16
INSTALLATION & OWNER’S MANUAL Control Box Type Thank you very much for purchasing our air conditioner, Before using your air conditioner , please read this manual carefully and keep it for future reference.
Transcript
Page 1: INSTALLATION & OWNER’S MANUAL - Midea...AHUKZ-01 AHUKZ-02 5 installation manual 5. MATERIAL AND SIZE OF THE PIPING Size(mm) Pipe Material Copper Pipe for Air Conditioner Model Φ8

INSTALLATION & OWNER’S MANUAL

Control Box Type

Thank you very much for purchasing our air conditioner, Before using your air conditioner , please read this manual carefully and keep it for future reference.

Outdoor unit

Indoor unit

Control box

Page 2: INSTALLATION & OWNER’S MANUAL - Midea...AHUKZ-01 AHUKZ-02 5 installation manual 5. MATERIAL AND SIZE OF THE PIPING Size(mm) Pipe Material Copper Pipe for Air Conditioner Model Φ8

Outdoor unit

Indoor unit

Control box

Page 3: INSTALLATION & OWNER’S MANUAL - Midea...AHUKZ-01 AHUKZ-02 5 installation manual 5. MATERIAL AND SIZE OF THE PIPING Size(mm) Pipe Material Copper Pipe for Air Conditioner Model Φ8

Use the attached accessories parts and specified parts for installation. otherwise, it will cause the set to fall, water leakage, electric shock ,fire.

Install at a strong and firm location which is able to withstand the set' s weight. If the strength is not enough or installation is not properly done, the set will drop to cause injury.

Before obtaining access to terminals, all supply circuits must be disconnected.

The appliance must be positioned so that the plug is accessible.

The enclosure of the appliance shall be marked by word, or by symbols, with the direction of the fluid flow.

For electrical work, follow the local national wiring standard, regulation and this installation instructions. An independent circuit and single outlet must be used. If electrical circuit capacity is not enough or defect in electrical work, it will cause electric shock ,fire.

Use the specified cable and connect tightly and clamp the cable so that no external force will be acted on the terminal. If connection or fixing is not perfect, it will cause heat-up or fire at the connection.

Wiring routing must be properly arranged so that control board cover is fixed properly. If control board cover is not fixed perfectly, it will cause heat-up at connection point of terminal, fire or electric shock.

If the supply cord is damaged, it must be replaced by the manufacture or its sevice agent or similarly qualifued person in order to avoid a hazard.

An all-pole disconnection switch having a cintract separation of at least 3mm in a poles should be connected in fixed wiring.

When carrying out piping connection, take care not to let air substances go into refrigeration cycle. Otherwise, it will cause lower capacity, abnormal high pressure in the refrigeration cycle, explosion and injury.

Do not modify the length of the power supply cord or use of extension cord, and do not share the single outlet with other electrical appliances. Otherwise, it will cause fire or electric shock.

Carry out the specified installation work after taking into account strong winds, typhoons or earthquakes.Improper installation work may result in the equipment falling and causing accidents.

If the refrigerant leaks during installation, ventilate the area immediately.Toxic gas may be produced if the refrigerant comes into the place contacting with fire.

After completing the installation work, check that the refrigerant does not leak.Toxic gas may be produced if the refrigerant leaks into the room and comes into contact with a source of fire, such as a fan heater, stove or cooker.

1installation manual

Be sure to be in conformity with the local, national and international laws and regulations.

Read "PRECAUTIONS" carefully before installation.

The following precautions include important safety items. Observe them and never forget.

Keep this manual in a handy place for future reference.

1. PRECAUTIONS

WARNING

WARNING

The safety precautions listed here are divided into two categories. In either case, important safety information is listed which must be read carefully.

After completing the installation, make sure that the unit operates properly during the start-up operation. Please instruct the customer on how to operate the unit and keep it maintained. Also, inform customers that they should store this installation manual for future reference.

Be sure only trained and qualified service personnel to install, repair or service the equipment.Improper installation, repair, and maintenance may result in electric shocks, short-circuit, leaks, fire or other damage to the equipment.

Install according to this installation instructions strictly. If installation is defective, it will cause water leakage, electric shock, fire.

When installing the unit in a small room, take measures against to keep refrigerant concentration from exceeding allowable safety limits in the event of refrigerant leakage. Contact the place of purchase for more information. Excessive refrigerant in a closed ambient can lead to oxygen deficiency.

Failure to observe a warning may result in death.

CAUTIONFailure to observe a caution may result in injury or damage to the equipment.

CONTENTS PAGE

PRECAUTIONS.......................................................................................

INSTALLATION INFORMATION................................................................

ATTACHED FITTINGS..............................................................................

INSTALLATION METHOD&DIMENSION...................................................

MATERIAL AND SIZE OF THE PIPING.....................................................

ELECTRICAL WIRING............................................................................

APPLICALTION CONTROL......................................................................

TROUBLE SHOOTING.............................................................................

1

2

3

4

5

5

7

9

Outdoor unit

Indoor unit

Control box

Page 4: INSTALLATION & OWNER’S MANUAL - Midea...AHUKZ-01 AHUKZ-02 5 installation manual 5. MATERIAL AND SIZE OF THE PIPING Size(mm) Pipe Material Copper Pipe for Air Conditioner Model Φ8

2installation manual

To install properly, please read this "installation manual" at first.

The air conditioner must be installed by qualified persons.

When installing the indoor unit or its tubing, please follow this manual as strictly as possible.

If the air conditioner is installed on a metal part of the building, it must be electrically insulated according to the relevant standards to electrical appliances.

When all the installation work is finished, please turn on the power only after a thorough check.

Regret for no further announcement if there is any change of this manual caused by product improvement.

2. INSTALLATION INFORMATION

INSTALLATION ORDERSelect the location;

Install the indoor unit;

Install the outdoor unit;

Install the connecting pipe ;

Connect the drain pipe;

Wiring;

Test operation.

CAUTION

Ground the air conditioner.Do not connect the ground wire to gas or water pipes, lightning rod or a telephone ground wire.Incomplete grounding may result in electric shocks.

Be sure to install an earth leakage breaker.Failure to install an earth leakage breaker may result in electric shocks.

Connect the outdoor unit wires , then connect the indoor unit wires. You are not allow to connect the air conditioner with the power source until w(including iring and piping the air conditioner is done.

While following the instructions in this installation manual, install drain piping in order to ensure proper drainage and insulate piping in order to prevent condensation.Improper drain piping may result in water leakage and property damage.

Install the indoor and outdoor units, power supply wiring and connecting wires at least 1 meter away from televisions or radios in order to prevent image interference or noise.Depending on the radio waves, a distance of 1 meter may not be sufficient enough to eliminate the noise.

The appliance is not intended for use by young children or infirm persons without supervision.

Young children should be supervised to ensure that they do not play with the appliance.

Don't install the air conditioner in the following locations:

There is petrolatum existing.

There is salty air surrounding (near the coast).

There is caustic gas (the sulfide, for example) existing in the air (near a hot spring).

The Volt vibrates violently (in the factories).

In buses or cabinets.

In kitchen where it is full of oil gas.

There is strong electromagnetic wave existing.

There are inflammable materials or gas.

There is acid or alkaline liquid evaporating.

Other special conditions.

Outdoor unit

Indoor unit

Control box

Page 5: INSTALLATION & OWNER’S MANUAL - Midea...AHUKZ-01 AHUKZ-02 5 installation manual 5. MATERIAL AND SIZE OF THE PIPING Size(mm) Pipe Material Copper Pipe for Air Conditioner Model Φ8

3. ATTACHED FITTINGSPlease check whether the following fittings are of full scope. If there are some spare fittings , please restore them carefully.

3installation manual

Table.3-1

QUANTITYSHAPENAME

2. Plastic expanded tube

3. Temp.sensor(AHUKZ-01 only)

4. Temp.sensor (AHUKZ-02 only)

8. Wire controller installation manual

5. Display panel connecting wire group

7. Installation&owner’s manual

4

8

3

6

1

1

2

FUNCTION

1. Screw ST3.9x25 for installation board Secure the installation board

6. Wire controller connecting wire group

1

X2

EBADC

T2B

T2T1

T2B

T2T1

Outdoor unit

Indoor unit

Control box

Page 6: INSTALLATION & OWNER’S MANUAL - Midea...AHUKZ-01 AHUKZ-02 5 installation manual 5. MATERIAL AND SIZE OF THE PIPING Size(mm) Pipe Material Copper Pipe for Air Conditioner Model Φ8

4installation manual

Units: mm

4. INSTALLATION METHOD & DIMENSION

AHUKZ-01AHUKZ-02

NOTEAs hanging installation please use Screw ST3.9x25 for installation.As hanging installation, the box should be vertical, and as hoisting installation, it should be installed horizontally, and prohibit to be sloped, inverted.Please refer to the foregoing,make sure the laying direction of the refrigerant pipe and the connecting place of the connecting wire.All the pictures in this manual are for explanation purpose only. They may be slightly different from the air conditioner you purchased(depend on model).The actual shape shall prevail.

12

3

4

Installation method : Hoisting

Filter access door

Remote receiver

Filter access door

Filter access doorConnect to outdoor unit

Connect to indoor unit

Filter access door

Filter access door

Wire controller

Installation method : HangingFig.4-1

Fig.4-2 Fig.4-3

Install vertically

Install horizontally

Outdoor unit

Indoor unit

Control box

95 111 98

205

184

122

395270

18

140

122

122

428

461

485

80270

5Φ5

Φ6Φ12

142

6330

0

Page 7: INSTALLATION & OWNER’S MANUAL - Midea...AHUKZ-01 AHUKZ-02 5 installation manual 5. MATERIAL AND SIZE OF THE PIPING Size(mm) Pipe Material Copper Pipe for Air Conditioner Model Φ8

6-1 The specification of power

Single-phase

220-240V ~ 50Hz

Model

PhasePower

Voltage and Frequency

AHUKZ-01 AHUKZ-02

5installation manual

5. MATERIAL AND SIZE OF THE PIPING

Size(mm)

Pipe Material Copper Pipe for Air Conditioner

Model Φ8

AHUKZ-01

(Liquid side) Φ12.7

AHUKZ-02

Table.5-1

6. ELECTRICAL WIRING

CAUTION

The air conditioner should use separate power supply with rated voltage.The external power supply to the air conditioner should have ground wiring, which is linked to the ground wiring of the indoor and outdoor unit.The wiring work should be done by qualified persons according to circuit drawing.The fixed connecting lines must equip with at lease 3mm electric shock spacing.A leakage protector should be installed according to the National Standard concerning electrical appliance.Be sure to locate the power wiring and the signal wrings well to avoid cross-disturbance and their contact with connecting pipe or stop value body. Generally, do not twist two wiring together unless the joint is soldered well and covered with insulator tape.Do not turn on the power until you have checked carefully after wiring.

CAUTION

CAUTION

The specification of power as the follow display figure, if the capacity is too small will lead to over heat of the wiring,and cause burning of the machine accident.

The air-gap notch in the circuit breaker is used for insulating the flexible conductor, so that must respond to the related national wire requests to connect to the fixed circuit.

CAUTION

The air-conditioner can connect to the central controller (CCM). Before the operation, please correctly connect the wire and well set the system address and network address of indoor unit.

6-2 Terminal block setting figure

Please refer to the indoor unit wiring figure for connecting wire.

P1 N1 P2 N2XT2

Connect to water pump Alarm signal

XT3

TO CCM COMM.BUS

Please use 3-core shielding wire, and ground the shielding layer.

TO OUTDOOR COMM.BUS

The connecting distance of control box and indoor unit should not more than 5 m. This control box can only connect to R410A refrigerant system. During the installation of connecting pipes, do not let air, dust, or other sundries enter to the piping system. Install the connecting pipe only after the indoor and outdoor units have been fixed. When installing the connecting pipes, it must be kept dry and do not let water enter to the piping system. The connecting copper pipes should be wrapped with thermal insulation materials (the thick should be more than 10mm; the close wet area should be thicken properly).

1

23

4

5

6

1

2

3

4

5

6

7

white blue black blackyellow ash

O1

Connect to remote switch

O2 W1 W2

XT4

The connecting terminals of the water level switch

W1 and W2 are shorted by default, when connect the

indoor unit with water pump please remove the short

connecting wire and connect to the water level switch.

white white whiteblack

Connect to water level switch

Table.6-1

L N XT1

1 2 3 4

Connect to indoor fanNeutral

HighMedium

Low

Connect to indoor power 220-240V~ 50Hz 208-230V~ 60Hz

Outdoor unit

Indoor unit

Control box

Fig.6-1

Fig.6-2

Fig.6-3

Fig.6-4

208-230V ~ 60Hz

Page 8: INSTALLATION & OWNER’S MANUAL - Midea...AHUKZ-01 AHUKZ-02 5 installation manual 5. MATERIAL AND SIZE OF THE PIPING Size(mm) Pipe Material Copper Pipe for Air Conditioner Model Φ8

6installation manual

6-3 Electric control box wiring figure

6-4 Indoor and outdoor unit wiring figure

CAUTION

CAUTION

AHUKZ-01 adopts one master control board, AHUKZ-02 adopts two master control boards, when installing, both the two master control boards of AHUKZ-02 should connect to the temp sensor T1, T2 and T2B, and place the corresponding two sensors of the two master control boards in the same location.T1 is indoor temperature sensor, install to the air inlet of the indoor unit.T2 is indoor evaporator intermediate temperature sensor, install to the intermediate of temperature evaporatorz.T2B is indoor evaporator outlet sensor, install to the outlet of the evaporator.

1

234

Body sensewire controller

T2

T2B

T1

B A

Temp sensor wire group (T1, T2, T2B) anddisplay panel connecting wire group, throughthe side hole of control box and use the tighten belt to fix the wire groups.

Connecting wire controller Connector

Indoor temp sensor (T1), indoor evaporator intermediate temp sensor (T2), indoor evaporator outlet temp sensor (T2B), please connects respond to the wiring nameplate.

Fig.6-5

220-240V~50Hz Signal wire

Liquid pipe

Gas pipe

Liquid pipe

Fan wireWater pump

Water level switch

T2 Intermediate section of evaporator

T2B Air pipe outlet

T1 Air-return inlet

Outdoor unitOutdoor unit

Indoor unitIndoor unit

Control boxControl box

Fig.6-6

If it is needed, user can select the backup function in the dotted line frame.

208-230V~60Hz

Page 9: INSTALLATION & OWNER’S MANUAL - Midea...AHUKZ-01 AHUKZ-02 5 installation manual 5. MATERIAL AND SIZE OF THE PIPING Size(mm) Pipe Material Copper Pipe for Air Conditioner Model Φ8

7installation manual

7. APPLICALTION CONTROL

Set the PCB code of the indoor unit electric control box by different usage. After setting, be sure to turn off the total power switch again and then switch on again. The setting function can not be carried out if not to turn off the total power switch again and then switch on again (Fig.7-1).

ENC1

0

1

2

3

4

5

6

7

8

9

2200W(0.8HP)

2800W(1.0HP)

3600W(1.3HP)

4500W(1.6HP)

5600W(2.0HP)

7100W(2.5HP)

8000W(3.0HP)

9000W(3.2HP)

11200W(4.0HP)

14000W(5.0HP)

Toggle switch For setting cooling capacity

Code Setting cooling capacity

Caution:

The horsepower

has been set

before leaving

the factory;

anyone can’t

modify it except

the maintenance

person.

7-2 System Address and Network Address Setting

7-1 Application control

7-3 Mainboard Code Indication Label

1234

SW1ON

1234

SW1ON

1234

SW1ON

● 1 means the factory test mode● 0 automatic search address mode (factory default)

● 1 means the factory test mode● 0 means select AC fan

● 00 means DC fan static pressureselection 0 set (reserved)

Definition of every SW1 position

1234

SW1ON

1234

SW1ON

SW1ON

● 01 means DC fan static pressureselection 1 set (reserved)

● 10 means DC fan static pressureselection 2 set (reserved)

● 11 means DC fan static pressureselection 3 set (reserved)

1234

SW2ON

1234

SW2ON

1234

SW2ON

1234

SW2ON

● 00 means temperature ofshut down against cool airis 15°C

Definition of every SW2 position

● 00 means temperature ofshut down against cool airis 20°C

● 00 means temperature ofshut down against cool airis 24°C

● 00 means temperature ofshut down against cool airis 26°C

1) The default system address is “00” for AHUKZ-01, “00” and “01” for system A and B of AHUKZ-02 respectively.

2) If there are several indoor units multi-connected, the system address may be conflict between the different units. In that case, reset the in door unit’s address is needed.

3) If the system address conflict occur, the indoor units must use remote controller to set the system address first (For setting system address to the indoor unit with two or more master boards, it have to use display panel with 10-core wire to connect the display panel, and address setting for every master board respectively).

4) Communicating the indoor and outdoor units to finish setting network address, its address is the same as the indoor unit address, no need to setting separately.

5) When all the indoor units are AHUKZ-01/AHUKZ-02 or V4+ series indoor units, centralized control of indoor unit can finish upside the outdoor unit, no need to do the centralized control inside the indoor unit, the detailed instruction refers to V4+ Outdoor Unit Instruction.

6) For the previous indoor unit centralized control function, can connect to the (X,Y,E) terminals and form centralized control network, at that time no need to set the network address, then also can through the outlay network module, mainboard (CN20) and form a network.

0 1

34

56789AB

CD

E F

ENC1Fig.7-1

● Function specification:

ENC1——Cooling capacity setting, set the cooling capacity of this machine (Table. 7-1).

Table.7-1

Outdoor unit

Indoor unit

Control box

Table.7-2

Table.7-3

Table.7-4

Page 10: INSTALLATION & OWNER’S MANUAL - Midea...AHUKZ-01 AHUKZ-02 5 installation manual 5. MATERIAL AND SIZE OF THE PIPING Size(mm) Pipe Material Copper Pipe for Air Conditioner Model Φ8

8installation manual

1234

SW2ON

1234

SW2ON

1234

SW2ON

1234

SW2ON

● 00 means the time of TERMALstop the fan is 4 minutes

● 00 means the time of TERMALstop the fan is 8 minutes

● 00 means the time of TERMALstop the fan is 12 minutes

● 00 means the time of TERMALstop the fan is 16 minutes

1 2

SW5ON

1 2

SW5ON

● 00 means the temperaturecompensation under heatingmode is 6°C

Definition of every SW5 position

● 01 means the temperaturecompensation under heatingmode is 2°C

1 2

SW5ON

1 2

SW5ON

● 10 means the temperaturecompensation under heatingmode is 4°C

● 11 means the temperaturecompensation under heatingmode is 8°C

1 2 3

SW6ON

1 2 3

SW6ON

1 2 3

SW6ON

● 1 means the old display panel● 0 means the new display panel

Reserved

Definition of every position

●1 means automatic mode automatic fan●0 means non-automatic mode automatic fan

J1

J1

J2

J1 Jumperless for has power down memoryfunction

J1 Jumperless for has nopower down memory function

Reserved

Definition of J1,J2 positions

1 2

SW7ON

1 2

SW7ON

Standard configuration

The last set ofthe network

Definition of every SW7 position

ON

ON

Means 0

Means 1

Definition of every 0/1 code

Please adjust the code ENC1 to the proper position (both the AHUKZ-02 model system A and system B should be adjusted)For AHUKZ-01 model:9kW please set the main board’s code ENC1 in the electric controller to 7; 11.2kW please set the main board’s code ENC1 in the electric controller to 8;14kW please set the main board’s code ENC1 in the electric controller to 9.

For AHUKZ-02 model:20kW please set two main boards’ code ENC1 in the electric controller to 8; 25kW please set one main board’s code ENC1 in the electric controller to 8, and set the another code ENC1 to 9; 28kW please set two main boards’ code ENC1 in the electric controller to 9.

For the same indoor unit, each main board must has different indoor unit addresses and network addresses.

When use centralized controller to control indoor unit, and set address for the AHUKZ-02 with two or more main boards, we suggest that set the neighbor address for the same main board of indoor unit. When use centralized controller for controlling, main board in the same indoor unit must ON and OFF at the same time, for avoiding that affect the usage function of the machine.

1

2

3

CAUTION

Outdoor unit

Indoor unit

Control box

Table.7-5

Table.7-6

Table.7-7

Table.7-8

Table.7-9

Table.7-10

Table.7-11

Page 11: INSTALLATION & OWNER’S MANUAL - Midea...AHUKZ-01 AHUKZ-02 5 installation manual 5. MATERIAL AND SIZE OF THE PIPING Size(mm) Pipe Material Copper Pipe for Air Conditioner Model Φ8

9installation manual

8. TROUBLE SHOOTING

Table.8-1

NO. Type Contents LED Display Remarks

The evaporator sensor check point is abnomaor room temp.sensor is abnormal.

Indoor/outdoor unit communication is abnormal.

Condenser sensor check point isabnormal or outdoor temp.

Water level switch is abnormal

Mode conflict

Error code “H1,H2,H3,E2,E3 or E4”

Error code“E1”

Error code“Ed ”

Error code“EE”

Error code“E0”

After the malfunctionsdisappear, it restoresautomatically.

After the malfunctions disappear, it restoresautomatically.

After the malfunctions disappear, it restoresautomatically.

If the malfunctions can’t be solved in three min. all the indoor alarm lamps flash at 0.5Hz.Turn off the power to restore.

When the indoor unit turns to heating mode or is turned off, thealarm will disappear.

1

2

3

4

5

Malfun-ction

Malfun-ction

Malfun-ction

Malfun-ction

Alarm

Fig.8-1

PRE-DEF indicator(cooling and heating type) or fan only indicator(cooling only type)

Infrared signal receiver

Operation lamp Timer indicator Alarm indicator

Temporary buttonLED display

Outdoor unit

Indoor unit

Control box

Page 12: INSTALLATION & OWNER’S MANUAL - Midea...AHUKZ-01 AHUKZ-02 5 installation manual 5. MATERIAL AND SIZE OF THE PIPING Size(mm) Pipe Material Copper Pipe for Air Conditioner Model Φ8

MDV11IU-001BW

202000171586

Outdoor unit

Indoor unit

Control box

Page 13: INSTALLATION & OWNER’S MANUAL - Midea...AHUKZ-01 AHUKZ-02 5 installation manual 5. MATERIAL AND SIZE OF THE PIPING Size(mm) Pipe Material Copper Pipe for Air Conditioner Model Φ8

Outdoor unit

Indoor unit

Control box

Page 14: INSTALLATION & OWNER’S MANUAL - Midea...AHUKZ-01 AHUKZ-02 5 installation manual 5. MATERIAL AND SIZE OF THE PIPING Size(mm) Pipe Material Copper Pipe for Air Conditioner Model Φ8

Outdoor unit

Indoor unit

Control box

Page 15: INSTALLATION & OWNER’S MANUAL - Midea...AHUKZ-01 AHUKZ-02 5 installation manual 5. MATERIAL AND SIZE OF THE PIPING Size(mm) Pipe Material Copper Pipe for Air Conditioner Model Φ8

Outdoor unit

Indoor unit

Control box

Page 16: INSTALLATION & OWNER’S MANUAL - Midea...AHUKZ-01 AHUKZ-02 5 installation manual 5. MATERIAL AND SIZE OF THE PIPING Size(mm) Pipe Material Copper Pipe for Air Conditioner Model Φ8

Outdoor unit

Indoor unit

Control box