+ All Categories
Home > Documents > Instruction Manual SIMEAS P

Instruction Manual SIMEAS P

Date post: 24-Nov-2015
Category:
Upload: iwansatya
View: 112 times
Download: 1 times
Share this document with a friend
Description:
Instruction Manual SIMEAS P
Popular Tags:
60
© Siemens AG 2000; All Rights Reserved SIMEAS P Power Meter Instruction manual Foreword Commissioning 1 Operation 2 Measured variables 3 Device parameterization 4 Profibus DP 5 Edition: 01.05.01
Transcript
  • Siemens AG 2000; All Rights Reserved

    SIMEAS PPower MeterInstruction manual

    Foreword

    Commissioning 1

    Operation 2

    Measured variables 3

    Device parameterization 4

    Profibus DP 5

    Edition: 01.05.01

  • Commissioning Manual for SIMEAS P Power Meter

    Siemens AG 2000; All Rights Reserved Page 2 out of 60-

    Information forYour Own Safety

    This manual does not contain a full list of the safety measures for operation of the equipment (module,device) because special operating conditions may necessitate further measures. However, it doescontain information which must be adhered to in the interests of your own personal safety and to avoidmaterial damages. This information is highlighted by a warning triangle and are represented as follows,depending on the degree of potential danger:

    _____________________________________________________________________________________________

    Warning

    means that failure to take the necessary safety precautions can result in death, serious injury orconsiderable material damage

    Caution

    means that failure to take the necessary safety precautions will result in death, serious injury orconsiderable material damage

    _____________________________________________________________________________________________

    Qualified personnel Commissioning and operation of the equipment (module, device) described in this manual may only beperformed by qualified personnel. Qualified personnel in the sense of the safety information contained inthis manual are persons who are authorized to commission, start up, ground and label devices, systemsand circuits according to safety standards.

    Use for the intended purposeThe equipment (device, module) may only be used for the application cases specified in the catalog andthe technical manual and only in connection with OEM devices and components recommended andapproved by Siemens.The prerequisites for perfect, reliable operation of the product are proper transport, proper storage,installation and assembly, as well as proper operation and maintenance.When operating electrical equipment, certain parts of this equipment automatically carry dangerousvoltages. Improper handling can therefore result in serious injury or material damage:

    The equipment must be grounded at the PE terminal before making any connections whatsoever.

    Dangerous voltages may occur in all circuit components connected to the power supply.

    Dangerous voltages may still exist in the equipment even after it has been disconnected from thepower supply (capacitor memory)

    Equipment with current transformer circuits may not be operated in an open state.

    The limit values specified in the manual and in the operating instructions must not be exceeded; thismust also be taken into account during inspection and commissioning

    _____________________________________________________________________________________________

    Exclusion of liabilityWe have checked the contents of this publication and everyeffort has been made to ensure that the descriptions of bothhardware and software are as accurate as possible. However,deviations from the description cannot be completely ruled out,so that no liability can be accepted for any errors or omissionscontained in the information given.The data in this manual are checked regularly and thenecessary corrections are included in subsequent editions. Weare grateful for any improvements that you care to suggest.

    Subject to technical modifications without notice.

    CopyrightCopyright Siemens AG April d, yyyy 2:10 a10/p10 All RightsReservedIt is prohibited to pass on or copy this document or to use ordisclose its contents without our express permission. Anyduplication is a violation of the law and subject to criminal andcivil penalties. All rights reserved, particularly in the event of apatent award or utility model registration.Registered trademarksSIMATIC, SIMATIC NET, SINAUT and SICAM areregistered trademarks of the SIEMENS AG. The other namesappearing in this manual may be trade names the use of whichby third parties for their own purposes may infringe the rightsof the owners.

    _____________________________________________________________________________________________

  • Commissioning Manual for SIMEAS P Power Meter

    Siemens AG 2000; All Rights Reserved Page 3 out of 60-

    Foreword

    Purpose of this manual

    This manual describes the functions of the Power Meter SIMEAS P

    Target group

    This manual addresses the users of SIMEAS P.

    Standards

    SIMEAS P was developed according to the principles of ISO 9000.

    Additional support

    If you have questions concerning SIMEAS P please contact: Your local Siemens distributor The Siemens hotline (workdays from 7.30 to 17.00 h):

    +0049(0)180- 5247000 Fax: 0180-5242471

    or

    Email: [email protected]

    More information under:

    www.powerquality.de

  • Commissioning Manual for SIMEAS P Power Meter

    Siemens AG 2000; All Rights Reserved Page 4 out of 60-

    Commissioning

    1.1 Scope of delivery..................................................................................................5Dimensions and weight .................................................................................................51.3 Block diagram......................................................................................................51.4 Interface and terminals.......................................................................................6

    1.4.1 Terminal assignment of SIMEAS P ....................................................................... 61.4.2 Pin assignment of the interface............................................................................... 61.4.3 Connection examples ............................................................................................... 7

    1.4.3.1 General.................................................................................................................. 71.4.3.2 Single-phase AC current ....................................................................................... 71.4.3.3 Three-wire three-phase-balanced.......................................................................... 81.4.3.4 Three-wire three-phase unbalanced ( 2 I ) ............................................................ 81.4.3.5 Three-wire three-phase unbalanced ( 3 I ) ............................................................ 81.4.3.6 Three-phase four-wire balanced ........................................................................... 81.4.3.7 Three-phase four-wire, unbalanced (low-voltage system).................................... 91.4.3.8 Three-phase four-wire, unbalanced (high-voltage system)................................... 9

    1.4.4 Commissioning......................................................................................................... 9

    1

  • Commissioning Manual for SIMEAS P Power Meter

    Siemens AG 2000; All Rights Reserved Page 5 out of 60-

    Inputs / Outputs

    Binary output 1

    Binary output 2

    Communicationinterface9-pin D/SUB

    Auxiliary energyUniversal powersupply24 to 250V DC100 to 230V AC

    U L1U L2U L3U N

    I L1

    I L2

    I L3

    AC/ DC

    1.1 Scope of deliveryDelivery noteOriginal cardboard box with the SIMEAS P logo.

    Contents: 1 device SIMEAS P 2 fixings for panel mounting. 1 instruction manual 1 return note 1 test report of the device

    1.2 Dimensions and weightTechnical data of housing

    Housing type:Switchboard cabinet according to DIN

    43700Degree of protection:

    Front IP 41Terminals IP 20

    Dimensions of cabinet:144 x 144 x 86 ( W x H x D )

    Weight:approx. 0.9 kg

    Connection elements

    Auxiliary energy:Terminals for cable diameter 2.5 mm2

    Voltage inputs:Terminals for cable diameter 2.5 mm2

    Current inputs:Terminals for cable diameter 4.0 mm2

    Binary outputs:Terminals for cable diameter 2.5 mm2

    RS485 bus interface:9-pin D-Sub-connector

    1.3 Block diagram

  • Commissioning Manual for SIMEAS P Power Meter

    Siemens AG 2000; All Rights Reserved Page 6 out of 60-

    1.4 Interface and terminals

    1.4.1 Terminal assignment of SIMEAS P

    1.4.2 Pin assignment of the interface

    Pin-N. RS485 interface Profibus interface1 Protective earth Protective earth23 A B (RxD/TxD-P)4 RTS CTRL-A5 GNDEXT GNDEXT6 +5 VEXT +5 VEXT78 B A (RxD/TxD-N)9

    The housing of the RS 485 interface is connected to the protective earth (PE).The bus termination is accomplished in the connecting cable.The isolated supply voltage of the interface is available at the D-SUB femaleconnector to enable the terminating resistors for the data signals to be connectedin the connecting cable.

  • Commissioning Manual for SIMEAS P Power Meter

    Siemens AG 2000; All Rights Reserved Page 7 out of 60-

    1.4.3 Connection examples

    1.4.3.1 GeneralThe following examples of input wirings are examples (according to DIN 43807).Up to the rated maximum current and voltage values, the device can also beconnected without an interposed current or voltage transducers.

    Voltage transducers can be applied in star connection or in V-connection.

    All input or output terminals not required for the measurement remain unoccupied.

    Designation of the terminals of AC current and three-phase currentmeasuring devices according to DIN 43807 / Oct. 1983:

    DIN 43807 1 3 4 6 7 9 11 2 5 8

    Terminal IL1IL1

    IL2

    IL2

    IL3

    IL3 N UL1 UL2 UL3

    SIMEAS P E1 E2 E3 E4 E5 E6 F4 F1 F2 F3

    Caution:The earth continuity of the transducers is represented in this way only for the sakeof simplicity.The grounding must be performed directly at the transducer and for eachtransducer separately.

    1.4.3.2 Single-phase AC current

  • Commissioning Manual for SIMEAS P Power Meter

    Siemens AG 2000; All Rights Reserved Page 8 out of 60-

    1.4.3.3 Three-wire three-phase-balanced

    1.4.3.4 Three-wire three-phase unbalanced ( 2 I )

    1.4.3.5 Three-wire three-phase unbalanced ( 3 I )Ohne Bild

    1.4.3.6 Three-phase four-wire balanced

  • Commissioning Manual for SIMEAS P Power Meter

    Siemens AG 2000; All Rights Reserved Page 9 out of 60-

    1.4.3.7 Three-phase four-wire, unbalanced (low-voltage system)

    1.4.3.8 Three-phase four-wire, unbalanced (high-voltage system)

    1.4.4 CommissioningBefore switching on the auxiliary voltage, it must be verified that the operationalcharacteristics correspond to those indicated on the rating plate. This applies inparticular to the auxiliary voltage and the rated current and voltage values of thestation. After a 15-minute warm-up phase, the device observes the error limits.

  • Operation Manual for SIMEAS P Power Meter

    Siemens AG 2000; All Rights Reserved Page 10 out of 60-

    Operation

    2.1 Display of the screens ........................................................................................112.2 Contents of the screens......................................................................................11

    2.2.1 Screen types ............................................................................................................ 112.2.2 2 Measured values digital...................................................................................... 122.2.3 2 Measured values digital / analog ....................................................................... 122.2.4 4 Measured values digital...................................................................................... 122.2.5 4 Measured values digital / analog ....................................................................... 122.2.6 Arrow diagram.....................................................Fehler! Textmarke nicht definiert.2.2.7 Harmonics screens ................................................................................................. 132.2.8 Min Max values................................................................................................... 132.2.9 Oscilloscope ............................................................................................................ 14

    2.2.9.1 General............................................................................................................... 142.2.9.2 Menu.................................................................................................................. 142.2.9.3 Characteristics of "Instantaneous value" recording ........................................... 152.2.9.4 Characteristics of "Rms value" recording.......................................................... 16

    2.2.10 Status line ............................................................................................................... 17

    2

  • Operation Manual for SIMEAS P Power Meter

    Siemens AG 2000; All Rights Reserved Page 11 out of 60-

    2.1 Display of the screensWhen SIMEAS P has been adapted to its measuring task (chapter 4) andconnected (chapter 2), the measured variables determined by the user aredisplayed on screens. The screens can be selected via

    the two front buttons. Press a button once to display the

    next or the previous screen. Hold the button to scroll through

    the screens automatically. Equally, a fixed automatic scrolling

    through the screens can beparameterized.

    You scroll through screens in a loop,i.e after the last screen the first isdisplayed and vice versa.

    2.2 Contents of the screens

    The user must be able to read all information relevant for the measurement task ata glance.

    For this purpose, the screens feature a simple and individual design. The numberof screens (max. 20), the screen types and their contents can be individuallyparameterized by the user

    The following screen types are available:

    2.2.1 Screen types 2 MVS digital 2 MSV digital / analog 4 MSV digital 4 MSV digital / analog Arrow diagram Harmonic U / I Min Max values Oscilloscope Sinus / rms values

  • Operation Manual for SIMEAS P Power Meter

    Siemens AG 2000; All Rights Reserved Page 12 out of 60-

    2.2.2 2 Measured values digital

    Status line for SIMEAS P

    Display of any 2 measuredvariables from the measuredvariable table.

    2.2.3 2 Measured values digital / analog

    Display of any 2 measured variablesfrom the measured variable table.

    Parameterizable start and final valueof each analog bar.

    2.2.4 4 Measured values digital

    Display of any 4 measured variablesfrom the measured variable table.

    2.2.5 4 Measured values digital / analog

    Display of any 4 measured variablesfrom the measured variable table.

    Parameterizable start and final valueof each analog bar.

    2.2.6 Vector Diagram

    Here the status of the system can beread a glance.

    Digital and graphic display of allconnected conductorsmeasured variables: U / I / cos phi

  • Operation Manual for SIMEAS P Power Meter

    Siemens AG 2000; All Rights Reserved Page 13 out of 60-

    2.2.7 Harmonics screens

    Graphic display of screens withharmonics of current or voltage.

    Display of all odd numbers in allconductors up to 21 harmonics.

    When "ENTER" is pressed,a window appears on the right upperscreen indicating the digital values of one harmonic for all three conductors.

    Via the buttons all odd harmonics up to 21 can be selected in thedisplayed window.

    Hold the "ENTER" button to enter the main menu of level 2. Graphic display in % of the measured value. 100% represents the maximum

    value of the first harmonic of one of the three conductors. Digital values:voltages in %, current in A.

    The harmonics (5th,7th,11th,13th,17th,19th) considered important in thestandard can also be displayed individually as measured variables on themeasured values screens.

    2.2.8 Min Max values

    Up to 8 measured variables frommeasured variable tables (exceptenergy and metered values) can bemonitored here.

    Display of the minimum value, theaverage value, and the maximum valueof a variable measured since the startof the recording.

    The recording starts with the "Reset" of the Min Max values on theparameterization level or when the device is switched on.

    If no time is set, the duration of the recording is indicated in hours and minutes.If the time is set, the date and the time of the recording start are indicated.

    Any number of listing screens can be parameterized. Using space lines instead of measured variables provides a clearer overview of

    the representation.

  • Operation Manual for SIMEAS P Power Meter

    Siemens AG 2000; All Rights Reserved Page 14 out of 60-

    2.2.9 Oscilloscope

    2.2.9.1 General

    The oscilloscope represents a special case among the screens. Only one screenoscilloscope can be selected. The settings are made directly on the screenoscilloscope via the button Enter = Menu. Always 3 measured variables are recorded. The level height of each measured variable is accomplished automatically. Display of the measured value of each measured variable via cursor position. Generally, 10 % of the history of each recording is displayed. Only one recording is possible. When initiating a new recording, the previous

    one is deleted. When triggering the oscilloscope via limit violation, the recording can also be

    executed in the background. Only the first of several limit violations which triggers a recording is recorded.

    Further violations are ignored. A new recording must be activated in the menuvia "OK + enable".

    The total duration of a recording including the pre-fault history and the post-fault history is limited to 7040 measuring points for sinus values and 14000measuring points for rms values per measured value.

    2.2.9.2 Menu

    Record type Instantaneous value Rms value

    Measured values 1 to 3 From measured variable table

    (depending on record type)

    Trigger Manual (after start-up via the front button "ENTER") Limit value 1 to 6 (Upon selection and confirmation an input window for

    modifying or confirming the limit value parameters appears. As described in thechapter "Device parameterization, "Input window for limit values", hysteresis,filter time, and the connection of several measured variables can bedetermined.)

    Recording time The recording time depends on the record type. For instantaneous values the setting of the recording time is fixed to 2 second. For rms values it can be adjusted < 4.0 h.

    * Record type : Instantaneous value* Measured value 1 : U L1* Measured value 2 : L2* Measured value 3 : U E-N* Trigger : Manual* Length : 0 : 0 : 2

    < Zoom off< Cursor off< Abortion< OK + enable< Main menu

  • Operation Manual for SIMEAS P Power Meter

    Siemens AG 2000; All Rights Reserved Page 15 out of 60-

    Zoom If the zoom function is activated via "on" and confirmed, the time axis can be

    changed up to the minimum or maximum variable via the buttons

    Cursor If the cursor is activated via "on" and confirmed, the cursor can be moved on

    the time axis by using the buttons . If the button is pressed once, thecursor moves by one position. If the button is held, the cursor movesautomatically with increasing speed.

    The values of the measured variables are automatically displayed on the Yaxis for the corresponding cursor position.

    Abortion Modified settings in the menu are not accepted. Back to the oscilloscope

    screen.

    OK + enable Modified settings in the menu are accepted and trigger the recording. Back to

    the oscilloscope screen.

    Main menu Here the user can access the main menu of level 2 from the oscilloscope

    screen.

    2.2.9.3 Characteristics of "Instantaneous value" recording

    Recording time cannot be changed and is fixed to approx. 2s ( 200 ms of pre-fault history and approx. 1800ms of post-fault history). (7040 measuring pointsper measured variable).

    The time axis in the screen can be changed via zoom from 60 ms to 2000 ms

    Sampling points

    The measuring interrupt is thus adapted to the frequency that each period issampled with 64 measuring points.

    Therefore, the sampling rate is: At 50 Hz = 3.20 kHz At 60 Hz = 3.84 kHz

    Trigger via limit violation:The rms value of each half wave is calculated and tested for Max/Min violations. Aviolation immediately triggers the recording.

  • Operation Manual for SIMEAS P Power Meter

    Siemens AG 2000; All Rights Reserved Page 16 out of 60-

    Only the measured variables currentor voltage are available for input.The parameters hysteresis and filtertime are meaningless.

    2.2.9.4 Characteristics of "Rms value" recording

    3 measured variables can be selected from the measured variable table exceptenergy and metered values.

    Recording time can be modified up to a maximum of 3h 59min. (approx.14000 measuring points per measured variable)

    Each second one measuring point of a measured variable is saved. Pre-fault history is always 10% of the selected recording time. Time axis on the screen can be changed via the zoom function:

    Note

    As 10% of the recording time are always written as pre-fault history, the time forwriting the pre-fault history must expire before a new recording can be triggered.The minimum time resolution on the display is limited for the recording time by thenumber of the approx. 200 pixels. That is 1 pixel = 1s per measured value. Theshortest time period which can be displayed on the time axis is thus approx. 3 min.For recording times < 3min, only a part of the display width is used for recording.

  • Operation Manual for SIMEAS P Power Meter

    Siemens AG 2000; All Rights Reserved Page 17 out of 60-

    2.2.10 Status line

    The screens ( except harmonics and oscilloscope ) feature a status line whichdisplays the status of SIMEAS P.

    1.) Diagnostic messages">

  • Measured variables Manual for SIMEAS P Power Meter

    Siemens AG 2000; All Rights Reserved Page 18 out of 60-

    Measured variables

    Measured variables depending on the connection typeTable 1 Measured variables depending on the connection type

    N Measured variable

    1-ph

    ase

    AC c

    urr

    ent

    Thre

    e-w

    ireth

    ree-

    phas

    e-

    bala

    nced

    Thre

    e-w

    ireth

    ree-

    phas

    eu

    nba

    lanc

    ed

    3I

    Thre

    e-w

    ireth

    ree-

    phas

    eu

    nba

    lanc

    ed

    2I

    Thre

    e-ph

    ase

    four

    -wire

    bala

    nced

    Thre

    e-ph

    ase

    four

    -wire

    un

    bala

    nce

    d

    Comments

    1 (space line)* X X X X X X2 Voltage L1-N X X X UL13 Voltage L2-N X UL24 Voltage L3-N X UL35 Voltage E-N X X X X X X UE-N6 Voltage L1-L2 X X X X UL127 Voltage L2-L3 X X X X UL238 Voltage L3-L1 X X X X UL319 Voltage averag value L-N* L-N/3 L-N/3 L-N/3 L1-N L-N/3 U

    10 Current L1 X X X X X X IL111 Current L2 X X X IL212 Current L3 X X X IL313 Current average value* X X I / 3 I14 Current N X X I015 Active power L1 X X PL116 Active power L2 X PL217 Active power L3 X PL318 Active power X X X X X P19 Reactive power L1 X X QL120 Reactive power L2 X QL221 Reactive power L3 X QL322 Reactive power X X X X X Q23 Apparent power L1 X X SL124 Apparent power L2 X SL225 Apparent power L3 X SL326 Apparent power X X X X X S27 Active factor cos L1 X X CosL128 Active factor cos L2 X CosL229 Active factor cos L3 X CosL330 Active factor cos X X X X X Cos31 Power factor L1 X X LFL132 Power factor L2 X LFL233 Power factor L3 X LFL334 Power factor X X X X X LF

    3

  • Measured variables Manual for SIMEAS P Power Meter

    Siemens AG 2000; All Rights Reserved Page 19 out of 60-

    N Measured variable

    1-ph

    ase

    AC c

    urr

    ent

    Thre

    e-w

    ireth

    ree-

    phas

    e-

    bala

    nced

    Thre

    e-w

    ireth

    ree-

    phas

    eu

    nba

    lanc

    ed

    3I

    Thre

    e-w

    ireth

    ree-

    phas

    eu

    nba

    lanc

    ed

    2I

    Thre

    e-ph

    ase

    four

    -wire

    bala

    nced

    Thre

    e-ph

    ase

    four

    -wire

    un

    bala

    nce

    d

    Comments

    35 Phase angle L1 X X PhiL136 Phase angle L2 X PhiL237 Phase angle L3 X PhiL338 Phase angle X X X X X Phi39 Mains frequency X X X X X X Frq40 Asymmetric voltage X USymU41 Asymmetric voltage X USymI42 THD voltage L1 X X THD UL143 THD voltage L2 X THD UL244 THD voltage L3 X THD UL345 THD current L1 X X THD IL146 THD current L2 X THD IL247 THD current L3 X THD IL348 Harmonic voltage L1* X X X X X X HUL1 5,7,11,13,17,1949 Harmonic voltage L2* X X X HUL2 5,7,11,13,17,1950 Harmonic voltage L3* X X X HUL3 5,7,11,13,17,1951 Harmonic current L1* X X X X X X HIL1 5,7,11,13,17,1952 Harmonic current L2* X X X HIL2 5,7,11,13,17,1953 Harmonic current L3* X X X HIL3 5,7,11,13,17,1954 Active power E import L1* X X PL1 imp. /h55 Active power E import L2* X PL2 imp. /h56 Active power E import L3* X PL3 imp. /h57 Active power E import * X X X X X P imp. /h58 Active power E export L1 X X PL1 exp. /h59 Active power E export L2 X PL2 exp. /h60 Active power E export L3 X PL3 exp. /h61 Active power E export X X X X X P exp. /h62 Active power absolute L1* PL1 sum /h63 Active power absolute L2* PL2 sum /h64 Active power absolute L3* PL3 sum /h65 Active power absolute * P sum /h66 P balance* X X X X X P balance /h67 Reactive power ind. L1 X X QL1 ind. /h68 Reactive power ind. L2 X QL2 ind. /h69 Reactive power ind. L3 X QL3 ind. /h70 Reactive power ind. X X X X X Q ind. /h71 Reactive power cap. L1 X X QL1 cap. /h72 Reactive power cap. L2 X QL2 cap. /h73 Reactive power cap. L3 X QL3 cap. /h74 Reactive power cap. X X X X X Q cap. /h75 Reactive power absolute L1* X X QL1 sum /h76 Reactive power absolute L2* X QL2 sum /h77 Reactive power absolute L3* X QL3 sum /h78 Reactive power absolute * X X X X X Q sum /h79 Apparent power ES L1 X X SL1 /h80 Apparent power ES L2 X SL2 /h81 Apparent power ES L3 X SL3 /h82 Apparent power ES X X X X X S /h83 Counter 1 / 2 / 3 / 4* X X X X X X Cntr.1,2,3,4

  • Measured variables Manual for SIMEAS P Power Meter

    Siemens AG 2000; All Rights Reserved Page 20 out of 60-

    * ExplanationNr. Name Description

    1 (space line) If a space line is selected, the field of this measured variable remains empty onthe display screens.

    9 Votage average value L-N The average value of the applied phase voltages U-N is displayed here. For theconnection type 3-conductor.... this value is calculated

    13 Current average value The average value of the 3 currents is displayed here.48to

    53

    HarmonicsU/I

    The standard IEC 1000-2-2 and also EN 50160 specify compatibility levels fromthe range up to 21 only for harmonics of orders 5, 7, 11, 13, 17, 19. Those ofeven order and those divisible by 3 are considered irrelevant.The selection in the "Harmonics" screen is therefore limited to all uneven ordersup to 21. The selection of single harmonics in the measured values screens islimited to 5th, 7th, 11th, 13th, 17th and 19th.For voltage the percentage value of the harmonics refers to the measured value.For current the values are displayed directly in A.

    54to

    57

    Active power E import Import is given if a standards-conforming connection produces a positivemeasured.

    62to

    65

    Active power absolute The sum of the absolute values (without sign) of import and export of the activepower.

    66 P balance The balance of the active power of export and import is indicated. The import ispositive. (import minus export). As the variable can have different polarity, theoutput as pulse via relay is not possible.

    75to

    78

    Reactive power absolute The sum of the absolute values (without sign) of cap. and ind. of the reactivepower.

    83 Counters 1 / 2 / 3 / 4 Limit violations can be added and displayed digitally here.

  • Device parameterization Manual for SIMEAS P Power Meter

    Siemens AG 2000; All Rights Reserved Page 21 out of 60-

    Device parameterization

    4.1 Operating notes..................................................................................................224.1.1 Button functions..................................................................................................... 224.1.2 Window structure .................................................................................................. 224.1.3 Notes........................................................................................................................ 23

    4.2 Overview of the levels........................................................................................234.3 Main menu .........................................................................................................24

    4.3.1 Basic parameters.................................................................................................... 244.3.1.1 Overview of the parameters............................................................................... 244.3.1.2 Connection / transducer ..................................................................................... 254.3.1.3 Outputs............................................................................................................... 274.3.1.4 Interface ............................................................................................................. 284.3.1.5 Changing the code ............................................................................................. 294.3.1.6 Calibration ......................................................................................................... 294.3.1.7 Additional settings ............................................................................................. 30

    4.3.2 Language / designation.......................................................................................... 304.3.3 Information on SIMEAS....................................................................................... 314.3.4 Date / time............................................................................................................... 314.3.5 Reset ........................................................................................................................ 314.3.6 Screens parameterization...................................................................................... 32

    4.3.6.1 Screen structure ................................................................................................. 33

    4

  • Device parameterization Manual for SIMEAS P Power Meter

    Siemens AG 2000; All Rights Reserved Page 22 out of 60-

    4.1 Operating notes

    This chapter describes all setting options of SIMEAS P adjustable via its frontbuttons.

    The main menu of the parameterization level can be accessed from the measuredvalues screen, the Min/Max screen and the arrow diagram screen via the "ENTERbutton.From the harmonics screen it can be accessed by holding the "ENTER" buttonpressed.From the oscilloscope screen via "ENTER" "MENU"

    4.1.1 Button functions

    The following functions can be executed via the buttons: Moving the cursor to the entry line. Scrolling through selection lists when entering parameters. Selecting figures and characters when entering numerical values.

    If the buttons are held pressed, the scrolling continues automatically.The cursor, parameters or numbers in general are scrolled through via the buttons.

    The selected line, parameter, or number are confirmed by applying the "ENTER"button.

    4.1.2 Window structure

    Select * and "Enter" and thecursor jumps directly to the enterposition in the same window.

    Select > and "Enter" anda new window opens for furtherentries.

    Apply < "OK" to confirm the settingand to return to the previous level.

    If you apply < "abortion", the modified settings are not saved and you return to thescreens of level 1.

    ENTER

    * Number of screens : 14* Screen interval : 0 Sec.* Illumination : 99 Min.* Contrast : 5> Screen construction

    < OK< Abortion

  • Device parameterization Manual for SIMEAS P Power Meter

    Siemens AG 2000; All Rights Reserved Page 23 out of 60-

    4.1.3 Notes

    The selection of the measured variables depends on the selected connectiontype.

    The input of numbers is plausibilized and displayed with the note: "Overflow".The input value is then set to the maximum value.

    If the auxiliary energy is switched off during parameterization, a log text for theselection appears when the device is restarted. Therefore, the auxiliary energyshould only be switched off on level 1 (measuring screens).

    Log text

    Select "No" via the buttons toretain the default settings prior to thefailure of the auxiliary energy.

    Choose"Yes" by applying the "ENTER"button to restore the default values.

    4.2 Overview of the levels Level 1 is the level with the measurement screens The levels 2 to 4 are parameterization levels as will be described in the

    following.

    Basicparameters

    Parameterizationscreens

    Information onSIMEAS P

    Overview ofparameters

    Connectiontransducer

    Outputs Inter-faces

    Changecode

    Cali-bration

    Screenstructure

    Language /designation

    Date / time Reset

    Additionalsettings

    Main menu

    Power Meter

    Caution faulty parameters!

    Reset ?

    No Yes( Arrow ) ( Enter )

  • Device parameterization Manual for SIMEAS P Power Meter

    Siemens AG 2000; All Rights Reserved Page 24 out of 60-

    4.3 Main menu

    Via the main menu the othersubmenus can be accessed.

    4.3.1 Basic parameters

    Via the menu basic parameters the inputscreens for the parameterization of thedevice can be selected.

    4.3.1.1 Overview of the parametersHere, the most important settings of thedevice are displayed on one screen.

    > Basic parameters> Language / designation> Information on SIMEAS> Date / Time> Reset> Parameterization screens

    < Exit

    > Overview of the parameters> Output / transducer> Outputs> Interface> Change code> Calibration> Additional settings

    > OK< Exit

    Calculation mode: standard 4-conductor any loadCurrent: 1.2 AVoltage: 480VRel 1: Limit value 1Rel 1: Limit value 2Bus Adr.: 01

    < Abortion

  • Device parameterization Manual for SIMEAS P Power Meter

    Siemens AG 2000; All Rights Reserved Page 25 out of 60-

    4.3.1.2 Connection / transducerConnection:

    As described in chapter 1:"connection examples", the type ofpower supply can be selected here.

    1-phase AC current Three-phase four-wire balanced Three-phase four-wire unbalanced Three-phase three-wire balanced Three-phase three-wire unbalanced ( 2 x I ) Three-phase three-wire unbalanced ( 3 x I )" Three-phase three-wire unbalanced " can be selected either with the connectionof 2 current transducers ( standard / Aron measuring circuit ) or with 3 currenttransducers.

    Current transducers:

    Yes ( Transducer input can be selected/ max. prim: 999 999 A; sec: 6 A) No ( Transducer input cannot be selected)Measuring range:

    1.2 A ( rated range 1 A ) 6 A ( rated range 5 A )Here, the user himself can select the internal current measuring range of SIMEASP.

    Caution: The measuring range must be determined for the setting with and without

    transducer. The selected measuring range must be greater than the secondary value of the

    transducer! The accuracy of SIMEAS P refers to this measuring range. The determination of this range indicates the maximum current measuring

    range which can be displayed on the device.

    Example:Transducer: 500 / 1 AMeasuring range 1.2 A: Max. display range : 0 to 600AMeasuring range 6 A: Max. display range: 0 to 3000A

    Recommendation: Generally 6 A

    Connection* Three-phase four-wire unbalanced* Current transducer: Yes* 100 A / 1 A* Measuring range: 1.2 A* Voltage transducer: No* kV / V* Measuring range L N : 480 V< OK< Abortion

  • Device parameterization Manual for SIMEAS P Power Meter

    Siemens AG 2000; All Rights Reserved Page 26 out of 60-

    Current transducer

    Yes ( Transducer input can be selected / max. prim: 1000.00 kV; sec.: 420 V)No ( Transducer input cannot be selected)Measuring range L-L:

    132 V ( rated range 100/110 V ) 228 V ( rated range 190 V ) 480 V ( rated range 400 V ) 828 V ( rated range 690 V )Conversion table for line voltage L-L into phase voltage L-N

    Selectable measuringrange L - L

    Equivalent tomeasuring range L - N

    0 to 132 V 0 to 76.2 V0 to 228 V 0 to 132 V0 to 480 V 0 to 276 V0 to 828 V 0 to 480 V

    Here, the user himself can select the internal measuring range of SIMEAS P. Up toY 400 / 690V can be connected directly without a transducer.

    Caution:

    The range must be determined for the setting with and without transducer. The selected measuring range must be greater than the secondary value of the

    transducer! The accuracy of SIMEAS P refers to this measuring range. The determination of this range indicates the maximum range which can be

    displayed on the device. The frequency measurement of SIMEAS P is initiated only when the

    determined voltage is >20%. Also for "Connection: single-phase AC current" the measuring range must be

    indicated as line to line voltage L-L. The L-N measuring range must bedetermined according to the conversion table.

    Example:Transducer: 10 kV / 100 VMeasuring range 132 V: Max display range: 0 to 13.2 kVMeasuring range 228 V: Max display range: 0 to 22.8 kV

    Recommendation:If the connection is made to transducers featuring secondary voltages of 100, 115or 120V, the measuring range "132 V" should be selected.If the connection is performed directly to Y 230 / 400V, the measuring range"480 V" should be chosen.If the connection is made directly to Y 400 / 690V, the measuring range of"828 V" should be selected.If "Connection: Single-phase AC current is made to 230V, the measuring range"480 V" (=256V L-N) should be chosen.

  • Device parameterization Manual for SIMEAS P Power Meter

    Siemens AG 2000; All Rights Reserved Page 27 out of 60-

    4.3.1.3 Outputs

    Here, the user can determine thefunction of the binary outputs.(Electronic relay potential-free)The various options for setting a relaywill be presented in the following.

    Selection: Off Relay has no function Device in operation Relay connected if auxiliary energy is applied. Energy pulses If selected, a new window "Energy pulses" appears. Limit values 1 If selected, a new window "Limit value 1" appears. Limit values 2 If selected, a new window "Limit value 2" appears. Limit values 3 If selected, a new window "Limit value 3" appears. Limit values 4 If selected, a new window "Limit value 4" appears. Limit values 5 If selected, a new window "Limit value 5" appears. Limit values 6 If selected, a new window "Limit value 6" appears.

    Input window for energy pulses

    Energy Selection of all energy variables

    from measured variable tablesdepending on the type of theconnection

    Value Input of the energy value per pulse

    Pulse duration Can be selected from 50, 100, 150, 200......to 500 ms.

    * Relay 1: Limit values 5* Relay 2: Energy pulses

    < OK< Abortion

    Energy pulses

    * Energy: P L1 import. / h* Value: 1.0000 kWh / imp* Pulse interval: 200 ms

    < OK< Abortion

  • Device parameterization Manual for SIMEAS P Power Meter

    Siemens AG 2000; All Rights Reserved Page 28 out of 60-

    Input window for limit value

    The values entered for hysteresis,pulse duration and filter time are validfor all logically connected measuredvariables.

    Hysteresis Input of 0,1 to 10 % max. Value refers to the rated values.

    Pulse duration 0,5s; 1s; 5s; 10s; 30s; 60s; 300s; (triggering for as long as a limit

    violation applies)Filter time Input of 0.0 to 9.9s max.

    (Minimum time during which a limitviolation must occur tolaunch a triggering)

    Limit values Selection of any measured variable from the measured variable table ( no

    energy variable or metered variable) It must be determined whether the triggering is launched if the measured

    variable is undershot or overshot( < > ). Indicating the measured value which initiates the triggering. Further measured variables can be connected logically via "and" or "or". A

    maximum of up to any 6 measured variables is possible.

    4.3.1.4 Interface

    Bus address Input of address 1 to 255

    Baudrate Selection only for connection to

    a PC.The baudrate of the Profibusis supported automatically up to12 MBd with the selection beingperformed via the master station.

    Protocol PC-RS485 ( For connection to a PC via parameterization software ) Profibus

    Limit value 5* Hysteresis: 1.0 %* Pulse duration: 30 s* Filter time: 1.0 s* U L1 < 9,8 kV or* U L1 > 10,2 kV< OK< Abortion

    * Bus address: 3* Baudrate: 9600 Bd* Protocol: PC RS 485

    < OK< Abortion

  • Device parameterization Manual for SIMEAS P Power Meter

    Siemens AG 2000; All Rights Reserved Page 29 out of 60-

    4.3.1.5 Changing the codeCode 1: Off: No function On: ( only active in connection

    with code 2).Secured functions: Parameterization of the screens Reset Language / designation

    Code 2: Off: No function (code 1 also deactivated ) On: Code activated.

    Secured functions: Basic parameters

    Notes:

    A password always consists of a 6-digit number. If you have forgotten the password, the device can also be activated by using

    the master password. Code 1 is only active if code 2 is also activated. If both code 1 and code 2 are activated, the password of code 2 can be used to

    access all protected functions of code 1. If an identical password is chosen for code 1 and code 2, all functions of code

    1 and code 2 can be activated by means of one single password. In level 1 a lock displayed on the status line indicates whether the status of the

    device is protected (closed) or unprotected (open). After a codeword has been parameterized, a time of 1 minute expires before it

    is activated in level 1 (the activation can be recognized by the closing of thelock on the status line).

    If the protected functions are called in the menu, a window for entering thepassword appears.

    If a protected parameter is activated by means of a password, all otherparameters of this code, too, are activated. A re-activation is performed onlyafter a time of 1 minute has expired in level 1.

    4.3.1.6 CalibrationSee chapter "Calibration.

    * Code 1 : 000000* off* Code 2 : 000000* off

    < OK< Abortion

  • Device parameterization Manual for SIMEAS P Power Meter

    Siemens AG 2000; All Rights Reserved Page 30 out of 60-

    4.3.1.7 Additional settings

    Counters 1 to 4

    On the screens the counters1 to 4 can be displayed digitally.Limit values can be assigned to thesecounters. When a counter is selected,a second window opens for the inputof the corresponding values(see binary outputs).

    Calculation mode Standard DIN Fourier

    The calculation mode for some measured variables can be changed here. Forfurther information see chapter "Measured variables.

    Current direction + (Standard if connection was performed correctly pursuant to the standard) - (Current direction is negated)The current direction can be changed here, so that connections do not have to beexchanged.

    4.3.2 Language / designation

    Sprache / Language

    The language of SIMEAS Pcan be selected here. D = German GB = English

    Designation

    Changing the conductor names on the screens

    L1, L2, L3 a, b, c

    > Counter 1 - Limit value 1> Counter 2 - Limit value 2> Counter 3 - Limit value 3> Counter 4 - Limit value 4* Calculation mode: Standard* Current direction: +

    < OK< Abortion

    * Sprache / Language : D

    * Designation L1, L2, L3

    < OK< Abortion

  • Device parameterization Manual for SIMEAS P Power Meter

    Siemens AG 2000; All Rights Reserved Page 31 out of 60-

    4.3.3 Information on SIMEAS

    All device characteristics aredisplayed on one window.

    4.3.4 Date / time

    Only few functions of the SIMEAS Pbasic version require time informationand even there it is not forciblynecessary.

    Oscilloscope Date of calibration

    Since the basic version does notdispose of a battery buffering, timeinformation is reset if the auxiliary energy fails.

    4.3.5 Reset

    Reset Total reset of SIMEAS P All energy values Min Aver Max values Counter limit violations

    Order number: 7KG7000-8AASerial number: BF0101047653Version number: 01.00.12Bus address: 1Date of calibration: 18.01.2000

    < OK

    * Date : 01. 02. 2001

    * Time : 10 : 17 : 57 am

    * 12 / 24h : 12

    < OK< Abortion

    * Total reset of SIMEAS P: No* Reset energy values : No* Reset MinAver-Max : No* Reset alarm counter : No

    < OK< Abortion

  • Device parameterization Manual for SIMEAS P Power Meter

    Siemens AG 2000; All Rights Reserved Page 32 out of 60-

    4.3.6 Screens parameterization

    The contents and display mode ofthe screens can be determined in thiswindow.

    Number of screens

    Between 1 and 20

    Number of screens which can beselected on level 1 via the front buttons.

    Screen interval

    Between 0 and 60 seconds

    0 sec. = fixed screens ( selection only via the front buttons )

    Illumination:

    Between 0 and 99 minutes

    0 Min. = Illumination off99 Min. = Illumination on permanently

    Contrast:

    Between 0 and 9

    * Number of screens : 14* Screen interval : 0 Sec.* Illumination : 99 Min.* Contrast : 5> Screen structure

    < OK< Abortion

  • Device parameterization Manual for SIMEAS P Power Meter

    Siemens AG 2000; All Rights Reserved Page 33 out of 60-

    4.3.6.1 Screen structure

    The contents of the screens can bedetermined in the window "Screenstructure.

    Screen:

    Selection of a screen among thenumber previously determined.

    The contents of the screens areautomatically displayed when switching from one screen to the next.

    Contents:

    The contents of the selected screens can be modified here.

    2 MSV digital 2 MSV digital / analog 4 MSV digital 4 MSV digital / analog Harmonics U / I Min Max values Arrow diagram Oscilloscope sinus / rms values

    If a content is selected, the input of the other characteristics is automaticallydisplayed below this value. E.g. for 4 MSV digital the selection of the 4 measuredvariables with conductor.

    * Screen : 14* Contents : 4 MSV digital* 1 : I L1* 2 : I L2* 3 : I L3* 4 : freq

    < OK< Abortion

  • Profibus DP Manual for SIMEAS P Power Meter

    Siemens AG 2000; All Rights Reserved Page 34 out of 60-

    Profibus DP

    5.1 Introduction .......................................................................................................355.2 General introduction.........................................................................................355.3 SIMEAS P integration into an automation system ........................................37

    5.3.1 Basic setting of SIMEAS P.................................................................................... 375.3.2 Integration via the file ........................................................................................... 38

    5.4 Cyclic data exchange .........................................................................................395.4.1 Basic types for the cyclic data exchange .............................................................. 405.4.2 Overview of the basic types................................................................................... 41

    5.5 Data exchange via PROFIBUS DPV1 .............................................................445.6 Diagnostics .........................................................................................................445.7 Detailed protocol description ...........................................................................45

    5.7.1 Introduction............................................................................................................ 455.7.2 Standard services ................................................................................................... 46

    5.7.2.1 File transfer: From master to slave .................................................................... 465.7.2.2 File transfer: From slave to master .................................................................... 475.7.2.3 Mapping to Profibus-DP.................................................................................... 48

    5.7.3 Device protocol SIMEAS P (layer +).................................................................... 495.7.3.1 Continuous transmission of measured data ....................................................... 495.7.3.2 Basic type 1 ....................................................................................................... 505.7.3.3 Basic type 2 ....................................................................................................... 505.7.3.4 Basic type 3 ....................................................................................................... 50

    5.7.4 Transmission of measured data upon request..................................................... 505.7.5 Parameterization.................................................................................................... 52

    5.7.5.1 Device information ............................................................................................ 535.7.5.2 Measurement information (status) (comfort)..................................................... 535.7.5.3 Send/receive measurement settings ................................................................... 545.7.5.4 Connection setting ............................................................................................. 595.7.5.5 Measured values ................................................................................................ 59

  • Profibus DP Manual for SIMEAS P Power Meter

    Siemens AG 2000; All Rights Reserved Page 35 out of 60-

    5.1 Introduction

    The following chapter contains a description of how the communicationfacilites of the SIMEAS P Power Meter ( 7KG7000-8AA ) are connected.The brief, general introduction on the topics communication andPROFIBUS is followed by chapters providing all relevant informationconcerning the PROFIBUS connection of SIMEAS P. In the annex you will find thePROFIBUS data records in detail.

    5.2 General introductionPROFIBUS- DP is an open, standardized and manufacturer-independ field bussystem. PROFIBUS DP is standardized according to DIN (E) 19424 Part 3 / EN50170 and thus provides the ideal basis required for the high demands posed todata exchange in the domain of distributed peripherals and field devices. Morethan 1000 manufactures to date (date: Sept. 2000) offer more than 1500 productsand user organisations in 23 countries provide technical support for the users ofthe approx. 3 million PROFIBUS nodes installed worldwide.Further integration and connection to common automation concepts is equallyunproblematic since all major manufacturers of programmable logic controllers(PLC) offer PROFIBUS DP master modules and the systems operate nearly inrealtime due to the high transmission rates of up to 12 Mbaud.

    The protocol used for the communication of the PROFIBUS nodes provides for thecommunication between the complex, democratic automation devices (masters)thus enabling each node to accomplish its communication tasks within specifiedtime intervals.Furthermore a cylic data exchange is implemented via the Profibus for thecommunication of a master with the associated simple peripherals (slaves) withsmall effort.

    For this purpose, PROFIBUS relies on a hybrid control system for bus accessconsisting of a central token-passing procedure between the active bus nodes(masters) and one central master-slave procedure for data exchange betweenactive and passive bus nodes.This control system for bus access enables the following system configurations tobe implemented:

    - Pure master-slave system- Pure master-master system with token passing- A system consisting of a combination of both procedures

    5

  • Profibus DP Manual for SIMEAS P Power Meter

    Siemens AG 2000; All Rights Reserved Page 36 out of 60-

    Sensor Drive Actuator Trans - ducerSensor Sensor

    M

    Drive

    M V

    PROFIBUS

    Passive Stations, Slave Devices

    Active Stations, Master Devices

    Locigal Token Ring between the Master Devices

    The figure depicts an example with 3 master modules and 7 slaves. The 3 masterdevices constitute a logic circle. Control of the token is accomplished by the MAC(bus access control). In the start-up phase it generates the token and controls thatonly one token is passed within the logic circle.

    Each slave communicating cyclically via the PROFIBUS is assigned one class-1master. The cyclic data exchange is accomplished according to the DP standardprofile (DPV0). A class-1 master primarily fulfils automation tasks. In addition to thecyclic data exchange a class-1 master can also establish an acyclic communicationconnection to its slaves and thus utilize the expanded functions of a slave.

    A class-2 master is especially appropriate to accomplish commissioning tasks,diagnostics and visualization tasks. It is connected to the PROFIBUS in addition toa class-1 master and can address slaves and exchange data via acyclic services,provided this is permitted by the slaves.

    The acyclic data transmission is accomplished via DPV1. DPV 1 supplements theexisting PROFIBUS standard by several functions. Among others this enables theslave configuration to be modified during running operation and to establish anacyclic data exchange. DPV1 also enables data to be read directly from the slaveby a class-2 master although the slave still entertains a connection to a class-1master.

    A suitable example is represented by the cyclic data exchange between a powermeter and the PLC as class-1 master and the simultaneous acyclic visualizatione.g. by means of the WinCC monitoring system installed on a PC with aPROFIBUS interface (class-2 master).

  • Profibus DP Manual for SIMEAS P Power Meter

    Siemens AG 2000; All Rights Reserved Page 37 out of 60-

    5.3 SIMEAS P integration into an automation system

    5.3.1 Basic setting of SIMEAS PCall the input window "interface in the parameterization menu of SIMEAS P.

    Settings:

    Bus address: 3 to 125Protocol: Profibus

    Specifying the baudrate has nofunction for the protocol Profibus DP.Baudrate is selected via the masterstation. (max. 12Mbit/s)

    * Bus address: 3* Baudrate: 9600 Bd* Protocol: PC RS 485

    < OK< Abortion

    Profibus DPcommunicationof SIMEAS P

    Communication

    (class-1 master)

    Communicationwith the

    (class-2 master)

    Integration asDP standard slave

    Configuration withGSD file and

    master-specific tool

    Operating andmonitoring via

    DPV1 with HMI system(e.g. WinCC)

    Operating andmonitoring and

    diagnostics via DPV1with one additional

    PLC

    PC/PLC

  • Profibus DP Manual for SIMEAS P Power Meter

    Siemens AG 2000; All Rights Reserved Page 38 out of 60-

    5.3.2 Integration via the GSD fileThe configuration of the device parameters is accomplished via a configuration toolwhich each DP standard master contains. If a SIMATC S7 is applied as master,this is the HW Config of the SIMATIC STEP7 package. If it is not a SIMATIC S7,the configuration can be performed in dependence of the master e.g. via COMPROFIBUS.If the GSD file containing the device master data of the power meter has not yetbeen installed, this file must previously be integrated into the configuration tool. Forthis purpose, you can, e.g., copy the GSD file to the subdirectory in which all GSDfiles of the configuration tool are stored and update the device library via thecorresponding menu item. All parameters are stored in the GSD file which must besent by the master during start-up of the slave.

    Subsequently, select the SIMEAS P Power Meter from the device catalog, thedesired basic type and all other parameters, measured variables and addresses ofthe data transmission.

    Via the GSD file the SIMEAS P Power Meter is always integrated as DP standardslave. Optionally, additional data can easily be transmitted also via DPV1 and e.g.parameters can be modified.

    HW Config of STEP7 featuring the integration of a DP slave via GSD file

  • Profibus DP Manual for SIMEAS P Power Meter

    Siemens AG 2000; All Rights Reserved Page 39 out of 60-

    Measured variables in HW Config of STEP7

    5.4 Cyclic data exchangeDuring cyclic data transfer each telegram transfers a specified number of userdata. For this purpose, it must be determined during the configuration of the slave(here SIMEAS P) how many and what data are exchanged cyclically between thepower meter and the PLC. Cyclic data exchange therefore represents the bestoption for transferring information which are required continuously and rapidly. Thetime interval between two values depends on the number of nodes, the datavolume and the baudrate.Subsequent modifications of the data volume during operation are not possible.Therefore, the exclusively cyclic data exchange is very well suited for acommunication that operates with a small volume of user data.

  • Profibus DP Manual for SIMEAS P Power Meter

    Siemens AG 2000; All Rights Reserved Page 40 out of 60-

    5.4.1 Basic types for the cyclic data exchangeDue to the large data volume provided by the SIMEAS P Power Meters, acompromise between the data volume and the performance on the bus had to befound. If the information volume transmitted during data exchange is too large andonly a small amount of the data can be used, the performance of the PROFIBUS isimpaired.Therefore, three basic types are available for efficient and flexible transmission.During configuration this enables the best-suited basic type and the correspondingbus configuration to be selected for the specific application case. Configuration isaccomplished by means of a PROFIBUS configuration tool such as e.g. COMPROFIBUS or HW Config of Simatic S7. The basic types are already pre-assignedand enable a fast commissioning without additional configuration /parameterization.

    Selection of the basic types

    Of course, configuration within one basic type can also be defined by the user.

    Note: Data that is not required permanently can additionally be transmitted viaDPV1.

  • Profibus DP Manual for SIMEAS P Power Meter

    Siemens AG 2000; All Rights Reserved Page 41 out of 60-

    5.4.2 Overview of the basic typesThe following table provides an overview of the basic types including the size andthe division of the information which can be called cyclically by SIMEAS P.

    Byte Basic type1 Basic type 2 Basic type 30-3 Status

    SIMEAS PStatusSIMEAS P

    StatusSIMEAS P

    4-7Data block 1 Data block 1 Data block 1

    8-11Data block 2 Data block 2 Data block 2

    12-15Data block 3 Data block 3 Data block 3

    16-19Data block 4 Data block 4

    20-23Data block 5 Data block 5

    24-27Data block 6 Data block 6

    28-31Data block 7

    32-35Data block 8

    36-39Data block 9

    40-43Data block 10

    44-47Data block 11

    48-51Data block 12

    Overview of the Input Packet Layouts of the different basic types

    If the configuration is modified, the desired data block numbers can be determinedto transmit any information within one basic type.

  • Profibus DP Manual for SIMEAS P Power Meter

    Siemens AG 2000; All Rights Reserved Page 42 out of 60-

    Explanation of the status bytes for SIMEAS P

    Bit number SIMEAS P0 Binary output 11 Binary output 22 Binary output 33 Binary output 44-7 not used8-31 not used

    Status bytes SIMEAS P

    Overview of the input data for SIMEAS P

    Byte Basic type 1, 2 and 30-7 Control bits

    Explanation of the control bits

    Byte number SIMEAS P0 Command ID1-7 Parameters

    Overview of the commands

    Command ID Parameter TypZero command 0x00 --- ---Reset 0x10 Min-Aver-Max = 0x01

    Energy values = 0x02Alarm counter = 0x04

    Bit array 8bit

    Set clock 0x20 Date + time in seconds from 1.1.1980 long

  • Profibus DP Manual for SIMEAS P Power Meter

    Siemens AG 2000; All Rights Reserved Page 43 out of 60-

    A measured value is transmitted as floating-point value in a data block.

    Floating PointFloating Point NumberNotation: Floating-Point (4 octets)Range of Values: see IEEE Std 754 Short Real Number (32 bits)Coding: see IEEE Std 754 Short Real Number (32 bits)

    Coding of Data of Data Type Floating Point

  • Profibus DP Manual for SIMEAS P Power Meter

    Siemens AG 2000; All Rights Reserved Page 44 out of 60-

    5.5 Data exchange via PROFIBUS DPV1PROFIBUS DPV1 is an expansion of the PROFIBUS DP protocol. Devices forPROFIBUS DP and also for PROFIBUS DPV1 can be connected to one line. It isdownward compatible; therefore the PROFIBUS DP protocol and the PROFIBUSDPV1 protocol can run over the same line. Additional data blocks can thus betransmitted acyclically with up to 240 bytes of user data by means of applicationprograms such as STEP7 or WinCC.The PROFIBUS DPV1 protocol thus constitutes the basis for a comfortable dataexchange of e.g. parameter data, diagnostic data, control data, and test data.

    The prerequisite is a DPV1-compatible class-1 master or class-2 master. Theyenable the above mentioned data to be transmitted via an additional establishedchannel.The class-2 master can even establish communication to slaves that are notconfigured and parameterized by this master and which still entertain a connectionto a class-1 master. A class-2 master is especially suitable for commissioning,diagnostics, and visualization tasks e.g. by using the program WinCC.

    5.6 DiagnosticsIf the SIMEAS P Power Meter has problems during data transmission or if animportant status occurs in the power meter, it generates a high-priority diagnostictelegram. The master collects this high-priority diagnostic telegram as soon aspossible, thus enabling the user to react fast if critical states occur.

    For a Simatic S7 this diagnostic telegram initiates a diagnosis alarm and the objectblock (OB82) responsible for the processing of diagnosis alarms is invoked. If theobject block is not programmed, the alarm indication is not processed and the PLCenters the Stop mode. If the object block is programmed, the alarm indication canbe evaluated and subsequent actions and indications for the user can be initiated.

  • Profibus DP Manual for SIMEAS P Power Meter

    Siemens AG 2000; All Rights Reserved Page 45 out of 60-

    5.7 Detailed protocol description

    5.7.1 Introduction

    A protocol for SIMEAS P (power meter) via Profibus DP V1 will be defined in thefollowing. This protocol is used for different purposes. Among others, the protocolsupports the parameterization as required by the end user, the calibration, thecollection of measured values and the final testing of the device.The individual layers required for providing the communication services accordingto the ISO-OSI reference model will be explained.

    Layer 1: according to ProfibusLayer 2: according to ProfibusLayer 3-7: not relevantLayer +: DP profile: device functionality of SIMEAS P

    7

    6

    5

    4

    3

    2 (data link layer)1 (physical layer)

    + SIMEAS P

    DP Functionality

    Layerwise subdivison of the communication services

    Physical layer

    The physical layer is designed according to Profibus DP (RS485).

    Data link layer

    The link layer is designed according to Profibus DP.

  • Profibus DP Manual for SIMEAS P Power Meter

    Siemens AG 2000; All Rights Reserved Page 46 out of 60-

    5.7.2 Standard services

    Standardized services for the application layer are described which are currentlylimited to the file transfer as the sole service. The file transfer is defined in the twodirections of data transfer. From the master (controlling station) to the slave(controlled station) and vice versa. The definition is in accordance with theIEC 870-5-5 file transfer.

    5.7.2.1 File transfer: From master to slave

    Application function ofmaster

    Application function ofslave

    Communicationservices

    A_FILE_READY.Send

    A_SECTION1_Segment1.Send

    A_FILE_READY.Ind

    Confirm (ACK/NACK)

    A_SECTION1_Segment1.IndA_SECTION1_Segment1.Conf

    Confirm (ACK/NACK)A_SECTION1_Segment2.Send

    A_SECTION1_Segment2.Ind

    A_SECTIONn_Segment1.SendA_SECTIONn_Segment1.Ind

    A_SECTIONn_Segmentm.SendA_SECTIONn_Segmentm.Ind

    Confirm (ACK/NACK)A_SECTIONn_Segmentm.Conf

    A_EOF.SendA_EOF.ind

    Confirm (ACK/NACK)A_EOF.Conf(ACK/NACK)

    A_FILE_READY.Conf(ACK/ NACK)

  • Profibus DP Manual for SIMEAS P Power Meter

    Siemens AG 2000; All Rights Reserved Page 47 out of 60-

    Description:File transfer is used here to transmit data from the master to the slave. The mastersubdivides the file into sections. Each section can be further divided into segments.If no data is available for sending, the master does not send aSectionN_SegmentM telegram and the A_EOF telegram follows directly after theconfirmation A_File_Ready.

    Corrupted data:If the master detects an error in the data received it responds by sending NACK.The slave then repeats the telegram. If the slave does not send a response, themaster repeats the sending of the telegram after a certain period of time (timeout).

    5.7.2.2 File transfer: From slave to master

    Application function ofslave

    Application function ofmaster

    Communicationservices

    A_SELECT_FILE.Conf (ACK/NACK)

    A_File_READY.respond

    Confirm (ACK/NACK)

    A_Data.indA_Data.request (0)

    A_File_READY.indA_Data.request (1)

    A_Data.ind

    A_SECTION1_SEGMENT1.respA_SECTION1_SEGMENT1.ind

    A_SECTIONM_SEGMENTn.respA_SECTIONM_SEGMENTn.ind

    A_Data.indA_DATA.request (n)

    A_EOF.respondA_EOF.ind

    A_SELECT_FILE.indA_SELECT_FILE.Send

  • Profibus DP Manual for SIMEAS P Power Meter

    Siemens AG 2000; All Rights Reserved Page 48 out of 60-

    Description:

    This file transfer is used to receive data from the slave. The master subdivides thefile into sections. Each section can be further divided into segments. If the slavehas no data to send, no SectionN_SegmentM telegram is sent and the A_EOFtelegram follows immediately after the confirmation A_File_Ready. The datarequest contains a counter number which is incremented by 1 for eachtransmission step. The counting starts at 0. When the maximum value has beenachieved, the counter number is reset to 0.

    Corrupted data:If the slave detects an error in the telegrams received, it responds by sendingNACK. The master then repeats the telegram. If the slave does not send aresponse, the master repeats the request after a certain period of time (timeout).Timeouts are defined independently of each other for each telegram.

    5.7.2.3 Mapping to Profibus-DPThe standard for Profibus DP does not provide a service that is directly comparableto file transfer. The nature of file transfer is the bitwise transmission of larger datavolumes upon request. This contradicts the operating principle of Profibus to agreat deal. Originally, Profibus DP performed only cyclic data transmission of aspecified length; the expansions (DPV1), however, at least enable acyclic datatransmission upon request. These are, however, restricted to a permanentlyassigned address space of 64kB. For this reason a file transfer is established bymeans of the available services. However, it cannot be assumed that this filetransfer is supported by standards-compatible application software on the masteras a standard feature. File transfer under Profibus is thus only suitable forapplication services with an optional structure (they can also be renounced) orredundant (standards-compatible support is also available).The file transfer on Profibus DP relies on acyclic data transmission (MSAC1 orMSAC2 , API=0). Competence for this service is assumed by slot 0, index 240whose assignment corresponds to the telegram structure in "Maintenance protocolASCII" (see Fehler! Verweisquelle konnte nicht gefunden werden.).The communication procedures SEND/CONFIRM or REQUEST/RESPOND of theASCII protocol are mapped to the services DDLM_Rd_Outp/ DDLM_Rd_Inp of theProfibus protocol. All requests to a slave are thus mapped by writing a data block(0.240) and the responses from the device by reading a data record (0.240).

  • Profibus DP Manual for SIMEAS P Power Meter

    Siemens AG 2000; All Rights Reserved Page 49 out of 60-

    5.7.3 Device protocol SIMEAS P (layer +)

    5.7.3.1 Continuous transmission of measured data

    The cyclic transmission of measured data to the master is accomplished via theProfibus service MSCY1. To enable weighing with respect to performance or busload and information needs, different sizes can be selected for data transmissionpackets. These so-called basic types define the size and the contents of requestpacket and response packet. 3 different basic types are available. They can beselected within the Profibus configuration tool.For each basic type specific information elements are defined which can constitutea part of the request packet or the response packet.

    Commands can be sent to SIMEAS P.Structure (8 bytes)

    Byte 7 6 5 4 3 2 1 0Content

    Commands understood by SIMEAS PCommand ID Parameter TypeZero command 0x00 --- ---Reset 0x10 Min-Aver-Max = 0x01

    Energy values = 0x02Alarm counter = 0x04

    Bit array 8bits

    Set clock 0x20 Date + time in seconds long

    Example:Set time to 00:10:00 of 1.1.1980: 0x20,0x58,0x02,0x00,0x00,0x00,0x00,0x00Reset alarm counter and energy counter: 0x10,0x06,0x00...

    Status information is supplied by the device. The status of the binary outputs (BOx)is communicated instantaneously.Structure (4 bytes)

    Byte 3.7 3.6 3.5 3.4 3.3 3.2 3.1 3.0 2 1 0Content BO1 BO2 BO3 BO4 -- -- -- -- -- -- --

    A measured value is transmitted as floating-point value in a data block.Structure (4 bytes)

  • Profibus DP Manual for SIMEAS P Power Meter

    Siemens AG 2000; All Rights Reserved Page 50 out of 60-

    5.7.3.2 Basic type 1Request = { }Response = { , {}3}

    5.7.3.3 Basic type 2Request = { }Response = { , {}6}

    5.7.3.4 Basic type 3Request = { }Response = { , {}12}

    5.7.4 Transmission of measured data upon requestAcyclic data transmission via addressing to slot and index.Via the slot the individual modules of modular devices are addressed. Slot 0identifies the device as a whole. SIMEAS P is a compact device and therefore it isaddressed exclusively via slot 0.The meaning of the data records which are distinguished via the index is statedbelow.

    DS 93 CommandsGroup Byte Type MeaningCommands 0 8 Byte see 5.7.3.1

    DS 94 Measured values (main group)Group Byte Type Measuring pointsVoltage 0 float L1,L2,L3

    L12,L23,L31NE,SUM

    Current 32 float L1,L2,L3,SUMMains frequency 48 floatActive output 52 float L1,L2,L3,SUMReactive output 68 float L1,L2,L3,SUMApparent output 84 float L1,L2,L3,SUMPerformance factor 100 float L1,L2,L3,SUMActive factor 116 float L1,L2,L3,SUMPhase angle 132 float L1,L2,L3,SUM

    Note: The measured variables are transmitted individually and successively asfloating-point values named according to the measuring points. 37 measuredvalues are thus transmitted via this data block.

  • Profibus DP Manual for SIMEAS P Power Meter

    Siemens AG 2000; All Rights Reserved Page 51 out of 60-

    DS 160 Measured values (1. subgroup)Group Byte Type Measuring pointsVoltage symmetry 0 float ---Current symmetry 4 float ---Harmonic distortion voltage 8 float L1,L2,L3Harmonic distortion current 20 float L1,L2,L3Harmonic voltage 32 float L1 5,7,11,13,17,19

    L2 5,7,11,13,17,19L3 5,7,11,13,17,19

    Harmonic current 122 float L1 5,7,11,13,17,19L2 5,7,11,13,17,19L3 5,7,11,13,17,19

    Note: The measured variables are transmitted individually and successively asfloating-point values named according to the measuring points. ?? measuredvalues are thus transmitted via this data block.

    DS 161 Measured values (2. subgroup)Group Byte Type Measuring pointsEnergy 0 float EPP, EPS, EQI, EQC, ES,

    EPT, EPNCounter limit violations 1,2,3,4

    Note: The measured variables are transmitted individually and successively asfloating-point values named according to the measuring points. 11 measuredvalues are thus transmitted via this data block.

    DS 94 DS 100 device identificationOverview

    Group Byte Type Function0..239 Byte

    DS 97 Device identificationDetail

    Group Byte Type Function0 char MLFB (machine-readable

    product designation)25 char Serial number45 long FW version

    Date of calibration 49 char Date ddmmyyyy57 char Time hhmm

  • Profibus DP Manual for SIMEAS P Power Meter

    Siemens AG 2000; All Rights Reserved Page 52 out of 60-

    5.7.5 Parameterization

    File format PROFILE

    File Transfer enables data volumes to be transmitted which are flexible in theirsize. The structuring of these data volumes is not further defined. A file format isnow defined which will be used frequently in the following. It is the objective toestablish a data structure which can be expanded flexibly and which enables ahigh degree of interoperability between the software (parameterization software,evaluation software etc.) and SIMEAS P hardware of different versions. The modelfor this structure are files in the format of a Windows *.INI file (Windows 3.xProfiles).Each octet is of the data type ASCII and not "case sensitive". A file is transmittedas sections1 (SECTIONS defined by key words in square brackets []).Syntax:

    The description of the information elements is accomplished sectionwise. For eachsection (SECTION) the contents and the data types used are described.Each section contains its name at the beginning. This serves as a first structuringof the information elements. The content of the section is indicated in each line bythe individual information elements in the form:Key =ValueEach line must be terminated by an end-of line-identifier CHAR(0).Data types are put in brackets . They are not transmitted as plain textbut serve as wildcard for a value whose data type is indicated by the qualifier within. Standard data types such as , etc. are explained atthe end of this paragraph. Data types in curly brackets { and } indicate thatseveral values of the data type separated by a comma can be entered.

    Example: ={}become e.g. U=L1,L2.L12,L31 or I=L1,L2

    Not every information element must be available in future versions of a concretedata format or information elements might be added in the future. To handle thesemodifications with the appropriate flexibility, the following is defined:An information element whose name is unknown or not supported will be ignored.

    An information element for which a row with the corresponding name cannot befound, is assigned a default value if possible.

    Comments can be limited by a semicolon. If a semicolon is set, the remainder ofthe line is regarded as a comment.

    General data types:FIXED : Fixed-point number, only figuresFLOAT : Floating-point number, with point as separator, without

    exponentBOOL : 0=FALSE/OFF, 1=TRUE/ONDATE : tt.mm.yyyy

    1 Sections of the file format PROFILE and of the File Transfer do not necessarily have to be

    equivalent.

  • Profibus DP Manual for SIMEAS P Power Meter

    Siemens AG 2000; All Rights Reserved Page 53 out of 60-

    TIME : hh:m(in)m(in)STRING: character string (no special interpretation)

    5.7.5.1 Device informationFile transfer (Name of file = 05)File format Profile

    SECTION: [DeviceInformation]

    Contents:[DeviceInformation]MLFB=SerialNr=FWVersion=CalibrationDate=CalibrationValues=

    Data types: MLFB (can be sent) (can be sent) Firmware-Version (xx.xx.xx) STRING (z.B.: UL1L2L3=450V U0=110V IL1L2L3=2Af=50Hz)

    5.7.5.2 Measurement information (status) (comfort)This functionality becomes relevant in the comfort version only.File transfer (Name of file = 06)File format Profile

    SECTION: [MeasurementInformation]

    Contents[MeasurementInformation]

  • Profibus DP Manual for SIMEAS P Power Meter

    Siemens AG 2000; All Rights Reserved Page 54 out of 60-

    5.7.5.3 Send/receive measurement settings

    File transfer (Name of file = 01)File format ProfileThe parameter names and their values (syntax and semantics) are explained in thefollowing paragraph. It is assumed that the basic meaning of each parameterbecomes evident by its name. The basis for the definition is established by theindications [R1] (compare reference directory at the beginning of the document).The following sections are used:

    [Country][ProcessLink][BinaryOutput1] [BinaryOutput2][Screens]

    Comfort:[BinaryInput][AnalogInput][AnalogOutput]SECTION: [Country]

    Contents:[Country]Language=LineDescriptor=

    Data types: FIXED (Code)German = GREnglish = UKUS-English= USFrench = FRSpanish = ESItalian = IT FIXED (Code)L1,L2,L3 = L123a,b,c = ABC

    SECTION: [ProcessLink]

    Contents:[ProcessLink]Type=Frequency= in Hz // received by device onlyNomVolt=WithConvU=WithConvI=ConvUPrim=ConvUSec=ConvIPrim=

  • Profibus DP Manual for SIMEAS P Power Meter

    Siemens AG 2000; All Rights Reserved Page 55 out of 60-

    ConvISec=

    Data types: FIXED (Code)

    1-phase = 13-conductor uniform load = 23-conductor any load (2*I) = 33-conductor any load (3*I) = 44-conductor uniform load = 54-conductor any load = 6

    Float in V Float in A Float in V Float in V Float in A Float in A

    SECTION: [Condition1] to [Condition6]

    Contents:Trigger=,,,{,,,}TriggerPulse= in sTriggerHysteresis= in % see Table 1: Measured variables (Coding and data types)

    Overshoot = GTUndershoot = LT

    FLOAT in SI units

    AND operation = *OR operation = +

    Example for limit value conditionsTrigger = UL1,GT,100,*,IL1,GT,1,+,PL1,GT,100i.e.: ((voltage L1 > 100 volt) and (current L1 > 1A)) or (active output L1 > 100 watt)

  • Profibus DP Manual for SIMEAS P Power Meter

    Siemens AG 2000; All Rights Reserved Page 56 out of 60-

    SECTION: [BinaryOutput1] oder [BinaryOutput2]

    Contents:[BinaryOutput1] || [BinaryOutput2]Mode=Energy=EnergyValue= in kWh/ImpulsEnergyPulse= in sTrigger=Data types: FIXED (Code)Off = 1Device active = 2Energy = 3Threshold = 4 referenced condition in section [Condition]

    SECTION: [Screen]

    Contents:[Screen]StatusLine=Interval= secondsIlluminationTime= secondsContrast=ScreenCount=ScreenType=ScreenQuantity=ScreenQuantityMin=ScreenQuantityMax=

    Data types Index of Screens 1..ScreenCount (max. 20)

    Index of measured variables 1..n (dependingon indication type)

    2 Measured values digital = D2 (2 variables)2 Measured values analog = A2 (2 variables)4 Measured values digital =D4 (4 variables)4 Measured values analog = A4 (4 variables)Harmonics = HU oder HI (fixed variables)Min-Max =MinMax8 (8 variables)Arrow diagram = P (fixed variables)Curve shape = C1 (1 variable)

  • Profibus DP Manual for SIMEAS P Power Meter

    Siemens AG 2000; All Rights Reserved Page 57 out of 60-

    Table 1: Measured variables (Coding and data types)Measured variable ID SI unit

    Voltage 400 U L1,L2,L3L12,L23,L31NE,SUM

    V

    Current 401 I L1,L2,L3,SUM A

    Mains frequency 402 f ------ Hz

    Active output 403 P L1,L2,L3,SUM W

    Reactive output 404 Q L1,L2,L3,SUM VA

    Apparent output 405 S L1,L2,L3,SUM var

    Power factor 406 PF L1,L2,L3,SUM none

    Active factor 407 COSPHI L1,L2,L3,SUM none

    Phase angle 408 PHI L1,L2,L3,SUM degree

    Voltage symmetry 410 SYMU ------ percent

    Current symmetry 411 SYMI ------ percent

    Harmonic distortionvoltage

    430 THDU L1,L2,L3 percent

    Harmonic distortioncurrent

    440 THDI L1,L2,L3 percent

    Harmonic voltage 500 HU L1,L2,L3 1..n percentHarmonic current 550 HI L1,L2,L3 1..n percentEnergy 600 EPP, EPS,

    EQI, EQC,ES, EPT,EPN

    SUM ---

    Counter limit violations 700 CT 1,2,3,4 ---

    EPT = Energy absolute basing on output P (export/import)EPN = Energy balance basing on output PEPP = Energy basing on output P importEPS = Energy basing on output P exportEQI = Energy basing on output a Q inductiveEQC = Energy basing on output Q capacitiveES = Energy basing on output S

    Index calculationHarmonics Energy Other variablesIndex = ID + -1SubIndex =

    Index = ID + SubIndex =

    Index = IDSubIndex =

    1..8: L1,L2,L3,L12,L23,L31,SUM,NE 0..6: EPP,EPS,EQI,EQC,ES,EPT,EPN

  • Profibus DP Manual for SIMEAS P Power Meter

    Siemens AG 2000; All Rights Reserved Page 58 out of 60-

    Example of a parameter INI file:

    [Country]Language=GR ; German versionLineDescriptor=L123 ; onductors are designated 1,L2,L3[ProcessLink]Type=5 ; 4-conductor any loadFrequency=50 ; 50 HzNomVolt=230 ; rated voltage 230 voltWithConvU=0WithConvI=0 ; without transducerConvUPrim=10000 ; remember transducer values neverthelessConvUSec=100 ; 10 to.1 kVConvIPrim=500ConvISec=5 : 500 to 5 ampere[ProcessLink]Type = 3 ;Frequency = 50NomCurr=3NomVolt = 230WithConvU=0WithConvI=1ConvIPrim = 10ConvISec = 1[BinaryOutput1]Mode= 3; ; Energy pulsesEnergy= EPNET ; Energy balanceEnergyValue=10 ; 10 kWh/pulseEnergyPulse=0.2 ; 200 msTrigger = UL1GT100*IL1GT1+PL1GT100 ; 3 limit valuesTriggerPulse=5 ; 5 secondsTriggerHysteresis= 0.5 ; 0.5 % hysteresis[BinaryOutput2]Mode= 1; ; OffEnergy= EPN ; Energy balanceEnergyValue=10 ; 10 kWh/pulseEnergyPulse=0.2 ; 200 msTrigger = UL1GT100*IL1GT1+PL1GT100 ; 3 limit valuesTriggerPulse=5 ; 5 secondsTriggerHysteresis= 0.5 ; 0.5 % hysteresis[Screen]StatusLine=1 ; Status line is displayedInterval=1 ; Screen displayed for 1 secondIlluminationTime=5 ; 5 secondsContrast=8 ; Contrast set to 8ScreenCount=2 ; 2 displays (screens)Screen1Type=A2Screen1Quantity1=UL1Screen1Quantity2=IL1Screen1Quantity1Min=210Screen1Quantity1Max=250 ; 210..250 VScreen1Quantity2Min=0Screen1Quantity2Max=5 ; 0..5 AScreen2Type=HU

  • Profibus DP Manual for SIMEAS P Power Meter

    Siemens AG 2000; All Rights Reserved Page 59 out of 60-

    5.7.5.4 Connection setting

    File transfer (file name = 02 )File format Profile

    SECTION: [CommunicationLink]

    Contents:[CommunicationLink]ModemInitString=DirectCableConnection=Baudrate=StartProtcol=

    Data types: in inverted commas (z.B.: "ATQ0V0X3S0=1CR") FIXED (Code)

    Maintenance protocol = 0Operating protocol = 1

    5.7.5.5 Measured values

    Transfer

    File transfer (file name = 03 )Contents:Binary values with fixed format

    BYTE Format type (with time information = 1 else 0)WORD IndexBYTE SubIndexfloat Measured value3 BYTE Minutes from 1.1.19992 BYTE msec Offset

    Reset values

    SEND/CONFIRMSTX 0 M R 0 0 0 1D1PS1 PS2 PS3 ETXD1 FIXED (Code)

    Counter values = 1Min-Max values = 2Instantaneous value= 3

  • Profibus DP Manual for SIMEAS P Power Meter

    Siemens AG 2000; All Rights Reserved Page 60 out of 60-

    Set clock

    SEND/CONFIRM

    STX A1 A2 T 0 0 1 4D1z D1e M1z M1e Y1t Y1h Y1z Y1eH2z H2e M2z M2e S2z S2ePS1 PS2 PS3 ETX

    D,M,Y1 Date in the form of DD.MM.YYYY (Day, Month, Year)H,M,S2 Time in the form of HH.MM.SS (Hours, Minutes, Seconds)


Recommended