IECEx Certificate of Conformity INTERNATIONAL ELECTROTECHNICAL COMMISSION IEC Certificatlon Scheme for Explosive Atmospheres for rufes.nc1 demi •• ct the IECEx Scheme vislt _.iecex..com CertifiCllteNo.: "'.tu" Date of lsaue: Applicant: IECEx SIR 05.0033U 2006-02-10 Weldmuller Interface GmbH & Co Klngenbergstraue 16 32758 lletmoId Gormany Issue No.: Q Page 1 014 Elecbical ApparaIus: 8AK R Range of Hllil Mounted TestJOisconnect T.rmißIIls O~ tKX:essory: Type of Protection: Type n ExnAn Approvedforl&aue on be/tIJlfoffhe IECEx CeditIcsi1on_ Pwitiun: SignBturw: (torprlntedversion) Date: CE_ Certiblion 0fIk:er c.~ 2oo~ - 0'2.- 1. This c:ertiicale and sdledule may only be repoduced in ful. 2. This oertilcate Is. not Ir8nsfefabte end remains tM property of the issuing body. 3. The Status and authentidty ofthls certilcate may be verified by visiting the OfIIciallECEx Website. Certificate issued by" SIRA Certification Service South Hili ChisIehurst Kent BR7 5EH United Kingdom __'_Ud
Transcript
Page 1: IECEx Certificate of Conformityold.caltech.ie/pdf/CERT_IECEX_SAKR.pdf · .11 IECEx Certificate of Conformity CertificateNo.: Date oflssue: IECEx SIR 05.0033U 2006-42-10 Schedule lssueNo.:

IECEx Certificateof Conformity

INTERNATIONAL ELECTROTECHNICAL COMMISSIONIEC Certificatlon Scheme for Explosive Atmospheres

for rufes.nc1 demi •• ct the IECEx Scheme vislt _.iecex..com

CertifiCllteNo.:

"'.tu"Date of lsaue:

Applicant:

IECEx SIR 05.0033U

2006-02-10

Weldmuller Interface GmbH & CoKlngenbergstraue 1632758 lletmoIdGormany

Issue No.: Q

Page 1 014

Elecbical ApparaIus: 8AK R Range of Hllil Mounted TestJOisconnect T.rmißIIlsO~ tKX:essory:

Type of Protection: Type n

ExnAn

Approvedforl&aue on be/tIJlfoffhe IECExCeditIcsi1on_

Pwitiun:

SignBturw:(torprlntedversion)

Date:

CE_

Certiblion 0fIk:er

c.~2oo~ - 0'2.-

1. This c:ertiicale and sdledule may only be repoduced in ful.2. This oertilcate Is. not Ir8nsfefabte end remains tM property of the issuing body.3. The Status and authentidty ofthls certilcate may be verified by visiting the OfIIciallECEx Website.

Certificate issued by"

SIRA Certification ServiceSouth Hili

ChisIehurstKent BR7 5EH

United Kingdom__'_Ud

Page 2: IECEx Certificate of Conformityold.caltech.ie/pdf/CERT_IECEX_SAKR.pdf · .11 IECEx Certificate of Conformity CertificateNo.: Date oflssue: IECEx SIR 05.0033U 2006-42-10 Schedule lssueNo.:

IECEx Certificateof Conformity

CertificateNo.:

Date of lsaue:

Manufactum:

Manufacturlng Iocation(s):

IECEx SIR D5.0033U

2006-02-10

Weldmull8r Interface GmbH & CoKingenbergstrasse 1832758 DelmoldGennany

IssueNo.: 0

Page20f ••

T11Iscertilcete Is issued •• verification that a sample(s), represenlative of productiOll, was assessed end tested andfound to co~ with the IEC Standard ist beIow end th81th8 l"Mflufacture'f5 qualily system, relating to the Ex productrlcovered by ttll& certiftcate, was asseued Bnd found to comply wIth the IECEx QuaMty system requirements. Thlscertillcate Is granted subJ&et 10 the conditions as set out in IECEx Scheme Rulea, IECEx 02 end Operations! Documentaes amended.

STANDARDS:The eIedric8I apparatus and 80y acceptable variatklns tu it spedIed In the sdJedule of this certilcate end 1tle ldentiIeddoaJments. was found to c:o!11)lywith the foIowIng standards:

IEC 60079--15 : 2001Edition: 2

E1ectrlcll apparalull Ior explosive gas atmosphern - Part 15: Type of prot&ction 'n'

TEST & ASSESSMENT REPORT8:A sample(.) ofthe equipmenllisted hN .uooessfuly met the 8xaminalion sndt&st requirements flS f8COIT1tKJ In

IECEx ATA::

GBlSIRlExTR06.OOO9IOOFile RefBrence:

UKISIRI05JR51L131nB

NUKEMlQAR06.OOO6IOO

Page 3: IECEx Certificate of Conformityold.caltech.ie/pdf/CERT_IECEX_SAKR.pdf · .11 IECEx Certificate of Conformity CertificateNo.: Date oflssue: IECEx SIR 05.0033U 2006-42-10 Schedule lssueNo.:

.11 IECEx Certificateof Conformity

CertificateNo.:

Date oflssue:

IECEx SIR 05.0033U

2006-42-10

Schedule

lssueNo.: 0

Page 301.

EautPMENT:ExlUIJIfIfd Mdaystem. CtJItIefr!dby Ihi. oerlifir:tft •• tu foIows."

The Type SAK R Range of Rait Mounted TestlOiSCOMeCl: Terminals aAt a single pole terminal 8ssembly thatusas a disconneclion link mounted into a moulded polyamide PA66 or mehilmine insulation housing. Eachtenninal assembly consists of a tin-ptated, copper/zinc, splil, ClJrTent bar, which form. a knlla blade contact. Thlsis fitted with a zino-plated steel, slidlng yoke and .crew 8t esch end. 1JI.11en the screw ja tightenecl. the yoke iscompressecl agaln.t Ihe D..Ifrent bar and serrations incorporated in the surface prevent slippage of thec:onductor. The SAK R Terminals a,. ratecl up to 10 A and are furtherdescribed in the Annexe ofthis certificate.

CONDITIONS CF CERllFICA TlON: NO

Page 4: IECEx Certificate of Conformityold.caltech.ie/pdf/CERT_IECEX_SAKR.pdf · .11 IECEx Certificate of Conformity CertificateNo.: Date oflssue: IECEx SIR 05.0033U 2006-42-10 Schedule lssueNo.:

•• IECEx Certificateof Conformity

Certilk:ateNo.:

Date oflssue:

Additionallnfonnation:

Annexe: IECEx SIR 05.Q033U.pdf

IECEx SIR 05.0033U

2OCl6-42-10 Issue No.: 0

Page "of"

Page 5: IECEx Certificate of Conformityold.caltech.ie/pdf/CERT_IECEX_SAKR.pdf · .11 IECEx Certificate of Conformity CertificateNo.: Date oflssue: IECEx SIR 05.0033U 2006-42-10 Schedule lssueNo.:

Annexe to: IECEx SIR 05.0033U

•siraApplicant: Weidmuller Interface GmbH & Co. Certification ServiceElectrlcal Component: Type SAK R Range of Rail Mounted Test,tDisconnect

Terminals

Terminal reslstance(mo @ 20'C)see note below

SAK R amide PA66 2.66SAK R melamine 400 10 0.5 4 2.38

Note: When any of Ihe abol/e tenmina~ are filled Inside Jundion boxes, Ihe tenminalresistance fIgure to be used forthe plIl'JXJSe cf assessing Öle maximum power dissipation is as listed in lable alxJve.

The voltage rating is an absolute condition of use as stated in Table 7 of EN 50021: 1999. The eurrent rating isnot an absolute figure but [s the recommended value when used in a general purpose junction box ormarshalling box with cables having the following ratings:

CableSize mm 0.5 1MaximumCummt A 5 10

The Type SAK R Range of RaU Mounted TestjDisconnect Terminals comprlse a single pole feed-throughterminal assembly, wlth disconnection link that is mounted Inta a moulded polyamide PA66 or melamlneinsulatlon housing. Each terminal assembly conslsts of a tin-plated, copper/zinc, split, current bar, which formsa knife blade contact. This is fttted wlth a zinc-plated steel, sliding yoke ancl saew at each end. When thescrew is tightened, the yoke is compressed against the current bar ancl serrations incorporated in the surfaceprevent slIppage of the concluctor.

The disconnection link consists of a polyamide PA66 insulated, hinged lever, which is fttted with a tin-plated,ropper/tin, leaf spring contact. The disconnection link is operated by an upward movement of the hingedcontact lever; this breaks the connection between the two, knlfe contacts.

A polyamide PA66 insulated rover is fitted in the moulding to hold and shield the main knife terminals.

Self--defonnation is incorporated in the design when the screws are tightened down, this is used to provide anautomatie ancl progressive anti-rotation/anti-vibration locking effect.

On both the 32 mm (SAK R) & 15 mm (SAK R 15) rall versions, a f1at section, stainless steel spring is kx:ated ina recess at the foot of the tenninal housing, which allows it to be dipped onto a TS32 or TS15 assembly railrespectively. A natural spring effect is designed inta the plastic moulding of the 35 mm (SAK R 35) rail versionto al10w it to be dipped onta a TS35 assembly rall.

The followlng terminals are covered:

Terminal Type Voltagerating

1.510

2.510

410

Higher O.Irrents may be permitted subject to individual examination of each specific application.

The marking is either moulded inta the body of the tenninal or "tampe" printed onto R.

All the terminals may be used in assoclation with Type QB 2, QB 3 or QB4 (twa way, three way or tour wayrespectively) cross-connectors and/or partitions, in which case, the voltage and current ratings are unchanged.In addition, all the terminals may be usecl in assoclatlon with AP end plates. The terminal assembly is to beclamped In place, at both ends, using either a WeidmulIer, Type EK earth terminal, cr associated Type EW (15,15/2 or 35), EWK (1 or 2), WEW (35/1 or 35/2) end bracket respectively.

Special points for notlng

1 The end terminal shall be covered with the associated Type AP end plate ancl the terminal assemblyc1amped in place at both encls, using either a Weidmuller, Type EK earth terminal or associated endbrackets lypes EW (15, 15/2 or 35), EWK (I or 2) and WEW (35/1 or 35/2) respectively.

Where wire siZes that are smaller than 0.5 mmz are used, a oimped lug or ferrule wlth a minimum sizeof 0.5 mm2 shall be fltted to the wire.

Except where shown in a certifieate as belng internal wiring of apparatus, not more than one single crmultiple strand lead shall be connected into either side of any termInal, unless multiple conductors havebeen joined in a suitable manner, e.g. two conductors into a single insulated crimped boot lace ferrule.

Sira Certificatlon ServiceDate: 25 November 2005 Page 1 of 2 Rake Lane. Eccleslon, Chesler. CH4 9JN. England

Tel .•.44 (0)1244 670900 Fax: +44(0)1244 681330

Email. exhazardClsira co_ukSira CettifiCalion SeMce ISa S6I'Vic:e 01Sira Test & CertitiCation ltd

Page 6: IECEx Certificate of Conformityold.caltech.ie/pdf/CERT_IECEX_SAKR.pdf · .11 IECEx Certificate of Conformity CertificateNo.: Date oflssue: IECEx SIR 05.0033U 2006-42-10 Schedule lssueNo.:

Annexeto:

Applicant:ElectrlcalComponent:

IECEx SIR OS.OO33U

Weidmuller Interface GmbH & Co.Type SAK R Range of Rail Mounted Test/DisconnectTerminals

•siraCertification Service

Any wires that are connected to the tenninals shall be insulated for the appropliate voltage and thisinsulatiOn shall extend to within Imm of the metal of the terminal throat.

All terminal screws, used or unused, shal1 be tightened down.

The terminals shall be installed on the relevant mounting rai!:

Type Railstandard Weidmullerrail reference

SAKR IEC60715:1995 Am. 1 TS32SAKR 15 IEC 60715:1995 Am. 1 T515SAKR 35 IEC 60715:1995 Am. 1 T535

The minimum creepage and dearance distances between the installecl tenninals and adjacent exposedfaces of equipment, enclosure walls and covers shall be 5 mm and 4 mm respectively.

The terminals shall never be exposecl to temperatures that are outside of the following range:

Material TemperatureRange

Polyamide PA66 -50"C 10 +9O"CMelamine (KrG) -5Q"C 10 +9O"C

In addition, they shall only be installed and wired with cable in a temperature range of -lOOC to +SO°c.

When these terminals are used in an atmosphere that contains combustible dust, they shatl be installedinside an enclosure that has been suitably certified for use in this environment by a notified body.

10 The tightening torque applied to the terminal screws shall be between 0.5 Nm and 1 Nm.

11 The supply to the Type SAK R Range cf Rail Mounted Test/Disconnect Terminals shall be switched offwhen the disconnectJconnect facility is used i.e. durtng upward or downward movement of thedisconnecbon lever assembly.

12 Where the terminals are subjected to excessive vibration and vertically mounted, they shall be mountedwith the disconnectlon lever hinged at the bottam.

13 All of the Type QB cross-conneetors shall be Jimited to the same current rating as the related terminaland shall not be used with currents in excess of this value.

14 Where the prong of a Type QB cross-connector is used In a tenninal way, a further single conductor of1mm1 minimum aoss-sectional area may be connected to the same terminal way on top of the prong.

15 The Type QB cross-oonnector shall be fitted with the angled insulation on the cro5s-a>nnecting anninclined upwards towards the top of the terminal block.

16 All Type QB cross-connectors shall be isolated from adjacent terminals and other Type QB cross-connectors using AP end plates.

Date: 25 November 2005Sira Certificatlon Service

Page 2 of 2 RakeLane.Eccleston,Chester,CH49JN.EnglandTel' +44 (0)1244 670900 Fax: +44 (0)1244 681330

Email: elChazardOsira co_ukSira Certificafion Service is a service of Sira Test & Certitication Ltd