+ All Categories
Home > Documents > INSTALLATION INSTRUCTIONS G20 SERIES UNITS

INSTALLATION INSTRUCTIONS G20 SERIES UNITS

Date post: 01-Jan-2017
Category:
Upload: leminh
View: 239 times
Download: 11 times
Share this document with a friend
24
,167$//$7,21 ,16758&7,216 * 6(5,(6 81,76 5(7$,1 7+(6( ,16758&7,216 )25 )8785( 5()(5(1&( :+$7 72 ’2 ,) <28 60(// *$6 ,I WKH LQIRUPDWLRQ LQ WKLV PDQXDO LV QRW IROORZHG H[DFWO\ D ILUH RU H[SORVLRQ PD\ UHVXOW FDXVLQJ SURSHUW\ GDPDJH SHUVRQDO LQMXU\ RU ORVV RI OLIH :$51,1* ’R QRW VWRUH RU XVH JDVROLQH RU RWKHU IODPPDEOH YDSRUV DQG OLTXLGV LQ WKH YLFLQLW\ RI WKLV RU DQ\ RWKHU DSSOLDQFH ,QVWDOODWLRQ DQG VHUYLFH PXVW EH SHUIRUPHG E\ D TXDOLILHG LQVWDOOHU VHUYLFH DJHQF\ RU WKH JDV VXSSOLHU - ’R QRW WU\ WR OLJKW DQ\ DSSOLDQFH - ’R QRW WRXFK DQ\ HOHFWULFDO VZLWFK GR QRW XVH DQ\ SKRQH LQ \RXU EXLOGLQJ - ,PPHGLDWHO\ FDOO \RXU JDV VXSSOLHU IURP D QHLJKERU•V SKRQH )ROORZ WKH JDV VXSSOLHU•V LQVWUXFWLRQV - ,I \RX FDQQRW UHDFK \RXU JDV VXSSOLHU FDOO WKH ILUH GHSDUWPHQW - ([WLQJXLVK DQ\ RSHQ IODPHV
Transcript
Page 1: INSTALLATION INSTRUCTIONS G20 SERIES UNITS

3DJH �

£

352'8&7 /,7(5$785(

¤���� /HQQR[ ,QGXVWULHV ,QF�

'DOODV� 7H[DV

,167$//$7,21

,16758&7,216

*�� 6(5,(6 81,76GAS UNITS

503,543M9/96Supersedes 503,222M

7$%/( 2) &217(176

UNIT DIMENSIONS 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .PARTS ARRANGEMENT 3. . . . . . . . . . . . . . . . . . . . . . . . . . .REQUIREMENTS 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .GENERAL 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .COMBUSTION, DILUTION AND VENTILATION AIR 5. . .INSTALLATION--Setting Equipment 7. . . . . . . . . . . . . . . . .RETURN AIR OPENING GUIDELINES 7. . . . . . . . . . . . . . . .FILTER ASSEMBLY AND FILTERS 8. . . . . . . . . . . . . . . . . . .DUCT SYSTEM 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .VENTING 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .GAS PIPING 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .ELECTRICAL 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .UNIT START--UP 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .HIGH ALTITUDE INFORMATION 19. . . . . . . . . . . . . . . . . . .GAS PRESSURE ADJUSTMENT 19. . . . . . . . . . . . . . . . . . .OTHER UNIT ADJUSTMENTS 20. . . . . . . . . . . . . . . . . . . . .SERVICE 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .REPAIR PARTS 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .START--UP AND PERFORMANCE CHECK LIST 23. . . . . .BCC2 TROUBLESHOOTING 24. . . . . . . . . . . . . . . . . . . . . . .

5(7$,1 7+(6( ,16758&7,216)25 )8785( 5()(5(1&(

:+$7 72 '2 ,) <28 60(// *$6�

,I WKH LQIRUPDWLRQ LQ WKLV PDQXDO LV QRWIROORZHG H[DFWO\� D ILUH RU H[SORVLRQPD\ UHVXOW FDXVLQJ SURSHUW\ GDPDJH�SHUVRQDO LQMXU\ RU ORVV RI OLIH�

:$51,1*

'R QRW VWRUH RU XVH JDVROLQH RU RWKHUIODPPDEOH YDSRUV DQG OLTXLGV LQ WKHYLFLQLW\ RI WKLV RU DQ\ RWKHU DSSOLDQFH�

,QVWDOODWLRQ DQG VHUYLFH PXVW EHSHUIRUPHG E\ D TXDOLILHG LQVWDOOHU�VHUYLFH DJHQF\ RU WKH JDV VXSSOLHU�

- 'R QRW WU\ WR OLJKW DQ\ DSSOLDQFH�

- 'R QRW WRXFK DQ\ HOHFWULFDO VZLWFK� GR QRWXVH DQ\ SKRQH LQ \RXU EXLOGLQJ�

- ,PPHGLDWHO\ FDOO \RXU JDV VXSSOLHU IURP DQHLJKERU·V SKRQH� )ROORZ WKH JDV VXSSOLHU·VLQVWUXFWLRQV�

- ,I \RX FDQQRW UHDFK \RXU JDV VXSSOLHU� FDOOWKH ILUH GHSDUWPHQW�

- ([WLQJXLVK DQ\ RSHQ IODPHV�

/LWKR 8�6�$�

Page 2: INSTALLATION INSTRUCTIONS G20 SERIES UNITS

3DJH �

G20 UNIT DIMENSIONS--INCHES (MM)

AIR FLOW

SUPPLYAIR

OPENING

FLUE OUTLET(center side to side)

22 (559)

2-1/4(57)

1-11/16(43)

2-5/8 (67)(Right)

28-3/8(721)

1-1/16(27)

1-1/16(27)

B

C

E

H

FReturn Air

Return Air

WHISPER HEAT

GAS PIPINGINLET

(Both Sides)

17-3/4(451)

ELECTRICALINLETS

(Both Sides)

RETURN AIROPENING(Either Sideor Bottom)

26-1/8(664)

A

D

22 (559) 2-1/16(52)

1-1/2 (38)

17-1/2 (445)(Left)

20-1/2 (521)(Right)

G

*OPTIONALBOTTOM RETURN AIR FILTER KIT REQUIRED

RETURN AIRFILTER

(Either Sideor *Bottom)

2-3/8 (60)(Left)

Model No. A B C D E F G H

G20Q2E(X)-50

G20Q3E(X)-50

G20Q2E(X)-75

G20Q3E(X)-75

49

(1245)

16-1/4

(413)

14-1/8

(359)

14

(356)

11

(279)

2-5/8

(67)

8-1/8

(206)

3-1/8

(79)

G20Q4E(X)-75

G20Q3/4E(X)-100

49

(1245)

21-1/4

(540)

19-1/8

(486)

14

(356)

14

(356)

3-5/8

(92)

10-5/8

(270)

3-1/8

(79)

G20Q5/6E(X)-100

G20Q3/4E(X)-125

G20Q5/6E(X)-125

53

(1346)

26-1/4

(667)

24-1/8

(613)

18

(457)

21

(533)

2-5/8

(67)

13-1/8

(333)

3-3/8

(86)

G20Q5/6E(X)-15053

(1346)

31-1/4

(794)

29-1/8

(740)

18

(457)

26

(660)

2-5/8

(67)

15-5/8

(397)

3-3/8

(86)

Page 3: INSTALLATION INSTRUCTIONS G20 SERIES UNITS

3DJH �

G20 PARTS ARRANGEMENT

FIGURE 1

PARTS IDENTIFICATION

(G20 Units Shown)

HEATEXCHANGER

DRAFTHOOD

UPPER ACCESSPANEL

BURNERS

BURNERBOX

IGNITIONCONTROL

BLOWER

GASMANIFOLD

BURNER BOXDAMPER ASSEMBLY

REAR BAFFLE

TOP STRIP

LIMITCONTROL

CABINET

CONTROL BOX

ROLL--OUTSWITCH

BLOCKED VENTSHUT--OFFSWITCH

CABINET CAP

GAS VALVE

PILOT/ELECTRODEASSEMBLY

REMOVABLEBURNERBOX TOP

DAMPERMOTOR/GEAR

PATCH PLATE

PATCHPLATE

SPRING

DAMPERSWITCH

DAMPER SWITCHCOVER

ROLL--OUTSWITCH

DAMPER

BURNERBOX

DAMPER BOX PARTS ARRANGEMENT

FIGURE 2

REMOVABLEBURNER BOX TOP

Page 4: INSTALLATION INSTRUCTIONS G20 SERIES UNITS

3DJH �

5(48,5(0(176

All G20 units are A.G.A. (American Gas Association) and

C.G.A (Canadian Gas Association) certified.

In the US, installation of Lennox gas central furnaces

must conform with local building codes or, in the ab-

senceof local codes,with the currentNational FuelGas

Code (ANSI--Z223.1). The National Fuel Gas Code is

available from:

American National Standards Institute, Inc.

1430 Broadway

New York, NY 10018

NOTE--G20X series units (units equipped with flame

rods) are certified for use with natural gas only.

Air supply for combustion and ventilation must con-

form to the methods outlined in the current National

Fuel Gas Code.

WARNING

Product contains fiberglass wool.

Disturbing the insulation in this product duringinstallation, maintenance, or repair will exposeyou to fiberglass wool. Breathing this may causelung cancer. (Fiberglass wool is known to theState of California to cause cancer.)

Fiberglass wool may also cause respiratory, skin,and eye irritation.

To reduce exposure to this substanceor for furtherinformation, consult material safety data sheetsavailable from address shown below, or contactyour supervisor.

Lennox Industries Inc.P.O. Box 799900Dallas, TX 75379--9900

The furnace is certified for installation clearances to com-

bustible material as listed on the appliance rating plate

and in table 1 for installations in an alcove or closet.

Clearances Location Inches (mm)

Service access

To combustiblematerials

From Draft HoodRelief Opening

Front

Top, side and rear

Flue

Front

36 (914)*

1 (25)

6 (152)**

6 (152)

NOTE--Service access clearance must be maintained.

TABLE 1

* If tight installation, front service clearance may be 24� (610mm).**1� (25mm) for type �B1� Vent Pipe.

Floor 0 (0)

Accessibility and service clearances must take prece-

dence over fire protection clearances.

Vent installations shall be in accordance with the

GAMA venting tables booklet supplied with this unit

and applicable provisions of local building codes .

NOTE--For installation on combustible floors, appliance

shall not be installed directly on carpeting, tile, or other

combustible material other than wood flooring.

For installation in a residential garage, unit must be

installed so that burner(s) and ignition source are lo-

cated no less than 18� (457 mm) above floor. Furnace

must be located or protected to avoid physical damage

by vehicles.

Unit must be adjusted to obtain a temperature rise

within the range specified on appliance rating plate.

Thedraft hoodshall be installed in the sameatmospheric

pressure zone as the combustion air inlet to the furnace.

G20 units must be installed so that electrical compo-

nents are protected from water.

When furnace is used in conjunction with cooling

units, it shall be installed in parallel with, or on the up-

stream side of, cooling units to avoid condensation in

the heating element.With a parallel flow arrangement,

damper (or othermeans to control the flow of air) shall

be adequate to prevent chilled air from entering the

furnace and, if manually operated, must be equipped

with means to prevent operation of either unit, unless

damper is in the full �heat� or �cool� position.

When installed, furnace must be electrically grounded

in accordance with local codes or, in the absence of lo-

cal codes, with the current National Electric Code,

ANSI/NFPA No. 70. The National Electric Code (ANSI/

NFPA No. 70) is available from:

National Fire Protection Association

470 Atlantic Avenue

Boston, MA 02210

Field wiring connection with unit must meet or exceed

specifications of type T wire and withstand a 63EF

(17EC) temperature rise. When furnace is installed so

that supply ducts carry air circulated by furnace to

areas outside space containing furnace, return air shall

be handled by a duct(s) sealed to the furnace casing

and terminating outside space containing furnace.

This furnace is certified for installation clearances to

combustible material as listed on appliance rating plate

and in table 1. Accessibility and service clearances must

take precedence over fire protection clearances.

In Canada, installation of C.G.A. certified units must

conform with current Standard CAN/CGA--B149.1

�Installation Code for Natural Gas Burning Appliances

and Equipment� and CAN/CGA--B149.2 �Installation

Code for Propane Gas Burning Appliances and Equip-

ment,� local plumbing or waste water codes and other

applicable local codes. Authorities having jurisdiction

shouldbe consultedbefore installation.Adequate clear-

Page 5: INSTALLATION INSTRUCTIONS G20 SERIES UNITS

3DJH �

ance shall be made around air openings into the vesti-

bule area. Provisions shall be made for proper opera-

tion and for combustion air and ventilation air supply

according to the current CAN/CGA--B149 standards.

All electrical wiring and grounding for the unitmust be

in accordancewith the current regulations of the Cana-

dian Electrical Code Part I (C.S.A. Standard C22.1) and/

or local codes.

NOTE--G20 series units must not be used as a

�construction heater� at any timeduring any phase of

construction. Very low return air temperature, harm-

ful vapors andmisplacementof the filterswill damage

the unit and its efficiency.

GENERAL

These instructions are intended as a general guide

and do not supersede local codes in anyway. Authori-

ties having jurisdiction should be consulted before

installation.

A--Shipping and Packing List

1--Leveling bolt package (if ordered)

1--Thermostat (if ordered)

1--Rubber grommet (for electrical make--up)

B--Shipping Damage

Check unit for shipping damage. Receiving party

should contact last carrier immediately if any shipping

damage is found.

WARNING

Improper installation, adjustment, alteration, ser-vice or maintenance can cause property damage,personal injury or loss of life. Installation and ser-vice must be performed by a qualified installer,service agency or the gas supplier.

COMBUSTION, DILUTION & VENTILATION AIR

Until recently, therewas no problem in bringing in suf-

ficient amounts of outdoor air for combustion ---- in-

filtration provided all the air that was needed and then

some. In today�s homes built with energy conservation

inmind, tight construction practices make it necessary

to bring in air from outside for combustion. Consider-

ationmust also be given to the use of exhaust fans, ap-

pliance vents, chimneys and fireplaces because they

force additional air that could be used for combustion

out of the house. Unless outside air is brought into the

home for combustion, negative pressure (pressure

outside is greater than inside pressure)will build to the

point that a down draft can occur in the furnace vent

pipe or chimney. Combustion gases enter the living

space creating a potentially dangerous situation.

In the absence of local codes concerning air for com-

bustion and ventilation, this section outlines guide-

lines and recommends procedures for installing G20

furnaces in amanner that ensures efficient and safeop-

eration. Special consideration must be given to com-

bustion air needs as well as requirements for exhaust

vents and gas piping. A portion of this information has

been reprintedwith permission from the National Fuel

Gas Code (ANSI--Z223.1). This reprintedmaterial is not

the complete and official position of the ANSI on the

referenced subject, which is represented only by the

standard in its entirety.

In Canada, refer to the standard CAN/CGA--B149.1 and

--B149.2 installation codes.

Combustion Air Requirements

&$87,21

,QVXIILFLHQW FRPEXVWLRQ DLU FDQ FDXVH KHDGDFKHV�QDXVHD� GL]]LQHVV RU DVSK\[LDWLRQ� ([FHVVLYH H[�SRVXUH WR FRQWDPLQDWHG FRPEXVWLRQ DLU ZLOO UHVXOWLQ VDIHW\ DQG SHUIRUPDQFH UHODWHG SUREOHPV�$YRLGH[SRVXUH WR WKH IROORZLQJ VXEVWDQFHV LQ WKH FRP�EXVWLRQ DLU VXSSO\�3HUPDQHQW ZDYH VROXWLRQV�&KORULQDWHG ZD[HV DQG FOHDQHUV�&KORULQH EDVH VZLPPLQJ SRRO FKHPLFDOV�:DWHU VRIWHQLQJ FKHPLFDOV�'H� �LFLQJ VDOWV RU FKHPLFDOV�&DUERQ WHWUDFKORULGH�+DORJHQ W\SH UHIULJHUDQWV�&OHDQLQJ VROYHQWV �VXFK DV SHUFKORURHWK\OHQH��3ULQWLQJ LQNV� SDLQW UHPRYHUV� YDUQLVKHV� HWF��+\GURFKORULF DFLG�&HPHQWV DQG JOXHV�$QWLVWDWLF IDEULF VRIWHQHUV IRU FORWKHV GU\HUV� DQG0DVRQU\ DFLG ZDVKLQJ PDWHULDOV�

All gas--fired appliances require air to be used for the

combustion process. If sufficient amounts of combus-

tion air are not available, the furnace or other appliance

will operate in an inefficient and unsafe manner.

Enough air must be provided to meet the needs of all

fuel--burning appliances, as well as appliances such as

exhaust fanswhich force air out of thehome.When fire-

places, exhaust fans, or clothes dryers are used at the

same time as the furnace, much more air is required to

ensure proper combustion and to prevent a down--draft

situation. Insufficient amounts of air also cause incom-

plete combustionwhich can result in carbonmonoxide.

The requirements for providing air for combustion and

ventilation depend largely on whether the furnace is

installed in an unconfined or confined space.

Page 6: INSTALLATION INSTRUCTIONS G20 SERIES UNITS

3DJH �

Unconfined Space

An unconfined space is an area such as a basement or

large equipment room with a volume greater than 50

cubic feet per 1,000 Btu (1.42m3 per .29kW) per hour of

the combined input rating of all appliances installed in

that space. This space also includes adjacent rooms

whicharenot separatedbyadoor. Thoughanareamay

appear to beunconfined, itmight benecessary tobring

in outdoor air for combustion if the structure does not

provide enough air by infiltration. If the furnace is lo-

cated in a building of tight construction with weather

stripping and caulking around thewindows anddoors,

follow the procedures outlined for using air from the

outside for combustion and ventilation.

Confined Space

A confined space is an area with volume less than 50 cu-

bic feet per 1,000 Btu (1.42m3per .29kW) per hour of the

combined input rating of all appliances installed in that

space. This definition includes furnace closets or small

equipment rooms.

When the furnace is installed so that supply ducts carry

air circulated by the furnace to areas outside the space

containing the furnace, the return air must be handled

by ducts which are sealed to the furnace casing and

which terminate outside the space containing the fur-

nace. This is especially important when the furnace is

mounted on a platform in a confined space such as a

closet or small equipment room. Even a small leak

around the base of the unit at the platform or at the re-

turn air duct connection can cause a potentially dan-

gerous negative pressure condition. Air for combus-

tion and ventilation can be brought into the confined

space either from inside the building or from outside.

Air from Inside

If the confined space housing the furnace adjoins space

categorized as unconfined, air can be brought in by pro-

viding two permanent openings between the two

spaces. Each opening must have a minimum free area

of 1 square inch per 1,000 Btu (645mm2 per .29kW) per

hour of the total input rating of all gas--fired equipment

in the confined space. Eachopeningmustbeat least 100

square inches (645cm2). One opening shall be within

12� (305mm) of the top of the enclosure and one open-

ing within 12� (305mm) of the bottom (See figure 3).

Air from Outside

If air from outside is brought in for combustion and

ventilation, the confined space shall be provided with

two permanent openings. One opening shall bewithin

12� (305mm)of the top of the enclosure andonewithin

12� (305mm) of the bottom. These openings must

communicate directly or by ducts with the outdoors or

spaces (crawl or attic) that freelycommunicatewith the

outdoors or indirectly through vertical ducts. Each

opening shall have a minimum free area of 1 square

inch per 4,000 Btu (645mm2 per 1.17kW) per hour of to-

tal input rating of all equipment in the enclosure (See

figures 4 and 5). When communicating with the out-

doors through horizontal ducts, each opening shall

have a minimum free area of 1 square inch per 2,000

Btu (645mm2 per .59kW) per total input rating of all

equipment in the enclosure (See figure 6).

(48,30(17 ,1 &21),1(' 63$&(

$// $,5 )520 ,16,'(

&+,01(<25 *$69(17

:$7(5+($7(5

23(1,1*6�7R $GMDFHQW

5RRP�

),*85( �

127(� �(DFK RSHQLQJ VKDOO KDYH D IUHH DUHD RI DW OHDVW � VTXDUH LQFKSHU �����%WX ����PP� SHU ���N:� SHU KRXURI WKH WRWDO LQSXW UDWLQJ RIDOO HTXLSPHQW LQ WKH HQFORVXUH� EXW QRW OHVV WKDQ ��� VTXDUH LQFKHV�

*��)851$&(

(48,30(17 ,1 &21),1(' 63$&($// $,5 )520 2876,'(

�,QOHW $LU IURP &UDZO 6SDFH DQG2XWOHW $LU WR 9HQWLODWHG $WWLF�

127(� �7KH LQOHW DQG RXWOHW DLU RSHQLQJV VKDOO HDFK KDYH D IUHH DUHD RIDW OHDVW � VTXDUH LQFK SHU ����� %WX ����PP�SHU ����N:� SHU KRXU RIWKH WRWDO LQSXW UDWLQJ RI DOO HTXLSPHQW LQ WKH HQFORVXUH�

9(17,/$7,21 /289(56�(DFK HQG RI DWWLF�

287/(7$,5 :$7(5

+($7(5

,1/(7$,5

&+,01(<25 *$69(17

9(17,/$7,21/289(56

�)RU XQKHDWHG FUDZOVSDFH�

),*85( �

*��)851$&(

Page 7: INSTALLATION INSTRUCTIONS G20 SERIES UNITS

3DJH �

(48,30(17 ,1 &21),1(' 63$&($// $,5 )520 2876,'(

�$OO $LU 7KURXJK 9HQWLODWHG $WWLF�

127(� �7KH LQOHW DQG RXWOHW DLU RSHQLQJV VKDOO HDFK KDYH D IUHH DUHD RIDW OHDVW RQH VTXDUH LQFK SHU ����� %WX ����PP�SHU ����N:� SHU KRXURI WKH WRWDO LQSXW UDWLQJ RI DOO HTXLSPHQW LQ WKH HQFORVXUH�

&+,01(<25 *$69(17

:$7(5+($7(5

287/(7$,5

9(17,/$7,21 /289(56�(DFK HQG RI DWWLF�

,1/(7 $,5�(QGV ��l DERYH

ERWWRP�

),*85( �

*��)851$&(

(48,30(17 ,1 &21),1(' 63$&($// $,5 )520 2876,'(

287/(7 $,5

,1/(7 $,5

:$7(5+($7(5

&+,01(<25 *$69(17

),*85( �

127(� �(DFK DLU GXFW RSHQLQJ VKDOO KDYH D IUHH DUHD RI DW OHDVW RQHVTXDUH LQFK SHU ����� %WX ����PP�SHU ���N:� SHU KRXU RI WKH WRWDOLQSXW UDWLQJ RI DOO HTXLSPHQW LQ WKHHQFORVXUH� ,I WKHHTXLSPHQW URRP LVORFDWHG DJDLQVW DQ RXWVLGHZDOO DQG WKH DLU RSHQLQJV FRPPXQLFDWH GL�UHFWO\ZLWK WKHRXWGRRUV� HDFKRSHQLQJ VKDOO KDYHD IUHHDUHD RI DW OHDVW� VTXDUH LQFKSHU �����%WX ����PP�SHU ����N:�SHU KRXU RI WKH WRWDOLQSXW UDWLQJ RI DOO RWKHU HTXLSPHQW LQ WKH HQFORVXUH�

*��)851$&(

When ducts are used, they shall be of the same cross--

sectional area as the free area of the openings towhich

they connect. The minimum dimension of rectangular

air ducts shall be no less than 3� (76mm). In calculating

free area, the blocking effect of louvers, grilles, or

screensmust be considered. If the design and free area

of protective covering is not known for calculating the

size opening required, it may be assumed that wood

louvers will have 20 to 25 percent free area and metal

louvers and grilles will have 60 to 75 percent free area.

Louvers and grilles must be fixed in the open position

or interlocked with the equipment so that they are

opened automatically during equipment operation.

,167$//$7,21��6HWWLQJ (TXLSPHQW

1-- Holes are provided in the corners of unit base for

leveling unit. Install leveling bolts (if desired) or

shim under unit. See figure 7.

127(� �,I OHYHOLQJ EROWV DUH XVHG� EH VXUH WR LQVWDOO WKH

SODVWLF QXWV DQG WLJKWHQ VQXJO\ EHIRUH VHWWLQJ WKH XQLW�

&$%,1(76,'(

$)7(5 81,7 ,6 /(9(/�7,*+7(1 7+,6 187

81,7%$6(

/(9(/ 81,7:,7+ 7+,6 187

,167$// 3/$67,&1876 :,7+ )/$7

6,'( 72:$5' %$6(�/(9(/,1*%2/7

/(9(/,1* %2/7 ,167$//$7,21

),*85( �

2-- Set unit in desired location allowing for clearances

listed on appliance rating plate. Also allow for gas

supply connection, electrical supply, vent connec-

tions and installation and service clearances.

5(7851 $,5 23(1,1* *8,'(/,1(6

:$51,1*

,PSURSHU LQVWDOODWLRQ RI XQLW FDQ UHVXOW LQ SHUVRQDOLQMXU\ RU GHDWK� &RPEXVWLRQ DQG IOXH SURGXFWVPXVWQHYHU EH DOORZHG WR HQWHU WKH UHWXUQ DLU V\VWHPRU DLULQ WKH OLYLQJVSDFH�8VHVKHHWPHWDO VFUHZVDQG MRLQWWDSH WR VHDO UHWXUQ DLU V\VWHP WR IXUQDFH�,Q SODWIRUP LQVWDOODWLRQV ZLWK IXUQDFH UHWXUQ� WKHIXUQDFH VKRXOG EH VHDOHG DLUWLJKW WR WKH UHWXUQ DLUSOHQXP� $ GRRU PXVW QHYHU EH XVHG DV D SRUWLRQ RIWKH UHWXUQ DLU GXFW V\VWHP� 7KH EDVH PXVW SURYLGHD VWDEOH VXSSRUW DQG DQ DLUWLJKW VHDO WR WKH IXUQDFH�$OORZ DEVROXWHO\ QR VDJJLQJ� FUDFNV� JDSV� HWF�)RU QR UHDVRQ VKRXOG UHWXUQ DQG VXSSO\ DLU GXFWV\VWHPV HYHU EH FRQQHFWHG WR RU IURP RWKHU KHDW�LQJ GHYLFHV VXFK DV D ILUHSODFH RU VWRYH� HWF� )LUH�H[SORVLRQ� FDUERQ PRQR[LGH SRLVRQLQJ� SHUVRQDOLQMXU\ DQG�RU SURSHUW\ GDPDJH FRXOG UHVXOW�

:$51,1*

%ORZHU GRRUPXVW EH VHFXUHO\ LQ SODFH ZKHQ EORZ�HU DQG EXUQHUV DUH RSHUDWLQJ� *DV IXPHV� ZKLFKFRXOG FRQWDLQ FDUERQPRQR[LGH� FDQ EH GUDZQ LQWROLYLQJ VSDFH UHVXOWLQJ LQ SHUVRQDO LQMXU\ RU GHDWK�

If cold air return is to terminate through the floor under

the furnace, a direct, airtight and sealed connection

must be made to the bottom of the furnace. For instal-

lations where the return air is taken from a return air

drop, unit may be installed using either the left or right

side of furnace.

For side return air applications, cut furnace cabinet at

sized knockout squares for maximum return air.

Return air canbebrought in either sideor at thebottom

of the unit. Scribe lines show the outline of each side

return air opening.

Page 8: INSTALLATION INSTRUCTIONS G20 SERIES UNITS

3DJH �

),/7(5 $66(0%/< $1' ),/7(56

G20 series units are equipped with a reusable foam filter.

The filtermustbe inplaceanytime theunit is inoperation.

A bottom return air kit is available for bottom return air

opening applications.

For side return air openings, use supplied filter racks to

hold filter. To install lower filter rack, remove two

screws from lower side of cabinet. Place flange of filter

rack inside bottom panel and side panel. Secure with

previously removed cabinet/base bottom screws. To

install upper filter rack, loosen screws fromside of cab-

inet at blower deck level. Insert three tabs in slots that

are on the inside of the cabinet. Tabs must be between

side panel and blower deck flange. Retighten screws to

secure. See figure 8.

),*85( �

),/7(5 5$&. )25 *���8VHG RQ VLGH UHWXUQ RQO\�

%27720

%$6(

/2:(5

),/7(5

5$&.

%/2:(5 '(&.

6,'( 3$1(/

),/7(5

3/$&( 833(5

),/7(5 5$&.

7$%

,172 6/27

/2:(5

),/7(5 5$&.

833(5

),/7(5 5$&. 7$%6

'8&7 6<67(0

Size and install supply and return air duct system us-

ing industry--approved standards that result in a quiet

and low--static system with uniform air distribution.

Supply Air Duct System

Installation of units not equippedwith a cooling coil re-

quire a removable access panel in the supply air duct.

The access panel should be large enough to permit in-

spection of heat exchanger for leaks after installation.

Lennox recommends using the SENSITTM HT kit for

heatexchanger inspections. Theaccess panelmust not

allow leaks in the supply air duct system.

Return Air Duct System

NOTE--All G20 series units with bottom return air require

a bottom return kit which is available as an accessory.

NOTE--Return air duct should be secured to the unit us-

ing rivets or S--locks. Using screws to secure the return

air duct to theunitwill interferewith the filter andcause

improper filtration.

9(17,1*

G20 series furnacesmust be vented in compliancewith

all local codes, the venting tables provided in this

manual for applications in the U.S.A., the current stan-

dards of CAN/CGA--B149.1 and --B149.2 in Canada, and

these instructions.

G20 series units havebeen classified as Category I type

furnaceswhen vertically vented in accordancewith the

latest edition of ANSI Z21.47 Central Furnace Standard

in the U.S.A. and the current standard of CAN/CGA--

B149.1 and B149.2 of the National Gas and Propane

Installation Code in Canada.

The vent sizing tables in this manual have been ex-

tracted from the National Fuel Gas Code (NFPA 54 /

ANSI Z223.1) and are provided for convenience to

serve as aguideline for proper vent installation. Proper

application, termination, construction and location of

vents must conform to local codes having jurisdiction.

In the absence of local codes, the NFGC serves as the

defining document.

Refer to the tables and the venting information con-

tained in these instructions for proper sizing and instal-

lation of the venting system.

Use this information in conjunction with the provided

venting tables in the U.S.A., and the appropriate vent-

ing tables in the standards of CAN/CGA--B149.1 and

B149.2 of the National Gas and Propane Installation

Code in Canada, to properly size the vent or vent con-

nector that attaches to the furnace flue collar.

Roundvent connectors shouldbeused in the following

sizes: --50 and --75 units, 4� (102mm); --100 units, 5�

(127mm); and --125 and --150 units, 6� (152mm). A 9�

(229mm) minimum length vertical vent connector

must be run from the furnace flue outlet to the first el-

bow. See figure 9.

Venting Using a Masonry Chimney

The following additional requirements apply when a

lined masonry chimney is being used to vent an G20

furnace:

A Category I appliance must never be connected to a

chimney that is servicing a solid fuel appliance. If a fire-

place chimney flue is used to vent this appliance, the

fireplace opening must be permanently sealed. See

figure 9.

Any masonry chimney used for venting a G20 series

gas furnace must be lined, and must be sized and

installed per all applicable local building codes or, in

the absence of local codes, the current National Fuel

Gas Code (ANSI--Z223.1) in the U.S.A. and the current

standards of CAN/CGA--B149.1 and --B149.2 in Canada.

Venting in an unlined masonry chimney is prohibited.

The effective area of the chimney serving a single ap-

pliance must be no less than the effective area of the

draft hood outlet. The chimney must extend vertically

at least 5 ft. (1.5m) above the flue collar.

Page 9: INSTALLATION INSTRUCTIONS G20 SERIES UNITS

3DJH �

�l����PP�0,1�

*��)851$&(

3(50$1(17/<6($/(' ),5(3/$&(

23(1,1*

+/

9(57,&$/ 9(17 86,1*

/,1(' 0$6215< &+,01(<

),*85( �

A chimney with one or more sides exposed to the out-

side of the structure is considered to be an exterior

chimney. A Type B or listed chimney lining system

passing through an unused masonry chimney flue is

not considered to be exposed to the outdoors.

Masonry chimneys used to vent Category I central fur-

naces must be either tile--lined or lined with a listed

metal lining systemordedicatedgas vent.Unlinedma-

sonry chimneys are prohibited.

A Type �B� vent or masonry chimney liner shall termi-

nate above the roof surface with a listed cap or a listed

roof assembly in accordancewith the terms of their re-

spective listings and the vent manufacturer�s instruc-

tions.

Do not install amanual damper, barometric draft regu-

lator, or flue restrictor between the furnace and the

chimney.

If type �B� double--wall vent is used inside a chimney,

no other appliance can be vented into the chimney.

Outer wall of type �B� vent pipe must not be exposed

to flue products.

Insulation for the flexible vent pipe must be an encap-

sulated fiberglass sleeve recommended by the flexible

vent pipe manufacturer.

The space between liner and chimney wall should

NOT be insulated with puffed mica or any other loose

granular insulating material.

If �B� vent or an insulated flexible vent pipe cannot be

used as liners, the chimney must be rebuilt to accom-

modate one of these methods or some alternate ap-

proved method must be found to vent the appliance.

When inspection reveals that an existing chimney is

not safe for the intended purpose, it shall be rebuilt to

conform to nationally recognized standards, lined or

relined with suitable materials or replaced with a gas

vent or chimney suitable for venting G20 series units.

The chimney passagewaymust be checked periodical-

ly to ensure that it is clear and free of obstructions.

General Venting Requirements

All G20 furnaces must be vented in accordance with

the methods outlined in these instructions.

1-- Vent diameter recommendations and maximum

runs allowed are found in the provided venting

tables in the U.S.A., and the appropriate venting

tables in the standards of CAN/CGA--B149.1 and

B149.2 of the National Gas and Propane Installa-

tion Code in Canada.

2-- In no case should the vent or vent connector diam-

eter be less than the diameter specified in the pro-

vided venting tables in the U.S.A., and the ap-

propriate venting tables in the standards of

CAN/CGA--B149.1 and B149.2 of the National Gas

and Propane Installation Code in Canada.

3-- For single appliance vents: If the vertical vent or

tile--lined chimney has a larger diameter or flow

area than the vent connector, use the vertical vent

diameter to determine theminimumvent capacity

and the vent connector diameter to determine the

maximumvent capacity. The flowareaof theverti-

cal vent, however, shall not exceed 7 times the

flow area of the listed appliance categorized vent

area, drafthood outlet area or flue collar area un-

less designed in accordance with approved engi-

neering methods.

4-- For multiple appliance vents: The flow area of the

largest sectionof vertical vent or chimney shall not

exceed 7 times the smallest listed appliance cate-

gorizedvent area, flue collar areaor drafthoodout-

let area unless designed in accordance with ap-

proved engineering methods.

5-- The entire length of single wallmetal vent connec-

tor shall be readily accessible for inspection, clean-

ing, and replacement.

6-- Single appliance venting configurations with zero

lateral lengths, see tables 2 and 3, are assumed to

have no elbows in the vent system. For all other

vent configurations, vent system is assumed to

have two 90E elbows. For each additional 90E el-

bow or equivalent (for example two 45E elbows

equal one 90E elbow) beyond two, the maximum

capacity listed in venting table should be reduced

by 10 percent (0.90 x maximum listed capacity).

7-- The common venting tables 4, 5, 6, and 7 were

generated using a maximum horizontal vent con-

nector length of 1--1/2 feet (18 inches) for each inch

of connector diameter as follows:

CONNECTOR

DIAMETER

(INCHES)

MAXIMUM HORIZONTALCONNECTOR LENGTH

(FEET)

3 4--1/2

4 6

5 7--1/2

6 9

7 10--1/2

Page 10: INSTALLATION INSTRUCTIONS G20 SERIES UNITS

3DJH ��

8-- If the commonvertical vent is offset, themaximum

common vent capacity listed in the common vent-

ing tables should be reduced by 20%, the equiva-

lent of two 90E elbows (0.80 x maximum common

vent capacity). The horizontal length of the offset

shall not exceed 1--1/2 feet for each inch of com-

mon vent diameter.

9-- The vent pipe shouldbe as short as possiblewith

the least number of elbows and angles to do the

job. The vent connector should be routed to the

vent utilizing the shortest possible route.

10-- A vent connector shall be supported without any

dips or sags and shall slope aminimumof 1/4� per

linear foot of connector, back towards the ap-

pliance.

11 Vent connectors shall be firmly attached to furnace

flue collars by sheet metal screws or other ap-

proved means, except vent connectors of listed

Type �B� vent material which shall be assembled

in accordance with the manufacturer�s instruc-

tions. Joints between sections of single wall con-

nector piping shall be fastened by sheet metal

screws or other approved means.

12-- When the vent connector used for Category I ap-

pliances must be located in or pass through a

crawl space or other areas whichmaybe cold, that

portion of the vent connector shall be listed

double--wall Type B vent material or material hav-

ing equivalent insulation qualities.

13-- All venting pipe passing through floors, walls, and

ceilingsmust be installed with the listed clearance

to combustible materials and be fire stopped ac-

cording to local codes. In absence of local codes,

refer to NFGC (Z223.1).

14-- No portion of the venting system can extend into, or

pass through any circulation air duct or plenum.

15-- Vent connectors serving Category I appliances

shall not be connected to any portion of mechani-

cal draft systems operation under positive pres-

sure such as Category III or IV venting systems.

16-- If vent connectors are combined prior to entering

the common vent, themaximum common vent ca-

pacity listed in the common venting tables must be

reduced by 10%, the equivalent of one 90E elbow

(0.90 x maximum common vent capacity).

17--Common vent diametermust always be at least as

large as the largest vent connector diameter.

18-- In no case, shall the vent connector be upsized

more than two consecutive table size diameters

over the size of the drafthood outlet or flue collar

outlet.

19-- A manual damper, barometric draft regulator or

flue restrictor must not be installed between fur-

nace and any chimney.

20-- When connecting this appliance to an existing dedi-

cated or common venting system, the venting sys-

tem, must be inspected for signs of corrosion, and

general condition. The sizing of the vent system

must be reviewed and conform to these instructions

and the provided venting tables in the U.S.A., and

the appropriate venting tables in the standards of

CAN/CGA--B149.1 and B149.2 of the National Gas

and Propane Installation Code in Canada. If the ex-

isting system is in conflict with these requirements,

the venting system must be resized.

TABLE 2

CAPACITY OF TYPE B DOUBLE--WALL VENTS WITH

TYPE B DOUBLE--WALL CONNECTORS

SERVING A SINGLE CATEGORY I APPLIANCE

Height Lateral

Vent and Connector Diameter -- D(inches)

HeightH

(f )

LateralL

(f )

4 Inch 5 Inch 6 InchH(feet)

L(feet) MAXIMUM Appliance Input Rating in

Thousands of Btu Per Hour

0 86 141 205

62 67 105 157

64 64 103 153

6 61 100 149

0 94 155 235

82 75 120 180

85 71 115 173

8 66 109 165

0 100 166 255

102 81 129 195

105 77 124 188

10 70 115 175

0 112 187 285

2 93 150 225

15 5 87 142 2175

10 82 135 208

15 76 128 198

0 119 202 307

2 100 166 249

205 96 160 241

2010 89 150 228

15 84 142 217

20 78 134 206

0 128 220 336

2 112 185 280

5 108 176 273

30 10 102 171 261

15 96 163 249

20 90 154 237

30 NR NR 219

NOTE: Single appliance venting configurations with zero lateral lengthsare assumed to have no elbows in the vent system. For all other vent con-figurations, the vent system is assumed to have two90E elbows. For eachadditional 90E elbow or equivalent (for example two 45E elbows equalone 90E elbow) beyond two, the maximum capacity listed in the ventingtable should be reduced by 10 percent (0.90 x maximum listed capacity).

Page 11: INSTALLATION INSTRUCTIONS G20 SERIES UNITS

3DJH ��

TABLE 3CAPACITY OF TYPE B DOUBLE--WALL VENTS WITH

SINGLE--WALL METAL CONNECTORSSERVING A SINGLE CATEGORY I APPLIANCE

Height Lateral

Vent and Connector Diameter -- D(inches)

HeightH

(f )

LateralL

(f )

4 Inch 5 Inch 6 InchH(feet)

L(feet) MAXIMUM Appliance Input Rating in

Thousands of Btu Per Hour

0 85 140 204

6

2 66 104 156

64 63 102 152

6 60 99 148

0 93 154 234

8

2 75 119 179

85 69 114 171

8 64 107 163

0 99 165 254

10

2 80 128 194

105 76 122 186

10 68 112 171

0 111 186 283

2 93 149 224

15 5 86 140 217

10 79 131 203

15 72 124 192

0 118 201 306

2 99 165 248

20

5 94 158 239

2010 86 146 224

15 80 136 210

20 NR 126 196

0 127 219 334

2 111 183 279

5 106 173 271

30 10 98 168 25730

15 NR 157 242

20 NR NR 228

30 NR NR NR

NOTE: Single appliance venting configurations with zero lateral lengthsare assumed to have no elbows in the vent system. For all other vent con-figurations, the vent system is assumed to have two 90E elbows. For eachadditional 90E elbow or equivalent (for example two 45E elbows equalone 90E elbow) beyond two, the maximum capacity listed in the ventingtable should be reduced by 10 percent (0.90 x maximum listed capacity).

TABLE 4CAPACITY OF TYPE B DOUBLE--WALL VENTS WITH

TYPE B DOUBLE--WALL CONNECTORSSERVING TWO OR MORE CATEGORY I APPLIANCES

VENT CONNECTOR CAPACITY

VentH i ht

ConnectorRi

Vent and Connector Diameter -- D(inches)

HeightH

RiseR

4 Inch 5 Inch 6 InchH

(feet)R

(feet) MAXIMUM Appliance Input Rating inThousands of Btu Per Hour

1 46 72 104

6 2 55 86 1246

3 62 96 139

1 48 76 109

8 2 57 90 129

3 64 101 145

1 50 78 113

10 2 59 93 134

3 67 104 150

1 53 83 120

15 2 63 99 1425

3 71 111 160

1 56 87 125

20 2 66 104 1490

3 74 116 168

1 59 93 134

30 2 70 110 15830

3 79 124 178

TABLE 5CAPACITY OF TYPE B DOUBLE--WALL VENTS WITH

TYPE B DOUBLE--WALL CONNECTORSSERVING TWO OR MORE CATEGORY I APPLIANCES

COMMON VENT CAPACITY

Common Vent Diameter -- D (inches)

VentHeig

4 Inch 5 Inch 6 Inch 7 InchHeight

Appliance Input Rating in Thousands of Btu Per HourhtH

(feet)

NAT+

NAT

FAN+

NAT

NAT+

NAT

FAN+

NAT

NAT+

NAT

FAN+

NAT

NAT+

NAT

FAN+

NAT

6 65 81 103 116 147 161 200 248

8 73 90 114 129 163 178 223 275

10 79 97 124 141 178 194 242 299

15 91 112 144 164 206 228 280 352

20 102 123 160 183 229 255 310 394

30 118 138 185 210 266 297 360 459

Page 12: INSTALLATION INSTRUCTIONS G20 SERIES UNITS

3DJH ��

TABLE 6CAPACITY OF TYPE B DOUBLE--WALL VENT WITH

SINGLE--WALL METAL CONNECTORSSERVING TWO OR MORE CATEGORY I APPLIANCES

VENT CONNECTOR CAPACITY

VentH i ht

ConnectorRi

Vent and Connector Diameter -- D(inches)

HeightH

RiseR

4 Inch 5 Inch 6 InchH

(feet)R

(feet) MAXIMUM Appliance Input Rating inThousands of Btu Per Hour

1 46 71 102

6 2 55 85 1236

3 62 95 138

1 52 81 116

15 2 62 97 138

3 70 109 157

1 57 89 129

30 2 67 106 152

3 76 120 172

TABLE 7CAPACITY OF TYPE B DOUBLE--WALL VENTS WITH

SINGLE--WALL METAL CONNECTORSSERVING TWO OR MORE CATEGORY I APPLIANCES

COMMON VENT CAPACITY

Common Vent Diameter -- D (inches)

VentHeig

4 Inch 5 Inch 6 Inch 7 InchHeight

Appliance Input Rating in Thousands of Btu Per HourhtH

(feet)

NAT+

NAT

FAN+

NAT

NAT+

NAT

FAN+

NAT

NAT+

NAT

FAN+

NAT

NAT+

NAT

FAN+

NAT

6 64 78 100 113 144 158 196 244

8 71 87 112 126 159 173 218 269

10 76 94 120 137 174 189 236 292

15 88 108 140 159 200 221 274 343

20 98 118 155 177 223 247 302 383

30 113 132 179 202 257 286 349 446

Removal of Unit from Common Venting System

In the event that an existing furnace is removed from a

venting system commonly run with separate gas ap-

pliances, the venting system is likely to be too large to

properly vent the remaining attached appliances. The

following test should be conducted while each ap-

pliance in operation and theother appliances not in op-

eration remain connected to the common venting sys-

tem. If the venting system has been installed

improperly, the system must be corrected as outlined

in the previous section.

1-- Seal any unused openings in the common venting

system.

2-- Visually inspect the venting system for proper size

and horizontal pitch and determine there is no

blockage or restriction, leakage, corrosion and

other deficiencies which could cause an unsafe

condition.

3-- Insofar as is practical, close all building doors and

windows andall doors between the space inwhich

the appliances remaining connected to the com-

mon venting system are located and other spaces

of the building. Turn on clothes dryers and any ap-

pliances not connected to the common venting

system. Turn on any exhaust fans, such as range

hoods and bathroom exhausts, so they will oper-

ate at maximum speed. Do not operate a summer

exhaust fan. Close fireplace dampers.

4-- Follow the lighting instruction. Place the appliance

being inspected in operation. Adjust thermostat

so appliance will operate continuously.

5-- Test for spillage at the draft hood relief opening af-

ter 5 minutes of main burner operation. Use the

flame of a match or candle, or smoke from a ciga-

rette, cigar or pipe.

6-- After it has been determined that each appliance

remaining connected to the common venting sys-

temproperly ventswhen testedas outlined above,

return doors, windows, exhaust fans, fireplace

dampers and any other gas--burning appliance to

their previous condition of use.

7-- If improper venting is observed during any of the

above tests, the common venting systemmust be

corrected. The common venting system should be

re--sized to approach the minimum size as deter-

mined by using the appropriate tables in appendix

G in the current standards of theNational FuelGas

Code ANSI Z223--1 in the U.S.A., and the appropri-

ate Category 1 Natural Gas and Propane ap-

pliances venting sizing tables in the current stan-

dards of theCAN/CGA--B149.1 and .2 in theNatural

Gas and Propane Installation Code in Canada.

Page 13: INSTALLATION INSTRUCTIONS G20 SERIES UNITS

3DJH ��

+RUL]RQWDO 9HQWLQJ

6,'( :$// 9(17,1* .,7 :,5,1*

&

/�

/����9$&

33&� ��

�237,21$/�

0

/� 01 7� 7� 7�

: 5 < *

:

*

5

<

�� 9$&7+(50267$7

7+(50267$7 &211(&7,2167(50,1$/ ,1 )851$&(

-81&7,21 %2;

5(/$<

&.� ��� &21752/ %2;

35(6685(6:,7&+

6:*32:(59(17(502725

$

%

� �

),*85( ��

7

),(/' ,167$//(' :,5,1*

)$&725< ,167$//(' :,5,1*

12

This furnace is design certified by the American Gas

Association for horizontal venting through an outside

wall only with the use of a Field Controls Company

Model #SWG--5L side wall venting kit available from

Lennox Dealer Service Center. No other Field brand

venting kit or any other manufacturer�s venting kit is

acceptable. Horizontal venting of this furnace without

the use of the above stated kit is prohibited. See figure

10 for field wiring of side wall horizontal venting kit.

When horizontally vented, minimum clearance for ter-

mination from electric meters, gas meters, regulators

and relief equipment is 4 ft. (1.2m).

At vent termination, care must be taken to maintain

protective coatings over buildingmaterials (prolonged

exposure to exhaust condensate can destroy protec-

tive coatings). It is recommended that the exhaust out-

let not be located within 6 ft. (1.8m) of a condensing

unit because the condensate can damage the painted

coating.

Page 14: INSTALLATION INSTRUCTIONS G20 SERIES UNITS

3DJH ��

*$6 3,3,1*

Gas Supply

1-- This unit is shipped standard for left side installa-

tion of gas piping. Simply connect gas supply to

piping assembly.

2-- A piping hole is also fabricated in the right side of

the unit for alternate piping arrangements.

3-- When connecting gas supply, factors such as

lengthof run, number of fittings and furnace rating

must be considered to avoid excessive pressure

drop. Table 8 lists recommendedpipe sizes for typ-

ical applications.

4-- Gas piping must not run in or through air ducts,

clothes chutes, chimneys or gas vents, dumbwait-

ers or elevator shafts.

5-- Piping should be sloped 1/4 inch per 15 feet (6mm

per 4.57m) upward toward the meter from the fur-

nace. The pipingmust be supported at proper inter-

vals, every 8 to 10 feet (2.44m to 3.05m), using suit-

able hangers or straps. A drip leg should be

installed in vertical pipe runs to the unit.

6-- In some localities, codes may require installation

of a manual main shut--off valve and union (fur-

nished by installer) external to the unit. Union

must be of the ground joint type.

,03257$17

&RPSRXQGV XVHG RQ WKUHDGHG MRLQWV RI JDV SLSLQJPXVW EH UHVLVWDQW WR WKH DFWLRQV RI OLTXLILHG SHWUR�OHXP JDVHV�

NOTE--In the case emergency shut--off is required, shut

offmainmanual gas valve and disconnectmain power

to unit. These devices should be properly labeled by

the installer.

NOTE--Installer must provide a 1/8� (3.2mm) N.P.T.

plugged tap in the field piping upstreamof the gas sup-

ply connection to the unit. Tap must be accessible for

test gauge connection. See figure 11.

),*85( ��

*5281'-2,1781,21

$8720$7,&*$6 9$/9(

�ZLWK PDQXDO VKXW� �RII YDOYH�

),(/'3529,'('

$1' ,167$//('

*5281'-2,17 81,21

/()7 6,'( 3,3,1*�67$1'$5'�

5,*+7 6,'( 3,3,1*�$/7(51$7(�

$8720$7,&*$6 9$/9(

�ZLWK PDQXDO VKXW� �RII YDOYH�

'5,3 /(*

'5,3 /(*

0$18$/0$,1 6+87� �2))

9$/9(�:LWK ���l ����PP� 1373OXJJHG 7DS 6KRZQ�

0$18$/0$,1 6+87� �2))

9$/9(�:LWK ���l ����PP� 137

3OXJJHG 7DS6KRZQ�

TABLE 8GAS PIPE CAPACITY -- FT3/HR (kL/HR)

Nominal Internal Length of Pipe--Feet(m)NominalIron Pipe Size--Inches(mm)

InternalDiameter

--Inches(mm)10

(3.048)20

(6.096)

30

(9.144)

40

(12.192)

50

(15.240)

60

(18.288)

70

(21.336)

80

(24.384)

90

(27.432)

100

(30.480)

1/4

(6.35)

.364

(9.246)

43

(1.13)

29

(.82)

24

(.68)

20

(.57)

18

(.51)

16

(.45)

15

(.42)

14

(.40)

13

(.37)

12

(.34)

3/8

(9.53)

.493

(12.522)

95

(2.69)

65

(1.84)

52

(1.47)

45

(1.27)

40

(1.13)

36

(1.02)

33

(.73)

31

(.88)

29

(.82)

27

(.76)

1/2

(12.7)

.622

(17.799)

175

(4.96)

120

(3.40)

97

(2.75)

82

(2.32)

73

(2.07)

66

(1.87)

61

(1.73)

57

(1.61)

53

(1.50)

50

(1.42)

3/4

(19.05)

.824

(20.930)

360

(10.19)

250

(7.08)

200

(5.66)

170

(4.81)

151

(4.28)

138

(3.91)

125

(3.54)

118

(3.34)

110

(3.11)

103

(2.92)

1

(25.4)

1.049

(26.645)

680

(919.25)

465

(13.17)

375

(10.62)

320

(9.06)

285

(8.07)

260

(7.36)

240

(6.80)

220

(6.23)

205

(5.80)

195

(5.52)

1--1/4

(31.75)

1.380

(35.052)

1400

(39.64)

950

(26.90)

770

(21.80)

660

(18.69)

580

(16.42)

530

(15.01)

490

(13.87)

460

(13.03)

430

(12.18)

400

(11.33)

1--1/2

(38.1)

1.610

(40.894)

2100

(59.46)

460

(41.34)

1180

(33.41)

990

(28.03)

900

(25.48)

810

(22.94)

750

(21.24)

690

(19.54)

650

(18.41)

620

(17.56)

2

(50.8)

2.067

(52.502)

3950

(111.85)

2750

(77.87)

2200

(62.30)

1900

(53.80)

1680

(47.57)

1520

(43.04)

1400

(39.64)

1300

(36.81)

1220

(34.55)

1150

(32.56)

2--1/2

(63.5)

2.469

(67.713)

6300

(178.39)

4350

(123.17)

3520

(99.67)

3000

(84.95

2650

(75.04)

2400

(67.96)

2250

(63.71)

2050

(58.05)

1950

(55.22)

1850

(52.38)

3

(76.2)

3.068

(77.927)

11000

(311.48)

7700

(218.03)

6250

(176.98)

5300

(150.07)

4750

(134.50)

4300

(121.76)

3900

(110.43)

3700

(104.77)

3450

(97.69)

3250

(92.03)

4

(101.6)

4.026

(102.260)

23000

(651.27)

15800

(447.39)

12800

(362.44)

10900

(308.64)

9700

(274.67)

8800

(249.18)

8100

(229.36)

7500

(212.37)

7200

(203.88)

6700

(189.72)

NOTE--Capacity given in cubic feet of gas per hour (kilo liters of gas per hour) and based on 0.60 specific gravity gas.

Page 15: INSTALLATION INSTRUCTIONS G20 SERIES UNITS

3DJH ��

Leak Check

After gas piping is completed, carefully check all piping

connections (factory and field) for gas leaks. Use a leak

detecting solution or other preferred means.

&$87,21

6RPH VRDSV XVHG IRU OHDN GHWHFWLRQ DUH FRUURVLYHWR FHUWDLQPHWDOV�&DUHIXOO\ ULQVHSLSLQJ WKRURXJKO\DIWHU OHDN WHVW KDV EHHQ FRPSOHWHG� 'R QRW XVHPDWFKHV� FDQGOHV� IODPH RU RWKHU VRXUFHV RI LJQL�WLRQ WR FKHFN IRU JDV OHDNV�

NOTE--In case emergency shutdown is required, shut

down main manual gas valve and disconnect main

power to unit. These devices should be properly la-

beled by the installer.

,03257$17

:KHQ WHVWLQJ SUHVVXUH RI JDV OLQHV� JDV YDOYHPXVWEH GLVFRQQHFWHG DQG LVRODWHG� 6HH ILJXUH ��� *DVYDOYHV FDQ EH GDPDJHG LI VXEMHFWHG WR PRUH WKDQ��� SVLJ ����� N3D��

),*85( ��

0$18$/ 0$,1 6+87� �2))

9$/9( :,// 127

+2/' 1250$/

7(67 35(6685(

&$3

)851$&(

,62/$7(*$6 9$/9(

The furnace must be isolated from the gas supply sys-

tem by closing its individual manual shut--off valve

during anypressure testingof thegas supply systemat

pressures equal to or less than 1/2 psig (3.48 kPa).

,03257$17

*��; VHULHV XQLWV �XQLWV HTXLSSHGZLWK IODPH URGV�DUH DSSURYHG IRU XVH ZLWK QDWXUDO JDV RQO\�

(/(&75,&$/

Refer to figure 13 for blower control board, figure 14 for

point to point field wiring and figure 15 for schematic

wiring diagrams and troubleshooting.

1-- Select fuse and wire size according to the blower

motor amps.

2-- Snapholeplugs areprovidedonboth sidesof cabi-

net to facilitate wiring.

3-- Install room thermostat according to instructions

provided with thermostat.

4-- Install a separate fused disconnect switch near the

unit so power can be turned off for servicing.

5-- Before connecting thermostat wiring to unit, re-

move screws holding the hinged section of the

control box. Swing the hinged section downward

to to ensure wires are proper length.

6-- Complete wiring connections to equipment using

wiringdiagramsprovidedwithunit and in figures 14,

15 and NO TAG. Use 18 gauge wire or larger for

thermostat connections.

7-- Electrically ground unit in accordance with local

codes or, in the absence of local codes, in accor-

dancewith the current National Electric Code (ANSI/

NFPA No. 70) and in Canada with the current Cana-

dian Electric Code part 1 (CSA standard C22.1).

127(�1RQ� �LQVXODWHG JURXQG ZLUHV PXVW EH

ZUDSSHG LQ HOHFWULFDO WDSH WR DYRLG GDPDJLQJ WKH

%&&� EORZHU FRQWURO FHQWHU�

8-- A 120 volt accessory terminal (ACC) is provided on

the BCC2 blower control center. Any accessory

ratedup to1ampcanbe connected to this terminal

and the neutral leg of the accessory can be at-

tached to any free 120 volt neutral terminal on the

BCC2 blower control center. The accessory termi-

nal is energized whenever the blower is in opera-

tion. See figure 13. A troubleshooting flowchart

for the BCC2blower control is located in figure 31.

9-- The continuous fan (CF) 120 volt terminal is used

with an optional continuous low fan kit that is

available from Lennox. The kit allows the furnace

blower to run continuously on low speed.

Page 16: INSTALLATION INSTRUCTIONS G20 SERIES UNITS

3DJH ��

),*85( ��

%&&� %/2:(5 &21752/ %2$5'

1(875$/7(50,1$/6

$&&(6625<7(50,1$/

7+(50267$7 7(50,1$/675,3 �'(7$&+$%/(�

%/2:(5 7,0($'-8670(17

-803(5

+($7,1*63((' 7$37(50,1$/

&22/,1*63((' 7$37(50,1$/

'800<7(50,1$/6

&217,18286 )$17(50,1$/

7R 5HPRYH 7HUPLQDO 6WULS�*UDVS (QGV RI %ORFN %HWZHHQ7KXPE DQG )RUHILQJHU� 3XVK

%ORFN 'RZQ DQG 2XW�

),*85( ��

< 5 :*

*: < &5

%&&� &21752/

&21752/ %2;

7+(50267$7

,*1,7,21

&21752/

*$6

9$/9(

'$03(5

'225

6:,7&+

)/$0(

52//287

6:,7&+

/,0,7

%/2&.('

9(17

6+872))

6:,7&+

%/$&.

:+,7(

72 &2035(6625

&217$&725

),(/' ,167$//(' /2: 92/7$*(

),(/' ,167$//(' /,1( 92/7$*(

7<3,&$/ *�� ),(/' :,5,1* ',$*5$0

/� 1

)86('',6&211(&76:,7&+

�)851,6+('%<,167$//(5�

*5281'

75$16)250(5

'225

,17(5/2&.

6:,7&+

Page 17: INSTALLATION INSTRUCTIONS G20 SERIES UNITS

3DJH ��

),*85( ��

7<3,&$/ *��( :,5,1* ',$*5$0

Page 18: INSTALLATION INSTRUCTIONS G20 SERIES UNITS

3DJH ��

81,7 67$57��83

FOR YOUR SAFETY READ BEFORE LIGHTING

:$51,1*

'R QRW XVH WKLV IXUQDFH LI DQ\ SDUW KDV EHHQ XQGHU�ZDWHU� ,PPHGLDWHO\ FDOO D TXDOLILHG VHUYLFH WHFKQL�FLDQ WR LQVSHFW WKH IXUQDFH DQG WR UHSODFH DQ\ SDUWRI WKH FRQWURO V\VWHP DQG DQ\ JDV FRQWURO ZKLFKKDV EHHQ XQGHU ZDWHU�

:$51,1*

,I RYHUKHDWLQJ RFFXUV RU LI JDV VXSSO\ IDLOV WR VKXWRII� VKXW RII WKH PDQXDO JDV YDOYH WR WKH DSSOLDQFHEHIRUH VKXWWLQJ RII HOHFWULFDO VXSSO\�

&$87,21

%HIRUH DWWHPSWLQJ WR SHUIRUP DQ\ VHUYLFH RU PDLQ�WHQDQFH� WXUQ WKH HOHFWULFDO SRZHU WR XQLW 2)) DWGLVFRQQHFW VZLWFK�

BEFORE LIGHTING smell all around the appliance area

for gas. Be sure to smell next to the floor because some

gas is heavier than air and will settle on the floor.

Use only your hand to push in or turn the gas control

knob or lever. Never use tools. If the knob or lever will

not push in or turn by hand, do not try to repair it, call a

qualified service technician. Force or attempted repair

may result in a fire or explosion.

To place G20 furnace into operation:

All G20 units are equipped with an intermittent pilot igni-

tion system. Do not attempt to manually light pilots on

these furnaces. Each time thermostat calls forheat, thepi-

lot will automatically light. The pilot does not burn when

there is no call for heat on units with electronic ignitions.

:$51,1*

,I \RXGRQRW IROORZ WKHVH LQVWUXFWLRQV H[DFWO\� D ILUHRU H[SORVLRQPD\ UHVXOW FDXVLQJ SURSHUW\ GDPDJH�SHUVRQDO LQMXU\ RU ORVV RI OLIH�

*DV 9DOYH 2SHUDWLRQ �)LJXUHV �� ���

1-- STOP! Read the safety information at the begin-

ning of this section.

2-- Set thermostat to lowest setting. See figure 16.

3-- Turn off all electrical power to appliance.

4-- This appliance is equipped with an ignition device

which automatically lights the pilot. Do not try to

light the pilot by hand.

7+(50267$76

),*85( ��

5-- Remove control access panel.

6-- On Honeywell VR8204 gas valves, turn knob on

gas valve clockwise to OFF. Units with Robert-

shaw 7200 gas valve, depress lever and move to

OFF position. Do not force. See figure 18.

21

2))

),*85( ��

HONEYWELL VR8204 SERIES GAS VALVE

*$6 9$/9( 6+2:1 ,1 2)) 326,7,21

*$6 9$/9(

6(/(&725

$50

,1 2))

326,7,21

52%(576+$: ���� *$6 9$/9(

),*85( ��

7-- Wait five (5) minutes to clear out any gas. If you

then smell gas, STOP! Immediately call your gas

supplier from a neighbor�s phone. Follow the gas

supplier�s instructions. If you do not smell gas go

to next step.

8-- On Honeywell VR8204 gas valves, turn knob on

gas valve counterclockwise to ON. Units with

Robertshaw 7200 gas valve, depress lever and

move to ON position. Do not force.

9-- Replace control access panel.

10-- Turn on all electrical power to unit.

Page 19: INSTALLATION INSTRUCTIONS G20 SERIES UNITS

3DJH ��

11-- Set thermostat to desired setting.

NOTE--When unit is initially started, steps 1 through 11

may need to be repeated to purge air from pilot line.

12-- If the appliance still will not operate, follow the

instructions �To Turn Off Gas To Unit� and call

your service technician or gas supplier.

7R 7XUQ 2II *DV 7R 8QLW

1-- Set thermostat to lowest setting.

2-- Turnoff all electrical power tounit if service is to be

performed.

3-- Remove control access panel.

4-- On Honeywell VR8204 gas valves, turn knob on gas

valve clockwise to OFF. Units with Robertshaw

7200 gas valve, depress lever andmove toOFFposi-

tion. Do not force.

5-- Replace control access panel.

+,*+ $/7,78'( ,1)250$7,21

G20 series units are certified for installations from 0 to

4000 feet (0 to 1219m) above sea level without modifi-

cation. For installations from 4000 feet to 7500 feet

(1219m to 2286m) above sea level, a high altitude kit

(44H56) must be installed. The kit contains special flue

baffles used to replace factory--installed baffles. No

derate is required.

*$6 35(6685( $'-8670(17

Gas Flow

To check for proper gas flow to combustion chamber, de-

termineBtu input from appliance rating plate. Divide this

input rating by theBtuper cubic foot of available gas. Re-

sult is the required number of cubic ft. (cubic meter) per

hour. Determine the flow of gas through gas meter for

twominutes andmultiply by 30 to get the hourly flow of

gas to burner.

Gas Pressure

1-- Check gas line pressure with unit firing at maxi-

mum rate. A minimum of 4.5� w.c. (1.12kPa) for

natural gas or 10.5� w.c. (2.61kPa) for LP/propane

gas should be maintained.

2-- After linepressurehasbeencheckedandadjusted,

check manifold pressure. Correct manifold pres-

sure for LP/propane gas is 9.5� w.c. (2.36kPa) No

adjustment is needed inhigh altitude applications.

A natural gas to LP/propane gas changeover kit is

required to convert unit. Refer to the installation

instructions supplied with changeover kit for con-

version procedure.

Correct manifold pressure for natural gas is 3.5�

w.c. (.87kPa). No adjustment is needed in high alti-

tude applications. See figures 19 and 20 for man-

ifold pressure adjustment screw location.

52%(576+$: ���� *$6 9$/9(

5(*8/$725 $'-8670(17 6&5(: /2&$7,21

),*85( ��

5(*8/$725&29(5 6&5(: $'-867,1*

6&5(:

,1/(735(6685(

7$3

,1/(735(6685(

7$3

+21(<:(// *$6 9$/9(

5(*8/$725 $'-8670(17 6&5(: /2&$7,21

&$3 6&5(:�%ODFN�

$'-867,1* 6&5(:�:KLWH�

*$6 ,1/(7

35(6685( 5(*8/$725

),*85( ��

Page 20: INSTALLATION INSTRUCTIONS G20 SERIES UNITS

3DJH ��

27+(5 81,7 $'-8670(176

Limit Control

Limit Control--Factory set: No adjustment necessary.

Fan Control

The fan on time of 45 seconds is not adjustable. Fan off

time (time that the blower operates after the heat de-

mand has been satisfied) can be adjusted by moving

the jumper on the BCC2blower control center. The unit

is shipped with a factory fan off setting of 90 seconds.

Fan off timewill affect comfort and is adjustable to sat-

isfy individual applications. See figure 21.

��

���

��� ���

��

���

���

���

��

���

��� ���

��

���

��� ���

��

���

��� ���

-803(5

-803(5

-803(5

-803(5

12 -803(5

�� 6(&21' )$12)) 7,0(

��� 6(&21' )$12)) 7,0(

��� 6(&21' )$12)) 7,0(

��� 6(&21' )$12)) 7,0(

��� 6(&21' )$12)) 7,0(

),*85( ��

)$1 2)) 7,0( $'-8670(17

Temperature Rise

Check temperature rise and, if necessary, adjust blow-

er speed to maintain temperature rise within range

shown on unit rating plate.

Thermostat Adjustment

Set thermostat heat anticipation setting for G20 units

at .10 ampsor at the lowest setting availablebutnot be-

low .10 amps. An isolation relay is built into the BCC2

blower control board to enhance the compatibility of

the thermostat to the gas control.

Electrical

1-- Check all wiring for loose connections.

2-- Check for correct voltage at unit (unit operating).

3-- Check amp--draw on blower motor.

Motor Nameplate__________Actual__________

Blower Speeds

Blower speed selection is accomplished by changing

the taps at the harness connector at the blower motor.

See figure 22.

Refer to speed selection chart on unit wiring diagram.

NOTE--CFM readings are taken external to unit with a

dry evaporator coil and without accessories.

),*85( ��

%/2:(5 63((' 7$3 6(/(&7,21

+$51(66

&211(&725

'(35(66 7$% 72 5(/($6(

:,5( &211(&725� 6(/(&7

&211(&725 /2&$7,21 )25

1(: 63(('� ,16(57 :,5( 81�

7,/ ,7 &/,&.6�

Flue and Chimney

1-- Check flue pipe, chimney and all connections for

tightness and to make sure there is no blockage.

2-- Check unit for proper draft.

Failure to Operate

If unit fails to operate check the following:

1-- Is thermostat calling for heat?

2-- Is main disconnect switch closed?

3-- Is there a blown fuse?

4-- Is filter dirty or plugged? Dirty or plugged filters

will cause unit to go off on limit control.

5-- Is gas turned on at meter?

6-- Is manual main shut--off valve open?

7-- Is internal manual shut--off valve open?

After items 1 through 7 have been checked and unit still

will not start, manually reset vent safety shut--off switch

located at the right sideof draft hood. If unit operation re-

sumes and then cuts out again, inspect furnace vent sys-

tem for proper sizing and installation. Also, check for

vent blockage and for proper draft. If unit still does not

start, reset roll--out switch on burner box. See figure 2. If

unit starts and cuts out, check heat section for blockage.

Pilot and Burner Flame

After the G20 unit has been installed and wired, the pi-

lot flame should be periodically checked and adjusted,

if necessary, to insure proper unit operation. Use the

following procedure to adjust the pilot flame.

Pilot Flame Adjustment

1-- Turn off power to the unit.

2-- Disconnect wire from MV terminal on the gasvalve.

Page 21: INSTALLATION INSTRUCTIONS G20 SERIES UNITS

3DJH ��

3-- On Honeywell VR8204 gas valves, turn knob ongas valve counterclockwise toON. Units with Rob-ertshaw7200gas valve, depress lever andmove toON position. Do not force.

4-- Restore power to unit.

5-- Set thermostat to call for heat.

At this point the pilot valve portion of the gas valve will

be energized after a call for heat is initiated. Pilotwill then

light. Examine the pilot flame to determine if it is a soft,

stable flame that surrounds the flame sensor. See figure

23. If this is not the case, the pilot needs adjustment.

3,/27 )/$0(�6LGH 9LHZ�

%851(5

),*85( ��

)/$0( 6(1625

6-- Identify the gas valve being used and locate the pi-

lot adjustment screw. On some gas valves the ac-

tual adjustment screw is under a cap. See figures

24, and 25 for pilot adjustment screw locations.

21

2))

),*85( ��

HONEYWELL VR8204 SERIES GAS VALVE

3,/27 $'-8670(17 6&5(:�81'(5 &$3�

),*85( ��

52%(576+$: ���� *$6 9$/9(

3,/27 $'-8670(17 6&5(:

3,/27

$'-�

7-- Turn thepilot adjustment screwuntil the pilot flameis soft and stably surrounds the flame sensor.

8-- Take a microamp reading of the flame signal com-ing from the flame sensor. The normal range is0.80 to 1.20 microamps with a minimum of 0.70microamps.

9-- After correct pilot flame has been obtained, adjustthermostat to stop a call for heat.

10-- Turn off power to unit.

11-- Reconnect MV wire to MV terminal on gas valve.

12-- Restore power to unit and assure normal operation.

Burner Flame

Start burner and allow to operate for a few minutes to

establish normal burning conditions. Check burner

flame by observation. Flame should be predominantly

blue in color, strong in appearance and should rise di-

rectly from the burner ports in the heat exchanger.

Check to see that flame is burning from all continuous

ribbon ports and that flame does not impinge on the

sides of the heat exchanger.

%851(5 )/$0(

),*85( ��

127(� �9,(: %851(5 )/$0( 7+528*+'$03(5 23(1,1* �1RW 6KRZQ�

6(59,&(

:$51,1*

'LVFRQQHFW SRZHU EHIRUH VHUYLFLQJ XQLW�

&$87,21

/DEHO DOO ZLUHV SULRU WR GLVFRQQHFWLRQ ZKHQ VHUYLF�LQJ FRQWUROV� :LULQJ HUURUV FDQ FDXVH LPSURSHUDQG GDQJHURXV RSHUDWLRQ� 9HULI\ SURSHU RSHUDWLRQDIWHU VHUYLFLQJ�

At the beginning of each heating season, the system

should be checked as follows:

Blower

Check and clean blower wheel for any debris. Blower

motor is prelubricated for extended bearing life. No

further lubrication is needed.

Page 22: INSTALLATION INSTRUCTIONS G20 SERIES UNITS

3DJH ��

Filters

1-- Filters should be inspected monthly and must be

cleaned or replaced when dirty to assure proper

furnace operation.

2-- Reusable foam filters supplied with G20 can be

washed with water and mild detergent. When dry,

they should be sprayed with filter handicoater prior

to reinstallation. Filter handicoater is RP Products

coating no. 481 and is available as Lennox part no.

P--8--5069. If replacement is necessary, refer to

table 9.

7$%/( �),/7(5 6,=( $1' 3$57 180%(5

MODEL NUMBERSIDE RETURNInches (mm)

BOTTOM RETURNInches (mm)

4�� ���� 4�� ����4�� ���� 4�� ����

�� ; �� ; ����� ; ��� ; ���

3� ��� �����

�� ; �� ; ����� ; ��� ; ���

3� ��� �����

4�� ���� 4���� ������ ; �� ; �

���� ; ��� ; ���3� ��� �����

�� ; �� ; ����� ; ��� ; ���

��+��

4���� �����4���� ����� 4���� ����

�� ; �� ; ����� ; ��� ; ���

3� ��� �����

�� ; �� ; ����� ; ��� ; ���

��+��

4���� ������ ; �� ; �

���� ; ��� ; ���3� ��� �����

�� ; �� ; ����� ; ���� ; ���

��+��

Flue and Chimney

Check flue pipe, chimney and all connections for tight-

ness and to make sure there is no blockage.

Electrical Check

1-- Check all wiring for loose connections.

2-- Check for correct voltage at unit (unit operating).

3-- Check amp--draw on blower motor.

Motor Nameplate__________Actual__________

Cleaning Heat Exchanger and Burners

NOTE--Usepapers or protective covering in frontof fur-

nace while cleaning furnace.

To clean heat exchanger:

1-- Turn off both electrical and gas power supplies to

furnace. Refer to figures 1 and 2 during disassem-

bly and reassembly procedures.

2-- Remove burner and upper access panel, flue pipe

and draft hood.

3-- Disconnect supply gas piping.

4-- Remove burner box top by removing four holding

screws.

5-- Remove two screws each from the left and right

patch plates. Remove patch plates, damper prove

switch cover and damper.

6-- Remove screws holding gasmanifold in place and

pull burners from heat exchanger.

7-- Remove baffles inside top opening of heat exchang-

er by twisting tabs to align with slots in baffles.

8-- Insert a 24� (600 mm) steel rod that has a 20�

(508mm) length of chain attached to one end into

top opening of heat exchanger. See figure 27.

&/($1,1* +($7 (;&+$1*(5

&RQQHFW FKDLQ WR URG DQG GURSFKDLQ GRZQ WKURXJK WRS RI KHDW H[�FKDQJHU� &RQQHFW DW ERWWRP WRDQRWKHU URG� 0RYH URGV XS DQGGRZQ� EDFN DQG IRUWK WR FOHDQ KHDWH[FKDQJHU�

),*85( ��

9-- Shake rod to drop chain through the clamshell into

burner cavity in bottom of heat exchanger.

10-- Attachbottomof chain to another 24� (600mm) rod.

11-- Push and pull the rods back and forth and up and

down with a vigorous motion. The chain will dis-

lodge the soot and scale deposits inside the heat

exchanger. Repeat for each clamshell.

12-- With a shop vacuum or rags, clean out soot and

scale deposits from bottom of heat exchanger.

7R FOHDQ EXUQHUV�

NOTE--FOR UNITS WITH FLAME RODS, remove two

springs and withdraw rods from back of burner. Clean

flame rods with wire brush. Continue with items 13

through 15 below and reinstall flame rods and springs.

13-- Clean top of burner ports with a wire brush.

14-- Clean burner ports by inserting a cleaning tool

(made from a piece of sheet metal cut to fit the

burner ports) andwork in andout of eachport. See

figure 29.

&/($1,1* 723

),*85( ��

&/($1,1* 32576

),*85( ��

&/($1,1* ,16,'(

),*85( ��

Page 23: INSTALLATION INSTRUCTIONS G20 SERIES UNITS

3DJH ��

15-- Clean inside of each burner with a bottle cleaning

brush. See figure 30.

16--Replaceburnersmaking sure to fully engage in rear

receiving slot in heat exchanger. Resecure gas

manifold and supply piping.

17--Reinstall baffles inside top opening of heat ex-

changer twisting tabs to secure baffles.

18-- Resecure damper assembly, damper prove switch

cover and burner box top. Carefully open damper

by hand to ensure that the damper spring closes

damper correctly and that the damper prove

switch is engaged when damper is open.

&$87,21

8VH H[WUHPH FDUH ZKHQ RSHQLQJ GDPSHU GRRU WRSUHYHQW SHUPDQHQW GDPDJH WR WKH GDPSHU PRWRU�

19-- Before replacing draft hood, flue pipe and access

panels, inspect draft hood gasket. Replace gasket

if necessary.

20-- Carefully check all piping connections (factory and

field) for gas leaks. Use a leak detecting solution or

other preferred means.

&$87,21

6RPH VRDSV XVHG IRU OHDN GHWHFWLRQ DUH FRUURVLYHWR FHUWDLQPHWDOV�&DUHIXOO\ ULQVHSLSLQJ WKRURXJKO\DIWHU OHDN WHVW KDV EHHQ FRPSOHWHG� 'R QRW XVHPDWFKHV� FDQGOHV� IODPH RU RWKHU VRXUFHV RI LJQL�WLRQ WR FKHFN IRU JDV OHDNV�

21-- Turn on gas and electrical supply.

5(3$,5 3$576 /,67

The following repair parts are available through inde-

pendent Lennox dealers.When ordering parts, include

the complete furnace model number listed on the

A.G.A. or C.G.A. ratingplate ---- Example:G20Q5/6--150.

CABINET PARTS

Upper access panel

Blower panel

Top strip

Cabinet cap

CONTROL PANEL PARTS

Transformer

Blower Control Center (BCC2)

BLOWER PARTS

Blower wheel

Motor

Motor mounting frame

Blower housing cut--off plate

HEATING PARTS

Heat exchanger

Gas manifold

Draft hood

Gas valve

Main burners

Ignition control

Main burner orifices

Ignition cable

Pilot burner

Igniter

Pilot/electrode assembly

Damper switch

Limit control

Couplings

Flame roll--out switch

Damper spring

Blocked vent shut--off switch

9 pin plug

Damper motor

Grommets

*�� 67$57��83 $1' 3(5)250$1&( &+(&. /,67

)LOWHU &OHDQ 6HFXUH"

6XSSO\ 9ROWDJH

(OHFWULFDO &RQQHFWLRQV 7LJKW"

67$57� �83 $1' 3(5)250$1&( &+(&. /,67

-RE 1DPH

-RE /RFDWLRQ

,QVWDOOHU

8QLW 0RGHO 1R�

)XUQDFH %WX ,QSXW

/LQH 3UHVVXUH

-RE 1R�

&LW\

&LW\

6HULDO 1R�

'DWH

6WDWH

6HUYLFH7HFKQLFLDQ

$LU 6KXWWHUV 3URSHUO\ $GMXVWHG �,I ,QVWDOOHG�"

)OXH &RQQHFWLRQV 7LJKW"

+($7,1* 6(&7,21

7+(50267$7

&DOLEUDWHG" +HDW $QWLFLSDWRU 3URSHUO\ 6HW" /HYHO"5HJXODWRU 3UHVVXUH

)XHO 7\SH� 1DWXUDO *DV" /3�3URSDQH *DV"

%ORZHU 0RWRU $PSV

%ORZHU 0RWRU +�3�

%ORZHU 0RWRU /XEULFDWLRQ 2�.�"

*DV 3LSLQJ &RQQHFWLRQV 7LJKW /HDN� �7HVWHG"

3URSHU 'UDIW"

9HQW &OHDU"

6WDWH

7HPSHUDWXUH 5LVH)DQ &RQWURO 2II 6HWWLQJ

)DQ &RQWURO 6HWWLQJ ��� 6HFRQGV )L[HG 2Q�

Z�F�� 1DW�� Z�F�� /3�3URSDQH

Page 24: INSTALLATION INSTRUCTIONS G20 SERIES UNITS

3DJH ��

&+(&.��� �81,7 32:(5�� �,17(5/2&. 6:,7&+�� �75$16)250(5�� �/,0,7 6:,7&+

67$57

,6��9$& $&5266

5 &"

<(6

-803(5 $&52666&5(:6 5 *

<(6

'2(6 81,723(5$7("

12

12

,6%/2:(5

5811,1* 21 +,*+63(('"

12,6

���9$& $&52661 $"

5(3/$&(%&&�

12<(6

<(6

&+(&. %/2:(5:,5,1* $1'%/2:(5

,6���9$& $&5266

1 $&&"

125(3/$&(%&&�

<(6

-803(5 $&52665 :

�5(029( 5 * -803(5�

,6'$03(5 02725

21"

12

5(3/$&(%&&�

12 ,6���9$& $&5266

1 &$%"

&+(&.'$03(5 02725:,5,1* $1'

'$03(5 02725

<(6

<(6 ,681,7 /,7"

12

&+(&.��� �'$03(5 02725�� �,*1,7,21 &21752/�� �*$6 9$/9(�� �,*1,725�� �/,0,7 6:,7&+(6�� �3529( 6:,7&+<(6

,6 %/2:(55811,1* 21 /2:63(('� �� 6(&�

$)7(5 )851$&( /,*+76"

12,6

���9$& $&52661 +"

<(6

,6��9$& $&5266

& 9"

5(3/$&(%&&�

12

12

&+(&.:,5,1*

<(6,6���9$& $&5266

1 $&&"

<(6

5(029(5 :

-803(5

$)7(57+( 6(/(&7('7,0(� '2(6 7+(%/2:(5 7851

2))"

<(6 12

<(6

5(3/$&(%&&�

(1' 2) 7(67

%&&�

7528%/(6+227,1*

)/2:&+$57

12

5(3/$&(%&&�

&+(&. %/2:(5:,5,1* $1'%/2:(5

),*85( ��

&+(&. )86(�5(3/$&( ,) 1(('('�


Recommended