+ All Categories
Home > Documents > INDEX [ ] · PDF fileleakage current may flow due to touching of open phase wire of service...

INDEX [ ] · PDF fileleakage current may flow due to touching of open phase wire of service...

Date post: 08-Mar-2018
Category:
Upload: vuongxuyen
View: 237 times
Download: 9 times
Share this document with a friend
41
Performa No. Particulars Remarks/Report SoP 001 Fatal & Non Fatal Accident Report Yly. FY 2011-12 SoP 002 Action taken report for safety measures complied for the accidents occurred Yly. FY 2011-12 SoP 003 Register for compiling the complaints classificationwise Yly. FY 2011-12 SoP 004 Actons or steps carried out by distribution licensee towards public awareness in the year Yly. FY 2011-12 SoP 005 Action taken report by the Redressal Committee Yly. FY 2011-12 SoP 006 Failure of Distribution Transformer. Yly. FY 2011-12 SoP 007 Failure of Power Transformer. Not Pertain to DISCOMs SoP 008 Sample Test result for Neutral Voltage Yly. FY 2011-12 SoP 009 Sample result for Voltage Variations Yly. FY 2011-12 SoP 010 Sample Test result for Harmonics Yly. FY 2011-12 SoP 011 A System Average Interruption Frequency Index (SAIFI) Yly. FY 2011-12 SoP 011 B System Average Interruption Duration Index (SAIDI) Yly. FY 2011-12 SoP 011 C Momentary Average Interruption Frequency Index (MAIFI) Yly. FY 2011-12 SoP 012 System Losses at EHT / 11 KV and below Yly. FY 2011-12 SoP 013 Meter Faults Yly. FY 2011-12 SoP 014 Statement Showing the ATC losses, Collection efficiency and Billing Efficiency Yly. FY 2011-12 SoP 015 Release of New Connections, status as on March'2010 Yly. FY 2011-12 SoP 016 Compensation Details Yly. FY 2011-12 INDEX
Transcript

Performa No. Particulars Remarks/Report

SoP 001 Fatal & Non Fatal Accident Report Yly. FY 2011-12

SoP 002 Action taken report for safety measures complied for the accidents occurred Yly. FY 2011-12

SoP 003 Register for compiling the complaints classificationwise Yly. FY 2011-12

SoP 004 Actons or steps carried out by distribution licensee towards public awareness in the year Yly. FY 2011-12

SoP 005 Action taken report by the Redressal Committee Yly. FY 2011-12

SoP 006 Failure of Distribution Transformer. Yly. FY 2011-12

SoP 007 Failure of Power Transformer. Not Pertain to DISCOMs

SoP 008 Sample Test result for Neutral Voltage Yly. FY 2011-12

SoP 009 Sample result for Voltage Variations Yly. FY 2011-12

SoP 010 Sample Test result for Harmonics Yly. FY 2011-12

SoP 011 A System Average Interruption Frequency Index (SAIFI) Yly. FY 2011-12

SoP 011 B System Average Interruption Duration Index (SAIDI) Yly. FY 2011-12

SoP 011 C Momentary Average Interruption Frequency Index (MAIFI) Yly. FY 2011-12

SoP 012 System Losses at EHT / 11 KV and below Yly. FY 2011-12

SoP 013 Meter Faults Yly. FY 2011-12

SoP 014 Statement Showing the ATC losses, Collection efficiency and Billing Efficiency Yly. FY 2011-12

SoP 015 Release of New Connections, status as on March'2010 Yly. FY 2011-12

SoP 016 Compensation Details Yly. FY 2011-12

INDEX

FH NFH FH FA NFH FH FA NFH

1 Sabarmati 0 7 22 30 15 22 30 22

2 Mehsana 0 4 7 17 3 7 17 7

3 Palanpur 1 3 6 16 2 7 16 5

4 Himatnagar 0 3 15 24 2 15 24 5

TOTAL 1 17 50 87 22 51 87 39

Name of areaSr. No.

Uttar Gujarat Vij Company Ltd ,Mehsana

ANNUAL REPORT- April-11 to March-12

YEAR :-2011-12

Performa - SOP 001 : Fatal and Non-fatal accident report for Year ending .

Cumulative since the April-11 of the current FY Year

NUMBER OF ACCIDENTS FOR THE YEAR (April-11 to March-12)

Departmental Out side

No.of accidents in the Year 2011-12

C:\Users\ubchauhan5032\Desktop\ANNUAL_SOP_Report-2011-12_

FA/FH/NFH

Dept / O/S

1 2 3 4 6 7 8 9 10 11 12

1 SBT Bhat Miss Diwaliben M Parmar App Age 19 yrs NFH O/S 21.02.11

Victim was moving with Iron Sheet(Patara),at new constucted house at linter level under the 11 KV Kasindra JGY feeder,Iron sheet touches the 11 kv line and got shock, Immediately admitted at Pvt hospital at A'bad & shifted to V S hospital on dtd 21.03.11 .No one had reported the accident but it

comes to knowledge of DE, Changodar as informed by police on dtd 31.03.11 at evening hrs.

Not Recd NA NA

Estimate for line shifting was paid on Date24.12.2010, Work completed on 26.02.2011,

Nil

2 SBT Iyava Shri Uday Ramnarayan Nai Age app 21 Yrs FH O/S 03.04.2011

12.00 noon Victim while drinking water from water cooler in premises of HT consumer R.B.Polymer (HT

connection No 17292),due to leakage in water cooler, he got electric Shock and died. Not Recd NA NA Nil

3 MSH Meu Buffalo FA 29.03.11 Due to Heavy wind, tree Branch fall on LT 1Phase 3 Wire line, So one live Conuctor broken & fall on small Buffalo,got electrocuted and met with FA.

Accident occurred due to breaking of Live LT conductor

Suggested to carry out Periodic maintenace of Line

Line maintenance including Tree cutting is done

Line maintenance including Tree cutting is done No

4 MSH Kansa Shri Thakor Sureshji Dharshiji Age:22 yrs. FH O/S 11.04.11

The victim was trying to prepare arrangement to fill up wheat waste in the tractor trolley with iron pipe. The tractor trolley was parked below the line of 11kv JGY Kansa feeder. As he lifted the iron pipe (

about 12 feet) ,it was touched to the live conductor of 11kv Line, he got electric shock. He was admitted to civil hospital patan but he died.( The distance beetween ground to 11 kv line is 16.5 feet .)

Accident occurred due to contact of iron pipe during lifting of iron pipe

Suggested to to aware the party about the safety rules of electricity.

guideline issued to party & his relatives to use safety norms while working below the

guideline issued to party & his relatives to use safety norms while working below the live line

No

5 HMT Debhari Solanki Babubhai Nathabhi FH O/S 12.4.11

Victim was lightning the bulb with flexible wire by inserting in the plug & flexible wire is extended with other thick wire and coating with plastic tap on that joint. While victim insert that wire in the plug the

plastic tap is open and he came in contact with that open joint and met with FH accident.

CEI Report not received

The consumr made aware to use wires of ISI quality & without joints.

No

6 HMT Tintoi Dabhi Atulbhai Laxmanbhi FH O/S 12.4.11The victim was plucking fruit from tree of Goras Ambali with the help of iron square channel(about 6

mtr long).While plucking Ambli from tree iron channel touched to 11 KV High Tension line of Bolundra Ag Feeder, he got shocked and died .(The distance beetween ground to 11 kv HT line is 6 mtr .)

CEI Report not received

Victim himself responsible No

7 SBT Randheja Tulsibhai Kalabhai solanki Helper Ag:42 Years NFH Dept. 16.4.11

L.I .with two helpers had gone to attend the fault of conductor broken of 11 KV VAVOL AG feeder. Line clear of vavol Ag feeder was taken by L.I .and earthing was provided on pole(27/3) . While doing

stringing of conductor by victim on pole he got induction shock & met with NFH accident. . Detail investigation is under progress . There is crossing of 11 kv kirtidham jgy feeder & 11 kv Vavol AG

feeder .

Not Recd NA NA Nil

8 HMT Bayad Kotwal Kodarbhai Shankarbhi NFH O/S

04.4.11 reporting dated 21.04.11

An unauthorise person was trying to theft by hooking the telephone wire with live LT line. At the same time victim got electrical shocked and fallen down from the pole and injured.

CEI report received

Victim has used anauthorised telephone wire for hooking so he himself is responsible

Victim himself responsible No

9 PLN DedhaYogeshkumar Mahendrabhai Suthar-1.5 years old

FH O/S 11.04.11 Due to internal fault of floor mill's motor in his premises,victim came in contact with leakage current of faulty motor, got electrocution & met with FA. Awaited Use ISI Marka appliances &

ELCB also 0

10 SBT Transad Buffalo FA 25.4.11 There is break in twin core service wire on the psc pole where accident took place. Momentory

leakage current may flow due to touching of open phase wire of service line to G.I wire of earthing of pole . Buffalo might came in contact with this leakage current ,got electrocution & met with FA.

Not Recd NA NA Nil

11 HMT Nanawada Bariya Hareshbhai Bhurabhai FH O/S 2.05.11

The Victim was climed on transfromer structure for doing suicide. And then touched to live Conductor R-phase which is coming from D.O. unit to HT Bushing of the X'mer, he got electrical shock & met

with FH Accident .

CEI Report not received

Victim himself responsible No

5

Detailed Reason of AccidentFinding of CEI/EI/ AEI

Remedies suggested by CEI / EI/ AEI in various cases

Type of AccidentWhether the remedy suggested is complied

Action taken to avoid recurrence of such Accident.

Date of occurance

Compensation Paid

Uttar Gujarat Vij Company Ltd ,MehsanaYEAR :-April -11 to March-12

Year 2011-12

Performa-SoP002:-Action taken report for safety measures complied for the accidents occurred

Sr. No.

CircleLocation

of Accident

Details of victim

FA/FH/NFH

Dept / O/S

1 2 3 4 6 7 8 9 10 11 125

Detailed Reason of AccidentFinding of CEI/EI/ AEI

Remedies suggested by CEI / EI/ AEI in various cases

Type of AccidentWhether the remedy suggested is complied

Action taken to avoid recurrence of such Accident.

Date of occurance

Compensation Paid

Sr. No.

CircleLocation

of Accident

Details of victim

12 PLN Janali Andabhai Virabhai Bhil 30-years old FH O/S 14.05.11at:

00.45 amVictim climbed on transformer center of 11 kv Janali-AG feeder for doing suicide& he came in contact

with R-phase LT Stud of Transformer and got shock & met with fatal accident..

IERules-1956 as per section-91 provide barbad wire on pole & section-35

IERules-1956 as per section-91 provide barbad wire on pole & section-35 provide denger board

Necessary instruction pass to field officer

Vide publicity & awarness required to consumers about live wire & power.

0

13 SBT Palundra

Shri Vishnusinh Parbatsinh Bihola , Age-Approx-21 years of Village: Palundra-Dhanpura

NFH O/S 16.5.11

On dt. 16/5/2011 at Loc No-20/6/180/3 (double pole structure) of 22kv Vasana Rathod(JGY) Feeder one DO fuse wire of D.O. was burnt.So victim reached at the place & tried to make connection of Do

fuse wire by bamboo of (4 mtr and 2 mtr Joint) for making power supply "ON". While making connection with bamboo, Do fuse wire comes in induction zone of near by phase,there was a big

fleshover occured and his chest part burnt, admitted to civil Hospital G'nagar.

Not Recd NA NA Nil

14 SBT Ambaliyasan

Shri Nareshbhai D.Vaghari NFH O/S 18.05.11

Tree cutting work on 11 kv Ambaliyasan AG Feeder was carried out in supervision of village helper Shri J.T. Rathva with the help of outsider Shri N.D.Vaghari .During tree cutting work J.T.Rathva

helper went to drink water on near by bore. Meanwhile by mistake victim climbed on other Chaluva AG feeder passing parallel to 11 kv Ambaliyasan AG Feeder , to remove "Galo vel" by hand from HT

wire, got electric shock,met with NFH accident

Not Recd NA NA Nil

15 SBT

Moti Adaraj--Bayamanu Paru

Thakor Prakashji Keshaji Age 15 Yrs FH O/S 17.5.11 There was a ceremony of Chamunda Mataji Temple. Victim during work of decoration ,came in

contact with leakage current from Microphone & got electric shock & met with FH Accident . Not Recd NA NA Nil

16 SBT VavolShri Brijpalsinh Jitendrasinh Waghela,age 14 years

FH O/S 23.05.11

A temporory connection was given to Shri V.C. Patel for construction purpose of his Salvik Homes Scheme at village Vavol. On Dated 23.05.2011, Victim boy was playing in garden with Grass cutter Machine ( Non Electric).A flexible wire of Tiles polishing Machine was laying on the Ground,passing

from Garden. While playing this flexible wire got cut due to grass cutter machine & so boy got electric shock and died on spot.

Not Recd NA NA Temp. Connection is disconnected. Nil

17 SBT KeralaShri Bhupatbhai Ladhubhai Makwana Age 18 Yrs

NFH O/S 24.05.11While levelling of roof of newly construction of house at village Kerala, Victim touched to live

conductor of 11 kv Chiyada Ag feeder of Keral S/S passing near it & met with Non fatal Human accident.Distance from Roof to line is about 1 feet Horizontally and 3.5 feet Vertically.

Not Recd NA NA

Notice issued to Shri Naranbhai Visabahi Beldar to stop construction vide letter No UGVCL/Tech/Bav I/945/25.05.2011 & FIR lodge vide 946 date 25.05.2011

Nil

18 PLN Kakoshi Shri Mafatlal Narsinhbhai Karen Age-38 years old FH Dept. 23.05.11

11 kv Vagharol-JGY feeder & 11 kv Pachakwada-AG feeder are going parallel at village kakoshi after emanating from 66 kv Kakoshi S/S . Maintenance of 11 KV Pachakwada-AG feeder was arranged by SDO and program was given to seven linestaff in supervision of shri K.N. Damor( L.I .).L/C of 11 kv Pachakwada-AG feeder was taken by Shri K.N.Damor (L.I.) at 9:30 a.m. & work was started .Victim Shri M.N. Karen (Helper)was climbed on 11 kv Vagharol-JGY feeder instead of 11 kv Pachakwada-

AG feeder at Location no-10 as wrong feeder name was written on that pole as 11 kv Pachakwada-AG feeder. So victim was climbed on wrong feeder due to wrong marking of feeder and he got

electric shock.He was shifted to JANATA hospital ,Patan for medical treatment but the victim was Died.

Awaited Inquiry for supervisior are under process. 373800

19 PLN Fatehpur Cow FA 24.05.11 One LT line phase conductor broken from LT Shackle insulator of PSC pole & fall on cow sitting below the Line & got electrocution & met with Fatal Accident. Awaited Maintenance work carried

out periodically. 0

20 SBTNidhrad (Munikrupa Chokdi)

Shri Harishbhai Bhagwanbhai Mena FH O/S

27.05.11 AT 17:30 Hrs

Rajeshkumar P.Patel(Land owner) had carried out refilling of the sand by 7' to 8' above the ground level for construction purpose and so the ground clearence from the side conductor of 11 kv shilaj

feeder passing just between his land was reduced to 12' to 13' . While lifting 13' to 14' long iron angle during working in land by victim Shree H.B.Mena, it accidentally touched to the live conductor of 11 kv Shilaj AG Dom feeder so he got electrocuted & met with FH accident Note-R.P.Patel had applied

for line shifting but he had not paid the estimate (Last date for payment was 11.05.2011 )

Not Recd NA NAline shifting work pole erected line will be shift before 10.11.11

Nil

21 MSH Hathipura Cow FA 1.06.11 Due to wind Pressure ,tree fall on LT 1 Phase 2 Wire line ,due to this live Conuctor broken & fall on small cow under the line came in contact with it & electrocuted.

CEI Report is not received

N/A as CEI report is not received

N/A as CEI report is not received

Line maintenance including Tree cutting is done No

22 HMT Bhanji ni vav Bullock FA 3.06.11 Due to cyclone LT line conductor snapped . Mean while the bullock was passing below the line and

came in contact with live wire, got electrocuted and met with FA.

CEI Report not received

Necessary Maintenance carried out No

FA/FH/NFH

Dept / O/S

1 2 3 4 6 7 8 9 10 11 125

Detailed Reason of AccidentFinding of CEI/EI/ AEI

Remedies suggested by CEI / EI/ AEI in various cases

Type of AccidentWhether the remedy suggested is complied

Action taken to avoid recurrence of such Accident.

Date of occurance

Compensation Paid

Sr. No.

CircleLocation

of Accident

Details of victim

23 SBT Bopal Shri Pravin Goswami VS Helper 36 Yrs NFH Dept 05.06.11

At present due to road widnening work by AUDA authority, 11 KV Ghuma feeder passing there was made dead. and also removed DO fuse,near Arohi Homes,The consumers of Ghuma feeder of

Changodar S/Dn ahead of it was fed from U/G Samarpan feeder( 4 to 5 poles ahead from DO.)The LT line of Arohi home T/C( Fed from U/G Samarpan feeder) was mounted below on HT pole of Ghuma

feeder, While restringing of LT wire,of Arohi Homes T/C, Victim's left arm touched to live 11 KV wire of Ghuma feeder charged from U/G Samarpan feeder & met with NFH Accident.

Not Recd NA NA Nil

24 HMT LalodaRathod Rajivkumar Bhagavandas Helper (V.S)

NFH Dept 05.06.11

As 11KV H.T. feeder was on fault, Shri R.B. Rathod-victim, alongwith the staff of Idar ® was attending the feeder.As live LT line was crossed to HT fdr nr. Shakti stone Ind. At that time Step by step

attending the fault of the 11 KV H.T. feeder by victim he met with non fatal electrical accident while trying to give jumper to the shackle pole of 11 K.V. H.T. feeder & got injured .

NOTE-LT line of 11 Kv Mohanpura feeder touched to conductor of 11 kv H.T. Feeder in Laloda village near Shakti Stone IND. And also LT line D.O. fuse was not diconnected so LT line power goes to HT

fdr

CEI Report not received

Provided 9 feet extension for line clearance between HT&LT line and line staff is educated for avoiding accident and utilisation of safety equipment

No

25 HMT Dhobhada Vaghela Mahendrasinh Ramsinh FH O/S 05.06.11

The D.O. fuse was droped out of 11KV Babsar Ag feeder. The victim was trying to switch on the D.O. switch by the lunger with the help of the wooden rod and at the same time due to any reason victim

got electrical shocked and met with FH Accident.

CEI Report not received

safety awarness given to villagers during SDO visit as well as in gramsabha programme

No

26 SBTJUDA ,Near.W/W X'mer

Buffalo FA

30.05.11 reporting dated 20.06.11

No any Leakage current found. Accident took place near Transformer centre. There is possibility of momentarily current may passed in earth wire due to unbalance current and poor earthing buffalo came in contact and got electrocuted. As per Post mortum report .As per P.M. report the death of

buffalo is due to electric shock.

Not Recd NA NA Nil

27 SBT Dashela Buffalo FA

04.6.11 reporting dated 20.06.11

Due to momentary leakage current may be passed through T/C center (Girder pole) to surrounding wet land. But at the time of site visit no any leakage current found. As per P.M. Report death of Buffalo is

due to electric Shock.Not Recd NA NA Nil

28 HMT Himatnagr Cow FA 16.06.11Due to Cyclone & rain , jumper of LT line touched with angle, resulted leakage current in said pole through earth. The said pole was supported by steel pole,leakage current also passes through said

steel pole. Meanwhile cow came in contact with this steel pole .

CEI Report not received

Rejumpering Done and necessary maint. Carried out. No

29 SBT Kathwada GIDC

Shri Hiteshbhai Dasarthbhai Bhavaiya NFH O/S 22.06.11

11 KV Odhav feeder line passing through compound wall of plot no 320 Kathawada GIDC. Plot owner has made kachha roof at warandha of plot & it’s out side edge is laying under 11 KV overhead line. Victim was working on the roof and while standing on roof comes in contact with 11 KV line & got

electrocution & met with NFH Accident.

Not Recd NA NA Notice issued to party No. 1162/ 27.6.11 nil

30 SBT

Hirajinu paru, Goraj ,NR.VTC X'MER

Buffalo FA 22.06.11 AT 17.30

4 SQ MM Cable broken suddenly and fell on the buffalo standing in the ''warandha''. The warandha was constructed under the LT cable span. Buffalo came in contact with live wire and got electrocuted. Not Recd NA NA Nil

31 SBT Giramtha BuffaloFA (2 Nos. of Buffaloes)

24.6.11 AT 8:00 a.m

In Thakor vas of village: Giramtha on dated:24.6.2011 monkeys were jumping on the ceiling of house of Shri Mansuri Abdulbhai Ummarbhai, due to which two conductor of LT wire came in contact and

broke down. At that time on the road two buffaloes of Shri Laxmanji Galabji Thakor were passing near the house of Mohanbhai Keshaji and came in contact with live LT wire and got electrocuted.

Not Recd NA NA LT ABC provided on 24.6.11 nil

32 SBT Balva Cow FA 28.06.11Scooter clutch wire(might be taken by bird) was fallen on phase wire of LT Line & second end of this

clutch wire was touch with bolt of U clamp. The earthing wire was tited with bolt of U clamp & thus the current passed through the earth wire & the Cow came in contact with earth wire , got electrocuted.

Not Recd NA NA Fuse removed Nil

33 HMT Rudardi Prajapati Hareshkumar Mangaldas Village Helper NFH Dept 23.6.11

While attending the Lighting complaint of no power at Village Rudardi, victim was trying to give service wire to LT line. Mean while his hand touched to Live LT line & got electrocution,as a result, he fall

down from the pole and met with NFH electrical accident. Victim had not isolated power supply from T/C.

CEI Report not received

Warning mamo issued to concern and line staff is educated for avoiding accident and utilisation of safety equipment

No

34 PLN Upaliyasara Buffalo FA 24.06.11

Fatal accident occurred to five nos Buffalows due to broken of 11kv Rafu-AG feeder conductor & observed conductor broken due to pin insulator fire & feeder was not tripped & not declared as a P/F.

So All five nos Buffalow one by one came with contact of live conductor ,got electrocuted. Awaited Maintenance work carried

out periodically. 0

35 HMT Antroli Parmar Bharatkumar Rajuji FH O/S

29.6.11 reporting dated 01.07.11

The driver parked his Truck under HT Line.In this span – the owner of the Quarry has filled quarry west at the middle of span and due to this clearance of line is reduced to 14’ 2” instead of 19

Feet.Mean Time Cleaner of the Truck climbed on the cabin and then stood on the cabin. At that time he came in contact with live HT Line( Nava JGY Fdr.) passing over the cabin and got electroculated

and Died.

CEI Report not received

The ground clearance increased by erection of Taba

No

FA/FH/NFH

Dept / O/S

1 2 3 4 6 7 8 9 10 11 125

Detailed Reason of AccidentFinding of CEI/EI/ AEI

Remedies suggested by CEI / EI/ AEI in various cases

Type of AccidentWhether the remedy suggested is complied

Action taken to avoid recurrence of such Accident.

Date of occurance

Compensation Paid

Sr. No.

CircleLocation

of Accident

Details of victim

36 MSH Khanusa Shri Shaileshji Pratapji Thakor NFH O/S

23.06.11 reporting dated 01.07.11

Victim was working for fitting metal sheets on the shed constrcted for Tobacco godown, the victim was working on shed by sitting and suddenly he get the call on his mobile and stand up during talking on the mobile and suddenly he came in the contact with induction zone of 11 KV line conductor passing

over the shed and he met with the non fatal electrical accident.Distance between lowest conductor and Shed is 7.0 ft. Distance between Lowest conductor and ground level is 18 ft.

CEI Report is not received

N/A as CEI report is not received

N/A as CEI report is not received

Notice has been given to the owner of premises to remove illegal construction

No

37 SBT Kalol Shri Punambhai Rajubhai Marwadi Age app 25 Yrs FH O/S 1.07.11

In consumer's premises (Chhapra),load side flexible wiring was wrapped with iron pipe,(Pipe support roof patara),Open Joint in flexible wire touched with iron pipe, so leakege current passes through

it.The victim come in contact of leakege current & got electrocuted & met with FH accident.Not Recd NA NA Nil

38 SBT Dhamatvan Cow FA 3.07.11 Due to rain & wind , one jumper of LT line was touching the angle of that girder pole, due to which

neutral power return on TC center & cow came in the contact of TC structure, got electrocuted Not Recd NA NA Rejumpering with insulated wire done on 3.7.11 Nil

39 SBT Jaliyamath

Shri Vikramsinh Udesinh Thakor-Indiranagar At Navanagar: Age app: 20 yrs.

FH O/S 5.07.11

Shri Vikramsinh Udesinh Thakor was working as "Mason" at Jalaram Tin Factory to errect wall and Shed.At the time of working he hold Babbler (Lelu) in his hand and standing on iron pipe support,Due to force of Babbler single phase service passing through very near to him, which is tied up with angle of shed, breaks and live service wire touches to angle of shed.He came in contact with live part and

got electrocuted.

Not Recd NA NA Nil

40 PLN Vedancha 2 Buffalo and Cow

FA ( 2 nos. of Buffaloes & Cow)

9.07.11An electrical Fatal accident occurred to Three animals due to pin insulator fire at location no 66/148 of 11kv Arbuda-JGY feeder & conductor broken due to lightining stroke . So Animals came with contact

of leakage current & met with FA.Awaited Maintenance work carried

out periodically. 0

41 MSH Madhi Buffalo FA 8.07.11

A Celling Fan found faulty in house of Chuhan Dhulaji Somaji , and A lekage current from the fan flows from fan to angle , and angle to steel shade of the house. A leakage current from the steel

shade of Chauhan Dhulaji Somaji' house flows to the steel shade of Chauhan Udaji Jivaji's gaman which is next to the chauhan dhulaji somaji's house, below which a buffalo of the owner is there. In the

gaman steel shade is also vertically put such that vertical steel shade come in the contact with the steel shade fixed above the gaman. so the leakage current was also flows to the vertical steel shade. Suddenly a buffalo in the gaman come in contact with the vertical steel shade and got electrocution.

CEI Report is not received

N/A as CEI report is not received

N/A as CEI report is not received

Consumer premises installtion must be with safety precautions,Consumer is instructed accordingly

No

42 MSH Mansa Cow FA 9.07.11In mansa city at takteshwar road near court building ,during Heavy rain & wind pressure LT conductor

snapped, &fall down on the ground . A cow passing through that area came in contact with live conductor & met with fatal electrical accident.

CEI Report is not received

N/A as CEI report is not received

N/A as CEI report is not received

Line maintenance done No

43 MSH Hathipura Cow FA 10.07.11Due to wind Pressure ,tree fall on LT 3 Phase 4 Wire Ag line . So one live Conductor broken &

fall on ground. A Cow grazing near this area and came in to contact with live conductor & got electrocuted.

CEI Report is not received

N/A as CEI report is not received

N/A as CEI report is not received

Line maintenance incuding Tree cutting is done No

44 MSH

Vahgarivas. Indiranagar chanasma

Cow FA 10.07.11

One stay wire is provided on the LT pole and 5 ltg and street light connection are given from the said pole. out of 5 ltg. connction ,One of the service wire of shri Vaghari Dhanjibhai Sakarabhai have the damaged insulation on service wire and open part of the service touched to the GI wire of the said service . When the cow was passing betn. pole & the stay ,the stay wire was vibrated & touched to the GI Wire of demage service, so the electric current was passed in stay wire between the portion

from stay insulator to ground level and when the cow came in contact with stay wire and got electroculated .

CEI Report yet not received

N/A as CEI report is not received

N/A as CEI report is not received

Rectification done by such pole by providing stay insulator as per standard electricity norms & damage service replaced

No

45 HMT Dhirpura Buffalo FA 8.7.11Due to service wire broken on loc. No-8 & touched with neutral wire of LT line. So leakage Current

passed towards the transformer centre through neutral wire. So leakage current passes to transformer earthing wire, Mean while Buffalow came in contact with earthing wire & got shocked & died.

CEI Report not received

Relace service wire & necessary maint. Carried out

No

46 HMT Sonasan Ta:prantij

Dahyabhai Manibhail Rawal FH O/S 12.7.11

Victim was cutting the branch of neem tree with metal rod ,mean time branch of the tree touched & fallen on the live line of 11kv Dalpur fdr & he got shocked through rod by wet branch . Then he falled

down & met with FH Accident

CEI Report not received

TREE CUTING CARRID OUT AT MAXXIMUM DISTANCE

No

47 HMTGambhirpura (Bhiloda)

Cow FA 9.07.11 Due to heavy rain & cyclon single phase service wire- phase wire burnt & touch with "D" clamp on the pole. The same pole is wet due to heavy rain so current passes through the wet pole. Mean while A

cow passes near the pole & came in contact with the pole and got shocked and died

CEI Report not received

Service wire replaced & lt jumpering done. No

48 HMT Mau (Tanda-2) Buffalo FA 10.7.11

Due to heavy rain & cyclon transformers LT side cable of R phase burnt & touch to transformer body. So leakage current passes in earthing wire through transformer. Mean while the Buffalo passes near transfomer centre & came in contact with earthing wire of transformer centre & got shocked and died.

CEI Report not received

Transformer's LT cable replaced & transformer maint. Done.

No

FA/FH/NFH

Dept / O/S

1 2 3 4 6 7 8 9 10 11 125

Detailed Reason of AccidentFinding of CEI/EI/ AEI

Remedies suggested by CEI / EI/ AEI in various cases

Type of AccidentWhether the remedy suggested is complied

Action taken to avoid recurrence of such Accident.

Date of occurance

Compensation Paid

Sr. No.

CircleLocation

of Accident

Details of victim

49 HMT Janali Fanat Popatbhai Jivabhai FH O/S 9.7.11 During night hours illegal power given to the fencing of cotton farm by direct hooking from the

line.Mean while victim passed near that fencing & came in contact with live fencing wire and got electrocuted & died .

CEI Report not received

Letter given to Police station : BSD/tech/1243 Dt:13.7.11 regarding party used illegal power so acci. occurred

No

50 SBT Viramgam CowFA (2 no. of Cows)

9.7.11Due to heavy rain & wind at night time , a twin core service wire phase came in contact with a tubular

pole.The 2 cows passing nearby the pole & nearby accumulated water & came in contact with leakage current & got electrocuted.

Not Recd NA NA Preventive maintenance carried out nil

51 SBT

Fatepura-Vachlu paru at Pethapur

Shri Pravinsinh Gulabsinh Parmar FH O/S 20.6.11

At village :Fatepura-Vachlu paru at Pethapur,near bank of river Sabarmati, there is a single phase connection of Ramesh Gopiji Vanraja. From this connection the outgoing cable of meter extended for office use of weighing scale and flexible opened-break wire used for supply of tube light out side this

office. This breaked - wire touches with iron angle kept for supprt of roof of office.At the time of weighing of truck, victim touched with the iron angle came in contact of leakage current got shock and

died.

Not Recd NA NA Nil

52 SBT Kudasan Shri Mahendrabhai Gabhabhai Wagela FH O/S 9.7.11

11KV Koba AG Feeder which is passing near from Swagat Reinforest-2.One of resident owner had thrown a wastage plastic bag which hanged on 11KV Koba AG Feeder.So,Victim tried to remove that

plastic bag with iron rod, placing himself at compound wall at Swagat Reinforest-2.& He got shocked & died on 10.7.2011 at Civil hospital,Ahmedabad.

Not Recd NA NA Nil

53 SBT Zezara Shri Arvindbhai Kalyanbhai Dalvadi FH O/S 12.07.11

Un authorised building erection work in process by Sava Sahakari Mandali at Zezara village. Victim was working on wall which is below 11kv Kumarkhan feeder line approximately 5 feet and came in

contact with live wire and got electrocuted. Not Recd NA NA Nil

54 SBT Mundi Buffalo FA 08.07.11 Due to heavy rain & wind ,Disc insulator of 11 KV line punctured ,hence conductor snapped and fell on ground. Buffalo while passing came in contact with live wire,got electrocuted and died. Not Recd NA NA Nil

55 MSH Katrasamal

Shri D V Samodara ( Gang Helper )33years lod NFH Dept 14.7.2011. (

At.13 hrs.)

While attending NO POWER LT complaina at village Katrasamal Ta& Di. Patan of Shri Patel Kantibhai Ujabhai. At that time his left hand touched to the jumper of phase wire & hence the victim burnt at his hand & immediately victim admitted at Janta Hospital,Patan. Detail investigation is under

process & will be submitted on the receipt of the same.

CEI Report yet not received

N/A as CEI report is not received

N/A as CEI report is not received

Notice issued to Victim vide letter No.4346 dt 21.7.11 to use safety tools & tackle while working with live line

No

56 SBT Vyana Shri Harishchandra C Dave Asstt. L. M NFH Dept 18.07.11

11 KV ONGC Ranchhodpura is on fault,While replacing faulty Pin Insulator in tape line, D.O fuse of tape line was removed, one jumper not properly cut , which was touching to wire causing line become

live, Victim touches live wire and got shock and fell down from pole admitted to Hospital..Not Recd NA NA Nil

57 SBT AmiyapurShri Thakor Rakeshbhai Bhavanbhai,(Dumper Operator). Age app 25 yrs

FH O/S 19.7.11 While raising dumper during operation,dumper touches the 11 kv line of New C.G Road feeder

passing near Tapovan Circle,Amiyapur.Live conductor break and fell on Dumper.victim tried to came out from cabin got shock and died.Ht line is on Girder pole distance from ground to conductor is 25 ft.

Not Recd NA NA Nil

58 SBT Dholka Shri Nathabhai Kanjibhai Dhadvi Age 37 (Approx) NFH O/S 13.07.10

An "allovera" pot is placed on perafit of terrace of Shri Pratpsinh Samantsinh Mahida's house at Gokulnagar.The distance between terrace and LT line is 2 ft Horizontal and 20 ft vertical from

ground.Due to jumping of Monkey,LT wire swings and stuck in allovera leaves.Victim at about 20.30 Hrs touches the plant , got shock became un-concious and admitted to hospital.

Not Recd NA NA Nil

59 HMT Dhirpura Buffalo FA 9.7.11

Two parallel HT & LT line is existing. One house is constructed below the LT line. So the same house owner has proposed for LT line shifting. So the LT line conductor is opened from the pole and then LT

line supply is given by 6 mm2 P.V.C. cable with G.I wire on L.T line pole on one side. The 6 mm2 P.V.C. cable is supported on H.T pole on other side. Meanwhile due to over load , the G.I wire is short circuited & came in contact with LT PVC cable phase wire.Hence there was leakage of current in G.I

wire which was connected with G.I wire of earthing of H.T pole.Mean while The buffalo came in contact with G.I earthing wire of H.T pole & got electrocuted.

CEI Report not received

Necessary maintance carried out No

60 HMT Bhudasan Bullock FA 18.7.11At consume premises holder of bulb short ckted & resulted in to leakage Current passed near by PSC

pole through earthing wire. Mean while a bullock came in contact with earthing wire & got shocked & died.

CEI Report not received

The consumr made aware to use ISI quality material . No

61 HMT MODASA1. Vaghela Yogeshsinh Takhatsinh 2.Vaghela Lalsinh Magansinh

FH O/S 20.7.11

Both Victim were playing the game with iron bar( 15 ft length ) on the ground. The one end of the iron bar was in the hand of Yogesh and the other end of the iron bar in the hand of Lalsinh. During pulling

the bar, one end of said bar was left from the hand of Lalsinh & touched with the live 11 KV WW feeder line and the other side of the iron bar was in Yogesh hand. So Yogesh got shocked & met with

fatal accident. At the same time Lalsinh came near Yogesh for save & Lalsinh was injured. The clerance between 11 KV line & ground is apprx. 18 ft.

CEI Report not received

N/A No

FA/FH/NFH

Dept / O/S

1 2 3 4 6 7 8 9 10 11 125

Detailed Reason of AccidentFinding of CEI/EI/ AEI

Remedies suggested by CEI / EI/ AEI in various cases

Type of AccidentWhether the remedy suggested is complied

Action taken to avoid recurrence of such Accident.

Date of occurance

Compensation Paid

Sr. No.

CircleLocation

of Accident

Details of victim

62 HMT Arsoda Ta:Prantij Buffalo FA 19.7.11 Due to overnight heavy rain LT line cond was broken & At the same time buffalo came into the

contact with this live broken cond. & got shocked & met with electrical accident

CEI Report not received

PROPER CAPACITY DO FUSE PROVIDED WHITCH BLOWN IMMEDIATELY ON BREKING OF CONDUCTOR . ALSO LINE MAITENANCE CARRIED OUT

No

63 MSH Linch Cow FA 7.07.11

Due to heating of the R-Phase of the cable from the distribution box, an insulation of the R-phase was damaged and the bear portion of the R-Phase was touching to the girder pole of the T/C centre. Due to

rain fall a bear portion of the R-Phase charged the girder pole and a cow came in the contact with girder pole and got electric shock .

CEI Report is not received

N/A as CEI report is not received

N/A as CEI report is not received

Faulty cable replaced Not applied for

64 PLNMota joravarpura

BuffaloFA ( 3 no. s of Buffalo)

14.07.11Due to heavy wind pressure ,11KV Gujarwada feeder conductor slip away with pin insulator from GI

pin and hanging above the ground level. Meanwhile Buffaloes were came in contact with live conductor and got electrocuted .

Awaited Maintenance work carried out periodically. 0

65 PLN Sinad

Makawana Parmabhai Bhanabhai-50years old &Jayeshbhai Vasarambhai Parmar-15years old

NFH O/S 19.07.11Due to heavy wind , jumper broken of 11kv shrinath JGY feeder & found conductor hanging near to earth at village sinad & found both victim came with contact of live wire & got electrocuted & met with

NFH.Awaited Maintenance work carried

out periodically. 0

66 MSH Adiya Buffalo FA 17.7.11 The internal wiring of Dudheshwar Mahadev Temple was defective and due to that there was leakage

current on earthing of T/C .The Buffalo passing near by Transformer Center near this Mahadev Temple , got electrocuted .

CEI Report yet not received

N/A as CEI report is not received

N/A as CEI report is not received

Proper wiring done at consumer end & TC earthing reactivated

No

67 SBT Vanthal BuffaloFA (2 Nos of Buffalo)

11.7.11 Due to heavy rain water is accumulated near T/C centre, momentarily current may pass through earth wire and buffaloes came in contact with earth wire & got electrocuted. Not Recd NA NA Preventive maintenance

carried out nil

68 SBT Adalaj

Shri Rajendrasinh Shambhuji Vaghela, Dumper Cliner , Age approx. 33 Yrs

FH O/S23.7.11 at approx. 2:30 hrs

There is a LT 3ph4w line of 11 KV Adalaj Feeder passing, At adalaj . While operating dumper (to empty dumper which is full of river sand )under this LT line by victim , dumper came in contact with LT

Line ( distance between lowest conductor to ground is 18 foot 2 inch )and LT Conductor broken and fell on Dumper truck. At the same time victim touched dumper and he got shocked and died.

Not Recd NA NA Nil

69 SBT Bavla Buffalo FA 21.07.11 At 16.45 Hrs

Due to leakage of current of transformer centre (opp Vijay Trolly Bavla -Sanand road vill Bavla) passed through PDC street light’s neutral wire, G.I wire of service broken and fall on the ground.Neutral wire touches the G.I wire of service and leakage currnt flows through it, A buffalo came in contact with G.I

wire got electric shock and died.

Not Recd NA NA Nil

70 SBT Mahij Buffalo FA 25.7.11 Due to one HT conductor of 11KV Geratpur feeder snapping from jumper and lying on ground, a buffalo came in contact with the live wire on ground & got electrocuted. Not Recd NA NA Restringing is done with rejumNil

71 SBT Metal Buffalo FA 8.07.11Due to heavy rain and cyclone on 07.07.2011 water is accumulated near T/C centre, momentarily current may pass through earth wire and buffalo came in contact with this leakage current & got

electrocuted.Not Recd NA NA Nil

72 SBT Sakodara Cow FA (2 Cows) 20.07.11

Water was accumulated near AG T/C (11 kv Shiyawada Ag Dom feeder) due to rain.At the time of Site Panchnama no any leakage current found,momentary leakage current may pass due to un balance

phase current,Cows while passing near to T/C came in contact with leakage current,got electric shock and died.

Not Recd NA NA Nil

73 HMT Gadha Chauhan Rekhabahen Rameshsinh(Bhalusinh) FH O/S 22.7.11

As the insulation of the PVC twin core service cable of resi.conn.of victim was corroded so one phase is opened which was Lying on the Galvanised sheet of shed of the house . The leakage current

spread in the shed of galvanised sheet supported by galvanised pipe.Victim has used steel wire for drying the clothes which was tied with galvanised pipe..Thus leakage current flown in the above steel

wire (Through galvanise pipe) on which clothes were kept for drying .While drying the wet clothes Rekhabahen got electrical shocked and died.Twin core service cable of resi. Connection of victim was

disturbed from pole to meter due to errection of galvanised shed by the consumer

CEI Report not received

service wire of victim house is replaced immideately and LT maintenance of entire village is carried out .Also villagers are educated not to carried out kachcha shed near electric sevice line.

No

74 MSH Khambhel Cow FA 8.07.11Water was accumulated near village T/C due to rain. At the time of Site Panchnama no any leakage current found,momentary leakage current may be pass between neutral and earth of x'mer. Cow

while passing near to T/C came in contact with leakage current,got electrocuted.

E.I. has not submitted finding report

N/A as E.I. has not submitted finding report

N/A

As it may be leakage current in Earthing/Neutral hence propoer and healthy earthing reactiveted

Not paid

75 SBT Ambareli Shri Dahyabhai A. Vegda NFH O/S 22.07.10

A house building is under construction below 11 KV Kariana Ag Feeder un authentically. Victim Shri D.A Vegda climbed on the centing of terrace of house building and his hand came in contact with HT overhead line conductor & met with Non fatal electrical accident. Sufficient clearance is there between

Ground and line (approx 16 feet) distance between wall and line is 2' 6". Filling is done by party to raise the plinth height of house.

Not Recd NA NA Nil

FA/FH/NFH

Dept / O/S

1 2 3 4 6 7 8 9 10 11 125

Detailed Reason of AccidentFinding of CEI/EI/ AEI

Remedies suggested by CEI / EI/ AEI in various cases

Type of AccidentWhether the remedy suggested is complied

Action taken to avoid recurrence of such Accident.

Date of occurance

Compensation Paid

Sr. No.

CircleLocation

of Accident

Details of victim

76 SBTVirochannagar. (Ag. Land)

Cow FA 26.07.11 11 KV Conductor snapped, Due to faulty Pin Insulator broken from top. Conductor fell on the ground & Victim cow came in contact with live conductor got electrocuted and died. Conductor is snapped but

no tripping recorded at Chharodi S/S.Not Recd NA NA Nil

77 SBTPipan (Below vill T/C)

Buffalo FA 11.07.11 A buffalo is found dead near village T/C,There is a leakage of 100 volts at the time of visiting the site between neutral and earth on x'mer & Buffalo got electrocuted . Not Recd NA NA Nil

78 SBT

Rethal , (Near AG T/C of Merubhai Jamalbhai)

Buffalo FA 13.07.11 Minor leakege current found between neutral stud of TC to earth wire of AG TC. The reason for

leakage is not found. It may due to un balance current. The rain water was logging around TC. The buffalo came in contact with leakage current got electrocuted and died.

Not Recd NA NA Nil

79 MSH Piplana Buffalo FA 26.7.2011 7.50 am

The Buffalo of shree Jitaji Kamaji Thakor Piplana was passing near by newly errected Transformer Center (without transformer) of Village Piplana near village T/C got electrocuted and died . There is LT Line on newly errected transformer center and this LT line is fed by cable coming from existing nearby transormer. By investigating it is found that the cable of LT Line is fired and touched to angle of newly

erected transformer center hence baffalo got electrocuted by toching the earthing of newly errected transfome center.

CEI Report yet not received

N/A as CEI report is not received

N/A as CEI report is not received

Rectification done by replacing damaged cable No

80 HMT Dehagamda Buffalo FA 1.08.11

Due to faulty shorted switch of siren of Dhudh mandali , leakage current flow in the transformer neutral earth wire. While buffalo passing near this transformer , came in contact with earth wire & got

electrocuted.

CEI Report not received

Siren of Dudh mandali Disconnected No

81 PLN WAV Buffalo FA 2.08.11 There was Leakage current on Transformer Neutral earth wire near Gayatri school.A Buffalo while passing came in contact with this Leakage current & electrocuted . Awaited Maintenance work carried

out periodically. 0

82 MSH Harij Buffalo FA 31.7.11There was leakage current on neutral earthing wire of T/C due to Harij nagarpalika w/w motor was short. Fencing of T/C was in touch with the earthing wire of T/C. Buffalow while passing nearby T/C

,touched this fencing & got electrocuted.

CEI Report yet not received

N/A as CEI report is not received

N/A as CEI report is not received

Fauly motor of consumer has been repaired and earthing laying is properly done & TC earthing reactivated

No

83 SBT Kalol Shri Nimeshkumar Govindbhai Prajapati Helper Nardipur

NFH Dept 04.08.11

Victim was working on tapping girder pole of 11 kv Ambika feeder of 66 kv kalol s/s after taking line clear of feeder and Earthing carried out on nearest T/C center of main line by removing of D.O. fuse

near Bhavaninagar area. i.e. third pole from S/S. The D.O of Bhavaninagar area T/C was not taken off and earthing from that line is also not done. Near by Udaji ni chali is feeding with the power of 11 kv

Janpath feeder and which is in ON condition. While working one side conductor opening of jumper & pin binding is completed successfully and when he had started the work with other conductor he met

with accident.At that time from kalol s/s near by feeders 11 kv janpath , tower chok and kalol city feeders were made off from s/s , and than victim him self with getting some relaxatation he came

down from the pole .The detail cause is under investigation, but it is assume that from any consumer of janpath feeder line power exchange to the 11 kv Ambika feeder L.T. line consumer & that may come

throgh L.T. line to t/c & 11 kv line, & accident may occured.

Not Recd NA NA Nil

84 HMT Vavadi Buffalo FA 9.8.11 Due to heavy rain and wind , tree fallen on 1ph2w LT line. The pole & conductor Of the same line was Broken & live conductor fall on the buffalo under the line ,so buffalo got electrocuted.

CEI Report not received

Necessary Maintenance carried out No

85 HMT Munpur BuffaloFA (2 nos. of Buffalo)

9.8.11 Due to heavy rain and wind, LT conductor broken & fallen on to the ground. While passing through that place,two buffalloes came in contact with same live conductor and got electrocuted.

CEI Report not received

whole lt line tree cuting carried out & propper capacity do fuse provided

No

86 HMT Ranjedi Buffalo FA 4.8.11 Due to heavy rain & wind, JGY LT Line Pole was Tilted . So AG LT Line Phase wire touched to JGY

LT Neutral wire at crossing .So current Passed through JGY LT Neutral wire to T/C centre and its Distribution box. Meanwhile the Buffallo came in Contact with Distribution box and got electrocuted.

CEI Report not received

The tilted pole rectified and Lt line Maintenance carried out

No

87 HMT kotada Buffalo FA 10.8.11 Due to heavy rain and wind, Tree fallen on LT conductor and so LT conductor broken & fallen on to

the ground. Mean time the buffallo came in contact with same live conductor and got electrical shocked & died

CEI Report not received

whole lt line tree cuting carried out & propper capacity do fuse provided

No

88 MSH Mitha Buffalo FA 11.08.11

In LT Distribution box, the contact of (R-phase) fuse was very heated and so plastic packing melted and the bolt of this packing was in direct contact with the body of distribution box. So,leakage current flow in water logged near the transformer cenre. Buffalo while passing near this transformer centre

got electrocuted.

CEI Report is not received

N/A as CEI report is not received

N/A as CEI report is not received

LT Distribution Box replaced Not applied for

89 MSH THOL Camel FA 11.08.11 Due to heavy rain and wind pressure in early morning at about 6.30 a.m , tree branches were broken &

fall on live conductor of 1-ph 3w L.T. line so conductor broken and fall on ground. While passing through that place, camel came in contact with this L.T. line conductor & than got electrocuted .

E.I. has not submitted finding report

Awaiting finding report from E.I.

N/A

Conductor broken due to heavy wind pressure and heavy rain although cond joited properly

Not paid

FA/FH/NFH

Dept / O/S

1 2 3 4 6 7 8 9 10 11 125

Detailed Reason of AccidentFinding of CEI/EI/ AEI

Remedies suggested by CEI / EI/ AEI in various cases

Type of AccidentWhether the remedy suggested is complied

Action taken to avoid recurrence of such Accident.

Date of occurance

Compensation Paid

Sr. No.

CircleLocation

of Accident

Details of victim

90 SBT Salajada 3 Buffalo and CalfFA (3 Buffalo & 1 Calf)

11.08.11

There was heavy wind & continuous rain. The 11 KV disc insulator got fired hence hardware side part got damaged and opened and jumper was momentarily touched to the fabrication part of the PSC

pole, so leakage current was flowing from 11 KV jumper to GI earth wire through fabrication. The water was accumulated in the bottom part of the pole due to rain. Victim three buffalos and one calf age two

years(approximately) came in contact with this leakage current got electrocuted and died.

Not Recd NA NA Nil

91 SBT Randesan Buffalo FA 14.8.11 Due to rain and wind , tree was fallen on LT line of 11 kv Infocity Feeder.So LT line conductor

snapped, Buffalo came in contact with live LT line wire,while eating grass and got electrocuted near Dasarathbahi's farm.

Not Recd NA NA Nil

92 SBT Nardipur Cow FA 15/08/11 Due to rain and wind ,tree branch was fall on LT line of 11kv P & T Nardipur feeder & So conductor was broken & fall on cow ,came in contact with live wire got electrocuted. Not Recd NA NA Nil

93 SBT Shiyawada Cow FA 15.08.11At the time of site investigation no leakage current found. Momentary leakge current may passed

through the earthing wire due to un balance phase of D.P. structure , Cow while passing nearer to D P structure came in contact and got electric shock.

Not Recd NA NA Nil

94 PLN Bharvadvas Cow FA 11.08.11

An electrical Fatal animal accident occurred to cow due to broken of street light phase which is fallown on ground & leakage current flow near surrounding area due to rain ,at that time cow was

came with contact of leakage current and on the spot diedAwaited

Vide publicity & awarness required to consumers about live wire & power.

0

95 PLN Nidroda Desai Godabhai Mafabhai-36years old FH O/S 10.08.11

Service line for Victim's house connection was taken up to meter by wounded it on hook on the wall. Victim was hanging milk can(BARNI) on same hook daily. So service line insulation was broken and phase wire was opened. While taking the milk can from hook , victim came in contact with the open

phase wire and got shocked and died.

Awaited Maintenance work carried out periodically. 0

96 PLN Janali Buffalo FA 12.08.11 Conductor of 3-phase 4wire LT Line was broken & fall on ground. Buffalo came in contact with this live broken conductor & got electrocuted. Awaited Maintenance work carried

out periodically. 0

97 PLN Soni BuffaloFA (Buffalo-2 nos.)

05.08.11

Without any information,Contractor of 'sujalam sufalam' canal has carried out canal work under line of Metro feeder & so clearence between ground of canal border and line crossing the canal was

reduced to about 5 feet near soni village. While passing on canal border ,two buffaloes came in contact with line due to low clearence & got electrocuted.

Awaited Maintenance work carried out periodically. 0

98 HMT Pishal Chauhan Babubhai Bhagabhai FH O/S 14.08.11

Due to heavy wind & Rain ,1ph 2w LT Line Phase Wire Broken from D Shackle and fall down in Farm.Due to heavy Rain Water logged in farm .At this time victim was Passed from this water and

came in Contact With Live Wire and Got heavy shock & Died.

CEI Report not received

Necessary Maintenance carried out No

99 HMT Tunadar Buffalo FA 12.8.11 Due to heavy rain and wind Tree fallen on line so LT cond broken & fallen on to the ground. Mean

time the victim buffallos came in contact with same live conductor fallen on the ground and got electrical shocked & died

CEI Report not received

Necessary tree cutting & Maintenance carried out No

100 HMT HMT Limbachiya Manishaben Kamleshbhai FH O/S 14.8.11

In premises of victim the ceiling fan is Hanged with the support of Iron roof & ceiling fan is supplied with flexible wire without any insulation between roof & wire.The same insulation wire is opened from the connector & touched with the body of the fan & leakege current passed through body of the fan to

roof.Also One iron wire was tied with in touch of the roof where clothes are hanged.So the leakage current passed through roof to this wire & while taking up the clothes from this wire the victim came

into contact with this wire & got electrical shocked & died .

CEI Report not received

New Test Report taken from the party after correction of his wiring & meeting was arranged with Party for information about safty norms of electricty and danger of it.

No

101 HMT Vanaj Cow FA 13.08.11Due to cyclon tree was falllen on 1-ph 2 wire LT line. The phase wire of LT line broken and phase wire jumper touched with neutral wire jumper and so power returned at X'mer earth wire. Mean time Cow

came in contact with earth wire & got shocked & died.

CEI Report not received

LT line Maintenance Done No

102 HMT Dolpur Buffalo FA 17.08.11Due to heavy rain and wind, One phase conductor of 3 ph 4wire LT line was snapped in check dam as

LT line is crossing over the check dam.The checkdam is filled with water and while eating the grass the Buffallow enter in the check dam water & got electrocuted .

CEI Report not received

Lt line spacers provided & line Maintenance carried out

No

103 SBT Jaliyamath Shri Amartgiri Madhavgiri Goswami Age app:70 yrs. FH O/S 20.8.11 @

14:15 Hrs

In a small hut having iron roof with wooden support, A 15 w bulb was hanged on iron wire and electrically connected with telephone wire to his internal switch board .The insulation of this telephone

wire was broken and the inside wire touched with the iron wire. So the current passes through the telephone wire to iron wire and in the iron roof. Smt Premilaben was hanging clothes to dry on the iron wire which is in contact with the iron roof.As she touched the wire she came in contact with live electric

current ,To save her Shri Rameshgiri(her husband) and Shri Amratgiri(Victim) also came in contact with live current.Shri Amartgiri get shocked and felt down and declared dead.Smt Premilaben and

Rameshgiri met with NFH Accident.

Not Recd NA NA Nil

104 SBT Makhiyav Cow FA 21.08.11 Due to heavy rain water was logged around the pole. Conductor of LT line was snapped from shackle insulator and fall on D clamp. So leakage current flows through D clamp to earthing wire.The victim

cow while passing came in contact with earthing wire got electrocuted and died.Not Recd NA NA Nil

105 SBT Rajpur Shri Solanki Baldevbhai Maganbhai NFH O/S 20.08.11

In house of Shri Dineshbhai Somabhai Solanki, leakege current passed through metal pipe of fan to the common wall of two house and in metal door ( Jali) of Victim's house due to internal wiring of

ceilling fan and humidity due to rainy weather. Victim came in contact of leakege current, while closing the metal door(jali)& got shocked.

Not Recd NA NA Nil

FA/FH/NFH

Dept / O/S

1 2 3 4 6 7 8 9 10 11 125

Detailed Reason of AccidentFinding of CEI/EI/ AEI

Remedies suggested by CEI / EI/ AEI in various cases

Type of AccidentWhether the remedy suggested is complied

Action taken to avoid recurrence of such Accident.

Date of occurance

Compensation Paid

Sr. No.

CircleLocation

of Accident

Details of victim

106 SBTSankod (Shaktipura)

Smt Hansaben Karasanbhai Karamshibhai Koli Patel

NFH O/S 20.08.11

The Arial Bunch cable is provided on LT pole to prevent theft. At the time of site visit, the insulation of AB cable was found damaged i.e.phase and neutral wire was opened un authorisely. An extra PVC 2.5

mm2 cable was not connected with LT line AB cable at the time of site visit but it is assumed that it was connected with LT line AB cable and removed after occurance of accident. This 2.5 mm2 PVC

cable was digged under land and at some places hide in grass. While cutting the grass by victim, PVC cable got damaged and she came in contact with live phase wire and got electric shock. This cable was laid by house holder for theft of power hence UGVCL is not solely responsible for this electrical

accident.

Not Recd NA NA Nil

107 PLN Lotiya Buffalo FA 20.08.11An electrical Fatal animal accident occurred to Buffalo due to rain water accumulated near T/C & so leakage current flow near surrounding area of Village T/C by Distribution x'mer neautral wire ,at that

time Buffalo was came with contact of leakage current and died.Awaited Maintenance work carried

out periodically. 0

108 MSH Kansa NA Thakor Chhagaji Ragaji NFH O/S 20.08.11

11 KV Spining Mill feeder eminating from 132 KV Visnagar sub station is passing approximately 6 feet over bunglow no 38's north side cornerof Sidheswari society in Kansa NA .Ground floor

Costruction work of bunglow no 38 is completed up to slab level & already Laying of centring work of ground floor slab is about 13 feet hight from ground . Form work of slab is of ms sheet.Thakor

Chhagaji Raghaji Age 28 years labour of construction work climbed on slab to put paper packing in gap of centring & by mistake he stood & his hair touched with Live line momenterily & he got electric shock & he fell down on slab .Thus Non Fatal accident took place.Due to momentarily touching No

triping came on 11 kv spining mill at the time of accident.

CEI Report is not received

N/A as CEI report is not received

N/A as CEI report is not received

S/DN issued notice to party for construction work done before shifting of linevide letter no DE/VSN-1/TECH/3729 DT 20-8-2011

No

109 HMT Butal Buffalo FA 26.8.11 Due to heavy rain and wind, conductor snapped on Calf(baby buffalo). So calf contacted with the live LT conductor and got electrocuted.

CEI Report not received

Maintenance carried out No

110 SBTDehgam, ved no mahollo

Bhatia Nilamben Dhimantkumar,Age app:25 yrs.

FH O/S 30.8.11 @ 17:45 hrs

Due to internal consumer wiring problem, table fan shorted, and leakge current passed through it. During cleaning in the house, victim touched with table fan and she got electrocuted. Not Recd NA NA Nil

111 HMT Pipaliya Ta:Hmt

Rakesh Nandubhai Mahida FH O/S 12.8.11

During the site visit of the accident site no evidance of lekage of the current has been found.But as per the eye witness statement victim has got electric shock while starting to motor for AG connection.The P.M. report also confirms death due to elec.shock.Hence it seems that victim might have touched any

live part while starting the motor and got elec.shock & died.

CEI Report not received

accident occurred in consumer premises No

112 MSH Sabalpur Senma Mangalbhai Shankarbhai NFH O/S

30.8.20113.00 PM HRS

11 KV Karbatiya JGY feeder eminating from 66 KV Vadnagar substation is passing approximately 3 to 5 feet over the house . This house of Shree A.M.Senma is KachhaZupada & reconstructed as a

Pakka Makan under Sardar Avas Yojana in 2007-2008. 11 kv line is passing over 3 to 5 feet on left side of the house & the height of house is approximately 10 feet. 11 KV line hight is approximately

13to 15feet from ground . Shree Mangalbhai Shankarbhai Senma climbed on the tarace of the house of neighborhood Shri A.M.Senma to collect the wooden pieces which was stacked on terrace of the house . By throwing the wooden pieces from Terrace to Ground & By mistake he came in contact of Live conductor & he got Electric shock & thus Non Fatal Accident occurred. Tripping came on 11 kv Karbatiya JGYfeeder at the time of accident. UGVCL has not given the lighting connection in this

house due to illegal construction of house under 11 kv line.

CEI Report is not received

N/A as CEI report is not received

N/A as CEI report is not received

SDO has issued the notice to the party for the illeagl constructon vide letter no. UGVCL/VAD/Tech/3919 dtd. 02/09/11

No

113 PLN Sodhoshi Cow FA 29.8.2011 Conductor of 3-phase 4wire LT Line was broken & fall on ground. While passing , cow came in contact with broken conductor & got electrocuted. Awaited Maintenance work carried

out periodically. 0

114 MSH Malsund Buffalo FA 02.09.2011

The buffalo was passing near by the LT pole at village Malsund touched the earthing wire and got electrocuted and died.By investigating the reason it was found that the jumper of LT line was burnt and touched the U-clamp and so to earth wire hence leakage current passed through earthing wire and by

touching the eath wire the buffalo got electrocuted.

CEI Report yet not received

N/A as CEI report is not received

N/A as CEI report is not received

Rectification done by proper rejumpering of LT line and TC eathing reactivated

No

115 MSH Harij Shri Prajapati Vasantbhai Joitabhai FH O/S 03.09.11

at 09:15 PM

Shri Prajapati Vasantbhai Joitabhai(Victim), age-56 years, was engaged in ganeshotsav at his street near his house.on date 3/09/2011 at 9.15 pm they were doing aarti of god ganesha and his hand

touched to the shutter frame of shop which was touching to faulty wiring made for decoration purpose and got electric shock and falled down and had got serious injery on head. Doctor in ambulance services (108) has declared dead in the way to hospital. There is no any permanent or temporary

connection at the premises where the accident occured.

CEI Report yet not received

N/A as CEI report is not received

N/A as CEI report is not received

ganesh mahotsav organiser was informed to utilise proper guage wire in good condition for decoration and instructed to ask temporary connection for such event

No

116 PLN Mujpur Cow FA 04.09.11 A Fatal accident occurred to Cow due to broken of 3-phase 4wire LT Line conductor in mujpur village & fallown on ground while cow came with contact with broken conductor & got electrical shock Awaited Maintenance work carried

out periodically. 0

117 HMT Akrund Buffalo FA 07.09.11 Due to heavy rain & cyclone Akrund Ag. fdr Lt conductor broken,meanwhilc buffalo came in contact with this live conductor & got shocked & died.

CEI Report not received

Maintenance carried out No

118 SBTChhatral GIDC Phase-3

Buffalo FA 02.09.11 Buffalo came in contact with leakage current of Neutral earthing of Transformer and got electrocuted Not Recd NA NA Nil

FA/FH/NFH

Dept / O/S

1 2 3 4 6 7 8 9 10 11 125

Detailed Reason of AccidentFinding of CEI/EI/ AEI

Remedies suggested by CEI / EI/ AEI in various cases

Type of AccidentWhether the remedy suggested is complied

Action taken to avoid recurrence of such Accident.

Date of occurance

Compensation Paid

Sr. No.

CircleLocation

of Accident

Details of victim

119 SBT Vayna

1.Rabari Bharatbhai Harjibhai (fatal) 2.Rabari Khodabhai Rambhai 3.Rabari Dharmeshbhai Virambhai

1 FH & 2 NFH O/S 06.09.11

There is temple of Ramdev Pir At villege Vayna.Some people were going to the temple with long flag ( 18 feet).Which is touched with 11 KV line of Ishvarpura JGY feeder(clearance from ground to line is 20

feet).Due to rain flag and stick get wet,So they got electric shock.One man died & Other two men injured.

Not Recd NA NA Nil

120 SBT Goraj 2 Cow and BuffaloF A (Two Cow and buffalo)

7.09.2011 6.00 Am

Tree branch fell on LT line ( 1ph 2 wire), conductor broken and fell on ground. Victim animals came in contact with live phase wire got electroctuted and died. Not Recd NA NA Nil

121 SBT Mehkal Smt Shilpaben Chelusinh Chauhan ,Age app:32yrs. FH O/S 08.09.11

The one end of Iron wire is bounded with the wooden support of the iron roof while other end is bounded with tree infront of house for drying clothes.The bulb was hanged with the wooden support of the iron roof.There is a open joint wiring, one feet away from the bulb(both phase and neutral) and also

which is in contact with the iron roof .So current passes through iron roof and iron wire.Due to heavy rainfall on that day Smt Shilpaben had gone for taking the dry clothes,as she touched the wire she got

shocked and died.

Not Recd NA NA Nil

122 SBT Chharodi Buffalo FA 11.09.11Buffalo has stratched GI earth wire of PSC pole while rubbing her horn,hence GI eathing wire of 11 KV MIT feeder disturbed and GI wire opened from Side clamp & toched to 11 KV Live feeder conductor momentarily. Victim buffalo got elctric shock got electrocuted and died.

Not Recd NA NA Nil

123 HMT Sakariya Bullock FA 5.9.11 Due to heavy wind & rain tree fallen on LT line so one phase of Lt line fallen on ground,mean time bullock came in contact with this live wire & got shocked & died on the spot.

CEI Report not received

Lt line Maintenance carried out No

124 HMT Tintoi Gameti Ushaben Dilipbhai FH O/S 9.9.11

In the party premise, The main switch board is conected with single phase motor starter board with 1 ph service wire. On the motor starter board black(neutral) wire was connected with fuse & other yellow(phase) wire was open from fuse. When the victim gone to switch on the motor & came in contact with phase wire & got electrical shocked & Died.

CEI Report not received

Notice issued to consumer and new Test report was taken from him for correct premise wiring

No

125 HMT Rupal Buffalo FA 7.9.11Due to heavy rain & cyclone momentarily leakage current might have passed from transformer earthing, mean while buffalow came in contact with this earthing wire & got shocked & died.No sufficient cause for leakage of current is found on LT net work as well as transformer centre.

CEI Report not received

Maintenance carried out No

126 PLN Nenava Devada Umedsinh Gensinh-21 years old FH O/S 12.09.11

A fatal electrical accident occurred to outsider, While victim came into the contact of Domestic floor mill that is in own premises & at that time leakage current already flowing on floor mill and victim got shocked

Awaited Use ISI Marka appliances & ELCB also 0

127 MSH

Nr Adundara road Shmashan, kadi

Buffalo FA 11.09.11

Buffalo of smt.Jasiben Lembabhai Rabari (age:@ 40 yrs.)passing nearby adundara road shmashan opp. Adundara road w/w kadi came in contact with transformer Earthing. Due to shortcircuited either motor or starter , leakage current flows through transformer Neutral Earthing at where buffalo due to habbits electroculated.

E.I. has not submitted finding report

N/A as E.I. has not submitted finding report

N/A

Leakege current due to it may Muni W/W starter or any other leakage from party side to Xmer hence as no reason from our company side.Aithough earthing reactivated.

Not paid

128 SBT Kudasan

Shri Sanjitkumar.Satish.Sardar,Age:26 Years & Bishvajeet.Mahatu,Age:24 Years

FH O/S 12.9.11 @ 20:30 Hrs

A temporary 3-ph connection is given for construction purpose at village Kudasan . About 90 meters far from xmer center,a distribution board with main switch installed for two circuits of bore and submersible pump. In One fuse of main switch direct wire is inserted , While victims were taking bath using submersible pump. Due to sudden power cut , one of victim had checked their distribution board and found loose connection of looping arrangement. He tried to solve and get shocked. Another victim while trying to help him , he also got shock. After emergency medical treatment in Gandhinagar civil hospital,they both are declared dead.

Not Recd NA NA At Primary Stage,Connection Is Disconnected. Nil

129 SBTBopal(Nr. Safal Parisar-1)

Shri Monaji Pakaji Vaniya, Age: 46 years FH O/S 04.09.11 @

10:30 AM

S/Dn office was not informed regarding this incidence, They were informed by the police station with asking opinion whether the accident can be occurred or not?.No any evidence was found on dtd 06.09.11,regarding electrical accident at the time of Site Punchnama.As per Information provided by shri Mansukhbhai Budhabhai Rajput, the said victim shri Monaji Pakaji Vaniya was driver of the Hyva DUMPER.Due to negligency of the victim, he had put the dumper on auto hydraulic mode without verifying any site situation and started to clean the back side of the dumper. Meanwhile Dumper moved up and might have been touched to the overhead HT line(Ambli feeder) and thus the accident might have been taken place.

Not Recd NA NA Nil

130 SBT

Dholka (Khan Talav Canal Road)

Buffalo FA14.09.11 Apprx. 03:45 PM

One conductor of 3Ph-4W LT line, crossing the Khan Talav Canal Road, was snatched by the roof of an unknown truck.no.GJ-18-T-9708 passing through the road and the live LT broken conductor fell on the victim (buffalo) passing through the road. The victim met with the electrical accident due to electrocution. The ground clearence was verified personally & found around 16 ft from the ground. The road level has also been risen due to canal road re-surfacing is under progress.

Not Recd NA NA Nil

131 MSH Solaiya Cow FA 13.09.11

At Solaiya Village near SGP T/W, a cow passing among the watered earth area touching to bore well colum pipe which was having electric leakage due to borewell motor faulty and short. The cow came in contact with that eletruleted area got the electric current due to this leakage & met with fatal electrical accident.

CEI Report is not received

N/A as CEI report is not received

N/A as CEI report is not received

SGP is instructed to maintain the safety measures within their installation

No

FA/FH/NFH

Dept / O/S

1 2 3 4 6 7 8 9 10 11 125

Detailed Reason of AccidentFinding of CEI/EI/ AEI

Remedies suggested by CEI / EI/ AEI in various cases

Type of AccidentWhether the remedy suggested is complied

Action taken to avoid recurrence of such Accident.

Date of occurance

Compensation Paid

Sr. No.

CircleLocation

of Accident

Details of victim

132 HMT Bhandhana Buffalo FA O/S 3.9.11 Due to cyclone & rain tree fallen on LT line so two conductor of Lt line fallen on ground,mean time

buffalo came in contact with this live wire & got shocked & died on the spot.

CEI Report not received

LT line Maintenance Done No

133 HMT Lilchha Bullock FA O/S 15.9.11 One wire of 3 ph. 4 wire LT line broken & fallen on raod side, mean time Bullock cart passes on road & same time bullock came in contact with this live wire & got shocked & died on the spot.

CEI Report not received

LT line Maintenance Done No

134 HMT Phinchod Parmar Popatbhai Sadubhai,Helper NFH Dept 23.9.11

While replacing of faulty transformer of 11 KV Khodam AG feeder at village Phinchod victim climbed on transformer centre to hang the chain pulley block and his right hand touched to Y phase and spark occurs.Before climbing on transformer centre Prajapati S.M.village helper of Phinchod village has AB switch cut off to dead the line of that section, Victim has thrown ring wire to check this feeder is live or dead but at that time no any spark was seen then he has touched an earthig rod to R,Y and B phase for earthing purpose then climbed on transformer centre to hang chain pulley block and touched to Y phase and got shocked and fallen down. The leakage current reason is under investigation & it will be resubmitted after division report.

CEI Report not received

On dtd 1.10.2011 feeder maintenance carried out and restringing of loose conductor done for proper clearance. In line staff meeting awarness is given to avoid accident to line staff.

No

135 SBT Kudasan Naresbhai Hirabhai Kolipatel,Age:18 years FH O/S 29.9.11 @

18:30 Hrs,

A temporary 3-ph connection is given for construction purpose at village Kudasan . About 80 meters far from xmer center,a distribution board with main switch installed in the room. From that a flexible wire is connected in the switch board far about 30 meters approximately.victim tried to push that open wire in the plug of that switch board and got shocked After emergency medical treatment in Gandhinagar civil hospital,He declared dead.

Not Recd NA NA At Primary Stage,Connection Is Disconnected. Nil

136 PLN Vill-Thali Chaudhary Janakbhai Jasabhai-Helper(v/s) NFH Dept 19.09.11

During fault attending work of 11kv Anganwada JGY feeder , which is isolated at location 34/3 & 34/3/40/41.At the same time on pole no-34/3/42 the pin insulator was found doubtful like puncture. The victim was climb on the same pole for the inspection of pin insulator & victim got electric shock & suddenly fallown on ground.On details investigation it is came to the knowledge that one other 11kv Jampur feeder was passing near 11kv Anganwada JGY feeder.The AG connection of Patel Anadabhai Ramabhai was given from AG T/C of 11kv Jampur feeder. Also the lighting connection of same party was given from 11kv Anganwada JGY feeder, which is so near from AG connection.Due to power failure of 11kv Anganwada JGY feeder party has got power by connecting private wire with AG supply & due to this return power was came on 11kv Anganwada JGY feeder.

AwaitedExplanation ask to survisor vide letter no-UGVCL/DOD/R-2032/1-10-2011

0

137 PLN Vill-Aithor Buffalo FA O/S 26.9.2011A Fatal accident occurred to Buffalow due to broken of 3-phase 5wire LT Line conductor at village Aithor near W/W & fallown on ground while Buffalow came with contact of broken conductor & got electrical shock.

Awaited Maintenance work carried out periodically. 0

138 HMT Antroli Raval Ashokbhai Bhikhabhai FH O/S 17.10.11 In victim premises he tried to switch on the light at that time its hand touched to unbrekable flexible

wire & victim got shocked & died.CEI report awaited N/A N/A

A meeting was arranged for given information about safety norms of electricity with village people residing there for none use of conducting things i.e. iron bar,open wire,steel measuring tap etc which are danger for getting electrical accident.

0

139 HMT Laxmipura Bhangi Jigarkumar Sureshbhai FH O/S 15.1.12 at

16.00 hrs

11 KV Kalol JGY fedeer is passing over house under construction(which is illegal) where the accident occurred.While catching the kite the victim came in conact of 11 KV line passing over the house under construction and fallen on ground and met with fatal accident

CEI report awaited N/A N/A

Letter written to TDO, Khedbrahma and Talati, Gram Panchayat, Laxmipura to stop illegal consruction.

0

140 HMTMotipura (Chandarni)

Chauhan Bhavanaben Balaji NFH O/S 29.11.2011

As per massage from outsider on dt:- 30.11.11 jointly inspected the site by Gambhoi s/dn & Bhiloda-1 s/dn. A non fatal accident occurred to outsider human namely Chauhan Bhavanaben Balaji at village: Motipura on dtd: 29.11.11. However, the actual reason yet to be pointed out. During site visit there was no any person came forwarded for eye witness.But, as per joint site investigation report of Gambhoi sdn & Bhiloda-1 sdn at the farm of shri. Chauhan Bhuptaji Galaji, one 11kv pole exists. There is a spark observed on top conductor of that pole near to top pin insulator and also burnt skin observed on earthing wire below V cross arm. It concluded that, there might be try to attempt of suicide by victim unauthorizely through climbing on that pole. Also detail investigation report of Police is awaited till today.

CEI report awaited N/A N/A

Letter given to Gambhoi Police Station vide no.UGVCL/BSD/Tech/2663/3.12.11

0

141 HMT Kakaritimba

owner -Pagi Pratapbhai Nathabhai

FA(Buffalo) 29.09.11

In 11 KV Odha Ag feeder, some Unknown person was trying to switch On the D.O. Fuse at Double Pole Structure (with do fuse). During this, the D.O. fuse was touched to the channel and Current passed through Pole to the Earth. At the same time the Buffalo was in the Water pit and got electric shock due to wet soil and Died.

Electrical Inspector report awaited

N/A N/A Maintenance of DO Tapping has been carried out 0

142 HMT Chandrana

owner- Gamar Chunabhai Singabhai ta:khedbrahma)

FA(Buffalo) 21.12.11

2 nos. of LT Line pole was found tilted & LT line 1-phase 2 wire conductor come near to ground so village helper had made this line LT circuit dead,and isolated by removing LT jumper and had reported to Kheroj s/dn office.Meanwhile without permission any un known person charged line by giving temporary jumer, due to this mischiep dead line charged. Mean while buffallow passing under this LT line & came in contact with live line and met with fatal accident.

CEI report awaited N/A N/A

FIR lodged against unknown defaulter at Poshina police station.

0

FA/FH/NFH

Dept / O/S

1 2 3 4 6 7 8 9 10 11 125

Detailed Reason of AccidentFinding of CEI/EI/ AEI

Remedies suggested by CEI / EI/ AEI in various cases

Type of AccidentWhether the remedy suggested is complied

Action taken to avoid recurrence of such Accident.

Date of occurance

Compensation Paid

Sr. No.

CircleLocation

of Accident

Details of victim

143 MSH Bhalana shri B C Bhagora,Village Helper of Sankra Ta Harij NFH Dept 1.12.2011

11:00Hr

Non Fatal Electrical Accident Occurred to Victim while working of tree cutting on LT Line of village Bhalana Ta Harij .11KV Line of Piplana Feeder(Katra S/S) was passing near by LT Line.While removing creepers,cutting instrument "Dhariya" touched with 11kv line and accident occured. On investigation it is found that line clear of 11kv Sarel feeder(Dunawada S/S) instead of Piplana feeder (Katra )was taken by LM Shri R.G.Pande. Also earthing was not done at site while working .

CEI Report is not received

N/A as CEI report is not received

N/A as CEI report is not received

accident occurred due to mistake of both lineman and helper , lineman and helper are instructed to keep safety equipments with them and make sure that the LC of proper feeder was taken and make proper earthing of line while working.

0

144 MSH Delmal shri B.S.Thakor Village Helper (Delmal ) NFH Dept

29/01/2012 AT ABOUT 11.30 HRS

On Date 29/01/2012 ( Sunday ),The Delmal village helper was going to attend the complaint of Ag connection in R/O Shri Rabari Virambhai Gandabhai ( Conn.No 21805/00364/0 ) of village Delmal ( Preparing new DO jumpers ) Which is on 11 KV Limbja feeder & at the time of accident the single

phase power supply was ON . He went the site of Ag connection & dismentalled all the three DOs of transformer centre & for disconnect the line he sent the outsider man to cut off the line by

dismentalling the DOs of this 11 KV tap line which is about 10 poles away from this trans centre & with out conformation that the DOs are dismentalled or not He prepared all the three out going jumpers complately with binnding & when he prepared to repaired the incomming DO jumpers , He got the

electrical shock & fell down from the Transformer DO angle & got the injuries on his back side

CEI Report is not received

N/A as CEI report is not received

N/A as CEI report is not received

Inform to linestaff to avoid this type of mistake in future & use safety equipments while working on line & line must be done dead by earthing on both the side

No

145 MSH Visnagar Parmar Maheshkumar Shankarbhai (Helper) NFH Dept 12.10.11

12:45 PM

On dt 12-10-11 ShriMaheshkumarShankarbhai Parmar Helper was going to release single phase connection to Shri Vikramshinh Rajput at block no 25 of Radhe Bunglows . which is situated on

Thalota road Visnagar . 3 Phase 5Wire LT Line of 11 kv City -3 feeder eminating from 132 kv Visnagar s/sis existing . 1 Phase connection is given on LT PSC pole . After installation of meter& laying of 2.5 mm2 service cable he climbed on psc poleto give service connection on the Live LT Line conductor. While he joint 2.5 mm2 pvc cable to Live conductor his left hand upper side came in contact with Live

conductor and he got Electric shock & he fell down to the ground & thus Non Fatal accident took place.

CEI VISITED SITE ON 19-12-2011

CEI REPORT NOT RECEIVED TILL TODAY

NIL

Victim & other line staff were instructed to use safety tools while working & also given the guideline regarding safety awareness

No

146 MSH Malsund shri Virabhai Ambabhai parmar FH O/S 02.10.11 at

15:30 Hrs.

The victim shri Virabhai Ambabhai Parmar, aged 45 years (approx) resi of Malsund , Ta-Harij was living at farm of Agri. consumer Shri Patel Ramabhai Karsanbhai having Ag Con.No-28548000821.

The connection is located at village malsund. The one Drop out fuse link of the transformer centre was blown off, hence the victim had tried to provide D.O fuse link by weted woodden bamboo. as per eye

witness statement, while this operation the victim had got electrocuted & died on the spot. further Harij office has not received any complaint regarding power failure or fuse blown off from consumer.

CEI Report is not received

N/A as CEI report is not received

N/A as CEI report is not received

Inform & warned to Consumer regarding unauthorised operation of DO fuse, and explained to make a complaint to concern SDO regarding power failure

No

147 MSH Kadi Rajput Manojkumar Hemanshubhai FH O/S 07.11.2011

at 11:15 PM

An electrical accident occurred to an outsider namely Rajput Manojkumar Hemanshubhai at village Kadi near Thol Road, opp.Gangotri shopping centre.On dated 07/11/2011 at approximately 11:15 PM, a Truck(Tanker) No GJ 18 T 0037 was parked below HT line of 11 kv Amul ind. Feeder eminating from 66 kv Kadi s/s. At that time victim climb on the tanker to take a rest, while walking on Tanker he came

into contact with live conductor of 11 kv HT line & electrocuated.

CEI Report is not received

N/A as CEI report is not received

N/A as CEI report is not received

New 10 Meter PSC Pole erected under 11 KV Line and height is maintained with horizontal distance to avoide the accident in future

Not claimed so not given compensation

148 MSH Boriavi Shri Dilipbhai Mahadevbhai Chaudhary FH O/S 27.12.2011

at 07:00 PMPending due to no one in the village came forward as a eye witness or willing to give any type of

statement.

CEI Report is not received

N/A as CEI report is not received

N/A as CEI report is not received

Village people were instructed to inform concern SDO or make a complaint at CCC for any line fault

NO

149 MSH BAVLU FH to Shri THAKOR BABUJI MANAJI FH O/S 23-02-2012

12:45 pm

As per press note on 24-02-2012 about fatal accident to shri Thakor Babuji Manaji, this office has visited site on 24-02-2012 at 10:30 am and taken statement of victim's brother shri Thakor Kalaji Manaji. Victim had no any electrical connection given by U.G.V.C.L. but he was using power from

residencial connection of Shri Thakor Dhanaji Manaji by yellow colour's private flexible 1/18 wires of about 25 meter. As per Thakor kalaji Manaji's statement, "Victim and his wife had quarrel with

neighbour on 23-02-2012. Opponent draw victim behind his home, bitting him badly on victim's chest and stomach by wooden stick and hand, from where the wires towards victim's home was passing with the support of wooden support. During this quarrel, flexible wire was broken and comes in contact with victim. Victim was fall down but still opponent continued to bitting him and victim was died." But as this

office was not informed on the same day, and panchnaama is carried out after having come to know by press note, this office can't conclude whether the death was due to electric shock of private flexible

wire from Thakor Dhanaji Manaji's connection towar

CEI Report is not received

N/A as CEI report is not received

N/A as CEI report is not received

The accident occurred in Private wiring, so we have intimated the consumer to use Standard equipement and wiring at premises.

Not claimed so not given compensation

150 MSH Gerita Shrimati Laxmiben Narayanbhai Patel FH O/S 28.12.2011

On site verification it was found that victim got single phase residential connection for lighting purpose at Gerita village. Single phase motor used by consumer through 1/18 guage copper wire from switch board. One of the end of this wire was connected at Switch Board and another end of this wire have

connected with male plug connector. Single phase motor have female plug connector. while the single phase motor was on and victim was removing the male and female connector to switch off the motor

directly and at that time victim touched the live male contact of the wire and got electric shock and died.

CEI Report is not received

N/A as CEI report is not received

N/A as CEI report is not received

ADVICE GIVEN TO CUSTOMER FOR RECTIFICATON OF HIS HOUSE WIRING

There is no UGVCL Fault

FA/FH/NFH

Dept / O/S

1 2 3 4 6 7 8 9 10 11 125

Detailed Reason of AccidentFinding of CEI/EI/ AEI

Remedies suggested by CEI / EI/ AEI in various cases

Type of AccidentWhether the remedy suggested is complied

Action taken to avoid recurrence of such Accident.

Date of occurance

Compensation Paid

Sr. No.

CircleLocation

of Accident

Details of victim

151 MSH LunvaOwner of buffaloAjamkhan Mehmunkhan Pathan

FA(Buffalo) 16.11.2011

In Lunva village AG sim area 3 phase AG connection no AG 340 of 65 HP in respect of Shri Chhattekhan MujahinkhanPathan is located. The power supply is given from 11 kv AG Khoda feeder emanating from 66 kv Khoda s/s. A 100 kva transformer center is located near to Room [Oradi] of ag connection. A Havada is situated near AG Connection Room On dt 16-11-2011 evening time a buffalo

came for drinking water from Havada& then he went near to transformer center & he touch the GI Wire of transformer center & he got electric shock& buffalo died. Investigation done for motor& Patti cable, the Patti cable is puncture & due to puncture of cable leakage current got path from Patti cable to service cable of transformer center to GI Wire of transformercenter. Fatal Animal Accident occurred

due to party’s Patti cable puncture.

CEI NOT VISITED SITE

CEI NOT VISITED SITE

NIL

Party was instructed to replace the patti cable & use standard electric motor for ag purpose

No

152 PLN

Sudrosan (Roda seva Asram)

Shri Narottambhai Tejarambhai Parmar-38 years old(Village-Helper)

NFH Dept 11.12.11

A non fatal electrical accident occurred to victim while victim climbed on 11 kv Dunavada-JGY for repairing of sackle pole jumper,at that time victim got shock due to one Tapping are not removed by

victim.at side observed by DE-Thara & found victim was remove two DO-Tapping & one Tapping not remove at location no-MPH/DUJ/133/08/121.

Victim himself responsible

Victim himself responsible

Field officers asked to take remedial measures as suggested by E/I.

Show cause notice issued vide letter no-UGVCL/ROD/T/EE/224/10-1-12.

no

153 PLN At-Dhaneri Shri Dilipsih Bhavansih Chavada-Helper NFH Dept

15-12-11 reporting 28.02.12

A non fatal electrical accident occurred to victim while victim climbed on 11 kv Rameshwar-JGY for maintenance work ,,at that time victim got shock due to return power of Genarator used in milk dairy of

Dhaneri village.

C.E.I report is awaited

Inform to police station-Dantiwada against Milk dairy vide letter no-DNT/5394/16-12-2011

no

154 PLN Bhataram Patel Nanajibhai Rupabhai-45 years old. FH O/S 19.11.2011

A fatal electrical accident occurred to outsider, During wrapping the black insulation tape on the broken phase wires,which carry the power from meter to fuse board & observed two phases comes together, thus the victim got shock & died on the spot in AG Connection room(Consumer no-73431/00144/2) .

Victim himself responsible

Victim himself responsible

Field officers asked to take remedial measures as suggested by E/I.

FAULT NOT ON UGVCL SIDE no

155 PLN Dhanera-city

Rajput Kisorsing Ramsing-30 years old FH O/S 19.11.2011

Victim applied 1-phase motor wire plug in switch board and try to start motor & found leakage current passes through her body due to victim hand contact to broken insulation Wire near plug, and got

electric shock in her premises.

Victim himself responsible

Victim himself responsible

Field officers asked to take remedial measures as suggested by E/I.

FAULT NOT ON UGVCL SIDE no

156 PLN Kalyana Rajput Laxmanji Bhagaji-60 years old NFH O/S 01.10.11

A Non Fatal Human electrical accident occurred to victim ,while victim climbed on 11 kv nilkanth AG feeder for Unathorised Reconnection of his AG connection(22821/00507/5).This AG connection was

disconnected by DE-Kakoshi on 28-9-2011 dtd from tapping pole near this connection due to non payment of energy bill of AG Connection & found victim came with contact of live wire of 11 kv

Nilkanth AG feeder and got electric shok.

IERules-1956 as per section-82 Educate to consumer for inform to UGVCL office for any function works done near by electric line for avoid such type accident.

IERules-1956 as per section-82 Educate to consumer for inform to UGVCL office for any function works done near by electric line for avoid such type accident.

Field officers asked to take remedial measures as suggested by E/I.

Danger board & barbed wire provided no

FA/FH/NFH

Dept / O/S

1 2 3 4 6 7 8 9 10 11 125

Detailed Reason of AccidentFinding of CEI/EI/ AEI

Remedies suggested by CEI / EI/ AEI in various cases

Type of AccidentWhether the remedy suggested is complied

Action taken to avoid recurrence of such Accident.

Date of occurance

Compensation Paid

Sr. No.

CircleLocation

of Accident

Details of victim

157 PLN vill-Juna nesada

Owner of Cow -Bhopaji Dhudaji Thakor, FA (Cow) 15.10.11

A Fatal accident occurred to Cow due to Fire of Pin Insulator of 11 kv Manpura feeder conductor at location no-130/14/4 & found conductor broken which is fallown on ground, while Cow came with

contact of Live conductor & got electrical shock.

IERules-1956 as per section-29 maintenance work carried out periodically

IERules-1956 as per section-29 maintenance work carried out periodically

Field officers asked to take remedial measures as suggested by E/I.

Maintenance work carried out no

158 PLN Jetavas Ta : Danta

Buffaiow :-1 OF Shree Kharadi Pabubhai Devabhai

FA(Buffalo) 12.10.11

Animal Fatal Accident occurred due to broken of guy insulator of stay wire & earthing wire of village t/c. Due to broken guy insulator ,earthing wire is contacts with stay wire . So leakage current passes

through earthing wire to stay wire and Buffalow came in contact with stay wire & got electrocuted and died on spot.

IERules-1956 as per section-29 maintenance work carried out periodically

IERules-1956 as per section-29 maintenance work carried out periodically

Field officers asked to take remedial measures as suggested by E/I.

Maintenance work carried out no

159 PLN Jagana Owner of cow-Jarmol Nanajibhai Karasanbhai FA (Cow) 22.11.2011

HT. line one conductor broken and fall on ground from location no. 69 of 11 kv gujrat agro feeder due to pin puncture.cow came into cotact with live conductor and expired on the spot.at that time this

feeder not tripped.

IERules-1956 as per section-29 maintenance work carried out periodically

IERules-1956 as per section-29 maintenance work carried out periodically

Field officers asked to take remedial measures as suggested by E/I.

Maintenance work carried out no

160 PLN KalanaBuffalow :-1 OF Shree Patel Maganbhai Nagarbhai

FA(Buffalo)

30-11-11 reporting 13.2.12

A Fatal accident occurred due to leakage current flow surrounding AG T/C & Buffalo come near current flow area near T/C, At site observed Motor of AG connection found short so leakage current

flow through neutral of Transformer.& got electrical shock

IERules-1956 AS PER Section 67 give instruction to field office for reactivation of earthing of T/C for avoid such type of accident.

IERules-1956 AS PER Section 67 give instruction to field office for reactivation of earthing of T/C for avoid such type of accident.

Field officers asked to take remedial measures as suggested by E/I.

Reactivation of earthing of T/C no

161 SBT KadadaraShri Girishbhai Mithabhai Vohra & Shri Bhikhabhai Prajapati Helper

NFH Dept 15.11.11

The line clear of 11 KV Kadadara feeder of 66 KV Vehlal S/S was taken by Shri D.S.Tadgar on date 15/11/2011 at 10.30 am by phone with Line clear No 35134.and start work of jumpering on T/C at Bhagat farm, Zak Kadadara road .At 11.30 Hrs Shri L.S.Thakor,Helper had return the line clear of Pasunj ni Muvadi feeder taken vide L/C No 35133,By mistake SBO Shri R.D.kalasma of Vehlal S/S

had charged the breaker of Kadadara feeder instead of Pasunj ni Muvadi feeder, both victim working on line was got electic shock and fell down, Emergency medical treatment given to them at P.H.C

Vehlal & then admit to Appolo Hospital.

Awaited NA NA NA Not paid

162 SBT Hansalpur GIDC

Harshadbhai J Parmar, App LM NFH Dept 1.3.12,

12:10

While removing of single phase meter from GIDC at Rasiklal vadilal(jalaram) ind as per new GERC circular to merge meter the phase and natural wire accidently touch with one to another due to this

flash over occured and victim got flash on face and hands

ESI VISITED ON 13.3.12

Report awaited NA

Employee had given letter 1028/2.3.12 to take care in future & observed the safty rule.

Not paid

163 SBT Hansalpur GIDC

Arvindbhai Mathurbhai Patel, Helper NFH Dept 1.3.12,

12:30

While removing of single phase meter from GIDC at marshal agro ind as per new GERC circular to merge meter ,while cutting the insulation of phase wire accidently slips on main switch and touch with

live phase due to this flash over occures and victim got flash on face and hands

ESI VISITED ON 13.3.13

Report awaited NA

Employee had given letter 1029/2.3.12 to take care in future & observed the safty rule.

Not paid

FA/FH/NFH

Dept / O/S

1 2 3 4 6 7 8 9 10 11 125

Detailed Reason of AccidentFinding of CEI/EI/ AEI

Remedies suggested by CEI / EI/ AEI in various cases

Type of AccidentWhether the remedy suggested is complied

Action taken to avoid recurrence of such Accident.

Date of occurance

Compensation Paid

Sr. No.

CircleLocation

of Accident

Details of victim

164 SBT VavolShri Hareshbhai Jethabhai Marwadi App Age 14 Yrs

FH O/S

19.11.2011 / 12.30pm. reported by division on 15.12.2011

A Single phase conn is given in name of Shri J.L.Marwadi (26927/3416/10) In the load side single phase motor is used for the water supply in to the tank . At the time when the motor is running and the power supply is "ON" position. Victim touches to the metal part of body to fit pvc pipe to the exhaust

pipe of the motor and accident occur..

Awaited NA NA NA Not paid

165 SBT vavol Binkal Dineshbai Patel, Age: 22 Yrs. FH O/S 18.02.12 @

11:30 hrs.

A fatal human – Outsider electrical accident occurred on dtd, 18-02-2012 to shri Binkalkumar Dineshbhai Patel, Aged – 22 yrs (Approx) at village Vavol under Gandhinagar S/dn.At Accident site undersigned & Junior Engineer, have visit on dtd, 18-02-2012, @ 15.00 hrs, it is found above victim

was doing contactor’s work for providing Mandap at Newly opening site of Akshar Villa at village VAVOL for providing Steel pipe pole on the road side to mounting colored cloth FLAG. At that time above Steel pipe pole touched directly to overhead line passing from road of 11 KV Uvarsad AG

feeder. They have got electrolyte and referred to further treatment at private hospital but victim was dead.

Awaited NA NA NA Not paid

166 SBT

Nr. Shivalik villa, Rajpath Raod,Ambli

Shri Chetan Dhanjibhai Katariya (27 years)-FH & Shri Suresh Nathabhai parmar (27 years)- NFH

FH & NFH O/S 11.10.11 @ 9:42 AM

Victims(the labourers of Rajesh power Services p.ltd) were working on the DP structure(RSJ) to remove the fabrication/material, without any permission or intimation to the SDn office.M/s Rajesh

Power pvt ltd or any representative of agency had not intimated to this office nor asked for any shutdown on that day to carry out any work from their side.11 kv power of Rajpath fdr(Science City SS)

was going through the 70 mm2 XLPE cable from the same DP structure.There was a joint between incoming cable from RMU & outgoing cable to Society transformer, covering with PVC tape. Anyhow one Victim came in the cantact with the cable joint and at the same time other victim was fallen from

the DP structure to the ground.

Report awaited Report awaited Report

awaited

Contractor is given notice for not to do work without supervisor.

Not paid

167 SBT Matoda

Shri. Khori Aratbhai Amrabhai (FH) & Shri.Taviyad Aratbhai Hirabhai (NFH) Labou of contractor M/S. Prakash Electrical

FH & NFH O/S 1.03.2012While erecting 10 mtr. Psc pole with help of crain, pole tied with GI wire No.8 on top of the pole & top of the pole came in contact with live conductor of 11 kv Arvee Denim feeder emanating from 66 KV

moraiya S/s. & both victims getting electric Shock.

Report awaited Report awaited Report

awaited Line raising work completed Not paid

168 SBT Langhnaj Smt. Gitaben dalsukhbhai Raval (40 Years) NFH O/S 14-10-11

@17.00 hrs

The conductor of 11 Langhnaj(AG) feeder emanating from 66 kv Langhnaj s/s snapped due to bird fault and fell on her body. She was working in Agri. land under the line. Due to this she came in contact

with live broken conductor and got shock. She got burn injuries on right arm and leg.Awaited NA NA NA Not paid

169 SBT Shilaj Shri Jitendrabhai Maheshbhai Patel NFH O/S 14.11.11 at

23:00

Said victim is bollero vehicle driver and luggage was lying in the carrier. He went on the vehicle roof/carieer to took luggege and at the same time he might be came in the induction zone of live 11

kv line. Awaited NA NA NA Not paid

170 SBT Lodariyal Kishan Virambhai Koli Patel age- 10 year NFH O/S 17.01.2012

at 14:05

A nonfatal electrical accident occurred to a boy Kishan Virambhai Koli Patel age 10 years on dated 17.01.2012 at 14.05 Hrs.came in contact of live 11 kv Lodariyal feeder line passing over 2 feet above

on rooftop of house of Sh. Prahladbhai Chamanbhai Patel while catching the kite.

Report awaited Report awaited Report

awaited

Estimate for line shifting was given vide L No:-516 dt.23.03.10 but not paid till this date

Not paid

171 SBT Chandkheda

Damor Shardaben Thaneshwarbhai NFH O/S 05.02.12

In Consumer premises,LT side, Due to leakage in mono Submercible moter, current passing in watertank. During operating of Metalic Valve attached to watertank, victim came in contact with

leakage of current.Got shock. Awaited NA NA NA Not paid

172 SBTNR.SINDBAD HOTEL

Baldevbhai Dahyabhai Ravar(35 YRS.) NFH O/S 8.03.12 Victim was intensely climbed on pole and touch to the live line top of incoming side of Single Pole D.O.

structure of Nutan Balmandir School TC of 11KV Chatral Feeder Line yes To dismantle non used DPS

No,As,used for other connection

Fencing work carried Not paid

173 SBTSarjan Estate Kathwada

Shri Punitraj Ajaypratapsinh Rajput NFH O/S

29.10.11 at 2:00 reported on 30.03.12

An accident occurred was not reported at sl dn at that time by any offices i.e. Medical officer, Police station. &:party to s/dn. After receiving the letter from Electrical Insp. Vide letter no. EIA/932/2012Dtd. 29.2.2012 detail investigation done by s/dn and this report is submitted vide ref. letter. Looking to the report, an accident occurred at mid night approximately 2.30 hrs. during talking on mobile as no any eye witness so actual cause of accident not known. But as per P.M. report &:police panchnama the cause of accident is due to electric current. A memorandum of settlement dtd.12.12.2011 between

Victim's mother &:owner of factory was executed after payment of Rs. 600001 - by owner of factory.

EI VISIT ON 28.2.12 Report awaited NA NA Not paid

174 SBT Dhandhuka

owner -Shri Desai Yusufbhai Kalubhai

FA ( She Goat)

16-01.2012 nearly 9.00 AM

Single phase two core service wire is damaged and leakage current came through girder pole and she goat came contact with girder pole & died NO NO NO MAINTENANCE DONE Not paid

175 SBT Hudco/Singerwa

owner -Shri Baldevbhai Nagjibhai Rabari FA (Cow) 14.1.12,

15:20

Because of kite festival, kite got entangled on conductor of 11KV Kathwada-3 feeder Location No. 106 and due to pulling of same by children, conductor got snapped and fell on the cow passing below the

line hence got electrocuted

AEI VISTED ON 30.1.12

Report awaited NA Restring of conductor done on 14.1.12 Not paid

176 SBT

Viramgam near bharvadi darvaja

Owner Shri kanjibhai Vasibhai Rabari FA (Cow)

19.3.2012 at 12.15 hrs

A cow was passing near the transformer centre which was on plinth. The cow was scratching with the stay wire which broke and got entangled in the horns and the stay wire touched the jumper of the

X'mer centre and hence the cow got electrocuted.NA NA NA maintenance carried out on

19.3.12 Not paid

FA/FH/NFH

Dept / O/S

1 2 3 4 6 7 8 9 10 11 125

Detailed Reason of AccidentFinding of CEI/EI/ AEI

Remedies suggested by CEI / EI/ AEI in various cases

Type of AccidentWhether the remedy suggested is complied

Action taken to avoid recurrence of such Accident.

Date of occurance

Compensation Paid

Sr. No.

CircleLocation

of Accident

Details of victim

177 SBT Cha.vasana

owner -Bharvad Haribhai Surabhai

FA(Buffalo)

03.02.12 at 15:35

While rubbing the head with loose stay wire by victim buffalo at cha.vasna -claris road at loc no 43 & 44 (D.P. AB switch Structure)of 11 kv Bhat feeder (Ag feeder), loose stay wire came in contact with the jumper of switch below the stay insulator part and so leakage current pass through the body of

victim buffalo so got electrocuted and met with FA.

Report awaited Report awaited Report

awaitedBroken service wire is removed at these time Not paid

Within 50% of

stipulated time

Within stipulated

time

Upto double the stipulated

time

More than double the stipulated

time

1 2 3 4 5 6 7 8 9 10 11

A(i) 0 169383 169383 65123 104260 0 0 169383 0 Loose conn. from pole

A(ii) 0 32086 32086 17970 14116 0 0 32086 0 Int.due to line breakdown

A(iii) 0 12429 12429 7212 5217 0 0 12429 0 Interruption due to failure of transformer

B(i) 0 4986 4986 3362 1624 0 0 4986 0 Ordinary case, which requires no augmentation

B(ii) 0 3246 3246 1862 1384 0 0 3246 0 Where augmentation is required

C(i) 0 15205 15205 8772 6433 0 0 15205 0 Stopped/Defective Meters

C(ii) 0 5271 5271 2701 2570 0 0 5271 0 Billing on average basis for more than two bills

D(i) 0 10827 10827 6266 4561 0 0 10827 0 Loose Wires

D(ii) 0 1819 1819 1243 576 0 0 1819 0 Inadequate ground clearance

E(i) 0 5905 5905 2949 2956 0 0 5905 0 For current bills where no additional information is required

E(ii) 0 3134 3134 1747 1387 0 0 3134 0 Where additional information relating to correctness of reading etc. is required

F(i) 0 4014 4014 2049 1965 0 0 4014 0 Where extension of mains is not required

F(ii) 0 1955 1955 887 1068 0 0 1955 0 Where extension of mains is required

F(iii) 0 3474 3474 2405 1069 0 0 3474 0 Modification in connected load

F(iv) 0 8832 8832 3646 5186 0 0 8832 0 Name change/reconnection

G 0 1213 1213 762 451 0 0 1213 0 Refund of amount due in regard to temporary connection

H 0 25500 25500 11046 14454 0 0 25500 0 Others

Total 0 309279 309279 140002 169277 0 0 309279 0

ANNUAL REPORT- April-11 to March-12

Uttar Gujarat Vij Company Ltd ,Mehsana

Classification of complaint

REGISTER FOR COMPILING THE COMPLAINTS CLASSIFICATIONWISE

APPENDIX - B (already in the SoP regulation )

Performa SoP 003 B:YEAR :-2011-12

Classification

Pending complaintof previous

Year

Balance complaints

to be redressed (4)

- (9)

In stipulated time Beyond stipulated timeNo.of complaints redressed during the Year

Total (5) to (8)

Complaints received

during the Year

Total complaints

C:\Users\ubchauhan5032\Desktop\ANNUAL_SOP_Report-2011-12_

Sr. No. Actons or steps carried out by distribution licensee towards public awareness in the Year Likely number of consumers influrenced Details about media

1 2 3

1 Display board of SOP at circle, Division & S/Dn 263704 Notice Board

2 Display board of Name of information officers under RTI Act 2005 at Circle,Division,Sub- division offices. 258072 Notice Board

3 Consumer care centers at various places 329749 Verbal & Notice Board at CCC

4 Advertisement through Daily News papers 23084 Daily News papers

5 Pamphlets distributed among public 231225 Pamphlets

6 Advertisement through slide in TV / Banners 385900 T V Channels

7 On Uttar Gujarat Vij Company Ltd Web site 171381 Internate

8 Through Regular Energy Bill 4492353 Energy Bill

9 Others 1472858 CD

Uttar Gujarat Vij Company Ltd ,MehsanaANNUAL REPORT- April-11 to March-12

YEAR :-2011-12

Performa SoP 004

C:\Users\ubchauhan5032\Desktop\ANNUAL_SOP_Report-2011-12_

Sr. No. Month Date and time meeting conducted

No. of complaints registered at the

meeting

No. of complaints pending at the end of

the meeting27.4.11:11.00 am 10 428.4.11:11.00 am 4 18.6.11:11.00 am 14 229.6-11:11.00 am 16 7

3 July.-11 20.7.11 at 11.00 12 54 August.-11 24.8.11 at 11.00 15 5

8.09.11 at 11.00 8 223.09.11 at 11.00 8 227.09.11 at 11.00 5 528.09.11 at 11.00 6 129.09.11 at 11.00 7 115-12-2011 at 11.00am 19 926-12-2011 at 11.00am 20 827-12-2011 at 11.00am 21 828-12-2011 at 11.00am 20 525-01-2012 21 727-01-2012 13 514-02-2012 26 918-02-2012 21 921-02-2012 15 728-02-2012 9 52/3/2012 15 514-03-2012 11 316-03-2012 12 323-03-2012 16 430-03-2012 17 3

Jun-112

1

Uttar Gujarat Vij Company Ltd ,Mehsana

Performa SoP 005 B: Action taken report by the Redressal Committee

Apr-11

ANNUAL REPORT- April-11 to March-12YEAR :-2011-12

8 Feb-12

9 Mar-12

7 Jan-12

September.115

6 Dec-11

C:\Users\ubchauhan5032\Desktop\ANNUAL_SOP_Report-2011-12_

Sr. No.

No. of existing Distribution transformer at the start of the Year

01.04.2011

No.of Distribution transformers added during

the Year

Tota number of Distribution transformers

As on 30.03.12

Total number of Distribution

tranformer failed during the Year

% failure rate of Distribution

transformer during the Year

A B C=A+B D H= (D) * 100/C

1 124128 8387 132515 10792 8.14

Uttar Gujarat Vij Company Ltd ,Mehsana

Performa SOP 006 : Failure of Distribution Transformer.

ANNUAL REPORT- April-11 to March-12

YEAR :-2011-12

C:\Users\ubchauhan5032\Desktop\ANNUAL_SOP_Report-2011-12_

1 2 3 4 5 6

Sr.No Category of consumers

Sample Size

(Numbers)

Standard specified in regulation

Deviation of results from the

sample test (Numbers)

% age compliance

=5*100/3

1 Domestic 668224 2% 8211 1.23

2 Commercial 83243 2% 451 0.54

3 Industrial 11891 2% 87 0.73

4 Agricultural 129534 2% 2956 2.28

5 Public water works 4040 2% 28 0.69

6 HT industrial 1251 2% 1 0.08

H T consumers

Uttar Gujarat Vij Company Ltd ,MehsanaYearly Submission

YEAR :-2011-12

Performa SoP 008 : Sample Test result for Neutral Voltage

Compliance Sample Test Report for Neutral Voltage

L T consumers

1 2 3 4 5

Voltage Level Sample Size (Numbers)

Limit or prescribed standard

Deviation of results from the sample test

(Numbers)

% age compliance =4*100/2

Low Voltage 707536 +6% to -6%' 3283 0.46

High Voltage 579 +6% to -6%' 12 2.07

Extra High Voltage 9 +10% to -10%' 0 0.00

Compliance Sample Test Report for Voltage variations

Uttar Gujarat Vij Company Ltd ,MehsanaYearly Submission

YEAR :-2011-12

Performa SoP 009 : Sample result for Voltage variations

1 2 3 4 5 6

Sr.No Category of consumers

Sample Size (Numbers)

Limit or standard prescribed

Deviation of results from the sample test

(Numbers)

% age compliance =5*100/3

1 L T consumers 705802 3.50% 0 0.00

2 HT consumers 251 3.00% 0 0.00

3EHT consumers 3 3.00% 0 0.00

Compliance Sample Test Report for Harmonics

Uttar Gujarat Vij Company Ltd ,MehsanaYearly Submission

YEAR :-2011-12Performa SoP 010 : Sample Test result for Harmonics

SoP 011 - A : System Average Interrruption Frequency Index (SAIFI) for AG. category

Sr.No YEAR

Ni - Number of Customers for each sustained interruptions (in

numbers)

NT - Total No of customers

served (in Numbers)

SAIFI = Ni/Nt(Monthly SAIFI)

1 2 3 4 5= 3 / 41 April.11 97022 294915 0.332 May.11 147620 297636 0.503 June.11 249477 305796 0.824 July.11 709445 307227 2.315 August.11 653503 335309 1.956 Sept.11 490276 342590 1.437 Oct.11 348808 336105 1.048 Nov.11 172349 345382 0.509 Dec.11 146323 351710 0.42

10 Jan.12 143105 350873 0.4111 Feb.12 106188 356655 0.3012 March.12 108533 358980 0.30

Uttar Gujarat Vij Company Ltd ,MehsanaANNUAL REPORT- April-11 to March-12

Year 2011-12

C:\Users\ubchauhan5032\Desktop\ANNUAL_SOP_Report-2011-12_

Uttar Gujarat Vij Company Ltd ,MehsanaANNUAL REPORT- April-11 to March-12

Year 2011-12SoP 011 - B : System Average Interrruption Duration Index (SAIDI) for AG. category

Sr.No YEAR

Ri =Restoration Time

for each sustained

interruption event

Ni - Number of interrupted

Customers for each sustained

interruption event

Ri* Ni -Total customer

interrution Duration

NT - Total No of

customers served

(in Numbers)

SAIDI = Ri*Ni/Nt(Monthly SAIDI)

1 2 3 4 5 = 3 * 4 6 7= 5 / 61 April.11 790:31:00 162 127838:25:00 294915 0:26:012 May.11 1321:48:40 150 198443:47:00 297635 0:40:003 June.11 2843:55:00 153 434879:36:23 305796 1:25:204 July.11 7892:02:25 177 1396044:51:40 327227 4:15:595 August.11 6036:40:20 191 1154226:25:00 335309 3:26:326 Sept.11 3775:32:51 223 840413:21:50 342590 2:27:117 Oct.11 2281:46:00 1509 597363:58:00 336105 1:46:388 Nov.11 1378:42:00 976 264952:33:00 345382 0:46:029 Dec.11 1248:37:50 891 231253:48:30 351710 0:39:27

10 Jan.12 1210:23:00 189 229343:47:00 350873 0:39:1311 Feb.12 904:45:45 180 162895:17:30 356655 0:27:2412 March.12 823:06:00 198 163167:21:00 358980 0:27:16

C:\Users\ubchauhan5032\Desktop\ANNUAL_SOP_Report-2011-12_

Uttar Gujarat Vij Company Ltd ,MehsanaANNUAL REPORT- April-11 to March-12

Year 2011-12SoP 011 - C : Momentary Average Interruption Frequency Index (MAIFI) for AG. category

Sr.No YEAR

IMi =Number of Momentary

interruptions for the month

(in numbers)

Nmi =Total no of

customers for each

momentary interruptions (in numbers)

Imi =Nmi

Number of customer

Mementary interruptions(in numbers)

Nt -Total no of customers

served(in

numbers)

MAIFI=Imi*Nmi/

Nt

1 2 3 4 5 = 3 * 4 6 7= 5 / 61 April.11 7546 159 119834 294914 4.072 May.11 8135 156 1273115 297635 4.283 June.11 9604 156 1497846 305796 4.94 July.11 14682 158 2314882 327227 7.075 August.11 13676 167 2284187 335309 6.816 Sept.11 12538 171 2146701 342590 6.277 Oct.11 10679 185 1974175 336105 5.878 Nov.11 9181 163 1496662 345382 4.339 Dec.11 8068 156 1255372 351710 3.57

10 Jan.12 6892 165 1136863 350873 3.2411 Feb.12 6051 160 970561 356655 2.7212 March.12 7380 157 1158068 358980 3.23

C:\Users\ubchauhan5032\Desktop\ANNUAL_SOP_Report-2011-12_

Sr.No Month

Ni - Number of Customers for each sustained

interruptions (in numbers)

NT - Total No of customers served

(in Numbers)

SAIFI = Ni/Nt(Monthly SAIFI)

1 2 3 4 5= 3 / 41 April.11 567371 1626602 0.352 May.11 673940 1603315 0.423 June.11 1524868 1613647 0.944 July.11 4002581 1641110 2.445 August.11 3426901 1662151 2.066 Sept.11 2929363 1652721 1.597 Oct.11 1515159 1615563 0.948 Nov.11 655728 1633445 0.409 Dec.11 668283 1632423 0.41

10 Jan.12 746253 1623439 0.4611 Feb.12 479449 1631444 0.2912 March.12 565433 1682727 0.34

Uttar Gujarat Vij Company Ltd ,MehsanaANNUAL REPORT- April-11 to March-12

YEAR :-2011-12

SoP 011 - A : System Average Interrruption Frequency Index (SAIFI) for JGY category

C:\Users\ubchauhan5032\Desktop\ANNUAL_SOP_Report-2011-12_

Uttar Gujarat Vij Company Ltd ,MehsanaANNUAL REPORT- April-11 to March-12

YEAR :-2011-12

Sr.No Month

Ri =Restoration Time for each

sustained interruption event

(in hours)

Ni - Number of interrupted Customers

for each sustained interruption event

(in numbers)

Ri* Ni -Total customer

interrution Duration

NT - Total No of customers served

(in Numbers)

SAIDI = Ri*Ni/Nt(Monthly SAIDI)

1 2 3 4 5 = 3 * 4 6 7= 5 / 61 April.11 189:04:00 2607 492929:23:24 1626602 0:18:112 May.11 278:11:24 2454 682651:42:36 1603315 0:25:333 June.11 670:02:20 2368 1586470:54:46 1613647 0:58:594 July.11 2181:29:00 2597 5665751:06:00 1641110 3:27:095 August.11 1585:22:15 2704 4286273:59:50 1662151 2:34:446 Sept.11 1219:20:00 2875 3505855:51:00 1652721 2:07:177 Oct.11 681:44:00 2598 1771395:22:00 1615563 1:05:478 Nov.11 260:15:00 2900 754758:52:00 1633445 0:27:439 Dec.11 277:05:00 2886 799573:17:00 1632423 0:29:23

10 Jan.12 274:25:00 3129 858684:20:00 1623439 0:31:4411 Feb.12 160:55:00 3426 551307:26:00 1631444 0:20:1712 March.12 214:41:00 2911 625016:41:00 1682727 0:22:17

SoP 011 - B : System Average Interrruption Duration Index (SAIDI) for JGY category

C:\Users\ubchauhan5032\Desktop\ANNUAL_SOP_Report-2011-12_

Uttar Gujarat Vij Company Ltd ,MehsanaANNUAL REPORT- April-11 to March-12

YEAR :-2011-12

Sr.No Month

IMi =Number of Momentary interruptions for the

month(in numbers)

Nmi =Total no of customers for each momentary

interruptions (in numbers)

Imi =Nmi

Number of customer Mementary

interruptions(in numbers)

Nt -Total no of

customers served(in numbers)

MAIFI=Imi*Nmi/

Nt

1 2 3 4 5 = 3 * 4 6 7= 5 / 61 April.11 4758 2585 12300850 1626602 7.562 May.11 4473 2643 11821128 1603315 7.373 June.11 5282 2690 14206722 1613647 8.84 July.11 6975 2622 18288124 1641110 11.145 August.11 7274 2600 18914369 1662151 11.386 Sept.11 6792 2601 17665813 1652721 10.697 Oct.11 6214 2614 16241233 1615563 10.058 Nov.11 5183 2670 13840006 1633445 8.479 Dec.11 4523 2704 12229555 1632423 7.49

10 Jan.12 4113 2734 11246085 1623439 6.9311 Feb.12 3458 2749 9504335 1631444 5.8312 March.12 4036 2646 10678015 1682727 6.35

SoP 011 - C : Momentary Average Interruption Frequency Index (MAIFI) for JGY category

C:\Users\ubchauhan5032\Desktop\ANNUAL_SOP_Report-2011-12_

Sr.No Month

Ni - Number of Customers for each

sustained interruptions (in

numbers)

NT - Total No of customers served

(in Numbers)

SAIFI = Ni/Nt(Monthly SAIFI)

1 2 3 4 5= 3 / 41 April.11 137735 750321 0.182 May.11 233993 758883 0.313 June.11 608574 775761 0.784 July.11 1281838 749134 1.715 August.11 807034 739760 1.096 Sept.11 601592 747751 0.817 Oct.11 871722 748758 1.168 Nov.11 311959 796246 0.399 Dec.11 138351 794287 0.17

10 Jan.12 233415 794287 0.2911 Feb.12 144525 795609 0.1812 March.12 166592 808820 0.21

Uttar Gujarat Vij Company Ltd ,MehsanaANNUAL REPORT- April-11 to March-12

YEAR :-2011-12SoP 011 - A : System Average Interrruption Frequency Index (SAIFI) for Other than AG & JGY category

C:\Users\ubchauhan5032\Desktop\ANNUAL_SOP_Report-2011-12_

Uttar Gujarat Vij Company Ltd ,MehsanaANNUAL REPORT- April-11 to March-12

YEAR :-2011-12

Sr.No Month

Ri =Restoration Time for

each sustained interruption event

(in hours)

Ni - Number of interrupted

Customers for each sustained

interruption event(in numbers)

Ri* Ni -Total customer

interrution Duration

NT - Total No of customers served

(in Numbers)

SAIDI = Ri*Ni/Nt(Monthly SAIDI)

1 2 3 4 5 = 3 * 4 6 7= 5 / 61 April.11 70:09:00 1441 101080:21:00 750321 0:08:052 May.11 120:57:00 1118 135214:55:00 758883 0:10:413 June.11 348:48:00 1771 617864:31:00 775761 0:47:474 July.11 711:43:00 1734 1234347:11:00 749134 1:38:525 August.11 416:40:55 1822 759068:26:20 739760 1:01:346 Sept.11 286:47:00 1644 471466:41:00 747751 0:37:507 Oct.11 116:14:00 6712 780138:54:00 748758 1:02:318 Nov.11 104:55:00 1722 180633:26:00 796246 0:13:379 Dec.11 67:31:00 1458 98408:23:00 794287 0:07:26

10 Jan.12 110:44:00 1724 190953:26:00 794287 0:14:2511 Feb.12 91:51:00 1167 107185:10:00 795609 0:08:0512 March.12 83:41:00 1663 139122:04:00 808820 0:10:19

SoP 011 - B : System Average Interrruption Duration Index (SAIDI) forOther than AG & JGY category

C:\Users\ubchauhan5032\Desktop\ANNUAL_SOP_Report-2011-12_

Uttar Gujarat Vij Company Ltd ,MehsanaANNUAL REPORT- April-11 to March-12

YEAR :-2011-12

Sr.No Month

IMi =Number of Momentary

interruptions for the month

(in numbers)

Nmi =Total no of customers for each momentary

interruptions (in numbers)

Imi =Nmi

Number of customer

Mementary interruptions(in numbers)

Nt -Total no of

customers served(in numbers)

MAIFI=Imi*Nmi/

Nt

1 2 3 4 5 = 3 * 4 6 7= 5 / 6

1 April.11 1609 2037 3278040 750321 4.372 May.11 1523 2067 3148678 758883 4.153 June.11 1931 2486 4800377 775761 6.194 July.11 2761 2449 6760448 749134 9.025 August.11 2412 2308 5567114 739760 7.536 Sept.11 2126 2256 4796635 747751 6.417 Oct.11 1873 4153 7778056 748758 10.398 Nov.11 1574 2463 3876325 796246 4.879 Dec.11 1435 2726 3912322 794287 4.93

10 Jan.12 1684 2860 4816382 794287 6.0611 Feb.12 1363 2224 3030693 795609 3.8112 March.12 1484 2290 3398268 808820 4.20

SoP 011 - C : Momentary Average Interruption Frequency Index (MAIFI) for Other than AG & JGY category

C:\Users\ubchauhan5032\Desktop\ANNUAL_SOP_Report-2011-12_

Sr.No Month

Ni - Number of Customers for each

sustained interruptions (in

numbers)

NT - Total No of customers served

(in Numbers)

SAIFI = Ni/Nt(Monthly SAIFI)

1 2 3 4 5= 3 / 4

April.11 802128 2671838 0.3May.11 1055552 2684215 0.39June.11 2382918 2706640 0.88July.11 5998804 2717471 2.21

August.11 4887438 2737220 1.79Sept.11 3721234 2743062 1.36Oct.11 2735689 2700426 1.01Nov.11 1140036 2775073 0.41Dec.11 952957 2778420 0.34Jan.12 1122773 2768599 0.41Feb.12 730162 2783708 0.26

March.12 840558 2850527 0.29

Uttar Gujarat Vij Company Ltd ,MehsanaANNUAL REPORT- April-11 to March-12

YEAR :-2011-12SoP 011 - A : System Average Interrruption Frequency Index (SAIFI) for UGVCL as a whole

Uttar Gujarat Vij Company Ltd ,MehsanaANNUAL REPORT- April-11 to March-12

YEAR :-2011-12

Sr.No Month

Ri =Restoration Time for

each sustained interruption event

(in hours)

Ni - Number of interrupted

Customers for each sustained

interruption event(in numbers)

Ri* Ni -Total customer

interrution Duration

NT - Total No of customers

served (in Numbers)

SAIDI = Ri*Ni/Nt(Monthly

SAIDI)

1 2 3 4 5 = 3 * 4 6 7= 5 / 6April.11 1049:44:00 906 721848:09:24 2671838 0:16:13May.11 1720:57:04 1444 1016310:24:36 2684215 0:22:43June.11 3862:45:20 2448 2639215:02:09 2706640 0:58:30July.11 10785:14:25 769 9296143:08:40 2717471 3:03:01

August.11 8038:43:30 771 6199568:51:10 2737220 2:15:54Sept.11 5281:39:50 912 4817735:53:50 2743062 1:45:23Oct.11 1593:13:50 1976 3148898:14:00 2700426 1:09:58Nov.11 1743:52:00 688 1200344:51:00 2775073 0:25:57Dec.11 1593:13:50 709 1129235:28:30 2778420 0:24:23Jan.12 1595:32:00 802 1278981:33:00 2768599 0:27:43Feb.12 1157:31:45 710 821387:53:30 2783708 0:17:42

March.12 1121:28:00 827 927306:06:00 2850527 0:19:31

SoP 011 - B : System Average Interrruption Duration Index (SAIDI) for UGVCL as a whole

Uttar Gujarat Vij Company Ltd ,MehsanaANNUAL REPORT- April-11 to March-12

YEAR :-2011-12

Sr.No Month

IMi =Number of Momentary interruptions for the

month(in numbers)

Nmi =Total no of customers for each momentary

interruptions (in numbers)

Imi =Nmi

Number of customer Mementary

interruptions(in numbers)

Nt -Total no of customers

served(in numbers)

MAIFI=Imi*Nmi/

Nt

1 2 3 4 5 = 3 * 4 6 7= 5 / 6April.11 13913 1206 16777824 2671838 6.28May.11 14131 1149 16242921 2684215 6.05June.11 16817 1219 20504946 2706640 7.58July.11 24418 1121 27363454 2717471 10.07

August.11 23362 1146 26765670 2737220 9.78Sept.11 21156 1147 24609149 2743062 8.97Oct.11 18766 1385 25993464 2700426 9.63Nov.11 15938 1205 19212993 2775073 6.92Dec.11 14026 1214 17397249 2778420 6.26Jan.12 12689 1355 17199330 2768599 6.21Feb.12 10872 1242 13505589 2783708 4.85

March.12 12900 1181 15234351 2850527 5.34

SoP 011 - C : Momentary Average Interruption Frequency Index (MAIFI) for UGVCL as a whole

i Energy Delivered into EHT / 11 KV and LT Distribution System from EHT / 11 KV SS (Mus) A 15861.898

ii Energy Sold (Billed) EHT direct sales (Mus) B 872.10

iii Energy Sold (Billed) in the 11 KV LT system (Mus) C 13384.397

iv Total Sales (Mus) (B+C) 14256.50

v Losses (Mus) {(A) - (B+C)} 1605.40

vi % Losses {(A) - (B+C)} X 100 / (A) 10.12

Losses in 11 KV System and Connected Equipment

Uttar Gujarat Vij Company Ltd ,Mehsana Yearly April-11 To March-12

Performance SoP 012 - System Losses at EHT / 11 KV and below SoP 012 - CALCULATION OF SYSTEM LOSSES AT EHT / 11 KV

Consumer Category

No. of faulty meters at the start of the

Year

No. of faulty meters added

during the Year

Total No. of defective / faulty

meter

No. of faulty Meters repaired and

replaced during the Year

No. of faulty meters pending at the end

of the Year

1 2 3=2+1 4 5=3-4

Single Phase 15039 97605 112644 111225 1419

Three Phase 639 9171 9810 9805 5

H.T. 0 46 46 46 0

Uttar Gujarat Vij Company Ltd ,Mehsana

Performa SOP 013 : Meter faults

ANNUAL REPORT- April-11 to March-12

YEAR :-2011-12

C:\Users\ubchauhan5032\Desktop\ANNUAL_SOP_Report-2011-12_

Qtr. Months Units input (Mus)

Units Billed (Mus)

Billing Efficiency

Revenue Billed

(Rs. Lacs)

Revenue Collected (Rs.

Lacs)

Collection Efficiency %

Business Efficiency ATC Loss %

A B C=(B/A)*100 D E F=(E/D)*100 G=(C*F)/100 H=100-G

April'11 1433.57 1139.25 79.47 363 375 103.51 82.26 17.74

May'11 1505.58 1160.15 77.06 366 362 98.87 76.19 23.81

June'11 1420.80 1153.40 81.18 407 392 96.16 78.06 21.94

Sub Total 4360 3453 79.19 1136 1129 99.38 78.70 21.30

July'11 998.8 966.3 96.74 356 360 101.09 97.80 2.20

Aug.'11 857.0 912.3 106.46 393 400 101.67 108.24 -8.24

Sept.'11 845.2 918.3 108.64 359 380 105.93 115.08 -15.08

Sub Total 2701 2796.874 100.00 1107.71 1139 100.00 100.00 0.00

Oct'11 1431.2 1210.8 84.60 370 360 97.19 82.22 17.78

Nov'11 1486.0 1312.4 100.00 374 451 120.53 120.53 -20.53

Dec'11 1493.4 1317.8 88.24 423 412 97.25 85.82 14.18

Sub Total 4411 3840.98 87.09 744 810 100.00 87.09 12.91

Jan'12 1464.10 1355.97 92.61 385 352 91.46 84.70 15.30

Feb'12 1413.73 1375.24 97.28 473 628 132.76 129.15 -29.15

March'12 1510.87 1432.17 94.79 432 301 69.80 66.16 33.84

Sub Total 4389 4163.39 94.87 2025 2202 100.00 94.87 5.13

V Grand Total 15860 14254 89.87 5012 5280 100.00 89.87 10.13

**

IV

The details are updated for FY 2011-12 as per CGL Report.

Efficency above 100% is taken as 100%

Uttar Gujarat Vij Company Ltd ,MehsanaYear 2011-12

Performa SoP 014: Statement Showing the ATC losses, collection efficiency and Billing Efficiency

I

II

III

Sr. No. Event Compensation No. of cases where

compensation was given (in numbers)

Amt.of compensation paid (in Rs.)

Duty to provide supply

a) New connection

b) Additional load

c) Temporary supply

d) Shifting service connection

e) Transfer of service connectionf) Change in tariff category of consumer

2 Complaints in billing Rs.50 for non reply within the period prescribed in Regulations

3 Replacement of meters LT Rs.25 per day of delay maximum Rs.2,500 and HT Rs. 250 per day of delay maximum of Rs. 5,000/-

4 Interruption of supplyLT Rs.25 for every 6 hrs. of delay maximum of Rs.500 and HT Rs. 50 for every 6 hrs. delay maximum Rs. 1000

5 Voltage fluctuations and complaints

Rs.50 for failure to visit or convey findings wihin the stipulated period

6 Responding to consumers complaints

Rs. 25 for each day of delay maximum Rs. 500

7 Grievance Handling Rs. 25 for failure in handling grievance.

TOTAL :- …NIL… ……NIL…..

Rs.50 per day of delay from the limit specified in the performance regulations

1

Uttar Gujarat Vij Company Ltd ,Mehsana

Performa SoP 016 : Compensation details

COMPENSATION DETAILS

ANNUAL REPORT- April-11 to March-12

YEAR :-2011-12

C:\Users\ubchauhan5032\Desktop\ANNUAL_SOP_Report-2011-12_


Recommended