+ All Categories
Home > Documents > Instruction Book M-3425A Generator Protection...Pickup is based on the generator nominal current...

Instruction Book M-3425A Generator Protection...Pickup is based on the generator nominal current...

Date post: 24-Oct-2020
Category:
Upload: others
View: 3 times
Download: 0 times
Share this document with a friend
382
Instruction Book M-3425A Generator Protection
Transcript
  • Instruction Book

    M-3425AGenerator Protection

  • Generator Protection M‑3425AIntegrated Protection System® for Generators of All Sizes

    PROTECTION

    Unit shown with optional M‑3925A Target Module and M‑3931 HMI (Human‑Machine Interface) Module

    • ExceedsIEEEC37.102andStandard242requirementsforgeneratorprotection

    • Protectsgeneratorsofanyprimemover,groundingandconnectiontype

    • Providesallmajorprotectivefunctionsforgeneratorprotection includingOut-of-Step(78),Split-PhaseDifferential(50DT), UnderFrequencyTimeAccumulation(81A),Inadvertent Energizing(50/27)andTurn-to-TurnFault(59X)

    • ExpandedIPScom®CommunicationsSoftwareprovidessimpleand logicalsettingandprogramming,includinglogicschemes

    • SimpleapplicationwithBaseandComprehensiveprotectionpackages

    • Loadencroachmentblindersandpowerswingblockingfor systembackupprotection(21)toenhancesecurityduring systemabnormalconditions

    • Options:EthernetConnection,FieldGround/BrushLift-OffProtection(64F/B),SyncCheck(25),100%StatorGroundFaultProtectionbylowfrequencyinjection(64S)andExpandedI/O(15additionalOutputContactsand8additionalControl/StatusInputs)

  • –2–

    M‑3425A Generator Protection Relay

    Optional Protective Functions • SyncCheckwithPhaseAngle,∆Vand∆F

    withdeadline/deadbusoptions(25) • FieldGround(64F)andBrushLiftOff(64B)

    (IncludesM-3921FieldGroundCoupler) • 100% Stator Ground protection by low

    frequency injection (64S). The followingequipmentisrequiredwiththe64Soption:

    –20Hzsignalgenerator(430-00426) –Band-passFilter(430-00427)

    –400/5A20HzCT(430-00428)

    Standard Features • Eight programmable outputs and six

    programmableinputs • Oscillographic recordingwithCOMTRADE

    orBECOformat • Time-stampedtargetstoragefor32events • Metering of all measured parameters and

    calculatedvalues • Three communications ports (two RS-232

    andoneRS-485) • M-3820DIPScom®CommunicationsSoftware • IncludesMODBUSandBECO2200protocols • Standard 19" rack-mount design (vertical

    mountingavailable) • Removableprintedcircuitboardandpowersupply • 50and60Hzmodelsavailable • Both1Aand5AratedCTinputsavailable • Additionaltripinputsforexternallyconnected

    devices • IRIG-Btimesynchronization • OperatingTemperature:–20°Cto+70°C • SequenceofEventsLog • TripCircuitMonitoring • BreakerMonitoring • FourSetpointGroups

    Optional Features • Redundantpowersupply • M-3925ATargetModule • M-3931 Human-Machine Interface (HMI)

    Module • RJ45 Ethernet port utilizing MODBUS over

    TCP/IP and BECO2200 over TCP/IP pro-tocols

    • RJ45EthernetportutilizingIEC61850Pro-tocol

    • M-3801D IPSplot® PLUS Oscillograph AnalysisSoftware

    • Expanded I/O (15 additional outputs and 8additionalinputs)

    • StandardandExpandedI/OModelsavailableinverticalpanelmount

    Protective FunctionsBase Package • Overexcitation(V/Hz)(24) • PhaseUndervoltage(27) • Directional power sensitive triple-setpoint

    Reverse Power, Low Forward Power or Overpowerdetection,oneofwhichcanbeusedforsequentialtripping(32)

    • Dual-zone, offset-mho Loss of Field (40),which may be applied with undervoltagecontrolledacceleratedtripping

    • Sensitive Negative Sequence Overcurrent protectionandalarm(46)

    • InstantaneousPhaseOvercurrent(50) • InadvertentEnergizing(50/27) • GeneratorBreakerFailure(50BF) • InstantaneousNeutralOvercurrent(50N) • InverseTimeNeutralOvercurrent(51N) • Three-phase Inverse Time Overcurrent

    (51V) with voltage control and voltage re-straint.

    • PhaseOvervoltage(59) • NeutralOvervoltage(59N) • Multi-purposeOvervoltage(59X) • VTFuse-LossDetectionandblocking

    (60FL) • ResidualDirectionalOvercurrent(67N) • Four-stepOver/Underfrequency(81) • PhaseDifferentialCurrent(87) • Ground (zero sequence) Differential

    Current(87GD) • IPSlogictakesthecontactinputstatusand

    function status and generates outputs byemploying (OR, AND, and NOT) booleanlogicandatimer.

    Protective FunctionsComprehensive PackageTheComprehensivePackageincludesallBasePack-agefunctions,aswellasthefollowing:

    • Three-zone Phase Distance protection forphase fault backup protection (21). ZonethreecanbeusedforOut-of-StepBlocking.Loadencroachmentblinderscanbeapplied.

    • 100% Stator Ground Fault protection usingThirdHarmonicNeutralUndervoltage(27TN)or(59D)ThirdHarmonicVoltageDifferential(ratio)

    • Stator Overload (49) (Positive SequenceOvercurrent)

    • Definite Time Overcurrent (50DT) can beusedforsplitphasedifferential

    • Out-of-Step(78) • UnderFrequencyAccumulation(81A) • RateofChangeofFrequency(81R)

  • –3–

    M‑3425A Generator Protection Relay

    PROTECTIVE FUNCTIONSDevice Setpoint Number Function Ranges Increment Accuracy†

    Phase Distance (three‑zone mho characteristic) CircleDiameter#1,#2,#3 0.1to100.0Ω 0.1Ω 0.1Ωor5% (0.5to500.0Ω) (0.5Ωor5%)

    Offset#1,#2,#3 –100.0to100.0Ω 0.1Ω 0.1Ωor5% (–500.0to500.0Ω) (0.5Ωor5%)

    ImpedanceAngle#1,#2,#3 0°to90° 1° 1°

    Load Encroachment Blinder #1,#2,#3 Angle 1°to90° 1° 1° RReach 0.1to100Ω

    TimeDelay#1,#2,#3 1to8160Cycles 1Cycle 1Cycleor1%

    Out-of-StepDelay 1to8160Cycles 1Cycle 1Cycleor1%

    OvercurrentSupervision 0.1to20A 0.1A 0.1Aor2% (0.02to4A) 0.01A 0.02Aor2%

    When out-of-step blocking on Zone 1 or Zone 2 is enabled, Zone 3 will not trip and it will be used to detect the out-of-step condition for blocking Function 21 #1 and/or 21 #2.

    Volts / Hz Definite Time Pickup#1,#2 100to200% 1% 1%

    TimeDelay#1,#2 30to8160Cycles 1Cycle 25Cycles

    Inverse Time

    Pickup 100to200% 1% 1% CharacteristicCurves InverseTime#1–#4 — —

    TimeDial: Curve#1 1to100 1 1% TimeDial: Curves#2–#4 0.0to9.0 0.1 1%

    ResetRate 1to999Sec. 1Sec. 1Secondor1% (fromthresholdoftrip)

    The percent pickup is based on nominal VT secondary voltage and nominal system frequency settings. The pickup accuracy stated is only applicable from 10 to 80 Hz, 0 to 180 V, 100 to 150% V/Hz and a nominal voltage setting of 120 V.

    Phase Undervoltage

    Pickup#1,#2,#3 5to180V 1V 0.5Vor0.5% 0.8Vor0.75%*

    TimeDelay#1,#2,#3 1to8160Cycles 1Cycle 1Cycleor0.5%**

    * When both RMS and Line-Ground to Line-Line VT connection is selected.

    **When RMS (total waveform) is selected, timing accuracy is O20 cycles or 1%.

    †Selectthegreateroftheseaccuracyvalues. Valuesinparenthesesapplyto1ACTsecondaryrating.

    21

    24

    27

  • –4–

    M‑3425A Generator Protection Relay

    PROTECTIVE FUNCTIONS (cont.)Device Setpoint Number Function Ranges Increment Accuracy†

    Third‑Harmonic Undervoltage, Neutral

    Pickup#1,#2 0.10to14.00V 0.01V 0.1Vor1%

    PositiveSequence VoltageBlock 5to180V 1V 0.5Vor0.5%

    ForwardUnderPowerBlock 0.01to1.00PU 0.01PU 0.01PUor2%

    ReverseUnderPowerBlock–1.00to–0.01PU 0.01PU 0.01PUor2%

    LeadUnderVArBlock –1.00to–0.01PU 0.01PU 0.01PUor2%

    LagUnderVArBlock 0.01to1.00PU 0.01PU 0.01PUor2%

    LeadPowerFactorBlock 0.01to1.00 0.01 0.03PUor3%

    LagPowerFactorBlock 0.01to1.00 0.01 0.03PUor3%

    HighBandForward PowerBlock 0.01to1.00PU 0.01PU 0.01PUor2%

    LowBandForward PowerBlock 0.01to1.00PU 0.01PU 0.01PUor2%

    TimeDelay#1,#2 1to8160Cycles 1Cycle –1to+5Cyclesor1%

    Directional Power

    Pickup#1,#2,#3 –3.000to+3.000PU 0.001PU 0.002PUor2%

    TimeDelay#1,#2,#3 1to8160Cycles 1Cycle +16Cyclesor1%

    The minimum Pickup limits are –.002 and +.002 respectively.

    The per-unit pickup is based on nominal VT secondary voltage and nominal CT secondary current settings. This function can be selected as either overpower or underpower in the forward direction (positive setting) or reverse direction (negative setting). Element #3 can be set as real power or reactive power. This function includes a pro-grammable target LED that may be disabled.

    Loss of Field (dual‑zone offset‑mho characteristic)

    CircleDiameter#1,#2 0.1to100.0Ω 0.1Ω 0.1Ωor5% (0.5to500.0Ω) (0.5Ωor5%)

    Offset#1,#2 –50.0to50.0Ω 0.1Ω 0.1Ωor5% (–250.0to250.0Ω) (0.5Ωor5%)

    TimeDelay#1,#2 1to8160Cycles 1Cycle 1Cycleor1%

    TimeDelaywith VoltageControl#1,#2 1to8160Cycles 1Cycle 1Cycleor1%

    VoltageControl 5to180V 1V 0.5Vor0.5% (positivesequence)

    DirectionalElement 0°to20° 1° —

    Time delay with voltage control for each zone can be individually enabled.

    †Selectthegreateroftheseaccuracyvalues. Valuesinparenthesesapplyto1ACTsecondaryrating.

    40

    32

    27TN

  • –5–

    M‑3425A Generator Protection Relay

    PROTECTIVE FUNCTIONS (cont.)Device Setpoint Number Function Ranges Increment Accuracy†

    Negative Sequence Overcurrent

    Definite Time Pickup 3to100% 1% 0.5%of5A (0.5%of1A)

    TimeDelay 1to8160Cycles 1Cycle 1Cycleor1%

    Inverse Time Pickup 3to100% 1% 0.5%of5A (0.5%of1A)

    TimeDialSetting 1to95 1 3Cyclesor3% (K=I2

    2t)

    DefiniteMaximum TimetoTrip 600to65,500Cycles 1Cycle 1Cycleor1%

    DefiniteMinimumTime 12Cycles — fixed

    ResetTime(Linear) 1to600Seconds 1Second 1Secondor1% (fromthresholdoftrip)

    Pickup is based on the generator nominal current setting.

    Stator Overload Protection

    TimeConstant#1,#2 1.0to999.9minutes 0.1minutes

    MaximumOverloadCurrent 1.00to10.00A 0.01A 0.1Aor2% (0.20to2.00A)

    Instantaneous Phase Overcurrent

    Pickup#1,#2 0.1to240.0A 0.1A 0.1Aor3% (0.1to48.0A) (0.02Aor3%) TimeDelay#1,#2 1to8160Cycles 1Cycle 1Cycleor1%

    When frequency f is < (fnom –5 ) Hz add an additional time of (1.5/f + 0.033) sec to the time delay accuracy.

    Breaker Failure

    Pickup PhaseCurrent 0.10to10.00A 0.01A 0.1Aor2% (0.02to2.00A) (0.02Aor2%)

    NeutralCurrent 0.10to10.00A 0.01A 0.1Aor2% (0.02to2.00A) (0.02Aor2%)

    TimeDelay 1to8160Cycles 1Cycle 1Cycleor1%

    50BF can be initiated from designated M-3425A output contacts or programmable control/status inputs.

    Definite Time Overcurrent

    PickupPhaseA#1,#2 0.20Ato240.00A 0.01A 0.1Aor3% (0.04Ato48.00A) (0.02Aor3%)

    PickupPhaseB#1,#2 (sameasabove)

    PickupPhaseC#1,#2 (sameasabove)

    TimeDelay#1,#2 1to8160Cycles 1Cycle 1Cycleor1%

    This function uses generator line-side currents.

    When 50DT function is used for split-phase differential protection, 50BF, 87, and 87GD functions should not be used, and the IA, IB and IC inputs must be connected to the split phase differential currents.

    †Selectthegreateroftheseaccuracyvalues. Valuesinparenthesesapplyto1ACTsecondaryrating.

    50DT

    50

    50BF

    50BF-Ph

    50BF-N

    46

    49

  • –6–

    M‑3425A Generator Protection Relay

    PROTECTIVE FUNCTIONS (cont.)Device Setpoint Number Function Ranges Increment Accuracy†

    Instantaneous Neutral Overcurrent

    Pickup 0.1to240.0A 0.1A 0.1Aor3% (0.1to48.0A) (0.02Aor3%) TimeDelay 1to8160Cycles 1Cycle 1Cycleor1%

    When the frequency f is < (fnom –5) Hz add an additional time of (1.5/f + 0.033) sec to the time delay accuracy.

    Inadvertent Energizing

    Overcurrent Pickup 0.5to15.00A 0.01A 0.1Aor2% (0.1to3.00A) (0.02Aor2%)

    Undervoltage Pickup 5to130V 1V 0.5V

    Pick-upTimeDelay 1to8160Cycles 1Cycle 1Cycleor1%

    Drop-outTimeDelay 1to8160Cycles 1Cycle 1Cycleor1%

    When RMS (total Waveform) is selected, timing accuracy is O20 cycles or 1%.

    Inverse Time Neutral Overcurrent

    Pickup 0.25to12.00A 0.01A 0.1Aor1% (0.05to2.40A) (0.02Aor1%)

    CharacteristicCurve DefiniteTime/Inverse/VeryInverse/ExtremelyInverse/IECCurves ModeratelyInverse/VeryInverse/ExtremelyInverse/IEEECurves

    TimeDial 0.5to11.0 0.1 3Cyclesor3%* 0.05to1.10(IECcurves) 0.01 0.5to15.0(IEEEcurves) 0.01

    * For IEC Curves the timing accuracy is 5%.

    When the frequency f is < (fnom –5 )Hz add an additional time of (1.5/f + 0.033) sec to the time delay accuracy.

    Inverse Time Phase Overcurrent, with Voltage Control or Voltage Restraint

    Pickup 0.50to12.00A 0.01A 0.1Aor1% (0.10to2.40A) (0.02Aor1%)

    CharacteristicCurve DefiniteTime/Inverse/VeryInverse/ExtremelyInverse/IECCurves ModeratelyInverse/VeryInverse/ExtremelyInverse/IEEECurves

    TimeDial 0.5to11.0 0.1 3Cyclesor3%* 0.05to1.10(IECcurves) 0.01 0.5to15.0(IEEEcurves) 0.01

    VoltageControl(VC) 5to180V 1V 0.5Vor0.5% or VoltageRestraint(VR) LinearRestraint — —

    * For IEC Curves the timing accuracy is 5%.

    51V

    51N

    50N

    50/27

    50

    27

    †Selectthegreateroftheseaccuracyvalues. Valuesinparenthesesapplyto1ACTsecondaryrating.

  • –7–

    M‑3425A Generator Protection Relay

    PROTECTIVE FUNCTIONS (cont.)Device Setpoint Number Function Ranges Increment Accuracy†

    Phase Overvoltage

    Pickup#1,#2,#3 5to180V 1V 0.5Vor0.5% 0.8Vor0.75%*

    TimeDelay#1,#2,#3 1to8160Cycles 1Cycle 1Cycleor1%**

    InputVoltageSelect Phase,PositiveorNegativeSequence***

    * When both RMS and Line-Ground to Line-Line is selected.

    ** When RMS (total waveform) is selected, timing accuracy is O20 cycles or 1%.

    *** When positive or negative sequence voltage is selected, the 59 Function uses the discrete Fourier transform (DFT) for magnitude calculation, irrespective of the RMS/DFT selection, and timing accuracy is 1 Cycle or 1%. Positive and negative sequence voltages are calculated in terms of line-to-line voltage when Line to Line is selected for V.T. Configuration.

    Third‑Harmonic Voltage Differential Ratio

    Ratio(Vx/VN) 0.1to5.0 0.1

    TimeDelay 1to8160Cycles 1Cycle 1Cycleor1%

    PositiveSeqVoltageBlock 5to180V 1V 0.5Vor0.5%

    LineSideVoltage VXor3V0(calculated)

    The 59D function has a cutoff voltage of 0.5 V for 3rd harmonic VX voltage. If the 180 Hz component of VN is exp-tected to be less than 0.5 V the 59D function can not be used.

    The 59D function with VX cannot be enabled if the 25 function is enabled. The line side voltage can be selected as the third harmonic of 3V0 (equivalent to VA + VB + VC) or VX.

    3V0 selection for line side voltage can only be used with line-ground VT configuration.

    Neutral Overvoltage

    Pickup#1,#2,#3 5.0to180.0V 0.1V 0.5Vor0.5%

    TimeDelay#1,#2,#3 1to8160Cycles 1Cycle 1Cycleor1%

    When 64S is purchased, the 59N Time Delay Accuracy is –1 to +5 cycles.

    Multi‑purpose Overvoltage

    Pickup#1,#2 5.0to180.0V 0.1V 0.5Vor0.5%

    TimeDelay#1,#2 1to8160Cycles 1Cycle 1Cycleor1%

    Multi-purpose input that may be used for turn-to-turn stator ground protection, bus ground protection, or as an extra Phase-Phase, or Phase-Ground voltage input.

    When 64S is purchased, the 59N Time Delay accuracy is –1 to +5 cycles.

    VT Fuse‑Loss Detection

    A VT fuse‑loss condition is detected by using the positive and negative sequence components of the voltages and currents. VT fuse‑loss output can be initiated from internally generated logic, and/or from input contacts.

    AlarmTimeDelay 1to8160Cycles 1Cycle 1Cycleor1%

    ThreePhaseVT FuseLossDetection Enable/Disable

    59

    59N

    60FL

    59X

    59D

    †Selectthegreateroftheseaccuracyvalues. Valuesinparenthesesapplyto1ACTsecondaryrating.

  • –8–

    M‑3425A Generator Protection Relay

    PROTECTIVE FUNCTIONS (cont.)Device Setpoint Number Function Ranges Increment Accuracy†

    Residual Directional Overcurrent

    Definite Time* Pickup 0.5to240.0A 0.1A 0.1Aor3% (0.1to48.0A) (0.02Aor3%)

    TimeDelay 1to8160Cycles 1Cycle –1to+3Cyclesor1%

    Inverse Time* Pickup 0.25to12.00A 0.01A 0.1Aor3% (0.05to2.40A) (0.02Aor3%)

    CharacteristicCurve DefiniteTime/Inverse/VeryInverse/ExtremelyInverse/IECCurves ModeratelyInverse/VeryInverse/ExtremelyInverse/IEEECurves

    TimeDial 0.5to11.0 0.1 3Cyclesor5% 0.05to1.10(IECCurves) 0.01 0.5to15.0(IEEEcurves) 0.01

    Directional Element MaxSensitivityAngle(MSA) 0to359° 1°

    PolarizingQuantity 3Vo(calculated),VNorVX*Directional control for 67NDT or 67NIT may be disabled.VX polarization cannot be used if 25 function is enabled.3Vo polarization can only be used with line-ground VT configuration.Operating current for 67N can be selected as 3Io (calculated) or IN (Residual CT).

    If 87GD is enabled, 67N with IN (Residual CT) operating current will not be available.

    Out of Step (mho characteristic)

    CircleDiameter 0.1to100.0Ω 0.1Ω 0.1Ωor5% (0.5to500.0Ω) (0.5Ωor5%)

    Offset –100.0to100.0Ω 0.1Ω 0.1Ωor5% (–500.0to500.0Ω) (0.5Ωor5%)

    ImpedanceAngle 0°to90° 1° 1°

    Blinder 0.1to50.0Ω 0.1Ω 0.1Ωor5% (0.5to250.0Ω) (0.5Ωor5%)

    TimeDelay 1to8160Cycles 1Cycle 1Cycleor1%

    TriponmhoExit Enable/Disable

    PoleSlipCounter 1to20 1

    PoleSlipReset 1to8160Cycles 1Cycle 1Cycleor1%

    Frequency

    Pickup#1,#2,#3,#4 50.00to67.00Hz 0.01Hz 0.02Hz 40.00to57.00Hz*

    TimeDelay#1–#4 3to65,500Cycles 1Cycle 2Cyclesor1%

    The pickup accuracy applies to 60 Hz models at a range of 57 to 63 Hz, and to 50 Hz models at a range of 47 to 53 Hz. Beyond these ranges, the accuracy is 0.1 Hz.

    * This range applies to 50 Hz nominal frequency models.

    †Selectthegreateroftheseaccuracyvalues. Valuesinparenthesesapplyto1ACTsecondaryrating.

    81

    78

    67N

  • –9–

    M‑3425A Generator Protection Relay

    PROTECTIVE FUNCTIONS (cont.)Device Setpoint Number Function Ranges Increment Accuracy†

    Frequency Accumulation

    Bands#1,#2,#3,#4,#5,#6 HighBand#1 50.00to67.00Hz 0.01Hz 0.02Hz 40.00to57.00Hz*

    LowBand#1–#6 50.00to67.00Hz 0.01Hz 0.02Hz 40.00to57.00Hz*

    Delay#1–#6 3to360,000Cycles 1Cycle 2Cyclesor1%

    When using multiple frequency bands, the lower limit of the previous band becomes the upper limit for the next band, i.e., Low Band #2 is the upper limit for Band #3, and so forth. Frequency bands must be used in sequential order, 1 to 6. Band #1 must be enabled to use Bands #2–#6. If any band is disabled, all following bands are disabled.

    When frequency is within an enabled band limit, accumulation time starts (there is an internal ten cycle delay prior to accumulation) and allows the underfrequency blade resonance to be established to avoid unnecessary accumulation of time. When duration is greater than set delay, the alarm asserts and a target log entry is made.

    The pickup accuracy applies to 60 Hz models at a range of 57 to 63 Hz, and 50 Hz models at a range of 47 to 53 Hz. Beyond these ranges, the accuracy is 0.1 Hz.

    * This range applies to 50 Hz nominal frequency models.

    Rate of Change of Frequency

    Pickup#1,#2 0.10to20.00Hz/Sec. 0.01Hz/Sec. 0.05Hz/Sec.or5%

    TimeDelay#1,#2 3to8160Cycles 1Cycle +20Cycles

    NegativeSequence VoltageInhibit 0to99% 1% 0.5%

    Phase Differential Current

    Pickup#1,#2 0.20Ato3.00A 0.01A 0.1Aor5% (0.04to0.60A) (0.02Aor5%)

    PercentSlope#1,#2 1to100% 1% 2%

    TimeDelay*#1,#2 1to8160Cycles 1Cycle 1Cycleor1%

    CTCorrection** 0.50to2.00 0.01

    *When a time delay of 1 cycle is selected, the response time is less than 1–1/2 cycles.

    **The CT Correction factor is multiplied by IA,IB,IC.

    Ground (zero sequence) Differential Current

    Pickup 0.20to10.00A 0.01A 0.1Aor5% (0.04to2.00A) (0.02Aor5%)

    TimeDelay 1to8160Cycles* 1Cycle +1to-2Cyclesor1%

    CTRatioCorrection(RC) 0.10to7.99 0.01

    *The Time Delay Setting should not be less than 2 Cycles.

    The 87GD function is provided primarily for low-impedance grounded generator applications. This function oper-ates as a directional differential. If 3I0 or In is extremely small (less than 0.2 secondary Amps), the element be-comes non-directional.

    If 67N function with IN (Residual) operating current is enabled, 87GD will not be available. Also, if 50DT is used for split-phase differential, 87GD function will not be available.

    †Selectthegreateroftheseaccuracyvalues. Valuesinparenthesesapplyto1ACTsecondaryrating.

    87

    87GD

    81R

    81A

  • –10–

    M‑3425A Generator Protection Relay

    PROTECTIVE FUNCTIONS (cont.)Device Setpoint Number Function Ranges Increment Accuracy†

    IPSlogicTM

    IPSlogic uses element pickups, element trip commands, control/status input state changes, output contact close signals to develop 6 programmable logic schemes.

    TimeDelay#1–#6 1to8160Cycles 1Cycle 1Cycleor1%

    Breaker Monitoring

    Pickup 0to50,000kACycles 1kACycles 1kACycles orkA2Cycles orkA2Cycles orkA2Cycles

    TimeDelay 0.1to4095.9Cycles 0.1Cycles 1Cycleor1%

    TimingMethod ITorI2T

    PresetAccumulators 0to50,000kACycles 1kACycle PhaseA,B,C

    The Breaker Monitor feature calculates an estimate of the per-phase wear on the breaker contacts by measuring and integrating the current (or current squared) through the breaker contacts as an arc.

    The per-phase values are added to an accumulated total for each phase, and then compared to a user-pro-grammed threshold value. When the threshold is exceeded in any phase, the relay can set a programmable output contact.

    The accumulated value for each phase can be displayed.

    The Breaker Monitoring feature requires an initiating contact to begin accumulation, and the accumulation begins after the set time delay.

    Trip Circuit Monitoring

    TimeDelay 1to8160Cycles 1Cycle 1Cycleor1%

    The AUX input is provided for monitoring the integrity of the trip circuit. This input can be used for nominal trip coil voltages of 24 V dc, 48 V dc, 125 V dc and 250 V dc.

    Nominal Settings

    NominalVoltage 50.0to140.0V 0.1V —

    NominalCurrent 0.50to6.00A 0.01A —

    VTConfiguration Line-Line/Line-Ground/ Line-GroundtoLine-Line* Delta/WyeUnit Transformer Disable/DeltaAB/DeltaAC

    Seal-InDelay 2to8160Cycles 1Cycle 1Cycleor1%

    *When Line-Ground to Line-Line is selected, the relay internally calculates the line-line voltages from the line-ground voltages for all voltage-sensitive functions. This Line-Ground to Line-Line selection should only be used for a VT connected Line-Ground with a secondary voltage of 69 V (not 120 V).

    †Selectthegreateroftheseaccuracyvalues. Valuesinparenthesesapplyto1ACTsecondaryrating.

    IPS

    BM

    TC

  • –11–

    M‑3425A Generator Protection Relay

    64F

    64B

    25

    25S

    25D

    64S

    OPTIONAL PROTECTIVE FUNCTIONSDevice Setpoint Number Function Ranges Increment Accuracy†

    Sync Check

    Dead Check DeadVoltageLimit 0to60V 1V 0.5Vor±0.5%

    DeadTimeDelay 1to8160Cycles 1Cycle –1to+3Cyclesor1%

    Sync Check PhaseAngleLimit 0°to90° 1° 1°

    UpperVoltageLimit 60to140V 1V 0.5Vor±0.5%

    LowerVoltageLimit 40to120V 1V 0.5Vor±0.5%

    DeltaVoltageLimit 1.0to50.0V 0.1V 0.5Vor±0.5%

    DeltaFrequencyLimit 0.001to0.500Hz 0.001Hz 0.0007Hzor±5%

    SyncCheckTimeDelay 1to8160Cycles 1Cycle –1to+3Cyclesor±1%

    Various combinations of input supervised hot/dead closing schemes may be selected. The 25 function cannot be enabled if the 59D function with VX or 67N function with VX is enabled.

    Field Ground Protection

    Pickup#1,#2 5to100KΩ 1KΩ 10%or±1KΩ TimeDelay#1,#2 1to8160Cycles 1Cycle (2IF+1)Sec.

    InjectionFrequency(IF) 0.10to1.00Hz 0.01Hz

    Brush Lift‑Off Detection(measuringcontrolcircuit) Pickup 0to5000mV 1mV

    TimeDelay 1to8160Cycles 1Cycle (2IF+1)Sec.

    When 64F is purchased, an external Coupler Module (M-3921) is provided for isolation from dc field voltages.

    Figure 10, Field Ground Protection Block Diagram, illustrates a typical connection utilizing the M-3921 Field Ground Coupler. Hardware dimensional and mounting information is shown in Figure 11, M-3921 Field Ground Coupler Mounting Dimensions.

    100% Stator Ground Protection by low frequency injection

    TotalCurrentPickup 2to75mA 0.1mA 2mAor10% RealComponentof TotalCurrentPickup 2to75mA 0.1mA 2mAor10% TimeDelay 1to8160Cycles 1Cycle 1Cycle*or1%

    An external Low Frequency Generator, Band Pass Filter and Current Transformer are required for this function. Figure 13, 64S Function Component Connection Diagram, illustrates a typical 100% Stator Ground Protection by Low Frequency Injection application. Hardware dimensional and mounting information is illustrated in Figures 14 and 15.

    59D and 27TN function should be disabled when the 64S function is enabled. 59N may be applied when this func-tion is enabled.

    * Time Delay accuracy in cycles is based on 20 Hz frequency.

    †Selectthegreateroftheseaccuracyvalues. Valuesinparenthesesapplyto1ACTsecondaryrating.

  • –12–

    M‑3425A Generator Protection Relay

    DescriptionTheM-3425AGeneratorProtectionRelayissuitableforallgeneratorratingsandprimemovers.Typicalcon-nectiondiagramsare illustrated inFigure4,M-3425AOne-LineFunctionalDiagram(configured forphasedifferential),andFigure5,One-LineFunctionalDiagram(configuredforsplit-phasedifferential).

    Configuration OptionsTheM-3425AGeneratorProtectionRelayisavailableineitheraBaseorComprehensivepackageofprotec-tivefunctions.Thisprovidestheuserwithflexibilityinselectingaprotectivesystemtobestsuittheapplication.AdditionalOptionalProtectiveFunctionsmaybeaddedatthetimeofpurchaseatper-functionpricing.

    TheHuman-MachineInterface(HMI)Module,TargetModule,orredundantpowersupplycanbeselectedattimeofpurchase.

    WhentheFieldGround(64F)PremiumProtectiveFunctionispurchased,anexternalcouplermodule(M-3921)isprovidedforisolationfromthedcfieldvoltages.

    When100%StatorGround(64S)protectionusinglow-frequencyinjectionispurchased,anexternalbandpassfilterandfrequencygeneratorisprovided.

    Multiple Setpoint Profiles (Groups)Therelaysupportsfoursetpointprofiles.Thisfeatureallowsmultiplesetpointprofilestobedefinedfordifferentpowersystemconfigurationsorgeneratoroperatingmodes.ProfilescanbeswitchedeithermanuallyusingtheHuman-MachineInterface(HMI),bycommunications,programmablelogicorbycontrol/statusinputs.

    NOTE: Duringprofileswitching,relayoperationisdisabledforapproximately1second.

    MeteringTherelayprovidesmeteringofvoltages(phase,neutralandsequencequantities),currents(phase,neutralandsequencequantities),realpower,reactivepower,powerfactorandimpedancemeasurements.

    Meteringaccuraciesare:

    Voltage: 0.5Vor0.5%,whicheverisgreater 0.8Vor0.75%,whicheverisgreater(whenbothRMSandLine-GroundtoLine-Lineare selected)

    Current: 5Arating,0.1Aor3%,whicheverisgreater 1Arating,0.02Aor3%,whicheverisgreater

    Power: 0.01PUor2%ofVAapplied,whicheverisgreater

    Frequency: 0.02Hz(from57to63Hzfor60Hzmodels;from47to53Hzfor50Hzmodels) 0.1Hzbeyond63Hzfor60Hzmodels,andbeyond53Hzfor50Hzmodels

    Volts/Hz: 1%

    Oscillographic RecorderTheoscillographicrecorderprovidescomprehensivedatarecordingofallmonitoredwaveforms,storingupto416cyclesofdata.Thetotalrecordlengthisuser-configurablefrom1to16partitions.Thesamplingrateis16timesthepowersystemnominalfrequency(50or60Hz).Therecordermaybetriggeredusingeitherthedesignatedcontrol/statusinputs,tripoutputs,orusingserialcommunications.Whenuntriggered,therecordercontinuouslystoreswaveformdata, therebykeeping themost recentdata inmemory.When triggered, therecorderstorespre-triggerdata,thencontinuestostoredatainmemoryforauser-defined,post-triggerdelayperiod.ThedatarecordscanbestoredineitherBeckwithElectricformatorCOMTRADEformat.

    Target StorageInformationassociatedwiththelast32tripsisstored.Theinformationincludesthefunction(s)operated,thefunctionspickedup,input/outputstatus,timestamp,andphaseandneutralcurrentsatthetimeoftrip.

  • –13–

    M‑3425A Generator Protection Relay

    Sequence of Events LogTheSequenceofEventsLogrecordsrelayelementstatus,I/Ostatus,measuredvaluesandcalculatedvaluestimestampedwith1msresolutionatuser-definedevents.TheSequenceofEventsLogincludes512ofthemostrecentlyrecordedrelayevents.TheeventsandtheassociateddataisavailableforviewingutilizingtheM-3820DIPScomCommunicationsSoftware.

    CalculationsCurrent and Voltage RMS Values: UsesDiscreteFourierTransformalgorithmonsampledvoltageandcurrentsignalstoextractfundamentalfrequencyphasorsforrelaycalculations. RMScalculationforthe50,51N,59and27functions,andthe24functionareobtainedusingthetimedomainapproachtoobtainaccuracyoverawidefrequencyband.WhentheRMSoptionisselected,themagnitudecalculationfor59and27functionsisaccurateoverawidefrequencyrange(10to80Hz).WhentheDFToptionisselected,themagnitudecalcula-tionisaccuratenearnominalfrequency(50Hz/60Hz)butwilldegradeoutsidethenominalfrequency.For50and51NfunctionstheDFTisusedwhenthefrequencyis55Hzto65Hzfor60Hz(nominal)and45Hzto55Hzfor50Hz(nominal),outsideofthisrangeRMScalculationisused.

    Power Input OptionsNominal110/120/230/240Vac,50/60Hz,ornominal110/125/220/250Vdc.Operatesproperlyfrom85Vacto265Vacandfrom80Vdcto312.5Vdc.Withstands300Vacor315Vdcfor1second.Nominalburden40VAat120Vac/125Vdc.

    Nominal24/48Vdc,operatesproperlyfrom18Vdcto56Vdc,withstands65Vdcfor1second.Burden25VAat24Vdcand30VAat48Vdc.

    AnoptionalredundantpowersupplyisavailableforunitsthatarepurchasedwithouttheexpandedI/O.

    ForthoseunitspurchasedwiththeexpandedI/O,theunitincludestwopowersupplieswhicharerequiredtopowertherelay.Burden(nominal)46VA@120Vac.

    Sensing InputsFive Voltage Inputs: Ratedforanominalvoltageof50Vacto140Vacat60Hzor50Hz.Willwithstand240Vcontinuousvoltageand360Vfor10seconds.Sourcevoltagesmaybeline-to-groundorline-to-lineconnected.PhasesequenceABCorACBissoftwareselectable.Voltagetransformerburdenlessthan0.2VAat120Vac.

    Seven Current Inputs: Ratednominal current (IR) of 5.0Aor1.0Aat 60Hzor50Hz.Willwithstand3IR continuouscurrentand100IRfor1second.Currenttransformerburdenislessthan0.5VAat5A,or0.3VA at1A.

    Control/Status InputsThecontrol/statusinputs,INPUT1throughINPUT6,canbeprogrammedtoblockanyrelayprotectivefunction,totriggertheoscillographrecorder,tooperateoneormoreoutputsorcanbeaninputintoIPSlogic.ToprovidebreakerstatusLEDindicationonthefrontpanel,theINPUT1control/statusinputcontactmustbeconnectedtothe52bbreakerstatuscontact.Theminimumcurrentvaluetoinitiate/pickupanInputis>25mA.

    TheoptionalexpandedI/Oincludesanadditional8programmablecontrol/statusinputs(INPUT7throughINPUT14).

    ▲ CAUTION:Thecontrol/statusinputsshouldbeconnectedtodrycontactsonly,andareinternallyconnected(wetted)witha24Vdcpowersupply.

    Output ContactsAnyofthefunctionscanbeindividuallyprogrammedtoactivateanyoneormoreoftheeightprogrammableoutputcontactsOUTPUT1throughOUTPUT8.Anyoutputcontactcanalsobeselectedaspulsedorlatched.IPSlogiccanalsobeusedtoactivateanoutputcontact.

    TheoptionalexpandedI/Oincludesanadditional15programmableoutputcontacts(OUTPUT9throughOUT-PUT23).ThesecontactsareconfigurableonlyusingIPScomsoftware.

    Theeightoutputcontacts(sixform‘a’andtwoform‘c’),thepowersupplyalarmoutputcontact(form‘b’),the self-testalarmoutputcontact(form‘c’)andtheoptional15expandedI/Ooutputcontacts(form'a')areallratedperANSI/IEEEC37.90-1989fortripping.Make30Afor0.2seconds,carry8A,break6Aat120Vac,break0.5Aat48Vdc;0.3A,125Vdc;0.2A,250VdcwithL/R=40mSec.

  • –14–

    M‑3425A Generator Protection Relay

    IPSlogicThisfeaturecanbeprogrammedutilizingtheIPScom®CommunicationsSoftware.IPSlogictakesthecontactinputstatusandfunctionstatus,andbyemploying(OR,AND,andNOT)booleanlogicandatimer,canactivateanoutputorchangesettingprofiles.

    Target/Status Indicators and ControlsTheRELAY OK LEDrevealspropercyclingofthemicrocomputer.TheBRKR CLOSEDLEDwillilluminatewhenthebreakerisclosed(whenthe52bcontactinputisopen).TheOSC TRIGLEDindicatesthatoscillographicdatahasbeenrecordedintheunit'smemory.TheTARGETLEDwillilluminatewhenanyoftherelayfunctionsoperate.PressingandreleasingtheTARGET RESETbuttonresetsthetargetLEDiftheconditionscausingtheoperationhavebeenremoved.HoldingtheTARGET RESETpushbuttondisplaysthepresentpickupstatusoftherelayfunctions.ThePS1andPS2LEDswillremainilluminatedaslongaspowerisappliedtotheunitandthepowersupplyisoperatingproperly.TIME SYNCLEDilluminateswhenvalidIRIG-Bsignalisappliedandtimesynchronizationhasbeenestablished.

    CommunicationCommunicationsportsincluderearpanelRS-232andRS-485ports,afrontpanelRS-232port,arear-panelIRIG-BportandanEthernetport(optional).Thecommunicationsprotocolimplementsserial,byte-oriented,asynchronouscommunication,providing the following functionswhenusedwith theWindows™-compatibleM-3820DIPScom®CommunicationsSoftware.MODBUSandBECO2200protocolsaresupportedproviding:

    • Interrogationandmodificationofsetpoints

    • Time-stampedinformationforthe32mostrecenttrips

    • Real-timemeteringofallquantitiesmeasured

    • DownloadingofrecordedoscillographicdataandSequenceofEventsRecorderdata.

    TheoptionalEthernetportcanbepurchasedwithMODBUSoverTCP/IPandBECO2200overTCP/IPprotocolsorwiththeIEC61850protocol.

    IRIG-BTheM-3425AGeneratorProtectionRelaycanaccepteithermodulatedordemodulatedIRIG-Btimeclocksyn-chronizationsignal.TheIRIG-Btimesynchronizationinformationisusedtocorrectthehour,minutes,seconds,andmillisecondsinformation.

    HMI Module (optional)Local access to the relay is provided through an optionalM-3931HMI (Human-Machine Interface)Mod-ule,allowing foreasy-to-use,menu-drivenaccess toall functionsutilizingsixpushbuttonsanda2-lineby 24characteralphanumericvacuumflorescentdisplay.FeaturesoftheHMIModuleinclude:

    • User-definableaccesscodesthatallowthreelevelsofsecurity

    • Interrogationandmodificationofsetpoints

    • Time-stampedinformationforthe32mostrecenttrips

    • Real-timemeteringofallquantitiesmeasured

    Target Module (optional)AnoptionalM-3925ATargetModuleprovides24targetand8outputLEDs.AppropriatetargetLEDswillillumi-natewhenthecorrespondingfunctionoperates.ThetargetscanberesetwiththeTARGET RESETpushbutton.TheOUTPUTLEDsindicatethestatusoftheprogrammableoutputrelays.

  • –15–

    M‑3425A Generator Protection Relay

    Temperature Controller MonitoringAnyTemperatureControllerequippedwithacontactoutputmaybeconnectedtotheM-3425Aandcontrolledby the relay'sprogrammable IPSlogic function.Figure1 isanexampleofa typicalTemperatureControllerMonitoring application.TheOmron E5C2Temperature Controller is a DIN rail mounted RTD interface totheM-3425AGeneratorProtectionrelay.TheE5C2acceptstypeJorKthermocouples,platinumRTDsor thermistorsas its input.Supplyvoltage for theE5C2accepts110/120Vac,50/60Hz,or220/240Vac 50/60Hzor24Vdc.

    TemperatureController

    Omron E5C2P.D. 750

    or equivalent

    IN X

    IN RTN

    M-3425A

    IPSlogic

    Alarm/TripR1C

    R2

    Figure 1 Typical Temperature Controller Monitoring Application

    I/O Expansion (optional)OptionalI/OExpansionprovidesanadditional15form'a'outputcontactsandanadditional8control/statusinputs.OutputLEDsindicatethestatusoftheoutputrelays.

    Tests and StandardsTherelaycomplieswiththefollowingtypetestsandstandards:

    Voltage Withstand

    Dielectric WithstandIEC60255-5 3,500Vdcfor1minuteappliedtoeachindependentcircuittoearth 3,500Vdcfor1minuteappliedbetweeneachindependentcircuit 1,500Vdcfor1minuteappliedtoIRIG-Bcircuittoearth 1,500Vdcfor1minuteappliedbetweenIRIG-Btoeachindependentcircuit 1,500Vdcfor1minuteappliedbetweenRS-485toeachindependentcircuit

    Impulse VoltageIEC60255-5 5,000Vpk,+/-polarityappliedtoeachindependentcircuittoearth 5,000Vpk,+/-polarityappliedbetweeneachindependentcircuit 1.2by50µs,500ohmsimpedance,threesurgesat1every5seconds

    Insulation ResistanceIEC60255-5 >100Megaohms

  • –16–

    M‑3425A Generator Protection Relay

    Electrical Environment

    Electrostatic Discharge TestEN60255-22-2 Class4(8kV)—pointcontactdischarge

    EN60255-22-2 Class4(15kV)–airdischarge

    Fast Transient Disturbance TestEN60255-22-4 ClassA(4kV,2.5kHz)

    Surge Withstand CapabilityANSI/IEEE 2,500Vpk-pkoscillatoryappliedtoeachindependentcircuittoearthC37.90.1- 2,500Vpk-pkoscillatoryappliedbetweeneachindependentcircuit1989 5,000VpkFastTransientappliedtoeachindependentcircuittoearth 5,000VpkFastTransientappliedbetweeneachindependentcircuit

    ANSI/IEEE 2,500Vpk-pkoscillatoryappliedtoeachindependentcircuittoearthC37.90.1- 2,500Vpk-pkoscillatoryappliedbetweeneachindependentcircuit2002 4,000VpkFastTransientburstappliedtoeachindependentcircuittoearth 4,000VpkFastTransientburstappliedbetweeneachindependentcircuit

    NOTE: Thesignalisappliedtothedigitaldatacircuits(RS-232,RS-485,IRIG-B,Ethernetcommunicationportandfieldgroundcouplingport)throughcapacitivecouplingclamp.

    Radiated SusceptibilityANSI/IEEE 25-1000Mhz@35V/mC37.90.2

    Output ContactsANSI/IEEE Make30Afor0.2seconds,offfor15secondsfor2,000operations,perSection6.7.1,TrippingC37.90.0 OutputPerformanceRequirements

    Atmospheric Environment

    TemperatureIEC60068-2-1 Cold,–20°CIEC60068-2-2 DryHeat,+70°CIEC60068-2-3 DampHeat,+40°C@93%RH

    Mechanical Environment

    VibrationIEC60255-21-1 VibrationresponseClass1,0.5g VibrationenduranceClass1,1.0g

    IEC60255-21-2ShockResponseClass1,5.0g ShockWithstandClass1,15.0g BumpEnduranceClass1,10.0g

    Compliance UL-Listedper508 – IndustrialControlEquipment

  • –17–

    M‑3425A Generator Protection Relay

    UL-ListedComponentper508ATableSA1.1IndustrialControlPanels

    CSA-CertifiedperC22.2No.14-95 – IndustrialControlEquipment

    CESafetyDirective–EN61010-1:2001,CATII,PollutionDegree2

    PhysicalWithout Optional Expanded I/O

    Size: 19.00"widex5.21"highx10.20"deep(48.3cmx13.2cmx25.9cm)

    Mounting: Theunitisastandard19",semiflush,three-unithigh,rack-mountpaneldesign,conformingtoANSI/EIARS-310CandDIN41494Part5specifications.Verticalorhorizontalpanel-mountoptionsareavailable.

    Approximate Weight: 17lbs(7.7kg)

    Approximate Shipping Weight: 25lbs(11.3kg)

    With Optional Expanded I/O

    Size: 19.00"widex6.96"highx10.2"deep(48.3cmx17.7cmx25.9cm)

    Mounting: Theunitisastandard19",semiflush,four-unithigh,rack-mountpaneldesign,conformingtoANSI/EIARS-310CandDIN41494Part5specifications.Verticalorhorizontalpanel-mountoptionsareavailable.

    Approximate Weight: 19lbs(8.6kg)

    Approximate Shipping Weight: 26lbs(11.8kg)

    Recommended Storage Parameters

    Temperature: 5°Cto40°C

    Humidity:Maximumrelativehumidity80%fortemperaturesupto31°C,decreasingto31°Clin-earlyto50%relativehumidityat40°C.

    Environment:Storageareatobefreeofdust,corrosivegases,flammablematerials,dew, percolatingwater,rainandsolarradiation.

    See M-3425A Instruction Book, Appendix E, Layup and Storage for additional information.

    Patent & WarrantyTheM-3425AGeneratorProtectionRelayiscoveredbyU.S.Patents5,592,393and5,224,011.

    TheM-3425AGeneratorProtectionRelayiscoveredbyafiveyearwarrantyfromdateofshipment.

    Specification subject to change without notice.

    External ConnectionsM-3425AexternalconnectionpointsareillustratedinFigures2and3.

  • –18–

    M‑3425A Generator Protection Relay

    Figu

    re 2

    Ex

    tern

    al C

    onne

    ctio

    ns (W

    ithou

    t Opt

    iona

    l Exp

    ande

    d I/O

    )

    N

    OT

    ES:

    1.SeeM-3425AInstructionBookSection2.3,SetpointsandTimeSettings,subsectionfor64B/FFieldGroundProtection.

    2.BeforemakingconnectionstotheTripCircuitMonitoringinput,seeM-3425AInstructionBookSection5.5,CircuitBoardSwitchesandJumpers,

    fortheinformationregardingsettingTripCircuitMonitoringinputvoltage.Connectingavoltageotherthanthevoltagethattheunitisconfigured

    tomayresultinmis-operationorpermanentdamagetotheunit.

    3.

    8 W

    AR

    NIN

    G: O

    NLY

    DR

    Y C

    ON

    TAC

    TS

    mu

    st b

    e co

    nn

    ecte

    d t

    o in

    pu

    ts (

    term

    inal

    s 5

    thro

    ug

    h 1

    0 w

    ith

    11

    com

    mo

    n)

    bec

    ause

    th

    ese

    con

    tact

    in

    pu

    ts a

    re in

    tern

    ally

    wet

    ted

    . Ap

    plic

    atio

    n o

    f ex

    tern

    al v

    olt

    age

    on

    th

    ese

    inp

    uts

    may

    res

    ult

    in d

    amag

    e to

    th

    e u

    nit

    s.

    4.

    8

    WA

    RN

    ING

    : Th

    e p

    rote

    ctiv

    e g

    rou

    nd

    ing

    ter

    min

    al m

    ust

    be

    con

    nec

    ted

    to

    an

    ear

    thed

    gro

    un

    d a

    ny t

    ime

    exte

    rnal

    co

    nn

    ecti

    on

    s h

    ave

    bee

    n

    mad

    e to

    th

    e u

    nit

    .

    ��

    ����

    ���

    ���

    ��

    ��

    ����

    ���

    ���

    ��

    �����

    �����

    ���

    ��

    ��

    ��

    ��

    ���

    ��

    ���

    ��

    ��

    �����

    ���

    ��

    ��

    ��

    ��

    ���

    ���

    ���

    ���

    �� 

    ��������

    ��

    �������

    �������

    �� 

    � 

    �����

    �����

    ��

    ��

    ��

    ��

    ��

    ��

    ��

    ���

    ������

    ���

    ��

    ��������

    ��

    ��

    ��

    ��

     ����

    ��

    ��

    ��

    ����

    ����

    ����

    � �

    ����

    �����

    ����

    ��

    ��

    ��

    ���

    ��

    ���

    ���

    ��� ��

    ��

    ��

    ����

    �����

    ���

    ���

    ������

    ��

    �������

    ���

    ���

    ��

    ��

    ���

    ��

    ���

    ��

    ��

    ��

    ����

    ����

    ����

    ������������

    ��������

    ����������������

    ������������

    ����������������

    ��������

    ��

    ��

    ���

    ��

    ���

    ���

    ���

    ��

    ���

    ����

    ����

    ����

    ��

    � �

    ��

    ��

    ����

    ����

    �� ��

    ��

    ����

    ����

    ����

    ���

    ���

    ��

    ��

    ����

    �����

    ��

    ��

    ��

    ��

    ��

    ���

    ���� ��

    ���

    �����

    ��

    ����

    ���

    ����

    ���

    ��

    ��

    ��

    ��

    ��

    ��

    ���

    ��

    ���

    ��

    ���

    ��

    ��

    ���

    � 

    ���

    ���

    ����

    ��

    ��

    ���

    �����

  • –19–

    M‑3425A Generator Protection Relay

    �� ���

    ����

    ����

    ����

    ����

    ��

    ���

    ����

    ����

    ������

    �����

    ��

    ��

    ��

    ��

    ��

    ��

    ����

    ������

    ��

    ���

    ���

    ��

    ��

    ���

    ��

    ��

    �����

    ���

    �����

    ��

    ���

    ��

    ����

    ��

    ���

    ��

    ��

    ��

    ��

    ���

    ��

    ��

    ���

    ����

    ���

    ��

    ����

    ��

    ��

    ���

    ��

    �������

    ���

    ��

    ����

    ���

    ����

    ����

    ����

    ����

    ��

    ����

    ����

    ����

    ���

    ��

    ����

    ��

    ���

     

    ��

    ��

    ��

    ��

    ����

    ���

    ���

    �������

    ���

    ����

    ���

    ������

    ��

    ��

    ��������

    ����������������

    ����������������

    ����������������

    ����������������

    ��

    ��

    ����

    ��

    �����

    ����

    ��

    ��

    ��

    � ��

    � ��

    ��

    ��

    ����

    ��

    ��

    ��

    ��

    ��

    ���

    ������

    ��

    ���

    �����

    ���

    �����

    ��

    ��

    ����

    ����

    ����

    ��

    ����

    ��

    ��

    ��

    ����

    ��

    ��

    ��

    ��

    ��

    ���

    ��

    ��� �

    ���

    ��

    �����

    ��

    ��

    �������

    ��

    ����

    ����

    ����

    ����

    ��

    ��

    ��

    ��

    �������

    ��

    ��

    ����

    ���

    ����

    ����

    ����

    ����

    ���

    ����

    ��

    ����

    ����

    ���

    ���

    ���

    ���

    ���

    ���

    ��

    ��

    ��

    ��

    ���

    ����

    ���

    ���

    ��

    ��

    ��

    ��

    ���

    ����

    ��

    ��

    ��

    ��

    ��

    ����

    ���

    ��

    ��

    ��

    ��

    ���

    ���

    ����

    ��

    ���

    ����

    ��

    ���

    Figu

    re 3

    Ex

    tern

    al C

    onne

    ctio

    ns (W

    ith O

    ptio

    nal E

    xpan

    ded

    I/O)

    N

    OT

    ES:

    1.SeeM-3425AInstructionBookSection2.3,SetpointsandTimeSettings,subsectionfor64B/FFieldGroundProtection.

    2.BeforemakingconnectionstotheTripCircuitMonitoringinput,seeM-3425AInstructionBookSection5.5,CircuitBoardSwitchesandJumpers,

    fortheinformationregardingsettingTripCircuitMonitoringinputvoltage.Connectingavoltageotherthanthevoltagethattheunitisconfigured

    tomayresultinmis-operationorpermanentdamagetotheunit.

    3.

    8 W

    AR

    NIN

    G: O

    NLY

    DR

    Y C

    ON

    TAC

    TS

    mu

    st b

    e co

    nn

    ecte

    d to

    inp

    uts

    (ter

    min

    als

    5 th

    rou

    gh

    10

    wit

    h 1

    1 co

    mm

    on

    an

    d te

    rmin

    als

    68 th

    rou

    gh

    75

    wit

    h 6

    6 an

    d 6

    7 co

    mm

    on

    ) b

    ecau

    se t

    hes

    e co

    nta

    ct in

    pu

    ts a

    re in

    tern

    ally

    wet

    ted

    . Ap

    plic

    atio

    n o

    f ex

    tern

    al v

    olt

    age

    on

    th

    ese

    inp

    uts

    may

    re

    sult

    in d

    amag

    e to

    th

    e u

    nit

    s.

    4.

    8

    WA

    RN

    ING

    : Th

    e p

    rote

    ctiv

    e g

    rou

    nd

    ing

    ter

    min

    al m

    ust

    be

    con

    nec

    ted

    to

    an

    ear

    thed

    gro

    un

    d a

    ny t

    ime

    exte

    rnal

    co

    nn

    ecti

    on

    s h

    ave

    bee

    n

    mad

    e to

    th

    e u

    nit

    .

  • –20–

    M‑3425A Generator Protection Relay

    50DT

    Utility System

    52Unit

    52Gen

    50BFPh

    87

    492132 504078 60FL 51V 50/27

    27

    81R 81 27 59 24

    64F 64B

    M-3921+

    -

    CT

    VT

    M-3425A

    87GD 50N

    50BFN 51N

    R

    64S27TN27

    32R

    High-impedance Grounding with ThirdHarmonic 100% Ground Fault Protection

    Low-impedance Grounding with Ground Differentialand Overcurrent Stator Ground Fault Protection

    These functions are available inthe Comprehensive Package. Asubset of these functions are alsoavailable in a Base Package.

    This function is available as aoptional protective function.

    This function provides control forthe function to which it points.

    M-3425A TypicalConnection Diagram

    25

    59D

    VT (Note 1)

    Targets(Optional)

    Integral HMI(Optional)

    Metering

    Waveform Capture

    IRIG-B

    Front RS232Communication

    Multiple SettingGroups

    Programmable I/O

    Self Diagnostics

    Dual Power Supply(Optional)

    Rear Ethernet Port (Optional)

    Rear RS-485Communication

    BreakerMonitoring

    Trip CircuitMonitoring

    67N67N Polarization(Software Select)

    81A

    50N50BFN 51N

    46

    59X

    59N

    3VO (Calculated)VX

    VN

    3IO

    IN

    67N Operating Current(Software Select)

    VT (Note 1)

    (Note 3)

    (Note 5)

    CT (Residual)(Note 4)

    59D Line SideVoltage

    (Software Select)

    VX3VO (Calculated)

    CT (Neutral)(Notes 2 & 5)

    CTM

    (Metering)

    M

    (Metering)

    Rear RS232Communication

    Event Log

      NOTES: 1. When25functionisenabled,59X,59DwithVXand67NwithVXarenotavailable,andviceversa. 2. When67NfunctionwithIN(Residual)operatingcurrentisenabled,87GDisnotavailable,andvice

    versa. 3. WhenVTsourceisusedasaturn-to-turnfaultprotectiondevice(SeeM-3425AInstructionBook,

    Chapter2,Application,foradditional59Xapplications.) 4. ThecurrentinputINcanbeconnectedeitherfromneutralcurrentorresidualcurrent. 5. The50BFN,50N,51N,59D,67N(withINorVN)and87GDfunctionsareunavailablewhenthe64S

    functionhasbeenpurchased.SeetheM-3425AInstructionBookforconnectiondetails.

    Figure 4 One‑Line Functional Diagram (Configured with Phase Differential)

  • –21–

    M‑3425A Generator Protection Relay

    Utility System

    52Unit

    52Gen

    81R 81 59 27 24

    M-3921+

    -

    VT

    CT

    M-3425A

    50N 51N

    R

    CT27

    32R

    High-impedance Grounding with ThirdHarmonic 100% Ground Fault Protection

    Low-impedance Grounding withOvercurrent Stator Ground Fault Protection

    These functions are available inthe Comprehensive Package. Asubset of these functions are alsoavailable in a Base Package.

    This function is available as aoptional protective function.

    This function provides control forthe function to which it points.

    M-3425A TypicalConnection Diagram(Configured for Split-Phase Differential)

    25

    59D

    50DT

    67N

    Targets(Optional)

    Integral HMI(Optional)

    Metering

    Waveform Capture

    IRIG-B

    Front RS232Communication

    Multiple SettingGroups

    Programmable I/O

    Self Diagnostics

    Dual Power Supply(Optional)

    Rear EthernetPort (Optional)

    Rear RS-485Communication

    BreakerMonitoring

    Trip CircuitMonitoring

    27TN

    81A

    46492132 504078 60FL 51V 50/27

    2764F 64B

    59X

    64S 59N

    CT (Residual)(Note 5)

    VT (Note 1)

    VT (Note 1)

    67N Polarization(Software Select)

    3VO (Calculated)

    VX

    VN

    (Note 2)

    CT (Note 3)

    (Note 4)

    59D Line SideVoltage

    (Software Select)

    VX 3VO (Calculated)

    CT (Neutral)(Note 5)

    M

    (Metering)

    M

    (Metering)

    Rear RS232Communication

    Event Log

      NOTES:

    1. When25functionisenabled,59X,59DwithVXand67NwithVXarenotavailable,andviceversa.

    2. Whenusedasaturn-turnfaultprotectiondevice.

    3. CTsareconnectedforsplit-phasedifferentialcurrent.

    4. 67NoperatingcurrentcanonlybeselectedtoIN(Residual)forthisconfiguration.

    5. Thecurrentinput(IN)canbeconnectedeitherfromneutralcurrentorresidualcurrent.

    6. The50BFN,50N,51N,59D,67N(withINorVN)and87GDfunctionsareunavailablewhenthe64Sfunctionhasbeenpurchased.SeetheM-3425AInstructionBookforconnectiondetails.

    Figure 5 One‑Line Functional Diagram (configured for split‑phase differential)

  • –22–

    M‑3425A Generator Protection Relay

    Standard 19" Horizontal Mount Chassis

    19.00[48.26]

    17.50[44.45]

    17.50[44.45]

    ACTUAL

    5.21[13.23]

    ACTUAL

    0.40 [1.02] X 0.27[0.68] Slot (4X)

    10.20[25.91]

    19.00[48.26]

    18.31[46.51]

    0.35[0.89]

    1.48[3.76]

    2.25[5.72]

    NOTE: Dimensions in brackets are in centimeters. NOTES:1.Dimensionsinbracketsareincentimeters.

    2.SeeInstructionBookChapter5forMountingandCutoutinformation.

    Figure 6 Horizontal Unit Dimensions Without Expanded I/O (H1)

  • –23–

    M‑3425A Generator Protection Relay

    1.67[4.24]

    19.00[48.26]

    18.31[46.51]

    2.25[5.72]

    0.28 [0.71]Dia. (4X)

    17.68[44.91]

    5.59[14.20]Actual

    1.67[4.24]

    2.25[5.72]

    10.20[25.91]

    COM 1

    TARGETS

    OUT 1

    OUT 2

    OUT 3

    OUT 4

    OUT 5

    OUT 6

    OUTPUTSOUT 7

    OUT 8

    EXIT ENTER

    TARGET DIAG

    TIME

    OSC.TRIG

    SYNC

    BRKRCLOSED

    OKRELAY

    TARGETRESET

    PS 2 PS 1

    17.5[44.45]

    ACTUAL

    5.65[14.40]

    Recommended cutout when relay is not used asstandard rack mount and is panel cut out mounted.

    19.00[48.26]

    17.50[44.45]

    0.35[0.89]

    0.03[0.076]

    NOTE: Dimensions in brackets are in centimeters. NOTES:1.Dimensionsinbracketsareincentimeters.

    2.SeeInstructionBookChapter5forMountingandCutoutinformation.

    Figure 7 Vertical Unit Dimensions Without Expanded I/O (H2)

  • –24–

    M‑3425A Generator Protection Relay

    Figure 8 M-3425A Vertical Unit Layout

    50

    Hz

    60

    Hz

    SE

    RIA

    LN

    O.

    MO

    DE

    L: M-3425A

    FIRM

    WA

    RE

    : D-0150

    659

    IRIG- B

    35

    36

    6 4 F

    RA

    TE

    DV

    OL

    TA

    GE

    60

    -140

    VA

    C,5

    0/6

    0H

    z

    39

    40

    37

    38

    44

    42

    43

    41

    64

    COUPLER

    ET HERNETC O M 2

    FIELD GROUND

    !

    CO M 3RS 4 8 5

    B CV

    V A B

    VVA

    BV

    V C

    VA

    C

    !

    4824

    125

    A UX250 -

    ++

    IN6

    IN5

    -

    RA

    TE

    DC

    UR

    RE

    NT

    1A,N

    OM

    5A

    ,NO

    M

    45

    46

    V

    65

    X

    50

    47

    49

    48

    55

    53

    54

    51

    520.01A

    NO

    M6

    4S

    58

    56

    57

    ALARMS

    INPUTS

    A

    VN

    I

    BI

    IC

    !

    IN2

    IN1

    (52b)

    IN3

    IN4

    RT NIN

    P/ S

    OUTPUTS

    IN

    aI

    I b

    I c

    SELF-TEST

    8

    7

    COM 2

    BE

    CK

    WIT

    HE

    LE

    CT

    RIC

    CO

    .IN

    C.

    619

    0118

    thA

    VE

    NO

    .L

    AR

    GO

    ,F

    L3

    37

    73

    RS 2 3 2

    1

    3

    5

    4

    2

    6

    72

    7-5

    44

    -23

    26

    14

    WA

    RN

    ING

    !C

    ON

    TA

    CT

    WIT

    HT

    ER

    MIN

    AL

    SM

    AY

    CA

    US

    EE

    LE

    CT

    RIC

    SH

    OC

    KF

    OR

    CO

    NT

    AC

    TR

    AT

    ING

    SS

    EE

    INS

    TR

    UC

    TIO

    NM

    AN

    UA

    L

    10

    8

    9

    7

    13

    12

    11

    16

    18

    17

    15

    22

    20

    19

    21

    23

    63

    60

    62

    61

    55

    26

    86

    5-18

    --

    65

    85

    21

    -8

    56

    F3

    F43 A MP,

    (3A B) 1

    +

    -

    -

    +

    PS 2

    PS 1

    PS2

    F1

    F2

    5

    4

    3

    2

    PS1

    25

    24

    27

    26

    28

    31

    29

    30

    33

    32

    34

    U.S

    . PA

    TEN

    T 5,592,393, 5,224,011

    NRTL /CLR 89464

    R

    COM 1

    TARGETS

    OUT 1

    OUT 2

    OUT 3

    OUT 4

    OUT 5

    OUT 6

    OUTPUTS

    OUT 7

    OUT 8

    EXIT ENTER

    TARGET

    BRKRCLOSED

    TARGETRESET

    PS 2

    DIAG

    PS 1

    OSC.TRIG

    TIMESYNCOK

    RELAY

    R

    M-3425AGENERATORPROTECTION

    250V,

  • –25–

    M‑3425A Generator Protection Relay

    0.35[0.89]

    18.31[46.51]

    NOTES:1.Dimensionsinbracketsareincentimeters.

    2.SeeInstructionBookChapter5forMountingandCutoutinformation.

    Figure 9 Horizontal and Vertical Unit Dimensions With Expanded I/O (H5 and H6)

  • –26–

    M‑3425A Generator Protection Relay

    FOR

    CO

    NTA

    CT R

    ATIN

    GS

    SE

    E IN

    STR

    UC

    TION

    AL M

    AN

    UA

    LW

    ARN

    ING

    ! CO

    NTAC

    T WITH

    TERM

    INALS M

    AY CAU

    SE ELECTR

    IC SH

    OC

    K50H

    z60H

    zS

    ER

    IAL N

    O.

    FIRM

    WA

    RE

    : D-0150

    MO

    DE

    L: M-3425A

    COUPLER

    FIELD

    GND

    IND. CONT. EQ.LISTED

    RC US

    83F4

    RTNIN

    COM 2

    COM 2

    IRIG-B

    105

    104

    102

    101

    100

    99

    96

    97

    95

    94

    98

    9392

    90

    91

    103

    89

    88

    86

    85

    84

    83

    87

    80

    81

    79

    78

    77

    76

    74

    73

    75

    82

    72

    71

    69

    68

    70

    67

    66

    RS232

    ETHERNET

    64F

    IN 10

    IN 9

    IN 8

    IN 7

    IN 14

    IN 13

    IN 12

    IN 11

    INPUTS

    OUTPUTS

    15

    16

    17

    18

    19

    20

    21

    22

    23

    9

    10

    11

    12

    13

    14

    F 4 F2

    F3 F1

    6381

    5-8 6

    625

    62

    55 265-6

    6181

    59

    58

    608

    5

    1

    PS 2 2

    34

    33

    32

    -

    330

    31

    29

    +PS1 4

    -PS2 5

    27

    26

    6I c

    24

    22

    23

    25+ O

    UTPUTS 28

    250V

    PS 1

    57

    55

    56

    54

    6 4 S

    530.01A NOM

    51

    50

    48

    47

    49

    52

    bI 7 21

    19

    20

    8

    17

    18

    16

    I

    P/SALARMS

    C

    15

    14

    13

    BI

    A !

    RT N 11IN

    12

    SELF

    46

    65

    45

    XV

    64

    44

    43

    41

    42

    40

    39

    I

    (52b)10

    9

    NV7

    5

    6

    IN 6

    8INPUTS

    VCV AC

    C

    -COM 3RS485

    4

    3

    2+

    +

    VV B

    -AUX

    V

    BAVA

    !48

    250125

    1

    24

    B

    37

    36

    35

    !

    38

    -

    -

    IN 5

    IN 4

    IN 3

    IN 2

    IN 1

    TEST

    3AMP

    (3AB)

    VOLTAGERATED

    60-140VAC50/60Hz

    5 A, NO M

    1A ,N O M

    RATEDCURRENT

    I

    I

    a

    N

    LAR

    GO

    ,FL

    33

    773

    619

    0118

    thAV

    EN

    O.

    BE

    CK

    WIT

    HE

    LE

    CT

    RIC

    CO

    .IN

    C.

    727

    -54

    4-2

    32

    6

    OUT 1

    OUT 2

    OUT 3

    OUT 4

    OUT 5

    OUT 6

    OUTPUTSOUT 7

    OUT 8

    TARGETS

    EXIT ENTER

    COM 19

    10

    TARGET DIAG

    TIME

    OSC.TRIG

    SYNC

    BRKRCLOSED

    OKRELAY

    TARGETRESET

    11

    12

    14

    15

    16

    OUTPUTS

    17

    18

    19

    22

    20

    21

    23

    13

    PS 2 PS 1

    .

    R

    CHIWK T

    IC RTEEBLEC CNI.CO

    Made in U.S.A.

    M-3425AGENERATORPROTECTION

    NOTES:1. The M-3425A Expanded I/O vertical panel is the same physical size as the M-3425A Expanded I/O horizontal panel. See Figure 7 for dimennsions.2. See Instruction Book Section 5 for Mounting and Cutout information.

    U.S. PATENT5,592,3935,224,011

    Figure 10 M-3425A Expanded I/O Vertical Unit Layout

  • –27–

    M‑3425A Generator Protection Relay

    M-3921 Field Ground Coupler

    �����������������������

    �����

    ��

    ����������������

    ��

    ������

    ��� ����������  ��

    ����������������

    ������������

    ��������� 

    �������

     �

    �������

    ��  

    Figure 11 Field Ground Protection Block Diagram

    NOTES: 1. Theabovecircuitmeasuresinsulationresistance(Rf)betweenrotorfieldwindingandground(64F).

    2. Relayinjects15Vsquarewave(Vout)andmeasuresreturnsignal(Vf)tocalculateRf.

    3. Theinjectionfrequencycanbeset(0.1to1.0Hz)basedontherotorcapacitance,inordertoimproveaccuracy.

    4. Thesignalrisetimeisanalyzedtodetermineifshaftbrushesareliftingoropen(64B).

    5. Mayalsobeappliedongeneratorswithbrushlessexcitationwithagroundingbrushandpilotgroundfaultdetectionbrush.

    Function SpecificationField/Exciter Supply Voltage Rating(Terminal(3)to(2)):

    • 60to1200Vdc,continuous

    • 1500Vdc,1minute

    Operating Temperature:–20°to+70°,Centigrade

    Patent & WarrantyTheM-3921FieldGroundCoupleriscoveredbyafive-yearwarrantyfromdateofshipment.

  • –28–

    M‑3425A Generator Protection Relay

    Tests and StandardsM-3921FieldGroundCouplercomplieswiththefollowingtestsandstandards:

    Voltage Withstand

    Isolation5kVacfor1minute,allterminalstocase

    Impulse VoltageIEC60255–5, 5,000 V pk, 1.2 by 50 µs, 0.5 J, 3 positive and 3 negative impulses at 5 second intervalsperminute

    Electrical InterferenceElectrostatic Discharge TestEN60255-22-2 Class4(8kV)—pointcontactdischarge Class4(15kV)—airdischarge

    Fast Transient Disturbance TestsIEC61000-4-4 Class4(4kV,2.5kHz)

    Surge Withstand CapabilityANSI/IEEE 2,500Vpk-pkoscillatoryappliedtoeachindependentcircuittoearthC37.90.1- 2,500Vpk-pkappliedbetweeneachindependentcircuit1989 5,000VpkFastTransientappliedtoeachindependentcircuittoearth 5,000VpkFastTransientappliedbetweeneachindependentcircuit

    ANSI/IEEE 2,500Vpk-pkoscillatoryappliedtoeachindependentcircuittoearthC37.90.1- 2,500Vpk-pkappliedbetweeneachindependentcircuit2002 4,000VpkFastTransientappliedtoeachindependentcircuittoearth 4,000VpkFastTransientappliedbetweeneachindependentcircuit

    NOTE: Thesignalisappliedtothedigitaldatacircuits(RS-232,RS-485,IRIG-B,Ethernetcommunicationportandfieldgroundcouplingport)throughcapacitivecouplingclamp.

    Radiated SusceptibilityANSI/IEEE 25-1000Mhz@35V/mC37.90.2

    Atmospheric EnvironmentIEC60068–2–1Cold,–20°CIEC60068–2–2 DryHeat,+70°CIEC60068–2–3DampHeat,+40°C@93%RH

    Enclosure ProtectionNEMA1,IECIPC-65

  • –29–

    M‑3425A Generator Protection Relay

    .18

    DIA

    [0.4

    6] 4

    HO

    LES

    MO

    UN

    TIN

    G P

    AT

    TE

    RN

    WIT

    HO

    UT

    TA

    BS

    Fie

    ld G

    roun

    dC

    oupl

    er4.

    72 [1

    1.99

    ]

    7.87

    [19.

    99]

    2.96

    RE

    F [7

    .52]

    3.54

    [9.0

    ]

    �N

    OT

    E: D

    imen

    sion

    s in

    bra

    cket

    s ar

    e in

    cen

    timet

    ers.

    7.40

    [18.

    79]

    9.06

    [23.

    01]

    3.54

    [9.0

    ]

    .18

    DIA

    [0.4

    6] 4

    X

    ��

    ���

    ��

    �����

    ���

    �����

    ���

    ���

    ��

    ���

    M-3

    921

    Figure 12 M-3921 Field Ground Coupler Mounting Dimensions

  • –30–

    M‑3425A Generator Protection Relay

    64S 100% Stator Ground Protection by Low Frequency Signal Injection NOTE: TheStatorGroundProtectionfunction(64S)mustbeselectedwhentheM-3425Aisinitiallyordered.

    The100%statorgroundfaultprotectionisprovidedbyinjectinganexternal20Hzsignalintotheneutralofthegenerator.Theprotectionisprovidedwhenthemachineison-lineaswellasoff-line(providedthatthe20Hzgeneratorandrelayarepoweredon.)ThisschemerequiresthefollowingexternalcomponentsinadditiontoM-3425Aprotectionsystem:

    • 20HzSignal-generator(BECOSurfaceMount/FlushPartNo.430-00426)(Siemens7XT33)

    • Band-passfilter(BECOSurfaceMount/FlushPartNo.430-00427)(Siemens7XT34)

    • 20 Hz Measuring Current Transformer, 400/5 A CT (BECO Par t No. 430-00428) (ITI-CTW3-60-T50-401)

    Thevoltagesignalgeneratedbythe20Hzsignal-generatorisinjectedintothesecondaryofthegeneratorneu-tralgroundingtransformerthroughaband-passfilter.Theband-passfilterpassesthe20Hzsignalandrejectsout-of-bandsignals.Theoutputofthe20Hzband-passfilterisconnectedtotheVNinputoftheM-3425Arelaythroughasuitablevoltagedivider,thatlimitstheM-3425AtoO200Vac(thevoltagegeneratormaybebypassediftheexpected50/60Hzvoltageduringaphase-to-groundfaultofthegeneratorisO 200V.)The20HzcurrentisalsoconnectedtotheINinputoftheM-3425A,throughthe20Hzcurrenttransformer.

    Whenthegeneratorisoperatingnormally(nogroundfault)onlyasmallamountof20Hzcurrentwillflowasaresultofthestatorcapacitancetoground.Whenagroundfaultoccursanywhereonthegeneratorstatorwindingsthe20Hzcurrentwillincrease.The64Sfunctionwillissueatripsignalafterasettimedelaywhenthemeasured20Hzcurrentexceedsthepickupcurrent.

    ForcaseswheretheLoadResistor(RN)issmall,theUndervoltageInhibitshouldnotbeenabled,asthevolt-agewillbesmall.

    The59Nfunction(90to95%)shouldalsobeusedinconjunctionwith64Sprotectiontoprovidebackup.

  • –31–

    M‑3425A Generator Protection Relay

    RN

    1B1

    1A1

    1B4

    1A3

    1A4

    20 H

    zB

    and

    Pass

    Filte

    r

    20 H

    zG

    ener

    ator

    11

    Bl

    Supp

    ly V

    olta

    geD

    C

    10

    0-23

    0 VA

    C**

    UH

    +

    L

    1

    UH

    -

    L

    2

    L

    3

    Exte

    rnal

    Blo

    ck

    Dev

    ice

    Ope

    rativ

    e

    4445

    M-3

    425A

    5253

    400A 5A

    L

    Kl

    k

    Max

    . 20

    0 V

    V N

    I N

    Neu

    tral

    Gro

    undi

    ngTr

    ansf

    orm

    er

    Wiri

    ngSh

    ield

    ed

    20 H

    z C

    T40

    0/5

    A

    59NH

    igh*

    Volta

    ge

    * Fo

    r app

    licat

    ions

    with

    a tr

    ansf

    orm

    er s

    econ

    dary

    ratin

    g th

    at w

    ill re

    sult

    in 5

    0/60

    Hz

    phas

    e g

    roun

    d fa

    ult v

    olta

    ges

    >200

    V a

    c, u

    se th

    e "H

    igh

    Vol

    tage

    " con

    nect

    ion

    for t

    he 5

    9N F

    unct

    ion.

    ** If

    20

    Hz

    Sig

    nal G

    ener

    ator

    is p

    rior t

    o M

    odel

    EE

    a s

    tep

    dow

    n tra

    nsfo

    rmer

    is n

    eces

    sary

    for v

    olta

    ges

    >120

    VA

    C.

    Con

    nect

    ion

    term

    inal

    s fo

    rM

    odel

    A00

    /EE

    show

    n.

    12

    1 2 3 6 8 7 9 5

    1A2

    Figure 13 64S Function Component Connection Diagram (Model A00/EE 20 Hz Signal Generator)

  • –32–

    M‑3425A Generator Protection Relay

    20 Hz Signal Generator Function Specifications

    Auxiliary VoltageRatedauxiliaryvoltageUHac 3x(100/120Vac),50/60Hz1x(100to120Vac),50/60Hz

    Permissiblevariationsac 88to230Vac

    OR

    RatedauxiliaryvoltageUHdc 110to220Vdc

    PermissibleVariationsdc 88to250Vdc

    Permissibleconsumptionat8Ohmimpendance O100VA

    NOTE: 230VACispermissibleforcommissioningonly,whichislimitedintime.

    20 Hz Output VoltageConnections(11and12)

    OutputVoltage approx.26V±10%,rectangular;20Hz0.1Hz

    PowerOutput,permanently 100VAoverallranges

    NOTE: Outputisnotresistanttoshort-circuits.

    Binary Input for BlockingConnections(6and8)

    SwitchingThreshold Adjustablevoltagerangewithjumper

    –Forcontrolvoltages 24V 48V 60V DC19V:Uhigh P DC19V,Ulow O DC10V

    –Forcontrolvoltages 110V 125V 220V 250V DC88V:Uhigh P DC88V,Ulow O DC44V

    Permissiblevoltage,continuous 300Vdc

    Life ContactConnections(5,7and9)

    SwitchingcapacityMAKE 30W/VA BREAK 20VA 30Wresistanceload 25W@L/RO50ms

    Switchingvoltage DC24VtoDC250V AC24toAC230V

    Permissiblecurrent 1Apermanent

    Permissible Ambient TemperaturesRLdescribestheloadresistanceattheBandPassoutput.

    withRL 5Ohm O700CorO1580F

    NOTE: Withmaximumpoweroutput,thedevicehasapowerlossofapproximately24W.Toensureunhin-deredheatdissipationthroughtheventholes,thedistancetootherdeviceslocatedatthetopandbottommustbeatleast100mm.Thisdevicemustthereforealwaysbemountedinthebottompartofthecabinet.

  • –33–

    M‑3425A Generator Protection Relay

    NOTE: DetailedMountinginformationiscontainedintheM-3425AInstructionBookChapter5,InstallationSection5.6.

    Figure 14 20Hz Signal Generator Dimensions

    Dimensions in mm

  • –34–

    M‑3425A Generator Protection Relay

    Band-pass Filter Specifications

    Load Capacity of the 20 Hz Band-pass FilterConnections(1B1-1B4)

    Permissiblevoltage,continuous 55Vac

    PermissiblevoltageforO30s 550Vac

    Frequencyofsuperimposedacvoltage P45Hz

    Overloadcapability,continuous 3.25Aac

    TestVoltage 2.8kVdc

    Load Capability of the Voltage Divider CircuitConnections(1A1-1A4):

    Permissiblevoltage,continuous 55Vac

    PermissiblevoltageforO30s 50Vac

    TestVoltage 2.8kVdc

    Permissible Ambient TemperatureswithRL 5Ωburden O550CorO1310F

    NOTE: Thedevicemayproduceupto75Wpowerlossesduringservice.Inordertopreventheatpockets,thedissipationofthelossesmustnotberestricted.Theminimumclearanceaboveandbelowthedevicetootherunitsorwallsis100mmor4inches.Incubicles,thedeviceshallbeinstalledinthebottomarea.

  • –35–

    M‑3425A Generator Protection Relay

    Figure 16 20 Hz Measuring Current Transformer 400‑5 A CT

    NOTE: DetailedMountinginformationiscontainedintheM-3425AInstructionBookChapter5,InstallationSection5.

    Figure 15 Band‑pass Filter Dimensions

  • 800-3425A-SP-10MC1 09/11©2001BeckwithElectricCo.AllRightsReserved.PrintedinU.S.A. (#01-67)(04.25.03)

  • ���������������������������������������������� ��!���!������"�!#���!���!���������� ���$��!������!%������������������ ���&���'%���(�����$�!�%�������������������)����������#�!�����) ��� ��'����������������!���"�������� ���&���%���(�*�)�+�!��� ��������!���+���������+�����!������!����!�� ���� ��+�������������������� ���$��!'������!%�����(

    DANGER! HIGH VOLTAGE

    – This sign warns that the area is connected to a dangerous high voltage, and youmust never touch it.

    PERSONNEL SAFETY PRECAUTIONSThe following general rules and other specific warnings throughout the manual must be followed during application,test or repair of this equipment. Failure to do so will violate standards for safety in the design, manufacture, and intendeduse of the product. Qualified personnel should be the only ones who operate and maintain this equipment. BeckwithElectric Co., Inc. assumes no liability for the customer’s failure to comply with these requirements.

    – This sign means that you should refer to the corresponding section of the operation

    manual for important information before proceeding.

    Always Ground the Equipment

    To avoid possible shock hazard, the chassis must be connected to an electrical ground. When servicingequipment in a test area, the Protective Earth Terminal must be attached to a separate ground securelyby use of a tool, since it is not grounded by external connectors.

    Do NOT operate in an explosive environmentDo not operate this equipment in the presence of flammable or explosive gases or fumes. To do so wouldrisk a possible fire or explosion.

    Keep away from live circuitsOperating personnel must not remove the cover or expose the printed circuit board while power is ap-plied. In no case may components be replaced with power applied. In some instances, dangerous volt-ages may exist even when power is disconnected. To avoid electrical shock, always disconnect power anddischarge circuits before working on the unit.

    Exercise care during installation, operation, & maintenance proceduresThe equipment described in this manual contains voltages high enough to cause serious injury or death.Only qualified personnel should install, operate, test, and maintain this equipment. Be sure that all per-sonnel safety procedures are carefully followed. Exercise due care when operating or servicing alone.

    Do not modify equipmentDo not perform any unauthorized modifications on this instrument. Return of the unit to a BeckwithElectric repair facility is preferred. If authorized modifications are to be attempted, be sure to followreplacement procedures carefully to assure that safety features are maintained.

  • PRODUCT CAUTIONSBefore attempting any test, calibration, or maintenance procedure, personnel must be completely familiarwith the particular circuitry of this unit, and have an adequate understanding of field effect devices. If acomponent is found to be defective, always follow replacement procedures carefully to that assure safetyfeatures are maintained. Always replace components with those of equal or better quality as shown in theParts List of the Instruction Book.

    Avoid static chargeThis unit contains MOS circuitry, which can be damaged by improper test or rework procedures. Careshould be taken to avoid static charge on work surfaces and service personnel.

    Use caution when measuring resistancesAny attempt to measure resistances between points on the printed circuit board, unless otherwise notedin the Instruction Book, is likely to cause damage to the unit.

  • NOTE

    The following features, described in this Instruction Book, are only available for firmware versionD-0150-V01.00.34 and later:

    59N 20 Hz Injection Mode (Page 2-58)

    IEEE curves for 51N, 51V, and 67N functions (Appendix D)

    Sequence of Events Recorder (Page 4-18)

    Dropout/Reset Time Delay added to IPSlogic (Page 2-91)

    Response Time Delay for Communications (Page 4-3)

    25 Function (does not produce a target) (Page 2-21)

  • This Page Left Intentionally Blank

  • i

    Table of Contents

    Chapter 1 Introduction

    1.1 Instruction Book Contents ............................................................................1–1

    1.2 M-3425A Generator Protection Relay ...........................................................1–2

    1.3 Accessories ..................................................................................................1–4

    Chapter 2 Application

    2.1 Configuration .....................................................................................................2–2 Profiles ...............................................................................................................2–3 Functions ...........................................................................................................2–3 Special Considerations ......................................................................................2–3 Relay System Setup ..........................................................................................2–3

    2.2 System Diagrams ..............................................................................................2–8

    2.3 Setpoints and Time Settings ............................................................................2–14 21 Phase Distance ..........................................................................................2–14 24 Overexcitation Volts/Hz ...............................................................................2–18 M-3425A Firmware Versions D-0114VXX.XX.XX and Earlier .........................2–19 M-3425A Firmware Version D-0150V 01.00.34 ...............................................2–19 M-3425A Firmware Version D-0150V 01.04.00 ...............................................2–19 25 Sync Check.................................................................................................2–21 Phase Angle Check .........................................................................................2–21 Delta Voltage and Delta Frequency Check ......................................................2–21 27 Phase Undervoltage ...................................................................................2–25 27TN #2 Screens are identical to 27TN #1. .....................................................2–28 32 Directional Power ........................................................................................2–29 Protection from Generator Motoring ................................................................2–29 Protection from Generator Overload................................................................2–29 Protection from Excessive Reactive Power .....................................................2–29 40 Loss of Field ...............................................................................................2–33 46 Negative Sequence Overcurrent ................................................................2–37 49 Stator Overload Protection ........................................................................2–39 50/50N Instantaneous Overcurrent, Phase and Neutral Circuits .....................2–42 50BF Generator Breaker Failure/HV Breaker Flashover .................................2–44 50DT Definite Time Overcurrent (for split-phase differential) ...........................2–46 50/27 Inadvertent Energizing ...........................................................................2–47 51N Inverse Time Neutral Overcurrent ............................................................2–49 51V Inverse Time Phase Overcurrent with Voltage Control/Restraint ..............2–50 59 Phase Overvoltage .....................................................................................2–52 59D Third Harmonic Voltage Differential (Ratio) ..............................................2–53 59N Overvoltage, Neutral Circuit or Zero Sequence .......................................2–55 59X Multipurpose Overvoltage (Turn-to-Turn Stator Fault Protection or Bus Ground Protection) ...............................................................................2–56

    TABLE OF CONTENTSM-3425A Generator Protection

    Instruction Book

  • ii

    M-3425A Instruction Book

    Chapter 2 Application (Cont.'d)

    60FL VT Fuse Loss .........................................................................................2–58 Internal Fuse Loss Detection Logic .................................................................2–58 External Fuse-Loss Function ...........................................................................2–58 60FL VT Fuse Loss Alarm Function ................................................................2–58 64B/F Field Ground Protection ........................................................................2–61 64F Field Ground Detection ............................................................................2–61 Factors Affecting 64F Performance .................................................................2–61 64B Brush Lift-Off Detection ............................................................................2–63 64S 100% Stator Ground Protection by Low Frequency Signal Injection .......2–65 67N Residual Directional Overcurrent .............................................................2–71 78 Out-of-Step .................................................................................................2–74 81 Frequency ...................................................................................................2–77 81A Frequency Accumulator ...........................................................................2–79 81R Rate of Change of Frequency ..................................................................2–81 87 Phase Differential .......................................................................................2–82 87GD Ground (Zero Sequence) Differential ....................................................2–84 Breaker Monitoring ..........................................................................................2–85 Trip Circuit Monitoring ......................................................................................2–86 IPSlogic™ ........................................................................................................2–87 Settings and Logic Applicable when IPSlogic™ Function(s) programmed using IPScom® ..........................................................................2–89 DO/RST (Dropout/Reset) Timer Feature .........................................................2–91 Reset Delay Timer ...........................................................................................2–91 Dropout Delay Timer ........................................................................................2–91

    Chapter 3 Operation

    3.1 Front Panel Controls ..........................................................................................3–1 Alphanumeric Display ........................................................................................3–1 Screen Blanking ................................................................................................3–1 Arrow Pushbuttons ............................................................................................3–1 Exit Pushbutton..................................................................................................3–1 Enter Pushbutton ...............................................................................................3–1 Target & Status Indicators and Controls ............................................................3–1 Power Supply #1 (#2) LED ................................................................................3–2 Relay OK LED ...................................................................................................3–2 Oscillograph Recorded LED ..............................................................................3–2 Breaker Closed LED ..........................................................................................3–2 Target Indicators and Target Reset ....................................................................3–2 Time Sync LED ..................................................................................................3–2 Diagnostic LED ..................................................................................................3–2 Accessing Screens ............................................................................................3–2 Default Message Screens ............................................................................3–2

    3.2 Initial Setup Procedure/Settings ...................................................................3–5

    3.3 Setup Unit Data .................................................................................................3–5 Setup Unit Data Entry ........................................................................................3–5 Setu


Recommended