INDUSTRIAL SYSTEMS, INC. ELEVATOR CODE LUNCH AND LEARN. EFFECTIVE 9-1-2008. TDLR ADOPTED THE CODE PUBLISHED BY THE AMERICAN SOCIETY OF MECHANICAL ENGINEERS (ASME) REGARDING DRAINAGE OF ELEVATOR SUMPS CONSTRUCTION FOR WHICH A CONTRACT IS EXECUTED AFTER - PowerPoint PPT Presentation
19
INDUSTRIAL SYSTEMS, INDUSTRIAL SYSTEMS, INC. INC. ELEVATOR CODE ELEVATOR CODE LUNCH AND LEARN LUNCH AND LEARN
Transcript
Page 1: INDUSTRIAL SYSTEMS, INC.

INDUSTRIAL SYSTEMS, INC.INDUSTRIAL SYSTEMS, INC.

ELEVATOR CODEELEVATOR CODE

LUNCH AND LEARNLUNCH AND LEARN

Page 2: INDUSTRIAL SYSTEMS, INC.

EFFECTIVE 9-1-2008EFFECTIVE 9-1-2008 TDLR ADOPTED THE CODE PUBLISHED TDLR ADOPTED THE CODE PUBLISHED

BY THE AMERICAN SOCIETY OF BY THE AMERICAN SOCIETY OF MECHANICAL ENGINEERS (ASME) MECHANICAL ENGINEERS (ASME) REGARDING DRAINAGE OF ELEVATOR REGARDING DRAINAGE OF ELEVATOR SUMPSSUMPS

CONSTRUCTION FOR WHICH A CONSTRUCTION FOR WHICH A CONTRACT IS EXECUTED AFTER CONTRACT IS EXECUTED AFTER

9-1-08, THE HOSE BIBB , MANUAL 9-1-08, THE HOSE BIBB , MANUAL SWITCH AND DRUM APPROACH WILL SWITCH AND DRUM APPROACH WILL NO LONGER BE PERMITTED.NO LONGER BE PERMITTED.

Page 3: INDUSTRIAL SYSTEMS, INC.

SUMP PUMPS AND DRAINS SHALL SUMP PUMPS AND DRAINS SHALL AUTOMATICALLY REMOVE FLUID FROM AUTOMATICALLY REMOVE FLUID FROM ALL ELEVATOR PITS WITHOUT ALL ELEVATOR PITS WITHOUT ANY ANY HUMAN INTERVENTION!HUMAN INTERVENTION!

THE LOCALITIES AND THE TEXAS THE LOCALITIES AND THE TEXAS COMMISSION OF EVIRONMENTAL COMMISSION OF EVIRONMENTAL QUALITY (TCEQ) SHALL REGULATE QUALITY (TCEQ) SHALL REGULATE WHAT CAN BE DONE WITH THE WHAT CAN BE DONE WITH THE DISCHARGED FLUID AFTER IT IS DISCHARGED FLUID AFTER IT IS AUTOMATICALLY REMOVED FROM THE AUTOMATICALLY REMOVED FROM THE ELEVATOR PITELEVATOR PIT

Page 4: INDUSTRIAL SYSTEMS, INC.

ASME A 17.1 SECTION 2.2.2.5ASME A 17.1 SECTION 2.2.2.5(DESIGN AND CONSTRUCTION (DESIGN AND CONSTRUCTION

OF ELEVATOR PITS)OF ELEVATOR PITS) 2.2.2.5 “ IN ELEVATORS PROVIDED 2.2.2.5 “ IN ELEVATORS PROVIDED

WITH FIREFIGHTERS EMERGENCY WITH FIREFIGHTERS EMERGENCY OPERATION, A DRAIN OR SUMP PUMP OPERATION, A DRAIN OR SUMP PUMP SHALL BE PROVIDED AS WELL. THE SHALL BE PROVIDED AS WELL. THE SUMP PUMP OR DRAIN SHALL HAVE SUMP PUMP OR DRAIN SHALL HAVE THE CAPACITY TO REMOVE A MINIMUM THE CAPACITY TO REMOVE A MINIMUM OF 11.4 CU. METERS PER HOUR (3,000 OF 11.4 CU. METERS PER HOUR (3,000 GALLONS PER HOUR).”GALLONS PER HOUR).”

Page 5: INDUSTRIAL SYSTEMS, INC.

WHY?WHY? THE INTENT AND TDLR’S THE INTENT AND TDLR’S

INTERPRETATION OF THE RULE IS FOR INTERPRETATION OF THE RULE IS FOR WATER AND WATER/ WITH ANY OTHER WATER AND WATER/ WITH ANY OTHER SUBSTANCE TO BE REMOVED SUBSTANCE TO BE REMOVED AUTOMATICALLY SO AN ELEVATOR AUTOMATICALLY SO AN ELEVATOR CAN CONTINUE TO BE AVAILIBLE FOR CAN CONTINUE TO BE AVAILIBLE FOR USE IN AN EMERGENCY SUCH AS A USE IN AN EMERGENCY SUCH AS A FIRE. FIRE.

Page 6: INDUSTRIAL SYSTEMS, INC.

THE FOLLOWING COMPONENTS THE FOLLOWING COMPONENTS “ARE PROHIBITED”“ARE PROHIBITED”

A.A. LOCAL ELEVATOR SUMP PUMP MANUAL LOCAL ELEVATOR SUMP PUMP MANUAL SWITCHING.SWITCHING.

B.B. MANUAL DRUM AND BARREL SWITCHINGMANUAL DRUM AND BARREL SWITCHING

C.C. SUMP PUMP DISCHARGE/TERMINATIONSUMP PUMP DISCHARGE/TERMINATION TO A HOSE BIB.TO A HOSE BIB.

Page 7: INDUSTRIAL SYSTEMS, INC.

THE FOLLOWING IS AN THE FOLLOWING IS AN ACCEPTED PRACTICEACCEPTED PRACTICE

THE DRAIN FROM THIS SUMP PUMP THE DRAIN FROM THIS SUMP PUMP WILL BE ALLOWED TO TERMINATE WILL BE ALLOWED TO TERMINATE WATER INTO THE SEWER SYSTEM. WATER INTO THE SEWER SYSTEM.

ALL OF THE ALARMS FOR NOTICATION ALL OF THE ALARMS FOR NOTICATION AND PROPER AUTOMATIC FUNCITON AND PROPER AUTOMATIC FUNCITON OF THE PUMP SYSTEM SHALL BE OF THE PUMP SYSTEM SHALL BE INSTALLED.INSTALLED.

Page 8: INDUSTRIAL SYSTEMS, INC.

COMMON QUESTIONSCOMMON QUESTIONS

DOES THE CODE REQUIRE THAT DOES THE CODE REQUIRE THAT MULTIPLE ELEVATORS IN A SINGLE MULTIPLE ELEVATORS IN A SINGLE HOISTWAY HAVE A SUMP PUMP FOR HOISTWAY HAVE A SUMP PUMP FOR EACH ELEVATOR?EACH ELEVATOR?

ARE ALL SUMP PUMPS AND ARE ALL SUMP PUMPS AND AUTOMATIC CONTROLS CREATED AUTOMATIC CONTROLS CREATED EQUAL?EQUAL?

Page 9: INDUSTRIAL SYSTEMS, INC.

WHAT SHOULD MY PIT SIZE BE?WHAT SHOULD MY PIT SIZE BE? The recommended 50 GPM Sump Pit size is The recommended 50 GPM Sump Pit size is

24”x24”x24”24”x24”x24”

WHAT DOSE COSA SAY ABOUT DIRECT WHAT DOSE COSA SAY ABOUT DIRECT DISCHARGE INTO THE SEWER?DISCHARGE INTO THE SEWER?

WHAT DOSE COSA SAY ABOUT A WHAT DOSE COSA SAY ABOUT A WATER/OIL SEPARATOR?WATER/OIL SEPARATOR?

Page 10: INDUSTRIAL SYSTEMS, INC.

NEC QUESTION TO TDLRNEC QUESTION TO TDLR

The NEC CODE, 2008 SECT. 620.21 The NEC CODE, 2008 SECT. 620.21 PARAGRAPH #4-E P.959PARAGRAPH #4-E P.959

states that a sump pump or oil recovery states that a sump pump or oil recovery pump located in the pit shall be permitted to pump located in the pit shall be permitted to be cord connected, hard usage oil resistant be cord connected, hard usage oil resistant type of a length not to exceed 6FT. Will type of a length not to exceed 6FT. Will TDLR enforce the 6FT. rule in the low lying TDLR enforce the 6FT. rule in the low lying TEXAS Coastal Regions?TEXAS Coastal Regions?

Page 11: INDUSTRIAL SYSTEMS, INC.

ANSWERE FROM TDLRANSWERE FROM TDLR

(TDLR will enforce the 6FT. rule STATE (TDLR will enforce the 6FT. rule STATE WIDE.)WIDE.)

-LAWRENCE TAYLOR--8-19-2009-LAWRENCE TAYLOR--8-19-2009

Page 12: INDUSTRIAL SYSTEMS, INC.

QUESTION TO TDLRQUESTION TO TDLR

Can the sump pump control panel be Can the sump pump control panel be installed in the elevator machine room?installed in the elevator machine room?

Page 13: INDUSTRIAL SYSTEMS, INC.

ANSWERE FROM TDLRANSWERE FROM TDLR

(YES, the sump pump control panel may be (YES, the sump pump control panel may be installed in the elevator Machine room.)installed in the elevator Machine room.)

-LAWRENCE TAYLOR----8-19-2009 -LAWRENCE TAYLOR----8-19-2009

Page 14: INDUSTRIAL SYSTEMS, INC.

QUESTION TO TDLRQUESTION TO TDLR

MR. LAWRENCE TAYLOR, MR. LAWRENCE TAYLOR,

HELLO HOW ARE Y'ALL DOING IN HELLO HOW ARE Y'ALL DOING IN AUSTIN TODAY? I HAD ANOTHER AUSTIN TODAY? I HAD ANOTHER QUESTION FOR YOU SIR. QUESTION FOR YOU SIR.

CAN AN ELECTRIC VALVE OR ANY CAN AN ELECTRIC VALVE OR ANY VALVE BE INSTALLED IN THE VALVE BE INSTALLED IN THE HOISTWAY PIPING? HOISTWAY PIPING?

Page 15: INDUSTRIAL SYSTEMS, INC.

ANSWARE FROM TDLRANSWARE FROM TDLR

(As long as the valve will not shut off the (As long as the valve will not shut off the pump then yes it is allowed to be in the hoist pump then yes it is allowed to be in the hoist way.)way.)

-Lawrence Taylor-Lawrence Taylor

Page 16: INDUSTRIAL SYSTEMS, INC.

WHAT IS THE RECOMMENDED WHAT IS THE RECOMMENDED SUMP PUMP?SUMP PUMP?

THE STANCOR OIL-MINDER TEXAS VERSION THE STANCOR OIL-MINDER TEXAS VERSION SUBMERSIBLE PUMP AND CONTROL SYSTEM SUBMERSIBLE PUMP AND CONTROL SYSTEM MEETS AND EXCEEDS THE NEW RULES THAT MEETS AND EXCEEDS THE NEW RULES THAT HAVE BEEN ADAPTED BY (TDLR)HAVE BEEN ADAPTED BY (TDLR)

THE STANCOR SE-50-TV-RP WILL THE STANCOR SE-50-TV-RP WILL AUTOMATICALLY DISCHARGE WATER FROM AUTOMATICALLY DISCHARGE WATER FROM ELEVATOR SUMP PITS, TRANSFORMER ELEVATOR SUMP PITS, TRANSFORMER VAULTS, AND OTHER TYPES OF SUMPS WITH VAULTS, AND OTHER TYPES OF SUMPS WITH OUT DANGER OF EJECTING OIL OUT OF THE OUT DANGER OF EJECTING OIL OUT OF THE SUMP AND INTO A SEWER SYSTEM.SUMP AND INTO A SEWER SYSTEM.

Page 17: INDUSTRIAL SYSTEMS, INC.
Page 18: INDUSTRIAL SYSTEMS, INC.

REMINDERSREMINDERS

IF YOU THINK YOU FALL UNDER THE IF YOU THINK YOU FALL UNDER THE GRANDFATHER CLAUSE THEN YOU GRANDFATHER CLAUSE THEN YOU BETTER BE PREPARED.BETTER BE PREPARED.

THE ELEVATOR INSPECTORS WILL BE THE ELEVATOR INSPECTORS WILL BE LOOKING FOR CERTIFICATION OF THE LOOKING FOR CERTIFICATION OF THE FOLLOWING : PUMP CAPACITY, FOLLOWING : PUMP CAPACITY, COMPLIANCE WITH NEC IE:WATER AND COMPLIANCE WITH NEC IE:WATER AND OIL RESISTANT CORDS NO LONGER OIL RESISTANT CORDS NO LONGER THEN 6 FEET.THEN 6 FEET.

Page 19: INDUSTRIAL SYSTEMS, INC.

THANK YOU FOR YOUR TIME !THANK YOU FOR YOUR TIME ! ANY FURTHER QUESTIONS MAY BE ANY FURTHER QUESTIONS MAY BE

DIRECTED TO:DIRECTED TO: INDUSTRIAL SYSTEMS,INC.INDUSTRIAL SYSTEMS,INC.

RICHARD POWELL OR CHRIS LONGRICHARD POWELL OR CHRIS LONG

210-493-4200210-493-4200