INSTALLATION & OWNER’S MANUAL
Control Box Type
Thank you very much for purchasing our air conditioner, Before using your air conditioner , please read this manual carefully and keep it for future reference.
Outdoor unit
Indoor unit
Control box
Outdoor unit
Indoor unit
Control box
Use the attached accessories parts and specified parts for installation. otherwise, it will cause the set to fall, water leakage, electric shock ,fire.
Install at a strong and firm location which is able to withstand the set' s weight. If the strength is not enough or installation is not properly done, the set will drop to cause injury.
Before obtaining access to terminals, all supply circuits must be disconnected.
The appliance must be positioned so that the plug is accessible.
The enclosure of the appliance shall be marked by word, or by symbols, with the direction of the fluid flow.
For electrical work, follow the local national wiring standard, regulation and this installation instructions. An independent circuit and single outlet must be used. If electrical circuit capacity is not enough or defect in electrical work, it will cause electric shock ,fire.
Use the specified cable and connect tightly and clamp the cable so that no external force will be acted on the terminal. If connection or fixing is not perfect, it will cause heat-up or fire at the connection.
Wiring routing must be properly arranged so that control board cover is fixed properly. If control board cover is not fixed perfectly, it will cause heat-up at connection point of terminal, fire or electric shock.
If the supply cord is damaged, it must be replaced by the manufacture or its sevice agent or similarly qualifued person in order to avoid a hazard.
An all-pole disconnection switch having a cintract separation of at least 3mm in a poles should be connected in fixed wiring.
When carrying out piping connection, take care not to let air substances go into refrigeration cycle. Otherwise, it will cause lower capacity, abnormal high pressure in the refrigeration cycle, explosion and injury.
Do not modify the length of the power supply cord or use of extension cord, and do not share the single outlet with other electrical appliances. Otherwise, it will cause fire or electric shock.
Carry out the specified installation work after taking into account strong winds, typhoons or earthquakes.Improper installation work may result in the equipment falling and causing accidents.
If the refrigerant leaks during installation, ventilate the area immediately.Toxic gas may be produced if the refrigerant comes into the place contacting with fire.
After completing the installation work, check that the refrigerant does not leak.Toxic gas may be produced if the refrigerant leaks into the room and comes into contact with a source of fire, such as a fan heater, stove or cooker.
1installation manual
Be sure to be in conformity with the local, national and international laws and regulations.
Read "PRECAUTIONS" carefully before installation.
The following precautions include important safety items. Observe them and never forget.
Keep this manual in a handy place for future reference.
1. PRECAUTIONS
WARNING
WARNING
The safety precautions listed here are divided into two categories. In either case, important safety information is listed which must be read carefully.
After completing the installation, make sure that the unit operates properly during the start-up operation. Please instruct the customer on how to operate the unit and keep it maintained. Also, inform customers that they should store this installation manual for future reference.
Be sure only trained and qualified service personnel to install, repair or service the equipment.Improper installation, repair, and maintenance may result in electric shocks, short-circuit, leaks, fire or other damage to the equipment.
Install according to this installation instructions strictly. If installation is defective, it will cause water leakage, electric shock, fire.
When installing the unit in a small room, take measures against to keep refrigerant concentration from exceeding allowable safety limits in the event of refrigerant leakage. Contact the place of purchase for more information. Excessive refrigerant in a closed ambient can lead to oxygen deficiency.
Failure to observe a warning may result in death.
CAUTIONFailure to observe a caution may result in injury or damage to the equipment.
CONTENTS PAGE
PRECAUTIONS.......................................................................................
INSTALLATION INFORMATION................................................................
ATTACHED FITTINGS..............................................................................
INSTALLATION METHOD&DIMENSION...................................................
MATERIAL AND SIZE OF THE PIPING.....................................................
ELECTRICAL WIRING............................................................................
APPLICALTION CONTROL......................................................................
TROUBLE SHOOTING.............................................................................
1
2
3
4
5
5
7
9
Outdoor unit
Indoor unit
Control box
2installation manual
To install properly, please read this "installation manual" at first.
The air conditioner must be installed by qualified persons.
When installing the indoor unit or its tubing, please follow this manual as strictly as possible.
If the air conditioner is installed on a metal part of the building, it must be electrically insulated according to the relevant standards to electrical appliances.
When all the installation work is finished, please turn on the power only after a thorough check.
Regret for no further announcement if there is any change of this manual caused by product improvement.
2. INSTALLATION INFORMATION
INSTALLATION ORDERSelect the location;
Install the indoor unit;
Install the outdoor unit;
Install the connecting pipe ;
Connect the drain pipe;
Wiring;
Test operation.
CAUTION
Ground the air conditioner.Do not connect the ground wire to gas or water pipes, lightning rod or a telephone ground wire.Incomplete grounding may result in electric shocks.
Be sure to install an earth leakage breaker.Failure to install an earth leakage breaker may result in electric shocks.
Connect the outdoor unit wires , then connect the indoor unit wires. You are not allow to connect the air conditioner with the power source until w(including iring and piping the air conditioner is done.
While following the instructions in this installation manual, install drain piping in order to ensure proper drainage and insulate piping in order to prevent condensation.Improper drain piping may result in water leakage and property damage.
Install the indoor and outdoor units, power supply wiring and connecting wires at least 1 meter away from televisions or radios in order to prevent image interference or noise.Depending on the radio waves, a distance of 1 meter may not be sufficient enough to eliminate the noise.
The appliance is not intended for use by young children or infirm persons without supervision.
Young children should be supervised to ensure that they do not play with the appliance.
Don't install the air conditioner in the following locations:
There is petrolatum existing.
There is salty air surrounding (near the coast).
There is caustic gas (the sulfide, for example) existing in the air (near a hot spring).
The Volt vibrates violently (in the factories).
In buses or cabinets.
In kitchen where it is full of oil gas.
There is strong electromagnetic wave existing.
There are inflammable materials or gas.
There is acid or alkaline liquid evaporating.
Other special conditions.
Outdoor unit
Indoor unit
Control box
3. ATTACHED FITTINGSPlease check whether the following fittings are of full scope. If there are some spare fittings , please restore them carefully.
3installation manual
Table.3-1
QUANTITYSHAPENAME
2. Plastic expanded tube
3. Temp.sensor(AHUKZ-01 only)
4. Temp.sensor (AHUKZ-02 only)
8. Wire controller installation manual
5. Display panel connecting wire group
7. Installation&owner’s manual
4
8
3
6
1
1
2
FUNCTION
1. Screw ST3.9x25 for installation board Secure the installation board
6. Wire controller connecting wire group
1
X2
EBADC
T2B
T2T1
T2B
T2T1
Outdoor unit
Indoor unit
Control box
4installation manual
Units: mm
4. INSTALLATION METHOD & DIMENSION
AHUKZ-01AHUKZ-02
NOTEAs hanging installation please use Screw ST3.9x25 for installation.As hanging installation, the box should be vertical, and as hoisting installation, it should be installed horizontally, and prohibit to be sloped, inverted.Please refer to the foregoing,make sure the laying direction of the refrigerant pipe and the connecting place of the connecting wire.All the pictures in this manual are for explanation purpose only. They may be slightly different from the air conditioner you purchased(depend on model).The actual shape shall prevail.
12
3
4
Installation method : Hoisting
Filter access door
Remote receiver
Filter access door
Filter access doorConnect to outdoor unit
Connect to indoor unit
Filter access door
Filter access door
Wire controller
Installation method : HangingFig.4-1
Fig.4-2 Fig.4-3
Install vertically
Install horizontally
Outdoor unit
Indoor unit
Control box
95 111 98
205
184
122
395270
18
140
122
122
428
461
485
80270
5Φ5
Φ6Φ12
142
6330
0
6-1 The specification of power
Single-phase
220-240V ~ 50Hz
Model
PhasePower
Voltage and Frequency
AHUKZ-01 AHUKZ-02
5installation manual
5. MATERIAL AND SIZE OF THE PIPING
Size(mm)
Pipe Material Copper Pipe for Air Conditioner
Model Φ8
AHUKZ-01
(Liquid side) Φ12.7
AHUKZ-02
Table.5-1
6. ELECTRICAL WIRING
CAUTION
The air conditioner should use separate power supply with rated voltage.The external power supply to the air conditioner should have ground wiring, which is linked to the ground wiring of the indoor and outdoor unit.The wiring work should be done by qualified persons according to circuit drawing.The fixed connecting lines must equip with at lease 3mm electric shock spacing.A leakage protector should be installed according to the National Standard concerning electrical appliance.Be sure to locate the power wiring and the signal wrings well to avoid cross-disturbance and their contact with connecting pipe or stop value body. Generally, do not twist two wiring together unless the joint is soldered well and covered with insulator tape.Do not turn on the power until you have checked carefully after wiring.
CAUTION
CAUTION
The specification of power as the follow display figure, if the capacity is too small will lead to over heat of the wiring,and cause burning of the machine accident.
The air-gap notch in the circuit breaker is used for insulating the flexible conductor, so that must respond to the related national wire requests to connect to the fixed circuit.
CAUTION
The air-conditioner can connect to the central controller (CCM). Before the operation, please correctly connect the wire and well set the system address and network address of indoor unit.
6-2 Terminal block setting figure
Please refer to the indoor unit wiring figure for connecting wire.
P1 N1 P2 N2XT2
Connect to water pump Alarm signal
XT3
TO CCM COMM.BUS
Please use 3-core shielding wire, and ground the shielding layer.
TO OUTDOOR COMM.BUS
The connecting distance of control box and indoor unit should not more than 5 m. This control box can only connect to R410A refrigerant system. During the installation of connecting pipes, do not let air, dust, or other sundries enter to the piping system. Install the connecting pipe only after the indoor and outdoor units have been fixed. When installing the connecting pipes, it must be kept dry and do not let water enter to the piping system. The connecting copper pipes should be wrapped with thermal insulation materials (the thick should be more than 10mm; the close wet area should be thicken properly).
1
23
4
5
6
1
2
3
4
5
6
7
white blue black blackyellow ash
O1
Connect to remote switch
O2 W1 W2
XT4
The connecting terminals of the water level switch
W1 and W2 are shorted by default, when connect the
indoor unit with water pump please remove the short
connecting wire and connect to the water level switch.
white white whiteblack
Connect to water level switch
Table.6-1
L N XT1
1 2 3 4
Connect to indoor fanNeutral
HighMedium
Low
Connect to indoor power 220-240V~ 50Hz 208-230V~ 60Hz
Outdoor unit
Indoor unit
Control box
Fig.6-1
Fig.6-2
Fig.6-3
Fig.6-4
208-230V ~ 60Hz
6installation manual
6-3 Electric control box wiring figure
6-4 Indoor and outdoor unit wiring figure
CAUTION
CAUTION
AHUKZ-01 adopts one master control board, AHUKZ-02 adopts two master control boards, when installing, both the two master control boards of AHUKZ-02 should connect to the temp sensor T1, T2 and T2B, and place the corresponding two sensors of the two master control boards in the same location.T1 is indoor temperature sensor, install to the air inlet of the indoor unit.T2 is indoor evaporator intermediate temperature sensor, install to the intermediate of temperature evaporatorz.T2B is indoor evaporator outlet sensor, install to the outlet of the evaporator.
1
234
Body sensewire controller
T2
T2B
T1
B A
Temp sensor wire group (T1, T2, T2B) anddisplay panel connecting wire group, throughthe side hole of control box and use the tighten belt to fix the wire groups.
Connecting wire controller Connector
Indoor temp sensor (T1), indoor evaporator intermediate temp sensor (T2), indoor evaporator outlet temp sensor (T2B), please connects respond to the wiring nameplate.
Fig.6-5
220-240V~50Hz Signal wire
Liquid pipe
Gas pipe
Liquid pipe
Fan wireWater pump
Water level switch
T2 Intermediate section of evaporator
T2B Air pipe outlet
T1 Air-return inlet
Outdoor unitOutdoor unit
Indoor unitIndoor unit
Control boxControl box
Fig.6-6
If it is needed, user can select the backup function in the dotted line frame.
208-230V~60Hz
7installation manual
7. APPLICALTION CONTROL
Set the PCB code of the indoor unit electric control box by different usage. After setting, be sure to turn off the total power switch again and then switch on again. The setting function can not be carried out if not to turn off the total power switch again and then switch on again (Fig.7-1).
ENC1
0
1
2
3
4
5
6
7
8
9
2200W(0.8HP)
2800W(1.0HP)
3600W(1.3HP)
4500W(1.6HP)
5600W(2.0HP)
7100W(2.5HP)
8000W(3.0HP)
9000W(3.2HP)
11200W(4.0HP)
14000W(5.0HP)
Toggle switch For setting cooling capacity
Code Setting cooling capacity
Caution:
The horsepower
has been set
before leaving
the factory;
anyone can’t
modify it except
the maintenance
person.
7-2 System Address and Network Address Setting
7-1 Application control
7-3 Mainboard Code Indication Label
1234
SW1ON
1234
SW1ON
1234
SW1ON
● 1 means the factory test mode● 0 automatic search address mode (factory default)
● 1 means the factory test mode● 0 means select AC fan
● 00 means DC fan static pressureselection 0 set (reserved)
Definition of every SW1 position
1234
SW1ON
1234
SW1ON
SW1ON
● 01 means DC fan static pressureselection 1 set (reserved)
● 10 means DC fan static pressureselection 2 set (reserved)
● 11 means DC fan static pressureselection 3 set (reserved)
1234
SW2ON
1234
SW2ON
1234
SW2ON
1234
SW2ON
● 00 means temperature ofshut down against cool airis 15°C
Definition of every SW2 position
● 00 means temperature ofshut down against cool airis 20°C
● 00 means temperature ofshut down against cool airis 24°C
● 00 means temperature ofshut down against cool airis 26°C
1) The default system address is “00” for AHUKZ-01, “00” and “01” for system A and B of AHUKZ-02 respectively.
2) If there are several indoor units multi-connected, the system address may be conflict between the different units. In that case, reset the in door unit’s address is needed.
3) If the system address conflict occur, the indoor units must use remote controller to set the system address first (For setting system address to the indoor unit with two or more master boards, it have to use display panel with 10-core wire to connect the display panel, and address setting for every master board respectively).
4) Communicating the indoor and outdoor units to finish setting network address, its address is the same as the indoor unit address, no need to setting separately.
5) When all the indoor units are AHUKZ-01/AHUKZ-02 or V4+ series indoor units, centralized control of indoor unit can finish upside the outdoor unit, no need to do the centralized control inside the indoor unit, the detailed instruction refers to V4+ Outdoor Unit Instruction.
6) For the previous indoor unit centralized control function, can connect to the (X,Y,E) terminals and form centralized control network, at that time no need to set the network address, then also can through the outlay network module, mainboard (CN20) and form a network.
0 1
34
56789AB
CD
E F
ENC1Fig.7-1
● Function specification:
ENC1——Cooling capacity setting, set the cooling capacity of this machine (Table. 7-1).
Table.7-1
Outdoor unit
Indoor unit
Control box
Table.7-2
Table.7-3
Table.7-4
8installation manual
1234
SW2ON
1234
SW2ON
1234
SW2ON
1234
SW2ON
● 00 means the time of TERMALstop the fan is 4 minutes
● 00 means the time of TERMALstop the fan is 8 minutes
● 00 means the time of TERMALstop the fan is 12 minutes
● 00 means the time of TERMALstop the fan is 16 minutes
1 2
SW5ON
1 2
SW5ON
● 00 means the temperaturecompensation under heatingmode is 6°C
Definition of every SW5 position
● 01 means the temperaturecompensation under heatingmode is 2°C
1 2
SW5ON
1 2
SW5ON
● 10 means the temperaturecompensation under heatingmode is 4°C
● 11 means the temperaturecompensation under heatingmode is 8°C
1 2 3
SW6ON
1 2 3
SW6ON
1 2 3
SW6ON
● 1 means the old display panel● 0 means the new display panel
Reserved
Definition of every position
●1 means automatic mode automatic fan●0 means non-automatic mode automatic fan
J1
J1
J2
J1 Jumperless for has power down memoryfunction
J1 Jumperless for has nopower down memory function
Reserved
Definition of J1,J2 positions
1 2
SW7ON
1 2
SW7ON
Standard configuration
The last set ofthe network
Definition of every SW7 position
ON
ON
Means 0
Means 1
Definition of every 0/1 code
Please adjust the code ENC1 to the proper position (both the AHUKZ-02 model system A and system B should be adjusted)For AHUKZ-01 model:9kW please set the main board’s code ENC1 in the electric controller to 7; 11.2kW please set the main board’s code ENC1 in the electric controller to 8;14kW please set the main board’s code ENC1 in the electric controller to 9.
For AHUKZ-02 model:20kW please set two main boards’ code ENC1 in the electric controller to 8; 25kW please set one main board’s code ENC1 in the electric controller to 8, and set the another code ENC1 to 9; 28kW please set two main boards’ code ENC1 in the electric controller to 9.
For the same indoor unit, each main board must has different indoor unit addresses and network addresses.
When use centralized controller to control indoor unit, and set address for the AHUKZ-02 with two or more main boards, we suggest that set the neighbor address for the same main board of indoor unit. When use centralized controller for controlling, main board in the same indoor unit must ON and OFF at the same time, for avoiding that affect the usage function of the machine.
1
2
3
CAUTION
Outdoor unit
Indoor unit
Control box
Table.7-5
Table.7-6
Table.7-7
Table.7-8
Table.7-9
Table.7-10
Table.7-11
9installation manual
8. TROUBLE SHOOTING
Table.8-1
NO. Type Contents LED Display Remarks
The evaporator sensor check point is abnomaor room temp.sensor is abnormal.
Indoor/outdoor unit communication is abnormal.
Condenser sensor check point isabnormal or outdoor temp.
Water level switch is abnormal
Mode conflict
Error code “H1,H2,H3,E2,E3 or E4”
Error code“E1”
Error code“Ed ”
Error code“EE”
Error code“E0”
After the malfunctionsdisappear, it restoresautomatically.
After the malfunctions disappear, it restoresautomatically.
After the malfunctions disappear, it restoresautomatically.
If the malfunctions can’t be solved in three min. all the indoor alarm lamps flash at 0.5Hz.Turn off the power to restore.
When the indoor unit turns to heating mode or is turned off, thealarm will disappear.
1
2
3
4
5
Malfun-ction
Malfun-ction
Malfun-ction
Malfun-ction
Alarm
Fig.8-1
PRE-DEF indicator(cooling and heating type) or fan only indicator(cooling only type)
Infrared signal receiver
Operation lamp Timer indicator Alarm indicator
Temporary buttonLED display
Outdoor unit
Indoor unit
Control box
MDV11IU-001BW
202000171586
Outdoor unit
Indoor unit
Control box
Outdoor unit
Indoor unit
Control box
Outdoor unit
Indoor unit
Control box
Outdoor unit
Indoor unit
Control box
Outdoor unit
Indoor unit
Control box