply voltage to panel Check main supply

Clear short circuit

Check relay and fuse

(Use a meter to check if there’s

electric current)

- Connecting pipelines

WSP, WRP, BSP & BRP

Leaking of water Replace leaking components or

worn out gaskets between flanges

joints. Tighten joints. For threaded

joints, used proper sealant or tape.

- Valves Flow Switch not activated

3-way motorised valve is partially

jammed or failed to open fully

Check if chiller is in operation

May need to rectify or change valve

Page 12: HydroBall Operational Manual

Company Reg No. 200300791R

© All Rights Reserved

Private and Confidential 11

5 Schematic of HydroBall System


Recommended