06-2015 RI8PG302 INSTRUCTIONS AK-CC 250A Data communication MOD-BUS: Coordinated defrost t amb = 0 - +55°C 230 V a.c. 50/60 Hz 2.5 VA CE (250 V a.c.) UL *** (240 V a.c.) DO1. Refrigeration * 8 (6) A 10 A Resistive 5FLA, 30LRA DO2. Defrost * 8 (6) A 10 A Resistive 5FLA, 30LRA DO3. Fan or refrigeration 2 * 6 (3) A 6 A Resistive 3FLA, 18LRA 131 VA Pilot duty DO4. Alarm, light, rail heat or hotgas defrost * 4 (1) A Min. 100 mA** 4 A Resistive 131 VA Pilot duty * DO1 and DO2 are 16 A relays. DO3 and DO4 are 8 A relays. Max. load must be keept. ** Gold plating ensures make function with small contact loads *** UL-approval based on 30000 couplings 10 V < U < 256 V No Function Pt /PTC sensors See page 6.
Transcript
Page 1: Instructions AK-CC 250A€¦ · ** Gold plating ensures make function with small contact loads *** UL-approval based on 30000 couplings 10 V < U < 256 V No Function ... Temperature

06-2015 RI8PG302

INSTRUCTIONS

AK-CC 250A

Data communication MOD-BUS: Coordinated defrost

tamb = 0 - +55°C

230 V a.c. 50/60 Hz

2.5 VA

CE (250 V a.c.) UL *** (240 V a.c.)

DO1. Refrigeration * 8 (6) A10 A Resistive5FLA, 30LRA

DO2. Defrost * 8 (6) A10 A Resistive5FLA, 30LRA

DO3. Fan or refrigeration 2 *

6 (3) A6 A Resistive3FLA, 18LRA131 VA Pilot duty

DO4. Alarm, light, rail heat or hotgas defrost *

4 (1) AMin. 100 mA**

4 A Resistive131 VA Pilot duty

* DO1 and DO2 are 16 A relays. DO3 and DO4 are 8 A relays. Max. load must be keept.** Gold plating ensures make function with small contact loads*** UL-approval based on 30000 couplings

10 V < U < 256 V

NoFunction

Pt /PTC sensors

See page 6.

Page 2: Instructions AK-CC 250A€¦ · ** Gold plating ensures make function with small contact loads *** UL-approval based on 30000 couplings 10 V < U < 256 V No Function ... Temperature

2 Instructions RI8PG302 © Danfoss 06/2015 AK-CC 250A

1 2

3 4

5 6

o61 — Electrical connections

7 8

9 10

Dan

foss

84B2

428.

12

Dan

foss

84B2

429.

13

Dan

foss

84B2

430.

13

*) DI1, DI2: AU: Guld, Gold, Or, Oro l = max. 15 m

*)*)

*)

*) *)

*)*)

*) *)

! ! !

*)

Page 3: Instructions AK-CC 250A€¦ · ** Gold plating ensures make function with small contact loads *** UL-approval based on 30000 couplings 10 V < U < 256 V No Function ... Temperature

AK-CC 250A Instructions RI8PG302 © Danfoss 06/2015 3

Setting:

1 Open parameter r12 and stop the regulation

2 Open parameter o06 and set the used sensor type

3 Select electric connection based on the draw-ings on page 2

4 Open parameter o61 and set the electric con-nection number in it

5 Now select one of the preset settings from the table on the right-hand side

6 Open parameter o62 and set the number for the array of presettings

7 Open parameter r12 and start the regulation

8 Go through the survey of factory settings. Make any necessary changes in the respective parameters.

9 For network. a. Set the address in o03 b. Start scan function in the system unit.

Auxiliary table for settings(quick-setup)

Case Room

Defrost stop on

time

Defrost stop on S5

Defrost stop on

time

Defrost stop on S5

Preset settings (o62) 1 2 3 4 5 6

Temperature (SP) 4°C 2°C -24°C 6°C 3°C -22°CMax. temp. setting (r02) 6°C 4°C -22°C 8°C 5°C -20°CMin. temp. setting (r03) 2°C 0°C -26°C 4°C 1°C -24°CSensor signal for thermostat. S4% (r15) 100% 0%Alarm limit high (A13) 10°C 8°C -15°C 10°C 8°C -15°CAlarm limit low (A14) -5°C -5°C -30°C 0°C 0°C -30°CSensor signal for alarm funct.S4% (A36) 100% 0%Interval between defrost (d03) 6 h 6h 12h 8h 8h 12hDefrost sensor: 0=time, 1=S5, 2=S4 (d10) 0 1 1 0 1 1DI1 config. (o02) Case cleaning =10 Door function =3Sensor signal for display view S4% (017) 100% 0%

Array 1-6: The settings in the grey fields will be changed

English

Parameters EL-diagram number (page 2) Min.-value

Max.-value

Factory setting

Actual settingFunction Codes 1 2 3 4 5 6 7 8 9 10

Normal operationTemperature (set point) --- -50.0°C 50.0°C 2.0°CThermostatDifferential *** r01 0.0 K 20.0K 2.0 KMax. limitation of stepson setting *** r02 -49.0°C 50°C 50.0°CMin. limitation of set point setting *** r03 -50.0°C 49.0°C -50.0°CAdjustment of temperature indication r04 -20.0 K 20.0 K 0.0 KTemperature unit (°C/°F) r05 °C °F °CCorrection of the signal from S4 r09 -10.0 K +10.0 K 0.0 KCorrection of the signal from S3 r10 -10.0 K +10.0 K 0.0 KManual service, stop regulation, start regulation (-1, 0, 1) r12 -1 1 0Displacement of reference during night operation r13 -10.0 K 10.0 K 0.0 KDefinition and weighting, if applicable, of thermostat sensors - S4% (100%=S4, 0%=S3)

r15 0% 100% 100%

The heating function is started a number of degrees below the thermostats cutout temperature

r36 -15.0 K -3.0 K -15.0 K

Activation of reference displacement r40 r39 OFF ON OFFValue of reference displacement (activate via r39 or DI) r40 -50.0 K 50.0 K 0.0 KAlarmDelay for temperature alarm A03 0 min 240 min 30 minDelay for door alarm *** A04 0 min 240 min 60 minDelay for temperature alarm after defrost A12 0 min 240 min 90 minHigh alarm limit *** A13 -50.0°C 50.0°C 8.0°CLow alarm limit *** A14 -50.0°C 50.0°C -30.0°CAlarm delay DI1 A27 0 min 240 min 30 minAlarm delay DI2 A28 0 min 240 min 30 minSignal for alarm thermostat. S4% (100%=S4, 0%=S3) A36 0% 100% 100%CompressorMin. ON-time c01 0 min 30 min 0 minMin. OFF-time c02 0 min 30 min 0 minTime delay for cutin of comp.2 c05 0 sec 999 sec 0 secCompressor relay 1 must cutin and out inversely(NC-function)

c30 0OFF

1ON

0OFF

DefrostDefrost method (none/EL/GAS/BRINE) d01 no bri ELDefrost stop temperature d02 0.0°C 25.0°C 6.0°CInterval between defrost starts d03 0 hours 48 hours 8 hoursMax. defrost duration d04 0 min 180 min 45 minDisplacement of time on cutin of defrost at start-up d05 0 min 240 min 0 minDrip off time d06 0 min 60 min 0 minDelay for fan start after defrost d07 0 min 60 min 0 minFan start temperature d08 -15.0°C 0.0°C -5.0°CFan cutin during defrost0: Stopped1: Running2: Running during pump down and defrost

d09 0 2 1

Defrost sensor (0=time, 1=S5, 2=S4) d10 0 2 0Pump down delay d16 0 min 60 min 0 minDrain delay d17 0 min 60 min 0 minMax. aggregate refrigeration time between two defrosts d18 0 hours 48 hours 0 hoursDefrost on demand - S5 temperature’s permitted variation dur-ing frost build-up. On central plant choose 20 K (=off)

d19 0.0 K 20.0 k 20.0 K

Delay of hot gas injection d23 0 min 60 min 0 min

Page 4: Instructions AK-CC 250A€¦ · ** Gold plating ensures make function with small contact loads *** UL-approval based on 30000 couplings 10 V < U < 256 V No Function ... Temperature

4 Instructions RI8PG302 © Danfoss 06/2015 AK-CC 250A

1 2 3 4 5 6 7 8 9 10FanFan stop at cutout compressor F01 no yes noDelay of fan stop F02 0 min 30 min 0 minFan stop temperature (S5) F04 -50.0°C 50.0°C 50.0°CHACCPActual temperature measurement for the HACCP function h01Last registered peak temperature h10Selection of function and sensor for the HACCP function. 0 = no HACCP function. 1 = S4 used (maybe also S3). 2 = S5 used

h11 0 2 0

Alarm limit for the HACCP function h12 -50.0°C 50.0°C 8.0°CTime delay for the HACCP alarm h13 0 min. 240 min. 30 min.Select signal for the HACCP function. S4% (100% = S4, 0% = S3) h14 0% 100% 100%Real time clockSix start times for defrost. Setting of hours. 0=OFF

t01-t06 0 hours 23 hours 0 hours

Six start times for defrost.Setting of minutes.0=OFF

t11-t16 0 min 59 min 0 min

Clock - Setting of hours *** t07 0 hours 23 hours 0 hoursClock - Setting of minute *** t08 0 min 59 min 0 minClock - Setting of date *** t45 1 31 1Clock - Setting of month *** t46 1 12 1Clock - Setting of year *** t47 0 99 0MiscellaneousDelay of output signals after start-up o01 0 s 600 s 5 sInput signal on DI1. Function:0=not used. 1=status on DI1. 2=door function with alarm when open. 3=door alarm when open. 4=defrost start (pulse-pres-sure). 5=ext.main switch. 6=night operation 7=change refer-ence (activate r40). 8=alarm function when closed. 9=alarm function when open. 10=case cleaning (pulse pressure). 11=forced cooling at hot gas defrost.

o02 1 11 0

Network address (0=off) o03 0 240 0Access code 1 (all settings) o05 0 100 0Used sensor type. See page 6.Pt: Pt 1000 Ω @ 0°CP01: PTC 1000 Ω (nominal 990 Ω) = EKS 111P02: PTC 1000 Ω @ 25°C (nominal 1000 Ω)

o06 Pt P02 Pt

Display step = 0.5 (normal 0.1 at Pt sensor) o15 no yes noMax hold time after coordinated defrost o16 0 min 60 min 20Select signal for display view. S4% (100%=S4, 0%=S3) o17 0% 100% 100%Input signal on DI2. Function: (0=not used. 1=status on DI2. 2=door function with alarm when open. 3=door alarm when open. 4=defrost start (pulse-pres-sure). 5=ext. main switch 6=night operation 7=change refer-ence (activate r40). 8=alarm function when closed. 9=alarm function when open. 10=case cleaning (pulse pressure). 11=forced cooling at hot gas defrost.). 12=coordinated defrost)

o37 0 12 0

Configuration of light function (relay 4)1=ON during day operation. 2=ON / OFF via data communica-tion. 3=ON follows the DI-function, when DI is selected to door function or to door alarm

o38 1 3 1

Activation of light relay (only if o38=2) o39 OFF ON OFFRail heat On time during day operations o41 0% 100% 0Rail heat On time during night operations o42 0% 100% 0Rail heat period time (On time + Off time) o43 6 min 60 min 10 minCase cleaning. 0=no case cleaning. 1=Fans only. 2=All output Off.

*** o46 0 2 0

Selection of EL diagram. See overview page 2 * o61* 1 10 1Download a set of predetermined settings. See overview previous page.

* o62* 0 6 0

Access code 2 (partly access) *** o64 0 100 0Save the controllers present settings to the programming key. Select your own number.

o65 0 25 0

Load a set of settings from the programming key (previously saved via o65 function)

o66* 0 25 0

Replace the controllers factory settings with the present set-tings

o67 OFF On OFF

ServiceStatus codes are shown on page 5 S0-S33Temperature measured with S5 sensor *** u09Status on DI1 input. on/1=closed u10Temperature measured with S3 sensor *** u12Status on night operation (on or off) 1=closed *** u13Temperature measured with S4 sensor *** u16Thermostat temperature u17Read the present regulation reference u28Status on DI2 output. on/1=closed u37Temperature shown on display u56Measured temperature for alarm thermostat u57Status on relay for cooling ** u58Status on relay for fan ** u59

Page 5: Instructions AK-CC 250A€¦ · ** Gold plating ensures make function with small contact loads *** UL-approval based on 30000 couplings 10 V < U < 256 V No Function ... Temperature

AK-CC 250A Instructions RI8PG302 © Danfoss 06/2015 5

*) Can only be set when regulation is stopped (r12=0)**) Can be controlled manually, but only when r12=-1***) With access code 2 the access to these menus will be limited

SW = 2.3x

Factory settings are indicated for standard units. Other code numbers have custom-ized settings.

Fault code display Alarm code display Status code displayE 1 Fault in controller A 1 High temperature alarm S0 RegulatingE 6 Change battery + check clock A 2 Low temperature alarm S 1 Waiting for end of the coordinated defrost

E 25 S3 sensor error A 4 Door alarm S 2 ON-time CompressorE 26 S4 sensor error A 5 Max. Hold time S 3 OFF-time CompressorE 27 S5 sensor error A 15 DI 1 alarm S 4 Drip-off time

A 16 DI 2 alarm S 10 Refrigeration stopped by main switchA 45 Standby mode S 11 Refrigeration stopped by thermostatA 59 Case cleaning S 14 Defrost sequence. DefrostingA 60 HACCP alarm S 15 Defrost sequence. Fan delay

S 17 Door open (open DI input)S 20 Emergency coolingS 25 Manual control of outputsS 29 Case cleaningS 30 Forced coolingS 32 Delay of output at start-upS33 Heat function r36 is activenon The defrost temperature cannot be dis-

played. There is stop based on time-d- Defrost in progressPS Password required

The buttons

Set menu1. Push the upper button until a parameter

r01 is shown2. Push the upper or the lower button and

find that parameter you want to change3. Push the middle button until the

parameter value is shown4. Push the upper or the lower button and

select the new value5. Push the middle button again to enter

the value.

Cutout alarm relay / receipt alarm/see alarm code • Push short the upper button

Set temperature1. Push the middle button until the

temperature value is shown2. Push the upper or the lower button and

select the new value3. Push the middle button to select the

setting.

Reading the temperature at defrost sensor• Push briefly the lower button

Manuel start or stop of a defrost• Push the lower button for four seconds.

(Though not for application 4).

See HACCP registration1. Give the middle button a long push until

h01 appears2. Select required h01-h103. See value by giving the middle button a

short push

LED

Light emitting diode = refrigeration = defrost = fan running

Flashes fast at alarm

HACCPHACCP function is active

Status on relay for defrost ** u60Status on relay for rail heat ** u61Status on relay for alarm ** u62Status on relay for light ** u63Status on relay for valve in suction line ** u64Status on relay for compressor 2 ** u67

Page 6: Instructions AK-CC 250A€¦ · ** Gold plating ensures make function with small contact loads *** UL-approval based on 30000 couplings 10 V < U < 256 V No Function ... Temperature

6 Instructions RI8PG302 © Danfoss 06/2015 AK-CC 250A

The Product contains electrical components And may not be disposed together with domestic waste.Equipment must be separate collected with Electrical and Elec-tronic waste. According to Local and currently valid legislation.

AD

AP-

KOO

o06Pt: Pt 1000 Ω @ 0°C (AKS 11, AKS 12, AKS 21)P01: PTC 1000 Ω (nominal 990 Ω) = EKS 111P02: PTC 1000 Ω @ 25°C (nominal 1000 Ω)

Pt 1000 @ 0°C

PTC 1000 Ω PTC 1000 Ω @ 25°C

AKS 11, AKS 12, AKS 21

KTY81-121EKS 111

KTY81-110

°C Ω Ω Ω30 1167.7 1029 104025 1097.3 990 100020 1077.9 951 96115 1058.5 914 92310 1039.0 877 886

5 1019.5 841 8500 1000.0 807 815

−5 980.4 773 781−10 960.9 740 747−15 941.2 708 715−20 921.6 677 684−25 901.9 647 653−30 882.2 617 624−35 862.5 589 595−40 842.7 562 567

Carel:TSH/TST/TSM/TSQ/PT1

Dixell:PMG/PMP/PMT

Carel:03/06/015

Dixell:S6

Elliwell:SN6/SN7

Lae:ST1K.CP

Frigo:VX6

o06 Pt P01 P02

AK-CC 250A

Sensor overview