ABOUT Equinix, Inc. (Nasdaq: EQIX), connects more than 4,750 companies directly to their customers and partners inside the world’s most networked data centers. Today, enterprise, cloud, networking, digital media and financial services companies leverage the Equinix interconnection platform in 33 strategic markets across the Americas, EMEA and Asia-Pacific. By connecting directly to their strategic partners and end users, customers are forming dynamic ecosystems inside Equinix. These interconnected ecosystems enable companies to optimize the performance of their content and applications and protect their vital digital assets. Equinix operates four International Business Exchange TM (IBX®) data centers and one disaster recovery center in Shanghai. Equinix Shanghai SH5 IBX+ data center occupies a 4-story dedicated building located in the Yangpu district, just north of the Lujiazui Finance and Trade Zone and the Bund. This is one of many state of the art IBX centers in key metropolitan areas throughout Asia-Pacific that offers premium colocation and Smart Hands™ services. LOCATION Building No. 9 No. 619 Longchang Road Yangpu District Shanghai 200090 PRC From Airports – 14.8 miles (23.9 km) from Shanghai Hongqiao International Airport (SHA); 23.4 miles (37.7 km) from Shanghai Pudong International Airport (PVG) Location Orientation – 5.5 miles (8.9 km) from Lujiazui Financial District Parking – Paid parking available on campus PROFILE Phone – +86 21 5156 7242 Email [email protected] GLOBAL SLA 99.999+% Power availability 99.99+% Temperature and Humidity availability 99.99+% Cross Connect availability POWER Electrical Capacity (Critical Customer Load) – 3 kVA per cabinet Electrical Capacity (Uninterruptible Power System) 2 x (2 x 400) kVA + 2 x (3 x 400) kVA + 2 x (3 x 400) kVA (N+N) Utility Feeders – 2 x 6.6 kV Power Transformers – 6 x 2 MVA (6.6 kV / 400 V) Standby Power – Diesel Generators 4 x 1,000 kVA + 2 x 2,000 kVA + 2 x 2,250 kVA ATS (Automatic Transfer Switch) – For CRAC cooling system COOLING Cooling Capacity – 3 kVA per cabinet Cooling Plant – Computer Room Air Conditioners 29 x 100 kW (N+1, DX Units) + 18 x 77 kW (N+2, DX Units with ESM) SECURITY Physical – Dedicated data center building within secured campus; physical access control lists manage ingress and egress; multi-layered defense Human – 24x7x365 security officers Electronic – 24x7x365 CCTV recordings (90 days of video recording), proximity card access control and two factors authentication for private suite/cage (optional) Equinix.cn SH5 SHANGHAI IBX+ DATA CENTER IBX+ TECHNICAL SPECIFICATIONS Square Footage Breakdown Leased Area 57,344 ft 2 (5,327 m 2 ) Colocation Area 25,327 ft 2 (2,353 m 2 ) IBXflex Space Custom Request
Transcript

ABOUT

Equinix, Inc. (Nasdaq: EQIX), connects more than 4,750 companies directly to their customers and partners inside the world’s most networked data centers. Today, enterprise, cloud, networking, digital media and financial services companies leverage the Equinix interconnection platform in 33 strategic markets across the Americas, EMEA and Asia-Pacific. By connecting directly to their strategic partners and end users, customers are forming dynamic ecosystems inside Equinix. These interconnected ecosystems enable companies to optimize the performance of their content and applications and protect their vital digital assets.

Equinix operates four International Business ExchangeTM (IBX®) data centers and one disaster recovery center in Shanghai. Equinix Shanghai SH5 IBX+ data center occupies a 4-story dedicated building located in the Yangpu district, just north of the Lujiazui Finance and Trade Zone and the Bund. This is one of many state of the art IBX centers in key metropolitan areas throughout Asia-Pacific that offers premium colocation and Smart Hands™ services.

LOCATION

Building No. 9 No. 619 Longchang Road Yangpu District Shanghai 200090 PRC

From Airports – 14.8 miles (23.9 km) from Shanghai Hongqiao International Airport (SHA); 23.4 miles (37.7 km) from Shanghai Pudong International Airport (PVG) Location Orientation – 5.5 miles (8.9 km) from Lujiazui Financial District Parking – Paid parking available on campus

PROFILE

Phone – +86 21 5156 7242Email – [email protected]

GLOBAL SLA

� 99.999+% Power availability � 99.99+% Temperature and

Humidity availability � 99.99+% Cross Connect availability

POWER

Electrical Capacity (Critical Customer Load) – 3 kVA per cabinetElectrical Capacity (Uninterruptible Power System) –2 x (2 x 400) kVA + 2 x (3 x 400) kVA + 2 x (3 x 400) kVA (N+N)Utility Feeders – 2 x 6.6 kVPower Transformers – 6 x 2 MVA (6.6 kV / 400 V)Standby Power – Diesel Generators 4 x 1,000 kVA + 2 x 2,000 kVA + 2 x 2,250 kVA ATS (Automatic Transfer Switch) – For CRAC cooling system

COOLING

Cooling Capacity – 3 kVA per cabinetCooling Plant – Computer Room Air Conditioners 29 x 100 kW (N+1, DX Units) + 18 x 77 kW (N+2, DX Units with ESM)

SECURITY

Physical – Dedicated data center building within secured campus; physical access control lists manage ingress and egress; multi-layered defenseHuman – 24x7x365 security officersElectronic – 24x7x365 CCTV recordings (90 days of video recording), proximity card access control and two factors authentication for private suite/cage (optional)

Equinix.cn

SH5 SHANGHAI IBX+ DATA CENTER IBX+ TECHNICAL SPECIFICATIONS

Square Footage BreakdownLeased Area 57,344 ft2 (5,327 m2)Colocation Area 25,327 ft2 (2,353 m2)IBXflex Space Custom Request

© 2015 Equinix, Inc.

BUILDING

Construction Type – Reinforced concreteindustrial structure Building Type – 4-story leased building withraised floorsFloor Load – 10 kN/m²Slab-to-ceiling Height – 4.5 m

FIRE PROTECTION

Fire Detection – Smoke detectors & Very Early Smoke Detection Apparatus (VESDA)Fire Suppression – FM200 gas suppression (Phase 1 & 2) and Inergen (Phase 3)Fire Rating – Minimum 2 hours rating

CERTIFICATIONS

� ISO/IEC 27001: 2013 � SSAE16 SOC-1 Type II

CABLING AVAILABLE

System – Multi-layer fiber runner & copper cable ladder Cross Connects – Cat5e/6, COAX and Fiber

IBX+ TECHNICAL SPECIFICATIONS

SH5 SHANGHAI IBX+ DATA CENTER

SEATTLE

DENVER

ATLANTA

BOSTON

PHILADELPHIA

MIAMI

TORONTO

DUSSELDORF

MUNICH

ZURICH MILAN

GENEVA

DUBAI

PARIS

LONDON

RIO DE JANEIRO

SÃO PAULO

AMSTERDAM

FRANKFURTSILICONVALLEY

LOS ANGELES

CHICAGO

NEW YORK

DALLASWASHINGTON, DC

SINGAPORE

HONG KONG

SHANGHAI

TOKYOOSAKA

JAKARTA

SYDNEY

Equinix locations

Partner Data Center

AMERICAS EMEA ASIA-PACIFIC

MELBOURNE

EQUINIX IBX DATA CENTER LOCATIONS

Located in 33 strategic markets across the Americas, EMEA, and Asia-Pacific.

SH5 IBX Site Spec (A4) v0315 DS-EN PT-BL Q414


Recommended