+ All Categories
Home > Documents > Improved DSP-controlled online UPS system with high real output power

Improved DSP-controlled online UPS system with high real output power

Date post: 16-Sep-2016
Category:
Upload: j-l
View: 215 times
Download: 3 times
Share this document with a friend
7
Improved DSP-controlled online UPS system with high real output power T.-J. Liang and J.-L. Shyu Abstract: A circuit topology is proposed for single-phase online UPS systems. The proposed circuit incorporates a built-in bidirectional AC/DC converter, which provides power factor correction and active power filtering. The input stage, based on a bidirectional AC/DC converter, functions as a rectifier with unity power factor correction for normal AC line mode operation, and as an active power filter for outage mode operation. During input power failure, the bidirectional AC/DC converter functions as an active power filter, providing reactive power to the load. Simultaneously, the DC/AC voltage inverter output stage supplies real power from the battery bank to the critical load. The real power capability is improved compared with that of a conventional online UPS system, and extra loads can be connected to the UPS system during outage. The power circuit of the proposed UPS system is presented and analysed. Circuit models are derived and a UPS digital control system using a digital signal processor (DSP) is developed. Finally, simulated and experimental results obtained from a laboratory prototype are presented to confirm the feasibility and features of the proposed UPS scheme. 1 Introduction Uninterruptible power supplies (UPS) ensure continuous power flow to critical loads in the event of disturbance surges or AC line failure, and have been used for a wide variety of loads, including telecommunication systems, medical systems, industrial control systems etc. Generally, an UPS system requires the normal utility AC line input current to have a low total harmonic distortion (THD) sinusoidal current with unity power factor. A UPS is required to deliver a well-regulated sinusoidal output voltage with low THD to the load, regardless of whether the utility AC power source is normal or not. Online and offline UPS systems are the two major UPS schemes [1–6] . Online UPS systems are generally preferred because of high reliability and good voltage regulation. Because AC lines are easily contaminated, a power factor correction circuit is usually employed to obtain high power factor from the UPS system, thereby preventing contam- ination of the AC lines [7–9] . In a conventional online UPS system, the input stage is disabled and kept idle during AC line outage. The conventional UPS system has an inherent real output power limitation for nonlinear loads, as the load current may contain undesirable harmonics and is not kept in phase with the output voltage. As a result, the output power factor of the conventional UPS systems is low while feeding nonlinear loads because the real power absorbed by the load is low. Nevertheless, a UPS system is expected to produce nearly sinusoidal output current at the output side and thus raise the output power factor of the UPS system. An active power filter (APF) is usually employed to compensate for line current harmonics and the reactive power of nonlinear loads, yielding a near-unity power factor and sinusoidal current waveform for the AC voltage source [10, 11] . This paper presents the hardware implementation and experimental results of a bidirectional AC/DC converter with power factor correction and active power filtering, a system that was presented previously as a simulation [12] . The input stage, based on a bidirectional AC/DC converter, functions as a power factor correction circuit for normal AC line mode operation to increase the AC line power factor and to reduce the AC line current harmonic components. During input power failure, the bidirectional AC/DC converter functions as an active power filter, providing reactive power to the load. Thus the real output power capability is improved compared with that of a conventional online UPS, and an efficient economic UPS system is achieved. 2 Proposed UPS configuration Figure 1 shows the proposed online UPS circuit configura- tion which consists of a bidirectional AC/DC converter and a DC/AC voltage inverter. An LC lowpass filter is used at the output side for eliminating unwanted harmonic AC line V DC DC/AC DC/AC voltage voltage inverter inverter L o C o bidirectional bidirectional AC/DC AC/DC converter converter L S v s v o S1 S2 rated load extra load C D AC + + Fig. 1 Proposed online UPS system T.-J. Liang is with the Department of Electrical Engineering, National Cheng Kung University, 1 University Road, Tainan, Taiwan 70101, ROC J.-L. Shyu is with the Department of Electrical Engineering, Kao Yuan Institute of Technology, 1821 Chung-Shan Road, Lu-Chu Hsian, Kaohsiung Hsian, Taiwan, ROC r IEE, 2004 IEE Proceedings online no. 20040020 doi:10.1049/ip-epa:20040020 Paper first received 20th September and in revised form 4th June 2003 IEE Proc.-Electr. Power Appl., Vol. 151, No. 1, January 2004 121
Transcript

Improved DSP-controlled online UPS system withhigh real output power

T.-J. Liang and J.-L. Shyu

Abstract: A circuit topology is proposed for single-phase online UPS systems. The proposed circuitincorporates a built-in bidirectional AC/DC converter, which provides power factor correction andactive power filtering. The input stage, based on a bidirectional AC/DC converter, functions as arectifier with unity power factor correction for normal AC line mode operation, and as an activepower filter for outage mode operation. During input power failure, the bidirectional AC/DCconverter functions as an active power filter, providing reactive power to the load. Simultaneously,the DC/AC voltage inverter output stage supplies real power from the battery bank to the criticalload. The real power capability is improved compared with that of a conventional online UPSsystem, and extra loads can be connected to the UPS system during outage. The power circuit ofthe proposed UPS system is presented and analysed. Circuit models are derived and a UPS digitalcontrol system using a digital signal processor (DSP) is developed. Finally, simulated andexperimental results obtained from a laboratory prototype are presented to confirm the feasibilityand features of the proposed UPS scheme.

1 Introduction

Uninterruptible power supplies (UPS) ensure continuouspower flow to critical loads in the event of disturbancesurges or AC line failure, and have been used for a widevariety of loads, including telecommunication systems,medical systems, industrial control systems etc. Generally,an UPS system requires the normal utility AC line inputcurrent to have a low total harmonic distortion (THD)sinusoidal current with unity power factor. A UPS isrequired to deliver a well-regulated sinusoidal outputvoltage with low THD to the load, regardless of whetherthe utility AC power source is normal or not. Online andoffline UPS systems are the two major UPS schemes [1–6].Online UPS systems are generally preferred because of highreliability and good voltage regulation.Because AC lines are easily contaminated, a power factor

correction circuit is usually employed to obtain high powerfactor from the UPS system, thereby preventing contam-ination of the AC lines [7–9]. In a conventional online UPSsystem, the input stage is disabled and kept idle during ACline outage. The conventional UPS system has an inherentreal output power limitation for nonlinear loads, as the loadcurrent may contain undesirable harmonics and is not keptin phase with the output voltage. As a result, the outputpower factor of the conventional UPS systems is low whilefeeding nonlinear loads because the real power absorbed bythe load is low. Nevertheless, a UPS system is expected toproduce nearly sinusoidal output current at the output side

and thus raise the output power factor of the UPS system.An active power filter (APF) is usually employed tocompensate for line current harmonics and the reactivepower of nonlinear loads, yielding a near-unity power factorand sinusoidal current waveform for the AC voltage source[10, 11].This paper presents the hardware implementation and

experimental results of a bidirectional AC/DC converterwith power factor correction and active power filtering, asystem that was presented previously as a simulation [12].The input stage, based on a bidirectional AC/DC converter,functions as a power factor correction circuit for normalAC line mode operation to increase the AC line powerfactor and to reduce the AC line current harmoniccomponents. During input power failure, the bidirectionalAC/DC converter functions as an active power filter,providing reactive power to the load. Thus the real outputpower capability is improved compared with that of aconventional online UPS, and an efficient economic UPSsystem is achieved.

2 Proposed UPS configuration

Figure 1 shows the proposed online UPS circuit configura-tion which consists of a bidirectional AC/DC converter anda DC/AC voltage inverter. An LC lowpass filter is used atthe output side for eliminating unwanted harmonic

AC line

VDC

DC/AC DC/AC voltage voltage inverterinverter

Lo

Co

bidirectional bidirectional AC/DC AC/DC converterconverter

LSvs vo

S1

S2

rated load

extra load

CDAC

+ +

− −

Fig. 1 Proposed online UPS system

T.-J. Liang is with the Department of Electrical Engineering, National ChengKung University, 1 University Road, Tainan, Taiwan 70101, ROC

J.-L. Shyu is with the Department of Electrical Engineering, Kao Yuan Instituteof Technology, 1821 Chung-Shan Road, Lu-Chu Hsian, Kaohsiung Hsian,Taiwan, ROC

r IEE, 2004

IEE Proceedings online no. 20040020

doi:10.1049/ip-epa:20040020

Paper first received 20th September and in revised form 4th June 2003

IEE Proc.-Electr. Power Appl., Vol. 151, No. 1, January 2004 121

components from the inverter output voltage. Switch S1 isincorporated in the power circuit to provide isolationbetween the UPS and the input AC power. When an inputpower failure occurs, power is transferred to the critical loadfrom the battery bank through the DC/AC voltage inverter.The system has two operating modes. One is the normal

mode (Fig. 2a), and the other is the outage mode (Fig. 2b).In the normal mode, switch S2 is opened and thebidirectional AC/DC converter functions as a power factorcorrection rectifier, so that the line current is sinusoidal andin phase with the line voltage. The DC/AC voltage inverteris modulated such that the output voltage amplitude is heldconstant with low THD. During outage mode operation,switch S2 is closed and the bidirectional AC/DC converteris linked with the output of the DC/AC voltage inverter.The bidirectional AC/DC converter functions as an activepower filter, i.e. the bidirectional converter provides reactivepower and non-sinusoidal current to the load. The DC/ACvoltage inverter can supply high real output power to theload. Thus the output power factor of the DC/AC voltageinverter is near-unity and the overall real output powercapability of the UPS system is improved. For outageoperation, this additional real power capability allows theaddition of significantly extra load.

3 System analysis and controller design

The proposed UPS system comprises a bidirectional AC/DC converter and a DC/AC voltage source inverter.

3.1 Power factor correction rectifierFigure 3 shows the circuit schematic and the controller ofthe power factor correction (PFC) rectifier [7–9]. Whenutility AC power is normal, the bidirectional AC/DCconverter operates as a PFC rectifier to improve inputpower factor. The control scheme consists of two parts: aninner current controller and outer voltage controller. Thecontrol strategy of the gating signals involves comparing theoutput voltage vcp of the current controller with triangularcarrier vtri. Under this gating control scheme, the linecurrent is follows the current command i�s such that near-unity power factor and low current harmonics are obtained.

If the control voltage vcp is kept constant over a switchingperiod, the duty ratios of the PFC rectifier can be expressedby:

d1p ¼ 12þ vcp2vtri

d2p ¼ 12� vcp2vtri

ð1Þ

where d1p and d2p denote the duty ratios of lower switchesSW2 and SW4 at every switching period Ts. The amplitudeof the triangular carrier is vtri. Resistance of the AC line isneglected to simplify circuit analysis. The equations of thePFC circuit model shown in Fig. 3a can be obtained asfollows:

Lsdisdt

¼ vs � vp ð2Þ

where vp is the pulse width modulation (PWM) PFCvoltage, vs is the supply voltage and is is the line current.PFC voltage vp is represented in terms of duty ratios d1p andd2p as:

vp ¼ ðd1p � d2pÞVDC ¼ kpwmvcp ð3Þwhere kpw¼ vDC/vtri is the gain of the PFC rectifier. If thebattery bank is fully charged and neglecting the power lossof the converter, the DC-side current of the PFC circuit canbe expressed as:

id ¼ CDdvDCdt

þ vDCRDC

ð4Þ

vo

VDCAC

DC/AC voltage inverter

LoCo

vo

Lo

Co

AC line

LS

iois

vs

on

off

PFC rectifier

+

if

ioif

S2

S2

ilrated load

extra load

CD

S1

S1

active power filter (APF)

VDCAC

DC/AC voltage inverter

AC line

LS

ia

vs

off

on

ilrated load

extra load

CD

+

− −

+

+

a

b

Fig. 2 UPS operation modesa Schematic of proposed online UPS system during normal modeb Schematic of proposed online UPS system during outage mode

is

CDvDC

SW1

SW4

SW1SW2

SW3SW4

SW2

SW3

id

icRDC

iL

AC

LS

vs vp

*sivcp

vtricurrent controller

voltage controller

is

sin �t DCv

*vDC

Gsc(s)

Lss1kpwm

vs

(k )is* isvcp (k)

kcp

kif

vpcurrent current

controllercontroller

fi

vfk

kif

1v DC (k )

ev (k )

vpv (k )Gpv (z)*

vDC

sin (k )

voltage voltage controllercontroller

current current looploop

is

is(k)*kad RDCCDs+1

RDCid

fv

+

+

+

+ −

+ + +

−−

+

+−

+

a

b

c

Fig. 3 Circuit configuration and control strategy of bidirectionalAC/DC converter during normal modea PFC circuitb Current loopc Voltage loop

122 IEE Proc.-Electr. Power Appl., Vol. 151, No. 1, January 2004

Using the power balance relation between the inputand output of the PWM converter at unity power factorgives:

kad9idis¼ vs

vDCð5Þ

where kad denotes as power transfer gain. Figs. 3b andc show the controllers using circuit modelling equations(1)–(5).To eliminate the disturbance of the line voltage vs shown

in Fig. 3b, the disturbance compensator is set to:

GscðsÞ ¼ 1=kpwm ð6ÞA proportional controller kcp is chosen as the currentcontroller. In this case, the transfer function between i�s andis can be derived as:

isi�s¼ kcpkpwm

Lssþ kcpkpwmkif¼ 1

kifð7Þ

where kif is current feedback scaling gain and i�s is the linecurrent command. The digital current control algorithm canbe written as:

vcpðkÞ ¼ ½i�s ðkÞ � isðkÞ�kcp � vsðkÞkpwm

ð8Þ

The digital proportionalFintegral (PI) controller Gpv(z)shown in Fig. 3c is used to regulate the DC voltage and isexpressed as:

GpvðzÞ ¼ kpp þ kpiTvz� 1 ð9Þ

where Tv is the sampling period of the voltage loop, and kpp

and kpi are the proportional and integral gains of the PIcontroller. Therefore, the finite difference equation of the PIcontroller can be obtained as:

vpvðkÞ ¼kppfevðkÞ � evðk � 1Þgþ kpievðkÞ þ vpvðk � 1Þ ð10Þ

where ev(k�1) and vpv(k�1) are the voltage error andcontroller output at the (k�1) sampling instant. Multiplyingvpv(k) by the synchronising signal sin(k) of measured supplyvoltage vs(k), the resulting line current command i�s ðkÞ isthen obtained as:

i�s ðkÞ ¼ vpvðkÞ sin ðkÞ ð11ÞSubstituting (10) into (11) gives the line current commandi�s ðkÞ. Therefore, the desired duty ratios d1p(k) and d2p(k)can be calculated by substituting (8) into (1).

3.2 Active power filterWhen utility power failure is detected, the APF isimmediately connected in parallel with the loads throughswitch S2. The input stage bidirectional AC/DC converter isthen switched from PFC mode to APF mode andconnected in parallel with the DC/AC voltage inverter.The APF circuit configuration and controllers are shown inFig. 4 [10, 11]. Multi-loop controls, an inner current loopfor regulating the DC/AC inverter output current io and anouter voltage loop for regulating the DC bus voltage, areused as the APF control system. The APF is designed toprovide compensatory reactive energy to load current il sothat the DC/AC voltage inverter output current io is inphase with the sinusoidal output voltage vo regardless ofload nonlinearities.Using a procedure similar to the above PFC circuit

analysis, the APF circuit modelling equations can now bewritten. The duty ratios d1a and d2a of the switches SW1

(SW4) and SW3 (SW2) are expressed as:

d1a ¼1

2þ vca2vtri

d2a ¼1

2� vca2vtri

ð12Þ

where d1a and d2a are the APF duty ratios and vtri is theamplitude of the triangular carrier. The voltage equation ofAPF can be derived as:

Lsdiadt

¼ va � vo ð13Þ

where ia is the APF output current, vo is the output voltageof the DC/AC voltage inverter and va is the PWM APFvoltage. The APF voltage va can be obtained in terms ofduty ratios d1a and d2a as:

va ¼ ðd1a � d2aÞVDC ¼ kpwmvca ð14Þwhere kpwm¼ vDC/vtri denotes the APF converter gain. Thecurrent equations on the DC side and AC side can bewritten as:

ic ¼ CDdvDCdt

ð15Þ

il ¼ ia þ io ð16ÞThe current controller and voltage controller are illustratedin Figs. 4b and c, where kif and kvf are the current andvoltage sensor scaling gains. The current controller shownin Fig. 4b is a proportional controller with proportional

ia

sin ωt

DC/AC DC/AC voltage voltage inverterinverter

CD vDC

icLS

vavo

ilrated load

extra load

ioif

vDC

SW5 SW7

SW8SW6

SW5

SW6

SW7

SW5

SW8

SW8

SW7

SW6

Lfvi

APFAPF

current controller

voltage controller

io

i*

vDC

*vDC

vcavtri

kif

Lss1kpwm

ilvo

io (k)* kca ioiavca(k)

Gos(s)

current current controllercontroller

va

fi

vDC

kvf

li

v* (k)

i * (k)

sin (k)

ev (k) vav (k)

Gav (z)

voltage voltage controllercontroller

current current looploop

iaiokif

1kad

icCD s

1

fv

+

+

+

+ ++

++

+ + +

+

+

−−

−−

+

− −

+

+ +

o

Gis (s)

a

b

c

o DC

Fig. 4 Circuit configuration and control strategy of bidirectionalAC/DC converter during outage modea APF circuitb Current loopc Voltage loop

IEE Proc.-Electr. Power Appl., Vol. 151, No. 1, January 2004 123

gain kca. The closed-loop transfer function of current loop isexpressed as:

io ¼kpwmkca

Lssþ kif kpwmkcai�o þ

1

Lssþ kif kpwmkcail ð17Þ

The second term of (17) shows that il is viewed as adisturbance. If the feed-forward compensator Gos(s) shownin Fig. 4b is set to 1/kpwm and the current controller kca is setto high proportional gain, then disturbance is eliminated forvo and il. Thus the resulting current loop can be furthersimplified to a constant gain:

ioi�o¼ 1

kifð18Þ

The control voltage vca(k) generated from the current loopcan be derived as:

vcaðkÞ ¼ ½i�oðkÞ � ioðkÞ�kca þvoðkÞkpwm

ð19Þ

The outer voltage loop is shown in Fig. 4c. A digital PIvoltage controllerGav(z) is used. Using procedures similar tothose described previously in the PFC control system, thecomposite voltage loop control algorithm can also beobtained as:

vavðkÞ ¼kapfevðkÞ � evðk � 1Þgþ kaievðkÞ þ vavðk � 1Þ ð20Þ

where kap and kai are the proportional and integral gain ofthe PI controller. By letting feed-forward disturbancecompensator Gls(s)¼ kif, disturbance il is cancelled. Then,the output current command i�oðkÞ of the DC/AC voltageinverter is computed by multiplying i�oðkÞ with unit vectorsin(k) of the output voltage vo(k). This gives:

i�oðkÞ ¼ vavðkÞ sinðkÞ � kif ilðkÞ ð21ÞEquation (20) is used to determine i�oðkÞ. Duty ratios d1aand d2a are obtained by substituting (19) into (12).

3.3 DC/AC voltage inverterThe circuit diagram and control block diagram of a voltageinverter are shown in Fig. 5 [13–15]. The inverter has twocontrollers: one is for the inner current loop and the other isfor the outer voltage loop. The multi-loop control techniquewith feed-forward control is used to make the outputvoltage vo follow the sinusoidal voltage command v�o closely.The duty ratios d1i and d2i of upper switches SW5 (SW8) andSW7 (SW6) are:

d1i ¼1

2þ vci2vtri

d2i ¼1

2� vci2vtri

ð22Þ

Applying Kirchhoff’s law on the AC output side gives:

Lodifdt

¼ vi � vo ð23Þ

where vi is the PWM inverter output voltage, which may beobtained from duty ratios d1i and d2i as:

vi ¼ ðd1i � d2iÞVDC ¼ kpwmvci ð24Þwhere kpwm¼ vDC/vtri denotes the inverter gain. FromFig. 5a, the current equation can be obtained as:

Codvodt

¼ if � io ð25Þ

where if is the inductor current and io is the output current.Using (22)–(25), the multi-loop control system of theinverter output voltage can therefore be developed as

shown in Figs. 5b and c. kvf and kif are the voltage andcurrent sensor scaling gains. The voltage controller andcurrent controller can be realised by proportional gains kvi

and kci to simplify the control algorithm. As shown inFig. 5b, if feed-forward disturbance compensator Gvs(s)satisfies:

GvsðsÞ ¼ 1=kpwm ð26Þthe disturbance of output voltage vo can be cancelled. Thetransfer function of the current loop can be simplified as:

ifi�f

¼ 1

kifð27Þ

The desired control voltage vci(k) is

vciðkÞ ¼ ½i�f ðkÞ � if ðkÞ�kci þvoðkÞkpwm

ð28Þ

The output current io also acts as a disturbance to thevoltage loop shown in Fig. 5c. Likewise, io can be eliminatedby setting:

GisðsÞ ¼ kif ð29ÞTo produce an output voltage with zero steady state error, acommand feed-forward controller Gff(s) is used, derived as:

Gff ðsÞ ¼kifCo

kvfð30Þ

ioif

vDC

SW5

SW5

SW6

SW7

SW8

SW7

SW6 SW8

ilLo

vi

currentcontroller

voltage controller

if

i * (k)

vo

vci

vo loadloadextra extra loadload

vtri

Co

a

b

c

kif

Gvs (s)

Los1kpwm

vo

kci ifvci (k) vicurrent current

controllercontroller

fi

kvf

kvi Cos1

kif

1ev (k)vo

voltage voltage controllercontroller

current current looploop

v* (k)

if

Zload

1Gff (z ) Gis (s)io

fv

+

+

−+

+−

+

+ +

+++

+

+

f

i * f

v*o

o

i* (k)f

v* (k)o

−+

+++

Fig. 5 Circuit configuration and control strategy of DC/ACvoltage invertera Inverter circuitb Current loopc Voltage loop

124 IEE Proc.-Electr. Power Appl., Vol. 151, No. 1, January 2004

Thus the inductor current command i�f ðkÞ is represented by:

i�f ðkÞ ¼½v�oðkÞ � voðkÞ�kvi

þ kcfCo

kvfv��ðkÞ þ kif ioðkÞ ð31Þ

where v�oðkÞ is the sinusoidal voltage command.Substituting (31) into (28), the control voltage vci(k) can

be obtained. The duty ratios d1i and d2i at every switchingperiod can then be calculated by substituting (28) into (22).Note that the DSP software design is easy to implement

as the multi-loop control algorithms during normal andoutage modes have similar control structures.

4 Simulated and experimental results

The closed-loop UPS system has been tested by bothsimulation and experiment. An experimental prototypeusing a digital signal processor TMS320F240 digitalcontroller was built. The sampling frequency fc and fv ofthe current controller and voltage controller were set to18kHz and 9kHz, respectively. The PWM switchingfrequency fs was 18kHz. The UPS specifications and circuitparameters are:

AC input voltage : 110 Vrms; 60HzACoutput voltage : 110 Vrms; 60Hz

DCbus voltage : VDC ¼ 210VPower factor : � 0:98

Input filter inductance : Ls ¼ 3:0mHSwitching frequency fs: 18 kHz

Output filter capacitor :Co ¼ 30 mFDCcapacitor : CDC ¼ 940 mF

Output filter inductor : Lo ¼ 1:0mHDCLoad :RDC ¼ 80O

In the design of these controllers, the controller parameterswere chosen to ensure that satisfactory dynamic responsewas obtained over the operating range of the UPS system.The controllers were tested systematically in the operatingconditions given in Table 1.

Figure 6 shows the line voltage vs and line current iswaveforms for the PFC rectifier during normal mode. Itconfirms that, under normal mode condition, the PFCrectifier can obtain high power factor line current with lowcurrent harmonics. The line current is controlled to besinusoidal and in phase with the AC mains voltage while innormal mode. Line current harmonic components show aTHD of 3.16% and an input power factor of 0.995. TheUPS output voltage shows good regulation with low THDwhen feeding nonlinear loads, as shown in Fig. 7. Despite adistorted current io, the measured THD of inverter outputvoltage vo is 4.53%. Figure 8 shows that the bidirectionalAC/DC converter acts as an APF and produces the currentrequired by a nonlinear load in outage mode. Inverter

output voltage vo, load current il, active filter current ia andoutput current io are presented in Fig. 8. Active filter currentia shows almost the same harmonic components as loadcurrent il. Thus inverter output current io becomessinusoidal with nearly unity power factor at the DC/ACvoltage inverter side. The THD of the DC/AC voltageinverter output current io is 6.89%.Table 2 lists the measured values during normal and

outage modes. It also shows that line current THD, reactivepower Q and UPS apparent power S are significantlydecreased when the UPS operates at outage mode, clearlyshowing the effectiveness of the proposed UPSsystem. Consequently, the proposed UPS system ensures353W real output power to the existing load, but is alsocapable of delivering an additional 143W real power to anyadditional load. Thus the proposed UPS exhibits excellentperformance for nonlinear loads. The transitions fromnormal mode to outage mode and vice versa are shown inFigs. 9 and 10. The above experimental results all giveconsistent agreement with simulated results, confirming

Table 1: Parameters of the controllers

PFC controller(normal mode)

kpp¼ 0.6, kpi¼0.92, kcp¼30, kvf¼ 0.02,kif¼ 0.21, kad¼ 0.51, kpwm¼ 42

APF controller(outage mode)

kap¼ 0.091, kai¼0.03, kca¼30, kvf¼ 0.02,kif¼ 0.2, kad¼ 0.51, kpwm¼ 42

Voltage controller(voltage inverter)

kvi¼ 0.6, kci¼20, kvf¼ 0.02, kif¼ 0.2,kpwm¼42

vs

vsis

is

100

00 2.0k

dist

ortio

n, %

frequency, Hz

a

b

c

Fig. 6 Simulated and experimental results of AC line voltage vs

and current is in normal mode (vs 50 V/division, is 5 A/division, time5 ms/division)a Simulated resultb Experimental resultc Harmonic spectrum of line current is; THD¼ 3.16%

IEE Proc.-Electr. Power Appl., Vol. 151, No. 1, January 2004 125

good performance compared with the conventional UPSapproach.

5 Conclusions

This paper has presented a online UPS system with built-inbidirectional AC/DC converter with improved performancerelative to that of a conventional UPS system. ADSP-basedUPS prototype has been implemented to verify the multi-loop digital control schemes. The control systems aredescribed and simulations presented to verify the perfor-mance of the proposed system. Simulation results fornormal mode show a near-unity input power factor and awell-regulated output voltage to the load. The UPS systemshows a well-regulated output voltage and an outputcurrent in phase with the output voltage during outage.Experimental results are in good agreement with simulatedresults, confirming the effectiveness of the proposed UPSand improved operating characteristics compared withthose of conventional online UPS systems. Advantages ofthe proposed system include high real output power

vo

io

a

b

vo

io

100

00 2.0k

dist

ortio

n, %

frequency, Hzc

Fig. 7 Simulated and experimental results of DC/AC inverteroutput voltage vo and output current io in normal mode (vo 50 V/division, io: 5 A/division, time 5 ms/division)a Simulated resultb Experimental resultc Harmonic spectrum of voltage vo; THD¼ 4.53%

vo

vo

il

ia

io

il

ia

io

100

00 2.0k

dist

ortio

n, %

frequency, Hzc

b

a

Fig. 8 Simulated and experimental results of UPS system duringoutage mode (inverter output voltage vo, 100 V/division; load currentil, 10 A/division; bidirectional AC/DC output current ia, 5 A/division;inverter output current io, 5 A/division; time 5 ms/division)a Simulated resultb Experimental resultc Harmonic spectrum of inverter output current io; THD¼ 6.89%

Table 2: Operating parameters at outage mode

ConventionalUPS

Proposed UPSsystem

Output current io THD % 71.62 6.89

Output power factor 0.707 0.991

Real power P 353W 353W

Reactive power Q 357 VAr 45 VAr

Apparent power S 500VA 356VA

Inverter voltage vo RMS 110V 110V

Inverter output current io RMS 4.48A 3.21A

126 IEE Proc.-Electr. Power Appl., Vol. 151, No. 1, January 2004

capacity, full utilisation of the power converter and lowsystem cost per unit of real output power.

6 Acknowledgments

The authors wish to thank Dr. J.F. Chen for offeringmany useful suggestions concerning the research in thispaper.

7 References

1 Hirachi, K., Sakane, M., Matsui, T., Kajima, A., and Nakaoka, M.:‘Cost-effective practical developments of a high performance andmulti-functional UPS with new system configurations and theirspecific control implementations’. Proc. IEEE Power electronicsspecialist conf. (PESC), 1995, pp. 480–485

2 Chen, J.F., and Chou, C.L.: ‘Combination of voltage-controlled andcurrent-controlled inverter for UPS parallel operation’, IEEE Trans.Power Electron., 1995, 10, (5), pp. 547–558

3 Krishnan, R.: ‘Design and development of a high frequencyon-line uninterruptible power supply’. Proc. IEEE Industrialelectronics, control, and instrumentation Conf. (IECON), 1995,pp. 578–583

4 Kamran, F., and Habetler, T.G.: ‘A novel on-line UPS with universalfiltering capabilities’, IEEE Trans. Power Electron., 1998, 13, (3),pp. 410–418

5 Joos, G., Lin, Y., Ziogas, P.D., and Lindsay, J.F.: ‘An on-line UPSwith improved input-output characteristics’. Proc. IEEE Appliedpower electronics Conf. (APEC), 1992, pp. 598–605

6 Von Jouanne, Enjeti, P.N., and Lucas, D.J.: ‘ DSP control of high-power UPS systems feeding nonlinear loads’, IEEE Trans. Ind.Electron., 1996, 43, (1), pp. 121–125

7 Kazerani, M., Ziogas, P.D., and Joos, G.: ‘An AC-to-DCactive current waveshaping technique for solid-state input powerfactor conditioners’, IEEE Trans. Ind. Electron., 1991, 38, (1),pp. 72–78

8 Salmon, J.C.: ‘Techniques for minimizing the input current distortionof current-controlled single-phase boost rectifiers’, IEEE Trans. PowerElectron., 1993, 8, (4), pp. 509–520

9 Spiazzi, G., and Lee, F.C.: ‘Implementation of single-phase power-factor-correction circuits in three-phase application’, IEEE Trans. Ind.Electron., 1997, 44, (3), pp. 365–371

10 De Souza, F.P., and Barbi, I.: ‘ Power factor correction of linear andnonlinear loads employing a single phase active power filter based on afull-bridge current source inverter controlled through the sensor of theAC mains current’. Proc. IEEE Power electronics specialist Conf.(PESC), 1999, pp. 387–392

11 Singh, B., Haddad, K.A., and Chanadra, A.: ‘A review of active filtersfor power quality improvement’, IEEE Trans. Ind. Electron., 1999, 46,(5), pp. 960–971

12 Liang, T.J., Shyu, J.L., and Chen, J.F.: ‘High real output poweron-line UPS system with built-in reactive power compensation’.Proc. IEEE Power electronics specialist conf. (PESC), 2001,pp. 1555–1560

13 Ryan, M.J., and Lorenz, R.D.: ‘Control topology options forsingle-phase UPS inverters’, IEEE Trans. Ind. Appl., 1997, 33, (2),pp. 493–501

14 Abdel_Rahim, N., and Quaicoe, J.E.: ‘Analysis and design of amultiple feedback loop control strategy for a single-phase voltage-source UPS inverter’, IEEE Trans. Power Electron., 1996, 11, (4),pp. 532–541

15 Ito, Y., and Kawauchi, S.: ‘Microprocessor-based robust digitalcontrol for UPS with three-phase PWM inverter’, IEEE Trans. PowerElectron., 1995, 10, (2), pp. 196–204

vs

vo

io

il

is / ia

is ia

Fig. 9 Experimental results of UPS system during suddentransition from normal to outage mode

ia / is

vs

vo

io

il

ia is

Fig. 10 Experimental results of UPS system during suddentransition from outage to normal mode

IEE Proc.-Electr. Power Appl., Vol. 151, No. 1, January 2004 127


Recommended