SEE FILTER RM PLAN FOR ROOM BELOW SEE TELEPHONE EQUIP. RM PLAN FOR ROOM ABOVE A B C D E F G H J K M N P L 2 3 4 6 8.1 9 10 11 12 13 15 17 18 19 7 14 2 3 4 6 9 10 11 12 13 15 17 18 19 8 A B C D E F G H J K M N P L STAIR B USE OF FORCE SIMULATOR RM 008 STO. RM 009 BOYS LOCKER ROOM 030 OFFICE 018 SHOWERS 031 STAIR C GIRLS LOCKER ROOM 035 STORAGE RM 022 OUTDOOR STO. 023 MECH EQ 024 MECH EQ 025 TACTICAL MANEUVER TRAINING 026 OFFICE 027 OFFICE 028 OFFICE 029 POOL 030 LOWER STAIR H LOWER STAIR G CORRIDOR 021 STORAGE 011 CORRIDOR 021 CORRIDOR 021 STAIR A ELECTRICAL 010 NETWORK SERVICES 007 ELECTRIC TRANSFORMER 001 EM GENERATOR 002 STORAGE 004 STORAGE 006 MECHANICAL EQUIPMENT 003 JAN CLO 016 JAN CLO 020 TOILET 005 TELEPHONE EQUIP. RM 033 POOL FILTER ROOM 031 ELEV MACH RM 032 TACTICAL MANEUVER TRAINING 026 TOILETS 032 TOILETS 033 SHOWERS 034 STORAGE 036 STORAGE 037 DRAWING NO.: ISSUE NO. ISSUE DATE DESCRIPTION PROJECT NO.: 1517-01 Alterations to Quirk West Building 50 Williams Street Hartford, CT NORTH KEY PLAN WILLIAMS STREET 33 North Plains Industrial Rd Wallingford, CT 06492 Tel: 203.467.4370 Fax: 203.793.7729 Web: www.iesllc.biz Innovative Engineering Services, LLC An Integrated engineering + design firm I E S MECH'L/ELEC'L/PLUMBING ENGINEERS ENVIRONMENTAL ENGINEER FUSS & O'NEILL ENVIROSCIENCE, LLC 146 HARTFORD ROAD MANCHESTER, CT 06040 ELEVATOR CONSULTANT 810-82ND STREET NORTH BERGEN, NJ 07047 VerTacan, LLC CONSULTANTS POOL CONSULTANT 333 WESTCHESTER AVENUE WHITE PLAINS NY, 10606 WALNUT STREET ALBANY AVENUE 07-22-2016 1 100% SUBMISSION FP-100 GROUND FLOOR FIRE PROTECTION PLAN SCALE: 1/8"=1'-0" GROUND FLOOR FIRE PROTECTION PLAN FIRE PROTECTION DRAWING NOTES
Transcript
Page 1: INSTALL NEW PIPING AND UPRIGHT SPRINKLER HEADS WITH …€¦ · office 018 showers 031 stair c girls locker room 035 storage rm 022 outdoor sto. 023 mech eq 024 mech eq 025 tactical

SEE FILTER RM PLANFOR ROOM BELOW

SEE TELEPHONEEQUIP. RM PLANFOR ROOM ABOVE

A

B

C

D

E

F

G

H

J

K

M

N

P

L

2 3 4 6 8.1 9 10 11 12 13 15 17 18 197 14

2 3 4 6 9 10 11 12 13 15 17 18 198

A

B

C

D

E

F

G

H

J

K

M

N

P

L

STAIR B

USE OF FORCE SIMULATOR RM008

STO. RM009

BOYS LOCKER ROOM030

OFFICE018

SHOWERS031

STAIR C

GIRLS LOCKER ROOM035

STORAGE RM022

OUTDOOR STO.023

MECH EQ024 MECH EQ

025

TACTICAL MANEUVER TRAINING026

OFFICE027

OFFICE028

OFFICE029

POOL030

LOWER STAIR HLOWER STAIR G

CORRIDOR021

STORAGE011

CORRIDOR021CORRIDOR

021

STAIR A

ELECTRICAL010

NETWORK SERVICES007

ELECTRIC TRANSFORMER001

EM GENERATOR002

STORAGE004

STORAGE006

MECHANICAL EQUIPMENT003

JAN CLO016

JAN CLO020

TOILET005

TELEPHONE EQUIP. RM033

POOL FILTER ROOM031

ELEV MACH RM032

TACTICAL MANEUVER TRAINING026

TOILETS032

TOILETS033

SHOWERS034

STORAGE036

STORAGE037

DRAWING NO.:

ISSUE NO. ISSUE DATE DESCRIPTION

PROJECT NO.: 1517-01

Alterations to Quirk WestBuilding

50 Williams StreetHartford, CT

NORTH

KEY PLAN

WILLIAMS STREET

33 North Plains Industrial RdWallingford, CT 06492Tel: 203.467.4370 Fax: 203.793.7729Web: www.iesllc.biz

Innovative EngineeringServices, LLCAn Integrated engineering + design firm

I E S

MECH'L/ELEC'L/PLUMBING ENGINEERS

ENVIRONMENTAL ENGINEER

FUSS & O'NEILL ENVIROSCIENCE, LLC146 HARTFORD ROADMANCHESTER, CT 06040

ELEVATOR CONSULTANT

810-82ND STREETNORTH BERGEN, NJ 07047

VerTacan, LLC

CONSULTANTS

POOL CONSULTANT

333 WESTCHESTER AVENUEWHITE PLAINS NY, 10606

WA

LNU

T ST

REET

ALB

AN

Y A

VEN

UE

07-22-20161 100% SUBMISSION

FP-100

GROUND FLOORFIRE PROTECTION PLAN

SCALE: 1/8"=1'-0"

GROUND FLOOR FIRE PROTECTION PLAN

FIRE PROTECTION DRAWING NOTES

AutoCAD SHX Text
RAMP DN
AutoCAD SHX Text
RAMP DN
AutoCAD SHX Text
RAMP DN
AutoCAD SHX Text
RAMP DN
AutoCAD SHX Text
FHC
AutoCAD SHX Text
FHC
AutoCAD SHX Text
FHC
AutoCAD SHX Text
FHC
AutoCAD SHX Text
FHC
AutoCAD SHX Text
EXISTING SPRINKLER HEADS TO REMAIN
AutoCAD SHX Text
2
AutoCAD SHX Text
2
AutoCAD SHX Text
2
AutoCAD SHX Text
2
AutoCAD SHX Text
2
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
3
AutoCAD SHX Text
3
AutoCAD SHX Text
3
AutoCAD SHX Text
EXISTING SPRINKLER HEAD TO REMAIN IN ELEV MACH RM
AutoCAD SHX Text
INSTALL NEW PIPING AND UPRIGHT SPRINKLER HEADS WITH CAGES IN THIS AREA.
AutoCAD SHX Text
DISCONNECT, REMOVE & REPLACE SPRINKLER HEADS AND PIPING IN POOL FILTER ROOM. INSTALL SPRINKLER HEADS PER NEW LAYOUT.
AutoCAD SHX Text
G:\IES Projects\2014 Projects\14021 Quirk West Building\Contract Documents\14021 FP-100.dwg
AutoCAD SHX Text
SCALE: 1/8"= 1'-0"
AutoCAD SHX Text
NEW SPRINKLER HEAD, CONNECT TO EXISTING SPRINKLER BRANCH PIPING 1-1/2" OR LARGER (TYP). EXISTING SPRINKLER HEAD TO REMAIN. REMOVE EXISTING SPRINKLER HEAD AND CAP PIPING AT EXISTING BRANCH PIPING.
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
3
Page 2: INSTALL NEW PIPING AND UPRIGHT SPRINKLER HEADS WITH …€¦ · office 018 showers 031 stair c girls locker room 035 storage rm 022 outdoor sto. 023 mech eq 024 mech eq 025 tactical

A

B

C

D

E

F

G

H

J

K

M

N

P

L

2 3 4 6 8.1 9 10 11 12 13 15 17 18 197 14

2 3 4 6 9 10 11 12 13 15 17 18 198

A

B

C

D

E

F

G

H

J

K

M

N

P

L

MECHANICAL124

PASSAGE111

RECEPTION OFFICE103

LOBBY101

SUPERVISOR'S OFFICE117

LIBRARY115

COMMANDER'S OFFICE120

BREAK RM.116

MAIN EQUIP STO. RM121

MUSTER ROOM102

TRAINING ROOM-1105

WOMEN104

MEN108

STAFF106

STO/DRESSING RM110

ARCHIVE/RECORDS112

TRAINING RM-2114

SITU

ATI

ON

HA

LLW

AY

11

9

ELEVATOR

CORRIDOR122

STAIR F

MUSIC STO.131

STORAGE132

KITCHEN136

MUSIC ROOM137

BOYS139

GIRLS144

RECEPTION145

EXERCISE143

PAL MULTI-PURPOSE ROOM148

SUPERVISOR150

OFFICE151 TEL/CO

152

COMPUTER LAB149

ARTS&CRAFTS/130

PANTRY133

146

STAIR H

STAIR D

CORRIDOR122

158

CHECK IN145.A

STORAGE147

STO155

FOYER/RECEPTION154

DRAWING NO.:

ISSUE NO. ISSUE DATE DESCRIPTION

PROJECT NO.: 1517-01

Alterations to Quirk WestBuilding

50 Williams StreetHartford, CT

NORTH

KEY PLAN

WILLIAMS STREET

33 North Plains Industrial RdWallingford, CT 06492Tel: 203.467.4370 Fax: 203.793.7729Web: www.iesllc.biz

Innovative EngineeringServices, LLCAn Integrated engineering + design firm

I E S

MECH'L/ELEC'L/PLUMBING ENGINEERS

ENVIRONMENTAL ENGINEER

FUSS & O'NEILL ENVIROSCIENCE, LLC146 HARTFORD ROADMANCHESTER, CT 06040

ELEVATOR CONSULTANT

810-82ND STREETNORTH BERGEN, NJ 07047

VerTacan, LLC

CONSULTANTS

POOL CONSULTANT

333 WESTCHESTER AVENUEWHITE PLAINS NY, 10606

WA

LNU

T ST

REET

ALB

AN

Y A

VEN

UE

07-22-20161 100% SUBMISSION

FP-101

FIRST FLOORFIRE PROTECTION PLAN

SCALE: 1/8"=1'-0"

FIRST FLOOR FIRE PROTECTION PLAN

FIRE PROTECTION DRAWING NOTES

AutoCAD SHX Text
OPEN BELOW
AutoCAD SHX Text
1
AutoCAD SHX Text
4
AutoCAD SHX Text
4
AutoCAD SHX Text
4
AutoCAD SHX Text
4
AutoCAD SHX Text
4
AutoCAD SHX Text
4
AutoCAD SHX Text
4
AutoCAD SHX Text
4
AutoCAD SHX Text
3
AutoCAD SHX Text
1"
AutoCAD SHX Text
1"
AutoCAD SHX Text
1-1/4"
AutoCAD SHX Text
1-1/2"
AutoCAD SHX Text
1-1/2"
AutoCAD SHX Text
3
AutoCAD SHX Text
3
AutoCAD SHX Text
3
AutoCAD SHX Text
3
AutoCAD SHX Text
3
AutoCAD SHX Text
3
AutoCAD SHX Text
3
AutoCAD SHX Text
3
AutoCAD SHX Text
3
AutoCAD SHX Text
3
AutoCAD SHX Text
3
AutoCAD SHX Text
3
AutoCAD SHX Text
3
AutoCAD SHX Text
3
AutoCAD SHX Text
1"
AutoCAD SHX Text
1"
AutoCAD SHX Text
1-1/4"
AutoCAD SHX Text
2
AutoCAD SHX Text
2
AutoCAD SHX Text
2
AutoCAD SHX Text
G:\IES Projects\2014 Projects\14021 Quirk West Building\Contract Documents\14021 FP-101.dwg
AutoCAD SHX Text
SCALE: 1/8"= 1'-0"
AutoCAD SHX Text
CONNECT TO 3" MAIN OR LARGER. NEW SPRINKLER IN LOOK-THROUGH WINDOW. SEE ARCHITECTURAL DRAWING FOR EXACT LOCATION. REMOVE EXISTING SPRINKLER HEAD AND CAP PIPING AT BRANCH PIPING (TYP). EXISTING SPRINKLER HEAD TO REMAIN (TYP).
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
3
AutoCAD SHX Text
4
Page 3: INSTALL NEW PIPING AND UPRIGHT SPRINKLER HEADS WITH …€¦ · office 018 showers 031 stair c girls locker room 035 storage rm 022 outdoor sto. 023 mech eq 024 mech eq 025 tactical

STAIR HSTAIR F

STAIR D

MEN'S LOCKER ROOM233

WOMENS LOCKERS232

W. TOILET230

MEN'S TOILET234

LOBBY

STORAGE212

BOYS TOILET237

SHOWER 240.A

GIRLS LOCKER ROOM241

CORRIDOR223

CORRIDOR204

GYMNASIUM 1201

AUDITORIUM202

GYMNASIUM 2203

STAGE211

STORAGE236

JAN. CLO210

LAUNDRY222

MEN220

WOMEN221

STAGE STORAGE219

SHOWERS230.A SHOWERS

234.A

BOYS LOCKER ROOM236

CORRIDOR204

G.TOILET240

SHOWER237.ASTORAGE

209

STORAGE231

STORAGE239

STORAGE235

JAN211

POLICE ACADEMY POLICE ACTIVITIES LEAGUE

EXISTEXIST

CORRIDOR226

A

B

C

D

E

F

G

H

J

K

M

N

P

L

2 3 4 6 8.1 9 10 11 12 13 15 17 18 197 14

2 3 4 6 9 10 11 12 13 15 17 18 198

A

B

C

D

E

F

G

H

J

K

M

N

P

L

DRAWING NO.:

ISSUE NO. ISSUE DATE DESCRIPTION

PROJECT NO.: 1517-01

Alterations to Quirk WestBuilding

50 Williams StreetHartford, CT

NORTH

KEY PLAN

WILLIAMS STREET

33 North Plains Industrial RdWallingford, CT 06492Tel: 203.467.4370 Fax: 203.793.7729Web: www.iesllc.biz

Innovative EngineeringServices, LLCAn Integrated engineering + design firm

I E S

MECH'L/ELEC'L/PLUMBING ENGINEERS

ENVIRONMENTAL ENGINEER

FUSS & O'NEILL ENVIROSCIENCE, LLC146 HARTFORD ROADMANCHESTER, CT 06040

ELEVATOR CONSULTANT

810-82ND STREETNORTH BERGEN, NJ 07047

VerTacan, LLC

CONSULTANTS

POOL CONSULTANT

333 WESTCHESTER AVENUEWHITE PLAINS NY, 10606

WA

LNU

T ST

REET

ALB

AN

Y A

VEN

UE

07-22-20161 100% SUBMISSION

FP-102

SECOND FLOORFIRE PROTECTION PLAN

SCALE: 1/8"=1'-0"

SECOND FLOOR FIRE PROTECTION PLAN

FIRE PROTECTION DRAWING NOTES

AutoCAD SHX Text
2
AutoCAD SHX Text
2
AutoCAD SHX Text
2
AutoCAD SHX Text
2
AutoCAD SHX Text
1
AutoCAD SHX Text
3
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
2
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
G:\IES Projects\2014 Projects\14021 Quirk West Building\Contract Documents\14021 FP-102.dwg
AutoCAD SHX Text
SCALE: 1/8"= 1'-0"
AutoCAD SHX Text
NEW SPRINKLER HEAD. CONNECT TO EXISTING SPK. BRANCH PIPING 1-1/2" OR LARGER (TYP). EXISTING SPRINKLER HEAD TO REMAIN. REMOVE EXISTING SPRINKLER HEAD AND CAP PIPING AT EXISTING BRANCH PIPING.
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
3
Page 4: INSTALL NEW PIPING AND UPRIGHT SPRINKLER HEADS WITH …€¦ · office 018 showers 031 stair c girls locker room 035 storage rm 022 outdoor sto. 023 mech eq 024 mech eq 025 tactical

A

B

C

D

E

F

G

H

J

K

M

N

P

L

2 3 4 6 8.1 9 10 11 12 13 15 17 18 197 14

2 3 4 6 9 10 11 12 13 15 17 18 198

A

B

C

D

E

F

G

H

J

K

M

N

P

L

STAIR G STAIR HSTAIR F

STAIR BSTAIR C

STAIR A STAIR D

POLICE ACADEMY GYMNASIUM AUDITORIUM PAL GYMNASIUM

MECHANICAL EQUIPMENT301

LOW ROOF-1 LOW ROOF-2

DRAWING NO.:

ISSUE NO. ISSUE DATE DESCRIPTION

PROJECT NO.: 1517-01

Alterations to Quirk WestBuilding

50 Williams StreetHartford, CT

NORTH

KEY PLAN

WILLIAMS STREET

33 North Plains Industrial RdWallingford, CT 06492Tel: 203.467.4370 Fax: 203.793.7729Web: www.iesllc.biz

Innovative EngineeringServices, LLCAn Integrated engineering + design firm

I E S

MECH'L/ELEC'L/PLUMBING ENGINEERS

ENVIRONMENTAL ENGINEER

FUSS & O'NEILL ENVIROSCIENCE, LLC146 HARTFORD ROADMANCHESTER, CT 06040

ELEVATOR CONSULTANT

810-82ND STREETNORTH BERGEN, NJ 07047

VerTacan, LLC

CONSULTANTS

POOL CONSULTANT

333 WESTCHESTER AVENUEWHITE PLAINS NY, 10606

WA

LNU

T ST

REET

ALB

AN

Y A

VEN

UE

07-22-20161 100% SUBMISSION

FP-103

THIRD FLOORFIRE PROTECTION PLAN

SCALE: 1/8"=1'-0"

THIRD FLOOR FIRE PROTECTION PLAN

AutoCAD SHX Text
EXISTING SPRINKLERS TO REMAIN
AutoCAD SHX Text
EXISTING SPRINKLERS TO REMAIN
AutoCAD SHX Text
EXISTING SPRINKLERS TO REMAIN
AutoCAD SHX Text
G:\IES Projects\2014 Projects\14021 Quirk West Building\Contract Documents\14021 FP-103.dwg
AutoCAD SHX Text
SCALE: 1/8"= 1'-0"
Page 5: INSTALL NEW PIPING AND UPRIGHT SPRINKLER HEADS WITH …€¦ · office 018 showers 031 stair c girls locker room 035 storage rm 022 outdoor sto. 023 mech eq 024 mech eq 025 tactical

DRAWING NO.:

ISSUE NO. ISSUE DATE DESCRIPTION

PROJECT NO.: 1517-01

Alterations to Quirk WestBuilding

50 Williams StreetHartford, CT

NORTH

KEY PLAN

WILLIAMS STREET

33 North Plains Industrial RdWallingford, CT 06492Tel: 203.467.4370 Fax: 203.793.7729Web: www.iesllc.biz

Innovative EngineeringServices, LLCAn Integrated engineering + design firm

I E S

MECH'L/ELEC'L/PLUMBING ENGINEERS

ENVIRONMENTAL ENGINEER

FUSS & O'NEILL ENVIROSCIENCE, LLC146 HARTFORD ROADMANCHESTER, CT 06040

ELEVATOR CONSULTANT

810-82ND STREETNORTH BERGEN, NJ 07047

VerTacan, LLC

CONSULTANTS

POOL CONSULTANT

333 WESTCHESTER AVENUEWHITE PLAINS NY, 10606

WA

LNU

T ST

REET

ALB

AN

Y A

VEN

UE

07-22-20161 100% SUBMISSION

FP-200

FIRE PROTECTION NOTES,LEGENDS, SCHEDULES AND

DETAILSSCALE: AS NOTED

FIRE PROTECTION GENERAL NOTES

FIRE PROTECTION DEMOLITION NOTES

ABBREVIATIONS

FIRE PROTECTION PIPING LEGEND

FIRE PROTECTION SYMBOL LEGEND

AUXILIARY DRAIN DETAIL RELOCATED SPRINKLER INSTALLATION DETAIL

HYDRAULIC SYSTEM SIGNAGE DETAIL

TYPICAL SPRINKLER HEAD DROP DETAIL

SEISMIC SEPARATION ASSEMBLY DETAIL

AutoCAD SHX Text
G:\IES Projects\2014 Projects\14021 Quirk West Building\Contract Documents\14021 FP-200.dwg
AutoCAD SHX Text
FIRE PROTECTION GENERAL NOTES 1.THESE GENERAL NOTES ARE APPLICABLE TO ALL FIRE PROTECTION DRAWINGS. THESE GENERAL NOTES ARE APPLICABLE TO ALL FIRE PROTECTION DRAWINGS. 2.DRAWINGS ARE DIAGRAMMATIC AND SHOW THE GENERAL INTENT OF WORK, SEE DETAILS, RISERS, DRAWINGS ARE DIAGRAMMATIC AND SHOW THE GENERAL INTENT OF WORK, SEE DETAILS, RISERS, AND SPECIFICATIONS FOR ADDITIONAL INFORMATION. 3.THE DRAWINGS INDICATE A SUGGESTED SPRINKLER HEAD LAYOUT AND THAT EACH AREA IS THE DRAWINGS INDICATE A SUGGESTED SPRINKLER HEAD LAYOUT AND THAT EACH AREA IS COVERED BY SPRINKLER PROTECTION AS REQUIRED PER NFPA-13. THE SPRINKLER QUANTITIES SHALL NOT BE COUNTED, AS A TAKE OFF OR AS EXACT LOCATIONS. REFER TO NFPA 13 FOR EXACT SPACING, DENSITY, AND LOCATION REQUIREMENTS. 4.SPRINKLERS IN FINISHED CEILING AREAS SHALL ALWAYS BE LOCATED IN THE CENTER OF CEILING SPRINKLERS IN FINISHED CEILING AREAS SHALL ALWAYS BE LOCATED IN THE CENTER OF CEILING TILES UNLESS INDICATED OTHERWISE. 5.THE FIRE PROTECTION CONTRACTOR SHALL REVIEW THE ARCHITECTURAL REFLECTED CEILING PLANS THE FIRE PROTECTION CONTRACTOR SHALL REVIEW THE ARCHITECTURAL REFLECTED CEILING PLANS AS PART OF THIS CONTRACT FOR ADDITIONAL INFORMATION SUCH AS CEILING HEIGHTS, TYPES, SOFFITS AND OR OTHER DEVICE LOCATIONS. 6.THE FIRE PROTECTION CONTRACTOR SHALL REVIEW THE ELECTRICAL DIVISION DRAWINGS AND THE FIRE PROTECTION CONTRACTOR SHALL REVIEW THE ELECTRICAL DIVISION DRAWINGS AND COORDINATE THE FIRE PROTECTION WORK WITH LOCATIONS OF LIGHTS, AND CEILING MOUNTED DEVICES WHICH MAY INTERFERE WITH SPRINKLER HEAD LOCATIONS OR SPRAY PATTERNS. 7.THE FIRE PROTECTION CONTRACTOR SHALL REVIEW THE HVAC DIVISION DRAWINGS AND COORDINATE THE FIRE PROTECTION CONTRACTOR SHALL REVIEW THE HVAC DIVISION DRAWINGS AND COORDINATE THE FIRE PROTECTION WORK WITH LOCATIONS OF CEILING MOUNTED DEVICES SUCH AS DIFFUSERS, GRILLS, REGISTORS, AND ALSO THE LOCATIONS OF HEAT PRODUCING EQUIPMENT AND DUCTWORK REQUIRING SPRINKLER PROTECTION BELOW IT. 8.THE FIRE PROTECTION CONTRACTOR SHALL PROVIDE PIPE EXPANSION JOINTS ALL BUILDING THE FIRE PROTECTION CONTRACTOR SHALL PROVIDE PIPE EXPANSION JOINTS ALL BUILDING EXPANSION JOINT LOCATIONS AND EXPANSION LOOPS AT ALL BUILDING EXPANSION/SEISMIC JOINT LOCATIONS AS REQUIRED PER NFPA 13 AND BUILDING CODES. REVIEW ARCHITECTURAL AND STRUCTURAL DRAWINGS FOR EXACT LOCATIONS OF EXPANSION AND SEISMIC JOINTS. 9.THE FIRE PROTECTION CONTRACTOR SHALL INSTALL ALL PIPING EQUIPMENT AND ACCESSORIES IN THE FIRE PROTECTION CONTRACTOR SHALL INSTALL ALL PIPING EQUIPMENT AND ACCESSORIES IN ACCORDANCE WITH THE LATEST STATE BUILDING CODE AND LOCAL AUTHORITIES HAVING JURISDICTION. COORDINATION BETWEEN TRADES IS REQUIRED TO INSURE COMPLIANCE WITH THE GOVERNING CODES. 10.ALL PIPING, EQUIPMENT OR ACCESSORIES INSTALLED IN PLENUM RATED CEILINGS SHALL BE LISTED ALL PIPING, EQUIPMENT OR ACCESSORIES INSTALLED IN PLENUM RATED CEILINGS SHALL BE LISTED AND APPROVED FOR SUCH INSTALLATION.
AutoCAD SHX Text
FIRE PROTECTION DEMOLITION NOTES 1.THE FIRE PROTECTION CONTRACTOR SHALL VISIT THE SITE AND BECOME FAMILIAR WITH THE THE FIRE PROTECTION CONTRACTOR SHALL VISIT THE SITE AND BECOME FAMILIAR WITH THE EXISTING SYSTEMS AND CONDITIONS IN AREAS OF RENOVATION. 2.ALL EXISTING PIPING AND EQUIPMENT SHOWN HAS BEEN TAKEN FROM THE BEST AVAILABLE ALL EXISTING PIPING AND EQUIPMENT SHOWN HAS BEEN TAKEN FROM THE BEST AVAILABLE EXISTING INFORMATION. THE DRAWINGS ARE DIAGRAMMATIC AND ALL PIPING AND DEVICES MAY NOT BE SHOWN.THE INTENT OF THESE DRAWINGS IS THAT IN ALL AREAS OF RENOVATIONS THAT THESE SYSTEMS ARE REMOVED AS NOTED WHETHER OR NOT SHOWN. 3.THE FIRE PROTECTION CONTRACTOR SHALL REMOVE ALL FIRE PROTECTION PIPING SYSTEMS THE FIRE PROTECTION CONTRACTOR SHALL REMOVE ALL FIRE PROTECTION PIPING SYSTEMS INCLUDING BUT NOT LIMITED TO SPRINKLER/STANDPIPE, SPRINKLERS HANGERS, VALVES, SWITCHES, AND DEVICES AS SHOW OR INDICATED ON THE DRAWINGS. COORDINATE WITH ELECTRICAL CONTRACTOR ALL WIRING WORK RELATED TO DEVICES BEING REMOVED. 4.ALL PIPING TO BE REMOVED SHALL BE REMOVED COMPLETELY OR CAPPED AS SHOWN WITHOUT ALL PIPING TO BE REMOVED SHALL BE REMOVED COMPLETELY OR CAPPED AS SHOWN WITHOUT LEAVING ANY DEAD ENDED PIPING OR ABANDONED PIPING. 5.NO FIRE PROTECTION EQUIPMENT OR DEVICES THAT HAVE BEEN DISCONNECTED OR ABANDONED NO FIRE PROTECTION EQUIPMENT OR DEVICES THAT HAVE BEEN DISCONNECTED OR ABANDONED SHALL REMAIN. 6.IT IS THE INTENT OF THESE DRAWINGS THAT ANY AND ALL DEVICES REMOVED SHALL NOT BE IT IS THE INTENT OF THESE DRAWINGS THAT ANY AND ALL DEVICES REMOVED SHALL NOT BE REUSED SUCH AS SPRINKLERS, BUT ONLY NEW SHALL BE INSTALLED. 7.ANY SYSTEM OR EQUIPMENT TO REMAIN ACTIVE DURING RENOVATION SHALL BE KEPT IN OPERATION ANY SYSTEM OR EQUIPMENT TO REMAIN ACTIVE DURING RENOVATION SHALL BE KEPT IN OPERATION BY PROVIDING TEMPORARY CONNECTIONS AS REQUIRED UNTIL NEW SYSTEMS ARE INSTALLED AND OPERATIONAL. 8.ALL SERVICE INTERRUPTIONS SHALL BE COORDINATED WITH THE OWNER AND, THE FIRE MARSHAL ALL SERVICE INTERRUPTIONS SHALL BE COORDINATED WITH THE OWNER AND, THE FIRE MARSHAL MUST BE CONTACTED IN ADVANCE PRIOR TO COMMENCEMENT OF ANY WORK. 9.THE FIRE MARSHAL AND OR THE INSURANCE UNDERWRITER SHALL BE CONTACTED TO REVIEW AND THE FIRE MARSHAL AND OR THE INSURANCE UNDERWRITER SHALL BE CONTACTED TO REVIEW AND APPROVE THE EXTENT OR PHASING OF THE FIRE PROTECTION DEMOLITION IN ORDER TO PROTECT THE OCCUPANTS AND PROPERTY.THESE DOCUMENTS DO NOT ADDRESS THE PHASING OF THE SYSTEM REMOVAL, ONLY THE EXTENT. 10.THE FIRE PROTECTION CONTRACTOR SHALL ALSO REVIEW THE ARCHITECTURAL DEMOLITION DRAWINGS THE FIRE PROTECTION CONTRACTOR SHALL ALSO REVIEW THE ARCHITECTURAL DEMOLITION DRAWINGS AS PART OF THIS CONTRACT FOR ADDITIONAL INFORMATION AND REQUIREMENTS.
AutoCAD SHX Text
ABOVE FINISH FLOOR
AutoCAD SHX Text
AFF
AutoCAD SHX Text
CONNECT TO EXISTING
AutoCAD SHX Text
CTE
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
EX
AutoCAD SHX Text
EXISTING TO REMAIN
AutoCAD SHX Text
ETR
AutoCAD SHX Text
GALLONS PER MINUTE
AutoCAD SHX Text
GPM
AutoCAD SHX Text
NOT IN CONTRACT
AutoCAD SHX Text
NIC
AutoCAD SHX Text
TAMPER SWITCH
AutoCAD SHX Text
TS
AutoCAD SHX Text
TYPICAL
AutoCAD SHX Text
TYP
AutoCAD SHX Text
VERIFY IN FIELD
AutoCAD SHX Text
VIF
AutoCAD SHX Text
FLOW DIRECTION
AutoCAD SHX Text
SP
AutoCAD SHX Text
WET SPRINKLER SYSTEM
AutoCAD SHX Text
PIPE DOWN
AutoCAD SHX Text
PIPE DROP
AutoCAD SHX Text
PIPE UP
AutoCAD SHX Text
REMOVE EXISTING PIPING OR EQUIPMENT
AutoCAD SHX Text
FLUSHING CONNECTION
AutoCAD SHX Text
CONCEALED SPRINKLER
AutoCAD SHX Text
PENDANT SPRINKLER
AutoCAD SHX Text
UPRIGHT SPRINKLER
AutoCAD SHX Text
WET SIDEWALL SPRINKLER
AutoCAD SHX Text
CONNECT TO EXISTING
AutoCAD SHX Text
PLUGGED OR CAPPED PIPE
AutoCAD SHX Text
1" PLUG
AutoCAD SHX Text
AUXILIARY DRAIN
AutoCAD SHX Text
SIGN WITH CHAIN
AutoCAD SHX Text
1" GLOBE VALVE
AutoCAD SHX Text
1" x 4" NIPPLE
AutoCAD SHX Text
1" THREADED OUTLET
AutoCAD SHX Text
MAIN PIPING
AutoCAD SHX Text
N.T.S.
AutoCAD SHX Text
GALVANIZED ALL-THREADED ROD ATTACHED TO STRUCTURE
AutoCAD SHX Text
PIPE HANGER
AutoCAD SHX Text
SPRINKLER BRANCH PIPING
AutoCAD SHX Text
EXT'G THREADED IRON ELBOW FITTING (TYPICAL)
AutoCAD SHX Text
EXT'G THREADED STEEL DROP PIPE (TYPICAL)
AutoCAD SHX Text
EXT'G REDUCER FITTING (TYPICAL)
AutoCAD SHX Text
EXT'G SPRINKLER HEAD TO BE REMOVED
AutoCAD SHX Text
EXT'G HUNG CEILING PANEL OR SHEETROCK (REFER TO ARCHITECTURAL PLANS FOR CEILING TYPES)
AutoCAD SHX Text
NEW THREADED IRON ELBOW FITTING (TYPICAL)
AutoCAD SHX Text
NEW THREADED STEEL DROP PIPE (TYPICAL)
AutoCAD SHX Text
NEW REDUCER FITTING (TYPICAL)
AutoCAD SHX Text
NEW SPRINKLER HEAD LOCATION, REFER TO SPECIFICATIONS AND PLANS FOR TYPES (TYPICAL).
AutoCAD SHX Text
NEW THREADED STEEL BRANCH PIPING (TYPICAL)
AutoCAD SHX Text
EXT'G THREADED STEEL BRANCH PIPING (TYPICAL)
AutoCAD SHX Text
N.T.S.
AutoCAD SHX Text
HYDRAULIC-SYSTEM
AutoCAD SHX Text
THIS BUILDING IS PROTECTED BY A HYDRAULICALLY DESIGNED AUTOMATIC SPRINKLER SYSTEM
AutoCAD SHX Text
HYDRAULIC SIGN NOTES: 1.THE FIRE PROTECTION CONTRACTOR SHALL IDENTIFY EACH THE FIRE PROTECTION CONTRACTOR SHALL IDENTIFY EACH HYDRAULIC DESIGNED SPRINKLER SYSTEM WITH A PERMANENTLY MARKED, WATERPROOF METAL SIGN SECURED WITH CORROSION-RESISTANT WIRE, CHAIN OR OTHER APPROVED MEANS. SUCH SIGNAGE SHALL BE PLACED AT EACH ALARM VALVE SUPPLYING THE CORRESPONDING HYDRAULICALLY DESIGNED AREA. THE SIGN SHALL INCLUDE THE FOLLOWING INFORMATION: A.LOCATION OF DESIGN AREA OR AREAS. LOCATION OF DESIGN AREA OR AREAS. B.DISCHARGE DENSITIES OVER THE DESIGN AREA OR AREAS. DISCHARGE DENSITIES OVER THE DESIGN AREA OR AREAS. C.REQUIRED FLOW AND RESIDUAL PRESSURE DEMAND AT REQUIRED FLOW AND RESIDUAL PRESSURE DEMAND AT BASE OF RISER. D.OCCUPANCY CLASSIFICATION OR COMMODITY OCCUPANCY CLASSIFICATION OR COMMODITY CLASSIFICATION AND MAXIMUM PERMITTED STORAGE HEIGHT AND CONFIGURATION. E.HOSE STREAM DEMAND INCLUDED IN ADDITION TO THE HOSE STREAM DEMAND INCLUDED IN ADDITION TO THE SPRINKLER DEMAND.
AutoCAD SHX Text
SQ FT
AutoCAD SHX Text
GPM SQ FT
AutoCAD SHX Text
GPM
AutoCAD SHX Text
PSI
AutoCAD SHX Text
LOCATION
AutoCAD SHX Text
BASIS OF DESIGN
AutoCAD SHX Text
SYSTEM DEMAND
AutoCAD SHX Text
1. DENSITY
AutoCAD SHX Text
1. GPM DISCHARGE
AutoCAD SHX Text
BASE OF THE RISER
AutoCAD SHX Text
NO. OF SPRINKLERS
AutoCAD SHX Text
2. DESIGNED AREA OF DISCHARGE
AutoCAD SHX Text
2. RESIDUAL PRESSURE AT THE
AutoCAD SHX Text
N.T.S.
AutoCAD SHX Text
2. THIS SPRINKLER HEAD DROP IS APPLICABLE ONLY WHERE IT IS NOT NECESSARY TO RETAIN AN UPRIGHT SPRINKLER FOR PROTECTION OF COMBUSTIBLE CONSTRUCTION ABOVE THE CEILING.
AutoCAD SHX Text
1. ADJUST SPRINKLER DROPS AS NECESSARY TO CLEAR OBSTRUCTIONS SUCH AS STRUCTURAL COMPONENTS, DUCTWORK, LIGHT FIXTURES, ETC. PROVIDE A PIPE HANGER IF THE HORIZONTAL OFFSET LENGTH EXCEEDS 24 INCHES.
AutoCAD SHX Text
SPRINKLER BRANCH LINE
AutoCAD SHX Text
N.T.S.
AutoCAD SHX Text
NOTES:
AutoCAD SHX Text
1" X 1/2" PIPE REDUCING COUPLING
AutoCAD SHX Text
SUSPENDED CEILING
AutoCAD SHX Text
REFER TO FLOOR PLANS FOR SPRINKLER HEAD TYPE
AutoCAD SHX Text
PROVIDE LENGTH TO SUIT
AutoCAD SHX Text
PROVIDE LENGTH TO SUIT
AutoCAD SHX Text
CHROME ESCUTCHEON PLATE
AutoCAD SHX Text
3. ON EXISTING PIPING SYSTEMS CONTRACTOR TO VERIFY TEE OUTLET SIZE. PROVIDE EXTRA HEAVY NIPPLE MAXIMUM 4" LENGTH.
AutoCAD SHX Text
%%UELEVATION
AutoCAD SHX Text
10" LONG NIPPLE "C"
AutoCAD SHX Text
"A"
AutoCAD SHX Text
C
AutoCAD SHX Text
L
AutoCAD SHX Text
2 ELLS
AutoCAD SHX Text
10" LONG NIPPLE "D"
AutoCAD SHX Text
COUPLING
AutoCAD SHX Text
"B"
AutoCAD SHX Text
C
AutoCAD SHX Text
L
AutoCAD SHX Text
FIRE SPRINKLER MAIN
AutoCAD SHX Text
2 ELLS AND NIPPLE "E"
AutoCAD SHX Text
NORMAL POSITION
AutoCAD SHX Text
PLAN
AutoCAD SHX Text
LONGITUDINAL MOVEMENT
AutoCAD SHX Text
COUPLING (TYPICAL)
AutoCAD SHX Text
FIRE SPRINKLER MAIN
AutoCAD SHX Text
"A"
AutoCAD SHX Text
ELL
AutoCAD SHX Text
"C"
AutoCAD SHX Text
ELL
AutoCAD SHX Text
ELL
AutoCAD SHX Text
"B"
AutoCAD SHX Text
VERTICAL MOVEMENT
AutoCAD SHX Text
NORMAL POSITION
AutoCAD SHX Text
"D"
AutoCAD SHX Text
ELL
AutoCAD SHX Text
NIPPLE "E" 8 1/2" FOR 3" PIPE 7 1/2" FOR 2 1/2" PIPE
AutoCAD SHX Text
LATERAL MOVEMENT
AutoCAD SHX Text
HORIZONTAL VIEWS
AutoCAD SHX Text
N.T.S.
AutoCAD SHX Text
SPRINKLER
AutoCAD SHX Text
SPK
AutoCAD SHX Text
REMOVE EXISTING SPRINKLER HEAD AND INSTALL
AutoCAD SHX Text
NEW HEAD WHERE SHOWN