Heat & Glo • CFX-CRESCENT • 705-900 Rev. M • 12/05 1
Model:CFX-Crescent
Installers Guide
Underwriters Laboratories Listed
CFX-Crescent will be shownwith DF-Crescent door
attached in most illustrations.
In the Commonwealth of Massachusetts:• installation must be performed by a licensed
plumber or gas fitter;• a CO detector shall be installed in the room
where the appliance is installed.
- Do not store or use gasoline or other flam-mable vapors and liquids in the vicinity of thisor any other appliance.
- What to do if you smell gas• Do not try to light any appliance.• Do not touch any electrical switch.• Do not use any phone in your building.• Immediately call your gas supplier from a
neighbor's phone. Follow the gas supplier'sinstructions.
• If you cannot reach your gas supplier, callthe fire department.
- Installation and service must be performed by aqualified installer, service agency, or the gassupplier.
WARNING: IMPROPER INSTALLA-TION, ADJUSTMENT, ALTERATION,SERVICE OR MAINTENANCE CANCAUSE INJURY OR PROPERTY DAM-AGE. REFER TO THIS MANUAL. FORASSISTANCE OR ADDITIONAL INFOR-MATION CONSULT A QUALIFIED IN-STALLER, SERVICE AGENCY, OR THEGAS SUPPLIER.
READ THIS MANUAL BEFORE INSTALLING OROPERATING THIS APPLIANCE. THIS INSTALLERSGUIDE MUST BE LEFT WITH APPLIANCE FORFUTURE REFERENCE.
1. This appliance may be installed in an af-termarket, permanently located, manufac-tured (mobile) home, where not prohibitedby local codes.
2. This appliance is only for use with the typeof gas indicated on the rating plate. Thisappliance is not convertible for use withother gases, unless a certified kit is used.
Please contact your Heat & Glo dealer with anyquestions or concerns. For the number of your nearestHeat & Glo dealer, please call 1-888-427-3973.
Printed in U.S.A. Copyright 2005
Heat & Glo, a brand of Hearth & Home Technologies Inc.20802 Kensington Boulevard, Lakeville, MN 55044
WARNING: IF THE INFORMATIONIN THESE INSTRUCTIONS IS NOTFOLLOWED EXACTLY, A FIRE OREXPLOSION MAY RESULT CAUS-ING PROPERTY DAMAGE, PER-SONAL INJURY, OR DEATH.
This product may be covered by one or more of the following patents: (United States) 4593510, 4686807, 4766876, 4793322, 4811534, 5000162, 5016609, 5076254, 5113843, 5191877, 5218953, 5263471,5328356, 5341794, 5347983, 5429495, 5452708, 5542407, 5601073, 5613487, 5647340, 5688568, 5762062, 5775408, 5890485, 5931661, 5941237, 5947112, 5996575, 6006743, 6019099, 6048195,6053165, 6145502, 6170481, 6237588, 6296474, 6374822, 6413079, 6439226, 6484712, 6543698, 6550687, 6601579, 6672860, 6688302B2, 6715724B2, 6729551, 6736133, 6748940, 6748942, 6769426,6774802, 6796302, 6840261, 6848441, 6863064, 6866205, 6869278, 6875012, 6880275, 6908039, 6919884, D320652, D445174, D462436; (Canada) 1297749, 2195264, 2225408, 2313972; (Australia)780250, 780403, 1418504 or other U.S. and foreign patents pending.
Heat & Glo • CFX-CRESCENT • 705-900 Rev. M • 12/052
!
SAFETY AND WARNING INFORMATION
READ and UNDERSTAND all instructions carefully before starting the installation.FAILURE TO FOLLOW these installation instructions may result in a possible firehazard and will void the warranty.
Prior to the first firing of the fireplace, READ the Using Your Fireplace section of theOwners Guide.
DO NOT USE this appliance if any part has been under water. Immediately CALL aqualified service technician to inspect the unit and to replace any part of the controlsystem and any gas control which has been under water.
THIS UNIT IS NOT FOR USE WITH SOLID FUEL.
Installation and repair should be PERFORMED by a qualified service person. Theappliance and venting system should be INSPECTED before initial use and at leastannually by a professional service person. More frequent cleaning may be requireddue to excessive lint from carpeting, bedding material, etc. It is IMPERATIVE that theunit’s control compartment, burners, and circulating air passageways BE KEPTCLEAN to provide for adequate combustion and ventilation air.
Always KEEP the appliance clear and free from combustible materials, gasoline, andother flammable vapors and liquids.
NEVER OBSTRUCT the flow of combustion and ventilation air. Keep the front of theappliance CLEAR of all obstacles and materials for servicing and proper operations.
Due to the high temperature, the appliance should be LOCATED out of traffic areasand away from furniture and draperies. Clothing or flammable material SHOULD NOTBE PLACED on or near the appliance.
Children and adults should be ALERTED to the hazards of high surface temperatureand should STAY AWAY to avoid burns or clothing ignition. Young children should beCAREFULLY SUPERVISED when they are in the same room as the appliance.
These units MUST use one of the vent systems described in the Installing the Fireplacesection of the Installers Guide. NO OTHER vent systems or components MAY BE USED.
This gas fireplace and vent assembly MUST be vented directly to the outside andMUST NEVER be attached to a chimney serving a separate solid fuel burningappliance. Each gas appliance MUST USE a separate vent system. Common ventsystems are PROHIBITED.
INSPECT the external vent cap on a regular basis to make sure that no debris isinterfering with the air flow.
The glass door assembly MUST be in place and sealed, and the trim door assemblyMUST be in place on the fireplace before the unit can be placed into safe operation.
DO NOT OPERATE this appliance with the glass door removed, cracked, or broken.Replacement of the glass door should be performed by a licensed or qualified serviceperson. DO NOT strike or slam the glass door.
The glass door assembly SHALL ONLY be replaced as a complete unit, as suppliedby the gas fireplace manufacturer. NO SUBSTITUTE material may be used.
DO NOT USE abrasive cleaners on the glass door assembly. DO NOT ATTEMPT toclean the glass door when it is hot.
Turn off the gas before servicing this appliance. It is recommended that a qualifiedservice technician perform an appliance check-up at the beginning of each heatingseason.
Any safety screen or guard removed for servicing must be replaced before operatingthis appliance.
DO NOT place furniture or any other combustible household objects within 36 inches ofthe fireplace front.
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
Heat & Glo • CFX-CRESCENT • 705-900 Rev. M • 12/05 3
Table ofContents
Safety and Warning Information .............................. 2
Service Parts List ..................................................... 4
Section 1: Approvals and Codes ........................... 6Appliance Certification ........................................... 6Installation Codes .................................................. 6High Altitude Installations ....................................... 6
Section 2: Getting Started ...................................... 7Introducing the Heat & Glo Gas Fireplaces ............. 7Pre-installation Preparation ................................... 7
Section 3: Installing the Fireplace ........................ 9Step 1 Locating the Fireplace .............................. 9Step 2 Framing the Fireplace ............................ 10Step 3 Installing the Vent System ...................... 11
A. Vent System Approvals ...................... 11B. Installing Vent Components ................ 15C. Vent Termination ................................ 20
Step 4 Positioning, Leveling, andSecuring the Fireplace ........................... 25
Step 5 The Gas Control Systems ..................... 25Step 6 The Gas Supply Line.............................. 26Step 7 Gas Pressure Requirements ................. 27Step 8 Wiring the Fireplace ............................... 28Step 9 Finishing ................................................ 30Step 10 Removing Glass Door, Installing Trim,
Logs and Ember Material ..................... 31Removing Glass Door ........................... 31Installing Door Handles .......................... 31Positioning the Logs............................... 32Shutter Settings ..................................... 32Placing the Ember Materialand Lava Rocks ..................................... 32
Step 11 Before Lighting the Fireplace .................. 33Step 12 Lighting the Fireplace ............................. 33After the Installation ............................................. 33
Section 4: Maintaining and Servicing Your Fireplace ..................................... 34
= Contains updated information.
Heat & Glo • CFX-CRESCENT • 705-900 Rev. M • 12/054
10 Log Set Assembly
Part number list on following page.
20
5
21
2
8
18
7
1
4
3
6
19
17
15
16
14
13
11
12
9
(NG, LP) Exploded Parts Diagram
Service Parts CFX-CrescentBeginning Manufacturing Date: 6/00Ending Manufacturing Date: ______
22
23
24
25
26
27
28
Heat & Glo • CFX-CRESCENT • 705-900 Rev. M • 12/05 5
Service Parts List (NG, LP)
ITEM COMMON PARTS SERIAL # PART NUMBER
1 Burner Orifice NG (#35A) 065-8001 Burner Orifice LP (#51A) 079-8032 Log Grate 705-360A3 Pilot Assembly NG 385-510A3 Pilot Assembly LP 385-511A4 Glass Door Assembly GLA-CRESCENT5 Combustion Blower 705-567A6 Limit Switch 514-5307 Glass Clip Assembly - Top (qty. 2) SRV705-206A8 Glass Attachment Assembly - Bottom (qty. 2) 386-122A9 Finishing Strips (qty. 2) 705-23310 Log Set Assembly LOGS-CRESCENT11 Log 1 SRV705-70112 Log 2 SRV705-70313 Log 3 SRV705-70214 Log 4 SRV705-70415 Log 5 SRV705-70516 Log 6 SRV593-70417 Burner Tube 570-302A22 Insulation Board 705-40323 Flex Ball Valve Assembly 492-320A24 Insulation Support 705-260
Patch Kit SRV-PATCH-CFXMineral Wool Embers 050-721Lava Rock Bag 705-420DSI IGNITION ONLY Pre 002182991
18 Burner NG 705-326A18 Burner LP 705-325A19 Junction Box 100-256A20 Valve NG & LP 476-50021 Module 501-592
Ignitor 501-591Conversion Kit NG NGK-CRESCENTConversion Kit LP LPK-CRESCENTIPI IGNITION ONLY Post 002182992
18 Burner NG 705-328A18 Burner LP 705-327A19 Junction Box 705-250A20 Valve NG 593-50020 Valve LP 593-50121 Module 593-59225 Wire Assembly 593-590A26 Fresh Air Diffuser 705-26427 Pilot Plate 705-26228 Valve Bracket 705-205
Pilot Gasket 705-4063V Adaptor Plug 593-593AConversion Kit LP LPK-CRESCENT-IPIACCESSORIESBun Warmer Door, Black - Optional BW-CRESCENT-BKBun Warmer Door, Brushed Nickel - Optional BW-CRESCENT-BNRemote Control Kit RC-SMART-HNGRemote Control Kit SMART-STAT-HNGWall Switch Kit, Off-white WSK-21Wall Switch Kit, White WSK-21-WDecorative Arch 3" x 1" - Black ARCH-BKDecorative Arch 3" x 1" - Brushed Nickel ARCH-BNOutside Air (4" Flex not included) AK-CFXTrim Door, Brushed Nickel - Optional DF-CRESCENT-BNTrim Door, Black - Optional DF-CRESCENT-BK
IMPORTANT: THIS IS DATED INFORMATION. The most current information is located on your dealers VIP site. When ordering,supply serial and model numbers to ensure correct service parts.
CFX-Crescent
Heat & Glo • CFX-CRESCENT • 705-900 Rev. M • 12/056
1Approvalsand Codes
Approval Listingsand Codes
Appliance CertificationThe Heat & Glo fireplace models discussed in thisInstallers Guide have been tested to certificationstandards and listed by the applicable laboratories.
CERTIFICATION MODEL LABORATORY TYPE STANDARD CFX-Crescent Underwriters Direct Vent ANSI Z21.50-2000•CSA2.22-M98
Laboratories Gas Fireplace
Installation Codes
The fireplace installation must conform to local codes. Before installing thefireplace, consult the local building code agency to ensure that you are incompliance with all applicable codes, including permits and inspections.
In the absence of local codes, the fireplace installation must conform to theNational Fuel Gas Code ANSI Z223.1 (in the United States) or the CAN/CGA-B149 Installation Codes (in Canada). The appliance must be electricallygrounded in accordance with local codes or, in the absence of local codes withthe National Electric Code ANSI/NFPA No. 70 (in the United States), or to theCSA C22.1 Canadian Electric Code (in Canada).
This model may be installed in a bedroom or bed-sitting room in the U.S.A. andCanada.
High Altitude InstallationsU.L. Listed gas appliances are tested and approved without requiring changes forelevations from 0 to 2,000 feet in the U. S. A. and in Canada.
When installing this appliance at an elevation above 2,000 feet, it may be necessaryto decrease the input rating by changing the existing burner orifice to a smallersize. Input rate should be reduced by 4% for each 1000 feet above a 2000 footelevation in the U.S.A. or 10% for elevations between 2000 and 4500 feet in Canada.If the heating value of the gas has been reduced, these rules do not apply. Toidentify the proper orifice size, check with the local gas utility.
If installing this appliance at an elevation above 4,500 feet (in Canada), check withlocal authorities.
Heat & Glo Quality Systemsregistered by SGS ICS
Heat & Glo • CFX-CRESCENT • 705-900 Rev. M • 12/05 7
2GettingStarted
Introducing theHeat & GloGas Fireplaces
Heat & Glo direct vent gas fireplaces are designed tooperate with all combustion air siphoned fromoutside of the building and all exhaust gasesexpelled to the outside.The information contained in this Installers Guide,unless noted otherwise, applies to all models andgas control systems.Gas fireplace diagrams, including the dimensions,are shown in this section.
Pre-installationPreparation
This gas fireplace and its components are testedand safe when installed in accordance with thisInstallers Guide. Report to your dealer any partsdamaged in shipment, particularly the condition ofthe glass. Do not install any unit with damaged,incomplete, or substitute parts.The vent system components and trim doors areshipped in separate packages. The gas logs arepackaged separately and must be field installed.Read all of the instructions before starting theinstallation. Follow these instructions carefullyduring the installation to ensure maximumsafety and benefit. Failure to follow theseinstructions will void the owner’s warranty andmay present a fire hazard.
This model MUST use SL-Series Direct VentComponents and Termination Kits (as indicated in thisguide) for exhausting flue gases AND model AK-CFXAir Kit for combustion air. NOTE: 4-inch insulatedducting is required. See venting section for details.
The Heat & Glo Warranty will be voided by, and Heat& Glo disclaims any responsibility for, the followingactions:• Installation of any damaged fireplace or vent
system component.• Modification of the fireplace or direct vent system.• Installation other than as instructed by Heat & Glo.• Improper positioning of the gas logs or the glass
door.• Installation and/or use of any component part not
manufactured and approved by Heat & Glo, notwithstanding any independent testing laboratory orother party approval of such component part oraccessory.
ANY SUCH ACTION MAY POSSIBLY CAUSE AFIRE HAZARD.
Heat & Glo • CFX-CRESCENT • 705-900 Rev. M • 12/058
When planning a fireplace installation, it’s necessary to determine:• Where the unit is to be installed.• The vent system configuration to be used.• Gas supply piping.• Electrical wiring.• Framing and finishing details. Refer to Finishing Variations addendum included
in manual bag.• Whether optional accessories, such as a remote control, arch surround or door
front are desired.If the fireplace is to be installed on carpeting or tile, or on any combustiblematerial other than wood flooring, the fireplace should be installed on a metal orwood panel that extends the full width and depth of the fireplace.
Figure 1. Diagram of the CFX-CRESCENT
12 3/4 (323mm)
19 1/8 (487mm)
3 (76mm) Ø Ø6 5/8 (168mm)
9 1/2 (241mm)
12 5/8 (319mm)
25 3/8 (645mm)
2 3/8 (62mm)
5 1/2 (138mm)
9 3/4 (248mm)
2 3/4 (68mm)
ELECTRICALACCESS 43 1/8 (2)
(1096mm)
12 7/8 (326mm)8 1/2 (216mm)
38 1/4(972mm)
2 3/8 (61mm)
1 1/8 (29mm)
GAS LINEACCESS
34 1/2 (876mm)
6 (153mm)
9 (231mm)
38 1/2(978mm)
46 3/4(1187mm)
TOP VENTCOLLARS
CONTROLVALVE
ELECTRICALACCESS
AK-CFXSTARTINGCOLLAR
Heat & Glo • CFX-CRESCENT • 705-900 Rev. M • 12/05 9
3Installing theFireplace
Step 1Locating thefireplace
Figure 2. Fireplace Dimensions, Locations, and Space Requirements
Clearance RequirementsThe top, back, and sides of the fireplace are definedby stand-offs.
Minimum Clearances from the Fireplace toCombustible Materials
Glass Rear Sides of Top ofFront Floor of Fireplace Fireplace Fireplace* Ceiling*
36 inches 0 1/2 inch 1/2 inch 14 1/2 inches** 24 inches(914mm) (13mm) (13mm) (368mm) (610mm)
The diagram below shows space and clearancerequirements for locating a fireplace within a room.
A B C D E66 5/8 33 1/4 47 1/8 19 5/8 35 1/2
NOTE: Dimensions shown in inches.
C
BA
E
D I INCH
* NOTE: Add 1 3/8” to these measurements if measuring from the top of the door.** NOTE: 2 x 4 framing only allowed at 43 5/8” (see Figures 3 and 26).
The minimum clearance to a perpendicular wall extend-ing past the face of the fireplace is one inch (25mm).The back of the fireplace may be recessed 19 1/4inches (489mm) into combustible construction.
The distance from the unit to combustible constructionis to be measured from the unit outer wrap surface tothe combustible construction, NOT from the screwheads that secure the unit together.
Heat & Glo • CFX-CRESCENT • 705-900 Rev. M • 12/0510
Framing should beconstructed of 2 X 4lumber or heavier.
A B C D 35 1/2” 43 5/8” 19 5/8” 47 3/4”(902mm) (1108mm) (498mm) (1213mm)
Shows center of10” x 10” ventframing holesfor top venting.
Figure 3. Framing Dimensions
Minimum Clearances from the Vent Pipe toCombustible Materials
For VerticalFor Horizontal Sections Sections At Wall Firestops
Top Bottom Sides Top Bottom Sides
3 inches 1 inch 1 inch 1 inch 2-1/2 inches 1/2 inch 1 inch(75 mm) (25 mm) (25 mm) (25 mm) (63.7 mm) (13 mm) (25 mm)
For minimum clearances, see the direct venttermination clearance diagrams on pages 21 and22 in this section.
Step 2Framing theFireplace
Fireplace framing can be built before or after thefireplace is set in place. Framing should bepositioned to accommodate wall coverings andfireplace facing material. The diagram below showsframing reference dimensions.
CAUTION MEASURE FIREPLACE DIMENSIONS ANDVERIFY FRAMING METHODS AND WALLCOVERING DETAILS BEFORE FRAMINGCONSTRUCTION BEGINS.
46 3/4 (REF)
DA
B
C
Heat & Glo • CFX-CRESCENT • 705-900 Rev. M • 12/05 11
Figure 4. Vent Components and Terminations
Vent SystemTermination Kits
Vent System Components
A. Vent System ApprovalsThis model is approved to use SL-series direct vent pipe com-ponents and terminations (as indicated in this guide), and mod-el AK-CFX air kits. Approved vent system components are la-beled for identification. This pipe is tested and listed as an ap-proved component of the fireplace. The pipe is tested to be runinside an enclosed wall. There is NO requirement for inspectionopenings at each joint within the wall. There is no required pitchfor horizontal vent runs. This model is not approved for usewith SLK-01D termination cap. NO OTHER VENTING SYS-TEMS OR COMPONENTS MAY BE USED.Detailed installation instructions are included with each vent termina-tion kit and should be used in conjunction with this Installers Guide.Drawing below shows vent system components and terminations.
Step 3Installing theVent System
!
SLK-991DA SLK-01TRD
HORIZONTALTERMINATION
WALL FIRESTOP
90 DEGREEELBOW
VERTICALTERMINATION STORM COLLAR
ROOF FLASHING
HORIZONTAL PIPESUPPORT
PIPE LENGTH
WALL BRACKET
CEILINGFIRESTOP
COMBUSTION AIR DUCT COLLAR
NOTE: SLK-01D is NOTapproved for use.
NOTE: When installing the AK-CFX outside air kit, it is normally not necessaryto install the air intake cap on the same wall as the exhaust termination cap.However, installations involving tall buildings or areas subjected to frequent highwinds, it is recommended that the air intake cap be installed on the same wallas the exhaust termination cap.
Identifying Vent ComponentsThe vent systems installed on this gas fireplace may include up to eight 90° elbowassemblies. The relationships of vertical rise to horizontal run in vent configurationsusing 90° elbows MUST BE strictly adhered to. The rise to run relationships are shownin the venting drawings and tables. Refer to the diagrams on the next several pages.
NOTE: TWO 45° ELBOWS MAY BE USED IN PLACE OF ONE 90° ELBOW.RISE TO RUN RATIOS IN THE VENT SYSTEM MUST BE FOLLOWED IF 45°ELBOWS ARE USED.
WARNING: THIS UNIT IS DESIGNED TO OPERATE USING OUTSIDE COM-BUSTION AIR. IT IS MANDATORY TO INSTALL AN AK-CFX AIR KIT USING4-INCH INSULATED DUCTING. THE 4-INCH (102MM) DUCT COLLAR FORTHE AIR KIT WILL COME MOUNTED TO THE FIREPLACE. SEE FIGURE 6.
Heat & Glo • CFX-CRESCENT • 705-900 Rev. M • 12/0512
Figure 5. SL-Series Direct Vent Component Specifications
(4-inch inner pipe/6 5/8-inch outer pipe)
Note: Pipes overlap 1 3/8 inches (34.93mm) at each joint.
9 1/4
6 5/8
6 1/2 6 3/8
6 1/2 9 5/8
9 5/8
6 5/8
6 3/8
8 3/4
SL-09D
12-17
SL-12/17D (SL12-17D) SL-24D SL-36D SL-48D
47 3/4
35 3/4
23 3/4
SL-45D
SL-90D
SL-17/24D(SL17-24D)
17-24
SL-06DSL-12D
5 3/4
6 5/8
6 1/211 3/4
Heat & Glo • CFX-CRESCENT • 705-900 Rev. M • 12/05 13
Figure 7. Straight Up Vertical Venting
STRAIGHT UPVERTICAL VENTING
V (FT.)
46' MAX. (14M)
The combustion air duct on the right side of the unit can runhorizontally or elbow upward 46 feet long. This duct canelbow down to a maximum of 18 feet.
Figure 6. Unit with duct collar.
COMBUSTIONDUCT COLLAR
FORAK-CFX AIR KIT
CAP
V
Heat & Glo • CFX-CRESCENT • 705-900 Rev. M • 12/0514
Figure 8. Venting with eight (8) 90° ElbowsUnit could have up to eight elbows off the top, with a maximum of 50 feet hori-zontal before any vertical, however, a vertical run of 46 feet maximum could beintroduced at any point of the horizontal run and even right off the top of the unit.
Total H (Horizontal run) = 50 feet maximum.Total V (Vertical run) = 46 feet maximum.
Any combination in between would be applicable.
COMBUSTIONAIR DUCT
COMBUSTIONAIR DUCT
40 FTMAXIMUM
18 FTMAXIMUM
40 FTMAXIMUM
Heat & Glo • CFX-CRESCENT • 705-900 Rev. M • 12/05 15
B. Installing Vent Components1. Attach the First Vent Component to the
Starting CollarsTo attach the first vent component to the startingcollars of the fireplace:• Apply a 3/8 inch (9.5 mm) bead of stove cement
around the 4 inch (102 mm) fireplace starting collar.• Slide the first vent section onto the collars attached
to the top of the unit. Use four self tapping screws tosecure the outer pipe to the outer collar.
• Apply a 3/8 inch (9.5mm) bead of stove cementaround the 6 5/6 inch (168mm) outer collar.
1. Apply the stovecement.
2. Line up the internalbeads and slide pipeon. Note: Outer pipeslides into outer (coneshaped) collar 1/2 inch.
3. Fasten with fourscrews.
4. Apply the stovecement to outer collarjoint.
STARTINGCOLLAR
STOVESEALANT
BEAD
1 INCH(25.4mm)
FIRST VENTCOMPONENT
3/8” (9.5mm)
!
Figure 9. Attaching the First Vent Component tothe Starting Collars
WARNING: A 3/8 INCH (9.5 MM) BEADOF STOVE CEMENT MUST BEPLACED AROUND THE 4 INCH (102MM) FIREPLACE STARTING COLLARBEFORE ATTACHING THE FIRST VENTCOMPONENT. FAILURE TO SEAL THISJOINT MAY CAUSE THE FIREPLACETO OPERATE IMPROPERLY. SEE THEDIAGRAM .
Heat & Glo • CFX-CRESCENT • 705-900 Rev. M • 12/0516
2. Continue Adding Vent ComponentsTo continue adding vent components in accordancewith the pre-planned vent system configuration:• Ensure that each succeeding vent component is
securely fitted and locked into the preceding com-ponent in the vent system.
90° elbows may be installed and rotated to any pointaround the preceding component’s vertical axis. If anelbow does not end up in a locked position with thepreceding component, attach with a minimum of two(2) sheet metal screws.
Continue adding ventcomponents, lockingeach succeedingcomponent into place.
Figure 10. Adding Venting Components3. Install Support BracketsFor Horizontal Runs - The vent system must besupported every five (5) feet of horizontal run by ahorizontal pipe support.To install support brackets for horizontal runs:• Place the pipe supports around the vent pipe.• Nail the pipe supports to the framing members.
Heat & Glo • CFX-CRESCENT • 705-900 Rev. M • 12/05 17
For Vertical Runs - The vent system must besupported every eight (8) feet (2.4 m) above thefireplace flue outlet by wall brackets.
To install support brackets for vertical runs:
• Attach wall brackets to the vent pipe and securethe wall bracket to the framing members withnails or screws.
Use wall brackets tosupport vertical runsevery 8 feet (2.4 m)above the fireplace flueoutlet.
Figure 11. Installing Support Brackets
4. Install Firestops
For Horizontal Runs - Firestops are REQUIREDon both sides of a combustible wall through whichthe vent passes. The exterior firestop is not requiredat the termination cap for model CFX-Crescent. (SLK-01TRD is required for horizontal terminations).
To install firestops for horizontal runs that passthrough either interior or exterior walls:
• Cut a 10-inch by 10-inch (254 mm X 254 mm)hole through the wall. The center of the hole isone (1) inch (25.4 mm) above the center of thehorizontal vent pipe.
WALL BRACKET
WALL STUD
8 FT.(2.3m)FLUE
OUTLET
1 INCH MIN.(25.4m)
Heat & Glo • CFX-CRESCENT • 705-900 Rev. M • 12/0518
Figure 12. 10" x 10" Hole and Vent Pipe
2. Position the firestops.
3. Place the heat shieldto the top.
4. Continue the vent run.
Figure 13. Heat Shield, Interior and ExteriorFirestops
For Vertical Runs - One ceiling firestop isREQUIRED at the hole in each ceiling throughwhich the vent passes.To install firestops for vertical runs that pass throughceilings:• Position a plumb bob directly over the center of
the vertical vent component.• Mark the ceiling to establish the centerpoint of the
vent.
• Position the firestops on both sides of the holepreviously cut and secure the firestops with nailsor screws.
• The heat shields of the firestops MUST BEplaced towards the top of the hole.
• Continue the vent run through the firestops.
NOTE: There must be NO insulation or othercombustibles inside the framed firestop opening.
1. Cut the 10-inch by10-inch hole.
VENT PIPE
1" (25.4 mm)
10"(254mm)
10"(254mm)
TRIM HEATSHIELD IF TOOLONG, ADD TO SHIELD IF TOOSHORT
INTERIORFIRESTOP
HEAT SHIELD
NOTE:Exterior firestop not shown.Horizontal termination onlyapproved for SLK-01TRDtrapezoidal cap.
Heat & Glo • CFX-CRESCENT • 705-900 Rev. M • 12/05 19
Figure 14 . 9”x 9” Hole & New Framing Members
If the area above the ceiling is NOT an attic, posi-tion and secure the ceiling firestop on the ceilingside of the previously cut and framed hole.
This shows a ceilinginstallation.
Figure 15. Ceiling Firestop (Ceiling Side)
• Drill a hole or drive a nail through this centerpoint.
• Check the floor above for any obstructions, suchas wiring or plumbing runs.
• Reposition the fireplace and vent system, ifnecessary, to accommodate the ceiling joistsand/or obstructions.
• Cut a 9-inch x 9-inch (229mm x 229mm) holethrough the ceiling, using the centerpoint previ-ously marked.
• Frame the hole with framing lumber the samesize as the ceiling joists.
1. Cut the 9-inch by9-inch hole.
2. Add the new framingmembers.
JOIST
CEILING FIRESTOP
CEILING
NAILS (4 REQUIRED)
CEILING
NEWFRAMINGMEMBERS
EXISTING CEILING JOISTS
CHIMNEYHOLE
9" (229 mm) 9" (229 mm)
Heat & Glo • CFX-CRESCENT • 705-900 Rev. M • 12/0520
If the area above the ceiling IS an attic, position andsecure the firestop on top of the previously framed hole.
NOTE: There must be NO insulation or othercombustibles inside the framed firestop opening.
This shows an atticinstallation.
1. Keep insulation awayfrom the vent pipe atleast 1 inch (25 mm).
Figure 16. Attic Firestop
C. Vent Termination
For Horizontal Terminations - The trapezoidal capSLK-01TRD is the only cap that is approved toterminate a horizontal vent run.
To attach and secure the termination to the lastsection of horizontal vent:
• Rotate and interlock the ends as described at thebeginning of the Installing Vent Componentssection.
• The termination kit should pass through the wallfirestops from the exterior of the building.
• Adjust the termination cap to its final exteriorposition on the building (see Figure 17).
CEILING
CEILING FIRESTOP
RAFTER
NAILS (4 REQUIRED)
Heat & Glo • CFX-CRESCENT • 705-900 Rev. M • 12/05 21
Figure 17. Trapezoid Termination Cap
For trapezoidal termination:
1. Screw the cap to theexterior wall throughthe flanges in the cap.
2. Seal the joint betweenthe pipe and theexterior firestop.
!
6 3/4”(171mm)
WARNING: VENTING TERMINALS SHALLNOT BE RECESSED INTO A WALL OR SID-ING. VENT TERMINATION CLEARANCES
MUST BE FOLLOWED TO AVOID FIRE DANGER.SEE VENT TERMINATION MINIMUM CLEARANC-ES DIAGRAM ON FOLLOWING PAGE.
Heat & Glo • CFX-CRESCENT • 705-900 Rev. M • 12/0522
V = VENT TERMINAL X = AIR SUPPLY INLET = AREA WHERE TERMINAL IS NOT PERMITTED
Figure 18. Vent Termination Minimum Clearances
A = 12" ....................... clearances above grade, veran-da, porch, deck or balcony
B = 12" ....................... clearances to window or doorthat may be opened, or to per-manently closed window.
D* = 18" ....................... vertical clearance to unventilat-ed soffit or to ventilated soffit lo-cated above the terminal
*48” min. .............. for vinyl clad soffits and belowelectrical service
F = 9" ........................ clearance to outside cornerG = 6" ......................... clearance to inside cornerH = 3 ft. (Canada) ...... not to be installed above a gas
meter/regulator assembly within3 feet (90cm) horizontally from thecenter-line of the regulator
I = 3 ft. (U.S.A.)6 ft. (Canada) ...... clearance to gas service regu-
lator vent outletJ = 9" (U.S.A.)
12" (Canada) ........ clearance to non-mechanical airsupply inlet to building or thecombustion air inlet to any otherappliance
K = 3 ft. (U.S.A.)6 ft. (Canada) ......... clearance to a mechanical air
supply inletL** = 7 ft. ......................... clearance above paved side-
walk or a paved driveway locat-ed on public property
M*** = 18" ......................... clearance under veranda,porch, deck, balcony or over-hang
42” ......................... vinylN = 6” ........................... non-vinyl sidewalls
12” ......................... vinyl sidewallsP = 8 ft.
CAUTION: IF EXTERIOR WALLS ARE FINISHED WITH VINYL SIDING, IT IS SUGGESTED THAT A VINYL PROTECTOR KIT BEINSTALLED.
** a vent shall not terminate directly above a sidewalk or paveddriveway which is located between two single family dwellingsand serves both dwellings.
*** only permitted if veranda, porch, deck or balcony is fully open ona minimum of 2 sides beneath the floor or meets Note 2.
NOTE 1: On private property where termination is less than 7 feetabove a sidewalk, driveway, deck, porch, veranda or balcony, use ofa listed cap shield is suggested.
NOTE 2: Termination in an alcove space (spaces open only on one sideand with an overhang) are permitted with the dimensions specified forvinyl or non-vinyl siding and soffits. 1. There must be 3 feet minimumbetween termination caps. 2. All mechanical air intakes within 10 feetof a termination cap must be a minimum of 3 feet below the terminationcap. 3. All gravity air intakes within 3 feet of a termination cap must bea minimum of 1 foot below the termination cap.
MN
PR
Q
(See Note 1)
(See Note 1)
(See Note 2)
S = 6" MIN. .................. clearance from sides of elec-trical service
T = 12" MIN. ................ clearance above electricalservice
______________________________________________________________________
______________________________________________________________________
______________________________________________________________________
______________________________________________________________________
QMIN RMAX
1 cap 3 feet 2 x Q ACTUAL
2 caps 6 feet 1 x Q ACTUAL
3 caps 9 feet 2/3 x Q ACTUAL
4 caps 12 feet 1/2 x Q ACTUAL
QMIN = # termination caps x 3 RMAX = (2 / # termination caps) x QACTUAL
(See Note 5)
(See Note 5)
ElectricalService
V
SV S
V
T
D*
V
NOTE 3: Local codes or regulations may require differentclearances.
NOTE 4: Termination caps may be hot. Consider their proximity todoors or other traffic areas.
NOTE 5: Location of the vent termination must not interfere withaccess to the electrical service.
WARNING: In the U.S: Vent system termination is NOT permittedin screened porches. You must follow side wall, overhang andground clearances as stated in the instructions.
In Canada: Vent system termination is NOT permitted in screenedporches. Vent system termination is permitted in porch areaswith two or more sides open. You must follow all side walls,overhang and ground clearances as stated in the instructions.
Heat & Glo assumes no responsibility for the improper perfor-mance of the fireplace when the venting system does not meetthese requirements.
DE
BL
v
v v
v
v
v
v
v
BB
A H
MX
J or K
I
A
G
F
U.S.(3 FT)B
Heat & Glo • CFX-CRESCENT • 705-900 Rev. M • 12/05 23
For Vertical Terminations - To locate the vent andinstall the vent sections:
• Locate and mark the vent centerpoint on theunderside of the roof, and drive a nail through thecenterpoint.
• Make the outline of the roof hole around thecenterpoint nail.
• The size of the roof hole framing dimensionsdepend on the pitch of the roof. There MUST BEa 1-inch (25.4 mm) clearance from the verticalvent pipe to combustible materials.
• Mark the roof hole accordingly.
• Cover the opening of the installed vent pipes.
• Cut and frame the roof hole.
• Use framing lumber the same size as the roofrafters and install the frame securely. Flashing an-chored to the frame must withstand heavy winds.
• Continue to install concentric vent sections upthrough the roof hole (for inside vent installations)or up past the roof line until you reach the appro-priate distance above the roof (for outside termi-nations).
WARNINGMAJOR U.S. BUILDING CODESSPECIFY MINIMUM CHIMNEY AND/ORVENT HEIGHT ABOVE THE ROOF TOP.THESE MINIMUM HEIGHTS ARENECESSARY IN THE INTEREST OFSAFETY. SEE THE FOLLOWINGDIAGRAM FOR MINIMUM HEIGHTS,PROVIDED THE TERMINATION CAP ISAT LEAST TWO (2) FEET FROM AVERTICAL WALL AND 2-FEET BELOW AHORIZONTAL OVERHANG.
This also pertains to vertical vent systems installedon the outside of the building.
NOTE:
!
Heat & Glo • CFX-CRESCENT • 705-900 Rev. M • 12/0524
Roof Pitch H (min.) ft.
flat to 6/12 1.0over 6/12 to 7/12 1.25over 7/12 to 8/12 1.5over 8/12 to 9/12 2.0over 9/12 to 10/12 2.5over 10/12 to 11/12 3.25over 11/12 to 12/12 4.0over 12/12 to 14/12 5.0over 14/12 to 16/12 6.0over 16/12 to 18/12 7.0over 18/12 to 20/12 7.5over 20/12 to 21/12 8.0
Figure 19. Minimum Height from Roof to Lowest Discharge Opening
To seal the roof hole, and to divert rain and snowfrom the vent system:
• Attach a flashing to the roof using nails, and usea non-hardening mastic around the edges of theflashing base where it meets the roof.
• Attach a storm collar over the flashing joint toform a water-tight seal. Place non-hardeningmastic around the joint, between the storm collarand the vertical pipe.
• Slide the termination cap over the end of the ventpipe and rotate the pipe clockwise 1/4 turn.
1. Attach the flashingand apply sealantaround the edges ofthe flashing base.
2. Attach the stormcollar over the flash-ing joint and applysealant between thestorm collar andvertical pipe.
HORIZONTALOVERHANG
VERTICALWALL
TERMINATIONCAP
12X
ROOF PITCHIS X/ 12
LOWEST DISCHARGE
OPENING
H (MIN.) - MINIMUM HEIGHT FROM ROOFTO LOWEST DISCHARGE OPENING
2 FT.MIN.
2 FT. MIN.
Heat & Glo • CFX-CRESCENT • 705-900 Rev. M • 12/05 25
Figure 21. Proper Positioning, Leveling, and Securing of a Fireplace
Step 5The Gas ControlSystem
WARNING: THIS UNIT IS NOT FOR USEWITH SOLID FUEL.
Intermittent Pilot Ignition (IPI) System
Figure 22. Gas Control System
Step 4Positioning,Leveling, andSecuring theFireplace
!
!
WARNING: To secure properclearances the front framingheader must be installed onits narrow edge and to thefront of the frame.
BOTTOM (2)FRAMING TABS
TOP (4)FRAMING
TABS
To properly position, level,and secure the fireplace:1. Place the fireplace into
position.2. Level the fireplace from
side to side and fromfront to back.
3. Fold out top four framingtabs to be flush with (2)bottom tabs as shown(Figure 21).
4. Secure the fireplace tothe framing by nailing orscrewing to all six fram-ing tabs.
NOTE: Before positioningfireplace into framing re-move Finishing Strips thatare secured to right sideof fireplace. The strips willbe used in the finishingprocess. Refer to Finish-ing Variations addendumincluded in manual bag.
WARNING: CONTINUOUS 110-120 VAC SER-VICE MUST BE WIRED DIRECTLY TO THEFIREPLACE JUNCTION BOX .
The gas control systemused with this model isIntermittent Pilot Ignition(IPI). This system in-cludes a 3V control valve.electronic module, andintermittent pilot.
Figure 20. Remove Finishing Strips
FINISHINGSTRIPS
IGNITOR
Heat & Glo • CFX-CRESCENT • 705-900 Rev. M • 12/0526
NOTE: Have the gas supply line installed in accordancewith local building codes by a qualified installer ap-proved and/or licensed as required by the locality. (Inthe Commonwealth of Massachusetts installation mustbe performed by a licensed plumber or gas fitter).NOTE: Before the first firing of the fireplace, the gassupply line should be purged of any trapped air.NOTE: Consult local building codes to properly size the gassupply line leading to 1/2 inch (13 mm) hook-up at the unit.This gas fireplace is designed to accept a 1/2 inch (13mm) gas supply line. To install the gas supply line:• A listed (and Commonwealth of Massachusetts approved)
1/2 inch (13mm) tee-handle manual shut-off valve and alisted flexible gas connector are connected to the 1/2inch (13mm) inlet of the control valve. NOTE: If substi-tuting for these components, please consult local codesfor compliance.
• A 1/8 inch (3 mm) N.P.T. plugged tapping, accessible fortest gauge connection, should be provided for in the gassupply line leading to the unit’s shut-off valve.
• Remove the decorative door on the unit by pulling awayfrom the unit to release it from the clips on each side.
• Locate the gas line access hole in the outer casing of thefireplace.
• Insert the gas supply line through the gas line hole, andconnect it to the shut-off valve.
• When attaching the pipe, support the control so that thelines are not bent or torn.
• After the gas line installation is complete, all connections mustbe tightened and checked for leaks with a commercially-avail-able, non-corrosive leak check solution. Be sure to rinse off allleak check solution following testing.
Step 6The GasSupply Line
WARNING: DO NOT USE AN OPENFLAME TO CHECK FOR GAS LEAKS.!
ELECTRICALACCESS
GASVALVE
FLEXCONNECTOR
MANUALSHUT-OFF
VALVE
USE WRENCHON SHUT-OFF VALVEWHEN TIGHTENING
GAS LINE
Figure 23. Gas Supply Line
• At the gas lineaccess hole in theouter casing, useinsulation to re-packthe space aroundthe gas pipe.
• The gas line shouldbe installed by aqualified servicetechnician.
Heat & Glo • CFX-CRESCENT • 705-900 Rev. M • 12/05 27
Step 7Gas PressureRequirements
Pressure requirements for Heat & Glo gas fireplacesare shown in the table below.
Pressure Natural Gas Propane
Minimum 5.0 inches 11.0 inchesInlet Pressure w.c. w.c.
Maximum Inlet 14.0 inches 14.0 inchesGas Pressure w.c. w.c.
Manifold 3.5 inches 10.0 inchesPressure w.c. w.c.
A one-eighth (1/8) inch (3 mm) N.P.T. plugged tappingis provided on the inlet and outlet side of the gascontrol for a test gauge connection to measure themanifold pressure.
The fireplace and its individual shut-off valve mustbe disconnected from the gas supply piping systemduring any pressure testing of the system at testpressures in excess of one-half (1/2) psig (3.5 kPa).
The fireplace must be isolated from the gas supplypiping system by closing its individual shut-off valveduring any pressure testing of the gas supply pipingsystem at test pressures equal to or less than one-half (1/2) psig (3.5 kPa).
Step 8Wiring theFireplace
NOTE: Electrical wiring must be installed by alicensed electrician.CAUTION: DISCONNECT REMOTE CONTROLSIF YOU ARE ABSENT FOR EXTENDED TIMEPERIODS. THIS WILL PREVENT ACCIDENTALFIREPLACE OPERATION.
Intermittent Pilot Ignition (IPI) WiringAppliance RequirementsThis appliance requires that 110-120 VAC be wiredto the factory installed junction box. Maintain correctpolarity when wiring the junction box. A wall switch isalso required to operate the unit. See wiring diagramfor details.
! WARNING: DO NOT CONNECT 110-120 VAC TO THEGAS CONTROL VALVE OR THE APPLIANCE WILL
MALFUNCTION AND THE VALVE WILL BE DESTROYED.
Heat & Glo • CFX-CRESCENT • 705-900 Rev. M • 12/0528
CAUTION
Optional AccessoriesOptional remote control kits require that 110-120VAC be wired to the fireplace junction box.
Wall SwitchA wall switch is provided and is required. Positionthe wall switch in the desired position on the wall.The wall switch is 110-120 VAC and requiresappropriate wire be used. A junction box should beused for the wire connections. See wiring diagramfor details.At the appliance connect the wire to the ON/OFFswitch pigtails.
LABEL ALL WIRES PRIOR TO DISCONNEC-TION WHEN SERVICING CONTROLS. WIRINGERRORS CAN CAUSE IMPROPER AND DAN-GEROUS OPERATION. VERIFY PROPER OPER-ATION AFTER SERVICING.
Figure 24. Intermittent Pilot Ignition Wiring Diagram
OPTIONALWALL
SWITCH
OPTIONALREMOTE
CONTROL
REMOVE THESE CONNECTORSTO WIRE REMOTE
REMOVE THESE CONNECTORSTO WIRE SWITCHES
JUNCTION BOX120 VAC
PLUG IN
TRANSFORMER3 VAC
BLK
BLK
YLWYLW
BLK
YLW
RELAY
BLK WHT
BRN
BRN
WHT
ORG
GROUND TOFIREPLACE
CHASSIS
BRN
OR
G
HIGH LIMITSWITCH
GR
N
BRN
VALVE
FAN
XFMR
INTERMITTENTPILOT
IGNITION
IGNITION MODULE 3 VAC
FAN
WHT
WH
TPLUG-IN
3V TRANSFORMER
LOW VOLTAGESEE NOTE 1
HIGHTEMP
SWITCH IGNITIONMODULE
(3V)
LOW VOLTAGESEE NOTE 1
VALVE
GROUNDREMOTECONTROL HOTNEUTRAL
FLAME SPARKER/SENSOR
Heat & Glo • CFX-CRESCENT • 705-900 Rev. M • 12/05 29
Figure 25. Intellifire (WSK-MLT) Wiring Diagram
DO NOTUSE
BATTERIES
(BLACK) (RED)
(RED)(BLACK)
DO NOTUSE G Y R
(RED)
(BLACK)
(BROWN)
(BROWN)
(ORANGE)
(ORANGE)(BLACK)
(BLACK)
ACPLUG
FANCONNECTION
FLAME HIGH/LOW
3V ADAPTOR PLUGDO NOTUSE
FLAMESOLENOID
IPIVALVE
(ORANGE)
(GREEN)
IPIMODULE (BROWN)
(BROWN)
LEAVE ASFACTORY WIRED
REAR VIEW
FRONT VIEW
AUXCONNECTION
GROUND PIGTAIL GREEN
(RED) (YELLOW)
FLAME ON (RED) (BLACK)
LEAVE PLUGGEDTO JUNCTION BOX
WSK-MLTThe WSK-MLT kit can be used with the CFX-Crescent but only with limited function. Followwiring diagram (see Figure 25).
Heat & Glo • CFX-CRESCENT • 705-900 Rev. M • 12/0530
Step 9Finishing
3”
9”10”
12”
4”5”
6”7”
8”
11”
NON-COMBUSTIBLEMATERIAL
FLOOR
4.5” 5.5”6.5”
7.5”
8.5”
9.5”10.5”
11.5”12.5”
13.5”
24”
14.5”
53”
38.5”
2 X 4 FRAMINGALLOWED AT 43 5/8”
TOP FRONT EDGEOF FIREPLACE
CEILING
IF JOINTS BETWEEN THE FINISHED WALLS AND THEFIREPLACE SURROUND (TOP AND SIDES) ARESEALED, A 300° F. MINIMUM SEALANT MATERIALMUST BE USED. THESE JOINTS ARE NOT REQUIREDTO BE SEALED. ONLY NON-COMBUSTIBLE MATE-RIAL (USING 300° F. MINIMUM ADHESIVE, IF NEED-ED) CAN BE APPLIED AS FACING TO THE FIREPLACESURROUND. SEE THE DIAGRAM SHOWN BELOW.
CAUTION
Figure 27. Sealant Material
HIGH TEMPERATURE(300 F/149 C MIN.)TOP SEAL JOINT
0 0FINISH WALL MATERIALMAY BE COMBUSTIBLE
- TOP AND SIDES
1/2”
1/2”HIGH TEMP (300 F/149 C MIN.) SIDE SEAL JOINT0 0
34 1/2”
5 7/8”
NON-COMBUSTIBLEAREA
Hearth ExtensionsA hearth extensionmay be desirable foraesthetic reasons.However, ANSI orCAN/CGA testingstandards do notrequire hearthextensions for gasfireplace appliances.
NOTE: Add 1 3/8” to thesemeasurements if measuring fromthe top of the door.
Figure 26. Min. Vertical and Max. HorizontalDimensions of Combustibles above Fireplace
The following diagram shows the minimum vertical andcorresponding maximum horizontal dimensions offireplace mantels or other combustible projections abovethe top front edge of the fireplace. See Figures 2 and 3for other fireplace clearances. Only non-combustiblematerials may be used to cover the black fireplace front.
Heat & Glo • CFX-CRESCENT • 705-900 Rev. M • 12/05 31
Installing the TrimCombustible materials may be brought up to thespecified clearances on the side and the top front edgesof the fireplace, but MUST NEVER overlap onto thefront face. The joints between the finished wall and thefireplace top and sides can only be sealed with a 300° F.(149° C) minimum sealant.
Install optional marble and brass trim surround kits asdesired. Marble, brass, brick, tile, or other non-combustible materials can be used to cover up the gapbetween the sheet rock and the fireplace. They canoverlap front face up to arch door front.
When overlapping on both sides, leave enough spaceso the decorative door is accessible.
NON-COMBUSTIBLE FINISHING MATERIALSMUST NEVER COVER/OVERLAP ARCHEDDECORATION DOOR.
Step 10Glass DoorRemoval,Installing Trim,Handle, Logsand EmberMaterial
CAUTION
Figure 28. Glass Door Removal
TOP TWOSCREWS
BOTTOMRETENTION
CLIPS
GLASSASSEMBLY
Remove the glass assembly. Using a phillips screwdriver, loosen the top two screws. Unfasten the bottomretention clips and pull glass assembly out from thebottom. See Figure 28.
Removing Glass Door
Heat & Glo • CFX-CRESCENT • 705-900 Rev. M • 12/0532
Figure 29. Placement of Ember Material
Positioning the LogsThe logs have been packaged separately, refer to theinstallation instructions that accompany the logs.Save the log instructions with this manual.
If sooting occurs, the logs might need to be repositionedslightly to avoid excessive flame impingement.
EMBER MATERIAL
LAVAROCK
BURNERTRAY
Placing the Ember Material and Lava RockTwo separate bags of ember material and one bagof lava rock are shipped with this gas fireplace: Thebag labeled Golden Ember (GE-93) is flame colorantmaterial. The bag labeled Glowing Ember (050-721)is standard glowing ember material. To place theember material:
• Remove the trim door by lifting up and away from theunit or if you have an ARCH door, pull away from theunit to release it from the clips on each side.
• Remove the glass door from the unit. Refer toglass removal in Step 10.
• Cover the top of the burner with a single layer ofember material. NOTE: Do NOT cover burnerports with embers. Then sprinkle GE-93 on top ofthe burner.
• Save the remaining ember materials for use duringfireplace servicing.
• Place lava rock on burner tray.
• Replace the glass door and a front trim door on theunit.
___________________________________________
Shutter SettingsNG LP
Burner 5/16” Fully Open
Heat & Glo • CFX-CRESCENT • 705-900 Rev. M • 12/05 33
Before lighting the fireplace, be sure to do thefollowing:• Remove all paperwork from underneath the
fireplace.Review safety warnings and cautions• Read the Safety and Warning Information section
at the beginning of this Installers Guide.Double-check for gas leaks• Before lighting the fireplace, double-check the unit for
possible gas leaks.Double-check vent terminations.• Before lighting the fireplace, double-check the unit for
possible obstructions that could be blocking the ventterminations.
Double-check for faulty components• Any component that is found to be faulty MUST BE
replaced with an approved component. Tampering withthe fireplace components is DANGEROUS and voidsall warranties.
A small amount of air will be in the gas supply lines. Whenfirst lighting the fireplace, it will take a few minutes for thelines to purge themselves of this air. Once the purging iscomplete, the fireplace will light and will operate normally.
Subsequent lightings of the fireplace will not require thispurging of air from the gas supply lines, unless the gasvalve has been turned to the OFF position, in whichcase the air would have to be purged.
NOTE: The fireplace should be run 3 to 4 hours on theinitial start-up. Turn it off and let it cool completely.Remove and clean the glass. Replace the glass and runthe fireplace for an additional 8 hours. This will help tocure the products used in the paint and logs.
Step 11Before Lightingthe Fireplace
Step 12Lightingthe Fireplace
After theInstallation
!
You’ve reviewed all safety warnings, you’ve checked thefireplace for gas leaks, you know the vent system isunobstructed, and you’ve checked for faulty components.Now you’re ready to light the fireplace.
WARNING: PLEASE REFER TO THE USER’SMANUAL FOR ALL CAUTIONS, SAFETY, AND
WARNING INFORMATION PERTAINING TO THELIGHTING AND OPERATION OF THE FIRE-PLACE.
LEAVE THIS INSTALLATION MANUAL WITHTHE APPLIANCE FOR FUTURE REFERENCE.
During this break-in period it is recommended that somewindows in the house be opened for air circulation. This willhelp avoid setting off smoke detectors, and help eliminateany odors associated with the fireplace’s initial burning.
Heat & Glo • CFX-CRESCENT • 705-900 Rev. M • 12/0534
4MaintainingandServicingYourFireplace
FireplaceMaintenance
Although the frequency of your fireplace servicing andmaintenance will depend on use and the type ofinstallation, you should have a qualified servicetechnician perform an appliance check-up at thebeginning of each heating season. See the table belowfor specific guidelines regarding each fireplacemaintenance task.
IMPORTANT TURN OFF THE GAS BEFORE SERVICINGYOUR FIREPLACE.
Type ofFireplace Fireplace Maintenance Task To
Maintenance Frequency By Be Completed
Replacing Once annually, Qualified Brush away loose ember material nearOld Ember during the Service the burner. Replace old emberMaterial annual check-up Technician material with new dime-size and -shape
pieces of Golden Ember (GE-93) andGlowing Ember (050-721). New embermaterial should be placed alternately ontop of the burner—a layer of GoldenEmber, a layer of Glowing Ember,and so on. Save the remaining embermaterial and repeat this procedure atyour next servicing. For moreinformation, see Placing EmberMaterial in the INSTALLERS GUIDE.
Cleaning Once annually Qualified Brush or vacuum the controlBurner Service compartment, fireplace logs, and& Controls Technician burner areas surrounding the logs.
Cleaning Periodically Qualified Make a visual check of the straight flameFlame Service sensor rod. Use emery cloth toSensor Rod Technician/ carefully remove any existing white(IPI System) Owner deposits.
Checking Periodically Qualified Make a visual check of your fireplace’sFlame Service flame patterns. Make sure the flamesPatterns, Technician/ are steady—not lifting or floating. SeeFlame Height Owner Figure 30.
Checking Before initial use Qualified Inspect the external vent cap on aVent System and at least Service regular basis to ensure that no debris is
annually thereafter, Technician/ interfering with the flow of air. Inspectmore frequently Owner entire vent system for proper function.if possible
Cleaning After first 3 to 4 hours Homeowner Remove and clean glass after the first 3Glass Door of use. As necessary to 4 hours of use. After the initial cleaning,
after initial cleaning. clean as necessary, particularly afteradding new ember (flame colorant)material. Film deposits on the inside ofthe glass door should be cleaned offusing a household glass cleaner.
NOTE: DO NOT handle or attempt toclean the door when it is hot andDO NOT use abrasive cleaners. Referto Step 10 for Glass Removal.
Heat & Glo • CFX-CRESCENT • 705-900 Rev. M • 12/05 35
Figure 30. Burner Flame Patterns
MAKE SURE THE FLAMESARE STEADY—NOTLIFTING OR FLOATING.