Portland Installation & Operating Manual Trident Boilers: SF160, SF260, SF360 SAFETY NOTICE PLEASE READ THIS ENTIRE MANUAL BEFORE YOU INSTALL AND/OR USE YOUR NEW BOILER. FAILURE TO FOLLOW INSTRUCTIONS MAY RESULT IN PROPERTY DAMAGE, BODILY INJURY, OR EVEN DEATH. IF THIS HARMAN BOILER IS NOT PROPERLY INSTALLED, A HOUSE FIRE MAY RESULT. FOR YOUR SAFETY, FOLLOW INSTALLATION DIRECTIONS. CONTACT LOCAL BUILDING OR FIRE OFFICIALS ABOUT RESTRICTIONS AND INSTALLATION INSPECTION REQUIREMENTS IN YOUR AREA. CONTACT YOUR LOCAL AUTHORITY (SUCH AS MUNICIPAL BUILDING DEPARTMENT, FIRE DEPARTMENT, FIRE PREVENTION BUREAU, ETC.) TO DETERMINE THE NEED FOR A PERMIT. SAVE THESE INSTRUCTIONS R6 Manual #3-90-70742
Transcript
Page 1: Installation & Operating Manual Trident Boilers: … & Operating Manual Trident Boilers: SF160, SF260, SF360. SAFETY NOTICE. PLEASE READ THIS ENTIRE MANUAL BEFORE YOU INSTALL AND/OR

Portland

Installation & Operating Manual

Trident Boilers: SF160, SF260, SF360

SAFETY NOTICEPLEASE READ THIS ENTIRE MANUAL BEFORE YOU INSTALL AND/OR USE YOUR NEW BOILER. FAILURE TO FOLLOW INSTRUCTIONS MAY RESULT IN PROPERTY DAMAGE, BODILY INJURY, OR EVEN DEATH.

IF THIS HARMAN BOILER IS NOT PROPERLY INSTALLED, A HOUSE FIRE MAY RESULT. FOR YOUR SAFETY, FOLLOW INSTALLATION DIRECTIONS.

CONTACT LOCAL BUILDING OR FIRE OFFICIALS ABOUT RESTRICTIONS AND INSTALLATION INSPECTION REQUIREMENTS IN YOUR AREA.

CONTACT YOUR LOCAL AUTHORITY (SUCH AS MUNICIPAL BUILDING DEPARTMENT, FIRE DEPARTMENT, FIRE PREVENTION BUREAU, ETC.) TO DETERMINE THE NEED FOR A PERMIT.

SAVE THESE INSTRUCTIONS

R6

Manual #3-90-70742

Page 2: Installation & Operating Manual Trident Boilers: … & Operating Manual Trident Boilers: SF160, SF260, SF360. SAFETY NOTICE. PLEASE READ THIS ENTIRE MANUAL BEFORE YOU INSTALL AND/OR

Page 3: Installation & Operating Manual Trident Boilers: … & Operating Manual Trident Boilers: SF160, SF260, SF360. SAFETY NOTICE. PLEASE READ THIS ENTIRE MANUAL BEFORE YOU INSTALL AND/OR

Congratulations, Youhavejustpurchasedthefinestwood/coalboileravailable.HarmanTridentboilersareconstructedofhighqualitymaterialsandaremanufacturedbyahighlyskilledteamofassemblymen.Eachboilerisinspectedandpressuretestedforqualityassurance.

Thismanualisdesignedtoprovideallofthebasicinformationneededforasafeandproperinstallation.However,therearemanyskillsneededthatcannotbelearnedbyreadingthismanual.HarmanHomeHeatingrecommendsthattheinstallationbeperformedbyaplumbingandheatingexpert.

TheHarmanTridentBoilersaredesignedtooperatesafe,easyandautomatically.Youmayhowever,needtolearnafewbasicskillstomaintainafire.Especiallyifthisisyourfirstventureintosolidfuelburning.Ifyouhaveanyproblems,re-readtheseinstructions.Ifyoucannotresolvetheissue(s),ContactyourHarmandealer.

TABLE OF CONTENTSPackingList

Installation Aquastat Wiring Venting Plumbing

Operating Instructions Starting a Wood Fire Starting a Coal Fire Loading Fuel ShakingAshes

Safety Tips

Maintenance

Specifications

Warranty

Service Log

Service Parts

4

56778

1010111111

12

13

13

14

16

17

Page 4: Installation & Operating Manual Trident Boilers: … & Operating Manual Trident Boilers: SF160, SF260, SF360. SAFETY NOTICE. PLEASE READ THIS ENTIRE MANUAL BEFORE YOU INSTALL AND/OR

PackingList

Itemsneededforassemblyandinstallation.PleasenotifyyourHarmanDealerifyouaremissinganyitems.

Included with Boiler:--ShakerHandle--AshPan--WarrantyRegistrationForm

Items In Boiler Kit # 1-00-01020: (Sold Separately)--JohnsonControlsAquastat-(3)pieces;A350Controllerw/Sensorwire S350 Stage Module Y350PowerSupply--ImmersionWell--DinRailand(2)EndClamps--TerminalBox--TerminalBlockand(2)#8-32nuts--PressureReliefValve(30psi.)--Temperature/PressureGauge--AutomaticDraftControlAssembly--(1pc.)FlexConduitw/(2)90°Fittingsw/nuts,and(3)ChaseNipplesw/nuts--(2)ManualDraftControlKnobAssembly--(3)BrassCoilSpringHandle

Notice:The Aquastat controls supplied with the Boiler Kit are designed only to maintain water temperature within

the boiler. The actual heating system is controlled separately by your

thermostat(s) opening zone valves or energizing circulation pump(s).

Do not attach a thermostat to the supplied controls. Note: This appliance is also approved for

installation into a shop.

Appliance Certification.Model:TridentSeriesBoiler-SF160,SF260,& SF360.Test Lab:Omni-TestLaboratories,Inc.Report #: 135-S-05-4Type: Solid Fuel (Wood, Coal) Fired Appliance for Residential UseStandard(s):CAN/CSAB366.1-M87,and applicablesectionsofUL834and ETLM 78.1

Page 5: Installation & Operating Manual Trident Boilers: … & Operating Manual Trident Boilers: SF160, SF260, SF360. SAFETY NOTICE. PLEASE READ THIS ENTIRE MANUAL BEFORE YOU INSTALL AND/OR

InstallationGetting Started Thesheetmetalsidesandtopareeasilyremovedtoreducethechanceofdentsand/orscratchesinthefinish.Simplyliftthetopoff,andthatwillallowthesidestobepulledawayandup,forremoval.Tore-install,slidethechannel,atthebottomofeachsidepiece,overthelipatthebot-tomoftheboiler,andholddownwardwhilemov-ing the side panel into place. Then slide the top downoverthesides.

NOTE:Thesheetmetaltopholdsthesidesinplace,thus,noboltsorscrewsareneeded.

Caution: Boiler should not Be installed Closer than 36 inChes (915 mm) to any ComBustiBle ma-terial

Locating Boiler Placetheboilerasclosetothechimneyaspossible,whilestillmaintainingtheabovemen-tionedclearances.Bolttheshakerhandleontotheblockonthesideoftheboiler,usingthe(2)5/16X3/4in.boltsandlock-washers.Assembly InstalltheTemperature/PressureGaugeintothepipestubinthecenteroftheroundplateonthefrontoftheboiler(FIG.1) InstalltheA350sensorwireallthewayintotheimmersionwellandscrewthewellintooneofthetopholesonthefaceoftheboiler. Turnthepressurereliefvalveintothestubontopoftheboiler,nexttothesupplyoutletfit-ting.NOTE: Use teflon tape to seal the threads on all fittings. Any unused fittings must be plugged. Boltthetwomanualdraftcontrolsthrough the holes in the top load door. (FIG.2) Thedraftcontrolknobshouldspinfreelyandopentoadistanceofapproximately3/8in.fromthedoorsurface,whilebeingabletocloseagainstthe door surface.

FIG.�

�/8to1/�in.

ImmersionWell

Temp/PressureGauge

OptionalElectricBack-upElements

AutomaticDraftControl

PressureReliefValve

FIG.1

JohnsonControlsAquastatand

TerminalBlock

ShakerHandle

DomesticHotWaterCoilOption

Page 6: Installation & Operating Manual Trident Boilers: … & Operating Manual Trident Boilers: SF160, SF260, SF360. SAFETY NOTICE. PLEASE READ THIS ENTIRE MANUAL BEFORE YOU INSTALL AND/OR

BolttheAutomaticDraftControlthroughthe1/2in.holeinthecenterofthebottomdoor.BesuretoholdtheDraftControlstraightwhiletightening.Feedthetwowiresfromthedraftmo-torthroughtheflexibleconduitanda90˚fitting.Securethefittingtothedraftmotorandthatendoftheconduitatthistime.ChecktheflapperdoorontheAutomaticDraftControlassuringthatitmovesfreely. Installthe(3)brasscoilspringhandlesontothedoorlatchesandtheshakerhandle.Startthespringhandleontotheshaftandtwistitcoun-ter-clockwisewhilepushing.

Aquastat Installation (See optional items, page 7) Lay the din rail onaflatsurface,withtheflatsidedown.Secureoneendclamp,ontheleftside.SlidetheA350controllerontotherailfromrighttoleftuntilitisagainsttheendclamp.SlidetheY350ontotherailandguidetheplug-inconnector,joiningittothe A350. Next, install the S350, again, guiding theplug-inconnectorcarefully.Installtheotherendclamptotherightsideofthedinrail.Removethecoversfromallthreecontrolsbylooseningfourscrewseach.Installtheterminalboxtothecontrolsusing(3)chasenipplesandlocknuts,suppliedwiththekit.Usingthefourholesintheterminalbox,mounttheterminalboxandcontrolstotheboilersheetmetalsideasshowninFig.1.Using(2)#8-32nuts,installtheterminalblockontothestudslocatedinsidetheterminalbox.

Wiring Diagram

Installation

FIG.�

Page 7: Installation & Operating Manual Trident Boilers: … & Operating Manual Trident Boilers: SF160, SF260, SF360. SAFETY NOTICE. PLEASE READ THIS ENTIRE MANUAL BEFORE YOU INSTALL AND/OR

Wiring and Electrical Followingthewiringdiagram,runallwirestotheirdesignatedconnections.Savethemainpowerforthelasthook-up,andleavethebreakerintheoffposition.ThesensorwiresattachtotheA350Controllerontheterminalsmarked“sen”and“com”.Makesurethesensorissubmergedfullyintothewellandsecuredwiththeset-screws.Setting The Aquastat InsidetheA350control,youwillseeasquarejumper,andadifferentialdial.Besurethejumperisinthe“Heating”position.Thedifferen-tialdialissettodeterminehowlow,belowthetemperaturesetpoint,youwantthewatertem-peraturetogobeforetheAutomaticDraftControlopens.Agoodinitialsettingforthisdialis5°.Besurethe120Vwiresareattachedtothecommonandthenormallyopenterminals,andreplacethecover.Theexternaldialissetforthewatertem-peratureyouwishtomaintain,agoodsettingis180°. Inside the Y350 control, ensure that your wiresareconnectedtothe120VACterminals,and replace the cover. InsidetheS350control,whichisusedasoverheatprotection,you’llseetwodials;offset,anddifferential.Thereisalsoajumperwhich,inthiscase,getsplacedinthe“cooling”position.TheoffsetdialsetsthenumberofdegreesabovetheA350setpointthatyouwanttheoverheatdumptoactivate.Agoodsetpointwouldbe20°.Thatwouldmeanthatifthewaterreaches200°,usingtheA350setpointof180°,theS350wouldclose it’s contacts and energize the overheat dumpzone.Thedifferentialdialsetsthepointthattheoverheatdumpwouldstop.Withthedifferen-tialsetat15°,usingthetemperaturesabove,thecircuitwouldre-open,stoppingtheoverheatdumpatawatertemperatureof185°.The120Vwiringisattachedonthenormallyopenandthecommonposition.Thenormallyclosedpositionisnotused. Re-installthecoversontothethreeCon-trols.

Optional Items Thereisadomestichotwatercoilavailablefor your Trident Boiler. The coil installs in the front oftheboiler,andallowsyourdomesticwatertobeheatedbytheheatingsystemwater.Installthecoilnow,byremovingtheroundplateandreplac-ingitwiththecoilandit’sroundplate.Besuretotightentheboltsevenly,toensureagoodseal. Ifelectricback-upisdesired,installnow.Therewillbetwoadditionalcontrolboxestoaddtoyouraquastat,whichwillrequiretheuseofalongerdinrail.ThetwoheatingelementswillinstallintothefrontoftheboilerasshowninFig.1

FIG.�

Venting TheHarmanTridentBoilermustbein-stalledintoachimneyapprovedforsolidfuelburningappliances.IntheU.S.,theboilermustbeconnectedto;(1)aprefabricatedchimneycomply-ingwiththerequirementsforTypeHTchimneysintheStandardforChimneys,FactoryBuilt,Resi-dential Type and Building Heating Appliances, UL 103.Or;(2)acodeapprovedmasonrychimneywithaflueliner.InCanada,withprefabricatedchimneysystemstestedandlistedtotheHighTemperatureChimneyStandardULCS-629,orwithacodeapprovedmasonrychimney.Theminimumrecommendedheightforanychimneyis16ft.(4.8m)abovethefluecollar.Donotre-ducefluediameter.Nominalsizeflueis8X8in.or equivalent, up to 8 X 12 in. Codes also require thatthechimneymustextendaminimumof

Installation

Page 8: Installation & Operating Manual Trident Boilers: … & Operating Manual Trident Boilers: SF160, SF260, SF360. SAFETY NOTICE. PLEASE READ THIS ENTIRE MANUAL BEFORE YOU INSTALL AND/OR

8

3feet(0.9m)abovethepointatwhichtheyexitfromtheroof,itmustalsoextend2feet(0.6m)abovethehighestpointwithina10ft.(3m)radius.

DO NOT CONNECT ThIS uNIT TO A ChIMNEy fLuE ThAT IS SERVING ANOThER AppLIANCE.

Limitconnectorpipeto8ft.orless,withnomorethantwoelbows.Allhorizontalsectionsshouldhave1/4in.riseperfoot.Thechimneymustbecapableofprovidingadraftreadingofatleast.06in.ofwatercolumn.Abarometricdampercanbeinstalledtopreventexcessiveanderraticdraft.Allconnectorpipeshouldbesecuredwithsheetmetalscrewsateachjoint.

Installationplumbing TheHarmanTridentBoilercanbeusedasa“StandAlone”boilerorasanadd-ontoanexist-inghotwaterheatingsystem. Thediagramsinthismanualaremeanttoshowthenecessaryequipmentandpiping.Yoursystemmaylookverydifferent.However,ifconfig-uredproperly,thesameresultswillbeachieved. Fig.6showsatypicalplumbingdiagramfortyingintoanexistingsystem.Thismethodprovideswatercirculationbetweenthetwoboilerswithacirculatingpump.Inthissetup,thedomes-ticwatercoilintheexistingboilerwillbeheated,makingitunnecessarytoinstallawatercoilintheTrident Boiler. Tying-intoanexistingboilermustbedoneinthereturnlinebetweenthecirculatorandtheexistingboiler.Runapipefromtheretoasmallcirculator,andthenintothe1-1/4in.fittingontherearoftheTridentBoiler.Nextrunapipefromthe1-1/4in.fittingonthetopoftheTridentBoilertoaTeefittinginthesupplylineoftheexistingboiler.ThisTeefittingmustbeinstalledbetweentheex-istingboilerandtheFlowControlValve,asshowninFig.6.Anairvalveshouldbeinstalledonthisline also.

FIG.�

FIG.�

AirValve

Notice:The Aquastat controls supplied with the Trident Boiler are designed only to maintain water temperature within

the boiler. The actual heating sys-tem is controlled separately by your

thermostat(s) opening zone valves or energizing circulation pump(s).

Do not attach a thermostat to the sup-plied controls.

Page 9: Installation & Operating Manual Trident Boilers: … & Operating Manual Trident Boilers: SF160, SF260, SF360. SAFETY NOTICE. PLEASE READ THIS ENTIRE MANUAL BEFORE YOU INSTALL AND/OR

Thecirculatorinstalledbetweenthetwoboilersmaybehookeduptoruncontinuouslyduringtheheatingseasonor,anadditionalS350control(notsupplied)couldbeinstalledtoturnitonandoffautomatically.Thiscontrolmustbeusedasa“closeonriseoftemperature”(jumperincoolingposi-tion). HarmanHomeHeatingrecommendsthat1-1/4in.pipebeusedbetweenthetwoboilers.AlsorecommendedisthatthefirstsectionofpipeoffofthetopoftheTridentBoilerbethreadedgalvanizedorthreadedblack-steelpipe. TheHarmanTridentBoilerissuppliedwithadualfunctionaquastat.TheA350isusedtocontroltheautomaticdraftcontrolwhetheropen,toincreaseheat,orclosed,todecreaseheat.TheS350isusedasoverheatprotection.Sinceawoodorcoalfireisstillproducingheatwhenthedraftisclosed,thisoverheatprotectionisrequired.YoucouldhavetheS350energizeacirculatingpumporazonevalveseparatefromtheheatingsystem,oritcouldbehookedupsothatitflowstheheatedwaterthroughoutthesystem.Eitherway,itmustbeabletoflowawayfromtheboiler. Figure7showsatypicalschematicoftheTridentboilerasa“standalone”system.Note;thecrossoverpipe(#12)isnottotallynecessarybutisrecommendedtoprovidecirculationwithintheboilerwhiletheheatingsystemissatisfied.Thiswillensureaneventemperaturewithintheboiler.Thetemperingvalveshown(#10)istopreventexcessivetemperatureofthedomesticwater.

FIG.�

Installation

Page 10: Installation & Operating Manual Trident Boilers: … & Operating Manual Trident Boilers: SF160, SF260, SF360. SAFETY NOTICE. PLEASE READ THIS ENTIRE MANUAL BEFORE YOU INSTALL AND/OR

10

OperationAutomatic Draft Control Theheatoutputisregulatedbytheauto-maticdraftcontrolonthebottomdoor.Theelectricmotor(A)opensandclosestheflapperdoor(B).Openingandclosingtheflapperdoorregulatestheairflowintothefirebox. Themaximumairflowcanbeadjustedbyturningtheadjustingbolt(C).Turncounter-clockwiseformoreair,andclockwiseforlessair.Adjustthisboltonlywhiletheflapperdoorisintheclosedposition.Otherwise,motordamagecouldoccur. Theidleairadjuster(D)controlsthemini-mumamountofairthatentersthefirebox.Adjust-mentismadebyturningtheadjusterverticalforzeroidleair,orhorizontalformaximumidleair.ItisbesttostartoutwithamediumsettingasshowninFigure9.

FIG.8

FIG.�

Starting a Wood fire Makesuretheboilerandallpipingisfullofwaterandthatallairhasbeenpurgedfromthesystem.Never start a fire without water in the system. An explosion will occur. Turnonelectricalpowertotheboiler.Thisshouldcausetheautomaticdraftcontroltoopen.Opentheashpandoortoallowfreeairmove-ment.Withthefireboxdooropen,crumbleap-proximately8sheetsofnewspaperandplaceonthegrates.Laysomesmallkindlingontopofthenewspaper.Besurethiskindlingisdryandnomorethan3/4in.indiameter.Layerthekindlinginacriss-crosstypepattern,toallowmaximumairflow.Nextlaysomelargerpiecesofwoodontopofthekindling(approximately2in.diameter).Usingamatchorlighter,lightthepaperjustinsidethedoor.Closeandlatchthefireboxdoorandal-lowthefiretoburnafewminutes.Afteraboutfiveminutes,closetheashpandoorandre-openthefireboxdooraninchortwo,toallowthesmoketoclear.Add4or5largerlogs(about4in.diameter)tothewellestablishedfireandclosethefireboxdoor.Leavetheashpandooropenforaboutfiveminutesonly.Nowopenthefireboxdoorusingthesamemethodasbefore,alwaysclosingtheashpandoorbeforeopeningthefireboxdoor.Nowyoucanloadthefireboxtothedesiredlevel.Youmayloadwoodtothetopofthefirebox.Closeandlatchthedoor.Theashpandoormayagainbeopenedtospeedtheignitionprocess.Do not leave the boiler unattended with any door open. Afterthewoodisburningwell,closetheashpandoor.Theautomaticdraftcontrolwillnowregulatethefire,basedontemperaturedemand. Theidleairadjustermustbetunedtowherethefiredoesn’tgooutduringlongperiodswithnodemand.Experiencewilldictatethebestsettingforyourinstallation.Normally,thetwomanualdraftcontrolsonthefireboxdoorarekeptclosedwhileburningwood.

Page 11: Installation & Operating Manual Trident Boilers: … & Operating Manual Trident Boilers: SF160, SF260, SF360. SAFETY NOTICE. PLEASE READ THIS ENTIRE MANUAL BEFORE YOU INSTALL AND/OR

11

OperationStarting a Coal fire Makesuretheboilerandallpipingisfullofwaterandthatallairhasbeenpurgedfromthesystem.Never start a fire without water in the system. An explosion will occur. Turnonelectricalpowertotheboiler.Thisshouldcausetheautomaticdraftcontroltoopen.Opentheashpandoortoallowfreeairmove-ment.Usethesameprocedureasstartingawoodfireexcept,donotloadthelargerdiameterwoodUsewoodabout2in.diametermaximum.Thissizewillformaveryhotcharcoalbedinlesstime.Again,theashpandoormaybeopenedperiodi-cally to speed the ignition process. DO NOT LEAVE ThE BOILER uNATTENDED WITh ANy DOOR OpEN. Whenyouhaveaccumulatedasubstantialcharcoalbed,startaddingathinlayerofcoal.PeaorNutsizedcoalisbetterforstartingthanStovecoal. Whenthefirstlayerisburningwithsomeblueflame,continuetoaddthinlayersofcoaluntilthereisasolidbedofburningcoal.Leteachlayerburnablueflamebeforeaddinganotherlayer.Ad-ditionalcoalcanbelayeredinuntilthebedisap-proximately10inchesdeep.Bynow,youshouldhavetheashpandoorclosed,andtheautomaticdraftcontrolwillcontinuetoregulatethefire. Theidleairadjustermayneedtobesetforslightlylessairforcoalthanwood.Hereagain,experiencewilldictatethebestsetting.Themaxi-mumairboltcanbeturnedalltheway“counter-clockwise”toallowforaquickerrecovery.Neveradjustthisboltwiththeflapperopen. Thetwomanualdraftcontrols,onthefireboxdoor,areusedtoallowsecondaryairtopassoverthefirewhenburningcoal.Thishelpstoburnthegassesthatareemittedfromthecoalas it is heated. Your setting for these draft controls shouldbebetween1/2and1completeturnfromclosed.Adjustbothcontrolsequally.

Loading Coalshouldneverbeaddedunlessthereisareasonablyhotfire.Thecoalbedshouldbebrightandvigorous.Ifyouhaveanactivecoalbed,fullloadscanbeaddedatanytime.Ifnot,addnewcoalinlayers,asdescribedinstartingacoalfire.Shaking the Grates Shakingshouldbedoneonlywhenthereisawell-establishedfire.Thefrequencyofshak-ingwilldependonthedegreeofburning.Twiceadayshakingisrecommended.Thebestresultsareachievedwithshort,choppystrokesasop-posedtolong,evenstrokes.Fullrockingofthegratesmayallowburningcoaltofallintotheashpan.Theamountofshakingiscritical,toomuchcandisruptthefirebed,andtoolittlewillrestrictair-flow.Theproperamountofshakingisnormallyachievedwhenhotredcoalsfirststarttodropthrough the grates into the ash pan. Everyeffortshouldbemadetonotletacoalfireburndowntoolow.Thiswillcausethereloadingprocesstobemuchlonger,witharealgoodchanceoflosingthefirealtogether. Donotshakeorstirwithalowfire.Opentheashpandoortogetmaximumairflowingintothefirebox.Onceburningisrestored,closetheashpandoorandaddalayerofcoaltothefirebed.FollowtheinstructionsunderStartingaCoalFire.Whenthenewcoalisthoroughlyignited,andthereisasubstantialbedofhotcoals,thegratesmaythenbeshaken.Ashes and Ash Removal Ashesshouldneverbeallowedtoaccu-mulateabovethetopoftheashpan.Ashesincontactwiththebottomofthegratesactasinsu-lation,whichintensifiestheheatonthegratesandcausesthemtosagorwarp.Also,toomuchashaccumulationwillrestrictair-flowwhichwillmakefiremaintenancemoredifficult.Placeashesinasealedmetalcontainer,outside,untiltheyarecooledenoughforfinaldisposal.Coalproducesconsiderablymoreashthanwood,sotheintervalsbetweenemptyingaremuchshorter.

Page 12: Installation & Operating Manual Trident Boilers: … & Operating Manual Trident Boilers: SF160, SF260, SF360. SAFETY NOTICE. PLEASE READ THIS ENTIRE MANUAL BEFORE YOU INSTALL AND/OR

1�

Safety Tips Whenopeningthefireboxdoor,itshouldbecracked,slightlyopen,forafewsecondstoallowairintoburnanygaseswhichmaybepresent.Thiswillalsoallowsmoketobedrawnawayfromthedoor.Whenevertheashpandoorisopen,itshouldbeclosedbeforeopeningthefireboxdoor.

Thefireboxshouldneverbefilledwithexcessivecoaltowheretheflueexitisblockedorimpededinanyway.

Burning coal produces Carbon Monoxide. If the flue exit is blocked, the Carbon Monoxide can be forced out of the boiler, into the room, with possible fATAL consequences. Withtheexceptionofstart-uporfresheningofthefire,orperformingashremoval,theashpandoorshouldbekeptclosed.

NeverinstallaHarmanTridentBoilerintoachimneywithahistoryofdown-drafts.

Keep Children Away-- May Cause Seri-ous Burns.

CAuTION: All surfaces of the boiler are hot. Do not touch. Keep children away. Serious burns will result if touched. This is a heat producing appliance.

DANGER: fire hazard, Do not use chemicals or flammable liquids to start or “freshen-up” a fire. Severe burns or a house fire may result. Do not burn Garbage, Gasoline, Thinners, Oil, Kero-sene Etc. An explosion, a house fire or serious personal injury could result. Keep all such liquids well away from this boiler.

Duringthefirstfewhoursofburning,abluesmokemaybeobservedrisingfromtheboiler.This is the paint going through the curing process. Itisadvisabletoincreasetheamountoffreshairintheroomduringthisbreakinperiod.Thiscanbeachievedbyopeningdoorsandwindows.Don’tbealarmed,thisisnormalandwillonlylastashortwhile.Chimney problems Not Enough Draft-Chimneyistoolow.Thegeneralruleforchimneysis16feettall,andtwofeethigherthananythingtenfeetaroundit.

Airmaybeleakinginaroundaloosefittingclean-out door.

Toomanyelbowsinconnectorpipe,orseamsandjoints of connector pipe are not secured properly.

Improperlysizedchimneyorstovepipe.

Chimneymaybeblockedwithcreosoteorbirdnestsorsimilarobstructions.

Crackedordefectivechimneyflueorliner.

Down Drafts- Trees or other topographi-calbarriersmayimpedeonchimneyperformancecausingaircurrentstobepusheddownwardintotheflue.Thiscanalsobecausedbyneighboringbuildingsorotherchimneys.

Creosote and condensation- If creo-soteorcondensationrunsoutofthechimneyorstovepipe,checkthefollowing;Chimneycaporlinermaybedefective,Boilermaybepositionedtoofarawayfromthechimneywhichwouldnotallowthechimneytowarm,Woodbeingburnedmaybegreenorwet,Boilermaybeover-sizedfortheresidencecausingittobeburnedonlowtoooften.

Excessive Draft-Thiscanbecontrolledwithabarometricdamperinthestovepipe.

Operation

Page 13: Installation & Operating Manual Trident Boilers: … & Operating Manual Trident Boilers: SF160, SF260, SF360. SAFETY NOTICE. PLEASE READ THIS ENTIRE MANUAL BEFORE YOU INSTALL AND/OR

1�

MaintenanceMaintenance Thespiralchamberisbasicallyself-cleaning.However,ifthereisadraftproblemandyouhavebeenburningwoodforalongtimewithlittledemand,thespiralchamberwillneedtobecleaned.Tocleanthespiralchamber,removethestovepipeandscrapeanycreosoteordebrisfromthetopandfrontofthechamber.Therearofthechambershouldnothavemuchaccumulation.Ifitdoes,cleanitout.

NOTE:1/4”to1/2”ofcreosoteinthespiralchamberisnormal.

Thepipesinsidethefireboxwillaccumulatecreosoteifthedemandforheatistoolow,whenburningwood.1/8”to1/4”ofcreosoteisnormalonthepipesandfireboxwalls.Ifmorecreosotehasaccumulated,itshouldbescrapedoffofthesesurfaces.

NOTE:Creosoteinthefireboxcanbeburnedoffbyburningcoalforafewdays.

Thefirebricksmaybecomecrackedduringthecourseofnormaloperation.Acrackedbrickthatisstillinplace,isstilldoingitsjob,andneednotbereplacedimmediately.Ifabrickisbroken,andhasfallenoutofplace,itshouldbereplacedbeforeanyfurtherburningoccurs.ThefirebricksusedintheTridentBoilerareavailableforreplacementfromyourHarmandealer. Gasketsonthedoorsaretheretoregulateairtothefirebox.Ifagasketisfailing,you’llnoticedifficultyincontrollingthefire.Inspectthegasketsregularly,andreplacewithHarmansuppliedmate-rial only.

Specifications Sf-160 Sf-260 Sf-360Heating Capacity (Square Feet) 2200 Max. 3200 Max. 4500 Max.

ApproximateBTUperhour(woodorcoal) 90,000 130,000 180,000

AMP Rating 40 40 40

Water Capacity (US Gallon) 25 32 42

Weight 640Lbs 780Lbs 925Lbs

Hydro-PressureTested Yes Yes Yes

FireboxDimensions(inches) 16Wx22Lx19H 18W x 26L x 20H 18W x 30L x 25H

RecommendedLogLength(inches) 19 23 27

Door Opening Size (inches) 11 x 13 13 x 13 13 x 13

OverallDimensions(inches) 23W x 23.5L x 45H 26W x 27.5L x 45.5H 26W x 31.5L x 51.5H

FlueSize(diameter) 6 inch 7 inch 7 inch

FlueHeight(topofflue) 37.5 inches 38.75 inches 44 inches

NumberOfGrates(10Lbs.Each) 4 5 6

Type Of Fuel Coal / Wood Coal / Wood Coal / Wood

Water Inlet and Outlet Size 1.25 NPT 1.25 NPT 1.25 NPT

AutomaticDraftControl Yes Yes Yes

Aquastat Yes Yes Yes

Temperature/PressureGauge Yes Yes Yes

ASME Pressure Relief Valve Yes Yes Yes

Ash Pan With Handle Yes Yes Yes

DomesticHotWaterCoil(optional) 4 GPM 4 GPM 4 GPM

ApproximateBTUperhour(electricoption) 30,000 30,000 30,000

KilowattRating(electricoption) 9 9 9

Page 14: Installation & Operating Manual Trident Boilers: … & Operating Manual Trident Boilers: SF160, SF260, SF360. SAFETY NOTICE. PLEASE READ THIS ENTIRE MANUAL BEFORE YOU INSTALL AND/OR

Warrantyharman™ Central heatinG ProduCts limited WarrantyHearth&HomeTechnologiesInc.,onbehalfofitsHarman™brand(”HHT”),extendsthefollowingwarrantyforallHarman™furnaceandboilerproducts(“Products”)thatarepurchasedfromanHHTauthorizeddealer.

WarrantyCoverage:Subjecttotheconditions,exclusionsandlimitationssetforthbelow,HHTwarrantstotheorigi-nalowneroftheProducts,andtoanytransfereetakingownershipoftheProductsatthesiteoforiginalinstallationwithintwoyearsfollowingthedateoforiginalpurchase,thattheProductswilloperatefreefromdefectsinmaterialandworkmanshipundernormalconditionsanduse,asdescribedintheoperatinginstructionsfurnishedwiththeProd-uct,duringthewarrantyperioddescribedbelow.HHTwill,atitsoption,repairorreplaceanyProductcoveredbythiswarrantythatisdeterminedtobedefectiveinmaterialorworkmanship.

WarrantyPeriod:Thewarrantyperiodrunsforsixyears,exceptformechanicalandelectricalcomponents,whicharewarrantedforthreeyears.Thewarrantyperiodbeginsontheearlierof:(i)thedateofinvoicefortheProduct;(ii)in the case of new home construction, the date of first occupancy of the residence or six months after the date of sale of the Product by an HHT authorized dealer, whichever occurs first; or (iii) the date 24 months following the date of ProductshipmentfromHHT,regardlessoftheinvoiceoroccupancydate.

WarrantyConditions:ThiswarrantyappliesonlytoProducts:(i)installed,operated,andmaintainedasrecommendedintheProductuser’smanual;(ii)purchasedthroughanHHTauthorizeddealer;(iii)whileremainingatthesiteoforiginalinstallation;and(iv)thathavenotbeenalteredafterleavingthefactory.

HowtoFileaClaim:ClaimsmustbemadewithinthewarrantyperiodtothedealerwhosoldtheProduct.Ifthatdealercannotprovidethewarrantyservice,contactthenearestHHTauthorizeddealer.AdditionalservicefeesmayapplyifyouareseekingwarrantyservicefromadealerotherthanthedealerfromwhomyouoriginallypurchasedtheProduct.Travelandshippingchargesforpartsarenotcoveredbythiswarranty.

WarrantyExclusions:Thiswarrantydoesnotcoverthefollowing:(1)consumableandnormalwearitems,includ-ing, without limitation, flame guides, grates, coal bars, afterburner hoods, fire brick, gaskets, paint, glass discoloration, burnpothousingweldments,burnpotgrateweldments(pelletorcorn),burnpotfrontplates(pelletorcorn),burnpotfrontplatelocks,cornaugerextensions,ceramicinserts,andceramicinsertplates;(�)noisecausedbyminorex-pansion,contractionormovementofparts;(�)damageresultingfrom:(i)failuretoinstall,operateormaintaintheProduct according to the installation and operating instructions and listing agent identification label furnished with the Product;(ii)failuretoinstalltheProductaccordingtolocalbuildingcodes;(iii)shippingorimproperhandling;(iv)abuse,misuse,continuedoperationwithdamaged,corrodedorfailedcomponents,accident,orincorrectlyperformedrepairs;(v)environmentalconditions,inadequateventilation,negativepressureordraftingcausedbytightlysealedconstruction, insufficient make-up air supply, or handling devices such as exhaust fans or forced air furnaces or other such causes; (vi) use of fuels other than those specified in the operating instructions; (vii) installation or use of com-ponents or accessories not supplied with the Product or authorized and approved in writing by HHT; (viii) modifica-tion of the product not expressly authorized and approved by HHT in writing; or (ix) interruptions or fluctuations of electricalpowersupplytotheProduct;(�)non-HHTcomponentsoraccessoriesusedinconjunctionwiththeProduct;(�)theProducts’capabilitytoheatadesiredspace;informationisprovidedtoassisttheconsumerandthedealerinselecting the proper Product for the application; consideration must be given to Product location and configuration, environmentalconditions,insulationandairtightnessofthestructure;or(�)additionalorunusualutilitybillsincurredduetoanymalfunctionordefectinProducts.

LimitationsofLiability:Repairorreplacementinaccordancewiththeprovisionsofthiswarrantywillbetheowner’sexclusiveremedyforandwillconstituteHHT’ssoleobligationunderthiswarranty,underanyotherwarranty(expressorimplied),orincontract,tortorotherwise.Noemployee,agent,dealer,orotherpersonisauthorizedtogiveanywarrantyonbehalfofHHT.TOTHEEXTENTALLOWEDBYLAW,HHTMAKESNOOTHERWARRANTY,EX-PRESSORIMPLIED,INCLUDINGANYWARRANTYOFMERCHANTABILITYORFITNESSFORAPARTIC-ULARPURPOSE.HHTWILLNOTBELIABLEFORANYCONSEQUENTIALORINCIDENTALDAMAGESARISINGOUTOFDEFECTSINORUSEOFTHEPRODUCTS.Somestatesdonotallowexclusionsorlimitationof incidental or consequential damages, so these limitations may not apply to you. This warranty gives you specific rights;youalsomayhaveotherrights,whichvaryfromstatetostate.Thedurationofanyimpliedwarrantyislimitedto the duration of the warranty period specified herein.

1�

Page 15: Installation & Operating Manual Trident Boilers: … & Operating Manual Trident Boilers: SF160, SF260, SF360. SAFETY NOTICE. PLEASE READ THIS ENTIRE MANUAL BEFORE YOU INSTALL AND/OR

Notes

1�

Notes

Page 16: Installation & Operating Manual Trident Boilers: … & Operating Manual Trident Boilers: SF160, SF260, SF360. SAFETY NOTICE. PLEASE READ THIS ENTIRE MANUAL BEFORE YOU INSTALL AND/OR

1�

Service Log

DATE Of SERVICE WORK pERfORMED pERfORMED By

Page 17: Installation & Operating Manual Trident Boilers: … & Operating Manual Trident Boilers: SF160, SF260, SF360. SAFETY NOTICE. PLEASE READ THIS ENTIRE MANUAL BEFORE YOU INSTALL AND/OR

Service parts

08/10

Sf160

part number list on following page.

Wood, Coal fi red Boiler Appliance

1-70-03233

Beginning Manufacturing Date: N/A Ending Manufacturing Date: N/A

1

2

3

4

67

8

5

Page 18: Installation & Operating Manual Trident Boilers: … & Operating Manual Trident Boilers: SF160, SF260, SF360. SAFETY NOTICE. PLEASE READ THIS ENTIRE MANUAL BEFORE YOU INSTALL AND/OR

Service parts

08/10

Beginning Manufacturing Date: N/A Ending Manufacturing Date: N/A

Sf160

IMPORTANT:THISISDATEDINFORMATION.Whenrequestingserviceorreplacementpartsforyourappliancepleaseprovidemodelnumberandserialnumber.Allpartslistedinthismanualmaybeorderedfromanauthorizeddealer.

Stockedat Depot

ITEM DESCRIpTION COMMENTS pART NuMBER1 Safetyreliefvalve 3-10-77382 y2 Press/tempgauge-rearmount 3-10-78427 y3 WELLWEL11A-601R Post1199 3-10-935111 y4 Stovewaterplate(6holes,1fitting) 1-10-080245 Doorhandle-cast Qty.2Req. 4-00-00042 y6 Longshakerhandleweldment 1-10-01005 y7 Automaticdraftcontrolassembly 1-10-03375 y8 Boilerelectricback-upforJohnsoncontrols Post1199 1-00-01019

AquastatreplacementforWhiteRogers Pre1199 1-00-03500 yAquastatsensor/A350controlAPPBC-25C Post1199 3-10-2992225 yAshpan 1-10-16027 yBoilercoilassembly 1-00-07006Boilerkitassembly 1-00-01020Boilerplategasket 3-10-24758 yCoilwaterplate(8holes,1fitting,2nuts) 1-10-07006ControllerA350AA-2C Post1199 3-10-1350112 yDoorLatch 4Sets 1-00-00036 yDraftcontrol-cast Qty.2Req. 4-00-00109-1Draftmotormountbracket 2-00-01010BDraftmotor120v 3-20-45338 yDraftregulatorTypeC-20(usewithnon-electrickit) 3-91-05000 yDualfuelashdoor-cast 4-00-00200-1DGrateholder-cast Qty.4Req. 3-00-00193 yGratelink-cast 4-00-00205D yNon-electricboilerkit(includesregulator&draftcontrol) 1-00-08012Non-electricdraftcontrolassembly 1-10-08013APowersupplyY350R-1C Post1199 3-10-935071 yRopegasket1/2”(door-ashpan) 1-00-53500 ySetofcutbrick 1-00-08124 yShakerbarweldment4-1/4” 1-10-02017W yShakerblock 2-00-01037-1 yShakerhandlemount 2-00-01037-2 yShortgrate13in-cast Qty.4Req. 3-00-00207 ySmallsolidloaddoor-cast 4-00-00197P yStagemoduleS350AA-1C Post1199 3-10-7350111 yStandardbrick9”x4-1/2”x1-1/4”(6needed) Pkgof7 1-00-900450125 y

Page 19: Installation & Operating Manual Trident Boilers: … & Operating Manual Trident Boilers: SF160, SF260, SF360. SAFETY NOTICE. PLEASE READ THIS ENTIRE MANUAL BEFORE YOU INSTALL AND/OR

Service parts

08/10

Beginning Manufacturing Date: N/A Ending Manufacturing Date: N/A

Sf160

IMPORTANT:THISISDATEDINFORMATION.Whenrequestingserviceorreplacementpartsforyourappliancepleaseprovidemodelnumberandserialnumber.Allpartslistedinthismanualmaybeorderedfromanauthorizeddealer.

Stockedat Depot

ITEM DESCRIpTION COMMENTS pART NuMBER1 Safetyreliefvalve 3-10-77382 y2 Press/tempgauge-rearmount 3-10-78427 y3 WELLWEL11A-601R Post1199 3-10-935111 y4 Stovewaterplate(6holes,1fitting) 1-10-080245 Doorhandle-cast Qty.2Req. 4-00-00042 y6 Longshakerhandleweldment 1-10-01005 y7 Automaticdraftcontrolassembly 1-10-03375 y8 Boilerelectricback-upforJohnsoncontrols Post1199 1-00-01019

AquastatreplacementforWhiteRogers Pre1199 1-00-03500 yAquastatsensor/A350controlAPPBC-25C Post1199 3-10-2992225 yAshpan 1-10-16027 yBoilercoilassembly 1-00-07006Boilerkitassembly 1-00-01020Boilerplategasket 3-10-24758 yCoilwaterplate(8holes,1fitting,2nuts) 1-10-07006ControllerA350AA-2C Post1199 3-10-1350112 yDoorLatch 4Sets 1-00-00036 yDraftcontrol-cast Qty.2Req. 4-00-00109-1Draftmotormountbracket 2-00-01010BDraftmotor120v 3-20-45338 yDraftregulatorTypeC-20(usewithnon-electrickit) 3-91-05000 yDualfuelashdoor-cast 4-00-00200-1DGrateholder-cast Qty.4Req. 3-00-00193 yGratelink-cast 4-00-00205D yNon-electricboilerkit(includesregulator&draftcontrol) 1-00-08012Non-electricdraftcontrolassembly 1-10-08013APowersupplyY350R-1C Post1199 3-10-935071 yRopegasket1/2”(door-ashpan) 1-00-53500 ySetofcutbrick 1-00-08124 yShakerbarweldment4-1/4” 1-10-02017W yShakerblock 2-00-01037-1 yShakerhandlemount 2-00-01037-2 yShortgrate13in-cast Qty.4Req. 3-00-00207 ySmallsolidloaddoor-cast 4-00-00197P yStagemoduleS350AA-1C Post1199 3-10-7350111 yStandardbrick9”x4-1/2”x1-1/4”(6needed) Pkgof7 1-00-900450125 y

Service parts

08/10

Sf260

part number list on following page.

Wood, Coal fi red Boiler Appliance

1-70-03236

Beginning Manufacturing Date: N/A Ending Manufacturing Date: Active

1

2

3

4

6

7

5

Page 20: Installation & Operating Manual Trident Boilers: … & Operating Manual Trident Boilers: SF160, SF260, SF360. SAFETY NOTICE. PLEASE READ THIS ENTIRE MANUAL BEFORE YOU INSTALL AND/OR

Service parts

08/10

Beginning Manufacturing Date: N/A Ending Manufacturing Date: Active

Sf260

IMPORTANT:THISISDATEDINFORMATION.Whenrequestingserviceorreplacementpartsforyourappliancepleaseprovidemodelnumberandserialnumber.Allpartslistedinthismanualmaybeorderedfromanauthorizeddealer.

Stockedat Depot

ITEM DESCRIpTION COMMENTS pART NuMBER1 Safetyreliefvalve 3-10-77382 y2 Press/tempgauge-rearmount 3-10-78427 y3 Stovewaterplate(6holes,1fitting) 1-10-080244 Doorhandle-cast Qty.2req. 4-00-00042 y5 Longshakerhandleweldment 1-10-01005 y6 Automaticdraftcontrolassembly 1-10-03375 y7 Boilerelectricback-upforJohnsoncontrols(option) Post1199 1-00-01019

AquastatreplacementforWhiteRodgers Pre1199 1-00-03500 yAquastatsensor/A350controlAPPBC-25C Post1199 3-10-2992225 yAshpan 1-10-25027 yBoilercoilassembly 1-00-07006Boilerkitassembly 1-00-01020Boilerplategasket 3-10-24758 yCoilwaterplate(8holes,1fitting,2nuts) 1-10-07006ControllerA350AA-2C Post1199 3-10-1350112 yDoorLatch 4Sets 1-00-00036 yDraftcontrol-cast Qty.2req. 4-00-00109-1Draftmotormountbracket 2-00-01010BDraftmotor120v 3-20-45338 yDraftregulatorTypeC-20(usewithnon-electrickit) 3-91-05000 yDualfuelashdoor-cast 4-00-00200-1DFlapperweldment17-1/2” 1-10-00407Grateholder2-cast Qty.2req. 3-00-00193 yGrateholder3-cast Qty.2req. 3-00-00194 yGratelink5-cast 3-00-00205 yLargesolidloaddoor-cast 4-00-00195PLonggrate15in-cast Qty.5req. 3-00-00208 yNon-electricboilerkit(includesregulator&draftcontrol) 1-00-08012Non-electricdraftcontrolassembly 1-10-08013APowersupplyY350R-1C Post1199 3-10-935071 yRopegasket1/2”(door-ashpan) 1-00-53500 ySetofcutbrick 1-00-00842 yShakerbarweldment4-11/16” 1-10-02018W yShakerblock 2-00-01037-1 yShakerhandlemount 2-00-01037-2 yStagemoduleS350AA-1C Post1199 3-10-7350111 yStandardbrick9”x4-1/2”x1-1/4”(8needed) Pkgof7 1-00-900450125 y

Page 21: Installation & Operating Manual Trident Boilers: … & Operating Manual Trident Boilers: SF160, SF260, SF360. SAFETY NOTICE. PLEASE READ THIS ENTIRE MANUAL BEFORE YOU INSTALL AND/OR

Service Parts

08/10

1

2

3

4

6

7

5

Sf360

part number list on following page.

Wood, Coal fired Boiler Appliance

1-70-03239

Beginning Manufacturing Date: N/A Ending Manufacturing Date: Active

Page 22: Installation & Operating Manual Trident Boilers: … & Operating Manual Trident Boilers: SF160, SF260, SF360. SAFETY NOTICE. PLEASE READ THIS ENTIRE MANUAL BEFORE YOU INSTALL AND/OR

Service Parts

08/10

IMPORTANT:THISISDATEDINFORMATION.Whenrequestingserviceorreplacementpartsforyourappliancepleaseprovidemodelnumberandserialnumber.Allpartslistedinthismanualmaybeorderedfromanauthorizeddealer.

Stockedat Depot

ITEM DESCRIpTION COMMENTS pART NuMBER1 Safetyreliefvalve 3-10-77382 y2 Press/tempgauge-rearmount 3-10-78427 y3 Stovewaterplate(6holes,1fitting) 1-10-080244 Doorhandle-cast Qty.2req. 4-00-00042 y5 Longshakerhandleweldment 1-10-01005 y6 Automaticdraftcontrolassembly 1-10-03375 y7 Boilerelectricback-upforJohnsoncontrols Post1199 1-00-01019

AquastatreplacementforWhiteRodgers Pre1199 1-00-03500 yAquastatsensor/A350controlAPPBC-25C Post1199 3-10-2992225 yAshpan 1-10-35027 yBoilercoilassembly 1-00-07006Boilerkitassembly 1-00-01020Boilerplategasket 3-10-24758 yCoilwaterplate(8holes,1fitting,2nuts) 1-10-07006ControllerA350AA-2C Post1199 3-10-1350112 yDoorLatch 4Sets 1-00-00036 yDraftcontrol-cast Qty.2req. 4-00-00109-1Draftmotormountbracket 2-00-01010BDraftmotor120v 3-20-45338 yDraftregulatorTypeC-20(usewithnon-electrickit) 3-91-05000 yDualfuelashdoor-cast 4-00-00200-1DFlapperweldment17-1/2” 1-10-00407Grateholder3-cast Qty4req 3-00-00194 yGratelink6-cast 3-00-00206 yLargesolidloaddoor-cast 4-00-00195PLonggrate15in-cast Qty.6req. 3-00-00208 yNon-electricboilerkit(includesregulator&draftcontrol) 1-00-08012Non-electricdraftcontrolassembly 1-10-08013APowersupplyY350R-1C Post1199 3-10-935071 yRopegasket1/2”(door-ashpan) 1-00-53500 yShakerbarweldment4-11/16” 1-10-02018W yShakerblock 2-00-01037-1 yShakerhandlemount 2-00-01037-2 yStagemoduleS350AA-1C Post1199 3-10-7350111 yStandardbrick9”x4-1/2”x1-1/4”(20needed) Pkgof7 1-00-900450125 y