HYDROLOGIC &HYDRAULIC REPORT
IH 610 W/ US 59 S INTERCHANGESOUTH DRAINAGE ELEMENTS
CSJ: 0271-17-146
HARRIS COUNTY, TEXAS
Prepared for:
&
VOLUME 1
H & H RESOURCES, INC. (F-3678)
DECEMBER 2013
7/26/2019 Hydrologic and Hydraulic Report TxDOT
2/272
7/26/2019 Hydrologic and Hydraulic Report TxDOT
3/272
Hydrologic & Hydraulic Analysis
IH 610 W/ US 59 S Interchange South Drainage Elements, CSJ: 0271-17-146
i
TABLE OF CONTENTSVOLUME 1 OF 2
EXECUTIVE SUMMARY .......................................................................................................... 1
Table 1 Summary Cost Table ............................................................................................................................ 1
1 INTRODUCTION .................................................................................................................. 2
1.1 PROJECT DESCRIPTION AND LOCATION............................................................................ 2
1.2 PURPOSE............................................................................................................................. 3
1.3 SCOPE OF WORK................................................................................................................ 4
1.4 DATA SOURCES................................................................................................................... 5
1.5 OBSERVATIONS FROM AS-BUILT PLANS RESEARCH........................................................ 7
1.5.1 US 59/METRO Plans ................................................................................................................................... 7
1.5.2 Westpark Tollroad Detention Ponds ........................................................................................................... 8
1.5.3 Westpark Culvert Plans ............................................................................................................................... 9
1.5.4 Westpark Tollway Plans ............................................................................................................................ 10
1.5.5 Westheimer Connector plans ..................................................................................................................... 14
1.6 OBSERVATIONS FROM ANECDOTAL INFORMATION........................................................ 14
2 METHODOLOGY ............................................................................................................... 15
2.1 HYDROLOGIC APPROACH................................................................................................ 15
2.2
HYDRAULIC APPROACH................................................................................................... 17
3 HYDROLOGIC SUMMARY ............................................................................................. 19
3.1 OUTFALL IDENTIFICATION.............................................................................................. 19
3.2 OUTFALL SUMMARY........................................................................................................ 19
4 HYDRAULIC ANALYSIS .................................................................................................. 21
4.1 EXISTING CONDITIONS WITH SILT.................................................................................. 22
4.2 EXISTING CONDITIONS WITH NO SILT IN WESTPARK TRUNKLINE................................ 26
4.3 EXISTING CONDITIONS WITH W129STAGE 3 ................................................................. 28
7/26/2019 Hydrologic and Hydraulic Report TxDOT
4/272
Hydrologic & Hydraulic Analysis
IH 610 W/ US 59 S Interchange South Drainage Elements, CSJ: 0271-17-146
ii
4.4 PROPOSED CONDITIONS WITH W129STAGE 3 ................................................................ 31
4.4.1 Increase Detention Pond at W16........................................................................................................ 33
4.4.2 Detention Pond at W18 ...................................................................................................................... 34
4.4.3 Detention Pond at 4-H3 ...................................................................................................................... 34
4.4.4 Oversized Storm Sewer at US 59 SBFR ............................................................................................. 35
4.4.5 Trench Drain along IH 610 SB/US 59 SB Direct Connector ............................................................ 36
4.4.6
Increase Detention Storage at Ponds DB6-1 and DB6-2 .................................................................. 36
4.4.7 Increase Height of Retaining Walls along IH 610 SBFR/Westpark Tollroad.................................. 37
4.4.8 Pump Station Modifications ............................................................................................................... 37
4.5 PROPOSED CONDITIONS WITH SILT................................................................................. 41
4.6 PROPOSED CONDITIONS WITH NO SILT IN WESTPARK TRUNKLINE.............................. 44
5 MITIGATION FOR THE IH 610 BRAYS BAYOU STORM SEWER ......................... 47
6 ENTITY PARTICIPATION ............................................................................................... 49
7
CONCLUSIONS AND RECOMMENDATIONS ............................................................. 51
Table 7 Summary Phase Table ........................................................................................................................ 52
7/26/2019 Hydrologic and Hydraulic Report TxDOT
5/272
Hydrologic & Hydraulic Analysis
IH 610 W/ US 59 S Interchange South Drainage Elements, CSJ: 0271-17-146
iii
APPENDICES
APPENDIX A EXISTING CONDITIONS DRAINAGE AREA MAPS
PROPOSED CONDITIONS DRAINAGE AREA MAPS
APPENDIX B EXISTING HYDROLOGIC COMPUTATIONS
PROPOSED HYDROLOGIC COMPUTATIONS
APPENDIX C OVERALL EXISTING SWMM LAYOUT
EXISTING SUMMARIES OF RESULTS
VOLUME 2 OF 2
APPENDIX D OVERALL PROPOSED SWMM LAYOUT
PROPOSED SUMMARIES OF RESULTS
APPENDIX E DETENTION POND LAYOUTS
APPENDIX F BRAYS BAYOU STORM SEWER SYSTEM
SMALL WATERSHED VOLUME CALCULATIONSSTORM SEWER VOLUME COMPUTATIONS
APPENDIX G SEQUENCE OF CONSTRUCTION EXHIBITS
APPENDIX H CD WITH ELECTRONIC FILES
7/26/2019 Hydrologic and Hydraulic Report TxDOT
6/272
Hydrologic & Hydraulic Analysis
IH 610 W/ US 59 S Interchange South Drainage Elements, CSJ: 0271-17-146
1
EXECUTIVE SUMMARY
This is a comprehensive drainage study of IH 610 West at US 59 South interchange, in
Harris County, Texas. The purpose of the study is to identify and recommend solutions
for the existing drainage problems within the interchange and the US 59 corridor between
Chimney Rock and Newcastle. This report also presents mitigation measures
recommended to offset impacts due to proposed improvements.
The following is a summary of the identified issues along with recommended solutions.
These issues are located on Figure 1 in this section. The estimate of probable cost for
each solution is discussed in Section 6: Entity Participation.
Table 1 Summary of Recommended Solutions
I.D. Report Ref Issue Solution
A 1.5.1US 59 ML Ponding beneath METRO elevated
lane and beneath IH 610 MLTrench drains
B 1.5.3 Obs 2 Westpark storm sewer siltation Maintenance
C 4.3.1
Existing flooding of US 59 SBFR and adjacent
properties, proposed additional impervious
mitigation
Increase W16 Detention
D 4.3.2 Add W18 Detention
E 4.3.3Existing flooding of IH 610 SBFR/Westpark
Tollway
Add H3 Detention, 24 flex valve, and related
improvements
F 4.3.3 Add flex valve at Pond DB-7G 4.3.4 Raise grade of US 59 SBFR
H 4.3.4 Storm sewer and inlet improvements at US 59
SBFR
I 4.3.5 Increase Detention Storage at Ponds DB6-1 and
DB6-2
J 4.3.7 Adjust the pump timing for the IH 610 SBFR/
Westpark Tollroad & IH 610 NBFR pump stations
K 4.3.6 Increase wall height or add earthen berms at IH 610
SBFR/Westpark Tollroad.
L 1.5.4 Obs 5 Existing flooding of IH 610 NBFR Reroute storm sewer line (42 RCP)
M 1.5.4 Obs 4 Regrade abandoned pavement near Chimney Rock
Exit Ramp
N1 5
IH 610 Brays Bayou proposed additional
impervious mitigationStorm sewer improvements at IH 610 SBFR, NBFR
P1 1.5.3 Obs 2 Existing flooding of US 59 SBFR and Larchmont Complete Stage 3 of W129 channel improvements
1. Related improvements, not included on Figure 1
7/26/2019 Hydrologic and Hydraulic Report TxDOT
7/272
7/26/2019 Hydrologic and Hydraulic Report TxDOT
8/272
7/26/2019 Hydrologic and Hydraulic Report TxDOT
9/272
Hydrologic & Hydraulic Analysis
IH 610 W/ US 59 S Interchange South Drainage Elements, CSJ: 0271-17-146
2
1 INTRODUCTION
1.1 Project Description and Location
This project consists of a comprehensive drainage study of IH 610 West at US 59 South
interchange, in Harris County, Texas. The project is within the Cities of Houston and
Bellaire. The study includes an analysis of the existing drainage system and flooding
problems in and around the interchange, recommendations and analysis for the proposed
conditions, and mitigation of any impacts due to proposed improvements. The study is
being conducted as part of the reconstruction of the interchange, however, the study
includes mitigation of the entire proposed interchange improvements, which include
realignment of the direct connectors (DC), Post Oak Blvd, and the southbound (SB)
frontage road (FR) between IH 610 and Chimney Rock, a new Chimney Rock Rd exitramp, and reconstruction of the IH 610 main lanes (ML). The proposed direct connectors
constructed under CSJ 0271-17-145, -146, and -157 are Phase 1 of three phases.
The project is within two watersheds, Buffalo Bayou and Brays Bayou (see overall
drainage area maps in Appendix A). The boundary between the two is the old rail
corridor along Westpark Dr. The majority of the interchange drains to the east to Harrris
County Flood Control District (HCFCD) Ditch W129-00-00 through a large storm sewer
line along Westpark Dr. A portion of the area along the northbound (NB) and SB FRs
near Richmond Ave drains to the north through storm sewer along IH 610 to Buffalo
Bayou (HCFCD Unit W100-00-00). Part of the IH 610 NB to US 59 SB DC is within the
Brays Bayou watershed, as is the portion of IH 610 within the study area generally south
of Westpark Dr.to just south of Fournace Place.
This study and report is prepared by H & H Resources, Inc. (HHR), subconsultant to LJA
Engineering, Inc. (LJA), the prime consultant under TxDOT Contract 33-212P5016,
Work Authorization 1. HHRs role is to provide the drainage study as generally described
above, and to oversee drainage study implementation and improvements for the IH 610 /
7/26/2019 Hydrologic and Hydraulic Report TxDOT
10/272
Hydrologic & Hydraulic Analysis
IH 610 W/ US 59 S Interchange South Drainage Elements, CSJ: 0271-17-146
3
US 59 interchange. Klotz Associates (Klotz), another subconsultant to LJA under the
same TxDOT contract, is designing the IH 610 drainage system improvements south of
Westpark, based on mitigation recommendations in this study. A concurrent drainage
study and separate report is being prepared by AECOM, the prime consultant under a
separate TxDOT contract, CSJ 0271-17-145. The AECOM study area includes drainage
systems and contributing areas along IH 610 generally north of Richmond Ave., and
along US 59 generally east of the IH 610 NBFR.
As part of the overall interchange analysis, AECOM completed the W129-00-00 channel
analysis and determined the downstream boundary (tailwater) conditions for use in this
analysis for the Westpark storm sewer. Coordination with AECOM was also completed
at several locations where the systems between the W129-00-00 watershed and the IH
610N storm sewer are interconnected.
Aguirre & Fields, LP (AFLP), the prime consultant under yet another current TxDOT
contract (0271-17-157), is designing improvements for Phase 1 of the IH 610 / US 59
interchange, including improvements to existing detention facilities in the SE quadrant of
the interchange.
1.2 Purpose
The general purpose of this report is to identify the existing drainage problems within the
interchange and the US 59 corridor between Chimney Rock and Newcastle, and
recommend major drainage system improvements and mitigation. This study
incorporates all of the major drainage elements associated with the existing and proposed
roadway including the direct connectors and depressed sections. This report presents
recommendations for mitigation measures that will be required to offset calculated
impacts due to stated improvements.
7/26/2019 Hydrologic and Hydraulic Report TxDOT
11/272
Hydrologic & Hydraulic Analysis
IH 610 W/ US 59 S Interchange South Drainage Elements, CSJ: 0271-17-146
4
1.3 Scope of Work
The scope of work consists of performing an existing and proposed analysis that
incorporates all of the representative elements. The intent of the existing conditions
analysis is to establish a hydraulic baseline model for the existing storm sewer system
and identify any drainage problems. For the proposed conditions, the analysis was
completed to implement the proposed improvements due to the roadway construction,
recommend solutions for existing drainage problems and mitigate any impacts due to the
proposed changes. Additionally, the intent is to demonstrate that the proposed
improvements will not adversely impact the abutting properties and receiving streams
relative to the existing conditions. The drainage report includes hydrologic and hydraulic
computer models such as HEC-HMS and SWMM, drainage area maps, drainage outfall
descriptions, storm water storage requirements, and pump station recommendations.
Mitigation measures to reduce flooding in problem areas will be evaluated, and solutions
recommended. The report will present a comprehensive examination of the drainage
issues for the project area and will address the following items in detail:
Determine the existing drainage boundaries that contribute to the project area and
develop peak flows using rational method. Use Small Watershed Method and
Clark Unit Hydrograph method in HEC-HMS to develop hydrographs for import
into the hydraulic model. Develop an existing conditions hydraulic model, using SWMM (XP-Storm
Version 2012), from survey and as-built plans.
Identify drainage problems as shown in the existing hydraulic model and compare
to eyewitness information. Develop a list of the existing drainage problems
determined from the analysis and from research of the as-built plans.
Meet with TxDOT to discuss existing conditions analysis and existing problem
areas.
Determine proposed conditions drainage area boundaries based on proposed
roadway improvements for the ultimate interchange configuration within the
7/26/2019 Hydrologic and Hydraulic Report TxDOT
12/272
Hydrologic & Hydraulic Analysis
IH 610 W/ US 59 S Interchange South Drainage Elements, CSJ: 0271-17-146
5
project area. Develop proposed hydrology using same methodology as the
existing.
Develop a proposed conditions hydraulic model and implement design changes to
improve the existing drainage problems and mitigate potential impacts due to the
proposed changes.
Determine the impacts to the W129-00-00 and IH 610 South storm sewer system.
(The outfalls to Buffalo Bayou have been analyzed by AECOM and will be
discussed within their report.)
Coordinate with AECOM regarding all interconnections of the storm sewer and
tailwater conditions in the W129-00-00 channel.
Coordinate with Aguirre & Fields, LP, (AFLP) on proposed work in Phase 1 and
determine if any additional proposed work should be implemented with AFLPs
construction.
Limit the discharges to the receiving streams to existing capacity flows, as
determined by study of the existing conditions.
Provide a preliminary storm sewer trunk line design for the proposed conditions.
Coordinate with roadway and storm sewer PS&E designers to implement
proposed conditions as determined in the impact analysis.
Prepare a report of preliminary findings.
1.4 Data Sources
The following sources of information are used to develop the hydrologic and hydraulic
components: project topography/field surveys, aerial photography, as-built plans, City of
Houston Geographic Information & Management System (GIMS), and LiDAR
topography. All source data are either referenced to, or adjusted to the project vertical
datum: NAVD 88 (2001 adjustment). This datum is the same as the Harris County
benchmark network established by the Tropical Storm Allison Recovery Project
(TSARP), which serves as the basis for Federal Emergency Management Agency
(FEMA) Flood Insurance Rate Map (FIRM) effective flood study elevations.
7/26/2019 Hydrologic and Hydraulic Report TxDOT
13/272
Hydrologic & Hydraulic Analysis
IH 610 W/ US 59 S Interchange South Drainage Elements, CSJ: 0271-17-146
6
The project topography is provided by TxDOT and updated through field survey for the
project provided by RODS surveying. Subsurface utility survey is provided by RODS.
Aerial photography dated 2008 was obtained from LJA.
Several as-built plan sets were referenced for this study, dating back to the original
construction plans for US 59 and IH 610 in 1961. Five of the plan sets are determined to
be relevant for this study and are described below.
1. TxDOT/METRO 0027-13-123 (1987) - US 59 Southwest Freeway FR
relocation and freeway overlay widening from south of Westpark to east of IH610/US59 interchange.
2. Harris County Toll Road Authority (HCTRA) (2001) Westpark Tollway
from 0.1 mi west of Rice Ave. to 0.4 miles east of Rice Ave.
3.
Westpark Box Culverts (METRO) (1981) construction of Westpark
trunkline from Chimney Rock to W129-00-00
4. TxDOT 0271-17-138 (2001) - IH 610 depressed FRs and tollway connectorfrom Westpark Dr. to Richmond Ave.
5. TxDOT 0271-17-125 (2002) IH 610 from south of Westpark Dr. to north of
Richmond Ave, aka Westheimer Connectors.
The numbering system for the as-built plans was utilized to label the drainage areas and
nodes in the hydraulic model. The leading number refers to the plan set and the
following letter/number refers to the label as shown in the corresponding plan set. For
example, Node 1-F34 corresponds to MH-F34 as shown in Plan Set 1.
City of Houston GIMS is used to obtain data related to storm sewer systems outside of
the limits of the as-built plans. LiDAR is obtained from Harris County.
7/26/2019 Hydrologic and Hydraulic Report TxDOT
14/272
Hydrologic & Hydraulic Analysis
IH 610 W/ US 59 S Interchange South Drainage Elements, CSJ: 0271-17-146
7
1.5 Observations From As-built Plans Research
The following discussion is annotated to the plan source. Observations about existing
conditions and the implications for new drainage calculations and modeling are
described, as well as recommendations for constructed improvements if applicable.
1.5.1 US 59/METRO Plans
OBSERVATION 1
US 59 ML inlets are located beneath the METRO elevated lane east of IH 610 and behind
the slotted traffic rail. No inlet calculations for these inlets were found in the plan set.
Several existing inlets were removed in this area when this project was completed.
Contours indicate that the cross slope in this area is 0.2%. Plans show that the roadway is
in a superelevation transition and is also near the sag in the vertical profile.
Since inlet computations were not completed, the ponded width was not checked in this
area. Instead of a 2% cross slope, the 0.2% cross causes significantly more ponding than
expected or allowed. The superelevation transition occurs at sag in the profile which
further exacerbates the flooding condition.
Recommendation: Although the US 59 ML drainage system is outside the limits of the
proposed construction for this project, it is recommended that trench drains are placed
along the barrier on both sides of the roadway to reduce the ML flooding. (See Figure 1,
Location A.) The existing inlets could be utilized to connect to the existing drainage
system.
OBSERVATION 2
Another US 59 ML superelevation transition occurs beneath the IH 610 MLs. The
longitudinal slope in this area is almost 0%. This flat slope contributes to the lack of
conveyance.
7/26/2019 Hydrologic and Hydraulic Report TxDOT
15/272
Hydrologic & Hydraulic Analysis
IH 610 W/ US 59 S Interchange South Drainage Elements, CSJ: 0271-17-146
8
Recommendation: With the placement of the proposed Chimney Rock exit ramp, it is
recommended that trench drains are placed along the barrier between to reduce the ML
flooding and convey the flow under the proposed ramp. (See Figure 1, Location A.)
OBSERVATION 3
The construction of the METRO HOV lane through the interchange created a small swale
between the US 59 NBML and the HOV lane. The US 59 NBMLs prior to the HOV
drained directly into the grassy area under the IH 610 ML bridges and away from the US
59 NBML. Several columns for the existing direct connectors and IH 610 ML are within
the swale. These columns restrict the area in which water would be conveyed to the
inlets within the swale. Due to the restriction of the flow in the swale and the silting of
the openings in the slotted rail, the US 59 NBML has more ponding than it otherwise
would.
Recommendation: With the proposed roadway improvements to the US 59/IH 610 direct
connectors and the IH 610 MLs, several of the columns will be eliminated with the
removal of the existing bridges. In Phase 1, the IH 610NB/US 59SB and IH 610SB/US
59 NB direct connectors will be removed. For Phase 2 and 3, it is recommended that the
bent locations be modified to remove columns from the swale area if possible. These
changes should eliminate some of the ponding issues that are currently occurring. The
slotted rail and swale should also be maintained regularly to eliminate silting and debris
collection.
1.5.2 Westpark Tollroad Detention Ponds
OBSERVATION 1
The detention pond outlets in the plans do not represent what is now in the field. The
outlets were modified in the IH 610 FR and Westpark Tollroad depressed section plans
(Plan Set 4). Due to this change, it appears that the detention ponds may not be
functioning as originally designed.
7/26/2019 Hydrologic and Hydraulic Report TxDOT
16/272
Hydrologic & Hydraulic Analysis
IH 610 W/ US 59 S Interchange South Drainage Elements, CSJ: 0271-17-146
9
Recommendation: Modeling in this study will analyze outlets per current field survey.
1.5.3 Westpark Culvert Plans
OBSERVATION 1
The box culvert constructed in the early 1980s along the northern edge of Westpark
Drive replaced an open channel. The box was placed virtually flat, with almost no
longitudinal slope. West of Chimney Rock Road, the storm sewer is a single 10x5
RCB. It transitions to a 12x6 RCB through the intersection, then to a 2-10x7 RCB,
and finally to a 2-12x8 RCB. There are no junction boxes along this trunkline at
Westpark Drive, only openings in the wall between the boxes in various locations. All
of the trunklines from the north (those that drain US 59 and areas north of US 59)
connect to the north box culvert. Flow can only enter the south box through theseopenings. These openings vary in size from 2x2 to 6x6. The openings smaller than 6
in height are located 2 above the FL. The 6 openings match the FLs of the box culvert.
Since all of the storm sewer systems only tie to the north box (this also includes the
detention ponds along Westpark), the maximum capacity of the system may not be
realized because the flow is not effectively conveyed to the south box culverts.
Action item completed with modeling: The two storm sewer lines are modeled
separately and connected with orifices sized and located as shown in the plans to
determine the adequacy of the openings and operation of the system. The locations and
sizes were also verified by the surveyors.
OBSERVATION 2
AECOM mentioned during a coordination meeting that during construction of the
Westpark Tollroad, there were reports of the box culverts having a major silt problem
with the boxes filled as much as 60%. The silt problem seems to occur due to the very
7/26/2019 Hydrologic and Hydraulic Report TxDOT
17/272
Hydrologic & Hydraulic Analysis
IH 610 W/ US 59 S Interchange South Drainage Elements, CSJ: 0271-17-146
10
flat longitudinal slope of the storm sewer system and the presence of sand in the W129-
00-00 channel at the outfall of the Westpark System.
Action item completed: Since there are no manholes located on the Westpark storm
sewer line, the survey crew entered the storm sewer system and walked along the
northern RCB. The surveyors note the presence of silt and the depth of the silt along the
box culvert at each of the opening locations. Surveyors indicate that the silt depth
appears to be equal in each of the boxes.
Recommendation: The silt in the box culvert should be removed to allow for maximum
conveyance in the system. It is recommended that maintenance of the boxes should be
completed to keep the boxes clean of silt. Also, HCFCD completed a study to enclose
the W129-00-00 channel with box culverts from the confluence with Buffalo Bayou to
the Westpark storm sewer system. Construction of the HCFCD system was split into
three stages, with Stage 3 being the most upstream portion located between Richmond
and the Westpark system. The first two stages have been constructed with Stage 3
lacking current construction funding. Construction of Stage 3 should help minimize the
silting that occurs within the box and would allow for greater conveyance.
Action item completed with modeling: The Westpark storm sewer system is analyzed
with the silt in place in the existing and proposed condition to simulate the lost
conveyance within the system. The system is also analyzed in the existing and proposed
with the Phase 3 project in place and the silt removed from the Westpark storm sewer.
1.5.4 Westpark Tollway Plans
OBSERVATION 1
A 24 RCP gravity line from Inlet H3 (located between US 59 SBMLs and Connector B
(IH 610NB/US 59 SB) connects directly to detention pond DB-7; this line also connects
to storm sewer line between the METRO HOV lane and US 59 MLs. The retaining wall
7/26/2019 Hydrologic and Hydraulic Report TxDOT
18/272
Hydrologic & Hydraulic Analysis
IH 610 W/ US 59 S Interchange South Drainage Elements, CSJ: 0271-17-146
11
plans for Wall W-2 for the depressed IH 610 SBFR show that the low point in the wall is
at the corner of the US 59 SBML bridge and the separation area at elevation 56.20. Other
significant elevations:
The proposed pond design WSEL is shown as 57.00 with a flowline of 49.50.
The top of grate elevation at Inlet H3 is 54.94 with a flowline of 50.37.
The top of grate elevation at Inlet H2, located along the US 59 NB MLs, is 54.06
with a flowline of 49.86.
As the pond fills, the gravity line will fill with water and backup through the inlets. The
water will then spread out over the US 59 MLs near the HOV lane. Near inlet 4-H3, the
water will overflow the retaining wall and fall into the depressed IH 610 SBFR.
Action item completed with modeling: Overflow of this wall has been observed during a
flood event (See picture on following page). The elevations have been verified through
field survey. The system is modeled in SWMM and the observation should be verified
through the analysis.
Water overflowing the wall near Inlet 4-H3 (January 2012)
Photo Credit: Todd Thurber, LJA
7/26/2019 Hydrologic and Hydraulic Report TxDOT
19/272
Hydrologic & Hydraulic Analysis
IH 610 W/ US 59 S Interchange South Drainage Elements, CSJ: 0271-17-146
12
OBSERVATION 2
Several field changes to the detention pond at DB-7 may have created hydraulic
conditions different than intended by the design.
The plans indicate the 48 RCP between Ponds DB-7 and DB6-1 was placed at a
flatter slope than the original.
The contours indicate less volume in Pond DB-7 than was shown in the plans.
The capacity of the pipe is reduced from the as-built slope and requires more head to
meet same flow capacity as the design. Less exit flow would create higher WSEL in the
pond which could overflow into the depressed section.
Action item completed with modeling: During the last flood event in January 2012,
TxDOT personnel indicated that the wall was overtopped by water at this location and the
depressed section was flooded. It was also noted that Pond DB-7 was full of water but
Pond DB6-1 did not have water in it. The 48 outlet was blocked with debris and once
cleared, Pond DB-7 began to release water. According to rainfall data collected from the
Harris County Office of Emergency Management website, the rainfall recorded at the
closest locations to the interchange would be classified as less than a 2 year event.
Field survey has been completed and the elevations were utilized in the model. Although
the failure of the existing system last occurred due to clogging of the outfall pipe, thesystem should be modeled to determine if overtopping of the wall can occur at or before
the design event. The location is modeled in SWMM and the observation should be
verified through the analysis.
OBSERVATION 3
Inlets on the depressed section were designed for 25-yr storm frequency design capacity.
The elevation indicated for the maximum storage elevation in the proposed pump station
plans is higher than the elevation at the low point in the Westpark Tollway profile with
one lane ponded.
7/26/2019 Hydrologic and Hydraulic Report TxDOT
20/272
Hydrologic & Hydraulic Analysis
IH 610 W/ US 59 S Interchange South Drainage Elements, CSJ: 0271-17-146
13
Action item completed with modeling: This location is modeled in SWMM with the
pump station in place.
OBSERVATION 4
Water drains from the US 59 SBMLs through slotted traffic railing across an area of
abandoned temporary pavement. When the depressed section for Westpark Tollway and
IH 610 SBFR was built, the ditch along the pavement was not redesigned. The contours
indicate that the water is directed towards the wall and then overflows to the depressed
lanes below.
Action item completed with modeling: This area is modeled in SWMM and the
observation should be verified through the analysis. Regrading of this area will occur
with the proposed Chimney Rock exit ramp being placed.
OBSERVATION 5
In the design plans, the drainage area maps for the depressed section do not include the
overland flow from the direct connector side slopes. Also, overflow from the FRs along
the NW, NE, and SW quadrants appears to be possible if the HGL in these adjacent areas
becomes higher than the PGL entering into the depressions.
As indicated in the Westpark Tollway report (Brown & Gay Engineers, Inc. report dated
June 29, 2004) analyzing the flooding issues, the drainage areas to the pump stations are
larger than indicated in the original report. The design for pump stations should be
checked for the effect of the additional area. At the SE pump station, a large portion of
the US 59 ML drainage is directed to the pump station. The FR near the Houston
Chronicle building is also redirected to the pump station. The original plans connected
the FR storm sewer directly to the Westpark box culverts.
7/26/2019 Hydrologic and Hydraulic Report TxDOT
21/272
Hydrologic & Hydraulic Analysis
IH 610 W/ US 59 S Interchange South Drainage Elements, CSJ: 0271-17-146
14
At the NE quadrant, additional flow from the adjacent storm sewer systems can enter the
IH 610 NBFR depressed section. The storm sewer system for this area is split into three
segments. The north segment drains into the IH 610 north storm sewer system modeled
in the AECOM study. The middle segment at the curve in the FR is connected to the
depressed section system. The east segment is drained to W129-00-00 through a storm
sewer which is also modeled in the AECOM study. The southernmost inlet in the north
segment is an on-grade inlet that allows carryover to the middle segment, and this flow
was not accounted for in the depressed section computations. From the east segment, an
18 RCP was found in the field survey entering the middle segment storm sewer system.
According to the as-built plans, this line should have been removed and no connections
from the east should have occurred.
Action item completed with modeling: These areas are modeled in SWMM and the
observations should be verified through the analysis. Any changes to the pump station
design and/or timing at the IH 610 NBFR location could be done as part of CSJ 0271-17-
145, and the IH 610 SBFR station as part of Job 157 (Phase 1 construction plan sets).
1.5.5 Westheimer Connector plans
OBSERVATION 1
In the design plans, the 6x6 RCB downstream of the concrete lined channel beneath the
IH 610 MLs south of US 59 was realigned to avoid conflicts with the proposed
foundations for the connectors. During a field visit, it was noted that a flex valve was
present at the downstream end of the concrete lined channel. No field changes were
found in the as-built plans.
Action item completed with modeling: The flap gate is modeled in SWMM.
1.6 Observations from Anecdotal Information
TxDOT and the City of Houston have received several reports of flooding in the
Larchmont Subdivision located north of US 59 between Chimney Rock and South Rice,
7/26/2019 Hydrologic and Hydraulic Report TxDOT
22/272
Hydrologic & Hydraulic Analysis
IH 610 W/ US 59 S Interchange South Drainage Elements, CSJ: 0271-17-146
15
and in the US 59 SBFR at South Rice. According to contour information, the Larchmont
neighborhood, US 59 SBFR, and South Rice are significantly lower than the elevations at
Chimney Rock and Westpark. The Westpark storm sewer plans indicate that the top of
the box culvert is the pavement for Westpark Drive. Using the survey information
provided, the inside top of the Westpark storm sewer lines are higher than the ground
elevations along the US 59 FR and South Rice and within the Larchmont subdivision.
Considering that all of the outfalls tie to the Westpark system, these areas can flood due
to backwater from the Westpark boxes.
2 METHODOLOGY
The TxDOT Hydraulic Design Manual (HDM), October 2011, was utilized as the
primary methodological source for hydrologic and hydraulic analyses in this study.
Supporting methodologies were also obtained from the HCFCD Criteria Manual.
2.1 Hydrologic Approach
The Rational Method is used for peak flow calculations because the study area has small
watersheds unaffected by complex hydrologic features. The existing drainage areas were
delineated using the project topography, aerial photography, as-built plans, City of
Houston GIMS, LiDAR, and project survey data. The proposed drainage areas were
delineated based on the proposed roadway profiles and cross section data. The existing
and proposed drainage area maps are included in Appendix A.
Runoff coefficients (C-values) reflect the land use as indicated on the project aerial
photography and onsite observations. A composite C-value was determined for each of
the areas.
To compute Time of Concentration (Tc), the flow path was determined using available
topographic information. The travel time along the flow path was calculated using the
7/26/2019 Hydrologic and Hydraulic Report TxDOT
23/272
Hydrologic & Hydraulic Analysis
IH 610 W/ US 59 S Interchange South Drainage Elements, CSJ: 0271-17-146
16
following velocities: 0.5 fps for overland flow, 1.5 fps for gutter/channelized flow, and
3.0 fps for storm sewer flow. Tc is limited to >/= 10 minutes.
Rainfall data is taken from Recommendations for Rainfall Amounts in Harris County,
(TSARP White Papers (2002). The following are the Region 2 duration-depths for the
watersheds in this study:
Return Period (by Probability)
Duration 50% 10% 4% 1%
5 min 0.7 0.9 1.0 1.2
15 min 1.1 1.5 1.7 2.1
30 min 1.5 2.1 2.4 3.0
60 min 2.0 2.9 3.4 4.3
2 hr 2.3 3.6 4.3 5.7
3 hr 2.6 4.1 5.0 6.7
6 hr 3.1 5.1 6.4 8.912 hr 3.7 6.2 7.8 10.8
24 hr 4.4 7.6 9.6 13.2
Since the Rational Method produces only peak flow, additional methods are required to
develop hydrographs and runoff volume. Two methods are used, depending on the size
and location of the sub-area: Clark Unit Hydrograph Method, and the Small Watershed
Method.
The Clark Unit Hydrograph Method uses hydrologic parameters time of concentration
and Tc and R. Tc is computed as described above. The Storage Coefficient (R factor) is
adjusted to calibrate hydrograph peak to that computed by Rational Method. Rainfall
loss method is Green and Ampt which uses parameters Initial Loss, Moisture Deficit,
Suction, and Conductivity taken from Recommendation for Replacing HEC-1
Exponential Loss Function in HEC-HMS, (TSARP White Papers, 2002) as standard for
Buffalo Bayou and Brays Bayou. The following values are used:
Initial Loss = 0.1 inches
Volume Moisture Deficit = 0.385 (unitless)
Wetting Front Suction = 12.45 inchesHydraulic Conductivity = 0.024 in/hr
7/26/2019 Hydrologic and Hydraulic Report TxDOT
24/272
Hydrologic & Hydraulic Analysis
IH 610 W/ US 59 S Interchange South Drainage Elements, CSJ: 0271-17-146
17
The percent impervious ground cover is based on land use as indicated in project aerial
photography and field investigations. The computations using this unit hydrograph
method are made in HEC-HMS v3.5. For this study, the 2-, 10-, 25-, and 100-yr flows
were computed.
The (Malcom) Small Watershed Method is used for sub-areas BR-1 and BR-2 that drain
to Brays Bayou. This method is used to develop a curvilinear design hydrograph for
drainage areas < 640 acres, which peaks at a designated flow rate, and contains a runoff
volume consistent with the design rainfall. For more details on this method, see the
HCFCD Policy Criteria & Procedure Manual (2010), Section 3.6.
The HCFCD TSARP 24-hour rainfall and loss methods are used to determine the direct
runoff volume for the Small Watershed Method. Runoff volumes for the study event
(100-yr) were computed using excess rainfall based on percent impervious ground cover
and rainfall by frequency.
The Rational Method, HEC-HMS output, and hydrograph and volumecomputations are
included in Appendix B.
2.2 Hydraulic Approach
SWMM (XP-Storm 2012 V14.01) is used for hydraulic modeling because it accepts a
variety of drainage system components, such as externally-developed inflow hydrographs
for various frequency events, pipes, channels, culverts, weirs, inlets, and detention
facilities. The SWMM model uses a series of nodes and links to represent the physical
characteristics of the drainage system. The drainage system parameters are input into the
model through the Hydraulic mode of SWMM. The SWMM program offers several
methods for incorporating the runoff hydrographs into Hydraulic mode, including those
developed using the HEC-HMS and Small Watershed Method (SWM) at specific nodal
locations (Nodes) of the drainage network. The Hydraulic mode is a hydraulic flow
7/26/2019 Hydrologic and Hydraulic Report TxDOT
25/272
7/26/2019 Hydrologic and Hydraulic Report TxDOT
26/272
Hydrologic & Hydraulic Analysis
IH 610 W/ US 59 S Interchange South Drainage Elements, CSJ: 0271-17-146
19
3 HYDROLOGIC SUMMARY
3.1 Outfall Identification
The IH 610 / US 59 interchange ultimately drains to Buffalo Bayou and Brays Bayou
through several storm sewer connections. The focus of this report is on the following
outfalls.
Watershed Existing Outfall DescriptionApproximate B/L
Station
Existing Outfall
Structure
Buffalo Westpark box culverts to W129-00-00Chimney Rock to3050 E of IH 610
2/10x7 RCB/2-12x8 RCB
Brays IH 610 South (connection to SBFR) IH 610 ML 195+80 30 RCP
Brays IH 610 South (connection to NBFR) IH 610 ML 174+00 60 RCP
As indicated previously, the FRs in the NE and NW quadrants drain to the IH 610 North
storm sewer. This outfall as well as the hydraulic study of the outfall channel W129-00-
00 is being completed by AECOM.
3.2 Outfall Summary
The major outfall for the US 59/ IH 610 interchange is the Westpark box culverts. All of
the area between Westpark and IH 610 within the US 59 corridor drains to the Westpark
storm sewer through various connecting storm sewer systems. For this study, the
analysis of the Westpark storm sewer begins just west of the intersection with Chimney
Rock. The contributing drainage area upstream of this location is combined into one
drainage area and is applied at this location. Several storm sewer lines cross under US 59
and connect to the Westpark storm sewer. Some of the outfalls include drainage areas
with flow only from the US 59 corridor contributing; however, there are several
connections that carry offsite flow from north of the US 59 corridor to the Westpark
system. The lines carrying both on and offsite flow include a 48 RCP and 60 RCP at
Chimney Rock (Systems F and G), a 48 RCP at Barrington (System J), a 5x4 RCB and
48 RCP at Yorktown (System L), a 60 RCP at S. Rice (System M), and a 48 RCP at
McCue (System Q). According to the COH GIMS information, each of these lines was
built in the 1950s.
7/26/2019 Hydrologic and Hydraulic Report TxDOT
27/272
Hydrologic & Hydraulic Analysis
IH 610 W/ US 59 S Interchange South Drainage Elements, CSJ: 0271-17-146
20
Between S Rice and the US 59/IH 610 interchange, three detention ponds are included
with the construction of the Westpark Tollway and the depressed connection to Post Oak
Blvd. The two ponds along Westpark, DB6-1 to the east and DB6-2 to the west, are
directly connected to the Westpark storm sewer system with low flow orifice openings
and high flow overflow outlets. Although a small portion of the new Westpark Tollroad
storm sewer is connected to the detention ponds, these ponds act more as an offline
storage area for the Westpark storm sewer. The new storm sewer line along the southside
of the Westpark Tollroad is connected to the Westpark system near the outlet of Pond
DB6-1. The third detention pond, DB-7, is the outfall for the IH 610 SBFR and
Westpark Tollroad depressed section through the use of a pump station. The contributing
flow is pumped into Pond DB-7, and then conveyed through a 48 RCP into DB6-1.
Between the two depressed FRs, several changes have occurred since the original
construction to alter the flow paths; however, the only connection between the areas north
and south of the US 59 MLs has remained. Two 36 RCP (System W) convey flow from
the north to the south. The pipes discharge into a concrete lined channel where various
other storm sewer lines (part of System H and part of System S) also outfall. A 54 flex
valve is located at the downstream end of the concrete lined channel. A detention pond,
Node 1-W16, beneath the IH 610 MLs is also connected to the channel through 2-36
RCP. This acts as an offline storage area for the attenuated flow created by the flex
valve. Downstream of the flex valve, a 6x6 RCB outfalls into the Westpark storm
sewer system.
Another detention pond, DB-8, is located under the IH 610 MLs south of US 59. This is
the outfall for the depressed IH 610 NBFR and the US 59 MLs (System S) east of the
depressed section to approximately US 59 Station 191+00 along the northbound lanes
and 188+00 along the southbound lanes. This area also includes the at-grade US 59
NBFR east of the depressed section to station 189+00 and the contributing offsite area.
7/26/2019 Hydrologic and Hydraulic Report TxDOT
28/272
Hydrologic & Hydraulic Analysis
IH 610 W/ US 59 S Interchange South Drainage Elements, CSJ: 0271-17-146
21
A pump station conveys the flow to Pond DB-8 which is discharged to a 5x4 RCB to
the Westpark system.
Along Westpark, the roadway and adjacent properties between US 59 and Westpark
contribute directly to the Westpark storm sewer through roadway inlets and other storm
sewer lines. The flow for this area was placed in the Westpark system at various
locations within the hydraulic model.
South of Westpark, two major storm sewer lines run along each of the FRs to Cypress
Ditch (HCFCD T115-00-00) which outfalls into Brays Bayou. A 30 storm sewer line
crosses beneath IH 610 (Station 195+80) from the IH 610 NBFR to the IH 610 SBFR
storm sewer trunkline. The drainage area for the 30 line includes a portion of the IH 610
NB MLs from station 194+50 to 204+75, the IH 610 NBFR, and a portion of the
proposed IH 610 NB/ US 59 SB direct connector. Analysis of the IH 610 SBFR
trunkline is not part of this scope and is being completed as part of the Phase 1
construction, designed by AFLP. Mitigation (see Sect. 5) of the additional flow will be
completed upstream of the 30 RCP crossing.
South of the 30 RCP crossing, a large storm sewer system along the IH 610 NBFR
begins. The IH 610 South trunkline is located within the separation between the MLs and
NBFR. Due to the construction of the proposed direct connector, this storm sewer line
will need to be relocated between Station 175+00 and 188+00. Mitigation (see Sect. 5)
of additional flow due to the increase in impervious cover will be completed using inline
detention within the project limits.
4 HYDRAULIC ANALYSIS
Six major analyses were completed as part of this study with all of the frequencies
examined. The six analyses are Existing Conditions with silt, Existing Conditions with no
silt in Westpark Trunkline, Existing Conditions with W129 Stage 3, Proposed Conditions
7/26/2019 Hydrologic and Hydraulic Report TxDOT
29/272
7/26/2019 Hydrologic and Hydraulic Report TxDOT
30/272
Hydrologic & Hydraulic Analysis
IH 610 W/ US 59 S Interchange South Drainage Elements, CSJ: 0271-17-146
23
occur at the other frequencies. The US 59 SBFR, the Larchmont subdivision, and the
South Rice/ US 59 intersection are flooded in the 2-yr event. A summary of elevations
along the US 59 SBFR is shown below in Table 4.1a.
Table 4.1a Existing with Silt WSEL v Ground Elevations
Ex
Silt
WSEL
(ft)
Flood
Depth
(+/-)
Ex
Silt
WSEL
(ft)
Flood
Depth
(+/-)
Ex
Silt
WSEL
(ft)
Flood
Depth
(+/-)
Ex
Silt
WSEL
(ft)
Flood
Depth
(+/-)
4-A29 24.94 19.19 -5.75 40.31 15.37 49.89 24.95 56.44 31.50
4-J8 29.20 20.80 -8.40 40.93 11.73 49.94 20.74 56.46 27.26
4-JB2 34.32 30.37 -3.95 36.47 2.15 37.67 3.35 40.00 5.68
1-F34 55.00 56.17 1.17 57.35 2.35 57.66 2.66 58.00 3.00
1-G23 55.25 56.16 0.91 57.00 1.75 57.27 2.02 57.61 2.36
1-J8 53.78 55.60 1.82 56.56 2.78 56.99 3.21 57.49 3.71
1-J5 54.41 55.65 1.24 56.60 2.19 57.01 2.60 57.50 3.09
1-L14 53.60 55.88 2.28 56.97 3.37 57.44 3.84 57.95 4.35
1-L9a 54.91 55.74 0.83 56.63 1.72 57.02 2.11 57.49 2.58
1-L9 54.90 55.71 0.81 56.79 1.89 57.26 2.36 57.80 2.90
1-L11 54.28 55.75 1.47 56.63 2.35 57.02 2.74 57.48 3.20
1-M9 54.53 55.67 1.14 56.56 2.03 56.97 2.44 57.45 2.92
1-M7 53.62 55.67 2.05 56.56 2.94 56.97 3.35 57.45 3.83
1-M5 55.00 55.62 0.62 56.52 1.52 56.94 1.94 57.43 2.43
1-M12 54.00 55.63 1.63 56.51 2.51 56.92 2.92 57.40 3.40
1-M16 54.75 55.62 0.87 56.51 1.76 56.92 2.17 57.39 2.64
1-M19 55.00 55.63 0.63 56.49 1.49 56.89 1.89 57.36 2.36
1-Q5 54.52 55.65 1.13 56.46 1.94 56.85 2.33 57.32 2.80
1-Q4 54.52 55.80 1.28 56.39 1.87 56.78 2.26 57.25 2.72
1-Q3 54.00 55.83 1.83 56.38 2.38 56.77 2.77 57.23 3.23
1-Q7 54.50 55.19 0.69 55.74 1.24 56.13 1.63 56.58 2.08
4-B11 24.94 37.81 12.87 42.47 17.53 49.89 24.95 56.44 31.50
4-H3 54.35 54.70 0.35 54.84 0.48 54.88 0.53 56.44 2.09
1-W18 54.00 52.88 -1.12 54.71 0.71 55.14 1.14 56.36 2.36
1-W16 54.35 52.88 -1.47 54.63 0.28 55.17 0.82 56.40 2.05
Pond DB7 55.21 55.46 0.25 55.86 0.65 55.88 0.66 57.09 1.881-W14 55.00 52.88 -2.12 54.63 -0.37 55.17 0.17 56.44 1.44
Node
2-yr 10-yr 25-yr 100-yr
Ground
El
(ft)
The elevation at 1-L14 is the ground elevation in the adjacent street is 53.60. The flowline (FL) of the existing 2-5x2RCB is 51.68.
7/26/2019 Hydrologic and Hydraulic Report TxDOT
31/272
Hydrologic & Hydraulic Analysis
IH 610 W/ US 59 S Interchange South Drainage Elements, CSJ: 0271-17-146
24
The depressed sections do not flood at the 2-yr frequency although water does overtop
the retaining walls at 4-H3 and Pond DB-7. The retaining walls near 1-W18 and 1-W14
begin to overtop in the 10-yr frequency. A summary of the retaining wall elevations and
water surface elevations in this area is shown below.
Table 4.1b Existing WSEL v Retaining Wall Elevations
NodeRetaining
Wall ID
Retaining Wall
Overtopping
Elevation (ft)
2-yr
WSEL (ft)
10-yr
WSEL (ft)
25-yr
WSEL (ft)
100-yr
WSEL (ft)
4-H3 W-2 54.35 54.70 54.84 54.88 56.44
1-W18 W-4 54.00 52.88 54.71 55.14 56.36
1-W14 W-4 55.28 52.88 54.63 55.17 56.44
Pond DB7 W-2 55.21 55.46 55.86 55.88 57.09
As for the flooding witnessed in January of 2012, a preliminary analysis was completed
for the 2-yr frequency with the 48 RCP turned off in the model. The results indicate that
the IH 610 SBFR (node 4-J8) and the Westpark Tollway (node 4-A29) would be flooded.
The depth of water at node 4-A29 is 31.86 and 32.18 at 4-J8. The retaining walls near
inlet 4-H3 and at Pond DB-7 are also overtopped. Water does fill Pond DB6-1 but only
through backflow from the Westpark system. Pond DB6-1 empties as the tailwater on
the Westpark system recedes; however, Pond DB-7 and the depressed section remain full
of water throughout the duration of the analysis.
The Westpark storm sewer system appears to be balancing between the two boxes
through the openings along the length of the box. If the silt levels are greater than 2, the
orifices are also reduced. For this analysis, only a few of the orifice areas were reduced
by the silt. The flows and elevations within the two boxes are slightly different but not
significant.
For the 10-, 25-, and 100- yr frequencies, flooding in the IH 610 SBFR/ Westpark
Tollway occurs. A significant amount of flow from the McCue drainage area can flow
into the depressed section through overland flow. The high point in the gutter line
7/26/2019 Hydrologic and Hydraulic Report TxDOT
32/272
Hydrologic & Hydraulic Analysis
IH 610 W/ US 59 S Interchange South Drainage Elements, CSJ: 0271-17-146
25
between McCue and the depressed section is 54.79. The 10-, 25-, and 100- yr elevations
near McCue (node 1-Q7) are 55.74, 56.13, and 56.58, respectively. Flow begins to
overtop the high point in the gutter at STA 161+00 and drains to the low point in the US
59 SBFR (node 4-B11). The storm sewer in this area is connected to the IH 610 SBFR/
Westpark Tollway storm sewer system. Therefore, the additional flow is being conveyed
to the depressed section through storm sewer, and once the water surface elevation in this
portion of the US 59 SBFR exceeds 43.20, overland flow into the depressed section
occurs. The elevations at Nodes 4-A29 and 4-J8 are shown below.
Table 4.1c Existing WSEL v Ground Elevations in Depressed Sections
NodeGround El
(ft)
10-yr
WSEL (ft)
Flood Depth
(ft)
25-yr
WSEL (ft)
Flood Depth
(ft)
100-yr
WSEL (ft)
Flood Depth
(ft)
4-A29 24.94 40.31 15.37 49.89 24.95 56.44 31.50
4-J8 29.20 40.93 11.73 49.94 20.74 56.46 27.26
4-JB2 34.32 36.47 2.15 37.67 3.35 40.00 5.68
The IH 610 NBFR depressed section is flooded in the 10-, 25-, and 100-yr events.
Additional flow from the IH 610 NBFR at grade FR and the US 59 SBFR east of IH 610
drains toward the depressed section storm sewer system. Once the water surface
elevation in this quadrant reaches 53.00, overland flow into the depressed section occurs.
At the SE quadrant, additional overland flow from the east approaches the storm sewer
system near the Houston Chronicle building. At an elevation of 51.50, overland flow
into the depressed section occurs.
The pump stations for each of the depressed sections do not meet the 25-yr design storm.
For the west pump station, the adequacy of the pump station in the existing conditions
cannot be determined with the additional flow that overtops the retaining walls and
overland flow from the McCue area. The links representing the overtopping of theretaining walls and overland flow were turned off so the pump station could be more
accurately analyzed, assuming that unintended overflows are not present. For the 25-yr
event, the water surface elevation at node 4-A29 is 21.46, which is below the low point
7/26/2019 Hydrologic and Hydraulic Report TxDOT
33/272
7/26/2019 Hydrologic and Hydraulic Report TxDOT
34/272
Hydrologic & Hydraulic Analysis
IH 610 W/ US 59 S Interchange South Drainage Elements, CSJ: 0271-17-146
27
trunkline, and the box heights and orifices adjusted to as-built sizes. This analysis
demonstrates the results that regular maintenance of the Westpark Trunkline would have
on the overall system. A comparison between the existing with silt and existing without
silt at some of the critical locations is shown in Table 4.2a.
Table 4.2a Existing with Silt WSEL v Existing without Silt WSEL
Ex
Silt
WSEL
(ft)
Ex
No Silt
WSEL
(ft)
(+/-)
Ex
Silt
WSEL
(ft)
Ex
No Silt
WSEL
(ft)
(+/-)
Ex
Silt
WSEL
(ft)
Ex
No Silt
WSEL
(ft)
(+/-)
Ex
Silt
WSEL
(ft)
Ex
No Silt
WSEL
(ft)
(+/-)
4-A29 19.19 18.72 -0.48 40.31 35.78 -4.53 49.89 42.65 -7.24 56.44 55.99 -0.45
4-J8 20.80 20.63 -0.18 40.93 36.97 -3.96 49.94 42.68 -7.25 56.46 56.00 -0.46
4-JB2 30.37 30.32 -0.06 36.47 36.23 -0.24 37.67 37.41 -0.27 40.00 39.87 -0.121-J5 55.65 55.13 -0.52 56.60 56.42 -0.18 57.01 56.74 -0.27 57.50 57.26 -0.24
1-L9 55.71 55.11 -0.60 56.79 56.62 -0.17 57.26 56.97 -0.29 57.80 57.54 -0.26
1-M5 55.62 55.22 -0.40 56.52 56.38 -0.14 56.94 56.68 -0.26 57.43 57.19 -0.24
1-Q3 55.83 55.66 -0.17 56.38 56.21 -0.16 56.77 56.51 -0.26 57.23 57.00 -0.23
4-B11 40.58 37.49 -3.09 42.47 41.78 -0.69 49.89 42.71 -7.17 56.44 55.99 -0.45
4-H3 54.70 54.60 -0.10 54.84 54.81 -0.04 54.88 54.85 -0.03 56.44 55.99 -0.45
Pond DB7 55.46 53.80 -1.66 55.86 55.84 -0.01 55.88 55.87 -0.01 57.09 56.39 -0.70
1-W18 52.88 52.32 -0.56 54.71 54.31 -0.40 55.14 54.96 -0.17 56.36 55.89 -0.47
Node
2-yr 10-yr 25-yr 100-yr
Maintenance of the Westpark trunkline does reduce water surface elevations within thestudy limits; however, it does not eliminate the flooding problems along the US 59 SBFR
and adjacent properties or the flooding within the IH 610 SBFR/Westpark Tollway
depressed section. The IH 610 NBFR system is not affected by the changes at W129-00-
00. A comparison of the flood depths at some of the critical locations is shown in Table
4.2b.
Supplemental Tables 2.1 through 2.4 are available in Appendix C of the electronic file
included on the CD of the report.
7/26/2019 Hydrologic and Hydraulic Report TxDOT
35/272
7/26/2019 Hydrologic and Hydraulic Report TxDOT
36/272
Hydrologic & Hydraulic Analysis
IH 610 W/ US 59 S Interchange South Drainage Elements, CSJ: 0271-17-146
29
00-00 were provided by AECOM and include the HCFCD Stage 3 improvements to
W129-00-00. (See AECOMs report Hydrologic & Hydraulic Analysis: IH 610 W/US
59 S Interchange North Drainage Elements, CSJ: 0271-17-145 for details).
The analysis shows the tailwater along the Westpark storm sewer line is reduced, and in
turn, water surface elevations along the US 59 SBFR and in the IH 610 SBFR/Westpark
Tollway depressed sections are also reduced. A comparison between the existing with
silt and phase 3 at some of the critical locations is shown below.
Table 4.3a Existing with Silt WSEL v Existing with Stage 3 WSEL
Ex
Silt
WSEL(ft)
Ex
Stage 3
WSEL(ft)
(+/-)
Ex
Silt
WSEL(ft)
Ex
Stage 3
WSEL(ft)
(+/-)
Ex
Silt
WSEL(ft)
Ex
Stage 3
WSEL(ft)
(+/-)
Ex
Silt
WSEL(ft)
Ex
Stage 3
WSEL(ft) (+/-)
4-A29 19.19 18.72 -0.48 40.31 29.82 -10.49 49.89 40.65 -9.24 56.44 55.92 -0.51
4-J8 20.80 20.61 -0.18 40.93 30.15 -10.79 49.94 41.16 -8.78 56.46 56.03 -0.42
4-JB2 30.37 29.93 -0.44 36.47 35.74 -0.73 37.67 37.00 -0.67 40.00 39.77 -0.23
1-J5 55.65 54.67 -0.98 56.60 56.04 -0.56 57.01 56.57 -0.44 57.50 57.15 -0.35
1-L9 55.71 54.68 -1.03 56.79 56.14 -0.64 57.26 56.78 -0.48 57.80 57.39 -0.41
1-M5 55.62 54.92 -0.70 56.52 55.94 -0.58 56.94 56.51 -0.43 57.43 57.06 -0.37
1-Q3 55.83 55.56 -0.27 56.38 56.07 -0.31 56.77 56.33 -0.44 57.23 56.86 -0.38
4-B11 40.58 37.44 -3.14 42.47 39.54 -2.94 49.89 42.54 -7.35 56.44 55.92 -0.51
4-H3 54.70 54.59 -0.11 54.84 54.79 -0.05 54.88 54.83 -0.05 56.44 56.04 -0.40
Pond DB7 55.46 53.00 -2.46 55.86 55.74 -0.12 55.88 56.00 0.13 57.09 56.53 -0.56
1-W18 52.88 51.99 -0.89 54.71 54.59 -0.12 55.14 55.44 0.30 56.36 56.44 0.08
Node
2-yr 10-yr 25-yr 100-yr
Adding the Stage 3 improvements to W129-00-00 alone will not solve the flooding
problems along the US 59 SBFR and adjacent properties or the flooding within the IH
610 SBFR/Westpark Tollway depressed section. The IH 610 NBFR system is not
affected by the changes at W129-00-00. A comparison of the flood depths at some of the
critical locations is shown in Table 4.3b.
7/26/2019 Hydrologic and Hydraulic Report TxDOT
37/272
Hydrologic & Hydraulic Analysis
IH 610 W/ US 59 S Interchange South Drainage Elements, CSJ: 0271-17-146
30
Table 4.3b Existing with Stage 3 WSEL v Ground Elevations
Ex
Stage 3
WSEL
(ft)
(+/-)
Ex
Stage 3
WSEL
(ft)
(+/-)
Ex
Stage 3
WSEL
(ft)
(+/-)
Ex
Stage 3
WSEL
(ft)
(+/-)
4-A29 24.94 18.72 -6.23 29.82 4.88 40.65 15.71 55.92 30.98
4-J8 29.20 20.61 -8.59 30.15 0.95 41.16 11.96 56.03 26.83
4-JB2 34.32 29.93 -4.39 35.74 1.42 37.00 2.68 39.77 5.45
1-F34 55.00 55.19 0.19 56.76 1.76 57.25 2.25 57.73 2.73
1-G23 55.25 55.32 0.07 56.73 1.48 56.96 1.71 57.33 2.08
1-J8 53.78 54.64 0.86 55.99 2.21 56.55 2.77 57.11 3.33
1-J5 54.41 54.67 0.26 56.04 1.63 56.57 2.16 57.15 2.74
1-L14 53.60 54.76 1.16 56.33 2.73 56.95 3.35 57.56 3.96
1-L9a 54.91 54.66 -0.25 56.11 1.20 56.61 1.70 57.15 2.24
1-L9 54.90 54.68 -0.22 56.14 1.24 56.78 1.88 57.39 2.49
1-L11 54.28 54.77 0.49 56.10 1.82 56.60 2.32 57.15 2.87
1-M9 54.53 54.94 0.41 55.97 1.44 56.53 2.00 57.09 2.56
1-M7 53.62 54.94 1.32 55.97 2.35 56.53 2.91 57.09 3.47
1-M5 55.00 54.92 -0.08 55.94 0.94 56.51 1.51 57.06 2.06
1-M12 54.00 54.95 0.95 55.94 1.94 56.50 2.50 57.04 3.04
1-M16 54.75 54.97 0.22 55.94 1.19 56.49 1.74 57.03 2.28
1-M19 55.00 55.01 0.01 55.93 0.93 56.47 1.47 57.00 2.00
1-Q5 54.52 55.50 0.98 55.92 1.40 56.43 1.91 56.95 2.43
1-Q4 54.52 55.55 1.03 56.04 1.52 56.35 1.83 56.87 2.35
1-Q3 54.00 55.56 1.56 56.07 2.07 56.33 2.33 56.86 2.86
1-Q7 54.50 55.10 0.60 55.41 0.91 55.71 1.21 56.21 1.714-B11 24.94 37.44 12.50 39.54 14.60 42.54 17.60 55.92 30.98
4-H3 54.35 54.59 0.24 54.79 0.44 54.83 0.48 56.04 1.69
1-W18 54.00 51.99 -2.01 54.59 0.59 55.44 1.44 56.44 2.44
1-W16 54.35 51.98 -2.37 54.59 0.24 55.43 1.08 55.95 1.60
Pond DB7 55.21 53.00 -2.21 55.74 0.53 56.00 0.79 56.53 1.32
1-W14 55.00 51.98 -3.02 54.59 -0.41 55.41 0.41 55.93 0.93
Node
2-yr 10-yr 25-yr 100-yr
Ground
El
(ft)
The elevation at 1-L14 is the ground elevation in the adjacent street is 53.60. The flowline (FL) of the existing 2-5x2RCB is 51.68.
Summaries of the SWMM results are included in Appendix C Tables 3.1 through 3.4.
7/26/2019 Hydrologic and Hydraulic Report TxDOT
38/272
Hydrologic & Hydraulic Analysis
IH 610 W/ US 59 S Interchange South Drainage Elements, CSJ: 0271-17-146
31
4.4 Proposed Conditions with W129 Stage 3
The proposed conditions model with Stage 3 analysis includes the Westpark storm sewer
system with the as-built box and orifice heights as well as the tailwater for the completed
Stage 3 improvements to W129-00-00. It also contains several improvements within the
TxDOT ROW to reduce the flooding within the corridor and the adjacent properties. It
also mitigates the proposed increases in impervious cover for the ultimate US 59/IH 610
interchange.
As part of the realignment of the US 59 NB/IH 610 SB direct connector in Phase 1 Job
157, AFLP has proposed the removal of the embankment and 48 restrictor between
Ponds DB6-1 and DB-7. This change was implemented in this analysis prior to making
any other proposed updates. The new detention pond reduces the water surface elevation
in the vicinity of the retaining wall (wall elevation =55.21) for the 2-yr storm, but not
enough to avoid overtopping the wall. The 10- and 25-yr elevations are higher than the
existing elevations at Pond DB-7. This is due to the backwater from the Westpark storm
sewer system filling the pond which will allow more water to overflow to the depressed
section. A comparison of the elevations at existing Pond DB-7 and the AFLP proposed
Pond DB6-1 is shown in Table 4.4a. A comparison of elevations within the depressed
section at Node 4-A29 is also shown below in Table 4.4b. Supplemental Tables 4.1
through 4.4 are available in Appendix D of the electronic file included on the CD of the
report.
Table 4.4a Existing WSEL v Existing with AFLP Pond DB6-1
Location2-yr
WSEL (ft)
10-yr
WSEL (ft)
25-yr
WSEL (ft)
100-yr
WSEL (ft)
Existing Pond DB-7 55.46 55.86 55.88 57.09
Existing Pond DB6-1 55.39 56.35 56.80 57.35
Existing w/ AFLP Pond DB6-1 55.18 56.17 56.62 56.97
DB-7 Change in WSEL (ft) -0.27 0.31 0.74 -0.12
DB6-1 Change in WSEL (ft) -0.20 -0.18 -0.19 -0.38
7/26/2019 Hydrologic and Hydraulic Report TxDOT
39/272
Hydrologic & Hydraulic Analysis
IH 610 W/ US 59 S Interchange South Drainage Elements, CSJ: 0271-17-146
32
Table 4.4b Node 4-A29 Elevation Comparison
Location2-yr
WSEL (ft)
10-yr
WSEL (ft)
25-yr
WSEL (ft)
100-yr
WSEL (ft)
Existing Node 4-A29 19.19 40.31 49.89 56.44
Existing w/ AFLP Pond at Node 4-A29 18.90 41.13 50.95 56.24
4-A29 Change in WSEL (ft) -0.30 0.81 1.07 -0.20
It is recommended that the retaining wall adjacent to the existing Pond DB7 should be
raised to elevation 57 to avoid overtopping during the Phase 1 Job 157 construction.
Coordination with AFLP should be completed to determine the limits of the effected
retaining wall and proposed detention pond limits and volume modeled within this report.
At Node 4-H3, overflow of the adjacent retaining wall (wall elevation =54.35) will
continue to occur. Without additional storage volume at 4-H3 and a flex valve on the
existing 24 RCP outfall into Pond DB6-1 (see Section 4.4.3), the overtopping cannot be
stopped without causing the US 59 MLs to flood. The construction of the detention pond
as discussed below cannot be constructed until Phase 1 Job 146, which removes the
existing IH 610 NB/ US 59 SB direct connector. It appears that some excavation at 4-H3
could be completed during Phase 1 Job 157 construction without disturbing the
embankment; however, the effect of those improvements have not been analyzed. A
comparison of elevations at Node 4-H3 is shown in Table 4.4c.
Table 4.4c Node 4-H3 Elevation Comparison
Location2-yr
WSEL (ft)
10-yr
WSEL (ft)
25-yr
WSEL (ft)
100-yr
WSEL (ft)
Existing Node 4-H3 54.70 54.84 54.88 56.44
Existing w/ AFLP Pond at Node 4-H3 54.68 54.82 54.87 56.24
4-H3 Change in WSEL (ft) -0.02 -0.02 -0.01 -0.20
Reduction of the tailwater is critical in reducing the flooding within the US 59 corridor
and the adjacent properties. Two options were analyzed during the development of this
report. First, an analysis was completed that would meet the 10-yr storm event along the
US 59 SBFR. This option would require 2-10 x 10 RCB along the US 59 SB FR,
7/26/2019 Hydrologic and Hydraulic Report TxDOT
40/272
Hydrologic & Hydraulic Analysis
IH 610 W/ US 59 S Interchange South Drainage Elements, CSJ: 0271-17-146
33
modifications to the detention ponds DB6-1 and DB6-2 to include vertical walls and
excavation to elevation 30.00, and the construction of a new pump station to de-water
the ponds and storm sewer. This option is undesirable due to several reasons. First of all,
the water table in the interchange is very high. Seepage through the walls in the
depressed section has been noted. Therefore, excavation to an elevation approximately
15 deeper than the existing detention pond would not likely be feasible. Without the
possibility of deepening the detention pond, the large storm sewer boxes cannot be
placed. The flowline of the box culverts would need to be significantly lower to place
below the proposed pavement elevations. Another factor against this option is
constructability near the Rice Blvd overpass. A single 10 x 10 RCB can be placed
under the overpass; however, the depth of the RCB interferes with many utilities. Also,
the proposed routing of the box along the US 59 NB MLs cannot be done at the depth
needed. The width of the ROW is limited between a retaining wall and several
businesses. Through coordination with LJA, it was determined that the integrity of the
retaining wall could be compromised with the parallel placement of the 10 x 10 RCB.
The limited ROW would not allow room for the storm sewer to be placed at a distance
that would not have effects on the retaining wall.
The second option would also require larger trunklines along the US 59 SB FR, but
would maintain gravity drainage of detention ponds DB6-1 and DB6-2. Due to the slight
slope of the terrain and the minimal depth of the existing storm sewer system, a 10-yr
storm event cannot be obtained with this option. Therefore, a 2-yr storm sewer design for
the US 59 SB FR was developed, with the proposed recommendations that follow.
4.4.1 Increase Detention Pond at W16
First of all, Pond 1-W16 is expanded to include Pond DB-8 and the additional area
available due to the realignment of the IH 610 NB/ US 59 SB direct connector in Phase 1
Job 146. Approximately 22.86 ac-ft of storage volume is available at this location.
Additional volume could be realized by adding a retaining wall along the IH 610 NB/ US
7/26/2019 Hydrologic and Hydraulic Report TxDOT
41/272
Hydrologic & Hydraulic Analysis
IH 610 W/ US 59 S Interchange South Drainage Elements, CSJ: 0271-17-146
34
59 NB DC, however, the additional volume is not significant enough to have an impact
on the water surface elevations within the US 59 corridor or the adjacent properties. The
outlet from Pond 1-W16 will be the existing 5x4 RCB that currently serves as the outlet
from Pond DB-8. The current outfall for Pond 1-W16, 2-36 RCP that enter the concrete
lined channel, should be removed. This pond will now act as an offline storage area for
the Westpark storm sewer system. A detention pond layout is provided in Appendix E.
4.4.2 Detention Pond at W18
A detention pond north of US 59 is also planned at Node 1-W18. The maximum water
surface elevation of 55.00 is controlled by the existing US 59 MLs. The amount of
drainage area that can be directed to this detention pond is restricted by the two depressed
sections; therefore, additional flow from the south side of US 59 will be allowed to backup into the north pond through the existing 2-36 RCP. The outflow from the east pump
station will be redirected to the concrete lined channel just downstream of the 2-36 RCP.
A berm should be placed along the retaining wall on the west side so flow will not
overtop the retaining wall. For this analysis, it is assumed that retaining walls can be
placed along the DCs in the NE (Phase 2) and NW (Phase 1 Job 145) quadrants to
maximize the size of the detention pond. Approximately 38.19 ac-ft of storage volume is
available after Phase 2. This pond will also be utilized as mitigation volume for the
AECOM part of the study. A layout for this detention pond is also included in Appendix
E. An additional pond layout is also provided to show the limits of the detention pond
that can be constructed as part of Phase 1 Job 145. This alternate layout provides
approximately 28.68 ac-ft of detention.
4.4.3 Detention Pond at 4-H3
The gravity line between Inlet 4-H3 and the proposed Pond DB6-1 must remain in the
proposed conditions. A flex valve should be placed at the downstream end of the gravityline to eliminate backflow through the system. A small detention pond is proposed in the
separation between the US 59 MLs and the IH 610 SB/US 59 SB direct connector to
create storage volume for the runoff to this area. The inlet 4-H3 should be removed and
7/26/2019 Hydrologic and Hydraulic Report TxDOT
42/272
7/26/2019 Hydrologic and Hydraulic Report TxDOT
43/272
Hydrologic & Hydraulic Analysis
IH 610 W/ US 59 S Interchange South Drainage Elements, CSJ: 0271-17-146
36
US 59 at South Rice. The trunkline will then turn toward the east, parallel the US 59 NB
MLs, and discharge into Pond DB6-2.
4.4.5 Trench Drain along IH 610 SB/US 59 SB Direct Connector
Trench drain is proposed along the barrier of the IH 610 SB/US 59 SB direct connector to
capture mainlane flow and direct it toward the detention pond at 4-H3. In the existing
conditions, this area drains into a small concrete lined channel between the frontage road
and the direct connector. During the 10-yr storm event, the water overflows into the
depressed section along the US 59 SB FR and contributes to the flooding of the IH 610
SB FR/Westpark Tollroad depressed section. With the adjustment to the frontage road
profile, the edge of the direct connector cannot be drained to the concrete channel. The
low point in the direct connector edge of pavement is approximately 53.90. Trenchdrain is proposed between Station 360+00 and 363+50. This line should outfall into the
detention pond 4-H3. The results show that the water surface elevation in the 100-yr
storm will be 54.45, which allows 1 lane of the direct connector to be passable.
4.4.6 Increase Detention Storage at Ponds DB6-1 and DB6-2
The detention ponds DB6-1 and DB6-2 should be regraded and reshaped within the
available area to provide the maximum volume. The flowlines of Pond DB6-1 and DB6-
2 are proposed at elevations 47.64 and 47.50, respectively. The ultimate configuration
at Pond DB6-2 can be completed in Phase 1 Job 157. Pond DB6-1 will need to be phased
with a majority of the pond completed during Phase 1 Job 157. During Phase 2 of the
interchange reconstruction, Pond DB6-1 should excavated beyond the limits of the Phase
1 Job 157 definition to the edge of the existing HOV lane. This step assumes that the US
59 NB/ IH 610 NB DC can be reconfigured in the future construction to increase the
length of the bridge. (AECOM is investigating this proposed change.) The ultimate
storage available in each of the ponds is 49.26 ac-ft at Pond DB6-1 and 10.84 ac-ft atPond DB6-2. Pond layouts for Phase 1 Job 157 and Phase 2 conditions are included in
Appendix E.
7/26/2019 Hydrologic and Hydraulic Report TxDOT
44/272
Hydrologic & Hydraulic Analysis
IH 610 W/ US 59 S Interchange South Drainage Elements, CSJ: 0271-17-146
37
4.4.7 Increase Height of Retaining Walls along IH 610 SBFR/Westpark Tollroad
To eliminate the overflows of the retaining walls, it is recommended that the wall heights
are raised or protected by earthen berms. The wall along proposed Pond DB6-1 should
be raised to approximately elevation 57 at all locations south of US 59. North of US 59
adjacent to the proposed pond at 4-H3, the retaining wall should be protected up to
elevation 55. Along the east side of the Westpark depressed lanes, the walls both north
and south of US 59 should be raised or protected to elevation 56 as part of Job 146.
These changes will keep water from overflowing the walls at all frequencies analyzed.
4.4.8 Pump Station Modifications
The pump station on/off elevations should be adjusted to allow the pumps to perform
more effectively. With the overland flow and overtopping of the retaining walls
eliminated, the IH 610 SBFR/ Westpark Tollroad is not flooded in the 25-yr storm
frequency. A comparison of the on/off elevations for the existing and proposed
conditions at Pump Station PS-4 is shown in Table 4.4d.
Table 4.4d Pump Station PS-4 Existing V Proposed On/Off Elevations
On El (ft) Off El (ft) On El (ft) Off El (ft)
1 17.12 14.12 22.50 8.752 18.62 17.12 23.00 8.43
Sump 5.69 3.04 5.69 3.04
Existing ProposedPump
For the IH 610 NBFR, several changes to the on/off elevations were made to reduce the
flooding; however, the changes did not alleviate flooding in the 25-yr event. A change to
the storm sewer routing is proposed to reduce the drainage area to the pump station. First
of all, approximately 48% of the flow for P4-J42 will be redirected to a new storm sewer
line as proposed in the AECOM (Job 145) study. This storm sewer line will drain to the
east and directly into W129. This will eliminate several acres of offsite and US 59 ML
and FR flow from being directed towards the pump station. Also, a proposed 42 storm
7/26/2019 Hydrologic and Hydraulic Report TxDOT
45/272
Hydrologic & Hydraulic Analysis
IH 610 W/ US 59 S Interchange South Drainage Elements, CSJ: 0271-17-146
38
sewer line is proposed to disconnect the existing trunkline along the US 59 NB MLs from
the pump station system and reroute it directly to the Westpark trunkline. The routing of
this line is shown in Appendix D. The line will need to pass under the METRO HOV
lane and under the existing US 59 NB FR using jack and/or bore to avoid disruptions to
traffic. Approximately 0.05 ac of ROW will be needed for construction of this line.
With this adjustment, the depressed lanes will meet the 25-yr criteria. A comparison of
the on/off elevations for the existing and proposed conditions at Pump Station PS-5 is
shown in Table 4.4e.
Table 4.4e Pump Station PS-5 Existing V Proposed On/Off Elevations
On El (ft) Off El (ft) On El (ft) Off El (ft)1 22.45 20.70 27.50 18.75
2 22.70 21.95 30.00 19.00
3 24.70 22.95 32.00 18.65
4 26.70 23.70 32.50 18.55
Sump 16.64 15.64 16.64 15.64
Existing ProposedPump
A comparison of the water surface elevations to the ground levels within the depressed
section are shown in Table 4.4f. Water surface elevations between the existing and
proposed conditions are shown in Table 4.4g.
Table 4.4f Proposed WSEL v Ground Elevations in Depressed Sections
NodeGround El
(ft)
10-yr
WSEL (ft)
Flood
Depth (ft)
25-yr
WSEL (ft)
Flood
Depth (ft)
100-yr
WSEL (ft)
Flood
Depth (ft)
4-A29 24.94 24.68 -0.27 24.82 -0.12 37.91 12.97
4-J8 29.20 24.87 -4.34 25.03 -4.17 38.04 8.84
4-JB2 34.32 33.18 -1.14 33.50 -0.82 33.60 -0.73
7/26/2019 Hydrologic and Hydraulic Report TxDOT
46/272
Hydrologic & Hydraulic Analysis
IH 610 W/ US 59 S Interchange South Drainage Elements, CSJ: 0271-17-146
39
Table 4.4g Proposed WSEL v Existing WSEL in Depressed Sections
Node
10-yr
EX
WSEL
(ft)
10-yr
PR
WSEL
(ft)
Change
in
Depth
(ft)
25-yr
EX
WSEL
(ft)
25-yr
PR
WSEL
(ft)
Change
in
Depth
(ft)
100-yr
EX
WSEL
(ft)
100-yr
PR
WSEL
(ft)
Change
in
Depth
(ft)
4-A29 40.31 24.68 -15.64 49.89 24.82 -25.07 56.44 37.91 -18.53
4-J8 40.93 24.87 -16.07 49.94 25.03 -24.91 56.46 38.04 -18.41
4-JB2 36.47 33.18 -3.29 37.67 33.50 -4.17 40.00 33.60 -6.40
With these proposed changes, water surface elevations within the project limits are
greatly reduced when compared to existing conditions. Comparison of the Existing with
Silt and the Proposed with Phase 3 is shown below in Table 4.4h. The proposed
improvements also meet the 2-yr frequency for the frontage roads and the 25-yr in the
depressed sections. The water surface elevations for the improvements compared to the
ground elevations at critical locations are also shown below in Table 4.4i. Summaries of
the SWMM results are included in Appendix D Tables 5.1 through 5.4.
7/26/2019 Hydrologic and Hydraulic Report TxDOT
47/272
Hydrologic & Hydraulic Analysis
IH 610 W/ US 59 S Interchange South Drainage Elements, CSJ: 0271-17-146
40
Table 4.4h Existing with Silt WSEL v Proposed with Stage 3 WSEL
Ex
Silt
WSEL(ft)
Pr
Stage 3
WSEL(ft)
(+/-)
Ex
Silt
WSEL(ft)
Pr
Stage 3
WSEL(ft)
(+/-)
Ex
Silt
WSEL(ft)
Pr
Stage 3
WSEL(ft)
(+/-)
Ex
Silt
WSEL(ft)
Pr
Stage 3
WSEL(ft)
(+/-)
4-A29 19.19 23.05 3.86 40.31 24.68 -15.64 49.89 24.82 -25.07 56.44 37.91 -18.53
4-J8 20.80 23.13 2.33 40.93 24.87 -16.07 49.94 25.03 -24.91 56.46 38.04 -18.41
4-JB2 30.37 30.98 0.61 36.47 33.18 -3.29 37.67 33.50 -4.17 40.00 33.60 -6.40
1-J8 55.60 53.23 -2.37 56.56 55.61 -0.96 56.99 56.30 -0.70 57.49 57.06 -0.43
1-J5 55.65 53.07 -2.58 56.60 55.64 -0.96 57.01 56.36 -0.65 57.50 57.05 -0.44
1-L14 55.88 52.90 -2.99 56.97 55.82 -1.15 57.44 56.67 -0.77 57.95 57.38 -0.57
1-L6 55.74 52.92 -2.82 56.64 55.68 -0.96 57.02 56.37 -0.65 57.49 57.05 -0.44
1-L9 55.71 53.06 -2.65 56.79 55.72 -1.07 57.26 56.45 -0.81 57.80 57.12 -0.69
1-M9 55.67 52.88 -2.79 56.56 55.63 -0.93 56.97 56.33 -0.64 57.45 57.04 -0.40
1-M7 55.67 52.88 -2.79 56.56 55.60 -0.96 56.97 56.31 -0.66 57.45 57.04 -0.41
1-M5 55.62 52.85 -2.77 56.52 55.59 -0.93 56.94 56.29 -0.66 57.43 57.04 -0.391-M12 55.63 52.84 -2.78 56.51 55.59 -0.92 56.92 56.29 -0.64 57.40 57.04 -0.37
1-Q5 55.65 52.85 -2.80 56.46 55.57 -0.88 56.85 56.27 -0.58 57.32 57.02 -0.30
1-Q3 55.83 52.85 -2.98 56.38 55.57 -0.80 56.77 56.27 -0.50 57.23 57.02 -0.22
1-Q7 55.19 52.85 -2.34 55.74 55.57 -0.17 56.13 56.27 0.15 56.58 57.01 0.43
4-B11 37.81 37.15 -0.66 42.47 37.39 -5.09 49.89 37.47 -12.42 56.44 42.18 -14.26
4-H3 54.70 50.05 -4.65 54.84 51.72 -3.12 54.88 52.68 -2.20 56.44 54.36 -2.09
1-W18 52.88 50.36 -2.53 54.71 51.62 -3.09 55.14 52.73 -2.41 56.36 55.41 -0.95
1-W16 52.88 50.83 -2.05 54.63 51.92 -2.71 55.17 53.19 -1.98 56.40 55.55 -0.86
Pond W16 52.88 52.42 -0.47 54.64 55.09 0.44 55.17 55.76 0.58 56.40 56.53 0.12
Pond DB6-1 55.39 52.63 -2.76 56.35 55.31 -1.04 56.80 56.02 -0.79 57.35 56.80 -0.55
1-W14 52.88 50.86 -2.02 54.63 51.93 -2.70 55.17 53.28 -1.89 56.44 55.53 -0.91
Node
2-yr 10-yr 25-yr 100-yr
7/26/2019 Hydrologic and Hydraulic Report TxDOT
48/272
Hydrologic & Hydraulic Analysis
IH 610 W/ US 59 S Interchange South Drainage Elements, CSJ: 0271-17-146
41
Table 4.4i Proposed with Stage 3 WSEL V Ground Elevations
Pr
Stage 3
WSEL
(ft)
Flood
Depth
(+/-)
Pr
Stage 3
WSEL
(ft)
Flood
Depth
(+/-)
Pr
Stage 3
WSEL
(ft)
Flood
Depth
(+/-)
Pr
Stage 3
WSEL
(ft)
Flood
Depth
(+/-)
4-A29 24.94 23.05 -1.89 24.68 -0.27 24.82 -0.12 37.91 12.97
4-J8 29.20 23.13 -6.07 24.87 -4.34 25.03 -4.17 38.04 8.84
4-JB2 34.32 30.98 -3.34 33.18 -1.14 33.50 -0.82 33.60 -0.73
1-F34 55.00 55.14 0.13 56.45 1.45 57.05 2.05 57.66 2.66
1-G23 55.25 54.95 -0.30 56.36 1.11 56.50 1.25 57.08 1.83
1-J8 53.78 53.23 -0.55 55.61 1.83 56.30 2.52 57.06 3.28
1-J5 54.11 53.07 -1.04 55.64 1.53 56.36 2.25 57.05 2.94
1-L14 53.60 52.90 -0.70 55.82 2.22 56.67 3.07 57.38 3.78
1-L6 54.19 52.92 -1.27 55.68 1.49 56.37 2.18 57.05 2.86
1-L9 55.04 53.06 -1.98 55.72 0.68 56.45 1.41 57.12 2.08
1-L11 56.04 52.90 -3.14 55.67 -0.37 56.36 0.32 57.05 1.01
1-M9 54.77 52.88 -1.89 55.63 0.85 56.33 1.56 57.04 2.27
1-M7 54.54 52.88 -1.66 55.60 1.06 56.31 1.77 57.04 2.50
1-M5 54.94 52.85 -2.09 55.59 0.65 56.29 1.35 57.04 2.10
1-M12 54.36 52.84 -1.52 55.59 1.23 56.29 1.93 57.04 2.68
1-Q5 55.06 52.85 -2.21 55.57 0.51 56.27 1.21 57.02 1.96
1-Q3 55.48 52.85 -2.63 55.57 0.09 56.27 0.79 57.02 1.54
1-Q7 55.80 52.85 -2.95 55.57 -0.23 56.27 0.47 57.01 1.21
4-B11 40.58 37.15 -3.43 37.39 -3.19 37.47 -3.11 42.18 1.60
4-H3 55.00 50.05 -4.95 51.72 -3.28 52.68 -2.33 54.36 -0.64
1-W18 55.00 50.36 -4.65 51.62 -3.38 52.73 -2.27 55.41 0.411-W16 55.00 50.83 -4.17 51.92 -3.08 53.19 -1.81 55.55 0.55
Pond W16 58.00 52.42 -5.59 55.09 -2.92 55.76 -2.24 56.53 -1.47
Pond DB6-1 58.00 52.63 -5.37 55.31 -2.69 56.02 -1.99 56.80 -1.20
1-W14 57.00 50.86 -6.14 51.93 -5.07 53.28 -3.72 55.53 -1.47
Node
2-yr 10-yr 25-yr 100-yr
Ground
El
(ft)
The elevation at 1-L14 is the ground elevation in the adjacent street is 53.60. The flowline (FL) of the existing 2-5x2
RCB is 51.68.
4.5 Proposed Conditions with Silt
The proposed conditions model with silt analysis includes all of the proposed drainage
improvements discussed in the proposed conditions with Stage 3 analysis, but also
includes the silt levels within the Westpark storm sewer line and the existing W129-00-
00 conditions.
7/26/2019 Hydrologic and Hydraulic Report TxDOT
49/272
Hydrologic & Hydraulic Analysis
IH 610 W/ US 59 S Interchange South Drainage Element