+ All Categories
Home > Documents > Instrumentation and Control

Instrumentation and Control

Date post: 29-Oct-2014
Category:
Upload: humberto-enrique-oyaga-barrios
View: 288 times
Download: 2 times
Share this document with a friend
Description:
Instrumentation and Control Principles and Base
Popular Tags:
273
I nstrumentation and C ontrol Qualification Standard Reference Guide SEPTEMBER 2009
Transcript
Page 1: Instrumentation and Control

Instrumentation and Control

Qualification Standard

Reference Guide

SEPTEMBER 2009

Page 2: Instrumentation and Control

This page is intentionally blank.

Page 3: Instrumentation and Control

Table of Contents

i

LIST OF FIGURES ..................................................................................................................... iii LIST OF TABLES ........................................................................................................................ v ACRONYMS................................................................................................................................ vi PURPOSE...................................................................................................................................... 1 SCOPE ........................................................................................................................................... 1 PREFACE...................................................................................................................................... 1 TECHNICAL COMPETENCIES............................................................................................... 3 1. Instrumentation and control personnel shall demonstrate a working level knowledge of

fundamental electrical theory.................................................................................................... 3 2. Instrumentation and control personnel shall demonstrate a working level knowledge of

the following basic electrical equipment: ............................................................................... 12 3. Instrumentation and control personnel shall demonstrate a working level knowledge of

the characteristics and applications of electrical components used in instrumentation and control systems........................................................................................................................ 54

4. Instrumentation and control personnel shall demonstrate a working level knowledge of temperature detection circuitry and components used in instrumentation and control systems.................................................................................................................................... 70

5. Instrumentation and control personnel shall demonstrate a working level knowledge of pressure detection circuitry and components used in instrumentation and control systems.................................................................................................................................... 77

6. Instrumentation and control personnel shall demonstrate a working level knowledge of level detection circuitry and components used in instrumentation and control systems. .......... 81

7. Instrumentation and control personnel shall demonstrate a working level knowledge of flow detection circuitry and components used in instrumentation and control systems......... 87

8. Instrumentation and control personnel shall demonstrate a working level knowledge of position indication circuitry and components used in instrumentation and control systems.................................................................................................................................... 93

9. Instrumentation and control personnel shall demonstrate a working level knowledge of radiation detection equipment................................................................................................. 97

10. Instrumentation and control personnel shall demonstrate a working level knowledge of nuclear instrumentation......................................................................................................... 113

11. Instrumentation and control personnel shall demonstrate a working level knowledge of refractometers (as applicable to their facilities).................................................................... 121

12. Instrumentation and control personnel shall demonstrate a working level knowledge of sensor characteristics and instrument loop signal types. ...................................................... 124

13. Instrumentation and control personnel shall demonstrate a working level knowledge of process control systems......................................................................................................... 128

14. Instrumentation and control personnel shall demonstrate a working level knowledge of the characteristics and applications of pneumatic/hydraulic components used in instrumentation and control systems..................................................................................... 143

15. Instrumentation and control personnel shall demonstrate a working level knowledge of the characteristics and applications of electronic components used in instrumentation and control systems...................................................................................................................... 148

Page 4: Instrumentation and Control

Table of Contents

ii

16. Instrumentation and control personnel shall demonstrate a working level knowledge of systems integration to achieve performance, effectiveness, and cost objectives.................. 154

17. Instrumentation and control personnel shall demonstrate a working level knowledge of basic thermodynamic concepts and theories used in the design and operation of process control systems...................................................................................................................... 154

18. Instrumentation and control personnel shall demonstrate a familiarity level knowledge of basic heat transfer and fluid flow concepts and theories. ..................................................... 160

19. Instrumentation and control personnel shall demonstrate a familiarity level knowledge of mechanical engineering, theories, principles, and techniques. ............................................. 166

20. Instrumentation and control personnel shall demonstrate a familiarity level knowledge of the geoseismic/civil engineering theories, principles, and techniques that apply to instrumentation and control systems..................................................................................... 186

21. Instrumentation and control personnel shall demonstrate a familiarity level knowledge of the chemical engineering theories, principles, and techniques that apply to instrumentation and control systems..................................................................................... 188

22. Instrumentation and control personnel shall demonstrate the ability to read and interpret electrical diagrams, including: .............................................................................................. 194

23. Instrumentation and control personnel shall demonstrate the ability to read and interpret mechanical diagrams associated with instrumentation and control systems, including: ...... 202

24. Instrumentation and control personnel shall demonstrate the ability to read and interpret engineering fabrication, construction, and architectural drawings associated with instrumentation and control systems..................................................................................... 203

25. Instrumentation and control personnel shall demonstrate a working level knowledge of the various uses of computers and digital devices used in instrumentation and control systems.................................................................................................................................. 203

26. Instrumentation and control personnel shall demonstrate a working level knowledge of analytical equipment used to measure process chemistry..................................................... 206

27. Instrumentation and control personnel shall demonstrate a familiarity level knowledge of maintenance management practices related to instrumentation and control activities. ........ 217

28. Instrumentation and control personnel shall demonstrate the ability to evaluate the adequacy of local compliance of I&C systems with applicable design criteria (such as ISA 84.01, ISA 67.04.01, IEEE 603-1998, NEC or the Uniform Building Code) used by site/facility............................................................................................................................. 225

29. I&C personnel designated as vital safety systems subject matter experts shall demonstrate an expert level of knowledge on their level of understanding and approach to overseeing contractor activities by using the requirements of DOE O 420.1, Facility Safety, and the guidance in DOE-STD-1073-93, Guide for Operational Configuration Management Program, by performing system assessments addressing the following elements: ............................................................................................................................... 228

30. Instrumentation and control personnel shall demonstrate a familiarity level knowledge of DOE O 430.1, Life Cycle Asset Management...................................................................... 228

31. Instrumentation and control personnel shall demonstrate the ability to evaluate the adequacy of local compliance with applicable Instrumentation, Systems, and Automation

Page 5: Instrumentation and Control

Table of Contents

iii

Society (ISA) standards related to process control instrumentation and I&C systems (consider entire instrument loops, including sensors, transmitters, controllers, final elements). .............................................................................................................................. 240

32. Instrumentation and control personnel shall demonstrate a familiarity level knowledge of DOE O 414.1A, Quality Assurance, as it applies to instrument and control systems. ......... 241

33. Instrumentation and control personnel shall demonstrate the ability to apply problem analysis techniques necessary to identify problems, determine potential causes of problems, and identify corrective action............................................................................... 253

34. Instrumentation and control personnel shall demonstrate the ability to perform technical reviews of procedures related to instrumentation and controls. ........................................... 253

Selected Bibliography and Suggested Reading ...................................................................... 255

Figures

Figure 1. Relationship between resistance, reactance, and impedance...........................................8 Figure 2. Basic chemical battery...................................................................................................13 Figure 3. Basic DC generator........................................................................................................14 Figure 4. Basic AC generator........................................................................................................15 Figure 5. Production of a DC voltage using a thermocouple........................................................16 Figure 6. A simple hydrometer .....................................................................................................19 Figure 7. Chemical action during discharge .................................................................................22 Figure 8. Chemical action during charging...................................................................................23 Figure 9. Cells connected in a series.............................................................................................28 Figure 10. Simple AC generator ...................................................................................................29 Figure 11. Developing a sine wave voltage ..................................................................................30 Figure 12. Basic operation of a DC generator ..............................................................................31 Figure 13 . Left-hand rule for generators......................................................................................32 Figure 14. Three phase stator........................................................................................................36 Figure 15. Core-type transformer..................................................................................................41 Figure 16. Cutaway view of a molded case circuit breaker ..........................................................52 Figure 17. Electric schematic symbols .........................................................................................57 Figure 18. Components of an effective electrical safety system...................................................65 Figure 19. Internal construction of a typical RTD........................................................................71 Figure 20. RTD well and terminal head........................................................................................72 Figure 21. Internal construction of a typical thermocouple ..........................................................73 Figure 22. Simple thermocouple circuit........................................................................................74 Figure 23. Bridge circuit ...............................................................................................................75 Figure 24. Unbalanced bridge circuit............................................................................................76 Figure 25. Balanced bridge circuit................................................................................................77 Figure 26. Basic metallic bellows .................................................................................................78 Figure 27. Strain gauge pressure transducer .................................................................................79 Figure 28. Block diagram of a differential pressure level detection circuit..................................85

Page 6: Instrumentation and Control

Table of Contents

iv

Figure 29. Flow nozzle..................................................................................................................90 Figure 30. Differential pressure flow detection block diagram ....................................................91 Figure 31. Potentiometer valve position indicator ........................................................................94 Figure 32. Proportional counter ....................................................................................................98 Figure 33. Proportional counter circuit .......................................................................................101 Figure 34. Single channel analyzer operation.............................................................................102 Figure 35. Single channel analyzer output..................................................................................102 Figure 36. Discriminator .............................................................................................................103 Figure 37. BF3 proportional counter circuit ................................................................................104 Figure 38. Gas ionization curve ..................................................................................................106 Figure 39. Electronic energy band of an ionic crystal ................................................................108 Figure 40. Gamma spectrometer block diagram.........................................................................110 Figure 41. Multichannel analyzer output ....................................................................................111 Figure 42. Self-powered neutron detector...................................................................................112 Figure 43. Source range channel.................................................................................................116 Figure 44. Intermediate range channel........................................................................................117 Figure 45. Power range channel..................................................................................................118 Figure 46. Light is bent going from first material to second ......................................................122 Figure 47. Light going from high index to low...........................................................................123 Figure 48. Light at critical angle for refraction...........................................................................123 Figure 49. Internal reflection of light..........................................................................................124 Figure 50. Instrumentation system examples..............................................................................127 Figure 51. Open-loop control system..........................................................................................130 Figure 52. Closed-loop control system .......................................................................................130 Figure 53. Lube oil cooler temperature control system and equivalent block diagram..............133 Figure 54. System tuned using the Ziegler-Nichols closed-loop tuning method........................142 Figure 55. Pneumatic actuator: air-to-close, spring-to-open.......................................................145 Figure 56. Pneumatic actuator with controller and positioner ....................................................147 Figure 57. Venturi tube ...............................................................................................................159 Figure 58. Pressure versus depth.................................................................................................163 Figure 59. Gate valve ..................................................................................................................167 Figure 60. Z-body glove valve....................................................................................................168 Figure 61. Typical butterfly valve...............................................................................................170 Figure 62. Straight-through diaphragm valve .............................................................................171 Figure 63. Relief valve...............................................................................................................172 Figure 64. Simplied centrifugal pump ........................................................................................175 Figure 65. Circuit diagram for pressure-compensated flow-control valve .................................180 Figure 66. U-tube feedwater heat exchanger ..............................................................................181 Figure 67. Basic logic symbols ...................................................................................................195 Figure 68. Convention for depicting multiple inputs..................................................................196 Figure 69. Type-one time delay device.......................................................................................196 Figure 70. Type two time delay device.......................................................................................197 Figure 71. Type-three time delay device ....................................................................................198

Page 7: Instrumentation and Control

Table of Contents

v

Figure 72. Truth tables ................................................................................................................199 Figure 73. Logic gate status notation ..........................................................................................200 Figure 74. Analog input ..............................................................................................................203 Figure 75. Binary input ...............................................................................................................204 Figure 76. Digital control system with analog input/output .......................................................204 Figure 77. The separation of controller and process...................................................................205 Figure 78. Relationship between conductivity and ion concentration ........................................207

Tables

Table 1. Common alphas.............................................................................................................212 Table 2. Conductivity of some common solutions......................................................................212 Table 3. Critical decision authority thresholds............................................................................234

Page 8: Instrumentation and Control

vi

ACRONYMS AC alternating current ACB air circuit breaker A/D analog-to-digital ADC analog-to-digital converter Ah Ampere-hours ANSI American National Standards Institute ASME American Society of Mechanical Engineers BF3 boron trifluoride Btu British thermal unit BWR boiling water reactor C Celsius cc cubic centimeter CEMF counter electromotive force CRD contractor requirements document CSO Cognizant Secretarial Officer D/A digital-to-analog DAC digital-to-analog converter DAQ data acquisition DC direct current DCS distributed control systems DI&C digital instrumentation and control DOE U.S. Department of Energy DP or D/P differential pressure DPD diethyl-p-phenylenediamine DPM decades per minute E excited state EIA Electronics Industry Alliance EMF electromagnetic force EMI electromagnetic interference EPA U.S. Environmental Protection Agency ESD electrostatic discharge ESDA Electrostatic Discharge Association F Fahrenheit FAQS functional area qualification standard ft-lbf foot-pounds force g gravity G ground state Gc gravitational constant GFAAS graphite furnace atomic absorption spectroscopy G-M Geiger-Müller H2 hydrogen gas HASP health and safety plan HNO3 nitric acid

Page 9: Instrumentation and Control

vii

ACRONYMS hp horsepower HS-21 Office of Nuclear Safety Policy and Assistance HVAC heating, ventilation, and air conditioning Hz hertz I&C instrumentation and controls ICP-MS inductively coupled plasma—mass spectroscopy IEEE Institute of Electrical and Electronic Engineers IFI integrated facilities and infrastructure IGPP institutional general plant project in. inch I/P current-to-pneumatic ISA International Society of Automation K Kelvin KCl potassium chloride KE kinetic energy KSA knowledge, skill, and ability L liter lbf Pounds-force lbm pounds mass LM level modifier L/P low pressure LPSO Lead Program Secretarial Officer LR level recorder LT level transmitter LTS long-term stewardship LVDT linear variable differential transformers M&TE measuring and test equipment m mass mA milliamp MeV million electron bolts Mg milligram mL milliliter MSDS material safety data sheet mV millivolt MW molecular weight N north NATO North Atlantic Treaty Organization NCDENR North Carolina Department of Environment and Natural Resources NCSL National Conference of Standards Laboratories NCSP National Chemical Safety Program NCTO normally closed, timed-open NDA nondestructive assay NEC National Electrical Code

Page 10: Instrumentation and Control

viii

ACRONYMS NEMA National Electrical Manufacturers’ Association NFPA National Fire Protection Association NH3 ammonia NIST National Institute of Standards nm nanometer NNSA National Nuclear Security Administration NOTC normally open,-timed-closed NOTO normally open,-timed-open NPH natural phenomena hazard NQA nuclear quality assurance OCB oil circuit breaker Pb sponge lead PC performance category PE potential energy P&ID piping and instrumentation diagrams P/I pneumatic to current PID proportional integral derivative PLC programmable logic controller POA pilot-operated absolute valve ppb parts per billion ppm parts per million psi pounds per square inch psia absolute pressure psig gauge pressure PSO Program Secretarial Officer PT pressure transmitter PWB printed wiring board PWR pressurized water reactor q heat added to or removed from a system per unit mass Q heat QA quality assurance QAP quality assurance program QC quality control QME qualification of active mechanical equipment R individual gas constant RAM random access memory ROM read only memory rpm revolutions per minute RTD resistance temperature detector scfm standard cubic feet per minute S south SEC Secretarial Acquisition Executive SI International System of Units

Page 11: Instrumentation and Control

ix

ACRONYMS SSC system, structure, and component SSR solid-state relay Tb bulk temperature TDS total dissolved solid TEC total estimated costs TR temperature recorder Ts given temperature TT temperature transmitter TVSS transient voltage surge suppression TYSP ten-year site plan UPS uninterruptible power supply VE value engineering VIR valve-in receiver V volt WBS work breakdown structure λ lambda

Page 12: Instrumentation and Control

1

PURPOSE The purpose of this reference guide is to provide a document that contains the information required for a Department of Energy (DOE)/National Nuclear Security Administration (NNSA) technical employee to successfully complete the Instrumentation and Control Functional Area Qualification Standard (FAQS). Information essential to meeting the qualification requirements is provided; however, some competency statements require extensive knowledge or skill development. Reproducing all the required information for those statements in this document is not practical. In those instances, references are included to guide the candidate to additional resources.

SCOPE This reference guide addresses the competency statements in the June 2003 edition of DOE-STD-1162-2003, Instrumentation and Control Functional Area Qualification Standard. The qualification standard contains 34 competency statements.

Please direct your questions or comments related to this document to the NNSA Learning and Career Development Department.

PREFACE Competency statements and supporting knowledge and/or skill statements from the qualification standard are shown in contrasting bold type, while the corresponding information associated with each statement is provided below it.

A comprehensive list of acronyms and abbreviations is found at the beginning of this document. It is recommended that the candidate review the list prior to proceeding with the competencies, as the acronyms and abbreviations may not be further defined within the text unless special emphasis is required.

The competencies and supporting knowledge, skill, and ability (KSA) statements are taken directly from the FAQS. Most corrections to spelling, punctuation, and grammar have been made without remark, and all document-related titles, which variously appear in roman or italic type or set within quotation marks, have been changed to plain text, also mostly without remark. Capitalized terms are found as such in the qualification standard and remain so in this reference guide. When they are needed for clarification, explanations are enclosed in brackets.

Every effort has been made to provide the most current information and references available as of September 2009. However, the candidate is advised to verify the applicability of the information provided. It is recognized that some personnel may oversee facilities that utilize predecessor documents to those identified. In those cases, such documents should be included in local qualification standards via the Technical Qualification Program.

In the cases where information about an FAQS topic in a competency or KSA statement is not available in the newest edition of a standard (consensus or industry), an older version is referenced. These references are noted in the text and in the bibliography.

Page 13: Instrumentation and Control

2

Only significant corrections to errors in the technical content of the discussion text source material are identified. Editorial changes that do not affect the technical content (e.g., grammatical or spelling corrections, and changes to style) appear without remark.

Page 14: Instrumentation and Control

3

TECHNICAL COMPETENCIES

1. Instrumentation and control personnel shall demonstrate a working level knowledge of fundamental electrical theory.

a. Define and discuss the following terms: Voltage Current Power Conductor Insulator Inductance Capacitance Impedance Electromagnetic force Electromagnetic field Frequency Wavelength

The following definitions are taken from DOE-HDBK-1011/1-92 unless stated otherwise.

Voltage

The basic unit of measure for potential difference is the volt (symbol V), and, because the volt unit is used, potential difference is called voltage. An object’s electrical charge is determined by the number of electrons that the object has gained or lost. Because such a large number of electrons move, a unit called the coulomb is used to indicate the charge. One coulomb is equal to 6.28 × 1018 (billion, billion) electrons. For example, if an object gains one coulomb of negative charge, it has gained 6,280,000,000,000,000,000 extra electrons. A volt is defined as a difference of potential causing one coulomb of current to do one joule of work. A volt is also defined as that amount of force required to force one ampere of current through one ohm of resistance.

Current

The density of the atoms in copper wire is such that the valence orbits of the individual atoms overlap, causing the electrons to move easily from one atom to the next. Free electrons can drift from one orbit to another in a random direction. When a potential difference is applied, the direction of their movement is controlled. The strength of the potential difference applied at each end of the wire determines how many electrons change from a random motion to a more directional path through the wire. The movement or flow of these electrons is called electron current flow or just current.

Power

Electricity is generally used to do some sort of work, such as turning a motor or generating heat. Specifically, power is the rate at which work is done, or the rate at which heat is generated. The unit commonly used to specify electric power is the watt. In equations, you will find power

Page 15: Instrumentation and Control

4

abbreviated with the capital letter P, and watts, the units of measure for power, are abbreviated with the capital letter W. Power is also described as the current (I) in a circuit times the voltage (E) across the circuit.

P = IE

Conductor

Conductors are materials with electrons that are loosely bound to their atoms, or materials that permit free motion of a large number of electrons. Atoms with only one valence electron, such as copper, silver, and gold, are examples of good conductors. Most metals are good conductors.

Insulator

Insulators, or nonconductors, are materials with electrons that are tightly bound to their atoms and require large amounts of energy to free them from the influence of the nucleus. The atoms of good insulators have their valence shells filled with eight electrons, which means they are more than half filled. Any energy applied to such an atom will be distributed among a relatively large number of electrons. Examples of insulators are rubber, plastics, glass, and dry wood.

Inductance

Inductance is defined as the ability of a coil to store energy, induce a voltage in itself, and oppose changes in current flowing through it. The units of measurement are called henries. One henry is the amount of inductance that permits one volt to be induced when the current through the coil changes at a rate of one ampere per second.

Capacitance

Capacitance is defined as the ability to store an electric charge. Capacitance measured in farads, is equal to the amount of charge that can be stored in a device or capacitor divided by the voltage applied across the device or capacitor plates when the charge was stored.

The following is taken from DOE-HDBK-1011/3-92.

Impedance

Impedance is defined as the total opposition to current flow in a circuit.

The following is taken from Eric Weisstein’s World of Physics, definitions of electromagnetic force and electromagentic.

Electromagnetic Force

Electromagnetic force is an infinite-range attractive or repulsive force that acts between charged particles. A particle at rest feels only the force due to the electric field, called Coulomb’s law.

Electromagnetic Field

Electromagnetic field is the general field consisting of superimposed electric and magnetic fields. While properties such as the potential energy stored in the field remain invariant of the

Page 16: Instrumentation and Control

5

observing reference frame, special relativity shows that different observers will actually see differing strength of the constituent electric and magnetic fields. The electric and magnetic components of an electromagnetic field are untitled in special relativity into an entity known as the electromagnetic field tensor.

Page 17: Instrumentation and Control

6

The following is taken from International Electrical Supplies, Electric Frequency – Hertz.

Frequency

Frequency is the measurement of the number of times that a repeated event occurs per unit time. To calculate the frequency, one fixes a time interval, counts the number of occurrences of the event within that interval, and then divides this count by the length of the time interval.

In the International System of Units (SI units), the result is measured in hertz (Hz), after the German physicist, Heinrich Rudolf Hertz. One Hz means that an event repeats once per second. Other units that have been used to measure frequency include: cycles per second and revolutions per minute (rpm). Heart rate is measured in beats per minute.

An alternative method to calculate frequency is to measure the time between two consecutive occurrences of the event (the period) and then compute the frequency as the reciprocal of this time: f = 1/T where T is the period.

Measuring the frequency of sound, electromagnetic waves (such as radio or light), electrical signals, or other waves, the frequency in hertz is the number of cycles of the repetitive waveform per second. If the wave is a sound, frequency is what characterizes its pitch.

Frequency has an inverse relationship to the concept of wavelength. The frequency f is equal to the speed v of the wave divided by the wavelength λ (lambda) of the wave.

In the special case of electromagnetic waves moving through a vacuum, then v = c, where c is the speed of light in a vacuum.

The following is taken from Graf’s Modern Dictionary of Electronics.

Wavelength

Wavelength is defined as the distance between points of corresponding phase of two consecutive cycles of a wave.

b. Discuss Ohm’s law.

The following is taken from DOE-HDBK-1011/1-92.

In 1827, George Simon Ohm discovered that there was a definite relationship between voltage, current, and resistance in an electrical circuit. Ohm’s law defines this relationship and can be stated in three ways.

Applied voltage equals circuit current times the circuit resistance. This is represented by the equation:

E = I × R or E = IR

Current is equal to the applied voltage divided by the circuit resistance. This is represented by the equation

Page 18: Instrumentation and Control

7

I = R

E

Resistance of a circuit is equal to the applied voltage divided by the circuit current

R (or Ω) = I

E

where I = current (A[ampere]) E = voltage (V) R = resistance (Ω)

If any two of the component values are known, the third can be calculated.

c. Discuss Kirchhoff’s law.

The following is taken from DOE-HDBK-1011/1-92.

Through experimentation in 1857 the German physicist Gustav Kirchhoff developed methods to solve complex circuits. Kirchhoff developed two conclusions, known today as Kirchhoff's laws.

Law 1:

The sum of the voltage drops around a closed loop is equal to the sum of the voltage sources of that loop (Kirchhoff’s voltage law).

Law 2:

The current arriving at any junction point in a circuit is equal to the current leaving that junction (Kirchhoff’s current law).

Kirchhoff’s laws can be related to conservation of energy and charge for a circuit with one load and source. Since all of the power provided from the source is consumed by the load, energy and charge are conserved. Since voltage and current can be related to energy and charge, then Kirchhoff’s laws are only restating the laws governing energy and charge conservation.

Kirchhoff’s Voltage Law

Kirchhoff's first law is also known as his voltage law. The voltage law gives the relationship between the voltage drops around any closed loop in a circuit, and the voltage sources in that loop. The total of these two quantities is always equal. In equation form:

∑Esource = ∑IR

Kirchhoff’s voltage law can be applied only to closed loops. A closed loop must meet two conditions:

1. It must have one or more voltage sources.

Page 19: Instrumentation and Control

8

2. It must have a complete path for current flow from any point, around the loop, and back to that point.

In a simple series circuit, the sum of the voltage drops around the circuit is equal to the applied voltage. Actually, this is Kirchhoff’s voltage law applied to the simplest case, that is, where there is only one loop and one voltage source.

Kirchhoff’s second law is called his current law and states: “At any junction point in a circuit, the current arriving is equal to the current leaving.” Thus, if 15 amperes of current arrives at a junction that has two paths leading away from it, 15 amperes will divide among the two branches, but a total of 15 amperes must leave the junction. Normally Kirchhoff’s current law is not used by itself, but with the voltage law, in solving a problem.

d. Discuss the relationships in electrical circuits between voltage, current, resistance, impedance, and power.

The following is taken from DOE-HDBK-1011/3-92.

No circuit is without some resistance, whether desired or not. Resistive and reactive components in an AC circuit oppose current flow. The total opposition to current flow in a circuit depends on its resistance, its reactance, and the phase relationships between them. Impedance is defined as the total opposition to current flow in a circuit. The following equation is the mathematical representation for the magnitude of impedance in an AC circuit.

Z = 22 XR

where Z = impedance (Ω) R = resistance (Ω) X = net reactance (Ω)

The relationship between resistance, reactance, and impedance is shown in figure 1.

Source: DOE-HDBK-1011/3-92

Figure 1. Relationship between resistance, reactance, and impedance

Page 20: Instrumentation and Control

9

The current through a certain resistance is always in phase with the applied voltage. Resistance is shown on the zero axis. The current through an inductor lags applied voltage by 90°; inductive reactance is shown along the 90° axis. Current through a capacitor leads applied voltage by 90°; capacitive reactance is shown along the -90° axis. Net reactance in an AC circuit is the difference between inductive and capacitive reactance. The following equation is the mathematical representation for the calculation of net reactance when XL is greater than XC.

X = XL - XC

where X = net reactance (Ω) XL = inductance reactance (Ω) XC = capacitive reactance (Ω)

Impedance is the vector sum of the resistance and net reactance (X) in a circuit, as shown in figure 1. The angle θ is the phase angle and gives the phase relationship between the applied voltage and the current. Impedance in an AC circuit corresponds to the resistance of a DC circuit. The voltage drop across an AC circuit element equals the current times the impedance.

The following equation is the mathematical representation of the voltage drop across an AC circuit.

V = IZ

where V = voltage drop (V) I = current (A) Z = impedance (Ω) The phase angle gives the phase relationship between current and the voltage.

e. Discuss the function of the following components in an electrical circuit: Resistor Capacitor Inductor Diode Rectifier Transformer Relay Contact Fuse Time delay relay Overcurrent relay Undervoltage relay Switches Silicon-controlled rectifiers Underfrequency relay

The following definitions are taken from DOE-HDBK-1011/1-92 unless stated otherwise.

Page 21: Instrumentation and Control

10

Resistor

The following is taken from DOE-HDBK-1011/2-92.

Resistors are made of materials that conduct electricity, but offer opposition to current flow. These types of materials are also called semiconductors because they are neither good conductors nor good insulators. Semiconductors have more than one or two electrons in their valence shells, but less than seven or eight. Examples of semiconductors are carbon, silicon, germanium, tin, and lead. Each has four valence electrons.

Capacitor

The following is taken from DOE-HDBK-1011/2-92.

A capacitor consists of two electrodes or sets of electrodes in the form of plates, separated from each other by an insulating material called a dielectric. A capacitor stores electrical energy and blocks or permits the flow of AC depending on the capacitance and frequency.

Inductor

An inductor is a passive electrical device that stores energy in a magnetic field, typically by combining the effects of many loops of electric current.

Diode

A diode is an electrical device that allows electron flow in only one direction. Diodes are used in rectifiers and to convert AC to direct current (DC).

Rectifier

Most electrical power generating stations produce AC. The major reason for generating AC is that it can be transferred over long distances with fewer losses than DC; however, many of the devices that are used today operate only, or more efficiently, with DC.

For example, transistors, electron tubes, and certain electronic control devices require DC for operation. If we are to operate these devices from ordinary AC outlet receptacles, they must be equipped with rectifier units to convert AC to DC. To accomplish this conversion, we use diodes in rectifier circuits. The purpose of a rectifier circuit is to convert AC power to DC.

The most common type of solid-state diode rectifier is made of silicon. The diode acts as a gate that allows current to pass in one direction and blocks current in the other direction. The polarity of the applied voltage determines if the diode will conduct. The two polarities are known as forward bias and reverse bias.

The following is taken from DOE-HDBK-1011/4-92.

Transformer

A transformer works on the principle that energy can be transferred by magnetic induction from one set of coils to another set by means of a varying magnetic flux. The magnetic flux is produced by an AC source. The coil of a transformer that is energized from an AC source is called the primary winding (coil), and the coil that delivers this AC to the load is called the secondary winding (coil).

Page 22: Instrumentation and Control

11

When alternating voltage is applied to the primary winding, an AC will flow that will magnetize the magnetic core, first in one direction and then in the other direction. This alternating flux flowing around the entire length of the magnetic circuit induces a voltage in the secondary windings. The induced voltage will be the same frequency as the source.

A voltage will also be induced into the primary windings, since it is also in close proximity to the changing magnetic field. The voltage opposes the voltage applied to the primary windings and is counter electromotive force (CEMF).

The AC flowing through the primary windings establishes a primary magnetic field. The primary magnetic field will build up, collapse, and change directions due to the AC. The secondary winding is placed near the primary winding. The expanding and collapsing magnetic field of the primary winding produces relative motion, and electrical current is produced in the secondary winding.

Relay

A relay is an electromagnetic device with one or more sets of contacts that changes contact positions by magnetic attraction of a coil to an armature.

Contact

A contact is the conducting part of a relay that acts as a switch that is closed or opened by the magnetic pull of an energized relay coil of a circuit or a component.

Fuse

A fuse is an overcurrent protective device inserted in series with a circuit. It contains a metal that will break or melt when the current exceeds a specific value for a specific time.

The following is taken from All About Circuits, “Time Delay Relays.”

Time Delay Relay

Some relays are constructed with a kind of shock absorber mechanism attached to the armature that prevents immediate, full motion when the coil is either energized or de-energized. This addition gives the relay the property of time-delay actuation. Time-delay relays can be constructed to delay armature motion on coil energization, de-energization, or both.

Time-delay relay contacts must be specified not only as either normally-open or normally-closed, but whether the delay operates in the direction of closing or in the direction of opening.

The following is taken from U.S. Motors, Terminology Pertaining to Electric Machinery.

Overcurrent Relay

An overcurrent relay operates when the current through the relay, during its operating period, is equal to or greater than its setting.

Page 23: Instrumentation and Control

12

Undervoltage Relay

An undervoltage relay operates when voltage that is being monitored falls below a specified value.

The following is taken from All About Circuits, “Switch Types.”

Switches

An electrical switch is any device used to interrupt the flow of electrons in a circuit. Switches are essentially binary devices: they are either completely on (closed) or completely off (open).

The simplest type of switch is one where two electrical conductors are brought in contact with each other by the motion of an actuating mechanism. Other switches are more complex, containing electronic circuits able to turn on or off depending on some physical stimulus sensed. In any case, the final output of any switch will be a pair of wire-connection terminals that will be connected together by the switch’s internal contact mechanism (closed), or not connected together (open).

Any switch designed to be operated by a person is generally called a hand switch, and they are manufactured in several varieties.

Silicon-Controlled Rectifiers

According to the Fermilab, Accelerator Division Operations Department’s Glossary f Acelerator Terms, a silicon-controlled rectifier is a rectifier that has the ability to begin conducting at an arbitrary phase of an AC current cycle.

Underfrequency Relay

According to Global Spec, under-frequency relays respond to a decrease in the frequency of an alternating electrical input quantity.

2. Instrumentation and control personnel shall demonstrate a working level knowledge of the following basic electrical equipment: Batteries Motors and generators Transformers Backup power supplies Electrical switchgear and transmission equipment

a. Discuss the basic principle by which the following components produce current: Battery Direct current generator Alternating current generator Thermocouple Solar panel Fuel cell

Battery

The following is taken from DOE-HDBK1011/1-92.

Page 24: Instrumentation and Control

13

A battery consists of two or more chemical cells connected in series. The combination of materials within a battery is used for the purpose of converting chemical energy into electrical energy. To understand how a battery works, we must first discuss the chemical cell.

The chemical cell is composed of two electrodes made of different types of metal or metallic compounds that are immersed in an electrolyte solution. The chemical actions that result are complicated, and they vary with the type of material used in cell construction. Some knowledge of the basic action of a simple cell will be helpful in understanding the operation of a chemical cell in general.

In the cell, electrolyte ionizes to produce positive and negative ions. Simultaneously, chemical action causes the atoms within one of the electrodes to ionize. (See figure 2, part A).

Due to this action, electrons are deposited on the electrode, and positive ions from the electrode pass into the electrolyte solution (part B). This causes a negative charge on the electrode and leaves a positive charge in the area near the electrode (part C).

Source: DOE-HDBK-1011/1-92

Figure 2. Basic chemical battery

The positive ions, which were produced by ionization of the electrolyte, are repelled to the other electrode. At this electrode, these ions will combine with the electrons. Because this action causes removal of electrons from the electrode, it becomes positively charged.

Direct Current Generator

The following is taken from DOE-HDBK-1011/1-92.

A simple DC generator consists of an armature coil with a single turn of wire. The armature coil cuts across the magnetic field to produce a voltage output. As long as a complete path is present, current will flow through the circuit in the direction shown by the arrows in figure 3.

Page 25: Instrumentation and Control

14

In this coil position, commutator segment 1 is in contact with brush 1, while commutator segment 2 is in contact with brush 2.

Rotating the armature one-half turn in the clockwise direction causes the contacts between the commutator segments to be reversed. Now segment 1 is contacted by brush 2, and segment 2 is in contact with brush 1.

Due to this commutator action, that side of the armature coil which is in contact with either of the brushes is always cutting the magnetic field in the same direction. Brushes 1 and 2 have a constant polarity, and pulsating DC is delivered to the load circuit.

Source: DOE-HDBK-1011/1-92

Figure 3. Basic DC generator

Alternating Current Generator

The following is taken from DOE-HDBK-1011/3-92.

The elementary AC generator consists of a conductor, or loop of wire, in a magnetic field that is produced by an electromagnet. The two ends of the loop are connected to slip rings, and they are in contact with two brushes. When the loop rotates it cuts magnetic lines of force, first in one direction and then the other. A basic AC generator is illustrated in figure 4.

At the instant the loop is in the vertical position the coil sides are moving parallel to the field and do not cut magnetic lines of force. In this instant, there is no voltage induced in the loop. As the coil rotates in a counter-clockwise direction, the coil sides will cut the magnetic lines of force in opposite directions. The direction of the induced voltages depends on the direction of movement of the coil.

Page 26: Instrumentation and Control

15

Source: DOE-HDBK-1011/3-92

Figure 4. Basic AC generator

The induced voltages add in series, making slip ring X (figure 4) positive (+) and slip ring Y (figure 4) negative (-). The potential across resistor R will cause a current to flow from Y to X through the resistor. This current will increase until it reaches a maximum value when the coil is horizontal to the magnetic lines of force.

Thermocouple

The following is taken from DOE-HDBK-1011/1-92.

A thermocouple is a device used to convert heat energy into voltage output. The thermocouple consists of two different types of metal joined at a junction. As the junction is heated, the electrons in one of the metals gain enough energy to become free electrons. The free electrons will then migrate across the junction and into the other metal. This displacement of electrons produces a voltage across the terminals of the thermocouple.

The combinations used in the makeup of a thermocouple include iron and constantan; copper and constantan; antimony and bismuth; and chromel and alumel.

Thermocouples are normally used to measure temperature. The voltage produced causes a current to flow through a meter, which is calibrated to indicate temperature. The production of a DC voltage using a thermocouple is illustrated in figure 5.

Page 27: Instrumentation and Control

16

Source: DOE-HDBK-1011/1-92

Figure 5. Production of a DC voltage using a thermocouple

Solar Panel

The following is taken from Solar Panel Info, How do Solar Panels Work.

Solar panels collect solar radiation from the sun and actively convert that energy to electricity. Solar panels are comprised of several individual solar cells. These solar cells function similarly to large semiconductors and utilize a large-area p-n junction diode. When the solar cells are exposed to sunlight, the p-n junction diodes convert the energy from sunlight into usable electrical energy. The energy generated from photons striking the surface of the solar panel allows electrons to be knocked out of their orbits and released, and electric fields in the solar cells pull these free electrons in a directional current, from which metal contacts in the solar cell can generate electricity. The more solar cells in a solar panel and the higher the quality of the solar cells, the more total electrical output the solar panel can produce. The conversion of sunlight to usable electrical energy has been dubbed the photovoltaic effect

Page 28: Instrumentation and Control

17

Fuel Cell

The following is taken from the Breakthrough Technologies Institute’s Fuel Cells 200 Program.

A fuel cell is an electrochemical device that combines hydrogen and oxygen to produce electricity, with water and heat as its by-product. As long as fuel is supplied, the fuel cell will continue to generate power. Since the conversion of the fuel to energy takes place via an electrochemical process, not combustion, the process is clean, quiet, and highly efficient—two to three times more efficient than fuel burning.

b. Discuss the various types of batteries used in electronic components. Include in the discussion the following elements of battery operation: Method by which a direct current (DC) is produced Specific gravity Current capacity Amp-hour capacity Voltage applications Charge and discharge characteristics Battery life expectancy Materials used in the battery construction Battery physical characteristics, i.e., size, weight Environmental requirements for safe battery operation and disposal Specific component applications Electrolyte precautions

Types of Batteries

The following information is taken from DOE-HDBK-1011/2-92.

The lead-acid battery is the most common type of battery in use today. There are other types of storage batteries, each having certain advantages.

Wet and Dry Cells

Wet and dry cells are classified by the type of electrolyte the battery uses. The electrolyte of a cell may be a liquid or a paste. If the electrolyte is a paste, the cell is referred to as a dry cell. If the electrolyte is a solution, the cell is called a wet cell.

Carbon-Zinc Cell

The carbon-zinc cell is one of the oldest and most widely used types of dry cells. The carbon in the battery is in the form of a rod in the center of the cell which acts as the positive terminal. The case is made from zinc and acts as the negative electrode. The electrolyte for this type of cell is a chemical paste-like mixture which is housed between the carbon electrode and the zinc case. The cell is then sealed to prevent any of the liquid in the paste from evaporating. The advantage of a carbon-zinc battery is that it is durable and very inexpensive to produce. The cell voltage for this type of cell is about 1.5 volts.

Alkaline Cell

The alkaline cell is so called because it has an alkaline electrolyte of potassium hydroxide. The negative electrode is made from zinc, and the positive electrode is made of manganese

Page 29: Instrumentation and Control

18

dioxide. The typical alkaline cell generates 1.5 volts. The alkaline cell has the advantage of an extended life over that of a carbon-zinc cell of the same size; however, it is usually more expensive.

Nickel-Cadmium Cell

The nickel-cadmium cell is a secondary cell, and the electrolyte is potassium hydroxide. The negative electrode is made of nickel hydroxide, and the positive electrode is made of cadmium hydroxide. The nominal voltage of a nickel-cadmium cell is 1.25 volts. The nickel-cadmium battery has the advantage of being a dry cell that is a true storage battery with a reversible chemical reaction (i.e., it can be recharged). The nickel-cadmium battery is a rugged, dependable battery. It gives dependable service under extreme conditions of temperature, shock, and vibration. Due to its dependability, it is ideally suited for use in portable communications equipment.

Edison Cell

In an edison cell the positive plate consists of nickel and nickel hydrate, and the negative plate is made of iron. The electrolyte is an alkaline. Typical voltage output is 1.4 volts, and it should be recharged when it reaches 1.0 volts. The edison cell has the advantage of being a lighter and more rugged secondary cell than a lead-acid storage battery.

Mercury Cell

Mercury cells come in two types; one is a flat cell that is shaped like a button, while the other is a cylindrical cell that looks like a regular flashlight battery. Each cell produces about 1.35 volts. These cells are very rugged and have a relatively long shelf life. The mercury cell has the advantage of maintaining a fairly constant output under varying load conditions. For this reason, they are used in products such as electric watches, hearing aids, cameras, and test instruments.

Method by Which a Direct Current is Produced

The following is taken from DOE-HDBK-1011/1-92.

A battery consists of two or more chemical cells connected in series. The combination of materials within a battery is used for the purpose of converting chemical energy into electrical energy in a chemical cell.

The chemical cell is composed of two electrodes made of different types of metal or metallic compounds that are immersed in an electrolyte solution. The chemical actions that result are complicated, and they vary with the type of material used in cell construction.

In the cell, electrolyte ionizes to produce positive and negative ions. Simultaneously, chemical action causes the atoms within one of the electrodes to ionize.

Due to this action, electrons are deposited on the electrode, and positive ions from the electrode pass into the electrolyte solution. This causes a negative charge on the electrode and leaves a positive charge in the area near the electrode.

Page 30: Instrumentation and Control

19

The positive ions, which were produced by ionization of the electrolyte, are repelled to the other electrode. At this electrode, these ions will combine with the electrons. Because this action causes removal of electrons from the electrode, it becomes positively charged.

Specific Gravity

The following is taken from DOE-HDBK-1011/2-92.

Specific gravity is defined as the ratio comparing the weight of any liquid to the weight of an equal volume of water. The specific gravity of pure water is 1.000. Lead-acid batteries use an electrolyte that contains sulfuric acid. Pure sulfuric acid has a specific gravity of 1.835, since it weighs 1.835 times as much as pure water per unit volume.

Since the electrolyte of a lead-acid battery consists of a mixture of water and sulfuric acid, the specific gravity of the electrolyte will fall between 1.000 and 1.835. Normally, the electrolyte for a battery is mixed such that the specific gravity is less than 1.350.

Specific gravity is measured with a hydrometer. A simple hydrometer consists of a glass float inside a glass tube, as shown in figure 6. The hydrometer float is weighted at one end and sealed at both ends. A scale calibrated in specific gravity is positioned lengthwise along the body of the float.

Source: DOE-HDBK-1011/2-92

Figure 6. A simple hydrometer

The float is placed inside the glass tube, and the fluid to be tested is drawn into the tube. As the fluid is drawn into the tube, the hydrometer float will sink to a certain level in the fluid. The extent to which the hydrometer float protrudes above the level of the fluid depends on

Page 31: Instrumentation and Control

20

the specific gravity of the fluid. The reading on the float scale at the surface of the fluid is the specific gravity of the fluid.

Current Capacity

The following is taken from George Washington University, School of Engineering and Applied Sciences.

Current carrying capacity is defined as the amperage a conductor can carry before melting either the conductor or the insulation.

Heat, caused by an electrical current flowing through a conductor, will determine the amount of current a wire will handle. Theoretically, the amount of current that can be passed through a single bare copper wire can be increased until the heat generated reaches the melting temperature of the copper.

Amp-Hour Capacity

The following is taken from All About Circuits, Battery Ratings.

A battery with a capacity of 1 ampere-hour (Ah) should be able to continuously supply a current of 1 A to a load for exactly 1 hour, or 2 A for 1/2 hour, or 1/3 amp for 3 hours, etc., before becoming completely discharged. In an ideal battery, this relationship between continuous current and discharge time is stable and absolute, but real batteries don’t behave exactly as this simple linear formula would indicate. Therefore, when amp-hour capacity is given for a battery, it is specified at either a given current, given time, or assumed to be rated for a time period of 8 hours (if no limiting factor is given).

For example, an average automotive battery might have a capacity of about 70 Ah, specified at a current of 3.5 A. This means that the amount of time this battery could continuously supply a current of 3.5 A to a load would be 20 hours (70 Ah/3.5 A). But if a lower-resistance load were connected to that battery, drawing 70 A continuously, the battery should hold out for exactly 1 hour (70 Ah/70 A), but this might not be true in real life. With higher currents, the battery will dissipate more heat across its internal resistance, which has the effect of altering the chemical reactions taking place within. Chances are, the battery would fully discharge some time before the calculated time of 1 hour under this greater load.

Voltage Applications

The following is taken from Transtronics, “Sealed Lead Acid Battery Applications.”

Battery Voltage

There is much confusion about battery voltage because a battery has more than one voltage and often the literature is lax in defining which voltage is being discussed at the time. Also, measurements of a battery’s voltage, particularly float voltage, require time for the battery to stabilize. Float voltage - Battery voltage at zero current. You must wait about 20 minutes for

the battery to stabilize at this voltage. Nominal voltage - The voltage by which a battery is referred to. For example, a 12-

volt battery is made of 6 cells and has a float voltage of about 12 V.

Page 32: Instrumentation and Control

21

Charge voltage - The voltage a battery goes to while being charged. Discharge voltage - The voltage of a battery while discharging. This voltage is

determined by the charge state and the current flowing.

Charge voltage is usually stated as the battery capacity in ampere-hours divided by 5 (Ah/5). Thus, a 10 Ah battery would use a 2 A charge rate to specify the battery charge voltage. This voltage varies with the charge state of the battery, that is, it is higher when the battery has a full charge.

In a similar manner discharge voltage is usually specified at a current that is capacity in Ah divided by 20. A 10 Ah battery would have a load of 0.5 A on it while measuring this voltage.

Battery Efficiency

Energy efficiency is calculated on the amount of power used from the battery while discharging divided by the amount of power delivered to the battery while charging, multiplied by 100 to yield a percentage. A lead-acid battery has an efficiency of only 75 to 85 percent. The energy lost appears as heat and warms the battery. Keeping the charge and discharge rate of a battery low helps keep a battery cool and improves the battery life.

The energy losses don’t include losses in the charging circuit that may have an efficiency of anywhere from 60 percent to 80 percent. Thus, the overall- total efficiency is the product of these efficiencies and ends up being 45 to 68 percent.

Battery Capacity

Battery capacity refers to the total amount of energy stored within a battery. Rated capacity is in Ah, which is the product of the current times the number of hours to total discharge. The capacity is normally compared with a time of 20 hours and a temperature of 68 ºF (20 ºC). There are five factors that dictate the capacity of a given battery:

1. Size 2. Temperature 3. Cut off voltage 4. Discharge rate 5. History

Choosing Battery Capacity

Specifying battery capacity involves a bit more than multiplying the load current by the backup time in hours. You must first de-rate the battery for capacity tolerance, temperature, and discharge rate.

1. Multiply the average load current by the backup hours of operation you need. 2. Add 15 percent to cover loss of capacity from tolerance and uncycled batteries. 3. For every 10 ºC (18 ºF) below room temperature (72 ºF) that your worst case low

temperature is, add 10 percent. 4. If your backup time is less than 20 hours, add 10 percent for every time you have to

double your back-up time to equal more than 20 hours. For example, 20 minutes would have to be doubled 6 times to equal more than 20 hours. Thus you would have to add 60 percent on to your required capacity.

Page 33: Instrumentation and Control

22

5. Add 40 percent to provide for an economic life cycle. A battery with 60 percent of its capacity left is considered worn out.

Charge and Discharge Characteristics

The following is taken from DOE-HDBK-1011/2-92.

In a lead-acid battery, two types of lead are acted upon electro-chemically by an electrolytic solution of diluted sulfuric acid. As shown in figure 7, he positive plate consists of lead peroxide, and the negative plate is sponge lead.

Source: DOE-HDBK-1011/2-92

Figure 7. Chemical action during discharge

When a lead-acid battery is discharged, the electrolyte divides into hydrogen (H2) and sulfate. The H2 will combine with some of the oxygen that is formed on the positive plate to produce water, and thereby reduce the amount of acid in the electrolyte. The sulfate combines with the lead of both plates, forming lead sulfate.

As a lead-acid battery is charged in the reverse direction, the action described in the discharge is reversed. The lead sulfate is driven out and back into the electrolyte. The return of acid to the electrolyte will reduce the sulfate in the plates and increase the specific gravity. This will continue to happen until all of the acid is driven from the plates and back into the electrolyte, as shown in figure 8.

Page 34: Instrumentation and Control

23

Source: DOE-HDBK-1011/2-92

Figure 8. Chemical action during charging

As a lead-acid battery charge nears completion, hydrogen gas is liberated at the negative plate, and oxygen gas is liberated at the positive plate. This action occurs since the charging current is usually greater than the current necessary to reduce the remaining amount of lead sulfate on the plates. The excess current ionizes the water in the electrolyte. Since hydrogen is highly explosive, it is necessary to provide adequate ventilation to the battery whenever charging is in progress.

The electrolyte in a lead-acid battery plays a direct role in the chemical reaction. The specific gravity decreases as the battery discharges and increases to its normal, original value as it is charged. Since specific gravity of a lead-acid battery decreases proportionally during discharge, the value of specific gravity at any given time is an approximate indication of the battery’s state of charge. To determine the state of charge, compare the specific gravity, as read using a hydrometer, with the full charge value and the manufacturer’s published specific gravity drop, which is the decrease from full to nominal charge value.

Battery Life Expectancy

The following is taken from Dataweek, Battery Selection and Life Expectancy.

The formula for determining battery life expectancy is reasonably complex, requiring proprietary data that factor in a number of variables to determine the required capacity to deliver an expected run time. In addition to variables such as voltage, background current, and pulse profiles, the formula also factors in how the required temperature range will affect both the battery voltage, and, most important, the self-discharge rate of the battery.

Temperature has a significant impact on battery performance and life expectancy. If the application is designed for cold temperatures, such requirements can prove problematic for certain battery chemistries, since a cold electrolyte becomes less active, leading to higher internal resistance, which may lead to battery failure. When subjected to extremely high temperatures, certain battery chemistries and mechanical sealing techniques start to fail, affecting both short-term performance and long-term reliability.

Page 35: Instrumentation and Control

24

The self-discharge rate of a cell is governed by its electrolyte composition, its production processes, and its construction. As a general rule, the greater the cell’s internal surface area, the greater the self-discharge rate will be. In addition, high-rate spiral cells with large surface areas have inherently higher self-discharge rates compared to bobbin-type cells of equal size that utilize the same chemistry.

A lesser-known fact that impacts battery self-discharge involves impurity levels in the electrolyte. Through years of study and fine-tuning of the electrolyte production processes, experienced battery manufacturers have found ways to lower battery self-discharge rates by reducing electrolyte impurities and parasitic reactions to nominal levels.

Battery life is also affected by impedance. Unfortunately, battery impedance is not a nice stable number, but rather one that varies by time, temperature, and the mechanical environment it must operate within.

Impedance is measured by the internal resistance developed not only in the electrolyte, but also in the cathode and anode. Impedance can also rise as a result of electrolyte loss. Even though the coin cell’s seal remains intact, being in an elevated temperature environment can cause the electrolyte to simply diffuse through the seal.

Material Used in Battery Construction

The following is taken from DOE-HDBK-1084-95.

The active materials in a battery are those that participate in the electrochemical charge/discharge reaction. These materials include the electrolyte and the positive and negative electrodes. As mentioned earlier, the electrolyte in a lead-acid battery is a dilute solution of sulfuric acid (H2 SO4 ). The negative electrode of a fully charged battery is composed of sponge lead (Pb) and the positive electrode is composed of lead dioxide (PbO2).

Battery Physical Characteristics

The following is taken from DOE-HDBK-1011/2-92.

Wet and Dry Cells

Wet and dry cells are classified by the type of electrolyte the battery uses. The electrolyte of a cell may be a liquid or a paste. If the electrolyte is a paste, the cell is referred to as a dry cell. If the electrolyte is a solution, the cell is called a wet cell.

Carbon-Zinc Cell

The carbon-zinc cell is one of the oldest and most widely used types of dry cells. The carbon in the battery is in the form of a rod in the center of the cell that acts as the positive terminal. The case is made from zinc and acts as the negative electrode. The electrolyte for this type of cell is a chemical paste-like mixture that is housed between the carbon electrode and the zinc case. The cell is then sealed to prevent any of the liquid in the paste from evaporating.

The advantage of a carbon-zinc battery is that it is durable and very inexpensive to produce. The cell voltage for this type of cell is about 1.5 volts.

Page 36: Instrumentation and Control

25

Alkaline Cell

The alkaline cell is so called because it has an alkaline electrolyte of potassium hydroxide. The negative electrode is made from zinc, and the positive electrode is made of manganese dioxide. The typical alkaline cell generates 1.5 volts. The alkaline cell has the advantage of an extended life over that of a carbon-zinc cell of the same size; however, it is usually more expensive.

Nickel-Cadmium Cell

The nickel-cadmium cell is a secondary cell, and the electrolyte is potassium hydroxide. The negative electrode is made of nickel hydroxide, and the positive electrode is made of cadmium hydroxide. The nominal voltage of a nickel-cadmium cell is 1.25 volts. The nickel-cadmium battery has the advantage of being a dry cell that is a true storage battery with a reversible chemical reaction (i.e., it can be recharged). The nickel-cadmium battery is a rugged, dependable battery. It gives dependable service under extreme conditions of temperature, shock, and vibration. Due to its dependability, it is ideally suited for use in portable communications equipment.

Edison Cell

In an edison cell the positive plate consists of nickel and nickel hydrate, and the negative plate is made of iron. The electrolyte is an alkaline. Typical voltage output is 1.4 volts, and it should be recharged when it reaches 1.0 volt. The edison cell has the advantage of being a lighter and more rugged secondary cell than a lead-acid storage battery.

Mercury Cell

Mercury cells come in two types; one is a flat cell that is shaped like a button, while the other is a cylindrical cell that looks like a regular flashlight battery. Each cell produces about 1.35 volts. These cells are very rugged and have a relatively long shelf life. The mercury cell has the advantage of maintaining a fairly constant output under varying load conditions. For this reason, they are used in products such as electric watches, hearing aids, cameras, and test instruments.

Environmental Requirements for Safe Battery Operation and Disposal

The following is taken from DOE-HDBK-1011/2-92.

Because batteries store large amounts of energy, there are certain hazards that are associated with battery operation. These hazards must be fully understood to ensure safe operation of batteries. Hazards include shorted cells, gas generation, and battery temperature.

Shorted Cell

Cell short circuits can be caused by several conditions, which include the following: faulty separators; lead particles or other metals forming a circuit between the positive and negative plates; buckling of the plates; or excessive sediments in the bottom of the jar. The primary cause of some of these occurrences is overcharging and over discharging of the battery, which causes sediment to build up due to flaking of active material and buckling of cell plates.

Page 37: Instrumentation and Control

26

Overcharging and over discharging should be avoided at all costs. Short circuits cause a great reduction in battery capacity. With each shorted cell, battery capacity is reduced by a percentage equal to one over the total number of cells.

Gas Generation

A lead-acid battery cannot absorb all the energy from the charging source when the battery is nearing the completion of the charge. This excess energy dissociates water by way of electrolysis into hydrogen and oxygen. Oxygen is produced by the positive plate, and hydrogen is produced by the negative plate. This process is known as gassing.

Gassing is first noticed when cell voltage reaches 2.30–2.35 volts per cell and increases as the charge progresses. At full charge, the amount of hydrogen produced is about one cubic foot per cell for each 63 ampere-hours input. If gassing occurs and the gases are allowed to collect, an explosive mixture of hydrogen and oxygen can be readily produced. It is necessary, therefore, to ensure that the area is well ventilated and that it remains free of any open flames or spark-producing equipment.

As long as battery voltage is greater than 2.30 volts per cell, gassing will occur and cannot be prevented entirely. To reduce the amount of gassing, charging voltages above 2.30 volts per cell should be minimized (e.g., 13.8 volts for a 12-volt battery).

Battery Temperature

The operating temperature of a battery should preferably be maintained in the nominal band of 60 °F–80 °F. Whenever the battery is charged, the current flowing through the battery will cause heat to be generated by the electrolysis of water. The current flowing through the battery (I) will also cause heat to be generated (P) during charge and discharge as it passes through the internal resistance (Ri), as illustrated using the formula for power in the equation below.

P = I2Ri

Higher temperatures will give some additional capacity, but they will eventually reduce the life of the battery. Very high temperatures, 125 °F and higher, can actually do damage to the battery and cause early failure.

Low temperatures will lower battery capacity but also prolong battery life under floating operation or storage. Extremely low temperatures can freeze the electrolyte, but only if the battery is low in specific gravity.

Battery Disposal

The following is taken from DOE-HDBK-1084-95.

Disposal of lead-acid batteries should be performed according to all Federal, state, and local regulations. Lead-acid batteries should be reclaimed to avoid the regulatory requirements for hazardous waste treatment and disposal facilities. Reclamation is required by law in some states.

Page 38: Instrumentation and Control

27

The Federal regulations governing reclamation are found in 40 CFR 266, “Standards for the Management of Specific Hazardous Wastes and Specific Types of Hazardous Waste Management Facilities.” Persons who generate, transport, or collect spent batteries, or who store spent batteries but do not reclaim them are not subject to regulation under parts 262 through 266 or part 270, and also are not subject to the requirements of section 3010 of the RCRA.

Specific Component Applications

The following is taken from DOE-HDBK-1084-95.

A cell has five major components: the negative electrode, the positive electrode, the electrolyte, the separator, and the container.

The negative electrode supplies electrons to the external circuit (or load) during discharge. In a fully charged lead-acid storage battery, the negative electrode is composed of a sponge lead. The positive electrode accepts electrons from the load during discharge. In a fully charged lead-acid battery the positive electrode is composed of lead dioxide. It should be noted that the electrodes in a battery must be of dissimilar materials or the cell will not be able to develop an electrical potential and thus conduct electrical current. The electrolyte completes the internal circuit in the battery by supplying ions to the positive and negative electrodes. Dilute sulfuric acid is the electrolyte in lead-acid batteries. In a fully charged lead-acid battery, the electrolyte is approximately 25 percent sulfuric acid and 75 percent water.

The separator is used to electrically isolate the positive and negative electrodes. If the electrodes are allowed to come in contact, the cell will short-circuit and become useless because both electrodes would be at the same potential. The type of separator used varies by cell type. Materials used as separators must allow ion transfer between the electrolyte and electrodes. Many separators are made of a porous plastic or glass fiber material. The above components are housed in a container commonly called a jar or container.

Electrolyte Precautions

The following is taken from Concorde Battery, Battery Electrolyte Material Safety Data Sheet.

Electrolyte is corrosive and contact may cause skin irritation and chemical burns. Electrolyte causes severe irritation and burns of eyes, nose and throat. Ingestion can cause severe burns and vomiting.

Repeated contact with sulfuric acid battery electrolyte fluid may cause drying of the skin that may result in irritation, dermatitis, and skin burns. Repeated exposure to sulfuric acid mist may cause erosion of teeth, chronic eye irritation and/or chronic inflammation of the nose, throat and lungs.

c. Describe the relationship between voltage and current-carrying capacity for series-connected versus parallel-connected batteries.

The following is taken from DOE-HDBK-1011/2-92.

Page 39: Instrumentation and Control

28

When several cells are connected in series, the total voltage output of the battery is equal to the sum of the individual cell voltages. In the example of the battery in figure 9, the four 1.5-volt cells provide a total of 6 volts. When we connect cells in series, the positive terminal of one cell is connected to the negative terminal of the next cell. The current flow through a battery connected in series is the same as for one cell.

Source: DOE-HDBK-1011/2-92

Figure 9. Cells connected in a series

Cells connected in parallel give the battery a greater current capacity. When cells are connected in parallel, all the positive terminals are connected together, and all the negative terminals are connected together. The total voltage output of a battery connected in parallel is the same as that of a single cell.

Cells connected in parallel have the same effect as increasing the size of the electrodes and electrolyte in a single cell. The advantage of connecting cells in parallel is that it will increase the current-carrying capability of the battery.

d. Discuss the basic operation of alternating current (AC) and direct current (DC)generators. Include in the discussion the following elements of generator operation: Electromagnetic force Counter electromagnetic force Generator speed vs. frequency relationship Frequency control Generator field strength vs. output voltage relationship Field excitation Generator voltage regulation Generator protection circuitry and relaying

Page 40: Instrumentation and Control

29

AC Generator

The following is taken from DOE-HDBK-1011/3-92.

The elementary AC generator (figure 10) consists of a conductor, or loop of wire, in a magnetic field that is produced by an electromagnet. The two ends of the loop are connected to slip rings, and they are in contact with two brushes. When the loop rotates it cuts magnetic lines of force, first in one direction and then the other.

Source: DOE-HDBK-1011/3-92

Figure 10. Simple AC generator

The induced voltages add in series, making slip ring X (in figure 10) positive (+) and slip ring Y negative (-). The potential across resistor R will cause a current to flow from Y to X through the resistor. This current will increase until it reaches a maximum value when the coil is horizontal to the magnetic lines of force. The horizontal coil is moving perpendicular to the field and is cutting the greatest number of magnetic lines of force. As the coil continues to turn, the voltage and current induced decrease until they reach zero, where the coil is again in the vertical position (figure 11). In the other half revolution, an equal voltage is produced, but the polarity is reversed (figure 11). The current flow through R is now from X to Y (figure 10).

Page 41: Instrumentation and Control

30

Source: DOE-HDBK-1011/3-92

Figure 11. Developing a sine wave voltage

The periodic reversal of polarity results in the generation of a voltage, as shown in figure 11. The rotation of the coil through 360° results in an AC sine wave output.

DC Generator

The following is taken from DOE-HDBK-1011/2-92.

A basic DC generator has four basic parts: (1) a magnetic field; (2) a single conductor, or loop; (3) a commutator; and (4) brushes (figure 12). The magnetic field may be supplied by either a permanent magnet or an electromagnet. For now, we will use a permanent magnet to describe a basic DC generator.

Page 42: Instrumentation and Control

31

Source: DOE-HDBK-1011/2-92

Figure 12. Basic operation of a DC generator

Electromagnetic Force (EMF)

The following is taken from DOE-HDBK-1011/4-92.

A single conductor, shaped in the form of a loop, is positioned between the magnetic poles. As long as the loop is stationary, the magnetic field has no effect (no relative motion). If we rotate the loop, the loop cuts through the magnetic field, and an EMF (voltage) is induced into the loop.

When we have relative motion between a magnetic field and a conductor in that magnetic field, and the direction of rotation is such that the conductor cuts the lines of flux, an EMF is induced into the conductor. The magnitude of the induced EMF depends on the field strength and the rate at which the flux lines are cut. The stronger the field or the more flux lines cut for a given period of time, the larger the induced EMF.

The direction of the induced current flow can be determined using the left-hand rule for generators. This rule states that if you point the index finger of your left hand in the direction of the magnetic field (from north [N] to south [S]) and point the thumb in the direction of motion of the conductor, the middle finger will point in the direction of current flow (figure 13). In the generator shown in figure 13, for example, the conductor closest to the N pole is traveling upward across the field; therefore, the current flow is to the right, lower corner. Applying the left-hand rule to both sides of the loop will show that current flows in a counter-clockwise direction in the loop.

Page 43: Instrumentation and Control

32

Source: DOE-HDBK-1011/2-92

Figure 13 . Left-hand rule for generators

Counter Electromagnetic Force (Counter Electromotive Force)

The following is taken from DOE-HDBK-1011/2-92.

In a generator using a rotating armature, the conductors cut the magnetic lines of force in the magnetic field. Voltage is induced in the armature conductors. This induced voltage opposes the applied voltage; it counteracts some of the applied voltage, which reduces the current flow through the armature. This induced voltage acts counter to applied voltage; therefore, it is called counter-electromotive force.

Generator Speed vs. Frequency Relationship

The following is taken from DOE-HDBK-1011/3-92.

The frequency of the generated voltage is dependent on the number of field poles and the speed at which the generator is operated, as indicated in the following equation.:

f = 120

NP

where f = frequency (Hz) P = total number of poles N = rotor speed (rpm) 120 = conversion from minutes to seconds and from poles to pole pairs

The 120 in the equation is derived by multiplying the following conversion factors.

pairpole

poles2

utemin1

ondssec60

Page 44: Instrumentation and Control

33

In this manner, the units of frequency (hertz or cycles/second) are derived.

Frequency Control

The following is taken from DOE-HDBK-1011/3-92.

The frequency of an alternating voltage or current can be related directly to the angular velocity of a rotating coil. The units of angular velocity are radians per second, and 2π radians is a full revolution. A radian is an angle that subtends an arc equal to the radius of a circle. One radian equals 57.3 degrees. One cycle of the sine wave is generated when the coil rotates 2π radians.

Generator Field Strength vs. Output Voltage Relationship

The following is taken from DOE-HDBK-1011/3-92.

The magnitude of AC voltage generated by an AC generator is dependent on the field strength and speed of the rotor. Most generators are operated at a constant speed; therefore, the generated voltage depends on field excitation, or strength.

In a DC generator, the magnitude of the induced EMF depends on the field strength and the rate at which the flux lines are cut. The stronger the field or the more flux lines cut for a given period of time, the larger the induced EMF.

Field Excitation

The following is taken from DOE-HDBK-1011/3-92.

The signal output circuit, which controls field excitation of the AC generator, increases or decreases field excitation to either raise or lower the AC output voltage. The following is taken from DOE-HDBK-1011/2-92.

The magnetic fields in DC generators are most commonly provided by electromagnets. A current must flow through the electromagnet conductors to produce a magnetic field. In order for a DC generator to operate properly, the magnetic field must always be in the same direction.

Therefore, the current through the field winding must be direct current. This current is known as the field excitation current and can be supplied to the field winding in one of two ways. It can come from a separate DC source external to the generator or it can come directly from the output of the generator, in which case it is called a self-excited generator.

In a self-excited generator, the field winding is connected directly to the generator output. The field may be connected in series with the output, in parallel with the output, or in a combination of the two.

Separate excitation requires an external source, such as a battery or another DC source. It is generally more expensive than a self-excited generator. Separately excited generators are, therefore, used only where self-excitation is not satisfactory. They would be used in cases where the generator must respond quickly to an external control source or where the generated voltage must be varied over a wide range during normal operations.

Page 45: Instrumentation and Control

34

Generator Voltage Regulation

The following is taken from DOE-HDBK-1011/3-92.

The purpose of a voltage regulator is to maintain the output voltage of a generator at a desired value. As load on an AC generator changes, the voltage will also tend to change. The main reason for this change in voltage is the change in the voltage drop across the armature winding caused by a change in load current. In an AC generator, there is a IR drop and an IXL drop caused by the AC current flowing through the resistance and inductance of the windings. The IR drop is dependent on the amount of the load change only. The IXL drop is dependent on not only the load change, but also the power factor of the circuit. Therefore, the output voltage of an AC generator varies with both changes in load (i.e., current) and changes in power factor. Because of changes in voltage, due to changes in load and changes in power factor, AC generators require some auxiliary means of regulating output voltage.

[Note: IR = voltage drop on the line due to line resistance; in phase with the current. IX = voltage drop on the line due to line inductive resistance; leads the current by 90º.]

Generator Protection Circuitry and Relaying

The following is taken from DOE-HDBK-1011/4-92.

Protective relays are designed to cause the prompt removal of any part of a power system that might cause damage or interfere with the effective and continuous operation of the rest of the system. Protective relays are aided in this task by circuit breakers that are capable of disconnecting faulty components or subsystems.

Protective relays can be used for types of protection other than short circuit or overcurrent. The relays can be designed to protect generating equipment and electrical circuits from any undesirable condition, such as undervoltage, underfrequency, or interlocking system lineups.

There are only two operating principles for protective relays: (1) electromagnetic attraction and (2) electromagnetic induction. Electromagnetic attraction relays operate by a plunger being drawn up into a solenoid or an armature that is attracted to the poles of an electromagnet. This type of relay can be actuated by either DC or AC systems. Electromagnetic induction relays operate on the induction motor principle whereby torque is developed by induction in a rotor. This type of relay can be used only in AC circuits.

e. Discuss the basic operation of the various types of alternating current and direct current motors. Include in the discussion the following elements of motor operation as applicable to AC or DC motors: Electromagnetic force Counter electromagnetic force Starting current vs. running current Starting torque slip Current vs. load characteristics Variable speed operation Speed control Motor controller circuitry Applications of different types of motors

Page 46: Instrumentation and Control

35

AC Motor

The following is taken from DOE-HDBK-1011/4-92.

The principle of operation for all AC motors relies on the interaction of a revolving magnetic field created in the stator by AC current, with an opposing magnetic field either induced on the rotor or provided by a separate DC current source. The resulting interaction produces usable torque, which can be coupled to desired loads throughout the facility in a convenient manner.

DC Motor

The following is taken from DOE-HDBK-1011/2-92.

There are two conditions that are necessary to produce a force on a conductor: 1. The conductor must be carrying current. 2. The conductor must be within a magnetic field.

When these two conditions exist, a force will be applied to the conductor, which will attempt to move the conductor in a direction perpendicular to the magnetic field. This is the basic theory by which all DC motors operate.

Electromagnetic Force

The following is taken from DOE-HDBK-1011/1-92.

Figure 14 illustrates a three-phase stator to which a three-phase AC current is supplied.

The windings are connected in wye. The two windings in each phase are wound in the same direction. At any instant in time, the magnetic field generated by one particular phase will depend on the current through that phase. If the current through that phase is zero, the resulting magnetic field is zero. If the current is at a maximum value, the resulting field is at a maximum value. Since the currents in the three windings are 120° out of phase, the magnetic fields produced will also be 120° out of phase. The three magnetic fields will combine to produce one field, which will act upon the rotor. In an AC induction motor, a magnetic field is induced in the rotor opposite in polarity of the magnetic field in the stator. Therefore, as the magnetic field rotates in the stator, the rotor also rotates to maintain its alignment with the stator’s magnetic field.

Page 47: Instrumentation and Control

36

Source: DOE-HDBK-1011/1-92

Figure 14. Three phase stator

Counter Electromagnetic Force (Counter Electromotive Force)

The following is taken from DOE-HDBK-1011/2-92.

A generator action is developed in every motor. When a conductor cuts lines of force, an EMF is induced in that conductor. Current to start the armature turning will flow in the direction determined by the applied DC power source. After rotation starts, the conductor cuts lines of force. By applying the left-hand rule for generators, the EMF that is induced in the armature will produce a current in the opposite direction. The induced EMF, as a result of motor operation, is called counter electromotive force, or CEMF.

Since the CEMF is generated by the action of the armature cutting lines of force, the value of CEMF will depend on field strength and armature speed.

Starting Current vs. Running Current

The following is taken from DOE-HDBK-1011/2-92.

At the moment a DC motor is started, the armature is stationary and there is no CEMF being generated. The only component to limit starting current is the armature resistance, which in most DC motors is a very low value (approximately 1 ohm or less) as shown in this equation:

Ia = a

CEMFt

R

EE

Page 48: Instrumentation and Control

37

where Ia = armature current Et = terminal voltage ECEMF = counter EMF Ra = armature resistance

To reduce a very high starting current, an external resistance must be placed in series with the armature during the starting period. To show why this is essential, consider a 10-horsepower (hp) motor with an armature resistance of 0.4 ohms. If the motor were supplied by a 260 volt DC source, the resulting current would be as shown in the equations below.

Ia = a

CEMFt

R

EE

Ia =

4.0

0VDC260

Ia = 650 amps

where VDC = volt DC

This large current is approximately twelve times greater than actual full-load current for this motor. This high current would, in all probability, cause severe damage to the brushes, commutator, or windings. Starting resistors are usually incorporated into the motor design to limit starting current to 125–200 percent of full-load current.

The amount of starting resistance necessary to limit starting current to a more desirable value is calculated using the following equation:

Rs = s

t

I

E = Ra

where Rs = starting resistance Et = terminal voltage Is = desired armature starting current Ra = armature resistance

The starting resistors are used in a DC motor by placing them in the starting circuit of the motor controller that is used to start the DC motor. Starting resistors are normally of variable resistances, with the value of resistance in the circuit at any time being either manually or automatically controlled. The maximum amount of resistance will always be inserted when the motor is first started. As the speed of the motor increases, CEMF will begin to increase,

Page 49: Instrumentation and Control

38

decreasing armature current. The starting resistors may then be cut out, in successive steps,

tually impossible for the rotor of an AC induction motor to turn at the same speed as that of the rotating magnetic field. If the speed of the rotor were the same as that of the stator,

Without this induced EMF, there would be no interaction of fields to produce motion. The

The percentage difference between the speed of the rotor and the speed of the rotating

tor, as slip increases from zero to ~10%, the torque increases linearly. As the load and slip are increased beyond full-load torque, the torque will reach a maximum

The typical induction motor breakdown torque varies from 200 to 300 percent of full-load of torque at 100 percent slip and is normally 150 to

In general, the higher the inrush current, the lower the slip at which the motor can carry full

An increase in line voltage decreases the slip. A decrease in line voltage increases the slip. e decreases the heating of the motor. A decrease in line voltage

ey.

e

e that corresponds to a motor’s rated speed are available in certain standard voltages, which roughly increase in conjuntion with horsepower. Thus, the

until the motor reaches full running speed.

Starting Torque Slip

The following is taken from DOE-HDBK-1011/4-92.

It is vir

no relative motion between them would exist, and there would be no induced EMF in the rotor.

rotor must, therefore, rotate at some speed less than that of the stator if relative motion is to exist between the two.

magnetic field is called slip. The smaller the percentage, the closer the rotor speed is to the rotating magnetic field speed.

In an AC induction mo

value at about 25 percent slip. If load is increased beyond this point, the motor will stall andcome to a rapid stop.

torque. Starting torque is the value200 percent of full-load torque.

Current vs. Load Characteristics

The following is taken from Industrial Motor Control by Stephen L. Herman and Walter N. Alerich.

load, and the higher the efficiency. The lower the inrush current, the higher the slip at whichthe motor can carry full load, and the lower the efficiency.

An increase in line voltagincreases the heating of the motor.

Variable Speed Control

The following is taken from Overview of Motor Types Tutorial by Brian L Bol

Controlling the speed of a brushed DC motor is simple. The higher the armature voltage, thfaster the rotation. This relationship is linear to the motor’s maximum speed.

The maximum armature voltag

Page 50: Instrumentation and Control

39

smallest industrial motors are rated 90 VDC and 180 VDC. Larger units are rated at 250VDC and sometimes higher.

to the comparible AC

motor. This is partly due to the simplicity of control, but is also partly due to the fact that

In a brushed DC motor, torque control is also simple, since output torque is proportional to

The result of this design is that variable speed or variable torque electronics are easy to ufacture. Varying the speed of a brushed DC motor requires little more than a

tor is varied using external devices, usually field resistors. For a constant applied voltage to the field (E), as the resistance of the field (Rf) is lowered, the amount of current flow through the field (If) increases as shown by Ohm’s law in the following equation.

Specialty motors for use in mobile applications are rated 12, 24, or 48 VDC. Other tiny motors may be rated 5 VDC.

Most industrial DC motors will operate reliably over a speed range of about 20:1 -- down about 5-7 percent of base speed. This is much better performance than

most industrial DC motors are designed with variable speed operation in mind, and have added heat dissipation features which allow lower operating speeds.

current. If you limit the current, you have just limited the torque which the motor can achieve. This makes this motor ideal for delicate applications such as textile manufacturing.

design and manlarge enough potentiometer.

Speed Control

The following is taken from DOE-HDBK-1011/2-92.

The field of a DC mo

fr R

EI

An increase in field current will cause field flux (Φf) to increase. Conversely, if the resistanof the field is increased, f

ce ield flux will decrease. If the field flux of a DC motor is decreased,

the motor speed will increase. The reduction of field strength reduces the CEMF of the motor, since fewer lines of flux are being cut by the arm ture conductors, as shown in the following equation.

A reduction of counter EMF allows an increase in armature current as shown the following equation.

a

NKE FCEMF

a

CEMFta R

EEI

Page 51: Instrumentation and Control

40

This increase in armature current causes a larger torque to be developed; the increase in armature current more than offsets the decrease in field flux as shown in the following equation.

This increased torque causes the motor to increase in speed.

This increase in speed will then proportionately increase the CEMF. The speed and CEMF will continue to increase until the armature current and torque are reduced to values just large enough to supply the load at a new constant speed.

Speed control for an AC motor is expensive. The electronics required to handle an AC inverter drive are considerably more expensive than those required to handle a DC motor. However, if performance requirements can be met -- meaning that the required speed range is over 1/3rd of base speed -- AC inverters and AC motors are usually more cost-effective than DC motors and DC drives for applications larger than about 10 horsepower, because of cost savings in the AC motor.

Motor Controller Circuitry

The following is taken from DOE-HDBK-1011/4-92.

A manual controller is a controller whose contact assembly is operated by mechanical linkage from a toggle-type handle or a pushbutton arrangement. The controller is operated by hand.

The manual controller is provided with thermal and direct-acting overload units to protect the motor from overload conditions. The manual controller is basically an on-off switch with overload protection.

Manual controllers are normally used on small loads such as machine tools, fans, blowers, pumps, and compressors. These types of controllers are simple, and they provide quiet operation. The contacts are closed simply by moving the handle to the on position or pushing the start button. They will remain closed until the handle is moved to the off position or the stop button is pushed. The contacts will also open if the thermal overload trips.

Manual controllers do not provide low voltage protection or low voltage release. When power fails, the manual controller contacts remain closed, and the motor will restart when power is restored. This feature is highly desirable for small loads because operator action is not needed to restart the small loads in a facility; however, it is undesirable for larger loads because it could cause a hazard to equipment and personnel.

f. Discuss the purposes of a transformer.

According to DOE-HDBK-1011/4-92, transformers are used extensively for AC power transmissions and for various control and indication circuits.

aF IKT

Page 52: Instrumentation and Control

41

g. Discuss the basic operation of the various types of transformers. Include in the er operation and design:

nships between primary and secondary windings

Multiple secondary windings

Transformer ratings cooling requirements

g

he core. A transformer wound such as in figure 15, will operate at a greatly reduced efficiency due to the magnetic leakage. Magnetic leakage is the part of the magnetic flux that passes through either one of the coils, but not through both. The larger the distance between the primary and secondary windings, the longer the magnetic circuit and the greater the leakage.

discussion the following elements of transform Theory of operation Magnetic coupling Voltage/current relatio Purposes of a transformer Step-up vs. step-down transformer design

Transformer tap changers

Transformer Current transformers vs. potential transformers

The following descriptions and definitions are taken from DOE-HDBK-1011/4-92.

Theory of Operation

A transformer works on the principle that energy can be transferred by magnetic induction from one set of coils to another set by means of a varying magnetic flux. The magnetic flux is produced by an AC source.

The coil of a transformer that is energized from an AC source is called the primary windin(coil), and the coil that delivers this AC to the load is called the secondary winding (coil) (figure 15). In figure 15, the primary and secondary coils are shown on separate legs of the magnetic circuit so that we can easily understand how the transformer works. Actually, half of the primary and secondary coils are wound on each of the two legs, with sufficient insulation between the two coils and the core to properly insulate the windings from one another and t

Source: DOE-HDBK-1011/4-92

Figure 15. Core-type transformer

Page 53: Instrumentation and Control

42

Magnetic Coupling

The following is taken from Troubleshooting and Repairing Computer Printers by StephenL. Bigelow.

A transformer is actually a combination of inductors working together. It is composed ofseveral important parts: a primary winding, a secondary winding, and a core structure. An

AC voltage is applied across the primary winding. The AC voltage is constantly changing its nerated in a

.

Voltage/Current Relationships between Primary and Secondary Windings

n. wing around the entire length of the magnetic circuit induces a

voltage in both the primary and secondary windings. Since both windings are linked by the ed per turn of the primary and secondary windings must be the

used extensively for AC power transmissions and for various control and indication circuits.

The following is taken from DOE-HDBK-1011/4-92.

The voltage of the windings in a transformer rtional to the number of turns on the coils. This relationship is expressed in the following equation:

value and reversing its polarity over time. As a result, the magnetic field geprimary coil also fluctuates. When the fluctuating magnetic field intersects a secondary winding, an AC voltage is recreated across it. This principle is known as magnetic coupling

According to DOE-HDBK-1011/4-92, the coil of a transformer that is energized from an ACsource is called the primary winding (coil), and the coil that delivers this AC to the load is called the secondary winding (coil).

When alternating voltage is applied to the primary winding, an alternating current will flow that will magnetize the magnetic core, first in one direction and then in the other directioThis alternating flux flo

same flux, the voltage inducsame value and same direction. This voltage opposes the voltage applied to the primary winding and is CEMF.

Purposes of a Transformer

According to DOE-HDBK-1011/4-92, transformers are

Step-Up vs. Step-Down Transformer Design

is directly propo

s

p

V

V =

s

p

N

N

where VP = voltage on primary coil Vs = voltage on secondary coil Np = number of turns on the primary coil Ns = number of turns on the secondary coil

The ratio of primary voltage to secondary voltage is known as the voltage ratio. As mentioned previously, the ratio of primary turns of wire to secondary turns of wire is known as the turns ratio. By substituting into the equation, we find that the voltage ratio is equal to the turns ratio.

Page 54: Instrumentation and Control

43

A voltage ratio of 1:5 means that for each volt on the primary, there will be 5 volts on the secondary. If the secondary voltage of a transformer is greater than the primary voltage, the transformer is referred to as a step-up transformer. A ratio of 5:1 means that for every 5 volts

be 1 volt on the secondary. When secondary voltage is less mer.

le

-

hich were required to supply low voltage for the tubes’ filaments from a nominal primary voltage of 110 volts AC. Not only are voltages and currents of completely different

h a transformer, but all circuits are electrically isolated from one

to

imits. Tap changers offer variable control to keep the supply voltage within these limits. About 96 percent of all power transformers today above 10 megavolts-amperes

gers generally consist of a diverter switch and a selector switch operating as a unit to effect transfer current from one voltage tap to the next. It was more than 60 years

r transformers as a means of on load

1. Some form of impedance is present to prevent short circuiting of the tapped section.

e tap changer with a resistive type of impedance uses high-speed switching, whereas the reactive type uses slow

on the primary, there will only than primary voltage, the transformer is referred to as a step-down transfor

Multiple Secondary Windings

The following is taken from All About Circuits, Winding Configurations.

Transformers are very versatile devices. The basic concept of energy transfer between mutual inductors is useful enough between a single primary and single secondary coil, but transformers don’t have to be made with just two sets of windings. In some transformer circuits, three inductor coils share a common magnetic core, magnetically coupling or linking them together. The relationship of winding turn ratios and voltage ratios seen with a singpair of mutual inductors still holds true here for multiple pairs of coils. It is entirely possible to assemble a transformer in which one secondary winding is step-down and the other is stepup. In fact, this design of transformer was quite common in vacuum tube power supply circuits, w

magnitudes possible with sucanother.

Transformer Tap Changers

The following is taken from Wilson Power Solutions, What a Transformer Tap ChangerIis and What It Does.

A tap changer is a device fitted on power transformers for regulation of the output voltagerequired levels. This is normally achieved by changing the ratios of the transformers on the system by altering the number of turns in one winding of the appropriate transformer(s). Supply authorities are under obligation to their customers to maintain the supply voltage between certain l

incorporate on load tap changers as a means of voltage regulation. Tap changers can be on load or off load.

On load tap chan

ago on load tap changers were introduced to powevoltage control.

Tap changers possess two fundamental features:

2. A duplicate circuit is provided so that the load current can be carried by one circuit whilst switching is being carried out on the other.

The impedance mentioned above can either be resistive or reactive. Th

Page 55: Instrumentation and Control

44

moving switching. High-speed resistor switching is now the most popular method usworldwide, and hence it is the method

ed that is reviewed in this report.

y be located at one of the following locations, of winding:

At the line end of the winding

The most common types of arrangements are the last two. This is because they give the least

located at either the low voltage or high voltage nnected to the primary or secondary side windings of the

er on of tap changer in the winding

ted with different tap changer configurations Step voltage and circulating currents

most power supplies, a voltage regulator is used, which provides extra ripple reduction so that an

pply designers.

condary winding varies with the type of rectifier single-phase circuits are

full wave center tap (two diodes)

terval and the unidirectional DC current in the transformer secondary winding require a larger transformer core to avoid saturation.

is not very popular, and the only time it may be worth

The tapped portion of the winding madepending upon the type

In the middle of the winding At the star point

electrical stress between the tap changer and earth along with subjecting the tapings to less physical and electrical stress from fault currents entering the line terminals.

At lower voltages the tap changer may bewindings. Tap changers can be cotransformer depending on Current rating of the transformer Insulation levels present Type of winding within the transform Positi Losses associa

Cost Physical size

Transformer Ratings

The following is taken from PowerVolt, How to Determine Power Supply Transformer Ratings.

The transformer ratings depend upon the type of filter and rectifier configuration used. The commonly used filter types are inductor and capacitor input filters. However, due to increased weight and cost considerations, the inductor filter is not very popular. In

inductor-capacitor filter is not required. As a result, a capacitive filter is sufficient for a majority of the applications and is very popular among power su

The current drawn from the transformer secircuit used. The most commonly used half-wave (single diode)

full wave bridge (four diodes) dual complementary rectifier

The half-wave rectifier is simple and less costly than the other types. However, very high current spikes during the capacitive charging in

Consequently, the half-wave rectifierconsidering is for power levels below 1 watt.

Page 56: Instrumentation and Control

45

Transformer Cooling Requirements

The following is taken from Transformers and Motors by George Patrick Shultz.

All transformers must be equipped with some method for cooling. Heat decreases the transformer’s efficiency and reduces the unit’s life expectancy. Operating the transformer

allows for a great kilovolt ampere capacity to be delivered to the

ded for the area in which the transformer is to be installed. In this event, the ventilation system of the room should be inspected to make sure it is operating properly.

be clear of any obstructions that may prevent the heat from

to be inspected and tested to determine if the motors operate within the preset temperature ranges. Manufacturers’

ollowed for making these tests. When located in closed vaults,

e tests, er if water is to be used to provide the

pressure. Care must be taken not to damage the coils when removing or replacing them. If the

ling system can be checked. The coils are filled with water under pressure of 80 to 100 pounds per square inch (psi) and

A very small amount of moisture, 0.06 percent, will reduce the dielectric strength of the oil

Associated equipment with the water-cooled system also needs to be checked, including the and the alarm system. In addition, make

pressure.

below rated temperature load.

Dry-Type Transformers

For dry-type transformers, no particular check is necessary if conditions for ventilation have been provi

Transformer radiator vents should escaping.

Forced Air

If the cooling system consists of forced air for maintaining the temperature of the transformer, the motors should be checked for proper lubrications and operation. These motors will often be controlled by thermostats that also need

specifications are to be fmeans should be provided to exchange the air in the vaults.

Water-Cooled Systems

Water-cooled systems must be tested for leaks and proper operations. To make thesthe cooling coils should be removed from the transform

coils are to be checked in the transformer, air or the type of coolant oil used by the transformer can be used to make the pressure checks.

If the coils are removed from the transformer, the total water coo

they are checked for leaks. The coils remain under pressure for at least 1 hour to assure that no leaks will develop. A drop in pressure would indicate a leak.

by 50 percent. Moisture content beyond this point does not cause the dielectric strength of theoil to deteriorate much more.

water pump, pressure gauges, temperature gauges, sure there is a water source with an adequate flow and

Current Transformers vs. Potential Transformers

The following is taken from DOE-HDBK-1011/4-92.

Page 57: Instrumentation and Control

46

The current transformer steps down the current of a circuit to a lower value and is used insame types

the of equipment as a potential transformer. This is done by constructing the

secondary coil, consisting of many turns of wire, around the primary coil, which contains

signed for low-magnetizing current when under load, this large increase in magnetizing current will build up a large flux

ucing an

The potential transformer steps down voltage of a circuit to a low value that can be

ecific transformer designs to the following types of

circuits power

r phase configuration to another. They can include features for electrical isolation, power distribution, and control and instrumentation applications. Transformers

ple of magnetic induction between coils to convert voltage and/or

s ts

nsing

t power voltage falls below the predetermined threshold level, thereby assuring that certain core portions of

en the power supply goes below the predetermined threshold level

only a few turns of wire. In this manner, measurements of high values of current can be obtained.

A current transformer should always be short-circuited when not connected to an external load. Because the magnetic circuit of a current transformer is de

in the magnetic circuit and cause the transformer to act as a step-up transformer, indexcessively high voltage in the secondary when under no load.

effectively and safely used for operation of instruments such as ammeters, voltmeters, watt meters, and relays used for various protective purposes.

h. Discuss the application of spelectrical/electronic circuitry: Instrumentation power Voltage sensing circuits Current sensing Control circuitry Circuits requiring fault isolation protection

Instrumentation Power

According to DOE-HDBK-1011/4-92, power transformers convert power-level voltages from one level o

typically rely on the princicurrent levels.

Voltage Sensing Circuits

The following is taken from Patent Storm, US Patent 6147529 - Voltage Sensing Circuit.

Usually, voltage-sensing circuits are utilized to sense power up and power down operationin the application of integrated circuitry applications, and, accordingly, enable other circuito perform the corresponding actions if required. In the power up mode, the voltage-secircuit receives an input voltage signal, generating an enable output signal when the input voltage signal has exceeded a predetermined threshold level. Before that, when the input voltage signal is below the predetermined threshold level, the voltage-sensing circuit generates a disable signal to disable core portions of the integrated circuit so as to prevent uncertain functioning due to either voltage level or system noise. In the power down mode, the voltage-sensing circuit generates the disable output signal when the inpu

the circuit are disabled whand preventing uncertain functioning due to voltage level or system noise.

Page 58: Instrumentation and Control

47

Current Sensing Circuits

The following is taken from Texas Instruments, What is a Current Sensing Circuit and Howis it Used?

onitor the current flow by measuring the voltage drop across a rent

that is proportional to the current through the measured path.

The components of many appliances are administered by some kind of control circuitry.

.

Control circuitry power consumption depends on the complexity of the system. In general, ver, because portions of circuitry, and even

s remain powered, even the most complex circuitry needs a very small amount of power to respond when needed.

ted and destroyed by the current passing through it. A fuse contains a current carrying element sized so that the heat generated by the flow of normal current through it

, when an overcurrent or short-circuit current pes

uses and the Circuits They Protect

The plug fuse is a fuse that consists of a zinc or alloy strip, a fusible element enclosed in

The cartridge fuse is constructed with a zinc or alloy fusible element enclosed in a cylindrical ends of the tube.

used on circuits rated at either 250 volts or 600 volts and has a t-carrying capacity of 600 amps.

ollowing as backup power supplies: erters

Current-sensing circuits mresistor placed in the current’s path. The current sensor outputs either a voltage or a cur

Control Circuitry Power

The following is taken from Lawrence Berkeley National Laboratory, Standby Power.

Most home appliances have very simple control circuitry, consisting of a single micro-controller chip and its firmware. An exception to this case is the computer, which uses a much more complex system of circuitry and integrated circuit chips to control the system

more and bigger chips need more power. Howeportions of chips, can be shut down while other portion

Circuits Requiring Fault Isolation Protection

The following is taken from DOE-HDBK-1011/4-92.

A fuse is a device that protects a circuit from an overcurrent condition only. It has a fusible link directly hea

does not cause it to melt the element; howeverflows through the fuse, the fusible link will melt and open the circuit. There are several tyof fuses in use.

Types of F

porcelain or pyrex housing, and a screw base. This type of fuse is normally used on circuits rated at 125 V or less to ground and has a maximum continuous current-carrying capacity of30 amps.

fiber tube with the element ends attached to a metallic contact piece at the This type of fuse is normallymaxi nmum continuous curre

i. Discuss application of the f UPS inv Diesel generators Motor generators Auto transfer switches

Page 59: Instrumentation and Control

48

UPS Inverters

The following is taken from Technical Specifications for the Supply of an UninterrupPower System Composed of Thre

tible e-Phase Modules in Parallel Configuration.

les the tolerances of different output parameters (i.e., voltage, ed. Each inverter consists of a three-phase

frequency converter fitted with

s ents.

pass). Once returned to a normal state, the load is automatically supplied by the inverters. In the case of a non-

circuit, the inverters must be shut off by their electronic protection after full battery discharge, the UPS

will restart automatically when the mains supply is restored.

and

wer diesel generator engines that can supply emergency power to all the important and selected loads during a critical process

ese power units are used in almost all types of industries and commercial ese needs

are fulfilled through this backup diesel generator engine.

The UPS inverter design enabdistortion rates, frequency) to be maintain

a power converter bridge with insulated gate bipolar-type transistors a parallel series filter control and command electronics

The operating principle is based on pulse width modulation. The oscillator provides the frequency reference and is synchronized with the main’s frequency when this is within tolerance. It operates autonomously when the main is out of tolerance or absent.

It is also possible to desynchronize its operating when, for example, the UPS supply iprovided by a generator set, the stability of which is incompatible with the load requiremIn cases of sharp current build, and before the inverter voltage exceeds its tolerance, the load is transferred to the mains without interruption (automatic by-

discriminated short-without any deterioration. After the inverter has stopped

Diesel Generators

The following is taken from Diesel Generator Engine.

Diesel generator engines are basically designed to meet the power requirements of small- medium-sized companies and heavy usage needs for larger industries. The generator is aninnovative product which brings affordable and clean standby power that can be easilyaccessed by millions of industries, small businesses, and homes. The easy installation of generators and the reduced cost of back up power have made generators in demand from different areas of usage. There are a number of modern diesel generator engines that are specifically engineered to fulfill emergency power requirements. These types of units constantly monitor the electrical current, and they automatically start up when the power is interrupted or is shut off. There are some specific high-po

of the industries. Thsectors, whether big or small, which have uninterrupted power requirements, and th

Motor Generators

The following is taken from Encyclopedia Britannica, Motor Generator.

A motor generator is an electric motor coupled to an electric generator to convert electric power from one from to another. The motor operates from the available electric power source, and the generator provides power of the characteristics desired for the load. For

Page 60: Instrumentation and Control

49

example, a set may be designed to convert commercially available alternating current to ay provide high-frequency alternating

current power for induction heating. Such a combination has been termed a dynamotor. In

a driving motor, such as a gasoline or diesel engine.

The transfer switch has five positions that alter the mode of operation. The indication is

of operation. Also, the deviation meter indicates any deviation between

controlled variable and setpoint.

meter deflects full down for zero variable value, and full up for 100 percent variable value.

output is now varied by adjusting the manual output adjust knob. This adjustment is indicated on the

BAL. In many cases, controller output signals of the automatic mode and manual mode may

n

is can cause large swings in the value of the process variable and possible

gear.

The following is taken from Institute of Electrical and Electronics Engineers (IEEE) Std.

A power switchgear assembly consists of a complete assembly of one or more of the above

direct current, as in some welding applications; or it m

some sets, there may be more than one coupled generator. Motor generator is also used todenote an electric generator and

Auto Transfer Switches

The following is taken from DOE-HDBK-1013/2-02.

provided by a deviation meter.

AUTO. This is the normal position of the transfer switch. It places the controller in theautomatic mode

0 - 100 (AUTO side). In this position, the controller is still in automatic mode. However, the deviation meter now indicates the approximate value of the controlled variable. The deviation

MAN. This position places the controller in the manual mode of operation. Controller

output meter. The deviation meter indicates any deviation between controlled variable and setpoint.

0 - 100 (MAN side). The controller is still in the manual mode of operation, and the deviationmeter indicates controlled variable value as it did in the 0-100 (AUTO side) position.

not be the same. If the controller were directly transferred from automatic to manual or manual to automatic, the controller output signal could suddenly change from one value toanother. As a result, the final control element would experience a sudden change in positioor bump. Thdamage to the final control element.

j. Identify and discuss the operation of the different types of electrical switch

141-1993.

“Switchgear” is a general term that describes switching and interrupting devices, either aloneor in combination with other associated control, metering, protective, and regulating equipment, which are assembled in one or more sections.

noted devices and main bus conductors, interconnecting wiring, accessories, supporting structures, and enclosure. Power switchgear is applied throughout the electric power systemof an industrial plant, but is principally used for incoming line service and to control and

Page 61: Instrumentation and Control

50

protect load centers, motors, transformers, motor control centers, panelboards, and other secondary distribution equipment.

Outdoor switchgear assemblies can be of the non-walk-in or walk-in variety. Switchgear for

ffect of external influences, principally the sun, wind, moisture, and local ambient temperatures,

ered in determining the suitability and current-carrying capacity of the

fect of outdoor locations.

does not have an enclosure as part of the supporting structure. Since open switchgear assemblies are rarely used in industrial installations,

d switchgear assembly consists of a metal-enclosed supporting structure with the switchgear enclosed on the top and all sides with sheet metal. Access within the enclosure is

.

tal-enclosed switchgear used in industrial plants are defined as (1) metal

ng

ling primary and secondary

ol power transformers, are enclosed , or as cuit

opened.

industrial plants is generally located indoors for easier maintenance, avoidance of weather problems, and shorter runs of feeder cable or bus duct. In outdoor applications the e

should be considswitchgear.

In many locations, the use of lighter colored (non-metallic) paints will minimize the efsolar energy loading so as to avoid derating of the equipment in

Classifications

An open switchgear assembly is one that

consideration will be given to metal-enclosed assemblies only.

An enclose

provided by doors or removable panels

Metal-enclosed switchgear is universally used throughout industry for utilization and primarydistribution voltage service, for AC and DC applications, and for indoor and outdoor locations.

Types of Metal-Enclosed Switchgear

Specific types of meclad switchgear, (2) low-voltage power circuit breaker switchgear, and (3) interrupter switchgear. The metal-enclosed bus will also be discussed because it is frequently used inconjunction with power switchgear in modern industrial power systems.

Metal-clad switchgear is metal-enclosed power switchgear characterized by the followinecessary features: The main circuit switching and interrupting device is of the removable type arranged

with a mechanism for moving it physically between connected and disconnected positions, and equipped with self-aligning and self-coupdisconnecting devices.

Major parts of the primary circuit, such as the circuit switching or interrupting devices, buses, potential transformers, and contrby grounded metal barriers. Specifically included is an inner barrier in front ofa part of, the circuit interrupting device to ensure that no energized primary circomponents are exposed when the unit door is

All live parts are enclosed within grounded metal compartments. Automatic shuttersprevent exposure of primary circuit elements when the removable element is in the test, disconnected, or fully withdrawn position.

Page 62: Instrumentation and Control

51

Primary bus conductors and connections are covered with insulating material throughout. For special configurations, insulated barriers between phases and between phase and ground may be specified.

Mechanical interlocks are provided to ensure a proper and safe operating sequence. d

it elements, with the exception of

r relay panel and may also provide access to a secondary or control compartment within the housing.

an be

ar

of 1000 V and below is metal-enclosed

it breakers of 1000 V and below (fused or unfused) Non-insulated bus and connections (insulated and isolated bus is available)

r line-side contacts when the circuit breaker is withdrawn

y be stationary (fixed or plug-in). When cal interlocks must be provided to ensure a

Metal-enclosed interrupter switchgear is metal-enclosed power switchgear, including the

er fuses (if required) Non-insulated bus and connections

the

Instruments, meters, relays, secondary control devices, and their wiring are isolateby grounded metal barriers from all primary circushort lengths of wire associated with instrument transformer terminals.

The door through which the circuit-interrupting device is inserted into the housing may serve as an instrument o

Auxiliary frames may be required for mounting associated auxiliary equipment, such as potential transformers, control power transformers, etc.

All metal-clad switchgear is metal-enclosed, but not all metal-enclosed switchgear ccorrectly designated as metal-clad.

Low-Voltage Power Circuit Breaker Switchge

Metal-enclosed power circuit breaker switchgearpower switchgear, including the following equipment as required: Power circu

Instrument and control power transformers Instruments, meters, and relays Control wiring and accessory devices Cable and busway termination facilities Shutters to automatically cove

The power circuit breakers of 1000 V and below are contained in individual grounded metal compartments and controlled either remotely or from the front of the panels. The circuit bre rake s are usually of the drawout type, but ma

used, mechanidrawout-type circuit breakers are proper and safe operating sequence.

Interrupter Switchgear

following equipment as required: Interrupter switches or circuit switchers Pow

Instrument and control power transformers Control wiring and accessory devices

The interrupter switches and power fuses may be of the stationary or removable type. For removable type, mechanical interlocks are provided to ensure a proper and safe operating sequence.

Page 63: Instrumentation and Control

52

k. Identify and discuss the operation of the different types of circuit breakers.

The following is taken from DOE-HDBK-1011/4-92.

ommonly used in place of fuses and sometimes eliminate the need for a

the arc when the breaker contacts open.

Low-Voltage ACBs

A low-voltage ACB is one which is suited for circuits rated at 600 volts or lower. One of the most commonly used low-voltage ACBs is the molded case circuit breaker.

A cutaway view of the molded case circuit breaker is shown in figure 16.

The purpose of a circuit breaker is to break the circuit and stop the current flow when the current exceeds a predetermined value without causing damage to the circuit or the circuit breaker.

Circuit breakers are cswitch. A circuit breaker differs from a fuse in that it trips to break the circuit and may be reset, while a fuse melts and must be replaced.

Air circuit breakers (ACBs) are breakers where the interruption of the breaker contacts takes place in an air environment. Oil circuit breakers (OCBs) use oil to quench

Source: DOE-HDBK-1011/4-92

Figure 16. Cutaway view of a molded case circuit breaker

A circuit can be connected or disconnected using a circuit breaker by manually moving the operating handle to the on or off position. All breakers, with the exception of very small ones, have a linkage between the operating handle and contacts that allows a quick make

Page 64: Instrumentation and Control

53

(quick break contact action) regardless of how fast the operating handle is moved. Thhandle is also designed so that it cannot be held shut on a short-circuit or overload condition. If the circuit breaker opens under one of these conditions, the handle will go to the trip-free position. The trip-free position is midway between the on and off positions and cannot be rshut until the handle is pushed to the off position and reset.

A circuit breaker will automatically trip when the current through it exceeds a pre-determined value. In low

e

e-

er current ratings, automatic tripping of the circuit breaker is accomplished by use of thermal tripping devices. Thermal trip elements consist of a

oes

e then be opened by spring action. This bimetallic

element, which is responsive to the heat produced by current flowing through it, has an

f o

small enched. This action extinguishes the arc rapidly, which minimizes the

chance of a fire and also minimizes damage to the breaker contacts.

are six

ize. The continuous current rating of a breaker is governed by the trip element rating. The range of

hese circuit breakers are available in much higher continuous current and interrupting ratings than the molded case circuit breaker. Breakers of this type have current

kers use a closing device, known as a stored energy mechanism, for fast, positive closing action. Energy is stored by compressing large powerful coil springs that

bimetallic element that can be calibrated so that the heat from normal current through it dnot cause it to deflect. An abnormally high current, which could be caused by a short-circuit or overload condition, will cause the element to deflect and trip the linkage that holds thcircuit breaker shut. The circuit breaker will

inverse-time characteristic. If an extremely high current is developed, the circuit breaker will be tripped very rapidly.

For moderate overload currents, it will operate more slowly. Molded case breakers with much larger current ratings also have a magnetic trip element to supplement the thermal trip element. The magnetic unit utilizes the magnetic force that surrounds the conductor to operate the circuit breaker tripping linkage.

When the separable contacts of an air circuit breaker are opened, an arc develops between thetwo contacts. Different manufacturers use many designs and arrangements of contacts and their surrounding chambers. The most common design places the moving contacts inside oan arc chute. The construction of this arc chute allows the arc formed as the contacts open tdraw out into the arc chute. When the arc is drawn into the arc chute, it is divided into segments and qu

Molded case circuit breakers come in a wide range of sizes and current ratings. Thereframe sizes available: 100, 225, 400, 600, 800, and 2,000 amps. The size, contact rating, andcurrent-interrupting ratings are the same for all circuit breakers of a given frame s

voltage available is from 120 to 600 volts, and interrupting capacity ranges as high as 100,000 amps.

Much larger air circuit breakers are used in large commercial and industrial distribution systems. T

ratings as high as 4,000 amps, and interrupting ratings as high as 150,000 amps.

Most large air circuit brea

are attached to the contact assembly of a circuit breaker. Once these springs are compressed, the latch may be operated to release the springs, and spring pressure will shut the circuit breaker.

Page 65: Instrumentation and Control

54

Circuit breaker closing springs may be compressed manually or by means of a small electric motor. This type of circuit breaker can be classified as either a manually or electrically operated circuit breaker.

When a large air circuit breaker is closed, the operating mechanism is latched. As the circuit

operated solenoid trip coil.

e operated at frequent intervals or when

3.

a supply voltage is converted and/or

The following is taken from the Electronics Club, Power Supplies.

There are many types of power supplies. Most are designed to convert high-voltage AC mains electricity to a suitable low-voltage supply for electronic circuits and other devices. A power supply can by broken down into a series of blocks, each of which performs a particular function.

atly to

e digitally controlled power sources that provide accurate and adjustable levels of voltage, current, and frequency. They include a processor,

s

breaker is closed, a set of tripping springs or coils are compressed, and the circuit breaker may then be tripped by means of a trip latch. The trip latch mechanism may be either manually or remotely by means of a

Circuit breakers may be operated either manually or electrically. Electrically operated circuit breakers are used when circuit breakers are to bremote operation is required.

Instrumentation and control personnel shall demonstrate a working level knowledge of the characteristics and applications of electrical components used in instrumentation and control systems.

a. Discuss the various methods through which reduced for use in an electronic circuit.

For example, consider a 5-volt regulated supply:

A transformer steps down high-voltage AC mains to low-voltage AC. A rectifier converts AC to DC, but the DC output is varying. Smoothing stabilizes the DC from varying gremaking only a small ripple. A regulator eliminates ripple by setting DC output to a fixed voltage.

The following is taken from GlobalSpec, Programmable Power Supplies.

Programmable power supplies ar

voltage/current programming circuits, current shunt, and voltage/current read-back circuits. Remote sensing functions compensate for voltage drops in the load leads by providing feedback of the actual voltage at the load. Over-voltage and over-current protection mode

Page 66: Instrumentation and Control

55

are also available. Comparators continuously monitor the output voltage against a program reference value. If the output value exceeds the reference value, a trigger signal is sent to a silicon-controlled rectifier across the output, shutting off the source to the load. Most programmable power supplies are subjected to extensive testing and burn-in periods to ensure long-term performance.

Programmable power supplies can provide AC, DC, or both AC and DC outputs. Typically,

C

t,

terfaces its

lly,

that can result in undesirable outputs.

d equipment testing, certification, and calibration applications. Devices that are capable of following complex

e r-

ace

a

input voltage stability is not critical. Voltage multipliers can receive an input voltage directly from a power source, but often use a transformer to minimize potential

e

tuplers

AC outputs are either single-phase or three-phase. Single-phase power is often used for low voltage applications. Three-phase power is often used with high voltage power supplies. Waveform outputs include sine waves, square waves, and triangular waves. Important Aoutput specifications include output voltage, voltage accuracy, output frequency, and output current. Important DC output specifications include output voltage, voltage accuracy, currenand power. Apparent power is the product of the root mean square (RMS) current and theRMS voltage of the AC output. Efficiency is the AC output power divided by the input apparent power.

Programmable power supplies are available a variety of special features. Computer inprovide remote monitoring and control. Overcurrent protection is internal circuitry that limor shuts down the current output during overcurrent conditions. Similarly, overvoltage protection limits or shuts down the voltage output during overvoltage conditions. Typicaovervoltage protection is provided for the primary output. Pure sine output produces a very high quality, pure sine waveform output. Short circuit protection may include electronic current limiting and thermal resets with automatic recovery. Temperature-compensated devices balance changes in temperature

Programmable power supplies are used in a variety of automate

output profiles are also used in highly specialized applications such as crystal growth and differential thermal analysis at high pressures. Some programmable power supplies armodular, board-mounted, or include a floor-standing cabinet. Others are wall-mounted, floomounted, or sit on a desktop or shelf. Open-frame and enclosed units are also available. Programmable power supplies can include a serial interface such as general-purpose interfbus as well as integral software.

The following is taken from Global Spec, Voltage Multipliers.

Voltage multipliers are AC to DC converters that produce high-potential DC voltage fromlower voltage, AC source. They are used with constant, high-impedance loads and in applications where

hazards. The ratio of the output voltage to the input voltage determines whether a voltage multiplier is categorized as a voltage doubler, a voltage tripler, a voltage quadrupler, or a voltage pentupler. For example, voltage doublers are voltage multipliers whose output is twice the peak input voltage. Half-wave voltage doublers usually contain two half-wave voltage rectifiers. In full-wave voltage doublers, the capacitors are connected in parallel withthe output load. Voltage triplers contain additional series-aiding devices and can provideither positive alternation or negative alteration. Voltage quadruplers and voltage penare also available.

Page 67: Instrumentation and Control

56

Specifications for voltage multipliers include number of stages, AC input voltage, AC inpufrequency, DC output voltage, DC output power, temperature range, and integrated circuipackage type. Products are designated as ha

t t

lf-wave or full-wave and series or parallel. Multi-stage voltage multipliers can have 4, 6, 8 or 10 stages. Half wave voltage multipliers exert

llel

maximum output ses

arry specifications for applications and approvals. Products with high-ften used as the anode of cathode ray tubes in radar scopes,

levisions. Voltage multipliers can also be used as the primary power nput is rectified to pulsating DC.

atic diagram of a typical instrumentation and control circuit, ollowing electrical components in the circuit and discuss its , and rating as applicable:

Power supplies Solenoids Indicating lights

This is a performance-based KSA. The Qualifying Official will evaluate its completion.

Figure 17 shows the common symbols for relays, contacts, connectors, lines, resistors, and other miscellaneous electrical components.

uniform stress on components such as diodes and capacitors. Full wave voltage multipliers also exert uniform stress on components, but are suitable for higher voltages. Paramultipliers require a higher voltage rating on each successive stage, but require less capacitance per stage. The capacitors’ voltage capability determines thevoltage. With half wave parallel multipliers, the voltage stress on the capacitors increawith each successive stage. IC package types for voltage multipliers include dual in-line package and ceramic dual in-line package.

Voltage multipliers cre ovoltage outputs a

oscilloscopes and teent where the VAC isupply in equipm

b. Given a schemidentify each of the f

etersfunction, param Resistors Capacitors Relays Contacts Fuses Switches Diodes

Page 68: Instrumentation and Control

57

Source: DOE-HDBK-1011/1-92

Figure 17. Electric schematic symbols

For additional information, refer to DOE-HDBK-1016/1-93, DOE Fundamentals Handbook: Engineering Symbology, Prints, and Drawings, volumes 1 and 2, January 1993.

Page 69: Instrumentation and Control

58

c. Discuss the application of the various types of circuit breakers and fuses used in the power supplies to instrumentation and control circuits. Include in this discussion the circuit requirements for the sizing, ratings, and characteristics of these power-interrupting devices.

Refer to competency statement 2k for a discussion of circuit breakers. Fuses are discussed in competency statement 2h.

d. Describe how different types of relays are used in instrumentation and control circuits to accomplish the following functions. Include in the discussion the relay characteristics required for each application. Logic control Signal isolation Electrical protection Electrical switching Time delays Alarm annunciation Indication actuation

Logic Control

The following is taken from All About Circuits, Programmable Logic Controllers (PLCs).

Before the advent of solid-state logic circuits, logical control systems were designed and built exclusively around electromechanical relays. Relays are far from obsolete in modern design, but have been replaced in many of their former roles as logic-level control devices, relegated most often to those applications demanding high current and/or high-voltage switching.

Instruments and controls requiring on/off control abound in modern commerce and industry, but such control systems are rarely built from either electromechanical relays or discrete logic gates. Instead, digital computers fill the need, which may be programmed to do a variety of logical functions.

In the late 1960s an American company named Bedford Associates released a computing device they called the MODICON. As an acronym, it meant modular digital controller. Other engineering firms developed their own versions of this device, and it eventually came to be known in non-proprietary terms as a PLC, or programmable logic controller. The purpose of a PLC is to directly replace electromechanical relays as logic elements, substituting instead a solid-state digital computer with a stored program able to emulate the interconnection of many relays to perform certain logical tasks.

A PLC has many input terminals, through which it interprets high and low logical states from sensors and switches. It also has many output terminals, through which it outputs high and low signals to power lights, solenoids, instruments, controls, and other devices lending themselves to on/off control. In an effort to make PLCs easy to program, their programming language was designed to resemble ladder logic diagrams. Thus, an industrial electrician or electrical engineer accustomed to reading ladder logic schematics would feel comfortable programming a PLC to perform the same control functions.

Page 70: Instrumentation and Control

59

PLCs are industrial computers, and as such, their input and output signals are typically 120 volts AC, just like the electromechanical control relays they were designed to replace.

Signal Isolation

The following is taken from Wilkerson Instrument Co., Signal Isolation.

Signal isolation is a method of conditioning a signal without having a galvanic connection between the input and the output. Isolation is often also required between the input, output, and power source. Isolation is usually achieved by converting the input into a frequency and coupling the frequency signal to the output through a transformer or optical isolator. Typical isolation circuits can withstand 1,000 volts or more common mode signals on the input.

Isolation is useful in breaking ground loops and providing high-voltage common mode rejection. The need for isolation depends on the signal source wiring and the load on the signal conditioner. If the signal conditioner is wired in a fixed system in a consistent manner, isolation can probably be avoided through proper wiring practices. If the signal conditioner is available for other user wiring, isolation should be considered if the other user can create ground loops or apply high common mode signals to the conditioner.

Electrical Protection

The following is taken from All About Circuits, Protective Relays.

A special type of relay is one that monitors the current, voltage, frequency, or any other type of electric power measurement either from a generating source or to a load for the purpose of triggering a circuit breaker to open in the event of an abnormal condition. These relays are referred to in the electrical power industry as protective relays.

The circuit breakers that are used to switch large quantities of electric power on and off are actually electromechanical relays themselves. Unlike the circuit breakers found in residential and commercial use that determine when to trip (open) by means of a bimetallic strip inside that bends when it gets too hot from overcurrent, large industrial circuit breakers must be told by an external device when to open. Such breakers have two electromagnetic coils inside: one to close the breaker contacts and one to open them. The trip coil can be energized by one or more protective relays, as well as by hand switches, connected to switch 125 volt DC power. DC power is used because it allows for a battery bank to supply close/trip power to the breaker control circuits in the event of a complete (AC) power failure.

Protective relays can monitor large AC currents by means of current transformers that encircle the current-carrying conductors exiting a large circuit breaker, transformer, generator, or other device. Current transformers step down the monitored current to a secondary (output) range of 0–5 amps AC to power the protective relay. The current relay uses this 0–5 amp signal to power its internal mechanism, closing a contact to switch 125 volt DC power to the breaker’s trip coil if the monitored current becomes excessive.

Likewise, (protective) voltage relays can monitor high AC voltages by means of voltage, or potential, transformers that step down the monitored voltage to a secondary range of 0–120 volts AC, typically. Like protective current relays, this voltage signal powers the

Page 71: Instrumentation and Control

60

internal mechanism of the relay, closing a contact to switch 125 volt DC power to the breaker’s trip coil as the monitored voltage becomes excessive.

There are many types of protective relays, some with highly specialized functions. Not all monitor voltage or current, either. They all, however, share the common feature of outputting a contact closure signal that can be used to switch power to a breaker trip coil, close coil, or operator alarm panel.

Electrical Switching

The following is taken from Power-IO, Solid State Relay Terminology.

There are several types of electrical switching devices.

Mechanical Relays or Mechanical Contactors

The cost of a mechanical relay or mechanical contactor is influenced by amperage and usage. As these increase, so does the price. A mechanical device typically has two ratings: the number of mechanical cycles (a high number) and the number of electrical cycles (a low number). Therefore, mechanical devices should be used when the final device is activated infrequently. Mechanical relays are seldom used for heater applications since the cycle time is too slow and the overall product life is often too short. A mechanical device turns on or off when the coil is energized, which can result in noise spikes or surges since this is not at the zero crossing point. An ideal cycle time for a mechanical device is often 30–60 seconds or more. Some applications will require snubbers across the power terminals to help to suppress the voltage surge upon opening at the non-zero point.

Mercury Contactors or Mercury Displacement Relays

A mercury contactor uses a pool of mercury, inside a glass sealed tube, to electrically connect two contacts. This pool may contain more than 100 grams of mercury for a single contactor. Since mercury is considered a cancer hazard in the United States and is banned in some countries, there are restrictions on shipping, storing, or clean up if a contactor should leak or explode. A mercury contactor is not a zero crossing device, so there will be noise spikes or surges that may affect nearby electrical products or PLCs. An ideal on/off cycle time for a mercury contactor is often 10–20 seconds, with 3–8 million overall cycles. Mercury contactors are used frequently for industrial heater control of resistive heaters. When used 24 hours a day in a heater application, there may be 3 million on/off cycles in a single year. Therefore, the mercury contactors might be replaced many times during the life of the machine.

Solid State Relays (SSRs)

SSR devices are usually packaged in the familiar cube shape and are frequently referred to as “hockey puck relays.” SSRs can use internal triacs, but the better SSRs will use internal a pair of silicon controlled rectifiers. SSRs turn on and off at the zero crossing mark on a sinewave, so electrical surges and noise spikes are greatly reduced. Since there are no moving parts in SSRs, they can be cycled on and off many times per second. SSRs can be ideal products if you pay attention to three important application items: avoid over voltage (surges), over current, and over temperature.

Page 72: Instrumentation and Control

61

Solid-State Contactors

When an industrially hardened SSR is assembled onto a properly sized heat sink, the final product is frequently called a solid-state contactor. As a finished contactor, the device provides the fastest and most convenient way to install a complete solid-state switching product.

For heater control, solid-state contactors are typically used with programmable logic controllers, program controllers, or network input/output controllers that generate the pulsing control signal. This may be called a time proportional output, or pulse wave modulation. When used with some PLCs, it may be easier to reduce programming time by using an analog output.

Page 73: Instrumentation and Control

62

Time Delays

The following is taken from All About Circuits, Time Delays.

Some relays are constructed with a kind of “shock absorber” mechanism attached to the armature that prevents immediate, full motion when the coil is either energized or de-energized. This addition gives the relay the property of time-delay actuation. Time-delay relays can be constructed to delay armature motion on coil energization, de-energization, or both.

Time-delay relay contacts must be specified not only as either normally open or normally closed, but whether the delay operates in the direction of closing or in the direction of opening. The following is a description of the four basic types of time-delay relay contacts.

First we have the normally open, timed-closed (NOTC) contact. This type of contact is normally open when the coil is unpowered (de-energized). The contact is closed by the application of power to the relay coil, but only after the coil has been continuously powered for the specified amount of time. In other words, the direction of the contact’s motion (either to close or to open) is identical to a regular NO contact, but there is a delay in closing direction. Because the delay occurs in the direction of coil energization, this type of contact is alternatively known as a normally open, on-delay.

Next we have the normally open, timed-open (NOTO) contact. Like the NOTC contact, this type of contact is normally open when the coil is unpowered (de-energized), and closed by the application of power to the relay coil. However, unlike the NOTC contact, the timing action occurs upon de-energization of the coil rather than upon energization. Because the delay occurs in the direction of coil de-energization, this type of contact is alternatively known as a normally open, off-delay.

Next we have the normally closed, timed-open (NCTO) contact. This type of contact is normally closed when the coil is unpowered (de-energized). The contact is opened with the application of power to the relay coil, but only after the coil has been continuously powered for the specified amount of time. In other words, the direction of the contact’s motion (either to close or to open) is identical to a regular NC contact, but there is a delay in the opening direction. Because the delay occurs in the direction of coil energization, this type of contact is alternatively known as a normally closed, on-delay.

Finally we have the normally closed, timed-closed contact. Like the NCTO contact, this type of contact is normally closed when the coil is unpowered (de-energized), and opened by the application of power to the relay coil. However, unlike the NCTO contact, the timing action occurs upon de-energization of the coil rather than upon energization. Because the delay occurs in the direction of coil de-energization, this type of contact is alternatively known as a normally closed, off-delay.

Alarm Annunciation

The following is taken from EM 1110-2-3006.

Every power plant should be provided with an annunciation system providing both audible and visual signals in the event of trouble or abnormal conditions.

Page 74: Instrumentation and Control

63

Audio Signals. Howler horns and intermittent gongs are used for audible signal devices. An intermittent gong is provided in the plant control room. Howler horns are used in the unit area and in areas where the background noise is high or in areas remote from the unit.

Visual Signals. Visual signals are provided by lighted, lettered window panels of the annunciator. In larger plants, the annunciator panel indication is augmented by unit trouble lamps located in a readily visible position close to the unit. The plant sequence of events recorder is normally located in the control room. Separate annunciators (when provided) for station service systems and switchyards should be located on associated control panels of the station service switchgear or on the switchyard control panels.

All remote contacts used for trouble annunciation should be electrically independent of contacts used for other purposes so annunciator circuits are separated from other DC circuits. Auxiliary relays should be provided where electrically independent contacts cannot otherwise be obtained. The annunciator equipment should use solid-state logic units, lighted window type, designed and tested for surge withstanding capability in accordance with American National Standards Institute (ANSI) C37.90.1, and manufactured in accordance with ANSI/International Society of Automation (ISA) S18.1.

Indication Actuation

The following is taken from National Chemical Safety Program (NCSP) DOE Report 2000-ID-0001.

Hardware alarms should be based on positive indication of actuation or barrier failure (e.g., switch actuation, solenoid position, gas pressure, detection of radiation, or fluid flow), rather than perceived status based on a software command.

e. Describe the methods and devices used in instrumentation and control circuits to provide for protection against electrical transients.

The following is taken from National Electrical Manufacturer’s Association (NEMA), Electrical Transients: Keeping the Enemy Out of Your Facility.

To safeguard today’s facilities, designers often use a combination of several systems to divert electrical transients. Structural lightning protection systems are engineered and installed to protect the facility. Usually mounted on rooftops, these systems are designed to attract lightning and provide a path to ground on which the current can flow.

Another device, often installed at the service entrance, is the lightning arrestor. Lightning arrestors are designed to limit the surge current magnitude to a level that is not damaging to transformers, switchgear, or other service entrance equipment; in other words, they must reduce high-magnitude events to 2,000–3,000 volts. While this voltage range is within the withstand capability of most service entrance equipment, it will likely still be damaging to electronic loads within the facility.

To properly protect both service entrance equipment and electronic loads located deeper within a facility, a device that will clamp service entrance surges to an acceptable level of several hundred volts is required. Suppression filter systems and other transient voltage surge

Page 75: Instrumentation and Control

64

suppression (TVSS) devices are designed to do exactly this. While some TVSS offerings provide basic clamping and require module replacement after a given number of transient episodes, suppression filter systems that deliver long-term, repeated impulse protection without requiring component replacement are a more reliable, more cost-effective solution.

Installing surge protection at electrical service entrances has often been compared to protecting the forts of the Old West. In pioneer times, the most feared enemies were the bad guys outside the walls. As long as these dangerous elements were kept at bay, everyone inside was protected.

Transferring this philosophy to today’s modern facilities, the primary goal of electrical transient disturbance protection is to keep lightning and the other externally generated bad guys from getting inside by installing protective devices at the service entrance. But just like in the Old West, a secondary plan to attack internal transients is also essential to total facility protection.

f. Identify and discuss the use of electrical test equipment used to troubleshoot and analyze instrumentation and control circuit performance.

The following is taken from GlobalSpec, Logic Analyzers.

Logic analyzers are used to characterize and debug hardware, design and test firmware and software, and perform synthesis integration. General-purpose logic analyzers allow the user to specify the width and depth of the data window that is captured, the width being the number of points captured simultaneously, and the depth being the total time slices that the captured data represent. Most logic analyzers combine two instruments: a state analyzer and a timing analyzer. The timing analyzer approximates an oscilloscope’s time-interval-measurement capabilities. The state analyzer provides the type of information you would expect to see in a well-behaved, clock-driven sequential digital unit under test logic ones and zeros; it does not show glitches, clock skew, or path delays. Basically, the state analyzer is used to show what happened on the bus, while the timing analyzer demonstrates when it happened.

Timing analyzers are the part of logic analyzers that are analogous to oscilloscopes. The timing analyzer displays information in the same general form as a scope, with the horizontal axis representing time, and the vertical axis representing high and low logic levels. Because the waveforms on both instruments are time-dependent, the displays are said to be in the time domain.

State analyzers are used to track logic events in a synchronous form. They trace values on a bus or track functional problems and code flow. They can also be used to analyze the execution of computer programs.

When selecting between logic analyzers, there are a number of important features to consider: the number of input channels, the number of patterns generated, memory depth, sampling rate, and channel bandwidth.

The number of patterns generated refers to the number of patterns (per channel) that logic analyzers can measure. These patterns can be time, temperature, power, etc.

Page 76: Instrumentation and Control

65

Memory depth is an expression of the analyzers’ ability to capture and analyze relatively complex data.

Sampling rate, also called the sampling speed, refers to the speed at which sampling information is tracked, extracted, and displayed. Many manufacturers differentiate between state speed and timing speed.

Channel bandwidth, in a general sense, describes the logic analyzers’ information-carrying capacity. It can apply to telephone or network wiring as well as system buses, radio frequency signals, and monitors. Bandwidth is most accurately measured in cycles per second, or hertz, which is the difference between the lowest and highest frequencies transmitted. But it is also common to use bits or bytes per second instead.

g. Describe the requirements for electrical safety class systems.

The following is taken from NEMA, The Strengths of an Effective Electrical Safety System.

An effective electrical safety system has three distinct but interconnected components. Figure 18 is an illustration of the system.

Source: NEMA, The Strengths of an Effective Electrical Safety System

Figure 18. Components of an effective electrical safety system

Each portion of the system has to be capable of meeting the diverse needs of the segments of the electrical community. The segments of concern include users, consumers, electrical contractors (designers/installers), electrical inspectors, testing laboratories, manufacturers, electrical workers (maintenance), and insurers.

The system has to represent a consensus among the various segments. Not all segments will be satisfied with all elements of the system. A better level of overall acceptance and safety can be achieved by using a consensus-based approach that draws upon the expertise offered by each of the concerned segments.

In order to be effective, each of the three system elements must have the following key features.

Page 77: Instrumentation and Control

66

Installation Codes

The installation code is the key driver for the system. It provides the fundamental safety principles and installation rules that will provide a safe electrical system. The following key elements must be included in an installation code: Compatibility with Product Standards. Although installation code rules are generally

the driver, the development of those rules must take into account the standards requirements for products being considered for installation in the system. The installation code and the product standard must be compatible. This compatibility ensures that products support the safety objectives and are used and installed in a manner as contemplated by the manufacturer. It is erroneous to assume that one can simply select an electrical product built to any standard and safely install it in any system. Electrical code rules are written with the expectation that products comply with established requirements that are compatible with the code. Improper or vague code rules increase the potential for misapplication of products and the installation of incompatible system components that can lead to increased hazards for persons and property.

Enforceable Prescriptive Language. An installation code must be written in enforceable language with rules that clearly set out the installation parameters for a product. One key to standardization is to have everyone working from the same basic level of safety. Enforceable rules must be measurable and are often necessarily prescriptive. Without this basic prescriptive level, the benefits to standardization (both economical and safety related) are lost.

For years, there has been discussion of a “performance-based” or “objective-based” approach to codes. A performance-based approach makes sense for some areas of building design. Design of fire protection systems is a good example. There are sophisticated models for determining the required level of protection for various fire scenarios, and use of these models can help establish the system design. However, this type of approach does not work for determining the basic levels of electrical safety. Conductors have to be protected, disconnects have to be readily available and working space must be provided. These cannot be modeled; they are fundamental safety principles that manifest themselves in rules based on extensive experience.

In addition, electrical codes have already embraced a “performance design” where it may be appropriate. This can best be shown by using an example from the National Electrical Code (NEC). NEC 310.15 recognizes a methodology for determining the ampacity of a conductor using the Nehr-McGrath formulas. A designer can certainly use this to determine the ampacity of a conductor in a specific application. However, that conductor has to terminate in some type of electrical device. The terminations on this device are designed to operate at a maximum temperature. This maximum temperature is established by the product standards and covers many parameters that must be considered in product design. The relationship to the product standard is critical since this is an element that cannot be modeled in the field. Selection of a conductor that is too small results in overheating of the device terminations. In order to avoid this problem, there are specific prescriptive rules that establish the minimums for the conductor sizing that are consistent with the design of the product.

Page 78: Instrumentation and Control

67

Product Standards and Certification

Product standards establish the minimum level of safety and associated reliability for a product. Key areas for an effective product standard are as follows: Compatibility with the installation code. Like an electrical code, product standards

cannot exist in a vacuum. Product standards must be directly compatible with the electrical installation code that covers electrical products used in the electrical system. In order to properly test and certify a product there have to be established “ground rules” for the installation of the product. These ground rules are set forth in the form of an electrical code as outlined above.

Active Development Process. Product standards need to be developed with wide input and review from various electrical community segments. It is also critical that there not be multiple conflicting product standards. The best way to accomplish this objective is to process standards through a nationally recognized process that provides for wide participation of the electrical community. This wide review ensures that the product standard reflects the level of safety and the necessary infrastructure compatibility for the system within the defined scope of the standard. Designers, installers, or other users should not make the mistake of assuming that they can select a product built to any standard and expect that product to perform safely within their defined system. It is the formal review and adoption for the standards that establish them as the minimum requirements in a country. Despite their appearance and traditional use, standards are not purely technical. They reflect social objectives. They articulate what a society agrees are acceptable levels of risk. This is one reason for striving for balanced membership on standards making bodies. One example of the society driving product standards requirements can be found in the area of warnings and cautions used to prevent foreseeable accidents. These are a large part of many product standards. In societies where tort law reaches into standards writing, these considerations are paramount.

Support of Consistent Certification. Regardless of the method of certification used, product standards must be written in a manner that allows for consistent interpretation and enforcement. Inadequate testing protocols and vague language can lead to inconsistent application and could result in missing key safety elements of a product. Furthermore, it is critical to avoid having multiple product standards that cover the same product differently within a given safety system. Multiple standards lead to inefficiencies for the manufacturer, installer, inspector, and user.

Review and Enforcement

Most often overlooked in an effective safety system is the need to have an efficient and effective system of enforcement for compliance. Having solid electrical inspection programs that utilize qualified inspectors provides the needed controls for the system. There is a growing concern associated with the “quality assurance” based inspection approach. These systems rely on review of the plans and limited “auditing” in lieu of thorough and timely on-site inspections throughout the course of the construction. The majority of the electrical community welcomes a system of inspections that provides needed checks and balances. By contrast, taking a quality assurance approach only serves to keep the revenue from permit fees flowing without adding any value.

h. Discuss the factors to be considered when selecting electrical components for use in instrumentation and control circuits. Include in the discussion any

Page 79: Instrumentation and Control

68

consideration that must be given to the environment in which the circuit is required to perform its design function.

The following is taken from DOE-HDBK-1013/1-92.

Ambient temperature variations will affect the accuracy and reliability of temperature detection instrumentation. Variations in ambient temperature can directly affect the resistance of components in a bridge circuit and the resistance of the reference junction for a thermocouple. In addition, ambient temperature variations can affect the calibration of electric/electronic equipment. The effects of temperature variations are reduced by the design of the circuitry and by maintaining the temperature detection instrumentation in the proper environment.

The presence of humidity will also affect most electrical equipment, especially electronic equipment. High humidity causes moisture to collect on the equipment. This moisture can cause short circuits, grounds, and corrosion, which in turn may damage components. The effects due to humidity are controlled by maintaining the equipment in the proper environment.

i. Discuss the effects of electromagnetic interference and electrostatic discharge on the performance of components in a typical instrumentation and control circuit.

Electromagnetic Interference (EMI)

The following is taken from Nuclear Regulatory Commission (NRC) Regulatory Guide 1.180.

Existing instrumentation and control (I&C) equipment in nuclear facilities is currently being replaced with computer-based digital I&C systems or advanced analog systems. However, these technologies may exhibit greater vulnerability to the nuclear facility EMI environment than existing I&C systems. NRC Regulatory Guide 1.180 provides an acceptable method for qualifying digital and advanced analog systems for the projected electromagnetic environment in nuclear facilities.

The typical environment in a nuclear facility includes many sources of electrical noise, for example, hand-held two-way radios, arc welders, switching of large inductive loads, high fault currents, and high-energy fast transients associated with switching at the generator or transmission voltage levels.

The increasing use of advanced analog- and microprocessor-based I&C systems in safety-related plant systems has introduced concerns with respect to the creation of additional noise sources and the susceptibility of this equipment to the electrical noise already present in the nuclear facility environment.

Digital technology is constantly evolving, and manufacturers of digital systems are incorporating increasingly higher clock frequencies and lower logic level voltages into their designs. However, these performance advancements may have an adverse impact on the operation of digital systems with respect to EMI and power surges because of the increased likelihood of extraneous noise being misinterpreted as legitimate logic signals. With recent advances in analog electronics, many of the functions presently being performed by several analog circuit boards could be combined into a single analog circuit board operating at

Page 80: Instrumentation and Control

69

reduced voltage levels, thereby making analog circuitry more susceptible to EMI and power surges as well. Hence, operational and functional issues related to safety in the nuclear facility environment must address the possibility of upsets and malfunctions in I&C systems caused by EMI and power surges.

Electrostatic Discharge (ESD)

The following is taken from Electrostatic Discharge Association (ESDA), Electrostatic Discharge Technology Roadmap.

In the late 1970s, electrostatic discharge, or ESD, became a problem in the electronics industry. Low-level ESD events from people were causing device failures and yield losses. As the industry learned about this phenomenon, both device design improvements and process changes were made to make the devices more robust and processes more capable of handling these devices.

During the 1980s and early 1990s, device engineers were able to create protection structures that made the devices less sensitive to ESD events. Technology changes during this time also helped design engineers to develop more robust devices.

In the mid to late 1990s however, the requirements for increased performance (devices that operate in the gigahertz range) and the increase in the density of circuits on a device caused problems for traditional ESD protection circuits. To achieve the performance and density numbers required by industry, the devices have become more sensitive to ESD events since the late 1990s. The current trend, which is expected to continue, is circuit performance at the expense of ESD protection levels.

j. Discuss the design requirements for I&C system grounds.

The following is taken from DOE-HDBK-1092-2004.

Circuit and system grounding consists of connecting the grounded conductor, the equipment grounding conductor, the grounding bus bars, and all noncurrent-carrying metal parts to ground.

This is accomplished by connecting a properly sized, unspliced grounding electrode conductor between the grounding bus bar and the grounding electrode system. There are three fundamental purposes for grounding an electrical system:

1. To limit excessive voltage from lightning, line surges, and crossovers with higher voltage line

2. To keep conductor enclosures and noncurrent-carrying metal enclosures and equipment at zero potential to ground

3. To facilitate the opening of overcurrent protection devices in case of insulation failures because of faults, short circuits, etc.

Equipment grounding systems, which consist of interconnected networks of equipment grounding conductors, are used to perform the following functions: Limit the hazard to personnel (shock voltage) from the noncurrent-carrying metal

parts of equipment raceways and other conductor enclosures in case of ground faults

Page 81: Instrumentation and Control

70

Safely conduct ground-fault current at sufficient magnitude for fast operation of the circuit overcurrent protection devices

To ensure the performance of the above functions, equipment grounding conductors are required to be permanent and continuous, have ample capacity to safely conduct ground-fault current likely to be imposed on

them, and have impedance sufficiently low to limit the voltage to ground to a safe magnitude

and to facilitate the operation of the circuit overcurrent protection devices.

4. Instrumentation and control personnel shall demonstrate a working level knowledge of temperature detection circuitry and components used in instrumentation and control systems.

a. Discuss the basic functions of temperature detectors.

The following is taken from DOE-HDBK-1013/1-92.

Although the temperatures that are monitored vary slightly depending on the details of facility design, temperature detectors are used to provide three basic functions: indication, alarm, and control. The temperatures monitored may normally be displayed in a central location, such as a control room, and may have audible and visual alarms associated with them when specified preset limits are exceeded. These temperatures may have control functions associated with them so that equipment is started or stopped to support a given temperature condition or so that a protective action occurs.

Because temperature is one of the most important parameters of a material, many instruments have been developed to measure it. One type of detector used is the resistance temperature detector (RTD). The RTD is used at many DOE nuclear facilities to measure temperatures of the process or materials being monitored.

b. Describe the construction of a basic Resistance Temperature Detector (RTD).

The following is taken from DOE-HDBK-1013/1-92.

The RTD incorporates pure metals or certain alloys that increase in resistance as temperature increases and, conversely, decrease in resistance as temperature decreases. RTDs act somewhat like an electrical transducer, converting changes in temperature to voltage signals by the measurement of resistance. The metals that are best suited for use as RTD sensors are pure, of uniform quality, stable within a given range of temperature, and able to give reproducible resistance-temperature readings. Only a few metals have the properties necessary for use in RTD elements.

RTD elements are normally constructed of platinum, copper, or nickel. These metals are best suited for RTD applications because of their linear resistance-temperature characteristics, their high coefficient of resistance, and their ability to withstand repeated temperature cycles.

Page 82: Instrumentation and Control

71

The coefficient of resistance is the change in resistance per degree change in temperature, usually expressed as a percentage per degree of temperature. The material used must be capable of being drawn into fine wire so that the element can be easily constructed.

RTD elements are usually long, spring-like wires surrounded by an insulator and enclosed in a sheath of metal. Figure 19 shows the internal construction of an RTD.

Source: DOE-HDBK-1013/1-92

Figure 19. Internal construction of a typical RTD

This particular design has a platinum element that is surrounded by a porcelain insulator. The insulator prevents a short circuit between the wire and the metal sheath.

Inconel, a nickel-iron-chromium alloy, is normally used in manufacturing the RTD sheath because of its inherent corrosion resistance. When placed in a liquid or gas medium, the Inconel sheath quickly reaches the temperature of the medium. The change in temperature will cause the platinum wire to heat or cool, resulting in a proportional change in resistance.

This change in resistance is then measured by a precision resistance-measuring device that is calibrated to give the proper temperature reading. This device is normally a bridge circuit.

Page 83: Instrumentation and Control

72

Figure 20 shows an RTD protective well and terminal head. The well protects the RTD from damage by the gas or liquid being measured. Protecting wells are normally made of stainless steel, carbon steel, Inconel, or cast iron, and they are used for temperatures up to 1100 °C.

Source: DOE-HDBK-1013/1-92

Figure 20. RTD well and terminal head

c. Explain how Resistance Temperature Detector resistance varies with changes in sensed temperature.

The following is taken from DOE-HDBK-1013/1-92.

The resistance of an RTD varies directly with temperature: As temperature increases, resistance increases. As temperature decreases, resistance decreases.

RTDs are constructed using a fine, pure, metallic, spring-like wire surrounded by an insulator and enclosed in a metal sheath.

d. Explain how a Resistance Temperature Detector provides an output representative of the measured temperature.

The following is taken from DOE-HDBK-1013/1-92.

A change in temperature will cause an RTD to heat or cool, producing a proportional change in resistance. The change in resistance is measured by a precision device that is calibrated to give the proper temperature reading.

e. Describe the construction of a basic thermocouple, including the materials used.

The following is taken from DOE-HDBK-1013/1-92.

A thermocouple is constructed of two dissimilar metal wires joined at one end. When one end of each wire is connected to a measuring instrument, the thermocouple becomes a

Page 84: Instrumentation and Control

73

sensitive and highly accurate measuring device. Thermocouples may be constructed of several different combinations of materials. The performance of a thermocouple material is generally determined by using that material with platinum. The most important factor to be considered when selecting a pair of materials is the thermoelectric difference between the two materials. A significant difference between the two materials will result in better thermocouple performance.

Figure 21 shows the internal construction of a typical thermocouple. The leads of the thermocouple are encased in a rigid metal sheath. The measuring junction is normally formed at the bottom of the thermocouple housing. Magnesium oxide surrounds the thermocouple wires to prevent vibration that could damage the fine wires and to enhance heat transfer between the measuring junction and the medium surrounding the thermocouple.

Source: DOE-HDBK-1013/1-92

Figure 21. Internal construction of a typical thermocouple

f. Explain how a thermocouple provides an output representative of the measured temperature.

The following is taken from DOE-HDBK-1013/1-92.

Thermocouples will cause an electric current to flow in the attached circuit when subjected to changes in temperature. The amount of current that will be produced is dependent on the temperature difference between the measurement and reference junction, the characteristics of the two metals used, and the characteristics of the attached circuit. Figure 22 illustrates a simple thermocouple circuit.

Page 85: Instrumentation and Control

74

Source: DOE-HDBK-1013/1-92

Figure 22. Simple thermocouple circuit

Heating the measuring junction of the thermocouple produces a voltage that is greater than the voltage across the reference junction. The difference between the two voltages is proportional to the difference in temperature and can be measured on the voltmeter (in millivolts). For ease of operator use, some voltmeters are set up to read out directly in temperature through use of electronic circuitry.

g. Describe the environmental conditions that can affect the accuracy and reliability of temperature detection instrumentation.

The following is taken from DOE-HDBK-1013/1-92.

Ambient temperature variations will affect the accuracy and reliability of temperature detection instrumentation. Variations in ambient temperature can directly affect the resistance of components in a bridge circuit and the resistance of the reference junction for a thermocouple. In addition, ambient temperature variations can affect the calibration of electric/electronic equipment. The effects of temperature variations are reduced by the design of the circuitry and by maintaining the temperature detection instrumentation in the proper environment.

The presence of humidity will also affect most electrical equipment, especially electronic equipment. High humidity causes moisture to collect on the equipment. This moisture can cause short circuits, grounds, and corrosion, which in turn may damage components. The effects due to humidity are controlled by maintaining the equipment in the proper environment.

h. Given a diagram of a basic temperature instrumentation detection and control system, describe the function of the following components: Resistance temperature detector (RTD) Bridge circuit Direct current-alternating current converter

Page 86: Instrumentation and Control

75

Amplifier Balancing motor/mechanical linkage

This is a performance-based KSA. The Qualifying Official will evaluate its completion.

i. Describe the temperature instrument indications for the following faults: Short circuit Open circuit

According to DOE-HDBK-1013/1-92, if the RTD becomes open in either the unbalanced or balanced bridge circuits, the resistance will be infinite, and the meter will indicate a very high temperature. If it becomes shorted, the resistance will be zero, and the meter will indicate a very low temperature.

j. Explain the methods of bridge circuit compensation for changes in ambient temperature.

The following is taken from DOE-HDBK-1013/1-92.

The bridge operates by placing Rx in the circuit, as shown in figure 23, and then adjusting R3 so that all current flows through the arms of the bridge circuit. When this condition exists, there is no current flow through the ammeter, and the bridge is said to be balanced. When the bridge is balanced, the currents through each of the arms are exactly proportional. They are equal if R1 = R2. Most of the time the bridge is constructed so that R1 = R2. When this is the case, and the bridge is balanced, then the resistance of Rx is the same as R3, or Rx = R3.

When balance exists, R3 will be equal to the unknown resistance, even if the voltage source is unstable or is not accurately known. A typical Wheatstone bridge has several dials used to vary the resistance. Once the bridge is balanced, the dials can be read to find the value of R3.

Source: DOE-HDBK-1013/1-92

Figure 23. Bridge circuit

Page 87: Instrumentation and Control

76

Bridge circuits can be used to measure resistance to tenths or even hundredths of a percent accuracy. When used to measure temperature, some Wheatstone bridges with precision resistors are accurate to about + 0.1°F.

Two types of bridge circuits (unbalanced and balanced) are utilized in resistance thermometer temperature detection circuits. The unbalanced bridge circuit in figure 24 uses a millivoltmeter that is calibrated in units of temperature that correspond to the RTD resistance.

Source: DOE-HDBK-1013/1-92

Figure 24. Unbalanced bridge circuit

The battery in figure 24 is connected to two opposite points of the bridge circuit. The millivoltmeter is connected to the two remaining points. The rheostat regulates bridge current. The regulated current is divided between the branch with the fixed resistor and range resistor R1, and the branch with the RTD and range resistor R. As the electrical resistance of the RTD changes, the voltage at points X and Y changes. The millivoltmeter detects the change in voltage caused by unequal division of current in the two branches. The meter can be calibrated in units of temperature because the only changing resistance value is that of the RTD.

The balanced bridge circuit (figure 25) uses a galvanometer to compare the RTD resistance with that of a fixed resistor. The galvanometer uses a pointer that deflects on either side of zero when the resistance of the arms is not equal. The resistance of the slide wire is adjusted until the galvanometer indicates zero. The value of the slide resistance is then used to determine the temperature of the system being monitored.

Page 88: Instrumentation and Control

77

Source: DOE-HDBK-1013/1-92

Figure 25. Balanced bridge circuit

A slidewire resistor is used to balance the arms of the bridge. The circuit will be in balance whenever the value of the slidewire resistance is such that no current flows through the galvanometer. For each temperature change, there is a new value; therefore, the slider must be moved to a new position to balance the circuit.

5. Instrumentation and control personnel shall demonstrate a working level knowledge of pressure detection circuitry and components used in instrumentation and control systems.

a. Discuss the basic functions of pressure detectors.

The following is taken from DOE-HDBK-1013/1-92.

Although the pressures that are monitored vary slightly depending on the details of facility design, all pressure detectors are used to provide up to three basic functions: indication, alarm, and control. Since the fluid system may operate at both saturation and subcooled conditions, accurate pressure indication must be available to maintain proper cooling. Some pressure detectors have audible and visual alarms associated with them when specified preset limits are exceeded. Some pressure detector applications are used as inputs to protective features and control functions.

b. Explain how a bellows pressure detector produces an output signal representative of the measured pressure.

The following is taken from DOE-HDBK-1013/1-92.

Page 89: Instrumentation and Control

78

The need for a pressure-sensing element that was extremely sensitive to low pressures and that would provide power to activate recording and indicating mechanisms resulted in the development of the metallic bellows pressure-sensing element. The metallic bellows is most accurate when measuring pressures from 0.5 to 75 psig, or gauge pressure. However, when used in conjunction with a heavy range spring, some bellows can be used to measure pressures of over 1000 psig. Figure 26 shows a basic metallic bellows pressure-sensing element.

Source: DOE-HDBK-1013/1-92

Figure 26. Basic metallic bellows

The bellows is a one-piece, collapsible, seamless metallic unit that has deep folds formed from very thin-walled tubing. The diameter of the bellows ranges from 0.5 to 12 in. and may have as many as 24 folds. System pressure is applied to the internal volume of the bellows. As the inlet pressure to the instrument varies, the bellows will expand or contract. The moving end of the bellows is connected to a mechanical linkage assembly. As the bellows and linkage assembly move, either an electrical signal is generated or a direct pressure indication is provided. The flexibility of a metallic bellows is similar in character to that of a helical, coiled compression spring. Up to the elastic limit of the bellows, the relation between increments of load and deflection is linear. However, this relationship exists only when the bellows is under compression. It is necessary to construct the bellows such that all of the travel occurs on the compression side of the point of equilibrium. Therefore, in practice, the bellows must always be opposed by a spring, and the deflection characteristics will be the resulting force of the spring and bellows.

c. Explain how a bourdon tube pressure detector produces an output signal representative of the measured pressure.

The following is taken from DOE-HDBK-1013/1-92.

The bourdon tube pressure instrument is one of the oldest pressure-sensing instruments in use today. The bourdon tube consists of a thin-walled tube that is flattened diametrically on opposite sides to produce a cross-sectional area elliptical in shape, having two long, flat sides and two short, round sides. The tube is bent lengthwise into an arc of a circle of 270 to 300 degrees. Pressure applied to the inside of the tube causes distention of the flat sections and tends to restore its original round cross-section. This change in cross-section causes the tube to straighten slightly. Since the tube is permanently fastened at one end, the tip of the tube traces a curve that is the result of the change in angular position with respect to the center.

Page 90: Instrumentation and Control

79

Within limits, the movement of the tip of the tube can then be used to position a pointer or to develop an equivalent electrical signal to indicate the value of the applied internal pressure.

d. Explain how a strain gauge pressure transducer produces an output signal representative of the measured pressure.

The following is taken from DOE-HDBK-1013/1-92.

A strain gauge measures the external force (pressure) applied to a fine wire. The fine wire is usually arranged in the form of a grid. The pressure change causes a resistance change due to the distortion of the wire. The value of the pressure can be found by measuring the change in resistance of the wire grid.

The equation below shows the pressure to resistance relationship:

R = KA

L

where R = resistance of the wire grid in ohms K = resistivity constant for the particular type of wire grid L = length of wire grid A = cross-sectional area of wire grid

As the wire grid is distorted by elastic deformation, its length is increased, and its cross-sectional area decreases. These changes cause an increase in the resistance of the wire of the strain gauge. This change in resistance is used as the variable resistance in a bridge circuit that provides an electrical signal for indication of pressure. Figure 27 illustrates a strain gauge pressure transducer.

Source: DOE-HDBK-1013/1-92

Figure 27. Strain gauge pressure transducer

Page 91: Instrumentation and Control

80

An increase in pressure at the inlet of the bellows causes the bellows to expand. The expansion of the bellows moves a flexible beam to which a strain gauge has been attached. The movement of the beam causes the resistance of the strain gauge to change. The temperature-compensating gauge compensates for the heat produced by current flowing through the fine wire of the strain gauge.

An exciter that is used in place of a battery to eliminate the need for a galvanometer provides AC. When a change in resistance in the strain gauge causes an unbalanced condition, an error signal enters the amplifier and actuates the balancing motor. The balancing motor moves the slider along the slidewire, restoring the bridge to a balanced condition. The slider’s position is noted on a scale marked in units of pressure.

e. Describe the environmental concerns that can affect the accuracy and reliability of pressure detection instrumentation.

The following is taken from DOE-HDBK-1013/1-92.

Pressure instruments are sensitive to variations in the atmospheric pressure surrounding the detector. This is especially apparent when the detector is located within an enclosed space. Variations in the pressure surrounding the detector will cause the indicated pressure from the detector to change. This will greatly reduce the accuracy of the pressure instrument and should be considered when installing and maintaining these instruments.

Ambient temperature variations will affect the accuracy and reliability of pressure detection instrumentation. Variations in ambient temperature can directly affect the resistance of components in the instrumentation circuitry, and therefore, affect the calibration of electric/ electronic equipment. The effects of temperature variations are reduced by the design of the circuitry and by maintaining the pressure detection instrumentation in the proper environment.

The presence of humidity will also affect most electrical equipment, especially electronic equipment. High humidity causes moisture to collect on the equipment. This moisture can cause short circuits, grounds, and corrosion, which in turn may damage components. The effects due to humidity are controlled by maintaining the equipment in the proper environment.

f. Given a diagram of a basic pressure detection device, describe the function of the following components: Sensing element Transducer Pressure detection circuitry Pressure indication

This is a performance-based KSA. The Qualifying Official will evaluate its completion. The following information taken from DOE-HDBK-1013/1-92 may be helpful.

The sensing element senses the pressure of the monitored system and converts the pressure to a mechanical signal. The sensing element supplies the mechanical signal to a transducer. The transducer converts the mechanical signal to an electrical signal that is proportional to system pressure. If the mechanical signal from the sensing element is used directly, a transducer is not required and therefore not used. The detector circuitry will amplify and/or transmit this

Page 92: Instrumentation and Control

81

signal to the pressure indicator. The electrical signal generated by the detection circuitry is proportional to system pressure. The exact operation of detector circuitry depends on the type of transducer used. The pressure indicator provides remote indication of the system pressure being measured.

g. Discuss the failure modes of the various types of pressure indication instruments.

The following is taken from DOE-HDBK-1013/1-92.

If a pressure instrument fails, spare detector elements may be utilized if installed. If spare detectors are not installed, the pressure may be read at an independent local mechanical gauge, if available, or a precision pressure gauge may be installed in the system at a convenient point. If the detector is functional, it may be possible to obtain pressure readings by measuring voltage or current values across the detector leads and comparing this reading with calibration curves.

6. Instrumentation and control personnel shall demonstrate a working level knowledge of level detection circuitry and components used in instrumentation and control systems.

a. Identify the principle of operation of the following types of level instrumentation: Gauge glass Ball float Chain float Magnetic bond Conductivity probe Differential pressure Sonic probes Capacitance probes Bubblers Radar level sensors

The following definitions and descriptions are taken from DOE-HDBK-1013/1-92.

Gauge Glass

In gauge glass operation, a transparent tube is attached to the bottom and top of a tank that is monitored. The height of the liquid in the tube will be equal to the height of water in the tank.

Ball Float

The ball float is a direct reading liquid level mechanism. The most practical design for the float is a hollow metal ball or sphere. However, there are no restrictions to the size, shape, or material used. The design consists of a ball float attached to a rod, which in turn is connected to a rotating shaft that indicates level on a calibrated scale. The operation of the ball float is simple. The ball floats on top of the liquid in the tank. If the liquid level changes, the float will follow and change the position of the pointer attached to the rotating shaft.

The travel of the ball float is limited by its design to be within ±30 degrees from the horizontal plane that results in optimum response and performance. The actual level range is determined by the length of the connecting arm.

Page 93: Instrumentation and Control

82

Chain Float

The chain float gauge has a float ranging in size up to 12 inches in diameter and is used where small level limitations imposed by ball floats must be exceeded. The range of level measured will be limited only by the size of the vessel. The operation of the chain float is similar to the ball float except in the method of positioning the pointer and in its connection to the position indication. The float is connected to a rotating element by a chain with a weight attached to the other end to provide a means of keeping the chain taut during changes in level.

Magnetic Bond

The magnetic bond method was developed to overcome the problems related to cages and stuffing boxes. The magnetic bond mechanism consists of a magnetic float that rises and falls with changes in level. The float travels outside a non-magnetic tube that houses an inner magnet connected to a level indicator. When the float rises and falls, the outer magnet will attract the inner magnet, causing the inner magnet to follow the level within the vessel.

Conductivity Probe

A conductivity probe consists of one or more level detectors, an operating relay, and a controller. When the liquid makes contact with any of the electrodes, an electric current will flow between the electrode and ground. The current energizes a relay that causes the relay contacts to open or close depending on the state of the process involved. The relay in turn will actuate an alarm, a pump, a control valve, or all three. A typical system has three probes: a low-level probe, a high-level probe, and a high-level alarm probe.

Differential Pressure

The differential pressure (DP) detector method of liquid level measurement uses a DP detector connected to the bottom of the tank being monitored. The higher pressure, caused by the fluid in the tank, is compared to a lower reference pressure (usually atmospheric). This comparison takes place in the DP detector.

Sonic Probes

Devices such as ultrasonic flow equipment use the Doppler frequency shift of ultrasonic signals reflected from discontinuities in the fluid stream to obtain flow measurements. These discontinuities can be suspended solids, bubbles, or interfaces generated by turbulent eddies in the flow stream. The sensor is mounted on the outside of the pipe, and an ultrasonic beam from a piezoelectric crystal is transmitted through the pipe wall into the fluid at an angle to the flow stream. Signals reflected off flow disturbances are detected by a second piezoelectric crystal located in the same sensor. Transmitted and reflected signals are compared in an electrical circuit, and the corresponding frequency shift is proportional to the flow velocity.

Capacitance Probes

Capacitance probes consist of two flexible conductive plates and a dielectric. In this case, the dielectric is the fluid. As pressure increases, the flexible conductive plates will move farther apart, changing the capacitance of the transducer. This change in capacitance is measurable and is proportional to the change in pressure.

Page 94: Instrumentation and Control

83

Bubblers

The following is taken from Transactions in Measurement and Control, volume , Flow and Level Measurement.

Bubbler tubes provide a simple and inexpensive, but less accurate (±1–2 percent), level measurement system for corrosive or slurry-type applications. Bubblers use compressed air or an inert gas (usually nitrogen) introduced through a dip pipe. Gas flow is regulated at a constant rate (usually at about 500 cc/min). A DP regulator across a rotameter maintains constant flow, while the tank level determines the back-pressure. As the level drops, the back-pressure is proportionally reduced and is read on a pressure gauge calibrated in percent level or on a manometer or transmitter. The dip pipe should have a relatively large diameter (about 2 in.) so that the pressure drop is negligible. The bottom end of the dip pipe should be located far enough above the tank bottom so that sediment or sludge will not plug it. Also, its tip should be notched with a slot or “V” to ensure the formation of a uniform and continuous flow of small bubbles. An alternative to locating the dip pipe in the tank is to place it in an external chamber connected to the tank.

In pressurized tanks, two sets of dip pipes are needed to measure the level. The two back-pressures on the two dip pipes can be connected to the two sides of a U-tube manometer, a DP gauge, or a DP cell/transmitter. The pneumatic piping or tubing in a bubbler system should be sloped toward the tank so that condensed process vapors will drain back into the tank if purge pressure is lost. The purge gas supply should be clean, dry, and available at a pressure at least 10 psi greater than the expected maximum total pressure required (when the tank is full and the vapor pressure is at its maximum). An alternative to a continuous bubbler is to use a hand pump (similar to a bicycle tire pump) to provide purge air only when the level is being read.

Bubblers do consume inert gases, which can later accumulate and blanket processing equipment. They also require maintenance to ensure that the purge supply is always available and that the system is properly adjusted and calibrated. When all factors are considered, DPcells typically are preferred to bubblers in the majority of applications.

Radar Level Sensors

The following is taken from Sensors Magazine, Level Sensing in Harsh Environments with Guided-Wave Radar.

Radar works by measuring the time of flight of a transmitted signal. Known more accurately as time domain reflectometry, the process entails sending microwave pulses down through the material of interest and all the way to the bottom of the vessel. When a pulse reaches the product, the beam undergoes a change in impedance caused by the product’s dielectric. Part of the pulse is reflected back to the receiver, which then measures the exact duration of time between the departing and the returning signal, analyzes it, and displays the product level as a distance in feet, meters, or other units.

Page 95: Instrumentation and Control

84

b. Explain the process of density compensation in level detection systems.

The following is taken from DOE-HDBK-1013/1-92.

Before examining an example that shows the effects of density, the unit “specific volume” must be defined. Specific volume is defined as volume per unit of mass. Specific volume is the standard unit used when working with vapors and steam that have low values of density.

For the applications that involve water and steam, specific volume can be found using saturated-steam tables, which list the specific volumes for water and saturated steam at different pressures and temperatures.

The density of steam (or vapor) above the liquid level will have an effect on the weight of the steam or vapor bubble and the hydrostatic head pressure. As the density of the steam or vapor increases, the weight increases and causes an increase in hydrostatic head even though the actual level of the tank has not changed. The larger the steam bubble, the greater the change in hydrostatic head pressure.

A condensing pot at the top of the reference leg is incorporated to condense the steam and to keep the reference leg filled. The effect of the steam vapor pressure is cancelled at the DP transmitter due to the fact that this pressure is equally applied to both the low- and high-pressure sides of the transmitter.

Density compensation may also be accomplished through electronic circuitry. Some systems compensate for density changes automatically through the design of the level detection circuitry. Other applications compensate for density by manually adjusting inputs to the circuit as the pressurizer cools down and depressurizes, or during heatup and pressurization. Calibration charts are also available to correct indications for changes in reference leg temperature.

c. Given a basic diagram of a differential pressure detector level instrument, discuss the functions of the following: Differential pressure (D/p) transmitter Amplifier Indication

This is a performance-based KSA. The Qualifying Official will evaluate its completion. The following information taken from DOE-HDBK-1013/1-92 may be helpful.

Remote indication is necessary to provide transmittal of vital level information to a central location, such as the control room, where all level information can be coordinated and evaluated.

There are three major reasons for using remote level indication: 1. Level measurements may be taken at locations far from the main facility 2. The level to be controlled may be a long distance from the point of control 3. The level being measured may be in an unsafe/radioactive area.

Page 96: Instrumentation and Control

85

Figure 28 illustrates a block diagram of a typical differential pressure detector. It consists of a differential pressure (DP) transmitter (transducer), an amplifier, and level indication. The DP transmitter consists of a diaphragm with the high-pressure and low-pressure inputs on opposite sides. As the differential pressure changes, the diaphragm will move.

The transducer changes this mechanical motion into an electrical signal. The electrical signal generated by the transducer is then amplified and passed on to the level indicator for level indication at a remote location. Using relays, this system provides alarms on high and low level. It may also provide control functions such as repositioning a valve and protective features such as tripping a pump.

Source: DOE-HDBK-1013/1-92

Figure 28. Block diagram of a differential pressure level detection circuit

d. Describe the operation and applications of the following types of differential pressure detector level instruments: Open tank differential pressure transmitter Closed tank, dry reference leg Closed tank, wet reference leg

The following descriptions are taken from DOE-HDBK-1013/1-92.

Open Tank Differential Pressure Transmitter

When a tank is open to the atmosphere, it is necessary to use the high-pressure connection on the DP transmitter. The low-pressure side is vented to the atmosphere; therefore, the pressure differential is the hydrostatic head, or weight, of the liquid in the tank.

The maximum level that can be measured by the DP transmitter is determined by the maximum height of liquid above the transmitter. The minimum level that can be measured is determined by the point where the transmitter is connected to the tank.

Page 97: Instrumentation and Control

86

Closed Tank, Dry Reference Leg

Many tanks are totally enclosed to prevent vapors or steam from escaping, or to allow pressurizing the contents of the tank. When measuring the level in a tank that is pressurized, or the level that can become pressurized by vapor pressure from the liquid, both the high- pressure and low-pressure sides of the DP transmitter must be connected.

The high-pressure connection is connected to the tank at or below the lower range value to be measured. The low-pressure side is connected to a reference leg that is connected at or above the upper range value to be measured. The reference leg is pressurized by the gas or vapor pressure, but no liquid is permitted to remain in the reference leg. The reference leg must be maintained dry so that there is no liquid head pressure on the low-pressure side of the transmitter.

The high-pressure side is exposed to the hydrostatic head of the liquid plus the gas or vapor pressure exerted on the liquid’s surface. The gas or vapor pressure is equally applied to the low- and high-pressure sides. Therefore, the output of the DP transmitter is directly proportional to the hydrostatic head pressure, that is, the level in the tank.

Closed Tank, Wet Reference Leg

Where the tank contains a condensable fluid, such as steam, a slightly different arrangement is used. In applications with condensable fluids, condensation is greatly increased in the reference leg. To compensate for this effect, the reference leg is filled with the same fluid as the tank. The liquid in the reference leg applies a hydrostatic head to the high-pressure side of the transmitter, and the value of this level is constant as long as the reference leg is maintained full. If this pressure remains constant, any change in DP is due to a change on the low-pressure side of the transmitter.

The filled reference leg applies a hydrostatic pressure to the high-pressure side of the transmitter, which is equal to the maximum level to be measured. The DP transmitter is exposed to equal pressure on the high- and low-pressure sides when the liquid level is at its maximum; therefore, the DP is zero. As the tank level goes down, the pressure applied to the low-pressure side goes down also, and the DP increases. As a result, the DP and the transmitter output are inversely proportional to the tank level.

e. Describe the environmental concerns that can affect the accuracy and reliability of level detection instrumentation.

The following is taken from DOE-HDBK-1013/1-92.

Density of the fluid whose level is to be measured can have a large effect on level detection instrumentation. It primarily affects level-sensing instruments that utilize a wet reference leg. In these instruments, it is possible for the reference leg temperature to be different from the temperature of the fluid whose level is to be measured. An example of this is the level detection instrumentation for a boiler steam drum. The water in the reference leg is at a lower temperature than the water in the steam drum. Therefore, it is denser, and must be compensated for to ensure the indicated steam drum level is accurately indicated.

Ambient temperature variations will affect the accuracy and reliability of level-detection instrumentation. Variations in ambient temperature can directly affect the resistance of

Page 98: Instrumentation and Control

87

components in the instrumentation circuitry, and, therefore, affect the calibration of electric/electronic equipment. The effects of temperature variations are reduced by the design of the circuitry and by maintaining the level-detection instrumentation in the proper environment.

The presence of humidity will also affect most electrical equipment, especially electronic equipment. High humidity causes moisture to collect on the equipment. This moisture can cause short circuits, grounds, and corrosion, which in turn may damage components. The effects due to humidity are controlled by maintaining the equipment in the proper environment.

f. Discuss the failure modes of the various types of level indication instruments.

The following is taken from DOE-HDBK-1013/1-92.

When the level to be measured is in a pressurized tank at elevated temperatures, a number of consequences must be considered. As the temperature of the fluid in the tank is increased, the density of the fluid decreases. As the fluid’s density decreases, the fluid expands, occupying more volume. Even though the density is less, the mass of the fluid in the tank is the same. The problem encountered is that, as the fluid in the tank is heated and cooled, the density of the fluid changes, but the reference leg density remains relatively constant, which causes the indicated level to remain constant. The density of the fluid in the reference leg is dependent on the ambient temperature of the room in which the tank is located; therefore, it is relatively constant and independent of tank temperature. If the fluid in the tank changes temperature, and therefore density, some means of density compensation must be incorporated to have an accurate indication of tank level. This is the problem encountered when measuring pressurizer water level or steam generator water level in pressurized water reactors, and when measuring reactor vessel water level in boiling water reactors.

7. Instrumentation and control personnel shall demonstrate a working level knowledge of flow detection circuitry and components used in instrumentation and control systems.

a. Describe the basic construction and theory of operation of the following types of head flow detectors: Orifice plates Venturi tube Dall flow tube Pitot tube Rotameter Nutating disk Electromagnetic flow meter Ultrasonic flow detector

The following definitions and descriptions are taken from DOE-HDBK-1013/1-92.

Page 99: Instrumentation and Control

88

Orifice Plates

Orifice plates are flat plates 1/16 to 1/4 inch thick. They are normally mounted between a pair of flanges and are installed in a straight run of smooth pipe to avoid disturbance of flow patterns from fittings and valves.

Three kinds of orifice plates are used: concentric, eccentric, and segmental. The concentric orifice plate is the most common of the three types. The orifice is equidistant (concentric) to the inside diameter of the pipe. Flow through a sharp-edged orifice plate is characterized by a change in velocity. As the fluid passes through the orifice, the fluid converges, and the velocity of the fluid increases to a maximum value. At this point, the pressure is at a minimum value. As the fluid diverges to fill the entire pipe area, the velocity decreases back to the original value. The pressure increases to about 60–80 percent of the original input value. The pressure loss is irrecoverable; therefore, the output pressure will always be less than the input pressure. The pressures on both sides of the orifice are measured, resulting in a DP that is proportional to the flow rate.

Segmental and eccentric orifice plates are functionally identical to the concentric orifice. The circular section of the segmental orifice is concentric with the pipe. The segmental portion of the orifice eliminates damming of foreign materials on the upstream side of the orifice when mounted in a horizontal pipe. Depending on the type of fluid, the segmental section is placed on either the top or bottom of the horizontal pipe to increase the accuracy of the measurement.

Eccentric orifice plates shift the edge of the orifice to the inside of the pipe wall. This design also prevents upstream damming and is used in the same way as the segmental orifice plate.

Venturi Tube

The venturi tube is the most accurate flow-sensing element when properly calibrated. The venturi tube has a converging conical inlet, a cylindrical throat, and a diverging recovery cone. It has no projections into the fluid, no sharp corners, and no sudden changes in contour.

The inlet section decreases the area of the fluid stream, causing the velocity to increase and the pressure to decrease. The low pressure is measured in the center of the cylindrical throat since the pressure will be at its lowest value, and neither the pressure nor the velocity is changing. The recovery cone allows for the recovery of pressure such that total pressure loss is only 10–25 percent. The high pressure is measured upstream of the entrance cone.

Dall Flow Tube

The dall flow tube has a higher ratio of pressure developed to pressure lost than the venturi tube. It is more compact and is commonly used in large flow applications. The tube consists of a short, straight inlet section followed by an abrupt decrease in the inside diameter of the tube. This section, called the inlet shoulder, is followed by the converging inlet cone and a diverging exit cone. The two cones are separated by a slot or gap between the two cones. The low pressure is measured at the slotted throat (area between the two cones). The high pressure is measured at the upstream edge of the inlet shoulder.

Page 100: Instrumentation and Control

89

Pitot Tube

The pitot tube is another primary flow element used to produce a DP for flow detection. In its simplest form, it consists of a tube with an opening at the end. The small hole in the end is positioned such that it faces the flowing fluid. The velocity of the fluid at the opening of the tube decreases to zero. This provides for the high-pressure input to a DP detector. A pressure tap provides the low-pressure input.

The pitot tube actually measures fluid velocity instead of fluid flow rate. Pitot tubes must be calibrated for each specific application, as there is no standardization. This type of instrument can be used even when the fluid is not enclosed in a pipe or duct.

Rotameter

The rotameter is an area flow meter so named because a rotating float is the indicating element. The rotameter consists of a metal float and a conical glass tube, constructed such that the diameter increases with height. When there is no fluid passing through the rotameter, the float rests at the bottom of the tube. As fluid enters the tube, the higher density of the float will cause the float to remain on the bottom. The space between the float and the tube allows for flow past the float. As flow increases in the tube, the pressure drop increases. When the pressure drop is sufficient, the float will rise to indicate the amount of flow. The higher the flow rate, the greater the pressure drop. The higher the pressure drop, the farther up the tube the float rises.

The float should stay at a constant position at a constant flow rate. With a smooth float, fluctuations appear even when flow is constant. By using a float with slanted slots cut in the head, the float maintains a constant position with respect to flow rate. This type of flow meter is usually used to measure low flow rates.

Nutating Disk

The most common type of displacement flow meter is the nutating disk, or wobble plate meter. This type of flow meter is normally used for water service, such as raw water supply and evaporator feed. The movable element is a circular disk that is attached to a central ball. A shaft is fastened to the ball and held in an inclined position by a cam or roller. The disk is mounted in a chamber that has spherical side walls and conical top and bottom surfaces. The fluid enters an opening in the spherical wall on one side of the partition and leaves through the other side. As the fluid flows through the chamber, the disk wobbles, or executes a nutating motion. Since the volume of fluid required to make the disc complete one revolution is known, the total flow through a nutating disc can be calculated by multiplying the number of disc rotations by the known volume of fluid.

Electromagnetic Flow Meter

The electromagnetic flowmeter is similar in principle to the generator. The rotor of the generator is replaced by a pipe placed between the poles of a magnet so that the flow of the fluid in the pipe is normal to the magnetic field. As the fluid flows through this magnetic field, an EMF is induced in it that will be mutually normal (perpendicular) to the magnetic field and the motion of the fluid. This EMF may be measured with the aid of electrodes attached to the pipe and connected to a galvanometer or an equivalent. For a given magnetic

Page 101: Instrumentation and Control

90

field, the induced voltage will be proportional to the average velocity of the fluid. However, the fluid should have some degree of electrical conductivity.

Ultrasonic Flow Detector

Devices such as ultrasonic flow equipment use the Doppler frequency shift of ultrasonic signals reflected from discontinuities in the fluid stream to obtain flow measurements. These discontinuities can be suspended solids, bubbles, or interfaces generated by turbulent eddies in the flow stream. The sensor is mounted on the outside of the pipe, and an ultrasonic beam from a piezoelectric crystal is transmitted through the pipe wall into the fluid at an angle to the flow stream. Signals reflected off flow disturbances are detected by a second piezoelectric crystal located in the same sensor. Transmitted and reflected signals are compared in an electrical circuit, and the corresponding frequency shift is proportional to the flow velocity.

b. Describe density compensation of a steam flow instrument. Include a discussion of the reason for density compensation and the parameters used.

The following is taken from DOE-HDBK-1013/1-92.

Steam flow detection is normally accomplished through the use of a steam flow nozzle. The flow nozzle is commonly used for the measurement of steam flow and other high-velocity fluid flow measurements where erosion may occur. It is capable of measuring approximately 60 percent higher flow rates than an orifice plate with the same diameter. This is due to the streamlined contour of the throat, which is a distinct advantage for the measurement of high-velocity fluids. The flow nozzle requires less straight run piping than an orifice plate. However, the pressure drop is about the same for both. A typical flow nozzle is shown in figure 29.

Source: DOE-HDBK-1013/1-92

Figure 29. Flow nozzle

c. Given a basic diagram of a typical flow detection device, discuss the functions of the following: Differential pressure (D/P) transmitter Extractor Indication

Page 102: Instrumentation and Control

91

This is a performance-based KSA. The Qualifying Official will evaluate its completion.. The following information taken from DOE-HDBK-1013/1-92 may be helpful.

Figure 30 shows a block diagram of a typical differential pressure flow detection circuit. The DP transmitter operation is dependent on the pressure difference across an orifice, venturi, or flow tube. This differential pressure is used to position a mechanical device such as a bellows. The bellows acts against spring pressure to reposition the core of a differential transformer. The transformer’s output voltage on each of two secondary windings varies with a change in flow.

Source: DOE-HDBK-1013/1-92

Figure 30. Differential pressure flow detection block diagram

d. Describe the environmental concerns that can affect the accuracy and reliability of flow sensing instrumentation.

The following is taken from DOE-HDBK-1013/1-92.

The density of the fluid whose flow is to be measured can have a large effect on flow-sensing instrumentation. The effect of density is most important when the flow-sensing instrumentation is measuring gas flows, such as steam. Since the density of a gas is directly affected by temperature and pressure, any changes in either of these parameters will have a direct effect on the measured flow. Therefore, any changes in fluid temperature or pressure must be compensated for to achieve an accurate measurement of flow.

Ambient temperature variations will affect the accuracy and reliability of flow-sensing instrumentation. Variations in ambient temperature can directly affect the resistance of components in the instrumentation circuitry and, therefore, affect the calibration of electric/electronic equipment. The effects of temperature variations are reduced by the design of the circuitry and by maintaining the flow-sensing instrumentation in the proper environment.

The presence of humidity will also affect most electrical equipment, especially electronic equipment. High humidity causes moisture to collect on the equipment. This moisture can

Page 103: Instrumentation and Control

92

cause short circuits, grounds, and corrosion, which in turn may damage components. The effects due to humidity are controlled by maintaining the equipment in the proper environment.

Page 104: Instrumentation and Control

93

e. Discuss the failure modes of the various types of flow indication instruments.

The following is taken from DOE-HDBK-1013/1-92.

The DP transmitter operation is dependent on the pressure difference across an orifice, venturi, or flow tube. This DP is used to position a mechanical device such as a bellows. The bellows acts against spring pressure to reposition the core of a differential transformer. The transformer’s output voltage on each of two secondary windings varies with a change in flow.

A loss of DP integrity of the secondary element, the DP transmitter, will introduce an error into the indicated flow. This loss of integrity implies an impaired or degraded pressure boundary between the high-pressure and low-pressure sides of the transmitter. A loss of DP boundary is caused by anything that results in the high- and low-pressure sides of the DP transmitter being allowed to equalize pressure.

8. Instrumentation and control personnel shall demonstrate a working level knowledge of position indication circuitry and components used in instrumentation and control systems.

a. Describe the basic construction and theory of operation of synchro position indicators.

The following is taken from DOE-HDBK-1013/1-92.

Remote indication or control may be obtained by the use of self-synchronizing motors, called synchro equipment. Synchro equipment consists of synchro units that electrically govern or follow the position of a mechanical indicator or device. An electrical synchro has two distinct advantages over mechanical indicators: (1) greater accuracy, and (2) simpler routing of remote indication.

There are five basic types of synchros that are designated according to their function. The basic types are: transmitters, differential transmitters, receivers, differential receivers, and control transformers. If the power required to operate a device is higher than the power available from a synchro, power amplification is required. “Servomechanism” is a term that refers to a variety of power amplifiers. These devices are incorporated into synchro systems for automatic control rod positioning in some reactor facilities.

The transmitter, or synchro generator, consists of a rotor with a single winding and a stator with three windings placed 120 degrees apart. When the mechanical device moves, the mechanically attached rotor moves. The rotor induces a voltage in each of the stator windings based on the rotor’s angular position. Since the rotor is attached to the mechanical device, the induced voltage represents the position of the attached mechanical device. The voltage produced by each of the windings is utilized to control the receiving synchro position.

Page 105: Instrumentation and Control

94

b. Describe the basic construction and theory of operation of the following variable output position indicators: Potentiometers Linear variable differential transformers (LVDT)

The following descriptions are taken from DOE-HDBK-1013/1-92.

Potentiometers

Potentiometer valve position indicators (figure 31) provide an accurate indication of position throughout the travel of a valve or control rod. The extension is physically attached to a variable resistor. As the extension moves up or down, the resistance of the attached circuit changes, changing the amount of current flow in the circuit. The amount of current is proportional to the valve position.

Source: DOE-HDBK-1013/1-92

Figure 31. Potentiometer valve position indicator

Linear Variable Differential Transformers LVDT

An LVDT is a device that provides accurate position indication throughout the range of valve or control rod travel. Unlike the potentiometer position indicator, no physical connection to the extension is required.

The extension valve shaft, or control rod, is made of a metal suitable for acting as the movable core of a transformer. Moving the extension between the primary and secondary windings of a transformer causes the inductance between the two windings to vary, thereby varying the output voltage proportional to the position of the valve or control rod extension.

Page 106: Instrumentation and Control

95

If the open and shut positions are all that are desired, two small secondary coils could be used at each end of the extension’s travel.

c. Describe the basic construction and theory of operation of the following switch position indicators: Limit switches Reed switches

The following descriptions are taken from DOE-HDBK-1013/1-92.

Limit Switches

A limit switch is a mechanical device that can be used to determine the physical position of equipment. For example, an extension on a valve shaft mechanically trips a limit switch as it moves from open to shut or shut to open. The limit switch gives on/off output that corresponds to valve position. Normally, limit switches are used to provide full open or full shut indications.

Reed Switches

Reed switches are more reliable than limit switches, due to their simplified construction. The switches are constructed of flexible ferrous strips (reeds) and are placed near the intended travel of the valve stem or control rod extension.

When using reed switches, the extension used is a permanent magnet. As the magnet approaches the reed switch, the switch shuts. When the magnet moves away, the reed switch opens. This on/off indicator is similar to mechanical limit switches. By using a large number of magnetic reed switches, incremental position can be measured. This technique is sometimes used in monitoring a reactor’s control rod position.

d. Given a basic diagram of a position indicator, discuss the functions of the following: Detection device Indicator and control circuit

This is a performance-based KSA. The Qualifying Official will evaluate its completion. The following information taken from DOE-HDBK-1013/1-92 may be helpful.

Position detection devices provide a method to determine the position of a valve or control rod. The four types of position indicators are limit switches, reed switches, potentiometer valve position indicators, and LVDTs. Reed and limit switches act as on/off indicators to provide open and closed indications and control functions.

Reed switches can also be used to provide coarse, incremental position indication. Potentiometer and LVDT position indicators provide accurate indication of valve and rod position throughout their travel. In some applications, LVDTs can be used to indicate open and closed positions when small secondary windings are used at either end of the valve stem stroke.

The indicating and control circuitry provides for remote indication of valve or rod position and/or various control functions. Position indications vary from simple indications, such as a light to meter indications showing exact position.

Page 107: Instrumentation and Control

96

Control functions are usually in the form of interlocks. Pump isolation valves are sometimes interlocked with the pump. In some applications, these interlocks act to prevent the pump from being started with the valves shut. The pump/valve interlocks can also be used to automatically turn off the pump if one of its isolation valves shut or to open a discharge valve at some time interval after the pump starts.

Valves are sometimes interlocked with each other. In some systems, two valves may be interlocked to prevent both of the valves from being opened at the same time. This feature is used to prevent undesirable system flowpaths.

Control rod interlocks are normally used to prevent outward motion of certain rods unless certain conditions are met. One such interlock does not allow outward motion of control rods until the rods used to scram the reactor have been withdrawn to a predetermined height. This and all other rod interlocks ensure that the safety of the reactor remains intact.

e. Describe the environmental concerns that can affect the accuracy and reliability of position indication instrumentation.

The following is taken from DOE-HDBK-1013/1-92.

Ambient temperature variations can affect the accuracy and reliability of certain types of position indication instrumentation. Variations in ambient temperature can directly affect the resistance of components in the instrumentation circuitry and therefore, affect the calibration of electric/electronic equipment. The effects of temperature variations are reduced by the design of the circuitry and by maintaining the position indication instrumentation in the proper environment, where possible.

The presence of humidity will also affect most electrical equipment, especially electronic equipment. High humidity causes moisture to collect on the equipment. This moisture can cause short circuits, grounds, and corrosion, which in turn may damage components. The effects due to humidity are controlled by maintaining the equipment in the proper environment, where possible.

f. Discuss the failure modes of the various types of position indication instruments.

The following is taken from DOE-HDBK-1013/1-92.

Potentiometer valve position indicator failures are normally electrical in nature. An electrical short or open will cause the indication to fail at one extreme or the other. If an increase or decrease in the potentiometer resistance occurs, erratic indicated valve position occurs.

LVDTs are extremely reliable. As a rule, failures are limited to rare electrical faults that cause erratic or erroneous indications. An open primary winding will cause the indication to fail to some predetermined value equal to zero differential voltage. This normally corresponds to mid-stroke of the valve. A failure of either secondary winding will cause the output to indicate either full open or full closed.

Failures are normally limited to a reed switch which is stuck open or stuck shut. If a reed switch is stuck shut, the open (closed) indication will be continuously illuminated. If a reed

Page 108: Instrumentation and Control

97

switch is stuck open, the position indication for that switch remains extinguished regardless of valve position.

g. Discuss the functions and operation of position indication switches in motor operated valves.

The following is taken from DOE-HDBK-1013/1-92.

The indicating and control circuitry provides for remote indication of valve or rod position and/or various control functions. Position indications vary from simple indications, such as a light, to meter indications showing exact position.

Control functions are usually in the form of interlocks. Pump isolation valves are sometimes interlocked with the pump. In some applications, these interlocks act to prevent the pump from being started with the valves shut. The pump/valve interlocks can also be used to automatically turn off the pump if one of its isolation valves shut or to open a discharge valve at some time interval after the pump starts.

Valves are sometimes interlocked with each other. In some systems, two valves may be interlocked to prevent both of the valves from being opened at the same time. This feature is used to prevent undesirable system flow paths.

h. Describe the methods used to test and adjust the position indication switches in motor operated valves.

Refer to the local maintenance manuals for methods used to test and adjust the position indication switches in motor-operated valves.

9. Instrumentation and control personnel shall demonstrate a working level knowledge of radiation detection equipment.

a. Describe the operation of a proportional counter. Include the following elements in this discussion: Radiation detection Quenching Voltage variations

The following is taken from DOE-HDBK-1013/2-92.

Radiation Detection

A proportional counter is a detector that operates in the proportional region. Figure 32 illustrates a simplified proportional counter circuit.

Page 109: Instrumentation and Control

98

Source: DOE-HDBK-1013/2-92

Figure 32. Proportional counter

To be able to detect a single particle, the number of ions produced must be increased. As voltage is increased into the proportional region, the primary ions acquire enough energy to cause secondary ionizations (gas amplification) and increase the charge collected. These secondary ionizations may cause further ionization.

In this region, there is a linear relationship between the number of ion pairs collected and applied voltage. A charge amplification of 104 can be obtained in the proportional region. By proper functional arrangements, modifications, and biasing, the proportional counter can be used to detect alpha, beta, gamma, or neutron radiation in mixed radiation fields.

To a limited degree, the fill-gas will determine what type of radiation the proportional counter will be able to detect. Argon and helium are the most frequently used fill gases and allow for the detection of alpha, beta, and gamma radiation. When detection of neutrons is necessary, the detectors are usually filled with boron-triflouride gas.

The simplified circuit, illustrated in figure 32, shows that the detector wall acts as one electrode, while the other electrode is a fine wire in the center of the chamber with a positive voltage applied.

Voltage Variations

When a single gamma ray interacts with the gas in the chamber, it produces a rapidly moving electron that produces secondary electrons. About 10,000 electrons may be formed depending on the gas used in the chamber. The applied voltage can be increased until the amount of recombination is very low. However, further increases do not appreciably increase the number of electrons collected. This region in which all 10,000 electrons are collected is the ionization region.

As applied voltage is increased above 1000 V, the number of electrons becomes greater than the initial 10,000. The additional electrons that are collected are due to gas amplification. As voltage is increased, the velocity of the 10,000 electrons produced increases. However,

Page 110: Instrumentation and Control

99

beyond a certain voltage, the 10,000 electrons are accelerated to such speeds that they have enough energy to cause more ionization. This phenomenon is called gas amplification.

As an example, if the 10,000 electrons produced by the gamma ray are increased to 40,000 by gas amplification, the amplification factor would be 4. Gas amplification factors can range from unity in the ionization region to 103 or 104 in the proportional region. The high amplification factor of the proportional counter is the major advantage over the ionization chamber. The internal amplification of the proportional counter is such that low energy particles (< 10 KeV) can be registered, whereas the ion chamber is limited by amplifier noise to particles of > 10 KeV energy.

Proportional counters are extremely sensitive, and the voltages are large enough so that all of the electrons are collected within a few tenths of a microsecond. Each pulse corresponds to one gamma ray or neutron interaction. The amount of charge in each pulse is proportional to the number of original electrons produced. The proportionality factor in this case is the gas amplification factor. The number of electrons produced is proportional to the energy of the incident particle.

For each electron collected in the chamber, there is a positively charged gas ion left over. These gas ions are heavy compared to an electron and move much more slowly. Eventually the positive ions move away from the positively charged central wire to the negatively charged wall and are neutralized by gaining an electron. In the process, some energy is given off, which causes additional ionization of the gas atoms. The electrons produced by this ionization move toward the central wire and are multiplied en route. This pulse of charge is unrelated to the radiation to be detected and can set off a series of pulses. These pulses must be eliminated or quenched.

Quenching

One method for quenching these discharges is to add a small amount (~ 10%) of an organic gas, such as methane, in the chamber. The quenching gas molecules have a weaker affinity for electrons than the chamber gas does; therefore, the ionized atoms of the chamber gas readily take electrons from the quenching gas molecules. Thus, the ionized molecules of quenching gas reach the chamber wall instead of the chamber gas. The ionized molecules of the quenching gas are neutralized by gaining an electron, and the energy liberated does not cause further ionization, but causes dissociation of the molecule. This dissociation quenches multiple discharges. The quenching gas molecules are eventually consumed, thus limiting the lifetime of the proportional counter. There are, however, some proportional counters that have an indefinite lifetime because the quenching gas is constantly replenished. These counters are referred to as gas flow counters.

b. Describe the operation of an ionization chamber. Include the following elements in this discussion: Radiation detection Quenching Gamma sensitivity reduction

The following is taken from DOE-HDBK-1013/2-92.

Page 111: Instrumentation and Control

100

Radiation Detection

Ionization chambers are electrical devices that detect radiation when the voltage is adjusted so that the conditions correspond to the ionization region. The charge obtained is the result of collecting the ions produced by radiation. This charge will depend on the type of radiation being detected. Ionization chambers have two distinct disadvantages when compared to proportional counters: they are less sensitive, and they have a slower response time.

There are two types of ionization chambers: the pulse-counting ionization chamber and the integrating ionization chamber. In the pulse-counting ionization chamber, the pulses are detected due to particles traversing the chamber. In the integrating chamber, the pulses add, and the integrated total of the ionizations produced in a predetermined period of time is measured. The same type of ionization chamber may be used for either function. However, as a general rule, the integrating type ionization chamber is used.

Flat plates or concentric cylinders may be used in the construction of an ionization chamber. The flat plate design is preferred because it has a well-defined active volume and ensures that ions will not collect on the insulators and cause a distortion of the electric field. The concentric cylinder design does not have a well-defined active volume because of the variation in the electric field as the insulator is approached. Ionization chamber construction differs from the proportional counter (flat plates or concentric cylinders vice a cylinder and central electrode) to allow for the integration of pulses produced by the incident radiation. The proportional counter would require such exact control of the electric field between the electrodes that it would not be practical.

Quenching

Refer to element a of this competency for a discussion of quenching.

Gamma Sensitivity Reduction

When using an ionization chamber for detecting neutrons, beta particles can be prevented from entering the chamber by walls thick enough to shield out all of the beta particles. Gamma rays cannot be shielded from the detector; therefore, they always contribute to the total current read by the ammeter. This effect is not desired because the detector responds not only to neutrons, but also to gamma rays. Several ways are available to minimize this problem.

Discrimination is possible because the ionizations produced by the alpha particles differ in energy levels from those produced by gamma rays. A 1 MeV alpha particle moving through the gas loses all of its energy in a few centimeters. Therefore, all of the secondary electrons are produced along a path of only a few centimeters. A 1 MeV gamma ray produces a 1 MeV electron, and this electron has a long range and loses its energy over the entire length of its range. If we make the sensitive volume of the chamber smaller without reducing the area of the coated boron, the sensitivity to gamma rays is reduced.

c. Given a basic diagram of a proportional counter circuit, discuss the functions of the following: Proportional counter Preamplifier/amplifier Single channel analyzer/discriminator Scaler

Page 112: Instrumentation and Control

101

Timer

This is a performance-based KSA. The Qualifying Official will evaluate its completion. The following information taken from DOE-HDBK-1013/2-92 may be helpful.

Proportional counters measure the charge produced by each particle of radiation. To make full use of the counter’s capabilities, it is necessary to measure the number of pulses and the charge in each pulse. Figure 33 shows a typical circuit used to make such measurements.

Source: DOE-HDBK-1013/2-92

Figure 33. Proportional counter circuit

The capacitor converts the charge pulse to a voltage pulse. The voltage is equal to the amount of charge divided by the capacitance of the capacitor, as given in the following equation:

V = C

Q

where V = voltage pulse (volts) Q = charge (coulombs) C = capacitance (farads)

The preamplifier amplifies the voltage pulse. Further amplification is obtained by sending the signal through an amplifier circuit (typically about 10 volts maximum). The pulse size is then determined by a single channel analyzer. Figure 34 shows the operation of a single channel analyzer.

Page 113: Instrumentation and Control

102

Source: DOE-HDBK-1013/2-92

Figure 34. Single channel analyzer operation

The single channel analyzer has two dial settings: a “level” dial and a “window” dial. For example, when the level is set at 2 volts, and the window at 0.2 volts, the analyzer will give an output pulse only when the input pulse is between 2 and 2.2 volts. The output pulse is usually a standardized height and width logic pulse, as shown in figure 35.

Source: DOE-HDBK-1013/2-92

Figure 35. Single channel analyzer output

Since the single channel analyzer can be set so that an output is only produced by a certain pulse size, it provides for the counting of one specific radiation in a mixed radiation field.

This output is fed to a scaler that counts the number of pulses it receives. A timer gates the scaler so that the scaler counts the pulses for a predetermined length of time. Knowing the

Page 114: Instrumentation and Control

103

number of counts per a given time interval allows calculation of the count rate (number of counts per unit time).

Proportional counters can also count neutrons by introducing boron into the chamber. The most common means of introducing boron is by combining it with trifluoride gas to form boron trifluoride (BF3). When a neutron interacts with a boron atom, an alpha particle is emitted.The BF3 counter can be made sensitive to neutrons and not to gamma rays.

Gamma rays can be eliminated because the neutron-induced alpha particles produce more ionizations than gamma rays produce. This is due mainly to the fact that gamma ray-induced electrons have a much longer range than the dimensions of the chamber; the alpha particle energy is, in most cases, greater than gamma rays produced in a reactor. Therefore, neutron pulses are much larger than gamma ray-produced pulses.

By using a discriminator, the scaler can be set to read only the larger pulses produced by the neutron. A discriminator is basically a single channel analyzer with only one setting. Figure 36 illustrates the operation of a discriminator.

Source: DOE-HDBK-1013/2-92

Figure 36. Discriminator

If the discriminator is set at 2 volts, then any input pulse > 2 volts causes an output pulse. Figure 37 shows a typical circuit used to measure neutrons with a BF3 proportional counter.

Page 115: Instrumentation and Control

104

Source: DOE-HDBK-1013/2-92

Figure 37. BF3 proportional counter circuit

The BF3 proportional counter is used to monitor low power levels in a nuclear reactor. It is used in the startup or source range channels. Proportional counters cannot be used at high power levels because they are pulse-type detectors. Typically, it takes 10 to 20 microseconds for each pulse to go from 10 percent of its peak, to its peak, and back to 10 percent. If another neutron interacts in the chamber during this time, the two pulses are superimposed. The voltage output would never drop to zero between the two pulses, and the chamber would draw a steady current as electrons are being produced.

d. Describe how a compensated ion chamber compensates for gamma radiation.

The following is taken from DOE-HDBK-1013/2-92.

Compensating for the response to gamma rays extends the useful range of the ionization chamber. Compensated ionization chambers consist of two separate chambers: one chamber is coated with boron, and one chamber is not. The coated chamber is sensitive to both gamma rays and neutrons, while the uncoated chamber is sensitive only to gamma rays. Instead of having two separate ammeters and subtracting the currents, the subtraction of these currents is done electrically, and the net output of both detectors is read on a single ammeter. If the polarities are arranged so that the two chambers’ currents oppose one another, the reading obtained from the ammeter indicates the difference between the two currents. One plate of the compensated ion chamber is common to both chambers; one side is coated with boron, while the other side is not.

The boron coated chamber is referred to as the working chamber; the uncoated chamber is called the compensating chamber. When exposed to a gamma source, the battery for the working chamber will set up a current flow that deflects the meter in one direction. The compensating chamber battery will set up a current flow that deflects the meter in the opposite direction. If both chambers are identical, and both batteries are of the same voltage,

Page 116: Instrumentation and Control

105

the net current flow is exactly zero. Therefore, the compensating chamber cancels the current due to gamma rays.

The two chambers of a compensated ion chamber are never truly identical; in fact, they are often purposely constructed in different shapes. The chambers are normally constructed as concentric cylinders.

The use of concentric cylinders has an advantage because both chambers are exposed to nearly the same radiation field. Even though the chambers are not identical, proper selection of the operating voltage eliminates the gamma current. Working chamber operating voltage is given by the manufacturer and is selected to cause operation on the flat portion of the response curve, where very little recombination occurs. If working chamber voltage is increased to operating voltage, and compensating voltage is left at zero, the measured current will be due to gammas only in the working chamber. For this reason, compensating voltage is set while the reactor is shutdown (a minimum number of neutrons are present).

As the compensating chamber voltage is raised, the measured current will decrease as more of the current from the working chamber is canceled by the current from the compensating chamber. Eventually, the voltage becomes large enough so that the two currents cancel. When the currents cancel, the chamber is said to be 100 percent compensated, and the measured current is zero. At 100 percent compensation, the detector will respond to neutrons alone.

The compensating chamber usually has a slightly larger sensitive volume than the working chamber. Increasing the compensating current to a value greater than the working chamber current results in a net negative current. In this condition, the chamber is considered to be over-compensated. The compensating chamber cancels too much current from the working chamber, and the meter reads low. In this case, the compensating chamber cancels out all of the gamma current and some of the neutron current.

Percent compensation of a compensated ion chamber gives the percentage of the gamma rays that are canceled out. Percent compensation may be calculated based on measured current when the detector is exposed to gamma rays.

e. Describe the operation of an electroscope ionization chamber.

The following is taken from DOE-HDBK-1013/2-92.

The gold-leaf electroscope has been widely used in the past to study ionizing radiation. The first measurement of the properties of ionizing radiation was accomplished with this instrument. A microscope containing a graduated scale in the eyepiece is used to observe the gold leaf.

The newest electroscope uses a quartz fiber and has many advantages over the gold-leaf type. It is portable, less dependent on position, much smaller in size, and more sensitive. The capacity of the quartz fiber electroscope is about 0.2 pico-farads, and its voltage sensitivity is about one volt per division on the scale. The sensitive element is a fine gold-plated quartz fiber mounted on a parallel metal support.

A small piece of quartz fiber is mounted across the end of the gold-plated quartz fiber and serves as an index that is viewed through a microscope equipped with an eyepiece scale. The

Page 117: Instrumentation and Control

106

quartz fiber is charged by a battery pressing the charging key. As the quartz fiber is being charged, it is deflected from the support. It takes approximately 200 volts to produce full-scale deflection of the fiber. A glass window at the end of the ionization chamber allows for exposure of the fiber. As the gas (air) is ionized by the incident radiation, the fiber moves toward the position of zero charge.

Due to the electroscope’s dependability, simplicity, accuracy, and sensitivity, it is widely used in gamma radiation measurement. A self-reading pocket dosimeter is an example of an electroscope ionization chamber. Pocket dosimeters provide personnel with a means of monitoring their radiation exposure. The dosimeters are available in many ranges of gamma exposures from 0 through 200 milliroentgens to 0 through 1000 roentgens. The sensitivity of the instrument is determined at the time of manufacture. Appropriate scale markings are provided with each dose range.

f. Describe the operation of a Geiger-Müller (G-M) detector. Include the following elements in this discussion: Radiation detection Quenching Positive ion sheath

The following is taken from DOE-HDBK-1013/2-92.

Radiation Detection

The Geiger-Müller or G-M detector is a radiation detector that operates in region V, or G-M region, as shown in figure 38. G-M detectors produce larger pulses than other types of detectors. However, discrimination is not possible, since the pulse height is independent of the type of radiation. Counting systems that use G-M detectors are not as complex as those using ion chambers or proportional counters.

Source: DOE-HDBK-1013/2-92

Figure 38. Gas ionization curve

Page 118: Instrumentation and Control

107

The number of electrons collected by a gas-filled detector varies as applied voltage is increased. Once the voltage is increased beyond the proportional region, another flat portion of the curve is reached; this is known as the G-M region. The G-M region has two important characteristics:

1. The number of electrons produced is independent of applied voltage. 2. The number of electrons produced is independent of the number of electrons

produced by the initial radiation.

This means that the radiation producing one electron will have the same size pulse as radiation producing hundreds or thousands of electrons. The reason for this characteristic is related to the way in which electrons are collected.

When a gamma produces an electron, the electron moves rapidly toward the positively charged central wire. As the electron nears the wire, its velocity increases. At some point its velocity is great enough to cause additional ionizations. As the electrons approach the central wire, the additional ionizations produce a larger number of electrons in the vicinity of the central wire.

Positive Ion Sheath and Quenching

For each electron produced, there is a positive ion produced. As the applied voltage is increased, the number of positive ions near the central wire increases, and a positively charged cloud (called a positive ion sheath) forms around the central wire. The positive ion sheath reduces the field strength of the central wire and prevents further electrons from reaching the wire. It might appear that a positive ion sheath would increase the effect of the positive central wire, but this is not true; the positive potential is applied to the very thin central wire that makes the strength of the electric field very high. The positive ion sheath makes the central wire appear much thicker and reduces the field strength. This phenomenon is called the detector’s space charge. The positive ions will migrate toward the negative chamber picking up electrons. As in a proportional counter, this transfer of electrons can release energy, causing ionization and the liberation of an electron. To prevent this secondary pulse, a quenching gas is used, usually an organic compound.

The G-M counter produces many more electrons than does a proportional counter; therefore, it is a much more sensitive device. It is often used in the detection of low-level gamma rays and beta particles for this reason. Electrons produced in a G-M tube are collected very rapidly, usually within a fraction of a microsecond. The output of the G-M detector is a pulse charge and is often large enough to drive a meter without additional amplification. Because the same size pulse is produced regardless of the amount of initial ionization, the G-M counter cannot distinguish radiation of different energies or types. This is the reason G-M counters are not adaptable for use as neutron detectors. The G-M detector is mainly used for portable instrumentation due to its sensitivity, simple counting circuit, and ability to detect low-level radiation.

g. Describe the operation of a scintillation counter. Include the following elements in this discussion: Radiation detection Three classes of phosphors Photomultiplier tube operation

Page 119: Instrumentation and Control

108

The following descriptions are taken from DOE-HDBK-1013/2-92.

Scintillation Counter

The scintillation counter is a solid-state radiation detector that uses a scintillation crystal (phosphor) to detect radiation and produce light pulses. Figure 39 is important in the explanation of scintillation counter operation.

Source: DOE-HDBK-1013/2-92

Figure 39. Electronic energy band of an ionic crystal

Radiation Detection

As radiation interacts in the scintillation crystal, energy is transferred to bound electrons of the crystal’s atoms. If the energy that is transferred is greater than the ionization energy, the electron enters the conduction band and is free from the binding forces of the parent atom. This leaves a vacancy in the valence band and is termed a hole. If the energy transferred is less than the binding energy, the electron remains attached, but exists in an excited energy state. Once again, a hole is created in the valence band. By adding impurities during the growth of the scintillation crystal, the manufacturer is able to produce activator centers with energy levels located within the forbidden energy gap. The activator center can trap a mobile electron, which raises the activator center from its ground state (G) to an excited state (E). When the center de-excites, a photon is emitted. The activator centers in a scintillation crystal are referred to as luminescence centers. The emitted photons are in the visible region of the electromagnetic spectrum.

Page 120: Instrumentation and Control

109

Scintillation counters are constructed by coupling a suitable scintillation phosphor to a light-sensitive photo-multiplier tube.

Three Classes of Phosphors

There are three classes of solid state scintillation phosphors: organic crystals, inorganic crystals, and plastic phosphors.

Inorganic crystals include lithium iodide, sodium iodide, cesium iodide, and zinc sulfide. Inorganic crystals are characterized by high density, high atomic number, and pulse decay times of approximately one microsecond. Thus, they exhibit high efficiency for detection of gamma rays and are capable of handling high count rates.

Organic scintillation phosphors include naphthalene, stilbene, and anthracene. The decay time of this type of phosphor is approximately 10 nanoseconds. This type of crystal is frequently used in the detection of beta particles.

Plastic phosphors are made by adding scintillation chemicals to a plastic matrix. The decay constant is the shortest of the three phosphor types, approaching one or two nanoseconds. The plastic has a high hydrogen content; therefore, it is useful for fast neutron detectors.

Photomultiplier Tube Operation

The photomultiplier is a vacuum tube with a glass envelope containing a photocathode and a series of electrodes called dynodes. Light from a scintillation phosphor liberates electrons from the photocathode by the photoelectric effect. These electrons are not of sufficient number or energy to be detected reliably by conventional electronics. However, in the photomultiplier tube, they are attracted by a voltage drop of about 50 volts to the nearest dynode.

The photoelectrons strike the first dynode with sufficient energy to liberate several new electrons for each photoelectron. The second-generation electrons are, in turn, attracted to the second dynode where a larger third-generation group of electrons is emitted. This amplification continues through 10 to 12 stages. At the last dynode, sufficient electrons are available to form a current pulse suitable for further amplification by transistor circuits. The voltage drops between dynodes are established by a single external bias, approximately 1000 volts DC, and a network of external resistors to equalize the voltage drops.

The advantages of a scintillation counter are its efficiency and the high precision and counting rates that are possible. These latter attributes are a consequence of the extremely short duration of the light flashes, from about 10-9 to 10-6 seconds. The intensity of the light flash and the amplitude of the output voltage pulse are proportional to the energy of the particle responsible for the flash. Consequently, scintillation counters can be used to determine the energy, as well as the number, of the exciting particles (or gamma photons). The photomultiplier tube output is very useful in radiation spectrometry (determination of incident radiation energy levels).

Page 121: Instrumentation and Control

110

h. Describe the operation of a gamma spectrometer. Include the following elements in this discussion: Type of detector used Multichannel analyzer operation

The following descriptions are taken from DOE-HDBK-1013/2-92.

Type of Detector Used

Gamma spectroscopy is a radiochemistry measurement method that determines the energy and count rate of gamma rays emitted by radioactive substances. Gamma spectroscopy is an extremely important measurement. A detailed analysis of the gamma ray energy spectrum is used to determine the identity and quantity of gamma emitters present in a material.

The equipment used in gamma spectroscopy includes a detector, a pulse sorter (multichannel analyzer), and associated amplifiers and data readout devices. The detector is normally a sodium iodide scintillation counter. Figure 40 shows a block diagram of a gamma spectrometer.

Source: DOE-HDBK-1013/2-92

Figure 40. Gamma spectrometer block diagram

Multichannel Analyzer Operation

The multichannel pulse height analyzer is a device that will separate pulses based on pulse height. Each energy range of pulse height is referred to as a channel. The pulse height is proportional to the energy lost by a gamma ray. Separation of the pulses, based on pulse height, shows the energy spectrum of the gamma rays that are emitted. Multichannel analyzers typically have 100 or 200 channels over an energy range of 0 to 2 MeV. The output is a plot of pulse height and gamma activity as shown in figure 41. By analyzing the

Page 122: Instrumentation and Control

111

spectrum of gamma rays emitted, the user can determine the elements that caused the gamma pulses.

Source: DOE-HDBK-1013/2-92

Figure 41. Multichannel analyzer output

i. Describe how the following detect neutrons: Self-powered neutron detector Wide range fission chamber Flux wire

The following descriptions are taken from DOE-HDBK-1013/2-92.

Page 123: Instrumentation and Control

112

Self-Powered Neutron Detector

In very large reactor plants, the need exists to monitor neutron flux in various portions of the core on a continuous basis. This allows for quick detection of instability in any section of the core. This need brought about the development of the self-powered neutron detector that is small, inexpensive, and rugged enough to withstand the in-core environment. The self-powered neutron detector requires no voltage supply for operation. Figure 42 illustrates a simplified drawing of a self-powered neutron detector.

Source: DOE-HDBK-1013/2-92

Figure 42. Self-powered neutron detector

The central wire of a self-powered neutron detector is made from a material that absorbs a neutron and undergoes radioactive decay by emitting an electron (beta decay). Typical materials used for the central wire are cobalt, cadmium, rhodium, and vanadium. A good insulating material is placed between the central wire and the detector casing. Each time a neutron interacts with the central wire it transforms one of the wire’s atoms into a radioactive nucleus. The nucleus eventually decays by the emission of an electron. Because of the emission of these electrons, the wire becomes more and more positively charged. The positive potential of the wire causes a current to flow in the resistor. A millivoltmeter measures the voltage drop across the resistor. The electron current from beta decay can also be measured directly with an electrometer.

There are two distinct advantages of the self-powered neutron detector: (1) very little instrumentation is required—only a millivoltmeter or an electrometer, and (2) the emitter material has a much greater lifetime than boron or 235U lining (used in wide range fission chambers).

One disadvantage of the self-powered neutron detector is that the emitter material decays with a characteristic half-life. In the case of rhodium and vanadium, which are two of the most useful materials, the half-lives are 1 minute and 3.8 minutes, respectively. This means that the detector cannot respond immediately to a change in neutron flux, but takes as long as 3.8 minutes to reach 63 percent of steady-state value. This disadvantage is overcome by

Page 124: Instrumentation and Control

113

using cobalt or cadmium emitters that emit their electrons within 10–14 seconds after neutron capture. Self-powered neutron detectors that use cobalt or cadmium are called prompt self-powered neutron detectors.

Wide Range Fission Chamber

Fission chambers use neutron-induced fission to detect neutrons. The chamber is usually similar in construction to that of an ionization chamber, except that the coating material is highly enriched 235U. The neutrons interact with the 235U, causing fission. One of the two fission fragments enters the chamber, while the other fission fragment embeds itself in the chamber wall.

One advantage of using 235U coating rather than boron is that the fission fragment has a much higher energy level than the alpha particle from a boron reaction. Neutron-induced fission fragments produce many more ionizations in the chamber per interaction than do the neutron-induced alpha particles. This allows the fission chambers to operate in higher gamma fields than an uncompensated ion chamber with boron lining. Fission chambers are often used as current indicating devices and pulse devices simultaneously. They are especially useful as pulse chambers, due to the very large pulse size difference between neutrons and gamma rays. Because of the fission chamber’s dual use, it is often used in wide range channels in nuclear instrumentation systems. Fission chambers are also capable of operating over the source and intermediate ranges of neutron levels.

Flux Wire

Whenever it is necessary to measure reactor neutron flux profiles, a section of wire or foil is inserted directly into the reactor core. The wire or foil remains in the core for the length of time required for activation to the desired level. The cross-section of the flux wire or foil must be known to obtain an accurate flux profile. After activation, the flux wire or foil is rapidly removed from the reactor core and the activity counted. Activated foils can also discriminate energy levels by placing a cover over the foil to filter out (absorb) certain energy level neutrons. Cadmium covers are typically used for this purpose. The cadmium cover effectively filters out all of the thermal neutrons.

10. Instrumentation and control personnel shall demonstrate a working level knowledge of nuclear instrumentation.

a. Define the following terms: Signal-to-noise ratio Discriminator Analog Logarithm Period Decades per minute (DPM) Scalar

The following definitions are taken from DOE-HDBK-1013/2-92.

Page 125: Instrumentation and Control

114

Signal-to-Noise Ratio

Signal-to-noise ratio is the ratio of the electrical output signal to the electrical noise generated in the cable run or in the instrumentation.

Discriminator

Discrimination in radiation detection circuits refers to the process of distinguishing between different types of radiation on the basis of pulse height. A discriminator circuit selects the minimum or maximum pulse height that is to be counted.

Analog

Analog is defined as a mechanism in which data is represented by continuously variable physical quantities. As it applies to the intermediate range, the output of the intermediate range is an analog current. Due to the wide range of the flux measured, use of logarithmic circuitry is required for indication on a single scale instrument. Analog is used in contrast to digital to refer to circuits in which the magnitude of the signal carries the information.

Logarithm

Logarithm is defined as the exponent that indicates the power to which a number is raised to produce a given number (i.e., the logarithm of 100 to the base 10 is 2). When discussing nuclear instrumentation, this term refers to the electronic circuitry of the source and intermediate ranges. These ranges utilize logarithms due to the wide range of measured flux and the necessity to measure that flux on a single meter scale.

Period

In many applications it is essential to know the rate of change of power. This rate normally increases or decreases exponentially with time. The time constant for this change is referred to as the period. A period of 5 seconds means that the value changes by a factor of e (2.718) in 5 seconds.

Decades per Minute

Rate circuits are important in the source and intermediate ranges. Rate information is displayed on a meter in decades per minute. These meters indicate how fast reactor power is changing in decades (power of 10) each minute.

Scalar

The “scalar” refers to a measurement or quantity that is capable of being represented on a scale (i.e., neutron flux on source range, intermediate range, and power range meters).

b. Describe the operation of the detectors used in each of the following nuclear instrument applications: Source range Intermediate range Power range

The following descriptions are taken from DOE-HDBK-1013/2-92.

Page 126: Instrumentation and Control

115

Source Range

Source range instrumentation normally consists of two redundant count rate channels, each composed of a high-sensitivity proportional counter and associated signal measuring equipment. These channels are typically used over a counting range of 0.1 to 106 counts per second, but vary based on reactor design. Their outputs are displayed on meters in terms of the logarithm of the count rate.

Source range instrumentation also measures the rate of change of the count rate. The rate of change is displayed on meters in terms of the startup rate from -1 to +10 decades per minute. Protective functions are not normally associated with source range instrumentation because of inherent limitations in this range. However, interlocks may be incorporated.

Many reactor plants have found it necessary to place source range proportional counters in lead shielding to reduce gamma flux at the detectors. This serves two functions: (1) it increases the low-end sensitivity of the detector, and (2) it adds to detector life. Another means by which detector life is extended is to disable the high-voltage power supply to the detector and short the signal lead when neutron flux has passed into the intermediate range. There are some reactor plants that have made provisions for moving the source range detectors from their operating positions to a position of reduced neutron flux level once the flux level increases above the source range.

Intermediate Range

Intermediate-range nuclear instrumentation consists of a minimum of two redundant channels. Each of these channels is made up of a boron-lined or boron gas-filled compensated ion chamber and associated signal measuring equipment of which the output is a steady current produced by the neutron flux.

The compensated ion chamber is used in the intermediate range because the current output is proportional to the relatively stable neutron flux, and it compensates for signals from gamma flux. This range of indication also provides a measure of the rate of change of neutron level. This rate of change is displayed on meters in terms of startup rate in decades per minute (-1 to +10 decades per minute). High startup rate on either channel may initiate a protective action. This protective action may be in the form of a control rod withdrawal inhibit and alarm, or a high startup rate reactor trip.

Power Range

Power range nuclear instrumentation normally consists of four identical linear power level channels that originate in eight uncompensated ion chambers. The output is a steady current produced by the neutron flux. Uncompensated ion chambers are used in the power range because gamma compensation is unnecessary; the neutron-to-gamma flux ratio is high. Having a high neutron-to-gamma flux ratio means that the number of gammas is insignificant compared to the number of neutrons.

The output of each power range channel is directly proportional to reactor power and typically covers a range from 0 to 125 percent of full power, but varies with each reactor. The output of each channel is displayed on a meter in terms of power level in percent of full rated power. The gain of each instrument is adjustable, which provides a means for

Page 127: Instrumentation and Control

116

calibrating the output. This adjustment is normally determined by using a plant heat balance. Protective actions may be initiated by high power level on any two channels; this is termed coincidence operation.

c. Given a basic diagram of a typical source range instrument, discuss the functions of the following components: Linear amplifier Discriminator Pulse integrator Log count rate amplifier Differentiator

This is a performance-based KSA. The Qualifying Official will evaluate its completion. The following information taken from DOE-HDBK-1013/2-92 may be helpful.

Figure 43 shows a typical source range channel in functional form.

Source: DOE-HDBK-1013/2-92

Figure 43. Source range channel

B10 lined or BF3 gas-filled proportional counters are normally used as source range detectors. Proportional counter output is in the form of one pulse for every ionizing event; therefore, there is a series of random pulses varying in magnitude representing neutron and gamma ionizing events.

The pulse height may only be a few millivolts, which is too low to be directly used without amplification. The linear amplifier amplifies the input signal by a factor of several thousand to raise the pulse height to several volts.

Page 128: Instrumentation and Control

117

The discriminator excludes passage of pulses that are less than a predetermined level. The function of the discriminator is to exclude noise and gamma pulses that are lower in magnitude than neutron pulses. The pulses are then sent to the pulse integrator where they are integrated to give a signal that is proportional to the logarithm of the count rate.

The log count rate amplifier then amplifies the signal, which varies directly as the logarithm of the pulse rate, in the detector. The logarithmic count rate is then displayed on a meter with a logarithmic scale in counts per second.

The logarithmic count rate signal is differentiated to measure the rate of change in neutron flux. The differentiator output is proportional to reactor period. The value of reactor period is inversely proportional to the actual rate of change of reactor power and relates to power changes by factors of e (2.718). The power rate change based on factors of 10, in decades per minute, is more meaningful to the reactor operator. Therefore, the output of the differentiator is converted from reactor period to decades per minute through the meter scale used.

d. Given a basic diagram of a typical intermediate range instrument, discuss the functions of the following components: Log amplifier Differentiator Reactor protection interface

This is a performance-based KSA. The Qualifying Official will evaluate its completion. The following information taken from DOE-HDBK-1013/2-92 may be helpful.

Figure 44 shows a typical intermediate-range channel.

Source: DOE-HDBK-1013/2-92

Figure 44. Intermediate range channel

Page 129: Instrumentation and Control

118

e. Discuss the reason gamma compensation is not required in the power range.

The following is taken from DOE-HDBK-1013/2-92.

Power range nuclear instrumentation normally consists of four identical linear power level channels that originate in eight uncompensated ion chambers. The output is a steady current produced by the neutron flux. Uncompensated ion chambers are utilized in the power range because gamma compensation is unnecessary; the neutron-to-gamma flux ratio is high. Having a high neutron-to-gamma flux ratio means that the number of gammas is insignificant compared to the number of neutrons.

f. Given a basic diagram of a typical power range instrument, discuss the functions of the following components:

Linear amplifier Reactor protection interface

This is a performance-based KSA. The Qualifying Official will evaluate its completion.. The following information taken from DOE-HDBK-1013/2-92 may be helpful.

Figure 45 shows a typical power range channel.

Source: DOE-HDBK-1013/2-92

Figure 45. Power range channel

Two detectors in each channel are functionally connected in parallel so that the measured signal is the sum of the two detectors. This output drives a linear amplifier that amplifies the signal to a useful level.

The reactor protective interface provides signals for protective actions. Examples of protective action signals provided by the power range include a signal to the reactor protection system at a selected value (normally 10 percent

reactor power) to disable the high startup rate reactor trip a signal to protective systems when reactor power level exceeds predetermined values

Page 130: Instrumentation and Control

119

a signal for use in the reactor control system a signal to the power-to-flow circuit

g. Discuss the failure modes of fission chambers, ion chambers, and proportional counters.

Fission Chambers

The following is taken from Freepatentsonline, Integral Multi-Sensor Radiation Detector.

The neturon detector types presently available consist of ion chambers, fission counters, and self-powered detectors of the prompt and slow response types.

Present ion and fission chamber designs fail at one-third or less of the required life. Available experimental evidence indicates several modes of failure. The majority of ion chamber failures due to radiation damage can be attributed to either cable failure at the normal operating bias voltages (150–200 volts) or seal failure resulting in loss or contamination of the chamber fill gas.

The slow response self-powered detectors in addition to being susceptible to radiation damage are unacceptable due to slow response and poor sensitivity.

The prompt self-powered detectors have been unsuccessful due to sensitivity to spurious electrical signals that render the output unreliable.

Ion Chambers

The following is taken from DOE-HDBK-1013/2-92.

When using an ionization chamber for detecting neutrons, beta particles can be prevented from entering the chamber by walls thick enough to shield out all of the beta particles. Gamma rays cannot be shielded from the detector; therefore, they always contribute to the total current read by the ammeter. This effect is not desired because the detector responds not only to neutrons, but also to gamma rays.

Proportional Counters

The following is taken from Patentstorm, Proportional Counter.

Known proportional counters typically include a substantially cylindrical cathode, and an anode wire extends through the cathode. The cathode is sealed at both ends, and may be filled with a gas, such as helium-3 gas. The anode wire, of course, is insulated from the cathode. For example, a support insulator is secured to the anode at one end of the cathode and insulates the one end of the anode from the cathode. At the other end of the cathode, the wire is electrically connected to a lead wire, and the lead wire extends through a seal tube positioned at the end of the cathode.

To ensure accurate neutron counting, it is important to maintain the anode wire taut. However, particularly in some applications and due to temperature variations, keeping the anode wire taut is a significant challenge. For example, in an extremely hot operating environment, the cathode expands more than the anode. As the cathode expands, the tension

Page 131: Instrumentation and Control

120

on the anode wire is increased. Such expansion would stretch or break the anode. A spring is required to maintain anode wire tension.

In the past, a tension spring coupled at one end to the anode wire and coupled at its other end to the lead wire has been used to keep the anode wire taut in a variety of operating conditions. Although such an assembly of the anode wire, spring, and lead wire provides satisfactory results, the assembly is susceptible to vibration failure. Particularly, if the counter is subjected to prolonged vibration, the spot welds between the spring, anode wire, and lead wire have been found to sometimes fail.

Accordingly, it is desirable to provide a proportional counter that provides consistent and accurate readings in a wide range of temperature conditions and during vibration. It also would be desirable to provide such a proportional counter in which the anode wire is maintained substantially taut in a wide variety of applications and is less susceptible to vibration failure, without significantly increasing the costs of the proportional counter.

h. Discuss the various nondestructive assay (NDA) instruments (e.g., gamma counters, neutron multiplicity counters, etc.) available for measuring isotopic content, fissile material content, activity concentration for materials accountability of special nuclear materials and/or nuclear waste.

The following is taken from NUREG/CR-5550.

The term “nondestructive assay” (NDA) is applied to a series of measurement techniques for nuclear fuel materials. The techniques measure radiation induced or emitted spontaneously from the nuclear material. The measurements are nondestructive in that they do not alter the physical or chemical state of the nuclear material. In some cases, the emitted radiation is unique to the isotope of interest, and the radiation intensity can often be related to the mass of the isotopes. Other techniques to measure nuclear material involve sampling the material and analyzing the sample with destructive chemical procedures. NDA obviates the need for sampling, reduces operator exposure, and is much faster than chemical assay. Unfortunately, however, NDA is usually less accurate than chemical assay. The development of NDA reflects a trend toward automation and workforce reduction that is occurring throughout our society. NDA measurements are applied in all fuel-cycle facilities for material accounting, process control, criticality control, and perimeter monitoring.

The original impetus for NDA development was the need for increased nuclear material safeguards. As safeguard agencies throughout the world needed more nuclear material measurements, it became clear that rapid measurement methods were required that would not alter the state of nuclear material items. Development efforts to address these needs were supported by the U.S. Nuclear Regulatory Commission, the DOE, and the International Atomic Energy Agency. Rapid nondestructive measurement techniques are required by the safeguards inspectors who must verify the inventories of nuclear material held throughout the world.

NDA techniques are characterized as passive or active depending on whether they measure radiation from the spontaneous decay of the nuclear material or radiation induced by an

Page 132: Instrumentation and Control

121

external source. The principal NDA techniques are classified as gamma-ray assay, neutron assay, and calorimetry.

11. Instrumentation and control personnel shall demonstrate a working level knowledge of refractometers (as applicable to their facilities).

a. Discuss the use of refractometers in various facility applications.

The following is taken from the Cole Parmer Technical Library, Refractometers.

A refractometer is a simple instrument used for measuring concentrations of aqueous solutions. It requires only a few drops of liquid, and is used throughout the food, agricultural, chemical, and manufacturing industries.

The use and application of refractometers varies. This is a facility-based knowledge requirement. The local Qualifying Official will evaluate the completions of this KSA.

b. Discuss how the refractive index of a solution varies with the density of the solution.

The following is taken from the Cole-Parmer Technical Library, Refractometers.

When light enters a liquid. it changes direction; this is called refraction. Refractometers measure the degree to which the light changes direction, called the angle of refraction. A refractometer takes the refraction angles and correlates them to refractive index values that have been established. The concentrations of solutions can be determined using these values. For example, solutions have different refractive indexes depending on their concentration.

The prism in the refractometer has a greater refractive index than the solution. Measurements are read at the point where the prism and solution meet. With a low-concentration solution, the refractive index of the prism is much greater than that of the sample, creating a large refraction angle and a low reading. The reverse would happen with a high-concentration solution.

c. Discuss critical angle of refraction and how fully reflected light rays and partially reflected light rays form an image to derive the measurement.

The following is taken from the School of Champions, Snell’s Law for the Reflection of Light.

When visible light enters a transparent material, such as glass, at an angle, the direction of the light is refracted or bent at a different angle. The angle is determined by the initial angle and the index of refraction of the two materials. Snell’s law is an equation that determines the angle at which a ray or beam of light is refracted. When the light passes from a material of high index of refraction to low index of refraction, there is an angle at which the light starts to be reflected at the interface of the materials. This is called the critical angle for refraction.

If A in figure 46 is the index of refraction of the first material and a is the angle of the incoming ray or beam of light with respect to the perpendicular or normal to the surface, then

Page 133: Instrumentation and Control

122

b will be the angle to the normal of the ray in the second material where B is its index of refraction.

Source: School of Champions, Snell’s Law for the Refraction of Light

Figure 46. Light is bent going from first material to second

The index of refraction in material B equals the speed of light in a vacuum (c) divided by the speed of light in the material (cB).

B = Bc

c

Since index B is greater than index A, the speed of light in material B is less than the speed in material A. Thus, according to Snell’s law, the angle b is less than the angle a.

Snell’s law is written as

A*sin(a) = B*sin(b)

where sin(a) = the sine of angle a sin(b) = the sine of angle b

Typically, you want to find angle b or how much the light will be bent in the second material. Using some algebra, Snell’s law can be rewritten as

sin(b) = A*sin(a)/B or

b = arcsin[A*sin(a)/B]

where arcsin[A*sin(a)/B] is the arcsine or angle whose sine is A*sin(a)/B.

Thus, if the first material is air (index approximately = 1), the incoming angle is 30o and the second material is glass with an index = 1.5, you can calculate the angle of the light in glass.

sin(b) = A*sin (a)/B sin(b) = 1*sin (30o)/ 1.5

Page 134: Instrumentation and Control

123

sin(b) = 0.5/ 1.5 = 0.33 b = arcsine (0.33) = 19.5o

Thus, if light hits glass at 30o, its angle will change to 19.5o within the glass. Of course, if it is a glass plate, you will then use the opposite to obtain the exit angle of 30o back into air.

An interesting thing happens when light is going from a material with higher index of refraction to a lower index, such as going from water to air. There is an angle at which the light will not pass into the other material and will start to be reflected at the surface. This is called the critical angle of refraction.

Source: School of Champions, Snell’s Law for the Refraction of Light

Figure 47. Light going from high index to low

In figure 47 you can see that angle b is larger than angle a when index A is larger than index B. At some angle a, angle b will equal 90 degrees as shown in figure 48.

Source: School of Champions, Snell’s Law for the Refraction of Light

Figure 48. Light at critical angle for refraction

Page 135: Instrumentation and Control

124

Using Snell’s law, we can calculate this critical angle. Let the first material be water with index of refraction = 1.33, and let the second material be air with index = 1.

We want to find angle a: sin(a) = B*sin(b)/A sin(a) = 1*sin(90o)/1.33 since sin(90o) = 1, sin(a) = 1/1.33 = 0.75 a = arcsin(0.75) = 48.6o

This is the critical angle. When angle a is greater than that angle, the light will be reflected.

At angles greater than the critical angle for refraction, the light demonstrates an internal reflection as shown in figure 49.

Source: School of Champions, Snell’s Law for the Refraction of Light

Figure 49. Internal reflection of light

When a is greater than the critical angle for refraction as in figure 49, the light is reflected off the interface of the two materials just like a mirror.

The law of reflection holds where the incident angle equals the reflected angle. Thus, b = 180o - a.

12. Instrumentation and control personnel shall demonstrate a working level knowledge of sensor characteristics and instrument loop signal types.

a. Define and discuss the following sensor characteristics: Range Response time Accuracy Precision Sensitivity Dead-band

Page 136: Instrumentation and Control

125

The following definitions are taken from Lake Shore Cryotronics, Inc, Sensor Characteristics,unless stated othewise.

Range

Two factors limit the useful range of a sensor. First, the physical phenomena responsible for the temperature dependence of the property being measured must occur at a measurable level in absolute signal and sensitivity to temperature change. Second, the materials used in construction of the temperature sensor must be appropriate to the temperature range of use. Materials such as epoxies, solders, and insulators that are very useful at low temperatures can break down at higher temperatures. Exposure to extreme temperatures (either high or low) can induce strains in the sensor due to changes in the packaging materials or in the leads; the resulting strain can cause a shift in the low temperature calibration for that sensor.

Response Time

Thermal response times are determined by physical construction material and mass of the temperature-sensing element. Strain-free mounted sensors tend to have longer thermal response times. Diode sensors that are mounted directly on a sapphire substrate will be in very good thermal contact with the surroundings and hence have short thermal response times.

Accuracy

The term “accuracy” has been almost universally used in literature when presenting specifications, and is often used interchangeably with uncertainty. However, from a strict metrology viewpoint, a distinction does exist between accuracy and uncertainty. Accuracy refers to the closeness of agreement between the measurement and the true value of the measured quantity. Accuracy is a qualitative concept and should not have numbers associated with it. This can be understood since, in practice, one does not have a prior knowledge of the true value of the measured quantity. What one knows is the measured value and its uncertainty, i.e., the range of values that contains the true value of the measured quantity. The uncertainty is a quantitative result and the number typically presented in specifications.

In any proper measurement, an estimate of the measurement uncertainty should be given with the results of the measurement. There are often many sources that contribute uncertainties in a given measurement, and rigorous mathematical methods exist for combining the individual uncertainties into a total uncertainty for the measurement. Temperature sensors, installation, environment, instrumentation, thermal cycling, and thermal EMFs can all contribute to the measurement uncertainty.

A sensor calibration is a method to assign voltage or resistance measurements to a defined temperature scale. The level of confidence at which this can be done is defined by the uncertainty of the calibration.

It is possible to degrade the accuracy specification by as much as one or two orders of magnitude with improper installation and/or poor shielding and measurement techniques.

Precision

The following is taken from Wright State University, Intelligent Sensor Systems.

Page 137: Instrumentation and Control

126

Precision is the capacity of a measuring instrument to give the same reading when repetitively measuring the same quantity under the same prescribed conditions. Precision implies agreement between successive readings, not closeness to the true value. Precision is a necessary but not sufficient condition for accuracy. Two terms closely related to precision are “repeatability,” which is the precision of a set of measurements taken over a short time interval, and “reproducibility,” which is the precision of a set of measurements but taken over a long time interval, or performed by different operators, or with different instruments, or in different laboratories.

Sensitivity

Sensitivity can be presented in a variety of ways. Typically, it is given in terms of the signal sensitivity, which is the change in a measured parameter per change in temperature (Ω/Kelvin (K) or V/K). These sensitivities can be a very strong function of temperature. Diodes have sensitivities that range from 2 millivolt (mV)/K to 180 mV/K. Resistor sensitivities can range from less than 0.001 Ω/K to 1,000,000 Ω/K, depending on the device type and temperature.

Dead-Band

The following is taken from Transtronics, Understanding Dead Band.

Dead-band is most easily understood as a thermostat that keeps a house warm. When it is cold, the heat comes on until the house is warm, at which point the heat goes off. This is the stop point. Then, as time goes by, the house cools off and the furnace needs to restart. This would be the start point.

If the start and stop points have the same value, the furnace would go on and off every 30 seconds, causing wear and tear on the fan and wasting fuel. By spreading the start and stop points, the furnace runs longer. The difference between the start and stop points is the dead-band of the control loop.

Instrument Loop Signal Types

The following is taken from DOE-HDBK-1016/1-93.

Figure 50 shows two examples of simple instrument loops. Figure 50 (A) shows a temperature transmitter (TT) that generates two electrical signals. One signal goes to a board-mounted temperature recorder (TR) for display. The second signal is sent to a proportional-integral-derivative (PID) controller, the output of which is sent to a current-to-pneumatic (I/P) modifier. In the I/P modifier, the electric signal is converted into a pneumatic signal, commonly 3 psi to 15 psi, which in turn operates the valve. The function of the complete loop is to modify flow based on process fluid temperature. Note that there is not enough information to determine how flow and temperature are related and what the setpoint is, but in some instances the setpoint is stated on a piping and instrumentation diagram. Knowing the setpoint and purpose of the system will usually be sufficient to allow the operation of the instrument loop to be determined.

Page 138: Instrumentation and Control

127

Source: DOE-HDBK-1016/1-93

Figure 50. Instrumentation system examples

b. Discuss the following signal types used in instrumentation loops: Pneumatic (3–15 pounds) Electrical (4–20 milliamps) Electrical (1–5 volts)

Pneumatic (3-15 pounds)

The following is taken from DOE-HDBK-1016/1-93.

The pneumatic level transmitter (LT) illustrated in figure 50 (B) senses tank level. The output of the level transmitter is pneumatic and is routed to a board-mounted level modifier (LM). The level modifier conditions the signal and uses the modified signal for two purposes. The modifier drives a board-mounted recorder (LR) for indication, and it sends a modified pneumatic signal to the diaphragm-operated level control valve.

Page 139: Instrumentation and Control

128

Electrical (4–20 milliamps)

The following is taken from All About Circuits, Current Signal Systems.

It is possible, through the use of electronic amplifiers, to design a circuit outputting a constant amount of current rather than a constant amount of voltage. This collection of components is collectively known as a current source. A current source generates as much or as little voltage as needed across its leads to produce a constant amount of current through the electronic amplifier. This is just the opposite of a voltage source (an ideal battery), which will output as much or as little current as demanded by the external circuit in maintaining its output voltage constant.

The most common current signal standard in modern use is the 4 to 20 milliamp (mA) loop, with 4 milliamps representing 0 percent of measurement, 20 milliamps representing 100 percent, 12 milliamps representing 50 percent, and so on. A convenient feature of the 4–20 mA standard is its ease of signal conversion to 1–5 volt indicating instruments.

Electrical (1–5 volts)

The following is taken from All About Circuits, Voltage Signal Systems.

DC voltage can be used as an analog signal to relay information from one location to another. A major disadvantage of voltage signaling is the possibility that the voltage at the indicator (voltmeter) will be less than the voltage at the signal source, due to line resistance and indicator current draw. This drop in voltage along the conductor length constitutes a measurement error from transmitter to indicator.

Despite this inherent disadvantage, voltage signals are still used in many applications because of their extreme design simplicity. One common signal standard is 0–10 volts, meaning that a signal of 0 volts represents 0 percent of measurement, 10 volts represents 100 percent of measurement, 5 volts represents 50 percent of measurement, and so on. A more common voltage range is 1–5 volts, which makes use of the “live zero” concept for circuit fault indication.

13. Instrumentation and control personnel shall demonstrate a working level knowledge of process control systems.

a. Define and discuss the following process control terms: Control system Control system input Control system output Open loop system Closed loop system Feedback Controlled variable Manipulated variable

The following definitions are taken from DOE-HDBK-1013/2-92.

Page 140: Instrumentation and Control

129

Control System

A control system is a system of integrated elements whose function is to maintain a process variable at a desired value or within a desired range of values. The control system monitors a process variable or variables, then causes some action to occur to maintain the desired system parameter. For example in a central heating unit, the system monitors the temperature of the house using a thermostat. When the temperature of the house drops to a preset value, the furnace turns on, providing a heat source. The temperature of the house increases until a switch in the thermostat causes the furnace to turn off. Two terms which help define a control system are “input” and “output.”

Control System Input

Control system input is the stimulus applied to a control system from an external source to produce a specified response from the control system. In the case of the central heating unit, the control system input is the temperature of the house as monitored by the thermostat.

Control System Output

Control system output is the actual response obtained from a control system. In the example above, the temperature dropping to a preset value on the thermostat causes the furnace to turn on, providing heat to raise the temperature of the house.

In the case of nuclear facilities, the input and output are defined by the purpose of the control system. Knowledge of the input and the output of the control system enables the components of the system to be identified. A control system may have more than one input or output.

Control systems are classified by the control action, which is the quantity responsible for activating the control system to produce the output. The two general classifications are open-loop and closed-loop control systems.

Open Loop System

An open-loop control system is one in which the control action is independent of the output. An example of an open-loop control system is a chemical addition pump with a variable speed control (figure 51).

The feed rate of chemicals that maintain proper chemistry of a system is determined by an operator, who is not part of the control system. If the chemistry of the system changes, the pump cannot respond by adjusting its feed rate (speed) without operator action.

Closed Loop System

A closed-loop control system is one in which control action is dependent on the output. Figure 52 is an example of a closed-loop system.

The control system maintains the water level in a storage tank. The system performs this task by continuously sensing the level in the tank and adjusting a supply valve to add more or less water to the tank. The desired level is preset by an operator, who is not part of the system.

Page 141: Instrumentation and Control

130

Source: DOE-HDBK-1013/2-92.

Figure 51. Open-loop control system

Source: DOE-HDBK-1013/2-92

Figure 52. Closed-loop control system

Page 142: Instrumentation and Control

131

Feedback

The following is taken from DOE-HDBK-1013/2-92.

Feedback is information in a closed-loop control system about the condition of a process variable. This variable is compared with a desired condition to produce the proper control action on the process. Information is continually fed back to the control circuit in response to control action. In the previous example, the actual storage tank water level, sensed by the level transmitter, is feedback to the level controller. This feedback is compared with a desired level to produce the required control action that will position the level control as needed to maintain the desired level.

Controlled Variable

According to DOE-HDBK-1013/2-92, a controlled variable is the process variable that is maintained at a specified value or within a specified range. In the previous example, the storage tank level is the controlled variable.

Manipulated Variable

According to DOE-HDBK-1013/2-92, a manipulated variable is the process variable that is acted on by the control system to maintain the controlled variable at the specified value or within the specified range. In the previous example, the flow rate of the water supplied to the tank is the manipulated variable.

b. Given a diagram of a process control system, describe its operation including the function of the following basic components: Controller Controlled device Feedback elements and signal Setpoint/reference signal Actuating signal Manipulated variable

This is a performance-based KSA. The Qualifying Official will evaluate its completion. The following information taken from DOE-HDBK-1013/2-92 may be helpful.

Controller

The control elements are components needed to generate the appropriate control signal applied to the plant. These elements are also called the controller.

Controlled Device

The plant is the system or process through which a particular quantity or condition is controlled. This is also called the controlled device.

Feedback Elements and Signal

The feedback elements are components needed to identify the functional relationship between the feedback signal and the controlled output.

Page 143: Instrumentation and Control

132

Setpoint/Reference Signal

The reference signal is an external signal applied to the summing point of the control system to cause the plant to produce a specified action. This signal represents the desired value of a controlled variable and is also called the setpoint.

Actuating Signal

The actuating signal represents the control action of the control loop and is equal to the algebraic sum of the reference input signal and feedback signal. This is also called the error signal.

Manipulated Variable

The manipulated variable is the variable of the process acted upon to maintain the plant output (controlled variable) at the desired value.

Figure 53 shows a typical application of a block diagram to identify the operation of a temperature control system for lubricating oil. Diagram(A) in figure 53 shows a schematic diagram of the lube oil cooler and its associated temperature control system.

Page 144: Instrumentation and Control

133

Source: DOE-HDBK-1013/2-92

Figure 53. Lube oil cooler temperature control system and equivalent block diagram

Page 145: Instrumentation and Control

134

c. Discuss the factors in a process control system that contribute to process control time lags.

The following is taken from DOE-HDBK-1013/2-92.

Process control time lags are caused by three properties of the process: capacitance, resistance, and transportation time.

Capacitance is the ability of a process to store energy. In figure 53, for example, the walls of the tubes in the lube oil cooler, the cooling water, and the lube oil can store heat energy. This energy-storing property provides the ability to retard change. Even if the cooling water flow rate is increased, it will take a period of time for more energy to be removed from the lube oil to reduce its temperature.

Resistance is that part of the process that opposes the transfer of energy between capacities. In figure 53, the walls of the lube oil cooler oppose the transfer of heat from the lube oil inside the tubes to the cooling water outside the tubes.

Transportation time is time required to carry a change in a process variable from one point to another in the process. If the temperature of the lube oil (figure 53) is lowered by increasing the cooling water flow rate, some time will elapse before the lube oil travels from the lube oil cooler to the temperature transmitter. If the transmitter is moved farther from the lube oil cooler, the transportation time will increase. This time lag is not just a slowing down or retardation of a change. It is an actual time delay during which no change occurs.

d. Discuss stability in a process control system. Include in the discussion an explanation of converging and diverging oscillations and hunting.

The following is taken from DOE-HDBK-1013/2-92.

All control modes can return a process variable to a steady value following a disturbance. This characteristic is called stability.

Stability is the ability of a control loop to return a controlled variable to a steady, non-cyclic value, following a disturbance.

Control loops can be either stable or unstable. Instability is caused by a combination of process time lags, discussed earlier (i.e., capacitance, resistance, and transport time), and inherent time lags within a control system. This results in slow response to changes in the controlled variable.

Consequently, the controlled variable will continuously cycle around the setpoint value.

Oscillation is the term used to describe this cyclic characteristic. There are three types of oscillations that can occur in a control loop: decreasing amplitude, constant amplitude, and increasing amplitude.

Page 146: Instrumentation and Control

135

Decreasing Amplitude. These oscillations decrease in amplitude and eventually stop with a control system that opposes the change in the controlled variable. This is the condition desired in an automatic control system.

Constant Amplitude. Action of the controller sustains oscillations of the controlled variable. The controlled variable never reaches a stable condition; therefore, this condition is not desired.

Increasing Amplitude. The control system not only sustains oscillations but also increases them. The control element reaches its full travel limits and causes the process to go out of control.

e. Discuss the following process control system characteristics and terms: Reset control Rate control Proportional band Offset Span Deviation Cascading

The following descriptions are taken from DOE-HDBK-1013/2-92 unless stated otherwise.

Reset Control

Reset, or integral, control describes a controller in which the output rate of change is dependent on the magnitude of the input. Specifically, a smaller amplitude input causes a slower rate of change of the output. This controller is called an integral, or reset, controller because it approximates the mathematical function of integration.

The major advantage of reset controllers is that they have the unique ability to return the controlled variable back to the exact setpoint following a disturbance.

Disadvantages of the reset control mode are that it responds relatively slowly to an error signal and that it can initially allow a large deviation at the instant the error is produced. This can lead to system instability and cyclic operation. For this reason, the reset control mode is not normally used alone, but is combined with another control mode.

Rate Control (Derivative Control)

A device that produces a derivative signal is called a differentiator. The differentiator provides an output that is directly related to the rate of change of the input and a constant that specifies the function of differentiation. The derivative constant is expressed in units of seconds and defines the differential controller output.

The differentiator acts to transform a changing signal to a constant magnitude signal. As long as the input rate of change is constant, the magnitude of the output is constant. A new input rate of change would give a new output magnitude.

Derivative control cannot be used alone as a control mode. This is because a steady-state input produces a zero output in a differentiator. If the differentiator were used as a controller, the input signal it would receive would be the error signal. A steady-state error signal

Page 147: Instrumentation and Control

136

corresponds to any number of necessary output signals for the positioning of the final control element. Therefore, derivative action is combined with proportional action in a manner such that the proportional section output serves as the derivative section input.

Proportional Band

Proportional band is the change in value of the controlled variable that causes full travel of the final control element. The proportional band of a particular instrument is expressed as a percent of full range. For example, if full range of an instrument is 200 ºF and it takes a 50 ºF change in temperature to cause full valve travel, the percent proportional band is 50 ºF in 200 ºF, or 25 percent. Proportional bands may range from less than 1 percent to well over 200 percent. However, proportional bands over 100 percent cannot cause full valve travel even for full range change of the controlled variable.

Offset

Offset, also called droop, is deviation that remains after a process has stabilized. Offset is an inherent characteristic of the proportional mode of control. In other words, the proportional mode of control will not necessarily return a controlled variable to its setpoint.

Span

Span is the algebraic difference between limits of the pressure range.

Deviation

Deviation is the difference between the setpoint of a process variable and its actual value. This is a key term used when discussing various modes of control.

Cascading

The following is taken from Learncontrol.com, Cascade Control.

Cascade control uses the output of the primary controller to manipulate the setpoint of the secondary controller as if it were the final control element.

Reasons for cascade control: Allow faster secondary controller to handle disturbances in the secondary loop. Allow secondary controller to handle non-linear valve and other final control element

problems. Allow operator to directly control secondary loop during certain modes of operation

(such as startup).

Requirements for cascade control: Secondary loop process dynamics must be at least four times as fast as primary loop

process dynamics. Secondary loop must have influence over the primary loop. Secondary loop must be measured and controllable.

f. Describe the operation of the following types of automatic control systems: Two-position control system Proportional control system Integral control system

Page 148: Instrumentation and Control

137

Proportional plus reset control system Proportional plus reset plus rate control system

The following descriptions are taken from DOE-HDBK-1013/2-92.

Two-Position Control System

A two-position controller is a device that has two operating conditions: completely on or completely off. This device provides an output determined by whether the error signal is above or below the setpoint. The magnitude of the error signal is above or below the setpoint. The magnitude of the error signal past that point is of no concern to the controller.

Proportional Control System

In the proportional control system, there is a continuous linear relation between the value of the controlled variable and the position of the final control element. In other words, the amount of valve movement is proportional to the amount of deviation.

Integral Control System

Integral control describes a controller in which the output rate of change is dependent on the magnitude of the input. Specifically, a smaller amplitude input causes a slower rate of change of the output. This controller is called an integral controller because it approximates the mathematical function of integration. The integral control method is also known as reset control.

Proportional Plus Reset Control System

Proportional plus reset control is actually a combination of proportional and integral controls. Combining the two modes results in gaining the advantages and compensating for the disadvantages of the two individual modes.

The main advantage of the proportional control mode is that an immediate proportional output is produced as soon as an error signal exists at the controller. The proportional controller is considered a fast-acting device. This immediate output change enables the proportional controller to reposition the final control element within a relatively short period of time in response to the error.

The main disadvantage of the proportional control mode is that a residual offset error exists between the measured variable and the setpoint for all but one set of system conditions.

The main advantage of the integral control mode is that the controller output continues to reposition the final control element until the error is reduced to zero. This results in the elimination of the residual offset error allowed by the proportional mode.

The main disadvantage of the integral mode is that the controller output does not immediately direct the final control element to a new position in response to an error signal. The controller output changes at a defined rate of change, and time is needed for the final control element to be repositioned.

The combination of the two control modes is called the proportional plus reset control mode. It combines the immediate output characteristics of a proportional control mode with the zero residual offset characteristics of the integral mode.

Page 149: Instrumentation and Control

138

Proportional Plus Reset Plus Rate Control System

Proportional plus rate describes a control mode in which a derivative section is added to a proportional controller. This derivative section responds to the rate of change of the error signal, not the amplitude. This derivative action responds to the rate of change the instant it starts. This causes the controller output to be initially larger in direct relation with the error signal rate of change. The higher the error signal rate of change, the sooner the final control element is positioned to the desired value. The added derivative action reduces initial overshoot of the measured variable, and therefore aids in stabilizing the process sooner.

This control mode is called proportional plus rate control because the derivative section responds to the rate of change of the error signal.

g. Discuss the function and operation of the following components of a typical control station: Setpoint indicator Setpoint adjustment Deviation indicator Output meter Manual-automatic transfer switch Manual output adjust knob

The following definitions are taken from DOE-HDBK-1013/2-92.

Setpoint Indicator

The setpoint indicator indicates the setpoint (desired value) selected for the controller. The scale may be marked from 0 to 100 percent or it may correspond directly to the controlled variable (e.g., 0–1000 psig or -20 °F to +180 °F).

Setpoint Adjustment

The setpoint adjustment is a thumbwheel type adjustment dial that allows the operator to select the setpoint value. By rotating the thumbwheel, the scale moves under the setpoint index line.

Deviation Indicator

The deviation indicator displays any error (from -10 to +10 percent) between the setpoint value and the actual controlled variable value. With no error, the deviation pointer stays at mid-scale, in line with the setpoint index mark. If the controlled variable is lower than the setpoint, the deviation indicator deflects downward, and if it is higher, the indicator deflects upward.

Output Meter

The output meter indicates controller output signal in percent. This particular controller ranges from 0 to 100 percent current. However, this will correspond to an air signal for pneumatic controllers.

Manual-Automatic Transfer Switch

The manual-automatic transfer switch selects the operating mode of the controller.

Page 150: Instrumentation and Control

139

Manual Output Adjust Knob

The manual output adjust knob varies the controller output signal in the manual mode of operation. The knob is rotated clockwise to increase the signal and counterclockwise to decrease the signal.

h. Describe the operation of a self-balancing control station.

The following is taken from DOE-HDBK-1013/2-92.

The self-balancing control station has several controls and indicators that are the sam as those on a manual automatic control station. However, there are some controls and indicators that differ. In addition, the controller does not require a balancing procedure prior to shifting from one mode (manual or automatic) to another.

Self-balancing describes a control station in which the non-operating mode output signal follows (tracks) the operating mode output signal. When the control station is in the automatic mode, the manual output signal will follow the automatic output signal. Once the controller is transferred to the manual mode, the output signal will remain at its previous value until one of the manual push buttons is depressed. Then, the output will vary. When the controller is in manual mode, the automatic output signal will track the manual output signal. Once the controller is transferred from the manual to automatic mode, the automatic output signal will initially remain at the manual mode value. If a deviation did exist in the manual mode, the automatic output signal would change slowly and return the controlled variable to the setpoint.

i. Describe the operation of the following types of actuators: Pneumatic Hydraulic Solenoid Electric motor

The following descriptions are taken from DOE-HDBK-1013/2-92.

Pneumatic

A pneumatic actuator operates by a combination of force created by air and spring force. The actuator positions a control valve by transmitting its motion through the stem.

A rubber diaphragm separates the actuator housing into two air chambers. The upper chamber receives supply air through an opening in the top of the housing. The bottom chamber contains a spring that forces the diaphragm against mechanical stops in the upper chamber. Finally, a local indicator is connected to the stem to indicate the position of the valve.

The position of the valve is controlled by varying supply air pressure in the upper chamber. This results in a varying force on the top of the diaphragm. Initially, with no supply air, the spring forces the diaphragm upward against the mechanical stops and holds the valve fully open. As supply air pressure is increased from zero, its force on top of the diaphragm begins to overcome the opposing force of the spring. This causes the diaphragm to move downward

Page 151: Instrumentation and Control

140

and the control valve to close. With increasing supply air pressure, the diaphragm will continue to move downward and compress the spring until the control valve is fully closed. Conversely, if supply air pressure is decreased, the spring will begin to force the diaphragm upward and open the control valve. Additionally, if supply pressure is held constant at some value between zero and maximum, the valve will position at an intermediate position. Therefore, the valve can be positioned anywhere between fully open and fully closed in response to changes in supply air pressure.

A positioner is a device that regulates the supply air pressure to a pneumatic actuator. It does this by comparing the actuator’s demanded position with the control valve’s actual position. The demanded position is transmitted by a pneumatic or electrical control signal from a controller to the positioner.

The controller generates an output signal that represents the demanded position. This signal is sent to the positioner. Externally, the positioner consists of an input connection for the control signal, a supply air input connection, a supply air output connection, a supply air vent connection, and a feedback linkage. Internally, it contains an intricate network of electrical transducers, air lines, valves, linkages, and necessary adjustments. Other positioners may also provide controls for local valve positioning and gauges to indicate supply air pressure and control air pressure (for pneumatic controllers).

Hydraulic

Pneumatic actuators are normally used to control processes requiring quick and accurate response, as they do not require a large amount of motive force. However, when a large amount of force is required to operate a valve (for example, the main steam system valves), hydraulic actuators are normally used. Although hydraulic actuators come in many designs, piston types are most common.

A typical piston-type hydraulic actuator consists of a cylinder, piston, spring, hydraulic supply and return line, and stem. The piston slides vertically inside the cylinder and separates the cylinder into two chambers. The upper chamber contains the spring and the lower chamber contains hydraulic oil.

The hydraulic supply and return line is connected to the lower chamber and allows hydraulic fluid to flow to and from the lower chamber of the actuator. The stem transmits the motion of the piston to a valve. Initially, with no hydraulic fluid pressure, the spring force holds the valve in the closed position. As fluid enters the lower chamber, pressure in the chamber increases. This pressure results in a force on the bottom of the piston opposite to the force caused by the spring. When the hydraulic force is greater than the spring force, the piston begins to move upward, the spring compresses, and the valve begins to open. As the hydraulic pressure increases, the valve continues to open. Conversely, as hydraulic oil is drained from the cylinder, the hydraulic force becomes less than the spring force, the piston moves downward, and the valve closes. By regulating the amount of oil supplied or drained from the actuator, the valve can be positioned between fully open and fully closed.

Solenoid

An electric solenoid actuator consists of a coil, armature, spring, and stem. The coil is connected to an external current supply. The spring rests on the armature to force it

Page 152: Instrumentation and Control

141

downward. The armature moves vertically inside the coil and transmits its motion through the stem to the valve. When current flows through the coil, a magnetic field forms around the coil. The magnetic field attracts the armature toward the center of the coil. As the armature moves upward, the spring collapses and the valve opens. When the circuit is opened and current stops flowing to the coil, the magnetic field collapses. This allows the spring to expand and shut the valve.

A major advantage of solenoid actuators is their quick operation. Also, they are much easier to install than pneumatic or hydraulic actuators. However, solenoid actuators have two disadvantages. First, they have only two positions: fully open and fully closed. Second, they do not produce much force, so they usually only operate relatively small valves.

Electric Motor

Electric motor actuators vary widely in their design and applications. Some electric motor actuators are designed to operate in only two positions (fully open or fully closed). Other electric motors can be positioned between the two positions. An electric motor actuator’s major parts include an electric motor, clutch and gear box assembly, manual handwheel, and stem connected to a valve.

The motor moves the stem through the gear assembly. The motor reverses its rotation to either open or close the valve. The clutch and clutch lever disconnect the electric motor from the gear assembly and allow the valve to be operated manually with the handwheel. Most electric motor actuators are equipped with limit switches, torque limiters, or both. Limit switches de-energize the electric motor when the valve has reached a specific position. Torque limiters de-energize the electric motor when the amount of turning force has reached a specified value. The turning force normally is greatest when the valve reaches the fully open or fully closed position. This feature can also prevent damage to the actuator or valve if the valve binds in an intermediate position.

j. Discuss controller tuning.

The following is taken from the University of Michigan, Engineering, PID Tuning Classical.

Types of controller tuning methods include the trial and error method and process reaction curve methods. The most common classical controller tuning methods are the Ziegler-Nichols and Cohen-Coon methods. These methods are often used when the mathematical model of the system is not available. The Ziegler-Nichols method can be used for both closed and open loop systems, while Cohen-Coon is typically used for open loop systems. A closed-loop control system is a system that uses feedback control. In an open-loop system, the output is not compared to the input.

Ziegler-Nichols Method

The Ziegler-Nichols closed-loop tuning method allows you to use the ultimate gain value, Ku, and the ultimate period of oscillation, Pu, to calculate Kc . It is a simple method of tuning PID controllers and can be refined to give better approximations of the controller. You can obtain the controller constants Kc, Ti , and Td in a system with feedback. The Ziegler-Nichols closed-loop tuning method is limited to tuning processes that cannot run in an open-loop environment.

Page 153: Instrumentation and Control

142

Determining the ultimate gain value, Ku is accomplished by finding the value of the proportional-only gain that causes the control loop to oscillate indefinitely at steady state. This means that the gains from the I and D controller are set to zero so that the influence of P can be determined. It tests the robustness of the Kc value so that it is optimized for the controller. Another important value associated with this proportional-only control tuning method is the ultimate period (Pu). The ultimate period is the time required to complete one full oscillation while the system is at steady state. These two parameters, Ku and Pu, are used to find the loop-tuning constants of the controller. To find the values of these parameters, and to calculate the tuning constants, use the following procedure:

Closed Loop (Feedback Loop) 1. Remove integral and derivative action. Set integral time (Ti) to 999 or its largest value

and set the derivative controller (Td) to zero. 2. Create a small disturbance in the loop by changing the set point. Adjust the

proportional, increasing and/or decreasing, the gain until the oscillations have constant amplitude.

3. Record the gain value (Ku) and period of oscillation (Pu).

Source: University of Michigan, Engineering, PID Tuning Classical

Figure 54. System tuned using the Ziegler-Nichols closed-loop tuning method

4. Plug these values into the Ziegler-Nichols closed-loop equations and determine the necessary settings for the controller.

Cohen-Coon Method

The Cohen-Coon method of controller tuning corrects the slow, steady-state response given by the Ziegler-Nichols method when there is a large dead time (process delay) relative to the open loop time constant; a large process delay is necessary to make this method practical because otherwise unreasonably large controller gains will be predicted. This method is only

Page 154: Instrumentation and Control

143

used for first-order models with time delay, due to the fact that the controller does not instantaneously respond to the disturbance (the step disturbance is progressive instead of instantaneous).

The Cohen-Coon method is classified as an off-line method for tuning, meaning that a step change can be introduced to the input once it is at steady-state. Then the output can be measured based on the time constant and the time delay and this response can be used to evaluate the initial control parameters.

There exists a pre-determined list of recommended settings to get minimum offset and a desired standard decay ratio of 1/4, meaning that the second oscillation will have 1/4 the amplitude of the first.

14. Instrumentation and control personnel shall demonstrate a working level knowledge of the characteristics and applications of pneumatic/hydraulic components used in instrumentation and control systems.

[Note: The standard has two competency statements numbered 13.]

a. Describe the operation of a basic pneumatic transmitter.

The following is taken from the International Society of Automation, Sensors.

A pneumatic transmitter converts the value of the measurement into an air pressure signal that is sent through tubing to the controller. The connecting tubing carries the transmitted pressure to a receiver, which is a component located in the controller housing. The tubing is almost always one-quarter inch in outside diameter and may be copper, aluminum, or plastic. The receiver is simply a pressure gauge element, and the transmitted air pressure is converted into the movement of a bellows or diaphragm (that is, pressure is transduced into a position or force that is used by the controller).

b. Given a diagram of a typical pneumatic control circuit, describe the operation of the control system and explain the function of its components.

This is a performance-based KSA. The Qualifying Official will evaluate its completion.

c. Explain the term “live zero” as it applies to pneumatic control circuits.

The following is taken from All About Circuits, Analog and Digital Signals.

Live zero is a standard way of scaling a signal so that an indication of 0 percent can be discriminated from the status of a dead system. Take the pneumatic signal system as an example. If the signal pressure range for transmitter and indicator was designed to be 0 to 12 psi, with 0 psi representing 0 percent of process measurement and 12 psi representing 100 percent, a received signal of 0 percent could be a legitimate reading of 0 percent measurement or it could mean that the system was malfunctioning (an air compressor stopped, tubing is broken, a transmitter is malfunctioning, etc.). With the 0 percent point represented by 0 psi, there would be no easy way to distinguish one from the other.

Page 155: Instrumentation and Control

144

If, however, the instruments were scaled to use a scale of 3 to 15 psi, with 3 psi representing 0 percent and 15 psi representing 100 percent, any kind of a malfunction resulting in zero air pressure at the indicator would generate a reading of -25 percent (0 psi), which is clearly a faulty value. The person looking at the indicator would then be able to immediately tell that something was wrong.

d. Discuss the function and application of the following types of signal converters: I/P converter P/I converter

I/P Converter

The following is taken from the University of Washington, Baneyx, chapter 2, Contorl Loop Hardware.

The I/P converter uses a source of instrument air to change the air pressure (3-15 psig) applied to the control valve corresponding to the value of the analog signal. That is, if I is the value of the analog signal and P is the instrument air pressure delivered to the control valve,

16

4I =

12

3P

since a 4 to 20 mA range in the analog signal corresponds to a 3 to 15 psig range in the instrument air pressure and the zero of the analog signal is 4 mA and the zero of the pneumatic signal is 3 psig. Changes of instrument air pressure to the control valve cause changes in the stem position of the control valve, which result in changes in the flow rate to the process. These changes in the flow rate to the process cause changes in the temperature of the mixer, which are measured by the sensor, completing the feedback control loop. The final control element consists of the I/P converter, the instrument air system, and the control valve.

P/I Converter

The following is taken from Samson, Electropneumatic Converters for Pneumatic Signals.

P/I converters serve as interface between pneumatic and electric measuring and control units, being used for example to connect pneumatic transmitters to electric controllers, computers and process control systems. The input variable is a pneumatic signal and the output variable an electric DC current signal or DC voltage signal.

e. Describe the operation of a pneumatic actuator used in the following applications: Air-operated open/close valve Air-operated throttle valve Air-operated damper

The following is taken from DOE-HDBK-1013/2-92.

Page 156: Instrumentation and Control

145

A simplified diagram of a pneumatic actuator is shown in figure 55. The actuator operates by a combination of force created by air and spring force. The actuator positions a control valve by transmitting its motion through the stem.

A rubber diaphragm separates the actuator housing into two air chambers. The upper chamber receives supply air through an opening in the top of the housing.

Source: DOE-HDBK-1013/2-92

Figure 55. Pneumatic actuator: air-to-close, spring-to-open

The bottom chamber contains a spring that forces the diaphragm against mechanical stops in the upper chamber. Finally, a local indicator is connected to the stem to indicate the position of the valve.

The position of the valve is controlled by varying supply air pressure in the upper chamber. This results in a varying force on the top of the diaphragm. Initially, with no supply air, the spring forces the diaphragm upward against the mechanical stops and holds the valve fully open. As supply air pressure is increased from zero, its force on top of the diaphragm begins

Page 157: Instrumentation and Control

146

to overcome the opposing force of the spring. This causes the diaphragm to move downward and the control valve to close. With increasing supply air pressure, the diaphragm will continue to move downward and compress the spring until the control valve is fully closed. Conversely, if supply air pressure is decreased, the spring will begin to force the diaphragm upward and open the control valve. Additionally, if supply pressure is held constant at some value between zero and maximum, the valve will position at an intermediate position. Therefore, the valve can be positioned anywhere between fully open and fully closed in response to changes in supply air pressure.

A positioner is a device that regulates the supply air pressure to a pneumatic actuator. It does this by comparing the actuator’s demanded position with the control valve’s actual position. The demanded position is transmitted by a pneumatic or electrical control signal from a controller to the positioner. The pneumatic actuator in figure 55 is shown, in figure 56, with a controller and positioner added.

The controller generates an output signal that represents the demanded position. This signal is sent to the positioner. Externally, the positioner consists of an input connection for the control signal, a supply air input connection, a supply air output connection, a supply air vent connection, and a feedback linkage. Internally, it contains an intricate network of electrical transducers, air lines, valves, linkages, and necessary adjustments. Other positioners may also provide controls for local valve positioning and gauges to indicate supply air pressure and control air pressure (for pneumatic controllers).

Page 158: Instrumentation and Control

147

Source: DOE-HDBK-1013/2-92

Figure 56. Pneumatic actuator with controller and positioner

In figure 56, the controller responds to a deviation of a controlled variable from setpoint and varies the control output signal accordingly to correct the deviation. The control output signal is sent to the positioner, which responds by increasing or decreasing the supply air to the actuator. Positioning of the actuator and control valve is fed back to the positioner through the feedback linkage. When the valve has reached the position demanded by the controller, the positioner stops the change in supply air pressure and holds the valve at the new position. This, in turn, corrects the controlled variable’s deviation from setpoint.

For example, as the control signal increases, a valve inside the positioner admits more supply air to the actuator. As a result, the control valve moves downward. The linkage transmits the valve position information back to the positioner. This forms a small internal feedback loop for the actuator. When the valve reaches the position that correlates to the control signal, the linkage stops supply air flow to the actuator. This causes the actuator to stop. On the other hand, if the control signal decreases, another valve inside the positioner opens and allows the supply air pressure to decrease by venting the supply air. This causes the valve to move upward and open. When the valve has opened to the proper position, the positioner stops venting air from the actuator and stops movement of the control valve.

Page 159: Instrumentation and Control

148

An important safety feature is provided by the spring in an actuator. It can be designed to position a control valve in a safe position if a loss of supply air occurs. On a loss of supply air, the actuator in figure 56 will fail open. This type of arrangement is referred to as air-to-close, spring-to-open or simply fail-open. Some valves fail in the closed position. This type of actuator is referred to as air-to-open, spring-to-close or fail-closed. This fail-safe concept is an important consideration in nuclear facility design.

f. Describe the operation of an electrohydraulic control system.

The following is taken from Freepatentsonline, Electrohydraulic Control System.

The electrohydraulic control system includes a way valve of the type provided with a housing, fluid inflow and consumer ports in the housing, and at least one valve member movable in the valve housing for establishing connections between ports. A positioning arrangement receives an electrical input signal and positions the valve member in dependence thereon. A desired-value selector generates a desired-value signal indicative of the desired volumetric flow rate for the flow of fluid into the fluid inflow port and out one of the consumer ports. Transducers sense the position of the valve member and the pressures at the inflow and consumer ports and generate corresponding electrical feedback signals. A circuit arrangement connected to the desired-value selector and to the transducers compensates for the effect upon such volumetric flow rate of variations in the hydraulic loading of consumers supplied via the way valve by furnishing the aforementioned electrical input signal to the positioning arrangement as a predetermined function of both the desired-value and feedback signals.

15. Instrumentation and control personnel shall demonstrate a working level knowledge of the characteristics and applications of electronic components used in instrumentation and control systems.

a. Describe the operation and application of the following components found in instrumentation and control circuits: Summer Root extractor Gate Integrator Multiplier Proportional device

Summer

According to All About Circuits, a summer circuit is one that sums, or adds, multiple analog voltage signals together. There are two basic varieties of operational amplifier summer circuits: noninverting and inverting.

Root Extractor

According to DOE-HDBK-1013/1-92, the root extractor is used to electronically calculate the square root of the DP and provide an output proportional to system flow. The constants are determined by selection of the appropriate electronic components. The extractor output is

Page 160: Instrumentation and Control

149

amplified and sent to an indicator. The indicator provides either a local or a remote indication of system flow.

Gate

According to DOE-HDBK-1016/2-93, gates depict the operation/start/stop circuits of components and systems.

Integrator

The following is taken from DOE-HDBK-1013/2-92.

A device that performs the mathematical function of integration is called an integrator. The mathematical result of integration is called the integral. The integrator provides a linear output with a rate of change that is directly related to the amplitude of the step change input and a constant that specifies the function of integration.

The integrator acts to transform the step change into a gradually changing signal. The input amplitude is repeated in the output every 5 seconds. As long as the input remains constant at 10 percent, the output will continue to ramp up every 5 seconds until the integrator saturates.

Multiplier

The following is taken from Research Media and Cybernetics, Voltage Multipliers.

One of the cheapest and popular ways of generating high voltages at relatively low currents is the classic multistage diode/capacitor voltage multiplier, known as a Cockcroft Walton multiplier.

Unlike transformers, this method eliminates the requirement for the heavy core and the bulk of insulation/potting required. By using only capacitors and diodes, these voltage multipliers can step up relatively low voltages to extremely high values, while at the same time being far lighter and cheaper than transformers. The biggest advantage of such a circuit is that the voltage across each stage of this cascade is only equal to twice the peak input voltage, so it has the advantage of requiring relatively low-cost components and being easy to insulate.

Proportional Device

According to National Instruments Developer Zone, a proportional device is a system that corrects the deviation of a process from the set level back toward the setpoint. The correction is proportional to the amount of error.

b. Discuss the uses and applications for microprocessors in an instrumentation and control system.

The following information is taken from How Microprocessors Work by Marshall Brain.

A microprocessor executes a collection of machine instructions that tell the processor what to do. Based on the instructions, a microprocessor does three basic things:

1. Using its arithmetic/logic unit, a microprocessor can perform mathematical operations like addition, subtraction, multiplication, and division. Modern microprocessors

Page 161: Instrumentation and Control

150

contain complete floating-point processors that can perform extremely sophisticated operations on large floating-point numbers.

2. A microprocessor can move data from one memory location to another. 3. A microprocessor can make decisions and jump to a new set of instructions based on

those decisions.

c. Discuss each of the following terms, including their application to instrumentation and control systems. Computer memory (random access memory [RAM]/read-only memory [ROM]) Discrete logic Discrete semiconductors Analog integrated circuits Comparitor circuits Combinatorial logics Signal conditioning

Computer Memory

The following is taken from Computer Hope.com.

Random access memory (RAM), also known as main memory or system memory, is a term commonly used to describe the memory within a computer. Unlike read-only memory (ROM), RAM requires power; if power is lost, all data is also lost.

ROM is a type of memory that is capable of holding data and being read from; however, it is not capable of being written to or having its data modified. Unlike RAM, ROM is capable of keeping its contents whether if it has power or not.

Discrete Logic

According to PC Magazine, Encyclopedia, discrete logic is an individual gate on a single chip. Although up to hundreds of thousands of gates are routinely placed on a single chip, discrete logic chips that contain only one or two gates are also manufactured. These chips are used as glue chips between application-specific integrated circuits and other integrated circuits typically to reshape and transfer signals.

Discrete Semiconductors

The following is taken from All About Circuits, volume VI, Experiments, Discrete Semiconductor Circuits.

A semiconductor device is one made of silicon or any number of other specially prepared materials designed to exploit the unique properties of electrons in a crystal lattice, where electrons are not as free to move as in a conductor, but are far more mobile than in an insulator. A discrete device is one contained in its own package, not built on a common semiconductor substrate with other components, as is the case with integrated circuits. Thus, “discrete semiconductor circuits” are circuits built out of individual semiconductor components, connected together on some kind of circuit board or terminal strip.

The following is taken from Industrial Equipment Resource, Semiconductors.

Page 162: Instrumentation and Control

151

Semiconductors are electronic devices that under specific conditions of temperature and voltage, operate as insulators or conductors. They are also called solid-state devices since they do not use vacuum tubes to conduct electricity. These items use electronic conduction in the solid state as opposed to the gaseous state or thermionic emission in a high vacuum. Discrete semiconductor units are made as single devices.

In very low temperature the semiconductor will act as an insulator, and it will act as a conductor at room temperature; however it has much lower conductivity than a conductor at absolute zero, the uppermost filled electron energy band is completely filled in a semiconductor and only partially filled in a conductor.

The difference between a semiconductor and an insulator is a little more arbitrary. A semiconductor has a band gap that is small enough so that its conduction band is appreciably thermally populated with electrons at room temperature, whereas an insulator has a band gap that is too wide for there to be appreciable thermal electrons in its conduction band at the same temperature.

Semiconductors are widely used in modern electronics and are used in one form or another in white goods, electronic instruments, automobiles, space applications, industrial circuits, audio equipment, etc. Common trade names are transistors, diodes, thyristors, microprocessors, diodes and zener diodes.

Semi-conducting materials are silicon, silicon carbide, boron nitride, gallium arsenide, aluminum arsenide, silicon germanium, aluminum gallium arsenide, diamond, gallium nitride, germanium and indium phosphide.

These devices are made of layers that allow them to conduct electricity. They operate on the principle of electrons and holes. Electrons tend to move towards the hole layer, and this makes them conductive. Semiconductors are very useful in electronics because their conductivity can be altered when small amounts of impurities (dopants) are added. This is called doping. When you heavily dope a semiconductor you can actually increase its conductivity by a factor greater than a billion. In modern integrated circuits heavily doped polycrystalline silicon is sometimes used as a replacement for metals.

Analog Integrated Circuits

The following is taken from All About Circuits, Analog Integrated Circuits.

Analog circuits are circuits dealing with signals free to vary from zero to full power supply voltage. This stands in contrast to digital circuits, which almost exclusively employ all-or-nothing signals: voltages restricted to values of zero and full supply voltage, with no valid state in between those extreme limits. Analog circuits are often referred to as linear circuits to emphasize the valid continuity of signal range forbidden in digital circuits.

Analog integrated circuits are actually networks of interconnected components manufactured on a single wafer of semiconducting material. Most integrated circuits provide the same functionality as discrete semiconductor circuits at higher levels of reliability and at a fraction of the cost. Usually, discrete-component circuit construction is favored only when power dissipation levels are too high for integrated circuits to handle.

Page 163: Instrumentation and Control

152

Comparator Circuits

The following is taken from All About Circuits, Voltage Comparator.

A comparator circuit compares two voltage signals and determines which one is greater. The result of this comparison is indicated by the output voltage: if the op-amp’s output is saturated in the positive direction, the noninverting input (+) is a greater, or more positive, voltage than the inverting input (-), all voltages measured with respect to ground. If the op-amp’s voltage is near the negative supply voltage, it means the inverting input (-) has a greater voltage applied to it than the noninverting input (+).

Combinatorial Logics

The following is taken from PC Magazine, Encyclopedia, Combinational Logic.

Combinational logic also known as combinatorial logic, refers to a digital logic function made of primitive logic gates (AND, OR, NOT, etc.) in which all outputs of the function are directly related to the current combination of values on its inputs. Any changes to the signals being applied to the inputs will immediately propagate through the gates until their effects appear at the outputs.

Signal Conditioning

The following is taken from National Instruments, Signal Conditioning Fundamentals for Computer-Based Data Acquisition Systems.

Regardless of the types of sensors or transducers you are using, the proper signal conditioning equipment can improve the quality and performance of your system. Signal conditioning functions are useful for all types of signals, including amplification, filtering, and isolation.

Amplification

Because real-world signals are often very small in magnitude, signal conditioning can improve the accuracy of your data. Amplifiers boost the level of the input signal to better match the range of the analog-to-digital converter (ADC), thus increasing the resolution and sensitivity of the measurement. While many data acquisition (DAQ) devices include onboard amplifiers for this reason, many transducers, such a thermocouples, require additional amplification.

In addition, using external signal conditioners located closer to the signal source, or transducer, improves the signal-to-noise ratio of the measurement by boosting the signal level before it is affected by environmental noise.

Attenuation

Attenuation is the opposite of amplification. It is necessary when the voltages to be digitized are beyond the input range of the digitizer. This form of signal conditioning diminishes the amplitude of the input signal so that the conditioned signal is within range of the ADC. Attenuation is necessary for measuring high voltages.

Page 164: Instrumentation and Control

153

Filtering

Additionally, signal conditioners can include filters to reject unwanted noise within a certain frequency range. Almost all DAQ applications are subject to some level of 50 or 60 Hz noise picked up from power lines or machinery. Therefore, most conditioners include low pass filters designed specifically to provide maximum rejection of 50 to 60 Hz noise.

Another common use of filters is to prevent signal aliasing—a phenomenon that arises when a signal is undersampled (sampled too slowly). The Nyquist theorem states that when you sample an analog signal, any signal components at frequencies greater than one-half the sampling frequency appear in the sampled data as a lower frequency signal. You can avoid this signal distortion only by removing any signal components above one-half the sampling frequency with low pass filters before the signal is sampled.

Isolation

Improper grounding of the system is one of the most common causes for measurement problems, including noise and damaged measurement devices. Signal conditioners with isolation can prevent most of these problems. Such devices pass the signal from its source to the measurement device without a physical connection by using transformer, optical, or capacitive coupling techniques. Besides breaking ground loops, isolation blocks high-voltage surges and rejects high common-mode voltage and thus protects both the operators and expensive measurement equipment.

Multiplexing

Typically, the digitizer is the most expensive part of a data acquisition system. By multiplexing, you can sequentially route a number of signals into a single digitizer, thus achieving a cost-effective way to greatly expand the signal count of your system. Multiplexing is necessary for any high-channel-count application.

Simultaneous Sampling

When it is critical to measure two or more signals at the same instant in time, simultaneous sampling is required. Front-end signal conditioning can provide a much more cost-effective simultaneous sampling solution than purchasing a digitizer for each channel. Typical applications that might require simultaneous sampling include vibration measurements and phase difference measurements.

Digital Signal Conditioning

Digital signals can also require signal conditioning peripherals. Typically, you should not connect digital signals used in research and industrial environments directly to a DAQ board without some type of isolation because of the possibility of large voltage spikes or large common voltages. Some signal conditioning modules and boards optically isolate the digital input/output signals to remove these spurious signals. Digital input/output signals can control electromechanical or solid-state relays to switch loads such as solenoids, lights, and motors. You can also use solid-state relays to sense high-voltage field signals and convert them to digital signals.

Page 165: Instrumentation and Control

154

16. Instrumentation and control personnel shall demonstrate a working level knowledge of systems integration to achieve performance, effectiveness, and cost objectives.

a. Given a design package for an instrumentation and control system, evaluate its application within an integrated system for the following criteria: Instruments and controls meet the general human factors criteria and

considerations for safe and efficient system operation. Instruments and controls perform within the parameters required for safe and

efficient system operation. Instrument and control response times are adequate for safe and efficient

system operation. Instruments and controls are physically configured for safe and efficient

maintenance. Instruments and controls meet the general design criteria for the system in

which they are to be used.

b. Given a proposed application of an instrumentation and control system to an integrated system, evaluate the performance of the integrated system to determine that instrument and control performance requirements will be met.

c. Discuss the problems presented to instrumentation and control systems under various system applications.

Elements a through c are performance based. The Qualifying Official will evaluate their completion.

17. Instrumentation and control personnel shall demonstrate a working level knowledge of basic thermodynamic concepts and theories used in the design and operation of process control systems.

a. Define the following terms: Specific volume Density Specific gravity Mass Weight

The following definitions are taken from DOE-HDBK-1012/1-92.

Specific Volume

The specific volume of a substance is the total volume of that substance divided by the total mass of that substance (volume per unit mass). It has units of cubic feet per pound-mass (ft3/lbm).

Density

The density of a substance is the total mass of that substance divided by the total volume occupied by that substance (mass per unit volume). It has units of pound-mass per cubic feet (lbm/ft3). The density of a substance is the reciprocal of its specific volume.

Page 166: Instrumentation and Control

155

Specific Gravity

Specific gravity is a measure of the relative density of a substance as compared to the density of water at a standard temperature. Physicists use 39.2 °F (4 °C) as the standard, but engineers ordinarily use 60 °F. In SI units, the density of water is 1.00 g/cm3 at the standard temperature. Therefore, the specific gravity (which is dimensionless) for a liquid has the same numerical value as its density in units of g/cm3. Since the density of a fluid varies with temperature, specific gravities must be determined and specified at particular temperatures.

Mass

The mass of a body is the measure of the amount of material present in that body.

Weight

The weight of a body is the force exerted by that body when its mass is accelerated in a gravitational field.

b. Describe the thermodynamic properties of temperature and pressure.

The following is taken from DOE-HDBK-1012/1-92.

Temperature is a measure of the molecular activity of a substance. The greater the movement of molecules, the higher the temperature will be. It is a relative measure of how hot or cold a substance is and can be used to predict the direction of heat transfer.

Pressure is a measure of the force exerted per unit area on the boundaries of a substance (or system). It is caused by the collisions of the molecules of the substance with the boundaries of the system. As molecules hit the walls, they exert forces that try to push the walls outward. The forces resulting from all of these collisions cause the pressure exerted by a system on its surroundings. Pressure is frequently measured in units of pound-force per square inch (lbf/in2) (psi).

c. Compare and contrast the Fahrenheit, Celsius, Kelvin, and Rankine temperature scales, and discuss the concept of “absolute zero.”

The following is taken from DOE-HDBK-1012/1-92.

The two temperature scales normally employed for measurement purposes are the Fahrenheit (F) and Celsius (C) scales. These scales are based on a specification of the number of increments between the freezing point and the boiling point of water at standard atmospheric pressure. The Celsius scale has 100 units between these points, and the Fahrenheit scale has 180 units. The zero points on the scales are arbitrary.

The freezing point of water was selected as the zero point of the Celsius scale. The coldest temperature achievable with a mixture of ice and salt water was selected as the zero point of the Fahrenheit scale. The temperature at which water boils was set at 100 on the Celsius scale and 212 on the Fahrenheit scale. The relationship between the scales is represented by the following equations:

ºF = 32.0 + (9/5) ºC

Page 167: Instrumentation and Control

156

ºC = º (F - 32.0)(5/9)

It is necessary to define an absolute temperature scale having only positive values. The absolute temperature scale that corresponds to the Celsius scale is called the Kelvin scale, and the absolute scale that corresponds to the Fahrenheit scale is called the Rankine scale. The zero points on both absolute scales represent the same physical state. This state is where there is no molecular motion of individual atoms. The relationships between the absolute and relative temperature scales are shown in the following equations:

ºR = ºF + 460

K = ºC + 273

d. Describe the relationship between absolute pressure, gauge pressure, and vacuum.

The following is taken from DOE-HDBK-1012/1-92.

When pressure is measured relative to a perfect vacuum, it is called absolute pressure (psia), and when measured relative to atmospheric pressure (14.7 psi), it is called gauge pressure. The latter pressure scale was developed because almost all pressure gauges register zero when open to the atmosphere. Therefore, pressure gauges measure the difference between the pressure of the fluid to which they are connected and that of the surrounding air.

If the pressure is below that of the atmosphere, it is designated as a vacuum. A perfect vacuum would correspond to absolute zero pressure. All values of absolute pressure are positive, because a negative value would indicate tension, which is considered impossible in any fluid. Gauge pressures are positive if they are above atmospheric pressure and negative if they are below atmospheric pressure.

e. Define the following and describe their relationship: Energy Potential energy Kinetic energy Work Heat

The following definitions are taken from DOE-HDBK-1012/1-92.

Energy

Energy is defined as the capacity of a system to perform work or produce heat.

Potential Energy

Potential energy (PE) is defined as the energy of position. Using English system units, it is defined by the following equation:

PE = mgz/gc

where

Page 168: Instrumentation and Control

157

PE = potential energy (ft-lbf) m = mass (lbm) z = height above some reference level (ft) g = acceleration due to gravity (ft/sec2) gc = gravitational constant = 32.17 ft-lbm/lbf-sec2

In most practical engineering calculations, the acceleration due to gravity (g) is numerically equal to the gravitational constant (gc); thus, the potential energy in foot-pounds-force is numerically equal to the product of the mass (m) in pounds-mass times the height (z) in feet above some reference level.

Kinetic Energy

Kinetic energy (KE) is the energy of motion. Using English system units, it is defined by the following equation:

KE mv2/2gc

where KE = kinetic energy (ft-lbf) m = mass (lbm) v = velocity (ft/sec) gc = gravitational constant = 32.17 ft-lbm/lbf-sec2

Work

Work is a form of energy, but it is energy in transit. Work is not a property of a system. Work is a process done by or on a system, but a system contains no work.

This distinction between the forms of energy that are properties of a system and the forms of energy that are transferred to and from a system is important to the understanding of energy transfer systems.

Work is defined for mechanical systems as the action of a force on an object through a distance. It equals the product of the force (F) times the displacement (d).

In dealing with work in relation to energy transfer systems, it is important to distinguish between work done by the system on its surroundings and work done on the system by its surroundings. Work is done by the system when it is used to turn a turbine and thereby generate electricity in a turbine-generator. Work is done on the system when a pump is used to move the working fluid from one location to another. A positive value for work indicates that work is done by the system on its surroundings; a negative value indicates that work is done on the system by its surroundings.

Heat

Heat, like work, is energy in transit. The transfer of energy as heat, however, occurs at the molecular level as a result of a temperature difference. The symbol Q is used to denote heat. In engineering applications, the unit of heat is the British thermal unit (Btu). Specifically, this is called the 60 degree Btu because it is measured by a 1 degree temperature change, from 59.5 °F to 60.5 °F.

Page 169: Instrumentation and Control

158

As with work, the amount of heat transferred depends upon the path and not simply on the initial and final conditions of the system. Also, as with work, it is important to distinguish between heat added to a system from its surroundings and heat removed from a system to its surroundings. A positive value for heat indicates that heat is added to the system by its surroundings. This is in contrast to work that is positive when energy is transferred from the system and negative when transferred to the system. The symbol q is sometimes used to indicate the heat added to or removed from a system per unit mass. It equals the total heat (Q) added or removed divided by the mass (m).

f. Describe the following types of thermodynamic systems: Isolated system Open system Closed system

The following is taken from DOE-HDBK-1012/1-92.

Isolated System

An isolated system is one that is not influenced in any way by the surroundings. This means that no energy in the form of heat or work may cross the boundary of the system. In addition, no mass may cross the boundary of the system.

Open System

An open system is one that may have a transfer of both mass and energy with its surroundings.

Closed System

A closed system has no transfer of mass with its surroundings, but may have a transfer of energy (either heat or work) with its surroundings.

g. Discuss the application of Bernoulli’s principle to a process control system.

The following is taken from DOE-HDBK-1012/3-92.

Bernoulli’s equation results from the application of the general energy equation and the first law of thermodynamics to a steady flow system in which no work is done on or by the fluid, no heat is transferred to or from the fluid, and no change occurs in the internal energy (i.e., there is no temperature change) of the fluid.

Many plant components, such as a venturi, may be analyzed using Bernoulli’s equation and the continuity equation. A venturi is a flow-measuring device that consists of a gradual contraction followed by a gradual expansion. An example of a venturi is shown in figure 57. By measuring the differential pressure between the inlet of the venturi (point 1) and the throat of the venture (point 2), the flow velocity and mass flow rate can be determined based on Bernoulli’s equation.

Page 170: Instrumentation and Control

159

Source: DOE-HDBK-1012/3-92

Figure 57. Venturi tube

Bernoulli’s equation states that the total head of the flow must be constant. Since the elevation does not change significantly, if at all, between points 1 and 2, the elevation head at the two points will be essentially the same and will cancel out of the equation. So Bernoulli’s equation simplifies to the following equation for a venturi.

g

gVP

g2

v

g

gVP

g2

v c22

22c

11

21

Applying the continuity equation to points 1 and 2 allows us to express the flow velocity at point 1 as a function of the flow velocity at point 2 and the ratio of the two flow areas.

ρ1A1v1 = ρ2A2v2

v1 = 11

222

AP

vAP

v1 = v2

1

2

A

A

Using algebra to rearrange the first equation and substituting the above result for v1 allows us to solve for v2.

g

gvPP

g2c

21

2

1

2

2 vv

2

1

22

2

2 A

Avv 21 PP 2vgc

Page 171: Instrumentation and Control

160

2

1

22

2

2 A

A1 vv PP 21 2vgc

v2

2 =

2

1

2

c21

A

A-1

2vgPP

2

1

2

c212

A

A1

vg2PPv

2

1

2

c212

A

A1

vg2PPv

Therefore, the flow velocity at the throat of the venturi and the volumetric flow rate are directly proportional to the square root of the differential pressure.

The pressures at the upstream section and throat are actual pressures, and velocities from Bernoulli’s equation without a loss term are theoretical velocities. When losses are considered in the energy equation, the velocities are actual velocities. First, with the Bernoulli equation (that is, without a head-loss term), the theoretical velocity at the throat is obtained. Then by multiplying this by the venturi factor (Cv), which accounts for friction losses and equals 0.98 for most venturis, the actual velocity is obtained. The actual velocity times the actual area of the throat determines the actual discharge volumetric flow rate.

The pressure drop, P1-P2, across the venturi can be used to measure the flow rate using a U-tube manometer as shown in figure 57. The reading, R’, of the manometer is proportional to the pressure drop and thus the velocity of the fluid.

18. Instrumentation and control personnel shall demonstrate a familiarity level knowledge of basic heat transfer and fluid flow concepts and theories.

a. Explain the following terms: Static head Velocity head Friction head Head loss

The following information is taken from ITT Corporation, Goulds Pumps, Centrifugal Pump Fundamentals: Head, unless stated otherwise.

Page 172: Instrumentation and Control

161

Static Head

Static head is the vertical distance in feet between the free level of the source of supply and the point of free discharge or the free surface of the discharge liquid.

Velocity Head

Velocity head is the energy of a liquid as a result of its motion at some velocity V. It is the equivalent head in feet through which the water would have to fall to acquire the same velocity, or in other words, the head necessary to accelerate the water. Velocity head can be calculated from the following formula:

hv = g

2

2

v

where: g = 32.2 ft/sec2 v = liquid velocity in feet per second

The velocity head is usually insignificant and can be ignored in most high head systems. However, it can be a large factor and must be considered in low head systems.

Friction Head

Friction head is the head required to overcome the resistance to flow in the pipe and fittings. It is dependent upon the size, condition and type of pipe; number and type of pipe fittings; flow rate, and nature of the liquid.

Head Loss

The following is taken from DOE-HDBK-1012/3-92.

Head loss is a measure of the reduction in the total head (sum of elevation head, velocity head, and pressure head) of the fluid as it moves through a fluid system. Head loss is unavoidable in real fluids. It is present because of the friction between the fluid and the walls of the pipe; the friction between adjacent fluid particles as they move relative to one another; and the turbulence caused whenever the flow is redirected or affected in any way by such components as piping entrances and exits, pumps, valves, flow reducers, and fittings.

b. Describe the relationship between pressure and flow in a process system.

The following is taken from DOE-HDBK-1012/1-92.

A form of energy that is important in understanding energy transfer systems is P-V energy. This form of energy is called P-V energy because it arises from the pressure (P) and the volume (V) of a fluid. It is numerically equal to PV, the product of pressure and volume. Because energy is defined as the capacity of a system to perform work, a system where pressure and volume are permitted to expand performs work on its surroundings. Therefore, a fluid under pressure has the capacity to perform work. In engineering applications, the units of P-V energy, also called flow energy, are the units of pressure times volume (pounds-force per square foot times cubic feet), which equals foot-pounds force (ft-lbf).

Page 173: Instrumentation and Control

162

c. Using the ideal gas law, discuss the relationship between pressure, temperature, and volume.

The following is taken from DOE-HDBK-1012/1-92.

The ideal gas constant is designated by R, and the ideal gas equation is:

Pv = RT

where P = pressure v= volume T = temperature, and the pressure and temperature are absolute values.

The individual gas constant (R) may be obtained by dividing the universal gas constant (Ro) by the molecular weight (MW) of the gas. The units of (R) must always be consistent with the units of pressure, temperature, and volume used in the gas equation. No real gases follow the ideal gas law or equation completely. At temperatures near a gas’s boiling point, increases in pressure will cause condensation to take place and cause drastic decreases in volume. At very high pressures, the intermolecular forces of a gas are significant. However, most gases are in approximate agreement at pressures and temperatures above their boiling point.

The ideal gas law is used by engineers working with gases because it is simple to use and approximates real gas behavior. Most physical conditions of gases used by man fit the above description. Perhaps the most common use of gas behavior studied by engineers is that of the compression process using ideal gas approximations. Such a compression process may occur at constant temperature, constant volume, or under adiabatic conditions (no heat transfer). Whatever the process, the amount of work that results from it depends upon the process.

d. Describe the effects of pressure and temperature changes on confined fluids.

The following is taken from DOE-HDBK-1012/1-92.

The predominant effect of an increase in pressure in a compressible fluid, such as a gas, is an increase in the density of the fluid. An increase in the pressure of an incompressible fluid will not have a significant effect on the density. For example, increasing the pressure of 100 °F water from 15 psia to 15,000 psia will only increase the density by approximately 6 percent. Therefore, in engineering calculations, it is assumed that the density of incompressible fluids remains constant.

An increase in temperature will tend to decrease the density of any fluid. If the fluid is confined in a container of fixed volume, the effect of a temperature change will depend on whether the fluid is compressible.

If the fluid is a gas, it will respond to a temperature change in a manner predicted by the ideal gas laws. A 5 percent increase in absolute temperature will result in a 5 percent increase in the absolute pressure.

Page 174: Instrumentation and Control

163

If the fluid is an incompressible liquid in a closed container, an increase in the temperature will have a tremendously greater and potentially catastrophic effect. As the fluid temperature increases, it tries to expand, but expansion is prevented by the walls of the container. Because the fluid is incompressible, this results in a tremendous increase in pressure for a relatively minor temperature change. The change in specific volume for a given change in temperature is not the same at various beginning temperatures. Resultant pressure changes will vary. A useful rule for water is that pressure in a water-solid system will increase about 100 psi for every 1°F increase in temperature.

e. Describe how the density of a fluid varies with temperature.

According to DOE-HDBK-1012/1-92, an increase in temperature will tend to decrease the density of any fluid.

f. Describe the relationship between the pressure in a fluid column and the density and depth of the fluid.

The following is taken from DOE-HDBK-1012/3-92.

Careful measurements show that the pressure of a liquid is directly proportional to the depth, and for a given depth the liquid exerts the same pressure in all directions.

As shown in figure 58 the pressure at different levels in the tank varies and this causes the fluid to leave the tank at varying velocities. Pressure was defined to be force per unit area. In the case of this tank, the force is due to the weight of the water above the point where the pressure is being determined.

Source: DOE-HDBK-1012/3-92.

Figure 58. Pressure versus depth

Page 175: Instrumentation and Control

164

Example:

Pressure = Area

Force

= Area

Weight

P = cAg

mg

cAg

Vg

where: m = mass in lbm

g = acceleration due to earth’s gravity 32.17 2sec

ft.

gc = 32.17 2sec-lbf

ft.-lbm

2A = area in ft V = volume in ft3

r = density of fluid in 3ft

lbm

The volume is equal to the cross-sectional area times the height (h) of liquid. Substituting this into the above equation yields:

P = cAg

Ahg

cg

hg P =

This equation tells us that the pressure exerted by a column of water is directly proportional to the height of the column and the density of the water and is independent of the cross-sectional area of the column. The pressure thirty feet below the surface of a one inch diameter standpipe is the same as the pressure thirty feet below the surface of a large lake.

g. Define the terms “mass flow rate” and “volumetric flow rate.”

The following definitions are taken from DOE-HDBK-1012/3-92.

Mass Flow Rate

The mass flow rate (m) of a system is a measure of the mass of fluid passing a point in the system per unit time. The mass flow rate is related to the volumetric flow rate as shown in the equation below where ρ is the density of the fluid and V is the volumetric flow rate.

m = ρV

If the volumetric flow rate is in cubic feet per second and the density is in pounds-mass per cubic foot, the above equation results in mass flow rate measured in pounds-mass per second.

Page 176: Instrumentation and Control

165

Other common units for measurement of mass flow rate include kilograms per second and pounds-mass per hour.

Volumetric Flow Rate

The volumetric flow rate (V) of a system is a measure of the volume of fluid passing a point in the system per unit time. The volumetric flow rate can be calculated as the product of the cross-sectional area (A) for flow and the average flow velocity (v).

V = Av

If area is measured in square feet and velocity in feet per second, the above equation results in volumetric flow rate measured in cubic feet per second. Other common units for volumetric flow rate include gallons per minute, cubic centimeters per second, liters per minute, and gallons per hour.

h. Describe the phenomenon of water hammer, pressure spike, and steam hammer.

The following is taken from DOE-HDBK-1012/3-92.

Water Hammer

Water hammer is a liquid shock wave resulting from the sudden starting or stopping of flow. It is affected by the initial system pressure, the density of the fluid, the speed of sound in the fluid, the elasticity of the fluid and pipe, the change in velocity of the fluid, the diameter and thickness of the pipe, and the valve operating time.

During the closing of a valve, kinetic energy of the moving fluid is converted into potential energy. Elasticity of the fluid and pipe wall produces a wave of positive pressure back toward the fluid’s source. When this wave reaches the source, the mass of fluid will be at rest, but under tremendous pressure. The compressed liquid and stretched pipe walls will now start to release the liquid in the pipe back to the source and return to the static pressure of the source.

This release of energy will form another pressure wave back to the valve. When this shockwave reaches the valve, due to the momentum of the fluid, the pipe wall will begin to contract. This contraction is transmitted back to the source, which places the pressure in the piping below that of the static pressure of the source. These pressure waves will travel back and forth several times until the fluid friction dampens the alternating pressure waves to the static pressure of the source.

Normally, the entire hammer process takes place in under one second. The initial shock of suddenly stopped flow can induce transient pressure changes that exceed the static pressure. If the valve is closed slowly, the loss of kinetic energy is gradual. If it is closed quickly, the loss of kinetic energy is very rapid. A shock wave results because of this rapid loss of kinetic energy. The shock wave caused by water hammer can be of sufficient magnitude to cause physical damage to piping, equipment, and personnel. Water hammer in pipes has been known to pull pipe supports from their mounts, rupture piping, and cause pipe whip.

Page 177: Instrumentation and Control

166

Pressure Spike

A pressure spike is the resulting rapid rise in pressure above static pressure caused by water hammer. The highest pressure spike attained will be at the instant the flow changed and is governed by the following equation.

c

c

g

ΔνρΔP

where ΔP = pressure spike ρ = density of the fluid c = velocity of the pressure wave Δv = change in velocity of the fluid gc = gravitational constant 32.17

Steam Hammer

Steam hammer is similar to water hammer except it is for a steam system. Steam hammer is a gaseous shock wave resulting from the sudden starting or stopping of flow. Steam hammer is not as severe as water hammer for three reasons:

1. The compressibility of the steam dampens the shock wave. 2. The speed of sound in steam is approximately one third the speed of sound in water. 3. The density of steam is approximately 1600 times less than that of water.

The items of concern that deal with steam piping are thermal shock and water slugs (i.e., condensation in the steam system) as a result of improper warm up.

19. Instrumentation and control personnel shall demonstrate a familiarity level knowledge of mechanical engineering, theories, principles, and techniques.

a. Describe the basic construction and operation of the following types of valves used in a process system: Gate valve Globe valve Flow control valve Butterfly valve Diaphragm valves Check valve Relief and safety valves

The following is taken from DOE-HDBK-1018/2-93.

Gate Valve

A gate valve is a linear motion valve used to start or stop fluid flow. However, it does not regulate or throttle flow. The name “gate” is derived from the appearance of the disk in the flow stream. Figure 59 illustrates a gate valve.

Page 178: Instrumentation and Control

167

Source: DOE-HDBK-1018/2-93

Figure 59. Gate valve

The disk of a gate valve is completely removed from the flow stream when the valve is fully open. This characteristic offers virtually no resistance to flow when the valve is open. Hence, there is little pressure drop across an open gate valve. When the valve is fully closed, a disk-to-seal-ring contact surface exists for 360 degrees, and good sealing is provided. With the proper mating of a disk to the seal ring, very little or no leakage occurs across the disk when the gate valve is closed.

On opening the gate valve, the flow path is enlarged in a highly nonlinear manner with respect to percent of opening. This means that flow rate does not change evenly with stem

Page 179: Instrumentation and Control

168

travel. Also, a partially open gate disk tends to vibrate from the fluid flow. Most of the flow change occurs near shutoff with a relatively high fluid velocity causing disk and seat wear and eventual leakage if used to regulate flow. For these reasons, gate valves are not used to regulate or throttle flow.

A gate valve can be used for a wide variety of fluids and provides a tight seal when closed. The major disadvantages to the use of a gate valve are listed below:

1. It is not suitable for throttling applications. 2. It is prone to vibration in the partially open state. 3. It is more subject to seat and disk wear than a globe valve. 4. Repairs, such as lapping and grinding, are generally more difficult to accomplish.

Globe Valve

A globe valve is a linear motion valve used to stop, start, and regulate fluid flow. A Z-body globe valve is illustrated in figure 60.

Source: DOE-HDBK-1018/2-93

Figure 60. Z-body glove valve

The globe valve disk can be totally removed from the flow path, or it can completely close the flow path. The essential principle of globe valve operation is the perpendicular movement of the disk away from the seat. This causes the annular space between the disk and seat ring to gradually close as the valve is closed. This characteristic gives the globe valve good throttling ability, which permits its use in regulating flow. Therefore, the globe valve may be used for both stopping and starting fluid flow and for regulating flow.

Page 180: Instrumentation and Control

169

When compared to a gate valve, a globe valve generally yields much less seat leakage. This is because the disk-to-seat-ring contact is more at right angles, which permits the force of closing to tightly seat the disk.

Globe valves can be arranged so that the disk closes against or in the same direction of fluid flow. When the disk closes against the direction of flow, the kinetic energy of the fluid impedes closing but aids opening of the valve. When the disk closes in the same direction of flow, the kinetic energy of the fluid aids closing but impedes opening. This characteristic is preferable to other designs when quick-acting stop valves are necessary.

Globe valves also have drawbacks. The most evident shortcoming of the simple globe valve is the high head loss from two or more right angle turns of flowing fluid. Obstructions and discontinuities in the flow path lead to head loss. In a large high-pressure line, the fluid dynamic effects from pulsations, impacts, and pressure drops can damage trim, stem packing, and actuators. In addition, large valve sizes require considerable power to operate and are especially noisy in high-pressure applications.

Other drawbacks of globe valves are the large openings necessary for disk assembly, heavier weight than other valves of the same flow rating, and the cantilevered mounting of the disk to the stem.

Flow Control Valve

Flow control valves are used to maintain a constant predetermined flow in a system. They must be installed in the correct flow direction (indicated by label) to work properly. They use a diaphragm that changes shape with inlet pressure changes, thus maintaining a constant flow rate. They are normally used to replace more costly flow control devices.

Butterfly Valve

A butterfly valve illustrated in figure 61 is a rotary motion valve that is used to stop, regulate, and start fluid flow. Butterfly valves are easily and quickly operated because a 90 degree rotation of the handle moves the disk from a fully closed to a fully opened position. Larger butterfly valves are actuated by hand wheels connected to the stem through gears that provide mechanical advantage at the expense of speed.

Page 181: Instrumentation and Control

170

Source: DOE-HDBK-1018/2-93

Figure 61. Typical butterfly valve

Butterfly valves possess many advantages over gate, globe, plug, and ball valves, especially for large valve applications. Savings in weight, space, and cost are the most obvious advantages. The maintenance costs are usually low because there are a minimal number of moving parts and there are no pockets to trap fluids.

Diaphragm Valves

A diaphragm valve is a linear motion valve that is used to start, regulate, and stop fluid flow. The name is derived from its flexible disk, which mates with a seat located in the open area at the top of the valve body to form a seal. A diaphragm valve is illustrated in figure 62.

Diaphragm valves are, in effect, simple “pinch clamp” valves. A resilient, flexible diaphragm is connected to a compressor by a stud molded into the diaphragm. The compressor is moved up and down by the valve stem. Hence, the diaphragm lifts when the compressor is raised. As the compressor is lowered, the diaphragm is pressed against the contoured bottom in a straight-through valve, or against the body weir in the weir-type valve.

Diaphragm valves can also be used for throttling service. The weir-type is the better throttling valve, but it has a limited range. Its throttling characteristics are essentially those of a quick-opening valve because of the large shutoff area along the seat.

Page 182: Instrumentation and Control

171

Source: DOE-HDBK-1018/2-93

Figure 62. Straight-through diaphragm valve

A weir-type diaphragm valve is available to control small flows. It uses a two-piece compressor component. Instead of the entire diaphragm lifting off the weir when the valve is opened, the first increments of stem travel raise an inner compressor component that causes only the central part of the diaphragm to lift. This creates a relatively small opening through the center of the valve. After the inner compressor is completely open, the outer compressor component is raised along with the inner compressor and the remainder of the throttling is similar to the throttling that takes place in a conventional valve.

Diaphragm valves are particularly suited for the handling of corrosive fluids, fibrous slurries, radioactive fluids, or other fluids that must remain free from contamination.

Check Valve

Check valves are designed to prevent the reversal of flow in a piping system. These valves are activated by the flowing material in the pipeline. The pressure of the fluid passing through the system opens the valve, while any reversal of flow will close the valve. Closure is accomplished by the weight of the check mechanism, by back pressure, by a spring, or by a combination of these means. The general types of check valves are swing, tilting-disk, piston, butterfly, and stop.

Relief and Safety Valves

Relief and safety valves prevent equipment damage by relieving accidental over-pressurization of fluid systems. The main difference between a relief valve and a safety valve is the extent of opening at the setpoint pressure.

A relief valve, illustrated in figure 63, gradually opens as the inlet pressure increases above the setpoint. A relief valve opens only as necessary to relieve the over-pressure condition. A safety valve rapidly pops fully open as soon as the pressure setting is reached.

Page 183: Instrumentation and Control

172

A safety valve will stay fully open until the pressure drops below a reset pressure. The reset pressure is lower than the actuating pressure setpoint. The difference between the actuating pressure setpoint and the pressure at which the safety valve resets is called blowdown. Blowdown is expressed as a percentage of the actuating pressure setpoint.

Source: DOE-HDBK-1018/2-93

Figure 63. Relief valve

b. Discuss how valve operation controlled by a process control system can cause water hammer or pressure spiking if the system is not designed properly.

The following is taken from DOE-HDBK-1012/3-92.

During the closing of a valve, kinetic energy of the moving fluid is converted into potential energy. The elasticity of the fluid and pipe wall produces a wave of positive pressure back toward the fluid’s source. When this wave reaches the source, the mass of fluid will be at rest, but under tremendous pressure. The compressed liquid and stretched pipe walls will now start to release the liquid in the pipe back to the source and return to the static pressure of the source.

Page 184: Instrumentation and Control

173

This release of energy will form another pressure wave back to the valve. When this shockwave reaches the valve, due to the momentum of the fluid, the pipe wall will begin to contract. This contraction is transmitted back to the source, which places the pressure in the piping below that of the static pressure of the source. These pressure waves will travel back and forth several times until the fluid friction dampens the alternating pressure waves to the static pressure of the source. Normally, the entire hammer process takes place in under one second.

The initial shock of suddenly stopped flow can induce transient pressure changes that exceed the static pressure. If the valve is closed slowly, the loss of kinetic energy is gradual. If it is closed quickly, the loss of kinetic energy is very rapid. A shock wave results because of this rapid loss of kinetic energy. The shock wave caused by water hammer can be of sufficient magnitude to cause physical damage to piping, equipment, and personnel. Water hammer in pipes has been known to pull pipe supports from their mounts, rupture piping, and cause pipe whip.

c. Describe the basic operation and pressure/flow characteristics of the following types of pumps: Centrifugal pump Positive displacement pump

Centrifugal Pump

The following is taken from DOE-HDBK-1012/3-92.

Fluid entering a centrifugal pump is immediately directed to the low-pressure area at the center or eye of the impeller. As the impeller and blading rotate, they transfer momentum to incoming fluid. A transfer of momentum to the moving fluid increases the fluid’s velocity. As the fluid’s velocity increases, its kinetic energy increases. Fluid of high kinetic energy is forced out of the impeller area and enters the volute.

The volute is a region of continuously increasing cross-sectional area designed to convert the kinetic energy of the fluid into fluid pressure. The mechanism of this energy conversion is the same as that for subsonic flow through the diverging section of a nozzle. The mathematical analysis of flow through the volute is based on the general energy equation, the continuity equation, and the equation relating the internal properties of a system. The key parameters influencing the energy conversion are the expanding cross-sectional area of the volute, the higher system back pressure at the discharge of the volute, and the incompressible, subsonic flow of the fluid. As a result of the interdependence of these parameters, the fluid flow in the volute, similar to subsonic flow in a diverging nozzle, experiences a velocity decrease and a pressure increase.

Positive Displacement Pump

The following is taken from DOE-HDBK-1018/1-93.

A positive displacement pump is one in which a definite volume of liquid is delivered for each cycle of pump operation. This volume is constant regardless of the resistance to flow offered by the system the pump is in, provided the capacity of the power unit driving the pump or the pump component strength limits are not exceeded. The positive displacement

Page 185: Instrumentation and Control

174

pump delivers liquid in separate volumes with no delivery in between, although a pump having several chambers may have an overlapping delivery among individual chambers, which minimizes this effect. The positive displacement pump differs from centrifugal pumps, which deliver a continuous flow for any given pump speed and discharge resistance.

Positive displacement pumps can be grouped into three basic categories based on their design and operation. The three groups are reciprocating pumps, rotary pumps, and diaphragm pumps.

d. Describe the basic design and operation of a compressed air system used to supply instrument air, including a discussion of the function of the following components: Compressor Moisture separator Intercooler After cooler Receiver Air dryer

Compressor

The following is taken from DOE-HDBK-1018/2-93.

The centrifugal compressor, originally built to handle only large volumes of low pressure gas and air (maximum of 40 psig), has been developed to enable it to move large volumes of gas with discharge pressures up to 3,500 psig. However, centrifugal compressors are now most frequently used for medium volume and medium pressure air delivery. One advantage of a centrifugal pump is the smooth discharge of the compressed air.

The centrifugal force used by the centrifugal compressor is the same force used by the centrifugal pump. The air particles enter the eye of the impeller, designated D in figure 64. As the impeller rotates, air is thrown against the casing of the compressor. The air becomes compressed as more and more air is thrown out to the casing by the impeller blades.

Page 186: Instrumentation and Control

175

Source: DOE-HDBK-1018/2-93

Figure 64. Simplied centrifugal pump

The air is pushed along the path designated A, B, and C in figure 64. The pressure of the air is increased as it is pushed along this path. Note in figure 64 that the impeller blades curve forward, which is opposite to the backward curve used in typical centrifugal liquid pumps.

Centrifugal compressors can use a variety of blade orientation, including forward and backward curves as well as other designs.

Moisture Separator

The following is taken from Integrated Publishing, Moisture Separators.

The moisture separator in a pneumatic system is always located downstream of the compressor. Its purpose is to remove any moisture caused by the compressor. A complete moisture separator consists of a reservoir, a pressure switch, a dump valve, and a check valve, and it may also include a regulator and a relief valve. The dump valve is energized and de-energized by the pressure switch. When de-energized, it completely purges the separator reservoir and lines up to the compressor. The check valve protects the system against pressure loss during the dumping cycle and prevents reverse flow through the separator.

Intercooler

The following is taken from DOE-HDBK-1018/2-93.

If the compressor is multi-staged, there may be an intercooler, which is usually located after the first stage discharge and before the second stage suction. The principle of the intercooler is the same as that of the after coolers. The result is drier, cooler, compressed air. The structure of a particular cooler depends on the pressure and volume of the air it cools. Air

Page 187: Instrumentation and Control

176

coolers are used because drier compressed air helps prevent corrosion and cooler compressed air allows more air to be compressed for a set volume.

Aftercooler

The following is taken from DOE-HDBK-1018/2-93.

Coolers used on the discharge of a compressor are called aftercoolers. Their purpose is to remove the heat generated during the compression of the air. The decrease in temperature promotes the condensing of any moisture present in the compressed air. This moisture is collected in condensate traps that are either automatically or manually drained.

Receiver

The following is taken from Energy Manager Training, Design Compressed Air System and Components.

Air receivers provide storage capacity to prevent rapid compressor cycling; reduce wear and tear on compression modules, inlet control systems, and motors; eliminate pulsing air flow; avoid overloading purification system with surges in air demand; and damp out the dew point and temperature spikes that follow regeneration.

A rule of thumb is to provide a minimum of one gallon of receiver capacity for each cubic foot of compressor flow.

Air Dryer

The following is taken from Energy Manager Training, Design Compressed Air System and Components.

An aftercooler discharging compressed air at 100 °F passes 67 gallons of water per 1,000 standard cubic feet per minute (scfm) per 24 hours. Instrumentation fails when water and lubricant condense as the air is further cooled in the piping system or as the air expands through the orifices.

The air exiting the aftercooler is saturated, and any further temperature drop results in more condensation. A useful rule of thumb states that a 20 degree reduction in temperature condenses one-half the water vapor in saturated air.

Air dryers reduce the moisture content as measured in terms of a pressure dew point that is based on a specific set of inlet conditions to the dryer.

Dew point is the temperature at which water vapor condenses—saturated, 100% relative humidity. Pressure dew point is the dew point of the air at operating pressure. Atmospheric dew point refers to air expanded to atmospheric conditions. To avoid confusion, specify dryer performance in terms of pressure dew point.

Dryer Selection

The instruments and the lowest expected ambient temperature determine the drying method. The most common dryer is a refrigerated unit that cools the compressed air, condenses water

Page 188: Instrumentation and Control

177

and oil vapors, separates them, and drains them from the system. The dried compressed air is then fed to the instrument air system.

Dryer performance is specified as a pressure dew point class that is based on a specific inlet and ambient conditions. The lowest pressure dew point class with a refrigerated dryer is Class H. This class delivers a pressure dew point that of 33° to 39 °F. Refrigerated dryers should not operate below the Class H range because the water vapor will freeze in the dryer. The highest practical pressure dew point for a refrigerated dryer is 60 °F because higher pressure dew points give condensation in downstream piping.

In the United States, most dryer manufacturers base the pressure dew point performance on standard conditions: inlet air flow, 100 °F inlet air temperature, 100 psig operating pressure, 100 °F maximum ambient temperature (air-cooled units), 85 °F cooling water temperature (water-cooled units), and 5 psi maximum pressure drop.

Adjust air dryer sizing to account for deviation from standard conditions. For example, elevating the inlet air temperature 10 degrees increases the load on the dryer by more than 25 percent and raises the outlet pressure dew point above 50 °F. Maintaining the original 33°–39 °F dew point now requires a dryer 35 percent larger.

Desiccant dryers give pressure dew points below 33 °F if piping is exposed to freezing temperatures. Desiccants dry air through adsorption in which a hydroscopic material—chemical, alumina, silica, molecular sieve—removes the water and oil to reduce the dew point to the standard pressure dew point of -40 °F. Special designs produce dew points of 100 °F or lower.

Dryer Selection Guidelines

Non-cycling and cycling are the two types of refrigerated dryers. On a non-cycling dryer, the refrigeration compressor runs continuously regardless of dryer load. A thermostatic expansion valve and hot gas bypass valve regulate the flow of refrigerant into the heat exchanger to maintain dew point and minimize freeze-up. Since the unit uses full input power at all times, a non-cycling dryer should be selected for systems with a constant air flow.

In cycling dryers, the refrigerant cools an intermediate fluid that cools and dries the air. During low-load operation, the refrigeration circuit stops its compressor and restarts it when the fluid temperature rises. The cycling type dryer conserves energy and minimizes dryer freeze-up, making cycling dryers the choice with fluctuating air flow and inlet temperatures. Over-sized cycling dryers provide additional drying capacity for future air system upgrades.

e. Describe the function and operation of vibration monitoring equipment used to monitor large motors, pumps, and compressors.

The following is taken from Mechanical Engineering, Vibration Monitor.

The machinery vibration monitor for hazardous areas provides continuous machinery screening by detecting, evaluating, and announcing vibration problems to operators as they develop. This system learns and compares vibration spectrums, allowing it to detect even

Page 189: Instrumentation and Control

178

subtle, incremental, sustained changes. The system can shut down malfunctioning equipment to help prevent catastrophic breakdown, costly repairs, and downtime. The vibration monitor is designed to monitor large motors, pumps, and compressors.

f. Describe the basic operation of pressure regulating valves and flow control valves in a process system.

The following is taken from Integrated Publishing, Construction, Suction Pressure-Regulating Valves.

Pressure Regulating Valves

Pressure-regulating valves may be installed in the suction line at the outlet of an evaporator when a minimum temperature must be maintained. Pressure-regulating valves decrease the temperature difference, which would otherwise exist between the compartment temperature and the surface of the cooling coils. The amount of heat that can be transferred into the evaporating refrigerant is directly proportional to the temperature difference.

Three types of suction pressure-regulating valves are used—suction throttling valve, evaporator pressure regulators, or pilot-operated absolute valve (POA), developed by General Motors Corporation. These valves, in most cases, are adjustable. The POA valve uses a sealed pressure element that maintains a constant pressure independent of the altitude of the vehicle. There are two basic types of metering devices built into a single container—the VIR (valves-in-receiver) and the evaporator equalized VIR. These units combine the POA valve, receiver-drier, thermostatic expansion valve, and sight glass into a single unit. The VIR assembly is mounted next to the evaporator, which eliminates the need for an external equalizer line between the thermostatic expansion valve and the outlet of the POA valve. The equalizer function is carried out by a drilled hole (equalizer port) between the two-valve cavities in the VIR housing. The thermostatic expansion valve is also eliminated. The diaphragm of the VIR expansion valve is exposed to the refrigerant vapor entering the VIR unit from the outlet of the evaporator. The sight glass is in the valve housing at the inlet end of the thermostatic valve cavity where it gives a liquid indication of the refrigerant level.

Flow Control Valves

The following is taken from Hydraulics and Pneumatics, Other Flow Controls.

Proportional flow-control valves combine state-of-the-art hydraulic valve actuation with modern, sophisticated electronic control. These valves help simplify hydraulic circuitry by reducing the number of components a system may require while, at the same time, substantially increasing system accuracy and efficiency.

An electronically controlled, proportional flow-control valve modulates fluid flow in proportion to the input current it receives. The valves can easily control cylinders or smaller hydraulic motors in applications that require precise speed control or controlled acceleration or deceleration. Most proportional flow-control valves are pressure-compensated to minimize flow variations caused by changes in inlet or outlet pressure.

An electrohydraulic proportional valve consists of three main elements: 1. A pilot or proportional solenoid

Page 190: Instrumentation and Control

179

2. A metering area (where the valve spool is located), 3. An electronic position-feedback device, often an LVDT (linear variable differential

transformer)

Valve operation begins when it receives a signal from an outside controlling device such as a computer, programmable logic controller, traditional logic relay, or potentiometer. The control device delivers analog electrical signals to the valve driver card, which, in turn, sends a current signal to the solenoid on the valve.

The electromechanical force on the spool causes it to shift, gradually opening a flow path from the pump to the actuator port. The greater the command input signal, the greater the current to the valve solenoid, and, thus, the higher the flow from the valve. The important feature of this proportional valve is that all elements are proportional; thus, any change in input current changes force signals proportionately as well as the distance the valve spool will shift, the size of the flow path, the amount of fluid flowing through the valve, and finally the speed at which the actuator moves.

As the spool shifts, its motion is detected and monitored very accurately by a LVDT or other type of position-feedback transducer. This signal is fed back to the driver card where it is continuously compared with the input signals from the controller. If the two differ, the driver adjusts spool position until the two signals match.

Pressure-compensated proportional flow-control valves are two-port valves in which the main control orifice is adjusted electronically. Similar to conventional pressure-compensated flow-control valves, a pressure-compensated proportional flow-control valve maintains constant flow output by keeping the pressure drop constant across the main control orifice. The proportional valve, however, is different in that the control orifice is modified to work in conjunction with a stroke controlled solenoid.

In a two-port, pressure-compensated proportional flow-control valve, an electrically adjustable control orifice is connected in series with a pressure reducing valve spool, known as a compensator, figure 64. The compensator is located upstream of the main control orifice and is held open by a light spring. When there is no input signal to the solenoid, the light spring force holds the main control orifice closed. When the solenoid is energized, the solenoid pin acts directly on the control orifice, moving it downward against the spring to open the valve and allow oil to flow from port A to port B.

Page 191: Instrumentation and Control

180

Source: Hydraulics & Pneumatics, Other Flow Controls

Figure 65. Circuit diagram for pressure-compensated flow-control valve

At the same time, the LVDT provides the necessary feedback to hold position. In this case, the LVDT provides feedback to maintain a very accurate orifice setting.

Pressure compensation is achieved by incorporating a pilot passage at the inlet of the valve that connects to one side of the compensator spool, A2. There is another pilot passage located near the outlet of the valve beyond the control orifice, and it is connected to the opposite side of the compensator spool, A3. A bias spring on this side of the spool keeps the compensator in the open position. Load-induced pressure at the outlet port—or pressure deviations at the inlet port—modulate the compensator spool to increase or decrease the pressure drop across the compensator’s metering orifice. Acting as a pressure reducing valve, the compensator ensures that the main control orifice sees a constant pressure drop. When the pressure drop is constant, the flow remains constant.

The amplifier provides time controlled opening and closing of the orifice. For reverse free-flow, check valve C, built into the valve, provides a flow path from port B to A. Proportional flow-control valves are also available with either linear or progressive flow characteristics. The input signal range is the same for both. However, the progressive flow characteristic gives finer control at the beginning of orifice adjustment.

In case electrical power or feedback is lost, solenoid force drops to zero and the force exerted by the spring closes the orifice. When feedback wiring is connected incorrectly or damaged a light-emitting diode indicates the malfunction on the amplifier card.

g. Describe the basic theory of operation of a heat exchanger used in a process system.

The following is taken from DOE-HDBK-1018/1-93.

Page 192: Instrumentation and Control

181

Heat exchangers are found in most chemical or mechanical systems. They serve as the system’s means of gaining or rejecting heat. Some of the more common applications are found in heating, ventilation and air conditioning systems, radiators on internal combustion engines; boilers, condensers, and as preheaters or coolers in fluid systems.

Preheater

In large steam systems, or in any process requiring high temperatures, the input fluid is usually preheated in stages, instead of trying to heat it in one step from ambient to the final temperature.

Preheating in stages increases the plant’s efficiency and minimizes thermal shock stress to components, as compared to injecting ambient temperature liquid into a boiler or other device that operates at high temperatures. In the case of a steam system, a portion of the process steam is tapped off and used as a heat source to reheat the feedwater in preheater stages. Figure 66 is an example of the construction and internals of a U-tube feedwater heat exchanger found in a large power generation facility in a preheater stage.

Source: DOE-HDBK-1018/1-93

Figure 66. U-tube feedwater heat exchanger

As the steam enters the heat exchanger and flows over and around the tubes, it transfers its thermal energy and is condensed. Note that the steam enters from the top into the shell side of the heat exchanger, where it not only transfers sensible heat (temperature change) but also

Page 193: Instrumentation and Control

182

gives up its latent heat of vaporization (condenses steam into water). The condensed steam then exits as a liquid at the bottom of the heat exchanger. The feedwater enters the heat exchanger on the bottom right end and flows into the tubes. Note that most of these tubes will be below the fluid level on the shell side.

This means the feedwater is exposed to the condensed steam first and then travels through the tubes and back around to the top right end of the heat exchanger. After making the 180° bend, the partially heated feedwater is then subjected to the hotter steam entering the shell side.

The feedwater is further heated by the hot steam and then exits the heat exchanger. In this type of heat exchanger, the shell side fluid level is very important in determining the efficiency of the heat exchanger, as the shell side fluid level determines the number of tubes exposed to the hot steam.

Radiator

Commonly, heat exchangers are thought of as liquid-to-liquid devices only. But a heat exchanger is any device that transfers heat from one fluid to another. Some of a facility’s equipment depend on air-to-liquid heat exchangers. The most familiar example of an air-to liquid heat exchanger is a car radiator. The coolant flowing in the engine picks up heat from the engine block and carries it to the radiator. From the radiator, the hot coolant flows into the tube side of the radiator (heat exchanger). The relatively cool air flowing over the outside of the tubes picks up the heat, reducing the temperature of the coolant.

Because air is such a poor conductor of heat, the heat transfer area between the metal of the radiator and the air must be maximized. This is done by using fins on the outside of the tubes. The fins improve the efficiency of a heat exchanger and are commonly found on most liquid-to-air heat exchangers and in some high efficiency liquid-to-liquid heat exchangers.

h. Describe the various methods and characteristics of heat transfer that may occur in a process system.

The following is taken from DOE-HDBK-1012/2-92.

Heat is always transferred when a temperature difference exists between two bodies. There are three basic modes of heat transfer:

1. Conduction involves the transfer of heat by the interactions of atoms or molecules of a material through which the heat is being transferred.

2. Convection involves the transfer of heat by the mixing and motion of macroscopic portions of a fluid.

3. Radiation, or radiant heat transfer, involves the transfer of heat by electromagnetic radiation that arises due to the temperature of a body.

Conduction

Conduction involves the transfer of heat by the interaction between adjacent molecules of a material. Heat transfer by conduction depends on the driving force of temperature difference and the resistance to heat transfer. The resistance to heat transfer depends on the nature and

Page 194: Instrumentation and Control

183

dimensions of the heat transfer medium. All heat transfer problems involve the temperature difference, the geometry, and the physical properties of the object being studied.

In conduction heat transfer problems, the object being studied is usually a solid. Convection problems involve a fluid medium. Radiation heat transfer problems involve either solid or fluid surfaces, separated by a gas, vapor, or vacuum. There are several ways to correlate the geometry, physical properties, and temperature difference of an object with the rate of heat transfer through the object. In conduction heat transfer, the most common means of correlation is through Fourier’s Law of Conduction. The law, in its equation form, is used most often in its rectangular or cylindrical form (pipes and cylinders), both of which are presented below.

x

TkAQ

r

TkAQ

where Q= rate of heat transfer (Btu/hr) A = cross-sectional area of heat transfer (ft2) x = thickness of slab (ft) r = thickness of cylindrical wall (ft) T = temperature difference (°F) k = thermal conductivity of slab (Btu/ft-hr-°F)

Convection

Convection involves the transfer of heat by the motion and mixing of macroscopic portions of a fluid (that is, the flow of a fluid past a solid boundary). The term “natural convection” is used if this motion and mixing is caused by density variations resulting from temperature differences within the fluid. The term “forced convection” is used if this motion and mixing is caused by an outside force, such as a pump. The transfer of heat from a hot water radiator to a room is an example of heat transfer by natural convection. The transfer of heat from the surface of a heat exchanger to the bulk of a fluid being pumped through the heat exchanger is an example of forced convection.

Heat transfer by convection is more difficult to analyze than heat transfer by conduction because no single property of the heat transfer medium, such as thermal conductivity, can be defined to describe the mechanism. Heat transfer by convection varies from situation to situation, and it is frequently coupled with the mode of fluid flow. In practice, analysis of heat transfer by convection is treated empirically (by direct observation).

Convection heat transfer is treated empirically because of the factors that affect the stagnant film thickness: Fluid velocity Fluid viscosity Heat flux

Page 195: Instrumentation and Control

184

Surface roughness Type of flow (single-phase/two-phase)

Convection involves the transfer of heat between a surface at a given temperature (Ts) and fluid at a bulk temperature (Tb). The exact definition of the bulk temperature (Tb) varies depending on the details of the situation. For flow adjacent to a hot or cold surface, Tb is the temperature of the fluid far from the surface. For boiling or condensation, Tb is the saturation temperature of the fluid. For flow in a pipe, Tb is the average temperature measured at a particular cross section of the pipe.

Radiation

Radiant heat transfer involves the transfer of heat by electromagnetic radiation that arises due to the temperature of a body. Most energy of this type is in the infra-red region of the electromagnetic spectrum, although some of it is in the visible region. The term thermal radiation is frequently used to distinguish this form of electromagnetic radiation from other forms, such as radio waves, x-rays, or gamma rays. The transfer of heat from a fireplace across a room in the line of sight is an example of radiant heat transfer.

Radiant heat transfer does not need a medium, such as air or metal, to take place. Any material that has a temperature above absolute zero gives off some radiant energy. When a cloud covers the sun, both its heat and light diminish. This is one of the most familiar examples of heat transfer by thermal radiation.

i. Describe the basic design and operation of a typical heating, ventilation, and air conditioning (HVAC) system, including a discussion of the control system used to maintain habitability.

The following is taken from NCDENR, Energy Efficiency in Industrial HVAC Systems.

HVAC stands for heating, ventilation, and air conditioning and refers to the equipment, distribution network, and terminals used either collectively or individually to provide fresh filtered air, heating, cooling, and humidity control in a building.

A facility can have any combination of heating and cooling sources to supply the HVAC system. For heating a facility, a gas-or oil-fired boiler or furnace, heat pump, rooftop unit, new technology such as infrared radiation, or electric heat could be employed. Common cooling sources include rooftop units, chillers, heat pumps, air conditioners or some sort of off-peak cooling system.

Basic HVAC Design

HVAC systems vary in design and complexity. The following description represents a simple HVAC system. Modifications can be added to the basic system to reach the desired HVAC operation.

Air is taken through an outdoor air intake that is usually a louvered opening on the top or side of the building. Atmospheric pressure pushes the air through a damper, which regulates the amount of outdoor air taken in by the system. At this point, already conditioned return air from the system can be mixed with the outdoor air to form mixed air. The mixed air goes

Page 196: Instrumentation and Control

185

through a pre-filter where larger dust particles, insects, leaves, etc. are caught. A more efficient filter is usually present to address small particles. After the filters, the air enters a centrifugal fan. Once exiting the fan outlet, the air is under positive pressure and being pushed towards coils where the air is either heated or cooled, depending on the temperature of the air and the season. Under the coils lies a drain pan to collect any water condensing on the coils. If a humidifier or dehumidifier is needed it is usually incorporated into the cycle at this point. The air travels through ductwork where it reaches a distribution box and may travel through smaller ducts to supply the terminals, registers, or diffusers into the workspace. Once the air reaches its destination, it is returned through an air register (usually through a louvered door that opens into a space above the ceiling tiles) in the form of return air that will become mixed air or exit the building.

Air Conditioning

Air conditioning is treating air for temperature, cleanliness, and humidity and directing its distribution to meet requirements of a conditioned space. Comfort air conditioning is when the primary function of the system is to provide comfort to occupants of the conditioned space. The term “industrial air conditioning” is used when the primary function is other than comfort.

There are three basic types of air conditioners: 1. Direct expansion coolers include window air conditioners, heat pumps, and packaged

or rooftop units. Air is cooled and dehumidified as it moves past a cold, refrigerant-filled coil.

2. Chilled water systems use water cooled by a refrigeration machine instead of air. This cool water supplies a coil, which cools and dehumidifies the air.

3. Evaporative or swamp coolers are usually only appropriate in hot, dry climates and bring hot air in contact with a water spray or damp surface. The result is evaporation of moisture, which lowers the temperature of the air.

Ventilation

Ventilation is a process that either supplies or removes air from a space by natural or mechanical means. All air that is exhausted from a building must be replaced by outside air. Outside air must be brought to a certain temperature by makeup air units used throughout the building. Negative building pressure can be a problem during winter heating season and could lead to a number of other problems, such as difficulty in opening doors and equipment operation. Air seeps through gaps around windows, doors, and ducts.

Air is distributed through ducts. Units such as a window air conditioner, distribute air directly from the unit. Other units using baseboards or radiators may deliver heat through water, steam, or electric resistance systems. Blowers and registers deliver air in forced air systems.

Page 197: Instrumentation and Control

186

j. Given a process and instrumentation diagram and the technical specifications for a process system, describe the purpose of the system and the major flowpaths.

k. Given a process and instrumentation diagram and the technical specifications for a process system, describe the function of each of the major components of the system.

Competencies j and k are performance based. The Qualifying Official will evaluate their completion.

20. Instrumentation and control personnel shall demonstrate a familiarity level knowledge of the geoseismic/civil engineering theories, principles, and techniques that apply to instrumentation and control systems.

a. Discuss the seismic design constraints imposed on instrumentation and control systems important to safety.

The following is taken from DOE-STD-1020-2002.

Systems, structures, and components (SSCs) are placed in one of five performance categories (PCs) ranging from PC 0 to PC 4. No special considerations for natural phenomena hazards (NPH) are needed for PC 0. Different criteria are provided for the remaining four performance categories, each with a specified performance goal. Design and evaluation criteria aimed at target probabilistic performance goals require probabilistic NPH assessments. NPH loads are developed from such assessments by specifying NPH mean annual probabilities of exceedance. Performance goals may then be achieved by using the resulting loads combined with deterministic design and evaluation procedures that provide a consistent and appropriate level of conservatism. Design/evaluation procedures conform closely to industry practices using national consensus codes and standards so that the procedures will be easily understood by most engineers. SSCs comprising a DOE facility are to be assigned to a performance category using the approach described in the DOE G 420.1-2 and the performance categorization standard. The design and evaluation criteria in DOE-STD-1020-2002 are the specific provisions to be followed so that the performance goal associated with the performance category of the SSC under consideration is achieved. For each category, the criteria include the following steps:

1. NPH loads are determined at specified NPH probabilities as per DOE-STD-1023-95. 2. Design and evaluation procedures are used to evaluate SSC response to NPH loads. 3. Criteria are used to assess whether or not computed response in combination with

other design loads is permissible. 4. Design detailing provisions are implemented so that the expected performance during

a potential NPH occurrence will be achieved. 5. Quality assurance and peer review are applied using a graded approach.

Page 198: Instrumentation and Control

187

b. Describe the function and operation of instrumentation systems used to measure and annunciate seismic events at defense nuclear facilities.

The following is taken from DOE G 420.1-2.

Facilities or sites that have SSCs in performance category 2 (with hazardous material), PC 3, or PC 4 shall have instrumentation or other means to detect and record the occurrence and severity of seismic events. These systems measure ground acceleration and provide an alarm when it measures acceleration above a threshold value. The purpose of this is to provide an indication and a record of seismic events so that a thorough damage inspection may be completed.

c. Discuss the effects of vibration on instrumentation and control system performance and reliability, including the methods used to mitigate those effects.

The following is taken from North Atlantic Treaty Organization, Mechanical Environmental Tests.

The following list provides examples of problems that could occur when instrumentation is exposed to a vibration environment. Wire chafing Loosening of fasteners Intermittent electrical contacts Mutual contact and short circuiting of electrical components Seal deformation Structural and component fatigue Optical misalignment Cracking and rupturing Loosening of particles or parts that may become lodged in circuits or mechanisms Excessive electrical noise

The following is taken from Lawrence Livermore National Laboroatory, Seismic Shock and Vibration Isolation.

Two basic engineering strategies for the protection of equipment and structures from damages caused by seismic shock and vibration loadings are strengthening and isolation. The strengthening strategy aims at increasing the capacity of the ability of the structure to withstand the dynamic loading by incorporating additional structural materials and components, while the isolation strategy focuses on reducing the demand or the transmitted loading on the structure by adding an isolator or isolation system between the structure and the source of the loading. The isolation strategy is also often used for filtering out unwanted vibrations and noises. The isolation strategy has the advantage of not depending on alterations to the isolated structure and is often the preferred method for applications in equipment.

Page 199: Instrumentation and Control

188

d. Discuss the general factors that affect the seismic qualification of a system, component, or structure.

The following is taken from Washington Savannah River Company, Seismic Design and Retrofit of Systems and Components.

The seismic qualification of systems and components is achieved by one (or a combination) of four methods: Testing (AC156 for International Building Code-based seismic input, IEEE 344,

IEEE 382, American Society of Mechanical Engineers (ASME) qualification of active mechanical equipment (QME) 1): preferred method for active mechanical equipment, electrical equipment, instrumentation and controls.

Analysis (ASME QME, IEEE 344-2004, applicable code for system or component): preferred method for passive mechanical equipment and distribution systems, and for electrical distribution systems.

Earthquake experience data. Equipment may be qualified by similarity to previously qualified equipment.

Qualification by similarity must address o Dynamic similarity of components. o Envelope of seismic input of previously qualified component.

Seismic qualification must address end-of-life condition, in particular: Testing: determine the need for environmental qualification of electrical equipment

(cables, batteries, etc.) and non-metallic components and trims. Analysis: deduct corrosion allowance when calculating stresses, address degradation

mechanisms other than wall thinning (environmental cracking, fatigue, mechanical damage, etc.).

Earthquake experience: assess the material condition and maintenance history of installed systems and components. For example, concrete cracking is a standard check for anchor bolts.

21. Instrumentation and control personnel shall demonstrate a familiarity level knowledge of the chemical engineering theories, principles, and techniques that apply to instrumentation and control systems.

a. Discuss the design elements that must be considered when applying instrumentation and control systems for use with chemical processes.

The following is taken from DOE-HDBK-1139/1-2006.

Control of chemical hazards should be carried out at all levels following the same hierarchy of controls as with any other health and safety hazard, i.e., substitution, engineering, administrative, and personal protective equipment. The level and rigor to which chemical hazards are controlled will depend in part on regulatory or contract requirements.

When controls for hazardous chemicals are established, they should be based on the hazard identification and hazard analysis, including any additive or synergistic effects. If multiple hazards with varying severities exist, then the most conservative control should be used, i.e.,

Page 200: Instrumentation and Control

189

if two types of hazard are present that use similar types of controls, the more protective control should be used.

To ensure control of chemical hazards, management should Substitute less hazardous chemicals, when possible. Team with workers to analyze, identify, and mitigate hazards. Provide ventilation and/or enclosures, as needed. Ensure that all chemicals are in appropriate containers with labels and that material

safety data sheets (MSDSs) are readily accessible. Title 29 CFR 1910.1200, “Hazard Communication,” contains important sections about labels and MSDSs, and 29 CFR 1910.1450, “Laboratory Standard,” also contains a relevant section.

Provide exposure monitoring and medical surveillance as appropriate. Management should establish procedures for monitoring of workers who handle hazardous chemicals. If worker exposure exceeds acceptable DOE or Occupational Safety and Health Administration levels, an investigation should be conducted and corrective actions instituted promptly.

Conduct regular training, and provide workers with information and instruction on the use and storage of chemicals. Training supports procedural requirements by letting workers know why actions are needed that would otherwise be regarded as inconvenient or unnecessary.

Inform personnel of the signs and symptoms of control failures. Provide and maintain personal protective equipment. Enforce housekeeping and work practices.

For hazardous waste sites, the mechanism for identifying work site chemical hazards and controls may be found in the site-specific health and safety plan (HASP). Details of the HASP’s requirements may be found in 29 CFR 1910.120, and guidance may be found in the “Handbook for Occupational Health and Safety During Hazardous Waste Activities” (DOE/EH-0535).

b. Discuss the application of instrumentation and control system components used to measure and control level, flow, temperature, and pressure in chemical process systems that contain corrosive chemicals.

The following is taken from Lifetime Reliability Solutions, Process Instruments for Difficult and Corrosive Environments.

There is always a degree of uncertainty in selecting instrumentation for difficult or corrosive environments. Material selection for chemical compatibility involves a strained decision between cost and equipment reliability and longevity. The other major uncertainty is whether the instrument is appropriate for the application. This section presents a list of instrumentation successfully used in a range of difficult and chemically demanding environments.

Differential Pressure Transmitter

Many process chemicals will destroy the internals of a pressure transmitter (PT). To prevent contact with aggressive chemicals, a diaphragm process seal is used to connect to the process. The PT is mounted on the other side of the seal. Select materials for the diaphragm

Page 201: Instrumentation and Control

190

that give many years of corrosion-free service. Protect against pitting and stress corrosion cracking in particular. At times exotic alloys or Teflon coatings are required. Check isocorrosion curves for pitting and stress corrosion cracking before specifying the diaphragm.

Temperature Compensation

As the outside temperature changes, the oil fill expands or contracts. If a differential PT is not temperature compensating, the change in volume causes the pressure inside the transmitter to also change. This makes the sensor distort and give a false pressure reading. In such cases protect the PT against temperature fluctuations by shading it from heat and direct sunlight. Or specify a PT with temperature compensation.

Diaphragm Cleanliness

Sediment or crystal build-up on the sensing diaphragm will stop the diaphragm from flexing freely and will produce false readings. Products that crystallize at cooler temperatures need special attention. Keep the liquid temperature at the diaphragm surface hot enough to prevent crystals forming in the cooler crevice between the diaphragm and transmitter body, or insulate the body to reduce the heat loss through the walls.

Ultrasonic Level Detector

When an ultrasonic level detector is used to measure liquid level major issues are stillness of the liquid surface and vapor given off by the process. Problem readings occur with undulating and turbulent liquid surfaces and where a lot of vapor is generated. If the liquid surface is not still the detector will get changing readings. Where vapor is present the sound signals will encounter interference. This may be overcome by putting the detector at the top of a dip pipe.

Process Chemical Compatibility

Selecting the wrong materials of construction will result in the detector’s housing corroding or dissolving from chemical attack. Check that the long-term application is suitable for the vapors and maximum operating temperatures. Beware if it seems the manufacturer’s specifications were apparently satisfied by the average process conditions. The local temperature and chemical compatibility conditions must be satisfied. The design conditions of the bulk liquid may be known but the detector must handle its local temperatures and chemical concentrations, not the bulk temperature and process conditions.

Vacuum Service

Since ultrasonic level detectors require sound to be transmitted and reflected, they will only operate in environments that contain sound-transmitting atmospheres. As such, they will not be reliable in a process conducted under vacuum conditions.

Internal Structures

The pulse emitted from an ultrasonic level detector will be reflected back by any object in its path. If there are internal structures within a tank below the ultrasonic level detector, they will reflect the pulse and produce a false signal. Relocate the ultrasonic level detector to a place where there is clear space below it.

Page 202: Instrumentation and Control

191

Calibrations

Check and calibrate the high and low levels and the span when an ultrasonic level detector is in its final position. With tanks, fill them with water, and physically dip and measure the levels to compare results. Alternatively, take the ultrasonic level detector to a dummy test set-up and then replace it in its required position.

Radar Level Detector

Location

The radar must be positioned to prevent unwanted reflections off tank internal structural beams, wall welds, rivets, etc. Unwanted reflections can be electronically separated but now you have programming complications better avoided if possible. Keep the receiver below the bottom of the nozzle so that it is in clear space. Pulses can bounce off the nozzle walls to the receiver and produce false signals.

Foam on the liquid surface deadens the return pulse. If located inside vigorously agitated tanks there is a risk of blocking the opening of the antenna cone from splashed product or condensing vapors. This is a problem with products that sublime (evaporate then solidify on surfaces) like sulphur or that crystallize.

Check material compatibles and process condition resistance for many years of operating service.

pH Meter

Process Variables

For pH meters to be accurate they require retention, or hold-up time, for chemical interactions within the process to come to completion. Lag occurs because of the transfer time needed for the dosing system to add the dosed agent. Measurement lag is present between the process chemical’s change in pH and the probe’s detection of the change. The mixing rate and agitation available to properly mix the chemical being measured so a pH measurement reflects the bulk chemical pH adds further complication. The process properties such as corrosion, erosion, sediment, caking, etc., on the probe can affect the measurement quality.

The pH probe requires time for pH to stabilize without rapid changes, stable temperature without extremes, clean electrode surfaces, full probe contact with the liquid being measured, sufficient conductivity through the process chemical, and no poisoning or drying of the reference electrode.

Operating Issues

Chemical compatibility is critical and the appropriate plastics, elastomers and metals need to be selected for the service. Acids and alkaline vapors will work their way into the probe’s internals unless it is suitably protected.

The liquid junction of the reference electrode must always be wet. If the liquid junction dries out, the pH probe is destroyed. In such situations use a probe that has a wetting spray to keep it moist. It is also possible to put the probe in a drop-leg bend where the pipe work is

Page 203: Instrumentation and Control

192

intentionally run down and then up again to create a catchment of liquid to keep the probe wet. Install a drain valve in the drop leg to empty the pipeline.

Conductivity Meter

Conductivity meters measure dissolved ions in a liquid. The sensing surface on normal probes become encrusted with scale over time, and the probe must be removed for cleaning. A direct-contact probe must be chemically cleaned in weak hydrochloric acid, not by scraping or buffing the surface. Scratching the sensor increases the surface area in contact with the solution and alters the cell constant. A self-cleaning probe overcomes much of this problem.

The meter must be properly earthed, as required by the manufacturer. Since the probe emits and senses electric currents, it will display readings from any electric current that presents to it. Badly connected conductivity meter set-ups will give false results even though the meter reads true at the time of calibration. If this happens, check the electrical continuity of the sensing system and meter equipment.

Mechanical Flow Meter

For a flow meter to be accurate numerous factors must be right. The programmable logic controller scan rate must be quicker than the meter pulses or pulses can be missed. Sediment must not be allowed to wear away the meter’s internal clearances. Solid items get jammed in the meter or protrude into the flow path. The meter specifications are based on water flow in laboratory conditions and a product with different physical properties or temperature is measured. Software adjustment factors added in to make the meter produce the required results are lost or changed. Temperature changes in the meter circuit electronics caused by the process fluid or local environment conditions change the behavior of the meter. Broken turbine wheel, rotor blades or paddles produce the wrong pulses. Leaks into the meter destroy internal circuitry. The meter accuracy varies as the flow rate varies. Meter position or orientation allows bubble inclusion in the liquid (two-phase flow).

Mechanical Level Switch

Mechanical level switches are in direct contact with the process chemicals. This can corrode components, product can jam moving parts, materials used in construction and methods of construction can fail due to pressure surges (floats can leak at joints and fill up with process fluid) and moving parts gradually wear. Internal electrical components can fail from dust, moisture, chemical attack and temperature effects.

Temperature Sensor

Thermocouple

Two wire thermocouples quickly detect a difference in temperature between the measuring end and meter end. It is critical to have both wires in firmly in contact with what is being measured. This is best done by tack welding the wires to the surface being measured.

Resistance Thermal Device

In a resistance thermal device the sensor is a fine wire wound around an insulated core and the lot is encapsulated in epoxy resin or glass and protected by an outside sheath of stainless

Page 204: Instrumentation and Control

193

steel. Encapsulating the wire significantly increases the response time (lag time) and makes resistance thermal devices less favorable for control purposes where process temperature changes quickly. resistance thermal devices can be damaged by being subjected to excessive temperatures, by being chemically attacked by the process chemicals, and from physical damage.

An resistance thermal device is designed to cover a span of temperature and emits a signal in proportion to the temperature. This signal is then converted into an electrical signal. It is critical that the signal converter have the same temperature span range as the resistance thermal device to ensure a true reading.

Capacitance Probe

The accuracy of capacitance probes depends on the electrical properties of the liquid or solid being measured. To ensure an electric field develops between the probes, the medium in which the probe sits must not conduct electricity and short circuit the probe.

These instruments are not affected by changes in the content’s pressure, temperature, or specific gravity (density). They can detect the presence of separate layers of different liquids within the same tank.

False level readings can arise if the dielectric properties change along the length of the probe and care is needed when calibrating the device in tanks containing layered liquids. Large changes in the vapor content within the space above the contents can lead to false level readings. Ensure the plastic sheaths protect probes from attack in corrosive liquids.

Magnetic Flow Meter

For a magnetic flow meter to work correctly and with confidence it must always be full of only liquid. It cannot recognize the presence of bubbles and will give false flow rates if they are present. Modify the pipe work to produce full-bore flow in the meter.

If the electrodes transmitting the small voltages created in the liquid become coated with process contaminants false readings occur. Long signal transmission cable runs or outside electrical interference affecting cables can produce false readings.

Calibration accuracy tests are usually done with water, and when the meter is used on non-water fluids wide errors are possible.

Correct earthing is critical. The meter will read voltage from any source. To ensure only voltage across the liquid is measured, keep the meter body in electrical contact with the liquid. In plastic pipes, this is done with graphite gaskets between the body and flanges or by an earthing ring of chemically compatible metal connected to the meter body. In metal pipes, clamping to a metal tag on the meter body and on the pipe flanges makes the electrical contact.

Orifice Flow Meter

The accuracy of an orifice plate flow meter depends on the squared edge remaining round and sharp. Wear or damage will produce errors in the pressure reading. It is also necessary to ensure that no partial blockages occur upstream of the orifice that produce changes to the

Page 205: Instrumentation and Control

194

flow profile and pressure gradient. Blockages can occur in the sensing lines from the orifice to the transmitter or pressure gauge. The position at which the meters are located should be where the flow pattern in the pipe is straight and no turbulence exists.

22. Instrumentation and control personnel shall demonstrate the ability to read and interpret electrical diagrams, including: One-line diagrams Schematics Logic diagrams Printed wiring board diagrams

a. Given an electrical diagram, identify electrical component symbology.

b. Given a logic diagram for a control circuit, identify and describe the effects of an action taken.

Competencies a and b are performance based. The Qualifying Official will evaluate their completion.

c. Identify the symbols used on logic diagrams to represent the components.

The following is taken from DOE-HDBK-1016/2-93.

There are three basic types of logic gates. They are AND, OR, and NOT gates. Each gate is a very simple device that only has two states, on and off. The states of a gate are also commonly referred to as high or low, 1 or 0, or true or false, where on = high = 1 = true, and off = low = 0 = false. The state of the gate, also referred to as its output, is determined by the status of the inputs to the gate, with each type of gate responding differently to the various possible combinations of inputs. Specifically, these combinations are as follows: AND gate - provides an output (on) when all its inputs are on. When any one of the

inputs is off, the gate’s output is off. OR gate - provides an output (on) when any one or more of its inputs are on. The gate

is off only when all of its inputs are off. NOT gate - provides a reversal of the input. If the input is on, the output will be off. If

the input is off, the output will be on.

Because the NOT gate is frequently used in conjunction with AND and OR gates, special symbols have been developed to represent these combinations. The combination of an AND gate and a NOT gate is called a NAND gate. The combination of an OR gate with a NOT gate is called a NOR gate.

NAND gate - is the opposite (NOT) of an AND gate’s output. It provides an output (on) except when all the inputs are on.

NOR gate - is the opposite (NOT) of an OR gate’s output. It provides an output only when all inputs are off.

Page 206: Instrumentation and Control

195

Figure 67 illustrates the symbols covering the three basic logic gates plus NAND and NOR gates. The IEEE/ANSI symbols are used most often; however, other symbol conventions are provided in figure 66 for information.

Source: DOE-HDBK-1016/2-93

Figure 67. Basic logic symbols

The AND gate has a common variation called a COINCIDENCE gate. Logic gates are not limited to two inputs. Theoretically, there is no limit to the number of inputs a gate can have. But, as the number of inputs increases, the symbol must be altered to accommodate the increased inputs. There are two basic ways to show multiple inputs. Figure 68 shows both methods, using an OR gate as an example. The symbols used in figure 68 are used extensively in computer logic diagrams.

Page 207: Instrumentation and Control

196

Source: DOE-HDBK-1016/2-93.

Figure 68. Convention for depicting multiple inputs

d. Explain the operation of the three types of time delay devices.

The following is taken from DOE-HDBK-1016/2-93.

When logic diagrams are used to represent start/stop/operate circuits, the diagrams must also be able to symbolize the various timing devices found in the actual circuits. There are three major types of timers. They are (1) the type-one time delay device, (2) the type-two time delay device, and (3) the type-three time delay device.

Upon receipt of the input signal, the type-one time delay device delays the output (on) for the specified period of time, but the output will stop (off) as soon as the input signal is removed, as illustrated by figure 69. The symbol for this type of timer is also illustrated in figure 69.

Source: DOE-HDBK-1016/2-93

Figure 69. Type-one time delay device

Page 208: Instrumentation and Control

197

The type-two time delay de diately upon receipt of the input signal, but the output is maintained only for a specified period of time once the

vice provides an output signal (on) imme

input signal (off) has been removed. Figure 70 illustrates the signal response and the symbolused to denote this type of timer.

Source: DOE-HDBK-1016/2-93

Figure 70. Type two time delay device

Upon receipt of an input signal, type-three time delay devices provide an output signal for a specified period of time, regardless of the duration of the input. Figure 71 illustrates the signal response and the symbol used to denote the timer.

Page 209: Instrumentation and Control

198

Source: DOE-HDBK-1069/2-93

Figure 71. Type-three time delay device

e. Identify the symbols used to denote a logical “1” (or high) and a logical “0” (or low) as used in logic diagrams.

The following is taken from DOE-HDBK-1016/2-93.

When a logic gate has only two inputs, or the logic circuit to be analyzed has only one or two gates, it is fairly easy to remember how a specific gate responds and determine the output of the gate or circuit. But as the number of inputs and/or the complexity of the circuit grows, it becomes more difficult to determine the output of the gate or circuit. Truth tables, as illustrated in figure 72, are tools designed to help solve this problem. A truth table has a column for the input of each gate and a column for the output of each gate. The number of rows needed is based on the number of inputs, so that every combination of input signal is listed (mathematically, the number of rows is 2n, where n = number of inputs). In truth tables, the on and off status of the inputs and outputs is represented using 0s and 1s. As previously stated, 0 = off, and 1 = on.

Page 210: Instrumentation and Control

199

Figure 72 lists truth tables for the seven basic logic gates.

Source: DOE-HDBK-1016/2-93

Figure 72. Truth tables

When reading logic prints, the reader usually must decide the input values to each gate. But occasionally the print will provide information as to the normal state of each logic gate. This is denoted by a symbol similar to the bistable symbol, as shown in figure 72. The symbol is drawn so that the first part of the square wave indicates the normal state of the gate. The

Page 211: Instrumentation and Control

200

second part of the square wave indicates the off-normal state of the gate. Figure 73 also illustrates how this notation is applied.

Source: DOE-HDBK-1016/2-93

Figure 73. Logic gate status notation

f. Given a logic diagram and appropriate information, determine the output of each component and the logic circuit.

g. Given a one-line diagram, identify power sources and loads.

h. Given a one-line diagram or schematic diagram, analyze the effects of a component failure in a system.

i. Given a construction diagram, identify the power supplies.

KSAs f through i are performance based. The Qualifying Official will evaluate their completion.

j. Discuss the origin and purpose of “as-built” drawings.

The following is taken from Ezine Articles, The Importance of (Well Built)As-Built Drawings.

As-built drawings are defined by a number of industries, but in their simplest form, they are drawings that represent the actual built structure. Not as it was designed, but as it actually is today. There is no question that buildings don’t always get built per plan, so even with an

Page 212: Instrumentation and Control

201

existing set of drawings, it helps to prepare as-built drawings, but nothing replaces the actual measured and field verified set of drawings. And nothing will save cost and headaches as much as a thoroughly developed set of as-built drawings.

People always make changes to their designs during the construction process and these changes almost never make it back to a set of revised plans .If the change is made in the field, there’s no reason to update the plans, whose sole purpose is to tell the builder what to build. Also, a building of any vintage may have had additional projects that made alterations to it’s original form that may have affected everything from interior finishes to the core structural system of the building. These projects are often done without permits or plans

Developing As-Built Drawings

Measure everything. These measurements are not just sizes of rooms, but the fully integrated map of every wall, cabinet, fixture, appliance, door, window, etc. Then, measure the vertical elements like door and window sizes, heights, bearing heights, plate and beam heights etc. Measure soffit and fascia details, siding, roof pitches, exterior improvements, slopes in floors, and ceilings. The end result is essentially a set of drawings that depict exactly what is there today.

There are a lot of other things that happen during this process. A number of other systems can be documented while going through the building at this level of detail. Plumbing, mechanical, electrical and structural elements that can be observed are all documented so that any new work can be designed not to conflict with these systems. Structural systems are particularly important - especially if changes are being made to the plan that rely on the integrity of the existing structure or if the structural skeleton of the existing building is to be changed.

As-built drawings allow the engineer to integrate everything known about the building in order to put together architectural changes that work with the existing systems as opposed to ignoring them. This results in projects that are easier to build, less costly, and architecturally integrated so the final outcome is a building that flows and seamlessly transitions from the existing to the new.

k. Describe printed wiring board fabrication and assembly.

The following is taken from the Environmental Protection Agency (EPA), Design for the Environment, Printed Wiring Board Industry.

Printed wiring boards (PWBs) are categorized in several ways. When overall complexity is being considered, they are often categorized in terms of layer counts, or the number of circuit layers present on a single PWB. PWBs are usually classified along layer-count lines into three categories: multilayer, double sided, and single sided. Multilayer PWBs contain more than two layers of circuitry, i.e., at least one layer is embedded in the substrate beneath the surface of the board. A multilayer board may consist of 20 or more interconnected layers, but more common are 4, 6, and 8 layers. Double-sided boards have two interconnected layers and are generally easier to produce than multilayer PWBs, while single-sided PWBs have only one layer of circuitry.

Page 213: Instrumentation and Control

202

PWBs are also categorized by substrate, or base material, type and fall into three basic categories. Rigid PWBs typically are constructed with glass-reinforced epoxy-resin systems that produce a rigid board at thicknesses of less than 0.1 in. (0.062 in. is the most common rigid PWB thickness, although there is a trend toward thinner PWBs). Flexible (or flex) circuits are manufactured on polyimide and polyester substrates that remain flexible at finished thicknesses. Ribbon cables are common flexible circuits. A third category of PWBs consists of boards that are essentially combinations or assemblies of the first two: rigid-flex combinations of one or more rigid PWBs that have one or more flexible circuits laminated to them during the manufacturing process. Three-dimensional circuit assemblies can be created with rigid-flex combinations.

Manufacturing methods are of two types, although hybrid methods exist. Most common is subtractive processing, in which copper is selectively removed from a PWB to form a circuit. Within this process, however, copper and other metals are also added during plating steps. The term “subtractive” refers to the method of image transfer from a photo-tool or image file to a copper circuit on a PWB. Additive processing refers to a process in which an image is formed by selectively adding copper (electrolessly plating onto a substrate an image of a circuit). In a fully additive process, no etching or removal of copper occurs.

23. Instrumentation and control personnel shall demonstrate the ability to read and interpret mechanical diagrams associated with instrumentation and control systems, including: Construction drawings As-built drawings Piping and instrumentation diagrams (P&ID) Assembly drawings

a. Identify the symbols used for: Types of valves Types of valve operators

Types of instrumentation Types of instrument signal controllers and modifiers Types of system components (pumps, etc.) Types and sizes of piping

b. Identify the symbols used to denote the location of instruments, indicators, and controllers.

c. Identify how valve conditions are depicted.

d. Determine the system flow path for a given valve lineup.

Information for this competency is available in DOE-HDBK-1016/1-92, DOE Fundamentals Handbook: Engineering Symbology, Prints, and Drawings, volumes 1 and 2.

Page 214: Instrumentation and Control

203

24. Instrumentation and control personnel shall demonstrate the ability to read and interpret engineering fabrication, construction, and architectural drawings associated with instrumentation and control systems.

a. Given the above drawings, read and interpret the following symbology: Basic dimensional and tolerance Basic fabrication Basic construction Basic architectural

b. Given a drawing and a completed product, compare the product against the specifications on the drawing.

KSAs a and b are performance-based competencies. The Qualifying Official will evaluate their completion.

25. Instrumentation and control personnel shall demonstrate a working level knowledge of the various uses of computers and digital devices used in instrumentation and control systems.

a. Discuss analog to digital (A/D) and digital to analog (D/A) converters.

The following is taken from All About Circuits, Digital-Analog Conversion.

Connecting digital circuitry to sensor devices is simple if the sensor devices are inherently digital themselves. Switches, relays, and encoders are easily interfaced with gate circuits due to the on/off nature of their signals. However, when analog devices are involved, interfacing becomes much more complex. What is needed is a way to electronically translate analog signals into digital (binary) quantities, and vice versa. An analog-to-digital converter, or ADC, performs the former task while a digital-to-analog converter, or DAC, performs the latter.

An ADC inputs an analog electrical signal such as voltage or current and outputs a binary number. In block diagram form, it can be represented as in figure 74.

.

Source: All About Circuits

Figure 74. Analog input

Page 215: Instrumentation and Control

204

A DAC, on the other hand, inputs a binary number and outputs an analog voltage or current signal. In block diagram form, it looks like figure 75.

Source: All About Circuits

Figure 75. Binary input

Together, they are often used in digital systems to provide complete interface with analog sensors and output devices for control systems such as those used in automotive engine controls and as illustrated in figure 76.

Source: All About Circuits

Figure 76. Digital control system with analog input/output

It is much easier to convert a digital signal into an analog signal than it is to do the reverse.

b. Discuss programmable logic controllers (PLC) and distributed control systems (DCS), including use, operation, program control, etc.

The following is taken from Grand Valley State University, Programmable Logic Controllers.

Page 216: Instrumentation and Control

205

When a process is controlled by a PLC, it uses inputs from sensors to make decisions and update outputs to drive actuators, as shown in figure 77. The process is a real process that will change over time. Actuators will drive the system to new states (or modes of operation). This means that the controller is limited by the sensors available; if an input is not available, the controller will have no way to detect a condition.

n re

r battery is low and power was lost, the memory will be corrupt

itely. Unlike normal

t

n issue. Wireless systems are starting to of improved flexibility for both physical and logical

ay be retooled to the extent that several parts of the

.

Source: Grand Valley State University

Figure 77. The separation of controller and process

The control loop is a continuous cycle of the PLC reading inputs, solving the ladder logic,and then changing the outputs. As with any computer, this does not happen instantly. Whepower is initially turned on, the PLC does a quick “sanity check” to ensure that the hardwais working properly. If there is a problem, the PLC will halt and indicate there is an error. Foexample, if the PLC backupand this will result in a fault. If the PLC passes the sanity check, it will then scan (read) all the inputs. After the input values are stored in memory, the ladder logic will be scanned (solved) using the stored values—not the current values. This is done to prevent logic problems when inputs change during the ladder logic scan. When the ladder logic scan is complete, the outputs will be scanned (the output values will be changed). After this, the system goes back to do a sanity check, and the loop continues indefincomputers, the entire program will be run every scan. The typical time required for each ofthe stages is milliseconds.

The following is taken from Waste and Wastewater, Distribution Control System Primer.

A DCS is a control system method that is spread, or distributed, among several different uniprocesses. These processes may be related, as in a water treatment facility, or unrelated, as in a manufacturing plant where many different products are fabricated.

The DCS is typically a hard-wired system that exists within finite boundaries, such as a process plant or within a factory. Wired systems are reliable and are well suited for the typical process environment where flexibility is not abecome popular and hold the promise layout of a facility. An entire process mprocess will be physically moved or removed. Using wireless technology, system reconfiguration is as simple as disabling the station address or downloading the suitable database

Page 217: Instrumentation and Control

206

Whether wired or wireless, DCSs offer the advantage of centralized control, while retainingthe capability of distributed, or local, control. True DCSs use localized control, which is in turn controlled by the operator at a central location.

c. Discuss digital I&C scan rates.

The following is taken from DOE Quality Assurance Exchange, volume 4, issue 1, “DigitInstrumentation and Control Systems.”

al

al

dance for the use of DI&C systems in the

fort to

OE

ng and developing a consensus within the DOE complex that would meet the needs of DOE facilities to ensure adequate protection of workers, the public, and the environment. The goal for conducting industry research and developing a standard is

The following is taken from National Instruments, Scan Rate.

s per second. For example a scan rate of 10 Hz means 0 times per second. The scan rate equals the sample rate divided by

n. For example a scan including 32 channels with a would have a scan rate = (1000 S/s) / (32

ns/s.

demonstrate a working level knowledge ment used to measure process chemistry.

pes of instrumentation used to measure the following process

pH

Chlorine

Digital instrumentation and control (DI&C) systems are being used in DOE’s nuclear facilities for various safety controls, such as for ventilation and process systems. DI&C systems can share code, data transmission, data, and process equipment to a greater degree than analog systems. Although the sharing is the basis for many of the advantages of digitsystems, it also raises a key concern. A design using shared hardware, software, data, and code has the potential to propagate a common-cause or common-mode failure via either software errors, failures of hardware, or any combinations of those, thus defeating the concept of layer of protection (i.e., defense in depth) achieved by the design strategy. At present, DOE does not provide any specific guinuclear safety applications.

The Office of Nuclear Safety Policy and Assistance (HS-21) is taking the lead in an efaddress the above mentioned issues and develop a new standard for DI&C systems in nuclearfacility safety applications. HS-21 has formed a working group with expertise from Dsites and held the first working group meeting in December 2007. The working group is challenged with researchi

December 2008.

Scan rate is the number of scansampling each channel 1the number of channels in the scasampling rate of 1000 sample rate/scans (S/s) S/scan) = 31.25 sca

26. Instrumentation and control personnel shall uipof analytical eq

a. List the tychemistry parameters: Conductivity

Total dissolved solids Silica Turbidity

Page 218: Instrumentation and Control

207

Moisture/humidity Hydrogen Oxygen

Conductivity

current

G = I/R = I (amps) / E (volts)

Since the charge on ions in solution facilities the conductance of electrical current, the conductivity of a solution is proportional to its ion concentration. In some situations, however, conductivity may not correlate directly to concentration. Figure 78 illustrates the relationship between conductivity and ion concentration for two common solutions. Notice that the graph is linear for sodium chloride solution, but not for highly concentrated sulfuric acid. Ionic interactions can alter the linear relationship between conductivity and concentration in some highly concentrated solutions.

The following is taken from Eutech Instruments, Introduction to Conductivity.

Conductivity is the ability of a material to conduct electric current. The principle by which instruments measure conductivity is simple - two plates are placed in the sample, a potentialis applied across the plates (normally a sine wave voltage), and the current is measured. Conductivity (G), the inverse of resistivity (R) is determined from the voltage andvalues according to Ohm’ law.

Source: Eutech Instruments, Introduction to Conductivity

ens (S), formerly called the mho. Since cell

ll constant (L/A), where L is the length of the column of liquid between the electrode and A is

, Measuring pH in Lakes and Streams.

Figure 78. Relationship between conductivity and ion concentration

The basic unit of conductivity is the siemgeometry affects conductivity values, standardized measurements are expressed in specific conductivity units (S/cm) to compensate for variations in electrode dimensions. Specific conductivity (C) is simply the product of measured conductivity (G) and the electrode ce

the area of the electrodes.

pH

The following is taken from the State of Washington, Department of Ecology

Page 219: Instrumentation and Control

208

There are three methods for measuring pH: using a probe and meter, litmus paper, or a fieldkit. The most accurate and reliable method is to use a probe and meter. This method is no lessconvenient than the other methods, but requires a more expensive piece of equipment.

Litmus paper is simply a strip of colored paper that is soaked in sample water. The paper turns a different color depending upon the pH

of the solution. It provides a very coarse measurement of pH. It is fine for making simple determinations, but it is too coarse a

ement for allowing comparisons between sampling dates or stations.

The following is taken from Wilkes University, Total Dissolved Solids.

y a

that the primary dissolved minerals are either a combination of NaCl or KCl. Therefore, the measurement of total dissolved solids by these devices are not

pproximation.

y, inductively ectroscopy (ICP-MS), and inductively coupled plasma-atomic

a

ither GFAAS or ICP-MS. In GFAAS, a water sample is

measur

Total Dissolved Solids

Total dissolved solids can be measured in the field using an electronic pen. Many of these devices actually measure the conductivity of the water, i.e., the ability of the water to carrcharge, and not the actual total dissolved solids. These devices than calculate the total dissolved solids assuming

an accurate measure, but an a

Silica

The following is taken from NNSA, MicroMagazine, “Measuring and Removing Dissolved and Colloidal Silica in Ultrapure Water.”

The amount of reactive and unreactive silica in ultrapure water can be determined by various analytical methods, including gravimetry, colorimetry, graphite furnace atomic absorption spectroscopy (GFAAS), scanning electron microscopy, ion chromatographcoupled plasma-mass spemission spectroscopy.

Measuring Dissolved Silica

The most common method for measuring low levels of dissolved silica (<2 mg/L) is colorimetry. A sample of water is mixed with ammonium molybdate in an acid medium. Any reactive or dissolved silica reacts with the ammonium molybdate to form a yellow silicomolybdate complex. Amino or ascorbic acid is then added to create an intense heteropoly blue color. The degree of blueness is directly proportional to the amount of silicin the sample. This sequential batch sampling method can report up to six measurements per hour and is available from several suppliers as an automated instrument.

Measuring Total Silica

Total silica is measured by evaporized and reduced to individual atoms by thermal decomposition in a graphite tube furnace. The majority of atoms are in the ground state and readily absorb characteristic wavelengths of light. The amount of light absorbed by the silicon atoms indicates the total silica content in the water sample. In ICP-MS, a high-frequency inductive coupling plasma is used to ionize the sample. A nebulizer sprays the water sample into an argon plasma at 6000 K. In the argon plasma, the nebulizer droplets are vaporized, atomized, and ionized. The ions generated are then passed into a mass spectrometer where they are identified and

Page 220: Instrumentation and Control

209

measured, based on their mass-to-charge ratios. Because of the high cost of GFAAS and ICP-MS tools, the measurement of total silica by either of these methods is generally considered an off-line procedure; in most cases, a water sample is transported to a lab for analysis.

Measuring Colloidal Silica

al than even the 50-nanometer

ing is taken from the State of Washington, Department of Ecology, Measuring

property of water – a measure of the amount of t

ly poured into a glass d the result is read directly

as recently become recognized as the more ent for this analysis.

cal

ine (DPD) colorimetric method; ethod;

ic

different operations and maintenance requirements. hic

The amount of nonreactive or colloidal silica can be estimated by subtracting the value of the dissolved silica from that of the total silica. There is no direct method of measuring colloidsilica since the size of most colloidal silica particles is smaller(nm) detection limit of the most sensitive liquid borne particle counters. However, the nonvolatile residue monitor, a recently introduced instrument designed to continuously measure nonvolatile residue, has demonstrated the ability to measure colloidal silica down to <20 nm.2 The colloidal silica is detected as a component of the overall residue obtained from UP water by a spray/evaporation and residue agglomerate recovery technique. This technique cannot distinguish between the various sources of residue—including colloidal and dissolved silica—but it can detect overall residue contamination as low as 10 parts per trillion.

Turbidity

The followTotal Suspended Solids and Turbidity in Lakes and Streams.

Turbidity is a measurement of the opticallight that is scattered and absorbed by particles in the sample. It is a simple measurement tharequires the use of either a nephelometer or Jackson turbidimeter to compare a reference solution to the sample. Turbidity measurement does not require any sample preparation, other than shaking the sample bottle well before analysis. The sample is simptube, placed inside the instrument with a reference solution anfrom the instrument. (The nephelometer haccurate and recommended piece of equipm

Chlorine

The following is taken from EPA, Water and Waste Water Security Product Guide, ChemiSensor - Chlorine Measurement System.

There are several measurement methods currently available to measure chlorine in water samples. These include: N,N-diethyl-p-phenylenediam Iodometric m Amperometric electrodes; and Polarographic membrane sensors.

The chlorine measurement devices here use either the amperometric, DPD, or polarographmembrane sensor methods. It should be noted that there can be differences in the specific type of analyte, the range, and the accuracy of these different measurement methods. In addition, these different methods haveFor example, DPD systems require periodic replenishment of buffers, whereas polarograpsystems do not. Users may want to consider these requirements when choosing the appropriate sensor for their system.

Page 221: Instrumentation and Control

210

Moisture/Humidity

The following is taken from GlobalSpec, About Humidity Measurement Instruments.

Humidity measurement instruments and transducers test for absolute humidity, relative humidity, or dew point in air. The range humidity measurement instruments operate in is typically from 0 to 100 percent humidity. They are sometimes combined with other sensing devices such as temperature sensors.

Humidity measurement instruments and sensors can sense a number of different factors.

ent

liquids.

any technologies for humidity measurement instruments. Capacitive or dielectric ectric properties and

enhances its capacitance. Chilled mirror technology uses a mirror that is chilled to the point

ant.

instruments, a material absorbs water, expands and is measured with a strain gage. Psychrometers, often called wet/dry bulbs, measure relative

Hydrogen

wing is taken from Photohydrogen, Measuring Hydrogen Gas.

n gas both qualitatively and quantitatively, two prominent techniques are available: Clark-type electrodes and gas chromatography. The Clark-type electrode is a

n e

Oxygen

Absolute humidity, expressed as grams of water vapor per cubic meter volume of air, is a measure of the actual amount of water vapor or moisture in the air, regardless of the air's temperature. Relative humidity, expressed as a percent, also measures water vapor, but relative to the temperature of the air. The dew point temperature, which provides a measureof the actual amount of water vapor in the air, is the temperature to which the air must be cooled in order for that air to be saturated and dew to form. Because of the intertwining of atmospheric measurements, humidity measurement instruments are sometimes equipped with pressure and temperature sensors as well. Three main applications for humidity measureminstruments are judging moisture in gases or air, bulk solids or powders, or else if fuels or other

There are minstruments have a material that absorbs moisture, which changes its diel

that moisture starts to condense on it. This temperature is the dew point. With electrolytic technology, moisture is proportional to the current needed to electrolyze it from a desiccFor resistivity or impedance style sensors, a material absorbs moisture, which changes its resistivity or impedance. In strain gage

humidity by gauging the temperature difference between two thermometers, one wet and onedry.

The follo

To measure hydroge

sensitive instrument for studying hydrogen metabolism and allows measurements in the gas phase as well as in aqueous solution.

A gas chromatograph can be hooked up to a small external cell in which metal samples cabe heated up to 1000 ºC. Any hydrogen released from the metal is injected straight into thgas chromatograph, producing a clear peak on the resultant chromatogram.

The following is taken from NASA Tech Briefs, Fiber-Optic Sensors for Measuring Oxygen Dissolved in Water.

Page 222: Instrumentation and Control

211

Fiber-optic sensors can detect oxygen through changes in color. A sensor of this type includes coated with an oxygen-conducting polymer matrix. Specific metal complexes

d reversible binding of oxygen with associated changes in optical r matrix. In operation, the coated fiber is

e, and by use of optoelectronic components coupled with the on spectrum of the metal complexes in the coating is measured. The

m is then translated into the concentration of dissolved oxygen.

Turbidity Chlorine Moisture/humidity

Hydrogen

The following is taken from Eutech Instruments, Introduction to Conductivity.

Conductivity measurements are temperature dependent. The degree to which temperature affects conductivity varies from solution to solution and can be calculated using the following formula:

Gt = Gtcal 1 + α(T-Tcal)

where Gt = conductivity at any temperature T in °C, Gtcal = conductivity at calibration temperature Tcal in °C, α = temperature coefficient of solution at Tcal in °C.

an optical fiber that exhibit rapid anabsorption spectra are immobilized in the polymei e at a test sitmm rsed in water optical fiber, the absorptiabsorption spectru

b. Explain how each of the following process chemistry parameters is measured and converted to a usable signal for alarm, indication, and control: Conductivity pH Total dissolved solids Silica

Oxygen

Conductivity

Page 223: Instrumentation and Control

212

Table 1. Common alphas

Substance at 25 ºC Concentration Alpha HCl 10 wt% 1.56 KCl 10 wt% 1.88

H2SO4 50 wt% 1.93 NaCl 10 wt% 2.14 HF 1.5 wt% 7.20

HNO3 31 wt% 31.0

Source: Eutech Instruments, Introduction to Conductivity

Common alphas (a) are listed in table 1. To determine that α of other solutions, simply measure conductivity at a range of temperatures and graph the change in conductivity versus the change in temperature. Divide the slope of the graph by Gtcal to get α.

All meters have either fixed or adjustable automatic temperature compensation referenced to a standard temperature - usually 25 °C. Most meters with fixed temperature compensation use a α of 2%/°C (the approximate α of NaCl solutions at 25 °C). Meters with adjustable temperature compensation let you to adjust the α to more closely match the α of your measured solution.

Conductivity Meter Calibration and Cell Maintenance

Conductivity meters and cells should be calibrated to a standard solution before using. When selecting a standard, choose one that has the approximate conductivity of the solution to be measured. The conductivity of some common solutions is shown in table 2.

Table 2. Conductivity of some common solutions

Solution Conductivity Absolute pure water 0.055 μS/cm

Power plant boiler water 1.0 μS/cm Good city water 50 μS/cm

Ocean water 53mS/cm

Source: Eutech Instruments, Introduction to Conductivity

pH

The following is taken from DOE-HDBK-1015/2-93.

The reason for controlling pH is to minimize and control corrosion. The presence of excess H+ ions in solution results in an acidic condition. Acidic conditions are detrimental to the materials of construction in a number of ways. An acidic condition in coolant results in processes that are potentially harmful to the system as follows. First, a low pH promotes rapid corrosion by deteriorating or stripping off the protective corrosion film, and second, corrosion products such as ferrous oxide (Fe3 O4 ), which is predominant in the corrosion film, are highly soluble in an acidic solution.

Page 224: Instrumentation and Control

213

Total Dissolved Solids

The following is taken from Wilkes University, Total Dissolved Solids.

In a laboratory setting, the total dissolved solids are measured by filtering a measured volume of sample through a standard glass fiber filter. The filtrate is then added to a preweighed ceramic dish that is placed in a drying oven at a temperature of 103 ºC. After the sample dries, the temperature is increase to 180 ºC to remove occluded water. The total dissolved solids are then the weight of whatever remains in the dish.

The total dissolved solids concentration can be related to the conductivity of the water, but the relationship is not a constant. The relationship between total dissolved solids and conductivity is a function of the type and nature of the dissolved cations and anions in the water and possible the nature of any suspended materials. For example, a NaCl solution and KCl solution with a conductivity of 10000 umhos/cm will not have the sample concentration of NaCl or KCl and they will have different total dissolved solids concentration. Conductivity is measured through the use of a meter and is usually about 100 times the total cations or anions expressed as equivalents and the total dissolved solids in ppm usually ranges from 0.5 to 1.0 times the electrical conductivity.

An elevated total dissolved solids concentration does not mean that the water is a health hazard, but it does mean the water may have aesthetic problems or cause nuisance problems. These problems may be associated with staining, taste, or precipitation. With respect to trace metals, an elevated total dissolved solids may suggest that toxic metals may be present at an elevated level. Water with a very low total dissolved solid concentration may be corrosive and corrosive waters may leak toxic metals such as: copper and lead from the plumbing. This also means that trace metals could be present at levels that may pose a health risk.

Silica

The following is taken from NNSA, MicroMagazine, “Measuring and Removing Dissolved and Colloidal Silica in Ultrapure Water.”

Silica can exist in three physical/chemical forms: monomeric (dissolved/soluble/reactive), polymeric (colloidal/unreactive), and granular (particulate). Ultrapure water may contain silica in any of these three forms, and the forms may change from one to another, depending on the water’s acidity/alkalinity. Dissolved silica affects the thermal oxidation process on the water surface. Colloidal silica, which is defined as having a particle size of less than 100 nm, can act as an unwanted bridge between conducting surfaces. Dissolved silica may also interfere with gate composition and change the electrical characteristics of a device, rendering it useless. Deposits of colloidal silica can also act as nucleation sites for other particles.

Turbidity

The following is taken from Water Action Volunteers, The Basics About Turbidity.

Turbidity can be measured in the laboratory with a meter, called a nephelometer, which measures the amount of light scattered by particles in the water in nephelometric turbidity units.

Page 225: Instrumentation and Control

214

Increased turbidity will limit the amount of light that can enter a waterbody and may therefore limit plant photosynthesis, and thus, oxygen production. This means that the water may have less ability to support aquatic life with increased turbidity.

Chlorine

The following is taken from Water Quality Products, Measuring Chlorine.

DPD is a chemical indicator that reacts with the chlorine present and basically dyes the water a pink color that will indicate the chlorine level. For inline monitoring the difference is how the color change is read. While just the human eye reads the test strip, the inline test measures color change using an electric eye (also called a photodiode), making measurements more consistent and accurate. A light beam is passed through the sample and the amount of light transmitted is dependent on the amount of color in the sample. For example, if the sample is dark in color, less light will be able to pass through the sample and will indicate a high level of chlorine, while a lighter color will allow more light to pass through indicating a lower level of chlorine. Colorimeters can produce an output signal commonly of 4 to 20 milliamp (mA) to monitor, or control remotely. Colorimeters typically detect chlorine in the range of 0 to 5 parts per million (ppm).

A more sophisticated technique to measure chlorine inline is based on the amperometric method. In this method, chlorine is measured by a sensor probe containing the electrolyte potassium chloride (KCl). The probe is placed in the distribution system where water passes by. The chlorine present in the water moves across the membrane on the bottom of the probe and reacts with the KCl to generate an electric current. The probe measures the current produced to determine the level of chlorine. The stronger the current, the higher the level will be of present chlorine. This system is also capable of remote monitoring and/or control, using 4 to 20 mA output. This system can measure chlorine levels from 0 to 20 ppm.

Moisture/Humidity

The following is taken from GlobalSpec, About Humidity Measurement Instruments

One critical specification for Capacitive or dielectric instruments is the humidity or moisture range to be measured or else the dew point range. Humidity and moisture accuracy is expressed in terms of percentage of measurement. The dew point accuracy, since this is a temperature reading, is expressed as a variance in temperature output.

Outputs from humidity measurement instruments can be analog current, voltage, or frequency; digital, including computer signals; or a switch or alarm. They can have analog, digital or video type displays and can have a number of different form factors. They can be standard sensors or transducers, or a simple gauge or indicator. They can also be various types of instruments, whether handheld, bench top or mounted.

In addition to pressure and temperature compensation, humidity measurement instruments can have a number of features to make them more useful or easier to use. These can include data logging, event triggering, self-testing, self-calibration, and battery power.

Hydrogen

The following is taken from DOE-HDBK-1015/2-93.

Page 226: Instrumentation and Control

215

Because the presence of dissolved oxygen contributes to most mechanisms of corrosion, the concentration of oxygen is controlled and reduced by the addition of scavenging agents in most facilities. Hydrogen gas (H2) and hydrazine are the scavenging agents normally used to eliminate dissolved oxygen from the reactor coolant system. These substances scavenge oxygen by the following reactions:

2H2+O2

radiation

radiation2H2O

N2H4+O2→2H2 O+N2

Because hydrazine decomposes rapidly at temperatures above about 200 ºF hydrogen gas is used as the scavenging agent during hot operation and hydrazine is used when the reactor coolant system is cooled below 200 ºF.

The decomposition reactions of hydrazine pose additional problems in chemistry control. Even if sufficient hydrazine were added to overcome the loss due to decomposition, instability of coolant pH would probably occur by the following reactions.

2N2+5O2+2 H2O→4HNO3 (acid)

3H2+ N2+2 H2O→2NH4OH (base)

The use of hydrogen gas at temperatures above 200 ºF precludes the generation of the compounds formed. In addition, hydrogen is compatible with the high flux levels present in the reactor core. Accordingly, advantage may be taken of the reversibility of the radiolytic decomposition of water. The following reaction illustrates the scavenging process using hydrogen:

2H2+O2

radiation

radiation2H2O

As indicated, the reaction is an equilibrium process and will therefore depend on the relative concentrations of the reactants and the products. By maintaining an excess of hydrogen (H2), the reaction is forced to shift to the right and theoretically eliminates any dissolved oxygen that may be present. As long as an inventory of H2 is present in the coolant, dissolved oxygen will be eliminated or forced to recombine immediately after radiolytic decomposition, thereby being unavailable for corrosion reactions.

A boiling water reactor (BWR) facility is susceptible to corrosion, resulting from dissolved oxygen, in the same reactions as are present in a pressurized water reactor (PWR). However, because of the design of these facilities, the use of chemical additives is prohibited because continuous concentration would occur in the reactor vessel due to boiling. Boiling would result in a plating out process, and the irradiation of these concentrated additives or impurities would create an extreme environment of radiation levels as well as adverse corrosion locations.

Page 227: Instrumentation and Control

216

By the very nature of operation of a BWR facility, the buildup of high concentrations of dissolved oxygen is prevented. Because boiling is occurring in the reactor vessel and the steam generated is used in various processes and subsequently condensed, removal of dissolved gases is a continual process. As stated, boiling is an effective means of removing gases from a solution. If we were to compare the oxygen content of the steam and the water in a BWR, we would find typical concentrations of 100 parts per billion (ppb) to 300 ppb in the water and 10,000 ppb to 30,000 ppb in the steam. This concentration process is continuous during operation, and the dissolved oxygen remains in the gaseous state and is subsequently removed in the condensing units along with other noncondensible gases. As with PWR facilities, BWR facilities minimize the introduction of dissolved oxygen by pretreating makeup water by some method. The large oxygen concentrations measured in the steam system result primarily from the radiolysis of water, and as operation is continued, the equilibrium concentration of 100 ppb to 300 ppb is established. This concentration of oxygen is consistent with the objective of minimizing corrosion.

Oxygen

The following is taken from DOE-HDBK-1015/2-93.

Control of the dissolved oxygen content in a reactor facility system is of paramount importance because of its contribution to increased corrosion. The base reactions of concern regarding high concentrations of dissolved oxygen are the following:

3Fe + 2O2 = Fe3O4

4FE + 3O2 = 2Fe2O3

This corrosion film, ferrous oxide, is also known as magnetite and is a black, generally tightly-adherent film that provides a protective function to surfaces within the facility.

These reactions are dependent on the concentration of oxygen and temperature. The first reaction is predominant at high temperatures (above 400 ºF) in the presence of lower oxygen concentrations.

The second reaction occurs at temperatures below about 400 ºF in the presence of higher oxygen concentrations. Ferric oxide (Fe2 O3) is more commonly known as rust and is generally a reddish color. This corrosion product adheres loosely to surfaces and is therefore easily removed and transported throughout the system for subsequent deposition and possible irradiation. In either of the reactions, the corrosion rate is accelerated by increased concentrations of dissolved O2 and can be aggravated further by the presence of other substances that may be in the system.

c. Describe the environmental concerns that can affect the accuracy and reliability of analytical equipment used to measure process chemistry.

The following is taken from DOE-HDBK-1013/1-92.

Ambient temperature variations will affect the accuracy and reliability of analytical equipment used to measure process chemistry. Variations in ambient temperature can directly

Page 228: Instrumentation and Control

217

affect the resistance of components in a bridge circuit and the resistance of the reference junction for a thermocouple.

In addition, ambient temperature variations can affect the calibration of electric/electronic equipment. The effects of temperature variations are reduced by the design of the circuitry and by maintaining the equipment in the proper environment.

The presence of humidity will also affect most analytical equipment, especially electronic equipment. High humidity causes moisture to collect on the equipment. This moisture can cause short circuits, grounds, and corrosion, which in turn may damage components. The effects due to humidity are controlled by maintaining the equipment in the proper environment.

d. Discuss the failure modes of the various types of analytical equipment used to measure process chemistry.

The types of analytical equipment used to measure process chemistry varies from site to site. The local Qualifying Official will evaluate the completion of this KSA.

e. Describe the methods used to test each of the different types of instruments used to measure process chemistry.

The methods used to test instruments to measure process chemistry vary from site to site. The local Qualifying Official will evaluate the completion of this KSA.

27. Instrumentation and control personnel shall demonstrate a familiarity level knowledge of maintenance management practices related to instrumentation and control activities.

a. Define each of the following maintenance-related terms and explain their relationship to each other: Corrective Preventive Predictive Reliability centered

The following definitions are taken from DOE G 433.1-1.

Corrective

Corrective maintenance refers to the repair of failed or malfunctioning equipment, systems, or facilities to restore the intended function or design condition. This maintenance does not result in significant extension of expected useful life.

Preventive

Preventive maintenance refers to predictive, periodic, and planned maintenance actions taken to maintain a piece of equipment within design operating conditions and extend its life.

Page 229: Instrumentation and Control

218

Predictive

Predictive maintenance refers to maintenance activities involving continuous or periodic monitoring and diagnosis to forecast equipment failure.

Reliability Centered

Reliability-centered maintenance is a proactive systematic decision logic tree approach to identify or revise preventive maintenance tasks or plans to preserve or promptly restore operability, reliability, and availability of facility SSCs; or to prevent failures and reduce risk through types of maintenance action and frequency selection to ensure high performance. Reliability-centered maintenance is the performance of scheduled maintenance for complex equipment, quantified by the relationship of preventive maintenance to reliability and the benefits of reliability to safety and cost reduction through the optimization of maintenance task/frequency intervals. The concept relies on empirical maintenance task/frequency intervals to make determinations about real applicable data suggesting an effective interval for task accomplishment. The approach taken to establish a logical path for each functional failure is that each functional failure, failure effect, and failure cause be processed through the logic so that a judgment can be made as to the necessity of the task, and includes (1) reporting preventive maintenance activities, plans, and schedules; (2) optimizing/calculating the preventive maintenance interval by balancing availability, reliability, and cost; (3) ranking preventive maintenance tasks; (4) accessing preventive maintenance information from piping and instrumentation drawings; (5) accessing preventive maintenance and other maintenance data; (6) listing recurring failure modes/parts, including failure to start and failure to run; (7) calculating and monitoring SSC availability; (8) accessing preventive maintenance procedures, and (9) keeping track of preventive maintenance cost.

b. Discuss the importance of maintaining a proper balance of maintenance strategies to optimize cost-effective maintenance that achieves high equipment reliability.

According to DOE G 433.1-1, a proper balance of corrective and preventive maintenance should be employed to provide a high degree of confidence that property degradation is identified and corrected, that equipment life is optimized, and that the maintenance program is cost-effective.

c. Discuss the importance of maintaining a maintenance history and identify typical maintenance performance indicators.

Maintenance histories typically consist of a set of computer software modules and equipment databases containing facility data with the capability to process the data for facilities maintenance management functions. This set provides historical data, report writing capabilities, job analysis, and more. The data describe equipment, parts, jobs, crafts, costs, step-by-step instructions, and other information involved in the maintenance effort. This information may be stored, viewed, analyzed, reproduced, and updated with just a few keystrokes. The maintenance-related functions typically include maintenance cost and reliability data facility/equipment inventory facility/equipment history work input control

Page 230: Instrumentation and Control

219

job estimating work scheduling and tracking preventive and predictive maintenance facility inspection and assessment material management utilities management

Performance indicators should include a systematic analysis of an SSC or facility performance to categorize and establish operating history that enables graphic depiction and simulation of results in measurable terms, such as cause and effect, failures, production output or capacity, cost,or other subjects of interest.

d. Discuss the relationship between maintenance and conduct of operations, quality assurance, and configuration management.

The following descriptions are taken from DOE G 433.1-1.

Conduct of Operations

Because of the complex nature of operations and maintenance at DOE nuclear facilities and the interdependence of job activities, the way workers perform day-to-day activities to meet facility mission objectives should be formalized by established rules governing their work. For every operation, whether it be routine, infrequent, abnormal, emergency or casualty, a procedure should be in place so workers know how the operation should be conducted. Good procedures should produce good products. Verbatim compliance with procedures should be mandated policy. Compliance with procedures that are wrong or simply nonexistent could lead to failure. Knowing what to do when things go wrong is the fundamental key to understanding formal conduct of operations. Conduct of operations is the formality needed to ensure that workers know the status and configuration of systems and equipment at the facility during all phases of operations and maintenance.

Quality Assurance

Contractors responsible for a nuclear facility are required to implement a DOE-approved quality assurance program (QAP) according to 10 CFR 830, subpart A, “Quality Assurance” (the QA rule). Consequently, a QAP that applies to the maintenance management program should already be in place at each DOE nuclear facility. The QA rule includes ten criteria for the management, performance, and assessment of work so that it meets requirements. One of the criteria explicitly requires that items be maintained to prevent their damage, loss, or deterioration. A maintenance management program established using DOE G 433.1-1 will satisfy that explicit criterion and address the other QA criteria in an integrated fashion.

Examples of the maintenance management program elements that integrate and satisfy the QA criteria include organization—program, training, and qualification; condition of facilities and equipment—inspection and test; maintenance documentation—documents and records; work-control system—work processes; and maintenance evaluation and analysis—quality improvement, independent assessment,

and management assessment.

Page 231: Instrumentation and Control

220

A maintenance management program that integrates the QA criteria will perform continuing analysis and surveillance of the facility activities for safety, mission objectives, economics, system function, and compliance. It should provide constant oversight of nuclear operations, maintenance and program performance and should make the results available to contractor and DOE management or external regulators through the following: Reports on organization and system performance Identification of maintenance problem areas System corrective action plans Assurance that corrective actions have been accomplished to prevent recurrence of

the root cause of problems on a continuing basis, thereby assuring compliance on a continuing basis

DOE nuclear facility QA programs should be an integrated management plan for fitting all hardware and administrative controls together in a framework that provides for management visibility of the operation, clear decision-making authority, and identification of decision makers according to the matter under consideration, identification of interfaces and communication channels and all control points. The details of the program should be in written form and provide attributes of such a program that apply to all modes of facility operation, accident prevention, and accident mitigation. The administrative attributes intended to ensure that all SSCs required for safe operation of the facility are present should be identified in the facility documented safety analysis and should be classified by quality application such that they can be properly controlled.

All external organizations interfacing and performing work affecting the quality of a DOE nuclear facility design and operation should be identified in writing. This includes those organizations providing criteria, designs, specifications, and technical detail to cover the preparation, review, and approval of documents involving design and operational interfaces.

Persons and organizations performing independent assessment of the maintenance management program must have sufficient internal authority and organizational freedom to identify quality problems; initiate, recommend, or provide solutions; and verify implementation of solutions for QA.

Configuration Management

Configuration management is a discipline that applies technical and administrative direction and surveillance to identify and document the physical characteristics of a facility. It is a method of doing business that maintains consistency among design requirements, physical configuration, and facility documentation. It audits to verify conformance to specifications and related documentation. Basically, it boils down to doing all those things you know you should have been doing all along to properly manage and control physical and functional items at a facility.

Such a program can be broken down into five basic programmatic elements. 1. Program management 2. Design requirements 3. Document control 4. Change control 5. Assessments

Page 232: Instrumentation and Control

221

An important aspect of a configuration management program is the assurance that the design basis of a DOE nuclear facility is established, documented, and maintained. The facility SSCs and computer software should conform to approved design requirements, and any changes to them must be minimized through an integrated management review process, with established approval criteria. This will help to establish that the operations of the facility are reliable if personnel operating the facility are knowledgeable about changes through timely review and training. Proposed changes should be thoroughly evaluated to determine their impact on other hardware and documents. Such changes should be reviewed and approved by appropriate, responsible managers before implementation. This way, the program maintains a consistency between the documents of all departments and organizations (i.e., design, inspection, operations, maintenance, testing, or training). Safety, mission, economic impact, and benefit can be fully analyzed through the full range of review and approval contained in the program.

e. Discuss the requirements for the receipt and inspection of parts, materials, and equipment.

The following is taken from DOE G 433.1-1.

All phases of receiving, inspecting, handling, storing, retrieving, and issuing equipment, parts, and materials for maintenance should be covered by effectively implemented policies and procedures from the time an item is received until it is installed in the facility.

Many personnel at a facility are involved in some portion of the stores operation. They should be aware of the correct process to receive, inspect, handle, and store facility material and equipment so that it is easily retrievable and usable when issued. Therefore, policies should be established that address these functions. These policies must be understood by stores personnel and other organizations that interface with them, such as purchasing, QA, quality control (QC), engineering, radiological protection, operations, safety, and maintenance. Procedures should be prepared that specifically describe the responsibilities and the techniques for receiving, inspecting, handling, storing, retrieving, and issuing material from stores. QA/QC aspects of the stores function should be incorporated into these procedures.

Procurement is the first step in ensuring that the correct parts and materials are available, usable, and readily retrievable for issuance for maintenance activities.

When parts, materials, and equipment are received, stores personnel should inspect them before they are accepted for storage or are used. This inspection is conducted to verify that the items delivered agree with the approved purchase documentation, are packaged in accordance with purchase order specifications, have necessary product control requirements furnished by the vendor (such as special storage or shelf-life information), and appear to be in good condition. In the case of safety items and designated critical items important to reliable facility operations, stores personnel should inspect them to ensure that the vendor has supplied what was ordered, that the necessary formal documentation has accompanied the shipment or is otherwise on hand, and that items have been received in an acceptable condition. Technical staff and maintenance personnel may be needed to assist in the inspection of more complicated parts, materials, and equipment.

Page 233: Instrumentation and Control

222

Technical staff and QC personnel should approve any deviation from design specifications of material or equipment received before the item is accepted into the stores system. They should also approve any upgrade of material or equipment from a nonsafety to a safety category. An acceptance tag or label placed on the received material may be used to signify that the receiving inspection was performed and that the applicable requirements have been met. A separate receiving and inspection area, as well as a separate holding area, should be provided. The latter area is used to hold material and equipment that has not been officially received into the stores system because of nonconformance.

Nonconforming material must also be clearly tagged or labeled to prevent it from inadvertently being issued. A tracking or follow-up method should be established to ensure that problems with nonconforming items are promptly resolved.

During receipt inspection, the designated organization should ensure that special storage instructions have been addressed. Before final acceptance of an item, the designated organization should ensure that the necessary purchase order instructions and requirements are completed, such as the following: The tickler file has been updated. Appropriate items have been added to the preventive maintenance program. Appropriate inspection instructions are clearly defined.

Inspection and test activities should be selectively and judiciously applied to new, repaired, and replacement items, on the basis of risk to safety and/or importance to reliable capacity, to ensure items will perform as expected.

Plant engineering should develop a process for providing data sheets that form the basis for procurement of safety class items and other major purchases (i.e., equipment and construction projects). These data sheets should provide procurement information critical parameters and their acceptance criteria unique or special testing requirements/methods reorder instructions suspect/counterfeit parts information

Items or parameter values that do not satisfy established acceptance criteria should be rejected. Plant engineering approval should be required for other disposition.

Nonconforming items should be clearly identified; segregated from normal items to prevent inadvertent use; documented on a nonconformance report and/or a defective or substandard material

report; and tracked and dispositioned as soon as practical by the applicable authority.

Routine inspections performed by appropriate personnel should include the following: Ensuring that packaging is appropriate (as designated on the purchase order when

specified), is undamaged, and/or has not deteriorated

Page 234: Instrumentation and Control

223

Ensuring color, count, shape, size, part number, model number, manufacturer/vendor name, etc., are as specified on the purchase order

Ensuring shelf-life and other time-environment requirements have not been violated Ensuring date and time of receipt are logged for regular follow-up review during the

storage period Ensuring specified vendor documentation, in the quantities required by the purchase

order, exists

Special inspections should be performed on safety-class items, safety-significant SSCs, and other items when designated by the requisitioner. Special inspections should be performed by the organization specified on the

requisition. Special inspection requirements for items not involving engineering data sheets

should be defined by the requisitioner. Special inspections normally require

o formal quality records of all measured data o formal date inspection performed o identification of the individual and the organization performing the inspection o accept/reject status identification o signature of the applicable authority to approve the status

Items receiving special inspection (especially safety-class items and safety-significant SSCs) should be appropriately identified and segregated from normal stock to indicate status and ensure proper application.

Before becoming available for use or restock, materials and equipment that have been repaired and/or stored in the plant should require the same inspection defined for the original purchase and/or appropriate for its intended application as specified by engineering.

Stored items that are affected by time-environment should be regularly checked by designated personnel; expired or otherwise jeopardized items should be removed from normal storage until dispositioned by the proper authority.

An acceptance tag should be placed on the item after satisfactory receipt inspection. The tag should be legibly marked to indicate whether an item has any type of special storage requirements. This provides the user, requestor, or storeroom personnel with an easy method to ensure special storage control requirements are satisfied. The tag may cross-reference a particular entry in a file system (tickler file) for further instructions.

A method should be developed to accept material that has been repaired or reworked by the facility maintenance organization. Whenever materials or parts are repaired or reworked, suitable testing and inspection requirements should be specified by design engineering to ensure that the materials or parts perform acceptably when placed in service. This method should also address material that has been issued and is sent back to stores for reissuance.

Warehouse documents should be updated to reflect receipt of the material and any shelf-life or preventive maintenance requirements.

Page 235: Instrumentation and Control

224

f. Describe the difference between temporary and permanent repairs/work and the requirements and controls in place to prevent inadvertent modifications (consider both the hardware and software control elements of the configuration management program).

The following is taken from DOE G 433.1-1.

Temporary repairs are temporary modifications to the facility that allow equipment to remain in or be returned to service in a condition that is not the same as the original design specification. Prior to implementation, temporary repairs should receive a safety review in accordance with the facility temporary modification program to ensure the adequacy of the repair and its effect on personnel and equipment safety and reliability. Temporary repairs should be tracked after their completion for consideration of permanent repairs. Permanent corrective action should be taken as soon as practicable.

g. Describe the mechanisms for feedback of relevant information, such as trend analysis and instrumentation performance/reliability data, to identify necessary program modifications.

The following is taken from DOE G 433.1-1.

The predictive maintenance coordinator should compare recently acquired data with previous history data to detect any indicated change in equipment condition trends. If degradation indicates integrity of operating equipment may be endangered or if action criteria are being approached, the predictive maintenance coordinator should initiate one or more of the following actions. Coordinate with the data originator to determine whether corrective action has been

initiated. Validate the trend analysis/conclusion. Request additional testing or monitoring be performed to confirm the suspected

deficient condition. (Any of the various predictive maintenance techniques available may be used to obtain additional confirmatory information, if appropriate.)

Initiate action to have the defective equipment scheduled for repair. Recommend revisions to preventive maintenance procedures and/or schedules, if

appropriate. Acquire new equipment baseline data to verify correction of problems and to

establish new reference points.

h. Review a contractor preventive maintenance activity and describe the preventive maintenance factors to be considered as the activity is planned.

This is a performance-based KSA. The Qualifying Official will evaluate its completion.

i. Discuss the importance of post-maintenance testing and the elements of an effective post-maintenance testing program.

The following is taken from DOE-STD-1039-93.

Page 236: Instrumentation and Control

225

Before returning equipment to service following maintenance, the equipment should be tested to demonstrate that it is capable of performing its intended function. This serves two purposes. The testing should verify that the maintenance was performed correctly. It should also prove that no problems were introduced as a result of the maintenance activities.

The maintenance work control package or maintenance procedure should specify the type and duration of post-maintenance testing required. For some facilities, the specific requirements to prove operability of safety-related systems are identified in the technical safety requirements. An engineering evaluation should determine whether additional testing or different methods are required whenever the scope of work is changed, e.g., when additional work is performed to correct a previously undisclosed problem that is discovered during maintenance. All equipment functions that may have been affected by the maintenance should be tested.

Operation of the equipment for testing should be performed by qualified operations personnel in accordance with approved procedures. Maintenance personnel should monitor the testing. The operations supervisor is ultimately responsible for ensuring that the testing proves the operability of the equipment.

28. Instrumentation and control personnel shall demonstrate the ability to evaluate the adequacy of local compliance of I&C systems with applicable design criteria (such as ISA 84.01, ISA 67.04.01, IEEE 603-1998, NEC or the Uniform Building Code) used by site/facility.

a. Discuss the purpose and application of the criteria contained in the applicable I&C design standards.

ANSI/ISA-84.00.01-2004 part 2 provides guidance on the specification, design, installation, operation, and maintenance of safety instrumented functions and related safety instrumented systems.

ANSI/ISA-67.04.01-2006, Setpoints for Nuclear Safety-Related Instrumentation, develops a basis for establishing nuclear safety-related instrumentation setpoints. The standard addresses known contributing errors in the channel from the process (including the primary element and the sensor) through and including the final setpoint device.

ANSI/ IEEE 603-1998, IEEE Standard Criteria for Safety Systems for Nuclear Power Generating Stations, establishes minimum functional design criteria for the power, instrumentation, and control portions of nuclear power generating station safety systems. These criteria are established to provide a means for promoting safe practices for design and evaluation of safety system performance and reliability.

However, adhering to these criteria will not necessarily fully establish the adequacy of any safety system’s functional performance and reliability; nonetheless, omission of any of these criteria will, in most instances, be an indication of safety system inadequacy.

Additional information may be obtained from the Uniform Building Codes used at the site.

Page 237: Instrumentation and Control

226

b. Discuss what constitutes a safety-class or safety-significant item as represented by the various I&C design standards.

The following is taken from DOE G 433.1-1.

Safety-class items are SSCs, including primary environmental monitors and portions of process systems, whose failure could adversely affect the environment or safety and health of the public as identified by safety analyses.

Safety significant items are SSCs not designated as safety-class SSCs but whose preventive or mitigative function is a major contributor to defense in depth (i.e., prevention of uncontrolled material releases) and/or worker safety as determined from hazard analysis.

c. Discuss the application of single-failure criteria to instrumentation and control systems.

IEEE Std.-379-2000, Application of the Single-Failure Criterion to Nuclear Power Generating Station Safety Systems, was prepared on September 21, 2000. The standard provides guidance on the application of the single-failure criterion to the electrical power, instrumentation, and control portions of nuclear power plant safety systems.

The systems include the actuation and protection systems, as well as the sense, command, and execute features of the power system. The guidance in this standard has been developed for electrical systems. However, where the interface with mechanical systems is unavoidable (e.g., sensing lines), the mechanical portions are considered to be a part of the electrical system with which they interface.

d. Discuss the environmental qualification criteria for instrumentation and control system equipment.

The following is taken from 10 CFR 50.49.

The instrumentation and control system equipment environmental qualification program must include and be based on the following considerations: Temperature and pressure. The time-dependent temperature and pressure at the

location of the equipment important to safety must be established for the most severe design basis accident during or following which this equipment is required to remain functional.

Humidity. Humidity during design basis accidents must be considered. Chemical effects. The composition of chemicals used must be at least as severe as

that resulting from the most limiting mode of plant operation (e.g., containment spray, emergency core cooling, or recirculation from containment sump). If the composition of the chemical spray can be affected by equipment malfunctions, the most severe chemical spray environment that results from a single failure in the spray system must be assumed.

Radiation. The radiation environment must be based on the type of radiation, the total dose expected during normal operation over the installed life of the equipment, and the radiation environment associated with the most severe design basis accident during or following which the equipment is required to remain functional, including

Page 238: Instrumentation and Control

227

the radiation resulting from recirculating fluids for equipment located near the recirculating lines and including dose-rate effects.

Aging. Equipment qualified by test must be preconditioned by natural or artificial (accelerated) aging to its end-of-installed life condition. Consideration must be given to all significant types of degradation that can have an effect on the functional capability of the equipment. If preconditioning to an end-of-installed life condition is not practicable, the equipment may be preconditioned to a shorter designated life. The equipment must be replaced or refurbished at the end of this designated life unless ongoing qualification demonstrates that the item has additional life.

Submergence (if equipment will be subject to being submerged). Synergistic effects. Synergistic effects must be considered when these effects are

believed to have a significant effect on equipment performance. Margins. Margins must be applied to account for unquantified uncertainty, such as the

effects of production variations and inaccuracies in test instruments. These margins are in addition to any conservatisms applied during the derivation of local environmental conditions of the equipment unless these conservatisms can be quantified and shown to contain appropriate margins.

e. Discuss the requirements for testing capability for instrumentation and control systems as it relates to the applicable design standards.

The following is taken from 10 CFR 50.49.

Each item of instrumentation and control equipment important to safety must be qualified by one of the following methods: Testing of an identical item of equipment under identical conditions or under similar

conditions with a supporting analysis to show that the equipment to be qualified is acceptable

Testing of a similar item of equipment with a supporting analysis to show that the equipment to be qualified is acceptable

Experience with identical or similar equipment under similar conditions with a supporting analysis to show that the equipment to be qualified is acceptable

Analysis in combination with partial type test data that supports the analytical assumptions and conclusions

f. Discuss the criteria for generic human factors engineering considerations in the applicable design standards, as they apply to instrumentation and control systems.

The following is taken from DOE-STD-1104-2004.

Determining the impacts of human factors requires considering the degree to which process safety depends on human performance, whether workers can reasonably be expected to perform the tasks they are assigned, and whether procedures and training adequately guide and prepare workers to perform tasks correctly. The human factors assessment could include listing potential human-error causes of accidents; examining the location of and access to critical safety instruments, alarms, and equipment; or reviewing critical procedures used by operators and maintenance personnel. For critical operations, it may be necessary to perform

Page 239: Instrumentation and Control

228

task hazard analyses to analyze the operator/machine interface in process control rooms or other work locations to adequately evaluate human factor impacts.

g. Discuss criteria for developing the proper setpoints for interlocks and alarms.

For information regarding developing setpoints see ANSI/ISA-67.04.01-2000 Setpoints for Nuclear Safety-Related Instrumentation.

h. Given a design package for an instrumentation and control system for a mechanical, civil, structural, or electrical application, determine the general design criteria requirements for the instrumentation and controls.

This is a performance-based KSA. The Qualifying Official will evaluate its completion.

29. I&C personnel designated as vital safety systems subject matter experts shall demonstrate an expert level of knowledge on their level of understanding and approach to overseeing contractor activities by using the requirements of DOE O 420.1, Facility Safety, and the guidance in DOE-STD-1073-93, Guide for Operational Configuration Management Program, by performing system assessments addressing the following elements:

[Note: DOE-STD-1073-93 has been replaced by DOE-STD-1073-2003, Configuration Management.]

a. Determine that adequate and comprehensive documentation exists for the system design basis and safety basis (e.g., Documented Safety Analysis, Technical Safety Requirements, etc.).

b. Assess the adequacy of the system’s ability to perform in accordance with the system design basis and safety basis.

c. Determine how system operability and reliability are supported by the maintenance program and system upgrades/modifications.

d. Determine if the field installation is maintained consistent with the documented design during maintenance and modifications.

e. Confirm that knowledgeable and qualified technical personnel are monitoring, operating, and maintaining the safety system in an appropriate manner.

Elements a–e are performance-based KSAs. The Qualifying Official will evaluate their completion.

30. Instrumentation and control personnel shall demonstrate a familiarity level knowledge of DOE O 430.1, Life Cycle Asset Management.

[Note: DOE O 430.1, Life Cycle Asset Management, has been replaced by DOE O 430.1B, Real Property Asset Management. The KSAs for this competency will address DOE O 430.1B.]

Page 240: Instrumentation and Control

229

a. Discuss the purpose, scope, and application of DOE O 430.1B, Real Property Asset Management. Include in this discussion key terms, essential elements, and personnel responsibilities and authorities.

Purpose and Scope

The purpose of DOE O 430.1B is to establish a corporate, holistic, and performance-based approach to real property life-cycle asset management that links real property asset planning, programming, budgeting, and evaluation to program mission projections and performance outcomes. To accomplish the objective, DOE O 430.1B identifies requirements and establishes reporting mechanisms and responsibilities for real property asset management.

Application

DOE O 430.1B applies to all DOE elements listed in DOE O 430.1B, attachment 1, with responsibility for real property assets, including NNSA.

The contractor requirements document (CRD), attachment 2 of DOE O 430.1B, sets forth the requirements of the Order that must apply to all site/facility management contracts that include the CRD.

Key Terms and Essential Elements

The key terms and essential elements for the major real property asset management functional components are planning real estate acquisition maintenance and recapitalization disposition and long-term stewardship (LTS) value engineering(VE) performance goals and measures.

Each of these elements will be described briefly. For additional details please refer to DOE O 430.1B.

Planning

Planning is the overarching function within real property asset management that integrates the other functions of acquisition, real property utilization, maintenance, recapitalization, disposition, and LTS into a coordinated effort to ensure that current and future mission needs are met. Planning is dependent on clear objectives, sound data, and effective communication.

Real Estate

The real estate function encompasses several key activities over the life cycle of real property assets. These activities involve acquisition by lease or purchase; planning and management, including taking inventory, making assignments, conducting utilization surveys, and tracking assets; screening for excess real property assets; and disposal of real property assets.

Page 241: Instrumentation and Control

230

Acquisition

Acquisition of real property assets through construction must be planned and accomplished to meet program mission projections. Acquisition planning should include life-cycle cost considerations.

Maintenance and Recapitalization

Real property assets will be maintained in a manner that promotes operational safety, worker health, environmental protection and compliance, property preservation, and cost-effectiveness while meeting the program missions. This requires a balanced approach that not only sustains the assets but also provides for their recapitalization.

Disposition and LTS

Planning for disposition must be initiated when real property assets are identified as no longer required for current or future programs. Disposition includes stabilizing, preparing for reuse, deactivating, decommissioning, decontaminating, dismantling, demolishing, and/or disposing of real property assets.

Value Engineering

VE is an organized effort directed at analyzing the functions of systems, equipment, facilities, services, and supplies for the purpose of achieving the essential functions at the lowest life-cycle cost consistent with required performance, reliability, quality, maintainability, environmental protection, and safety.

Performance Goals and Measures

The DOE planning, programming, budgeting, and evaluation system requires that performance measures be established that link performance of program goals and budgets to outputs and outcomes. All DOE elements must develop real property asset performance measures commensurate with their duties and responsibilities. The Lead Program Secretarial Offices/Cognizant Secretarial Offices (LPSOs/CSOs) must establish annual performance targets for their real property assets and state their expected performance outputs and outcomes in their annual direction and guidance. Site-specific measures must be developed by each site/field manager to assess the level to which the LPSO-/CSO-established outputs and outcomes have been attained.

b. Discuss the project management terminology for which definitions are provided in DOE O 430.1B, Real Property Asset Management.

The following are some of the terms that are directly related to project management taken from attachment 3 of DOE O 430.1B. For additional definitions please refer to the Order.

Disposition Baseline

The disposition baseline is the technical, programmatic, and regulatory information that serves as input to the disposition preparation and planning process, and is essential to meet the goal of maximum risk reduction and long-term cost savings in the elimination of excess real property assets.

Page 242: Instrumentation and Control

231

Facility Condition Index

The facility condition index is the ratio of the cost of deferred maintenance to the facility’s replacement plant value. The cost of deferred maintenance deficiencies is determined by condition assessment inspections. The facilities information management system data is used to calculate the facility condition index.

Institutional General Plant Project (IGPP)

A IGPP consists of miscellaneous, minor (i.e., up to $5 million) new construction of a general institutional nature benefiting multiple cost objectives and required for general purpose site-wide needs. IGPPs do not include projects whose benefit can directly be attributed to a specific or single program. IGPPs are consistent with the general plant project threshold and capitalization criteria in the DOE Accounting Handbook, chapter 10. Example IGPP projects are multiprogrammatic/interdisciplinary scientific laboratory, institutional training facility, site-wide maintenance facilities and utilities, new roads, multiprogrammatic office space, multiprogrammatic facilities required for “quality of life” improvements, and replacement or upgrade to a core utility, land, and facility that is no longer reliable.

Integrated Facilities and Infrastructure (IFI) Crosscut Budget.

The IFI crosscut budget is a crosscut budget exhibit that has been developed to ensure sustained improvement in real property management. It constitutes, with the exception of new mission line-item projects, the resources required to implement a ten-year site plan. This crosscut budget identifies renovation, recapitalization, maintenance, and demolition projects for buildings and facilities by program and site. The IFI budget also includes reports on direct maintenance and an estimate of indirect maintenance and repair funding requirements. The IFI is developed in conjunction with the Department’s budgeting process and submitted annually with the Presidential budget to Congress.

Land-Use Planning

Land-use planning is a formal, integrated planning process that is used to identify an appropriate mix of land uses at each site and guidelines for development.

Life-Cycle Cost

Life-cycle cost is the sum total of the direct, indirect, recurring, nonrecurring, and other related costs incurred or estimated to be incurred in the design, development, production, operation, maintenance, support, and final disposition of real property over its anticipated useful life span.

Long-Term Stewardship

Long-term stewardship includes the physical controls, institutions, information, and other mechanisms needed to ensure protection of people and the environment at sites where DOE has completed or plans to complete cleanup (e.g., landfill closures, remedial actions, removal actions, and facility stabilization). This concept includes land-use controls, monitoring, maintenance, and information management.

Page 243: Instrumentation and Control

232

Ten-Year Site Plan (TYSP)

The TYSP is a planning document that identifies the site’s annual and strategic program requirements and priorities, and links these to real property asset requirements. Real property asset requirements must be consistent with program missions, budgets, and planning estimates. Planning employs costing efficiencies, eliminates excess buildings, consolidates operations where practicable, and addresses mission-critical requirements through an appropriate mix of recapitalization, new construction, and disposal of excess facilities.

Total Estimated Costs (TEC)

The TEC of a project is the specific cost of the project, including cost of land and land rights; engineering, design, and inspection costs; direct and indirect construction costs; and the cost of initial equipment necessary to place the plant or installation in operation.

Value Engineering

VE is an organized effort directed at analyzing the functions of systems, equipment, facilities, services, and supplies for the purpose of achieving the essential functions at the lowest life-cycle cost consistent with required performance, reliability, quality, and safety. Value analysis, value management, and value control are considered synonymous with VE.

c. Discuss in detail the roles played by various management levels within the Department as they relate to the project management system.

The following is taken from DOE O 430.1B.

A qualified DOE Federal facilities management staff must be assigned at cognizant Headquarters offices and field elements to provide for implementation of DOE O 430.1B and to ensure accountability. The following paragraphs describe the responsibilities and authorities for effective management of DOE real property assets and establish accountabilities for real property asset management from planning and acquisition through operations and disposal. LPSOs issue program missions, budgets, and planning estimates covering a 10-year

planning horizon for site infrastructure and LPSO-related real property assets and approve TYSPs and land-use management plans for their sites.

CSOs/PSOs issue program missions, budgets, and planning estimates covering a 10-year planning horizon for their program-related work and/or real property assets and approve elements of TYSPs related to their programmatic responsibilities at related sites.

Site/field managers ensure mission resource requirements for real property assets, including their plans and budgets, are prepared to meet the program missions, budgets, and planning estimates, and the results are documented in the TYSP. Site/field managers perform a key role coordinating program and tenant activities and real property asset needs at the site.

TYSPs are submitted by site/field managers to the LPSOs/CSOs/PSOs as the plans for real property assets at the sites. TYSPs support LPSO/CSO/PSO programming decisions regarding real property assets and subsequent site budget requests.

Page 244: Instrumentation and Control

233

The Office of Engineering and Construction Management develops policies and procedures for real property asset management and provides corporate oversight for implementation.

d. Discuss the purpose of “critical decisions.” Include in this discussion the responsible authorities for critical decisions.

[Note: Critical decisions are not discussed in DOE O 430.1B. The following information is taken from DOE O 413.3A.]

The five critical decisions are major milestones approved by the Secretarial Acquisition Executive (SEC) or Acquisition Executive that establish the mission need, the recommended alternative, the acquisition strategy, the performance baseline, and other essential elements required to ensure that the project meets applicable mission, design, security, and safety requirements. Each critical decision marks an increase in commitment of resources by the Department and requires successful completion of the preceding phase or critical decision. Collectively, the critical decisions affirm the following: There is a need that cannot be met through other than material means. The selected alternative and approach is the optimum solution. Definitive scope, schedule and cost baselines have been developed. The project is ready for implementation. The project is ready for turnover or transition to operations.

The amount of time between decisions will vary. Projects may quickly proceed through the early critical decisions due to a lack of complexity, the presence of constraints that reduce available alternatives, or the absence of significant technology and developmental requirements. In these cases, more than one critical decision may be approved simultaneously. Conversely, there may be a need to split a critical decision.

The Deputy Secretary serves as the SEC for the Department and promulgates Department-wide policy and direction. The critical decision authorities, thresholds and delegations are identified in table 3.

Page 245: Instrumentation and Control

234

Table 3. Critical decision authority thresholds

Critical Decision Authority Total Project Cost Thresholds

Life Cycle Clean-up Project Cost Thresholds

Secretarial Acquisition Executive

≥ $750M (or any project on an exception basis when

designated by the SEC)

No delegation authority

≥ $1B (or any clean-up project on an

exception basis when designation by the SEC)

Delegation authority to Program Secretarial Office

on an exception basis

Under Secretaries ≥ $100M and < $750M (or any project on an exception basis when

designated by the Under Secretaries)

Delegation authority to Program Secretarial Officer

for projects ≤ $400M

Not Applicable

Program Secretarial Officer ≥ $20M and < $100M

Delegation authority to a program manager or field

organization manager. CD-0 may not be delegated below

the Program Secretarial Officer

< $1B

Delegation to Headquarters or field SEC. CD-0 may not

be delegated below the Program Secretarial Officer

Chief Information Officer > $5M and ≤ $750M

Departmental Information Technology Projects

No delegation authority

Not Applicable

Source: DOE O 413.3A

e. Describe the process by which projects are designated.

The following is taken from DOE O 413.3A.

Most projects are designated into either major system projects or non-major system projects. Major system projects are projects with a total project cost greater than or equal to $750M or environmental management clean-up projects with an environmental management total project cost of $1B. All major system project critical decisions must be proposed by the appropriate PSO and approved by the Deputy Secretary as DOE’s designated SEC before proceeding to the next project phase or critical decision.

Page 246: Instrumentation and Control

235

Non-major projects are projects with a total project cost less than $750M or environmental management clean-up projects with an environmental management total project cost less than $1B. The designated Acquisition Executive must approve all non-major system project critical decisions, except for CD-0, which cannot be delegated below the Program Secretarial Officer.

Although most DOE projects are designated major or non-major projects, there are some unique project situations where customizing the process is beneficial, such as the following:

Environmental Management Cleanup Projects

These projects include environmental clean-up work, environmental management clean-up projects, and environmental restoration projects. These “projects” could include hundreds of release sites at the lowest level, that are aggregated into Environmental Protection Agency-regulated operable units or performance baseline summaries. These are further aggregated into a total site-wide program. Decontamination and decommissioning activities may also be aggregated in the same manner. Other projects may range from a single project for a closure site, to disposition of a waste stream, to a grouping of similar work activities or geographic locations within a large site.

Information Technology Projects

Departmental information technology capital assets will be defined by the Deputy Secretary and are characterized by (1) their widespread and continuous use among multiple departmental organizational units; (2) their vital importance to accomplishing the department’s business functions; and (3) their special importance to agency senior management. Information technology projects are not meant to encompass process or control systems that are an integral part of a broader project. Additionally, this policy is applicable to commercial-off-the-shelf acquisitions.

The DOE critical decision process is normally tailored for information technology projects to provide sufficient flexibility during the phased or spiral approach required for these projects.

Generally, system design and development using a combined CD-2/3 process is required to support various procurement alternatives and software/firmware implementation in lieu of conventional construction. This tailored approach does not reduce or eliminate management, performance to baselines or technical requirements. The Federal project director uses this framework to guide development of documentation to plan, manage, and execute the project and designate appropriate design approvals at the integrated project team level.

Design-Build Projects

Design-build is a project delivery method where a single contract is awarded for both design and construction. Design-build can be used most successfully with projects that have well-defined requirements, are not complex, and have limited risks. This applies to projects that have few “unknowns” or new technology requirements, little to no program or system integration, and are not unique or first-of-a-kind.

Projects such as road building, administrative facilities, fire stations, and/or replication of previously accomplished projects are generally the most appropriate for design-build

Page 247: Instrumentation and Control

236

consideration. The design-build approach requires the development of a functional design and clearly stated operating requirements that provide sufficient information to allow prospective contractors to prepare bids or proposals, but also allows them the flexibility to implement innovative design and construction approaches, value engineering, and other cost-and time-savings initiatives. This overall objective of the design-build approach is to reduce the total cost to the government and deliver projects more quickly than the traditional design-bid-build approach.

f. Describe the phases of a typical project.

The following is taken from DOE O 413.3A.

The phases of a typical project are initiation, definition, execution, and closeout. Each of these phases is described in the following paragraphs.

Initiation Phase

During this phase, pre-conceptual planning activities focus on the program’s strategic goals and objectives. User needs are analyzed for consistency with the Department’s strategic plan, Congressional direction, administration initiatives, and political and legal issues. One outcome of the analysis could be a determination that a user need exists that cannot be met through other than material means. This outcome leads to the development and approval of a mission need statement. The information developed during this phase also provides the basis for the project engineering and design budget request when preliminary design activities are planned.

Definition Phase

Upon approval of mission need, the project enters the definition phase where alternative concepts, based on user requirements, risks, costs, and other constraints, are analyzed to arrive at a recommended alternative. This is accomplished using systems engineering and other techniques and tools such as alternatives analysis and VE. This ensures the recommended alternative provides the essential functions and capability at optimum life-cycle cost, consistent with required performance, scope, schedule, cost, security, and environment, safety, and health considerations. During this phase, the required VE assessment is completed, and more detailed planning is accomplished, which further defines required capabilities. The products produced by this planning provide the detail necessary to develop a range of estimates for the project cost and schedule.

Execution Phase

Following the definition phase, preliminary design activities mark the beginning of the execution phase. Systems engineering continues to balance requirements, cost, schedule, and other factors to optimize the design, cost, and capabilities that satisfy the mission need. Engineering and design continue until the project has a sufficiently mature design that can be implemented successfully within a firm performance baseline.

During this phase, the initial design concepts and the preliminary design are developed into detailed and final designs and plans. These plans are used to procure or manufacture components, fabricate subsystems, or construct, remediate, decommission, or demolish facilities. Major activities in this phase include

Page 248: Instrumentation and Control

237

establishing performance measurement baselines and implementing change control procedures;

satisfying environmental and safety requirements; obtaining approved National Environmental Policy Act documentation, if required,

prior to the start of detail or final design; continuing to refine and optimize cost estimates, schedules, and designs; approving the final design for procurement and implementation; identifying and addressing security concerns.

Execution comprises the longest and most costly phase of a project. VE is implemented throughout the project execution phase to ensure the most effective solutions are implemented.

If the delivery method is design-build versus design-bid-build and a single contract is awarded for both design and construction, it may be necessary to tailor the project’s execution process to allow the project team to propose cost-effective innovative approaches that reduce project duration and cost.

Transition/Closeout Phase

When the project nears completion and has progressed into formal transition and commissioning, which generally includes final testing, inspection, and documentation, the project is prepared for operation, long-term care, or closeout. The nature of the transition and its timing depends on the type of project and the requirements that were identified subsequent to the mission need.

g. Explain the purpose and use of a project execution plan.

The following is taken from DOE O 413.3A.

The project execution plan is the core document for management of a project. The Federal project director is responsible for the preparation of this document. It establishes the policies and procedures to be followed to manage and control project planning, initiation, definition, execution, and transition/closeout, and uses the outcomes and outputs from all project planning processes, integrating them into a formally approved document. A project execution plan includes an accurate reflection of how the project is to be accomplished, resource requirements, technical considerations, risk management, configuration management, and roles and responsibilities. A preliminary project execution plan is required to support CD-1. This document continues to be refined throughout a project’s life cycle and revisions are documented through the configuration management process.

h. Discuss the role of configuration management as it relates to project management.

The following is taken from DOE O 413.3A.

A configuration management process must be established that controls changes to the physical configuration of project facilities, structures, systems, and components in compliance with ANSI/Electronics Industry Alliance (EIA)-649, National Consensus

Page 249: Instrumentation and Control

238

Standard for Configuration Management. This process must also ensure that the configuration is in agreement with the performance objectives identified in the technical baseline and the approved quality assurance plan.

i. Discuss the use of safety plans in the management of projects.

The following is taken from DOE M 413.3-1.

Delivering a facility or a modification that can meet its mission requirements while maintaining the safety of the public, the workers, and the environment is essential for a successful project.

For those facilities that contain or will contain hazardous materials, continuous development and integration of the safety analysis as an integral part of design is required. This is accomplished using integrated safety management within the design. The task of developing the safety basis for the facility often drives design and operational requirements. The early integration of safety requirements in the design permits the development of timely and cost-effective solutions from the start. However, providing a design that only meets all of the specified safety requirements may not be adequate for implementing a safety-through-design approach.

j. Discuss the relationship between work breakdown structure (WBS) and cost and schedule.

The following is taken from DOE G 430.1-1, chapter 5.

A WBS shows the relationship of all elements of a project. This provides a sound basis for cost and schedule control.

During that period of a project’s life from its inception to a completed project, a number of diverse financial activities must take place. These activities include cost estimating, budgeting, accounting, reporting, controlling and auditing. A WBS establishes a common frame of reference for relating job tasks to each other and relating project costs at the summary level of detail.

Since the WBS divides the package into work packages, it can also be used to interrelate the schedule and costs. The work packages or their activities can be used as the schedule’s activities. This enables resource loading of a schedule, resource budgeting against time, and the development of a variety of cost budgets plotted against time.

k. Describe the purpose and use of work packages and/or planning packages.

The following is taken from Project Management Knowledge, Work Packages.

A work package is a portion of the work breakdown structure that allows project management to define the steps necessary for completion of the work package. A work package can be thought of as a mini project that when combined with other work package units, form the completed project. An individual work package contains essential steps involved in completion of the work package, along with a deadline by which each of the

Page 250: Instrumentation and Control

239

steps must be completed in order for project management to stay on track. A work package may in itself be thought of as a deliverable. Work packages allow for simultaneous work on many different components of a project at the same time by multiple teams. Each team follows the steps defined in the work package and completes them by the specified deadline. When all teams have finished their individual work packages, the whole project comes together with seamless integration. Completion of a work package is most often overseen by a specific person, whether it is a manager, supervisor, team leader, or a designated team member. A work package is usually the bottom tier of the project management process. The following is taken from Project Management Knowledge, Planning Packages.

The project management concept of a planning package provides an invaluable means of categorization for the team project management leader in the efforts to effectively group and itemize a number of essential elements of the project. Specifically speaking, the planning package concept refers to the project’s particular work breakdown structure component which resides on the grand and total scheme below the already deciphered and already broken down control account, however lacking a carefully crafted and elaborately detailed itemization of the project’s defined schedule activities, yet nonetheless containing a fairly lucid delineation of the known work content to be performed and conducted during the time detailed. The planning package may be constructed and or outlined at any point but it is ideal to do so early in the process.

l. Describe the purpose of schedules, and discuss the use of milestones and activities.

The following is taken from Stanford University, Land, Buildings, and Real Estate, Schedule Development.

The cornerstone of any well-managed project is the schedule, which is a tool that identifies and organizes project tasks into a sequence of events that then form a project management plan. The process of building the schedule enables the project manager to identify the risk points, understand the proper linkage of events, assists in resource planning, and allows the project manager to establish goals for the team and the project.

The benefits of a well-constructed schedule are numerous. It becomes the framework to organize the project team to strive to common goals, it provides the project manager the tool to manage to a desired outcome, and it provides a means to measure performance of the team. A quality schedule includes planned control points that better ensure the success rate of the project. The specific control points that must be inserted and honored include, but are not limited to: Budget development and cost checks. This includes time to redesign in order to

realign the scope and budget. Management approvals.

The following is taken from DOE O 413.1A.

Critical milestones, in chronological order, provide the key tasks and target dates representing broad events required to correct a problem and its root cause(s).

Page 251: Instrumentation and Control

240

All critical milestones must list an original target activity completion date by month and year. This is the date included in the original action plan as the proposed completion of the milestone, and it must stay the same through closure. A revised target or actual completion date denoted by month and year must be listed if the milestone target completion date has been revised, in which case the most current

date must be listed; the milestone has been completed, in which case the completion month and year must

be listed.

Critical milestones completed during the current year should correspond with planned activities indicated on the prior year’s plan.

m. Describe the critical path method of scheduling.

The following is taken from DOE G 413.3-5.

The critical path is the longest path through a network schedule that consequently defines the shortest possible duration for completing a project. This path and its duration are determined by performing forward and backward passes through the network diagram based on the defined activity sequence and estimated activity durations.

n. Explain the concept of a project management baseline and describe the four baselines used in project management.

[Note: DOE Orders, standards, and guides define three baselines used in project management.]

The following is taken from DOE G 413.3-5.

Traditionally, in DOE a project, “baseline” comprised three components—technical, cost, and schedule—each of which is intimately related to the others. The requirement to establish key performance parameters has become a prominent feature of DOE project management.

31. Instrumentation and control personnel shall demonstrate the ability to evaluate the adequacy of local compliance with applicable Instrumentation, Systems, and Automation Society (ISA) standards related to process control instrumentation and I&C systems (consider entire instrument loops, including sensors, transmitters, controllers, final elements).

a. Discuss the purpose, scope, general content, and application of the ISA standards.

The following is taken from the ISA Web page.

The public policy goal of ISA is to serve the public and the automation control professional community by promoting automation control excellence through public policy activities; developing instrumentation, systems, and automation positions on public policy

issues;

Page 252: Instrumentation and Control

241

integrating and focusing local, state, national, and global ISA resources to impact public policy efficiently and effectively;

maintaining a quick response capability for short notice issues; undertaking agenda-setting and pro-active public policy activities; educating and assisting public policymakers to better understand how the automation

and control community impacts legislative and regulatory proposals; providing coalition-building leadership in order to increase the impact of ISA’s public

policy positions; promoting the understanding and participation of ISA members in public policy

activities.

b. Given a project involving process control instrumentation, identify the proper ISA standards necessary to effectively evaluate that element of the project.

This is a performance-based KSA. The Qualifying Official will evaluate its completion.

c. Discuss what constitutes acceptable contractor performance consistent with the requirements of the above standards.

d. Given the design drawings and specifications for a process control system, verify compliance with the appropriate ISA standards.

Contractor requirements vary from site to site. The Qualifying Official will evaluate the completion of these KSAs.

32. Instrumentation and control personnel shall demonstrate a familiarity level knowledge of DOE O 414.1A, Quality Assurance, as it applies to instrument and control systems.

[Note: DOE O 414.1A, has been replaced by DOE O 414.1C, Quality Assurance.]

a. Describe the types of documents related to instrumentation and control that should be controlled by a document control system.

The following is taken from DOE G 414.1-2A.

Documents and records are required in order to effectively manage, perform, and assess work. Documents and records should include applicable requirements to indicate that work (including safety) has been properly specified and accomplished. Management should identify any documents and records that must be developed and controlled. Management should commit the resources necessary to accomplish the document and record requirements.

Documents are required by organizations, projects, or programs to control policy, administrative, and/or technical information. A document may describe work to be done, data to be used at different locations or by different people, or, in changing situations, data to be controlled from time to time for reference purposes. A document control system should be established to supply such documents necessary for personnel to safely and correctly perform their assigned responsibilities. Document systems ensure that the mechanisms developed to

Page 253: Instrumentation and Control

242

implement the safety management functions of DOE P 450.4 are properly prepared, controlled, and available for managers and workers.

Knowledge of specific documents that are related to I&C at your facility will be evaluated by the local Qualifying Official.

b. Discuss the requirements for revision and distribution of controlled documents.

The following is taken from DOE-STD-1073-2003.

Controlled Document Distribution List

Contractors should establish and maintain controlled document distribution lists. The lists should identify both the documents that are to be controlled and the individuals who are holders of copies of those documents (“controlled document users,” or as identified in 10 CFR 830, appendix A, paragraph G.5, the “authorized users list”). The document owner should determine the list of controlled document users to be included on the controlled document list. The distribution list should include any satellite document distribution centers. To ensure they are included on the distribution list for revised documents, controlled document users should inform the document owners of their need for specific documents. Whenever a document is superseded by a new revision, a copy of the new revision must be sent to each controlled document user of the document.

Document Changes

The organization responsible for document control should be notified of any need to change a document as soon as that need is identified and approved, typically through the change control or work control processes. A document change notice may be used for this purpose. The organization responsible for document control should provide a receipt acknowledging the notification that a document should be changed. The organization responsible for document control should take the appropriate action to update the document and record the status in the document control database.

The contractor should specifically identify in the change control process what constitutes a minor change (e.g., inconsequential, editorial corrections). Major changes to controlled documents are any changes that are not defined as minor changes. Major changes to controlled documents must be reviewed and approved by the document owners. The configuration management process may specify a simpler review for minor changes.

Pending Changes

Pending changes are changes that have been approved for which the associated documents have not yet been updated and distributed. The organization responsible for document control should provide notice of pending changes to the controlled document users for the applicable documents. A notice of the pending change should also be attached to, or appropriately referenced on, the affected master document, in order to alert anyone requesting a copy of the document.

Page 254: Instrumentation and Control

243

Incorporate Changes

Contractors must incorporate approved changes into controlled documents in a timely manner. The contractor should control and limit the backlog of changes that have not been incorporated. Contractors should consider incorporating small changes in batches, where appropriate. When there is a large backlog of changes that have not been incorporated on a document, the documents may not reflect the physical facility or the approved safety basis consequently diminishing the value of the documents. Document control procedures should specify the limit of the number of changes that may be outstanding for a document before the document is revised. That limit may vary depending upon the type of document, document priority, complexity of the changes, and the degree of overlap of those changes.

Distribution of Documents

Whenever a document is issued or superseded by a new revision, the contractor organization responsible for document control must send a copy of the new revision to each controlled document user of the document, along with a request for written receipt acknowledgment. Contractors can facilitate the return of receipt acknowledgments by sending a receipt acknowledgment form with the revised document. Document control procedures should specify guidelines for the maximum time between issuance of the revised controlled document and distribution.

The recipients (controlled document users) should update their copy of the document (for example, by inserting changed pages), and discard any obsolete pages or copies of documents. The recipient must return a written acknowledgment of receipt to the document control organization. The controlled document users should periodically review controlled copies in use to ensure their accuracy and their consistency with the master copies.

c. Discuss the determination of calibration frequency for measuring and test equipment.

The following is taken from DOE G-10 CFR 835/E1.

A formal instrument calibration should be performed on each instrument at least annually.

The calibration should include a pre-calibration inspection/test normally followed by a documented calibration over the entire range of the instrument. Calibration for ranges where the instrument is not intended to be used need not be conducted, as long as the specific limitations on instrument use are clearly marked on the instrument. The frequency of calibration should be adjusted to the use of the instrument and its durability. The National Conference of Standards Laboratories (NCSL), Recommended Practice RP-1, Establishment and Adjustment of Calibration Intervals indicates that more frequent calibrations should be performed when greater than 15 percent of instruments are returned out of calibration at the selected calibration frequency (a minimum of annually). This should include all returned instruments that fail a source check in the field. NCSL/RP-1 also indicates that if, for those instruments for which the calibration cycle had been more frequent than annual, fewer than 5 percent are out of calibration, then the cycle may be lengthened but is not to exceed 1 year.

Page 255: Instrumentation and Control

244

d. Describe the effect of using inappropriate calibration standards on test equipment.

The following is taken from NFPA 70B.

Data loss and unsafe work conditions can result from the use of inappropriate calibration standards. All test equipment should be calibrated at regular intervals to ensure the validity of the data obtained. In order to get valid test results, it might be necessary to regulate the power input to the test equipment for proper waveform and frequency and to eliminate voltage surges.

e. Discuss the key elements of the procurement process for instrument and control systems as described in the DOE quality assurance Order.

The following is taken from DOE O 414.1C.

The following key elements pertain to the procurement process for electrical systems: Procure items and services that meet established requirements and perform as

specified. Evaluate and select prospective suppliers on the basis of specified criteria. Establish and implement processes to ensure that approved suppliers continue to

provide acceptable items and services.

f. Discuss calibration techniques for various instrument types.

The following is taken from DOE-STD-1054-93.

Measurement and testing equipment (M&TE) be calibrated using reference standards (secondary or working) whose calibration has a known valid relationship to nationally recognized standards or accepted values of natural physical constants. If national standards do not exist, the basis for calibration should be documented. The reference standard used should have an accuracy at least four times greater than the device under test. If this accuracy ratio cannot be met, analysis of the errors should be estimated to provide a valid uncertainty of the calibration process.

ANSI N323-1978, Radiation Protection Instrumentation Test and Calibration, provides requirements on the calibration of portable instruments. The reproducibility of the instrument readings should be known prior to making calibration adjustments. This is particularly important if the instrument has failed to pass a periodic performance test (i.e., the instrument response varies by more than ±20 percent from a set of reference readings using a check source) or if the instrument has been repaired.

The effect of energy dependence, temperature, humidity, ambient pressure, and source-to-detector geometry should be known when performing the primary calibration. Primary calibration should be performed at least annually.

g. Discuss the correct actions to be taken for an instrument found out of calibration.

The following is taken from DOE-STD-1054-93.

Page 256: Instrumentation and Control

245

(M&TE) found to exceed required calibration tolerance or that has been subjected to possible damage should be identified as rejected. When repairs are required to standards or other measuring and test equipment they shall be re-calibrated to the original requirements prior to being returned to normal service. When calibration/certification is performed, the as-found condition and/or minor adjustments to the measuring and test equipment shall be noted as part of the equipment history information.

h. Discuss instrument calibration data trending.

The following is taken from National Institute of Standards (NIST)/SEMATECH e-Handbook of Statistical Methods.

The process of collecting data for creating the calibration curve is critical to the success of the calibration program. General rules for designing calibration experiments apply, and guidelines that are adequate for the calibration models are given below.

A minimum of 5 reference standards is required for a linear calibration curve, and 10 reference standards should be adequate for more complicated calibration models.

The optimal strategy in selecting the reference standards is to space the reference standards at points corresponding to equal increments on the y-axis, covering the range of the instrument. Frequently, this strategy is not realistic because the person producing the reference materials is often not the same as the person who is creating the calibration curve. Spacing the reference standards at equal intervals on the x-axis is a good alternative.

If the instrument is not to be calibrated over its entire range, but only over a very short range for a specific application, then it may not be necessary to develop a complete calibration curve, and a bracketing technique will provide satisfactory results. The bracketing technique assumes that the instrument is linear over the interval of interest, and, in this case, only two reference standards are required—one at each end of the interval.

A minimum of two measurements on each reference standard is required and four is recommended. The repetitions should be separated in time by days or weeks. These repetitions provide the data for determining whether a candidate model is adequate for calibrating the instrument.

i. Discuss the quality assurance measures required for each of the following elements of a project: Design control Procurement control Instructions, procedures, and drawings Document control Control of purchased material, equipment, and services Identification, control, and traceability of materials, parts, and components Control of special processes Inspection Test control Calibration and control of test and measurement equipment Handling, storage, shipping, and preservation Inspection, test, and operating status

Page 257: Instrumentation and Control

246

Nonconformity of material, parts, or components Corrective action Quality assurance records Audits

The following descriptions are taken from DOE G 414.1-2A unless stated otherwise.

Design Control

The design process should translate design input into design output documents that are technically correct and compliant with the end-user’s requirements. Aspects critical to the performance, safety, or reliability of the designed items should be identified during the design phase. Design output documents should be prepared to support other processes, such as dose and risk assessments, procurement, manufacturing, assembly, construction, testing, inspection, maintenance, and decommissioning.

Technical and administrative design interfaces should be identified and methods established for their control.

Computer software used to originate or analyze design solutions during the design process should be validated for the intended use; otherwise, status of the code validation should be identified and documented prior to use.

The design organization should perform design analyses and checks to ensure that design output documents meet design input requirements and that any changes have been approved and documented.

Procurement Control

The procurement process should ensure that items and/or services provided by suppliers meet the requirements and expectations of the end user. The procurement process should be planned and controlled to ensure that the end user’s requirements are accurately, completely, and clearly communicated to

the supplier; supplier, designer, and end-user requirements are met during the production phase; the proper product is delivered on time and maintained until use.

Procurement processes should prevent introduction of suspect/counterfeit items and provide a method to detect them before they are released for use.

Instructions, Procedures, and Drawings

Procedures, work instructions, or other appropriate means used to define work processes should be documented and controlled. The scope and detail of documentation should be commensurate with the complexity and importance of the work, the skills required to perform the work, the hazards and risks or consequences of quality problems in the product, process, or service, and the need to meet regulatory and contract requirements. Control of processes, skills, hazards, and equipment should be clearly specified, understood, and fully documented. This serves as the point of integration for integrated safety management and quality assurance into an integrated management approach.

Page 258: Instrumentation and Control

247

Workers are responsible for the quality of their work. Workers should do their work correctly the first time, in accordance with established procedures and work instructions. Because workers are the best resource for contributing ideas for improving work processes, products, and services, they should be involved in work process design, process evaluation (pre-job briefing), and providing the feedback necessary for improvement..

Document Control

A document control system should be in place to control the preparation, review, approval, issue, control, and revision of documents. Documents are required by organizations, projects, or programs to control policy and administrative and/or technical information. A document may describe work to be done, data to be used at different locations or by different people, or, in changing situations, data to be controlled from time to time for reference purposes. The document control system should be established to supply the documents necessary for personnel to safely and correctly perform their assigned responsibilities. Document control systems ensure that the mechanisms developed to implement the safety management functions are properly prepared, controlled, and available for use.

Control of Purchased Material, Equipment, and Services

Work processes should be established and implemented to protect items in accordance with specified technical standards and administrative controls to prevent damage, loss, or deterioration. Work processes should specify protective methods for sensitive or perishable items, such as special handling, shipping, and storage controls for precision instrumentation and limited shelf-life items, and for items requiring special protective environmental controls, such as temperature and humidity controls.

Identification, Control, and Traceability of Materials, Parts, and Components

A process for the identification and control of items should be established and implemented to prevent the use of incorrect or defective items identify and control suspect/counterfeit items provide for the control and maintenance of items

“Item” is a collective term that may include hardware, samples, software, or data. The identification and control process should apply from manufacture or receipt through delivery, installation, or use. The process should also provide for the identification and configuration control of installed or replacement items in accordance with specified requirements. Physical identification of items is preferred. Suitable identification information includes the unique part, lot, heat, model, version, or serial numbers on the item, or in records traceable to the item, or both.

Control of Special Processes

The following is taken from ASME, Continuing Evolution of U.S. Nuclear Quality Assurance Principles, Practices and Requirements

Special processes that control or verify quality, such as those used in welding, heat treating, and nondestructive examination, shall be performed by qualified personnel using qualified procedures in accordance with specified requirements.

Page 259: Instrumentation and Control

248

Quality assurance programs, as defined by Nuclear Quality Assurance (NQA)-1, generally apply to the control classical, special processes, such as welding and nondestructive examination.

There may be other special processes that meet the intent of the NQA-1 definition and that also need special skills, training, procedures, and environmental controls to assure quality.

Inspection and Test Control

Inspections and tests are performed to verify that physical and functional aspects of items, services, and processes meet requirements and are fit for use and acceptance. Inspections and tests should be identified early in the design process and specified in the design output documents.

For items that are stored, the type of item and the length of time it is expected to remain in storage should be considered during inspection planning.

Personnel should check items prior to their use to ensure that the items are correct and suitable for their intended application. Personnel should check an item’s process output to verify that it meets or exceeds specified requirements.

The inspection/test process should identify the status of items, services, and processes requiring examination to ensure only those with acceptable inspection and test results are used. The process should provide for review and reinspection/retest of changed inspection/test parameters.

Final inspections are usually distinct from inspections conducted during the work process. Final inspection confirms the item, the service, or the process is ready for acceptance testing and/or operation. As such, it includes completeness, cleanliness, identification/markings, calibration, alignment/adjustment, adequate records, or other characteristics indicating conformance to requirements.

Inspection/test planning should be performed. Appropriate sections of approved codes or standards may be used for acceptance requirements and inspection/test methods.

At a minimum, inspection/test planning should contain provisions for the following: Identification of characteristics to be examined Required qualifications of individuals who perform the examination A description of examination methods, including equipment and calibration

requirements Acceptance and rejection criteria Suitable environmental conditions Required safety measures Mandatory hold points, when applicable

Inspections/tests should be performed by technically qualified personnel who have the authority to access appropriate information and facilities to verify acceptance. These qualified personnel should be independent of the activities being inspected/tested and should have the freedom to report the results of the inspections/tests. Inspection/test results should

Page 260: Instrumentation and Control

249

be evaluated and verified by authorized personnel to document that all requirements have been satisfied. Final acceptance should be verified and documented by the organization having final responsibility for the item or process.

Inspection and test records should, at a minimum, identify the item tested the date of the test the tester or data recorder observations results and acceptability action taken concerning any quality problems noted

Calibration and Control of Test and Measurement Equipment

M&TE used for inspections, tests, monitoring, and data collection should be calibrated, maintained, and controlled using a documented process. M&TE should be checked before use to ensure that it is of the proper type, range, accuracy, and precision and that it is uniquely identified and traceable to its calibration data. Procedures should be established for testing, retesting, adjusting, and recalibrating M&TE. M&TE should be calibrated to standards traceable to the National Institute of Standards and Technology or other nationally recognized standards when appropriate. If no nationally recognized standard exists, the basis for calibration should be documented. When calibrating and/or checking M&TE for use, consideration should be given to computer programs that are part of the M&TE.

The use of each item of M&TE should be traceable and associated with the item of M&TE. This is because measurements and tests performed with the M&TE may need to be reevaluated if the item of M&TE is subsequently found to be out of its acceptable calibration range. Systems that rely on recording the identity of the M&TE in work packages are ineffective because it is usually almost impossible to review all work packages to identify each use of a particular item of M&TE.

Handling, Storage, Shipping, and Preservation

Work processes should be established and implemented to protect items in accordance with specified technical standards and administrative controls to prevent the items’ damage, loss, or deterioration. Work processes should specify protective methods for sensitive or perishable items, such as special handling, shipping, and storage controls for precision instrumentation and limited shelf-life items, and for items requiring special protective environmental controls, such as temperature and humidity controls.

Inspection, Test, and Operating Status

The procurement process should provide for identifying the need for inspections and tests. Requirements for inspections and tests should be obtained from design documents. Inspections should be adequate to ensure conformance with purchase requirements, including verification that specified documentation has been provided by the supplier. The inspection should verify that items were not damaged during shipment. Inspection may include the following methods: Inspections of materials or equipment at the supplier’s plant Receipt inspection of the shipped items

Page 261: Instrumentation and Control

250

Review of objective evidence such as certifications and reports Verification or testing of items prior to or following shipment

Critical or important acceptance parameters and other requirements, such as inspection/test equipment or qualified inspection/test personnel, should be specified in design documentation. In addition, the risks associated with the possibility of obtaining suspect/counterfeit items should be evaluated and if appropriate, measures implemented to identify them.

Nonconformity of Material, Parts, or Components

The following is taken from DOE O 414.1C.

An item is suspect when visual inspection or testing indicates that it may not conform to established government or industry-accepted specifications or national consensus standards, or when its documentation, appearance, performance, material, or other characteristics may have been misrepresented by the supplier or manufacturer. A counterfeit item is one that has been copied or substituted without legal right or authority or whose material, performance, or characteristics have been misrepresented by the supplier or manufacturer. Items that do not conform to established requirements are not normally considered suspect/counterfeit items if nonconformity results from one or more of the following conditions (which must be controlled by site procedures as nonconforming items): Defects resulting from inadequate design or production quality control Damage during shipping, handling, or storage Improper installation Deterioration during service Degradation during removal Failure resulting from aging or misapplication Other controllable causes

Corrective Action

The following is taken from DOE G 414.1-5.

A principal deficiency that led to both the Columbia Space Shuttle disaster and Davis-Besse Nuclear Power Station vessel head corrosion incident was failure to evaluate the causal factors thoroughly and implement effective corrective actions in response to the same and similar identified problem findings that eventually resulted in catastrophic events. Lessons learned in the investigations following both of these events clearly dictate the exigency of maintaining a robust corrective action program that addresses Management/Criterion 3, Quality Improvement, addressed in QAPs

delineated in DOE O 414.1C, Quality Assurance; identifies, documents, evaluates, and trends problems to ensure the causal factors (to

include the root causes) and significance of each problem are understood; develops, tracks, and implements timely corrective actions to resolve the identified

problem findings; verifies completion and reviews the effectiveness of the completed corrective actions

to ensure that they successfully resolve and prevent recurrence of the same and similar problem findings.

Page 262: Instrumentation and Control

251

The thoroughness and effectiveness of a corrective action program to resolve and prevent recurrence of identified problem findings may directly impact the environment, safety and health of the site/organization, DOE workers, and the

public; mission accomplishment and operational performance of DOE sites and

organizations; national security; cost effectiveness of operations; cost avoidance resulting from repeat violations and civil penalties associated with the

failure to effectively correct and prevent problems.

The essence of a successful corrective action program at any level involves a combination of processes, people, and tools for systematic implementation and follow up programs. Principal considerations include: Keep the corrective action process simple. The process should be clear cut and easy

to use, employ user friendly tools, and not require a tremendous amount of manpower or training.

Involve all personnel as stakeholders in the program. Clearly define roles and responsibilities in identifying and reporting problems, and their importance to the effectiveness of the program in enhancing the mission performance and safety of the site/organization.

Provide easy access for reporting information across the site/organization to capture vital information.

Maintain strong management support and emphasis. An active management that demonstrates ownership of the program, encourages employees at all levels in the organization to participate, and is visually involved in directing and setting clear well-defined processes and resources is crucial to the success of the program. The manager responsible for the site/organization implementing the corrective action program should be the overall manager of the program and held accountable for meeting program requirements and suspense dates.

Periodically assess the effectiveness and direction of the program in meeting goals and objectives.

Automate data collection and processing wherever possible. This will enhance easier, more accurate, timely tracking and follow up.

Provide timely feedback to include lessons learned on program actions so members can see results and be encouraged to support the process.

Perform a reliable trending analysis of identified problems and associated causes to identify repeat occurrences, generic issues, and weaknesses at a level before they pose a more significant problem.

Quality Assurance Records

Documents and records are required in order to effectively manage, perform, and assess work. Documents and records should include applicable requirements to indicate that work (including safety) has been properly specified and accomplished. Management should identify any documents and records that must be developed and controlled. Management is responsible for providing the resources necessary to accomplish the document and record requirements.

Page 263: Instrumentation and Control

252

A record contains information that is retained for its expected future value. Records should be sufficient to support technical and regulatory decisions and provide evidence that work was correctly performed. Records may be in a variety of forms (e.g., electronic, written, or printed; microfilm; photographs; radiographs; or optical disks). Typical records include procedures, plans, and manuals; training and qualification results; acceptance test results; technical/ regulatory correspondence; operational records; design basis descriptions, design review results, design revisions, and configuration management data; and quality problem resolutions.

Records should be compiled in a records management system. The system should include provisions for specifying, preparing, reviewing, approving, disposing, and maintaining records. Records retention, protection, preservation, change, traceability, accountability, and retrievability should also be specified. The records management system should have schedules for records retention and disposition consistent with the requirements of DOE O 200.1A, Information Technology Management.

The hardware and software tools used to create and store records should be maintained to ensure that the records can be retrieved. The National Archives and Records Administration, 36 CFR parts 1200–1299, provides a recommended approach for maintenance of records, including electronic records management.

Audits

The following is taken from DOE G 414.1-1A.

An independent assessment may be an audit, surveillance, “for cause” review, or inspection conducted by individuals within the organization or company but independent from the work or process being evaluated, or by individuals from an external organization or company. In general, the purpose of this assessment is to perform the following: Evaluate compliance with standards and requirements Evaluate the performance of work; Measure the quality of the item or service; Examine process effectiveness/adequacy; and Promote improvement.

The organization or staff performing independent assessments should have sufficient authority and freedom from the line organization to carry out its responsibilities. Individuals should be technically qualified and knowledgeable in assessment techniques and in the areas being assessed.

Independent assessments evaluate the performance of work processes with regard to requirements, compliance, and expectations for safely performing the work and achieving the goals of the organization. The focus of independent assessments should be the items and services produced and their associated processes. Thus, management receives an objective view of the assessed activity. Independent assessments are typically performed less frequently than management assessments but go into greater depth.

Page 264: Instrumentation and Control

253

j. Discuss the site organizational roles, responsibilities, and authorities for development of process control systems software (i.e., applications software for Programmable Logic Controllers-(PLCs), Distributed Control Systems-DSCs, etc.).

k. Discuss the site requirements and guidance for the software quality assurance process for development of process control systems software.

l. Discuss the techniques the site uses to verify and validate process control systems software.

Items j–l are performance-based KSAs. The Qualifying Official will evaluate their completion.

33. Instrumentation and control personnel shall demonstrate the ability to apply problem analysis techniques necessary to identify problems, determine potential causes of problems, and identify corrective action.

a. Given event and/or occurrence data, apply problem analysis techniques, identify the problems, and determine how they could have been avoided.

b. Participate in a contractor or Department of Energy (DOE) problem analysis and critique the results.

c. Interpret a fault tree analysis.

Items a–c are performance-based KSAs. The Qualifying Official will evaluate their completion.

34. Instrumentation and control personnel shall demonstrate the ability to perform technical reviews of procedures related to instrumentation and controls.

a. Given one of the listed documents, review it for the following elements: [Note: The standard does not include a list of documents.] Technical adequacy Technical accuracy Proper format Sufficient level of detail Properly defined responsibilities Procedural steps are concise and easily understood Current references are accurate

b. Given an instrumentation and controls surveillance, test, maintenance, or operating procedure, verify procedural adequacy in the following areas: Acceptance criteria are identified and accurate Quality control is addressed Notification requirements are identified Procedural cautions are identified Proper equipment and material are identified Safety concerns are addressed Compliance with technical safety requirements

Page 265: Instrumentation and Control

254

Compliance with the safety analysis report

c. Given an instrumentation and controls surveillance, test, maintenance, or operating procedure, perform a safety evaluation to determine that an unreviewed safety question is not involved.

Items a–c are performance-based KSAs. The Qualifying Official will evaluate their completion.

Page 266: Instrumentation and Control

255

Selected Bibliography and Suggested Reading Code of Federal Regulations

10 CFR 50.49, “Environmental Qualification of Electric Equipment Important to Safety for Nuclear Power Plants.” January 1, 2009.

10 CFR 830, “Subpart A. Quality Assurance.” January 1, 2009. 29 CFR 1910.120, “Hazardous Waste Operations and Emergency Response.” July 1,

2008. 29 CFR 1910.1200, “Hazard Communication.” July 1, 2008. 36 CFR parts 1200–1299, “National Archives and Records Administration.” July 1, 2008. 40 CFR 266, “Standards for the Management of Specific Hazardous Wastes and Specific

Types of Hazardous Waste Management Facilities.” July 1, 2008. All About Circuits

Analog and Digital Signals. Analog Integrated Circuits. Averager and Summer Circuits. Battery Ratings. Current Signal Systems. Digital-Analog Conversion. Programmable Logic Controllers. Protective Relays. Switch Types. Time Delay Relays. Voltage Comparator. Voltage Signal Systems. Volume VI, Experiments, Discrete Semiconductor Circuits. Winding Configurations.

American National Standards Institute ANSI/IEEE C37.90.1, IEEE Standard for Surge Withstand Capability (SWC) Tests for

Relays and Relays Systems Associated with Electric Power Apparatus. 2002. ANSI/IEEE 603-1998, IEEE Standard Criteria for Safety Systems for Nuclear Power

Generating Stations. May 1, 1998. ANSI/EIA-649, National Consensus Standard for Configuration Management. April

2004. ANSI/ISA S18.1, Annunciator Sequences and Specifications. 1992. ANSI/ISA-67.04.01-2006, Setpoints for Nuclear Safety-Related Instrumentation. May 16,

2006. ANSI/ISA-84.00.01-2004, Functional Safety: Safety Instrumented Systems for the

Process Industry. September 2, 2004.

American Society of Mechanical Engineers ASME QME 1, Qualification of Active Mechanical Equipment Used in Nuclear Power

Plants. November 28, 2007. ASME, Continuing Evolution of U.S. Nuclear Quality Assurance Principles, Practices

and Requirements. August 2005.

Page 267: Instrumentation and Control

256

Bigelow, Stephen J. Troubleshooting and Repairing Computer Printers. June 1, 1996.

Boley, Brian L. Overview of Motor Types Tutorial. 1997.

Brain, Marshall. How Microprocessors Work. April 1, 2000.

Breakthrough Technologies Institute’s Fuel Cells 2000 Program.

Cole-Parmer Technical Library. Refractometers.

Computer Hope.com, RAM and ROM.

Concorde Battery. Battery Electrolyte Material Safety Data Sheet. October 6, 2008.

Dataweek, “Battery Selection and Life Expectancy.” March 10, 2004.

Diesel Generator Engine. www.diesel-generator-engine.com

Digital Transmission Systems. Technical Specifications for the Supply of an Uninterruptible Power System Composed of Three-Phase Modules in Parallel Configuration.

Electronics Club. Power Supplies.

Electrostatic Discharge Association. Electrostatic Discharge Technology Roadmap. March 4, 2005.

Encyclopedia Britannica. Motor Generator.

Energy Manager Training. Design Compressed Air System and Components.

Eutech Instruments, Introduction to Conductivity.

Ezine Articles, The Importance of (Well Built) As-Built Drawings.

Fermilab National Accelerator Laboratory. Accelerator Division Operations Department, Glossary of Accelerator Terms.

Freepatentsonline.com Integral Multi-Sensor Radiation Detector Electrohydraulic Control System.

George Washington University, School of Engineering and Applied Sciences. Current Carrying Capacity of Copper Conductors.

GlobalSpec: The Engineering Search Engine Logic Analyzers. Protective Relays and Monitoring Relays. Programmable Power Supplies. Voltage Multipliers.

Page 268: Instrumentation and Control

257

Graf, Rudolf F. Modern Dictionary of Electronics. 1999.

Grand Valley State University Programmable Logic Controllers.

Herman, Stephen L., Walter N. Alerich, Industrial Motor Control. 1998.

Hydraulics & Pneumatics. Other Flow Controls.

ICC Evaluation Service Inc. AC 156, Acceptance Criteria for Seismic Qualification By Shake-Table Testing of Nonstructural Components and Systems. December 2006.

Industrial Equipment Resource. Semiconductors.

Integrated Publishing Aviation, Moisture Separators. Construction, Suction Pressure-Regulating Valves.

Institute of Electrical and Electronics Engineers IEEE Std 141-1993, IEEE Recommended Practice for Electric Power Distribution for

Industrial Plants. December 2, 1993. IEEE Std-2000, Application of the Single-Failure Criterion to Nuclear Power Generating

Station Safety Systems. September 21, 2000. IEEE Std 344-2004, Recommended Practice for Seismic Qualification of Class 1E

Equipment for Nuclear Power Generating Stations. June 2004. IEEE Std 382-1996, Standard for Qualification of Actuators for Power-Operated Valve

Assemblies With Safety-Related Functions for Nuclear Power Plants. 1996.

International Electrical Supplies. Electric Frequency – Hertz.

International Society of Automation. Sensors.

ITT Corporation. Goulds Pumps. Centrifugal Pump Fundamentals: Head.

Lake Shore Cryotronics, Inc. Sensor Characteristics.

Lawrence Berkeley National Laboratory. Standby Power. August 18, 1998.

Lawrence Livermore National Laboratory. Seismic Shock and Vibration Isolation: Part I, Theory, Analysis, and Testing. 1995.

Learncontrol.com. Cascade Control.

Lifetime Reliability Solutions. Process Instruments for Difficult and Corrosive Environments.

Mechanical Engineering. Vibration Monitor. March 1, 2006.

Page 269: Instrumentation and Control

258

National Aeronautics and Space Administration. NASA Tech Briefs, Fiber-Optic Sensors for Measuring Oxygen Dissolved in Water. November 2000.

National Chemical Safety Program, DOE Report 2000-ID-0001, Safety Hazards from Failure of Safety Barriers under the Computer Control. February 8, 2000.

National Conference of Standards Laboratories. NCSL Recommended Practice RP-1, Establishment and Adjustment of Calibration Intervals. January 1996.

National Electrical Code. NEC 310.15, Conductor Ampacity. 2008.

National Electrical Manufacturers’ Association. NEMA, Electrical Transients: Keeping the Enemy Out of Your Facility.

National Fire Protection Association. NFPA 70B, Recommended Practice for Electrical Equipment Maintenance. 2006. National Instruments Developer Zone

PID Control of Continuous Processes. Scan Rates. Signal Conditioning Fundamentals for Computer-Based Data Acquisition Systems.

National Institute of Standards and Technology. NIST/SEMATECH e-Handbook of Statistical Methods, Data Collection. July 18, 2006.

National Nuclear Security Administration. MicroMagazine, Measuring and Removing Dissolved and Colloidal Silica in Ultrapure Water.

North Atlantic Treaty Organization, AECTP 400, Mechanical Environmental Tests. January 2006.

North Carolina Department of Environment and Natural Resources, Division of Pollution Prevention and Environmental Assistance. NCDENR, Energy Efficiency in Industrial HVAC Systems. September 2003.

Omega.com. Current to Pressure Converter.

Patent Storm US Patent 6147529, Voltage Sensing Circuit. November 14, 2000. US Patent 5812620, Proportional Counter. September 22. 1998.

Pathfinder Science, How to Measure Total Dissolved Solids. PC Magazine Encyclopedia

Discreet Logic. Combinatorial Logic.

Photohydrogen, Measuring Hydrogen Gas.

Physical Geography, chapter 8, Introduction to the Hydrosphere.

Page 270: Instrumentation and Control

259

Power-IO, Solid State Relay Terminology.

PowerVolt Inc. How to Determine Power Supply Transformer Ratings. 2001.

Project Management Knowledge Work Packages. Planning Packages.

Research Media and Cybernetics. Voltage Multipliers.

Samson, Electropneumatic Converters for Pneumatic Signals.

School of Champions. Snell’s Law for the Refraction of Light. September 8, 2005.

Sensors Magazine. Level Sensing in Harsh Environments with Guided-Wave Radar. April 2003.

Shultz, George, P. Transformers and Motors. 1997.

Solar Panel Info, How do Solar Panels Work.

State of Washington, Department of Ecology Measuring pH is Lakes and Streams. Measuring Total Suspended Solids and Turbidity in Lakes and Streams.

Texas Instruments. What Is a Current Sensing Circuit and How Is it Used?

Transactions: Flow and Level Measurement.

Transtronics Sealed Lead Acid Battery Applications. Understanding Dead Band.

U.S. Army Corps of Engineers. EM 1110-2-3006, Hydroelectric Power Plants Electrical Design. June 30, 1994.

U.S. Department of Energy Directives (Guides, Manuals, Orders, and Policies) DOE Guide 413.3-5, U.S. Department of Energy Performance Baseline Guide.

September 12, 2008. DOE Guide 414.1-1A, Management and Independent Assessments Guide for Use With 10

CFR, Part 830, Subpart A, and DOE O 414.1C, Quality Assurance; DOE M 450.4-1, Integrated Safety Management System Manual; and DOE O 226.1A, Implementation of Department of Energy Oversight Policy. September 27, 2007.

DOE Guide 414.1-2A, Quality Assurance Management System Guide for Use with 10 CFR 830 Subpart A, Quality Assurance Requirements, and DOE O 414.1C, Quality Assurance. June 17, 2005.

DOE Guide 414.1-5, Corrective Action Program Guide. March 2, 2006.

Page 271: Instrumentation and Control

260

DOE Guide 420.1-2, Guide for the Mitigation of Natural Phenomena Hazards for DOE Nuclear Facilities and NonNuclear Facilities. March 28, 2000.

DOE Guide 430.1-1, chapter 5, Cost Codes and the Work Breakdown Structure. March 28, 1997.

DOE Guide 433.1-1, Nuclear Facility Maintenance Management Program Guide for Use with DOE O 433.1. September 5, 2001.

DOE Manual 413.3-1, Project Management for the Acquisition of Capital Assets. March 28, 2003.

DOE Order 200.1A, Information Technology Management. December 23, 2008. DOE Order 413.3A, Program and Project Management for the Acquisition of Capital

Assets. November 17, 2008. DOE Order 414.1C, Quality Assurance. July 7, 2005. DOE Order 430.1B, Real Property Asset Management. February 8. 2008.

U.S. Department of Energy Handbooks and Standards DOE-HDBK-1011/1 through 4-92, DOE Fundamentals Handbook: Electrical Science.

Vol. 1–4. June 1992. DOE-HDBK-1012-92, DOE Fundamentals Handbook: Thermodynamics, Heat Transfer,

and Fluid Flow, volumes 1-3. June 1992. DOE-HDBK-1013-92, DOE Fundamentals Handbook: Instrumentation and Control,

volumes 1 and 2. June 1992. DOE-HDBK-1015/2-93, DOE Fundamentals Handbook: Chemistry, volume 2. January

1993. DOE-HDBK-1016-93, DOE Fundamentals Handbook: Engineering Symbology, Prints,

and Drawings, volumes 1 and 2. January 1993. DOE-HDBK-1018/2-92, DOE Fundamentals Handbook: Mechanical Science, volume 2.

January 1993. DOE-HDBK-1084-95, DOE Handbook: Primer on Lead-Acid Storage Batteries.

September 1995. DOE-HDBK-1092-2004, DOE Handbook: Electrical Safety. December 2004. DOE-HDBK-1104-2004, DOE Handbook: Process Safety Management for Highly

Hazardous Chemicals. August 2004. DOE-STD-1020-2002, DOE Standard: Natural Phenomena Hazards Design and

Evaluation Criteria for Department Of Energy Facilities. January 2002. DOE-STD-1023-94, DOE Standard: Natural Phenomena Hazards Characterization

Criteria. March 1994. DOE-STD-1039-93, DOE Standard: Guide to Good Practices for Control of Equipment

and System Status. March 1993. DOE-STD-1054-93, DOE Standard: Guideline to Good Practices for Control and

Calibration of Measuring and Test Equipment (M&TE) at DOE Nuclear Facilities. March 1993. (Archived)

DOE-STD-1072-2003, DOE Standard: Configuration Management. October 2003.

U.S. Department of Defense, MIL STD 45662A, Military Standard: Calibration Systems Requirements. August 1, 1988.

Other DOE Documents

Page 272: Instrumentation and Control

261

DOE/EH-0535, Handbook for Occupational Health and Safety During Hazardous Waste Activities, June 1996.

DOE Accounting Handbook. April 27, 2007. DOE G-10 CFR 835/E1, Instrumentation Calibration for Portable Survey Instruments.

November 1994. DOE Quality Assurance Exchange, volume 4, issue 1, Digital Instrumentation and

Control Systems. April 2008.

U.S. Environmental Protection Agency Design for the Environment, Printed Wiring Board Industry: Part 2-1 Overview.

November 13, 2008. Water and Waste Water Security Product Guide, Chemical Sensor - Chlorine

Measurement System. March 29, 2007.

US Motors. Terminology Pertaining to Electric Machinery. 2005.

U.S. Nuclear Regulatory Commission

NUREG/CR-5550, Passive Nondestructive Assay of Nuclear Materials. March 1991. NRC Regulatory Guide 1.180, Guidelines for Evaluating Electromagnetic and Radio-

Frequency Interference in Safety-Related Instrumentation and Control Systems. October 2003.

University of Michigan. Engineering, PID Tuning Classical.

University of Washington, Baneyx, chapter 2, Control Loop Hardware. faculty.washington.edu/baneyx/436/Orifice.pdf

Waste and Wastewater, Distribution Control System Primer.

Water Action Volunteers, The Basics About Turbidit.

Weisstein, Eric W. Eric Weisstein’s World of Physics Electromagnetic Field Electromagnetic Force

Wilkerson Instrument Co. Signal Isolation.

Wilkes University, Total Dissolved Solids.

Wilson Power Solutions Inc. What a Transformer Tap Changer is and What it Does.

Wright State University. Intelligent Sensor Systems.

Yamatake.com. Field P/I Converter.

Page 273: Instrumentation and Control

Instrumentat ion and Control

Qualif icat ion Standard Reference Guide

SEPTEMBER 2009


Recommended