ILC ( International Linear Collider ) Asian Region Electrical Design
H. Hashiguchi, Nikken Sekkei, Co. Ltd.,A. Enomoto, KEK
ILC Mechanical & Electrical Review and CFS Baseline Technical Review2012.3.21-23, CERN
2
Contents
① Electrical Power System② Electrical Grounding System③ Communication Network System
3
Electrical Power System
Design Concepts ・ Reliability ・ Efficiency・ Cost
4
Electrical Power System Site Specific Issues
・ HLRF layout: RDR-like・ Local HV lines: 150 – 500
kV・ Site MV: 66 kV・ Area MV: 6.6 kV
Strawman Baseline forTechnical Design
Phase2 (2010-2012)
SB2009Re-baselining
5
table overall electrical load summary:
Power(MW) Power Facter Power(MVA) AH1 AH2 AH3 AH4 AH5 AH6 AH7 AH8
Source e- 4.30 0.9 4.78 4.78
Source e+ 15.04 0.9 16.71 16.71
DR 17.42 0.9 19.36 16.45 2.90
RTML 11.88 0.9 13.20 5.94 0.66 0.66 5.94
ML 97.24 0.9 108.04 22.20 22.20 9.99 9.25 22.20 22.20
BDS 15.25 0.9 16.94 8.47 8.47
Dump 3.95 0.9 4.39 4.39
IR(DH) 0.46 0.9 0.51 0.51
Cryogenics 49.63 0.9 55.14 7.37 7.37 7.96 2.52 1.73 7.96 7.37 7.37
TOTAL 215.17 239.08 35.51 29.57 43.80 18.97 2.90 6.63 0.00 31.12 29.57 35.51
EH
Electrical Power SystemLoad Requirements (Full Power Op., ref. Sep. 2011)
Requirement ( for 500GeV )
6
Electrical Power SystemLoad Requirements (w. Power Factor)
Power Factor Assumption
table overall electrical load summary:
Power(MW) Power Facter Power(MVA) AH1 AH2 AH3 AH4 AH5 AH6 AH7 AH8
Source e- 4.30 0.9 4.78 4.78
Source e+ 15.04 0.9 16.71 16.71
DR 17.42 0.9 19.36 16.45 2.90
RTML 11.88 0.9 13.20 5.94 0.66 0.66 5.94
ML 97.24 0.9 108.04 22.20 22.20 9.99 9.25 22.20 22.20
BDS 15.25 0.9 16.94 8.47 8.47
Dump 3.95 0.9 4.39 4.39
IR(DH) 0.46 0.9 0.51 0.51
Cryogenics 49.63 0.9 55.14 7.37 7.37 7.96 2.52 1.73 7.96 7.37 7.37
TOTAL 215.17 239.08 35.51 29.57 43.80 18.97 2.90 6.63 0.00 31.12 29.57 35.51
EH
7
Electric Power Capacitytable overall electrical load summary:
Power(MW) Power Facter Power(MVA) AH1 AH2 AH3 AH4 AH5 AH6 AH7 AH8
Source e- 4.30 0.9 4.78 4.78
Source e+ 15.04 0.9 16.71 16.71
DR 17.42 0.9 19.36 16.45 2.90
RTML 11.88 0.9 13.20 5.94 0.66 0.66 5.94
ML 97.24 0.9 108.04 22.20 22.20 9.99 9.25 22.20 22.20
BDS 15.25 0.9 16.94 8.47 8.47
Dump 3.95 0.9 4.39 4.39
IR(DH) 0.46 0.9 0.51 0.51
Cryogenics 49.63 0.9 55.14 7.37 7.37 7.96 2.52 1.73 7.96 7.37 7.37
TOTAL 215.17 239.08 35.51 29.57 43.80 18.97 2.90 6.63 0.00 31.12 29.57 35.51
EH
Electrical Power SystemLoad Requirements (Capacity)
8Total 300MVA including margin
table overall electrical load summary:
Power(MW) Power Facter Power(MVA) AH1 AH2 AH3 AH4 AH5 AH6 AH7 AH8
Source e- 4.30 0.9 4.78 4.78
Source e+ 15.04 0.9 16.71 16.71
DR 17.42 0.9 19.36 16.45 2.90
RTML 11.88 0.9 13.20 5.94 0.66 0.66 5.94
ML 97.24 0.9 108.04 22.20 22.20 9.99 9.25 22.20 22.20
BDS 15.25 0.9 16.94 8.47 8.47
Dump 3.95 0.9 4.39 4.39
IR(DH) 0.46 0.9 0.51 0.51
Cryogenics 49.63 0.9 55.14 7.37 7.37 7.96 2.52 1.73 7.96 7.37 7.37
TOTAL 215.17 239.08 35.51 29.57 43.80 18.97 2.90 6.63 0.00 31.12 29.57 35.51
EH
+about 60MVA margin
Electrical Power SystemLoad Requirements (Capacity)
9
Electrical Power SystemSystem Redundancy (Surface-ground Main Substation)
VCT VCT
275KV/66KV100MVA
( in future )
( in future )
275KV/66KV100MVA
275KV/66KV100MVA
275KV/66KV100MVA
275KV/66KV100MVA
275KV/66KV100MVA
( in future )
( in future )
AH2 AH3 AH4 EH AH2 AH3 AH4 EHAH5 AH6 AH7 AH5 AH6 AH7
Transformer Space For 1TeV system
N ( 3 ) +1 transformer component
for 500GeV system
① ② ③ +1
275kV Receiving Equipment isAvailable For 1TeV system(Up to 500MVA)
10
VCT VCT
275KV/66KV100MVA
( in future )
( in future )
275KV/66KV100MVA
275KV/66KV100MVA
275KV/66KV100MVA
275KV/66KV100MVA
275KV/66KV100MVA
( in future )
A B
2 Components of Distribution panel
( in future )
AH2 AH3 AH4 EH AH2 AH3 AH4 EHAH5 AH6 AH7 AH5 AH6 AH7
Electrical Power SystemSystem Redundancy (Main Substation, cnt.)
11
66KV power distribution Main line diagram
AH2 AH3 AH4 EH AH5 AH6 AH7
A B
Main SubstationFrom 2 Components of
Distribution panel
to Each 66kV substation
Electrical Power SystemSystem Redundancy (Site Power Distribution)
122 transformers(30MVA ) at Each Hall
table overall electrical load summary:
Power(MW)Power FacterPower(MVA) AH1 AH2 AH3 AH4 AH5 AH6 AH7 AH8
Source e- 4.30 0.9 4.78 4.78
Source e+ 15.04 0.9 16.71 16.71
DR 17.42 0.9 19.36 16.45 2.90
RTML 11.88 0.9 13.20 5.94 0.66 0.66 5.94
ML 97.24 0.9 108.04 22.20 22.20 9.99 9.25 22.20 22.20
BDS 15.25 0.9 16.94 8.47 8.47
Dump 3.95 0.9 4.39 4.39
IR(DH) 0.46 0.9 0.51 0.51
Cryogenics 49.63 0.9 55.14 7.37 7.37 7.96 2.52 1.73 7.96 7.37 7.37
TOTAL 215.17 239.08 35.51 29.57 43.80 18.97 2.90 6.63 0.00 31.12 29.57 35.51
30MVA30MVA
30MVA30MVA
30MVA30MVA
30MVA30MVA
30MVA30MVA
30MVA30MVA
30MVA,30MVA30MVA( )66kV/6.6kV transformer
EH
Electrical Power SystemSystem Redundancy (Area 66/6.6kV Transformers)
13Keep one Stand-by Transformer(30MVA) at center warehouse on the ground
table overall electrical load summary:
Power(MW)Power FacterPower(MVA) AH1 AH2 AH3 AH4 AH5 AH6 AH7 AH8
Source e- 4.30 0.9 4.78 4.78
Source e+ 15.04 0.9 16.71 16.71
DR 17.42 0.9 19.36 16.45 2.90
RTML 11.88 0.9 13.20 5.94 0.66 0.66 5.94
ML 97.24 0.9 108.04 22.20 22.20 9.99 9.25 22.20 22.20
BDS 15.25 0.9 16.94 8.47 8.47
Dump 3.95 0.9 4.39 4.39
IR(DH) 0.46 0.9 0.51 0.51
Cryogenics 49.63 0.9 55.14 7.37 7.37 7.96 2.52 1.73 7.96 7.37 7.37
TOTAL 215.17 239.08 35.51 29.57 43.80 18.97 2.90 6.63 0.00 31.12 29.57 35.51
30MVA30MVA
30MVA30MVA
30MVA30MVA
30MVA30MVA
30MVA30MVA
30MVA30MVA
30MVA,30MVA30MVA( )66kV/6.6kV transformer
EH
Electrical Power SystemSpare 66/6.6kV Transformer
14
One line diagram of 66KV substation with generator
Each substatiosn installed in access halls and an experimental hall
66KV/6KV30MVA
66KV/6KV30MVA
6 % 6 %
VCBFor RF
500Kvar 500Kvar
×12
space
×8
VCB
×10 ×10
Capacitor for conventional load power factor improvement
Electrical Power System66/6.6kV Substations (@7 underground halls)
15
One line diagram of 66KV substation with
generator
Emergency GeneratorOn the ground
66KV/6KV30MVA
66KV/6KV30MVA
6 % 6 %
VCBFor RF
500Kvar 500Kvar
×12
space
×8
VCB
×10 ×10
6.6kV One main line branches about 10 RF
6.6kV One main line branches about 4 local substation
Emergency load assumption
Drainage pump , smoke extraction fan , and so forth
Helium gas extraction system also
prefers to add emergency load
Electrical Power System66/6.6kV Substations (@7 underground halls, cnt.)
16
A
G
Cooling WaterSystem
H H
B
G
C
K K
E
E
LEVEL
Pump
RFSide
CryomoduleSide
Electrical Facilities
A
8000
1000
091
600
5600
010
000
10000
8000
33500
8000
45000
R30000
1000
0
8000 7200
0
35500
1500
0
15000 15000
1500
0
41300
1000
0
4000
0
20000
20000
66kV Substation
Electrical Power System66/6.6kV Substations (@7 underground halls, cnt.)
Floor Plan
17
5000
6000
4500
ductGIS
20000
3000
0
30MTR
Monitoring system
SC F
6.6KV/200V6.6KV/200V
Battery
Monitoring system
GIS
30MTR
F SC
Floor layout plan
Maintenance space
6.6KV/200V6.6KV/200V
Battery
sectionA - A ’
60005000
Maintenance space
1000
0
20000
A A ’
Electrical Power System66/6.6kV Substations (@7 underground halls, cnt.)
18
1φ3W6.6KV
/200-100V100KVA
1φ3W6.6KV
/200-100V100KVA
3φ4W6.6KV/400V
200KVA
capacitor Harmonic filter
For RF150KVA
Local substation( each 4 RF )
Power supply for RF( each 1 RF )
Capacitor for RF power factor improvement
Harmonic filter for RF
Electrical Power System6.6kV Local Substations (@Service tunnel)
19
400
1098
4402
5500 60
00
Mesh grounding
6.6kVcables,200V cables
Cables for communicationsPlumbing for heat and cool system
66kV cables
3300 3500
1500
4200
11000
11600
12000
R4000
R7000
Maintenance space
Electrical Power SystemML Tunnel Section
20
1600
1600
1000
38000
A
Maintenance space
1500
Beam Tunnel
Service Tunnel
Electrical Power SystemML Tunnel Floor
21
FCU
Pulsegenerator
K l ystron
modulator
RackforRFPower supply for RF
(Each I RF , with Harmonic filter)
RackforRF
1500
1600
1600
1000
1500
1100 1100 4270
5000
305 1341 432 3385
800
800
1067
1251
A
Maintenance space
R4000
R7000
Section Layout
Electrical Power SystemML Tunnel Floor (Detail 1)
22
Pump
Control Panel
FCU
Local substation(each 4 RF)
Panel for grounding
Crystron
Pump
A
1600
1600
1000
3385 1100 1100 914
800
800
38000
610
1000
4000
1100
Maintenance space
1500
0
R4000
R7000
Section Layout
Electrical Power SystemML Tunnel Floor (Detail 2)
23
A38000
Electrical Power SystemML Tunnel Elevation
24
Pulsegenerator
modulatorRackforRF
Power supply for RF(Each I RF , with Harmonic filter)
RackforRF
RackforRF
Crystron
914 914 914
FCU
2007
914 914
A
2100
38000
Electrical Power SystemML Tunnel Elevation (Detail 1)
25
BeamsafetyRack
FCU
A
4000
2350
914 914
2324
2100914
38000
Pulsegenerator
Crystron
RackforRF
RackforRF
Pump
Local substation(each 4 RF)
Panel for grounding
Electrical Power SystemML Tunnel Elevation (Detail 2)
26
Grounding System
Purpose ・ Avoid influences of electric leakage from other
machines ・ Produce signal base for information systems ・ Thunder lightning protection
27
Electrical Grounding SystemTypical Model of Tunnel Ground System
Mesh grounding ( using arrangement bar )
Panel for Grounding ( for each 38m )
Beam tunnel
AH
Main line for
grounding
Grounding for lightning protection Functional
Grounding
Grounding for SPD
Service lineSPD
(surge protect device)
Main Panel for Grounding
Facilities on the ground
Lightning rod
Reduce Grounding Resistance
Flexible for switching grounding line connection
Lightning Protection On the ground
28
Communication Network System
Design Concept・ Reliability of Network for Information System ・ Reducing Space by Unified wiring
management・ Efficient Network by Unified wiring for
Reducing Construction Cost
29
Communication Network System Needs for ILC
① Systems for Communication ・ internet ・ telephone ・ pubulic address or paging
④ Systems for monitoring ・ electric power system monitoring ・ camera monitoring ・ air condition and pump monitoring
② Systems for Lineac control
③ Systems for Safety ・ fire ditection and guide ・ Radiation safety management
30
Communication Network System Equipment
Network infrastructures
panel wiring rack
31
Communication Network System Overall network system concept
Unified Wiring Networks
Systems for communication
Systems for lineac control
Systems forsafety Systems for
monitoring
Assumed systems based on unified Wiring Networks with back-up can reduce space.
32
Summary① Electrical Power System → Electrical Power System is discussed taking account
of reliability , efficiency, and cost. → Electrical equipment layout were discussed to
determine the cavern size of substations.
33
SummaryAsia region electrical design
② Electrical Grounding System → A grounding system for a hard-rock mountain site
was discussed.
③ Communication Network System → Unified and extended network system was proposed
taking advantage of sufficiently radiation-shielded “Kamaboko-type” service tunnel.
34
Appendix
ILC ‘Area System’- Superconducting Electron/Positron Linear Accelerators-
35
(4) Ring To Main Linac (RTML)
(3) Damping Ring (DR)
(5) Main Linac (ML)
x 560
(2) Positron (e+) Source (1) Electron (e-) Source(7) Experimental Hall
(6) Beam Delivery System (BDS)
e- Main Linac (ML)
e+ Main Linac (ML)
RTML
RTML
Beam Delivery System (BDS)
e+ Source
~31 kmExpansion to~50 km
(for 1 TeV)
Damping Ring (DR)
e+ Source
Design Progress from 2005 to 2009Reference Design Report (RDR) published in 2007.Re-baselining for cost containment undergoing.
36
Baseline Configuration Document
BCD (2005)
Reference Design Report
RDR (2007)
Strawman Baseline forTechnical Design
Phase2 (2010-2012)
SB2009
Current Baseline
Re-baselining
Main Linac (ML) RF Unit in RDR- Twin-tunnel accelerator configuration -
37
AC plug-in power: 150 kWOutput pulse: 120 kV x 130 A = 15.6 MW peak, 1.6 ms, 5 Hz
Averaged output power: 124.8 kWModulator Efficiency: 83%
Power loss: 25.2 kW
Input RF power: ~100 WInput DC pulse: 15.6 MW peak, 1.6 ms, 5 Hz
Output RF pulse: 10 MW peak, 1.565 ms, 5 HzAveraged output power: 78.25 kW
Klystron Efficiency: 65%Power loss: 46.55 kW
Power Loss: ~5.6 kW (7%)
Service Tunnel
Beam Tunnel
e- ML 282 RF unitse+ ML 278 RF units
Total 560 RF units
Field gradient: 31.5 MV/mEnergy gain per RF unit : 850 MeV
(with 22% tuning overhead)
37.956 m
ML RF Unit- Distributed RF System (DRFS) -
38
X
26.336 m (~70%) 11.62 m
~5.4 m (L)
(every 4th units)
35.100 m
(Every 4th Units,
152 m)
Cooling WaterSkid and
Common Electricity
1.6 m (W)
2.438 m (H)
Cryogenic System Configuration in RDR
39
Electrical / Mechanical Requirements - Electricity in RDR -
40
Electricity Distribution- 66 kV High Voltage Line Along The Site (Asian Regional Plan) -
41
Service Tunnel (RDR) / Main Tunnel (SB2009)
Surface