3DJH �
£
352'8&7 /,7(5$785(
¤���� /HQQR[ ,QGXVWULHV ,QF�
'DOODV� 7H[DV
,167$//$7,21
,16758&7,216
*�� 6(5,(6 81,76GAS UNITS
503,543M9/96Supersedes 503,222M
7$%/( 2) &217(176
UNIT DIMENSIONS 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .PARTS ARRANGEMENT 3. . . . . . . . . . . . . . . . . . . . . . . . . . .REQUIREMENTS 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .GENERAL 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .COMBUSTION, DILUTION AND VENTILATION AIR 5. . .INSTALLATION--Setting Equipment 7. . . . . . . . . . . . . . . . .RETURN AIR OPENING GUIDELINES 7. . . . . . . . . . . . . . . .FILTER ASSEMBLY AND FILTERS 8. . . . . . . . . . . . . . . . . . .DUCT SYSTEM 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .VENTING 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .GAS PIPING 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .ELECTRICAL 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .UNIT START--UP 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .HIGH ALTITUDE INFORMATION 19. . . . . . . . . . . . . . . . . . .GAS PRESSURE ADJUSTMENT 19. . . . . . . . . . . . . . . . . . .OTHER UNIT ADJUSTMENTS 20. . . . . . . . . . . . . . . . . . . . .SERVICE 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .REPAIR PARTS 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .START--UP AND PERFORMANCE CHECK LIST 23. . . . . .BCC2 TROUBLESHOOTING 24. . . . . . . . . . . . . . . . . . . . . . .
5(7$,1 7+(6( ,16758&7,216)25 )8785( 5()(5(1&(
:+$7 72 '2 ,) <28 60(// *$6�
,I WKH LQIRUPDWLRQ LQ WKLV PDQXDO LV QRWIROORZHG H[DFWO\� D ILUH RU H[SORVLRQPD\ UHVXOW FDXVLQJ SURSHUW\ GDPDJH�SHUVRQDO LQMXU\ RU ORVV RI OLIH�
:$51,1*
'R QRW VWRUH RU XVH JDVROLQH RU RWKHUIODPPDEOH YDSRUV DQG OLTXLGV LQ WKHYLFLQLW\ RI WKLV RU DQ\ RWKHU DSSOLDQFH�
,QVWDOODWLRQ DQG VHUYLFH PXVW EHSHUIRUPHG E\ D TXDOLILHG LQVWDOOHU�VHUYLFH DJHQF\ RU WKH JDV VXSSOLHU�
- 'R QRW WU\ WR OLJKW DQ\ DSSOLDQFH�
- 'R QRW WRXFK DQ\ HOHFWULFDO VZLWFK� GR QRWXVH DQ\ SKRQH LQ \RXU EXLOGLQJ�
- ,PPHGLDWHO\ FDOO \RXU JDV VXSSOLHU IURP DQHLJKERU·V SKRQH� )ROORZ WKH JDV VXSSOLHU·VLQVWUXFWLRQV�
- ,I \RX FDQQRW UHDFK \RXU JDV VXSSOLHU� FDOOWKH ILUH GHSDUWPHQW�
- ([WLQJXLVK DQ\ RSHQ IODPHV�
/LWKR 8�6�$�
3DJH �
G20 UNIT DIMENSIONS--INCHES (MM)
AIR FLOW
SUPPLYAIR
OPENING
FLUE OUTLET(center side to side)
22 (559)
2-1/4(57)
1-11/16(43)
2-5/8 (67)(Right)
28-3/8(721)
1-1/16(27)
1-1/16(27)
B
C
E
H
FReturn Air
Return Air
WHISPER HEAT
GAS PIPINGINLET
(Both Sides)
17-3/4(451)
ELECTRICALINLETS
(Both Sides)
RETURN AIROPENING(Either Sideor Bottom)
26-1/8(664)
A
D
22 (559) 2-1/16(52)
1-1/2 (38)
17-1/2 (445)(Left)
20-1/2 (521)(Right)
G
*OPTIONALBOTTOM RETURN AIR FILTER KIT REQUIRED
RETURN AIRFILTER
(Either Sideor *Bottom)
2-3/8 (60)(Left)
Model No. A B C D E F G H
G20Q2E(X)-50
G20Q3E(X)-50
G20Q2E(X)-75
G20Q3E(X)-75
49
(1245)
16-1/4
(413)
14-1/8
(359)
14
(356)
11
(279)
2-5/8
(67)
8-1/8
(206)
3-1/8
(79)
G20Q4E(X)-75
G20Q3/4E(X)-100
49
(1245)
21-1/4
(540)
19-1/8
(486)
14
(356)
14
(356)
3-5/8
(92)
10-5/8
(270)
3-1/8
(79)
G20Q5/6E(X)-100
G20Q3/4E(X)-125
G20Q5/6E(X)-125
53
(1346)
26-1/4
(667)
24-1/8
(613)
18
(457)
21
(533)
2-5/8
(67)
13-1/8
(333)
3-3/8
(86)
G20Q5/6E(X)-15053
(1346)
31-1/4
(794)
29-1/8
(740)
18
(457)
26
(660)
2-5/8
(67)
15-5/8
(397)
3-3/8
(86)
3DJH �
G20 PARTS ARRANGEMENT
FIGURE 1
PARTS IDENTIFICATION
(G20 Units Shown)
HEATEXCHANGER
DRAFTHOOD
UPPER ACCESSPANEL
BURNERS
BURNERBOX
IGNITIONCONTROL
BLOWER
GASMANIFOLD
BURNER BOXDAMPER ASSEMBLY
REAR BAFFLE
TOP STRIP
LIMITCONTROL
CABINET
CONTROL BOX
ROLL--OUTSWITCH
BLOCKED VENTSHUT--OFFSWITCH
CABINET CAP
GAS VALVE
PILOT/ELECTRODEASSEMBLY
REMOVABLEBURNERBOX TOP
DAMPERMOTOR/GEAR
PATCH PLATE
PATCHPLATE
SPRING
DAMPERSWITCH
DAMPER SWITCHCOVER
ROLL--OUTSWITCH
DAMPER
BURNERBOX
DAMPER BOX PARTS ARRANGEMENT
FIGURE 2
REMOVABLEBURNER BOX TOP
3DJH �
5(48,5(0(176
All G20 units are A.G.A. (American Gas Association) and
C.G.A (Canadian Gas Association) certified.
In the US, installation of Lennox gas central furnaces
must conform with local building codes or, in the ab-
senceof local codes,with the currentNational FuelGas
Code (ANSI--Z223.1). The National Fuel Gas Code is
available from:
American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
NOTE--G20X series units (units equipped with flame
rods) are certified for use with natural gas only.
Air supply for combustion and ventilation must con-
form to the methods outlined in the current National
Fuel Gas Code.
WARNING
Product contains fiberglass wool.
Disturbing the insulation in this product duringinstallation, maintenance, or repair will exposeyou to fiberglass wool. Breathing this may causelung cancer. (Fiberglass wool is known to theState of California to cause cancer.)
Fiberglass wool may also cause respiratory, skin,and eye irritation.
To reduce exposure to this substanceor for furtherinformation, consult material safety data sheetsavailable from address shown below, or contactyour supervisor.
Lennox Industries Inc.P.O. Box 799900Dallas, TX 75379--9900
The furnace is certified for installation clearances to com-
bustible material as listed on the appliance rating plate
and in table 1 for installations in an alcove or closet.
Clearances Location Inches (mm)
Service access
To combustiblematerials
From Draft HoodRelief Opening
Front
Top, side and rear
Flue
Front
36 (914)*
1 (25)
6 (152)**
6 (152)
NOTE--Service access clearance must be maintained.
TABLE 1
* If tight installation, front service clearance may be 24� (610mm).**1� (25mm) for type �B1� Vent Pipe.
Floor 0 (0)
Accessibility and service clearances must take prece-
dence over fire protection clearances.
Vent installations shall be in accordance with the
GAMA venting tables booklet supplied with this unit
and applicable provisions of local building codes .
NOTE--For installation on combustible floors, appliance
shall not be installed directly on carpeting, tile, or other
combustible material other than wood flooring.
For installation in a residential garage, unit must be
installed so that burner(s) and ignition source are lo-
cated no less than 18� (457 mm) above floor. Furnace
must be located or protected to avoid physical damage
by vehicles.
Unit must be adjusted to obtain a temperature rise
within the range specified on appliance rating plate.
Thedraft hoodshall be installed in the sameatmospheric
pressure zone as the combustion air inlet to the furnace.
G20 units must be installed so that electrical compo-
nents are protected from water.
When furnace is used in conjunction with cooling
units, it shall be installed in parallel with, or on the up-
stream side of, cooling units to avoid condensation in
the heating element.With a parallel flow arrangement,
damper (or othermeans to control the flow of air) shall
be adequate to prevent chilled air from entering the
furnace and, if manually operated, must be equipped
with means to prevent operation of either unit, unless
damper is in the full �heat� or �cool� position.
When installed, furnace must be electrically grounded
in accordance with local codes or, in the absence of lo-
cal codes, with the current National Electric Code,
ANSI/NFPA No. 70. The National Electric Code (ANSI/
NFPA No. 70) is available from:
National Fire Protection Association
470 Atlantic Avenue
Boston, MA 02210
Field wiring connection with unit must meet or exceed
specifications of type T wire and withstand a 63EF
(17EC) temperature rise. When furnace is installed so
that supply ducts carry air circulated by furnace to
areas outside space containing furnace, return air shall
be handled by a duct(s) sealed to the furnace casing
and terminating outside space containing furnace.
This furnace is certified for installation clearances to
combustible material as listed on appliance rating plate
and in table 1. Accessibility and service clearances must
take precedence over fire protection clearances.
In Canada, installation of C.G.A. certified units must
conform with current Standard CAN/CGA--B149.1
�Installation Code for Natural Gas Burning Appliances
and Equipment� and CAN/CGA--B149.2 �Installation
Code for Propane Gas Burning Appliances and Equip-
ment,� local plumbing or waste water codes and other
applicable local codes. Authorities having jurisdiction
shouldbe consultedbefore installation.Adequate clear-
3DJH �
ance shall be made around air openings into the vesti-
bule area. Provisions shall be made for proper opera-
tion and for combustion air and ventilation air supply
according to the current CAN/CGA--B149 standards.
All electrical wiring and grounding for the unitmust be
in accordancewith the current regulations of the Cana-
dian Electrical Code Part I (C.S.A. Standard C22.1) and/
or local codes.
NOTE--G20 series units must not be used as a
�construction heater� at any timeduring any phase of
construction. Very low return air temperature, harm-
ful vapors andmisplacementof the filterswill damage
the unit and its efficiency.
GENERAL
These instructions are intended as a general guide
and do not supersede local codes in anyway. Authori-
ties having jurisdiction should be consulted before
installation.
A--Shipping and Packing List
1--Leveling bolt package (if ordered)
1--Thermostat (if ordered)
1--Rubber grommet (for electrical make--up)
B--Shipping Damage
Check unit for shipping damage. Receiving party
should contact last carrier immediately if any shipping
damage is found.
WARNING
Improper installation, adjustment, alteration, ser-vice or maintenance can cause property damage,personal injury or loss of life. Installation and ser-vice must be performed by a qualified installer,service agency or the gas supplier.
COMBUSTION, DILUTION & VENTILATION AIR
Until recently, therewas no problem in bringing in suf-
ficient amounts of outdoor air for combustion ---- in-
filtration provided all the air that was needed and then
some. In today�s homes built with energy conservation
inmind, tight construction practices make it necessary
to bring in air from outside for combustion. Consider-
ationmust also be given to the use of exhaust fans, ap-
pliance vents, chimneys and fireplaces because they
force additional air that could be used for combustion
out of the house. Unless outside air is brought into the
home for combustion, negative pressure (pressure
outside is greater than inside pressure)will build to the
point that a down draft can occur in the furnace vent
pipe or chimney. Combustion gases enter the living
space creating a potentially dangerous situation.
In the absence of local codes concerning air for com-
bustion and ventilation, this section outlines guide-
lines and recommends procedures for installing G20
furnaces in amanner that ensures efficient and safeop-
eration. Special consideration must be given to com-
bustion air needs as well as requirements for exhaust
vents and gas piping. A portion of this information has
been reprintedwith permission from the National Fuel
Gas Code (ANSI--Z223.1). This reprintedmaterial is not
the complete and official position of the ANSI on the
referenced subject, which is represented only by the
standard in its entirety.
In Canada, refer to the standard CAN/CGA--B149.1 and
--B149.2 installation codes.
Combustion Air Requirements
&$87,21
,QVXIILFLHQW FRPEXVWLRQ DLU FDQ FDXVH KHDGDFKHV�QDXVHD� GL]]LQHVV RU DVSK\[LDWLRQ� ([FHVVLYH H[�SRVXUH WR FRQWDPLQDWHG FRPEXVWLRQ DLU ZLOO UHVXOWLQ VDIHW\ DQG SHUIRUPDQFH UHODWHG SUREOHPV�$YRLGH[SRVXUH WR WKH IROORZLQJ VXEVWDQFHV LQ WKH FRP�EXVWLRQ DLU VXSSO\�3HUPDQHQW ZDYH VROXWLRQV�&KORULQDWHG ZD[HV DQG FOHDQHUV�&KORULQH EDVH VZLPPLQJ SRRO FKHPLFDOV�:DWHU VRIWHQLQJ FKHPLFDOV�'H� �LFLQJ VDOWV RU FKHPLFDOV�&DUERQ WHWUDFKORULGH�+DORJHQ W\SH UHIULJHUDQWV�&OHDQLQJ VROYHQWV �VXFK DV SHUFKORURHWK\OHQH��3ULQWLQJ LQNV� SDLQW UHPRYHUV� YDUQLVKHV� HWF��+\GURFKORULF DFLG�&HPHQWV DQG JOXHV�$QWLVWDWLF IDEULF VRIWHQHUV IRU FORWKHV GU\HUV� DQG0DVRQU\ DFLG ZDVKLQJ PDWHULDOV�
All gas--fired appliances require air to be used for the
combustion process. If sufficient amounts of combus-
tion air are not available, the furnace or other appliance
will operate in an inefficient and unsafe manner.
Enough air must be provided to meet the needs of all
fuel--burning appliances, as well as appliances such as
exhaust fanswhich force air out of thehome.When fire-
places, exhaust fans, or clothes dryers are used at the
same time as the furnace, much more air is required to
ensure proper combustion and to prevent a down--draft
situation. Insufficient amounts of air also cause incom-
plete combustionwhich can result in carbonmonoxide.
The requirements for providing air for combustion and
ventilation depend largely on whether the furnace is
installed in an unconfined or confined space.
3DJH �
Unconfined Space
An unconfined space is an area such as a basement or
large equipment room with a volume greater than 50
cubic feet per 1,000 Btu (1.42m3 per .29kW) per hour of
the combined input rating of all appliances installed in
that space. This space also includes adjacent rooms
whicharenot separatedbyadoor. Thoughanareamay
appear to beunconfined, itmight benecessary tobring
in outdoor air for combustion if the structure does not
provide enough air by infiltration. If the furnace is lo-
cated in a building of tight construction with weather
stripping and caulking around thewindows anddoors,
follow the procedures outlined for using air from the
outside for combustion and ventilation.
Confined Space
A confined space is an area with volume less than 50 cu-
bic feet per 1,000 Btu (1.42m3per .29kW) per hour of the
combined input rating of all appliances installed in that
space. This definition includes furnace closets or small
equipment rooms.
When the furnace is installed so that supply ducts carry
air circulated by the furnace to areas outside the space
containing the furnace, the return air must be handled
by ducts which are sealed to the furnace casing and
which terminate outside the space containing the fur-
nace. This is especially important when the furnace is
mounted on a platform in a confined space such as a
closet or small equipment room. Even a small leak
around the base of the unit at the platform or at the re-
turn air duct connection can cause a potentially dan-
gerous negative pressure condition. Air for combus-
tion and ventilation can be brought into the confined
space either from inside the building or from outside.
Air from Inside
If the confined space housing the furnace adjoins space
categorized as unconfined, air can be brought in by pro-
viding two permanent openings between the two
spaces. Each opening must have a minimum free area
of 1 square inch per 1,000 Btu (645mm2 per .29kW) per
hour of the total input rating of all gas--fired equipment
in the confined space. Eachopeningmustbeat least 100
square inches (645cm2). One opening shall be within
12� (305mm) of the top of the enclosure and one open-
ing within 12� (305mm) of the bottom (See figure 3).
Air from Outside
If air from outside is brought in for combustion and
ventilation, the confined space shall be provided with
two permanent openings. One opening shall bewithin
12� (305mm)of the top of the enclosure andonewithin
12� (305mm) of the bottom. These openings must
communicate directly or by ducts with the outdoors or
spaces (crawl or attic) that freelycommunicatewith the
outdoors or indirectly through vertical ducts. Each
opening shall have a minimum free area of 1 square
inch per 4,000 Btu (645mm2 per 1.17kW) per hour of to-
tal input rating of all equipment in the enclosure (See
figures 4 and 5). When communicating with the out-
doors through horizontal ducts, each opening shall
have a minimum free area of 1 square inch per 2,000
Btu (645mm2 per .59kW) per total input rating of all
equipment in the enclosure (See figure 6).
(48,30(17 ,1 &21),1(' 63$&(
$// $,5 )520 ,16,'(
&+,01(<25 *$69(17
:$7(5+($7(5
23(1,1*6�7R $GMDFHQW
5RRP�
),*85( �
127(� �(DFK RSHQLQJ VKDOO KDYH D IUHH DUHD RI DW OHDVW � VTXDUH LQFKSHU �����%WX ����PP� SHU ���N:� SHU KRXURI WKH WRWDO LQSXW UDWLQJ RIDOO HTXLSPHQW LQ WKH HQFORVXUH� EXW QRW OHVV WKDQ ��� VTXDUH LQFKHV�
*��)851$&(
(48,30(17 ,1 &21),1(' 63$&($// $,5 )520 2876,'(
�,QOHW $LU IURP &UDZO 6SDFH DQG2XWOHW $LU WR 9HQWLODWHG $WWLF�
127(� �7KH LQOHW DQG RXWOHW DLU RSHQLQJV VKDOO HDFK KDYH D IUHH DUHD RIDW OHDVW � VTXDUH LQFK SHU ����� %WX ����PP�SHU ����N:� SHU KRXU RIWKH WRWDO LQSXW UDWLQJ RI DOO HTXLSPHQW LQ WKH HQFORVXUH�
9(17,/$7,21 /289(56�(DFK HQG RI DWWLF�
287/(7$,5 :$7(5
+($7(5
,1/(7$,5
&+,01(<25 *$69(17
9(17,/$7,21/289(56
�)RU XQKHDWHG FUDZOVSDFH�
),*85( �
*��)851$&(
3DJH �
(48,30(17 ,1 &21),1(' 63$&($// $,5 )520 2876,'(
�$OO $LU 7KURXJK 9HQWLODWHG $WWLF�
127(� �7KH LQOHW DQG RXWOHW DLU RSHQLQJV VKDOO HDFK KDYH D IUHH DUHD RIDW OHDVW RQH VTXDUH LQFK SHU ����� %WX ����PP�SHU ����N:� SHU KRXURI WKH WRWDO LQSXW UDWLQJ RI DOO HTXLSPHQW LQ WKH HQFORVXUH�
&+,01(<25 *$69(17
:$7(5+($7(5
287/(7$,5
9(17,/$7,21 /289(56�(DFK HQG RI DWWLF�
,1/(7 $,5�(QGV ��l DERYH
ERWWRP�
),*85( �
*��)851$&(
(48,30(17 ,1 &21),1(' 63$&($// $,5 )520 2876,'(
287/(7 $,5
,1/(7 $,5
:$7(5+($7(5
&+,01(<25 *$69(17
),*85( �
127(� �(DFK DLU GXFW RSHQLQJ VKDOO KDYH D IUHH DUHD RI DW OHDVW RQHVTXDUH LQFK SHU ����� %WX ����PP�SHU ���N:� SHU KRXU RI WKH WRWDOLQSXW UDWLQJ RI DOO HTXLSPHQW LQ WKHHQFORVXUH� ,I WKHHTXLSPHQW URRP LVORFDWHG DJDLQVW DQ RXWVLGHZDOO DQG WKH DLU RSHQLQJV FRPPXQLFDWH GL�UHFWO\ZLWK WKHRXWGRRUV� HDFKRSHQLQJ VKDOO KDYHD IUHHDUHD RI DW OHDVW� VTXDUH LQFKSHU �����%WX ����PP�SHU ����N:�SHU KRXU RI WKH WRWDOLQSXW UDWLQJ RI DOO RWKHU HTXLSPHQW LQ WKH HQFORVXUH�
*��)851$&(
When ducts are used, they shall be of the same cross--
sectional area as the free area of the openings towhich
they connect. The minimum dimension of rectangular
air ducts shall be no less than 3� (76mm). In calculating
free area, the blocking effect of louvers, grilles, or
screensmust be considered. If the design and free area
of protective covering is not known for calculating the
size opening required, it may be assumed that wood
louvers will have 20 to 25 percent free area and metal
louvers and grilles will have 60 to 75 percent free area.
Louvers and grilles must be fixed in the open position
or interlocked with the equipment so that they are
opened automatically during equipment operation.
,167$//$7,21��6HWWLQJ (TXLSPHQW
1-- Holes are provided in the corners of unit base for
leveling unit. Install leveling bolts (if desired) or
shim under unit. See figure 7.
127(� �,I OHYHOLQJ EROWV DUH XVHG� EH VXUH WR LQVWDOO WKH
SODVWLF QXWV DQG WLJKWHQ VQXJO\ EHIRUH VHWWLQJ WKH XQLW�
&$%,1(76,'(
$)7(5 81,7 ,6 /(9(/�7,*+7(1 7+,6 187
81,7%$6(
/(9(/ 81,7:,7+ 7+,6 187
,167$// 3/$67,&1876 :,7+ )/$7
6,'( 72:$5' %$6(�/(9(/,1*%2/7
/(9(/,1* %2/7 ,167$//$7,21
),*85( �
2-- Set unit in desired location allowing for clearances
listed on appliance rating plate. Also allow for gas
supply connection, electrical supply, vent connec-
tions and installation and service clearances.
5(7851 $,5 23(1,1* *8,'(/,1(6
:$51,1*
,PSURSHU LQVWDOODWLRQ RI XQLW FDQ UHVXOW LQ SHUVRQDOLQMXU\ RU GHDWK� &RPEXVWLRQ DQG IOXH SURGXFWVPXVWQHYHU EH DOORZHG WR HQWHU WKH UHWXUQ DLU V\VWHPRU DLULQ WKH OLYLQJVSDFH�8VHVKHHWPHWDO VFUHZVDQG MRLQWWDSH WR VHDO UHWXUQ DLU V\VWHP WR IXUQDFH�,Q SODWIRUP LQVWDOODWLRQV ZLWK IXUQDFH UHWXUQ� WKHIXUQDFH VKRXOG EH VHDOHG DLUWLJKW WR WKH UHWXUQ DLUSOHQXP� $ GRRU PXVW QHYHU EH XVHG DV D SRUWLRQ RIWKH UHWXUQ DLU GXFW V\VWHP� 7KH EDVH PXVW SURYLGHD VWDEOH VXSSRUW DQG DQ DLUWLJKW VHDO WR WKH IXUQDFH�$OORZ DEVROXWHO\ QR VDJJLQJ� FUDFNV� JDSV� HWF�)RU QR UHDVRQ VKRXOG UHWXUQ DQG VXSSO\ DLU GXFWV\VWHPV HYHU EH FRQQHFWHG WR RU IURP RWKHU KHDW�LQJ GHYLFHV VXFK DV D ILUHSODFH RU VWRYH� HWF� )LUH�H[SORVLRQ� FDUERQ PRQR[LGH SRLVRQLQJ� SHUVRQDOLQMXU\ DQG�RU SURSHUW\ GDPDJH FRXOG UHVXOW�
:$51,1*
%ORZHU GRRUPXVW EH VHFXUHO\ LQ SODFH ZKHQ EORZ�HU DQG EXUQHUV DUH RSHUDWLQJ� *DV IXPHV� ZKLFKFRXOG FRQWDLQ FDUERQPRQR[LGH� FDQ EH GUDZQ LQWROLYLQJ VSDFH UHVXOWLQJ LQ SHUVRQDO LQMXU\ RU GHDWK�
If cold air return is to terminate through the floor under
the furnace, a direct, airtight and sealed connection
must be made to the bottom of the furnace. For instal-
lations where the return air is taken from a return air
drop, unit may be installed using either the left or right
side of furnace.
For side return air applications, cut furnace cabinet at
sized knockout squares for maximum return air.
Return air canbebrought in either sideor at thebottom
of the unit. Scribe lines show the outline of each side
return air opening.
3DJH �
),/7(5 $66(0%/< $1' ),/7(56
G20 series units are equipped with a reusable foam filter.
The filtermustbe inplaceanytime theunit is inoperation.
A bottom return air kit is available for bottom return air
opening applications.
For side return air openings, use supplied filter racks to
hold filter. To install lower filter rack, remove two
screws from lower side of cabinet. Place flange of filter
rack inside bottom panel and side panel. Secure with
previously removed cabinet/base bottom screws. To
install upper filter rack, loosen screws fromside of cab-
inet at blower deck level. Insert three tabs in slots that
are on the inside of the cabinet. Tabs must be between
side panel and blower deck flange. Retighten screws to
secure. See figure 8.
),*85( �
),/7(5 5$&. )25 *���8VHG RQ VLGH UHWXUQ RQO\�
%27720
%$6(
/2:(5
),/7(5
5$&.
%/2:(5 '(&.
6,'( 3$1(/
),/7(5
3/$&( 833(5
),/7(5 5$&.
7$%
,172 6/27
/2:(5
),/7(5 5$&.
833(5
),/7(5 5$&. 7$%6
'8&7 6<67(0
Size and install supply and return air duct system us-
ing industry--approved standards that result in a quiet
and low--static system with uniform air distribution.
Supply Air Duct System
Installation of units not equippedwith a cooling coil re-
quire a removable access panel in the supply air duct.
The access panel should be large enough to permit in-
spection of heat exchanger for leaks after installation.
Lennox recommends using the SENSITTM HT kit for
heatexchanger inspections. Theaccess panelmust not
allow leaks in the supply air duct system.
Return Air Duct System
NOTE--All G20 series units with bottom return air require
a bottom return kit which is available as an accessory.
NOTE--Return air duct should be secured to the unit us-
ing rivets or S--locks. Using screws to secure the return
air duct to theunitwill interferewith the filter andcause
improper filtration.
9(17,1*
G20 series furnacesmust be vented in compliancewith
all local codes, the venting tables provided in this
manual for applications in the U.S.A., the current stan-
dards of CAN/CGA--B149.1 and --B149.2 in Canada, and
these instructions.
G20 series units havebeen classified as Category I type
furnaceswhen vertically vented in accordancewith the
latest edition of ANSI Z21.47 Central Furnace Standard
in the U.S.A. and the current standard of CAN/CGA--
B149.1 and B149.2 of the National Gas and Propane
Installation Code in Canada.
The vent sizing tables in this manual have been ex-
tracted from the National Fuel Gas Code (NFPA 54 /
ANSI Z223.1) and are provided for convenience to
serve as aguideline for proper vent installation. Proper
application, termination, construction and location of
vents must conform to local codes having jurisdiction.
In the absence of local codes, the NFGC serves as the
defining document.
Refer to the tables and the venting information con-
tained in these instructions for proper sizing and instal-
lation of the venting system.
Use this information in conjunction with the provided
venting tables in the U.S.A., and the appropriate vent-
ing tables in the standards of CAN/CGA--B149.1 and
B149.2 of the National Gas and Propane Installation
Code in Canada, to properly size the vent or vent con-
nector that attaches to the furnace flue collar.
Roundvent connectors shouldbeused in the following
sizes: --50 and --75 units, 4� (102mm); --100 units, 5�
(127mm); and --125 and --150 units, 6� (152mm). A 9�
(229mm) minimum length vertical vent connector
must be run from the furnace flue outlet to the first el-
bow. See figure 9.
Venting Using a Masonry Chimney
The following additional requirements apply when a
lined masonry chimney is being used to vent an G20
furnace:
A Category I appliance must never be connected to a
chimney that is servicing a solid fuel appliance. If a fire-
place chimney flue is used to vent this appliance, the
fireplace opening must be permanently sealed. See
figure 9.
Any masonry chimney used for venting a G20 series
gas furnace must be lined, and must be sized and
installed per all applicable local building codes or, in
the absence of local codes, the current National Fuel
Gas Code (ANSI--Z223.1) in the U.S.A. and the current
standards of CAN/CGA--B149.1 and --B149.2 in Canada.
Venting in an unlined masonry chimney is prohibited.
The effective area of the chimney serving a single ap-
pliance must be no less than the effective area of the
draft hood outlet. The chimney must extend vertically
at least 5 ft. (1.5m) above the flue collar.
3DJH �
�l����PP�0,1�
*��)851$&(
3(50$1(17/<6($/(' ),5(3/$&(
23(1,1*
+/
9(57,&$/ 9(17 86,1*
/,1(' 0$6215< &+,01(<
),*85( �
A chimney with one or more sides exposed to the out-
side of the structure is considered to be an exterior
chimney. A Type B or listed chimney lining system
passing through an unused masonry chimney flue is
not considered to be exposed to the outdoors.
Masonry chimneys used to vent Category I central fur-
naces must be either tile--lined or lined with a listed
metal lining systemordedicatedgas vent.Unlinedma-
sonry chimneys are prohibited.
A Type �B� vent or masonry chimney liner shall termi-
nate above the roof surface with a listed cap or a listed
roof assembly in accordancewith the terms of their re-
spective listings and the vent manufacturer�s instruc-
tions.
Do not install amanual damper, barometric draft regu-
lator, or flue restrictor between the furnace and the
chimney.
If type �B� double--wall vent is used inside a chimney,
no other appliance can be vented into the chimney.
Outer wall of type �B� vent pipe must not be exposed
to flue products.
Insulation for the flexible vent pipe must be an encap-
sulated fiberglass sleeve recommended by the flexible
vent pipe manufacturer.
The space between liner and chimney wall should
NOT be insulated with puffed mica or any other loose
granular insulating material.
If �B� vent or an insulated flexible vent pipe cannot be
used as liners, the chimney must be rebuilt to accom-
modate one of these methods or some alternate ap-
proved method must be found to vent the appliance.
When inspection reveals that an existing chimney is
not safe for the intended purpose, it shall be rebuilt to
conform to nationally recognized standards, lined or
relined with suitable materials or replaced with a gas
vent or chimney suitable for venting G20 series units.
The chimney passagewaymust be checked periodical-
ly to ensure that it is clear and free of obstructions.
General Venting Requirements
All G20 furnaces must be vented in accordance with
the methods outlined in these instructions.
1-- Vent diameter recommendations and maximum
runs allowed are found in the provided venting
tables in the U.S.A., and the appropriate venting
tables in the standards of CAN/CGA--B149.1 and
B149.2 of the National Gas and Propane Installa-
tion Code in Canada.
2-- In no case should the vent or vent connector diam-
eter be less than the diameter specified in the pro-
vided venting tables in the U.S.A., and the ap-
propriate venting tables in the standards of
CAN/CGA--B149.1 and B149.2 of the National Gas
and Propane Installation Code in Canada.
3-- For single appliance vents: If the vertical vent or
tile--lined chimney has a larger diameter or flow
area than the vent connector, use the vertical vent
diameter to determine theminimumvent capacity
and the vent connector diameter to determine the
maximumvent capacity. The flowareaof theverti-
cal vent, however, shall not exceed 7 times the
flow area of the listed appliance categorized vent
area, drafthood outlet area or flue collar area un-
less designed in accordance with approved engi-
neering methods.
4-- For multiple appliance vents: The flow area of the
largest sectionof vertical vent or chimney shall not
exceed 7 times the smallest listed appliance cate-
gorizedvent area, flue collar areaor drafthoodout-
let area unless designed in accordance with ap-
proved engineering methods.
5-- The entire length of single wallmetal vent connec-
tor shall be readily accessible for inspection, clean-
ing, and replacement.
6-- Single appliance venting configurations with zero
lateral lengths, see tables 2 and 3, are assumed to
have no elbows in the vent system. For all other
vent configurations, vent system is assumed to
have two 90E elbows. For each additional 90E el-
bow or equivalent (for example two 45E elbows
equal one 90E elbow) beyond two, the maximum
capacity listed in venting table should be reduced
by 10 percent (0.90 x maximum listed capacity).
7-- The common venting tables 4, 5, 6, and 7 were
generated using a maximum horizontal vent con-
nector length of 1--1/2 feet (18 inches) for each inch
of connector diameter as follows:
CONNECTOR
DIAMETER
(INCHES)
MAXIMUM HORIZONTALCONNECTOR LENGTH
(FEET)
3 4--1/2
4 6
5 7--1/2
6 9
7 10--1/2
3DJH ��
8-- If the commonvertical vent is offset, themaximum
common vent capacity listed in the common vent-
ing tables should be reduced by 20%, the equiva-
lent of two 90E elbows (0.80 x maximum common
vent capacity). The horizontal length of the offset
shall not exceed 1--1/2 feet for each inch of com-
mon vent diameter.
9-- The vent pipe shouldbe as short as possiblewith
the least number of elbows and angles to do the
job. The vent connector should be routed to the
vent utilizing the shortest possible route.
10-- A vent connector shall be supported without any
dips or sags and shall slope aminimumof 1/4� per
linear foot of connector, back towards the ap-
pliance.
11 Vent connectors shall be firmly attached to furnace
flue collars by sheet metal screws or other ap-
proved means, except vent connectors of listed
Type �B� vent material which shall be assembled
in accordance with the manufacturer�s instruc-
tions. Joints between sections of single wall con-
nector piping shall be fastened by sheet metal
screws or other approved means.
12-- When the vent connector used for Category I ap-
pliances must be located in or pass through a
crawl space or other areas whichmaybe cold, that
portion of the vent connector shall be listed
double--wall Type B vent material or material hav-
ing equivalent insulation qualities.
13-- All venting pipe passing through floors, walls, and
ceilingsmust be installed with the listed clearance
to combustible materials and be fire stopped ac-
cording to local codes. In absence of local codes,
refer to NFGC (Z223.1).
14-- No portion of the venting system can extend into, or
pass through any circulation air duct or plenum.
15-- Vent connectors serving Category I appliances
shall not be connected to any portion of mechani-
cal draft systems operation under positive pres-
sure such as Category III or IV venting systems.
16-- If vent connectors are combined prior to entering
the common vent, themaximum common vent ca-
pacity listed in the common venting tables must be
reduced by 10%, the equivalent of one 90E elbow
(0.90 x maximum common vent capacity).
17--Common vent diametermust always be at least as
large as the largest vent connector diameter.
18-- In no case, shall the vent connector be upsized
more than two consecutive table size diameters
over the size of the drafthood outlet or flue collar
outlet.
19-- A manual damper, barometric draft regulator or
flue restrictor must not be installed between fur-
nace and any chimney.
20-- When connecting this appliance to an existing dedi-
cated or common venting system, the venting sys-
tem, must be inspected for signs of corrosion, and
general condition. The sizing of the vent system
must be reviewed and conform to these instructions
and the provided venting tables in the U.S.A., and
the appropriate venting tables in the standards of
CAN/CGA--B149.1 and B149.2 of the National Gas
and Propane Installation Code in Canada. If the ex-
isting system is in conflict with these requirements,
the venting system must be resized.
TABLE 2
CAPACITY OF TYPE B DOUBLE--WALL VENTS WITH
TYPE B DOUBLE--WALL CONNECTORS
SERVING A SINGLE CATEGORY I APPLIANCE
Height Lateral
Vent and Connector Diameter -- D(inches)
HeightH
(f )
LateralL
(f )
4 Inch 5 Inch 6 InchH(feet)
L(feet) MAXIMUM Appliance Input Rating in
Thousands of Btu Per Hour
0 86 141 205
62 67 105 157
64 64 103 153
6 61 100 149
0 94 155 235
82 75 120 180
85 71 115 173
8 66 109 165
0 100 166 255
102 81 129 195
105 77 124 188
10 70 115 175
0 112 187 285
2 93 150 225
15 5 87 142 2175
10 82 135 208
15 76 128 198
0 119 202 307
2 100 166 249
205 96 160 241
2010 89 150 228
15 84 142 217
20 78 134 206
0 128 220 336
2 112 185 280
5 108 176 273
30 10 102 171 261
15 96 163 249
20 90 154 237
30 NR NR 219
NOTE: Single appliance venting configurations with zero lateral lengthsare assumed to have no elbows in the vent system. For all other vent con-figurations, the vent system is assumed to have two90E elbows. For eachadditional 90E elbow or equivalent (for example two 45E elbows equalone 90E elbow) beyond two, the maximum capacity listed in the ventingtable should be reduced by 10 percent (0.90 x maximum listed capacity).
3DJH ��
TABLE 3CAPACITY OF TYPE B DOUBLE--WALL VENTS WITH
SINGLE--WALL METAL CONNECTORSSERVING A SINGLE CATEGORY I APPLIANCE
Height Lateral
Vent and Connector Diameter -- D(inches)
HeightH
(f )
LateralL
(f )
4 Inch 5 Inch 6 InchH(feet)
L(feet) MAXIMUM Appliance Input Rating in
Thousands of Btu Per Hour
0 85 140 204
6
2 66 104 156
64 63 102 152
6 60 99 148
0 93 154 234
8
2 75 119 179
85 69 114 171
8 64 107 163
0 99 165 254
10
2 80 128 194
105 76 122 186
10 68 112 171
0 111 186 283
2 93 149 224
15 5 86 140 217
10 79 131 203
15 72 124 192
0 118 201 306
2 99 165 248
20
5 94 158 239
2010 86 146 224
15 80 136 210
20 NR 126 196
0 127 219 334
2 111 183 279
5 106 173 271
30 10 98 168 25730
15 NR 157 242
20 NR NR 228
30 NR NR NR
NOTE: Single appliance venting configurations with zero lateral lengthsare assumed to have no elbows in the vent system. For all other vent con-figurations, the vent system is assumed to have two 90E elbows. For eachadditional 90E elbow or equivalent (for example two 45E elbows equalone 90E elbow) beyond two, the maximum capacity listed in the ventingtable should be reduced by 10 percent (0.90 x maximum listed capacity).
TABLE 4CAPACITY OF TYPE B DOUBLE--WALL VENTS WITH
TYPE B DOUBLE--WALL CONNECTORSSERVING TWO OR MORE CATEGORY I APPLIANCES
VENT CONNECTOR CAPACITY
VentH i ht
ConnectorRi
Vent and Connector Diameter -- D(inches)
HeightH
RiseR
4 Inch 5 Inch 6 InchH
(feet)R
(feet) MAXIMUM Appliance Input Rating inThousands of Btu Per Hour
1 46 72 104
6 2 55 86 1246
3 62 96 139
1 48 76 109
8 2 57 90 129
3 64 101 145
1 50 78 113
10 2 59 93 134
3 67 104 150
1 53 83 120
15 2 63 99 1425
3 71 111 160
1 56 87 125
20 2 66 104 1490
3 74 116 168
1 59 93 134
30 2 70 110 15830
3 79 124 178
TABLE 5CAPACITY OF TYPE B DOUBLE--WALL VENTS WITH
TYPE B DOUBLE--WALL CONNECTORSSERVING TWO OR MORE CATEGORY I APPLIANCES
COMMON VENT CAPACITY
Common Vent Diameter -- D (inches)
VentHeig
4 Inch 5 Inch 6 Inch 7 InchHeight
Appliance Input Rating in Thousands of Btu Per HourhtH
(feet)
NAT+
NAT
FAN+
NAT
NAT+
NAT
FAN+
NAT
NAT+
NAT
FAN+
NAT
NAT+
NAT
FAN+
NAT
6 65 81 103 116 147 161 200 248
8 73 90 114 129 163 178 223 275
10 79 97 124 141 178 194 242 299
15 91 112 144 164 206 228 280 352
20 102 123 160 183 229 255 310 394
30 118 138 185 210 266 297 360 459
3DJH ��
TABLE 6CAPACITY OF TYPE B DOUBLE--WALL VENT WITH
SINGLE--WALL METAL CONNECTORSSERVING TWO OR MORE CATEGORY I APPLIANCES
VENT CONNECTOR CAPACITY
VentH i ht
ConnectorRi
Vent and Connector Diameter -- D(inches)
HeightH
RiseR
4 Inch 5 Inch 6 InchH
(feet)R
(feet) MAXIMUM Appliance Input Rating inThousands of Btu Per Hour
1 46 71 102
6 2 55 85 1236
3 62 95 138
1 52 81 116
15 2 62 97 138
3 70 109 157
1 57 89 129
30 2 67 106 152
3 76 120 172
TABLE 7CAPACITY OF TYPE B DOUBLE--WALL VENTS WITH
SINGLE--WALL METAL CONNECTORSSERVING TWO OR MORE CATEGORY I APPLIANCES
COMMON VENT CAPACITY
Common Vent Diameter -- D (inches)
VentHeig
4 Inch 5 Inch 6 Inch 7 InchHeight
Appliance Input Rating in Thousands of Btu Per HourhtH
(feet)
NAT+
NAT
FAN+
NAT
NAT+
NAT
FAN+
NAT
NAT+
NAT
FAN+
NAT
NAT+
NAT
FAN+
NAT
6 64 78 100 113 144 158 196 244
8 71 87 112 126 159 173 218 269
10 76 94 120 137 174 189 236 292
15 88 108 140 159 200 221 274 343
20 98 118 155 177 223 247 302 383
30 113 132 179 202 257 286 349 446
Removal of Unit from Common Venting System
In the event that an existing furnace is removed from a
venting system commonly run with separate gas ap-
pliances, the venting system is likely to be too large to
properly vent the remaining attached appliances. The
following test should be conducted while each ap-
pliance in operation and theother appliances not in op-
eration remain connected to the common venting sys-
tem. If the venting system has been installed
improperly, the system must be corrected as outlined
in the previous section.
1-- Seal any unused openings in the common venting
system.
2-- Visually inspect the venting system for proper size
and horizontal pitch and determine there is no
blockage or restriction, leakage, corrosion and
other deficiencies which could cause an unsafe
condition.
3-- Insofar as is practical, close all building doors and
windows andall doors between the space inwhich
the appliances remaining connected to the com-
mon venting system are located and other spaces
of the building. Turn on clothes dryers and any ap-
pliances not connected to the common venting
system. Turn on any exhaust fans, such as range
hoods and bathroom exhausts, so they will oper-
ate at maximum speed. Do not operate a summer
exhaust fan. Close fireplace dampers.
4-- Follow the lighting instruction. Place the appliance
being inspected in operation. Adjust thermostat
so appliance will operate continuously.
5-- Test for spillage at the draft hood relief opening af-
ter 5 minutes of main burner operation. Use the
flame of a match or candle, or smoke from a ciga-
rette, cigar or pipe.
6-- After it has been determined that each appliance
remaining connected to the common venting sys-
temproperly ventswhen testedas outlined above,
return doors, windows, exhaust fans, fireplace
dampers and any other gas--burning appliance to
their previous condition of use.
7-- If improper venting is observed during any of the
above tests, the common venting systemmust be
corrected. The common venting system should be
re--sized to approach the minimum size as deter-
mined by using the appropriate tables in appendix
G in the current standards of theNational FuelGas
Code ANSI Z223--1 in the U.S.A., and the appropri-
ate Category 1 Natural Gas and Propane ap-
pliances venting sizing tables in the current stan-
dards of theCAN/CGA--B149.1 and .2 in theNatural
Gas and Propane Installation Code in Canada.
3DJH ��
+RUL]RQWDO 9HQWLQJ
6,'( :$// 9(17,1* .,7 :,5,1*
&
/�
/����9$&
�
�
33&� ��
�237,21$/�
0
/� 01 7� 7� 7�
: 5 < *
:
*
5
<
�� 9$&7+(50267$7
7+(50267$7 &211(&7,2167(50,1$/ ,1 )851$&(
-81&7,21 %2;
5(/$<
&.� ��� &21752/ %2;
35(6685(6:,7&+
6:*32:(59(17(502725
$
%
� �
),*85( ��
7
),(/' ,167$//(' :,5,1*
)$&725< ,167$//(' :,5,1*
12
This furnace is design certified by the American Gas
Association for horizontal venting through an outside
wall only with the use of a Field Controls Company
Model #SWG--5L side wall venting kit available from
Lennox Dealer Service Center. No other Field brand
venting kit or any other manufacturer�s venting kit is
acceptable. Horizontal venting of this furnace without
the use of the above stated kit is prohibited. See figure
10 for field wiring of side wall horizontal venting kit.
When horizontally vented, minimum clearance for ter-
mination from electric meters, gas meters, regulators
and relief equipment is 4 ft. (1.2m).
At vent termination, care must be taken to maintain
protective coatings over buildingmaterials (prolonged
exposure to exhaust condensate can destroy protec-
tive coatings). It is recommended that the exhaust out-
let not be located within 6 ft. (1.8m) of a condensing
unit because the condensate can damage the painted
coating.
3DJH ��
*$6 3,3,1*
Gas Supply
1-- This unit is shipped standard for left side installa-
tion of gas piping. Simply connect gas supply to
piping assembly.
2-- A piping hole is also fabricated in the right side of
the unit for alternate piping arrangements.
3-- When connecting gas supply, factors such as
lengthof run, number of fittings and furnace rating
must be considered to avoid excessive pressure
drop. Table 8 lists recommendedpipe sizes for typ-
ical applications.
4-- Gas piping must not run in or through air ducts,
clothes chutes, chimneys or gas vents, dumbwait-
ers or elevator shafts.
5-- Piping should be sloped 1/4 inch per 15 feet (6mm
per 4.57m) upward toward the meter from the fur-
nace. The pipingmust be supported at proper inter-
vals, every 8 to 10 feet (2.44m to 3.05m), using suit-
able hangers or straps. A drip leg should be
installed in vertical pipe runs to the unit.
6-- In some localities, codes may require installation
of a manual main shut--off valve and union (fur-
nished by installer) external to the unit. Union
must be of the ground joint type.
,03257$17
&RPSRXQGV XVHG RQ WKUHDGHG MRLQWV RI JDV SLSLQJPXVW EH UHVLVWDQW WR WKH DFWLRQV RI OLTXLILHG SHWUR�OHXP JDVHV�
NOTE--In the case emergency shut--off is required, shut
offmainmanual gas valve and disconnectmain power
to unit. These devices should be properly labeled by
the installer.
NOTE--Installer must provide a 1/8� (3.2mm) N.P.T.
plugged tap in the field piping upstreamof the gas sup-
ply connection to the unit. Tap must be accessible for
test gauge connection. See figure 11.
),*85( ��
*5281'-2,1781,21
$8720$7,&*$6 9$/9(
�ZLWK PDQXDO VKXW� �RII YDOYH�
),(/'3529,'('
$1' ,167$//('
*5281'-2,17 81,21
/()7 6,'( 3,3,1*�67$1'$5'�
5,*+7 6,'( 3,3,1*�$/7(51$7(�
$8720$7,&*$6 9$/9(
�ZLWK PDQXDO VKXW� �RII YDOYH�
'5,3 /(*
'5,3 /(*
0$18$/0$,1 6+87� �2))
9$/9(�:LWK ���l ����PP� 1373OXJJHG 7DS 6KRZQ�
0$18$/0$,1 6+87� �2))
9$/9(�:LWK ���l ����PP� 137
3OXJJHG 7DS6KRZQ�
TABLE 8GAS PIPE CAPACITY -- FT3/HR (kL/HR)
Nominal Internal Length of Pipe--Feet(m)NominalIron Pipe Size--Inches(mm)
InternalDiameter
--Inches(mm)10
(3.048)20
(6.096)
30
(9.144)
40
(12.192)
50
(15.240)
60
(18.288)
70
(21.336)
80
(24.384)
90
(27.432)
100
(30.480)
1/4
(6.35)
.364
(9.246)
43
(1.13)
29
(.82)
24
(.68)
20
(.57)
18
(.51)
16
(.45)
15
(.42)
14
(.40)
13
(.37)
12
(.34)
3/8
(9.53)
.493
(12.522)
95
(2.69)
65
(1.84)
52
(1.47)
45
(1.27)
40
(1.13)
36
(1.02)
33
(.73)
31
(.88)
29
(.82)
27
(.76)
1/2
(12.7)
.622
(17.799)
175
(4.96)
120
(3.40)
97
(2.75)
82
(2.32)
73
(2.07)
66
(1.87)
61
(1.73)
57
(1.61)
53
(1.50)
50
(1.42)
3/4
(19.05)
.824
(20.930)
360
(10.19)
250
(7.08)
200
(5.66)
170
(4.81)
151
(4.28)
138
(3.91)
125
(3.54)
118
(3.34)
110
(3.11)
103
(2.92)
1
(25.4)
1.049
(26.645)
680
(919.25)
465
(13.17)
375
(10.62)
320
(9.06)
285
(8.07)
260
(7.36)
240
(6.80)
220
(6.23)
205
(5.80)
195
(5.52)
1--1/4
(31.75)
1.380
(35.052)
1400
(39.64)
950
(26.90)
770
(21.80)
660
(18.69)
580
(16.42)
530
(15.01)
490
(13.87)
460
(13.03)
430
(12.18)
400
(11.33)
1--1/2
(38.1)
1.610
(40.894)
2100
(59.46)
460
(41.34)
1180
(33.41)
990
(28.03)
900
(25.48)
810
(22.94)
750
(21.24)
690
(19.54)
650
(18.41)
620
(17.56)
2
(50.8)
2.067
(52.502)
3950
(111.85)
2750
(77.87)
2200
(62.30)
1900
(53.80)
1680
(47.57)
1520
(43.04)
1400
(39.64)
1300
(36.81)
1220
(34.55)
1150
(32.56)
2--1/2
(63.5)
2.469
(67.713)
6300
(178.39)
4350
(123.17)
3520
(99.67)
3000
(84.95
2650
(75.04)
2400
(67.96)
2250
(63.71)
2050
(58.05)
1950
(55.22)
1850
(52.38)
3
(76.2)
3.068
(77.927)
11000
(311.48)
7700
(218.03)
6250
(176.98)
5300
(150.07)
4750
(134.50)
4300
(121.76)
3900
(110.43)
3700
(104.77)
3450
(97.69)
3250
(92.03)
4
(101.6)
4.026
(102.260)
23000
(651.27)
15800
(447.39)
12800
(362.44)
10900
(308.64)
9700
(274.67)
8800
(249.18)
8100
(229.36)
7500
(212.37)
7200
(203.88)
6700
(189.72)
NOTE--Capacity given in cubic feet of gas per hour (kilo liters of gas per hour) and based on 0.60 specific gravity gas.
3DJH ��
Leak Check
After gas piping is completed, carefully check all piping
connections (factory and field) for gas leaks. Use a leak
detecting solution or other preferred means.
&$87,21
6RPH VRDSV XVHG IRU OHDN GHWHFWLRQ DUH FRUURVLYHWR FHUWDLQPHWDOV�&DUHIXOO\ ULQVHSLSLQJ WKRURXJKO\DIWHU OHDN WHVW KDV EHHQ FRPSOHWHG� 'R QRW XVHPDWFKHV� FDQGOHV� IODPH RU RWKHU VRXUFHV RI LJQL�WLRQ WR FKHFN IRU JDV OHDNV�
NOTE--In case emergency shutdown is required, shut
down main manual gas valve and disconnect main
power to unit. These devices should be properly la-
beled by the installer.
,03257$17
:KHQ WHVWLQJ SUHVVXUH RI JDV OLQHV� JDV YDOYHPXVWEH GLVFRQQHFWHG DQG LVRODWHG� 6HH ILJXUH ��� *DVYDOYHV FDQ EH GDPDJHG LI VXEMHFWHG WR PRUH WKDQ��� SVLJ ����� N3D��
),*85( ��
0$18$/ 0$,1 6+87� �2))
9$/9( :,// 127
+2/' 1250$/
7(67 35(6685(
&$3
)851$&(
,62/$7(*$6 9$/9(
The furnace must be isolated from the gas supply sys-
tem by closing its individual manual shut--off valve
during anypressure testingof thegas supply systemat
pressures equal to or less than 1/2 psig (3.48 kPa).
,03257$17
*��; VHULHV XQLWV �XQLWV HTXLSSHGZLWK IODPH URGV�DUH DSSURYHG IRU XVH ZLWK QDWXUDO JDV RQO\�
(/(&75,&$/
Refer to figure 13 for blower control board, figure 14 for
point to point field wiring and figure 15 for schematic
wiring diagrams and troubleshooting.
1-- Select fuse and wire size according to the blower
motor amps.
2-- Snapholeplugs areprovidedonboth sidesof cabi-
net to facilitate wiring.
3-- Install room thermostat according to instructions
provided with thermostat.
4-- Install a separate fused disconnect switch near the
unit so power can be turned off for servicing.
5-- Before connecting thermostat wiring to unit, re-
move screws holding the hinged section of the
control box. Swing the hinged section downward
to to ensure wires are proper length.
6-- Complete wiring connections to equipment using
wiringdiagramsprovidedwithunit and in figures 14,
15 and NO TAG. Use 18 gauge wire or larger for
thermostat connections.
7-- Electrically ground unit in accordance with local
codes or, in the absence of local codes, in accor-
dancewith the current National Electric Code (ANSI/
NFPA No. 70) and in Canada with the current Cana-
dian Electric Code part 1 (CSA standard C22.1).
127(�1RQ� �LQVXODWHG JURXQG ZLUHV PXVW EH
ZUDSSHG LQ HOHFWULFDO WDSH WR DYRLG GDPDJLQJ WKH
%&&� EORZHU FRQWURO FHQWHU�
8-- A 120 volt accessory terminal (ACC) is provided on
the BCC2 blower control center. Any accessory
ratedup to1ampcanbe connected to this terminal
and the neutral leg of the accessory can be at-
tached to any free 120 volt neutral terminal on the
BCC2 blower control center. The accessory termi-
nal is energized whenever the blower is in opera-
tion. See figure 13. A troubleshooting flowchart
for the BCC2blower control is located in figure 31.
9-- The continuous fan (CF) 120 volt terminal is used
with an optional continuous low fan kit that is
available from Lennox. The kit allows the furnace
blower to run continuously on low speed.
3DJH ��
),*85( ��
%&&� %/2:(5 &21752/ %2$5'
1(875$/7(50,1$/6
$&&(6625<7(50,1$/
7+(50267$7 7(50,1$/675,3 �'(7$&+$%/(�
%/2:(5 7,0($'-8670(17
-803(5
+($7,1*63((' 7$37(50,1$/
&22/,1*63((' 7$37(50,1$/
'800<7(50,1$/6
&217,18286 )$17(50,1$/
7R 5HPRYH 7HUPLQDO 6WULS�*UDVS (QGV RI %ORFN %HWZHHQ7KXPE DQG )RUHILQJHU� 3XVK
%ORFN 'RZQ DQG 2XW�
),*85( ��
< 5 :*
*: < &5
%&&� &21752/
&21752/ %2;
7+(50267$7
,*1,7,21
&21752/
*$6
9$/9(
'$03(5
'225
6:,7&+
)/$0(
52//287
6:,7&+
/,0,7
%/2&.('
9(17
6+872))
6:,7&+
%/$&.
:+,7(
72 &2035(6625
&217$&725
),(/' ,167$//(' /2: 92/7$*(
),(/' ,167$//(' /,1( 92/7$*(
7<3,&$/ *�� ),(/' :,5,1* ',$*5$0
/� 1
)86('',6&211(&76:,7&+
�)851,6+('%<,167$//(5�
*5281'
75$16)250(5
'225
,17(5/2&.
6:,7&+
3DJH ��
),*85( ��
7<3,&$/ *��( :,5,1* ',$*5$0
3DJH ��
81,7 67$57��83
FOR YOUR SAFETY READ BEFORE LIGHTING
:$51,1*
'R QRW XVH WKLV IXUQDFH LI DQ\ SDUW KDV EHHQ XQGHU�ZDWHU� ,PPHGLDWHO\ FDOO D TXDOLILHG VHUYLFH WHFKQL�FLDQ WR LQVSHFW WKH IXUQDFH DQG WR UHSODFH DQ\ SDUWRI WKH FRQWURO V\VWHP DQG DQ\ JDV FRQWURO ZKLFKKDV EHHQ XQGHU ZDWHU�
:$51,1*
,I RYHUKHDWLQJ RFFXUV RU LI JDV VXSSO\ IDLOV WR VKXWRII� VKXW RII WKH PDQXDO JDV YDOYH WR WKH DSSOLDQFHEHIRUH VKXWWLQJ RII HOHFWULFDO VXSSO\�
&$87,21
%HIRUH DWWHPSWLQJ WR SHUIRUP DQ\ VHUYLFH RU PDLQ�WHQDQFH� WXUQ WKH HOHFWULFDO SRZHU WR XQLW 2)) DWGLVFRQQHFW VZLWFK�
BEFORE LIGHTING smell all around the appliance area
for gas. Be sure to smell next to the floor because some
gas is heavier than air and will settle on the floor.
Use only your hand to push in or turn the gas control
knob or lever. Never use tools. If the knob or lever will
not push in or turn by hand, do not try to repair it, call a
qualified service technician. Force or attempted repair
may result in a fire or explosion.
To place G20 furnace into operation:
All G20 units are equipped with an intermittent pilot igni-
tion system. Do not attempt to manually light pilots on
these furnaces. Each time thermostat calls forheat, thepi-
lot will automatically light. The pilot does not burn when
there is no call for heat on units with electronic ignitions.
:$51,1*
,I \RXGRQRW IROORZ WKHVH LQVWUXFWLRQV H[DFWO\� D ILUHRU H[SORVLRQPD\ UHVXOW FDXVLQJ SURSHUW\ GDPDJH�SHUVRQDO LQMXU\ RU ORVV RI OLIH�
*DV 9DOYH 2SHUDWLRQ �)LJXUHV �� ���
1-- STOP! Read the safety information at the begin-
ning of this section.
2-- Set thermostat to lowest setting. See figure 16.
3-- Turn off all electrical power to appliance.
4-- This appliance is equipped with an ignition device
which automatically lights the pilot. Do not try to
light the pilot by hand.
7+(50267$76
),*85( ��
5-- Remove control access panel.
6-- On Honeywell VR8204 gas valves, turn knob on
gas valve clockwise to OFF. Units with Robert-
shaw 7200 gas valve, depress lever and move to
OFF position. Do not force. See figure 18.
21
2))
),*85( ��
HONEYWELL VR8204 SERIES GAS VALVE
*$6 9$/9( 6+2:1 ,1 2)) 326,7,21
*$6 9$/9(
6(/(&725
$50
,1 2))
326,7,21
52%(576+$: ���� *$6 9$/9(
),*85( ��
7-- Wait five (5) minutes to clear out any gas. If you
then smell gas, STOP! Immediately call your gas
supplier from a neighbor�s phone. Follow the gas
supplier�s instructions. If you do not smell gas go
to next step.
8-- On Honeywell VR8204 gas valves, turn knob on
gas valve counterclockwise to ON. Units with
Robertshaw 7200 gas valve, depress lever and
move to ON position. Do not force.
9-- Replace control access panel.
10-- Turn on all electrical power to unit.
3DJH ��
11-- Set thermostat to desired setting.
NOTE--When unit is initially started, steps 1 through 11
may need to be repeated to purge air from pilot line.
12-- If the appliance still will not operate, follow the
instructions �To Turn Off Gas To Unit� and call
your service technician or gas supplier.
7R 7XUQ 2II *DV 7R 8QLW
1-- Set thermostat to lowest setting.
2-- Turnoff all electrical power tounit if service is to be
performed.
3-- Remove control access panel.
4-- On Honeywell VR8204 gas valves, turn knob on gas
valve clockwise to OFF. Units with Robertshaw
7200 gas valve, depress lever andmove toOFFposi-
tion. Do not force.
5-- Replace control access panel.
+,*+ $/7,78'( ,1)250$7,21
G20 series units are certified for installations from 0 to
4000 feet (0 to 1219m) above sea level without modifi-
cation. For installations from 4000 feet to 7500 feet
(1219m to 2286m) above sea level, a high altitude kit
(44H56) must be installed. The kit contains special flue
baffles used to replace factory--installed baffles. No
derate is required.
*$6 35(6685( $'-8670(17
Gas Flow
To check for proper gas flow to combustion chamber, de-
termineBtu input from appliance rating plate. Divide this
input rating by theBtuper cubic foot of available gas. Re-
sult is the required number of cubic ft. (cubic meter) per
hour. Determine the flow of gas through gas meter for
twominutes andmultiply by 30 to get the hourly flow of
gas to burner.
Gas Pressure
1-- Check gas line pressure with unit firing at maxi-
mum rate. A minimum of 4.5� w.c. (1.12kPa) for
natural gas or 10.5� w.c. (2.61kPa) for LP/propane
gas should be maintained.
2-- After linepressurehasbeencheckedandadjusted,
check manifold pressure. Correct manifold pres-
sure for LP/propane gas is 9.5� w.c. (2.36kPa) No
adjustment is needed inhigh altitude applications.
A natural gas to LP/propane gas changeover kit is
required to convert unit. Refer to the installation
instructions supplied with changeover kit for con-
version procedure.
Correct manifold pressure for natural gas is 3.5�
w.c. (.87kPa). No adjustment is needed in high alti-
tude applications. See figures 19 and 20 for man-
ifold pressure adjustment screw location.
52%(576+$: ���� *$6 9$/9(
5(*8/$725 $'-8670(17 6&5(: /2&$7,21
),*85( ��
5(*8/$725&29(5 6&5(: $'-867,1*
6&5(:
,1/(735(6685(
7$3
,1/(735(6685(
7$3
+21(<:(// *$6 9$/9(
5(*8/$725 $'-8670(17 6&5(: /2&$7,21
&$3 6&5(:�%ODFN�
$'-867,1* 6&5(:�:KLWH�
*$6 ,1/(7
35(6685( 5(*8/$725
),*85( ��
3DJH ��
27+(5 81,7 $'-8670(176
Limit Control
Limit Control--Factory set: No adjustment necessary.
Fan Control
The fan on time of 45 seconds is not adjustable. Fan off
time (time that the blower operates after the heat de-
mand has been satisfied) can be adjusted by moving
the jumper on the BCC2blower control center. The unit
is shipped with a factory fan off setting of 90 seconds.
Fan off timewill affect comfort and is adjustable to sat-
isfy individual applications. See figure 21.
��
���
��� ���
��
���
���
���
��
���
��� ���
��
���
��� ���
��
���
��� ���
-803(5
-803(5
-803(5
-803(5
12 -803(5
�� 6(&21' )$12)) 7,0(
��� 6(&21' )$12)) 7,0(
��� 6(&21' )$12)) 7,0(
��� 6(&21' )$12)) 7,0(
��� 6(&21' )$12)) 7,0(
),*85( ��
)$1 2)) 7,0( $'-8670(17
Temperature Rise
Check temperature rise and, if necessary, adjust blow-
er speed to maintain temperature rise within range
shown on unit rating plate.
Thermostat Adjustment
Set thermostat heat anticipation setting for G20 units
at .10 ampsor at the lowest setting availablebutnot be-
low .10 amps. An isolation relay is built into the BCC2
blower control board to enhance the compatibility of
the thermostat to the gas control.
Electrical
1-- Check all wiring for loose connections.
2-- Check for correct voltage at unit (unit operating).
3-- Check amp--draw on blower motor.
Motor Nameplate__________Actual__________
Blower Speeds
Blower speed selection is accomplished by changing
the taps at the harness connector at the blower motor.
See figure 22.
Refer to speed selection chart on unit wiring diagram.
NOTE--CFM readings are taken external to unit with a
dry evaporator coil and without accessories.
),*85( ��
%/2:(5 63((' 7$3 6(/(&7,21
+$51(66
&211(&725
'(35(66 7$% 72 5(/($6(
:,5( &211(&725� 6(/(&7
&211(&725 /2&$7,21 )25
1(: 63(('� ,16(57 :,5( 81�
7,/ ,7 &/,&.6�
Flue and Chimney
1-- Check flue pipe, chimney and all connections for
tightness and to make sure there is no blockage.
2-- Check unit for proper draft.
Failure to Operate
If unit fails to operate check the following:
1-- Is thermostat calling for heat?
2-- Is main disconnect switch closed?
3-- Is there a blown fuse?
4-- Is filter dirty or plugged? Dirty or plugged filters
will cause unit to go off on limit control.
5-- Is gas turned on at meter?
6-- Is manual main shut--off valve open?
7-- Is internal manual shut--off valve open?
After items 1 through 7 have been checked and unit still
will not start, manually reset vent safety shut--off switch
located at the right sideof draft hood. If unit operation re-
sumes and then cuts out again, inspect furnace vent sys-
tem for proper sizing and installation. Also, check for
vent blockage and for proper draft. If unit still does not
start, reset roll--out switch on burner box. See figure 2. If
unit starts and cuts out, check heat section for blockage.
Pilot and Burner Flame
After the G20 unit has been installed and wired, the pi-
lot flame should be periodically checked and adjusted,
if necessary, to insure proper unit operation. Use the
following procedure to adjust the pilot flame.
Pilot Flame Adjustment
1-- Turn off power to the unit.
2-- Disconnect wire from MV terminal on the gasvalve.
3DJH ��
3-- On Honeywell VR8204 gas valves, turn knob ongas valve counterclockwise toON. Units with Rob-ertshaw7200gas valve, depress lever andmove toON position. Do not force.
4-- Restore power to unit.
5-- Set thermostat to call for heat.
At this point the pilot valve portion of the gas valve will
be energized after a call for heat is initiated. Pilotwill then
light. Examine the pilot flame to determine if it is a soft,
stable flame that surrounds the flame sensor. See figure
23. If this is not the case, the pilot needs adjustment.
3,/27 )/$0(�6LGH 9LHZ�
%851(5
),*85( ��
)/$0( 6(1625
6-- Identify the gas valve being used and locate the pi-
lot adjustment screw. On some gas valves the ac-
tual adjustment screw is under a cap. See figures
24, and 25 for pilot adjustment screw locations.
21
2))
),*85( ��
HONEYWELL VR8204 SERIES GAS VALVE
3,/27 $'-8670(17 6&5(:�81'(5 &$3�
),*85( ��
52%(576+$: ���� *$6 9$/9(
3,/27 $'-8670(17 6&5(:
3,/27
$'-�
7-- Turn thepilot adjustment screwuntil the pilot flameis soft and stably surrounds the flame sensor.
8-- Take a microamp reading of the flame signal com-ing from the flame sensor. The normal range is0.80 to 1.20 microamps with a minimum of 0.70microamps.
9-- After correct pilot flame has been obtained, adjustthermostat to stop a call for heat.
10-- Turn off power to unit.
11-- Reconnect MV wire to MV terminal on gas valve.
12-- Restore power to unit and assure normal operation.
Burner Flame
Start burner and allow to operate for a few minutes to
establish normal burning conditions. Check burner
flame by observation. Flame should be predominantly
blue in color, strong in appearance and should rise di-
rectly from the burner ports in the heat exchanger.
Check to see that flame is burning from all continuous
ribbon ports and that flame does not impinge on the
sides of the heat exchanger.
%851(5 )/$0(
),*85( ��
127(� �9,(: %851(5 )/$0( 7+528*+'$03(5 23(1,1* �1RW 6KRZQ�
6(59,&(
:$51,1*
'LVFRQQHFW SRZHU EHIRUH VHUYLFLQJ XQLW�
&$87,21
/DEHO DOO ZLUHV SULRU WR GLVFRQQHFWLRQ ZKHQ VHUYLF�LQJ FRQWUROV� :LULQJ HUURUV FDQ FDXVH LPSURSHUDQG GDQJHURXV RSHUDWLRQ� 9HULI\ SURSHU RSHUDWLRQDIWHU VHUYLFLQJ�
At the beginning of each heating season, the system
should be checked as follows:
Blower
Check and clean blower wheel for any debris. Blower
motor is prelubricated for extended bearing life. No
further lubrication is needed.
3DJH ��
Filters
1-- Filters should be inspected monthly and must be
cleaned or replaced when dirty to assure proper
furnace operation.
2-- Reusable foam filters supplied with G20 can be
washed with water and mild detergent. When dry,
they should be sprayed with filter handicoater prior
to reinstallation. Filter handicoater is RP Products
coating no. 481 and is available as Lennox part no.
P--8--5069. If replacement is necessary, refer to
table 9.
7$%/( �),/7(5 6,=( $1' 3$57 180%(5
MODEL NUMBERSIDE RETURNInches (mm)
BOTTOM RETURNInches (mm)
4�� ���� 4�� ����4�� ���� 4�� ����
�� ; �� ; ����� ; ��� ; ���
3� ��� �����
�� ; �� ; ����� ; ��� ; ���
3� ��� �����
4�� ���� 4���� ������ ; �� ; �
���� ; ��� ; ���3� ��� �����
�� ; �� ; ����� ; ��� ; ���
��+��
4���� �����4���� ����� 4���� ����
�� ; �� ; ����� ; ��� ; ���
3� ��� �����
�� ; �� ; ����� ; ��� ; ���
��+��
4���� ������ ; �� ; �
���� ; ��� ; ���3� ��� �����
�� ; �� ; ����� ; ���� ; ���
��+��
Flue and Chimney
Check flue pipe, chimney and all connections for tight-
ness and to make sure there is no blockage.
Electrical Check
1-- Check all wiring for loose connections.
2-- Check for correct voltage at unit (unit operating).
3-- Check amp--draw on blower motor.
Motor Nameplate__________Actual__________
Cleaning Heat Exchanger and Burners
NOTE--Usepapers or protective covering in frontof fur-
nace while cleaning furnace.
To clean heat exchanger:
1-- Turn off both electrical and gas power supplies to
furnace. Refer to figures 1 and 2 during disassem-
bly and reassembly procedures.
2-- Remove burner and upper access panel, flue pipe
and draft hood.
3-- Disconnect supply gas piping.
4-- Remove burner box top by removing four holding
screws.
5-- Remove two screws each from the left and right
patch plates. Remove patch plates, damper prove
switch cover and damper.
6-- Remove screws holding gasmanifold in place and
pull burners from heat exchanger.
7-- Remove baffles inside top opening of heat exchang-
er by twisting tabs to align with slots in baffles.
8-- Insert a 24� (600 mm) steel rod that has a 20�
(508mm) length of chain attached to one end into
top opening of heat exchanger. See figure 27.
&/($1,1* +($7 (;&+$1*(5
&RQQHFW FKDLQ WR URG DQG GURSFKDLQ GRZQ WKURXJK WRS RI KHDW H[�FKDQJHU� &RQQHFW DW ERWWRP WRDQRWKHU URG� 0RYH URGV XS DQGGRZQ� EDFN DQG IRUWK WR FOHDQ KHDWH[FKDQJHU�
),*85( ��
9-- Shake rod to drop chain through the clamshell into
burner cavity in bottom of heat exchanger.
10-- Attachbottomof chain to another 24� (600mm) rod.
11-- Push and pull the rods back and forth and up and
down with a vigorous motion. The chain will dis-
lodge the soot and scale deposits inside the heat
exchanger. Repeat for each clamshell.
12-- With a shop vacuum or rags, clean out soot and
scale deposits from bottom of heat exchanger.
7R FOHDQ EXUQHUV�
NOTE--FOR UNITS WITH FLAME RODS, remove two
springs and withdraw rods from back of burner. Clean
flame rods with wire brush. Continue with items 13
through 15 below and reinstall flame rods and springs.
13-- Clean top of burner ports with a wire brush.
14-- Clean burner ports by inserting a cleaning tool
(made from a piece of sheet metal cut to fit the
burner ports) andwork in andout of eachport. See
figure 29.
&/($1,1* 723
),*85( ��
&/($1,1* 32576
),*85( ��
&/($1,1* ,16,'(
),*85( ��
3DJH ��
15-- Clean inside of each burner with a bottle cleaning
brush. See figure 30.
16--Replaceburnersmaking sure to fully engage in rear
receiving slot in heat exchanger. Resecure gas
manifold and supply piping.
17--Reinstall baffles inside top opening of heat ex-
changer twisting tabs to secure baffles.
18-- Resecure damper assembly, damper prove switch
cover and burner box top. Carefully open damper
by hand to ensure that the damper spring closes
damper correctly and that the damper prove
switch is engaged when damper is open.
&$87,21
8VH H[WUHPH FDUH ZKHQ RSHQLQJ GDPSHU GRRU WRSUHYHQW SHUPDQHQW GDPDJH WR WKH GDPSHU PRWRU�
19-- Before replacing draft hood, flue pipe and access
panels, inspect draft hood gasket. Replace gasket
if necessary.
20-- Carefully check all piping connections (factory and
field) for gas leaks. Use a leak detecting solution or
other preferred means.
&$87,21
6RPH VRDSV XVHG IRU OHDN GHWHFWLRQ DUH FRUURVLYHWR FHUWDLQPHWDOV�&DUHIXOO\ ULQVHSLSLQJ WKRURXJKO\DIWHU OHDN WHVW KDV EHHQ FRPSOHWHG� 'R QRW XVHPDWFKHV� FDQGOHV� IODPH RU RWKHU VRXUFHV RI LJQL�WLRQ WR FKHFN IRU JDV OHDNV�
21-- Turn on gas and electrical supply.
5(3$,5 3$576 /,67
The following repair parts are available through inde-
pendent Lennox dealers.When ordering parts, include
the complete furnace model number listed on the
A.G.A. or C.G.A. ratingplate ---- Example:G20Q5/6--150.
CABINET PARTS
Upper access panel
Blower panel
Top strip
Cabinet cap
CONTROL PANEL PARTS
Transformer
Blower Control Center (BCC2)
BLOWER PARTS
Blower wheel
Motor
Motor mounting frame
Blower housing cut--off plate
HEATING PARTS
Heat exchanger
Gas manifold
Draft hood
Gas valve
Main burners
Ignition control
Main burner orifices
Ignition cable
Pilot burner
Igniter
Pilot/electrode assembly
Damper switch
Limit control
Couplings
Flame roll--out switch
Damper spring
Blocked vent shut--off switch
9 pin plug
Damper motor
Grommets
*�� 67$57��83 $1' 3(5)250$1&( &+(&. /,67
)LOWHU &OHDQ 6HFXUH"
6XSSO\ 9ROWDJH
(OHFWULFDO &RQQHFWLRQV 7LJKW"
67$57� �83 $1' 3(5)250$1&( &+(&. /,67
-RE 1DPH
-RE /RFDWLRQ
,QVWDOOHU
8QLW 0RGHO 1R�
)XUQDFH %WX ,QSXW
/LQH 3UHVVXUH
-RE 1R�
&LW\
&LW\
6HULDO 1R�
'DWH
6WDWH
6HUYLFH7HFKQLFLDQ
$LU 6KXWWHUV 3URSHUO\ $GMXVWHG �,I ,QVWDOOHG�"
)OXH &RQQHFWLRQV 7LJKW"
+($7,1* 6(&7,21
7+(50267$7
&DOLEUDWHG" +HDW $QWLFLSDWRU 3URSHUO\ 6HW" /HYHO"5HJXODWRU 3UHVVXUH
)XHO 7\SH� 1DWXUDO *DV" /3�3URSDQH *DV"
%ORZHU 0RWRU $PSV
%ORZHU 0RWRU +�3�
%ORZHU 0RWRU /XEULFDWLRQ 2�.�"
*DV 3LSLQJ &RQQHFWLRQV 7LJKW /HDN� �7HVWHG"
3URSHU 'UDIW"
9HQW &OHDU"
6WDWH
7HPSHUDWXUH 5LVH)DQ &RQWURO 2II 6HWWLQJ
)DQ &RQWURO 6HWWLQJ ��� 6HFRQGV )L[HG 2Q�
Z�F�� 1DW�� Z�F�� /3�3URSDQH
3DJH ��
&+(&.��� �81,7 32:(5�� �,17(5/2&. 6:,7&+�� �75$16)250(5�� �/,0,7 6:,7&+
67$57
,6��9$& $&5266
5 &"
<(6
-803(5 $&52666&5(:6 5 *
<(6
'2(6 81,723(5$7("
12
12
,6%/2:(5
5811,1* 21 +,*+63(('"
12,6
���9$& $&52661 $"
5(3/$&(%&&�
12<(6
<(6
&+(&. %/2:(5:,5,1* $1'%/2:(5
,6���9$& $&5266
1 $&&"
125(3/$&(%&&�
<(6
-803(5 $&52665 :
�5(029( 5 * -803(5�
,6'$03(5 02725
21"
12
5(3/$&(%&&�
12 ,6���9$& $&5266
1 &$%"
&+(&.'$03(5 02725:,5,1* $1'
'$03(5 02725
<(6
<(6 ,681,7 /,7"
12
&+(&.��� �'$03(5 02725�� �,*1,7,21 &21752/�� �*$6 9$/9(�� �,*1,725�� �/,0,7 6:,7&+(6�� �3529( 6:,7&+<(6
,6 %/2:(55811,1* 21 /2:63(('� �� 6(&�
$)7(5 )851$&( /,*+76"
12,6
���9$& $&52661 +"
<(6
,6��9$& $&5266
& 9"
5(3/$&(%&&�
12
12
&+(&.:,5,1*
<(6,6���9$& $&5266
1 $&&"
<(6
5(029(5 :
-803(5
$)7(57+( 6(/(&7('7,0(� '2(6 7+(%/2:(5 7851
2))"
<(6 12
<(6
5(3/$&(%&&�
(1' 2) 7(67
%&&�
7528%/(6+227,1*
)/2:&+$57
12
5(3/$&(%&&�
&+(&. %/2:(5:,5,1* $1'%/2:(5
),*85( ��
&+(&. )86(�5(3/$&( ,) 1(('('�