+ All Categories
Home > Documents > Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The...

Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The...

Date post: 30-Jan-2018
Category:
Upload: vumien
View: 228 times
Download: 2 times
Share this document with a friend
68
Installer manual LEK SMO 20 Control module IHB GB 1436-4 231758
Transcript
Page 1: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

Installer manual

LEK

SMO 20Control module

IHB GB 1436-4231758

Page 2: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

A detailed explanation of the button functions can be found on page 24.

How to scroll through menus and make different settings is described on page 26.

The mode for setting the indoor temperature is reached, when in the start mode in the main menu, by pressingthe OK button twice. Read more about the settings on page 28.

To temporarily increase the amount of hot water (if a hot water heater is installed to your SMO 20), first turn thecontrol knob to mark menu 2 (water droplet) and then press the OK button twice. Read more about the settingson page 34.

In event of disturbances in comfortIf a disturbance in comfort of any type occurs there are some measures that can be taken before you need tocontact your installer. See page 50 for instructions.

Page 3: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

Table of Contents

21 Important information2Safety information

52 Delivery and handling5Mounting

5Supplied components

63 The Control Module Design6Electrical components

74 Pipe connections7General

8Docking alternatives

115 Electrical connections11General

14Connections

17Optional connections

21Connecting accessories

226 Commissioning and adjusting22Preparations

22Commissioning with NIBE air/water heatpump

22Commissioning with additional heatingonly

22Check the reversing valve

22Check AUX socket

22Cooling mode

23Start guide

247 Control - Introduction24Display unit

25Menu system

288 Control - Menus28Menu 1 - INDOOR CLIMATE

34Menu 2 - HOT WATER

36Menu 3 - INFO

37Menu 4 - MY SYSTEM

43Menu 5 - SERVICE

479 Service47Service actions

5010 Disturbances in comfort50Manage alarm

50Troubleshooting

51Additional heating only

5211 Accessories

5412 Technical data54Dimensions and setting-out coordinates

55Technical specifications

56Electrical circuit diagram

60Index

1Table of Contents |SMO 20

Page 4: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

Safety informationThis manual describes installation and service proced-ures for implementation by specialists.

This appliance can be used by childrenaged from 8 years and above and per-sons with reduced physical, sensory ormental capabilities or lack of experienceand knowledge if they have been givensupervision or instruction concerninguse of the appliance in a safe way andunderstand the hazards involved. Chil-dren shall not play with the appliance.Cleaning and user maintenance shallnot be made by children without super-vision.

Rights to make any design or technicalmodifications are reserved.

©NIBE 2014.

Symbols

NOTE

This symbol indicates danger to machine orperson.

Caution

This symbol indicates important informationabout what you should observe when main-taining your installation.

TIP

This symbol indicates tips on how to facilitateusing the product.

MarkingSMO 20 is CE marked and fulfils IP21.

The CE marking means that NIBE ensures that theproduct meets all regulations that are placed on itbased on relevant EU directives. The CE mark is obligat-ory for most products sold in the EU, regardless wherethey are made.

IP21 means that the product can be touched by hand,that objects with a diameter larger than or equivalentto 12.5 mm cannot penetrate and cause damage andthat the product is protected against vertically fallingdrops.

Serial numberThe serial number can be found on the upper side ofthe cover on the control module.

LEK

Caution

Always give the product's serial number whenreporting a fault.

Country specific information

Installer manual

This installer manual must be left with the customer.

SMO 20Chapter 1 | Important information2

1 Important information

Page 5: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

Inspection of the installationCurrent regulations require the heating installation to be inspected before it is commissioned. The inspection mustbe carried out by a suitably qualified person. Fill in the page for information about installation data in the Usermanual.

DateSignatureNotesDescription✔

Electricity (page 11)

Communication, heat pump

Supply connected 230 V

Outside sensor

Temperature sensor, hot water charging

Temperature sensor, hot water top

Temperature sensor, external flow line

Temperature sensor, external supply lineafter electric heater

Temperature sensor, external return line

Charge pump

Shuttle valve

AUX 1

AUX 2

AUX 3

AUX 4

AUX 5

AUX 6

AA2-X4

Miscellaneous

Checking additional heater

Checking the function of the reversingvalve

Checking charge pump function

Completed installation check of heatpump and associated equipment

3Chapter 1 | Important informationSMO 20

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

Page 6: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

Contact information

KNV Energietechnik GmbH, Gahberggasse 11, 4861 SchörflingAT

Tel: +43 (0)7662 8963-0 Fax: +43 (0)7662 8963-44 E-mail: [email protected] www.knv.atNIBE Wärmetechnik AG, Winterthurerstrasse 710, CH-8247 FlurlingenCH

Tel: (52) 647 00 30 Fax: (52) 647 00 31 E-mail: [email protected] www.nibe.chDruzstevni zavody Drazice s.r.o, Drazice 69, CZ - 294 71 Benatky nad JizerouCZ

Tel: +420 326 373 801 Fax: +420 326 373 803 E-mail: [email protected] www.nibe.czNIBE Systemtechnik GmbH, Am Reiherpfahl 3, 29223 CelleDE

Tel: 05141/7546-0 Fax: 05141/7546-99 E-mail: [email protected] www.nibe.deVølund Varmeteknik A/S, Member of the Nibe Group, Brogårdsvej 7, 6920 VidebækDK

Tel: 97 17 20 33 Fax: 97 17 29 33 E-mail: [email protected] www.volundvt.dkNIBE Energy Systems OY, Juurakkotie 3, 01510 VantaaFI

Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: [email protected] www.nibe.fiNIBE Energy Systems France Sarl, Zone industrielle RD 28, 01600 ReyrieuxFR

Tel : 03 88 06 24 10 Fax : 03 88 06 24 11 E-mail: [email protected] www.nibe.frNIBE Energy Systems Ltd, 3C Broom Business Park, Bridge Way, Chesterfield S41 9QGGB

Tel: 0845 095 1200 Fax: 0845 095 1201 E-mail: [email protected] www.nibe.co.ukNIBE Energietechniek B.V., Postbus 634, NL 4900 AP OosterhoutNL

Tel: 0168 477722 Fax: 0168 476998 E-mail: [email protected] www.nibenl.nlABK AS, Brobekkveien 80, 0582 Oslo, Postadresse: Postboks 64 Vollebekk, 0516 OsloNO

Tel. sentralbord: +47 23 17 05 20 E-mail: [email protected] www.nibeenergysystems.noNIBE-BIAWAR Sp. z o. o. Aleja Jana Pawła II 57, 15-703 BIAŁYSTOKPL

Tel: 085 662 84 90 Fax: 085 662 84 14 E-mail: [email protected] www.biawar.com.pl© "EVAN" 17, per. Boynovskiy, Nizhny NovgorodRU

Tel./fax +7 831 419 57 06 E-mail: [email protected] www.nibe-evan.ruNIBE AB Sweden, Box 14, Hannabadsvägen 5, SE-285 21 MarkarydSE

Tel: +46-(0)433-73 000 Fax: +46-(0)433-73 190 E-mail: [email protected] www.nibe.se

For countries not mention in this list, please contact Nibe Sweden or check www.nibe.eu for more information.

SMO 20Chapter 1 | Important information4

Page 7: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

MountingNOTE

For wall mounting, use the mounting adaptedfor the base.

110

410

360

1031

021570

35

Use all mounting points and install SMO 20 upright flatagainst the wall without any part of the control moduleprotruding out beyond the edge of the wall.

Leave approximately 100 mm free space around thecontrol module to facilitate access and cable routingon installation and service.

NOTE

Access the screws for installing the front coverfrom underneath.

Supplied components

Heating pipe pasteOutside sensor

LE

K

Temperature sensorInsulation tape

LE

K

Cable tiesAluminium tape

5Chapter 2 | Delivery and handlingSMO 20

2 Delivery and handling

Page 8: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

LEK

L N 1 1 0 2 3 4PE

2120

1918

1716

1514

1312

1110

98

76

54

32

1

LEK

L N 1 1 0 2 3 4PE

Electrical componentsBase cardAA 2Display unitAA 4

AA4-XJ3 USB socket

AA4-XJ4 Service outlet (No function)Extra relay circuit boardAA 7Miniature circuit-breakerFA 1Terminal block, incoming electrical supplyX 1Terminal block, control signal circulation pump,sensors AUX inputs and heat pump

X 2

SwitchSF 1

Serial number platePF 3Cable grommet, incoming supply electricity,power for accessories

UB 1

Cable gland, signalUB 2

Designations in component locations according tostandard IEC 81346-1 and 81346-2.

SMO 20Chapter 3 | The Control Module Design6

3 The Control Module Design

Page 9: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

GeneralPipe installation must be carried out in accordance withcurrent norms and directives. See manual for compat-ible NIBE air/water heat pump for installation of theheat pump.

Compatible NIBE air/water heat pumpsCompatible NIBE air/water heat pumps must beequipped with a control card that has at least thesoftware version given in the following list. The controlcard version is displayed in the heat pump's display (ifapplicable) upon start-up.

Software versionProduct

55F2015

55F2016

111F2020

55F2025

55F2026

all versionsF2030

all versionsF2040

55F2300

Symbol key

MeaningSymbol

Shut-off valve

Non-return valve

Shunt / shuttle valve

Safety valve

Trim valve

Temperature sensor

Pressure gaugeP

Circulation pump

Particle filter

Temperature sensor installation on pipe

K

The temperature sensors are mounted with heat con-ducting paste, cable ties (the first cable tie is securedto the pipe in the middle of the sensor and the othercable tie is mounted approx. 5 cm beyond the sensor)and aluminium tape. Then insulate with supplied insu-lation tape.

NOTE

Sensor and communication cables must notbe placed near power cables.

7Chapter 4 | Pipe connectionsSMO 20

4 Pipe connections

Page 10: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

Docking alternativesSMO 20 can be connected with other products fromNIBE in several different ways, some of which are shownbelow (accessories may be required).

Further option information is available at www.nibe.euand in the respective assembly instructions for the ac-cessories used. See page 52 for a list of the accessoriesthat can be used with SMO 20.

Installations with SMO 20 can produce heating andhot water. Cooling can also be produced, but it de-pends on the heat pump that is used.

On cold days of the year when the access to energyfrom the air is reduced the additional heating cancompensate and help to produce heat. The additionalheating is also good to have as assistance if the heatpump ends up outside its working range or if it hasbeen blocked for any reason.

NOTE

The heating medium side and the hot waterside must be fitted with the necessary safetyequipment in accordance with the applicableregulations.

This is the outline diagram. Actual installationsmust be planned according to applicablestandards.

ExplanationSMO 20AA25Outdoor sensor1)BT1Temperature sensor, hot water charging1)BT6Temperature sensor, hot water top1)BT7Temperature sensor, external supply line1)BT25Room sensorBT50Temperature sensor, external supply lineafter electric heater

BT63

Temperature sensor, external return line1)BT71Circulation pump, Heating mediumGP10Reversing valve, Hot water/Heating medi-um2)

QN10

Additional heatEB1Immersion heaterEB1Auxiliary relay/Contactor2)KA1Heat pump systemEB101Temperature sensor, return line3)BT3Temperature sensor, condenser supplyline3)

BT12

Heat pumpEB101Safety valveFL10Charge pump2)GP12Particle filter3)HQ1Drain valve, Heating mediumQM1Shut-off valve, Heating medium, FlowQM31Shut off valve, Heating medium, ReturnQM32Shut-off valveQM43Cooling systemEQ1Temperature sensor, cooling supply line2)BT64Single jacket accumulator tank, coolingCP6Circulation pump, coolingGP13Reversing valve, Cooling/Heating2)QN12

MiscellaneousExpansion vessel closed, Hot waterCM1Buffer vessel (UKV)CP5Accumulator tank with hot water heatingCP10Immersion heaterEB20Safety valve, Heating mediumFL2Auxiliary relay/ContactorKA1Control valveRN10

1) Included in and supplied SMO 20

2) Included in and supplied accessory

3) Included in and supplied NIBE heat pump (can vary dependingon heat pump).

Designations according to standards 81346-1 and81346-2.

SMO 20Chapter 4 | Pipe connections8

Page 11: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

Compatible NIBE air water heat pump together with SMO 20 and immersion heater ahead ofthe exchange valve for hot water and cooling (floating condensing)

-FL2

-CM1

-EB101

-QM1

-BT3

-BT12 -QM31

-QM32 -QM43-GP12

-EB101

-HQ1

-BT1

-AA25

-AA25-BT50-AA25

-BT63-KA1

-EB1

-FL10

-RN10

-CP10

-AA25-QN10

-AA25-BT7

-AA25-BT6

-GP13

-CP6

-BT64

-EQ1-QN12

-EQ1

-EB1

NOTE

NIBE does not supply all components in thisoutline diagram.

This installations alternative is suitable for more com-plex installations with a focus on comfort.

SMO 20 (AA25) starts and stops the heat pump (EB101)to meet the heat and hot water demand of the install-ation. At simultaneous heating and hot water demandthe reversing valve switches (AA25-QN10) periodicallybetween the climate system and the water heater/ac-cumulator tank (CP10). When the hot water heater/ac-cumulator tank is fully charged (CP10), the reversingvalve switches (AA25-QN10) to the climate system.

Additional heat (EB1) is connected automatically whenthe energy demand exceeds the heat pump capacity.Immersion heater (EB20) in the water heater/accumu-lator tank (CP10) is used during the time to producehot water if the heat pump (EB101) is used for heatingthe building at the same time.

The additional heat can also be used if a higher temper-ature in the hot water is required than the heat pumpcan produce.

During cooling operation (requires compatible heatpump) reversing valve (EQ1-QN12) switches to thecooling system (EQ1). If several simultaneous demandsoccur while there is a cooling demand the installationreacts differently. In event of a hot water demand thereversing valve (EQ1-QN12) switches back and hotwater is produced until the demand is fulfilled. In eventof a heating demand the reversing valve (EQ1-QN12)instead switches periodically between the demands.

In event of a cooling demand the reversing valveswitches back to basic mode (heat/hot water).

9Chapter 4 | Pipe connectionsSMO 20

Page 12: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

CompatibleNIBE air/water heat pump togetherwith SMO20andelectric heater after reversingvalve for hot water and cooling (floating condensing)

-EB20-KA1

-FL2

-CM1

-EB101

-QM1

-BT3

-BT12 -QM31

-QM32 -QM43-GP12

-EB101

-HQ1

-BT1

-AA25

-AA25 -AA25

-FL10

-RN10

-CP10

-AA25-QN10

-AA25-BT7

-AA25-BT6

-BT25

-EB1

-CP5-GP10

-KA1

-BT71

-EB1

-AA25

-GP13

-CP6

-BT64

-EQ1-QN12

-EQ1

-BT50

NOTE

NIBE does not supply all components in thisoutline diagram.

This installations alternative is suitable for more com-plex installations with a focus on comfort.

SMO 20 (AA25) starts and stops the heat pump (EB101)to meet the heat and hot water demand of the install-ation. At simultaneous heating and hot water demandthe reversing valve switches (AA25-QN10) periodicallybetween the climate system and the water heater/ac-cumulator tank (CP10). When the hot water heater/ac-cumulator tank is fully charged (CP10), the reversingvalve switches (AA25-QN10) to the climate system.

Additional heat (EB1) is connected automatically whenthe energy demand exceeds the heat pump capacity.Immersion heater (EB20) in the water heater/accumu-lator tank (CP10) is used during the time to producehot water if the heat pump (EB101) is used for heatingthe building at the same time.

The additional heat can also be used if a higher temper-ature in the hot water is required than the heat pumpcan produce.

During cooling operation (requires compatible heatpump) reversing valve (EQ1-QN12) switches to thecooling system (EQ1). If several simultaneous demandsoccur while there is a cooling demand the installationreacts differently. In event of a hot water demand thereversing valve (EQ1-QN12) switches back and hotwater is produced until the demand is fulfilled. In eventof a heating demand the reversing valve (EQ1-QN12)instead switches periodically between the demands.In event of a cooling demand the reversing valveswitches back to basic mode (heat/hot water).

SMO 20Chapter 4 | Pipe connections10

Page 13: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

GeneralDisconnect SMO 20 before insulation testing thehouse wiring.If the building is equipped with an earth-faultbreaker, SMO 20 should be equipped with a separateone.SMO 20 must be installed via an isolator switch witha minimum breaking gap of 3mm.For the electrical wiring diagram for the controlmodule, see page 56.Communication and sensor cables to external con-nections must not be laid close to high current cables.The minimum area of communication and sensorcables to external connections must be 0.5 mm² upto 50 m, for example EKKX or LiYY or equivalent.Use a screened three core cable for communicationwith the heat pump.When cable routing in SMO 20, cable grommets (UB1and UB2, marked in image) must be used.

NOTE

The switch (SF1) must not be moved to "" or" " until the boiler in the system has beenfilled with water. The compressor in the heatpump and any external addition can be dam-aged.

NOTE

Electrical installation and service must be car-ried out under the supervision of a qualifiedelectrician. Cut the current with the circuitbreaker before carrying out any servicing.Electrical installation and wiring must be car-ried out in accordance with the stipulations inforce.

When installing SMO 20, NIBE's air/water heatpump and any addition must be current free.

NOTE

See outline diagram for your system for phys-ical location of the temperature sensor that isto be installed.

LEK

L N 1 1 0 2 3 4PE

2120

1918

1716

1514

1312

1110

98

76

54

32

1

Miniature circuit-breakerThe control module operating circuit and parts of itsinternal components are internally fused by a miniaturecircuit-breaker (FA1).

11Chapter 5 | Electrical connectionsSMO 20

5 Electrical connections

Page 14: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

Accessibility, electrical connectionThe cover of the control module is opened using a Torx25 driver. Assembly takes place in reverse order.

3

1

2

LEK

NOTE

The cover to access the base card is openedusing a Torx 25 screwdriver.

LEK

The display may need to be moved for easier accesswhen connecting electrics. This is easily done by follow-ing these steps.1.

LEK

b

a

Press in the catch on the upper rear side of thedisplay unit towards you (a) and move the displayunit upwards (b) so that the mountings unhookfrom the panel.

2.

LEK

Lift the display unit from its mountings.3.

LEK

Align the two lower mountings on the reverse ofthe display unit with the two upper holes in thepanel as illustrated.

SMO 20Chapter 5 | Electrical connections12

Page 15: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

4.

LEK

Secure the display on the panel.5. When the electrical connection is ready the display

must be reinstalled with three mounting pointsagain, otherwise the front cover cannot be in-stalled.

Cable lockUse a suitable tool to release/lock cables in the heatpump terminal blocks.

Terminal block on the electrical card

2

1

2

3

LEK

3

4

1

2

Terminal block

LEK

1 mm

3,5 mm

13Chapter 5 | Electrical connectionsSMO 20

Page 16: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

ConnectionsNOTE

To prevent interference, unscreened commu-nication and/or sensor to external connectionscables must not be laid closer than 20 cm tohigh voltage cable when cable routing.

Power connectionSMO 20 must be installed via an isolator switch with aminimum breaking gap of 3mm. Minimum cable areamust be dimensioned according to the fuse rating used.Supplied cable for incoming electricity is connected toterminal block X1.

1NL

LEK

L N 1 1 0 2 3 4PE

2120

1918

1716

1514

1312

1110

98

76

54

32

1

1 1NL 0 432PE

Tariff controlIf the voltage to the compressor in the heat pump dis-appears for a certain period, simultaneous blocking ofthese must take place via software controlled input(AUX input) to avoid alarm, see page 19.

Connecting the charge pump for the heatpump 1 and 2Connect circulation pump (EB101-GP12) as illustratedto terminal block X4:6 (PE), X4:6 (N) and X4:7 (230 V)on the base card (AA2).

Control signal for (EB101-GP12) is connected to termin-al block X2:1 (PWM) and X2:2 (GND) as illustrated.

NOTE

If the charge pumps are not correctly connec-ted at start up the control module receives analarm.

987654

SMO

Externt

PE LN

LEK

L N 1 1 0 2 3 4PE

2

1

4

3

SMO

ExterntLEK

L N 1 1 0 2 3 4PE

2120

1918

1716

1514

1312

1110

98

76

54

32

1

5

6

7

2

1

8

9

13

12

4

3

11

10

19

20

21

14

18

16

17

15

SMO 20Chapter 5 | Electrical connections14

Page 17: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

Communication with heat pumpConnect the heat pump (EB101) with a screened threecore cable to terminal block X2:19 (A), X2:20 (B) andX2:21 (GND) as illustrated.

LEK

L N 1 1 0 2 3 4PE

2120

1918

1716

1514

1312

1110

98

76

54

32

1

5

6

7

2

1

8

9

13

12

4

3

11

10

19

20

21

14

18

16

17

15

654321

A

B

GND

A

B

GND

A

B

GND

SMO

F2015/F2020/F2025/F2300

F2016/F2026

56

42

31

A

B

GND

F2030

54

23

1

A

B

GND

A

B

GND

F2040

19

20

21

18

X2

SMO 20

AA21-J2

X5

X5

AA23-X4

Outside sensorInstall the outside temperature sensor (BT1) in theshade on a wall facing north or north-west, so it is un-affected by the morning sun.

Connect the sensor to terminal block X2:3 and X2:6.Use a twin core cable of at least 0.5 mm² cable area.

If a conduit is used it must be sealed to prevent con-densation in the sensor capsule.

SMO Externt

5

6

7

2

1

4

3

LEK

L N 1 1 0 2 3 4PE

2120

1918

1716

1514

1312

1110

98

76

54

32

1

5

6

7

2

1

8

9

13

12

4

3

11

10

19

20

21

14

18

16

17

15

Temperature sensor, hot water chargingThe temperature sensor, hot water charging (BT6) isplaced in the submerged tube on the water heater.

Connect the sensor to terminal block X2:5 and X2:6.Use a twin core cable of at least 0.5 mm² cable area.

Hot water charging is activated in menu 5.2 or in thestart guide.

SMO Externt

5

6

7

2

1

4

3

LEK

L N 1 1 0 2 3 4PE

2120

1918

1716

1514

1312

1110

98

76

54

32

1

5

6

7

2

1

8

9

13

12

4

3

11

10

19

20

21

14

18

16

17

15

Temperature sensor, hot water topA temperature sensor for hot water top (BT7) can beconnected to SMO 20 to show the water temperatureat the top of the tank (if it is possible to install a sensorat the top of the tank).

Connect the sensor to terminal block X2:4 and X2:6.Use a twin core cable of at least 0.5 mm² cable area.

SMO Externt

5

6

7

2

1

4

3

LEK

L N 1 1 0 2 3 4PE

2120

1918

1716

1514

1312

1110

98

76

54

32

1

5

6

7

2

1

8

9

13

12

4

3

11

10

19

20

21

14

18

16

17

15

15Chapter 5 | Electrical connectionsSMO 20

Page 18: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

Temperature sensor, external flow lineConnect temperature sensor, external supply (BT25)(required for additional heat after reversing valve(QN10)), to terminal block X2:8 and X2:10. Use a twocore cable with a minimum 0.5 mm² cable area.

SMO Externt

9

10

11

6

8

7

LEK

L N 1 1 0 2 3 4PE

2120

1918

1716

1514

1312

1110

98

76

54

32

1

5

6

7

2

1

8

9

13

12

4

3

11

10

19

20

21

14

18

16

17

15

Temperature sensor, external supply at addi-tional heat before reversing valve (QN10)Connect temperature sensor, external supply afterelectric heater (BT63) (required for additional heat be-fore reversing valve for hot water charging (QN10)), toterminal block X2:9 and X2:10. Use a two core cablewith a minimum 0.5 mm² cable area.

SMO Externt

9

10

11

6

8

7

LEK

L N 1 1 0 2 3 4PE

2120

1918

1716

1514

1312

1110

98

76

54

32

1

5

6

7

2

1

8

9

13

12

4

3

11

10

19

20

21

14

18

16

17

15

SMO 20Chapter 5 | Electrical connections16

Page 19: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

Optional connectionsRoom sensorSMO 20 can be supplemented with a room sensor(BT50). The room temperature sensor has up to threefunctions:1. Show current room temperature in the control

module display.2. Option of changing the room temperature in °C.3. Makes it possible to change/stabilise the room

temperature.

Install the sensor in a neutral position where the settemperature is required. A suitable location is on a freeinner wall in a hall approx. 1.5 m above the floor. It isimportant that the sensor is not obstructed frommeasuring the correct room temperature by beinglocated, for example, in a recess, between shelves, be-hind a curtain, above or close to a heat source, in adraft from an external door or in direct sunlight. Closedradiator thermostats can also cause problems.

The control module operates without the sensor, butif one wishes to read off the accommodation's indoortemperature in SMO 20 display the sensor must be in-stalled. Connect the room sensor to terminal block X2:7and X2:10.

If the sensor is to be used to change the room temper-ature in °C and/or to change/stabilise the room tem-perature, the sensor must be activated in menu 1.9.4.

If the room sensor is used in a room with underfloorheating, it should only have an indicatory function, notcontrol of the room temperature.

9

10

11

6

8

7

LEK

L N 1 1 0 2 3 4PE

2120

1918

1716

1514

1312

1110

98

76

54

32

1

5

6

7

2

1

8

9

13

12

4

3

11

10

19

20

21

14

18

16

17

15

Caution

Changes of temperature in accommodationtake time. For example, short time periods incombination with underfloor heating will notgive a noticeable difference in room temperat-ure.

Step controlled additional heat

NOTE

Mark up any junction boxes with warnings forexternal voltage.

External step controlled additional heat can be con-trolled by up to three potential-free relays in the controlmodule (3 step linear or 7 step binary). Alternativelytwo relays (2 step linear or 3 step binary) can be usedfor step controlled additional heat which means thatthe third relay can be used to control the immersionheater in the water heater/accumulator tank.

Step in occurs with at least 1 minute interval and stepouts with at least 3 seconds interval.

Step 1 is connected to terminal block X2:2 on the extrarelay card (AA7).

Step 2 is connected to terminal block X2:4 on the extrarelay card (AA7).

Step 3 or immersion heater in the water heater/accu-mulator tank is connected to terminal block X2:6 onthe extra relay card (AA7).

Any control voltage is connected to terminal block X2:1,3 and 5 on extra relay card (AA7).

The settings for step controlled additional heat aremade in menu 4.9.3 and menu 5.1.12.

All additional heat can be blocked by connecting apotential free switch function to the software con-trolled input on terminal block X2 (see page 19) whichis selected in menu 5.4.

SMO

Externt

654321

1 0 PE

A1

A2

A1

A2

A1-K1 -K2 -K3

A2

External

SMO 20

AA7-X2X1

LEK

L N 1 1 0 2 3 4PE

X1

1 1NL 0 432PE

-X2

1

123456

2 3 4 5 6

-X1

AA7-X2

If the relays are to be used for control voltage, bridgethe supply from terminal block X1:1 toX2:1, X2:3 andX2:5 on additional relay card (AA7). Connect theneutral from the external addition to terminal blockX1:0.

17Chapter 5 | Electrical connectionsSMO 20

Page 20: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

Relay output for emergency mode

NOTE

Mark up any junction boxes with warnings forexternal voltage.

When the switch (SF1) is in " " mode (emergencymode) the circulation pump is activated (EB101-GP12).External accessories are disconnected.

The emergency mode relay can be used to activateexternal additional heat, an external thermostat mustthen be connected to the control circuit to control thetemperature. Ensure that the heating medium circu-lates through the external additional heating.

432PE

SMO

Externt

LEK

L N 1 1 0 2 3 4PE

2120

1918

1716

1514

1312

1110

98

76

54

32

1

1 1NL 0 432PE

Caution

No hot water is produced when emergencymode is activated.

1 0 432PE

SMO

Externt

N L

LEK

L N 1 1 0 2 3 4PE

2120

1918

1716

1514

1312

1110

98

76

54

32

1

1 1NL 0 432PE

If the relay is to be used for control voltage, bridge thesupply from terminal block X1:1 to X1:2 and connectneutral and control voltage from the external additionalheat to X1:0 (N) and X1:4 (L).

External circulation pumpConnect the external circulation pump (GP10) accord-ing to image for terminal block X4:9 (PE), X4:10 (N) andX4:11 (230 V) on the base card (AA2).

1312111098

SMO

Externt

PE LN

LEK

L N 1 1 0 2 3 4PE

Shuttle valveSMO 20 can be supplemented with an external revers-ing valve (QN10) for hot water control (see page 52for accessory).

Connect the external reversing valve (QN10) as illus-trated to the terminal block X4:2 (N), X4:3 (control)and X4:4 (L) on the base card (AA2).

654321

SMO

Externt

N L

LEK

L N 1 1 0 2 3 4PE

NIBE Uplink™Connect the network connected cable (straight, Cat.5eUTP) with RJ45-contact (male) to contact AA4-X9 onthe display unit (as illustrated). Use the cable grommet(UB2) in the control module for cable routing.

LEK

SMO 20Chapter 5 | Electrical connections18

Page 21: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

External connection optionsOn terminal block X2, SMO 20 has software controlledinputs and outputs for connection of sensors and ex-ternal switch function. This means that a sensor or anexternal switch function can be connected to one ofsix special connections where the function for connec-tion is decided in the control module software.

Caution

If an external contact function is connected toSMO 20, the function for use input or outputmust be selected in menu 5.4.

Selectable inputs terminal block X2 for these functionsare AUX1 (X2:11), AUX2 (X2:12), AUX3 (X2:13), AUX4(X2:15), AUX5 (X2:16) andAUX6 (X2:17). Earth is con-nected to terminal block X2:14 respectively X2:18 (seeelectrical wiring diagram for more information).

Selectable output is terminal block X4:15-17 on basecard (AA2.

B

SMO Externt

13

14

15

10

12

11

ALEK

L N 1 1 0 2 3 4PE

2120

1918

1716

1514

1312

1110

98

76

54

32

1

5

6

7

2

1

8

9

13

12

4

3

11

10

19

20

21

14

18

16

17

15

The example above uses the inputs AUX1 (X2:11) and AUX3(X2:13) on terminal block (X2).

Caution

Some of the following functions can also beactivated and scheduled via menu settings.

Possible selection for AUX inputsFollowing functions can be connected to the AUX in-puts on terminal block X2.Temperature sensor, external return line

If temperature sensor, external return line (BT71)needs to be used, connect it to selected input (menu5.4, see page 45) on terminal block X2. Use a 2 corecable of at least 0.5 mm2 cable area.

Temperature sensor, flow line cooling

If temperature sensor, supply line cooling (BT64)needs to be used, connect it to selected input (menu5.4, see page 45) on terminal block X2. Use a 2 corecable of at least 0.5 mm2 cable area.Switch for external blocking of additional heat

In those cases where external blocking of additionalheat is desired, this can be connected to terminalblock X2.

The additional heat is disconnected by connecting apotential free switch function to the input selectedin menu 5.4.

A closed contact results in the electrical output beingdisconnected.Contact for external blocking of compressor inthe heat pump

In those cases external blocking of compressor in theheat pump is desired, this can be connected to ter-minal block X2.

The compressor in the heat pump is disconnected byconnecting a potential free switch function to theinput selected in menu 5.4.

A closed contact results in the electrical output beingdisconnected.Contact for external tariff blocking

In cases where external tariff blocking is required itmust be connected to terminal block X2.

Tariff blocking means that the additional heat, thecompressor, heating and cooling are disconnectedby connecting a potential free switch function to theinput selected in menu 5.4.

A closed contact results in the electrical output beingdisconnected.Switch for "SG ready"

NOTE

This function can only be used in mains net-works that support the "SG Ready"-standard.

"SG Ready" requires two AUX inputs.

In cases where this function is required it must beconnected to terminal block X2.

"SG Ready" is a smart form of tariff control where yourelectricity supplier can affect the indoor, hot waterand/or pool temperatures (if applicable) or simply blockthe additional heat and/or compressor in the heatpump at certain times of the day (can be selected inmenu 4.1.5 after the function is activated). Activate thefunction by connecting potential free switch functionsto two inputs selected in menu 5.4 (SG Ready A andSG Ready B), see page45.

Closed or open switch means one of the following(A = SG Ready A and B = SG Ready B ):Blocking (A: Closed, B: Open)

"SG Ready" is active. The compressor in the heatpump and additional heat is blocked like the day'stariff blocking.Normal mode (A: Open, B: Open)

19Chapter 5 | Electrical connectionsSMO 20

Page 22: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

"SG Ready" is not active. No effect on the system.Low price mode (A: Open, B: Closed)

"SG Ready" is active. The system focuses on costssavings and can for example exploit a low tariff fromthe electricity supplier or over capacity from any ownpower source (effect on the system can be adjustedin the menu 4.1.5).Overcapacity mode (A: Closed, B: Closed)

"SG Ready" is active. The system is permitted to runat full capacity at over capacity with the electricitysupplier (effect on the system is settable in menu4.1.5).Switch for external blocking of heating

In those cases where external blocking of heat is de-sired, this can be connected to terminal block X2.

Heating is disconnected by connecting a potentialfree switch function to the input selected in menu5.4.

A closed switch results in blocked heating operation.Switch for external blocking of compressor

In cases where external blocking of cooling is used,this can be connected to terminal block X2.

Heating operation is disconnected by connecting apotential-free switch function to the input selectedin menu 5.4.

A closed switch results in blocked cooling operation.Contact for activation of “temporary lux"

An external switch function can be connected toSMO 20 for activation of the hot water function"temporary lux". The switch must be potential freeand connected to the selected input (menu 5.4) onterminal block X2.

"temporary lux" is activated for the time that thecontact is connected.Contact for activation of “external adjustment"

An external contact function can be connected toSMO 20 to change the supply temperature and theroom temperature.

When the switch is closed the temperature changesin °C (if the room sensor is connected and activated).If a room sensor is not connected or not activated,the desired offset of "temperature" (heating curveoffset) is set with the number of steps selected. Thevalue is adjustable between -10 and +10.climate system 1

The switch must be potential free and connectedto the selected input (menu 5.4) on terminal blockX2.

The value for the change is set in menu 1.9.2, "ex-ternal adjustment".

Switch for external alarm

Alarms from external devices can be connected tothe control and appear as an info alarm. Potential-free signal of NO or NC type can be connected.

Possible selection for AUXoutput (potentialfree variable relay)It is possible to have an external connection throughthe relay function via a potential-free variable relay(max 2 A) on the terminal block X4:15-17 on the basecard (AA2).

Optional functions for external connection:Indication of buzzer alarm. The function gives signalswhilst a constant alarm is indicated by the controlmodule.Cooling mode indication. This option requires activa-tion of some form of cooling function. The functiongives signals when the system permits cooling andcan be used to control external pumps for example.Active cooling (4 pipe) This option requires activationof some form of cooling function and can be usedfor simple 4-pipe systems (an outdoor unit). Thefunction gives signals when a connected heat pumpproduces cooling and there are no other demandsand cooling is permitted. This function can be usedto control reversing valve for cooling EP25-QN12.

Caution

With this option, charge pump (GP12) is al-ways controlled in "auto" operating mode,which means that the pump is running whenthe reversing valve (QN12) is towards thecooling system.

External heating medium pump. The function givessignals when an external circulation pump (GP10) isto be operated according to settings for the operat-ing mode.Control of circulation pump for hot water circulation.The function gives signals when a circulation pumpfor hot water circulation (GP11) is to be operatedaccording to settings in menu "hot water recirc."(2.9.2).

If any of the above is installed to terminal block X4:15-17 on base card (AA2) the function must be selectedin menu 5.4

The common alarm is preselected at the factory.

17161514

SMO

ExterntLEK

L N 1 1 0 2 3 4PE

The picture shows the relay in the alarm position.

When switch (SF1) is in the " " or “ ” position therelay is in the alarm position.

SMO 20Chapter 5 | Electrical connections20

Page 23: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

Hot water circulation pump or external heating medi-um pump connected to the buzzer alarm relay as illus-trated below.

NOTE

Mark up any junction boxes with warnings forexternal voltage.

17161514

SMO

Externt

L

L

N

N

PEPE

LEK

L N 1 1 0 2 3 4PE

Reversing valve for cooling connected to the buzzeralarm relay as illustrated below.

17161514

SMO

Externt

L

L

N

N

LEK

L N 1 1 0 2 3 4PE

Caution

The relay output may be loaded with a maxim-um of 2 A at a resistive load (230V AC).

Connecting accessoriesInstructions for connecting other accessories are in theinstallation instructions provided. See page 52 for thelist of the accessories that can be used with SMO 20.

21Chapter 5 | Electrical connectionsSMO 20

Page 24: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

PreparationsCompatible NIBE air/water heat pump must beequipped with a control card that has at least thesoftware version as listed on page 7. The controlcard version is displayed in the heat pump's display(if applicable) upon start-up.SMO 20 must be ready-connected.The climate system must be filled with water andbled.

Commissioning with NIBEair/water heat pumpNIBE F2005/F2020/F2005

Follow the instructions in the heat pump's Installationand Maintenance under section "Commissioning andadjustment" – "Start-up and inspection".

NIBE F2016/F2026/F2030/F2040/F2300Follow the instructions in the heat pump's Installationmanual under section "Commissioning and adjust-ment" – "Start-up and inspection".

SMO 201. Power the heat pump.2. Power SMO 20.3. Follow the start guide in the display on SMO 20

alternatively start the start guide in menu 5.7.

Commissioningwith addition-al heating onlyAt first start follow the start guide, otherwise followthe list below.1. Go to menu 4.2 operating mode.2. Mark ”add. heat only” using the control knob and

then press the OK button.3. Return to the main menus by pressing the Back

button.

Caution

When commissioning without NIBE air/waterheat pump an alarm communication error mayappear in the display.

The alarm is reset if the relevant heat pump isdeactivated in menu 5.2.2 ("installed slaves").

Check the reversing valve1. Activate "AA2-K1 (QN10)" in menu 5.6.2. Check that the reversing valve opens or is open for

hot water charging.3. Deactivate "AA2-K1 (QN10)" in menu 5.6.

Check AUX socketTo check any function connected to the AUX socket1. Activate "AA2-X4" in menu 5.6.2. Check the desired function.3. Deactivate "AA2-X4" in menu 5.6.

Cooling modeIf the installation contains a NIBE air/water heat pumpthat can produce cooling (for example NIBE F2040)cooling can be permitted in menu 5.11.1.1.

You can now select cooling mode indication in menu5.4 for AUX output.

SMO 20Chapter 6 | Commissioning and adjusting22

6 Commissioning and adjusting

Page 25: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

Start guideNOTE

There must be water in the climate systembefore the switch is set to " ".

1. Turn the control module switch (SF1) to "".2. Follow the instructions in the start guide in the

control module display. If the start guide does notstart when you start the control module, start itmanually in menu 5.7.

TIP

See page 24 for a more in-depth introductionto the installation’s control system (operation,menus etc.).

CommissioningThe first time the installation is started a start guide isstarted. The start guide instructions state what needsto carried out at the first start together with a runthrough of the installation’s basic settings.

The start guide ensures that the start-up is carried outcorrectly and cannot be bypassed. The start guide canbe started later in menu 5.7.

During the start up guide the reversing valves and theshunt valve are run backward and forwards to helpvent SMO 20.

Caution

As long as the start guide is active, no functionin the heat pump will start automatically.

The guide will appear at each heat pump re-start until it is deselected on the last page.

Operation in the start guide

A. B.

D.C.

A. Page

Here you can see how far you have come in the startguide.

Scroll between the pages of the start guide as follows:1. Turn the control knob until one of the arrows in

the top left corner (at the page number) has beenmarked.

2. Press the OK button to skip between the pages inthe start guide.

B. Name and menu number

Read what menu in the control system this page of thestart guide is based on. The digits in brackets refer tothe menu number in the control system.

If you want to read more about affected menus eitherread off in the sub-menu or in the installation manualfrom page 28.

C. Option / setting

Make settings for the system here.

D. Help menu

In many menus there is a symbol that indicatesthat extra help is available.

To access the help text:1. Use the control knob to select the help symbol.2. Press the OK button.

The help text often consists of several windows thatyou can scroll between using the control knob.

23Chapter 6 | Commissioning and adjustingSMO 20

Page 26: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

Display unit

DisplayInstructions, settings and operational informa-tion are shown on the display. The easy-to-readdisplay and menu system, facilitates navigationbetween the different menus and options toset the comfort or obtain the information yourequire.

A

Status lampThe status lamp indicates the status of thecontrol module. It:

lights green during normal operation.lights yellow in emergency mode.lights red in the event of a deployed alarm.

B

OK buttonThe OK button is used to:

confirm selections of sub menus/options/setvalues/page in the start guide.

C

Back buttonThe back button is used to:

go back to the previous menu.change a setting that has not been con-firmed.

D

Control knobThe control knob can be turned to the right orleft. You can:

scroll in menus and between options.increase and decrease the values.change page in multiple page instructions(for example help text and service info).

E

Switch (SF1)The switch assumes three positions:

On ()

Standby ( )

Emergency mode ( )

Emergency mode must only be used in theevent of a fault on the control module. In thismode, the compressor in the heat pumpswitches off and the immersion heater engages.The control module display is not illuminatedand the status lamp illuminates yellow.

F

SMO 20Chapter 7 | Control - Introduction24

7 Control - Introduction

Page 27: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

Menu system

Menu 1 - INDOOR CLIMATESetting the indoor climate. See page 28.

Menu 2 - HOT WATERSetting the hot water production. See page 34.

This menu only appears if a water heater is installed inthe system.

Menu 3 - INFODisplay of temperature and other operating informa-tion and access to the alarm log. See page 36.

Menu 4 - MY SYSTEMSetting time, date, language, display, operating modeetc. See page 37.

Menu 5 - SERVICEAdvanced settings. These settings are not available tothe end user. The menu is visible by pressing the Backbutton for 7 seconds. See page 43.

Symbols in the displayThe following symbols can appear in the display duringoperation.

DescriptionSymbol

This symbol appears by the informationsign if there is information in menu 3.1that you should note.

These two symbols indicate whether thecompressor in the outdoor unit or addi-tional heat in the installation is blockedvia SMO 20.

These can, for example, be blocked de-pending on which operating mode is se-lected in menu 4.2, if blocking is sched-uled in menu 4.9.5 or if an alarm has oc-curred that blocks one of them.

Blocking the compressor.

Blocking additional heat.

This symbol appears if lux mode for thehot water is activated.

This symbol indicates whether "holidaysetting" is activated in menu 4.7.

This symbol indicates whether SMO 20has contact with NIBE Uplink™.

This symbol indicates whether poolheating is active.

Accessory needed.

This symbol indicates whether cooling isactive.

Accessory needed.

25Chapter 7 | Control - IntroductionSMO 20

Page 28: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

OperationTo move the cursor, turn the control knob tothe left or the right. The marked position isbrighter and/or has a light frame.

Selecting menuTo advance in the menu system select a main menu bymarking it and then pressing the OK button. A newwindow then opens with sub menus.

Select one of the sub menus by marking it and thenpressing the OK button.

Selecting options

In an options menu the current selected option isindicated by a green tick.

To select another option:1. Mark the applicable option. One of the options

is pre-selected (white).2. Press the OK button to confirm the selected

option. The selected option has a green tick.

Setting a value

To set a value:1. Mark the value you want to set using the

control knob.2. Press the OK button. The background of the

value becomes green, which means that youhave accessed the setting mode.

3. Turn the control knob to the right to increasethe value and to the left to reduce the value.

4. Press the OK button to confirm the value youhave set. To change and return to the originalvalue, press the Back button.

SMO 20Chapter 7 | Control - Introduction26

Page 29: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

Use the virtual keyboard

In some menus where text may require entering, a vir-tual keyboard is available.

Depending on the menu, you can gain access to differ-ent character sets which you can select using the con-trol knob. To change character table, press the Backbutton. If a menu only has one character set the key-board is displayed directly.

When you have finished writing, mark "OK" and pressthe OK button.

Scroll through the windowsA menu can consist of several windows. Turn the con-trol knob to scroll between the windows.

Scroll through the windows in the start guide

1. Turn the control knob until one of the arrows inthe top left corner (at the page number) has beenmarked.

2. Press the OK button to skip between the steps inthe start guide.

Help menuIn many menus there is a symbol that indicatesthat extra help is available.

To access the help text:1. Use the control knob to select the help symbol.2. Press the OK button.

The help text often consists of several windows thatyou can scroll between using the control knob.

27Chapter 7 | Control - IntroductionSMO 20

Page 30: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

Menu 1 - INDOOR CLIMATEOverview

1.1 - temperature1 - INDOOR CLIMATE

1.3.1 - heating1.3 - scheduling

1.3.2 - cooling *

1.9.1 - curve1.9 - advanced

1.9.2 - external adjustment

1.9.3 - min. flow line temp.

1.9.4 - room sensor settings*

1.9.5 - cooling settings *

1.9.7 - own curve

1.9.8 - point offset

* Accessories are needed.

Sub-menus

For the menu INDOOR CLIMATE there are several sub-menus. Status information for the relevant menu canbe found on the display to the right of the menus.

temperature Setting the temperature for the climatesystem. The status information shows the set valuesfor the climate system.

scheduling Scheduling heating and cooling. Statusinformation "set" is displayed if you set a schedule butit is not active now, "holiday setting" is displayed if thevacation schedule is active at the same time as theschedule (the vacation function is prioritised), "active"displays if any part of the schedule is active, otherwiseit displays " off".

advanced Setting of heat curve, adjusting with extern-al contact, minimum value for supply temperature,room sensor and cooling function.

Menu 1.1 - temperatureSelect whether you want to set heating or cooling toset the desired temperature in the next menu "temper-ature heating/cooling".

Set the temperature (with room sensors installedand activated):

heating

Setting range: 5 - 30 °C

Default value: 20

cooling (accessory required)

Setting range: 5 - 30 °C

Default value: 25

The value in the display appears as a temperature in°C if the climate system is controlled by a room sensor.

Caution

A slow heat-releasing heating system, such asfor example, underfloor heating, may not besuitable for control using the heat pump'sroom sensor.

To change the room temperature, use the control knobto set the desired temperature in the display. Confirmthe new setting by pressing the OK button. The newtemperature is shown on the right-hand side of thesymbol in the display.

Setting the temperature (without room sensorsactivated):

Setting range: -10 to +10

Default value: 0

The display shows the set values for heating (curveoffset). To increase or reduce the indoor temperature,increase or reduce the value on the display.

Use the control knob to set a new value. Confirm thenew setting by pressing the OK button.

The number of steps the value has to be changed toachieve a degree change of the indoor temperaturedepends on the heating installation. One step is usuallyenough but in some cases several steps may be re-quired.

Setting the desired value. The new value is shown onthe right-hand side of the symbol in the display.

Caution

An increase in the room temperature can beslowed by the thermostats for the radiators orunder floor heating. Therefore, open thethermostats fully, except in those rooms wherea cooler temperature is required, e.g. bed-rooms.

SMO 20Chapter 8 | Control - Menus28

8 Control - Menus

Page 31: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

TIP

Wait 24 hours before making a new setting,so that the room temperature has time tostabilise.

If it is cold outdoors and the room temperatureis too low, increase the curve slope in menu1.9.1 by one increment.

If it is cold outdoors and the room temperatureis too high, lower the curve slope menu 1.9.1by one increment.

If it is warm outdoors and the room temperat-ure is too low, increase the value in menu 1.1by one increment.

If it is warm outdoors and the room temperat-ure is too high, reduce the value in menu 1.1by one increment.

Menu 1.3 - schedulingIn the menu scheduling indoor climate (heating/cool-ing) is scheduled for each weekday.

You can also schedule a longer period during a selectedperiod (vacation) in menu 4.7.

Menu 1.3.1 - heatingIncreases or decreases in the accommodation temper-ature can be scheduled here for up to three time peri-ods per day. If a room sensor is installed and activatedthe desired room temperature (°C) is set during thetime period. Without an activated room sensor thedesired change is set (of setting in menu 1.1). One stepis usually enough to change the room temperature byone degree, but in some cases several steps may berequired.

Schedule: The schedule to be changed is selected here.

Activated: Scheduling for the selected period is activ-ated here. Set times are not affected at deactivation.

Day: Select which day or days of the week the scheduleis to apply to here. To remove the scheduling for aparticular day, the time for that day must be reset bysetting the start time to the same as the stop time. If

the line "all" is used, all days in the period are set forthese times.

Time period: The start and stop time for the selectedday for scheduling are selected here.

Adjusting:How much the heating curve is to be offsetin relation to menu 1.1 during scheduling is set here.If the rooms sensor is installed the desired room tem-perature is set in °C.

Conflict: If two settings conflict with each other a redexclamation mark is displayed.

TIP

If you wish to set similar scheduling for everyday of the week start by filling in “all” and thenchanging the desired days.

TIP

Set the stop time earlier than the start time sothat the period extends beyond midnight.Scheduling then stops at the set stop time theday after.

Scheduling always starts on the date that thestart time is set for.

Caution

Changes of temperature in accommodationtake time. For example, short time periods incombination with underfloor heating will notgive a noticeable difference in room temperat-ure.

Menu 1.3.2 - cooling (accessory required)Here you can schedule when cooling is permitted inthe accommodation for up to two different time peri-ods per day.

Schedule: The schedule to be changed is selected here.

Activated: Scheduling for the selected period is activ-ated here. Set times are not affected at deactivation.

Day: Select which day or days of the week the scheduleis to apply to here. To remove the scheduling for a

29Chapter 8 | Control - MenusSMO 20

Page 32: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

particular day, the time for that day must be reset bysetting the start time to the same as the stop time. Ifthe line "all" is used, all days in the period are set forthese times.

Time period: The start and stop time for the selectedday for scheduling are selected here.

Adjusting:Whether or not cooling is permitted duringscheduling is set here.

Conflict: If two settings conflict with each other a redexclamation mark is displayed.

TIP

If you wish to set similar scheduling for everyday of the week start by filling in “all” and thenchanging the desired days.

TIP

Set the stop time earlier than the start time sothat the period extends beyond midnight.Scheduling then stops at the set stop time theday after.

Scheduling always starts on the date that thestart time is set for.

Menu 1.9 - advancedMenu advanced is intended for the advanced user.This menu has several sub-menus.

curve Setting the curve slope for heating and cooling.

external adjustment Setting the heat curve offsetwhen the external contact is connected.

min. flow line temp. Setting minimum permitted flowline temperature.

room sensor settings Settings regarding the roomsensor.

cooling settings Settings for cooling.

own curve Setting own curve for heating and cooling.

point offset Setting the offset of the heating curve orcooling curve at a specific outdoor temperature.

Menu 1.9.1 - curve

heating

Setting range: 0 - 15

Default value: 9

cooling (accessory required)

Setting range: 0 - 9

Default value: 0

The prescribed heating curve for your house can beviewed in the menu heating curve . The task of theheating curve is to give an even indoor temperature,regardless of the outdoor temperature, and therebyenergy efficient operation. It is from this heating curvethat the control module's control computer determinesthe temperature of the water to the heating system,supply temperature, and therefore the indoor temper-ature. Select the heating curve and read off how thesupply temperature changes at different outdoortemperatures here. If there is access to cooling the samesettings can be made for the cooling curve.

Curve coefficient

The slopes of the heating /cooling curves indicate howmany degrees the supply temperature is to be in-creased/reduced when the outdoor temperaturedrops/increases. A steeper slope means a higher supplytemperature for heating or a lower supply temperaturefor cooling at a certain outdoor temperature.

30

40

50

60

70°C

- 40°CUTETEMPERATUR

- 10010 - 20 - 30

Brantare kurvlutning

The optimum slope depends on the climate conditionsin your location, if the house has radiators or underfloor heating and how well insulated the house is.

The curve is set when the heating installation is in-stalled, but may need adjusting later. Normally, thecurve will not need further adjustment.

SMO 20Chapter 8 | Control - Menus30

Page 33: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

Caution

In the event of making fine adjustments of theindoor temperature, the curve must be offsetup or down instead, this is done in menu 1.1temperature .

Curve offset

An offset of the curve means that the supply temperat-ure changes as much for all the outdoor temperatures,e.g. that a curve offset of +2 steps increases the supplytemperature by 5 C at all outdoor temperatures.

Flow line temperature– maximum and minimumvalues

Because the flow line temperature cannot be calculatedhigher than the set maximum value or lower than theset minimum value the heating curve flattens out atthese temperatures.

Caution

Underfloor heating systems are normally maxflow line temperature set between 35 and 45°C.

Must be restricted with underfloor coolingmin. flow line temp. to prevent condensation.

Check the max temperature for your floor withyour installer/floor supplier.

The figure at the end of the curve indicates the curveslope. The figure beside the thermometer gives thecurve offset. Use the control knob to set a new value.Confirm the new setting by pressing the OK button.

Curve 0 is an own curve created in menu 1.9.7.

To select another curve (slope):1. Press the OK button to access the setting mode2. Select a new curve. The curves are numbered from

0 to 15, the greater the number, the steeper theslope and the greater the supply temperature.Curve 0 means that own curve (menu 1.9.7) isused.

3. Press the OK button to exit the setting.

To read off a curve:1. Turn the control knob so that the ring on the shaft

with the outdoor temperature is marked.2. Press the OK button.3. Follow the grey line up to the curve and out to the

left to read off the value for the supply temperatureat the selected outdoor temperature.

4. You can now select to take read outs for differentoutdoor temperatures by turning the control knobto the right or left and read off the correspondingflow temperature.

5. Press the OK or Back button to exit read off mode.

TIP

Wait 24 hours before making a new setting,so that the room temperature has time tostabilise.

If it is cold outdoors and the room temperatureis too low, increase the curve slope by one in-crement.

If it is cold outdoors and the room temperatureis too high, lower the curve slope by one incre-ment.

If it is warm outdoors and the room temperat-ure is too low, increase the curve offset by oneincrement.

If it is warm outdoors and the room temperat-ure is too high, lower the curve offset by oneincrement.

Menu 1.9.2 - external adjustment

climate system

Setting range: -10 to +10 or desired room temperat-ure if the room sensor is installed.

Default value: 0

Connecting an external contact, for example, a roomthermostat or a timer allows you to temporarily orperiodically raise or lower the room temperature whileheating. When the contact is on, the heat curve offsetis changed by the number of steps selected in themenu. If a room sensor is installed and activated thedesired room temperature (°C) is set.

Menu 1.9.3 - min. flow line temp.

heating

Setting range: 5-70 °C

Default value: 20 °C

cooling (accessory required)

Setting range: 7-30 °C

Default value: 18 °C

In menu 1.9.3 you select heating or cooling, in the nextmenu (min. supply temp.heating/cooling) set theminimum temperature on the supply temperature tothe climate system. This means that SMO 20 never cal-culates a temperature lower than that set here.

If there is more than one climate system the settingcan be made separately for each system.

TIP

The value can be increased if you have, for ex-ample, a cellar that you always want to heat,even in summer.

You may also need to increase the value in"stop heating" menu 4.9.2 "auto mode set-ting".

31Chapter 8 | Control - MenusSMO 20

Page 34: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

Menu1.9.4 - roomsensor settings (accessoryrequired)

factor system

heating

Setting range: 0.0 - 6.0

Factory setting heating: 2.0

cooling (accessory required)

Setting range: 0.0 - 6.0

Factory setting cooling: 1.0

Room sensors to control the room temperature can beactivated here.

Caution

A slow heat-releasing heating system, such asfor example, underfloor heating, may not besuitable for control using the heat pump'sroom sensor.

Here you can set a factor (a numerical value) that de-termines how much an over or sub normal temperature(the difference between the desired and actual roomtemperature) in the room is to affect the supply tem-perature to the climate system. A higher value gives agreater and faster change of the heating curve's setoffset.

NOTE

Too high a set value for "factor system" can(depending on your climate system) producean unstable room temperature.

Menu 1.9.5 - cooling settings (accessory re-quired)

delta at +20 °C

Setting range: 2 - 10 °C

Default value: 3

delta at +40 °C

Setting range: 2 - 20 °C

Default value: 6

start active cooling

Setting range: 30 – 300

Default value: 30

time betw. switch heat/cool

Setting range: 0 - 48 h

Default value: 2

You can use SMO 20 to cool the house during hotperiods of the year.

delta at +20 °C

Set the desired temperature on the temperature differ-ence between supply and return lines to the climatesystem during cooling operation when the outdoortemperature is +20 °C. SMO 20 then attempts to getas close to the set temperature as possible.

delta at +40 °C

Set the desired temperature on the temperature differ-ence between supply and return lines to the climatesystem during cooling operation when the outdoortemperature is +40 °C. SMO 20 then attempts to getas close to the set temperature as possible.

start active cooling

Caution

This setting option only appears if "activecooling" is activated in menu 5.2.4.

Here you can set when active cooling is to start.

Degree minutes are a measurement of the currentheating demand in the house and determine when thecompressor, cooling operation respectively additionalheat will start/stop.

time betw. switch heat/cool

This selection is only available in cooling 2 pipe systems.

Here you can set how long SMO 20 is to wait before itreturns to heating mode when the cooling demandhas ceased or vice versa.

Menu 1.9.7 - own curve

supply temperature

heating

Setting range: 5 – 70 °C

cooling (accessory required)

Setting range: 5 – 40 °C

Create your own heating or cooling curve here, bysetting the desired supply temperatures for differentoutdoor temperatures.

Caution

Curve 0 in menu 1.9.1 must be selected forown curve to apply.

Menu 1.9.8 - point offset

outdoor temp. point

Setting range: -40 – 30 °C

Default value: 0 °C

change in curve

Setting range: -10 – 10 °C

Default value: 0 °C

SMO 20Chapter 8 | Control - Menus32

Page 35: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

Select a change in the heating curve at a certain out-door temperature here. One step is usually enough tochange the room temperature by one degree, but insome cases several steps may be required.

The heat curve is affected at ± 5 °C from set outdoortemp. point.

It is important that the correct heating curve is selectedso that the room temperature is experienced as even.

TIP

If it is cold in the house, at, for example -2 °C,"outdoor temp. point" is set to "-2" and"change in curve" is increased until the desiredroom temperature is maintained.

Caution

Wait 24 hours before making a new setting,so that the room temperature has time tostabilise.

33Chapter 8 | Control - MenusSMO 20

Page 36: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

Menu 2 - HOT WATEROverview

2.1 - temporary lux2 - HOT WATER *

2.2 - comfort mode

2.3 - scheduling

2.9.1 - periodic increase2.9 - advanced

* Accessory needed.

Sub-menus

This menu only appears if a water heater is docked tothe heat pump.

For the menu HOT WATER there are several sub-menus. Status information for the relevant menu canbe found on the display to the right of the menus.

temporary lux Activation of temporary increase in thehot water temperature. Status information displays“off" or what length of time of the temporary temper-ature increase remains.

comfort mode Setting hot water comfort. The statusinformation displays what mode is selected, "economy","normal" or "luxury".

scheduling Scheduling hot water comfort. The statusinformation "set" appears if you have set schedulingbut it is not currently active, "holiday setting" appearsif holiday setting is active at the same time as schedul-ing (when the holiday function is prioritised), "active"appears if any part of scheduling is active, otherwise"off" appears.

advanced Setting periodic increase in the hot watertemperature.

Menu 2.1 - temporary lux

Setting range: 3, 6 and 12 hours and mode "off"

Default value: "off"

When hot water requirement has temporarily increasedthis menu can be used to select an increase in the hotwater temperature to lux mode for a selectable time.

Caution

If comfort mode "luxury" is selected in menu2.2 no further increase can be carried out.

The function is activated immediately when a timeperiod is selected and confirmed using the OK button.The remaining time for the selected setting is shownto the right.

When the time has run out SMO 20 returns to themode set in menu 2.2.

Select “off" to switch off temporary lux .

Menu 2.2 - comfort mode

Setting range: economy, normal, luxury

Default value: normal

The difference between the selectable modes is thetemperature of the hot tap water. Higher temperaturemeans that the hot water lasts longer.

economy: This mode gives less hot water than theothers, but is more economical. This mode can be usedin smaller households with a small hot water require-ment.

normal: Normal mode gives a larger amount of hotwater and is suitable for most households.

luxury: Lux mode gives the greatest possible amountof hot water. In this mode, the immersion heater, aswell as the compressor, is used to heat hot water, whichmay increase operating costs.

Menu 2.3 - schedulingTwo different periods of hot water comfort per daycan be scheduled here.

Scheduling is activated/deactivated by ticking/untick-ing"activated". Set times are not affected at deactiva-tion.

all

mon

tues

we

thur

fri

sat

sun

activated

schedule 2schedule 1

SCHEDULING HOT WATER 2.3

normal

Time period AdjustingDay

Activated Schedule

Conflict

Schedule: The schedule to be changed is selected here.

Activated: Scheduling for the selected period is activ-ated here. Set times are not affected at deactivation.

Day: Select which day or days of the week the scheduleis to apply to here. To remove the scheduling for a

SMO 20Chapter 8 | Control - Menus34

Page 37: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

particular day, the time for that day must be reset bysetting the start time to the same as the stop time. Ifthe line "all" is used, all days in the period are set forthese times.

Time period: The start and stop time for the selectedday for scheduling are selected here.

Adjusting: Set the hot water comfort that is to applyduring scheduling here.

Conflict: If two settings conflict with each other a redexclamation mark is displayed.

TIP

If you wish to set similar scheduling for everyday of the week start by filling in “all” and thenchanging the desired days.

TIP

Set the stop time earlier than the start time sothat the period extends beyond midnight.Scheduling then stops at the set stop time theday after.

Scheduling always starts on the date that thestart time is set for.

Menu 2.9 - advancedMenu advanced is intended for the advanced user.This menu has several sub-menus.

Menu 2.9.1 - periodic increase

period

Setting range: 1 - 90 days

Default value: 14 days

start time

Setting range: 00:00 - 23:00

Default value: 00:00

To prevent bacterial growth in the water heater, theheat pump and any additional heater can increase thehot water temperature for a short time at regular inter-vals.

The length of time between increases can be selectedhere. The time can be set between 1 and 90 days.Factory setting is 14 days. Untick "activated" to switchoff the function.

35Chapter 8 | Control - MenusSMO 20

Page 38: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

Menu 3 - INFOOverview

3.1 - service info3 - INFO

3.2 - compressor info

3.3 - add. heat info

3.4 - alarm log

3.5 - indoor temp. log

Sub-menus

For the menu INFO there are several sub-menus. Nosettings can be made in these menus, they just displayinformation. Status information for the relevant menucan be found on the display to the right of the menus.

service info shows temperature levels and settings inthe installation.

compressor info shows operating times, number ofstarts etc for the compressor in the heat pump.

add. heat info displays information about the addi-tional heat's operating times etc.

alarm log shows the latest alarms.

indoor temp. log the average temperature indoorsweek by week during the past year.

Menu 3.1 - service infoInformation about the actual operating status of theinstallation (e.g. current temperatures etc.) can be ob-tained here. No changes can be made.

The information is on several pages. Turn the controlknob to scroll between the pages.

Symbols in this menu:HeatingCompressor

Hot waterAddition

Cooling

Menu 3.2 - compressor infoInformation about the compressor’s operating statusand statistics can be obtained here. No changes canbe made.

The information is on several pages. Turn the controlknob to scroll between the pages.

Menu 3.3 - add. heat infoInformation about the additional heat's settings, oper-ating status and statistics can be obtained here. Nochanges can be made.

The information is on several pages. Turn the controlknob to scroll between the pages.

Menu 3.4 - alarm logTo facilitate fault-finding the installation's operatingstatus at alarm alerts is stored here. You can see inform-ation for the 10 most recent alarms.

To view the run status in the event of an alarm, markthe alarm and press the OK button.

Menu 3.5 - indoor temp. logHere you can see the average temperature indoorsweek by week during the past year. The dotted lineindicates the annual average temperature.

The average outdoor temperature is only shown if aroom temperature sensor/room unit is installed.

To read off an average temperature1. Turn the control knob so that the ring on the shaft

with the week number is marked.2. Press the OK button.3. Follow the grey line up to the graph and out to the

left to read off the average indoor temperature atthe selected week.

4. You can now select to take read outs for differentweeks by turning the control knob to the right orleft and read off the average temperature.

5. Press the OK or Back button to exit read off mode.

SMO 20Chapter 8 | Control - Menus36

Page 39: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

Menu 4 - MY SYSTEMOverview

4.1.3.1 - nibe uplink4.1.3 - internet4.1 - plus functions *4 - MY SYSTEM

4.1.3.8 - tcp/ip settings

4.1.3.9 - proxy settings

4.1.5 - SG Ready

4.1.6 - smart price adaption

4.2 - operating mode

4.4 - time & date

4.6 - language

4.7 - holiday setting

4.9.1 - op. prioritisation4.9 - advanced

4.9.2 - auto mode setting

4.9.3 - degree minute setting

4.9.4 - factory setting user

4.9.5 - schedule blocking

4.9.6 - schedule silent mode

* Accessory needed.

Sub-menus

For the menu MY SYSTEM there are several sub-menus. Status information for the relevant menu canbe found on the display to the right of the menus.

plus functions Settings applying to any installed extrafunctions in the heating system.

operating mode Activation of manual or automaticoperating mode. The status information shows the se-lected operating mode.

time & date Setting current time and date.

language Select the language for the display here.The status information shows the selected language.

holiday setting Vacation scheduling heating and hotwater comfort. Status information "set" is displayed ifyou set a vacation schedule but it is not active at themoment, "active" is displayed if any part of the vacationschedule is active, otherwise it displays " off".

advanced Settings of control module work mode.

Menu 4.1 - plus functionsSettings for any additional functions installed in SMO20 can be made in the sub menus.

Menu 4.1.3 - internetHere you make settings for connecting SMO 20 to theinternet.

NOTE

For these functions to work the network cablemust be connected.

Menu 4.1.3.1 - nibe uplinkHere you can manage the installation's connection toNIBE Uplink™ (http://www.nibeuplink.com) and seethe number of users connected to the installation viathe internet.

A connected user has a user account in NIBE Uplink™which have been given permission to control and/ormonitor your installation.

Request new connection string

To connect a user account on NIBE Uplink™ to yourinstallation, you must request a unique connectionstring.1. Mark “request new connection string" and press

the OK button.2. The installation now communicates with NIBE Up-

link™ to create a connection string.3. When a connection string has been received, it is

shown in this menu at "connection string" and isvalid for 60 minutes.

Disconnect all users1. Mark “switch off all users" and press the OK button.2. The installation now communicates with NIBE Up-

link™ to release your installation from all connec-ted users via the internet.

NOTE

After disconnecting all users none of them canmonitor or control your installation via NIBEUplink™ without requesting a new connectionstring.

Menu 4.1.3.8 - tcp/ip settingsYou can set TCP/IP settings for your installation here.

37Chapter 8 | Control - MenusSMO 20

Page 40: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

Automatic setting (DHCP)1. Tick “automatic". The installation now receives the

TCP/IP settings using DHCP.2. Mark “confirm" and press the OK button.

Manual setting1. Untick "automatic", you now have access to several

setting options.2. Mark “ip-address" and press the OK button.3. Enter the correct details via the virtual keypad.4. Mark “OK" and press the OK button.5. Repeat 1 - 3 for "net mask", "gateway" and "dns".6. Mark “confirm" and press the OK button.

Caution

The installation cannot connect to the internetwithout the correct TCP/IP settings. If unsureabout applicable settings use the automaticmode or contact your network administrator(or similar) for further information.

TIP

All settings made since opening the menu canbe reset by marking "reset" and pressing theOK button.

Menu 4.1.3.9 - proxy settingsYou can set proxy settings for your installation here.

Proxy settings are used to give connection informationto a intermediate server (proxy server) between theinstallation and Internet. These settings are primarilyused when the installation connects to the Internet viaa company network. The installation supports proxyauthentication of the HTTP Basic and HTTP Digest type.

If unsure about applicable settings use the preset set-tings or contact your network administrator (or similar)for further information.

Setting1. Tick “use proxy" if you do not want to use a proxy.2. Mark “server" and press the OK button.3. Enter the correct details via the virtual keypad.4. Mark “OK" and press the OK button.5. Repeat 1 - 3 for "port", "user name" and "pass-

word".6. Mark “confirm" and press the OK button.

TIP

All settings made since opening the menu canbe reset by marking "reset" and pressing theOK button.

Menu 4.1.5 - SG ReadyThis function can only be used in mains networks thatsupport the "SG Ready"-standard.

Make settings for the function "SG Ready" here.

affect room temperature

Here you set whether room temperature should beaffected when activating "SG Ready".

With low price mode of "SG Ready" the parallel offsetof the indoor temperature is increased by "+1". If aroom sensor is installed and activated, the desired roomtemperature increases by 1 °C.

With over capacity mode of "SG Ready" the paralleloffset for the indoor temperature is increased by"+2".If a room sensor is installed and activated, the desiredroom temperature increases by 2 °C.

affect hot water

Here you set whether the temperature of the hot watershould be affected when activating "SG Ready".

With low price mode on "SG Ready" the stop temper-ature of the hot water is set as high as possible at onlycompressor operation (immersion heater not permit-ted).

With over capacity mode of "SG Ready" the hot wateris set to "luxury" (immersion heater permitted).

affect cooling (accessories required)

Here you set whether room temperature during coolingoperation should be affected when activating "SGReady".

With low price mode of "SG Ready" and cooling oper-ation the indoor temperature is not affected.

With over capacity mode of "SG Ready" and coolingoperation the parallel offset for the indoor temperatureis reduced by"-1". If a room sensor is installed and ac-tivated, the desired room temperature decreases by 1°C.

NOTE

The function must be connected to two AUXinputs and activated in menu 5.4.

Menu 4.1.6 - smart price adaptionSmart price adaption moves the heat pump's consump-tion over 24 hours to periods with the cheapest electri-city tariff, which gives savings for hourly rate basedelectricity contracts. The function is based on hourlyrates for the next 24 hours being retrieved via NIBEUplink™ and therefore an internet connection and anaccount for NIBE Uplink™ are required.

Heating, pool and any cooling are controlled so thatthe energy supply over 24 hours is unchanged but thesupply occurs when the price is as low as possible. Thehot water uses the same function but also has a learn-ing function that learns the household's hot waterneeds and adapts to it. When the effect on the hotwater is active, it is no longer possible to control thehot water's comfort mode in menu 2.2.

Activate smart price adaption by highlighting thefunction and pressing the OK button. When smart priceadaption has been activated, the settings that can bemade are displayed. To select which selectable func-tions are to be permitted or not you highlight thefunction using the control knob and press the OK but-ton.

SMO 20Chapter 8 | Control - Menus38

Page 41: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

Price of electricity overview

Here you can obtain information on how the electricityprice varies over up to three days.

Range

Set your electricity price area here.

Affect room temperature

How much the room temperature is to be affected bythe electricity price is set here. The greater the value,the greater the effect the electricity price has and thesavings are larger, but at the same time there is an in-creased risk of affecting comfort.

Setting range: 1–10

Default value: 5

Affect hot water

How much the hot water is to be affected by the elec-tricity price is set here. The greater the value, thegreater the effect the electricity price has and the pos-sible savings are larger, but at the same time there isan increased risk of affecting comfort.

Setting range: 1–4

Default value: 2

Affect pool temperature

How much the pool temperature is to be affected bythe electricity price is set here. The greater the value,the greater the effect the electricity price has and thepossible savings are larger, but at the same time thereis an increased risk of affecting comfort.

Setting range: 1–10

Default value: 2

Affect cooling

How much the cooling temperature is to be affectedby the electricity price is set here. The greater the value,the greater the effect the electricity price has and thepossible savings are larger, but at the same time thereis an increased risk of affecting comfort.

Setting range: 1–10

Default value: 3

Menu 4.2 - operating mode

operating mode

Setting range: auto, manual, add. heat only

Default value: auto

functions

Setting range: compressor, addition, heating, cooling

The control module operating mode is usually set to"auto". It is also possible to set the control module to"add. heat only", when only additional heat is used, or"manual" and then select what functions are to bepermitted.

Change the operating mode by marking the desiredmode and pressing the OK button. When an operatingmode is selected it shows what in the control module

is permitted (crossed out = not permitted) and select-able alternatives to the right. To select selectablefunctions that are permitted or not you mark thefunction using the control knob and press the OK but-ton.

Operating mode auto

In this operating mode the control module automatic-ally selects what functions are permitted.

Operating mode manual

In this operating mode you can select what functionsare permitted. You cannot deselect "compressor" inmanual mode.

Operating mode add. heat only

In this operating mode the compressor is not activeand only additional heating is used.

Caution

If you choose mode "add. heat only" the com-pressor is deselected and there is a higher op-erating cost.

Caution

You cannot change from only additional heatif you do not have a heat pump connected(see menu 5.2.2).

Functions

"compressor" is that which produces heating and hotwater for the accommodation. If "compressor" isdeselected, a symbol is displayed in the main menu onthe symbol for the control module. You cannot deselect"compressor" in manual mode.

"addition" is what helps the compressor to heat theaccommodation and/or the hot water when it cannotmanage the whole requirement alone.

"heating" means that you get heat in the accommod-ation. You can deselect the function when you do notwish to have heating running.

"cooling" means that you get cooling in the accommod-ation in hot weather. You can deselect the functionwhen you do not wish to have the cooling running.This alternative requires an accessory for cooling orthat the heat pump has a built in function for coolingand is activated in the menu.

Menu 4.4 - time & dateSet time and date, display mode and time zone here.

TIP

Time and date are set automatically if the heatpump is connected to NIBE Uplink™. To obtainthe correct time, the time zone must be set.

Menu 4.6 - languageChoose the language that you want the informationto be displayed in here.

39Chapter 8 | Control - MenusSMO 20

Page 42: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

Menu 4.7 - holiday settingIf a room sensor is installed and activated the desiredroom temperature (°C) is set during the time period.This setting applies to all climate systems with roomsensors.

If a room sensor is not activated, the desired offset ofthe heating curve is set. This setting applies to all cli-mate systems without room sensors. One step is usuallyenough to change the room temperature by one de-gree, but in some cases several steps may be required.

Vacation scheduling starts at 00:00 on the start dateand stops at 23:59 on the stop date.

TIP

Complete holiday setting about a day beforeyour return so that room temperature and hotwater have time to regain usual levels.

TIP

Set the vacation setting in advance and activ-ate just before departure in order to maintainthe comfort.

Caution

If you choose to switch off hot water produc-tion during the vacation “periodic increase"(preventing bacterial growth) are blockedduring this time. "periodic increase" started inconjunction with the vacation setting beingcompleted.

Menu 4.9 - advancedMenu advanced is intended for the advanced user.This menu has several sub-menus.

Menu 4.9.1 - op. prioritisation

op. prioritisation

Setting range: 0 to 180 min

Default value: 30 min

The indicator marks where in the cycle the installationis.

If 0 minutes is selected it means that requirement isnot prioritised, but will only be activated when thereis no other requirement.

Menu 4.9.2 - auto mode setting

start cooling (accessory required)

Setting range: -20 – 40 °C

Default value: 25

stop heating

Setting range: -20 – 40 °C

Default values: 17

stop additional heat

Setting range: -25 – 40 °C

Default values: 5

filtering time

Setting range: 0 – 48 h

Default value: 24 h

When the operating mode is set to "auto", the controlmodule selects when start and stop of additional heatand heat production is permitted, dependent on theaverage outdoor temperature.

When the operating mode is set to "auto", the controlmodule selects when start and stop of additional heatand heat production is permitted, dependent on theaverage outdoor temperature. If accessories for coolingare present or if the heat pump has the integratedcooling function and it is activated in the menu youcan also select the start temperature for cooling.

Select the average outdoor temperatures in this menu.

You can also set the time over which (filtering time)the average temperature is calculated. If you select 0,the present outdoor temperature is used.

Caution

It cannot be set "stop additional heat" higherthan "stop heating".

Caution

In systems where heating and cooling sharethe same pipes "stop heating" cannot be sethigher than "start cooling" if there is not acooling/heating sensor.

SMO 20Chapter 8 | Control - Menus40

Page 43: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

Menu 4.9.3 - degree minute setting

current value

Setting range: -3000 – 3000

start compressor

Setting range: -1000 – -30

Default value: -60

start diff additional heat

Setting range: 100 – 1000

Default value: 400

diff. between additional steps

Setting range: 0 – 1000

Default value: 30

Degree minutes are a measurement of the currentheating requirement in the house and determine whenthe compressor respectively additional heat willstart/stop.

Caution

Higher value on "start compressor" gives morecompressor starts, which increase wear on thecompressor. Too low value can give unevenindoor temperatures.

Menu 4.9.4 - factory setting userAll settings that are available to the user (includingadvanced menus) can be reset to default values here.

Caution

After factory setting, personal settings such asheating curves must be reset.

Menu 4.9.5 - schedule blockingThe additional heat can be scheduled to be blockedfor up to two different time periods here.

When scheduling is active the relevant blocking symbolis shown in the main menu on the symbol for the con-trol module.

Schedule: The period to be changed is selected here.

Activated: Scheduling for the selected period is activ-ated here. Set times are not affected at deactivation.

Day: Select which day or days of the week the scheduleis to apply to here. To remove the scheduling for aparticular day, the time for that day must be reset bysetting the start time to the same as the stop time. Ifthe line "all" is used, all days in the period are set forthese times.

Time period: The start and stop time for the selectedday for scheduling are selected here.

Blocking: The desired blocking is selected here.

Conflict: If two settings conflict with each other a redexclamation mark is displayed.

Blocking the compressor in the outdoor unit.

Blocking additional heat.

TIP

If you wish to set similar scheduling for everyday of the week start by filling in “all” and thenchanging the desired days.

TIP

Set the stop time earlier than the start time sothat the period extends beyond midnight.Scheduling then stops at the set stop time theday after.

Scheduling always starts on the date that thestart time is set for.

Caution

Long term blocking can cause reduced comfortand operating economy.

41Chapter 8 | Control - MenusSMO 20

Page 44: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

Menu 4.9.6 - schedule silent modeThe compressor can be scheduled to be set to "quietmode" (the heat pump must support this) for up totwo different time periods here.

When scheduling is active the "quiet mode" symbol isshown in the main menu on the symbol for the controlmodule.

Schedule: The period to be changed is selected here.

Activated: Scheduling for the selected period is activ-ated here. Set times are not affected at deactivation.

Day: Select which day or days of the week the scheduleis to apply to here. To remove the scheduling for aparticular day, the time for that day must be reset bysetting the start time to the same as the stop time. Ifthe line "all" is used, all days in the period are set forthese times.

Time period: The start and stop time for the selectedday for scheduling are selected here.

Conflict: If two settings conflict with each other a redexclamation mark is displayed.

TIP

If you wish to set similar scheduling for everyday of the week start by filling in “all” and thenchanging the desired days.

TIP

Set the stop time earlier than the start time sothat the period extends beyond midnight.Scheduling then stops at the set stop time theday after.

Scheduling always starts on the date that thestart time is set for.

Caution

Long term scheduling of "quiet mode" cancause reduced comfort and operating eco-nomy.

SMO 20Chapter 8 | Control - Menus42

Page 45: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

Menu 5 - SERVICEOverview

5.1.1 - hot water settings *5.1 - operating settings5 - SERVICE

5.1.2 - max flow line temperat-ure

5.1.3 - max diff flow line temp.

5.1.4 - alarm actions

5.1.12 - addition

5.1.14 - flow set. climate sys-tem

5.1.22 - heat pump testing

5.1.23 - compressor curve

5.2.2 - installed heat pump

5.2.4 - accessories

5.4 - soft in/outputs

5.5 - factory setting service

5.6 - forced control

5.7 - start guide

5.8 - quick start

5.9 - floor drying function

5.10 - change log

5.11.1.1 - heat pump5.11.1 - EB1015.11 - slave settings

5.11.1.2 - charge pump

* Accessory needed.

Go to the main menu and hold the Back button in for7 seconds to access the Service menu.

Sub-menus

Menu SERVICE has orange text and is intended forthe advanced user. This menu has several sub-menus.Status information for the relevant menu can be foundon the display to the right of the menus.

operating settings Operating settings for the controlmodule.

system settings System settings for the control mod-ule, activating accessories etc.

soft in/outputs Setting software controlled inputs onthe terminal block (X2).

factory setting service Total reset of all settings (includ-ing settings available to the user ) to default values.

forced control Forced control of the different compon-ents in the indoor module.

start guide Manual start of the start guide which isrun the first time when the control module is started.

quick start Quick starting the compressor.

NOTE

Incorrect settings in the service menus candamage the installation.

Menu 5.1 - operating settingsOperating settings can be made for the control modulein the sub menus.

43Chapter 8 | Control - MenusSMO 20

Page 46: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

Menu 5.1.1 - hot water settings

economy

Setting range start temp. economy: 5 – 70 °C

Factory setting start temp. economy: 44 °C

Setting range stop temp. economy: 5 – 70 °C

Factory setting stop temp. economy: 47 °C

normal

Setting range start temp. normal: 5 – 70 °C

Factory setting start temp. normal: 47 °C

Setting range stop temp. normal: 5 – 70 °C

Factory setting stop temp. normal: 50 °C

luxury

Setting range start temp. lux: 5 – 70 °C

Factory setting start temp. lux: 52 °C

Setting range stop temp. lux: 5 – 70 °C

Factory setting stop temp. lux: 55 °C

stop temp. per. increase

Setting range: 55 – 70 °C

Default values: 55 °C

charge method

Setting range: target temp, delta temp

Default value: delta temp

Here you set the start and stop temperature of the hotwater for the different comfort options in menu 2.2 aswell as the stop temperature for periodic increase inmenu 2.9.1.

The charge method for hot water mode is selectedhere. "delta temp" is recommended for heaters withcharge coil, "target temp" for heaters with domesticcoil.

With "high power" activated, the hot water is chargedat a higher output than in the standard mode and thusgives a higher hot water capacity.

Menu 5.1.2 - max flow line temperature

climate system

Setting range: 5-70 °C

Default value: 60 °C

Set the maximum supply temperature for the climatesystem here.

Caution

Underfloor heating systems are normally maxflow line temperature set between 35 and 45°C.

Check the max floor temperature with yourfloor supplier.

Menu 5.1.3 - max diff flow line temp.

max diff compressor

Setting range: 1 – 25 °C

Default value: 10 °C

max diff addition

Setting range: 1 – 24 °C

Default value: 7 °C

Here you set the maximum permitted differencebetween the calculated and actual supply temperatureduring compressor respectively add. heat mode. Maxdiff. additional heat can never exceed max diff. com-pressor

max diff compressor

When the current supply temperature deviates fromthe set value compared to that calculated, the heatpump is forced to stop irrespective of the degree-minute value.

If the current supply temperature exceeds the calcu-lated flow with set value, the degree minute value isset to 0. The compressor in the heat pump stops whenthere is only a heating demand.

max diff addition

If "addition” is selected and activated in menu 4.2 andthe present supply temp exceeds the calculated withset value, the additional heat is forced to stop.

Menu 5.1.4 - alarm actionsSelect if you want the control module to alert you thatthere is an alarm in the display here.

Caution

If no alarm action is selected, it can result inhigher energy consumption in the event of analarm.

Menu 5.1.12 - addition

max step

Setting range (binary stepping deactivated): 0 – 3

Setting range (binary stepping activated): 0 – 7

Default value: 3

fuse size

Setting range: 1 - 200 A

Factory setting: 25 A

Here you select whether the step controlled additionalheat is positioned before or after the reversing valvefor hot water charging (QN10). Step controlled addi-tional heat is for example an external electric boiler.

You can set the maximum number of permitted addi-tional heat steps, if there is internal additional heat inthe tank (only accessible if the additional heat is posi-tioned after QN10), whether binary stepping is to beused and the size of the fuse.

SMO 20Chapter 8 | Control - Menus44

Page 47: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

TIP

See the accessory installation instructions forfunction description.

Menu 5.1.14 - flow set. climate system

presettings

Setting range: radiator, floor heat., rad. + floor heat.,DOT °C

Default value: radiator

Setting range DOT: -40,0 - 20,0 °C

Factory setting DOT: -18,0 °C

own setting

Setting range dT at DOT: 0,0-25,0

Factory setting dT at DOT: 10,0

Setting range DOT: -40,0 - 20,0 °C

Factory setting DOT: -18,0 °C

The type of heating distribution system the heatingmedium pump works towards is set here.

dT at DOT is the difference in degrees between flowand return temperatures at dimensioned outdoortemperature.

Menu 5.1.22 - heat pump testing

NOTE

This menu is intended for testing SMO 20 ac-cording to different standards.

Use of this menu for other reasons may resultin your installation not functioning as inten-ded.

This menu contains several sub-menus, one for eachstandard.

Menu 5.1.23 - compressor curveSet whether the compressor in the heat pump shouldwork to a particular curve under specific requirementsor if it should work to predefined curves.

You set a curve for a demand (heat, hot water etc.) byunticking "auto", turning the control knob until atemperature is marked and pressing OK. You can nowset at what temperatures the max. and min. frequen-cies, respectively will occur.

This menu can consist of several windows (one for eachavailable demand), use the navigation arrows in thetop left corner to change between the windows.

NOTE

This menu is only displayed if SMO 20 is con-nected to a heat pump with inverter controlledcompressor.

Menu 5.2 - system settingsMake different system settings for your installationhere, e.g. activate the connected heat pump and whichaccessories are installed.

Menu 5.2.2 - installed heat pumpIf a heat pump is connected to the master installation,set it here.

Menu 5.2.4 - accessoriesSet which accessories are installed on the installationhere.

If the water heater is connected to SMO 20 hot watercharging must be activated here.

Menu 5.4 - soft in/outputsHere you can select which in/output on the terminalblock (X2) the external contact function ((page 19)must be connected to.

Selectable inputs on terminal blocks AUX1-6 (X2:11-18 and output AA2-X4.

Menu 5.5 - factory setting serviceAll settings can be reset (including settings availableto the user) to default values here.

NOTE

When resetting, the start guide is displayedthe next time the control module is restarted.

Menu 5.6 - forced controlYou can force control the different components in thecontrol module and any connected accessories here.

Menu 5.7 - start guideWhen the control module is started for the first timethe start guide starts automatically. Start it manuallyhere.

See page 23 for more information about the startguide.

Menu 5.8 - quick startIt is possible to start the compressor from here.

Caution

There must be a heating or hot water demandto start the compressor.

Caution

Do not quick start the compressor too manytimes over a short period of time as this maydamage the compressor and its surroundingequipment.

45Chapter 8 | Control - MenusSMO 20

Page 48: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

Menu 5.9 - floor drying function

length of period 1 - 3, 5-7

Setting range: 0 - 30 days

Default value: 2 days

temp. period 1 - 3, 5-7

Setting range: 15 - 70 °C

Default value:20 °Ctemp. period 130 °Ctemp. period 240 °Ctemp. period 340 °Ctemp. period 530 °Ctemp. period 620 °Ctemp. period 7

length of period 4

Setting range: 0 - 30 days

Default value: 3 days

temp. period 4

Setting range: 15 - 70 °C

Default value: 45 °C

Set the function for under floor drying here.

You can set up to seven period times with differentcalculated flow temperatures. If less than seven periodsare to be used, set the remaining period times to 0days.

Mark the active window to activate the underfloordrying function. A counter at the bottom shows thenumber of days the function has been active.

NOTE

During floor drying the heating medium pumpin 100% runs regardless of the setting in menu5.1.10.

TIP

If operating mode "add. heat only" is to beused, select it in menu 4.2.

Menu 5.10 - change logRead off any previous changes to the control systemhere.

The date, time and ID no. (unique to certain settings)and the new set value is shown for every change.

NOTE

The change log is saved at restart and remainsunchanged after factory setting.

Menu 5.11 - heat pump settingsSettings for installed heat pump can be made in thesubmenus.

Menu 5.11.1 - EB101Make settings specifically for the installed heat pumpand charge pump here.

Menu 5.11.1.1 - heat pumpMake settings for the installed heat pump here. To seewhat settings you can make, see installation manualfor the heat pump.

Menu 5.11.1.2 - charge pump

operating mode

Setting range: auto / intermittent

Default value: auto

Set the operating mode for the charge pump here.

auto: The charge pump runs according to the currentoperating mode for SMO 20.

intermittent: The charge pump starts and stops 20seconds before and after the compressor in the heatpump.

speed during operation

heating, hot water, cooling

Setting range: auto / manual

Default value: auto

Manual setting

Setting range: 1–100 %

Default values: 70 %

max. allowed speed

Setting range: 80–100 %

Default values: 100 %

speed in wait mode

Setting range: 1–100 %

Default values: 30 %

Set the speed at which the charge pump is to operatein the present operating mode. Select "auto" if thespeed of the charge pump is to be regulated automat-ically (factory setting) for optimal operation.

If "auto" is activated for heating operation, you canalso make the setting "max. allowed speed" which re-stricts the charge pump and does not allow it to run ata higher speed than the set value.

For manual operation of the charge pump deactivate"auto" for the current operating mode and set the valueto between 1 and 100 % (the previously set value for"max. allowed speed" no longer applies).

waitmodemeans heating or cooling operating modesfor the charge pump, when the heat pump has neithera need for compressor operation nor electrical additionand slows down.

SMO 20Chapter 8 | Control - Menus46

Page 49: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

Service actionsNOTE

Servicing should only be carried out by personswith the necessary expertise.

When replacing components on SMO 20 onlyreplacement parts from NIBE may be used.

Emergency mode

NOTE

Switch (SF1) must not be put into mode "" orbefore the installation is filled with water.

The compressor in the heat pump can bedamaged.

Emergency mode is used in event of operational inter-ference and in conjunction with service. Hot water isnot produced in emergency mode.

Emergency mode is activated by setting switch (SF1)to ” ”. This means that:

The status lamp illuminates yellow.The display is not lit and the control computer is notconnected.Hot water is not produced.The compressor in the heat pump and charge pumpare switched off.The heating medium pump is active.The emergency mode relay (K1) is active.

External additional heating is active if it is connectedto the emergency mode relay (K1, terminal block X1).Ensure that the heating medium circulates through theexternal additional heating.

Temperature sensor data

Voltage (VDC)Resistance(kOhm)

Temperature(°C)

3.256351.0-403.240251.6-353.218182.5-303.189133.8-253.15099.22-203.10574.32-153.04756.20-102.97642.89-52.88933.0202.78925.6152.67320.02102.54115.77152.39912.51202.24510.00252.0838.045301.9166.514351.7525.306401.5874.348451.4263.583501.2782.968551.1362.467601.0072.068650.8911.739700.7851.469750.6911.246800.6071.061850.5330.908900.4690.779950.4140.672100

47Chapter 9 | ServiceSMO 20

9 Service

Page 50: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

USB service outlet

LE

K

SMO 20 is equipped with a USB socket in the displayunit. This USB socket can be used to connect a USBmemory to update the software, save logged informa-tion and handle the settings in SMO 20.

USB

INDOOR CLIMATE

MY SYSTEM

INFO

HOT WATER

When a USB memory is connected a new menu (menu7) appears in the display.

Menu 7.1 - update firmware

This allows you to update the software in SMO 20.

NOTE

For the following functions to work the USBmemory must contain files with software forSMO 20 from NIBE.

The fact box at the top of the display shows information(always in English) of the most probable update thatthe update software has selected form the USBmemory.

This information states which product the software isintended for, the software version and general inform-ation about them. If you wish to select another file thanthe one selected, the correct file can be selected by"choose another file".

start updating

Select “start updating" if you want to start the update.You are asked whether you really want to update thesoftware. Respond "yes" to continue or "no" to undo.

If you responded"yes" to the previous question theupdate starts and you can now follow the progress ofthe update on the display. When the update is com-plete SMO 20 restarts.

NOTE

A software update does not reset the menusettings in SMO 20.

NOTE

If the update is interrupted before it is com-plete (for example power cut etc.) the softwarecan be reset to the previous version if the OKbutton is held in during start up until the greenlamp starts to illuminate (takes about 10seconds).

SMO 20Chapter 9 | Service48

Page 51: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

choose another file

Select “choose another file" if you do not want to usethe suggested software. When you scroll through thefiles, information about the marked software is shownin a fact box just as before. When you have selected afile with the OK button you will return to the previouspage (menu 7.1) where you can choose to start theupdate.

Menu 7.2 - logging

Setting range: 1 s – 60 min

Default setting range: 5 s

Set whether the present measurement values fromSMO 20 are to be saved in a log on the USB memory.

Log for longer periods1. Set the desired interval between loggings.2. Tick “activated".3. The present values from SMO 20 are saved in a file

in the USB memory at the set interval until “activ-ated" is unticked.

Caution

Untick "activated" before removing the USBmemory.

Menu 7.3 - manage settings

Here you can manage (save as or retrieve from) all themenu settings (user and service menus) in SMO 20 witha USB memory.

Via "save settings" you save the menu settings to theUSB memory in order to restore them later or to copythe settings to another SMO 20.

NOTE

When you save the menu settings to the USBmemory you replace any previously saved set-tings on the USB memory.

Via "recover settings" you reset all menu settings fromthe USB memory.

NOTE

Reset of the menu settings from the USBmemory cannot be undone.

49Chapter 9 | ServiceSMO 20

Page 52: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

In most cases, the control module notes a malfunctionand indicates this with alarms and shows instructionsto rectify it in the display. See "Manage alarm" for in-formation about managing alarms. If the malfunctiondoes not appear in the display, or if the display is notlit, the following troubleshooting guide can be used.

Manage alarm

In the event of an alarm, some kind of malfunction hasoccurred, which is indicated by the status lamp chan-ging from green continuously to red continuously. Inaddition, an alarm bell appears in the informationwindow.

AlarmIn the event of an alarm with a red status lamp a mal-function has occurred that the heat pump and/orcontrol module cannot remedy itself. In the display, byturning the control knob and pressing the OK button,you can see the type of alarm it is and reset it. You canalso choose to set the installation to aid mode.

info / action Here you can read what the alarm meansand receive tips on what you can do to correct theproblem that caused the alarm.

reset alarm In most cases it is enough to select "resetalarm" to correct the problem that caused the alarm.If a green light illuminates after selecting "reset alarm"the alarm has been remedied. If a red light is still visibleand a menu called ”alarm” is visible in the display, theproblem that caused the alarm remains. If the alarmdisappears and then returns, see the troubleshootingsection (page 50).

aid mode ”aid mode” is a type of emergency mode.This means that the installation produces heat and/orhot water despite there being some kind of problem.This can mean that the heat pump's compressor is notrunning. In this case any electrical addition producesheat and/or hot water.

NOTE

To select aid mode an alarm action must beselected in menu 5.1.4.

Caution

Selecting "aid mode” is not the same as correct-ing the problem that caused the alarm. Thestatus lamp will therefore continue to be red.

TroubleshootingIf the operational interference is not shown in the dis-play the following tips can be used:

Basic actionsStart by checking the following possible fault sources:

The switch's (SF1) position.Group and main fuses of the accommodation.The property's earth circuit breaker.The control module's miniature circuit breaker (FA1).

Low hot water temperature or a lack of hotwaterThis part of the fault-tracing chapter only applies if thewater heater is installed in the system.

Closed or choked filling valve for the hot waterheater.

Open the valve.Mixing valve (if there is one installed) set too low.

Adjust the mixer valve.Control module in incorrect operating mode.

If mode "manual" is selected, select "addition".Large hot water consumption.

Wait until the hot water has heated up. Temporar-ily increased hot water capacity (temporary lux)can be activated in menu 2.1.

Too low hot water setting.Enter menu 2.2 and select a higher comfort mode.

Too low or no operating prioritisation of hot water.Enter menu 4.9.1 and increase the time for whenhot water is to be prioritised.

Low room temperatureClosed thermostats in several rooms.

Set the thermostats to max in as many rooms aspossible. Adjust the room temperature via menu1.1 instead of choking the thermostats.

Control module in incorrect operating mode.Enter menu 4.2. If mode "auto" is selected, selecta higher value on "stop heating“ in menu 4.9.2.If mode "manual" is selected, select "heating". Ifthis is not enough, select "addition".

Too low set value on the automatic heating control.Enter menu 1.1 "temperature" and adjust the offsetof the heating curve. If the room temperature isonly low in cold weather the curve slope in menu1.9.1 "heating curve" needs adjusting up.

Too low or no operating prioritisation of heat.Enter menu 4.9.1 and increase the time for whenheating is to be prioritised.

"Holiday mode" activated in menu 4.7.Enter menu 4.7 and select “Off”.

External switch for changing the room heating activ-ated.

Check any external switches.Air in the climate system.

SMO 20Chapter 10 | Disturbances in comfort50

10 Disturbances in comfort

Page 53: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

Vent the climate system.Closed valves (QM20), (QM32)to the climate system.

Open the valves.

High room temperatureToo high set value on the automatic heating control.

Enter menu 1.1 (temperature) and adjust the heatcurve offset downwards. If the room temperatureis only high in cold weather the curve slope in menu1.9.1 (heating curve) needs to be adjusted down.

External switch for changing the room heating activ-ated.

Check any external switches.

Low system pressureNot enough water in the climate system.

Top up the water in the climate system.

The compressor does not startThere is no heating requirement.

The heat pump does not call on heating nor hotwater.

Temperature conditions tripped.Wait until the temperature condition has been re-set.

Minimum time between compressor starts has notbeen reached.

Wait 30 minutes and check if the compressor hasstarted.

Alarm tripped.Follow the display instructions.

Additional heating onlyIf you are unsuccessful in rectifying the fault and areunable to heat the house, you can, whilst waiting forassistance, continue running the heat pump in ”add.heat only”. This means that additional heating only isused to heat the house.

Set the installation to additional heat mode1. Go to menu 4.2 operating mode.2. Mark ”add. heat only” using the control knob and

then press the OK button.3. Return to the main menus by pressing the Back

button.

Caution

When commissioning without NIBE air/waterheat pump an alarm communication error mayappear in the display.

The alarm is reset if the relevant heat pump isdeactivated in menu 5.2.2 ("installed slaves").

51Chapter 10 | Disturbances in comfortSMO 20

Page 54: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

Auxiliary relay HR 10Part no. 067 309

Charge pump CPD 11Charge pump for heat pump

CPD 11-25/65, Part no. 067 321

CPD 11-25/75, Part no. 067 320

Connection box K11Connection box with thermostat and overheatingprotection.

Part no. 018 893

External electrical addition ELK

ELK 5

Immersion heater

5 kW, 1 x 230 V

Part no. 069 025

ELK 8

Immersion heater

8 kW, 1 x 230 V

Part no. 069 026

ELK 15

Immersion heater

15 kW, 3 x 400 V

Part no. 069 022

ELK 26

Immersion heater

26 kW, 3 x 400 V

Part no. 067 074

Heat pump

F2030

7 kW Part no. 064 099

9 kW Part no. 064 070

F2040

8 kW Part no. 064 109

12 kW Part no. 064 092

16 kW Part no. 064 108

F2300

14 kW Part no. 064 063

20 kW Part no. 064 064

Hot water control

VST 05

Three way valve, Cu-pipe Ø22

Max heat pump size 8 kW

Part no. 089 882

VST 11

Shuttle valve, Cu-pipe Ø28(Max recommended power, 17 kW)

Part no. 089 152

VST 20

Reversing valve, Cu-pipe Ø35(Max recommended power, 40 kW)

Part no. 089 388

Immersion heater IU3 kW Part no. 018 084

6 kW Part no. 018 088

9 kW Part no. 018 090

Reversing valve for cooling

VCC 05

Part no. 067 311

VCC 11

Part no. 067 312

Room sensor RTS 40Part no. 067 065

Water heater/Accumulator tank

VPA 450/300

Water heater with double-jacketed vessel.

Copper Part no. 088 660

Enamel Part no. 088 670

VPB 200

Hot water heater with charge coil

Copper Part no. 088 515

Enamel Part no. 088 517

Stainless steel Part no 088 518

VPB 300

Hot water heater with charge coil

Copper Part no. 083 009

Enamel Part no. 083 011

Stainless steel Part no 083 010

VPB 500

Hot water heater with charge coil

Copper Part no. 083 220

SMO 20Chapter 11 | Accessories52

11 Accessories

Page 55: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

VPB 750-2

Hot water heater with charge coil

Copper Part no. 083 231

VPB 1000

Hot water heater with charge coil

Copper Part no. 083 240

VPAS 300/450

Water heater with double-jacketed vessel and solarcoil.

Copper Part no. 087 720

Enamel Part no. 087 710

53Chapter 11 | AccessoriesSMO 20

Page 56: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

Dimensions and setting-out coordinates

110

410

360

110

10310

21570

35

SMO 20Chapter 12 | Technical data54

12 Technical data

Page 57: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

Technical specifications

IP 21

SMO 20

Electrical data

230 V ~ 50 HzSupply voltage

IP21Enclosure class

4kVRated value for impulse voltage

2Electrical contamination

Optional connections

1Max number air/water heat pumps

8Max number of sensors

1Max number of charge pumps

3Max number of outputs for additional heat step

Miscellaneous

Type 1Operation mode (EN60730)

-25 – 70°CArea of operation

5 – 35°CAmbient temperature

1, 24Program cycles, hours

1, 2, 5, 7Program cycles, days

1min.Resolution, program

Dimensions and weight

360mmWidth

110mmDepth

410mmHeight

4.3kgWeight, (without packaging and enclosed components)

067 224Part No.

55Chapter 12 | Technical dataSMO 20

Page 58: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

Electrical circuit diagram

SMO 20Chapter 12 | Technical data56

Page 59: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

57Chapter 12 | Technical dataSMO 20

Page 60: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

SMO 20Chapter 12 | Technical data58

Page 61: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

59Chapter 12 | Technical dataSMO 20

Page 62: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

Item register

AAccessibility, electrical connection, 12Accessories, 52Alarm, 50

BBack button, 24

CCable lock, 13Commissioning and adjusting, 22

Commissioning with additional heating only, 22Commissioning with NIBE air/water heat pump, 22Cooling mode, 22Preparations, 22Start guide, 23

Commissioning with additional heating only, 22Commissioning with NIBE air/water heat pump, 22Communication with heat pump, 15Connecting accessories, 21Connecting the charge pump for the heat pump, 14Connections, 14Contact for activation of “external adjustment", 20Contact for activation of “temporary lux", 20Contact for external blocking of compressor in the heat pump, 19Contact for external tariff blocking, 19Contact information, 4Control, 24, 28

Control - Introduction, 24Control - Menus, 28

Control - Introduction, 24Display unit, 24Menu system, 25

Control knob, 24Control - Menus, 28

Menu 1 - INDOOR CLIMATE, 28Menu 2 - HOT WATER, 34Menu 3 - INFO, 36Menu 4 - MY SYSTEM, 37Menu 5 - SERVICE, 43

Cooling mode, 22Cooling mode indication, 20

DDelivery and handling, 5

Mounting, 5Supplied components, 5

Display, 24Display unit, 24

Back button, 24Control knob, 24Display, 24OK button, 24Status lamp, 24Switch, 24

Disturbances in comfort, 50Alarm, 50Manage alarm, 50Only additional heat, 51Troubleshooting, 50

Docking alternatives, 8

EElectrical connections, 11

Accessibility, electrical connection, 12Cable lock, 13Communication with heat pump, 15Connecting accessories, 21Connecting the charge pump for the heat pump, 14

Connections, 14External circulation pump, 18External connection options, 19General, 11Miniature circuit-breaker, 11NIBE Uplink™, 18Optional connections, 17Outdoor sensor, 15Power connection, 14Relay output for emergency mode, 18Reversing valve, 18Room sensor, 17Step controlled additional heat, 17Temperature sensor, external flow line, 16Temperature sensor, external supply line after electric heat-er, 16Temperature sensor, hot water charging, 15

External circulation pump, 18External connection options, 19

Contact for activation of “external adjustment", 20Contact for activation of “temporary lux", 20Contact for external blocking of compressor in the heatpump, 19Contact for external tariff blocking, 19Cooling mode indication, 20Extra circulation pump, 20Hot water circulation, 20Possible selection for AUX inputs, 19Possible selection for AUX output (potential free variable re-lay), 20Switch for "Smart Grid ready", 19Switch for activation of external alarm, 20Switch for external blocking of additional heat, 19Switch for external blocking of compressor, 20Switch for external blocking of heating, 20Temperature sensor, external flow line, 19Temperature sensor, flow line cooling, 19Temperature sensor, hot water top, 15

Extra circulation pump, 20

HHelp menu, 23, 27Hot water circulation, 20

IImportant information, 2

Safety information, 2Inspection of the installation, 3

MManage alarm, 50Marking, 2Menu 1 - INDOOR CLIMATE, 28Menu 2 - HOT WATER, 34Menu 3 - INFO, 36Menu 4 - MY SYSTEM, 37Menu 5 - SERVICE, 43Menu system, 25

Help menu, 23, 27Operation, 26Scroll through the windows, 27Selecting menu, 26Selecting options, 26Setting a value, 26Use the virtual keyboard, 27

Miniature circuit-breaker, 11Mounting, 5

SMO 20Chapter 13 | Item register60

13 Item register

Page 63: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

NNIBE Uplink™, 18

OOK button, 24Only additional heat, 51Operation, 26Optional connections, 17Outdoor sensor, 15

PPipe connections, 7

Docking alternatives, 8General, 7Symbol key, 7

Possible selection for AUX inputs, 19Possible selection for AUX output (potential free variable relay), 20Power connection, 14Preparations, 22

RRelay output for emergency mode, 18Reversing valve, 18Room sensor, 17

SSafety information, 2

Contact information, 4Inspection of the installation, 3Marking, 2Serial number, 2Symbols, 2

Scroll through the windows, 27Selecting menu, 26Selecting options, 26Serial number, 2Service, 47

Service actions, 47

Service actions, 47Standby mode, 47Temperature sensor data, 47USB service outlet, 48

Setting a value, 26Standby mode, 47Start guide, 23Status lamp, 24Step controlled additional heat, 17Supplied components, 5Switch, 24Switch for "Smart Grid ready", 19Switch for external blocking of additional heat, 19Switch for external blocking of compressor, 20Switch for external blocking of heating, 20Symbol key, 7Symbols, 2

TTechnical data, 54

Technical Data, 55Technical Data, 55Temperature sensor, external flow line, 16, 19Temperature sensor, external supply line after electric heater, 16Temperature sensor, flow line cooling, 19Temperature sensor, hot water charging, 15Temperature sensor, hot water top, 15Temperature sensor data, 47The Control Module Design, 6

Component locations, 6List of components, 6

Troubleshooting, 50

UUSB service outlet, 48Use the virtual keyboard, 27

61Chapter 13 | Item registerSMO 20

Page 64: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith
Page 65: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith
Page 66: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith
Page 67: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith
Page 68: Installer manual - nibe.hr · PDF filestandard IEC 81346-1 and 81346-2. 6 Chapter 3 | The Control Module Design SMO 20 3 The Control Module Design. General Pipeinstallationmustbecarriedoutinaccordancewith

231758

NIBE AB Sweden Hannabadsvägen 5Box 14 SE-285 21 [email protected]


Recommended