+ All Categories
Home > Documents > INSTALLATION & COMMISSIONING GUDELINE FOR A1000 · PDF fileINSTALLATION & COMMISSIONING...

INSTALLATION & COMMISSIONING GUDELINE FOR A1000 · PDF fileINSTALLATION & COMMISSIONING...

Date post: 14-Feb-2018
Category:
Upload: lediep
View: 275 times
Download: 14 times
Share this document with a friend
14
INSTALLATION & COMMISSIONING GUDELINE FOR A1000 AC DRIVE ESP:IA:INC:A1000:00… Dt. 28.09.10 1 **This procedure shall be used alongwith technical manual for A1000 drive. Figure below illustrates how to configure drive & motor to operate with peripheral devices: Note: For more detailed instructions on how to install each device, refer to the specific manual for that device.
Transcript
Page 1: INSTALLATION & COMMISSIONING GUDELINE FOR A1000 · PDF fileINSTALLATION & COMMISSIONING GUDELINE FOR A1000 AC DRIVE ESP:IA:INC:A1000:00 Dt. 28.09.10 1 **This procedure shall be used

  

INSTALLATION & COMMISSIONING GUDELINE FOR A1000 AC DRIVE

ESP:IA:INC:A1000:00… Dt. 28.09.10    1  

**This procedure shall be used alongwith technical manual for A1000 drive.

Figure below illustrates how to configure drive & motor to operate with peripheral devices:

Note: For more detailed instructions on how to install each device, refer to the specific manual for that device.

Page 2: INSTALLATION & COMMISSIONING GUDELINE FOR A1000 · PDF fileINSTALLATION & COMMISSIONING GUDELINE FOR A1000 AC DRIVE ESP:IA:INC:A1000:00 Dt. 28.09.10 1 **This procedure shall be used

  

INSTALLATION & COMMISSIONING GUDELINE FOR A1000 AC DRIVE

ESP:IA:INC:A1000:00… Dt. 28.09.10    2  

Power Circuit Connections:

Refer to diagrams in this section when wiring the drive’s main circuit. Connections varies based on drive capacity. The DC power supply for the main circuit also provides power to the control circuit.

NOTE 1: Do not use the negative DC bus terminal “-” as a ground terminal. This terminal is at high DC voltage potential. Improper wiring connections could damage the drive.

NOTE2: Remove the jumper when installing a DC reactor for CIMR-AD4A0002 to CIMR-AD4A0044 models

Three Phase 400V Class (CIMR-AD4A0002 to CIMR-AD4A0044)

Three Phase 400V Class (CIMR-AD4A0058 & CIMR-AD4A0072)

Three Phase 400V Class (CIMR-AD4A0088 & CIMR-AD4A0675)

Page 3: INSTALLATION & COMMISSIONING GUDELINE FOR A1000 · PDF fileINSTALLATION & COMMISSIONING GUDELINE FOR A1000 AC DRIVE ESP:IA:INC:A1000:00 Dt. 28.09.10 1 **This procedure shall be used

  

INSTALLATION & COMMISSIONING GUDELINE FOR A1000 AC DRIVE

ESP:IA:INC:A1000:00… Dt. 28.09.10    3  

Standard Connection Diagram : Example, 200V class 3.7kW

Page 4: INSTALLATION & COMMISSIONING GUDELINE FOR A1000 · PDF fileINSTALLATION & COMMISSIONING GUDELINE FOR A1000 AC DRIVE ESP:IA:INC:A1000:00 Dt. 28.09.10 1 **This procedure shall be used

  

INSTALLATION & COMMISSIONING GUDELINE FOR A1000 AC DRIVE

ESP:IA:INC:A1000:00… Dt. 28.09.10    4  

Removing the terminal cover of drives : CIMR-AD4A0002 to CIMR-AD4A0044 (IP20/NEMA Type 1 Enclosure Drives)

1. Loosen the terminal screw cover

2. Push in on the hook located on the bottom of the terminal cover & gently pull forward

3. Re-attaching terminal cover after wiring:

Page 5: INSTALLATION & COMMISSIONING GUDELINE FOR A1000 · PDF fileINSTALLATION & COMMISSIONING GUDELINE FOR A1000 AC DRIVE ESP:IA:INC:A1000:00 Dt. 28.09.10 1 **This procedure shall be used

  

INSTALLATION & COMMISSIONING GUDELINE FOR A1000 AC DRIVE

ESP:IA:INC:A1000:00… Dt. 28.09.10    5  

Removing the terminal cover of drives : CIMR-AD4A0058 to CIMR-AD4A0675 (IP00 Enclosure Drives)

1. Loosen the screws (do not completely remove the screws) CIMR-AD4A0208 to 675 has three screws on the top terminal cover :

2. Pull forward on terminal cover to free it from the drive:

Reattaching the terminal cover :

Page 6: INSTALLATION & COMMISSIONING GUDELINE FOR A1000 · PDF fileINSTALLATION & COMMISSIONING GUDELINE FOR A1000 AC DRIVE ESP:IA:INC:A1000:00 Dt. 28.09.10 1 **This procedure shall be used

  

INSTALLATION & COMMISSIONING GUDELINE FOR A1000 AC DRIVE

ESP:IA:INC:A1000:00… Dt. 28.09.10    6  

Removing & reattaching the digital operator:

1. While pinching inwards on the hook located on the right side of the digital operator, pull forward and remove the operator from the drive.

2. Insert the digital operator into the opening in the front cover while aligning it with the notches on the left side of the opening. Next press gently on the right side of the operator until it clicks into place.

Removing the front cover from models CIMR-AD4A0002 to 4A0044:

After removing the terminal cover and the digital operator, loosen the screw that affixes the front cover (model CIMR-AD4A0031, 4A0038 do not use a screw to affix the front cover). Pinch inwards on hooks found on each side of the front cover, then pull forward to remove it from the drive:

Page 7: INSTALLATION & COMMISSIONING GUDELINE FOR A1000 · PDF fileINSTALLATION & COMMISSIONING GUDELINE FOR A1000 AC DRIVE ESP:IA:INC:A1000:00 Dt. 28.09.10 1 **This procedure shall be used

  

INSTALLATION & COMMISSIONING GUDELINE FOR A1000 AC DRIVE

ESP:IA:INC:A1000:00… Dt. 28.09.10    7  

Removing the front cover from models CIMR-AD4A0058 to 4A0675:

1. Remove the terminal cover and the digital operator. 2. Loosen the installation screw on the front cover. 3. Use a straight-edge screwdriver to loosen the hooks on each side of the cover that hold it in place.

4. First unhook the left side of the front cover, then swing the left side towards you as shown in the

figure below till the cover comes out. Reverse the instructions from 4 >> 1 to reattach the cover:

Page 8: INSTALLATION & COMMISSIONING GUDELINE FOR A1000 · PDF fileINSTALLATION & COMMISSIONING GUDELINE FOR A1000 AC DRIVE ESP:IA:INC:A1000:00 Dt. 28.09.10 1 **This procedure shall be used

  

INSTALLATION & COMMISSIONING GUDELINE FOR A1000 AC DRIVE

ESP:IA:INC:A1000:00… Dt. 28.09.10    8  

Removing top protective cover:

Insert the tip of a straight-edge screwdriver into the small openings located on the front edge of the top protective cover. Gently apply pressure as shown in the figure below to free the cover from the drive. Note: Removing the top protective cover from a IP20/NEMA Type 1 enclosure drive voids the NEMA Type 1 protection but still keeps IP20 conformity.

Reattaching the protective cover:

Align the small protruding hooks on the sides of the top protective cover with the corresponding mounting holes on the top of the drive. Pinch the hooks inward so that the they connect with the mounting holes and fasten the top protective cover back into place:

Ground Wiring for multiple inverters connected:

Page 9: INSTALLATION & COMMISSIONING GUDELINE FOR A1000 · PDF fileINSTALLATION & COMMISSIONING GUDELINE FOR A1000 AC DRIVE ESP:IA:INC:A1000:00 Dt. 28.09.10 1 **This procedure shall be used

 

ESP:I 

Using

1

2

3

4

5

6

7

8

9

10

11

12

13

14

A:INC:A1000

g Digital Ope

INSTALL

:00… Dt. 28.0

erator:

ESC

RESE

RUN

Up Arr

Down A

STOP

ENTE

LO/RE SK

RUN

LO/RE

ALM LE

FOUT L

DRV LE

REV LE

LATION & C

09.10 

C Key

•••d

ET Key ••

N Key

S•••faw

row Key Sin

rrow Key Sin

P Key Sin

ER Key ••

Selection Key

Ste(ob

Light LFm

E Light L

ED Light LFO

ED Light L

ED Light LO

ED Light L

COMMISSION

Returns to th Moves the cu Pressing andisplay. Moves the cu Resets the d

Starts the drive is on, when t flashes durin flashes quick

ast stop DI or was active duriScrolls up to dincrements setScrolls down toncrements setStops drive open any mode. T Enters param Selects a me

Switches drive erminals (REMoperation frometween LOCAit while the drast blinking: r

mode.

it while the op

it : drive has dlashing : Alarm

Off : Normal stit: When displit: Drive is in o

Off: Drive is in it: reverse mo

NING GUDE

he previous disursor one spacd holding this

ursor to the rigrive to clear a

e in the LOCALthe drive is opng deceleratiokly the drive isa run commaing power up. isplay the nexttting values. o display the ntting values. eration. (Note

To disable the meter values aenu item to m control betwe

MOTE). The LEm keypad). ToAL and REMOTrive is operatinrun command

perator is sele

detected an alm / oPE error ate / no alrm lay shows outpoperation modprogramming

otor direction;

ELINE FOR A

splay. ce to the left. button will ret

ght. a fault situatioL mode. The Rerating the m

on to stop or ws disabled by and t item, selects

next item, sele

: This key has STOP key prioand settings. ove between

een the operatD is on when t

o disable the LTE, set parameng the motor. issued throug

ected to run th

larm/error / auto-tuning put drequencyde / during aug mode, drive w Off: forward d

A1000 AC D

turn to the Fre

on. Run LED

motor. when the frequa DI, the drive

s parameter n

ects paramete

highest prioriority, set param

displays. tor (LOCAL) anthe drive is in

LO/RE key to peter o2-01 to 0 Slow blinkinggh terminals b

he drive (LOCA

g errors

y utotuning will not accep

direction

DRIVE

equency Refer

uency reference was stopped

numbers and

er numbers an

ity, will stop ometer o2-06 t

nd the control the LOCAL mprohibit switch0 g: motor decelbut drive is in

AL mode).

pt RUN comma

rence

ce is 0. using a

nd

peration to 0

l circuit ode hing

erating; local

and

Page 10: INSTALLATION & COMMISSIONING GUDELINE FOR A1000 · PDF fileINSTALLATION & COMMISSIONING GUDELINE FOR A1000 AC DRIVE ESP:IA:INC:A1000:00 Dt. 28.09.10 1 **This procedure shall be used

  

INSTALLATION & COMMISSIONING GUDELINE FOR A1000 AC DRIVE

ESP:IA:INC:A1000:00… Dt. 28.09.10    10  

Page 11: INSTALLATION & COMMISSIONING GUDELINE FOR A1000 · PDF fileINSTALLATION & COMMISSIONING GUDELINE FOR A1000 AC DRIVE ESP:IA:INC:A1000:00 Dt. 28.09.10 1 **This procedure shall be used

  

INSTALLATION & COMMISSIONING GUDELINE FOR A1000 AC DRIVE

ESP:IA:INC:A1000:00… Dt. 28.09.10    11  

Startup flow charts:

Flowchart A : Basic Startup & motor tuning

Page 12: INSTALLATION & COMMISSIONING GUDELINE FOR A1000 · PDF fileINSTALLATION & COMMISSIONING GUDELINE FOR A1000 AC DRIVE ESP:IA:INC:A1000:00 Dt. 28.09.10 1 **This procedure shall be used

  

INSTALLATION & COMMISSIONING GUDELINE FOR A1000 AC DRIVE

ESP:IA:INC:A1000:00… Dt. 28.09.10    12  

Subchart A-1: Simple motor setup using V/F control

Subchart A2: High performance operation using Open Loop Vector (OLV) or Closed loop Vector (CLV)

Page 13: INSTALLATION & COMMISSIONING GUDELINE FOR A1000 · PDF fileINSTALLATION & COMMISSIONING GUDELINE FOR A1000 AC DRIVE ESP:IA:INC:A1000:00 Dt. 28.09.10 1 **This procedure shall be used

  

INSTALLATION & COMMISSIONING GUDELINE FOR A1000 AC DRIVE

ESP:IA:INC:A1000:00… Dt. 28.09.10    13  

<1> The load must be decoupled from the motor to properly perform Rotational Auto-Tuning. <2> Rotational Auto-Tuning can still be performed if the load is 30% or less, though Stationary Auto-Tuning will probably yield better control performance. <3> Make sure the motor and load can run freely, i.e., if a brake is mounted, make sure it is released. <4> ASR Gain Tuning automatically performs Inertia Tuning and sets parameters related to Feed Forward and the KEB Ride-Thru function.

Subchart A3: Operation with permanent magnet motors

Page 14: INSTALLATION & COMMISSIONING GUDELINE FOR A1000 · PDF fileINSTALLATION & COMMISSIONING GUDELINE FOR A1000 AC DRIVE ESP:IA:INC:A1000:00 Dt. 28.09.10 1 **This procedure shall be used

  

INSTALLATION & COMMISSIONING GUDELINE FOR A1000 AC DRIVE

ESP:IA:INC:A1000:00… Dt. 28.09.10    14  

<1> Enter the motor code to E5-01 when using a Yaskawa PM motor (SMRA Series, SSR1 Series, and SST4 Series). If using a motor from another manufacturer, enter FFFF. <2> Make sure the motor and load can run freely, i.e., if a brake is mounted, make sure it is released. <3> ASR Gain Tuning automatically performs Inertia Tuning and sets parameters related to Feed Forward and the KEB Ride-Thru function. Note: The Z pulse must be realigned if the PG encoder is replaced. Set T2-01 to 3 to recalibrate the drive for the new encoder.

 


Recommended