Improved Efficiency & Reliability for Data Center Servers Using Immersion Oil Cooling

Date post: 14-Dec-2014
Category:
Upload: cheryl-tulkoff
View: 165 times
Download: 3 times
Share this document with a friend
Description:
•Immersion Oil Cooling Technology Overview •Data Center Efficiency •Cost & Size Benefits •Technology Challenges •Reliability Enhancements •Summary •Challenges & Next Steps
56
Improved Efficiency & Reliability for Data Center Servers Using Immersion Oil Cooling Cheryl Tulkoff & Chris Boyd [email protected] [email protected] May 2013 Las Vegas, Nevada
Transcript
Page 1: Improved Efficiency & Reliability for Data Center Servers Using Immersion Oil Cooling

Improved Efficiency & Reliability for Data Center Servers Using Immersion

Oil Cooling

Cheryl Tulkoff & Chris Boyd

[email protected]

[email protected]

May 2013 Las Vegas, Nevada

Page 2: Improved Efficiency & Reliability for Data Center Servers Using Immersion Oil Cooling

• Immersion Oil Cooling Technology Overview

• Data Center Efficiency

• Cost & Size Benefits

• Technology Challenges

• Reliability Enhancements

• Summary

• Challenges & Next Steps

Agenda

Page 3: Improved Efficiency & Reliability for Data Center Servers Using Immersion Oil Cooling

• Not a new concept! – Direct liquid immersion

cooling has been used within IBM for over 20 years to cool high powered chips on multi-chip substrates during electrical testing prior to final module assembly.

– Early supercomputers relied on liquid cooling technologies. • Cray 2 supercomputer

Liquid Immersion Cooling

http://www.electronics-cooling.com/1996/05/direct-liquid-immersion-cooling-for-high-power-density-microelectronics/

Page 4: Improved Efficiency & Reliability for Data Center Servers Using Immersion Oil Cooling

• Liquid Submersion Blade Server – LiquidCool Solutions (Hardcore

Computer) Supports High Frequency Trading with Liquid Submersion Cooled Computers • Released in 2010

– 2012: LSS is the world’s first rack-mounted total liquid submerged server. The system’s patented liquid submersion cooling technology promises improvements in speed, performance, reliability and latency, while reducing environmental impact.

Liquid Immersion Cooling Example

http://www.liquidcoolsolutions.com/

Page 5: Improved Efficiency & Reliability for Data Center Servers Using Immersion Oil Cooling

Cooling Using Dielectric Oil

1200X more

effective at

removing

heat than

air

Oil costs ~$500 per 55 gallon barrel, ~35C

Page 6: Improved Efficiency & Reliability for Data Center Servers Using Immersion Oil Cooling

Tanks, Not Racks

Tanks can

dissipate

40kW of

power or

more

Page 7: Improved Efficiency & Reliability for Data Center Servers Using Immersion Oil Cooling

Business Value of Immersion Technology

• Greatly reduced capital and operating expense vs. conventional data centers

• Data center can be built in non-traditional facilities, including transportable “pods” – No need for air conditioning, raised floors or

chemical fire suppression

• No impact on software or network infrastructure – Retraining of support personnel not required

• A truly “green” solution • Reliability Enhancements

Will redefine

how data

centers and

servers will

be built in

the future

Page 8: Improved Efficiency & Reliability for Data Center Servers Using Immersion Oil Cooling

Typical Data Center Operating Costs Profile

8%

13%

18%

4%

57%

NetworkingEquipment

Power

Power Distribution& Cooling

OtherInfrastructure

Servers

Power costs represent 25-40%

of monthly operating expenses

3 yr. Server; 10 yr. Infrastructure Amortization

Page 9: Improved Efficiency & Reliability for Data Center Servers Using Immersion Oil Cooling

Power Usage Efficiency (PUE)

PUE = Total Facility Power

IT Load

Total Facility Power

Power • Switchgear • UPS • Battery Backup • Lighting • Etc.

Cooling • Chillers • CRACs • Etc.

IT Load • Servers • Switches • Storage • Etc.

Any energy expended other than

that to drive the IT Load

contributes to inefficiency

Page 10: Improved Efficiency & Reliability for Data Center Servers Using Immersion Oil Cooling

Industry PUE Profile

0

5

10

15

20

25

30

35

40

45

1-1.39 1.4-1.69 1.7-1.9 2.0-2.9 3.0-3.9 4.0 + Don'tKnow

n=300

Source: Digital Realty Trust 2012 Survey

%

Immersion Oil Cooling

PUE ≤ 1.08 Average PUE:

•Per Uptime

Institute: 1.8

•Per EPA

Energy Star

Program: 1.91

Page 11: Improved Efficiency & Reliability for Data Center Servers Using Immersion Oil Cooling

Huge Energy and Cost Savings

Fan-less, ultra-

efficient data center

Page 12: Improved Efficiency & Reliability for Data Center Servers Using Immersion Oil Cooling

Traditional Data Center vs. Immersion Cooled Data Center

Identical Processing Capacity Comparison (10,000 servers)

Traditional Data Center*

Immersion Oil Cooling Data Center

Data Center Size (sq. ft.)

Power Consumption

(MW)

12,500

6.88

4,000

3.12

32%

45%

Of the Size

Of the Power

*Assumes PUE of 1.8 and Dell PowerEdge R520 servers

Page 13: Improved Efficiency & Reliability for Data Center Servers Using Immersion Oil Cooling

Traditional Data Center vs. Immersion Cooled Data Center

*Assumes PUE of 1.8 and Dell PowerEdge R520 servers

Identical Power Comparison (5 MW)

Traditional Data Center*

Immersion Oil Cooling Data Center

Number of Servers

16,030

6,430

7,275

9,100

120%

71%

More Processing Capacity

Of the Size

Data Center Size (sq. ft.)

Page 14: Improved Efficiency & Reliability for Data Center Servers Using Immersion Oil Cooling

• Simpler than typical air cooling system

• Improvements in the instrumentation and reporting in progress

Oil Cooling System Components Schematic

Page 15: Improved Efficiency & Reliability for Data Center Servers Using Immersion Oil Cooling

Preparation: Works With Any OEM Server

Prep takes less

than

10 minutes

Remove fans

Replace thermal paste

Use sealed or solid-state drives

Page 16: Improved Efficiency & Reliability for Data Center Servers Using Immersion Oil Cooling

Server Maintenance

• If you do get thermal paste into the system, it can be easily filtered by temporarily replacing the catch screen in the pump module with a 2 um filter.

– The thermal paste dissolves in the oil, making it cloudy.

• How do you work on a server in immersion oil cooling?

– Pull the server out, wait for it to drain

– Keep a paper towel nearby

– Potential need to clean if returned to a repair center

Page 17: Improved Efficiency & Reliability for Data Center Servers Using Immersion Oil Cooling

Optimized Loading Design • The SLED: custom server design takes optimal

advantage of the cooling technology – Based on experience gained from more than 18 months of

experience operating an immersion cooled data center

Page 18: Improved Efficiency & Reliability for Data Center Servers Using Immersion Oil Cooling

• Skepticism from OEMs – This is changing--Intel's recent positive report – SuperMicro Computer is developing SKUs for immersion boards

• http://www.datacenterknowledge.com/archives/2012/03/22/submerged-supermicro-servers-accelerated-by-gpus/

– Network gear manufacturers are lagging behind server vendors

• Disk Arrays – Current hard disks leak, and the oil crashes the heads – Solid State Drives (SSDs) are expensive – Waiting to test the new Western Digital helium filled drives when

they ship next year, hermetically sealed • http://www.hgst.com/press-room/2012/hgst-announces-radically-new-

helium-filled-hard-disk-drive-platform

Some Immersion Technology Challenges

Page 19: Improved Efficiency & Reliability for Data Center Servers Using Immersion Oil Cooling

• Proving technology

• Impact on optical components – TTCP transfer times and

ping times are very similar crossing the switch network, regardless of whether the optical interfaces are immersed

– In all cases, no pings were lost • Coolant immersion does not

appear to adversely affect the error rate on the links.

Immersion Technology Challenges

Page 20: Improved Efficiency & Reliability for Data Center Servers Using Immersion Oil Cooling

• Impact on RF components?

• Performance Impacts? – None detected yet

– Trials underway

– Image of Ethernet switch which has been running immersed since January 2011

Immersion Technology Challenges

Page 21: Improved Efficiency & Reliability for Data Center Servers Using Immersion Oil Cooling

Potential Reliability Enhancements

Minimizes Common Operational Issues like: •Overheating •Temperature

swings •Server fan

failures •Dust •Air quality •Corrosion •Whiskers

Page 22: Improved Efficiency & Reliability for Data Center Servers Using Immersion Oil Cooling

• Tin Whisker Mitigation – Arcing

• Zinc Whisker Mitigation • Reduction in Corrosion & Electrochemical

Migration – Corrosive exposure reduction – Moisture reduction

• Environmental contaminant reduction – Dust, debris, particulates

• More stable and even thermal environment – No hot spots

Reliability Enhancements

Page 23: Improved Efficiency & Reliability for Data Center Servers Using Immersion Oil Cooling

Tin Whiskers Tin whiskers are hair-like single crystal metallic

filaments that grow from tin films.

Their unpredictability is the greatest concern.

The Aerospace and Defense industries consider tin whiskers the, “greatest reliability risk associated with Pb-free electronics”.

Manhattan project phase 2 report

Page 24: Improved Efficiency & Reliability for Data Center Servers Using Immersion Oil Cooling

What are the potential failure modes?

Direct Contact Causes an electrical short (arcing)

Requires growth of sufficient length and in the correct orientation

Electromagnetic (EM) Radiation Emits or receives EM signal and noise at

higher frequencies

Deterioration of signal for frequencies above 6 GHz independent of whisker length

Debris Whisker breaks off and shorts two leads

(primarily during handling)

These can be mitigated by immersion oil

Courtesy of P. Bush, SUNY Buffalo

Observation of tin whisker debris as reported to NASA from Sanmina-SC

DfR Solutions

Page 25: Improved Efficiency & Reliability for Data Center Servers Using Immersion Oil Cooling

Response to Tin Whisker Risk Biggest challenges are high reliability

applications with high volumes and strong cost pressures Examples: Enterprise servers, external

defibrillators, first-responder radios, industrial process monitoring, etc.

Every mitigation must be looked at closely in

regards to need and cost Requires a clear understanding of why and when

tin whiskers occur

Page 26: Improved Efficiency & Reliability for Data Center Servers Using Immersion Oil Cooling

• “If you manage a data center, especially one that sits on a raised floor, zinc whiskers might eventually have an impact on your operations.”

• “The whisker formation process consists of an unpredictable incubation period—typically lasting months or even years without any growth at all—followed by a period of growth at rates as high as 1 mm/year.”

• “Unfortunately, accelerated techniques do not currently exist to predict if, when, and to what extent a zinc-coated surface will produce zinc whiskers.” – Excerpts from paper by Jay Brusse and Michael Sampson

Zinc Whiskers: Hidden Cause of Equipment Failure

Page 27: Improved Efficiency & Reliability for Data Center Servers Using Immersion Oil Cooling

Zinc Whiskers

Zinc whiskers (here, magnified100×) growing on the underside of a raised-access floor tile. Image courtesy of Jay Brusse et al

• Failure mechanism appears to be quite widespread

• Awareness by facility or data center management personnel appears to be limited

Page 28: Improved Efficiency & Reliability for Data Center Servers Using Immersion Oil Cooling

Why Worry about Contamination and Cleanliness?

• Believed to be one of the primary drivers of field issues in electronics today – Induces corrosion and metal migration

(electrochemical migration – ECM)

• Intermittent behavior lends itself to no-fault-found (NFF) returns – Driven by self-healing behavior – Difficult to diagnosis

• Pervasive – Failure modes observed on batteries, LCDs, PCBAs, wiring,

switches, etc.

• Will continue to get worse

Page 29: Improved Efficiency & Reliability for Data Center Servers Using Immersion Oil Cooling

Future of Contamination / Cleanliness Issues • Continued reductions in pitch between conductors will make

future packaging more susceptible

• Increased use of leadless packages (QFN, land grid array, etc.) results in reduction in standoff

– Will reduce efficiency of cleaning, which may lead to increased concentration of contaminants

• Increased product sales into countries with polluted and tropical environments (East Asia, South Asia, etc.)

– ECM occurrence very sensitive to ambient humidity conditions

• Pb-Free and smaller bond pads

– Require more aggressive flux formulations

Page 30: Improved Efficiency & Reliability for Data Center Servers Using Immersion Oil Cooling

What is ECM? • One definition

– Movement of metal through an electrolytic solution under an applied electric field between insulated conductors

• Electrochemical migration (ECM) can occur on or in almost all electronic packaging

– Die surface

– Epoxy encapsulant

– Printed board

– Passive components

– Etc.

Page 31: Improved Efficiency & Reliability for Data Center Servers Using Immersion Oil Cooling

• Temperature

• Moisture

• Contamination

• Voltage/Electrical Field

• Temperature, moisture, and contamination aspects can all be reduced and/or eliminated with immersion oil cooling

ECM Drivers

Page 32: Improved Efficiency & Reliability for Data Center Servers Using Immersion Oil Cooling

Sources of Contaminants

• Printed board fabrication process

– Insufficiently cured polymers

– Rinse water

• Printed board assembly processes

– Fluxes

– Handling

• Salts from human contact (KCl and NaCl)

• Storage and use environment

Page 33: Improved Efficiency & Reliability for Data Center Servers Using Immersion Oil Cooling

Contaminants: Storage & Environment

• Storage – Cleaning chemicals

– Outgassing

– Polymeric materials

• Use Environment – Dust, Debris, Zinc whiskers

– Moisture, Evaporated sea water

– Industrial pollutants – sulfur, etc.

• Filtered oil prevents these from accumulating

on electronics

Page 34: Improved Efficiency & Reliability for Data Center Servers Using Immersion Oil Cooling

Influence of Pollutants: Creepage Corrosion • Recent field issues with printed circuit

boards (PCBs) plated with immersion silver – Sulfur-based creepage corrosion

• Failures in customer locations with elevated levels of sulfur-based gases – Rubber manufacturing – Sewage/waste-water treatment plants – Vehicle exhaust fumes (exit / entrance

ramps) – Petroleum refineries – Coal-generation power plants – Paper mills – Landfills – Large-scale farms – Automotive modeling studios – Swamps

• Immersion oil would prevent this exposure!

P. Mazurkiewicz , ISTFA 2006

Page 35: Improved Efficiency & Reliability for Data Center Servers Using Immersion Oil Cooling

35

Creepage Corrosion Failure of ImAg

•Corrosion product is semi-conductive (resistance of about 1Mohm).

•Resistance decreases as humidity increases.

•Traces sensitive to leakage current trigger the system failure.

•Visual inspection required to identify failures (most are CNDs).

Initiation of

a short

Page 36: Improved Efficiency & Reliability for Data Center Servers Using Immersion Oil Cooling

Pollutants: Not Always in Industrial Settings

• Chinese Drywall Cited in Building Woes – The drywall is emitting sulfur-based gases that are corroding air-

conditioner coils, computer wiring and metal picture frames.

• Drywall blamed for A.C. failures – Air-conditioning coils have turned black, along with wiring, piping

and even silver jewelry.

– "We have definitely identified that a combination of sulfide gases are the cause of the corrosion," said Robert P. DeMott, managing principal of Environ.

– "Foul odors reported by people living in the homes may also be caused by the combination of sulfur gases being released from the drywall,

• Chinese drywall class action lawsuit – LEE COUNTY, Fla. - The Lawsuit was filed against Knauf Plasterboard

Tianjin Co., LTD, The Knauf Group, Rothchilt International Limited and the Banner Supply Company.

– Known as "Chinese Drywall", it was manufactured oversees and was made from waste materials. As a result, it emits sulfur compounds that corrode copper wiring and other metals found in homes. Copper Corroded by Sulfur flumes

Drywall Sulfur Fumes Blamed for A.C. & Electrical Equipment failures

Page 37: Improved Efficiency & Reliability for Data Center Servers Using Immersion Oil Cooling

Infra-Red Thermal Evaluation

D11 Alum Caps

Q16

Thermal Anomalies Detected - Q16 producing heat when is it supposed to be in an off state - sneak circuit detected

- D11 detected a hot spot that exceeded thermal limit Expect to see hot spot reduction and improved thermal uniformity using immersion oil cooling

Page 38: Improved Efficiency & Reliability for Data Center Servers Using Immersion Oil Cooling

Reliability Engineer

Qual Engineer

Test Engineer

Mechanical Engineer

Thermal Engineer

Software Reliability Modeling & Prediction Tool

How Hot it Too Hot?

• PCB Design • Temp Cycling • Vibration • Shock • Bending • In Circuit

Test • DFMEA • Thermal

Derating • Failure Rate

Page 39: Improved Efficiency & Reliability for Data Center Servers Using Immersion Oil Cooling

Thermal Modeling & Prediction

• Create Thermal Environment for a typical, air-cooled data center

• Create 2nd environment for immersion oil cooled data center

• Compare

• Correlate to longer term actual data

Page 40: Improved Efficiency & Reliability for Data Center Servers Using Immersion Oil Cooling

Thermal Modeling & Prediction Life Curves

Can do what if scenarios changing lifetime, acceptable failure rate, and thermal environment

Page 41: Improved Efficiency & Reliability for Data Center Servers Using Immersion Oil Cooling

Produces a

Failure Rate

EM

HCI

NBTI

TDDB

EM

HCI

NBTI

TDDB

EM

HCI

NBTI

TDDB

Acceleration Factors

Analysis of

Functional

Groups

Functional Group A Functional Group B Functional Group i

Simulated Device

Deconstruction

Device

Properties

Manufacturer

Testing

Functional Group A Functional Group B Functional Group i

Device

Accelerated

Failure Rate

o Models the simultaneous

degradation behaviors of

multiple failure mechanisms on

integrated circuit devices

o Devised from published research

literature, technological

publications, and accepted

degradation models from:

o NASA\JPL

o University of Maryland

o Semiconductor Reliability

Community

o Easy to use software solution by

multiple engineering disciplines

ICs – Lifetime Prediction & Impact of Temperature

Page 42: Improved Efficiency & Reliability for Data Center Servers Using Immersion Oil Cooling

• Intel tests oil immersion to cool servers – “If you are going to add a significant amount of capacity

and have systems with a lot of density and don’t have good air flow in your data center, this is worth looking at,” said Mike Patterson, a senior thermal architect for data centers at Intel.

– “We asked a lot of tough questions and they had pretty good answers for all of them so we put a pilot together,” said Patterson. “There’s almost an emotional reaction [against oil immersion] at first, so people say they would never do that, but when they see the potential [energy] savings, they see there’s something there,” he said.

Industry Evaluation – Intel Experience

Page 43: Improved Efficiency & Reliability for Data Center Servers Using Immersion Oil Cooling

• Intel plans to start developing motherboards optimized for immersion cooling.

• Various OEMs involved in server hardware are expected to create modified designs with oil immersion in mind as well.

• Intel also found that no computer components — processors, hard drives etc. – were damaged from the yearlong immersion in mineral oil.

Industry Evaluation – Intel Experience

http://green.blogs.nytimes.com/2012/09/06/cooling-a-computer-server-with-mineral-oil/

Page 44: Improved Efficiency & Reliability for Data Center Servers Using Immersion Oil Cooling

Has what it thinks is the best of both worlds: putting the whole server "blade" (the individual hardware component of a server "farm") inside a container full of a special liquid called Novec.

Industry Evaluations – Iceotope

http://www.nbcnews.com/technology/futureoftech/new-way-keep-pcs-cool-submerge-them-goo-1C8603909

Page 45: Improved Efficiency & Reliability for Data Center Servers Using Immersion Oil Cooling

Technology Summary

• Immersion cooling technology has been used previously in the computing and electric power industries

• More than 600,000 hours of server time logged by customers including one of the largest grocery chains in Texas and Texas Multicore

• Virtually unlimited heat density and scalability

• Using highly effective enviro-friendly fluid for cooling greatly improves server reliability

• Will be vital for “hot” CPUs currently in development

• Dramatically reduced carbon footprint

Page 46: Improved Efficiency & Reliability for Data Center Servers Using Immersion Oil Cooling

• Immersion oil cooling offers significant environmental, cost, performance, and reliability advantages.

– Reduces potential for failure in:

• Tin Whisker Mitigation via arcing

• Zinc Whisker Mitigation

• Corrosion & Electrochemical Migration (ECM)

• Moisture reduction

• Environmental contaminant reduction

• Provides stable and even thermal environment

Technology Summary

Page 47: Improved Efficiency & Reliability for Data Center Servers Using Immersion Oil Cooling

• Oil bath monitoring

– Water (primarily initial equipment insertion)

– Contaminants (over time, leaching out from cables, plastics, etc).

– Cleaning of assemblies if offsite repair required

Future Work – Questions & Challenges

Page 48: Improved Efficiency & Reliability for Data Center Servers Using Immersion Oil Cooling

• Optimum oil temperature – how was it determined (35C) and how low can it go?

• Does the oil affect the contact resistance of connectors, relay contacts, or other electro-mechanical interconnects over time? That is, does the oil penetrate the metal-to-metal interface and create an insulating layer?

• Test specifically to show that electrolytic capacitors are not affected over the long term by immersion. They are not hermetic and they use ethylene glycol as the main solvent with adipic acid as the main charge carrier. These may slightly dissolve in the oil

Future Work – Questions & Challenges

Page 49: Improved Efficiency & Reliability for Data Center Servers Using Immersion Oil Cooling

• Extra performance

– Oil immersion may enable over-clocking of processors in ways not possible with air cooling

• Humidity barrier

– Oil immersion might be a good solution for small businesses in humid regions of the world such as southeast Asia. With the oil, they could build their data center in a warehouse with a concrete floor and not need all of the traditional chiller or HVAC equipment

• NEBS and telecom applications

– Oil immersion can significantly extend ride through time in the event of a cooling system failure.

– Could be useful for telecom where uptime and excursion capability is critical.

• Reduces component temperatures

– Helps extend the life of life limited and high temp components such as electrolytic caps, FETs, and silicon ICs.

Future Work – Questions & Challenges

Page 50: Improved Efficiency & Reliability for Data Center Servers Using Immersion Oil Cooling

• Oil Monitoring & Breakdown

• Cleaning of assemblies if offsite repair required

Future Work – Questions & Challenges

Page 51: Improved Efficiency & Reliability for Data Center Servers Using Immersion Oil Cooling

• Use a high humidity environment – – Choose a couple of servers and place them in oil (experiment cell) and place a couple of servers in air

(control cell). – Place both the oil immersion tank and the air servers in the same high humidity atmosphere. – Something like 30 or 35C and 80% RH. – Review climate of some of the humidity capitols of the world like Mumbai, Delhi, Singapore, Shanghai,

Kuala Lumpur, etc. and design a test that is accelerated relative to them.

• Use thermocouples to show how oil immersion reduces temps of high temp components – calculations to show improved life, lower failure rate of key components such as silicon ICs, FETs,

electrolytic caps

• Do over-clocking analysis on the processor – if oil keeps the processor much cooler, could you trade off processor life for performance, i.e. over-

clocking? – If the processor temp is kept low in oil, you should be able to over-clock and get more performance for

the same expected lifetime, e.g. 5-7 years.

• Ride through – cut off the oil cooling system and study the ride-through time. – Compare ride through time of oil (at least 30 min to 1 hour) to the ride through time for an air cooled

data center (couple of minutes).

Potential Experiment Conditions

Page 52: Improved Efficiency & Reliability for Data Center Servers Using Immersion Oil Cooling

Speaker Biography

Cheryl Tulkoff has over 22 years of experience in electronics manufacturing with an emphasis on failure analysis and reliability. She has worked throughout the electronics manufacturing life cycle beginning with semiconductor fabrication processes, into printed circuit board fabrication and assembly, through functional and reliability testing, and culminating in the analysis and evaluation of field returns. She has also managed no clean and RoHS-compliant conversion programs and has developed and managed comprehensive reliability programs.

Cheryl earned her Bachelor of Mechanical Engineering degree from Georgia Tech. She is a published author, experienced public speaker and trainer and a Senior member of both ASQ and IEEE. She has held leadership positions in the IEEE Central Texas Chapter, IEEE WIE (Women In Engineering), and IEEE ASTR (Accelerated Stress Testing and Reliability) sections. She chaired the annual IEEE ASTR workshop for four years, is an ASQ Certified Reliability Engineer, and a member of SMTA and iMAPS.

She has a strong passion for pre-college STEM (Science, Technology, Engineering, and Math) outreach and volunteers with several organizations that specialize in encouraging pre-college students to pursue careers in these fields.

Page 53: Improved Efficiency & Reliability for Data Center Servers Using Immersion Oil Cooling

Co-Author Biography

• Chris Boyd, Chief Technology Officer, Midas Green Technology, LLC. Chris Boyd has 20+ years’ experience in the telecommunications industry as a network operator, system engineer, and technical trainer. He is the co-founder of Midas Green Technology, LLC, a managed hosting provider which deploys a new server immersion cooling technology for commercial users.

• Chris is a recognized technologist and is a frequently requested consultant for data center, hosting and telecommunications companies. Chris has extensive experience developing and implementing leading innovative technology solutions in network management, performance management and patents for packet telephony routing. Chris is also treasurer of the Electric Frontier Foundation - Austin, working to ensure the internet remains a “level playing”

• field for the end user.

• Chris received a degree from UT Dallas in May, 1989 with areas of specialization in communication, computer science, and management.

Page 54: Improved Efficiency & Reliability for Data Center Servers Using Immersion Oil Cooling

• 1. Danielson, R.D., Tousignant, L., and Bar-Cohen, A.,Saturated Pool

Boiling Characteristics of Commercially Available Perfluorinated Liquids, Proc. of ASME/JSME Thermal Engineering Joint Conference, 1987.

• 2. Bergles, A.E., and Bar-Cohen, A., Immersion Cooling of Digital Computers, Cooling of Electronic Systems , Kakac, S., Yuncu, H., and Hijikata,K., eds, Kluwer Academic Publishers, Boston, MA, pp. 539-621, 1994.

• 3. Mudawar, I., and Maddox, D.E., Critical Heat Flux in Subcooled Flow Boiling of Fluorocarbon Liquid on a Simulated Chip in a Vertical Rectangular Channel, Intl. J Heat and Mass Transfer, 32, 1989.

• 4. Chrysler, G.M., Chu, R.C., and Simons, R.E., Jet Impingement Boiling of a Dielectric Coolant in Narrow Gaps, IEEE Trans. CHMT-Part A, Vol. 18 (3), pp.527-533, 1995.

• 5. Danielson, R.D., Krajewski, N., and Brost, J., Cooling a Superfast Computer, Electronic Packaging and Production, pp. 44-45, July 1986.

References

Page 55: Improved Efficiency & Reliability for Data Center Servers Using Immersion Oil Cooling

• “Are Zinc Whiskers Growing in Your Computer Room?” R. Hill, Data Clean Corp.; http://www.dataclean.com/pdf/ zincwhiskers3.pdf.

• “Testing Your Mettle: Zinc Whiskers in the Data Center,”B. Brown, Network World, Nov. 2004, http://www.nwfusion.com/news/2004/110104widernetwhiskers.html

• Pesky ‘Whiskers’ Zap PCs in Secretary of State’s Office,” Aldo Svaldi, The Denver Post, 1 July 2004, pp. C-01. • • “Precautions Against Zinc Whiskers,” Compaq Corp., Power Requirements for Non-Stop Himalaya Servers—

429905-001, http://h71033.www7.hp.com/TechPubs/PDF/Power_Requirements/TPSEC05.pdf. • “What Nasty Little Things Are Lurking Inside Your Data Center?” S. Tucker, Unisys World Monthly, Nov. 2002;

http://www.unisysworld.com/monthly/2002/11/whiskers.shtml. • “Zinc Whisker Abatement,” Worldwide Environmental Services; http://www.wes.net/field_engineering_services-

zinc_ • whisker_detail.htm. • “Zinc Whiskers: Could Zinc Whiskers Be Impacting Your Electronics?” J. Brusse, Apr. 2003; http://

nepp.nasa.gov/whisker/reference/tech_papers/Brusse2003-Zinc-Whisker-Awareness.pdf. • “Zinc Whisker Contamination: A Paper on the Effect and Abatement of Zinc Whiskers in Data Processing Centers,”

D. Loman, HP Services; http://www.dataclean.com/pdf/ZincWhiskerWhitePaper.pdf. • “Zinc Whiskers Growing on Raised Floor Tiles are Causing Conductive Contamination Failures and Equipment • Shutdowns,” The Uptime Institute; http://www.upsite.com/TUIpages/tuiflashzinc.html. • “Zinc Whiskers on Floor Tiles,” Infinite Access Floors; http://www.accessfloors.com.au/zincwhiskers.htm. • “Zinc Whisker Induced Failures in Electronic Systems,” ERA Technology, Winter 2003,

http://www.era.co.uk/news/rfa_feature_06.asp. • “Whisker Alert,” Japan Electronics & Information Technology Industries Association (JEITA), Jan. 2002;

http://it.jeita.or.jp/infosys/info/whisker/ (in Japanese). • http://www.layerzero.com/Innovations/stainless_steel_hardware.html (Data Center & Zinc whisker mitigation)

Zinc Whisker References

Page 56: Improved Efficiency & Reliability for Data Center Servers Using Immersion Oil Cooling

Contact Information

Questions? Contact Cheryl Tulkoff,

[email protected], 512-913-8624

www.dfrsolutions.com

Connect with me in LinkedIn as well!

See the server dunking videos at http://www.midasgreentech.com/svlg/