+ All Categories
Home > Documents > INSTRUCTION MANUAL · INPUT SOURCES (PAGING MICS, BGM PLAYERS ETC) 24V DC 24V DC 24V DC 24V DC...

INSTRUCTION MANUAL · INPUT SOURCES (PAGING MICS, BGM PLAYERS ETC) 24V DC 24V DC 24V DC 24V DC...

Date post: 07-Mar-2021
Category:
Upload: others
View: 3 times
Download: 0 times
Share this document with a friend
12
Thank you for choosing another quality product from Amperes Electronics. EP1200A is enhanced version with RS485 data output, enabling the unit to be used together with iPX5151 IP client for LAN based PA System. Emergency paging and siren activation shall be available throughout the entire network from main rack. Extra feature available from EP1200A is the availability of a dry contact, which is closed whenever the unit is activated. This allows connection to volume controller for overriding purpose. We believe that this product shall be able to meet your demanding requirement with affordable pricing and uncompromised features and quality. Though it is rather simple in the installation works, a brief read through the manual is recommended and we are confident that you are getting a product of excellence. INSTRUCTION MANUAL EP1200A Emergency Paging Microphone Panel VER 2 / 2015 FIRE
Transcript
Page 1: INSTRUCTION MANUAL · INPUT SOURCES (PAGING MICS, BGM PLAYERS ETC) 24V DC 24V DC 24V DC 24V DC MX2222 PRE-AMP MIXER EP1200A EMERGENCY PANEL POWER AMPLIFIERS ZS SPEAKER ZONE SELECTOR

Thank you for choosing another quality product from Amperes Electronics.

EP1200A is enhanced version with RS485 data output, enabling the unit to be used together with iPX5151 IP client for LAN based PA System. Emergency paging and siren activation shall be available throughout the entire network from main rack.

Extra feature available from EP1200A is the availability of a dry contact, which is closed whenever the unit is activated. This allows connection to volume controller for overriding purpose.

We believe that this product shall be able to meet your demanding requirement with affordable pricing and uncompromised features and quality. Though it is rather simple in the installation works, a brief read through the manual is recommended and we are confident that you are getting a product of excellence.

INSTRUCTION MANUAL

EP1200AEmergency Paging Microphone Panel

VER 2 / 2015

FIRE

Page 2: INSTRUCTION MANUAL · INPUT SOURCES (PAGING MICS, BGM PLAYERS ETC) 24V DC 24V DC 24V DC 24V DC MX2222 PRE-AMP MIXER EP1200A EMERGENCY PANEL POWER AMPLIFIERS ZS SPEAKER ZONE SELECTOR

Parts Identification

PAGE 2 EP1200A | EMERGENCY PAGING MICROPHONE PANEL

Front View:

Rear View:

1 2 3

5

4

FIRE

6

7

8

9

10 11 12 13 14

1. FIRE INDICATOR

2. EMERGENCY PAGING

This EMERGENCY PAGING button shall active all zones as well as sending emergency paging mode to other related equipment.

3. SIREN SWITCH

4. HANDHELD PAGING MICROPHONEPressing the microphone switch shall have priority over other inputs such as Siren, External Message input as well as normal paging or BGM feeds. For emergency paging which is to override VC and activate ALL CALL, press the emergency paging button (2) before start to talk.

Press the siren button shall activate the siren which is momentary. FIRE indicator shall lit and the MIC switch relay contact (8) shall close. Release of the switch shall deactivate the siren, Pressing it continuously shall activate the unit for about 10 seconds, after which the unit shall reset.

Whenever siren or external activation device is triggered, the FIRE indicator shall flash alongside with siren audio broadcast.

Page 3: INSTRUCTION MANUAL · INPUT SOURCES (PAGING MICS, BGM PLAYERS ETC) 24V DC 24V DC 24V DC 24V DC MX2222 PRE-AMP MIXER EP1200A EMERGENCY PANEL POWER AMPLIFIERS ZS SPEAKER ZONE SELECTOR

EP1200A | EMERGENCY PAGING MICROPHONE PANEL PAGE 3

Parts Identification

5. 24V INPUTThe unit operates on 24V DC. It is preferred that the unit to be supplied directly from the uninterrupted power source. ie. Back up batteries. Alternatively, connect it to a regulated power supply unit which is in turned has back up supply.

8. RELAY CONTACTTriggering the front panel mic switch shall activate an internal relay. This ports provide a dry contact which can be used to connect E/M overriding signal or to activate ALL CALL at speaker zone selector. The recommended rating for the contact is 3A. In case higher rating is required, please use external relay or contactor to accomodate the high current requirement.

7. REMOTE TRIGGER PORT FOR SIRENExternal sensor device such as heat detector or fire alarm interface device can be connected to this unit to activate the siren. The external device or switch must be voltage free to avoid damage to the unit. Siren activation shall be approximately 10 seconds, after which another contact is required to broadcast the siren.

6. EXTERNAL MESSAGE TRIGGER PORTExternal message player can be linked to it and can be broadcasted to the speakers when this port is triggered. A voltage free contact is recommended to trigger the message playback.

10. HANDHELD MIC LEVEL CONTROLThis is to adjust the front paging mic volume. It is recommended that the setting is made during testing and commissioning works.

11. SIREN OUTPUT LEVEL CONTROLAdjust the siren output to an optimum level during testing and commissiong works.

12. EXTERNAL MESSAGE AUDIO INPUTThe external message playback signal shall be balanced line level. ( e.g: audio from MR1301 )

13. PRE-AMPLIFIER INPUT JACKOutput from pre-amplifier mixer (balanced line level ) is connected to the unit which is normally closed when the unit is not activated. Triggering the panel shall bypass the signal to allow higher priority audio to the PA system.

14. DATA AUDIO OUTPUTAudio output from the decoder is balanced line output level. RJ45 connector consists of audio, data and power with the following pin configuration:-

Pin 1 - Data A Pin 2 - Data B Pin 3 - Relay Trigger SignalPin 4 - NC

Pin 5 - +24V SupplyPin 6 - Audio -ve outputPin 7 - GroundPin 8 - Audio +ve Output

9. RS485 PORTExternal controls or interface devices shall be able to communicate with the unit. It shall be able to communicate with software using RS485 to USB converter which shall be available in near future.

Page 4: INSTRUCTION MANUAL · INPUT SOURCES (PAGING MICS, BGM PLAYERS ETC) 24V DC 24V DC 24V DC 24V DC MX2222 PRE-AMP MIXER EP1200A EMERGENCY PANEL POWER AMPLIFIERS ZS SPEAKER ZONE SELECTOR

PAGE 4 EP1200A | EMERGENCY PAGING MICROPHONE PANEL

FIRE

PUBLIC ADDRESS POWER AMPLIFIER

SIGNAL -40 dB

SIGNAL -10 dB

POWER

PROTECT

CLIP

PA 2480 amperes

OI

amperesMX2222

POWEROFF SELECT

TUNERCD

CASSOFF

MASTER

MUSIC SOURCESIG IN

BASSMAXMIN

EXT INPUT

MAX MAXMIN

SOURCE

MIN

SIG IN

CHIME MIXER TREBLEMAXMIN

TONE CTRLCH5 CH6CH4

SIG INSIG IN SIG INMAXMIN MAXMIN MIN

CH3CH1 CH2

SIG INSIG INMAXMIN MAXMIN MAXMIN MAX

AUX

SIG IN

INPUT SOURCES (PAGING MICS, BGM PLAYERS ETC)

24V DC

24V DC

24V DC

24V DC

MX2222 PRE-AMP MIXER

EP1200A EMERGENCY PANEL

POWER AMPLIFIERS

ZS SPEAKER ZONE SELECTOR

SPK VOLUME CONTROLLERS

SPEAKERS

audio out - balanced

audio out - balanced

100V line audio output

100V line output24V E/M override24V E/M

override

100V line output

dry contact to activate ALL CALL and 24V E/M override signal

Schematic Diagram

The schematic shown above is typical for most conventional installations. Audio output from mixer shall go through EP1200A prior to amplifier inputs to enable emergengy paging being highest priority.

Page 5: INSTRUCTION MANUAL · INPUT SOURCES (PAGING MICS, BGM PLAYERS ETC) 24V DC 24V DC 24V DC 24V DC MX2222 PRE-AMP MIXER EP1200A EMERGENCY PANEL POWER AMPLIFIERS ZS SPEAKER ZONE SELECTOR

EP1200A | EMERGENCY PAGING MICROPHONE PANEL PAGE 5

Connecting The Unit

24V DC POWER SUPPLY / BACK UP

SUPPLY

TRIGGERING PORT TO ACTIVATE EXTERNAL PLAYBACK DEVICE

EXTERNAL AUDIO INPUT (BALANCED LINE SIGNAL) FROM MESSAGE

PLAYBACK DEVICE

OUTPUT FROM PRE-AMPLIFIER MIXER (BALANCED LINE LEVEL)

TO POWER AMPLIFIER INPUT (BALANCED LINE)

EXTERNAL SIREN ACTIVATION CONTACT

(VOLTAGE FREE) ie. FIRE CONTROL CENTER / SMOKE

DETECTORS, ETC

DRY CONTACT (NORMALLY OPEN)

CONNECT TO ZONE SELECTORS FOR E/M OVERRIDING SIGNAL

ACTIVATIONRS 485

Page 6: INSTRUCTION MANUAL · INPUT SOURCES (PAGING MICS, BGM PLAYERS ETC) 24V DC 24V DC 24V DC 24V DC MX2222 PRE-AMP MIXER EP1200A EMERGENCY PANEL POWER AMPLIFIERS ZS SPEAKER ZONE SELECTOR

ER1108 E/M OVERRIDE PANEL

EP1200A EMERGENCY PAGINGPANEL

ZONE 2AMPLIFIER

ZONE 5AMPLIFIER

AMPLIFIER

ZONE 1SPEAKERS

ZONE 8SPEAKERS

B G M 2

A no ther Q ua lity P roduct F rom

O U T P U T 4 O U T P U T 3 O U T P U T 2 O U T P U T 1O U T P U T 5O U T P U T 6O U T P U T 7O U T P U T 8

IN P U T 4 IN P U T 3 IN P U T 2 IN P U T 1IN P U T 5IN P U T 7IN P U T 8 IN P U T 6

PRIORITY INPUT

ZONE 3AMPLIFIER

ZONE 4AMPLIFIER

ZONE 7AMPLIFIER

ZONE 8AMPLIFIER

ZONE 1AMPLIFIER

MxP2188

MR1301

ZONE 6

PAGE 6 EP1200A | EMERGENCY PAGING MICROPHONE PANEL

Connecting The Unit - Matrix System

DC

24V

+

Audio

TriggerAudio

Trigger

In matrix installation, audio output shall be fed to ER1108 together with triggering signal. When EP1200A is active, all incoming audio from MxP2188 shall be bypassed to allow emergency paging.

Usage of DA2208 maybe required if quantity of amplifier is large.

Page 7: INSTRUCTION MANUAL · INPUT SOURCES (PAGING MICS, BGM PLAYERS ETC) 24V DC 24V DC 24V DC 24V DC MX2222 PRE-AMP MIXER EP1200A EMERGENCY PANEL POWER AMPLIFIERS ZS SPEAKER ZONE SELECTOR

EP1200A | EMERGENCY PAGING MICROPHONE PANEL PAGE 7

I NP

UTO

UTPU

T

P IN 8 -COMP IN 7 -24VP IN 6 -Z6P IN 5 -Z5P IN 4 -Z4P IN 3 -Z3P IN 2 -Z2P IN 1 -Z1

P IN 8 -COMP IN 7 -24VP IN 6 -Z12P IN 5 -Z11P IN 4 -Z10P IN 3 -Z9P IN 2 -Z8P IN 1 -Z7

+DC 24V

CONRLY

TRIGRLY

PRZS

MX2222

EP1200A

PA2480

EX2800

TD6240

ZS5121

PD2800MR1301

Audio

Audio

RS485 & Audio

AMP Output

Audio

Cat5eCat5e

Connecting The Unit - Conventional System

DC 24V+

Trigger

SPEAKER

Page 8: INSTRUCTION MANUAL · INPUT SOURCES (PAGING MICS, BGM PLAYERS ETC) 24V DC 24V DC 24V DC 24V DC MX2222 PRE-AMP MIXER EP1200A EMERGENCY PANEL POWER AMPLIFIERS ZS SPEAKER ZONE SELECTOR

PAGE 8 EP1200A | EMERGENCY PAGING MICROPHONE PANEL

iPX5151

iPX5151

LAN

iPX5101

iPX5151

P IN 8-COMP IN 7 -24VP IN 6 -Z6P IN 5 -Z5P IN 4 -Z4P IN 3 -Z3P IN 2 -Z2P IN 1 -Z1

P IN 8 -COMP IN 7 -24VP IN 6 -Z12P IN 5 -Z11P IN 4 -Z10P IN 3 -Z9P IN 2 -Z8P IN 1 -Z7

+DC 24V

CONRLY

TRIGRLY

PRZS

EP1200A

PD2800

MX2222

PA2480

ZS5121

TD6240

SPEAKER

Cat5e

Cat5e

Cat5e

Cat5e

Audio Output

RS485 (AB) Data

Cat5e

Audio

AMP Output

Cat5eCat5e

Configuring ALL CALL And E/M Overriding via iPX

EP1200A, which is installed at main rack for a large system using IP as communication interface, shall be able to override remote buildings / system as similar to single rack installation.

Page 9: INSTRUCTION MANUAL · INPUT SOURCES (PAGING MICS, BGM PLAYERS ETC) 24V DC 24V DC 24V DC 24V DC MX2222 PRE-AMP MIXER EP1200A EMERGENCY PANEL POWER AMPLIFIERS ZS SPEAKER ZONE SELECTOR

EP1200A | EMERGENCY PAGING MICROPHONE PANEL PAGE 9

Configuring ALL CALL And E/M Overriding

EP1200A

P IN 8 -COMP IN 7 -24VP IN 6 -Z6P IN 5 -Z5P IN 4 -Z4P IN 3 -Z3P IN 2 -Z2P IN 1 -Z1

+DC 24V

CONRLY

TRIG PRZS

EP1200A

PS9400 PSU

PM SERIESPAGING MIC

ZS5121 ZONE SELECTOR

Volume Controller

TO SPEAKERS

FR. ZONE SELECTOR 100V LINE OUTPUT

24V E/M Overriding

Signal

Connect this to allow EP1200A to trigger internal

relay of Zone Selector

+ -

The above diagram shows detailed connections for using EP1200A to override volume control and activating ALL CALL at zone selector.

Page 10: INSTRUCTION MANUAL · INPUT SOURCES (PAGING MICS, BGM PLAYERS ETC) 24V DC 24V DC 24V DC 24V DC MX2222 PRE-AMP MIXER EP1200A EMERGENCY PANEL POWER AMPLIFIERS ZS SPEAKER ZONE SELECTOR

PAGE 10 EP1200A | EMERGENCY PAGING MICROPHONE PANEL

Technical Specifications

Summary Of Features

Built in siren tone generator (constant signal)

Visual FIRE indicator

External voice message activation

Dual mode siren tone activation

Dry contact when paging mic is activated

Priority paging via front panel microphone, bypassing all other audio sources

Output level controls for siren and message / paging microphone

Interface to IP Paging Sytem via iPX5000

Power requirement 24V DCPower consumption 3.5W

MICROPHONEMic sensitivity -72 dB Omni directionalImpedance 600 OhmFrequency response 300 ~ 8 KHz

SIRENSiren frequency Continuous at 8 KHzSiren duration Continuous when activated Siren activation Front test switch / remote contact

Input channel Pre-amplifier output, message recorderOutput level Balanced line out (1.2V)Priority sequence Paging mic - siren - message - pre amp inIndicators Front FIRE with backlight illuminationDimension (WxHxD) 482 x 88 x 180 mmWeight 3.0 kg

Page 11: INSTRUCTION MANUAL · INPUT SOURCES (PAGING MICS, BGM PLAYERS ETC) 24V DC 24V DC 24V DC 24V DC MX2222 PRE-AMP MIXER EP1200A EMERGENCY PANEL POWER AMPLIFIERS ZS SPEAKER ZONE SELECTOR

Warranty Conditions

Disclaimer

Only Amperes Electronics Service Centres are allowed to make warranty repairs : a list of Amperes Electronics Service Centres may be asked for by the purchaser or send directly to Amperes Electronics Sdn Bhd at 70 Jalan Industri PBP 3, Tmn Perindustrian Pusat Bandar Puchong, 47100, Puchong, Selangor, Malaysia or its authorized master distributor, TNT Links Sdn Bhd / MyPA Systems Sdn Bhd. This warranty is not valid if repairs are performed by unauthorized personnel or service centres.

This warranty covers only repairs and replacement of defective parts ; cost and risks of transportation as well as removal and installation of the product from the main system are for the account of the purchaser. This warranty shall not extend to the replacement of the unit.

This warranty does not cover damages caused by misuse, neglect, accident of the product as well as using the product with power supply voltage other than shown on the product, or any other power supply source / adaptor not recommended by the manufacturer.

This warranty does not cover damages caused by fire, earthquakes, floods, lightning and every cause not directly related to the unit.

This warranty does not include any indemnity in favor of the purchaser or the dealer for the period out of use of the unit; moreover the warranty does not cover any damages which may be caused to people and things when using the product.

This warranty certificate is valid only for the described product, and is not valid if modifications are made on this certificate or on the identification label applied on the product.

This warranty covers all the material and manufacturing defects and is valid for a period of 12 months from the date of purchase or for a longer period in countries where this is stated by a national law. In this case, the extension is valid only in the country where the product is purchased.

Amperes Electronics Sdn Bhd is not obliged to modify previously manufactured products under warranty if the design changes or improvements are made.

Information contained in this manual is subject to change without prior notice and does not represent a commitment on the part of the vendor. AMPERES ELECTRONICS SDN BHD shall not be liable for any loss or damages whatsoever arising from the use of information or any error contained in this manual.

It is recommended that all services and repairs on this product be carried out by AMPERES ELECTRONICS SDN BHD or its authorized service agents.

AMPERES series must only be used for the purpose they were intended by the manufacturer and in conjunction with this operating manual.

AMPERES ELECTRONICS SDN BHD cannot accept any liability whatsoever for any loss or damages caused by service, maintenance or repair by unauthorized personnel, or by use other than that intended by the manufacturer.

Page 12: INSTRUCTION MANUAL · INPUT SOURCES (PAGING MICS, BGM PLAYERS ETC) 24V DC 24V DC 24V DC 24V DC MX2222 PRE-AMP MIXER EP1200A EMERGENCY PANEL POWER AMPLIFIERS ZS SPEAKER ZONE SELECTOR

Another Quality Product From

Amperes Electronics Sdn BhdCo Reg : 509025-X

www.ampereselectronics.com

This product has been manufactured under strictISO9001 : 2008 management system

Certificate no: 16895 / A / 0001 / UK / En

ISO 9001: 2008Design & Manufacture of Public Address Equipment and Systems

Certi�cate No. 16895 / A / 0001 / UK / En

EP1200A

EMERGENCY PAGING PANEL

Made In Malaysia Updated APRIL 2015


Recommended