INSTALLATION & INSTALLATION & COMMISSIONINGCOMMISSIONING
Technical Training 2007Technical Training 2007
5WSS 5WSS InstallationInstallation
• Hanging the UnitHanging the Unit
• Location ConsiderationsLocation Considerations
• Refrigerant PipingRefrigerant Piping
• Water PipingWater Piping
• Cleaning & Flushing SystemCleaning & Flushing System
Technical Training 2007Technical Training 2007
Hanging the UnitHanging the Unit
• Recommend to use Recommend to use Rubber isolatorRubber isolator on the brackets to reduce on the brackets to reduce
noise and vibration transmissions noise and vibration transmissions
Technical Training 2007Technical Training 2007
Location ConsiderationsLocation Considerations
1. Provide recommended service clearance to assure easy 1. Provide recommended service clearance to assure easy access for:access for:
• Water pipingWater piping
• Electrical connectionsElectrical connections
• Periodic maintenance and occasional servicePeriodic maintenance and occasional service
2.Recommended location (sound emission is outside the occupied space):
• Corridor
• Bathroom
• Special Room for Air-Conditioning Unit
Technical Training 2007Technical Training 2007
Refrigerant PipingRefrigerant Piping
Three major things to be concerned:Three major things to be concerned:• Piping LengthPiping Length
• ElevationElevation
• No. of bendsNo. of bends
Choose shortest path
Follow the recommended data in the table (Installation Manual)
Technical Training 2007Technical Training 2007
Refrigerant PipingRefrigerant PipingAdditional Charges for 5WSS Additional Charges for 5WSS
unitunit
• The pre-charged of R410A in The pre-charged of R410A in the 5WSS unit is suitable for the 5WSS unit is suitable for Standard Standard
pipe of length up to:pipe of length up to:
– 2 meter for 2 meter for 5WSS10/15/20/25/30/40/50 5WSS10/15/20/25/30/40/50 ARAR
– 5 meter for 5WSS60AR5 meter for 5WSS60AR
• When the piping is more than When the piping is more than the standard pipe length, the standard pipe length, please add accordinglyplease add accordingly
Technical Training 2007Technical Training 2007
Water PipingWater Piping
• Males couplings, BSPPMales couplings, BSPP
• no pipe insulation required no pipe insulation required
Water IN
Water OUT
Technical Training 2007Technical Training 2007
Water PipingWater Piping
Flexible hoseFlexible hose
• To ease water pipe installationTo ease water pipe installation
• Steel reinforced PVC hose with 2 female BSPP couplings at Steel reinforced PVC hose with 2 female BSPP couplings at the end.the end.
• Use O-rings provided to have a leak-proof jointUse O-rings provided to have a leak-proof joint
Female couplings
Technical Training 2007Technical Training 2007
Water PipingWater Piping
Pressure gauge
Water Inlet
Water Outlet
Gate Valve
Strainer
Automatic Shut-off
Valve
Flexible joint
Thermometer
Balancing Valve
WSS Unit
Technical Training 2007Technical Training 2007
Cleaning and Flushing SystemCleaning and Flushing SystemSystem must be cleaned and flushed
Close all air vents after filling
Fill with water and open all air vents
Individual supply and return pipes connected first
Drains at the lowest point open
Check piping leaking
Check all air vents in sequence to bleed off any trapped air
Short-circuited connection to the supply and return pipes removed
Open all the drains and vents to complete drain down
Water valves set to make up for the required flow rate
Technical Training 2007Technical Training 2007
Operating RangeThe operating range for EWT The operating range for EWT
is 12°C to 45°C.is 12°C to 45°C.
Rated Conditions:Rated Conditions:
Cooling Cooling
Ambient (DB/WB) : 27°C/19°C Ambient (DB/WB) : 27°C/19°C
Water IN: 30°C Water IN: 30°C Water OUT: 35°CWater OUT: 35°C
Heating:Heating:
Ambient (DB) : 20°CAmbient (DB) : 20°C
Water IN: 20°CWater IN: 20°C
Technical Training 2007Technical Training 2007
WH InstallationWH Installation
• Hanging the UnitHanging the Unit
• Location of HangingLocation of Hanging
• DuctworkDuctwork
• Water PipingWater Piping
• DrainageDrainage
• Cleaning & Flushing SystemCleaning & Flushing System
Technical Training 2007Technical Training 2007
Hanging the UnitHanging the Unit
Hanger threaded rods
Bolted to underside of ceiling slab
Technical Training 2007Technical Training 2007
Hanging the UnitHanging the Unit
• Recommend to use Recommend to use vibration isolatorsvibration isolators on on
the brackets to reduce noise and vibration the brackets to reduce noise and vibration
transmissions transmissions
• Spring isolatorSpring isolator to be used for better vibration to be used for better vibration
control.control.
spring
bottom washer
PVC tube
Upper washer, welded onto bracket
nut
bracket
Technical Training 2007Technical Training 2007
Hanging the UnitHanging the Unit
• Spring kit installation Spring kit installation
- Insert the threaded rod through the bracket- Insert the threaded rod through the bracket
- Insert the rod through the piece of soft PVC - Insert the rod through the piece of soft PVC
plastic tube. The tube will go through the plastic tube. The tube will go through the
mounting hole on the bracketmounting hole on the bracket
- Insert the spring over the plastic tube- Insert the spring over the plastic tube
- Screw in the bottom washer and locking nut- Screw in the bottom washer and locking nut
Spring Length Nominal load Deflection Natural frequencyModel (mm) (kg) (mm) (Hz)WH11-20B/BR 43 20 8 4.3 ~ 5WH25/30 B/BR 51 32 11 4.3 ~ 5WH40/50 B/BR 55 40 10 4.3 ~ 5WH60/70 B/BR 60 50 10 4.3 ~ 5
Technical Training 2007Technical Training 2007
Location of hangingLocation of hanging
Install at a location that gives sufficient space clearance for:Install at a location that gives sufficient space clearance for:
• Hanging the unitHanging the unit
• Installing and maintaining the water pipingInstalling and maintaining the water piping
• Installing and maintaining the duct workInstalling and maintaining the duct work
• Accessing the unit’s internal parts via access panelAccessing the unit’s internal parts via access panel
• Removal of air filter for cleaningRemoval of air filter for cleaning
Technical Training 2007Technical Training 2007
Location of hangingLocation of hanging
supply air
return air
500 mm
800 mm
800 mm
1200 mm
air filter
access panel
Dia. 23
Technical Training 2007Technical Training 2007
DuctworkDuctwork
Supply & ReturnSupply & Return
• Use good acoustic lined ductsUse good acoustic lined ducts
• Return air ducts are recommended where noise is criticalReturn air ducts are recommended where noise is critical
• Make sure ducts are connected firmly to prevent air Make sure ducts are connected firmly to prevent air leakageleakage
Technical Training 2007Technical Training 2007
DuctworkDuctwork
In general, there are 2 methods of applying the unit:In general, there are 2 methods of applying the unit:
1. Ducted supply, free return1. Ducted supply, free return
(a)(a)
WH unit
Supply duct
diffusersFree return
within the room
FREE
RETURN
EXPOSED
- The unit is left exposed within the room together with the - The unit is left exposed within the room together with the supply ductwork supply ductwork
Technical Training 2007Technical Training 2007
DuctworkDuctwork
1. Ducted supply, free return1. Ducted supply, free return
(b)(b)
WH unit
supply duct
ceiling boardreturn grille
diffusers
FREE RETURN WITHIN CEILING
- The unit is within the ceiling space acts as a return plenum.- The unit is within the ceiling space acts as a return plenum.
Technical Training 2007Technical Training 2007
DuctworkDuctwork
2. Ducted supply, ducted return2. Ducted supply, ducted return
- Useful when noise attenuation is critical in the room- Useful when noise attenuation is critical in the room
WH unit
supply duct
ceiling board
return grille
diffusers
return duct
Technical Training 2007Technical Training 2007
Water PipingWater Piping
Water OutWater In
WH Unit
• Males couplingsMales couplings
• In general, no pipe insulation required In general, no pipe insulation required
Technical Training 2007Technical Training 2007
Water PipingWater Piping
Flexible hoseFlexible hose
• To ease water pipe installationTo ease water pipe installation
• Steel reinforced PVC hose with 2 female BSP couplings at Steel reinforced PVC hose with 2 female BSP couplings at the end.the end.
• Use O-rings provided to have a leak-proof jointUse O-rings provided to have a leak-proof joint
Female couplings
Technical Training 2007Technical Training 2007
Water PipingWater Piping
Pressure gauge
Water Inlet
Water Outlet
Gate Valve
Strainer
Automatic Shut-off
Valve
Flexible joint
Thermometer
Balancing Valve
WH Unit
Technical Training 2007Technical Training 2007
DrainageDrainage
• Slanting drain pan design Slanting drain pan design
Slanting drain pan Drain
• Drain pipe must be inclined at an angle to allow free drainageDrain pipe must be inclined at an angle to allow free drainage
Drain pipe, ¾”
Slope downwards to the nearest drain(recommended 1:100)
U-Trap
Technical Training 2007Technical Training 2007
Cleaning and Flushing SystemCleaning and Flushing SystemSystem must be cleaned and flushed
Close all air vents after filling
Fill with water and open all air vents
Individual supply and return pipes connected first
Drains at the lowest point open
Check piping leaking
Check all air vents in sequence to bleed off any trapped air
Short-circuited connection to the supply and return pipes removed
Open all the drains and vents to complete drain down
Water valves set to make up for the required flow rate
Technical Training 2007Technical Training 2007
Operating RangeThe operating range for EWT The operating range for EWT
is 12°C to 45°C.is 12°C to 45°C.
Rated Conditions:Rated Conditions:
Cooling Cooling
Ambient (DB/WB) : 27°C/19°C Ambient (DB/WB) : 27°C/19°C
Water IN: 30°C Water IN: 30°C Water OUT: 35°CWater OUT: 35°C
Heating:Heating:
Ambient (DB) : 20°CAmbient (DB) : 20°C
Water IN: 20°CWater IN: 20°C