+ All Categories
Home > Documents > INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS AP ... · STEEL OIL-FIRED BOILER For service or...

INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS AP ... · STEEL OIL-FIRED BOILER For service or...

Date post: 02-Aug-2020
Category:
Upload: others
View: 0 times
Download: 0 times
Share this document with a friend
44
INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS AP-U "rMSERIES STEEL OIL-FIRED BOILER For service or repairs to boiler, call your heating contractor. When seeking information on boiler, provide Boiler Model Number and Serial Number as shown on Rating Label. Boiler Model Number Boiler Serial Number Installation Date AP U Heating Contractor Phone Number Address 8147101 R7-1/10 ® RESIDENTIAL HEATING BOILERS Price - $3.00
Transcript
Page 1: INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS AP ... · STEEL OIL-FIRED BOILER For service or repairs to boiler, call your heating contractor. When seeking information on boiler,

INSTALLATION, OPERATINGAND SERVICE INSTRUCTIONS

AP-U "rMSERIES

STEEL OIL-FIRED BOILER

For service or repairs to boiler, call your heating contractor. When seeking information onboiler, provide Boiler Model Number and Serial Number as shown on Rating Label.

Boiler Model Number Boiler Serial Number Installation Date

AP U

Heating Contractor Phone Number

Address

8147101 R7-1/10

®

RESIDENTIAL HEATING BOILERS

Price - $3.00

Page 2: INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS AP ... · STEEL OIL-FIRED BOILER For service or repairs to boiler, call your heating contractor. When seeking information on boiler,

IMPORTANT INFORMATION - READ CAREFULLY

All boilers must be installed in accordance with National, State and Local Plumbing, Heating and

Electrical Codes and the regulations of the serving utilities. These Codes and Regulations may differ

from this instruction manual. Authorities having jurisdiction should be consulted before installationsare made.

In all cases, reference should be made to the following Standards:

All wiring on boilers shall be made in accordance with the National Electrical Code and/or Local

Regulations.

A. Current Edition of American National Standard ANSI/NFPA 31, "Installation of Oil Burning

Equipment", for recommended installation practices.

B. Current Edition of American National Standard ANSI/NFPA 211, "Chimneys, Fireplaces, Vents,

and Solid Fuel Burning Appliances", For Venting requirements.

C. Current Edition of American Society of Mechanical Engineers ASME CSD-1, "Controls and Safety

Devices for Automatically Fired Boilers", for assembly and operations of controls and safetydevices.

The following terms are used throughout this manual to bring attention to the presence of hazards of various risk levels,or to important information concerning product life.

Indicates an imminently hazardous situationwhich, if not avoided, will result in death, seriousinjury or substantial property damage,

Indicates a potentially hazardous situation which,if not avoided, may result in moderate or minorinjury or property damage,

Indicates a potentially hazardous situation which,if not avoided, could result in death, serious injuryor substantial property damage,

Indicates special instructions on installation,operation, or maintenance which are importantbut not related to personal injury hazards,

This boiler has a limited warranty, a copy of which is printed on the back of this manual.

It is the responsibility of the installing contractor to see that all controls are correctly installed and areoperating properly when the installation is complete. The warranty for this boiler is valid only if the boiler hasbeen installed, maintained and operated in accordance with these instructions.

2

Page 3: INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS AP ... · STEEL OIL-FIRED BOILER For service or repairs to boiler, call your heating contractor. When seeking information on boiler,

DO NOT store or use gasoline or other flammable vapors or liquids in the vicinity of this or any otherappliance.

Improper installation, adjustment, alteration, service or maintenance can cause property damage, personalinjury or loss of life. Failure to follow all instructions in the proper order can cause personal injury ordeath. Read and understand all instructions, including all those contained in component manufacturersmanuals which are provided with the appliance before installing, starting-up, operating, maintaining orservicing this appliance. Keep this manual and literature in legible condition and posted near appliancefor reference by owner and service technician.

This boiler requires regular maintenance and service to operate safely. Follow the instructions containedin this manual. Installation, maintenance, and service must be performed only by an experienced, skilledand knowledgeable installer or service agency. All heating systems should be designed by competentcontractors and only persons knowledgeable in the layout and installation of hydronic heating systemsshould attempt installation of any boiler. It is the responsibility of the installing contractor to see that allcontrols are correctly installed and are operating properly when the installation is completed. Installationis not complete unless a pressure relief valve is installed into the tapping located on top of appliance- See Section III of this manual for details.

This boiler is not suitable for installation on combustible flooring, unless installed with a combustiblefloor shield (available at extra cost).

Do not install boiler on carpeting.

When boiler is installed on concrete which is over a material that is subject to melting (PVC, PEX radianttubing, etc.) the combustible floor shield must be used.

A concrete pad is not sufficient to protect combustible flooring.

Do not tamper with or alter the boiler or controls. Retain your contractor or a competent serviceman toassure that the unit is properly adjusted and maintained.

Have Firetubes cleaned at least once a year - preferably at the start of the heating season to remove sootand scale. The inside of combustion chamber should also be cleaned and inspected at the same time.

Have Oil Burner and Controls checked at least once a year or as may be necessitated.

Do not operate unit with jumpered or absent controls or safety devices.

Do not operate unit if any control, switch, component, or device has been subject to water.

Appliance materials of construction, products of combustion and the fuel contain alumina, silica, heavymetals, carbon monoxide, nitrogen oxides, aldehydes and/or other toxic or harmful substances whichcan cause death or serious injury and which are known to the state of California to cause cancer, birthdefects and other reproductive harm. Always use proper safety clothing, respirators and equipment whenservicing or working nearby the boiler.

This boiler is designed to burn No. 2 fuel oil only. Do not use gasoline, crankcase drainings, or any oilcontaining gasoline. Never burn garbage or paper in this boiler. Do not convert to any solid fuel (i.e.wood, coal). Do not convert to any gaseous fuel (i.e. natural gas, LP). All flammable debris, rags, paper,wood scraps, etc., should be kept clear of the boiler at all times.

Keep the boiler area clean and free of fire hazards.

Page 4: INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS AP ... · STEEL OIL-FIRED BOILER For service or repairs to boiler, call your heating contractor. When seeking information on boiler,

Thisboilercontainsvery hotwaterunderhighpressure. Donot unscrewanypipefittings nor attemptto disconnect any components of this boiler without positively assuring the water is cool and has nopressure. Always wear protective clothing and equipment when installing, starting up or servicing thisboiler to prevent scald injuries. Do not rely on the pressure and temperature gauges to determine thetemperature and pressure of the boiler. This boiler contains components which become very hot whenthe boiler is operating. Do not touch any components unless they are cool.

This appliance must be properly vented and connected to an approved vent system in good condition.Serious property damage could result if the boiler is connected to an approved vent system.

This boiler needs fresh air for safe operation and must be installed so there are provisions for adequatecombustion and ventilation air.

The interior of the venting and air intake systems must be inspected and cleaned before the start of theheating season and should be inspected periodically throughout the heating season for any obstructions.Clean and unobstructed venting and air intake systems are necessary to allow noxious fumes that couldcause injury or loss of life to vent safely and will contribute toward maintaining the boiler's efficiency.

This boiler is supplied with controls which may cause the boiler to shut down and not re-start withoutservice. If damage due to frozen pipes is a possibility, the heating system should not be left unattended incold weather; or appropriate safeguards and alarms should be installed on the heating system to preventdamage if the boiler is inoperative.

Do not operate boiler on combustible floor without a factory supplied floor shield. Concrete overwood joistsis considered combustible flooring. Do not operate on masonry floors, which may contain moisture.

Table of Contents

I. Pre-Installation ............................... 6

II. Knockdown Boiler Assembly .......... 9

III. Water Piping and Trim ................. 12

1M. Venting ......................................... 17

V. Electrical ....................................... 19

VI. Oil Piping ..................................... 22

VII. System Start-Up ............................ 24

VIII.

IX.

X.

Service and Cleaning .................... 33

Repair Parts .................................. 35

Beckett AFG Burner Parts for

AP-U TM Series Boilers .................... 38

XI. Riello Burner Parts for

_-U TM Series Boilers .................... 40

XII. AppendixLowWater Cut Off ....................... 41

4

Page 5: INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS AP ... · STEEL OIL-FIRED BOILER For service or repairs to boiler, call your heating contractor. When seeking information on boiler,

_" MPTSAFE_

RELIEF VALVECONNECTION

TOP VIEW

I #" MPTSUPPLYCONNECTION

CB!UNG

fo

wz

TANKLESS H_.TER

( _" NPT CONNECTIONS)

TEMPERATURE/PRESSURE GAU@E

RETURN

CONNECTION

FRONT VIEW

¢° FPDRNN VALVECONNECTION

AQUASTATCONTROL

BURNER

FLOOR

LiNE

RIGHT SIDE VIEW

Boiler ModelNumber

AP-490U

AP-590U

AP-690U

AP-790U

Dimension

,A _

34-9/16

41"

Minimum RecommendedChimney Sizes

Rectangular Round

8" x 8" x 15'6" x 15'

7" x 15'

Water

Capacity

(gallons)

10.7

10.1

16.3

15.4

Approx.Shipping Weight (lb.)

290

300

340

355

Figure 1: AP-U Series Boiler Dimensional Data

Page 6: INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS AP ... · STEEL OIL-FIRED BOILER For service or repairs to boiler, call your heating contractor. When seeking information on boiler,

I. Pre-lnstallation

A.

INSPECT SHIPMENT carefully for any signs ofdamage.

1. ALL EQUIPMENT is carefully manufactured,inspected and packed. Our responsibility ceasesupon delivery of the crated boiler to the carrier ingood condition.

2. ANY CLAIMS for damage or shortage of shipmentmust filed immediately against the carrier by theconsignee. No claims for variances from, or

shortage in orders, will be allowed by themanufacturer unless presented within sixty (60) daysafter receipt of goods.

LOCATE BOILER in front of final position beforeremoving crate.

1. LOCATE so that smoke pipe connection to chimneywill be short and direct. BOILER IS NOT SUIT-ABLE FOR INSTALLATION ON COMBUSTIBLE

FLOOR unless combustible floor shield, supplied byNew Yorker(R)Boiler Co. Inc., is used.

2.

3.

DO NOT install on carpeting. See Figure 3 for floorshield part number and installation instructions.

FOR BASEMENT INSTALLATION, provide asolid base, such as concrete, if floor is not level, or if

water may be encountered on floor around boiler.

PROVIDE SERVICE CLEARANCE of at least 48"

from the front of the jacket for servicing of burnerand removal of tankless heater.

For minilnuln clearances to combustible materials. See

Figure 2.

Do not support boiler by placing blocks at thefour (4) corners of the boiler.Boiler base must be evenly supported underentire base.

Do not operate boiler on combustible floorwithout a factory supplied floor shield.Concrete over wood joists is consideredcombustible flooring. Do not operateon masonry floors, which may containmoisture.

NOTE:

Figure 2:

FLOOR

UNE

RIGHT SIDE _W

Minimum Clearances to Combustible Materials

1.

2.

3.

6

Listed clearances comply with American National Standard ANSI/NFPA 3l, Installation of Oil Burning Equipment.

AP-U TM boilers can be installed in rooms with clearances from combustible material as listed above. Listed clearances cannot be reduced for alcove or closet installations.

For reduced clearances to combustible material, protection must be provided as described in the above ANSI/NFPA 31standard.

Page 7: INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS AP ... · STEEL OIL-FIRED BOILER For service or repairs to boiler, call your heating contractor. When seeking information on boiler,

Co

Do

REMOVAL OF BOILER

1. Move boiler (in carton) to installation site as close

as practical.

2. Remove the carton sleeve.

4.

Remove four (4) hex head lag screws, attachingboiler base plate to shipping skid.

Carefully, walk boiler to the edge of the skid. Tiltthe boiler back, allowing boiler base edge to rest onthe floor, then, remove the skid.

PROVIDE COMBUSTION AND VENTILATION

AIR. Local code provisions may apply and should bereferenced.

Adequate combustion and ventilation air mustbe provided to assure proper combustion andto maintain safe ambient air temperatures.

Do not install boiler where gasoline or otherflammable vapors or liquids, or sources ofhydrocarbons (i.e. bleaches, fabric softeners,etc.) are used or stored.

1. Determine volume of space (boiler room). Roomscolnlnunicating directly with the space in which theappliances are installed, through openings notfurnished with doors, are considered a part of the

space.

Volulne(ft 3)= Length(ft) x Width(ft) x Height(ft)

2. Determine total input of all appliances in the space.

Add inputs of all appliances in the space and roundthe result to the nearest 1000 BTU per hour.

3. Determine type of space. Divide Volume by totalinput of all appliances in space. If the result isgreater than or equal to 50 ft3/1000 BTU per hour,then it is considered an uncol_ned space. If theresult is less than 50 ft3/1000 BTU per hour then thespace is considered a co17finedspace.

4. For boiler located in an uncolTfined space of aconventionally constructed building, the fresh airinfiltration through cracks around windows anddoors normally provides adequate air forcombustion and ventilation.

5. For boiler located in a confined space or anunconfined space in a building of unusually tightconstruction, provide outdoor air with the use of twopermanent openings which colnlnunicate directly orby duct with the outdoors or spaces (crawl or attic)freely colmnunicating with the outdoors. Locate oneopening within 12 inches of top of space. Locateremaining opening within 12 inches of bottom ofspace. Minimum dimension of air opening is 3inches. Size each opening per following:

a. Direct communication with outdoors.

Minimum free area of 1 square inch per 4,000BTU per hour input of all equipment in space.

b. Vertical ducts. Minimum free area of 1 squareinch per 4,000 BTU per hour input of allequipment in space. Duct cross-sectional areashall be same as opening free area.

c. Horizontal ducts. Minimum free area of 1

square inch per 2,000 BTU per hour input of allequipment in space. Duct cross-sectional areashall be same as opening free area.

Alternate method for boiler located withincol_ned space. Use indoor air if two permanentopenings colnlnunicate directly with additionalspace(s) of sufficient volume such that combinedvolume of all spaces meet criteria for unconfinedspace. Size each opening for minilnuln free areaof 1 square inch per 1,000 BTU per hour input ofall equipment in spaces, but not less than 100square inches.

6. Louvers and Grilles of Ventilation Ducts

All outside openings should be screened andlouvered. Screens used should not be smaller

than 1/4 inch mesh. Louvers will prevent theentrance of rain and snow.

b. Free area requirements need to consider theblocking effect of louvers, grilles, or screensprotecting the openings. If the free area of thelouver or grille is not known, assume woodlouvers have 20-25 percent free area and metallouvers and grilles have 60-75 percent free area.

c. Louvers and grilles must be fixed in the openposition, or interlocked with the equipment toopen automatically during equipment operation.

Page 8: INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS AP ... · STEEL OIL-FIRED BOILER For service or repairs to boiler, call your heating contractor. When seeking information on boiler,

INSTALLATION INSTRUCTIONS FOR OPTIONAL SHIELD REQUIREDFOR COMBUSTIBLE FLOOR

This shield for combustible floors is intended for use only with the following New Yorker oil-fired boilers:

Use Part Number 6183504 for the following models:

AP-490U AP-590U AP-690U AP-790U

ADDS 4-3/16" TO BOILER HEIGHT

1)

2)

3)

Place shield on combustible floor with "TOP" surface

upward and "FRONT" surface directly below theexpected position of the oil burner.

Locate shield such that clearances to combustible walls

are as indicated in Figure 3. These dimensions willassure that the boiler jacket will be at least 18" fromthe side and rear walls and 48" from the front wall, as

required by ANSI/NFPA 31.

Fasten shield to combustible floor to keep shield fromshifting position during setting of boiler.

4) Set boiler squarely on top of shield such that base plateof boiler rests flat on top surface of shield and does notover-hang shield on any side. Confirm clearance tocombustible walls. Refer to Figure 2.

5) Do not enclose boiler (including shield) on all foursides. Boiler may be enclosed on any three sides whilemaintaining lninilnuln clearances shown in Figure 2 foreach of those three sides.

COMBUSTIBLE

Figure 3: Floor Shield

Page 9: INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS AP ... · STEEL OIL-FIRED BOILER For service or repairs to boiler, call your heating contractor. When seeking information on boiler,

I1. Knockdown Boiler Assembly

Knockdown AP-U Series boilers are shipped as two B. INSTALLING THE JACKET

separate items: 1.

Bare Boiler Assembly (mounted on skid)

Jacket Carton Assembly 2.

Inspect shipment carefully for any signs of damage.

A. REMOVAL OF BOILER

1. Remove and discard four boiler-to-skid hold down

fasteners. Refer to Figure 4.

2. Carefully walk boiler to the skid edge. Tilt the boilerback, allowing the base edge to rest on the floor, andremove the skid.

3. Remove the adhesive backed label-containingenvelope from boiler and set aside.

4. Remove Misc. Parts Bag and bagged Telnperamreand Pressure Gauge (both tucked inside canopy

assembly flue collar) and set aside.

3.

Remove jacket parts and jacket hardware bag fromJacket Carton Assembly shipping carton.

Install the Wrap-Around jacket panel first. BendWrap-Around panel as shown in Figure 5. Attachthe bent panel to base using three #10-1/2" slottedhex washer head screws supplied. Engage all screwsbut do not tighten yet.

Remove 5/16-18 hex nut, 5/16 flat washer,

observation cover spring and Observation PortCover and set aside.

4.

5.

6.

Attach Lower Front Jacket panel to installed Wrap-Around panel with four # 10-1/2" slotted hex washerhead screws supplied. See Figure 5.

Attach Upper Front Jacket panel to installed Wrap-Around panel with four # 10-1/2" slotted hex washerhead screws supplied. See Figure 5.

Lastly, install Top Jacket panel and secure toinstalled Wrap-Around panel with two remaining#10-1/2" slotted hex washer head screws. See Figure5.

7. Once installed, center Top Jacket panel opening overcanopy assembly flue collar and tighten up all threescrews securing Wrap-Around panel to base.

Figure 4: Bare Boiler on Skid

Figure 5: Jacket Installation

Page 10: INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS AP ... · STEEL OIL-FIRED BOILER For service or repairs to boiler, call your heating contractor. When seeking information on boiler,

8.

9.

Attach provided New Yorker logo plate to installedTop Jacket panel with two #8 x */4sheet metalscrews. See Figure 6.

Remove labels from the adhesive backed label-

containing envelope and attach them to jacketpanels. See Figure 6 for approximate labelpositioning.

C. INSTALLATION OF BOILER CONTROLS

1.

2.

Install provided Temperature and Pressure gaugeand aquastat well into appropriate tappings; tightensecurely to prevent water leaks.

Install provided 1-1/4 x 3/4 reducing hex bushingand drain valve into lower right hand 1-1/4 forgedcoupling 'drain' taping.

3.

4.

5.

6.

Install provided 1-1/4 x 3" black nipple into lowerleft hand 1-1/4 forged coupling 'return' taping.

Mount installer-supplied aquastat onto theilmnersion well. Wire the control per Figure 15 orFigure 16, Section IV 'Electrical" of the Installationand Operating Instructions,for AP- U Series Oil-Fired Boiler, as applicable.

Install provided safety relief valve (for details seeFigure 9.

Re-install Observation Port Cover and related

hardware in reverse order to removal. See Figure 7.

Figure 6: Label Locations

10

Page 11: INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS AP ... · STEEL OIL-FIRED BOILER For service or repairs to boiler, call your heating contractor. When seeking information on boiler,

D. BURNER INSTALLATION

1. Insure burner gasket proper fit/positioning on burnerair robe, relative to burner mounting flange, prior toburner mounting. See Figure 7.

Do not install burner without gasket.

2.

3.

Mount installer-supplied burner onto base frontpanel studs and secure with provided 5/16 flatwashers and brass 5/16-18 hex nuts. Refer to

Figure 7.

Wire the burner per instructions, provided with theburner, and, Figure 15, 15A, 16 or 16A, asapplicable.

OBSERVATION PORTCOVER

OBSERVATION COVER:SPRING

5/i6" FLAT WASRER

5/16"-18 HX NUT(H_,W HX)

BURNER MOUNTING FLANGE

W/ KEYHOLE SLOTS

@L BURNER

Figure 7: Burner Mounting

11

Page 12: INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS AP ... · STEEL OIL-FIRED BOILER For service or repairs to boiler, call your heating contractor. When seeking information on boiler,

III. Water Piping and Trim

Failure to properly pipe boiler may result in improper operation and damage to boiler or structure.

Oxygen contamination of boiler water will cause corrosion of iron and steel boiler components, andcan lead to boiler failure. New Yorker's Standard Warranty does not cover problems caused by oxygencontamination of boiler water or scale (lime) build-up caused by frequent addition of water.

A. DESIGN A PIPING SYSTEM and install boiler which

will prevent oxygen contamination of boiler water andfrequent water additions.

1. There are many possible causes of oxygencontamination such as:

a. Addition of excessive make-up water as a resultof system leaks.

b. Absorption through open tanks and fittings.

c. Oxygen permeable materials in the distributionsystem.

2. In order to insure long product life, oxygen sourcesshould be eliminated. This can be accomplished bytaking the following measures:

a. Repairing system leaks to eliminate the need foraddition of make-up water.

b. Eliminating open tanks from the system.

c. Eliminating and/or repairing fittings which allowoxygen absorption.

d. Use ofnon-perlneable materials in thedistribution system.

e. Isolating the boiler from the system water byinstalling a heat exchanger.

System supply and return piping must beconnected to correct boiler pipe.

New Yorker recommends sizing the systemcirculator to supply sufficient flow (GPM) toallow a 20°F temperature differential in thesystem. When sizing the system circulator,the pressure drop of all radiators, baseboardand radiant tubing and all connecting pipingmust be considered.

3. Connect System supply and return piping to boiler.See Figures 9 and 10. Also, consult I=B=RInstallation and Piping Guides. Maintain minilnuln1/2inch clearance from hot water piping tocombustible materials.

12

a. If this boiler is used in connection with

refrigeration systems, the boiler must be installedso that the chilled medium is piped in parallelwith the heating boiler using appropriate valvesto prevent the chilled medium from entering theboiler. See Figure 8. Also, consult I=B=RInstallation and Piping Guides.

SUPPLY lqA_N TF/ __U_N NAIN _R_['}Y

S C(:]SLIN6 SYS]_LH S C08LINC SYSi[:_,"

Figure 8: Recommended Piping for CombinationHeating and Cooling (Refrigeration) System

b. If this boiler is connected to heating coils locatedin air handling units where they may be exposedto refrigerated air, the boiler piping must beequipped with flow control valves to preventgravity circulation of boiler water during theoperation of the cooling system.

c. If boiler is used with an Indirect-Fired Domestic

Water Heater, install the Indirect-Fired DomesticWater Heater as a separate heating zone. Referto the Indirect-Fired Domestic Water Heater

Installation, Operating, and Service Instructionsfor additional information.

d. Use a system bypass if the boiler is to beoperated in a system which has a large volume orexcessive radiation where low boiler water

temperatures may be encountered (i.e. convertedgravity circulation system, etc.) The bypassshould be the same size as the supply and returnlines with valves located in the bypass and return

Page 13: INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS AP ... · STEEL OIL-FIRED BOILER For service or repairs to boiler, call your heating contractor. When seeking information on boiler,

e.

line as illustrated in Figures 10 and 11 in order toregulate water flow for maintenance of higherboiler water temperature. Set the bypass andreturn valves to a half throttle position to start.Operate boiler until the system water temperaturereaches its normal operating range. Adjust thevalves to maintain 180°F to 200°F boiler water

temperature and greater the 120°F returntemperature. Adjust both valves simultaneously.Closing the boiler return valve while opening thebypass valve will raise the boiler returntemperature. Opening the boiler return valvewhile closing the by-pass valve will lower theboiler return temperature.

A water boiler installed above radiation level

must be provided with a low water cutoff deviceas part of the installation.

INSTALL SAFETY RELIEF VALVE. See Figures 9,10 and 11. Safety Relief Valve must be installed withspindle in the vertical position. Installation of the reliefvalve must be consistent with ANSI/ASME Boiler and

Pressure Vessel Code, Section IV.

Safety (relief) valve discharge piping must bepiped near floor to eliminate potential of severeburns. Do not pipe in any area where freezingcould occur. Do not install any shut-off valves,plugs or caps.

Co AIR VENT. An air vent or purge must be incorporatedin the system to easily remove air from the boiler whenthe system is filled. The boiler has a built in dip tubewhich works with the air vent to clear the boiler of air.

Improper application of the air vent will cause steamingin the boiler. See Figure 9.

D. INSTALL DRAIN VALVE in return piping. See

Figures l0 and ll.

E.

17.

G.

OIL, GREASE, AND OTHER FOREIGNMATERIALS which accumulate in new hot water

and a new or reworked system should be boiledout, and then thoroughly flushed. A qualified watertreatment chemical specialist should be consulted forrecommendations regarding appropriate chemicalcompounds and concentrations which are compatiblewith local environmental regulations.

Figure 9: Air Vent and Safety Relief ValveInstallation Detail

AFTER THE BOILER AND SYSTEM HAVE BEEN

CLEANED and flushed, and before refilling the entiresystem add appropriate water treatment chemicals, ifnecessary, to bring the pH between 7 and 11.

CONNECT TANKLES S HEATER PIP1NG ASSHOWN IN FIGURE 12. See Table 1 for Tankless

Heater Rating.

Install automatic mixing valve at tankless heateroutlet to avoid risk of burns or scalding due toexcessively hot water at fixtures. Adjust andmaintain the mixing valve in accordance withthe manufacturer's instructions. Do not operatetankless heater without mixing valve.

13

Page 14: INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS AP ... · STEEL OIL-FIRED BOILER For service or repairs to boiler, call your heating contractor. When seeking information on boiler,

A_R VENT

LOW WATERCUT_O_

(O_T_ON/¢)

MR VENT

PRESSUREREUEFVAL_

%_ FROM ADO}TIONAL ZONES

FROM ZONE 2

F_M N_TE WATER NEAT_

OR ZONE 1

SHUT-OFFV#£VES

NOES_RUN EACH ZONE PIPE _WN THEN UP TO ZONETO PRD_ENT MR AC:CUMU_T_ON iN PiPiNG,

SHUTOFFVALVE

TONY_MATE

WATER H_T_

_: usED:)ZONE !

C_RCULa,TOR

TOZONE 2

TO/_DO_T/ONAL

ZONES

6" OF PLOOR FRONT VIEW

Figure 10: Recommended Boiler Piping for Circulator Zoned Heating Systems

Page 15: INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS AP ... · STEEL OIL-FIRED BOILER For service or repairs to boiler, call your heating contractor. When seeking information on boiler,

mR VE_

_-x, _ FROM ADDRIONAiL ZONES

iLOW'WATER

CUT_OFF(OP ION )

NR _NT

P_SSUREREUEFVALVE

i

_" "q_'Ir--_74 _ FROM NY-#ATE WATERHEAT_OR ZONE I

SHUT-O£FVAEVES

BYPASS tb,tNEVE_DI_ONAL

_TEM UMiT

i iF REQU RED)

Lt SUPPLYVALVE

_S_MSUPPLY

EXPANSIONT_NK

NOTES;:RUN EACH ZONE PiPE DOWN THEN UP TO ZONETO PR_NT AiR ACCUMULATION iN PIP!NG_

PRESSUREREDU@NG

V_VE

_!®!l

SHUT-OWVALVE

C:O_ WATERSUPPLY

TO,

_ _NO_ AL

i i'

TO TONY_MATE ZONE :2

HDATER

USED)OR ZONE !

6" OF _OOR FRONT VI_

Figure 11: Boiler Piping for Zone Valve Zoned Heating Systems

Page 16: INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS AP ... · STEEL OIL-FIRED BOILER For service or repairs to boiler, call your heating contractor. When seeking information on boiler,

THE FOLLOWING GUIDELINES SHOULD BE

FOLLOWED WHEN PIPING THE TANKLESS HEATER:

1. FLOW REGULATION -- If flow through the heateris greater than its rating, the supply of adequate hotwater may not be able to keep up with the demand.For this reason a flow regulator matching the heaterrating should be installed in the cold water line tothe heater. The flow regulator should preferably belocated below the inlet to the heater and a lninilnuln

of 3' away from the inlet so that the regulator is notsubjected to excess temperatures that may occurduring "off' periods when it is possible for heat tobe conducted back through the supply line. The flowregulator also limits the flow of supply waterregardless of inlet pressure variations in the range of20 to 125 psi.

2. TEMPERING OF HOT WATER -- Installation of

an automatic mixing valve will lengthen the deliveryof the available hot water by mixing some coldwater with the hot. This prevents the possibility ofscalding hot water at the fixtures. In addition,savings of hot water will be achieved since the userwill not waste as much hot water while seeking awater telnperamre. Higher telnperamre hot water

3.

4.

required by dishwashers and automatic washers ispossible by piping the hot water from the heaterprior to entering the mixing valve. The mixing valveshould be "trapped" by installing it below the coldwater inlet to heater to prevent lime formation in thevalve. Refer to Figure 12.

FLUSHING OF HEATER -- All water containssome sediment which settles on the inside of the

coil. Consequently, the heater should be periodicallybackwashed. This is accomplished by installing hosebibs as illustrated and allowing water at citypressure to run into hose bib A, through the heater,and out hose bib B until the discharge is clear. Thetees in which the hose bibs are located should be thesame size as heater connections to minilnize

pressure drop.

HARD WATER -- A water analysis is necessary todetermine the hardness of your potable water. Thisis applicable to some city water and particularly towell water. An appropriate water softener should beinstalled based on the analysis and dealer'srecolranendation. This is not only beneficial to thetankless heater but to piping and fixtures plus themany other benefits derived from soft water.

Figure 12: Schematic Tankless Heater Piping

Table 1: Tankless Heater Ratings

Boiler Model

AP-490U

AP-590U

AP-690U

AP-790U

Tankless Heater Model

S-4 S-5

GPM PSID GPM PSID

3 12 3½ 15

3¼ 16

3½ 1933A 25

16

Page 17: INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS AP ... · STEEL OIL-FIRED BOILER For service or repairs to boiler, call your heating contractor. When seeking information on boiler,

IV. Venting

A. GENERAL GUIDELINES.

1.

2.

Vent system installation must be in accordance withthese instructions and applicable provisions of localbuilding codes. Contact local building or fireofficials about restrictions and installation inspectionin your area.

The AP-U Series is designed to be vented into afireclay tile-lined masonry chimney or chimneyconstructed from type-L vent or a factory builtchimney that complies with the type HTrequirements of UL103. The chimney or vent pipeshall have a sufficient draft at all times, to assuresafe proper operation of the boiler. See Figure 13 forrecommended installation.

a.

b.

Install a draft regulator (supplied by installer)following the instructions furnished with theregulator. See Figure 14 for alternate regulatorlocations.

With any new or replacement installation thechimney has to be considered. Chimneys thathave a high heat loss become less suitable as theheat loss of the home goes down and theefficiency of the boiler goes up. Most homeshave a chimney appropriate for the fuel and theera in which the home was built. That may havebeen a coal fired or an inefficient oil fired boilerbuilt into a home without insulation or storm

windows. With increasing fuel prices that homeprobably has been insulated and fitted with stormwindows so that the heat loss of the home has

been reduced. This requires less fuel to beburned and sends less heat up the chimney.A new boiler probably has a higher efficiencythan the boiler being replaced. That probably

3.

means that the stack temperature from the newboiler will be lower than that from the old boiler

and with less room air being drawn up thechimney to dilute the stack gases. Thecombination of a large uninsulated chimney,reduced firing rate, reduced firing time, lowerstack temperature and less dilution air can, insome cases, contribute to the condensing ofsmall amounts of water vapor in the chimney.Such condensation, when it occurs, can causechimney deterioration. In extreme cases, thechimney may have to be lined to insulate thechimney and thus prevent the condensation. Theaddition of dilution air into the chimney mayassist in drying the chimney interior surfaces.A massive chimney on a cold, or exposed outsidewall may have produced adequate draft when itwas fired with a higher input and greater volumesof heated gases. With reduced input and volume,the draft may be severely affected. In oneinstance our research showed a new chimney ofadequate sizing produced only -.035" W.C. after

30 minutes of continuous firing at 13.0% CO 2.Outside wall chimneys take longer to heat up andcan have .00" W.C. draft at burner start-up. Youmay have to consider a special alloy chimneyflue liner with insulation around it and stabilizingdraft cap or even a draft inducing fan in severecases.

c. For the same reasons as in (2.) above, heatextractors mounted into the breeching are notrecommended.

For minilnuln clearances to combustible materials

refer to Figure 2.

17

Page 18: INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS AP ... · STEEL OIL-FIRED BOILER For service or repairs to boiler, call your heating contractor. When seeking information on boiler,

F_RECLAY TILELINED

THIMBLE

GA, MINo X FUDL S_ZEOF CANOPY OUTLET COLOR (DO NOT REDUCE)NOTE: ALL HOR!ZONTAL SNOKEP!PE SHOULD SLOPEUPWARD NOT LESS T_N ONE INCH _N FOUR FEF

AiR GAPREGU_TOR

DILUTION NR

CL_NOUT

O_L BURNER

FLOORUNE

VIEWFigure 13: Recommended Smokepipe Arrangement and Chimney Requirements

18

PROPER LOCATIONS UNACCEPTABLE LOCATIONS

_,A- ;L; 1

ACCEPTABLE LOCATION

_EER

0

I BOILER

5

0

BOILER

_[LER

I

IFigure 14: Draft Regulator Locations

Page 19: INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS AP ... · STEEL OIL-FIRED BOILER For service or repairs to boiler, call your heating contractor. When seeking information on boiler,

V. Electrical

Positively assure all electrical connections are unpowered before attempting installation or service ofelectrical components or connections of the boiler or building. Lock out all electrical boxes with padlockonce power is turned off.

Failure to properly wire electrical connections to the boiler may result in serious physical harm.

Electrical power may be from more than one source. Make sure all power is off before attempting anyelectrical work.

Each boiler must be protected with a properly sized fused disconnect.

Never jump out or make inoperative any safety or operating controls.

The wiring diagrams contained in this manual are for reference purposes only. Refer to the wiring diagramof any controls used with the boiler. Read, understand and follow all wiring instructions supplied withthe controls.

A. GENERAL 2.

2.

Install wiring and electrically ground boiler inaccordance with requirements of the authorityhaving jurisdiction, or in absence of suchrequirements the National Electrical Code, ANSI/NFPA 70, and/or the CSA C22.1 Electric Code.

A separate electrical circuit must be run from themain electrical service with an over-current device/disconnect in the circuit. A service switch is

recommended and may be required by some localjurisdictions.

3. Wiring should conform to Figure 15 and/or 16.

B. SYSTEM CONTROLS AND WIRING

1. Refer to National Electric Code or Local Electric

Codes for proper size and type of wire required.Follow Code.

3.

4.

5.

Use anti-short bushings on all wiring passing

through boiler jacket, junction boxes and/or controlboxes.

Use armored cable (BX) over all exposed linevoltage wiring.

If an indirect water heater is used, use priorityzoning. Do not use priority zoning for Hydro-AirSystems.

Single Zone System - Refer to Figure 15 or 16 forthe electrical diagram for this type of system.Connect the system circulator wire leads to theproper locations on the Aquastat control, L7224A/L7248A. See Figure 15Aor 16A. Connect thethermostat to the 'T-T' terminals on the L7224A/

L7248A control. Set thermostat heat anticipatorsettings to 0.60 amps.

19

Page 20: INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS AP ... · STEEL OIL-FIRED BOILER For service or repairs to boiler, call your heating contractor. When seeking information on boiler,

24V _HZRM_,_

iB:_B: @IJRPU !'Ii_

M2JASffAT CQN'_BOZRElY

_RCLILATOR

SC|IEMATIe DIAGRAM _GEND

UNE VBLTAOE BIB 14 A_G

lINE BBITA_)Z B4_Z IB g_¢

WPE _ OR TW/BW_ !_RE

_iRZNUT

_ Q@I!K (X_N_4_C_ R_BiP_AB_Z

JM_ZR SLI_HZ_IBY bONE_LL

_BBf_OR

BURNER

........_ ........

..........................................................................................................:_.!_.........

wH

WR W_

..............................................................................................................................................NZ 5_ _-._

BURNER

J-BOX

i, _4Y UP H_ C_!01_AL _I_Z AS SU_LU,I _*_f/,_ I:H _ LL@4CE _US BZ

RE_B_, _T _ _ REPhraSED WF#H _RE AS _BWN OR _S EQU@A_£N1",

BECKEE R184B _R_M#_Y OON'_ROL

................i_ 1ONCOR

................ _ VALVE

÷÷.............. _h L2 I I

i i..............................._;_ I i

¥_I IYE

r<OJ'tJ

W_EECODE_ BLACK

-- BLUE

GR * GRHN

OR - O_NCE

RB - REi}

YE YEIOB

BL,£@_ BLUE Wi _(TE TRACE

.........ZNV@_EJOM_TERMINN_S

x_._ 1-oT TERMINAtS

Figure 15: AP-U Boiler Wiring Less Tankless, Single Circulator w/Beckett Burner

B[LLO BURNER W/PRIMA_Y CONTROL

SCHEMATIC D]AQRAM LEGEND

...... tO_@ VOLTA_Z SIZE 18/2 AWG POWER

L,/M!T_D CIRCLIT C_I: '25 i05'C

LINE 'VOL]:ABE SIZE 14 AWO

T'f_E TW OR ?D4_'/AWM WIRE

UNZ VOLJAGE SiZE 18 AWGTYPE I'#OR TE_JA'#M WiRE

NC)TES:

I, I_ ANY OF ?RE ORIGINAL WIRE AS BUPPDZB _iTH BE _PLIANCZ MUST B£

BEPIACEB _ M*JS_BE REPLACFJ9 WITH _IR _B BBC:WN OR _TS EQU:BALEN_

#I_E CODE

BL _ BLUEOR _ QRZZ_

RD _ RED

WB _ _4_F

Figure 15A: AP-U Boiler Wiring Less Tankless, Single Circulator w/Riello Burner

20

Page 21: INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS AP ... · STEEL OIL-FIRED BOILER For service or repairs to boiler, call your heating contractor. When seeking information on boiler,

gaV _H_RM_ ¸

_)IE_,TId D_)SRAM _GEND

NOTE_

F_ ":Z:_ _ _ +!

; L _

@'+ffOR

,..,÷URNR

WH

_UNNER&:BOX

B_:_CK_f['TR7_848 PR+_RY CONIROL

.........................+° ++

Y_

W]_ dODE

O@ "- Off_ANOE

+ YfiLu_

cD--t

I

.... =+=--__:+ ?+t _++ MiNAbS

\_::, J+#+¢'ER

Figure 16: AP-U Boiler Wiring with Tankless, Single Circulator w/Beckett Burner

ZR

®

I'_'E_SSURPU+:9 BY II@S'f_LL_R

+

++ ii:::;:i--Z +.1w+++

; +: +

S+:RVffC+ FUSED DISCON+¢EC+S_TTO S+#ffOH

SCHEMATIC DIAGP,AM _GEND

..... LG!W VO TA_E SIZE 18/2 A'_G POWER

UM[TED CtRCU_ CABLE 75 IOB+C

UNE COLLAGE SiZE 14 A_#G

tYPE !# OR _EW/AW_ @tR_

SUPPgY

R+_U_O BURNER W/PR_ARY COtITROL

(2@/ ¢ONSTA+_T POWER::

"SIRE dODE

_L - BLUE

RD - R_

+@14 - WHITE

UN8 VOLTAGE SIZE 8 A'#G

NOTES:

I, ++" ANY O_ THE ORIG _'_L W;RE AS SUPPU_D WITH TH_ *+PPU_k_CE MUST 8_

R_LAI.';FD+ IT M_ST _£ R_PLACFO WIT+'_WIR A% S>4OWN OR RS EQUIVR_FNT.

Figure 16A: AP-U Boiler Wiring with Tankless, Single Circulator w/Riello Burner

21

Page 22: INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS AP ... · STEEL OIL-FIRED BOILER For service or repairs to boiler, call your heating contractor. When seeking information on boiler,

Vl. Oil Piping

A. GENERAL.

1. Use flexible oil line(s) so that burner can be

removed without disconnecting the oil supply.

2. A supply line fuel oil filter is recommended as aminilnuln for all firing rates but a pleated paper fueloil filter is recolmnended for the lowest firing rateapplication to prevent nozzle fouling.

3. Use Flared fittings only. Do not use compressionfittings.

4. Use of a high efficiency micron filter (Garber orequivalent) in addition to conventional filter ishighly recommended.

B. SINGLE-PIPE OIL LINES.

1. Standard burners are provided with single-stage3450 rpm fuel units with the bypass plug removedfor single-pipe installations.

2. The single-stage fuel unit may be installed single-pipe with gravity feed or lift. Maximum allowablelift is 8 feet. See Figure 17.

Oil piping must be absolutely airtight or leaks orloss of prime may result. Bleed line and fuel unitcompletely.

AIRVEN

FILLPIPE

OILTANK

FU EL

FLEXIBLE OIL PIPING RECOMMENDEDNEAR BURNER SWING DOOR

PUMP

SHUT-OFFVALVE

IN

MAIN FILTER

RECOMMENDEDFILTER (GA RBEROR EQUIVALENT)

MAXIMUM

ONE PiPE

Figure 17: Single-Pipe Installation

22

Page 23: INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS AP ... · STEEL OIL-FIRED BOILER For service or repairs to boiler, call your heating contractor. When seeking information on boiler,

Table 2: Single Stage Units (3450 RPM)Two Pipe Systems

Lift "H"(See Figure)

0 I

1'

2'

3'

4'

5'

6'

7'

8'

9'

10'

11'

12'

13'

14'

Maximum Length of Tubing"H" + "R" (See Figure)

3/8" OD Tubing(3 GPH)

84'

78'

73'

68'

63'

57'

52'

47'

42'

36'

31'

26'

21'

1/2" OD Tubing

(3 GPH)

100'

100'

100'

100'

100'

100'

100'

100'

100'

100'

100'

100'

83'

62'

41'

Table 3: Two-Stage Units (3450 RPM)Two Pipe Systems

Lift "H"(See Figure)

0 I

2'

4'

6'

8'

10'

12'

14'

16'

18'

Maximum Length of Tubing"H" + "R" (See Figure)

3/8" OD Tubing(3 GPH)

93'

85'

77'

69'

60'

52'

44'

36'

27'

1/2" OD Tubing

(3 GPH)

100'

100'

100'

100'

100'

100'

100'

100'

100'

76'

C. TWO-PIPE OIL LINES

1. For two-piped systems, where more lift is required,the two-stage fuel unit is recommended. Table 2(single-stage) and Table 3 (two-stage) showallowable lift and lengths of 3/8 inch and 1/2 inchOD robing for both suction and return lines. Referto Figure 18.

OUTSIDE TANK FUEL PUMP ABOVE

BOSOM OF TANK

FILLPIPE

AiRVENT

FUEL

RETURNLINE

FLEXIBLENEAR

RETURNLINE

OIL PIPING RECOMMENDEDBURNER SWING DOOR

RECOMMENDEDFILTER (GARBEROR EQUIVALENT)

INLET l

'H'

Figure 18: Two-Pipe Installation23

Page 24: INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS AP ... · STEEL OIL-FIRED BOILER For service or repairs to boiler, call your heating contractor. When seeking information on boiler,

VII. System Start-Up

VERIFY that the venting, water piping, oil piping,and electrical system are installed properly. Refer toinstallation instructions contained in this manual.

CONFIRM all electrical, water and oil supplies areturned off at the source and that the vent is clear fromobstructions.

Completely read, understand and follow allinstructions in this manual before attemptingstart up.

24

FILL ENTIRE HEATING SYSTEM WITH WATER

and vent air from system. Use the following procedureon a Series Loop or multi-zoned system installed as perFigure 10 or 11.

1. Close isolation valve in boiler supply piping.

2. Isolate all circuits by closing zone valves orbalancing valves.

3. Attach a hose to hose bib located just belowisolation valve in boiler supply piping. (Note -Terminate hose at a suitable floor drain or outdoor

area).

4. Starting with one circuit at a time, open zone valveor valve.

5. Open hose bib.

6. Open fill valve (Make-up water line should belocated directly after isolation valve in boiler supplypiping between air scoop and expansion tank).

7. Allow water to flow into drain until discharge fromhose is bubble free for 30 seconds.

8. When zone is completely purged of air, close zonevalve or balancing valve. Open the zone valve forthe next zone to be purged. Repeat this step until allzones have been purged. At completion, open allzone valves or valves.

The maximum operating pressure of this boiler is30 psig. Never exceed this pressure. Do not plugor change pressure relief valve.

9. Close hose bib, continue filling the system until thepressure gauge reads 12 psig. Close fill valve.(Note - If make-up water line is equipped withpressure reducing valve, system will automaticallyfill to 12 psig.

10. Open isolation valve in boiler supply piping.

11. Remove hose from hose bib.

Do

F.

Go

CONFIRM that the boiler and system have no waterleaks.

CHECK CONTROLS, WIRING AND BURNER tobe sure that all connections are tight and burner isrigid. Verify that all electrical connections have beencompleted, fuses installed, that the oil tank is filled andoil lines have been tested.

LUBRICATION. Follow instruction on burner and

circulator label to lubricate, ifoil lubricated. Most

motors currently used on residential type burnersemploy permanently lubricated bearings and thus donot require any field lubrication. Water lubricatedcirculators do not need field lubrication.

ADJUST CONTROLS SETTINGS with burner serviceswitch turned "ON".

1.

2.

SET ROOM THERMOSTAT about 10°F below

room temperature.

PRESS RED RESET BUTTON on front of

burner cover (Beckett, Riello burners) hold buttonfor one (1) second and release to reset primarycontrol.

3. On WATER BOILERS WITHOUT TANKLESS

HEATERS equipped with L7248 electronic aquastatcontroller, set High Limit (HL) at 180°F. Thistemperature can be varied to suit installationrequirements. L7248 controller has the High Limitadjustlnent range from 180°F to 240°F (82°C to116°C). High Limit Differential is fixed at 15°F(soc).

4. On WATER BOILERS WITH TANKLESS

HEATERS equipped with L7224 electronic aquastatcontroller, set operating control (low limit [LL]) at190°F and high limit (HL) at 210°F. Operatingcontrol (low limit) setting must be a lninilnuln of20°F below high limit setting.

L7224 controller has the High Limit adjustlnentrange from 130°F to 240°F (55°C to 116°C), and theLow Limit adjustlnent range from 110°F to 220°F(43°C to 104°C). High Limit Differential is fixed at10°F (6°C), and Low Limit Differential hasadjustlnent range from 10°F (6°C) to 25°F (14°C).

5. ADJUSTING AQUASTAT CONTROLLERSETTINGS. To discourage unauthorized changingof Aquastat settings, a procedure to enter theADJUSTMENT mode is required. To enter theADJUSTMENT mode, press the UP, DOWN, andI buttons (refer to Figure 19) simultaneously forthree seconds. Press the I button until the feature

requiring adjustlnent is displayed:

Page 25: INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS AP ... · STEEL OIL-FIRED BOILER For service or repairs to boiler, call your heating contractor. When seeking information on boiler,

CAPAC TOR

tRANSFORMER

FUSE

THERMOSTAiT ------TERM NALS

-- RELAYS

SENSOR CONNEC'[OR '--- FFLD T_"_RMINALS

L_ SENSOR HO(_':

(HORIZONTAL MOUNT)

Figure 19:1_7248/1_7224 Circuit Board Layout-Horizontal Mount

6.

• HL_-- High Limit.• LL -- Low Limit.• Ldf-- Low Limit Differential.• °F-- °C.

Then, press the UP and/or DOWN buttons to movethe set point to the desired value. After 60 secondswithout any button inputs, the control willautomatically return to the RUN mode.

Note that L7224 Aquastat Controller will display allfour (4) above-listed adjustlnent features, but L7248Aquastat Controller will not display Low Limit andLow Limit Differential adjustlnent features.

DISPLAY READOUT

In the RUN mode, the Aquastat will flash "bt"(boiler telnp) followed by the telnperamre (i.e.,220), followed by °F or °C.

To read boiler settings, press the I key to read theparameter of interest. For example, press I HighLimit (ILL) is displayed, followed by a three-digitnumber, i.e., 220, followed by °F or °C. Pressingthe I button again (on L7224 models) will displaythe Low Limit iLL) followed by a three-digitnumber and the corresponding degree designator.See Display Readout, Figure 20.

Text Desc ription Shows

bt Boiler Temperature

HL High Limit _k

LL Low Limit L t.

Ldf Low Limit Differential k dF

tt Local Thermostat Status _

tie Enviracom Thermostat Status

en Error Code

f Degrees Fahrenheit QF

C Degrees Celsius O_"

Figure 20: Display Readout Definitions

7.

Table 4:

After approximately 60 seconds without any keypresses, the display will enter a dim display mode.To return to the bright display mode, simply pressany key.

OPERATION

The L7224 model can be in any of four operationalstates - Nounal, High Limit, Low Limit and Error.The controller moves back and forth from HighLimit to Nounal to Low Limit state as part ofnounal operation.

The L7248 model is restricted to three operationalstates - Nounal, High Limit and Error. Thecontroller moves back and forth from High Limit toNounal state as part of nounal operation.

For both models, the controller will enter the Errorstate when there is an abnormal condition. The

operating states are:

a. Nounal: Boiler telnperamre went below theHigh Limit setting (minus the Differential) andhas not exceeded the High Limit setting; or theboiler telnperamre went above the Low Limitsetting and has not gone below the Low Limitsetting (minus the Differential).

b. High Limit: Boiler telnperamre went above theHigh Limit setting and has not dropped belowthe High Limit setting (minus the Differential).

c. Low Limit: Boiler telnperamre went below theLow Limit setting (minus the Low LimitDifferential) and has not gone above the LowLimit setting.

d. Error: The controller has detected an error

condition (e.g., open sensor) and has shut downthe burner output. The ZC output is energized.The controller continues to monitor the systemand automatically restarts if the error conditionclears. Refer to Table 4.

The operating sequence for the L7224/L7248 isshown in Table 5.

LED Error Codes

ErrorCause / Action

Code

Errl Sensor fault; check sensor.

Err2 ECOM fault; check EnviraCOM TM wiring.

Err3 Hardware fault; replace control.

Err4 B 1 fault; check B 1 wiring/voltage.

Err5 Low Line; check L1-L2, 110 Vac.

Err6 Fuse; check ECOM wires, replace fuse.

Err7 EEPROM, HL, LL, HdL Ldf; reset to defaultvalues. Restore desired settings.

Err8 Repeated B 1 fault (voltage present at B 1 whenoutput is turned off); check B 1 wiring/voltage.

25

Page 26: INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS AP ... · STEEL OIL-FIRED BOILER For service or repairs to boiler, call your heating contractor. When seeking information on boiler,

Table 5:Se(L7224 / L7248 Controller Operating

uence

Action

Thermostatcalls for heat.

Boiler exceeds

the High Limit.

Thermostat issatisfied.

Errorcondition 1-5.

Error

condition 6.

Errorcondition 7.

Error

condition 8.

System Response

Circulator starts when water temperature

is above Low Limit setting (if applicable).

Boiler temperature is checked. Burner starts

when water temperature is below High Limit

setting.

Burner is turned off. Burner restarts when the

water temperature drops below the High Limit

setting minus the Differential.

Circulator and burner turn off.

If an error condition is detected, all outputs

except ZC are shut down. Burner is off.

Control continues to function and restarts

when error is corrected.

During the error check sequence, the systemchecks tbr drift in the sensor and corrosion in

the connections.

EnviraCOM communication is not available.

The control has reset the High Limit, LowLimit and Differential setting to a defaultsetting and will continue to run at thosesettings.Performance of the system will be degraded.

If the error condition is detected, all outputsexcept ZC are shut down. Burner is off.Control continues to function and restarts

when all three user keys have been pressedlonger than 60 seconds.

26

8. HIGH LIMIT CONTROLLER

The High Limit opens and turns off the burner whenthe water temperature reaches the setpoint. TheHigh Limit automatically resets after the watertemperature drops past the setpoint and through theDifferential. The L7248 models have High LimitDifferential presets of 15°F (8°C). The L7224models have High Limit Differential presets of 10°F(6°C).

9. LOW LIMIT AND CIRCULATOR CONTROLLER

On a temperature rise, with the adjustableDifferential at the default setting of 10°F (6°C), theburner circuit breaks and the circulator circuit makes

(assuming no call for heat is present) at the LowLimit setpoint. On a temperature drop of 10°F(6°C) below the Low Limit setpoint, the burnercircuit makes and the circulator circuit breaks. See

Figure 21.

10. CHECKOUT

Put the system into operation and observe at leastone complete cycle to make sure that the controlleroperates properly. See Step 11, TROUBLESHOOTING to use LED to assist in determiningsystem operation.

i : (4:5

Figure 21 : Setpoints and Differentials

11. TROUBLE SHOOTING

When attempting to diagnose system performance,reference to the LED display can help to identifyspecific areas not working properly. The LEDdisplay will scroll Err, followed by a digit (1-8).Refer to Table 4 for a description of each error andsuggested actions.

For Beckett Burner

H. REMOVE GUN ASSEMBLY

1. Check nozzle size, head size, gun setting, andpositioning of electrodes. This information is shownin Figure 22, and Table 6.

2. Reinstall gun assembly.

I° VERIFY OIL BURNER SETTINGS BEFORESTARTING

1. BURNER AIR BAND AND AIR SHUTTER

SETTINGS, see Table 6.

2. OPEN ALL OIL LINE VALVES.

3. Attach a plastic hose to fuel pump vent fitting andprovide a container to catch the oil.

4. REMOVE GAUGE PORT PLUG from fuel pumpand install pressure gauge.

£LECTROOIE

_/11 AIOV ZLE

ELECTRODE ADJUSTMENTS

Figure 22: Electrode / Head Setting

Page 27: INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS AP ... · STEEL OIL-FIRED BOILER For service or repairs to boiler, call your heating contractor. When seeking information on boiler,

Table6: BeckettAFGBurners

BoilerModel

*AP-490U

AP-590U

AP-690U

AP-790U

Firing Rate(GPH)

0.75

1.00

1.10

1.35

Nozzle

0.65 - 80°ABDanfoss

0.85 - 80°BHAGO

0.90 - 80°BHAGO

1.10 - 80°BHAGO

Shutter

7

4

6

8

Band

0

0

0

0

Head (stop screw)

N/A

N/A

N/A

N/A

Air Settings

Pump Pressure

140

140

140

140

* Equipped with low firing rate baffle

J. START OIL BURNER

1. Open vent fitting on fuel pump.

2. TURN 'ON' BURNER service switch and allow

burner to run until oil flows from vent fitting in aSOLID stream without air bubbles for

approximately 10 seconds.

3. Close vent fitting and burner flame should start

immediately.

4. If the burner does not start immediately, check themanual overload switch on the motor, if so

equipped, and the safety switch on the burner

primary control.

K. ADJUST OIL PRESSURE

1. Locate oil pressure adjusting screw and turn screw

until Pressure Gauge reads the correct pump

pressure required for the specific boiler. Refer toTable 6.

2. DO NOT REMOVE PRESSURE GAUGE untillater.

L. OTHER ADJUSTMENTS

1. ADJUST THE AIR BAND AND/OR AIR

SHUTTER.

2.

3.

Beckett Burners:

a. Adjust air supply by loosening lock screws andmoving the air shutter and if necessary the airband. Refer to Table 6 preliminary settings.

ADJUST DRAFT REGULATOR for a draft of

-.02" (water gauge) over the fire after chimney hasreached operating telnperature and while burner isrunning.

READJUST AIR BANDS on burner for a lightorange colored flame while draft over the fire is-.02" w.c. Use a smoke test and adjust air forminilnuln smoke (not to exceed #1) with aminilnuln of excess air. Make final check using

suitable instrumentation to obtain a CO 2of 11.5 to12.5% with draft of-.02" w.c. in fire box. These

settings will assure a safe and efficient operating

®

4.

condition. If the flame appears stringy instead of a

solid flame, try another nozzle of the same type.

Flame should be solid and compact. After all

adjustments have been made, recheck for a draft of-.02" w.c. over the fire.

TURN "OFF" BURNER and remove pressure

gauge. Install gauge port plug and tighten. Start

burner again.

For Riello Burner

M. INSPECT NOZZLE_ ELECTRODES ANDTURBULATOR SETTING

1. Loosen Burner Cover Screws and remove BurnerCover.

2. Installation/Removal of Drawer Assembly, Refer toFigure 23.

Figure 23: Installation/Removal of Drawer Assembly

a. Removal:

• Disconnect oil delivery tube nut from pump.

• Loosen SCREW (3), and then unplug

PRIMARY CONTROL (1) by carefully

pulling it back and then up.

• Remove the AIR TUBE COVER

PLATE (5) by loosening the retaining

27

Page 28: INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS AP ... · STEEL OIL-FIRED BOILER For service or repairs to boiler, call your heating contractor. When seeking information on boiler,

3.

SCREW (4) (Two SCREWS-Model F5).

• Loosen SCREW (2), and then slide the

complete drawer assembly out of thecombustion head as shown.

b. Installation:

To insert drawer assembly, reverse theprocedure in Step 2a.

Nozzle Replacement, Refer to Figure 24

4.

% •

Figure 24: Nozzle Replacement

a. Remove the NOZZLE ADAPTER (2) from theDRAWER ASSEMBLY by loosening theSCREW (1).

b. Remove existing nozzle from nozzle adapter.

c. Insert the proper NOZZLE into NOZZLEADAPTER and tighten securely (Do not overtighten).

d. Replace adapter, with nozzle installed, intodrawer assembly and secure with screw (1).

Inspect and measure burner electrodes. Refer toFigure 25 for the proper electrode settings.

IMPORTANT: THESE DIMENSIONS MUST BE OBSERVED AND VERIFIED.

..................@r5/_4" :'_/64" 0r 2 to2.smm_

Figure 25: Electrode Setting

5. Re-install Drawer Assembly into CombustionHead per Step 2a.

6. Turbulator Setting, Refer to Figure 26

'4 0

Figure 26: Turbulator Setting

7.

a. Confirm the turbulator setting is correct forstandard higher (lnaxilnuln) input oil nozzleinstalled in the burner. If the lower (lninilnuln)input is desired, readjust turbulator setting toindex mark specified in Table 7.

b. Loosen NUT (1), and then turn SCREW (2) untilthe INDEX MARKER (3) is aligned with thecorrect index number in the Burner Setup chart(Table 7).

c. Retighten the RETAINING NUT (1).

MODEL F3 NOTE: Zero and three are scale

indicators only. From left to right the first line is3 and the last line 0.

Pump Connections and Port Identification, Referto Figure 27.

This burner is shipped with the oil pump set tooperate on a single line system. To operate on atwo-fine system the bypass plug must be installed.

WARNING: Do not operate a single line systemwith the by-pass plug installed. Operating a singleline system with the by-pass plug installed willresult in damage to the pump shaft seal.

NOTE: Pump pressure was factory pre-set but mustbe checked at time of burner start-up. A pressuregauge is attached to the PRESSURE/BLEEDERPORT (7) for pressure readings. Two PIPE

Table 7: Riello Burner Specifications

BoilerModel

AP-490U

AP-590U

AP-690U

AP-790U

FiringRate

(GPH)

0.75

1.00

1.10

1.35

BurnerModel

40F3

40F5

Nozzle

(Delavan)

0.65 - 60W

0.85 - 80B

0.90 - 80B

1.10 - 80B

Air Gate

Setting

2.75

3

3.5

Turbulator

Setting

1

0

2

PumpPressure

(PSIG)

145

Combus-tion Head

VSBT

Insertion

Depth

1%

28

Page 29: INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS AP ... · STEEL OIL-FIRED BOILER For service or repairs to boiler, call your heating contractor. When seeking information on boiler,

PUMP LEGEND

t. PUMP COVER2. PUMP COVER O-RING3. BSPP TO NPT ADAPTERS

4, SUPPLY AND RETURN OiL LINES5. RETURN PORT BY PASS SCREW

6, NOZZLE PORT - PUMP OULET TO NOZZLE7, PUMP PRESSURE PORT AND BLEEDER PORT8, PUMP SUPPLY PORT9. PUMP RETURN PORT

10. PUMP PRESSURE REGULATING SCREWtt, VACUUM PORTI2. PUMP VALVE STEM

Figure 27: Pump Connections and Port Identification

8.

CONNECTORS (4) are supplied with the burnerfor connection to either a single or two-line system.Also supplied are two ADAPTORS (3), two female¼" NPT to adapt oil lines to burner pipe connectors.All pump port threads are British Parallel Threaddesign. Direct connection of NPT threads to thepump will damage the pump body.

Riello manometers and vacuum gauges do notrequire any adapters, and can be safely connected tothe pump ports. An NPT x metric adapter must beused when connecting other gauge models.

Replace Burner Cover and Tighten Burner CoverScrews.

N. VERIFY OIL BURNER SETT1NGS BEFORESTARTING

1. Check burner AIR DAMPER (GATE) and

TURBULATOR settings per Table 7, readjust if

necessary.

2. OPEN ALL OIL LINE VALVES.

3. Provide a pan to catch oil.

4. Remove pressure port/bleeder plug from fuel pumpand install Riello Combination Pressure Gauge andBleeder "CalveAssembly.

5. OPEN FLAME OBSERVATION PORT COVER on

burner swing door.

O° START OIL BURNER

1. Open bleeder valve (vent fitting) on RielloCombination Pressure Gauge and Bleeder "CalveAssembly.

2. TURN 'ON' BURNER service switch and allow

burner to run until oil flows from vent fitting in aSOLID stream without air bubbles for

approximately 10 seconds.

3. Close vent fitting and burner flame should startilnlnediately.

P. ADJUST OIL PRESSURE

1. Locate oil pressure adjusting screw and turn screwto obtain proper pump pressure, refer to Table 7.

Qo ADJUST OIL BURNER WHILE OPERATING (flame

present)1. ADJUST DRAFT REGULATOR for a draft of-

0.02" (water gauge) over the fire after chilnney hasreached operating temperature and while burner isrunning.

2. READJUST THE AIR DAMPER SETTING on the

burner for a light orange colored flame while thedraft over the fire is -0.02". Use a smoke tester and

adjust air for lninilnuln smoke (not to exceed #1)with a lninilnuln of excess air. Make final check

using suitable instrumentation to obtain a CO 2of11.5 to 12.5% with draft of-0.02" (water gauge) infire box. These settings will assure a safe andefficient operating condition. If the flame appearsstringy instead of a solid fire, try another nozzle ofthe same type. Flame should be solid and compact.After all adjustlnents are made recheck for a draft of-0.02" over the fire.

3. READJUST THE TURBULATOR SETTING onlyif necessary.

a. AP-490U throughAP-790U

Move the turbulator setting forward or back one

position at a time to optimize the smoke and CO2readings.

4. Turn "OFF" burner and remove Riello Combination

Pressure Gauge and Bleeder "CalveAssembly.Install pressure port/bleeder plug and tighten. Startburner again.

R. FLAME FAILURE

Do not attempt to start the burner when excess oilhas accumulated, when the unit is full of vapor, orwhen the combustion chamber is very hot.

The AP-U boiler controls operate the burnerautomatically. If for unknown reasons the burnerceases to fire and the rest button on the primary controlhas tripped, the burner has experienced ignition failure.

29

Page 30: INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS AP ... · STEEL OIL-FIRED BOILER For service or repairs to boiler, call your heating contractor. When seeking information on boiler,

So

To

30

Before pressing the rest button, call your servicemanimmediately.

CHECK FOR CLEAN CUT OFF OF BURNER

1. AIR IN THE OIL LINE between fuel unit and

nozzle will compress when burner is on and willexpand when burner stops, causing oil to squirt fromnozzle at low pressure as burner slows down andcausing nozzle to drip after burner stops. Usuallycycling the burner operation about 5 to 10 times willrid oil line of this air.

2. IF NOZZLE CONTINUES TO DRIR repeat stepN. 1. If this does not stop the dripping, remove cutoff valve and seat, and wipe both with a clean clothuntil clean. Then replace and readjust oil pressure.If dripping or after burn persist replace fuel pump.

HINTS ON COMBUSTION

1. NOZZLES-- Although the nozzle is a relativelyinexpensive device, its function is critical to thesuccessful operation of the oil burner. The selectionof the nozzle supplied with the AP-U boiler is theresult of extensive testing to obtain the best flameshape and efficient combustion. Other brands of thesame spray angle and spray pattern may be used but

may not perform at the expected level of CO2 andsmoke. Nozzles are delicate and should protectedfrom dirt and abuse. Nozzles are mass produced andcan vary from sample to sample. For all of thosereasons a spare nozzle is a desirable item for aserviceman to carry.

2. FLAME SHAPE -- Looking into the combustionchamber through the flame plug hole, the flameshould appear straight with no sparklers rolling uptoward the top of the chamber. If the flame drags tothe right or left, sends sparklers upward or makeswet spots on the combustion chamber, the nozzleshould be replaced. If the condition persists look forfuel leaks, air leaks, water or dirt in the fuel as

described in following steps.

3. FUEL LEAKS--Any fuel leak between the pumpand the nozzle will be detrimental to goodcombustion results. Look for wet surfaces in the air

tube, under the ignitor, and around the air inlet. Anysuch leaks should be repaired as they may causeerratic burning of the fuel and in the extreme casemay become a fire hazard.

4. AIR LEAKS-- Any such leaks should be repaired,as they may cause erratic burning of the fuel and inextreme cases may become a fire hazard.

There may be many possible causes of leaks in oil linessuch as:

a. Fitting leaks due to misflared tubing or damagedfitting.

b. Fuel line leak due to crushed or bent tubing.

c. Filter connection leaks.

d. Tank connection leaks.

The following actions can eliminate air leaks:

a. Bleed pump as detailed in System Start-UpSection of this manual.

b. Replace flare fittings.

c. Replace oil supply line.

d. Repair oil filter leaks

e. Replace or repair tank fittings.

5. GASKET LEAKS-- If 11.5% to 12.5% CO2 with a#1 smoke cannot be obtained in stack, look for airleaks around the canopy seal. Such air leaks will

cause a lower CO 2 reading in the stack. The smallerthe firing rate the greater effect an air leak can have

on CO 2readings.

6. DIRT-- A fuel filter is a good investment.Accidental accumulation of dirt in the fuel systemcan clog the nozzle strainer and produce a poorspray pattern from the nozzle.

7. WATER-- Water in the fuel, in large amounts, willstall the fuel pump. Water in the fuel pump, insmaller amounts, will cause excessive wear on the

pump, but more importantly water does not burn. Itchills the flame, causes smoke, and allows unburned

fuel to pass through the combustion chamber andclog the flueways of the boiler.

CHECK TEST PROCEDURE. A very good test forisolating fuel side problems is to disconnect thefuel system and with a 24" length of tubing, fireout of an auxiliary five gallon pail of clean, fresh,warm #2 oil from another source. If the burner runssuccessfully when drawing out of the auxiliarypail then the problem is isolated to the fuel or fuellines being used on the jobsite.

8. COLD OIL-- If the oil temperature approaching thefuel pump is 40°F or lower, poor combustion ordelayed ignition may result. Cold oil is harder toatomize at the nozzle. Thus, the spray droplets getlarger and the flame shape gets longer. An outsidefuel tank that is above grade or has fuel lines buriedin the ground above the frost line is a good candi-date for cold oil. The best solution is to place thetank and oil lines in the ground below the frost line.

9. HIGH ALTITUDE INSTALLATIONS

10.

Typically, the rule to use for high altitudes is toincrease the air supply by 4% per each 1000 ft.above 2000 ft. altitude from sea level. This means

that the air setting will have to be higher than thecalibration marks in proportion to the altitude. Use

instruments and set for 11.5 to 12.5% CO2.

START-UP NOISE -- Late ignition is the cause ofstart-up noises. If it occurs recheck for electrodesettings, flame shape, air or water in the fuel lines.

Page 31: INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS AP ... · STEEL OIL-FIRED BOILER For service or repairs to boiler, call your heating contractor. When seeking information on boiler,

11. SHUT DOWN NOISE -- If the flame runs out of

air before it runs out of fuel, an after burn with

noise may occur. That may be the result of a faultycut-offvalve in the fuel pump, or it may be airtrapped in the nozzle line. It may take several firingcycles for that air to be fully vented through thenozzle. Water in the fuel or poor flame shape canalso cause shut down noises.

U. TEST CONTROLS

Before installation of the boiler is consideredcomplete, the operation of all boiler controls mustbe checked, particularly the primary control andhigh limit control.

2.

CHECK THERMOSTAT OPERATION. Raise and

lower thermostat setting as required to start and stopburner.

VERIFY PRIMARY CONTROL SAFETY

FEATURES using procedures outlined inInstructions furnished with control (See back ofControl Cover) or Instructions as follows:

Service of this boiler should be undertaken onlyby trained and skilled personnel from a qualifiedservice agency.

a. Simulate flame failure:

• Follow the starting procedure to turn on theburner.

b.

• Close the hand valve in the oil supply line.

• Control enters recycle mode and tries torestart burner after approximately 60seconds.

Safety switch should lock out in approximately15 seconds. Ignition and motor should stop andoil valve should open to stop oil flow.

• Indicator light will flash 1/2second on,1/2second off.

• Push red reset button to reset safety switch.

Simulate ignition failure:

• Follow the starting procedure to turn on theburner, but do not open the oil supply handvalve.

Safety switch should lock out in approximately15 seconds. Ignition and motor should stop andoil valve should open to stop oil flow.

3.

go Boiler

• Indicator light will flash 1/2second on,1/2second off.

• Push red reset button to reset safety switch.

c. Simulate power failure:

• Follow the starting procedure to turn on theburner.

• With the burner running, turn off the powerto the system by tripping the circuit breakeror removing the fuse.

• Burner should stop.

• Restore power. Burner should start.

* The CleanCut Oil Pump's Solenoid "Calveis abypass valve, not a blocking valve.

VERIFY HIGH LIMIT OPERATION.

a. Adjust thermostat to highest setting.

b. Observe temperature gauge. When telnperamreis indicated, adjust limit to setting belowobserved temperature. Burner should stop.

c. Adjust limit to setting above observedtemperature. Burner should start.

d. Adjust thermostat to lowest setting. Adjust limitto desired setting.

is now ready to be put into service.

IF, DURING NORMAL OPERATION, IT ISNECESSARY TO ADD WATER MORE FREQUENTLYTHAN ONCE A MONTH, CONSULT A QUALIFIEDSERVICE TECHNICIAN TO CHECK YOURSYSTEM FOR LEAKS.

A leaky system will increase the volume of make-upwater supplied to the boiler which can significantlyshorten the life of the boiler. Entrained in make-upwater are dissolved minerals and oxygen. When thefresh, cool make-up water is heated in the boiler theminerals fall out as sediment and the oxygen escapesas a gas. Both can result in reduced boiler life. Theaccumulation of sediment can eventually isolate thewater from contacting the steel. When this happensthe steel in that area gets extremely hot and eventuallycracks. The presence of free oxygen in the boiler createsa corrosive atmosphere which, if the concentrationbecomes high enough, can corrode the steel throughfrom the inside. Since neither of these failure types arethe result of a manufacturing defect the warranty doesnot apply. Clearly it is in everyone's best interest toprevent this type of failure. The maintenance of systemintegrity is the best method to achieve this.

31

Page 32: INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS AP ... · STEEL OIL-FIRED BOILER For service or repairs to boiler, call your heating contractor. When seeking information on boiler,

Advances in the new Series 5 Beckett R7184B 1032 Oil Primary Controls found on New Yorker AP-U boilers are bringing new

features to Oil-Fired AP-U's.

New Beckett Series 5 Control Features Include:

• EnviraCOM TM connnunication terminals and logic have been added for furore HVAC system networking.

• Quick connect terminals on the control allow quick component change out and reduce the number ofleads in the wiring box.

See below for location of Beckett R7184B 1032 Series 5 Control features:

_ESE _ BUWON

NOTE:

T TER_,AiNAL$

Figure 28: Beckett R7184B1032, Series 5 Control

The use of EnviraCOM TM terminals is not required for control operation.

32

Page 33: INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS AP ... · STEEL OIL-FIRED BOILER For service or repairs to boiler, call your heating contractor. When seeking information on boiler,

VIII. Service and Cleaning

BURNER SHUTDOWN: Open Service Switchto turn off burner.

Manual Oil Supply Valve should be closed andElectric Service to boiler turned off if boiler

will not be operated for an extended periodof time.

A. GENERAL. Inspection service and cleaning should

be conducted annually. Turn off electric power andclose oil supply valve while conducting service ormaintenance.

B. FIRETUBES AND COMBUSTION CHAMBER. (See

Figure 29)

1. CLEAN THE FIRETUBES

a. Disconnect electric to burner and remove stack.

b. For access to the firembes, pull top jacket paneloff. Remove brass nuts, that hold canopy down.Without taking off carriage bolts, pull canopyoff.

c. Remove turbulators.

d. Using a firetube brush clean firetubes. DO NOTextend brush past the end of the bottomtubesheet.

e. Assemble the boiler in reverse order.

Units should be cleaned at least once a year, preferablyat the end of each heating season.

It is not necessary to remove burner to clean boiler.

Brush, scrape, or vacuum from top.

NOTE: UNITS SHOULD BE C_NED ATLF_AST ONCE A YE/_R, PREFER_LYAT THE END OF EACH HEATING

SEASON.

iS NOT NECESSARY TO REMOVE

BURNER TO CLEAN BOILER.

BRUSH, SCRAPE OR VACUUMCLEAN FLUE TUBES CAREFULLYFROM TOP WITHOUT EXTENDINGCLONING TOOLS BEYONDBOTTOM OF FLUE TUBE TOPREVENT DAMAGE TO COMBUSTIONCHAMBER,

COMBUSTION C_B_

tS A LIGHTWEIGHT CERAMIC TYPE,

EXTEND CLEANINGTOOK BEYOND BOTTOM OFFLUE TUBES TO PRINTDAMAGE TO COMBUSTIONCH_BER.

BOILER MODEL_-490U & _-590U

AP-BgOU & AP-790U

II

STEP 1

DISCONNECT _DTRICAL POWER

TO O{L BURN_

STEP 2

REMOVE STACK

STEP 3

REMOVE J_K_ TOP PANEL

STEP 4-

REMOVE BRA_ HEX NUTS

ND WASHERS

STEP 5REMOVECANOPY

s_P 6REMO'v_ TURBULATORS

STEP 7

R_RBE PR_EDURE

TO ASSEMBLE

EXTEND _UE

BRUSH BEYOND THIS

POINT

COMBUSTION CHAMB_

CLEANING INSTRUCTIONS

Figure 29: Cleaning of AP-U Boiler33

Page 34: INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS AP ... · STEEL OIL-FIRED BOILER For service or repairs to boiler, call your heating contractor. When seeking information on boiler,

Warninq:

The Repair Parts list designates parts that contain refractory ceramic fibers(RCF). RCF has been classified as a possible human carcinogen. Whenexposed to temperatures about 1805°F, such as during direct flame contact,RCF changes into crystalline silica, a known carcinogen. When disturbed as aresult of servicing or repair, these substances become airborne and, if inhaled,may be hazardous to your health.

AVOID Breathinq Fiber Particulates and Dust

Precautionary Measures:

Do not remove or replace RCF parts or attempt any service or repair workinvolving RCF without wearing the following protective gear:

1. A National Institute for Occupational Safety and Health (NIOSH)approved respirator

2. Long sleeved, loose fitting clothing

3. Gloves

4. Eye Protection

• Take steps to assure adequate ventilation.

• Wash all exposed body areas gently with soap and water after contact.

• Wash work clothes separately from other laundry and rinse washingmachine after use to avoid contaminating other clothes.

• Discard used RCF components by sealing in an airtight plastic bag. RCFand crystalline silica are not classified as hazardous wastes in the UnitedStates and Canada.

First Aid Procedures:

• If contact with eyes: Flush with water for at least 15 minutes. Seekimmediate medical attention if irritation persists.

• If contact with skin: Wash affected area gently with soap and water.Seek immediate medical attention if irritation persists.

• If breathing difficulty develops: Leave the area and move to a locationwith clean fresh air. Seek immediate medical attention if breathingdifficulties persist.

• Ingestion: Do not induce vomiting. Drink plenty of water. Seekimmediate medical attention.

34

Page 35: INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS AP ... · STEEL OIL-FIRED BOILER For service or repairs to boiler, call your heating contractor. When seeking information on boiler,

IX. Repair Parts

All AP-U TM Repair Parts may be obtained through your local New Yorker Wholesale distribu-

tor. Should you require assistance in locating a New Yorker distributor in your area, or have

questions regarding the availability of New Yorker products or repair parts, please contact New

Yorker Boiler Co., Inc. Customer Service at (215) 855-8055 or Fax (215) 855-8229.

AP-U Series Boiler Repair Parts

ITEM DESCRIPTION

1 Jacket Top Panel Assembly

2 Jacket Lower Front Panel Assembly

3 Jacket Upper Front Panel Assembly - 490U / 590U

Jacket Upper Front Panel Assembly - 690U / 790U

4 Jacket WAR Panel Assembly - 490U / 590U

Jacket WAR Panel Assembly - 690U / 790U

5 Temperature / Pressure Gauge

6 Honeywell L7248A1000 Aquastat

Honeywell L7224A1008 Aquastat

7 Observation Port Cover

Observation Cover Spring V1

Flat Washer, SAE, 5/16"

Hex Nut, 5/16 -18, Heavy

8 Burner Primary Control, R7184B

PART NUMBER QTY.

6047104 1

60471042 1

60471041 1

60471061 1

60471043 1

60417063 1

100282-01 1

100879-01 1

100862-01 1

7026001 1

8026015 1

80860647 1

80860402 1

80160847 1

Figure 30: AP-U Boiler Jacket Parts and Controls35

Page 36: INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS AP ... · STEEL OIL-FIRED BOILER For service or repairs to boiler, call your heating contractor. When seeking information on boiler,

NOTE: When ordering parts always give the serial number and model number shown on the boiler. Also provide the name ofthe part(s) shown below:

36

Figure 31: AP-490U thru 790U Bare Boiler Repair Parts

Page 37: INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS AP ... · STEEL OIL-FIRED BOILER For service or repairs to boiler, call your heating contractor. When seeking information on boiler,

AP-USeries Boiler Repair Parts (continued)

ITEMDESCRIPTION QTY.

NO.

9 2

10 10

11 2

12 2

13 1

14 1

15 1

16 _A _

Hex Nut, 1/4 - 20, Brass

Flat Washer, SAE 1/4

C-bolt, 1/4 - 20 x 3

1/4" Threaded Stud Push Retainer

Canopy Assembly

Fiberglass Tape Gasket 1/8 x 1 x 12-3/8"

Fiberglass Tape Gasket 1/8 x 1 x 13-3/8"

Turbulator, Short

Turbulator, Long

Shell Assembly

Hex Lock Nut 1/4 - 20

Machine Screw 1/4 - 20 x 1-1/4"

Base Assembly

Combustion Chamber

Base Front Insulation

Cerafelt, 1/2" Thick x 2" x 18-1/2"

Cerafelt, 1/2" Thick x 2" x 13-3/4"

S-4 Heater Coil Assembly

S-5 Heater Coil Assembly

Blanket Heater Cover Plate

Gasket, Blanket Heater Cover Plate

SA-307B 3/8 x 1-1/4" Hex Head Bolt

Heavy Hex Nut, 3/8 - 16

Flat Washer USS, 3/8"

PART NO.

80860119

80860424

80860847

80861725

6113509

9206032

9206032

7116037

7116038

See Table Below

80860456

80860810

61835062

8203006

8203512

9206003

9206003

6037201

6037202

7033715

8206036

80861360

80860400

80860645

17 'B'18 4

19 4

2O 1

21 1

22 1

23 1

24 1

125

1

26 1

27 1

28 10

29 10

30 10

BOILER MODEL

AP-490U

AP-590U

AP-690U

AP-790U

'A'12

16

12

16

_B _

63071100

63071101

63071102

63071103

37

Page 38: INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS AP ... · STEEL OIL-FIRED BOILER For service or repairs to boiler, call your heating contractor. When seeking information on boiler,

X. Beckett AFG Burner Parts for AP-U Series Boilers

NOTE:

FOR REPLACEMENT OIL BURNER PARTS, CONTACT YOUR WHOLESALER OR THE BURNERMANUFACTURER:

R. W. BECKETT CORE

R O. BOX 1289

ELYRIA, OHIO 440361-800-645-2876

When ordering parts always give the serial and model numbers shown on the boiler and burner. Also, provide thename of the part(s) and part(s) number as listed below.

Boiler Model AP-490U AP-590U AP-690U AP-790U

Burner Model AFG AFG AFG AFG

Air Tube Combination AF40WR AF40BZ AF40WB AF40BZ

Spec. No. NY2101 NY2103 NY2105 NY2108

AFG Housing 5874BK 5874BK 5874BK 5874BK

Air Band 3492BKA 3492BKA 3492BKA 3492BKA

Air Band Nut 4150 4150 4150 4150

Air Band Screw 4198 4198 4198 4198

Air Shutter 3709 3709 3709 3709

Air Shutter Screw 4198 4198 4198 4198

Blower Wheel 2999U 2999U 2999U 2999U

Bulkhead Fitting 571801 571801 571801 571801

Bulkhead Fitting Locknut 3666 3666 3666 3666

Connector Tube Assembly 5636 5636 5636 5636

Coupling 2454 2454 2454 2454

Electrode Clamp 149 149 149 149

Electrode Clam p Screw 4219 4219 4219 4219

Electrode Insulator Assembly 5780 5780 5780 5780

Spider Spacer Assembly 5653 5653 5653 5653

Escutcheon Plate 3493 3493 3493 3493

Flange and Air Tube Assembly 3146806 3146806 3146806 3146806

Gasket 3811 3811 3811 3811

Head 360003 360004 360004 360004

Head Screws 4221 4221 4221 4221

Hole Plug 2139 2139 2139 2139

Housing Assembly w!lnlet Bell 5877 5877 5877 5877

Motor 21805U 21805U 21805U 21805U

Nozzle Adapter 213U 213U 213U 213U

Nozzle Line Electrode Assembly NL40WR NL40BZ NL40WB NL40BZ

Pu mp 21844 21844 21844 21844

Static Plate 3898 31646 3898 31646

Ignitor 51771U 51771U 51771U 51771U

Ignitor Hinge Screw 4217 4217 4217 4217

Ignitor Holding Screw 4198 4198 4198 4198

Ignitor Gasket Kit 51304 51304 51304 51304

Wire Guard 3345 3345 3345 3345

Junction box 5770 5770 5770 5770

Flame Detector 7006Q 7006Q 7006Q 7006Q

Baffle 5880 .........

38

Page 39: INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS AP ... · STEEL OIL-FIRED BOILER For service or repairs to boiler, call your heating contractor. When seeking information on boiler,

Ordering Information for Quality Replacement Parts

_LY

TU_

SIDE

FOR R_ N_

VIEWFRONT VIEW

4X4_

NOZZLE DETAIL

Figure 32: BECKETT AFG MODEL BURNER

39

Page 40: INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS AP ... · STEEL OIL-FIRED BOILER For service or repairs to boiler, call your heating contractor. When seeking information on boiler,

XI. Riello Burner Parts for AP-U Series Boilers

NOTE: When ordering parts always give the serial and model numbers shown on the boiler and burner.

Refer to Models F3 & F5 Installation Manual, Riello 40 Series Residential Oil Burners (C6501010) for an exploded viewof the burner and a list of spare parts.

For replacement Riello oil burner parts, contact your wholesaler or the burner manufacturer:

Riello Corporation of Alnerica35 Pond Park Road

Hingham, Massachusetts 02043Telephone: (617) 749-8292Facsimile: (617) 740-2069

Toll Free: (outside Massachusetts)(800) 992-7637

Riello Canada Inc.

2165 Meadowpine Blvd.Mississauga, Ontario L5N 6H6

Telephone: (905) 542-0303

Facsimile: (905) 542-1525

Toll Free: (800) 387-3898

40

Page 41: INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS AP ... · STEEL OIL-FIRED BOILER For service or repairs to boiler, call your heating contractor. When seeking information on boiler,

XII. Low Water Cut Off (LWCO) on Hot Water Boilers

When

A low water cutoff is required to protect a hot waterboiler when any connected heat distributor (radiation)is installed below the top of the hot water boiler (i.e.baseboard on the same floor level as the boiler). Inaddition, some jurisdictions require the use of a LWCOwith a hot water boiler.

Where

The universal location for a LWCO on both gas and oilhot water boilers is above the boiler, in either the supplyor return piping. The lninilnuln safe water level of awater boiler is at the uppermost top of the boiler; that is,it must be full of water to operate safely.

What Kind

Typically, in residential applications, a probe typeLWCO is used instead of a float type, due to theirrelative costs and the simplicity of piping for a probeLWCO.

How to Pipe

A "tee" is commonly used to connect the probe LWCOto the supply or return piping, as shown below.

EYS_EM SU#_[ g

gg IJRN I

LWCO Location

Select the appropriate size tee using the LWCOmanufacturer's instructions. Often, the branch

connection must have a minimum diameter to

prevent bridging between the probe and the tee. Also,the run of the tee must have a lninilnuln diameter to

prevent the end of the probe from touching or beinglocated too close to the inside wall of the run of the tee.

Ideally, manual shutoff valves should be locatedabove the LWCO and the boiler to allow for servicing.This will allow probe removal for inspection without

draining the heating system. Many probe LWCOmanufacturers reco_ranend an annual inspection of theprobe.

How to Wire

LWCO's are available in either 120 VAC or 24 VAC

configurations. The 120 VAC configuration can beuniversally applied to both gas and oil boilers by wiringit in the line voltage service to the boiler (after theservice switch, if so equipped).The presence of water in a properly installed LWCOwill cause the normally open contact of the LWCO toclose, thus providing continuity of the 120 VAC serviceto the boiler.

It is recommended to supply power to the probe LWCOwith the same line voltage boiler service as shown

below. 'r,:_r<E

EiR 87

5V_ _CP

(}SI>T 0 _& )

2{/60

I:._ (: N::)

TO 80£(?A}

Wiring of Typical LWCO

A 24 VAC LWCO is used primarily for gasfiredboilers where a 24 volt control circuit exists within the

boiler. However, a 24 VAC LWCO can only be usedif the boiler manufacturer has provided piping andwiring connections and instructions to allow for thisapplication.

How to Test

Shut off fuel supply. Lower water level until waterlevel is BELOW the LWCO. Generate a boiler demand

by turning up thermostat. Boiler should not attempt tooperate. Increase the water level by filling the system.The boiler should attempt to operate once the waterlevel is above the LWCO.

41

Page 42: INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS AP ... · STEEL OIL-FIRED BOILER For service or repairs to boiler, call your heating contractor. When seeking information on boiler,

DATE

SERVICE RECORDSERVICE PERFORMED

42

Page 43: INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS AP ... · STEEL OIL-FIRED BOILER For service or repairs to boiler, call your heating contractor. When seeking information on boiler,

DATE

SERVICE RECORDSERVICE PERFORMED

43

Page 44: INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS AP ... · STEEL OIL-FIRED BOILER For service or repairs to boiler, call your heating contractor. When seeking information on boiler,

NEW YORKER BOILER CO., INC.

imite arrantiesFor Residential Cast hon mad Steel Water Boilers

By this Warranty Statement New" Yorker Boiler Co., Inc. ("New Yorker"),

issues limited warranties subject to the terms and conditions stated below.

These limited warranties apply to residential cast iron and steel water boilers

labeled with the New Yorker ® brand which are sold on or after March 1,2004.

ONE YE_,JI LIMITED WARRANTY

One Yeas Limited Warranty for Residential Water Boilers New" Yorker

warrants to the original consumer purchaser at the original installation addressthat its residential cast iron and steel water boilers will be free fi'om defects in

material and workmanship under normal usage for a period of one year fromthe date of original installation. In the event that any defect in material or

workmanship is found during the one year period lbllowing the date of

installmion, New" Yorker will, at its option, repair the defective part or provide

a replacement free of chm'ge, F.O.B. its factory.FIVE "tEAR LIMITED WARRANTY

Five Yea-Pressure Vessel Limited Warranty for WC TM Residential Water

Boilers New Yorker warrants to the original consumer purchaser at the

original installation address that the pressure vessel of the boiler will be free

of defects in material and workmanship under noruml usage for a period of

five years following the date of installation. In the event that any defect in

material or workmanship is found during the five year period following thedine of installation, New Yorker will, at its option, repair the defective

pressure vessel or provide a replacement free of charge, F.O.B. its factor),.LIFE TIME LBIITED WARRANTY

Lifetime Pressure Vessel Limited Warranty for AP-UTM_ FIR.TM, S-AP TM,

microTEK3 TM, microTEKDV TM, CLW TM, CG-A TM and PVCG TM Residential

Water Boilers New" Yorker warrants to the original consumer purchaser at the

original installation address that the pressure vessel component of the boiler

will be fl'ee of defects in material mid workmanship under normal usage for

the lifetime of the original consumer purchaser. In the event th_ any defect inmaterial or workmanship is found during the ten year period following the

date of installation, New Yorker will, at its option, repair the defective

pressure vessel or provide areplacement free of charge, F.O.B. its factory. In

the event that any defect in material or workmanship is found after the tenth

y ear following the date of installation, New Yorker will provide a rep lacem ent

pressure vessel upon payment by the original consumer purchaser of anamount equal to a percentage of the then current retail price of the model

boiler involved (or, in the event that such model is not then in production, the

most comparable model then in production), as follows:Ye_'s In

Service llth 12th 13fl_ 14th 15th 16th 17th 18thConsmner

Purshaser Pays 5% 1_:_ 15% 2_/o 25% 30% 35% 40%

Years In [ 19th [ 20th ] 21st [ 22nd [ 23rd ] 24th [ 25th I

Se<ceI , I0,. I , I Oy° I I0,0I beyond ioIConsumer o o o o o o o

Purchaser I I I I I I IPays

EXCEPTIONS AND EXCLUSIONS

1. Components Manufactured by Others Following the expiration of the

foregoing one year limited warranty, all component parts of a boiler which are

manufactured by others (such as burners, burner controls, circulato5 tanklesswater heater, and New Yorker Link) shall be subject only to the

mamfacturer's win'realty, if any.

2. Removal and Raplacement Costs These wm'ranties do not cover expenses

of removal or reinstallation. Tile consumer purchaser will be responsible for

the cost of removing and replacing any defective part and all labor and related

materials connected therewith. Raplacenlent pasts will be invoiced to the

distributor in the usual manner mid will be subject to adjustment upon proof ofdefect.

3. Proper Installation These warranties are conditioned upon the installation

of the boiler in strict compliance with New Yorker's Installmion, Operating

and Service Instructions. New" Yorker specifically disclaims any liability of

any kind which arises from or relates to improper installation.

4. Improper Use or Maintenance These w_rranties will not be applicable if

the boiler is used or operated over its rated capacity, is installed for uses other

than home heating, or is not maintained in accordance with New Yorker's

Installation, Operating and Service Instructions and hydronics industrystandards.

5. Improper Operation These warranties _ill not be applicable if the boiler

has been damaged as aresult of being improperly serviced or operated,

including but not limited to the following: operated with insufficient water,allowed to fi'eeze; subjected to flood conditions; or operated with water

conditions and/or fuels or additives which cause unusual deposits or con'osion

in or on the pressure vessel or associated controls.

6. Geographic Limitations These wmranties apply only to boilers installed

within the 48 contiguous United States.

7. In_allation Requirements In order for these warranties to be effective:

a, The boiler must be installed in a single or _,o-family residential

dwelling. Tiffs wan-anty does not apply to boilers installed in apartments or

for commercial or industrial applications.

b. The boiler must be installed in strict compliance with New Yorker's

Installation, Operating and Service Instructions by an installer regularlyengaged in boiler inNallations.

¢. Boiler sections must not have been damaged during shipment orinstallation,

d. The boiler must be vented in accordance with chimney

recommendations set forth in New Yorker's Installation, Operating andService Instructions.

8. Exclusive Remedy New Yorker's obligation in the event of any breach of

these warranties is expressly limited to the repair or replacement of any partfound to be defective under conditions of normal use.

9. Limitation of Damages Under no circumstances will New Yorker be liable

for incidental indirect, special or consequential damages of any kind under

these warranties, including, without limitation injury or damage to persons or

property and damages for loss of use inconvenience or loss of time. New

Yorker's liability under these warranties shall under no circumstances exceed

the purchase price paid for the boiler involved. Some states do not allow theexclusion or limitation of incidental or consequential damages, so the above

limitation or exclusion may not apply to you.

1 0. Limitation of Wmranty These limited warranties are given in lieu of allother express _arranties and set fo_h the entire obligation of New Yorker

with respect to any defect in aresidential water boiler. New Yorker shall haveno express obligations, responsibilities or liabilities of any kind, other thanthose set forth herein,

ALL APPLICABLE IMPLIED WARRANTIES, IF ANY, INCLUDINGANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A

PARTICUL,_aR PURPOSE, ,_E EXPRESSLY LIMITED IN

DURATION TO A PERIOD OF ONE YEAR, EXCEPT THAT

IMPLIED WARRANTIES, IF ANY, APPLICABLE TO THEPRESSURE VESSEL OF A RESIDENTIAL WATER BOILER

SHALL BE LIMITED IN DURATION TO THE LESSER OF THE

DURATION OF SUCH IMPLIED WARRANTY OR A PERIOD

EQUAL TO THE TERM OF THE APPLICABLE EXPRESSWARRANTY. Some states do not allow limitations on how long an

implied walranty lasts, so the above limitation may not apply to you.PROCEDURE FOR OBTAINING WARRANTY SERVICE

Upon discove W of a condition believed to be related to a defect in material

or workmanship covered by these warranties, the original consumer purchaser

should notify the installer, who will in turn notify the distributor, ffthis action

is not possible or does not produce a prompt response, the original consmner

purchaser should wTite to New Yorker Boiler Co., Inc, at P.O. Box 10,

Hatfield, PA 19440-0010, giving full particulars in support of the claim.The original consumer purchaser is required to make available for

inspection by New Yorker or its represent_ive the parts claimed to be

defective and, if requested by New Yorker, to ship those parts prepaid to New

Yorker at the above address for inspection or repair. In addition, the originalconsumer purchaser agrees to make all reasonable efforts to settle any

disagreement arising in connection with any warranty claim before resortingto legal remedies in the courts.THIS WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS AND YOU

MAY ALSO HAVE OTHER RIGHTS WHICH VARY FROM STATE TO

STATE.

RESIDEN_D_& HEATING BOI_RS

02/04


Recommended