+ All Categories
Home > Documents > IB-NT-1.0 - Manual

IB-NT-1.0 - Manual

Date post: 01-Jun-2018
Category:
Upload: diego-costa
View: 227 times
Download: 1 times
Share this document with a friend

of 34

Transcript
  • 8/9/2019 IB-NT-1.0 - Manual

    1/34

    InternetBridge-NTInternet module

    SW version 1.0, December 2011

    REFERENCE GUIDE

    Copyright © 2011 ComAp s.r.o.

    ComAp, spol. s r.o .Kundratka 17, 180 00 Praha 8, Czech RepublicTel: +420 246 012 111, Fax: +420 266 316 647

    E-mail: [email protected] , www.comap.cz

    mailto:[email protected]://www.comap.cz/http://www.comap.cz/mailto:[email protected]

  • 8/9/2019 IB-NT-1.0 - Manual

    2/34

    IB-NT, SW version 1.0, ©ComAp – December 2011 Page 2 of 34IB-NT-1.0 Reference Guide.pdf

    Table of contents

    Ta ble of contents ..................................................................................................................................... 2 1 Document information..................................................................................................................... 3

    1.1 Clarification of notation........................................................................................................... 3 2 General guidelines .......................................................................................................................... 4

    2.1 What is InternetBridge-NT?.................................................................................................... 4 2.2 Features ................................................................................................................................. 4

    3 Installation....................................................................................................................................... 5 3.1 What is in the package?......................................................................................................... 5 3.2 Dimensions and terminals...................................................................................................... 5 3.3 Mounting................................................................................................................................. 6 3.4 Led indicators ......................................................................................................................... 7 3.5 WAN connection .................................................................................................................... 8

    3.5.1 Cellular mode..................................................................................................................... 8 3.5.2 Ethernet mode ................................................................................................................... 8

    3.6 Controller connection ............................................................................................................. 9 3.6.1 RS485 ................................................................................................................................ 9 3.6.2 CAN ................................................................................................................................. 11 3.6.3 RS232 .............................................................................................................................. 11

    4 Module setup ................................................................................................................................ 12 4.1 General setup....................................................................................................................... 15 4.2 Ethernet connection ............................................................................................................. 15 4.3 Cellular connection............................................................................................................... 16 4.4 E-mail and SMS ................................................................................................................... 18 4.5 Other settings ....................................................................................................................... 18 4.6 Firmware update .................................................................................................................. 20 4.7 Customizing the logo............................................................................................................ 20 4.8 Save and load the settings................................................................................................... 20

    5 Functions ...................................................................................................................................... 21 5.1 Direct Internet connection .................................................................................................... 21 5.2 AirGate connection............................................................................................................... 22 5.3 Web interface ....................................................................................................................... 23 5.4 Active e-mails and SMS....................................................................................................... 29 5.5 MODBUS/TCP ..................................................................................................................... 30 5.6 SNMP................................................................................................................................... 30

    6 Troubleshooting ............................................................................................................................ 31 7 Technical specifications................................................................................................................ 34

    7.1 Physical dimensions............................................................................................................. 34 7.2 Power supply........................................................................................................................ 34 7.3 Operating conditions ............................................................................................................ 34 7.4 WAN interface ...................................................................................................................... 34

  • 8/9/2019 IB-NT-1.0 - Manual

    3/34

    IB-NT, SW version 1.0, ©ComAp – December 2011 Page 3 of 34IB-NT-1.0 Reference Guide.pdf

    1 Document information

    INTERNET BRIDGE -NT - REFERENCE GUIDE WRITTEN BY : J AN TOMANDL ©2011 COM AP LTD.KUNDRATKA 17, P RAHA 8, CZECH REPUBLIC P HONE : +420246012111, FAX : +420266316647WEB : HTTP ://WWW .COMAP .CZ , E -MAIL: INFO @ COMAP .CZ

    DOCUMENT HISTORY

    REVISION NUMBER R ELATED SW . VERSION D ATE

    1 1.0 5.12.2011

    1.1 Clarification of notationNOTE : This type of paragraph calls readers attention to a notice or related theme.

    C AUTION ! This type of paragraph highlights a procedure, adjustment etc., which can cause a damage orunproper function of the equipment if not performed correctly and may not be clear at first sight.

    W ARNING ! This type of paragraph indicates things, procedures, adjustments etc. which need high level ofattention, otherwise can cause personal injury or death.

    http://www.comap.cz/http://www.comap.cz/http://www.comap.cz/http://www.comap.cz/http://www.comap.cz/http://www.comap.cz/http://www.comap.cz/http://www.comap.cz/http://www.comap.cz/http://www.comap.cz/http://www.comap.cz/http://www.comap.cz/http://www.comap.cz/http://www.comap.cz/

  • 8/9/2019 IB-NT-1.0 - Manual

    4/34

    IB-NT, SW version 1.0, ©ComAp – December 2011 Page 4 of 34IB-NT-1.0 Reference Guide.pdf

    2 General guidelines

    2.1 What is InternetBridge-NT?InternetBridge-NT is a communication module that allows connection of a single controller as well aswhole site to the Internet or Local area network. The connection to the Internet can be via built-incellular modem supporting 2G and 3G networks or Ethernet cable.

    The module can be used for controllers from following product lines: IG-NT, IS-NT and IC-NT.

    NOTE : For proper operation it is necessary to update the controller firmware to a version which supports IB-NT. For IG-NT and IS-NT standard branch the first version supporting IB-NT is 2.6.

    2.2 Features

    • Direct ethernet connection to ComAp PC programs• AirGate® support• SMTP protocol for sending of active emails from the controller• HTTP protocol for web-based monitoring and adjustment • MODBUS/TCP server • SNMP protocol

  • 8/9/2019 IB-NT-1.0 - Manual

    5/34

    IB-NT, SW version 1.0, ©ComAp – December 2011 Page 5 of 34IB-NT-1.0 Reference Guide.pdf

    3 Installation

    3.1 What is in the package?

    The package contains:

    • IB-NT module• Cellular antenna with magnetic holder• Terminal blocks

    The package does not contain :

    • Ethernet UTP cable• USB cable• SIM card

    3.2 Dimensions and terminals

    FRONT VIEW OF THE MODULE

  • 8/9/2019 IB-NT-1.0 - Manual

    6/34

    IB-NT, SW version 1.0, ©ComAp – December 2011 Page 6 of 34IB-NT-1.0 Reference Guide.pdf

    3.3 Mounting

    The device is designed to be mounted into a switchboard on a DIN rail. The required space is150x200mm as there are antenna connectors from the right side

    .

    MOUNTING

  • 8/9/2019 IB-NT-1.0 - Manual

    7/34

    IB-NT, SW version 1.0, ©ComAp – December 2011 Page 7 of 34IB-NT-1.0 Reference Guide.pdf

    3.4 Led indicators

    The LED indicators are located on the front panel. Led diodes that are located at the communicationports indicate communication activity at the respective port.

    Yellow: the module is attached into 2G network (GPRS/EDGE)

    Red: the module is attached to 3G network (UMTS)

    CELLULAR

    Blinking: the module registered cellular network but not attached to the APN.

    D ATA Blinks once when a data packet is sent to the WAN interface.

    A IRG ATE The module is connected to the AirGate®.

    CONTROLLERS At least one controller is connected to the module via configured interface.

    ERROR There is a problem that causes the module is not working properly.RJ45 GREEN Led is on if the Ethernet interface is in 100Mbit mode and is off in 10Mbit mode.

    RJ45 ORANGE Blinks when any data are sent or received at the Ethernet port.

  • 8/9/2019 IB-NT-1.0 - Manual

    8/34

    IB-NT, SW version 1.0, ©ComAp – December 2011 Page 8 of 34IB-NT-1.0 Reference Guide.pdf

    3.5 WAN connection

    WAN (Internet) connection type is to be adjusted via IB-NT Config in the SETTINGS->G ENERAL menu.

    3.5.1 Cellu lar mode

    See the chapter Cellular connection setup for details about settings related to the cellular mode.

    3.5.1.1 SIM installationInstall the SIM card into the holder (1). Push the button (2) with a blunt tool to release the holder, ejectthe holder by fingers from the holder housing, place the SIM card into the holder as described on thesticker (metal plates upwards) and insert the holder with the SIM card carefully back into the housing.

    3.5.1.2 AntennaInsert the antenna SMA male connector firmly into the connector labelled "Cellular" and screw the nutby hand to fix the connector parts together. Slightly tighten the nut using a flat wrench if necessary.

    NOTE : The antenna cable must not be interrupted by any terminals. If the cable from the supplied antenna istoo short buy an antenna with longer cable instead of prolonging it. Prolonged antenna cables mayresult in problems with signal strenght or loosing the signal at all.

    3.5.2 Ethernet modeSee the chapter Ethernet connection setup for details about settings related to the Ethernetconnection mode.

  • 8/9/2019 IB-NT-1.0 - Manual

    9/34

    IB-NT, SW version 1.0, ©ComAp – December 2011 Page 9 of 34IB-NT-1.0 Reference Guide.pdf

    3.6 Controller connection

    Controller connection type is to be adjusted via IB-NT Config in the SETTINGS->G ENERAL menu .

    NOTE : If multiple controllers are connected to the IB-NT each controller must have different controlleraddress .

    3.6.1 RS485

    Connect all controllers together by a twisted pair cable as indicated at the picture below. Use straightlinear wiring, do not create any nodes. Apply terminating resistors at boh ends of the RS485 cable.The IB-NT module contains integrated terminating resistor as well as balancing resistors, which areactivated by jumpers.

    NOTE : The port RS232(1) at the controllers must be switched to DIRECT mode (Comms settings ->RS232(1) mode = DIRECT) and must be redirected to RS485 terminals (Comms settings -> RS485(1)conv. = ENABLED).

    C AUTION ! The RS485(2) port at IG-NTC and IS-NT-BB does not fully support IB-NT . Some functions likeactive e-mails or sms might not work if this port is used. The RS485(2) port at IG-NTC-BB and IS-NTC-BB supports IB-NT in the full range of functions. Please use CAN connection instead.

    C AUTION ! The RS485(2) port at IG-NTC-BB and IS-NTC-BB supports fully IB-NT only if the IB-COM module,which provides the RS485(2) port, has firmware version higher than 1.0. Please refer to the ComApweb site for more information about IB-COM firmware update.

  • 8/9/2019 IB-NT-1.0 - Manual

    10/34

    IB-NT, SW version 1.0, ©ComAp – December 2011 Page 10 of 34IB-NT-1.0 Reference Guide.pdf

    WIRING OF RS485

  • 8/9/2019 IB-NT-1.0 - Manual

    11/34

    IB-NT, SW version 1.0, ©ComAp – December 2011 Page 11 of 34IB-NT-1.0 Reference Guide.pdf

    3.6.2 CAN

    Connect all controllers together by a twisted pair cable as indicated at the picture below. Use straightlinear wiring, do not create any nodes. Apply terminating resistors at boh ends of the CAN bus. TheIB-NT module contains integrated terminating resistor, which can be activated by jumper.

    NOTE : All controllers must be adjusted to the same CAN bus mode, i.e. either 8C or 32C (Comms settings ->CAN bus mode). Use 8C only if the bus length is longer than cca 200m.

    WIRING OF CAN

    3.6.3 RS232

    One single controller can be connected to the IB-NT module via RS232 interface. Use 3-wire cross-wired serial cable for this purpose. The respective controller port must be switched to DIRECT mode(Comms settings -> RS232(n) mode = DIRECT).

  • 8/9/2019 IB-NT-1.0 - Manual

    12/34

    IB-NT, SW version 1.0, ©ComAp – December 2011 Page 12 of 34IB-NT-1.0 Reference Guide.pdf

    4 Module setup

    For setup of the InternetBridge-NT module the PC program IB-NT Config is used. The program isinstalled by the ComAp PC Suite installation package and is located in the program group "ComAp PCSuite", submenu "Tools". Please refer to the ComAp web pages to get the latest version of thepackage. The file Installation packages content map will help you find the proper package.

    NOTE : The program requires Microsoft .NET 3.5 SP1 framework . If you do not have already installed theframework in your computer the installer will automatically launch installation from the Microsoft webpages. Broadband int ernet connection is recommended for the installation. The framework and its'service pack can be also installed anytime manually from the Microsoft web.

    The IB-NT Config can be connected using following connection methods:

    • USB - used for initial setting. The connection uses virual COM port, so the device must be

    connected first to your computer and then the virtual COM port is created. After that you canstart the IB-NT Config and select the proper COM port. The virtual COM port driver is installedtogether with the IB-NT Config.

    • Ethernet - can be used for later changes of the settings remotely if the module uses static IPaddress at the WAN interface and AirGate is switched off.

    NOTE :

    If you change the IP settings or switch AirGate on you will not be able to connect again usingthe same connection method and/or IP address. Make sure you know the AirGate ID beforeswitching on the AirGate remotely.

    • Ai rGate - can be used for later changes of the settings remotely using AirGate connection.

    http://www.comap.cz/support/downloads/_Installation%20Packages%20Content%20Map.xlshttp://www.comap.cz/support/downloads/_Installation%20Packages%20Content%20Map.xls

  • 8/9/2019 IB-NT-1.0 - Manual

    13/34

  • 8/9/2019 IB-NT-1.0 - Manual

    14/34

    IB-NT, SW version 1.0, ©ComAp – December 2011 Page 14 of 34IB-NT-1.0 Reference Guide.pdf

    Factory default password is "0". It is highly recommended to change the password. Go to menuSYSTEM -> P ASSWORD to change the password. Lost password? Write down the module serialnumber and password decode number that are displayed in the warning message and contact yourdistributor.

    After you made changes in settings of the module the changes must be confirmed and the modulemust be restarted. Use the menu SETTINGS->W RITE AND RESET .

  • 8/9/2019 IB-NT-1.0 - Manual

    15/34

    IB-NT, SW version 1.0, ©ComAp – December 2011 Page 15 of 34IB-NT-1.0 Reference Guide.pdf

    4.1 General setup

    The menu SETTINGS -> G ENERAL contains essential settings of the module.

    1. WAN CONNECTON MODE selects the communication interface which the module uses foracessing the external network (Internet). Select C ELLULAR if you want to use the built-incellular modem or select E THERNET if you want to use the ethernet socket.

    2. A IRG ATE ENABLE switches AirGate protocol on and off. If AirGate is on then use "AirGate"connection type in ComAp PC tools, if is is switched off use "Direct Internet".

    3. A IRG ATE ADDRESS specifies the AirGate address. Use "airgate.comap.cz".4. C ONNTROLLERS CONNECTION TYPE selects the communication inferface which is used for

    connection of the controllers.

    NOTE :

    If CAN bus is used and there are other communication devices/bridges such as other IB-NT, I-LB, IG-IB or InteliVision-8(CAN) the CAN address collision must be avoided, e.g. each device

    mus uset different CAN address.

    EXAMPLE :

    If you wand to use two IB-NT with SIM card from two different operators at one site andconnect them via CAN bus then configure one IB-NT to CAN, ADDR #1 and the other to CAN,

    ADDR #2.

    GENERAL SETTINGS

    4.2 Ethernet connection

    The menu SETTINGS->E THERNET CONNECTION contains settings related to the ethernet WANinterface . Values in this menu are not valid if cellular modem is used as WAN interface. Forcurrently used IP address and other IP related settings (independently on type of the WAN interfaceused) go to the menu STATUS.

    1. IP A

    DDRESSM

    ODE selects whether you want the module to work with fixed manually adjustedsettings or you want the module to get all settings automatically from a DHCP server.

  • 8/9/2019 IB-NT-1.0 - Manual

    16/34

    IB-NT, SW version 1.0, ©ComAp – December 2011 Page 16 of 34IB-NT-1.0 Reference Guide.pdf

    NOTE :

    For web access the fixed IP address mode is recommended.

    C AUTION !

    If you want to use static IP address you should consult this with the administrator of thenetwork, to which you want to connect. He must reserve the address for the bridge.

    2. IP ADDRESS adjusts the IP address of the module in manual mode or displays the IP addressassigned by DHCP server in automatic mode.

    3. N ETWORK M ASK adjusts the network mask in manual mode or displays the network maskobtained from DHCP server in automatic mode.

    4. G ATEWAY IP adjusts the gateway address in manual mode or displays the gateway addressassigned by DHCP server in automatic mode.

    5. DNS S ERVER IP adjusts the DNS server address in manual mode or displays the DNS serveraddress assigned by DHCP server in automatic mode.

    INTERNET PROTOCOL SETTINGS

    4.3 Cellular connection

    The menu SETTINGS->C ELLULAR CONNECTION contains settings related to the built-in cellular modem.

    1. N ETWORK S ELECTION is used to select manually the cellular operator or switch the modem toautomatic selection. It is recommended to use automatic mode except e.g. if you want to avoidroaming or if you want to select manually the network type (see setpoint below).

    2. NETWORK

    TYPE

    is used to select manually the nework type (2G or 3G) or leave the selection tobe done automatically by the module according to signal strength. The 3G network is prefferedin automatic mode. If the network type is adjusted manually then also the network itself mustbe selected manually (setpoint above).

    C AUTION !

    If manual network selection is used it might happen that the InternetBridge-NT will lose theinternet connection as a result of change of the coverage of the particular network type (2G or3G). This might be caused by reconfiguration of the network, network maintenance etc.

    3. A CCESS P OINT N AME is used to enter name of the internet access point. The proper nameshould be provided by the SIM card operator, however, the name "Internet" works in mostcases.

  • 8/9/2019 IB-NT-1.0 - Manual

    17/34

    IB-NT, SW version 1.0, ©ComAp – December 2011 Page 17 of 34IB-NT-1.0 Reference Guide.pdf

    4. SIM PIN S TATUS shows the current status of the SIM PIN lock. The SIM card must beunlocked (i.e. must not require PIN after switching on) to work properly in IB-NT. If the SIM islocked, press the button U NLOCK and enter correct PIN code. This will unlock the card anddisable PIN lock for the future.

    CELLULAR SETTINGS

  • 8/9/2019 IB-NT-1.0 - Manual

    18/34

    IB-NT, SW version 1.0, ©ComAp – December 2011 Page 18 of 34IB-NT-1.0 Reference Guide.pdf

    4.4 E-mail and SMS

    The menu SETTINGS->E- MAIL AND SMS contains settings related to sending active e-mails and SMS.

    1. IB-NT E-MAIL ADDRESS specifies the address which will appear as sender's address in activee-mails. This address must be valid, i.e. the domain name must exist and the SMTP servermust be able to convert it to IP address. Otherwise most of SMTP servers will refuse sendingsuch e-mail.

    2. SMTP S ERVER specifies the IP address or domain name of the SMTP server, which is used forsending e-mails.

    NOTE :

    In most cases Internet providers have their own SMTP servers, that are available for free fortheir customers and are accessible only if the e-mailing device is connected to the Internet viathe respective provider. Using free public SMTP servers (such as gmail or yahoo) is not

    recommended as it may cause unpredictable delays in e-mail delivery.

    3. SMTP AUTHENTIFICATION selects whether the SMTP server requires login or not. If yes the twosetpoints below are used to enter username and password.

    4. SMTP USER N AME for STMP servers which require authentification (e.g. public paid servers).5. SMTP P ASSWORD for STMP servers which require authentification (e.g. public paid servers).6. T IME ZONE is used to adjust time zone where the site (bridge) is located. This is necessary for

    the recipient's e-mail client to recalculate time and date of sending to the local time of therecipient.

    E-MAIL SETTINGS

    4.5 Other settings

    1. C OM AP PROTOCOL TCP PORT adjusts the port number used for Direct Internet or AirGateconnection. The default port is 23 and should not be changed unless there is a clear reasonfor the change. A typical reason might be a need to share of one static public IP addressamong multiple devices behin a router.

    C AUTION !

    Do not change this value if AirGate is used.

  • 8/9/2019 IB-NT-1.0 - Manual

    19/34

    IB-NT, SW version 1.0, ©ComAp – December 2011 Page 19 of 34IB-NT-1.0 Reference Guide.pdf

    2. A IRG ATE UDP PORT adjusts the port number used for registration into AirGate. The default portis 6127 and must not be changed unless you are using a private AirGate which is configuredto a different UDP port.

    3. SNMP TRAP DEST . ADDRESS adjusts the IP address to which the module sends SNMP trap ifthere is a new item in AlarmList in any of attached controlers.

    4. SNMP P ROTOCOL enables/disables the SNMP Agent function.

    5. MODBUS/TCP P ROTOCOL enables/disables the MODBUS/TCP server function.6. MODBUS ACCESS CODE selects if access code is required to initiate the MODBUS/TCPsession or not.

    OTHER SETTINGS

  • 8/9/2019 IB-NT-1.0 - Manual

    20/34

    IB-NT, SW version 1.0, ©ComAp – December 2011 Page 20 of 34IB-NT-1.0 Reference Guide.pdf

    4.6 Firmware update

    To update the firmware in the IB-NT module go to menu SYSTEM->F IRMWARE UPDATE ->F IRMWARE ,press the B ROWSE button and select the firmware file (.bin). Then press the U PLOAD to program thefirmware into the IB-NT module. When the programming i s fin ished successfuly the IB-NT willreset and apply t he new firmware . If the programming is not successful the previous firmware willremain in the module and you can try the firmware update again.

    4.7 Customizing the logo

    The company logo displayed at the controller web pages is customizable. The custom logo is to beuploaded from the menu SYSTEM->F IRMWARE UPDATE ->LOGO . The name of the logo file must be"logo.gif" (i.e. must be in GIF format) and must not exceed size of 100x45 (WxH) pixels. Afterprogramming of the logo the module will reset automatically.

    NOTE

    :

    It might be necessary to reload the web page manually after changing the logo otherwise the browsermight continue using previous logo from the browser's cache.

    4.8 Save and load the settings

    Using the menu SETTINGS->S AVE TO F ILE the current settings can be saved into a XML file. This filecan be later used to restore settings e.g. after the module is replaced (menu SETTINGS->L OAD FROMF ILE.

  • 8/9/2019 IB-NT-1.0 - Manual

    21/34

    IB-NT, SW version 1.0, ©ComAp – December 2011 Page 21 of 34IB-NT-1.0 Reference Guide.pdf

    5 Functions

    5.1 Direct Internet connection

    Direct Internet connection is recommended to be used if the IB-NT module has static IP address andthere is a network path from the client computer to the bridge.

    • This connection type is recommended if the client computer is in the same LAN as the IB-NT.• If you want to access the bridge from the Internet the bridge IP address must be also static

    and public or there must be a tunnel (port forwarding) created from the public IP (local networkgateway) to the local address of IB-NT at the port specified for ComAp protocol. If there is onlyone IB-NT in the LAN then the leave the port at 23. If you have multiple modules, then youshould use different port numbers and create multiple tunnels.

    • If you want to use direct Internet connection with the cellular connection the SIM card mustprovide static and public IP address.

    DIRECT CONNECTION IN A LAN

    P ORT FORWARDING EXAMPLE

  • 8/9/2019 IB-NT-1.0 - Manual

    22/34

    IB-NT, SW version 1.0, ©ComAp – December 2011 Page 22 of 34IB-NT-1.0 Reference Guide.pdf

    5.2 AirGate connection

    AirGate connection is recommended if you want to access the IB-NT module from the Internet usingComAp protocol (i.e. ComAp tools like InteliMonitor, GenConfig or WebSupervisor) and it is notpossible to have fixed IP address or you do not want to have it.

    AirGate is to be activated in the General Settings menu. When the IB-NT connects to the AirGate firsttime it is registered into the AirGate database and gets AirGate ID, which remains then the same evenif the module is switched off and on again. This Ai rGate ID is used for all controllers connected tothe IB-NT, the controllers are distinguished from each other by their controller address.

    AirGate ID is displayed in IB-NT Config (STATUS->WAN CONNECTION ->AIRG ATE ID).

  • 8/9/2019 IB-NT-1.0 - Manual

    23/34

    IB-NT, SW version 1.0, ©ComAp – December 2011 Page 23 of 34IB-NT-1.0 Reference Guide.pdf

    5.3 Web interface

    The web interface is intended to monitor the site from a web browser. Static IP address is required forthis function as you must know the IP address to put it into the browser. Public IP address or portforwarding is required if you want to see the web pages from the Internet.

    P ORT FORWARDING EXAMPLE FOR WEB CONNECTION

    The web server is designed for basic monitoring and adjustment of the controller using a web browser.Just put the IB-NT IP address into the browser to display the overview page with the list of connected

  • 8/9/2019 IB-NT-1.0 - Manual

    24/34

    IB-NT, SW version 1.0, ©ComAp – December 2011 Page 24 of 34IB-NT-1.0 Reference Guide.pdf

    controllers. Then click to a controller to see it's web pages. You will asked for the controll er accesscode prior to entering the controller web

    NOTE : Do not open multiple web connections to the same IB-NT from the same browser window using

    browser tabs. This may cause that the data in te tabs will be mixed-up.

    IB-NT OVERVIEW WEB PAGE

    NOTE : The web server is optimized for IE6 or higher and screen resolution 1024x768 pixels.

    NOTE : The logo displayed on the top of the web page is customizable. See the chapter Customizing the logo .

    C AUTION ! Do not use the browser navigation buttons as "Back", "Forward" or "Reload". Use the links and thereload button located in the toolbar instead.

  • 8/9/2019 IB-NT-1.0 - Manual

    25/34

    IB-NT, SW version 1.0, ©ComAp – December 2011 Page 25 of 34IB-NT-1.0 Reference Guide.pdf

    5.3.1.1 ScadaClick to the SCADA link in the toolbar to display the scada page. The scada page is also the mainpage which is displayed by default if you just put the IB-Lite address into the browser.

    NOTE : The scada page layout may differ according to the firmware branch, version and application. Certainold firmware versions does not support web access at all.

  • 8/9/2019 IB-NT-1.0 - Manual

    26/34

    IB-NT, SW version 1.0, ©ComAp – December 2011 Page 26 of 34IB-NT-1.0 Reference Guide.pdf

    5.3.1.2 MeasurementClick to the MEASUREMENT link in the toolbar to display the measurement page. Then click to therequired group name in the left box to display values of the group in the right box.

    NOTE : The measurement page is automatically refreshed every 60 seconds.

  • 8/9/2019 IB-NT-1.0 - Manual

    27/34

    IB-NT, SW version 1.0, ©ComAp – December 2011 Page 27 of 34IB-NT-1.0 Reference Guide.pdf

    5.3.1.3 Setpoints

    • Click to the SETPOINTS link in the toolbar to display the setpoints page.• Click to the required group name in the left box to display setpoints of the group in the right

    box.• Click to the required setpoint name or value to change the value. If the respective setpoint is

    protected by password, which is indicated by a lock icon by the setpoint name, you have toclick on the "Controller password" icon located in the toolbar and then enter valid password.

    NOTE : The setpoint page is automatically refreshed every 60 seconds. If an another user changes a setpointfrom other terminal, the web page will not show this change immediately as e.g. InteliMonitor.

  • 8/9/2019 IB-NT-1.0 - Manual

    28/34

    IB-NT, SW version 1.0, ©ComAp – December 2011 Page 28 of 34IB-NT-1.0 Reference Guide.pdf

    5.3.1.4 History

    • Click to the HISTORY link in the toolbar to display the history page.• Use the control buttons to move within the history file.

    NOTE : The history page is automatically refreshed every 5 minutes. If a new record appears in the controller,the web page will not show it immediately as e.g. InteliMonitor.

  • 8/9/2019 IB-NT-1.0 - Manual

    29/34

    IB-NT, SW version 1.0, ©ComAp – December 2011 Page 29 of 34IB-NT-1.0 Reference Guide.pdf

    5.3.1.5 Web server adjustment

    • Click to the "Webserver settings" icon in the toolbar to display the settings page.• Select the controller language the web pages will appear in.• Select the rate of automatic refresh of the scada page.

    These settings will be also applied for the web pages of the other controllers connected to the IB-NT.

    5.4 Active e-mails and SMS

    The module can send active e-mails and sms from the connected controllers if the controller isadjusted to send it. The controller setpoint group ACT .CALLS /SMS contains all settings related to thisfunction:

    1. Selection of events (alarm types) that will issue active E-mail or SMS.2. Seletion of message type (e.g. E-mail or SMS) for each channel.3. Entering the destination address (e.g. e-mail address or phone number) for each channel.

    There are several settings in the IB-NT itself that are required for proper sending of e-mails. It is,above all, SMTP server address and IB-NT mailbox (sender's e-mail). See the chapter E-mail andSMS .

    Sending of active SMS is working only if there is a SIM card inserted in the module and Internetconnection type is set to Cellular. Active e-mails is working independently on Internet connection type.

    NOTE : SMTP protocol is fixedly set to use port 25 and can not be changed.

  • 8/9/2019 IB-NT-1.0 - Manual

    30/34

    IB-NT, SW version 1.0, ©ComAp – December 2011 Page 30 of 34IB-NT-1.0 Reference Guide.pdf

    5.5 MODBUS/TCP

    The MODBUS/TCP protocol will be implemented in the version 2.0 of the IB-NT firmware.

    5.6 SNMPThe controllers connected to the InternetBridge module can be contacted also via SNMP v.1 protocol.The bridge acts as a SNMP agent and provides controller data for the remote SNMP Manager as wellas sends TRAPs always when a new alarm appears in the controller alarm list. The SNMP Agentfunctionb is to be enabled/disabled in the setup page O THER SETTINGS , setup item SNMP P ROTOCOL .

    • Each controller has it's own MIB table which is to be created form the controller configurationusing GenConfig (menu G ENERATE CFG IMAGE -> G ENERATE SNMP MIB T ABLE ).

    C AUTION !

    As the OID tree contains serial number of the controller iis absolutely necessary that the MIBtable is created from the configuration downloaded from the respective controller. If the MIB iscreated from default archive or archive downloaded from other controller the SNMP agent willnot report error.

    • If there is a new alarm in any of connected controllers the bridge sends a TRAP to thepredefined IP address (O THER SETTINGS -> SNMP TRAP . DEST . ADDRESS . The trap hasmeaning "New alarm appeared" and as the bindings contain the alarmlist of the controllerwhere the alarm appeared as well as the controller name and serial number.

    • The MIB table is fixed, can not be configured.

  • 8/9/2019 IB-NT-1.0 - Manual

    31/34

    IB-NT, SW version 1.0, ©ComAp – December 2011 Page 31 of 34IB-NT-1.0 Reference Guide.pdf

    6 Troubleshooting

    S YMPTOM

    Where is the IB-NT Config software? How can I get it?

    C AUSE S OLUTION

    The software is located in the program group"ComAp PC Suite", submenu "Tools". It isinstalled by the ComAp PC Suite installationpackage, please refer to the ComAp web pagesto get the latest version of the package. The fileInstallation packages content map will help youfind the proper package which contains thelatest IB-NT Config version.

    Download the installation package and installthe software.

    S YMPTOM

    I can not connect to the module from IB-NT Config.

    C AUSE S OLUTION

    There is not any COM port labelled "IB-NTComAp USB Device" in the list.

    Switch on the module, connect the USB cablefrom the module to your computer and wait untilthe USB device manager installs the drivers.Then restart IB-NT Config.

    The USB device manager reports a messagethat the connected device was not recognized

    and will not work properly when I connect IB-NT to my computer.

    The device driver is not missing or not installed

    properly. Please reinstall the IB-NT Config.

    Check if there is not other IB-NT Config runningin your computer, which is connected to thesame COM port.

    The IB-NT Config displays message "OpenCOM Error" when I am trying to connect to myIB-NT.

    Close the IB-NT Config, detach and attach theUSB cable and try to connect again.

    http://www.comap.cz/support/downloads/_Installation%20Packages%20Content%20Map.xlshttp://www.comap.cz/support/downloads/_Installation%20Packages%20Content%20Map.xls

  • 8/9/2019 IB-NT-1.0 - Manual

    32/34

    IB-NT, SW version 1.0, ©ComAp – December 2011 Page 32 of 34IB-NT-1.0 Reference Guide.pdf

    S YMPTOM

    The LED "Controllers" does not come up within several seconds after switch ing the poweron.

    C AUSE S OLUTION

    The wiring is not correct or terminating resisorsare not properly installed.

    Check the wiring according to the chapterController connection . Check if there areterminating resistors at both ends, but notanywhere else . Note, that most of ComApproducts have internal terminating resistors thatare to be activated by jumper. Check if thereisn't the juper accidentaly set in some deviceconnected in the middle of the bus.

    Selected communication interface does notmatch the one which is really used.

    Use IB-NT Config to check the port selected forcontroller connection. You will find it in themenu SETTINGS->G ENERAL .

    The CAN bus mode is not adjusted in allcontrollers to the same value.

    Check in all controllers connected to the bridgeif the setpoint "CAN bus mode" is adjusted ineach controller to the same value.

    There is a controller address collision. Adjust the setpoint "Contr. address" in eachcontroller to a different value.

    S YMPTOM

    The module is swi tched to cellular mode but the LED "Cellular" does not come up witi ncouple of minut es after switching the power on.

    C AUSE S OLUTION

    SIM card is not inserted properly. Check if the SIM card is installed as describedin the chapter SIM installation .

    SIM card is locked.Use IB-NT Config to unlock the SIM card withthe PIN code as described in the chapterCellular network setup .

    SIM card does not support internet connection. Ask your SIM card provider for help. If you arein doubts, you can try using the card in an otherinternet-enabled device such as a smartphone.

    Incorrect access point name. Ask your provider for proper APN name and

    then use IB-NT Config to change it.Check if you do not manually selected anoperator or network type which is not availableat current position. The manual operatorselection should be used only to preventroaming in situations where there is signal fromhome operator as well as from roamingoperators in the same location.

    The signal of the selected network operator istoo weak or not available at all. Use the IB-NTConfig to check the signal strength (STATUS->W IRELESS ).

    Try moving the antenna to different position orusing antenna with higher gain.

  • 8/9/2019 IB-NT-1.0 - Manual

    33/34

  • 8/9/2019 IB-NT-1.0 - Manual

    34/34

    7 Technical specifications

    7.1 Physical dimensionsWidth x Height x Depth 180x130x45mm

    Weight 450g

    7.2 Power supply

    Power supply range 8-36VDC

    Average powerconsumption cca 400mA@8V; 120mA@36V

    Peak power consumption cca 1,5A@8V; 0,5A@36V

    7.3 Operating conditions

    Operating temperature -20 to +60°C (-4 to 140°F)

    Storage temperature(without SIM card; ask youroperator for SIM card

    storage/operationconditions)

    -40 to +80°C (-40 to 176°F)

    Operating humidity TODO

    7.4 WAN interface

    Ethernet socket 100Base-TX, automatic negotiation

    Cellular modem capabilities GPRS,EGPRS,UMTS,HSPA

    Cellular modem GPRSbands 850,900,1800,1900MHz

    Cellular modem UMTSbands 800,850,1700,1900,2100MHz


Recommended