LA Sanitation & Environment Hyperion Water Reclamation Plant JULY 11, 2021 INCIDENT REPORT Presentation to the honorable Council President Nury Martinez and the Los Angeles City Council www.lacitysan.org/hyperion2021recovery Tuesday, August 10, 2021
Transcript
Page 1: Hyperion Water Reclamation Plant LA Sanitation & Environment

LA Sanitation & EnvironmentHyperion Water Reclamation Plant

JULY 11, 2021 INCIDENT REPORT

Presentation to the honorable Council President Nury Martinez and the Los Angeles City Council www.lacitysan.org/hyperion2021recovery

Tuesday, August 10, 2021

Page 2: Hyperion Water Reclamation Plant LA Sanitation & Environment

HYPERION WATER RECLAMATION PLANT LAYOUT

HEADWORKS BARSCREENS

PR

IMA

RY

TAN

KS

SECONDARY CLARIFIERS

Reclaimed Water to WBMWD

1-Mile O

utfall

5-Mile O

utfall

CSD #1 CSD #2CSD #3

GRIT BARN

CSD #4

Secondary Effluent Channel Screens

EPP

Emergency Storage

AWPF

28/10/2021 | Slide 2

Page 3: Hyperion Water Reclamation Plant LA Sanitation & Environment

• 12:00pm - Headworks bar screens begin experiencing problems - 4 were in service.

• 3:00pm - Untreated wastewater overflowed out of Headworks onto plant roadways

• 7:00pm - Untreated wastewater overflowed into 1-mile outfall

• 7:59pm - Plant notified CA Office of Emergency Services (OES)

• 8:11pm - OES notified LA County Dept. of Public Health

• 8:18pm - Plant notified National Response Center

• 9:30pm - LA County Dept. of Public Health arrived at Hyperion

8/10/2021 | Slide 3

Clogged bar screens

Headworks flooding around bar screens

OVERVIEWJuly 11, 2021

Plant roads flooded

Headworks flooded

Flooding outside offices

Debris Close Up

Page 4: Hyperion Water Reclamation Plant LA Sanitation & Environment

• 4:30am - Opened bypass gate to stop overflow of untreated wastewater out of Headworks building

• 8:41am - Overflow of untreated wastewater into 1-mile outfall stopped and recovery efforts began

8/10/2021 | Slide 4

OVERVIEWJuly 12, 2021

Headworks bypass gate, side view

Headworks bypass gate hooked to crane

Overhead crane to lift bypass gate

Headworks bypass

Headworks bypass gate

Page 5: Hyperion Water Reclamation Plant LA Sanitation & Environment

Headworks Surface Structure Decks (Barscreens)

Effluent Pumping Plant (EPP)

Primary Tanks

Clarifiers

Truck Loading Facility (TLF)

Digester Batteries

C-Street

E-Street

B-Street

Secondary Reactors

Bottom Floor Parking Structure

TWAS Pump Station

RAS Pump Rooms

Emergency Storage Tank

TSF

AWPF

Grit Basin Pumps

Maintenance Shop

C8 Switchgear

C7 Polymer Pumps

DMA Annex

DII Feed Pumps

PS Pumps

5

IMPACT TO HWRPBelow Ground Flooding

8/10/2021 | Slide 5

Page 6: Hyperion Water Reclamation Plant LA Sanitation & Environment

IMPACT TO HWRPPlant was flooded with untreated wastewater: damaging equipment and threatening the safety of staff; offices and elevators compromised

8/10/2021 | Slide 6

Page 7: Hyperion Water Reclamation Plant LA Sanitation & Environment

IMPACT TO HWRP Advanced Water Purification Facility construction site flooded

8/10/2021 | Slide 7

Site one week before flooding

Site after flooding

Site after flooding

Page 8: Hyperion Water Reclamation Plant LA Sanitation & Environment

BAR SCREENS PRIMARY TANKS

SECONDARY REACTORS

EFFLUENT PUMPING PLANT

TRUCK LOADING FACILITY

DIGESTERS SECONDARY CLARIFIERS

SECONDARY TREATED WATER TO 5-MILE OUTFALL

DEWATERING CENTRIFUGE

BIOSOLIDS TO GREEN ACRES

WASTCENTRIFUGE

RAS PUMPS

PRIMARY SLUDGE PUMPS

POLYMER SYSTEM

RAW WASTEWATER

8/10/2021 | Slide 8

HYPERION WATER RECLAMATION PLANT PROCESS RECOVERY EFFORTS

Page 9: Hyperion Water Reclamation Plant LA Sanitation & Environment

HWRP PROCESS RECOVERY EFFORTS

8/10/2021 | Slide 9

Demonstrating the water level underground

Removing water from underground galleries Pump bypasses

Pump bypasses RAS motors

Page 10: Hyperion Water Reclamation Plant LA Sanitation & Environment

8/10/2021 | Slide 10

Click here to download the full permit

REGULATORY OVERSIGHTNPDES Permit

Page 11: Hyperion Water Reclamation Plant LA Sanitation & Environment

HYPERION WATER RECLAMATION PLANT PROCESS RECOVERY EFFORTSTSS - total suspended solids / BOD - biological oxygen demand

8/10/2021 | Slide 11

Page 12: Hyperion Water Reclamation Plant LA Sanitation & Environment

● July 11 flow monitoring data from the five major outfall sewers into Hyperion reviewed for anomalies in flow

● The data verifies major flow deviation in outfall sewers correlating w reports of significant debris at Hyperion

INITIAL INVESTIGATION OF CAUSE

8/10/2021 | Slide 12

Page 13: Hyperion Water Reclamation Plant LA Sanitation & Environment

INITIAL INVESTIGATION OF CAUSENorth Outfall Sewer Flow Gauge (typical of all five outfall sewers)

8/10/2021 | Slide 13

• Analyzed flow data on all 200 flow monitoring sites for:○ sudden changes in flow velocity & depth of flow○ any backflow, surcharge, hydraulic abnormality

• Performing visual inspection of 900 maintenance holes w pole cameras looking for:○ access by outsiders; debris residuals; abnormal flow conditions

Page 14: Hyperion Water Reclamation Plant LA Sanitation & Environment

INFORMATION SHARINGHyperion 2021 Recovery web page

• All LASAN lab results• Correspondence with regulatory agencies,

including violation notices• Critical process equipment status

8/10/2021 | Slide 14

Plant Visits

• Invitations extended to media, elected officials, and NGOs to visit Hyperion• Facility and equipment photos shared

Media and Regulatory Agencies

• Full cooperation including inspections, investigations, and sharing of data• Sending frequent statements with updates

Modernized Communications

• Enhanced relationships with stakeholders and neighboring cities• More active communications with LA County

Page 15: Hyperion Water Reclamation Plant LA Sanitation & Environment

NEXT STEPSSeveral third party assessments undertaken • Plant protocols and procedures • Conveyance system• Communications: education campaign, notification

procedures, enhanced collaboration

Facility and Process Improvements• Implement procedures to open bypass gate at

pre-specified water levels• Seal and waterproof doors to prevent damage to

equipment inside plant facilities (46-50 doors)• Provide multiple connections to reroute flows from the

plant storm drain system and minimize overflow of wastewater into Santa Monica Bay in the event of a spill

• Work with AQMD to evaluate and improve air quality monitoring

• Anticipate normal operations resuming end of August

Findings and recommendations in 90 days

8/10/2021 | Slide 15

Page 16: Hyperion Water Reclamation Plant LA Sanitation & Environment

For more information about Hyperion Water Reclamation Plant, this incident, and next steps, please visit our website:

www.lacitysan.org/hyperion2021recovery

or call our 24-hour Customer Care Center at 1-800-773-2489