THE ATTACHED FILES ARE OFFICIAL RECORDS OF THE DIVISION OF DOCUMENT CONTROL. THEY HAVE BEEN CHARGED TO YOU FOR A LIMITED TIME PERIOD AND MUST BE RETURNED TO THE RECORDS FACILITY BRANCH 016. PLEASE DO NOT SEND DOCUMENT CHARGED OUT THROUGH THE MAIL. REMOVAL OF ANY PAGE(S) FROM DOCUMENT FOR REPRODUCTION MUST BE REFERRED TO FILE PERSONNEL.
DEADLINE RETURN DATE
~---------
MINNEAPOLI
RECORDS FACILITY BRANCH
INSERVICE INSPECTION - EXAMINATION SUMMARY
OCTOBER 19, 1987 TO DECEMBER 10, 1987
REFUELING OUTAGE NUMBER 13
INSPECTION PERIOD 2
SECOND INTERVAL
NORTHERN STATES POWER COMPANY
MINNEAPOLIS. MINNESOTA
Report Date: Commercial Service Date: January 29, 1988 June 30, 1971
DtR ADOCK 0500023
NORTHERN STATES POWER COMPANY
MONTICELLO NUCLEAR GENERATING PLANT - UNIT I
INSERVICE INSPECTION - EXAMINATION SUMMARY
OCTOBER 19, 1987 TO DECEMBER 10, 1987
REFUELING OUTAGE NUMBER 13
INSPECTION PERIOD 2
SECOND INTERVAL
Report Date: January 29, 1988
Prepared by: L.C. Dahlman Sr. M&SP Specialist
Reviewed by: Q OK. R.A.Kellerhall M&SP Specialist
Approved by: __- ___6 J.L. Ricker Superintendent, Materials and Special Processes
Commercial Service Date: June 30, 1971
L6
LO 0 C0
E
INSERVICE INSPECTION - EXAMINATION SUMMARY MONTICELLO NUCLEAR GENERATING PLANT - UNIT 1
October 19, 1987 to December 10, 1987.
1.0 INTRODUCTION
This report is a summary of the examinations performed during the 13th inservice inspection at the Monticello Nuclear Generating Plant - Unit 1. This was the first inspection conducted for inspection period two of the plant's 2nd ten year interval. The examinations were performed during the plant's 13th refueling outage from October 19, 1987 to December 10, 1987. Monticello Unit 1 began commercial operation on June 30, 1971.
This report identifies the components examined, the examination methods used, the examination number; and, summarizes the examination results of each of the following areas:
1. Pressure retaining components and supports of the reactor coolant and associated systems classified as ASME Class 1 and ASME Class 2.
2. Reactor Vessel Visual Examinations 3. System Pressure Testing
2.0 SUMMARY OF RESULTS
The evaluation of all the results from the inservice examinations indicated that the integrity of these systems has been maintained.
3.0 ASME CLASS 1 AND 2 COMPONENTS
3.1 EXAMINATION PLAN
The examination plan focused on the pressureretaining components and their supports of the reactor coolant and associated auxiliary systems classified as ASME Class 1 and ASME Class 2.
The examination plan was based on the examination requirements of the ASME Boiler and Pressure Vessel Code Section XI, 1977 Edition through and including the Summer 197.8 Addenda, and complied with Monticello's Technical Specification, Section TS 4.15. The examination is in accordance with the program submitted to the United States Nuclear Regulatory Commission on March 27, 1981 titled, "ASME Code Section XI Inservice Inspection and Testing Program and Information Required for NRC Review of Requests for Relief From ASME Code Section XI Requirements".
10 C? 2
3.2 EXAMINATION METHODS
Ultrasonic examination methods and techniques were used to perform the volumetric examinations. The ultrasonic test systems consisted of an ultrasonic digital/analog tester and a two channel strip chart recorder. One channel of the recorder was calibrated to reflect ultrasonic screen height (amplitude) and the second channel was calibrated to indicate metal path (range) to the reflector. This approach to the examination gives a permanent record to the extent possible.
Liquid penetrant or magnetic particle examination methods were used to perform the surface examinations. The liquid penetrant examinations were performed using color contrast-solvent removable materials. Magnetic particle examinations were performed using either a yoke with dry powder or an AC L-10 coil with fluorescent prepared bath.
All visual examinations were aided, when necessary, with artificial lighting and verified for adequacy with an 18% neutral gray card with a 1/32 inch black line.
3.3 EXAMINATION PROCEDURES
The ultrasonic examination procedures for piping welds complied with the requirements of Appendix III of ASME Section XI that was issued in the Summer 1978 Addenda. All other procedures complied with the requirements of the 1977 Edition through and including the Summer 1978 Addenda of ASME Section XI. A listing of the procedures used for the examinations is shown in Table III of Appendix C.
3.4 EQUIPMENT AND MATERIALS
All equipment and expendable materials used in the examinations are listed either by serial number or type along with their respective calibration date or batch number in Table IV of Appendix C.
The ultrasonic calibration standards used in the examinations are listed in Table II of Appendix C. These standards are owned and maintained by NSP at the plant site.
3.5 PERSONNEL
Northern States Power Company contracted Lambert, MacGill, Thomas, Inc. to perform balance of plant examinations. General Electric for the Reactor Vessel Visual Examinations. Hartford Steam Boiler Inspection and Insurance Company, representing ANII, provided the Authorized Inspection. C
0-
3.5 (cont'd)
All personnel involved in the performance or evaluation of examinations are listed along with their title, organization and ASNT Level of Certification in Table I of Appendix C.
Certifications for examination personnel are maintained on file by Northern States Power Company.
3.6 EVALUATION
Any indications disclosed in the examinations were evaluated by the examiner at the time, in accordance with the rules of the procedure and ASME Section XI.
The ultrasonic examiner(s) was aided in their evaluation by a calibration performed on a standard reference before each day's examination, checked before and after each individual examination and at intervals not exceeding four (4) hours. In addition, the ultrasonic data was recorded on strip charts which were made a part of the inspection report, and permitted further evaluation.
3.7 EXAMINATION REPORTS AND DOCUMENTATION
All examination reports and documentation are maintained on file by Northern States Power Company. Table I of Appendices A, and B identifies the examination report number(s) for each item examined. Many of the items identify more than one examination report because of the different types of examinations performed on the item.
Table I of Appendix A, and B summarizes all the examinations performed to date and identifies the amount that will be examined in the future to complete the ten year examination requirements. Forretrieval purposes, the prefix of the inspection report number corresponds with the year the inspection was performed. The examination report numbers for this outage are prefixed with "87-".
Table II of -Appendix A, and B compares the baseline examination or previous results with the results obtained during this examination. Table III of Appendix A, and B identifies the isometric drawings that were used for the examinations. The personnel, ultrasonic calibration blocks, procedures, equipment and materials that were used for the inspection are identified in the tables of Appendix C. Appendix D contains the Form NIS-1 titled, "Owner's Data Report for Inservice Inspections". 0
CL
3.8 SUMMARY OF RESULTS
The followin
SYSTEM
g is a list of anomalies detected:
TYPE AND NUMBER ITEM EXAM OF ID METHOD INDICATIONS
MAIN STEAM B
MAIN STEAM C
CORE SPRAY A
FEEDWATER B
FEEDWATER D
HPCI WATER DISCHARGE
HPCI STEAM SIDE
RHR DISCHARGE B
RHR DISCHARGE A
RHR LOOP A
RCIC STEAM DISCHARGE
RCIC WATER
CRD SCRAM HDR A
CRD SCRAM HDR B
STANDBY LIQUID CONTROL
RHR HEAT EXCHANGER
MSBJ-57 MSBK-51 MSBK-53
MSCK-48 MSCK-43
TWH-84 SS-27
FW-98-1
FWDK-3 1
CIAK-52
MT VT VT
VT VT
VT VT
VT
VT
VT
TDAK-16 VT
SR-24
TWH-173
MO-2030
MO-2075
TW-25
CDAK-19A
CDBK-16A CDBK- 17
CPAK-14A
LINEARS LOOSE BOLT MARKERS STAMPED WRONG
THREAD ENGAGEMENT THREAD ENGAGEMENT
THREAD ENGAGEMENT DRAWING COMPLIANCE
HEAVY RUST ON BOLTING
THREAD ENGAGEMENT
LOAD SETTING
THREAD ENGAGEMENT DRAWING COMPLIANCE
DRAWING COMPLIANCE
DRAWING COMPLIANCE THREAD ENGAGEMENT
RUSTED BOLTING
RUSTED BOLTING
THREAD ENGAGEMENT
THREAD ENGAGEMENT
LOOSE BOLT DRAWING COMPLIANCE
NO DRAWING
VT
VT
VT
VT
VT
VT
VT VT
VT
SUPPORT C VT ARC STRIKE
SYSTEM ID METHOD INDICATIONS
3.8 (cont'd)
All anomalies were either corrected or an engineering evaluation was performed to accept "as is" conditions. The linear MT indications were removed by light hand grinding and blending the area smooth; the hangers that were out of adjustment were readjusted; the hangers with drawing compliances were turned over to drawing control to update the drawings to reflect the 'as found' conditions; the hangers with loose bolts were tightened; the hangers with inadequate thread engagement were either adjusted or the nuts were tack welded to ensure that the connection would not come apart; the missing hanger drawing was found; the rusted bolting on the valves were wire brushed.
4.0 VISUAL EXAMINATION OF THE REACTOR VESSEL
A visual examination was performed on portions of the reactor vessel components utilizing an underwater TV camera, fiberscope, and a video recording system. The examinations were performed in accordance with Northern States Power Company's Procedure No. NSP-VT-4.0, Revision 1.
The examination procedure delineated the scope of the program and contained a separate appendix for each area to be examined. Each of the appendices contained a checkoff list the examiners used during the examinations to identify areas examined and abnormal conditions, if found.
The examination program focused on the Core Spray Sparger System, Feedwater Sparger System, Jet Pump Beams, Top Guide of Core, Guide Rod Brackets, and Steam Dryer Support Brackets. Examination areas for these systems included the following:
Core Spray: Tee junction box at 90* and 270*; piping and welds; piping brackets and reclad area; sparger piping, nozzles, and brackets, and shroud penetrations.,
Feedwater: Inner radius of vessel nozzles at 450, 135*, 225', and 315*, sparger piping and welds, end brackets and bolting, reclad areas, end pin and keeper box, and the individual flow nozzles
o on each sparger.
Top Guide of Core: Beams, ring bolts and hold down latches.
C
02 CL
4.0 (cont'd)
Guide Rod Bracket: Brackets, attachment welds, and adjacent reclad area.
Jet Pumps: Beam bolt and Tack Welds, Lock Plate, 2 plug welds, 4 tack welds, hold down beam, and wedge & restrainer, adjusting screws and tack welds.
Steam Dryer: Support brackets in each quadrant.
A video recording system was used to permanently document the abnormal conditions found during the examination, and to record system calibrations.
All examination reports and documentation are included with the balance of plant records and are maintained on file by Northern States Power Company.
5.0 FEEDWATER LEAKAGE
In reference to the Nuclear Regulatory Commission (NRC) letter received August 28, 1981 from Thomas Ippolito on "Implementation of Unresolved Safety Issue A-10, BWR Nozzle Cracking" and NSP"s submittal of April 22, 1985 giving supplemental information related to the Inservice Inspection Examination Summary for Refueling Outage No. 10, the following information relating to the feedwater sparger inspection performed during the 1987 Refuel and Maintenance outage is provided for the use of the NRC staff.
The total number of start-up and shutdown cycles since the last refueling outage is 12.
An on line feedwater nozzle thermal sleeve leak detection system has been used to monitor the feedwater nozzle thermal sleeve bypass flow. This system indicates that there is no significant bypass flow and there is no increasing trend on any to the nozzles.
X
0
C? O o~
Inservice Inspection - Examination Summary MONTICELLO NUCLEAR GENERATING PLANT - UNIT I
INDEX
1.0 INTRODUCTION
2.0 SUMMARY OF RESULTS
3.0 ASME 3.1 3.2 3.3 3.4 3.5 3.6 3.7 3.8
CLASS 1 AND 2 COMPONENTS Examination Plan Examination Methods Examination Procedures Equipment and Materials Personnel Evaluation Examination Reports and Documentation Summary of Results
4.0 VISUAL EXAMINATION OF REACTOR VESSEL
APPENDIX A - ASME Class 1 Examinations
Inservice Inspection Table S1.1 Table S2.1 Table S3.1 Table S4.1 Table S1.5 Table S6.1 Table S7.1 Table S8.1 Table S9.1 Table S1O.1 Table S11.1 Table S12.1 Table S13.1 Table S14.1 Table S15.1
Table S-II Table III
Examination Summary Tables: Reactor Vessel Vessel and Heat Exchangers Nozzle welds Partial Penetration Welds Dissimilar Metal Welds Pressure Retaining Bolting > 2" Pressure Retaining Bolting < 2" Vessel Supports Piping Pressure Boundary Support Members Component Supports Pump Casings and Valve Bodies Reactor Vessel Interior Control Rod Drive Housing Welds Pressure Retaining Components Examination Comparison Summary Isometric Summary
APPENDIX B - ASME Class 2 Examinations
Inservice Inspection Table S1.2 Table S2.2 Table S3.2 Table S4.2 Table S5.2 Table S6.2 Table S7.2
Table S-II Table III
Examination Summary Tables: Vessel Welds Nozzle Welds Support members Pressure Retaining Bolting > 2" Piping Pressure Boundary Pump Casings and Valve Bodies Pressure Retaining Components Examination Comparison Summary Isometric Summary
co
a)
Cr
C? O-
0
APPENDIX C -
Table I Table II Table III Table IV
- Personnel Listing - Ultrasonic Calibration Blocks - Procedure Listing - Equipment and Materials
APPENDIX D - NIS-1 Form
Form NIS-1, Owners' Data Report for Inservice Inspections
<0
CO
03
O
Ld LO O
U
APPENDIX A
ASME CLASS I EXAMINATIONS
O
C)
In
0 C? O oL
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table S1.1 Page 1 of 2
Major Item: REACTOR VESSEL WELDS
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSP. REQ'D MOUNT ITEM INSPECTION ITEM GORY ITEM TO BE EXAMINED IPER LMOUNT EXAM I IDENTIFICATION REPORT NO.
SHELL WELDS
CIRCUMFERENTIAL
LONGITUDINAL
HEAD WELDS
CIRCUMFERENTIAL
CLOSURE HEAD
BOTTOM HEAD
PPM-0043, Rev. 0 (6/86) (M&SP 5.2)
B1.10
B1.11
B1.12
B1.20
B1.21
B-A
B-A
B-A
B-A
B-A
10'
7'
9'
ONE
TWO
THREE
ONE
TWO THREE
ONE TWO THREE
ONE TWO, THREE
VCBB-1 VCBB-4 VCBB-4 VCBB-4
N1A N4A N4B N4C
VLCB-2 @ N5B VLCB-2 @ B1O
HCCB-2 @ 0 to 123 HCCB-2 @ 120to240
HCAB-1 @ HMAB-8 HCAB-1 @ HMAB-4
85-596,114,586,601 85-491,466,042,506 87-293,315,298,304 87-291,313,301,306
85-454,468,040,507 85-597,116,588,600
86-039,049,045,076 87--186,161,184,1190
86-282,292,335,303 87-247,258,273,297
LCD110482RO1
10'
7'
9'
8' 9"
4' 2' 9"
8.5' 8'
8.5'
3' 3' 3'
8.5 8'
3' 3'
Form 170278
I,
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
I EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSP. REQ'D MOUNT ITEM INSPECTION ITEM GORY ITEM TO BE EXAMINED I PER MOUNT EXAM IDENTIFICATION REPORT NO.
MERIDONAL
SHELL TO FLANGE WELD
HEAD TO FLANGE WELD
REPAIR WELDS
ONE
TWO
THREE
ONE TWO THREE
ONE TWO THREE
26'B-A
B-A
B-A
26'
18.5'
19'
19'
HMCB-2 HMAB-1 HMAB-6 HMAB-7 HMAB-8 HMAB-9 HMAB-2 HMAB-3 HMAB-7 HMAB-6
@
90 0 240 270 300
131.22
B1.30
131.40
131.50
86-037,050,043,075 86-283,309,336,304 86-284,293,337,302 86-285,294,339,301 86-286,295,342,300 86-287,308,338,299 87-245,257,271,295 87-246,256,272,296 87-187,162,185,193 87-188,164,183,192
86-291,298
86-038,047,044,077
* * & I A J £PPM-0043, Rev. 0 (6/86) (M&SP 5.2)
LCD110482RO1
21'
19'
19' 19' 19'
19' 19' 19'
VCBC-5
HCCC-1 @ 0 to 120
Form 17027B
Table S1.1 Page 2 of 2
Major item: REACTOR VESSEL WELDS
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table S2.1 Paa - 1 of
Major Item: VES SEF -& HEAT EXCHANGERS
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSP. REO'D MOUNT ITEM INSPECTION ITEMI GORY ITEM TO BE EXAMINED PER LMOUNT EXAM IDENTIFICATION REPORT NO.
PRESSURIZER VESSEL
STEAM GENERATORS
HEAT EXCHANGERS
I I L .1 LPPM-0043, Rev. 0 (6/86) (M&SP 5.2) Form 170278
LCD110482RO2
B2.10 & B2.20
B2.30 & B2.40
B2.50 & B2.60
B-B
B-B
B-B
. I .
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table S3.1 Page 1
Major Item: NOZZLE WELDS
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSP.- REO'D MOUNT ITEM INSPECTION ITEM GORY ITEM TO BE EXAMINED PER LMOUNT EXAM IDENTIFICATION REPORT NO.
NOZZLE-TO-VESSEL WELDS & NOZZLE INSIDE RADIUS SECTION
HEAD VENT
HEAD SPARE
STANDBY LIQUID CONTROL.
,MAIN STEAM
FEEDWATER
CORE SPRAY
CRD RETURN
RECIR OUTLET
ONE
TWO
THREE
TWO
ONE
TWO THREE
ONE
TWO
THREE
ONE THREE
ONE
ONE THREE
1
1
1
2
2
1
1
1
HVAD-1
RHDD-1, IR
MSAD-I
FWAD-1
FWCD-1 Bore,IR FWBD-1 Bore,IR
FWCD-1 Bore,IR
CSBD-1
CRAD-1
RCAD-1
84-140,145,147 146,155 87-202,189,163, 182,191
86-582,581,587, 572,599,598
86-492,467,074, 496,500,501 86-547,571 87-309,312,294, 314,299,302 87-310,311,292, 316,300,303
84-187, 190, 158, 193
191,
84-188,189,192, 168,240 82-195, 255
- .5 £ I L IPPM-0043, Rev. 0 (6/86) (M&SP 5.2)
LCD121687WMHO6
B3. 10 B3.20
B-D
of 2
Form 17-0278
.5 4
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table S3 1 Page 2 of 2
Major item: NOZZLE WELDS
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSP. REQ'D MOUNT ITEM INSPECTION ITEM I GORY ITEM TO BE EXAMINED PER MOUNT EXAM IDENTIFICATION REPORT NO.
(CONTINUED)
RECIR INLET
JET PUMP INSTR
PRESSURIZER VESSEL
STEAM GENERATORS
HEAT EXCHANGERS
ONE
TWO
THREE
ONE THREE
3
3
4
1 1
3
1
1
RRAD-1 RRDD-1 RRJD-1 RRED-1 IR
JPAD-1
82-170, 148 82-161, 171 82-160, 172 87-386, 362, 364, 352
389,
84-194, 237, 238, 239, 241
Form 170278
LCD121687WMHO6
B-D
B-D
B-D
B-D
B3. 10 B3.20
B3.30 & B3.40
B3.50 & 83.60
B3.70 & B3.80
B3.90 & B3. 100
PPM-0043, Rev. 0 (6/86) (M&SP 5.2)
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table S4 1 Paae1 of 1
Major Item:PART IAL PENETRATTON WELDS
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSP. REQ'D MOUNT ITEM INSPECTION ITEM IGORY ITEM TO BE EXAMINED IPER MOUNT EXAM I IDENTIFICATION REPORT NO.
84. 10
B4.11
B4. 12
B4. 13
B4. 14
B4.20
PPM-0043, Rev.
B-E
B-E
B-E
B-E
B-E
B-E
REACTOR VESSEL
PARTIAL PENT. WELDS
VESSEL NOZZLES
CRO PENETRATIONS
INSTR PENETRATIONS
PRESSURIZER
0 (6/86) (M&SP 5.2)
THREE
ONE TWO THREE
THREE
1
10 10 10
1
* *INSPECTED BY PLANT PERSONNEL DURING EACH REACTOR VESSEL LEAKAGE TEST
Form 170278
LCD121587WMHO1
Is . S
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table S5.1 Page 1 of 4
Major item: DISSIMILAR METAL WELDS
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSR REQ'D AMOUNT ITEM INSPECTION ITEM GORY ITEM TO BE EXAMINED I PER MOUNTI EXAM I IDENTIFICATION REPORT NO.
REACTOR VESSEL
NOZZLE-TO-SAFE-END-WELDS
HEAD VENT
HEAD SPARE
STANDBY LIQUID CONTROL
CORE SPRAY
CRD RETURN
RECIRC OUTLET
RECIRC INLET
ONE
TWO THREE
ONE TWO
ONE
THREE
ONE
ONE
THREE
ONE
TWO HREE
2
1
1
1 2
1
2
10
1
HVAF-2 HSBF-2 RHDJ-2
CPAF-2
CSBF-2 CSAJR-2(BASELINE) CSBJR-2(BASELINE)
CRAFR-2(BASELINE)
RCAF-2 RCBF-2 (Aug)
RRAF-2 RRDF-2 RRJF-2 ------ AUGMENTED----RRBF-2 RRCF-2 RREF-2 RRFF-2 RRGF-2 RRHF-2 RRKF-2 RREFR-2
84-134, 135 84-137, 138(Aug) 87-206,122,388,387
84-033, 061(Aug)
84-162,84-166 86-442,518,516,449 86-420,517,515,417
86-423,366,306,397
82-177, 82-257
196
82-70, 130 82-85, 151 82-84, 129
82-293 82-260 82-296 82-261 82-268 82-254 82-279 87-346,363,349
- .* d A A .1
Form 170278
LCD121687WMHO8
CS. 10 B-F
PPM-0043, Rev. 0 (6/86) (M&SP 5.2)
I~ I
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table S5.1 Page 2 of 4
Major Item: DISSIMILAR METAL WELDS
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSP. REQ'D MOUNT ITEM INSPECTION ITEM GORY ITEM TO BE EXAMINED I PER MOUNT EXAM IDENTIFICATION REPORT NO.
(CONTINUED)
JET PUMP INSTR
INSTRUMENT LINES
PRESSURIZER
STEAM GENERATORS
HEAT EXCHANGERS
ONE
THREE
ONE
TWO THREE
1 2
4
1
JPBF-2 JPAFR-2(BASELINE)
JPBFR-2(BASELINE)
VIAF-2 VIBF-2(Aug) VICF-2(Aug) VIDF-2(Aug) VIBF-2
84-043, 050 84-1151BL,1294BL, 1333BL 84-1152BL,1293BL, 1332BL
84-070,075 84-071,074 84-161,164 84-163,165 87-307,322,305
& i. a a
PPM-0043, Rev. 0 (6/86) (M&SP 5.2) Form 17-0278
LCD121687WMHO8
B5. 10
5.20
B5.30
B5.40
B-F
B-F
B-F
B-F
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table S5.1 Page 3 of 4
Major Item: DISSIMTI AR MFTAI WFI DS
EXAM COMPONENTIOR SYSTEM SUB CATE- AND DESCRIPTION OF INSP. REQD MOUNT ITEM INSPECTION ITEM GORY ITEM TO BE EXAMINED PER MOUNT EXAM IDENTIFICATION REPORT NO.
SAFE END WELDS
CORE SPRAY
HPCI STEAM
RHR (REW10)
RHR (TW20)
ONE
THREE
ONE
TWO
ONE TWO
ONE
TWO THREE
2
2
1
1
1 2
CSAF-14 CSAF-18 CSP-90-7(Aug) CSP-270-7(Aug) CSP-270-9(Aug) CSBF-12(Aug) CSBF-16(Aug) CSAFR-8(BASELINE) CSAFR-9(BASELINE) CSBFR-8(BASELINE) CSBFR-9(BASEL INE)
PSAF-28(Aug) PSAF-2C(Aug) PSAF-2B PSAF-2C
RHAF-4(Aug)
RHBF-4 (Aug) RHBF-20 (Aug) RHBF-24 (Aug) RHBF-20 (Aug) RHBF-24 (Aug) RHBFR-6
_______________ J II I .1 I U
PPM-0043, Rev. 0 (6/86) (M&SP 5.2)
84-096,103 84-094,098 84-220,259 84-182,184 84-156,213 84-093,102 84-101,105 86-012,018,163 86-013,019,164 86-317,314,377,323 86-318,315,376,322
84-109,113 84-110,114 87-255,317,253 87-254,318,252
82-274
82-241,273 82-242,262 82-245,272 84-085,089 84-082 87-385,367(NO PT)
Form 170278
LCD121687WMHO8
B5.50 B-F
, 4 1 f
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table S5.1 Page 4 of 4
Major Item: DISSIMILAR METAL WELDS
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSR REQ'D MOUNT ITEM INSPECTION ITEM GORY ITEM TO BE EXAMINED PER MOUNT EXAM I IDENTIFICATION REPORT NO.
(CONTINUED)
RHR (TW30)
RWCU
CRD SCRAM HDR A
CRD SCRAM HDR B
PPM-0043, Rev. 0 (6/86) (M&SP 5.2)
ONE
TWO THREE
ONE
ONE TWO THREE
ONE TWO THREE
3
2
1
1
1
1
RHCF-4 (Aug) RHCF-20 (Aug) RHCF-23 (Aug) RHCF-20 (Aug) RHCF-23 (Aug)
CWAF-2
CDAF-12 CDAF-43
CDBF-37
82-265,269 82-246,264 82-247,263 84-079,087 84-080
82-27,28
86-183,633,632 87-392,400,393
86-257,260,363
LCD121687WMHO8
B5.50
Form 170278
I . I I
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table S6 .1 Page 1 of 4
Major Item: PRESSURE RETAINING BOLTIN.> 2"
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSP. REQ'D MOUNT ITEM INSPECTION ITEM GORY ITEM TO BE EXAMINED I PER MOUNT EXAM IDENTIFICATION REPORT NO.
CLOSURE HEAD NUTS
CLOSURE STUDS, IN PLACE
CLOSURE STUDS, WHEN REMOVED
B6. 10
WASHERS
B-G-1
B-G-1
B-G-1
B-G-1
B-G-1
22
21 21
ONE
TWO THREE
ONE
TWO THREE
ONE
TWO THREE
ONE
TWO THREE
22
64
22
22
22 Prs
64 Prs
NUTS 1&2, 4&6, 13&15, 18&19, 47-52, 55&56, 58&59, 61-64 NUTS 1-36, 37-64
STUDS 1&2, 4&6, 13&15, 18&19, 47-52, 55&56, 58&59, 61-64
LIGAMENTS 1&2,4&6, 13&15, 18&19, 47-52, 55&56, 58&59, 61-64
WASHERS 1&2 4&6, 13&15, 18&19, 47-52, 55&56, 58&59, 61-64 WASHERS 1-36,37-64
I 1 I I I II
PPM-0043, Rev. 0 (6/86) (M&SP 5.2)
86-489,481
87-244,242,243,239
86-373,307,374
86-290, 297
86-480
87-241, 240
Form 470278
LCD121687WMHO7
22
21 21
22
21 21
22 Prs
21 Pr! 21 Pr!
B6.20
B6.30
B6.40
B6.50
LIGAMENTS BETWEEN STUD HOLES
CLOSURE WASHERS AND BUSHINGS
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table S6.1 Paa 2 of 4
Major Item: PRESSUR REIAINING BULING 72"
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSP. REQ'D MOUNT ITEM INSPECTION ITEM GORY ITEM TO BE EXAMINED PER MOUNT EXAM IDENTIFICATION REPORT NO.
(CONTINUED)
BUSHINGS
PRESSURIZER
STEAM GENERATORS
HEAT EXCHANGERS
PIPING
PUMPS
BOLTS & STUDS, IN PLACE
RECIRC PUMP A FLANGE BOLTS
RECIRC PUMP B FLANGE BOLTS
PPM-0043, Rev. 0 (6/86) (M&SP 5.2)
B6.50
B6.60
B6.90
B6. 120
B6. 180
22
21 21
B-G-1
B-G-1
B-G-1
B-G-1
B-G-1
22ONE
TWO THREE
O NE TWO THREE
ONE TWO THREE
BUSHINGS 1&2, 4&6, 13&15, 18&19, 47-52, 55&56, 58&59, 61-64
Bolts, 1 THRU 5 Bolts, 6 THRU 10
Bolts, 1 THRU 5
86-296
82-193 (VT only) 87-141, 123
82-174, 194
Form 170278
LCD121687WMHO7
5 5 6
5 5 6
5 5
5
I ,
, q I I
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table S6.1 Page 3 ofI4
Major Item: PRESSURE RETAINING BOLTING72"
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSP. REO'D MOUNT ITEM INSPECTION ITEM I GORY ITEM TO BE EXAMINED I PER MOUNT1 EXAM IDENTIFICATION REPORT NO.
BOLTS & STUDS, WHEN REMOVED
RECIRC PUMP A & B FLANGE BOLTS
BOLTING
RECIRC PUMP A FLANGE BOLTS
RECIRC PUMP B FLANGE BOLTS
VALVES
BOLTS & STUDS, IN PLACE
RECIRC A
RECIRC A
RECIRC B
RECIRC B
B6. 190
B6. 200
B6. 210
J I I A I A
B-G-1
B-G-1
B-G-1
82-173
82-192 (VT only)
82-180
82-182
82-179
82-181
Form 17-0278
LCD121687WMHO7
ONE TWO THREE
ONE TWO THREE
ONE TWO THREE
ONE TWO THREE
ONE TWO THREE
ONE TWO THREE
Bolts, 1 THRU 5
Bolts, 1 THRU 5
M02-53A
M02-43A
M02-53B
M02-43B
PPM-0043, Rev. 0 (6/86) (M&SP 5.2)
I . I
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table S6.1 Page 4 of 4
Major Item: PRESSURE RETAINING BOLTING7'?"
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSP. REO'D MOUNT ITEM INSPECTION ITEM I GORY ITEM TO BE EXAMINED PER MOUNT EXAM [ IDENTIFICATION REPORT NO.
BOLTS, & STUDS, WHEN REMOVED
RECIRC A & B
BOLTING
RECIRC A
IRECIRC A
RECIRC B
RECIRC B
PPM-0043, Rev. 0 (6/86) (M&SP 5.2)
LCD121687WMHO7
B6. 220
B6. 230
B-G-1
B-G-1
ONE TWO THREE
ONE TWO THREE
ONE TWO THREE
ONE TWO THREE
8
8
8
8
8 8 8
8 8 8
8 8 8
8 8 8
M02-53A
M02-43A
M02-53B
M02-43B
82-180
82-182
82-179
82-181
Form 17-0278
. 1 1,
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table S7.1 Page 1 of 5
Major Item: PRESSURE RETAINING BOLTING (2"
EXAM COMPONENT OR SYSTEM I I IP O SUB CATE- AND DESCRIPTION OF INSP. LREQ'D MOUNT ITEM INSPECTION ITEM GORY ITEM TO BE EXAMINED I PER AMOUNT EXAM IDENTIFICATION REPORT NO.
REACTOR VESSEL
BOLTS, STUDS, AND NUTS
HEAD VENT HEAD SPRAY HEAD SPARE
CONTROL ROD HOUSINGS
PRESSURIZER
STEAM GENERATORS
HEAT EXCHANGERS
PIPING
BOLTS, STUDS, AND NUTS
MAIN STEAM A
MAIN STEAM B
MAIN STEAM C
B7. 10
B7.20
B7.30
B7.40
B7.50
8 8 8
41
40 40
B-G-2
B-G-2
B-G-2
B-G-2
B-G-2
41
ONE TWO THREE
ONE
TWO THREE
ONE T-HREE
TWO
ONE 1
HOUSINGS HOUSINGS HOUSINGS HOUSINGS HOUSINGS
ROW ROW ROW ROW ROW
FLG @ MSAJ-18
FLG @ MSCJ-19
& ii. I. J L J &
PPM-0043, Rev. 0 (6/86) (M&SP 5.2)
LCD110482RO7
1 3
1
1
1
10 14 18 2 6
86-331 86-328 86-327 86-329 86-330
86-214
86-210
Form 170278
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table S7.1 Page 2 of 5
Major Item: PRESSURE RETAINING BOLTING4 2"
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSP. REQ'D MOUNT ITEM INSPECTION ITEM GORY ITEM TO BE EXAMINED PER MOUNT EXAM IDENTIFICATION REPORT NO.
(CONT'D)
MAIN STEAM D
RHR TW36
RECIRC A
RECIRC B
HEAD VENT LINE
PUMPS
BOLTS, STUDS, AND NUTS
RECIRC PUMP A GLAND BOLTS
RECIRC PUMP B GLAND BOLTS
B7.50
B7.60
1 1
1
B-G-2
FLG @ MSDJ-19 FLG @ MSDJ-23
Bolts @ RCAJ-20
Bolts 1-3
Bolts 1-3
_________ .1 A I A I
PPM-0043, Rev. 0 (6/86) (M&SP 5.2)
LCD110482RO7
ONE TWO THREE
TWO
ONE
THREE
ONE
ONE TWO THREE
ONE TWO THREE
3
3
B-G-2
86-215 87-160
82-357
86-508
86-584
Form 170278
. I
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table ST.1 Page J of 5
Major Item: PRESSURE RETAINING BOLTING 2"
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSP REQ'D MOUNT ITEM INSPECTION ITEM GORY ITEM TO BE EXAMINED I PER MOUNT EXAM IDENTIFICATION REPORT NO.
VALVES
BOLTS, STUDS, AND NUTS
MAIN STEAM A
MAIN STEAM B
MAIN STEAM C
MAIN STEAM D
FEEDWATER A
FEEDWATER B
CORE SPRAY A
CORE SPRAY B
ONE TWO THREE
ONE TWO
THREE
ONE TWO THREE
ONE TWO THREE
ONE TWO THREE
ONE TWO THREE
ONE
TWO THREE
INE TWO THREE
2
2
2
1
1 1
2
114 I 2A 2 - -
PPM-0043, Rev. 0 (6/86) (M&SP 5.2)
RV2-71A #3 RV2-71E #3
A02-80B A02-86B
A02-80C A02-86C
FW-97-2
FW-97-1 FW-98-1
POS-1758 A014-13B
MO-1753
LCD110482RO7
B7.70 B-G-2
86-544 86-537
87-158 87-042
86-479 86-424
86-126
287R86-127 87-287
84-108 84-107
84-172
Form 170278
I I I A
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table S7 .1 Page 4 of 5
Major Item: PRESSURE RETAINING BOLTINGC2"
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSP. REQ'D MOUNT ITEM INSPECTION ITEM GORY ITEM TO BE EXAMINED PER LMOUNT EXAM IDENTIFICATION REPORT NO.
B7.70 B-G-2
1 1
1 1 1
1 2
(CONT'D)
HPCI STEAM
RWCU
RHR REW1O
RHR TW20
RHR TW30
RHR TW36
RHR TW40
RCIC STEAM
1 1
1
1 2
MO-2035 MO-2034
MO-2398
MO-2029 MO-2030 POS-2028
POS-2019
MO-2014 POS-2018
MO-2026
MO-4085B
MO-2075
84-128 87-157
84-183
84-216 87-159, 87-285
159R
ONE TWO
ONE TWO THREE
ONE TWO
THREE
ONE TWO THREE
ONE TWO THREE
ONE TWO THREE
ONE TWO THREE
TWO THREE
£ A .1 & A I. I
PPM-0043, Rev. 0 (6/86) (M&SP 5.2)
LCD110482RO7
1 2
1 1 1
1 2
1 1 1
1 1
86-659
84-169 87-286
84-173
87-121
87-156, 156R
Form 170278
. A I I
, A I
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table S7.1 Page 5 of 5
Major Item: PRESSURE RETAINING RO TING< 2"
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSP. REO'D AMOUNT ITEM INSPECTION ITEM I GORY ITEM TO BE EXAMINED PER AMOUNT EXAM IDENTIFICATION REPORT NO.
B7.70 B-G-2
2
2
(CONT'D)
RECIRC A
RECIRC B
RECIRC MANIFOLD
HEAD VENT LINE
BOTTOM HEAD DRAIN
STANDBY LIQUID CONTROL
MAIN STEAM DRAIN
CRD SCRAM HEADER DRAIN LINE
RECIRC A DRAIN
RECIRC B DRAIN
.5 .1 .1 L .1 & .5
PPM-0043, Rev. 0 (6/86) (M&SP 5.2)
LCD110482RO7
THREE
TWO
ONE
TWO THREE
THREE
ONE TWO THREE
ONE TWO
ONE
ONE
TWO
M02-43B MO2-53B
MO2-65A M02-66A (REMOVED 1984)
XP-8 XP-7
MO-2373
CV-3-33-A
XR-6-1 XR-7-1
XR-6-2 XR-7-2
87-323 87-324
82-178 82-185
84-215 87-133
86-465
86-673
82-87 82-88
87-119 87-120
Form 170278
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table S8.1 Page 1 of
Major item: VESSEL SUPPORTS
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSP. REQ'D AMOUNT ITEM INSPECTION ITEM I GORY ITEM TO BE EXAMINED I PER IAMOUNT EXAM I IDENTIFICATION REPORT NO.
REACTOR VESSEL
INTEGRALLY WELDED ATTACHMENTS
SUPPORT SKIRT
STABILIZER LUGS
PRESSURIZER
STEAM GENERATORS
HEAT EXCHANGERS
ONE TWO THREE
17 18 18
17% 81" 120" - 180" 84-257, 257R
L L. £ L .1 I .5
PPM-0043, Rev. 0 (6/86) (M&SP 5.2) Form t0278
LCD110482RO8
7* I
B8. 10
B8.20
B8.30
B8.40
B-H
B-H
B-H
B-H
. I
I. I
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table S9.1 Pa e 1 of 18
Major Item: PI ING PRESSURE BOUNDARY
EXAM COMPONENT OR SYSTEM [ SUB CATE- AND DESCRIPTION OF I INSP. LREQD MOUNT ITEM INSPECTION ITEM GORY ITEM TO BE EXAMINED PER MOUNT EXAM IDENTIFICATION REPORT NO.
NOMINAL PIPE SIZE, 4 IN. AND GREATER
CIRCUMFERENTIAL AND *LONGITUDINAL WELDS
MAIN STEAM A PS1-18"
PS1-6"
MAIN STEAM B PS2-18"
PS2-6"
MAIN STEAM C PS3-18"
PPM-0043, Rev. 0 (6/86) (M&SP 5.2)
ONE
TWO THREE
ONE,
TWO THREE
ONE TWO THREE
ONE
TWO THREE
ONE
TWO
THREE
4
2
2
1
3
2
MSAJ-6 MSAJ-4 MSAJ-5 MSAJ-18
MSAJ-16, 20 (BASELINE)
MSBJ-15, 21 (BASELINE) MSBJ-19
MSCJ-9 MSCJ-19 MSCJ-10 MSCJ-29 MSCJ-8
86-138,162,179 86-136,160,181 86-137,161,180 86-055,064,109
82-311, 312
82-313, 314
87-103,105,104
86-052,058,132 86-056,063,112 86-051,057,133 87-090,098,091 87-378,384,379
LCD121787WMHO1
B9.10
B9.11 & B9.12
B-J
B-J
Form 17-0278
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table Sq.1 Page 2 of 18
Major Item: PIPING PRFsiilF BOUNDARY
EXAM COMPONENTIOR SYSTEM SUB CATE- AND DESCRIPTION OF INSP. REQ'D MOUNT ITEM INSPECTION ITEM GORY ITEM TO BE EXAMINED PER MOUNT EXAM IDENTIFICATION REPORT NO.
B9.11, & B9. 12
R-J
1 2
2
(CONTINUED)
PS3-6"
MAIN STEAM D PS4-18"
PS4-6"
FEEDWATER A
FEEDWATER B
ONE
TWO THREE
ONE
TWO THREE
ONE
TWO THREE
ONE
TWO THREE
ONE TWO
THREE
ONE TWO THREE
2
MSCJ-16, 21 (BASELINE)
MSDJ-36 MSDJ-38
MSDJ-17, 21 (BASELINE) MSDJ-19
FWAJ-8 FWAJ-9
FWAJ-18 FWP-A-5
1 .11 I A I A I
PPM-0043, Rev. 0 (6/86) (M&SP 5.2)
82-315,318
86-484,502,474 86-073,073R,095 475,475R
82-317,316
8E-219,391,216
86-139,117,135 86-140,118,134
87-208,207,370 87-277,308,278
Form 17-0278
LCD121787WMHO1
2
3
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table S9.1 Page 3 of 1s
Major Item: PIPING PRESSURE BOUNDARY
EXAM COMPONENTIOR SYSTEM SUB CATE- AND DESCRIPTION OF INSP. REQ'D MOUNT ITEM INSPECTION ITEM GORY ITEM TO BE EXAMINED PER MOUNT EXAM IDENTIFICATION REPORT NO.
B9.11 & B9. 12
B-J
1
2
2
(CONTINUED)
FEEDWATER C
FEEDWATER D
CORE SPRAY A
CORE SPRAY B
FWCJ-12
FWDJ-11 FWDJ-12
FWDJ-19 FWDJ-20
CSAJ-19 CSAJ-16(Aug) CSAJ-17(Aug) CSAJR-3(BASELINE) CSAJR-4(BASELINE) CSAJR-5(BASELINE) CSAJR-6(BASELINE) CSAJR-7(BASELINE) CSAJR-10(BASELINE) CSAJ-19 CSAJR-10
J I A I £ I
PPM-0043, Rev. 0 (6/86) (M&SP 5.2)
86-090,246,105
86-111,154,103 86-089,155,104
86-091,245,106 86-092,247,107
84,179,180 84-095,104 84-079,106 86-438,452,510,445 86-448,451,509,447 86-388,380,412,385 86-387,382,413,384 86-439,427,511,446 86-386,381,411,383 87-343,390,341 87-342,391,340
LCDI21787WMHO1
ONE TWO THREE
ONE
TWO THREE
ONE
TWO THREE
ONE
TWO
THREE
3
6
2
Form 170278
i I . I
.4 , 9
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table S9.1 Page 4 of 18
Major item: PIPING PRESSURE BOUNDARY
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSP. REQ'D MOUNT ITEM INSPECTION ITEM GORY ITEM TO BE EXAMINED I PER AMOUNT EXAM t IDENTIFICATION REPORT NO.
B9.11 & B9. 12
B-J
4
6
(CONTINUED)
CORE SPRAY B
HPCI-STEAM
RWCU LINE
RHR REW10
RHR TW20-16"
ONE
TWO THREE
ONE TWO THREE
ONE TWO
THREE
ONE
TWO THREE
ONE 6
CSBJ-21 CSBJ-22 CSBJ-13(AuO) CSBJ-14(Aug) CSBJR-3(BASELINE) CSBJR-4(BASELINE) CSBJR-5(BASELINE) CSBJR-6(BASELINE) CSBJR-7(BASELINE) CSBJR-10(BASELINE)
CWAJ-2A CWAJR-11 CWAJR-13A CWAJR-5
RHAJ-1,2,3 RHAJ-25 RHAJ-26 RHAJ-27
RHBJ-28,29 RHBJ-1 (Aug) RHBJ-3 (Aug) RHBJ-21(Aug) DUD1 O /An \
84-170,175 84-1.71,174 84-092,099 84-091,100 86-421,425,512,418 86-437,453,513,444 86-422,426,514,419 86-320,312,379,325 86-321,313,378,324 86-319,316,375,326
82-320 87-200,205,195 87-201,204,194 87-198,203,197
82-252,253,275 84-195,243 84-178,245 84-242,244
82-31,53,32,52 82-277 82-276 84-084,090 OA AO2
&~~~~~~~O A00 ___________
PPM-0043, Rev. 0 (6/86) (M&SP 5.2)
LCD121787WMHO1
1 3
6
Form 17o278
I I
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table S9. 1 Page 5 of 18
Major Item: PIPING PRFSSIRF ROtINDARY
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSP. LREO'D AMOUNT ITEM INSPECTION ITEM GORY | ITEM TO BE EXAMINED PER M OUN T EXAM IDENTIFICATION REPORT NO.
(CONTINUED)
RHR TW20-16"
RHR TW20-18"
RHR TW 30-16"
RHR TW30-18"
RHR TW36
TWO
THREE
ONE
TWO
THREE
ONE
TWO THREE
ONE
TWO THREE
ONE TWO
THREE
2
1
1
2
2 1
1
3
3
2
2
2
4
2
1 3
RHBJR-13 RHBJR-15
RHBJ-21 RHBJ-22 RHBJR-2 RHBJR-3
(Aug) (Aug)
RHCJ-7, 8 RHCJ-21(Aug) RHCJ-22(Aug)
RHCJ-1(Aug) RHCJ-3(Aug)
RHDJ-2(Aug) RHDJ-11 RHDJ-12 RHDJ-17
87-380,368(NO MT) 87-381,369(NO MT)
82-243 82-244 87-303,365(NO PT) 87-382,366(NO PT)
82-33,55,34,54 82-248/84-086,088 82-249/84-083
82-250 82-251
84-136,139 87-344,336,338 87-345,337,339 87-360,361,356
- _______________ a a a i
Form 170278
LCD121787WMHO1
B911 139. 12
B-J
PPM-0043, Rev. 0 (6/86) (M&SP 5.2)
I . I t
I. P
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table S9.1 Page 6 of 18
Major Item: PIPING PRESSURE BOUNDARY
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSP REQ'D AMOUNT ITEM INSPECTION ITEM GORY ITEM TO BE EXAMINED PER MOUNT EXAM I IDENTIFICATION REPORT NO.
B9.11 & B9. 12
B-J (CONTINUED)
RECIRC A
RECIRC B
ONE
TWO
THREE
ONE
17
2
16
Form 17-0278
LCD121787WMHO1
RCAJ-13 ---------- AUGMENTEDRCAJ-3 RCAJ-4 RCAJ-5 RCAJ-6 RCAJ-9 RCAJ-11 RCAJ-15 RCAJ-17 RCAJ-20 RCAJ-21 RCAJ-23 RCAJ-24 RCAJ-28 RCAJ-30 RCAJ-32 RCAJ-35 RCAJR-4 RCAJR-5
RCBJ-11,13 ----------- AUGMENTEE RCBJ-3 RCBJ-4 RCBJ-5 RCBJ-6 RCBJ-9 RCBJ-15 RCBJ-18 RCBJ-19 RCBJ-21
82-071,074 ----------
82-225 82-120 82-099 82-121 82-226 82-227 82-080 82-228 82-357 82-081 82-147 82-229 82-230 82-082 82-083 82-256 87-124,137,138,125 87-109,132,106
82-069,095,065,094 -----------------82-258 82-231 82-096 82-232 82-231 82-233 82-234 82-098 82-146
PPM-0043, Rev. 0 (6/86) (M&SP 5.2)
I .
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table S9.1 Page 7 of 18
Major Item: PIPING PRFSSiRF RO11NDARY
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSP. REQ'D AMOUNT ITEM INSPECTION ITEM GORY ITEM TO BE EXAMINED PER MOUNT EXAM I IDENTIFICATION REPORT NO.
(CONTINUED)
RECIRC B
,RECIRC BYPASS A
RECIRC BYPASS B
PPM-0043, Rev. 0 (6/86) (M&SP 5.2)
6
6
RCBJ-22 RCBJ-26 RCBJ-28 RCBJ-31 RCBJ-34
RBAJ-M12,M13 ------------- AUGMENTE RBAJ-2 RBAJ-M3 RBAJ-M15 RBAJ-M16 (REMOVED 1984)
RBBJ-M7, M8 ----------- AUGMENTED RBBJ-2 RBBJ-M3 RBBJ-M18 RBBJ-19 (REMOVED 1984)
82-235 82-236 82-097 82-237 82-240
82-078,302,079,301 )--------------82-288 82-289 82-287 82-286
82-076,213,077,186 ----------------82-282 82-283 82-285 82-284
Form 170278
LCD121787WMHO1
B9.11 & B9. 12
B3-J
TWO THREE
ONE
TWO THREE
ONE
TWO THREE
.1 .1 £ .1 5. I
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table S9. 1 Page 8 of 18
Major item: PIPING PRESSURE ROUNDARY
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSP. REQ'D MOUNT ITEM INSPECTION ITEM GORY ITEM TO BE EXAMINED I PER MOUNT EXAM I IDENTIFICATION REPORT NO.
B9.11 & B9. 12
21
B-i (CONTINUED)
RECIRC MANIFOLD
RECIRC RISERS RISER F
I I L J & .1 &
PPM-0043, Rev. 0 (6/86) (M&SP 5.2)
ONE
TWO THREE
ONE
TWO THREE
Form 17-0278
LCD121787WMHOI
4
RMAJ-2,9
---------- AUGMENTEDRMAJ-3 RMAJ-5 RMAJ-7 RMAJ-8 RMAJ-10 RMAJ-14 RMAJ-15 RMAJ-16 RMBJ-2 RMBJ-3 RMBJ-5 RMBJ-7 RMBJ-8 RMBJ-9 RMBJ-10 RMBJ-12 RMBJ-14 RMBJ-15 RMBJ-16
-------- AUGMENTED--RRFJ-3 RRFJ-4 RRFJ-5 RRFJ-7
82-30,72,72A,72B 67,73 ----------------82-214 82-218 82-217 82-270 82-113 82-122 82-216 82-215 82-131 82-219 82-220 82-132 82-271 82-221 82-133 82-222 82-358 82-216 82-224
82-238 82-209 82-119 82-190
2
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECrION-EXAMINATION SUMMARY
Table S9.1 Page of 18
Major Item: PIPNG PRESSURE BOUNDARY
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSP. REQ'D MOUNT ITEM INSPECTION ITEM GORY ITEM TO BE EXAMINED PER MOUNT EXAM IDENTIFICATION REPORT NO.
B9.11 & B9. 12
B-J (CONTINUED)
RISER G
RISER H
RISER J
RISER K
ONE
TWO THREE
ONE
TWO THREE
ONE
TWO THREE
ONE
TWO THREE
4
4
4
4
-------- AUGMENTED-RRGJ-3 RRGJ-4 RRGJ-5 RRGJ-7
RRHJ-7 ----------- AUGMENTED RRHJ-3 RRHJ-4 RRHJ-6
---------- AUGMENTEDRRJJ-3 RRJJ-4 RRJJ-5 RRJJ-7
--------- AUGMENTED-RRKJ-3 RRKJ-4 RRKJ-5 RRKJ-7
82-267 82-207 82-208 82-280
82-187,062,062R
82-333 82-205 82-206
82-266 82-118 82-204 82-188
-------------82-278 82-203 82-117 82-189
5 ___________ I- £ .1 £
PPM-0043, Rev. 0 (6/86) (M&SP 5.2)
LCD121787WMHO1
2
1
2
Form 170278
*1
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table S9.1 Page 10 of 18
Major item: PIPING PRESSURE BOUNDARY
EXAM COMPONENT OR SYSTEM [ SUB CATE- AND DESCRIPTION OF INSP. REO'D MOUNT ITEM INSPECTION ITEM GORY ITEM TO BE EXAMINED PER MOUNT EXAM IDENTIFICATION REPORT NO.
B9.11 & B9. 12
PPM-0043, Rev. 0 (6/86) (M&SP 5.2)
B-J (CONTINUED)
RISER A
RISER B
RISER C
RISER D
4
4
ONE
TWO THREE
ONE
TWO THREE
ONE
TWO THREE
ONE
TWO THREE
4
-------- AUGMENTEDRRAJ-3 RRAJ-4 RRAJ-5 RRAJ-7
-------- AUGMENTED--RRBJ-3 RRBJ-4 RRBJ-5 RRBJ-7
-------- AUGMENTED--RRCJ-3 RRCJ-4 RRCJ-5 RRCJ-7
-------- AUGMENTED--RRDJ-3 RRDJ-4 RRDJ-5 RRDJ-7
LCD121787WMHO1
4
2
82-295 82-114 82-197 82-191
-----------82-239 82-202 82-115 82-212
82-259 82-116 82-201 82-297
82-198 82-199 82-200 82-150
Form 17-0278
, I 5
t I
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPEcTION-EXAMINATION SUMMARY
Table S9.1 Page I of 18
Major Item: PIPING PRESSURE BOUNDARY
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSP. REQ'D MOUNT ITEM INSPECTION ITEM GORY ITEM TO BE EXAMINED PER b MOUNT EXAM IDENTIFICATION REPORT NO.
B-J89.11 & 89. 12
(CONTINUED)
RISER E
HEAD VENT
JET PUMP INSTR
JET PUMP INSTR.(CANISTER)
INSTRUMENT LINES FROM N11A & N11B
CRD SCRAM HEADER 12"
A LOOP
4ONE
TWO THREE
ONE
ONE TWO THREE
ONE TWO THREE
ONE
TWO THREE
---------- AUGMENTEDRREJ-3 RREJ-4 RREJ-5 RREJ-7
HVAJ-3
JPBJ-3(Aug)
Weld Weld Weld
#1 #2 #3
(Aug) (Aug) (Aug)
VIAJ-19
CDAJ-16
CDAJ-50 BASELINE EXAMS CDAJ-17,28,29 45,33,46,49 50,51,52,53
82-294 82-211 82-210 82-149
84-134,135
84-042,051
84-041,052 84-040,053 84-039
84-200,214
86-340,263,341, 494,493 86-612,651,650
82-323,012,016 010,015,324,325 326,008,007,013,337
LCD121787WMHO1
1
1
3
1
2
11
1
1
PPM-0043, Rev. 0 (6/86) (M&SP 5.2) Form 170278
1. 1 .
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table 59.1 Page 1z of 18
Major Item: PIPING PRESSURE BOUNDARY
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSP. REQ'D MOUNT ITEM INSPECTION ITEM I GORY ITEM TO BE EXAMINED PER MOUNT EXAM I IDENTIFICATION REPORT NO.
B9.11 & B9. 12
PPM-0043, Rev. 0 (6/86) (M&SP 5.2)
B-J
1
2
1
(CONTINUED)
B LOOP
CRD SCRAM HDR 6"
A LOOP
B LOOP
CRD SCRAM HDR 4"
A LOOP
1
8
2
ONE
TWO
THREE
ONE
TWO THREE
ONE
TWO THREE
ONE
TWO ITLJpr~
3
2
11
CDBJ-23
BASELINE EXAMS CDJB-11,12,22 23,39,40,43,44
CDBJ-40 CDBJ-43
BASELINE EXAMS CDAJ-24,18,27
BASELINE EXAMS CDBJ-21,20,15
CDAJ-11 CDAJ-14
BASELINE EXAMS CDAJ-1,8,10,11, 12,13,15,16,36, 42,43
86-360,490,359
82-014,332,011,018 009,017,331,330, 336 , 339 87-041,038(NO PT) 87-036,040,037
82-327,328,006
82-005,334,335
86-253,256,251 86-252,255,249
82-353,349,350, 351,001,556,355, 354,020,352,348, 003
LCD121787WMHOI
13
Form 170278
I . . I
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table 59.1 Page __ of 18
Major Item: PIPING PRESSURE BOUNDARY
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF . INSP. REQ'D MOUNT ITEM INSPECTION ITEM I GORY ITEM TO BE EXAMINED PER MOUNT EXAM I IDENTIFICATION REPORT NO.
(CONTINUED)
B LOOP
.SCRAM DISCHARGE VOLUME TANK
A LOOP
B LOOP
ONE
TWO THREE
ONE
TWO THREE
ONE
TWO THREE
1
1
1
1
1
1
9
1
2
2 1
CDBJ-7
BASELINE EXAMS CDBJ-1,6,7,8,9, 10,28,34,37
CDBJ-14
BASELINE EXAMS CDAJ-54,55
BASELINE EXAMS CDBJ-45,46 CDBJ-46
86-258,259,364
82-347,343,344, 002,341,340,342, 346,345,004 87-034,039,035
82-024,023
82-022,021 87-408,410(NO PT)
& d -
PPM-0043, Rev. 0 (6/86) (M&SP 5.2) Form 17-0278
LCD121787WMHO1
B9.11 & B9.12
13-J
I . I I
4
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECrION-EXAMINATION SUMMARY
Table S9.1 Page 14 of 18
Major Item: PIP NG PRESSURE BOUNDARY
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSP. REQ'D MOUNT ITEM INSPECTION ITEM GORY ITEM TO BE EXAMINED PER MOUNT EXAM IDENTIFICATION REPORT NO.
B9.20
B9.21 & B9.22
B9.30
B9.31
PPM-0043, Rev. 0 (6/86) (M&SP 5.2)
B-J
B-J
B-J
B-J
2
2
2
NOMINAL PIPE SIZE LESS THAN 4 IN.
CIRCUMFERENTIAL AND *LONGITUDINAL WELDS
RCIC STEAM
.STANDBY LIQUID CONTROL
MAIN STEAM CONDENSATE LEAKOFF
BRANCH CONNECTION WELDS
NOMINAL PIPE SIZE GREATER THAN 2 IN.
MAIN STEAM A
ONE
TWO THREE
ONE
TWO THREE
ONE
TWO THREE
ONE
TWO THREE
RSAJ-4 RSAJ-5
CPAJ-3A (Aug) CPAJ-4 (Aug) CPAJ-6 (Aug) CPAJR-16
CLAJ-4 CLAJ-6
MSAJ-15,19 (BASELINE) MSAJ-17
84-197 84-196
84-035,062 84-034,063 84-036,064 87-108,107
86-486,476 86-485,475
82-303,304
86-053,622,211,623
Form 17-0278
LCD121787WMHO1
2
3
1
2
4 I.
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table S9.1 Page 15 of IS
Major Item: PIPING PRESSURE BOUNDARY
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSP. LREQ'D MOUNT ITEM INSPECTION ITEM GORY ITEM TO BE EXAMINED PER MOUNT EXAM IDENTIFICATION REPORT NO.
B9.31
PPM-0043, Rev. 0 (6/86) (M&SP 5.2)
B-J
1
1
(CONTINUED)
MAIN STEAM B
MAIN STEAM C
MAIN STEAM D
RWCU
RECIRC A
RECIRC B
RECIRC BYPASS A
RECIRC BYPASS B
RECIRC MANIFOLD
ONE
TWO THREE
ONE
TWO THREE
ONE
TWO THREE
ONE
THREE
TWO
TWO THREE
ONE TWO
2
1
MSBJ-16,20 (BASELINE)
MSCJ-15,20 (BASELINE) MSCJ-18
MSDJ-16,20 MSDJ-18
CWAJ-1
(REMOVED 1984)
(REMOVED 1984)
RMAJ-12
82-305,306
82-308,307
86-054,390,212,393
82-310,309 86-220,389,213,392
82-321
82-29, 123
Form 170278
LCD121787WMHO1
1
2
1 1
1 1
1
1
1
I, 1
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table S9.1 Page 16 of 18
Major Item: PIPING PRFRS!ilF RnliNnARY
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSP. REQ'D AMOUNT ITEM INSPECTION ITEM GORY ITEM TO BE EXAMINED I PER MOUNT EXAM IDENTIFICATION REPORT NO.
NOMINAL PIPE SIZE 2 IN. AND LESS
MAIN STEAM B
RWCU
MAIN STEAM LEAKOFF
CONDENSATE
B9.32
B9.40
HEAD VENT
INSTRUMENT LINES
B-J
B-J
1 1THREE
ONE THREE
TWO
ONE
TWO
THREE
ONE
TWO THREE
3
MSAJ-35
RCBJR-11
50 51 58 59 44 49 55 60 64
VIAJ-1 VIAJ-2 VIAJ-3
86-573,580
87-129,126
84-143 84-142 84-141 84-144 87-172,171 87-174,173 87-176,175 87-178,177 87-180,179
84-202 84-201 84-069
a ____________________ a a a a a
PPM-0043, Rev. 0 (6/86) (M&SP 5.2)
LCD121787WMHO1
'CRD SCRAM HDR
RECIRC DRAIN A & B
SOCKET WELDS
1
4
5
Form 17-0278
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table S9 .1 Page 17 of 18
Major Item: PIPING PRESSURE BOUNDARY
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSP. RE'D MOUNT ITEM INSPECTION ITEM GORY ITEM TO BE EXAMINED PER MOUNT EXAM IDENTIFICATION REPORT NO.
(CONTINUED)
BOTTOM HEAD DRAIN
STANDBY LIQUID CONTROL
MAIN STEAM LEAKOFF
CONDENSATE
Rev. 0 (6/86) (M&SP 5.2)
ONE
TWO
THREE
ONE TWO THREE
ONE
4
3
1
3
13
HDAJ-25 HDAJ-26 HDAJ-27 HDAJ-28 HDAJ-10 HDAJ-42 HDAJ-9
CPAJ-22
24,25,26
(BASELINE EXAMS MSDAJ-1 MSDAJ-1A MSDAJ-1B MSDAJ-2 MSDAJ-3 MSDAJ-4 MSDAJ-5 MSDAJ-6 MSDAJ-7 MSDAJ-8 MSDAJ-9 MSDAJ-10 MSDAJ-11
86-488,478 86-482,472 86-487,477 86-483,473 87-359,354 87-199,196 87-358,353
84-032
86-574,579,575, 578,576,577
86-552,570 86-606,605 86-603,602 86-027 86-533,569 86-028 86-554,568 86-029 86-555,565 86-041 86-556,566 86-031,604 86-557,567
LCD121787WMHOl
B-JB9.40
PPM-0043, Form 17-0278
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECrION-EXAMINATION SUMMARY
Table S9.1 Page 18 of 18
Major Item: PIPING PRESSURE BOUNDARY
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSP. REQ'D MOUNT ITEM INSPECTION ITEM GORY ITEM TO BE EXAMINED PER MOUNT EXAM IDENTIFICATION REPORT NO.
(CONTINUED)
MAIN STEAM LEAKOFF
CONDENSATE
CRD SCRAM HEADER DRAINS
RECIRC MANIFOLD BYPASS OF M02-65A AND M02-65B
RECIRC A & B DRAIN
TWO THREE
ONE
TWO THREE
ONE TWO THREE
ONE TWO THREE
3 3
1
1
4
3
2 2 3
11
2
4
2 2
MSDDJ-1 MSDDJ-2 MSDDJ-3 MSDDJ-4 MSDDJ-5 MSDDJ-6 MSDDJ-7 MSDDJ-8 MSDDJ-9 MSDDJ-10 MSDDJ-11
SDAJ-3 SDBJ-5
VBBJ-8,9,10,11
(REMOVED 1984)
6A, 7A 3B, 6B
1 1 .1 L .5 1 .1 Form 17.0278PPM-0043, Rev. 0 (6/86) (M&SP 5.2)
86-499,564 86-036 86-498,563 86-035 86-497,562 86-034 86-549,561 86-548,560 86-033 86-550,559 86-551,558
86-230,248 86-262,361
82-93,90,92,91
82-162, 89 87-131,128,130,127
LCD121787WMHO1
B9.40 B-J
: A I t
Form 17-0278
k , A
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table S10.1
Paae 1 of 3 Major Item: SUPPORT MEMBERS
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSP. IREQ'D AMOUNT ITEM INSPECTION ITEM GORY ITEM TO BE EXAMINED I PER 1AMOUNT EXAM I IDENTIFICATION REPORT NO.
INTEGRALLY WELDED ATTACHMENTS AND B11.10 COMPONENT SUPPORTS
MAIN STEAM A
MAIN STEAM B
MAIN STEAM C
MAIN STEAM D
FEEDWATER A & B
FEEDWATER A
FEEDWATER C & D
PPM-0043, Rev. 0 (6/86) (M&SP 5.2)
ONE
TWO THREE
ONE TWO THREE
ONE TWO THREE
ONE TWO THREE
ONE
TWO THREE
ONE
TWO THREE
ONE
TWO THREE
1
1
2
1 1.
2 1
1
1
2
1
1
2
2
3
1
MSAK-7(BASELINE)
MSDK-32
FWAK-7(BASELINE) FWBK-7(BASELINE)
FWAK-29(BASELINE) FWAK-21
FWDK-13(BASELINE) FWDK-7 FWCK-7
FWDK-7
86-170,170R,182 182R,166
87-377,372,374
86-613 86-607,607R
86-142,113,066 86-611
86-110,108,067 86-594,594R 86-595,87-280, 282,283 87-279,281,284
Form 170278
LCD122187WMHO1
B10. 10 B-K-1
. I . A
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table S10.1 Page 2
Major Item: SUPPORT MEMBERS
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSP. REQ'D AMOUNT ITEM INSPECTION ITEM GORY ITEM TO BE EXAMINED IPER IAMOUNT EXAM IDENTIFICATION REPORT NO.
310. 10 B-K-1
1
1
(CONTINUED)
FEEDWATER D
RWCU
RHR TW36
RCIC STEAM
RECIRC A
RECIRC B
RECIRC MANIFOLD
ONE TWO THREE
ONE TWO THREE
ONE
TWO THREE
ONE
ONE
TWO THREE
ONE TWO
THREE
ONE
TWO
THREE
2
1
3
2 2
4
2
FWDK-29(BASELINE)
RHDK-14(BASELINE) RHDK-14A(BASELINE)
RSAK-6(BASELINE)
RCAK-16, RCAK-33
18
RCBK-10A,14 RCBKR-16 RCBKR-32
RMAK-13, 13B RMAK-17A, 17B RMAKR-6 RMBKR-13
__________ A __________ I A I £
PPM-0043, Rev. 0 (6186) (M&SP 5.2)
1
-
Form 17o78
LCD122187WMHO1
3
2 3
2 2
4
4
3
3
1
of 3
86-141,115,068
86-416,416R 86-586
86-415
82-42,63,41,64 82-40,40R,176
82-36,66,35,68 87-347,348,371 87-376,373,350
82-47,163,49,361 82-154,175,157,164 87-135,136,134 87-357,355,351
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERAl ING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table S10.I Page 3 of 3
Major Item: SUPPORT MEMBERS
EXAM COMPONENT OR SYSTEM [ I I IP O SUB CATE- AND DESCRIPTION OF INSP. ECON ITEM GORY ITEM TO BE EXAMINED PER MOUNT EXAM IDENTIFICATION REPORT NO.
(CONTINUED)
SCRAM DISCHARGE A & B
PUMPS
VALVES
PPM-0043, Rev. 0 (6/86) (M&SP 5.2)
ONE
TWO THREE
3
3
3
1
CDBK-2 CDBK-31 CDBK-47 CDBK-4
86-218,218R,365,31( 86-443,450,311 8F-261,362,352 8-7-004
I - a. a a.
Fon 170278
LCD122187WMHOI
310. 10
RIO. 20
B10.30
B-K-I
B-K-1
B-K-1
I k I I
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table S11.1 Page 1 of 5
Major Item: COMPONENT SUPPORTS
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSP. REO'D MOUNT ITEM INSPECTION ITEM GORY ITEM TO BE EXAMINED I PER MOUNT EXAM I IDENTIFICATION REPORT NO.
311. 10 B-K-2 COMPONENT SUPPORTS
MAIN STEAM A
MAIN STEAM B
MAIN STEAM C
MAIN STEAM D
FEEDWATER A
FEEDWATER A
FEEDWATER D
FEEDWATER D
2ONE TWO THREE
ONE TWO THREE
ONE TWO THREE
ONE TWO THREE
ONE TWO THREE
ONE TWO THREE
ONE TWO' THREE
ONE TWO THREE
I I L I ________ a
PPM-0043, Rev. 0 (6/86) (M&SP 5.2)
2
2
2
2
2 1
2 1 1
2
1 2 1 1
1
Form 170278
LCD110482R11
MSAK-13,14
MSCK-14,17
MSDK-31
FWAK-15,17 FWAK-13,14
FWAK-31
FWDK-17,14
FWDK-21,31 FWDK-31
86-069,414,414R
86-065,071
86-198
86-197,277,277R 86-608,609
86-278,278R,278R1
86-072,592
86-279,279R,589 87-288, 288R
, 0
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table S11.1 Page -2 .. ofb
Major Item: CO PONENT SUPPORTS
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSP. REQ'D MOUNT ITEM INSPECTION ITEM GORY ITEM TO BE EXAMINED PER MOUNT EXAM IDENTIFICATION REPORT NO.
B11. 10
PPM-0043, Rev. 0 (6/86) (M&SP 5.2)
B-K-2
1 2
1
1 2
(CONT'D)
CORE SPRAY A
CORE SPRAY B
HPCI-STEAM
RWCU
RHR REW10
RHR TW20
RHR TW30
ONE
TWO THREE
ONE
TWO THREE
ONE TWO THREE
ONE TWO THREE
ONE TWO THREE
ONE TWO THREE
ONE
TWO THREE
CSAK-15 CSAK-7(BASELINE) CSAK-15(BASELINE) CSAK-7
CSBK-6 CSBK-6(BASELINE) CSBK-15(BASELINE)
RHCK-10 RHCK-9 RHCKR-10,17A,24
LCD110482R11
2
3
84-111 86-667 86-670 87-335
84-112 86-668 86-669
84-261 84-260 87-375,289,290
Form 17-0278
I ,I , I .
, ir f a
NORTHERN STATES PONER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table S11.1 Page 3 of 5
Major Item: CO PONENT SUPPORTS
EXAM COMPONENT OR SYSTEM ITEM SUB CATE- AND DESCRIPTION OF INSP. REQ'D MOUNT ITEM INSPECTION ITEM GORY ITEM TO BE EXAMINED PER MOUNT EXAM IDENTIFICATION REPORT NO.
B11. 10 B-K-2 (CONT'D)
RHR TW36
RHR TW40
RCIC-STEAM
RECIRC A
RECIRC B
RECIRC BYPASS A & B
ONE TWO THREE
ONE TWO THREE
ONE
TWO THREE
ONE
TWO
THREE
ONE
TWO THREE
ONE TWO
HREE
RHDK-29(BASELINE)
RHEKR-10 RHEKR-12
RSAK-6 RSAK-9(BASELINE)
RCAK-6, 34 PHA-5 PSSA-5 PHAR-4, 5 PSSAR-5 RCAKR-12
RCBK-10, 12 PHB-6 PSSB-5
RBBK-14 (REMOVED 1984)
86-503
84-1508BL 87-110
84-217 86-685
82-043, 039 82-44 82-48 87-118, 117 87-116 87-115
82-37, 37R, 38 82-360, 360R 82-359
82-75
a a a a aPPM-0043, Rev. 0 (6/86) (M&SP 5.2)
LCD110482R11
4
1
Form 17-0278
, I I t
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table S11.1 Pa e of 5
Major Item: CO PONENT SUPPORTS
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSR REQ'D MOUNT ITEM INSPECTION IEM GORY CITEM TO BE EXAMINED E II TE GITEM TEIOB EAIE PER [MOUNT EXAM I IDENTIFICATION REPORT NO.1311.10
PPM-0043, Rev. 0 (6/86) (M&SP 5.2)
B-K-2
4
3
3
(CONT'D)
RECIRC MANIFOLD A & B
RECIRC RISERS MANIFOLD A & B
HEAD VENT LINE
BOTTOM HEAD DRAIN
STANDBY LIQUID CONTROL
MAIN STEAM CONDENSATE LEAK OFF 3"
ONE
TWO THREE
ONE
TWO
THREE
ONE TWO THREE
ONE
TWO THREE
ONE TWO THREE
ONE TWO THREE
RMAK-11, 13A, 17 RMBK-17
RRJK-6 .RRKK-6 RRDK-6 RRCKR-6 RRGKR-6 RRHKR-6
HVAK-21
HDAK-24A HDAK-28A HDAK-29A
CPAK-20 CPAK-14A
SR-723
82-45, 46, 159 82-158
82-50, 50R 82-51 82-155 87-113 87-112 87-111
84-218
86-471 86-671 86-672
84-219 87-114, 114R
87-009
LCD110482R11
1
3
1 1
1
Form 170278
,t I I
4 4
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table 11 .1 Page of 5
Major item: COMPONENT SUPPORTS
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSP. REQ'D AMOUNT ITEM INSPECTION ITEM I GORY ITEM TO BE EXAMINED I PER AMOUNT EXAM I IDENTIFICATION REPORT NO.
(CONTINUED)
MAIN STEAM CONDENSATE LEAK OFF 2"
CRD SCRAM HEADER A & B
B11.10
B11.20
B11.30
R-K-2
B-K-2
B-K-2
RECIRC VALVE BYPASS A&B
PUMPS
COMPONENT SUPPORTS
VALVES
COMPONENT SUPPORTS
PPM-0043, Rev. 0 (6/86) (M&SP 5.2)
ONE TWO
THREE
ONE
TWO
THREE
ONE TWO THREE
ONE TWO THREE
3
9
8
1
1
PSH-724, SR-722
725
CDAK-2A,3A,19, 20,38A,40,5
CDBK-3,17A CDBK-16A, 17
CDAK-19A,230,2A
CDAK-30,37,4
SDBK-6
VBBK-6A (REMOVED 1984)
87-011, 005 87-010
86-343,344,346, 347,348,349,254, 250,345 86-350,351 87-002,003,002R, 001,001R 87-333,333R,332, 328 87-329,330,331
86-674
82-156
Form 17-0278
LCD110482R11
CRD SCRAM A & B
HEADER DRAIN
IC
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAIR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table S12.1 Page I of 1
Major Item: PUMP CASING & VALVE BODIFS
IEXAM I CO)MPONENT OR SYSTEM I III SUB CATE- AND DESCRIPTION OF INSP. REQ'D MOUNT ITEM INSPECTION ITEM GORY ITEM TO BE EXAMINED I PER MOUNT EXAM IDENTIFICATION REPORT NO.
PUMPS
PUMP CASING WELDS
PUMP CASING
RECIRC PUMPS A & B
VALVES
VALVE BODY WELDS
VALVES BODY, EXCEEDING 4 IN. NOMINAL PIPE SIZE
ATWOOD MORRILL GLOBE VALVES
TARGET ROCK RELIEF VALVES
ANCHOR CHECK VALVES
ATWOOD MORRILL CHECK VALVE
ROCKWELL CHECK VALVE
ANCHOR GATE VALVE
CRANE CHAPMAN GATE VALVE
PPM-0043, Rev. 0 (6/86) (M&SP 5.2)
LCD110482R12
B12. 10
B12.20
B12. 10
B12.20
B-L-1
B-L-1
B-L-1
B-L-1
THREE
THREE
THREE
TWO
THREE
THREE
1 1 A010-46B 87-154
Form 170278
. I I .
, . t
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table S13.1 Page 1 of 2
Major item: REACTOR VESSEL INTERIOR
EXAM COMPONENT OR SYSTEM I SUB CATE- AND DESCRIPTION OF INSP. REQ'D MOUNT ITEM INSPECTION ITEM GORY ITEM TO BE EXAMINED I PER MOUNT EXAM I IDENTIFICATION REPORT NO.
REACTOR VESSEL
VESSEL INTERIOR
INTERIOR ATTACHMENTS & CORE SUPPORT STRUCTURES
B13.10
813.20 & 813.3
*B-N-I
B -N -1
*ONE
TWO THREE
ONE
TWO THREE
Appendix H Core Spray Appendix I Feedwater Appendix B Cladding Appendix E Jet Pumps *Inspected areas abo reactor core that is for examination.by t components during no
Appendix J Shroud Supports Appendix C Top Guide Appendix F Shroud Shelf Appendix K Steam Dryer Brackets Appendix L Dryer Support Appendix D Steam Separator Guide Rod Brackets *Inspected visually attachments and supp
84-149/86-693 87-031 84-148/86-694 87-032 86-689
86-691 87-030 ie and below the made accessible e removal of -mal refueling.
84-150
86-690 87-028 86-692
86-695
86-696 87-033 87-029
ccessible rts
J JI a a I _____________ I
PPM-0043, Rev. 0 (6/86) (M&SP 5.2)
LCD110482R13
* *
Form 170278
I I I
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table S13.1 Page 2 of 2
Major item: REACTOR VESSEL INTERIOR
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSP. REQ'D MOUNT ITEM INSPECTION ITEM GORY ITEM TO BE EXAMINED I PER MOUNT EXAM IDENTIFICATION REPORT NO.
REACTOR VESSEL (PWR)
CORE SUPPORT STRUCTURES
.5 ______ .1 & .1 & .1
PPM-0043, Rev. 0 (6/86) (M&SP 5.2) Form 17-0278
LCD110482R13
B13.30 B-N-1
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECrION-EXAMINATION SUMMARY
Table S14.1 Page 1 of1
Major Item: CONTROL ROD HOUSING WELDS
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSP REQD AMOUNT ITEM INSPECTION ITEM GORY ITEM TO BE EXAMINED L PER MOUNT EXAM IDENTIFICATION REPORT NO.
REACTOR VESSEL
WELDS IN CRD HOUSING ONE TWO THREE
1 1 1
1 22-03 86-332, 333
PPM-0043, Rev. 0 (6/86) (M&SP 5.2) Form 170278
114. 10 B-0
I A I I
PPM-0043, Rev. O (6/86) (M&SP 5.2) Form ITove
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table S15.1 Page 1 of 1
Major Item: PRESSURE RET NING COMPONENTS
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSP.. RED MOUNT ITEM INSPECTION ITEM IGORY ITEM TO BE EXAMINED IPER MOUNT EXAM IIDENTIFICATION REPORT NO.
REACTOR VESSEL
PIPING
PUMPS
VALVES
REACTOR VESSEL
PIPING
PUMPS
VALVES
PRESSURIZER
STEAM GENERATORS
HEAT EXCHANGERS
PPM-0043, Rev. 0 (6/86) (M&SP 5.2)
LCD121587WMHO4
B15. 10
115.50
115.60
B15.70
B15. 11
B15.51
B15.61
115.71
B15.20
B15.30
B 15.40
B-P
B-P
B-P
B-P
B-P
B-P
B-P
B-P
B-P
B-P
B-P
Form 170278
I I
IS I
NORTHERN STATES POWER COMPANY MONTICELLO Unit I Examination comparison Summary
SUB-ITEMI SYSTEM ICLASS I ISO IMETHI ITEM | REPORT PREVIOUS RESULTS CURRENT RESULTS LIMITATIONS
-------- I........--------.I------ I ---------- I---- I --------------- I --------- I -------------------- ------------------- I -----------------81.11 (REACTOR VESSEL I FIGURE 4 |UTO IVCBB-4 @ N4B 187-293 1 Resutts:NONE Resutts:NONE IINSULATION 8" UPSTRM WELD TOE 181.11 REACTOR VESSEL I FIGURE 4 JUT4 jVCBB-4 @ N4B 187-315 1 Resutts:NONE Results:NONE LIMITED TO 6"; INSULATION 181.11 IREACTOR VESSEL I IFIGURE 4 jUT6 IVCBB-4 @ N4B 187-298 1 Resutts:NONE Resutts:NONE INSULATION 6" DNSTRM WELD TOE IB1.11 IREACTOR VESSEL I IFIGURE 4 IVT1 IVCBB-4 @ N4B 187-304 1 Results:NONE Resutts:NAD NONE IB1.11 REACTOR VESSEL I FIGURE 4 IUTO IVCCB-4 @ N4C 187-291 1 Resuits:NONE Resutts:NONE jINSULATION 6" UPSTRM WELD TOE 1B1.11 REACTOR VESSEL I FIGURE 4 IUT4 IVCCB-4 @ N4C 187-313 1 Resutts:NONE Results:NONE LIMITED TO 8"; INSULATION 181.11 REACTOR VESSEL I FIGURE 4 JUT6 IVCCB-4 @ N4C -187-301 1 Resutts:NONE Results:NONE INSULATION 8" DNSTRM WELD TOE B1.11 REACTOR VESSEL I I IFIGURE 4 bVT1 IVCCB-4 6 N4C 187-306 1 Results:NONE Resutts:NAD NONE 181.21 REACTOR VESSEL I FIGURE 5 |UTO |HCAB-1 6 HMAB-4|87-247 Resutts:NONE Resutts:NONE 12"x4" LUG, 4" DS AT 18" 181.21 REACTOR VESSEL I FIGURE 5 |UT4 HCAB-1 6 HMAB-4187-258 I Results:NONE Results:NONE 12"x4" LUGS, 4" DS 6 18" CW. 181.21 REACTOR VESSEL I FIGURE 5 IUT6 |HCAB-1 6 HMAB-4187-273 Resutts:NONE Results:NONE NONE 81.21 |REACTOR VESSEL I I FIGURE 5 |VT1 |HCAB-1 6 HMAB-4187-297 Results:NONE Results:NAD NONE 181.21 IREACTOR VESSEL I IFIGURE 5 |UTO jHCCB-2 120-240 187-186 1 Resutts:NONE Resutts:IND ACCEPTABLE SPOT INDICATION
I I I I I I I I I I I I I IType:SPOT I I I I I I IAmptitude:35
xI I I 1 1 I-3 I I I I I I ILoc:1811 I I I I I I ILength:<.25 181.21 |REACTOR VESSEL I I FIGURE 5 |UT4 |HCCB-2 120-240 187-161 1 Results:NONE Results:NONE INONE
181.21 REACTOR VESSEL I I FIGURE 5 |UT6 IHCCB-2 120-240 187-184 1 Results:NONE Results:NAD NONE
|81.21 REACTOR VESSEL | I FIGURE 5 |VT1 (HCCB-2 120-240 187-190 1 Results:NONE Results:NAD NONE
JB1.22 REACTOR VESSEL | I IFIGURE 5 |UTO |HMAB-2 2'-5" 187-245 1 Resutts:N/A Resutts:NAD NONE
181.22 REACTOR VESSEL I I FIGURE 5 jUT4 |HMAB-2 2--5" 187-257 1 Resutts:N/A Resutts:NAD NONE 81.22 REACTOR VESSEL I I FIGURE 5 |UT6 IHMAB-2 2--5" 187-271 1 Resutts:N/A Results:NAD ACCEPTABLE SPOT INDICATION 181.22 IREACTOR VESSEL I I FIGURE 5 |VT1 IHMAB-2 2--5" 187-295 1 Resutts:N/A Results:NAD jNONE
181.22 |REACTOR VESSEL | I FIGURE 5 |UTO |HMAB-3 2'-5" 187-246 1 Resutts:N/A ResuLts:NAD NONE 1B1.22 |REACTOR VESSEL | I IFIGURE 5 |UT4 IHMAB-3 2'-5" 187-256 1 Resuits:N/A Results:NAD NONE 1B1.22 |REACTOR VESSEL I I IFIGURE 5 IUT6 |HMAB-3 2--5" 187-272 1 Resutts:N/A Resutts:NAD NONE I81.22 |REACTOR VESSEL I |FIGURE 5 IVT1 |HMAB-3 2--5" 187-296 1 Resutts:NONE Results:NAD NONE 181.22 |REACTOR VESSEL I |FIGURE 5 |UTO jHMCB-5 7' 187-187 1 Results:NONE ResuLts:NAD INONE 181.22 IREACTOR VESSEL I IFIGURE 5 |UT4 IHMCB-5 7' 187-162 1 Results:NONE Resutts:NAD INONE
|81.22 IREACTOR VESSEL I I jFIGURE 5 IUT6 |HMCB-5 7' 187-185 1 Resutts:NONE Resutts:NAD NONE
181.22 |REACTOR VESSEL I I IFIGURE 5 IVT1 |HMCB-5 7' 187-193 1 Results:NONE Resutts:NAD NONE 11.22 IREACTOR VESSEL I I IFIGURE 5 IUTO JHMC-6 7' 187-188 1 Resutts:NONE Results:NAD INONE
Page 1 of 26
, f . .
NORTHERN STATES POWE MONTICELLO Unit I
ISUB-ITEMI SYSTEM |CLASS
I -------- I........---.1----jB1.22 IREACTOR VESSEL I I 121.22 |REACTOR VESSEL I I 181.22 |REACTOR VESSEL | I B10.10 |CRD SCRAM HDR B I I 810.10 IFEEDWATER C I I f810.10 IFEEDWATER C I I 810.10 FEEDWATER C I 810.10 IFEEDWATER D I 1810.10 IFEEDWATER D I 810.10 IFEEDWATER D I 1810.10 MAIN STEAM D I JB10.10 IMAIN STEAM D I I 1810.10 MAIN STEAM D I 1810.10 IRECIRC LOOP B I 1810.10 IRECIRC LOOP B I I 1810.10 IRECIRC LOOP B I I 1810.10 IRECIRC LOOP B I 1810.10 IRECIRC LOOP B I I
I I I I I I I I 1810.10 IRECIRC LOOP B I I 1810.10 |RECIRC LOOP B I I 1810.10 IRECIRC MAINF LOOP A I 1810.10 |RECIRC MANIF LOOP A I 1810.10 IRECIRC MANIF LOOP A I 1810.10 IRECIRC MANIF LOOP B I 1810.10 IRECIRC MANIF LOOP B I 1810.10 jRECIRC MANIF LOOP B I 811.10 CORE SPRAY A I 1811.10 ICRD SCRAM HDR B I I
I I I I I I I I I
II I
R COMPANY TABLE S-II Examination Comparison Summary
.. .. . . . .. . . . .. .. .. .... ... .. ....... ............................................ I ISO IMETHI ITEM REPORT PREVIOUS RESULTS CURRENT RESULTS LIMITATIONS
- -- - --1 - -I- - - - - - - -I- - - - - - - - - - - - - - - - - - - - - - - - - - ------- ---------- ----- --
IFIGURE 5 |UT4 |HMCB-6 7- 187-164 | Results:NONE Resutts:NAD INONE |FIGURE 5 (UT6 |HMCB-6 7' 187-183 1 Results:NONE Results:NAD INONE |FIGURE 5 |VT1 (HMCB-6 7' 187-192 1 Resutts:NONE Results:NAD |NONE JISI-24B |VT3 ICDBK-4 187-004 I Results:N/A Resutts:NAD |NONE ISI-5B MT |FWCK-7 j87-280 | Results:NONE Results:NAD ILUGS 1-4
|ISI-5B JVT1 IFWCK-7 187-282 1 Results:NONE Resutts:NAD INONE ISI-5B |VT3 IFWCK-7 187-283 1 ResuLts:NONE Results:NAD INONE
JISI-5B |MT jFWDK-7 187-279 I Results:NONE Resutts:NAD ILUGS 1-4 1ISI-5B jVT1 IFWDK-7 187-281 | Results:NONE Results:NAD |NONE |ISI-5B IVT3 IFWDK-7 187-284 1 Results:NONE Results:NAD INONE ISI-4 MT IMSDK-32 187-377 1 Results:NONE ResuLts:NONE IPAINTED SURFACE
IISI-4 IVT1 IMSDK-32 187-372 | Results:NONE Results:NONE ILUGS 1-4
IISI-4 IVT3 IMSDK-32 |87-374 1 Resutts:NONE ResuLts:NONE |2 LUGS INSULATED ISI-13B PT IRCBKR-16 87-347 Results:NONE Results:NAD INONE ISI-13B IVT1 IRCBKR-16 87-348 Resutts:NONE Results:NAD INONE
IISI-13B IVT3 IRCBKR-16 187-371 1 Results:NONE Results:NAD NONE 11SI-13B IVT3 IRCBKR-29 |87-334 Results:NONE Results:NAD NONE 11SI-13B jPT IRCBKR-32 |87-376 1 Results:IND Results:NONE 11" BOTTOM OF LUGS
I | Type:LINEARS I I I I IAx Loc: I I I I I Circ Loc: I I I I I Length: I |ISI-13B IVT1 jRCBKR-32 j87-373 1 ResuLts:NONE | Resutts:NAD ji" BOTTOM OF LUGS
11SI-13B IVT3 IRCBKR-32 187-350 | Results:NONE I Results:NAD INONE 1ISI-13C IPT IRMAKR-6 187-135 1 Results:NONE | Results:NA0 |NONE IISI-13C IVT1 RMAKR-6 187-136 1 Results:NONE Results:NAD |NONE |ISI-13C IVT3 IRMAKR-6 j87-134 1 Resutts:NONE j Resutts:NAD jNONE |ISI-13D PT IRMBKR-13 187-357 1 Results:NONE Results:NAD INONE JISI-13D JVT1 IRMBKR-13 187-355 1 ResuLts:NONE Results:NAD |NONE IISI-13D IVT3 IRMBKR-13 187-351 1 Results:NONE Results:NAD INONE |ISI-6A IVT3 ICSAK-7 187-335 1 Results:NONE ResuLts:NAD |NONE 1ISI-24B IVT3 ICDBK-16A 187-002 1 Results:N/A I Results:IND jSEE REPORT 87-002R FOR REPAIR
IIType:BOLT LOOSE I I I I Ax Loc:
I I I I I I Circ Loc: I I I I I ILength: I I I I IIII
Page 2 of 26
TABLE S-II NORTHERN STATES POWER COMPANY MONTICELLO Unit I Examination Comparison summary
-------------------------------------------------------------------------------------------------------------------------ISUB-ITEMI SYSTEM CLASS I ISO JMETHI ITEM I REPORT PREVIOUS RESULTS CURRENT RESULTS LIMITATIONS I .. . . ... I...-------------- -- -------- -- I --------------- I ------ I ---- ------------ I-----------------I------------------------------I 811.10 ICRD SCRAM HDR B I |ISI-24B JVT3 ICDBK-16A 187-003 1 Results:N/A Results:NAD NONE 1811.10 CRD SCRAM HDR B 1 1, (ISI-24B |VT3 CDBK-16A 87-002R Results:N/A I Results:NAD INONE 1811.10 ICRD SCRAM HDR B | I |ISI-248 (VT3 ICOBK-17 87-001 Resutts:N/A Resutts:IND ENGINEER EVALUATION - ACCEPT.
I I |I Type:MISS WELD I I I I I I I I Ax Loc:
I I I I I I I I I Circ Loc: I I I I I I I I Length:
IB11.10 |CRD SCRAM HDR B I I ISI-24B |VT3 ICDBK-17 187-001R I Results:N/A | Results:NAD NONE 1811.10 CRD SCRAM HEADER A I ISI-24A VT3 ICDAK-19A 87-333 Results:N/A | Results:IND SEE REPORT 87-333R FOR REPAIR
I Type:THRD ENG'T I I I I I I I I IAx Loc: I I I I I 1 I I I C irc Loc: I
I JCRD SCRAM HEADER A |CRD SCRAM HEADER A
|CRD SCRAM HEADER A
ICRD SCRAM HEADER A
|CRD SCRAM HEADER A
ECRD SCRAM HEADER A IFEEDWATER D
I
I I
|FEEDWATER D
I I
I
|MS CONDENSATE jMS DRAIN A IMS DRAIN A |MS DRAIN D
jRECIRC LOOP A
| I |ISI-24A IVT3 ICDAK-19A I |ISI-24A IVT3 ICDAK-230
I I |ISI-24A (VT3 (CDAK-2A
| I IISI-24A IVT3 ICDAK-30
I I |ISI-24A JVT3 ICDAK-37 I I JISI-24A IVT3 CDAK-4 I I |ISI-5B JVT3 IFWDK-31
I I I I I I I IS I I S IP I I 1ISI1-5B IVT3 |FWDK-31
I I I I I I I I I I I I
I I |ISI-23 |VT3 jPSH-724 I I |ISI-23 IVT3 ISR-722 I I JISI-23 IVT3 IPSH-725
I |ISI-13A jVT3 |PHAR-4
I I I I I I I I I I I I I I I I I I I I
I I I Length: 187-333R I Results:N/A Results:NAD NONE
187-332 1 Results:N/A Resutts:NAD INONE
187-328 | Resutts:NONE Results:NAD INONE
187-329 1 Results:N/A Results:NAD NONE
187-330 1 Results:N/A Results:NAD INONE
187-331 | Results:N/A | Results:NAD NONE
187-288 1 Resutts:NONE ( Results:IND INUTS TACK WELDED SEE 87-288R
I I I Type:THRD ENG'T I 1 I Ax Loc:
I I I Circ Loc: I I I Length: 187-288R I Results:NONE Results:IND ENGINEER EVALUATION - ACCEPT.
I I | Type:THRD ENG'T I
187-009 187-011 187-010 187-005 187-118
Resutts:N Results:N
I Results:N Results:N Results:l
I Type:LOOS Ax Loc:
Circ Loc:
I Length:
/A /A /A /A ND E BOLT
Ax Loc: Circ Loc: Length: Results:NAD Results:NAD Results:NAD Resutts:NAD Results:NONE
(NONE NONE NONE INONE NONE
I
I
Page 3 of 26
I 1811.10 (811.10 811.10
IB11.10
1811.10
1811.10 6B11.10
1811.10 IB I I
jB11.10
I
I
|B11.10
JB11.10 |B11.10
|811.10
JB11.10 I I
I
I I
, I Vt 4
NORTHERN STATES POWER COMPANY MONTICELLO Unit I Examination comparison summary
-------------------------------------------------------------------------------------------------------------------------SUB-ITEMI SYSTEM fCLASS I ISO IMETHI ITEM I REPORT PREVIOUS RESULTS I CURRENT RESULTS I LIMITATIONS 1-------- ----------------------1------1----------I----1 ----- I -----------------1811.10 IRECIRC LOOP A I I IISI-13A 1VT3 |PHAR-5 187-117 1 Resutts:NONE I Resuits:NA NONE 1811.10 IRECIRC LOOP A I IISI-13A IVT3 PSSAR-5 187-116 1 Results:NONE Resutts:NAD INONE 811.10 jRECIRC LOOP A I ISI-13A 1VT3 IRCAKR-12 187-115 1 Results:NONE Resutts:NAD NONE IB11.10 IRECIRC RISER C I IISI-13D JVT3 jRRCKR-6 187-113 1 Resuits:NONE Results:NAD NONE 1111.10 (RECIRC RISER G I JISI-13C |VT3 IRRGKR-6 187-112 1 Resutts:NONE Results:NAD INONE 811.10 IRECIRC RISER H I I JISI-13C JVT3 jRRHKR-6 187-111 1 Resutts:IND Resutts:NONE NONE
I I I I ITpe:LOOSENUT I I I I I I I I I I I I I ILength: I |811.10 |RHR LOOP C I I |ISI-11C IVT3 IRHCKR-10 187-375 1 Resutts:NONE Results:NAD NONE 1811.10 (RHR LOOP C I I JISI-11C |VT3 IRHCKR-17A 187-289 1 Resutts:IND Resutts:NONE INONE
I I I I IWEEP I I I I I I ICircLoc:HOLE
ILength: 1811.10 JRHR LOOP C | I JISI-11C JVT3 |RHCKR-24 .187-290 1 Results:IND Results:NONE INONE I I I I I I
I I I I I ICircLoc:HOLE I I I I I I 1811.10 RHR LOOP E | I JISI-11E jVT3 (RHEKR-12 187-110 1 Resutts:NONE Results:NAD INONE 1811.10 STANDBY LIQUID CONTRI I |ISI-22 |VT3 ICPAK-14A 187-114 1 Results:NONE ResuLts:IND SEE PERORT 87-114R FOR REPAIR I I I I I IDRAWING I I I I I ILoc: I I I I I ILoc: I I I I I ILength: 1811.10 ISTANDBY LIQUID CONTRI I |ISI-22 jVT3 ICPAK-14A 187-114R I Results:NONE I Resutts:NAD INONE 1812.20 |RHR LOOP B I I IISI-11B IVT1 |A010-46B 187-154 1 Resutts:N/A I Resutts:NAD VALVE DISC SHUT. 1B3.100 IFEEDWATER B | I |ISI-5A |UT4 jFWBD-1 BORE 187-309 1 Resutts:NONE Resutts:NAD ITHERMAL LUG a 9 O'CLOCK. JB3.100 IFEEDWATER 8 1 jISI-5A jUT4 IFWBD-1 IR 187-312 1 Resutts:NONE Results:NAD ILUG @ 2 OCLOCK. 1B3.100 IFEEDWATER C I IISI-5B |UT4 IFWCD-1 BORE 187-310 1 Resutts:NONE Results:NAD ITHERMc-COUPLE 2 9 O'CLOCK. 1B3.100 jFEEDWATER C I IISI-5B IUT4 IFWCD-1 IR 187-311 1 Results:NONE Resutts:NAD INONE 1B3.100 IHEAD SPRAY N6A I I JISI-11D IUT4 IRHDD-1 IR 187-202 I Resutts:NONE Results:NAD INONE 183.100 RECIRC INLET E I |ISI-13D IUT4 IRRED-1 IR 187-386 1 Resutts:NONE Resutts:NAD NONE
Page 4 of 26
NORTHERN STATES POWER COMPANY MONTICELLO Unit I
SUB-ITEM! SYSTEM |CLASS | ISO
I-----I ---------------- I -----I1B3.90 IFEEDWATER B I I |ISI-5A 183.90 IFEEDWATER B | I |ISI-5A 83.90 IFEEDWATER B | I jISI-5A B3.90 IFEEDWATER B I I IISI-5A 1B3.90 IFEEDWATER B | I ISI-5A 1B3.90 IFEEDWATER C I I IISI-5B 183.90 FEEDWATER C I I ISI-5B B3.90 IFEEDWATER C I I ISI-5B 1B3.90 IFEEDWATER C | I IISI-5B IB3.90 HEAD SPRAY N6A I I IISI-11D JB3.90 HEAD SPRAY N6A | I ISI-11D IB3.90 IHEAD SPRAY N6A I IISI-11D IB3.90 |HEAD SPRAY N6A I I JISI-11D 183.90 |HEAD SPRAY N6A I I |ISI-11D 1B3.90 JHEAD SPRAY 46A | I |ISI-11D 1B3.90 IRECIRC INLET E I I JISI-13D
I I I I I I I I S I I I I
II I I I I I I I I I I 83.90 |RECIRC INLET E | I |1SI-13D
I I I I I I I I I I I I I I I I
B83.90 |RECIRC INLET E | I |1SI-13D
| I I I I I I I I I I
I I|I 11 I I I 1 I I I
T
Examination Co
IMETHI ITEM I REPORT I PREVIOUS RESULTS I CURRENT RESULTS
I ---- ..--- ---------------------- I- -------------------- 1--------------------1 jUTO FWBD-1 187-294 1 Results:NONE Results:NAD IT |UT4 IFWBD-1 187-314 | Results:NONE I Resutts:NAD IT IUT6 IFWBD-1 187-299 | Results:NONE ResuLts:NAD IT |UT6 jFWBD-1 187-299 1 Results:NONE j Results:N/A jVT1 IFWBD-1 187-302 | ResuLts:NONE | ResuLts:NAD |UTO jFWCD-1 187-292 1 Resutts:NONE ResuLts:NAD
|UT4 IFWCD-1 187-316 1 ResuLts:NONE Results:NAD IUT6 IFWCD-1 187-300 | Results:NONE | Resutts:NAD IN IVT1 jFWCD-1 j87-303 1 Resutts:NONE | ResuLts:NAD N IUTO IRHDD-1 187-189 | Results:NONE | Results:NAD N IUT4 IRHDD-1 187-163 | Results:NONE I Resutts:NAD IN IUT4 IRHDO-1 187-163 | Results:NONE Resutts:N/A IN IUT6 IRHDD-1 187-182 1 Results:NONE ResuLts:NAD IN
|UT6 IRHDD-1 187-182 I ResuLts:NONE I Results:N/A IN IVT1 IRHDD-1 187-191 1 Resutts:NONE | Resutts:NAD IN |UTO IRRED-1 187-362 I Results:NONE | ResuLts:IND I I I I I I Scan: 1L I I I I I Type:SPOT I I I I I Amplitude:40
I I I Ax Loc:5" I I I I Circ Loc:15 I I I I I Length:SPOT |UTO IRRED-1 187-362 1 Results:NONE I*ResuLts:IND I I I I I Scan: iL I I I I I I Type:SPOT I
I I I I AmpLitude:45 I I I I Ax Loc:3" | | | | | Circ Loc:6:00
| I | I | Length:SPOT |UTO IRRED-1 187-362 I Results:NONE I Resutts:IND I I I I I I Scan: iL L
I I I I Type:SPOT I I 1 I I Amplitude:55 | | | | I | Ax Loc:C.L. WELD I | | I I Circ Loc:6:00+17"1 I I I I I Length:SPOT I 1 1I I I II
ABLE S-II
mparison summary
LIMITATIONS ....-................. I HERMO-COUPLE a 2 O'CLOCK. *HERMO COUPLE 6) 2:00 3/4"LONG HERMO COUPLE a 2 O'CLOCK 0 S-2 DUE TO CONFIGURATION ONE NONE ONE 0 S-2 DUE TO CONFIGURATION ONE ONE ONE 0 SCAN -- NOZZLE.
ONE O SCAN 2 DUE TO NOZZLE ONE NSUL. 7:30-10:30
NSUL. 7:30-10:30
NSUL. 7:30-10:30
Page 5 of 26
, I . 0
I'
NORTHERN STATES POWE MONTICELLO Unit I
--------------------------|SUB-ITEMI SYSTEM JCLASS I -------- I----- ----------- 1----- I |B3.90 jRECIRC INLET E I I
1 II I I 1
183.90 IRECIRC INLET E I I B3.90 |RECIRC INLET E I I B3.90 (RECIRC INLET E I I
1B3.90 IRECIRC INLET E | I 85.10 |HEAD SPRAY N6A I 85.10 |HEAD SPRAY N6A I I 1B5.10 (HEAD SPRAY N6A I I (85.10 HEAD SPRAY N6A I JB5.10 |HEAD SPRAY N6A I I 185.10 jHEAD SPRAY N6A I I 185.10 (INSTRUMENT N6A B I 1B5.10 (INSTRUMENT N11B I
|B5.10 |INSTRUMENT N11B | I I II I II I II I II
I I I I I I I II I I 1 1I.1 RIR INEI
I II I II I II
I II I II
R COMPANYTABLE S-II
Examination Comparison summary
I ISO (METH| ITEM I REPORT I PREVIOUS RESULTS CURRENT RESULTS I LIMITATIONS -- - - - - -I- - - - - - - -I- - - - - - - - - - - - - - - - - - - - - - - - - - ---- ---- ---- ----
|ISI-13D |UTO IRRED-1 187-362 1 ResutS:NONE Resuits:IND (INSUL. 7:30-10:30
I Scan:1L I I I I fType:LAMINATION I I I I IAmplitude:65
IAx Loc:3.5 I I ( I (Circ Loc:12:OO-15"1 I I I ILength:1/2"L1/411W
|ISI-13D |UT4 |RRED-1 (87-389 1 Results:NONE Results:NAD (THRMO-CPLE @ 5:00, 8" (ISI-13D |UT4 (RRED-1 187-389 1 Resutts:NONE Resutts:NAD INO SCAN -- NOZZLE |ISI-13D jUT6 |RRED-1 (87-364 1 Resutts:NONE Results:NAD (NONE |ISI-13D (VT1 |RRED-1 (87-352 1 Resutts:NONE Resutts:NAD (NONE JISI-11D (PT (RHDJ-2 187-206 1 ResuLts:NONE Resutts:NAD (NONE |1SI-11D jUT4 |RHDJ-2 (87-122 1 Resutts:NONE Results:N/A (S-i LIMITED TO 1.25" |ISI-11D |UT4 |RHDJ-2 (87.122 1 Resuits:NONE Results:N/A (5-2 45 deg DOES NOT R (ISI-11D |UT4 (RHDJ-2 (87-122 1 Resutts:NONE Resutts:N/A (S-3 45 deg DOES NOT R (ISI-11D JUT4 |RHDJ-2 (87-388 1 Resutts:NONE Results:NAD (NONE |ISI-11D |VT1 |RHDJ-2 187-387 1 Resutts:NONE Results:NAD (NONE (ISI-18A (PT (VIBF-2 (87-307 1 Resutts:NONE Resutts:NAD (NONE (ISI-18A jUT4 |VIBF-2 (87-322 1 Results:GEO Results:GEO (NONE
Scan:l (Scan: 11 Type: Type:ID/O GEO
(Amplitude:<20 (Amplitude:<20 (Ax Loc: (Ax Loc: Circ Loc: Circ Loc:
I (( (Length: (Length:360 INTMIT (ISI-18A (UT4 |VIBF-2 (87-322 1 Resutts:NONE Results:GEO (NONE
IScan:2 Type:ID/OD GEO
IIAmpIitude:<20 (Ax Loc:
ICircLoc: ILength:360 INTMIT
|ISI-18A |VT1 IVIBF-2 (87.305 1 Resutts:NONE Results:NAD (NONE |ISI-13D (PT |RREFR-2 (87-346 1 Resutts:NONE Resutts:NAD (NONE JISI-13D (UT4 JRREFR-2 187-363 1 Resutts:GEO Resutts:NONE (1.8"SCAN S.E. FORGI
IScan: IType:IDGEO
IIAmpitude:<20 I (( Ax Loc:
Circ Loc:360 INTERM( I ILength: I II
Page 6 of 26
.I
FROM WLD(
BY FLANGE EACH ID EACH ID
NG GEOM.I
. I , I . 4
. 4 1
.4 4
TABLE S-II NORTHERN STATES POWER COMPANY MONTICELLO Unit I Examination comparison summary
1-------------I------------------------------------------------------------------------------------------------SUB-ITEMI SYSTEM ICLASS I ISO IMETHI ITEM I REPORT PREVIOUS RESULTS I CURRENT RESULTS I LIMITATIONS
.----- I----1--------I- I------ I----I ------- ---------- I--------------------I------- ----- I------- ----------1B5.10 IRECIRC INLET E I I 11SI-13D JUT4 RREFR-2 187-363 I Results:GEO | ResuLts:NONE 12.5" SCAN LENGTH -- NOZZLE GEOj
I I I I I I Scan:2 I I I I I I I .I Type:ID GEO
I I I I I I I IJAmplitude:30 I I I I I I IAx Loc:
I | | I | Circ Loc:360 INTERM I I I I I I Length:
165.10 IRECIRC INLET E I I IISI-13D jUT4 IRREFR-2 187-363 1 Results:GEO Resutts:NONE INONE I I I I I I I IScan:3 I I I I I I I I I I Type:ID GEO I I I I I I I I Amplitude:<20 I I I I I I I IAx Loc:
I|I I I I Circ Loc:360 INTERMI I I I I I I I Length: I jB5.10 fRECIRC INLEt E I IISI-13D IUT4 IRREFR-2 187-363 I Results:GEO Resutts:NONE fNONE I I I I I I I IScan:4 II I I I I I I I I Type:ID GEO
I I I I I I . I Amplitude:<20 I I I I I I I IAx Loc:
II I I I I |I Circ Loc:360 INTERMI I I I I I I ILength: I B5.10 RECIRC INLET E I ISI-13D jUT4 IRREFR-2 187-363 I Resutts:GEO ResuLts:NONE jNONE I I I I I I I IScan:3s I I I I I I I I I IjType:ID GEO I I I I I I I I AmpLitude:<20 I I I I I I I IAx Loc:
I I I I I Circ Loc:360 INTERMI I I I I I I I Length: I jB5.10 IRECIRC INLET E | 1 JISI-13D JUT4 IRREFR-2 187-363 Resutts:GEO ResuLts:NONE jNONE I I I I I I I IScan:4s I I I I I I I I I Type:ID GEO I I I I I I I I I AmpLitude:<20 I I I I I I I I IAx Loc: I
I|I I I | I Circ Loc:360 INTERMI I I I I I I I jLength: I
Page 7 of 26
.1 a
NORTHERN STATES POWER COMPANY MONTICELLO Unit I
------------------------------------------------------------ISUB-ITEMI SYSTEM |CLASS I ISO
. ...-- ....- ....- - .. -.1-- ---- I-------1B5.10 IRECIRC INLET E | I 1ISI-13D 85.50 CRD SCRAM HEADER A I I |ISI-24A 1B5.50 |CRD SCRAM HEADER A | I (ISI-24A
I I I I I I I I I I I I I I I I 1 I I I I I I I 185.50 CRD SCRAM HEADER A I I |ISI-24A B5.50 IHPCI STEAM I I jISI-7 (B5.50 IHPCI STEAM I I |ISI-7 I I I I
B55 |I SEMI ISI7 I I I I
I I I I
I55 |I SEMI ISI7 I I I I I I I I 1 I I I 1 I I I I I I I I I I I I I I I I I I I 1 1 I I I I I I I I I I
II I I
-
IMETHI ITEM
-I---- I-------------IVT1 |RREFR-2
PT ICDAF-43
IUT4 |CDAF-43
I I I I I I I I I I
I I jVT1 jCDAF-43
|PT PSAF-2B IUT4 IPSAF-28
I I
I I I I I I I I IUT4 JPSAF-2B
I I I I
I I I I A I I
I I |UT4 |PSAF-2B I I
I IA I I I I I I I I I I I I
REPOR
187-349 187-392 187-400 1
187-393 187-255 187-317
87-317
187-317
I8 -31
. I
TABLE B-.L
Examination comparison summary
T PREVIOUS RESULTS CURRENT RESULTS LIMITATIONS -- -------- ---------- -1------------I----------------- I I Results:NONE I Results:NAD INONE Results:N/A | Resutts:NAD NONE
| Resutts:GEO j Results:NONE INONE I Scan:2 I I Type: ID GEO I AmpLitude:50 I Ax Loc:
I Circ Loc: I Length: | ResuLts:N/A ResuLts:NAD INONE | Results:NONE f Results:NAD NONE | Results:GEO | ResuLts:GEO INONE Scan: I scan: 1
| Type:OD GEO | Type:GEO I Amplitude:35 I Amptitude:100 | Ax Loc: | Ax Loc: I Circ Loc: I Circ Loc:360 INT. Length: Length: I Results:GEO I ResuLts:GEO |NONE Scan:2 | Scan: 2 Type:ID/OD GEO Type:GEO I Amplitude:35 | Amplitude:100 I Ax Loc: I Ax Loc: Circ Loc: | Circ Loc:360 INT. Length: | Length: I I Results:GEO I Results:NONE |NONE I Scan:3 II I Type:ID/OD GEO Amplitude:35 | I Ax Loc: Circ Loc:
I Length: I | Results:GEO | Results:NONE jNONE Scan:4 II I Type:ID/OD GEO I Amplitude:35 Ax Loc:
I Circ Loc: Length:
Page 8 of 26
.3 1 1
TABLE 8-II NORTHERN STATES POWER COMPANY MONTICELLO Unit I Examination Comparison summary
SUB -ITEMI SYSTEM |CLASS | ISO IMETHI ITEM 1 REPORT I PREVIOUS RESULTS CURRENT RESULTS LIMITATIONS -------. I . ------------------- I ------ I ---------- I----I --------------- I ---------- I --------------------- I-------------------- I-------------------------
185.50 JHPCI STEAM I I |ISI-7 IUT4 IPSAF-28 187-317 1 Results:GEO Results:NONE NONE | | I I I I I IScan:4s I II I I I I I I Type:ID/OD GEO I I I I I I I IAmplitude:35
I I I I I 1 IAx Loc: II I I I I. I ICirc Loc: 1 I I I I I I I I Length: j85.50 IHPCI STEAM I I |ISI-7 |UT4 IPSAF-2B 187-317 I Resutts:GEO f Results:NONE NONE I I I I I 1 I IScan:1s I
I I I I I IType:O GEO I I I I I I I I IAmplitude:30 I
I I I I I I IAx Loc: I I I I I I I ICirc Loc: I
I I I I I I I Length: I B5.50 |HPCI STEAM I I JISI-7 IUT4 (PSAF-2B 187-317 1 Results:GEO ResuLts:NONE NONE I I I I I I I I Scan:2S I
I I I I I IType:OD GEO I I I I I I I IAmpLitude:30 I I I I I I I IAx Loc: I I I I I I I I ICirc Loc: I I I I I I I I I ILength: I 1B5.50 (HPCI STEAM I I ISI-7 IUT4 |PSAF-2B 187-317 | Resutts:GEO | Results:NONE NONE I I I I I I I IScan:3s I I
I I I I I I I Type:ID/OD GEO I I I I I I I I Amplitude:35 S I I I I I I IAx Loc: I I I I I 1 I I circ ioc: I I I I I I I I ILength: I 185.50 jHPCI STEAM I I ISI-7 IVT1 IPSAF-2B 187-253 1 Results:NONE Results:NA0 INONE 1B5.50 JHPCI STEAM I I IISI-7 IPT IPSAF-2C 187-254 1 ResuLts:IND ResuLts:NONE NONE
Type:ARC STRIKE I I I I I I I IAx Loc: I I I I I I - I I Circ Loc:7:oo I I I I I I I I ILength: I 85.50 IHPCI STEAM I 1ISI-7 IUT4 JPSAF-2C 187-318 I ResuLts:GEO Resutts:GEO INONE
Scan:1 IScan: 1 Type:ID GEO |Type:ID GEO AmpLitude:100 I Amptitude:100
I I I I I I I I Ax Loc: Ax Loc:1.2" IICirc Loc: I Circ Loc:3"
1 I I I I I I I Length: I Length:3.5"1
Page 9 of 26
. I
a*
NORTHERN STATES POWER COMPANY MONTICELLO Unit I Examination Comparison summary
-----------------------------------------------------------------------------------------ISUB-ITEMI SYSTEM ICLASS I ISO IMETHI ITEM I REPORT PREVIOUS RESULTS I CURRENT RESULTS LIMITATIONS I --------------------I--I-------l---------------------- --------------------I--------------I --------------------|B5.50 JHPCI STEAM I I JISI-7 IUT4 |PSAF-2C 187-318 1 Resuits:NONE Resutts:GEO NONE I I I I I I I I I I I IGEO I I I I Ampitude:100 IAx Loc:145
I I I I ILoc:3 I I I I Length: 1B5.50 |HPCI STEAM I I |ISI-7 |UT4 JPSAF-2C 187-318 1 Resutts:NONE Resutts:GEO NONE I I I I1 I I I I I I GEO I I I I I IAmptitude:99 I I I I Loc:1.05 I I Circ Loc:9.5
I I I I ILength:2.75 |B5.50 |HPCI STEAM 1 I IISI-7 JUT4 |PSAF-2C 187-318 1 Results:NONE Resutts:GEO INONE I I I I I I I I I I I IGEO I I I I I IAmpitude:85 I I I I I IL c:1.2 I I I I I ICirc Loc:9.5
I I I Length:2.75 B5.50 |HPCI STEAM | I|ISI-7 |UT4 |PSAF-2C 187-318 1 Resutts:NONE Results:GEO NONE I I I I II S I I I I IType:IDGEO I I I I I IAmptitude:11 S I I I I ILoc:.9
ICic Loc:16.5 I I I I Length:4 1B5.50 |HPCI STEAM I I |ISI-7 JUT4 JPSAF-2C 187-318 1 Results:NONE Results:GEO INONE I I I I I I I I I I I IGEO
I I I I I II I Amptitude:100 I IAx Loc:1.2
I I IC c Loc:16.5" I I I I Length:4
.. _.........._.........I..........1--__ ___-I-__-Page_10 1of_26 Paire10oof32
NORTHERN STATES POWER COMPANY TABLE S-II I MONTICELLO Unit I Examination Comparison Summary --------------------------------------------------------------------------------------------------------------------------I SUB-ITEMI SYSTEM jCLASS | ISO IMETHI ITEM I REPORT I PREVIOUS RESULTS | CURRENT RESULTS | LIMITATIONS
1--------1--------------------1------I---------- I----I-------------- I----------I -- - - ------------- ----- --------------- I ---------------------- I--- I 185.50 |HPCI STEAM | I |ISI-7 1UT4 |PSAF-2C 187-318 Results:NONE Resutts:GEO INONE I I I I I I I IScan: 1 I
I I I I I I I I IType:ID GEO I I I 1 1. I I I Amptitude:110 I
| | I I I I I I IAx Loc:1.0" I I I I I I I Circ Loc:22.25" | | |I| I I I I I I Length:4.25" | |B5.50 |HPCI STEAM I I ISI-7 IUT4 JPSAF-2C 187-318 | Results:GEO Resutts:GEO INONE I I I I I I I Iscan:1 IScan: 1 I
| Type:OD GEO Type:ID GEO I Amplitude:100 Amplitude:110 I | Ax Loc: Ax Loc:1.0" | IICirc Loc: Circ Loc:22.25"1 | Length: Length:4.25" I
B5.50 IHPCI STEAM I I IISI-7 IUT4 IPSAF-2C 187-318 I Results:GEO Results:NONE INONE I I I I I I IScan:2
I I I I I I I ITyPe:OD GEO I I I I I I IAmptitude:35 I
I I I I I I IAx Loc: I I I I I I I I ICirc Loc: I I I I I I I I I ILength: I I 1B5.50 |HPCI STEAM I I |ISI-7 jUT4 IPSAF-2C 187-318 I Results:GEO Results:NONE INONE I I I I I I I IScan:3 II
I I I I I I IType:OD GEO I I I I I I I I IAmptitude:25 I 1 I I I I I I IAx Loc: I I I I I I I I 1Circ Loc: I
I I I I I I ILength: II 1B5.50 jHPCI STEAM I I |ISI-7 IUT4 |PSAF-2C 187-318 I Resutts:GEO I ResuLts:NONE NONE I I I I I I I I Scan:4 I
I I I I I I IType:ID/OD GEO I I I I I I I I AmpLitude:25 I I I I I I I I IAx Loc: I I I I I I I I Circ Loc: I I I I I I I I Length: I I I 1 _ _ 1 .Pag__ I f 6 I
Page 11 of 26
I . I #
. .. . .. TABLE S-II NORTHERN STATES POWER COMPANY
| MONTICELLO Unit I Examination Comparison summary I--------------------------------------------------------------------------------------------------------------------------------------------------------I ISUB-ITEMI SYSTEM |CLASS I ISO IMETHI ITEM | REPORT I PREVIOUS RESULTS CURRENT RESULTS I LIMITATIONS
I-----I-------------------- ---- I ------ I I ------------ I----- ----------------- --1-------------I------------------------------I 185.50 IHPCI STEAM II ISI-7 IUT4 |PSAF-2C 187-318 | Results:GEO j Resutts:NONE NONE
I I I I I I I I Scan:1S I I I 1 I I I I jType:OD GEO |
S| | | I I I AmpLitude:30 | || | I | | |Ax Loc: I
I I I I I Circ Loc:9:00-12:00| I | | I I I Length: I
B5.50 IHPCI STEAM I 1ISI-7 UT4 IPSAF-2C 187-318 | ResuLts:GEO Resutts:NONE NONE
I I I I I I I Scan:2S I I I I I I I IType:O GEO |
SI I I I I I I Amptitude:35 | S I I I I I I IAx Loc: I I I I I I I I I Circ Loc:
I I I I II I Length: II 185.50 IHPCI STEAM' I ISI-7 IUT4 jPSAF-2C 187-318 1 Results:GEO Results:NONE INONE
1 I I I I I Scan:3s I I I I I I I I IType:O GEO I I I I I I I I 1Amptitude:35 | S I I I I I IAx Loc: I I I I I I I I I Circ Loc: I I I I I I I I Length: I 185.50 IHPCI STEAM I I 1ISI-7 IUT4 IPSAF-2C 187-318 1 Resutts:GEO Resutts:NONE NONE I I I I I I I IScan:4s I I I I I I I I IType:OD GEO I I I I I I I IAmplitude:30 I I I I I I I I I^xLoc: I I I I I I I I ICirc Loc: I I I I I I I I ILength: I 1B5.50 JHPCI STEAM I I IISI-7 IVT1 JPSAF-2C 187-252 1 ResuLts:NONE Results:NAD NONE 85.50 IRHR LOOP B j I jISI-11B IUT4 IRHBFR-6 187-385 | Resutts:GEO Results:GEO INONE I I I I I I I IScan:1 Scan: 1 I
Type:ID/OD GEO Type:ID GEO Amplitude:<20 Amptitude:20 Ax Loc: Ax Loc:.8 Circ Loc:360 INTERM Circ Loc:360
I I I I I I Length: I Length:360 INTMIT I agI _ I I I I fI I 26
Page 12 of 26
TABLE S-II NORTHERN STATES POWER COMPANY MONTICELLO Unit I Examination Comparison summary
----------------------------------------------------------------------------------------------------------------------SUB-ITEMI SYSTEM ICLASS I ISO IMETHI ITEM | REPORT I PREVIOUS RESULTS j CURRENT RESULTS LIMITATIONS ---- -------------------- I------I------- I---I---------------I------I------------ ---------- -----------------|B5.50 jRHR LOOP B I I |ISI-11B IUT4 IRHBFR-6 187-385 1 ResuLts:GEO Resutts:NONE INONE
I I I I I I IScan:2 II I I I f Type:ID/OD GEO
I I I I I I I Amplitude:<20 I I I I 1 I I IAx Loc:
| I I I| I I j Cire Loc:360 INTERMI | I I 1 I I Length: I
|85.50 IRHR LOOP B | I |ISI-11B IUT4 IRHBFR-6 187-385 1 Results:GEO I Results:NONE NONE I I I I I I I IScan:3 I I
I I I I I IType:ID/OD GEO I I I I I I I I Amplitude:<20 I I I I I I I I IAx L o: I
I| | II Circ Loc:360 INTERMI I I I I I I I Length: I I 185.50 IRHR LOOP B I I |ISI-11B IUT4 IRHBFR-6 187-385 j ResuLts:GEO I Resutts:NONE [NONE I I I I I I IScan:4 I I I I|I I I I| | Type:ID/0D GEO
II I Amplitude:<20 I I I I I I I IAx Loc:
I I I I| I | Circ Loc:360 INTERMJ I I I I I I I Length: I I 1B5.50 IRHR LOOP B | I |ISI-11B JUT4 IRHBFR-6 187-385 I Results:GEO I ResuLts:NONE NONE I I I I I I I IScan:3s I I I I I I I I I I Type:ID/OD GEO
III I I IAmplitude:<20 I I I I I I I IAx Loc: S I I I| I Circ Loc:360 INTERMI I I I I I I I ILength: I 185.50 IRHR LOOP B j I ISI-11B JUT4 IRHBFR-6 187-385 I Results:GEO I ResuLts:NONE INONE I I I I I I I IScan:4s I I I I I I I I I I Type:ID/OD GEO I I I I I 1 I I Amptitude:<20 I I I I I I I I IAx Loc: I
I I| I I II Circ Loc:360 INTERMI | I I I I I II I Length: I 1 III IIII I I I I I
Page 13 of 26
I . I f . I
I I
NORTHERN STATES POWER COMPANY MONTICELLO Unit I
I -------------------ISUB-ITEMI SYSTEM
I -------- I------------1B5.50 IRHR LOOP B 1B6.10 REACTOR VESSEL B6.10 IREACTOR VESSEL
jB6.10 REACTOR VESSEL
|B6.10 REACTOR VESSEL
jB6.180 IRECIRC PUMP A B6.200 IRECIRC PUMP A 1B6.50 IREACTOR VESSEL 186.50 |REACTOR VESSEL 1B7.50 |MAIN STEAM D
|B7.70 (FEEDWATER B
I |I
I I I I I I 1B7.70 IFEEDWATER B 187.70 (HPCI STEAM 1B7.70 |MAIN STEAM B 167.70 |MAIN STEAM B 1B7.70 IRCIC STEAM
I I I I 1 I |B7.70 jRCIC STEAM 1B7.70 (RECIRC DRAIN B 187.70 IRECIRC DRAIN B 1B7.70 IRECIRC LOOP B 1B7.70 IRECIRC LOOP B 1B7.70 IRHR LOOP A
1B7.70 |RHR LOOP A I
CLASS ISO IMETHI ITEM REPORT I PREVIOUS RESULTS
I .--.-. I----------I----I------------I--------I------I I IISI-11B jVT1 (RHBFR-6 187-367 | ResuLts:NONE
I FIGURE 3 |MT |NUTS 1-36 187-244 1 Resutts:NONE I IFIGURE 3 |VT1 |NUTS 1-36 187-242 | Results:NONE I FIGURE 3 IMT INUTS 37-64 187-243 | Resutts:NONE I FIGURE 3 |VT1 |NUTS 37-64 187-239 1 ResuLts:NONE I JISI-13A |UTO |FLG BOLT 6-10 187-141 | Resutts:NONE I IISI-13A JVT1 JFLG BOLT 6-10 187-123 1 Resutts:NONE
I I FIGURE 3 |VT1 WASHERS 1-36 PR187-241 | Results:NONE
| I IFIGURE 3 |VT1 IWASHRS 37-64 PR 87-240 I Results:NONE I I IISI-4 IVT1 BOLTS @ MSDJ-23187-160 I Resutts:NONE I I ISI-5B |VT1 FW-98-1 187-287 | Results:NONE
I I JII5 VIFW9- 18-8R IRstsNN I I I I I I I I I I I I I I I I I I I I |ISI-5B |VT1 |FW-981 187-287R | ResuLts:NONE | I JISI-7 |VT1 IMO-2034 187-157 I Results:NONE | I |ISI-2 IVT1 |AO280B 187-158 | ResuLts:NONE 1 I |ISI-2 |VT1 |A02-86B 187-042 | ResuLts:NONE | [ IISI-12 |VT1 IM0-2075 187-156 1 Resutts:NONE
I I I I I I I I I I I I I I I I I I | I|ISI-12 VT1 [M0-2075 187-156R Results:NONE I I|ISI-26 (VT1 |XR-6-2 |87-119 | Results:NONE I IISI-26 |VT1 |XR-7-2 j87-120 IResults:NONE I |ISI-13B IVT1 1MO2-43B 187-323 I Results:NONE I I. ISI-13B IVT1 |MO2-53B |87-324 | ResuLts:NONE I I 1ISI-11A |VT1 IM0-2030 187-159 | Results:NONE
I I I I I* I I I I I I I | I |ISI-11A |VT1 |MO-2030 187-159R | Results:NONE I I I I I I
TABLE S-II
Examination Comparison summary
Page 14 of 26
CURRENT RESULTS LIMITATIONS
N------------I ----------------Results:NAD INONE Results:NAD INONE
I Results:NAD MINOR ISOLATED PITTING
Results:NAD INONE
Results:NAD IMINOR ISOLATED PITTING
Results:NAD NONE
Results:NAD NONE Results:NAD IMINOR ISOLATED PITTING
I Results:NAD MINOR ISOLATED PITTING
| Results:NAD NONE Results:IND ISEE REPORT 87-287R FOR REPAIR
Type:BLT RUSTED
Ax Loc:
C circ Loc: Length: Resutts:NAD NONE
| ResuLts:NAD INONE
Results:NAD INONE
I Results:NAD NONE
I Results:IND SEE REPORT 87-156R FOR REPAIR
| Type:BLT RUSTED
Ax Loc:
Circ Loc:
I Length: I Results:NAD INONE Resutts:NAD |NONE Resutts:NAD INONE Results:NAD INONE ResuLts:NAD |NONE Results:IND |SEE REPORT 87-159R FOR REPAIR
| Type:BLT RUSTED Ax Loc:N/A
I Circ Loc:N/A | Length:N/A Resutts:NAD INONE
It 4
NORTHERN STATES POWER COMPANY MONTICELLO Unit I Examination Comparison Summary
---------------------------------------------------------------------------------------------------SUB-ITEMI SYSTEM ICLASS I ISO jMETHJ ITEM I REPORT PREVIOUS RESULTS CURRENT RESULTS LIMITATIONS -------- I--------------I ------ I------ I------------- I-------------------------- I----------------------
1B7.70 |RHR LOOP A I JISI-11A jVT1 (POS-2028 187-285 1 Results:NONE Resutts:NAD NONE 1B7.70 |RHR LOOP C I |ISI-11C |VT1 |POS-2018 187-286 1 Resutts:NONE Results:NAD INONE 1B7.70 IRHR LOOP E I JISI-11E |VT1 IMO-4085B 187-121 Resutts:NONE Resutts:NAD INONE B7.70 |STANDBY LIQUID CONTRI I |ISI-22 IVT1 |XP-7 187-133 1 Resuits:NONE Results:IND IWELDED BONNET I I I I I I I I I I I I
ICircLoc: I SI I I ILength: I 1B9.11 |CORE SPRAY A | I IISI-6A |MT ICSAJ-19 187-343 1 Resutts:NONE Results:NAD PAINTED SURFACE 1B9.11 ICORE SPRAY A I I |ISI-6A (UT4 ICSAJ-19 187-390 1 Resutts:GEO Resutts:GEO NO SCAN 1 PENERTATION CONFIG.I I I I I I I I I I I Type:IDGEO IAmpitude:25 Ampitude:40
Ax Loc: Ax Loc:.96 ICirc Loc:360 INTERMI Circ Loc:O I ILength: Length:360 INTMIT 1B9.11 ICORE SPRAY A | I IISI-6A IUT4 (CSAJ-19 187-390 Resutts:NONE Results:GEO INONE I I I I I I
I I I GEO I I I I I IAmpitude:35 I I I I I IAx Loc:BUTTED I I I I I ILoc:O I I I I I ILength:360 INTMIT 1B9.11 CORE SPRAY A I I ISI-6A IVT1 ICSAJ-19 187-341 1 Resutts:NONE ResuLts:NAD INONE B9.11 CORE SPRAY A | I IISI-6A |MT ICSAJR-10 187-342 1 Resuts:NONE Resutts:NAD INONE 1B9.11 CORE SPRAY A I jISI-6A JUT4 ICSAJR-10 187-391 1 Results:NONE Results:GEO NONE
cI I I I I I I I I GEO I I I I I IAmplitude:60 I I I I I ILoc:.55 I I I ILoc:O
I I I I ILength:360 |B9.11 ICORE SPRAY A I I |ISI-6A jUT4 ICSAJR-10 187-391 1 Results:NONE Results:GEO NONE I I I I I I
I I I I IGEO I I I IAmpitude:65 I I I I I ILoc:1.45 I I I I I ILoc:O I I I I Length:360
Page 15 of 26
I I I v . .
Is p t
TABLE S-II NORTHERN STATES POWER COMPANY
| MONTICELLO Unit I Examination Comparison summary
SUB-ITEMI SYSTEM ICLASS I ISO IMETHI ITEM I REPORT I PREVIOUS RESULTS I CURRENT RESULTS LIMITATIONS I..... - 1--------------------I .------I---------- .I----I---------------1-------- ---------------------------------------- I----------------------- -|89.11 CORE SPRAY A I IISI-6A |UT4 ICSAJR-10 187-391 1 Results:NONE | Resutts:GEO |NONE
I I I I I I I Scan: 2 | 1 I I I I I I I Type:ID GEO |
I I I I I . I I IAmplitude:80 | | | 1 1 I I I IAx Loc:.5 |1 I I I I I I I Circ Loc:O I
I I I I I I I jLength:360 | (89.11 |CORE SPRAY A | I fISI-6A |UT4 CSAJR-10 187-391 1 Results:NONE | Results:GEO INONE I I I I I I I I I Scan: 2
I I I I I I I I TYpe:OD GEO I 1 I I I I I I I Amplitude:80 I I I I I I I 1Ax Loc:1.4 I I I I I I I I I Circ Loc:O I I I I I I I I ItLength:360 I 1B9.11 CORE SPRAY A I IISI-6A JVT1 ICSAJR-10 j87-340 | Results:NONE ResuLts:NAD NONE 1B9.11 JCRD SCRAM HEADER B I |ISI-24B |MT ICDBJ-14 187-034 1 ResuLts:NONE Resutts:NAD IPAINTED SURFACE JB9.11 ICRD SCRAM HEADER 8 1 JISI-24B IUT4 ICDBJ-14 187-039 | Results:NONE Results:NAD NONE 1B9.11 JCRD SCRAM HEADER B I IISI-248 |VT1 ICDBJ-14 187-035 | Results:NONE Results:NAD NONE 1B9.11 |CRD SCRAM HEADER B I I jISI-24B JUT4 ICDBJ-40 j87-041 1 Results:GEO Results:NONE IS-2 LMTD BY TEE INTRODOS I I I I I I I I Scan:2 I I I I I I I 1 Type:ID GEO I I I I I I I I AmpLitude:35 I I I I I I I IAx Loc:
I I I I I I I Circ Loc: I I I I I I I I I Length: I 1B9.11 CRD SCRAM HEADER B | I JISI-248 jUT4 ICDBJ-40 187-041 | Results:NONE | Results:GEO INONE
I . I I I I 1 IScan:5 I I I I I I I I I IType:OD GEOM. I I I I I I I I I IAmplitude:50 I I I I I I I I I IAx Loc: I I I I I I I I I ICirc Loc: 0" To 13"
I I Length:13" I jB9.11 CRD SCRAM HEADER B I IISI-24B |UT4 ICDBJ-40 187-041 | Results:NONE Resutts:GEO INONE I I I I I I I I IScan:6 I
I I I I I I I IType:OD GEOM. I I I I I I I I I IAmptitude:40 I
I I I I I I I IAx Loc: I I |ICirc Loc: 0' TO 13"1
I I I I I I I I ILength:13" I
Page 16 of 26
I TABLE 8-II | NORTHERN STATES POWER COMPANY MONTICELLO Unit I Examination Compa 'ison Summary -----------------------------------------------------------------------------------------------------------------------
ISUs-ITEMI SYSTEM jCLASS I ISO IMETHI ITEM REPORT I PREVIOUS RESULTS CURRENT RESULTS LIMITATIONS I--------1-------------------- -----. I ------ I----I --------- I------ I --------- -- ----------- I-----------------------------I 1B9.11 ICRD SCRAM HEADER B I |ISI-24B (VT1 ICDBJ-40 87-038 | Results:NONE Results:NAD INONE 89.11 ICRD SCRAM HEADER B I JISI-24B jPT ICDBJ-43 187-036 I Results:NONE Resutts:NAD LONG SEAM PAINTED |B9.11 ICRD SCRAM HEADER B I IISI-24B |UT4 ICDBJ-43 187-040 1 Resutts:GEO Results:GEO S-1 LMTD , ELL INTRODOS, -4"
III I I I I Scan:2 Scan:2 I I I I I 1 I IType:OD GEO Type:OD GEOM.
j Amplitude:50 AmpLitude:20 I I I I I I I Ax Loc: Ax Loc:+1.0"
( Circ Loc: Circ Loc: 0"; 3711 ILength: Length:9"
1B9.11 CRD SCRAM HEADER B I IISI-248 |UT4 ICDBJ-43 187-040 | ResuLts:NONE Resutts:GEO |NONE 1 I I I I I I I Scan:2 I
| | | | I || 1 I Type:ID GEOM. I I I I I I I I Amptitude:<20 |
| | I | | 1 I IAx Loc:+0.6" | | | I I I I I ICirc Loc: 0"; 22"11
I I I I |Length:360 Int. |B9.11 |CRD SCRAM HEADER B I I 1ISI-248 |UT4 ICDBJ-43 187-040 1 Resutts:NONE | ResuLts:GEO INONE
I I I I I I I IScan:5 I I I I I I I I I I Type:ID GEOM. I I I I I I I I I Amplitude:<20 I I I I I I I I IAx Loc: I I I I I I I I ICirc Loc:71 TO 8"uI I I I I I I I I I tLength:1n II B9.11 |CRD SCRAM HEADER B I IJISI-24B IVT1 ICDBJ-43 187-037 | ResuLts:NONE I Results:NAD INONE 189.11 JCRD SCRAM HEADER B [ 1 IISI-24B IUT4 ICDBJ-46 187-408 | Resutts:GEO Results:GEO INONE
Scan:1 I Scan: 1 1 Type:ID GEO lType:ID GEO | Amplitude:25 | Amptitude:25 | Ax Loc: lAx Loc:1.05 Circ Loc: Circ Loc:9:00 Length: Length:360 INTMIT
1B9.11 CRD SCRAM HEADER B 1 ISI-248 |UT4 ICDBJ-46 187-408 | Results:NONE ResuLts:GEO NONE I I I I I 1I I I Scan: 2 I I I I I I I I IType:ID GEO I I I I I I I I I Amplitude:35
I I I I I I I IAx Loc:1.05 I I I I I I I I ICirc Loc:9:00
I Length:360 INTMIT I I _I _ I__...____JJ___ I 1II . I
Page 17 of 26
.4 3
$ I
3 C C
NORTHERN STATES POWER COMP I MONTICELLO Unit I 1---------------------------------------------SUB-ITEMI SYSTEM |CLASS ISO
I--------I.--------------------1 -1--------189.11 |CRD SCRAM HEADER B | I |ISI-24B B9.11 IFEEDWATER A I |ISI-5A 189.11 IFEEDWATER A | I jISI-5A
JB9.11 IFEEDWATER A I I |ISI-5A |89.11 IFEEDWATER A I I JISI-5A
1B9.11 IFEEDWATER A | I |ISI-5A
I I I I
1I I I | | I I
I I I I I I I I 81 IFEDATRAI I III5 I I I I
1I I I
I I I I I I I
I I I I I I I |B9.11 IFEEDWATER A | I |ISI-SA
II I I
B9 1 |FEI AE I IS 5A I I I I I I I I I I I I
I | I I | I I I
|I I I
ANY
.---.-..-..----------..-----------..------.-------.
IMETHI ITEM I REPORT j PREVIOUS RESULTS 1 ----..............---------..-.-----------------|VT1 ICDBJ-46 187-410 I Results:NONE MT IFWAJ-18 187-208 J Resutts:NONE IUT4 IFWAJ-18 187-207 | Resutts:NONE jVT1 (FWAJ-18 187-370 Results:NONE
|MT |FWP-A-5 187-277 | Resutts:NONE JUT4 IFWP-A-5 187-308 | Results:GEO I I I IScan:1
I | Type:ID GEO I I I I Amnpl itude:45 I I I IAx Loc: 1 I I I Circ Loc:
I| | Length: |UT4 (FWP-A-5 187-308 | Resutts:NONE I I I I I I I I I I I I I I I. I I I I I
IUT4 IFWP-A-5 187-308 1 Results:NONE
I I I I I I I I I I I I I I I I I I I I I I I I |UT4 JFWP-A-5 187-308 1 Results:GEO
I I I I Scan:2 Type:ID GEO Amplitude:60 Ax Loc: Circ Loc: Length:
IUT4 |FWP-A-5 187-308 1 Results:NONE
I I I I I I I I I I I I I I I I I I I 1I I I I I
TABLE S-II
Examination Comparison summary ...
-. -- --- -.-.. ...................- -- --. I
| CURRENT RESULTS | LIMITATIONS
-------------------- I------------------------------I Results:NAD jNONE
| Results:NAD INONE I Results:NAD |NONE Results:NAD jNONE Results:NAD |NONE Resutts:GEO jNONE Scan: 1
I Type:GEO Amplitude:98 I
I Ax Loc:.755 | Circ Loc:20 I Length:360 INTMIT | | Results:GEO NONE
Scan: 1
I Type:GEO Amptitude:55 Ax Loc:1.85
Circ Loc:20
| Length:360 INTMIT Results:GEO jNONE
I Scan: 1 Type:GEO
I Amplitude:75 I I Ax Loc:3.07
Circ Loc:20
I Length:360 INTMIT | Results:GEO INONE
I Scan: 2
| Type:GEO | Amptitude:65 I Ax Loc:1.70 Circ Loc:17
Length:360 INTMIT
| ResuLts:GEO INONE
Scan: 2
I Type:GEO I AmpLitude:75 | Ax Loc:1.075 Circ Loc:17 Length:360 INTMIT I
Page 18 of 26
I , I I I .
,I 4 1
NORTHERN STA MONTICELLO U
ISUB-ITEMI SYSTEM
I -------- ---------89.11 IFEEDWATER A JB9.11 |MAIN STEAM B
IB9.11 |MAIN STEAM B
B9.11 jMAIN STEAM B 189.11 |MAIN STEAM C
|B9.11 |MAIN STEAM C
I I I I
B9.11 B9.11 89.11
1B9.11 89.11 B9.11
|B9.11
T n
MAIN STEAM C MAIN STEAM C MAIN STEAM C MAIN STEAM C RECIRC LOOP A IRECIRC LOOP A
IRECIRC LOOP A
1B9.11 jRECIRC LOOP A I I I I I I I I | 1I I I | |_ _ I_ _ _ _ _
TABLE S-II ES POWER COMPANY it I Examination comparison summary ----- ......................................................................................I
1CLASS | ISO METHj ITEM REPORT PREVIOUS RESULTS CURRENT RESULTS LIMITATIONS . ---------- I----I-.--------------I------I........ ............ I............... I I ISI-5A |VT1 FWP-A-5 187-278 1 Resutts:NONE | ResuLts:NAD NONE .1 I I |ISI-2 IMT IMSBJ-19 187-103 | ResuLts:NONE f Results:NAD jPAINTED SURFACE | I jISI-2 IUT4 IMSBJ-19 87-105 1 Results:NONE Results:NAD IS-1,2 LMTD 360 DEG - CONFIG. I I (ISI-2 |VT1 IMSBJ-19 187-104 | ResuLts:NONE Results:NAD NONE
I I ISI-3 IMT IMSCJ-29 187-090 1 Resutts:NONE f Results:NAD NONE | I jISI-3 JUT4 IMSCJ-29 187-098 | ResuLts:NONE | Results:GEO INONE I I I I I I | Scan:2 I
I I I I I IType:ID GEO. I I I I I I I Amplitude:75 I I 1 I I I IAx Loc:1.25 I I I I I I I Circ Loc:O IN. I
I I I | ILength:360 INT. | I I IISI-3 jVT1 IMSCJ-29 187-091 1 Resutts:NONE Results:NAD INONE I I ISI-3 MT |MSCJ-8 187-378 | Results:NONE Results:NAD |PAINTED SURFACE I I JISI-3 JUT4 JMSCJ-8 187-384 1 Results:NONE Results:NAD INONE I I ISI-3 IVT1 IMSCJ-8 187-379 1 Results:NONE ResuLts:NAD INONE I I ISI-13A PT IRCAJR-4 187-124 | Resutts:NONE Resutts:NAD [NONE I I ISI-13A IUT4 IRCAJR-4 187-137 1 Results:GEO | Results:GEO INONE I I I I I scan:1 I Scan:1 I
| Type:ID/OD GEO Type:OD GEO. I Amptitude:<20 Amplitude:<25
I I I I I Ax Loc: Ax Loc:2.1 I Circ Loc:360 INTERMI Circ Loc:O IN.
I I I I I ILength: Length:360 | I 1ISI-13A |UT4 IRCAJR-4 187-137 | ResuLts:GEO Resutts:GEO INONE
I I I I I Scan:2 Scan:2 I I I I I I I Type:OD GEO Type:OD GEO.
Amptitude:<20 Amptitude:100 I Ax Loc: Ax Loc:2.4 I Circ Loc:360 INTERMI Circ Loc:O IN. Length: Length:360
I I 1ISI-13A IUT4 IRCAJR-4 187-137 1 Results:NONE Results:GEO INONE I I I I I I I Scan:2 I I I I I I I I Type:ID GEO. I I I I I I I AmpLitude:80 I I I I I I I Ax Loc:1.2 I I I I I I I I Circ Loc:O IN. I I I I I I I I Length:360 I 1 I I I I I I
Page 19 of 26
I , I * I k
4t
NORTHERN STATES POWER COMPANY TABLE 8-II MONTICELLO Unit I Examination Comparison summary
-------------------------------------------------------- I------------------------------------ --------------------------- I SUB-ITEMI SYSTEM ICLASS I ISO METHI ITEM REPORT I PREVIOUS RESULTS CURRENT RESULTS LIMITATIONS .-----.I.------------ --. --------- I---I -- ---------- I ---------- I ----- ---- - ------------------- I------------------------------I 869.11 IRECIRC LOOP A I I 1ISI-13A JUT4 JRCAJR-4 187-137 | Results:NONE | Resutts:GEO |NONE
I I I I I I I IScan:5 I I I I I I I I I IType:OD GEO. I
I I I I I I I Amptitude:30 I I I I I I I I I IAx Loc:2.0
|ICirc Loc:O IN. I I I I I I I I I I Length:12 IN. I |B9.11 IRECIRC LOOP A I I IISI-13A IUT4 IRCAJR-4 187-137 | ResuLts:NONE | ResuLts:GEO INONE I I I I I I I I I Scan:6 I I I I I 1 1 I I I Type:ID GEO. I I I I I I I - I I Amptitude:<20 I I I I I I IAx Loc:1.1
I I I I I I I I Circ Loc:O IN. I I I I I | | Length:12 IN.
1B9.11 IRECIRC LOOP A I I |ISI-13A |UT4 |RCAJR-4 187-137 1 Results:NONE I Results:GEO NONE 1 I I I I I I I IScan:6 I I I I I I I I I IType:OD GEO. I I I I I I I I I IAmplitude:25 I I I I I I I I IAx Loc:2.3 I I I I I I I I I I Circ Loc:O IN. I I I I I I I I | Length:12 IN. |B9.11 IRECIRC LOOP A I jISI-13A |UT4 IRCAJR-4 187-137 | Resutts:NONE I Resutts:GEO NONE 1 1 I I I I I I I Scan:9 I I I I I I I I I IType:OD GEO. I I I I I I I I I IAmplitude:20 I I I I I I 1 I I IAx Loc:2.2 I I I I I I I I I Circ Loc:O IN. I I I I I 1 I I I Length:12 IN. 1B9.11 IRECIRC LOOP A I I |ISI-13A |UT4 |RCAJR-4 187-137 | ResuLts:NONE j Results:GEO INONE I I I I I I I I IScan:10 I I I I I I I I I IType:0D GEO. I I I I I I I I I IAmplitude:20 I I I I I I I I I IAX Loc:2.2 I 1 I I I I I I I I Circ Loc:O IN. I
1 1 1 |Length:12 IN.
| I I I I I I I 26I Page 20 of 26
I * I %
TABLE S-II NORTHERN STATES POWER COMPANY
I MONTICELLO Unit I Examination Comparison Summary -------------------------------------------------------------------------------------------------------------------------------------------------------- I SUB-ITEMI SYSTEM ICLASS I ISO IMETHI ITEM REPORT I PREVIOUS RESULTS I CURRENT RESULTS LIMITATIONS
1--------1--------------------I------I----------1---- --------------- 1----------I--------------------I--------------------I------------------------------I 189.11 IRECIRC LOOP A I I ISI-13A IUT4 IRCAJR-4 187-138 | Results:NONE | Resutts:NAD |NONE B9.11 IRECIRC LOOP A I I SI-13A VT1 IRCAJR-4 187-125 1 ResuLts:NONE j Results:NAD |NONE B9.11 IRECIRC LOOP A I I ISI-13A PT JRCAJR-5 187-109 | Results:NONE Results:NAD jNONE 1B9.11 IRECIRC LOOP A I 1ISI-13A 1UT4 JRCAJR-5 87-132 1 Results:GEO Resutts:GEO INO S-2,3S,4S TEE CONFIGURATION I I I I I I I Scan:1 jScan:1 I
Type:ID GEO | Type:ID GEO. Amplitude:<20 | Amplitude:25 Ax Loc: lAx Loc:1.03 Circ Loc:360 INTERMI Circ Loc:O IN. Length: |Length:360
1B9.11 IRECIRC LOOP A I IISI-13A IUT4 IRCAJR-5 187-132 1 Results:NONE I Results:GEO INONE I I I I I I . I Scan:1 I
I I I I I I I I Type:OD GEO. | | |I | |Amptitude:35 I I I I I I I I IAx Loc:2.0 I
I I I I I I I I I Circ Loc:O IN. | | |I | |Length:360 INT.
1B9.11 IRECIRC LOOP A I I IISI-13A IUT4 JRCAJR-5 187-132 1 Results:GEO I Results:NONE NONE I I I I I I I IScan:3 II
| | | | | | I Type:LONG SEAM I I I I I I I I IAmplitude: I | I I I I I I IAx Loc: I I I I I I I I ICirc Loc: I I I I I I I I I Length: 189.11 IRECIRC LOOP A I I JISI-13A IUT4 IRCAJR-5 187-132 | Results:GEO | Results:NONE INONE I I I I I I I IScan:4 II I I I I I I I Type:OD GEO I I I I I I I I IAmptitude:<20 | | | | | | I || 1Ax Loc: I
S| | | | I Circ Loc:LONG SEAM I | |. I I I I I Length: I B9.11 IRECIRC LOOP A I I JISI-13A |UT4 |RCAJR-5 187-132 1 Results:NONE | Resutts:GEO INONE I I I I I I I I IScan:5 I
| | I | I | |Type:ID GEO. I I I I I I I I I Amplitude:25 I | I I I I I I IAx Loc:1.08 | I I I I I I I I I Circ Loc:O IN. |
| | | | | |Length:12 IN. (
I I IoI I I 6I Page 21 of 26
II S
1~ S S
NORTHERN STATES POWER COMPANY TABLE S-II MONTICELLO Unit I Examination comparison summary
1------------------------------------------------------------------------------------------------------------------ISUB-ITEMI SYSTEM ICLASS I ISO IMETHI ITEM REPORT PREVIOUS RESULTS CURRENT RESULTS LIMITATIONS I--------I---------------------------I----------I----I------------I -----------------|B9.11 IRECIRC LOOP A I I 1ISI-13A |UT4 |RCAJR-5 187-132 1 Resutts:NONE Resutts:GEO INONE SI I I IScan:5 I I I III I I I I I I IAmptitude:35 I
I I I Loc:2.38 I I I I I I IN.
I I Length:12N. 1B9.11 IRECIRC LOOP A | I 11SI-13A |UT4 IRCAJR-5 187-132 1 Resutts:NONE Results:GEO NONE I I I I Scan:6 I I I I I I IGEO. I I I I I IAmpLitude:30
SI I IILoc:1.05 I Loc:OIN.
I I I I I ILength:12 N. 1B9.11 fRECIRC LOOP A I I 1ISI-13A jUT4 IRCAJR-5 187-132 I Resutts:NONE Resutts:GEO NONE I I I I I I I I I I I I
I I I I IAmPLitude:35 I I I I I IILoc:2.35 I I I I I I IN. I I I I I IN. |B9.11 IRECIRC LOOP A I I |ISI-13A |VT1 |RCAJR-5 187-106 1 Resutts:NONE Resutts:NAD INONE 189.11 jRHR LOOP B | I JISI-11B jUT4 (RHBJR-13 187-380 1 Results:GEO Resutts:NONE INONE
I I I I IScan:1 I I I I I IType:ID/ODGEO I I I I I IAmplitude:50 I I I I IILoc: I I I I I ICirc Loc:360 INTERMI ILength: I 1B9.11 |RHR LOOP B I ISI-11B JUT4 IRHBJR-13 187-380 1 Results:GEO I Results:GEO INONE
I I I I Iscan:2 IScan:2 I I I I I IGEO I Type:GEOMETRY I
Amptitude:20 I Ampitude:45 I IAx Loc: Ax Loc:1.9 I I II II II ICirc Loc:360 INTERMI Circ Loc:360 INT. ILength: Length:360 INT.
Page 22 of 26
I I I I
I S * *
NORTHERN STATES POWER COMPANY MONTICELLO Unit I
----------------------------------------
TABLE S-II I Examination comparison summary I
ISUB-ITEMI SYSTEM JCLASS I ISO IMETHI ITEM REPORT PREVIOUS RESULTS CURRENT RESULTS I LIMITATIONS
1B9.11 |RHR LOOP B I I |ISI-11B VT1 IRHBJR-13 187-368 1 Resutts:NONE Results:NAD INONE 1B9.11 RHR LOOP B I I 1ISI-11B |UT4 IRHBJR-15 187-381 Resutts:GEO Resutts:GEO NONE I I I I I I IType:ID/OD GEO Type:GEO IAmpitude:75 Ampitude:60 I I I IAx Loc: Ax Loc:1.45
ICirc Loc:360 INTERM Circ Loc:360 ILength: Length:360 INTMIT |B9.11 IRHR LOOP B I 1ISI-11B |VT1 IRHBJR-15 187-369 1 Results:NONE Resutts:NAD NONE |B9.11 IRHR LOOP B I JISI-11B IUT4 IRHBJR-2 187-383 I Results:GEO I Resutts:NONE NO SCAN 2 DUE TO CONFIGURATION S I I I I IScan:1 I I I I GEO
I I I I IAmpLitude:25 I I I I ILoc:
ICirc Loc:360 INTERMI I I I I I I IB9.11 RHR LOOP B I IISI-11B IVT1 IRHBJR-2 187-365 1 Resutts:NONE Results:NAD NONE 1B9.11 |RHR LOOP B I I |ISI-118 |UT4 IRHBJR-3 187-382 1 Resutts:GEO Results:GEO INONE I I Scan:1 IScan:1 I I I I I IType:GEOMETRY IAmpitude:30 Amplitude: 40 IAx Loc: Ax Loc:-1."
I II I ICirc Loc:360 INTERMr' Circ Loc:360 INTER.I I I I IILength: Length: I
|B9.11 |RHR LOOP B | I ISI-118 |UT4 IRHBJR-3 187-382 I Resuits:GEO Results:GEO INONE
I I I I I I IType:O GEO Type:GEOMETRY I
IAmptitude:1 Amplitude: 45 IAx Loc: Ax Loc: 1.0 ICirc Loc:360 INTERMI Circ Loc:360 INTER. ILength: Length: I 89.11 jRHR LOOP B I IISI-11B |VT1 IRHBJR-3 187-366 I Resutts:NONE Resutts:NAD INONE 1B9.11 JRHR LOOP D I JISI-11D IMT IRHDJ-11 187-344 1 Resutts:NONE Resutts:NAD IPAINTED SURFACE 1B9.11 |RHR LOOP D I 1ISI-11D |UT4 IRHDJ-11 187-336 I Results:NONE Resutts:NAD NONE 189.11 JRHR LOOP D I JISI-11D IVT1 IRHDJ-11 187-338 | Results:NONE Resutts:NAD INONE
Page 23 of 26
I cIS * a
NORTHERN STATES POWER COMPANY TBESI IMONTICELLO Unit I Examination comparison summary ------------------------------------------------------------------ ------------- ------------------------------ I---I1* ----
ISUB-ITEM I SYSTEM I CLASS I ISO IMETH I ITEM I REPORT I PREVIOUS RESULTS ICURRENT RESULTS ILIMITATIONS ------ I---------------I---I ------- I----I ----------- I ------- I -------------- ----------------- I---------------------JB9.11 IRHR LOOP D I JISI-11D JMT IRHDJ-12 187-345 1 Results:NONE jResutts:NAD jPAINTED SURFACE 189.11 IRHR LOOP D I 11SI-11D IUT4 IRHDJ-12 187-337 1 Results:NONE IResults:NAD ILIMITED TO 2"- DUE TO ELL CONF.I fB9.11 IRHR LOOP D I I JISI-11D jVT1 IRHDJ-12 187-339 1 Resutts:NONE IResutts:NAD jNONEI JB9.11 IRHR LOOP D I I 11SI-11D IMT IRHDJ-17 187-360 1 Resutts:NONE IResutts:NAD INONEI jB9.11 IRHR LOOP D0 I JISI-11D JUT4 IRHDJ-17 187-361 1 Results:NONE Results:NAD IND SCAN 2 VALVEI 189.11 IRHR LOOP D 1 I I11 lD lVT1 IRHDJ-17 187-356 1 Results:NONE IResults:NAD INONEI JB9.1 JRWCU I I ISI-9 IMT ICWAJR-11 187-200 1 Resutts:NONE Results:NAD INONEI jB9.i1 IRWCU I I IISI-9 fUT4 ICWAJR-11 187-205 1 Resutts:GEO IResuLts:GEO INONEI
I Scan:1 IScan: II I I I I I I Type:ID GEO IType:GEOI I II II II jAmptitude:70 IAmplitude:55 I II I Ax Loc: lAx Loc:.5 I I IICirc Loc:360 INTERMI Circ Loc:OI I II I I ILength: I Length:360 INTER.
fB9.11 IRWCU I I IISI-9 IUT4 ICWAJR-11 187-205 1 Results:GEO I Results:GEO INONE I II I Scan:2 I Scan: 2 1 I I I I I I Tvpe:ID GEO IType:GEOI I I I I I I IAmptitude:60 IAmplitude:60I I II I Ax Loc: lAx Loc:.5 I I I IICirc Loc:360 INTERMj Circ Loc:OI I I IIILength: I Length:360 INTER. I
189.11 IRWCU I I IISI-9 IVT1 ICWAJR-11 187-195 1 ResIJlts:NONE I Resutts:NAD INONE 189.11 IRWCU I I IISI-9 IMT ICWAJR-13A 187-201 1 Results:NONE I Resutts:NAD INONE 189.11 IRWCU I I IISI-9 IUT4 ICWAJR-13A 187-204 1 Results:GEO I Results:GEO INONE
I Scan:1 I Scan: 1 1 I I I I Type:ID GEO IType:GEOI
I I I I I I jAmplitude:65 IAmptitude:60I I II I Ax Loc: jAx Loc:.5
I I IICirc Loc:360 INTERMI Circ Loc:OI I I IjjLength: I Length:360 INTER. I 189.11 IRWCU I I IISI-9 IUT4 ICWAJR-13A 187-204 1 Results:GEO I Results:GEO INONE
I II I Scan:2 I Scan: 2 1 I I I I I I Type:ID GEO ~ Type:GEOI I I I I I I IAmplitude:75 IAmplitude:65I I II I Ax Loc: jAx Loc:.5 I I II IICirc Loc:360 INTERMI Circ Loc:OI I I I IILength: I Length:360 INTER.
Page 24 of 26
NORTHERN STATES POWER COMPANY MONTICELLO Unit I Examination comparison summary
------------------------------------------------------------------------------------------------------------------------SUB-ITEMI SYSTEM ICLASS I ISO IMETHI ITEM REPORT PREVIOUS RESULTS CURRENT RESULTS LIMITATIONS
I-I---- I--------------------1------I----------I----I--------I---------------------jB9.11 jRWCUI I JISI-9 IVT1 ICWAJR-13A 187-194 1 Resutts:NONE Results:NAD INONE JB9.11 IRWCU I I |ISI-9 jMT ICWAJR-5 187-198 Results:NONE Results:NAD NONE 1B9.11 IRWCU I |ISI-9 |UT4 ICWAJR-5 187203 1 ResuttsGEO Resutts:GEO INONE I I I I I I I I I I I IType:GEO I I I I I IAmpitude:60 Amplitude:80 IAx Loc: Ax Loc:.4 I I I I I ICirc Loc:360 INTERMI Circ Loc:O ILength: Length:360 INTER. 189.11 JRWCU I I |ISI-9 JUT4 ICWAJR-5 187-203 1 Results:GEO I Results:GEO INONE
I I I I I I can: 1 I I I I I IType:GEO
I I I I I I IAmplitude:55 IAmplitude:85 I I I IAI I ILoc:.
I I IICirc Loc:360 INTERMI Circ Loc:OI ILength: I Length:360 INTER. 1B9.11 |RWCU I I IISI-9 JUT4 ICWAJR-5 187-203 1 Resutts:GEO Results:GEO ILIM1TED 5:-7: ELL INNER RADIUSI S I I IScan:2 IScan:2 IType:ID GEO Type:GEO
Amplitude:100 Amptitude:85 IAx Loc: Ax Loc:.45
I I IIICirc Loc:360 INTERMI Circ Loc:OI Length: I Length:360 INTER.
1B9.11 JRWCU I I ISI-9 IVT1 ICWAJR-5 187-197 1 Results:NONE I Results:NAD NONE 1B9.21 |STANDBY LIQUID CONTRI I ISI-22 IPT ICPAJR-16 187-108 1 Resutts:NONE I Resutts:NAD INONE 189.21 |STANDBY LIQUID CONTRI I lISI-22 JVT1 ICPAJR-16 187-107 1 Results:NONE Resutts:NAD NONE IB9.32 IRECIRC DRAIN B I IISI-26 PT IRCBJR-11 187-129 1 ResuLts:NONE Resutts:NAD INONE 1B9.32 IRECIRC DRAIN B I 1ISI-26 IVT1 IRCBJR-11 187-126 1 Resutts:NONE Resutts:NAD INONE 1B9.40 |BOTTOM HEAD DRAIN I IISI-21 IMT IHDAJ-10 187-359 1 Results:N/A Resutts:NAD INONE 189.40 |BOTTOM HEAD DRAIN I I IISI-21 jVTI IHDAJ-10 187-354 1 Resutts:N/A ResuLts:NAD INONE 1B9.40 IBOTTOM HEAD DRAIN I IISI-21 IMT IHDAJ-42 187-199 1 Results:N/A Resutts:NAD INONE 1B9.40 |BOTTOM HEAD DRAIN I JISI-21 VT1 IHDAJ-42 187-196 I Resutts:N/A Resuits:NAD INaNE 1B9.40 IBOTTOM HEAD DRAIN I I IISI-21 IMT JHDAJ-9 187-358 1 Resutts:N/A I Resutts:NAO NONE 189.40 |BOTTOM HEAD DRAIN I ISI-21 IVT1 |HDAJ-9 187-353 Results:N/A Resutts:NAD INaNE JB9.40 IHEAD VENT I IISI-15 IMT 44 87-172 Resutts:N/A Resutts:NAD INaNE
Page 25 of 26
. P I I
I. # I
TABLE S-II NORTHERN STATES POWER COMPANY
I MONTICELLO Unit I Examination Comparison Summary --------------------------------------------------------------------------------------------------------------------------I ISUB-ITEMI SYSTEM ICLASS I ISO IMETHI ITEM I REPORT I PREVIOUS RESULTS | CURRENT RESULTS LIMITATIONS I ------ I-------------- I---I ------- I----I ----------- I--------I-------------- ----------------- I----------------------fB9.40 IHEAD VENT | I |ISI-15 JVT1 144 187-171 1 Results:N/A Results:NAD INONE |B9.40 IHEAD VENT I I JISI-15 MT |49 187-174 1 Results:N/A Results:NAD INONE JB9.40 |HEAD VENT I I IISI-15 IVT1 |49 187-173 1 Resutts:N/A Resutts:NAD NONE B9.40 (HEAD VENT I I IISI-15 |MT |55 187-176 1 Resutts:N/A Results:NAD INONE 1B9.40 |HEAD VENT I I IISI-15 jVT1 |55 187-175 1 Results:N/A Resutts:NAD NONE 1B9.40 |HEAD VENT I I |ISI-15 IMT 160 187-178 1 ResuLts:N/A ResuLts:NAD INONE 1B9.40 |HEAD VENT I I |1SI-15 |VT1 160 187-177 1 Resutts:N/A Resutts:NAD INONE B9.40 jHEAD VENT I I IISI-15 IMT 64 187-180 1 Results:N/A Results:NAD NONE 1B9.40 HEAD VENT I I |ISI-15 |VT1 164 187-179 1 Resutts:N/A ResuLts:NAD INONE 1B9.40 IRECIRC DRAIN B I I |ISI-26 |PT 13B 187-131 | ResuLts:N/A Resutts:NAD INONE 189.40 IRECIRC DRAIN B I I JISI-26 jVT1 13B 187-128 1 Results:N/A I Resutts:NAD NONE 1B9.40 IRECIRC DRAIN B I ISI-26 |PT 16B 187-130 I ResuLts:N/A Resutts:NAD INONE 1B9.40 IRECIRC DRAIN B 1 JISI-26 jVT1 16B 187-127 I ResuLts:N/A | Resutts:NAD INONE
S I I . I I I I _I I I I Page 26 of 26
- 1 0, 0 1 1
NORTHERN STATES POWER COMPANY MONTICELLO UNIT I ISOMETRIC SUMMARY CLASS I
TABLE III PAGE 1 OF 5
MAIN STEAM
MAIN STEAM
MAIN STEAM
MAIN STEAM
FEEDWATER
FEEDWATER
CORE SPRAY
CORE SPRAY
NUMBER
ISI-i
ISI-2
ISI-3
ISI-4
ISI-5A
NUMBER
PSI- 18" ED PS1-6" ED
PS2-18" ED PS2-6"ED
PS3- 18 "ED PS3-6"ED
PS4- 18 "ED PS4-6 "ED
FW2B-14"ED
FW2B-10"ED
FW2A-14"ED
FW2A-10"ED
TW7-8"ED TW7-8"EF
TW11-8"ED TW11-8"EF
ISI-5B
ISI-6A
ISI-6B
I I I I I I . f I f
NORTHERN STATES POWER COMPANY MONTICELLO UNIT I ISOMETRIC SUMMARY CLASS I
COMPONENT OR SYSTEMNSP ISO NUMBER
ISI-7
ISI-9
ISI-10
ISI-11A
ISI-1IB
ISI-1iC
ISI-1ID
ISI-IE
ISI-12
ISI-13A
ISI-13A SHT.2
REVISION NUMBER
1
2
1
2
2
2
2
0
1
3
2
NUMBER
PS18-8"ED
REW3-4"ED REW3-4"VCA
CRD7-3"EF
REW10-18"ED REW10-18"DCA
TW20-18"DCA TW20-16"DB
HIGH PRESSURE COOLANT INJECTION - STEAM SIDE
REACTOR WATER CLEANUP
REACTOR VESSEL NOZZLE N9 (REROUTED AND N9 CAPPED)
RESIDUAL HEAT REMOVAL
RESIDUAL HEAT REMOVAL
RESIDUAL HEAT REMOVAL
RESIDUAL HEAT REMOVAL
RESIDUAL HEAT REMOVAL (EQUALIZER)
REACTOR CORE INJECTION COOLANT (STEAM SIDE)
RECIRCULATION (ELBOWS) (SAFE-ENDS)
RECIRCULATION PUMP A SUPPORTS
TABLE III PAGE 2 OF 5
16" 16"
4' 9'
4,'
3"
28" 28" 28"
A A
B B
C C C
D
E
A
A
TW30-18"DCA TW30-16"DCA TW30-16"DB
TW36-4"ED
TW40-4"DBA
PS17-3"ED
REW13A-28"DCA REW13A-28"DCA REW13A-28"DCA
STD
5 11
4 12-2
18
8 67
67 10
67 65 10
4 45
58
1
63 66 71
1
1 2
. I . t
" "o
NORTHERN STATES POWER COMPANY MONTICELLO UNIT I ISOMETRIC SUMMARY
TABLE III PAGE 3 OF 5
CLASS I
COMPONENT OR SYSTEMnor 10i NUMBER
ISI-13B
ISI-13B SHT. 2
ISI-13C
ISI-13D
ISI-14
ISI-15
ISI-16
ISI-17
LOOP DESIG
B
A
B
RECIRCULATION (ELBOWS) (SAFE-ENDS)
RECIRCULATION PUMP B SUPPORTS
RECIRCULATION MANIFOLD RISER F RISER G RISER H RISER J RISER K SAFE-ENDS
RECIRCULATION MANIFOLD RISER A RISER B RISER C RISER 0 RISER E SAFE-ENDS
HEAD SPARE
HEAD VENT
JET PUMP INSTRUMENTATION
STANDBY LIQUID CONTROL
LINE NUMBER
REW13B-28"DCA REW13B-28"DCA REW13B-28"DCA
REW32-22"DCA REW14-12"DCA REW15-12"DCA REW16-12"DCA REW17-12"DCA REW18-12"DCA
REW32-22"DCA REW23-12"DCA REW22-12"DCA REW21-12"DCA REW20-12"DCA REW19-12"DCA
-- N6--
--N7 --V15-2"ED
-N8A&B
--N1O--
kICA T Cr. I flrITCTI~II 1
NUMBER
A&B
UT-CAL STD
63 66 71
62 64 64 64 64 64 70
62 64 64 64 64 64 70
45
46
72
73 73A
I
NORTHERN STATES POWER COMPANY MONTICELLO UNIT I ISOMETRIC SUMMARY CLASS I
COMPONENT OR SYSTEM
INSTRUMENT NOZZLE N11A
INSTRUMENT NOZZLE N11B
INSTRUMENT NOZZLES
BOTTOM HEAD DRAIN
STANDBY LIQUID CONTROL
NSP ISO NUMBER
ISI-18
ISI-18A
ISI-19
ISI-21
ISI-22
ISI-23
ISI-24A
ISI-24B
REVISION NUMBER
3
2
1
3
3
3
2
3
CRD SCRAM HEADER
CRD SCRAM HEADER
LOOP DESIG
B B B B B B
LINE NUMBER
-NIA-
-N11B-
-N12A--N12B-
REW31-2"ED
CH2-1.5"DC CH2-1.5"EF
PS15-3"EB PSI5 -3 "ED PS15A-2"ED PS15B-2"ED PS15C-2"ED PS15D-2"ED
CRD13A-4"DB CRD16A-4"CCD CR014A-6"DB CRD15A-4"DB CRD16A-12"CCD CRD16A-24"CCD
CRD13B-4"DB CRD16B-4"CCD CRD12B-6"DB CRD15B-4"DB CRD16B-12"CCD CRD16B-24"CCD
TABLE III PAGE 4 OF 5
LINE SIZE
3" 1.5"
3" 1.5"
3" 3"
2"
1.5" 1.5"
3" 3" 2" 2" 2" 2"
4" 4" 6" 4" 12" 24"
4" 4" 6" 4" 12" 24"
MAIN STEAM LEAKOFF
CONDENSATE
WALL THICK
.530"
.200"
.530"
.200"
.530"
.530
.218"
.218"
.218"
.300" .300" .343" .343" .343" .343"
.337"
.337"
.432"
.337"
.591" 1.027"
.337"
.337"
.432"
.337"
.591" 1.027"
UT-CAL STD
47
47
47 47
16
17
1 1
4 57 6 4 56 57
4 57 6 4 56 57
2 1 0 I I . 0
NORTHERN STATES POWER MONTICELLO UNIT I ISOMETRIC SUMMARY
NSP ISO REVISION NUMBER NUMBER
ISI-24C 2
ISI-26 1
FIG. 1 1
FIG.
FIG.
FIG.
FIG.
FIG.
FIG.
1
1
1
0
2
0
COMPANY
CLASS I
COMPONENT OR SYSTEM
CRD SCRAM HEADER DISCHARGES
RECIRCULATION DRAIN LINES
CONTROL ROD DRIVE LOCATION AND HOUSING WELDS
CIRCUMFERENTIAL AND LONGITUDINAL VESSEL WELDS
REACTOR VESSEL STUD, WASHERS AND LIGAMENT LOCATION
REACTOR VESSEL NOZZLE LOCATION AND IDENTIFICATION
REACTOR VESSEL HEAD WELDS
REACTOR VESSEL CIRCUMFERENTIAL SEAM WELDS
REACTOR VESSEL BOTTOM HEAD NOZZLE LOCATION
LOOP DESIG
A B
A B
TABLE III PAGE 5 OF 5
'
WALL THICK
.343"
.343"
.218"
.218"
.491"
.420"
LINE NUMBER
CRD16A-2"CCD CRD16B-2"CCD
REW28-2"EF REW29-2"EF
I-
LINE SIZE
2" 2"
2" 2"
UT-CAL STD
RPV 1
STUD- 14
RPV 1 30
RPV 3
RPV 1
, 4 1 . I t I I
E
APPENDIX B
ASME CLASS II EXAMINATIONS
0
Cc
0 0 LO
O~.
. I .
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTOON-EXAMINATION SUMMARY
Table S1.2 Page 1 of 1
Major Item: VESSFL WFI DS
I EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSP. LREQ'D AMOUNT ITEM INSPECTION ITEM GORY ITEM TO BE EXAMINED PER MOUNT EXAM IDENTIFICATION REPORT NO.
SHELL CIRCUMFERENTIAL WELDS
RHR HEAT EXCHANGERS E-200A
E-200B
HEAD CIRCUMFERENTIAL WELDS
RHR HEAT EXCHANGERS E-200A E-200B
TUBE SHEET TO SHELL WELDS
PPM-0043, Rev. 0 (6/86) (M&SP 5.2)
ONE TWO THREE
TWO
(3) 1 1 1
(1)
1
1
1
W-1 W-2 (E200B)
W-4 (E200B)
MULTIPLE VESSELS 84-037, 177 87-415, 407
87-416, 413
Form 170278
JFS121687WMHO1
C1.10
C1.20
C1.30
C-A
C-A
C-A
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table S2.2 Page LDS
Major Item: NOZ-ZLE WELDS
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSP. REQ'D AMOUNT ITEM INSPECTION ITEM GORY ITEM TO BE EXAMINED PER MOUNT EXAM IDENTIFICATION REPORT NO.
NOZZLES IN VESSELS 1/2 IN.OR LESS IN NOMINAL THICKNESS
NOZZLES IN VESSELS OVER 1/2 IN. IN NOMINAL THICKNESS
RHR HEAT EXCHANGERS E-200A
E-200B
PPM-0043, Rev. 0 (6/86) (M&SP 5.2)
ONE TWO TWO THREE
1 1 1 1
1 1 1
W-7 N-4 N-3
(E200A) (E200B)
84-027,84-176 87-411,418,412 87-405,417,406
Fomm 70278
LCD121687WMHO4
C2. 10
C2.20
C-B
C-B
of 1
I I I .
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table S3.2 Page 1 of 13
Major Item: SUPPORT MEMBERS
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSP REQ'D MOUNT ITEM INSPECTION ITEM I GORY - ITEM TO BE EXAMINED PER IAMOUNT EXAM IDENTIFICATION REPORT NO.
INTEGRALLY WELDED SUPPORT ATTACHMENTS
RHR HEAT EXCHANGERS E-200A
E-200B
COMPONENT SUPPORTS
,RHR HEAT EXCHANGERS E-200A
E-200B
SUPPORTS-MECHANICAL AND HYDRAULIC
PIPING
*INTEGRALLY WELDED SUPPORT ATTACHMENTS
MAIN STEAM A
MAIN STEAM B
C3. 10
C3.20
C3.40
C3.40
(3) 1 1
1
2 1 1 2
C-C
C-C
C-C
C-C
2 2
2 1 1
ONE TWO
THREE
ONE TWO TWO THREE
ONE TWO THREE
ONE TWO THREE
Support"A"&"B" Support C
Su pport" A" & " B" Support C Support B
MSAK-59A
84-044 87-402,401,047, 403,404,212
84-044 87-047 87-211
*INCLUDES THE CORRESPONDING C3.50 (VT-3) & C3.60 (VT-4) EXAMINATIONS WHERE APPLICABLE
86-060,191,409
.1 .a-~ 4 ________________ = -
PPM-0043, Rev. 0 (6/86) (M&SP 5.2) Form 17027F
JFS031885WMHO3-LT
1
1
1
I I
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table S3.2 Page 2 of 13
Major Item: SUPPORT MEMBERS
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSR REO'D IAMOUNT ITEM INSPECTION ITEM GORY ITEM TO BE EXAMINED I PER AMOUNT EXAM IDENTIFICATION REPORT NO.
C3.40 C-C (CONTINUED)
MAIN STEAM C
MAIN STEAM D
SUPPLY TO STEAM SEAL SYSTEM
HPCI WATER DISCHARGE
HPCI STEAM
HPCI STEAM DISCHARGE
CORE SPRAY A DISCHARGE
ONE TWO THREE
ONE TWO THREE
ONE TWO THREE
ONE
TWO THREE
ONE TWO THREE
ONE TWO THREE
ONE
TWO THREE
CIAK-31 CIAK-52 CIAK-45
(BASELINE)
TDAK-10(BASELINE)
CSAK-35 TWH-54,81,86 CSAK-52 CSAK-46
82-101 86-124 87-012
86-030,268,268R,436
84-067, 067R 86-358, 357, 156 86-165 87-020
.5 .5. & .1 £ .1 £
PPM-0043, Rev. 0 (6/86) (M&SP 5.2) Form 70278
JFS031885WMHO3-LT
1 1 1
1
1 4
1
I II I I I 1. 1.
it 4 4 C
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table S3.2 Page 3
Major item: SUPPORT MEMBERS
EXAM COMPONENT OR SYSTEM SUB CATE- I AND DESCRIPTION OF INSP REQ'D AMOUNT ITEM INSPECTION ITEM GORY ITEM TO BE EXAMINED I PER MOUNT EXAM IDENTIFICATION REPORT NO.
C3.40 C-C
2
1
1 1
1
(CONTINUED)
CORE SPRAY B DISCHARGE
REACTOR WATER FROM SKIMMER SYSTEM
RHR SERVICE WATER
RHR SUCTION A
RHR DISCHARGE A
RHR SUCTION B
RHR DISCHARGE B TW19-10"GE
ONE
TWO THREE
ONE
TWO THREE
ONE
TWO THREE
ONE TWO
THREE
ONE
TWO THREE
ONE TWO THREE
ONE TWO THREE
4
1
2
1 1
2 2
TWH-55,501 CSBK-41 TWH-67A(BASELINE) TWH-67A
RWAK-25,8
SWAK-42 SWAK-43(BASELINE)
TWH-9,6 TWH-1 TWH-3
TWH-65A,62A,62 (BASELINE) TWH-173
TWH-16A(BASELINE) TWH-16A
TWH-91(BASELINE)
I I.. A I A I .5
PPM-0043, Rev. 0 (6/86) (M&SP 5.2)
86-406,070 86-455,456,456R,272 86-032,269,099 87-079,084,056
86-289,288,334,222, 225,225R,217
82-292, 109, 109R 86-654, 653, 657
86-129, 173 87-087,094,054 87-086,095,052
86-660,178,680
87-150,151,153,153R
86-621,628,463 87-259,268,276
86-264
Forin 170278
JFS031885WMH03-LT
2
1
2
1
of 13
1 4
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table S3,2 Page 4
Major Item: SUPPORT MFMRFRS
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSP. REO'D AMOUNT ITEM INSPECTION ITEM I GORY ITEM TO BE EXAMINED I PER MOUNT EXAM I IDENTIFICATION REPORT NO.
(CONTINUED)
TW20-16"GE
CONTAINMENT SPRAY A & B
*COMPONENT SUPPORTS
MAIN STEAM A
MAIN STEAM B
MAIN STEAM C
C3.40
C3.50
c-c
c-C
86-396,395,403
86-407,408,408R,372
86-410,223 86-505,504,200,200R 86-441,448,448R,371 87-148,149,152
*INCLUDES THE CORRESPONDING C3.60 (VT-4) EXAMINATIONS WHERE APPLICABLE
86-270, 205
86-271, 206 87-223,223R,222,222[
ONE TWO THREE
ONE
TWO THREE
ONE TWO THREE
ONE TWO THREE
ONE TWO THREE
L _________ J A I A I
Form 170278
JFS031885WMH03-LT
I .
of 13
TWH-169(BASELINE)
TWH-143 (BASELINE EXAMS) TWH-144, 75 TWH-76 SS-31 TWH-143
MSAK-45, 56
MSBK-42, 54 MSBK-51,53
MSCK-53, 56 MSCK-43, 48
86-208, 207 87-143,144,144R
PPM-0043, Rev. 0 (6/86) (M&SP 5.2)
a ,I . I$
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTI1ON-EXAMINATION SUMMARY
Table S3 .2 Page 5 of 13
Major item: SUPPORT MEMBERS
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSP. REQ'D AMOUNT ITEM INSPECTION ITEM GORY ITEM TO BE EXAMINED I PER . AMOUNT EXAM I IDENTIFICATION REPORT NO.
(CONTINUED)
MAIN STEAM D
SUPPLY TO STEAM SEAL SYSTEM
PS11-6"ED
PS14-ED
PS7-10" ED
PS7-8" ED
MAIN STEAM EQUALIZER HDR
HPCI WATER DISCHARGE
ONE
TWO THREE
ONE TWO THREE
ONE TWO THREE
THREE
ONE TWO THREE
ONE
2
2
3 3
7
13
MSDK-55 MSDK-52A(BASELINE)
SSAK-9, SSBK-4A
SSAK-17,18,18A SSAK-14A,21,22
TWH-38, CIAK-59 SR-69, SS-35 CIAK-26,27A,28 BASELINE EXAMS CIAK-25,27A,28 37,37A,44A,59A 61A TWH-37A,38,39A SS-35, SR-69
86-209 86-394
86-235, 234
86-428,429,233 87-221,220,399
82-106, 82-086 84-011 84-019,012,013
86-148,144,149 464,675,125,677, 676 86-147,145,146 86-150,143
Form 170278
JFS031885WMH03-LT
C3.50 C-C
PPM-0043, Rev. 0 (6/86) (M&SP 5.2)
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTIION-EXAMINATION SUMMARY
Table S3.2 Page 6
Major Item: SUPPORT MEMBERS
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSP. REQ'D AMOUNT ITEM INSPECTION ITEM GORY ITEM TO BE EXAMINED IPER MOUNT EXAM IDENTIFICATION REPORT NO.
C3.50 C-C4
9
(CONTINUED)
HPCI WATER SUCTION
HPCI STEAM
HPCI STEAM DISCHARGE
CORE SPRAY A SUCTION
TWO
THREE
ONE TWO THREE
ONE
TWO THREE
ONE TWO THREE
ONE
TWO
TURF FU _____________________ L *****~~ I I
PPM-0043, Rev. 0 (6/86) (M&SP 5.2)
CIAK-25,50,59A TWH-36 BASELINE EXAMS CIAK-26,37,40,48A CIAK-50,52,59 TWH-40,39
TDAK-23, 25, 26 BASELINE EXAMS TDAK-13,16,17
23,26,26A,33
34,40A,5,26B
TDAKR-30 TDAK-13,16,17,5
TDBK-7, 8
TWH-53,54 BASELINE EXAMS TWH-52,81A,82,83, 83A,84,85 SR-58 SS-27 TWH-53,52
rorm 170278
JFS031885WMHO3-LT
3 12
4
2
2 8
2
87-155,395,145 87-181
87-022,026,025,013 87-014,015,015R,00E 87-023,024
82-108, 107, 103
86-244,661,661R, 655,655R, 662,656,656R,663, 665, 151,151R,666,435, 435R,470 86-658 87-147,396,394,146
86-187,186
84-006, 010
86-682,159,356,368 157,280,281,355,158 86-461 87-018,327 87-017,319
of 13
I . I .
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table S3.2 Page 7
Major Item: SUPPORT MEMBERS
EXAM COMPONENT OR SYSTEM I SUB CATE- AND DESCRIPTION OF INSP. REO'D MOUNT ITEM INSPECTION ITEM I GORY ITEM TO BE EXAMINED I PER AMOUNT EXAM I IDENTIFICATION REPORT NO.
(CONTINUED)
CORE SPRAY DISCHARGE
A
CORE SPRAY B SUCTION
CORE SPRAY B DISCHARGE
REACTOR WATER FROM SKIMMER SYSTEM
RCIC WATER SUCTION
C-c5
5
4
ONE
TWO
THREE
ONE
TWO THREE
ONE
TWO
THREE
ONE TWO THREE
ONE TWO THREE
TWH-81,82 CSAK-31,32A CSAK-42 BASELINE EXAMS CSAK-37,39A,44A 47,54 CSAK-32A SR-58 TWH-83,84
TWH-55 BASELINE EXAMS TWH-58,66A,510,512 514,69 SS-28B TWH-57,58
TWH-69,70,113
BASELINE EXAMS CSBKA-43,38,35,32 TWH-66A CSBK-35
RWAK-25A,28 RWAK-35
TW-25 TW-25
84-009, 008 84-066, 066R, 86-353
068
86-369,369R,459,46( 458,370 87-019 87-326 87-320,325,325R
84-018
86-097,681,096,098 093,094 86-266 87-053,055
84-058, 058R, 016, 016R,015,015R
86-275,273,274,276 87-423 87-321
86-267,664 87-027
84-014 87-217,217R
I 1. A I A I A
Form 170278
JFS031885WMHO3-LT
C3.50
2 1
1 1
of 13
PPM-0043, Rev. 0 (6/86) (M&SP 5.2)
I . I .
4
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table S3.2 Page 8
Major Item: SUPPORT MEMBERS
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSP. REQ'D AMOUNT ITEM INSPECTION ITEM GORY ITEM TO BE EXAMINED PER AMOUNT EXAM IDENTIFICATION REPORT NO.
C3.50 C-C (CONTINUED)
RCIC STEAM DISCHARGE
RHR SERVICE WATER
RHR SUCTION A REW10-18"HE
TW14B-20"HE
TW28-20"HE
82-102,102R,104, 87-414,219
105
84-235,235R,024, 024R,017,023,023R 043
ONE TWO' THREE
ONE
TWO THREE
ONE
TWO THREE
ONE
TWO THREE
ONE TWO THREE
Form 170278
JFS031885WMH03-LT
SS-38A&B,RSH-13 RSH-14,15
SWAK-25,26,31 34,43
BASELINE EXAMS SWAK-59A,51,17,16, 13A,6,9 SWAK-25,20
SS-21,TWH-7 BASELINE EXAMS TWH-8,7,7A,6A
TWH-6,SS-24 TWH-1A(BASELINE) TWH-2
TWH-18(BASELINE)
86-189,188,430, 432,431,433,434 87-007,006
84-133,131,131R
86-398,128,130,174
84-031,029 86-172 87-100
86-131
PPM-0043, Rev. 0 (6/86) (M&SP 5.2)
of 13
1 6 1 .
,
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table S3 .2 Page9 of 13
Major Item: SUPPORT MFMRFRS
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSP. LREO'D AMOUNT ITEM INSPECTION ITEM I GORY ITEM TO BE EXAMINED I PER MOUNT EXAM I IDENTIFICATION REPORT NO.
C3.50 C-C1
3 2
3
3 7
(CONTINUED)
RHR DISCHARGE A TW29-10"GE
TW30-14"GE
TW30-16"GE
TW30-16"DE
RHR SUCTION B REW10-18"HE
TW14A-20"HE
ONE
TWO THREE
ONE
TWO
THREE
ONE TWO THREE
ONE TWO THREE
ONE
TWO THREE
ONE
TWO THREE
TWH-61 BASELINE EXAMS TWH-59A,61,61A TWH-59,59A
TWH-63,SS-25, TWH-73 BASELINE EXAMS TWH-64A,73A,73B TWH-62A,64,64A,65 TWH-65A,73A,73B
BASELINE EXAMS TWH-20,20A,10,10A
TWH-16, TWH-58 BASELINE EXAMS TWH-12A,16 TWH-12
a a -
84-030
86-176,194,175 87-099,101
84-028,132,076, 076R
86-177,196,195 87-051,049,050,102 87-048,215,216
86-122,684,404,123
82-291, 82-290
86-462,469,469R 87-021,275
Form 170278
JFS031885WMHO3-LT
4
2
2 1
PPM-0043, Rev. 0 (6/86) (M&SP 5.2)
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table S3.2 Page 10 of 13
Major Item: SUPPORT MFMRFRS
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSP. REQ'D AMOUNT ITEM INSPECTION ITEM GORY ITEM TO BE EXAMINED IPER AMOUNT IEXAM IDENTIFICATION REPORT NO.
C3.50 C-C
2 1
(CONTINUED)
TW27-20" HE
RHR DISCHARGE B TW19-10"GE
TW19-14"GE
TW20-14"GE
TW22-14"GE
1
ONE
TWO THREE
ONE
TWO THREE
ONE
TWO THREE
ONE
TWO
THREE
ONE TWO THREE
2
BASELINE EXAMS TWH-19
BASELINE EXAMS TWH-632,93A,93,94
TWH-632
TWH-94,95A (BASELINE) TWH-94,94A
TWH-100,101,102 BASELINE EXAMS TWH-95,98A,99,100 101A SR-24 TWH-95,98
TWH-168,SR-23
a a. a a . a
PPM-0043, Rev. 0 (6/86) (M&SP 5.2)
86-121
86-399,401,265, 265R,400 87-209
86-405,683
87-210,274
8P-057,055,056
86-402,185,168, 168R,167,167R,184 87-016,016R 87-214,213
84-054,059
Form 170278
JFS031885WMH03-LT
4
1
2
2
3
5
3
2
I .
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table S3.2 Page 11 of 13
Major Item: SUPPORT MEMBERS
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSP. REQ'D JAMOUNTI ITEM INSPECTION ITEM GORY ITEM TO BE EXAMINED I PER MOUNT EXAM 'IDENTIFICATION REPORT NO.
C3.50
C3.60
ONE
TWO THREE
ONE
TWO THREE
2
1 3
2
1 4.
2
8
C-C
C-C
SS-30, TWH-140 BASELINE EXAMS TWH-139A,140,140A 140B,142,142A, 145,139
TWH-74, TWH-75 BASELINE EXAMS TWH-76A,77,77A, 78,79,80,80A
________________ I I~ & I _____________ -
PPM-0043, Rev. 0 (6/86) (M&SP 5.2)
(CONTINUED)
CONTAINMENT SPRAY A & B
TW23-12"GE
TW23-10"GE
TW33-12"GE
TW33-10"GE
*SUPPORTS - MECHANICAL AND HYDRAULIC
PUMPS
Form 170278
JFS031885WMHO3-LT
2
7
82-145, 140, 140R
86-229,354,354R, 226,288,231,227, 679,305,652,232
82-144, 82-143
86-202,204,201, 159,367,203,495, 495R
*INCLUDED UNDER C3.40 & C3.50 -
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINIATION SUMMARY
Table S3.2 Page 12
Major item: SUPPORT MEMBEIR
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSP. REQ'D AMOUNT ITEM INSPECTION ITEM GORY ITEM TO BE EXAMINED IPER MOUNT EXAM IDENTIFICATION REPORT NO.
C3. 70
C3.80
C3.90
VALVES
PPM-0043, Rev. 0 (6/86) (M&SP 5.2)
C-C
C-C
C-C
*INTEGRALLY WELDED SUPPORT ATTACHMENTS
RHR PUMPS (P-202D)
-CORE SPRAY PUMPS (14-1B)
COMPONENT SUPPORTS
HPCI TURBINE & PUMPS
RCIC TURBINE & PUMP
SUPPORTS - MECHANICAL AND HYDRAULIC
MNT FT (P202A)
MNT FT (P202C) Support "D"
Support "B"
Support "A" Support "A" & "B"
Support "A" Support C, D
*INCLUDES THE CORRESPONDING C3.80 (VT-3) EXAMINATIONS
87-089,092,046
87-088,093,045 84-065,073
84-001,007
82-110 86-152,153
86-169 87-424,218
JFS031885WMHO3-LT
of 13
TWO THREE TWO ONE
THREE ONE
ONE
TWO THREE
ONE TWO THREE
1 2
Form 170278
I 0
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table S3 2 Pace 13
Major Item: SUPPORT MEMBERS
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSP. REQ'D AMOUNT ITEM INSPECTION ITEM I GORY I ITEM TO BE EXAMINED I PER AMOUNT EXAM IDENTIFICATION REPORT NO.
INTEGRALLY WELDED SUPPORT ATTACHMENTS
COMPONENT SUPPORTS
SUPPORTS - MECHANICAL AND HYDRAULIC
*INCLUDED UNDER C3.40, C3.50, & C3.60
A A I & I & I
PPM-0043, Rev. 0 (6/86) (M&SP 5.2) Form 170278
JFSO31885WMHO3-LT
C3. 100
C3. 110
C3. 120
C-C
C-c
C-C
of 13
, I I I
I . . t
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table S4.2 Page 1 of 1
Major Item: PRESSURE RETAINING BOLTING 2"
! EXAM COMPONENT OR SYSTEM I I SUB CATE- LAND DESCRIPTION OF INSP REQ'D AMOUNT ITEM INSPECTION ITEM GORY ITEM TO BE EXAMINED PER A MOUNT EXAM IDENTIFICATION REPORT NO.
BOLTS AND STUDS
PIPING
BOLTS AND STUDS
PUMPS
BOLTS AND STUDS
VALVES
BOLTS AND STUDS
PPM-0043, Rev. 0 (6/86) (M&SP 5.2)I & - a
Form 170278
LCD121687WMHO3
C4.10
C4.20
C4.30
C4.40
C-D
C-D
C-D
C-D
0 , 0. I I .
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table S5.2 Pa e 1 of 8
Major Item: PIPING PRESSURE BOUNDARY
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSP. REQ'D AMOUNT ITEM INSPECTION ITEM I GORY I ITEM TO BE EXAMINED PER AMOUNT EXAM I IDENTIFICATION REPORT NO.
PIPING WELDS 1/2 IN. OR LESS NOMINAL WALL THICKNESS
CIRCUMFERENTIAL AND *LONGITUDINAL WELDS
('75 CATEGORY C-F)
SUPPLY TO STEAM SEAL SYSTEM PS10-5"
PS11-6"ED PS12-6 "ED PS13-6"ED PS14-6"ED
RHR SUCTION A & B REW10-18"HE
TW14B-20"HE TW14A-20"HE
TW16-14"HE TW18-14HE TW15-14"HE TW17-18"HE
PPM-0043, Rev. 0 (6/86) (M&SP 5.2)
ONE
THREE
ONE
THREE
ONE TWO THREE
ONE
TWO
THREE
3 SSAJ-48,47,51
SSAJ-10
32,403
355
W-7
C5. 10
C5. 11 & C5.12
LCD121687WMH10
C-F
C-F
RELIEF NO.15
*2.5T MIN. FROM EACH SCHEDULED CIRC WELD INTERSECTION WILL BE EXAMINED
86-241,236,236R, 240,239,242,237
86-243,238
82-184,82-183
82-365
87-078,083
Fo,, 170278
I I . I
I4 I
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table S5.2 Page 2 of 8
Major Item: PIPING PRESSURE BOUNDARY
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSP. REQ'D MOUNT ITEM INSPECTION ITIEM GORY ITEM TO BE EXAMINED PER MOUNT EXAM IDENTIFICATION REPORT NO.
C5.11 & CS.12
C-F (CONTINUED)
RHR DISCHARGE A & B TW29-10"GE
TW19-10"GE
TW29-14"GE TW19-14"(;E
TW30-14"GE
TW20-14"GE
TW30-16"GE TW20-16"GE
TW22-14"GE
('75 CATEGORY C-G)
HPCI WATER SUCTION TW1-14"HE C16-14"HE
HPCI STEAM PS18-8"ED
HPCI STEAM DISCH RS2-16"HE
87-165,168,085,096 87-262,265
84-047 87-077,082 87-260,267
84-049, 84-048 87-419,421,167, 170,166,169 87-428,427,261,266
84-077 87-249,248 84-078
Form 170278
LCD121687WMH1O
TWO TWO THREE
ONE TWO
ONE TWO
TWO THREE
TWO ONE TWO ONE
TWO THREE
TWO THREE
TWO THREE
W-12,362 W-313
16 W-367 W-323
369,370 W-3,13,374
W-22,329
25 25A 348
PPM-0043, Rev. 0 (6/86) (M&SP 5.2)
A -
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table S5.2 Page 3 of 8
Major item: PIPING PRESSURE BOUNDARY
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESC RIPTION OF INSP. RE'D MOUNT ITEM INSPECTION ITEM IGORY ITEM TO BE EXAMINED --PER - MOUNT EXAM IDENTIFICATION REPORT NO.
C5. 11 & C5.12
PPM-0043, Rev. 0 (6/86) (M&SP 5.2)
C-F (CONTINUED)
RS2-18"HE RS2-20"HE
CORE SPRAY A & B SUCTION
TW6-12"HE TW10-12"HE
CORE SPRAY A & B DISCHARGE
TW7-10"GE
TW11-10"GE
TW7-8"ED TW11-8"ED
TW8-8"GE TW12-8"GE
REACTOR WATER FROM SKIMMER SYSTEM
REW11-8"HE
RCIC WATER SUCTION TW5-6"HE
C17-6"HE
THREE
ONE TWO THREE
ONE TWO THREE
ONE
THREE
ONE TWO THREE
ONE TWO THREE
84-004,005 87-076,081,075,080
84-003,002 87-269,270
84-072
86-221,224
82-100 87-397,398
LCD121687WMH10
1
1 1
18, 532 W-654,8F
1, 4 W-564
CSAJ-32
RWAJ-7
14 W-227
Form 17-0278
1 1 4 1
it a I
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table S5.2 Page 4 of 8
Major item:PIPING PRESSURE BOUNDARY
EXAM COMPONENT OR SYSTEM SUB CATE- At4D DESCRIPTION OF INSP. REQ'D AMOUNT ITEM INSPECTION ITEM GORY I ITEM TO BE EXAMINED PER MOUNT EXAM IDENTIFICATION REPORT NO.
C5. 11 & C5.12
C-F
C-F
(CONTINUED)
RCIC STEAM DISCHARGE RS3-8"HE*
RHR SERVICE WATER SW9-8"GE
RHR SUCTION A & B TW28-20"HE TW27-20"HE
CONTAINMENT SPRAY A & B
TW23-12"GE TW33-12"GE
TW23-10"GE TW33-10"GE
FEEDWATER TO RWCU TO HPCI
86-120,119
84-186,185
84-046
82-142 87-420,422
82-141
411
SWAJ-39,40
3
22 W-18
28
AUGMENTED W-1 W-2 W-3 W-4 W-12 W-12A
_________ I A I A I.
PPM-0043, Rev. 0 (6/86) (M&SP 5.2)
121 122 123 126 124 125
LCD121687WMH10
ONE TWO THREE
ONE TWO THREE
ONE TWO
ONE TWO THREE
ONE THREE
ONE84-115, 84-116, 84-117, 84-120, 84-118, 84-119,
Form 170278
.4 . -
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTIION-EXAMINATION SUMMARY
Table S5.2 Paae 5 of 8
Major Item: PIPING PRESSURE BOUNDARY
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSP REQ'D AMOUNT ITEM INSPECTION ITEM GORY ITEM TO BE EXAMINED PER LMOUNTI EXAM IDENTIFICATION REPORT NO.
FEEDWATER TO RWCU TO HPCI
CONTROL ROD DRIVE TO REACTOR WATER CLEAN-UP ONE
.5 .a~ I .4 & .4
PPM-0043, Rev. 0 (6/86) (M&SP 5.2)
C5.11 &C5.12 C-F
C-F
Form 170278
LCD121687WMH10
W-1 W-2 W-3 W-4 W-12 W-12A W-1 W-2 W-3 W-4 W- 12 W-12A
AUGMENTED W-7 W-11 W-12 W-13 W-14 W-7 W-11 W-12 W-13 W-14 W-7 W-11 W-12 W-13 W-14
86-006,021,083 86-007,023,084 86-009,024,085 86-008,022,086 86-010,025,087 86-011,020,088 87-063,069,057 87-064,070,058 87-066,071,060 87-065,072,059 87-067,073,061 87-068,074,062
84-247, 253 84-246, 258 84-250, 256 84-249, 254 84-248, 255 86-005,015,078 86-004,016,082 86-003,026,081 86-002,017,080 86-001,014,079 87-226,238,229 87-225,234,233 87-224,235,232 87-228,237,231 87-227,236,230
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
TableS5.2 Page 6 of 8
Major Item:PIPING PRESSURE BOUNDARY
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSP. REQ'D AMOUNT . ITEM INSPECTION ITEM IGORY ITEM TO BE EXAMINED PER AMOUNT EXAM IDENTIFICATION REPORT NO.
C5.20
C5.21 & C5.22
C-F
C-F
PIPING WELDS OVER 1/2 IN. NOMINAL WALL THICKNESS
CIRCUMFERENTIAL AND *LONGITUDINAL WELDS
('75 CATEGORY C-F)
MAIN STEAM A,13,C,&D PS1-18"ED PS2-18"ED PS3-18"ED
PS4-18"ED
SUPPLY TO STEAM SEAL SYSTEM
PS7-8"ED
PS7-10"ED
MAIN STEAM EQUALIZER HDR
PS30-18"EDB
10"DRIPLEG
FEEDWATER A.& B FW2A-14"ED FW2B-14"ED
1 1 2
2
1
2
ONE TWO' TWO
THREE
ONE
TWO THREE
ONE
TWO THREE
ONE
MSAJ-59 MSBJ-43 MSBJ-57 MSCJ-46
SSAJ-35,SSAJ-37
SSAJ-19
MSEJ-12 MSEJ-13
FWDJ-38
*2.5T MIN FROM EACH SCHEDULED CIRC WELD INTERSECTION WILL BE EXAMINED
86-059,100,190 8 -043,097,044 87-425,425R,409,42E 87-140,142,139
82-142,111 82-153,112 87-250,251
86-061,061R,102,192 86-062,101,193
82-025,026
A A. J A I A I
Form 170278
LCD121687WMH10
1 1
PPM-0043, Rev. 0 (6/86) (M&SP 5.2)
, V I (
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table S5.2 Page 7 of 8
Major Item:PIPING PRESSURE BOUNDARY
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSP. REQ'D AMOUNT ITEM INSPECTION ITEM GORY ITEM TO BE EXAMINED PER MOUNT EXAM L IDENTIFICATION REPORT NO.
(CONTINUED)
RHR DISCHARGE A & B TW30-16"DB TW20-16"DB
('75 CATEGORY C-G) HPCI WATER DISCHARGE
TW3-12"ED
PIPE BRANCH CONNECTIONS
CIRCUMFERENTIAL AND *LONGITUDINAL WELDS
('75 CATEGORY C-F)
SUPPLY TO STEAM SEAL SYSTEM PS11-6"ED PS12-6"ED PS13-6"ED PS14-6"ED
RHR SUCTION A & B TW16-14"HE TW18-14"HE TW15-14"HE TW17-14"HE
C5.21 &C5.22
C5.30
C5.31 & C5.32
3
TWO
ONE
TWO THREE THREE
THREE
TWO
CIAJ-62,29,30
W-939
84-129,130,22, 25,21,26
*2.5T MIN FROM EACH SCHEDULED CIRC WELD INTERSECTION WILL BE EXAMINED
MULTIPLE STREAMS
MULTIPLE STREAMS 87-263,264
L I... A & A L A
PPM-0043, Rev. 0 (6/86) (M&SP 5.2) Form 170278
LCD121687WMH1O
1
C-F
C-F
I , 0,
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table 55.2 Page 8 of 8
Major Item: PIPING PRESSURE BOUNDARY
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSP. REQ'D AMOUNT ITEM INSPECTION ITEM GORY ITEM TO BE EXAMINED PER IAMOUNT EXAM I IDENTIFICATION REPORT NO.
(CONTINUED)
RHR DISCHARGE B TW22-14"GE
(CATEGORY C-G)
REACTOR WATER FROM SKIMMER SYSTEM
REW11-8"HE
RHR SUCTION A & B TW28-20"HE
TW27-20"IHE
TWO
ONE
1
1 1 820
MULTIPLE STREAMS
SINGLE STREAMS
84-045
Ii 1 A I _____________ A I A
PPM-0043, Rev. 0 (6/86) (M&SP 5.2) Form 170278
LCD121687WMH10
C5.31 & C5.32
C-F
1. k I
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table S6.2 Page 1 of I
Major Item: PUMP CASINGS AND VAI VF RnnTFS
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSP. REO'D MOUNT ITEM INSPECTION ITEM GORY ITEM TO BE EXAMINED PER .MOUNT EXAM I IDENTIFICATION REPORT NO.
PUMP CASING WELDS
VALVE BODY WELDS
I I. £ 1 A I -
PPM-0043, Rev. 0 (6/86) (M&SP 5.2) Form 170278
LCD121687WMHO2
C6. 10
C6.20
C-G
C-G
* I A
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT INSERVICE INSPECTION-EXAMINATION SUMMARY
Table S7.2 Page 1 of 1
Major item: PRESSURE RETAINING COMPONENTS
EXAM COMPONENT OR SYSTEM SUB CATE- AND DESCRIPTION OF INSP. REQ'D AMOUNT ITEM INSPECTION ITEM GORY - ITEM TO BE EXAMINED PER MOUNT EXAM I IDENTIFICATION REPORT NO.
PRESSURE VESSELS PIPING PUMPS VALVES
PRESSURE VESSELS PIPING PUMPS VALVES
*SYSTEM PRESSURE TEST PERFORMED BY PLANT EACH INSPECTION PERIOD
*SYSTEM HYDROSTATIC TEST PERFORMED BY PLANT EACH INSPECTION INTERVAL
LCD121687WMHO1
C7.10 C7.20 C7.30 C7.40
C7.11 C7.21 C7.31 C7.41
C-H C-H C-H C-H
C-H C-H C-H C-H
PPM-0043, Rev. 0 (6/86) (M&SP 5.2) Form 170278
I TABLE S-II INORTHERN STATES POWE3R COMPANY
ISU13-ITEMI SYSTEM ICLASS; ISO I METH I I TEM IREPORT IPREVIOUS RESULTS CURRENT RESULTS ILIMITATIONS I -------- I --------------- I------ I ---------- I ---- I --------------- I ---------- I -------------------- ---------------- I..................------JCi.i0 IRHR Hi EXCH. B 1 1 I Is-50 1UT4 IWELD 2 187-415 1 Resutts:N/A Resutts:NAD ILIMITED TO 1.511--FLANGE IC1.10 IRHR Hi EXCH. B 1 11IISI-50 IUT4 jWELD 2 187-415 1Resutts:N/A Resutts:NAD ILIMITED BY NOZZ,10-'EA SIDE 0 lC1.10 IRHR Hi EXCH. B 1~ 11ISI-50 IVT1 IWELD 2 187-407 1Results:N/A Results:NAD INONE IC1.20 IRHR HT EXCH. B 1 151 S-50 IUT4 IWELD 4 187-416 1 Resutts:N/A Resutts:GEO INONE
I II I II Scan: 1 1 I II I II Type:OD GEO I I II I IAmptitude:<20 I I II I II Ax Loc: I I II I II Circ Loc: I I II I II Length:360I
IC1.20 IRHR HT EXCH. B I I I SI-50 IUT4 IWELD 4 187-416 1Resutts:N/A Resutts:NAD 13"1 PLUGS;3,9;.7511 FROM WELD IC1.20 fRHR HT EXCH. B 1 I 11: JI-SO JVT1 IWELD 4 187-413 I Resutts:N/A IResutts:NAD INONE JC2.20 IRHR HT EXCH. A 1 i 11IISI-50 IMT IN4 187-411 I Resutts:N/A IResutts:NAD INONE JC2.20 IRHR HT EXCH. A 1 11. ISI-50 IUT4 IN4 187-418 1 Resutts:N/A Results:NAD INO SCAN 1 DUE TO NOZZLE JC2.20 IRHR HT EXCH. A I II JISI-50 IVT1 IN4 187-412 1 Results:N/A Results:NAD INONE IC2.20 JRHR HT EXCH.' B 1 IX JISI-50 IMT IN3 187-405 1 Resutts:NONE JResutts:NAD INONE IC2.20 JRHR HT EXCH. B I IX JSI-5O IUT4 IN3 187-417 1 Results:N/A Resutts:NAD INO SCAN 2 DUE TO NOZZLE IC2.20 IRHR HT EXCH. B IX" IlSI-50 IVr1 IN3 187-406 1 Resutts:N/A Resutts:NAD INONE 1C3.1O IRHR HT EXCH. A I II IISI-50 IMT ISUPPORT C 187-402 1 Resutts:N/A I Resutts:NAD INONE IC3.1O JRHR HT EXCH. A IIX JISI-50 lVT1 ISUPPORT C 187-401 1 Resutts:N/A IResutts:IND INONE
I I I I II IType:ARC STRIKE I II III I Ax Loc: I I I I I II I Circ Loc:I I I I III I ILength:I
JC3.1O IRHR Hr EXCH. A 1 I 151 S-50 IVT1 ISUPPORT C 187-401R I Resutts:N/A I Results:NAD INONE IC3.1O IRHR HT EXCH. B 1 11 JIS1-50 IMT ISUPPORT C 187-403 1 Results:N/A I Resutts:NAD INONE 1C3.1O IRHR Hr EXCH. B I If IlSI-50 lVT1 ISUPPORT C 187-404 1 ResuLts:N/A I Resutts:NAD INONE IC3.1o IRHR Hr EXCH. B 1 11 JISI-50 IVT3 ISUPPORT C 187-212 I Resutts:N/A I Resutts:NAD INONE IC3.20 IRHR HT EXCH. A 1 11 lISI-50 IVT3 ISUPPORT C 187-047 1 Results:N/A I Resutts:NAD INONE 1C3.20 IRHR HI EXCH. B 1 11 I~SI-50 IVT3 ISUPPORT B 187-211 1 Results:N/A I Results:NAD INONE JC3.4o lCONTAINMENT SPRAY A 1 1I I~SI-44 IMT ITWH-143 187-148 1 Results:NONE I Results:NAD INONE IC3.40 lCONTAINMENT SPRAY A 1 1I IISI-44 IVTl ITWH-143 187-149 1 Resutts:NONE I Results:NAD INONE IC3.40 lCONTAINMENT SPRAY A 1 11 I~SI-44 IVT3 ITWH-143 187-152 1 Resutts:NONE I Results:NAD INONE 1C3.40 ICORE SPRAY A 1 11 IISI-34A 1VT3 ICSAK-46 187-020 1 Results:N/A IResults:NAD INONE IC3.40 ICORE SPRAY B DISCH 1 11 IISI-35 IMT ITWH-67A 187-079 1 Resutts:NONE I Results:NAD INONE 11 1 -________1_______________________I_____ .1 ___________ _____I__________1______I __________ I________1_____________ 1_____________________ 1_______________________________
Page 1 of 10
I I
I I
I TABLE S-II NORTHERN STATES POWER COMPANY
SUB-ITEMI SYSTEM |CLASS | ISO IMETHI ITEM REPORT PREVIOUS RESULTS | CURRENT RESULTS LIMITATIONS -------- -- I------------I . I ---------- I----I --------------- I ---------- I -------------------- -------------------- I------------------------------I
JC3.40 |CORE SPRAY B DISCH II IISI-35 jVT1 ITWH-67A 187-084 | Results:NONE Results:NAD NONE lC3.40 |CORE SPRAY B DISCH | 11 |ISI-35 IVT3 ITWH-67A 187-056 | Results:N/A | ResuLts:NAD NONE |C3.40 |HPCI WTR DISCH. II IISI-31 IVT3 ICIAK-45 187-012 1 Resutts:N/A | Results:NAD NONE IC3.40 |RHR DISCHARGE A | I |ISI-41 IMT ITWH-173 187-150 Results:N/A Results:NAD NONE 1C3.40 IRHR DISCHARGE A | I |ISI-41 IVT1 ITWH-173 87-151 Results:N/A Resutts:NAD NONE IC3.40 (RHR DISCHARGE A | II |ISI-41 IVT3 ITWH-173 187-153 1 Results:N/A | Results:IND SEE REPORT 87-153R FOR REPAIR I I I I I I I i I Type:THRD ENG'T I I I I I I I I IAx Loc: I I I I I I I I I Circ Loc: I I I I I I I I I Length: JC3.40 |RHR DISCHARGE A I II |ISI-41 |VT3 ITWH-173 187-153R I ResuLts:N/A Results:IND NONE
I I I I I I I I Type:DRWG COMPL I I I I I I I I I Ax Loc: I I I I I I I 1 I ICirc Loc: I I I .I I I I I Length: I |C3.40 |RHR SUCTION A | II |ISI-40 MT ITWH-1 187-087 | Results:N/A ResuLts:NAD NONE |C3.40 |RHR SUCTION A | II |ISI-40 IVT1 ITWH-1 187-094 | Results:N/A Resutts:NAD NONE |C3.40 |RHR SUCTION A | II |ISI-40 jVT3 ITWH-1 187-054 | Results:N/A Results:NAD NONE |C3.40 |RHR SUCTION A I II |ISI-40 IMT |TWH-3 187-086 | Results:N/A I ResuLts:NAD NONE IC3.40 |RHR SUCTION A I II |ISI-40 IVT1 |TWH-3 187-095 1 Resutts:N/A Results:NAD NONE IC3.40 IRHR SUCTION A II jISI-40 |VT3 |TWH-3 187-052 1 Results:N/A Results:NAD NONE |C3.40 |RHR SUCTION B 1 II |ISI-42 |MT ITWH-16A 187-259 1 Resutts:NONE ResuLts:NAD NONE |C3.40 |RHR SUCTION B II |ISI-42 IVT1 ITWH-16A 187-268 1 Results:NONE ResuLts:NAD NONE IC3.40 |RHR SUCTION B II IISI-42 IVT3 ITWH-16A 187-276 | Results:NONE | ResuLts:NAD NONE |C3.50 |CORE SPRAY A II 1ISI-34 IVT3 |SS-27 187-018 | Results:NONE I Results:IND SEE REPORT 87-327 FOR RELOOK I I I I I I I I IType:DWG COMPL I
I I I I I I I I Ax Loc: I I I I I I I I I ICirc Loc: I I I I I I I I I Length: IC3.50 CORE SPRAY A I II |ISI-34 |VT3 ITWH-53 187-017 | Resutts:IND | Results:NAD INONE I I I I I I I I Type:NO DRAWING I I I I I I I IAx Loc: I I I I I I I I Circ Loc: I I I I I I I I I Length: 1C3.50 CORE SPRAY A 1 II ISI-34A |VT3 ICSAK-32A 187-019 | Results:IND ResuLts:NAD INONE I I I I I I I I Type:NO DRAWING I I I I I I I IAx Loc: I I I I I I I ICirc Loc: I I I I I I I ILength:
Page 2 of 10
S.
TABLE S-II NORTHERN STATES POWER COMPANY
SUB-ITEMI SYSTEM ICLASS I ISO IMETHI ITEM I REPORT | PREVIOUS RESULTS CURRENT RESULTS | LIMITATIONS
I-------- I--------------------I----- I ---------- I----I ---------------- I ---------- I -------------------- I-------------------- I---------------------- ---JC3.50 |CORE SPRAY A DISCH 1 II JISI-34 |VT3 ISR-58 187-326 1 Resutts:NONE Results:NAD INONE JC3.50 |CORE SPRAY A DISCH | II 1ISI-34 IVT3 ITWH-83 187-320 I Results:NONE Results:NAD INONE 1C3.50 |CORE SPRAY A DISCH | II 11SI-34 JVT3 ITWH-84 187-325 1 Results:NONE j Results:IND SEE REPORT 87-396R FOR REPAIR S I I I I I I I I Type:THRD ENG'T I I I I II I IAx Loc: I I I I I I I I Circ Loc: I
I I I I I I I Length: IC3.50 |CORE SPRAY A DISCH | II |ISI-34 1VT3 ITWH-84 187-325R I Results:NONE Results:IND ENGINEER EVALUATION - ACCEPT. I I I I I I I I I Type:DRWG COMPL I I I I I I I I IAx Loc: I I I I I I I I I Circ Loc: I I I I I I I I I I Length: IC3.50 |CORE SPRAY B DISCH | II ISI-35 |VT3 ITWH-66A 187-423 1 Results:NONE Results:NAD INONE 1C3.50 |CORE SPRAY B DISCH | II JISI-35A IVT3 ICSBK-35 187-321 1 Results:NONE Resutts:NAD NONE 1C3.50 |CORE SPRAY B SUCTIONI II |ISI-35 |VT3 ITWH-57 187-053 1 ResuLts:N/A Results:NAD INONE IC3.50 |CORE SPRAY B'SUCTIONJ II IISI-35 |VT3 |TWH-58 187-055 1 ResuLts:NONE Results:NAD NONE JC3.5o ICORE SPRAY SUCTION 1 I |ISI-34 |VT3 ISS-27 187-327 | Results:N/A | ResuLts:NAD NONE JC3.50 ICORE SPRAY SUCTION | II 1ISI-34 |VT3 ITWH-52 187-319 I Results:NONE I Results:NAD NONE 1C3.50 |HPCI STEAM | II |ISI-32 |VT3 ITDAK-13 187-147 | Results:NONE I Results:NAD NONE JC3.50 |HPCI STEAM 1 I JISI-32 |VT3 ITDAK-16 187-396 | Results:NONE | Results:IND ISEE REPORT 87-396R FOR REPAIR I I I I I I I I I Type:THRD ENG'T
I I I I I I I IAx Loc: I I I I I I I I ICirc Loc: 1 I I I I I I I ILength: |C3.50 |HPCI STEAM I II ITSI-32 |VT3 ITDAK-16 187-396R I Results:NONE | ResuLts:IND ENGINEER EVALUATION - ACCEPT. I I I I I I I I I Type:DWRG COMPL I I I I I I I I IAx Loc:
I I I I I I I I Circ Loc: 1 1 I I I I I I I ILength: 1C3.50 |HPCI STEAM 1 II JISI-32 |VT3 ITDAK-17 187-394 1 Results:NONE Results:NAD INONE 1C3.50 IHPCI STEAM 1 II IISI-32 |VT3 ITDAK-5 187-146 1 Results:NONE | Results:NAD INONE 1C3.50 |HPCI WATER DISCHARGE| II |ISI-31 JVT3 ICIAK-25 187-155 | Results:NONE Results:NAD NONE JC3.50 |HPCI WATER DISCHARGE| II |ISI-31 JVT3 ICIAK-50 187-395 | Results:NONE Results:NAD INONE |C3.50 IHPCI WATER DISCHARGE| II IISI-31 jVT3 ICIAK-59A 187-145 | Results:NONE I ResuLts:NAD NONE 1C3.50 IHPCI WATER DISCHARGE| II |ISI-31 jVT3 |TWH-36 187-181 | Results:N/A ResuLts:NAD NONE
I _ I _I I __ I II I I I
Page 3 of 10
I *
TABLE S-II NORTHERN STATES POWER COMPANY
-----.--..-.--.------..............--.----..-----........-----..-------.-.---.......--.--------.-------------------------------------------------------- I SUB-ITEMI SYSTEM ICLASS I ISO IMETHI ITEM I REPORT I PREVIOUS RESULTS | CURRENT RESULTS | LIMITATIONS
-------- I-------------------I------I---------- I----I --------------- I----------I----------------- -- ------------------ I1----------------------------- I 1C3.50 |HPCI' WTR DISCH. 1 II ISI-31 IVT3 ICIAK-26 |87-022 | ResuLts:NONE | Results:NAD NONE 1C3.50 IHPCI WTR DISCH. 1 II JISI-31 IVT3 ICIAK-37 187-026 | Results:NONE Resutts:NAD NONE 1C3.50 jHPCI WTR DISCH. | II jISI-31 IVT3 ICIAK-40 187-025 | ResuLts:NONE Results:NAD INONE JC3.50 (HPCI WTR DISCH. | II JISI-31 JVT3 ICIAK-48A 187-013 | ResuLts:NONE Resutts:IND fENGINEER EVALUATION - ACCEPT. I I I I I I .I I I Type:EXTRA PLT S I I I I I I I IAx Loc:
I I I I I I I Circ Loc: I I I I I I I I I Length: IC3.50 jHPC[ WTR DISCH. | II |ISI-31 VT3 ICIAK-50 187-014 | ResuLts:NONE | Results:NAD NONE IC3.50 |HPC[ WTR DISCH. | II |ISI-31 |VT3 ICIAK-52 187-015 | Results:N/A j ResuLts:IND SEE REPORT 87-015R FOR REPAIR
I I I I I I I I I Type:LOAD SET I I I I I I I I IAx Loc: I I I I I I I I I Circ Loc: I I I I I I I I I Length: |C3.50 IHPCI WTR DISCH. 1 I |ISI-31 IVT3 ICIAK-52 187-015R I Results:N/A | ResuLts:NAD NONE |C3.50 IHPCI WTR DISCH. j II |ISI-31 1VT3 ICIAK-59 187-008 1 Results:NONE ResuLts:NAD NONE |C3.50 IHPC1 WTR DISCH. II 1ISI-31 IVT3 ITWH-39 187-024 1 Results:N/A | Results:NAD INONE |C3.50 IHPCI WTR DISCH. II JISI-31 IVT3 ITWH-40 187-023 1 Results:N/A Results:NAD INONE IC3.50 IMAIN STEAM B II 1JISI-27 jVT3 jMSBK-51 187-223 | Results:N/A I Results:IND SEE REPORT 87-223R FOR REPAIR I I I I I I I I I Type:BLT LOOSE I I I I I I I I I Ax Loc: 1 I I I I 1 I I I Circ Loc: 1 I I I I I I I ILength: I 1C3.50 IMAIN STEAM B 1 II |ISI-27 |VT3 IMSBK-51 187-223R I Resutts:N/A I ResuLts:NAD NONE 1C3.50 IMAIN1 STEAM B 1 II JISI-27 |VT3 IMSBK-53 187-222 1 Resutts:N/A I ResuLts:IND SEE REPORT 87-222R FOR REPAIR I I I I I I I I I Type:MARKERS I I I I I I I I IAx Loc: I I I I I I I I ICirc oc II I I I I I I I I I Length: 1C3.50 |MAIN STEAM B II ISI-27 jVT3 IMSBK-53 187-222R I Results:N/A | Results:NAD INONE 1C3.50 |MAIN STEAM C II JISI-28 |VT3 IMSCK-43 187-143 | Results:N/A | Results:IND INUTS TACK WELDED SEE 87-143R
II | | | Type:THRD ENG'T I I I I I I I I IAx Loc: I I I I I I I I I Circ Loc: I I I I I I I I I Length:
Page 4 of 10
. I
I TABLE S-II NORTHERN STATES POWER COMPANY
I-------------------------------------------------------------------------------------------------------------------------------------------------------I ISUB-ITEMI SYSTEM ICLASS I ISO IMETHI ITEM REPORT PREVIOUS RESULTS I CURRENT RESULTS I LIMITATIONS I.--- ---- ---------------- I------I -- -------- ----1---------------1---------- --------------------- 1--------------------I------------------------------I JC3.50 |MAIN STEAM C | II IISI-28 IVT3 IMSCK-48 187-144 1 ResuLts:N/A j Results:IND INUTS TACK WELDED SEE 87-144R I I I I I I I I I Type:THRD ENGIT I I I I I I I I Ax Loc:
I I I I I I I I Circ Loc: I I I I I I I I ILength: |C3.50 JMAIN STEAM C II |ISI-28 IVT3 IMSCK-48 187-144R I Results:N/A Resutts:IND ENGINEER EVALUATION - ACCEPT. I I I I I I I I I Type:THRD ENG'T I I I I I I I I IAx Loc:
I I I I I I I I Circ Loc: 1 I I I I I I I ILength: I |C3.50 |RCIC STEAM DISCHARGE| II IISI-38 |VT3 IRSH-14 |87-414 1 Resutts:N/A Results:NAD INONE 1C3.50 JRCIC STEAM DISCHARGE| II ISI-38 |VT3 IRSH-15 |187-219 1 Results:N/A | Resutts:NAD INONE IC3.50 IRCIC WATER SUCTION 1 II JISI-38 |VT3 ITW-25 187-217 1 Results:NONE Results:IND ISEE REPORT 87-217R FOR REPAIR I I I I I I I I I Type:THRD ENGIT I I I II I I IAx Loc: I I I I I I .I 1 I Cire Loc: I I I I I I I I I Length: 1C3.50 IRCIC WATER SUCTION 1 II |ISI-38 IVT3 ITW-25 |87-217R I Results:NONE | Results:NAD NONE IC3.50 jRHR DISCH. B | II |1SI-43 |VT3 ISR-24 187-016 1 Results:N/A I Results:IND SEE REPORT 87-016R FOR REPAIR
I I I I I .I I Type:DWG COMPL I I I I I I I I IAx Loc: I I I I I I I I I Circ Loc: I I I I I I I I I Length: JC3.50 |RHR DISCH. B 1 II 1ISI-43 IVT3 ISR-24 187-016R I ResuLts:N/A I ResuLts:NAD NONE 1C3.50 RHR DISCHARGE A II |ISI-41 jVT3 ITWH-59 187-099 1 Resutts:N/A Results:NAD NONE 1C3.50 IRHR DISCHARGE A II |ISI-41 jVT3 ITWH-59A 187-101 | Results:NONE I ResuLts:NAD NONE IC3.50 jRHR DISCHARGE A 1 II 1ISI-41 IVT3 ITWH-62A 187-051 | Results:N/A ResuLts:NAD INONE IC3.50 JRHR DISCHARGE A 1 II |ISI-41 jVT3 ITWH-64 187-049 | Resutts:N/A Results:NAD INONE 1C3.50 |RHR DISCHARGE A 1 II |ISI-41 JVT3 ITWH-64A 187-050 1 Resutts:NONE Results:NAD NONE IC3.50 IRHR DISCHARGE A 1 II 1ISI-41 jVT3 ITWH-65 187-102 1 Results:N/A Results:NAD INONE 1C3.50 IRHR DISCHARGE A II |ISI-41 jVT3 ITWH-65A 187-048 I Results:N/A Resutts:NAD INONE 1C3.50 |RHR DISCHARGE A 1 II 1ISI-41 (VT3 JTWH-73A 187-215 | Results:NONE Resutts:NAD INONE 1C3.50 |RHR DISCHARGE A 1 II IISI-41 |VT3 jTWH-73B 187-216 | Results:NONE Resutts:NAD INONE 1C3.50 |RHR DISCHARGE B I 1I |ISI-43 JVT3 ITWH-632 187-209 | Results:NONE Resutts:NAD |NONE jC3.50 |RHR DISCHARGE B 1 II |ISI-43 |VT3 ITWH-94 187-210 | Results:NONE Results:NAD |NONE
_ I I I _ I IIII_ II~II
Page 5 of 10
I . I *
NORTHERN STATES POWER COMPANY TABLE S-II
------------------------------------------------------------------------ I-------------...................................................................SUB-ITEMI SYSTEM ICLASS I ISO IMETHI ITEM I REPORT | PREVIOUS RESULTS | CURRENT RESULTS I LIMITATIONS -------- I.--------------------I------I---------- I----1---------------I----------I-------------------- -------------------- I------------------------------I
IC3.50 IRHR DISCHARGE B 1 11 ISI-43 JVT3 ITWH-94A 187-274 | Results:N/A ResuLts:NAD NONE IC3.50 |RHR DISCHARGE B 1 I |ISI-43 fVT3 ITWH-95 187-214 1 Results:NONE Results:NAD NONE IC3.50 |RHR DISCHARGE B | I |ISI-43 |VT3 ITWH-98 187-213 1 Results:N/A Resutts:NAD NONE |C3.50 |RHR SERV. WTR I II JISI-39 |VT3 ISWAK-25 187-007 | Results:IND Results:NAD NONE I I I I I I I Type:LOOSE NUT I I I I I I I IAx Loc: I
I I I I I ICirc Loc: II I I I I I I Length: II JC3.50 jRHR SERV.WTR I 1 ISI-39 IVT3 ISWAK-20 187-006 | Results:N/A ResuLts:NAD INONE
1C3.50 IRHR SUCTION A I |ISI-40 |VT3 |TWH-2 187-100 | Results:N/A ResuLts:NAD INONE 1C3.50 IRHR SUCTION B 1 II 1ISI-42 |VT3 ITWH-12 187-021 | Resutts:N/A Results:NAD NONE JC3.50 IRHR SUCTION B 1 II 1JISI-42 |VT3 ITWH-12 187-275 | Results:N/A Results:NAD NONE JC3.50 IRW FROM SKIMMER 1 II ISI-36 IVT3 IRWAK-35 187-027 1 Results:N/A ResuLts:NAD NONE IC3.50 SUPPLY TO STEAM SEAL II 11ISI-30 fVT3 ISSAK-14A 187-221 | Results:N/A Resutts:NAD NONE 1C3.50 SUPPLY TO STEAM SEALI II |ISI-30 |VT3 ISSAK-21 187-220 | Results:N/A Results:NAD INONE IC3.50 |SUPPLY TO STEAM SEALI II |ISI-30 |VT3 ISSAK-22 187-399 | Results:N/A | Resutts:NAD INONE 1C3.70 |RHR PUMP A 1 II 1ISI-48 |MT IP202A MNT FT 2 j87-089 1 Results:N/A f Results:NAD (SIDE 2 INACCESSABLE fC3.70 IRHR PUMP A I 1|ISI-48 |VT1 IP202A MNT FT 2 187-092 1 Results:N/A I Resutts:NAD ISIDE 2 INACCESSABLE IC3.70 jRHR PUMP A I 1I JISI-48 |VT3 |P202A MNT FT 2 187-046 1 Results:N/A I Results:NAD INONE fC3.70 JRHR PUMP C 1 II 1ISI-48 IMT |P202C MNT FT 2 187-088 | Results:N/A I Results:NAD |SIDE 2 INACCESSABLE 1C3.70 IRHR PUMP C I 1 IISI-48 |VT1 |P202C MNT FT 2 187-093 | Results:N/A | Results:NAD |SIDE 2 INACCESSABLE 1C3.70 jRHR PUMP C 1 II ISI-48 |VT3 |P202C MNT FT 2 187-045 | Results:N/A I ResuLts:NAD |NONE |C3.80 IRCIC PUMP I 1 IISI-47 |VT3 ISUPPORT C 187-424 | ResuLts:N/A I Results:NAD |NONE |C3.80 IRCIC PUMP 1 II 1ISI-47 |VT3 ISUPPORT D 187-218 1 Results:N/A I Resutts:NAD INONE (C5.11 |CONTAINMENT SPRAY B II 1ISI-44 JMT |-18 187-420 | Results:NONE I Results:NAD INONE fC5.11 |CONTAINMENT SPRAY B II ISI-44 JVT1 |W-18 187-422 | Results:NONE I Results:NAD INONE (C5.11 |CORE SPRAY B DISCH 1 II 1ISI-35 MT |W-564 187-269 | Results:N/A I Results:NAD INONE |C5.11 |CORE SPRAY B DISCH I I ISI-35 |VT1 |W-564 187-270 | Results:N/A I Results:NAD INONE JC5.11 |CORE SPRAY .B SUCTION1 II 11SI35 |MT jW-654 187-076 | Results:N/A I ResuLts:NAD NONE |C5.11 ICORE SPRAY B SUCTION1 II IISI-35 |VT1 IW-654 187-081 1 Results:N/A ResuLts:NAD NONE 1C5.11 |CORE SPRAY B SUCTIONI II ISI-35 |MT |W-8F 187-075 1 Results:N/A ResuLts:NAD NONE JC5.11 ICORE SPRAY B SUCTIONI II ISI-35 jVT1 |W-8F .187-080 | Results:N/A Results:NAD NONE JC5.11 IRCIC WATER DISCHARGE1 II IISI-38 IMT |W-227 187-397 | Results:N/A Results:NAD INONE 1C5.11 IRCIC WATER DISCHARGEI II ISI-38 |VT1 W-227 187-398 | Results:N/A Results:NAD INONE IC5.11 |RHR DISCHARGE A 1 II 11ISI-41 |MT jW-12 187-165 1 ResuLts:N/A Results:NAD INONE 1 _ _1_I I_ _II_ _LII I
Page 6 of 10
I , I .
NORTHERN STATES POWER COMPANY MONTICELLO Unit I Examination Comp:,ison summary
----------------------------------------------------------------------------------------------------------------------SUB-ITEMI SYSTEM ICLASS I ISO IMETHI ITEM I REPORT I PREVIOUS RESULTS CURRENT RESULTS LIMITATIONS ------ I----------------I- I------ ------------ I------ I------------I---------- -- I -----------------
JC5.11 |RHR DISCHARGE A 1 II |ISI-41 |MT IW-12 187-165 Resutts:N/A I Resutts:NAD INONE 1C5.11 IRHR DISCHARGE A 1 II |1SI-41 JVT1 (W-12 87-168 1 Results:N/A I Resutts:NAD NONE 1C5.11 |RHR DISCHARGE A | II 1JISI-41 |MT lW-13 187-167 1 Resutts:N/A I Resutts:NAD INONE JC5.11 |RHR DISCHARGE A | II ISI-41 VT1 IW-13 187-170 1 Resutts:N/A Resutts:NAD NONE JC5.11 jRHR DISCHARGE A | II |ISI-41 MT IW-3 87-419 Resutts:N/A Results:NAD PAINTED SURFACE JC5.11 IRHR DISCHARGE A | II jISI-41 VT1 JW-3 187-421 1 Resutts:N/A Resutts:NAD INONE |C5.11 IRHR DISCHARGE A 1 II IISI-41 MT IW-362 87-085 1 Resutts:N/A Results:NAD WELDED SUPPORT @ 6 O'CLOCK. |C5.11 IRHR DISCHARGE A I II IISI-41 IVT1 IW-362 187-096 1 Resutts:N/A Resutts:NAD 12.25- WELDED SUPPORT @ 6:00. |C5.11 (RHR DISCHARGE A | II ISI-41 MT IW-367 187-077 1 Results:N/A Results:NAD IPAINTED SURFACE |C5.11 IRHR DISCHARGE A | II JISI-41 jVT1 (W-367 187-082 1 Results:N/A Results:NAD PAINTED SURFACE |C5.11 IRHR DISCHARGE A 1 II ISI-41 IMT |W-374 187-166 1 Results:N/A Resutts:NAD INONE fC5.11 IRHR DISCHARGE A | II ISI-41 |VT1 IW-374 187-169 1 Results:N/A Resutts:NAD NONE |C5.11 |RHR DISCHARGE B 1 II ISI-43 IMT |W-22 187-428 1 Results:N/A ResuLts:NAD INONE
.|C5.11 |RHR DISCHARGE B 1 1 JISI-43 |VT1 IW-22 187-427 1 Resutts:N/A ResuLts:NAD NONE |C5.11 |RHR DISCHARGE B II |ISI-43 IMT IW-25A 187-249 1 Results:N/A Resutts:NAD IPAINTED SURFACE |C5.11 |RHR DISCHARGE B 1 11 JISI-43 |VT1 W-25A 187-248 1 Resutts:N/A I Results:NAD NONE |C5.11 |RHR DISCHARGE B | II 11ISI-43 MT IW-313 187-262 1 Results:N/A I Resutts:NAD NONE JC5.11 IRHR DISCHARGE B I II jISI-43 |VT1 IW-313 187-265 1 Resutts:N/A I Resutts:NAD INONE |C5.11 |RHR DISCHARGE B | II |ISI-43 IMT IW-323 187-260 1 Results:N/A Resutts:NAD NONE 1C5.11 IRHR DISCHARGE B | II |ISI-43 |VT1 IW-323 187-267 1 Resutts:N/A Resutts:NAD INONE JC5.11 |RHR DISCHARGE 8 | II IISI-43 jMT IW-329 187-261 1 Resutts:N/A Resutts:NAD INONE 1C5.11 fRHR DISCHARGE B I 11ISI-43 |VT1 |W-329 187-266 1 Resutts:N/A I Results:NAD NONE 1C5.11 IRHR SUCTION A II ISI-40 jMT |W-7 187-078 1 Results:N/A Results:NAD IPAINTED SURFACE 1C5.11 |RHR SUCTION A 1 II 1ISI-40 |VT1 |1-7 187-083 1 Resuts:N/A Resutts:NAD NONE |C5.21 IMAIN STEAM B II jISI-27 MT IMSBJ-43 187-043 1 Resutts:N/A Results:NAD IPAINTED SURFACE JC5.21 |MAIN STEAM B | II |ISI-27 IUT4 IMSBJ-43 187-097 1 Resutts:N/A Resutts:GEO NONE 1 I III 1
I I I I I IEO. I I I I I IAmptitude:30 I I I I I ILoc: .6
I I I I ILoc:7. I I I I ILength:7. (C5.21 JMAIN STEAM B 1 II ISI-27 IVT1 IMSBJ-43 187-044 1 Resutts:N/A Resutts:NAD INONE 1C5.21 |MAIN STEAM B 1 II 1ISI-27 |MT IMSBJ-57 187-425R I Resutts:N/A Resutts:NAD NONE |C5.21 IMAIN STEAM B 1 II 1ISI-27 IMT IMSBJ-57 187-425 1 Resutts:N/A Results:IND ISEE REPORT 87-425R FOR REPAIR I I I I I IType:MULTIPLE I I I I I ILoc:
I I I I ILoc: I I I I Length:
Page 7 of 10
Page 8 of 10
NORTHERN STATES POWER COMPANY | MONTICELLO Unit I Examination comparison summary ----------------------------------------------------------------------------------------------------------------------SUB-ITEMI SYSTEM |CLASS I ISO IMETHI ITEM I REPORT I PREVIOUS RESULTS CURRENT RESULTS LIMITATIONS
1-------- I--------------------I------1----------1 I -------------- I ---------- I..... -------------------- I ----------------JC5.21 jMAIN STEAM B | II ISI-27 |UT4 IMSBJ-57 187-409 1 Resutts:N/A Resutts:NAD INONE JC5.21 |MAIN STEAM B 1 II ISI-27 |VT1 IMSBJ-57 187-426 1 Results:N/A ResuLts:NAD NONE JC5.21 MAIN STEAM C I 1 IISI-28 |MT IMSCJ-46 187-140 1 Results:N/A Results:NAD IPAINTED SURFACE |C5.21 (MAIN STEAM C II |ISI-28 |UT4 IMSCJ-46 187-142 1 Results:N/A Resuts:NAD NONE (C5.21 |MAIN STEAM C II iISI-28 IVT1 IMSCJ-46 187-139 Resutts:N/A Resutts:NAD NONE |C5.21 fSUPPLY TO STEAM SEALI | IISI-30 IMT ISSAJ-19 187-250 1 Resutts:N/A Resutts:NAD IPAINTED SURFACE JC5.21 |SUPPLY TO STEAM SEAL II JISI-30 IVT1 ISSAJ-19 187-251 1 ResuLts:N/A Resutts:NAD NONE |C5.31 JRHR SUCTION B II ISI-42 |MT |W-939 187-263 1 Results:N/A Results:NAD NONE fC5.31 |RHR SUCTION B | II ISI-42 JVT1 IW-939 187-264 1 Results:N/A Resutts:NAD NONE |MISC CRD TO RWCU 1 I |ISI-51 |PT W-11 187-225 1 Results:NONE Results:NAD NONE |MISC JCRD TO RWCU 1 II JISI-51 |UT4 lW-11 187-234 1 Resutts:NONE Resutts:NONE IS-2 LIMITED To 3/4"-TEE CONFIG |MISC |CRD TO RWCU | II |ISI-51 IVT1 lW-11 187-233 1 Results:NONE Results:NAD NONE fMISC JCRD TO RWCU 1 II j ISI-51 IPT |W-12 187-224 1 Results:NONE Results:NAD INONE MISC (CRD TO RWCU | I |ISI-51 IUT4 |W-12 187-235 1 Results:NONE Results:NAD NONE MISC |CRD TO RWCU | II JISI-51 IVT1 IW-12 187-232 1 Results:NONE Resutts:NAD INONE MISC JCRD TO RWCU 1 I |ISI-51 IPT IW-13 187-228 1 Resutts:NONE Results:NAD NONE MISC |CRD TO RWCU 1 II |ISI-51 |UT4 IW-13 187-237 1 Results:NONE Results:NAD NONE MISC |CRD TO RWCU 1 I JISI-51 IVT1 (W-13 187-231 1 Results:NONE Resutts:NAD INONE IMISC JCRD TO RWCU | I |ISI-51 |PT IW-14 187-227 1 Results:NONE I Results:NAD NONE MISC |CRD TO RWCU 1 II jISI-51 jUT4 jW-14 187-236 1 Resutts:NONE I Resutts:NAD INONE IMISC |CRD TO RWCU | II |ISI-51 |VT1 IW-14 187-230 1 Resutts:NONE Results:NAD INONE MISC JCRD TO RWCU 1 II ISI-51 IPT lW-7 187-226 1 Results:NONE I Resutts:NAD NONE MISC |CRD TO RWCU 1 11 ISI-51 |UT4 |W-7 187-238 1 Resutts:NONE Results:NAD INONE MISC ICRD TO RWCU | II 1JISI-51 jVT1 JW-7 187-229 1 Results:NONE Results:NAD NONE MISC |FW TO RWCU TO HPCI I II IISI-37 |MT |W-1 187-063 Resutts:NONE Resutts:NAD INONE MISC jFW TO RWCU TO HPCI 1 1 |ISI-37 JUT4 lW-1 87-069 Results:NONE Resutts:GEO SCAN LIMITED TO 1.6" BY W-2.
I I I I Iscan:2 I I I I IGEO. I I I I IAmlitude:3 I I I I ILoc:.95 I I I I ILoc:2.5 I I I I ILength:.75
MISC |FW TO RWCU TO HPCI 1 II IISI-37 |VT1 lw-1 187-057 1 Results:NONE I Resutts:NAD NONE MISC jFW TO RWCU TO HPCI 1 II |ISI-37 IMT lW-12 187-067 Resutts:NONE I Resutts:NAD INONE
(MISC |FW TO RWCU TO HPCI | II |ISI-37 JUT4 |W-12 187-073 1 Results:NONE I Resutts:GEO NO S-2 OBSTRUCTED BY W-12A I I I I I I
I I I I IGEO I I I I II I Amptitude: 60
IAx Loc:-I .1 S I I I ILoc:7'
SLength:360 INT. 1I I I I I
I
I I I I
-I
NORTHERN STATES POWER COMPANY TABLE S-Il MONTICELLO Unit I Examination Comparison summary
-------------------------------------------------------------------------------------------------------------------------ISUB-ITEMI SYSTEM |CLASS ISO IMETHI ITEM I REPORT I PREVIOUS RESULTS CURRENT RESULTS LIMITATIONS I---------I---------------------I------I----------1--- 1 -------------------------IMISC |FW TO RWCU TO HPCI II IISI-37 1UT4 IW-12 187-073 1 Resutts:NONE Resutts:GEO INONE I I I I I I I I I I I I IGEO I I I I IAmpitude:20 I I I I I Ioc: I I I I I ICirc Loc:36 INT.
I ILength:360NT. IMISC |FW TO RWCU TO HPCI 1 II 11ISI-37 |VT1 (W-12 187-061 1 Resutts:NONE Results:NAD INONE IMISC |FW TO RWCU TO HPCI I1 IISI-37 IMT IW-12A 187-068 1 Results:NONE Results:NAD NONE MISC IFW TO RWCU TO HPCI II 1ISI-37 JUT4 IW-12A 187-074 1 Resutts:N/A Resutts:N/A ISEE REPORT 87-073 FOR SCAN 1 MISC |FW TO RWCU TO HPCI 1 I ISI-37 IUT4 IW-12A 187-074 1 Results:NONE Results:N/A SEE REPORT 87-073 FOR SCAN 2 IMISC IFW TO RWCU TO HPCI II ISI-37 jUT4 IW-12A 187-074 1 Results:NONE Resutts:NONE jS-3 TEE LIMITATION & WELD 12 MISC |FW TO RWCU TO HPCI II 1ISI-37 IUT4 IW-12A 187-074 Results:NONE Resutts:NONE IS-4 COVRD BY ULD 12, .7" UPSTMI MISC IFW TO RWCU TO HPCI I 1 IISI-37 JVT1 IW-12A 187-062 1 Resutts:NONE Results:NAD IN/A MISC [FW TO RWCU 10 HPCI II ISI-37 IMT JW-2 187-064 1 Results:NONE Resutts:NAD NONE MISC |FW TO RWCU TO HPCI II 1ISI-37 IUT4 |W-2 187-070 1 Resutts:NONE Results:GEO ISCAN LIMITED TO 1.6- BY W-1
I I I I IScan: I I I I I IEO. I I I I I IAmptitude:55 I I I I Loc:. I I I I I I15 SI I ILength:.5 IMISC |FW TO RWCU TO HPCI | II |ISI-37 |UT4 |W-2 187-070 1 Results:NONE Results:GEO NO SCAN 2 TEE CONFIGURATION I I I I I IScan:
I I I I ITPe:GEO. I I I I I IAmplitude:50
I I I I ILoc: I I I I I ILoc: I I I I Length: MISC |FW TO RWCU TO HPCI I 1I 1ISI-37 IVT1 |W-2 187-058 I Resutts:NONE Resutts:NAD NONE MISC |FW TO RWCU TO HPCI 1 II ISI-37 IMT fW-3 187-066 1 Resutts:NONE Resutts:NAD INONE MISC IFW TO RWCU TO HPCI II 1ISI-37 |UT4 |W-3 187-071 1 Results:NONE Resutts:NAD IS-2 LMTD BY W-12,1.81 & NO S-1 IMISC IFW TO RWCU TO HPCI 1 II 11ISI-37 JVT1 jW-3 187-060 1 Resutts:NONE Resuits:NAD INONE IMISC IFW TO RWCU TO HPCI 1 II ISI-37 IMT jW-4 187-065 1 Resutts:NONE Resutts:NAD INONE IMISC jFW TO RWCU TO HPCI 1 II JISI-37 |UT4 |W-4 187-072 1 Resuits:NONE Resutts:GEO INONE
I I I I II I I I I I IGEO I I I I I IAmpitude:<20 I I I I I ILoc: I I I I I ICirc Loc:36 INT S I I I Length:360NT
Page 9 of 10
TABLE S-II NORTHERN STATES POWER COMPANY
I MONTICELLO Unit I Examination Comparison summary ------- I---------------------------------------------------------------------------------------- *-------- *----------------I SUB-ITEMj SYSTEM ICLASS I ISO IMETHI ITEM REPORT PREVIOUS RESULTS CURRENT RESULTS LIMITATIONS ------ I------------- ----- I ------- I----I ----------- I ------- I ------------- ---------------- I----------------------|MISC IFW TO RWCU TO HPCI II jISI-37 IUT4 jW-4 187-072 | Results:NONE I Results:N/A INO SCAN TEE CONFIGURATION. JMISC IFW TO RWCU TO HPCI II IISI-37 jVT1 IW-4 187-059 1 Results:NONE Resutts:NAD NONE 11I I I I I I I- 1 1
Page 10 of 10
NORTHERN STATES POWER COMPANY MONTICELLO UNIT I ISOMETRIC SUMMARY CLASS II
NSP ISO REVISION LOOP NUMBER NUM3ER COMPONENT OR SYSTEM DESIG
MAIN STEAM
MAIN STEAM
MAIN STEAM
MAIN STEAM
SUPPLY TO STEAM SEAL SYSTEM
MAIN STEAM EQUALIZER HEADER
HIGH PRESSURE COOLANT INJECTION WATER SIDE DISCHARGE
ISI-26
ISI-27
ISI-28
ISI-29
ISI-30
ISI-30A
ISI-31
ISI-31A
ISI-32
ISI-33
INJECTION
INJECTION
INJECTION
A
B
C
D
PS1-18"ED
PS2-18"ED
PS3-18"ED
PS4-18"ED
PS14-6"ED PS13-6"ED PS12-6"ED PS11-6"ED PS1O-5"ED PS7-10"ED PS7-8"ED
PS30-18"ED DRIP LEG
TW3-12"ED
TWI-14"HE C16-14"HE
PS18-8"ED
RS2-20"HE RS2-18"HE RS2-16"HE
TABLE III PAGE 1 OF 4
UT-CAL STD
8
8
8
8
6 6 6 6 34 28 21
8 28
29 43
41 41
5
38 39 31
HIGH PRESSURE COOLANT WATER SIDE SUCTION
HIGH PRESSURE COOLANT STEAM SIDE
HIGH PRESSURE COOLANT STEAM SIDE DISCHARGE
NORTHERN STATES POWER COMPANY MONTICELLO UNIT I ISOMETRIC SUMMARY CLASS II
COMPONENT OR SYSTEM
CORE SPRAY
CORE SPRAY DISCHARGE
CORE SPRAY
CORE SPRAY DISCHARGE
NSP ISO NUMBER
ISI-34
ISI-34A
ISI-35
ISI-35A
ISI-36
ISI-37
ISI-38
ISI-39
ISI-40
REVISION NUMBER
2
1
2
1
3
3
2
3
2
FEEDWATER
REACTOR CORE COOLANT
INJECTION
RHR SERVICE WATER
RHR SUCTION
LOOP DESIG
A A
A A A
B B
B B B
A B
A A A A A
LINE NUMBER
TW6-12"HE TW7-10"HE
TW7-8"ED TW7-10"GE TW8-8"GE
TW10-12"HE TW11-10"GE
TW11-8"ED TW11-10"GE TW12-8"GE
REW11-8"HE
FW2A-14"ED FW2B-14"ED
TW5-6"HE C17-6"HE RS3-8"HE
SW9-8"GE
REW10-18"HE TW14B-20'HE TW16-14"HE TW18-14"HE TW28-20"HE
TABLE III PAGE 2 OF 4
LINE SIZE
12" 10"
8" 10" 8"
12" 10"
8" 10" 8"
8"
14" 14"
6" 6" 8"
8"
18" 20" 14" 14" 20"
REACTOR WATER SYSTEM
FROM SKIMMER
WALL THICK
.375"
.365"
.500"
.3655"
.322"
.375"
.365"
.500"
.365"
.322"
.322"
.937"
.937"
.280"
.280"
.322"
.322"
.375"
.375"
.375"
.375"
.375"
UT-CAL STD
42 32
5 32 33
42 32
5 32 33
33
23 23
44 44 33
33
39 38 41 41 38
I
NORTHERN STATES POWER COMPANY MONTICELLO UNIT I ISOMETRIC SUMMARY CLASS II
TABLE III PAGE 3 OF 4
*iCfl Ten flriirr',nLm 1 1
NUMBER COMPONENT OR SYSTEMLOOP
DESIGI ~ ~~ I _____
RHR DISCHARGE
RHR SUCTION
RHR DISCHARGE
CONTAINMENT SPRAY
ISI-41
ISI-42
ISI-43
ISI-44
ISI-45
ISI-46
ISI-47
COOLANT INJECTION
COOLANT INJECTION
REACTOR CORE INJECTION COOLANT TURBINE AND PUMP
LINE NUMBER
TW29-10"GE TW29-14"GE TW30-14"GE TW30-16"GE TW30-16"DB
REW-18"HE TW14A-20"HE TW15-14"HE TW17-14"HE TW27-20"HE
TW19-10"GE TW19-14"GE TW20-14"GE TW20-16"GE TW20-16"DB TW22-14"GE
TW23-12"GE TW23-10"GE
TW33-12"GE TW33-10"GE
nSr 13y NUMBER
HIGH PRESSURE TURBINE
HIGH PRESSURE PUMPS
--CAL STD
32 41 41 40 10
39 38 41 41 38
32 41 41 40 10 41
42 32
42 32
I . I I . , I ,
----------
I
NORTHERN STATES POWER COMPANY MONTICELLO UNIT I ISOMETRIC SUMMARY CLASS II
TABLE III PAGE 4 OF 4
1 r - r 1----- -- -
COMPONENT OR SYSTEM
RESIDUAL HEAT REMOVAL - PUMPS
CORE SPRAY - PUMPS
RESIDUAL HEAT REMOVAL HEAT EXCHANGERS
CONTROL ROD DRIVE TO REACTOR WATER CLEANUP
NSP ISO NUMBER
ISI-48
ISI-49
ISI-50
ISI-51
REVISION NUMBER
0
0
0
0
LOOP DESIG
LINE NUMBER
I - 1
LINE SIZE
WALL THICK
UT-CAL STD
15 19
3" 3"
.300"
.438"
'I
APPENDIX C TABLE I-PERSONNEL LISTING
TABLE II-ULTRASONIC CALIBRATION BLOCKS TABLE III-PROCEDURE LISTING
TABLE VI-EQIPMENT AND MATERIALS
co
0
C? 0 a.
a.0
CONTRACTOR: Lambert, MacGill, Thomas, Inc.
NAME JOB TITLE
G.J. DAVIS TECH
L.R. DAVIS TECHNICIAN
S.J. FREELAND TECHNICIAN
D.B. MACGILL SUPERVISOR
S.D. MACGILL TRAINEE
D.B. RICHEY TECHNICIAN
G.J. STRAIT TECHNICIAN
E.L. THOMAS SUPERVISOR
W.L. THOMAS TECHNICIAN
RECERT
/ /
/ /
/ /
/ /
/ /
/ /
/ /
/ /
/ /
A.W. VOSS TECH
Page 1 of 2
MT LEVEL RECERT
II 05/01/88
PT LEVEL RECERT
II 04/01/88
PERSUNNEL ROSTER
UT LEVEL RECERT
I. 03/22/88
I0 II II 08/10/88 08/10/88102/01/90
I 04/21/90 / /
III III III 03/03/89103/03/89 01/20/89
/1/8
III 06/14/89
/0/8
III 11/09/89
II I II 09/27/88 04/17/90
/0/8
III
04/04/89 III
04/16/90
III III III 01/02/89 12/30/881 12/30/88
/ / /I
04/28/90
01/31/88101/31/88110/24/89
IGSCC QUAL?
Y
N
N
N
Y
Y
Y
N
Y
TABLE I 12/14/87
515 Aldo Ave. Santa Clara, CA 95054
VT-i LVL RECERT
II 08/06/89
/ /
/ /
/ /
/ /
VT-3 LVL VISION RECERT DUE DATE
II 08/07/89 03/02/88
//
//
//
//
II I II 04/29/88 05/01/88
II 08/06/89
III 05/13/89
/ /
/
II 08/06/89
III 05/13/89
/ /
/ /
03/11/88
04/15/88
09/22/88
09/17/88
01/22/88
06/19/88
10/09/88
01/22/88
01/19/88
REMARKS
Released 11/14/87
* .
CONTRACTOR: Lambert, MacGill, Thomas, Inc.
NAME JOB TITLE
A.S. WHEALDON TECH
ET LEVELIMT LEVELRECERT
L. J. WOOD TECHNICIAN / /
Page 2 of 2
/ /
RECERT
//
//
PT LEVEL RECERT
/2/8
I I 10/27/88
PERSONNEL ROSTER
UT LEVEL RECERT
/1/8
II 02/11/88
IGSCC QUAL?
N
VT-i LVL RECERT
/1/
/ /
VT-3 LVL RECERT
II 07/24/87
/1/
VISION DUE DATE
01/09/88
05/11/88
TABLE I 12/14/87
515 Aldo Ave. Santa Clara, CA 95054
REMARKS
I
PERSONNEL ROSTER TABLE ICONTRACTOR: 12/14/87 General Electric Company 175 Curtner Avenue Nuclear Fuel and Service Div. San Jose, CA 95125
NAME ET LEVEL MT LEVEL PT LEVEL UT LEVEL IGSCC VT-i LVL VT-3 LVL VISION REMARKS JOB TITLE RECERT RECERT RECERT RECERT QUAL? RECERT RECERT DUE DATE
K.A. EARP II II TECH / / / / / / / / 12/16/88 12/16/88 12/18/87
J.T. KEGEL TECH / / // /
II II 06/24/90 06/24/90
Page 1 of I
PERSONNEL ROSTER TABLE I CONTRACTOR: 12/14/87 Hartford Steam Boiler Insp. & Insur. Co. 300 S. Riverside Plz Special Insp. Service Div. Chicago, IL 60606 ------------------------------------------------------------------------------------ ---------
NAME ET LEVEL MT LEVEL PT LEVEL UT LEVEL IGSCC VT-i LVL VT-3 LVL VISION REMARKS JOB TITLE RECERT RECERT RECERT RECERT QUAL? RECERT RECERT DUE DATE
------------------ -------- -------- -------- ----- -------- -------- -------- ----------- -------J.A. MARKSON ANII // // // // /
Page 1 of 1
NORTHERN STATES POWER COMPANY MONTICELLO UNIT I ULTRASONIC CALIBRATION BLOCKS
NSP NO.
4
5
8
10
11
15
18
23
28
PIPE SCHEDULE & THICKNESS
80 .337"
SIZE DIA.
4"
8"
18"
16"
8"
3"
3"
14"
10"
APPENDIX C TABLE II PAGE 1 OF 3
MATERIAL
A106 GR B
A106 GR B
A106 GR B
A106
A312
A312
A312
A106
A106
GR B
TP304
TP304
TP304
GR B
GR B
80
80
80
80
80
160
100
80
.500"
.937"
.843"
.500"
.300"
.438"
.937"
.593"
SERIAL OR HEAT NO.
L42009
N53114
(122491)
N36809
15885
03052
01598
7137
N35898
CALIBRATION REPORTS
LRD-001 LRD-002 LRD-007 LRD-009 ELT-022 ELT-029
ELT-028
LRD-013 ELT-002 ELT-003 ELT-006 AWV-001
LRD-011
LRD-008
ELT-014
ELT-013
DBR-005
ELT-012
DATE
10-26-87 10-27-87 11-06-87 11-17-87 11-16-87 11-21-87
11- 13-87
11-19-87 10-28-87 10-28-87 11-02-87 11-21-87
11-18-87
11-11-87
11-09-87
11-09-87
11-13-87
11-07-87
1. . I . I I
NORTHERN STATES POWER COMPANY MONTICELLO UNIT I ULTRASONIC CALIBRATION BLOCKS
SILZE DIA.
5-5/16"
APPENDIX C TABLE II PAGE 2 OF 3
MATERIAL
A533 GR B
NSP NO.
30
37
45
47
51
56
57
59
63
65
67
70
PIPE SCHEDULE & THICKNESS
--- .500"
100 1.6195"
--- .530"
--- .875"
--- .591"
--- 1.027"
160 .906"
--- 1.096"
--- .681"
60 .750"
TP316
TP316
TP316
I
A234 GR WPB
A182 GR F 304
S336 CL F8
A515 GR 70
A312 TP304
A312 TP304
A105
A376 TP316
OD
OD
A376
A376
A376
24"
9"
3"
4,
12"
24"
8"
28"
16"
18"
12" SE
I SERIAL OR HEAT NO.
C5571
L00543
CMB
CMB
31634
12564
CMC ACY
32681
13549
13549
626390
CALIBRATION REPORTS
ELT-011 ELT-018 ELT-019 ELT-025
LRD-016
ELT-009 ELT-026 ELT-021
ELT-030
ELT-001
LRD-015
ELT-004
LRD-003 ELT-005
LRD-014
LRD-012
ELT-023
DATE
11-06-87 11-13-87 11-13-87 11-17-87
11-22-87
11-05-87 11-19-87 11-14-87
11-22-87
10-26-87
11-21-87
10-29-87
10-31-87 10-30-87
11-19-87
11-18-87
11-18-87
NORTHERN STATES POWER COMPANY MONTICELLO UNIT I ULTRASONIC CALIBRATION BLOCKS
APPENDIX C TABLE II
SPAGE 3 OF 3
SILE PIPE SCHEDULE MATERIAL SERIAL OR CALIBRATION DIA. & THICKNESS HEAT NO. REPORTS
RPV-31 3.66"
NO.
RPV-1 C2220/1
C9220
LRD-010 LRD-017 LRD-018 DBR-001 DBR-002 DBR-003 DBR-004 ELT-015 ELT-016 ELT-017 ELT-020 ELT-024 ELT-027 ELT-031 ELT-032
LRD-005 LRD-006 ELT-007 ELT-008 ELT-010
I
A533 B CL. 1
A533 B CL. 1
5-5/16"
I I 1 0 'I
DATE
11-17-87 11-23-87 11-23-87 11-04-87 11-04-87 11-12-87 11-12-87 11-10-87 11-11-87 11-11-87 11-12-87 11-17-87 11-17-87 11-23-87 11-23-87
11-03-87 11-04-87 11-03-87 11-04-87 11-05-87
r ,
NORTHERN STATES POWER COMPANY MONTICELLO UNIT I PROCEDURE LISTING
APPENDIX C TABLE III PAGE 1 OF 2
PROCEDURE NUMBER I FIELD PROCEDURE TITLE PLANT APPROVAL CHANGE DESCRIPTION AND REVISION CHANGE I I DATE
NSP-PT-1,
NSP-MT-1,
NSP-MT-2,
NSP-UT-1,
NSP-UT-2,
NSP-UT-3,
NSP-UT-3A,
NSP-UT-4B,
NSP-UT-5,
NSP-UT-6,
NSP-UT-16,
REV. 4
REV. 4
REV. 2
REV. 3
REV. 5
REV. 4
REV. 0
REV. 4
REV. 4
REV. 3
REV. 5
NONE
NONE
NONE
NONE
NONE
NONE
NONE
NONE
NONE
NONE
LIQUID PENETRANT EXAMINATION MAGNETIC PARTICLE EXAMINATION WET MAGNETIC PARTICLE EXAMINATION ULTRASONIC EXAMINATION OF PIPE WELDS AUTOMATIC DATA RECORDING ULTRASONIC EXAMINATION OF FERRITIC VESSELS ULTRASONIC EXAMINATION OF MONTICELLO REACTOR VESSEL AXIAL ULTRASONIC EXAMINATION OF STUDS AND BOLTS ULTRASONIC EXAMINATION OF REACTOR VESSEL NOZZLE FORGING INNER RADII ULTRASONIC EXAMINATION OF REACTOR VESSEL NOZZLE BORE ULTRASONIC EXAMINATION FOR INTERGRANULAR STRESS CORROSION CRACKING
10-24-87
10-24-87
10-24-87
10-24-87
10-24-87
10-24-87
10-24-87
10-24-87
10-24-87
10-24-87
10-24-87
I I I ,
NORTHERN STATES POWER COMPANY MONTICELLO UNIT I PROCEDURE LISTING
APPENDIX C TABLE III PAGE 2 OF 2
PROCEDURE NUMBER FIELD PROCEDURE TITLE PLANT APPROVAL CHANGE DESCRIPTION AND REVISION CHANGE I I DATE
NSP-VT-1.0, REV. 2 NSP-VT-2.0, REV. 1
NSP-VT-2.O, REV. 2
NSP-VT-3.0, REV. 1
NSP-VT-4.0, REV. 1
NONE NONE
NONE
VISUAL EXAMINATION VISUAL EXAMINATION OF HANGER ASSEMBLIES VISUAL EXAMINATION OF HANGER ASSEMBLIES VISUAL EXAMINATION OF PUMP AND VALVE INTERNAL PRESSURE BOUNDARY SURFACES VISUAL EXAMINATION OF MONTICELLO REACTOR VESSEL INTERIOR
10-24-87 01-08-87
10-24-87
05-02-86
10-24-87
; II . I #
NORTHERN STATES POWER COMPANY Table IV MONTICELLO Unit I EQUIPMENT & MATERIALS
ULTRASONIC INSTRUMENTS MANUFACTURER MODEL SERIAL RECALIBRATION REMARKS
NUMBER DUE DATE ------------------------- --------------- ---------------LMT SLAVE 13 1/27/87 LMT SLAVE 19 12/15/87 LMT SLAVE 20 12/16/87 NORTEC 131-D 126 1130/87 NORTEC 131-D 167 12/17/88 NORTEC 131-D 269 12/18/87 NORTEC 131-D 287 01/20/88 NORTEC 131-D 291 01/01/88 NORTEC 131-D 311 01/15/88 NORTEC 131-D 371 12/08/87
STRIP CHART RECORDERS MANUFACTURER MODEL SERIAL RECALIBRATION REMARKS
NUMBER DUE DATE ------------------------- --------------- ---------------GOULD BRUSH 220 18940 05/03/88 GOULD BRUSH 220 19016 01/16/88 GOULD BRUSH 220 19023 01/15/88 GOULD BRUSH 222 095 04/12/88
SURFACE TEMPERATURE GAUGES MANUFACTURER MODEL SERIAL TYPE REMARKS
NUMBER S---------------------------------- ----------
PTC 310F 903 PTC 310F 906 PTC 310F 910 PTC 310F 935 PTC 310F 939 PTC 310F 941 PTC 310F 949 PTC 310F 953 PTC 310F 956 PTC 310F 957 PTC 310F 961 PTC 310F 962
IMAKMIICAcrnTlif-i M MAGNETIC PARTICLE EQUIPMENTRx
MAGNAFLUX MAGNAFLUX PARKER UV PROD.
MUDEL
Y6 Y6 CONT PROBE J221
NUMBER
LMT- 002 LMT-003 2768 26737
I YPE
YOKE
RLMARKS
AM~ CTTE' MAlH
ON SIL 4UrL.
NSP-ONSITE QUAL
NORTHERN STATES POWER COMPANY MONTICELLO Unit I
Table IV EQUIPMENT & MATERIALS
MANUFACTURER
ATS DIMAC DIMAC DIMAC DIMAC DIMAC JORGENSEN LEKA ORLA'S
MANUFACTURER
MAGNAFLUX MAGNAFLUX MAGNUFLUX
ULTRASONTC REFPEPNCF RinrvzBLUCK TYPE
1018 STEEL 304 SS 304 SS 304 SS 4140 CS 4140 CS ASTM A36 4140 CS STAINLESS
SERIAL NUMBER
798705 033 048 058 063 067 LMT-1 402 30RL
MATERIAL TYPE
STEPWEDGE ROMPAS ROMPAS ROMPAS ROMPAS ROMPAS IIW BLOCK ROMPAS STEP BLOCK
LIQUID PENETRANT MATERIALS
MATERIAL
DEVELOPER PENETRANT CLEANER
BATCH NUMBER
83L057 5G082 86C033
TYPE
SKD-NF/ZP-9B SKL-HF/SKL-S SKC-NF/ZC-7B
REMARKS
I
'I
NORTHERN STATES POWER COMPANY MONTICELLO Unit I
Table IV EQUIPMENT & MATERIALS
ULTRASONIC
TYPEMANUFACTURRL
AEROTECH AEROTECH AEROTECH AEROTECH AEROTECH AEROTECH AEROTECH AEROTECH AEROTECH AEROTECH AEROTECH AEROTECH AUTOMATION AUTOMATION AUTOMATION AUTOMATION AUTOMATION AUTOMATION AUTOMATION AUTOMATION AUTOMATION AUTOMATION AUTOMATION AUTOMATION AUTOMATION AUTOMATION AUTOMATION AUTOMATION AUTOMATION AUTOMATION AUTOMATION AUTOMATION AUTOMATION AUTOMATION BRANSON HARISONIC HARISONIC HARISONIC HARISONIC HARISONIC HARISONIC HARISONIC HARISONIC HARISONIC HARISONIC
LTRASOlNIC SEApCw UNITS7
ANGLE BEAM ANGLE BEAM ANGLE BEAM ANGLE BEAM ANGLE BEAM ANGLE BEAM ANGLE BEAM ANGLE BEAM ANGLE BEAM ANGLE BEAM ANGLE BEAM ANGLE BEAM ANGLE BEAM ANGLE BEAM ANGLE BEAM STRAIGHT BEAM STRAIGHT BEAM ANGLE BEAM ANGLE BEAM ANGLE BEAM ANGLE BEAM ANGLE BEAM ANGLE BEAM ANGLE BEAM ANGLE BEAM ANGLE BEAM STRAIGHT BEAM ANGLE BEAM ANGLE BEAM ANGLE BEAM ANGLE BEAM ANGLE BEAM ANGLE BEAM STRAIGHT BEAM STRAIGHT BEAM STRAIGHT BEAM STRAIGHT BEAM ANGLE BEAM ANGLE BEAM STRAIGHT BEAM ANGLE BEAM ANGLE BEAM STRAIGHT BEAM ANGLE BEAM ANGI E DAM M11 LLL ULM '[
SERIAL NUMBER
012674 C07592 D26781 D26782 F05134 F05145 Fl5183 F15198 F26143 H10142 J05547 K17340 C84217 186333 186334 38669 51309 A85054 C84242 C85194 C85195 C85197 C85198 C85201 C85202 185248 185251 J85128 J85274 J85297 J85321 L85219 L85220 NSCO11 4894 98871 98872 A52 A9768 B6466 C4164 C4171 C5492 P238 P927
.5"X. 5"
.5"X1. 0"
.25"
.25"
.5"
.5"
.25"
.25"
.5"
.5"
.25"
.5"
.5"X.5"
.75"X.75"
.75"X.75"
.5"
.5"
.25"X.25"
.25"X.25"
.5" X1"
.5"X1"
.5"X1"
.5"X1"
.38"X.38"
.38"X.38"
.25"
.25"
.38"X.38"
.5"X.5"
.5"X.5"
.5"X.5"
.38"X.38"
.38"X.38"
.25"
.5"X.5" 1" 1.0" 1"X.5" .5"X.5" .25" .38"X.38" .38"X.38" .75" 1 "X" 1.5" DIA
I -
'
2.25 2.25 3.5 2.25 5.0 5.0 5.0 5.0 2.25 1.5 2.25 2.25 2.25 2.25 2.25 1.0 5.0 2.25 2.25 2.25 2.25 2.25 2.25 2.25 2.25 2.25 2.25 2.25 2.25 2.25 2.25 1.5 1.5 10 1.5 2.25 2.25 2.25 1.5 5.0 1.5 1.5 5.0 1.0 1.0
NORTHERN STATES POWER COMPANY Table IV MONTICELLO Unit I EQUIPMENT & MATERIALS
MANUFACTURER
HARISONIC HARISONIC HARISONIC HARISONIC HARISONIC HARISONIC HARISONIC HARISONIC HARISONIC HARISONIC HARISONIC HARISONIC HARISONIC HARISONIC HARISONIC HARISONIC HARISONIC HARISONIC HARISONIC HARISONIC HARISONIC KBA KRAUTKR'ER KRAUTKR'ER MATLSASSUR MATLSASSUR NORTEC PANAMETRIC PANAMETRIC SUSI
ANGLE STRAI ANGLE ANGLE STRAI STRAI ANGLE STRAI ANGLE STRAI STRAI STRAI ANGLE ANGLE ANGLE ANGLE ANGLE STRAI ANGLE ANGLE ANGLE ANGLE ANGLE ANGLE STRAI STRAI STRAIG STRAIG STRAIG ANGLE
ULTRASONIC SEARCH UNITS TYPE SERIAL IlE
NUMBER
BEAM P928 1.0" DIA GHT BEAM P979 .75" BEAM R12348 .25"X.25" BEAM R30103 .38"X.38" GHT BEAM RCI-001 1" GHT BEAM RCI-005 .5" BEAM S2286 5"X.5" GHT BEAM S5139 i" BEAM T10224 .5"X.5" GHT BEAM T2211 .5" GHT BEAM T6157 .38" GHT BEAM T6240 .5" BEAM V10601 .38"X.38" BEAM V10602 .38"X.38" BEAM V10704 1"X1" BEAM V10705 1"X1" BEAM V12540 .38"X.38" GHT BEAM V6271 .75" BEAM W1283 1"X1" BEAM W6207 .5"X.5" BEAM W7227 .5"X.5" BEAM 012702 .5" BEAM F26458 10MM X10MM BEAM F26460 10MM X1oMM GHT BEAM 911871 .5" GHT BEAM 916872 .38" HT BEAM 17950 .25" HT BEAM 5840 1.125 HT BEAM 7585 1.0" BEAM 1379 .5"X.5"
FREQUENCY 1.0 1.0 3.5 3.5 2.25 2.25 1.5 2.25 2.25 5.0 3.5 1.1 1.5 1.5 2.25 2.25 3.5 2.25 2.25. 2.25 1.5 1.5 2.0 2.0 2.25 5.0 5.0 1.0 2.25 1.5
O
APPENDIX D
NIS-1 FORM
FORM NIS-1, OWNERS DATA REPORT FOR INSERVICE INSPECTION
Ld Lo C?
CL
FORM NIS-1 OWNER'S DATA REPORT FOR INSERVICE INSPECTIONS
FORM NIS-1 OWNER'S DATA REPORT FOR INSERVICE INSPECTIONS (As required by the Provision of the ASME Code Rules)
1.) Owner: Northern States Power Company
Address: 414 Nicollet Mall. Minneapolis, Minnesota 55401
2.) Plant: MONTICELLO NUCLEAR GENERATING PLANT
Address: MONTICELLO, MINNESOTA
3.) Plant Unit : I 4.) Owner (Certificate of Authorization): -
5.) Commercial Service Date: 06-30-71 6.) National Board NO. for Unit: -
7.) Components Inspected: Manufacturer
Component or Manufacturer or Installer State or Nationa Appurtenance or Installer Serial No. Province No. Board N
PRESSURE RETAINING WELDS IN REACTOR VESSEL
B1.11 CIRCUMFERENTIAL SHELL WELDSVCBB-4 @ N4B CB&I VCBB-4 @ N4C
B1.21 CIRUMFERENTIAL HEAD WELDS
B-4697
B-4697
B-4697
HCAB-1 @ HMAB-4 CB&I HCCB-2 1200 TO 2400
B1.22 MERIDONAL HEAD WELDSHMAB-2 CB&I HMAB-3 HMCB-5 HMCB-6
FULL PENETRATION WELDS OF NOZZLES IN VESSELS
B3.90 NOZZLE-TO-VESSEL WELDSFEEDWATER B FWBD-1
FEEDWATER C FWCD-1
HEAD SPRAY N6A RHDD-1
RECIRCULATION INLET LOOP E RRED-1
PAGE 1 OF 20
0
E
CB&I
CB&I
CB&I
CB&I
B-4697
B-4697
B-4697
B-4697a co
LO Co 0 C?-
I
l o.
FORM HIS-i OWNER'S DATA REPORT FOR INSERVICE INSPECTIONS
FORM NIS-1 OWNER'S DATA REPORT FOR INSERVICE INSPECTIONS (As required by the Provision of the ASME Code Rules)
1.) Owner: Northern States Power Company
-- Address:- 414 Nicollet Mall. Minneapolis, Minnesota 55401
2.) Plant: MONTICELLO NUCLEAR GENERATING PLANT
Address: MONTICELLO, MINNESOTA
3.) Plant Unit : I 4.) Owner (Certificate of Authorization): -
5.) Commercial Service Date: 06-30-71 6.) National Board NO. for Unit: -
7.) Components Inspected: Manufacturer
Component or Manufacturer or Installer State or Nationa Appurtenance or Installer Serial No. Province No. Board N
R3.100 NOZZLE INSTD RADTIU SCrTTnICFEEDWATER B CB&I FWBD-1 FWBD-1 IR FWBD-1 BORE
FEEDWATER C CB&I FWCD-1 FWCD-1 IR FWCD-1 BORE
HEAD SPRAY N6A CB&I RHDD-1 IR
RECIRCULATION CB&I INLET LOOP E RRED-1 IR
PRESSURE RETAINING DISSIMILAR METAL WELDS
B-4697
B-4697
B-4697
B-4697
REACTOR VESSEL
B5.10 NOMINAL PIPE SIZE 4 INCH - NOZZLE-TO-SAFE END BUTT WELDSHEAD SPRAY N6A RHDJ-2
INSTRUMENT NOZZEL N11B VIBF-2
RECIRCULATION INLET LOOP E RREFR-2
GE/BECHTEL
GE/BECHTEL
GE/BECHTEL
PAGE 2 OF 20
E
c
CD
a:
LO U-)
C? o~
09
l
o.
FORM NIS-1 OWNER'S DATA REPORT FOR INSERVICE INSPECTIONS (As required by the Provision of the ASME Code Rules)
1.) Owner: Northern States Power Company
Address: 414 Nicollet Mall, Minneapolis, Minnesota 55401
2.) Plant: MONTICELLO NUCLEAR GENERATING PLANT
Address: MONTICELLO. MINNFSOTA
3.) Plant Unit : I 4.) Owner (Certificate of Authorization): --5.) Commercial Service Date: 06-30-71 6.) National Board NO. for Unit: -
7.) Components Inspected:
Component or Appurtenance
Manufacturer or Installer
Manufacturer or Installer Serial No.
State or Province No.
National Board No.
B5.50 SAFE END WELDS CONTROL ROD DRIVE GE/BECHTEL SCRAM HEADER A CDAF-43
HIGH PRESSURE COOLANT INJECTION STEAM SIDE PSAF-2B PSAF-2C
RESIDUAL HEAT REMOVAL LOOP B RHBFR-6
GE/BECHTEL
GE/BECHTEL
PRESSURE RETAINING BOLTING, GREATER THAN 2 in. IN DIAMETER
B6.10 CLOSURE HEAD NUTSREACTOR VESSEL NUTS 1-64
CB&I B-4697
B6.50 CLOSURE WASHERS, BUSHINGSREACTOR VESSEL WASHERS 1-64
CB&I B-4697
PUMPS
B6.180 BOLTS AND STUDS, IN PLACE RECIRCULATION PUMP A FLANGE BOLTS 6-10
PAGE 3 OF 20
PIPING
LO LO a co
9
CD
C?
CL
FORM NIS-1 OWNER'S DATA REPORT FOR INSERVICE INSPECTIONS
FORM NIS-1 OWNER'S DATA REPORT FOR INSERVICE INSPECTIONS (As required by the Provision of the ASME Code Rules)
1.) Owner: Northern States Power Company.
Address: 414 Nicollet-Mall,--Minneapolis-, Minnesota-55401
2.) Plant: MONTICELLO NUCLEAR GENERATING PLANT
Address: MONTICELLO, MINNESOTA
3.) Plant Unit : I 4.) Owner (Certificate of Authorization): -
5.) Commercial Service Date: 06-30-71 6.) National Board NO. for Unit: -
7.) Components Inspected: Manufacturer
Component or Manufacturer or Installer State or Nationa Appurtenance or Installer Serial No. Province No. Board N
B6.200 BOLTING RECIRCULATION PUMP A FLG BOLTS 6-10
PRESSURE RETAINING BOLTING, 2 in. AND LESS IN DIAMETER
PIPING
B7.50 BOLT. STUDS AND NUTS
l
o.
MAIN STEAM D GE/BECHTEL BOLTS'@ MSDJ-23
VALVES
B7.70 BOLTS, STUDS, AND NUTS FEEDWATER B GE/BECHTEL FW-98-1
HIGH PRESSURE GE/BECTHEL COOLANT INJECTON STEAM SIDE MO-2034
MAIN STEAM B GE/BECHTEL A02-80B A02-86B
REACTOR COOLANT GE/BECHTEL TmJCrTTNM CTEAM MO-2075
RECIRCULATION GE/BECHTEL DRAIN LOOP B XR-6-2 XR-7-2
PAGE 4 OF 20
E
0
cc
FORM NIS-1 OWNER'S DATA REPORT FOR INSERVICE INSPECTIONS
FORM NIS-1 OWNER'S DATA REPORT FOR INSERVICE INSPECTIONS (As required by the Provision of the ASME Code Rules)
1.) Owner: Northern States Power Company
Address: 414 Nicollet Mall, Minneapolis, Minnesota-55401
2.) Plant: MONTICELLO NUCLEAR GENERATING PLANT
Address: MONTICELLO, MINNESOTA
Plant Unit :I 4.) Owner (Certificate of Authorization): --
5.) Commercial Service Date: 06-30-71 6.) National Board NO. for Unit: -
7.) Components Inspected:
Component or Appurtenance
B7.70 CONTINUED
RECIRCULATION LOOP B M02-43B M02-53B
RESIDUAL HEAT REMOVAL LOOP A MO-2030 POS-2028
RESIDUAL HEAT REMOVAL LOOP C POS-2018
STANDBY LIQUID CONTROL XP-7
Manufacturer or Installer
GE/BECHTEL
GE/BECHTEL.
GE/BECHTEL
GE/BECHTEL
Manufacturer or Installer Serial No.
State or Province No.
National Board No.
PRESSURE RETAINING WELDS IN PIPINGPIPING
B9.11 NOMINALCORE SPRAY LOOP A CSAJ-19,CSAJR-10
PIPE SIZE > 4". CIRCUMFERENTIAL WELDSGE/BECHTEL
CONTROL ROD DRIVE GE/BECHTEL CDRAM 14,ADR B CDBJ-14,40,43,46
FEEDWATER A FWP-A-5
MAIN STEAM B MSBJ-19
GE/BECHTEL
GE/BECHTEL
PAGE 5 OF 20
3.)
0
cc ui LO C0 C0
a-
B9.11 NOMINAL
L2
FORM NIS-1 OWNER'S DATA REPORT FOR INSERVICE INSPECTIONS (As required by the Provision of the ASME Code Rules)
1.) Owner: Northern States Power Company
Address: 414 Nicollet Mall, Minneapolis, Minnesota 55401
2.) Plant: MONTICELLO NUCLEAR GENERATING PLANT
Address: MONTICELLO, MINNESOTA
3.) Plant Unit : I 4.) Owner (Certificate of Authorization): -
5.) Commercial Service Date: 06-30-71 6.) National Board NO. for Unit: -7.) Components Inspected:
Manufacturer Component or Manufacturer or Installer State or National Appurtenance or Installer Serial No. Province No. Board No.
B9.11 CONTINUED
MAIN STEAM C GE/BECHTEL --MSCJ-29,8
RECIRCULATION GE/BECHTEL --LOOP A RCAJR-4,5
RESIDUAL HEAT GE/BECHTEL --REMOVAL LOOP B RHBJR-13,15,2,3
RESIDUAL HEAT GE/BECHTEL --REMOVAL LOOP .D RHDJ-11,12,17
REACTOR WATER GE/BECHTEL --CLEANUP CWAJR-11,13A,5
B9.21 NOMINAL PIPE SIZE < 4 in. CIRCUMFERENTIAL WELDS STANDBY LIQUID GE/BECHTEL --- --CONTROL CPAJR-16
B9.32 NOMINAL PIPE SIZE < 4 in. RECIRCULATION GE/BECHTEL --- --DRAIN LOOP B RCBjR-.11
W
LO 0 C? PAGE 6 OF 20
a.
FORM NIS-1 OWNER'S DATA REPORT FOR INSERVICE INSPECTIONS (As required by the Provision of the ASME Code Rules)
1.) Owner: Northern States Power Company
Address: 414 Nicollet Mall, Minneapolis, Minnesota 55401
2.) Plant: MONTICELLO NUCLEAR GENERATING PLANT
Address: MONTICELLO, MINNESOTA
3.) Plant Unit : I 4.) Owner (Certificate of Authorization): -
5.) Commercial Service Date: 06-30-71 6.) National Board NO. for Unit: -
7.) Components Inspected: Manufacturer
Component or Manufacturer or Installer State or National Appurtenance or Installer Serial No. Province No. Board No.
B9.40 SOCKET WELDS REACTOR VESSEL GE/BECHTEL --- --- --BOTTOM HEAD DRAIN HDAJ-10,42,9
REACTOR VESSEL GE/BECHTEL --- --- --HEAD VENT W-44,49,55,60,64
RECIRCULATION GE/BECHTEL --- --- --DRAIN B W-3B,6B
SUPPORT MEMBERS FOR PIPING, PUMPS, AND VALVES
PIPING
B10.10 INTEGRALLY WELDED ATTACHMENTS CONTORL ROD DRIVE GE/BECTHEL --SCRAM HEADER B CDBK-4
FEEDWATER C GE --- --- --FWCK-7
FEEDWATER D GE --- --- --FWDK-7
MAIN STEAM D GE --- --MSDK-32
co RECIRCULATION GE/BECTHEL --- --- --LOOP B o RCBKR-16 RCBKR-29 RCBKR-32 d
PAGE 7 OF 20 C
n?
FORM NIS-1 OWNER'S DATA REPORT FOR INSERVICE INSPECTIONS
FORM NIS-1 OWNER'S DATA REPORT FOR INSERVICE INSPECTIONS (As required by the Provision of the ASME Code Rules)
1.) Owner: Northern States Power Company
Address: 414 Nicollet Mall, Minneapolis, Minnesota 55401
2.) Plant: MONTICELLO NUCLEAR GENERATING PLANT
Address: MONTICELLO MINNESOTA
3.) Plant Unit : I 4.) Owner (Certificate of Authorization): --
5.) Commercial Service Date: 06-30-71 6.) National Board NO. for Unit: -
7.) Components Inspected:
Component or Appurtenance
B10.10 CONTINUED
RECIRCULATION MANIFOLD A RMAKR-6
RECIRCULATION MAINFOLD B RMBKR-13
Manufacturer or Installer
GE/BECTHEL
GE/BECTHEL
Manufacturer or Installer Serial No.
State or Province No.
National Board No.
COMPONENT SUPPORTS FOR PIPING, PUMPS, AND VALVES
PIPING
B11.10 COMPONENT SUPPORTS CORE SPRAY A GE/BECTHEL --CSAK-7
CONTROL ROD DRIVE GE/BECTHEL SCRAM HEADER B CDBK-16A CDBK-17
CONTROL ROD DRIVE GE/BECTHEL SCRAM HEADER A CDAK-19A CDAK-230 CDAK-2A ICDAK-30 CDAK-37 CDAK-4
FEEDWATER D FWDK-31
GE/BECTHEL
PAGE 8 OF 20
R
0
0
0
C? o CL
a-
I
FORM NIS-1 OWNER'S DATA REPORT FOR INSERVICE INSPECTIONS (As required by the Provision of the ASME Code Rules)
1.) Owner: Northern States Power Company
Address: 414 Nicollet Mall
2.) Plant: MONTICELLO NUCLEAR GENERATING PLANT
Address: MONTICELLO. MINNESOTA
3.) Plant Unit : I 4.) Owner (Certificate of Authorization): -
5.) Commercial Service Date: 06-30-71 6.) National Board NO. for Unit: -7.) Components Inspected:
Component or Appurtenance
B11.10 CONTINUED
MAIN STEAM CONDENSATE SR-723
MAIN STEAM A DRAIN PSH-724 SR-722
MAIN STEAM D DRAIN PSH-725
RECIRCULATION LOOP A PHAR-4 PHAR-5 PSSAR-5 RCAKR-12
RECIRCULATION RISER C RRCKR-6
RECIRCULATION RISER G RRGKR-6
RECIRCULATION RISER H RRHKR-6
Manufacturer or Installer
GE/BECTHEL
GE/BECTHEL
GE/BECTHEL
GE/BECTHEL
GE/BECTHEL
GE/BECTHEL
GE/BECTHEL
Manufacturer or Installer Serial No.
State or Province No.
National Board No.
PAGE 9 OF 20
E
Cl 0
0
LO o
cy
FORM NIS-1 OWNER'S DATA REPORT FOR INSERVICE INSPECTIONS (As required by the Provision of the ASME Code Rules)
1.) Owner: Northern States Power Company
Address: 414 Nicollet Mall, Minneapolis, Minnesota 55401
2.) Plant: MONTICELLO NUCLEAR GENERATING PLANT
Address: MONTICELLO, MINNESOTA
3.) Plant Unit : I 4.) Owner (Certificate of Authorization): -
5.) Commercial Service Date: 06-30-71 6.) National Board NO. for Unit: -
7.) Components Inspected: Manufacturer
Component or Manufacturer or Installer State or Nationa Appurtenance or Installer Serial No. Province No. Board N
B11.10 CONTINUED
RESIDUAL HEAT GE/BECTHEL --- --- --REMOVAL LOOP C RHCKR-10 RHCKR-17A RHCKR-24
RESIDUAL HEAT GE/BECTHEL --- --- --REMOVAL LOOP E RHEKR-12
STANDBY LIQUID GE/BECTHEL --CONTROL CPAK-14A
PUMP CASINGS AND VALVE BODIES
VALVES B12.30 VALVE BODY WELDSRESIDUAL HEAT REMOVAL LOOP C A010-46B
GE/BECTHEL
l
o.
PAGE 10 OF 20
E
0)
CD
Cc
LO C C?
FORM NIS-1 OWNER'S DATA REPORT FOR INSERVICE INSPECTIONS (As required by the Provision of the ASME Code Rules)
1.) Owner: Northern States Power Company
Address: 414 Nicollet Mall, Minneapolis, Minnesota 55401
2.) Plant: MONTICELLO NUCLEAR GENERATING PLANT
Address: MONTICELLO, MINNESOTA
3.) Plant Unit : I 4.) Owner (Certificate of Authorization): -
5.) Commercial Service Date: 06-30-71 6.) National Board NO. for Unit: -
7.) Components Inspected: Manufacturer
Component or Manufacturer or Installer State or National Appurtenance or Installer Serial No. Province No. Board No.
ASME CLASS II
PRESSURE RETAINING WELDS IN PRESSURE VESSELS
C1.10 SHELL CIRCUMFERENTIAL WELDSRESIDUAL HEAT PERFEX REMOVAL HEAT EXCHANGER BW-2
C1.20 HEAD CIRCUMFERENTAIL WELDS RESIDUAL HEAT PERFEX --REMOVAL HEAT EXCHANGER B W-4
PRESSURE RETAINING NOZZLE WELDS IN VESSELS
C2.20 NOZZELS IN VESSELS 1 IN. OR LESS IN NOMINAL THICKNESSRESIDUAL HEAT REMOVAL HEAT EXCHANGER A W-N4
RESIDUAL HEAT REMOVAL HEAT EXCHANGER B W-N3
PERFEX
PAGE 11 OF 20
0
E
<0
Ld Lo
PERFEX--
5
FORM NIS-1 OWNER'S DATA REPORT FOR INSERVICE INSPECTIONS (As required by the Provision of the ASME Code Rules)
1.) Owner: Northern States Power Company
Address: 414 Nicollet Mall, Minneapolis, Minnesota 55401
2.) Plant: MONTICELLO NUCLEAR GENERATING PLANT
Address: MONTICELLO, MINNESOTA
3.) Plant Unit : I 4.) Owner (Certificate of Authorization): -
5.) Commercial Service Date: 06-30-71 6.) National Board NO. for Unit: -
7.) Components Inspected: Manufacturer
Component or Manufacturer or Installer State or National Appurtenance or Installer Serial No. Province No. Board No.
EXAMINATION CATEGORY C-C AND C-E. SUPPORT MEMBERS
PRESSURE VESSELS
C3.10 INTERGALLY WELDED SUPPORT ATTACHMENTS RESIDUAL HEAT PERFEX --- -REMOVAL HEAT EXCHANGER A SUPPORT C
RESIDUAL HEAT PERFEX -- -REMOVAL HEAT EXCHANGER B SUPPORT C
C3.20 COMPONENT SUPPORTS RESIDUAL HEAT PERFEX --- -REMOVAL HEAT EXCHANGER A SUPPORT C
RESIDUAL HEAT PERFEX --- .. REMOVAL HEAT EXCHANGER B SUPPORT B
PIPING
C3.40 INTEGRALLY WELDED SUPPORT ATTACHMENTS CONTAiNMENT GE/BECHTEL --SPRAY A TWH-143
CORE SPRAY A GE/BECHTEL --- --- --CSAK-46 oc
PAGE 12 OF 20c
FORM NIS-1 OWNER'S DATA REPORT FOR INSERVICE INSPECTIONS (As required by the Provision of the ASME Code Rules)
1.) Owner: Northern States Power Company.
Address: 414 Nicollet Mall, Minneapolis, Minnesota 55401
2.) Plant: MONTICELLO NUCLEAR GENERATING PLANT
Address: MONTICELLO, MINNESOTA
3.) Plant Unit : I 4.) Owner (Certificate of Authorization): -
5.) Commercial Service Date: 06-30-71 6.) National Board NO. for Unit: -
7.) Components Inspected: Manufacturer
Component or Manufacturer or Installer State or Nationa Appurtenance or Installer Serial No. Province No. Board N
C3.40 CONTINUED
CORE SPRAY B GE/BECHTEL --- --DISCHARGE TWH-67A
HIGH PRESSURE GE/BECHTEL COOLANT INJECTION WATER DISCHARGE CIAK-45
RESIDUAL HEAT GE/BECHTEL --- --- -REMOVAL LOOP A DISCHARGE TWH-173
RESIDUAL HEAT GE/BECHTEL --- - -
REMOVAL LOOP A SUCTION TWH-1,3
RESIDUAL HEAT GE/BECHTEL --- --- --REMOVAL LOOP B SUCTION TWH-16A
C3.50 COMPONENT SUPPORTSCORE SPRAY A SS-27,TWH-53, CSAK-32A
CORE SPRAY A DISCHARGE SR-58,TWH-83,84
GE/BECHTEL
1 0.
GE/BECHTEL
PAGE 13 OF 20
0 20a
cc
0 9
A
FORM NIS-1 OWNER'S DATA REPORT FOR INSERVICE INSPECTIONS (As required by the Provision of the ASME Code Rules)
1.) Owner: Northern States Power Company
Address: 414 Nicollet Mall, Minneapolis, Minnesota 55401
2.) Plant: MONTICELLO NUCLEAR GENERATING PLANT
Address: MONTICELLO, MINNESOTA
3.) Plant Unit : I 4.) Owner (Certificate of Authorization): -
5.) Commercial Service Date: 06-30-71 6.) National Board NO. for Unit: -
7.) Components Inspected:
Component or Appurtenance
C3.50 CONTINUED
Manufacturer or Installer
Manufacturer or Installer Serial No.-
State or Province No.
National Board No.
CORE SPRAY B DISCHARGE TWH-66A, CSBK-35
CORE SPRAY B SUCTION TWH-57,58
CORE SPRAY A SUCTION SS-27, TWH-52
HIGH PRESSURE COOLANT INJECTION STEAM SIDE TDAK-13,16,17,5
HIGH PRESSURE COOLANT INJECTION WATER DISCHARGE CIAK-25,50,59A, TWH-36,39,40 CIAK-26,37,40,48A CIAK-50,52,59
MAIN STEAM B MSBK-51,53
MAIN STEAM C MSCK-43,48
REACTOR CORE |INJECTION COOLING TEAM DISCHARGE SH-14,15
GE/BECHTEL
GE/BECHTEL
GE/BECHTEL
GE/BECHTEL
GE/BECHTEL
GE/BECHTEL
GE/BECHTEL
GE/BECHTEL
PAGE 14 OF 20
0
0
C L6 9
FORM NIS-1 OWNER'S DATA REPORT FOR INSERVICE INSPECTIONS (As required by the Provision of the ASME Code Rules)
1.) Owner: Northern States Power Company
Address: 414 Nicollet m11 I ** , , ,I. nInnIvInLd JJtUI
2.) Plant: MONTICELLO NUCLEAR GENERATING PLANT
Address: MONTICELLO, MINNESOTA
3.) Plant Unit : I 4.) Owner (Certificate of Authorization): -
5.) Commercial Service Date: 06-30-71 6.) National Board NO. for Unit: -
7.) Components Inspected:
Component or Appurtenance
C3.50 CONTINUED
Manufacturer or Installer
Manufacturer or Installer Serial No.
State or Province No.
National Board No.
REACTOR CORE GE/BECHTEL INJECTION COOLING WATER SUCTION TW-25
RESIDUAL HEAT GE/BECHTEL REMOVAL LOOP B DISCHARGE SR-24 TWH-632,94,94A TWH-95,98
RESIDUAL HEAT GE/BECHTEL REMOVAL LOOP A DISCHARGE TWH-59,59A,62A,64 TWH-64A,65,65A, TWH-73A,73B
RESIDAUL HEAT GE/BECHTEL REMOVAL SERVICE WATER SWAK-25,20
RESIDUAL HEAT GE/BECHTEL REMOVAL LOOP A SUCTION TWH-2
RESIDUAL HEAT GE/BECHTEL REMOVAL LOOP B SUCTION TWH-12
PAGE 15 OF 20
0
LO 0 C?
5IL
O
FORM NIS-1 OWNER'S DATA REPORT FOR INSERVICE INSPECTIONS (As required by the Provision of the ASME Code Rules)
1.) Owner: Northern States Power Company
Address: 414 Nicollet Mall, Minneapolis, Minnesota 55401
2.) Plant: MONTICELLO NUCLEAR GENERATING PLANT
Address: MONTICELLO, MINNESOTA
3.) Plant Unit : I 4.) Owner (Certificate of Authorization): -
5.) Commercial Service Date: 06-30-71 6.) National Board NO. for Unit: -
7.) Components Inspected: Manufacturer
Component or Manufacturer or Installer State or National Appurtenance or Installer Serial No. Province No. Board No.
C3.50 CONTINUED
REACTOR WATER GE/BECHTEL --- -FROM SKIMMER SYSTEM RWAK-35
SUPPLY TO GE/BECHTEL --- --STEAM SEAL SSAK-14A,21,22
PUMPS
C3.70 INTEGRALLY WELDED SUPPORT ATTACHMENTS
RESIDUAL HEAT BINGHAM 270427 --- --REMOVAL PUMP A MOUNTING FEET
RESIDUAL HEAT BINGHAM 270428 --- --REMOVAL PUMP C MOUNTING FEET
C3.80 COMPONENT SUPPORTS
REACTOR CORE TERRY STEAM 35690 --- --INJECTION COOLING TURBINE CO. PUMP SUPPORT C Cl1innonTr f1
LO o C? Pn
FORM NIS-1 OWNER'S DATA REPORT FOR INSERVICE INSPECTIONS (As required by the Provision of the ASME Code Rules)
1.) Owner: Northern States Power Company
Address: 414 Nicollet Mall, Minneapolis, Minnesota 55401
2.) Plant: MONTICELLO N!LEAR GENERATING PLANT
Address: MONTICELLO, MINNESOTA
3.) Plant Unit : I 4.) Owner (Certificate of Authorization): -
5.) Commercial Service Date: 06-30-71 6.) National Board NO. for Unit: -
7.) Components Inspected:
Component or Appurtenance
Manufacturer or Installer
Manufacturer or Installer Serial No.
State or Province No.
PRESSURE RETAINING WELDS IN PIPING
C5.11 PIPING WELDS 1/2 in. OR LESS NOMINAL WALL THICKNESS - CIRCUMFERENTIAL WELDS
CONTAINMENT SPRAY B W-18
CORE SPRAY B DISCHARGE W-564
CORE SPRAY B SUCTION W-654,8F
GE/BECHTEL
GE/BECHTEL
GE/BECHTEL
REACTOR CORE GE/BECHTEL INJECTION COOLING WATER DISCHARGE W-227
RESIDUAL HEAT GE/BECHTEL REMOVAL LOOP A DISCHARGE W-12,13,3,362,367,374
RESIDUAL HEAT GE/BECHTEL REMOVAL LOOP B DISCHARGE W-22,25A,313,323,329
RESIDUAL HEAT GE/BECHTEL REMOVAL LOOP A SUCTION W-7
PAGE 17 OF 20
E
National Board No.
a:
0 Od c9
FORM NIS-1 OWNER'S DATA REPORT FOR INSERVICE INSPECTIONS (As required by the Provision of the ASME Code Rules)
1.) Owner: Northern States Power Company
Address: 414 Nicollet Mall, Minneapolis, Minnesota 55401
2.) Plant:- MONTICELLO NUCLEAR GENERATING PLANT
Address: MONTICELLO, MINNESOTA
3.) Plant Unit : I 4.) Owner (Certificate of Authorization): -
5.) Commercial Service Date: 06-30-71 6.) National Board NO. for Unit: --
7.) Components Inspected:
Component or Appurtenance
Manufacturer or Installer
Manufacturer or Installer Serial No.
State or Province No.
(371 PTPTNr. WFIfl~ ~ 1/9 inMAIN STEAM B MSBJ-43,57
MAIN STEAM C MSCJ-46
GE/BECHTEL
GE/BECHTEL
NOMINAL WALL THICKNESS - CIRCUMFERENTIAL WELDS
SUPPLY TO STEAM GE/BECHTEL SEAL SSAJ-19
RESIDUAL HEAT REMOVAL LOOP B SUCTION W-939
GE/BECHTEL
MISCELLANEOUS WELDS
CONTROL ROD DRIVE BECHTEL RETURN TO REACTOR WATER CLEANUP W-11,12,13,14,7
FEEDWATER TO REACTOR WATER CLEANUP TO HIGH PRESSURE COOLANT INJECTION W-1,2,3,4,12,12A
BECHTEL
PAGE 18 OF 20
E
National Board No.
0 0
0)
LO 0
C0
C5 21PIPTr, wr ne. , . i
FORM NIS-1 (back)
8.) Examination Dates 10-19-87 to 12-10-87 9.) Inspection Interval 06-30-81 to 06-29-92
10.) Abstract of Examinations. Include a list of examination and a statement concerning status of work required for current interval.
This was the first inspection conducted for inspection period two of the 2nd Ten Year Inspection Interval. The examinations completed 50% of the required pressure retaining components and their supports of the reactor coolant and associated auxiliary systems classified as ASME Class I and II. 11.) Abstract of Conditions Noted.
There were no signs of degradation to systems scheduled for examination.
The anomalies detected were: 1 linear MT indications; 1 hanger with improper load settings; .5 hanger with drawing compliances; 1 hanger with improperly marked load scale ; 2 hangers with loose bolts or nuts; 7 hangers with inadequate thread engagement; 1 hanger with no drawing available; 1 support with an arc strike; and 3 valves with rusted bolting.
12.) Abstract of Corrective Measures Recommended and Taken:
All anomalies were either corrected or an engineering evaluation was performed to accept "as is" conditions. The MT indications were corrected by light hand grinding and blending the surface smooth; the hangers that were out of adjustment were readjusted; the hangers with drawing compliances were turned over to drawing control to reflect the 'as found' conditions or were accepted 'as is' based on engineering evaluations; loose bolts were tightened; the hangers with inadequated thread engagement were either readjusted or the nuts were tack welded to prevent nuts from coming loose; the missing hanger drawing was located ; and the support with an arc strike was buffed out and reinspected.
We certify that the statements made in this report are correct and the examinations and corrective measures taken conform to the rules of the ASME Code, Section XI.
DatejAm2 1986 Signe B / 7 6' /_ _ _ _ _ Owner
Certificate of Authorization no. (If applicable) _, _ _
Expiration Date
)
Page 19 of 20 C
CERTIFICATE OF INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and/or the State or Providence of MINNESOTA and employed by HARTFORD STEAM BOILER INSPECTION & INSURANCE COMPANY of HARTFORD, CONNECTICUT have inspected the components described in this Owner's Data Report during the period /o-i'- 7 to I-so -87 and state that to the best of my knowledge and belief, the Owner has preformed examinations and taken corrective measures described in this Owner's Data Report in accordance with the requirements of the ASME Code, Section XI. By signing the certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Data Report. Futhermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or loss of any kind arising form or connected with this inspection.
Date Z9 19 6 I
___ __ __ _ Commissions AlaJ5993 Arf, ?bB//O 'Insoector's Signature National Board, State, Providence & No.
PAGE 20 OF 20