+ All Categories
Home > Documents > HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

Date post: 08-Feb-2017
Category:
Upload: trinhnguyet
View: 220 times
Download: 0 times
Share this document with a friend
174
Conditions of Service: GPM:______ TDH:______ The curves reflect maximum performance characteristics without exceeding full load (Nameplate) horsepower. All pumps have a service factor of 1.2. Operation is recommended in the bounded area with operational point within the curve limit. Performance curves are based on actual tests with clear water at 70° F. and 1280 feet site elevation. HYDROMATIC ® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE EJECTOR PERFORMANCE DATA Wholesale Products Page: 6520-1 Dated: July 2008 Supersedes: January 2001 RPM: 1750 Discharge: 3” or 4” Solids: 2 ½” or 3” 25 0 15 30 45 60 75 75 125 175 225 275 325 375 1750 RPM 0 425 60 Hz MODEL NO. S3S & SB3S 5 10 15 20 25 U.S. GPM M 3 /HR HEAD (FEET) HEAD (METERS) 0 10 20 30 40 50 60 70 80 90 20 30 40 45 50 55 55 50 45 3 2 1.5 6.13" DIA. 5.88" DIA. 5.63" DIA. 5.25" DIA. 4.75" DIA. 0 0 15 30 45 60 75 100 200 300 400 500 600 700 1750 RPM 0 800 60 Hz MODEL NO. S4S & SB4S 5 10 15 20 25 0 25 50 75 100 125 150 175 U.S. GPM M 3 /HR HEAD (FEET) HEAD (METERS) 6.06" DIA. 6.25" DIA. 6.50" DIA. 6.75" DIA. 7.13" DIA. 7.38" DIA. 7.5" DIA. 3 5 7.5 20 30 40 50 55 60 60 55 50 S3S S4S
Transcript
Page 1: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

Conditions of Service:

GPM:______ TDH:______

The curves reflect maximum performance characteristics without exceeding full load (Nameplate) horsepower. All pumps have a service factor of 1.2. Operation is recommended in the bounded area with operational point within the curve limit. Performance curves are based on actual tests with clear water at 70° F. and 1280 feet site elevation.

HYDROMATIC®

S3S/SB3S & S4S/SB4SSINGLE SEAL SEWAGE EJECTOR

PERFORMANCE DATA

Wholesale Products Page: 6520-1Dated: July 2008

Supersedes: January 2001RPM: 1750 Discharge: 3” or 4”

Solids: 2 ½” or 3”

25

015

3045

6075

75 125 175 225 275 325 375

1750 RPM

0

425

60 Hz

MODEL NO. S3S & SB3S

510

1520

25

U.S. GPMM3/HR

HEA

D (F

EET)

HEA

D (M

ETER

S)

0 10 20 30 40 50 60 70 80 90

2030 40 45 50 55

55

5045

321.5

6.13" DIA.5.88" DIA.5.63" DIA.5.25" DIA.4.75" DIA.

0

015

3045

6075

100 200 300 400 500 600 700

1750 RPM

0

800

60 Hz

MODEL NO. S4S & SB4S

510

1520

25

0 25 50 75 100 125 150 175U.S. GPMM3/HR

HEA

D (F

EET)

HEA

D (M

ETER

S)

6.06" DIA.6.25" DIA.6.50" DIA.

6.75" DIA.

7.13" DIA.7.38" DIA.7.5" DIA.

35

7.5

20 30 4050

5560

60

5550

S3S

S4S

Page 2: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

DIMENSIONAL DATA

Wholesale Products Page: 6520-2Dated: January 2001

THIS PAGE LEFT INTENTIONALLY BLANK

HYDROMATIC®

S3S/SB3S & S4S/SB4SSINGLE SEAL SEWAGE EJECTOR

Page 3: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

All dimensions in inches.Casting dimensions may vary ± 1/8 inch.

HYDROMATIC®

S3SSINGLE SEAL SEWAGE EJECTOR

DIMENSIONAL DATA

A

B

F

G

I EC

H

D

3" 125# Flange

Wholesale Products Page: 6520-2ADated: April 2002

A B C D E F G H IS3S 20-5/8 10-1/2 13-3/8 4-3/8 8-1/4 5-5/8 4-7/8 13-3/8 5-1/8

Page 4: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

All dimensions in inches.Casting dimensions may vary ± 1/8 inch.

HYDROMATIC®

SB3SSINGLE SEAL SEWAGE EJECTOR

DIMENSIONAL DATA

A

F

G

C

H

D

B

EI

3" NPT

Wholesale Products Page: 6520-2BDated: April 2002

A B C D E F G H ISB3S 20-5/8 8-3/4 7-7/8 4-3/8 10-11/16 5-13/16 4-13/16 18-1/16 5-7/32

Page 5: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

All dimensions in inches.Casting dimensions may vary ± 1/8 inch.

HYDROMATIC®

S4SSINGLE SEAL SEWAGE EJECTOR

DIMENSIONAL DATA

I

D

A

G

F

B

E

C

H

4" 125# Flange

Wholesale Products Page: 6520-2CDated: April 2002

A B C D E F G H IS4S 23-1/8 12-3/4 16-3/8 6-1/2 10 7 5-3/4 20-3/16 6-3/8

Page 6: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

All dimensions in inches.Casting dimensions may vary ± 1/8 inch.

HYDROMATIC®

SB4SSINGLE SEAL SEWAGE EJECTOR

DIMENSIONAL DATA

I

D

B

C

A

G

F

E

H

4" NPT

Wholesale Products Page: 6520-2DDated: April 2002

A B C D E F G H ISB4S 23-1/8 11-3/8 8-5/16 6-1/2 11-1/8 7-1/16 5-13/16 20-3/16 6-1/2

Page 7: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

ELECTRICAL DATA

MODEL: S3S/SB3S & S4S/SB4S

Wholesale Products Page: 6520-3Dated: April 2002

Supersedes: January 2001

R.P.M. 1750MOTOR TYPE ENCLOSED, OIL COOLED INDUCTION, VFD SUITABLEMOTOR DESIGN NEMA TYPE B (3ø)  L (1ø)GENERAL INSULATION CLASS FSTATOR WINDING CLASS FMAXIMUM STATOR TEMPERATURE 311°FMOTOR PROTECTION N/AVOLTAGE TOLERANCE ±10%

HP

VOLT

AGE

PHAS

E

NEC

COD

E

SERV

ICE

FACT

OR

FULL

LOA

D AM

PS

RUN

KW

STAR

T AM

PS

STAR

T KV

A

RUN

KVA

MTR

. EFF

. 10

0% F

L

MTR

. EFF

. 75

% F

L

MTR

. EFF

. 50

% F

L

PWR.

FAC

T.

100%

FL

PWR.

FAC

T.

75%

FL

PWR.

FAC

T.

50%

FL

1.5 230 1 L 1.2 12.8 1.9 62 14.3 2.5 .60 .56 .48 .75 .68 .60

1.5

200

3 P 1.2

6.6

1.6

46

15.9 2.3 .70 .65 .56 .70 .62 .52230 5.8 40460 2.9 20575 2.3 16

2.0 230 1 L 1.2 12.8 1.9 62 14.3 2.5 .60 .56 .48 .75 .68 .60

2.0

200

3 L 1.2

6.6

1.6

46

15.9 2.3 .70 .65 .56 .70 .62 .52230 5.8 40460 2.9 20575 2.3 16

3.0 230 1 J 1.2 20.0 3.9 62 14.3 4.6 .58 .60 .57 .84 .81 .70

3.0

200

3 J 1.2

10.9

3.1

64.5

22.3 3.8 .72 .70 .64 .82 .80 .72230 9.5 56460 4.8 28575 3.8 22.5

5.0 200 1 G 1.2 29.5 5.7 125 28.8 6.8 .66 .65 .60 .84 .77 .64

5.0

200

3 L 1.2

17.6

4.8

108

37.4 6.1 .79 .77 .72 .78 .73 .62230 15.3 94460 7.6 47575 6.1 37.6

7.5

200

3 K 1.2

29.0

7.2

194

67.0 10.1 .78 .76 .71 .72 .66 .56230 25.2 168460 12.6 84575 10.1 67.2

HYDROMATIC®

S3S/SB3S & S4S/SB4SSINGLE SEAL SEWAGE EJECTOR

Page 8: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

ELECTRICAL DATA

Wholesale Products Page: 6520-4Dated: January 2001

THIS PAGE LEFT INTENTIONALLY BLANK

HYDROMATIC®

S3S/SB3S & S4S/SB4SSINGLE SEAL SEWAGE EJECTOR

Page 9: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

TECHNICAL DATAHYDROMATIC®

S3S/SB3SSINGLE SEAL SEWAGE EJECTORMODEL: S3S/SB3S

Wholesale Products Page: 6520-5Dated: April 2002

Supersedes: January 2001

Physical DataDISCHARGE SIZE 3” NPTSOLIDS SIZE 2 ½”IMPELLER TYPE BALANCED, SEMI OPEN, 2 VANECABLE LENGTH 30’ STANDARDPAINT PAINTED AFTER ASSEMBLY. DARK GREEN, WATER REDUCIBLE ENAMEL,

ONE COAT, AIR DRIED.

TemperatureMAXIMUM LIQUID 140°FMAXIMUM STATOR 311°FOIL FLASH POINT 390°FHEAT SENSOR Open: Closed:

257°F MAX. / 239°F MIN.194°F MAX. / 119°F MIN.

Technical DataPOWER CORD TYPE STW-A WATER RESISTANT 600V, 60°C

MAT

ERIA

LS O

F CO

NST

RUCT

ION MOTOR HOUSING CAST IRON ASTM A-48 CLASS 30

CASING CAST IRON ASTM A-48 CLASS 30IMPELLER CAST IRON ASTM A-48 CLASS 30MOTOR SHAFT 400 STAINLESS STEELHARDWARE 300 SERIES STAINLESS STEEL“O” RINGS BUNA-N

MECHANICAL SEALSStandard: CARBON / CERAMIC, TYPE 21, BF1C1

UPPER BEARING (RADIAL) SINGLE ROW — BALLLOWER BEARING (THRUST) SINGLE ROW — BALL

Page 10: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

TECHNICAL DATAHYDROMATIC®

S4S/SB4SSINGLE SEAL SEWAGE EJECTORMODEL: S4S/SB4S

Wholesale Products Page: 6520-6Dated: April 2002

Supersedes: January 2001

Physical DataDISCHARGE SIZE 4” NPTSOLIDS SIZE 3”IMPELLER TYPE BALANCED, SEMI OPEN, 2 VANECABLE LENGTH 15’ STANDARD

30’ OPTIONALPAINT PAINTED AFTER ASSEMBLY. DARK GREEN, WATER REDUCIBLE ENAMEL,

ONE COAT, AIR DRIED.

TemperatureMAXIMUM LIQUID 140°FMAXIMUM STATOR 311°FOIL FLASH POINT 390°FHEAT SENSOR Open: Closed:

257°F MAX. / 239°F MIN.194°F MAX. / 119°F MIN.

Technical DataPOWER CORD TYPE STW-A WATER RESISTANT 600V, 60°C

MAT

ERIA

LS O

F CO

NST

RUCT

ION MOTOR HOUSING CAST IRON ASTM A-48 CLASS 30

CASING CAST IRON ASTM A-48 CLASS 30IMPELLER CAST IRON ASTM A-48 CLASS 30MOTOR SHAFT 400 STAINLESS STEELHARDWARE 300 SERIES STAINLESS STEEL“O” RINGS BUNA-N

MECHANICAL SEALSStandard: CARBON / CERAMIC, TYPE 21, BF1C1

UPPER BEARING (RADIAL) SINGLE ROW — BALLLOWER BEARING (THRUST) SINGLE ROW — BALL

Page 11: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

SPECIFICATION DATA

1.01 GENERAL Contractor shall furnish all labor, materials, equipment and incidentals required to provide __________

(Qty.) submersible centrifugal non clog sewage pump(s) as specified herein. The pump models covered in this specification are the S3S/SB3S and S4S/SB4S. The pump furnished for this application shall be MODEL ____________ as manufactured by Hydromatic Pumps.

2.01 DESIGN CONDITIONS Each pump shall be rated ________ H.P., ________ volts, ________ phase, ________ hertz and operate

at ________ RPM.

3.01 OPERATING CONDITIONS The pump shall deliver ________ U.S. GPM/LPS at feet/meters TDH, and handle a ________ inch solid.

The curve submitted for approval shall state, in addition to head and capacity performance, solid handling capability, amp rating, and design impeller diameter.

4.01 CONSTRUCTION Each pump shall be of the sealed submersible type, incorporating features normally found in pumps

furnished for the heavy duty industrial or municipal markets. These features include:

1. The seal housing for the S3S/SB3S and S4S/SB4S is corrosion resistant high density thermoplastic.

2. The pump inlet shall be open and clear, without screening to provide access for sewage and solids.

3. All external mating parts shall be machined and Buna N, O-Ring sealed. 4. All fasteners exposed to the pumped liquid shall be 300 series stainless steel. 5. All power cords shall be water resistant UL or CSA approved, with double insulation, and sized

as a function of Amp. draw.

5.01 MOTOR AND SHAFT The stator, rotor and bearings shall be mounted in a sealed submersible type housing. Single phase

motors shall be split phase or capacitor start with centrifugal switch. Three phase motors shall be Polyphase. Full Load and Locked Rotor Amps. as well as Start and Run winding resistance shall be tabulated for each pump.

6.01 BEARINGS, SHAFT AND MECHANICAL SEAL An upper radial and lower thrust bearing shall be required. These shall be heavy duty single row ball

bearings which are permanently and continuously lubricated and cooled by the dielectric oil which fills the motor housing. The motor shaft shall be stainless steel and sealed from the pumped liquid with a carbon ceramic mechanical seal.

MODELS: S3S/SB3S & S4S/SB4S

Wholesale Products Page: 6520-7Dated: January 2001

HYDROMATIC®

S3S/SB3S & S4S/SB4SSINGLE SEAL SEWAGE EJECTOR

Page 12: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

USA CANADA293 Wright Street, DelAvAN, Wi 53115 WWW.hYDrOMAtiC.COM 269 trilliUM Drive, KitCheNer, ONtAriO, CANADA N2g 4W5Ph: 888-957-8677 OrDerS FAX: 800-426-9446 Ph: 519-896-2163 OrDerS FAX: 519-896-6337

Because we are continuously improving our products and services, Pentair reserves the right to change specifications without prior notice.

© 2013 Pentair ltd. All rights reserved. W-01-260 (03/25/13)

SPECIFICATION DATA

7.01 IMPELLER The Impeller shall be high capacity, two vane, non clog design with pump out vanes on the back side.

These vanes wash out grit and stringy material that will damage the shaft and mechanical seal.

8.01 AUTOMATIC CONTROL All pumps should be capable of automatic operation.

9.01 PRESSURE SWITCH The Single Phase pumps are furnished with a pressure diaphragm switch that features a piggy-back plug

that allows the pump to be operated manually without removal from the sump.

10.01 FLOAT SWITCH The Single Phase pump is supplied with a tilt-sensitive wide-angle float switch is sealed in a non-

corrosive PVC enclosure. The unit is UL listed for water and sewage and CSA certified. The float switch shall also be fitted with a piggy-back plug that allows the pump to be operated manually without removal from the sump.

11.01 MANUAL CONTROL The Single Phase pumps are not supplied with any type of automatic control. A super or double wide angle

piggy-back float switch can be supplied and fitted to these pumps.

12.01 PAINTING All cast iron parts shall be painted before assembly with a water reducible alkyd air dried enamel.

The paint shall be applied in one coat with a minimum thickness of 3 to 4 mils.

13.01 TESTING All pumps shall be individually tested to include the following:

1. The pump and power cord shall be visually inspected for imperfections, cuts or nicks. 2. The pump shall have a ground continuity check and the motor chamber shall be Hi-potted

to test for moisture content and/or insulation defects. 3. The motor and volute housing shall be pressurized and a 10 second air leak decay test run. 4. Oil is added, and the pump is run. Voltage and current are monitored visually, electronically,

and the tester listens for any noise or malfunction.

Wholesale Products Page: 6520-8Dated: January 2001

HYDROMATIC®

S3S/SB3S & S4S/SB4SSINGLE SEAL SEWAGE EJECTOR

Page 13: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

TOTA

L H

EAD

IN F

EET

0

20

40

60

80

100

100 20 30 40 50Capacity-U.S. G.P.M.

60

2 HP

Conditions of Service:

GPM:______ TDH:______

The curves reflect maximum performance characteristics without exceeding full load (Nameplate) horsepower. All pumps have a service factor of 1.2. Operation is recommended in the bounded area with operational point within the curve limit. Performance curves are based on actual tests with clear water at 70° F. and 1280 feet site elevation.

PERFORMANCE DATA

Wholesale Products Page: 6710-1Dated: January 2001

RPM: 3450 Discharge: 1 ¼” Solids: 2”

HYDROMATIC®

HPGR200SUBMERSIBLE SEWAGE GRINDER

Page 14: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

All dimensions in inches. Metric for international use. Component dimensions may vary ± 1/8 inch. Dimensional data not for construction purpose unless certified. Dimensions and weights are approximate. On/Off level adjustable. We reserve the right to make revisions to our product (s) and the product (s) specifications without notice.

DIMENSIONAL DATA

15 3/8"(390.52 mm)

3 7/16"(77.79 mm)

14 5/8"(371.48 mm)

16 7/16"(417.51mm)

7 3/4"(198.85 mm)

5 3/8"(136.52 mm)

Wholesale Products Page: 6710-2Dated: January 2001

HYDROMATIC®

HPGR200SUBMERSIBLE SEWAGE GRINDER

Page 15: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

ELECTRICAL DATA

MODEL: HPGR200R.P.M. 3450MOTOR TYPE ENCLOSED, OIL COOLED INDUCTION, CAP STARTMOTOR DESIGN NEMA TYPE A (1ø)GENERAL INSULATION CLASS BSTATOR WINDING CLASS FMAXIMUM STATOR TEMPERATURE 130°CVOLTAGE TOLERANCE ±10%

HP VOLTAGE PHASE NEC CODE

SERVICE FACTOR

FULL LOADAMPS

RUNKW

START KVA

RUN KVA

2 230 1 J 1.0 15.0 - 11.9 3.2

Wholesale Products Page: 6710-3Dated: January 2001

HYDROMATIC®

HPGR200SUBMERSIBLE SEWAGE GRINDER

Page 16: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

TECHNICAL DATA

MODEL: HPGR200Physical DataDISCHARGE SIZE 1 ¼” NPTIMPELLER TYPE SEMI-OPEN 5 VANECABLE LENGTH 15’ STANDARDPAINT PAINTED AFTER ASSEMBLY. DARK GREEN, ENAMEL, ONE COAT, AIR DRIED.

TemperatureMAXIMUM LIQUID 140°FMAXIMUM STATOR 266°FOIL FLASH POINT 390°FHEAT SENSOR Open: Closed:

257°F MAX. / 239°F MIN.194°F MAX. / 149°F MIN.

Technical DataPOWER CORD TYPE SOW / SOW-A WATER RESISTANT 600V, 60°C

MAT

ERIA

LS O

F CO

NST

RUCT

ION MOTOR HOUSING CAST IRON ASTM A-48 CLASS 30

CASING CAST IRON ASTM A-48 CLASS 30IMPELLER RED BRASS #85-5-5-5,

ASTM B584-836 / VALOX 420 SEO WITH BRONZE INSERT

CUTTERSStationary:

Upper (Axial):Lower (Radial):

440C STAINLESS STEEL HARDENED TO 55-60 ROCKWELL C440C STAINLESS STEEL HARDENED TO 55-60 ROCKWELL C440C STAINLESS STEEL HARDENED TO 55-60 ROCKWELL C

MOTOR SHAFT 416 STAINLESS STEELHARDWARE 300 SERIES STAINLESS STEEL“O” RINGS BUNA-N

MECHANICAL SEALSStandard:Optional:

UPPER CARBON / CERAMIC / BUNA-N, TYPE 21LOWER TUNGSTEN CARBIDE / TUNGSTEN CARBIDE, TYPE 21, BD1D1

UPPER BEARING (RADIAL) SINGLE ROW BALL 6203LOWER BEARING (THRUST) SINGLE ROW BALL 6306MIN. B-10 BEARING LIFE 50,000 Hrs

Wholesale Products Page: 6710-4Dated: January 2001

HYDROMATIC®

HPGR200SUBMERSIBLE SEWAGE GRINDER

Page 17: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

SPECIFICATION DATA

1.01 GENERAL Contractor shall furnish all labor, materials, equipment and incidentals required to provide __________

(Qty.) submersible centrifugal non clog sewage pump(s) as specified herein. The pump model covered in this specification is the HPGR200. The pump furnished for this application shall be MODEL ____________ as manufactured by Hydromatic Pumps.

2.01 DESIGN CONDITIONS Each pump shall be rated ________ H.P., ________ volts, ________ phase, ________ hertz and operate

at ________ RPM.

3.01 OPERATING CONDITIONS The pump shall deliver ________ U.S. GPM/LPS at feet/meters TDH, and handle a ________ inch solid.

The curve submitted for approval shall state, in addition to head and capacity performance, solid handling capability, amp rating, and design impeller diameter.

4.01 CONSTRUCTION Each pump shall be of the sealed submersible type, incorporating features normally found in pumps

furnished for the heavy duty industrial or municipal markets. These features include:

1. The seal housing for the HPGR200 is corrosion resistant high density thermoplastic. 2. The pump inlet shall be open and clear, without screening to provide access for sewage

and solids. 3. All external mating parts shall be machined and Buna N, O-Ring sealed. 4. All fasteners exposed to the pumped liquid shall be 300 series stainless steel. 5. All power cords shall be water resistant UL or CSA approved, with double insulation, and sized

as a function of Amp. draw.

5.01 MOTOR AND SHAFT The stator, rotor and bearings shall be mounted in a sealed submersible type housing. Single phase

motors shall be split phase or capacitor start with centrifugal switch. Three phase motors shall be Polyphase. Full Load and Locked Rotor Amps. as well as Start and Run winding resistance shall be tabulated for each pump.

6.01 BEARINGS, SHAFT AND MECHANICAL SEAL An upper radial and lower thrust bearing shall be required. These shall be heavy duty single row ball

bearings which are permanently and continuously lubricated and cooled by the dielectric oil which fills the motor housing. The motor shaft shall be stainless steel and sealed from the pumped liquid with a carbon ceramic mechanical seal.

MODEL: HPGR200

Wholesale Products Page: 6710-5Dated: January 2001

HYDROMATIC®

HPGR200SUBMERSIBLE SEWAGE GRINDER

Page 18: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

USA CANADA293 WRiGHt StReet, DelAvAN, Wi 53115 WWW.HYDROMAtiC.COM 269 tRilliUM DRive, KitCHeNeR, ONtARiO, CANADA N2G 4W5PH: 888-957-8677 ORDeRS FAX: 800-426-9446 PH: 519-896-2163 ORDeRS FAX: 519-896-6337

Because we are continuously improving our products and services, Pentair reserves the right to change specifications without prior notice.

© 2013 Pentair ltd. All Rights Reserved. W-01-260 (03/25/13)

SPECIFICATION DATA

7.01 IMPELLER The Impeller shall be high capacity, two vane, non clog design with pump out vanes on the back side.

These vanes wash out grit and stringy material that will damage the shaft and mechanical seal.

8.01 AUTOMATIC CONTROL All single phase pumps should be capable of automatic operation.

9.01 PRESSURE SWITCH The Single Phase pumps are furnished with a pressure diaphragm switch that features a piggy-back plug

that allows the pump to be operated manually without removal from the sump.

10.01 FLOAT SWITCH The Single Phase pump is supplied with a tilt-sensitive wide-angle float switch is sealed in a non-

corrosive PVC enclosure. The unit is UL listed for water and sewage and CSA certified. The float switch shall also be fitted with a piggy-back plug that allows the pump to be operated manually without removal from the sump.

11.01 MANUAL CONTROL The Single Phase pumps are not supplied with any type of automatic control. A super or double wide angle

piggy-back float switch can be supplied and fitted to these pumps.

12.01 PAINTING All cast iron parts shall be painted before assembly with a water reducible alkyd air dried enamel.

The paint shall be applied in one coat with a minimum thickness of 3 to 4 mils.

13.01 TESTING All pumps shall be individually tested to include the following:

1. The pump and power cord shall be visually inspected for imperfections, cuts or nicks. 2. The pump shall have a ground continuity check and the motor chamber shall be Hi-potted

to test for moisture content and/or insulation defects. 3. The motor and volute housing shall be pressurized and a 10 second air leak decay test run. 4. Oil is added, and the pump is run. Voltage and current are monitored visually, electronically,

and the tester listens for any noise or malfunction.

Wholesale Products Page: 6710-6Dated: January 2001

HYDROMATIC®

HPGR200SUBMERSIBLE SEWAGE GRINDER

Page 19: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

TOTA

L HE

AD IN

FEE

T

40

35

30

25

20

15

100 10 20 30 40 50 60 70 80 90 100

CAPACITY GALLONS PER MINUTE

SPX50H

SPX50

Conditions of Service:

GPM:______ TDH:______

The curves reflect maximum performance characteristics without exceeding full load (Nameplate) horsepower. All pumps have a service factor of 1.2. Operation is recommended in the bounded area with operational point within the curve limit. Performance curves are based on actual tests with clear water at 70° F. and 1280 feet site elevation.

PERFORMANCE DATA

Wholesale Products Page: 6800-1Dated: October 2007

SPX50 RPM: 1750 Discharge: 2” Solids: 2”SPX50H RPM: 1750 Discharge: 1 ½” Solids: ¾”

HYDROMATIC®

SPX50/SPX50HEXPLOSION PROOF, SEWAGE EJECTOR

Page 20: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

All dimensions in inches. Metric for international use. Component dimensions may vary ± 1/8 inch. Dimensional data not for construction purpose unless certified. Dimensions and weights are approximate. On/Off level adjustable. We reserve the right to make revisions to our product (s) and the product (s) specifications without notice.

DIMENSIONAL DATA

21-1/8"(537)

2"(51)

5-13/32"(137)

9-1/32"(229)

3-19/32"(91)

3-31/32"(101)

(239)9-13/32"

2" NPT

Wholesale Products Page: 6800-2Dated: October 2007

HYDROMATIC®

SPX50/SPX50HEXPLOSION PROOF, SEWAGE EJECTOR

4"(102)

4"(102)

9-5/16"(236)

(241)9-15/32"

NPT1-1/2"

4-13/16"(122)

1-31/32"(50)

20"(508)

SPX50[Dimensions in mm]

SPX50H[Dimensions in mm]

Page 21: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

ELECTRICAL DATA

MODEL: SPX50

Wholesale Products Page: 6800-3Dated: October 2007

HYDROMATIC®

SPX50/SPX50HEXPLOSION PROOF, SEWAGE EJECTOR

R.P.M. 1750MOTOR TYPE OIL COOLED INDUCTION, CAPACITOR STARTMOTOR DESIGN NEMA TYPE TYPE NGENERAL INSULATION CLASS BMAXIMUM STATOR TEMPERATURE 266°F (130°C)MOTOR PROTECTION WINDING HEAT SENSORS

HP VOLTAGE PHASE NEC CODE SERVICE FACTOR FULL LOAD AMPS1/2 200/230 1 - 1 5.9/5.3

MODEL: SPX50HR.P.M. 1750MOTOR TYPE OIL COOLED INDUCTION, CAPACITOR STARTMOTOR DESIGN NEMA TYPE TYPE NGENERAL INSULATION CLASS BMAXIMUM STATOR TEMPERATURE 266°F (130°C)MOTOR PROTECTION WINDING HEAT SENSORS

HP VOLTAGE PHASE NEC CODE SERVICE FACTOR FULL LOAD AMPS1/2 200/230 1 - 1 5.9/5.3

Page 22: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

TECHNICAL DATA

MODEL: SPX50/SPX50HPhysical DataDISCHARGE SIZE 2” NPT (SPX50), 1 ½” NPT (SPX50H)SOLIDS SIZE 2” (SPX50), ¾” (SPX50H)IMPELLER TYPE RECESSESCABLE LENGTH 20’ STANDARDPAINT

TemperatureMAXIMUM LIQUID 140°FMAXIMUM STATOR 266°F (130°C)OIL FLASH POINT 390°F

Technical DataPOWER CORD TYPE SOW / SOW-A

MAT

ERIA

LS O

F CO

NST

RUCT

ION MOTOR HOUSING CAST IRON

CASING CAST IRONIMPELLER CAST IRONMOTOR SHAFT 416 STAINLESS STEELHARDWARE 416 STAINLESS STEEL“O” RINGS -

MECHANICAL SEALSStandard: CARBON / CERAMIC

UPPER BEARING BALL RADIAL 6203LOWER BEARING BALL - THRUST 6306

Wholesale Products Page: 6800-4Dated: October 2007

HYDROMATIC®

SPX50/SPX50HEXPLOSION PROOF, SEWAGE EJECTOR

Page 23: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

SPECIFICATION DATA

1.01 GENERAL Contractor shall furnish all labor, materials, equipment and incidentals required to provide __________

(Qty.) submersible centrifugal sewage pump(s) as specified herein. The pump models covered in this specification are the SPX50/SPX50H. The pump furnished for this application shall be MODEL ____________ as manufactured by Hydromatic Pumps.

2.01 DESIGN CONDITIONS Each pump shall be rated ________ H.P., ________ volts, ________ phase, ________ hertz and operate

at ________ RPM.

3.01 OPERATING CONDITIONS The pump shall deliver ________ U.S. GPM/LPS at feet/meters TDH, and handle a ________ inch solid.

The curve submitted for approval shall state, in addition to head and capacity performance, solid handling capability, amp rating, and design impeller diameter.

4.01 CONSTRUCTION Each pump shall be of the sealed submersible type, incorporating features normally found in pumps

furnished for the residential market. These features include:

1. The seal housing for the SPX50/SPX50H is corrosion resistant cast iron. 2. The pump inlet shall be open and clear, without screening to provide access for sewage

and solids. 3. All external mating parts shall be machined and Buna N, O-Ring sealed. 4. All fasteners exposed to the pumped liquid shall be 300 series stainless steel. 5. All power cords shall be water resistant UL or CSA approved, with double insulation, and sized

as a function of Amp. draw.

5.01 MOTOR AND SHAFT The stator, rotor and bearings shall be mounted in a sealed submersible type housing. Single phase

motors shall be split phase or capacitor start with centrifugal switch. Three phase motors shall be Polyphase. Full Load and Locked Rotor Amps as well as Start and Run winding resistance shall be tabulated for each pump.

6.01 BEARINGS, SHAFT AND MECHANICAL SEAL An upper radial and lower thrust bearing shall be required. These shall be heavy duty single row ball

bearings which are permanently and continuously lubricated and cooled by the dielectric oil which fills the motor housing. The motor shaft shall be stainless steel and sealed from the pumped liquid with a carbon ceramic mechanical seal.

MODELS: SPX50/SPX50H

Wholesale Products Page: 6800-5Dated: October 2007

HYDROMATIC®

SPX50/SPX50HEXPLOSION PROOF, SEWAGE EJECTOR

Page 24: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

USA CANADA293 WrigHt Street, DelAvAN, Wi 53115 WWW.HYDrOMAtiC.COM 269 trilliUM Drive, KitCHeNer, ONtAriO, CANADA N2g 4W5PH: 888-957-8677 OrDerS FAX: 800-426-9446 PH: 519-896-2163 OrDerS FAX: 519-896-6337

Because we are continuously improving our products and services, Pentair reserves the right to change specifications without prior notice.

© 2013 Pentair ltd. All rights reserved. W-01-260 (03/25/13)

SPECIFICATION DATA

7.01 IMPELLER The Impeller shall be high capacity, two vane, non clog design with pump out vanes on the back side.

These vanes wash out grit and stringy material that will damage the shaft and mechanical seal.

8.01 AUTOMATIC CONTROL All single phase pumps should be capable of automatic operation.

9.01 MANUAL CONTROL The Single Phase pumps are not supplied with any type of automatic control. A super or double wide angle

piggy-back float switch can be supplied and fitted to these pumps.

10.01 PAINTING All cast iron parts shall be painted before assembly with a water reducible alkyd air dried enamel.

The paint shall be applied in one coat with a minimum thickness of 3 to 4 mils.

12.01 TESTING All pumps shall be individually tested to include the following:

1. The pump and power cord shall be visually inspected for imperfections, cuts or nicks. 2. The pump shall have a ground continuity check and the motor chamber shall be Hi-potted

to test for moisture content and/or insulation defects. 3. The motor and volute housing shall be pressurized and a 10 second air leak decay test run. 4. Oil is added, and the pump is run. Voltage and current are monitored visually, electronically,

and the tester listens for any noise or malfunction.

Wholesale Products Page: 6800-6Dated: October 2007

HYDROMATIC®

SPX50/SPX50HEXPLOSION PROOF, SEWAGE EJECTOR

Page 25: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

Conditions of Service:

GPM:______ TDH:______

The curves reflect maximum performance characteristics without exceeding full load (Nameplate) horsepower. All pumps have a service factor of 1.2. Operation is recommended in the bounded area with operational point within the curve limit. Performance curves are based on actual tests with clear water at 70° F. and 1280 feet site elevation.

PERFORMANCE DATA

Wholesale Products Page: 6650-1Dated: June 2007

RPM: 3450 Discharge: * Solids: ⅟₁₆”

HYDROMATIC®

HE8/HE12/HE20/HE25/HE30/HE35/HE50HIGH HEAD FILTERED EFFLUENT

Pump ModelVoltageHP½½¾1

115230230230

HE8-51HE8-52HE8-72HE8-12

GALLONS PER MINUTE

8 GPM

0 2 4 6 8 10 12 14 16 18 20

500

400

300

200

100TOTA

L HE

AD IN

FEE

T

1 HP

3/4 HP

1/2 HP

*Discharge Size 1-1/4" NPT

Pump ModelVoltageHP½½¾1

115230230230

GALLONS PER MINUTE

12 GPM

0 2 4 6 8 10 12 14 16 18 20

400

300

200

100TOTA

L HE

AD IN

FEE

T

1 HP

3/4 HP

1/2 HP

HE12-51HE12-52HE12-72HE12-12

*Discharge Size 1-1/4" NPT

Pump ModelVoltageHP½½¾1

115230230230

HE20-51HE20-52HE20-72HE20-12

GALLONS PER MINUTE

20 GPM

0 3 6 9 12 15 18 21 24 27 30

400

300

200

100TOTA

L HE

AD IN

FEE

T

1 HP

3/4 HP

1/2 HP

1-1/2 HP

HE20-1522301½

*Discharge Size 1-1/4" NPT

0 5 10 15 20 25 30 35 40 45 50

25 GPM

TOTA

L HE

AD IN

FEE

T

Pump ModelVoltageHPGALLONS PER MINUTE

1 230230

HE25-12HE25-1521½

1 HP

1-1/2 HP300

200

100

0

*Discharge Size 2" NPT

30 GPM

Pump ModelVoltageHPGALLONS PER MINUTE

120

80

40

TOTA

L HE

AD IN

FEE

T

0 5 10 15 20 25 30 35 40 45 50

½ 115 HE30-51

1/2 HP

*Discharge Size 1-1/4" NPT

35 GPM

Pump ModelVoltageHPGALLONS PER MINUTE

150

100

50

TOTA

L HE

AD IN

FEE

T

0 5 10 15 20 25 30 35 40 45 50

1 230230

HE35-12HE35-152

1 HP

1-1/2 HP

*Discharge Size 2" NPT

GALLONS PER MINUTE

50 GPM

400

300

200

100

TOTA

L HE

AD IN

FEE

T

Pump ModelVoltageHP½1 230 HE50-152

*Discharge Size 2" NPT500

1-1/2 HP

0 10 20 30 40 50 60 70 80 90

Page 26: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

All dimensions in inches. Metric for international use. Component dimensions may vary ± 1/8 inch. Dimensional data not for construction purpose unless certified. Dimensions and weights are approximate. On/Off level adjustable. We reserve the right to make revisions to our product (s) and the product (s) specifications without notice.

DIMENSIONAL DATA

A

B

D

E

CM

MODEL A B C D E M DISCHARGE

HE8-51 24-1/4” 9-1/2” 12” 14-3/4” 20-3/4” 19-1/2” 1-1/4”HE8-52 24-1/4” 9-1/2” 12” 14-3/4” 20-3/4” 19-1/2” 1-1/4”HE8-72 26” 10-1/2” 13” 15-1/2” 22-1/2” 21” 1-1/4”HE8-12 29-3/4” 11-3/4” 14-1/4” 18” 26-1/4” 23” 1-1/4”

HE12-51 23-1/4” 9-1/2” 12” 13-3/4” 19-3/4” 20” 1-1/4”HE12-52 23-1/4” 9-1/2” 12” 13-3/4” 19-3/4” 20” 1-1/4”HE12-72 26-1/4” 10-1/2” 13” 15-3/4” 22-3/4” 21-1/2” 1-1/4”HE12-12 29” 11-3/4” 14-1/4” 17-1/4” 25-1/2” 23-1/2” 1-1/4”HE20-51 23-1/2” 9-1/2” 12” 14” 20” 20” 1-1/4”HE20-52 23-1/2” 9-1/2” 12” 14” 20” 20” 1-1/4”HE20-72 25-1/2” 10-1/2” 13” 15” 22” 22” 1-1/4”HE20-12 27-1/2” 11-3/4” 14-1/4” 15-3/4” 24” 26” 1-1/4”

HE20-152 34-1/4” 15-1/4” 17-3/4” 19” 30-3/4” 27” 1-1/4”HE30-51 23-1/2” 9-1/2” 12” 14” 20-1/2” 20” 1-1/4”HE25-12 29-3/4” 11-3/4” 14-1/4” 18” 28” 27” 2”

HE25-152 36-1/4” 15-1/4” 17-3/4” 21” 34-1/2” 29” 2”HE35-12 26-1/4” 11-3/4” 14-1/4” 14-1/2” 24-1/2” 27” 2”

HE35-152 33-3/4” 15-1/4” 17-3/4” 18-1/2” 32” 29” 2”HE50-152 34” 15-1/4” 17-3/4” 21” 32-1/4” 29” 2”

A = Overall Pump HeightB = Motor HeightC = Intake HeightD = Pump End HeightE = Bypass Orifice HeightM = Minimum Liquid LevelDischarge = Discharge Size (NPT)

Wholesale Products Page: 6650-2Dated: June 2007

HYDROMATIC®

HE8/HE12/HE20/HE25/HE30/HE35/HE50HIGH HEAD FILTERED EFFLUENT

Page 27: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

ELECTRICAL DATA

MODEL: HE8/HE12/HE20/HE25/HE30/HE35/HE50

Wholesale Products Page: 6650-3Dated: June 2007

HYDROMATIC®

HE8/HE12/HE20/HE25/HE30/HE35/HE50HIGH HEAD FILTERED EFFLUENT

R.P.M. 3450MOTOR PROTECTION BUILT IN OVERLOAD AND SURGE PROTECTION

HP VOLTAGE PHASE NEC CODE SERVICE FACTOR FULL LOAD AMPS

1/2115

1 - 1

10.5

230

63/4 81 9.8

1-1/2 13.1

Page 28: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

TECHNICAL DATA

MODEL: HE8/HE12/HE20/HE25/HE30/HE35/HE50Physical DataDISCHARGE SIZE (NPT) (1 ¼” on 8, 12, 20, and 30 GPM pumps) (2” on 25 and 35 GPM pumps)SOLIDS SIZE ⅟₁₆”IMPELLER TYPE -CABLE LENGTH 20’ STANDARD

30’ OPTIONALPAINT -

TemperatureMAXIMUM LIQUID 122°FMAXIMUM STATOR -OIL FLASH POINT -

Technical DataPOWER CORD TYPE SJTW, STW-A

MAT

ERIA

LS O

F CO

NST

RUCT

ION MOTOR HOUSING STAINLESS STEEL

CASING STAINLESS STEELIMPELLER THERMOPLASTICMOTOR SHAFT -HARDWARE STAINLESS STEEL“O” RINGS -

MECHANICAL SEALSStandard: -

UPPER BEARING -LOWER BEARING -

Wholesale Products Page: 6650-4Dated: June 2007

HYDROMATIC®

HE8/HE12/HE20/HE25/HE30/HE35/HE50HIGH HEAD FILTERED EFFLUENT

Page 29: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

SPECIFICATION DATA

1.01 GENERAL Contractor shall furnish all labor, materials, equipment and incidentals required to provide __________

(Qty.) submersible centrifugal effluent pump(s) as specified herein. The pump models covered in this specification are the HE8, HE12, HE20, HE25, HE30, HE35 and HE50. The pump furnished for this application shall be MODEL ____________ as manufactured by Hydromatic Pumps.

2.01 DESIGN CONDITIONS Each pump shall be rated ________ H.P., ________ volts, ________ phase, ________ hertz and operate

at ________ RPM.

3.01 OPERATING CONDITIONS The pump shall deliver ________ U.S. GPM/LPS at feet/meters TDH, and handle a ________ inch solid.

The curve submitted for approval shall state, in addition to head and capacity performance, solid handling capability, amp rating, and design impeller diameter.

4.01 CONSTRUCTION Each pump shall be of the sealed submersible type, incorporating features normally found in pumps

furnished for the residential market. These features include:

1. The seal housing for the HE8, HE12, HE20, HE25, HE30, HE35 and HE50 is corrosion resistant stainless steel.

2. The pump inlet shall be double screened. 3. All power cords shall be water resistant UL or CSA approved.

5.01 MOTOR AND SHAFT The stator, rotor and bearings shall be mounted in a sealed submersible type housing. Single phase

motors shall be split phase or capacitor start with centrifugal switch. Three phase motors shall be Polyphase. Full Load and Locked Rotor Amps as well as Start and Run winding resistance shall be tabulated for each pump.

6.01 IMPELLER The Impeller shall be thermoplastic construction.

7.01 MANUAL CONTROL The Single Phase pumps are not supplied with any type of automatic control.

8.01 TESTING All pumps shall be individually tested to include the following:

1. The pump and power cord shall be visually inspected for imperfections, cuts or nicks. 2. The pump shall have a ground continuity check and the motor chamber shall be Hi-potted

to test for moisture content and/or insulation defects.

MODEL: HE8/HE12/HE20/HE25/HE30/HE35/HE50

Wholesale Products Page: 6650-5Dated: June 2007

HYDROMATIC®

HE8/HE12/HE20/HE25/HE30/HE35/HE50HIGH HEAD FILTERED EFFLUENT

Page 30: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

USA CANADA293 WrigHt StrEEt, DElAvAN, Wi 53115 WWW.HYDrOMAtiC.COM 269 trilliUM DrivE, KitCHENEr, ONtAriO, CANADA N2g 4W5PH: 888-957-8677 OrDErS FAX: 800-426-9446 PH: 519-896-2163 OrDErS FAX: 519-896-6337

Because we are continuously improving our products and services, Pentair reserves the right to change specifications without prior notice.

© 2013 Pentair ltd. All rights reserved. W-01-260 (03/25/13)

SPECIFICATION DATA

THIS PAGE LEFT INTENTIONALLY BLANK

Wholesale Products Page: 6650-6Dated: June 2007

HYDROMATIC®

HE8/HE12/HE20/HE25/HE30/HE35/HE50HIGH HEAD FILTERED EFFLUENT

Page 31: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

CAPACITY-U.S. G.P.M.

TOTA

L HE

AD IN

FEE

T

0 4 8 12 16 20 24

25

20

15

10

5

0

1/6 HP

Conditions of Service:

GPM:______ TDH:______

The curves reflect maximum performance characteristics without exceeding full load (Nameplate) horsepower. All pumps have a service factor of 1.2. Operation is recommended in the bounded area with operational point within the curve limit. Performance curves are based on actual tests with clear water at 70° F. and 1280 feet site elevation.

HYDROMATIC®

HUP1/6 HP SUBMERSIBLE UTILITY PUMP

PERFORMANCE DATA

Wholesale Products Page: 6660-1Dated: January 2001

RPM: 1550 Discharge: 1” Solids: ⅛”

Page 32: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

All dimensions in inches. Metric for international use. Component dimensions may vary ± 1/8 inch. Dimensional data not for construction purpose unless certified. Dimensions and weights are approximate. On/Off level adjustable. We reserve the right to make revisions to our product (s) and the product (s) specifications without notice.

DIMENSIONAL DATA

6-1/32"(153)

5-5/16"(135)

2-5/16"(59)

7-3/4”(197)

8-45/64”(221)

1-25/64"(35)

8-27/64”(214)

7-1/8”(181)

HYDROMATIC®

HUP1/6 HP SUBMERSIBLE UTILITY PUMP

Wholesale Products Page: 6660-2Dated: January 2001

Page 33: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

ELECTRICAL DATA

MODEL: HUPR.P.M. 1550MOTOR TYPE P.S.C., AIR FILLED AND WATER COOLED

HP VOLTAGE PHASE NEC CODE SERVICE FACTOR FULL LOAD AMPS1/6 115 1 - 1 2

HYDROMATIC®

HUP1/6 HP SUBMERSIBLE UTILITY PUMP

Wholesale Products Page: 6660-3Dated: January 2001

Page 34: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

TECHNICAL DATA

MODEL: HUPPhysical DataDISCHARGE SIZE 1” NPTSOLIDS SIZE ⅛”IMPELLER TYPE -CABLE LENGTH 10’ STANDARDPAINT -

TemperatureMAXIMUM LIQUID 140°FMAXIMUM STATOR -OIL FLASH POINT -

Technical DataPOWER CORD TYPE SJTW, STW-A

MAT

ERIA

LS O

F CO

NST

RUCT

ION MOTOR HOUSING THERMOPLASTIC

CASING THERMOPLASTICIMPELLER THERMOPLASTICMOTOR SHAFT -HARDWARE -“O” RINGS -

MECHANICAL SEALSStandard: -

UPPER BEARING -LOWER BEARING -

HYDROMATIC®

HUP1/6 HP SUBMERSIBLE UTILITY PUMP

Wholesale Products Page: 6660-4Dated: January 2001

Page 35: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

SPECIFICATION DATA

1.01 GENERAL Contractor shall furnish all labor, materials, equipment and incidentals required to provide __________

(Qty.) submersible centrifugal non clog sewage pump(s) as specified herein. The pump model covered in this specification is the HUP. The pump furnished for this application shall be MODEL ____________ as manufactured by Hydromatic Pumps.

2.01 DESIGN CONDITIONS Each pump shall be rated ________ H.P., ________ volts, ________ phase, ________ hertz and operate

at ________ RPM.

3.01 OPERATING CONDITIONS The pump shall deliver ________ U.S. GPM/LPS at feet/meters TDH, and handle a ________ inch solid.

The curve submitted for approval shall state, in addition to head and capacity performance, solid handling capability, amp rating, and design impeller diameter.

4.01 CONSTRUCTION Each pump shall be of the sealed submersible type, incorporating features normally found in pumps

furnished for the heavy duty industrial or municipal markets. These features include:

1. The seal housing for the HUP is corrosion resistant high density thermoplastic. 2. The pump inlet shall be open and clear, without screening to provide access for sewage

and solids. 3. All external mating parts shall be machined and Buna N, O-Ring sealed. 4. All fasteners exposed to the pumped liquid shall be 300 series stainless steel. 5. All power cords shall be water resistant UL or CSA approved, with double insulation, and sized

as a function of Amp. draw.

5.01 MOTOR AND SHAFT The stator, rotor and bearings shall be mounted in a sealed submersible type housing. Single phase

motors shall be split phase or capacitor start with centrifugal switch. Three phase motors shall be Polyphase. Full Load and Locked Rotor Amps. as well as Start and Run winding resistance shall be tabulated for each pump.

6.01 BEARINGS, SHAFT AND MECHANICAL SEAL An upper radial and lower thrust bearing shall be required. These shall be heavy duty single row ball

bearings which are permanently and continuously lubricated and cooled by the dielectric oil which fills the motor housing. The motor shaft shall be stainless steel and sealed from the pumped liquid with a carbon ceramic mechanical seal.

MODEL: HUP

HYDROMATIC®

HUP1/6 HP SUBMERSIBLE UTILITY PUMP

Wholesale Products Page: 6660-5Dated: January 2001

Page 36: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

USA CANADA293 WrigHt Street, DelAvAN, Wi 53115 WWW.HYDrOMAtiC.COM 269 trilliUM Drive, KitCHeNer, ONtAriO, CANADA N2g 4W5PH: 888-957-8677 OrDerS FAX: 800-426-9446 PH: 519-896-2163 OrDerS FAX: 519-896-6337

Because we are continuously improving our products and services, Pentair reserves the right to change specifications without prior notice.

© 2013 Pentair ltd. All rights reserved. W-01-260 (03/25/13)

SPECIFICATION DATA

7.01 IMPELLER The Impeller shall be high capacity, two vane, non clog design with pump out vanes on the back side.

These vanes wash out grit and stringy material that will damage the shaft and mechanical seal.

8.01 AUTOMATIC CONTROL All single phase pumps should be capable of automatic operation.

9.01 PRESSURE SWITCH The single phase pumps are furnished with a pressure diaphragm switch that features a piggy-back plug

that allows the pump to be operated manually without removal from the sump.

10.01 FLOAT SWITCH The Single Phase pump is supplied with a tilt-sensitive wide-angle float switch is sealed in a non-

corrosive PVC enclosure. The unit is UL listed for water and sewage and CSA certified. The float switch shall also be fitted with a piggy-back plug that allows the pump to be operated manually without removal from the sump.

11.01 MANUAL CONTROL The Single Phase pumps are not supplied with any type of automatic control. A super or double wide angle

piggy-back float switch can be supplied and fitted to these pumps.

12.01 PAINTING All cast iron parts shall be painted before assembly with a water reducible alkyd air dried enamel.

The paint shall be applied in one coat with a minimum thickness of 3 to 4 mils.

13.01 TESTING All pumps shall be individually tested to include the following:

1. The pump and power cord shall be visually inspected for imperfections, cuts or nicks. 2. The pump shall have a ground continuity check and the motor chamber shall be Hi-potted

to test for moisture content and/or insulation defects. 3. The motor and volute housing shall be pressurized and a 10 second air leak decay test run. 4. Oil is added, and the pump is run. Voltage and current are monitored visually, electronically,

and the tester listens for any noise or malfunction.

HYDROMATIC®

HUP1/6 HP SUBMERSIBLE UTILITY PUMP

Wholesale Products Page: 6660-6Dated: January 2001

Page 37: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

40

0

10

20

30

TOTA

L DY

NAM

IC H

EAD-

FEET

50

60

0 32 64 96 128 160 192CAPACITY-U.S. G.P.M.

70

80

1/2 HP

1 HP

1-1/2 HP

2 HP

Conditions of Service:

GPM:______ TDH:______

The curves reflect maximum performance characteristics without exceeding full load (Nameplate) horsepower. All pumps have a service factor of 1.2. Operation is recommended in the bounded area with operational point within the curve limit. Performance curves are based on actual tests with clear water at 70° F. and 1280 feet site elevation.

PERFORMANCE DATA

Wholesale Products Page: 6560-1Dated: January 2001

RPM: 3450 Discharge: 2” Solids: 2”

HYDROMATIC®

SKHS SERIESSUBMERSIBLE NON-CLOG, SEWAGE EJECTOR

Page 38: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

All dimensions in inches. Metric for international use. Component dimensions may vary ± 1/8 inch. Dimensional data not for construction purpose unless certified. Dimensions and weights are approximate. On/Off level adjustable. We reserve the right to make revisions to our product (s) and the product (s) specifications without notice.

DIMENSIONAL DATA

Wholesale Products Page: 6560-2Dated: January 2001

HYDROMATIC®

SKHS SERIESSUBMERSIBLE NON-CLOG, SEWAGE EJECTOR

4-3/4"(120)

3-3/4"(95)

4-9/32"(180)

8-3/4"(222)

5-7/8"(149)

6-1/4"(158)

19"(482)

16-1/4"(412)

Page 39: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

ELECTRICAL DATA

MODEL: SKHS50/100/150/200R.P.M. 3450MOTOR TYPE OIL FILLED, THERMAL OVERLOAD WITH AUTOMATIC RESET

MOTOR PROTECTION THERMAL OVERLOAD WITH AUTOMATIC RESET

PUMP MODEL HP VOLTAGE PHASE FULL LOAD AMPSSKHS50M1

1/2

1151

14.2SKHS50M7 208 9.2SKHS50M2 230 8.3SKHS50M6 208

3

6.6SKHS50M3 230 6.0SKHS50M4 460 3.0SKHS50M5 575 2.4

SKHS100M7

1

2081

12.6SKHS100M2 230 11.4SKHS100M6 208

3

8.8SKHS100M3 230 8.0SKHS100M4 460 4.0SKHS100M5 575 3.2SKHS150M7

1 1/2

2081

15.3SKHS150M2 230 13.9SKHS150M6 208

3

8.5SKHS150M3 230 7.6SKHS150M4 460 3.9SKHS150M5 575 3.1SKHS200M2

2

230 1 18.0SKHS200M6 208

3

10.4SKHS200M3 230 9.2SKHS200M4 460 4.6SKHS200M5 575 3.7

ALL CURVES CUT OFF AT 140 G.P.M.

Wholesale Products Page: 6560-3Dated: July 2005

HYDROMATIC®

SKHS SERIESSUBMERSIBLE NON-CLOG, SEWAGE EJECTOR

Page 40: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

TECHNICAL DATA

MODEL: SKHS50/100/150/200Physical DataDISCHARGE SIZE 2” NPT (STANDARD), 3” NPT (OPTIONAL)SOLIDS SIZE 2”IMPELLER TYPE 2 VANECABLE LENGTH 20’ STANDARDPAINT PAINTED AFTER ASSEMBLY, DARK GREEN, WATER REDUCIBLE ENAMEL,

ONE COAT, AIR DRIED.

TemperatureMAXIMUM LIQUID 140°FMAXIMUM STATOR -OIL FLASH POINT -

Technical DataPOWER CORD TYPE STW-A

MAT

ERIA

LS O

F CO

NST

RUCT

ION MOTOR HOUSING CAST IRON

CASING CAST IRONIMPELLER CAST IRONMOTOR SHAFT 416 STAINLESS STEELHARDWARE STAINLESS STEEL“O” RINGS BUNA-N

MECHANICAL SEALSStandard: CARBON / CERAMIC

UPPER BEARING SINGLE ROW-BALLLOWER BEARING SINGLE ROW-BALL

Wholesale Products Page: 6560-4Dated: January 2001

HYDROMATIC®

SKHS SERIESSUBMERSIBLE NON-CLOG, SEWAGE EJECTOR

Page 41: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

SPECIFICATION DATA

1.01 GENERAL Contractor shall furnish all labor, materials, equipment and incidentals required to provide __________

(Qty.) submersible centrifugal non clog sewage pump(s) as specified herein. The pump models covered in this specification are the SKHS50, SKHS100, SKHS150 and SKHS200. The pump furnished for this application shall be MODEL ____________ as manufactured by Hydromatic Pumps.

2.01 DESIGN CONDITIONS Each pump shall be rated ________ H.P., ________ volts, ________ phase, ________ hertz and operate

at ________ RPM.

3.01 OPERATING CONDITIONS The pump shall deliver ________ U.S. GPM/LPS at feet/meters TDH, and handle a ________ inch solid.

The curve submitted for approval shall state, in addition to head and capacity performance, solid handling capability, amp rating, and design impeller diameter.

4.01 CONSTRUCTION Each pump shall be of the sealed submersible type, incorporating features normally found in pumps

furnished for the heavy duty industrial or municipal markets. These features include:

1. The pump, motor, and seal housing shall be high quality gray cast iron, ASTM A-48, Class 30. 2. The pump inlet shall be open and clear, without screening to provide access for sewage

and solids. 3. All external mating parts shall be machined and Buna N, O-Ring sealed. 4. All fasteners exposed to the pumped liquid shall be 300 series stainless steel. 5. All power cords shall be water resistant UL or CSA approved, with double insulation, and sized

as a function of Amp. draw.

5.01 MOTOR AND SHAFT The stator, rotor and bearings shall be mounted in a sealed submersible type housing. Single phase

motors shall be split phase or capacitor start with centrifugal switch. Three phase motors shall be Polyphase. Full Load and Locked Rotor Amps. as well as Start and Run winding resistance shall be tabulated for each pump.

6.01 BEARINGS, SHAFT AND MECHANICAL SEAL An upper radial and lower thrust bearing shall be required. These shall be heavy duty single row ball

bearings which are permanently and continuously lubricated and cooled by the dielectric oil which fills the motor housing. The motor shaft shall be stainless steel and sealed from the pumped liquid with a carbon ceramic mechanical seal.

MODELS: SKHS50, SKHS100, SKHS150 and SKHS200

Wholesale Products Page: 6560-5Dated: January 2001

HYDROMATIC®

SKHS SERIESSUBMERSIBLE NON-CLOG, SEWAGE EJECTOR

Page 42: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

USA CANADA293 WRIgHt StREEt, DElAvAN, WI 53115 WWW.HYDROMAtIC.COM 269 tRIllIUM DRIvE, KItCHENER, ONtARIO, CANADA N2g 4W5PH: 888-957-8677 ORDERS FAX: 800-426-9446 PH: 519-896-2163 ORDERS FAX: 519-896-6337

Because we are continuously improving our products and services, Pentair reserves the right to change specifications without prior notice.

© 2013 Pentair ltd. All Rights Reserved. W-01-260 (03/25/13)

SPECIFICATION DATA

7.01 IMPELLER The Impeller shall be high capacity, two vane, non clog design with pump out vanes on the back side.

These vanes wash out grit and stringy material that will damage the shaft and mechanical seal.

8.01 AUTOMATIC CONTROL All single phase pumps should be capable of automatic operation.

9.01 FLOAT SWITCH The SKHS 1Ø pumps is offered with a tilt-sensitive wide-angle float switch is sealed in a non-corrosive

PVC enclosure. The unit is UL listed for water and sewage and CSA certified. The float switch shall also be fitted with a piggy-back plug that allows the pump to be operated manually without removal from the sump.

10.01 PAINTING All cast iron parts shall be painted before assembly with a water reducible alkyd air dried enamel.

The paint shall be applied in one coat with a minimum thickness of 3 to 4 mils.

12.01 TESTING All pumps shall be individually tested to include the following:

1. The pump and power cord shall be visually inspected for imperfections, cuts or nicks. 2. The pump shall have a ground continuity check and the motor chamber shall be Hi-potted

to test for moisture content and/or insulation defects. 3. The motor and volute housing shall be pressurized and a 10 second air leak decay test run. 4. Oil is added, and the pump is run. Voltage and current are monitored visually, electronically,

and the tester listens for any noise or malfunction.

Wholesale Products Page: 6560-6Dated: January 2001

HYDROMATIC®

SKHS SERIESSUBMERSIBLE NON-CLOG, SEWAGE EJECTOR

Page 43: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

SK100

SK75

0

10

20

30

40

20 40 60 80 100 120 140 160

TOTA

L H

EAD

IN F

EET

Capacity-U.S. G.P.M.

Liters/Second 0 2 8 1064

HEA

D-M

ETER

S

0

3

6

9

12

0

Conditions of Service:

GPM:______ TDH:______

The curves reflect maximum performance characteristics without exceeding full load (Nameplate) horsepower. All pumps have a service factor of 1.2. Operation is recommended in the bounded area with operational point within the curve limit. Performance curves are based on actual tests with clear water at 70° F. and 1280 feet site elevation.

HYDROMATIC®

SK75/100SUBMERSIBLE SEWAGE EJECTOR

PERFORMANCE DATA

Wholesale Products Page: 6300-1Dated: January 2001

RPM: 1750 Discharge: 2” Solids: 2”

Page 44: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

DIMENSIONAL DATA

8-1/16"(204)

4-5/16"(109) 5-7/8"

(149)

4-3/4"(120)

3-13/16"(96)

22-1/4"(565)

6-1/2"(165)

21-1/16"(534)

All dimensions in inches. Metric for international use. Component dimensions may vary ± 1/8 inch. Dimensional data not for construction purpose unless certified. Dimensions and weights are approximate. On/Off level adjustable. We reserve the right to make revisions to our product (s) and the product (s) specifications without notice.

HYDROMATIC®

SK75/100SUBMERSIBLE SEWAGE EJECTOR

Wholesale Products Page: 6300-2Dated: January 2001

Page 45: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

ELECTRICAL DATA

MODEL: SK75R.P.M. 1750MOTOR TYPE OIL FILLED WITH AUTOMATIC RESET THERMAL OVERLOADMOTOR PROTECTION AUTOMATIC RESET / THERMAL OVERLOAD

HP VOLTAGE PHASE NEC CODE SERVICE FACTOR FULL LOAD AMPS

3/4

2001

- 1

10.4230 9.0200

3

4.0230 3.5460 1.8575 1.44

HYDROMATIC®

SK75SUBMERSIBLE SEWAGE EJECTOR

Wholesale Products Page: 6300-3Dated: January 2001

Page 46: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

ELECTRICAL DATA

MODEL: SK100

HYDROMATIC®

SK100SUBMERSIBLE SEWAGE EJECTOR

Wholesale Products Page: 6300-4Dated: January 2001

R.P.M. 1750MOTOR TYPE OIL FILLED WITH AUTOMATIC RESET THERMAL OVERLOADMOTOR PROTECTION AUTOMATIC RESET / THERMAL OVERLOAD

HP VOLTAGE PHASE NEC CODE SERVICE FACTOR FULL LOAD AMPS

1

2001

- 1

11.5230 10.0200

3

5.0230 4.4460 2.2575 1.7

Page 47: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

TECHNICAL DATA

MODEL: SK75Physical DataDISCHARGE SIZE 2” NPT (STANDARD), 3” NPT (OPTIONAL)SOLIDS SIZE 2”IMPELLER TYPE 2 VANE NON CLOGCABLE LENGTH 20’ STANDARDPAINT PAINTED AFTER ASSEMBLY, DARK GREEN, WATER REDUCIBLE ENAMEL,

ONE COAT, AIR DRIED.

TemperatureMAXIMUM LIQUID 140°FMAXIMUM STATOR -OIL FLASH POINT -

Technical DataPOWER CORD TYPE STW-A

MAT

ERIA

LS O

F CO

NST

RUCT

ION MOTOR HOUSING CAST IRON

CASING CAST IRONIMPELLER CAST IRONMOTOR SHAFT 416 STAINLESS STEELHARDWARE STAINLESS STEEL“O” RINGS BUNA - N

MECHANICAL SEALSStandard: CARBON / CERAMIC

UPPER BEARING SINGLE ROW-BALLLOWER BEARING SINGLE ROW-BALL

HYDROMATIC®

SK75SUBMERSIBLE SEWAGE EJECTOR

Wholesale Products Page: 6300-5Dated: January 2001

Page 48: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

TECHNICAL DATA

MODEL: SK100

HYDROMATIC®

SK100SUBMERSIBLE SEWAGE EJECTOR

Wholesale Products Page: 6300-6Dated: January 2001

Physical DataDISCHARGE SIZE 2” NPT (STANDARD), 3” NPT (OPTIONAL)SOLIDS SIZE 2”IMPELLER TYPE 2 VANE NON CLOGCABLE LENGTH 20’ STANDARDPAINT PAINTED AFTER ASSEMBLY, DARK GREEN, WATER REDUCIBLE ENAMEL,

ONE COAT, AIR DRIED.

TemperatureMAXIMUM LIQUID 140°FMAXIMUM STATOR -OIL FLASH POINT -

Technical DataPOWER CORD TYPE STW-A

MAT

ERIA

LS O

F CO

NST

RUCT

ION MOTOR HOUSING CAST IRON

CASING CAST IRONIMPELLER CAST IRONMOTOR SHAFT 416 STAINLESS STEELHARDWARE STAINLESS STEEL“O” RINGS BUNA-N

MECHANICAL SEALSStandard: CARBON / CERAMIC

UPPER BEARING SINGLE ROW-BALLLOWER BEARING SINGLE ROW-BALL

Page 49: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

SPECIFICATION DATA

1.01 GENERAL Contractor shall furnish all labor, materials, equipment and incidentals required to provide __________

(Qty.) submersible centrifugal sewage ejector pump(s) as specified herein. The pump models covered in this specification are the SK75 and SK100. The pump furnished for this application shall be MODEL ____________ as manufactured by Hydromatic Pumps.

2.01 DESIGN CONDITIONS Each pump shall be rated ________ H.P., ________ volts, ________ phase, ________ hertz and operate

at ________ RPM.

3.01 OPERATING CONDITIONS The pump shall deliver ________ U.S. GPM/LPS at feet/meters TDH, and handle a ________ inch solid.

The curve submitted for approval shall state, in addition to head and capacity performance, solid handling capability, amp rating, and design impeller diameter.

4.01 CONSTRUCTION Each pump shall be of the sealed submersible type, incorporating features normally found in pumps

furnished for the residential market. These features include:

1. The pump volute, motor, and seal housing shall be high quality gray cast iron, ASTM A-48, Class 30.

2. The pump inlet shall be open and clear, without screening to provide access for sewage and solids.

3. All external mating parts shall be machined and Buna N, O-Ring sealed. 4. All fasteners exposed to the pumped liquid shall be 300 series stainless steel. 5. All power cords shall be water resistant UL or CSA approved, with double insulation, and sized

as a function of Amp. draw.

5.01 MOTOR AND SHAFT The stator, rotor and bearings shall be mounted in a sealed submersible type housing. Single phase

motors shall be split phase or capacitor start with centrifugal switch. Three phase motors shall be Polyphase. Full Load and Locked Rotor Amps as well as Start and Run winding resistance shall be tabulated for each pump.

6.01 BEARINGS, SHAFT AND MECHANICAL SEAL An upper bushing bearing and lower thrust bearing shall be required. The upper bearing shall be brass

while the lower bearing is a single row ball. They are both permanently and continuously lubricated and cooled by the dielectric oil which fills the motor housing. The motor shaft shall be stainless steel and sealed from the pumped liquid with a carbon ceramic mechanical seal.

MODELS: SK75 and SK100

HYDROMATIC®

SK75/100SUBMERSIBLE SEWAGE EJECTOR

Wholesale Products Page: 6300-7Dated: January 2001

Page 50: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

USA CANADA293 Wright Street, DelAvAN, Wi 53115 WWW.hYDrOMAtiC.COM 269 trilliUM Drive, KitCheNer, ONtAriO, CANADA N2g 4W5Ph: 888-957-8677 OrDerS FAX: 800-426-9446 Ph: 519-896-2163 OrDerS FAX: 519-896-6337

Because we are continuously improving our products and services, Pentair reserves the right to change specifications without prior notice.

© 2013 Pentair ltd. All rights reserved. W-01-260 (03/25/13)

SPECIFICATION DATA

7.01 IMPELLER The Impeller shall be high capacity, two vane, non-clog design with pump out vanes on the back side.

These vanes wash out grit and stringy material that will damage the shaft and mechanical seal.

8.01 AUTOMATIC CONTROL All single phase pumps should be capable of automatic operation.

9.01 MANUAL CONTROL The Single Phase SK75 and SK100 pumps are not supplied with any type of automatic control. A super or

double wide angle piggy-back float switch can be supplied and fitted to these pumps.

10.01 PAINTING All cast iron parts shall be painted before assembly with a water reducible alkyd air dried enamel.

The paint shall be applied in one coat with a minimum thickness of 3 to 4 mils.

11.01 TESTING All pumps shall be individually tested to include the following:

1. The pump and power cord shall be visually inspected for imperfections, cuts or nicks. 2. The pump shall have a ground continuity check and the motor chamber shall be Hi-potted

to test for moisture content and/or insulation defects. 3. The motor and volute housing shall be pressurized and a 10 second air leak decay test run. 4. Oil is added, and the pump is run. Voltage and current are monitored visually, electronically,

and the tester listens for any noise or malfunction.

HYDROMATIC®

SK75/100SUBMERSIBLE SEWAGE EJECTOR

Wholesale Products Page: 6300-8Dated: January 2001

Page 51: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

SK50 SK60

0

10

20

30

40

20 40 60 80 100 120

TOTA

L H

EAD

IN F

EET

Capacity-U.S. G.P.M.

Liters/Second 0 2 864

HEA

D-M

ETER

S

0

3

6

9

12

0

Conditions of Service:

GPM:______ TDH:______

The curves reflect maximum performance characteristics without exceeding full load (Nameplate) horsepower. All pumps have a service factor of 1.2. Operation is recommended in the bounded area with operational point within the curve limit. Performance curves are based on actual tests with clear water at 70° F. and 1280 feet site elevation.

HYDROMATIC®

SK60SUBMERSIBLE SEWAGE EJECTOR

PERFORMANCE DATA

Wholesale Products Page: 6290-1Dated: January 2001

RPM: 1750 Discharge: 2” Solids: 2”

Page 52: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

DIMENSIONAL DATA

2" NPTDISCHARGE

4-3/4"(121)

3-13/16"(97)

4-5/16"(110) 8-1/16" (206)

5-7/8"(149)

16"(406)

5-1/16"(129)

PUMPOFF

6-1/2"(165)

13-5/16"(338)

PUMPON

17-1/4"(438)

DISCHARGEHEIGHT

6-3/16"(157)

HYDROMATIC®

SK60SUBMERSIBLE SEWAGE EJECTOR

Wholesale Products Page: 6290-2Dated: January 2001

All dimensions in inches. Metric for international use. Component dimensions may vary ± 1/8 inch. Dimensional data not for construction purpose unless certified. Dimensions and weights are approximate. On/Off level adjustable. We reserve the right to make revisions to our product (s) and the product (s) specifications without notice.

Page 53: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

ELECTRICAL DATA

MODEL: SK50R.P.M. 1750MOTOR TYPE OIL FILLED WITH AUTOMATIC RESET THERMAL OVERLOADMOTOR PROTECTION AUTOMATIC RESET / THERMAL OVERLOAD

HP VOLTAGE PHASE NEC CODE SERVICE FACTOR FULL LOAD AMPS

6/10

1151

- 1

12200 6.9230 6.0200

3

2.9230 2.5460 1.3575 1.04

HYDROMATIC®

SK60SUBMERSIBLE SEWAGE EJECTOR

Wholesale Products Page: 6290-3Dated: January 2001

Page 54: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

TECHNICAL DATA

MODEL: SK50Physical DataDISCHARGE SIZE 2” NPT (STANDARD), 3” NPT (OPTIONAL)SOLIDS SIZE 2”IMPELLER TYPE NON CLOGCABLE LENGTH 10’ STANDARD

20’ OPTIONALPAINT PAINTED AFTER ASSEMBLY, DARK GREEN, WATER REDUCIBLE ENAMEL,

ONE COAT, AIR DRIED.

TemperatureMAXIMUM LIQUID 140°FMAXIMUM STATOR -OIL FLASH POINT -

Technical DataPOWER CORD TYPE STW-A

MAT

ERIA

LS O

F CO

NST

RUCT

ION MOTOR HOUSING CAST IRON

CASING CAST IRONIMPELLER CAST IRONMOTOR SHAFT 416 STAINLESS STEELHARDWARE STAINLESS STEEL“O” RINGS BUNA-N

MECHANICAL SEALSStandard: CARBON / CERAMIC

UPPER BEARING SINGLE ROW-BALLLOWER BEARING SINGLE ROW-BALL

HYDROMATIC®

SK60SUBMERSIBLE SEWAGE EJECTOR

Wholesale Products Page: 6290-4Dated: January 2001

Page 55: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

SPECIFICATION DATA

1.01 GENERAL Contractor shall furnish all labor, materials, equipment and incidentals required to provide __________

(Qty.) submersible centrifugal sewage ejector pump(s) as specified herein. The pump model covered in this specification is the SK60. The pump furnished for this application shall be MODEL ____________ as manufactured by Hydromatic Pumps.

2.01 DESIGN CONDITIONS Each pump shall be rated ________ H.P., ________ volts, ________ phase, ________ hertz and operate

at ________ RPM.

3.01 OPERATING CONDITIONS The pump shall deliver ________ U.S. GPM/LPS at feet/meters TDH, and handle a ________ inch solid.

The curve submitted for approval shall state, in addition to head and capacity performance, solid handling capability, amp rating, and design impeller diameter.

4.01 CONSTRUCTION Each pump shall be of the sealed submersible type, incorporating features normally found in pumps

furnished for the residential market. These features include:

1. The pump volute, motor, and seal housing shall be high quality gray cast iron, ASTM A-48, Class 30.

2. The pump inlet shall be open and clear, without screening to provide access for sewage and solids.

3. All external mating parts shall be machined and Buna N, O-Ring sealed. 4. All fasteners exposed to the pumped liquid shall be 300 series stainless steel. 5. All power cords shall be water resistant UL or CSA approved, with double insulation, and sized

as a function of Amp. draw.

5.01 MOTOR AND SHAFT The stator, rotor and bearings shall be mounted in a sealed submersible type housing. Single phase

motors shall be split phase or capacitor start with centrifugal switch. Three phase motors shall be Polyphase. Full Load and Locked Rotor Amps as well as Start and Run winding resistance shall be tabulated for each pump.

6.01 BEARINGS, SHAFT AND MECHANICAL SEAL An upper bushing bearing and lower thrust bearing shall be required. The upper bearing shall be brass

while the lower bearing is a heavy duty single row ball. They are both permanently and continuously lubricated and cooled by the dielectric oil which fills the motor housing. The motor shaft shall be stainless steel and sealed from the pumped liquid with a carbon ceramic mechanical seal.

MODEL: SK50

HYDROMATIC®

SK60SUBMERSIBLE SEWAGE EJECTOR

Wholesale Products Page: 6290-5Dated: January 2001

Page 56: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

USA CANADA293 Wright Street, DelAvAN, Wi 53115 WWW.hYDrOMAtiC.COM 269 trilliUM Drive, KitCheNer, ONtAriO, CANADA N2g 4W5Ph: 888-957-8677 OrDerS FAX: 800-426-9446 Ph: 519-896-2163 OrDerS FAX: 519-896-6337

Because we are continuously improving our products and services, Pentair reserves the right to change specifications without prior notice.

© 2013 Pentair ltd. All rights reserved. W-01-260 (03/25/13)

SPECIFICATION DATA

7.01 IMPELLER The Impeller shall be high capacity, two vane, non-clog design with pump out vanes on the back side.

These vanes wash out grit and stringy material that will damage the shaft and mechanical seal.

8.01 AUTOMATIC CONTROL All single phase pumps should be capable of automatic operation.

9.01 PRESSURE SWITCH The Single Phase SK60 pump is furnished with a pressure diaphragm switch that features a piggy-back

plug that allows the pump to be operated manually without removal from the sump.

10.01 PAINTING All cast iron parts shall be painted before assembly with a water reducible alkyd air dried enamel.

The paint shall be applied in one coat with a minimum thickness of 3 to 4 mils.

11.01 TESTING All pumps shall be individually tested to include the following:

1. The pump and power cord shall be visually inspected for imperfections, cuts or nicks. 2. The pump shall have a ground continuity check and the motor chamber shall be Hi-potted

to test for moisture content and/or insulation defects. 3. The motor and volute housing shall be pressurized and a 10 second air leak decay test run. 4. Oil is added, and the pump is run. Voltage and current are monitored visually, electronically,

and the tester listens for any noise or malfunction.

HYDROMATIC®

SK60SUBMERSIBLE SEWAGE EJECTOR

Wholesale Products Page: 6290-6Dated: January 2001

Page 57: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

SK50 SK60

0

10

20

30

40

20 40 60 80 100 120

TOTA

L H

EAD

IN F

EET

Capacity-U.S. G.P.M.

Liters/Second 0 2 864

HEA

D-M

ETER

S

0

3

6

9

12

0

Conditions of Service:

GPM:______ TDH:______

The curves reflect maximum performance characteristics without exceeding full load (Nameplate) horsepower. All pumps have a service factor of 1.2. Operation is recommended in the bounded area with operational point within the curve limit. Performance curves are based on actual tests with clear water at 70° F. and 1280 feet site elevation.

HYDROMATIC®

SK50SUBMERSIBLE SEWAGE EJECTOR

PERFORMANCE DATA

Wholesale Products Page: 6270-1Dated: January 2001

RPM: 1750 Discharge: 2” Solids: 2”

Page 58: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

DIMENSIONAL DATA

All dimensions in inches. Metric for international use. Component dimensions may vary ± 1/8 inch. Dimensional data not for construction purpose unless certified. Dimensions and weights are approximate. On/Off level adjustable. We reserve the right to make revisions to our product (s) and the product (s) specifications without notice.

4-5/16"(109)

8-1/16"(128)5-7/8"

(149)

4-3/4"(120)

3-13/16"(96)

2" NPTDISCHARGE

11-1/2"(292)

PUMP ON

12-5/16"(312)

6-9/16"(166)

5-1/2"(139)

PUMP OFF

11-7/16"(290)

DISCHARGEHEIGHT

HYDROMATIC®

SK50SUBMERSIBLE SEWAGE EJECTOR

Wholesale Products Page: 6270-2Dated: January 2001

Page 59: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

ELECTRICAL DATA

MODEL: SK50R.P.M. 1750MOTOR TYPE OIL FILLED WITH AUTOMATIC RESET THERMAL OVERLOADGENERAL INSULATION CLASS AMOTOR PROTECTION AUTOMATIC RESET / THERMAL OVERLOAD

HP VOLTAGE PHASE NEC CODE SERVICE FACTOR FULL LOAD AMPS

1/2115

1 - 112

230 6

HYDROMATIC®

SK50SUBMERSIBLE SEWAGE EJECTOR

Wholesale Products Page: 6270-3Dated: January 2001

Page 60: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

TECHNICAL DATA

MODEL: SK50Physical DataDISCHARGE SIZE 2” NPT (STANDARD), 3” NPT (OPTIONAL)SOLIDS SIZE 2”IMPELLER TYPE NON CLOGCABLE LENGTH 10’ STANDARD

20’ OPTIONALPAINT PAINTED AFTER ASSEMBLY, DARK GREEN, WATER REDUCIBLE ENAMEL,

ONE COAT, AIR DRIED.

TemperatureMAXIMUM LIQUID 140°FMAXIMUM STATOR -OIL FLASH POINT -

Technical DataPOWER CORD TYPE SJTW

MAT

ERIA

LS O

F CO

NST

RUCT

ION MOTOR HOUSING CAST IRON

CASING CAST IRONIMPELLER CAST IRONMOTOR SHAFT STEELHARDWARE STAINLESS STEEL“O” RINGS BUNA-N

MECHANICAL SEALSStandard: CARBON / CERAMIC

UPPER BEARING SINGLE ROW-BALLLOWER BEARING SINGLE ROW-BALL

HYDROMATIC®

SK50SUBMERSIBLE SEWAGE EJECTOR

Wholesale Products Page: 6270-4Dated: January 2001

Page 61: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

SPECIFICATION DATA

1.01 GENERAL Contractor shall furnish all labor, materials, equipment and incidentals required to provide __________

(Qty.) submersible centrifugal sewage ejector pump(s) as specified herein. The pump model covered in this specification is the SK50. The pump furnished for this application shall be MODEL ____________ as manufactured by Hydromatic Pumps.

2.01 DESIGN CONDITIONS Each pump shall be rated ________ H.P., ________ volts, ________ phase, ________ hertz and operate

at ________ RPM.

3.01 OPERATING CONDITIONS The pump shall deliver ________ U.S. GPM/LPS at feet/meters TDH, and handle a ________ inch solid.

The curve submitted for approval shall state, in addition to head and capacity performance, solid handling capability, amp rating, and design impeller diameter.

4.01 CONSTRUCTION Each pump shall be of the sealed submersible type, incorporating features normally found in pumps

furnished for the residential market. These features include:

1. The pump volute, motor, and seal housing shall be high quality gray cast iron, ASTM A-48, Class 30.

2. The pump inlet shall be open and clear, without screening to provide access for sewage and solids.

3. All external mating parts shall be machined and Buna N, O-Ring sealed. 4. All fasteners exposed to the pumped liquid shall be 300 series stainless steel. 5. All power cords shall be water resistant UL or CSA approved, with double insulation, and sized

as a function of Amp. draw.

5.01 MOTOR AND SHAFT The stator, rotor and bearings shall be mounted in a sealed submersible type housing. Single phase

motors shall be split phase or capacitor start with centrifugal switch. Three phase motors shall be Polyphase. Full Load and Locked Rotor Amps as well as Start and Run winding resistance shall be tabulated for each pump.

6.01 BEARINGS, SHAFT AND MECHANICAL SEAL An upper bushing bearing and lower thrust bearing shall be required. The upper bearing shall be brass

while the lower bearing is a heavy duty single row ball. They are both permanently and continuously lubricated and cooled by the dielectric oil which fills the motor housing. The motor shaft shall be stainless steel and sealed from the pumped liquid with a carbon ceramic mechanical seal.

MODEL: SK50

HYDROMATIC®

SK50SUBMERSIBLE SEWAGE EJECTOR

Wholesale Products Page: 6270-5Dated: January 2001

Page 62: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

USA CANADA293 Wright Street, DelAvAN, Wi 53115 WWW.hYDrOMAtiC.COM 269 trilliUM Drive, KitCheNer, ONtAriO, CANADA N2g 4W5Ph: 888-957-8677 OrDerS FAX: 800-426-9446 Ph: 519-896-2163 OrDerS FAX: 519-896-6337

Because we are continuously improving our products and services, Pentair reserves the right to change specifications without prior notice.

© 2013 Pentair ltd. All rights reserved. W-01-260 (03/25/13)

SPECIFICATION DATA

7.01 IMPELLER The Impeller shall be high capacity, two vane, non-clog design with pump out vanes on the back side.

These vanes wash out grit and stringy material that will damage the shaft and mechanical seal.

8.01 AUTOMATIC CONTROL All single phase pumps should be capable of automatic operation.

9.01 FLOAT SWITCH The SK50 pump is supplied with a tilt-sensitive wide-angle float switch which is sealed in a non-corrosive

PVC enclosure. The unit is UL listed for water and sewage and CSA certified. The float switch shall also be fitted with a piggy-back plug that allows the pump to be operated manually without removal from the sump.

10.01 PAINTING All cast iron parts shall be painted before assembly with a water reducible alkyd air dried enamel.

The paint shall be applied in one coat with a minimum thickness of 3 to 4 mils.

11.01 TESTING All pumps shall be individually tested to include the following:

1. The pump and power cord shall be visually inspected for imperfections, cuts or nicks. 2. The pump shall have a ground continuity check and the motor chamber shall be Hi-potted

to test for moisture content and/or insulation defects. 3. The motor and volute housing shall be pressurized and a 10 second air leak decay test run. 4. Oil is added, and the pump is run. Voltage and current are monitored visually, electronically,

and the tester listens for any noise or malfunction.

HYDROMATIC®

SK50SUBMERSIBLE SEWAGE EJECTOR

Wholesale Products Page: 6270-6Dated: January 2001

Page 63: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

0Capacity - U.S. G.P.M.

Liters/Second

0 30 60 90 120 150 180

0 2 4 6 8 10

HEA

D-FE

ET

HEA

D-M

ETER

S

10

40

30

20

0

3

12

9

6 SKV50

Conditions of Service:

GPM:______ TDH:______

The curves reflect maximum performance characteristics without exceeding full load (Nameplate) horsepower. All pumps have a service factor of 1.2. Operation is recommended in the bounded area with operational point within the curve limit. Performance curves are based on actual tests with clear water at 70° F. and 1280 feet site elevation.

HYDROMATIC®

SKV50SEWAGE EJECTOR

PERFORMANCE DATA

Wholesale Products Page: 6280-1Dated: June 2011

RPM: 1650 Discharge: 2” Solids: 2”

Page 64: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

All dimensions in inches. Metric for international use. Component dimensions may vary ± 1/8 inch. Dimensional data not for construction purpose unless certified. Dimensions and weights are approximate. On/Off level adjustable. We reserve the right to make revisions to our product (s) and the product (s) specifications without notice.

DIMENSIONAL DATA

12 49/64"(324.5)

PUMPOff

6 5/16"(160.6)2 1/16"

(52.3)

PUMPON

14 1/2"(367.9)

DISCHARGEHEIGHT

2" NPTDISCHARGE

9"(228.4)

3 1/2"(88.9)

41/2"(114.6)

1125/64" (289.3)

5 7/16"(138)

17/32"(13.5)

Switch Diaphragm TetheredPump ON 12-1/4” (31.1cm) 14” (35.6cm)

Pump OFF 3-3/4” (9.5cm) 7-1/2” (19 cm)

HYDROMATIC®

SKV50SEWAGE EJECTOR

Wholesale Products Page: 6280-2Dated: June 2011

Page 65: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

ELECTRICAL DATA

MODEL: SKV40R.P.M. 1650MOTOR TYPE OIL FILLED WITH AUTOMATIC RESET THERMAL OVERLOADGENERAL INSULATION CLASS BMOTOR PROTECTION AUTOMATIC RESET / THERMAL OVERLOAD

HP VOLTAGE PHASE NEC CODE SERVICE FACTOR FULL LOAD AMPS

1/2115

1 - 112

230 6

HYDROMATIC®

SKV50SEWAGE EJECTOR

Wholesale Products Page: 6280-3Dated: June 2011

Page 66: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

TECHNICAL DATA

MODEL: SKV40Physical DataDISCHARGE SIZE 2”SOLIDS SIZE 2”IMPELLER TYPE RECESSED VORTEXCABLE LENGTH 10’ STANDARD

20’ OPTIONALPAINT PAINTED AFTER ASSEMBLY, DARK GREEN, WATER REDUCIBLE ENAMEL,

ONE COAT, AIR DRIED.

TemperatureMAXIMUM LIQUID 140°FMAXIMUM STATOR -OIL FLASH POINT -

Technical DataPOWER CORD TYPE SJTW

MAT

ERIA

LS O

F CO

NST

RUCT

ION MOTOR HOUSING CAST IRON

CASING CAST IRONIMPELLER THERMOPLASTICMOTOR SHAFT STAINLESS STEELHARDWARE STAINLESS STEEL“O” RINGS BUNA-N

MECHANICAL SEALSStandard: CARBON / CERAMIC

UPPER BEARING SLEEVELOWER BEARING SINGLE ROW-BALL

HYDROMATIC®

SKV50SEWAGE EJECTOR

Wholesale Products Page: 6280-4Dated: June 2011

Page 67: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

SPECIFICATION DATA

1.01 GENERAL Contractor shall furnish all labor, materials, equipment and incidentals required to provide __________

(Qty.) submersible centrifugal sewage ejector pump(s) as specified herein. The pump model covered in this specification is the SKV50. The pump furnished for this application shall be MODEL ____________ as manufactured by Hydromatic Pumps.

2.01 DESIGN CONDITIONS Each pump shall be rated ________ H.P., ________ volts, ________ phase, ________ hertz and operate

at ________ RPM.

3.01 OPERATING CONDITIONS The pump shall deliver ________ U.S. GPM/LPS at feet/meters TDH, and handle a ________ inch solid.

The curve submitted for approval shall state, in addition to head and capacity performance, solid handling capability, amp rating, and design impeller diameter.

4.01 CONSTRUCTION Each pump shall be of the sealed submersible type, incorporating features normally found in pumps

furnished for the residential market. These features include:

1. The pump inlet shall be open and clear, without screening to provide access for sewage and solids.

2. All external mating parts shall be machined and Buna N, O-Ring sealed. 3. All fasteners exposed to the pumped liquid shall be 300 series stainless steel. 4. All power cords shall be water resistant UL or CSA approved, with double insulation, and sized

as a function of Amp. draw.

5.01 MOTOR AND SHAFT The stator, rotor and bearings shall be mounted in a sealed submersible type housing. Single phase

motors shall be permanently split capacitor. Full Load and Locked Rotor Amps. as well as Start and Run winding resistance shall be tabulated for each pump.

6.01 BEARINGS, SHAFT AND MECHANICAL SEAL An upper sleeve and lower thrust bearing shall be required. The lower bearing shall be heavy duty single

row ball bearing which is permanently and continuously lubricated and cooled by the dielectric oil which fills the motor housing. The motor shaft shall be stainless steel and sealed from the pumped liquid with a carbon ceramic mechanical seal.

MODEL: SKV40

HYDROMATIC®

SKV50SEWAGE EJECTOR

Wholesale Products Page: 6280-5Dated: June 2011

Page 68: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

USA CANADA293 Wright Street, DelAVAN, Wi 53115 WWW.hYDrOMAtiC.COM 269 trilliUM DriVe, KitCheNer, ONtAriO, CANADA N2g 4W5Ph: 888-957-8677 OrDerS FAX: 800-426-9446 Ph: 519-896-2163 OrDerS FAX: 519-896-6337

Because we are continuously improving our products and services, Pentair reserves the right to change specifications without prior notice.

© 2013 Pentair ltd. All rights reserved. W-01-260 (03/25/13)

SPECIFICATION DATA

7.01 IMPELLER The Impeller shall be thermoplastic, ten vane, vortex design with pump out vanes on the back side.

These vanes wash out grit and stringy material that will damage the shaft and mechanical seal.

8.01 AUTOMATIC CONTROL All single phase pumps should be capable of automatic operation.

9.01 PRESSURE SWITCH The single phase pumps are furnished with a pressure diaphragm switch that features a piggy-back plug

that allows the pump to be operated manually without removal from the sump.

10.01 FLOAT SWITCH The SKV50 pump is supplied with a tilt-sensitive wide-angle float switch which is sealed in a non-

corrosive PVC enclosure. The unit is UL listed for water and sewage and CSA certified. The float switch shall also be fitted with a piggy-back plug that allows the pump to be operated manually without removal from the sump.

11.01 MANUAL CONTROL The Single Phase pumps are not supplied with any type of automatic control. A wide angle piggy-back

float switch can be supplied and fitted to these pumps.

12.01 PAINTING All cast iron parts shall be painted before assembly with a water reducible alkyd air dried enamel.

The paint shall be applied in one coat with a minimum thickness of 3 to 4 mils.

13.01 TESTING All pumps shall be individually tested to include the following:

1. The pump and power cord shall be visually inspected for imperfections, cuts or nicks. 2. The pump shall have a ground continuity check and the motor chamber shall be Hi-potted

to test for moisture content and/or insulation defects. 3. The motor and volute housing shall be pressurized and a 10 second air leak decay test run. 4. Oil is added, and the pump is run. Voltage and current are monitored visually, electronically,

and the tester listens for any noise or malfunction.

HYDROMATIC®

SKV50SEWAGE EJECTOR

Wholesale Products Page: 6280-6Dated: June 2011

Page 69: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

Capacity-U.S. G.P.M.

Liters/Second

0 20 40 60 80

0 1 2 5

HEAD

-FEE

T

HEAD

-MET

ERS

10

15

25

20

3

4

8

7

4/10 HP5

3 4

02

Conditions of Service:

GPM:______ TDH:______

The curves reflect maximum performance characteristics without exceeding full load (Nameplate) horsepower. All pumps have a service factor of 1.2. Operation is recommended in the bounded area with operational point within the curve limit. Performance curves are based on actual tests with clear water at 70° F. and 1280 feet site elevation.

HYDROMATIC®

SKV40SUBMERSIBLE SEWAGE EJECTOR

PERFORMANCE DATA

Wholesale Products Page: 6730-1Dated: January 2001

RPM: 1550 Discharge: 2” Solids: 2”

Page 70: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

All dimensions in inches. Metric for international use. Component dimensions may vary ± 1/8 inch. Dimensional data not for construction purpose unless certified. Dimensions and weights are approximate. On/Off level adjustable. We reserve the right to make revisions to our product (s) and the product (s) specifications without notice.

DIMENSIONAL DATA

12 3/8"(314)

12 15/16"(328)DISCHARGE

HEIGHT

5 7/16"(138)

3 3/16"(80)

3 7/16"(87)

4 3/4"(120)

3 15/16"(99)

12 3/8"(314)

1215/16"(328)DISCHARGE

HEIGHT

5 7/16"(138)

Diaphragm SwitchOn = 8-7/8"Off = 4-1/4"

Vertical SwitchOn = 8-15/16"Off = 4-7/16"

Wide Angle SwitchOn = 12-1/2"Off = 6-1/42"

HYDROMATIC®

SKV40SUBMERSIBLE SEWAGE EJECTOR

Wholesale Products Page: 6730-2Dated: January 2001

Page 71: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

ELECTRICAL DATA

MODEL: SKV40R.P.M. 1550MOTOR TYPE OIL FILLED, SPLIT PHASE WITH THERMAL OVERLOADMOTOR PROTECTION AUTOMATIC RESET / THERMAL OVERLOAD

HP VOLTAGE PHASE NEC CODE SERVICE FACTOR FULL LOAD AMPS

4/10115

1 - 112

230 6

HYDROMATIC®

SKV40SUBMERSIBLE SEWAGE EJECTOR

Wholesale Products Page: 6730-3Dated: January 2001

Page 72: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

TECHNICAL DATA

MODEL: SKV40Physical DataDISCHARGE SIZE 2” NPTSOLIDS SIZE 2”IMPELLER TYPE RECESSED VORTEXCABLE LENGTH 10’ STANDARD

20’ OPTIONALPAINT PAINTED AFTER ASSEMBLY, DARK GREEN, WATER REDUCIBLE ENAMEL,

ONE COAT, AIR DRIED.

TemperatureMAXIMUM LIQUID 140°FMAXIMUM STATOR -OIL FLASH POINT -

Technical DataPOWER CORD TYPE SJTW

MAT

ERIA

LS O

F CO

NST

RUCT

ION MOTOR HOUSING CAST IRON

CASING CAST IRONIMPELLER THERMOPLASTICMOTOR SHAFT STEELHARDWARE STAINLESS STEEL“O” RINGS BUNA-N

MECHANICAL SEALSStandard: CARBON / CERAMIC

UPPER BEARING N/ALOWER BEARING SINGLE ROW-BALL

HYDROMATIC®

SKV40SUBMERSIBLE SEWAGE EJECTOR

Wholesale Products Page: 6730-4Dated: January 2001

Page 73: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

SPECIFICATION DATA

1.01 GENERAL Contractor shall furnish all labor, materials, equipment and incidentals required to provide __________

(Qty.) submersible centrifugal sewage ejector pump(s) as specified herein. The pump model covered in this specification is the SKV40. The pump furnished for this application shall be MODEL ____________ as manufactured by Hydromatic Pumps.

2.01 DESIGN CONDITIONS Each pump shall be rated ________ H.P., ________ volts, ________ phase, ________ hertz and operate

at ________ RPM.

3.01 OPERATING CONDITIONS The pump shall deliver ________ U.S. GPM/LPS at feet/meters TDH, and handle a ________ inch solid.

The curve submitted for approval shall state, in addition to head and capacity performance, solid handling capability, amp rating, and design impeller diameter.

4.01 CONSTRUCTION Each pump shall be of the sealed submersible type, incorporating features normally found in pumps

furnished for the residential market. These features include:

1. The pump volute, motor, and seal housing shall be high quality gray cast iron, ASTM A-48, Class 30. The seal housing for the SKV is corrosion resistant high density thermoplastic.

2. The pump inlet shall be open and clear, without screening to provide access for sewage and solids.

3. All external mating parts shall be machined and Buna N, O-Ring sealed. 4. All fasteners exposed to the pumped liquid shall be 300 series stainless steel. 5. All power cords shall be water resistant UL or CSA approved, with double insulation, and sized

as a function of Amp. draw.

5.01 MOTOR AND SHAFT The stator, rotor and bearings shall be mounted in a sealed submersible type housing. Single phase

motors shall be split phase or capacitor start with centrifugal switch. Three phase motors shall be Polyphase. Full Load and Locked Rotor Amps as well as Start and Run winding resistance shall be tabulated for each pump.

6.01 BEARINGS, SHAFT AND MECHANICAL SEAL An upper bushing bearing and lower thrust bearing shall be required. The upper bearing shall be brass

while the lower bearing is a heavy duty single row ball. They are both permanently and continuously lubricated and cooled by the dielectric oil which fills the motor housing. The motor shaft shall be stainless steel and sealed from the pumped liquid with a carbon ceramic mechanical seal.

MODEL: SKV40

HYDROMATIC®

SKV40SUBMERSIBLE SEWAGE EJECTOR

Wholesale Products Page: 6730-5Dated: January 2001

Page 74: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

USA CANADA293 Wright Street, DelAVAN, Wi 53115 WWW.hYDrOMAtiC.COM 269 trilliUM DriVe, KitCheNer, ONtAriO, CANADA N2g 4W5Ph: 888-957-8677 OrDerS FAX: 800-426-9446 Ph: 519-896-2163 OrDerS FAX: 519-896-6337

Because we are continuously improving our products and services, Pentair reserves the right to change specifications without prior notice.

© 2013 Pentair ltd. All rights reserved. W-01-260 (03/25/13)

SPECIFICATION DATA

7.01 IMPELLER The Impeller shall be a thermoplastic, eight vane, vortex design with three pump out vanes on the back

side. These vanes wash out grit and stringy material that will damage the shaft and mechanical seal.

8.01 AUTOMATIC CONTROL All single phase pumps should be capable of automatic operation.

9.01 PRESSURE SWITCH The single phase pumps are furnished with a pressure diaphragm switch that features a piggy-back plug

that allows the pump to be operated manually without removal from the sump.

10.01 FLOAT SWITCH The SKV40 pump is supplied with a tilt-sensitive wide-angle float switch which is sealed in a non-

corrosive PVC enclosure. The unit is UL listed for water and sewage and CSA certified. The float switch shall also be fitted with a piggy-back plug that allows the pump to be operated manually without removal from the sump.

11.01 VERTICAL MECHANICAL SWITCH The V-A1 single phase pump is furnished with a magnetic mechanical switch which is sealed in a non-

corrosive PVC enclosure. The switch will be activated by a PVC float sliding up and down a non-corrosive rod. The mechanical switch cord shall also be fitted with a piggy-back plug that allows the pump to be operated manually without removal from the sump.

12.01 PAINTING All cast iron parts shall be painted before assembly with a water reducible alkyd air dried enamel.

The paint shall be applied in one coat with a minimum thickness of 3 to 4 mils.

13.01 TESTING All pumps shall be individually tested to include the following:

1. The pump and power cord shall be visually inspected for imperfections, cuts or nicks. 2. The pump shall have a ground continuity check and the motor chamber shall be Hi-potted

to test for moisture content and/or insulation defects. 3. The motor and volute housing shall be pressurized and a 10 second air leak decay test run. 4. Oil is added, and the pump is run. Voltage and current are monitored visually, electronically,

and the tester listens for any noise or malfunction.

HYDROMATIC®

SKV40SUBMERSIBLE SEWAGE EJECTOR

Wholesale Products Page: 6730-6Dated: January 2001

Page 75: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

Capacity-U.S. G.P.M.

Liters/Second

0 20 40 60 80

0 1 2 5

HEAD

-FEE

T

HEAD

-MET

ERS

10

15

25

20

3

4

8

7

4/10 HP5

3 4

02

Conditions of Service:

GPM:______ TDH:______

The curves reflect maximum performance characteristics without exceeding full load (Nameplate) horsepower. All pumps have a service factor of 1.2. Operation is recommended in the bounded area with operational point within the curve limit. Performance curves are based on actual tests with clear water at 70° F. and 1280 feet site elevation.

PERFORMANCE DATA

Wholesale Products Page: 7140-1Dated: August 2002

Supersedes: May 2002RPM: 1550 Discharge: 2” Solids: 2”

HYDROMATIC®

BV-40SUBMERSIBLE NON-CLOG, SEWAGE EJECTOR

Page 76: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

All dimensions in inches. Metric for international use. Component dimensions may vary ± 1/8 inch. Dimensional data not for construction purpose unless certified. Dimensions and weights are approximate. On/Off level adjustable. We reserve the right to make revisions to our product (s) and the product (s) specifications without notice.

DIMENSIONAL DATA

13"(330.2)

13 9/16"(344.49)

DISCHARGEHEIGHT

61/ 8"(155.57

Diaphragm SwitchOn = 8 7/8"Off = 41/4"

Vertical SwitchOn = 815 /16"Off = 4 7/16"

Wide Angle SwitchOn = 121/2"Off = 6 1/42"

13"(330.2)

13 9/16"(344.49)

DISCHARGEHEIGHT

61/8"(155.57

3 3/16"(80)

37/16"(87)

43/4"(120)

315/16"(99)

Wholesale Products Page: 7140-2Dated: August 2002

Supersedes: May 2002

HYDROMATIC®

BV-40SUBMERSIBLE NON-CLOG, SEWAGE EJECTOR

Page 77: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

ELECTRICAL DATA

MODEL: BV-40

Wholesale Products Page: 7140-3Dated: May 2002

R.P.M. 1550MOTOR TYPE OIL FILLED, SPLIT PHASE WITH THERMAL OVERLOADMOTOR PROTECTION AUTOMATIC RESET / THERMAL OVERLOAD

HP VOLTAGE PHASE NEC CODE SERVICE FACTOR FULL LOAD AMPS4/10 115 1 - 1 12.6

HYDROMATIC®

BV-40SUBMERSIBLE NON-CLOG, SEWAGE EJECTOR

Page 78: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

TECHNICAL DATA

MODEL: BV-40

Wholesale Products Page: 7140-4Dated: May 2002

Physical DataDISCHARGE SIZE 2” NPTSOLIDS SIZE 2”IMPELLER TYPE RECESSED VORTEXCABLE LENGTH 10’ STANDARD

20’ OPTIONALPAINT PAINTED AFTER ASSEMBLY, DARK GREEN, WATER REDUCIBLE ENAMEL,

ONE COAT, AIR DRIED.

TemperatureMAXIMUM LIQUID 120°FMAXIMUM STATOR -OIL FLASH POINT -

Technical DataPOWER CORD TYPE SJTW

MAT

ERIA

LS O

F CO

NST

RUCT

ION

VOLUTE THERMOPLASTICMOTOR HOUSING CAST IRON(BEARING/ SEAL HOUSING)

CAST IRON

IMPELLER THERMOPLASTICMOTOR SHAFT STEELHARDWARE STAINLESS STEEL“O” RINGS BUNA-N

MECHANICAL SEALSStandard: CARBON / CERAMIC

UPPER BEARING BRONZE SLEEVELOWER BEARING SINGLE ROW-BALL

HYDROMATIC®

BV-40SUBMERSIBLE NON-CLOG, SEWAGE EJECTOR

Page 79: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

SPECIFICATION DATA

1.01 GENERAL Contractor shall furnish all labor, materials, equipment and incidentals required to provide __________

(Qty.) submersible centrifugal non clog sewage pump(s) as specified herein. The pump model covered in this specification is the BV-40. The pump furnished for this application shall be MODEL ____________ as manufactured by Hydromatic Pumps.

2.01 DESIGN CONDITIONS Each pump shall be rated ________ H.P., ________ volts, ________ phase, ________ hertz and operate

at ________ RPM.

3.01 OPERATING CONDITIONS The pump shall deliver ________ U.S. GPM/LPS at feet/meters TDH, and handle a ________ inch solid.

The curve submitted for approval shall state, in addition to head and capacity performance, solid handling capability, amp rating, and design impeller diameter.

4.01 CONSTRUCTION Each pump shall be of the sealed submersible type, incorporating features normally found in pumps

furnished for the heavy duty industrial or municipal markets. These features include:

1. The pump, motor, and seal housing shall be high quality gray cast iron, ASTM A-48, Class 30. The pump volute for the BV-40 is corrosion resistant high density thermoplastic.

2. The pump inlet shall be open and clear, without screening to provide access for sewage and solids.

3. All external mating parts shall be machined and Buna N, O-Ring sealed. 4. All fasteners exposed to the pumped liquid shall be 300 series stainless steel. 5. All power cords shall be water resistant UL or CSA approved, with double insulation, and sized

as a function of Amp. draw.

5.01 MOTOR AND SHAFT The stator, rotor and bearings shall be mounted in a sealed submersible type housing. Single phase

motors shall be split phase or capacitor start with centrifugal switch. Full Load and Locked Rotor Amps as well as Start and Run winding resistance shall be tabulated for each pump.

6.01 BEARINGS, SHAFT AND MECHANICAL SEAL An upper radial and lower thrust bearing shall be required. The upper baring is a bronze sleeve type and

the lower baring shall be heavy duty single row ball bearings which are permanently and continuously lubricated and cooled by the dielectric oil which fills the motor housing. The motor shaft shall be stainless steel and sealed from the pumped liquid with a carbon ceramic mechanical seal.

MODEL: BV-40

Wholesale Products Page: 7140-5Dated: May 2002

HYDROMATIC®

BV-40SUBMERSIBLE NON-CLOG, SEWAGE EJECTOR

Page 80: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

USA CANADA293 Wright Street, DelAVAN, Wi 53115 WWW.hYDrOMAtiC.COM 269 trilliUM DriVe, KitCheNer, ONtAriO, CANADA N2g 4W5Ph: 888-957-8677 OrDerS FAX: 800-426-9446 Ph: 519-896-2163 OrDerS FAX: 519-896-6337

Because we are continuously improving our products and services, Pentair reserves the right to change specifications without prior notice.

© 2013 Pentair ltd. All rights reserved. W-01-260 (03/25/13)

SPECIFICATION DATA

7.01 IMPELLER The Impeller shall be high capacity, eight vane, non clog design with pump out vanes on the back side.

These vanes wash out grit and stringy material that will damage the shaft and mechanical seal.

8.01 AUTOMATIC CONTROL All single phase pumps should be capable of automatic operation.

9.01 PRESSURE SWITCH The BV-40 pump is furnished with a pressure diaphragm switch that features a piggy-back plug that

allows the pump to be operated manually without removal from the sump.

10.01 FLOAT SWITCH The BV-40 pump is supplied with a tilt-sensitive wide-angle float switch is sealed in a non-corrosive PVC

enclosure. The unit is UL listed for water and sewage and CSA certified. The float switch shall also be fitted with a piggy-back plug that allows the pump to be operated manually without removal from the sump.

11.01 PAINTING All cast iron parts shall be painted before assembly with a water reducible alkyd air dried enamel.

The paint shall be applied in one coat with a minimum thickness of 3 to 4 mils.

12.01 TESTING All pumps shall be individually tested to include the following:

1. The pump and power cord shall be visually inspected for imperfections, cuts or nicks. 2. The pump shall have a ground continuity check and the motor chamber shall be Hi-potted

to test for moisture content and/or insulation defects. 3. The motor and volute housing shall be pressurized and a 10 second air leak decay test run. 4. Oil is added, and the pump is run. Voltage and current are monitored visually, electronically,

and the tester listens for any noise or malfunction.

Wholesale Products Page: 7140-6Dated: May 2002

HYDROMATIC®

BV-40SUBMERSIBLE NON-CLOG, SEWAGE EJECTOR

Page 81: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

TOTA

L H

EAD

IN F

EET

Capacity-U.S. G.P.M.

Liters/Second

HEA

D-M

ETER

S

9

6

3

0

30

20

10

00 20 40 60 80 100 120 1400 2 4 6 8

SP50 & SP50AB

SP40

Conditions of Service:

GPM:______ TDH:______

The curves reflect maximum performance characteristics without exceeding full load (Nameplate) horsepower. All pumps have a service factor of 1.2. Operation is recommended in the bounded area with operational point within the curve limit. Performance curves are based on actual tests with clear water at 70° F. and 1280 feet site elevation.

PERFORMANCE DATA

Wholesale Products Page: 6920-1Dated: January 2001

RPM: 1750 Discharge: 2” Solids: 1 ½”

HYDROMATIC®

SP50ABSUBMERSIBLE NON-CLOG, SEWAGE EJECTOR

Page 82: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

DIMENSIONAL DATA

Wholesale Products Page: 6920-2Dated: January 2001

All dimensions in inches. Metric for international use. Component dimensions may vary ± 1/8 inch. Dimensional data not for construction purpose unless certified. Dimensions and weights are approximate. On/Off level adjustable. We reserve the right to make revisions to our product (s) and the product (s) specifications without notice.

4-3/8"(111)

8-1/8"(206)5-7/8"

(149)

2" NPTDISCHARGE

7-5/16"(185)

4-5/8"(117)

4"(101)

18" (457) MINIMUM SUMP DIA.

12-7/16"(315)

14-1/4"(361)

PUMP ON

12-13/16"(325)

5-3/4"(146)

PUMP OFF

5-7/8"(149)

DISCHARGEHEIGHT

HYDROMATIC®

SP50ABSUBMERSIBLE NON-CLOG, SEWAGE EJECTOR

Page 83: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

ELECTRICAL DATA

Wholesale Products Page: 6920-3Dated: January 2001

MODEL: SP50ABR.P.M. 1750MOTOR TYPE OIL FILLED WITH AUTOMATIC RESET THERMAL OVERLOAD

GENERAL INSULATION CLASS AMOTOR PROTECTION AUTOMATIC RESET / THERMAL OVERLOAD

HP VOLTAGE PHASE NEC CODE SERVICE FACTOR FULL LOAD AMPS1/2 115 1 - 1 12

HYDROMATIC®

SP50ABSUBMERSIBLE NON-CLOG, SEWAGE EJECTOR

Page 84: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

TECHNICAL DATA

MODEL: SP50AB

Wholesale Products Page: 6920-4Dated: January 2001

Physical DataDISCHARGE SIZE 2” NPT (STANDARD), 3” NPT (OPTIONAL)SOLIDS SIZE 1 ½”IMPELLER TYPE NON CLOGCABLE LENGTH 10’ STANDARD

20’ OPTIONALPAINT PAINTED AFTER ASSEMBLY, DARK GREEN, WATER REDUCIBLE ENAMEL,

ONE COAT, AIR DRIED.

TemperatureMAXIMUM LIQUID 140°FMAXIMUM STATOR -OIL FLASH POINT -

Technical DataPOWER CORD TYPE STW-A

MAT

ERIA

LS O

F CO

NST

RUCT

ION MOTOR HOUSING BRASS

CASING BRASSIMPELLER BRASSMOTOR SHAFT 416 STAINLESS STEELHARDWARE STAINLESS STEEL“O” RINGS BUNA-N

MECHANICAL SEALSStandard: CARBON / CERAMIC

UPPER BEARING SINGLE ROW-BALLLOWER BEARING SINGLE ROW-BALL

HYDROMATIC®

SP50ABSUBMERSIBLE NON-CLOG, SEWAGE EJECTOR

Page 85: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

SPECIFICATION DATA

1.01 GENERAL Contractor shall furnish all labor, materials, equipment and incidentals required to provide __________

(Qty.) submersible centrifugal sewage ejector pump(s) as specified herein. The pump model covered in this specification is the SP50AB. The pump furnished for this application shall be MODEL ____________ as manufactured by Hydromatic Pumps.

2.01 DESIGN CONDITIONS Each pump shall be rated ________ H.P., ________ volts, ________ phase, ________ hertz and operate

at ________ RPM.

3.01 OPERATING CONDITIONS The pump shall deliver ________ U.S. GPM/LPS at feet/meters TDH, and handle a ________ inch solid.

The curve submitted for approval shall state, in addition to head and capacity performance, solid handling capability, amp rating, and design impeller diameter.

4.01 CONSTRUCTION Each pump shall be of the sealed submersible type, incorporating features normally found in pumps

furnished for the heavy duty industrial or municipal markets. These features include:

1. The pump volute, motor, and seal housing shall be high quality gray cast iron, ASTM A-48, Class 30. The castings for the SP50AB shall be Naval Bronze ASTM B-584.

2. The pump inlet shall be open and clear, without screening to provide access for sewage and solids.

3. All external mating parts shall be machined and Buna N, O-Ring sealed. 4. All fasteners exposed to the pumped liquid shall be 300 series stainless steel. 5. All power cords shall be water resistant UL or CSA approved, with double insulation, and sized

as a function of Amp. draw.

5.01 MOTOR AND SHAFT The stator, rotor and bearings shall be mounted in a sealed submersible type housing. Single phase

motors shall be split phase or capacitor start with centrifugal switch. Three phase motors shall be Polyphase. Full Load and Locked Rotor Amps. as well as Start and Run winding resistance shall be tabulated for each pump.

6.01 BEARINGS, SHAFT AND MECHANICAL SEAL An upper radial and lower thrust bearing shall be required. These shall be heavy duty single row ball

bearings which are permanently and continuously lubricated and cooled by the dielectric oil which fills the motor housing. The motor shaft shall be stainless steel and sealed from the pumped liquid with a carbon ceramic mechanical seal.

MODEL: SP50AB

Wholesale Products Page: 6920-5Dated: January 2001

HYDROMATIC®

SP50ABSUBMERSIBLE NON-CLOG, SEWAGE EJECTOR

Page 86: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

USA CANADA293 Wright Street, DelAvAN, Wi 53115 WWW.hYDrOMAtiC.COM 269 trilliUM Drive, KitCheNer, ONtAriO, CANADA N2g 4W5Ph: 888-957-8677 OrDerS FAX: 800-426-9446 Ph: 519-896-2163 OrDerS FAX: 519-896-6337

Because we are continuously improving our products and services, Pentair reserves the right to change specifications without prior notice.

© 2013 Pentair ltd. All rights reserved. W-01-260 (03/25/13)

SPECIFICATION DATA

7.01 IMPELLER The Impeller shall be high capacity, two vane, non-clog design with pump out vanes on the back side.

These vanes wash out grit and stringy material that will damage the shaft and mechanical seal.

8.01 AUTOMATIC CONTROL All single phase pumps should be capable of automatic operation.

9.01 PRESSURE SWITCH The Single Phase SP50AB pump is furnished with a pressure diaphragm switch that features a piggy-back

plug that allows the pump to be operated manually without removal from the sump.

10.01 PAINTING All cast iron parts shall be painted before assembly with a water reducible alkyd air dried enamel.

The paint shall be applied in one coat with a minimum thickness of 3 to 4 mils.

11.01 TESTING All pumps shall be individually tested to include the following:

1. The pump and power cord shall be visually inspected for imperfections, cuts or nicks. 2. The pump shall have a ground continuity check and the motor chamber shall be Hi-potted

to test for moisture content and/or insulation defects. 3. The motor and volute housing shall be pressurized and a 10 second air leak decay test run. 4. Oil is added, and the pump is run. Voltage and current are monitored visually, electronically,

and the tester listens for any noise or malfunction.

Wholesale Products Page: 6920-6Dated: January 2001

HYDROMATIC®

SP50ABSUBMERSIBLE NON-CLOG, SEWAGE EJECTOR

Page 87: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

TOTA

L H

EAD

IN F

EET

Capacity-U.S. G.P.M.

Liters/Second

HEA

D-M

ETER

S

9

6

3

0

30

20

10

00 20 40 60 80 100 120 1400 2 4 6 8

SP50 & SP50AB

SP40

Conditions of Service:

GPM:______ TDH:______

The curves reflect maximum performance characteristics without exceeding full load (Nameplate) horsepower. All pumps have a service factor of 1.2. Operation is recommended in the bounded area with operational point within the curve limit. Performance curves are based on actual tests with clear water at 70° F. and 1280 feet site elevation.

HYDROMATIC®

SP40SUBMERSIBLE SEWAGE EJECTOR

PERFORMANCE DATA

Wholesale Products Page: 6140-1Dated: January 2001

RPM: 1750 Discharge: 2” Solids: 1 ¼”

Page 88: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

HYDROMATIC®

SP40SUBMERSIBLE SEWAGE EJECTOR

DIMENSIONAL DATA

Wholesale Products Page: 6140-2Dated: January 2001

All dimensions in inches. Metric for international use. Component dimensions may vary ± 1/8 inch. Dimensional data not for construction purpose unless certified. Dimensions and weights are approximate. On/Off level adjustable. We reserve the right to make revisions to our product (s) and the product (s) specifications without notice.

3-3/4"(95)

PUMP OFF

4-5/16"(109)

13-1/16"(331)

12-1/4"(311)

PUMP ON

14-1/16"(357)

3-3/4"(95)

4-5/16"(109)

3-15/16"(100)

6-13/16"(173)

5-1/8"(130)

2" NPTDISCHARGE

4-15/16"(125)

DISCHARGEHEIGHT

Page 89: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

ELECTRICAL DATAHYDROMATIC®

SP40SUBMERSIBLE SEWAGE EJECTORMODEL: SP40

Wholesale Products Page: 6140-3Dated: January 2001

R.P.M. 1750MOTOR TYPE OIL FILLED WITH AUTOMATIC RESET THERMAL OVERLOAD

GENERAL INSULATION CLASS AMOTOR PROTECTION AUTOMATIC RESET / THERMAL OVERLOAD

HP VOLTAGE PHASE NEC CODE SERVICE FACTOR FULL LOAD AMPS

4/10115

1 - 19.5

230 4.7

Page 90: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

TECHNICAL DATAHYDROMATIC®

SP40SUBMERSIBLE SEWAGE EJECTORMODEL: SP40

Wholesale Products Page: 6140-4Dated: January 2001

Physical DataDISCHARGE SIZE 2” NPTSOLIDS SIZE ¼”IMPELLER TYPE NON CLOGCABLE LENGTH 10’ STANDARD

20’ OPTIONALPAINT PAINTED AFTER ASSEMBLY, DARK GREEN, WATER REDUCIBLE ENAMEL,

ONE COAT, AIR DRIED.

TemperatureMAXIMUM LIQUID 140°FMAXIMUM STATOR -OIL FLASH POINT -

Technical DataPOWER CORD TYPE SJTW

MAT

ERIA

LS O

F CO

NST

RUCT

ION MOTOR HOUSING CAST IRON

CASING CAST IRONIMPELLER THERMOPLASTICMOTOR SHAFT STEELHARDWARE STAINLESS STEEL“O” RINGS BUNA-N

MECHANICAL SEALSStandard: CARBON / CERAMIC

UPPER BEARING SINGLE ROW-BALLLOWER BEARING SINGLE ROW-BALL

Page 91: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

SPECIFICATION DATAHYDROMATIC®

SP40SUBMERSIBLE SEWAGE EJECTOR

1.01 GENERAL Contractor shall furnish all labor, materials, equipment and incidentals required to provide __________

(Qty.) submersible centrifugal sewage ejector pump(s) as specified herein. The pump model covered in this specification is the SP40. The pump furnished for this application shall be MODEL ____________ as manufactured by Hydromatic Pumps.

2.01 DESIGN CONDITIONS Each pump shall be rated ________ H.P., ________ volts, ________ phase, ________ hertz and operate

at ________ RPM.

3.01 OPERATING CONDITIONS The pump shall deliver ________ U.S. GPM/LPS at feet/meters TDH, and handle a ________ inch solid.

The curve submitted for approval shall state, in addition to head and capacity performance, solid handling capability, amp rating, and design impeller diameter.

4.01 CONSTRUCTION Each pump shall be of the sealed submersible type, incorporating features normally found in pumps

furnished for the residential market. These features include:

1. The pump volute, motor, and seal housing shall be high quality gray cast iron, ASTM A-48, Class 30.

2. The pump inlet shall be open and clear, without screening to provide access for sewage and solids.

3. All external mating parts shall be machined and Buna N, O-Ring sealed. 4. All fasteners exposed to the pumped liquid shall be 300 series stainless steel. 5. All power cords shall be water resistant UL or CSA approved, with double insulation, and sized

as a function of Amp. draw.

5.01 MOTOR AND SHAFT The stator, rotor and bearings shall be mounted in a sealed submersible type housing. Single phase

motors shall be split phase or capacitor start with centrifugal switch. Three phase motors shall be Polyphase. Full Load and Locked Rotor Amps as well as Start and Run winding resistance shall be tabulated for each pump.

6.01 BEARINGS, SHAFT AND MECHANICAL SEAL An upper radial and lower thrust bearing shall be required. These shall be heavy duty single row ball

bearings which are permanently and continuously lubricated and cooled by the dielectric oil which fills the motor housing. The motor shaft shall be stainless steel and sealed from the pumped liquid with a carbon ceramic mechanical seal.

MODEL: SP40

Wholesale Products Page: 6140-5Dated: January 2001

Page 92: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

USA CANADA293 Wright Street, DelAvAN, Wi 53115 WWW.hYDrOMAtiC.COM 269 trilliUM Drive, KitCheNer, ONtAriO, CANADA N2g 4W5Ph: 888-957-8677 OrDerS FAX: 800-426-9446 Ph: 519-896-2163 OrDerS FAX: 519-896-6337

Because we are continuously improving our products and services, Pentair reserves the right to change specifications without prior notice.

© 2013 Pentair ltd. All rights reserved. W-01-260 (03/25/13)

SPECIFICATION DATAHYDROMATIC®

SP40SUBMERSIBLE SEWAGE EJECTOR

7.01 IMPELLER The Impeller shall be high capacity, two vane, non-clog design with pump out vanes on the back side.

These vanes wash out grit and stringy material that will damage the shaft and mechanical seal.

8.01 AUTOMATIC CONTROL All single phase pumps should be capable of automatic operation.

9.01 PRESSURE SWITCH The Single Phase SP40 pump is furnished with a pressure diaphragm switch that features a piggy-back

plug that allows the pump to be operated manually without removal from the sump.

10.01 PAINTING All cast iron parts shall be painted before assembly with a water reducible alkyd air dried enamel.

The paint shall be applied in one coat with a minimum thickness of 3 to 4 mils.

11.01 TESTING All pumps shall be individually tested to include the following:

1. The pump and power cord shall be visually inspected for imperfections, cuts or nicks. 2. The pump shall have a ground continuity check and the motor chamber shall be Hi-potted

to test for moisture content and/or insulation defects. 3. The motor and volute housing shall be pressurized and a 10 second air leak decay test run. 4. Oil is added, and the pump is run. Voltage and current are monitored visually, electronically,

and the tester listens for any noise or malfunction.

Wholesale Products Page: 6140-6Dated: January 2001

Page 93: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

TOTA

L H

EAD

IN F

EET

Capacity-U.S. G.P.M.

Liters/Second

HEA

D-M

ETER

S

18

12

6

00 20 40 60 80 100 120 140

0 2 4 6 8

SPD100H

SPD50H

60

40

20

0

Conditions of Service:

GPM:______ TDH:______

The curves reflect maximum performance characteristics without exceeding full load (Nameplate) horsepower. All pumps have a service factor of 1.2. Operation is recommended in the bounded area with operational point within the curve limit. Performance curves are based on actual tests with clear water at 70° F. and 1280 feet site elevation.

HYDROMATIC®

SPD50H/100HSUBMERSIBLE HIGH HEAD, DOUBLE SEAL EFFLUENT

PERFORMANCE DATA

Wholesale Products Page: 6130-1Dated: September 2011Supersedes: April 2002

RPM: 3450 Discharge: 2” Solids: ¾”

SPD50HSPD100H

Page 94: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

All dimensions in inches. Metric for international use. Component dimensions may vary ± 1/8 inch. Dimensional data not for construction purpose unless certified. Dimensions and weights are approximate. On/Off level adjustable. We reserve the right to make revisions to our product (s) and the product (s) specifications without notice.

DIMENSIONAL DATA

Wholesale Products Page: 6130-2Dated: September 2011

HYDROMATIC®

SPD50H/100HSUBMERSIBLE HIGH HEAD, DOUBLE SEAL EFFLUENT

Page 95: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

ELECTRICAL DATA

Wholesale Products Page: 6130-3Dated: September 2011

MODEL: SPD50HR.P.M. 3450MOTOR TYPE OIL FILLED WITH AUTOMATIC RESET OVERLOADMOTOR PROTECTION THERMAL OVERLOAD WITH AUTOMATIC RESET

HP VOLTAGE PHASE NEC CODE SERVICE FACTOR FULL LOAD AMPS

1/2

1151

- 1

14230 7200

3

3.6230 3.5460 1.8575 1.9

HYDROMATIC®

SPD50H/100HSUBMERSIBLE HIGH HEAD, DOUBLE SEAL EFFLUENT

Page 96: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

ELECTRICAL DATA

MODEL: SPD100H

Wholesale Products Page: 6130-4Dated: September 2011

R.P.M. 3450MOTOR TYPE OIL FILLED WITH THERMAL OVERLOADMOTOR PROTECTION THERMAL OVERLOAD WITH AUTOMATIC RESET

HP VOLTAGE PHASE NEC CODE SERVICE FACTOR FULL LOAD AMPS

1

230 1

- 1

9.9200

3

5.5230 5.2460 2.5575 2.5

HYDROMATIC®

SPD50H/100HSUBMERSIBLE HIGH HEAD, DOUBLE SEAL EFFLUENT

Page 97: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

TECHNICAL DATA

MODEL: SPD50H

Wholesale Products Page: 6130-5Dated: September 2011

Physical DataDISCHARGE SIZE 2” NPT (STANDARD), 3” NPT (OPTIONAL)SOLIDS SIZE ¾”IMPELLER TYPE 2 VANE NON CLOGCABLE LENGTH 10’ STANDARD

20’ OPTIONALPAINT PAINTED AFTER ASSEMBLY, DARK GREEN, WATER REDUCIBLE ENAMEL,

ONE COAT, AIR DRIED.

TemperatureMAXIMUM LIQUID 140°FMAXIMUM STATOR -OIL FLASH POINT -

Technical DataPOWER CORD TYPE SJTW / STW-A

MAT

ERIA

LS O

F CO

NST

RUCT

ION MOTOR HOUSING CAST IRON

CASING CAST IRONIMPELLER CAST IRONMOTOR SHAFT -HARDWARE STAINLESS STEEL“O” RINGS -

MECHANICAL SEALSStandard: CARBON / CERAMIC

UPPER BEARING BALLLOWER BEARING BALL

HYDROMATIC®

SPD50H/100HSUBMERSIBLE HIGH HEAD, DOUBLE SEAL EFFLUENT

Page 98: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

TECHNICAL DATA

MODEL: SPD100H

Wholesale Products Page: 6130-6Dated: September 2011

Physical DataDISCHARGE SIZE 2” NPT (STANDARD) 3” NPT (OPTIONAL)SOLIDS SIZE ¾”IMPELLER TYPE 2 VANE NON CLOGCABLE LENGTH 20’ STANDARDPAINT PAINTED AFTER ASSEMBLY, DARK GREEN, WATER REDUCIBLE ENAMEL,

ONE COAT, AIR DRIED.

TemperatureMAXIMUM LIQUID 140°FMAXIMUM STATOR -OIL FLASH POINT -

Technical DataPOWER CORD TYPE STW-A

MAT

ERIA

LS O

F CO

NST

RUCT

ION MOTOR HOUSING CAST IRON

CASING CAST IRONIMPELLER CAST IRONMOTOR SHAFT 416 STAINLESS STEELHARDWARE STAINLESS STEEL“O” RINGS BUNA-N

MECHANICAL SEALSStandard: CARBON / CERAMIC

UPPER BEARING BALLLOWER BEARING BALL

HYDROMATIC®

SPD50H/100HSUBMERSIBLE HIGH HEAD, DOUBLE SEAL EFFLUENT

Page 99: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

SPECIFICATION DATA

1.01 GENERAL Contractor shall furnish all labor, materials, equipment and incidentals required to provide __________

(Qty.) submersible centrifugal high head double seal effluent pump(s) as specified herein. The pump models covered in this specification are the SPD50H and SPD100H. The pump furnished for this application shall be MODEL ____________ as manufactured by Hydromatic Pumps.

2.01 DESIGN CONDITIONS Each pump shall be rated ________ H.P., ________ volts, ________ phase, ________ hertz and operate

at ________ RPM.

3.01 OPERATING CONDITIONS The pump shall deliver ________ U.S. GPM/LPS at feet/meters TDK, and handle a ________ inch solid.

The curve submitted for approval shall state, in addition to head and capacity performance, solid handling capability, amp rating, and design impeller diameter.

4.01 CONSTRUCTION Each pump shall be of the sealed submersible type, incorporating features normally found in pumps

furnished for the residential market. These features include:

1. The pump volute and motor housing shall be high quality gray cast iron, ASTM A-48, Class 30. 2. The pump inlet shall be open and clear, without screening to provide access for effluent and

septic tank solids. 3. All external mating parts shall be machined and Buna N, O-Ring sealed. 4. All fasteners exposed to the pumped liquid shall be 300 series stainless steel. 5. All power cords shall be water resistant UL or CSA approved, with double insulation, and sized

as a function of Amp. draw.

5.01 MOTOR AND SHAFT The stator, rotor and bearings shall be mounted in a sealed submersible type housing. Single phase

motors shall be split phase with solid state switch and start capacitor. Three phase motors shall be Polyphase. Full Load and Locked Rotor Amps as well as Start and Run winding resistance shall be tabulated for each pump.

6.01 BEARINGS AND SHAFT A thrust bearing shall be required. It shall be heavy duty single row ball bearings which are permanently

and continuously lubricated and cooled by the dielectric oil which fills the motor housing. The motor shaft shall be stainless steel and sealed from the pumped liquid with a carbon ceramic mechanical seal.

7.01 SEALS AND SENSORS The rotor and stator in the motor housing shall be separated and protected from the pumped liquid by an

oil filled housing incorporating two type 21 carbon ceramic mechanical seals mounted in tandem.

MODELS: SHEF50 and SHEF100

Wholesale Products Page: 6130-7Dated: September 2011

HYDROMATIC®

SPD50H/100HSUBMERSIBLE HIGH HEAD, DOUBLE SEAL EFFLUENT

Page 100: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

USA CANADA293 WrigHt Street, DelAvAN, Wi 53115 WWW.HYDrOMAtiC.COM 269 trilliUM Drive, KitCHeNer, ONtAriO, CANADA N2g 4W5PH: 888-957-8677 OrDerS FAX: 800-426-9446 PH: 519-896-2163 OrDerS FAX: 519-896-6337

Because we are continuously improving our products and services, Pentair reserves the right to change specifications without prior notice.

© 2013 Pentair ltd. All rights reserved. W-01-260 (03/25/13)

SPECIFICATION DATA

Wholesale Products Page: 6130-8Dated: September 2011

This seal housing shall be equipped with a moisture sensing probe installed between the seals, and the sensing of moisture in the seal chamber shall be automatic, continuous and not require the pump be stopped or removed from the wet well.

8.01 EXCEPTIONS (SENSOR) The seal failure sensor is optional on single phase automatic and single phase manual pumps.

9.01 IMPELLER The Impeller shall be high capacity, two vane, high head design with pump out vanes on the back side.

These vanes wash out grit and stringy material that will damage the shaft and mechanical seal.

10.01 AUTOMATIC CONTROL All single phase pumps should be capable of automatic operation.

11.01 PRESSURE SWITCH The Single Phase SPD50H pump is furnished with a pressure diaphragm switch that is UL listed for water

and sewage and CSA certified. The diaphragm switch cord shall be fitted with a piggy-back plug that allows the pump to be operated manually without removal from the sump.

12.01 FLOAT SWITCH The SPD100AH pump (automatic version) is supplied with a tilt-sensitive wide-angle float switch which is

sealed in a non-corrosive PVC enclosure. The switch is UL listed for water and sewage and CSA certified. The float switch cord shall also be fitted with a piggy-back plug that allows the pump to be operated manually without removal from the sump.

13.01 PAINTING All cast iron parts shall be painted before assembly with a water reducible alkyd air dried enamel.

The paint shall be applied in one coat with a minimum thickness of 3 to 4 mils.

14.01 TESTING All pumps shall be individually tested to include the following:

1. The pump and power cord shall be visually inspected for imperfections, cuts or nicks. 2. The pump shall have a ground continuity check and the motor chamber shall be Hi-potted

to test for moisture content and/or insulation defects. 3. The motor and volute housing shall be pressurized and a 10 second air leak decay test run. 4. Oil is added, and the pump is run. Voltage and current are monitored visually, electronically,

and the tester listens for any noise or malfunction.

HYDROMATIC®

SPD50H/100HSUBMERSIBLE HIGH HEAD, DOUBLE SEAL EFFLUENT

Page 101: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

Conditions of Service:

GPM:______ TDH:______

The curves reflect maximum performance characteristics without exceeding full load (Nameplate) horsepower. All pumps have a service factor of 1.2. Operation is recommended in the bounded area with operational point within the curve limit. Performance curves are based on actual tests with clear water at 70° F. and 1280 feet site elevation.

HYDROMATIC®

SHEF45HIGH HEAD EFFLUENT

PERFORMANCE DATA

Wholesale Products Page: H10465-1Dated: January 2014

RPM: 3450 Discharge: 2” Solids: ¾”

CAPACITY GALLONS PER MINUTE

6501 0112

TOTA

L H

EAD

IN M

ETER

S

TOTA

L H

EAD

IN F

EET

CAPACITY LITERS PER MINUTE

50

40

30

20

10

0

15

12

9

6

3

0

0 50 100 150 200 250 300 350

0 10 20 30 40 50 60 70 80 90 100

6535 0312

Page 102: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

All dimensions in inches. Metric for international use. Component dimensions may vary ± 1/8 inch. Dimensional data not for construction purpose unless certified. Dimensions and weights are approximate. On/Off level adjustable. We reserve the right to make revisions to our product (s) and the product (s) specifications without notice.

DIMENSIONAL DATAHYDROMATIC®

SHEF45HIGH HEAD EFFLUENT

Wholesale Products Page: H10465-2Dated: January 2014

5.88 [149.4]

3.90 [99.1] 7.29 [185.2]

3.54 [89.8]

4.33 [109.9]

DISCHARGE 2" NPT

4.39 [111.5]

1.51 [38.4]

12.59 [319.8]

15.48 [393.3]

6534 0312

Page 103: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

ELECTRICAL DATAHYDROMATIC®

SHEF45HIGH HEAD EFFLUENT

Wholesale Products Page: H10465-3Dated: January 2014

R.P.M. 3450MOTOR TYPE THERMAL OVERLOAD, OIL FILLEDMOTOR PROTECTION AUTOMATIC RESET / THERMAL OVERLOAD

HP VOLTAGE PHASE NEC CODE SERVICE FACTOR FULL LOAD AMPS

1/2115 1 - 1 9.0230 1 1 4.5

MODEL: SHEF45 HIGH HEAD EFFLUENT

SHEF456535 0312

Page 104: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

TECHNICAL DATAHYDROMATIC®

SHEF45HIGH HEAD EFFLUENT

Wholesale Products Page: H10465-4Dated: January 2014

Physical DataDISCHARGE SIZE 2” NPTSOLIDS SIZE ¾”IMPELLER TYPE NON CLOG CAST IRONCABLE LENGTH 20’ STANDARD

30’ OPTIONALPAINT PAINTED AFTER ASSEMBLY DARK GREEN, WATER REDUCIBLE ENAMEL,

ONE COAT, AIR DRIED.

TemperatureMAXIMUM LIQUID 140°FMAXIMUM STATOR -OIL FLASH POINT -

Technical DataPOWER CORD TYPE SJTOOW / SJTOOW-A

MAT

ERIA

LS O

F CO

NST

RUCT

ION MOTOR HOUSING CAST IRON

CASING CAST IRONIMPELLER THERMOPLASTICMOTOR SHAFT 416 STAINLESS STEELHARDWARE STAINLESS STEEL“O” RINGS BUNA - N

MECHANICAL SEALSStandard: CARBON / CERAMIC

UPPER BEARING BALLLOWER BEARING BALL

MODEL: SHEF45 HIGH HEAD EFFLUENT

Page 105: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

SPECIFICATION DATAHYDROMATIC®

SHEF45HIGH HEAD EFFLUENT

Wholesale Products Page: H10465-5Dated: January 2014

MODELS: SUBMERSIBLE SUMP/ EFFLUENT MODEL SHEF451.01 GENERAL

Contractor shall furnish all labor, materials, equipment and incidentals required to provide __________ (Qty.) submersible centrifugal high head effluent pump(s) as specified herein. The pump model covered in this specification is the SHEF45. The pump furnished for this application shall be MODEL ____________ as manufactured by Hydromatic.

2.01 DESIGN CONDITIONSEach pump shall be rated _______ H.P., ________ volts, _______ phase,_______ hertz and operate at _______ RPM.

3.01 OPERATING CONDITIONSThe pump shall deliver _______ U.S. GPM/LPS at feet/meters TDK, and handle a _______ inch solid. The curve submitted for approval shall state, in addition to head and capacity performance, solid handling capability, amp rating, and design impeller diameter.

4.01 CONSTRUCTIONEach pump shall be of the sealed submersible type incorporating features normally found in pumps furnished for the residential market. These features include:A The pump volute and motor housing shall be high quality gray cast iron, ASTM A-48, Class 30.B The pump inlet shall be open and clear, without screening to provide access for effluent and

septic tank solids.C All external mating parts shall be machined and Buna N, O-Ring sealed.D All fasteners exposed to the pumped liquid shall be 300 series stainless steel.E All power cords shall be water resistant UL or CSA approved, with double insulation and sized as

a function of Amp. draw.

5.01 MOTOR AND SHAFTThe stator, rotor and bearings shall be mounted in a sealed submersible type housing. Single phase motors shall be split phase with centrifugal switch and start capacitor. Full Load and Locked Rotor Amps as well as Start and Run winding resistance shall be tabulated for each pump.

Page 106: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

SPECIFICATION DATAHYDROMATIC®

SHEF45HIGH HEAD EFFLUENT

Wholesale Products Page: H10465-6Dated: January 2014

MODELS: SUBMERSIBLE SUMP/ EFFLUENT MODEL SHEF456.01 BEARINGS, SHAFT AND MECHANICAL SEAL

An upper radial and lower thrust bearing shall be required. The upper and lower bearings shall be heavy duty single row ball bearings. The bearings will be permanently and continuously lubricated and cooled by the dielectric oil which fills the motor housing. The motor shaft shall be corrosion resistant steel and sealed from the pumped liquid with a carbon ceramic mechanical seal.

7.01 IMPELLERThe impeller shall be high capacity, two vane, high head design with four pump out vanes on the back side. These vanes wash out grit and stringy material that could damage the shaft and mechanical seal.

8.01 AUTOMATIC CONTROLAll single phase pumps should be capable of automatic operation.

9.01 FLOAT SWITCHThe pump is supplied with a tilt sensitive wide-angle float switch which is sealed in a non-corrosive PVC enclosure. The switch is UL listed for water and sewage and CSA certified. The float switch shall also be fitted with a piggy-back plug that allows the pump to be operated manually without removal from the sump.

10.01 PAINTINGAll cast iron parts shall be painted before assembly with a water reducible alkyd air dried enamel. The paint shall be applied in one coat with a minimum thickness of 3 to 4 mils.

11.01 TESTINGAll pumps shall be individually tested to include the following:A The pump and power cord shall be visually inspected for imperfections, cuts or nicks.B The pump shall have a ground continuity check and the motor chamber shall be Hi-potted to test

for moisture content and/or insulation defects.C The motor and volute housing shall be pressurized and a 10 second air leak decay test run.D A specific amount of oil is added. The pump is run in a fully automated, sequenced, control

console, which monitors voltage, current and watts visually and electronically. The tester listens for any noise or malfunction.

Page 107: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

TOTA

L H

EAD

IN F

EET

Capacity-U.S. G.P.M.Liters/Second

HEA

D-M

ETER

S

30

24

18

12

6

0

100

80

60

40

20

00 20 40 60 80 1000 2 4 6

SHEF50

SHEF100

Conditions of Service:

GPM:______ TDH:______

The curves reflect maximum performance characteristics without exceeding full load (Nameplate) horsepower. All pumps have a service factor of 1.2. Operation is recommended in the bounded area with operational point within the curve limit. Performance curves are based on actual tests with clear water at 70° F. and 1280 feet site elevation.

HYDROMATIC®

SHEF50/100SUBMERSIBLE HIGH HEAD EFFLUENT

PERFORMANCE DATA

Wholesale Products Page: 6370-1Dated: January 2001

RPM: 3450 Discharge: 2” Solids: ¾”

SHEF50SHEF100

Page 108: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

All dimensions in inches. Metric for international use. Component dimensions may vary ± 1/8 inch. Dimensional data not for construction purpose unless certified. Dimensions and weights are approximate. On/Off level adjustable. We reserve the right to make revisions to our product (s) and the product (s) specifications without notice.

DIMENSIONAL DATA

12-1/4"(311)

14"(356)

4-9/16"(116)

3-15/16"(84) 7-1/16" (179)

5-1/4"(133)

3-11/16"(94)

3-11/16"(94)

2" (51)

DISCHARGE 2" NPT

DISCHARGE PIPENOT INCLUDED

FLOATSWITCH

14-1/2"(368)

16-5/16"(414)

4-1/16"(103) 7-3/8" (187)

5-5/8" (143)

4-1/8"(105)

4-9/16"(116)

2" (51)

DISCHARGE 2" NPT

4" (102)

Wholesale Products Page: 6370-2Dated: January 2001

HYDROMATIC®

SHEF50/100SUBMERSIBLE HIGH HEAD EFFLUENT

SHEF50 SHEF100

Page 109: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

ELECTRICAL DATA

MODEL: SHEF50

Wholesale Products Page: 6370-3Dated: January 2001

R.P.M. 3450MOTOR TYPE THERMAL OVERLOAD WITH AUTOMATIC RESETMOTOR PROTECTION AUTOMATIC RESET / THERMAL OVERLOAD

HP VOLTAGE PHASE NEC CODE SERVICE FACTOR FULL LOAD AMPS

1/2

1151

- 1

14.5200 7.6230

33.1

460 1.6575 1.2

HYDROMATIC®

SHEF50SUBMERSIBLE HIGH HEAD EFFLUENT

Page 110: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

ELECTRICAL DATA

MODEL: SHEF100

Wholesale Products Page: 6370-4Dated: January 2001

R.P.M. 3450MOTOR TYPE OIL FILLED WITH AUTOMATIC RESET THERMAL OVERLOADMOTOR PROTECTION AUTOMATIC RESET / THERMAL OVERLOAD

HP VOLTAGE PHASE NEC CODE SERVICE FACTOR FULL LOAD AMPS

1

2001

- 1

12.1230 12.1230

35.8

460 2.8575 1.9

HYDROMATIC®

SHEF100SUBMERSIBLE HIGH HEAD EFFLUENT

Page 111: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

TECHNICAL DATA

MODEL: SHEF50

Wholesale Products Page: 6370-5Dated: January 2001

Physical DataDISCHARGE SIZE 2” NPTSOLIDS SIZE ¾”IMPELLER TYPE NON CLOGCABLE LENGTH 20’ STANDARD

30’ OPTIONALPAINT PAINTED AFTER ASSEMBLY DARK GREEN, WATER REDUCIBLE ENAMEL,

ONE COAT, AIR DRIED.

TemperatureMAXIMUM LIQUID 140°FMAXIMUM STATOR -OIL FLASH POINT -

Technical DataPOWER CORD TYPE SJTW / STW-A

MAT

ERIA

LS O

F CO

NST

RUCT

ION MOTOR HOUSING CAST IRON

CASING CAST IRONIMPELLER THERMOPLASTICMOTOR SHAFT 416 STAINLESS STEELHARDWARE STAINLESS STEEL“O” RINGS BUNA-N

MECHANICAL SEALSStandard: CARBON / CERAMIC

UPPER BEARING BALLLOWER BEARING BALL

HYDROMATIC®

SHEF50SUBMERSIBLE HIGH HEAD EFFLUENT

Page 112: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

TECHNICAL DATA

MODEL: SHEF100

Wholesale Products Page: 6370-6Dated: January 2001

HYDROMATIC®

SHEF100SUBMERSIBLE HIGH HEAD EFFLUENT

Physical DataDISCHARGE SIZE 2” NPTSOLIDS SIZE ¾”IMPELLER TYPE NON CLOGCABLE LENGTH 20’ STANDARD

30’ OPTIONALPAINT PAINTED AFTER ASSEMBLY, DARK GREEN, WATER REDUCIBLE ENAMEL,

ONE COAT, AIR DRIED.

TemperatureMAXIMUM LIQUID 140°FMAXIMUM STATOR -OIL FLASH POINT -

Technical DataPOWER CORD TYPE SJTW / STW-A

MAT

ERIA

LS O

F CO

NST

RUCT

ION MOTOR HOUSING CAST IRON

CASING CAST IRONIMPELLER THERMOPLASTICMOTOR SHAFT STAINLESS STEELHARDWARE STAINLESS STEEL“O” RINGS BUNA-N

MECHANICAL SEALSStandard: CARBON / CERAMIC

UPPER BEARING BALLLOWER BEARING BALL

Page 113: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

SPECIFICATION DATA

1.01 GENERAL Contractor shall furnish all labor, materials, equipment and incidentals required to provide __________

(Qty.) submersible centrifugal high head effluent pump(s) as specified herein. The pump models covered in this specification are the SHEF 50 and SHEF100. The pump furnished for this application shall be MODEL ____________ as manufactured by Hydromatic Pumps.

2.01 DESIGN CONDITIONS Each pump shall be rated ________ H.P., ________ volts, ________ phase, ________ hertz and operate

at ________ RPM.

3.01 OPERATING CONDITIONS The pump shall deliver ________ U.S. GPM/LPS at feet/meters TDH, and handle a ________ inch solid.

The curve submitted for approval shall state, in addition to head and capacity performance, solid handling capability, amp rating, and design impeller diameter.

4.01 CONSTRUCTION Each pump shall be of the sealed submersible type, incorporating features normally found in pumps

furnished for the residential market. These features include:

1. The pump volute, motor, and seal housing shall be high quality gray cast iron, ASTM A-48, Class 30.

2. The pump inlet shall be open and clear, without screening to provide access for effluent and septic tank solids.

3. All external mating parts shall be machined and Buna N, O-Ring sealed. 4. All fasteners exposed to the pumped liquid shall be 300 series stainless steel. 5. All power cords shall be water resistant UL or CSA approved, with double insulation, and sized

as a function of Amp. draw.

5.01 MOTOR AND SHAFT The stator, rotor and bearings shall be mounted in a sealed submersible type housing. Single phase

motors shall be split phase with centrifugal switch and start capacitor. Three phase motors shall be Polyphase. Full Load and Locked Rotor Amps as well as Start and Run winding resistance shall be tabulated for each pump.

6.01 BEARINGS, SHAFT AND MECHANICAL SEAL An upper radial and lower thrust bearing shall be required. The upper and lower bearings in the SHEF50

and SHEF100 shall be heavy duty single row ball bearings. The bearings will be permanently and continuously lubricated and cooled by the dielectric oil which fills the motor housing. The motor shaft shall be corrosion resistant steel and sealed from the pumped liquid with a carbon ceramic mechanical seal.

MODELS: SHEF50 and SHEF100

Wholesale Products Page: 6370-7Dated: January 2001

HYDROMATIC®

SHEF50/100SUBMERSIBLE HIGH HEAD EFFLUENT

Page 114: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

USA CANADA293 WrigHt StrEEt, DElAvAN, Wi 53115 WWW.HYDrOMAtiC.COM 269 trilliUM DrivE, KitCHENEr, ONtAriO, CANADA N2g 4W5PH: 888-957-8677 OrDErS FAX: 800-426-9446 PH: 519-896-2163 OrDErS FAX: 519-896-6337

Because we are continuously improving our products and services, Pentair reserves the right to change specifications without prior notice.

© 2013 Pentair ltd. All rights reserved. W-01-260 (03/25/13)

SPECIFICATION DATA

7.01 IMPELLER The Impeller in the SHEF50/100 shall be high capacity, two vane, high head design with four pump out

vanes on the back side. These vanes wash out grit and stringy material that will damage the shaft and mechanical seal.

8.01 AUTOMATIC CONTROL All single phase pumps should be capable of automatic operation.

9.01 FLOAT SWITCH The SHEF50 and SHEF100 pumps are supplied with a tilt sensitive wide-angle float switch which is sealed

in a non-corrosive PVC enclosure. The switch is UL listed for water and sewage and CSA certified. The float switch shall also be fitted with a piggy-back plug that allows the pump to be operated manually without removal from the sump.

10.01 PAINTING All cast iron parts shall be painted before assembly with a water reducible alkyd air dried enamel.

The paint shall be applied in one coat with a minimum thickness of 3 to 4 mils.

11.01 TESTING All pumps shall be individually tested to include the following:

1. The pump and power cord shall be visually inspected for imperfections, cuts or nicks. 2. The pump shall have a ground continuity check and the motor chamber shall be Hi-potted

to test for moisture content and/or insulation defects. 3. The motor and volute housing shall be pressurized and a 10 second air leak decay test run. 4. Oil is added, and the pump is run. Voltage and current are monitored visually, electronically,

and the tester listens for any noise or malfunction.

Wholesale Products Page: 6370-8Dated: January 2001

HYDROMATIC®

SHEF50/100SUBMERSIBLE HIGH HEAD EFFLUENT

Page 115: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

SHEF40

0 10 20 30 40 50 60 70

FT

40

30

20

10

0

GPM

Conditions of Service:

GPM:______ TDH:______

The curves reflect maximum performance characteristics without exceeding full load (Nameplate) horsepower. All pumps have a service factor of 1.2. Operation is recommended in the bounded area with operational point within the curve limit. Performance curves are based on actual tests with clear water at 70° F. and 1280 feet site elevation.

HYDROMATIC®

SHEF40SUBMERSIBLE HIGH HEAD EFFLUENT

PERFORMANCE DATA

Wholesale Products Page: 6680-1Dated: April 2002

Supersedes: January 2001RPM: 1550 Discharge: 1 ½” Solids: ¾”

Page 116: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

All dimensions in inches. Metric for international use. Component dimensions may vary ± 1/8 inch. Dimensional data not for construction purpose unless certified. Dimensions and weights are approximate. On/Off level adjustable. We reserve the right to make revisions to our product (s) and the product (s) specifications without notice.

DIMENSIONAL DATA

Wholesale Products Page: 6680-2Dated: January 2001

HYDROMATIC®

SHEF40SUBMERSIBLE HIGH HEAD EFFLUENT

Page 117: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

ELECTRICAL DATA

MODEL: SHEF40

Wholesale Products Page: 6680-3Dated: January 2001

R.P.M. 1550MOTOR TYPE SHADED POLE WITH THERMAL OVERLOAD, OIL FILLEDMOTOR PROTECTION AUTOMATIC RESET / OVERLOAD PROTECTED

HP VOLTAGE PHASE NEC CODE SERVICE FACTOR FULL LOAD AMPS

4115

1 - 112.0

230 6.5

HYDROMATIC®

SHEF40SUBMERSIBLE HIGH HEAD EFFLUENT

Page 118: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

TECHNICAL DATA

MODEL: SHEF40

Wholesale Products Page: 6680-4Dated: January 2001

Physical DataDISCHARGE SIZE 1 ½” NPTSOLIDS SIZE ¾”IMPELLER TYPE VORTEXCABLE LENGTH 10’ STANDARD

20’ OPTIONALPAINT PAINTED AFTER ASSEMBLY, DARK GREEN, WATER REDUCIBLE ENAMEL,

ONE COAT, AIR DRIED.

TemperatureMAXIMUM LIQUID 140°FMAXIMUM STATOR -OIL FLASH POINT -

Technical DataPOWER CORD TYPE SJTW

MAT

ERIA

LS O

F CO

NST

RUCT

ION MOTOR HOUSING CAST IRON

CASING CAST IRONIMPELLER THERMOPLASTICMOTOR SHAFT STEELHARDWARE STAINLESS STEEL“O” RINGS BUNA-N

MECHANICAL SEALSStandard: CARBON / CERAMIC

UPPER BEARING N/ALOWER BEARING SINGLE ROW-BALL

HYDROMATIC®

SHEF40SUBMERSIBLE HIGH HEAD EFFLUENT

Page 119: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

SPECIFICATION DATA

1.01 GENERAL Contractor shall furnish all labor, materials, equipment and incidentals required to provide __________

(Qty.) submersible centrifugal high head effluent pump(s) as specified herein. The pump model covered in this specification is the SHEF40. The pump furnished for this application shall be MODEL ____________ as manufactured by Hydromatic Pumps.

2.01 DESIGN CONDITIONS Each pump shall be rated ________ H.P., ________ volts, ________ phase, ________ hertz and operate

at ________ RPM.

3.01 OPERATING CONDITIONS The pump shall deliver ________ U.S. GPM/LPS at feet/meters TDH, and handle a ________ inch solid.

The curve submitted for approval shall state, in addition to head and capacity performance, solid handling capability, amp rating, and design impeller diameter.

4.01 CONSTRUCTION Each pump shall be of the sealed submersible type, incorporating features normally found in pumps

furnished for the residential market. These features include:

1. The pump volute, motor, and seal housing shall be high quality gray cast iron, ASTM A-48, Class 30.

2. The pump inlet shall be open and clear, without screening to provide access for effluent and septic tank solids.

3. All external mating parts shall be machined and Buna N, O-Ring sealed. 4. All fasteners exposed to the pumped liquid shall be 300 series stainless steel. 5. All power cords shall be water resistant UL or CSA approved, with double insulation, and sized

as a function of Amp. draw.

5.01 MOTOR AND SHAFT The stator, rotor and bearings shall be mounted in a sealed submersible type housing. Single phase

motors shall be shaded pole (SHEF40). Three phase motors shall be Polyphase. Full Load and Locked Rotor Amps as well as Start and Run winding resistance shall be tabulated for each pump.

6.01 BEARINGS, SHAFT AND MECHANICAL SEAL An upper radial and lower thrust bearing shall be required. The upper bearing shall be brass (SHEF40),

while the lower bearing is a single row ball. The bearings will be permanently and continuously lubricated and cooled by the dielectric oil which fills the motor housing. The motor shaft shall be corrosion resistant steel and sealed from the pumped liquid with a carbon ceramic mechanical seal.

MODEL: SHEF40

Wholesale Products Page: 6680-5Dated: January 2001

HYDROMATIC®

SHEF40SUBMERSIBLE HIGH HEAD EFFLUENT

Page 120: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

USA CANADA293 WrigHt StrEEt, DElAvAN, Wi 53115 WWW.HYDrOMAtiC.COM 269 trilliUM DrivE, KitCHENEr, ONtAriO, CANADA N2g 4W5PH: 888-957-8677 OrDErS FAX: 800-426-9446 PH: 519-896-2163 OrDErS FAX: 519-896-6337

Because we are continuously improving our products and services, Pentair reserves the right to change specifications without prior notice.

© 2013 Pentair ltd. All rights reserved. W-01-260 (03/25/13)

SPECIFICATION DATA

7.01 IMPELLER The Impeller in the SHEF40 shall be high capacity, two vane, high head design.

8.01 AUTOMATIC CONTROL All single phase pumps should be capable of automatic operation.

9.01 FLOAT SWITCH The SHEF40 pump is supplied with a tilt sensitive wide-angle float switch which is sealed in a non-

corrosive PVC enclosure. The switch is UL listed for water and sewage and CSA certified. The float switch shall also be fitted with a piggy-back plug that allows the pump to be operated manually without removal from the sump.

10.01 PAINTING All cast iron parts shall be painted before assembly with a water reducible alkyd air dried enamel.

The paint shall be applied in one coat with a minimum thickness of 3 to 4 mils.

11.01 TESTING All pumps shall be individually tested to include the following:

1. The pump and power cord shall be visually inspected for imperfections, cuts or nicks. 2. The pump shall have a ground continuity check and the motor chamber shall be Hi-potted

to test for moisture content and/or insulation defects. 3. The motor and volute housing shall be pressurized and a 10 second air leak decay test run. 4. Oil is added, and the pump is run. Voltage and current are monitored visually, electronically,

and the tester listens for any noise or malfunction.

Wholesale Products Page: 6680-6Dated: January 2001

HYDROMATIC®

SHEF40SUBMERSIBLE HIGH HEAD EFFLUENT

Page 121: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

TOTA

L H

EAD

IN F

EET

Capacity-U.S. G.P.M.

Liters/Second

HEA

D-M

ETER

S

12

9

6

3

0

40

30

20

10

00 10 20 30 40 50

0 1 2 3

SHEF30

Conditions of Service:

GPM:______ TDH:______

The curves reflect maximum performance characteristics without exceeding full load (Nameplate) horsepower. All pumps have a service factor of 1.2. Operation is recommended in the bounded area with operational point within the curve limit. Performance curves are based on actual tests with clear water at 70° F. and 1280 feet site elevation.

HYDROMATIC®

SHEF30SUBMERSIBLE HIGH HEAD EFFLUENT

PERFORMANCE DATA

Wholesale Products Page: 6350-1Dated: January 2001

RPM: 1550 Discharge: 1 ½” Solids: ¾”

Page 122: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

All dimensions in inches. Metric for international use. Component dimensions may vary ± 1/8 inch. Dimensional data not for construction purpose unless certified. Dimensions and weights are approximate. On/Off level adjustable. We reserve the right to make revisions to our product (s) and the product (s) specifications without notice.

DIMENSIONAL DATA

11/2" NPTDISCHARGE

31/2"(89)

5 7/8"(149)

41/2"(114)

31/2"(89)

31/2"(89)

91/2" (241)

3 3/4"(95)

9 7/8"(250)

PUMP ON

117/8"(301)

Wholesale Products Page: 6350-2Dated: January 2001

HYDROMATIC®

SHEF30SUBMERSIBLE HIGH HEAD EFFLUENT

Page 123: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

ELECTRICAL DATA

MODEL: SHEF30

Wholesale Products Page: 6350-3Dated: January 2001

R.P.M. 1550MOTOR TYPE SHADED POLE WITH THERMAL OVERLOAD, OIL FILLEDMOTOR PROTECTION AUTOMATIC RESET / OVERLOAD PROTECTED

HP VOLTAGE PHASE NEC CODE SERVICE FACTOR FULL LOAD AMPS1/3 115 1 - 1 8.0

HYDROMATIC®

SHEF30SUBMERSIBLE HIGH HEAD EFFLUENT

Page 124: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

TECHNICAL DATA

MODEL: SHEF30

Wholesale Products Page: 6350-4Dated: January 2001

Physical DataDISCHARGE SIZE 1 ½” NPTSOLIDS SIZE ¾”IMPELLER TYPE VORTEXCABLE LENGTH 20’ STANDARDPAINT PAINTED DARK GREEN, WATER REDUCIBLE ENAMEL, ONE COAT,

AIR DRIED.

TemperatureMAXIMUM LIQUID 140°FMAXIMUM STATOR -OIL FLASH POINT -

Technical DataPOWER CORD TYPE SJTW

MAT

ERIA

LS O

F CO

NST

RUCT

ION MOTOR HOUSING CAST IRON

CASING CAST IRONIMPELLER THERMOPLASTICMOTOR SHAFT STEELHARDWARE STAINLESS STEEL“O” RINGS BUNA-N

MECHANICAL SEALSStandard: CARBON / CERAMIC

UPPER BEARING N/ALOWER BEARING SINGLE ROW-BALL

HYDROMATIC®

SHEF30SUBMERSIBLE HIGH HEAD EFFLUENT

Page 125: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

SPECIFICATION DATA

1.01 GENERAL Contractor shall furnish all labor, materials, equipment and incidentals required to provide __________

(Qty.) submersible centrifugal high head effluent pump(s) as specified herein. The pump model covered in this specification is the SHEF30. The pump furnished for this application shall be MODEL ____________ as manufactured by Hydromatic Pumps.

2.01 DESIGN CONDITIONS Each pump shall be rated ________ H.P., ________ volts, ________ phase, ________ hertz and operate

at ________ RPM.

3.01 OPERATING CONDITIONS The pump shall deliver ________ U.S. GPM/LPS at feet/meters TDH, and handle a ________ inch solid.

The curve submitted for approval shall state, in addition to head and capacity performance, solid handling capability, amp rating, and design impeller diameter.

4.01 CONSTRUCTION Each pump shall be of the sealed submersible type, incorporating features normally found in pumps

furnished for the residential market. These features include:

1. The pump volute, motor, and seal housing shall be high quality gray cast iron, ASTM A-48, Class 30.

2. The pump inlet shall be open and clear, without screening to provide access for effluent and septic tank solids.

3. All external mating parts shall be machined and Buna N, O-Ring sealed. 4. All fasteners exposed to the pumped liquid shall be 300 series stainless steel. 5. All power cords shall be water resistant UL or CSA approved, with double insulation, and sized

as a function of Amp. draw.

5.01 MOTOR AND SHAFT The stator, rotor and bearings shall be mounted in a sealed submersible type housing. Single phase

motors shall be shaded pole (SHEF30). Three phase motors shall be Polyphase. Full Load and Locked Rotor Amps as well as Start and Run winding resistance shall be tabulated for each pump.

6.01 BEARINGS, SHAFT AND MECHANICAL SEAL An upper bushing and lower thrust bearing shall be required. The upper bearing shall be Cast Iron

(SHEF30), while the lower bearing is a single row ball. The bearings will be permanently and continuously lubricated and cooled by the dielectric oil which fills the motor housing. The motor shaft shall be corrosion resistant steel and sealed from the pumped liquid with a carbon ceramic mechanical seal.

MODEL: SHEF30

Wholesale Products Page: 6350-5Dated: January 2001

HYDROMATIC®

SHEF30SUBMERSIBLE HIGH HEAD EFFLUENT

Page 126: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

USA CANADA293 WrigHt StrEEt, DElAvAN, Wi 53115 WWW.HYDrOMAtiC.COM 269 trilliUM DrivE, KitCHENEr, ONtAriO, CANADA N2g 4W5PH: 888-957-8677 OrDErS FAX: 800-426-9446 PH: 519-896-2163 OrDErS FAX: 519-896-6337

Because we are continuously improving our products and services, Pentair reserves the right to change specifications without prior notice.

© 2013 Pentair ltd. All rights reserved. W-01-260 (03/25/13)

SPECIFICATION DATA

7.01 IMPELLER The Impeller in the SHEF30 shall be thermoplastic, eight vane, vortex design with three pump out

vanes on the back side. These vanes wash out grit and stringy material that will damage the shaft and mechanical seal.

8.01 AUTOMATIC CONTROL All single phase pumps should be capable of automatic operation.

9.01 FLOAT SWITCH The SHEF30 pump is supplied with a tilt sensitive wide-angle float switch which is sealed in a non-

corrosive PVC enclosure. The switch is UL listed for water and sewage and CSA certified. The float switch shall also be fitted with a piggy-back plug that allows the pump to be operated manually without removal from the sump.

10.01 PAINTING All cast iron parts shall be painted before assembly with a water reducible alkyd air dried enamel.

The paint shall be applied in one coat with a minimum thickness of 3 to 4 mils.

11.01 TESTING All pumps shall be individually tested to include the following:

1. The pump and power cord shall be visually inspected for imperfections, cuts or nicks. 2. The pump shall have a ground continuity check and the motor chamber shall be Hi-potted

to test for moisture content and/or insulation defects. 3. The motor and volute housing shall be pressurized and a 10 second air leak decay test run. 4. Oil is added, and the pump is run. Voltage and current are monitored visually, electronically,

and the tester listens for any noise or malfunction.

Wholesale Products Page: 6350-6Dated: January 2001

HYDROMATIC®

SHEF30SUBMERSIBLE HIGH HEAD EFFLUENT

Page 127: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

1/2 HP

32

24

16

8

0

1750 R.P.M.

0 10 20 30 40 50 60

TOTA

L DY

NAM

IC H

EAD-

FEET

CAPACITY-U.S. G.P.M.

Conditions of Service:

GPM:______ TDH:______

The curves reflect maximum performance characteristics without exceeding full load (Nameplate) horsepower. All pumps have a service factor of 1.2. Operation is recommended in the bounded area with operational point within the curve limit. Performance curves are based on actual tests with clear water at 70° F. and 1280 feet site elevation.

HYDROMATIC®

OSP50ABSUBMERSIBLE SUMP/EFFLUENT

PERFORMANCE DATA

Wholesale Products Page: 6230-1Dated: April 2002

Supersedes: January 2001RPM: 1750 Discharge: 1 ¼” Solids: ⅝”

Page 128: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

All dimensions in inches. Metric for international use. Component dimensions may vary ± 1/8 inch. Dimensional data not for construction purpose unless certified. Dimensions and weights are approximate. On/Off level adjustable. We reserve the right to make revisions to our product (s) and the product (s) specifications without notice.

HYDROMATIC®

OSP50ABSUBMERSIBLE SUMP/EFFLUENT

DIMENSIONAL DATA

Wholesale Products Page: 6230-2Dated: April 2002

Supersedes: January 2001

Page 129: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

ELECTRICAL DATAHYDROMATIC®

OSP50ABSUBMERSIBLE SUMP/EFFLUENTMODEL: OSP50AB

Wholesale Products Page: 6230-3Dated: July 2008

Supersedes: April 2002

R.P.M. 1750MOTOR TYPE OIL FILLED WITH AUTOMATIC RESET, SPLIT PHASEGENERAL INSULATION CLASS AMOTOR PROTECTION AUTOMATIC RESET / THERMAL OVERLOAD

HP VOLTAGE PHASE NEC CODE SERVICE FACTOR FULL LOAD AMPS1/2 115 1 - 1 9.5

Page 130: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

TECHNICAL DATAHYDROMATIC®

OSP50ABSUBMERSIBLE SUMP/EFFLUENTMODEL: OSP50AB

Wholesale Products Page: 6230-4Dated: April 2002

Supersedes: January 2001

Physical DataDISCHARGE SIZE 1 ¼” NPTSOLIDS SIZE ⅝”IMPELLER TYPE OPEN VANECABLE LENGTH 20’ STANDARDPAINT PAINTED AFTER ASSEMBLY, DARK GREEN, WATER REDUCIBLE ENAMEL,

ONE COAT, AIR DRIED.

TemperatureMAXIMUM LIQUID 140°FMAXIMUM STATOR -OIL FLASH POINT -

Technical DataPOWER CORD TYPE STW-A

MAT

ERIA

LS O

F CO

NST

RUCT

ION MOTOR HOUSING BRONZE

CASING BRONZEIMPELLER BRONZEMOTOR SHAFT STEELHARDWARE STAINLESS STEEL“O” RINGS BUNA-N

MECHANICAL SEALSStandard: CARBON / CERAMIC

UPPER BEARING SINGLE ROW-BALLLOWER BEARING SINGLE ROW-BALL

Page 131: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

SPECIFICATION DATAHYDROMATIC®

OSP50ABSUBMERSIBLE SUMP/EFFLUENT

1.01 GENERAL Contractor shall furnish all labor, materials, equipment and incidentals required to provide __________

(Qty.) submersible centrifugal sump/effluent pump(s) as specified herein. The pump model covered in this specification is the OSP50AB. The pump furnished for this application shall be MODEL ____________ as manufactured by Hydromatic Pumps.

2.01 DESIGN CONDITIONS Each pump shall be rated ________ H.P., ________ volts, ________ phase, ________ hertz and operate

at ________ RPM.

3.01 OPERATING CONDITIONS The pump shall deliver ________ U.S. GPM/LPS at feet/meters TDH, and handle a ________ inch solid.

The curve submitted for approval shall state, in addition to head and capacity performance, solid handling capability, amp rating, and design impeller diameter.

4.01 CONSTRUCTION Each pump shall be of the sealed submersible type, incorporating features normally found in pumps

furnished for the residential market. These features include:

1. The castings for the OSP50AB shall be Naval Bronze ASTM B-584. 2. The pump inlet shall be open and clear, without screening to provide access for effluent and

septic tank solids. 3. All external mating parts shall be machined and Buna N, O-Ring sealed. 4. All fasteners exposed to the pumped liquid shall be 300 series stainless steel. 5. All power cords shall be water resistant UL or CSA approved, with double insulation, and sized

as a function of Amp. draw.

5.01 MOTOR AND SHAFT The stator, rotor and bearings shall be mounted in a sealed submersible type housing. Single phase

motors shall be Split phase with centrifugal switch. Full Load and Locked Rotor Amps as well as Start and Run winding resistance shall be tabulated for each pump.

6.01 BEARINGS, SHAFT AND MECHANICAL SEAL An upper radial and lower thrust bearing shall be required. These shall be heavy duty single row ball

bearings which are both permanently and continuously lubricated and cooled by the dielectric oil which fills the motor housing. The motor shaft shall be corrosion resistant steel and sealed from the pumped liquid with a carbon ceramic mechanical seal.

MODEL: OSP50AB

Wholesale Products Page: 6230-5Dated: April 2002

Supersedes: January 2001

Page 132: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

USA CANADA293 Wright Street, DelAvAN, Wi 53115 WWW.hYDrOMAtiC.COM 269 trilliUM Drive, KitCheNer, ONtAriO, CANADA N2g 4W5Ph: 888-957-8677 OrDerS FAX: 800-426-9446 Ph: 519-896-2163 OrDerS FAX: 519-896-6337

Because we are continuously improving our products and services, Pentair reserves the right to change specifications without prior notice.

© 2013 Pentair ltd. All rights reserved. W-01-260 (03/25/13)

SPECIFICATION DATAHYDROMATIC®

OSP50ABSUBMERSIBLE SUMP/EFFLUENT

7.01 IMPELLER The Impeller shall be Naval Bronze ASTM B-584 six vane, open design.

8.01 AUTOMATIC CONTROL All pumps should be capable of automatic operation.

9.01 PRESSURE SWITCH The OSP50AB Single Phase pump is furnished with a pressure diaphragm switch that is UL listed for

water and sewage and CSA certified. The diaphragm switch shall be fitted with a piggy-back plug that allows the pump to be operated manually without removal from the sump.

10.01 TESTING All pumps shall be individually tested to include the following:

1. The pump and power cord shall be visually inspected for imperfections, cuts or nicks. 2. The pump shall have a ground continuity check and the motor chamber shall be Hi-potted

to test for moisture content and/or insulation defects. 3. The motor and volute housing shall be pressurized and a 10 second air leak decay test run. 4. A specific amount of oil is now added. The pump is run in a fully automated, sequenced, control

console, which monitors voltage, current and watts visually and electronically. The tester listens for any noise or malfunction.

Wholesale Products Page: 6230-6Dated: April 2002

Supersedes: January 2001

Page 133: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

TOTA

L HE

AD IN

FEE

T

100

10

20

30

40

20 30 40 50 60 70

OSP50OSP50AB

Capacity-U.S. G.P.M.

Liters/Second 0 1 2 3 4

HEAD

-MET

ERS

0

3

12

6

9

0

Conditions of Service:

GPM:______ TDH:______

The curves reflect maximum performance characteristics without exceeding full load (Nameplate) horsepower. All pumps have a service factor of 1.2. Operation is recommended in the bounded area with operational point within the curve limit. Performance curves are based on actual tests with clear water at 70° F. and 1280 feet site elevation.

HYDROMATIC®

OSP50SUBMERSIBLE SUMP/EFFLUENT

PERFORMANCE DATA

Wholesale Products Page: 6220-1Dated: April 2002

Supersedes: January 2001RPM: 1750 Discharge: 1 ½” Solids: ⅝”

Page 134: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

All dimensions in inches. Metric for international use. Component dimensions may vary ± 1/8 inch. Dimensional data not for construction purpose unless certified. Dimensions and weights are approximate. On/Off level adjustable. We reserve the right to make revisions to our product (s) and the product (s) specifications without notice.

HYDROMATIC®

OSP50SUBMERSIBLE SUMP/EFFLUENT

DIMENSIONAL DATA

Wholesale Products Page: 6220-2Dated: April 2002

Supersedes: January 2001

Page 135: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

ELECTRICAL DATAHYDROMATIC®

OSP50SUBMERSIBLE SUMP/EFFLUENTMODEL: OSP50

Wholesale Products Page: 6220-3Dated: July 2008

Supersedes: October 2002

R.P.M. 1750MOTOR TYPE OIL FILLED WITH AUTOMATIC RESET, SPLIT PHASEGENERAL INSULATION CLASS AMOTOR PROTECTION AUTOMATIC RESET / THERMAL OVERLOAD

HP VOLTAGE PHASE NEC CODE SERVICE FACTOR FULL LOAD AMPS

1/2115

1 - 19.5

230 5.2

Page 136: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

TECHNICAL DATAHYDROMATIC®

OSP50SUBMERSIBLE SUMP/EFFLUENTMODEL: OSP50

Wholesale Products Page: 6220-4Dated: April 2002

Supersedes: January 2001

Physical DataDISCHARGE SIZE 1 ½” NPTSOLIDS SIZE ⅝”IMPELLER TYPE OPEN VANECABLE LENGTH 10’ STANDARD

20’ OPTIONALPAINT PAINTED AFTER ASSEMBLY, DARK GREEN, WATER REDUCIBLE ENAMEL,

ONE COAT, AIR DRIED.

TemperatureMAXIMUM LIQUID 140°FMAXIMUM STATOR -OIL FLASH POINT -

Technical DataPOWER CORD TYPE SJTW

MAT

ERIA

LS O

F CO

NST

RUCT

ION MOTOR HOUSING CAST IRON

CASING CAST IRONIMPELLER NAVAL BRONZE (OPEN VANE), THERMOPLASTIC (VORTEX)MOTOR SHAFT STEELHARDWARE STAINLESS STEEL“O” RINGS BUNA-N

MECHANICAL SEALSStandard: CARBON / CERAMIC

UPPER BEARING SINGLE ROW-BALLLOWER BEARING SINGLE ROW-BALL

Page 137: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

SPECIFICATION DATAHYDROMATIC®

OSP50SUBMERSIBLE SUMP/EFFLUENT

1.01 GENERAL Contractor shall furnish all labor, materials, equipment and incidentals required to provide __________

(Qty.) submersible centrifugal sump/effluent pump(s) as specified herein. The pump model covered in this specification is the OSP50. The pump furnished for this application shall be MODEL ____________ as manufactured by Hydromatic Pumps.

2.01 DESIGN CONDITIONS Each pump shall be rated ________ H.P., ________ volts, ________ phase, ________ hertz and operate

at ________ RPM.

3.01 OPERATING CONDITIONS The pump shall deliver ________ U.S. GPM/LPS at feet/meters TDH, and handle a ________ inch solid.

The curve submitted for approval shall state, in addition to head and capacity performance, solid handling capability, amp rating, and design impeller diameter.

4.01 CONSTRUCTION Each pump shall be of the sealed submersible type, incorporating features normally found in pumps

furnished for the residential market. These features include:

1. The pump volute, motor, and seal housing of the OSP50 shall be high quality gray cast iron, ASTM A-48, Class 30.

2. The pump inlet shall be open and clear, without screening to provide access for effluent and septic tank solids.

3. All external mating parts shall be machined and Buna N, O-Ring sealed. 4. All fasteners exposed to the pumped liquid shall be 300 series stainless steel. 5. All power cords shall be water resistant UL or CSA approved, with double insulation, and sized

as a function of Amp. draw.

5.01 MOTOR AND SHAFT The stator, rotor and bearings shall be mounted in a sealed submersible type housing. Single phase

motors shall be Split phase with centrifugal switch. Full Load and Locked Rotor Amps as well as Start and Run winding resistance shall be tabulated for each pump.

6.01 BEARINGS, SHAFT AND MECHANICAL SEAL An upper radial and lower thrust bearing shall be required. These shall be heavy duty single row ball

bearings which are both permanently and continuously lubricated and cooled by the dielectric oil which fills the motor housing. The motor shaft shall be corrosion resistant steel and sealed from the pumped liquid with a carbon ceramic mechanical seal.

MODEL: OSP50

Wholesale Products Page: 6220-5Dated: April 2002

Supersedes: January 2001

Page 138: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

USA CANADA293 Wright Street, DelAvAN, Wi 53115 WWW.hYDrOMAtiC.COM 269 trilliUM Drive, KitCheNer, ONtAriO, CANADA N2g 4W5Ph: 888-957-8677 OrDerS FAX: 800-426-9446 Ph: 519-896-2163 OrDerS FAX: 519-896-6337

Because we are continuously improving our products and services, Pentair reserves the right to change specifications without prior notice.

© 2013 Pentair ltd. All rights reserved. W-01-260 (03/25/13)

SPECIFICATION DATAHYDROMATIC®

OSP50SUBMERSIBLE SUMP/EFFLUENT

7.01 IMPELLER The Impeller shall be Naval Bronze ASTM B-584 six vane, open design, or thermoplastic, high capacity,

eight vane, vortex design.

8.01 AUTOMATIC CONTROL All pumps should be capable of automatic operation.

9.01 PRESSURE SWITCH The OSP50 Single Phase pump is furnished with a pressure diaphragm switch that is UL listed for water

and sewage and CSA certified. The diaphragm switch shall be fitted with a piggy-back plug that allows the pump to be operated manually without removal from the sump.

10.01 PAINTING All cast iron parts shall be painted before assembly with a water reducible alkyd air dried enamel.

The paint shall be applied in one coat with a minimum thickness of 3 to 4 mils.

11.01 TESTING All pumps shall be individually tested to include the following:

1. The pump and power cord shall be visually inspected for imperfections, cuts or nicks. 2. The pump shall have a ground continuity check and the motor chamber shall be Hi-potted

to test for moisture content and/or insulation defects. 3. The motor and volute housing shall be pressurized and a 10 second air leak decay test run. 4. A specific amount of oil is now added. The pump is run in a fully automated, sequenced, control

console, which monitors voltage, current and watts visually and electronically. The tester listens for any noise or malfunction.

Wholesale Products Page: 6220-6Dated: April 2002

Supersedes: January 2001

Page 139: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

8

4

0 0

10

20

30

0 10 20 30 40 50 60

0.0

0 2 4 6 8 10 12

1.0 2.0 3.0

Hea

d, m

eter

s

Hea

d, fe

et

Capacity, US GPM

liters/second

cu meters/hr

1/3 HP

Conditions of Service:

GPM:______ TDH:______

The curves reflect maximum performance characteristics without exceeding full load (Nameplate) horsepower. All pumps have a service factor of 1.2. Operation is recommended in the bounded area with operational point within the curve limit. Performance curves are based on actual tests with clear water at 70° F. and 1280 feet site elevation.

HYDROMATIC®

P33A1PEDESTAL SUMP PUMP

PERFORMANCE DATA

Wholesale Products Page: 6550-1Dated: January 2001

RPM: 1625 Discharge: 1 ¼” Solids: ⅛”

Page 140: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

All dimensions in inches. Metric for international use. Component dimensions may vary ± 1/8 inch. Dimensional data not for construction purpose unless certified. Dimensions and weights are approximate. On/Off level adjustable. We reserve the right to make revisions to our product (s) and the product (s) specifications without notice.

HYDROMATIC®

P33A1PEDESTAL SUMP PUMP

DIMENSIONAL DATA

33.5"(850)

10.5"(266)

9"(228)

1.25"(31)NPTDISCHARGE

Wholesale Products Page: 6550-2Dated: January 2001

Page 141: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

ELECTRICAL DATAHYDROMATIC®

P33A1PEDESTAL SUMP PUMPMODEL: P33A1

Wholesale Products Page: 6550-3Dated: January 2001

R.P.M. 1725MOTOR TYPE SHADED POLE

HP VOLTAGE PHASE NEC CODE SERVICE FACTOR FULL LOAD AMPS1/3 115 1 - 1 6.5

Page 142: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

TECHNICAL DATAHYDROMATIC®

P33A1PEDESTAL SUMP PUMPMODEL: P33A1

Wholesale Products Page: 6550-4Dated: January 2001

Physical DataDISCHARGE SIZE 1 ¼” NPTSOLIDS SIZE ¼”IMPELLER TYPE -CABLE LENGTH 8’ STANDARDPAINT -

TemperatureMAXIMUM LIQUID 140°FMAXIMUM STATOR -OIL FLASH POINT -

Technical DataPOWER CORD TYPE -

MAT

ERIA

LS O

F CO

NST

RUCT

ION MOTOR HOUSING -

CASING THERMOPLASTICIMPELLER THERMOPLASTICMOTOR SHAFT -HARDWARE -“O” RINGS -

MECHANICAL SEALSStandard: -

UPPER BEARING -LOWER BEARING -

Page 143: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

SPECIFICATION DATAHYDROMATIC®

P33A1PEDESTAL SUMP PUMP

1.01 GENERAL Contractor shall furnish all labor, materials, equipment and incidentals required to provide __________

(Qty.) submersible centrifugal non clog sewage pump(s) as specified herein. The pump model covered in this specification is the P33A1. The pump furnished for this application shall be MODEL ____________ as manufactured by Hydromatic Pumps.

2.01 DESIGN CONDITIONS Each pump shall be rated ________ H.P., ________ volts, ________ phase, ________ hertz and operate

at ________ RPM.

3.01 OPERATING CONDITIONS The pump shall deliver ________ U.S. GPM/LPS at feet/meters TDH, and handle a ________ inch solid.

The curve submitted for approval shall state, in addition to head and capacity performance, solid handling capability, amp rating, and design impeller diameter.

4.01 CONSTRUCTION Each pump shall be of the sealed submersible type, incorporating features normally found in pumps

furnished for the heavy duty industrial or municipal markets. These features include:

1. The seal housing for the P33A1 is corrosion resistant high density thermoplastic. 2. The pump inlet shall be open and clear, without screening to provide access for sewage

and solids. 3. All external mating parts shall be machined and Buna N, O-Ring sealed. 4. All fasteners exposed to the pumped liquid shall be 300 series stainless steel. 5. All power cords shall be water resistant UL or CSA approved, with double insulation, and sized

as a function of Amp. draw.

5.01 MOTOR AND SHAFT The stator, rotor and bearings shall be mounted in a sealed submersible type housing. Single phase

motors shall be split phase or capacitor start with centrifugal switch. Three phase motors shall be Polyphase. Full Load and Locked Rotor Amps. as well as Start and Run winding resistance shall be tabulated for each pump.

6.01 BEARINGS, SHAFT AND MECHANICAL SEAL An upper radial and lower thrust bearing shall be required. These shall be heavy duty single row ball

bearings which are permanently and continuously lubricated and cooled by the dielectric oil which fills the motor housing. The motor shaft shall be stainless steel and sealed from the pumped liquid with a carbon ceramic mechanical seal.

MODEL: P33A1

Wholesale Products Page: 6550-5Dated: January 2001

Page 144: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

USA CANADA293 Wright Street, DelAvAN, Wi 53115 WWW.hYDrOMAtiC.COM 269 trilliUM Drive, KitCheNer, ONtAriO, CANADA N2g 4W5Ph: 888-957-8677 OrDerS FAX: 800-426-9446 Ph: 519-896-2163 OrDerS FAX: 519-896-6337

Because we are continuously improving our products and services, Pentair reserves the right to change specifications without prior notice.

© 2013 Pentair ltd. All rights reserved. W-01-260 (03/25/13)

SPECIFICATION DATAHYDROMATIC®

P33A1PEDESTAL SUMP PUMP

7.01 IMPELLER The Impeller shall be high capacity, two vane, non clog design with pump out vanes on the back side.

These vanes wash out grit and stringy material that will damage the shaft and mechanical seal.

8.01 AUTOMATIC CONTROL All single phase pumps should be capable of automatic operation.

9.01 PRESSURE SWITCH The Single Phase pump is furnished with a pressure diaphragm switch that features a piggy-back plug

that allows the pump to be operated manually without removal from the sump.

10.01 FLOAT SWITCH The pump is supplied with a tilt-sensitive wide-angle float switch is sealed in a non-corrosive PVC

enclosure. The unit is UL listed for water and sewage and CSA certified. The float switch shall also be fitted with a piggy-back plug that allows the pump to be operated manually without removal from the sump.

11.01 MANUAL CONTROL The Single Phase pump is not supplied with any type of automatic control. A super or double wide angle

piggy-back float switch can be supplied and fitted to these pumps.

12.01 PAINTING All cast iron parts shall be painted before assembly with a water reducible alkyd air dried enamel.

The paint shall be applied in one coat with a minimum thickness of 3 to 4 mils.

13.01 TESTING All pumps shall be individually tested to include the following:

1. The pump and power cord shall be visually inspected for imperfections, cuts or nicks. 2. The pump shall have a ground continuity check and the motor chamber shall be Hi-potted

to test for moisture content and/or insulation defects. 3. The motor and volute housing shall be pressurized and a 10 second air leak decay test run. 4. Oil is added, and the pump is run. Voltage and current are monitored visually, electronically,

and the tester listens for any noise or malfunction.

Wholesale Products Page: 6550-6Dated: January 2001

Page 145: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

0 10 20 30 40 50 60 70

40

30

20

10

0

GPM

FT

SW/SD/VS50

Conditions of Service:

GPM:______ TDH:______

The curves reflect maximum performance characteristics without exceeding full load (Nameplate) horsepower. All pumps have a service factor of 1.2. Operation is recommended in the bounded area with operational point within the curve limit. Performance curves are based on actual tests with clear water at 70° F. and 1280 feet site elevation.

HYDROMATIC®

SD/SW/VS50SUBMERSIBLE SUMP/EFFLUENT

PERFORMANCE DATA

Wholesale Products Page: 7130-1Dated: July 2006

RPM: 1550 Discharge: 1 ½” Solids: ¾”

SD50 SW50 VS50

Page 146: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

HYDROMATIC®

SD/SW/VS50SUBMERSIBLE SUMP/EFFLUENT

DIMENSIONAL DATA

Wholesale Products Page: 7130-2Dated: July 2006

All dimensions in inches. Metric for international use. Component dimensions may vary ± 1/8 inch. Dimensional data not for construction purpose unless certified. Dimensions and weights are approximate. On/Off level adjustable. We reserve the right to make revisions to our product (s) and the product (s) specifications without notice.

3-7/8"(98)

3-7/8"(98)

3-7/8"(98) 6-5/8" (168)

5" (127)

1-1/2" NPT

10-3/8"(264)

10-7/8"(276)

4" (102)PUMPOFF

7-1/2" (191)PUMP

ON

2-5/8"(67)

DISCHARGEHEIGHT

10-3/8"(264)

9-3/16"(233)

4" (102)PUMPOFF

9" (229)PUMP

ON

2-5/8"(67)

DISCHARGEHEIGHT

SW50

VS50

SD50

Page 147: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

ELECTRICAL DATAHYDROMATIC®

SD/SW/VS50SUBMERSIBLE SUMP/EFFLUENTMODEL: SD/SW/VS50

Wholesale Products Page: 7130-3Dated: July 2006

R.P.M. 1550MOTOR TYPE SHADED POLE WITH THERMAL OVERLOAD, OIL FILLEDMOTOR PROTECTION AUTOMATIC RESET / OVERLOAD PROTECTED

HP VOLTAGE PHASE NEC CODE SERVICE FACTOR FULL LOAD AMPS1/2 115 1 - 1 12.0

SD50 SW50 VS50

Page 148: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

TECHNICAL DATAHYDROMATIC®

SD/SW/VS50SUBMERSIBLE SUMP/EFFLUENTMODEL: SD/SW/VS50

Wholesale Products Page: 7130-4Dated: July 2006

Physical DataDISCHARGE SIZE 1 ½” NPTSOLIDS SIZE ¾”IMPELLER TYPE TWO VANE SEMI-OPENCABLE LENGTH 10’ STANDARD

20’ OPTIONALPAINT PAINTED DARK GREEN, WATER REDUCIBLE ENAMEL, ONE COAT,

AIR DRIED.

TemperatureMAXIMUM LIQUID 120°FMAXIMUM STATOR -OIL FLASH POINT -

Technical DataPOWER CORD TYPE SJTW

MAT

ERIA

LS O

F CO

NST

RUCT

ION MOTOR HOUSING CAST IRON

CASING CAST IRONIMPELLER THERMOPLASTICMOTOR SHAFT STEELHARDWARE STAINLESS STEEL“O” RINGS BUNA-N

MECHANICAL SEALSStandard: CARBON / CERAMIC

UPPER BEARING BRONZE SLEEVELOWER BEARING SINGLE ROW-BALL

Page 149: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

SPECIFICATION DATAHYDROMATIC®

SD/SW/VS50SUBMERSIBLE SUMP/EFFLUENT

1.01 GENERAL Contractor shall furnish all labor, materials, equipment and incidentals required to provide __________

(Qty.) submersible centrifugal sump pump(s) as specified herein. The pump models covered in this specification are the VS50, SW50, and SD50. The pump furnished for this application shall be MODEL ____________ as manufactured by Hydromatic Pumps.

2.01 DESIGN CONDITIONS Each pump shall be rated ________ H.P., ________ volts, ________ phase, ________ hertz and operate

at ________ RPM.

3.01 OPERATING CONDITIONS The pump shall deliver ________ U.S. GPM/LPS at feet/meters TDH, and handle a ________ inch solid.

The curve submitted for approval shall state, in addition to head and capacity performance, solid handling capability, amp rating, and design impeller diameter.

4.01 CONSTRUCTION Each pump shall be of the sealed submersible type, incorporating features normally found in pumps

furnished for the heavy duty industrial or municipal markets. These features include:

1. The pump volute, motor, and seal housing shall be high quality gray cast iron, ASTM A-48, Class 30.

2. The pump shall feature a multiple strainer inlet that prevents clogging from foreign objects and provides optimum operation and reduced maintenance.

3. All external mating parts shall be machined and Buna N, O-Ring sealed. 4. All fasteners exposed to the pumped liquid shall be 300 series stainless steel. 5. All power cords shall be water resistant UL or CSA approved, with double insulation, and sized

as a function of Amp. draw.

5.01 MOTOR AND SHAFT The stator, rotor and bearings shall be mounted in a sealed submersible type housing. Single phase

motors shall be Shaded Pole, with automatic reset thermal overload protection. Full Load and Locked Rotor Amps as well as Run winding resistance shall be tabulated for each pump.

6.01 BEARINGS, SHAFT AND MECHANICAL SEAL An upper radial and lower thrust bearing shall be required. The upper bearing shall be bronze sleeve type

while the lower bearing is heavy duty single row ball. They are both permanently, continuously lubricated and cooled by the dielectric oil, which fills the motor housing. The motor shaft shall be corrosion resistant steel and sealed from the pumped liquid with a carbon ceramic mechanical seal.

MODELS: VS50, SW50 and SD50

Wholesale Products Page: 7130-5Dated: July 2006

Page 150: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

USA CANADA293 Wright Street, DelAVAN, Wi 53115 WWW.hYDrOMAtiC.COM 269 trilliUM DriVe, KitCheNer, ONtAriO, CANADA N2g 4W5Ph: 888-957-8677 OrDerS FAX: 800-426-9446 Ph: 519-896-2163 OrDerS FAX: 519-896-6337

Because we are continuously improving our products and services, Pentair reserves the right to change specifications without prior notice.

© 2013 Pentair ltd. All rights reserved. W-01-260 (03/25/13)

SPECIFICATION DATAHYDROMATIC®

SD/SW/VS50SUBMERSIBLE SUMP/EFFLUENT

7.01 IMPELLER The Impeller shall be a thermoplastic, two vane, semi-open design.

8.01 AUTOMATIC CONTROL All pumps should be capable of automatic operation.

9.01 PRESSURE SWITCH The SD50 single phase pumps are furnished with a pressure diaphragm switch that is UL listed for water

and sewage and CSA certified. The diaphragm switch cord shall be fitted with a piggyback plug that allows the pump to be operated manually without removal from the sump.

10.01 FLOAT SWITCH The SW50 single phase pumps are supplied with a tilt-sensitive wide-angle float switch which is sealed in

a non-corrosive PVC enclosure. The switch is UL listed for water and sewage and QSA certified. The float switch shall also be fitted with a piggyback plug that allows the pump to be operated manually without removal from the sump.

11.01 VERTICAL MECHANICAL SWITCH The VS50 single phase pumps are furnished with a magnetic mechanical switch which is sealed in a non-

corrosive PVC enclosure. The switch will be activated by a PVC float sliding up and down a non-corrosive rod. The mechanical switch cord shall also be fitted with a piggyback plug that allows the pump to be operated manually without removal from the sump.

12.01 PAINTING All cast iron parts shall be painted before assembly with a water reducible alkyd air dried enamel.

The paint shall be applied in one coat with a minimum thickness of 3 to 4 mils.

13.01 TESTING All pumps shall be individually tested to include the following:

1. The pump and power cord shall be visually inspected for imperfections, cuts or nicks. 2. The pump shall have a ground continuity check and the motor chamber shall be Hi-potted

to test for moisture content and/or insulation defects. 3. The motor and volute housing shall be pressurized and a 10 second air leak decay test run. 4. A specific amount of oil is now added. The pump is run in a fully automated, sequenced, control

console, which monitors voltage, current and watts visually and electronically. The tester listens for any noise or malfunction.

Wholesale Products Page: 7130-6Dated: July 2006

Page 151: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

00

10

20

30

SD33, SW33, VS33

10 20 30 40 50

TOTA

L HE

AD IN

FEE

T

Capacity-U.S. G.P.M.

Liters/Second 0 1 2 3

HEAD

-MET

ERS

0

3

9

6

Conditions of Service:

GPM:______ TDH:______

The curves reflect maximum performance characteristics without exceeding full load (Nameplate) horsepower. All pumps have a service factor of 1.2. Operation is recommended in the bounded area with operational point within the curve limit. Performance curves are based on actual tests with clear water at 70° F. and 1280 feet site elevation.

HYDROMATIC®

SD/SW/VS33SUBMERSIBLE SUMP/EFFLUENT

PERFORMANCE DATA

Wholesale Products Page: 6390-1Dated: October 2002

RPM: 1550 Discharge: 1 ½” Solids: ½”

SD33

SW33

VS33

Page 152: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

All dimensions in inches. Metric for international use. Component dimensions may vary ± 1/8 inch. Dimensional data not for construction purpose unless certified. Dimensions and weights are approximate. On/Off level adjustable. We reserve the right to make revisions to our product (s) and the product (s) specifications without notice.

HYDROMATIC®

SD/SW/VS33SUBMERSIBLE SUMP/EFFLUENT

DIMENSIONAL DATA

3-1/2"(89)

5-7/8" (149)4-1/2" (114)

1-1/2" NPT

10-1/8"(257)

11-1/8"(283)

3-3/8" (86)PUMPOFF

7-7/8"(200)

PUMPON

3"(76)

DISCHARGEHEIGHT

10-1/8"(257)

11-1/8"(283)

3"(76)

DISCHARGEHEIGHT

3-1/2"(89)

3-1/2"(89)

3-3/8" (86)PUMPOFF

7-7/8"(200)

PUMPON

Wholesale Products Page: 6390-2Dated: October 2002

SW33

VS33

SD33

Page 153: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

ELECTRICAL DATAHYDROMATIC®

SD/SW/VS33SUBMERSIBLE SUMP/EFFLUENTMODEL: SD/SW/VS33

Wholesale Products Page: 6390-3Dated: October 2002

R.P.M. 1550MOTOR TYPE SHADED POLE WITH THERMAL OVERLOAD, OIL FILLEDMOTOR PROTECTION AUTOMATIC RESET / OVERLOAD PROTECTED

HP VOLTAGE PHASE NEC CODE SERVICE FACTOR FULL LOAD AMPS1/3 115 1 - 1 10.0

SD33

SW33

VS33

Page 154: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

TECHNICAL DATAHYDROMATIC®

SD/SW/VS33SUBMERSIBLE SUMP/EFFLUENTMODEL: SD/SW/VS33

Wholesale Products Page: 6390-4Dated: January 2001

Physical DataDISCHARGE SIZE 1 ½” NPTSOLIDS SIZE ½”IMPELLER TYPE VORTEXCABLE LENGTH 10’ STANDARD

20’ OPTIONALPAINT PAINTED DARK GREEN, WATER REDUCIBLE ENAMEL, ONE COAT,

AIR DRIED.

TemperatureMAXIMUM LIQUID 140°FMAXIMUM STATOR -OIL FLASH POINT -

Technical DataPOWER CORD TYPE SJTW

MAT

ERIA

LS O

F CO

NST

RUCT

ION MOTOR HOUSING CAST IRON

CASING CAST IRONIMPELLER THERMOPLASTICMOTOR SHAFT STEELHARDWARE STAINLESS STEEL“O” RINGS BUNA-N

MECHANICAL SEALSStandard: CARBON / CERAMIC

UPPER BEARING N/ALOWER BEARING SINGLE ROW-BALL

Page 155: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

SPECIFICATION DATAHYDROMATIC®

SD/SW/VS33SUBMERSIBLE SUMP/EFFLUENT

1.01 GENERAL Contractor shall furnish all labor, materials, equipment and incidentals required to provide __________

(Qty.) submersible centrifugal sump/effluent pump(s) as specified herein. The pump models covered in this specification are the VS33, SW33, and SD33. The pump furnished for this application shall be MODEL ____________ as manufactured by Hydromatic Pumps.

2.01 DESIGN CONDITIONS Each pump shall be rated ________ H.P., ________ volts, ________ phase, ________ hertz and operate

at ________ RPM.

3.01 OPERATING CONDITIONS The pump shall deliver ________ U.S. GPM/LPS at feet/meters TDK, and handle a ________ inch solid.

The curve submitted for approval shall state, in addition to head and capacity performance, solid handling capability, amp rating, and design impeller diameter.

4.01 CONSTRUCTION Each pump shall be of the sealed submersible type, incorporating features normally found in pumps

furnished for the residential market. These features include:

1. The pump volute and motor housing shall be high quality gray cast iron, ASTM A-48, Class 30. 2. The pump shall feature a multiple strainer inlet that prevents clogging from foreign objects and

provides optimum operation and reduced maintenance. 3. All external mating parts shall be machined and Buna N, O-Ring sealed. 4. All fasteners exposed to the pumped liquid shall be 300 series stainless steel. 5. All power cords shall be water resistant UL or CSA approved, with double insulation, and sized

as a function of Amp. draw.

5.01 MOTOR AND SHAFT The stator, rotor and bearings shall be mounted in a sealed submersible type housing. Single phase

motors shall be Shaded Pole, with automatic reset thermal overload protection. Full Load and Locked Rotor Amps as well as Run winding resistance shall be tabulated for each pump.

6.01 BEARINGS, SHAFT AND MECHANICAL SEAL An upper bushing bearing and lower thrust bearing shall be required. The upper bearing shall be brass

(VS, SD and SW) while the lower bearing is heavy duty single row ball. They are both permanently, continuously lubricated and cooled by the dielectric oil, which fills the motor housing. The motor shaft shall be corrosion resistant steel and sealed from the pumped liquid with a carbon ceramic mechanical seal.

MODELS: VS33, SW33, and SD33

Wholesale Products Page: 6390-5Dated: October 2002

Page 156: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

USA CANADA293 Wright Street, DelAVAN, Wi 53115 WWW.hYDrOMAtiC.COM 269 trilliUM DriVe, KitCheNer, ONtAriO, CANADA N2g 4W5Ph: 888-957-8677 OrDerS FAX: 800-426-9446 Ph: 519-896-2163 OrDerS FAX: 519-896-6337

Because we are continuously improving our products and services, Pentair reserves the right to change specifications without prior notice.

© 2013 Pentair ltd. All rights reserved. W-01-260 (03/25/13)

SPECIFICATION DATAHYDROMATIC®

SD/SW/VS33SUBMERSIBLE SUMP/EFFLUENT

7.01 IMPELLER The Impeller shall be a thermoplastic, eight vane, vortex design with three pump out vanes on the back

side. These vanes wash out grit and stringy material that will damage the shaft and mechanical seal.

8.01 AUTOMATIC CONTROL All pumps should be capable of automatic operation.

9.01 PRESSURE SWITCH The SD33 Single Phase pump is furnished with a pressure diaphragm switch that is UL listed for water

and sewage and GSA certified. The diaphragm switch cord shall be fitted with a piggy-back plug that allows the pump to be operated manually without removal from the sump.

10.01 FLOAT SWITCH The SW33 Single Phase pump is supplied with a tilt-sensitive wide-angle float switch which is sealed in

a non-corrosive PVC enclosure. The switch is UL listed for water and sewage and QSA certified. The float switch shall also be fitted with a piggy-back plug that allows the pump to be operated manually without removal from the sump.

11.01 VERTICAL MECHANICAL SWITCH The VS33 single phase pump is furnished with a magnetic mechanical switch which is sealed in a non-

corrosive PVC enclosure. The switch will be activated by a PVC float sliding up and down a non-corrosive rod. The mechanical switch cord shall also be fitted with a piggy-back plug that allows the pump to be operated manually without removal from the sump.

12.01 PAINTING All cast iron parts shall be painted before assembly with a water reducible alkyd air dried enamel.

The paint shall be applied in one coat with a minimum thickness of 3 to 4 mils.

13.01 TESTING All pumps shall be individually tested to include the following:

1. The pump and power cord shall be visually inspected for imperfections, cuts or nicks. 2. The pump shall have a ground continuity check and the motor chamber shall be Hi-potted

to test for moisture content and/or insulation defects. 3. The motor and volute housing shall be pressurized and a 10 second air leak decay test run. 4. A specific amount of oil is now added. The pump is run in a fully automated, sequenced, control

console, which monitors voltage, current and watts visually and electronically. The tester listens for any noise or malfunction.

Wholesale Products Page: 6390-6Dated: October 2002

Page 157: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

8

4

0 0

10

20

30

0 10 20 30 40 50 60

0.0

0 2 4 6 8 10 12

1.0 2.0 3.0

Hea

d, m

eter

s

Hea

d, fe

et

Capacity, US GPM

liters/second

cu meters/hr

.3 HP

Conditions of Service:

GPM:______ TDH:______

The curves reflect maximum performance characteristics without exceeding full load (Nameplate) horsepower. All pumps have a service factor of 1.2. Operation is recommended in the bounded area with operational point within the curve limit. Performance curves are based on actual tests with clear water at 70° F. and 1280 feet site elevation.

HYDROMATIC®

W/D/V-A1SUBMERSIBLE SUMP/EFFLUENT

PERFORMANCE DATA

Wholesale Products Page: 6570-1Dated: June 2011

RPM: 1550 Discharge: 1 ½” Solids: ½”

W-A1

V-A1

D-A1

Page 158: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

All dimensions in inches. Metric for international use. Component dimensions may vary ± 1/8 inch. Dimensional data not for construction purpose unless certified. Dimensions and weights are approximate. On/Off level adjustable. We reserve the right to make revisions to our product (s) and the product (s) specifications without notice.

HYDROMATIC®

W/D/V-A1SUBMERSIBLE SUMP/EFFLUENT

DIMENSIONAL DATA

Wholesale Products Page: 6570-2Dated: June 2011

Model Turn On Turn OffD-A1 10” (25cm) 4” (10cm)V-A1 7.875” (20cm) 3.375” (8.5cm)W-A1 9.5” (24cm) 3.5” (9cm)

7-7/8"(200)

10-5/8"(270)

1-1/2" (38)

NPTDISCHARGE

3-1/2"(89)

5-7/8"(149)

4-1/2"(114)

3-1/2"(89)

3-1/2"(89)

3"(76)

PUMP ON

PUMP OFF

Page 159: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

ELECTRICAL DATAHYDROMATIC®

W/D/V-A1SUBMERSIBLE SUMP/EFFLUENTMODEL: D/V/W-A1 Professional Series Sump Pump

Wholesale Products Page: 6570-3Dated: June 2011

D-A1W-A1

V-A1

R.P.M. 1550MOTOR TYPE SHADED POLE WITH THERMAL OVERLOAD, OIL FILLEDMOTOR PROTECTION AUTOMATIC RESET / OVERLOAD PROTECTED

HP VOLTAGE PHASE NEC CODE SERVICE FACTOR FULL LOAD AMPS1/3 115 1 - 1 8.0

Page 160: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

TECHNICAL DATAHYDROMATIC®

W/D/V-A1SUBMERSIBLE SUMP/EFFLUENTMODEL: D/V/W-A1 Professional Series Sump Pump

Wholesale Products Page: 6570-4Dated: June 2011

Physical DataDISCHARGE SIZE 1 ½” NPTSOLIDS SIZE ½”IMPELLER TYPE VORTEXCABLE LENGTH 10’ STANDARD

20’ OPTIONALPAINT PAINTED DARK GREEN, WATER REDUCIBLE ENAMEL, ONE COAT,

AIR DRIED.

TemperatureMAXIMUM LIQUID 140°FMAXIMUM STATOR -OIL FLASH POINT -

Technical DataPOWER CORD TYPE SJTW

MAT

ERIA

LS O

F CO

NST

RUCT

ION MOTOR HOUSING CAST IRON

CASING THERMOPLASTICIMPELLER THERMOPLASTICMOTOR SHAFT STEELHARDWARE STAINLESS STEEL“O” RINGS BUNA-N

MECHANICAL SEALSStandard: CARBON / CERAMIC

UPPER BEARING N/ALOWER BEARING SINGLE ROW-BALL

Page 161: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

SPECIFICATION DATAHYDROMATIC®

W/D/V-A1SUBMERSIBLE SUMP/EFFLUENT

1.01 GENERAL Contractor shall furnish all labor, materials, equipment and incidentals required to provide __________

(Qty.) submersible centrifugal sump/effluent pump(s) as specified herein. The pump models covered in this specification are the V-A1, W-A1, and D-A1. The pump furnished for this application shall be MODEL ____________ as manufactured by Hydromatic Pumps.

2.01 DESIGN CONDITIONS Each pump shall be rated ________ H.P., ________ volts, ________ phase, ________ hertz and operate

at ________ RPM.

3.01 OPERATING CONDITIONS The pump shall deliver ________ U.S. GPM/LPS at feet/meters TDK, and handle a ________ inch solid.

The curve submitted for approval shall state, in addition to head and capacity performance, solid handling capability, amp rating, and design impeller diameter.

4.01 CONSTRUCTION Each pump shall be of the sealed submersible type, incorporating features normally found in pumps

furnished for the residential market. These features include:

1. The pump volute and motor housing shall be high quality gray cast iron, ASTM A-48, Class 30. 2. The pump shall feature a multiple strainer inlet that prevents clogging from foreign objects and

provides optimum operation and reduced maintenance. 3. All external mating parts shall be machined and Buna N, O-Ring sealed. 4. All fasteners exposed to the pumped liquid shall be 300 series stainless steel. 5. All power cords shall be water resistant UL or CSA approved, with double insulation, and sized

as a function of Amp. draw.

5.01 MOTOR AND SHAFT The stator, rotor and bearings shall be mounted in a sealed submersible type housing. Single phase

motors shall be Shaded Pole, with automatic reset thermal overload protection. Full Load and Locked Rotor Amps as well as Run winding resistance shall be tabulated for each pump.

6.01 BEARINGS, SHAFT AND MECHANICAL SEAL A heavy duty single row ball bearing shall be required. It is permanently, continuously lubricated and

cooled by the dielectric oil, which fills the motor housing. The motor shaft shall be corrosion resistant steel and sealed from the pumped liquid with a carbon ceramic mechanical seal.

MODELS: D-A1, V-A1, and W-A1

Wholesale Products Page: 6570-5Dated: June 2011

Page 162: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

USA CANADA293 Wright Street, DelAVAN, Wi 53115 WWW.hYDrOMAtiC.COM 269 trilliUM DriVe, KitCheNer, ONtAriO, CANADA N2g 4W5Ph: 888-957-8677 OrDerS FAX: 800-426-9446 Ph: 519-896-2163 OrDerS FAX: 519-896-6337

Because we are continuously improving our products and services, Pentair reserves the right to change specifications without prior notice.

© 2013 Pentair ltd. All rights reserved. W-01-260 (03/25/13)

SPECIFICATION DATAHYDROMATIC®

W/D/V-A1SUBMERSIBLE SUMP/EFFLUENT

7.01 IMPELLER The Impeller shall be a thermoplastic, eight vane, vortex design with three pump out vanes on the back

side. These vanes wash out grit and stringy material that will damage the shaft and mechanical seal.

8.01 AUTOMATIC CONTROL All pumps should be capable of automatic operation.

9.01 PRESSURE SWITCH The D-A1 Single Phase pump is furnished with a pressure diaphragm switch that is UL listed for water

and sewage and GSA certified. The diaphragm switch cord shall be fitted with a piggy-back plug that allows the pump to be operated manually without removal from the sump.

10.01 FLOAT SWITCH The W-A1 Single Phase pump is supplied with a tilt-sensitive wide-angle float switch which is sealed in

a non-corrosive PVC enclosure. The switch is UL listed for water and sewage and QSA certified. The float switch cord shall also be fitted with a piggy-back plug that allows the pump to be operated manually without removal from the sump.

11.01 VERTICAL MECHANICAL SWITCH The V-A1 single phase pump is furnished with a magnetic mechanical switch which is sealed in a non-

corrosive PVC enclosure. The switch will be activated by a PVC float sliding up and down a non-corrosive rod. The mechanical switch cord shall also be fitted with a piggy-back plug that allows the pump to be operated manually without removal from the sump.

12.01 PAINTING All cast iron parts shall be painted before assembly with a water reducible alkyd air dried enamel.

The paint shall be applied in one coat with a minimum thickness of 3 to 4 mils.

13.01 TESTING All pumps shall be individually tested to include the following:

1. The pump and power cord shall be visually inspected for imperfections, cuts or nicks. 2. The pump shall have a ground continuity check and the motor chamber shall be Hi-potted

to test for moisture content and/or insulation defects. 3. The motor and volute housing shall be pressurized and a 10 second air leak decay test run. 4. A specific amount of oil is now added. The pump is run in a fully automated, sequenced, control

console, which monitors voltage, current and watts visually and electronically. The tester listens for any noise or malfunction.

Wholesale Products Page: 6570-6Dated: June 2011

Page 163: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

1/4 HP

CAPACITY GALLONS PER MINUTE

TOTA

L HE

AD IN

FEE

T

0 5 10 15 20 25 30 35

2422201816141210

86420

Conditions of Service:

GPM:______ TDH:______

The curves reflect maximum performance characteristics without exceeding full load (Nameplate) horsepower. All pumps have a service factor of 1.2. Operation is recommended in the bounded area with operational point within the curve limit. Performance curves are based on actual tests with clear water at 70° F. and 1280 feet site elevation.

HYDROMATIC®

A+SUBMERSIBLE SUMP/EFFLUENT

PERFORMANCE DATA

Wholesale Products Page: 6820-1Dated: January 2001

RPM: 3450 Discharge: 1½” Solids: ¼”

Page 164: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

All dimensions in inches. Metric for international use. Component dimensions may vary ± 1/8 inch. Dimensional data not for construction purpose unless certified. Dimensions and weights are approximate. On/Off level adjustable. We reserve the right to make revisions to our product (s) and the product (s) specifications without notice.

HYDROMATIC®

A+SUBMERSIBLE SUMP/EFFLUENT

DIMENSIONAL DATA

15.5" (393)

10"(254)

11"(279)

Wholesale Products Page: 6820-2Dated: January 2001

Page 165: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

ELECTRICAL DATAHYDROMATIC®

A+SUBMERSIBLE SUMP/EFFLUENTMODEL: BA-1/BV-A1

Wholesale Products Page: 6820-3Dated: January 2001

R.P.M. 3450MOTOR TYPE P.S.C. OIL FILLED MOTORGENERAL INSULATION CLASS AMAXIMUM STATOR TEMPERATURE 105°F

HP VOLTAGE PHASE NEC CODE SERVICE FACTOR FULL LOAD AMPS1/4 115 1 - 1 6.5

Page 166: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

TECHNICAL DATAHYDROMATIC®

A+SUBMERSIBLE SUMP/EFFLUENTMODEL: BA-1/BV-A1

Wholesale Products Page: 6820-4Dated: January 2001

Physical DataDISCHARGE SIZE 1 ½” NPTSOLIDS SIZE ¼”IMPELLER TYPE -CABLE LENGTH 10’ STANDARDPAINT -

TemperatureMAXIMUM LIQUID 140°FMAXIMUM STATOR -OIL FLASH POINT -

Technical DataPOWER CORD TYPE SJTW

MAT

ERIA

LS O

F CO

NST

RUCT

ION MOTOR HOUSING CAST IRON

CASING THERMOPLASTICIMPELLER THERMOPLASTICMOTOR SHAFT STEELHARDWARE STAINLESS STEEL“O” RINGS -

MECHANICAL SEALSStandard: -

UPPER BEARING BALL BEARINGLOWER BEARING BALL BEARING

Page 167: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

SPECIFICATION DATAHYDROMATIC®

A+SUBMERSIBLE SUMP/EFFLUENT

1.01 GENERAL Contractor shall furnish all labor, materials, equipment and incidentals required to provide __________

(Qty.) submersible centrifugal sewage grinder pump(s) as specified herein. The pump models covered in this specification are the V-A1, W/D-A1, VS25/33, SW25/33, and SD25/33. The pump furnished for this application shall be MODEL ____________ as manufactured by Hydromatic Pumps.

2.01 DESIGN CONDITIONS Each pump shall be rated ________ H.P., ________ volts, ________ phase, ________ hertz and operate

at ________ RPM.

3.01 OPERATING CONDITIONS The pump shall deliver ________ U.S. GPM/LPS at feet/meters TDK, and handle a ________ inch solid.

The curve submitted for approval shall state, in addition to head and capacity performance, solid handling capability, amp rating, and design impeller diameter.

4.01 CONSTRUCTION Each pump shall be of the sealed submersible type, incorporating features normally found in pumps

furnished for the heavy duty industrial or municipal markets. These features include:

1. The pump volute, motor, and seal housing shall be high quality gray cast iron, ASTM A-48, Class 30.

2. The pump shall feature a multiple strainer inlet that prevents clogging from foreign objects and provides optimum operation and reduced maintenance.

3. All external mating parts shall be machined and Buna N, O-Ring sealed. 4. All fasteners exposed to the pumped liquid shall be 300 series stainless steel. 5. All power cords shall be water resistant UL or CSA approved, with double insulation, and sized

as a function of Amp. draw.

5.01 MOTOR AND SHAFT The stator, rotor and bearings shall be mounted in a sealed submersible type housing. Single phase

motors shall be Shaded Pole, with automatic reset thermal overload protection. Full Load and Locked Rotor Amps as well as Run winding resistance shall be tabulated for each pump.

6.01 BEARINGS, SHAFT AND MECHANICAL SEAL An upper radial and lower thrust bearing shall be required. The upper bearing shall; be, Cast iron (V-A1

and W/D-A1) or Bronze (VS, SD and SW) while the lower bearing is heavy duty single row ball. They are both permanently, continuously lubricated and cooled by the dielectric oil, which fills the motor housing. The motor shaft shall be corrosion resistant steel and sealed from the pumped liquid with a carbon ceramic mechanical seal.

MODELS: V-A1, W/D-A1, VS25/33, SW25/33 and SD25/33

Wholesale Products Page: 6820-5Dated: January 2001

Page 168: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

USA CANADA293 Wright Street, DelAvAN, Wi 53115 WWW.hYDrOMAtiC.COM 269 trilliUM Drive, KitCheNer, ONtAriO, CANADA N2g 4W5Ph: 888-957-8677 OrDerS FAX: 800-426-9446 Ph: 519-896-2163 OrDerS FAX: 519-896-6337

Because we are continuously improving our products and services, Pentair reserves the right to change specifications without prior notice.

© 2013 Pentair ltd. All rights reserved. W-01-260 (03/25/13)

SPECIFICATION DATAHYDROMATIC®

A+SUBMERSIBLE SUMP/EFFLUENT

7.01 IMPELLER The Impeller shall be a thermoplastic, eight vane, non-clog design with three pump out vanes on the back

side. These vanes wash out grit and stringy material that will damage the shaft and mechanical seal.

8.01 AUTOMATIC CONTROL All pumps should be capable of automatic operation.

9.01 PRESSURE SWITCH The D-A1, SD25, and SD33 Single Phase pumps are furnished with a pressure diaphragm switch that is

UL listed for water and sewage and GSA certified. The diaphragm switch cord shall be fitted with a piggy-back plug that allows the pump to be operated manually without removal from the sump.

10.01 FLOAT SWITCH The W-A1, SW25, and SW33 Single Phase pumps are supplied with a tilt-sensitive wide-angle float switch

which is sealed in a non-corrosive PVC enclosure. The switch is UL listed for water and sewage and QSA certified. The float switch shall also be fitted with a piggy-back plug that allows the pump to be operated manually without removal from the sump.

11.01 VERTICAL MECHANICAL SWITCH The V-A1, VS25 and VS33 single phase pumps are furnished with a magnetic mechanical switch which is

sealed in a non-corrosive PVC enclosure. The switch will be activated by a PVC float sliding up and down a non-corrosive rod. The mechanical switch cord shall also be fitted with a piggy-back plug that allows the pump to be operated manually without removal from the sump.

12.01 PAINTING All cast iron parts shall be painted before assembly with a water reducible alkyd air dried enamel.

The paint shall be applied in one coat with a minimum thickness of 3 to 4 mils.

13.01 TESTING All pumps shall be individually tested to include the following:

1. The pump and power cord shall be visually inspected for imperfections, cuts or nicks. 2. The pump shall have a ground continuity check and the motor chamber shall be Hi-potted

to test for moisture content and/or insulation defects. 3. The motor and volute housing shall be pressurized and a 10 second air leak decay test run. 4. A specific amount of oil is now added. The pump is run in a fully automated, sequenced, control

console, which monitors voltage, current and watts visually and electronically. The tester listens for any noise or malfunction.

Wholesale Products Page: 6820-6Dated: January 2001

Page 169: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

Wholesale Products Page: 6780-1Dated: January 2001

RPM: 3450 Discharge: 1½” Solids: ¼”

1/4 HP

CAPACITY GALLONS PER MINUTE

TOTA

L HE

AD IN

FEE

T

0 5 10 15 20 25 30 35

2422201816141210

86420

Conditions of Service:

GPM:______ TDH:______

The curves reflect maximum performance characteristics without exceeding full load (Nameplate) horsepower. All pumps have a service factor of 1.2. Operation is recommended in the bounded area with operational point within the curve limit. Performance curves are based on actual tests with clear water at 70° F. and 1280 feet site elevation.

HYDROMATIC®

BV-A1/B-A1SUBMERSIBLE SUMP/EFFLUENT

PERFORMANCE DATA

Page 170: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

All dimensions in inches. Metric for international use. Component dimensions may vary ± 1/8 inch. Dimensional data not for construction purpose unless certified. Dimensions and weights are approximate. On/Off level adjustable. We reserve the right to make revisions to our product (s) and the product (s) specifications without notice.

3-5/16"(85)

4-1/2"(114)

3-1/8"(79)

1-1/2"NPT

8-1/4"(209)

3-1/8"(79)

9-3/8"(238)

9-5/8"(244)

7"(178)

2-1/2"(63)

Turn On

Turn Off

9-1/2"(241)

3-5/16"(85)

4-1/2"(114)

3-1/8"(79)

1-1/2"NPT

8-5/8"(219)

10-5/16"(268)

4-1/2"(114)

1-1/2"(38)

Turn On

Turn Off

B-A1 BV-A1

HYDROMATIC®

BV-A1/B-A1SUBMERSIBLE SUMP/EFFLUENT

DIMENSIONAL DATA

Wholesale Products Page: 6780-2Dated: January 2001

Page 171: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

ELECTRICAL DATAHYDROMATIC®

BV-A1/B-A1SUBMERSIBLE SUMP/EFFLUENT

R.P.M. 3450MOTOR TYPE P.S.C. OIL FILLED MOTORGENERAL INSULATION CLASS AMAXIMUM STATOR TEMPERATURE 105°F

HP VOLTAGE PHASE NEC CODE SERVICE FACTOR FULL LOAD AMPS1/4 115 1 - 1 6.5

MODEL: BA-1/BV-A1

Wholesale Products Page: 6780-3Dated: January 2001

Page 172: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

TECHNICAL DATAHYDROMATIC®

BV-A1/B-A1SUBMERSIBLE SUMP/EFFLUENTMODEL: BA-1/BV-A1

Wholesale Products Page: 6780-4Dated: January 2001

Physical DataDISCHARGE SIZE 1 ½” NPTSOLIDS SIZE ¼”IMPELLER TYPE -CABLE LENGTH 10’ STANDARDPAINT -

TemperatureMAXIMUM LIQUID 140°FMAXIMUM STATOR -OIL FLASH POINT -

Technical DataPOWER CORD TYPE SJTW

MAT

ERIA

LS O

F CO

NST

RUCT

ION MOTOR HOUSING CAST IRON

CASING THERMOPLASTICIMPELLER THERMOPLASTICMOTOR SHAFT STEELHARDWARE STAINLESS STEEL“O” RINGS -

MECHANICAL SEALSStandard: -

UPPER BEARING BALL BEARINGLOWER BEARING BALL BEARING

Page 173: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

SPECIFICATION DATAHYDROMATIC®

BV-A1/B-A1SUBMERSIBLE SUMP/EFFLUENT

1.01 GENERAL Contractor shall furnish all labor, materials, equipment and incidentals required to provide __________

(Qty.) submersible centrifugal sump pump(s) as specified herein. The pump models covered in this specification are the BV-A1 and B-A1. The pump furnished for this application shall be MODEL ____________ as manufactured by Hydromatic Pumps.

2.01 DESIGN CONDITIONS Each pump shall be rated ________ H.P., ________ volts, ________ phase, ________ hertz and operate at

________ RPM.

3.01 OPERATING CONDITIONS The pump shall deliver ________ U.S. GPM/LPS at feet/meters TDK, and handle a ________ inch solid.

The curve submitted for approval shall state, in addition to head and capacity performance, solid handling capability, amp rating, and design impeller diameter.

4.01 CONSTRUCTION Each pump shall be of the sealed submersible type, incorporating features normally found in pumps

furnished for the residential market. These features include:

1. The pump shall be constructed of high grade thermoplastic and high quality gray cast iron, ASTM A-48, Class 30.

2. The pump shall feature a multiple strainer inlet that prevents clogging from foreign objects and provides optimum operation and reduced maintenance.

3. All external mating parts shall be machined and Buna N, O-Ring sealed. 4. All fasteners exposed to the pumped liquid shall be stainless steel. 5. All power cords shall be water resistant UL or CSA approved, with double insulation, and sized

as a function of Amp. draw.

5.01 MOTOR AND SHAFT The stator, rotor and bearings shall be mounted in a sealed submersible type housing. Single phase

motors shall be Shaded Pole, with automatic reset thermal overload protection. Full Load and Locked Rotor Amps as well as Run winding resistance shall be tabulated for each pump.

6.01 BEARINGS, SHAFT AND MECHANICAL SEAL An upper radial and lower thrust bearing shall be required. These shall be single row ball bearings which

are permanently, continuously lubricated and cooled by the dielectric oil, which fills the motor housing. The motor shaft shall be corrosion resistant steel and sealed from the pumped liquid with a carbon ceramic mechanical seal.

MODELS: BV-A1 and B-A1

Wholesale Products Page: 6780-5Dated: January 2001

Page 174: HYDROMATIC® S3S/SB3S & S4S/SB4S SINGLE SEAL SEWAGE ...

USA CANADA293 Wright Street, DelAVAN, Wi 53115 WWW.hYDrOMAtiC.COM 269 trilliUM DriVe, KitCheNer, ONtAriO, CANADA N2g 4W5Ph: 888-957-8677 OrDerS FAX: 800-426-9446 Ph: 519-896-2163 OrDerS FAX: 519-896-6337

Because we are continuously improving our products and services, Pentair reserves the right to change specifications without prior notice.

© 2013 Pentair ltd. All rights reserved. W-01-260 (03/25/13)

SPECIFICATION DATAHYDROMATIC®

BV-A1/B-A1SUBMERSIBLE SUMP/EFFLUENT

7.01 IMPELLER The Impeller shall be a thermoplastic, eight vane, non-clog design with three pump out vanes on the back

side. These vanes wash out grit and stringy material that will damage the shaft and mechanical seal.

8.01 AUTOMATIC CONTROL All pumps should be capable of automatic operation.

9.01 FLOAT SWITCH The B-A1 Single Phase pump is supplied with a tilt-sensitive wide-angle float switch which is sealed in a

non-corrosive PVC enclosure. The switch is UL listed for water and sewage and QSA certified.

10.01 VERTICAL MECHANICAL SWITCH The BV-A1 Single Phase pump is furnished with a magnetic mechanical switch which is sealed in a non-

corrosive PVC enclosure. The switch will be activated by a PVC float sliding up and down a non-corrosive rod.

11.01 PAINTING All cast iron parts shall be painted before assembly with a water reducible alkyd air dried enamel.

The paint shall be applied in one coat with a minimum thickness of 3 to 4 mils.

12.01 TESTING All pumps shall be individually tested to include the following:

1. The pump and power cord shall be visually inspected for imperfections, cuts or nicks. 2. The pump shall have a ground continuity check and the motor chamber shall be Hi-potted

to test for moisture content and/or insulation defects. 3. The motor and volute housing shall be pressurized and a 10 second air leak decay test run. 4. A specific amount of oil is now added. The pump is run in a fully automated, sequenced, control

console, which monitors voltage, current and watts visually and electronically. The tester listens for any noise or malfunction.

Wholesale Products Page: 6780-6Dated: January 2001


Recommended